Mitsubishi Electronics fre700
Table of Contents 45 sections FR-E700INSTRUCTION MANUAL (BASIC) · This section is specifically about safety matters · 1 PRODUCT CHECKING AND PARTS IDENTIFICATION · 2 INSTALLATION AND WIRING · … ShowHide
FR-E700INSTRUCTION MANUAL (BASIC)p.1This section is specifically about safety mattersp.21 PRODUCT CHECKING AND PARTS IDENTIFICATIONp.42 INSTALLATION AND WIRINGp.52.1 Peripheral devicesp.62.2 Installation of the inverter and instructionsp.72.3 Wiringp.82.3.1 Terminal connection diagramp.82.3.2 Terminal specificationsp.92.3.3 Terminal arrangement of the main circuit terminal, power supply and the motor wiringp.102.3.4 Cables and wiring lengthp.112.3.5 Wiring of control circuitp.132.3.6 Connecting the 24V external power supplyp.152.3.7 Safety stop functionp.162.4 Connection of a dedicated external brake resistor (MRS type, MYS type, FR-ABR)p.182.5 Wiring for CC-Link communicationp.192.5.1 System configuration examplep.192.5.2 Connection of several invertersp.202.5.3 Connection cable and plugp.212.5.4 Connection of CC-Link dedicated cablep.222.5.5 Unit replacement while onlinep.232.6 CC-Link function settingp.242.6.1 Station number setting (Pr. 542)p.242.6.2 Baud rate setting (Pr. 543)p.243 PRECAUTIONS FOR USE OF THE INVERTERp.254 FAILSAFE OF THE SYSTEM WHICH USES THE INVERTERp.275 PARAMETER LISTp.286 TROUBLESHOOTINGp.326.1 Reset method of protective functionp.326.2 List of fault or alarm indicationsp.336.3 Check first when you have a troublep.367 PRECAUTIONS FOR MAINTENANCE AND INSPECTIONp.377.1 Inspection itemsp.377.2 Replacement of partsp.388 SPECIFICATIONSp.398.1 Ratingp.398.2 Common specificationsp.418.3 Outline dimension drawingsp.42Appendix 1 Instructions for Compliance with the EU Directivesp.43Appendix 2 Instructions for UL and cULp.46REVISIONSp.49Instruction Manual Supplement(BCN-C22005-659)p.501 For the terminating resistor selection switchp.502 Additional notes for instructions for UL and cULp.51International FA Centerp.52
Page 1 of the Mitsubishi Electronics fre700 user manual — PRODUCT CHECKING AND PARTS IDENTIFICATION............... 1
Page 1 · click to enlarge
Page 1

INVERTER

FR-E700 INSTRUCTION MANUAL (BASIC)

CC-Link communication function

FR-E720-0.1KNC to 15KNC FR-E740-0.4KNC to 15KNC FR-E720S-0.1KNC to 2.2KNC

Thank you for choosing this Mitsubishi Inverter. This Instruction Manual (Basic) provides handling information and precautions for use of the equipment. Please forward this Instruction Manual (Basic) to the end user.

PRODUCT CHECKING AND PARTS IDENTIFICATION 1

INSTALLATION AND WIRING .................................................... 2

PRECAUTIONS FOR USE OF THE INVERTER.......................... 22

FAILSAFE OF THE SYSTEM WHICH USES THE INVERTER .... 24

PARAMETER LIST.................................................................... 25

TROUBLESHOOTING ............................................................... 29

PRECAUTIONS FOR MAINTENANCE AND INSPECTION......... 34

SPECIFICATIONS..................................................................... 36

To obtain the Instruction Manual (Applied) and the Safety stop function instruction manual

Contact where you purchased the inverter, your Mitsubishi sales representative, or the nearest Mitsubishi FA Center for the following manuals: y Instruction Manual (Applied) [IB(NA)-0600402ENG] y Safety stop function instruction manual [BCN-A211508-004] These manuals are required if you are going to utilize functions and performance. The PDF version of this manual is also available for download at "MELFANS Web," the Mitsubishi Electric FA network service on the world wide web (URL: http://www.MitsubishiElectric.co.jp/melfansweb)

Page 2 of the Mitsubishi Electronics fre700 user manual — A-1
Page 2 · click to enlarge
Page 2

This Instruction Manual (Basic) provides handling information and precautions for use of the equipment. Please forward this Instruction Manual (Basic) to the end user.

2. Fire Prevention

This section is specifically about safety matters

Do not attempt to install, operate, maintain or inspect the inverter until you have read through the Instruction Manual (Basic) and appended documents carefully and can use the equipment correctly. Do not use this product until you have a full knowledge of the equipment, safety information and instructions. In this Instruction Manual (Basic), the safety instruction levels are classified into "WARNING" and "CAUTION".

CAUTION

z Inverter must be installed on a nonflammable wall without

holes (so that nobody touches the inverter heatsink on the rear side, etc.). Mounting it to or near flammable material can cause a fire. z If the inverter has become faulty, the inverter power must

be switched OFF. A continuous flow of large current could cause a fire. z When using a brake resistor, a sequence that will turn OFF

power when a fault signal is output must be configured. Otherwise the brake resistor may overheat due to damage of the brake transistor and possibly cause a fire. z Do not connect a resistor directly to the DC terminals P/+

WARNING

Incorrect handling may cause hazardous conditions, resulting in death or severe injury.

CAUTION

Incorrect handling may cause hazardous conditions, resulting in medium or slight injury, or may cause only material damage.

and N/-. Doing so could cause a fire.

3.Injury Prevention

CAUTION

z The voltage applied to each terminal must be the ones

The level may even lead to a serious consequence according to conditions. Both instruction levels must be followed because these are important to personal safety.

CAUTION

specified in the Instruction Manual. Otherwise burst, damage, etc. may occur. z The cables must be connected to the correct terminals.

Otherwise burst, damage, etc. may occur. z Polarity must be correct. Otherwise burst, damage, etc.

1. Electric Shock Prevention

WARNING

may occur. z While power is ON or for some time after power-OFF, do

z While power is ON or when the inverter is running, do not

not touch the inverter as they will be extremely hot. Doing so can cause burns.

open the front cover. Otherwise you may get an electric shock. z Do not run the inverter with the front cover or wiring cover

4. Additional Instructions

removed. Otherwise you may access the exposed high- voltage terminals or the charging part of the circuitry and get an electric shock. z Even if power is OFF, do not remove the front cover

Also the following points must be noted to prevent an

accidental failure, injury, electric shock, etc. (1) Transportation and Mounting

CAUTION z The product must be transported in correct method that corresponds to the weight. Failure to do so may lead to injuries. z Do not stack the boxes containing inverters higher than the number recommended. z The product must be installed to the position where withstands the weight of the product according to the information in the Instruction Manual. z Do not install or operate the inverter if it is damaged or has parts missing. z When carrying the inverter, do not hold it by the front cover or setting dial; it may fall off or fail. z Do not stand or rest heavy objects on the product. z The inverter mounting orientation must be correct. z Foreign conductive objects must be prevented from entering the inverter. That includes screws and metal fragments or other flammable substance such as oil. z As the inverter is a precision instrument, do not drop or subject it to impact. z The inverter must be used under the following environment. Otherwise the inverter may be damaged. EnvironmentSurrounding air temperature-10°C to +50°C (non-freezing) Ambient humidity90%RH or less (non-condensing) Storage temperature-20°C to +65°C *1 AtmosphereIndoors (free from corrosive gas, flammable gas, oil mist, dust and dirt) Altitude/ vibrationMaximum 1,000m above sea level. 5.9m/s2 or less at 10 to 55Hz (directions of X, Y, Z axes) ∗1 Temperature applicable for a short time, e.g. in transit.

except for wiring or periodic inspection. You may accidentally touch the charged inverter circuits and get an electric shock. z Before wiring or inspection, power must be switched OFF.

To confirm that, LED indication of the operation panel must be checked. (It must be OFF.) Any person who is involved in wiring or inspection shall wait for at least 10 minutes after the power supply has been switched OFF and check that there are no residual voltage using a tester or the like. The capacitor is charged with high voltage for some time after power OFF, and it is dangerous. z This inverter must be earthed (grounded). Earthing

(grounding) must conform to the requirements of national and local safety regulations and electrical code (NEC section 250, IEC 536 class 1 and other applicable standards). A neutral-point earthed (grounded) power supply for 400V class inverter in compliance with EN standard must be used. z Any person who is involved in wiring or inspection of this

equipment shall be fully competent to do the work. z The inverter must be installed before wiring. Otherwise

you may get an electric shock or be injured. z Setting dial and key operations must be performed with

dry hands to prevent an electric shock. z Do not subject the cables to scratches, excessive stress,

heavy loads or pinching. Otherwise you may get an electric shock. z Do not change the cooling fan while power is ON. It is

cables with wet hands. Otherwise you may get an electric shock. z When measuring the main circuit capacitor capacity, the

DC voltage is applied to the motor for 1s at powering OFF. Never touch the motor terminal, etc. right after powering OFF to prevent an electric shock.

A-1

Page 3 of the Mitsubishi Electronics fre700 user manual — A-2
Page 3 · click to enlarge
Page 3

(2) Wiring

(5) Emergency stop

CAUTION

Mitsubishi Electronics fre700 — (2) Wiring diagram (page 3)
Fig. 1 · (2) Wiring

z Do not install a power factor correction capacitor or surge

zA safety backup such as an emergency brake must be

suppressor/capacitor type filter on the inverter output side. These devices on the inverter output side may be overheated or burn out. z The connection orientation of the output cables U, V, W to

provided to prevent hazardous condition to the machine and

zWhen the breaker on the inverter input side trips, the

wiring must be checked for fault (short circuit), and internal

the motor affects the rotation direction of the motor.

parts of the inverter for a damage, etc. The cause of the trip

(3) Trial run

must be identified and removed before turning ON the

CAUTION

z Before starting operation, each parameter must be

confirmed and adjusted. A failure to do so may cause some machines to make unexpected motions.

corrective action must be taken, and the inverter must be

(4) Usage

WARNING

z Any person must stay away from the equipment when the

zDo not carry out a megger (insulation resistance) test on

retry function is set as it will restart suddenly after trip.

the control circuit of the inverter. It will cause a failure.

z Since pressing key may not stop output depending

on the function setting status, separate circuit and switch that make an emergency stop (power OFF, mechanical brake operation for emergency stop, etc.) must be provided. z OFF status of the start signal must be confirmed before

z The inverter must be treated as industrial waste.

resetting the inverter fault. Resetting inverter alarm with the start signal ON restarts the motor suddenly. z The inverter must be used for three-phase induction motors.

Many of the diagrams and drawings in this Instruction

Connection of any other electrical equipment to the inverter output may damage the equipment. z Do not modify the equipment. z Do not perform parts removal which is not instructed in this

Manual (Basic) show the inverter without a cover or partially

open for explanation. Never operate the inverter in this

manner. The cover must be always reinstalled and the

manual. Doing so may lead to fault or damage of the product.

CAUTION

Harmonic suppression guideline (when inverters are used in Japan)

z The electronic thermal relay function does not guarantee

protection of the motor from overheating. It is recommended to install both an external thermal and PTC thermistor for overheat protection. z Do not use a magnetic contactor on the inverter input for

special high voltage". (For further details, refer to the

frequent starting/stopping of the inverter. Otherwise the life of the inverter decreases. z The effect of electromagnetic interference must be

reduced by using a noise filter or by other means. Otherwise nearby electronic equipment may be affected. z Appropriate measures must be taken to suppress

harmonics. Otherwise power supply harmonics from the inverter may heat/damage the power factor correction capacitor and generator. z When driving a 400V class motor by the inverter, the

motor must be an insulation-enhanced motor or measures must be taken to suppress surge voltage. Surge voltage attributable to the wiring constants may occur at the motor terminals, deteriorating the insulation of the motor. z When parameter clear or all parameter clear is performed,

the required parameters must be set again before starting operations because all parameters return to the initial value. z The inverter can be easily set for high-speed operation.

Before changing its setting, the performances of the motor and machine must be fully examined. z Stop status cannot be hold by the inverter's brake

function. In addition to the inverter’s brake function, a holding device must be installed to ensure safety. z Before running an inverter which had been stored for a long

period, inspection and test operation must be performed. z For prevention of damage due to static electricity, nearby

metal must be touched before touching this product to eliminate static electricity from your body.

A-2

Page 4 of the Mitsubishi Electronics fre700 user manual — 1 PRODUCT CHECKING AND PARTS IDENTIFICATION
Page 4 · click to enlarge
Page 4

1 PRODUCT CHECKING AND PARTS IDENTIFICATION

Unpack the inverter and check the capacity plate on the front cover and the rating plate on the inverter side face to ensure that

the product agrees with your order and the inverter is intact. zInverter model

Mitsubishi Electronics fre700 — 1 PRODUCT CHECKING AND PARTS IDENTIFICATION diagram (page 4)
Fig. 2

Represents the inverter capacity [kW] E720 Three-phase 200V class

CC-Link communication connector (2-port type) (Refer to page 19)

Switch for manufacturer setting (SW2) Do not change the initial setting (OFF).

Standard control circuit terminal block (Refer to page 6)

∗Location of the capacity plate and the rating plate differs

Refer to the outline dimension drawing. ( Refer to the

  • Accessory · P-clip (for M4 screw) Use this to ground (earth) the CC-Link dedicated cable. (Refer to page 19)

· Fan cover fixing screws (M3 × 35mm) These screws are necessary for compliance with the EU Directive (Refer to page 41)

CapacityQuantity FR-E720-1.5KNC to 3.7KNC, FR-E740-1.5KNC to 3.7KNC, FR-E720S-0.75KNC to 2.2KNC 1 FR-E720-5.5KNC to 15KNC, FR-E740-5.5KNC to 15KNC 2
Page 5 of the Mitsubishi Electronics fre700 user manual — PR
Page 5 · click to enlarge
Page 5

Installation of the inverter and instructions

2 INSTALLATION AND WIRING

AC power supply Use within the permissible power supply specifications of the inverter. To ensure safety, use a moulded case circuit breaker, earth leakage circuit breaker or magnetic contactor to switch power ON/OFF.

Load the "QJ61BT11N", "QJ61BT11", "AJ61QBT11", "A1SJ61QBT11", "AJ61BT11" or "A1SJ61BT11" CC-Link system master/local module on the main or extension base unit having the programmable controller CPU used as the master station.

(Refer to page 36)

Moulded case circuit breaker (MCCB) or earth leakage circuit breaker (ELB), fuse The breaker must be selected carefully since an in-rush current flows in the inverter at power ON.

Master station (for example, QJ61BT11N)

(Refer to page 3)

Magnetic contactor (MC) Install the magnetic contactor to ensure safety. Do not use this magnetic contactor to start and stop the inverter. Doing so will cause the inverter life to be shorten.

Approved safety relay module Required for compliance with safety standard.

(Refer to page 3)

Reactor (FR-HAL, FR-HEL option) Reactors (option) must be used when power harmonics measures are taken, the power factor is to be improved or the inverter is installed near a large power supply system (500kVA or more). The inverter may be damaged if you do not use reactors. Select the reactor according to the model. Remove the jumpers across terminals P/+ and P1 to connect the DC reactor.

S1 S2 PC

Brake resistor (FR-ABR, MRS type, MYS type) Braking capability can be improved. (0.4K or higher) Always install a thermal relay when using a brake resistor whose capacity is 11K or higher. (Refer to page 15)

AC reactor (FR-HAL) DC reactor (FR-HEL) *

P/+ PR

EMC filter (ferrite core) * (FR-BSF01, FR-BLF)

P1 P/+

R/L1 S/L2 T/L3

EMC filter (ferrite core) (FR-BSF01, FR-BLF) Install an EMC filter (ferrite core) to reduce the electromagnetic noise generated from the inverter. Effective in the range from about 1MHz to 10MHz. A wire should be wound four turns at a maximum.

Install an EMC filter (ferrite core) to reduce the electromagnetic noise generated from the inverter. Effective in the range from about 1MHz to 10MHz. When more wires are passed through, a more effective result can be obtained. A wire should be wound four turns or more.

EMC filter (capacitor) * (FR-BIF)

N/- P/+ U W

Reduces the radio noise.

* Filterpack (FR-BFP2), which contains DC reactor and EMC filter in one package, is also available.

The regenerative braking capability of the inverter can be exhibited fully. Install this as required.

P/+ P/+

PR

Devices connected to the output Do not install a power factor correction capacitor, surge suppressor or capacitor type filter on the output side of the inverter. When installing a moulded case circuit breaker on the output side of the inverter, contact each manufacturer for selection of the moulded case circuit breaker.

Earth (Ground) To prevent an electric shock, always earth (ground) the motor and inverter. For reduction of induction noise from the power line of the inverter, it is recommended to wire the earth (ground) cable by returning it to the earth (ground) terminal of the inverter.

PR

Resistor unit (FR-BR) Discharging resistor (GZG, GRZG)

possible within the permissible range. This must be noted especially when the inverter is installed in an enclosure. (Refer to page 4) y Wrong wiring might lead to damage of the inverter. The control signal lines must be kept fully away from the main circuit

to protect them from noise. (Refer to page 5) y Do not install a power factor correction capacitor, surge suppressor or capacitor type filter on the inverter output side.

This will cause the inverter to trip or the capacitor and surge suppressor to be damaged. If any of the above devices are connected, immediately remove them. y Electromagnetic wave interference

The input/output (main circuit) of the inverter includes high frequency components, which may interfere with the communication devices (such as AM radios) used near the inverter. In this case, install options among the capacitor type EMC filter FR-BIF (for use in the input side only), the ferrite core type EMC filter FR-BSF01/FR-BLF, Filterpack, and EMC filter to minimize the interference. ( Refer to the Instruction Manual (Applied)). y Refer to the instruction manual of each option and peripheral devices for details of peripheral devices.

Show 9 more labels / short text on this page
Programmable controller · Terminating resistor · CC-Link dedicated cable · Terminating resistor · Inverter (FR-E700-NC) · Earth (Ground) · Motor · Brake unit (FR-BU2) · Earth (Ground)
Page 6 of the Mitsubishi Electronics fre700 user manual — MCCB INV
Page 6 · click to enlarge
Page 6

Peripheral devices

2.1 Peripheral devices

Check the inverter model of the inverter you purchased. Appropriate peripheral devices must be selected according to the capacity.

Refer to the following list and prepare appropriate peripheral devices:

Inverter ModelMotor Output (kW)Moulded Case Circuit Breaker (MCCB) ∗1 or Earth Leakage Circuit Breaker (ELB) ∗2 (NF, NV type)Magnetic Contactor (MC) ∗3Reactor Reactor connectionReactor connectionFR-HALFR-HEL withoutwithwithoutwith Three-Phase 200VFR-E720-0.1KNC0.15A5AS-N10S-N100.4K ∗40.4K ∗4 FR-E720-0.2KNC0.25A5AS-N10S-N100.4K ∗40.4K ∗4 FR-E720-0.4KNC0.45A5AS-N10S-N100.4K0.4K FR-E720-0.75KNC0.7510A10AS-N10S-N100.75K0.75K FR-E720-1.5KNC1.515A15AS-N10S-N101.5K1.5K FR-E720-2.2KNC2.220A15AS-N10S-N102.2K2.2K FR-E720-3.7KNC3.730A30AS-N20, S-N21S-N103.7K3.7K FR-E720-5.5KNC5.550A40AS-N25S-N20, S-N215.5K5.5K FR-E720-7.5KNC7.560A50AS-N25S-N257.5K7.5K FR-E720-11KNC1175A75AS-N35S-N3511K11K FR-E720-15KNC15125A100AS-N50S-N5015K15K Three-Phase 400VFR-E740-0.4KNC0.45A5AS-N10S-N10H0.4KH0.4K FR-E740-0.75KNC0.755A5AS-N10S-N10H0.75KH0.75K FR-E740-1.5KNC1.510A10AS-N10S-N10H1.5KH1.5K FR-E740-2.2KNC2.215A10AS-N10S-N10H2.2KH2.2K FR-E740-3.7KNC3.720A15AS-N10S-N10H3.7KH3.7K FR-E740-5.5KNC5.530A20AS-N20, S-N21S-N11, S-N12H5.5KH5.5K FR-E740-7.5KNC7.530A30AS-N20, S-N21S-N20, S-N21H7.5KH7.5K FR-E740-11KNC1150A40AS-N20, S-N21S-N20, S-N21H11KH11K FR-E740-15KNC1560A50AS-N25S-N20, S-N21H15KH15K Single-Phase 200VFR-E720S-0.1KNC0.15A5AS-N10S-N100.4K ∗40.4K ∗4 FR-E720S-0.2KNC0.25A5AS-N10S-N100.4K ∗40.4K ∗4 FR-E720S-0.4KNC0.410A10AS-N10S-N100.75K ∗40.75K ∗4 FR-E720S-0.75KNC0.7515A10AS-N10S-N101.5K ∗41.5K ∗4 FR-E720S-1.5KNC1.520A20AS-N10S-N102.2K ∗42.2K ∗4 FR-E720S-2.2KNC2.240A30AS-N20, S-N21S-N103.7K ∗43.7K ∗4

∗1 ySelect an MCCB according to the power supply capacity.

MCCB INV

IM

yInstall one MCCB per inverter.

MCCB INV

IM

∗2 For the use in the United States or Canada, select a UL and cUL certified fuse with Class T fuse equivalent cut-off

speed or faster with the appropriate rating for branch circuit protection. Alternatively, select a UL489 molded case circuit breaker (MCCB).

∗3 Magnetic contactor is selected based on the AC-1 class. The electrical durability of magnetic contactor is 500,000 times. When the magnetic contactor is

used for emergency stop during motor driving, the electrical durability is 25 times.

When using the MC for emergency stop during motor driving or using on the motor side during commercial-power supply operation, select the MC with class

AC-3 rated current for the motor rated current.

∗4 The power factor may be slightly lower.

y When the inverter capacity is larger than the motor capacity, select an MCCB and a magnetic contactor according to

the inverter model and cable and reactor according to the motor output.

y When the breaker on the inverter input side trips, check for the wiring fault (short circuit), damage to internal parts of

the inverter, etc. Identify the cause of the trip, then remove the cause and power on the breaker.

Page 7 of the Mitsubishi Electronics fre700 user manual — (2) Environment
Page 7 · click to enlarge
Page 7

Installation of the inverter and instructions

2.2 Installation of the inverter and instructions

(1) Installation of the inverter

Remove the front cover and wiring cover to fix the inverter to the surface. (Remove the covers in the directions of the arrows.)

Mitsubishi Electronics fre700 — (1) Installation of the inverter diagram (page 7)
Fig. 3 · (1) Installation of the inverter

FR-E720-1.5KNC or higher FR-E740-0.4KNC or higher FR-E720S-0.75KNC or higher

y When encasing multiple inverters, install them in parallel as a cooling

y For heat dissipation and maintenance, take at least the clearances

shown in the table below from the inverter to the other devices and to

1cm or more 1cm or more 1cm or more ∗1, ∗2 ∗1 ∗1, ∗2

∗1 Take 5cm or more clearances for 5.5K or higher.

∗2 When using the inverters at the surrounding air temperature of 40°C or less, the inverters can be installed without any clearance between

(2) Environment

Before installation, check that the environment meets the specifications on page 38.

y Install the inverter on a strong surface securely and vertically with bolts.

y Leave enough clearances and take cooling measures.

y Avoid places where the inverter is subjected to direct sunlight, high temperature and high humidity.

y Install the inverter on a non-flammable wall surface.

Enclosure surface mounting

Page 8 of the Mitsubishi Electronics fre700 user manual — RD L.ERR
Page 8 · click to enlarge
Page 8

Wiring

2.3 Wiring

2.3.1 Terminal connection diagram

*1 DC reactor (FR-HEL) When connecting a DC reactor, remove the jumper across P1 and P/+. Control circuit terminal Main circuit terminal Sink logic

*2 A brake transistor is not built-in to the 0.1K and 0.2K.

MCCB MC

*3 Brake resistor (FR-ABR, MRS, MYS type) Install a thermal relay to prevent an overheat and burnout of the brake resistor. (The brake resistor cannot be connected to the 0.1K and 0.2K.)

Single-phase AC power supply

R/L1 S/L2

R

PR N/-

MCCB MC

P1 P/+

Three-phase AC power supply

R/L1

U V W

S/L2 T/L3

IM

Main circuit

Control circuit

24V external power supply

Use Pr.190 RX2 (Y0 terminal) function selection to change the function assigned to the terminal.

SD

Y0

Open collector output Y0 (While the inverter is running)

SE Safety stop signal

Open collector output common Sink/source common

S1

Safety stop input (Channel 1)

Safety stop input (Channel 2)

S2

Safety stop input common

PC

SD L.RUN

LED (operation status indicator)

LEDs turn ON/OFF to indicate the operation status.

RD L.ERR

RUN

y To prevent a malfunction caused by noise, separate the signal cables more than 10cm from the power cables. Also

separate the main circuit wire of the input side and the output side.

y After wiring, wire offcuts must not be left in the inverter.

Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean. When drilling mounting holes

in an enclosure etc., take care not to allow chips and other foreign matter to enter the inverter.

y The output of the single-phase power input specification is three-phase 200V.

Show 20 more labels / short text on this page
Single-phase power input · Brake unit · (Option) · *1 · Earth (Ground) · *3 · Jumper · *2 · Motor · Earth (Ground) · Earth (Ground) · Open collector output · 24V power supply · +24 · Common terminal · Shorting · wire · USB connector · CC-Link communication · connector (2-port type)
Page 9 of the Mitsubishi Electronics fre700 user manual — Wiring
Page 9 · click to enlarge
Page 9

Wiring

2.3.2 Terminal specifications

TypeTerminal SymbolTerminal NameDescription Main circuitR/L1, S/L2, T/L3 *AC power inputConnect to the commercial power supply. * When using single-phase power input, terminals are R/L1 and S/L2. U, V, WInverter outputConnect a three-phase squirrel-cage motor. P/+, PRBrake resistor connectionConnect a brake resistor (FR-ABR, MRS type, MYS type) across terminals P/+ and PR. (The brake resistor cannot be connected to the 0.1K or 0.2K.) P/+, N/-Brake unit connectionConnect the brake unit (FR-BU2). P/+, P1DC reactor connectionRemove the jumper across terminals P/+ and P1 and connect a DC reactor. Earth (Ground)For earthing (grounding) the inverter chassis. Must be earthed (grounded). Control circuit24V external power supply+2424V external power supplyEven when the main circuit power supply is OFF, CC-Link communication continues with the input from the 24V external power supply.Input voltage 23.5 to 26.5VDC Input current 0.7A or less SD24V external power supply common terminalCommon terminal for the terminal +24 Safety stop functionS1Safety stop input (Channel 1)Terminal S1/S2 are safety stop signals for use with in conjunction with an approved external safety unit. Both terminal S1/S2 must be used in dual channel form. Inverter output is shutoff depending on shorting/opening between S1 and PC, S2 and PC. In the initial status, terminal S1 and S2 are shorted with terminal PC by shorting wire. Remove the shorting wire and connect the safety relay module when using the safety stop function.Input resistance 4.7kΩ Voltage when contacts are open 21 to 26VDC When contacts are shortcircuited 4 to 6mADC S2Safety stop input (Channel 2) PCSafety stop input terminal commonCommon terminal for safety stop input terminals S1 and S2. Open collectorY0Open collector output Y0 (Inverter running)Switched low when the inverter output frequency is equal to or higher than the starting frequency (initial value 0.5Hz). Switched high during stop or DC injection brake operation. (Low indicates that the open collector output transistor is ON (conducts). High indicates that the transistor is OFF (does not conduct).) Use Pr.190 RX2 (terminal Y0) function selection to change the function assigned to the terminal.Permissible load 24VDC (maximum 27VDC) 0.1A (a voltage drop is 3.4V maximum when the signal is ON) SEOpen collector output commonCommon terminal of terminal Y0. CC-LinkCONA CONBCC-Link communication connectorPin arrangement 543 21 CONA Pin number 5 4 3 2 1 Signal name SLD NC DG DB DA CONB One-touch connector for CC-Link communication Model name Manufacturer A6CON-L5P Mitsubishi Electric Corporation 35505-6000-B0M GF Sumitomo 3M Limited
Pin number54321 Signal nameSLDNCDGDBDA
Model nameManufacturer A6CON-L5PMitsubishi Electric Corporation 35505-6000-B0M GFSumitomo 3M Limited
Page 10 of the Mitsubishi Electronics fre700 user manual — 2.3.3 Terminal arrangement of the main circuit terminal, power supply and the motor wiring
Page 10 · click to enlarge
Page 10
Mitsubishi Electronics fre700 — 2.3.3 Terminal arrangement of the main circuit terminal, power supply and the motor wiring diagram (page 10)
Fig. 4 · 2.3.3 Terminal arrangement of the main circuit termi…
2.3.3 Terminal arran Three-phase 200V classgement of the main circuit terminal, power supply and the motor wiring FR-E720-0.1KNC to 0.75KNC N/- R/L1 S/L2 T/L3 Power supplyJumper P/+ PR IM MotorFR-E720-1.5KNC to 3.7KNC Jumper N/- P/+ R/L1 S/L2 T/L3 PR IM Power supply Motor FR-E720-5.5KNC, 7.5KNC R/L1 S/L2 T/L3 N/- P/+ PR Jumper IM Power supply MotorFR-E720-11KNC, 15KNC R/L1 S/L2 T/L3 N/- P/+ PR Jumper IM Power supply Motor Three-phase 400V class FR-E740-0.4KNC to 3.7KNC Jumper N/- P/+ R/L1 S/L2 PR Power sT/L3 IM upply MotorFR-E740-5.5KNC, 7.5KNC Jumper R/L1 S/L2T/L3 IM upply Motor N/- P/+ PR Power s FR-E740-11KNC, 15KNC N/- P/+ PR R/L1 Jumper Power supplyS/L2 T/L3 IM Motor Single-phase 200V class FR-E720S-0.1KNC to 0.4KNC N/- R/L1 S/L2 Power supplyJumper P/+ PR IM MotorFR-E720S-0.75KNC to 2.2KNC N/- P/+ Jumper R/L1 S/L2 PR IM Power supply Motor

the power cable to the U, V, W of the inverter. Doing so will damage the inverter. y Connect the motor to U, V, and W. Turning ON the forward rotation switch (signal) at this time rotates the motor

Page 11 of the Mitsubishi Electronics fre700 user manual — Single-phase 200V class (when input power supply is 220V)
Page 11 · click to enlarge
Page 11

Wiring

2.3.4 Cables and wiring length

(1) Cable size and other specifications of the main circuit terminals and the earthing terminal

Select the recommended cable size to ensure that a voltage drop will be 2% or less.

If the wiring distance is long between the inverter and motor, a main circuit cable voltage drop will cause the motor torque to

decrease especially at the output of a low frequency.

The following table indicates a selection example for the wiring length of 20m. Three-phase 200V class (when input power supply is 220V)

Mitsubishi Electronics fre700 — Wiring diagram (page 11)
Fig. 5 · Wiring
Applicable Inverter ModelTerminal Screw Size ∗4Tightening Torque N·mCrimping TerminalCable Size HIV Cables, etc. (mm2) ∗1AWG ∗2PVC Cables, etc. (mm2) ∗3 R/L1 S/L2 T/L3U, V, WR/L1 S/L2 T/L3U, V, WEarth (ground) cableR/L1 S/L2 T/L3U, V, WR/L1 S/L2 T/L3U, V, WEarth (ground) cable FR-E720-0.1KNC to 0.75KNCM3.51.22-3.52-3.522214142.52.52.5 FR-E720-1.5KNC, 2.2KNCM41.52-42-422214142.52.52.5 FR-E720-3.7KNCM41.55.5-45.5-43.53.53.51212444 FR-E720-5.5KNCM52.55.5-55.5-55.55.55.51010666 FR-E720-7.5KNCM52.514-58-51485.56816106 FR-E720-11KNCM52.514-514-514141466161616 FR-E720-15KNCM6(M5)4.422-622-622221444252516

Three-phase 400V class (when input power supply is 440V)

Mitsubishi Electronics fre700 — Three-phase 400V class (when input power supply is 440V) diagram (page 11)
Fig. 6 · Three-phase 400V class (when input power supply is 4…
Applicable Inverter ModelTerminal Screw Size ∗4Tightening Torque N·mCrimping TerminalCable Size HIV Cables, etc. (mm2) ∗1AWG ∗2PVC Cables, etc. (mm2) ∗3 R/L1 S/L2 T/L3U, V, WR/L1 S/L2 T/L3U, V, WEarth (ground) cableR/L1 S/L2 T/L3U, V, WR/L1 S/L2 T/L3U, V, WEarth (ground) cable FR-E740-0.4KNC to 3.7KNCM41.52-42-422214142.52.52.5 FR-E740-5.5KNCM41.55.5-42-43.523.5121442.54 FR-E740-7.5KNCM41.55.5-45.5-43.53.53.51212444 FR-E740-11KNCM41.55.5-45.5-45.55.5810106610 FR-E740-15KNCM52.58-58-588888101010

Single-phase 200V class (when input power supply is 220V)

Mitsubishi Electronics fre700 — Single-phase 200V class (when input power supply is 220V) diagram (page 11)
Fig. 7 · Single-phase 200V class (when input power supply is…
Applicable Inverter ModelTerminal Screw Size ∗4Tightening Torque N·mCrimping TerminalCable Size HIV Cables, etc. (mm2) ∗1AWG ∗2PVC Cables, etc. (mm2) ∗3 R/L1 S/L2 T/L3U, V, WR/L1 S/L2 T/L3U, V, WEarth (ground) cableR/L1 S/L2 T/L3U, V, WR/L1 S/L2 T/L3U, V, WEarth (ground) cable FR-E720S-0.1KNC to 0.4KNCM3.51.22-3.52-3.522214142.52.52.5 FR-E720S-0.75KNCM41.52-42-422214142.52.52.5 FR-E720S-1.5KNCM41.52-42-422214142.52.52.5 FR-E720S-2.2KNCM41.55.5-42-43.522121442.52.5

∗1 The cable size is that of the cable (HIV cable (600V class 2 vinyl-insulated cable) etc.) with continuous maximum permissible temperature of 75°C. Assumes

that the surrounding air temperature is 50°C or less and the wiring distance is 20m or less.

∗2 The recommended cable size is that of the cable (THHW cable) with continuous maximum permissible temperature of 75°C. Assumes that the surrounding

air temperature is 40°C or less and the wiring distance is 20m or less. (Selection example for use mainly in the United States.)

∗3 The recommended cable size is that of the cable (PVC cable) with continuous maximum permissible temperature of 70°C. Assumes that the surrounding air

temperature is 40°C or less and the wiring distance is 20m or less. (Selection example for use mainly in Europe.)

∗4 The terminal screw size indicates the terminal size for R/L1, S/L2, T/L3, U, V, W, PR, P/+, N/-, P1 and a screw for earthing (grounding).

A screw for earthing (grounding) of the FR-E720-15KNC is indicated in ( ).

For single-phase power input, the terminal screw size indicates the size of terminal screw for R/L1, S/L2, U, V, W, PR, P/+, N/-, P1 and a screw for earthing

(grounding).

y Tighten the terminal screw to the specified torque. A screw that has been tighten too loosely can cause a short circuit

or malfunction. A screw that has been tighten too tightly can cause a short circuit or malfunction due to the unit breakage. y Use crimping terminals with insulation sleeve to wire the power supply and motor.

Page 12 of the Mitsubishi Electronics fre700 user manual — reduction) in the low speed range. (2) Total wiring length
Page 12 · click to enlarge
Page 12

Wiring

The line voltage drop can be calculated by the following formula:

3 × wire resistance[mΩ/m] × wiring distance[m] × current[A] 1000

Line voltage drop [V]=

Use a larger diameter cable when the wiring distance is long or when it is desired to decrease the voltage drop (torque

reduction) in the low speed range. (2) Total wiring length

The overall wiring length for connection of a single motor or multiple motors should be within the value in the table below.

Pr. 72 PWM frequency selection Setting (carrier frequency)0.1K 0.2K 0.4K0.75K1.5K2.2K3.7K or Higher 1 (1kHz) or less200V class200m 200m 300m500m500m500m500m 400V class⎯ ⎯200m200m300m500m500m 2 to15 (2kHz to 14.5kHz)200V class30m 100m 200m300m500m500m500m 400V class⎯ ⎯30m100m200m300m500m
Mitsubishi Electronics fre700 — reduction) in the low speed range. (2) Total wiring length diagram (page 12)
Fig. 8 · reduction) in the low speed range. (2) Total wiring…

When driving a 400V class motor by the inverter, surge voltages attributable to the wiring constants may occur at the

motor terminals, deteriorating the insulation of the motor. Take the following measures (1) or (2) in this case.

(1) Use a "400V class inverter-driven insulation-enhanced motor" and set frequency in Pr. 72 PWM frequency selection

according to wiring length.

Wiring Length 50m or less50m to 100mExceeding 100m Carrier frequency14.5kHz or less8kHz or less2kHz or less

(2) Connect the surge voltage suppression filter (FR-ASF-H/FR-BMF-H) on the inverter output side.

y Especially for long-distance wiring, the inverter may be affected by a charging current caused by the stray

capacitances of the wiring, leading to a malfunction of the overcurrent protective function, fast response current limit

function, or stall prevention function or a malfunction or fault of the equipment connected on the inverter output side.

If malfunction of fast-response current limit function occurs, disable this function. If malfunction of stall prevention

function occurs, increase the stall level. ( Refer to Pr. 22 Stall prevention operation level and Pr. 156 Stall prevention

operation selection in Chapter 5 of the Instruction Manual (Applied))

y Refer to Chapter 5 of the Instruction Manual (Applied) for details of Pr. 72 PWM frequency selection. Refer to the manual of

the option for details of surge voltage suppression filter (FR-ASF-H/FR-BMF-H).

y When using the automatic restart after instantaneous power failure function with wiring length exceeding than 100m,

select without frequency search (Pr. 162 = "1 (initial setting) or 11"). ( Refer to Chapter 5 of the Instruction Manual

(Applied))

Page 13 of the Mitsubishi Electronics fre700 user manual — Wire Size (mm 2 ) Blade terminal product
Page 13 · click to enlarge
Page 13

Wiring

2.3.5 Wiring of control circuit

(1) Terminal layout of control circuit terminal

Recommended wire size:

Mitsubishi Electronics fre700 — (1) Terminal layout of control circuit terminal diagram (page 13)
Fig. 9 · (1) Terminal layout of control circuit terminal

0.3mm2 to 0.75mm2

(2) Wiring method

For the control circuit wiring, strip off the sheath of wires, and use them with a blade terminal. For a single wire, strip off the sheath of the wire and apply directly. Insert the blade terminal or the single wire into a socket of the terminal.

1. Strip off the sheath about the length below. If the length of the sheath peeled is too long, a short circuit may occur among neighboring wires. If the length is too short, wires might come off. Wire the stripped wire after twisting it to prevent it from becoming loose. In addition, do not solder it.
Mitsubishi Electronics fre700 — (2) Wiring method diagram (page 13)
Fig. 10 · (2) Wiring method
2. Crimp the blade terminal. Insert wires to a blade terminal, and check that the wires come out for about 0 to 0.5 mm from a sleeve. Check the condition of the blade terminal after crimping. Do not use a blade terminal of which the crimping is inappropriate, or the face is damaged.
Mitsubishi Electronics fre700 — (2) Wiring method diagram (page 13)
Fig. 11 · (2) Wiring method

Wires are not inserted into the shell Crumpled tip

Commercially available blade terminals (as of January 2010) zPhoenix Contact Co.,Ltd.

Mitsubishi Electronics fre700 — (2) Wiring method diagram (page 13)
Fig. 12 · (2) Wiring method

crimping tool with insulation sleeve without insulation sleeve for UL wire ∗

0.75 (for two wires) AI-TWIN 2 x 0,75-10GY — —

∗A blade terminal with an insulation sleeve compatible with MTW wire which has a thick wire insulation

zNICHIFU Co.,Ltd.

Wire Size (mm 2 ) Blade terminal product

number Insulation product number Blade terminal

crimping tool

0.3 to 0.75 BT 0.75-11 VC 0.75 NH 67

zWiring

Page 14 of the Mitsubishi Electronics fre700 user manual — (4) Wiring instructions
Page 14 · click to enlarge
Page 14
Mitsubishi Electronics fre700 — 2.3.5 Wiring of control circuit diagram (page 14)
Fig. 13 · 2.3.5 Wiring of control circuit

When using a single wire or a stranded wire without a blade

terminal, push an open/close button all the way down with a

y When using a stranded wire without a blade terminal, twist enough to avoid short circuit with a nearby terminals or

wires. y Place the flathead screwdriver vertical to the open/close button. In case the blade tip slips, it may cause to damage of

zWire removal Pull the wire with pushing the open/close button all the way down firmly with a flathead screwdriver.

Mitsubishi Electronics fre700 — 2.3.5 Wiring of control circuit diagram (page 14)
Fig. 14 · 2.3.5 Wiring of control circuit
Mitsubishi Electronics fre700 — 2.3.5 Wiring of control circuit diagram (page 14)
Fig. 15 · 2.3.5 Wiring of control circuit

pushing the open/close button all the way down may damage the terminal block. y Use a small flathead screwdriver (Tip thickness:

0.4mm/tip width: 2.5mm). If a flathead screwdriver with a narrow tip is used, terminal block may be damaged. Commercially available product (as of October 2008)

y Place the flathead screwdriver vertical to the open/

close button. In case the blade tip slips, it may cause to damage of inverter or injury.

Terminals SD and SE are common terminals for I/O signals. (Both common terminals are isolated from each other.) Do not earth them. Terminal SD is a common terminal for the 24V external power supply terminal (+24). The open collector circuit is isolated from the internal control circuit by photocoupler. Terminal SE is a common terminal for the open collector output terminal (Y0). The contact input circuit is isolated from the internal control circuit by photocoupler.

(4) Wiring instructions

1. It is recommended to use the cables of 0.3mm 2 to 0.75mm 2 gauge for connection to the control circuit terminals. 2) The maximum wiring length should be 30m. 3) Do not short across terminals +24 and SD. It may cause a failure to the external power supply. 4) Use shielded or twisted cables for connection to the control circuit terminals and run them away from the main and power circuits (including the 200V relay sequence circuit).
Page 15 of the Mitsubishi Electronics fre700 user manual — Wiring
Page 15 · click to enlarge
Page 15

Wiring

2.3.6 Connecting the 24V external power supply

CC-Link communication between the master module and the inverter can be continued while the main power circuit is OFF if the 24V external power supply is connected across terminals +24 and SD. When the main circuit power supply is turned ON, the power supply changes from the 24V external power supply to the main circuit power supply. (1) Specification of the applied 24V external power supply y Input voltage 23.5 to 26.5VDC y Input current 0.7A or less (2) Confirming the 24V external power supply y "EV" flickers in the monitor display on the operation panel while the 24V external power is being supplied. The 24V

external power supply operation signal (EV) is also output. For the EV signal, assign the function to the terminal Y0 or a virtual terminal of CC-Link communication by setting "68 (positive logic) or 168 (negative logic)" in Pr. 190 to Pr. 192 or Pr. 313 to Pr. 315 (Output terminal function selection).

(3) Function of the 24V external power supply operation y When the main power supply is turned ON during the 24V external power supply operation, a reset is performed in the

inverter, then the power supply changes to the main circuit power supply. During the reset operation in the inverter, the inverter cannot be controlled through the CC-Link communication. y The operation stops when the power supply changes to the 24V external power supply from the main circuit power

supply regardless of the operating status (in a stop, in running, in automatic restart after instantaneous power failure, in offline tuning, in main circuit capacitor life measurement).

y All start signals (STF signal, STR signal, and on the operation panel) are invalid during the 24V external power

supply operation. y Faults history and parameters can be read and parameters can be written (when the parameter write from the

operation panel is enabled) using the operation panel keys. y The safety stop function is also valid during the 24V external power supply operation. When the safety stop function is

active, however, "SA" is not displayed because "EV" is displayed. The "EV" display has priority over the "SA" display. y The following items can be monitored during the 24V external power supply operation:

Frequency setting, output current peak value∗, converter output voltage peak value∗, cumulative energization time, actual operation time∗, cumulative power∗, PID set point, PID measured value, PID deviation, and cumulative power 2∗ (dedicated to CC-Link communication) ∗The monitored data is not updated after the power supply is changed from the main circuit power supply. (Refer to Chapter 5 of the Instruction Manual (Applied) for the details of each monitor.) y The valid signals when the 24V external power supply is ON are EV, SAFE, SAFE2, Y90, Y91, Y95, REM, LF, and

ALM. (Other signals are OFF.) (Refer to Chapter 5 of the Instruction Manual (Applied) for the detail of each signal.) y The alarms, which have occurred when the main circuit power supply is ON, continue to be output after the power

supply is changed to the 24V external power supply. Perform the inverter reset to reset the alarms. y The retry function is invalid for all alarms when the 24V external power supply is ON. y If the power supply changes from the main circuit power supply to the 24V external power supply while measuring the

main circuit capacitor's life, the measurement completes after the power supply changes back to the main circuit power supply (Pr.259 = "3").

y When the 24V external power supply is input while the main circuit power supply is OFF, the CC-Link communication

is enabled, but the inverter operation is disabled. y Inrush current higher than the value described in (1) may flow at a power-ON. Confirm that the power supply and

other devices are not affected by the inrush current and the voltage drop caused by it. y When the wiring length between the external power supply and the inverter is long, the voltage often drops. Select the

appropriate wiring size and length to keep the voltage in the rated input voltage range. y In a serial connection of several inverters, the current increases when it flows through the inverter wiring near the power

supply. The increase of the current causes voltage to drop further. When connecting different inverters to different power supplies, use the inverters after confirming that the input voltage of each inverter is within the rated input voltage range. y "E.SAF" may appear when the start-up time of the 24V power supply is too long in the 24V external power supply operation.

Flickering

Page 16 of the Mitsubishi Electronics fre700 user manual — (2) Wiring connection diagram
Page 16 · click to enlarge
Page 16

Wiring

2.3.7 Safety stop function

(1) Description of the function

The terminals related to the safety stop function are shown below.

Terminal Symbol Description

S1 ∗1 For input of safety stop channel 1. Between S1 and PC / S2 and PC Open: In safety stop state. Short: Other than safety stop state. S2 ∗1 For input of safety stop channel 2.

PC ∗1 Common terminal for terminal S1 and S2.

Outputs the safety stop status. The signal is output when inverter output is shut off due to the safety stop function.

OFFDrive enabled or drive stop (at an internal

Y0 or virtual terminal of CC-Link

safety circuit failure∗5) ON: Drive stop (no internal safety circuit failure∗5)

Outputs when an alarm or failure is detected. The signal is output when no internal safety circuit failure∗5 exists.

OFFInternal safety circuit failure ∗5 ON : No internal safety circuit failure ∗5

SE Common terminal for open collector outputs (terminal Y0)

∗1 In the initial status, terminals S1 and S2 are shorted with terminal PC by shortening wire. Remove the shortening wire and connect the safety relay module when using the safety stop function. ∗2 Inverter running (RUN signal) is assigned to the terminal Y0 in the initial status. ∗3 To use the SAFE signal, set "80 (positive logic) or 180 (negative logic)" in any of Pr.190 to Pr.192 or Pr.313 to Pr.315 (Output terminal function selection) to assign the function. ( Refer to Chapter 5 of the Instruction Manual (Applied)) ∗4 To use the SAFE 2 signal, set "81 (positive logic) or 181 (negative logic)" to any of Pr.190 to Pr.192 or Pr.313 to Pr.315 (Output terminal function selection) to assign the function. ( Refer to Chapter 5 of the Instruction Manual (Applied)) ∗5 At an internal safety circuit failure, one of E.SAF, E.6, E.7, and E.CPU is displayed on the operation panel.

recognized. y Use SAFE signal to monitor safety stop status. SAFE signal cannot be used as safety stop input signal to other

devices (other than the safety relay module). y SAFE 2 signal can only be used to output an alarm or to prevent restart of an inverter. The signal cannot be used as

safety stop input signal to other devices.

(2) Wiring connection diagram

To prevent restart at fault occurrence, connect terminals Y0 (SAFE 2 signal) and SE to terminals XS0 and XS1, which

are the feedback input terminals of the safety relay module.

By setting Pr. 190 RX2 (terminal Y0) function selection = "81 (SAFE2 signal)", terminal RUN is turned OFF at fault occurrence.

Mitsubishi Electronics fre700 — (2) Wiring connection diagram diagram (page 16)
Fig. 16 · (2) Wiring connection diagram

*1 Output signals differ by the setting of Pr. 190 RX2 (terminal Y0) function selection.

the other functions. Set parameters after confirming the function of terminal Y0.

SAFE signal ∗3 · communication∗2 · SAFE2 signal ∗4

Page 17 of the Mitsubishi Electronics fre700 user manual — ON
Page 17 · click to enlarge
Page 17

Wiring

(3) Safety stop function operation

Input

Input signal Internal safety circuit∗1 Output signal Inverter operation enable signal S1-PC S2-PC SAFE∗3 SAFE2∗3

power

OFF — — — OFF OFF Output shutoff (Safe state)

Short Short No failure OFF ON Drive enabled

Failure OFF OFF Output shutoff (Safe state)

ON

Open Open No failure ∗2 ON ON Output shutoff (Safe state)

Failure OFF OFF Output shutoff (Safe state)

Short Open Failure OFF OFF Output shutoff (Safe state)

Open Short Failure OFF OFF Output shutoff (Safe state)

∗1 At an internal safety circuit failure, one of E.SAF, E.6, E.7, and E.CPU is displayed on the operation panel.

∗2 SA is displayed when both of the S1 and S2 signals are in open status and no internal safety circuit failure exists.

∗3 ON: Transistor used for an open collector output is conducted.

OFF: Transistor used for an open collector output is not conducted.

For more details, refer to the Safety stop function instruction manual (BCN-A211508-004). (Refer to the front cover for how to

obtain the manual.)

Page 18 of the Mitsubishi Electronics fre700 user manual — 110VDC 0.5A,
Page 18 · click to enlarge
Page 18

Connection of a dedicated external brake resistor (MRS type, MYS type, FR-ABR)

2.4 Connection of a dedicated external brake resistor (MRS type, MYS type, FR-ABR)

Install a dedicated brake resistor (MRS type, MYS type, FR-ABR) outside when the motor driven by the inverter is made to run by the load, quick deceleration is required, etc. Connect a dedicated brake resistor (MRS type, MYS type, FR-ABR) to terminal P/+ and PR. (For the locations of terminal P/+ and PR, refer to the terminal block layout (page 7).)

Set parameters below. ( Refer to the Instruction Manual (Applied) for the parameter details.)

Mitsubishi Electronics fre700 — Connection of a dedicated external brake resistor (MRS type, MYS type, FR-ABR) diagram (page 18)
Fig. 17 · Connection of a dedicated external brake resistor (M…

Connected Brake Resistor Pr. 30 Regenerative function selection Setting Pr. 70 Special regenerative brake duty Setting MRS type, MYS type 0 (initial value) — MYS type (used at 100% torque/6%ED) 1 6%

FR-ABR 1 7.5K or lower 10% 11K or higher 6%

It is recommended to configure a sequence, which shuts off power in the input side of the inverter by the external thermal

relay as shown below, to prevent overheat and burnout of the brake resistor (MRS, MYS) and high duty brake resistor (FR-

ABR) in case the regenerative brake transistor is damaged. (The brake resistor cannot be connected to the 0.1K or 0.2K.)

Thermal relay (OCR) (*1)

High-duty brake resistor (FR-ABR)

P/+ S/L2 T/L3

R/L1

R

PR

T

*2 ∗1 Refer to the table below for the type number of each capacity of thermal relay and the

F

diagram below for the connection.

MC

ON OFF

(Always install a thermal relay when using a brake resistor whose capacity is 11K or

∗2 When the power supply is 400V class, install a step-down transformer.

MC

Power Supply

Voltage Brake Resistor Thermal Relay Type (Mitsubishi product) Contact Rating

MRS120W200 TH-N20CXHZ-0.7A

MRS120W100 TH-N20CXHZ-1.3A MRS120W60 TH-N20CXHZ-2.1A MRS120W40 TH-N20CXHZ-3.6A MYS220W50 (two

110VAC 5A,

220VAC 2A (AC11 class)

110VDC 0.5A,

units in parallel) TH-N20CXHZ-5A

220VDC 0.25A (DC11 class)

Power Supply

Voltage Brake Resistor Thermal Relay Type (Mitsubishi product) Contact Rating

FR-ABR-0.4K TH-N20CXHZ-0.7A

FR-ABR-0.75K TH-N20CXHZ-1.3A FR-ABR-2.2K TH-N20CXHZ-2.1A FR-ABR-3.7K TH-N20CXHZ-3.6A FR-ABR-5.5K TH-N20CXHZ-5A FR-ABR-7.5K TH-N20CXHZ-6.6A FR-ABR-11K TH-N20CXHZ-11A FR-ABR-15K TH-N20CXHZ-11A

TH-N20 1/L 1 5/L 3

110VAC 5A

220VAC 2A (AC11 class)

FR-ABR-H0.4K TH-N20CXHZ-0.24A FR-ABR-H0.75K TH-N20CXHZ-0.35A FR-ABR-H1.5K TH-N20CXHZ-0.9A FR-ABR-H2.2K TH-N20CXHZ-1.3A FR-ABR-H3.7K TH-N20CXHZ-2.1A FR-ABR-H5.5K TH-N20CXHZ-2.5A FR-ABR-H7.5K TH-N20CXHZ-3.6A FR-ABR-H11K TH-N20CXHZ-6.6A FR-ABR-H15K TH-N20CXHZ-6.6A

110VDC 0.5A,

2/T 1 6/T 3

220VDC 0.25A (DC11 class)

To the inverter terminal P/+

y The brake resistor connected should only be the dedicated brake resistor. y Brake resistor cannot be used with the brake unit.

y Do not use the brake resistor (MRS type, MYS type) with a lead wire extended.

y Do not connect the resistor directly to the terminals P/+ and N/-. This could cause a fire.

Show 5 more labels / short text on this page
MC Inverter · Power supply · OCR Contact · higher) · To a resistor
Page 19 of the Mitsubishi Electronics fre700 user manual — (1) Programmable controller side
Page 19 · click to enlarge
Page 19

Wiring for CC-Link communication

2.5 Wiring for CC-Link communication

2.5.1 System configuration example

(1) Programmable controller side

Mount the "QJ61BT11N", "LJ61BT11", "AJ61QBT11", "A1SJ61QBT11", "AJ61BT11" or "A1SJ61BT11" "CC-Link system master/local module" on the main or extension base unit having the programmable controller CPU used as the master

station. (2) Connect the master station of the CC-Link programmable controller unit to the CC-Link

communication connector of FR-E700-NC with the CC-Link dedicated cable.

Mitsubishi Electronics fre700 — (1) Programmable controller side diagram (page 19)
Fig. 18 · (1) Programmable controller side

y When the CPU has the automatic refresh function (example: QnA series CPU)

Through communication with the corresponding devices using sequence ladder logic, data is automatically transferred to the

refresh buffer of the master station at the execution of the END instruction to perform communication with the remote devices.

y When the CPU does not have the automatic refresh function (example: AnA series CPU)

Data is transferred to the refresh buffer of the master station directly by sequence ladder logic to perform communication with

Page 20 of the Mitsubishi Electronics fre700 user manual — O N 1 2
Page 20 · click to enlarge
Page 20

Wiring for CC-Link communication

2.5.2 Connection of several inverters

An inverter can join the link system as a CC-Link remote device station, and such device stations can be controlled and monitored with a user program of a programmable controller. These devices can be useful components of an automated factory. Connect shielding wires of the CC-Link dedicated cable to "SLD" of each unit.

FR-E700-NC *2 FR-E700-NC

DA DB DG

DA DB DG NC NC NC SLD *4

DA DB DG

Terminating resistor selection switch (SW1) *3

SLD

SLD

∗1 Use the terminating resistors supplied with the programmable controller. ∗2 Set "1" and "2" of the terminating resistor selection switch (SW1) to OFF (without terminating resistor) in the middle units.

Without terminating resistor (initial setting)

O N 1 2

OFFOFF

O N 1 2

ON OFF

Do not use.

O N 1 2

OFF ON

130 Ω

O N 1 2

ON ON

110 Ω

130Ω is a resistance value for the CC-Link Ver.1.00 dedicated high performance cable.

∗3 Set the terminating resistor selection switch (SW1). ( Refer to Chapter 1 of the Instruction Manual (Applied) for switch positions.)

Do not use the built-in terminating resistor selection switch (SW1) when using a one-touch connecter plug with terminating resistor. (SW1-OFF, 2-OFF) (Refer to page 20 for the details of the one-touch connector plug with terminating resistor.) ∗4 Use a conduction area of a P-clip (enclosed item) to ground (earth) shielding wires of the CC-Link dedicated cable to a position (as close as possible to the inverter) on the enclosure. Take caution not to subject the CC-Link communication connector to stress. (Refer to page 19) (1) Maximum number of units connected to one master station (CC-Link Ver.1.10) 42 units (when only inverters are connected)

If any other units are included, the number of stations occupied depends on the unit and therefore the following conditions must be satisfied: {(1 × a) + (2 × b) + (3 × c) + (4 × d)} ≤ 64

a: Number of units occupying 1 station c: Number of units occupying 3 stations b: Number of units occupying 2 stations d: Number of units occupying 4 stations {(16 × A) + (54 × B) + (88 × C)} ≤ 2304

A: Number of remote I/O ≤ 64 B: Number of remote device stations ≤ 42 C: Number of local, standby master and intelligent device stations ≤ 26

(2) Maximum number of units connected to one master station (CC-Link Ver.2.00) 42 units (when only inverters are connected)

  • If any other units are included, the number of stations occupied depends on the unit and therefore the following conditions must be satisfied:
  • {(a + a2 + a4 + a8) + (b + b2 + b4 + b8) × 2 + (c + c2 + c4 + c8) × 3 + (d + d2 + d4 + d8) × 4} ≤ 64
  • {(a × 32 + a2 × 32 + a4 × 64 + a8 × 128) + (b × 64 + b2 × 96 + b4 × 192 + b8 × 384) + (c × 96 + c2 × 160 + c4 × 320 + c8 × 640) + (d × 128 + d2 × 224 + d4 × 448 + d8 × 896)} ≤ 8192
  • {(a × 4 + a2 × 8 + a4 × 16 + a8 × 32) + (b × 8 + b2 × 16 + b4 × 32 + b8 × 64) + (c × 12 + c2 × 24 + c4 × 48 + c8 × 96) + (d × 16 + d2 × 32 + d4 × 64 + d8 × 128)} ≤ 2048

a: Number of single setting devices occupying one station b: Number of single setting devices occupying two stations c: Number of single setting devices occupying three stations d: Number of single setting devices occupying four stations a2: Number of double setting devices occupying one station b2: Number of double setting devices occupying two stations c2: Number of double setting devices occupying three stations d2: Number of double setting devices occupying four stations a4: Number of quadruple setting devices occupying one station b4: Number of quadruple setting devices occupying two stations c4: Number of quadruple setting devices occupying three stations d4: Number of quadruple setting devices occupying four stations a8: Number of octuple setting devices occupying one station b8: Number of octuple setting devices occupying two stations c8: Number of octuple setting devices occupying three stations d8: Number of octuple setting devices occupying four stations • 16 × A + 54 × B + 88 × C ≤ 2304 A: Numbers of remote I/O ≤ 64 B: Number of remote device stations ≤ 42 C: Number of local and intelligent device stations ≤ 26

Show 12 more labels / short text on this page
Master module · Blue · Blue · Terminating resistor *1 · White · White · Yellow · Yellow · Shielded twisted cable · Shielded twisted cable · *4 · Description
Page 21 of the Mitsubishi Electronics fre700 user manual — REMARKS
Page 21 · click to enlarge
Page 21

Wiring for CC-Link communication

2.5.3 Connection cable and plug

In the CC-Link system, use CC-Link dedicated cables.

If the cable used is other than the CC-Link dedicated cable, the performance of the CC-Link system is not guaranteed.

For the specifications of the CC-Link dedicated cable, refer to the website of the CC-Link Partner Association.

Website of the CC-Link Partner Association http://www.cc-link.org/

y One-touch communication connector plug (as of December 2009)

Refer to the following table for the plug required to fabricate a cable on your own.

Model Manufacturer

A6CON-L5P Mitsubishi Electric Corporation

35505-6000-B0M GF 3M

(1) Cable-end treatment

Apply the following treatment to the CC-Link dedicated cable that is inserted to a one-touch communication connector plug.

Mitsubishi Electronics fre700 — 35505-6000-B0M GF 3M diagram (page 21)
Fig. 19
1. Cut the sheath. 2. Separate shielding wires from the drain wire. Cut the shielding
3. Cut the aluminum tape and braid. 4. Straighten the drain wire and twist it from the root.

y Where possible, round the cable tip that is cut off with a tool such as nippers. If the cable is not rounded, it may get caught in

the middle of a plug, without fully entering into the plug.

y If required, apply an insulation treatment to the shielding wire area where it is not covered by the one-touch communication

(2) Plug cover check

Check that a plug cover is snapped into a plug.

y Do not push the plug cover onto the plug before inserting a cable. Once crimped, the plug cover cannot be reused.

(3) Cable insertion

Lift up the tail of the plug cover, and fully insert a cable. Insert

Mitsubishi Electronics fre700 — (3) Cable insertion diagram (page 21)
Fig. 20 · (3) Cable insertion

different signal wires to the one-touch communication connector

plug as shown in the right figure.

REMARKS

y Insert the cable fully. Failure to do so may cause a crimping failure.

y A cable sometimes comes out of the head of the cover.

In that case, pull the cable a little so that the cable stays under the plug cover.

Plug · Plug cover

Page 22 of the Mitsubishi Electronics fre700 user manual — (1) Connection to the connector
Page 22 · click to enlarge
Page 22

Wiring for CC-Link communication

(4) Crimping the plug cover

Push the plug cover onto the plug with a tool such as pliers. After crimping, check that the plug cover is

securely snapped into the plug as shown in the right figure.

REMARKS

y Misaligned latches between the plug cover and the plug may keep the cover lifted. The plug cover is not sufficiently crimped

in this condition. Push the plug cover until it snaps into the plug.

2.5.4 Connection of CC-Link dedicated cable

Mitsubishi Electronics fre700 — 2.5.4 Connection of CC-Link dedicated cable diagram (page 22)
Fig. 21 · 2.5.4 Connection of CC-Link dedicated cable

(1) Connection to the connector

Connect the CC-Link dedicated cable to the CC-link communication connector.

Use an M4 screw and a conduction area of a P-clip (enclosed item) to ground (earth) shielding wires of the CC-Link dedicated

cable to a position (as close as possible to the inverter) on the enclosure.

Take caution not to subject the CC-Link communication connector to stress.

Mitsubishi Electronics fre700 — (1) Connection to the connector diagram (page 22)
Fig. 22 · (1) Connection to the connector

Take caution not to subject the cables to stress.

After wiring, wire offcuts must not be left in the inverter. Wire offcuts can cause an alarm, failure or malfunction.

Page 23 of the Mitsubishi Electronics fre700 user manual — Model Manufacturer
Page 23 · click to enlarge
Page 23

Wiring for CC-Link communication

2.5.5 Unit replacement while online

Connect an online communication connector to the CC-Link communication connector. The online communication connector

enables a unit replacement without interrupting the communication. Always connect the online communication connector to

CONA (front side) of the CC-Link communication connector. (Do not connect it to CONB (back side) of the CC-Link

communication connector. Doing so will cause a failure or breakage of the inverter and the connectors.)

Also connect a one-touch connector plug with terminating resistor to the CC-Link communication connector of FR-E700-NC at

the end.

(A replacement while online is not available for the units, which are using the built-in terminating resistor selection switches

(SW1).)

Mitsubishi Electronics fre700 — (SW1).) diagram (page 23)
Fig. 23

Use the following online communication connector and one-touch connector plug with terminating resistor.

y One-touch connector plug with terminating resistor (as of December 2009)

Model Manufacturer

A6CON-TR11 Mitsubishi Electric Corporation

y Do not use the online communication connector A6CON-LJ5P (Mitsubishi Electric Corporation) and 35720-L200-B00

AK (3M) for this product. Doing so will cause a failure or breakage of the inverter and the connectors.

Page 24 of the Mitsubishi Electronics fre700 user manual — REMARKS
Page 24 · click to enlarge
Page 24

CC-Link function setting

2.6 CC-Link function setting

2.6.1 Station number setting (Pr. 542)

y Use Pr. 542 Communication station number (CC-Link) to set station number of the inverter. Set this parameter within the range

of 1 to 64. (Pr. 542 is initially set to "1.")

y Use different station numbers for different devices. (If different devices have the same station number, the

communication cannot be performed properly.)

Inverter No.1 Remote device station

Inverter No.2 Remote device station

Inverter No.3 Remote device station

remote I/O station (occupies one station)

Station 00 Station 01 Station 02 Station 03 Station 04

Number of stations connected is 4.

REMARKS

y Set consecutive numbers for the station numbers. (Do not skip a number in sequence like "station number 1 - station number

2- station number 4".)

The station number does not have to match with the physical connection sequence. (There is no problem with having the

physical connection sequence like "station number 1 - station number 3 - station number 4 - station number 2".)

y One inverter occupies one station. (One remote device station)

y "L.ERR" LED flickers if the setting is changed. When power is switched ON again (inveter is reset), the setting value is

applied and the LED turns OFF.

2.6.2 Baud rate setting (Pr. 543)

y Set the transmission speed. (Refer to the manual for the CC-Link master module for details of transmission speed.)

Pr. 543 Setting Transmission Speed

0 (initial setting) 156kbps

2 2.5Mbps

REMARKS

y "L.ERR" LED flickers if the setting is changed. When power is switched ON again (inveter is reset), the setting value is

applied and the LED turns OFF.

Show 5 more labels / short text on this page
CC-Link master module · Programmable controller · 1 625kbps · 3 5Mbps · 4 10Mbps
Page 25 of the Mitsubishi Electronics fre700 user manual — (6) Electromagnetic wave interference
Page 25 · click to enlarge
Page 25

PRECAUTIONS FOR USE OF THE INVERTER

3 PRECAUTIONS FOR USE OF THE INVERTER

The FR-E700 series is a highly reliable product, but incorrect peripheral circuit making or operation/handling method may

shorten the product life or damage the product.

Before starting operation, always recheck the following items.

(1) Use crimping terminals with insulation sleeve to wire the power supply and motor.

(2) Application of power to the output terminals (U, V, W) of the inverter will damage the inverter. Never perform

such wiring.

(3) After wiring, wire offcuts must not be left in the inverter.

Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean.

When drilling mounting holes in an enclosure etc., take care not to allow chips and other foreign matter to enter the

inverter.

(4) Use cables of the size to make a voltage drop 2% or less.

If the wiring distance is long between the inverter and motor, a main circuit cable voltage drop will cause the motor torque to decrease especially at the output of a low frequency.

Refer to page 8 for the recommended wire sizes.

(5) The overall wiring length should be 500m or less.

Especially for long distance wiring, the fast-response current limit function may decrease or the equipment connected to

the secondary side may malfunction or become faulty under the influence of a charging current due to the stray capacity

of the wiring. Therefore, note the overall wiring length. (Refer to page 9)

(6) Electromagnetic wave interference

The input/output (main circuit) of the inverter includes high frequency components, which may interfere with the

communication devices (such as AM radios) used near the inverter. In this case, install the FR-BIF optional capacitor

type filter (for use in the input side only) or FR-BSF01 common mode filter to minimize interference.

(7) Do not install a power factor correction capacitor, surge suppressor or capacitor type filter on the inverter

output side.

This will cause the inverter to trip or the capacitor and surge suppressor to be damaged. If any of the above devices are connected, immediately remove them. (When using capacitor type filter (FR-BIF) for single-phase power supply

specification, make sure of secure insulation of T-phase, and connect to the input side of the inverter.)

(8) For some short time after the power is switched OFF, a high voltage remains in the smoothing capacitor.

Before wiring or inspecting inside the inverter, wait 10 minutes or longer after turning OFF the power supply, then confirm

that the voltage across the main circuit terminals P/+ and N/- of the inverter is 30VDC or less using a tester, etc. The

capacitor is charged with high voltage for some time after power OFF, and it is dangerous.

(9) If "EV" is displayed on the operation panel, turn off the 24V external power supply before wiring and inspection.

(10) A short circuit or earth (ground) fault on the inverter output side may damage the inverter modules.

y Fully check the insulation resistance of the circuit prior to inverter operation since repeated short circuits caused by

peripheral circuit inadequacy or an earth (ground) fault caused by wiring inadequacy or reduced motor insulation

resistance may damage the inverter modules.

y Fully check the to-earth (ground) insulation and phase to phase insulation of the inverter output side before power-on.

Especially for an old motor or use in hostile atmosphere, securely check the motor insulation resistance etc.

Page 26 of the Mitsubishi Electronics fre700 user manual — (18) Instructions for overload operation
Page 26 · click to enlarge
Page 26

PRECAUTIONS FOR USE OF THE INVERTER

(11) Do not use the inverter input side magnetic contactor to start/stop the inverter.

Since repeated inrush currents at power ON will shorten the life of the converter circuit (switching life is about 1,000,000

times.), frequent starts and stops of the MC must be avoided. Turn ON/OFF the inverter start controlling terminals (STF,

STR) to run/stop the inverter. ( Refer to the Instruction Manual (Applied))

(12) Across P/+ and PR terminals, connect only an external regenerative brake discharging resistor.

Do not connect a mechanical brake.

The brake resistor cannot be connected to the 0.1K or 0.2K. Leave terminals P/+ and PR open.

Also, never short between these terminals.

(13) Do not apply a voltage higher than the permissible voltage to the inverter I/O signal circuits.

Application of a voltage higher than the permissible voltage to the inverter I/O signal circuits or opposite polarity may

damage the I/O devices.

(14) Provide electrical and mechanical interlocks for MC1 and

MC2 which are used for bypass operation.

MC1

Interlock U V W

When the wiring is incorrect and if there is a bypass operation

R/L1 S/L2 T/L3

IM

circuit as shown right, the inverter will be damaged when the

MC2

power supply is connected to the inverter U, V, W terminals, due to arcs generated at the time of switch-over or chattering caused

by a sequence error.

(15) If the machine must not be restarted when power is restored after a power failure, provide a magnetic contactor

in the inverter's input side and also make up a sequence which will not switch ON the start signal.

If the start signal (start switch) remains ON after a power failure, the inverter will automatically restart as soon as the

power is restored.

(16) Inverter input side magnetic contactor (MC)

On the inverter input side, connect a MC for the following purposes. (Refer to page 3 for selection.) 1)To release the inverter from the power supply when a fault occurs or when the drive is not functioning (e.g. emergency stop operation). For example, MC avoids overheat or burnout of the brake resistor when heat capacity of the resistor is insufficient or brake regenerative transistor is damaged with short while connecting an optional brake resistor. 2)To prevent any accident due to an automatic restart at restoration of power after an inverter stop made by a power failure 3)To separate the inverter from the power supply to ensure safe maintenance and inspection work. The inverter's input side MC is used for the above purpose, select class JEM1038-AC3 MC for the inverter input side current when making an emergency stop during normal operation.

(17) Handling of inverter output side magnetic contactor

Switch the magnetic contactor between the inverter and motor only when both the inverter and motor are at a stop. When the magnetic contactor is turned ON while the inverter is operating, overcurrent protection of the inverter and such will activate. When MC is provided for switching to the commercial power supply, for example, switch it ON/OFF after the inverter and motor have stopped.

(18) Instructions for overload operation

When performing operation of frequent start/stop of the inverter, rise/fall in the temperature of the transistor element of

the inverter will repeat due to a repeated flow of large current, shortening the life from thermal fatigue. Since thermal

fatigue is related to the amount of current, the life can be increased by reducing current at locked condition, starting

current, etc. Decreasing current may increase the life. However, decreasing current will result in insufficient torque and the inverter may not start. Therefore, choose the inverter which has enough allowance for current (up to 2 rank larger in

capacity).

(19) Make sure that the specifications and rating match the system requirements.

Power supply · Undesirable current · Inverter

Page 27 of the Mitsubishi Electronics fre700 user manual — No. Interlock Method Check Method Used Signals Refer to Page
Page 27 · click to enlarge
Page 27

FAILSAFE OF THE SYSTEM WHICH USES THE INVERTER

4 FAILSAFE OF THE SYSTEM WHICH USES THE INVERTER

When a fault occurs, the inverter trips to output a fault signal. However, a fault output signal may not be output at an inverter fault occurrence when the detection circuit or output circuit fails, etc. Although Mitsubishi assures best quality products, provide an interlock which uses inverter status output signals to prevent accidents such as damage to machine when the inverter fails for some reason and at the same time consider the system configuration where failsafe from outside the inverter, without using the inverter, is enabled even if the inverter fails.

(1) Interlock method which uses the inverter status output signals

By providing interlocks, inverter fault can be detected. For the interlocks, use different status output signals of the

inverter (virtual terminals of the CC-Link communication) in combinations shown below.

No. Interlock Method Check Method Used Signals Refer to Page

Refer to Chapter 4

1. Inverter protective function operation

Operation check of an alarm contact Circuit error detection by negative logic

Fault output signal (ALM signal)

of the Instruction Manual (Applied).

Refer to Chapter 4

2. Inverter running status Check of the reset release signal Reset release signal (RY signal)

of the Instruction Manual (Applied).

Start signal (STF signal, STR signal) Running signal (RUN signal)

Refer to Chapter 4

3. Inverter running status Logic check of the start signal and running signal

of the Instruction Manual (Applied).

Start signal (STF signal, STR signal) Output current detection signal (Y12 signal)

4. Inverter running status Logic check of the start signal and output current

Refer to Chapter 4

of the Instruction Manual (Applied).

(2) Backup method outside the inverter Even if the interlock is provided by the inverter status signal, enough failsafe is not ensured depending on the failure status of the inverter itself. For example, even if the interlock is provided using the inverter fault output signal, start signal and RUN signal output, there is a case where a fault output signal is not output and RUN signal is kept output even if an inverter fault occurs. Provide a speed detector to detect the motor speed and current detector to detect the motor current and consider the backup system such as checking up as below according to the level of importance of the system.

1) Start signal and actual operation check Check the motor running and motor current while the start signal is input to the inverter by comparing the start signal to the inverter and detected speed of the speed detector or detected current of the current detector. Note that the motor current runs as the motor is running for the period until the motor stops since the inverter starts decelerating even if the start signal turns off. For the logic check, configure a sequence considering the inverter deceleration time. In addition, it is recommended to check the three-phase current when using the current detector.

2. Command speed and actual operation check Check if there is no gap between the actual speed and commanded speed by comparing the inverter speed command and detected speed of the speed detector.

air volume, etc.)

To the alarm detection sensor

Show 4 more labels / short text on this page
Controller · System failure · Inverter · Sensor (speed, temperature,
Page 28 of the Mitsubishi Electronics fre700 user manual — PARAMETER LIST
Page 28 · click to enlarge
Page 28

PARAMETER LIST

5 PARAMETER LIST

For simple variable-speed operation of the inverter, the initial setting of the parameters may be used. Set the necessary

parameters to meet the load and operational specifications. Parameter setting, change and check can be made from the

operation panel.

Mitsubishi Electronics fre700 — PARAMETER LIST diagram (page 28)
Fig. 24

y indicates simple mode parameters. (Initially set to extended mode)

y The parameters surrounded by a black border in the table allow its setting to be changed during operation even if "0" (initial

value) is set in Pr. 77 Parameter write selection. (Note that the Pr.77 setting cannot be changed through the CC-Link

26 Multi-speed setting (speed 6) 0 to 400Hz, 9999 9999

∗1 1 Maximum frequency 0 to 120Hz 120Hz

27 Multi-speed setting (speed 7) 0 to 400Hz, 9999 9999

4 Multi-speed setting (high speed) 0 to 400Hz 60Hz

5 Multi-speed setting (middle speed) 0 to 400Hz 30Hz

31 Frequency jump 1A 0 to 400Hz, 9999 9999

6 Multi-speed setting (low speed) 0 to 400Hz 10Hz

32 Frequency jump 1B 0 to 400Hz, 9999 9999

7 Acceleration time 0 to 3600/ 360s 5/10/15s

33 Frequency jump 2A 0 to 400Hz, 9999 9999

8 Deceleration time 0 to 3600/ 360s 5/10/15s

34 Frequency jump 2B 0 to 400Hz, 9999 9999

9 Electronic thermal O/L relay 0 to 500A Rated inverter

35 Frequency jump 3A 0 to 400Hz, 9999 9999

10 DC injection brake operation frequency 0 to 120Hz 3Hz

36 Frequency jump 3B 0 to 400Hz, 9999 9999

11 DC injection brake operation time 0 to 10s 0.5s

12 DC injection brake operation voltage 0 to 30% 6/4/2% ∗3

40 RUN key rotation direction selection 0, 1 0

18 High speed maximum frequency 120 to 400Hz 120Hz

45 Second deceleration time 0 to 3600/ 360s, 9999 9999

46 Second torque boost 0 to 30%, 9999 9999

19 Base frequency voltage 0 to 1000V, 8888, 9999 9999

47 Second V/F (base frequency) 0 to 400Hz, 9999 9999

22 Stall prevention operation level 0 to 200% 150%

23 Stall prevention operation level compensation factor at double speed

0, 5, 7 to 12, 14, 20, 23 to 25, 52 to 57, 61, 62, 100

24 Multi-speed setting (speed 4) 0 to 400Hz, 9999 9999

54 to 56 Parameter for manufacturer setting. Do not set.

25 Multi-speed setting (speed 5) 0 to 400Hz, 9999 9999

57 Restart coasting time 0, 0.1 to 5s, 9999 9999

Page 29 of the Mitsubishi Electronics fre700 user manual — Parameter Name Setting
Page 29 · click to enlarge
Page 29

PARAMETER LIST

Parameter Name Setting

Initial Value

Parameter Name Setting

Initial Value

Range

Range

58 Restart cushion time 0 to 60s 1s

117 to 124 Parameter for manufacturer setting. Do not set.

59 Remote function selection 0, 1, 2, 3 0

125 Frequency setting gain frequency 0 to 400Hz 60Hz

60 Energy saving control selection 0, 9 0

126 Parameter for manufacturer setting. Do not set.

61 Reference current 0 to 500A, 9999 9999

127 PID control automatic switchover frequency

62 Reference value at acceleration

0 to 200%, 9999 9999

128 PID action selection

40 to 43, 50,

63 Reference value at deceleration

0 to 200%, 9999 9999

129 PID proportional band 0.1 to 1000%,

65 Retry selection 0 to 5 0

66 Stall prevention operation reduction starting frequency 0 to 400Hz 60Hz

130 PID integral time 0.1 to 3600s,

67 Number of retries at fault occurrence

0 to 10, 101 to 110 0

131 PID upper limit 0 to 100%,

68 Retry waiting time 0.1 to 360s 1s

132 PID lower limit 0 to 100%,

69 Retry count display erase 0 0

70 Special regenerative brake duty 0 to 30% 0%

133 Parameter for manufacturer setting. Do not set.

134 PID differential time 0.01 to 10.00s,

0, 1, 3 to 6, 13 to 16, 23, 24, 40, 43, 44, 50, 53, 54

145, 146 Parameter for manufacturer setting. Do not set.

147 Acceleration/deceleration time switching frequency

0 to 400Hz, 9999 9999

72 PWM frequency selection 0 to 15 1

150 Output current detection level 0 to 200% 150%

151 Output current detection signal delay time 0 to 10s 0s

73, 74 Parameter for manufacturer setting. Do not set.

75 Reset selection/PU stop selection

0 to 3, 14 to 17 14

152 Zero current detection level 0 to 200% 5%

77 ∗6 Parameter write selection 0, 1, 2 0

153 Zero current detection time 0 to 1s 0.5s

78 Reverse rotation prevention selection 0, 1, 2 0

156 Stall prevention operation selection

0 to 31, 100, 101 0

79 ∗9 Operation mode selection 0, 1, 2, 3, 4,

157 OL signal output timer 0 to 25s, 9999 0s

160 User group read selection 0, 1, 9999 0

80 Motor capacity 0.1 to 15kW, 9999 9999

161 Frequency setting/key lock operation selection 0, 1, 10, 11 0

81 Number of motor poles 2, 4, 6, 8, 10, 9999 9999

162 Automatic restart after instantaneous power failure selection

0 to 500A (0 to ****), 9999 ∗5 9999

0, 1, 10, 11 1

82 Motor excitation current

165 Stall prevention operation level for restart 0 to 200% 150%

83 Rated motor voltage 0 to 1000V 200V/ 400V ∗4

168, 169 Parameter for manufacturer setting. Do not set.

84 Rated motor frequency 10 to 120Hz 60Hz

170 Watt-hour meter clear 0, 10, 9999 9999

89 Speed control gain (Advanced magnetic flux vector)

0 to 200%, 9999 9999

171 Operation hour meter clear 0, 9999 9999

172 User group registered display/ batch clear

9999, (0 to 16) 0

0 to 50Ω (0 to ****), 9999 ∗5 9999

90 Motor constant (R1)

173 User group registration 0 to 999, 9999 9999

0 to 50Ω (0 to ****), 9999 ∗5 9999

174 User group clear 0 to 999, 9999 9999

91 Motor constant (R2)

178, 179 Parameter for manufacturer setting. Do not set.

0 to 1000mH (0 to 50Ω, 0 to ****), 9999 ∗5 9999

180 RY4 function selection 0 to 5, 7, 8,

92 Motor constant (L1)

181 RY3 function selection 1

14 to 16, 18,

0 to 1000mH (0 to 50Ω, 0 to ****), 9999 ∗5 9999

182 RY2 function selection 2

183 RY9 function selection 24

93 Motor constant (L2)

184 RYB function selection 62

0 to 100% (0 to 500Ω, 0 to ****), 9999 ∗5

94 Motor constant (X)

96 Auto tuning setting/status 0, 1, 11, 21 0

Show 14 more labels / short text on this page
0 to 400Hz, · 9999 9999 · 0, 20, 21, · 51, 60, 61 · 9999 100% · 9999 1s · 9999 9999 · 9999 9999 · 9999 9999 · 71 Applied motor · 6, 7 0 · 10, 12, · 24, 25, 62, · 65 to 67,
Page 30 of the Mitsubishi Electronics fre700 user manual — 5 PARAMETER LIST
Page 30 · click to enlarge
Page 30
Mitsubishi Electronics fre700 — 5 PARAMETER LIST diagram (page 30)
Fig. 25

251 Output phase loss protection selection 0, 1 1

255 Life alarm status display (0 to 15) 0

256 Inrush current limit circuit life display (0 to 100%) 100%

257 Control circuit capacitor life display (0 to 100%) 100%

258 Main circuit capacitor life display (0 to 100%) 100%

261 Power failure stop selection 0, 1, 2 0

268 Monitor decimal digits selection 0, 1, 9999 9999

276 PWM carrier frequency at stop-on contact 0 to 9, 9999 9999

277 Stall prevention operation current switchover 0, 1 0

280 Brake opening current detection time 0 to 2s 0.3s

232 Multi-speed setting (speed 8) 0 to 400Hz, 9999 9999

281 Brake operation time at start 0 to 5s 0.3s

233 Multi-speed setting (speed 9) 0 to 400Hz, 9999 9999

283 Brake operation time at stop 0 to 5s 0.3s

287 Droop filter time constant 0 to 1s 0.3s

292 Automatic acceleration/ deceleration 0, 1, 7, 8, 11 0

0 to 6, 99, 100 to 106, 199, 9999 9999

297 Password lock/unlock 1000 to 9999 (0 to 5) 9999

298 Frequency search gain 0 to 32767, 9999 9999

299 Rotation direction detection selection at restarting 0, 1, 9999 0

246 Slip compensation time constant 0.01 to 10s 0.5s

247 Constant-power range slip compensation selection 0, 9999 9999

249 Earth (ground) fault detection at start 0, 1 0

Page 31 of the Mitsubishi Electronics fre700 user manual — 2%: 11K, 15K
Page 31 · click to enlarge
Page 31

PARAMETER LIST

Parameter Name Setting

Initial Value

Parameter Name Setting

Initial Value

Range

Range

0, 1, 3, 4, 7, 8,

800 Control method selection 20, 30 20

11 to 16, 20,

0 to 500A (0 to ****) , 9999 ∗5 9999

313 RX9 function selection

25, 26, 46, 47,

64, 68, 80, 81,

872 ∗8 Input phase loss protection selection 0, 1 1

90, 91, 93, 95,

882 Regeneration avoidance operation selection 0, 1, 2 0

314 RXA function selection 9999

883 Regeneration avoidance operation level 300 to 800V 400VDC/ 780VDC

885 Regeneration avoidance compensation frequency limit value

0 to 10Hz, 9999 6Hz

315 RXB function selection 9999

886 Regeneration avoidance voltage gain 0 to 200% 100%

888 Free parameter 1 0 to 9999 9999

338 to 340 Parameter for manufacturer setting. Do not set.

889 Free parameter 2 0 to 9999 9999

342 Communication EEPROM write selection 0, 1 0

C0 Parameter for manufacturer setting. Do not set.

C2 Frequency setting bias

343 Parameter for manufacturer setting. Do not set.

frequency 0 to 400Hz 0Hz

349 Communication reset selection 0, 1 0

C3 to C7, C22 to C25,

450 Second applied motor 0, 1, 9999 9999

990, 991 Parameter for manufacturer setting. Do not set.

495 Remote output selection 0, 1, 10, 11 0

496 Remote output data 1 0 to 4095 0

Pr.CL Parameter clear 0, 1 0

497 Parameter for manufacturer setting. Do not set.

ALLC All parameter clear 0, 1 0

500 Communication error execution waiting time 0 to 999.8s 0

Er.CL Faults history clear 0, 1 0

Pr.CH Initial value change list — —

501 Communication error occurrence count display 0 0

∗1 Differ according to capacities.

502 Stop mode selection at communication error 0, 1, 2, 3 0

6%0.75K or lower

503 Maintenance timer 0 (1 to 9998) 0

4%1.5K to 3.7K

3%: 5.5K, 7.5K

504 Maintenance timer alarm output set time

0 to 9998, 9999 9999

2%: 11K, 15K

∗2 Differ according to capacities.

541 Frequency command sign selection (CC-Link) 0, 1 0

5s3.7K or lower
10s5.5K, 7.5K

542∗7 Communication station number (CC-Link) 1 to 64 1

15s11K, 15K

∗3 Differ according to capacities.

543∗7 Baud rate selection (CC-Link) 0 to 4 0

6%: 0.1K, 0.2K

544∗6 CC-Link extended setting 0, 1, 12, 14, 18 0

4%0.4K to 7.5K

2%: 11K, 15K

547 to 551 Parameter for manufacturer setting. Do not set.

550 NET mode operation command source selection 0, 2, 9999 9999

∗4 The initial value differs according to the voltage class. (200V class/400V

∗5 The range differs according to the Pr. 71 setting.

551 PU mode operation command source selection 2 to 4, 9999 9999

∗6 The setting cannot be changed through the FL remote communication.

∗7 Changing the setting value causes the "L.ERR" LED to flicker. Turn OFF

555 Current average time 0.1 to 1.0s 1s

the power once, then turn ON again (inverter reset) to apply the setting

556 Data output mask time 0 to 20s 0s

and to turn OFF the LED.

∗8 Available only for the three-phase power input model.

557 Current average value monitor signal output reference current 0 to 500A

∗9 Settings cannot be written during CC-Link communication (under

Network operation mode).

563 Energization time carrying- over times (0 to 65535) 0

564 Operating time carrying-over times (0 to 65535) 0

571 Holding time at a start 0 to 10s, 9999 9999

611 Acceleration time at a restart 0 to 3600s, 9999 9999

653 Speed smoothing control 0 to 200% 0

665 Regeneration avoidance frequency gain 0 to 200% 100

Show 16 more labels / short text on this page
859 Torque current · 96, 98, 99, · 100, 101, 103, · 104, 107, 108, · 111 to 116, · 120, 125, 126, · ∗4 · 146, 147, 164, · 168, 180, 181, · 190, 191, 193, · 195, 196, 198, · 199, 9999 · class) · Rated · inverter · current
Page 32 of the Mitsubishi Electronics fre700 user manual — OFF
Page 32 · click to enlarge
Page 32

Reset method of protective function

6 TROUBLESHOOTING

When a fault occurs in the inverter, the inverter trips and the display on the operation panel automatically changes to one of

the fault or alarm indications on page 30. If the fault does not correspond to any of the following faults or if you have any other problem, please contact your sales

representative.

z Retention of fault output signal .. When the magnetic contactor (MC) provided on the input side of the inverter is opened when

a fault occurs, the inverter's control power will be lost and the fault output will not be held.

z Fault or alarm indication When a fault or alarm occurs, the operation panel display automatically switches to the fault

or alarm indication.

z Resetting method When a fault occurs, the inverter output is kept stopped. Unless reset, therefore, the inverter

cannot restart. z When any fault occurs, take the appropriate corrective action, then reset the inverter, and resume operation.

Not doing so may lead to the inverter fault and damage.

Inverter fault or alarm indications are roughly categorized as below.

A message regarding operational fault and setting fault by the operation panel is displayed. The inverter does not trip.

The inverter does not trip even when a warning is displayed. However, failure to take appropriate measures will lead to a fault.

The inverter does not trip. An alarm can also be output with a parameter setting.

When a fault occurs, the inverter trips and a fault signal is output. The ALM signal is also output.

REMARKS

y For the details of fault displays and other malfunctions, also refer to the Instruction Manual (Applied). y Past eight faults can be displayed using the setting dial.

6.1 Reset method of protective function

The inverter can be reset by performing any of the following operations. Note that the internal thermal integrated value of the

electronic thermal relay function and the number of retries are cleared (erased) by resetting the inverter.

Inverter recovers about 1s after reset is released.

Operation 1: Using the operation panel, press to reset the inverter.

(This may only be performed when a fault occurs.)

Operation 2...... Write HFD (inverter reset) to an instruction code of CC-Link

communication. (Inverter reset though CC-Link communication is invalid during communication error.)

Operation 3...... Switch OFF the power once, then switch it ON again after the

ON

indicator of the operation panel turns OFF.

OFF

REMARKS

y Use the operation 1 or 2 to reset when using the 24V external power supply.

start signal ON restarts the motor suddenly.

Show 4 more labels / short text on this page
(1) Error message · (2) Warning · (3) Alarm · (4) Fault
Page 33 of the Mitsubishi Electronics fre700 user manual — Fault
Page 33 · click to enlarge
Page 33

List of fault or alarm indications

6.2 List of fault or alarm indications

When a fault occurs, the inverter trips and the PU display automatically changes to one of the following fault or alarm indications.

Function Name Description Corrective action Display

Operation panel lock Appears when operation was tried during operation panel lock. Press for 2s to release lock.

Error message

Password locked Appears when a password restricted parameter is read/written.

Enter the password in Pr. 297 Password lock/unlock to unlock the password function before operating.

y Check the setting of Pr. 77 Parameter write selection. y Check the settings of Pr. 31 to Pr. 36 (frequency jump). y After stopping operation, make parameter setting. y After setting the operation mode to the "PU operation mode",

Parameter write error Appears when an error occurred during parameter writing.

make parameter setting.

Inverter reset Appears when the RES signal is ON. y Turn OFF the reset command

y Increase or decrease the Pr. 0 Torque boost setting by 1% and

check the motor status. y Set a larger value in Pr. 7 Acceleration time and Pr. 8

Deceleration time. y Reduce the load weight. y Try Advanced magnetic flux vector control and General-

purpose magnetic flux vector control. y Change the Pr. 14 Load pattern selection setting. y Set stall prevention operation current in Pr. 22 Stall prevention

Stall prevention (overcurrent) Appears during overcurrent stall prevention.

operation level. (The initial value is 150%.) The acceleration/ deceleration time may change. Increase the stall prevention operation level with Pr. 22 Stall prevention operation level, or disable stall prevention with Pr. 156 Stall prevention operation selection. (Operation at OL occurrence can be selected using Pr. 156.)

Appears during overvoltage stall prevention. Appears while the regeneration avoidance function is activated.

The deceleration time may change. Increase the deceleration time using Pr. 8 Deceleration time.

Appears if the regenerative brake duty reaches or exceeds 85% of the Pr. 70 Special regenerative brake duty value. If the regenerative brake duty reaches 100%, a regenerative overvoltage (E. OV_) occurs.

y Increase the deceleration time. y Check that the Pr. 30 Regenerative function selection and Pr. 70

Regenerative brake prealarm ∗6

Special regenerative brake duty settings.

Warning

Electronic thermal relay function prealarm

Appears when the electronic thermal O/L relay has reached 85% of the specified value.

y Reduce the load and frequency of operation. y Set an appropriate value in Pr. 9 Electronic thermal O/L relay.

PU stop Appears when on the operation panel was

Turn the start signal OFF and release with .

pressed during External operation.

Maintenance signal output ∗6

Appears when the cumulative energization time has exceeded the maintenance output timer set value.

Setting "0" in Pr. 503 Maintenance timer erases the signal.

Undervoltage Appears when the main circuit power became low voltage.

Check the power supply system equipment such as power supply.

y When not using the safety stop function, short across

terminals S1 and PC and across S2 and PC with shorting wire for the inverter to run. y If is indicated when across S1 and PC and across S2 and PC are both shorted while using the safety stop function (drive enabled), internal failure might be the cause. Check the wiring of terminals S1, S2 and PC and contact your sales representative if the wiring has no fault.

Safety stop Appears when the safety stop function is activated (during output shutoff).

Turn ON the power supply for the inverter (main circuit). y If appears by turning ON the power supply of the inverter (main circuit) while the external 24V power is supplied, check the power supply (for the main circuit). y Check if the jumper is installed securely between terminal

24V external power supply operation

Flickers when the main circuit power supply is not supplied and the 24V external power is supplied.

P/+ and P1.

Alarm

Appears when the cooling fan remains stopped when operation is required or when the speed has decreased.

Check for fan alarm. Please contact your sales representative.

y Increase the acceleration time. (Shorten the downward

acceleration time for the lift.) y When "E.OC1" is always lit at start, disconnect the motor

once and start the inverter. If "E.OC1" is still lit, contact your sales representative. y Check the wiring to make sure that output short circuit/

Fault

Overcurrent trip during acceleration

Appears when an overcurrent occurred during acceleration.

ground fault does not occur. y Set 50Hz in Pr. 3 Base frequency. y Lower the setting of stall prevention operation level. y Activate the fast-response current limit operation. y Set base voltage (rated voltage of the motor, etc.) in Pr. 19

Base frequency voltage.

Show 6 more labels / short text on this page
∗2 · Stall prevention (overvoltage) · ∗3 · ∗4 · Fan alarm · ∗5
Page 34 of the Mitsubishi Electronics fre700 user manual — Fault
Page 34 · click to enlarge
Page 34

List of fault or alarm indications

Function Name Description Corrective action Display

y Keep load stable. y Check the wiring to make sure that output short circuit/

Overcurrent trip during constant speed

Appears when an overcurrent occurred during constant speed operation.

ground fault does not occur. y Lower the setting of stall prevention operation level. y Activate the fast-response current limit operation.

y Increase the deceleration time. y Check the wiring to make sure that output short circuit/

Overcurrent trip during deceleration or stop

Appears when an overcurrent occurred during deceleration and at a stop.

ground fault does not occur. y Check the mechanical brake operation. y Lower the setting of stall prevention operation level. y Activate the fast-response current limit operation.

y Decrease the acceleration time. y Use regeneration avoidance function (Pr. 882, Pr. 883, Pr. 885,

Regenerative overvoltage trip during acceleration

Appears when an overvoltage occurred during acceleration.

Pr. 886). y Set the Pr.22 Stall prevention operation level correctly.

y Keep load stable. y Use regeneration avoidance function (Pr. 882, Pr. 883, Pr. 885,

Regenerative overvoltage trip during constant speed

Appears when an overvoltage occurred during constant speed operation.

Pr. 886). y Use the brake resistor, brake unit or power regeneration

common converter (FR-CV) as required. y Set the Pr.22 Stall prevention operation level correctly.

y Increase the deceleration time. (Set the deceleration time

which matches the moment of inertia of the load) y Make the brake cycle longer. y Use regeneration avoidance function (Pr. 882, Pr. 883, Pr. 885,

Regenerative overvoltage trip during deceleration or stop

Appears when an overvoltage occurred during deceleration and at a stop.

Pr. 886). y Use the brake resistor, brake unit or power regeneration

common converter (FR-CV) as required.

y Increase acceleration/deceleration time. y Adjust the torque boost setting. y Set the load pattern selection setting according to the load

Fault

Inverter overload trip (electronic thermal relay function)

Appears when the electronic thermal relay function for inverter element protection was activated.

pattern of the using machine. y Reduce the load weight. y Set the surrounding air temperature to within the

specifications.

y Reduce the load weight. y For a constant-torque motor, set the constant-torque motor in

Motor overload trip (electronic thermal relay function) ∗1

Appears when the electronic thermal relay function for motor protection was activated.

Pr. 71 Applied motor. y Check that stall prevention operation setting is correct.

y Set the surrounding air temperature to within the

specifications. y Clean the heatsink. y Replace the cooling fan.

Heatsink overheat Appears when the heatsink was overheated.

Appears if one of the three phases on the inverter input side is lost. It may also appear if phase-to-phase voltage of the three-phase power input becomes largely unbalanced.

y Wire the cables properly. y Repair a break portion in the cable. y Check the Pr. 872 Input phase loss protection selection setting. y Set Pr. 872 = "0" (without input phase loss protection) when

Input phase loss ∗6 ∗7 ∗8

three-phase input voltage is largely unbalanced.

Appears when the output frequency drops to 1Hz as a result of deceleration due to the excess motor load.

Reduce the load weight. (Check the Pr. 22 Stall prevention operation level setting.)

This function stops the inverter output if an alarm occurs in the brake circuit, e.g. damaged brake transistors. In this case, the inverter must be powered off immediately.

Brake transistor alarm detection

Replace the inverter.

Output side earth (ground) fault overcurrent at start ∗6

Appears when an earth (ground) fault occurred on the inverter's output side. (detects only at a start)

Remedy the ground fault portion.

If one of the three phases (U, V, W) on the inverter's output side (load side) is lost during inverter operation (except during DC injection brake operation and when output frequency is under 1Hz), inverter stops the output.

y Wire the cables properly. y Check the Pr. 251 Output phase loss protection selection setting.

∗5 · Stall prevention stop · Output phase loss

Page 35 of the Mitsubishi Electronics fre700 user manual — Fault
Page 35 · click to enlarge
Page 35

List of fault or alarm indications

Function Name Description Corrective action Display

y Refer to "Error check with LEDs" in the Instruction Manual

(Applied), and take a corrective action for the error. y Check the connection of the CC-Link dedicated cable. y Check that each CC-Link dedicated cable length between

nodes is within the specified value. (Refer to the User's Manual of the CC-Link master module for the cable length between the nodes compatible with the CC-Link Ver.1.00.) y Set the built-in terminating resistor switch to ON at the end

Stops inverter outputs at a communication line error of CC-Link communication.

stations. Alternatively, correctly connect the one-touch connector plug with terminating resistor.

y Set Pr.296 ≠ "0 or 100" for the password lock. y If the problem still persists after taking the above measure,

Option fault y Appears when Pr.296 = "0 or 100."

contact your sales representative.

y Take measures against noises if there are devices producing

y Stops the inverter output if there is excess

excess electrical noises around the inverter. y Set back the switch for manufacturer setting in the initial

electrical noise around the inverter. y Also appears when a switch for manufacturer

setting. y If the problem still persists after taking the above measure,

setting is changed.

contact your sales representative.

Please contact your sales representative. When performing parameter write frequently for communication purposes, set "1" in Pr. 342 to enable RAM write. Note that powering OFF returns the inverter to the status before RAM write.

Parameter storage device fault

Appears when operation of the element where parameters stored became abnormal. (control board)

Inverter output is stopped when the control circuit board and the main circuit board do not match with each other.

Please contact your sales representative. (For parts replacement, consult the nearest Mitsubishi FA Center.)

Fault

Retry count excess ∗6 Operation restart within the set number of retries has failed. Eliminate the cause of the error preceding this error indication.

y Take measures against noises if there are devices producing

excess electrical noises around the inverter. y Check the connection between terminals PC and SD. (E6/

CPU fault Appears during the CPU and peripheral circuit errors.

E7) y Please contact your sales representative.

Stops inverter outputs when a sequence fault occurs while using the brake sequence function (Pr. 278 to Pr. 283).

Brake sequence fault ∗6

Check the parameters and correct the wiring.

Configure a circuit where frequent power ON/OFF is not repeated. If the problem still persists after taking the above measure, please contact your sales representative.

Inrush current limit circuit fault

Appears when the resistor of the inrush current limit circuit overheated.

Internal circuit fault Appears when an internal circuit fault has occurred. Please contact your sales representative.

y When not using the safety stop function, short across

terminals S1 and PC and across S2 and PC with shorting wire. y When using the safety stop function, check that wiring of

Safety circuit fault Appears when safety circuit is malfunctioning.

terminal S1, S2 and PC is correct and the safety stop input signal source such as safety relay module is operating properly. Refer to the Safety stop function instruction manual (BCN-211508-004) for causes and countermeasures. (Please contact your sales representative for the manual.)

∗1 Resetting the inverter initializes the internal cumulative heat value of the electronic thermal relay function.

∗2 The error message shows an operational error. The inverter output is not shut off.

∗3 Warnings are messages given before fault occur. The inverter output is not shut off.

∗4 Alarms warn the operator of failures with output signals. The inverter output is not shut off.

∗5 When faults occur, the protective functions are activated to trip the inverter and output the fault signals.

∗6 This protective function does not function in the initial status.

∗7 This protective function activates when Pr.872 Input phase loss protection selection = "1".

∗8 This function is only available for three-phase power input models.

Show 8 more labels / short text on this page
Communication option fault · Option fault · Internal board fault · ∗5 · / · / · / · to
Page 36 of the Mitsubishi Electronics fre700 user manual — Check first when you have a trouble
Page 36 · click to enlarge
Page 36

Check first when you have a trouble

6.3 Check first when you have a trouble

If the following malfunctions occur, refer to the troubleshooting in the Instruction Manual (Applied).

y Motor does not start

y Motor or machine is making abnormal acoustic noise y Inverter generates abnormal noise

y Motor generates heat abnormally

y Motor rotates in the opposite direction

y Speed greatly differs from the setting

y Acceleration/deceleration is not smooth

y Speed varies during operation

y Operation mode is not changed properly

y Operation panel display is not operating y Motor current is too large

y Speed does not accelerate

y Unable to write parameter setting

Page 37 of the Mitsubishi Electronics fre700 user manual — Interval Corrective Action at Alarm
Page 37 · click to enlarge
Page 37

Inspection items

7 PRECAUTIONS FOR MAINTENANCE AND INSPECTION

The inverter is a static unit mainly consisting of semiconductor devices. Daily inspection must be performed to prevent any fault from occurring due to the adverse effects of the operating environment, such as temperature, humidity, dust, dirt and vibration, changes in the parts with time, service life, and other factors.

REMARKS

y For the details of fault displays and other malfunctions, also refer to the Instruction Manual (Applied).

z Precautions for maintenance and inspection

Before wiring or inspecting inside the inverter, wait 10 minutes or longer after turning OFF the power supply, then confirm that the voltage across the main circuit terminals P/+ and N/- of the inverter is 30VDC or less using a tester, etc. The capacitor is charged with high voltage for some time after power OFF, and it is dangerous. If "EV" is displayed on the operation panel, turn OFF the 24V external power supply before inspection.

7.1 Inspection items

Interval Corrective Action at Alarm

Area of

Inspection

Item Description

Check Daily Periodic

Inspection

Occurrence

Check the surrounding air temperature, humidity, dirt, corrosive gas, oil mist, etc. { Improve environment

Overall unit Check for unusual vibration and noise. { Check alarm location and retighten Power supply

Check that the main circuit voltages are normal.∗1 { Inspect the power supply

(1) Check with megger (across main circuit

terminals and earth (ground) terminal). { Contact the manufacturer

(2) Check for loose screws and bolts. { Retighten (3) Check for overheat traces on the parts. { Contact the manufacturer (4) Check for stain. { Clean

(1) Check conductors for distortion.

{ Contact the manufacturer

(2) Check cable sheaths for breakage and

{ Contact the manufacturer

deterioration (crack, discoloration, etc.).

Terminal block Check for damage. { Stop the device and contact the manufacturer.

(1) Check for liquid leakage. { Contact the manufacturer (2) Check for safety valve projection and bulge. { Contact the manufacturer (3) Visual check and judge by the life check of the

Smoothing aluminum electrolytic capacitor

main circuit capacitor ( Refer to Chapter 7 of the Instruction Manual (Applied))

Relay Check that the operation is normal and no chatter is heard. { Contact the manufacturer

(1) Check that the output voltages across phases

with the inverter operated alone is balanced. { Contact the manufacturer

(2) Check that no fault is found in protective and

display circuits in a sequence protective operation test.

{ Contact the manufacturer

Overall (1) Check for unusual odor and discoloration. { Stop the device and contact the manufacturer. (2) Check for serious rust development. { Contact the manufacturer

(1) Check for liquid leakage in a capacitor and

deformation trance. { Contact the manufacturer

(2) Visual check and judge by the life check of the

main circuit capacitor ( Refer to Chapter 7 of the Instruction Manual (Applied))

(1) Check for unusual vibration and noise. { Replace the fan (2) Check for loose screws and bolts. { Fix with the fan cover fixing screws (3) Check for stain. { Clean

Heatsink (1) Check for clogging. { Clean (2) Check for stain. { Clean

Indication (1) Check that display is normal. { Contact the manufacturer (2) Check for stain. { Clean

Meter Check that reading is normal. { Stop the device and contact the manufacturer.

Check for vibration and abnormal increase in operation noise. { Stop the device and contact the manufacturer.

∗1 It is recommended to install a device to monitor voltage for checking the power supply voltage to the inverter. ∗2 One to two years of periodic inspection cycle is recommended. However, it differs according to the installation environment. Consult us for periodic inspection.

Show 22 more labels / short text on this page
Customer's · ∗2 · Surrounding environment · General · voltage · General · Conductors, cables · Main circuit · { · Operation check · Control · circuit, Protective · circuit · Parts check · Aluminum electrolytic capacitor · { · Cooling fan · Cooling · system · Display · Load motor Operation · check
Page 38 of the Mitsubishi Electronics fre700 user manual — Part Name Estimated Lifespan ∗1 Description
Page 38 · click to enlarge
Page 38

Replacement of parts

When using the safety stop function, periodic inspection is required to confirm that safety function of the safety system

operates correctly.

For more details, refer to the Safety stop function instruction manual (BCN-A211508-004). (Refer to the front cover for how to obtain the manual.)

7.2 Replacement of parts

The inverter consists of many electronic parts such as semiconductor devices. The following parts may deteriorate with age because of their structures or physical characteristics, leading to reduced performance or fault of the inverter. For preventive maintenance, the parts must be replaced periodically. Use the life check function as a guidance of parts replacement.

Part Name Estimated Lifespan ∗1 Description

Cooling fan 10 years Replace (as required)

Main circuit smoothing capacitor 10 years ∗2 Replace (as required)

On-board smoothing capacitor 10 years ∗2 Replace the board (as required)

Relays — as required

∗1 Estimated lifespan for when the yearly average surrounding air temperature is 40°C

(without corrosive gas, flammable gas, oil mist, dust and dirt etc.)

∗2 Output current80% of the inverter rated current

For parts replacement, consult the nearest Mitsubishi FA Center.

Page 39 of the Mitsubishi Electronics fre700 user manual — Model FR-E740KNC 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15
Page 39 · click to enlarge
Page 39

Rating

8 SPECIFICATIONS

8.1 Rating

z Three-phase 200V power supply

Mitsubishi Electronics fre700 — z Three-phase 200V power supply diagram (page 39)
Fig. 26 · z Three-phase 200V power supply

Model FR-E720- KNC 0.1 0.2 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15

Applicable motor capacity (kW) ∗1 0.1 0.2 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15

Rated capacity (kVA) ∗2 0.3 0.6 1.2 2.0 3.2 4.4 7.0 9.5 13.1 18.7 23.9

Overload current rating ∗3 150% 60s, 200% 3s (inverse-time characteristics)

AC (DC) voltage/frequency Three-phase 200 to 240V 50Hz/60Hz (283 to 339VDC ∗8)

fluctuation 170 to 264V 50Hz/60Hz (240 to 373VDC ∗8)

Power supply capacity (kVA) ∗6 0.4 0.8 1.5 2.5 4.5 5.5 9 12 17 20 28

Approximate mass (kg) 0.5 0.5 0.7 1.0 1.4 1.4 1.7 4.3 4.3 6.5 6.5

z Three-phase 400V power supply

Mitsubishi Electronics fre700 — z Three-phase 400V power supply diagram (page 39)
Fig. 27 · z Three-phase 400V power supply

Model FR-E740KNC 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15

Applicable motor capacity (kW)∗1 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15

Rated capacity (kVA)∗2 1.2 2.0 3.0 4.6 7.2 9.1 13.0 17.5 23.0

Overload current rating∗3 150% 60s, 200% 3s (inverse-time characteristics)

Power supply capacity (kVA)∗6 1.5 2.5 4.5 5.5 9.5 12 17 20 28

Approximate mass (kg) 1.4 1.4 1.9 1.9 1.9 3.2 3.2 6.0 6.0

∗1 The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi 4-pole standard motor. ∗2 The rated output capacity indicated assumes that the output voltage is 230V for three-phase 200V class and 440V for three-phase 400V class. ∗3 The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For repeated duty, allow time for the inverter and motor to return to or below the temperatures under 100% load. ∗4 The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range. However, the pulse voltage value of the inverter output side voltage remains unchanged at about that of the power supply. ∗5 The braking torque indicated is a short-duration average torque (which varies with motor loss) when the motor alone is decelerated from 60Hz in the shortest time and is not a continuous regenerative torque. When the motor is decelerated from the frequency higher than the base frequency, the average deceleration torque will reduce. Since the inverter does not contain a brake resistor, use the optional brake resistor when regenerative energy is large. A brake unit (FR-BU2) may also be used. (Option brake resistor cannot be used for 0.1K and 0.2K.) ∗6 The power supply capacity varies with the value of the power supply side inverter impedance (including those of the input reactor and cables). ∗7 Setting 2kHz or more in Pr. 72 PWM frequency selection to perform low acoustic noise operation in the surrounding air temperature exceeding 40°C, the rated output current is the value in parenthesis. ∗8 y Connect DC power supply to terminal P/+ and N/-. Connect the plus side of the power supply to terminal P/+ and minus side to terminal N/-. y Since the voltage between P/+ and N/- may increase due to the regeneration energy from the motor and exceeds 415V temporarily, select the DC power

supply which can withstand the voltage/energy during regeneration. If using the power supply which can not withstand voltage/energy during regeneration, insert diodes in series for reverse current prevention. y Although the FR-E700 series has the built-in inrush current limit circuit, select the DC power supply considering the inrush current at powering ON as the

inrush current four times of the rated inverter flows at powering ON. y Since the power supply capacity depends on the output impedance of the power, select the power supply capacity which has enough allowance according

to the AC power supply system capacity.

Page 40 of the Mitsubishi Electronics fre700 user manual — z Single-phase 200V power supply
Page 40 · click to enlarge
Page 40

Rating

z Single-phase 200V power supply

Model FR-E720SKNC 0.1 0.2 0.4 0.75 1.5 2.2

Applicable motor capacity (kW)∗1 0.1 0.2 0.4 0.75 1.5 2.2

Rated capacity (kVA)∗2 0.3 0.6 1.2 2.0 3.2 4.4

Rated current (A)∗7 0.8 (0.8)

1.5 (1.4)

3.0 (2.5)

5.0 (4.1)

8.0 (7.0)

11.0 (10.0)

Overload current rating∗3 150% 60s, 200% 3s (inverse-time characteristics)

Rated output voltage∗4 Three-phase 200 to 240V

Regenerative braking torque ∗5 150% 100% 50% 20%

Rated input AC voltage/frequency Single-phase 200 to 240V 50Hz/60Hz

Permissible AC voltage fluctuation 170 to 264V 50Hz/60Hz

Permissible frequency fluctuation Within ±5%

Power supply capacity (kVA)∗6 0.5 0.9 1.5 2.5 4.0 5.2

Protective structure (JEM1030) Open type (IP00)

Cooling system Self-cooling Forced air cooling

Approximate mass (kg) 0.6 0.6 0.9 1.4 1.5 2.0

∗1 The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi 4-pole standard motor. ∗2 The rated output capacity indicated assumes that the output voltage is 230V. ∗3 The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For repeated duty, allow time for the inverter and motor to return to or below the temperatures under 100% load. If the automatic restart after instantaneous power failure function (Pr. 57) or power failure stop function (Pr. 261) is set and power supply voltage is low while load becomes bigger, the bus voltage decreases to power failure detection level and load of 100% or more may not be available. ∗4 The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range. However, the pulse voltage value of the inverter output side voltage remains unchanged at about that of the power supply. ∗5 The braking torque indicated is a short-duration average torque (which varies with motor loss) when the motor alone is decelerated from 60Hz in the shortest time and is not a continuous regenerative torque. When the motor is decelerated from the frequency higher than the base frequency, the average deceleration torque will reduce. Since the inverter does not contain a brake resistor, use the optional brake resistor when regenerative energy is large. A brake unit (FR-BU2) may also be used. (Option brake resisitor cannot be used for 0.1K and 0.2K.) ∗6 The power supply capacity varies with the value of the power supply side inverter impedance (including those of the input reactor and cables). ∗7 Setting 2kHz or more in Pr. 72 PWM frequency selection to perform low acoustic noise operation with the surrounding air temperature exceeding 40°C, the rated output current is the value in parenthesis.

Output · Power supply

Page 41 of the Mitsubishi Electronics fre700 user manual — Common specifications
Page 41 · click to enlarge
Page 41

Common specifications

8.2 Common specifications

Control method Soft-PWM control/high carrier frequency PWM control (V/F control, Advanced magnetic flux vector control, General-purpose magnetic flux vector control, Optimum excitation control are available) Output frequency range 0.2 to 400Hz Frequency setting resolution (digital input) 0.01Hz

Frequency accuracy (digital input) Within 0.01% of the set output frequency

Voltage/frequency characteristics Base frequency can be set from 0 to 400Hz, Constant-torque/variable torque pattern can be selected

Starting torque 200% or more (at 0.5Hz)...when Advanced magnetic flux vector control is set (3.7K or lower)

Torque boost Manual torque boost

Acceleration/deceleration time setting 0.01 to 360s, 0.1 to 3600s (acceleration and deceleration can be set individually), linear or S-pattern acceleration/

deceleration modes are available. DC injection brake Operation frequency (0 to 120Hz), operation time (0 to 10s), operation voltage (0 to 30%) can be changed.

Stall prevention operation level Operation current level can be set (0 to 200% adjustable), whether to use the function or not can be selected

Surrounding air temperature -10°C to +50°C (non-freezing) ∗2

Ambient humidity 90%RH or less (non-condensing)

Storage temperature ∗1 -20°C to +65°C Atmosphere Indoors (without corrosive gas, flammable gas, oil mist, dust and dirt etc.) Altitude/vibration Maximum 1000m above sea level, 5.9m/s 2 or less at 10 to 55Hz (directions of X, Y, Z axes)

∗1 Temperatures applicable for a short time, e.g. in transit. ∗2 When using the inverters at the surrounding air temperature of 40°C or less, the inverters can be installed closely attached (0cm clearance).

Control specifications · Environment

Page 42 of the Mitsubishi Electronics fre700 user manual — Outline dimension drawings
Page 42 · click to enlarge
Page 42

Outline dimension drawings

8.3 Outline dimension drawings

Mitsubishi Electronics fre700 — Outline dimension drawings diagram (page 42)
Fig. 28 · Outline dimension drawings

108 FR-E720-0.2KNC FR-E720-0.4KNC 140 FR-E720-0.75KNC 160 FR-E720-1.5KNC 108 96 163 FR-E720-2.2KNC FR-E720-3.7KNC 170 158 170 FR-E720-5.5KNC 180 164 260 244 192.5 FR-E720-7.5KNC

  • Three-phase 400V class
Mitsubishi Electronics fre700 — Outline dimension drawings diagram (page 42)
Fig. 29 · Outline dimension drawings
  • Single-phase 200V class
Mitsubishi Electronics fre700 — Outline dimension drawings diagram (page 42)
Fig. 30 · Outline dimension drawings

108 FR-E720S-0.2KNC FR-E720S-0.4KNC 170 FR-E720S-0.75KNC 108 96 163 FR-E720S-1.5KNC 188.5 FR-E720S-2.2KNC 140 128 150 138 183

Page 43 of the Mitsubishi Electronics fre700 user manual — (1) EMC Directive
Page 43 · click to enlarge
Page 43

Appendix 1 Instructions for Compliance with the EU Directives

The EU Directives are issued to standardize different national regulations of the EU Member States and to facilitate free

movement of the equipment, whose safety is ensured, in the EU territory.

Since 1996, compliance with the EMC Directive that is one of the EU Directives has been legally required. Since 1997,

compliance with the Low Voltage Directive, another EU Directive, has been also legally required. When a manufacturer

confirms its equipment to be compliant with the EMC Directive and the Low Voltage Directive, the manufacturer must declare

the conformity and affix the CE marking.

z The authorized representative in the EU

The authorized representative in the EU is shown below.

Name: Mitsubishi Electric Europe B.V.

AddressGothaer Strasse 8, 40880 Ratingen, Germany

We declare that this inverter, when equipped with the dedicated EMC filter, conforms with the EMC Directive in industrial

environments and affix the CE marking on the inverter. When using the inverter in a residential area, take appropriate

measures and ensure the conformity of the inverter used in the residential area.

(1) EMC Directive

We declare that this inverter, when equipped with the EMC Directive compliant EMC filter, conforms with the EMC Directive

and affix the CE marking on the inverter.

  • EMC Directive: 2004/108/EC
  • Standard(s): EN61800-3:2004 (Second environment / PDS Category "C3")

Environment including residential buildings. Includes building directly connected without a transformer to the low

voltage power supply network which supplies power to residential buildings.

Environment including all buildings except buildings directly connected without a transformer to the lower voltage power supply network which supplies power to residential buildings.

∗Set the EMC Directive compliant EMC filter to the inverter. Insert line noise filters and ferrite cores to the power and

control cables as required.

∗Connect the inverter to an earthed power supply.

∗Install a motor, the EMC Directive compliant EMC filter, and a control cable according to the instructions written in the

EMC Installation Guidelines (BCN-A21041-204) (Please contact your sales representative for the EMC Installation

Guidelines.)

∗The cable length between the inverter and the motor is 5m maximum.

∗Confirm that the final integrated system with the inverter conforms with the EMC Directive.

z Note · Second environment · z Note

Page 44 of the Mitsubishi Electronics fre700 user manual — (2) Low Voltage Directive
Page 44 · click to enlarge
Page 44

(2) Low Voltage Directive

We have self-confirmed our inverters as products compliant to the Low Voltage Directive (Conforming standard EN 61800-

5-1) and place the CE mark on the inverters.

∗Do not use an earth leakage circuit breaker as an electric shock protector without connecting the equipment to the earth.

Connect the equipment to the earth securely.

∗Wire the earth (ground) terminal independently. (Do not connect two or more cables to one terminal.)

∗Use the cable sizes on page 8 under the following conditions.

y Surrounding air temperature40°C maximum

If conditions are different from above, select appropriate wire according to EN60204 ANNEX C TABLE 5. ∗Use a tinned (plating should not include zinc) crimping terminal to connect the earth cable. When tightening the screw,

be careful not to damage the threads.

For use as a product compliant with the Low Voltage Directive, use PVC cable on page 8.

∗Use the moulded case circuit breaker and magnetic contactor which conform to the EN or IEC Standard.

∗When using an earth leakage circuit breaker, use a residual current operated protective device (RCD) of type B (breaker

which can detect both AC and DC). If not, provide double or reinforced insulation between the inverter and other

equipment, or put a transformer between the main power supply and inverter.

∗Use the inverter under the conditions of overvoltage category II (usable regardless of the earth (ground) condition of the

power supply), overvoltage category III (usable with the earthed-neutral system power supply, 400V class only) specified

in IEC664.

yTo use the inverter under the conditions of pollution degree 3, install it in the enclosure of IP54 or higher.

yTo use the inverter outside of an enclosure in the environment of pollution degree 2, fix a fan cover with fan cover fixing

screws enclosed.

3.7K or lower

5.5K or higher

Mitsubishi Electronics fre700 — (2) Low Voltage Directive diagram (page 44)
Fig. 31 · (2) Low Voltage Directive

∗On the input and output of the inverter, use cables of the type and size set forth in EN60204 Appendix C. ∗Control circuit terminals on page 5 are safely isolated from the main circuit. ∗Environment

Surrounding Air Temperature -10°C to +50°C -20°C to +65°C -20°C to +65°C

Humidity 90% RH or less 90% RH or less 90% RH or less

Details are given in the technical information "Low Voltage Directive Conformance Guide" (BCN-A21041-203). (Please contact your sales representative for the technical information.)

Outline of instructions

Page 45 of the Mitsubishi Electronics fre700 user manual — Electronic thermal relay function operation characteristic
Page 45 · click to enlarge
Page 45

∗Select a UL and cUL certified fuse with Class T fuse equivalent cut-off speed or faster with the appropriate rating for

branch circuit protection, or a UL489 molded case circuit breaker (MCCB) in accordance with the table below.

FR-E720- KNC 0.1 0.2 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 Rated fuse voltage(V) 240V or more

Fuse Maximum allowable rating (A)∗

Without power factor improving reactor 15 15 15 20 30 40 60 70 80 150 175

With power factor improving reactor 15 15 15 20 20 30 50 60 70 125 150

Molded case circuit breaker (MCCB) Maximum allowable rating (A)* 15 20 25 40 60 80 110 150

FR-E740- KNC 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 Rated fuse voltage(V) 480V or more

Fuse Maximum allowable rating (A)∗

Without power factor improving reactor 6 10 15 20 30 40 70 80 90

With power factor improving reactor 6 10 10 15 25 35 60 70 90

Molded case circuit breaker (MCCB) Maximum allowable rating (A)* 15 20 30 40 50 70

FR-E720S- KNC 0.1 0.2 0.4 0.75 1.5 2.2 Rated fuse voltage(V) 240V or more

Without power factor improving reactor 15 20 20 30 40 60

Fuse Maximum allowable rating (A)∗

With power factor improving reactor 15 20 20 20 30 50

Molded case circuit breaker (MCCB) Maximum allowable rating (A)* 15 15 15 20 25 40

∗Maximum allowable rating by US National Electrical Code. Exact size must be chosen for each installation.

∗When using the electronic thermal relay function as motor overload protection, set the rated motor current to Pr. 9

Electronic thermal O/L relay.

Electronic thermal relay function operation characteristic

Mitsubishi Electronics fre700 — Electronic thermal relay function operation characteristic diagram (page 45)
Fig. 32 · Electronic thermal relay function operation characte…

This function detects the overload (overheat) of the motor, stops the operation of the inverter's output transistor, and stops the output. (The operation characteristic is shown on the left)

Pr. 9 = 50% setting of inverter rating*1, 2

30Hz or more *3 30Hz or more *3 20Hz 10Hz

Operation range Range on the right of characteristic curve Non-operation range Range on the left of characteristic curve

When using the Mitsubishi constant-torque motor 1) Set "1" or any of "13" to "16", "50", "53", "54" in Pr. 71. (This provides a 100% continuous torque characteristic in the low-speed range.) 2) Set the rated current of the motor in Pr. 9.

Characteristic when electronic thermal relay function for motor protection is turned off (when Pr. 9 setting is 0(A))

∗1 When 50% of the inverter rated output current (current value) is set in Pr. 9 ∗2 The % value denotes the percentage to the inverter rated output current. It is not the percentage to the motor rated current. ∗3 When you set the electronic thermal relay function dedicated to the Mitsubishi constant- torque motor, this characteristic curve applies to operation at 6Hz or higher.

Inverter output current(%) (% to the rated inverter current)

⋅Protective function by electronic thermal relay function is reset by inverter power reset and reset signal input. Avoid

unnecessary reset and power-OFF. ⋅When multiple motors are operated by a single inverter, protection cannot be provided by the electronic thermal relay

function. Install an external thermal relay to each motor. ⋅When the difference between the inverter and motor capacities is large and the setting is small, the protective

characteristics of the electronic thermal relay function will be deteriorated. In this case, use an external thermal relay. ⋅A special motor cannot be protected by the electronic thermal relay function. Use the external thermal relay. ⋅Electronic thermal relay may not function when 5% or less of inverter rated current is set to electronic thermal relay

setting.

∗Short circuit current ratings

Suitable For Use in A Circuit Capable of Delivering Not More Than 5 kA rms Symmetrical Amperes, 264 V Maximum.

Suitable For Use in A Circuit Capable of Delivering Not More Than 5 kA rms Symmetrical Amperes, 528 V Maximum.

y200V class · y400V class

Page 46 of the Mitsubishi Electronics fre700 user manual — REMARKS
Page 46 · click to enlarge
Page 46

Appendix 2 Instructions for UL and cUL

(Standard to comply withUL 508C, CSA C22.2 No. 14)
1. General Precaution The bus capacitor discharge time is 10 minutes. Before starting wiring or inspection, switch power off, wait for more than 10 minutes, and check for residual voltage between terminal P/+ and N/- with a meter etc. to avoid a hazard of electrical shock.

2. Installation The below types of inverter have been approved as products for use in enclosure and approval tests were conducted under the following conditions. Design the enclosure so that the surrounding air temperature, humidity and ambience of the inverter will satisfy the specifications (Refer to page 4). Wiring protection Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit protection must be provided in accordance with the National Electrical Code for the U.S. or the Canadian Electrical Code for Canada and any additional codes. As specified on page 42, UL Class T fuses or any faster acting fuse with the appropriate rating or Listed UL 489 Molded Case Circuit Breaker (MCCB) must be employed.

  • 3. Short circuit ratings
  • 200V class Suitable For Use in A Circuit Capable of Delivering Not More Than 100 kA rms Symmetrical Amperes, 264 V Maximum.
  • 400V class Suitable For Use in A Circuit Capable of Delivering Not More Than 100 kA rms Symmetrical Amperes, 528 V Maximum.
4. Wiring For wiring the input (R/L1, S/L2, T/L3) and output (U, V, W) terminals of the inverter, use the UL Listed copper, stranded wires (rated at 75°C) and round crimping terminals. Crimp the crimping terminals with the crimping tool recommended by the terminal maker.
5. Motor overload protection When using the electronic thermal relay function as motor overload protection, set the rated motor current to Pr. 9 "Electronic thermal O/L relay". (Refer to page 42 )

⋅Protective function by electronic thermal relay function is reset by inverter power reset and reset signal input. Avoid

unnecessary reset and power-OFF. ⋅When multiple motors are operated by a single inverter, protection cannot be provided by the electronic thermal relay

function. Install an external thermal relay to each motor. ⋅When the difference between the inverter and motor capacities is large and the setting is small, the protective

characteristics of the electronic thermal relay function will be deteriorated. In this case, use an external thermal relay. ⋅A special motor cannot be protected by the electronic thermal relay function. Use the external thermal relay. ⋅Electronic thermal relay may not function when 5% or less of inverter rated current is set to electronic thermal relay

setting.

REMARKS

y Safety stop function is not certified by the UL.

Page 47 of the Mitsubishi Electronics fre700 user manual — MEMO
Page 47 · click to enlarge
Page 47

MEMO

Page 48 of the Mitsubishi Electronics fre700 user manual — MEMO
Page 48 · click to enlarge
Page 48

MEMO

Page 49 of the Mitsubishi Electronics fre700 user manual — 46 IB-0600401ENG-A
Page 49 · click to enlarge
Page 49

REVISIONS

*The manual number is given on the bottom left of the back cover.

Print Date *Manual Number Revision

May 2011 IB-0600401ENG-A First edition

  • For Maximum Safety
  • Mitsubishi inverters are not designed or manufactured to be used in equipment or systems in situations that can affect or endanger human life.
  • When considering this product for operation in special applications such as machinery or systems used in passenger transportation, medical, aerospace, atomic power, electric power, or submarine repeating applications, please contact your nearest Mitsubishi sales representative.
  • Although this product was manufactured under conditions of strict quality control, you are strongly advised to install safety devices to prevent serious accidents when it is used in facilities where breakdowns of the product are likely to cause a serious accident.
  • Please do not use this product for loads other than three-phase induction motors.

46 IB-0600401ENG-A

Page 50 of the Mitsubishi Electronics fre700 user manual — 1/2 BCN-C22005-659
Page 50 · click to enlarge
Page 50

FRE700-NC Series Instruction Manual Supplement

1 For the terminating resistor selection switch

Please make corrections to the following error in this manual.

Connection of several inverters

Instruction Manual (Basic) : page 17 Instruction Manual (Applied): page 50

(Incorrect)

Set "1" and "2" of the terminating resistor selection switch (SW1) to OFF (without terminating resistor) in the middle units.

Mitsubishi Electronics fre700 — Connection of several inverters diagram (page 50)
Fig. 33 · Connection of several inverters

130 is a resistance value for the CC-Link Ver. 1.00 dedicated high performance cable

(Correct)

Set "1" and "2" of the terminating resistor selection switch (SW1) to OFF (without terminating resistor) in the middle units.

Mitsubishi Electronics fre700 — (Correct) diagram (page 50)
Fig. 34 · (Correct)

130 is a resistance value for the CC-Link Ver. 1.00 dedicated high performance cable

1/2 BCN-C22005-659

Page 51 of the Mitsubishi Electronics fre700 user manual — 2/2 BCN-C22005-659
Page 51 · click to enlarge
Page 51

2 Additional notes for instructions for UL and cUL

Instruction Manual (Basic) : page 43

General precaution

Motor overload protection

When using the electronic thermal relay function as motor overload protection, set the rated motor current to Pr. 9 "Electronic thermal O/L relay".

Motor over temperature sensing is not provided by the drive.

2/2 BCN-C22005-659

Page 52 of the Mitsubishi Electronics fre700 user manual — International FA Center
Page 52 · click to enlarge
Page 52

International FA Center

Mitsubishi Electronics fre700 — International FA Center diagram (page 52)
Fig. 35 · International FA Center

zNorth American FA Center

zIndia FA Center

MITSUBISHI ELECTRIC AUTOMATION, INC. 500 Corporate Woods Parkway, Vernon Hills, IL60061 U.S.A TEL. +1-847-478-2100 FAX. +1-847-478-0327

Mitsubishi Electric Asia Pvt. Ltd. Gurgaon Branch

2nd Floor, DLF Building No.9B, DLF Cyber City Phase , Gurgaon 122002, Haryana, India TEL. +91-124-4630300 FAX. +91-124-4630399

zKorean FA Center

MITSUBISHI ELECTRIC AUTOMATION KOREA CO., LTD. B1F,2F, 1480-6, Gayang-Dong, Gangseo-Gu, Seoul, 157-200, Korea TEL. +82-2-3660-9607 FAX. +82-2-3664-0475

zThailand FA Center

MITSUBISHI ELECTRIC AUTOMATION (THAILAND) CO., LTD. Bang-Chan Industrial Estate No.111, Soi Serithai 54, T.Kannayao, A.Kannayao, Bangkok 10230 TEL. +66-2-906-3238 FAX. +66-2-906-3239

zTaiwan FA Center

SETSUYO ENTERPRISE CO., LTD. 6F No.105, Wu Kung 3rd RD, Wu-Ku Hsiang Taipei Hsien, 248, Taiwan TEL. +886-2-2299-2499 FAX. +886-2-2299-2509

zASEAN FA Center

MITSUBISHI ELECTRIC ASIA PTE, LTD. 307 Alexandra Road #05-01/02, Mitsubishi Electric Building, Singapore 159943 TEL. +65-6470-2480 FAX. +65-6476-7439

zBeijing FA Center

MITSUBISHI ELECTRIC AUTOMATION (CHINA) LTD. BEIJING OFFICE 9F Office Tower 1, Henderson Center, 18 Jianguomennei Avenue, Dongcheng District, Beijing, China 100005 TEL. +86-10-6518-8830 FAX. +86-10-6518-8030

zEuropean FA Center

MITSUBISHI ELECTRIC EUROPE B. V. GERMAN BRANCH Gothaer Strasse 8, D-40880 Ratingen, Germany TEL. +49-2102-486-0 FAX. +49-2102-486-1120

zUK FA Center

zRussian FA Center

MITSUBISHI ELECTRIC EUROPE B.V. -Representative Office in St. Petersburg Sverdlovskaya Emb.,44, Bld Sch, BC "Benua";195027, St.Petersburg, Russia TEL. +7-812-633-3496 FAX. +7-812-633-3499

MITSUBISHI ELECTRIC EUROPE B. V. UK BRANCH Travellers Lane, Hatfield, Hertfordshire, AL10 8XB, UK. TEL. +44-1707-276100 FAX. +44-1707-278695

zCentral and Eastern Europe FA Center

MITSUBISHI ELECTRIC EUROPE B.V. CZECH BRANCH Avenir Business Park, Radlicka 714/113a,158 00 Praha 5, Czech Republic TEL. +420-251-551-470 FAX. +420-251-551-471

zTianjin FA Center

MITSUBISHI ELECTRIC AUTOMATION (CHINA) LTD. TIANJIN OFFICE B-2 801/802, Youyi Building, No.50 Youyi Road, Hexi District, Tianjin, China 300061 TEL +86-22-2813-1015 FAX. +86-22-2813-1017

zBrazil FA Center

MELCO-TEC Representacao Comercial e Assessoria Tecnica Ltda. Av. Paulista 1439, conj.74, Bela Vista CEP: 01311-200 Sao Paulo-SP-Brazil TEL. +55-11-3146-2202 FAX. +55-11-3146-2217

zShanghai FA Center

MITSUBISHI ELECTRIC AUTOMATION (CHINA) LTD. 4/F Zhi Fu Plazz, No.80 Xin Chang Road, Shanghai, China 200003 TEL. +86-21-6121-2460 FAX. +86-21-6121-2424

zGuangzhou FA Center

MITSUBISHI ELECTRIC AUTOMATION (CHINA) LTD. GUANGZHOU OFFICE Rm.1609, North Tower, The Hub Center, No.1068, Xing Gang East Road, Haizhu District, Guangzhou, China 510335 TEL. +86-20-8923-6713 FAX. +86-20-8923-6715

Page 53 of the Mitsubishi Electronics fre700 user manual — International FA Center
Page 53 · click to enlarge
Page 53
HEAD OFFICETOKYO BUILDING 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN

IB-0600401ENG-A(1105)MEE Printed in Japan Specifications subject to change without notice.

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the Mitsubishi Electronics fre700

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Mitsubishi Electronics fre700

Be the first to ask — other owners or our team will answer.

Original document

Mitsubishi Electronics fre700 manual PDF

53 pages·3.9 MB·Microwave Oven·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…