Hardware Manual
Manual revision : C
Date : September 2008



Mitsubishi has a world wide reputation for its efforts in continually developing and pushing back the frontiers of industrial automation. What is sometimes overlooked by the user is the care and attention to detail that is taken with the documentation. However, to continue this process of improvement, the comments of the Mitsubishi users are always welcomed. This page has been designed for you, the reader, to fill in your comments and fax them back to us. We look forward to hearing from you.
Fax numbers: Your name:
Mitsubishi Electric
America (01) 847-478-2253 Your company:
Australia (02) 638-7072
Germany (0 21 02) 4 86-1 12 Your location:
Spain (34) 93-589-1579
United Kingdom (01707) 278-695
Please tick the box of your choice
What condition did the manual arrive in? Good Minor damage Unusable
What do you think to the manual presentation? Tidy Unfriendly
Are the explanations understandable? Yes Not too bad Unusable
Which explanation was most difficult to understand:
Are there any diagrams which are not clear? Yes No
If so,which:
What do you think to the manual layout? Good Not too bad Unhelpful
If there one thing you would like to see improved, what is it?
Could you find the information you required easily using the index and/or the contents, if possible please identify your experience:
Do you have any comments in general about the Mitsubishi manuals?
Thank you for taking the time to fill out this questionnaire. We hope you found both the product and this manual easy to use.



Guidelines for the Safety of the User and Protection of the F940GOT Handy Series (F94*GOT-*BD-RH-E)
This manual provides information for the use of the F940GOT Handy Series. The manual has been written to be used by trained and competent personnel. The definition of such a person or persons is as follows;
a) Any engineer who is responsible for the planning, design and construction of automatic
equipment using the product associated with this manual should be of a competent nature, trained and qualified to the local and national standards required to fulfill that role. These engineers should be fully aware of all aspects of safety with regards to automated equipment.
b) Any commissioning or service engineer must be of a competent nature, trained and
qualified to the local and national standards required to fulfill that job. These engineers should also be trained in the use and maintenance of the completed product. This includes being completely familiar with all associated documentation for the said product. All maintenance should be carried out in accordance with established safety practices.
c) All operators of the completed equipment (see Note) should be trained to use this
product in a safe manner in compliance to established safety practices. The operators should also be familiar with documentation which is associated with the operation of the completed equipment.
contains or uses the product associated with this manual.
At various times throughout this manual certain symbols will be used to highlight points of information which are intended to ensure the users personal safety and protect the integrity of equipment. Whenever any of the following symbols are encountered its associated note must be read and understood. Each of the symbols used will now be listed with a brief description of its meaning.

The table below shows abbreviations, generic names and terms used in this manual.
Abbreviation/ generic name/term Description
Handy GOT Generic name of F94GOT-SBD-RH-E and F94GOT-LBD-RH-E (=0 or 3)
F940 Handy GOT Generic name of F940GOT-SBD-RH-E and F940GOT-LBD-RH-E
F943 Handy GOT Generic name of F943GOT-SBD-RH-E and F943GOT-LBD-RH-E
QCPU (Q mode) Generic name of Q02CPU, Q02HCPU, Q06HCPU, Q12HCPU and Q25HCPU CPU units
QCPU (A mode) Generic name of Q02CPU-A, Q02HCPU-A and Q06HCPU-A CPU units
QCPU Generic name of QCPU (Q mode) and QCPU (A mode) CPU units
QnACPU (large type) Generic name of Q2ACPU, Q2ACPU-S1, Q3ACPU, Q4ACPU and Q4ARCPU CPU units
QnACPU (small type) Generic name of Q2ASCPU, Q2ASCPU-S1, Q2ASHCPU and Q2ASHCPU- S1 CPU units
QnACPU Generic name of QnACPU (large type) and QnACPU (small type) CPU units
ACPU (large type) Generic name of AnUCPU, AnACPU and AnNCPU CPU units
ACPU (small type) Generic name of A2US(H)CPU, AnS(H)CPU and A1SJ(H)CPU CPU units
ACPU Generic name of ACPU (large type), ACPU (small type) and A1FXCPU CPU units
FXCPU Generic name of FX0, FX0S, FX1S, FX0N, FX1N, FX1, FX2, FX2N, FX2C and FX2NC Series CPU units
Abbreviation of screen creation software for GOT-A900/GOT-F900 Series
GT Designer2 SWD5C-GTD2-E Screen creation software for GOT- 900 Series (English version)
Abbreviation of screen creation software for GOT-A900/GOT-F900 Series
GT Designer2 · GT Designer


Further information can be found in the following manuals.
{: Either manual is necessary.
Refer to the manual of the connected programmable controller for details concerning that unit.

F940GOT Handy Series Associated Manual Lists

The F940GOT Handy Series (hereafter called "Handy GOT") is an all-in-one type Handy GOT equipped with a touch key display unit (F94*GOT-*WD-E) and mechanical keys (operation switches) available for command input to the machine. The Handy GOT can connect to MELSEC FX, A, QnA and Q PLCs as well as a host of third party manufactured units.

Screens displayed for the Handy GOT can be created using the programming software, GT Designer 2.
Introduction 1

F940GOT Handy Series Introduction 1
!
The name of these operation switches can be personalized using a transparent sheet and a label sheet offered as accessories. (Refer to Chapter 4)

Table 1.1: Product Lists Production Name Description
F940GOT-SBD-RH-E Handy GOT main unit This type uses RS-422 communication for connecting to PLC. - SBD type is 8 Colors - LBD type is White and black F940GOT-LBD-RH-E
F943GOT-SBD-RH-E Handy GOT main unit This type uses RS-232C communication for connecting to PLC. - SBD type is 8 Colors - LBD type is White and black F943GOT-LBD-RH-E
1.2.1 Model Name The model name of the Handy GOT is read as follows.
Table 1.2: Notes on Model Name
A 0 RS-422 communication for connecting to PLC
3 RS-232C communication for connecting to PLC
S STN type 8 colors liquid crystal
L STN type black and white liquid crystal
Accessories:
- Sheets to change switch names A transparent sheet and a mount sheet are offered as accessories so that operation switch names can be changed. For the name changing procedure, see section 3.4.5.
- Ferrite filter for CE EMC For compliance to CE EMC regulations it is necessary to add a ferrite filter on the external cable for F940GOT-*BD- RH-E or F943GOT-*BD-RH-E. Further information can be found in the Notification of CE marking sheet in the product box and section 3.3.1 of this manual. This ferrite filter model name/number is TDK ZCAT2436- 1330A-M-BK.
Introduction 1 · Description ·

F940GOT Handy Series Introduction 1
1.3.1 External Cable
These external cables contain dedicated wires for communications, DC power supply, operation switches, grip switch, keylock switch and the emergency stop switch. One of the cables below is always necessary.
F9GT-RHCAB-3M 37-pin D-sub connector on one side, - 3M: Cable length is 3m (9' 10") - 6M: Cable length is 6m (19' 8") - 10M:Cable length is 10m (32' 9")
F9GT-RHCAB-10M
Note:
When using F9GT-RHCAB-*M external cable, one of the following relay cables is necessary.
Order the following options upon necessity.
This cable cannot be used for the F943GOT-*BD-RH-E (RS-232C communication type Handy GOT).
This cable cannot be used for the F943GOT-*BD-RH-E (RS-232C communication type Handy GOT).
·

This cable cannot be used for the F940GOT-*BD-RH-E (RS-422 communication type Handy GOT).
GT Designer2 SW1D5C-GTD2-E V1.00 or more (CD-ROM)
FX-PCS-DU/WIN-E SW0PC-FXDU/WIN-E Version V2.52 or more (3.5 FD)
GT Designer SW5D5C-GOTR-PACKE Version 5.05F or more (CD-ROM)
Introduction 1 ·

F940GOT Handy Series Introduction 1
1.4.1 Dimensions and Part Names of Front Panel
! " #
' ( ! # ! & ! & & #
$ % ! & #
a) Touch key LCD unit
This display unit offers the functions equivalent to those offered by the F940GOT series display unit. Further information on the standard F940GOT series can be found in the GOT-F900 Series Operation Manual. b) Emergency stop switch
Independent contact, 24V DC specification. c) Grip switch LED
LED for confirming ON/OFF status of the grip switch. The parameters for controlling the LED can be set in the screen creation software and PLC program. d) Operation switches
Direct connection to inputs on the PLC. The name of these operation switches can be personalized using a transparent sheet and a label sheet offered as accessories. Each of these switches is equipped with a green LED which indicates its status. The green LED lighting command is transferred between the PLC through serial communication. These LEDs can be controlled the by the user program in the PLC.
Lit while 24V DC power is supplied to the Handy GOT. f) Grip switch
A grip switch is provided on the side of the Handy GOT. The 3-position switch (OFF/ON/ OFF) turns ON when pressed halfway and turns OFF when pressed all the way or when released. g) Operation switch name sheet insertion slot
Can be seen when the operation switch cover is removed from the lower portion of the Handy GOT. h) Strap holders
Loops for the strap i) Keylock switch
2-position switch. A key can be inserted or removed to lock the switch position.

+
) *
a) Metal hook for mounting on a wall
Offered to mount the Handy GOT on a wall.
Adjustable length strap allowing comfortable holding of the Handy GOT.
c) Port for communications signals, the DC power supply, the operation switches and the
d) FX2NC-32BL Battery
Built in to back up data. For replacement instructions, refer to chapter 4.
e) Port for a personal computer (9-pin D-Sub, male) (for RS-232C communication)
Offered to transfer screen data created using the programming software or using the two-port interface function.
Offered to connect to a PLC, power supply and operation switches.

F940GOT Handy Series Introduction 1

F940GOT Handy Series Specifications 2
During a communication error (including cable break) while monitoring devices with the Handy GOT, communication between the Handy GOT and programmable controller CPU is interrupted and it is impossible to operate the switches or devices in the PLC through the Handy GOT. Communication and operation resumes when the Handy GOT system is correctly configured. DO NOT configure the emergency stop or safety features to operate through the Handy GOT, and be sure that there is no adverse consequences in the event of a Handy GOT - PLC communications malfunction.

F940GOT Handy Series Specifications 2
The figure below shows the external dimensions of the Handy GOT.
15(0.60")
69.5 (2.74") 27 (1.07")
88(3.47")
(1.48") 7.5(0.30")
78(3.08") 13 (0.52")
7 (0.28")
24 (0.95") 129(5.08")
160(6.30") 37.5
210.5(8.29")
210.5(8.29")
210.5(8.29")
191(7.52")
189(7.45")
129(5.08") 126(4.97")
18 (0.71")
Approx.120
(4.73")
20 (0.40") 38 (1.50")
156(6 .15") 10(0.40")
15 (0.60")
35.7 (1.41")
176(6.93")
38 (1.50")
12.7 (0.50")
10 (0.40")
7 (0.28")
13 (0.52")
27 (1.07")
41 (1.62")
64.5 (2.54")
64.5 (2.54") 156(6.15") 176(6.93")
70.7 (2.79")
41 (1.62") 51 (2.01") 58 (2.29")
70.7 (2.79")
35 (1.38")
29.7 (1.17")
7 (0.28")
Unit: mm (inches) Color: Munsell System 0.20G5.17/0.69 Mass: 0.87 kg (1.92 lbs) not including the cable

F940GOT Handy Series Specifications 2
Table 2.1: Power Supply Specifications Items Specifications
Power Supply Voltage 24V DC, +10% -15%
Power Supply Ripple 200 mV or less
Current Consumption Ratings: 300 mA at 24V DC (200 mA at 24V DC when backlight is turned OFF)
Fuse 1.0 A built-in fuse (impossible to change)
Max. Allowable Momentary Power Supply Failure period
5 ms; If less than 5 ms, the Handy GOT will continue operation. If 5 ms or more, the Handy GOT will shut down.
Battery Built-in, FX2NC-32BL type lithium battery. (Approximately 3 years life)
Table 2.2: General Specifications Item Specifications
Operating Temperature 0 ~ 40 °C (32 ~ 104 °F)
Storage Temperature -20 ~ 60 °C (-4 ~ 140 °F)
Humidity 35 ~ 85% Relative Humidity, No condensation
10 ~ 57 Hz: 0.075 mm Half Amplitude 57 ~ 150 Hz: 9.8 m/s2 Acceleration Sweep Count for X, Y, Z: 10 times (80 min. in each direction)
Vibration Resistance - intermittent vibration
10 ~ 57 Hz: 0.035 mm Half Amplitude 57 ~ 150 Hz: 4.9 m/s2 Acceleration Sweep Count for X, Y, Z: 10 times (80 min. in each direction)
Vibration Resistance - Continuous vibration
Shock Resistance 147m/s2 Acceleration, 3 times in each direction X, Y, and Z
Noise Immunity 1000 Vp-p, 1micro second, 30 ~ 100 Hz, tested by noise simulator
Dielectric Withstand Voltage 500 V AC > 1 min., tested between power terminals and ground
Insulation Resistance 5 MΩ > at 500 V DC, tested between power terminals and ground
Ground Grounding register 100 Ω or less (Class D)
Must be free of lamp black, corrosive gas, flammable gas, or excessive amount of electroconductive dust particles and must be no direct sunlight. (Same as for saving)
Operating atmosphere · Protection IP 54

F940GOT Handy Series Specifications 2
Table 2.3: Screen Hardware Specifications Items F94*GOT-SBD-RH-E F94*GOT-LBD-RH-E
Display Device STN color liquid crystal display
Resolution 320 × 240 (dot), 40 characters × 15 lines
Dot Pitch 0.36 mm (0.014") Horizontal × 0.36 mm (0.014") Vertical.
Effective Display Size 115 mm (4.53") × 86 mm (3.39"); 6 (5.7 inch) type
Number of Colors 8 colors White and Black
Life of liquid crystal Approximately 50,000 hours (Operating temperature: 25°C / 77°F)
Backlight Cold cathode tube
Life of Backlight 40,000 hours or more (Operating temperature: 25°C / 77°F)
Touch Keys Maximum 50 touch keys / screen, 20 × 12 matrix
Number of Screens User screen: 500 screens or less System screen: Allocated screens No. 1001-1030.
User Memory Flash memory 512 KB (built-in)
Table 2.4: Switch Specifications Item Description
Operation switch N/O contact × 4 points, 10mA/24V DC (Operation life time: Approximately 1,000,000 times)
Emergency stop switch 2 N/C contacts, 1A/24V DC (resistive load), independent wiring (Operation life time: Approximately 100,000 times)
Keylock switch 2-position, 1A/24V DC (resistive load), independent wiring (Operation life time: Approximately 100,000 times)
3-position (OFF/ON/OFF), 2 N/O contacts, independent wiring 1A/24V DC (resistive load) (Operation life time: Approximately 500,000 times)
Interface · With personal computer · Grip switch

F940GOT Handy Series Installation 3
This section describes the installation of the Handy GOT. All the specifications should be thoroughly understood before performing the installation. Further information about selecting and wiring the cables can be found in the GOT-F900 SERIES HARDWARE MANUAL (CONNECTION).
Rewire all phases of the power source, before installation or wiring work in order to avoid electric shock or damage to the product.
Note:
When holding the Handy GOT for operation, place your hand through the hand strap provided on its rear face. You can adjust the length of the hand strap.
,

F940GOT Handy Series Installation 3
When mounting the Handy GOT on a wall, use the metal hook provided on its rear face.
+ . * + + ( ! & ( # ( ( ! ' $ #
+ +
The wall fixture should be able to support the weight of the main unit (approximately 0.87 kg/ 1.91 lbs) and a load of approximately 1 ~ 3 kg (2.20 ~ 6.61 lbs) which varies depending on the communication cable length. Take this into consideration and attach a suitable metal fixture on the wall.
When using the Handy GOT on a flat surface, such as a desk or shelf, keep the Handy GOT parallel to the surface so that it does not drop. Also, fix the communication cable to the desk.
/ 0 0 + *

F940GOT Handy Series Installation 3
A hand/shoulder strap (prepared by the user) to help prevent accidental drops can be attached to the loops.
2 *
1
Dimensions of the loop
5 (0.2")
14 (0.55")

F940GOT Handy Series Installation 3
This section explains the connection configurations for the Handy GOT. Further information can be found in GOT-F900 SERIES HARDWARE MANUAL (CONNECTION).

The signal allocation within the connector of the external cable are shown below.


F940GOT Handy Series Installation 3
Description Pin No. Color of wire Arrangement
(RS232C)
1 Shield FG (shield) Frame ground
2 Yellow/Blue a) TXD+ (SDA) SD (TXD)
3 Yellow/Red a) TXD- (SDB) ER (DTR)
4 White/Blue a) RTS+ (RSA) RD (RXD)
5 White/Red a) RTS- (RSB) DR (DSR)
6 Gray/Blue a) RXD+ (RDA) RS (RTS)
7 Gray/Red a) RXD- (RDB) CS (CTS)
8 Orange/Blue a) CTS+ (CSA) NC
9 Orange/Red a) CTS- (CSB) NC
10 Orange/Red c) SG Signal ground
11 − − NC Not used
12 White/Red b) SW-COM COM for Operation switches
13 Gray/Blue b) SW1
Operation switches 14 Gray/Red b) SW2
15 Orange/Blue b) SW3
16 Orange/Red b) SW4
17 − − NC Not used
18 Gray/Blue d) DC24V G 24V DC power supply "-" 19 Gray/Red d)
20 Pink/Red d) ES1-1
Emergency stop switch 21 Pink/Blue d) ES1-1
22 Orange/Red e) ES1-2
23 Orange/Blue e) ES1-2
24 White/Red d) DSW-1
Grip switch 25 White/Blue d) DSW-1
26 Yellow/Red d) DSW-2
27 Yellow/Blue d) DSW-2
28 White/Blue b) KSW-C Common for keylock switch
29 Yellow/Red b) KSW-1 Keylock switch 30 Yellow/Blue b) KSW-2
31 Pink/Red b) Spare SW Spare 32 Pink/Blue b) Spare SW
33,34,35 − − NC Not used
36 Orange/Blue d) DC 24V+ 24V DC power supply "+" 37 Orange/Red d)
These are signals for communication with the PLC. When connecting to a port other than the programming port of the FX, A, QnA or Q series PLC, refer to the manual of the connected module. Also use a relay cable. For relay cable details, refer to section 1.3.2.
F940GOT Handy · F943GOT Handy · of color

F940GOT Handy Series Installation 3
This section explains the installation procedure for the optional external cable to the Handy GOT main unit.
a) Rear cover mounting screws, (M3 × 8mm, 4 screws) b) Packing c) Installation hole
(A)Port for power supply (CN1; 8-pin type)
(B)Port for communication and operation switches (CN2; 20-pin type)
(C)Connector for grip switch (CN4; 5-pin type)
(D)Connector for emergency stop switch (CN5; 4-pin type)
(E)Connector for keylock switch (CN6; 3-pin type)

F940GOT Handy Series Installation 3
* + * 7 .
.
Make sure to tighten the hexagon nut for cable mounting with a sufficient force to avoid loosening. As guideline, tighten it until the packing is crushed by 0.5 mm (0.02") or more.
, 0 * + *
, 0 * * +
& ' ! 8 ( ! $ " #
* + +
As guideline, make sure that the clearance is 3.5 mm (0.14") or less.
)

F940GOT Handy Series Installation 3
a) Before replacing the rear cover, make sure that the packing b) has not come off.
b) Attach the rear cover.
c) Tighten the four mounting screws.
Make sure the tightening torque is 0.49 to 0.68 N⋅m.
For compliance to CE EMC regulations it is necessary to add a ferrite filter on the external cable for F940GOT-*BD-RH-E or F943GOT-*BD-RH-E. The filter should be attached as shown with the filter surrounding the external cable. The recommended ferrite filter is the TDK ZCAT2436-1330A-M- BK or equivalent.
( " ! ' ' # + / +

F940GOT Handy Series Installation 3
3.4.1 Using the F940GOT Handy
/ $ " ( 9 , 5 + 0
a) External cable (with 37-pin D-Sub, male connector)
F9GT-RHCAB-3M 3m (9' 10")
F9GT-RHCAB-6M 6m (19' 10")
F9GT-RHCAB-10M 10m (32' 9")
b) Relay cable for connection to PLC
F9GT-RHCAB2-150
1.5m (4' 11") FX Series (FX0, FX0S, FX0N, FX1S, FX1N, FX2N, FX2NC)
F9GT-RHCAB3-150 FX (FX, FX2C), A, QnA Series
When connecting to a port or unit other than the programming port of an FX, A or QnA series PLC, make a cable corresponding to the configuration of the communications port in question. For allocation of Handy GOT communication signals, refer to section 3.2.
1 ·

F940GOT Handy Series Installation 3
Installing a connector on the panel of a control box or cabinet Connect a Q Series PLC using a relay cable as shown below.
/ $ " ' 9 , 5 + 0
a) External cable (with 37-pin D-Sub, male connector)
F9GT-RHCAB-3M (3m /9' 10")
b) Relay cable for connection to Q series PLC
F9GT-RHCAB5-150 (1.5m /4' 11") for Q series PLC
When connecting to a port or unit other than the programming port of a Q series PLC, make a cable corresponding to the configuration of the communications port in question. For allocation of Handy GOT communication signals, refer to section 3.2.
1 ·

F940GOT Handy Series Installation 3
Refer to the GOT-F900 Serise HARDWARE MANUAL [CONNECTION].
9 * + 2 ! 3 + + *
5 0 + +
9 / ; 1 5 8 < - ) 6 )
/ * * ( ( + 7 + 6
' % 6 < * 7 + + * 2
9 * + 2 ! 3 + + * 9 / ; & 6 < * 7 3 = 3 1
5 0 + +
/ * * ( ( + 7 + 6
' % 6 < * 7 + + * 2
9 * + 2 ! 3 + + *
5 0 + +
9 = 1 5 < - ) 6 )
/ * * ( ( + 7 + 6
' % 6 < * 7 + + * 2

F940GOT Handy Series Installation 3
When mounting the relay cable connector on the panel of a control box or cabinet, prepare the panel of the control box or cabinet as follows.
63.5 (2.5") 2-φ3.2±0.1 (0.13"±0.004")
59.1 (2.33") or more
11.4 (0.45") or more indicates the cut area.
Insert a jack socket into the hole shown above, and tighten it with M3 (0.12") nuts.
' ( ! & #
5 0 + +
> . .
" ! 8 ( ! $ #
+ + *
' ( ! & #
> . .
5 + ) * - '
Panel cut size · 10°

F940GOT Handy Series Preparation of the Operation Switch Name Sheet 4
This section explains how to prepare the operation switch name sheet.
? 2
6 A % ( ! % # B
( ! ' $ #
< ( ! ( "
& ( @ (
( ! % $ @ (
5 & ( ! ( 8 #
& & & 8
( ! " % # ( ! 8 % # ( ! 8 % # ( ! 8 % #
( ! % #
$ ' ! % 8 #
C B
( · < · [Recommended OHP sheet]

F940GOT Handy Series Preparation of the Operation Switch Name Sheet 4
Insert a screwdriver into the gap *1 or *3 between the operation switch cover and the main unit, then slowly push the operation switch cover up.
When either side *1 or *3 comes off, pull the operation switch cover in the sliding direction to remove it.
D
D
+
Insert the name sheet into the following position.
) +
1 + + 2
Align the operation switch cover with the protrusion *1 or *3 shown in the figure in the step 1), then attach the operation switch cover while flexing it slightly.

F940GOT Handy Series Maintenance and Diagnostics 5
Make sure to turn the power OFF before connecting/disconnecting cables. If you connect/disconnect cables while the power is turned ON, failure or malfunction may occur.
5.1.1 Replacement of the Battery
When the battery voltage drops, a control device (system information) assigned with the programming software turns ON. The control device interlocks with an auxiliary relay in the PLC. It is recommended to provide a lamp while utilizing the output of the PLC so that volt- age drop can be monitored outside the Handy GOT. For details of control devices, refer to the GOT-F900 SERIES OPERATION MANUAL.
System information write device is set to D20 D24 b3: Battery voltage drop (which turns on when the battery voltage drops) Use D24 in a PLC program as follows.
M0V D24 K2M20
M23 Battery voltage drop
Y Indication outside PLC
Top control device No. is set to M0 M6: Battery voltage drop (which turns ON when the battery voltage drops) Use M6 in a PLC program as follows.
M6 Battery voltage drop
Y Indication outside PLC

F940GOT Handy Series Maintenance and Diagnostics 5
The battery can back up the alarm history, sampling and the current time for approximately one month after the control device for the battery voltage drop turns ON. When the control device (system information) turns ON, replace the battery (FX2NC-32BL) as soon as possible. The screen data is stored in the flash memory. Even if the battery power is completely depleted, the screen data remains in the flash memory.
a) Turn off the power of the Handy GOT.
b) Open the small window of the rear panel.
c) Remove the existing battery from the holder and
disconnect it.
d) Within 30 seconds, connect a new battery.
/ & ) 5 < ' & 4
e) Insert the new battery into the holder and close the
small window.
5.2.1 Preliminary Check

F940GOT Handy Series Maintenance and Diagnostics 5
When an operation switch or emergency stop switch does not operate, check the following points.

SW1 SW-COM and SW1 12 and 13 White/Red and Gray/Blue (B)*3
SW2 SW-COM and SW2 12 and 14 White/Red and Gray/Red (B)*3
SW3 SW-COM and SW3 12 and 15 White/Red and Orange/Blue (B)*3
SW3 SW-COM and SW4 12 and 16 White/Red and Orange/Red (B)*3
ES1-1 ES1-1 and ES1-1 20 and 21 Pink/Red and Pink/Blue (D)*3
ES1-2 ES1-2 and ES1-2 22 and 23 Orange/Red and Orange/Blue (D)*3
KSW-1 KSW-COM and KSW-1 28 and 29 White/Blue and Yellow/Red (B)*3
KSW-2 KSW-COM and KSW-2 28 and 30 White/Blue and Yellow/Blue (B)*3
*1 Connect an external cable to the Handy GOT, press and hold each switch, then check the conduction between the pins or wires.
F9GT-HCAB-M 37-pin D-sub, male connector
*2 Connect an external cable and relay cable to the Handy GOT, press and hold each switch, then check the conduction between wires.
*3 Arrangement of color type.


F940GOT Handy Series Maintenance and Diagnostics 5
When the display is dark, adjust the brightness selecting "MODE SELECT MENU SCREEN" - "OTHER MODE" - "SET-UP MODE" - "LCD CONTRAST". If the screen remains dark even after adjustment, it is recommended to replace the backlight. For replacement of the backlight, consult with a Mitsubishi Electric distributor. For the details of the utility function, refer to the GOT-A900 SERIES OPERATING MANUAL (EXTENTION FUNCTIONS/OPTIONAL FUNCTIONS).
The table below shows the list of error messages displayed during manipulation or operation. Check the contents, and take proper action.
The PLC is running in EPROM mode. Or the write-protect switch of the EEPROM is set to ON.
Run the PLC in RAM mode. Or set the write-protect switch of the EEPROM to OFF.
CAN NOT WRITE PLC MEMORY.
A personal computer is attempting to write a program using "DATA TRANSFER” in "OTHER MODE" while the PLC is running. Or an entry code has been registered.
Stop the PLC. Or enter the correct entry code.
PLC IS RUNNING.
DATA IS NOT FOUND. There are no screen data or data files. Create the data using the programming software.
Screen No. 0 (FX-PCS-DU/WIN-E) or screen No. 1 (GT Designer) does not exist. When a screen is to be changed over, there is no destination screen.
Create screen No. 0 or 1. Or change the changeover destination screen, or create the corresponding screen.
DISPLAY SCREEN IS NOT AVAILABLE.



HEAD OFFICE: TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310 JAPAN HIMEJI WORKS: 840, CHIYODA CHO, HIMEJI, JAPAN
MODEL CODE 09R811
Effective Sep. 2008 Specifications are subject to change without notice.
What the fault codes shown on the display mean and how to clear them.
| Code | Meaning | Fix | |
|---|---|---|---|
| M6 | Battery voltage drop (which turns ON when the battery voltage drops) | p.39 |
Owners and our team usually reply within a day — and your question helps the next person too.