always consult a professional electrical engineer who is qualified and trained to the local
correct installation and operation of the communication facilities of FX series.
and national standards which apply to the installation site.
should be read and understood.
Foreword


This manual provides information for the installation and use of the Graphic Operation Terminal F940GOT.
The manual has been written to be used by trained and competent personnel. The definition of such a person
a ) Any engineer who is responsible for the planning, design and construction of automatic equipment
using the product associated with this manual should be of a competent nature, (trained and qualified
to the local and national standards required to fulfill that role). These engineers should be fully aware
b ) Any commissioning or service engineer must be of a competent nature, trained and qualified to the
local and national standards required to fulfill that job. These engineers should also be trained in the
use and maintenance of the completed product. This includes being completely familiar with all asso-
ciated documentation for the said product. All maintenance should be carried out in accordance with
c ) All operators of the compliance product should be trained to use that product in a safe and coordi-
nated manner in compliance to established safety practices. The operators should also be familiar
with all documentation which is connected with the actual operation of the completed equipment.
of safety with regards to automated equipment.
product associated with this manual.
established safety practices.
or persons is as follows;

At various times through out this manual certain symbols will be used to highlight points of information which
are intended to ensure the users personal safety and protect the integrity of the equipment. Whenever any of
the following symbols are encountered, its associated note must be read and understood. Each of the sym-
bols used will now be listed with a brief description of its meaning.
Hardware warnings · Software warnings

F940GOT-SWD-E/LWD-E


INTRODUCTION 1.
This section describes the product configuration and the system configuration of the graphic
Confirm various functions of each unit.
operation terminal.

F940GOT-SWD-E/LWD-E INTRODUCTION 1.
The graphic operation terminal (which may be hereafter
abbreviated as "GOT") is attached on the panel face of a
control panel or an operation panel, and connected to a
program connector in an FX or A Series programmable
controller (which may be hereafter abbreviated as "PLC")
Not only the CPU port connection method but also the
computer link port connection method is available so that
the GOT can be connected to a PLC other than MELSEC
You can monitor various devices and change the data of
There are several display screens built in the GOT which
offer various functions. In addition, you can create display
The built-in screens (system screens) and the screens
made by the user (user screens) have the following func-
the PLC while checking the screen of the GOT.
(except the A0J2) inside the control panel.
or a micro computer board.
tions respectively.
screens.

F940GOT-SWD-E/LWD-E INTRODUCTION 1.
The screens created by the user can be displayed. The following functions can be assigned
to each screen. And the screens to be displayed can be limited using the security function.
-Up to 500 screens created by the user can be displayed. The screens can be created
using the FX-PCS-DU/WIN-E V2.00 for the DU or using the SWoD5C-GOTRE-PACK
("o" indicates a numeric not less than 1.) for the GOT. Two or more screens can be
-Not only characters such as alphabets, numerics, Hiragana, Katakana and Kanji but
also simple graphics such as straight lines, circles and rectangles can be displayed. In
-Set values and current values of word devices in the PLC can be displayed in numerics
-The specified range of the screen can be displayed reversely in accordance with the
the F940GOT-SWD-E, screens can be displayed in 8 colors.
ON/OFF status of bit devices in the PLC.
or bar graphs for monitoring.
overlaid or changed over.
b) Monitor function · a) Display function

F940GOT-SWD-E/LWD-E INTRODUCTION 1.
-By manipulating the operation keys in the GOT, bit devices in the PLC can be set to ON
and OFF. The display panel face can be assigned as touch keys to offer the switch func-
If a touch key is pressed by a hard or sharp object, it may become failed.
-The numeric data being monitored can be changed.
Make sure to press a touch key by fingers.
c) Data change function
tion.
d) Switch function

F940GOT-SWD-E/LWD-E INTRODUCTION 1.
-The contents of buffer memories (BFMs) of special blocks can be read, written and
-The ON/OFF status of each device and the set value and the current value of each
Different from the monitor function in the screen display function described in the previ-
ous page, the screen can be displayed only inputting a desired device No. from the key-
- Programs can be read, written and monitored in the form of instruction list program.
timer, counter and data register in the PLC can be monitored and changed.
-Specified bit devices can be forcedly set to ON and OFF.
b) Buffer memory (only in the FX2N and FX2NC Series)
a) List program (only in the FX Series)
monitored.
board.
c) Device monitor

F940GOT-SWD-E/LWD-E INTRODUCTION 1.
The current value of specified data registers are acquired in a constant cycle or when the
When a bit device becomes ON, the assigned message is displayed (overlapped) on the
-When a bit device becomes ON, a corresponding message is displayed on the user
*As to 2], the alarm history can be output to a printer using the screen creation soft- ware.
Alarm messages can be assigned to up to 256 consecutive bit devices in the PLC.
In addition, a specified user screen can be displayed by setting a corresponding bit
-Up to 1,000 alarms (turning ON of bit devices) can be stored as the alarm history.
-The sampling data can be displayed in the form of list or graph.
-The sampling data can be output to a printer in the form of list.
-The number of alarms occurred in each device can be stored.
screen. The message list can be also displayed.
trigger condition is satisfied.
d) Data sampling function
device to ON.
user screen.
e) Alarm function

F940GOT-SWD-E/LWD-E INTRODUCTION 1.
-The GOT can function as an interface to enable data communication between the PLC
and a personal computer in which the relay ladder creation software is started up. At
-The real-time clock is built in, and the current time can be set and displayed.
-The screen contrast and the buzzer sound volume can be adjusted.
this time, the GOT screen can be displayed also.
Many other functions are built in.
f) Other functions

F940GOT-SWD-E/LWD-E INTRODUCTION 1.
Metal fixtures used to attach the GOT to a control panel
The GOT is equipped with accessories (1) to (3) below.
- Tightening bolt 6 pieces (M3 x 20)
Parts (4) to (8) are offered as options.
- Metal fixture 6 pieces

F940GOT-SWD-E/LWD-E INTRODUCTION 1.
Used to attach the GOT to a control panel
Packing to prevent dusts and water

F940GOT-SWD-E/LWD-E INTRODUCTION 1.
Each of them is an optional cable to connect the GOT and the
(in accordance with the Windows95 and the WindowsNT)
Connection cable FX-40DU-CAB-10M (10 m, 32.81 ft)
(3m, 9.84 ft, with L-shape connector on the GOT side)
("o" indicates a numeric not less than 1.)
(in accordance with the Windows95)
FX-PCS-DU/WIN-E V2.10 or later
FX/FX2C/A Series PLC.
Connection cable FX-50DU-CABL · SWoD5C-GOTRE-PACK

F940GOT-SWD-E/LWD-E INTRODUCTION 1.
This is not required when the GOT is connected to a gener-
Each of them is an optional cable to connect the GOT and
By using either one, the GOT can be directly connected to
alpurpose personal computer or connected to a peripheral
This is an optional interface to use the GOT and a periph-
eral unit to create sequence programs at the same time.
Connection cable FX-50DU-CAB0-10M (10 m, 32.81 ft)
Connection cable FX-50DU-CAB0-20M (20 m, 65.62 ft)
Connection cable FX-50DU-CAB0-30M (30 m, 98.43 ft)
(3 m, 9.84 ft, with L-shape connector on the GOT side)
Connection cable FX-50DU-CAB0-1M (1 m, 3.28 ft)
the FX0/FX0S/FX0N/FX2N/FX2NC Series PLC.
unit via a computer link unit.
the PLC.
Connection cable FX-50DU-CAB0L

F940GOT-SWD-E/LWD-E INTRODUCTION 1.
This is used to back up the alarm history data, the real-time
This is an optional EPROM memory (M27C4002-**F (4 MB)
manufactured by SGS-THOMSON) to save the user screen
The user screen data can be written using a general-pur-
pose ROM writer connected to the screen creation soft-
This is attached when the GOT is delivered.
clock, etc.
data.
ware.

F940GOT-SWD-E/LWD-E INTRODUCTION 1.
When a same screen is to be transferred to two or more
GOT units, transfer can be performed quickly and easily
using this adaptor compared with the screen creation soft-
This optional sheet protects the display screen against
This is a spare part of the display screen backlight.
The backlight is built in when the GOT is delivered.
Adhere it on the screen.
ware.
dirt.

F940GOT-SWD-E/LWD-E INTRODUCTION 1.

*1 Connection cables of different length are available. (Refer to the options in "1.2 Product configuration".)
When the GOT is directly connected to the PLC :When the GOT is connected via a computer link unit, refer to
Attach a ROM to the F9GT-40UMB, then connect it to a connector provided on the rear
computer is 9-pin type) or Data transfer cable FX-232CAB-2 (when the RS-232C
F940GOT-SWD-E/LWD-E Data transfer cable FX-232CAB-1 (when the RS-232C connector in the personal
It cannot be used when a computer link (RS-232C communication) is used.
The system configuration to use the GOT is described below.
Section 2.

A Series (except QnA)
Connection cable FX-40DU-CAB *1
1.3 System configuration
FX0/FX0S/FX0N/FX2N/
50DU-CAB0 for CPU port connection*1

F940GOT-SWD-E/LWD-E INTRODUCTION 1.
Screen creation software for A900GOT
Screen creation software for DU FX-
(" " is a numeric not less than 1.)
PCS-DU/WIN-E (V2.10 or later)
(Prints out sampling data, alarm history and alarm messages.)
Peripheral units for GOT
Printer equipped with RS-232C interface

< General-purpose printers >
< Dedicated printers >
using a general-purpose ROM writer.)
ESC/P
(when the RS-232C connector in the
Data transfer cable F2-232CAB-1
personal computer is 25-pin type)

F940GOT-SWD-E/LWD-E INTRODUCTION 1.

*1 Connection cables of different length are available. (Refer to the options in "1.2 Product configuration".)
The figure below shows connection to peripheral units used to create sequence programs.
When the two-port interface function is used, the operation environment should be set.
(when the RS-232C connector in the personal computer is half-pitch, 14-pin type)
(Refer to the description on "SERIAL PORT" on the SET-UP MODE screen.)
(when the RS-232C connector in the personal computer is 9-pin type)
Connected to RS-232C connector in GOT

A Series (except QnA)
Connection cable FX-40DU-CAB *1
When built-in two-port interface function is used
F940GOT-SWD-E/LWD-E
FX0/FX0S/FX0N/FX2N/
50DU-CAB0 for CPU port connection*1

F940GOT-SWD-E/LWD-E INTRODUCTION 1.
This two-port interface function is effective in CPU port connection (via the RS-422). This
function is not available in computer link connection (via the RS-422 or the RS-232C) and CPU
And even in CPU port connection (via the RS-422), this function is not available when two or
Peripheral unit to create
more GOT units are connected (Refer to Paragraph 2.7.).
When the two-port interface function is used using the software
* A general-purpose computer can be directly connected, and both the GOT and the personal computer can be used at
connection cable having the model name shown on the left to
package SW D5C(F)-GPPW-E, make sure to use the
the same time (without using the FX-2PIF).
port connection (via the RS-232C).
connect a personal computer.
sequence programs · personal computer · General-purpose

F940GOT-SWD-E/LWD-E INTRODUCTION 1.

A Series (except QnA)
When the two-port interface FX-2PIF is used
FX/FX2C/ Series FX0/FX0S/FX0N/FX2N/
FX-422CAB0
FX-2PIF

F940GOT-SWD-E/LWD-E INTRODUCTION 1.
The two-port interface FX-2PIF is available in CPU port connection (via the RS-422). This
interface is not available in computer link connection (via the RS-422 or the RS-232C) and
And even in CPU port connection (via the RS-422), this interface is not available when two or
The FX2N/FX2NC Series
range of the FX Series.
can be used in the
(A Series cannot be used.)
Peripheral unit to create
A6GPP/A6PHP
more GOT units are connected (Refer to Paragraph 2.7.).
CPU port connection (via the RS-232C).

F940GOT-SWD-E/LWD-E INTRODUCTION 1.

Installation, Wiring and General Specifications 2.
Never use the unit in a place with dusts, soot, conductive dusts, corrosive gas or flamma-
If the unit is used in an unfavorable place described above, electrical shock, fire, malfunc-
ble gas, place exposed to high temperature, condensation or wind and rain or a place
This section describes installation of the GOT and wiring of the power supply.
ation terminal when you drill screw holes or perform the wiring work.
tion, damages of the unit or deterioration of the unit may be caused.
connectors respectively while the power is turned off.
Imperfect connection may cause malfunction.
Fire, failure or malfunction may be caused.
subject to vibrations or impacts.
Caution on installation
F940GOT-SWD-E/LWD-E

F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.
The GOT is to be embedded in a panel. Perform the installation procedure described below.
+0.04 - 0.00
121 (4.76 ) +1 -0
153 (6.02 ) +1
+0.04
* Make sure that the plate thickness of the mounting panel is 5 mm (0.2 inches) or less.
Attach a packing to the GOT. Insert the GOT from the front
On the panel face, drill a mounting hole of the dimensions
shown on the right.
of the panel face.

F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.


Hang the hook of each metal fixture (offered as accessory)
* Make sure that the tightening torque for each tightening bolt is 0.3 to 0.5 N m.
When installing the GOT, make sure that the inside dimen-
to a mounting hook hole in the GOT. Tighten a mounting
However, to prevent dusts and water, fix the GOT in six
bolt (offered as accessory) securely in each position.
The GOT can be fixed in four positions at corners.
sions shown on the right are assured in the panel.
a) PLC connection cable
positions.
b) Tightening bolt · a) Metal fixture · b) Packing

F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.
When supplying the power from a programmable controller, connect a ground terminal in
ground terminal in the graphic operation terminal to a ground terminal in the connected
wiring.If the power supply is not shut down outside, electrical shock or damages of the
the graphic operation terminal to a ground terminal in the programmable controller and
perform Class 3 grounding. When supplying the power from the outside, connect a
If the AC power supply is connected to a DC power terminal or an I/O terminal, the
If the power supply is connected reversely, failures may be caused.
Never perform common grounding with strong electrical systems.
external power supply unit and perform Class 3 grounding.
DC power supply correctly as described in this manual.
graphic operation terminal may be burnt.
unit may be caused.
CAUTION

F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.
Connect the power terminal in the GOT to the 24V DC service power supply in the PLC
24V 0V S/S RUN X0 X1 X2 - +
The power is supplied to the GOT from a PLC or an external power supply unit.
basic unit or PLC extension unit.

F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.
Connect the power terminal provided on the rear face of the GOT to the 24V DC terminal in
24V 0V S/S RUN X0 X1 X2 - +
PLC GOT
the external power supply unit.

F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.
power interruption duration Operation shall be continued against instantaneous
Current consumption 390mA / 24V DC 410mA / 24V DC
power interruption for less than 5 ms.
Power ripple 200mV or less
Supply voltage 24V DC +10%
-15%

F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.
power to the GOT from the 24V DC service power in the FX Series PLC basic unit or exten-
sion unit, take into account the total current supplied to proximity switches and extension
blocks. If the total current exceeds the capacity of the service power, the GOT should
obtain the power from an external power supply unit. In the case of the FX0/FX0S/FX0N
When power interruption for 5 ms or more or the voltage drop occurs, the GOT stops its
operation. However, when the power is recovered, the GOT automatically restarts opera-
tion. (The screen displayed after recovery is determined by the operation environment set-
does not occur. Use crimp-style terminals of M3 size, and tighten them securely with the
torque of 0.5 to 0.8 N m so that troubles will not occur.
Series PLC, an external power supply unit is required.
the GOT continues its operation.
ting.)

F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.
130 (5.12)
162 (6.38)
×1 to ×4 in each of the vertical and horizontal directions.
characters (JIS Level 1) can be displayed in the size of
Alphabets, numerics and Katakana characters can be
Alphabets, numerics, Katakana characters and Kanji
Allows graphic display of 320 × 240 dots.
40 half-width characters × 15 lines
displayed also in the size of ×1/4.
mm (inches) · a) · a) Display unit

F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.
152 (5.98)
Backs up the sampling data, the alarm history and the
The screen data is stored in the built-in flush memory,
Supplies the power to the GOT, and allows grounding.
Connects the data transfer adopter F9GT-40UMB to
transfer the screen data stored in the EPROM.
Connects an optional extension equipment.
and does not require the battery.
current time.

F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.
a) Connector for personal computer (RS-232C connector):
b) Connects a personal computer to transfer to the PLC
the screen data created by the screen creation software
and sequence programs using the two-port interface
Used when a printer is connected or when a PLC is con-
nected via a computer link unit.
function.
a) · b) · D-sub 9-pin, male

F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.
-0.00 +0.04
120 (4.72)
-0 +0.04
57 (2.24)
5 (0.20)
130 (5.12)
162 (6.38)
152 (5.98)
-0 +1 · +1

F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.
10 times in each of X,
Noise resistance By noise simulator whose noise voltage is 1,000 Vp-p, noise width is 1µs and
Withstand voltage 500V AC for 1 minute Between all power terminals as a whole
Impact resistance In accordance with JIS B3501 and IEC 1131-2 (147 m/s2, three times in
Ambient temperature During operation: 0 to +50°C (0 to +40°C when extension interface is used)
mittent 10-57Hz - 0.075mm
tinuous 10-57Hz - 0.035mm
are applied 57-150Hz 9.8m/s2 -
are applied 57-150Hz 4.9m/s2 -
and ground terminal Insulation resistance 500V DC, 5MΩ or more by megger
Operating atmosphere Corrosive gas and much dusts shall not be detected.
each of X, Y and Z directions)
cycle is 30 to 100 Hz
Grounding Class 3 grounding
2.5 General specificationsl
Vibration resistance

F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.
Display element STN type full-dot matrix LCD, monochrome (F940GOT-LWD-E) or color
One channel in conformance to RS-422 for communication with PLC
One channel in conformance to RS-232C for transfer of screen data
Supply voltage 24V DC +10%, -15% Current consumption: 390 mA/24V DC (F940GOT-LWD-E)
410 mA/24V DC (F940GOT-SWD-E)
Extension interface for connection of optional extension unit
Screen LCD of 320 x 240 dots, 20 full-width characters × 15 lines,
Backlight Cold cathode tube (Service life: 25,000 times or more)
Key 50 touch keys maximum/screen, 20 × 12 matrix
Interface

F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.
Use the following cable to connect a personal computer.
c) FX-232CAB-1, FX-232CAB-2 or F2-232CAB-1

F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.
9 8 7 6
9 8 7 6
5 4 3 2 1
5 4 3 2 1
Pin assignment and connection diagram of transfer cables
2 3 6 8 5 4
2 3 6 8 5 4
- Transfer cable FX-232CAB-1
- Transfer cable FX-232CAB-2
9 8 7 6
5 4 3 2 1

F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.
9 8 7 6
5 4 3 2 1
2 3 8 4 5 6
1 2 3 5 6 7 20
- Transfer cable F2-232CAB-1
25 24 23 22 21 20 19 18 17 16 15 14
13 12 11 10 9 8 7 6 5 4 3 2 1

F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.
* When the screen mode is selected while a cable is not connected, a communication error occurs.

Y5 Y4 Y3 Y2 COM2 Y1 COM1 Y0 COM0 COM 24+
X7 X6 X5 X4 X3 X2 X1 X0 COM N L
Use either of the following cables to connect the PLC directly.

a) · d)

F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.
AnN, AnA, AnS, AnSJ, AnSH, A1SJH, A2C, A2CJ, A0J2H, AnU, AnUS, A2USH or A1FX
FX-50DU-CAB0-20M, FX-50DU-CAB0-30M or FX-50DU-CAB0L
c) FX-50DU-CAB0, FX-50DU-CAB0-1M, FX-50DU-CAB0-10M,
A171SCPU-S3, A171SHCPU, A172SHCPU or A272UHCPU
b) FX-40DU-CAB, FX-40DU-CAB-10M or FX-50DU-CABL
f) FX0/FX0S/FX0N/FX2N/FX2NC Series PLC
d) FX/FX2C Series PLC
e) A Series PLC
g) Motion controller · a) F940GOT

F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.
Pin assignment and connection diagram of connection cables (The connection cables are
9 8 7 6
9 8 7 6
- Connection cable FX-40DU-CAB (L, -10M) or FX-50DU-CABL
- Connection cable FX-50DU-CAB0 (L, -1M, -10M, -20M, -30M)
5 4 3 2 1
5 4 3 2 1
1 2 3 4 5 6 7 8 9
1 2 4 5 6 7 9
2 3 4 5 7 15 16 17 18 8 21
2 7 6 3 1 4 5
PLC
25 24 23 22 21 20 19 18 17 16 15 14
offered as options.)
13 12 11 10 9 8 7 6 5 4 3 2 1

F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.
As the connection type, select "CPU PORT (RS232C)" or "CPU PORT (RS422)" in "CON-
While the GOT display is used, peripheral units of the GOT and peripheral units used to cre-
ate sequence programs cannot be used except when the following system configuration is
realized using the FX2N -422-BD in the FX2N Series. Cables to connect such peripheral
15 m (49.2ft)
units should be disconnected while the GOT display is used.
1st unit 2nd unit 3rd unit 4th unit
30 m (98.4 ft)
connected to one PLC (1-to-N connection).
NECTION" on the PLC TYPE screen.
15 m (49.2 ft)
Side of GOT FX/A Series

F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.
1 2 3 4 5 6 7 8 9
When the speed in the case one GOT unit is connected is regarded as "1",
Speed in 1st unit x 2 = Speed in 2nd unit (1/2 of speed in 1st unit)
Speed in 2nd unit x 2 = Speed in 3rd unit (1/4 of speed in 1st unit)
Speed in 3rd unit x 2 = Speed in 4th unit (1/8 of speed in 1st unit)
1 2 3 4 5 6 7 8 9
number of connected GOT units becomes larger.
programming connectors in the FX2N unit.
Connection cable examples:
Connection diagram

F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.
In this case also, In the case of the FX2N Series, communication can be performed by CPU
In this case also, up to four GOT units can be connected to one PLC (1-to-N connection).
To connect peripheral units used to create sequence programs, use programming connec-
Up to four GOT units can be connected to one PLC (1-to-N connection).
port connection (RS-232C communication) using the FX2N-232-BD.
30m (98.4 ft)
(RS-232C communication) using the FX2N-232-BD.
15m (49.2 ft)
30m (98.4ft)
tors in the FX2N main unit.

F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.
When the speed in the case one GOT unit is connected is regarded as "1",
1 2 3 4 5 6 7 8 9
Speed in 1st unit x 2 = Speed in 2nd unit (1/2 of speed in 1st unit)
Speed in 2nd unit x 2 = Speed in 3rd unit (1/4 of speed in 1st unit)
Speed in 3rd unit x 2 = Speed in 4th unit (1/8 of speed in 1st unit)
1 2 3 4 5 6 7 8 9
number of connected GOT units becomes larger.
Connection cable examples:
Connection diagram

F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.
When two or more GOT units are connected to the FX/A/QnA Series PLC, communication is
performed in the location sequence from the GOT unit nearest to the CPU (that is, in the
sequence of the 1st, 2nd, 3rd and 4th GOT units). Accordingly, when turning on the power of
If the power cannot be turned on in the GOT units from the one nearest to the CPU, set the
GOT units (in "SET-UP MODE") or the screen creation software so that communication is per-
Setting example:The title screen display time is different by 2 seconds in each GOT unit, and
* Perform the same setting without regard to the connection type (RS-232C or RS-422) of two or more GOT units.
formed while the title screen display time is different by 2 to 3 seconds in each GOT unit.
the GOT units for the first time, turn on the power from the one nearest to the CPU.
communication is started from the GOT unit nearest to the CPU.
FX/A/QnA Title screen display time (initial value: 4 sec)

F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.
The GOT can be connected to the MELSEC A Series via a computer link unit as shown below.
For the communication setting for the computer link unit, refer to the F940GOT Oper-
RS232C
RS422
For the connection diagram, refer to the next page.
RS232C RS422
To computer link unit
ation Manual offered separately.
< A Series >
is not used.
Programming · connector

F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.
< For RS-232C communication > The connection cable F2-232CAB is also available.
9 8 7 6
5 4 3 2 1
9 8 7 6
1 2 3 7 8 6 5
5 4 3 2 1
1 6 2 7 5
1 2 3 4 5 6 7 8 20
DTR
FG
SD
RD
RS
CS
SG
CD
< For RS-422 communication >
RDB
SDA
SDB
SG
25 24 23 22 21 20 19 18 17 16 15 14
13 12 11 10 9 8 7 6 5 4 3 2 1

F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.
9 8 7 6
5 4 3 2 1
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
< For RS-232C communication >
DSR
CD
RD
SD
SG
RS
CS
9 8 7 6
5 4 3 2 1

F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.
The GOT can be connected to the SYSMAC C Series manufactured by OMRON via a host link
For the setting of the host link unit, refer to the F940GOT Operation Manual offered
A host link unit or a CPU equipped with an interface for host link is required.
RS422
2.9 Connection to SYSMAC C Series
To host link unit
< SYSMAC C Series >
unit as shown below.
separately.

F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.
For connection of a model not shown in the examples below, refer to the manual of the C
< For RS-232C communication > Example of connection to C200H-LK201-V1
< For RS-422 communication > Example of connection to C200H-LK202-V1
9 8 7 6
9 8 7 6
5 4 3 2 1
5 4 3 2 1
GOT
1 6 2 7 5
1 2 3 7 8 5
1 6 5 9 3
1 2 3 4 5 7
RDA
SDB
SDA
RD
SG
SG
FG
SD
RS
CS
25 24 23 22 21 20 19 18 17 16 15 14
9 8 7 6
Series link unit.
13 12 11 10 9 8 7 6 5 4 3 2 1
5 4 3 2 1

F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.
9 8 7 6
Example of connection to CQM1 (in which RS-232C port is built in)
5 4 3 2 1
1 2 3 7 8 5
1 2 3 4 5 9
SD
RD
RS
CS
SG
< For RS-232C communication >
9 8 7 6
5 4 3 2 1

F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.
The GOT can be connected to the FLEX-PC N Series manufactured by FUJI Electric via a link
the operation environment setting
Select the connection type using
described in the next section or
the screen creation software.
A link unit (general-purpose RS-232C/RS485 interface module) is required to be con-
nected. Or a CPU in which an RS-232C interface is built in is required.
Link port connection (RS-232C)
CPU port connection (RS-232C)
Link port connection (RS-422)
RS422
To link unit or built-in RS-232C interface
2.10 Connection to FLEX-PC N Series
< FLEX-PC N Series >
unit shown below.

F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.
9 8 7 6
- CPU in which RS-232C interface is built in NJ-CPU-B16
Connect the GOT and the link unit (PLC) as shown below.
5 4 3 2 1
side Link unit side
1 6 2 7 5
< For link port connection (RS-422) >
RDA
RDB
SDA
SDB
SG
NJ-RS2, NJ-RS4

F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.
9 8 7 6
9 8 7 6
5 4 3 2 1
5 4 3 2 1
side Link unit side
1 2 3 7 8 6 5 4
2 3 7 8 5
< For connection of built-in RS-232C interface >
< For link port connection (RS-232C) >
1 2 3 4 5 6 7 20
2 3 4 5 7
DTR
FG
SD
RD
RS
CS
SG
RD
SD
RS
CS
SG
25 24 23 22 21 20 19 18 17 16 15 14
15 14 13 12 11 10 9
13 12 11 10 9 8 7 6 5 4 3 2 1
8 7 6 5 4 3 2 1

F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.
In genera-purpose communication, the host unit is connected to the GOT via the RS-232C
and functions as the parent station in communication. Inside the GOT, there is a data area
using the screen creation software in the personal computer. The screen data specifies the
layout of objects displayed on the screen, and specifies actions to be performed by pressing
The GOT is equipped with the function to display the word data in the form of numbers and
The contents of display and control in the GOT are determined by the screen data created
The target of access is the data area inside the GOT. The data location to be accessed is
to hold word data and bit data. The host unit can read and write the data area using com-
bar graphs, the function to access the data for changing the status of the bit data using
The GOT can be connected to a general controller such as micro computer board.
(The connected controller is hereafter referred to as "host (unit)".)
specified by the screen data.
munication commands.
switches, etc.
of touch keys.

F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.
transfer the data to the data area inside the GOT using write commands. The transfer des-
tination is a location specified by the screen data. The data change result by manipulation
of keys can be transferred from the data area inside the GOT to the host unit if the host unit
gives read commands. In general-purpose communication, interrupt codes can be sent as
Accordingly, to display the data stored in the host unit on the screen, the host unit should
(micro computer board, etc.)
GOT
change triggers.
Host unit · Display/Input Internal data · Screen data

F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.
* The control lines RTS, CTS, DTR and DSR are not used.
Connect the GOT and the host unit as shown below.
9 8 7 6
5 4 3 2 1
1 2 3 7 8 6 4 5
SD
RD
SG

F940GOT-SWD-E/LWD-E Installation, Wiring and General Specifications 2.
The setting related to communication can be performed using the screen creation software
- GOT main body: Select "SET-UP MODE" and "SERIAL PORT (RS-232C)" in this order.
To set the baud rate, the data length, the stop bit length and the parity,
Baud rate 19,200 / 9,600 / 4,800 / 2,400 / 1,200 / 600 or 300 bps
Set each parameter to an either value shown below.
To use general-purpose communication,
COMMUNICATION" in this order.
Parity Even, odd or none
Data length 8 or 7 bits
Stop bit length 1 or 2 bits
or the GOT main body.
Communication".
tings"

Startup 3.
This section describes the startup procedure from turning on of the power of the GOT to selec-
This section describes also the environment setting important to use of the GOT. Make sure to
read this section carefully.
tion of the mode.
3. Startup

F940GOT-SWD-E/LWD-E Startup 3.
This paragraph describes the startup procedure from turning on of the power of the GOT to
of the screen of the GOT is pressed and held for 1 second or
The operation environment can be set on the OTHER
more, the SET-UP MODE screen is displayed.
on the SET-UP MODE screen.
MODE screen.
The OPENING SCREEN is displayed.
The SET-UP MODE screen
touch key.
power supply unit of the GOT.
is displayed.
selection of the mode.
Perform wiring of the
Connect the PLC.
touch key.

F940GOT-SWD-E/LWD-E Startup 3.
* This SELECT MODE screen can be called also by press- ing a corner of the screen set in "MAIN MENU CALL
pressed, the corresponding mode is selected.
KEY" on the SET-UP MODE screen.
selected.
A user screen is displayed.
When there is no screen data
The screen mode is
screen is displayed.
screen is displayed.
selected.
The SELECT MODE · The selected mode

F940GOT-SWD-E/LWD-E Startup 3.
USER SCREEN MODE
[ SELECT MODE screen ]
ALARM MODE
OTHER MODE
TEST MODE
HPP MODE

F940GOT-SWD-E/LWD-E Startup 3.
The operation environment setting function performs initial setting important to operation of the
GOT. The SET-UP MODE screen can be displayed by turning on the power while pressing and
holding the upper left corner of the screen in accordance with "3.1 Startup procedure" or by
If an entry code has been registered using the security function (described in the F940GOT
Operation Manual offered separately), however, the operation environment can be set only
when an entry code input by the user is equivalent to the registered entry code.
MAIN MENU CALL KEY
[ SET-UP MODE screen ]
CLEAR USER DATA
SET BACKLIGHT
LCD CONTRAST
SERIAL PORT
LANGUAGE
SET CLOCK
selecting "SET-UP MODE" on the OTHER MODE screen.
BUZZER
3.2 Operation environment setting
holding the upper left corner of the screen.
Set the system language (Refer to p. 44.).
The SET-UP MODE screen is displayed.
Turn on the power while pressing and
Press the END key.

F940GOT-SWD-E/LWD-E Startup 3.
Allows to set the language displayed on the system screens such as Japanese and
To be selected when a printer is connected to the GOT or when communication is per-
Allows to set the duration in which the OPENING SCREEN screen is displayed immedi-
Allows to set the position of the touch key which calls the SELECT MODE screen from
Allows to set the time at which the backlight becomes extinguished.
Allows to set the time used in the time switch and the time display.
The areas enclosed with broken lines function as touch keys.
formed between the GOT and a micro computer board.
the screen mode (in which a user screen is displayed).
(Broken lines are not actually displayed on the screen.)
Allows to set the connected PLC type.
ately after the power is turned on.
e) MAIN MENU CALL KEY
English.

F940GOT-SWD-E/LWD-E Startup 3.
Allows to set the buzzer sound issued when a key is pressed.
Change over the menu item on the SET-UP MODE screen.
Allows to set the LCD brightness.
Exits the SET-UP MODE screen.
Deletes the user screen data.
j) CLEAR USER DATA

F940GOT-SWD-E/LWD-E Startup 3.
Each setting screen is displayed as shown below. On each screen, when the END key at the
upper right corner is pressed after setting is completed, the SET-UP MODE screen is dis-
Allows to set the language displayed on the system
Allows to set the language displayed on the user
screens. JAPANESE, CHINESE and KOREAN are
available. Only one language can be selected at a
(CHINESE and KOREAN will be available in a few
JAPANESE and ENGLISH are available.
screens and in error messages.
time.
days.)
SYSTEM LANGUAGE:
[ PLC TYPE screen ]
played.

F940GOT-SWD-E/LWD-E Startup 3.
Allows to select either one among FX SERIES, A
SERIES, C SERIES (manufactured by OMRON), N
SERIES (manufactured by FUJI Electric) and UNI-
Allows to set the connection method of the PLC
cation in accordance with the RS-422 via a link unit.
The A Series, the C Series and the N Series are
nication with the DU in accordance with the RS-
232C via a link unit. The A Series, the C Series and the N Series are
The FX Series and the A Series are available.
VERSAL (general-purpose communication).
program connector in the PLC.
selected in 1] above.
available.
available.
enclosed with solid lines func-
tion as touch keys. Every time
a touch key is pressed, the dis-
played contents are changed
FX SERIES
CPU PORT
[ PLC TYPE screen ]
CONNECTION:
STATION #:
over.

F940GOT-SWD-E/LWD-E Startup 3.
Allows to set the station No. of the link unit connected
to the GOT when "LINK PORT" is selected in 2] above.
c) STATION #

F940GOT-SWD-E/LWD-E Startup 3.
Every time a touch key is pressed, the displayed con-
function is not available.
tents are changed over.
XON/XOFF
NOT USED
:
:
:
:
:
:
[ SERIAL PORT]
PRINTAER
DATA BIT
STOP BIT
SPEED
PARITY
![Page 78 of the Mitsubishi Electronics Touch Screen Operator Interface (F940GOT-SWD-E) user manual — [ OPENNING SCREEN ]](/cdn/reader/b0/b0d197df84bca3645559b930de72af4ebfd3268688415c11496584d8f27c50ab/images/page-78.webp?w=400)
F940GOT-SWD-E/LWD-E Startup 3.
name, the version, etc. is displayed when the power is
* When "DISPLAY TIME" is set to "0", the OPENING SCREEN screen indicating only the version is dis-
It is recommended to set 1 second or more for the
FX Series and 4 seconds or more for the A Series.
key to register the input time.
played for 4 seconds.
bottom of the screen.
turned on.
5 6 7 8 9 CLR
0 1 2 3 4 ENT
DISPRAY TIME 20 SEC.

F940GOT-SWD-E/LWD-E Startup 3.
which the menu call key has been assigned, the menu
mode is available. Any other mode is not available.
The menu call key is mesh type, and 2 x 2 in size.
four corners of the screen.
SELECT MODE screen.
call function is disabled.
[ MENU CALL KEY screen ] END
[ MENU CALL ]
![Page 80 of the Mitsubishi Electronics Touch Screen Operator Interface (F940GOT-SWD-E) user manual — [ SET CLOCK ] END](/cdn/reader/b0/b0d197df84bca3645559b930de72af4ebfd3268688415c11496584d8f27c50ab/images/page-80.webp?w=400)
F940GOT-SWD-E/LWD-E Startup 3.
of the screen. Enter the desired date or time, and
press the ENT key to register it.
mode and the alarm mode.
5 6 7 8 9 CLR
0 1 2 3 4 ENT
DATE 1 / 3 / 1999
TIME 10: 10: 10
[ SET CLOCK ]
![Page 81 of the Mitsubishi Electronics Touch Screen Operator Interface (F940GOT-SWD-E) user manual — [ SET BACKLIGHT ]](/cdn/reader/b0/b0d197df84bca3645559b930de72af4ebfd3268688415c11496584d8f27c50ab/images/page-81.webp?w=400)
F940GOT-SWD-E/LWD-E Startup 3.
pressed or the user screen is not changed over within
the specified OFF time, the backlight becomes extin-
pad displayed at the bottom of the screen. Enter the
desired time, and press the ENT key to register it.
F940GOT Operation Manual.)
guished.
5 6 7 8 9 CLR
0 1 2 3 4 ENT
OFF TIME 10 MIN.
![Page 82 of the Mitsubishi Electronics Touch Screen Operator Interface (F940GOT-SWD-E) user manual — [ BUZZER ] END](/cdn/reader/b0/b0d197df84bca3645559b930de72af4ebfd3268688415c11496584d8f27c50ab/images/page-82.webp?w=400)
F940GOT-SWD-E/LWD-E Startup 3.
When the key is pressed, the LCD becomes
brighter.
[ LCD CONTRAST ] END
BUZZER OFF
BUZZER ON
[ LCD CONTRAST ]
[ BUZZER ]
![Page 83 of the Mitsubishi Electronics Touch Screen Operator Interface (F940GOT-SWD-E) user manual — [ CLEAR USER DATA] END](/cdn/reader/b0/b0d197df84bca3645559b930de72af4ebfd3268688415c11496584d8f27c50ab/images/page-83.webp?w=400)
F940GOT-SWD-E/LWD-E Startup 3.
When the message "COMPLETED!" is displayed, the
data is cleared completely. YES
OK TO CLEAR USER DATA?
[ CLEAR USER DATA]
NO

F940GOT-SWD-E/LWD-E Startup 3.

Extension Module 4.
This section describes handling of the extension module interface provided on the rear face of
The data transfer adaptor F9GT-40UMB is used to store the user screen data stored in the
EPROM for user screen data FX-EPROM-4M to the flush memory in the GOT. (The user
This adaptor is useful when a same screen is transferred to two or more GOT units.
screen data can be written to the EPROM using the screen creation software.)
F940GOT-SWD-E/LWD-E
the GOT.

F940GOT-SWD-E/LWD-E Extension Module 4.
1)Attach the FX-EPROM-4M a) in which user screens are saved to the F9GT-40UMB b).
Pay rigid attention not to bend leads of the FX-EPROM-4M a) nor
2)Put upward the user screen/system screen selector switch c). If this switch is put downward by mistake and data is transferred,
In this case, put the selector switch c) upward and transfer the
3)Attach the F9GT-40UMB to the extension module interface d). Make sure that the power of the GOT has been turned off pre-
4)Turn on the power of the GOT. Then, the screen data will be auto- matically transferred to the GOT in 2 to 3 minutes.
user screens will not be displayed normally.
c)User screen/system screen selector switch
touch them with bare fingers.
data again.
liminarily.

F940GOT-SWD-E/LWD-E Extension Module 4.
5)When transfer is finished, make sure to turn off the power of the GOT and remove the adaptor b).

F940GOT-SWD-E/LWD-E Extension Module 4.

Maintenance 5.
If the backlight is replaced while the graphic operation terminal is attached on the panel,
If the battery for memory backup is handled in such a way, it may be burst or take fire.
This section describes maintenance such as replacement of the battery and the backlight.
If the backlight is replaced while the power is supplied, you may get electrical shock.
into fire nor short-circuit the battery for memory backup.
minal main body from the panel.
it may drop and injure you.
5. Maintenance
F940GOT-SWD-E/LWD-E

F940GOT-SWD-E/LWD-E Maintenance 5.
However, the service life is 5 years in the battery, approximately 50,000 hours in the LCD
It is recommended to replace these parts periodically using the procedure described
If a connection cable is connected/disconnected while the power is supplied, failure or
If an extension module is attached/removed while the power is supplied, the contents
If the unit is disassembled or modified, failure, malfunction or fire may be caused.
In addition, inspect other equipment and pay rigid attention to the following points.
Consumable parts which may shorten the service life are not built in the GOT.
stored in the memory or the EPROM memory itself may be damaged.
* For repair, contact MITSUBISHI ELECTRIC SYSTEM SERVICE.
and 25,000 hours or more in the backlight.
malfunction may be caused.
below.

F940GOT-SWD-E/LWD-E Maintenance 5.
When the battery voltage drops, the control devices for system information set by the screen cre-
ation software becomes ON. The control devices are interlocking with auxiliary relays in the PLC.
It is recommended to attach a lamp using the output of the PLC so that the ON/OFF status of the
D24 b3: Battery voltage drop Becomes ON when the battery voltage drops.
M6: Battery voltage drop Becomes ON when the battery voltage drops.
When the system information of the write device is set D20.
When the head No. of the control devices is set to M0.
This control device is used in a sequence program as follows.
This control device is used in a sequence program as follows.
7th bit can be monitored from the outside. For the details of control devices, refer to the Operation Manual.
Example :When the SW1D5C-GOTR-PACK are used.
Example :When the FX-PCS-DU/WIN are used.
Y Indication outside PLC
Y Indication outside PLC
5.2 Replacement of battery
M8000
M23
M6
Battery voltage drop · Battery voltage drop

F940GOT-SWD-E/LWD-E Maintenance 5.
trol device for battery voltage drop becomes ON. After 1 month, these data cannot be held.
* The battery backs up the alarm history, the sampling data and the current time. Because the screen data is stored in the flush memory, it is held even if the battery becomes dis-
The alarm history and the sampling data are held for approximately 1 month after the con-
It is recommended to replace the battery soon.
a) a) Battery PM-20BL
abled.

F940GOT-SWD-E/LWD-E Maintenance 5.
force, the cable connecting the rear panel and
the front panel may be disconnected or the PCB
It is recommended to insert a screwdriver into the
holder. Then, the backlight can be taken out easily.
ners, and slowly remove the rear panel.
may be damaged. Be careful.
Replace the backlight F9GT-40LTS using the following procedure.

F940GOT-SWD-E/LWD-E Maintenance 5.

Troubleshooting 6.
The POWER LED in the GOT is lit by the 5 V power supply inside the GOT. When the POWER
LED is extinguished, nothing is displayed on the screen or no key is accepted, the power sup-
Especially when the power is supplied from the FX Series PLC, the following points are sus-
Disconnect all equipment except the GOT from the +24 terminal in the FX Series PLC, and
When the display screen is dark, adjust "LCD CONTRAST" on the SET-UP MODE screen.
When the screen is still dark, it is recommended to replace the backlight (F9GT-40LTS).
When an abnormality has occurred, check the following points.
This section describes troubleshooting during operation.
check whether the GOT operates normally.
ply may be insufficient.
F940GOT-SWD-E/LWD-E
pected.

F940GOT-SWD-E/LWD-E Troubleshooting 6.
The table below shows the list of error messages displayed during manipulation and operation
Or set to OFF the protect switch of the
FOUND. There are no screen data nor data files. Create the data using the screen creation
Change the screen changeover destina-
tion or create the specified screen.
Set the PLC to the RAM mode.
Create the screen No. 0 or 1.
Stop the PLC.
EEPROM.
software.
Confirm the contents of an error, and take appropriate actions.
Or the protect switch of the EEPROM is
A program is tried to be written from the
personal computer using "DATA TRANS-
FER" on the OTHER MODE screen while
The screen No. 0 or 1 has not been cre-
There is not a screen (the screen No. 0 in
the FX-PCS-DU/WIN-E or the screen No.
1 in the SW1D5C-GOTR-PACK) specified as the screen changeover destination by
The PLC is running in the EPROM mode.
Or an entry code has been registered.
the screen creation software.
the PLC is running.
set to ON.
ated.
SCREEN IS NOT
DATA IS NOT
AVAILABLE.
MEMORY.
RUNNING.
of the GOT.

F940GOT-SWD-E/LWD-E Troubleshooting 6.
Remove the cause of flashing of the LED,
then manipulate the personal computer
set range. Refer to the manual, and input a value
Refer to the manual, and specify a device
Manipulate the personal computer again.
Or replace the cable with a new one.
The power supply of the PLC is set to OFF. Set to ON the power of the PLC.
defective. Connect the cable correctly.
within the set range.
within the set range.
again.
The cable is imperfectly connected or
The power of the PLC was set to OFF
The CPUÅEE LED on the PLC started to
flash while communication was performed.
INCORRECT. The input value is outside the allowable
The input device is outside the allowable
though a bit device had to be specified.
while communication was performed.
set range.
DEVICE ERROR.
COMMUNICA-
OCCURS.*1

F940GOT-SWD-E/LWD-E Troubleshooting 6.
* When it is difficult to search the changed data, it is recommended to write the data again to the GOT from the screen data backup file created using the screen creation software.
*1 When the cause of the communication error is removed, the error message automatically disappears (and the GOT automatically recovers to the normal status.).
Unlock or delete the entry code in "ENTRY
The created screen data is destroyed. Clear all data by pressing the ACK key.
CODE" on the OTHER MODE
screen.
THE FUNCTION. An entry code has been registered in the
PLC.

Additional Functions (in Ver3.00 or later) 7.
* The additional functions 1) to 4) above are effective from the following software version. SW2D5C-GOTR-PACK-E Ver. A manufactured in July, 1999 or later.
(whose manufacturer’s serial No. is "97***" or later)
Unit manufactured in July, 1999 or later
Ver. 3.00 or later
to ON/OFF a bit device in the PC.
F940GOT-SWD-E,
F940GOT-LWD-E
F940GOT-SWD-E/LWD-E
available.

F940GOT-SWD-E/LWD-E Additional Functions (in Ver3.00 or later) 7.
* Connection is same as that of the A Series except computer link connection via the RS- 422 interface whose connector is D-sub, 25-pin type. Refer to connection diagrams of the A Series.
the F940GOT during CPU communication, only the personal computer software
When the RS-422 interface for computer link connection is D-sub, 25-pin connector
9 8 7 6
Computer link correction (RS-422, RS-232C)
5 4 3 2 1
SWoD5C(F)-GPPW is available for communication.
QnA, Q2AS CPU direct connection (RS-422)
7.2 Connection to MELSEC QnA Series PC
ˆ
25 24 23 22 21 20 19 18 17 16 15 14
13 12 11 10 9 8 7 6 5 4 3 2 1

F940GOT-SWD-E/LWD-E Additional Functions (in Ver3.00 or later) 7.
The SLC 500 Series PC manufactured by Allen-Bradley can be connected using a program-
For the communication setting, refer to the F940GOT Operation Manual.
SLC5/03, SLC5/04 CPU direct connection (RS-232C)
ming connector in the PC.

F940GOT-SWD-E/LWD-E Additional Functions (in Ver3.00 or later) 7.
For the cable length and the detailed specifications of the SLC Series, refer to the manual of
9 8 7 6
5 4 3 2 1
RD(RXD)
SD(TXD)
DSR
RTS
CTS
CD
SG
ˆ
ˆ
RD(RXD)
SD(TXD)
DTR
DSR
RTS
CTS
CD
SG
NC
SLC
CPU
9 8 7 6
the SLC Series.
5 4 3 2 1

F940GOT-SWD-E/LWD-E Additional Functions (in Ver3.00 or later) 7.
The F940-GOT can be connected to any bar code reader whose communication specifica-
For the communication setting and sequence programs, refer to the F940GOT Operation
The F940-GOT can be connected to a bar code reader.
tions and data format are as shown below.
Data (8 bits) CR (0DH)
Communication baud rate 9600bps
Data length 8 bit
Stop bit length 1 bit
Manual offered separately.
Communication port RS232C · Parity Even

F940GOT-SWD-E/LWD-E Additional Functions (in Ver3.00 or later) 7.
* Because the RS-232C connector is used to connect a bar code reader, the printout func- tion and the two-port interface function are not available while a bar code reader is con-
When the F940GOT is connected to a PC unit via RS-232C, any bar code reader cannot
1:None 2:RD(RXD) 3:SD(TXD) 4:DTR 5:SG
be connected.
9 8 7 6
nected.
5 4 3 2 1

F940GOT-SWD-E/LWD-E Additional Functions (in Ver3.00 or later) 7.
the screen hard copy function is not
play unit, its dust-proof ability and water-
* Verified printer model name LBP450 (A4 laser printer) manufactured by CANON
proof ability are not effective.
* Cautions on connection
available.
The screen being displayed can be output to a printer.
Printer with ESC/P J84, RS-232C interface
System screens cannot be printed out.
User screens (in the screen mode)
- Communication baud rate:
- Flow control:

F940GOT-SWD-E/LWD-E Additional Functions (in Ver3.00 or later) 7.
Now, the initial display position can be specified for each screen using the screen creation
selected alarms or the entire alarm history
screen. While alarm devices are set to ON,
is not deleted. FFB7 (H) Deletes the entire alarm history.
7.7 Specification of Ten-Key Window Initial Display Position
codes was fixed at the lower right corner conventionally.
FFB6 (H) Deletes displayed alarms selected on the
history in the alarm mode.
software.

Additional Functions (in V3.10 or later) 8.
F940GOT-LWD-E (Whose manufacturer’s SERIAL No.9X**** or later)
SW3D5C-GOTRE-PACK Version.A December, 1999 or later
at a constant cycle, and constants can be written.

F940GOT-SWD-E/LWD-E Additional Functions (in V3.10 or later) 8.

Additional Functions (in V4.00 or later) 9.
- Italian, English, Dutch language, Swedish, Spanish, Danish language, German,
“SET UP MODE” → “LANGUAGE” → “CHARACTER SET” → “WEST EUROPE”
F940GOT-LWD-E (Whose manufacturer’s SERIAL No.01**** or later)
SW4D5C-GOTRE-PACK Version.A January, 2000 or later
Correspondence of character font
Portuguese, and French

F940GOT-SWD-E/LWD-E Additional Functions (in V4.00 or later) 9.

Under no circumstances will MITSUBISHI ELECTRIC be liable responsible for any consequential damage that may
All examples and diagrams shown in this manual are intended only as an aid to understanding the text, not to guar-
antee operation. MITSUBISHI ELECTRIC will accept no responsibility for actual use of the product based on these
Owing to the very great variety in possible application of this equipment, you must satisfy yourself as to its suitability
arise as a result of the installation or use of this equipment.
for your specific application.
illustrative examples.

to change without notice.
Effective FEB. 2000
HARDWARE MANUAL
F940GOT-SWD-E/LWD-E
JY992D77901D
(MEE0002)
Specification are subject