INSTRUCTION MANUAL (Applied)
TROUBLESHOOTING
MAINTENANCE AND INSPECTION
SPECIFICATIONS
WIRING
PRECAUTIONS FOR
USE OF THE INVERTER
FL REMOTE
COMMUNICATION FUNCTION
PARAMETERS
FL remote communication function
FR-E720-0.1KNF to 15KNF
FR-E740-0.4KNF to 15KNF
INVERTER
FR-E700

Thank you for choosing this Mitsubishi Inverter. This Instruction Manual (Applied) provides instructions for advanced use of the FR-E700 series FL remote type inverters. Incorrect handling might cause an unexpected fault. Before using the inverter, always read this Instruction Manual and the Instruction Manual (Basic) [IB-0600397ENG] packed with the product carefully to use the equipment to its optimum performance.
WARNING
Do not attempt to install, operate, maintain or inspect the inverter until you have read through the Instruction Manual (Basic) and appended documents carefully and can use the equipment correctly. Do not use this product until you have a full knowledge of the equipment, safety information and instructions. In this Instruction Manual, the safety instruction levels are classified into "WARNING" and "CAUTION".
z While power is ON or when the inverter is running, do not
open the front cover. Otherwise you may get an electric shock. z Do not run the inverter with the front cover or wiring cover
removed. Otherwise you may access the exposed high- voltage terminals or the charging part of the circuitry and get an electric shock. z Even if power is OFF, do not remove the front cover except
Incorrect handling may cause hazardous conditions, resulting in death or severe injury.
for wiring or periodic inspection. You may accidentally touch the charged inverter circuits and get an electric shock. z Before wiring or inspection, power must be switched OFF. To
Incorrect handling may cause hazardous conditions, resulting in medium or slight injury, or may cause only material damage.
confirm that, LED indication of the operation panel must be checked. (It must be OFF.) Any person who is involved in wiring or inspection shall wait for at least 10 minutes after the power supply has been switched OFF and check that there are no residual voltage using a tester or the like. The capacitor is charged with high voltage for some time after power OFF, and it is dangerous. z This inverter must be earthed (grounded). Earthing
The level may even lead to a serious consequence according to conditions. Both instruction levels must be followed because these are important to personal safety.
(grounding) must conform to the requirements of national and local safety regulations and electrical code (NEC section 250, IEC 536 class 1 and other applicable standards). A neutral-point earthed (grounded) power supply for 400V class inverter in compliance with EN standard must be used. z Any person who is involved in wiring or inspection of this
equipment shall be fully competent to do the work. z The inverter must be installed before wiring. Otherwise you
may get an electric shock or be injured. z Setting dial and key operations must be performed with dry
hands to prevent an electric shock. Otherwise you may get an electric shock. z Do not subject the cables to scratches, excessive stress,
heavy loads or pinching. Otherwise you may get an electric shock. z Do not change the cooling fan while power is ON. It is
with wet hands. Otherwise you may get an electric shock. z When measuring the main circuit capacitor capacity, the DC
voltage is applied to the motor for 1s at powering OFF. Never touch the motor terminal, etc. right after powering OFF to prevent an electric shock.
z Inverter must be installed on a nonflammable wall without
holes (so that nobody touches the inverter heatsink on the rear side, etc.). Mounting it to or near flammable material can cause a fire. z If the inverter has become faulty, the inverter power must
be switched OFF. A continuous flow of large current could cause a fire. z When using a brake resistor, a sequence that will turn OFF
power when a fault signal is output must be configured. Otherwise the brake resistor may overheat due to damage of the brake transistor and possibly cause a fire. z Do not connect a resistor directly to the DC terminals P/+
and N/-. Doing so could cause a fire.

3.Injury Prevention
CAUTION
z The voltage applied to each terminal must be the ones
z Before starting operation, each parameter must be
specified in the Instruction Manual. Otherwise burst,
confirmed and adjusted. A failure to do so may cause
damage, etc. may occur.
some machines to make unexpected motions.
z The cables must be connected to the correct terminals.
Otherwise burst, damage, etc. may occur.
z Polarity must be correct. Otherwise burst, damage, etc.
z Any person must stay away from the equipment when the
may occur.
retry function is set as it will restart suddenly after trip.
z While power is ON or for some time after power-OFF, do
not touch the inverter as they will be extremely hot. Doing
z Since pressing key may not stop output depending
so can cause burns.
on the function setting status, separate circuit and switch
that make an emergency stop (power OFF, mechanical
Also the following points must be noted to prevent an
brake operation for emergency stop, etc.) must be
accidental failure, injury, electric shock, etc. (1) Transportation and Mounting
provided.
z OFF status of the start signal must be confirmed before
resetting the inverter fault. Resetting inverter alarm with
z The product must be transported in correct method that
the start signal ON restarts the motor suddenly.
corresponds to the weight. Failure to do so may lead to
z The inverter must be used for three-phase induction motors.
injuries.
Connection of any other electrical equipment to the
z Do not stack the boxes containing inverters higher than
inverter output may damage the equipment.
the number recommended.
z Do not modify the equipment.
z The product must be installed to the position where
z Do not perform parts removal which is not instructed in this
withstands the weight of the product according to the
manual. Doing so may lead to fault or damage of the product.
information in the Instruction Manual.
z Do not install or operate the inverter if it is damaged or
has parts missing.
z The electronic thermal relay function does not guarantee
z When carrying the inverter, do not hold it by the front
protection of the motor from overheating. It is recommended
cover or setting dial; it may fall off or fail.
to install both an external thermal for overheat protection.
z Do not stand or rest heavy objects on the product.
z Do not use a magnetic contactor on the inverter input for
z The inverter mounting orientation must be correct.
frequent starting/stopping of the inverter. Otherwise the
z Foreign conductive objects must be prevented from
life of the inverter decreases.
entering the inverter. That includes screws and metal
z The effect of electromagnetic interference must be
fragments or other flammable substance such as oil.
reduced by using a noise filter or by other means.
z As the inverter is a precision instrument, do not drop or
Otherwise nearby electronic equipment may be affected.
subject it to impact.
z Appropriate measures must be taken to suppress
z The inverter must be used under the following
harmonics. Otherwise power supply harmonics from the
environment. Otherwise the inverter may be damaged.
inverter may heat/damage the power factor correction
capacitor and generator.
-10°C to +50°C (non-freezing)
z When driving a 400V class motor by the inverter, the
motor must be an insulation-enhanced motor or measures
must be taken to suppress surge voltage. Surge voltage
attributable to the wiring constants may occur at the
motor terminals, deteriorating the insulation of the motor.
oil mist, dust and dirt)
z When parameter clear or all parameter clear is performed,
the required parameters must be set again before starting
operations because all parameters return to the initial value.
z The inverter can be easily set for high-speed operation.
Before changing its setting, the performances of the
motor and machine must be fully examined.
z Stop status cannot be hold by the inverter's brake
z Do not install a power factor correction capacitor or surge
function. In addition to the inverter’s brake function, a
suppressor/capacitor type filter on the inverter output
holding device must be installed to ensure safety.
side. These devices on the inverter output side may be
z Before running an inverter which had been stored for a long
overheated or burn out.
period, inspection and test operation must be performed.
z The connection orientation of the output cables U, V, W to
z For prevention of damage due to static electricity, nearby
the motor affects the rotation direction of the motor.
metal must be touched before touching this product to
eliminate static electricity from your body.
(3) Trial run · (4) Usage · (2) Wiring

z A safety backup such as an emergency brake must be
provided to prevent hazardous condition to the machine
and equipment in case of inverter failure.
z When the breaker on the inverter input side trips, the
wiring must be checked for fault (short circuit), and
internal parts of the inverter for a damage, etc. The cause
of the trip must be identified and removed before turning
ON the power of the breaker.
z When any protective function is activated, appropriate
corrective action must be taken, and the inverter must be
reset before resuming operation.
(6) Maintenance, inspection and parts replacement
z Do not carry out a megger (insulation resistance) test on
the control circuit of the inverter. It will cause a failure.
z The inverter must be treated as industrial waste.
Many of the diagrams and drawings in this Instruction Manual show the inverter without a cover or partially open for explanation. Never operate the inverter in this manner. The cover must be always reinstalled and the instruction in this Instruction Manual must be followed when operating the inverter.
(5) Emergency stop · (7) Disposal · General instruction



This chapter explains the "OUTLINE" for use of this product. Always read the instructions before using the equipment.
1.1 Product checking and parts identification 2 1.2 Inverter and peripheral devices 3 1.3 Removal and reinstallation of the cover 5 1.4 Installation of the inverter and enclosure design 8

Inverter Mitsubishi inverter FR-E700 series FL remote type
FR-E700-NF Mitsubishi inverter FR-E700 series FL remote type
Pr Parameter number PU operation Operation using the operation panel
Mitsubishi standard motor SF-JR Mitsubishi constant-torque motor ... SF-HRCA
Company and product names herein are the trademarks and registered trademarks of their

1.1 Product checking and parts identification
Unpack the inverter and check the capacity plate on the front cover and the rating plate on the inverter side face to ensure that the product agrees with your order and the inverter is intact. zInverter model

Represents the inverter capacity [kW] E720 Three-phase 200V class
∗Location of the capacity plate and the rating plate differs
Refer to the outline dimension drawing. (Refer to page 226)

Capacity Quantity FR-E720-1.5KNF to 3.7KNF, FR-E740-1.5KNF to 3.7KNF 1 FR-E720-5.5KNF to 15KNF, FR-E740-5.5KNF to 15KNF 2
Harmonic suppression guideline (when inverters are used in Japan)
All models of general-purpose inverters used by specific consumers are covered by "Harmonic suppression guideline for consumers who receive high voltage or special high voltage". (For further details, refer to page 35.)

1.2 Inverter and peripheral devices
AC power supply Use within the permissible power supply specifications of the inverter. To ensure safety, use a moulded case circuit breaker, earth leakage circuit breaker or magnetic contactor to switch power ON/OFF.
(Refer to page 224)
Moulded case circuit breaker (MCCB) or earth leakage circuit breaker (ELB), fuse The breaker must be selected carefully since an in-rush current flows in the inverter at power on.
(Refer to page 4)
Magnetic contactor (MC) Install the magnetic contactor to ensure safety. Do not use this magnetic contactor to start and stop the inverter. Doing so will cause the inverter life to be shorten.
Approved safety relay module Required for compliance with safety standard.
(Refer to page 38)
Reactor (FR-HAL, FR-HEL option) Reactors (option) must be used when power harmonics measures are taken, the power factor is to be improved or the inverter is installed near a large power supply system (500kVA or more). The inverter may be damaged if you do not use reactors. Select the reactor according to the model. Remove the jumpers across terminals P/+ and P1 to connect the DC reactor.
OUTLINE
Brake resistor (FR-ABR, MRS type, MYS type) Braking capability can be improved. (0.4K or higher) Always install a thermal relay when using a brake resistor whose capacity is 11K or higher. (Refer to page 25)
AC reactor (FR-HAL) DC reactor (FR-HEL) *
EMC filter (ferrite core) * (FR-BSF01, FR-BLF)
P1 P/+
EMC filter (ferrite core) (FR-BSF01, FR-BLF) Install an EMC filter (ferrite core) to reduce the electromagnetic noise generated from the inverter. Effective in the range from about 1MHz to 10MHz. A wire should be wound four turns at a maximum.
Install an EMC filter (ferrite core) to reduce the electromagnetic noise generated from the inverter. Effective in the range from about 1MHz to 10MHz. When more wires are passed through, a more effective result can be obtained. A wire should be wound four turns or more.
EMC filter (capacitor) * (FR-BIF)
Reduces the radio noise.

* Filterpack (FR-BFP2), which contains DC reactor and EMC filter in one package, is also available.
The regenerative braking capability of the inverter can be exhibited fully. Install this as required.
Devices connected to the output Do not install a power factor correction capacitor, surge suppressor or capacitor type filter on the output side of the inverter. When installing a moulded case circuit breaker on the output side of the inverter, contact each manufacturer for selection of the moulded case circuit breaker.
Earth (Ground) To prevent an electric shock, always earth (ground) the motor and inverter. For reduction of induction noise from the power line of the inverter, it is recommended to wire the earth (ground) cable by returning it to the earth (ground) terminal of the inverter.
PR
PR
Resistor unit (FR-BR) Discharging resistor (GZG, GRZG)
possible within the permissible range. This must be noted especially when the inverter is installed in an enclosure. (Refer to page 8) y Wrong wiring might lead to damage of the inverter. The control signal lines must be kept fully away from the main circuit
to protect them from noise. (Refer to page 14) y Do not install a power factor correction capacitor, surge suppressor or capacitor type filter on the inverter output side.
This will cause the inverter to trip or the capacitor and surge suppressor to be damaged. If any of the above devices are connected, immediately remove them. y Electromagnetic wave interference
The input/output (main circuit) of the inverter includes high frequency components, which may interfere with the communication devices (such as AM radios) used near the inverter. In this case, install options among the capacitor type EMC filter FR-BIF (for use in the input side only), the ferrite core type EMC filter FR-BSF01/FR-BLF, filterpack, and EMC filter to minimize the interference. (Refer to page 32). y Refer to the instruction manual of each option and peripheral devices for details of peripheral devices.

1.2.1 Peripheral devices
Check the inverter model of the inverter you purchased. Appropriate peripheral devices must be selected according to the capacity. Refer to the following list and prepare appropriate peripheral devices:
Moulded Case Circuit Breaker
(MCCB) ∗1 or Earth Leakage Circuit Breaker
(ELB) ∗2 (NF, NV type)
Reactor connection Reactor connection FR-HAL FR-HEL without with without with
FR-E720-0.1KNF 0.1 5A 5A S-N10 S-N10 0.4K ∗4 0.4K ∗4
FR-E720-0.2KNF 0.2 5A 5A S-N10 S-N10 0.4K ∗4 0.4K ∗4 FR-E720-0.4KNF 0.4 5A 5A S-N10 S-N10 0.4K 0.4K FR-E720-0.75KNF 0.75 10A 10A S-N10 S-N10 0.75K 0.75K FR-E720-1.5KNF 1.5 15A 15A S-N10 S-N10 1.5K 1.5K FR-E720-2.2KNF 2.2 20A 15A S-N10 S-N10 2.2K 2.2K FR-E720-3.7KNF 3.7 30A 30A S-N20, S-N21 S-N10 3.7K 3.7K FR-E720-5.5KNF 5.5 50A 40A S-N25 S-N20, S-N21 5.5K 5.5K FR-E720-7.5KNF 7.5 60A 50A S-N25 S-N25 7.5K 7.5K FR-E720-11KNF 11 75A 75A S-N35 S-N35 11K 11K FR-E720-15KNF 15 125A 100A S-N50 S-N50 15K 15K
FR-E740-0.4KNF 0.4 5A 5A S-N10 S-N10 H0.4K H0.4K FR-E740-0.75KNF 0.75 5A 5A S-N10 S-N10 H0.75K H0.75K FR-E740-1.5KNF 1.5 10A 10A S-N10 S-N10 H1.5K H1.5K FR-E740-2.2KNF 2.2 15A 10A S-N10 S-N10 H2.2K H2.2K FR-E740-3.7KNF 3.7 20A 15A S-N10 S-N10 H3.7K H3.7K FR-E740-5.5KNF 5.5 30A 20A S-N20, S-N21 S-N11, S-N12 H5.5K H5.5K FR-E740-7.5KNF 7.5 30A 30A S-N20, S-N21 S-N20, S-N21 H7.5K H7.5K FR-E740-11KNF 11 50A 40A S-N20, S-N21 S-N20, S-N21 H11K H11K FR-E740-15KNF 15 60A 50A S-N25 S-N20, S-N21 H15K H15K
∗1 ySelect an MCCB according to the power supply capacity.
IM
yInstall one MCCB per inverter.
IM
∗2 For the use in the United States or Canada, select a UL and cUL certified fuse with Class T fuse equivalent cut-off
speed or faster with the appropriate rating for branch circuit protection. Alternatively, select a UL489 molded case circuit breaker (MCCB).
∗3 Magnetic contactor is selected based on the AC-1 class. The electrical durability of magnetic contactor is 500,000 times. When the magnetic contactor is
used for emergency stop during motor driving, the electrical durability is 25 times.
When using the MC for emergency stop during motor driving or using on the motor side during commercial-power supply operation, select the MC with class
AC-3 rated current for the motor rated current.
∗4 The power factor may be slightly lower.
y When the inverter capacity is larger than the motor capacity, select an MCCB and a magnetic contactor according to
the inverter model and cable and reactor according to the motor output.
y When the breaker on the inverter input side trips, check for the wiring fault (short circuit), damage to internal parts of
the inverter, etc. Identify the cause of the trip, then remove the cause and power on the breaker.

1.3 Removal and reinstallation of the cover
1.3.1 Front cover

Remove the front cover by pulling it toward you in the direction of arrow.
To reinstall, match the cover to the inverter front and install it straight.


y Fully make sure that the front cover has been reinstalled securely.
y The same serial number is printed on the capacity plate of the front cover and the rating plate of the inverter. Since
these plates have the same serial numbers, always reinstall the removed cover onto the original inverter.

1.3.2 Wiring cover

The cover can be removed easily by pulling it toward you. To reinstall, fit the cover to the inverter along the guides.
For removal, push the dent on the wiring cover with your finger and

1.4 Installation of the inverter and enclosure design
When an inverter enclosure is to be designed and manufactured, heat generated by contained equipment, etc., the environment of an operating place, and others must be fully considered to determine the enclosure structure, size and equipment layout. The inverter unit uses many semiconductor devices. To ensure higher reliability and long period of operation, operate the inverter in the ambient environment that completely satisfies the equipment specifications.
As the inverter installation environment should satisfy the standard specifications indicated in the following table, operation in any place that does not meet these conditions not only deteriorates the performance and life of the inverter, but also causes a failure. Refer to the following points and take adequate measures.
Environmental standard specifications of inverter
temperature -10 to +50°C (non-freezing)
Ambient humidity 90%RH or less (non-condensing)
Atmosphere Free from corrosive and explosive gases, free from dust and dirt
Maximum altitude 1,000m or less
Vibration 5.9m/s2 or less at 10 to 55Hz (directions of X, Y, Z axes)
(1) Temperature The permissible surrounding air temperature of the inverter is between -10 and +50°C. Always operate the inverter within this temperature range. Operation outside this range will considerably shorten the service lives of the semiconductors, parts, capacitors and others. Take the following measures so that the surrounding air temperature of the inverter falls within the specified range.
(2) Humidity Normally operate the inverter within the 45 to 90% range of the ambient humidity. Too high humidity will pose problems of reduced insulation and metal corrosion. On the other hand, too low humidity may produce a spatial electrical breakdown. The insulation distance specified in JEM1103 "Control Equipment Insulator" is defined as humidity 45 to 85%.
y Take the measures against high humidity in 1). y Do not power OFF the inverter. (Keep the start signal of the inverter OFF.)
Item Description · Surrounding air

Dust and dirt will cause such faults as poor contact of contact points, reduced insulation or reduced cooling effect due to moisture absorption of accumulated dust and dirt, and in-panel temperature rise due to clogged filter. In the atmosphere
where conductive powder floats, dust and dirt will cause such faults as malfunction, deteriorated insulation and short circuit in a short time.
Since oil mist will cause similar conditions, it is necessary to take adequate measures.
Countermeasures y Place in a totally enclosed enclosure.
Take measures if the in-enclosure temperature rises. (Refer to page 10) y Purge air.
Pump clean air from outside to make the in-panel pressure higher than the outside-air pressure.
If the inverter is exposed to corrosive gas or to salt near a beach, the printed board patterns and parts will corrode or the
relays and switches will result in poor contact. In such places, take the measures given in Section 3.
As the inverter is non-explosion proof, it must be contained in an explosion proof enclosure. In places where explosion may be
caused by explosive gas, dust or dirt, an enclosure cannot be used unless it structurally complies with the guidelines and has passed the specified tests. This makes the enclosure itself expensive (including the test charges). The best way is to avoid
installation in such places and install the inverter in a non-hazardous place.
Use the inverter at the altitude of within 1000m. If it is used at a higher place, it is likely that thin air will reduce the cooling effect and low air pressure will deteriorate dielectric strength.
The vibration resistance of the inverter is up to 5.9m/s2 at 10 to 55Hz frequency and 1mm amplitude for the directions of X, Y,
Z axes. Vibration or impact, if less than the specified value, applied for a long time may make the mechanism loose or cause poor contact to the connectors.
Especially when impact is imposed repeatedly, caution must be taken as the part pins are likely to break.
Countermeasures y Provide the panel with rubber vibration isolators.
y Strengthen the structure to prevent the panel from resonance. y Install the panel away from sources of vibration.

1.4.2 Cooling system types for inverter enclosure
From the enclosure that contains the inverter, the heat of the inverter and other equipment (transformers, lamps, resistors,
etc.) and the incoming heat such as direct sunlight must be dissipated to keep the in-panel temperature lower than the permissible temperatures of the in-panel equipment including the inverter.
The cooling systems are classified as follows in terms of the cooling calculation method. 1) Cooling by natural heat dissipation from the enclosure surface (totally enclosed type)
Cooling System Enclosure Structure Comment
Low in cost and generally used, but the panel size increases
as the inverter capacity increases. For relatively small
capacities.
Being a totally enclosed type, the most appropriate for hostile
environment having dust, dirt, oil mist, etc. The panel size
increases depending on the inverter capacity.
Fin cooling Having restrictions on the heatsink mounting position and
area, and designed for relative small capacities.
Forced ventilation For general indoor installation. Appropriate for panel
downsizing and cost reduction, and often used.
Heat pipe Totally enclosed type for panel downsizing.

1.4.3 Inverter placement
Enclosure surface mounting
Remove the front cover and wiring cover to fix the inverter to the surface.
y FR-E720-0.1KNF to 0.75KNF y FR-E720-1.5KNF or higher y FR-E740-0.4KNF or higher


y When encasing multiple inverters, install them in parallel as a cooling

y For heat dissipation and maintenance, take at least the clearances
shown in the table below from the inverter to the other devices and to
1cm or more 1cm or more 1cm or more ∗1, ∗2 ∗1 ∗1, ∗2
∗1 Take 5cm or more clearances for 5.5K or higher. ∗2 When using the inverters at the surrounding air temperature of 40°C or less, the inverters can be installed without any clearance between
Heat is blown up from inside the inverter by the small fan built in the unit. Any equipment placed above the inverter should be heat resistant.

When multiple inverters are placed in the same enclosure, generally arrange them horizontally as shown
in the right figure (a). When it is inevitable to arrange them vertically to minimize space, take such measures as
Inverter
to provide guides since heat from the bottom inverters can increase the temperatures in the top inverters,
causing inverter failures.
When mounting multiple inverters, fully take caution not to make the surrounding air temperature of the inverter
higher than the permissible value by providing ventilation
and increasing the panel size.
(a) Horizontal arrangement (b) Vertical arrangement
Arrangement of multiple inverters
Heat generated in the inverter is blown up from the bottom of the unit as warm air by the cooling fan. When installing a
ventilation fan for that heat, determine the place of ventilation fan installation after fully considering an air flow. (Air passes
through areas of low resistance. Make an airway and airflow plates to expose the inverter to cool air.)
Placement of ventilation fan and inverter

This chapter describes the basic "WIRING" for use of this product. Always read the instructions before using the equipment.
2.1 Wiring 14 2.2 Main circuit terminal specifications 15 2.3 Control circuit specifications 20 2.4 Connection of stand-alone option unit 25

2.1 Wiring
2.1.1 Terminal connection diagram

*1. DC reactor (FR-HEL) When connecting a DC reactor, remove the jumper across P1 and P/+. Control circuit terminal Main circuit terminal Sink logic
*2 A brake transistor is not built-in to the 0.1K and 0.2K.
*3 Brake resistor (FR-ABR, MRS, MYS type) Install a thermal relay to prevent an overheat and burnout of the brake resistor. (The brake resistor cannot be connected to the 0.1K and 0.2K.)
D1: Communication setting status LED (CHG) D2: Device status LED (DEV) D3: Reception/transmission LED (TX/RX) D4: Remote status LED (RMT)
y To prevent a malfunction caused by noise, separate the signal cables more than 10cm from the power cables. Also
separate the main circuit wire of the input side and the output side. y After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean. When drilling mounting holes in an enclosure etc., take care not to allow chips and other foreign matter to enter the inverter.

2.2 Main circuit terminal specifications
2.2.1 Specification of main circuit terminal

AC power input Connect to the commercial power supply.
U, V, W Inverter output Connect a three-phase squirrel-cage motor.
Connect a brake resistor (FR-ABR, MRS type, MYS type) across terminals P/+ and
(The brake resistor cannot be connected to the 0.1K or 0.2K.)
P/+, N/- Brake unit connection Connect the brake unit (FR-BU2).
P/+, P1 DC reactor connection Remove the jumper across terminals P/+ and P1 and connect a DC reactor.
Earth (Ground) For earthing (grounding) the inverter chassis. Must be earthed (grounded).
2.2.2 Terminal arrangement of the main circuit terminal, power supply and the motor wiring


y Make sure the power cables are connected to the R/L1, S/L2, T/L3. (Phase need not be matched.) Never connect the
power cable to the U, V, W of the inverter. Doing so will damage the inverter.
y Connect the motor to U, V, W. Turning ON the forward rotation switch (signal) at this time rotates the motor
counterclockwise when viewed from the load shaft.

2.2.3 Cables and wiring length
Select the recommended cable size to ensure that a voltage drop will be 2% or less.
If the wiring distance is long between the inverter and motor, a main circuit cable voltage drop will cause the motor torque to decrease especially at the output of a low frequency.
The following table indicates a selection example for the wiring length of 20m. Three-phase 200V class (when input power supply is 220V)

∗1 AWG ∗2 PVC Cables, etc. (mm2)
FR-E720-0.1KNF to 0.75KNF M3.5 1.2 2-3.5 2-3.5 2 2 2 14 14 2.5 2.5 2.5
FR-E720-1.5KNF, 2.2KNF M4 1.5 2-4 2-4 2 2 2 14 14 2.5 2.5 2.5
FR-E720-3.7KNF M4 1.5 5.5-4 5.5-4 3.5 3.5 3.5 12 12 4 4 4
FR-E720-5.5KNF M5 2.5 5.5-5 5.5-5 5.5 5.5 5.5 10 10 6 6 6
FR-E720-7.5KNF M5 2.5 14-5 8-5 14 8 5.5 6 8 16 10 6
FR-E720-11KNF M5 2.5 14-5 14-5 14 14 14 6 6 16 16 16
FR-E720-15KNF M6(M5) 4.4 22-6 22-6 22 22 14 4 4 25 25 16

∗1 AWG ∗2 PVC Cables, etc. (mm2)
FR-E740-0.4KNF to 3.7KNF M4 1.5 2-4 2-4 2 2 2 14 14 2.5 2.5 2.5
FR-E740-5.5KNF M4 1.5 5.5-4 2-4 3.5 2 3.5 12 14 4 2.5 4
FR-E740-7.5KNF M4 1.5 5.5-4 5.5-4 3.5 3.5 3.5 12 12 4 4 4
FR-E740-11KNF M4 1.5 5.5-4 5.5-4 5.5 5.5 8 10 10 6 6 10
FR-E740-15KNF M5 2.5 8-5 8-5 8 10 10 10
∗1 The cable size is that of the cable (HIV cable (600V class 2 vinyl-insulated cable) etc.) with continuous maximum permissible temperature of 75°C. Assumes
that the surrounding air temperature is 50°C or less and the wiring distance is 20m or less. ∗2 The recommended cable size is that of the cable (THHW cable) with continuous maximum permissible temperature of 75°C. Assumes that the surrounding air
temperature is 40°C or less and the wiring distance is 20m or less. (Selection example for use mainly in the United States.)
∗3 The recommended cable size is that of the cable (PVC cable) with continuous maximum permissible temperature of 70°C. Assumes that the surrounding air
temperature is 40°C or less and the wiring distance is 20m or less. (Selection example for use mainly in Europe.)
∗4 The terminal screw size indicates the terminal size for R/L1, S/L2, T/L3, U, V, W, and a screw for earthing (grounding).
A screw for earthing (grounding) of the FR-E720-15KNF is indicated in ( ).R/L1, S/L2P/N/
y Tighten the terminal screw to the specified torque. A screw that has been tighten too loosely can cause a short circuit
or malfunction. A screw that has been tighten too tightly can cause a short circuit or malfunction due to the unit
breakage.
y Use crimping terminals with insulation sleeve to wire the power supply and motor.
The line voltage drop can be calculated by the following formula:
3 × wire resistance[mΩ/m] × wiring distance[m] × current[A] 1000
Line voltage drop [V]=
Use a larger diameter cable when the wiring distance is long or when it is desired to decrease the voltage drop (torque reduction) in the low speed range.

z Always earth (ground) the motor and inverter.
Generally, an electrical apparatus has an earth (ground) terminal, which must be connected to the ground before use. An electrical circuit is usually insulated by an insulating material and encased. However, it is impossible to manufacture
an insulating material that can shut off a leakage current completely, and actually, a slight current flow into the case. The purpose of earthing (grounding) the case of an electrical apparatus is to prevent operator from getting an electric
shock from this leakage current when touching it. To avoid the influence of external noises, this earthing (grounding) is important to audio equipment, sensors, computers
and other apparatuses that handle low-level signals or operate very fast. 2) Earthing (grounding) methods and earthing (grounding) work
As described previously, earthing (grounding) is roughly classified into an electrical shock prevention type and a noise-
affected malfunction prevention type. Therefore, these two types should be discriminated clearly, and the following work must be done to prevent the leakage current having the inverter's high frequency components from entering the
malfunction prevention type earthing (grounding): (a)If possible, use (l) independent earthing (grounding) in figure below for the inverter. If independent earthing
(grounding) is not available, use (ll) joint earthing (grounding) in the figure below which the inverter is connected with the other equipment at an earthing (grounding) point. The (lll) common earthing (grounding) as in the figure below, which inverter shares a common earth (ground) cable with the other equipment, must be avoided. A leakage current including many high frequency components flows in the earth (ground) cables of the inverter and inverter-driven motor. Therefore, use the independent earthing (grounding) and separated the earthing (grounding) cable of the inverter from equipments sensitive to EMI. In a high building, it may be effective to use the EMI prevention type earthing (grounding) connecting to an iron structure frame, and electric shock prevention type earthing (grounding) with the independent earthing (grounding) together. (b)This inverter must be earthed (grounded). Earthing (Grounding) must conform to the requirements of national and
local safety regulations and electrical codes. (NEC section 250, IEC 536 class 1 and other applicable standards). Use an neutral-point earthed (grounded) power supply for 400V class inverter in compliance with EN standard. (c)Use the thickest possible earth (ground) cable. The earth (ground) cable should be of not less than the size indicated
in the table on the previous page 17. (d)The grounding point should be as near as possible to the inverter, and the ground wire length should be as short as
possible. (e)Run the earth (ground) cable as far away as possible from the I/O wiring of equipment sensitive to noises and run
them in parallel in the minimum distance.
(I)Independent earthing Best
(II)Common earthing Good
(III)Common earthing Not allowed
To be compliant with the EU Directive (Low Voltage Directive), refer to the Instruction Manual (Basic).
Inverter Other equipment · Inverter Other equipment · Inverter Other equipment

The overall wiring length for connection of a single motor or multiple motors should be within the value in the table below.

0.1K 0.2K 0.4K 0.75K 1.5K 2.2K 3.7K or Higher
1 (1kHz) or less 200V class 200m 200m 300m 500m
400V class - - 200m 200m 300m 500m 500m
200V class 30m 100m 200m 300m 500m 500m 500m
400V class - - 30m 100m 200m 300m 500m

When driving a 400V class motor by the inverter, surge voltages attributable to the wiring constants may occur at the motor terminals, deteriorating the insulation of the motor. In this case, refer to page 39.
y Especially for long-distance wiring, the inverter may be affected by a charging current caused by the stray
capacitances of the wiring, leading to a malfunction of the overcurrent protective function, fast response current limit function, or stall prevention function or a malfunction or fault of the equipment connected on the inverter output side. If malfunction of fast-response current limit function occurs, disable this function. If malfunction of stall prevention function occurs, increase the stall level. (Refer to page 101 for Pr. 22 Stall prevention operation level and Pr. 156 Stall prevention operation selection ) y Refer to page 163 for details of Pr. 72 PWM frequency selection. y When using the automatic restart after instantaneous power failure function with wiring length exceeding 100m,
select without frequency search (Pr. 162 = "1 (initial value), 11"). (Refer to page 151)

2.3 Control circuit specifications
2.3.1 Control circuit terminal
Symbol Terminal Name Description Rated Specifications Refer to
24V external power supply
Even when the main circuit power supply is OFF, FL remote communication continues with the input from the 24V external power supply.
+24 24V external power
23.5 to 26.5VDC
0.7A or less
SD 24V external power
supply common terminal Common terminal for the terminal +24 — —
Terminal S1/S2 are safety stop signals for use with in
S1 Safety stop input
conjunction with an approved external safety unit.
Input resistance 4.7kΩ
Both terminal S1/S2 must be used in dual channel
Voltage when contacts are
form. Inverter output is shutoff depending on shorting/
opening between S1 and PC, S2 and PC.
In the initial status, terminal S1 and S2 are shorted
When contacts are short-
S2 Safety stop input
with terminal PC by shorting wire.
Remove the shorting wire and connect the safety
relay module when using the safety stop function.
PC Safety stop input terminal
Common terminal for safety stop input terminals S1 and S2. — —
Symbol Terminal Name Description Rated Specifications Refer to
This terminal is switched to Low during the operation
with no internal safety circuit fault (E.SAF, E.6, E.7,
E.CPU). It is switched to High in operation statuses
(maximum 27VDC) 0.1A
Y0 Open collector output Y0
other than above.
(a voltage drop is 3.4V
(safety monitor output 2)
(Low indicates that the open collector output transistor
maximum when the signal
is ON (conducts). High indicates that the transistor is
OFF (does not conduct).)
SE Open collector output
common Common terminal of terminal Y0. — —
Connector Name Description Refer to
connector With the FL remote communication connector, FL remote communication can be performed. 48

2.3.2 Wiring of control circuit

Recommend wire size:
0.3mm2 to 0.75mm2
zWiring For the control circuit wiring, strip off the sheath of wires, and use them with a blade terminal. For a single wire, strip off the sheath of the wire and apply directly. Insert the blade terminal or the single wire into a socket of the terminal.


Wires are not inserted into the shell Crumpled tip
Blade terminals available on the market: (as of Oct. 2008) zPhoenix Contact Co.,Ltd.

crimping tool with insulation sleeve without insulation sleeve for UL wire∗
0.75 (for two wires) AI-TWIN 2 x 0,75-10GY — —
∗A blade terminal with an insulation sleeve compatible with MTW wire which has a thick wire insulation
zNICHIFU Co.,Ltd.
Wire Size (mm2) Blade terminal product
number Insulation product number Blade terminal
0.3 to 0.75 BT 0.75-11 VC 0.75 NH 67
crimping tool

When using a single wire or a stranded wire without a blade terminal, push an open/close button all the way down with a flathead screw driver, and insert the wire.
y When using a stranded wire without a blade terminal, twist enough to avoid short circuit with a nearby terminals or
wires. y Place the flathead screwdriver vertical to the open/close button. In case the blade tip slips, it may cause to damage of
inverter or injury.
zWire removal Pull the wire with pushing the open/close button all the way down firmly with a flathead screwdriver.
y Use a small flathead screwdriver (Tip thickness: 0.4mm/tip width: 2.5mm).
If a flathead screwdriver with a narrow tip is used, terminal block may be damaged. Introduced products :(as of Oct. 2008)
Flathead screwdriver SZF 0- 0,4 x 2,5 Phoenix Contact Co.,Ltd.
y Place the flathead screwdriver vertical to the open/close button. In case the blade tip slips, it may cause to damage of
inverter or injury.
Terminals SD and SE are common terminals for I/O signals. (Both common terminals are isolated from each other.) Do not earth them. Terminal SD is a common terminal for 24V external power supply terminal (+24). The open collector circuit is isolated from the internal control circuit by photocoupler. Terminal SE is a common terminal for the open collector output terminal (Y0). The contact input circuit is isolated from the internal control circuit by photocoupler.

2.3.3 Connecting the 24V external power supply
FL remote communication between the master module and the inverter can be continued while the main power circuit is OFF if the 24V external power supply is connected across terminals +24 and SD. When the main circuit power supply is turned ON, the power supply changes from the 24V external power supply to the main circuit power supply. (1) Specification of the applied 24V external power supply y Input voltage 23.5 to 26.5VDC y Input current 0.7A or less (2) Operation panel display during the 24V external power supply operation y "EV" flickers.
(3) Function of the 24V external power supply operation y When the main power supply is turned ON during the 24V external power supply operation, a reset is performed in the
inverter, then the power supply changes to the main circuit power supply. During the reset operation in the inverter, the inverter cannot be controlled through the FL remote communication. y The operation stops when the power supply changes to the 24V external power supply from the main circuit power
supply regardless of the operating status (in a stop, in running, in automatic restart after instantaneous power failure, in offline (online) tuning, in main circuit capacitor life measurement).
y All start signals (STF signal, STR signal, and on the operation panel) are invalid during the 24V external power
supply operation. y Faults history and parameters can be read and parameters can be written (when the parameter write from the
operation panel is enabled) using the operation panel keys. y The safety stop function is also valid during the 24V external power supply operation. When the safety stop function is
active, however, "SA" is not displayed because "EV" is displayed. The "EV" display has priority over the "SA" display. y The following items can be monitored during the 24V external power supply operation.
Frequency setting, output current peak value∗, converter output voltage peak value∗, cumulative energization time, actual operation time∗, cumulative power∗, and cumulative power 2∗ (monitor dedicated to the FL remote communication)
∗The monitored data is not updated after the power supply is changed from the main circuit power supply. (Refer to page 147 for the details of each monitor.) y The valid signals when the 24V external power supply is ON are ALM, Safety alarm, Edit, NET, READY and Y95.
(Other signals are OFF.) (Refer to page 59 and 60 for the detail of each signal.) y The alarms, which have occurred when the main circuit power supply is ON, continue to be output after the power
supply is changed to the 24V external power supply. Perform the inverter reset to reset the alarms. y The retry function is invalid for all alarms when the 24V external power supply is ON. y If the power supply changes from the main circuit power supply to the 24V external power supply while measuring the
main circuit capacitor's life in the PU operation mode, the measurement completes after the power supply changes back to the main circuit power supply (Pr.259 = "3").
y When the 24V external power supply is input while the main circuit power supply is OFF, the FL remote
communication is enabled, but the inverter operation is disabled. y Inrush current higher than the value described in (1) may flow at a power-ON. Confirm that the power supply and
other devices are not affected by the inrush current and the voltage drop caused by it. y When the wiring length between the external power supply and the inverter is long, the voltage often drops. Select the
appropriate wiring size and length to keep the voltage in the rated input voltage range. y In a serial connection of several inverters, the current increases when it flows through the inverter wiring near the
power supply. The increase of the current causes voltage to drop further. When connecting different inverters to different power supplies, use the inverters after confirming that the input voltage of each inverter is within the rated input voltage range. y "E.SAF" may appear when the start-up time of the 24V power supply is too long in the 24V external power supply
operation.
Flickering

2.3.4 Safety stop function
The terminals related to the safety stop function are shown below.

S1∗1 For input of safety stop channel 1. Between S1 and PC / S2 and PC Open: In safety stop state. Short: Other than safety stop state. S2∗1 For input of safety stop channel 2.
PC∗1 Common terminal for terminal S1 and S2.
Y0 (SAFE2 signal) Outputs when an alarm or failure is detected. The signal is output when no internal safety circuit failure∗2 exists.
OFF: Internal safety circuit failure.∗2 ON : No internal safety circuit failure.∗2 SE Common terminal for open collector outputs (terminal Y0)
∗1 In the initial status, terminal S1 and S2 are shorted with terminal PC by shortening wire. Remove the shortening wire and connect the safety relay module when using the safety stop function. ∗2 At an internal safety circuit failure, one of E.SAF, E.6, E.7, and E.CPU is displayed on the operation panel.
Specifications differ according to the date assembled. Refer to page 232 to check the SERIAL number.
safety stop input signal to other devices.
To prevent restart at fault occurrence, connect terminals Y0 (SAFE2 signal) and SE to terminals XS0 and XS1, which are the feedback input terminals of the safety relay module. Terminal Y0 is turned OFF at a fault occurrence.


circuit∗1 Output signal (SAFE2)∗3 Operation state S1-PC S2-PC OFF OFF Output shutoff (Safe state)
Short Short No failure ON Drive enabled Detected OFF Output shutoff (Safe state)
Open Open No failure∗2 ON Output shutoff (Safe state) Detected OFF Output shutoff (Safe state) Short Open Detected OFF Output shutoff (Safe state) Open Short Detected OFF Output shutoff (Safe state)
∗1 At an internal safety circuit failure, one of E.SAF, E.6, E.7, and E.CPU is displayed on the operation panel. ∗2 SA is displayed when both of the S1 and S2 signals are in open status and no internal safety circuit failure exists. ∗3 ON: Transistor used for an open collector output is conducted. OFF: Transistor used for an open collector output is not conducted. For more details, refer to the Safety stop function instruction manual (BCN-A211508-004). (Refer to the front cover of the Instruction Manual (Basic) for how to obtain the manual.)

2.4 Connection of stand-alone option unit
The inverter accepts a variety of stand-alone option units as required. Incorrect connection will cause inverter damage or accident. Connect and operate the option unit carefully in accordance with the corresponding option unit manual.
2.4.1 Connection of a dedicated external brake resistor (MRS type, MYS type, FR-ABR)
Install a dedicated brake resistor (MRS type, MYS type, FR-ABR) outside when the motor is made to run by the load, quick deceleration is required, etc. Connect a dedicated brake resistor (MRS type, MYS type, FR-ABR) to terminal P/+ and PR. (For the locations of terminal P/+ and PR, refer to the terminal block layout (page 15).) Set parameters below.

selection Setting Pr. 70 Special regenerative brake duty Setting
MYS type (used at 100% torque / 6%ED) 1 6% Refer to page 136 FR-ABR 1 7.5K or lower 10%
Connect the brake resistor across terminals P/+ and PR. Connect the brake resistor across terminals P/+ and PR.
Connect the brake resistor across terminals P/+ and PR. Connect the brake resistor across terminals P/+ and PR.
∗1 Do not remove the jumper across terminals P/+ and P1 except when connecting a DC reactor.
∗2 The shape of jumper differs according to capacities.

z It is recommended to configure a sequence, which shuts off power in the input side of the inverter by the external thermal
relay as shown below, to prevent overheat and burnout of the brake resistor (MRS type, MYS type) and high duty brake
resistor (FR-ABR) in case the regenerative brake transistor is damaged. (The brake resistor cannot be connected to the 0.1K and 0.2K.)

High-duty brake resistor (FR-ABR) Thermal relay (OCR) (∗1)
∗3 Refer to the table below for the type number of each capacity of thermal relay and the diagram below for the connection.
(Always install a thermal relay when using a brake resistor whose capacity is 11K or higher)
∗4 When the power supply is 400V class, install a step-down transformer.

FR-ABR-0.75K TH-N20CXHZ-1.3A FR-ABR-2.2K TH-N20CXHZ-2.1A FR-ABR-3.7K TH-N20CXHZ-3.6A FR-ABR-5.5K TH-N20CXHZ-5A FR-ABR-7.5K TH-N20CXHZ-6.6A FR-ABR-11K TH-N20CXHZ-11A FR-ABR-15K TH-N20CXHZ-11A
FR-ABR-H0.4K TH-N20CXHZ-0.24A FR-ABR-H0.75K TH-N20CXHZ-0.35A FR-ABR-H1.5K TH-N20CXHZ-0.9A FR-ABR-H2.2K TH-N20CXHZ-1.3A FR-ABR-H3.7K TH-N20CXHZ-2.1A FR-ABR-H5.5K TH-N20CXHZ-2.5A FR-ABR-H7.5K TH-N20CXHZ-3.6A FR-ABR-H11K TH-N20CXHZ-6.6A FR-ABR-H15K TH-N20CXHZ-6.6A
To the inverter terminal P/+
y The brake resistor connected should only be the dedicated brake resistor.
y Brake resistor cannot be used with the brake unit, etc.
y Do not use the brake resistor (MRS type, MYS type) with a lead wire extended.
y Do not connect a resistor directly to the terminals P/+ and N/-. This could cause a fire.
To a resistor

2.4.2 Connection of the brake unit (FR-BU2)
Connect the brake unit (FR-BU2(-H)) as shown below to improve the braking capability at deceleration. If the transistors in the
brake unit should become faulty, the resistor can be unusually hot. To prevent unusual overheat and fire, install a magnetic contactor on the inverter's input side to configure a circuit so that a current is shut off in case of fault. (1) Connection example with the GRZG type discharging resistor

∗1 Connect the inverter terminals (P/+ and N/-) and brake unit (FR-BU2) terminals so that their terminal names match with each other. (Incorrect connection will damage the inverter and brake unit.) ∗2 When the power supply is 400V class, install a step-down transformer. ∗3 The wiring distance between the inverter, brake unit (FR-BU2) and discharging resistor should be within 5m. Even when the wiring is twisted, the cable length must not exceed 10m. ∗4 It is recommended to install an external thermal relay to prevent overheat of discharging resistors. ∗5 Refer to FR-BU2 manual for connection method of discharging resistor.

FR-BU2-3.7K GRZG 200-10Ω (three in series) TH-N20CXHZ 3.6A
FR-BU2-7.5K GRZG 300-5Ω (four in series) TH-N20CXHZ 6.6A
FR-BU2-15K GRZG 400-2Ω (six in series) TH-N20CXHZ 11A
FR-BU2-H7.5K GRZG 200-10Ω (six in series) TH-N20CXHZ 3.6A
FR-BU2-H15K GRZG 300-5Ω (eight in series) TH-N20CXHZ 6.6A
y Set "1" in Pr. 0 Brake mode selection of the FR-BU2 to use GRZG type discharging resistor.
y Do not remove the jumper across terminals P/+ and P1 except when connecting a DC reactor.

OFF ON
T
MC
MC
FR-BR
MCCB MC
R/L1
U
P
TH1
Three-phase AC power supply
IM
PR
T/L3
W
TH2
FR-BU2
PR
A
P/+
P/+
B
N/-
N/-
BUE
SD
∗1 Connect the inverter terminals (P/+ and N/-) and brake unit (FR-BU2) terminals so that their terminal names match with each other. (Incorrect connection will damage the inverter and brake unit.) ∗2 When the power supply is 400V class, install a step-down transformer. ∗3 The wiring distance between the inverter, brake unit (FR-BU2) and resistor unit (FR-BR) should be within 5m. Even when the wiring is twisted, the cable length must not exceed 10m. ∗4 Normal: across TH1-TH2...close, Alarm: across TH1-TH2...open ∗5 A jumper is connected across BUE and SD in the initial status.
y Do not remove the jumper across terminals P/+ and P1 except when connecting a DC reactor.
When using the DC reactor (FR-HEL), connect it across terminals P/+ and P1.
In this case, the jumper connected across terminals P/+ and P1 must be removed. Otherwise, the reactor will not exhibit its performance.
P/+
FR-HEL
Remove the jumper.
y The wiring distance should be within 5m.
y The size of the cables used should be equal to or larger than that of the power supply cables (R/L1, S/L2, T/L3). (Refer

OF THE INVERTER
This chapter explains the "PRECAUTIONS FOR USE OF THE
INVERTER" for use of this product.
Always read the instructions before using the equipment.
3.2 Installation of power factor improving reactor ......................... 37
3.3 Power-OFF and magnetic contactor (MC) ................................. 38
3.4 Inverter-driven 400V class motor ............................................... 39
3.5 Precautions for use of the inverter ............................................ 40
3.6 Failsafe of the system which uses the inverter ........................ 42

3.1 EMC and leakage currents
3.1.1 Leakage currents and countermeasures
Capacitances exist between the inverter I/O cables, other cables and earth and in the motor, through which a leakage current flows. Since its value depends on the static capacitances, carrier frequency, etc., low acoustic noise operation at the increased carrier frequency of the inverter will increase the leakage current. Therefore, take the following measures. Select the earth leakage current breaker according to its rated sensitivity current, independently of the carrier frequency setting.
Leakage currents may flow not only into the inverter's own line but also into the other lines through the earth (ground) cable,
etc. These leakage currents may operate earth (ground) leakage circuit breakers and earth leakage relays unnecessarily.
y If the carrier frequency setting is high, decrease the Pr. 72 PWM frequency selection setting.
line, operation can be performed with the carrier frequency kept high (with low noise). zTo-earth (ground) leakage currents
y Take caution as long wiring will increase the leakage current. Decreasing the carrier frequency of the inverter reduces the
leakage current. y Increasing the motor capacity increases the leakage current. The leakage current of the 400V class is larger than that of
the 200V class. (2) Line-to-line leakage currents
Harmonics of leakage currents flowing in static capacitances between the inverter output cables may operate the external thermal relay unnecessarily. When the wiring length is long (50m or more) for the 400V class small-capacity model (7.5kW or
less), the external thermal relay is likely to operate unnecessarily because the ratio of the leakage current to the rated motor current increases.
zLine-to-line leakage current data example (200V class)
Leakage Current (mA) * Wiring length 50m Wiring length 100m
0.4 1.8 310 500 0.75 3.2 340 530 1.5 5.8 370 560 2.2 8.1 400 590 3.7 12.8 440 630 5.5 19.4 490 680 7.5 25.6 535 725
*The leakage currents of the 400V class are about twice as large.
Line-to-line leakage currents path
y Use Pr. 9 Electronic thermal O/L relay. y If the carrier frequency setting is high, decrease the Pr. 72 PWM frequency selection setting.
zInstallation and selection of moulded case circuit breaker
Install a moulded case circuit breaker (MCCB) on the power receiving side to protect the wiring of the inverter input side. Select the MCCB according to the inverter input side power factor (which depends on the power supply voltage, output frequency and load). Especially for a completely electromagnetic MCCB, one of a slightly large capacity must be selected since its operation characteristic varies with harmonic currents. (Check it in the data of the corresponding breaker.) As an earth leakage current breaker, use the Mitsubishi earth leakage current breaker designed for harmonics and surge suppression.

When using the earth leakage current breaker with the inverter circuit, select its rated sensitivity current as follows, independently of the PWM carrier frequency.
y Breaker designed for harmonic and
Ign: Leakage current of inverter input side noise filter Igm: Leakage current of motor during commercial power
Rated sensitivity current:
IΔn≥10×{Ig1+Ign+Igi+3×(Ig2+Igm)}

Example of leakage current of cable path per 1km during the commercial power supply operation when the CV cable is routed in metal conduit
Example of leakage current of three-phase induction motor during the commercial power supply operation

Example of leakage current per 1km during the commercial power supply operation when the CV cable is routed in metal conduit
Example of leakage current of three- phase induction motor during the commercial power supply operation
1.5 3.7 2.2 7.5 15 11 20 5.5 Motor capacity (kW) For " " connection, the amount of leakage current is appox.1/3 of the above value.
2 3.5 5.5 8 1422 30 38 60 80 100 150 0. 1
2 3.5 5.5 8 1422 30 38 60 80 100 150
0.1 0.2 0.4 0.75 1.5 2.2 3.7 5.5 11 7.5 20 15
Leakage current Ig1 (mA) 33 × 5m = 0.17 1000m
5.5mm2 50m 5.5mm2 5m
Leakage current Ign (mA) 0 (without noise filter)
Leakage current Igi (mA) 1
IM 3φ 200V2.2kW
Leakage current Ig2 (mA) 33 × 50m = 1.65 1000m
Ig1 Ign Ig2 Igm
Motor leakage current Igm (mA) 0.18
Total leakage current (mA) 3.00 6.66
Rated sensitivity current (mA)
(≥Ig × 10) 30 100
y Install the earth leakage breaker (ELB) on the input side of the inverter.
y In the connection earthed-neutral system, the sensitivity current is blunt against an earth (ground) fault in the
inverter output side. Earthing (Grounding) must conform to the requirements of national and local safety regulations
and electrical codes. (NEC section 250, IEC 536 class 1 and other applicable standards)
y When the breaker is installed on the output side of the inverter, it may be unnecessarily operated by harmonics even
if the effective value is less than the rating.
In this case, do not install the breaker since the eddy current and hysteresis loss will increase, leading to temperature
rise.
y General products indicate the following models BV-C1, BC-V, NVB, NV-L, NV-G2N, NV-G3NA, NV-2F earth leakage
relay (except NV-ZHA), NV with AA neutral wire open-phase protection
The other models are designed for harmonic and surge suppression NV-C/NV-S/MN series, NV30-FA, NV50-FA, BV-
C2, earth leakage alarm breaker (NF-Z), NV-ZHA, NV-H

3.1.2 EMC measures
Some electromagnetic noises enter the inverter to malfunction it and others are radiated by the inverter to malfunction
peripheral devices. Though the inverter is designed to have high immunity performance, it handles low-level signals, so it requires the following basic techniques. Also, since the inverter chops outputs at high carrier frequency, that could generate
electromagnetic noises. If these electromagnetic noises cause peripheral devices to malfunction, EMI measures should be taken to suppress noises. These techniques differ slightly depending on EMI paths.
(1) Basic techniques y Do not run the power cables (I/O cables) and signal cables of the inverter in parallel with each other and do not bundle
them. y Use twisted shield cables for the detector connecting and control signal cables and connect the sheathes of the shield
cables to terminal SD. y Earth (Ground) the inverter, motor, etc. at one point.
(2) Techniques to reduce electromagnetic noises that enter and malfunction the inverter (Immunity measures) When devices that generate many electromagnetic noises (which use magnetic contactors, magnetic brakes, many relays,
for example) are installed near the inverter and the inverter may be malfunctioned by electromagnetic noises, the following measures must be taken:
y Provide surge suppressors for devices that generate many electromagnetic noises to suppress electromagnetic noises. y Fit data line filters (page 33) to signal cables.
y Earth (Ground) the shields of the detector connection and control signal cables with cable clamp metal.
(3) Techniques to reduce electromagnetic noises that are radiated by the inverter to malfunction peripheral devices (EMI
measures) Inverter-generated electromagnetic noises are largely classified into those radiated by the cables connected to the inverter
and inverter main circuits (I/O), those electromagnetically and electrostatically induced to the signal cables of the peripheral devices close to the main circuit power supply, and those transmitted through the power supply cables.
Inverter generated electromagnetic noise
Noise directly radiated from inverter
Noise radiated from power supply cable
Noise radiated from motor connection cable
Electrical path propagated noise
Noise propagated through power supply cable
Noise from earth (ground) cable due to leakage current

When devices that handle low-level signals and are liable to malfunction due to electromagnetic noises, e.g.
instruments, receivers and sensors, are contained in the enclosure that contains the inverter or when their signal
cables are run near the inverter, the devices may be malfunctioned by air-propagated electromagnetic noises. The
following measures must be taken:
y Install easily affected devices as far away as possible from the inverter.
y Run easily affected signal cables as far away as possible from the inverter and its I/O cables.
y Do not run the signal cables and power cables (inverter I/O cables) in parallel with each other and do not bundle them.
y Insert common mode filters into I/O and capacitors between the input lines to suppress cable-radiated noises.
y Use shield cables as signal cables and power cables and run them in individual metal conduits to produce further effects.
When the signal cables are run in parallel with or bundled with the power cables, magnetic and static induction noises
may be propagated to the signal cables to malfunction the devices and the following measures must be taken:
y Install easily affected devices as far away as possible from the inverter.
y Run easily affected signal cables as far away as possible from the I/O cables of the inverter.
y Do not run the signal cables and power cables (inverter I/O cables) in parallel with each other and do not bundle them.
y Use shield cables as signal cables and power cables and run them in individual metal conduits to produce further effects.
When the power supplies of the peripheral devices are connected to the power supply of the inverter in the same line,
inverter-generated noises may flow back through the power supply cables to malfunction the devices and the
following measures must be taken:
y Install the common mode filter (FR-BLF, FR-BSF01) to the power cables (output cable) of the inverter.
When a closed loop circuit is formed by connecting the peripheral device wiring to the inverter, leakage currents may
flow through the earth (ground) cable of the inverter to malfunction the device. In such a case, disconnection of the
earth (ground) cable of the device may cause the device to operate properly.
zData line filter
Data line filter is effective as an EMC measure. Provide a data line filter for the detector cable, etc.
Install common mode filter
FRBLF FRBSF01
Install common mode filter
on inverter input side.
on inverter output side.
PRECAUTIONS FOR USE OF THE INVERTER
Install capacitor type FR-BIF filter on inverter input side.
Use 4-core cable for motor power cable and use one cable as earth (ground) cable.
Separate inverter and power line by more than 30cm (at least 10cm) from sensor circuit.
Use a twisted pair shielded cable
Power supply for sensor
Do not earth (ground) enclosure directly.
Do not earth (ground) shield but connect it to signal common cable.
Do not earth (ground) control cable.
y For compliance with the EU EMC directive, please refer the Instruction Manual (Basic).

3.1.3 Power supply harmonics
The inverter may generate power supply harmonics from its converter circuit to affect the power generator, power capacitor
etc. Power supply harmonics are different from noise and leakage currents in source, frequency band and transmission path. Take the following countermeasure suppression techniques.
zThe differences between harmonics and RF noises are indicated below:
Frequency Normally 40th to 50th degrees or less
(up to 3kHz or less) High frequency (several 10kHz to 1GHz order)
Environment To-electric channel, power impedance To-space, distance, wiring path
Quantitative understanding Theoretical calculation possible Random occurrence, quantitative grasping difficult
Generated amount Nearly proportional to load capacity Change with current variation ratio (larger as switching
Affected equipment immunity Specified in standard per equipment Different depending on maker's equipment specifications
Suppression example Provide reactor. Increase distance.
The harmonic current generated from the inverter to the input side differs according to various
conditions such as the wiring impedance, whether a reactor is used or not, and output frequency and
output current on the load side. For the output frequency and output current, we understand that they should be calculated in the
R
X U
P1 R/L1
P/+
S
Y
S/L2
IM
conditions under the rated load at the maximum operating frequency.
T/L3
W
(FR-HAL)
Do not insert power factor improving capacitor.
The power factor improving capacitor and surge suppressor on the inverter output side may be overheated or damaged
by the harmonic components of the inverter output. Also, since an excessive current flows in the inverter to activate
overcurrent protection, do not provide a capacitor and surge suppressor on the inverter output side when the motor is
driven by the inverter. For power factor improvement, install a reactor on the inverter input side or in the DC circuit.

3.1.4 Harmonic suppression guideline in Japan
Harmonic currents flow from the inverter to a power receiving point via a power transformer. The harmonic suppression guideline was established to protect other consumers from these outgoing harmonic currents. The three-phase 200V input specifications 3.7kW or less are previously covered by "Harmonic suppression guideline for household appliances and general-purpose products" and other models are covered by "Harmonic suppression guideline for consumers who receive high voltage or special high voltage". However, the transistorized inverter has been excluded from the target products covered by "Harmonic suppression guideline for household appliances and general-purpose products" in January 2004 and "Harmonic suppression guideline for household appliances and general-purpose products" was repealed on September 6, 2004. All capacity and all models of general-purpose inverter used by specific consumers are covered by "Harmonic suppression guideline for consumers who receive high voltage or special high voltage" (hereinafter referred to as "Guideline for specific consumers"). "Guideline for specific consumers"
This guideline sets forth the maximum values of harmonic currents outgoing from a high-voltage or especially high-voltage consumer who will install, add or renew harmonic generating equipment. If any of the maximum values is exceeded, this guideline requires that consumer to take certain suppression measures.
Table 1 Maximum Values of Outgoing Harmonic Currents per 1kW Contract Power
Received Power Voltage 5th 7th 11th 13th 17th 19th 23rd Over 23rd 6.6kV 3.5 2.5 1.6 1.3 1.0 0.9 0.76 0.70 22kV 1.8 1.3 0.82 0.69 0.53 0.47 0.39 0.36 33kV 1.2 0.86 0.55 0.46 0.35 0.32 0.26 0.24

capacity total Equal to or less than reference capacity Equivalent capacity total
Table 2 Conversion Factors for FR-E700 Series

Without reactor K31= 3.4 With reactor (AC side) K32 = 1.8 With reactor (DC side) K33 = 1.8 With reactors (AC, DC sides) K34 = 1.4
Table 3 Equivalent Capacity Limits
Received Power Voltage Reference Capacity 6.6kV 50kVA 22/33 kV 300kVA 66kV or more 2000kVA
Table 4 Harmonic Contents (Values at the fundamental current of 100%)

Reactor 5th 7th 11th 13th 17th 19th 23rd 25th Not used 65 41 8.5 7.7 4.3 3.1 2.6 1.8 Used (AC side) 38 14.5 7.4 3.4 3.2 1.9 1.7 1.3 Used (DC side) 30 13 8.4 5.0 4.7 3.2 3.0 2.2 Used (AC, DC sides) 28 9.1 7.2 4.1 3.2 2.4 1.6 1.4

generating equipment and is calculated with the following equation. If the sum of equivalent capacities is higher than the limit in Table 3, harmonics must be calculated with the following procedure:
P0 = Σ(Ki×Pi) [kVA] ∗Rated capacity: Determined by the capacity of the applied motor and
Ki: Conversion factor (refer to Table 2) Pi: Rated capacity of harmonic generating equipment∗[kVA] i: Number indicating the conversion circuit type
found in Table 5. It should be noted that the rated capacity used here is
used to calculate generated harmonic amount and is different from the
power supply capacity required for actual inverter drive.
y Harmonic content: Found in Table 4.
Table 5 Rated Capacities and Outgoing Harmonic Currents for Inverter Drive
Rated Current [A] Fundamental Wave Current
Outgoing Harmonic Current Converted from 6.6kV(mA)
(No reactor, 100% operation ratio)
Converted from 6.6kV
200V 400V 5th 7th 11th 13th 17th 19th 23rd 25th
0.4 1.61 0.81 49 0.57 31.85 20.09 4.165 3.773 2.107 1.519 1.274 0.882
0.75 2.74 1.37 83 0.97 53.95 34.03 7.055 6.391 3.569 2.573 2.158 1.494
1.5 5.50 2.75 167 1.95 108.6 68.47 14.20 12.86 7.181 5.177 4.342 3.006
2.2 7.93 3.96 240 2.81 156.0 98.40 20.40 18.48 10.32 7.440 6.240 4.320
3.7 13.0 6.50 394 4.61 257.1 161.5 33.49 30.34 16.94 12.21 10.24 7.092
5.5 19.1 9.55 579 6.77 376.1 237.4 49.22 44.58 24.90 17.95 15.05 10.42
7.5 25.6 12.8 776 9.07 504.4 318.2 65.96 59.75 33.37 24.06 20.18 13.97
11 36.9 18.5 1121 13.1 728.7 459.6 95.29 86.32 48.20 34.75 29.15 20.18
15 49.8 24.9 1509 17.6 980.9 618.7 128.3 116.2 64.89 46.78 39.24 27.16
If the outgoing harmonic current is higher than the maximum value per 1kW contract power × contract power, a harmonic suppression technique is required.
No. Item Description
Install an AC reactor (FR-HAL) on the AC side of the inverter or a DC reactor (FR-HEL) on its DC side or both to suppress outgoing harmonic currents.
2 Installation of power factor
When used with a series reactor, the power factor improving capacitor has an effect of absorbing harmonic currents.
Use two transformers with a phase angle difference of 30° as in -Δ, Δ-Δ combination to provide an effect corresponding to 12 pulses, reducing low-degree harmonic currents.
A capacitor and a reactor are used together to reduce impedances at specific frequencies, producing a great effect of absorbing harmonic currents.
This filter detects the current of a circuit generating a harmonic current and generates a harmonic current equivalent to a difference between that current and a fundamental wave current to suppress a harmonic current at a detection point, providing a great effect of absorbing harmonic currents.

3.2 Installation of power factor improving reactor
When the inverter is connected near a large-capacity power transformer (500kVA or more) or when a power capacitor is to be
switched over, an excessive peak current may flow in the power input circuit, damaging the converter circuit. To prevent this, always install an optional reactor (FR-HAL, FR-HEL).
Power supply system capacity
MCCB MC
R
X U
R/L1
Range requiring installation of the reactor
Y
S/L2
IM
T Z
T/L3
W P1
P/+
DC reactor (FR-HEL) *
∗ When connecting the FR-HEL, remove the jumper across terminals P/+ and P1.
The wiring length between the FR-HEL and inverter should be 5m maximum and minimized.
y Use the same wire size as that of the power supply wire (R/L1, S/L2, T/L3). (Refer to page 17)

3.3 Power-OFF and magnetic contactor (MC)
On the inverter input side, it is recommended to provide an MC for the following purposes.
(Refer to page 4 for selection.) 1) To release the inverter from the power supply when the fault occurs or when the drive is not functioning (e.g. emergency
stop operation). For example, MC avoids overheat or burnout of the brake resistor when heat capacity of the resistor is insufficient or brake regenerative transistor is damaged with short while connecting an optional brake resistor.
The inverter's input side MC is used for the above purpose, select class JEM1038-AC3 MC for the inverter input side current when making an emergency stop during normal operation.
y Since repeated inrush currents at power ON will shorten the life of the converter circuit (switching life is about 1,000,000
times.), frequent starts and stops of the magnetic contactor must be avoided. Start and stop the inverter by turning ON/OFF the
input signal (forward/reverse rotation signal) of the FL remote communication.
y If the main power supply needs to be shut off at an inverter fault, configure a system where the output of an inverter alarm is
monitored through FL remote communication, and the magnetic contactor is turned OFF by an programmable controller output.
Three- phase AC power supply
S/L2
IM
MC
T/L3
W
Y00
COM FL remote communication
Switch the magnetic contactor between the inverter and motor only when both the inverter and motor are at a stop. When the
magnetic contactor is turned ON while the inverter is operating, overcurrent protection of the inverter and such will activate. When an MC is provided for switching to the commercial power supply, for example, switch it ON/OFF after the inverter and
motor have stopped.

3.4 Inverter-driven 400V class motor
In the PWM type inverter, a surge voltage attributable to wiring constants is generated at the motor terminals. Especially for a
400V class motor, the surge voltage may deteriorate the insulation. When the 400V class motor is driven by the inverter, consider the following measures:
It is recommended to take either of the following measures: (1) Rectifying the motor insulation and limiting the PWM carrier frequency according to the wiring
For the 400V class motor, use an insulation-enhanced motor. Specifically,
motor". 3) Set Pr. 72 PWM frequency selection as indicated below according to the wiring length
Wiring Length 50m or less 50m to 100m exceeding 100m
Pr. 72 PWM frequency selection 15 (14.5kHz) or less 8 (8kHz) or less 2 (2kHz) or less
Connect the surge voltage suppression filter (FR-ASF-H/FR-BMF-H) on the inverter output side.
y For details of Pr. 72 PWM frequency selection, refer to page 163.
y For explanation of surge voltage suppression filter (FR-ASF-H/FR-BMF-H), refer to the manual of each option.
zMeasures

3.5 Precautions for use of the inverter
The FR-E700 series is a highly reliable product, but incorrect peripheral circuit making or operation/handling method may
shorten the product life or damage the product. Before starting operation, always recheck the following items.
(1) Use crimping terminals with insulation sleeve to wire the power supply and motor.
(2) Application of power to the output terminals (U, V, W) of the inverter will damage the inverter. Never perform
such wiring.
(3) After wiring, wire offcuts must not be left in the inverter. Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean.
When drilling mounting holes in an enclosure etc., take care not to allow chips and other foreign matter to enter the inverter.
(4) Use cables of the size to make a voltage drop 2% or less.
If the wiring distance is long between the inverter and motor, a main circuit cable voltage drop will cause the motor torque to decrease especially at the output of a low frequency.
Refer to page 17 for the recommended wire sizes.
(5) The overall wiring length should be 500m or less. Especially for long distance wiring, the fast-response current limit function may decrease or the equipment connected to
the secondary side may malfunction or become faulty under the influence of a charging current due to the stray capacity of the wiring. Therefore, note the overall wiring length. (Refer to page 19)
The input/output (main circuit) of the inverter includes high frequency components, which may interfere with the
communication devices (such as AM radios) used near the inverter. In this case, install the FR-BIF optional capacitor type filter (for use in the input side only) or FR-BSF01 common mode filter to minimize interference.
(7) Do not install a power factor correction capacitor, surge suppressor or capacitor type filter on the inverter
output side. This will cause the inverter to trip or the capacitor and surge suppressor to be damaged. If any of the above devices are
connected, immediately remove them.
(8) For some short time after the power is switched OFF, a high voltage remains in the smoothing capacitor. Before wiring or inspecting inside the inverter, wait 10 minutes or longer after turning OFF the power supply, then confirm
that the voltage across the main circuit terminals P/+ and N/- of the inverter is 30VDC or less using a tester, etc. The capacitor is charged with high voltage for some time after power OFF, and it is dangerous.
(9) If "EV" is displayed on the operation panel, turn off the 24V external power supply before wiring and inspection.
(10) A short circuit or earth (ground) fault on the inverter output side may damage the inverter modules.
y Fully check the insulation resistance of the circuit prior to inverter operation since repeated short circuits caused by
peripheral circuit inadequacy or an earth (ground) fault caused by wiring inadequacy or reduced motor insulation
resistance may damage the inverter modules.
y Fully check the to-earth (ground) insulation and phase to phase insulation of the inverter output side before power-on.
Especially for an old motor or use in hostile atmosphere, securely check the motor insulation resistance etc.
(11) Do not use the inverter input side magnetic contactor to start/stop the inverter.
Since repeated inrush currents at power ON will shorten the life of the converter circuit (switching life is about 1,000,000
times.), frequent starts and stops of the MC must be avoided. Turn ON/OFF the inverter start controlling terminals (STF, STR) to run/stop the inverter. (Refer to page 38)

(12) Across P/+ and PR terminals, connect only an external regenerative brake discharging resistor.
Do not connect a mechanical brake.
The brake resistor cannot be connected to the 0.1K or 0.2K. Leave terminals P/+ and PR open. Also, never short between these terminals.
(13) Do not apply a voltage higher than the permissible voltage to the inverter I/O signal circuits.
Application of a voltage higher than the permissible voltage to the inverter I/O signal circuits or opposite polarity may damage the I/O devices.
MC2 which are used for bypass operation.
When the wiring is incorrect and if there is a bypass operation circuit as shown right, the inverter will be damaged when the
IM
V W
MC2
power supply is connected to the inverter U, V, W terminals, due
to arcs generated at the time of switch-over or chattering caused by a sequence error.
(15) If the machine must not be restarted when power is restored after a power failure, provide a magnetic contactor
in the inverter's input side and also make up a sequence which will not switch ON the start signal. If the start signal (start switch) remains ON after a power failure, the inverter will automatically restart as soon as the
power is restored.
On the inverter input side, connect a MC for the following purposes. (Refer to page 4 for selection.) 1)To release the inverter from the power supply when a fault occurs or when the drive is not functioning (e.g. emergency stop operation). For example, MC avoids overheat or burnout of the brake resistor when heat capacity of the resistor is insufficient or brake regenerative transistor is damaged with short while connecting an optional brake resistor. 2)To prevent any accident due to an automatic restart at restoration of power after an inverter stop made by a power failure 3)To separate the inverter from the power supply to ensure safe maintenance and inspection work. The inverter's input side MC is used for the above purpose, select class JEM1038-AC3 MC for the inverter input side current when making an emergency stop during normal operation.
Switch the magnetic contactor between the inverter and motor only when both the inverter and motor are at a stop. When the magnetic contactor is turned ON while the inverter is operating, overcurrent protection of the inverter and such will activate. When MC is provided for switching to the commercial power supply, for example, switch it ON/OFF after the inverter and motor have stopped.
When performing operation of frequent start/stop of the inverter, rise/fall in the temperature of the transistor element of
the inverter will repeat due to a repeated flow of large current, shortening the life from thermal fatigue. Since thermal fatigue is related to the amount of current, the life can be increased by reducing current at locked condition, starting
current, etc. Decreasing current may increase the life. However, decreasing current will result in insufficient torque and the inverter may not start. Therefore, choose the inverter which has enough allowance for current (up to 2 rank larger in
capacity).
(19) Make sure that the specifications and rating match the system requirements.

3.6 Failsafe of the system which uses the inverter
When a fault occurs, the inverter trips to output a fault signal. However, a fault output signal may not be output at an inverter
fault occurrence when the detection circuit or output circuit fails, etc. Although Mitsubishi assures best quality products, provide an interlock which uses inverter status output signals to prevent accidents such as damage to machine when the
inverter fails for some reason and at the same time consider the system configuration where failsafe from outside the inverter, without using the inverter, is enabled even if the inverter fails.
(1) Interlock method which uses the inverter status output signals By providing interlocks, inverter fault can be detected. For the interlocks, use different status output signals of the
inverter (virtual terminals of the FL remote communication) in combinations shown below.
Operation check of an alarm contact Circuit error detection by negative logic
Fault output signal (ALM signal) 59
Start signal (STF signal, STR signal) Running signal (RUN signal)
Start signal (STF signal, STR signal) Output current detection signal (Y12 signal)
Inverter fault occurrence (trip)
inverter trips, the fault output signal (ALM signal) is output. With this signal, you can check if the inverter is operating
properly.
ON
ON
OFF
Reset cancel signal (READY signal) is output when the reset operation of the inverter is cancelled by turning ON
ON OFF
RH
ON
the power of the inverter. Check if the READY signal is output after the reset
DC injection brake operation point
operation of the inverter is canceled.
DC injection brake operation
Pr. 13 Starting frequency
The inverter running signal (RUN signal) is output when the inverter is running.
Check if RUN signal is output when inputting the start signal to the inverter (forward signal is STF signal and
RUN ON OFF
reverse signal is STR signal). For logic check, note that RUN signal is output for the period from the inverter
decelerates until output to the motor is stopped, configure a sequence considering the inverter deceleration time.

4)Checking the motor operating status by the start signal input to the inverter and inverter output current detection signal. The output current detection signal (Y12 signal) is output when the inverter operates and currents flows in the motor.
Check if Y12 signal is output when inputting the start signal to the inverter (forward signal is STF signal and reverse signal is STR signal). Note that the current level at which Y12 signal is output is set to 150% of the inverter rated current
in the initial setting, it is necessary to adjust the level to around 20% using no load current of the motor as reference with Pr.150 Output current detection level.
For logic check, as same as the inverter running signal (RUN signal), the inverter outputs for the period from the inverter decelerates until output to the motor is stopped, configure a sequence considering the inverter deceleration time.
(2) Backup method outside the inverter Even if the interlock is provided by the inverter status signal, enough failsafe is not ensured depending on the failure
status of the inverter itself. For example, when the inverter CPU fails, even if the interlock is provided using the inverter fault output signal, start signal and RUN signal output, there is a case where a fault output signal is not output and RUN
signal is kept output even if an inverter fault occurs. Provide a speed detector to detect the motor speed and current detector to detect the motor current and consider the
backup system such as checking up as below according to the level of importance of the system.
1)Start signal and actual operation check Check the motor running and motor current while the start signal is input to the inverter by comparing the start signal to
the inverter and detected speed of the speed detector or detected current of the current detector. Note that the motor current runs as the motor is running for the period until the motor stops since the inverter starts decelerating even if the
start signal turns off. For the logic check, configure a sequence considering the inverter deceleration time. In addition, it is recommended to check the three-phase current when using the current detector.
2)Command speed and actual operation check
Check if there is no gap between the actual speed and commanded speed by comparing the inverter speed command and detected speed of the speed detector.
air volume, etc.)
To the alarm detection sensor


This chapter explains the "FL REMOTE COMMUNICATION
FUNCTION" for use of this product.
Always read the instructions before using the equipment.
4.2 Node address setting .................................................................. 46
4.3 Wiring............................................................................................ 47
4.4 LED status .................................................................................... 49
4.5 Operation mode setting............................................................... 50
4.6 FL remote communication.................. ....................................... 52
4.7 Cyclic transmission..................................................................... 53
4.8 Message transmission ................................................................ 61

4.1 FL remote communication specification
Type Built-in to an inverter, RJ-45 connector connection method Power supply Supplied from the inverter or the 24V external power supply
Connection cable FL-net dedicated cable (Refer to page 47)
Communication speed Auto negotiation (auto detection) (10Mbps/100Mbps)
Topology y Star (connection with a hub in the center)
y Star bus (connection with multiple hubs)
Transmission protocol FL remote
Node address setting Can be set with node address switch. (Refer to page 46)
Reflected to IP address as well. (192.168.250. node address) I/O points Input 64 points, output 64 points
Set the node address between "1 to 64" using node address switches. (Refer to page 2) The setting is applied when the power turns OFF once, then ON again.
Set the arrow (×) of the corresponding switches to the number to set a desired address.
Node address 1: Set the "×" of X10(SW2) to "0" and the "×" of X1(SW1) to "1."
Node address 26: Set the "×" of X10(SW2) to "2" and the "×" of X1(SW1) to "6."
y Always remove the front cover before setting a node address with node address switches.
(Refer to page 5 for how to remove the front cover.)
y Set the node address switch to the switch number position correctly. If the switch is set
between numbers, normal data communication can not be established.
y If the node address switch is set to a value other than "1 to 64", it is invalid due to outside of setting range. In this
case, DEV LED is lit red and E.OPT appears on the operation panel. (Refer to page 209)
y You cannot set the same node address to other devices on the network. (Doing so disables proper communication.)
y Set the inverter node address before switching ON the inverter and do not change the setting while power is
ON. Otherwise you may get an electric shock.

4.3 Wiring
4.3.1 Connecting to the network
(1) Be sure to check the following points before connecting the inverter to the network. y Check that the correct node address is set. (Refer to page 46) y Check that the FL-net dedicated cable is correctly connected to the FL remote communication connector. (Refer to page 48) (2) System configuration

Enough safety measures are necessary when installing the FL-net dedicated cable and connecting to the FL remote network. Consult the network provider and network administrator (person in charge of network planning and IP address management) including terminal treatment of connection cable, construction of trunk cable, etc. We are not responsible for system troubles from connecting to the FL remote network.
Use the following FL-net dedicated cables.
Cables :TPCC5 or more(Twisted Pair Communication Cable for LAN Category 5) For the shape, use STP (Shielded Twisted Pair)
(according to the 100BASE-TX(IEEE802.3u) standard) Maximum wiring length :100m maximum between the hub and the inverter
(according to the 100BASE-TX(IEEE802.3u) standard)

y FL-net dedicated cable...recommended product (as of October 2009)
Model name Cable length Manufacturer FLG-S-{{{ 1m to 100m Shinwa Co., Ltd. (Example: when the cable length is 1m) FLG-S-010


Connect the FL-net dedicated cable to the FL remote communication connector.
y Do not connect the FL-net dedicated cable to the terminal reserved for manufacturer settings.
Do not connect a parameter unit (FR-PU07, etc.) to the FL remote communication connector. Doing so may
Take caution not to subject the cables to stress.
After wiring, wire offcuts must not be left in the inverter. Wire offcuts can cause an alarm, failure or


Each LED indicates the operating status of the inverter and network according to the indication status.
: Communication set status LED : Device status LED : Reception/transmission LED : Remote status LED
LED Status Node Status Description DEV RMT
Power is OFF The inverter power is OFF.
y Node address is out of range (other than 1 to 64).
y The option board is faulty.
y A contact fault or other failure has occurred in the option connector between the
inverter and a communication option.
FL remote network is not connected Although hardware is normal, it is not connected to the FL remote network.
FL remote network at a remote stop It is correctly set to connect to the FL remote network and waiting for remote I/O control.
FL remote network during remote
connection processing Although remote I/O control started, initial processing is in progress.
Master is not present When the master is disconnected from FL remote network. FL remote network
during remote operation During remote I/O control
Own node is disconnected When the own node is disconnected from FL remote network.
Setting error Although it is connected to the FL remote, setting error is found.
(When the slave is not the one the master is expected.) Duplicate node When node address is duplicate with other node address Unsupported protocol Communication is attempted via an unsupported protocol.
:OFF, : red is lit, : green is lit, :red is flickering, : green is flickering, : red and green are alternately flickering

Transmitting (TX)/receiving (RX) Flickers at high speed during continuous transmitting/receiving

LED Status Node Status Description Communication setting is not
Red flickers when the setting value actually reflected and of node address switch
differ. The setting value of the node address switch is reflected by re-powering ON the
inverter in this status, then communication setting status LED turns OFF.
Hardware fault

4.5 Operation mode setting
4.5.1 Operation mode basics
y The operation mode specifies the source of the start command and the frequency command for the inverter. y Basically, there are following operation modes.
y Network operation mode (NET operation mode): For inputting a start command and a frequency command through FL
remote communication.
y PU operation mode: For inputting start command and frequency command with the operation panel.
y At power-on, the inverter starts up in the Network operation mode. The operation mode can be switched using on the
operation panel when "1" is set in the X12 signal (Bit11). X12 signal gives a control input command through FL remote communication. (Refer to page 57)
y Confirm the operation mode from the operation panel. (Refer to page 74)

y The stop function (PU stop selection) activated by pressing of the operation panel is valid even in other than the
(Refer to Pr. 75 Reset selection/PU stop selection (page 165))

4.5.2 PU operation interlock
y The PU operation interlock function is designed to forcibly change the operation mode to the Network operation mode
when the PU operation interlock signal (X12) input turns OFF. This function prevents the operation mode from being accidentally unswitched from the PU operation mode. If the
operation mode is left unswitched from the PU operation mode, the inverter does not reply to the commands sent through FL remote communication.
X12 Signal Function/Operation Operation mode Parameter write
ON y Operation mode (PU, NET) switching enabled
Parameter write is enabled (depending on Pr. 77
Parameter write selection and each parameter write
y Output stop during Network operation
conditions (Refer to page 78 for the parameter list))
y Forcibly switched to Network operation mode
Parameter write is disabled
y Network operation allowed
(Note that the Pr.297 setting is available when Pr.296 ≠
y Switching between the PU operation mode is enabled
"9999.")
Mode Operating Status Switching to PU
During stop ON Æ OFF ∗1
If Network operation frequency setting and start
signal are entered, operation is performed in that
Running ON Æ OFF ∗1 Disallowed
status.
During stop OFF Æ ON During stop Allowed ON Æ OFF Disallowed
Running OFF Æ ON During operation Æ output stop Disallowed ON Æ OFF Output stop Æ operation Disallowed ∗1 The operation mode switches to the Network operation mode independently of whether the start signal (STF, STR) is ON or OFF. Therefore, the
motor is run in Network operation mode when the X12 signal is turned OFF with either of STF and STR ON.
∗2 At fault occurrence, pressing of the operation panel resets the inverter.
y If the X12 signal is ON, the operation mode cannot be switched to the PU operation mode when the start signal (STF,
STR) is ON.
y Operation availability in each operation mode is shown below.
(Monitoring and parameter read can be performed from any operation regardless of operation mode.)
PU Operation NET Operation
Run command (start) { ×
Run command (stop) { Δ ∗3
Running frequency setting { ×
Parameter write { ∗1 × ∗2
Inverter reset { ×
Run command (start) × {
Run command (stop) × {
Running frequency setting × {
Parameter write × ∗2 { ∗1
Inverter reset × {
∗1 Some parameters may be write-disabled according to the Pr. 77 Parameter write selection setting and operating status. (Refer to page 166)
∗2 Some parameters are write-enabled independently of the operation mode and command source presence/absence. When Pr. 77 = 2, write is enabled.
(Refer to the parameter list on page 78) Parameter clear is disabled. ∗3 Enabled only when stopped by the PU. At a PU stop, PS is displayed on the operation panel. As set in Pr. 75 Reset selection/PU stop selection. (Refer to page 165)

4.6 FL remote communication
4.6.1 Overview of FL remote communication
Main items to be output from the inverter to the network and their descriptions are explained below. ({: with function, ×: without function)

Inverter monitor Monitor various items such as inverter output current and
Inverter status Monitors the output signal of the inverter. { { 59, 64
Operation mode read Reads the operation mode of the inverter. × { 63
Output frequency read Monitors the output frequency of the inverter. { { 60, 64
Parameter read Reads parameter settings of the inverter. × { 65
Fault records Monitors the fault history of the inverter. × { 66
y Refer to page 51 for functions controllable from the network in each operation mode.
Main items which can be commanded from the network to the inverter and their descriptions are explained below.

Run command Sets the control input command such as forward rotation
signal (STF) and reverse rotation signal (STR). { × 57
Frequency setting Sets the running frequency of the inverter. { × 58
Parameter write Sets parameters of the inverter. × { 65
Fault records all clear Clears the fault of the inverter. × { 66
y Refer to page 51 for functions controllable from the network in each operation mode.
FL remote data communication supports "cyclic transmission" which transmits data periodically (Refer to page 53) and "message transmission" which transmits data non-periodically (Refer to page 61).


4.7 Cyclic transmission
Cyclic transmission transmits data periodically. Each node shares data through common memory. Data of I/O area is updated periodically by cyclic transmission.
The master controls the inverter by setting run command (control input command, set frequency, etc.) in the output data area. The inverter sets the inverter status (output frequency, output current, various signals, etc.) in the input data area and sends it to the master.
Node 1 Node 2

4.7.1 Common memory
Concept of common memory is stated below.
y The common memory is used as a shared memory between nodes which perform cyclic transmission. y The common memory has two areas which are "common memory area 1" and "common memory area 2".
Common memory area 1 is I/O data area. Common memory area 2 is the control information area. Two different areas can be assigned to each node.
y When the area each node sends exceed the transmission size (1024 bytes) by one frame, data is transmitted by multiple
frames.
y When receiving data which are divided into multiple frames as above, common memory is not updated until all frames sent
from one node are received. Synchronism per node unit is guaranteed.
y Entire network has an area of 8k bits (0.5k word) + 8k words = 8.5k words.
The maximum send data capacity per one node is 8.5k words. (Note that one word is 2 bytes.)
2 15 2 0
Common memory area 1
0.5k Word
8.5k Words
Common memory area 2
y Among common memory, both common memory area 1 and common memory 2 can be set as a transmission area of one
node as desired within the maximum area. y Each node on FL remote network can share the same data in the whole system by broadcasting data at a constant period.
In addition, each node has own transmission area which does not overlap each other to exchange data. (For common memory function, the transmission area assigned to one node is a receive area for other nodes.)
of node = 01
of node = 02
of node = 03
of node = 04

Size Description Refer to
Data to be sent from inverter to master (4 words).
The data includes inverter status, output frequency, etc. 59
Data to be sent from master to inverter (4 words).
The data includes starting command, frequency command, etc. 57
H00000000 0 4 Input data (#1) H00000008 4 4 Input data (#2) H00000010 8 4 Input data (#3) : H000001F0 248 4 Input data (#63) H000001F8 252 4 Input data (#64)
H00000200 256 4 Output data (#1) H00000208 260 4 Output data (#2) H00000210 264 4 Output data (#3) : H000003F0 504 4 Output data (#63) H000003F8 508 4 Output data (#64)
* When accessing a message, the access size should be the size stated in the table above.
y When node status is other than "during FL remote network remote operation", all output data is changed to "0".
(Refer to page 49 for change of the setting.)
y When transmitting a message, common memory area 1 and 2 are read only. (Refer to page 62)
Control information (inverter→master) 1024 words (2048 bytes)
Control information (master→inverter) 1024 words (2048 bytes)
indicates node address.)
H00000400 0 1 Slave status (#) H00000402 1 1 Actual status slave type (#1) H00000404 2 14 Simple setting check area (#1) : H00000BE0 1008 1 Slave status (#64) H00000BE2 1009 1 Actual status slave type (#64) H00000BE4 1010 14 Simple setting check area (#64)
H00000C00 1024 1 Remote control area (#1) H00000C02 1025 1 Expected slave type (#1) H00000C04 1026 14 Simple setting area (#1) : H000013E0 2032 1 Remote control area (#64) H000013E2 2033 1 Expected slave type (#64) H000013E4 2034 14 Simple setting area (#64)
* When accessing a message, the access size should be the size stated in the table above.
y When sending a message, common memory area 1 and 2 are read only. (Refer to page 62)

(1) Control information (inverter→master)
Value Slave status 0 FL remote network is not connected 1 FL remote network remote at a stop 2 FL remote network remote connection processing 3 FL remote network remote operating 4 Master is not present 5 Own node is disconnected 6 Setting error
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Output points H00 to H3F (One point to 64 point)
Input points H00 to H3F (One point to 64 point)
Not used. (Displays data imported in the simple setting area set from the master.)
(2) Control information (master→inverter)
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Refer to
Not used

4.7.2 Output data (master to inverter)
[Master output area (master → inverter)]

Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Set control input command such as forward and reverse rotation commands.
Bit Signal Description Related Parameters
0 STF signal Forward rotation
1 STR signal Reverse rotation
Pr. 59 = 0 (initial value) Low-speed operation command Pr. 4 to Pr. 6, Pr. 24 to Pr. 27 111
Pr. 59 = 1, 2 ∗1 Remote setting (setting clear) Pr. 59 113
Pr. 270 = 1 ∗2 Stop-on contact selection 0 Pr. 270, Pr. 275, Pr. 276 139
3 RM signal Pr. 59 = 0 (initial value) Middle-speed operation command Pr. 4 to Pr. 6, Pr. 24 to Pr. 27 111
Pr. 59 = 1, 2 ∗1 Remote setting (deceleration) Pr. 59 113
4 RH signal Pr. 59 = 0 (initial value) High-speed operation command Pr. 4 to Pr. 6, Pr. 24 to Pr. 27 111
Pr. 59 = 1, 2 ∗1 Remote setting (acceleration) Pr. 59 113
Pr. 270 = 1 ∗2 Stop-on contact selection 1 Pr. 270, Pr. 275, Pr. 276 139
6 to 8 — (not used) Always 0 — —
9 MRS signal Output stop 0: output shut off cancel, 1: output shut off Pr. 17 143
10 — (not used) Always 0 — —
Bit11 Signal Function/Operation Operation mode Parameter write
y Forcibly switched to Network
operation mode y Network operation is allowed y Switching to the PU operation
Parameter write is disabled (Note that the Pr.297 setting is available when Pr.296 ≠ "9999.")
y Operation mode (PU, NET)
Parameter write is enabled (depending on Pr. 77 Parameter write selection and each parameter write conditions)
switching is enabled y Output stop during Network
12 to 14 — (not used) Always 0 — —
Resets the inverter when the setting of Bit15 is changed from 0 to 1 at
occurrence of inverter error. Resetting the inverter resets the fault and initializes
the inverter status. (FL remote communication remains online.)
∗1 When Pr. 59 Remote function selection = "1" or "2", the functions of the RL, RM and RH signals are changed as given in the table.
∗2 When Pr. 270 Stop-on contact control selection = "1", functions of RL and RT signals are changed as in the table.
y The values of each bit, "0" and "1," indicate "OFF" and "ON."

The set frequency can be set in 0.01Hz increments.
0 to 15 0.00Hz to 400.00Hz 0.01Hz
Example: If you want to set 120.00Hz, set 12000, which is the value multiplied by 100.
y Regardless of the Pr.37 setting, the value is always set in frequency (Hz).
Bit Range Unit

4.7.3 Input data (inverter to master)
[Master input area (inverter → master)]

Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Monitors the output signal of the inverter from the network.
Bit Signal Description Related Parameters
Bit0 Bit1 Operation Forward rotation: 0 Reverse rotation: 0 During stop Forward rotation: 1 Reverse rotation: 0 During forward rotation Forward rotation: 0 Reverse rotation: 1 During reverse rotation Forward rotation: 1 Reverse rotation: 1 Not used
2 RUN signal Inverter running When the inverter output frequency reaches or exceeds Pr.13 Starting frequency, the value changes to "1". — 142
3 SU signal Reached the
When the output frequency reaches the set frequency, the
value changes to "1". Pr.41 144
4 — (not used) Always 0 — —
5 OL signal Overload alarm While stall prevention function is activated, the value
changes to "1". Pr.22, Pr.23, Pr.66 101
6 FU signal Output frequency
When the output frequency reaches the frequency set in Pr. 42
(Pr. 43 for reverse rotation), the value changes to "1". Pr.42, Pr.43 144
7 ALM signal Fault When the inverter protective function is activated to stop
the output (fault), the value changes to "1". — 192
8 — (not used) Always 0 — —
When an internal safety circuit fault (E.SAF, E. 6, E. 7, or
E.CPU) occurs, the value changes to "1". — —
10 Edit signal Edit enabled 0: Parameter change disabled (X12 signal = "0")
When the output current is higher than the Pr.150 setting
12 Y12 signal Output current
and persists for longer than the time set in Pr.151, the value
Pr.150, Pr.151 145
changes to "1".
When the output current is lower than the Pr.152 setting and
13 Y13 signal Zero current
persists for longer than the time set in Pr.153, the value
Pr.152, Pr.153 145
changes to "1".
15 — (not used) Always 0 — —
y The values of each bit, "0" and "1," indicate "OFF" and "ON."
Description of an alarm that occurred in the inverter can be read.
0 to 7 Alarm code When an alarm (fault) occurs in the inverter, fault code is displayed. (Refer to page 67)

Whether the control circuit capacitor, main circuit capacitor, cooling fan, and each parts of the inrush current limit circuit have reached the life alarm output level or not can be checked.
The control circuit capacitor life is calculated from the energization time and temperature
8 Control circuit capacitor life
according to the operating status, and is counted down from 100%.
An alarm is output when the control circuit capacitor life falls below 10%.
(The setting value goes back to 0 when the part is replaced.)
On the assumption that the main circuit capacitor capacitance at factory shipment is 100%, the
capacitor life is checked every time measurement is made. An alarm is output when the measured
value falls below 85%. The life check of the main circuit capacitor can be performed by measuring
9 Main circuit capacitor life
at the maintenance time, etc.
After setting "1" in Pr. 259 Main circuit capacitor life measuring, switch OFF power once, then ON
again to check that Pr. 259 = "3" (measuring completion).
(The setting value goes back to 0 when the part is replaced.)
10 Cooling fan life
This function detects that the cooling fan speed falls 50% or below and outputs an alarm.
(The setting value goes back to 0 when the part is replaced.)
Counts the number of contact (relay, contactor, thyristor) ON times and counts down every 100%
11 Inrush current limit circuit life
(0 times) to 1%/10,000 times.
Outputs an alarm when the speed reaches 10% (900000 times).
(The setting value goes back to 0 when the part is replaced.)
Output when the heatsink temperature reaches about 85% of the heatsink overheat protection
providing temperature. (Refer to page 199 for the details.)
14 — (not used) (Always 0)
When the Pr. 503 Maintenance timer setting has elapsed the time (100h increments) set in Pr.504
Maintenance timer alarm output set time, the value changes to 1. (Turn ON Y95 signal.)
When Pr. 504 = "9999", no function is selected. (Refer to page 180 for the details.)
y The values of each bit, "0" and "1," indicate "OFF" and "ON."
The output frequency of the inverter can be monitored in 0.01Hz increments.
0 to 15 0.00Hz to 400.00Hz 0.01Hz
Example: If the monitor value is 120.00Hz, 12000 (the value multiplied by 100) is displayed.
y Regardless of the Pr.37 setting, the value is always displayed in frequency (Hz).
The output current of the inverter can be monitored in 0.1A increments.
0 to 15 0.0A to 3276.7A 0.1A

4.8 Message transmission
Message transmission is a non-periodic data communication method to communicate to a specified node when send request
is given. Basic function of message transmission is as follows.
(1) When a node receives a token, one frame can be sent before sending cyclic frame. (2) The message frame size which can be sent at a time is 1024 bytes at maximum.
(3) This method applies algorithm which controls refresh time not exceeding refresh cycle permissible time. (4) Two transmission functions are available. One is "one-to-one message transmission" to send to specified nodes, and
another is "one-to-n message transmission" to send to all nodes. (5) y For "one-to-one message transmission", whether the other node has received data correctly or not is checked.
y For "one-to-n message transmission", response is not given after receipt of a message.

Following functions are provided with a message transmission.

Word block read/write Performs data read/write per word unit (one address 16 bit) to the virtual
address space (32 bit address space) of other node from the network. 62
Network parameter read Reads network parameter information of other node from network. 68
Log data read Reads log information of other node from network. 69
Log data clear Clears log information (Refer to page 69) of other node from network. 69
Profile read Reads system parameter of device profile of other node from network. 70
Message loopback Returns message data received then performs message communication
4.8.1 Error response at word block read/write
Error response may be received when reading/writing the product information of connected Mitsubishi inverter. In such a case, error code is attached to the data portion.
The list of error code is shown below.

H0020 Size error y Write size was other than one word.
H0030 Data error y A value outside the data range was specified.
y Attempted to write to a parameter during an operation.
Message frame · 1024 bytes

4.8.2 Word block read/write
Performs data read/write per word unit (one address 16 bit unit) to the virtual address space (32 bit address space) of other
node from the network. y Word block read

Offset Bit15 to Bit0 +0 Error code (Refer to page 61)
y Word block write

Offset Bit15 to Bit0 +0 Error code (Refer to page 61)

area 1 0 to 511 512 Input/output data { × 55
H00001400 2048 to 8191 6144 Control information (blank) × × 55
0 to 71 72 Product information { × 62
H100000C8 100 to 100 1 Operation mode { × 63
H100000DC 110 to 110 1 Inverter status { × 64
H100000F0 120 to 121 2 Set frequency { × 64
H10000190 200 to 299 100 Inverter monitor { × 64
H100007D0 1000 to 1999 1000 Parameter { { 65
H10001770 3000 to 3899 900 Fault record { { 66
Reads product information such as the inverter type, inverter capacity, etc.

∗When accessing a message, the access size should be the size stated in the table above.


Returns "MITSUBISHI ELECTRIC CORPORATION". The rest are the characters for space.
Offset Bit15 to Bit8 Bit7 to Bit0 +0 Second character First character +1 Fourth character Third character : +49 Hundredth character Ninety ninth character
Offset Bit15 to Bit0 +0 Error code (Refer to page 61)

For the 200V class FR-E700, "FR-E720" is returned. The rest are the characters for space.
Offset Bit15 to Bit8 Bit7 to Bit0 +0 Second character First character +1 Fourth character Third character : +19 Fortieth character Thirty ninth character
Offset Bit15 to Bit0 +0 Error code (Refer to page 61)

Inverter Capacity Value 0.1kW 1 0.2kW 2 : 15kW 150
Offset Bit15 to Bit0 +0 Error code (Refer to page 61)
Read the operation mode of the inverter from network.

∗When accessing a message, the access size should be the size stated in the table above.

Operation mode Value PU operation H0001 PUJOG operation H0003 Network operation H0004
Offset Bit15 to Bit0 +0 Error code (Refer to page 61)

Monitors the output signal of the inverter from network.

∗When accessing a message, the access size should be the size stated in the table above.

Inverter status is returned. (Refer to page 59 for details)
Offset Bit15 to Bit0 +0 Error code (Refer to page 61)
Set frequency can be read from RAM or EEPROM in 0.01Hz increments.

∗When accessing a message, the access size should be the size stated in the table above.

Offset Bit15 to Bit0 +0 Error code (Refer to page 61)
y Regardless of the Pr.37 setting, the value is always displayed in frequency (Hz).
Inverter monitored value can be read.

Offset Bit15 to Bit0 +0 Inverter monitor value (Refer to page 65)
Offset Bit15 to Bit0 +0 Error code (Refer to page 61)

Inverter monitor value of each monitor is as in the table below. (When accessing a message, the access size should be 2 bytes (1 word).)

∗Output terminal monitor details
— ALM signal
FU signal — — — Terminal
(7) Parameter
Inverter parameters can be read or written through the network. Refer to the Chapter 5 for details of the parameters.

∗When accessing a message, the access size should be the size stated in the table above.

Offset Bit15 to Bit0 +0 Error code (Refer to page 61)

Offset Bit15 to Bit0 +0 Error code (Refer to page 61)
y Parameter write is available only when "1" is set in the X12 signal (Bit11), which gives a control input command
through FL remote communication. (Refer to page 57)
(Note that the Pr.77 setting cannot be written through FL remote communication.)
b15 b0

Fault history can be monitored up to eight past faults occurred in the inverter.

H10001770 3000 1 Fault record all clear × {
H10001838 3100 to 3899 800 Past eight faults history { ×
H10001840 3104 1 Output frequency at fault occurrence { ×
H10001842 3105 1 Output current at fault occurrence { ×
H10001844 3106 1 Output voltage at fault occurrence { ×
H10001846 3107 1 Energization time at fault occurrence { ×
H10001DB8 3804 1 Output frequency at fault occurrence { ×
H10001DBA 3805 1 Output current at fault occurrence { ×
H10001DBC 3806 1 Output voltage at fault occurrence { ×
H10001DBE 3807 1 Energization time at fault occurrence { ×
∗When accessing a message, the access size should be the size stated in the table above.

Offset Bit15 to Bit0 +0 Error code (Refer to page 61)

Offset Bit15 to Bit0 +0 Fault code (Refer to page 67)
Offset Bit15 to Bit0 +0 Error code (Refer to page 61)

Alarm display (5 characters) is returned as a character string. (Refer to page 67)
Offset Bit15 to Bit8 Bit7 to Bit0 +0 Second character First character +1 Fourth character Third character +2 Sixth character (space character) Fifth character
Offset Bit15 to Bit0 +0 Error code (Refer to page 61)

Output frequency, output current, output voltage, and energization time at fault occurrence is
returned.
Offset Bit15 to Bit0 +0 Data at fault occurrence
Offset Bit15 to Bit0 +0 Error code (Refer to page 61)
Fault name is returned in a character string. The rest are space characters. (Refer to page 67)
Offset Bit15 to Bit8 Bit7 to Bit0 +0 Second character First character +1 Fourth character Third character : +89 One hundred eightieth character One hundred seventy-ninth character
Offset Bit15 to Bit0 +0 Error code (Refer to page 61)
Refer to page 194 for details of alarm definitions.
Fault code ∗ Fault
H0010 E.OC1 Overcurrent shut-off during acceleration
H0011 E.OC2 Overcurrent shut-off during constant speed
H0012 E.OC3 Overcurrent shut-off during deceleration or stop
H0020 E.OV1 Regenerative overvoltage shut-off during acceleration
H0021 E.OV2 Regenerative overvoltage shut-off during constant speed
H0022 E.OV3 Regenerative overvoltage shut-off during deceleration or stop
H0030 E.THT Inverter overload shut-off(electronic thermal relay function)
H0031 E.THM Motor overload shut-off(electronic thermal relay function)
H0040 E.FIN Fin overheat
H0052 E.ILF Input phase failure
H0060 E.OLT Stall prevention stop
H0070 E.BE Brake transistor alarm detection
H0080 E.GF Output side earth(ground) fault overcurrent
H0081 E.LF Output phase failure
H00A0 E.OPT Option alarm
H00A1 E.OP1 Communication option alarm
H00B0 E.PE Parameter storage device alarm
H00B2 E.RET Retry count excess
H00B3 E.PE2 Parameter storage device alarm
H00C0 E.CPU CPU error
H00C5 E.IOH Inrush current limit circuit alarm
H00C9 E.SAF Safety circuit fault
H00F1 E.1 Option1 alarm
CPU error H00F6 E.6
H00FD E.13 Internal circuit error
∗Alarm code size of cyclic transmission is 1 byte. The last two digits of alarm code are displayed.

4.8.3 Network parameter read
With this function, network parameter information of other node is read from network.
Offset Bit15 to Bit8 Bit7 to Bit0 Remarks +0 Second character First character Node name Character string of "FR-E700" is stored. In the reset places, space characters are set.
+1 Fourth character Third character +2 Sixth character Fifth character +3 Eighth character Seventh character +4 Tenth character Ninth character +5 Second character First character Vender name Character string of "MELCO" is stored. In the reset places, space characters are set.
+6 Fourth character Third character +7 Sixth character Fifth character +8 Eighth character Seventh character +9 Tenth character Ninth character +10 Second character First character Manufacturer model name Character string of "FR-A7NF" is stored. In the reset places, space characters are set.
+11 Fourth character Third character +12 Sixth character Fifth character +13 Eighth character Seventh character +14 Tenth character Ninth character +15 First address of area 1 +16 Size of area 1 Always 4 words +17 First address of area 2 +18 Size of area 2 Always 16 words
+19 (spare) Token monitoring time
out time Always 10ms
+20 (spare) Minimum permissible
clearance Always 1.0ms
+21 (spare) Link status Refer to the description below. +22 (spare) Protocol Always H80 +23 Higher-layer status Refer to the description below.
0 to 65535ms Refresh cycle permissible time (120% value of the time the token circulates one ring) of own node.
+24 Refresh cycle permissible time setting
+25 Refresh cycle measured value (present value) 0 to 65535ms Measured value (current value, maximum value, minimum value) of one cycle of own node.
+26 Refresh cycle measured value (maximum value)
+27 Refresh cycle measured value (minimum value)
Offset Bit15 to Bit0 +0 Error code (Refer to page 61)
b7 b6 b5 b4 b3
0 0 b2 b1 b0
The inverter periodically creates "higher layer status" based on "slave control status of FL remote" and "inverter status". In addition, the inverter reports the "higher layer status" to the master (FA link layer) periodically.
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Error information 00: NORMAL (Without inverter error) 01: WARNING (Minor fault occurrence) 10, 11: ALARM (Inverter error has occurred)
Operation information 0: STOP (Slave control status of FL remote is not operating) 1: RUN (Slave control status of FL remote is operating)

4.8.4 Log data read
With this function, log information of other node is read from network.
Offset Bit7 to Bit0
Offset Bit7 to Bit0
+152 to +164 —
+0 The number of communication socket
+168 The number of message transmission
+4 The number of communication socket
+172 The number of message sequence
+8 The number of Ethernet transmitting
error times +12 to +20 —
+176 The number of message sequence
retransmitting recognition times +180 to +188 — +192 The number of ACK error times
+24 The number of communication socket
+196 The number of ACK sequence version
+28 The number of communication socket
+32 The number of Ethernet receiving
+200 The number of ACK sequence
error times +36 to +44 —
+204 The number of ACK node number
+48 The number of token transmitting
error times +208 The number of ACK TCD error times +212 to +236 —
+52 The number of cyclic frame
+240 The number of token multiplexing
recognition times +244 The number of token destroyed times +248 The number of token reissued times +252 to +260 —
+56 The number of 1:1 message
+60 The number of 1:n message
transmitting times +64, +68 — +72 The number of token receiving times
+264 The number of token hold time out
+268 The number of token monitoring time
+76 The number of cyclic frame receiving
out times +272 to +284 — +288 Total operation times
+80 The number of 1:1 message receiving
+84 The number of 1:n message receiving
+292 The number of frame waiting status
times +88, +92 —
times +296 Entry time +300 The number of times disconnected
+96 The number of cyclic transmission
+304 The number of disconnected times
+100 The number of cyclic address size
error times +104 The number of cyclic CBN error times +108 The number of cyclic TBN error times
+308 The number of recognition times of
other node disconnected +312 to
+112 The number of cyclic BSIZE error
times +116 to +140 —
+364 List of participation recognized node
+144 The number of message transmission
+148 The number of message transmission
Offset Bit15 to Bit0 +0 Error code (Refer to page 61)
Clears log information (Refer to page 69) of other node from network.
Offset Bit15 to Bit0 +0 Error code (Refer to page 61)
![Page 81 of the Mitsubishi Electronics Frequency Inverter (FR-E700) user manual — [INTEGER], 2, (0001-9999),](/cdn/reader/49/4983794b9e0fb5e0e956aaa032267f3a437e9b0d83080e9aa676db83c0e269a6/images/page-81.webp?w=400)
4.8.6 Profile read
With this function, system parameter of device profile of other node is read from network.
Offset Bit15 to Bit0 +0
: Read data (see the table below for details)
Offset Bit15 to Bit0 +0 Error code (Refer to page 61)
Parameter Name Name character Data Type Parameter description Length Character Length Character
common specification version 6 "COMVER" INTEGER 1 1
character 2 "ID" PrintableString 7 "SYSPARA"
number 3 "REV" INTEGER 1 0
[INTEGER], 1, (01-12),
[INTEGER], 1, (01-31)
Device type 10 "DVCATEGORY" PrintableString 3 "INV"
Vender name 6 "VENDOR" PrintableString 10 "MELCO "
Product model name 7 "DVMODEL" PrintableString 10 "FR-A7NF "
Parameter Name Name Character Data Type Parameter Description Length Character Length Character
distinguishing characters 2 "ID" PrintableString 7 "DEVPARA"
MAC address 10 "MACADDRESS" INTEGER 6
(Example) 08 00 70 46 D0 00
Firmware version (inverter) 7 "INV VER" PrintableString 5 ROM number
Firmware version (option) 7 "OPT VER" PrintableString 5 ROM number

Arrangement of transfer syntax data (coded)
30 81AA Identifier Length Description
30 6F Identifier Length Description
13 02 "ID"
13 07 "SYSPARA"
13 03 "REV"
13 07 "REVDATE"
30 0A Identifier Length Description
02 01 0A
02 01 1F
13 0A "DVCATEGORY"
13 03 "INV"
13 06 "VENDOR"
13 0A "MELCO "
13 07 "DVMODEL"
13 0A "FR-A7NF "
30 39 Identifier Length Description
13 07 "DEVPARA"
13 0A "MACADDRESS"
02 06 (6-byte data)
13 05 (5-byte data)
13 05 (5-byte data)
∗Identifier 13 indicates PrintableString type, identifier 02 indicates INTEGER type.
Perform communication test of device by returning message data received.
Offset Bit15 to Bit0 +0
: Any data up to 1024 bytes.
Offset Bit15 to Bit0 +0
: Same data as request data is sent.


This chapter explains the "PARAMETERS" for use of this
product.
Always read the instructions before using the equipment.
The following marks are used to indicate the controls as below.
......V/F control
......Advanced magnetic flux vector control
AD MFVC AD MFVC AD MFVC
General-purpose magnetic flux vector control (Parameters without any mark are valid for all controls.)

5.1 Operation panel
5.1.1 Names and functions of the operation panel
The operation panel cannot be removed from the inverter.
Operating status indicator Lit or flicker during inverter operation. ∗
Operation mode indicator PU: Lit to indicate PU operation mode. EXT: Not lit. NET: Lit to indicate Network operation
being performed.
mode. (Lit at power-ON at initial setting.)
∗Slow flickering (1.4s cycle):
When the reverse rotation operation is
being performed.
Unit indicator Hz: Lit to indicate frequency.
∗Fast flickering (0.2s cycle):
(Flickers when the set frequency monitor is displayed.) A: Lit to indicate current. (Both "Hz" and "A" turn OFF when other than the above is displayed.)
When was pressed or the start
command was given, but the operation
cannot be made.
yWhen the frequency command is less
than the starting frequency. yWhen the MRS signal is input.
Monitor (4-digit LED) Shows the frequency, parameter number, etc.
Parameter setting mode Lit to indicate parameter setting mode.
Setting dial (Setting dial: Mitsubishi inverter dial) Used to change the frequency setting and parameter settings. Press to display the following. y Displays the set frequency in the
Monitor indicator Lit to indicate monitoring mode.
Stop operation Used to stop Run command. Fault can be reset when protective function is activated (fault).
monitor mode y Displays the order in the faults history
Operation mode switchover Used to switch between the NET and PU operation modes. Cancels PU stop also. (Refer to page 165.)
Mode switchover Used to change each setting mode. Pressing for a while (2s) can lock operation. (Refer to page 183)
Start command The rotation direction can be selected by setting Pr. 40.
Determination of each setting If pressed during operation, monitor changes as below:

5.1.2 Basic operation (factory setting)

∗Switching from the Network operation mode to the PU and PU JOG operation modes using is available when "1" is set in the X12 signal (Bit11), which
gives a control input signal through FL remote communication. (Refer to page 57.)
Setting "0" in the X12 signal (Bit11) forces PU and PU JOG operation modes to change to Network operation mode.

5.1.3 Changing the parameter setting value
Changing example Change the Pr. 1 Maximum frequency setting.
The inverter starts up in the Network operation
mode.
The monitor display appears. 2. Change the X12 signal (Bit11) setting to "1."
X12 signal (Bit11) gives a control input
command through FL remote communication. 3. Press to choose the PU operation mode.
PU indicator is lit.
PRM indicator is lit.
mode.
(The parameter number read previously appears.)

" "(120.0Hz (initial value)) appears.
" " (60.00Hz). 8. Press to set.
y Turn to read another parameter.
y Press to show the setting again.
y Press twice to show the next parameter.
y Press twice to return the monitor to frequency monitor.

is displayed...Why?
appears Write error during operation
y The number of digits displayed on the operation panel is four. Only the upper four digits of values can be displayed and set. If the
values to be displayed have five digits or more including decimal places, the fifth or later numerals can not be displayed nor set.
When 120Hz is set, 120.0 is displayed and second decimal place is not displayed nor set.

5.1.4 Setting dial push
Push the setting dial ( ) to display the set frequency* currently set.
∗Appears when PU operation mode is selected.


y "{" indicates valid and "×" indicates invalid of "control mode-based correspondence table", "parameter clear", and "all parameter clear".
0 Torque boost 0 to 30% 0.1% 6/4/3/2% ∗1 94 0 { × × { {
1 Maximum frequency 0 to 120Hz 0.01Hz 120Hz 105 1 {
2 Minimum frequency 0 to 120Hz 0.01Hz 0Hz 105 2 {
3 Base frequency 0 to 400Hz 0.01Hz 60Hz 107 3 { × × { {
4 Multi-speed setting (high speed) 0 to 400Hz 0.01Hz 60Hz 111 4 {
5 Multi-speed setting (middle speed) 0 to 400Hz 0.01Hz 30Hz 111 5 {
6 Multi-speed setting (low speed) 0 to 400Hz 0.01Hz 10Hz 111 6 {
7 Acceleration time 0 to 3600/360s 0.1/0.01s 5/10/15s ∗2 116 7 {
8 Deceleration time 0 to 3600/360s 0.1/0.01s 5/10/15s ∗2 116 8 {
10 DC injection brake operation frequency 0 to 120Hz 0.01Hz 3Hz 135 10 {
11 DC injection brake operation time 0 to 10s 0.1s 0.5s 135 11 {
12 DC injection brake operation voltage 0 to 30% 0.1% 6/4/2% ∗3 135 12 {
— 13 Starting frequency 0 to 60Hz 0.01Hz 0.5Hz 119 13 {
— 14 Load pattern selection 0 to 3 1 0 109 14 { × × { {
15 Jog frequency 0 to 400Hz 0.01Hz 5Hz 171 15 {
16 Jog acceleration/deceleration time 0 to 3600/360s 0.1/0.01s 0.5s 171 16 {
— 17 MRS input selection 0, 2, 4 1 0 143 17 {
— 18 High speed maximum frequency 120 to 400Hz 0.01Hz 120Hz 105 18 {
— 19 Base frequency voltage 0 to 1000V, 8888, 9999 0.1V 9999 107 19 { × × { {
frequency 1 to 400Hz 0.01Hz 60Hz 116 20 {
increments 0, 1 1 0 116 21 {
22 Stall prevention operation level 0 to 200% 0.1% 150% 101 22 {
compensation factor at double speed 0 to 200%, 9999 0.1% 9999 101 23 {
24 Multi-speed setting (speed 4) 0 to 400Hz, 9999 0.01Hz 9999 111 24 {
25 Multi-speed setting (speed 5) 0 to 400Hz, 9999 0.01Hz 9999 111 25 {
26 Multi-speed setting (speed 6) 0 to 400Hz, 9999 0.01Hz 9999 111 26 {
27 Multi-speed setting (speed 7) 0 to 400Hz, 9999 0.01Hz 9999 111 27 {
selection 0, 1, 2 1 0 120 29 {
For simple variable-speed operation of the inverter, the initial setting of the parameters may be used as they are. Set the
necessary parameters to meet the load and operational specifications. Parameter setting, change and check are available
y The parameters surrounded by a black border in the table allow its setting to be changed during operation even if "0" (initial
value) is set in Pr. 77 Parameter write selection. (Note that the Pr.77 setting cannot be changed through FL remote
Page
to
Initial
Value
tion Parameter Name Setting Range Minimum
Increments
Setting
9 Electronic thermal O/L relay 0 to 500A 0.01A
from the operation panel. For details of parameters, refer to the instruction manual.
y indicates simple mode parameters. (initially set to extended mode)
— 29 Acceleration/deceleration pattern
23 Stall prevention operation level
communication.)
JOG


31 Frequency jump 1A 0 to 400Hz, 9999 0.01Hz 9999 106 31 {
32 Frequency jump 1B 0 to 400Hz, 9999 0.01Hz 9999 106 32 {
33 Frequency jump 2A 0 to 400Hz, 9999 0.01Hz 9999 106 33 {
34 Frequency jump 2B 0 to 400Hz, 9999 0.01Hz 9999 106 34 {
35 Frequency jump 3A 0 to 400Hz, 9999 0.01Hz 9999 106 35 {
36 Frequency jump 3B 0 to 400Hz, 9999 0.01Hz 9999 106 36 {
— 37 Speed display 0, 0.01 to 9998 0.001 0 146 37 {
— 40 RUN key rotation direction selection 0, 1 1 0 182 40 {
41 Up-to-frequency sensitivity 0 to 100% 0.1% 10% 144 41 {
42 Output frequency detection 0 to 400Hz 0.01Hz 6Hz 144 42 {
rotation 0 to 400Hz, 9999 0.01Hz 9999 144 43 {
44 Second acceleration/deceleration time 0 to 3600/360s 0.1/0.01s 5/10/15s ∗2 116 44 {
45 Second deceleration time 0 to 3600/360s, 9999 0.1/0.01s 9999 116 45 {
46 Second torque boost 0 to 30%, 9999 0.1% 9999 94 46 { × × { {
47 Second V/F (base frequency) 0 to 400Hz, 9999 0.01Hz 9999 107 47 { × × { {
current 0 to 200%, 9999 0.1% 9999 101 48 {
51 Second electronic thermal O/L relay 0 to 500A, 9999 0.01A 9999 123 51 {
— 52 DU/PU main display data selection 0, 5, 7 to 12, 14, 20, 23 to 25, 52 to 57, 61, 62, 100 1 0 147 52 {
57 Restart coasting time 0, 0.1 to 5s, 9999 0.1s 9999 151 57 {
58 Restart cushion time 0 to 60s 0.1s 1s 151 58 {
— 59 Remote function selection 0, 1, 2, 3 1 0 113 59 {
— 60 Energy saving control selection 0, 9 1 0 162 60 { × × { {
61 Reference current 0 to 500A, 9999 0.01A 9999 121 61 {
62 Reference value at acceleration 0 to 200%, 9999 1% 9999 121 62 {
63 Reference value at deceleration 0 to 200%, 9999 1% 9999 121 63 {
— 65 Retry selection 0 to 5 1 0 158 65 {
starting frequency 0 to 400Hz 0.01Hz 60Hz 101 66 {
67 Number of retries at fault occurrence 0 to 10, 101 to 110 1 0 158 67 {
68 Retry waiting time 0.1 to 360s 0.1s 1s 158 68 {
69 Retry count display erase 0 1 0 158 69 {
— 70 Special regenerative brake duty 0 to 30% 0.1% 0% 136 70 {
— 72 PWM frequency selection 0 to 15 1 1 163 72 {
— 77∗6 Parameter write selection 0, 1, 2 1 0 166 77 {
— 78 Reverse rotation prevention selection 0, 1, 2 1 0 167 78 {
— 73 Parameter for manufacturer setting. Do not set. 73 Parameter for manufacturer setting. Do not set. — 74 74 — 75 Reset selection/PU stop selection 0 to 3, 14 to 17 1 14 165 75 { { { × ×
— 54 Parameter for manufacturer setting. Do not set. 54 Parameter for manufacturer setting. Do not set. — 55 55 — 56 56
— 79 Parameter for manufacturer setting. Do not set. 79 Parameter for manufacturer setting. Do not set.
Page
95, 98,
— 30 Regenerative function selection 0, 1, 2 1 0 136,
Value
— 71 Applied motor 0, 1, 3 to 6, 13 to 16, 23, 24, 40, 43, 44, 50, 53, 54 1 0
Increments
Setting
43 Output frequency detection for reverse
— 66 Stall prevention operation reduction
48 Second stall prevention operation


82 Motor excitation current 0 to 500A (0 to ****), 9999 ∗5 0.01A (1) ∗5 9999 127 82 × { { × {
84 Rated motor frequency 10 to 120Hz 0.01Hz 60Hz 127 84 × {
magnetic flux vector) 0 to 200%, 9999 0.1% 9999 95 89 × { × × {
9999 ∗5 0.001Ω (1) ∗5 9999 127 90 { { { × {
9999 ∗5 0.001Ω (1) ∗5 9999 127 91 × { { × {
(0.001Ω, 1) ∗5 9999 127 92 × { { × {
(0.001Ω, 1) ∗5 9999 127 93 × { { × {
(0.01Ω, 1) ∗5 9999 127 94 × { { × {
switching frequency 0 to 400Hz, 9999 0.01Hz 9999 116 147 {
150 Output current detection level 0 to 200% 0.1% 150% 145 150 {
time 0 to 10s 0.1s 0s 145 151 {
152 Zero current detection level 0 to 200% 0.1% 5% 145 152 {
153 Zero current detection time 0 to 1s 0.01s 0.5s 145 153 {
— 156 Stall prevention operation selection 0 to 31, 100, 101 1 0 101 156 {
— 157 OL signal output timer 0 to 25s, 9999 0.1s 0s 101 157 {
— 160 User group read selection 0, 1, 9999 1 0 167 160 {
selection 0, 1, 10, 11 1 0 183 161 { { { × {
— 118 118 — 119 119 — 120 120 — 121 121 — 122 122 — 123 123 — 124 124 — 125 125 — 126 126 — 127 127 — 128 128 — 129 129 — 130 130 — 131 131 — 132 132 — 133 133 — 134 134 — 145 145 — 146 146
Page
93, 95,
93, 95,
96 Auto tuning setting/status 0, 1, 11, 21 1 0 127,
83 Rated motor voltage 0 to 1000V 0.1V 200V/400V
Value
80 Motor capacity 0.1 to 15kW, 9999 0.01kW 9999
81 Number of motor poles 2, 4, 6, 8, 10, 9999 1 9999
Increments
Setting
92 Motor constant (L1) 0 to 1000mH (0 to 50Ω, 0 to ****), 9999 ∗5 0.1mH
93 Motor constant (L2) 0 to 1000mH (0 to 50Ω, 0 to ****) , 9999 ∗5 0.1mH
94 Motor constant (X) 0 to 100% (0 to 500Ω, 0 to ****) , 9999 ∗5 0.1%
90 Motor constant (R1) 0 to 50Ω (0 to ****) ,
91 Motor constant (R2) 0 to 50Ω (0 to ****) ,
Parameter for manufacturer setting. Do not set.
151 Output current detection signal delay
— 161 Frequency setting/key lock operation
89 Speed control gain (Advanced
— 147 Acceleration/deceleration time


power failure selection 0, 1, 10, 11 1 1 151 162 {
restart 0 to 200% 0.1% 150% 151 165 {
170 Watt-hour meter clear 0, 10, 9999 1 9999 147 170 { { { × {
— 179 179 — 180 180 — 181 181 — 182 182 — 183 183 — 184 184 — 190 190 — 191 191 — 192 192 — 232 232 — 233 233 — 234 234 — 235 235 — 236 236 — 237 237 — 238 238 — 239 239 — 240 Soft-PWM operation selection 0, 1 1 1 163 240 {
— 244 Cooling fan operation selection 0, 1 1 1 176 244 {
245 Rated slip 0 to 50%, 9999 0.01% 9999 100 245 { × { { {
246 Slip compensation time constant 0.01 to 10s 0.01s 0.5s 100 246 { × { { {
compensation selection 0, 9999 1 9999 100 247 { × { { {
— 249 Earth (ground) fault detection at start 0, 1 1 0 160 249 {
0.1s 9999 138 250 {
— 251 Output phase loss protection selection 0, 1 1 1 160 251 {
259 Main circuit capacitor life measuring 0, 1 (2, 3, 8, 9) 1 0 177 259 {
261 Power failure stop selection 0, 1, 2 1 0 156 261 {
— 268 Monitor decimal digits selection 0, 1, 9999 1 9999 147 268 {
— 270 Stop-on contact control selection 0, 1 1 0 139 270 × {
171 Operation hour meter clear 0, 9999 1 9999 147 171 { { { × ×
clear 9999, (0 to 16) 1 0 167 172 { { { × ×
173 User group registration 0 to 999, 9999 1 9999 167 173 { { { × ×
174 User group clear 0 to 999, 9999 1 9999 167 174 { { { × ×
255 Life alarm status display (0 to 15) 1 0 177 255 { { { × ×
256 Inrush current limit circuit life display (0 to 100%) 1% 100% 177 256 { { { × ×
257 Control circuit capacitor life display (0 to 100%) 1% 100% 177 257 { { { × ×
258 Main circuit capacitor life display (0 to 100%) 1% 100% 177 258 { { { × ×
— 168 Parameter for manufacturer setting. Do not set. 168 Parameter for manufacturer setting. Do not set. — 169 169
— 241 Parameter for manufacturer setting. Do not set. 241 Parameter for manufacturer setting. Do not set.
— 267 Parameter for manufacturer setting. Do not set. 267 Parameter for manufacturer setting. Do not set.
— 269 Parameter for manufacturer setting. Do not set. 269 Parameter for manufacturer setting. Do not set.
Page
to
Initial
Value
tion Parameter Name Setting Range Minimum
Increments
Setting
Parameter for manufacturer setting. Do not set.
162 Automatic restart after instantaneous
172 User group registered display/batch
165 Stall prevention operation level for
247 Constant-power range slip
— 250 Stop selection


speed multiplying factor 0 to 300%, 9999 0.1% 9999 139 275 × {
contact 0 to 9, 9999 1 9999 139 276 × {
switchover 0, 1 1 0 101 277 {
286 Droop gain 0 to 100% 0.1% 0% 173 286 × { × { {
287 Droop filter time constant 0 to 1s 0.01s 0.3s 173 287 × { × { {
— 292 Automatic acceleration/deceleration 0, 1, 7, 8, 11 1 0 121 292 {
selection 0 to 2 1 0 121 293 {
— 295 Magnitude of frequency change setting 0, 0.01, 0.1, 1, 10 0.01 0 185 295 {
199, 9999 1 9999 169 296 { { { × {
9999 1 9999 169 297 { { { × {
— 298 Frequency search gain 0 to 32767, 9999 1 9999 151 298 { { { × {
at restarting 0, 1, 9999 1 0 151 299 {
450 Second applied motor 0, 1, 9999 1 9999 125 450 {
display 0 1 0 161 501 {
time 0 to 9998, 9999 1 9999 180 504 { { { × {
— 571 Holding time at a start 0 to 10s, 9999 0.1s 9999 119 571 {
— 611 Acceleration time at a restart 0 to 3600s, 9999 0.1s 9999 151 611 {
503 Maintenance timer 0 (1 to 9998) 1 0 180 503 { { { × ×
— 548 548 — 549 549 — 550 550 — 551 551 — 555 555 — 556 556 — 557 557 — 563 Energization time carrying-over times (0 to 65535) 1 0 147 563 { { { × ×
— 564 Operating time carrying-over times (0 to 65535) 1 0 147 564 { { { × ×
Parameter for manufacturer setting. Do not set. — 339 339 — 340 340 — 342 342 — 343 343
Parameter for manufacturer setting. Do not set. — 496 496 — 497 497 — 500 500
— 502 Parameter for manufacturer setting. Do not set. 502 Parameter for manufacturer setting. Do not set.
— 279 279 — 280 280 — 281 281 — 282 282 — 283 283
Page
to
Initial
Value
tion Parameter Name Setting Range Minimum
Increments
Setting
296 Password lock level 0 to 6, 99, 100 to 106,
297 Password lock/unlock (0 to 5), 1000 to 9998,
Parameter for manufacturer setting. Do not set.
Parameter for manufacturer setting. Do not set.
Parameter for manufacturer setting. Do not set.
Parameter for manufacturer setting. Do not set.
— 501 Communication error occurrence count
275 Stop-on contact excitation current low-
— 299 Rotation direction detection selection
— 293 Acceleration/deceleration separate
504 Maintenance timer alarm output set
276 PWM carrier frequency at stop-on
— 277 Stall prevention operation current


— 653 Speed smoothing control 0 to 200% 0.1% 0 164 653 {
gain 0 to 200% 0.1% 100 174 665 {
— 859 Torque current 0 to 500A (0 to ****) , 9999 ∗5 0.01A (1) ∗5 9999 127 859 × { { × {
872 Input phase loss protection selection 0, 1 1 1 160 872 {
selection 0, 1, 2 1 0 174 882 {
780VDC ∗4 174 883 {
frequency limit value 0 to 10Hz, 9999 0.01Hz 6Hz 174 885 {
886 Regeneration avoidance voltage gain 0 to 200% 0.1% 100% 174 886 {
Pr.CL Parameter clear 0, 1 1 0 186 Pr.CL —
ALLC All parameter clear 0, 1 1 0 186 ALLC —
Er.CL Faults history clear 0, 1 1 0 188 Er.CL —
Pr.CH Initial value change list — — — 187 Pr.CH —
888 Free parameter 1 0 to 9999 1 9999 181 888 { { { × ×
889 Free parameter 2 0 to 9999 1 9999 181 889 { { { × ×
— C3 C3
— C4 C4
— C5 C5
— C6 C6
— C7 C7
— C22 C22
— C23 C23
— C24 C24
— C25 C25
— 990 990 — 991 991
Page
— 800 Control method selection 20, 30 1 20 93, 95,
Initial
Value
level 300 to 800V 0.1V 400VDC/
Increments
Setting
6%: 0.1K, 0.2K 4%: 0.4K to 7.5K 2%: 11K, 15K ∗4 The initial value differs according to the voltage class. (200V class/400V class)
Parameter for manufacturer setting. Do not set.
∗6 The setting cannot be changed through FL remote communication.
885 Regeneration avoidance compensation
— 665 Regeneration avoidance frequency
882 Regeneration avoidance operation
883 Regeneration avoidance operation
∗5 The range differs according to the Pr. 71 setting.
6%: 0.75K or lower 4%: 1.5K to 3.7K 3%: 5.5K, 7.5K 2%: 11K, 15K ∗2 Differ according to capacities.
∗1 Differ according to capacities.
5s: 3.7K or lower 10s: 5.5K, 7.5K 15s: 11K, 15K ∗3 Differ according to capacities.
Initial value change list

5.3.1 Changing the control method (Pr. 80, Pr. 81, Pr. 800) 93
5.4.1 Manual torque boost (Pr. 0, Pr. 46) 94 5.4.2 Advanced magnetic flux vector control (Pr. 71, Pr. 80, Pr. 81, Pr.89, Pr. 800) 95 5.4.3 General-purpose magnetic flux vector control (Pr. 71, Pr. 80, Pr. 81, Pr. 800) 98 5.4.4 Slip compensation (Pr. 245 to Pr. 247) 100 5.4.5 Stall prevention operation (Pr. 22, Pr. 23, Pr. 48, Pr. 66, Pr. 156, Pr. 157, Pr. 277) 101
5.5.1 Maximum/minimum frequency (Pr. 1, Pr. 2, Pr. 18) 105 5.5.2 Avoiding mechanical resonance points (frequency jumps) (Pr. 31 to Pr. 36) 106
5.6.1 Base frequency, voltage (Pr. 3, Pr. 19, Pr. 47) 107 5.6.2 Load pattern selection (Pr. 14) 109
5.7.1 Operation by multi-speed operation (Pr. 4 to Pr. 6, Pr. 24 to Pr. 27) 111 5.7.2 Remote setting function (Pr. 59) 113
5.8.1 Setting of the acceleration and deceleration time (Pr. 7, Pr. 8, Pr. 20, Pr. 21, Pr. 44, Pr. 45, Pr. 147) 116 5.8.2 Starting frequency and start-time hold function (Pr. 13, Pr. 571) 119 5.8.3 Acceleration/deceleration pattern (Pr. 29) 120 5.8.4 Shortest acceleration/deceleration (automatic acceleration/deceleration) (Pr. 61 to Pr. 63, Pr. 292, Pr. 293) 121
5.9.1 Motor overheat protection (Electronic thermal O/L relay) (Pr. 9, Pr. 51) 123 5.9.2 Applied motor (Pr. 71, Pr. 450) 125 5.9.3 Exhibiting the best performance for the motor (offline auto tuning) (Pr. 71, Pr. 80 to Pr. 84, Pr. 90 to Pr. 94, Pr. 96, Pr. 859) 127
5.10.1 DC injection brake (Pr. 10 to Pr. 12) 135 5.10.2 Selection of a regenerative brake (Pr. 30, Pr. 70) 136 5.10.3 Stop selection (Pr. 250) 138 5.10.4 Stop-on contact control function (Pr. 6, Pr. 48, Pr. 270, Pr. 275, Pr. 276) 139
5.11.1 Operation of start signals (STF, STR signal) 141 5.11.2 Reset cancel signal (READY signal) and inverter running signal (RUN signal) 142 5.11.3 Second function selection signal (RT signal) 143 5.11.4 Inverter output shutoff signal (MRS signal, Pr. 17) 143 5.11.5 Detection of output frequency (SU, FU signal, Pr. 41 to Pr. 43) 144 5.11.6 Output current detection function (Y12 signal, Y13 signal, Pr. 150 to Pr. 153) 145

5.12.1 Speed display and speed setting (Pr. 37) 146 5.12.2 Monitor display selection of the operation panel (Pr. 52, Pr. 170, Pr. 171, Pr. 268, Pr. 563, Pr. 564) 147
5.13.1 Automatic restart after instantaneous power failure/flying start (Pr. 57, Pr. 58, Pr. 96, Pr. 162, Pr. 165, Pr. 298, Pr. 299, Pr. 611) 151 5.13.2 Power-failure deceleration stop function (Pr. 261) 156
5.14.1 Retry function (Pr. 65, Pr. 67 to Pr. 69) 158 5.14.2 Input/output phase loss protection selection (Pr. 251, Pr. 872) 160 5.14.3 Earth (ground) fault detection at start (Pr. 249) 160 5.14.4 Display and erasure of communication error occurrence count (Pr. 501) 161
5.15 Energy saving operation 162
5.15.1 Optimum excitation control (Pr. 60) 162
5.16.1 PWM carrier frequency and soft-PWM control (Pr. 72, Pr. 240) 163 5.16.2 Speed smoothing control (Pr. 653) 164
5.17.1 Reset selection/PU stop selection (Pr. 75) 165 5.17.2 Parameter write disable selection (Pr. 77) 166 5.17.3 Reverse rotation prevention selection (Pr. 78) 167 5.17.4 Extended parameter display and user group function (Pr. 160, Pr. 172 to Pr. 174) 167 5.17.5 Password function (Pr. 296, Pr. 297) 169
5.18.1 Jog operation (Pr. 15, Pr. 16) 171 5.18.2 Droop control (Pr. 286, Pr. 287) 173 5.18.3 Regeneration avoidance function (Pr. 665, Pr. 882, Pr. 883, Pr. 885, Pr. 886) 174
5.19.1 Cooling fan operation selection (Pr. 244) 176 5.19.2 Display of the life of the inverter parts (Pr. 255 to Pr. 259) 177 5.19.3 Maintenance timer alarm (Pr. 503, Pr. 504) 180 5.19.4 Free parameter (Pr. 888, Pr. 889) 181
5.20 Setting from the operation panel 182
5.20.1 RUN key rotation direction selection (Pr. 40) 182 5.20.2 Operation panel frequency setting/key lock operation selection (Pr. 161) 183 5.20.3 Magnitude of frequency change setting (Pr. 295) 185
5.22 Initial value change list 187
5.23 Check and clear of the faults history 188

5.3 Control mode
V/F control (initial setting), Advanced magnetic flux vector control and General-purpose magnetic flux vector control are
available with this inverter.
yIt controls frequency and voltage so that the ratio of frequency (F) to voltage (V) is constant when changing frequency.
yThis control divides the inverter output current into an excitation current and a torque current by vector calculation and
makes voltage compensation to flow a motor current which meets the load torque. yGeneral-purpose magnetic flux vector control is the same function as the FR-E500 series. For other cases, select
Advanced magnetic flux vector control.
POINT If the following conditions are not satisfied, select V/F control since malfunction such as insufficient torque and uneven rotation may occur.
y The motor capacity should be equal to or one rank lower than the inverter capacity. (Note that the capacity
should be 0.1kW or higher.)
y Motor to be used is any of Mitsubishi standard motor, high efficiency motor (SF-JR, SF-HR 0.2kW or higher) or
Mitsubishi constant-torque motor (SF-JRCA four-pole, SF-HRCA 0.2kW to 15kW). When using a motor other
than the above (other manufacturer's motor), perform offline auto tuning without fail.
y Single-motor operation (one motor run by one inverter) should be performed.
y Wiring length from inverter to motor should be within 30m. (Perform offline auto tuning in the state where wiring
work is performed when the wiring length exceeds 30m.)

5.3.1 Changing the control method (Pr. 80, Pr. 81, Pr. 800)

Set when selecting the control method for Advanced magnetic flux vector control and General-purpose magnetic flux vector control. The initial value is V/F control.
zSelect a control mode using Pr. 800 Control method selection.
80 Motor capacity 9999 0.1 to 15kW Set the applied motor capacity. 9999 V/F Control
81 Number of motor poles 9999 2, 4, 6, 8, 10 Set the number of motor poles. 9999 V/F Control
∗Set a value other than "9999" in Pr. 80 and Pr. 81.
(1) Setting of the motor capacity and the number of motor poles (Pr. 80, Pr. 81)
yMotor specifications (motor capacity and number of motor poles) must be set to select Advanced magnetic flux vector
control or General-purpose magnetic flux vector control. ySet the motor capacity (kW) in Pr. 80 Motor capacity and set the number of motor poles in Pr. 81 Number of motor poles.
ySelect the inverter control method for V/F control, Advanced magnetic flux vector control, and General-purpose magnetic
flux vector control.

(Pr. 800 initial value) Advanced magnetic flux vector control
(Pr. 80, Pr. 81 initial value) — ∗ V/F control
∗Control method is V/F control regardless of the setting value of Pr. 800 when "9999" is set in Pr. 80 Motor capacity or Pr. 81 Number of motor poles.
Advanced magnetic flux vector control Refer to page 95 General-purpose magnetic flux vector control Refer to page 98 Pr. 450 Second applied motor Refer to page 125 Pr. 44 Second acceleration/deceleration time, Pr. 45 Second deceleration time Refer to page 116 Pr. 46 Second torque boost Refer to page 94 Pr. 47 Second V/F (base frequency) Refer to page 107 Pr. 48 Second stall prevention operation current Refer to page 101 Pr. 51 Second electronic thermal O/L relay Refer to page 123
Parameters referred to

5.4 Adjustment of the output torque (current) of the motor
Purpose Parameter that should be Set Refer to Page Set starting torque manually Manual torque boost Pr. 0, Pr. 46 94
Automatically control output current according to load
Pr. 71, Pr. 80, Pr. 81, Pr. 89,
Pr. 90, Pr. 450, Pr. 800 95, 98
Compensate for motor slip to secure low-speed torque
Pr. 245 to Pr. 247 100
Limit output current to prevent inverter trip Stall prevention operation Pr. 22, Pr. 23, Pr. 66, Pr. 156,
Pr. 157 101
A voltage drop in the low-frequency range can be compensated to improve motor torque reduction in the low-speed range. zMotor torque in the low-frequency range can be adjusted to the load to increase the starting motor torque. zTurning the RT signal ON/OFF switches between two start torque boost settings.
Number Name Initial Value Setting
0.1K to 0.75K 6%
0 to 30% Set the output voltage at 0Hz as %. 1.5K to 3.7K 4% 5.5K, 7.5K 3% 11K, 15K 2%
9999 0 to 30% Set the torque boost when the RT
signal is ON. 9999 Without second torque boost ∗The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)

yOn the assumption that Pr. 19 Base frequency voltage is 100%, set
the output voltage at 0Hz in % to Pr. 0 (Pr. 46). yAdjust the parameter little by little (about 0.5%), and check the
motor status each time. If the setting is too large, the motor will overheat. The guideline is about 10% at the greatest.
yWhen you want to change torque boost according to applications, switch multiple motors with one inverter, etc., use Second
torque boost. yPr. 46 Second torque boost is valid when the RT signal is ON.
y The RT signal acts as the second function selection signal and makes the other second functions valid. (Refer to page 143)
characteristics, load, acceleration/deceleration time, wiring length, etc., resulting in an overcurrent trip (OL (overcurrent alarm) then E.OC1 (overcurrent trip during acceleration), overload trip (E.THM (motor overload trip), or E.THT (inverter overload trip). (When a fault occurs, release the start command, and decrease the Pr. 0 setting 1% by 1% to reset.) (Refer to page 192.) y The Pr. 0, Pr. 46 settings are valid only when V/F control is selected. y When using the inverter dedicated motor (constant-torque motor) with the 5.5K, 7.5K, set torque boost value to 2%.
When Pr. 0 = "3%"(initial value), if Pr. 71 value is changed to the setting for use with a constant-torque motor, the Pr. 0 setting changes to 2%.
Pr. 3 Base frequency, Pr. 19 Base frequency voltage Refer to page 107 Pr. 71 Applied motor Refer to page 125
Parameter · Range Description · Parameters referred to

5.4.2 Advanced magnetic flux vector control (Pr. 71, Pr. 80, Pr. 81, Pr.89, Pr. 800)
Advanced magnetic flux vector control can be selected by setting the capacity, poles and type of the motor used in Pr. 80 and Pr. 81.
z Advanced magnetic flux vector control?
The low speed torque can be improved by providing voltage compensation to flow a motor current which meets the
load torque. Output frequency compensation (slip compensation) is made so that the motor actual speed approximates a speed command value. Effective when load fluctuates drastically, etc.
When the FR-E500 series used for General-purpose magnetic flux vector control was replaced, select General- purpose magnetic flux vector control only when the same operation characteristic is necessary. (Refer to page 98)
Value Setting Range Description
0,1, 3 to 6,
By selecting a standard motor or constant-torque motor,
13 to 16, 23, 24
71 Applied motor 0
thermal characteristic and motor constants of each motor
are set.
80 Motor capacity 9999 0.1 to 15kW Set the applied motor capacity.
9999 2, 4, 6, 8, 10 Set the number of motor poles.
Motor speed fluctuation due to load fluctuation is adjusted
9999 0 to 200%
during Advanced magnetic flux vector control.
100% is a referenced value.
9999 Gain matching with the motor set in Pr.71.
20 Advanced magnetic flux vector control ∗
30 General-purpose magnetic flux vector control ∗ (Refer to
The above parameters can be set when Pr. 160 User group read selection = "0".(Refer to page 167)
∗Set a value other than "9999" in Pr. 80 and Pr. 81.
POINT If the following conditions are not satisfied, select V/F control since malfunction such as insufficient torque and uneven rotation may occur.
y The motor capacity should be equal to or one rank lower than the inverter capacity. (Note that the capacity
should be 0.1kW or higher.)
y Motor to be used is any of Mitsubishi standard motor (SF-JR 0.2kW or higher), high efficiency motor (SF-HR
0.2kW or higher) or Mitsubishi constant-torque motor (SF-JRCA four-pole, SF-HRCA 0.2kW to 15kW). When
using a motor other than the above (other manufacturer's motor), perform offline auto tuning without fail. y Single-motor operation (one motor run by one inverter) should be performed.
y The wiring length from inverter to motor should be within 30m. (Perform offline auto tuning in the state where
wiring work is performed when the wiring length exceeds 30m.)
Permissible wiring length between inverter and motor differs according to the inverter capacity and setting value of Pr. 72 PWM frequency selection (carrier frequency). Refer to page 19 for the permissible wiring length.

Perform secure wiring.
(Refer to page 14)
Set the motor. (Pr. 71)
Motor Pr. 71 Setting ∗1 Remarks Mitsubishi standard motor Mitsubishi high efficiency motor
SF-JR 0 (initial value) SF-HR 40
Others 3 Offline auto tuning is necessary. ∗2
SF-JRCA 4P 1 SF-HRCA 50 Others (SF-JRC, etc.) 13 Offline auto tuning is necessary. ∗2 Other manufacturer's standard motor — 3 Offline auto tuning is necessary. ∗2
Other manufacturer's constant-torque motor
— 13 Offline auto tuning is necessary. ∗2
∗1 Refer to page 125 for other settings of Pr. 71. ∗2 Refer to page 127 for offline auto tuning.
Set the motor capacity and the number of motor poles.
(Pr. 80, Pr. 81) (Refer to page 95)
Set motor capacity (kW) in Pr. 80 Motor capacity and the number of motor poles (number of poles) in Pr. 81 Number of motor poles. (V/F control is performed when the setting is "9999" (initial value). Select the control method. (Pr. 800) (Refer to page 95)
Set "20" (initial value) in Pr. 800 to make Advanced magnetic flux vector control valid.
Set the operation command. (Refer to page 50)
Select the start command and speed command.
As required y Perform offline auto tuning. (Pr. 96) (Refer to page 127)
y Uneven rotation slightly increases as compared to the V/F control. (It is not suitable for machines such as grinding
machine and wrapping machine which requires less uneven rotation at low speed.
y When a surge voltage suppression filter (FR-ASF-H/FR-BMF-H) is connected between the inverter and motor, output
torque may decrease.)
Mitsubishi constant- torque motor · (1)Start command

(1) Adjust the motor speed fluctuation at load fluctuation (Pr. 89 Speed control gain (Advanced magnetic flux
The motor speed fluctuation at load fluctuation can be adjusted using Pr. 89. (It is useful when the speed command does not match the motor speed
after the FR-E500 series inverter is replaced with the FR-E700 series inverter, etc.)
Pr. 71, Pr. 450 Applied motor Refer to page 125 Pr. 800 Control method selection Refer to page 93
Load torque · Speed · Parameters referred to

5.4.3 General-purpose magnetic flux vector control (Pr. 71, Pr. 80, Pr. 81, Pr. 800)
General-purpose magnetic flux vector control is the same function as the FR-E500 series. Select this control when the same operation characteristic is necessary. For other cases, select Advanced magnetic
flux vector control. (Refer to page 95)
Value Setting Range Description
0,1, 3 to 6,
By selecting a standard motor or constant-torque motor,
13 to 16, 23, 24
71 Applied motor 0
thermal characteristic and motor constants of each motor
are set.
80 Motor capacity 9999 0.1 to 15kW Applied motor capacity.
9999 2, 4, 6, 8, 10 Number of motor poles.
20 20 Advanced magnetic flux vector control ∗ (Refer to page 95)
30 General-purpose magnetic flux vector control ∗
The above parameters can be set when Pr. 160 User group read selection = "0".(Refer to page 167)
∗Set a value other than "9999" in Pr. 80 and Pr. 81.
POINT If the following conditions are not satisfied, select V/F control since malfunction such as insufficient torque and
uneven rotation may occur. y The motor capacity should be equal to or one rank lower than the inverter capacity. (note that the capacity
should be 0.1kW or higher) y Motor to be used is any of Mitsubishi standard motor (SF-JR 0.2kW or higher), high efficiency motor (SF-JR,
SF-HR 0.2kW or higher) or Mitsubishi constant-torque motor (SF-JRCA four-pole, SF-HRCA 0.2kW to 15kW). When using a motor other than the above (other manufacturer's motor), perform offline auto tuning without fail.
y Single-motor operation (one motor run by one inverter) should be performed. y The wiring length from inverter to motor should be within 30m. (Perform offline auto tuning in the state where
wiring work is performed when the wiring length exceeds 30m.) Permissible wiring length between inverter and motor differs according to the inverter capacity and setting value
of Pr. 72 PWM frequency selection (carrier frequency). Refer to page 19 for the permissible wiring length.

Perform secure wiring.
(Refer to page 14)
Set the motor.(Pr. 71)
Motor Pr. 71 Setting ∗1 Remarks Mitsubishi standard motor Mitsubishi high efficiency motor
SF-JR 0 (initial value) SF-HR 40
Others 3 Offline auto tuning is necessary. ∗2
SF-JRCA 4P 1 SF-HRCA 50 Others (SF-JRC, etc.) 13 Offline auto tuning is necessary. ∗2 Other manufacturer's standard motor — 3 Offline auto tuning is necessary. ∗2
Other manufacturer's constant-torque motor
— 13 Offline auto tuning is necessary. ∗2
∗1 Refer to page 125 for other settings of Pr. 71. ∗2 Refer to page 127 for offline auto tuning.
Set the motor capacity and the number of motor poles.
(Pr. 80, Pr. 81) (Refer to page 98)
Set motor capacity (kW) in Pr. 80 Motor capacity and the number of motor poles (number of poles) in Pr. 81 Number of motor poles. (V/F control is performed when the setting is "9999" (initial value).
Select the control method.(Pr. 800) (Refer to page 98)
Set "30" in Pr. 800 to make General-purpose magnetic flux vector control valid.
Set the operation command. (Refer to page 50)
Select the start command and speed command.
As required y Perform offline auto tuning. (Pr. 96) (Refer to page 127)
y Set slip compensation. (Pr. 245, Pr. 246, Pr. 247) (Refer to page 100)
y Uneven rotation slightly increases as compared to the V/F control. (It is not suitable for machines such as grinding
machine and wrapping machine which requires less uneven rotation at low speed.
y When a surge voltage suppression filter (FR-ASF-H/FR-BMF-H) is connected between the inverter and motor, output
torque may decrease.)
Pr.3 Base frequency, Pr.19 Base frequency voltage Refer to page 107 Pr.71 Applied motor Refer to page 125 Pr.77 Parameter write selection Refer to page 166
Mitsubishi constant- torque motor · (1)Start command · Parameters referred to

5.4.4 Slip compensation (Pr. 245 to Pr. 247)
GP MFVC GP MFVC GP MFVC
When V/F control or General-purpose magnetic flux vector control is performed, the inverter output current may be used to assume motor slip to keep the motor speed constant.

245 Rated slip 9999 0.01 to 50% Rated motor slip.
246 Slip compensation time constant 0.5s 0.01 to 10s
9999 Slip compensation is made in the constant power
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)
y Slip compensation is validated when the motor rated slip calculated by the following formula is set in Pr. 245. Slip
compensation is not made when Pr. 245 = "0" or "9999".
Rated slip = Synchronous speed at base frequency - rated speed × 100[%] Synchronous speed at base frequency
y When performing slip compensation, the output frequency may become greater than the set frequency. Set the Pr. 1 Maximum
frequency value a little higher than the set frequency.
y Slip compensation is always valid when Advanced magnetic flux vector control is selected, the Pr. 245 to Pr. 247 settings are
invalid.
Pr. 1 Maximum frequency Refer to page 105 Pr. 3 Base frequency Refer to page 107
Parameters referred to

5.4.5 Stall prevention operation (Pr. 22, Pr. 23, Pr. 48, Pr. 66, Pr. 156, Pr. 157, Pr. 277)
This function monitors the output current and automatically changes the output frequency to prevent the inverter from
coming to trip due to overcurrent, overvoltage, etc. In addition, simple torque limit which limits the output torque to the predetermined value can be selected.
It can also limit stall prevention and fast-response current limit operation during acceleration/deceleration, driving or regeneration.
If the output current exceeds the stall prevention operation level, the output frequency of the inverter is automatically varied to reduce the output current. zFast-response current limit
If the current exceeds the limit value, the output of the inverter is shut off to prevent an overcurrent. zTorque limit
The inverter output frequency is controlled so that the output torque (torque current) will not exceed the stall prevention operation level (motor rated torque is referenced).
Number Name Initial Value Setting Range Description
150% 0 Stall prevention operation invalid
0.1 to 200% Set the current value to start the stall
prevention operation.
The stall operation level can be reduced
9999 0 to 200%
when operating at a high speed above the
rated frequency.
9999 Constant according to Pr. 22.
9999 0 Stall prevention operation invalid 0.1 to 200% Second stall prevention operation level 9999 Same level as Pr. 22.
Set the frequency at which the stall
60Hz 0 to 400Hz
prevention operation level starts being
reduced.
Select whether stall prevention operation
0 0 to 31, 100, 101
and fast-response current limit operation
will be performed or not.
157 OL signal output timer 0s 0 to 25s Output start time of the OL signal output
when stall prevention is activated. 9999 Without the OL signal output
0 0 Output current is the limit level
1 Output torque (torque current) is the limit
level The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)
∗This parameter allows its setting to be changed during operation in any operation mode even if "0 (initial value) or 1" is set in Pr. 77 Parameter write selection.
PARAMETERS
RT
Pr. 22
Stall prevention operation invalid
- + Pr. 48
Stall prevention operation level
Pr. 23, Pr. 66

ySet in Pr. 22 the percentage of the output current to the rated
inverter current at which stall prevention operation will be
performed. Normally set this parameter to 150% (initial value). yStall prevention operation stops acceleration (makes
Pr. 22
deceleration) during acceleration, makes deceleration during constant speed, and stops deceleration (makes acceleration)
during deceleration. yWhen stall prevention operation is performed, the OL signal is
output.
Stall prevention operation example
y If an overload status lasts long, an inverter trip (e.g. electronic thermal O/L relay (E.THM)) may occur.
(3) A machine protection and load limit by torque limit (Pr. 277)
yWhen Pr. 277 Stall prevention current switchover = "1", torque limit can be set.
yWhen output torque (torque current) exceeds the stall prevention operation level, the output frequency is controlled to limit
the output torque. For the stall prevention operation level at this time, the motor rated torque is defined as reference.
y When driving multiple motors with one inverter, torque limit does not function properly.
y Since magnetic flux decreases in the constant output range (Pr. 3 Base frequency or more), the inverter operate with lower torque
than the stall prevention operation level.
y When torque limit is activated during regeneration, the output frequency is increased up to the maximum frequency.
y Torque limit does not function at 5Hz or less during deceleration.
y Note the following when using torque limit under V/F control.
(a) Capacity of the inverter and motor should be the same.
(b) Stall prevention operation level (torque limit level) is the rated torque reference of the motor whose capacity is equivalent to
the inverter.
(c) When Pr. 0 Torque boost setting is large, torque limit is likely to occur in the low speed range.
(d) Use the Advanced magnetic flux vector control when more appropriate torque limit is necessary.
(4) Stall prevention operation signal output and output timing adjustment (OL signal, Pr. 157)
yWhen the output current exceeds the stall prevention operation level and stall prevention is activated, the stall prevention
operation signal (OL signal) turns ON for longer than 100ms. When the output current falls to or below the stall prevention operation level, the output signal turns OFF.
yUse Pr. 157 OL signal output timer to set whether the OL signal is output immediately or after a preset period of time. yThis operation is also performed when the regeneration avoidance function or (overvoltage stall) is executed.
Pr. 157 Setting Description
Overload state (OL operation)
(initial value) Output immediately.
0.1 to 25 Output after the set time (s) has elapsed.
9999 Not output.
Pr. 157 set time(s)
y If the frequency has fallen to 1Hz by stall prevention operation and remains for 3s, a fault (E.OLT) appears to trip the
inverter output.

(5) Setting of stall prevention operation in high frequency range (Pr. 22, Pr. 23, Pr. 66)
(Pr. 22 = 150%, Pr. 23 = 100%, Pr. 66 = 60Hz)
Pr. 22
When Pr. 23 = 9999
When Pr. 23 = "9999", the stall prevention operation level is as set in Pr. 22 to 400Hz.
Stall prevention operation level as set in Pr. 23
30 22.5
0 100 60 200 150 300 400
Pr. 66 400Hz
yDuring high-speed operation above the rated motor frequency, acceleration may not be made because the motor current
does not increase. If operation is performed in a high frequency range, the current at motor lockup becomes smaller than the rated output current of the inverter, and the protective function (OL) is not executed even if the motor is at a stop.
To improve the operating characteristics of the motor in this case, the stall prevention level can be reduced in the high frequency range. This function is effective for performing operation up to the high-speed range on a centrifugal separator
etc. Normally, set 60Hz in Pr. 66 and 100% in Pr. 23. yFormula for stall prevention operation level
Stall prevention operation level in high frequency range (%) = A + B × [ Pr. 22 - A ] × [ Pr. 23 - 100 ] Pr. 22 - B 100
However, A = Pr. 66 (Hz) × Pr. 22 (%) , B = Pr. 66 (Hz) × Pr. 22 (%) Output frequency (Hz) 400Hz
yBy setting "9999" (initial value) in Pr. 23 Stall prevention operation level compensation factor at double speed, the stall
prevention operation level is constant at the Pr. 22 setting up to 400Hz. (6) Set two types stall prevention operation levels (Pr. 48)
yTurning RT signal ON makes Pr. 48 Second stall prevention operation current valid.
y The RT signal acts as the second function selection signal and makes the other second functions valid.
(Refer to page 143)

(7) Limit the stall prevention operation and fast-response current limit operation according to the operating status (Pr. 156) yRefer to the following table and select whether stall prevention operation and fast-response current limit operation will be
performed or not and the operation to be performed at OL signal output.
Pr. 156
Pr. 156
value) { 16 { z
1 z { 17 z { { { z 2 { z { { { 18 { z { { z 3 z z { { { 19 z z { { z 4 { { z { { 20 { { z { z 5 z { z { { 21 z { z { z 6 { z z { { 22 { z z { z 7 z z z { { 23 z z z { z 8 { { { z { 24 { { { z z 9 z { { z { 25 z { { z z 10 { z { z { 26 { z { z z 11 z z { z { 27 z z { z z 12 { { z z { 28 { { z z z 13 z { z z { 29 z { z z z 14 { z z z — ∗2 30 { z z z — ∗2 15 z — ∗2 31 z — ∗2
{
z {
z — ∗2
z — ∗2
∗1 When "Operation not continued for OL signal output" is selected, the fault (stopped by stall prevention) is displayed and operation stopped.
∗2 Since stall prevention is not activated, OL signal and E.OLT are not output. ∗3 The settings "100" and "101" allow operations to be performed in the driving and regeneration modes, respectively. The setting "101" disables the fast- response current limit in the driving mode. ∗4 OL signal is not output at fast-response current limit operation.
y When the load is heavy or the acceleration/deceleration time is short, stall prevention is activated and acceleration/
deceleration may not be made according to the preset acceleration/deceleration time. Set Pr. 156 and stall prevention operation level to the optimum values. y In vertical lift applications, make setting so that the fast-response current limit is not activated. Torque may not be
produced, causing a load drop due to gravity.
Do not set a small value as the stall prevention operation current. Otherwise, torque generated will reduce.
Test operation must be performed. Stall prevention operation during acceleration may increase the acceleration time. Stall prevention operation performed during constant speed may cause sudden speed changes. Stall prevention operation during deceleration may increase the deceleration time, increasing the deceleration distance.
y Pr. 3 Base frequency Refer to page 107

5.5 Limiting the output frequency

Purpose Parameter that should be Set Refer to Page Set upper limit and lower limit of output frequency
Perform operation by avoiding mechanical resonance points Frequency jump Pr. 31 to Pr. 36 106

Clamp the upper and lower limits of the output frequency.
1 Maximum frequency 120Hz 0 to 120Hz Upper limit of the output frequency. 2 Minimum frequency 0Hz 0 to 120Hz Lower limit of the output frequency.
120Hz 120 to 400Hz Set when performing the operation at 120Hz
∗The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)

y Use Pr. 1 Maximum frequency to set the maximum frequency. If the
value of the frequency command entered is higher than the setting,
the output frequency is clamped at the maximum frequency. y When you want to perform operation above 120Hz, set the upper
limit of the output frequency to Pr. 18 High speed maximum frequency. (When Pr. 18 is set, Pr. 1 automatically switches to the frequency of
Pr. 18. Also, when Pr. 1 is set, Pr. 18 is automatically changed to the frequency set in Pr. 1.
y Use Pr. 2 Minimum frequency to set the minimum frequency.
y If the set frequency is less than Pr. 2, the output frequency is clamped at Pr. 2 (will not fall below Pr. 2 ).
y When Pr. 15 Jog frequency is equal to or less than Pr. 2, the Pr. 15 setting has precedence over the Pr. 2 setting. y When stall prevention is activated to decrease the output frequency, the output frequency may drop to Pr. 2 or below.
signal will run the motor at the preset frequency according to the set acceleration time even if the command frequency is not input.
Pr. 13 Starting frequency Refer to page 119 Pr. 15 Jog frequency Refer to page 171
Parameters referred to

5.5.2 Avoiding mechanical resonance points (frequency jumps) (Pr. 31 to Pr. 36)
When avoiding resonance arisen from the natural frequency of a mechanical system, use these parameters to jump the
resonant frequencies.
Number Name Initial Value Setting Range Description
31 Frequency jump 1A 9999 0 to 400Hz, 9999
32 Frequency jump 1B 9999 0 to 400Hz, 9999 33 Frequency jump 2A 9999 0 to 400Hz, 9999 34 Frequency jump 2B 9999 0 to 400Hz, 9999 35 Frequency jump 3A 9999 0 to 400Hz, 9999 36 Frequency jump 3B 9999 0 to 400Hz, 9999
1A to 1B, 2A to 2B, 3A to 3B is frequency
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)
y Up to three areas can be set, with the jump frequencies set to
Pr. 35 Pr. 36 Frequency jump
either the top or bottom point of each area.
y The value set to 1A, 2A or 3A is a jump point and operation in
the jump zone is performed at these frequencies.
Pr. 33 Pr. 34
Pr. 31 Pr. 32
Example 1 To fix the frequency to 30Hz in the range 30Hz to 35Hz, set 35Hz in Pr. 34 and
30Hz in Pr. 33.
Example 2 To jump the frequency to 35Hz in the range 30Hz to 35Hz, set 35Hz in Pr. 33
and 30Hz in Pr. 34.
During acceleration/deceleration, the running frequency within the set area is valid.
Parameter · jumps · Set frequency (Hz)

5.6 V/F pattern
Purpose Parameter that should be Set Refer to Page
Set motor ratings Base frequency, Base frequency voltage Pr. 3, Pr. 19, Pr. 47 107
Select a V/F pattern according to applications. Load pattern selection Pr. 14 109
Used to adjust the inverter outputs (voltage, frequency) to the motor rating.
Number Name Initial Value Setting Range Description
3 Base frequency 60Hz 0 to 400Hz Rated motor frequency. (50Hz/60Hz)
0 to 1000V Base voltage.
19 ∗ Base frequency voltage 9999
8888 95% of power supply voltage
9999 Same as power supply voltage
9999 0 to 400Hz Base frequency when the RT signal is ON.
9999 Second V/F invalid
∗The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)
y When operating a standard motor, generally set the rated
frequency of the motor to Pr. 3 Base frequency. When running the
motor using commercial power supply-inverter switch-over operation, set Pr. 3 to the same value as the power supply
frequency. y If the frequency given on the motor rating plate is "50Hz" only,
Pr. 19
Output frequency (Hz) Pr. 3 Pr. 47
always set to "50Hz". Leaving the base frequency unchanged from "60Hz" may make the voltage too low and the torque insufficient. It
may result in an inverter trip due to overload. Special care must be taken when "1" (variable torque load) is set in
Pr. 14 Load pattern selection . y When using the Mitsubishi constant-torque motor, set Pr. 3 to
60Hz.
y When you want to change the base frequency when switching two types of motors with one inverter, use the Pr. 47 Second V/
F (base frequency). y Pr. 47 Second V/F (base frequency) is valid when the RT signal is ON.
PARAMETERS
y The RT signal acts as the second function selection signal and makes the other second functions valid. (Refer to page 143)
Parameter · Output voltage (V)

yUse Pr. 19 Base frequency voltage to set the base voltage (e.g. rated motor voltage). yIf the setting is less than the power supply voltage, the maximum output voltage of the inverter is as set in Pr. 19.
yPr. 19 can be utilized in the following cases.
(a) When regeneration is high (e.g. continuous regeneration)
During regeneration, the output voltage becomes higher than the reference and may cause an overcurrent trip (E.OC ) due to an increased motor current.
(b) When power supply voltage variation is large
When the power supply voltage exceeds the rated voltage of the motor, speed variation or motor overheat may be
caused by excessive torque or increased motor current.
y When Advanced magnetic flux vector control or General-purpose magnetic flux vector control is selected, Pr. 3, Pr. 47
and Pr. 19 are invalid and Pr. 83 and Pr. 84 are valid.
selection = "1" (S-pattern acceleration/deceleration A).
Pr. 14 Load pattern selection Refer to page 109 Pr. 29 Acceleration/deceleration pattern selection Refer to page 120 Pr. 83 Rated motor voltage, Pr. 84 Rated motor frequency Refer to page 127 General-purpose magnetic flux vector control Refer to page 98 Advanced magnetic flux vector control Refer to page 95
Parameters referred to

5.6.2 Load pattern selection (Pr. 14)
You can select the optimum output characteristic (V/F characteristic) for the application and load characteristics.
Number Name Initial Value Setting Range Description
0 For constant-torque load
1 For variable torque load
2 For constant-torque elevators
14 Load pattern selection 0
(at reverse rotation boost of 0%)
3 For constant-torque elevators
(at forward rotation boost of 0%)
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)
Pr. 14 = 0
y At or less than the base frequency, the output voltage varies linearly with the output
frequency. y Set this value when driving the load whose load torque is constant even if the speed
varies, e.g. conveyor, cart or roll drive.
Pr. 3 Base frequency Output frequency (Hz)
If the load is a fan or pump, select for constant-torque load (setting "0") in any of the following cases.
y When a blower of large inertia moment (J) is accelerated in a short time
y For constant-torque load such as rotary pump or gear pump
y When load torque increases at low speed, e.g. screw pump
Pr. 14 = 1
y At or less than the base frequency, the output voltage varies with the output frequency
in a square curve.
y Set this value when driving the load whose load torque varies in proportion to the
square of the speed, e.g. fan or pump.
Pr. 3 Base frequency Output frequency (Hz)
Pr. 14 = 2
Pr. 14 = 3
For vertical lift loads At forward rotation boost...Pr. 0 (Pr. 46) setting At reverse rotation boost...0%
For vertical lift loads At forward rotation boost...0% At reverse rotation boost...Pr. 0 (Pr. 46) setting
y Set "2" when a vertical lift load is fixed as power
driving load at forward rotation and regenerative load at reverse rotation.
y Pr. 0 Torque boost is valid during forward rotation
and torque boost is automatically changed to
"0%" during reverse rotation. Pr. 46 Second torque boost is valid when the RT signal turns
Pr. 0 Pr. 46
Pr. 0 Pr. 46
ON. y Set "3" for an elevated load that is in the driving
Base frequency Output frequency (Hz)
Base frequency Output frequency (Hz)
mode during reverse rotation and in the regenerative load mode during forward rotation
according to the load weight, e.g. counterweight system.

y When torque is continuously regenerated as vertical lift load, it is effective to set the rated voltage in Pr. 19 Base frequency voltage
to prevent trip due to current at regeneration.
y In addition, when the RT signal is ON, the other second functions are also valid.
y Load pattern selection does not function under Advanced magnetic flux vector control and General-purpose
magnetic flux vector control.
Pr. 0, Pr. 46 (Torque boost) Refer to page 94 Pr. 3 Base frequency Refer to page 107 General-purpose magnetic flux vector control Refer to page 98 Advanced magnetic flux vector control Refer to page 95
Parameters referred to

5.7 Frequency setting by input signals

Purpose Parameter that should be Set Refer to Page Make frequency setting by combination of input signals Multi-speed operation Pr. 4 to Pr. 6, Pr. 24 to Pr. 27 111
Infinitely variable speed setting by input signals Remote setting function Pr. 59 113
5.7.1 Operation by multi-speed operation (Pr. 4 to Pr. 6, Pr. 24 to Pr. 27)
Use these parameters to change the speed to pre-set speeds using the RH, RM and RL signals. Speeds can be pre-set using parameters.

A pre-set speed can be selected by simply turning ON/OFF the RH, RM and RL signals.
60Hz 0 to 400Hz Frequency when RH turns ON
30Hz 0 to 400Hz Frequency when RM turns ON
10Hz 0 to 400Hz Frequency when RL turns ON
24 ∗ Multi-speed setting (speed 4) 9999 0 to 400Hz, 9999 Frequency from speed 4 to speed 7 can
25 ∗ Multi-speed setting (speed 5) 9999 0 to 400Hz, 9999
26 ∗ Multi-speed setting (speed 6) 9999 0 to 400Hz, 9999
27 ∗ Multi-speed setting (speed 7) 9999 0 to 400Hz, 9999
The above parameters allow their settings to be changed during operation in any operation mode even if "0" (initial value) is set in Pr. 77 Parameter write selection.
∗These parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)

yThe inverter operates at frequencies set in Pr. 4 when RH signal is ON,
Pr. 5 when RM signal is ON and Pr. 6 when RL signal is ON.
y For multi-speed setting, if two or three speeds are simultaneously selected, priority is given to the set frequency of the lower signal.
For example, when the RH and RM signals turn ON, the RM signal (Pr. 5) has a higher priority.

(2) Multi-speed setting for 4 or more speeds (Pr. 24 to Pr. 27)

yFrequency from speed 4 to speed 7 can be set according to the
combination of the RH, RM and RL signals. Set the running frequencies
in Pr. 24 to Pr. 27 (In the initial value setting, speed 4 to speed 7 are invalid).
y Multi-speed setting using parameters is available even during PU operation.
y Pr. 24 to Pr. 27 settings have no priority among them.
y When Pr. 59 Remote function selection ≠ "0", multi-speed setting is invalid as RH, RM and RL signals are remote setting signals.
Pr. 59 Remote function selection Refer to page 113
Parameters referred to

5.7.2 Remote setting function (Pr. 59)
zContinuous variable-speed operation can be performed using acceleration and deceleration signals. zBy simply setting this parameter, you can use the acceleration, deceleration and setting clear functions of the
motorized speed setter (FR-FK).
Number Name Initial Value Setting
Description RH, RM, RL signal
0 Multi-speed setting —
1 Remote setting With
2 Remote setting Not used
59 Remote function selection 0
Not used (Turning STF/STR OFF
frequency.)
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 156)
When Pr. 59 = 1, 2
When Pr. 59 = 1
When Pr. 59 = 3
When Pr. 59 = 2, 3
ON ON ON
(RM)
ON
ON
(STF)
ON ON ON ON
ON ON
∗FL remote communication operation frequency (other than multi-speed) or PU operation frequency
yUse Pr. 59 to select whether the remote setting function is used or not and whether the frequency setting storage function
in the remote setting mode is used or not. When Pr. 59 is set to any of "1 to 3" (remote setting function valid), the functions of the RH, RM and RL signals are changed to acceleration (RH), deceleration (RM) and clear (RL). yWhen using the remote setting function, following frequencies can be compensated to the frequency set by RH and RM
operation according to the operation mode. During FL remote communication operation FL remote communication frequency command other than for
During PU operation PU operation frequency
PARAMETERS
yThe frequency setting storage function stores the remotely-set frequency (frequency set by RH/RM operation) into the
memory (EEPROM). When power is switched OFF once, then ON, operation is resumed with that output frequency value.
(Pr. 59 = 1)
Remote setting frequency is saved in the following timings: y When the start signal (STF or STR) turns OFF
y Every minute after turning OFF (ON) the RH (acceleration) and RM (deceleration) signals together. (The frequency
is overwritten if the latest frequency is different from the previous frequency when comparing the two. The state of
the RL signal does not affect writing.) y When the power supply changes to the 24V external power supply while the start signal (STF or STR) is ON. (When
the operation panel indication shows "EV.")

(acceleration) and RM (deceleration) is 0 to
The set frequency is clamped at (main speed + Pr. 1)
maximum frequency (Pr. 1 or Pr. 18 setting).
Output frequency is clamped at Pr. 1
is (main speed + maximum frequency).
Pr. 1
ON
y When the acceleration or deceleration signal switches ON, acceleration/deceleration time is as set in Pr. 44 Second
acceleration/deceleration time and Pr. 45 Second deceleration time. Note that when the time set in Pr. 7 or Pr. 8 is longer than
the time set in Pr. 44 or Pr. 45, the acceleration/deceleration time is as set in Pr. 7 or Pr. 8. (when RT signal is OFF)
When the RT signal is ON, acceleration/deceleration is made in the time set in Pr. 44 and Pr. 45, regardless of the Pr. 7
or Pr. 8 setting.
y Even if the start signal (STF or STR) is OFF, turning ON the acceleration (RH) or deceleration (RM) signal varies the
preset frequency.
y When switching the start signal from ON to OFF, or changing frequency by the RH or RM signal frequently, set the
frequency setting value storage function (write to EEPROM) invalid (Pr. 59 = "2, 3"). If set valid (Pr. 59 = "1"), frequency
is written to EEPROM frequently, this will shorten the life of the EEPROM.

During Jog operation, the remote setting function is invalid.
Setting frequency is "0"
y Even when the remotely-set frequency is cleared by turning ON the RL (clear) signal after turn OFF (ON) of both the RH and RM signals, the inverter operates at the remotely-set frequency stored in the last operation if power is reapplied before one minute has elapsed since turn OFF (ON) of both the RH and RM signals
Remotely-set frequency stored last time
Remotely-set frequency stored last time
ON
ON Power supply ON
ON
y When the remotely-set frequency
is cleared by turning ON the RL (clear) signal after turn OFF (ON) of both the RH and RM signals, the inverter operates at the frequency in the remotely-set frequency cleared state if power is reapplied after one minute has elapsed since turn OFF (ON) of both the RH and RM signals.
Remotely-set frequency stored last time 1 minute
More than 1 minute Operation is performed at the set frequency 0Hz.
ON
ON
ON
ON
CAUTION
When selecting this function, re-set the maximum frequency according to the machine.
Pr. 1 Maximum frequency, Pr. 18 High speed maximum frequency Refer to page 105 Pr. 7 Acceleration time, Pr. 8 Deceleration time, Pr. 44 Second acceleration/deceleration time, Pr. 45 Second deceleration time Refer to page 116

5.8 Setting of acceleration/deceleration time and acceleration/ deceleration pattern
Purpose Parameter that should be Set Refer to Page Motor acceleration/deceleration time setting
Pr. 7, Pr. 8, Pr. 20, Pr. 21, Pr. 44,
Pr. 45, Pr. 147
Starting frequency Starting frequency and start-time hold Pr. 13, Pr. 571 119
Set acceleration/deceleration pattern suitable for application
Acceleration/deceleration pattern Pr. 29 120
Automatically set optimum acceleration/deceleration time
Automatic acceleration/ deceleration Pr. 61 to Pr. 63, Pr. 292 121
5.8.1 Setting of the acceleration and deceleration time (Pr. 7, Pr. 8, Pr. 20, Pr. 21, Pr. 44, Pr. 45, Pr. 147)
Used to set motor acceleration/deceleration time. Set a larger value for a slower speed increase/decrease or a smaller value for a faster speed increase/decrease.
For the acceleration time at automatic restart after instantaneous power failure, refer to Pr. 611 Acceleration time at a restart (page 151).
Number Name Initial Value Setting
3.7K or lower 5s 0 to 3600/ 360s ∗2 Motor acceleration time. 5.5K, 7.5K 10s 11K, 15K 15s
3.7K or lower 5s 0 to 3600/ 360s ∗2 Motor deceleration time. 5.5K, 7.5K 10s 11K, 15K 15s
Acceleration/ deceleration reference frequency
Frequency that will be the basis of acceleration/deceleration time. As acceleration/deceleration time, set the frequency change time from stop to Pr. 20.
60Hz 1 to 400Hz
3.7K or lower 5s 0 to 3600/ 360s ∗2 Acceleration/deceleration time when the RT signal is ON. 5.5K, 7.5K 10s
9999 0 to 3600/ 360s ∗2 Deceleration time when the RT signal is ON. 9999 Acceleration time = deceleration time
9999 0 to 400Hz Frequency when automatically switching to the acceleration/deceleration time of Pr. 44 and Pr. 45.
∗1 The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)
∗2 Depends on the Pr. 21 Acceleration/deceleration time increments setting. The initial value for the setting range is "0 to 3600s" and the setting increments is "0.1s".

Pr. 20 (60Hz)
yUse Pr. 7 Acceleration time to set the acceleration time required to reach Pr. 20
Acceleration/deceleration reference frequency from 0Hz.
ySet the acceleration time according to the following formula.
Pr. 20
× Acceleration time from a stop to the
maximum operating frequency Maximum operating
Pr. 7, Pr. 44
Pr. 8, Pr. 45
frequency - Pr. 13
Example) How to find the setting value for Pr.7 when increasing the output
60Hz × 10s 12.1s 50Hz - 0.5Hz
frequency to the maximum frequency of 50Hz in 10s with Pr.20 = "60Hz (initial setting)" and Pr. 13 = "0.5Hz (initial setting)."
Pr. 7 =
yUse Pr. 8 Deceleration time to set the deceleration time required to reach 0Hz from Pr. 20 Acceleration/deceleration reference
frequency.
ySet the deceleration time according to the following expression.
time setting = Pr. 20 × Deceleration time from the maximum operating frequency to a stop Maximum operating frequency - Pr. 10
Example) How to find the setting value for Pr.8 when decreasing the output
Pr. 8 = 120Hz × 10s 25.5s 50Hz-3Hz
frequency from the maximum frequency of 50Hz in 10s with Pr.20 = "120Hz" and Pr. 10 = "3Hz (initial setting)."
(3) Change the setting range and increments of the acceleration/deceleration time (Pr. 21)
yUse Pr. 21 to set the acceleration/deceleration time and minimum setting range.
Value "0" (initial value) 0 to 3600s (minimum setting increments: 0.1s) Value "1" 0 to 360s (minimum setting increments: 0.01s)
(It does not influence the setting of Pr. 611 Acceleration time at a restart.)
When Pr. 7 is set to "5.0s" at Pr. 21 setting of "0", and then Pr. 21 is changed to "1", the Pr. 7 setting automatically
changes to "0.5s".

(4) Set two kinds of acceleration/deceleration times (RT signal, Pr. 44, Pr. 45, Pr. 147 )
yPr. 44 and Pr. 45 are valid when the RT signal is ON, or the output frequency reaches or exceeds the setting of Pr. 147. yWhen "9999" is set to Pr. 45, the deceleration time becomes equal to the acceleration time (Pr. 44).
yAcceleration/deceleration time changes when the RT signal turns ON or when the output frequency reaches the Pr.147
setting or higher.

9999 (initial value) Pr. 7, Pr. 8 No automatic switching of the acceleration/deceleration
0.00Hz Pr. 44, Pr. 45 Second acceleration/deceleration time from a start
0.00Hz ≤ Pr. 147 ≤ Set frequency Output frequency < Pr. 147: Pr. 7, Pr. 8
Set frequency < Pr. 147 Pr. 7, Pr. 8 No automatic switching, since output frequency will not
∗When the RT signal turns on, the acceleration/deceleration time switches to the second acceleration/deceleration time even when the output frequency is
not reached to Pr. 147 setting.

y When the acceleration/deceleration pattern is S-pattern acceleration/deceleration A (refer to page 120), the acceleration/
deceleration time is the time required to reach Pr. 3 Base frequency.
y Acceleration/deceleration time formula when the set frequency is the base frequency or higher
t=
× f2+
y Guideline for acceleration/deceleration time at the Pr. 3 Base frequency of 60Hz (0Hz to set frequency)

y The RT signal acts as the second function selection signal and makes the other second functions valid. (Refer to page 143)
y When the Pr. 7, Pr. 8, Pr. 44 and Pr. 45 settings are 0.03s or less, the acceleration/deceleration time is 0.04s. At that time, set Pr.
20 to "120Hz" or less.
y Any value can be set to the acceleration/deceleration time but the actual motor acceleration/deceleration time cannot be made shorter
than the shortest acceleration/deceleration time determined by the mechanical system J (moment of inertia) and motor torque.
Pr. 3 Base frequency Refer to page 107 Pr. 10 DC injection brake operation frequency Refer to page 135 Pr. 29 Acceleration/deceleration pattern selection Refer to page 120
4 × · Parameters referred to

5.8.2 Starting frequency and start-time hold function (Pr. 13, Pr. 571)

You can set the starting frequency and hold the set starting frequency for a certain period of time.
Set these functions when you need the starting torque or want to smooth motor drive at a start.
Frequency at start can be set in the range
571 Holding time at a start 9999 0.0 to 10.0s Holding time of Pr. 13 Starting frequency.
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)

yFrequency at start can be set in the range 0 to 60Hz.
yYou can set the starting frequency at which the start signal is turned
ON.
The inverter will not start if the frequency setting signal is less than the value set in Pr. 13.
For example, when 5Hz is set in Pr. 13, the motor will not start running until the frequency setting signal reaches 5Hz.

yThis function holds during the period set in Pr. 571 and the output
frequency set in Pr. 13 Starting frequency. yThis function performs initial excitation to smooth the motor drive at a
start.
When Pr. 13 = "0Hz", the starting frequency is held at 0.01Hz.

y When the start signal was turned OFF during start-time hold, deceleration is started at that point.
y At switching between forward rotation and reverse rotation, the starting frequency is valid but the start-time hold
start signal will run the motor at the preset frequency even if the command frequency is not input.

5.8.3 Acceleration/deceleration pattern (Pr. 29)

You can set the acceleration/deceleration pattern suitable for application.
The above parameters can be set when Pr. 160 User group read selection ="0". (Refer to page 167)

yFor the inverter operation, the output frequency is made to change linearly (linear
acceleration/deceleration) to prevent the motor and inverter from excessive stress
to reach the set frequency during acceleration, deceleration, etc. when frequency changes. Linear acceleration/deceleration has a uniform frequency/time slope.
yFor machine tool spindle applications, etc.
Used when acceleration/deceleration must be made in a short time to a high-
speed range of not lower than the base frequency. In this acceleration/deceleration pattern, Pr. 3 Base frequency (fb) is the inflection
point of the S pattern and you can set the acceleration/deceleration time appropriate for motor torque reduction in a constant-power operation range of
base frequency (fb) or higher.
y As the acceleration/deceleration time of S-pattern acceleration/deceleration A, set the time taken until Pr. 3 Base
frequency is reached, not Pr. 20 Acceleration/deceleration reference frequency.

yFor prevention of load shifting in conveyor and other applications.
Since acceleration/deceleration is always made in an S shape from current
frequency (f2) to target frequency (f1), this function eases shock produced at acceleration/deceleration and is effective for load collapse prevention, etc.
Pr. 3 Base frequency Refer to page 107 Pr. 7 Acceleration time, Pr. 8 Deceleration time, Pr. 20 Acceleration/deceleration reference frequency Refer to page 116
Parameters referred to

5.8.4 Shortest acceleration/deceleration (automatic acceleration/deceleration) (Pr. 61 to Pr. 63, Pr. 292, Pr. 293)
The inverter operates in the same conditions as when appropriate values are set in each parameter even if
acceleration/deceleration time and V/F pattern are not set. This function is useful when you just want to operate, etc. without fine parameter setting.
61 Reference current 9999 0 to 500A Set the reference current during shortest
acceleration/deceleration.
9999 Rated inverter output current value is reference
9999 0 to 200% Set the limit value during shortest acceleration.
9999 150% is a limit value
9999 0 to 200% Set the limit value during shortest deceleration.
9999 150% is a limit value
1 Shortest acceleration/deceleration (without brake)
11 Shortest acceleration/deceleration (with brake)
7, 8 For manufacturer setting. Do not set.
0 Both acceleration and deceleration are made in the
1 Only acceleration is made in the shortest
2 Only deceleration is made in the shortest
The above parameters can be set when Pr. 160 User group read selection ="0". (Refer to page 167)
(1) Shortest acceleration/deceleration mode (Pr. 292 = "1, 11", Pr. 293)
ySet when you want to accelerate/decelerate the motor for the shortest time. It is desired to make acceleration/deceleration
in a shorter time for a machine tool etc. but the design values of machine constants are unknown. yAcceleration/deceleration speed is automatically adjusted at a start of acceleration/deceleration from the value of the
setting value of Pr. 7 Acceleration time and Pr. 8 Deceleration time so that acceleration/deceleration is made with the maximum torque the inverter can output. (The setting values of Pr. 7 and Pr. 8 are not changed.)
yEither acceleration or deceleration can be made in the shortest time using Pr. 293 Acceleration/deceleration separate
selection. When the setting value is "0" (initial value), both acceleration and deceleration can be made in the shortest time.
ySet "11" when an optional MRS type, MYS type brake resistor, high-duty brake resistor or brake unit is connected.
Deceleration time can be further shortened.
yWhen the shortest/acceleration mode is selected, the stall prevention operation level during acceleration/deceleration from
the value of becomes 150% (adjustable using Pr. 61 to Pr. 63 ). Setting of Pr. 22 Stall prevention operation level is used only
during a constant speed operation. yIt is inappropriate to use for the following applications.
a) Machine with a large inertia such as a fan (more than 10 times). Since stall prevention operation will be activated for
a long time, this type of machine may trip due to motor overloading, etc.
b) To perform operation with a constant acceleration/deceleration time.
y Even if automatic acceleration/deceleration mode has been selected, inputting the RT signal (second function selection) during
an inverter stop will switch to the normal operation and give priority to the second function selection. Note that RT signal input is
invalid even if RT signal is input during operation in the automatic acceleration/deceleration mode.
y Since acceleration/deceleration is made with the stall prevention operation being activated, the acceleration/deceleration speed
always varies according to the load conditions.
y Note that when proper values are set in Pr. 7 and Pr. 8, acceleration/deceleration time may be shorter than selecting shortest
acceleration/deceleration mode.

(2) Adjustment of shortest acceleration/deceleration mode (Pr. 61 to Pr. 63)
yBy setting the adjustment parameters Pr. 61 and Pr. 63, the application range can be made wider.
Number Name Setting Range Description
For example, when the motor and inverter are different in capacity,
set the rated motor current value.
Set reference current (A) of the stall prevention operation level
during acceleration/deceleration.
9999 (initial value) The rated inverter current is defined as reference.
Set when it is desired to change the reference level of acceleration
and deceleration.
Set the stall prevention operation level (ratio to the current value of
Pr. 61) during acceleration/deceleration.
9999 (initial value) Stall prevention operation level is 150% for the shortest acceleration/
deceleration.
y Since the Pr. 61 to Pr. 63 settings automatically return to the initial value (9999) if the Pr. 292 setting is changed, set Pr. 292 first
when you need to set Pr. 61 to Pr. 63.
Pr. 0 Torque boost Refer to page 94 Pr. 7 Acceleration time, Pr. 8 Deceleration time Refer to page 116 Pr. 22 Stall prevention operation level Refer to page 101

5.9 Selection and protection of a motor

Purpose Parameter that should be Set Refer to Page Motor protection from overheat Electronic thermal O/L relay Pr. 9, Pr. 51 123 Use the constant-torque motor Applied motor Pr. 71 125 The motor performance can be maximized for operation in magnetic flux vector control method.
Offline auto tuning Pr. 71, Pr. 80 to Pr. 84, Pr. 90 to Pr. 94, Pr. 96, Pr. 859 127

Set the current of the electronic thermal relay function to protect the motor from overheat. This feature provides the optimum protective characteristics, including reduced motor cooling capability, at low speed.
rated current ∗1 0 to 500A Set the rated motor current.
9999 0 to 500A Valid when the RT signal is ON.
∗1 The initial value of the 0.75K or lower is set to 85% of the rated inverter current. ∗2 The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167) (1) Electronic thermal O/L relay (Pr. 9)
This function detects the overload (overheat) of the motor and trips. (The operation characteristic is shown on the left) y Set the rated current (A) of the motor in Pr. 9.
Electronic thermal O/L relay operation characteristic

Pr. 9 = 50% setting of inverter rating*1, 2
(If the motor has both 50Hz and 60Hz rating and the Pr. 3 Base frequency is set to 60Hz, set the 1.1 times of the 60Hz rated motor current.) y Set "0" in Pr. 9 when you do not want to operate the
30Hz or more *3 30Hz or more *3 20Hz 10Hz
Operation range Range on the right of characteristic curve Non-operation range Range on the left of characteristic curve
electronic thermal O/L relay, e.g. when using an external thermal relay with the motor. (Note that the output transistor protection of the inverter functions (E.THT).) y When using a Mitsubishi constant-torque motor
Characteristic when electronic thermal relay function for motor protection is turned off (when Pr. 9 setting is 0(A))
∗1 When 50% of the inverter rated output current (current value) is
Inverter output current(%) (% to the rated inverter current)
set to Pr. 9
∗2 The % value denotes the percentage to the inverter rated output current. It is not the percentage to the motor rated current.
∗3 When you set the electronic thermal O/L relay dedicated to the
Mitsubishi constant-torque motor, this characteristic curve applies
to operation at 6Hz or higher.
y Fault by electronic thermal relay function is reset by inverter power reset and reset signal input. Avoid unnecessary
reset and power-OFF. y When multiple motors are operated by a single inverter, protection cannot be provided by the electronic thermal
function. Install an external thermal relay to each motor. y When the difference between the inverter and motor capacities is large and the setting is small, the protective
characteristics of the electronic thermal relay function will be deteriorated. In this case, use an external thermal relay. y A special motor cannot be protected by the electronic thermal relay function. y The operation time of the transistor protection thermal shortens when the Pr. 72 PWM frequency selection setting
increases. y Electronic thermal relay may not function when 5% or less of inverter rated current is set to electronic thermal relay setting.

Use this function when running two motors of different rated currents individually by a single inverter. (When running two
motors together, use external thermal relays.) ySet the rated current of the second motor to Pr. 51. yWhen the RT signal is ON, thermal protection is provided based on the Pr. 51 setting.

9999 0 9999 × 0 × 0.01 to 500 × Δ × {
9999 { × { × 0 { × Δ × 0.01 to 500 { Δ Δ {
Other than 9999 0 9999 × 0 × 0.01 to 500 × Δ × {
9999 { Δ Δ { 0 { × Δ × 0.01 to 500 { Δ Δ { { ... Output current value is used to perform integration processing. Δ Output current is assumed as 0A to perform integration processing. (cooling processing) × Electronic thermal relay function is not activated.
y The RT signal acts as the second function selection signal and makes the other second functions valid. (Refer to page 143)

y The electronic thermal relay function prealarm (TH) is
displayed when the electronic thermal O/L relay cumulative value reaches 85% of the level set in Pr. 9 or Pr. 51. If it reaches 100% of the Pr. 9 Electronic thermal O/L relay setting, a motor overload trip (E.THM/E.THT) occurs.
Pr. 71 Applied motor Refer to page 125 Pr. 72 PWM frequency selection Refer to page 163
Parameters referred to

5.9.2 Applied motor (Pr. 71, Pr. 450)
Setting of the used motor selects the thermal characteristic appropriate for the motor. Setting is required to use a constant-torque motor. Thermal characteristic of the electronic thermal relay function suitable for the motor is set. When General-purpose magnetic flux vector or Advanced magnetic flux vector control is selected, the motor constants (SF-JR, SF-HR, SF-JRCA, SF-HRCA, etc.) necessary for control are selected as well.
Number Name Initial Value Setting Range Description
71 Applied motor 0 0, 1, 3 to 6, 13 to 16, 23, 24, 40, 43, 44, 50, 53, 54
Selecting the standard motor or constant-torque motor sets the corresponding motor thermal characteristic.
0, 1 Set when using the second motor.
9999 Second motor is invalid (thermal characteristic of the first motor (Pr. 71))
450 Second applied motor 9999
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)
(1) Set the motor to be used Refer to the following list and set this parameter according to the motor used.
Pr. 71 (Pr. 450)
Setting Thermal Characteristic of the Electronic Thermal Relay Function
Pr. 71 Pr. 450 Standard (SF-JR, etc.)
(SF-JRCA, etc.) 0 (Pr. 71 initial value) Thermal characteristics of a standard motor {
1 Thermal characteristics of the Mitsubishi constant-torque motor { 40 — Thermal characteristic of Mitsubishi high efficiency motor (SF-HR) { ∗1 50 — Thermal characteristic of Mitsubishi constant-torque motor (SF-HRCA) { ∗2 3 — Standard motor
{ 13 — Constant-torque motor {
23 — Mitsubishi standard motor (SF-JR 4P 1.5kW or less) {
Select "Offline auto tuning setting"
43 — Mitsubishi high efficiency motor (SF-HR) { ∗1
53 — Mitsubishi constant-torque motor (SF- HRCA) { ∗2
{ 14 — Constant-torque motor {
4 — Standard motor
24 — Mitsubishi standard motor (SF-JR 4P 1.5kW or less) {
Auto tuning data can be read,
changed, and set.
44 — Mitsubishi high efficiency motor (SF-HR) {∗1
54 — Mitsubishi constant-torque motor (SF- HRCA) { ∗2
{ 15 — Constant-torque motor { 6 — Standard motor Delta connection
5 — Standard motor Star connection Direct input of motor constants is
{ 16 — Constant-torque motor {
Without second applied motor
∗1 Motor constants of Mitsubishi high efficiency motor SF-HR. ∗2 Motor constants of Mitsubishi constant-torque motor SF-HRCA.
y When performing offline auto tuning, set any of "3, 13, 23, 43, 53" in Pr. 71.
(Refer to page 127 for offline auto tuning.) y For the 5.5K and 7.5K, the Pr. 0 Torque boost and Pr. 12 DC injection brake operation voltage settings are automatically changed
according to the Pr. 71 setting as follows.
Setting ∗2 Pr. 0 3% 2% Pr. 12 4% 2% ∗1 Pr. 71 setting: 0, 3 to 6, 23, 24,40, 43, 44 ∗2 Pr. 71 setting: 1, 13 to 16, 50, 53, 54
y Set the electronic thermal relay function to the thermal characteristic for the constant-torque motor when using a
geared motor (GM-S, GM-D, GM-SY, GM-HY2 series) to perform Advanced magnetic flux vector control or General- purpose magnetic-flux vector control.

y Set Pr. 450 Second applied motor to use two different motors with one inverter.
y When "9999" (initial value) is set, no function is selected. y When a value other than 9999 is set in Pr. 450, the second motor is valid when the RT signal turns ON.

y The RT signal acts as the second function selection signal and makes the other second functions valid. (Refer to page 143)
Make sure to set this parameter correctly according to the motor used.
Incorrect setting may cause the motor to overheat and burn.
Pr. 0 Torque boost Refer to page 94 Pr. 12 DC injection brake operation voltage Refer to page 135 Pr. 80 Motor capacity, Pr. 81 Number of motor poles Refer to page 127 Pr. 82 to Pr. 84, Pr. 90 to Pr. 94 (motor constants), Pr. 96 Auto tuning setting/status Refer to page 127 Pr. 800 Control method selection Refer to page 93

5.9.3 Exhibiting the best performance for the motor (offline auto tuning) (Pr. 71, Pr. 80 to Pr. 84, Pr. 90 to Pr. 94, Pr. 96, Pr. 859)
The motor performance can be maximized with offline auto tuning. zWhat is offline auto tuning?
When performing Advanced magnetic flux vector control or General-purpose magnetic flux vector control, the motor can be run with the optimum operating characteristics by automatically measuring the motor constants (offline auto
tuning) even when each motor constants differs, other manufacturer's motor is used, or the wiring length is long (30m or more as a reference).
Number Name Initial Value Setting Range Description
0, 1, 3 to 6,
By selecting a standard motor or constant-
71 Applied motor 0
13 to 16, 23, 24, 40,
torque motor, thermal characteristic and motor
43, 44, 50, 53, 54
constants of each motor are set.
80 Motor capacity 9999 0.1 to 15kW Applied motor capacity.
81 Number of motor poles 9999 2, 4, 6, 8, 10 Number of motor poles.
(The value measured by offline auto tuning is
82 Motor excitation current 9999
automatically set.)
9999 Uses the Mitsubishi motor (SF-JR, SF-HR,
SF-JRCA, SF-HRCA) constants.
83 Rated motor voltage 200V class 200V 0 to 1000V Rated motor voltage (V). 400V class 400V 84 Rated motor frequency 60Hz 10 to 120Hz Rated motor frequency (Hz). 90 Motor constant (R1) 9999 0 to 50Ω, 9999 Tuning data
91 Motor constant (R2) 9999 0 to 50Ω, 9999 92 Motor constant (L1) 9999 0 to 1000mH, 9999 93 Motor constant (L2) 9999 0 to 1000mH, 9999 94 Motor constant (X) 9999 0 to 100%, 9999
(The value measured by offline auto tuning is
automatically set.)
HR, SF-JRCA, SF-HRCA) constants.
0 Offline auto tuning is not performed
For Advanced magnetic flux vector control
Offline auto tuning is performed without motor
running (all motor constants).
For General-purpose magnetic flux vector
Offline auto tuning is performed without motor
running.
(motor constant (R1) only)
Offline auto tuning for V/F control (automatic
restart after instantaneous power failure (with
frequency search)) (Refer to page 153)
(The value measured by offline auto tuning is
859 Torque current 9999
automatically set.)
9999 Uses the Mitsubishi motor (SF-JR, SF-HR,
SF-JRCA, SF-HRCA) constants.
The above parameters can be set when Pr. 160 User group read selection = "0".(Refer to page 167)

y The setting range and increments of Pr. 82, Pr. 90 to Pr. 94 and Pr. 859 changes according to the setting value of Pr. 71 and
Pr. 96.
Applied Motor Internal Stored Value ∗1 Direct Input Value ∗2 Auto Tuning Measured Value
Number Function Name Setting Range Setting
Increments Setting Range Setting
Increments Setting Range Setting
82 Motor excitation current 0 to 500A, 9999 0.01A 0 to 500A, 9999 0.01A 0 to ****, 9999 1
90 Motor constant (R1) 0 to 50Ω, 9999 0.001Ω 0 to 50Ω, 9999 0.001Ω 0 to ****, 9999 1
91 Motor constant (R2) 0 to 50Ω, 9999 0.001Ω 0 to 50Ω, 9999 0.001Ω 0 to ****, 9999 1
92 Motor constant (L1) 0 to 1000mH, 9999 0.1mH 0 to 50Ω, 9999 0.001Ω 0 to ****, 9999 1
93 Motor constant (L2) 0 to 1000mH, 9999 0.1mH 0 to 50Ω, 9999 0.001Ω 0 to ****, 9999 1
94 Motor constant (X) 0 to 100%, 9999 0.1% 0 to 500Ω, 9999 0.01Ω 0 to ****, 9999 1
859 Torque current 0 to 500A, 9999 0.01A 0 to 500A, 9999 0.01A 0 to ****, 9999 1
∗1 When Pr. 71 = "0, 1, 40 or 50", or setting value of Pr. 96 read after performing offline auto tuning is not "3, 13, 23".
∗2 When Pr. 71 = "5, 6, 15, or 16"
∗3 When Pr. 71 = "3, 13, 23, 43 or 53" and setting value of Pr. 96 read after performing offline auto tuning is "3, 13, 23". Or when Pr. 71 = "4, 14, 24, 44 or 54".
y This function is valid only when a value other than "9999" is set in Pr. 80 and Pr. 81 and Advanced magnetic flux
vector control or General-purpose magnetic flux vector control is selected.
y Even when motors (other manufacturer's motor, SF-JRC, etc.) other than Mitsubishi standard motor (SF-JR
0.2kW or higher), high efficiency motor (SF-HR 0.2kW or higher), and Mitsubishi constant-torque motor (SF- JRCA four-pole, SF-HRCA 0.2kW to 15kW) are used or the wiring length is long (30m or more as a reference),
using the offline auto tuning function runs the motor with the optimum operating characteristics.
y Tuning is enabled even when a load is connected to the motor.
As the motor may run slightly, fix the motor securely with a mechanical brake or make sure that there will be no problem in safety if the motor runs (caution is required especially in elevator). Note that tuning performance is
unaffected even if the motor runs slightly.
y Reading/writing/copy of motor constants tuned by offline auto tuning are enabled.
y The offline auto tuning status can be monitored with the operation panel.
y Do not connect a surge voltage suppression filter (FR-ASF-H/FR-BMF-H) between the inverter and motor.
Check the following before performing offline auto tuning.
y Make sure Advanced magnetic flux vector control or General-purpose magnetic flux vector control (Pr. 80, Pr. 81) is
selected.
y A motor should be connected. Note that the motor should be at a stop at a tuning start. y The motor capacity should be equal to or one rank lower than the inverter capacity. (note that the capacity should be
0.1kW or more) y A high-slip motor, high-speed motor and special motor cannot be tuned. (The maximum frequency is 120Hz.)
y As the motor may run slightly, fix the motor securely with a mechanical brake or make sure that there will be no problem
in safety if the motor runs (caution is required especially in elevator). Note that tuning performance is unaffected even if
the motor runs slightly. y Offline auto tuning will not be performed properly if it is performed with a surge voltage suppression filter (FR-ASF-H/FR-
BMF-H) connected between the inverter and motor. Remove it before starting tuning.
∗3 Parameter · Increments

When performing Advanced magnetic flux vector control, set "1" to perform tuning. It takes approximately 25 to 75s∗ until tuning is completed.
(Excitation noise is produced during tuning.)
∗Tuning time differs according to the inverter capacity and motor type. y When the setting is "11" Tune motor constants (R1) only without running the motor.
When performing General-purpose magnetic flux vector control, set "11" to perform
tuning. It takes approximately 9s until tuning is completed.
value is 60Hz) in Pr. 84 Rated motor frequency. (For a Japanese standard motor, etc. which has both 50Hz and 60Hz rated values, use it with an initial value (200V/60Hz
or 400V/60Hz). 5) Set Pr. 71 Applied motor according to the motor used.
Motor Pr. 71 Setting ∗1
Mitsubishi standard motor Mitsubishi high efficiency motor
SF-JR 4P 1.5kW or less 23
SF-JRCA 4P 13
SF-HRCA 53
Others (SF-JRC, etc.) 13
standard motor — 3
Other manufacturer's constant-torque motor — 13
∗1 Refer to page 125, for other settings of Pr. 71.
Others 3 · Mitsubishi constant-torque motor · Other manufacturer's

POINT Before performing tuning, check the monitor display of the operation panel if the inverter is in the status for tuning.
(Refer to 3) below.) When the start command is turned ON under V/F control, the motor starts.
change the operation mode to the PU operation mode using on the operation panel.
(When the Network operation mode is selected and "1" is set in the X12 signal (Bit 11), which gives a control input command through FL remote communication, the inverter output is shutoff. Therefore, inputting a start signal through
FL remote communication does not start tuning in this condition.)
y To force tuning to end, press of the operation panel.
y X12 signal is the only valid input/output signal during the offline auto tuning.
Setting "0" in the X12 signal while tuning is being set or performed forces the operation mode to change to Network
operation mode.
Use the X12 signal after setting "0" (stop command) in the forward/reverse rotation command (STF/STR signal) to set
and perform tuning.
y When executing offline auto tuning, input the run command after switching on the main circuit power (R/L1, S/L2, T/
L3) of the inverter.


Tune all motor constants (Pr. 96 = "1") Approximately 25 to 75s
(Tuning time differs according to the inverter capacity and motor type.)
Tune motor constants (R1) only (Pr. 96 = "11") Approximately 9s
y The set frequency monitor displayed during the offline auto tuning is 0Hz.

the monitor display of the operation panel returns to normal.
Display Error Cause Remedy
8 Forced end Set "1" or "11" in Pr. 96 and perform tuning again.
9 Inverter protective function operation Make setting again.
91 Current limit (stall prevention) function was activated. Set "1" in Pr. 156.
92 Converter output voltage reached 75% of rated value. Check for fluctuation of power supply voltage.
Check the motor wiring and make setting again.
A motor is not connected.
Set the rated current of the motor in Pr. 9.
constants have not been set.)
Perform an inverter reset and restart tuning. 8) When the rated power specification of the motor is 200/220V(400/440V) 60Hz, set 1.1 times the rated motor current
value in Pr.9 Electronic thermal O/L relay after tuning is completed.
y Do not change the Pr. 96 setting after completion of tuning (3 or 13). If the Pr. 96 setting is changed, tuning data is
invalid. If the Pr. 96 setting is changed, tuning must be performed again.
y The motor constants measured once in the offline auto tuning are stored as parameters and their data are held until
the offline auto tuning is performed again.
y An instantaneous power failure occurring during tuning will result in a tuning error. After power is restored, the
inverter goes into the normal operation mode.
y Any alarm occurring during tuning is handled as in the ordinary mode. Note that if a fault retry has been set, retry is
ignored.
As the motor may run slightly during offline auto tuning, fix the motor securely with a mechanical brake or
make sure that there will be no problem in safety if the motor runs. Note that if the motor runs slightly, tuning
performance is unaffected.
Error · 93 Calculation error

The data measured in the offline auto tuning can be read and utilized or changed.
Motor Pr. 71 Setting ∗1
SF-JR 4 SF-JR 4P 1.5kW or less 24 SF-HR 44 Others 4
Mitsubishi high efficiency motor
SF-JRCA 4P 14 SF-HRCA 54 Others (SF-JRC, etc.) 14 Other manufacturer's
standard motor - 4
constant-torque motor - 14
∗1 For other settings of Pr.71, refer to page 125.
Number Name Setting Range Setting
82 Motor excitation current 0 to ****, 9999 1 9999
90 Motor constant (R1) 0 to ****, 9999 1 9999
91 Motor constant (R2) 0 to ****, 9999 1 9999
92 Motor constant (L1) 0 to ****, 9999 1 9999
93 Motor constant (L2) 0 to ****, 9999 1 9999
94 Motor constant (X) 0 to ****, 9999 1 9999
859 Torque current 0 to ****, 9999 1 9999
y When "9999" is set in Pr. 82, Pr. 90 to Pr. 94, Pr. 859, Mitsubishi motor (SF-JR, SF-HR, SF-JRCA, SF-HRCA) constants are used.
y As the motor constants measured in the offline auto tuning have been converted into internal data (****), refer to the following
setting example when making setting:
Setting example To slightly increase Pr. 90 value (5%)
When Pr. 90 is displayed as "2516",
set 2642 (2516 x 1.05=2641.8) in Pr. 90.
(The value displayed has been converted into a value for internal use. Hence, simple addition of a given
value to the displayed value has no significance.)

(5) Method to set the motor constants without using the offline auto tuning data
The Pr. 90 to Pr. 94 motor constants may either be entered in [Ω] or in [mH]. Before starting operation, confirm which motor constant unit is used.
zTo enter the Pr. 90 to Pr. 94 motor constants in [Ω]
1)Set Pr. 71 according to the motor used.
Star Connection Motor Delta Connection Motor
Setting Standard motor 5 6
Constant-torque motor 15 16
2)In the parameter setting mode, read the following parameters and set desired values.
Iq =torque current, I100 =rated current, I0 =no load current
Iq = I1002 - I02
Number Name Setting Range Setting
82 Motor excitation current
(no load current) 0 to 500A, 9999 0.01A 9999
90 Motor constant (r1) 0 to 50Ω, 9999 0.001Ω 9999
91 Motor constant (r2) 0 to 50Ω, 9999 0.001Ω 9999
92 Motor constant (x1) 0 to 50Ω, 9999 0.001Ω 9999
93 Motor constant (x2) 0 to 50Ω, 9999 0.001Ω 9999
94 Motor constant (xm) 0 to 500Ω, 9999 0.01Ω 9999
859 Torque current 0 to 500A, 9999 0.01A 9999
3)Refer to the following table and set Pr. 83 and Pr. 84.
Number Name Setting Range Setting
83 Rated motor voltage 0 to 1000V 0.1V 200V class 200V
84 Rated motor frequency 10 to 120Hz 0.01Hz 60Hz
y When "9999" is set in Pr. 82, Pr. 90 to Pr. 94, Pr. 859, Mitsubishi motor (SF-JR, SF-HR, SF-JRCA, SF-HRCA) constants are used.
y If "star connection" is mistaken for "delta connection" or vice versa during setting of Pr. 71, Advanced magnetic flux
vector control and General-purpose magnetic flux vector control cannot be exercised properly.

zTo enter the Pr. 90 to Pr. 94 motor constants in [mH]

Mitsubishi constant-torque motor SF-JRCA 4P 1 SF-HRCA 50 ∗1 For other settings of Pr. 71, refer to page 125.
Calculate the Pr. 94 value from the following formula.
Pr. 94 setting = (1 - M2

Motor equivalent circuit diagram

(no load current) 0 to 500A, 9999 0.01A 9999
90 Motor constant (R1) 0 to 50Ω, 9999 0.001Ω 9999
91 Motor constant (R2) 0 to 50Ω, 9999 0.001Ω 9999
92 Motor constant (L1) 0 to 1000mH, 9999 0.1mH 9999
93 Motor constant (L2) 0 to 1000mH, 9999 0.1mH 9999
94 Motor constant (X) 0 to 100%, 9999 0.1% 9999
859 Torque current 0 to 500A, 9999 0.01A 9999

83 Rated motor voltage 0 to 1000V 0.1V 200V class 200V
84 Rated Motor Frequency 10 to 120Hz 0.01Hz 60Hz
y When "9999" is set in Pr. 82, Pr. 90 to Pr. 94, Pr. 859, Mitsubishi motor (SF-JR, SF-HR, SF-JRCA, SF-HRCA) constants are used.
Pr. 7 Acceleration time, Pr. 8 Deceleration time Refer to page 116 Pr. 9 Electronic thermal O/L relay Refer to page 123 Pr. 71 Applied motor Refer to page 125 Pr. 80 Motor capacity, Pr. 81 Number of motor poles Refer to page 93 Pr. 156 Stall prevention operation selection Refer to page 101 Pr. 800 Control method selection Refer to page 93
Parameters referred to

5.10 Motor brake and stop operation

Purpose Parameter that should be Set Refer to Page Motor braking torque adjustment DC Injection brake Pr. 10 to Pr. 12 135 Improve the motor braking torque with an option
Coast the motor to a stop Selection of motor stopping method Pr. 250 138
Used to stop the motor with a mechanical brake (vibration restraint at stop-on-contact)
5.10.1 DC injection brake (Pr. 10 to Pr. 12)

The DC injection brake can be operated at a motor stop to adjust the stop timing and braking torque. In DC injection brake operation, DC voltage is directly applied to the motor to prevent the motor shaft from rotating. The motor will not return to the original position if the motor shaft rotates due to external force.
"0" is set, DC injection brake is disabled. 0.4K to 7.5K 4%
The above parameters can be set when Pr. 160 User group read selection ="0". (Refer to page 167)

y When the frequency at which the DC injection brake will be operated is
set to Pr. 10, the DC voltage is applied to the motor upon reaching to the set frequency during deceleration.
yIn Pr. 11, set the time of the DC injection brake. yWhen the motor does not stop due to large load moment (J), increasing
the setting produces an effect. yWhen Pr. 11 = "0s", the DC injection brake is disabled. (At a stop, the
motor coasts.)
y Use Pr. 12 to set the percentage to the power supply voltage. y When Pr. 12 = "0%", the DC injection brake is disabled. (At a stop, the motor coasts.) y When using the constant-torque motor (SF-JRCA) and energy saving motor (SF-HR, SF-HRCA), change the Pr. 12 setting
as follows:
Motor Pr.12 DC injection brake operation voltage Setting
SF-JRCA 3.7K or lower 4% 5.5K or higher 2%
3.7K or lower 4% 5.5K, 7.5K 3% 11K, 15K 2%
REMARKS
y For the 5.5K, 7.5K, when the Pr. 12 setting is the following, changing the Pr. 71 Applied motor setting automatically changes the
Pr. 12 setting. Therefore, it is not necessary to change the Pr. 12 setting.
(a) When 4% (initial value) is set in Pr. 12
The Pr. 12 setting is automatically changed to 2% if the Pr. 71 value is changed from the value selecting the standard motor (0, 3 to 6, 23, 24, 40, 43, 44) to the value selecting the constant-torque motor (1, 13 to 16, 50, 53, 54). (b) When 2% is set in Pr. 12
The Pr. 12 setting is automatically changed to 4% (initial value) if the Pr. 71 value is changed from the value selecting the constant-torque motor (1, 13 to 16, 50, 53, 54) to the value selecting the standard motor (0, 3 to 6, 23, 24, 40, 43, 44). y Even if the Pr. 12 setting is increased, braking torque is limited so that the output current is within the rated inverter current.


As stop holding torque is not produced, install a mechanical brake.
Pr. 13 Starting frequency Refer to page 119 Pr. 71 Applied motor Refer to page 125

z When making frequent starts/stops, use the optional brake resistor (MRS type, MYS type), high-duty brake resistor
(FR-ABR) and brake unit (FR-BU2) to increase the regenerative brake duty.
1 Brake resistor (MYS type) used at 100% torque / 6%ED
High-duty brake resistor (FR-ABR) 2 For manufacturer setting. Do not set.
Brake duty (6%) when using the brake resistor (MYS type),
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)
(1) When using the brake resistor (MRS type, MYS type) and the brake unit (FR-BU2)
ySet Pr. 30 = "0 (initial value)". The Pr. 70 setting is made invalid.
At this time, the regenerative brake duty is as follows.
Model Regenerative Brake Duty FR-E720-0.4KNF to 3.7KNF 3% FR-E720-5.5KNF or higher
FR-E740-0.4KNF or higher 2%
(2) When using the brake resistor (MYS type) at 100% torque / 6%ED (FR-E720-3.7KNF only)
ySet "1" in Pr. 30. ySet “6%” in Pr. 70.
ySet "1" in Pr. 30. ySet Pr. 70 as follows.
7.5K or lower 10% 11K, 15K 6%


Ratio of the brake duty to the Pr. 70 setting (%)
y[RB] appears on the operation panel when 85% of the
regenerative brake duty set in Pr. 70 is reached. If the regenerative brake duty reaches 100% of the Pr. 70
setting, a regenerative overvoltage (E.OV1 to E.OV3) occurs.

y Refer to page 25 to 28 for connecting the brake resistor (MRS type, MYS type), high-duty brake resistor (FR-ABR) and brake unit
The value set in Pr. 70 must not exceed the setting of the brake resistor used. Otherwise, the resistor can overheat.
Pr. 57 Restart coasting time Refer to page 151

5.10.3 Stop selection (Pr. 250)

Used to select the stopping method (deceleration to a stop or coasting) when the start signal turns OFF. Used to stop the motor with a mechanical brake, etc. together with switching OFF of the start signal.
0 to 100s The start signal is turned OFF, and the motor coasts to a stop after the
specified time period. 9999 When the start signal is turned OFF, the motor decelerates to stop. 1000s to 1100s,
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)

ySet Pr. 250 to "9999" (initial value) or "8888".
yThe motor decelerates to a stop when the start signal
Deceleration time (Time set in Pr. 8, etc.)
(STF/STR) turns OFF.
Output is shut off when set time elapses after start signal turned OFF Pr. 250
yUse Pr. 250 to set the time from when the start signal
turns OFF until the output is shut off.
yThe output is shut off when the time set in Pr. 250 has
elapsed after the start signal had turned OFF. The motor
coasts to a stop. yThe RUN signal turns OFF when the output stops.
y Stop selection is invalid when the following functions are activated.
y Power failure stop function (Pr. 261)
y PU stop (Pr. 75)
y When setting of Pr. 250 is not 9999, acceleration/deceleration is performed according to the frequency command, until start
signal is OFF and output is shutoff.
y When the start signal is turned ON again during motor coasting, the motor starts at Pr. 13 Starting frequency.
Pr .7 Acceleration time, Pr. 8 Deceleration time Refer to page 116 Pr. 13 Starting frequency Refer to page 119
Parameters referred to

5.10.4 Stop-on contact control function (Pr. 6, Pr. 48, Pr. 270, Pr. 275, Pr. 276)
GP MFVC GP MFVC GP MFVC
To ensure accurate positioning at the upper limit etc. of a lift, stop-on-contact control causes a mechanical brake to be closed while the motor is developing a holding torque to keep the load in contact with a mechanical stopper etc. This function suppresses vibration which is liable to occur when the load is stopped upon contact in vertical motion applications, ensuring steady precise positioning.
Value Setting Range Description
6 Multi-speed setting (low speed) 10Hz 0 to 400Hz Sets the output frequency for stop-on-contact control.
48∗1 Second stall prevention operation current 9999 0 to 200% Sets the stall prevention operation level for stall prevention operation level. 9999 Pr. 22 setting
270∗1 Stop-on contact control selection 0 0 Normal operation 1 Stop-on-contact control
275∗1, ∗2 Stop-on contact excitation current low- speed multiplying factor
9999 0 to 300% Set the force (holding torque) for stop-on-contact control. Normally set 130% to 180%. 9999 Without compensation
276∗1 PWM carrier frequency at stop-on contact 9999 0 to 9 Sets a PWM carrier frequency for stop-on-contact control. 9999 As set in Pr. 72 PWM frequency selection.
∗1 These parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)
∗2 These parameters allow their settings to be changed during operation even if "0" (initial value) is set in Pr. 77 Parameter write selection.

* Goes into stop-on-contact control when both RL and RT switches are ON. RL and RT may be switched ON in any order with any time difference.
(a) Acceleration time (Pr. 7 ) (b) Deceleration time (Pr. 8 ) (c) Second deceleration time (Pr. 44/Pr. 45 )
(2) Set stop-on-contact control y Make sure that the inverter is in the Network operation mode. (Refer to page 50) y Select Advanced magnetic flux vector control or General-purpose magnetic flux vector control. y Set "1" in Pr. 270 Stop-on contact control selection. y Set output frequency during stop-on-contact control in Pr. 6 Multi-speed setting (low speed).
The frequency should be as low as possible (about 2Hz). If it is set to more than 30Hz, the operating frequency will be 30Hz. y When both the RT and RL signals are switched ON, the inverter starts the stop-on-contact control, in which operation is
performed at the frequency set in Pr. 6 independently of the preceding speed.
y By increasing the Pr. 275 setting, the low-speed (stop-on-contact) torque increases, but overcurrent fault (E.OCT) may
occur or the machine may oscillate in a stop-on-contact state. y The stop-on-contact function is different from servo-lock function, and if used to stop or hold a load for an extended
period, this function can cause the motor to overheat. After a stop, immediately change to a mechanical brake to hold the load. y Under the following operating conditions, the stop-on-contact function is invalid:
PU operation (Pr. 79), Jog operation, remote setting function operation (Pr. 59), automatic acceleration/deceleration operation (Pr. 292)


(both RL and RT are ON) Output frequency Multi-speed, setting frequency (Refer to page 58) Pr. 6 setting Stall prevention operation
(either RL or RT is OFF or both are OFF)
(Pr. 22 when Pr. 48 = "9999") Excitation current low
speed scaling factor — Only Pr. 275 (0 to 300%) is compensated
Carrier frequency Pr. 72 setting Pr. 276 setting when output frequency is 3Hz
or less (Pr. 72 when Pr. 276 = "9999") Fast-response current
(4) Set frequency when stop-on-contact control (Pr. 270 = 1) is selected
y The following table lists the frequencies set when the input terminals (RH, RM, RL, RT, JOG) are selected together.
Bold frame indicates stop-on-contact control is valid.
y Stop-on-contact control is invalid when remote setting function is selected (Pr. 59 = 1 to 3).
Input Signal ({ = ON) Set Frequency RH RM RL RT { Pr. 4 Multi-speed setting (high speed)
{ Pr. 5 Multi-speed setting (middle speed) { Pr. 6 Multi-speed setting (low speed) { Depends on the set frequency. (Refer to page 58)
{ { Pr. 26 Multi-speed setting (speed 6) { { Pr. 25Multi-speed setting (speed 5) { { Pr. 4 Multi-speed setting (high speed)
{ { Pr. 24 Multi-speed setting (speed 4) { { Pr. 5 Multi-speed setting (middle speed) { { Pr. 6 Multi-speed setting (low speed)
{ { { Pr. 6 Multi-speed setting (low speed) { { { Pr. 6 Multi-speed setting (low speed) { { { Pr. 26 Multi-speed setting (speed 6)
{ { { Pr. 27 Multi-speed setting (speed 7) { Pr. 6 Multi-speed setting (low speed)
Depends on the set frequency. (Refer to page 58)
Pr. 4 to Pr. 6, Pr. 24 to Pr. 27 (multi-speed setting) Refer to page 111 Pr. 15 Jog frequency Refer to page 171 Pr. 48 Second stall prevention operation current Refer to page 101 Pr. 59 Remote function selection Refer to page 113 Pr. 72 PWM frequency selection Refer to page 163 Pr. 292 Automatic acceleration/deceleration Refer to page 121
Parameters referred to

5.11 I/O signal control

Purpose Parameter that should be Set Refer to Page Operation of start signals (STF, STR signal) — 141
Setting MRS signal (output shutoff) to NC contact specification MRS input selection Pr. 17 143
Detection of output current Output current detection Zero current detection Pr. 150 to Pr. 153 145
yThe forward/reverse rotation signals (STF/STR) are used as start and stop signals. Turn ON either of the forward and
reverse rotation signals to start the motor in the corresponding direction. Switch both OFF (or both ON) of the start signals during operation to decelerate the inverter to a stop. yThe speed setting signal may either be given by Pr. 4 to Pr. 6 Multi-speed setting (high, middle, low speeds), etc.

y When Pr. 250 is set to any of "0 to 100", turning OFF the start command coasts the inverter to a stop. (Refer to page 138)
Pr. 4 to Pr. 6 (multi-speed setting) Refer to page 111 Pr. 250 Stop selection Refer to page 138

5.11.2 Reset cancel signal (READY signal) and inverter running signal (RUN signal)
ON OFF
STF
ON
RH
DC injection brake operation point
DC injection brake operation
Pr. 13 Starting frequency
READY
RUN ON OFF
y When the reset operation of the inverter is canceled, reset cancel signal (READY) is output. y When the output frequency of the inverter rises to or above Pr. 13 Starting frequency , the output of the inverter running signal
(RUN) is turned ON. During an inverter stop or DC injection brake operation, the output is OFF.
OFF
ON
ON
ON
OFF
READY OFF ON
RUN OFF ON OFF OFF OFF ON
∗When a fault occurs, the MRS signal is ON, or the safety stop function is active.

5.11.3 Second function selection signal (RT signal)
y When the RT signal turns ON, the second function becomes valid. y The second function has the following applications.
(a) Switching between normal use and emergency use (b) Switching between heavy load and light load
(c) Changing of acceleration/deceleration time by broken line
(d) Switching of characteristic between the main motor and sub
Acceleration time is reflected
RH
RM
When the RT signal is ON, the following second functions are selected at the same time.
Torque boost Pr. 0 Pr. 46 94
Base frequency Pr. 3 Pr. 47 107
Acceleration time Pr. 7 Pr. 44 116
Deceleration time Pr. 8 Pr. 44, Pr. 45 116
Electronic thermal O/L relay Pr. 9 Pr. 51 123
Stall prevention Pr. 22 Pr. 48 101
Applied motor Pr. 71 Pr. 450 125
The inverter output can be shut off by the MRS signal. Also, logic for the MRS signal can be selected.
Number Name Initial Value Setting Range Description
17 MRS input selection 0 0, 4 Normally open input
2 Normally closed input (NC contact input specifications) The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)
yTurning ON the output shutoff signal (MRS) during inverter running
The motor coasts to stop
shuts off the output immediately. yMRS signal may be used as described below.
(a) When mechanical brake (e.g. electromagnetic brake) is used to stop
The inverter output is shut off when the mechanical brake operates. (b) To provide interlock to disable operation by the inverter
With the MRS signal ON, the inverter cannot be operated if the start signal is entered into the inverter.
(c) Coast the motor to a stop.
ON
When the start signal is turned OFF, the inverter decelerates the
motor to a stop in the preset deceleration time, but when the MRS signal is turned ON, the motor coasts to a stop.
y When Pr. 17 is set to "2", the MRS signal (output stop) can be changed
to the normally closed (NC contact) input specification. When the MRS
signal turns ON (opens), the inverter shuts off the output.

5.11.5 Detection of output frequency (SU, FU signal, Pr. 41 to Pr. 43)
The inverter's output frequency is detected, and the signals are output through FL remote communication.
Number Name Initial Value Setting Range Description
10% 0 to 100% Level where the SU signal turns ON.
6Hz 0 to 400Hz Frequency where the FU signal turns ON.
9999 0 to 400Hz Frequency where the FU signal turns ON in reverse
rotation.
9999 Same as Pr. 42 setting
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)
Set frequency Adjustment range Pr.41
yWhen the output frequency reaches the set frequency, the
up-to-frequency signal (SU) is output. yThe Pr. 41 value can be adjusted within the range 0% to
±100% on the assumption that the set frequency is 100%. yThis parameter can be used to ensure that the running
frequency has been reached to provide the operation start signal etc. for related equipment.
ON
SU
(2) Output frequency detection
(FU signal, Pr. 42, Pr. 43 )
yThe output frequency detection signal (FU) is output when
the output frequency reaches or exceeds the Pr. 42 setting. yThis function can be used for electromagnetic brake
Pr.42
Pr.43
operation, open signal, etc. yFrequency detection that is dedicated to reverse operation
use can be set by setting detection frequency to Pr. 43. This function is effective for switching the timing of
electromagnetic brake operation between forward rotation (rise) and reverse rotation (fall) during vertical lift operation,
etc. yWhen Pr. 43 ≠ "9999", the Pr. 42 setting is used for forward
rotation and the Pr. 43 setting is used for reverse rotation.
y All signals are OFF during DC injection brake.
y The output frequency to be compared with the set frequency is the output frequency before slip compensation is performed.

5.11.6 Output current detection function (Y12 signal, Y13 signal, Pr. 150 to Pr. 153)
The output current is detected while the inverter is running, and the signals are output through FL remote communication.
Number Name Initial Value Setting
150 Output current detection level 150% 0 to 200% 100% is the rated inverter current.
Output current detection period. The time from when the output current has risen above the setting until the output current detection signal (Y12) is output.
151 Output current detection signal delay time 0s 0 to 10s
152 Zero current detection level 5% 0 to 200% The rated inverter current is assumed to be 100%.
153 Zero current detection time 0.5s 0 to 1s Period from when the output current drops below the Pr. 152 value until the zero current detection signal (Y13) is output.
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)

yThe output current detection function can be used for
excessive torque detection, etc. yIf the output current remains higher than the Pr.150 setting for
longer than the time period set in Pr.151 in the inverter operation using FL remote communication, the output
current detection signal (Y12) is output. yWhen the Y12 signal turns ON, the ON state is held for
approximately 100ms.
yIf the output current remains lower than the Pr.152 setting for
longer than the time period set in Pr.153 in the inverter
operation using FL remote communication, the zero current detection signal (Y13) is output.
yWhen the inverter's output current falls to "0", torque will not
be generated. This may cause a drop due to gravity when
the inverter is used in vertical lift application. To prevent this, the Y13 signal can be output from the
inverter to close the mechanical brake when the output current has fallen to "zero".
∗The zero current detection signal (Y13) holds the
signal for approximately 100ms once turned ON.
PARAMETERS
y This function is also valid during execution of the offline auto tuning. y The response time of Y12 and Y13 signals is approximately 0.1s. Note that the response time changes according to the load
condition. y When Pr. 152 = "0", detection is disabled.
The zero current detection level setting should not be too low, and the zero current detection time setting not too long. Otherwise, the detection signal may not be output when torque is not generated at a low output current.
To prevent the machine and equipment from resulting in hazardous conditions detection signal, install a safety backup such as an emergency brake even the zero current detection function is set valid.
Offline auto tuning Refer to page 127
Parameter · Range Description · Parameters referred to

5.12 Monitor display and monitor output signal

Page Display motor speed Set speed Speed display and speed setting Pr. 37 146
Change the monitored item displayed on the operation panel
5.12.1 Speed display and speed setting (Pr. 37)

The monitor display and frequency setting of the operation panel can be changed to the machine speed.
37 Speed display 0 0 Frequency display, setting 0.01 to 9998∗ Machine speed at 60Hz.
The above parameters can be set when Pr. 160User group read selection = "0". (Refer to page 167)
∗The maximum value of the setting range differs according to the Pr. 1 Maximum frequency (Pr.18 High speed maximum frequency) and it can be calculated from the
following formula.
Maximum setting value of Pr. 37 < 16777.215 × 60 (Hz)
Setting value of Pr. 1 (Pr.18) (Hz)
y To display the machine speed, set in Pr. 37 the machine speed for 60Hz operation.
For example, when Pr. 37 = "1000", "1000" is displayed on the output frequency and set frequency monitor when the running frequency is 60Hz. When running frequency is 30Hz, "500" is displayed.
Pr. 37 Setting Output Frequency
Monitor Frequency Setting Parameter Setting
0 (initial value) Hz 0.01 to 9998 Machine speed ∗1 Machine speed ∗1 Machine speed ∗1
∗1 Machine speed conversion formula Pr. 37 × frequency/60Hz ∗2 Hz is displayed in 0.01Hz increments and machine speed is in 0.001.
y Under V/F control, the output frequency of the inverter is displayed in terms of synchronous speed, and therefore,
displayed value = actual speed + motor slip. The display changes to the actual speed (estimated value calculated based on the motor slip) when Advanced magnetic flux vector control was selected or slip compensation was valid. y Since the panel display of the operation panel is 4 digits in length, the monitor value of more than "9999" is displayed " ". y While the machine speed is displayed on the monitor, values of other parameters related to speed (Pr. 1 , etc.) are in
frequency increments. Set other parameters (Pr. 1, etc) related to speed in increments of frequency. y Due to the limitations on the resolution of the set frequency, the indication in the second decimal place may differ
from the setting. y When frequency or set frequency is monitored through FL remote communication, frequency is displayed for
monitor description regardless of Pr. 37 setting.
Make sure that the running speed setting is correct.
Otherwise, the motor might run at extremely high speed, damaging the machine.
Pr. 1 Maximum frequency, Pr.18 High speed maximum frequency Refer to page 105 Pr. 52 DU/PU main display data selection Refer to page 147 Pr. 800 Control method selection Refer to page 93
Set Frequency · Monitor · Parameters referred to

5.12.2 Monitor display selection of the operation panel (Pr. 52, Pr. 170, Pr. 171, Pr. 268, Pr. 563, Pr. 564)
The monitor to be displayed on the main screen of the operation panel can be selected.
Number Name Initial Value Setting Range Description
Select the monitor to be displayed on the
0, 5, 7 to 12, 14, 20,
operation panel.
23 to 25, 55, 61, 62,
Refer to the following table for monitor
description.
0 Set "0" to clear the watt-hour meter monitor.
10 Set the maximum value for the monitoring from
170 Watt-hour meter clear 9999
communication to 9999kWh.
9999 Set the maximum value for the monitoring from
communication to 65535kWh.
Set "0" in the parameter to clear the operation
171 Operation hour meter clear 9999 0, 9999
time monitor.
Setting 9999 does not clear.
0 Displayed as integral value
1 Displayed in 0.1 increments.
The numbers of cumulative energization time
0 0 to 65535
monitor exceeded 65535h is displayed.
0 0 to 65535
The numbers of operation time monitor
exceeded 65535h is displayed. (Reading only)
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)
∗1 This parameter allows its setting to be changed during operation in any operation mode even if "0" (initial value) is set in Pr. 77 Parameter write selection.
∗2 The setting values "56 and 57" are for manufacturer setting. Do not set.
ySet the monitored item to be displayed on the operation panel and parameter unit (FR-PU04/FR-PU07) in Pr. 52 DU/PU
main display data selection. yRefer to the following table and set the monitored item to be displayed.
Monitored Item Unit Pr. 52 Setting Description
Output frequency 0.01Hz 0/100 Displays the inverter output frequency.
Output current 0.01A 0/100 Displays the inverter output current effective value.
Output voltage 0.1V 0/100 Displays the inverter output voltage.
Fault display — 0/100 Displays 8 past faults individually.
Frequency setting value 0.01Hz 5 Displays the set frequency.
Motor torque 0.1% 7 Displays the motor torque in % on the assumption that the rated motor torque is 100%. (Displays 0% during V/F control)
Converter output voltage 0.1V 8 Displays the DC bus voltage value.
Regenerative brake duty 0.1% 9 Brake duty set in Pr. 30, Pr. 70
Electronic thermal relay function load factor 0.1% 10 Displays the thermal cumulative value on the assumption that the thermal operation level is 100% (Larger thermal between the motor thermal and transistor thermal). ∗4
Output current peak value 0.01A 11 Holds and displays the peak value of the output power monitor. (Cleared at every start)
Converter output voltage peak value 0.1V 12 Holds and displays the peak value of the DC bus voltage value. (Cleared at every start)
Output power 0.01kW 14 Displays the power on the inverter output side
Cumulative energization time ∗1 1h 20 Adds up and displays the energization time after inverter shipment. You can check the numbers of the monitor value exceeded 65535h with Pr. 563.
Actual operation time ∗1, ∗2 1h 23 Adds up and displays the inverter operation time. You can check the numbers of the monitor value exceeded 65535h with Pr. 564. Can be cleared by Pr. 171. (Refer to page 149)
Motor load factor 0.1% 24 Displays the output current value on the assumption that the inverter rated current value is 100%. Monitor value = output power monitor value/rated inverter current 100 [%]

Monitored Item Unit Pr. 52 Setting Description
Cumulative power ∗3 0.01kWh ∗5 25 Adds up and displays the power amount based on the output power monitor. Can be cleared by Pr. 170. (Refer to page 149)
Inverter output terminal monitor — 55 Displays the ON/OFF statuses of the inverter output terminals and FL remote communication virtual terminals (FU, ALM signal) on the operation panel. (Refer to page 149 for details)
Motor thermal load factor 0.1% 61 Motor thermal heat cumulative value is displayed. (Motor overload trip (E.THM) at 100%)
Inverter thermal load factor 0.1% 62 Transistor thermal heat cumulative value is displayed. (Inverter overload trip (E.THT) at 100%)
Adds up and displays the power amount based on the output power monitor. (dedicated monitor for FL remote communication) Can be cleared by Pr. 170. (Refer to page 149)
Cumulative power 2 0.01kWh —
∗1 The cumulative energization time and actual operation time are accumulated from 0 to 65535 hours, then cleared, and accumulated again from 0. When the operation panel is used, the time is displayed up to 65.53 (65530h) in the indication of 1h = 0.001, and thereafter, it is added up from 0. ∗2 Actual operation time is not accumulated when the cumulative operation time is less than 1h until turning OFF of the power supply. ∗3 Since the panel display of the operation panel is 4 digits in length, the monitor value of more than "9999" is displayed " ". ∗4 Larger thermal value between the motor thermal and transistor thermal is displayed. A value other than 0% is displayed if the surrounding air temperature (heatsink temperature) is high even when the inverter is at a stop. ∗5 The unit is 1kWh when monitoring through FL remote communication.
y By setting "0" in Pr. 52, the monitoring of output speed to fault display can be selected in sequence by .
y When the operation panel is used, the displayed units are Hz and A only and the others are not displayed.
y The monitor set in Pr. 52 is displayed in the third monitor position. However, change the output current monitor for the motor
load factor.
∗The monitor displayed at powering on is the first monitor. Display the monitor you want to display on the first monitor and hold
down for 1s. (To return to the output frequency monitor, hold down for 1s after displaying the output frequency
monitor.)
Power-on monitor (first monitor) Second monitor Third monitor Fault monitor
Output current monitor Output voltage monitor Output frequency monitor
Example)When Pr. 52 is set to "20" (cumulative energization time), the monitor is displayed on the operation panel as described
below.
Power-on monitor (first monitor) Second monitor Third monitor Fault monitor
Output current monitor Cumulative energization time monitor Output frequency monitor

y When "100" is set in Pr. 52, the set frequency
and output frequency are displayed during stop
and operation respectively. (LED of Hz flickers during stop and is lit during operation.)
∗ The set frequency displayed indicates the frequency to be output when the start
command is ON. Different from the frequency setting displayed when Pr. 52 = "5", the value based on maximum/minimum frequency and frequency jump is displayed.
y During an error, the output frequency at error occurrence appears. y During MRS signal is ON, the values displayed are the same as during a stop. y During offline auto tuning, the tuning status monitor has priority.
Initial Value · With fault · With fault

yWhen Pr.52 = "55," statuses of the output terminals and FL remote communication virtual terminals (FU, ALM signal) are
monitored on the operation panel.
yThe I/O terminal monitor is displayed on the third monitor. yThe LEDs are ON when a signal is input to terminal Y0 and when the signals FU and ALM are input. The LEDs are OFF
when no signal is input to terminal Y0 nor the signals FU and ALM. The center line of the LED is always ON.
Center line is always ON
(4) Cumulative power/cumulative power 2 monitor and clear (Pr. 170)
yMonitored values are accumulated in the cumulative power monitor (Pr.52 = "25") or in the cumulative power monitor 2
(dedicated to FL remote communication), and the displayed values are updated every hour.
yThe operation panel and FL remote communication display increments and display ranges are as indicated below.
Operation Panel ∗1 FL remote Communication
Range Monitor Unit for
Range Monitor Unit for
Cumulative Power 2 Pr. 170 = 10 Pr. 170 = 9999
0 to 99.99kWh 0.01kWh
0 to 9999kWh 0 to 65535kWh
(initial value) 1kWh 0.01kWh 100.0 to 999.9kWh 0.1kWh
1000 to 9999kWh 1kWh
∗1 Power is measured in the range of 0 to 9999.99kWh, and displayed in 4 digits.
When the monitor value exceeds "99.99", a carry occurs, e.g. "100.0", so the value is displayed in 0.1kWh increments.
yWriting "0" in Pr.170 clears the cumulative power monitor and the cumulative power 2 monitor.
y If "0" is written to Pr. 170 and Pr. 170 is read again, "9999" or "10" is displayed.
(5) Cumulative energization time and actual operation time monitor (Pr. 171, Pr. 563, Pr. 564)
yCumulative energization time monitor (Pr. 52 = "20") accumulates energization time from shipment of the inverter every
one hour.
yOn the actual operation time monitor (Pr. 52 = "23"), the inverter running time is added up every hour. (Time is not added
up during a stop.)
yIf the monitored value exceeds 65535, it is added up from 0. You can check the numbers of cumulative energization time
monitor exceeded 65535h with Pr. 563 and the numbers of actual operation time monitor exceeded 65535h with Pr. 564.
yWriting "0" to Pr. 171 clears the cumulative power monitor. (The cumulative time monitor can not be cleared.)
y The cumulative energization time does not increase if the power is ON for less than an hour.
y The actual operation time does not increase if the cumulative running time during power-ON status is less than an hour.
y If "0" is written to Pr. 171 and Pr. 171 is read again, "9999" is always displayed. Setting "9999" does not clear the actual operation
time meter.
Monitor Unit for · Cumulative Power · Cumulative Power

yAs the operation panel display is 4 digits long, the decimal places may vary at analog input, etc. The decimal places can
be hidden by selecting the decimal digits.
In such a case, the decimal digits can be selected by Pr. 268.
Pr. 268 Setting Description
9999 (initial value) No function
For the first or second decimal places (0.1 increments or 0.01 increments) of the monitor, numbers in the first
decimal place and smaller are rounded to display an integral value (1 increments).The monitor value smaller than
0.99 is displayed as 0.
1 When 2 decimal places (0.01 increments) are monitored, the 0.01 decimal place is dropped and the monitor
displays the first decimal place (0.1 increments). The monitored digits in 1 increments are displayed as they are.
y The number of display digits on the cumulative energization time (Pr. 52 = "20"), actual operation time (Pr. 52 = "23"), and
cumulative power (Pr. 52 = "25") does not change.
Pr. 30 Regenerative function selection, Pr. 70 Special regenerative brake duty Refer to page 136 Pr. 37 Speed display Refer to page 146
Parameters referred to

5.13 Operation selection at power failure and instantaneous power failure
Purpose Parameter that should be Set Refer to Page At instantaneous power failure occurrence, restart inverter without stopping motor
Pr. 57, Pr. 58, Pr. 96, Pr. 162, Pr. 165, Pr. 298,
Pr. 299, Pr. 611
When undervoltage or a power failure occurs, the inverter can be decelerated to a stop.
Pr. 261 156
5.13.1 Automatic restart after instantaneous power failure/flying start (Pr. 57, Pr. 58, Pr. 96, Pr. 162, Pr. 165, Pr. 298, Pr. 299, Pr. 611)
You can restart the inverter without stopping the motor in the following cases: y When power comes back on after an instantaneous power failure y When motor is coasting at start
Number Name Initial Value
1.5K or lower 1s 2.2K to 7.5K 2s 11K or higher ...3s The above times are coasting time.
57 Restart coasting time 9999
0.1 to 5s Waiting time for inverter-triggered restart after an instantaneous power failure. 9999 No restart 58 Restart cushion time 1s 0 to 60s Voltage starting time at restart.
0 Offline auto tuning is not performed
1 Advanced magnetic flux vector control Offline auto tuning is performed without motor running (all motor constants) (Refer to page 95)
11 For General-purpose magnetic flux vector control Offline auto tuning is performed without motor running (motor constants (R1) only) (Refer to page 98)
96 Auto tuning setting/status 0
21 Offline auto tuning (tuning performed without motor running) for V/F control and automatic restart after instantaneous power failure (with frequency search)
0 With frequency search 1 Without frequency search (reduced voltage system) 10 Frequency search at every start 11 Reduced voltage at every start
150% 0 to 200% Considers the rated inverter current as 100% and sets the stall prevention operation level during restart operation.
When offline auto tuning is performed under V/F control, frequency search gain necessary for frequency search for automatic restart after instantaneous power failure is set as well as the motor constants (R1).
298 Frequency search gain 9999 0 to 32767
9999 Uses the Mitsubishi motor (SF-JR, SF-HR, SF-JRCA, SF-HRCA) constants
0 Without rotation direction detection 1 With rotation direction detection
When Pr. 78 = 0, With rotation direction detection When Pr. 78 = 1, 2 Without rotation direction detection
9999 0 to 3600s Acceleration time to reach Pr. 20 Acceleration/deceleration reference frequency at a restart.
9999 Acceleration time for restart is the normal acceleration time (e.g. Pr. 7) The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)
Parameter · Setting · Range Description

When Pr. 162 = 1, 11 (without frequency search) (1) Automatic restart operation selection

z Without frequency search
When Pr. 162 = "1 (initial value) " or "11", automatic restart operation is performed in a reduced voltage system, where the voltage is gradually risen with the output frequency unchanged from prior to an instantaneous power failure independently of the coasting speed of the motor.
y This system stores the output frequency and
rotation direction prior to an instantaneous power failure and restart using the stored value. Therefore, if the instantaneous power failure time exceeds 0.2s and the stored value cannot be retained, the inverter starts at Pr. 13 Starting frequency (initial value = 0.5Hz) in the starting direction upon power restoration.
Coasting time Pr. 57 setting Restart cushion time (Pr. 58 setting)
* The output shut off timing differs according to the load condition.
When Pr. 162 = 0, 10 (with frequency search) z With frequency search

When "0 or 10" is set in Pr. 162, the inverter smoothly starts
after detecting the motor speed upon power restoration. (The motor capacity should be equal to or one rank lower than the inverter capacity) When using the frequency search, perform offline auto tuning. (Refer to page 127 for Advanced magnetic flux vector control, General-purpose magnetic flux vector control and page 153 for V/F control.) yDuring reverse rotation, the inverter can be restarted
smoothly as the direction of rotation is detected. yYou can select whether to make rotation direction
detection or not with Pr. 299 Rotation direction detection selection at restarting. When capacities of the motor and inverter differ, set "0" (without rotation direction detection) in Pr. 299.
Acceleration time at a restart (Pr. 611 setting)
* The output shut off timing differs according to the load condition.
Pr. 299 Setting Pr. 78 Setting 0 1 2 9999 { × × 0 (initial value) × × × 1 { { {
{: the rotation direction is detected. ×: the rotation direction is not detected.
y Speed detection time (frequency search) changes according to the motor speed. (maximum 100ms) y When the inverter capacity is two rank or more larger than the motor capacity, the inverter may not start due to overcurrent trip (E.OC ). y If two or more motors are connected to one inverter, the function does not operate properly. (The inverter does not start smoothly.) y When reverse rotation is detected when Pr. 78 = "1" (reverse rotation disabled), the rotation direction is changed to forward
rotation after decelerates in reverse rotation when the start command is forward rotation. The inverter will not start when the start command is reverse rotation.
y When automatic restart operation after instantaneous power failure is activated while the motor is running at a low speed (less
than 10Hz), the motor restarts in the direction prior to instantaneous power failure without detecting the rotation direction (Pr. 299 Rotation direction detection selection at restarting = "1"). y If the frequency search result exceeds the set frequency, the output frequency is limited at the set frequency. y When the wiring length exceeds 100m, select without frequency search (Pr. 162 = "1, 11").
z Restart operation at every start
When Pr. 162 = "10 or 11", automatic restart operation is also performed every start, in addition to the automatic restart after instantaneous power failure. When Pr. 162 = "0", automatic restart operation is performed at the first start after power supply ON, but not performed at the second time or later.

yCoasting time is the time from when the motor speed is detected until automatic restart control is started.
ySet Pr. 57 to "0" to perform automatic restart operation.
The coasting time is automatically set to the value below. Generally this setting will pose no problems.
1.5K or lower ...1s
2.2K to 7.5K 2s
11K or higher 3s
yOperation may not be performed well depending on the magnitude of the moment of inertia (J) of the load or running
frequency. Adjust the coasting time between 0.1s and 5s according to the load specifications. (3) Restart cushion time (Pr. 58)
yCushion time is the length of time taken to raise the voltage appropriate to detected motor speed (output frequency prior to
instantaneous power failure when Pr. 162 = "1, 11") from 0V. yNormally the initial value need not be changed for operation, but adjust it according to the magnitude of the moment of
inertia (J) of the load or torque.
Pr. 58 Time
yUsing Pr. 165, you can set the stall prevention operation level at a restart. yUsing Pr. 611, you can set the acceleration time until Pr.20 Acceleration/deceleration reference frequency is reached when
automatic restart operation is performed besides the normal acceleration time.
y If the Pr. 21 Acceleration/deceleration time increments is changed, the setting increments of Pr. 611 remain unchanged.
yWhen automatic restart after instantaneous power failure operation (with frequency search) is valid at V/F control, perform
offline auto tuning. yPerform offline auto tuning during V/F control in the following order to set Pr. 298 Frequency search gain automatically.
(Refer to page 127 during Advanced magnetic flux vector control and General-purpose magnetic flux vector control.)
zBefore performing offline auto tuning
Check the following before performing offline auto tuning.
yThe inverter is under V/F control yA motor should be connected. Note that the motor should be at a stop at a tuning start.
yThe motor capacity should be equal to or one rank lower than the inverter capacity. (note that the capacity is 0.1kW or
yA high-slip motor, high-speed motor and special motor cannot be tuned. (The maximum frequency is 120Hz.) yEven if tuning is performed without motor running (Pr. 96 Auto tuning setting/status = "21"), the motor may run slightly.
Therefore, fix the motor securely with a mechanical brake, or before tuning, make sure that there will be no problem in safety if the motor runs (caution is required especially in vertical lift applications). Note that tuning performance is
unaffected even if the motor runs slightly. yOffline auto tuning will not be performed properly if it is performed with a surge voltage suppression filter (FR-ASF-H, FR-
BMF-H) connected between the inverter and motor. Remove it before starting tuning.
Voltage · 100% · more)

It takes approximately 9s ∗ until tuning is completed. (Excitation noise is produced during tuning.)
∗Tuning time differs according to the inverter capacity and motor type. 2) Set the rated motor current (initial value is rated inverter current) in Pr. 9 Electronic thermal O/L relay. (Refer to page 123)

SF-JR 3 SF-JR 4P 1.5kW or less 23 SF-HR 43 Others 3
SF-JRCA 4P 13 SF-HRCA 53 Others (SF-JRC, etc.) 13 Other manufacturer's standard motor — 3 Other manufacturer's constant torque motor — 13
∗1 Refer to page 125 for other settings of Pr. 71. zExecution of tuning
Before performing tuning, check the monitor display of the operation panel if the inverter is in the status for tuning. (Refer to 3) below)
change the operation mode to the PU operation mode using on the operation panel.
(When the Network operation mode is selected and "1" is set in the X12 signal (Bit 11), which gives a control input command through FL remote communication, the inverter output is shutoff. Therefore, inputting a start signal through FL remote communication does not start tuning in this condition.)
y To force tuning to end, press of the operation panel.
y X12 signal is the only valid input/output signal during the offline auto tuning.
Setting "0" in the X12 signal while tuning is being set or performed changes the operation mode to the Network operation mode forcibly. y Use the X12 signal after setting "0" (stop command) in the forward/reverse rotation command (STF/STR signal) to set
and perform tuning. y When executing offline auto tuning, input the run command after switching ON the main circuit power (R/L1, S/L2, T/
L3) of the inverter.

(4) Error end (when inverter protective function operation is activated)
Offline Auto Tuning Setting Time
Tune motor constants (R1) only (Pr. 96 = "21")
Approx. 9s (Tuning time differs according to the inverter capacity and motor type.)
zSetting

the monitor display of the operation panel returns to normal.

8 Forced end Set "21" in Pr. 96 and perform tuning again.
Set the rated current of the motor in Pr. 9.
constants have not been set.)
Perform an inverter reset and restart tuning.
y Do not change the Pr. 96 setting after completion of tuning (23). If the Pr. 96 setting is changed, tuning data is invalid.
If the Pr. 96 setting is changed, tuning must be performed again.
y The motor constants measured once in the offline auto tuning are stored as parameters and their data are held until
the offline auto tuning is performed again.
y An instantaneous power failure occurring during tuning will result in a tuning error.
After power is restored, the inverter goes into the normal operation mode.
y Any alarm occurring during tuning is handled as in the ordinary mode. Note that if a fault retry has been set, retry is
ignored.
y The set frequency monitor displayed during the offline auto tuning is 0Hz.
y Automatic restart operation will also be performed after a reset or when a retry is made by the retry function.
When automatic restart after instantaneous power failure has been selected, the motor and machine will start
suddenly (after the reset time has elapsed) after occurrence of an instantaneous power failure.
Stay away from the motor and machine. When you have selected automatic restart after instantaneous power failure function, apply in easily visible
places the CAUTION stickers supplied to the Instruction Manual (Basic).
When the start signal is turned OFF or is pressed during the restart cushion time after instantaneous
power failure, deceleration starts after Pr. 58 Restart cushion time has elapsed.
Pr. 7 Acceleration time, Pr. 21 Acceleration/deceleration time increments Refer to page 116 Pr. 13 Starting frequency Refer to page 119 Pr. 65, Pr. 67 to Pr. 69 Retry function Refer to page 158 Pr. 71 Applied motor Refer to page 125 Pr. 78 Reverse rotation prevention selection Refer to page 167
Parameters referred to

5.13.2 Power-failure deceleration stop function (Pr. 261)
When a power failure or undervoltage occurs, the inverter can be decelerated to a stop or can be decelerated and re- accelerated to the set frequency.
Coasts to stop.
When undervoltage or power failure occurs, the inverter output
is shut off.
1 When undervoltage or a power failure occurs, the inverter can
be decelerated to a stop.
When undervoltage or a power failure occurs, the inverter can
be decelerated to a stop.
If power is restored during a power failure, the inverter
accelerates again.
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)
ON OFF
yWhen Pr. 261 is set to "1" or "2", the inverter decelerates to a
stop if an undervoltage or power failure occurs.
Pr. 261 = 0
Pr. 261 = 1, 2
failure
yWhen undervoltage or power failure has occurred, the output
frequency is decreased and controlled so that the converter
circuit (DC bus) voltage is constant and decreased to 0Hz to stop.
Pr. 261 = 1 (3) Power failure stop function (Pr. 261 = "1")
yIf power is restored during power failure deceleration,
During deceleration at occurrence of power failure
deceleration to a stop is continued and the inverter remains
stopped. To restart, turn OFF the start signal once, then turn it ON again.
During stop at occurrence of power failure
REMARKS
y When automatic restart after instantaneous power failure is selected (Pr. 57 ≠ "9999"), power failure stop function is invalid and
automatic restart operation after instantaneous power failure is valid.
y When the power failure deceleration to stop function is active (Pr.261 = "1"), the inverter will not start by turning the power ON
while the start signal (STR/STF) is being input through FL remote communication. After switching ON the power, turn OFF the
start signal once and then ON again to make a start.
Not started as inverter is stopped due to power failure
OFF ON

(4) Operation continuation at instantaneous power failure function (Pr. 261 = "2")
yWhen power is restored during deceleration after a power failure, acceleration is made again up to the set frequency. yWhen this function is used in combination with the automatic restart after instantaneous power failure function(Pr.57 ≠
"9999"), deceleration can be made at a power failure and acceleration can be made again after power restoration.


When power is restored during deceleration at occurrence of power failure
When used with automatic restart after instantaneous power failure
∗ Acceleration time depends on Pr. 7 (Pr. 44).
y When operation continuation at instantaneous power failure function is used, keep the starting signal (STF/STR) ON
even during instantaneous power failure. If the starting signal turns OFF during instantaneous power failure, the
inverter decelerates according to the deceleration time setting, causing the motor to coast if enough regenerative
energy is not obtained.
y During a stop or trip, the power failure stop selection is not performed.
Even if the power failure stop function is valid, some loads may cause the inverter to trip and the motor to
coast. The motor will coast if enough regenerative energy is not given from the motor to the inverter.
Pr. 57 Restart coasting time Refer to page 151
Parameters referred to

5.14 Operation setting at fault occurrence

Purpose Parameter that should be Set Refer to Page Recover by retry operation at a fault occurrence Retry operation Pr. 65, Pr. 67 to Pr. 69 158
Earth (ground) fault detection at start Pr. 249 160
5.14.1 Retry function (Pr. 65, Pr. 67 to Pr. 69)
If a fault occurs, the inverter resets itself automatically to restart. You can also select the fault for a retry. When you have selected automatic restart after instantaneous power failure (Pr. 57 Restart coasting time ≠ 9999), restart operation is performed at the retry operation time which is the same of that of a power failure. (Refer to page 151 for the restart function.)
65 Retry selection 0 0 to 5 A fault for retry can be selected. (Refer to the next page)
0 No retry function
1 to 10 Set the number of retries at fault occurrence.
A fault output is not provided during retry operation.
Set the number of retries at fault occurrence. (The setting
value of minus 100 is the number of retries.)
A fault output is provided during retry operation.
68 Retry waiting time 1s 0.1 to 360s Set the waiting time from when an inverter fault occurs
until a retry is made. 69 Retry count display erase 0 0 Clear the number of restarts succeeded by retry.
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)
y Retry operation automatically resets a fault and restarts

the inverter at the starting frequency when the time set in
Pr. 68 elapses after the inverter is tripped. y Retry operation is performed by setting Pr. 67 to any value
other than "0". Set the number of retries at fault occurrence in Pr. 67.
y When retries fail consecutively more than the number of
times set in Pr. 67, a retry count excess fault (E.RET)
occurs, resulting in inverter trip. (Refer to retry failure example)
y Use Pr. 68 to set the waiting time from when the inverter
trips until a retry is made in the range 0.1 to 360s.
y Reading the Pr. 69 value provides the cumulative number
of successful restart times made by retry.
The cumulative count in Pr. 69 is increased by 1 when a retry is regarded as successful after normal operation
continues without faults occurring for more than four times longer than the time set in Pr. 68 after a retry start.
(When retry is successful, cumulative number of retry failure is cleared.)
y Writing "0" to Pr. 69 clears the cumulative count.

y Using Pr. 65, you can select the fault that will cause a retry to be executed. No retry will be made for the fault not indicated.
(Refer to page 194 for the fault description.)
z indicates the faults selected for retry.
Pr. 65 Setting 0 1 2 3 4 5 E.OC1 z E.OC2 z E.OC3 z E.OV1 z E.OV2 z E.OV3 z E.THM z E.THT z
Pr. 65 Setting 0 1 2 3 4 5
Retry
Retry
E. BE z z E. GF z z E.OLT z z E.OPT z z E.OP1 z z E. PE z z E.ILF z z
y The data stored as the error reset for retry is only that of the fault which occurred the first time.
y When an inverter fault is reset by the retry function at the retry time, the accumulated data of the electronic thermal
relay function, regeneration brake duty etc. are not cleared. (Different from the power-ON reset.)
y Retry is not performed if E.PE (Parameter storage device fault) occurred at power ON.
y If a fault that is not selected for a retry occurs during retry operation (retry waiting time), the retry operation stops
while the fault indication is still displayed.
When you have selected the retry function, stay away from the motor and machine when the inverter is
tripped. They will start suddenly (after the reset time has elapsed) after the inverter trip. When you have selected the retry function, apply in easily visible places the CAUTION stickers supplied with
the Instruction Manual (Basic).
Pr. 57 Restart coasting time Refer to page 151
Parameters referred to

5.14.2 Input/output phase loss protection selection (Pr. 251, Pr. 872)
You can choose whether to make Input/output phase loss protection valid or invalid. y Output phase loss protection is a function to stop the inverter output if one of the three phases (U, V, W) on the
inverter's output side (load side) is lost. y Input phase loss protection is a function to stop the inverter output if one of the three phases (R/L1, S/L2, T/L3) on the
inverter's input side is lost.
Number Name Initial Value Setting Range Description
1 0 Without output phase loss protection
1 With output phase loss protection
1 0 Without input phase loss protection
1 With input phase loss protection
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)
y If phase loss occurs during inverter running (except for during DC brake operation, or output frequency is 1Hz or less),
output phase loss protection (E.LF) activates, and inverter trips.
y When Pr. 251 is set to "0", output phase loss protection (E.LF) becomes invalid.
y When Pr. 872 is set to "1", input phase loss protection (E.ILF) is provided if a phase loss of one phase among the three
phases is detected for 1s continuously.
y If an input phase loss continues for a long time, the converter section and capacitor lives of the inverter will be
shorter.
y If the load is light or during a stop, lost phase cannot be detected because detection is performed based on the
fluctuation of bus voltage. Large unbalanced phase-to-phase voltage of the three-phase power supply may also
cause input phase loss protection (E.ILF).
y Phase loss can not be detected during regeneration load operation.
You can choose whether to make earth (ground) fault detection at start valid or invalid. Earth (Ground) fault detection is executed only right after the start signal is input to the inverter.
Protective function will not activate if an earth (ground) fault occurs during operation.
Number Name Initial Value Setting Range Description
0 0 Without earth (ground) fault detection
1 With earth (ground) fault detection
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)
y As detection is executed at start, output is delayed for approx. 20ms every start.
y If an earth (ground) fault is detected while Pr. 249 = "1," the output side earth (ground) fault overcurrent (E.GF) is activated and
the inverter trips. (Refer to page 200)
y If the motor capacity is smaller than the inverter capacity of the 5.5K or higher, earth (ground) fault detection may not be
provided.
Parameter · Parameter

5.14.4 Display and erasure of communication error occurrence count (Pr. 501)
The inverter operates as below at a communication error during FL remote communication.
The cumulative number of communication error occurrences
can be indicated.
Writing "0" erases this cumulative count.
∗The above parameter can be always read regardless of the Pr.160 User group read selection setting. (Refer to page 167)
The cumulative number of communication error occurrences can be indicated. Writing "0" to Pr.501 erases this cumulative count.
At the point of communication line error occurrence, Pr.501 display is incremented by 1.
Normal Error Count timing depending on communication line status Incremented by 1
y The communication error count occurrence is stored into RAM temporarily. Since this data is stored in EEPROM at
one-hour intervals, performing power-ON reset or inverter may cause the Pr. 501 data to be the value stored in
EEPROM the last time depending on the reset timing.
The inverter operates as below at a communication line error or a fault in the FL remote communication circuit.
z Operation at error occurrence
Communication line Decelerated to stop E.OP1 lit after stop Provided after stop FL remote communication
circuit in the inverter Decelerated to stop E.1 lit after stop Provided after stop
z Operation at error removal
Communication line Kept stopped E.OP1 kept lit Kept provided FL remote communication
circuit in the inverter Kept stopped E.1 kept lit Kept provided
y Communication line error [E.OP1] is displayed when a fault occurs on the FL remote communication line.
y The fault output indicates fault output signal (ALM signal) or alarm bit output.
y The fault record is stored into the faults history. (The fault record is written to the faults history when a fault output is
provided.)
After the error is removed, the fault indication is reset and returns to the ordinary monitor, and the faults history
returns to the preceding fault indication.
y The deceleration time is the ordinary deceleration time setting (e.g. Pr. 8, Pr. 44, Pr. 45).

5.15 Energy saving operation
Purpose Parameter that should be Set Refer to Page Energy saving operation Optimum excitation control Pr. 60 162

Without a fine parameter setting, the inverter automatically performs energy saving operation. This operation is optimum for fan and pump applications
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)
y When "9" is set in Pr. 60, the inverter operates in the Optimum excitation control mode. y The Optimum excitation control mode is a control system which controls excitation current to improve the motor efficiency
to maximum and determines output voltage as an energy saving method.
y When the motor capacity is too small as compared to the inverter capacity or two or more motors are connected to one inverter,
the energy saving effect is not expected.
y When the Optimum excitation control mode is selected, deceleration time may be longer than the setting value. Since
overvoltage alarm tends to occur as compared to the constant-torque load characteristics, set a longer deceleration
time.
y Optimum excitation control functions only under V/F control. Optimum excitation control does not function under
Advanced magnetic flux vector control and General-purpose magnetic flux vector control.
y Optimum excitation control will not be performed during an automatic restart after instantaneous power failure.
y Since output voltage is controlled by Optimum excitation control, output current may slightly increase.
Advanced magnetic flux vector control Refer to page 95 General-purpose magnetic flux vector control Refer to page 98 Pr. 57 Restart coasting time Refer to page 151
Parameters referred to

5.16 Motor noise, EMI measures, mechanical resonance

Purpose of Use Parameter that should be Set Refer to Page
Reduce mechanical resonance Speed smoothing control Pr. 653 164

72 * PWM frequency selection 1 0 to 15
1 When Pr. 72 = "0 to 5", soft-PWM is valid.
The above parameters can be set when Pr.160 User group read selection = "0". (Refer to page 167) ∗The parameters in the table allow its setting to be changed during operation even if "0" (initial value) is set in Pr. 77 Parameter write selection.
yYou can change the PWM carrier frequency of the inverter. yChanging the PWM carrier frequency produces an effect on avoiding the resonance frequency of a mechanical system or
motor or on EMI measures or on leakage current reduction caused by the PWM switching.
ySoft-PWM control is a control method that changes the motor noise from a metallic tone into an unoffending complex tone.
y Decreasing the PWM carrier frequency effect on EMI measures and on leakage current reduction, but increases
motor noise.
y When PWM carrier frequency is set to 1kHz or less (Pr.72 ≤ 1), fast response current limit may function prior to stall
prevention operation due to increase in ripple currents, resulting in insufficient torque. In such case, set fast-
response current limit operation invalid using Pr. 156 Stall prevention operation selection .
y When setting 2kHz or more in Pr. 72 to perform operation in the place where the surrounding air temperature
exceeding 40°C, caution should be taken as the rated inverter current should be reduced. (Refer to page 224)
Pr. 156 Stall prevention operation selection Refer to page 101
Parameters referred to

5.16.2 Speed smoothing control (Pr. 653)
Vibration due to mechanical resonance influences the inverter control, causing the output current (torque) unstable. In this case, the output current (torque) fluctuation can be reduced to ease vibration by changing the output frequency.
Number Name Initial Value Setting Range Description
653 Speed smoothing control 0 0 to 200% Increase or decrease the value using
100% as reference to check an effect.
The above parameters can be set when Pr. 160 User group read selection = "0".(Refer to page 167)
Output frequency Speed command
Frequency output Voltage output
Speed smoothing control Pr.653
If vibration due to mechanical resonance occurs, set 100% in Pr. 653, run the inverter at the frequency which generates
maximum vibration and check if the vibration will be reduced or not after several seconds. If effect is not produced, gradually increase the Pr. 653 setting and check the effect repeatedly until the most effective
value is set in Pr. 653.
If vibration becomes large by increasing the Pr. 653 setting, gradually decrease the Pr. 653 setting than 100% to check the effect in a similar manner.
Depending on the machine, vibration may not be reduced enough or an effect may not be produced.

5.17 Misoperation prevention and parameter setting restriction

Purpose Parameter that should be Set Refer to Page Stops from operation panel PU stop selection Pr. 75 165 Prevention of parameter rewrite Parameter write disable selection Pr. 77 166 Prevention of reverse rotation of the motor Reverse rotation prevention selection Pr. 78 167
Parameter restriction using password Password function Pr. 296, Pr. 297 169
5.17.1 Reset selection/PU stop selection (Pr. 75)
The stop function can be selected on the operation panel.

0 to 3 Pressing decelerates the motor to a
14 to 17 Pressing decelerates the motor to a
stop in the PU and Network operation modes. yThe above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167) yThis parameter allows its setting to be changed during operation in any operation mode even if "0 (initial value) or 1" is set in Pr. 77 Parameter write
selection. Also, if (all) parameter clear is executed, this setting will not return to the initial value.
ySetting Pr. 75 = "14 to 17" enables the emergency stop with the on the operation panel in the PU and Network operation
modes.
yWhen the inverter is stopped by the PU stop function, " " (PS) is displayed. A fault output is not provided.
yAfter the motor is stopped from the PU, it is necessary to perform PU stop (PS) reset to restart. PS reset can be made from
the operation panel. yCancel the PS indication and restart the operation by resetting the power or by performing an error reset of FL remote
communication.
yWhen Pr. 75 is set to any of "0 to 3", PU stop (PS display) is invalid, deceleration to a stop by is valid only in the PU
operation mode.
(2) How to restart the motor stopped by input from the PU in Network operation mode (PU stop (PS) reset method)

1)After completion of deceleration to a stop, switch OFF the STF or STR signal.
y If Pr. 250 Stop selection is set to other than "9999" to select coasting to a stop, the motor will not be coasted to a stop but
decelerated to a stop by the PU stop function during FL remote communication operation.
Do not reset the inverter while the start signal is being input. Otherwise, the motor will start instantly after resetting, leading to potentially hazardous conditions.

5.17.2 Parameter write disable selection (Pr. 77)
You can select whether write to various parameters can be performed or not. Use this function to prevent parameter values from being rewritten by misoperation.
Number Name Initial Value Setting Range Description
0 Write is enabled only during a stop.
77 Parameter write selection 0
1 Parameter can not be written.
2 Parameter write is enabled in any operation
mode regardless of operation status.
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)
Pr. 77 can be set anytime regardless of the operation mode or the operation status. However, it cannot be changed through FL remote
communication.
yParameters can be written only during a stop.
yThe shaded parameters in the parameter list (page 78) can always be written regardless of the operation mode and
operating status. However, Pr. 72 PWM frequency selection, Pr. 240 Soft-PWM operation selection, and Pr. 275 Stop-on contact
excitation current low-speed multiplying factor can be written when the inverter is running in the PU operation mode, but cannot be written in the Network operation mode.
yParameter write is not enabled.
(Read is enabled.) yParameter clear and all parameter clear cannot be
22 Stall prevention operation level
performed, either. yThe parameters given on the right can be written if Pr. 77 =
75 Reset selection/PU stop selection
77 Parameter write selection
160 User group read selection
"1". (Note that the Pr.77 setting cannot be changed through FL remote communication.)
296 Password lock level
yParameters can always be written. yThe following prameters cannot be written when the inverter is running if Pr. 77 = "2". Stop the inverter when changing their
parameter settings.
23 Stall prevention operation level compensation factor at double speed
83 Rated motor voltage
84 Rated motor frequency
40 RUN key rotation direction selection
90 to 94 (Motor constants)
48 Second stall prevention operation current
96 Auto tuning setting/status
60 Energy saving control selection
277 Stall prevention operation current switchover
66 Stall prevention operation reduction starting frequency
293 Acceleration/deceleration separate selection
298 Frequency search gain
450 Second applied motor
800 Control method selection
81 Number of motor poles
82 Motor excitation current

5.17.3 Reverse rotation prevention selection (Pr. 78)

This function can prevent reverse rotation fault resulting from the incorrect input of the start signal.
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)
y Set this parameter when you want to limit the motor rotation to only one direction.
y This parameter setting has higher priority than the input from the operation panel or the forward/reverse rotation
command from the communication.
5.17.4 Extended parameter display and user group function (Pr. 160, Pr. 172 to Pr. 174)
Parameter which can be read from the operation panel can be restricted.

1 Displays the parameters registered in the user group.
0 (0 to 16) Displays the number of cases registered as a user group (reading only)
173 ∗1, ∗2 User group registration 9999 0 to 999, 9999 Sets the parameter numbers to be registered to the user group
174 ∗1, ∗2 User group clear 9999 0 to 999, 9999 Sets the parameter numbers to be cleared from the user group
∗1 This parameter can be set when Pr. 160 User group read selection = "0".
∗2 The values read from Pr. 173 and Pr. 174 are always "9999".
∗3 Pr. 501 can always be read regardless of the Pr. 160 User group read selection setting.
∗4 This parameter allows its setting to be changed during operation in any operation mode even if "0 (initial value) or 1" is set in Pr. 77 Parameter write
selection.
yWhen Pr. 160 = "9999", only the simple mode parameters can be displayed on the operation panel. (Refer to the parameter
list , page 78, for the simple mode parameters.) yIn the initial setting (Pr. 160 = "0") status, simple mode parameters and extended parameters can be displayed.
y Every parameter can be read regardless of the Pr.160 setting when reading parameters through FL remote communication.
PARAMETERS
yThe user group function is designed to display only the parameters necessary for setting. yFrom among all parameters, 16 parameters maximum can be registered in the user group. When Pr. 160 is set to "1", only
the parameters registered to the user group can be accessed. (The parameters not registered in the user group can not be read.)
yTo set a parameter in the user group, set its parameter number in Pr. 173. yTo delete a parameter from the user group, set its parameter number to Pr. 174. Set "9999" in Pr. 172 to batch delete
parameters registered.

When registering Pr. 3 to user group
mode display.
z The inverter should be at a stop. z Make sure that the inverter is in PU
mode.
Displays Pr. 173 User group
" ".
5. Turn until Pr. 3 appears. Select the parameter number
to be registered.
" " and " " are displayed alternately. To continue parameter registration, repeat
completed!!
When deleting Pr. 3 from user group
mode display.
z The inverter should be at a stop. z The inverter should be in the PU operation
mode.
to be registered.
" " and " " are displayed alternately. To continue parameter clear, repeat steps 3 to 6.
y Pr. 77 and Pr. 160 can always be read, independently of the user group setting.
y Pr. 77, Pr. 160 and Pr. 172 to Pr. 174 cannot be registered to the user group.
y When Pr. 174 is read, "9999" is always displayed. Although "9999" can be written, no function is available.
y When any value other than "9999" is set to Pr. 172, no function is available.

5.17.5 Password function (Pr. 296, Pr. 297)
Registering a 4-digit password can restrict parameter reading/writing.
Number Name Initial Value Setting Range Description
0 to 6, 99, 100 to 106, 199 ∗4 Select restriction level of parameter reading/ writing when a password is registered.
296∗1 Password lock level 9999
9999 No password lock
1000 to 9998 Register a 4-digit password
Displays password unlock error count. (Reading only) (Valid when Pr. 296 = "100" to "106")
297∗2 Password lock/unlock 9999
(0 to 5) ∗3
9999 ∗3 No password lock
Above parameters allow their settings to be changed during operation in any operation mode even if "0 (initial value) or 1" is set in Pr. 77 Parameter write selection.
∗1 The above parameters can be set when Pr. 160 User group read selection = "0".
∗2 When Pr. 296 = "9999" (no password lock), set Pr. 160 = "0" to enable the setting of this parameter. When the password lock is set, this parameter can be set
anytime regardless of the Pr. 160 setting.
∗3 The setting value "0 or 9999" can be set to Pr.297 at any time although the setting is invalid (the displayed value does not change).
∗4 Setting Pr.296 = "0 or 100" will cause the Option fault (E.OPT) to occur and the inverter to trip. Do not set these values.
yLevel of reading/writing restriction by PU/NET mode operation command can be selected by Pr. 296.
Pr. 296 Setting Operation command of the operation panel Operation command through FL remote communication Read ∗1 Write ∗2 Read Write ∗2 9999 { 0, 100 Option fault (E.OPT) occurs, and the inverter trips. 1, 101 { × { × 2, 102 { × { { 3, 103 { { { × 4, 104 × × { × 5, 105 × × { { 6, 106 { { { ×
99, 199 Only parameters registered in the user group can be read/written.∗3
(For the parameters not registered in the user group, same restriction level as "4, 104" applies.)
∗1 If the parameter reading is restricted by the Pr. 160 setting, those parameters are unavailable for reading even when "{" is indicated.
∗2 If the parameter writing is restricted by the Pr. 77 setting, those parameters are unavailable for writing even when "{" is indicated.
∗3 Read/write is enabled only in the simple mode parameters registered in the user group when Pr.160 User group read selection = "9999". Pr.296 and Pr.297 are
always read/write enabled whether registered to a user group or not.
Pr.296 Setting
Unlock Error Pr.297 Display
1 to 6, 99 No restriction Always 0 101 to 106, 199 Restricted at fifth error Displays error count (0 to 5)
* During [Pr. 296 = any of "101 to 106, 199"], if password unlock error has occurred 5 times, correct password will not unlock the restriction. Parameter all clear can unlock the restriction. (In this case, parameter settings are cleared.) 2) Write a four-digit number (1000 to 9998) in Pr. 297 as a password. (When Pr. 296 = "9999", Pr. 297 cannot be written.) When password is registered, parameter reading/writing is restricted with the restriction level set in Pr. 296 until unlocking.
y After registering a password, a read value of Pr. 297 is always one of "0" to "5".
y When a password restricted parameter is read/written, is displayed. y Even if a password is registered, parameters which the inverter itself writes, such as inverter parts life, are overwritten as needed.
· Restriction of Password · Value

There are two ways of unlocking the password. y Enter a password in Pr. 297.
Unlocked when a password is correct. If a password is incorrect, an error occurs and not unlocked. During [Pr. 296 = any of "101 to 106, 199"], if password unlock error has occurred 5 times, correct password will not unlock the restriction. (During password lock) y Perform all parameter clear.
y If the password has been forgotten, perform all parameter clear to unlock the parameter restriction. In that case,
other parameters are also cleared. y All parameter clear cannot be performed during the operation.

Pr. 296 ≠ 9999 Pr. 297 = 0 to 4
Pr. 296 Read { ∗1 { { { Write { ∗1 { ∗1 × ×
Pr. 297 Read { ∗1 { { { Write × { { { ∗3 Performing parameter clear { { × × Performing parameter all clear { { { ∗2 { ∗2 {: enabled, ×: restricted
∗1 Reading/writing is unavailable when there is restriction to reading by the Pr. 160 setting. (Reading is available in NET mode regardless of Pr. 160 setting.) ∗2 Unavailable during the operation. ∗3 Correct password will not unlock the restriction.
Pr. 77 Parameter write selection Refer to page 166 Pr. 160 Extended function display selection Refer to page 167
Parameters referred to

5.18 Special operation and frequency control
Purpose Parameter that should be Set Refer to Page Perform jog operation Jog operation Pr. 15, Pr. 16 171 Frequency control appropriate for load torque Droop control Pr. 286, Pr. 287 173
Regeneration avoidance function Pr. 882, Pr. 883, Pr. 885, Pr. 886 174
5.18.1Jog operation (Pr. 15, Pr. 16)
You can set the frequency and acceleration/deceleration time for Jog operation. JOG operation can be performed from the operation panel. This operation can be used for conveyor positioning, test operation, etc.
Value Setting Range Description
15 Jog frequency 5Hz 0 to 400Hz Frequency for Jog operation.
Acceleration/deceleration time for Jog operation. As the acceleration/ deceleration time, set the time taken to reach the frequency (initial value is 60Hz) set in Pr. 20 Acceleration/deceleration reference frequency. Acceleration/deceleration time can not be set separately.
0.5s 0 to 3600/ 360s ∗
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)
∗When the Pr. 21 Acceleration/deceleration time increments setting is "0" (initial value), the setting range is "0 to 3600s" and setting increments is "0.1s". When
the setting is "1", the setting range is "0 to 360s" and the setting increments is "0.01s".
Parameter · Number Name Initial

ySelects Jog operation mode from the operation panel. Operation is performed only while the start button is pressed.
z The monitor mode should have been
selected. z The inverter should be at a stop. 2. Change the X12 signal (Bit11) setting to "1."
X12 signal (Bit11) gives a control input
command through FL remote communication. 3. Press to choose the PU Jog operation
mode.
z While is pressed, the motor rotates.
Hold down.
z The motor runs at 5Hz. (Pr. 15 initial value)
[When changing the frequency of PU Jog operation] 6. Press to choose the parameter setting
PRM indicator is lit.
mode.
(The parameter number read previously
appears.)

Flicker...Parameter setting complete!! 11. Perform the operations in steps 1 to 5.
The motor rotates at 10Hz.
y When Pr. 29 Acceleration/deceleration pattern selection = "1" (S-pattern acceleration/deceleration A), the acceleration/
deceleration time is the period of time required to reach Pr. 3 Base frequency.
y The Pr. 15 setting should be equal to or higher than the Pr. 13 Starting frequency.
y During Jog operation, the second acceleration/deceleration via the RT signal cannot be selected. (The other second
functions are valid. (Refer to page 227))
y Pr. 13 Starting frequency Refer to page 119
y Pr. 20 Acceleration/deceleration reference frequency, Pr. 21 Acceleration/deceleration time increments Refer to page 116
y Pr. 29 Acceleration/deceleration pattern selection Refer to page 120

5.18.2 Droop control (Pr. 286, Pr. 287)

This function is designed to balance the load in proportion to the load torque to provide the speed drooping characteristic under Advanced magnetic flux vector control. This function is effective for balancing the load when using multiple inverters.
Drooping amount at the rated torque as a percentage with
0.3s 0 to 1s Time constant of the filter applied on the torque current.

y The output frequency is changed according to
the magnitude of torque current under
Advanced magnetic flux vector control. The drooping amount at the rated torque is set
by the droop gain as a percentage using the rated frequency as a reference.
y The maximum droop compensation frequency
is 120Hz.
frequency = Torque current after filtering × Pr. 84 Rated motor frequency × Pr. 286 Droop gain
Rated value of torque current 100
y Set the droop gain to about the rated slip of the motor.
Rated slip = Synchronous speed at base frequency - rated speed × 100[%] Synchronous speed at base frequency
y The maximum value of frequency after droop compensation is either 120Hz or Pr. 1 Maximum frequency, whichever is smaller.
Pr. 1 Maximum frequency Refer to page 105
Droop compensation · Parameters referred to

5.18.3 Regeneration avoidance function (Pr. 665, Pr. 882, Pr. 883, Pr. 885, Pr. 886)
This function detects a regeneration status and increases the frequency to avoid the regenerative status.
z Possible to avoid regeneration by automatically increasing the frequency and continue operation if the fan happens
to rotate faster than the set speed due to the effect of another fan in the same duct.
Number Name Initial Value Setting
0 Regeneration avoidance function invalid 1 Regeneration avoidance function is always valid
2 Regeneration avoidance function is valid only during a constant speed operation
Bus voltage level at which regeneration avoidance operates. When the bus voltage level is set to low, overvoltage error will be less apt to occur. However, the actual deceleration time increases.
The set value must be higher than the "power supply voltage × ". 400V class
Regeneration avoidance compensation frequency limit value
0 to 10Hz Limit value of frequency which rises at activation of regeneration avoidance function.
9999 Frequency limit invalid
100% 0 to 200% Responsiveness at activation of regeneration avoidance. A larger setting will improve responsiveness to the bus voltage change. However, the output frequency could become unstable. When vibration is not suppressed by decreasing the Pr. 886 setting, set a smaller value in Pr. 665. 665 Regeneration avoidance frequency gain
100% 0 to 200%
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)
yWhen the regeneration load is large, the DC bus voltage rises and an overvoltage fault (E. OV ) may occur.
When this bus voltage rise is detected and the bus voltage level reaches or exceeds Pr. 883, increasing the frequency
avoids the regeneration status. yThe regeneration avoidance function is always ON when "1" is set in Pr. 882 and activated only during a constant speed
when "2" is set in Pr. 882.


y The acceleration/deceleration ramp while the regeneration avoidance function is operating changes depending on the
regeneration load.
y The DC bus voltage of the inverter is about times as input voltage.
When the input voltage is 220VAC, bus voltage is approximately 311VDC.
When the input voltage is 440VAC, bus voltage is approximately 622VDC.
However, it varies with the input power supply waveform.
y The Pr. 883 setting should be kept higher than the DC bus voltage level. Otherwise, the regeneration avoidance function is
always on even in the non-regeneration status and the frequency increases.
y While overvoltage stall ( ) is activated only during deceleration and stops the output frequency, the regeneration avoidance
function is always on (Pr. 882 = 1) or activated only during a constant speed (Pr. 882 = 2) and increases the frequency according
to the regeneration amount.
You can limit the output frequency compensated for (increased) by the
regeneration avoidance function. yThe frequency is limited to the output frequency (frequency prior to

regeneration avoidance operation) + Pr. 885 Regeneration avoidance compensation frequency limit value during acceleration or constant speed.
If the frequency increased by regeneration avoidance function exceeds the limit value during deceleration, the limit value is held until the output
frequency falls to 1/2 of Pr. 885. yWhen the frequency increased by regeneration avoidance function has
reached Pr. 1 Maximum frequency, it is limited to the maximum frequency. yWhen Pr. 885 is set to "9999", regeneration avoidance function operation
frequency setting is invalid.
yIf the frequency becomes instable during regeneration avoidance operation, decrease the setting of Pr. 886 Regeneration
avoidance voltage gain. Reversely, if sudden regeneration causes an overvoltage alarm, increase the setting. When vibration is not suppressed by decreasing the Pr. 886 setting, set a smaller value in Pr. 665 Regeneration avoidance
frequency gain.
y When regeneration avoidance operation is performed, (overvoltage stall) is displayed and the OL signal is
output. Set the operation pattern at an OL signal output using Pr. 156 Stall prevention operation selection. Set the output
timing of the OL signal using Pr. 157 OL signal output timer.
y When regeneration avoidance operation is performed, stall prevention is also activated.
y The regeneration avoidance function cannot shorten the actual deceleration time taken to stop the motor. The actual
deceleration time depends on the regeneration energy consumption capability. When shortening the deceleration
time, consider using the regeneration unit (FR-BU2) and brake resistor (MRS type, MYS type and FR-ABR etc.,) to
consume regeneration energy at constant speed.
y When using the regeneration unit (FR-BU2) and brake resistor (MRS type, MYS type, FR-ABR etc.), set Pr. 882 to "0
(initial value)" (regeneration avoidance function invalid). When using the regeneration unit, etc. to consume
regeneration energy at deceleration, set Pr. 882 to "2" (regeneration avoidance function valid only at a constant
speed).
Pr. 1 Maximum frequency Refer to page 105 Pr. 8 Deceleration time Refer to page 116 Pr. 22 Stall prevention operation level Refer to page 101
Parameters referred to

5.19 Useful functions
Purpose Parameter that should be Set Refer to Page
Inverter part life display Pr. 255 to Pr. 259 177 Maintenance output function Pr. 503, Pr. 504 180
Freely available parameter Free parameter Pr. 888, Pr. 889 181
5.19.1 Cooling fan operation selection (Pr. 244)
You can control the operation of the cooling fan built in the inverter (FR-E720-1.5KNF or higher, FR-E740-1.5KNF or higher).
Number Name Initial Value Setting Range Description
Operates in power-ON status.
Cooling fan ON/OFF control invalid (the
cooling fan is always ON at power ON)
Cooling fan ON/OFF control valid
The fan is always ON while the inverter is
running. During a stop, the inverter status
is monitored and the fan switches ON-
OFF according to the temperature.
The above parameters can be set when Pr.160 User group read selection = "0". (Refer to page 167)
y In either of the following cases, fan operation is regarded as faulty and [FN] is shown on the operation panel.
y Pr. 244 = "0"
When the fan comes to a stop with power ON.
yPr. 244 = "1"
When the inverter is running and the fan stops during fan ON command.
Parameter

5.19.2 Display of the life of the inverter parts (Pr. 255 to Pr. 259)
Degrees of deterioration of main circuit capacitor, control circuit capacitor, cooling fan and inrush current limit circuit can
be diagnosed by monitor. When any part has approached the end of its life, an alarm can be output by self diagnosis to prevent a fault.
(Use the life check of this function as a guideline since the life except the main circuit capacitor is calculated theoretically.)
Number Name Initial Value Setting
Displays whether the control circuit capacitor,
main circuit capacitor, cooling fan, and each parts
255 Life alarm status display 0 (0 to 15)
of the inrush current limit circuit has reached the
life alarm output level or not. (Reading only)
Displays the deterioration degree of the inrush
100% (0 to 100%)
current limit circuit.
Displays the deterioration degree of the control
100% (0 to 100%)
circuit capacitor.
Displays the deterioration degree of the main
circuit capacitor.
100% (0 to 100%)
The value measured by Pr. 259 is displayed.
Setting "1" and turning the power supply off starts
the measurement of the main circuit capacitor life.
When the Pr. 259 value is "3" after powering on
(2, 3, 8, 9)
again, the measuring is completed.
Writes deterioration degree in Pr. 258.
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)
y Since repeated inrush currents at power ON will shorten the life of the converter circuit, frequent starts and stops of the
magnetic contactor must be avoided.

yWhether any of the control circuit capacitor, main circuit capacitor, cooling fan and inrush current limit circuit has reached the life alarm output level or not can be checked by Pr. 255 Life alarm status display.
1 15 bit 7 0
0 1 0 0
Pr. 255 read Pr. 255 setting read
bit0 Control circuit capacitor life
bit1 Main circuit capacitor life bit2 Cooling fan life
Bit image is displayed in decimal
bit3 Inrush current limit circuit life
Pr. 255 (decimal)
Main Circuit Capacitor Life
15 1111 {
14 1110 { { { ×
13 1101 { { × {
12 1100 { { × ×
11 1011 { × { {
10 1010 { × { ×
9 1001 { × × {
8 1000 { × × ×
7 0111 × { { {
6 0110 × { { ×
5 0101 × { × {
4 0100 × { × ×
3 0011 × × { {
2 0010 × × { ×
1 0001 × × × {
0 0000 × {: With warnings, ×: Without warnings
yThe life of the inrush current limit circuit (relay, contactor and inrush resistor) is displayed in Pr. 256 .
yThe number of contact (relay, contactor, thyristor) ON times is counted, and it is counted down from 100% (0 times) every
1%/10,000 times.
As soon as 10% (900,000 times) is reached, Pr. 255 bit 3 is turned ON.
yThe deterioration degree of the control circuit capacitor is displayed in Pr. 257 as a life. yIn the operating status, the control circuit capacitor life is calculated from the energization time and temperature, and is
counted down from 100%. As soon as the control circuit capacitor life falls below 10%, Pr. 255 bit 0 is turned ON.

yThe deterioration degree of the control circuit capacitor is displayed in Pr. 258 as a life.
yOn the assumption that the main circuit capacitor capacitance at factory shipment is 100%, the capacitor life is displayed
in Pr. 258 every time measurement is made. When the measured value falls to or below 85%, Pr. 255 bit 1 is turned ON and also an alarm is output to the Y90 signal. yMeasure the capacitor capacity according to the following procedure and check the deterioration level of the capacitor
capacity.
change the operation mode to the PU operation mode using on the operation panel.
Pr. 259 Description Remarks 0 No measurement Initial value
1 Measurement start Measurement starts when the power supply is switched OFF. 2 During measurement
Only displayed and cannot be set 3 Measurement complete 8 Forced end 9 Measurement error
y When the main circuit capacitor life is measured under the following conditions, "forced end" (Pr. 259 = "8") or "measuring error"
(Pr. 259 ="9") occurs or it remains in "measuring start" (Pr. 259 = "1"). Therefore, do not measure in such case. In addition, even when "measurement completion" (Pr. 259 = "3") is confirmed under the following conditions, normal measurement can not be done. (a) DC power supply is connected to the terminal P/+ and N/-. (b) The power supply switched ON during measurement. (c) The motor is not connected to the inverter. (d) The motor is running (coasting) (e) The motor capacity is two rank smaller as compared to the inverter capacity. (f) The inverter is tripped or a fault occurred when power is OFF. (g) The inverter output is shut off with the MRS signal. (h) The start command is given while measuring. (i) I/O signals are conducted through FL remote communication and I/O terminals of the control terminal block. (j) The setting value "1" is set in the X12 signal (Bit11), which gives a control input command through FL remote
communication, in the Network operation mode. (k) "EV" is displayed on the operation panel (main circuit power supply is OFF, 24V external power supply is ON.) y Turning the power ON during measuring before LED of the operation panel turns OFF, it may remain in "measuring" (Pr. 259 =
"2") status. In such case, carry out operation from step 3.
For accurate life measurement of the main circuit capacitor, wait 3 hours or longer after turning OFF. The temperature left in the main circuit capacitor affects measurement.
When measuring the main circuit capacitor capacity (Pr. 259 Main circuit capacitor life measuring = "1"), the DC
voltage is applied to the motor for 1s at powering OFF. Never touch the motor terminal, etc. right after powering OFF to prevent an electric shock.

yThe cooling fan speed of 50% or less is detected, and "FN" is displayed on the operation panel. As an alarm display, Pr.
255 bit2 is turned ON.
y When the inverter is mounted with two or more cooling fans, "FN" is displayed with one or more fans with speed of 50% or less.
y For replacement of each part, contact the nearest Mitsubishi FA center.
Maintenance timer signal (Y95) is output when the inverter's cumulative energization time reaches the time period set
by the parameter during FL remote communication. (MT) is displayed on the operation panel.
This can be used as a guideline for the maintenance time for peripheral devices.
Number Name Initial Value Setting Range Description
Displays the cumulative energization time
of the inverter in 100h increments.
503 Maintenance timer 0 0 (1 to 9998)
Writing the setting of "0" clears the
cumulative energization time.
9999 0 to 9998 Time taken until when the maintenance
timer alarm output signal (Y95) is output.
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)
Set "0" in Pr. 503
Maintenance timer (Pr. 503)
Pr. 504
y The cumulative energization time of the inverter is stored into the EEPROM every hour and is displayed in Pr. 503
Maintenance timer in 100h increments. Pr. 503 is clamped at 9998 (999800h). y When the Pr. 503 value reaches the time set to Pr. 504 Maintenance timer alarm output set time (100h increments), the
maintenance timer alarm output signal (Y95) is output.
y The cumulative energization time is counted every hour. The energization time of less than 1h is not counted.

5.19.4 Free parameter (Pr. 888, Pr. 889)
You can input any number within the setting range 0 to 9999. For example, the number can be used:
y As a unit number when multiple units are used. y As a pattern number for each operation application when multiple units are used.
y As the year and month of introduction or inspection.
Number Name Initial Value Setting Range Description
888 Free parameter 1 9999 0 to 9999 Any values can be set. Data is held even
if the inverter power is turned OFF. 889 Free parameter 2 9999 0 to 9999
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)
The above parameters allow their settings to be changed during operation in any operation mode even if "0" (initial value) is set in Pr.77 Parameter
write selection.
Pr. 888 and Pr. 889 do not influence the inverter operation.
Parameter

5.20 Setting from the operation panel

Purpose Parameter that should be Set Refer to Page Selection of rotation direction by
Use the setting dial of the operation panel like a potentiometer for frequency setting. Key lock of operation panel
Change the magnitude of change of frequency setting by the setting dial of the operation panel

Used to choose the direction of rotation by operating of the operation panel.
The above parameter can be set when Pr. 160 User group read selection = "0". (Refer to page 167)

5.20.2 Operation panel frequency setting/key lock operation selection (Pr. 161)
The setting dial of the operation panel can be used for setting like a potentiometer. The key operation of the operation panel can be disabled.

0 Setting dial frequency setting Key lock invalid 1 Setting dial potentiometer
10 Setting dial frequency setting Key lock valid 11 Setting dial potentiometer
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)
(1) Using the setting dial like a potentiometer to set the frequency.
Operation example Changing the frequency from 0Hz to 60Hz during operation
The inverter starts up in the Network operation
mode. The monitor display appears. 2. Change the X12 signal (Bit11) setting to "1."
X12 signal (Bit11) gives a control input
command through FL remote communication. 3. Press to choose the PU operation mode.
PU indicator is lit.
PRM indicator is lit.
mode.
(The parameter number read previously appears.) 5. Turn until (Pr. 161) appears.
" "(initial value) appears. 7. Turn to change it to the set value " ".
Press twice to choose the monitor/
frequency monitor. 10.Press to start the inverter.
The frequency flickers for about 5s.
The flickering frequency is the set frequency.
You need not press .

y If the display changes from flickering "60.00" to "0.00", the setting of Pr. 161 Frequency setting/key lock operation selection may not
be "1".
y Independently of whether the inverter is running or at a stop, the frequency can be set by simply turning the dial.
y When the frequency is changed, it will be stored in EEPROM as the set frequency after 10s.
y When setting frequency by turning the setting dial, the frequency goes up to the set value of Pr.1 Maximum frequency
(initial value: 120Hz). Adjust Pr.1 Maximum frequency setting according to the application.
(2) Disable the setting dial and key operation of the operation panel (Press [MODE] long (2s))
yOperation using the setting dial and key of the operation panel can be invalid to prevent parameter change, and
unexpected start or frequency setting.
ySet "10 or 11" in Pr. 161, then press for 2s to make the setting dial and key operation invalid.
yWhen the setting dial and key operation are invalid, appears on the operation panel. If dial or key operation is
attempted while dial and key operation are invalid, appears. (When dial or key is not touched for 2s, monitor
display appears.)
yTo make the setting dial and key operation valid again, press for 2s.
y Even if the setting dial and key operation are disabled, the monitor display and are valid.
y Release the operation lock to release the PU stop by key operation.

5.20.3 Magnitude of frequency change setting (Pr. 295)
When setting the set frequency with the setting dial, frequency changes in 0.01Hz increments in the initial status. Setting this parameter increases the magnitude of frequency which changes according to the rotated amount of the

The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 167)
This parameter allows its setting to be changed during operation in any operation mode even if "0" (initial value) is set in Pr. 77 Parameter write
selection.
When a value other than "0" is set in Pr. 295, the minimum varying width when the set frequency is changed by the setting dial can be set.
For example, when "1.00Hz" is set in Pr. 295, one click (one dial gauge) of the setting dial changes the frequency in increments of 1.00Hz→2.00Hz→3.00Hz.
When Pr. 295 = "1"
1 click 1 click 1 click
∗One rotation of the setting dial equals to 24 clicks (24 dial gauges).
y When machine speed display is selected with Pr. 37, the minimum increments of the magnitude of change is determined by
Pr.295 as well. Note that the setting value may differ as speed setting changes the set machine speed and converts it to the
speed display again.
y When the set frequency (speed) is 100 or more, frequency is displayed in 0.1 increments. Therefore, the minimum varying
width is 0.1 even when Pr. 295 < 0.1.
y When the machine speed setting is 1000 or more, frequency is displayed in 1 increments. Therefore, the minimum varying
width is 1 even when Pr. 295 < 1.
PARAMETERS
y For Pr. 295 , unit is not displayed .
y This parameter is valid only in the set frequency mode. When other frequency-related parameters are set, it is not
activated.
y When 10 is set, frequency setting changes in 10Hz increments. Note the excess speed. (in potentiometer mode)

5.21 Parameter clear/ All parameter clear
POINT y Set "1" in Pr.CL Parameter clear or ALLC all parameter clear to initialize all parameters. (Parameters are not
cleared when "1" is set in Pr. 77 Parameter write selection.)
y Refer to the extended parameter list on page 78 for parameters cleared with this operation.
The inverter starts up in the Network operation
mode. The monitor display appears. 2. Change the X12 signal (Bit11) setting to "1."
X12 signal (Bit11) gives a control input
command through FL remote communication. 3. Press to choose the PU operation mode.
PU indicator is lit.
PRM indicator is lit.
mode.
(The parameter number read previously appears.)
" "(initial value) appears.

1 Set parameters back to the initial values. Refer to the parameter list on page 78 for availability of
The inverter is not in the PU operation mode. Carry out operation from step 2 again.

5.22 Initial value change list
Displays and sets the parameters changed from the initial value.
The inverter starts up in the Network operation
mode. The monitor display appears. 2. Change the X12 signal (Bit11) setting to "1."
X12 signal (Bit11) gives a control input
command through FL remote communication. 3. Press to choose the PU operation mode.
PU indicator is lit.
PRM indicator is lit.
mode.
(The parameter number read previously appears.)
∗It may take several seconds for
creating the initial value change
change list screen.
list. " " flickers while

changed.
zPress to read the currently set value.
Turn and press to change the
(refer to step 6 and 7 on page 76) Flicker Parameter setting complete!!
zTurn to read another parameter.
zThe display returns to after all
parameters are displayed.
the parameter setting mode.
y Turning sets other parameters.
y Pressing displays the change list again.
y Only simple mode parameter is displayed when simple mode is set (Pr. 160 = 9999)
y Only user group is displayed when user group is set (Pr. 160 = "1").
y Pr. 160 is displayed independently of whether the setting value is changed or not.
y When parameter setting is changed after creating the initial value change list, the setting will be reflected to the initial
value change list next time.
Pr. 160 User group read selection Refer to page 167
setting · Parameters referred to

5.23 Check and clear of the faults history

Eight past faults can be displayed with the setting dial.
Faults history number (The number of past faults is displayed.)
∗The cumulative energization time and actual operation time are accumulated from 0 to 65535 hours, then cleared, and accumulated again from 0.
When the operation panel is used, the time is displayed up to 65.53 (65530h) in the indication of 1h = 0.001, and thereafter, it is added up from 0.

POINT
y Set "1" in Er.CL Fault history clear to clear the faults history.
The monitor display appears.
PRM indicator is lit.
(The parameter number read previously appears.)
appears. 4. Press to read the currently set value. " " (initial
value) appears.
y Turn to read another parameter.
y Press to show the setting again.
y Press twice to show the next parameter.
Pr. 77 Parameter write selection Refer to page 166
Parameters referred to


This chapter provides the "TROUBLESHOOTING" of this product. Always read the instructions before using the equipment.
6.1 Reset method of protective function 192 6.2 List of fault or alarm indications 193 6.3 Causes and corrective actions 194 6.4 Correspondences between digital and actual characters 203 6.5 Check first when you have a trouble 204

When a fault occurs in the inverter, the inverter trips and the display on the operation panel automatically changes to a fault or
alarm indication shown on page 193. If the fault does not correspond to any of the following faults or if you have any other problem, please contact your sales representative. z Retention of fault output signal...When the magnetic contactor (MC) provided on the input side of the inverter is opened
when a fault occurs, the inverter's control power will be lost and the fault output will not be held. z Fault or alarm indication When a fault or alarm occurs, the operation panel display automatically switches to the fault
or alarm indication. z Resetting method When a fault occurs, the inverter output is kept stopped. Unless reset, therefore, the inverter
cannot restart. (Refer to page 192) z When any fault occurs, take the appropriate corrective action, then reset the inverter, and resume operation.
Not doing so may lead to the inverter fault and damage.
Inverter fault or alarm indications are roughly categorized as below. (1) Error message A message regarding operational fault and setting fault by the operation panel is displayed. The inverter does not trip. (2) Warning The inverter does not trip even when a warning is displayed. However, failure to take appropriate measures will lead to a fault. (3) Alarm The inverter does not trip. (4) Fault
When a fault occurs, the inverter trips, and the ALM signal is also output.

y Past eight faults can be displayed using the setting dial.
(1) Resetting the inverter
The inverter can be reset by performing any of the following operations. Note that the internal thermal integrated value of the electronic thermal relay function and the number of retries are cleared (erased) by resetting the inverter. Inverter recovers about 1s after the reset is released.
Operation 1: Using the operation panel, press to reset the inverter.
(This may only be performed when a fault occurs. (Refer to page 197 for fault.))
Operation 2: Change the error reset signal setting of FL remote communication from "0" to "1."
(This may only be performed when a fault occurs. (Refer to page 197 for fault.)) Operation 3: Switch OFF the power once, then switch it ON again after the indication of the
operation panel turns OFF.
REMARKS
y Use the operation 1 or 2 to reset when using the 24V external power supply.
y OFF status of the start signal must be confirmed before resetting the inverter fault. Resetting inverter fault with the
start signal ON restarts the motor suddenly.

6.2 List of fault or alarm indications

E.GF Output side earth (ground) fault overcurrent at start 200

6.3 Causes and corrective actions
A message regarding operational troubles is displayed. Output is not shutoff.
Name Operation panel lock
Description Operation lock mode is set. Operation other than is invalid. (Refer to page 184)
Corrective action Press for 2s to release lock.
Name Password locked Description Password function is active. Display and setting of parameter is restricted. Check point
Corrective action Enter the password in Pr. 297 Password lock/unlock to unlock the password function before operating. (Refer to page
169).
Name Write disable error
y You attempted to make parameter setting when Pr. 77 Parameter write selection has been set to disable parameter
write.
y Frequency jump setting range overlapped.
Check point y Check the setting of Pr. 77 Parameter write selection. (Refer to page 166).
y Check the settings of Pr. 31 to Pr. 36 (frequency jump). (Refer to page 106)
Name Write error during operation
Description When parameter write was performed during operation with a value other than "2" (writing is enabled independently
of operation status in any operation mode) is set in Pr. 77 and the STF (STR) is ON.
Check point y Check the Pr. 77 setting. (Refer to page 166).
y Check that the inverter is not operating.
Corrective action y Set "2" in Pr. 77.
y After stopping operation, make parameter setting.
Name Mode designation error Description Appears if a parameter setting is attempted in the NET operation mode with Pr. 77 ≠ "2."
Check point y Check that operation mode is PU operation mode.
y Check the Pr. 77 setting. (Refer to page 166).
Corrective action y After setting the operation mode to the "PU operation mode", make parameter setting. (Refer to page 212)
y After setting Pr. 77 = "2", make parameter setting.
indication Err.
y Appears when a reset command is executed by an error reset of FL remote communication and on the
operation panel.
y Appears at power-OFF. Corrective action y Turn OFF the reset command

(2) Warning When a warning occurs, the output is not shut off.
Name Stall prevention (overcurrent)
When the output current (output torque when Pr. 277 Stall prevention current switchover = "1") of the inverter exceeds the stall prevention operation level (Pr. 22 Stall prevention operation level, etc.), this function stops the increase in frequency until the overload current decreases to prevent the inverter from resulting in overcurrent trip. When the overload current has reduced below stall prevention operation level, this function increases the frequency again.
When the output current (output torque when Pr. 277 Stall prevention current switchover = "1") of the inverter exceeds the stall prevention operation level (Pr. 22 Stall prevention operation level, etc.), this function reduces frequency until the overload current decreases to prevent the inverter from resulting in overcurrent trip. When the overload current has reduced below stall prevention operation level, this function increases the frequency up to the set value.
When the output current (output torque when Pr. 277 Stall prevention current switchover = "1") of the inverter exceeds the stall prevention operation level (Pr. 22 Stall prevention operation level, etc.), this function stops the decrease in frequency until the overload current decreases to prevent the inverter from resulting in overcurrent trip. When the overload current has decreased below stall prevention operation level, this function decreases the frequency again.
y Check that the Pr. 0 Torque boost setting is not too large. y Check that the Pr. 7 Acceleration time and Pr. 8 Deceleration time settings are not too small. y Check that the load is not too heavy. y Are there any failure in peripheral devices? y Check that the Pr. 13 Starting frequency is not too large. y Check that the Pr. 22 Stall prevention operation level is appropriate
y Increase or decrease the Pr. 0 Torque boost setting 1% by 1% and check the motor status. (Refer to page 94) y Set a larger value in Pr. 7 Acceleration time and Pr. 8 Deceleration time. (Refer to page 116) y Reduce the load weight. y Try Advanced magnetic flux vector control and General-purpose magnetic flux vector control. y Change the Pr. 14 Load pattern selection setting. y Set stall prevention operation current in Pr. 22 Stall prevention operation level. (The initial value is 150%.) The
acceleration/deceleration time may change. Increase the stall prevention operation level with Pr. 22 Stall prevention operation level, or disable stall prevention with Pr. 156 Stall prevention operation selection. (Operation at OL occurrence can be selected using Pr. 156.)
Name Stall prevention (overvoltage)
y If the regenerative energy of the motor becomes excessive to exceed the regenerative energy
consumption capability, this function stops the decrease in frequency to prevent overvoltage trip.
As soon as the regenerative energy has reduced, deceleration resumes.
y If the regenerative energy of the motor becomes excessive when regeneration avoidance function
is selected (Pr. 882 =1), this function increases the speed to prevent overvoltage trip.
(Refer to page 174).
Check point y Check for sudden speed reduction.
y Check that regeneration avoidance function (Pr. 882, Pr. 883, Pr. 885, Pr. 886) is used. (Refer to page 174). Corrective action The deceleration time may change. Increase the deceleration time using Pr. 8 Deceleration time.
Description Stop with on the operation panel is selected in Pr. 75 Reset selection/PU stop selection.
(For Pr. 75 refer to page 165 .)
Check point Check for a stop made by pressing of the operation panel.
Corrective action Turn the start signal OFF and release with .

Name Regenerative brake prealarm
Appears if the regenerative brake duty reaches or exceeds 85% of the Pr. 70 Special regenerative brake duty value.
When the setting of Pr. 70 Special regenerative brake duty is the initial value (Pr. 70 = "0"), this warning does not occur. If
the regenerative brake duty reaches 100%, a regenerative overvoltage (E. OV_) occurs.
Check point y Check that the brake resistor duty is not high. y Check that the Pr. 30 Regenerative function selection and Pr. 70 Special regenerative brake duty settings are correct.
Corrective action y Increase the deceleration time. y Check that the Pr. 30 Regenerative function selection and Pr. 70 Special regenerative brake duty settings.
Name Electronic thermal relay function prealarm
Description Appears if the cumulative value of the Pr. 9 Electronic thermal O/L relay reaches or exceeds 85% of the preset level. If
it reaches 100% of the Pr. 9 Electronic thermal O/L relay setting, a motor overload trip (E. THM) occurs.
Check point y Check for large load or sudden acceleration.
y Is the Pr. 9 Electronic thermal O/L relay setting is appropriate? (Refer to page 123)
Corrective action y Reduce the load and frequency of operation.
y Set an appropriate value in Pr. 9 Electronic thermal O/L relay. (Refer to page 123)
Name Maintenance signal output
Indicates that the cumulative energization time of the inverter has reached a given time.
When the setting of Pr. 504 Maintenance timer alarm output set time is the initial value (Pr. 504 = "9999"), this warning
does not occur.
Check point The Pr. 503 Maintenance timer setting is larger than the Pr. 504 Maintenance timer alarm output set time setting. (Refer to
page 180). Corrective action Setting "0" in Pr. 503 Maintenance timer erases the signal.
If the power supply voltage of the inverter decreases, the control circuit will not perform normal functions. In addition, the motor torque will be insufficient and/or heat generation will increase. To prevent this, if the power supply voltage decreases below about 115VAC (about 230VAC for 400V class, about 58VAC for 100V class), this function stops the
inverter output and displays . An alarm is reset when the voltage returns to normal. Check point Check that the power supply voltage is normal. Corrective action Check the power supply system equipment such as power supply.
Name Safety stop Description Appears when safety stop function is activated (during output shutoff). (Refer to page 24)
Check point If the indication appears when safety stop function is not used, check that shorting wires between S1 and PC, S2 and
PC are connected.
y When not using the safety stop function, short across terminals S1 and PC and across S2 and PC with shorting
wire for the inverter to run. y If is indicated when across S1 and PC and across S2 and PC are both shorted while using the safety stop function (drive enabled), internal failure might be the cause. Check the wiring of terminals S1, S2 and PC and contact your sales representative if the wiring has no fault.

Name 24V external power supply operation Description Flickers when the main circuit power supply is OFF and the 24V external power is being supplied.
y Check if the 24V external power is supplied. y Check if the (main circuit) power supply for the inverter is ON. Check if the voltage is low. y Check if the jumper between terminal P/+ and P1 is removed.
y Turn ON the power supply for the inverter (main circuit). y If appears by turning ON the power supply of the inverter (main circuit) while the external 24V power is supplied, check the power supply (for the main circuit). y Check if the jumper is installed securely between the terminal P/+ and P1.
(3) Alarm When an alarm occurs, the output is not shut off.

Description For the inverter that contains a cooling fan, appears on the operation panel when the cooling fan stops due to an alarm or different operation from the setting of Pr. 244 Cooling fan operation selection. Check point Check the cooling fan for an alarm. Corrective action Check for fan alarm. Please contact your sales representative.
(4) Fault When a fault occurs, the inverter trips and a fault signal is output.
indication E.OC1
Name Overcurrent trip during acceleration
Description When the inverter output current reaches or exceeds approximately 230% of the rated current during acceleration, the protective circuit is activated and the inverter trips.
y Check for sudden acceleration. y Check that the downward acceleration time is not long for lifts. y Check for output short-circuit/ground fault. y Check that the Pr. 3 Base frequency setting is not 60Hz when the motor rated frequency is 50Hz. y Check if the stall prevention operation level is set too high. y Check if the fast-response current limit operation is disabled. y Check that regeneration is not performed frequently. (Check that the output voltage becomes larger than the V/F
reference value at regeneration and overcurrent occurs due to the high voltage.)
y Increase the acceleration time. (Shorten the downward acceleration time for lifts.) y When "E.OC1" is always lit at starting, disconnect the motor once and start the inverter.
If "E.OC1" is still lit, contact your sales representative. y Check the wiring to make sure that output short circuit/ground fault does not occur. y Set 50Hz in Pr. 3 Base frequency. (Refer to page 107) y Lower the setting of stall prevention operation level. (Refer to page 101). y Activate the fast-response current limit operation. y Set base voltage (rated voltage of the motor, etc.) in Pr. 19 Base frequency voltage. (Refer to page 107)
indication E.OC2
Name Overcurrent trip during constant speed
Description When the inverter output current reaches or exceeds approximately 230% of the rated current during constant speed operation, the protective circuit is activated and the inverter trips.
y Check for sudden load change. y Check for output short-circuit/ground fault. y Check if the stall prevention operation level is set too high. y Check if the fast-response current limit operation is disabled.
y Keep load stable. y Check the wiring to make sure that output short circuit/ground fault does not occur. y Lower the setting of stall prevention operation level. (Refer to page 101). y Activate the fast-response current limit operation.

indication E.OC3
Name Overcurrent trip during deceleration or stop
Description When the inverter output current reaches or exceeds approximately 230% of the rated inverter current during deceleration (other than acceleration or constant speed), the protective circuit is activated and the inverter trips.
y Check for sudden speed reduction. y Check for output short-circuit/ground fault. y Check for too fast operation of the motor's mechanical brake. y Check if the stall prevention operation level is set too high. y Check if the fast-response current limit operation is disabled.
y Increase the deceleration time. y Check the wiring to make sure that output short circuit/ground fault does not occur. y Check the mechanical brake operation. y Lower the setting of stall prevention operation level. (Refer to page 101). y Activate the fast-response current limit operation.
indication E.OV1
Name Regenerative overvoltage trip during acceleration
If regenerative energy causes the inverter's internal main circuit DC voltage to reach or exceed the specified value, the protective circuit is activated and the inverter trips. The circuit may also be activated by a surge voltage produced in the power supply system.
Check point y Check for too slow acceleration. (e.g. during downward acceleration in vertical lift load) y Check that the setting of Pr. 22 Stall prevention operation level is not too small.
y Decrease the acceleration time. y Check that regeneration avoidance function (Pr. 882, Pr. 883, Pr. 885, Pr. 886) is used. (Refer to page 174). y Set the Pr.22 Stall prevention operation level correctly.
indication E.OV2
Name Regenerative overvoltage trip during constant speed
If regenerative energy causes the inverter's internal main circuit DC voltage to reach or exceed the specified value, the protective circuit is activated to stop the inverter output. The circuit may also be activated by a surge voltage produced in the power supply system.
Check point y Check for sudden load change. y Check that the setting of Pr. 22 Stall prevention operation level is not too small.
y Keep load stable. y Check that regeneration avoidance function (Pr. 882, Pr. 883, Pr. 885, Pr. 886) is used. (Refer to page 174). y Use the brake resistor, brake unit or power regeneration common converter (FR-CV) as required. y Set the Pr.22 Stall prevention operation level correctly.
indication E.OV3
Name Regenerative overvoltage trip during deceleration or stop
If regenerative energy causes the inverter's internal main circuit DC voltage to reach or exceed the specified value, the protective circuit is activated to stop the inverter output. The circuit may also be activated by a surge voltage produced in the power supply system. Check point Check for sudden speed reduction.
y Increase the deceleration time. (Set the deceleration time which matches the moment of inertia of the load) y Longer the brake cycle. y Use regeneration avoidance function (Pr. 882, Pr. 883, Pr. 885, Pr. 886). (Refer to page 174). y Use the brake resistor, brake unit or power regeneration common converter (FR-CV) as required.

indication E.THT
Name Inverter overload trip (electronic thermal relay function)
If the temperature of the output transistor element exceeds the protection level under the condition that a current not less than the rated inverter current flows and overcurrent trip does not occur (230% or less), the electronic thermal relay activates to stop the inverter output. (Overload capacity 150% 60s, 200% 3s)
y Check that acceleration/deceleration time is not too short. y Check that torque boost setting is not too large (small). y Check that load pattern selection setting is appropriate for the load pattern of the using machine. y Check the motor for use under overload. y Check for too high surrounding air temperature.
y Increase acceleration/deceleration time. y Adjust the torque boost setting. y Set the load pattern selection setting according to the load pattern of the using machine. y Reduce the load weight. y Set the surrounding air temperature to within the specifications.
indication E.THM
Name Motor overload trip (electronic thermal relay function) ∗1
The electronic thermal relay function in the inverter detects motor overheat due to overload or reduced cooling capability during constant-speed operation and pre-alarm (TH display) is output when the integrated value reaches 85% of the Pr. 9 Electronic thermal O/L relay setting and the protection circuit is activated to stop the inverter output when the integrated value reaches the specified value. When running a special motor such as a multi-pole motor or multiple motors, provide a thermal relay on the inverter output side since such motor(s) cannot be protected by the electronic thermal relay function.
y Check the motor for use under overload. y Check that the setting of Pr. 71 Applied motor for motor selection is correct. (Refer to page 125). y Check that stall prevention operation setting is correct.
y Reduce the load weight. y For a constant-torque motor, set the constant-torque motor in Pr. 71 Applied motor. y Check that stall prevention operation setting is correct. (Refer to page 101).
∗1 Resetting the inverter initializes the internal thermal integrated data of the electronic thermal relay function.
indication E.FIN
If the heatsink overheats, the temperature sensor is actuated and the inverter trips. FIN signal is output through FL remote communication when the temperature rises to 85% of the heatsink overheat protection temperature. (Refer to page 60)
y Check for too high surrounding air temperature. y Check for heatsink clogging.
y Check that the cooling fan is not stopped (Check that is not displayed on the operation panel).
y Set the surrounding air temperature to within the specifications. y Clean the heatsink. y Replace the cooling fan.
indication E.ILF
Name Input phase loss
Inverter trips when function valid setting (=1) is selected in Pr. 872 Input phase loss protection selection and one phase of
the three phase power input is lost. (Refer to page 160).
It may function if phase-to-phase voltage of the three-phase power input becomes largely unbalanced.
Check point y Check for a break in the cable for the three-phase power supply input.
y Check that phase-to-phase voltage of the three-phase power input is not largely unbalanced.
y Wire the cables properly.
y Repair a break portion in the cable.
y Check the Pr. 872 Input phase loss protection selection setting.
y Set Pr. 872 = "0" (without input phase loss protection) when three-phase input voltage is largely unbalanced.

indication E.OLT
Name Stall prevention stop stop
If the output frequency has fallen to 1Hz by stall prevention operation and remains for 3s, a fault (E.OLT) appears and trips the inverter. OL appears while stall prevention is being activated. E.OLT may not occur if stall prevention (OL) is activated during output phase loss. Check point y Check the motor for use under overload. (Refer to page 102). Corrective action y Reduce the load weight. (Check the Pr. 22 Stall prevention operation level setting.)
indication E.BE
Name Brake transistor alarm detection
When a brake transistor alarm has occurred due to the large regenerative energy from the motor etc., the brake
transistor alarm is detected and the inverter trips.
In this case, the inverter must be powered OFF immediately.
Check point y Reduce the load inertia. y Check that the frequency of using the brake is proper. Corrective action Replace the inverter.
indication E.GF
Name Output side earth (ground) fault overcurrent at start
The inverter trips if an earth (ground) fault overcurrent flows at start due to an earth (ground) fault that occurred on the inverter's output side (load side). Whether this protective function is used or not is set with Pr. 249 Earth (ground) fault detection at start. When the setting of Pr. 249 Earth (ground) fault detection at start is the initial value (Pr. 249 ="0"), this warning does not occur. Check point Check for a ground fault in the motor and connection cable. Corrective action Remedy the ground fault portion.
indication E.LF
Name Output phase loss
If one of the three phases (U, V, W) on the inverter's output side (load side) is lost during inverter operation (except during DC injection brake operation and when output frequency is under 1Hz), inverter stops the output. Whether the protective function is used or not is set with Pr. 251 Output phase loss protection selection.
Check point y Check the wiring. (Check that the motor is normal.) y Check that the capacity of the motor used is not smaller than that of the inverter.
Corrective action y Wire the cables properly. y Check the Pr. 251 Output phase loss protection selection setting.
indication E.OP1
Name Communication option fault Description Inverter output is stopped when a fault occurs on the communication line of FL remote communication.
y Check if the inverter's LED shows any fault.
y Check if the FL-net dedicated cable has a break.
y Check if the length of the FL-net dedicated cable is within the specified range.
y Refer to "Troubleshooting in FL remote communication" on page 209, and take corrective actions for the fault.
y Check the connection of the FL-net dedicated cable.
y Check that each FL-net dedicated cable length between nodes is within the specified range. (Refer to page 46).

Indication E.OPT
y Appears when a node address is set out of the setting range (other than 1 to 64). Also appears when the node
address is set improperly.
y Appears when Pr.296 Password lock level ="0 or 100."
y Check if the node address is set within the range of 1 to 64.
y Check if the node address switch is set between numbers.
y Check if "0 or 100" is set in Pr. 296.
y Set the node address within the range of 1 to 64. (Refer to page 46).
y Set the node address switch to the switch number position correctly. (Refer to page 46).
y Set Pr.296 ≠ "0 or 100" for the password lock.
y If the problem still persists after taking the above measure, please contact your sales representative.
indication E. 1
Description y Inverter output is stopped if there is excess electrical noise around the inverter or in other conditions.
y Appears when the setting of the master is incorrect.
y Check for excess electrical noises around the inverter.
y Check if a protocol other than FL remote protocol is selected. Also check if the number of words in the
transmission/receive area is set to "0."
y Take measures against noises if there are devices producing excess electrical noises around the inverter. y Select FL remote protocol. Set an appropriate number of words for the transmission/receive area. (Refer to page 54
for the setting for the transmission/receive area.) y If the problem still persists after taking the above measure, please contact your sales representative.
indication E.PE
Name Parameter storage device fault (control circuit board) Description Stops the inverter output if fault occurred in the parameter stored. (EEPROM fault) Check point Check for too many number of parameter write times. Corrective action Please contact your sales representative.
Indication E.PE2
Name Internal board fault Description When a combination of control board and main circuit board is wrong, the inverter is tripped. Check point —
Corrective action Please contact your sales representative. (For parts replacement, consult the nearest Mitsubishi FA Center.)
indication E.RET
Name Retry count excess
If operation cannot be resumed properly within the number of retries set, this function trips the inverter. The indication is available only when Pr. 67 Number of retries at fault occurrence is set. When the initial value (Pr. 67 = "0") is set, this protective function is not available. Check point Find the cause of fault occurrence. Corrective action Eliminate the cause of the error preceding this error indication.

E. 6
E. 7
E.CPU
Name CPU fault Description Stops the inverter output if the communication fault of the built-in CPU occurs.
Check point y Check for devices producing excess electrical noises around the inverter. y Check if the terminals PC and SD are shorted. (E.6/ E.7)
y Take measures against noises if there are devices producing excess electrical noises around the inverter. y Check the connection between terminals PC and SD. (E.6/ E.7) y Please contact your sales representative.
indication E.IOH
Name Inrush current limit circuit fault Description Stops the inverter output when the resistor of inrush current limit circuit overheated. The inrush current limit circuit fault Check point Check that frequent power ON/OFF is not repeated.
Corrective action Configure a circuit where frequent power ON/OFF is not repeated. If the problem still persists after taking the above measure, please contact your sales representative.
indication E.13
Name Internal circuit fault Description Stop the inverter output when an internal circuit fault occurred. Corrective action Please contact your sales representative.
indication E.SAF
Name Safety circuit fault
Appears when safety circuit is malfunctioning. Appears when one of the lines between S1 and PC, or between S2 and PC is opened. May appear when the start-up time of the 24V power supply is too long in the 24V external power supply operation.
y If the indication appears when safety stop function is not used, check if shorting wires between S1 and PC, S2 and
PC are connected. y If the indication appears when safety stop function is used, check that the safety relay module or the connection
has no fault. y Check if the start up time of the 24V external power supply is 500ms or longer.
y When not using the safety stop function, short across terminals S1 and PC and across S2 and PC with shorting
wire. (Refer to page 24). y When using the safety stop function, check that wiring of terminal S1, S2 and PC is correct and the safety stop
input signal source such as safety relay module is operating properly. Refer to the Safety stop function instruction manual (BCN-A211508-004) for the details. Refer the front cover of the Instruction Manual (Basic) for how to obtain the manual. y Set the start up time of the 24V external power supply within 500ms.
y If faults other than the above appear, contact your sales representative.

6.4 Correspondences between digital and actual characters
There are the following correspondences between the actual alphanumeric characters and the digital characters displayed on
the operation panel:




6.5 Check first when you have a trouble
POINT y If the cause is still unknown after every check, it is recommended to initialize the parameters (initial value) then
set the required parameter values and check again.

Power ON a moulded case circuit breaker (MCCB), an
Check for the decreased input voltage, input phase loss,
Motor is not connected properly. Check the wiring between the inverter and the motor. 15
When using a DC reactor (FR-HEL), remove the jumper
across P/+ and P1, and then connect the DC reactor.
Check the start command source, and input a start
Turn ON only one of the forward and reverse rotation
Both the forward and reverse rotation start signals (STF,
If STF and STR signals are turned ON simultaneously in
(RUN LED on the operation panel is flickering.) Enter a frequency command. 58
Output stop signal (MRS) or error reset is ON.
Inverter starts the operation with a given start command
(RUN LED on the operation panel flickers while MRS
Shorting wires across S1 and PC and across S2 and
When not using the safety stop function, short across
terminals S1 and PC and across S2 and PC with
of restarting from a input stop from the operation
The setting value "1" is set in the X12 signal (Bit11),
Set "0" in the X12 signal (Bit11), which gives a control
which gives a control input command through FL remote
Pr. 0 Torque boost setting is improper when V/F control is
Set Pr. 78 when you want to limit the motor rotation to
Pr. 13 Starting frequency setting is greater than the
The inverter does not start if the frequency setting signal
is less than the value set in Pr. 13.
Set Pr. 1 higher than the actual frequency used.
Pr. 15 Jog frequency setting is lower than the Pr. 13
Set Pr. 15 Jog frequency higher than Pr. 13 Starting

points Possible Cause Countermeasures
When power is restored, ensure the safety, and turn
Inverter decelerated to a stop when power failure
OFF the start signal once, then turn ON again to restart.
deceleration stop function is selected.
Inverter restarts when Pr. 261="2".
When offline auto tuning ends, press of the
operation panel. For the Network operation, turn OFF
Performing auto tuning.
the start signal (STF or STR).
This operation resets the offline auto tuning, and the
operation panel monitor display returns to the normal.
(Without this operation, next operation cannot be started.)
Load Load is too heavy. Reduce the load. —
Shaft is locked. Inspect the machine (motor). —
When any fault occurs, take an appropriate corrective
Others Operation panel display shows an error (e.g. E.OC1).
action, then reset the inverter, and resume the
operation.
points Possible Cause Countermeasures
In the initial setting, Pr. 240 Soft-PWM operation selection is
enabled to change motor noise to an unoffending
No carrier frequency noises (metallic noises) are
complex tone. Therefore, no carrier frequency noises
generated.
(metallic noises) are generated.
Set Pr. 240 = "0" to disable this function.
Set Pr. 31 to Pr. 36 (Frequency jump).
When it is desired to avoid resonance attributable to the
Resonance occurs. (output frequency)
natural frequency of a mechanical system, these
parameters allow resonant frequencies to be jumped.
Change Pr. 72 PWM frequency selection setting.
Changing the PWM carrier frequency produces an effect
Resonance occurs. (carrier frequency)
on avoiding the resonance frequency of a mechanical
system or a motor.
Auto tuning is not performed under Advanced magnetic
flux vector control or General-purpose magnetic flux
Perform offline auto tuning. 127
vector control.
Others Mechanical looseness Adjust machine/equipment so that there is no
mechanical looseness. —
Motor Operating with output phase loss Check the motor wiring. —
Contact the motor manufacturer.
points Possible Cause Countermeasures
Fan Fan cover was not correctly installed when a cooling fan
was replaced. Install a fan cover correctly. 216

6.5.4 Motor generates heat abnormally
points Possible Cause Countermeasures
Motor fan is not working
Clean the motor fan.
Improve the environment. —
(Dust is accumulated.)
Phase to phase insulation of the motor is insufficient. Check the insulation of the motor. — Main
The inverter output voltage (U, V, W) are unbalanced. Check the output voltage of the inverter.
Check the insulation of the motor. 213
The Pr. 71 Applied motor setting is wrong. Check the Pr. 71 Applied motor setting. 125
— Motor current is large. Refer to "6.5.11 Motor current is too large" 208
points Possible Cause Countermeasures
Phase sequence of output terminals U, V and W is
Connect phase sequence of the output cables (terminal
U, V, W) to the motor correctly 15
incorrect.
Pr. 40 RUN key rotation direction selection setting is
incorrect. Check the Pr. 40 setting. 182
points Possible Cause Countermeasures
Pr. 1, Pr. 2, Pr. 18 settings are improper. Check the settings of Pr. 1 Maximum frequency, Pr. 2
Minimum frequency, Pr. 18 High speed maximum frequency. 105
Pr. 31 to Pr. 36 (frequency jump) settings are improper. Narrow down the range of frequency jump. 106 Load
Reduce the load weight. —
Set Pr. 22 Stall prevention operation level higher according
Stall prevention function is activated due to a heavy
to the load. (Setting Pr. 22 too large may result in
load.
frequent overcurrent trip (E.OC ).)
Motor Check the capacities of the inverter and the motor. —
points Possible Cause Countermeasures
For V/F control, set Pr. 3 Base frequency and Pr. 47 Second
V/F (base frequency). 107
The base frequency does not match the motor
For Advanced magnetic flux vector control or General-
characteristics.
purpose magnetic flux vector control, set Pr. 84 Rated
motor frequency.
Reduce the load weight. —
Set Pr. 22 Stall prevention operation level higher according
Stall prevention function is activated due to a heavy
to the load. (Setting Pr. 22 too large may result in
load.
frequent overcurrent trip (E.OC ).)
Check the capacities of the inverter and the motor. —
Acceleration/deceleration time is too short. Increase acceleration/deceleration time. 116
Torque boost (Pr. 0, Pr. 46) setting is improper under V/F
Increase/decrease Pr. 0 Torque boost setting value by
0.5% increments to the setting. 94
control, so the stall prevention function is activated.
If the frequency becomes unstable during regeneration
Regeneration avoidance operation is performed
avoidance operation, decrease the setting of Pr. 886
Regeneration avoidance voltage gain.

6.5.8 Speed varies during operation
When Advanced magnetic flux vector control or the slip compensation is selected, the output frequency varies between 0 and
2Hz as load fluctuates. This is a normal operation and not a fault.
points Possible Cause Countermeasures
Load Load varies during an operation. Select Advanced magnetic flux vector control or
General-purpose magnetic flux vector control. 95
Frequency setting signal is varying. Check the frequency setting signal. —
Pr. 80 Motor capacity and Pr. 81 Number of motor poles
setting is improper for the capacities of the inverter and
Check the Pr. 80 Motor capacity and Pr. 81 Number of
motor poles setting. 95
the motor for Advanced magnetic flux vector control or
General-purpose magnetic flux vector control.
Fluctuation of power supply voltage is too large. Change the Pr. 19 Base frequency voltage setting (about
3%) under V/F control. 107
Disable automatic control functions, such as energy
saving operation, fast-response current limit function,
regeneration avoidance function, Advanced magnetic
Hunting occurs by the generated vibration, for example,
flux vector control, General-purpose magnetic flux
when structural rigidity at load side is insufficient.
vector control, and stall prevention.
Adjust so that the control gain decreases and the level of
safety increases.
Change Pr. 72 PWM frequency selection setting. 163
Wiring length exceeds 30m when Advanced magnetic
flux vector control or General-purpose magnetic flux
Perform offline auto tuning. 127
vector control is performed.
Adjust Pr. 0 Torque boost by increasing with 0.5%
increments for low-speed operation. 94
Wiring length is too long for V/F control, and a voltage
drop occurs.
Change to Advanced magnetic flux vector control or
General-purpose magnetic flux vector control. 95
points Possible Cause Countermeasures
Check that the STF and STR signals are OFF.
Start signal (STF or STR) is ON.
When either is ON, the operation mode cannot be
changed.
"0" is set in the X12 signal (Bit11), which gives a control
Set "1" in the X12 signal (Bit11), which gives a control
input command through FL remote communication. 57
input command through FL remote communication.
Others FL-net dedicated cable is not installed properly. (The
cable has contact faults and breaks.) Install the FL-net dedicated cable properly. 48
points Possible Cause Countermeasures
Check for the wiring and the installation.
Wiring or installation is improper.
14 Make sure that the connector is fitted securely across
terminal P/+ and P1. Main
Power is not input. Input the power. 14

6.5.11 Motor current is too large
Check points Possible Cause Countermeasures
Torque boost (Pr. 0, Pr. 46) setting is improper under V/F control, so the stall prevention function is activated.
Increase/decrease Pr. 0 Torque boost setting value by 0.5% increments to the setting. 94
Set rated frequency of the motor to Pr. 3 Base frequency. Use Pr. 19 Base frequency voltage to set the base voltage (e.g. rated motor voltage).
V/F pattern is improper when V/F control is performed. (Pr. 3, Pr. 14, Pr. 19)
Change Pr. 14 Load pattern selection according to the load characteristic. 109
Reduce the load weight. — Set Pr. 22 Stall prevention operation level higher according to the load. (Setting Pr. 22 too large may result in frequent overcurrent trip (E.OC ).)
Stall prevention function is activated due to a heavy load.
Check the capacities of the inverter and the motor. — Auto tuning is not performed under Advanced magnetic flux vector control or General-purpose magnetic flux vector control.
Perform offline auto tuning. 127
Check points Possible Cause Countermeasures
Check the settings of Pr. 1 Maximum frequency and Pr. 2 Minimum frequency. If you want to run the motor at 120Hz or higher, set Pr. 18 High speed maximum frequency.
Pr. 1, Pr. 2, Pr. 18 settings are improper.
Torque boost (Pr. 0, Pr. 46) setting is improper under V/F control, so the stall prevention function is activated.
Increase/decrease Pr. 0 Torque boost setting value by 0.5% increments so that stall prevention does not occur. 94
Set rated frequency of the motor to Pr. 3 Base frequency. Use Pr. 19 Base frequency voltage to set the base voltage (e.g. rated motor voltage).
V/F pattern is improper when V/F control is performed. (Pr. 3, Pr. 14, Pr. 19)
Change Pr. 14 Load pattern selection according to the load characteristic. 109
Reduce the load weight. — Set Pr. 22 Stall prevention operation level higher according to the load. (Setting Pr. 22 too large may result in frequent overcurrent trip (E.OC ).)
Stall prevention function is activated due to a heavy load.
Check the capacities of the inverter and the motor. — Auto tuning is not performed under Advanced magnetic flux vector control or General-purpose magnetic flux vector control.
Perform offline auto tuning. 127
Brake resistor is connected between terminal P/+ and P1 or between terminal P1 and PR by mistake.
Connect an optional brake transistor (MRS type, MYS type, FR-ABR) between terminal P/+ and PR. 25
Check points Possible Cause Countermeasures
Stop the operation. When Pr. 77 = "0" (initial value), write is enabled only during a stop.
Operation is being performed (signal STF or STR is ON).
"0" is set in the X12 signal (Bit11), which gives a control input command through FL remote communication.
Set "1" in the X12 signal (Bit11), which gives a control input command through FL remote communication. 57
Choose the PU operation mode. Or, set Pr. 77 = "2" to enable parameter write regardless of the operation mode.
You are attempting to set a parameter from the operation panel while in Network operation mode.
Parameter is disabled by the Pr. 77 Parameter write selection setting. Check Pr. 77 Parameter write selection setting. 166
Key lock is activated by the Pr. 161 Frequency setting/key lock operation selection setting.
Check Pr. 161 Frequency setting/key lock operation selection setting. 183

6.5.14 Troubleshooting in FL remote communication
If a fault occurs and the inverter fails to operate properly, locate the cause of the fault and take proper corrective action by referring to the troubleshooting below. If the corresponding information is not found in the table, the inverter has problem, or
the component parts are damaged, contact your sales representative.
Possible Causes Check Point Countermeasure Operation
(Refer to page 49)
The firmware has an internal
fault. — Please contact your sales
representative.
Select the FL remote protocol.
Check if a protocol other than FL
Set an appropriate number of
remote protocol is selected. Also
Incorrect setting to the
words for the transmission/
check if the number of words in the
receive area. (Refer to page 54
transmission/receive area is set to
for the setting of the
"0."
transmission/receive area.)
— Please contact your sales
communication circuit in the
representative.
inverter is faulty.
Set the node address within
Node address is out of range
Check that the node address
the range (1 to 64)
(other than 1 to 64).
setting is within the range (1 to 64).
(Refer to page 46)
Check that the node address
Set the node address switch to
Node address is not
switch is not set between
the number position correctly.
correctly set.
numbers.
(Refer to page 46)
— Please contact your sales
communication circuit in the
representative.
inverter is faulty.
The inverter is not
participated in FL remote
between the inverter and
Check that no break in the cable
Make sure to connect the
disconnected.
between the inverter and switching
cable between the inverter and
switching hub. DEV
After the inverter participated
hub.
in FL remote network,
inverter and switching hub is
disconnected.
Check that node address setting of
Set the node address of the
the inverter and slave station
inverter and slave station of
established.
setting of the master are the same.
the master to the same setting.
RMT Unsupported protocol A protocol other than FL remote is
Use the master that has the FL
selected.
remote setting.
:OFF, : red is lit, : green is lit, :red is flickering


This chapter provides the "PRECAUTIONS FOR MAINTENANCE AND INSPECTION" of this product. Always read the instructions before using the equipment.
7.1 Inspection items 212 7.2 Measurement of main circuit voltages, currents and powers . 218

The inverter is a static unit mainly consisting of semiconductor devices. Daily inspection must be performed to prevent any
fault from occurring due to the adverse effects of the operating environment, such as temperature, humidity, dust, dirt and
vibration, changes in the parts with time, service life, and other factors.
zPrecautions for maintenance and inspection
When accessing the inverter for inspection, wait for at least 10 minutes after the power supply has been switched OFF, and then make sure that the voltage across the main circuit terminals P/+ and N/- of the inverter is not more than 30VDC using a
tester, etc. The capacitor is charged with high voltage for some time after power OFF, and it is dangerous. If "EV" is displayed on the operation panel, turn off the 24V external power supply before inspection.
Basically, check for the following faults during operation. (1) Motor operation fault
(2) Improper installation environment (3) Cooling system fault
(4) Abnormal vibration, abnormal noise (5) Abnormal overheat, discoloration
Check the areas inaccessible during operation and requiring periodic inspection. For a periodic inspection, contact your sales representative.
(1) Check for cooling system fault Clean the air filter, etc. (2) Tightening check and retightening The screws and bolts may become loose due to vibration, temperature changes,
etc. Check and tighten them. Tighten them according to the specified tightening torque (Refer to page 17).
(3) Check the conductors and insulating materials for corrosion and damage. (4) Measure insulation resistance.
(5) Check and change the cooling fan and relay.
When using the safety stop function, periodic inspection is required to confirm that safety function of the safety system operates correctly.
(For more details, refer to the Safety stop function instruction manual (BCN-A211508-004)). (Refer to the front cover of the Instruction Manual (Basic) for how to obtain the manual.)

7.1.3 Daily and periodic inspection
Interval Corrective Action at
Inspection Inspection Item Description
Check the surrounding air temperature, humidity, dirt, corrosive gas, oil mist, etc. { Improve environment
Overall unit Check for unusual vibration and noise. { Check alarm location and retighten
Power supply voltage Check that the main circuit voltages are normal.∗1 { Inspect the power supply
(1) Check with megger (across main circuit
terminals and earth (ground) terminal). { Contact the manufacturer
(2) Check for loose screws and bolts. { Retighten
(3) Check for overheat traces on the parts. { Contact the manufacturer
(4) Check for stain { Clean
(1) Check conductors for distortion. (2) Check cable sheaths for breakage and
{ Contact the manufacturer
{ Contact the manufacturer
deterioration (crack, discoloration, etc.)
Terminal block Check for damage. { Stop the device and contact the manufacturer.
(1) Check for liquid leakage. { Contact the manufacturer
(2) Check for safety valve projection and
bulge. { Contact the manufacturer
Smoothing aluminum electrolytic capacitor
(3) Visual check and judge by the life check
of the main circuit capacitor (Refer to page 214)
Relay Check that the operation is normal and no chatter is heard. { Contact the manufacturer
(1) Check that the output voltages across
phases with the inverter operated alone is
{ Contact the manufacturer
(2) Check that no fault is found in protective
and display circuits in a sequence protective operation test.
{ Contact the manufacturer
(1) Check for unusual odor and
discoloration. { Stop the device and contact the manufacturer.
(2) Check for serious rust development { Contact the manufacturer
(1) Check for liquid leakage in a capacitor
and deformation trace { Contact the manufacturer
(2) Visual check and judge by the life check
of the main circuit capacitor (Refer to page 214)
(1) Check for unusual vibration and noise. { Replace the fan
(2) Check for loose screws and bolts { Fix with the fan cover fixing screws
(3) Check for stain { Clean
(1) Check for clogging { Clean
(2) Check for stain { Clean
(1) Check that display is normal. { Contact the manufacturer
(2) Check for stain { Clean
Meter Check that reading is normal { Stop the device and contact the manufacturer.
Load motor Operation check Check for vibration and abnormal increase in operation noise { Stop the device and contact the manufacturer.
∗1 It is recommended to install a device to monitor voltage for checking the power supply voltage to the inverter.
∗2 One to two years of periodic inspection cycle is recommended. However, it differs according to the installation environment.
For a periodic inspection, contact your sales representative.

7.1.4 Display of the life of the inverter parts
The self-diagnostic alarm is output when the life span of the control circuit capacitor, cooling fan and each parts of the inrush current limit circuit is near its end. It gives an indication of replacement time.
The life alarm output can be used as a guideline for life judgment.

Cooling fan Less than 50% of the predetermined speed
Refer to page 177 to perform the life check of the inverter parts.
(1) Disconnect the external power supply cables (R/L1, S/L2, T/L3) and motor cables (U, V, W). (2) Prepare a tester. (Use 100Ω range.)
Change the polarity of the tester alternately at the inverter terminals R/L1, S/L2, T/L3, U, V, W, P/+ and N/-, and check for electric continuity.
to the smoothing capacitor, the tester may not indicate ∞. At the time of electric continuity, the measured value is
several to several tens-of ohms depending on the module type, circuit tester type, etc. If all measured values are
almost the same, the modules are without fault.

(Assumes the use of an analog meter.)
Always run the inverter in a clean status. When cleaning the inverter, gently wipe dirty areas with a soft cloth immersed in neutral detergent or ethanol.
Do not use solvent, such as acetone, benzene, toluene and alcohol, as they will cause the inverter surface paint to peel off.
The display, etc. of the operation panel are vulnerable to detergent and alcohol. Therefore, avoid using them for
cleaning.

7.1.7 Replacement of parts
The inverter consists of many electronic parts such as semiconductor devices.
The following parts may deteriorate with age because of their structures or physical characteristics, leading to reduced performance or fault of the inverter. For preventive maintenance, the parts must be replaced periodically.
Use the life check function as a guidance of parts replacement.

capacitor 10 years ∗2 Replace the board (as required)
∗1 Estimated lifespan for when the yearly average surrounding air temperature is 40°C
(without corrosive gas, flammable gas, oil mist, dust and dirt etc.)
For parts replacement, contact the nearest Mitsubishi FA Center.
The replacement interval of the cooling fan used for cooling the parts generating heat such as the main circuit semiconductor
is greatly affected by the surrounding air temperature. When unusual noise and/or vibration is noticed during inspection, the cooling fan must be replaced immediately.



the fan so that the arrow on the left of "AIR FLOW" faces up.
y Installing the fan in the opposite of air flow direction can cause the inverter life to be shorter. y Prevent the cable from being caught when installing a fan. y Switch the power OFF before replacing fans. Since the inverter circuits are charged with voltage even after
power OFF, replace fans only when the inverter cover is on the inverter to prevent an electric shock accident.

A large-capacity aluminum electrolytic capacitor is used for smoothing in the main circuit DC section, and an aluminum electrolytic capacitor is used for stabilizing the control power in the control circuit. Their characteristics are deteriorated by the adverse effects of ripple currents, etc. The replacement intervals greatly vary with the surrounding air temperature and operating conditions. When the inverter is operated in air-conditioned, normal environment conditions, replace the capacitors about every 10 years. When a certain period of time has elapsed, the capacitors will deteriorate more rapidly. Check the capacitors at least every year (less than six months if the life will be expired soon). The appearance criteria for inspection are as follows: 1) Case: Check the side and bottom faces for expansion 2) Sealing plate: Check for remarkable warp and extreme crack. 3) Check for external crack, discoloration, liquid leakage, etc. Judge that the capacitor has reached its life when the measured capacitance of the capacitor reduced below 80% of the rating.
Refer to page 177 to perform the life check of the main circuit capacitor.
To prevent a contact fault, etc., relays must be replaced according to the cumulative number of switching times (switching life).

7.2 Measurement of main circuit voltages, currents and powers
Since the voltages and currents on the inverter power supply and output sides include harmonics, measurement data
depends on the instruments used and circuits measured. When instruments for commercial frequency are used for measurement, measure the following circuits with the instruments
given on the next page. z When installing meters etc. on the inverter output side
When the inverter-to-motor wiring length is large, especially in the 400V class, small-capacity models, the meters and CTs may generate heat due to line-to-line leakage current. Therefore, choose the equipment which has enough allowance for
the current rating.


Item Measuring Point Measuring Instrument Remarks (Reference Measured Value)
Across R/L1 and S/L2
Within permissible AC voltage fluctuation (Refer to
R/L1, S/L2, T/L3 line
R/L1, S/L2, T/L3 and
(designed for inverter) or
P1=W11+W12+W13 (3-wattmeter method)
Calculate after measuring power supply voltage, power
supply side current and power supply side power.
Pf1 P1 3V1 I × 1 100 × = %
Rectifier type AC voltage
Across U and V,
Difference between the phases is within 1% of the
V and W and W and U
maximum output voltage.
I2 U, V and W line currents Moving-iron type AC
Difference between the phases is 10% or lower of
the rated inverter current.
U, V, W and
(designed for inverter) or
P 2
U and V, V and W
2-wattmeter method (or 3-wattmeter method)
Calculate in similar manner to power supply side power factor.
Pf2 P2 3V2 I2 × 100 × = %
Inverter LED display is lit. 1.35 × V1
Converter output Across P/+ and N/- Moving-coil type
380V maximum during regeneration for 200V class
760V maximum during regeneration for 400V class
∗1 Use an FFT to measure the output voltage accurately. An FA tester or general measuring instrument cannot measure accurately.
∗2 When the carrier frequency exceeds 5kHz, do not use this instrument since using it may increase eddy-current losses produced in metal parts inside the
instrument, leading to burnout. In this case, use an approximate-effective value type.
∗3 A digital power meter (designed for inverter) can also be used to measure.

7.2.1 Measurement of powers
Use digital power meters (for inverter) for the both of inverter input and output side. Alternatively, measure using
electrodynamic type single-phase wattmeters for the both of inverter input and output side in two-wattmeter or three- wattmeter method. As the current is liable to be imbalanced especially in the input side, it is recommended to use the three-
wattmeter method. Examples of process value differences produced by different measuring meters are shown below.
An error will be produced by difference between measuring instruments, e.g. power calculation type and two- or three- wattmeter type three-phase wattmeter. When a CT is used in the current measuring side or when the meter contains a PT on
the voltage measurement side, an error will also be produced due to the frequency characteristics of the CT and PT.
[Measurement conditions]
Constant-torque (100%) load, note that 60Hz or more should be constantly output 3.7kW, 4-pole
Constant-torque (100%) load, note that 60Hz or more should be constantly output 3.7kW, 4-pole
motor, value indicated in 3-wattmeter method is 100%.
motor, value indicated in 3-wattmeter method is 100%.
3-wattmeter method (Electro-dynamometer type) 2-wattmeter method (Electro-dynamometer type) Clip AC power meter (For balanced three-phase load) Clamp-on wattmeter (Hall device power arithmetic type)
3-wattmeter method (Electro-dynamometer type) 2-wattmeter method (Electro-dynamometer type) Clip AC power meter (For balanced three-phase load) Clamp-on wattmeter (Hall device power arithmetic type)
0 20 40 60 80 100 120Hz
0 20 40 60 80 100 120Hz
Example of
Measuring Inverter Input Power
Measuring Inverter Output Power
7.2.2 Measurement of voltages and use of PT
(1) Inverter input side
As the input side voltage has a sine wave and it is extremely small in distortion, accurate measurement can be made with an ordinary AC meter. (2) Inverter output side
Since the output side voltage has a PWM-controlled rectangular wave, always use a rectifier type voltmeter. A needle type tester can not be used to measure the output side voltage as it indicates a value much greater than the actual value. A moving-iron type meter indicates an effective value which includes harmonics and therefore the value is larger than that of the fundamental wave. The value monitored on the operation panel is the inverter-controlled voltage itself. Hence, that value is accurate and it is recommended to monitor values using the operation panel. (3) PT
No PT can be used in the output side of the inverter. Use a direct-reading meter. (A PT can be used in the input side of the inverter.)
120 % · 120 %

7.2.3 Measurement of currents
Use a moving-iron type meter on both the input and output sides of the inverter. However, if the carrier frequency exceeds 5kHz, do not use that meter since an overcurrent losses produced in the internal metal parts of the meter will increase and the meter may burn out. In this case, use an approximate-effective value type. Since current on the inverter input side tends to be unbalanced, measurement of three phases is recommended. Correct value can not be obtained by measuring only one or two phases. On the other hand, the unbalanced ratio of each phase of the output side current should be within 10%. When a clamp ammeter is used, always use an effective value detection type. A mean value detection type produces a large error and may indicate an extremely smaller value than the actual value. The value monitored on the operation panel is accurate if the output frequency varies, and it is recommended to monitor values (provide analog output) using the operation panel. Examples of process value differences produced by different measuring meters are shown below.
[Measurement conditions] Value indicated by moving-iron type ammeter is 100%.
[Measurement conditions] Value indicated by moving-iron type ammeter is 100%.
Clip AC power meter
Clip AC power meter
Clamp-on wattmeter current measurement
Clamp-on wattmeter current measurement Clamp meter
0 60Hz 40 20
0 60Hz 40 20
Example of measuring inverter output current
7.2.4 Use of CT and transducer
A CT may be used in both the input and output sides of the inverter, but the one used should have the largest possible VA ability because an error will increase if the frequency gets lower.
When using a transducer, use the effective value calculation type which is immune to harmonics.
Calculate using effective power and apparent power. A power-factor meter can not indicate an exact value.
Total power factor of the inverter = Effective power
3-phase input power found by 3-wattmeter method
× V (power supply voltage) × I (input current effective value)
The output voltage of the converter is developed across terminals P and N and can be measured with a moving-coil type
meter (tester). Although the voltage varies according to the power supply voltage, approximately 270VDC to 300VDC (540VDC to 600VDC for the 400V class) is output when no load is connected and voltage decreases during driving load
operation. When energy is regenerated from the motor during deceleration, for example, the converter output voltage rises to nearly
400VDC to 450VDC (800VDC to 900VDC for the 400V class) maximum.

7.2.7 Insulation resistance test using megger
z For the inverter, conduct the insulation resistance test on the main circuit only as shown below and do not perform the test
on the control circuit. (Use a 500VDC megger.)
U V W
NOTE
y Before performing the insulation resistance test on the external circuit, disconnect the cables from all terminals of
the inverter so that the test voltage is not applied to the inverter.
y For the electric continuity test of the control circuit, use a tester (high resistance range) and do not use the megger or
buzzer.
Do not conduct a pressure test. Deterioration may occur.

This chapter provides the "SPECIFICATIONS" of this product.
Always read the instructions before using the equipment.
8.2 Common specifications .............................................................. 225
8.3 Outline dimension drawings....................................................... 226

8.1 Rating
z Three-phase 200V power supply

Model FR-E720- KNF 0.1 0.2 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15
Applicable motor capacity (kW) ∗1 0.1 0.2 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15
Rated capacity (kVA) ∗2 0.3 0.6 1.2 2.0 3.2 4.4 7.0 9.5 13.1 18.7 23.9
Overload current rating ∗3 150% 60s, 200% 3s (inverse-time characteristics)
AC (DC) voltage/frequency Three-phase 200 to 240V 50Hz/60Hz (283 to 339VDC ∗8)
fluctuation 170 to 264V 50Hz/60Hz (240 to 373VDC ∗8)
Power supply capacity (kVA) ∗6 0.4 0.8 1.5 2.5 4.5 5.5 9 12 17 20 28
Approximate mass (kg) 0.5 0.5 0.7 1.0 1.4 1.4 1.7 4.3 4.3 6.5 6.5
z Three-phase 400V power supply

Model FR-E740- KNF 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15
Applicable motor capacity (kW)∗1 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15
Rated capacity (kVA)∗2 1.2 2.0 3.0 4.6 7.2 9.1 13.0 17.5 23.0
Overload current rating∗3 150% 60s, 200% 3s (inverse-time characteristics)
Power supply capacity (kVA)∗6 1.5 2.5 4.5 5.5 9.5 12 17 20 28
Approximate mass (kg) 1.4 1.4 1.9 1.9 1.9 3.2 3.2 6.0 6.0
∗1 The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi 4-pole standard motor. ∗2 The rated output capacity indicated assumes that the output voltage is 230V for three-phase 200V class and 440V for three-phase 400V class. ∗3 The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For repeated duty, allow time for the inverter and motor to return to or below the temperatures under 100% load. ∗4 The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range. However, the pulse voltage value of the inverter output side voltage remains unchanged at about that of the power supply. ∗5 The braking torque indicated is a short-duration average torque (which varies with motor loss) when the motor alone is decelerated from 60Hz in the shortest time and is not a continuous regenerative torque. When the motor is decelerated from the frequency higher than the base frequency, the average deceleration torque will reduce. Since the inverter does not contain a brake resistor, use the optional brake resistor when regenerative energy is large. A brake unit (FR-BU2) may also be used. (Option brake resistor cannot be used for 0.1K and 0.2K.) ∗6 The power supply capacity varies with the value of the power supply side inverter impedance (including those of the input reactor and cables). ∗7 Setting 2kHz or more in Pr. 72 PWM frequency selection to perform low acoustic noise operation in the surrounding air temperature exceeding 40°C, the rated output current is the value in parenthesis. ∗8 y Connect DC power supply to terminal P/+ and N/-. Connect the plus side of the power supply to terminal P/+ and minus side to terminal N/-. y Since the voltage between P/+ and N/- may increase due to the regeneration energy from the motor and exceeds 415V temporarily, select the DC power
supply which can withstand the voltage/energy during regeneration. If using the power supply which can not withstand voltage/energy during regeneration, insert diodes in series for reverse current prevention. y Although the FR-E700 series has the built-in inrush current limit circuit, select the DC power supply considering the inrush current at powering ON as the
inrush current four times of the rated inverter flows at powering ON. y Since the power supply capacity depends on the output impedance of the power, select the power supply capacity which has enough allowance according
to the AC power supply system capacity.

8.2 Common specifications
Control method Soft-PWM control/high carrier frequency PWM control (V/F control, Advanced magnetic flux vector control, General-purpose magnetic flux vector control, Optimum excitation control are available)
Output frequency range 0.2 to 400Hz
Frequency setting resolution (Digital input) 0.01Hz
Frequency accuracy (Digital input) Within 0.01% of the set output frequency
Voltage/frequency characteristics Base frequency can be set from 0 to 400Hz, Constant-torque/variable torque pattern can be selected
Starting torque 200% or more (at 0.5Hz)...when Advanced magnetic flux vector control is set (3.7K or lower)
Torque boost Manual torque boost
Acceleration/deceleration time setting 0.01 to 360s, 0.1 to 3600s (acceleration and deceleration can be set individually), linear or S-pattern acceleration/
deceleration modes are available.
DC injection brake Operation frequency (0 to 120Hz), operation time (0 to 10s), operation voltage (0 to 30%) can be changed.
Stall prevention operation level Operation current level can be set (0 to 200% adjustable), whether to use the function or not can be selected.
Frequency setting signal (Digital input)
Signals are entered from the operation panel or through FL remote communication. Frequency setting increments can be set.
Start signal Forward and reverse rotation can be selected.
Maximum/minimum frequency setting, frequency jump operation, automatic restart after instantaneous power failure operation, forward/reverse rotation prevention, remote setting, second function, multi-speed operation, stop-on contact control, droop control, regeneration avoidance, slip compensation, operation mode selection, offline auto tuning function
Safety stop function∗2 Safety shutoff signal can be input from terminals S1 and S2. (compliant with EN ISO 13849-1 Category 3 / PLd EN62061 / IEC61508 SIL2)
Open collector output (One terminal) Safety monitor output 2 (Fixed) Operating status
The following operating status can be displayed: output frequency, motor current (steady), output voltage, frequency setting, cumulative energization time, actual operation time, motor torque, converter output voltage, regenerative brake duty, electronic thermal relay function load factor, output current peak value, converter output voltage peak value, motor load factor, inverter output terminal monitor, output power, cumulative power, motor thermal load factor, and inverter thermal load factor.
Indication on the operation panel
Fault record Fault record is displayed when a fault occurs. Past 8 fault records (output voltage/current/frequency/cumulative energization time right before the fault occurs) are stored.
Overcurrent during acceleration, overcurrent during constant speed, overcurrent during deceleration, overvoltage during acceleration, overvoltage during constant speed, overvoltage during deceleration, inverter protection thermal operation, motor protection thermal operation, heatsink overheat, input phase failure, stall prevention stop, output side earth (ground) fault overcurrent at start∗4, output short circuit, output phase failure, option fault, parameter error, retry count excess ∗4, CPU fault, brake transistor alarm, inrush resistance overheat, communication error, safety circuit fault
Fan alarm∗2, overcurrent stall prevention, overvoltage stall prevention, PU stop, parameter write error, regenerative brake prealarm ∗4, electronic thermal relay function prealarm, maintenance output ∗4, undervoltage, operation panel lock, password locked∗4, inverter reset, safety stop, 24V external power supply operation
Surrounding air temperature -10°C to +50°C (non-freezing) ∗3
Ambient humidity 90%RH or less (non-condensing)
Storage temperature∗1 -20°C to +65°C
Atmosphere Indoors (without corrosive gas, flammable gas, oil mist, dust and dirt etc.)
Altitude/vibration Maximum 1000m above sea level, 5.9m/s 2 or less at 10 to 55Hz (directions of X, Y, Z axes)
∗1 Temperatures applicable for a short time, e.g. in transit. ∗2 As the FR-E720-0.1KNF to 0.75KNF, FR-E740-0.4KNF and 0.75KNF are not provided with the cooling fan, this alarm is not available. ∗3 When using the inverters at the surrounding air temperature of 40°C or less, the inverters can be installed closely attached (0cm clearance). ∗4 This protective function is not available in the initial status.

8.3 Outline dimension drawings
zFR-E720-0.1KNF to 0.75KNF

Inverter Model D D1 FR-E720-0.1KNF, 0.2KNF 89.5 10 FR-E720-0.4KNF 121.5 42 FR-E720-0.75KNF 141.5 62
zFR-E720-1.5KNF, 2.2KNF


zFR-E720-3.7KNF

zFR-E720-5.5KNF to 15KNF


zFR-E740-0.4KNF to 3.7KNF

∗1 FR-E740-0.4KNF, 0.75KNF are not provided with the cooling fan.
zFR-E740-5.5KNF, 7.5KNF



zFR-E740-11KNF, 15KNF


This chapter provides the "APPENDIX" of this product. Always read the instructions before using the equipment.

Check the SERIAL number indicated on the inverter rating plate or package. (Refer to page 2)
{ { {{{{{{ Symbol Year Month Control number
SERIAL (Serial No.)
The SERIAL consists of one symbol, two characters indicating
production year and month, and six characters indicating control
number.
The last digit of the production year is indicated as the Year, and
the Month is indicated by 1 to 9, X (October), Y (November), and
Z (December).
The changes apply to the December 2010 production or later. (Refer to page 24) y The operating conditions (E.6, E.7, and E.CPU) are added for the SAFE2 signal, which are used in the safety stop
function.
Rating plate example




*The manual number is given on the bottom left of the back cover.
Print Date ∗Manual Number Revision Feb. 2011 IB(NA)-0600398ENG-A First edition

IB(NA)-0600398ENG-A (1102)MEE Printed in Japan Specifications subject to change without notice.
Pages referenced in this manual — manufacturer, support and downloads.
What the fault codes shown on the display mean and how to clear them.
| Code | Meaning | Fix | |
|---|---|---|---|
| D1 | Communication setting status LED (CHG) | p.25 | |
| D2 | Device status LED (DEV) | p.25 | |
| D4 | Remote status LED (RMT) | p.25 | |
| H0010 | Address error | p.72 | |
| H0020 | Size error | p.72 | |
| H0030 | Data error | p.72 | |
| H0040 | Write disable error | p.72 | |
| H0060 | During reset | p.72 | |
| H10000190 | Output frequency | p.76 | |
| H10000192 | Output current | p.76 | |
| H10000194 | Output voltage | p.76 | |
| H10000198 | Set frequency | p.76 | |
| H1000019C | Motor torque | p.76 | |
| H1000019E | Converter output voltage | p.76 | |
| H100001A0 | Regenerative brake duty | p.76 | |
| H100001A2 | Electronic thermal relay function load factor | p.76 | |
| H100001A4 | Output current peak value | p.76 | |
| H100001A6 | Converter output voltage peak value | p.76 | |
| H100001AA | Output power | p.76 | |
| H100001AE | Output terminal status ∗ | p.76 | |
| H100001B6 | Cumulative energization time | p.76 | |
| H100001BC | Actual operation time | p.76 | |
| H100001BE | Motor load factor | p.76 | |
| H100001C0 | Cumulative power | p.76 | |
| H10000208 | Motor thermal load factor | p.76 | |
| H1000020A | Inverter thermal load factor | p.76 | |
| H1000020C | Cumulative power 2 | p.76 | |
| 8 | Forced end | Set "1" or "11" in Pr. 96 and perform tuning again. | p.136 |
| 9 | Inverter protective function operation | Make setting again. | p.136 |
| 91 | Current limit (stall prevention) function was activated. | Set "1" in Pr. 156. | p.136 |
| 92 | Converter output voltage reached 75% of rated value. | Check for fluctuation of power supply voltage. | p.136 |
| 93 | Calculation error A motor is not connected. | Check the motor wiring and make setting again. Set the rated current of the motor in Pr. 9. | p.136 |
| E.1 | The firmware has an internal fault. | — | p.214 |
| E.OP1 | The inverter is not participated in FL remote network and communication between the inverter and switching hub is disconnected. | Check that no break in the cable between the inverter and switching hub. | p.214 |