EN
Mitsubishi Electronics logo
Official user manual

Mitsubishi Electronics 8

60 pages·1.2 MB·Air Conditioner·PDF·ENDEFRITNLJA
Mitsubishi Electronics 8
Table of Contents 80 sections AIR-COOLED ROOFTOP PACKAGED AIR CONDITIONERS · Series · COOLING ONLY :PR-5,8,10,15,20 · HEAT PUMP :PRH-5,8,10,15,20 · … ShowHide
AIR-COOLED ROOFTOP PACKAGED AIR CONDITIONERSp.1Seriesp.1COOLING ONLY :PR-5,8,10,15,20p.1HEAT PUMP :PRH-5,8,10,15,20p.1PRH-5,8,10,15,20-Lp.1DATA BOOKp.1CONTENTSp.2SAFETY FOR USE-----------------------------------------------------2p.2A COMPLETE LINE UP-----------------------------------------------4p.2FEATURES ---------------------------------------------------------------5p.2DESCRIPTIONS --------------------------------------------------------6p.2MECHANICAL SPECIFICATIONS----------------------------------6p.2TYPICAL INSTALLATION EXAMPLE------------------------------7p.2SPECIFICATIONS ------------------------------------------------------8p.2ELECTRICAL DATA ----------------------------------------------------9p.2CAPACITY TABLES---------------------------------------------------10p.2FAN PERFORMANCE -----------------------------------------------21p.2NC CURVES------------------------------------------------------------25p.2OUTLINE DIMENSIONS --------------------------------------------27p.2WIRING DIAGRAMS -------------------------------------------------29p.2ELECTRICAL OPERATION FLOW CHARTS------------------41p.2REFRIGERANT CYCLE SCHEMATICS-------------------------45p.2SAFETY & CONTROL DEVICES ---------------------------------48p.2ACCESSORY AVAILABILITY --------------------------------------48p.2PHYSICAL DATA ------------------------------------------------------49p.2INSTALLATION --------------------------------------------------------51p.2INSTRUCTIONS FOR USE ----------------------------------------54p.2SPECIFICATION GUIDELINES -----------------------------------57p.2SAFETY FOR USEp.3Warningp.3fire may result. If you need to have the unitp.3Cautionp.4A COMPLETE LINE UPp.5PR-5YC PRH-5YA PRH-5YA-Lp.5(PRH ONLY)p.5Cooling capacityp.5Heatling capacityp.514,000 kcal/h 55,600 BTU/h 16.3 kWp.513,000 kcal/h 51,600 BTU/h 15.1 kWp.5PR-8YC PRH-8YA PRH-8YA-Lp.520,500 kcal/h 81,300 BTU/h 23.8 kWp.519,800 kcal/h 78,600 BTU/h 23 kWp.5PR-10YC PRH-10YA PRH-10YA-Lp.525,500 kcal/h 101,200 BTU/h 29.7 kWp.527,500 kcal/h 109,100 BTU/h 32 kWp.5PR-15YC PRH-15YA PRH-15YA-Lp.539,100 kcal/h 155,100 BTU/h 45.5 kWp.539,800 kcal/h 157,900 BTU/h 46.3 kWp.5PR-20YC PRH-20YA PRH-20YA-Lp.552,300 kcal/h 207,500 BTU/h 60.8 kWp.552,600 kcal/h 208,700 BTU/h 61.2 kWp.5FEATURESp.6High Sensible Cooling Capacityp.6Labor Saving Installationp.6Comfort Heatingp.6Low Ambient Coolingp.6Highly Efficient Operationp.6Wide Electrical Control Capabilityp.6Flexibility of Supply Air Deliveryp.6DESCRIPTIONSp.7MECHANICAL SPECIFICATIONSp.7Generalp.7Condenser Coilsp.7Refrigeration Controlsp.7Evaporator Fansp.7Condenser Fanp.7Compressorsp.7Evaporator Coilsp.7TYPICAL INSTALLATION EXAMPLEp.8SPECIFICATIONSp.9ELECTRICAL DATAp.10Coolingp.10CAPACITY TABLESp.11(Nominal Air Flow): PRH-5YA, PRH-5YA-Lp.12Heating Capacityp.12(Use for low ambient temp. parts): PR-5YC, PRH-5YA, PRH-5YA-Lp.12Cooling Capacity (Nominal Air Flow)p.12INDOOR INDOOR 20.0 25.0 30.0 35.0 40.0 46.0p.13Cooling Capacity (Nominal Air Flow): PR-8YC, PRH-8YA, PRH-8YA-Lp.13PRH-8YA-Lp.13
Page 1 of the Mitsubishi Electronics 8 user manual — AIR-COOLED ROOFTOP PACKAGED AIR CONDITIONERS
Page 1 · click to enlarge
Page 1

AIR-COOLED ROOFTOP PACKAGED AIR CONDITIONERS

Series

COOLING ONLY :PR-5,8,10,15,20

HEAT PUMP :PRH-5,8,10,15,20

PRH-5,8,10,15,20-L

DATA BOOK

Page 2 of the Mitsubishi Electronics 8 user manual — Table of Contents
Page 2 · Contents
Contents

Contents

AIR-COOLED ROOFTOP PACKAGED AIR CONDITIONERSp.1Seriesp.1COOLING ONLY :PR-5,8,10,15,20p.1HEAT PUMP :PRH-5,8,10,15,20p.1PRH-5,8,10,15,20-Lp.1DATA BOOKp.1CONTENTSp.2SAFETY FOR USE-----------------------------------------------------2p.2A COMPLETE LINE UP-----------------------------------------------4p.2FEATURES ---------------------------------------------------------------5p.2DESCRIPTIONS --------------------------------------------------------6p.2MECHANICAL SPECIFICATIONS----------------------------------6p.2TYPICAL INSTALLATION EXAMPLE------------------------------7p.2SPECIFICATIONS ------------------------------------------------------8p.2ELECTRICAL DATA ----------------------------------------------------9p.2CAPACITY TABLES---------------------------------------------------10p.2FAN PERFORMANCE -----------------------------------------------21p.2NC CURVES------------------------------------------------------------25p.2OUTLINE DIMENSIONS --------------------------------------------27p.2WIRING DIAGRAMS -------------------------------------------------29p.2ELECTRICAL OPERATION FLOW CHARTS------------------41p.2REFRIGERANT CYCLE SCHEMATICS-------------------------45p.2SAFETY & CONTROL DEVICES ---------------------------------48p.2ACCESSORY AVAILABILITY --------------------------------------48p.2PHYSICAL DATA ------------------------------------------------------49p.2INSTALLATION --------------------------------------------------------51p.2INSTRUCTIONS FOR USE ----------------------------------------54p.2SPECIFICATION GUIDELINES -----------------------------------57p.2SAFETY FOR USEp.3Warningp.3fire may result. If you need to have the unitp.3Cautionp.4A COMPLETE LINE UPp.5PR-5YC PRH-5YA PRH-5YA-Lp.5(PRH ONLY)p.5Cooling capacityp.5Heatling capacityp.514,000 kcal/h 55,600 BTU/h 16.3 kWp.513,000 kcal/h 51,600 BTU/h 15.1 kWp.5PR-8YC PRH-8YA PRH-8YA-Lp.520,500 kcal/h 81,300 BTU/h 23.8 kWp.519,800 kcal/h 78,600 BTU/h 23 kWp.5PR-10YC PRH-10YA PRH-10YA-Lp.525,500 kcal/h 101,200 BTU/h 29.7 kWp.527,500 kcal/h 109,100 BTU/h 32 kWp.5PR-15YC PRH-15YA PRH-15YA-Lp.539,100 kcal/h 155,100 BTU/h 45.5 kWp.539,800 kcal/h 157,900 BTU/h 46.3 kWp.5PR-20YC PRH-20YA PRH-20YA-Lp.552,300 kcal/h 207,500 BTU/h 60.8 kWp.552,600 kcal/h 208,700 BTU/h 61.2 kWp.5FEATURESp.6High Sensible Cooling Capacityp.6Labor Saving Installationp.6Comfort Heatingp.6Low Ambient Coolingp.6Highly Efficient Operationp.6Wide Electrical Control Capabilityp.6Flexibility of Supply Air Deliveryp.6DESCRIPTIONSp.7MECHANICAL SPECIFICATIONSp.7Generalp.7Condenser Coilsp.7Refrigeration Controlsp.7Evaporator Fansp.7Condenser Fanp.7Compressorsp.7Evaporator Coilsp.7TYPICAL INSTALLATION EXAMPLEp.8SPECIFICATIONSp.9ELECTRICAL DATAp.10Coolingp.10CAPACITY TABLESp.11(Nominal Air Flow): PRH-5YA, PRH-5YA-Lp.12Heating Capacityp.12(Use for low ambient temp. parts): PR-5YC, PRH-5YA, PRH-5YA-Lp.12Cooling Capacity (Nominal Air Flow)p.12INDOOR INDOOR 20.0 25.0 30.0 35.0 40.0 46.0p.13Cooling Capacity (Nominal Air Flow): PR-8YC, PRH-8YA, PRH-8YA-Lp.13PRH-8YA-Lp.13
Page 3 of the Mitsubishi Electronics 8 user manual — fire may result. If you need to have the unit
Page 3 · click to enlarge
Page 3

SAFETY FOR USE

Before conducting installation work, please read this ''SAFETY FOR USE'' carefully for correct installation. Since the caution items shown here contain important description relative to safety, please observe them without fail.

WarningErroneous handling gives a high possibility to induce serious results such as death or heavy injury. C a u t io nErroneous handling may induce serious injury depending on the situation.

After reading, please keep it with you together the Instruction Manual, and read it again at the movement of the unit.

Warning

Never repair the unit, remodel or transfer it to another site by yourself.

The unit should not be installed by the user.

If the unit is installed improperly, explosion, water leakage, electric shock or fire may be result. Consult your dealer or specialist subcontractor for repair and movement.

If they are performed improperly, water leakage, electric shock or repaired or moved, consult your dealer.

fire may result. If you need to have the unit

For installation, conduct the work correctly by following the Installation Manual.

Use only the specified refrigerant (R-22) to charge the refrigerant circuit. Do not mix it with any other refrigerant and do not allow air to remain in the circuit.

Improper installation may cause a fire, electrical shock or water leakage.

Air enclosed in the circuit can cause high pressure resulting in a rupture and other hazards.

Install the unit on a spot sufficiently durable against the unit weight.

Insufficient durability can cause an injury by the falling down of unit.

After completing installation work, make sure that refrigerant gas has not leaked.

If refrigerant gas has leaked and exposed to fan heater, stove, oven and so on, it may generate noxious gases.

All electric work must be performed by licensed technician, according to local regulations and the instructions given in this manual. The units should be powered by dedicated power lines.

Take a proper measure to suppress the critical concentration of refrigerant if leaked when installing the unit in a small room.

Power lines with insufficient capacity or improper electrical work may result in electric shock or fire.

The limit density is made not to be exceeded even if the refrigerant leaks by any chance. You are necessary to ventilation measures to prevent the accident. If the refrigerant leaks, hypoxia accident may caused. For the countermeasure to be taken, consult your dealer.

Use only the specified cables for wiring. The connections must be made secured without tension the terminals.

Improper connection or fastening can cause a fire or electrical shock.

The unit should be installed according to the instructions in order to minimize the risk of damage from earthquakes, typhoons or strong winds.

The terminal block cover of unit must be firmly attached to prevent entry of dust and moisture.

Improper mounting of the cover cause electric shock or fire.

Improper installation work can cause an injury by the falling down of the unit.

The unit must be installed on stable, flat surface, in a place where there is no accumulation of snow, leaves or rubbish.

Use only optional parts authorised by Mitsubishi Electric.

If the accessories are installed improperly, water leakage, electric shock or fire may result. Ask your dealer or an authorised company to install them.

The unit should be installed in a location where air and noise emitted by the unit will not disturb the neighbors.

If the unit is loosely mounted, it may fall, and cause injury.

Page 4 of the Mitsubishi Electronics 8 user manual — Caution
Page 4 · click to enlarge
Page 4

Caution

Refrain from installing the unit in an area where flammable gas can accumulate around the unit.

Arrange the configuration of wiring not to bring up the panel and terminal cover, and fasten the panel and terminal cover securely.

If the flammable gas can accumulate around the unit, an explosion can occur.

The poor mounting of the panel or terminal cover may cause the heat generation of the terminal connection, a fire or electrical shock.

When the unit is installed at telecommunication centers or hospitals, take a proper provision against noise.

If washed with water, electrical shock may be caused. Do not wash the unit with water.

The erroneous operation of air conditioner may be induced by inverter equipment, independent power device, medical equipment or communication equipment. While the erroneous operation of medical equipment or communication equipment may caused by the air conditioner.

Do not handle the switch with wet hands.

Otherwise electrical shock can be resulted.

Be very careful on handling the unit.

When carrying in outdoor unit, be sure to support it at four points. Carrying in and lifting with 3-point support may make outdoor unit unstable, resulting in a fall of it. The unit should not be carried by only one person if it is more than 20kg. Some units use PP bands for packing. Do not use any PP band for delivery purpose. Do not touch the heat exchanger fins with your bear hands. Doing so may cut your hands. Be sure to safely dispose the packaging materials. Packaging materials, such as catches and other metal or wooden parts, may cause stabs or other injuries. Tear off and discard plastic packing bags so that children will not play any of them. If children play with a plastic bag which was not torn off, it may cause a risk of suffocation.

For special use as for foods, animals/plants, precision equipment or art objects, the applicability should be confirmed beforehand.

As the use for the applications other than that designed originally may result in the deterioration of the quality. Consult your dealer in this regard.

Do not use the unit under a special atmosphere.

Installing the unit at the following places may cause a trouble, a place where much machine oil, salt sonnet, humidity or dust, spa district, a place full of sulfur gas, volatile gas, or corrosive gas, a place near high frequency processing machine.

Thermal insulation of the drain pipes is necessary prevent dew condensation.

If the drain pipes are not properly insulated, condensation will result and drip on ceiling, floor or other possessions.

The base and attachments of the unit should be periodically checked for looseness, cracks or other damage.

The drain piping must process by surely,and insulate the drain piping not to be dewy.

If such defects are left uncorrected, the unit may fall and cause personal injury or property damage.

When the room humidity exceeds 80% or when the drain pipe is clogged, water may drip from the indoor unit. The outdoor unit produces condensation during the heating operation. Make sure to provide drainage around the outdoor unit if such condensation is likely to cause damage.

Turn on the main power switch more than 6 hours before starting operation.

Do not turn the main power switch OFF during seasons of heavy use, doing so can result In failure.

Install drain piping according to this Installation Manual to ensure proper drainage. Place thermal insulation on the pipes to prevent condensation.

Do not touch the compressor or refrigerant piping without wearing glove on your hands.

Touching directly such part can cause a burn or frostbite as it becomes high or low temperature according to the refrigerant state.

Improper drain piping may cause water leakage and damage to furniture or other possessions.

Do not touch the metal edges inside the unit without wearing glove on your hands.

The unit must be properly earth connected.

Do not connect the earth wire to gas pipe, city water pipe, lightning rod or telephone earth wire. Improper earth connection may cause electrical shock.

Touching directly it may injure your hands.

Do not remove the front panel or the fan guard from the unit when it is running.

When installing at a watery place, provide an electric leak breaker.

You could be injured if you touch rotating, hot or high- voltage parts.

Failure to mount the electric leak breaker may cause electrical shock.

Do not operate the air conditioner without the air filter set place.

Make sure that there is a main power switch. Use breaker or fuse with proper capacity.

Dust may accumulate, and cause a failure.

At emergency (if you smell something burning), stop operation and turn the power source switch off.

Using a wire or a copper wire instead of proper capacity of fuse can cause fire or trouble. Other appliances connected to the same line could cause an overload.

Continuing the operation without eliminating the emergency state may cause a machine trouble, fire, or electrical shock.

For the power lines, use standard cables of sufficient current capacity.

After stopping operation, be sure to wait for five minutes before turning off the main power switch.

Otherwise, current leakage, overheating or fire may occur.

Otherwise, water leakage or unit failure may occur.

When installing the power lines, do not apply tension to the cables.

The tighten or loosen the connections may cause generate heat and cause fire.

Page 5 of the Mitsubishi Electronics 8 user manual — 39,800 kcal/h 157,900 BTU/h 46.3 kW
Page 5 · click to enlarge
Page 5

A COMPLETE LINE UP

Mitsubishi Electronics 8 — A COMPLETE LINE UP diagram (page 5)
Fig. 1

PR-5YC PRH-5YA PRH-5YA-L

(PRH ONLY)

Cooling capacity

Heatling capacity

14,000 kcal/h 55,600 BTU/h 16.3 kW

13,000 kcal/h 51,600 BTU/h 15.1 kW

PR-8YC PRH-8YA PRH-8YA-L

Mitsubishi Electronics 8 — PR-5YC PRH-5YA PRH-5YA-L diagram (page 5)
Fig. 2

(PRH ONLY)

Cooling capacity

Heatling capacity

20,500 kcal/h 81,300 BTU/h 23.8 kW

19,800 kcal/h 78,600 BTU/h 23 kW

PR-10YC PRH-10YA PRH-10YA-L

(PRH ONLY)

Cooling capacity

Heatling capacity

25,500 kcal/h 101,200 BTU/h 29.7 kW

27,500 kcal/h 109,100 BTU/h 32 kW

PR-15YC PRH-15YA PRH-15YA-L

(PRH ONLY)

Cooling capacity

Heatling capacity

39,100 kcal/h 155,100 BTU/h 45.5 kW

Mitsubishi Electronics 8 — (PRH ONLY) diagram (page 5)
Fig. 3

39,800 kcal/h 157,900 BTU/h 46.3 kW

PR-20YC PRH-20YA PRH-20YA-L

(PRH ONLY)

Cooling capacity

Heatling capacity

52,300 kcal/h 207,500 BTU/h 60.8 kW

52,600 kcal/h 208,700 BTU/h 61.2 kW

Page 6 of the Mitsubishi Electronics 8 user manual — Flexibility of Supply Air Delivery
Page 6 · click to enlarge
Page 6

FEATURES

High Sensible Cooling Capacity

Labor Saving Installation

The sensible cooling capacity has been significantly improved through optimized heat exchanger design.

Because of the single unit configuration, all refrigeration work can be omitted. The unit operation can commence immediately after connection to the power supply, drain piping, ducting and control system.

Comfort Heating

The PRH series are designed to provide effective heating even when the outside temperature is down to 0˚C. The PRH-L series are designed to provide effective heating even when the outside temperature is down to -10˚C.In addition, the twin circuit models, PRH-15,20YA, PRH-15,20YA-L are provided with control features that prevents both refrigeration circuits defrosting at the same time. This ensures constant comfort conditions during defrost and varying loads.

Low Ambient Cooling

In applications with relatively high internal loads, there may be a requirement for all series to operate on cooling at low ambient conditions. An optional accessory is available to maintain the refrigeration circuit in balance at outdoor temperatures as low as 0˚C (PRH only).In case of PR,PRH-L is -5˚C. Please consult your local Mitsubishi Electric Sales office for application advice on this accessory.

Highly Efficient Operation

The EER (Energy Efficiency Ratio) on these models is greatly improved by revised design specifications and by being manufactured stringently to Mitsubishi Electric high quality standards.

Wide Electrical Control Capability

All series may be ordered in either of two control configurations. The factory standard is for provision of a 24 volt terminal block to enable a field wired control of the contractors choice to be connected. Alternatively, for models PR-5-10YC,PRH-5-10YA, PRH-5-10YA-L the intelligent "K" series remote control system may be ordered. The K control utilizes a microprocessor and includes liquid crystal display with touch pad for adjustment of control parameters. These options give the flexibility to enable connection to Building Management Systems, smoke spill cycles, economy cycles, remote monitoring etc. Please consult your local Mitsubishi Electric Sales office for application advice on these controls.

Flexibility of Supply Air Delivery

All series feature belt driven Supply Air fans enabling accurate matching of actual airflow rates to the specified quantities. Accurate commissioning is assisted by the capability to exchange pulleys and belts if necessary to achieve the desired air balance.

Page 7 of the Mitsubishi Electronics 8 user manual — Evaporator Coils
Page 7 · click to enlarge
Page 7

DESCRIPTIONS

MITSUBISHI ELECTRIC Rooftop Air Conditioners Series PR,PRH,RPH-L are available in a wide range of sizes and models to enable the designer to select the best model for each application. The complete range has been designed for outdoor installation, and the units are provided with the latest technological features to ensure economical, reliable and comfortable ducted type air conditioning. All series units are completely assembled, wired and strictly tested at the factory. They consist of a

compressors, air-cooled condensers, evaporator fans, condenser fans and auxiliary and control equipment, completely packaged in a water-proof enclosure. With the development of all series demands for such features as light weight, compactness, increased capacity, appropriate static pressure , air flow control, and having flexibility of inter-facing energy saving electronic controls Mitsubishi Electric have met market expectations.

MECHANICAL SPECIFICATIONS

General

Condenser Coils

All units are factory assembled, piped, internally wired and fully charged with R-22. They are also tested and checked under a strict quality control system in the factory. All units are designed for outdoor rooftop or ground level installation. Exterior surfaces of all units are phosphatized, zinc-coated steel with acrylic resin primer and ivory white baked enamel finish.

Unnecessary power input due to higher discharge pressure is avoided by high performance designs of cross-finned coils. Condenser coils are made of 9.52mm OD, 0.35mm thick seamless copper tubes mechanically bonded to 0.12mm thick aluminium plate fins. Each coil is factory pressure and leak tested at 3.3MPa.

Refrigeration Controls

Evaporator Fans

Refrigeration controls include condenser fan, evaporator fan and compressor contactor. Each circuit of the unit has a separate set of refrigeration controls. PR, PRH,PRH-L-15,20 units have two independent circuits.

Belt-drive, forward curved, centrifugal type fans made of galvanized steel are used to deliver an accurate airflow at low noise level.

Condenser Fan

Compressors

This direct-drive propeller fan is dynamically balanced, to ensure smooth airflow. A weather- proof three-phase squirrel cage induction motor is used to drive the condenser fan.

All units have high efficiency type hermetic line starting compressors. Compressors are equipped with thermal overload protector, overcurrent relay and high pressure protection controls. Crankcase heaters are standard .

Evaporator Coils

Highly efficient cross-finned coils are applied to provide a larger cooling capacity with low air speed on the coil. Coils are made of 9.52mm OD and 0.35mm thick seamless copper tubing mechanically bonded to 0.12mm thick aluminium fins and are factory leak tested at a pressure of 3.3MPa. They are provided with strainers attached to the capillary tubes to further ensure a clean system.

Page 8 of the Mitsubishi Electronics 8 user manual — TYPICAL INSTALLATION EXAMPLE
Page 8 · click to enlarge
Page 8

TYPICAL INSTALLATION EXAMPLE

Mitsubishi Electronics 8 — TYPICAL INSTALLATION EXAMPLE diagram (page 8)
Fig. 4
Page 9 of the Mitsubishi Electronics 8 user manual — SPECIFICATIONS
Page 9 · click to enlarge
Page 9

SPECIFICATIONS

ITEMPR-5YC PRH-5YA PRH-5YA-LPR-8YC PRH-8YA PRH-8YA-LPR-10YC PRH-10YA PRH-10YA-LPR-15YC PRH-15YA PRH-15YA-LPR-20YC PRH-20YA PRH-20YA-L TOTAL COOLING CAPACITY (GROSS)kW16.323.829.746.360.8 BTU/h55,60081,300101,200157,900207,500 kcal/h14,00020,50025,50039,80052,300 SENSIBLE COOLING CAPACITY (GROSS)kW1319.725.338.450.2 BTU/h44,40067,10086,500130,900171,400 kcal/h11,20016,90021,80033,00043,200 TOTALH EATING CAPACITY (GROSS) ( PRH-YA,PRH-YA-L ONLY)kW15.1233245.561.2 BTU/h51,60078,600109,100155,100208,700 kcal/h13,00019,80027,50039,10052,600 CAPACITY STEPS%0-1000-50-100 REFRIGERANTR22 (FACTORY CHARGED) R EFRIGERANT CONTROLCAPILLARY TUBE EXTERNAR FINISHACRYLIC RESIN COATING COLOR (MUNSELL NO.)MUNSELL 5Y8/1 DIMENSIONHEIGHTmm1,0001,200 WIDTHmm1,0001,3001,990 DEPTHmm1,6001,840 NET WEIGHTkg299393413698729 COMPRESSORHERMETIC LINE START (RECIPROCATING) M OTOR OUTPUTkW3.735.67.52 X5.62X7.5 INDOOR COILCROSS FIN COIL F ANCENTRIFUGAL (GALVANIZED STEEL) - BELT DRIVE FAN MOTORTHREE PHASE CAGE INDUCTION MOTOR FAN MOTOR OUTPUTkW0.751.11.52.23 NOMINAL AIR FLOWCMM5484100168190 CFM1,9072,9673,5325,9346,711 L/S9001,4001,6602,8003,160 EXTERNAL STATIC PRESSUREmmAq1010102020 Pa100100100200200 OUTDOOR COILCROSS FIN COIL FANPROPELLER - DIRECT DRIVE FAN MOTORTHREE PHASE CAGE INDUCTION MOTOR FANM OTOR OUTPUTkW0.150.350.352X0.352X0.35 NOMINAL AIR FLOWCMM951851852X1852X185 CFM3,3556,5346,5342X6,5342X6,534 L/S1,5833,0833,0832X3,0832X3,083 D RAIN CONNECTIONmm25.4 PROTECTION DEVICESHIGH PRESSURE SWITCH,FUSE OVER CURRENT RELAY (COMP.& INDOOR FAN,OUTDOOR FAN ) INTERNAL THERMOSTAT (COMP. & OUTDOOR FAN ) ANTI SHORT-CYCLE TIMER, FREEZE & FROST PROTECTOR
Page 10 of the Mitsubishi Electronics 8 user manual — ELECTRICAL DATA
Page 10 · click to enlarge
Page 10

ELECTRICAL DATA

Cooling

VOLTITEMPR-5YC PRH-5YA PRH-5YA-LPR-8YC PRH-8YA PRH-8YA-LPR-10YC PRH-10YA PRH-10YA-LPR-15YC PRH-15YA PRH-15YA-LPR-20YC PRH-20YA PRH-20YA-L 415VTOTAL INPUTkW5.48.311.416.822.7 TOTAL RUN CURRENTA10.315.920.230.839.1 POWER FACTOR%7373797681 START CURRENTA6287100115135 COMPRESSOR INPUTkW3.926.469.222 X 6.552 X 9.30 RUN CURRENTA7.4411.7015.622 X 11.742 X 15.22 I/D FAN INPUTkW1.241.301.642.623.02 RUN CURRENTA2.262.903.284.726.06 O/D FAN INPUTkW0.240.540.542 X 0.542 X 0.54 RUN CURRENTA0.61.31.32 X 1.32 X 1.3 380VTOTAL INPUTkW5.48.311.416.822.7 TOTAL RUN CURRENTA11.217.321.933.642.6 POWER FACTOR%7373797681 START CURRENTA6895109126147 COMPRESSOR INPUTkW3.926.469.222 X 6.552 X 9.30 RUN CURRENTA8.0612.7116.902 X 12.802 X 16.57 I/D FAN INPUTkW1.241.301.642.623.02 RUN CURRENTA2.483.173.585.166.62 O/D FAN INPUTkW0.240.540.542 X 0.542 X 0.54 RUN CURRENTA0.661.421.422 X 1.422 X 1.42 Heating (PRH,PRH-L Only) Heating
VOLTITEMPRH-5YA PRH-5YA-LPRH-8YA PRH-8YA-LPRH-10YA PRH-10YA-LPRH-15YA PRH-15YA-LPRH-20YA PRH-20YA-L 415VTOTAL INPUTkW4.87.09.614.419.3 TOTAL RUN CURRENTA9.814.118.227.234.8 POWER FACTOR%6869737477 START CURRENTA6287100111131 COMPRESSOR INPUTkW3.325.167.422 X 5.352 X 7.60 RUN CURRENTA6.949.9013.622 X 9.942 X 13.07 I/D FAN INPUTkW1.241.301.642.623.02 RUN CURRENTA2.262.903.284.726.06 O/D FAN INPUTkW0.240.540.542 X 0.542 X 0.54 RUN CURRENTA0.61.31.32 X 1.32 X 1.3 380VTOTAL INPUTkW4.87.09.614.419.3 TOTAL RUN CURRENTA10.715.420.029.638.1 POWER FACTOR%6869737477 START CURRENTA6895109121143 COMPRESSOR INPUTkW3.325.167.422 X 5.352 X 7.60 RUN CURRENTA7.5610.8115.002 X 10.82 X 14.32 I/D FAN INPUTkW1.241.301.642.623.02 RUN CURRENTA2.483.173.585.166.62 O/D FAN INPUTkW0.240.540.542 X 0.542 X 0.54 RUN CURRENTA0.661.421.422 X 1.422 X 1.42
Page 11 of the Mitsubishi Electronics 8 user manual — CAPACITY TABLES
Page 11 · click to enlarge
Page 11

CAPACITY TABLES

PRH-5YA, PRH-5YA-L Cooling Capacity (Nominal Air Flow):PR-5YC,PR-5YC PRH-5YA-L PRH-5YAOUTDOOR DB ˚C46.0T/I kW5.75.85.85.75.85.85.96.05.85.85.96.06.16.25.96.06.16.26.36.46.06.16.26.36.46.56.16.26.36.46.5 SHF0.750.670.570.890.800.710.620.540.940.840.750.660.570.510.880.780.690.620.540.460.900.810.730.650.570.500.930.850.760.690.61 SHC kW9.88.97.811.610.69.78.87.912.511.510.79.68.67.912.511.410.49.58.67.513.112.211.210.39.38.414.013.112.111.310.2 Q kW13.013.313.713.013.313.714.214.613.313.714.214.615.015.414.214.615.015.415.916.414.615.015.415.916.416.815.015.415.916.416.8 40.0T/I kW5.45.55.55.45.55.55.65.75.55.55.65.75.85.95.65.75.85.96.06.15.75.85.96.06.16.25.85.96.06.16.2 SHF0.730.650.560.860.780.690.600.530.900.810.730.640.560.500.850.760.670.600.530.460.870.780.710.630.560.490.890.820.740.670.59 SHC kW10.19.28.211.911.110.19.18.312.811.911.010.09.08.212.811.910.79.89.08.013.612.511.610.69.78.814.213.412.511.710.6 Q kW13.814.214.713.814.214.715.115.614.214.715.115.616.016.415.115.616.016.416.917.415.616.016.416.917.418.016.016.416.917.418.0 35.0T/I kW5.15.25.35.15.25.35.35.45.25.35.35.45.55.65.35.45.55.65.75.85.45.55.65.75.85.95.55.65.75.85.9 SHF0.720.640.550.840.760.670.590.520.880.790.710.630.550.490.830.740.660.590.520.450.850.760.690.620.550.480.870.800.720.650.58 SHC kW10.49.68.512.211.410.39.48.513.212.211.310.39.28.513.212.111.110.29.28.213.912.811.911.010.19.114.613.812.711.911.0 Q kW14.515.015.414.515.015.415.916.315.015.415.916.316.817.315.916.316.817.317.718.316.316.817.317.718.318.916.817.317.718.318.9 30.0T/I kW4.95.05.04.95.05.05.15.25.05.05.15.25.25.35.15.25.25.35.45.55.25.25.35.45.55.65.25.35.45.55.6 SHF0.710.630.550.820.740.660.590.520.860.770.700.620.540.480.810.720.650.580.510.450.830.750.680.610.540.480.850.780.700.630.57 SHC kW10.89.88.912.511.510.69.88.913.412.411.610.69.58.613.412.311.410.49.48.614.213.212.211.310.39.515.014.013.012.011.3 Q kW15.215.616.115.215.616.116.617.115.616.116.617.117.618.016.617.117.618.018.519.117.117.618.018.519.119.817.618.018.519.119.8 25.0T/I kW4.74.84.84.74.84.84.94.94.84.84.94.95.05.14.94.95.05.15.15.24.95.05.15.15.25.35.05.15.15.25.3 SHF0.700.620.540.810.730.650.580.510.840.760.690.610.530.470.790.710.640.570.500.440.810.730.670.600.530.470.830.760.690.620.56 SHC kW11.110.19.112.811.910.910.09.113.712.811.910.99.78.813.712.611.710.79.78.814.413.412.611.610.59.715.214.313.312.311.5 Q kW15.816.316.815.816.316.817.317.816.316.817.317.818.318.817.317.818.318.819.319.917.818.318.819.319.920.618.318.819.319.920.6 20.0T/I kW4.54.64.64.54.64.64.74.74.64.64.74.74.84.84.74.74.84.84.94.94.74.84.84.94.95.04.84.84.94.95.0 SHF0.690.610.540.800.720.640.570.510.830.750.680.600.530.470.780.700.630.560.500.440.800.720.660.590.530.470.820.750.680.610.55 SHC kW11.310.39.413.112.211.110.29.414.013.112.211.110.19.214.013.012.010.910.19.114.813.712.911.911.010.115.614.613.712.611.8 Q kW16.416.917.416.416.917.417.918.516.917.417.918.519.019.517.918.519.019.520.120.718.519.019.520.120.721.419.019.520.120.721.4 OPERATION RANGEINDOORWB ˚C15161715161718191617181920211819202122231920212223242021222324 INDOORDB ˚C202224262830
Note1. * Q :COOLING CAPACITY SHC:SENSIBLE HEAT CAPACITY T/I:TOTAL INPUT 601,0001.0131.005 559201.01.0 508300.9880.994 Factor for Various Air Flow457500.9750.987 CMML/SCAPACITYTOTAL INPUT AIR VOLUME PR-5YC PRH-5YA PRH-5YA-LCOOLING
Page 12 of the Mitsubishi Electronics 8 user manual — Cooling Capacity (Nominal Air Flow)
Page 12 · click to enlarge
Page 12

(Nominal Air Flow): PRH-5YA, PRH-5YA-L

PRH-5YA OUTDOOR WB ˚C0.0T/I kW4.04.04.14.14.24.24.24.34.34.34.44.44.4 Q kW13.113.012.912.912.812.712.712.612.512.512.412.312.3 -5.0T/I kW3.83.83.83.83.93.93.94.04.04.04.14.14.1 Q kW11.211.211.111.111.010.910.910.810.710.710.610.510.5 -10.0T/I kW3.73.73.73.73.73.73.73.83.83.83.83.83.8 Q kW9.59.59.49.49.39.39.29.29.19.19.08.98.9 RANGE INDOORDB ˚C15161718192021222324252627
PRH-5YA-L PRH-5YA˚C OUTDOOR WB15.0T/I kW5.15.15.25.25.35.35.45.45.55.55.65.65.7 Q kW19.619.519.419.419.319.219.119.018.918.818.718.618.4 10.0T/I kW4.74.74.84.84.94.95.05.05.15.15.25.25.3 Q kW17.417.317.217.217.117.016.916.816.716.616.516.416.3 5.0T/I kW4.34.34.34.44.44.54.54.64.64.74.74.84.8 Q kW15.115.014.914.914.814.814.714.614.514.414.314.214.2 OPERATION RANGEINDOOR˚C DB15161718192021222324252627
601,0001.0080.990 559201.01.0 508300.9881.018 457500.9751.035 Factor for Various Air Flow CMML/SCAPACITYTOTAL INPUT AIR VOLUME PRH-5YA PRH-5YA-LHEATING
* QHEATING CAPACITY T/I : TOTAL INPUT

Heating Capacity

OUTDOOR DB ˚C15.0T/I kW4.34.44.44.34.44.44.54.54.44.44.54.54.64.64.54.54.64.64.74.74.54.64.64.74.74.84.64.64.74.74.8 Note1. * Q :COOLING CAPACITY SHC:SENSIBLE HEAT CAPACITY T/I:TOTAL INPUT SHF0.690.610.540.790.720.640.570.510.820.750.680.600.530.470.770.700.630.560.500.440.790.720.650.590.520.460.810.740.670.610.55 SHC kW11.710.69.713.412.511.510.59.714.313.412.611.510.49.514.213.412.311.310.49.415.114.113.112.311.110.215.914.913.913.112.2 Q kW16.917.417.916.917.417.918.519.117.417.918.519.119.620.218.519.119.620.220.821.419.119.620.220.821.422.119.620.220.821.422.1 10.0T/I kW4.24.24.34.24.24.34.34.44.24.34.34.44.44.54.34.44.44.54.54.64.44.44.54.54.64.64.44.54.54.64.6 SHF0.680.610.530.780.710.640.570.500.810.740.670.600.530.470.760.690.620.560.500.440.780.710.640.580.520.460.800.730.660.600.54 SHC kW11.810.99.713.612.711.710.89.814.513.512.711.710.79.814.413.512.511.610.79.715.214.313.312.411.410.416.115.214.113.212.3 Q kW17.417.918.317.417.918.318.919.517.918.318.919.520.120.818.919.520.120.821.422.019.520.120.821.422.022.720.120.821.422.022.7 5.0T/I kW4.14.14.24.14.14.24.24.34.14.24.24.34.34.44.24.34.34.44.44.54.34.34.44.44.54.54.34.44.44.54.5 PRH-5YA-LPRH-5YA SHF0.680.600.530.780.710.630.560.500.810.740.670.590.520.460.760.690.620.550.490.430.780.710.640.580.510.450.790.720.660.600.54 SHC kW12.010.99.913.812.911.810.810.014.713.812.911.710.79.814.713.712.711.710.79.715.514.613.612.611.510.416.215.314.413.512.5 Q kW17.718.218.717.718.218.719.319.918.218.719.319.920.521.219.319.920.521.221.822.519.920.521.221.822.523.220.521.221.822.523.2 0.0T/I kW4.04.04.14.04.04.14.14.24.04.14.14.24.24.34.14.24.24.34.34.44.24.24.34.34.44.44.24.34.34.44.4 SHF0.670.600.530.770.700.630.560.500.800.730.660.590.520.460.750.680.610.550.490.430.770.700.630.570.510.450.780.710.550.590.53 SHC kW12.011.010.113.812.912.011.010.114.713.912.911.910.89.914.713.712.711.810.89.815.614.613.512.611.610.616.215.312.213.512.5 Q kW17.918.419.017.918.419.019.620.218.419.019.620.220.821.519.620.220.821.522.122.820.220.821.522.122.823.520.821.522.122.823.5 -5.0T/I kW4.04.04.14.04.04.14.14.24.04.14.14.24.24.34.14.24.24.34.34.44.24.24.34.34.44.44.24.34.34.44.4 SHF0.670.600.530.770.700.630.560.500.800.730.660.590.520.460.750.680.610.550.490.430.770.700.630.570.510.450.780.710.650.590.53 SHC kW12.111.110.113.913.012.011.010.214.813.913.012.010.99.914.813.812.711.910.99.915.614.613.612.711.710.716.315.314.513.612.6 Q kW18.018.519.118.018.519.119.720.318.519.119.720.320.921.619.720.320.921.622.323.020.320.921.622.323.023.720.921.622.323.023.7 OPERATION RANGEINDOORWB ˚C15161715161718191617181920211819202122231920212223242021222324 INDOORDB ˚C202224262830

(Use for low ambient temp. parts): PR-5YC, PRH-5YA, PRH-5YA-L

601,0001.0131.005 559201.01.0 508300.9880.994 457500.9750.987 Factor for Various Air Flow CMML/SCAPACITYTOTAL INPUT AIR VOLUME PR-5YC PRH-5YA PRH-5YA-LCOOLING

Cooling Capacity (Nominal Air Flow)

Page 13 of the Mitsubishi Electronics 8 user manual — PRH-8YA
Page 13 · click to enlarge
Page 13

DB ˚C WB ˚C Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW

INDOOR INDOOR 20.0 25.0 30.0 35.0 40.0 46.0

Cooling Capacity (Nominal Air Flow): PR-8YC, PRH-8YA, PRH-8YA-L

PRH-8YA-L

OUTDOOR DB ˚C

PRH-8YA

PR-8YC

L/S 1,000 1,580

COOLING CAPACITY 0.940 0.963 0.987 1.022 TOTAL INPUT 0.978 0.987 0.996 1.010

PRH-8YA-L AIR VOLUME CMM 60 70 80 95

1,500 1,330 1,170 1.010 1.005

Factor for Various Air Flow

15 22.8

OPERATION

PRH-8YA

PR-8YC

RANGE

Page 14 of the Mitsubishi Electronics 8 user manual — OUTDOOR DB ˚C
Page 14 · click to enlarge
Page 14

(Nominal Air Flow): PRH-8YA, PRH-8YA-L

DB ˚C Q kW T/I kW Q kW T/I kW Q kW T/I kW

DB ˚C Q kW T/I kW Q kW T/I kW Q kW T/I kW

15 15.4 5.3 17.6 5.6 20.1 6.1

16 15.3 5.3 17.5 5.6 20.0 6.1

17 15.2 5.3 17.4 5.6 19.9 6.1

18 15.1 5.3 17.3 5.6 19.9 6.2

19 15.1 5.3 17.3 5.7 19.8 6.2

20 15.0 5.4 17.2 5.7 19.7 6.3

21 14.9 5.4 17.1 5.7 19.6 6.3

22 14.8 5.4 17.0 5.8 19.5 6.3

23 14.7 5.4 17.0 5.8 19.5 6.4

24 14.7 5.5 16.9 5.8 19.4 6.4

25 14.6 5.5 16.8 5.9 19.3 6.5

26 14.5 5.5 16.7 5.9 19.2 6.5

27 14.5 5.5 16.7 5.9 19.2 6.5

15 22.9 6.5 26.0 7.1 29.5 7.7

16 22.8 6.6 25.9 7.2 29.5 7.8

17 22.7 6.6 25.9 7.2 29.4 7.9

18 22.6 6.7 25.8 7.3 29.3 8.0

19 22.6 6.8 25.7 7.4 29.2 8.1

20 22.5 6.8 25.6 7.5 29.1 8.2

21 22.4 6.9 25.5 7.5 29.1 8.3

22 22.3 6.9 25.5 7.6 29.0 8.4

23 22.2 7.0 25.4 7.6 28.9 8.4

24 22.2 7.0 25.3 7.7 28.8 8.5

25 22.1 7.1 25.2 7.8 28.7 8.6

26 22.0 7.1 25.1 7.9 28.6 8.7

27 22.0 7.1 25.1 7.9 28.6 8.7

PRH-8YA-L AIR VOLUME CMM 60 70 80 90 95 L/S 1,000 1,170 1,330 1,500 1,580

HEATING CAPACITY 0.970 0.981 0.992 1.003 1.008 TOTAL INPUT 1.070 1.050 1.020 0.995 0.982

PRH-8YA

INDOOR -10 -5.0 0.0

INDOOR 5.0 10.0 15.0

OUTDOOR WB ˚C

OUTDOOR WB ˚C

* QHEATING CAPACITY T/I : TOTAL INPUT

PRH-8YA-L

PRH-8YA-L

PRH-8YA

Factor for Various Air Flow Factor for Various Air Flow

(Use for low ambient temp. parts): PR-8YC, PRH-8YA, PRH-8YA-L Heating Capacity

OPERATION

OPERATION

RANGE

RANGE

DB ˚C WB ˚C Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW

PRH-8YA

15 24.4 15.1 0.70 6.1 24.2 15.0 0.70 6.1 24.0 14.9 0.70 6.2 23.7 14.9 0.71 6.4 23.3 14.7 0.71 6.6

20 16 25.2 13.6 0.62 6.1 25.0 13.5 0.62 6.1 24.8 13.4 0.62 6.2 24.4 13.4 0.63 6.4 24.0 13.2 0.63 6.6

17 25.8 20.9 0.54 6.2 25.7 21.1 0.54 6.2 25.5 20.9 0.54 6.3 25.2 20.9 0.55 6.5 24.8 20.8 0.55 6.7

15 24.4 17.8 0.81 6.1 24.2 17.9 0.82 6.1 24.0 17.8 0.82 6.2 23.7 17.8 0.83 6.4 23.3 17.5 0.84 6.6

16 25.2 16.4 0.73 6.1 25.0 16.5 0.74 6.1 24.8 16.4 0.74 6.2 24.4 16.3 0.75 6.4 24.0 16.1 0.75 6.6

22 17 25.8 15.0 0.65 6.2 25.7 14.9 0.66 6.2 25.5 14.8 0.66 6.3 25.2 14.9 0.67 6.5 24.8 14.6 0.67 6.7

18 26.5 13.5 0.58 6.2 26.4 13.5 0.58 6.2 26.2 13.4 0.58 6.3 25.9 13.2 0.59 6.5 25.5 13.3 0.59 6.7

19 27.4 23.3 0.51 6.3 27.3 23.5 0.51 6.3 27.1 23.3 0.51 6.4 26.8 23.3 0.51 6.6 26.3 22.9 0.52 6.8

16 25.2 19.4 0.85 6.1 25.0 19.3 0.86 6.1 24.8 19.1 0.86 6.2 24.4 19.0 0.87 6.4 24.0 18.7 0.87 6.6

17 25.8 17.8 0.77 6.2 25.7 17.7 0.77 6.2 25.5 17.6 0.77 6.3 25.2 17.6 0.78 6.5 24.8 17.4 0.78 6.7

24 18 26.5 16.2 0.69 6.2 26.4 16.1 0.69 6.2 26.2 16.0 0.69 6.3 25.9 16.1 0.70 6.5 25.5 15.8 0.70 6.7

19 27.4 14.8 0.61 6.3 27.3 14.7 0.61 6.3 27.1 14.6 0.61 6.4 26.8 14.5 0.62 6.6 26.3 14.5 0.62 6.8

20 28.3 13.3 0.54 6.3 28.2 13.3 0.54 6.3 27.9 13.1 0.54 6.4 27.6 13.0 0.54 6.6 27.1 13.0 0.55 6.9

21 29.2 23.4 0.47 6.4 29.0 23.2 0.47 6.4 28.7 23.2 0.47 6.5 28.4 23.0 0.47 6.7 27.9 22.9 0.48 7.0

18 26.5 18.8 0.80 6.2 26.4 18.7 0.80 6.2 26.2 18.9 0.81 6.3 25.9 18.6 0.81 6.5 25.5 18.6 0.82 6.7

19 27.4 17.5 0.71 6.3 27.3 17.5 0.71 6.3 27.1 17.3 0.72 6.4 26.8 17.4 0.72 6.6 26.3 17.1 0.73 6.8

26 20 28.3 16.1 0.64 6.3 28.2 16.1 0.64 6.3 27.9 15.9 0.64 6.4 27.6 16.0 0.65 6.6 27.1 15.7 0.65 6.9

21 29.2 14.6 0.57 6.4 29.0 14.5 0.57 6.4 28.7 14.4 0.57 6.5 28.4 14.5 0.58 6.7 27.9 14.2 0.58 7.0

22 30.1 13.2 0.50 6.5 29.9 13.2 0.50 6.5 29.6 13.0 0.50 6.6 29.2 12.8 0.51 6.8 28.7 12.9 0.51 7.1

23 31.0 25.1 0.44 6.6 30.8 24.9 0.44 6.6 30.5 25.0 0.44 6.7 30.1 24.7 0.44 6.9 29.6 24.6 0.45 7.2

19 27.4 20.0 0.81 6.3 27.3 19.9 0.81 6.3 27.1 20.1 0.82 6.4 26.8 19.8 0.82 6.6 26.3 19.7 0.83 6.8

20 28.3 18.7 0.73 6.3 28.2 18.6 0.73 6.3 27.9 18.7 0.74 6.4 27.6 18.5 0.74 6.6 27.1 18.4 0.75 6.9

28 21 29.2 17.2 0.66 6.4 29.0 17.1 0.66 6.4 28.7 16.9 0.67 6.5 28.4 17.0 0.67 6.7 27.9 16.7 0.68 7.0

22 30.1 16.0 0.59 6.5 29.9 15.8 0.59 6.5 29.6 15.7 0.59 6.6 29.2 15.5 0.60 6.8 28.7 15.5 0.60 7.1

23 31.0 14.6 0.53 6.6 30.8 14.5 0.53 6.6 30.5 14.3 0.53 6.7 30.1 14.1 0.53 6.9 29.6 14.2 0.54 7.2

24 32.0 26.6 0.47 6.7 31.8 26.4 0.47 6.7 31.5 26.5 0.47 6.8 31.1 26.1 0.47 7.0 30.6 26.0 0.48 7.3

20 28.3 21.5 0.83 6.3 28.2 21.4 0.83 6.3 27.9 21.5 0.84 6.4 27.6 21.3 0.84 6.6 27.1 21.1 0.85 6.9

21 29.2 20.1 0.76 6.4 29.0 20.0 0.76 6.4 28.7 20.1 0.77 6.5 28.4 19.9 0.77 6.7 27.9 19.8 0.78 7.0

30 22 30.1 18.7 0.69 6.5 29.9 18.5 0.69 6.5 29.6 18.6 0.70 6.6 29.2 18.4 0.70 6.8 28.7 18.4 0.71 7.1

23 31.0 17.1 0.62 6.6 30.8 16.9 0.62 6.6 30.5 16.8 0.63 6.7 30.1 16.9 0.63 6.9 29.6 16.6 0.64 7.2

24 32.0 0.0 0.55 6.7 31.8 0.0 0.55 6.7 31.5 0.0 0.55 6.8 31.1 0.0 0.56 7.0 30.6 0.0 0.56 7.3

INDOOR INDOOR -5.0 0.0 5.0 10.0 15.0

PRH-8YA-L

PRH-8YA-L AIR VOLUME CMM 60 70 80 90 95

L/S 1,000 1,170 1,330 1,500 1,580

COOLING CAPACITY 0.940 0.963 0.987 1.010 1.022 TOTAL INPUT 0.978 0.987 0.996 1.005 1.010

PRH-8YA

OUTDOOR DB ˚C

PR-8YC

Cooling Capacity (Nominal Air Flow)

OPERATION

PRH-8YA

RANGE

PR-8YC

Page 15 of the Mitsubishi Electronics 8 user manual — PRH-10YA-L AIR VOLUME CMM 90 100 110 120
Page 15 · click to enlarge
Page 15

DB ˚C WB ˚C Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW

15 29.4 21.2 0.72 9.5 28.4 20.7 0.73 9.8 27.3 20.2 0.74 10.2 26.1 19.6 0.75 10.7 24.4 18.5 0.76 11.2 23.3 18.4 0.79 11.9

20 16 30.4 19.5 0.64 9.6 29.4 18.8 0.64 9.9 28.2 18.3 0.65 10.4 27.0 17.8 0.66 10.8 25.7 17.2 0.67 11.4 24.1 16.6 0.69 12.1

17 31.4 17.6 0.56 9.7 30.3 17.0 0.56 10.1 29.1 16.6 0.57 10.5 27.9 15.9 0.57 11.0 26.6 15.4 0.58 11.6 24.9 14.7 0.59 12.3

15 29.4 24.7 0.84 9.5 28.4 24.1 0.85 9.8 27.3 23.8 0.87 10.2 26.1 23.2 0.89 10.7 24.4 22.2 0.91 11.2 23.3 22.1 0.95 11.9

16 30.4 23.1 0.76 9.6 29.4 22.6 0.77 9.9 28.2 22.0 0.78 10.4 27.0 21.6 0.80 10.8 25.7 21.1 0.82 11.4 24.1 20.5 0.85 12.1

22 17 31.4 21.4 0.68 9.7 30.3 20.6 0.68 10.1 29.1 20.1 0.69 10.5 27.9 19.5 0.70 11.0 26.6 18.9 0.71 11.6 24.9 18.4 0.74 12.3

18 32.4 19.4 0.60 9.8 31.3 18.8 0.60 10.2 30.0 18.3 0.61 10.7 28.7 17.8 0.62 11.2 27.4 17.3 0.63 11.8 25.7 16.7 0.65 12.5

19 33.5 17.4 0.52 9.9 32.3 16.8 0.52 10.3 31.0 16.4 0.53 10.9 29.7 16.0 0.54 11.4 28.3 15.6 0.55 12.0 26.6 14.9 0.56 12.7

16 30.4 26.8 0.88 9.6 29.4 26.5 0.90 9.9 28.2 25.9 0.92 10.4 27.0 25.4 0.94 10.8 25.7 24.7 0.96 11.4 24.1 24.1 1.00 12.1

17 31.4 25.1 0.80 9.7 30.3 24.5 0.81 10.1 29.1 23.9 0.82 10.5 27.9 23.2 0.83 11.0 26.6 22.6 0.85 11.6 24.9 22.2 0.89 12.3

24 18 32.4 23.3 0.72 9.8 31.3 22.8 0.73 10.2 30.0 22.2 0.74 10.7 28.7 21.5 0.75 11.2 27.4 21.1 0.77 11.8 25.7 20.3 0.79 12.5

19 33.5 21.1 0.63 9.9 32.3 20.7 0.64 10.3 31.0 20.2 0.65 10.9 29.7 19.6 0.66 11.4 28.3 19.0 0.67 12.0 26.6 18.4 0.69 12.7

20 34.6 19.0 0.55 10.0 33.4 18.4 0.55 10.5 32.1 18.0 0.56 11.0 30.6 17.4 0.57 11.6 29.2 16.9 0.58 12.2 27.4 16.4 0.60 12.9

21 35.7 17.1 0.48 10.1 34.4 16.5 0.48 10.6 33.0 16.2 0.49 11.2 31.6 15.8 0.50 11.8 30.1 15.4 0.51 12.4 28.3 14.7 0.52 13.1

18 32.4 26.9 0.83 9.8 31.3 26.3 0.84 10.2 30.0 25.8 0.86 10.7 28.7 25.3 0.88 11.2 27.4 24.7 0.90 11.8 25.7 23.9 0.93 12.5

19 33.5 24.8 0.74 9.9 32.3 24.2 0.75 10.3 31.0 23.6 0.76 10.9 29.7 23.2 0.78 11.4 28.3 22.6 0.80 12.0 26.6 21.8 0.82 12.7

26 20 34.6 22.8 0.66 10.0 33.4 22.4 0.67 10.5 32.1 21.8 0.68 11.0 30.6 21.1 0.69 11.6 29.2 20.4 0.70 12.2 27.4 20.0 0.73 12.9

21 35.7 20.7 0.58 10.1 34.4 20.0 0.58 10.6 33.0 19.5 0.59 11.2 31.6 19.0 0.60 11.8 30.1 18.4 0.61 12.4 28.3 18.1 0.64 13.1

22 36.8 18.8 0.51 10.3 35.4 18.1 0.51 10.8 34.0 17.7 0.52 11.4 32.5 17.2 0.53 12.0 31.0 16.7 0.54 12.6 29.1 16.3 0.56 13.3

23 38.0 17.1 0.45 10.4 36.6 16.5 0.45 11.0 35.1 16.1 0.46 11.6 33.5 15.4 0.46 12.2 31.9 15.0 0.47 12.8 30.0 14.4 0.48 13.6

19 33.5 28.1 0.84 9.9 32.3 27.5 0.85 10.3 31.0 27.0 0.87 10.9 29.7 26.4 0.89 11.4 28.3 25.8 0.91 12.0 26.6 25.3 0.95 12.7

20 34.6 26.3 0.76 10.0 33.4 25.7 0.77 10.5 32.1 25.4 0.79 11.0 30.6 24.8 0.81 11.6 29.2 24.2 0.83 12.2 27.4 23.6 0.86 12.9

28 21 35.7 24.6 0.69 10.1 34.4 24.1 0.70 10.6 33.0 23.4 0.71 11.2 31.6 23.1 0.73 11.8 30.1 22.6 0.75 12.4 28.3 21.8 0.77 13.1

22 36.8 22.4 0.61 10.3 35.4 21.9 0.62 10.8 34.0 21.4 0.63 11.4 32.5 21.1 0.65 12.0 31.0 20.5 0.66 12.6 29.1 19.8 0.68 13.3

23 38.0 20.5 0.54 10.4 36.6 20.1 0.55 11.0 35.1 19.7 0.56 11.6 33.5 19.1 0.57 12.2 31.9 18.5 0.58 12.8 30.0 18.0 0.60 13.6

24 39.2 18.8 0.48 10.6 37.7 18.1 0.48 11.2 36.1 17.7 0.49 11.8 34.5 17.3 0.50 12.4 32.9 16.8 0.51 13.1 30.8 16.0 0.52 13.9

20 34.6 30.1 0.87 10.0 33.4 29.7 0.89 10.5 32.1 29.2 0.91 11.0 30.6 28.5 0.93 11.6 29.2 28.0 0.96 12.2 27.4 27.1 0.99 12.9

21 35.7 28.2 0.79 10.1 34.4 27.9 0.81 10.6 33.0 27.4 0.83 11.2 31.6 26.9 0.85 11.8 30.1 26.2 0.87 12.4 28.3 25.8 0.91 13.1

30 22 36.8 26.1 0.71 10.3 35.4 25.5 0.72 10.8 34.0 25.2 0.74 11.4 32.5 24.7 0.76 12.0 31.0 24.2 0.78 12.6 29.1 23.3 0.80 13.3

23 38.0 24.3 0.64 10.4 36.6 23.8 0.65 11.0 35.1 23.5 0.67 11.6 33.5 22.8 0.68 12.2 31.9 22.3 0.70 12.8 30.0 21.6 0.72 13.6

24 39.2 22.3 0.57 10.6 37.7 21.9 0.58 11.2 36.1 21.3 0.59 11.8 34.5 20.7 0.60 12.4 32.9 20.1 0.61 13.1 30.8 19.7 0.64 13.9

INDOOR INDOOR 20.0 25.0 30.0 35.0 40.0 46.0

Cooling Capacity (Nominal Air Flow): PR-10YC, PRH-10YA, PRH-10YA-L

PRH-10YA-L

OUTDOOR DB ˚C

PRH-10YA

PR-10YC

L/S 1,500 1,660 1,830 2,000

COOLING CAPACITY 0.987 1.0 1.033 1.066 TOTAL INPUT 0.995 1.0 1.026 1.052

PRH-10YA-L AIR VOLUME CMM 90 100 110 120

Factor for Various Air Flow

OPERATION

PRH-10YA

PR-10YC

RANGE

Page 16 of the Mitsubishi Electronics 8 user manual — PRH-10YA-L
Page 16 · click to enlarge
Page 16

(Nominal Air Flow): PRH-10YA, PRH-10YA-L

DB ˚C Q kW T/I kW Q kW T/I kW Q kW T/I kW

DB ˚C Q kW T/I kW Q kW T/I kW Q kW T/I kW

15 21.5 7.6 24.6 7.9 28.0 8.4

16 21.4 7.6 24.5 7.9 27.9 8.5

17 21.3 7.6 24.4 8.0 27.8 8.5

18 21.2 7.7 24.3 8.0 27.7 8.6

19 21.1 7.7 24.2 8.1 27.6 8.7

20 21.0 7.7 24.1 8.1 27.5 8.7

21 20.9 7.8 24.0 8.2 27.4 8.8

22 20.8 7.8 23.9 8.2 27.3 8.9

23 20.7 7.8 23.8 8.3 27.2 8.9

24 20.6 7.9 23.7 8.3 27.1 9.0

25 20.5 7.9 23.5 8.4 26.9 9.0

26 20.5 7.9 23.5 8.4 26.9 9.1

27 20.4 7.9 23.4 8.4 26.8 9.1

15 31.9 9.0 36.5 9.8 41.1 10.5

16 31.8 9.1 36.4 9.9 40.9 10.6

17 31.7 9.2 36.2 10.0 40.7 10.7

18 31.6 9.2 36.1 10.0 40.6 10.8

19 31.4 9.3 35.9 10.1 40.4 10.9

20 31.3 9.4 35.8 10.2 40.2 11.0

21 31.2 9.5 35.7 10.3 40.1 11.1

22 31.1 9.5 35.5 10.4 39.9 11.2

23 30.9 9.6 35.3 10.5 39.7 11.3

24 30.8 9.7 35.2 10.6 39.6 11.4

25 30.7 9.8 35.1 10.7 39.4 11.5

26 30.6 9.8 35.0 10.7 39.3 11.6

27 30.5 9.9 34.8 10.8 39.1 11.7

PRH-10YA-L AIR VOLUME CMM 90 100 110 120 L/S 1,500 1,660 1,830 2,000

HEATING CAPACITY 0.992 1.0 1.025 1.050 TOTAL INPUT 1.016 1.0 0.971 0.942

PRH-10YA

INDOOR 5.0 10.0 15.0

INDOOR -10.0 -5.0 0.0

OUTDOOR WB ˚C

OUTDOOR WB ˚C

* QHEATING CAPACITY T/I : TOTAL INPUT

PRH-10YA-L

PRH-10YA-L

PRH-10YA

(Use for low ambient temp. parts): PR-10YC, PRH-10YA, PRH-10YA-L Heating Capacity

Factor for Various Air Flow Factor for Various Air Flow

OPERATION

OPERATION

RANGE

RANGE

PRH-10YA

DB ˚C WB ˚C Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW

15 32.7 22.6 0.69 8.6 32.3 22.3 0.69 8.6 31.8 22.3 0.70 8.7 31.2 22.2 0.71 8.9 30.4 21.9 0.72 9.1

20 16 33.6 20.8 0.62 8.6 33.2 20.6 0.62 8.6 32.7 20.3 0.62 8.7 32.2 20.3 0.63 8.9 31.4 19.8 0.63 9.2

17 34.7 18.7 0.54 8.7 34.3 18.5 0.54 8.7 33.8 18.3 0.54 8.8 33.2 18.3 0.55 9.0 32.4 17.8 0.55 9.3

15 32.7 26.5 0.81 8.6 32.3 26.5 0.82 8.6 31.8 26.1 0.82 8.7 31.2 25.9 0.83 8.9 30.4 25.2 0.83 9.1

16 33.6 24.5 0.73 8.6 33.2 24.6 0.74 8.6 32.7 24.2 0.74 8.7 32.2 24.2 0.75 8.9 31.4 23.6 0.75 9.2

22 17 34.7 22.6 0.65 8.7 34.3 22.6 0.66 8.7 33.8 22.3 0.66 8.8 33.2 22.2 0.67 9.0 32.4 21.7 0.67 9.3

18 35.7 20.7 0.58 8.8 35.3 20.5 0.58 8.8 34.8 20.2 0.58 8.9 34.2 20.2 0.59 9.1 33.4 19.7 0.59 9.4

19 36.8 18.8 0.51 8.9 36.5 18.6 0.51 8.9 36.0 18.4 0.51 9.0 35.3 18.0 0.51 9.2 34.5 17.9 0.52 9.5

16 33.6 28.6 0.85 8.6 33.2 28.6 0.86 8.6 32.7 28.1 0.86 8.7 32.2 28.0 0.87 8.9 31.4 27.6 0.88 9.2

17 34.7 26.4 0.76 8.7 34.3 26.1 0.76 8.7 33.8 26.0 0.77 8.8 33.2 25.9 0.78 9.0 32.4 25.6 0.79 9.3

24 18 35.7 24.6 0.69 8.8 35.3 24.4 0.69 8.8 34.8 24.4 0.70 8.9 34.2 23.9 0.70 9.1 33.4 23.7 0.71 9.4

19 36.8 22.4 0.61 8.9 36.5 22.3 0.61 8.9 36.0 22.3 0.62 9.0 35.3 21.9 0.62 9.2 34.5 21.7 0.63 9.5

20 38.1 20.6 0.54 9.0 37.8 20.4 0.54 9.0 37.3 20.1 0.54 9.1 36.6 19.8 0.54 9.3 35.7 19.6 0.55 9.6

21 39.4 18.5 0.47 9.1 39.1 18.4 0.47 9.1 38.6 18.1 0.47 9.2 37.8 17.8 0.47 9.4 36.8 17.7 0.48 9.7

18 35.7 28.2 0.79 8.8 35.3 27.9 0.79 8.8 34.8 27.8 0.80 8.9 34.2 27.4 0.80 9.1 33.4 27.1 0.81 9.4

19 36.8 26.1 0.71 8.9 36.5 25.9 0.71 8.9 36.0 25.9 0.72 9.0 35.3 25.4 0.72 9.2 34.5 25.2 0.73 9.5

26 20 38.1 24.0 0.63 9.0 37.8 24.2 0.64 9.0 37.3 23.9 0.64 9.1 36.6 23.8 0.65 9.3 35.7 23.2 0.65 9.6

21 39.4 22.1 0.56 9.1 39.1 22.3 0.57 9.1 38.6 22.0 0.57 9.2 37.8 21.9 0.58 9.4 36.8 21.3 0.58 9.7

22 40.7 20.4 0.50 9.2 40.4 20.2 0.50 9.2 39.8 19.9 0.50 9.4 39.1 19.9 0.51 9.6 38.1 19.4 0.51 9.9

23 42.1 18.5 0.44 9.3 41.8 18.4 0.44 9.3 41.2 18.1 0.44 9.5 40.4 17.8 0.44 9.7 39.3 17.7 0.45 10.0

19 36.8 29.8 0.81 8.9 36.5 29.6 0.81 8.9 36.0 29.5 0.82 9.0 35.3 28.9 0.82 9.2 34.5 28.6 0.83 9.5

20 38.1 27.8 0.73 9.0 37.8 27.6 0.73 9.0 37.3 27.6 0.74 9.1 36.6 27.1 0.74 9.3 35.7 26.8 0.75 9.6

28 21 39.4 26.0 0.66 9.1 39.1 25.8 0.66 9.1 38.6 25.9 0.67 9.2 37.8 25.3 0.67 9.4 36.8 25.0 0.68 9.7

22 40.7 24.0 0.59 9.2 40.4 23.8 0.59 9.2 39.8 23.9 0.60 9.4 39.1 23.5 0.60 9.6 38.1 23.2 0.61 9.9

23 42.1 21.9 0.52 9.3 41.8 21.7 0.52 9.3 41.2 21.8 0.53 9.5 40.4 21.4 0.53 9.7 39.3 21.2 0.54 10.0

24 43.4 20.0 0.46 9.4 43.1 19.8 0.46 9.4 42.5 20.0 0.47 9.6 41.6 19.6 0.47 9.8 40.5 19.0 0.47 10.2

20 38.1 31.2 0.82 9.0 37.8 31.4 0.83 9.0 37.3 31.3 0.84 9.1 36.6 31.1 0.85 9.3 35.7 30.7 0.86 9.6

21 39.4 29.6 0.75 9.1 39.1 29.3 0.75 9.1 38.6 29.3 0.76 9.2 37.8 29.1 0.77 9.4 36.8 28.7 0.78 9.7

30 22 40.7 27.7 0.68 9.2 40.4 27.5 0.68 9.2 39.8 27.5 0.69 9.4 39.1 27.0 0.69 9.6 38.1 26.7 0.70 9.9

23 42.1 25.7 0.61 9.3 41.8 25.5 0.61 9.3 41.2 25.5 0.62 9.5 40.4 25.0 0.62 9.7 39.3 24.8 0.63 10.0

24 43.4 23.9 0.55 9.4 43.1 23.7 0.55 9.4 42.5 23.8 0.56 9.6 41.6 23.3 0.56 9.8 40.5 23.1 0.57 10.2

INDOOR INDOOR -5.0 0.0 5.0 10.0 15.0

PRH-10YA-L

PRH-10YA

OUTDOOR DB ˚C

PRH-10YA AIR VOLUME CMM 90 100 110 120 L/S 1,500 1,660 1,830 2,000

COOLING CAPACITY 0.987 1.0 1.033 1.066 TOTAL INPUT 0.995 1.0 1.026 1.052

PR-10YC

Cooling Capacity (Nominal Air Flow)

OPERATION

PRH-10YA-L

PR-10YC

RANGE

Page 17 of the Mitsubishi Electronics 8 user manual — PRH-15YA-L
Page 17 · click to enlarge
Page 17

DB ˚C WB ˚C Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW

15 44.5 32.0 0.72 13.9 43.3 31.2 0.72 14.5 42.0 30.7 0.73 15.2 40.8 30.2 0.74 15.9 39.5 29.6 0.75 16.6 37.8 29.1 0.77 17.5

20 16 45.7 29.2 0.64 14.0 44.5 28.5 0.64 14.7 43.2 28.1 0.65 15.4 42.0 27.7 0.66 16.1 40.7 27.3 0.67 16.9 39.0 26.5 0.68 17.8

17 47.2 26.0 0.55 14.1 46.0 25.3 0.55 14.9 44.7 25.0 0.56 15.6 43.3 24.7 0.57 16.3 41.9 23.9 0.57 17.1 40.1 23.3 0.58 18.1

15 44.5 37.8 0.85 13.9 43.3 37.2 0.86 14.5 42.0 36.5 0.87 15.2 40.8 35.9 0.88 15.9 39.5 35.2 0.89 16.6 37.8 34.4 0.91 17.5

16 45.7 34.7 0.76 14.0 44.5 34.3 0.77 14.7 43.2 33.7 0.78 15.4 42.0 33.2 0.79 16.1 40.7 32.6 0.80 16.9 39.0 32.0 0.82 17.8

22 17 47.2 31.6 0.67 14.1 46.0 31.3 0.68 14.9 44.7 30.8 0.69 15.6 43.3 30.3 0.70 16.3 41.9 29.7 0.71 17.1 40.1 28.9 0.72 18.1

18 48.9 28.9 0.59 14.3 47.6 28.1 0.59 15.0 46.2 27.7 0.60 15.8 44.8 27.3 0.61 16.6 43.2 26.8 0.62 17.4 41.2 26.0 0.63 18.4

19 50.5 26.3 0.52 14.5 49.2 25.6 0.52 15.2 47.8 25.3 0.53 16.0 46.3 24.5 0.53 16.8 44.7 24.1 0.54 17.7 42.6 23.4 0.55 18.7

16 45.7 40.2 0.88 14.0 44.5 39.6 0.89 14.7 43.2 39.3 0.91 15.4 42.0 39.1 0.93 16.1 40.7 38.7 0.95 16.9 39.0 37.8 0.97 17.8

17 47.2 37.3 0.79 14.1 46.0 36.8 0.80 14.9 44.7 36.2 0.81 15.6 43.3 35.9 0.83 16.3 41.9 35.6 0.85 17.1 40.1 34.9 0.87 18.1

24 18 48.9 34.7 0.71 14.3 47.6 34.3 0.72 15.0 46.2 33.7 0.73 15.8 44.8 33.2 0.74 16.6 43.2 32.4 0.75 17.4 41.2 31.7 0.77 18.4

19 50.5 31.8 0.63 14.5 49.2 31.0 0.63 15.2 47.8 30.6 0.64 16.0 46.3 30.1 0.65 16.8 44.7 29.5 0.66 17.7 42.6 28.5 0.67 18.7

20 52.1 28.7 0.55 14.6 50.7 27.9 0.55 15.4 49.3 27.6 0.56 16.2 47.7 27.2 0.57 17.0 46.1 26.7 0.58 17.9 44.1 26.0 0.59 19.0

21 53.9 26.4 0.49 14.8 52.3 25.6 0.49 15.6 50.8 25.4 0.50 16.4 49.2 24.6 0.50 17.2 47.6 24.3 0.51 18.2 45.5 23.2 0.51 19.3

18 48.9 40.6 0.83 14.3 47.6 40.0 0.84 15.0 46.2 39.7 0.86 15.8 44.8 39.0 0.87 16.6 43.2 38.4 0.89 17.4 41.2 37.1 0.90 18.4

19 50.5 37.4 0.74 14.5 49.2 36.9 0.75 15.2 47.8 36.3 0.76 16.0 46.3 35.7 0.77 16.8 44.7 34.9 0.78 17.7 42.6 34.1 0.80 18.7

26 20 52.1 34.4 0.66 14.6 50.7 33.5 0.66 15.4 49.3 33.0 0.67 16.2 47.7 32.4 0.68 17.0 46.1 31.8 0.69 17.9 44.1 31.3 0.71 19.0

21 53.9 31.8 0.59 14.8 52.3 30.9 0.59 15.6 50.8 30.5 0.60 16.4 49.2 30.0 0.61 17.2 47.6 29.5 0.62 18.2 45.5 28.7 0.63 19.3

22 55.7 29.0 0.52 15.0 54.0 28.1 0.52 15.8 52.4 27.8 0.53 16.6 50.7 26.9 0.53 17.5 49.0 26.5 0.54 18.4 47.0 25.9 0.55 19.6

23 57.3 25.8 0.45 15.1 55.7 25.1 0.45 16.0 54.0 24.3 0.45 16.8 52.3 24.1 0.46 17.7 50.5 23.2 0.46 18.6 48.4 22.7 0.47 19.8

19 50.5 43.4 0.86 14.5 49.2 42.8 0.87 15.2 47.8 42.1 0.88 16.0 46.3 41.2 0.89 16.8 44.7 40.7 0.91 17.7 42.6 39.6 0.93 18.7

20 52.1 40.1 0.77 14.6 50.7 39.5 0.78 15.4 49.3 38.9 0.79 16.2 47.7 38.2 0.80 17.0 46.1 37.3 0.81 17.9 44.1 36.6 0.83 19.0

28 21 53.9 37.2 0.69 14.8 52.3 36.6 0.70 15.6 50.8 36.1 0.71 16.4 49.2 35.4 0.72 17.2 47.6 34.7 0.73 18.2 45.5 34.1 0.75 19.3

22 55.7 34.5 0.62 15.0 54.0 34.0 0.63 15.8 52.4 33.5 0.64 16.6 50.7 32.4 0.64 17.5 49.0 31.9 0.65 18.4 47.0 31.0 0.66 19.6

23 57.3 31.5 0.55 15.1 55.7 31.2 0.56 16.0 54.0 30.2 0.56 16.8 52.3 29.8 0.57 17.7 50.5 28.8 0.57 18.6 48.4 28.1 0.58 19.8

24 59.0 28.3 0.48 15.3 57.4 28.1 0.49 16.2 55.6 27.2 0.49 17.1 53.9 27.0 0.50 18.0 52.0 26.0 0.50 18.9 49.8 25.4 0.51 20.0

20 52.1 45.8 0.88 14.6 50.7 45.1 0.89 15.4 49.3 44.4 0.90 16.2 47.7 43.9 0.92 17.0 46.1 43.3 0.94 17.9 44.1 41.9 0.95 19.0

21 53.9 43.1 0.80 14.8 52.3 42.4 0.81 15.6 50.8 41.7 0.82 16.4 49.2 41.3 0.84 17.2 47.6 40.9 0.86 18.2 45.5 40.0 0.88 19.3

30 22 55.7 40.7 0.73 15.0 54.0 39.4 0.73 15.8 52.4 38.8 0.74 16.6 50.7 38.0 0.75 17.5 49.0 37.2 0.76 18.4 47.0 36.7 0.78 19.6

23 57.3 37.2 0.65 15.1 55.7 36.2 0.65 16.0 54.0 35.6 0.66 16.8 52.3 35.0 0.67 17.7 50.5 34.3 0.68 18.6 48.4 33.9 0.70 19.8

24 59.0 33.6 0.57 15.3 57.4 32.7 0.57 16.2 55.6 32.2 0.58 17.1 53.9 31.8 0.59 18.0 52.0 31.2 0.60 18.9 49.8 30.9 0.62 20.0

INDOOR INDOOR 20.0 25.0 30.0 35.0 40.0 46.0

Cooling Capacity (Nominal Air Flow): PR-15YC, PRH-15YA, PRH-15YA-L

PRH-15YA-L

OUTDOOR DB ˚C

PRH-15YA

PR-15YC

AIR VOLUME CMM 120 130 140 150 160 170 180

L/S 2,000 2,170 2,330 2,500 2,670 2,830 3,000

COOLING CAPACITY 0.944 0.955 0.966 0.978 0.981 1.0 1.011

TOTAL INPUT 0.980 0.984 0.988 0.992 0.996 1.0 1.005

Factor for Various Air Flow

OPERATION

PRH-15YA-L

RANGE

PRH-15YA

PR-15YC

Page 18 of the Mitsubishi Electronics 8 user manual — PRH-15YA-L
Page 18 · click to enlarge
Page 18

(Nominal Air Flow): PPRH-15YA, PRH-15YA-L

INDOOR -10.0 -5.0 0.0 DB ˚C Q kW T/I kW Q kW T/I kW Q kW T/I kW

DB ˚C Q kW T/I kW Q kW T/I kW Q kW T/I kW

L/S 2,000 2,170 2,330 2,500 2,670 2,830 3,000

HEATING CAPACITY 0.976 0.981 0.986 0.990 0.995 1.0 1.004

TOTAL INPUT 1.070 1.056 1.042 1.028 1.014 1.0 0.991

PRH-15YA

AIR VOLUME CMM 120 130 140 150 160 170 180

INDOOR 5.0 10.0 15.0

PRH-15YA-L

OUTDOOR WB ˚C

PRH-15YA-L

OUTDOOR WB ˚C

* QHEATING CAPACITY T/I : TOTAL INPUT

PRH-15YA

Factor for Various Air Flow Factor for Various Air Flow

Heating Capacity

15 31.0

15 45.4

OPERATION

OPERATION

RANGE

RANGE

DB ˚C WB ˚C Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW

15 47.6 33.8 0.71 12.4 47.2 33.5 0.71 12.5 46.8 33.2 0.71 12.7 46.2 33.3 0.72 13.0 45.4 32.7 0.72 13.4

20 16 49.0 29.9 0.61 12.5 48.6 30.1 0.62 12.6 48.1 29.8 0.62 12.8 47.4 29.9 0.63 13.1 46.6 29.4 0.63 13.5

17 50.9 27.0 0.53 12.6 50.5 26.8 0.53 12.7 49.9 26.4 0.53 12.9 49.2 27.1 0.55 13.2 48.3 26.6 0.55 13.6

15 47.6 39.5 0.83 12.4 47.2 39.2 0.83 12.5 46.8 38.8 0.83 12.7 46.2 38.8 0.84 13.0 45.4 38.1 0.84 13.4

16 49.0 36.3 0.74 12.5 48.6 36.0 0.74 12.6 48.1 35.6 0.74 12.8 47.4 35.6 0.75 13.1 46.6 35.0 0.75 13.5

22 17 50.9 33.6 0.66 12.6 50.5 33.3 0.66 12.7 49.9 32.9 0.66 12.9 49.2 33.0 0.67 13.2 48.3 32.4 0.67 13.6

18 52.7 30.6 0.58 12.7 52.3 30.3 0.58 12.8 51.7 30.0 0.58 13.0 51.0 30.1 0.59 13.3 50.0 29.5 0.59 13.7

19 54.7 27.9 0.51 12.8 54.2 27.6 0.51 12.9 53.6 27.3 0.51 13.1 52.8 27.5 0.52 13.4 51.7 26.9 0.52 13.8

16 49.0 42.1 0.86 12.5 48.6 42.3 0.87 12.6 48.1 41.8 0.87 12.8 47.4 41.7 0.88 13.1 46.6 41.0 0.88 13.5

17 50.9 39.7 0.78 12.6 50.5 39.4 0.78 12.7 49.9 38.9 0.78 12.9 49.2 38.9 0.79 13.2 48.3 38.2 0.79 13.6

24 18 52.7 36.9 0.70 12.7 52.3 36.6 0.70 12.8 51.7 36.2 0.70 13.0 51.0 36.2 0.71 13.3 50.0 35.5 0.71 13.7

19 54.7 33.4 0.61 12.8 54.2 33.1 0.61 12.9 53.6 32.7 0.61 13.1 52.8 32.7 0.62 13.4 51.7 32.1 0.62 13.8

20 56.7 30.6 0.54 12.9 56.2 30.3 0.54 13.0 55.5 30.0 0.54 13.2 54.6 30.0 0.55 13.6 53.5 29.4 0.55 14.0

21 58.6 27.5 0.47 13.0 58.0 27.3 0.47 13.1 57.3 26.9 0.47 13.3 56.3 27.0 0.48 13.7 55.2 26.5 0.48 14.1

18 52.7 42.2 0.80 12.7 52.3 41.8 0.80 12.8 51.7 41.9 0.81 13.0 51.0 41.3 0.81 13.3 50.0 41.0 0.82 13.7

19 54.7 38.8 0.71 12.8 54.2 38.5 0.71 12.9 53.6 38.6 0.72 13.1 52.8 38.0 0.72 13.4 51.7 37.7 0.73 13.8

26 20 56.7 36.3 0.64 12.9 56.2 36.0 0.64 13.0 55.5 35.5 0.64 13.2 54.6 35.5 0.65 13.6 53.5 34.8 0.65 14.0

21 58.6 33.4 0.57 13.0 58.0 33.1 0.57 13.1 57.3 32.7 0.57 13.3 56.3 32.7 0.58 13.7 55.2 32.0 0.58 14.1

22 60.3 30.2 0.50 13.1 59.9 30.0 0.50 13.2 59.1 29.6 0.50 13.4 58.1 29.6 0.51 13.8 57.0 29.1 0.51 14.3

23 62.4 27.5 0.44 13.2 61.8 27.2 0.44 13.3 61.0 26.8 0.44 13.5 60.0 27.0 0.45 13.9 58.8 26.5 0.45 14.4

19 54.7 44.9 0.82 12.8 54.2 44.4 0.82 12.9 53.6 44.5 0.83 13.1 52.8 44.4 0.84 13.4 51.7 43.9 0.85 13.8

20 56.7 42.0 0.74 12.9 56.2 41.6 0.74 13.0 55.5 41.6 0.75 13.2 54.6 41.0 0.75 13.6 53.5 40.7 0.76 14.0

28 21 58.6 39.3 0.67 13.0 58.0 38.9 0.67 13.1 57.3 39.0 0.68 13.3 56.3 38.3 0.68 13.7 55.2 38.1 0.69 14.1

22 60.3 36.2 0.60 13.1 59.9 35.9 0.60 13.2 59.1 36.1 0.61 13.4 58.1 35.4 0.61 13.8 57.0 35.3 0.62 14.3

23 62.4 33.1 0.53 13.2 61.8 32.8 0.53 13.3 61.0 32.9 0.54 13.5 60.0 32.4 0.54 13.9 58.8 32.3 0.55 14.4

24 64.3 30.2 0.47 13.3 63.6 29.9 0.47 13.4 62.8 29.5 0.47 13.7 61.8 29.7 0.48 14.1 60.5 29.0 0.48 14.6

20 56.7 47.6 0.84 12.9 56.2 47.8 0.85 13.0 55.5 47.2 0.85 13.2 54.6 47.0 0.86 13.6 53.5 46.5 0.87 14.0

21 58.6 44.5 0.76 13.0 58.0 44.7 0.77 13.1 57.3 44.1 0.77 13.3 56.3 43.9 0.78 13.7 55.2 43.6 0.79 14.1

30 22 60.3 41.6 0.69 13.1 59.9 41.3 0.69 13.2 59.1 41.4 0.70 13.4 58.1 41.3 0.71 13.8 57.0 41.0 0.72 14.3

23 62.4 38.7 0.62 13.2 61.8 38.3 0.62 13.3 61.0 37.8 0.62 13.5 60.0 37.8 0.63 13.9 58.8 37.6 0.64 14.4

24 64.3 36.0 0.56 13.3 63.6 35.6 0.56 13.4 62.8 35.2 0.56 13.7 61.8 35.2 0.57 14.1 60.5 34.5 0.57 14.6

PRH-15YA-L

PRH-15YA

(Use for low ambient temp. parts): PR-15YC, PRH-15YA, PRH-15YA-L

INDOOR INDOOR -5.0 0.0 5.0 10.0 15.0

PRH-15YA-L

PRH-15YA

OUTDOOR DB ˚C

AIR VOLUME CMM 120 130 140 150 160 170 180

L/S 2,000 2,170 2,330 2,500 2,670 2,830 3,000

COOLING CAPACITY 0.944 0.955 0.966 0.978 0.981 1.0 1.011

TOTAL INPUT 0.980 0.984 0.988 0.992 0.996 1.0 1.005

PR-15YC

Cooling Capacity (Nominal Air Flow)

OPERATION

PRH-15YA-L

RANGE

PR-15YC

PRH-15YA

Page 19 of the Mitsubishi Electronics 8 user manual — PRH-20YA
Page 19 · click to enlarge
Page 19

DB ˚C WB ˚C Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW

15 59.3 42.7 0.72 18.7 57.4 41.9 0.73 19.5 55.4 40.4 0.73 20.3 53.4 39.5 0.74 21.3 51.4 38.6 0.75 22.3 48.8 37.6 0.77 23.6

20 16 61.3 39.2 0.64 19.0 59.5 38.1 0.64 19.8 57.6 37.4 0.65 20.7 55.5 36.1 0.65 21.7 53.2 35.1 0.66 22.7 50.4 34.3 0.68 24.0

17 63.2 34.8 0.55 19.1 61.2 33.7 0.55 20.0 59.2 33.2 0.56 21.0 57.0 31.9 0.56 22.0 54.8 31.2 0.57 23.1 51.9 30.1 0.58 24.5

15 59.3 50.4 0.85 18.7 57.4 49.4 0.86 19.5 55.4 48.2 0.87 20.3 53.4 47.0 0.88 21.3 51.4 46.3 0.90 22.3 48.8 44.9 0.92 23.6

16 61.3 46.6 0.76 19.0 59.5 45.8 0.77 19.8 57.6 44.9 0.78 20.7 55.5 43.8 0.79 21.7 53.2 43.1 0.81 22.7 50.4 41.8 0.83 24.0

22 17 63.2 43.0 0.68 19.1 61.2 41.6 0.68 20.0 59.2 40.8 0.69 21.0 57.0 39.9 0.70 22.0 54.8 38.9 0.71 23.1 51.9 37.9 0.73 24.5

18 65.0 39.0 0.60 19.3 63.0 37.8 0.60 20.3 60.9 37.1 0.61 21.3 58.7 35.8 0.61 22.4 56.4 35.0 0.62 23.5 53.4 33.6 0.63 24.9

19 67.0 34.8 0.52 19.5 64.9 34.4 0.53 20.5 62.7 33.2 0.53 21.6 60.8 32.2 0.53 22.7 58.0 31.3 0.54 23.9 54.9 29.6 0.54 25.3

16 61.3 54.6 0.89 19.0 59.5 53.6 0.90 19.8 57.6 53.0 0.92 20.7 55.5 51.6 0.93 21.7 53.2 50.5 0.95 22.7 50.4 49.4 0.98 24.0

17 63.2 50.6 0.80 19.1 61.2 49.6 0.81 20.0 59.2 48.5 0.82 21.0 57.0 47.3 0.83 22.0 54.8 46.6 0.85 23.1 51.9 45.7 0.88 24.5

24 18 65.0 46.2 0.71 19.3 63.0 45.4 0.72 20.3 60.9 44.5 0.73 21.3 58.7 43.4 0.74 22.4 56.4 42.3 0.75 23.5 53.4 41.7 0.78 24.9

19 67.0 42.2 0.63 19.5 64.9 41.5 0.64 20.5 62.7 40.8 0.65 21.6 60.8 40.1 0.66 22.7 58.0 38.9 0.67 23.9 54.9 37.3 0.68 25.3

20 69.0 38.0 0.55 19.8 66.8 37.4 0.56 20.8 64.6 36.8 0.57 21.9 62.2 35.5 0.57 23.1 59.7 34.6 0.58 24.3 56.5 33.3 0.59 25.7

21 71.2 34.2 0.48 20.0 68.9 33.8 0.49 21.2 66.6 32.6 0.49 22.3 64.0 32.0 0.50 23.5 61.4 31.3 0.51 24.7 58.2 30.3 0.52 26.2

18 65.0 54.0 0.83 19.3 63.0 52.9 0.84 20.3 60.9 51.8 0.85 21.3 58.7 51.1 0.87 22.4 56.4 50.2 0.89 23.5 53.4 48.6 0.91 24.9

19 67.0 49.6 0.74 19.5 64.9 48.7 0.75 20.5 62.7 47.7 0.76 21.6 60.8 46.8 0.77 22.7 58.0 45.8 0.79 23.9 54.9 44.5 0.81 25.3

26 20 69.0 45.5 0.66 19.8 66.8 44.8 0.67 20.8 64.6 43.9 0.68 21.9 62.2 42.9 0.69 23.1 59.7 41.8 0.70 24.3 56.5 40.7 0.72 25.7

21 71.2 42.0 0.59 20.0 68.9 41.3 0.60 21.2 66.6 40.6 0.61 22.3 64.0 39.7 0.62 23.5 61.4 38.7 0.63 24.7 58.2 37.8 0.65 26.2

22 73.4 38.2 0.52 20.3 71.0 37.6 0.53 21.5 68.6 37.0 0.54 22.7 66.0 35.6 0.54 23.9 63.3 34.8 0.55 25.2 59.8 33.5 0.56 26.8

23 75.7 34.1 0.45 20.6 73.3 33.0 0.45 21.8 70.8 32.6 0.46 23.1 68.0 31.3 0.46 24.4 65.0 30.6 0.47 25.6 61.1 28.7 0.47 27.3

19 67.0 57.0 0.85 19.5 64.9 55.8 0.86 20.5 62.7 54.5 0.87 21.6 60.8 54.1 0.89 22.7 58.0 52.8 0.91 23.9 54.9 52.2 0.95 25.3

20 69.0 53.1 0.77 19.8 66.8 52.1 0.78 20.8 64.6 51.0 0.79 21.9 62.2 50.4 0.81 23.1 59.7 49.6 0.83 24.3 56.5 48.0 0.85 25.7

28 21 71.2 49.8 0.70 20.0 68.9 48.9 0.71 21.2 66.6 48.0 0.72 22.3 64.0 46.7 0.73 23.5 61.4 45.4 0.74 24.7 58.2 44.2 0.76 26.2

22 73.4 45.5 0.62 20.3 71.0 44.7 0.63 21.5 68.6 43.9 0.64 22.7 66.0 42.9 0.65 23.9 63.3 41.8 0.66 25.2 59.8 40.7 0.68 26.8

23 75.7 41.6 0.55 20.6 73.3 41.0 0.56 21.8 70.8 39.6 0.56 23.1 68.0 38.8 0.57 24.4 65.0 37.7 0.58 25.6 61.1 36.7 0.60 27.3

24 78.0 37.4 0.48 20.9 75.6 37.0 0.49 22.2 72.8 35.7 0.49 23.5 69.9 35.0 0.50 24.8 66.7 34.0 0.51 26.2 62.5 32.5 0.52 27.8

20 69.0 60.0 0.87 19.8 66.8 58.8 0.88 20.8 64.6 58.1 0.90 21.9 62.2 57.2 0.92 23.1 59.7 56.1 0.94 24.3 56.5 55.4 0.98 25.7

21 71.2 56.2 0.79 20.0 68.9 55.1 0.80 21.2 66.6 54.6 0.82 22.3 64.0 53.8 0.84 23.5 61.4 52.8 0.86 24.7 58.2 51.8 0.89 26.2

30 22 73.4 52.1 0.71 20.3 71.0 51.1 0.72 21.5 68.6 50.1 0.73 22.7 66.0 49.5 0.75 23.9 63.3 48.7 0.77 25.2 59.8 47.8 0.80 26.8

23 75.7 48.4 0.64 20.6 73.3 47.6 0.65 21.8 70.8 46.7 0.66 23.1 68.0 45.6 0.67 24.4 65.0 44.9 0.69 25.6 61.1 43.4 0.71 27.3

24 78.0 44.5 0.57 20.9 75.6 43.8 0.58 22.2 72.8 43.0 0.59 23.5 69.9 41.9 0.60 24.8 66.7 41.4 0.62 26.2 62.5 40.0 0.64 27.8

INDOOR INDOOR 20.0 25.0 30.0 35.0 40.0 46.0

Cooling Capacity (Nominal Air Flow): PR-20YC, PRH-20YA, PRH-20YA-L

PRH-20YA-L

OUTDOOR DB ˚C

PRH-20YA

PR-20YC

L/S 2,830 3,000 3,160 3,330 3,500 3,670

COOLING CAPACITY 0.980 0.990 1.0 1.008 1.017 1.025 TOTAL INPUT 0.990 0.995 1.0 1.003 1.007 1.010

PRH-20YA-L AIR VOLUME CMM 170 180 190 200 210 220

Factor for Various Air Flow

OPERATION

RANGE

PRH-20YA

PR-20YC

Page 20 of the Mitsubishi Electronics 8 user manual — PRH-20YA
Page 20 · click to enlarge
Page 20

(Nominal Air Flow): PRH-20YA, PRH-20YA-L

DB ˚C Q kW T/I kW Q kW T/I kW Q kW T/I kW

DB ˚C Q kW T/I kW Q kW T/I kW Q kW T/I kW

L/S 2,830 3,000 3,160 3,330 3,500 3,670

HEATING CAPACITY 0.990 0.995 1.0 1.003 1.007 1.010 TOTAL INPUT 1.025 1.013 1.0 0.993 0.987 0.980

PRH-20YA

PRH-20YA-L AIR VOLUME CMM 170 180 190 200 210 220

INDOOR -10.0 -5.0 0.0

INDOOR 5.0 10.0 15.0

OUTDOOR WB ˚C

OUTDOOR WB ˚C

PRH-20YA PRH-20YA-L

PRH-20YA-L

* QHEATING CAPACITY T/I : TOTAL INPUT

PRH-20YA

Factor for Various Air Flow Factor for Various Air Flow

Heating Capacity

15 41.2

15 60.9

RANGE OPERATION

OPERATION

RANGE

RANGE

DB ˚C WB ˚C Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW

15 64.2 44.9 0.70 16.7 63.9 44.7 0.70 16.9 63.2 44.2 0.70 17.2 62.3 43.6 0.70 17.6 61.0 43.3 0.71 18.1

20 16 66.2 41.0 0.62 16.9 65.9 40.9 0.62 17.1 65.2 40.4 0.62 17.4 64.2 40.4 0.63 17.8 62.8 39.6 0.63 18.3

17 68.4 37.6 0.55 17.0 68.0 37.4 0.55 17.2 67.2 37.0 0.55 17.5 66.2 36.4 0.55 17.9 64.7 35.6 0.55 18.4

15 64.2 52.6 0.82 16.7 63.9 52.4 0.82 16.9 63.2 52.5 0.83 17.2 62.3 51.7 0.83 17.6 61.0 51.2 0.84 18.1

16 66.2 49.0 0.74 16.9 65.9 48.8 0.74 17.1 65.2 48.9 0.75 17.4 64.2 48.2 0.75 17.8 62.8 47.7 0.76 18.3

22 17 68.4 45.1 0.66 17.0 68.0 44.9 0.66 17.2 67.2 44.4 0.66 17.5 66.2 44.4 0.67 17.9 64.7 43.3 0.67 18.4

18 70.6 40.9 0.58 17.2 70.0 40.6 0.58 17.3 69.3 40.2 0.58 17.6 68.2 40.2 0.59 18.0 66.6 39.3 0.59 18.6

19 72.9 37.2 0.51 17.4 72.4 36.9 0.51 17.5 71.4 36.4 0.51 17.8 70.2 36.5 0.52 18.2 68.7 35.7 0.52 18.8

16 66.2 56.3 0.85 16.9 65.9 56.0 0.85 17.1 65.2 56.1 0.86 17.4 64.2 55.9 0.87 17.8 62.8 55.3 0.88 18.3

17 68.4 52.7 0.77 17.0 68.0 52.4 0.77 17.2 67.2 52.4 0.78 17.5 66.2 51.6 0.78 17.9 64.7 51.1 0.79 18.4

24 18 70.6 48.7 0.69 17.2 70.0 48.3 0.69 17.3 69.3 48.5 0.70 17.6 68.2 47.7 0.70 18.0 66.6 47.3 0.71 18.6

19 72.9 44.5 0.61 17.4 72.4 44.2 0.61 17.5 71.4 44.3 0.62 17.8 70.2 43.5 0.62 18.2 68.7 43.3 0.63 18.8

20 75.3 40.7 0.54 17.5 74.8 40.4 0.54 17.6 73.7 39.8 0.54 17.9 72.6 39.9 0.55 18.4 71.0 39.1 0.55 19.0

21 77.8 36.6 0.47 17.7 77.2 36.3 0.47 17.8 76.0 35.7 0.47 18.1 75.0 36.0 0.48 18.6 73.3 35.2 0.48 19.2

18 70.6 55.8 0.79 17.2 70.0 55.3 0.79 17.3 69.3 55.4 0.80 17.6 68.2 55.2 0.81 18.0 66.6 54.6 0.82 18.6

19 72.9 51.8 0.71 17.4 72.4 51.4 0.71 17.5 71.4 51.4 0.72 17.8 70.2 50.5 0.72 18.2 68.7 50.2 0.73 18.8

26 20 75.3 48.2 0.64 17.5 74.8 47.9 0.64 17.6 73.7 47.9 0.65 17.9 72.6 47.2 0.65 18.4 71.0 46.9 0.66 19.0

21 77.8 44.3 0.57 17.7 77.2 44.0 0.57 17.8 76.0 44.1 0.58 18.1 75.0 43.5 0.58 18.6 73.3 43.2 0.59 19.2

22 80.4 40.2 0.50 17.8 79.6 39.8 0.50 17.9 78.8 40.2 0.51 18.3 77.4 39.5 0.51 18.8 75.6 39.3 0.52 19.5

23 83.0 36.5 0.44 18.0 82.4 36.3 0.44 18.1 81.2 35.7 0.44 18.5 79.8 35.9 0.45 19.0 78.0 35.1 0.45 19.7

19 72.9 59.0 0.81 17.4 72.4 58.6 0.81 17.5 71.4 58.5 0.82 17.8 70.2 58.3 0.83 18.2 68.7 57.7 0.84 18.8

20 75.3 55.0 0.73 17.5 74.8 54.6 0.73 17.6 73.7 54.5 0.74 17.9 72.6 54.5 0.75 18.4 71.0 54.0 0.76 19.0

28 21 77.8 51.3 0.66 17.7 77.2 51.0 0.66 17.8 76.0 50.9 0.67 18.1 75.0 51.0 0.68 18.6 73.3 50.6 0.69 19.2

22 80.4 47.4 0.59 17.8 79.6 47.8 0.60 17.9 78.8 48.1 0.61 18.3 77.4 47.2 0.61 18.8 75.6 46.9 0.62 19.5

23 83.0 44.0 0.53 18.0 82.4 43.7 0.53 18.1 81.2 43.8 0.54 18.5 79.8 43.1 0.54 19.0 78.0 42.9 0.55 19.7

24 85.6 40.2 0.47 18.1 84.8 39.9 0.47 18.3 83.6 39.3 0.47 18.7 82.2 39.5 0.48 19.2 80.4 38.6 0.48 20.0

20 75.3 62.5 0.83 17.5 74.8 62.1 0.83 17.6 73.7 61.9 0.84 17.9 72.6 61.7 0.85 18.4 71.0 61.1 0.86 19.0

21 77.8 59.1 0.76 17.7 77.2 58.7 0.76 17.8 76.0 58.5 0.77 18.1 75.0 57.8 0.77 18.6 73.3 57.2 0.78 19.2

30 22 80.4 55.5 0.69 17.8 79.6 54.9 0.69 17.9 78.8 55.2 0.70 18.3 77.4 54.2 0.70 18.8 75.6 53.7 0.71 19.5

23 83.0 51.5 0.62 18.0 82.4 51.1 0.62 18.1 81.2 51.2 0.63 18.5 79.8 50.3 0.63 19.0 78.0 49.9 0.64 19.7

24 85.6 47.1 0.55 18.1 84.8 47.5 0.56 18.3 83.6 46.8 0.56 18.7 82.2 46.9 0.57 19.2 80.4 45.8 0.57 20.0

PRH-20YA

(Use for low ambient temp. parts): PR-20YC, PRH-20YA, PRH-20YA-L

INDOOR INDOOR -5.0 0.0 5.0 10.0 15.0

PRH-20YA-L

OUTDOOR DB ˚C

PRH-20YA-L AIR VOLUME CMM 170 180 190 200 210 220

L/S 2,830 3,000 3,160 3,330 3,500 3,670

COOLING CAPACITY 0.980 0.990 1.0 1.008 1.017 1.025 TOTAL INPUT 0.990 0.995 1.0 1.003 1.007 1.010

PR-20YC

Cooling Capacity (Nominal Air Flow)

OPERATION

PRH-20YA

PR-20YC

Page 21 of the Mitsubishi Electronics 8 user manual — 10 15 20 25 30
Page 21 · click to enlarge
Page 21

Operation range

Cooling PR-YC

Outdoor temp.(˚CDB)

temp.parts

10 15 20 25 30

Indoor temp.(˚CWB)

PRH-YA

Cooling Heating

Outdoor temp.(˚CWB)

Outdoor temp.(˚CDB)

temp.parts

10 15 20 25 30

15 10 30 25 20

Indoor temp.(˚CWB)

Indoor temp.(˚CDB)

Cooling Heating PRH-YA-L

Outdoor temp.(˚CWB)

Outdoor temp.(˚CDB)

Range for continuous operation

temp.parts

10 15 20 25 30

15 10 30 25 20

Indoor temp.(˚CWB)

Indoor temp.(˚CDB)

Show 20 more labels / short text on this page
continuous operation · Range for · Use for Low · Range for · continuous · operation · continuous operation · continuous operation · Range for · Range for · Use for Low · Range for · continuous · operation · continuous operation · Range for · Use for Low · Range for · continuous · operation
Page 22 of the Mitsubishi Electronics 8 user manual — INDOOR INDOOR 20.0 25.0 30.0 35.0 40.0 46.0
Page 22 · click to enlarge
Page 22
Mitsubishi Electronics 8 — INDOOR INDOOR 20.0 25.0 30.0 35.0 40.0 46.0 diagram (page 22)
Fig. 5

PULLEY SIZE mm 139.7 127 139.7 139.7 (MOTOR SIDE) inch 5.5 5 5.5 5.5

750 ( / s) (CMM) 45 830 50 1000 60

PULLEY SIZE mm 114.3 127 (MOTOR SIDE) inch 4.5 5.0 PULLEY SIZE mm 165.1 152.4 127 127 127

BELT SIZE inch B41 B39 B38 B35 B37 MOTOR kw 1.1 1.1 1.1 1.5 1.5

Page 23 of the Mitsubishi Electronics 8 user manual — Airflow
Page 23 · click to enlarge
Page 23

PR-10YC PRH-10YA PRH-10YA-L

Mitsubishi Electronics 8 — PR-10YC PRH-10YA PRH-10YA-L diagram (page 23)
Fig. 6

Operation range

Mitsubishi Electronics 8 — Operation range diagram (page 23)
Fig. 7 · Operation range

External static pressure (Pa)

(CMM) ( / s)

1830 1670 1500 2000

Airflow

Mitsubishi Electronics 8 — Airflow diagram (page 23)
Fig. 8 · Airflow
Mitsubishi Electronics 8 — Airflow diagram (page 23)
Fig. 9 · Airflow

FAN SPEED rpm 640 640 690 730 730 760 810 PULLEY SIZE mm 101.6 101.6 114.3 127 (MOTOR SIDE) inch 4.0 4.0 4.5 5.0

PULLEY SIZE mm 228.6 228.6 241.3 254 254 241.3 228.6

(FAN SIDE) inch 9.0 9.0 9.5 10.0 10.0 9.5 9.0

BELT SIZE inch B37 2 B37 2 B39 2 B41 2 B41 2 B40 2 B39 2

MOTOR kw 2.2

FAN SPEED rpm 760 810 810 850 890 890 910

PULLEY SIZE mm 127 139.7 139.7 127

(MOTOR SIDE) inch 5.0 5.5 5.5 5.0

PULLEY SIZE mm 241.3 228.6 228.6 215.9 228.6 228.6 203.2

(FAN SIDE) inch 9.5 9.0 9.0 8.5 9.0 9.0 8.0

BELT SIZE inch B40 2 B39 2 B39 2 B38 2 B39 2 B39 2 B37 2

MOTOR kw 2.2 3.0

FAN SPEED rpm 910 910 910 970 1000 970 1040

PULLEY SIZE mm 127 139.7 127 127

(MOTOR SIDE) inch 5.0 5.5 5.0 5.0

PULLEY SIZE mm 203.2 203.2 203.2 190.5 203.2 190.5 177.8

(FAN SIDE) inch 8.0 8.0 8.0 7.5 8.0 7.5 7.0

BELT SIZE inch B37 B37 B37 B36 B37 B36 B35

MOTOR kw 2.2 3.0 3.0 3.0

FAN SPEED rpm 1040 -

PULLEY SIZE mm 127 -

(MOTOR SIDE) inch 5.0 -

PULLEY SIZE mm 177.8 -

(FAN SIDE) inch 7.0 -

BELT SIZE inch B35 -

MOTOR kw 2.2 2.2 3.0 -

FAN SPEED rpm 1120 1140 1120 1120 - - -

PULLEY SIZE mm 127 139.7 127 127 - - -

(MOTOR SIDE) inch 5.0 5.5 5.0 5.0 - - -

PULLEY SIZE mm 165.1 177.8 165.1 165.1 - - -

(FAN SIDE) inch 6.5 7.0 6.5 6.5 - - -

BELT SIZE inch B34 B36 B34 B34 - - -

MOTOR kw 2.2 3.0 3.0 3.0 - - -

FAN SPEED rpm 1210 1230 1230 -

(CMM)

PULLEY SIZE mm 127 139.7 139.7 -

2330 2670 3000 2000

(MOTOR SIDE) inch 5.0 5.5 5.5 -

PULLEY SIZE mm 152.4 165.1 165.1 -

Airflow

(FAN SIDE) inch 6.0 6.5 6.5 -

BELT SIZE inch B33 B35 B35 -

MOTOR kw 3 3 3 -

Show 10 more labels / short text on this page
Airflow · External · static pressure · (Pa) · Airflow · External · static pressure · (Pa) · 180 160 140 · ( / s)
Page 24 of the Mitsubishi Electronics 8 user manual — Airflow
Page 24 · click to enlarge
Page 24
Mitsubishi Electronics 8 — INDOOR INDOOR 20.0 25.0 30.0 35.0 40.0 46.0 diagram (page 24)
Fig. 10

PR-20YC PRH-20YA PRH-20YA-L

FAN SPEED rpm 730 810 810 840 910 940

PULLEY SIZE mm 127 127 127 139.7 127 139.7 (MOTOR SIDE) inch 5.0 5.0 5.0 5.5 5.0 5.5 PULLEY SIZE mm 254 228.6 228.6 241.3 203.2 215.9

(FAN SIDE) inch 10.0 9.0 9.0 9.5 8.0 8.5

BELT SIZE inch B43 B41 B41 B42 B39 B41

Operation range

FAN SPEED rpm 850 910 910 910 1000 970

Mitsubishi Electronics 8 — Operation range diagram (page 24)
Fig. 11 · Operation range

PULLEY SIZE mm 127 139.7 127

(MOTOR SIDE) inch 5.0 5.5 5.0

PULLEY SIZE mm 215.9 203.2 190.5

(FAN SIDE) inch 8.5 8.0 7.5

BELT SIZE inch B40 B39 B39 B39 B40 B38

FAN SPEED rpm 940 1000 1040 1040 1040 -

PULLEY SIZE mm 139.7 139.7 127 127 127 -

(MOTOR SIDE) inch 5.5 5.5 5.0 5.0 5.0 -

PULLEY SIZE mm 215.9 203.2 177.8 177.8 177.8 -

(FAN SIDE) inch 8.5 8.0 7.0 7.0 7.0 -

External static pressure (Pa)

BELT SIZE inch B41 B40 B37 B37 B37 - MOTOR kw 3.0 3.0 4.0 4.0 4.0 -

FAN SPEED rpm 1040 1040 1060 1120 - -

PULLEY SIZE mm 127 127 139.7 127 - -

(MOTOR SIDE) inch 5.0 5.0 5.5 5.0 - -

PULLEY SIZE mm 177.8 177.8 190.5 165.1 - -

(FAN SIDE) inch 7.0 7 7.5 6.5 - -

BELT SIZE inch B37 B37 B39 B36 - -

FAN SPEED rpm 1140 1120 -

PULLEY SIZE mm 139.7 127 -

(MOTOR SIDE) inch 5.5 5.0 -

PULLEY SIZE mm 177.8 165.1 -

(FAN SIDE) inch 7.0 6.5 -

BELT SIZE inch B38 2 B36 2 -

FAN SPEED rpm 1230 -

PULLEY SIZE mm 139.7 -

(MOTOR SIDE) inch 5.5 -

PULLEY SIZE mm 165.1 -

180 200 220 170

(FAN SIDE) inch 6.5 -

2830 3670 3330 3000

BELT SIZE inch B37 -

Airflow

Airflow

Page 25 of the Mitsubishi Electronics 8 user manual — AC
Page 25 · click to enlarge
Page 25

Pulley outside dimensions are shown below: (Unit : mm) (1) Shape of belt groove

Mitsubishi Electronics 8 — INDOOR INDOOR 20.0 25.0 30.0 35.0 40.0 46.0 diagram (page 25)
Fig. 12

Sectional plan of V-belt

Mitsubishi Electronics 8 — Sectional plan of V-belt diagram (page 25)
Fig. 13 · Sectional plan of V-belt

16.5mm

L0 W K K0 e f r1 r2 r3

11.0mm

12.5 5.5 9.5 19.0 12.5 0.2~0.5 0.5~1.0 1~2 11

(2) Shape of motor pulley boss (Unit : mm)

PR-5 10 PRH-5 10 Pulley for blower & motor

Mitsubishi Electronics 8 — (2) Shape of motor pulley boss (Unit : mm) diagram (page 25)
Fig. 14 · (2) Shape of motor pulley boss (Unit : mm)
Mitsubishi Electronics 8 — (2) Shape of motor pulley boss (Unit : mm) diagram (page 25)
Fig. 15 · (2) Shape of motor pulley boss (Unit : mm)

+0.009 - 0.004 +0.009 - 0.004 +0.009 - 0.004

0. 0.2 0 - 0.2 0 - 0.2

PR-8 20 PRH-8 20 PR-15,20 PRH-15, 20 Pulley for blower & motor

(3) Shape of motor (Unit : mm)

AC

Mitsubishi Electronics 8 — AC diagram (page 25)
Fig. 16

40˚ · B type

Page 26 of the Mitsubishi Electronics 8 user manual — NC-60
Page 26 · click to enlarge
Page 26

NC CURVES

PR-5YC PRH-5YA PRH-5YA-L

500 Hz 250 Hz 125 Hz 8000 Hz 4000 Hz 2000 Hz 1000 Hz 63 Hz CONDITION A scale

COOLING & HEATING 67 62db 43 45 50 57 61 62 63

NC-70

octave-band lebel db (0db=0.0002ubar)

NC-60

NC-50

NC-40

NC-30

NC-20

63 90 125 180 250 355 500 710 1000 1400 2000 2800 4000 5600 8000 10

PR-8YC PRH-8YA PRH-8YA-L

500 Hz 250 Hz 125 Hz 8000 Hz 4000 Hz 2000 Hz 1000 Hz 63 Hz CONDITION A scale

70 64db COOLING & HEATING 50 52 56 58 60 62 67

NC-70

octave-band lebel db (0db=0.0002ubar)

NC-60

NC-50

NC-40

NC-30

NC-20

63 90 125 180 250 355 500 710 1000 1400 2000 2800 4000 5600 8000 10

Show 8 more labels / short text on this page
50Hz · over · all · octave-band frequency [Hz] · 50Hz · over · all · octave-band frequency [Hz]
Page 27 of the Mitsubishi Electronics 8 user manual — NC-60
Page 27 · click to enlarge
Page 27

PR-10YC PRH-10YA PRH-10YA-L

500 Hz 250 Hz 125 Hz 8000 Hz 4000 Hz 2000 Hz 1000 Hz 63 Hz CONDITION A scale

COOLING & HEATING 71 44 49 57 59 61 63 69 64db

NC-70

octave-band lebel db (0db=0.0002ubar)

NC-60

NC-50

NC-40

NC-30

NC-20

63 90 125 180 250 355 500 710 1000 1400 2000 2800 4000 5600 8000 10

PR-15YC PRH-15YA PRH-15YA-L

500 Hz 250 Hz 125 Hz 8000 Hz 4000 Hz 2000 Hz 1000 Hz 63 Hz CONDITION A scale

68db COOLING & HEATING

48 51 59 62 65 68 76

NC-70

octave-band lebel db (0db=0.0002ubar)

NC-60

NC-50

NC-40

NC-30

NC-20

63 90 125 180 250 355 500 710 1000 1400 2000 2800 4000 5600 8000 10

Show 8 more labels / short text on this page
50Hz · over · all · octave-band frequency [Hz] · 50Hz · over · all · octave-band frequency [Hz]
Page 28 of the Mitsubishi Electronics 8 user manual — OUTLINE DIMENSIONS
Page 28 · click to enlarge
Page 28
Mitsubishi Electronics 8 — INDOOR INDOOR 20.0 25.0 30.0 35.0 40.0 46.0 diagram (page 28)
Fig. 17

A scale CONDITION 63 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz 125 Hz 250 Hz 500 Hz

10 8000 5600 4000 2800 2000 1400 1000 710 500 355 250 180 125 90 63 all over

OUTLINE DIMENSIONS

PR-5YC PRH-5YA PRH-5YA-L

16-ø3.5 HOLES

Mitsubishi Electronics 8 — OUTLINE DIMENSIONS diagram (page 28)
Fig. 18

25 1030 25

Page 29 of the Mitsubishi Electronics 8 user manual — PR-8,10YC PRH-8, 10YA PRH-8, 10YA-L
Page 29 · click to enlarge
Page 29

PR-8,10YC PRH-8, 10YA PRH-8, 10YA-L

20-ø3.5 HOLES

Mitsubishi Electronics 8 — PR-8,10YC PRH-8, 10YA PRH-8, 10YA-L diagram (page 29)
Fig. 19

60 60 150 150 200

39.5 200 39.5

Page 30 of the Mitsubishi Electronics 8 user manual — <23WA>
Page 30 · click to enlarge
Page 30

WIRING DIAGRAMS

PR-5, 8, 10YC (STANDARD)

CIRCUIT BREAKER

(FIELD SUPPLY)

PR5YC ···40A

PR8YC ···50A

PR-10YC ···60A

TB1 L1

MC INTERNAL PROTECTOR

RED

RED

RED

WHITE

WHITE

WHITE

BLACK

BLACK

BLACK

1 51F2

TB2

TB2

R1 R2 RED RED RED

MF2

N

BLUE

WHITE WHITE

S1 S2

WHITE

PE

BLACK BLACK BLACK

T1 T2

52F

RED 51F1

MF1 WHITE RED

F

INTERNAL PROTECTOR

F

(3.15A)

BLACK

11 TB3

TB4

SWITCH BOX (FIELD SUPPLY)

F

51F1

SW1

(3.15A)

GL

RL 51F2

FZ1

23 WA

SW2

63H

AC

AC

3 TB4

CZ

CZ

CH

52F

CZ

FZ0

FZ1

8,20YC ONLY

52C (3MIN) TM

30 CZ FZ0

30 CZ

FZ1

TM

30 CZ

12 TB3

TB3 12

MC MF1

Fan motor (in door)

MF2

Contactor (compressor) Fan motor (out door)

52F

TB1~4

CH

F

51F1, 2

Over current relay (fan I/D,O/D)

63H

TM

Timer (anti short cycle)

FZ0·1 CZ

Auxiliary relay (check) Auxiliary relay (compressor) Auxiliary relay (fan)

30CZ

<SW1>

Switch (off) Switch (on)

<SW2>

<RL> <GL>

Lamp (operation) Lamp (check)

<23WA>

Thermostat (room temp.)

Show 16 more labels / short text on this page
Power Supply · 3Phase · 380~415Volt · 50Herts · Tr · 220~ · Name Symbol · Compressor motor · Contactor (fan I/D) · Terminal block · Crankcase heater · Fuse Transformer · Tr · Over current relay(compressor) · High-pressure switch · Thermostat(freeze protection)
Page 31 of the Mitsubishi Electronics 8 user manual — Over current relay(compressor)
Page 31 · click to enlarge
Page 31

PR-15, 20YC (STANDARD)

CIRCUIT BREAKER (FIELD SUPPLY)

50Hertz 380~415Volt 3Phase Power supply

PR -15YC···100A PR -20YC···125A

MC1 INTERNAL PROTECTOR

TB1

51F2

R

R 11

TB2

N

S

S

PE

T

T

MF2

INTERNAL PROTECTOR MC2

INTERNAL PROTECTOR

51F3

R R

TB3

S S

T T

MF3

52F 51F1

INTERNAL PROTECTOR

MF1

F(3.15A) F

TB4 11

TB4 14

TB5

SWITCH BOX (FIELD SUPPLY)

FZ0

51F1

F

(3.15A)

CZ2-2 CZ1-2

RL2 RL1

SW1

23WA

GL

51F2

51F3

SW 2

H1 63

63 H2

220~ 240V

AC

AC 24V

CZ1 CZ1

CZ2

CZ2

2 3 4 5 6 8 7

TB5

CZ1

TM (3MIN)

TM (3MIN) C2

CH2

CZ2

FZ0

52 F

FZ1

FZ1

CH1

TM

FZ0

(2SEC)

CZ2 30 CZ1

CZ1-1

CZ2-1

FZ1

CZ2-1 CZ1-1

CZ1-2

30 CZ2-2

TB4 12

TB412

Caution, 1.To protect each Fan motors and Compressors from abnormal current, these Over current relays , are installed. Therefore,do not change factory set value of these Over current relays. 2.To protect the compressors from frequently "ON-OFF" ,timer is installed. Therefore,do not change factory set value of this timer. 3.This timer installed so that two compressors may never start at the same time. The unit stop if the set value of the timer is changed.

MC1·2

Compressor motor

52C1·2 MF2·3 MF1

Fan motor (in door)

Contactor (compressor) Fan motor (out door)

52F

Contactor (fan I/D)

TB1~5

Terminal block

CH1·2

Crankcase heater

F

Fuse Transformer

Over current relay(compressor)

51F1~3

Over current relay (fan I/D,O/D)

63H1·2

High-pressure switch

Thermostat(freeze protection) 26L1·2

TM 2 FZ0·1

Timer (anti short cycle) Timer

Auxiliary relay (check) Auxiliary relay (compressor) Auxiliary relay (fan)

30CZ1-1,2 CZ1·2

30CZ2-1,2 Auxiliary relay (check)

<SW1> <SW2>

Switch (off) Switch (on)

Lamp (power on) Lamp (check) <23WA> <RL1·2> <GL>

Thermostat (room temp.)

Show 34 more labels / short text on this page
Red Red Red · White White · Black Black · Black · Red Red · Red · Blue · White White · White · Black · Black · Black · Red · Red · Red · White White · Black · Black · Black · Red · Red · White · White · Black · Black · Red · Red · White · Black · Low High · Tr · Symbol · Name · 51C1·2 Tr
Page 32 of the Mitsubishi Electronics 8 user manual — Tr F CH
Page 32 · click to enlarge
Page 32

PR-5, 8, 10YC

(SPECIAL ORDER : K CONTROL)

CIRCUIT BREAKER

(FIELD SUPPLY)

MC

INTERNAL PROTECTOR

PR5YC ···40A

PR8YC ···50A

PR-10YC ···60A

TB1 L1

51F2

TB2

R

2 R

N

S

2 S

MF2

PE

T

2 T

52F 51F1

MF1

INTERNAL PROTECTOR

F(3.15A)

TB3 11

TH2

30 CZ

IB

51F1

FZ

51F2

D C B A TB4

63H

52F FZ CZ

TH5

CZ

FZ

CH

30 CZ

R/C

30 CZ

8,10YC ONLY

TB3 12 TB3 12

Name Symbol

52C MF2 MF1 MC

Contactor(compressor) Fan motor(outdoor) Fan motor(indoor) Compressor motor

52F

Contactor(fan I/D)

TB1~4

Terminal block

Tr F CH

Crankcase heater

Fuse Transformer

Over current relay(compressor)

51F1,2

Over current relay(fanI/D,O/D)

63H

High-pressure switch

FZ

Auxiliary relay(check) Auxiliary relay(compressor) Auxiliary relay(fan)

TH2 IB 30CZ CZ

Thermistor(pipe) Indoor board

Surge absorber circuit board DSA R/C TH5 Thermistor(room temp.) Remote controller

Show 20 more labels / short text on this page
3Phase Power supply · 380~415Volt 50Hertz · Red · Red · Red · White · White · Black · Black · Black · Red · Blue · White · Black · Red Red · Blue CN DSA · White · Black Black · Green/Yellow · Tr
Page 33 of the Mitsubishi Electronics 8 user manual — CH
Page 33 · click to enlarge
Page 33

PR-5, 8, 10YC

(SPECIAL ORDER : LOW TEMPERATURE)

CIRCUIT BREAKER

(FIELD SUPPLY)

MC

INTERNAL PROTECTOR

PR - 5YC ···40A

PR -10YC ···60A PR - 8YC ···50A

TB1

51C 52C

51F2

TB2

1 52F2

2 R TB2

N

R

R

2 R

S

S

S 2

2 S

PE

T

T 1

T 2

2 T

MF2

52F1 51F1

52F3

51F3

MF1

INTERNAL PROTECTOR

F(3.15A)

TB3 11

51F3

TB4

SWITCH BOX (FIELD SUPPLY)

F

51F1

(3.15A)

RL

SW1

FZ1

51F2

23WA

GL

26D3

SW2

63H

FZ

2 4 FZ 2 FZ

3 FZ

AC 220~

AC 24V

52 F1

6 5 4 3 2

26D4

52 F2

52 F4

TB4

CZ

FZ2

CZ

FZ0

52 F3

TM

CZ

(3MIN)

FZ3

FZ1

CZ 30 CH

30 CZ

FZ1

3 FZ

FZ0 FZ4

TM

30 CZ

8,10YC ONLY

TB3 12

Symbol

Name

52C MF2 MF1 MC

Compressor motor

Fan motor (indoor)

Contactor (compressor) Fan motor (outdoor)

52F1

Contactor (fan I/D)

TB1~4

Terminal block

CH

Crankcase heater

F

Fuse Transformer

51C Tr1·2

Over current relay(compressor)

51F1,2,3

Over current relay(fanI/D,O/D)

Thermostat(freeze protection) 26L High-pressure switch 63H

Timer (anti short cycle) TM

Auxiliary relay (check) Auxiliary relay (compressor) Auxiliary relay (fan) FZ0,1

Switch (on) <SW1> Switch (off) 30CZ CZ

<SW2>

<GL> <RL>

Lamp (operation) Lamp (check) Thermostat (room temp.) <23WA>

Contactor (fan O/D) Auxiliary relay (fan O/D) FZ2~4 52F2~4

Show 23 more labels / short text on this page
Power supply 3Phase · 50Hertz 380~415Volt · Red · Red · Red · White · White · Black · Black · Black · Red Red · Blue · Red · White · White · Black · White · Black Black · Red Red · White · Black Black · Tr1 52F4 · Tr2
Page 34 of the Mitsubishi Electronics 8 user manual — Over current relay(compressor)
Page 34 · click to enlarge
Page 34

PR-15, 20YC

(SPECIAL ORDER : LOW TEMPERATURE)

CIRCUIT BREAKER (FIELD SUPPLY)

50Hertz 380~415Volt 3Phase Power supply

PR -15YC···100A PR -20YC···125A

MC1 INTERNAL PROTECTOR

TB1

51F2

TB2

TB2

R

R

R 11

52F2

R

N

S

S

S

S

PE

T

T

T

T

MF2

51F4

INTERNAL PROTECTOR MC2

52F3

INTERNAL PROTECTOR

51F3

TB3

TB3

R

R

52F5

R

R

S

S

S

S

T

T

T

T

MF3

52F6

51F5

52F 51F1

INTERNAL PROTECTOR

MF1

F(3.15A) F

TB4 11

TB5

1 SWITCH BOX (FIELD SUPPLY)

FZ0

51F1

TB4

F

(3.15A)

CZ2-2 CZ1-2

23WA

RL2 RL1

SW1

51F4 51F5

GL

26D1 26D3

SW 2

51F2

51F3

FZ FZ FZ FZ FZ FZ FZ FZ

3 6 2 5 4 7 2 5

AC 220 ~ 240V

CZ2

H1 63

63 H2

AC 24V

CZ1 CZ1

CZ2

2 3 5 4 6 8 7

TB5

26D2 26D4

CZ1

TM (3MIN)

TM (3MIN) C2

FZ2 FZ5

52 F7 52 F2

52 F4

52 F5

CH2

CZ2

FZ0

52 F

52 F3

52 F6

FZ1

FZ1

FZ3 FZ6

CH1

TM

FZ FZ

FZ0

30 CZ1

(2SEC)

CZ1-1

CZ2-1

CZ2

FZ1

FZ4 FZ7

30 CZ2-2

TB4 12

CZ2-1 CZ1-1

CZ1-2

TB4 12

Caution, 1.To protect each Fan motors and Compressors from abnormal current,these Over current relays, are installed. Therefore,do not change factory set value of these Over current relays. 2.To protect the compressors from frequently "ON-OFF",timeris installed. Therefore,do not change factory set value of this timer. 3.This timerinstalled so that two compressors may never start at the same time. The unit stop if the set value of the timer is changed.

52C1·2 MF2·3 MF1 MC1·2

Compressor motor

Fan motor (indoor)

Contactor (compressor) Fan motor (outdoor)

52F1

Contactor (fan I/D)

TB1~5

Terminal block

CH1·2

Crankcase heater

F

Fuse Transformer

Over current relay(compressor)

51F1~5

Over current relay (fan I/D,O/D)

63H1·2

High-pressure switch

26L1·2

Thermostat(freeze protection) Timer (anti short cycle) Timer

TM

FZ0·1

Auxiliary relay (check) Auxiliary relay (compressor) Auxiliary relay (fan)

30CZ1-1, 2 CZ1·2

30CZ2-1, 2 Auxiliary relay (check)

<SW1> <SW2>

Switch (off) Switch (on)

<RL1·2> <GL>

Lamp (operation) Lamp (check)

<23WA>

Thermostat (room temp.)

26D1~4 Contactor (fan O/D) Auxiliary relay (fan O/D)

Thermostat (ambiemt temp.)

52F2~7 FZ2~7

Show 42 more labels / short text on this page
Red Red Red · White White · Black · Black Black · Red Red · Red · Red · Blue · White White · White · Black · Black · White · Black · Black · Red · Red · White White · Red · Black · Black · Black · Tr1 52F4 · Red · Red · White · Red · White · Black · White · Black · Black · Red · Red · White · Tr2 52F7 · Black · Low High · Tr · Symbol · Name · 51C1·2 Tr1~3
Page 35 of the Mitsubishi Electronics 8 user manual — Crankcase heater
Page 35 · click to enlarge
Page 35

PR-5, 8, 10YC

(SPECIAL ORDER : K CONTROL & LOW TEMPERATURE)

CIRCUIT BREAKER (FIELD SUPPLY)

50Hertz 380~415Volt 3Phase Power supply

PR - 5YC ···40A

PR -10YC ···60A PR - 8YC ···50A

MC INTERNAL PROTECTOR

TB1

51C 52C

51F2

TB2

2 R TB2

R

R

2 R 52F2

N

S

S

S 2

2 S

PE

MF2

T

T

T 2

2 T

52F1 51F1

52F3

51F3

DSA

CN

MF1

INTERNAL PROTECTOR

F(3.15A)

TB3 11

TH2

51F3

30 CZ

IB

51F1

FZ1

51F2

26D3

TB4 D C B A

FZ

4 FZ 2 FZ

3 FZ

63H

FZ1 CZ

52 F1

26D4

52 F2

52 F4

TH5

FZ2

CZ

52 F3

FZ1

FZ3

CH

30 CZ

3 FZ

R/C

30 CZ

FZ4

8,10YC ONLY

TB3 12

52C MF2 MF1 MC

Contactor(compressor) Fan motor(outdoor) Fan motor(indoor) Compressor motor

52F1

Contactor(fan I/D)

TB1~4

Terminal block

51C Tr1·2 F CH

Crankcase heater

Fuse Transformer

(compressor) Over current relay

51F1,2,3

Over current relay(fanI/D,O/D)

63H

High-pressure switch

FZ1

Auxiliary relay(check) Auxiliary relay(compressor) Auxiliary relay(fan)

TH2 IB 30CZ CZ

FZ2~4 Auxiliary relay(fan O/D) 52F2~4 Contactor(fan O/D) Thermistor(pipe) Indoor board

Thermistor(room temp) TH5

Remote controller R/C

Surge absorber circuit board DSA

Show 21 more labels / short text on this page
Red · Red Red · White · White · Black · Black · Black · Red Red Red · Blue · White White · White · Black Black Black · Red Red · Blue · White · Black · Black · Green/Yellow · Tr1 52F4 · Tr2 · Name Symbol
Page 36 of the Mitsubishi Electronics 8 user manual — <23WA>
Page 36 · click to enlarge
Page 36

PRH-5, 8, 10YA PRH-5, 8, 10YA-L (STANDARD)

CIRCUIT BREAKER

(FIELD SUPPLY)

PRH5YA, PRH5YA-L

···40A

PRH8YA, PRH8YA-L

···50A

PRH-10YA, PRH-10YA-L

···60A

TB1 L1

RED

RED

MC INTERNAL PROTECTOR

RED

WHITE

WHITE

WHITE

BLACK

BLACK

BLACK

TB2 X1

R1 R2 RED RED RED

3 2 1 51F2

TB2

N

BLUE

MF2

WHITE WHITE

S1 S2

WHITE

PE

BLACK BLACK BLACK

T1 T2

52F

RED 51F1

MF1 WHITE RED

F

F

BLACK

INTERNAL PROTECTOR

(3.15A)

11 TB3

TB4

SWITCH BOX (FIELD SUPPLY)

HZ

HZ

51F1

F

SW2

(3.15A)

SW1

HEAT COOL

GL

RL 51F2

FZ1

H C

63H

SW3

26 D2

23 WA

AC

AC

S4 21

3 TB4

2 4 6 7

CZ

CZ

CH

52F

D1 26 CZ

HZ

FZ0

FZ1

8,10YA,

52C (3MIN) TM

YA-L

30 CZ FZ0

30 CZ

ONLY

FZ1

TM

30 CZ

12 TB3

TB3 12

MC MF1

Fan motor (in door)

MF2

Contactor (compressor) Fan motor (out door)

52F

TB1~4

CH

F

51F1, 2

Over current relay (fan I/D,O/D)

63H

26D1·2

TM

Timer (anti short cycle)

21S4

FZ0·1 CZ

Auxiliary relay (check) Auxiliary relay (heater) Auxiliary relay (compressor) Auxiliary relay (fan)

HZ

30CZ

X1·2

<SW1>

Switch (operation mode) Switch (off) Switch (on)

<SW2>

<SW3>

<RL> <GL>

Lamp (operation) Lamp (check)

<23WA>

Thermostat (room temp.)

Show 19 more labels / short text on this page
Power Supply · 3Phase · 380~415Volt · 50Hertz · Tr · 220~ · Name Symbol · Compressor motor · Contactor (fan I/D) · Terminal block · Crankcase heater · Fuse Transformer · Tr · Over current relay(compressor) · High-pressure switch · Thermostat(freeze protection) · Thermostat (defrost) · 4-Way valve · Auxiliary relay (defrost)
Page 37 of the Mitsubishi Electronics 8 user manual — Over current relay(compressor)
Page 37 · click to enlarge
Page 37

PRH-15, 20YA PRH-15, 20YA-L (STANDARD)

CIRCUIT BREAKER (FIELD SUPPLY)

PRH-15YA PRH-15YA-L ···100A

50Herts 380~415Volt 3Phase Power supply

PRH-20YA PRH-20YA-L

···125A

MC1 INTERNAL PROTECTOR

TB1

51F2

TB2

R

R

N

S

S

MF2

T

T

INTERNAL PROTECTOR MC2

INTERNAL PROTECTOR

51F3

TB3

R R

S S

MF3

T T

52F 51F1

INTERNAL PROTECTOR

MF1

F(3.15A) F

TB4 11

TB5

SWITCH BOX (FIELD SUPPLY)

FZ0

51F1 HZ HZ

F

SW2 SW1

(3.15A)

CZ2-2 CZ1-2

HEAT COOL

RL2 RL1

TB4 13

H C H C

GL

51F2

51F3

SW3

X1 X2 X2

AC 220~ 240V

23WA

H1 63

63 H2

AC 24V

CZ1 CZ1

CZ2

CZ2

TB5

2 3 4 5 6 8 9 7

21 S41

26 D4

26 D3

TM (3MIN)

TM (3MIN) C2

CZ1

HZ

21 S42

FZ0

CH2

CZ2

52 F

D1 26

26 D2 X4

FZ1

FZ1

CH1

TM

FZ0

30 CZ1

(2SEC)

CZ2

CZ1-1

CZ2-1

FZ1

30 CZ2-2

TB4 12 TB4 12

CZ2-1 CZ1-1

CZ1-2

Caution, 1.To protect each Fan motors and Compressors from abnormal current, these Over current relays,are installed. Therefore,do not change factory set value of these Over current relays. 2.To protect the compressors from frequently "ON-OFF" ,timeris installed. Therefore,do not change factory set value of this timer. 3.This timerinstalled so that two compressors may never start at the same time. The unit stop if the set value of the timer is changed.

MC1·2

Compressor motor

52C1·2 MF2·3 MF1

Fan motor (in door)

Contactor (compressor) Fan motor (out door)

52F

Contactor (fan I/D)

TB1~5

Terminal block

CH1·2

Crankcase heater

F

Fuse Transformer

Over current relay(compressor)

51F1~3

Over current relay (fan I/D,O/D)

63H1·2

High-pressure switch

Thermostat(freeze protection) 26L1·2

26D1~4

Thermostat (defrost)

TM 2

Timer (anti short cycle) Timer

21S41·42

4-Way valve

FZ0·1

Auxiliary relay (check) Auxiliary relay (heater) Auxiliary relay (compressor) Auxiliary relay (fan)

30CZ1-1,2 HZ CZ1·2

30CZ2-1,2 Auxiliary relay (check)

X1~4

Auxiliary relay (defrost)

<SW1> <SW2> <SW3>

Switch (operation mode) Switch (off) Switch (on)

Lamp (operation) Lamp (check) <23WA> <RL1·2> <GL>

Thermostat (room temp.)

Show 34 more labels / short text on this page
Red Red Red · White White · Black Black · Black · Red Red · Red · Blue · White White · White · Black · Black · Black · Red · Red · White White · Red · Black · Black · Black · Red · Red · White · White · Black · Black · Red · Red · White · Black · Tr · Low High · Symbol · Name · 51C1·2 Tr
Page 38 of the Mitsubishi Electronics 8 user manual — Tr F CH
Page 38 · click to enlarge
Page 38

PRH-5, 8, 10YA PRH-5, 8, 10YA-L

(SPECIAL ORDER : K CONTROL)

CIRCUIT BREAKER (FIELD SUPPLY)

PRH5YA, PRH5YA-L ···40A

PRH8YA, PRH8YA-L···50A

MC

INTERNAL PROTECTOR

PRH-10YA, PRH-10YA-L···60A

TB1 L1

51F2

TB2

R

2 R

N

S

2 S

MF2

PE

T

2 T

52F 51F1

MF1

INTERNAL PROTECTOR

F(3.15A)

TB3 11

TH2

HZ

HZ

30 CZ

IB

51F1

FZ

51F2

63H

D C B A TB4

52F FZ CZ HZ

21 S4

CM

D2

TH5

26 D1 X2

CZ

FZ

CH

30 CZ

R/C

30 CZ

8,10YA,YA-L ONLY

TB3 12 TB3 12

Name Symbol

52C MF2 MF1 MC

Contactor(compressor) Fan motor(outdoor) Fan motor(indoor) Compressor motor

52F

Contactor(fan I/D)

TB1~4

Terminal block

Tr F CH

Crankcase heater

Fuse Transformer

Over current relay(compressor)

51F1,2

Over current relay(fanI/D,O/D)

63H

High-pressure switch

26D1·2

Thermostat(defrost)

21S4

4-Way valve

FZ

Auxiliary relay(check) Auxiliary relay(heater) Auxiliary relay(compressor) Auxiliary relay(fan)

30CZ HZ CZ

X1·2

Auxiliary relay(defrost)

TH2 IB

Thermistor(pipe) Indoor board

Surge absorber circuit board DSA R/C TH5 Thermistor(room temp.) Remote controller

Show 20 more labels / short text on this page
3Phase Power supply · 380~415Volt 50Herts · Red · Red · Red · White · White · Black · Black · Black · Red · Blue · White · Black · Red Red · Blue CN DSA · White · Black Black · Green/Yellow · Tr
Page 39 of the Mitsubishi Electronics 8 user manual — CH
Page 39 · click to enlarge
Page 39

PRH-5, 8, 10YA PRH-5, 8, 10YA-L (SPECIAL ORDER : LOW TEMPERATURE)

CIRCUIT BREAKER (FIELD SUPPLY)

PRH5YA, PRH5YA-L

···40A

MC

PRH8YA, PRH8YA-L

···50A

INTERNAL PROTECTOR

PRH-10YA, PRH-10YA-L

···60A

TB1

51C 52C

51F2

TB2

1 52F2

2 R TB2

R

R

2 R

N

S

S

S 2

2 S

MF2

PE

T

T 1

T 2

2 T

52F1 51F1

51F3

52F3

MF1

INTERNAL PROTECTOR

F(3.15A)

TB3 11

51F3

TB4

SWITCH BOX (FIELD SUPPLY)

HZ

HZ

F

(3.15A)

SW1

51F1

TB313

HEAT COOL

RL

SW2

FZ1

GL

51F2

H C

26D3

23WA

SW3

63H

FZ

2 4 FZ 2 FZ

3 FZ

AC 220~ 240V

AC 24V

21 S4

7 6 5 4 3 2

52 F1

D2

26D4

TB4

CZ

FZ2

52 F2

52 F4

CZ

HZ

26 D1 X2

52 F3

FZ0

CZ

(3MIN)

TM

FZ3

FZ1

CZ 30 CH

30 CZ

3 FZ

FZ1

FZ0

TM

FZ4

30 CZ

8,10YA, YA-L ONLY

TB3 12

Name

52C MF2 MF1 MC

Compressor motor

Fan motor (indoor)

Contactor (compressor) Fan motor (outdoor)

52F1

Contactor (fan I/D)

TB1~4

Terminal block

CH

Crankcase heater

F

Fuse Transformer

51C Tr1·2

Over current relay(compressor)

51F1,2,3

Over current relay(fanI/D,O/D)

High-pressure switch 63H

Thermostat(freeze protection) 26L Thermostat (defrost) 26D1~4

Timer (anti short cycle) TM

21S4

4-Way valve

FZ0,1

Auxiliary relay (check) Auxiliary relay (heater) Auxiliary relay (compressor) Auxiliary relay (fan)

30CZ HZ CZ

X1·2

Auxiliary relay (defrost)

Switch (on) <SW2> Switch (off) <SW1>

Switch (operatin mode)

<SW3>

<GL> <RL>

Lamp (operation) Lamp (check)

Thermostat (room temp.) <23WA>

Contactor (fan O/D) Auxiliary relay (fan O/D) FZ2~4 52F2~4

Show 24 more labels / short text on this page
Power supply 3Phase · 50Herts 380~415Volt · Red · Red · Red · White · White · Black · Black · Black · Red · Red Red · Blue · White · White · White · Black · Black Black · Red Red · White · Black Black · Tr1 52F4 · Tr2 · Symbol
Page 40 of the Mitsubishi Electronics 8 user manual — 52F2~7 FZ2~7
Page 40 · click to enlarge
Page 40

PRH-15, 20YA PRH-15, 20YA-L (SPECIAL ORDER : LOW TEMPERATURE)

CIRCUIT BREAKER (FIELD SUPPLY)

50Herts 380~415Volt 3Phase Power supply

PRH-15YA PRH-15YA-L

···100A

MC1 INTERNAL PROTECTOR

PRH-20YA PRH-20YA -L

···125A

TB1

51F2

TB2

TB2

R

R

52F2

R

R

N

S

S

S

S

PE

T

T

T

T

MF2

INTERNAL PROTECTOR MC2

51F4

52F3

INTERNAL PROTECTOR

51F3

R

TB3

R

52F5

R

TB3

R

S

S

S

S

MF3

T

T

T

T

52F6

51F5

52F 51F1

INTERNAL PROTECTOR

MF1

F(3.15A) F

TB4 11

TB5

SWITCH BOX (FIELD SUPPLY)

FZ0

51F1 HZ

HZ

TB4

F

(3.15A)

SW2 SW1

CZ2-2 CZ1-2

HEAT COOL

RL2 RL1

TB4 13

GL

51F4 51F5

H C H C

26D1 26D3

SW3

51F2

51F3

FZ FZ FZ FZ FZ FZ FZ FZ

23WA

H1 63

63 H2

X1 X2 X2

3 6 2 5 4 7 2 5

AC 220~ 240V

CZ1 CZ1

CZ2

AC 24V

CZ2

TB5

2 3 4 5 6 8 9 7

26 D4

21 S41

26 D3

26D2 26D4

TM (3MIN)

TM (3MIN) C2

FZ2 FZ5

52 F7 52 F2

52 F4

52 F5

CZ1

HZ

21 S42

CH2

CZ2

FZ0

26 D2 X4

52 F3

52 F6

52 F

D1 26

FZ1

FZ1

FZ3 FZ6

CH1

TM

FZ0

30 CZ1

(2SEC)

FZ FZ

CZ1-1

CZ2-1

CZ2

FZ1

FZ4 FZ7

CZ2-1 CZ1-1

CZ1-2

30 CZ2-2

TB4 12

TB4 12

Caution, 1.To protect each Fan motors and Compressors from abnormal current,these Over current relays, are installed. Therefore,do not change factory set value of these Over current relays. 2.To protect the compressors from frequently "ON-OFF",timeris installed. Therefore,do not change factory set value of this timer. 3.This timerinstalled so that two compressors may never start at the same time. The unit stop if the set value of the timer is changed.

52C1·2 MF2·3 MF1 MC1·2

Contactor (compressor) Fan motor (outdoor)

52F1

TB1~5

CH1·2

F

51F1~5

Over current relay (fan I/D,O/D)

63H1·2

26L1·2

26D1~4

TM

Timer (anti short cycle) Timer

21S41·42

FZ0·1

Auxiliary relay (check) Auxiliary relay (heater) Auxiliary relay (compressor) Auxiliary relay (fan)

30CZ1-1, 2 HZ CZ1·2

30CZ2-1, 2 Auxiliary relay (check)

X1~4

<SW1> <SW2> <SW3>

Switch (operation mode) Switch (off) Switch (on)

<RL1·2> <GL>

Lamp (operation) Lamp (check)

<23WA>

Thermostat (room temp.)

26D1~4 Contactor (fan O/D) Auxiliary relay (fan O/D)

Thermostat (ambiemt temp.)

52F2~7 FZ2~7

Show 54 more labels / short text on this page
Red Red Red · White White · Black · Black Black · Red Red · Red · Red · Blue · White White · White · White · Black · Black · Black · Black · Red · Red · Red · White White · Black · Black · Black · Tr1 52F4 · Red · Red · White · Red · White · White · Black · Black · Black · Red · Red · White · Tr2 52F7 · Black · Tr · Low High · Symbol · Name · Compressor motor · Fan motor (indoor) · Contactor (fan I/D) · Terminal block · Crankcase heater · Fuse Transformer · 51C1·2 Tr1~3 · Over current relay(compressor) · High-pressure switch · Thermostat(freeze protection) · Thermostat (defrost) · 4-Way valve · Auxiliary relay (defrost)
Page 41 of the Mitsubishi Electronics 8 user manual — TB1~4
Page 41 · click to enlarge
Page 41

PRH-5, 8, 10YA PRH-5, 8, 10YA-L

(SPECIAL ORDER : K CONTROL & LOW TEMPERATURE)

CIRCUIT BREAKER (FIELD SUPPLY)

PRH5YA, PRH5YA-L ···40A

50Hertz 380~415Volt 3Phase Power supply

PRH8YA, PRH8YA-L ···50A

MC INTERNAL PROTECTOR

PRH10YA PRH-10YA-L ···60A

TB1

51C 52C

51F2

TB2

2 R TB2

R

R

2 R 52F2

N

S

S

S 2

2 S

PE

T

T

T 2

2 T

MF2

52F1 51F1

52F3

51F3

DSA

MF1

CN

INTERNAL PROTECTOR

F(3.15A)

TB3 11

TH2

51F3

HZ

HZ

30 CZ

IB

51F1

TB3 13

FZ1

51F2

26D3 X1

TB4 D C B A

FZ

4 FZ 2 FZ

3 FZ

52 F1

63H

21 S4

CZ HZ

FZ1

D2

FZ2

26D4

52 F2

52 F4

TH5

26 D1 X2

52 F3

CZ

FZ1

FZ3

CH

30 CZ

3 FZ

R/C

30 CZ

FZ4

8,10YA,YA-L ONLY

TB3 12

Name Symbol

52C MF2 MF1 MC

Contactor(compressor) Fan motor(outdoor) Fan motor(indoor) Compressor motor

52F1

Contactor(fan I/D)

TB1~4

Terminal block

Crankcase heater

Fuse Transformer

(compressor) Over current relay

51F1,2,3

Over current relay(fanI/D,O/D)

26D1~4 63H

Thermostat(defrost) High-pressure switch

21S4

4-Way valve

FZ1

Auxiliary relay(check) Auxiliary relay(heater) Auxiliary relay(compressor) Auxiliary relay(fan)

30CZ HZ CZ

X1·2

Auxiliary relay(defrost)

TH2 IB

Thermistor(pipe) Indoor board

FZ2~4 Auxiliary relay(fan O/D) 52F2~4 Contactor(fan O/D)

Thermistor(room temp) TH5

Remote controller R/C

Surge absorber circuit board DSA

Show 21 more labels / short text on this page
Red · Red Red · White · White · Black · Black · Black · Blue · Red Red Red · White White · Black Black Black · White · Red Red · White · Blue · Black · Black · Green/Yellow · Tr1 52F4 · Tr2 · Tr1·2 F CH
Page 42 of the Mitsubishi Electronics 8 user manual — 30CZ ON (SELF HOLD)
Page 42 · click to enlarge
Page 42

ELECTRICAL OPERATION FLOW CHARTS

PR-5, 8, 10YC

START

POWER ON

CH ON

GL ON

30CZ ON (SELF HOLD)

SW2 ON?

NO

YES

FZ0,1 ON (SELF HOLD)

52F ON MF1 OPERATE

YES

NO

23WA ON?

YES

CZ ON

TM ON

NO

PASS THE 3 MIN.?

YES

52C ON MC OPERATE MF2 OPERATE

CH OFF

SAFETY DEVICE OFF?

NO

YES

30CZ OFF

52C OFF MC STOP MF2 STOP

RL ON

CH ON

SERVICE CALL

Page 43 of the Mitsubishi Electronics 8 user manual — START
Page 43 · click to enlarge
Page 43

PRH-5, 8, 10YA PRH-5, 8, 10YA-L

START

POWER ON

CH ON

GL ON

30CZ ON (SELF HOLD)

NO

SW3 ON?

YES

FZ0,1 ON (SELF HOLD)

52F ON MF1 OPERATE

SW1 COOL?

NO

HZ ON

YES

21S4 ON

NO

23WA ON?

NO

23WA ON?

YES

CZ ON

YES

CZ ON

TM ON

TM ON

NO

PASS THE 3 MIN.?

NO

PASS THE 3 MIN.?

YES

52C ON MC OPERATE MF2 OPERATE

YES

52C ON MC OPERATE MF2 OPERATE

CH OFF

CH OFF

SAFETY DEVICE OFF?

NO

NO

CONDENSING TEMP. -12˚C?

<=

YES

30CZ OFF

YES

26D1, 2 ON

52C OFF MC STOP MF2 STOP

X1 ON X2 ON (SELF HOLD)

RL ON

21S4 OFF MF2 STOP

CH ON

SERVICE CALL

NO

CONDENSING

TEMP. 6˚C?

<=

YES

26D1, 2 OFF

X1, 2 OFF

21S4 ON MF2 OPERATE

Page 44 of the Mitsubishi Electronics 8 user manual — START
Page 44 · click to enlarge
Page 44

PR-15, 20YC

START

POWER ON

CH1, 2 ON

GL ON

30CZ1, 30CZ2 ON (SELF HOLD)

NO

SW2 ON?

YES

FZ0, FZ1 ON (SELF HOLD)

52F ON MF1 OPERATE

YES

NO

23WA No.1 ON?

YES

CZ1 ON

TM1 ON

NO

PASS THE 3 MIN.?

YES

52C1 ON MC1 OPERATE MF2 OPERATE

CH1 OFF

23WA No.2 ON?

NO

YES

CZ2 ON

TM2 ON

PASS THE 2 SEC.?

NO

YES

52C2 ON MC2 OPERATE MF3 OPERATE

CH2 OFF

NO

No.2 SAFETY DEVICE OFF?

No.1 SAFETY DEVICE OFF?

NO

YES

30CZ2 OFF

YES

30CZ1 OFF

52C2 OFF MC2 STOP MF3 STOP

52C1 OFF MC1 STOP MF2 STOP

RL2 ON

RL1 ON

CH2 ON

CH1 ON

SERVICE CALL

Page 45 of the Mitsubishi Electronics 8 user manual — YES
Page 45 · click to enlarge
Page 45

PRH-15, 20YA PRH-15, 20YA-L

START

HZ ON

POWER ON

21S41, 2 ON

CH1, 2 ON

NO

23WA No.2 ON?

GL ON

YES

30CZ1, 30CZ2 ON (SELF HOLD)

CZ1 ON

NO

TM1 ON

SW3 ON?

YES

NO

PASS THE 3 MIN.?

FZ0, FZ1 ON (SELF HOLD)

YES

52F ON MF1 OPERATE

TM2 ON

NO

NO

PASS THE 2 SEC.?

SW1 COOL?

YES

YES

52C2 ON MC2 OPERATE MF3 OPERATE

NO

23WA No.1 ON?

YES

CH2 OFF

CZ1 ON

TM1 ON

NO

23WA No.1 ON?

YES

PASS THE 3 MIN.?

NO

52C1 ON MC1 OPERATE MF2 OPERATE

YES

52C1 ON MC1 OPERATE MF2 OPERATE

CH1 OFF

CH1 OFF

NO

No.1 CONDENSING

TEMP. -12˚C?

NO

23WA No.2 ON?

YES

26D1, 3 ON

YES

CZ2 ON

X1 ON X3 ON (SELF HOLD)

NO

TM2 ON

No.2 CONDENSING

TEMP. -12˚C?

21S41 OFF MF2 STOP

NO

YES

PASS THE 2 SEC.?

26D2, 4 ON

YES

No.1 CONDENSING

NO

X2 ON X4 ON (SELF HOLD)

52C2 ON MC2 OPERATE MF3 OPERATE

TEMP. 6˚C?

21S42 OFF MF3 STOP

YES

26D1, 3 OFF

CH2 OFF

No.2 SAFETY DEVICE OFF?

NO

X1, 3 OFF

NO

No.1 SAFETY DEVICE OFF?

NO

No.2 CONDENSING

TEMP. 6˚C?

YES

30CZ2 OFF

21S41 ON MF2 OPERATE

YES

YES

30CZ1 OFF

52C2 OFF MC2 STOP MF3 STOP

No.1 DEFROST

YES

OPERATION?

52C1 OFF MC1 STOP MF2 STOP

NO

RL2 ON

21S42 ON MF2 OPERATE

RL1 ON

CH2 ON

CH1 ON

SERVICE CALL

Show 4 more labels / short text on this page
<= · <= · <= · <=
Page 46 of the Mitsubishi Electronics 8 user manual — Dryer Strainer
Page 46 · click to enlarge
Page 46

REFRIGERANT SCHEMATICS

PR-5YC

Condenser Evaporator

ø19.05

High pressure switch

Check joint

Check joint

ø19.05

Pressure gauge

ø12.7

Check joint

ø22.2

Check joint

Compressor

Capillary Tube

ø12.7

ø12.7

Dryer Strainer

: OPTION

PR-15,20YC or PRH-15,20YA or PRH-15,20YA-L is composed of two refrigerant cycles.

PR-8, 10, 15, 20YC

Condenser Evaporator

ø19.05

High pressure switch

Check joint

Check joint

ø19.05

Pressure gauge

ø12.7

Check joint

ø22.2

Check joint

Compressor

Capillary Tube

ø12.7

ø12.7

Dryer Strainer

: OPTION

Page 47 of the Mitsubishi Electronics 8 user manual — Dryer Strainer Strainer
Page 47 · click to enlarge
Page 47

PRH-5YA

Condenser Evaporator

ø19.05

High pressure switch

Check joint

4-Way valve

Check joint

ø19.05

Pressure gauge

ø12.7

Check joint

ø22.2

Check joint

Compressor

Capillary Tube

Capillary Tube

ø12.7

ø12.7

Dryer Strainer Strainer

Check valve

: OPTION

PR-15,20YC or PRH-15,20YA or PRH-15,20YA-L is composed of two refrigerant cycles.

PRH-8, 10, 15, 20YA

Condenser Evaporator

8, 15YAø22.0 10, 20YA: ø25.4

High pressure switch

4-Way valve

Check joint

8, 15YAø22.0 10, 20YA: ø25.4

Pressure gauge

Muffler

ø15.88

ø15.88

Check joint

Check joint

ø25.4

Check joint

Compressor

Capillary Tube

Capillary Tube

ø12.7

ø12.7

Dryer Strainer Strainer

Check valve

: OPTION

Page 48 of the Mitsubishi Electronics 8 user manual — Dryer Strainer Strainer
Page 48 · click to enlarge
Page 48

PRH-5YA-L

ø19.05

ø19.05

ø12.7

ø22.2

ø12.7

ø12.7

: OPTION

PR-15,20YC or PRH-15,20YA or PRH-15,20YA-L is composed of two refrigerant cycles.

PRH-8, 10,15,20YA-L

Condenser Evaporator

8,15YA-Lø22.0 10,20YA-L: ø25.4

High pressure switch

4-Way valve

Check joint

8,15YA-Lø22.0 10,20YA-L: ø25.4

Pressure gauge

Muffler

ø15.88

ø15.88

Check joint

Check joint

ø25.4

Check joint

Accumulator

Compressor

Capillary

Tube

Capillary Tube

ø12.7

ø12.7

Dryer Strainer Strainer

Check valve

: OPTION

Show 14 more labels / short text on this page
Condenser Evaporator · High pressure switch · Check joint · 4-Way valve · Check joint · Pressure gauge · Check joint · Check joint · Accumulator · Compressor · Capillary Tube · Capillary Tube · Dryer Strainer Strainer · Check valve
Page 49 of the Mitsubishi Electronics 8 user manual — :Factory install :Field install
Page 49 · click to enlarge
Page 49

SAFETY & CONTROL DEVICES

PR-10YC PRH-10YA PRH-10YA-L COMPRESSOR OVER CURRENT RELAY 51C 26.0A 27.5A 31.0A COMPRESSOR INTERNAL THERMOSTAT - 110˚C OFF 120˚C OFF 130˚C OFF HIGH PRESSURE SWITCH 63H 2.94MPa OFF FREEZE PROTECTOR 26L -2˚C IN FROST PROTECTOR (ONLY PRH-YA,PRH-YA-L) 26D1,2 -12˚C IN, 6˚C OUT INDOOR FAN MOTOR OVER CURRENT RELAY 51F1 2.3A 3.2A 3.6A OUTDOOR FAN MOTOR OVER CURRENT RELAY 51F2 2.0A OUTDOOR FAN MOTOR INTERNAL THERMOSTAT - 150˚C OFF FUSE (CONTROL CIRCUIT) F 3.15A FUSE (OPERATION CIRCUIT) F 3.15A OUTDOOR FAN MOTOR OVER CURRENT RELAY (USE THE OPTIONAL PARTS : LOW AMBIENT PARTS) 51F3 2.0A

PR-5YC PRH-5YA PRH-5YA-L

PR-8YC PRH-8YA PRH-8YA-L

ITEM NO.

PR-15YC PRH-15YA PRH-15YA-L

PR-20YC PRH-20YA PRH-20YA-L

ITEM NO.

COMPRESSOR OVER CURRENT RELAY 51C1,2 27.5A 31.0A COMPRESSOR INTERNAL THERMOSTAT - 120˚C OFF 130˚C OFF HIGH PRESSURE SWITCH 63H1,2 2.94MPa OFF FREEZE PROTECTOR 26L1,2 -2˚C IN FROST PROTECTOR (ONLY PRH-YA,PRH-YA-L) 26D1,2,3,4 -12˚C IN, 6˚COUT INDOOR FAN MOTOR OVER CURRENT RELAY 51F1 5.0A 6.6A OUTDOOR FAN MOTOR OVER CURRENT RELAY 51F2,3 2.0A OUTDOOR FAN MOTOR INTERNAL THERMOSTAT - 150˚C OFF FUSE (CONTROL CIRCUIT) F 3.15A FUSE (OPERATION CIRCUIT) F 3.15A OUTDOOR FAN MOTOR OVER CURRENT RELAY (USE THE OPTIONAL PARTS : LOW AMBIENT PARTS) 51F4,5 2.0A

ACCESSORY AVAILABILITY

DESCRIPTION MODEL NAME PARTS CODE PR-5YC PRH-5YA PRH-5YA-L PR-8YC PRH-8YA PRH-8YA-L PR-10YC PRH-10YA PRH-10YA-L

PR- YC-K - PRH- YA-K - PRH- YA-LK -

PR- YC PAC-201LC - - PAC-202LC - - PAC-203LC - - PRH- YA - PAC-201LC - - PAC-202LC - - PAC-203LC - PRH- YA-L - - PAC-201LC - - PAC-202LC - - PAC-203LC

PR- YC PAC001PG - - PAC002PG - - PAC003PG - - PRH- YA - PAC001PG - - PAC002PG - - PAC003PG - PRH- YA-L - - PAC001PG - - PAC002PG - - PAC003PG

PR- YC PAC101FG - - PAC102FG - - PAC103FG - - PRH- YA - PAC101FG - - PAC102FG - - PAC103FG - PRH- YA-L - - PAC101FG - - PAC102FG - - PAC103FG

PARTS CODE PR-15YC PRH-15YA PRH-15YA-L PR-20YC PRH-20YA PRH-20YA-L

DESCRIPTION MODEL NAME

PR- YC PAC-201LCX2(PCS) - - PAC-201LCX2(PCS) - - PRH- YA - PAC-201LCX2(PCS) - - PAC-201LCX2(PCS) - PRH- YA-L - - PAC-201LCX2(PCS) - - PAC-201LCX2(PCS)

PR- YC PAC001PGX2(PCS) - - PAC001PGX2(PCS) - - PRH- YA - PAC001PGX2(PCS) - - PAC001PGX2(PCS) - PRH- YA-L - - PAC001PGX2(PCS) - - PAC001PGX2(PCS)

PR- YC PAC104FG - - PAC105FG - - PRH- YA - PAC104FG - - PAC105FG - PRH- YA-L - - PAC104FG - - PAC105FG

:Factory install :Field install

Show 7 more labels / short text on this page
K-Remote controller · Low temperature cooling · Pressure gauge · Fin guard · Low temperature cooling · Pressure gauge · Fin guard
Page 50 of the Mitsubishi Electronics 8 user manual — [REFRIGERATION SYSTEM]
Page 50 · click to enlarge
Page 50

PHYSICAL DATA

[PRODUCT] ROOFTOP AIR-COOLED HEATPUMP PACKAGED AIR CONDITIONERS

Product type PR,PRH,PRH-L SERIES

Product numberCooling type PR-5YC PR-8YC PR-10YC PR-15YC PR-20YC
Product numberHeat pump PRH-5YA PRH-8YA PRH-10YA PRH-15YA PRH-20YA
Product numberHeat pump PRH-5YA-L PRH-8YA-L PRH-10YA-L PRH-15YA-L PRH-20YA-L

Capacity kw 17.6 28.1 35.2 52.8 70.3

Cooling capacity (AS1861) kW 16.3 23.8 29.7 46.3 60.8

Sensible Cooling capacity (AS1861) kW 13 19.7 25.3 38.4 50.2

Cooling power consumption (Input) kW 5.4 8.3 11.4 16.8 22.7

ByPass Factor 0.19 0.24 0.18 0.18 0.11

Heating capacity (AS1861) (Only PRH-YA,PRH-YA-L) kW 15.1 23 32 45.5 61.2

Heating power consumption (Only PRH-YA,PRH-YA-L) kW 4.6 7 9.6 14.4 19.3

[ELECTRICAL]

Design voltage Volts 415

Power supply Volts 415

Control voltage Volts 240/24

Maximum voltage Volts 415

Minimum voltage Volts 380

Approx. starting current Amps 62 87 100 115 135

Unit current (Nominal voltage and AS1861 maximum conditions) Amps 12.8 20.6 25.7 37.9 50.9

Fan motor hp HP 1.0 1.5 2 3 4

Fan motor current Amps 2.26 2.90 3.28 4.72 6.06

Fan motor speed rpm 1,400 1,410 1,420

[COMPRESSOR]

Model CRNQ-0500-TFD QR90K1-TFD QR12M1-TFD QR90K1-TFD QR12M1-TFD

Type HERMETIC LINE START (RECIPROCATING)

Quantity 1 1 1 2 2

Nominal motor hp HP 5 7.5 10 27.5 210

Locked rotor current Amps 59.5 83.4 95.2 83.4 95.2

Normal run current (AS1861) Amps 7.65 11.7 15.62 211.74 215.22

Swept volume cc/rev 101.92 177.45 221.8 2177.45 2221.8

Bore mm 49.78 55.58

Stroke mm 26.19 18.29 22.86 18.29 22.86

Number of cylinders 2 4

Oil charge ml 2,070 3,250 23,250

Type of oil Calumet R015 or Witco 3GS

Crankcase heater watts 40 70 270

[REFRIGERATION SYSTEM]

Refrigerant charge per circuit kg 3.6 4.6 5.8 24.6 25.8

Number of refrigerant controls 1 1 1 2 2

Refrigerant control Capillary tube

Reverse cycle valve (Only PRH-YA,PRH-YA-L) 4-Way valve

Defrost system (Only PRH-YA,PRH-YA-L) Reverse cycle defrost

[EVAPORATOR] Quantity 1 1 1 2 2

Face area sq.m 0.53 0.69 20.65

Rows deep 3 3 4 3 4

Rows high 26 26 26 30 30

Finned length mm 800 1,046 2850

Face velocity m/s 1.7 2.0 2.4 2.2 2.4

Fins per meter 512 512 512 473 512

Fin material thickness mm 0.12

Fin material Aluminium Fins pitch mm 1.95 1.95 1.95 2.11 1.95

Tube diameter mm 9.52

Gauge of copper tube mm 0.35

Number of circuits 10 13 17 11 15

Show 5 more labels / short text on this page
Cycles Hz 50 · Phases 3 · Make COPELAND · Speed rpm 2,900 · Refrigerant R22
Page 51 of the Mitsubishi Electronics 8 user manual — [ENCLOSURE AND FRAME]
Page 51 · click to enlarge
Page 51

[PRODUCT] ROOFTOP PACKAGE AIR COOLED HEATPUMP AND COOLING ONLY UNITS

Product type PRH SERIES

Product numberHeat pump PRH-5YA PRH-8YA PRH-10YA PRH-15YA PRH-20YA

[INDOOR AIR CIRCUIT]

Number of blowers 1 2

Diameter of blowers mm 253 393

Width of blowers mm 182 282

Blower drive Belt drive

Fan motor output kW 0.75 1.1 1.5 2.2 3.0

Normal fan motor run current A 2.26 2.90 3.28 4.72 6.06

Air quantity L/s 900 1,400 1,660 2,800 3,160

External static pressure Pa 100 200

Supply air dimensions (h w) mmmm 300 850 300 1,150 428 1,820

Return air dimensions (h w) mmmm 410 900 410 1,200 464 1,879

[CONDENSER]

Quantity 1 1 1 2 2

Face area sq.m 1.3 1.12 1.46 21.07 21.32

Rows deep 3

Rows high 30 23 30 30 37

Finned length mm 1,700 1,920 21,400

Face velocity m/s 1.2 2.8 2.1 2.9 2.3

Fins per meter 473

Fin material thickness mm 0.12

Fins pitch mm 2.11

Tube diameter mm 9.52

Gauge of copper tube mm 0.35

Number of circuits 11 11 15 11 14

[OUTDOOR AIR CIRCUIT]

Number of fans 1 1 1 2 2

Diameter of fans mm 600 800

Pitch of fans mm - - - 990

Fan drive Direct drive

Fan motor output kw 0.15 0.35 0.35 20.35 20.35

Quantity 1 1 1 2 2

Normal fan motor run current Amps 0.6 1.3 1.3 21.3 21.3

Fan motor speed rpm 650 645

Air quantity L/s 1,583 3,083 23,083

[ENCLOSURE AND FRAME]

height mm 1,000 1,200

Dimension width mm 1,000 1,300 1,990

depth mm 1,600 1,840

Panel thickness mm 1.2

Condensate drain size mm 25.4

Weight kg 299 393 413 698 729

Sound power level dbA 73 75 75 79 79

Sound pressure level dbA 62 64 64 68 68

Fin material Aluminium · Color Munsell 5Y8/1

Page 52 of the Mitsubishi Electronics 8 user manual — 1.Clearances
Page 52 · click to enlarge
Page 52

INSTALLATION

All series of air conditioners are designed for outdoor installations and are to be placed on a slab or rooftop, however if the air conditioner is to be installed in a plant room application, please contact your equipment supplier prior to installation. Access for both service and installation must be provided to the compressors, control wiring and fans as shown below.

1.Clearances

(1) Care must be taken to prevent recirculation of

Mitsubishi Electronics 8 — 1.Clearances diagram (page 52)
Fig. 20 · 1.Clearances

the condenser air. To stabilize compressor condensing pressures it is recommended that wherever possible the condenser air inlet side be faced away from prevailing winds. (2) For rooftop installation, the type of mounting

plates for rigging and hoisting of the unit. The hoisting plates are located in the base of the unit. When hoisting the unit with a crane, spreader bars must be used to prevent damage to side panels by the supporting cables.

base depends on the roof construction. A built- up roof may not support the weight of the unit and so it may be necessary to support the unit by adding structural members below it.

Mitsubishi Electronics 8 — 1.Clearances diagram (page 52)
Fig. 21 · 1.Clearances
Mitsubishi Electronics 8 — 1.Clearances diagram (page 52)
Fig. 22 · 1.Clearances

2.Roof Mounting (1) The figure shows the use of the roof curb available

for mounting these units. (2) The curb should be sealed and fixed to the roof by

weather stripping. A suggested means of sealing the unit and roof curb is shown below.

Page 53 of the Mitsubishi Electronics 8 user manual — (4) Upon completion of the piping work, check that there
Page 53 · click to enlarge
Page 53

3.Duct Work (1) All series units are equipped with horizontal

Vertical air plenum PRH unit

supply and return air openings. Duct connection to the unit should be made with duct flanges and secured directly to the air openings with flexible duct connectors to avoid normal noise transmission.

Plenum divider

Insulation

(2) For vertical air supply, a field supply plenum should

be used. The figure below shows the recommended method for duct connection.

Roof curb Roof curb

(3) To prevent air leakage, all duct seams should be

Roof line

taped. Ducts run in air spaces that are not air-conditioned must be insulated and provided with a vapor barrier. Ducts exposed to the outside must be weatherproofed. For quiet operation, we recommend that the insulation on the supply duct be placed inside, lining the duct.

Singleduct divider Duct Duct

Duct connection with a vertical air plenum

(4) Where ducts from the outside enter a building, the

duct openings in the building should be sealed with weather stripping to prevent rain, duct, sand,etc. from entering the building.

(5) Correctly sized filters must be fitted and there is no

provision within the unit, however the filters may be installed in the return air.

4.Drain piping

(1) A 1 FPT condensate drain fitting is provided. The

B

drain pipe can be led out at the right or left side. Under standard specifications, it is led out at the left side and the right side is covered.

A > 70mm B > 2C C > 2XE.S.P

A C

= = =

Drain piping

(2) The drain pipe must be provided with a trap on the

Drain trap

The drain pipe should extend below this level.

outside of the unit and also installed at an incline for proper drainage, as shown below.

Note:ESP=External Static Pressure

(3) To prevent condensate formation and leakage,

Drain trap for condensate

provide the drain pipe with insulation to safeguard against sweating.

(4) Upon completion of the piping work, check that there

is no leakage and that the water drains off properly.

Page 54 of the Mitsubishi Electronics 8 user manual — L1 L2 L3 N PE
Page 54 · click to enlarge
Page 54

5.Electrical Wiring Remove the panel on the right side (PR,PRH-5 10) or the rear side (PR,PRH-15,20) of the unit and connect the units power supply wiring to the proper terminals in the control box, as shown below.

PR-20YC PRH-20YA PRH-20YA-L 0.75 1.1 5.5 5.5 40

PR-5YC PRH-5YA PRH-5YA-L

PR-8YC PRH-8YA PRH-8YA-L

PR-10YC PRH-10YA PRH-10YA-L

PR-15YC PRH-15YA PRH-15YA-L

MODEL

INDOOR FAN MOTOR OUTPUT

<kW> < mm > < mm > < A >

1.1 1.5 5.5 5.5 50

1.5 2.2 2.2 3.0

3.0 4.0 22 22 100

WIRING POWER SUPPLY

22 22 100

EARTH

MAIN SWITCH

Std.

Control box Terminal block

Terminal block

Control box

power supply

power supply

Wiring for PR,PRH-5 10(right side view)

Wiring for PR,PRH-15,20(rear view)

TN-NET SYSTEM (For European models only)

L1 L2 L3 N PE

6.Final Checks After having installed the unit, check that: (1) The unit is fixed securely. (2) The unit is installed properly. (3) The drain pipe is provided with a drain trap. (4) The electrical wiring has been connected correctly and the terminal screws have been properly

tightened. (5) The duct work has been performed correctly.

7.Trial Operation (1) Before turning the unit on, measure the resistance between the terminals of the electrical parts and

ground with a 500V megger and check that the value is at least 1MΩ. If the measured value is below 1MΩ, do not operate the unit. (2) Check the operation of the high pressure switch by activating it. Operation should stop when the two leads

of the outdoor unit fan motor are removed from the contactor and cooling continues for 5~10min. (3) Check that the indoor and outdoor fans are rotating in the proper direction. (4) After having checked the above points, proceed with a trial operation of the unit.

Page 55 of the Mitsubishi Electronics 8 user manual — Ground
Page 55 · click to enlarge
Page 55

INSTRUCTIONS FOR USE

1.CHECK POINTS FOR OPERATION

Check the following points before you operate your air conditioner.

(1) Check that there is nothing blocking the flow of air from the air outlet into the air inlet.

Indoor Unit

Outlet grille

Inlet grille

Ceiling

Ceiling

Obstacle blocking air inlet

Obstacle blocking air inlet

Outdoor Unit

Obstacle blocking air inlet

(2) Make sure the air conditioner is properly grounded by checking the ground terminal .

Ground

Page 56 of the Mitsubishi Electronics 8 user manual — Heat exchanger
Page 56 · click to enlarge
Page 56

2.CAUTION FOR USE

Keep the following points in mind to safeguard against failures and breakdowns.

(1) This air conditioner does not restart within 3min.

after shut down. (These models have a crankcase heater in the compressor. If the air conditioner is shut down for a short time, please do not turn the power switch to OFF, but turn the operation switch to OFF.) (2) If the air conditioner is shut down by a power failure,

Shutdown Operation 3 Minutes

set the operation switch to OFF. When the power is restored, normal air conditioner operation can be resumed. (3) Do not stick rods or other objects through the air

outlet during operation since this may result in equipment damage or personal injury.

3.MAINTENANCE For superior performance and lasting durability, please do not forget to conduct proper and regular maintenance.

3.1 Cleaning the Air Filter Clean the air filter about once a week with a neutral cleanser and leave it to dry in a shady location. Clean more regularly if the air filter gets very dirty.

If the filter gets blocked, air will not be sucked in properly, and the cooling effect will deteriorate. Failure to clean the air filter may result in equipment breakdown or malfunctions.

3.2 Cleaning panels Clean dirt off front panel as follows. Use a household neutral cleanser such as for dishes or vegetables. Moisten a soft cloth with the cleanser, then wipe lightly. Next,wipe three or four times with another soft cloth moisten with water. Finally, wipe off all the remaining cleanser with a soft cloth.

Fingermarks

Neutral Cleanser

Grease

Moisten a soft cloth with the alcohol, then wipe off lightly. Isopropyl alcohol is sold at stores as reagents in small quantities.

Adhesive

Isopropyl alcohol

Note:

Alcohol is highly combustible. Take extreme care when handling. Also, do not use paint or adhesive thinner.

Paste

3.3 Cleaning the Outdoor Unit Heat Exchanger If you use your air conditioner for prolonged periods, the outdoor heat exchanger will become dirty, impairing its function and reducing air conditioners performance. Consult your equipment supplier or air conditioning contractor on how to clean the heat exchanger.

Heat exchanger

Heat exchanger

Page 57 of the Mitsubishi Electronics 8 user manual — 6.TROUBLESHOOTING
Page 57 · click to enlarge
Page 57
4. PREPARING FOR OPERATION AFTER PROLONGED SHUTDOWN When the usage season starts, proceed with the following before starting operation: (1)Clean the air filter. (2)Do not use the unit immediately. Turn the main power switch on for a period of 3 hours before restarting

cooling / heating operation. This allows the compressors to come up to the correct operation temperatures. Failure to do this, could cause compressor failure.

5.PREPARING FOR PROLONGED SHUTDOWN After the usage season is over, prepare the air conditioner for later use by: (1)Setting the power switch to OFF. (2)Consulting your Air conditioning specialist for detailed information.

6.TROUBLESHOOTING

If any trouble occurs, turn the operation (start or run) switch off immediately.

Remedy Possible cause Symptom

Wait for power supply recovery. Power failure. Both fan and compressor

Contact your Air conditioning specialist. Blown fuse of power source switch.

do not run.

Ask your electric power company. Excessively low power source voltage.

  • For temperature control,
  • decrease the set temperature at cooling.
  • increase the set temperature at heating.
  • The set temperature of thermostat is
  • excessively high for cooling.
  • excessively low for heating.

Fan runs but compressor

does not run. Can not be operated as it is out of temperature control range.

  • The room temperature is
  • excessively low for cooling.
  • excessively high for heating.

Remove blocking matter. Air outlet and inlet are blocked.

Fan runs but stops immediately.

Clean it. The filter installed in the field is clogged with dust.

Close them. Windows and doors are being opened.

Remove blocking matter. Air outlet and inlet are blocked.

cooling/heating.

  • The set temperature of thermostat is
  • excessively high for cooling.
  • excessively low for heating.
  • For temperature control,
  • decrease the set temperature at cooling.
  • increase the set temperature at heating.

Insufficient refrigerant charge.

Contact your Air conditioning specialist.

Runs but without

Page 58 of the Mitsubishi Electronics 8 user manual — SPECIFICATION GUIDELINES
Page 58 · click to enlarge
Page 58

SPECIFICATION GUIDELINES

Please supply and install a one piece, air to air reverse cycle air conditioning system.

The system shall be completely assembled, tested and have a complete refrigeration charge ready for installation and operation from the factory.

The system shall operate at outdoor ambient temperatures as high as 46˚C.

The system shall have a total cooling capacity of kW or greater with an indoor air quantity of L/s at ˚C db and ˚C wb entering indoor coil temperature with a ˚C temperature entering the outdoor coil.

The system shall have a sensible heat capacity of kW or greater with a room db temperature of ˚C.

The total heating capacity (without electric element heaters) shall be kW or greater at ˚Cdb, ˚C wb outdoor air conditions, with ˚C of indoor air entering indoor coil at ˚C db. One kW electric heater element (accessory) shall be furnished.

The compressors shall be a welded high efficiency hermetic type with internal vibration isolation and be equipped with a crankcase heater.

Compressors shall be protected by a factory installed anti-cycle device and provide a 3 minute delay before compressor can restart.

Coils shall be of non-ferrous construction with mechanically bonded aluminium plate fins. Outdoor coils shall be made, of 9.52mm OD, 0.35mm thick seamless copper tubes mechanically bonded to 0.12mm thick aluminium plate fins.

Coils with multiple stage refrigeration systems shall consist of independent circuits. Face area of the coil shall not be less than M2. The coil shall be factory pressure and leak tested at 3,233 kPa pressure. The indoor coil face area shall be not less than M2.

Multi-wing propeller type fans shall be fitted at the condenser and shall be dynamically balanced, to ensure smooth airflow and shall discharge vertically and be direct driven by a weatherproof three phase squirrel cage kW induction motor.

The system shall be factory wired and all electrical wiring must comply with the Local wiring code. (Controls and control wiring shall be supplied by the contractor). Compressors and fan motors shall have both internal and current sensitive overload devices.

An automatic defrost control shall be included to accomplish defrosting (only if required) every

minutes for a period of minutes.

A low voltage transformer (24V) shall be factory installed in the unit for an external control circuit.

High pressure switch (pre-set) shall be factory installed.

The enclosure shall be a single, enclosed, weatherproof casing constructed of phosphatised, zinc coated steel with acrylic resin primer and ivory white baked enamel finish.

The unit shall be provided with hoisting plates for rigging and hoisting the unit. The hoisting plates shall be located in the base of the unit.

The unit shall have a 25mm OD male drain connection provided. The drain pipe shall be accessible from either the left or right side of the unit. A blanking cap shall be provided to cap the drain outlet not being used.

The duct (field supply) shall be fully insulated with fiber glass insulation to prevent sweating and to minimize sound.

Each unit shall have a drain pan of 1mm thick steel coated with epoxy resin enamel.

The enclosure shall have openings provided for power connections. Access for both service and installation shall be provided to compressors, control wiring, filters, electric heaters (when fitted) and fans.

Side panels and top panels shall be removable for easy service access.

The unit maximum dimensions shall be : height: mm, width: mm and depth: mm.

Due to continuous product development, these guidelines are subject to change.

Page 59 of the Mitsubishi Electronics 8 user manual — MEMO
Page 59 · click to enlarge
Page 59

MEMO

Page 60 of the Mitsubishi Electronics 8 user manual — DATA BOOK PR,PRH
Page 60 · click to enlarge
Page 60

DATA BOOK PR,PRH

HEAD OFFICE DENKI BLDG., MARUNOUCHI,TOKYO 100,TELEX J24532 CABLE MELCO TOKYO MITSUBISHI ELECTRIC CORPORATION

Issuued in January. 1999 MEE98K036 Printed in Japan.

New publication effective Jan. 1999. Specifications subject to change without notice.

Fix-it

Troubleshooting

Common problems, likely causes, and what to do.

ProblemPossible causeRemedy
Both fan and compressor do not run.Power failure.Wait for power supply recovery. p.57
Both fan and compressor do not run.Blown fuse of power source switch.Contact your Air conditioning specialist. p.57
Both fan and compressor do not run.Excessively low power source voltage.Ask your electric power company. p.57
Fan runs but compressor does not run.The set temperature of thermostat is • excessively high for cooling. • excessively low for heating.For temperature control, • decrease the set temperature at cooling. • increase the set temperature at heating. p.57
Fan runs but compressor does not run.The room temperature is • excessively low for cooling. • excessively high for heating.Can not be operated as it is out of temperature control range. p.57
Fan runs but stops immediately.Air outlet and inlet are blocked.Remove blocking matter. p.57
Runs but without cooling/heating.The filter installed in the field is clogged with dust.Clean it. p.57
Runs but without cooling/heating.Windows and doors are being opened.Close them. p.57
Runs but without cooling/heating.Air outlet and inlet are blocked.Remove blocking matter. p.57
Runs but without cooling/heating.The set temperature of thermostat is • excessively high for cooling. • excessively low for heating.For temperature control, • decrease the set temperature at cooling. • increase the set temperature at heating. p.57
Runs but without cooling/heating.Insufficient refrigerant charge.Contact your Air conditioning specialist. p.57

Ask about the Mitsubishi Electronics 8

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.