FR-E700 INSTRUCTION MANUAL (BASIC)
CC-Link communication function
FR-E720-0.1KNC to 15KNC FR-E740-0.4KNC to 15KNC FR-E720S-0.1KNC to 2.2KNC
Thank you for choosing this Mitsubishi Inverter. This Instruction Manual (Basic) provides handling information and precautions for use of the equipment. Please forward this Instruction Manual (Basic) to the end user.
INSTALLATION AND WIRING .................................................... 2
PRECAUTIONS FOR USE OF THE INVERTER.......................... 22
FAILSAFE OF THE SYSTEM WHICH USES THE INVERTER .... 24
PARAMETER LIST.................................................................... 25
TROUBLESHOOTING ............................................................... 29
PRECAUTIONS FOR MAINTENANCE AND INSPECTION......... 34
SPECIFICATIONS..................................................................... 36
To obtain the Instruction Manual (Applied) and the Safety stop function instruction manual
Contact where you purchased the inverter, your Mitsubishi sales representative, or the nearest Mitsubishi FA Center for the following manuals: y Instruction Manual (Applied) [IB(NA)-0600402ENG] y Safety stop function instruction manual [BCN-A211508-004] These manuals are required if you are going to utilize functions and performance. The PDF version of this manual is also available for download at "MELFANS Web," the Mitsubishi Electric FA network service on the world wide web (URL: http://www.MitsubishiElectric.co.jp/melfansweb)

This Instruction Manual (Basic) provides handling information and precautions for use of the equipment. Please forward this Instruction Manual (Basic) to the end user.
This section is specifically about safety matters
Do not attempt to install, operate, maintain or inspect the inverter until you have read through the Instruction Manual (Basic) and appended documents carefully and can use the equipment correctly. Do not use this product until you have a full knowledge of the equipment, safety information and instructions. In this Instruction Manual (Basic), the safety instruction levels are classified into "WARNING" and "CAUTION".
z Inverter must be installed on a nonflammable wall without
holes (so that nobody touches the inverter heatsink on the rear side, etc.). Mounting it to or near flammable material can cause a fire. z If the inverter has become faulty, the inverter power must
be switched OFF. A continuous flow of large current could cause a fire. z When using a brake resistor, a sequence that will turn OFF
power when a fault signal is output must be configured. Otherwise the brake resistor may overheat due to damage of the brake transistor and possibly cause a fire. z Do not connect a resistor directly to the DC terminals P/+
Incorrect handling may cause hazardous conditions, resulting in death or severe injury.
Incorrect handling may cause hazardous conditions, resulting in medium or slight injury, or may cause only material damage.
and N/-. Doing so could cause a fire.
CAUTION
z The voltage applied to each terminal must be the ones
The level may even lead to a serious consequence according to conditions. Both instruction levels must be followed because these are important to personal safety.
specified in the Instruction Manual. Otherwise burst, damage, etc. may occur. z The cables must be connected to the correct terminals.
Otherwise burst, damage, etc. may occur. z Polarity must be correct. Otherwise burst, damage, etc.
WARNING
may occur. z While power is ON or for some time after power-OFF, do
z While power is ON or when the inverter is running, do not
not touch the inverter as they will be extremely hot. Doing so can cause burns.
open the front cover. Otherwise you may get an electric shock. z Do not run the inverter with the front cover or wiring cover
removed. Otherwise you may access the exposed high- voltage terminals or the charging part of the circuitry and get an electric shock. z Even if power is OFF, do not remove the front cover
Also the following points must be noted to prevent an
except for wiring or periodic inspection. You may accidentally touch the charged inverter circuits and get an electric shock. z Before wiring or inspection, power must be switched OFF.
To confirm that, LED indication of the operation panel must be checked. (It must be OFF.) Any person who is involved in wiring or inspection shall wait for at least 10 minutes after the power supply has been switched OFF and check that there are no residual voltage using a tester or the like. The capacitor is charged with high voltage for some time after power OFF, and it is dangerous. z This inverter must be earthed (grounded). Earthing
(grounding) must conform to the requirements of national and local safety regulations and electrical code (NEC section 250, IEC 536 class 1 and other applicable standards). A neutral-point earthed (grounded) power supply for 400V class inverter in compliance with EN standard must be used. z Any person who is involved in wiring or inspection of this
equipment shall be fully competent to do the work. z The inverter must be installed before wiring. Otherwise
you may get an electric shock or be injured. z Setting dial and key operations must be performed with
dry hands to prevent an electric shock. z Do not subject the cables to scratches, excessive stress,
heavy loads or pinching. Otherwise you may get an electric shock. z Do not change the cooling fan while power is ON. It is
cables with wet hands. Otherwise you may get an electric shock. z When measuring the main circuit capacitor capacity, the
DC voltage is applied to the motor for 1s at powering OFF. Never touch the motor terminal, etc. right after powering OFF to prevent an electric shock.

(5) Emergency stop
CAUTION

z Do not install a power factor correction capacitor or surge
zA safety backup such as an emergency brake must be
suppressor/capacitor type filter on the inverter output side. These devices on the inverter output side may be overheated or burn out. z The connection orientation of the output cables U, V, W to
provided to prevent hazardous condition to the machine and
zWhen the breaker on the inverter input side trips, the
wiring must be checked for fault (short circuit), and internal
the motor affects the rotation direction of the motor.
parts of the inverter for a damage, etc. The cause of the trip
must be identified and removed before turning ON the
z Before starting operation, each parameter must be
confirmed and adjusted. A failure to do so may cause some machines to make unexpected motions.
corrective action must be taken, and the inverter must be
WARNING
z Any person must stay away from the equipment when the
zDo not carry out a megger (insulation resistance) test on
retry function is set as it will restart suddenly after trip.
the control circuit of the inverter. It will cause a failure.
z Since pressing key may not stop output depending
on the function setting status, separate circuit and switch that make an emergency stop (power OFF, mechanical brake operation for emergency stop, etc.) must be provided. z OFF status of the start signal must be confirmed before
z The inverter must be treated as industrial waste.
resetting the inverter fault. Resetting inverter alarm with the start signal ON restarts the motor suddenly. z The inverter must be used for three-phase induction motors.
Many of the diagrams and drawings in this Instruction
Connection of any other electrical equipment to the inverter output may damage the equipment. z Do not modify the equipment. z Do not perform parts removal which is not instructed in this
Manual (Basic) show the inverter without a cover or partially
open for explanation. Never operate the inverter in this
manner. The cover must be always reinstalled and the
manual. Doing so may lead to fault or damage of the product.
Harmonic suppression guideline (when inverters are used in Japan)
z The electronic thermal relay function does not guarantee
protection of the motor from overheating. It is recommended to install both an external thermal and PTC thermistor for overheat protection. z Do not use a magnetic contactor on the inverter input for
special high voltage". (For further details, refer to the
frequent starting/stopping of the inverter. Otherwise the life of the inverter decreases. z The effect of electromagnetic interference must be
reduced by using a noise filter or by other means. Otherwise nearby electronic equipment may be affected. z Appropriate measures must be taken to suppress
harmonics. Otherwise power supply harmonics from the inverter may heat/damage the power factor correction capacitor and generator. z When driving a 400V class motor by the inverter, the
motor must be an insulation-enhanced motor or measures must be taken to suppress surge voltage. Surge voltage attributable to the wiring constants may occur at the motor terminals, deteriorating the insulation of the motor. z When parameter clear or all parameter clear is performed,
the required parameters must be set again before starting operations because all parameters return to the initial value. z The inverter can be easily set for high-speed operation.
Before changing its setting, the performances of the motor and machine must be fully examined. z Stop status cannot be hold by the inverter's brake
function. In addition to the inverter’s brake function, a holding device must be installed to ensure safety. z Before running an inverter which had been stored for a long
period, inspection and test operation must be performed. z For prevention of damage due to static electricity, nearby
metal must be touched before touching this product to eliminate static electricity from your body.

Unpack the inverter and check the capacity plate on the front cover and the rating plate on the inverter side face to ensure that
the product agrees with your order and the inverter is intact. zInverter model

Represents the inverter capacity [kW] E720 Three-phase 200V class
CC-Link communication connector (2-port type) (Refer to page 19)
Switch for manufacturer setting (SW2) Do not change the initial setting (OFF).
Standard control circuit terminal block (Refer to page 6)
∗Location of the capacity plate and the rating plate differs
Refer to the outline dimension drawing. ( Refer to the
· Fan cover fixing screws (M3 × 35mm) These screws are necessary for compliance with the EU Directive (Refer to page 41)

2 INSTALLATION AND WIRING
AC power supply Use within the permissible power supply specifications of the inverter. To ensure safety, use a moulded case circuit breaker, earth leakage circuit breaker or magnetic contactor to switch power ON/OFF.
Load the "QJ61BT11N", "QJ61BT11", "AJ61QBT11", "A1SJ61QBT11", "AJ61BT11" or "A1SJ61BT11" CC-Link system master/local module on the main or extension base unit having the programmable controller CPU used as the master station.
(Refer to page 36)
Moulded case circuit breaker (MCCB) or earth leakage circuit breaker (ELB), fuse The breaker must be selected carefully since an in-rush current flows in the inverter at power ON.
Master station (for example, QJ61BT11N)
(Refer to page 3)
Magnetic contactor (MC) Install the magnetic contactor to ensure safety. Do not use this magnetic contactor to start and stop the inverter. Doing so will cause the inverter life to be shorten.
Approved safety relay module Required for compliance with safety standard.
(Refer to page 3)
Reactor (FR-HAL, FR-HEL option) Reactors (option) must be used when power harmonics measures are taken, the power factor is to be improved or the inverter is installed near a large power supply system (500kVA or more). The inverter may be damaged if you do not use reactors. Select the reactor according to the model. Remove the jumpers across terminals P/+ and P1 to connect the DC reactor.
Brake resistor (FR-ABR, MRS type, MYS type) Braking capability can be improved. (0.4K or higher) Always install a thermal relay when using a brake resistor whose capacity is 11K or higher. (Refer to page 15)
AC reactor (FR-HAL) DC reactor (FR-HEL) *
EMC filter (ferrite core) * (FR-BSF01, FR-BLF)
R/L1 S/L2 T/L3
EMC filter (ferrite core) (FR-BSF01, FR-BLF) Install an EMC filter (ferrite core) to reduce the electromagnetic noise generated from the inverter. Effective in the range from about 1MHz to 10MHz. A wire should be wound four turns at a maximum.
Install an EMC filter (ferrite core) to reduce the electromagnetic noise generated from the inverter. Effective in the range from about 1MHz to 10MHz. When more wires are passed through, a more effective result can be obtained. A wire should be wound four turns or more.
EMC filter (capacitor) * (FR-BIF)
Reduces the radio noise.
* Filterpack (FR-BFP2), which contains DC reactor and EMC filter in one package, is also available.
The regenerative braking capability of the inverter can be exhibited fully. Install this as required.
PR
Devices connected to the output Do not install a power factor correction capacitor, surge suppressor or capacitor type filter on the output side of the inverter. When installing a moulded case circuit breaker on the output side of the inverter, contact each manufacturer for selection of the moulded case circuit breaker.
Earth (Ground) To prevent an electric shock, always earth (ground) the motor and inverter. For reduction of induction noise from the power line of the inverter, it is recommended to wire the earth (ground) cable by returning it to the earth (ground) terminal of the inverter.
Resistor unit (FR-BR) Discharging resistor (GZG, GRZG)
possible within the permissible range. This must be noted especially when the inverter is installed in an enclosure. (Refer to page 4) y Wrong wiring might lead to damage of the inverter. The control signal lines must be kept fully away from the main circuit
to protect them from noise. (Refer to page 5) y Do not install a power factor correction capacitor, surge suppressor or capacitor type filter on the inverter output side.
This will cause the inverter to trip or the capacitor and surge suppressor to be damaged. If any of the above devices are connected, immediately remove them. y Electromagnetic wave interference
The input/output (main circuit) of the inverter includes high frequency components, which may interfere with the communication devices (such as AM radios) used near the inverter. In this case, install options among the capacitor type EMC filter FR-BIF (for use in the input side only), the ferrite core type EMC filter FR-BSF01/FR-BLF, Filterpack, and EMC filter to minimize the interference. ( Refer to the Instruction Manual (Applied)). y Refer to the instruction manual of each option and peripheral devices for details of peripheral devices.

2.1 Peripheral devices
Check the inverter model of the inverter you purchased. Appropriate peripheral devices must be selected according to the capacity.
Refer to the following list and prepare appropriate peripheral devices:
∗1 ySelect an MCCB according to the power supply capacity.
IM
yInstall one MCCB per inverter.
IM
∗2 For the use in the United States or Canada, select a UL and cUL certified fuse with Class T fuse equivalent cut-off
speed or faster with the appropriate rating for branch circuit protection. Alternatively, select a UL489 molded case circuit breaker (MCCB).
∗3 Magnetic contactor is selected based on the AC-1 class. The electrical durability of magnetic contactor is 500,000 times. When the magnetic contactor is
used for emergency stop during motor driving, the electrical durability is 25 times.
When using the MC for emergency stop during motor driving or using on the motor side during commercial-power supply operation, select the MC with class
AC-3 rated current for the motor rated current.
∗4 The power factor may be slightly lower.
y When the inverter capacity is larger than the motor capacity, select an MCCB and a magnetic contactor according to
the inverter model and cable and reactor according to the motor output.
y When the breaker on the inverter input side trips, check for the wiring fault (short circuit), damage to internal parts of
the inverter, etc. Identify the cause of the trip, then remove the cause and power on the breaker.

2.2 Installation of the inverter and instructions
Remove the front cover and wiring cover to fix the inverter to the surface. (Remove the covers in the directions of the arrows.)

FR-E720-1.5KNC or higher FR-E740-0.4KNC or higher FR-E720S-0.75KNC or higher
y When encasing multiple inverters, install them in parallel as a cooling
y For heat dissipation and maintenance, take at least the clearances
shown in the table below from the inverter to the other devices and to
1cm or more 1cm or more 1cm or more ∗1, ∗2 ∗1 ∗1, ∗2
∗1 Take 5cm or more clearances for 5.5K or higher.
∗2 When using the inverters at the surrounding air temperature of 40°C or less, the inverters can be installed without any clearance between
Before installation, check that the environment meets the specifications on page 38.
y Install the inverter on a strong surface securely and vertically with bolts.
y Leave enough clearances and take cooling measures.
y Avoid places where the inverter is subjected to direct sunlight, high temperature and high humidity.
y Install the inverter on a non-flammable wall surface.
Enclosure surface mounting

2.3 Wiring
2.3.1 Terminal connection diagram
*1 DC reactor (FR-HEL) When connecting a DC reactor, remove the jumper across P1 and P/+. Control circuit terminal Main circuit terminal Sink logic
*2 A brake transistor is not built-in to the 0.1K and 0.2K.
*3 Brake resistor (FR-ABR, MRS, MYS type) Install a thermal relay to prevent an overheat and burnout of the brake resistor. (The brake resistor cannot be connected to the 0.1K and 0.2K.)
Single-phase AC power supply
R
PR N/-
MCCB MC
P1 P/+
Three-phase AC power supply
U V W
S/L2 T/L3
IM
Main circuit
Control circuit
24V external power supply
Use Pr.190 RX2 (Y0 terminal) function selection to change the function assigned to the terminal.
Y0
Open collector output Y0 (While the inverter is running)
SE Safety stop signal
Open collector output common Sink/source common
Safety stop input (Channel 1)
Safety stop input (Channel 2)
Safety stop input common
SD L.RUN
LED (operation status indicator)
LEDs turn ON/OFF to indicate the operation status.
RUN
y To prevent a malfunction caused by noise, separate the signal cables more than 10cm from the power cables. Also
separate the main circuit wire of the input side and the output side.
y After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean. When drilling mounting holes
in an enclosure etc., take care not to allow chips and other foreign matter to enter the inverter.
y The output of the single-phase power input specification is three-phase 200V.

2.3.2 Terminal specifications


the power cable to the U, V, W of the inverter. Doing so will damage the inverter. y Connect the motor to U, V, and W. Turning ON the forward rotation switch (signal) at this time rotates the motor

2.3.4 Cables and wiring length
(1) Cable size and other specifications of the main circuit terminals and the earthing terminal
Select the recommended cable size to ensure that a voltage drop will be 2% or less.
If the wiring distance is long between the inverter and motor, a main circuit cable voltage drop will cause the motor torque to
decrease especially at the output of a low frequency.
The following table indicates a selection example for the wiring length of 20m. Three-phase 200V class (when input power supply is 220V)



∗1 The cable size is that of the cable (HIV cable (600V class 2 vinyl-insulated cable) etc.) with continuous maximum permissible temperature of 75°C. Assumes
that the surrounding air temperature is 50°C or less and the wiring distance is 20m or less.
∗2 The recommended cable size is that of the cable (THHW cable) with continuous maximum permissible temperature of 75°C. Assumes that the surrounding
air temperature is 40°C or less and the wiring distance is 20m or less. (Selection example for use mainly in the United States.)
∗3 The recommended cable size is that of the cable (PVC cable) with continuous maximum permissible temperature of 70°C. Assumes that the surrounding air
temperature is 40°C or less and the wiring distance is 20m or less. (Selection example for use mainly in Europe.)
∗4 The terminal screw size indicates the terminal size for R/L1, S/L2, T/L3, U, V, W, PR, P/+, N/-, P1 and a screw for earthing (grounding).
A screw for earthing (grounding) of the FR-E720-15KNC is indicated in ( ).
For single-phase power input, the terminal screw size indicates the size of terminal screw for R/L1, S/L2, U, V, W, PR, P/+, N/-, P1 and a screw for earthing
(grounding).
y Tighten the terminal screw to the specified torque. A screw that has been tighten too loosely can cause a short circuit
or malfunction. A screw that has been tighten too tightly can cause a short circuit or malfunction due to the unit breakage. y Use crimping terminals with insulation sleeve to wire the power supply and motor.

The line voltage drop can be calculated by the following formula:
3 × wire resistance[mΩ/m] × wiring distance[m] × current[A] 1000
Line voltage drop [V]=
Use a larger diameter cable when the wiring distance is long or when it is desired to decrease the voltage drop (torque
The overall wiring length for connection of a single motor or multiple motors should be within the value in the table below.

When driving a 400V class motor by the inverter, surge voltages attributable to the wiring constants may occur at the
motor terminals, deteriorating the insulation of the motor. Take the following measures (1) or (2) in this case.
(1) Use a "400V class inverter-driven insulation-enhanced motor" and set frequency in Pr. 72 PWM frequency selection
according to wiring length.
(2) Connect the surge voltage suppression filter (FR-ASF-H/FR-BMF-H) on the inverter output side.
y Especially for long-distance wiring, the inverter may be affected by a charging current caused by the stray
capacitances of the wiring, leading to a malfunction of the overcurrent protective function, fast response current limit
function, or stall prevention function or a malfunction or fault of the equipment connected on the inverter output side.
If malfunction of fast-response current limit function occurs, disable this function. If malfunction of stall prevention
function occurs, increase the stall level. ( Refer to Pr. 22 Stall prevention operation level and Pr. 156 Stall prevention
operation selection in Chapter 5 of the Instruction Manual (Applied))
y Refer to Chapter 5 of the Instruction Manual (Applied) for details of Pr. 72 PWM frequency selection. Refer to the manual of
the option for details of surge voltage suppression filter (FR-ASF-H/FR-BMF-H).
y When using the automatic restart after instantaneous power failure function with wiring length exceeding than 100m,
select without frequency search (Pr. 162 = "1 (initial setting) or 11"). ( Refer to Chapter 5 of the Instruction Manual
(Applied))

2.3.5 Wiring of control circuit
Recommended wire size:

0.3mm2 to 0.75mm2
For the control circuit wiring, strip off the sheath of wires, and use them with a blade terminal. For a single wire, strip off the sheath of the wire and apply directly. Insert the blade terminal or the single wire into a socket of the terminal.


Wires are not inserted into the shell Crumpled tip
Commercially available blade terminals (as of January 2010) zPhoenix Contact Co.,Ltd.

0.75 (for two wires) AI-TWIN 2 x 0,75-10GY — —
∗A blade terminal with an insulation sleeve compatible with MTW wire which has a thick wire insulation
zNICHIFU Co.,Ltd.
number Insulation product number Blade terminal
crimping tool
0.3 to 0.75 BT 0.75-11 VC 0.75 NH 67
zWiring


When using a single wire or a stranded wire without a blade
terminal, push an open/close button all the way down with a
y When using a stranded wire without a blade terminal, twist enough to avoid short circuit with a nearby terminals or
wires. y Place the flathead screwdriver vertical to the open/close button. In case the blade tip slips, it may cause to damage of
zWire removal Pull the wire with pushing the open/close button all the way down firmly with a flathead screwdriver.


pushing the open/close button all the way down may damage the terminal block. y Use a small flathead screwdriver (Tip thickness:
0.4mm/tip width: 2.5mm). If a flathead screwdriver with a narrow tip is used, terminal block may be damaged. Commercially available product (as of October 2008)
y Place the flathead screwdriver vertical to the open/
close button. In case the blade tip slips, it may cause to damage of inverter or injury.
Terminals SD and SE are common terminals for I/O signals. (Both common terminals are isolated from each other.) Do not earth them. Terminal SD is a common terminal for the 24V external power supply terminal (+24). The open collector circuit is isolated from the internal control circuit by photocoupler. Terminal SE is a common terminal for the open collector output terminal (Y0). The contact input circuit is isolated from the internal control circuit by photocoupler.

2.3.6 Connecting the 24V external power supply
CC-Link communication between the master module and the inverter can be continued while the main power circuit is OFF if the 24V external power supply is connected across terminals +24 and SD. When the main circuit power supply is turned ON, the power supply changes from the 24V external power supply to the main circuit power supply. (1) Specification of the applied 24V external power supply y Input voltage 23.5 to 26.5VDC y Input current 0.7A or less (2) Confirming the 24V external power supply y "EV" flickers in the monitor display on the operation panel while the 24V external power is being supplied. The 24V
external power supply operation signal (EV) is also output. For the EV signal, assign the function to the terminal Y0 or a virtual terminal of CC-Link communication by setting "68 (positive logic) or 168 (negative logic)" in Pr. 190 to Pr. 192 or Pr. 313 to Pr. 315 (Output terminal function selection).
(3) Function of the 24V external power supply operation y When the main power supply is turned ON during the 24V external power supply operation, a reset is performed in the
inverter, then the power supply changes to the main circuit power supply. During the reset operation in the inverter, the inverter cannot be controlled through the CC-Link communication. y The operation stops when the power supply changes to the 24V external power supply from the main circuit power
supply regardless of the operating status (in a stop, in running, in automatic restart after instantaneous power failure, in offline tuning, in main circuit capacitor life measurement).
y All start signals (STF signal, STR signal, and on the operation panel) are invalid during the 24V external power
supply operation. y Faults history and parameters can be read and parameters can be written (when the parameter write from the
operation panel is enabled) using the operation panel keys. y The safety stop function is also valid during the 24V external power supply operation. When the safety stop function is
active, however, "SA" is not displayed because "EV" is displayed. The "EV" display has priority over the "SA" display. y The following items can be monitored during the 24V external power supply operation:
Frequency setting, output current peak value∗, converter output voltage peak value∗, cumulative energization time, actual operation time∗, cumulative power∗, PID set point, PID measured value, PID deviation, and cumulative power 2∗ (dedicated to CC-Link communication) ∗The monitored data is not updated after the power supply is changed from the main circuit power supply. (Refer to Chapter 5 of the Instruction Manual (Applied) for the details of each monitor.) y The valid signals when the 24V external power supply is ON are EV, SAFE, SAFE2, Y90, Y91, Y95, REM, LF, and
ALM. (Other signals are OFF.) (Refer to Chapter 5 of the Instruction Manual (Applied) for the detail of each signal.) y The alarms, which have occurred when the main circuit power supply is ON, continue to be output after the power
supply is changed to the 24V external power supply. Perform the inverter reset to reset the alarms. y The retry function is invalid for all alarms when the 24V external power supply is ON. y If the power supply changes from the main circuit power supply to the 24V external power supply while measuring the
main circuit capacitor's life, the measurement completes after the power supply changes back to the main circuit power supply (Pr.259 = "3").
y When the 24V external power supply is input while the main circuit power supply is OFF, the CC-Link communication
is enabled, but the inverter operation is disabled. y Inrush current higher than the value described in (1) may flow at a power-ON. Confirm that the power supply and
other devices are not affected by the inrush current and the voltage drop caused by it. y When the wiring length between the external power supply and the inverter is long, the voltage often drops. Select the
appropriate wiring size and length to keep the voltage in the rated input voltage range. y In a serial connection of several inverters, the current increases when it flows through the inverter wiring near the power
supply. The increase of the current causes voltage to drop further. When connecting different inverters to different power supplies, use the inverters after confirming that the input voltage of each inverter is within the rated input voltage range. y "E.SAF" may appear when the start-up time of the 24V power supply is too long in the 24V external power supply operation.
Flickering

2.3.7 Safety stop function
The terminals related to the safety stop function are shown below.
S1 ∗1 For input of safety stop channel 1. Between S1 and PC / S2 and PC Open: In safety stop state. Short: Other than safety stop state. S2 ∗1 For input of safety stop channel 2.
PC ∗1 Common terminal for terminal S1 and S2.
Outputs the safety stop status. The signal is output when inverter output is shut off due to the safety stop function.
Y0 or virtual terminal of CC-Link
safety circuit failure∗5) ON: Drive stop (no internal safety circuit failure∗5)
Outputs when an alarm or failure is detected. The signal is output when no internal safety circuit failure∗5 exists.
SE Common terminal for open collector outputs (terminal Y0)
∗1 In the initial status, terminals S1 and S2 are shorted with terminal PC by shortening wire. Remove the shortening wire and connect the safety relay module when using the safety stop function. ∗2 Inverter running (RUN signal) is assigned to the terminal Y0 in the initial status. ∗3 To use the SAFE signal, set "80 (positive logic) or 180 (negative logic)" in any of Pr.190 to Pr.192 or Pr.313 to Pr.315 (Output terminal function selection) to assign the function. ( Refer to Chapter 5 of the Instruction Manual (Applied)) ∗4 To use the SAFE 2 signal, set "81 (positive logic) or 181 (negative logic)" to any of Pr.190 to Pr.192 or Pr.313 to Pr.315 (Output terminal function selection) to assign the function. ( Refer to Chapter 5 of the Instruction Manual (Applied)) ∗5 At an internal safety circuit failure, one of E.SAF, E.6, E.7, and E.CPU is displayed on the operation panel.
recognized. y Use SAFE signal to monitor safety stop status. SAFE signal cannot be used as safety stop input signal to other
devices (other than the safety relay module). y SAFE 2 signal can only be used to output an alarm or to prevent restart of an inverter. The signal cannot be used as
safety stop input signal to other devices.
To prevent restart at fault occurrence, connect terminals Y0 (SAFE 2 signal) and SE to terminals XS0 and XS1, which
are the feedback input terminals of the safety relay module.
By setting Pr. 190 RX2 (terminal Y0) function selection = "81 (SAFE2 signal)", terminal RUN is turned OFF at fault occurrence.

*1 Output signals differ by the setting of Pr. 190 RX2 (terminal Y0) function selection.
the other functions. Set parameters after confirming the function of terminal Y0.
SAFE signal ∗3 · communication∗2 · SAFE2 signal ∗4

Input
Input signal Internal safety circuit∗1 Output signal Inverter operation enable signal S1-PC S2-PC SAFE∗3 SAFE2∗3
OFF — — — OFF OFF Output shutoff (Safe state)
Short Short No failure OFF ON Drive enabled
Failure OFF OFF Output shutoff (Safe state)
Open Open No failure ∗2 ON ON Output shutoff (Safe state)
Failure OFF OFF Output shutoff (Safe state)
Short Open Failure OFF OFF Output shutoff (Safe state)
Open Short Failure OFF OFF Output shutoff (Safe state)
∗1 At an internal safety circuit failure, one of E.SAF, E.6, E.7, and E.CPU is displayed on the operation panel.
∗2 SA is displayed when both of the S1 and S2 signals are in open status and no internal safety circuit failure exists.
∗3 ON: Transistor used for an open collector output is conducted.
OFF: Transistor used for an open collector output is not conducted.
For more details, refer to the Safety stop function instruction manual (BCN-A211508-004). (Refer to the front cover for how to
obtain the manual.)

2.4 Connection of a dedicated external brake resistor (MRS type, MYS type, FR-ABR)
Install a dedicated brake resistor (MRS type, MYS type, FR-ABR) outside when the motor driven by the inverter is made to run by the load, quick deceleration is required, etc. Connect a dedicated brake resistor (MRS type, MYS type, FR-ABR) to terminal P/+ and PR. (For the locations of terminal P/+ and PR, refer to the terminal block layout (page 7).)
Set parameters below. ( Refer to the Instruction Manual (Applied) for the parameter details.)

Connected Brake Resistor Pr. 30 Regenerative function selection Setting Pr. 70 Special regenerative brake duty Setting MRS type, MYS type 0 (initial value) — MYS type (used at 100% torque/6%ED) 1 6%
FR-ABR 1 7.5K or lower 10% 11K or higher 6%
It is recommended to configure a sequence, which shuts off power in the input side of the inverter by the external thermal
relay as shown below, to prevent overheat and burnout of the brake resistor (MRS, MYS) and high duty brake resistor (FR-
ABR) in case the regenerative brake transistor is damaged. (The brake resistor cannot be connected to the 0.1K or 0.2K.)
Thermal relay (OCR) (*1)
High-duty brake resistor (FR-ABR)
R/L1
R
PR
T
*2 ∗1 Refer to the table below for the type number of each capacity of thermal relay and the
diagram below for the connection.
ON OFF
(Always install a thermal relay when using a brake resistor whose capacity is 11K or
∗2 When the power supply is 400V class, install a step-down transformer.
Power Supply
Voltage Brake Resistor Thermal Relay Type (Mitsubishi product) Contact Rating
MRS120W200 TH-N20CXHZ-0.7A
MRS120W100 TH-N20CXHZ-1.3A MRS120W60 TH-N20CXHZ-2.1A MRS120W40 TH-N20CXHZ-3.6A MYS220W50 (two
220VAC 2A (AC11 class)
units in parallel) TH-N20CXHZ-5A
220VDC 0.25A (DC11 class)
Voltage Brake Resistor Thermal Relay Type (Mitsubishi product) Contact Rating
FR-ABR-0.4K TH-N20CXHZ-0.7A
FR-ABR-0.75K TH-N20CXHZ-1.3A FR-ABR-2.2K TH-N20CXHZ-2.1A FR-ABR-3.7K TH-N20CXHZ-3.6A FR-ABR-5.5K TH-N20CXHZ-5A FR-ABR-7.5K TH-N20CXHZ-6.6A FR-ABR-11K TH-N20CXHZ-11A FR-ABR-15K TH-N20CXHZ-11A
110VAC 5A
220VAC 2A (AC11 class)
FR-ABR-H0.4K TH-N20CXHZ-0.24A FR-ABR-H0.75K TH-N20CXHZ-0.35A FR-ABR-H1.5K TH-N20CXHZ-0.9A FR-ABR-H2.2K TH-N20CXHZ-1.3A FR-ABR-H3.7K TH-N20CXHZ-2.1A FR-ABR-H5.5K TH-N20CXHZ-2.5A FR-ABR-H7.5K TH-N20CXHZ-3.6A FR-ABR-H11K TH-N20CXHZ-6.6A FR-ABR-H15K TH-N20CXHZ-6.6A
2/T 1 6/T 3
220VDC 0.25A (DC11 class)
To the inverter terminal P/+
y The brake resistor connected should only be the dedicated brake resistor. y Brake resistor cannot be used with the brake unit.
y Do not use the brake resistor (MRS type, MYS type) with a lead wire extended.
y Do not connect the resistor directly to the terminals P/+ and N/-. This could cause a fire.

2.5 Wiring for CC-Link communication
2.5.1 System configuration example
Mount the "QJ61BT11N", "LJ61BT11", "AJ61QBT11", "A1SJ61QBT11", "AJ61BT11" or "A1SJ61BT11" "CC-Link system master/local module" on the main or extension base unit having the programmable controller CPU used as the master
station. (2) Connect the master station of the CC-Link programmable controller unit to the CC-Link
communication connector of FR-E700-NC with the CC-Link dedicated cable.

y When the CPU has the automatic refresh function (example: QnA series CPU)
Through communication with the corresponding devices using sequence ladder logic, data is automatically transferred to the
refresh buffer of the master station at the execution of the END instruction to perform communication with the remote devices.
y When the CPU does not have the automatic refresh function (example: AnA series CPU)
Data is transferred to the refresh buffer of the master station directly by sequence ladder logic to perform communication with

2.5.2 Connection of several inverters
An inverter can join the link system as a CC-Link remote device station, and such device stations can be controlled and monitored with a user program of a programmable controller. These devices can be useful components of an automated factory. Connect shielding wires of the CC-Link dedicated cable to "SLD" of each unit.
DA DB DG
DA DB DG NC NC NC SLD *4
DA DB DG
Terminating resistor selection switch (SW1) *3
SLD
∗1 Use the terminating resistors supplied with the programmable controller. ∗2 Set "1" and "2" of the terminating resistor selection switch (SW1) to OFF (without terminating resistor) in the middle units.
Without terminating resistor (initial setting)
OFFOFF
O N 1 2
ON OFF
Do not use.
OFF ON
130 Ω
O N 1 2
ON ON
110 Ω
130Ω is a resistance value for the CC-Link Ver.1.00 dedicated high performance cable.
∗3 Set the terminating resistor selection switch (SW1). ( Refer to Chapter 1 of the Instruction Manual (Applied) for switch positions.)
Do not use the built-in terminating resistor selection switch (SW1) when using a one-touch connecter plug with terminating resistor. (SW1-OFF, 2-OFF) (Refer to page 20 for the details of the one-touch connector plug with terminating resistor.) ∗4 Use a conduction area of a P-clip (enclosed item) to ground (earth) shielding wires of the CC-Link dedicated cable to a position (as close as possible to the inverter) on the enclosure. Take caution not to subject the CC-Link communication connector to stress. (Refer to page 19) (1) Maximum number of units connected to one master station (CC-Link Ver.1.10) 42 units (when only inverters are connected)
If any other units are included, the number of stations occupied depends on the unit and therefore the following conditions must be satisfied: {(1 × a) + (2 × b) + (3 × c) + (4 × d)} ≤ 64
a: Number of units occupying 1 station c: Number of units occupying 3 stations b: Number of units occupying 2 stations d: Number of units occupying 4 stations {(16 × A) + (54 × B) + (88 × C)} ≤ 2304
A: Number of remote I/O ≤ 64 B: Number of remote device stations ≤ 42 C: Number of local, standby master and intelligent device stations ≤ 26
(2) Maximum number of units connected to one master station (CC-Link Ver.2.00) 42 units (when only inverters are connected)
a: Number of single setting devices occupying one station b: Number of single setting devices occupying two stations c: Number of single setting devices occupying three stations d: Number of single setting devices occupying four stations a2: Number of double setting devices occupying one station b2: Number of double setting devices occupying two stations c2: Number of double setting devices occupying three stations d2: Number of double setting devices occupying four stations a4: Number of quadruple setting devices occupying one station b4: Number of quadruple setting devices occupying two stations c4: Number of quadruple setting devices occupying three stations d4: Number of quadruple setting devices occupying four stations a8: Number of octuple setting devices occupying one station b8: Number of octuple setting devices occupying two stations c8: Number of octuple setting devices occupying three stations d8: Number of octuple setting devices occupying four stations • 16 × A + 54 × B + 88 × C ≤ 2304 A: Numbers of remote I/O ≤ 64 B: Number of remote device stations ≤ 42 C: Number of local and intelligent device stations ≤ 26

2.5.3 Connection cable and plug
In the CC-Link system, use CC-Link dedicated cables.
If the cable used is other than the CC-Link dedicated cable, the performance of the CC-Link system is not guaranteed.
For the specifications of the CC-Link dedicated cable, refer to the website of the CC-Link Partner Association.
Website of the CC-Link Partner Association http://www.cc-link.org/
y One-touch communication connector plug (as of December 2009)
Refer to the following table for the plug required to fabricate a cable on your own.
A6CON-L5P Mitsubishi Electric Corporation
(1) Cable-end treatment
Apply the following treatment to the CC-Link dedicated cable that is inserted to a one-touch communication connector plug.

y Where possible, round the cable tip that is cut off with a tool such as nippers. If the cable is not rounded, it may get caught in
the middle of a plug, without fully entering into the plug.
y If required, apply an insulation treatment to the shielding wire area where it is not covered by the one-touch communication
Check that a plug cover is snapped into a plug.
y Do not push the plug cover onto the plug before inserting a cable. Once crimped, the plug cover cannot be reused.
Lift up the tail of the plug cover, and fully insert a cable. Insert

different signal wires to the one-touch communication connector
plug as shown in the right figure.
y Insert the cable fully. Failure to do so may cause a crimping failure.
y A cable sometimes comes out of the head of the cover.
In that case, pull the cable a little so that the cable stays under the plug cover.
Plug · Plug cover

Push the plug cover onto the plug with a tool such as pliers. After crimping, check that the plug cover is
securely snapped into the plug as shown in the right figure.
y Misaligned latches between the plug cover and the plug may keep the cover lifted. The plug cover is not sufficiently crimped
in this condition. Push the plug cover until it snaps into the plug.

Connect the CC-Link dedicated cable to the CC-link communication connector.
Use an M4 screw and a conduction area of a P-clip (enclosed item) to ground (earth) shielding wires of the CC-Link dedicated
cable to a position (as close as possible to the inverter) on the enclosure.
Take caution not to subject the CC-Link communication connector to stress.

Take caution not to subject the cables to stress.
After wiring, wire offcuts must not be left in the inverter. Wire offcuts can cause an alarm, failure or malfunction.

2.5.5 Unit replacement while online
Connect an online communication connector to the CC-Link communication connector. The online communication connector
enables a unit replacement without interrupting the communication. Always connect the online communication connector to
CONA (front side) of the CC-Link communication connector. (Do not connect it to CONB (back side) of the CC-Link
communication connector. Doing so will cause a failure or breakage of the inverter and the connectors.)
Also connect a one-touch connector plug with terminating resistor to the CC-Link communication connector of FR-E700-NC at
the end.
(A replacement while online is not available for the units, which are using the built-in terminating resistor selection switches

Use the following online communication connector and one-touch connector plug with terminating resistor.
y One-touch connector plug with terminating resistor (as of December 2009)
A6CON-TR11 Mitsubishi Electric Corporation
y Do not use the online communication connector A6CON-LJ5P (Mitsubishi Electric Corporation) and 35720-L200-B00
AK (3M) for this product. Doing so will cause a failure or breakage of the inverter and the connectors.

2.6 CC-Link function setting
2.6.1 Station number setting (Pr. 542)
y Use Pr. 542 Communication station number (CC-Link) to set station number of the inverter. Set this parameter within the range
of 1 to 64. (Pr. 542 is initially set to "1.")
y Use different station numbers for different devices. (If different devices have the same station number, the
communication cannot be performed properly.)
Inverter No.1 Remote device station
Inverter No.2 Remote device station
Inverter No.3 Remote device station
remote I/O station (occupies one station)
Station 00 Station 01 Station 02 Station 03 Station 04
Number of stations connected is 4.
y Set consecutive numbers for the station numbers. (Do not skip a number in sequence like "station number 1 - station number
2- station number 4".)
The station number does not have to match with the physical connection sequence. (There is no problem with having the
physical connection sequence like "station number 1 - station number 3 - station number 4 - station number 2".)
y One inverter occupies one station. (One remote device station)
y "L.ERR" LED flickers if the setting is changed. When power is switched ON again (inveter is reset), the setting value is
applied and the LED turns OFF.
y Set the transmission speed. (Refer to the manual for the CC-Link master module for details of transmission speed.)
0 (initial setting) 156kbps
2 2.5Mbps
y "L.ERR" LED flickers if the setting is changed. When power is switched ON again (inveter is reset), the setting value is
applied and the LED turns OFF.

3 PRECAUTIONS FOR USE OF THE INVERTER
The FR-E700 series is a highly reliable product, but incorrect peripheral circuit making or operation/handling method may
shorten the product life or damage the product.
Before starting operation, always recheck the following items.
(1) Use crimping terminals with insulation sleeve to wire the power supply and motor.
(2) Application of power to the output terminals (U, V, W) of the inverter will damage the inverter. Never perform
such wiring.
(3) After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean.
When drilling mounting holes in an enclosure etc., take care not to allow chips and other foreign matter to enter the
inverter.
(4) Use cables of the size to make a voltage drop 2% or less.
If the wiring distance is long between the inverter and motor, a main circuit cable voltage drop will cause the motor torque to decrease especially at the output of a low frequency.
Refer to page 8 for the recommended wire sizes.
(5) The overall wiring length should be 500m or less.
Especially for long distance wiring, the fast-response current limit function may decrease or the equipment connected to
the secondary side may malfunction or become faulty under the influence of a charging current due to the stray capacity
of the wiring. Therefore, note the overall wiring length. (Refer to page 9)
The input/output (main circuit) of the inverter includes high frequency components, which may interfere with the
communication devices (such as AM radios) used near the inverter. In this case, install the FR-BIF optional capacitor
type filter (for use in the input side only) or FR-BSF01 common mode filter to minimize interference.
(7) Do not install a power factor correction capacitor, surge suppressor or capacitor type filter on the inverter
output side.
This will cause the inverter to trip or the capacitor and surge suppressor to be damaged. If any of the above devices are connected, immediately remove them. (When using capacitor type filter (FR-BIF) for single-phase power supply
specification, make sure of secure insulation of T-phase, and connect to the input side of the inverter.)
(8) For some short time after the power is switched OFF, a high voltage remains in the smoothing capacitor.
Before wiring or inspecting inside the inverter, wait 10 minutes or longer after turning OFF the power supply, then confirm
that the voltage across the main circuit terminals P/+ and N/- of the inverter is 30VDC or less using a tester, etc. The
capacitor is charged with high voltage for some time after power OFF, and it is dangerous.
(9) If "EV" is displayed on the operation panel, turn off the 24V external power supply before wiring and inspection.
(10) A short circuit or earth (ground) fault on the inverter output side may damage the inverter modules.
y Fully check the insulation resistance of the circuit prior to inverter operation since repeated short circuits caused by
peripheral circuit inadequacy or an earth (ground) fault caused by wiring inadequacy or reduced motor insulation
resistance may damage the inverter modules.
y Fully check the to-earth (ground) insulation and phase to phase insulation of the inverter output side before power-on.
Especially for an old motor or use in hostile atmosphere, securely check the motor insulation resistance etc.

(11) Do not use the inverter input side magnetic contactor to start/stop the inverter.
Since repeated inrush currents at power ON will shorten the life of the converter circuit (switching life is about 1,000,000
times.), frequent starts and stops of the MC must be avoided. Turn ON/OFF the inverter start controlling terminals (STF,
STR) to run/stop the inverter. ( Refer to the Instruction Manual (Applied))
(12) Across P/+ and PR terminals, connect only an external regenerative brake discharging resistor.
Do not connect a mechanical brake.
The brake resistor cannot be connected to the 0.1K or 0.2K. Leave terminals P/+ and PR open.
Also, never short between these terminals.
(13) Do not apply a voltage higher than the permissible voltage to the inverter I/O signal circuits.
Application of a voltage higher than the permissible voltage to the inverter I/O signal circuits or opposite polarity may
damage the I/O devices.
MC2 which are used for bypass operation.
Interlock U V W
When the wiring is incorrect and if there is a bypass operation
IM
circuit as shown right, the inverter will be damaged when the
power supply is connected to the inverter U, V, W terminals, due to arcs generated at the time of switch-over or chattering caused
by a sequence error.
(15) If the machine must not be restarted when power is restored after a power failure, provide a magnetic contactor
in the inverter's input side and also make up a sequence which will not switch ON the start signal.
If the start signal (start switch) remains ON after a power failure, the inverter will automatically restart as soon as the
power is restored.
On the inverter input side, connect a MC for the following purposes. (Refer to page 3 for selection.) 1)To release the inverter from the power supply when a fault occurs or when the drive is not functioning (e.g. emergency stop operation). For example, MC avoids overheat or burnout of the brake resistor when heat capacity of the resistor is insufficient or brake regenerative transistor is damaged with short while connecting an optional brake resistor. 2)To prevent any accident due to an automatic restart at restoration of power after an inverter stop made by a power failure 3)To separate the inverter from the power supply to ensure safe maintenance and inspection work. The inverter's input side MC is used for the above purpose, select class JEM1038-AC3 MC for the inverter input side current when making an emergency stop during normal operation.
Switch the magnetic contactor between the inverter and motor only when both the inverter and motor are at a stop. When the magnetic contactor is turned ON while the inverter is operating, overcurrent protection of the inverter and such will activate. When MC is provided for switching to the commercial power supply, for example, switch it ON/OFF after the inverter and motor have stopped.
When performing operation of frequent start/stop of the inverter, rise/fall in the temperature of the transistor element of
the inverter will repeat due to a repeated flow of large current, shortening the life from thermal fatigue. Since thermal
fatigue is related to the amount of current, the life can be increased by reducing current at locked condition, starting
current, etc. Decreasing current may increase the life. However, decreasing current will result in insufficient torque and the inverter may not start. Therefore, choose the inverter which has enough allowance for current (up to 2 rank larger in
capacity).
(19) Make sure that the specifications and rating match the system requirements.
Power supply · Undesirable current · Inverter

4 FAILSAFE OF THE SYSTEM WHICH USES THE INVERTER
When a fault occurs, the inverter trips to output a fault signal. However, a fault output signal may not be output at an inverter fault occurrence when the detection circuit or output circuit fails, etc. Although Mitsubishi assures best quality products, provide an interlock which uses inverter status output signals to prevent accidents such as damage to machine when the inverter fails for some reason and at the same time consider the system configuration where failsafe from outside the inverter, without using the inverter, is enabled even if the inverter fails.
(1) Interlock method which uses the inverter status output signals
By providing interlocks, inverter fault can be detected. For the interlocks, use different status output signals of the
inverter (virtual terminals of the CC-Link communication) in combinations shown below.
Refer to Chapter 4
Operation check of an alarm contact Circuit error detection by negative logic
Fault output signal (ALM signal)
of the Instruction Manual (Applied).
Refer to Chapter 4
of the Instruction Manual (Applied).
Start signal (STF signal, STR signal) Running signal (RUN signal)
Refer to Chapter 4
of the Instruction Manual (Applied).
Start signal (STF signal, STR signal) Output current detection signal (Y12 signal)
Refer to Chapter 4
of the Instruction Manual (Applied).
(2) Backup method outside the inverter Even if the interlock is provided by the inverter status signal, enough failsafe is not ensured depending on the failure status of the inverter itself. For example, even if the interlock is provided using the inverter fault output signal, start signal and RUN signal output, there is a case where a fault output signal is not output and RUN signal is kept output even if an inverter fault occurs. Provide a speed detector to detect the motor speed and current detector to detect the motor current and consider the backup system such as checking up as below according to the level of importance of the system.
1) Start signal and actual operation check Check the motor running and motor current while the start signal is input to the inverter by comparing the start signal to the inverter and detected speed of the speed detector or detected current of the current detector. Note that the motor current runs as the motor is running for the period until the motor stops since the inverter starts decelerating even if the start signal turns off. For the logic check, configure a sequence considering the inverter deceleration time. In addition, it is recommended to check the three-phase current when using the current detector.
air volume, etc.)
To the alarm detection sensor

5 PARAMETER LIST
For simple variable-speed operation of the inverter, the initial setting of the parameters may be used. Set the necessary
parameters to meet the load and operational specifications. Parameter setting, change and check can be made from the
operation panel.

y indicates simple mode parameters. (Initially set to extended mode)
y The parameters surrounded by a black border in the table allow its setting to be changed during operation even if "0" (initial
value) is set in Pr. 77 Parameter write selection. (Note that the Pr.77 setting cannot be changed through the CC-Link
26 Multi-speed setting (speed 6) 0 to 400Hz, 9999 9999
∗1 1 Maximum frequency 0 to 120Hz 120Hz
27 Multi-speed setting (speed 7) 0 to 400Hz, 9999 9999
4 Multi-speed setting (high speed) 0 to 400Hz 60Hz
5 Multi-speed setting (middle speed) 0 to 400Hz 30Hz
31 Frequency jump 1A 0 to 400Hz, 9999 9999
6 Multi-speed setting (low speed) 0 to 400Hz 10Hz
32 Frequency jump 1B 0 to 400Hz, 9999 9999
7 Acceleration time 0 to 3600/ 360s 5/10/15s
33 Frequency jump 2A 0 to 400Hz, 9999 9999
8 Deceleration time 0 to 3600/ 360s 5/10/15s
34 Frequency jump 2B 0 to 400Hz, 9999 9999
9 Electronic thermal O/L relay 0 to 500A Rated inverter
35 Frequency jump 3A 0 to 400Hz, 9999 9999
10 DC injection brake operation frequency 0 to 120Hz 3Hz
36 Frequency jump 3B 0 to 400Hz, 9999 9999
11 DC injection brake operation time 0 to 10s 0.5s
12 DC injection brake operation voltage 0 to 30% 6/4/2% ∗3
40 RUN key rotation direction selection 0, 1 0
18 High speed maximum frequency 120 to 400Hz 120Hz
45 Second deceleration time 0 to 3600/ 360s, 9999 9999
46 Second torque boost 0 to 30%, 9999 9999
19 Base frequency voltage 0 to 1000V, 8888, 9999 9999
47 Second V/F (base frequency) 0 to 400Hz, 9999 9999
22 Stall prevention operation level 0 to 200% 150%
23 Stall prevention operation level compensation factor at double speed
0, 5, 7 to 12, 14, 20, 23 to 25, 52 to 57, 61, 62, 100
24 Multi-speed setting (speed 4) 0 to 400Hz, 9999 9999
54 to 56 Parameter for manufacturer setting. Do not set.
25 Multi-speed setting (speed 5) 0 to 400Hz, 9999 9999
57 Restart coasting time 0, 0.1 to 5s, 9999 9999

Initial Value
Parameter Name Setting
Initial Value
Range
Range
58 Restart cushion time 0 to 60s 1s
117 to 124 Parameter for manufacturer setting. Do not set.
59 Remote function selection 0, 1, 2, 3 0
125 Frequency setting gain frequency 0 to 400Hz 60Hz
60 Energy saving control selection 0, 9 0
126 Parameter for manufacturer setting. Do not set.
61 Reference current 0 to 500A, 9999 9999
127 PID control automatic switchover frequency
62 Reference value at acceleration
0 to 200%, 9999 9999
128 PID action selection
40 to 43, 50,
63 Reference value at deceleration
0 to 200%, 9999 9999
129 PID proportional band 0.1 to 1000%,
65 Retry selection 0 to 5 0
66 Stall prevention operation reduction starting frequency 0 to 400Hz 60Hz
130 PID integral time 0.1 to 3600s,
67 Number of retries at fault occurrence
0 to 10, 101 to 110 0
131 PID upper limit 0 to 100%,
68 Retry waiting time 0.1 to 360s 1s
132 PID lower limit 0 to 100%,
69 Retry count display erase 0 0
70 Special regenerative brake duty 0 to 30% 0%
133 Parameter for manufacturer setting. Do not set.
134 PID differential time 0.01 to 10.00s,
0, 1, 3 to 6, 13 to 16, 23, 24, 40, 43, 44, 50, 53, 54
145, 146 Parameter for manufacturer setting. Do not set.
147 Acceleration/deceleration time switching frequency
0 to 400Hz, 9999 9999
72 PWM frequency selection 0 to 15 1
150 Output current detection level 0 to 200% 150%
151 Output current detection signal delay time 0 to 10s 0s
73, 74 Parameter for manufacturer setting. Do not set.
75 Reset selection/PU stop selection
0 to 3, 14 to 17 14
152 Zero current detection level 0 to 200% 5%
77 ∗6 Parameter write selection 0, 1, 2 0
153 Zero current detection time 0 to 1s 0.5s
78 Reverse rotation prevention selection 0, 1, 2 0
156 Stall prevention operation selection
0 to 31, 100, 101 0
79 ∗9 Operation mode selection 0, 1, 2, 3, 4,
157 OL signal output timer 0 to 25s, 9999 0s
160 User group read selection 0, 1, 9999 0
80 Motor capacity 0.1 to 15kW, 9999 9999
161 Frequency setting/key lock operation selection 0, 1, 10, 11 0
81 Number of motor poles 2, 4, 6, 8, 10, 9999 9999
162 Automatic restart after instantaneous power failure selection
0 to 500A (0 to ****), 9999 ∗5 9999
0, 1, 10, 11 1
82 Motor excitation current
165 Stall prevention operation level for restart 0 to 200% 150%
83 Rated motor voltage 0 to 1000V 200V/ 400V ∗4
168, 169 Parameter for manufacturer setting. Do not set.
84 Rated motor frequency 10 to 120Hz 60Hz
170 Watt-hour meter clear 0, 10, 9999 9999
89 Speed control gain (Advanced magnetic flux vector)
0 to 200%, 9999 9999
171 Operation hour meter clear 0, 9999 9999
172 User group registered display/ batch clear
9999, (0 to 16) 0
0 to 50Ω (0 to ****), 9999 ∗5 9999
90 Motor constant (R1)
173 User group registration 0 to 999, 9999 9999
0 to 50Ω (0 to ****), 9999 ∗5 9999
174 User group clear 0 to 999, 9999 9999
91 Motor constant (R2)
178, 179 Parameter for manufacturer setting. Do not set.
0 to 1000mH (0 to 50Ω, 0 to ****), 9999 ∗5 9999
180 RY4 function selection 0 to 5, 7, 8,
92 Motor constant (L1)
181 RY3 function selection 1
14 to 16, 18,
0 to 1000mH (0 to 50Ω, 0 to ****), 9999 ∗5 9999
182 RY2 function selection 2
183 RY9 function selection 24
93 Motor constant (L2)
184 RYB function selection 62
0 to 100% (0 to 500Ω, 0 to ****), 9999 ∗5
94 Motor constant (X)
96 Auto tuning setting/status 0, 1, 11, 21 0


251 Output phase loss protection selection 0, 1 1
255 Life alarm status display (0 to 15) 0
256 Inrush current limit circuit life display (0 to 100%) 100%
257 Control circuit capacitor life display (0 to 100%) 100%
258 Main circuit capacitor life display (0 to 100%) 100%
261 Power failure stop selection 0, 1, 2 0
268 Monitor decimal digits selection 0, 1, 9999 9999
276 PWM carrier frequency at stop-on contact 0 to 9, 9999 9999
277 Stall prevention operation current switchover 0, 1 0
280 Brake opening current detection time 0 to 2s 0.3s
232 Multi-speed setting (speed 8) 0 to 400Hz, 9999 9999
281 Brake operation time at start 0 to 5s 0.3s
233 Multi-speed setting (speed 9) 0 to 400Hz, 9999 9999
283 Brake operation time at stop 0 to 5s 0.3s
287 Droop filter time constant 0 to 1s 0.3s
292 Automatic acceleration/ deceleration 0, 1, 7, 8, 11 0
0 to 6, 99, 100 to 106, 199, 9999 9999
297 Password lock/unlock 1000 to 9999 (0 to 5) 9999
298 Frequency search gain 0 to 32767, 9999 9999
299 Rotation direction detection selection at restarting 0, 1, 9999 0
246 Slip compensation time constant 0.01 to 10s 0.5s
247 Constant-power range slip compensation selection 0, 9999 9999
249 Earth (ground) fault detection at start 0, 1 0

Initial Value
Parameter Name Setting
Initial Value
Range
Range
0, 1, 3, 4, 7, 8,
800 Control method selection 20, 30 20
11 to 16, 20,
0 to 500A (0 to ****) , 9999 ∗5 9999
313 RX9 function selection
25, 26, 46, 47,
64, 68, 80, 81,
872 ∗8 Input phase loss protection selection 0, 1 1
90, 91, 93, 95,
882 Regeneration avoidance operation selection 0, 1, 2 0
314 RXA function selection 9999
883 Regeneration avoidance operation level 300 to 800V 400VDC/ 780VDC
885 Regeneration avoidance compensation frequency limit value
0 to 10Hz, 9999 6Hz
315 RXB function selection 9999
886 Regeneration avoidance voltage gain 0 to 200% 100%
888 Free parameter 1 0 to 9999 9999
338 to 340 Parameter for manufacturer setting. Do not set.
889 Free parameter 2 0 to 9999 9999
342 Communication EEPROM write selection 0, 1 0
C0 Parameter for manufacturer setting. Do not set.
C2 Frequency setting bias
343 Parameter for manufacturer setting. Do not set.
frequency 0 to 400Hz 0Hz
349 Communication reset selection 0, 1 0
C3 to C7, C22 to C25,
450 Second applied motor 0, 1, 9999 9999
990, 991 Parameter for manufacturer setting. Do not set.
495 Remote output selection 0, 1, 10, 11 0
496 Remote output data 1 0 to 4095 0
Pr.CL Parameter clear 0, 1 0
497 Parameter for manufacturer setting. Do not set.
ALLC All parameter clear 0, 1 0
500 Communication error execution waiting time 0 to 999.8s 0
Er.CL Faults history clear 0, 1 0
Pr.CH Initial value change list — —
501 Communication error occurrence count display 0 0
∗1 Differ according to capacities.
502 Stop mode selection at communication error 0, 1, 2, 3 0
503 Maintenance timer 0 (1 to 9998) 0
504 Maintenance timer alarm output set time
0 to 9998, 9999 9999
∗2 Differ according to capacities.
541 Frequency command sign selection (CC-Link) 0, 1 0
542∗7 Communication station number (CC-Link) 1 to 64 1
∗3 Differ according to capacities.
543∗7 Baud rate selection (CC-Link) 0 to 4 0
544∗6 CC-Link extended setting 0, 1, 12, 14, 18 0
547 to 551 Parameter for manufacturer setting. Do not set.
550 NET mode operation command source selection 0, 2, 9999 9999
∗4 The initial value differs according to the voltage class. (200V class/400V
∗5 The range differs according to the Pr. 71 setting.
551 PU mode operation command source selection 2 to 4, 9999 9999
∗6 The setting cannot be changed through the FL remote communication.
∗7 Changing the setting value causes the "L.ERR" LED to flicker. Turn OFF
555 Current average time 0.1 to 1.0s 1s
the power once, then turn ON again (inverter reset) to apply the setting
556 Data output mask time 0 to 20s 0s
and to turn OFF the LED.
∗8 Available only for the three-phase power input model.
557 Current average value monitor signal output reference current 0 to 500A
∗9 Settings cannot be written during CC-Link communication (under
Network operation mode).
563 Energization time carrying- over times (0 to 65535) 0
564 Operating time carrying-over times (0 to 65535) 0
571 Holding time at a start 0 to 10s, 9999 9999
611 Acceleration time at a restart 0 to 3600s, 9999 9999
653 Speed smoothing control 0 to 200% 0
665 Regeneration avoidance frequency gain 0 to 200% 100

6 TROUBLESHOOTING
When a fault occurs in the inverter, the inverter trips and the display on the operation panel automatically changes to one of
the fault or alarm indications on page 30. If the fault does not correspond to any of the following faults or if you have any other problem, please contact your sales
representative.
z Retention of fault output signal .. When the magnetic contactor (MC) provided on the input side of the inverter is opened when
a fault occurs, the inverter's control power will be lost and the fault output will not be held.
z Fault or alarm indication When a fault or alarm occurs, the operation panel display automatically switches to the fault
or alarm indication.
z Resetting method When a fault occurs, the inverter output is kept stopped. Unless reset, therefore, the inverter
cannot restart. z When any fault occurs, take the appropriate corrective action, then reset the inverter, and resume operation.
Not doing so may lead to the inverter fault and damage.
Inverter fault or alarm indications are roughly categorized as below.
A message regarding operational fault and setting fault by the operation panel is displayed. The inverter does not trip.
The inverter does not trip even when a warning is displayed. However, failure to take appropriate measures will lead to a fault.
The inverter does not trip. An alarm can also be output with a parameter setting.
When a fault occurs, the inverter trips and a fault signal is output. The ALM signal is also output.
y For the details of fault displays and other malfunctions, also refer to the Instruction Manual (Applied). y Past eight faults can be displayed using the setting dial.
The inverter can be reset by performing any of the following operations. Note that the internal thermal integrated value of the
electronic thermal relay function and the number of retries are cleared (erased) by resetting the inverter.
Inverter recovers about 1s after reset is released.
Operation 1: Using the operation panel, press to reset the inverter.
(This may only be performed when a fault occurs.)
communication. (Inverter reset though CC-Link communication is invalid during communication error.)
indicator of the operation panel turns OFF.
REMARKS
y Use the operation 1 or 2 to reset when using the 24V external power supply.
start signal ON restarts the motor suddenly.

6.2 List of fault or alarm indications
When a fault occurs, the inverter trips and the PU display automatically changes to one of the following fault or alarm indications.
Operation panel lock Appears when operation was tried during operation panel lock. Press for 2s to release lock.
Password locked Appears when a password restricted parameter is read/written.
Enter the password in Pr. 297 Password lock/unlock to unlock the password function before operating.
y Check the setting of Pr. 77 Parameter write selection. y Check the settings of Pr. 31 to Pr. 36 (frequency jump). y After stopping operation, make parameter setting. y After setting the operation mode to the "PU operation mode",
Parameter write error Appears when an error occurred during parameter writing.
make parameter setting.
Inverter reset Appears when the RES signal is ON. y Turn OFF the reset command
y Increase or decrease the Pr. 0 Torque boost setting by 1% and
check the motor status. y Set a larger value in Pr. 7 Acceleration time and Pr. 8
Deceleration time. y Reduce the load weight. y Try Advanced magnetic flux vector control and General-
purpose magnetic flux vector control. y Change the Pr. 14 Load pattern selection setting. y Set stall prevention operation current in Pr. 22 Stall prevention
Stall prevention (overcurrent) Appears during overcurrent stall prevention.
operation level. (The initial value is 150%.) The acceleration/ deceleration time may change. Increase the stall prevention operation level with Pr. 22 Stall prevention operation level, or disable stall prevention with Pr. 156 Stall prevention operation selection. (Operation at OL occurrence can be selected using Pr. 156.)
Appears during overvoltage stall prevention. Appears while the regeneration avoidance function is activated.
The deceleration time may change. Increase the deceleration time using Pr. 8 Deceleration time.
Appears if the regenerative brake duty reaches or exceeds 85% of the Pr. 70 Special regenerative brake duty value. If the regenerative brake duty reaches 100%, a regenerative overvoltage (E. OV_) occurs.
y Increase the deceleration time. y Check that the Pr. 30 Regenerative function selection and Pr. 70
Regenerative brake prealarm ∗6
Special regenerative brake duty settings.
Electronic thermal relay function prealarm
Appears when the electronic thermal O/L relay has reached 85% of the specified value.
y Reduce the load and frequency of operation. y Set an appropriate value in Pr. 9 Electronic thermal O/L relay.
PU stop Appears when on the operation panel was
Turn the start signal OFF and release with .
pressed during External operation.
Maintenance signal output ∗6
Appears when the cumulative energization time has exceeded the maintenance output timer set value.
Setting "0" in Pr. 503 Maintenance timer erases the signal.
Undervoltage Appears when the main circuit power became low voltage.
Check the power supply system equipment such as power supply.
y When not using the safety stop function, short across
terminals S1 and PC and across S2 and PC with shorting wire for the inverter to run. y If is indicated when across S1 and PC and across S2 and PC are both shorted while using the safety stop function (drive enabled), internal failure might be the cause. Check the wiring of terminals S1, S2 and PC and contact your sales representative if the wiring has no fault.
Safety stop Appears when the safety stop function is activated (during output shutoff).
Turn ON the power supply for the inverter (main circuit). y If appears by turning ON the power supply of the inverter (main circuit) while the external 24V power is supplied, check the power supply (for the main circuit). y Check if the jumper is installed securely between terminal
24V external power supply operation
Flickers when the main circuit power supply is not supplied and the 24V external power is supplied.
P/+ and P1.
Appears when the cooling fan remains stopped when operation is required or when the speed has decreased.
Check for fan alarm. Please contact your sales representative.
y Increase the acceleration time. (Shorten the downward
acceleration time for the lift.) y When "E.OC1" is always lit at start, disconnect the motor
once and start the inverter. If "E.OC1" is still lit, contact your sales representative. y Check the wiring to make sure that output short circuit/
Overcurrent trip during acceleration
Appears when an overcurrent occurred during acceleration.
ground fault does not occur. y Set 50Hz in Pr. 3 Base frequency. y Lower the setting of stall prevention operation level. y Activate the fast-response current limit operation. y Set base voltage (rated voltage of the motor, etc.) in Pr. 19
Base frequency voltage.

y Keep load stable. y Check the wiring to make sure that output short circuit/
Overcurrent trip during constant speed
Appears when an overcurrent occurred during constant speed operation.
ground fault does not occur. y Lower the setting of stall prevention operation level. y Activate the fast-response current limit operation.
y Increase the deceleration time. y Check the wiring to make sure that output short circuit/
Overcurrent trip during deceleration or stop
Appears when an overcurrent occurred during deceleration and at a stop.
ground fault does not occur. y Check the mechanical brake operation. y Lower the setting of stall prevention operation level. y Activate the fast-response current limit operation.
y Decrease the acceleration time. y Use regeneration avoidance function (Pr. 882, Pr. 883, Pr. 885,
Regenerative overvoltage trip during acceleration
Appears when an overvoltage occurred during acceleration.
Pr. 886). y Set the Pr.22 Stall prevention operation level correctly.
y Keep load stable. y Use regeneration avoidance function (Pr. 882, Pr. 883, Pr. 885,
Regenerative overvoltage trip during constant speed
Appears when an overvoltage occurred during constant speed operation.
Pr. 886). y Use the brake resistor, brake unit or power regeneration
common converter (FR-CV) as required. y Set the Pr.22 Stall prevention operation level correctly.
y Increase the deceleration time. (Set the deceleration time
which matches the moment of inertia of the load) y Make the brake cycle longer. y Use regeneration avoidance function (Pr. 882, Pr. 883, Pr. 885,
Regenerative overvoltage trip during deceleration or stop
Appears when an overvoltage occurred during deceleration and at a stop.
Pr. 886). y Use the brake resistor, brake unit or power regeneration
common converter (FR-CV) as required.
y Increase acceleration/deceleration time. y Adjust the torque boost setting. y Set the load pattern selection setting according to the load
Inverter overload trip (electronic thermal relay function)
Appears when the electronic thermal relay function for inverter element protection was activated.
pattern of the using machine. y Reduce the load weight. y Set the surrounding air temperature to within the
specifications.
y Reduce the load weight. y For a constant-torque motor, set the constant-torque motor in
Motor overload trip (electronic thermal relay function) ∗1
Appears when the electronic thermal relay function for motor protection was activated.
Pr. 71 Applied motor. y Check that stall prevention operation setting is correct.
y Set the surrounding air temperature to within the
specifications. y Clean the heatsink. y Replace the cooling fan.
Heatsink overheat Appears when the heatsink was overheated.
Appears if one of the three phases on the inverter input side is lost. It may also appear if phase-to-phase voltage of the three-phase power input becomes largely unbalanced.
y Wire the cables properly. y Repair a break portion in the cable. y Check the Pr. 872 Input phase loss protection selection setting. y Set Pr. 872 = "0" (without input phase loss protection) when
Input phase loss ∗6 ∗7 ∗8
three-phase input voltage is largely unbalanced.
Appears when the output frequency drops to 1Hz as a result of deceleration due to the excess motor load.
Reduce the load weight. (Check the Pr. 22 Stall prevention operation level setting.)
This function stops the inverter output if an alarm occurs in the brake circuit, e.g. damaged brake transistors. In this case, the inverter must be powered off immediately.
Brake transistor alarm detection
Replace the inverter.
Output side earth (ground) fault overcurrent at start ∗6
Appears when an earth (ground) fault occurred on the inverter's output side. (detects only at a start)
Remedy the ground fault portion.
If one of the three phases (U, V, W) on the inverter's output side (load side) is lost during inverter operation (except during DC injection brake operation and when output frequency is under 1Hz), inverter stops the output.
y Wire the cables properly. y Check the Pr. 251 Output phase loss protection selection setting.
∗5 · Stall prevention stop · Output phase loss

y Refer to "Error check with LEDs" in the Instruction Manual
(Applied), and take a corrective action for the error. y Check the connection of the CC-Link dedicated cable. y Check that each CC-Link dedicated cable length between
nodes is within the specified value. (Refer to the User's Manual of the CC-Link master module for the cable length between the nodes compatible with the CC-Link Ver.1.00.) y Set the built-in terminating resistor switch to ON at the end
Stops inverter outputs at a communication line error of CC-Link communication.
stations. Alternatively, correctly connect the one-touch connector plug with terminating resistor.
y Set Pr.296 ≠ "0 or 100" for the password lock. y If the problem still persists after taking the above measure,
Option fault y Appears when Pr.296 = "0 or 100."
contact your sales representative.
y Take measures against noises if there are devices producing
y Stops the inverter output if there is excess
excess electrical noises around the inverter. y Set back the switch for manufacturer setting in the initial
electrical noise around the inverter. y Also appears when a switch for manufacturer
setting. y If the problem still persists after taking the above measure,
setting is changed.
contact your sales representative.
Please contact your sales representative. When performing parameter write frequently for communication purposes, set "1" in Pr. 342 to enable RAM write. Note that powering OFF returns the inverter to the status before RAM write.
Parameter storage device fault
Appears when operation of the element where parameters stored became abnormal. (control board)
Inverter output is stopped when the control circuit board and the main circuit board do not match with each other.
Please contact your sales representative. (For parts replacement, consult the nearest Mitsubishi FA Center.)
Retry count excess ∗6 Operation restart within the set number of retries has failed. Eliminate the cause of the error preceding this error indication.
y Take measures against noises if there are devices producing
excess electrical noises around the inverter. y Check the connection between terminals PC and SD. (E6/
CPU fault Appears during the CPU and peripheral circuit errors.
E7) y Please contact your sales representative.
Stops inverter outputs when a sequence fault occurs while using the brake sequence function (Pr. 278 to Pr. 283).
Brake sequence fault ∗6
Check the parameters and correct the wiring.
Configure a circuit where frequent power ON/OFF is not repeated. If the problem still persists after taking the above measure, please contact your sales representative.
Inrush current limit circuit fault
Appears when the resistor of the inrush current limit circuit overheated.
Internal circuit fault Appears when an internal circuit fault has occurred. Please contact your sales representative.
y When not using the safety stop function, short across
terminals S1 and PC and across S2 and PC with shorting wire. y When using the safety stop function, check that wiring of
Safety circuit fault Appears when safety circuit is malfunctioning.
terminal S1, S2 and PC is correct and the safety stop input signal source such as safety relay module is operating properly. Refer to the Safety stop function instruction manual (BCN-211508-004) for causes and countermeasures. (Please contact your sales representative for the manual.)
∗1 Resetting the inverter initializes the internal cumulative heat value of the electronic thermal relay function.
∗2 The error message shows an operational error. The inverter output is not shut off.
∗3 Warnings are messages given before fault occur. The inverter output is not shut off.
∗4 Alarms warn the operator of failures with output signals. The inverter output is not shut off.
∗5 When faults occur, the protective functions are activated to trip the inverter and output the fault signals.
∗6 This protective function does not function in the initial status.
∗7 This protective function activates when Pr.872 Input phase loss protection selection = "1".
∗8 This function is only available for three-phase power input models.

6.3 Check first when you have a trouble
If the following malfunctions occur, refer to the troubleshooting in the Instruction Manual (Applied).
y Motor does not start
y Motor or machine is making abnormal acoustic noise y Inverter generates abnormal noise
y Motor generates heat abnormally
y Motor rotates in the opposite direction
y Speed greatly differs from the setting
y Acceleration/deceleration is not smooth
y Speed varies during operation
y Operation mode is not changed properly
y Operation panel display is not operating y Motor current is too large
y Speed does not accelerate
y Unable to write parameter setting

7 PRECAUTIONS FOR MAINTENANCE AND INSPECTION
The inverter is a static unit mainly consisting of semiconductor devices. Daily inspection must be performed to prevent any fault from occurring due to the adverse effects of the operating environment, such as temperature, humidity, dust, dirt and vibration, changes in the parts with time, service life, and other factors.
y For the details of fault displays and other malfunctions, also refer to the Instruction Manual (Applied).
Before wiring or inspecting inside the inverter, wait 10 minutes or longer after turning OFF the power supply, then confirm that the voltage across the main circuit terminals P/+ and N/- of the inverter is 30VDC or less using a tester, etc. The capacitor is charged with high voltage for some time after power OFF, and it is dangerous. If "EV" is displayed on the operation panel, turn OFF the 24V external power supply before inspection.
Area of
Inspection
Item Description
Check Daily Periodic
Inspection
Occurrence
Check the surrounding air temperature, humidity, dirt, corrosive gas, oil mist, etc. { Improve environment
Overall unit Check for unusual vibration and noise. { Check alarm location and retighten Power supply
Check that the main circuit voltages are normal.∗1 { Inspect the power supply
(1) Check with megger (across main circuit
terminals and earth (ground) terminal). { Contact the manufacturer
(2) Check for loose screws and bolts. { Retighten (3) Check for overheat traces on the parts. { Contact the manufacturer (4) Check for stain. { Clean
(1) Check conductors for distortion.
{ Contact the manufacturer
(2) Check cable sheaths for breakage and
{ Contact the manufacturer
deterioration (crack, discoloration, etc.).
Terminal block Check for damage. { Stop the device and contact the manufacturer.
(1) Check for liquid leakage. { Contact the manufacturer (2) Check for safety valve projection and bulge. { Contact the manufacturer (3) Visual check and judge by the life check of the
Smoothing aluminum electrolytic capacitor
main circuit capacitor ( Refer to Chapter 7 of the Instruction Manual (Applied))
Relay Check that the operation is normal and no chatter is heard. { Contact the manufacturer
(1) Check that the output voltages across phases
with the inverter operated alone is balanced. { Contact the manufacturer
(2) Check that no fault is found in protective and
display circuits in a sequence protective operation test.
{ Contact the manufacturer
Overall (1) Check for unusual odor and discoloration. { Stop the device and contact the manufacturer. (2) Check for serious rust development. { Contact the manufacturer
(1) Check for liquid leakage in a capacitor and
deformation trance. { Contact the manufacturer
(2) Visual check and judge by the life check of the
main circuit capacitor ( Refer to Chapter 7 of the Instruction Manual (Applied))
(1) Check for unusual vibration and noise. { Replace the fan (2) Check for loose screws and bolts. { Fix with the fan cover fixing screws (3) Check for stain. { Clean
Heatsink (1) Check for clogging. { Clean (2) Check for stain. { Clean
Indication (1) Check that display is normal. { Contact the manufacturer (2) Check for stain. { Clean
Meter Check that reading is normal. { Stop the device and contact the manufacturer.
Check for vibration and abnormal increase in operation noise. { Stop the device and contact the manufacturer.
∗1 It is recommended to install a device to monitor voltage for checking the power supply voltage to the inverter. ∗2 One to two years of periodic inspection cycle is recommended. However, it differs according to the installation environment. Consult us for periodic inspection.

When using the safety stop function, periodic inspection is required to confirm that safety function of the safety system
operates correctly.
For more details, refer to the Safety stop function instruction manual (BCN-A211508-004). (Refer to the front cover for how to obtain the manual.)
The inverter consists of many electronic parts such as semiconductor devices. The following parts may deteriorate with age because of their structures or physical characteristics, leading to reduced performance or fault of the inverter. For preventive maintenance, the parts must be replaced periodically. Use the life check function as a guidance of parts replacement.
Cooling fan 10 years Replace (as required)
Main circuit smoothing capacitor 10 years ∗2 Replace (as required)
On-board smoothing capacitor 10 years ∗2 Replace the board (as required)
Relays — as required
∗1 Estimated lifespan for when the yearly average surrounding air temperature is 40°C
(without corrosive gas, flammable gas, oil mist, dust and dirt etc.)
For parts replacement, consult the nearest Mitsubishi FA Center.

8 SPECIFICATIONS
8.1 Rating

Model FR-E720- KNC 0.1 0.2 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15
Applicable motor capacity (kW) ∗1 0.1 0.2 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15
Rated capacity (kVA) ∗2 0.3 0.6 1.2 2.0 3.2 4.4 7.0 9.5 13.1 18.7 23.9
Overload current rating ∗3 150% 60s, 200% 3s (inverse-time characteristics)
AC (DC) voltage/frequency Three-phase 200 to 240V 50Hz/60Hz (283 to 339VDC ∗8)
fluctuation 170 to 264V 50Hz/60Hz (240 to 373VDC ∗8)
Power supply capacity (kVA) ∗6 0.4 0.8 1.5 2.5 4.5 5.5 9 12 17 20 28
Approximate mass (kg) 0.5 0.5 0.7 1.0 1.4 1.4 1.7 4.3 4.3 6.5 6.5

Applicable motor capacity (kW)∗1 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15
Rated capacity (kVA)∗2 1.2 2.0 3.0 4.6 7.2 9.1 13.0 17.5 23.0
Overload current rating∗3 150% 60s, 200% 3s (inverse-time characteristics)
Power supply capacity (kVA)∗6 1.5 2.5 4.5 5.5 9.5 12 17 20 28
Approximate mass (kg) 1.4 1.4 1.9 1.9 1.9 3.2 3.2 6.0 6.0
∗1 The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi 4-pole standard motor. ∗2 The rated output capacity indicated assumes that the output voltage is 230V for three-phase 200V class and 440V for three-phase 400V class. ∗3 The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For repeated duty, allow time for the inverter and motor to return to or below the temperatures under 100% load. ∗4 The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range. However, the pulse voltage value of the inverter output side voltage remains unchanged at about that of the power supply. ∗5 The braking torque indicated is a short-duration average torque (which varies with motor loss) when the motor alone is decelerated from 60Hz in the shortest time and is not a continuous regenerative torque. When the motor is decelerated from the frequency higher than the base frequency, the average deceleration torque will reduce. Since the inverter does not contain a brake resistor, use the optional brake resistor when regenerative energy is large. A brake unit (FR-BU2) may also be used. (Option brake resistor cannot be used for 0.1K and 0.2K.) ∗6 The power supply capacity varies with the value of the power supply side inverter impedance (including those of the input reactor and cables). ∗7 Setting 2kHz or more in Pr. 72 PWM frequency selection to perform low acoustic noise operation in the surrounding air temperature exceeding 40°C, the rated output current is the value in parenthesis. ∗8 y Connect DC power supply to terminal P/+ and N/-. Connect the plus side of the power supply to terminal P/+ and minus side to terminal N/-. y Since the voltage between P/+ and N/- may increase due to the regeneration energy from the motor and exceeds 415V temporarily, select the DC power
supply which can withstand the voltage/energy during regeneration. If using the power supply which can not withstand voltage/energy during regeneration, insert diodes in series for reverse current prevention. y Although the FR-E700 series has the built-in inrush current limit circuit, select the DC power supply considering the inrush current at powering ON as the
inrush current four times of the rated inverter flows at powering ON. y Since the power supply capacity depends on the output impedance of the power, select the power supply capacity which has enough allowance according
to the AC power supply system capacity.

Model FR-E720SKNC 0.1 0.2 0.4 0.75 1.5 2.2
Applicable motor capacity (kW)∗1 0.1 0.2 0.4 0.75 1.5 2.2
Rated capacity (kVA)∗2 0.3 0.6 1.2 2.0 3.2 4.4
Rated current (A)∗7 0.8 (0.8)
1.5 (1.4)
3.0 (2.5)
5.0 (4.1)
8.0 (7.0)
11.0 (10.0)
Overload current rating∗3 150% 60s, 200% 3s (inverse-time characteristics)
Rated output voltage∗4 Three-phase 200 to 240V
Regenerative braking torque ∗5 150% 100% 50% 20%
Rated input AC voltage/frequency Single-phase 200 to 240V 50Hz/60Hz
Permissible AC voltage fluctuation 170 to 264V 50Hz/60Hz
Permissible frequency fluctuation Within ±5%
Power supply capacity (kVA)∗6 0.5 0.9 1.5 2.5 4.0 5.2
Protective structure (JEM1030) Open type (IP00)
Cooling system Self-cooling Forced air cooling
Approximate mass (kg) 0.6 0.6 0.9 1.4 1.5 2.0
∗1 The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi 4-pole standard motor. ∗2 The rated output capacity indicated assumes that the output voltage is 230V. ∗3 The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For repeated duty, allow time for the inverter and motor to return to or below the temperatures under 100% load. If the automatic restart after instantaneous power failure function (Pr. 57) or power failure stop function (Pr. 261) is set and power supply voltage is low while load becomes bigger, the bus voltage decreases to power failure detection level and load of 100% or more may not be available. ∗4 The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range. However, the pulse voltage value of the inverter output side voltage remains unchanged at about that of the power supply. ∗5 The braking torque indicated is a short-duration average torque (which varies with motor loss) when the motor alone is decelerated from 60Hz in the shortest time and is not a continuous regenerative torque. When the motor is decelerated from the frequency higher than the base frequency, the average deceleration torque will reduce. Since the inverter does not contain a brake resistor, use the optional brake resistor when regenerative energy is large. A brake unit (FR-BU2) may also be used. (Option brake resisitor cannot be used for 0.1K and 0.2K.) ∗6 The power supply capacity varies with the value of the power supply side inverter impedance (including those of the input reactor and cables). ∗7 Setting 2kHz or more in Pr. 72 PWM frequency selection to perform low acoustic noise operation with the surrounding air temperature exceeding 40°C, the rated output current is the value in parenthesis.
Output · Power supply

8.2 Common specifications
Control method Soft-PWM control/high carrier frequency PWM control (V/F control, Advanced magnetic flux vector control, General-purpose magnetic flux vector control, Optimum excitation control are available) Output frequency range 0.2 to 400Hz Frequency setting resolution (digital input) 0.01Hz
Frequency accuracy (digital input) Within 0.01% of the set output frequency
Voltage/frequency characteristics Base frequency can be set from 0 to 400Hz, Constant-torque/variable torque pattern can be selected
Starting torque 200% or more (at 0.5Hz)...when Advanced magnetic flux vector control is set (3.7K or lower)
Torque boost Manual torque boost
Acceleration/deceleration time setting 0.01 to 360s, 0.1 to 3600s (acceleration and deceleration can be set individually), linear or S-pattern acceleration/
deceleration modes are available. DC injection brake Operation frequency (0 to 120Hz), operation time (0 to 10s), operation voltage (0 to 30%) can be changed.
Stall prevention operation level Operation current level can be set (0 to 200% adjustable), whether to use the function or not can be selected
Surrounding air temperature -10°C to +50°C (non-freezing) ∗2
Ambient humidity 90%RH or less (non-condensing)
Storage temperature ∗1 -20°C to +65°C Atmosphere Indoors (without corrosive gas, flammable gas, oil mist, dust and dirt etc.) Altitude/vibration Maximum 1000m above sea level, 5.9m/s 2 or less at 10 to 55Hz (directions of X, Y, Z axes)
∗1 Temperatures applicable for a short time, e.g. in transit. ∗2 When using the inverters at the surrounding air temperature of 40°C or less, the inverters can be installed closely attached (0cm clearance).
Control specifications · Environment

8.3 Outline dimension drawings

108 FR-E720-0.2KNC FR-E720-0.4KNC 140 FR-E720-0.75KNC 160 FR-E720-1.5KNC 108 96 163 FR-E720-2.2KNC FR-E720-3.7KNC 170 158 170 FR-E720-5.5KNC 180 164 260 244 192.5 FR-E720-7.5KNC


108 FR-E720S-0.2KNC FR-E720S-0.4KNC 170 FR-E720S-0.75KNC 108 96 163 FR-E720S-1.5KNC 188.5 FR-E720S-2.2KNC 140 128 150 138 183

The EU Directives are issued to standardize different national regulations of the EU Member States and to facilitate free
movement of the equipment, whose safety is ensured, in the EU territory.
Since 1996, compliance with the EMC Directive that is one of the EU Directives has been legally required. Since 1997,
compliance with the Low Voltage Directive, another EU Directive, has been also legally required. When a manufacturer
confirms its equipment to be compliant with the EMC Directive and the Low Voltage Directive, the manufacturer must declare
the conformity and affix the CE marking.
The authorized representative in the EU is shown below.
Name: Mitsubishi Electric Europe B.V.
We declare that this inverter, when equipped with the dedicated EMC filter, conforms with the EMC Directive in industrial
environments and affix the CE marking on the inverter. When using the inverter in a residential area, take appropriate
measures and ensure the conformity of the inverter used in the residential area.
We declare that this inverter, when equipped with the EMC Directive compliant EMC filter, conforms with the EMC Directive
and affix the CE marking on the inverter.
Environment including residential buildings. Includes building directly connected without a transformer to the low
voltage power supply network which supplies power to residential buildings.
Environment including all buildings except buildings directly connected without a transformer to the lower voltage power supply network which supplies power to residential buildings.
∗Set the EMC Directive compliant EMC filter to the inverter. Insert line noise filters and ferrite cores to the power and
control cables as required.
∗Connect the inverter to an earthed power supply.
∗Install a motor, the EMC Directive compliant EMC filter, and a control cable according to the instructions written in the
EMC Installation Guidelines (BCN-A21041-204) (Please contact your sales representative for the EMC Installation
Guidelines.)
∗The cable length between the inverter and the motor is 5m maximum.
∗Confirm that the final integrated system with the inverter conforms with the EMC Directive.
z Note · Second environment · z Note

We have self-confirmed our inverters as products compliant to the Low Voltage Directive (Conforming standard EN 61800-
5-1) and place the CE mark on the inverters.
∗Do not use an earth leakage circuit breaker as an electric shock protector without connecting the equipment to the earth.
Connect the equipment to the earth securely.
∗Wire the earth (ground) terminal independently. (Do not connect two or more cables to one terminal.)
∗Use the cable sizes on page 8 under the following conditions.
If conditions are different from above, select appropriate wire according to EN60204 ANNEX C TABLE 5. ∗Use a tinned (plating should not include zinc) crimping terminal to connect the earth cable. When tightening the screw,
be careful not to damage the threads.
For use as a product compliant with the Low Voltage Directive, use PVC cable on page 8.
∗Use the moulded case circuit breaker and magnetic contactor which conform to the EN or IEC Standard.
∗When using an earth leakage circuit breaker, use a residual current operated protective device (RCD) of type B (breaker
which can detect both AC and DC). If not, provide double or reinforced insulation between the inverter and other
equipment, or put a transformer between the main power supply and inverter.
∗Use the inverter under the conditions of overvoltage category II (usable regardless of the earth (ground) condition of the
power supply), overvoltage category III (usable with the earthed-neutral system power supply, 400V class only) specified
in IEC664.
yTo use the inverter under the conditions of pollution degree 3, install it in the enclosure of IP54 or higher.
yTo use the inverter outside of an enclosure in the environment of pollution degree 2, fix a fan cover with fan cover fixing
screws enclosed.
3.7K or lower
5.5K or higher

∗On the input and output of the inverter, use cables of the type and size set forth in EN60204 Appendix C. ∗Control circuit terminals on page 5 are safely isolated from the main circuit. ∗Environment
Surrounding Air Temperature -10°C to +50°C -20°C to +65°C -20°C to +65°C
Humidity 90% RH or less 90% RH or less 90% RH or less
Details are given in the technical information "Low Voltage Directive Conformance Guide" (BCN-A21041-203). (Please contact your sales representative for the technical information.)
Outline of instructions

∗Select a UL and cUL certified fuse with Class T fuse equivalent cut-off speed or faster with the appropriate rating for
branch circuit protection, or a UL489 molded case circuit breaker (MCCB) in accordance with the table below.
FR-E720- KNC 0.1 0.2 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 Rated fuse voltage(V) 240V or more
Fuse Maximum allowable rating (A)∗
Without power factor improving reactor 15 15 15 20 30 40 60 70 80 150 175
With power factor improving reactor 15 15 15 20 20 30 50 60 70 125 150
Molded case circuit breaker (MCCB) Maximum allowable rating (A)* 15 20 25 40 60 80 110 150
FR-E740- KNC 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15 Rated fuse voltage(V) 480V or more
Fuse Maximum allowable rating (A)∗
Without power factor improving reactor 6 10 15 20 30 40 70 80 90
With power factor improving reactor 6 10 10 15 25 35 60 70 90
Molded case circuit breaker (MCCB) Maximum allowable rating (A)* 15 20 30 40 50 70
FR-E720S- KNC 0.1 0.2 0.4 0.75 1.5 2.2 Rated fuse voltage(V) 240V or more
Without power factor improving reactor 15 20 20 30 40 60
Fuse Maximum allowable rating (A)∗
With power factor improving reactor 15 20 20 20 30 50
Molded case circuit breaker (MCCB) Maximum allowable rating (A)* 15 15 15 20 25 40
∗Maximum allowable rating by US National Electrical Code. Exact size must be chosen for each installation.
∗When using the electronic thermal relay function as motor overload protection, set the rated motor current to Pr. 9
Electronic thermal O/L relay.

This function detects the overload (overheat) of the motor, stops the operation of the inverter's output transistor, and stops the output. (The operation characteristic is shown on the left)
Pr. 9 = 50% setting of inverter rating*1, 2
30Hz or more *3 30Hz or more *3 20Hz 10Hz
Operation range Range on the right of characteristic curve Non-operation range Range on the left of characteristic curve
When using the Mitsubishi constant-torque motor 1) Set "1" or any of "13" to "16", "50", "53", "54" in Pr. 71. (This provides a 100% continuous torque characteristic in the low-speed range.) 2) Set the rated current of the motor in Pr. 9.
Characteristic when electronic thermal relay function for motor protection is turned off (when Pr. 9 setting is 0(A))
∗1 When 50% of the inverter rated output current (current value) is set in Pr. 9 ∗2 The % value denotes the percentage to the inverter rated output current. It is not the percentage to the motor rated current. ∗3 When you set the electronic thermal relay function dedicated to the Mitsubishi constant- torque motor, this characteristic curve applies to operation at 6Hz or higher.
Inverter output current(%) (% to the rated inverter current)
⋅Protective function by electronic thermal relay function is reset by inverter power reset and reset signal input. Avoid
unnecessary reset and power-OFF. ⋅When multiple motors are operated by a single inverter, protection cannot be provided by the electronic thermal relay
function. Install an external thermal relay to each motor. ⋅When the difference between the inverter and motor capacities is large and the setting is small, the protective
characteristics of the electronic thermal relay function will be deteriorated. In this case, use an external thermal relay. ⋅A special motor cannot be protected by the electronic thermal relay function. Use the external thermal relay. ⋅Electronic thermal relay may not function when 5% or less of inverter rated current is set to electronic thermal relay
setting.
∗Short circuit current ratings
Suitable For Use in A Circuit Capable of Delivering Not More Than 5 kA rms Symmetrical Amperes, 264 V Maximum.
Suitable For Use in A Circuit Capable of Delivering Not More Than 5 kA rms Symmetrical Amperes, 528 V Maximum.
y200V class · y400V class

2. Installation The below types of inverter have been approved as products for use in enclosure and approval tests were conducted under the following conditions. Design the enclosure so that the surrounding air temperature, humidity and ambience of the inverter will satisfy the specifications (Refer to page 4). Wiring protection Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit protection must be provided in accordance with the National Electrical Code for the U.S. or the Canadian Electrical Code for Canada and any additional codes. As specified on page 42, UL Class T fuses or any faster acting fuse with the appropriate rating or Listed UL 489 Molded Case Circuit Breaker (MCCB) must be employed.
⋅Protective function by electronic thermal relay function is reset by inverter power reset and reset signal input. Avoid
unnecessary reset and power-OFF. ⋅When multiple motors are operated by a single inverter, protection cannot be provided by the electronic thermal relay
function. Install an external thermal relay to each motor. ⋅When the difference between the inverter and motor capacities is large and the setting is small, the protective
characteristics of the electronic thermal relay function will be deteriorated. In this case, use an external thermal relay. ⋅A special motor cannot be protected by the electronic thermal relay function. Use the external thermal relay. ⋅Electronic thermal relay may not function when 5% or less of inverter rated current is set to electronic thermal relay
setting.
y Safety stop function is not certified by the UL.



*The manual number is given on the bottom left of the back cover.
Print Date *Manual Number Revision
May 2011 IB-0600401ENG-A First edition

1 For the terminating resistor selection switch
Please make corrections to the following error in this manual.
Instruction Manual (Basic) : page 17 Instruction Manual (Applied): page 50
(Incorrect)
Set "1" and "2" of the terminating resistor selection switch (SW1) to OFF (without terminating resistor) in the middle units.

130 is a resistance value for the CC-Link Ver. 1.00 dedicated high performance cable
Set "1" and "2" of the terminating resistor selection switch (SW1) to OFF (without terminating resistor) in the middle units.

130 is a resistance value for the CC-Link Ver. 1.00 dedicated high performance cable

Instruction Manual (Basic) : page 43
General precaution
When using the electronic thermal relay function as motor overload protection, set the rated motor current to Pr. 9 "Electronic thermal O/L relay".
Motor over temperature sensing is not provided by the drive.


zNorth American FA Center
zIndia FA Center
MITSUBISHI ELECTRIC AUTOMATION, INC. 500 Corporate Woods Parkway, Vernon Hills, IL60061 U.S.A TEL. +1-847-478-2100 FAX. +1-847-478-0327
Mitsubishi Electric Asia Pvt. Ltd. Gurgaon Branch
2nd Floor, DLF Building No.9B, DLF Cyber City Phase , Gurgaon 122002, Haryana, India TEL. +91-124-4630300 FAX. +91-124-4630399
zKorean FA Center
MITSUBISHI ELECTRIC AUTOMATION KOREA CO., LTD. B1F,2F, 1480-6, Gayang-Dong, Gangseo-Gu, Seoul, 157-200, Korea TEL. +82-2-3660-9607 FAX. +82-2-3664-0475
zThailand FA Center
MITSUBISHI ELECTRIC AUTOMATION (THAILAND) CO., LTD. Bang-Chan Industrial Estate No.111, Soi Serithai 54, T.Kannayao, A.Kannayao, Bangkok 10230 TEL. +66-2-906-3238 FAX. +66-2-906-3239
zTaiwan FA Center
SETSUYO ENTERPRISE CO., LTD. 6F No.105, Wu Kung 3rd RD, Wu-Ku Hsiang Taipei Hsien, 248, Taiwan TEL. +886-2-2299-2499 FAX. +886-2-2299-2509
zASEAN FA Center
MITSUBISHI ELECTRIC ASIA PTE, LTD. 307 Alexandra Road #05-01/02, Mitsubishi Electric Building, Singapore 159943 TEL. +65-6470-2480 FAX. +65-6476-7439
zBeijing FA Center
MITSUBISHI ELECTRIC AUTOMATION (CHINA) LTD. BEIJING OFFICE 9F Office Tower 1, Henderson Center, 18 Jianguomennei Avenue, Dongcheng District, Beijing, China 100005 TEL. +86-10-6518-8830 FAX. +86-10-6518-8030
zEuropean FA Center
MITSUBISHI ELECTRIC EUROPE B. V. GERMAN BRANCH Gothaer Strasse 8, D-40880 Ratingen, Germany TEL. +49-2102-486-0 FAX. +49-2102-486-1120
zUK FA Center
zRussian FA Center
MITSUBISHI ELECTRIC EUROPE B.V. -Representative Office in St. Petersburg Sverdlovskaya Emb.,44, Bld Sch, BC "Benua";195027, St.Petersburg, Russia TEL. +7-812-633-3496 FAX. +7-812-633-3499
MITSUBISHI ELECTRIC EUROPE B. V. UK BRANCH Travellers Lane, Hatfield, Hertfordshire, AL10 8XB, UK. TEL. +44-1707-276100 FAX. +44-1707-278695
zCentral and Eastern Europe FA Center
MITSUBISHI ELECTRIC EUROPE B.V. CZECH BRANCH Avenir Business Park, Radlicka 714/113a,158 00 Praha 5, Czech Republic TEL. +420-251-551-470 FAX. +420-251-551-471
zTianjin FA Center
MITSUBISHI ELECTRIC AUTOMATION (CHINA) LTD. TIANJIN OFFICE B-2 801/802, Youyi Building, No.50 Youyi Road, Hexi District, Tianjin, China 300061 TEL +86-22-2813-1015 FAX. +86-22-2813-1017
zBrazil FA Center
MELCO-TEC Representacao Comercial e Assessoria Tecnica Ltda. Av. Paulista 1439, conj.74, Bela Vista CEP: 01311-200 Sao Paulo-SP-Brazil TEL. +55-11-3146-2202 FAX. +55-11-3146-2217
zShanghai FA Center
MITSUBISHI ELECTRIC AUTOMATION (CHINA) LTD. 4/F Zhi Fu Plazz, No.80 Xin Chang Road, Shanghai, China 200003 TEL. +86-21-6121-2460 FAX. +86-21-6121-2424
zGuangzhou FA Center
MITSUBISHI ELECTRIC AUTOMATION (CHINA) LTD. GUANGZHOU OFFICE Rm.1609, North Tower, The Hub Center, No.1068, Xing Gang East Road, Haizhu District, Guangzhou, China 510335 TEL. +86-20-8923-6713 FAX. +86-20-8923-6715

IB-0600401ENG-A(1105)MEE Printed in Japan Specifications subject to change without notice.