Series
COOLING ONLY :PR-5,8,10,15,20
HEAT PUMP :PRH-5,8,10,15,20
PRH-5,8,10,15,20-L
DATA BOOK


Before conducting installation work, please read this ''SAFETY FOR USE'' carefully for correct installation. Since the caution items shown here contain important description relative to safety, please observe them without fail.
After reading, please keep it with you together the Instruction Manual, and read it again at the movement of the unit.
Never repair the unit, remodel or transfer it to another site by yourself.
The unit should not be installed by the user.
If the unit is installed improperly, explosion, water leakage, electric shock or fire may be result. Consult your dealer or specialist subcontractor for repair and movement.
If they are performed improperly, water leakage, electric shock or repaired or moved, consult your dealer.
For installation, conduct the work correctly by following the Installation Manual.
Use only the specified refrigerant (R-22) to charge the refrigerant circuit. Do not mix it with any other refrigerant and do not allow air to remain in the circuit.
Improper installation may cause a fire, electrical shock or water leakage.
Air enclosed in the circuit can cause high pressure resulting in a rupture and other hazards.
Install the unit on a spot sufficiently durable against the unit weight.
Insufficient durability can cause an injury by the falling down of unit.
After completing installation work, make sure that refrigerant gas has not leaked.
If refrigerant gas has leaked and exposed to fan heater, stove, oven and so on, it may generate noxious gases.
All electric work must be performed by licensed technician, according to local regulations and the instructions given in this manual. The units should be powered by dedicated power lines.
Take a proper measure to suppress the critical concentration of refrigerant if leaked when installing the unit in a small room.
Power lines with insufficient capacity or improper electrical work may result in electric shock or fire.
The limit density is made not to be exceeded even if the refrigerant leaks by any chance. You are necessary to ventilation measures to prevent the accident. If the refrigerant leaks, hypoxia accident may caused. For the countermeasure to be taken, consult your dealer.
Use only the specified cables for wiring. The connections must be made secured without tension the terminals.
Improper connection or fastening can cause a fire or electrical shock.
The unit should be installed according to the instructions in order to minimize the risk of damage from earthquakes, typhoons or strong winds.
The terminal block cover of unit must be firmly attached to prevent entry of dust and moisture.
Improper mounting of the cover cause electric shock or fire.
Improper installation work can cause an injury by the falling down of the unit.
The unit must be installed on stable, flat surface, in a place where there is no accumulation of snow, leaves or rubbish.
Use only optional parts authorised by Mitsubishi Electric.
If the accessories are installed improperly, water leakage, electric shock or fire may result. Ask your dealer or an authorised company to install them.
The unit should be installed in a location where air and noise emitted by the unit will not disturb the neighbors.
If the unit is loosely mounted, it may fall, and cause injury.

Refrain from installing the unit in an area where flammable gas can accumulate around the unit.
Arrange the configuration of wiring not to bring up the panel and terminal cover, and fasten the panel and terminal cover securely.
If the flammable gas can accumulate around the unit, an explosion can occur.
The poor mounting of the panel or terminal cover may cause the heat generation of the terminal connection, a fire or electrical shock.
When the unit is installed at telecommunication centers or hospitals, take a proper provision against noise.
If washed with water, electrical shock may be caused. Do not wash the unit with water.
The erroneous operation of air conditioner may be induced by inverter equipment, independent power device, medical equipment or communication equipment. While the erroneous operation of medical equipment or communication equipment may caused by the air conditioner.
Do not handle the switch with wet hands.
Otherwise electrical shock can be resulted.
Be very careful on handling the unit.
When carrying in outdoor unit, be sure to support it at four points. Carrying in and lifting with 3-point support may make outdoor unit unstable, resulting in a fall of it. The unit should not be carried by only one person if it is more than 20kg. Some units use PP bands for packing. Do not use any PP band for delivery purpose. Do not touch the heat exchanger fins with your bear hands. Doing so may cut your hands. Be sure to safely dispose the packaging materials. Packaging materials, such as catches and other metal or wooden parts, may cause stabs or other injuries. Tear off and discard plastic packing bags so that children will not play any of them. If children play with a plastic bag which was not torn off, it may cause a risk of suffocation.
For special use as for foods, animals/plants, precision equipment or art objects, the applicability should be confirmed beforehand.
As the use for the applications other than that designed originally may result in the deterioration of the quality. Consult your dealer in this regard.
Do not use the unit under a special atmosphere.
Installing the unit at the following places may cause a trouble, a place where much machine oil, salt sonnet, humidity or dust, spa district, a place full of sulfur gas, volatile gas, or corrosive gas, a place near high frequency processing machine.
Thermal insulation of the drain pipes is necessary prevent dew condensation.
If the drain pipes are not properly insulated, condensation will result and drip on ceiling, floor or other possessions.
The base and attachments of the unit should be periodically checked for looseness, cracks or other damage.
The drain piping must process by surely,and insulate the drain piping not to be dewy.
If such defects are left uncorrected, the unit may fall and cause personal injury or property damage.
When the room humidity exceeds 80% or when the drain pipe is clogged, water may drip from the indoor unit. The outdoor unit produces condensation during the heating operation. Make sure to provide drainage around the outdoor unit if such condensation is likely to cause damage.
Turn on the main power switch more than 6 hours before starting operation.
Do not turn the main power switch OFF during seasons of heavy use, doing so can result In failure.
Install drain piping according to this Installation Manual to ensure proper drainage. Place thermal insulation on the pipes to prevent condensation.
Do not touch the compressor or refrigerant piping without wearing glove on your hands.
Touching directly such part can cause a burn or frostbite as it becomes high or low temperature according to the refrigerant state.
Improper drain piping may cause water leakage and damage to furniture or other possessions.
Do not touch the metal edges inside the unit without wearing glove on your hands.
The unit must be properly earth connected.
Do not connect the earth wire to gas pipe, city water pipe, lightning rod or telephone earth wire. Improper earth connection may cause electrical shock.
Touching directly it may injure your hands.
Do not remove the front panel or the fan guard from the unit when it is running.
When installing at a watery place, provide an electric leak breaker.
You could be injured if you touch rotating, hot or high- voltage parts.
Failure to mount the electric leak breaker may cause electrical shock.
Do not operate the air conditioner without the air filter set place.
Make sure that there is a main power switch. Use breaker or fuse with proper capacity.
Dust may accumulate, and cause a failure.
At emergency (if you smell something burning), stop operation and turn the power source switch off.
Using a wire or a copper wire instead of proper capacity of fuse can cause fire or trouble. Other appliances connected to the same line could cause an overload.
Continuing the operation without eliminating the emergency state may cause a machine trouble, fire, or electrical shock.
For the power lines, use standard cables of sufficient current capacity.
After stopping operation, be sure to wait for five minutes before turning off the main power switch.
Otherwise, current leakage, overheating or fire may occur.
Otherwise, water leakage or unit failure may occur.
When installing the power lines, do not apply tension to the cables.
The tighten or loosen the connections may cause generate heat and cause fire.


(PRH ONLY)
Cooling capacity
Heatling capacity
14,000 kcal/h 55,600 BTU/h 16.3 kW
13,000 kcal/h 51,600 BTU/h 15.1 kW
PR-8YC PRH-8YA PRH-8YA-L

Cooling capacity
Heatling capacity
20,500 kcal/h 81,300 BTU/h 23.8 kW
19,800 kcal/h 78,600 BTU/h 23 kW
PR-10YC PRH-10YA PRH-10YA-L
(PRH ONLY)
Cooling capacity
Heatling capacity
25,500 kcal/h 101,200 BTU/h 29.7 kW
27,500 kcal/h 109,100 BTU/h 32 kW
PR-15YC PRH-15YA PRH-15YA-L
(PRH ONLY)
Cooling capacity
Heatling capacity
39,100 kcal/h 155,100 BTU/h 45.5 kW

PR-20YC PRH-20YA PRH-20YA-L
(PRH ONLY)
Cooling capacity
Heatling capacity
52,300 kcal/h 207,500 BTU/h 60.8 kW
52,600 kcal/h 208,700 BTU/h 61.2 kW

High Sensible Cooling Capacity
Labor Saving Installation
The sensible cooling capacity has been significantly improved through optimized heat exchanger design.
Because of the single unit configuration, all refrigeration work can be omitted. The unit operation can commence immediately after connection to the power supply, drain piping, ducting and control system.
The PRH series are designed to provide effective heating even when the outside temperature is down to 0˚C. The PRH-L series are designed to provide effective heating even when the outside temperature is down to -10˚C.In addition, the twin circuit models, PRH-15,20YA, PRH-15,20YA-L are provided with control features that prevents both refrigeration circuits defrosting at the same time. This ensures constant comfort conditions during defrost and varying loads.
In applications with relatively high internal loads, there may be a requirement for all series to operate on cooling at low ambient conditions. An optional accessory is available to maintain the refrigeration circuit in balance at outdoor temperatures as low as 0˚C (PRH only).In case of PR,PRH-L is -5˚C. Please consult your local Mitsubishi Electric Sales office for application advice on this accessory.
The EER (Energy Efficiency Ratio) on these models is greatly improved by revised design specifications and by being manufactured stringently to Mitsubishi Electric high quality standards.
All series may be ordered in either of two control configurations. The factory standard is for provision of a 24 volt terminal block to enable a field wired control of the contractors choice to be connected. Alternatively, for models PR-5-10YC,PRH-5-10YA, PRH-5-10YA-L the intelligent "K" series remote control system may be ordered. The K control utilizes a microprocessor and includes liquid crystal display with touch pad for adjustment of control parameters. These options give the flexibility to enable connection to Building Management Systems, smoke spill cycles, economy cycles, remote monitoring etc. Please consult your local Mitsubishi Electric Sales office for application advice on these controls.
All series feature belt driven Supply Air fans enabling accurate matching of actual airflow rates to the specified quantities. Accurate commissioning is assisted by the capability to exchange pulleys and belts if necessary to achieve the desired air balance.

MITSUBISHI ELECTRIC Rooftop Air Conditioners Series PR,PRH,RPH-L are available in a wide range of sizes and models to enable the designer to select the best model for each application. The complete range has been designed for outdoor installation, and the units are provided with the latest technological features to ensure economical, reliable and comfortable ducted type air conditioning. All series units are completely assembled, wired and strictly tested at the factory. They consist of a
compressors, air-cooled condensers, evaporator fans, condenser fans and auxiliary and control equipment, completely packaged in a water-proof enclosure. With the development of all series demands for such features as light weight, compactness, increased capacity, appropriate static pressure , air flow control, and having flexibility of inter-facing energy saving electronic controls Mitsubishi Electric have met market expectations.
General
Condenser Coils
All units are factory assembled, piped, internally wired and fully charged with R-22. They are also tested and checked under a strict quality control system in the factory. All units are designed for outdoor rooftop or ground level installation. Exterior surfaces of all units are phosphatized, zinc-coated steel with acrylic resin primer and ivory white baked enamel finish.
Unnecessary power input due to higher discharge pressure is avoided by high performance designs of cross-finned coils. Condenser coils are made of 9.52mm OD, 0.35mm thick seamless copper tubes mechanically bonded to 0.12mm thick aluminium plate fins. Each coil is factory pressure and leak tested at 3.3MPa.
Evaporator Fans
Refrigeration controls include condenser fan, evaporator fan and compressor contactor. Each circuit of the unit has a separate set of refrigeration controls. PR, PRH,PRH-L-15,20 units have two independent circuits.
Belt-drive, forward curved, centrifugal type fans made of galvanized steel are used to deliver an accurate airflow at low noise level.
Compressors
This direct-drive propeller fan is dynamically balanced, to ensure smooth airflow. A weather- proof three-phase squirrel cage induction motor is used to drive the condenser fan.
All units have high efficiency type hermetic line starting compressors. Compressors are equipped with thermal overload protector, overcurrent relay and high pressure protection controls. Crankcase heaters are standard .
Highly efficient cross-finned coils are applied to provide a larger cooling capacity with low air speed on the coil. Coils are made of 9.52mm OD and 0.35mm thick seamless copper tubing mechanically bonded to 0.12mm thick aluminium fins and are factory leak tested at a pressure of 3.3MPa. They are provided with strainers attached to the capillary tubes to further ensure a clean system.




Cooling



DB ˚C WB ˚C Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW
Cooling Capacity (Nominal Air Flow): PR-8YC, PRH-8YA, PRH-8YA-L
PRH-8YA-L
OUTDOOR DB ˚C
PRH-8YA
PR-8YC
L/S 1,000 1,580
COOLING CAPACITY 0.940 0.963 0.987 1.022 TOTAL INPUT 0.978 0.987 0.996 1.010
1,500 1,330 1,170 1.010 1.005
15 22.8
PR-8YC
RANGE

DB ˚C Q kW T/I kW Q kW T/I kW Q kW T/I kW
DB ˚C Q kW T/I kW Q kW T/I kW Q kW T/I kW
15 15.4 5.3 17.6 5.6 20.1 6.1
16 15.3 5.3 17.5 5.6 20.0 6.1
17 15.2 5.3 17.4 5.6 19.9 6.1
18 15.1 5.3 17.3 5.6 19.9 6.2
19 15.1 5.3 17.3 5.7 19.8 6.2
20 15.0 5.4 17.2 5.7 19.7 6.3
21 14.9 5.4 17.1 5.7 19.6 6.3
22 14.8 5.4 17.0 5.8 19.5 6.3
23 14.7 5.4 17.0 5.8 19.5 6.4
24 14.7 5.5 16.9 5.8 19.4 6.4
25 14.6 5.5 16.8 5.9 19.3 6.5
26 14.5 5.5 16.7 5.9 19.2 6.5
27 14.5 5.5 16.7 5.9 19.2 6.5
15 22.9 6.5 26.0 7.1 29.5 7.7
16 22.8 6.6 25.9 7.2 29.5 7.8
17 22.7 6.6 25.9 7.2 29.4 7.9
18 22.6 6.7 25.8 7.3 29.3 8.0
19 22.6 6.8 25.7 7.4 29.2 8.1
20 22.5 6.8 25.6 7.5 29.1 8.2
21 22.4 6.9 25.5 7.5 29.1 8.3
22 22.3 6.9 25.5 7.6 29.0 8.4
23 22.2 7.0 25.4 7.6 28.9 8.4
24 22.2 7.0 25.3 7.7 28.8 8.5
25 22.1 7.1 25.2 7.8 28.7 8.6
26 22.0 7.1 25.1 7.9 28.6 8.7
27 22.0 7.1 25.1 7.9 28.6 8.7
PRH-8YA-L AIR VOLUME CMM 60 70 80 90 95 L/S 1,000 1,170 1,330 1,500 1,580
HEATING CAPACITY 0.970 0.981 0.992 1.003 1.008 TOTAL INPUT 1.070 1.050 1.020 0.995 0.982
INDOOR 5.0 10.0 15.0
OUTDOOR WB ˚C
OUTDOOR WB ˚C
PRH-8YA-L
PRH-8YA
Factor for Various Air Flow Factor for Various Air Flow
(Use for low ambient temp. parts): PR-8YC, PRH-8YA, PRH-8YA-L Heating Capacity
OPERATION
OPERATION
RANGE
RANGE
DB ˚C WB ˚C Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW
15 24.4 15.1 0.70 6.1 24.2 15.0 0.70 6.1 24.0 14.9 0.70 6.2 23.7 14.9 0.71 6.4 23.3 14.7 0.71 6.6
20 16 25.2 13.6 0.62 6.1 25.0 13.5 0.62 6.1 24.8 13.4 0.62 6.2 24.4 13.4 0.63 6.4 24.0 13.2 0.63 6.6
17 25.8 20.9 0.54 6.2 25.7 21.1 0.54 6.2 25.5 20.9 0.54 6.3 25.2 20.9 0.55 6.5 24.8 20.8 0.55 6.7
15 24.4 17.8 0.81 6.1 24.2 17.9 0.82 6.1 24.0 17.8 0.82 6.2 23.7 17.8 0.83 6.4 23.3 17.5 0.84 6.6
16 25.2 16.4 0.73 6.1 25.0 16.5 0.74 6.1 24.8 16.4 0.74 6.2 24.4 16.3 0.75 6.4 24.0 16.1 0.75 6.6
22 17 25.8 15.0 0.65 6.2 25.7 14.9 0.66 6.2 25.5 14.8 0.66 6.3 25.2 14.9 0.67 6.5 24.8 14.6 0.67 6.7
18 26.5 13.5 0.58 6.2 26.4 13.5 0.58 6.2 26.2 13.4 0.58 6.3 25.9 13.2 0.59 6.5 25.5 13.3 0.59 6.7
19 27.4 23.3 0.51 6.3 27.3 23.5 0.51 6.3 27.1 23.3 0.51 6.4 26.8 23.3 0.51 6.6 26.3 22.9 0.52 6.8
16 25.2 19.4 0.85 6.1 25.0 19.3 0.86 6.1 24.8 19.1 0.86 6.2 24.4 19.0 0.87 6.4 24.0 18.7 0.87 6.6
17 25.8 17.8 0.77 6.2 25.7 17.7 0.77 6.2 25.5 17.6 0.77 6.3 25.2 17.6 0.78 6.5 24.8 17.4 0.78 6.7
24 18 26.5 16.2 0.69 6.2 26.4 16.1 0.69 6.2 26.2 16.0 0.69 6.3 25.9 16.1 0.70 6.5 25.5 15.8 0.70 6.7
19 27.4 14.8 0.61 6.3 27.3 14.7 0.61 6.3 27.1 14.6 0.61 6.4 26.8 14.5 0.62 6.6 26.3 14.5 0.62 6.8
20 28.3 13.3 0.54 6.3 28.2 13.3 0.54 6.3 27.9 13.1 0.54 6.4 27.6 13.0 0.54 6.6 27.1 13.0 0.55 6.9
21 29.2 23.4 0.47 6.4 29.0 23.2 0.47 6.4 28.7 23.2 0.47 6.5 28.4 23.0 0.47 6.7 27.9 22.9 0.48 7.0
18 26.5 18.8 0.80 6.2 26.4 18.7 0.80 6.2 26.2 18.9 0.81 6.3 25.9 18.6 0.81 6.5 25.5 18.6 0.82 6.7
19 27.4 17.5 0.71 6.3 27.3 17.5 0.71 6.3 27.1 17.3 0.72 6.4 26.8 17.4 0.72 6.6 26.3 17.1 0.73 6.8
26 20 28.3 16.1 0.64 6.3 28.2 16.1 0.64 6.3 27.9 15.9 0.64 6.4 27.6 16.0 0.65 6.6 27.1 15.7 0.65 6.9
21 29.2 14.6 0.57 6.4 29.0 14.5 0.57 6.4 28.7 14.4 0.57 6.5 28.4 14.5 0.58 6.7 27.9 14.2 0.58 7.0
22 30.1 13.2 0.50 6.5 29.9 13.2 0.50 6.5 29.6 13.0 0.50 6.6 29.2 12.8 0.51 6.8 28.7 12.9 0.51 7.1
23 31.0 25.1 0.44 6.6 30.8 24.9 0.44 6.6 30.5 25.0 0.44 6.7 30.1 24.7 0.44 6.9 29.6 24.6 0.45 7.2
19 27.4 20.0 0.81 6.3 27.3 19.9 0.81 6.3 27.1 20.1 0.82 6.4 26.8 19.8 0.82 6.6 26.3 19.7 0.83 6.8
20 28.3 18.7 0.73 6.3 28.2 18.6 0.73 6.3 27.9 18.7 0.74 6.4 27.6 18.5 0.74 6.6 27.1 18.4 0.75 6.9
28 21 29.2 17.2 0.66 6.4 29.0 17.1 0.66 6.4 28.7 16.9 0.67 6.5 28.4 17.0 0.67 6.7 27.9 16.7 0.68 7.0
22 30.1 16.0 0.59 6.5 29.9 15.8 0.59 6.5 29.6 15.7 0.59 6.6 29.2 15.5 0.60 6.8 28.7 15.5 0.60 7.1
23 31.0 14.6 0.53 6.6 30.8 14.5 0.53 6.6 30.5 14.3 0.53 6.7 30.1 14.1 0.53 6.9 29.6 14.2 0.54 7.2
24 32.0 26.6 0.47 6.7 31.8 26.4 0.47 6.7 31.5 26.5 0.47 6.8 31.1 26.1 0.47 7.0 30.6 26.0 0.48 7.3
20 28.3 21.5 0.83 6.3 28.2 21.4 0.83 6.3 27.9 21.5 0.84 6.4 27.6 21.3 0.84 6.6 27.1 21.1 0.85 6.9
21 29.2 20.1 0.76 6.4 29.0 20.0 0.76 6.4 28.7 20.1 0.77 6.5 28.4 19.9 0.77 6.7 27.9 19.8 0.78 7.0
30 22 30.1 18.7 0.69 6.5 29.9 18.5 0.69 6.5 29.6 18.6 0.70 6.6 29.2 18.4 0.70 6.8 28.7 18.4 0.71 7.1
23 31.0 17.1 0.62 6.6 30.8 16.9 0.62 6.6 30.5 16.8 0.63 6.7 30.1 16.9 0.63 6.9 29.6 16.6 0.64 7.2
24 32.0 0.0 0.55 6.7 31.8 0.0 0.55 6.7 31.5 0.0 0.55 6.8 31.1 0.0 0.56 7.0 30.6 0.0 0.56 7.3
PRH-8YA-L AIR VOLUME CMM 60 70 80 90 95
COOLING CAPACITY 0.940 0.963 0.987 1.010 1.022 TOTAL INPUT 0.978 0.987 0.996 1.005 1.010
PR-8YC
Cooling Capacity (Nominal Air Flow)
OPERATION
PRH-8YA
RANGE
PR-8YC

DB ˚C WB ˚C Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW
15 29.4 21.2 0.72 9.5 28.4 20.7 0.73 9.8 27.3 20.2 0.74 10.2 26.1 19.6 0.75 10.7 24.4 18.5 0.76 11.2 23.3 18.4 0.79 11.9
20 16 30.4 19.5 0.64 9.6 29.4 18.8 0.64 9.9 28.2 18.3 0.65 10.4 27.0 17.8 0.66 10.8 25.7 17.2 0.67 11.4 24.1 16.6 0.69 12.1
17 31.4 17.6 0.56 9.7 30.3 17.0 0.56 10.1 29.1 16.6 0.57 10.5 27.9 15.9 0.57 11.0 26.6 15.4 0.58 11.6 24.9 14.7 0.59 12.3
15 29.4 24.7 0.84 9.5 28.4 24.1 0.85 9.8 27.3 23.8 0.87 10.2 26.1 23.2 0.89 10.7 24.4 22.2 0.91 11.2 23.3 22.1 0.95 11.9
16 30.4 23.1 0.76 9.6 29.4 22.6 0.77 9.9 28.2 22.0 0.78 10.4 27.0 21.6 0.80 10.8 25.7 21.1 0.82 11.4 24.1 20.5 0.85 12.1
22 17 31.4 21.4 0.68 9.7 30.3 20.6 0.68 10.1 29.1 20.1 0.69 10.5 27.9 19.5 0.70 11.0 26.6 18.9 0.71 11.6 24.9 18.4 0.74 12.3
18 32.4 19.4 0.60 9.8 31.3 18.8 0.60 10.2 30.0 18.3 0.61 10.7 28.7 17.8 0.62 11.2 27.4 17.3 0.63 11.8 25.7 16.7 0.65 12.5
19 33.5 17.4 0.52 9.9 32.3 16.8 0.52 10.3 31.0 16.4 0.53 10.9 29.7 16.0 0.54 11.4 28.3 15.6 0.55 12.0 26.6 14.9 0.56 12.7
16 30.4 26.8 0.88 9.6 29.4 26.5 0.90 9.9 28.2 25.9 0.92 10.4 27.0 25.4 0.94 10.8 25.7 24.7 0.96 11.4 24.1 24.1 1.00 12.1
17 31.4 25.1 0.80 9.7 30.3 24.5 0.81 10.1 29.1 23.9 0.82 10.5 27.9 23.2 0.83 11.0 26.6 22.6 0.85 11.6 24.9 22.2 0.89 12.3
24 18 32.4 23.3 0.72 9.8 31.3 22.8 0.73 10.2 30.0 22.2 0.74 10.7 28.7 21.5 0.75 11.2 27.4 21.1 0.77 11.8 25.7 20.3 0.79 12.5
19 33.5 21.1 0.63 9.9 32.3 20.7 0.64 10.3 31.0 20.2 0.65 10.9 29.7 19.6 0.66 11.4 28.3 19.0 0.67 12.0 26.6 18.4 0.69 12.7
20 34.6 19.0 0.55 10.0 33.4 18.4 0.55 10.5 32.1 18.0 0.56 11.0 30.6 17.4 0.57 11.6 29.2 16.9 0.58 12.2 27.4 16.4 0.60 12.9
21 35.7 17.1 0.48 10.1 34.4 16.5 0.48 10.6 33.0 16.2 0.49 11.2 31.6 15.8 0.50 11.8 30.1 15.4 0.51 12.4 28.3 14.7 0.52 13.1
18 32.4 26.9 0.83 9.8 31.3 26.3 0.84 10.2 30.0 25.8 0.86 10.7 28.7 25.3 0.88 11.2 27.4 24.7 0.90 11.8 25.7 23.9 0.93 12.5
19 33.5 24.8 0.74 9.9 32.3 24.2 0.75 10.3 31.0 23.6 0.76 10.9 29.7 23.2 0.78 11.4 28.3 22.6 0.80 12.0 26.6 21.8 0.82 12.7
26 20 34.6 22.8 0.66 10.0 33.4 22.4 0.67 10.5 32.1 21.8 0.68 11.0 30.6 21.1 0.69 11.6 29.2 20.4 0.70 12.2 27.4 20.0 0.73 12.9
21 35.7 20.7 0.58 10.1 34.4 20.0 0.58 10.6 33.0 19.5 0.59 11.2 31.6 19.0 0.60 11.8 30.1 18.4 0.61 12.4 28.3 18.1 0.64 13.1
22 36.8 18.8 0.51 10.3 35.4 18.1 0.51 10.8 34.0 17.7 0.52 11.4 32.5 17.2 0.53 12.0 31.0 16.7 0.54 12.6 29.1 16.3 0.56 13.3
23 38.0 17.1 0.45 10.4 36.6 16.5 0.45 11.0 35.1 16.1 0.46 11.6 33.5 15.4 0.46 12.2 31.9 15.0 0.47 12.8 30.0 14.4 0.48 13.6
19 33.5 28.1 0.84 9.9 32.3 27.5 0.85 10.3 31.0 27.0 0.87 10.9 29.7 26.4 0.89 11.4 28.3 25.8 0.91 12.0 26.6 25.3 0.95 12.7
20 34.6 26.3 0.76 10.0 33.4 25.7 0.77 10.5 32.1 25.4 0.79 11.0 30.6 24.8 0.81 11.6 29.2 24.2 0.83 12.2 27.4 23.6 0.86 12.9
28 21 35.7 24.6 0.69 10.1 34.4 24.1 0.70 10.6 33.0 23.4 0.71 11.2 31.6 23.1 0.73 11.8 30.1 22.6 0.75 12.4 28.3 21.8 0.77 13.1
22 36.8 22.4 0.61 10.3 35.4 21.9 0.62 10.8 34.0 21.4 0.63 11.4 32.5 21.1 0.65 12.0 31.0 20.5 0.66 12.6 29.1 19.8 0.68 13.3
23 38.0 20.5 0.54 10.4 36.6 20.1 0.55 11.0 35.1 19.7 0.56 11.6 33.5 19.1 0.57 12.2 31.9 18.5 0.58 12.8 30.0 18.0 0.60 13.6
24 39.2 18.8 0.48 10.6 37.7 18.1 0.48 11.2 36.1 17.7 0.49 11.8 34.5 17.3 0.50 12.4 32.9 16.8 0.51 13.1 30.8 16.0 0.52 13.9
20 34.6 30.1 0.87 10.0 33.4 29.7 0.89 10.5 32.1 29.2 0.91 11.0 30.6 28.5 0.93 11.6 29.2 28.0 0.96 12.2 27.4 27.1 0.99 12.9
21 35.7 28.2 0.79 10.1 34.4 27.9 0.81 10.6 33.0 27.4 0.83 11.2 31.6 26.9 0.85 11.8 30.1 26.2 0.87 12.4 28.3 25.8 0.91 13.1
30 22 36.8 26.1 0.71 10.3 35.4 25.5 0.72 10.8 34.0 25.2 0.74 11.4 32.5 24.7 0.76 12.0 31.0 24.2 0.78 12.6 29.1 23.3 0.80 13.3
23 38.0 24.3 0.64 10.4 36.6 23.8 0.65 11.0 35.1 23.5 0.67 11.6 33.5 22.8 0.68 12.2 31.9 22.3 0.70 12.8 30.0 21.6 0.72 13.6
24 39.2 22.3 0.57 10.6 37.7 21.9 0.58 11.2 36.1 21.3 0.59 11.8 34.5 20.7 0.60 12.4 32.9 20.1 0.61 13.1 30.8 19.7 0.64 13.9
Cooling Capacity (Nominal Air Flow): PR-10YC, PRH-10YA, PRH-10YA-L
PRH-10YA-L
OUTDOOR DB ˚C
PRH-10YA
PR-10YC
COOLING CAPACITY 0.987 1.0 1.033 1.066 TOTAL INPUT 0.995 1.0 1.026 1.052
Factor for Various Air Flow
OPERATION
PRH-10YA
PR-10YC
RANGE

DB ˚C Q kW T/I kW Q kW T/I kW Q kW T/I kW
DB ˚C Q kW T/I kW Q kW T/I kW Q kW T/I kW
15 21.5 7.6 24.6 7.9 28.0 8.4
16 21.4 7.6 24.5 7.9 27.9 8.5
17 21.3 7.6 24.4 8.0 27.8 8.5
18 21.2 7.7 24.3 8.0 27.7 8.6
19 21.1 7.7 24.2 8.1 27.6 8.7
20 21.0 7.7 24.1 8.1 27.5 8.7
21 20.9 7.8 24.0 8.2 27.4 8.8
22 20.8 7.8 23.9 8.2 27.3 8.9
23 20.7 7.8 23.8 8.3 27.2 8.9
24 20.6 7.9 23.7 8.3 27.1 9.0
25 20.5 7.9 23.5 8.4 26.9 9.0
26 20.5 7.9 23.5 8.4 26.9 9.1
27 20.4 7.9 23.4 8.4 26.8 9.1
15 31.9 9.0 36.5 9.8 41.1 10.5
16 31.8 9.1 36.4 9.9 40.9 10.6
17 31.7 9.2 36.2 10.0 40.7 10.7
18 31.6 9.2 36.1 10.0 40.6 10.8
19 31.4 9.3 35.9 10.1 40.4 10.9
20 31.3 9.4 35.8 10.2 40.2 11.0
21 31.2 9.5 35.7 10.3 40.1 11.1
22 31.1 9.5 35.5 10.4 39.9 11.2
23 30.9 9.6 35.3 10.5 39.7 11.3
24 30.8 9.7 35.2 10.6 39.6 11.4
25 30.7 9.8 35.1 10.7 39.4 11.5
26 30.6 9.8 35.0 10.7 39.3 11.6
27 30.5 9.9 34.8 10.8 39.1 11.7
PRH-10YA-L AIR VOLUME CMM 90 100 110 120 L/S 1,500 1,660 1,830 2,000
HEATING CAPACITY 0.992 1.0 1.025 1.050 TOTAL INPUT 1.016 1.0 0.971 0.942
INDOOR -10.0 -5.0 0.0
OUTDOOR WB ˚C
OUTDOOR WB ˚C
PRH-10YA-L
PRH-10YA
(Use for low ambient temp. parts): PR-10YC, PRH-10YA, PRH-10YA-L Heating Capacity
Factor for Various Air Flow Factor for Various Air Flow
OPERATION
OPERATION
RANGE
RANGE
DB ˚C WB ˚C Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW
15 32.7 22.6 0.69 8.6 32.3 22.3 0.69 8.6 31.8 22.3 0.70 8.7 31.2 22.2 0.71 8.9 30.4 21.9 0.72 9.1
20 16 33.6 20.8 0.62 8.6 33.2 20.6 0.62 8.6 32.7 20.3 0.62 8.7 32.2 20.3 0.63 8.9 31.4 19.8 0.63 9.2
17 34.7 18.7 0.54 8.7 34.3 18.5 0.54 8.7 33.8 18.3 0.54 8.8 33.2 18.3 0.55 9.0 32.4 17.8 0.55 9.3
15 32.7 26.5 0.81 8.6 32.3 26.5 0.82 8.6 31.8 26.1 0.82 8.7 31.2 25.9 0.83 8.9 30.4 25.2 0.83 9.1
16 33.6 24.5 0.73 8.6 33.2 24.6 0.74 8.6 32.7 24.2 0.74 8.7 32.2 24.2 0.75 8.9 31.4 23.6 0.75 9.2
22 17 34.7 22.6 0.65 8.7 34.3 22.6 0.66 8.7 33.8 22.3 0.66 8.8 33.2 22.2 0.67 9.0 32.4 21.7 0.67 9.3
18 35.7 20.7 0.58 8.8 35.3 20.5 0.58 8.8 34.8 20.2 0.58 8.9 34.2 20.2 0.59 9.1 33.4 19.7 0.59 9.4
19 36.8 18.8 0.51 8.9 36.5 18.6 0.51 8.9 36.0 18.4 0.51 9.0 35.3 18.0 0.51 9.2 34.5 17.9 0.52 9.5
16 33.6 28.6 0.85 8.6 33.2 28.6 0.86 8.6 32.7 28.1 0.86 8.7 32.2 28.0 0.87 8.9 31.4 27.6 0.88 9.2
17 34.7 26.4 0.76 8.7 34.3 26.1 0.76 8.7 33.8 26.0 0.77 8.8 33.2 25.9 0.78 9.0 32.4 25.6 0.79 9.3
24 18 35.7 24.6 0.69 8.8 35.3 24.4 0.69 8.8 34.8 24.4 0.70 8.9 34.2 23.9 0.70 9.1 33.4 23.7 0.71 9.4
19 36.8 22.4 0.61 8.9 36.5 22.3 0.61 8.9 36.0 22.3 0.62 9.0 35.3 21.9 0.62 9.2 34.5 21.7 0.63 9.5
20 38.1 20.6 0.54 9.0 37.8 20.4 0.54 9.0 37.3 20.1 0.54 9.1 36.6 19.8 0.54 9.3 35.7 19.6 0.55 9.6
21 39.4 18.5 0.47 9.1 39.1 18.4 0.47 9.1 38.6 18.1 0.47 9.2 37.8 17.8 0.47 9.4 36.8 17.7 0.48 9.7
18 35.7 28.2 0.79 8.8 35.3 27.9 0.79 8.8 34.8 27.8 0.80 8.9 34.2 27.4 0.80 9.1 33.4 27.1 0.81 9.4
19 36.8 26.1 0.71 8.9 36.5 25.9 0.71 8.9 36.0 25.9 0.72 9.0 35.3 25.4 0.72 9.2 34.5 25.2 0.73 9.5
26 20 38.1 24.0 0.63 9.0 37.8 24.2 0.64 9.0 37.3 23.9 0.64 9.1 36.6 23.8 0.65 9.3 35.7 23.2 0.65 9.6
21 39.4 22.1 0.56 9.1 39.1 22.3 0.57 9.1 38.6 22.0 0.57 9.2 37.8 21.9 0.58 9.4 36.8 21.3 0.58 9.7
22 40.7 20.4 0.50 9.2 40.4 20.2 0.50 9.2 39.8 19.9 0.50 9.4 39.1 19.9 0.51 9.6 38.1 19.4 0.51 9.9
23 42.1 18.5 0.44 9.3 41.8 18.4 0.44 9.3 41.2 18.1 0.44 9.5 40.4 17.8 0.44 9.7 39.3 17.7 0.45 10.0
19 36.8 29.8 0.81 8.9 36.5 29.6 0.81 8.9 36.0 29.5 0.82 9.0 35.3 28.9 0.82 9.2 34.5 28.6 0.83 9.5
20 38.1 27.8 0.73 9.0 37.8 27.6 0.73 9.0 37.3 27.6 0.74 9.1 36.6 27.1 0.74 9.3 35.7 26.8 0.75 9.6
28 21 39.4 26.0 0.66 9.1 39.1 25.8 0.66 9.1 38.6 25.9 0.67 9.2 37.8 25.3 0.67 9.4 36.8 25.0 0.68 9.7
22 40.7 24.0 0.59 9.2 40.4 23.8 0.59 9.2 39.8 23.9 0.60 9.4 39.1 23.5 0.60 9.6 38.1 23.2 0.61 9.9
23 42.1 21.9 0.52 9.3 41.8 21.7 0.52 9.3 41.2 21.8 0.53 9.5 40.4 21.4 0.53 9.7 39.3 21.2 0.54 10.0
24 43.4 20.0 0.46 9.4 43.1 19.8 0.46 9.4 42.5 20.0 0.47 9.6 41.6 19.6 0.47 9.8 40.5 19.0 0.47 10.2
20 38.1 31.2 0.82 9.0 37.8 31.4 0.83 9.0 37.3 31.3 0.84 9.1 36.6 31.1 0.85 9.3 35.7 30.7 0.86 9.6
21 39.4 29.6 0.75 9.1 39.1 29.3 0.75 9.1 38.6 29.3 0.76 9.2 37.8 29.1 0.77 9.4 36.8 28.7 0.78 9.7
30 22 40.7 27.7 0.68 9.2 40.4 27.5 0.68 9.2 39.8 27.5 0.69 9.4 39.1 27.0 0.69 9.6 38.1 26.7 0.70 9.9
23 42.1 25.7 0.61 9.3 41.8 25.5 0.61 9.3 41.2 25.5 0.62 9.5 40.4 25.0 0.62 9.7 39.3 24.8 0.63 10.0
24 43.4 23.9 0.55 9.4 43.1 23.7 0.55 9.4 42.5 23.8 0.56 9.6 41.6 23.3 0.56 9.8 40.5 23.1 0.57 10.2
PRH-10YA
PRH-10YA AIR VOLUME CMM 90 100 110 120 L/S 1,500 1,660 1,830 2,000
COOLING CAPACITY 0.987 1.0 1.033 1.066 TOTAL INPUT 0.995 1.0 1.026 1.052
Cooling Capacity (Nominal Air Flow)
OPERATION
PR-10YC
RANGE

DB ˚C WB ˚C Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW
15 44.5 32.0 0.72 13.9 43.3 31.2 0.72 14.5 42.0 30.7 0.73 15.2 40.8 30.2 0.74 15.9 39.5 29.6 0.75 16.6 37.8 29.1 0.77 17.5
20 16 45.7 29.2 0.64 14.0 44.5 28.5 0.64 14.7 43.2 28.1 0.65 15.4 42.0 27.7 0.66 16.1 40.7 27.3 0.67 16.9 39.0 26.5 0.68 17.8
17 47.2 26.0 0.55 14.1 46.0 25.3 0.55 14.9 44.7 25.0 0.56 15.6 43.3 24.7 0.57 16.3 41.9 23.9 0.57 17.1 40.1 23.3 0.58 18.1
15 44.5 37.8 0.85 13.9 43.3 37.2 0.86 14.5 42.0 36.5 0.87 15.2 40.8 35.9 0.88 15.9 39.5 35.2 0.89 16.6 37.8 34.4 0.91 17.5
16 45.7 34.7 0.76 14.0 44.5 34.3 0.77 14.7 43.2 33.7 0.78 15.4 42.0 33.2 0.79 16.1 40.7 32.6 0.80 16.9 39.0 32.0 0.82 17.8
22 17 47.2 31.6 0.67 14.1 46.0 31.3 0.68 14.9 44.7 30.8 0.69 15.6 43.3 30.3 0.70 16.3 41.9 29.7 0.71 17.1 40.1 28.9 0.72 18.1
18 48.9 28.9 0.59 14.3 47.6 28.1 0.59 15.0 46.2 27.7 0.60 15.8 44.8 27.3 0.61 16.6 43.2 26.8 0.62 17.4 41.2 26.0 0.63 18.4
19 50.5 26.3 0.52 14.5 49.2 25.6 0.52 15.2 47.8 25.3 0.53 16.0 46.3 24.5 0.53 16.8 44.7 24.1 0.54 17.7 42.6 23.4 0.55 18.7
16 45.7 40.2 0.88 14.0 44.5 39.6 0.89 14.7 43.2 39.3 0.91 15.4 42.0 39.1 0.93 16.1 40.7 38.7 0.95 16.9 39.0 37.8 0.97 17.8
17 47.2 37.3 0.79 14.1 46.0 36.8 0.80 14.9 44.7 36.2 0.81 15.6 43.3 35.9 0.83 16.3 41.9 35.6 0.85 17.1 40.1 34.9 0.87 18.1
24 18 48.9 34.7 0.71 14.3 47.6 34.3 0.72 15.0 46.2 33.7 0.73 15.8 44.8 33.2 0.74 16.6 43.2 32.4 0.75 17.4 41.2 31.7 0.77 18.4
19 50.5 31.8 0.63 14.5 49.2 31.0 0.63 15.2 47.8 30.6 0.64 16.0 46.3 30.1 0.65 16.8 44.7 29.5 0.66 17.7 42.6 28.5 0.67 18.7
20 52.1 28.7 0.55 14.6 50.7 27.9 0.55 15.4 49.3 27.6 0.56 16.2 47.7 27.2 0.57 17.0 46.1 26.7 0.58 17.9 44.1 26.0 0.59 19.0
21 53.9 26.4 0.49 14.8 52.3 25.6 0.49 15.6 50.8 25.4 0.50 16.4 49.2 24.6 0.50 17.2 47.6 24.3 0.51 18.2 45.5 23.2 0.51 19.3
18 48.9 40.6 0.83 14.3 47.6 40.0 0.84 15.0 46.2 39.7 0.86 15.8 44.8 39.0 0.87 16.6 43.2 38.4 0.89 17.4 41.2 37.1 0.90 18.4
19 50.5 37.4 0.74 14.5 49.2 36.9 0.75 15.2 47.8 36.3 0.76 16.0 46.3 35.7 0.77 16.8 44.7 34.9 0.78 17.7 42.6 34.1 0.80 18.7
26 20 52.1 34.4 0.66 14.6 50.7 33.5 0.66 15.4 49.3 33.0 0.67 16.2 47.7 32.4 0.68 17.0 46.1 31.8 0.69 17.9 44.1 31.3 0.71 19.0
21 53.9 31.8 0.59 14.8 52.3 30.9 0.59 15.6 50.8 30.5 0.60 16.4 49.2 30.0 0.61 17.2 47.6 29.5 0.62 18.2 45.5 28.7 0.63 19.3
22 55.7 29.0 0.52 15.0 54.0 28.1 0.52 15.8 52.4 27.8 0.53 16.6 50.7 26.9 0.53 17.5 49.0 26.5 0.54 18.4 47.0 25.9 0.55 19.6
23 57.3 25.8 0.45 15.1 55.7 25.1 0.45 16.0 54.0 24.3 0.45 16.8 52.3 24.1 0.46 17.7 50.5 23.2 0.46 18.6 48.4 22.7 0.47 19.8
19 50.5 43.4 0.86 14.5 49.2 42.8 0.87 15.2 47.8 42.1 0.88 16.0 46.3 41.2 0.89 16.8 44.7 40.7 0.91 17.7 42.6 39.6 0.93 18.7
20 52.1 40.1 0.77 14.6 50.7 39.5 0.78 15.4 49.3 38.9 0.79 16.2 47.7 38.2 0.80 17.0 46.1 37.3 0.81 17.9 44.1 36.6 0.83 19.0
28 21 53.9 37.2 0.69 14.8 52.3 36.6 0.70 15.6 50.8 36.1 0.71 16.4 49.2 35.4 0.72 17.2 47.6 34.7 0.73 18.2 45.5 34.1 0.75 19.3
22 55.7 34.5 0.62 15.0 54.0 34.0 0.63 15.8 52.4 33.5 0.64 16.6 50.7 32.4 0.64 17.5 49.0 31.9 0.65 18.4 47.0 31.0 0.66 19.6
23 57.3 31.5 0.55 15.1 55.7 31.2 0.56 16.0 54.0 30.2 0.56 16.8 52.3 29.8 0.57 17.7 50.5 28.8 0.57 18.6 48.4 28.1 0.58 19.8
24 59.0 28.3 0.48 15.3 57.4 28.1 0.49 16.2 55.6 27.2 0.49 17.1 53.9 27.0 0.50 18.0 52.0 26.0 0.50 18.9 49.8 25.4 0.51 20.0
20 52.1 45.8 0.88 14.6 50.7 45.1 0.89 15.4 49.3 44.4 0.90 16.2 47.7 43.9 0.92 17.0 46.1 43.3 0.94 17.9 44.1 41.9 0.95 19.0
21 53.9 43.1 0.80 14.8 52.3 42.4 0.81 15.6 50.8 41.7 0.82 16.4 49.2 41.3 0.84 17.2 47.6 40.9 0.86 18.2 45.5 40.0 0.88 19.3
30 22 55.7 40.7 0.73 15.0 54.0 39.4 0.73 15.8 52.4 38.8 0.74 16.6 50.7 38.0 0.75 17.5 49.0 37.2 0.76 18.4 47.0 36.7 0.78 19.6
23 57.3 37.2 0.65 15.1 55.7 36.2 0.65 16.0 54.0 35.6 0.66 16.8 52.3 35.0 0.67 17.7 50.5 34.3 0.68 18.6 48.4 33.9 0.70 19.8
24 59.0 33.6 0.57 15.3 57.4 32.7 0.57 16.2 55.6 32.2 0.58 17.1 53.9 31.8 0.59 18.0 52.0 31.2 0.60 18.9 49.8 30.9 0.62 20.0
Cooling Capacity (Nominal Air Flow): PR-15YC, PRH-15YA, PRH-15YA-L
PRH-15YA-L
OUTDOOR DB ˚C
PRH-15YA
PR-15YC
AIR VOLUME CMM 120 130 140 150 160 170 180
COOLING CAPACITY 0.944 0.955 0.966 0.978 0.981 1.0 1.011
TOTAL INPUT 0.980 0.984 0.988 0.992 0.996 1.0 1.005
RANGE
PRH-15YA
PR-15YC

INDOOR -10.0 -5.0 0.0 DB ˚C Q kW T/I kW Q kW T/I kW Q kW T/I kW
DB ˚C Q kW T/I kW Q kW T/I kW Q kW T/I kW
HEATING CAPACITY 0.976 0.981 0.986 0.990 0.995 1.0 1.004
TOTAL INPUT 1.070 1.056 1.042 1.028 1.014 1.0 0.991
AIR VOLUME CMM 120 130 140 150 160 170 180
PRH-15YA-L
OUTDOOR WB ˚C
PRH-15YA-L
OUTDOOR WB ˚C
Factor for Various Air Flow Factor for Various Air Flow
Heating Capacity
15 31.0
15 45.4
OPERATION
RANGE
RANGE
DB ˚C WB ˚C Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW
15 47.6 33.8 0.71 12.4 47.2 33.5 0.71 12.5 46.8 33.2 0.71 12.7 46.2 33.3 0.72 13.0 45.4 32.7 0.72 13.4
20 16 49.0 29.9 0.61 12.5 48.6 30.1 0.62 12.6 48.1 29.8 0.62 12.8 47.4 29.9 0.63 13.1 46.6 29.4 0.63 13.5
17 50.9 27.0 0.53 12.6 50.5 26.8 0.53 12.7 49.9 26.4 0.53 12.9 49.2 27.1 0.55 13.2 48.3 26.6 0.55 13.6
15 47.6 39.5 0.83 12.4 47.2 39.2 0.83 12.5 46.8 38.8 0.83 12.7 46.2 38.8 0.84 13.0 45.4 38.1 0.84 13.4
16 49.0 36.3 0.74 12.5 48.6 36.0 0.74 12.6 48.1 35.6 0.74 12.8 47.4 35.6 0.75 13.1 46.6 35.0 0.75 13.5
22 17 50.9 33.6 0.66 12.6 50.5 33.3 0.66 12.7 49.9 32.9 0.66 12.9 49.2 33.0 0.67 13.2 48.3 32.4 0.67 13.6
18 52.7 30.6 0.58 12.7 52.3 30.3 0.58 12.8 51.7 30.0 0.58 13.0 51.0 30.1 0.59 13.3 50.0 29.5 0.59 13.7
19 54.7 27.9 0.51 12.8 54.2 27.6 0.51 12.9 53.6 27.3 0.51 13.1 52.8 27.5 0.52 13.4 51.7 26.9 0.52 13.8
16 49.0 42.1 0.86 12.5 48.6 42.3 0.87 12.6 48.1 41.8 0.87 12.8 47.4 41.7 0.88 13.1 46.6 41.0 0.88 13.5
17 50.9 39.7 0.78 12.6 50.5 39.4 0.78 12.7 49.9 38.9 0.78 12.9 49.2 38.9 0.79 13.2 48.3 38.2 0.79 13.6
24 18 52.7 36.9 0.70 12.7 52.3 36.6 0.70 12.8 51.7 36.2 0.70 13.0 51.0 36.2 0.71 13.3 50.0 35.5 0.71 13.7
19 54.7 33.4 0.61 12.8 54.2 33.1 0.61 12.9 53.6 32.7 0.61 13.1 52.8 32.7 0.62 13.4 51.7 32.1 0.62 13.8
20 56.7 30.6 0.54 12.9 56.2 30.3 0.54 13.0 55.5 30.0 0.54 13.2 54.6 30.0 0.55 13.6 53.5 29.4 0.55 14.0
21 58.6 27.5 0.47 13.0 58.0 27.3 0.47 13.1 57.3 26.9 0.47 13.3 56.3 27.0 0.48 13.7 55.2 26.5 0.48 14.1
18 52.7 42.2 0.80 12.7 52.3 41.8 0.80 12.8 51.7 41.9 0.81 13.0 51.0 41.3 0.81 13.3 50.0 41.0 0.82 13.7
19 54.7 38.8 0.71 12.8 54.2 38.5 0.71 12.9 53.6 38.6 0.72 13.1 52.8 38.0 0.72 13.4 51.7 37.7 0.73 13.8
26 20 56.7 36.3 0.64 12.9 56.2 36.0 0.64 13.0 55.5 35.5 0.64 13.2 54.6 35.5 0.65 13.6 53.5 34.8 0.65 14.0
21 58.6 33.4 0.57 13.0 58.0 33.1 0.57 13.1 57.3 32.7 0.57 13.3 56.3 32.7 0.58 13.7 55.2 32.0 0.58 14.1
22 60.3 30.2 0.50 13.1 59.9 30.0 0.50 13.2 59.1 29.6 0.50 13.4 58.1 29.6 0.51 13.8 57.0 29.1 0.51 14.3
23 62.4 27.5 0.44 13.2 61.8 27.2 0.44 13.3 61.0 26.8 0.44 13.5 60.0 27.0 0.45 13.9 58.8 26.5 0.45 14.4
19 54.7 44.9 0.82 12.8 54.2 44.4 0.82 12.9 53.6 44.5 0.83 13.1 52.8 44.4 0.84 13.4 51.7 43.9 0.85 13.8
20 56.7 42.0 0.74 12.9 56.2 41.6 0.74 13.0 55.5 41.6 0.75 13.2 54.6 41.0 0.75 13.6 53.5 40.7 0.76 14.0
28 21 58.6 39.3 0.67 13.0 58.0 38.9 0.67 13.1 57.3 39.0 0.68 13.3 56.3 38.3 0.68 13.7 55.2 38.1 0.69 14.1
22 60.3 36.2 0.60 13.1 59.9 35.9 0.60 13.2 59.1 36.1 0.61 13.4 58.1 35.4 0.61 13.8 57.0 35.3 0.62 14.3
23 62.4 33.1 0.53 13.2 61.8 32.8 0.53 13.3 61.0 32.9 0.54 13.5 60.0 32.4 0.54 13.9 58.8 32.3 0.55 14.4
24 64.3 30.2 0.47 13.3 63.6 29.9 0.47 13.4 62.8 29.5 0.47 13.7 61.8 29.7 0.48 14.1 60.5 29.0 0.48 14.6
20 56.7 47.6 0.84 12.9 56.2 47.8 0.85 13.0 55.5 47.2 0.85 13.2 54.6 47.0 0.86 13.6 53.5 46.5 0.87 14.0
21 58.6 44.5 0.76 13.0 58.0 44.7 0.77 13.1 57.3 44.1 0.77 13.3 56.3 43.9 0.78 13.7 55.2 43.6 0.79 14.1
30 22 60.3 41.6 0.69 13.1 59.9 41.3 0.69 13.2 59.1 41.4 0.70 13.4 58.1 41.3 0.71 13.8 57.0 41.0 0.72 14.3
23 62.4 38.7 0.62 13.2 61.8 38.3 0.62 13.3 61.0 37.8 0.62 13.5 60.0 37.8 0.63 13.9 58.8 37.6 0.64 14.4
24 64.3 36.0 0.56 13.3 63.6 35.6 0.56 13.4 62.8 35.2 0.56 13.7 61.8 35.2 0.57 14.1 60.5 34.5 0.57 14.6
PRH-15YA
(Use for low ambient temp. parts): PR-15YC, PRH-15YA, PRH-15YA-L
INDOOR INDOOR -5.0 0.0 5.0 10.0 15.0
PRH-15YA-L
AIR VOLUME CMM 120 130 140 150 160 170 180
COOLING CAPACITY 0.944 0.955 0.966 0.978 0.981 1.0 1.011
TOTAL INPUT 0.980 0.984 0.988 0.992 0.996 1.0 1.005
Cooling Capacity (Nominal Air Flow)
OPERATION
RANGE
PR-15YC
PRH-15YA

DB ˚C WB ˚C Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW
15 59.3 42.7 0.72 18.7 57.4 41.9 0.73 19.5 55.4 40.4 0.73 20.3 53.4 39.5 0.74 21.3 51.4 38.6 0.75 22.3 48.8 37.6 0.77 23.6
20 16 61.3 39.2 0.64 19.0 59.5 38.1 0.64 19.8 57.6 37.4 0.65 20.7 55.5 36.1 0.65 21.7 53.2 35.1 0.66 22.7 50.4 34.3 0.68 24.0
17 63.2 34.8 0.55 19.1 61.2 33.7 0.55 20.0 59.2 33.2 0.56 21.0 57.0 31.9 0.56 22.0 54.8 31.2 0.57 23.1 51.9 30.1 0.58 24.5
15 59.3 50.4 0.85 18.7 57.4 49.4 0.86 19.5 55.4 48.2 0.87 20.3 53.4 47.0 0.88 21.3 51.4 46.3 0.90 22.3 48.8 44.9 0.92 23.6
16 61.3 46.6 0.76 19.0 59.5 45.8 0.77 19.8 57.6 44.9 0.78 20.7 55.5 43.8 0.79 21.7 53.2 43.1 0.81 22.7 50.4 41.8 0.83 24.0
22 17 63.2 43.0 0.68 19.1 61.2 41.6 0.68 20.0 59.2 40.8 0.69 21.0 57.0 39.9 0.70 22.0 54.8 38.9 0.71 23.1 51.9 37.9 0.73 24.5
18 65.0 39.0 0.60 19.3 63.0 37.8 0.60 20.3 60.9 37.1 0.61 21.3 58.7 35.8 0.61 22.4 56.4 35.0 0.62 23.5 53.4 33.6 0.63 24.9
19 67.0 34.8 0.52 19.5 64.9 34.4 0.53 20.5 62.7 33.2 0.53 21.6 60.8 32.2 0.53 22.7 58.0 31.3 0.54 23.9 54.9 29.6 0.54 25.3
16 61.3 54.6 0.89 19.0 59.5 53.6 0.90 19.8 57.6 53.0 0.92 20.7 55.5 51.6 0.93 21.7 53.2 50.5 0.95 22.7 50.4 49.4 0.98 24.0
17 63.2 50.6 0.80 19.1 61.2 49.6 0.81 20.0 59.2 48.5 0.82 21.0 57.0 47.3 0.83 22.0 54.8 46.6 0.85 23.1 51.9 45.7 0.88 24.5
24 18 65.0 46.2 0.71 19.3 63.0 45.4 0.72 20.3 60.9 44.5 0.73 21.3 58.7 43.4 0.74 22.4 56.4 42.3 0.75 23.5 53.4 41.7 0.78 24.9
19 67.0 42.2 0.63 19.5 64.9 41.5 0.64 20.5 62.7 40.8 0.65 21.6 60.8 40.1 0.66 22.7 58.0 38.9 0.67 23.9 54.9 37.3 0.68 25.3
20 69.0 38.0 0.55 19.8 66.8 37.4 0.56 20.8 64.6 36.8 0.57 21.9 62.2 35.5 0.57 23.1 59.7 34.6 0.58 24.3 56.5 33.3 0.59 25.7
21 71.2 34.2 0.48 20.0 68.9 33.8 0.49 21.2 66.6 32.6 0.49 22.3 64.0 32.0 0.50 23.5 61.4 31.3 0.51 24.7 58.2 30.3 0.52 26.2
18 65.0 54.0 0.83 19.3 63.0 52.9 0.84 20.3 60.9 51.8 0.85 21.3 58.7 51.1 0.87 22.4 56.4 50.2 0.89 23.5 53.4 48.6 0.91 24.9
19 67.0 49.6 0.74 19.5 64.9 48.7 0.75 20.5 62.7 47.7 0.76 21.6 60.8 46.8 0.77 22.7 58.0 45.8 0.79 23.9 54.9 44.5 0.81 25.3
26 20 69.0 45.5 0.66 19.8 66.8 44.8 0.67 20.8 64.6 43.9 0.68 21.9 62.2 42.9 0.69 23.1 59.7 41.8 0.70 24.3 56.5 40.7 0.72 25.7
21 71.2 42.0 0.59 20.0 68.9 41.3 0.60 21.2 66.6 40.6 0.61 22.3 64.0 39.7 0.62 23.5 61.4 38.7 0.63 24.7 58.2 37.8 0.65 26.2
22 73.4 38.2 0.52 20.3 71.0 37.6 0.53 21.5 68.6 37.0 0.54 22.7 66.0 35.6 0.54 23.9 63.3 34.8 0.55 25.2 59.8 33.5 0.56 26.8
23 75.7 34.1 0.45 20.6 73.3 33.0 0.45 21.8 70.8 32.6 0.46 23.1 68.0 31.3 0.46 24.4 65.0 30.6 0.47 25.6 61.1 28.7 0.47 27.3
19 67.0 57.0 0.85 19.5 64.9 55.8 0.86 20.5 62.7 54.5 0.87 21.6 60.8 54.1 0.89 22.7 58.0 52.8 0.91 23.9 54.9 52.2 0.95 25.3
20 69.0 53.1 0.77 19.8 66.8 52.1 0.78 20.8 64.6 51.0 0.79 21.9 62.2 50.4 0.81 23.1 59.7 49.6 0.83 24.3 56.5 48.0 0.85 25.7
28 21 71.2 49.8 0.70 20.0 68.9 48.9 0.71 21.2 66.6 48.0 0.72 22.3 64.0 46.7 0.73 23.5 61.4 45.4 0.74 24.7 58.2 44.2 0.76 26.2
22 73.4 45.5 0.62 20.3 71.0 44.7 0.63 21.5 68.6 43.9 0.64 22.7 66.0 42.9 0.65 23.9 63.3 41.8 0.66 25.2 59.8 40.7 0.68 26.8
23 75.7 41.6 0.55 20.6 73.3 41.0 0.56 21.8 70.8 39.6 0.56 23.1 68.0 38.8 0.57 24.4 65.0 37.7 0.58 25.6 61.1 36.7 0.60 27.3
24 78.0 37.4 0.48 20.9 75.6 37.0 0.49 22.2 72.8 35.7 0.49 23.5 69.9 35.0 0.50 24.8 66.7 34.0 0.51 26.2 62.5 32.5 0.52 27.8
20 69.0 60.0 0.87 19.8 66.8 58.8 0.88 20.8 64.6 58.1 0.90 21.9 62.2 57.2 0.92 23.1 59.7 56.1 0.94 24.3 56.5 55.4 0.98 25.7
21 71.2 56.2 0.79 20.0 68.9 55.1 0.80 21.2 66.6 54.6 0.82 22.3 64.0 53.8 0.84 23.5 61.4 52.8 0.86 24.7 58.2 51.8 0.89 26.2
30 22 73.4 52.1 0.71 20.3 71.0 51.1 0.72 21.5 68.6 50.1 0.73 22.7 66.0 49.5 0.75 23.9 63.3 48.7 0.77 25.2 59.8 47.8 0.80 26.8
23 75.7 48.4 0.64 20.6 73.3 47.6 0.65 21.8 70.8 46.7 0.66 23.1 68.0 45.6 0.67 24.4 65.0 44.9 0.69 25.6 61.1 43.4 0.71 27.3
24 78.0 44.5 0.57 20.9 75.6 43.8 0.58 22.2 72.8 43.0 0.59 23.5 69.9 41.9 0.60 24.8 66.7 41.4 0.62 26.2 62.5 40.0 0.64 27.8
Cooling Capacity (Nominal Air Flow): PR-20YC, PRH-20YA, PRH-20YA-L
PRH-20YA-L
OUTDOOR DB ˚C
PRH-20YA
PR-20YC
COOLING CAPACITY 0.980 0.990 1.0 1.008 1.017 1.025 TOTAL INPUT 0.990 0.995 1.0 1.003 1.007 1.010
PRH-20YA-L AIR VOLUME CMM 170 180 190 200 210 220
RANGE
PR-20YC

DB ˚C Q kW T/I kW Q kW T/I kW Q kW T/I kW
DB ˚C Q kW T/I kW Q kW T/I kW Q kW T/I kW
HEATING CAPACITY 0.990 0.995 1.0 1.003 1.007 1.010 TOTAL INPUT 1.025 1.013 1.0 0.993 0.987 0.980
PRH-20YA-L AIR VOLUME CMM 170 180 190 200 210 220
INDOOR 5.0 10.0 15.0
OUTDOOR WB ˚C
OUTDOOR WB ˚C
PRH-20YA PRH-20YA-L
PRH-20YA-L
Factor for Various Air Flow Factor for Various Air Flow
Heating Capacity
15 41.2
15 60.9
OPERATION
RANGE
RANGE
DB ˚C WB ˚C Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW Q kW SHC kW SHF T/I kW
15 64.2 44.9 0.70 16.7 63.9 44.7 0.70 16.9 63.2 44.2 0.70 17.2 62.3 43.6 0.70 17.6 61.0 43.3 0.71 18.1
20 16 66.2 41.0 0.62 16.9 65.9 40.9 0.62 17.1 65.2 40.4 0.62 17.4 64.2 40.4 0.63 17.8 62.8 39.6 0.63 18.3
17 68.4 37.6 0.55 17.0 68.0 37.4 0.55 17.2 67.2 37.0 0.55 17.5 66.2 36.4 0.55 17.9 64.7 35.6 0.55 18.4
15 64.2 52.6 0.82 16.7 63.9 52.4 0.82 16.9 63.2 52.5 0.83 17.2 62.3 51.7 0.83 17.6 61.0 51.2 0.84 18.1
16 66.2 49.0 0.74 16.9 65.9 48.8 0.74 17.1 65.2 48.9 0.75 17.4 64.2 48.2 0.75 17.8 62.8 47.7 0.76 18.3
22 17 68.4 45.1 0.66 17.0 68.0 44.9 0.66 17.2 67.2 44.4 0.66 17.5 66.2 44.4 0.67 17.9 64.7 43.3 0.67 18.4
18 70.6 40.9 0.58 17.2 70.0 40.6 0.58 17.3 69.3 40.2 0.58 17.6 68.2 40.2 0.59 18.0 66.6 39.3 0.59 18.6
19 72.9 37.2 0.51 17.4 72.4 36.9 0.51 17.5 71.4 36.4 0.51 17.8 70.2 36.5 0.52 18.2 68.7 35.7 0.52 18.8
16 66.2 56.3 0.85 16.9 65.9 56.0 0.85 17.1 65.2 56.1 0.86 17.4 64.2 55.9 0.87 17.8 62.8 55.3 0.88 18.3
17 68.4 52.7 0.77 17.0 68.0 52.4 0.77 17.2 67.2 52.4 0.78 17.5 66.2 51.6 0.78 17.9 64.7 51.1 0.79 18.4
24 18 70.6 48.7 0.69 17.2 70.0 48.3 0.69 17.3 69.3 48.5 0.70 17.6 68.2 47.7 0.70 18.0 66.6 47.3 0.71 18.6
19 72.9 44.5 0.61 17.4 72.4 44.2 0.61 17.5 71.4 44.3 0.62 17.8 70.2 43.5 0.62 18.2 68.7 43.3 0.63 18.8
20 75.3 40.7 0.54 17.5 74.8 40.4 0.54 17.6 73.7 39.8 0.54 17.9 72.6 39.9 0.55 18.4 71.0 39.1 0.55 19.0
21 77.8 36.6 0.47 17.7 77.2 36.3 0.47 17.8 76.0 35.7 0.47 18.1 75.0 36.0 0.48 18.6 73.3 35.2 0.48 19.2
18 70.6 55.8 0.79 17.2 70.0 55.3 0.79 17.3 69.3 55.4 0.80 17.6 68.2 55.2 0.81 18.0 66.6 54.6 0.82 18.6
19 72.9 51.8 0.71 17.4 72.4 51.4 0.71 17.5 71.4 51.4 0.72 17.8 70.2 50.5 0.72 18.2 68.7 50.2 0.73 18.8
26 20 75.3 48.2 0.64 17.5 74.8 47.9 0.64 17.6 73.7 47.9 0.65 17.9 72.6 47.2 0.65 18.4 71.0 46.9 0.66 19.0
21 77.8 44.3 0.57 17.7 77.2 44.0 0.57 17.8 76.0 44.1 0.58 18.1 75.0 43.5 0.58 18.6 73.3 43.2 0.59 19.2
22 80.4 40.2 0.50 17.8 79.6 39.8 0.50 17.9 78.8 40.2 0.51 18.3 77.4 39.5 0.51 18.8 75.6 39.3 0.52 19.5
23 83.0 36.5 0.44 18.0 82.4 36.3 0.44 18.1 81.2 35.7 0.44 18.5 79.8 35.9 0.45 19.0 78.0 35.1 0.45 19.7
19 72.9 59.0 0.81 17.4 72.4 58.6 0.81 17.5 71.4 58.5 0.82 17.8 70.2 58.3 0.83 18.2 68.7 57.7 0.84 18.8
20 75.3 55.0 0.73 17.5 74.8 54.6 0.73 17.6 73.7 54.5 0.74 17.9 72.6 54.5 0.75 18.4 71.0 54.0 0.76 19.0
28 21 77.8 51.3 0.66 17.7 77.2 51.0 0.66 17.8 76.0 50.9 0.67 18.1 75.0 51.0 0.68 18.6 73.3 50.6 0.69 19.2
22 80.4 47.4 0.59 17.8 79.6 47.8 0.60 17.9 78.8 48.1 0.61 18.3 77.4 47.2 0.61 18.8 75.6 46.9 0.62 19.5
23 83.0 44.0 0.53 18.0 82.4 43.7 0.53 18.1 81.2 43.8 0.54 18.5 79.8 43.1 0.54 19.0 78.0 42.9 0.55 19.7
24 85.6 40.2 0.47 18.1 84.8 39.9 0.47 18.3 83.6 39.3 0.47 18.7 82.2 39.5 0.48 19.2 80.4 38.6 0.48 20.0
20 75.3 62.5 0.83 17.5 74.8 62.1 0.83 17.6 73.7 61.9 0.84 17.9 72.6 61.7 0.85 18.4 71.0 61.1 0.86 19.0
21 77.8 59.1 0.76 17.7 77.2 58.7 0.76 17.8 76.0 58.5 0.77 18.1 75.0 57.8 0.77 18.6 73.3 57.2 0.78 19.2
30 22 80.4 55.5 0.69 17.8 79.6 54.9 0.69 17.9 78.8 55.2 0.70 18.3 77.4 54.2 0.70 18.8 75.6 53.7 0.71 19.5
23 83.0 51.5 0.62 18.0 82.4 51.1 0.62 18.1 81.2 51.2 0.63 18.5 79.8 50.3 0.63 19.0 78.0 49.9 0.64 19.7
24 85.6 47.1 0.55 18.1 84.8 47.5 0.56 18.3 83.6 46.8 0.56 18.7 82.2 46.9 0.57 19.2 80.4 45.8 0.57 20.0
(Use for low ambient temp. parts): PR-20YC, PRH-20YA, PRH-20YA-L
INDOOR INDOOR -5.0 0.0 5.0 10.0 15.0
PRH-20YA-L
PRH-20YA-L AIR VOLUME CMM 170 180 190 200 210 220
COOLING CAPACITY 0.980 0.990 1.0 1.008 1.017 1.025 TOTAL INPUT 0.990 0.995 1.0 1.003 1.007 1.010
Cooling Capacity (Nominal Air Flow)
OPERATION
PR-20YC

Cooling PR-YC
Outdoor temp.(˚CDB)
temp.parts
Indoor temp.(˚CWB)
PRH-YA
Cooling Heating
Outdoor temp.(˚CWB)
Outdoor temp.(˚CDB)
temp.parts
15 10 30 25 20
Indoor temp.(˚CWB)
Indoor temp.(˚CDB)
Cooling Heating PRH-YA-L
Outdoor temp.(˚CWB)
Outdoor temp.(˚CDB)
Range for continuous operation
temp.parts
15 10 30 25 20
Indoor temp.(˚CWB)
Indoor temp.(˚CDB)


PULLEY SIZE mm 139.7 127 139.7 139.7 (MOTOR SIDE) inch 5.5 5 5.5 5.5
750 ( / s) (CMM) 45 830 50 1000 60
PULLEY SIZE mm 114.3 127 (MOTOR SIDE) inch 4.5 5.0 PULLEY SIZE mm 165.1 152.4 127 127 127
BELT SIZE inch B41 B39 B38 B35 B37 MOTOR kw 1.1 1.1 1.1 1.5 1.5



(CMM) ( / s)
1830 1670 1500 2000


FAN SPEED rpm 640 640 690 730 730 760 810 PULLEY SIZE mm 101.6 101.6 114.3 127 (MOTOR SIDE) inch 4.0 4.0 4.5 5.0
PULLEY SIZE mm 228.6 228.6 241.3 254 254 241.3 228.6
(FAN SIDE) inch 9.0 9.0 9.5 10.0 10.0 9.5 9.0
BELT SIZE inch B37 2 B37 2 B39 2 B41 2 B41 2 B40 2 B39 2
MOTOR kw 2.2
FAN SPEED rpm 760 810 810 850 890 890 910
PULLEY SIZE mm 127 139.7 139.7 127
(MOTOR SIDE) inch 5.0 5.5 5.5 5.0
PULLEY SIZE mm 241.3 228.6 228.6 215.9 228.6 228.6 203.2
(FAN SIDE) inch 9.5 9.0 9.0 8.5 9.0 9.0 8.0
BELT SIZE inch B40 2 B39 2 B39 2 B38 2 B39 2 B39 2 B37 2
MOTOR kw 2.2 3.0
FAN SPEED rpm 910 910 910 970 1000 970 1040
PULLEY SIZE mm 127 139.7 127 127
(MOTOR SIDE) inch 5.0 5.5 5.0 5.0
PULLEY SIZE mm 203.2 203.2 203.2 190.5 203.2 190.5 177.8
(FAN SIDE) inch 8.0 8.0 8.0 7.5 8.0 7.5 7.0
BELT SIZE inch B37 B37 B37 B36 B37 B36 B35
MOTOR kw 2.2 3.0 3.0 3.0
FAN SPEED rpm 1040 -
PULLEY SIZE mm 127 -
(MOTOR SIDE) inch 5.0 -
PULLEY SIZE mm 177.8 -
(FAN SIDE) inch 7.0 -
BELT SIZE inch B35 -
MOTOR kw 2.2 2.2 3.0 -
FAN SPEED rpm 1120 1140 1120 1120 - - -
PULLEY SIZE mm 127 139.7 127 127 - - -
(MOTOR SIDE) inch 5.0 5.5 5.0 5.0 - - -
PULLEY SIZE mm 165.1 177.8 165.1 165.1 - - -
(FAN SIDE) inch 6.5 7.0 6.5 6.5 - - -
BELT SIZE inch B34 B36 B34 B34 - - -
MOTOR kw 2.2 3.0 3.0 3.0 - - -
FAN SPEED rpm 1210 1230 1230 -
PULLEY SIZE mm 127 139.7 139.7 -
2330 2670 3000 2000
(MOTOR SIDE) inch 5.0 5.5 5.5 -
PULLEY SIZE mm 152.4 165.1 165.1 -
(FAN SIDE) inch 6.0 6.5 6.5 -
BELT SIZE inch B33 B35 B35 -
MOTOR kw 3 3 3 -


FAN SPEED rpm 730 810 810 840 910 940
PULLEY SIZE mm 127 127 127 139.7 127 139.7 (MOTOR SIDE) inch 5.0 5.0 5.0 5.5 5.0 5.5 PULLEY SIZE mm 254 228.6 228.6 241.3 203.2 215.9
(FAN SIDE) inch 10.0 9.0 9.0 9.5 8.0 8.5
BELT SIZE inch B43 B41 B41 B42 B39 B41
FAN SPEED rpm 850 910 910 910 1000 970

PULLEY SIZE mm 127 139.7 127
(MOTOR SIDE) inch 5.0 5.5 5.0
PULLEY SIZE mm 215.9 203.2 190.5
(FAN SIDE) inch 8.5 8.0 7.5
BELT SIZE inch B40 B39 B39 B39 B40 B38
FAN SPEED rpm 940 1000 1040 1040 1040 -
PULLEY SIZE mm 139.7 139.7 127 127 127 -
(MOTOR SIDE) inch 5.5 5.5 5.0 5.0 5.0 -
PULLEY SIZE mm 215.9 203.2 177.8 177.8 177.8 -
(FAN SIDE) inch 8.5 8.0 7.0 7.0 7.0 -
BELT SIZE inch B41 B40 B37 B37 B37 - MOTOR kw 3.0 3.0 4.0 4.0 4.0 -
FAN SPEED rpm 1040 1040 1060 1120 - -
PULLEY SIZE mm 127 127 139.7 127 - -
(MOTOR SIDE) inch 5.0 5.0 5.5 5.0 - -
PULLEY SIZE mm 177.8 177.8 190.5 165.1 - -
(FAN SIDE) inch 7.0 7 7.5 6.5 - -
BELT SIZE inch B37 B37 B39 B36 - -
FAN SPEED rpm 1140 1120 -
PULLEY SIZE mm 139.7 127 -
(MOTOR SIDE) inch 5.5 5.0 -
PULLEY SIZE mm 177.8 165.1 -
(FAN SIDE) inch 7.0 6.5 -
BELT SIZE inch B38 2 B36 2 -
FAN SPEED rpm 1230 -
PULLEY SIZE mm 139.7 -
(MOTOR SIDE) inch 5.5 -
PULLEY SIZE mm 165.1 -
180 200 220 170
(FAN SIDE) inch 6.5 -
2830 3670 3330 3000
BELT SIZE inch B37 -
Airflow

Pulley outside dimensions are shown below: (Unit : mm) (1) Shape of belt groove


16.5mm
L0 W K K0 e f r1 r2 r3
11.0mm
12.5 5.5 9.5 19.0 12.5 0.2~0.5 0.5~1.0 1~2 11
PR-5 10 PRH-5 10 Pulley for blower & motor


+0.009 - 0.004 +0.009 - 0.004 +0.009 - 0.004
(3) Shape of motor (Unit : mm)

40˚ · B type

PR-5YC PRH-5YA PRH-5YA-L
500 Hz 250 Hz 125 Hz 8000 Hz 4000 Hz 2000 Hz 1000 Hz 63 Hz CONDITION A scale
COOLING & HEATING 67 62db 43 45 50 57 61 62 63
octave-band lebel db (0db=0.0002ubar)
NC-50
NC-40
NC-30
NC-20
63 90 125 180 250 355 500 710 1000 1400 2000 2800 4000 5600 8000 10
500 Hz 250 Hz 125 Hz 8000 Hz 4000 Hz 2000 Hz 1000 Hz 63 Hz CONDITION A scale
70 64db COOLING & HEATING 50 52 56 58 60 62 67
octave-band lebel db (0db=0.0002ubar)
NC-50
NC-40
NC-30
NC-20
63 90 125 180 250 355 500 710 1000 1400 2000 2800 4000 5600 8000 10

500 Hz 250 Hz 125 Hz 8000 Hz 4000 Hz 2000 Hz 1000 Hz 63 Hz CONDITION A scale
COOLING & HEATING 71 44 49 57 59 61 63 69 64db
octave-band lebel db (0db=0.0002ubar)
NC-50
NC-40
NC-30
NC-20
63 90 125 180 250 355 500 710 1000 1400 2000 2800 4000 5600 8000 10
500 Hz 250 Hz 125 Hz 8000 Hz 4000 Hz 2000 Hz 1000 Hz 63 Hz CONDITION A scale
68db COOLING & HEATING
48 51 59 62 65 68 76
octave-band lebel db (0db=0.0002ubar)
NC-50
NC-40
NC-30
NC-20
63 90 125 180 250 355 500 710 1000 1400 2000 2800 4000 5600 8000 10


A scale CONDITION 63 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz 125 Hz 250 Hz 500 Hz
10 8000 5600 4000 2800 2000 1400 1000 710 500 355 250 180 125 90 63 all over
PR-5YC PRH-5YA PRH-5YA-L
16-ø3.5 HOLES

25 1030 25

20-ø3.5 HOLES

60 60 150 150 200
39.5 200 39.5

PR-5, 8, 10YC (STANDARD)
(FIELD SUPPLY)
PR5YC ···40A
PR8YC ···50A
PR-10YC ···60A
TB1 L1
MC INTERNAL PROTECTOR
RED
RED
RED
WHITE
WHITE
WHITE
BLACK
BLACK
BLACK
1 51F2
TB2
TB2
R1 R2 RED RED RED
MF2
N
BLUE
WHITE WHITE
S1 S2
WHITE
PE
BLACK BLACK BLACK
T1 T2
52F
RED 51F1
MF1 WHITE RED
F
INTERNAL PROTECTOR
F
(3.15A)
BLACK
11 TB3
TB4
SWITCH BOX (FIELD SUPPLY)
F
51F1
SW1
(3.15A)
GL
RL 51F2
FZ1
23 WA
SW2
63H
AC
AC
3 TB4
CZ
CZ
CH
52F
CZ
FZ0
FZ1
8,20YC ONLY
52C (3MIN) TM
30 CZ FZ0
30 CZ
FZ1
TM
30 CZ
12 TB3
TB3 12
Fan motor (in door)
Contactor (compressor) Fan motor (out door)
TB1~4
CH
51F1, 2
Over current relay (fan I/D,O/D)
TM
Timer (anti short cycle)
Auxiliary relay (check) Auxiliary relay (compressor) Auxiliary relay (fan)
<SW1>
Switch (off) Switch (on)
<RL> <GL>
Lamp (operation) Lamp (check)
Thermostat (room temp.)

50Hertz 380~415Volt 3Phase Power supply
MC1 INTERNAL PROTECTOR
TB1
51F2
R
R 11
TB2
N
S
S
PE
T
T
MF2
INTERNAL PROTECTOR MC2
INTERNAL PROTECTOR
51F3
R R
TB3
S S
T T
MF3
52F 51F1
INTERNAL PROTECTOR
MF1
F(3.15A) F
TB4 11
TB4 14
TB5
SWITCH BOX (FIELD SUPPLY)
FZ0
51F1
F
(3.15A)
CZ2-2 CZ1-2
RL2 RL1
SW1
23WA
GL
51F2
51F3
SW 2
H1 63
63 H2
220~ 240V
AC
AC 24V
CZ1 CZ1
CZ2
CZ2
2 3 4 5 6 8 7
CZ1
TM (3MIN)
TM (3MIN) C2
CH2
CZ2
FZ0
52 F
FZ1
FZ1
CH1
TM
FZ0
(2SEC)
CZ2 30 CZ1
CZ1-1
CZ2-1
FZ1
CZ2-1 CZ1-1
CZ1-2
30 CZ2-2
TB4 12
TB412
Caution, 1.To protect each Fan motors and Compressors from abnormal current, these Over current relays , are installed. Therefore,do not change factory set value of these Over current relays. 2.To protect the compressors from frequently "ON-OFF" ,timer is installed. Therefore,do not change factory set value of this timer. 3.This timer installed so that two compressors may never start at the same time. The unit stop if the set value of the timer is changed.
Compressor motor
52C1·2 MF2·3 MF1
Fan motor (in door)
Contactor (compressor) Fan motor (out door)
52F
Contactor (fan I/D)
TB1~5
Terminal block
CH1·2
Crankcase heater
F
Fuse Transformer
51F1~3
Over current relay (fan I/D,O/D)
63H1·2
High-pressure switch
Thermostat(freeze protection) 26L1·2
TM 2 FZ0·1
Timer (anti short cycle) Timer
Auxiliary relay (check) Auxiliary relay (compressor) Auxiliary relay (fan)
30CZ1-1,2 CZ1·2
30CZ2-1,2 Auxiliary relay (check)
<SW1> <SW2>
Switch (off) Switch (on)
Lamp (power on) Lamp (check) <23WA> <RL1·2> <GL>
Thermostat (room temp.)

(SPECIAL ORDER : K CONTROL)
(FIELD SUPPLY)
MC
INTERNAL PROTECTOR
PR5YC ···40A
PR8YC ···50A
PR-10YC ···60A
TB1 L1
51F2
TB2
R
2 R
N
S
2 S
MF2
PE
T
2 T
52F 51F1
MF1
INTERNAL PROTECTOR
F(3.15A)
TB3 11
TH2
30 CZ
IB
51F1
FZ
51F2
D C B A TB4
63H
52F FZ CZ
TH5
CZ
FZ
CH
30 CZ
R/C
30 CZ
8,10YC ONLY
TB3 12 TB3 12
52C MF2 MF1 MC
Contactor(compressor) Fan motor(outdoor) Fan motor(indoor) Compressor motor
52F
Contactor(fan I/D)
TB1~4
Terminal block
Crankcase heater
Fuse Transformer
Over current relay(compressor)
51F1,2
Over current relay(fanI/D,O/D)
63H
High-pressure switch
FZ
Auxiliary relay(check) Auxiliary relay(compressor) Auxiliary relay(fan)
TH2 IB 30CZ CZ
Thermistor(pipe) Indoor board
Surge absorber circuit board DSA R/C TH5 Thermistor(room temp.) Remote controller

(SPECIAL ORDER : LOW TEMPERATURE)
(FIELD SUPPLY)
MC
INTERNAL PROTECTOR
PR - 5YC ···40A
PR -10YC ···60A PR - 8YC ···50A
TB1
51C 52C
51F2
TB2
1 52F2
2 R TB2
N
R
R
2 R
S
S
S 2
2 S
PE
T
T 1
T 2
2 T
MF2
52F1 51F1
52F3
51F3
MF1
INTERNAL PROTECTOR
F(3.15A)
TB3 11
51F3
TB4
SWITCH BOX (FIELD SUPPLY)
F
51F1
(3.15A)
RL
SW1
FZ1
51F2
23WA
GL
26D3
SW2
63H
FZ
2 4 FZ 2 FZ
3 FZ
AC 220~
AC 24V
52 F1
6 5 4 3 2
52 F2
52 F4
TB4
CZ
FZ2
CZ
FZ0
52 F3
TM
CZ
(3MIN)
FZ3
FZ1
CZ 30 CH
30 CZ
FZ1
3 FZ
FZ0 FZ4
TM
30 CZ
8,10YC ONLY
TB3 12
Name
52C MF2 MF1 MC
Compressor motor
Fan motor (indoor)
Contactor (compressor) Fan motor (outdoor)
52F1
Contactor (fan I/D)
TB1~4
Terminal block
Crankcase heater
F
Fuse Transformer
51C Tr1·2
Over current relay(compressor)
51F1,2,3
Over current relay(fanI/D,O/D)
Thermostat(freeze protection) 26L High-pressure switch 63H
Timer (anti short cycle) TM
Auxiliary relay (check) Auxiliary relay (compressor) Auxiliary relay (fan) FZ0,1
Switch (on) <SW1> Switch (off) 30CZ CZ
<SW2>
<GL> <RL>
Lamp (operation) Lamp (check) Thermostat (room temp.) <23WA>
Contactor (fan O/D) Auxiliary relay (fan O/D) FZ2~4 52F2~4

(SPECIAL ORDER : LOW TEMPERATURE)
50Hertz 380~415Volt 3Phase Power supply
MC1 INTERNAL PROTECTOR
TB1
51F2
TB2
TB2
R
R
R 11
52F2
R
N
S
S
S
S
PE
T
T
T
T
MF2
51F4
INTERNAL PROTECTOR MC2
52F3
INTERNAL PROTECTOR
51F3
TB3
TB3
R
R
52F5
R
R
S
S
S
S
T
T
T
T
MF3
52F6
51F5
52F 51F1
INTERNAL PROTECTOR
MF1
F(3.15A) F
TB4 11
TB5
1 SWITCH BOX (FIELD SUPPLY)
FZ0
51F1
TB4
F
(3.15A)
CZ2-2 CZ1-2
23WA
RL2 RL1
SW1
51F4 51F5
GL
26D1 26D3
SW 2
51F2
51F3
FZ FZ FZ FZ FZ FZ FZ FZ
3 6 2 5 4 7 2 5
CZ2
H1 63
63 H2
AC 24V
CZ1 CZ1
CZ2
2 3 5 4 6 8 7
26D2 26D4
CZ1
TM (3MIN)
TM (3MIN) C2
FZ2 FZ5
52 F7 52 F2
52 F4
52 F5
CH2
CZ2
FZ0
52 F
52 F3
52 F6
FZ1
FZ1
FZ3 FZ6
CH1
TM
FZ FZ
FZ0
30 CZ1
(2SEC)
CZ1-1
CZ2-1
CZ2
FZ1
FZ4 FZ7
30 CZ2-2
TB4 12
CZ2-1 CZ1-1
CZ1-2
TB4 12
Caution, 1.To protect each Fan motors and Compressors from abnormal current,these Over current relays, are installed. Therefore,do not change factory set value of these Over current relays. 2.To protect the compressors from frequently "ON-OFF",timeris installed. Therefore,do not change factory set value of this timer. 3.This timerinstalled so that two compressors may never start at the same time. The unit stop if the set value of the timer is changed.
Compressor motor
Fan motor (indoor)
Contactor (compressor) Fan motor (outdoor)
52F1
Contactor (fan I/D)
TB1~5
Terminal block
CH1·2
Crankcase heater
F
Fuse Transformer
51F1~5
Over current relay (fan I/D,O/D)
63H1·2
High-pressure switch
26L1·2
Thermostat(freeze protection) Timer (anti short cycle) Timer
TM
FZ0·1
Auxiliary relay (check) Auxiliary relay (compressor) Auxiliary relay (fan)
30CZ1-1, 2 CZ1·2
30CZ2-1, 2 Auxiliary relay (check)
<SW1> <SW2>
Switch (off) Switch (on)
<RL1·2> <GL>
Lamp (operation) Lamp (check)
<23WA>
Thermostat (room temp.)
26D1~4 Contactor (fan O/D) Auxiliary relay (fan O/D)
Thermostat (ambiemt temp.)
52F2~7 FZ2~7

(SPECIAL ORDER : K CONTROL & LOW TEMPERATURE)
50Hertz 380~415Volt 3Phase Power supply
PR -10YC ···60A PR - 8YC ···50A
MC INTERNAL PROTECTOR
TB1
51C 52C
51F2
TB2
2 R TB2
R
R
2 R 52F2
N
S
S
S 2
2 S
PE
MF2
T
T
T 2
2 T
52F1 51F1
52F3
51F3
DSA
CN
MF1
INTERNAL PROTECTOR
F(3.15A)
TB3 11
TH2
51F3
30 CZ
IB
51F1
FZ1
51F2
26D3
TB4 D C B A
FZ
4 FZ 2 FZ
3 FZ
63H
FZ1 CZ
52 F1
26D4
52 F2
52 F4
TH5
FZ2
CZ
52 F3
FZ1
FZ3
CH
30 CZ
3 FZ
R/C
30 CZ
FZ4
8,10YC ONLY
TB3 12
Contactor(compressor) Fan motor(outdoor) Fan motor(indoor) Compressor motor
52F1
Contactor(fan I/D)
Terminal block
51C Tr1·2 F CH
Fuse Transformer
(compressor) Over current relay
51F1,2,3
Over current relay(fanI/D,O/D)
63H
High-pressure switch
FZ1
Auxiliary relay(check) Auxiliary relay(compressor) Auxiliary relay(fan)
TH2 IB 30CZ CZ
FZ2~4 Auxiliary relay(fan O/D) 52F2~4 Contactor(fan O/D) Thermistor(pipe) Indoor board
Thermistor(room temp) TH5
Remote controller R/C
Surge absorber circuit board DSA

(FIELD SUPPLY)
PRH5YA, PRH5YA-L
···40A
PRH8YA, PRH8YA-L
···50A
PRH-10YA, PRH-10YA-L
···60A
TB1 L1
RED
RED
MC INTERNAL PROTECTOR
RED
WHITE
WHITE
WHITE
BLACK
BLACK
BLACK
TB2 X1
R1 R2 RED RED RED
3 2 1 51F2
TB2
N
BLUE
MF2
WHITE WHITE
S1 S2
WHITE
PE
BLACK BLACK BLACK
T1 T2
52F
RED 51F1
MF1 WHITE RED
F
F
BLACK
INTERNAL PROTECTOR
(3.15A)
11 TB3
TB4
SWITCH BOX (FIELD SUPPLY)
HZ
HZ
51F1
F
SW2
(3.15A)
SW1
HEAT COOL
GL
RL 51F2
FZ1
H C
63H
SW3
26 D2
23 WA
AC
AC
S4 21
3 TB4
2 4 6 7
CZ
CH
52F
D1 26 CZ
HZ
FZ0
FZ1
8,10YA,
52C (3MIN) TM
YA-L
30 CZ FZ0
30 CZ
ONLY
FZ1
TM
30 CZ
12 TB3
TB3 12
Fan motor (in door)
Contactor (compressor) Fan motor (out door)
TB1~4
CH
51F1, 2
Over current relay (fan I/D,O/D)
26D1·2
TM
Timer (anti short cycle)
FZ0·1 CZ
Auxiliary relay (check) Auxiliary relay (heater) Auxiliary relay (compressor) Auxiliary relay (fan)
30CZ
X1·2
<SW1>
Switch (operation mode) Switch (off) Switch (on)
<SW3>
<RL> <GL>
Lamp (operation) Lamp (check)
Thermostat (room temp.)

PRH-15YA PRH-15YA-L ···100A
50Herts 380~415Volt 3Phase Power supply
···125A
MC1 INTERNAL PROTECTOR
TB1
51F2
TB2
R
R
N
S
S
MF2
T
T
INTERNAL PROTECTOR MC2
INTERNAL PROTECTOR
51F3
TB3
R R
S S
MF3
T T
52F 51F1
INTERNAL PROTECTOR
MF1
F(3.15A) F
TB4 11
TB5
SWITCH BOX (FIELD SUPPLY)
FZ0
51F1 HZ HZ
F
SW2 SW1
(3.15A)
CZ2-2 CZ1-2
HEAT COOL
RL2 RL1
TB4 13
H C H C
GL
51F2
51F3
SW3
X1 X2 X2
AC 220~ 240V
23WA
H1 63
63 H2
AC 24V
CZ1 CZ1
CZ2
CZ2
TB5
2 3 4 5 6 8 9 7
26 D4
26 D3
TM (3MIN)
TM (3MIN) C2
CZ1
HZ
21 S42
FZ0
CH2
CZ2
52 F
D1 26
26 D2 X4
FZ1
FZ1
CH1
TM
FZ0
30 CZ1
(2SEC)
CZ2
CZ1-1
CZ2-1
FZ1
30 CZ2-2
TB4 12 TB4 12
CZ2-1 CZ1-1
CZ1-2
Caution, 1.To protect each Fan motors and Compressors from abnormal current, these Over current relays,are installed. Therefore,do not change factory set value of these Over current relays. 2.To protect the compressors from frequently "ON-OFF" ,timeris installed. Therefore,do not change factory set value of this timer. 3.This timerinstalled so that two compressors may never start at the same time. The unit stop if the set value of the timer is changed.
Compressor motor
52C1·2 MF2·3 MF1
Fan motor (in door)
Contactor (compressor) Fan motor (out door)
52F
Contactor (fan I/D)
TB1~5
Terminal block
CH1·2
Crankcase heater
F
Fuse Transformer
51F1~3
Over current relay (fan I/D,O/D)
63H1·2
High-pressure switch
Thermostat(freeze protection) 26L1·2
26D1~4
Thermostat (defrost)
TM 2
Timer (anti short cycle) Timer
21S41·42
4-Way valve
FZ0·1
Auxiliary relay (check) Auxiliary relay (heater) Auxiliary relay (compressor) Auxiliary relay (fan)
30CZ1-1,2 HZ CZ1·2
30CZ2-1,2 Auxiliary relay (check)
X1~4
Auxiliary relay (defrost)
<SW1> <SW2> <SW3>
Switch (operation mode) Switch (off) Switch (on)
Lamp (operation) Lamp (check) <23WA> <RL1·2> <GL>
Thermostat (room temp.)

(SPECIAL ORDER : K CONTROL)
PRH5YA, PRH5YA-L ···40A
PRH8YA, PRH8YA-L···50A
MC
INTERNAL PROTECTOR
PRH-10YA, PRH-10YA-L···60A
TB1 L1
51F2
TB2
R
2 R
N
S
2 S
MF2
PE
T
2 T
52F 51F1
MF1
INTERNAL PROTECTOR
F(3.15A)
TB3 11
TH2
HZ
HZ
30 CZ
IB
51F1
FZ
51F2
63H
D C B A TB4
52F FZ CZ HZ
21 S4
CM
D2
TH5
26 D1 X2
CZ
FZ
CH
30 CZ
R/C
30 CZ
8,10YA,YA-L ONLY
TB3 12 TB3 12
52C MF2 MF1 MC
Contactor(compressor) Fan motor(outdoor) Fan motor(indoor) Compressor motor
52F
Contactor(fan I/D)
TB1~4
Terminal block
Crankcase heater
Fuse Transformer
Over current relay(compressor)
51F1,2
Over current relay(fanI/D,O/D)
63H
High-pressure switch
26D1·2
Thermostat(defrost)
21S4
4-Way valve
FZ
Auxiliary relay(check) Auxiliary relay(heater) Auxiliary relay(compressor) Auxiliary relay(fan)
30CZ HZ CZ
X1·2
Auxiliary relay(defrost)
TH2 IB
Thermistor(pipe) Indoor board
Surge absorber circuit board DSA R/C TH5 Thermistor(room temp.) Remote controller

PRH5YA, PRH5YA-L
···40A
MC
PRH8YA, PRH8YA-L
···50A
INTERNAL PROTECTOR
PRH-10YA, PRH-10YA-L
···60A
TB1
51C 52C
51F2
TB2
1 52F2
2 R TB2
R
R
2 R
N
S
S
S 2
2 S
MF2
PE
T
T 1
T 2
2 T
52F1 51F1
51F3
52F3
MF1
INTERNAL PROTECTOR
F(3.15A)
TB3 11
51F3
TB4
SWITCH BOX (FIELD SUPPLY)
HZ
HZ
F
(3.15A)
SW1
51F1
TB313
HEAT COOL
RL
SW2
FZ1
GL
51F2
H C
26D3
23WA
SW3
63H
FZ
2 4 FZ 2 FZ
3 FZ
AC 220~ 240V
AC 24V
21 S4
7 6 5 4 3 2
D2
26D4
TB4
CZ
FZ2
52 F2
52 F4
CZ
HZ
26 D1 X2
52 F3
FZ0
CZ
(3MIN)
TM
FZ3
FZ1
CZ 30 CH
30 CZ
3 FZ
FZ1
FZ0
TM
FZ4
30 CZ
8,10YA, YA-L ONLY
TB3 12
52C MF2 MF1 MC
Compressor motor
Fan motor (indoor)
Contactor (compressor) Fan motor (outdoor)
52F1
Contactor (fan I/D)
TB1~4
Terminal block
Crankcase heater
F
Fuse Transformer
51C Tr1·2
Over current relay(compressor)
51F1,2,3
Over current relay(fanI/D,O/D)
High-pressure switch 63H
Thermostat(freeze protection) 26L Thermostat (defrost) 26D1~4
Timer (anti short cycle) TM
21S4
4-Way valve
FZ0,1
Auxiliary relay (check) Auxiliary relay (heater) Auxiliary relay (compressor) Auxiliary relay (fan)
30CZ HZ CZ
X1·2
Auxiliary relay (defrost)
Switch (on) <SW2> Switch (off) <SW1>
Switch (operatin mode)
<SW3>
<GL> <RL>
Lamp (operation) Lamp (check)
Thermostat (room temp.) <23WA>
Contactor (fan O/D) Auxiliary relay (fan O/D) FZ2~4 52F2~4

50Herts 380~415Volt 3Phase Power supply
···100A
MC1 INTERNAL PROTECTOR
PRH-20YA PRH-20YA -L
···125A
TB1
51F2
TB2
TB2
R
R
52F2
R
R
N
S
S
S
S
PE
T
T
T
T
MF2
INTERNAL PROTECTOR MC2
51F4
52F3
INTERNAL PROTECTOR
51F3
R
TB3
R
52F5
R
TB3
R
S
S
S
S
MF3
T
T
T
T
52F6
51F5
52F 51F1
INTERNAL PROTECTOR
MF1
F(3.15A) F
TB4 11
TB5
SWITCH BOX (FIELD SUPPLY)
FZ0
51F1 HZ
HZ
TB4
F
(3.15A)
SW2 SW1
CZ2-2 CZ1-2
HEAT COOL
RL2 RL1
TB4 13
GL
51F4 51F5
H C H C
26D1 26D3
SW3
51F2
51F3
FZ FZ FZ FZ FZ FZ FZ FZ
23WA
H1 63
63 H2
X1 X2 X2
3 6 2 5 4 7 2 5
CZ1 CZ1
CZ2
AC 24V
CZ2
TB5
2 3 4 5 6 8 9 7
21 S41
26 D3
26D2 26D4
TM (3MIN)
TM (3MIN) C2
FZ2 FZ5
52 F7 52 F2
52 F4
52 F5
CZ1
HZ
21 S42
CH2
CZ2
FZ0
26 D2 X4
52 F3
52 F6
52 F
D1 26
FZ1
FZ1
FZ3 FZ6
CH1
TM
FZ0
30 CZ1
(2SEC)
FZ FZ
CZ1-1
CZ2-1
CZ2
FZ1
FZ4 FZ7
CZ2-1 CZ1-1
CZ1-2
30 CZ2-2
TB4 12
TB4 12
Caution, 1.To protect each Fan motors and Compressors from abnormal current,these Over current relays, are installed. Therefore,do not change factory set value of these Over current relays. 2.To protect the compressors from frequently "ON-OFF",timeris installed. Therefore,do not change factory set value of this timer. 3.This timerinstalled so that two compressors may never start at the same time. The unit stop if the set value of the timer is changed.
Contactor (compressor) Fan motor (outdoor)
TB1~5
CH1·2
F
Over current relay (fan I/D,O/D)
26L1·2
26D1~4
TM
Timer (anti short cycle) Timer
FZ0·1
Auxiliary relay (check) Auxiliary relay (heater) Auxiliary relay (compressor) Auxiliary relay (fan)
30CZ2-1, 2 Auxiliary relay (check)
<SW1> <SW2> <SW3>
Switch (operation mode) Switch (off) Switch (on)
Lamp (operation) Lamp (check)
Thermostat (room temp.)
26D1~4 Contactor (fan O/D) Auxiliary relay (fan O/D)
Thermostat (ambiemt temp.)

(SPECIAL ORDER : K CONTROL & LOW TEMPERATURE)
PRH5YA, PRH5YA-L ···40A
50Hertz 380~415Volt 3Phase Power supply
MC INTERNAL PROTECTOR
PRH10YA PRH-10YA-L ···60A
TB1
51C 52C
51F2
TB2
2 R TB2
R
R
2 R 52F2
N
S
S
S 2
2 S
PE
T
T
T 2
2 T
MF2
52F1 51F1
52F3
51F3
DSA
MF1
CN
INTERNAL PROTECTOR
F(3.15A)
TB3 11
TH2
51F3
HZ
HZ
30 CZ
IB
51F1
TB3 13
FZ1
51F2
26D3 X1
TB4 D C B A
FZ
4 FZ 2 FZ
3 FZ
52 F1
63H
21 S4
CZ HZ
FZ1
D2
FZ2
26D4
52 F2
52 F4
TH5
26 D1 X2
52 F3
CZ
FZ1
FZ3
CH
30 CZ
3 FZ
R/C
30 CZ
FZ4
8,10YA,YA-L ONLY
TB3 12
52C MF2 MF1 MC
Contactor(compressor) Fan motor(outdoor) Fan motor(indoor) Compressor motor
52F1
Contactor(fan I/D)
Terminal block
Crankcase heater
Fuse Transformer
(compressor) Over current relay
51F1,2,3
Over current relay(fanI/D,O/D)
26D1~4 63H
Thermostat(defrost) High-pressure switch
21S4
4-Way valve
FZ1
Auxiliary relay(check) Auxiliary relay(heater) Auxiliary relay(compressor) Auxiliary relay(fan)
30CZ HZ CZ
X1·2
Auxiliary relay(defrost)
TH2 IB
Thermistor(pipe) Indoor board
FZ2~4 Auxiliary relay(fan O/D) 52F2~4 Contactor(fan O/D)
Thermistor(room temp) TH5
Remote controller R/C
Surge absorber circuit board DSA

PR-5, 8, 10YC
POWER ON
CH ON
GL ON
SW2 ON?
NO
YES
FZ0,1 ON (SELF HOLD)
52F ON MF1 OPERATE
YES
NO
23WA ON?
YES
CZ ON
TM ON
NO
PASS THE 3 MIN.?
YES
52C ON MC OPERATE MF2 OPERATE
CH OFF
SAFETY DEVICE OFF?
NO
YES
30CZ OFF
52C OFF MC STOP MF2 STOP
RL ON
CH ON
SERVICE CALL

POWER ON
CH ON
GL ON
30CZ ON (SELF HOLD)
NO
SW3 ON?
YES
FZ0,1 ON (SELF HOLD)
52F ON MF1 OPERATE
SW1 COOL?
NO
HZ ON
YES
21S4 ON
NO
23WA ON?
NO
23WA ON?
YES
CZ ON
YES
CZ ON
TM ON
TM ON
NO
PASS THE 3 MIN.?
NO
PASS THE 3 MIN.?
YES
52C ON MC OPERATE MF2 OPERATE
YES
52C ON MC OPERATE MF2 OPERATE
CH OFF
CH OFF
SAFETY DEVICE OFF?
NO
NO
CONDENSING TEMP. -12˚C?
<=
YES
30CZ OFF
YES
26D1, 2 ON
52C OFF MC STOP MF2 STOP
X1 ON X2 ON (SELF HOLD)
RL ON
21S4 OFF MF2 STOP
CH ON
SERVICE CALL
NO
CONDENSING
TEMP. 6˚C?
<=
YES
26D1, 2 OFF
X1, 2 OFF
21S4 ON MF2 OPERATE

POWER ON
CH1, 2 ON
GL ON
30CZ1, 30CZ2 ON (SELF HOLD)
NO
SW2 ON?
YES
FZ0, FZ1 ON (SELF HOLD)
52F ON MF1 OPERATE
YES
NO
23WA No.1 ON?
YES
CZ1 ON
TM1 ON
NO
PASS THE 3 MIN.?
YES
52C1 ON MC1 OPERATE MF2 OPERATE
CH1 OFF
23WA No.2 ON?
NO
YES
CZ2 ON
TM2 ON
PASS THE 2 SEC.?
NO
YES
52C2 ON MC2 OPERATE MF3 OPERATE
CH2 OFF
NO
No.2 SAFETY DEVICE OFF?
No.1 SAFETY DEVICE OFF?
NO
YES
30CZ2 OFF
YES
30CZ1 OFF
52C2 OFF MC2 STOP MF3 STOP
52C1 OFF MC1 STOP MF2 STOP
RL2 ON
RL1 ON
CH2 ON
CH1 ON
SERVICE CALL

HZ ON
POWER ON
21S41, 2 ON
CH1, 2 ON
NO
23WA No.2 ON?
YES
30CZ1, 30CZ2 ON (SELF HOLD)
CZ1 ON
NO
TM1 ON
SW3 ON?
YES
NO
PASS THE 3 MIN.?
FZ0, FZ1 ON (SELF HOLD)
YES
52F ON MF1 OPERATE
TM2 ON
NO
NO
PASS THE 2 SEC.?
SW1 COOL?
YES
YES
52C2 ON MC2 OPERATE MF3 OPERATE
NO
23WA No.1 ON?
CH2 OFF
CZ1 ON
TM1 ON
NO
23WA No.1 ON?
PASS THE 3 MIN.?
NO
52C1 ON MC1 OPERATE MF2 OPERATE
YES
52C1 ON MC1 OPERATE MF2 OPERATE
CH1 OFF
CH1 OFF
NO
No.1 CONDENSING
NO
23WA No.2 ON?
26D1, 3 ON
YES
CZ2 ON
X1 ON X3 ON (SELF HOLD)
NO
TM2 ON
No.2 CONDENSING
21S41 OFF MF2 STOP
NO
YES
PASS THE 2 SEC.?
26D2, 4 ON
YES
No.1 CONDENSING
X2 ON X4 ON (SELF HOLD)
52C2 ON MC2 OPERATE MF3 OPERATE
TEMP. 6˚C?
21S42 OFF MF3 STOP
YES
26D1, 3 OFF
CH2 OFF
No.2 SAFETY DEVICE OFF?
X1, 3 OFF
NO
No.1 SAFETY DEVICE OFF?
No.2 CONDENSING
YES
30CZ2 OFF
21S41 ON MF2 OPERATE
YES
YES
30CZ1 OFF
52C2 OFF MC2 STOP MF3 STOP
No.1 DEFROST
OPERATION?
52C1 OFF MC1 STOP MF2 STOP
NO
RL2 ON
21S42 ON MF2 OPERATE
RL1 ON
CH2 ON
CH1 ON
SERVICE CALL

PR-5YC
ø19.05
Check joint
Check joint
ø19.05
ø12.7
ø22.2
Compressor
Capillary Tube
ø12.7
ø12.7
: OPTION
PR-15,20YC or PRH-15,20YA or PRH-15,20YA-L is composed of two refrigerant cycles.
ø19.05
Check joint
Check joint
ø19.05
ø12.7
ø22.2
Compressor
Capillary Tube
ø12.7
ø12.7
: OPTION

ø19.05
Check joint
4-Way valve
Check joint
ø19.05
ø12.7
ø22.2
Compressor
Capillary Tube
Capillary Tube
ø12.7
ø12.7
Check valve
: OPTION
PR-15,20YC or PRH-15,20YA or PRH-15,20YA-L is composed of two refrigerant cycles.
4-Way valve
Check joint
Muffler
ø15.88
ø15.88
Check joint
ø25.4
Compressor
Capillary Tube
Capillary Tube
ø12.7
ø12.7
Check valve
: OPTION

ø19.05
ø19.05
ø12.7
ø22.2
ø12.7
ø12.7
PR-15,20YC or PRH-15,20YA or PRH-15,20YA-L is composed of two refrigerant cycles.
4-Way valve
Check joint
Muffler
ø15.88
ø15.88
Check joint
ø25.4
Accumulator
Compressor
Capillary
Tube
Capillary Tube
ø12.7
ø12.7
Check valve
: OPTION

PR-10YC PRH-10YA PRH-10YA-L COMPRESSOR OVER CURRENT RELAY 51C 26.0A 27.5A 31.0A COMPRESSOR INTERNAL THERMOSTAT - 110˚C OFF 120˚C OFF 130˚C OFF HIGH PRESSURE SWITCH 63H 2.94MPa OFF FREEZE PROTECTOR 26L -2˚C IN FROST PROTECTOR (ONLY PRH-YA,PRH-YA-L) 26D1,2 -12˚C IN, 6˚C OUT INDOOR FAN MOTOR OVER CURRENT RELAY 51F1 2.3A 3.2A 3.6A OUTDOOR FAN MOTOR OVER CURRENT RELAY 51F2 2.0A OUTDOOR FAN MOTOR INTERNAL THERMOSTAT - 150˚C OFF FUSE (CONTROL CIRCUIT) F 3.15A FUSE (OPERATION CIRCUIT) F 3.15A OUTDOOR FAN MOTOR OVER CURRENT RELAY (USE THE OPTIONAL PARTS : LOW AMBIENT PARTS) 51F3 2.0A
PR-8YC PRH-8YA PRH-8YA-L
ITEM NO.
PR-20YC PRH-20YA PRH-20YA-L
ITEM NO.
COMPRESSOR OVER CURRENT RELAY 51C1,2 27.5A 31.0A COMPRESSOR INTERNAL THERMOSTAT - 120˚C OFF 130˚C OFF HIGH PRESSURE SWITCH 63H1,2 2.94MPa OFF FREEZE PROTECTOR 26L1,2 -2˚C IN FROST PROTECTOR (ONLY PRH-YA,PRH-YA-L) 26D1,2,3,4 -12˚C IN, 6˚COUT INDOOR FAN MOTOR OVER CURRENT RELAY 51F1 5.0A 6.6A OUTDOOR FAN MOTOR OVER CURRENT RELAY 51F2,3 2.0A OUTDOOR FAN MOTOR INTERNAL THERMOSTAT - 150˚C OFF FUSE (CONTROL CIRCUIT) F 3.15A FUSE (OPERATION CIRCUIT) F 3.15A OUTDOOR FAN MOTOR OVER CURRENT RELAY (USE THE OPTIONAL PARTS : LOW AMBIENT PARTS) 51F4,5 2.0A
DESCRIPTION MODEL NAME PARTS CODE PR-5YC PRH-5YA PRH-5YA-L PR-8YC PRH-8YA PRH-8YA-L PR-10YC PRH-10YA PRH-10YA-L
PR- YC-K - PRH- YA-K - PRH- YA-LK -
PR- YC PAC-201LC - - PAC-202LC - - PAC-203LC - - PRH- YA - PAC-201LC - - PAC-202LC - - PAC-203LC - PRH- YA-L - - PAC-201LC - - PAC-202LC - - PAC-203LC
PR- YC PAC001PG - - PAC002PG - - PAC003PG - - PRH- YA - PAC001PG - - PAC002PG - - PAC003PG - PRH- YA-L - - PAC001PG - - PAC002PG - - PAC003PG
PR- YC PAC101FG - - PAC102FG - - PAC103FG - - PRH- YA - PAC101FG - - PAC102FG - - PAC103FG - PRH- YA-L - - PAC101FG - - PAC102FG - - PAC103FG
DESCRIPTION MODEL NAME
PR- YC PAC-201LCX2(PCS) - - PAC-201LCX2(PCS) - - PRH- YA - PAC-201LCX2(PCS) - - PAC-201LCX2(PCS) - PRH- YA-L - - PAC-201LCX2(PCS) - - PAC-201LCX2(PCS)
PR- YC PAC001PGX2(PCS) - - PAC001PGX2(PCS) - - PRH- YA - PAC001PGX2(PCS) - - PAC001PGX2(PCS) - PRH- YA-L - - PAC001PGX2(PCS) - - PAC001PGX2(PCS)
PR- YC PAC104FG - - PAC105FG - - PRH- YA - PAC104FG - - PAC105FG - PRH- YA-L - - PAC104FG - - PAC105FG
![Page 50 of the Mitsubishi Electronics Air Conditioner (10) user manual — [REFRIGERATION SYSTEM]](/cdn/reader/f4/f482ffcff7ed24c47bb6d0aa982706bf2ecc7560f4e404ac48d6e77b2209599f/images/page-50.webp?w=400)
Product type PR,PRH,PRH-L SERIES
Capacity kw 17.6 28.1 35.2 52.8 70.3
Cooling capacity (AS1861) kW 16.3 23.8 29.7 46.3 60.8
Sensible Cooling capacity (AS1861) kW 13 19.7 25.3 38.4 50.2
Cooling power consumption (Input) kW 5.4 8.3 11.4 16.8 22.7
ByPass Factor 0.19 0.24 0.18 0.18 0.11
Heating capacity (AS1861) (Only PRH-YA,PRH-YA-L) kW 15.1 23 32 45.5 61.2
Heating power consumption (Only PRH-YA,PRH-YA-L) kW 4.6 7 9.6 14.4 19.3
Design voltage Volts 415
Power supply Volts 415
Control voltage Volts 240/24
Maximum voltage Volts 415
Minimum voltage Volts 380
Approx. starting current Amps 62 87 100 115 135
Unit current (Nominal voltage and AS1861 maximum conditions) Amps 12.8 20.6 25.7 37.9 50.9
Fan motor hp HP 1.0 1.5 2 3 4
Fan motor current Amps 2.26 2.90 3.28 4.72 6.06
Fan motor speed rpm 1,400 1,410 1,420
Model CRNQ-0500-TFD QR90K1-TFD QR12M1-TFD QR90K1-TFD QR12M1-TFD
Type HERMETIC LINE START (RECIPROCATING)
Quantity 1 1 1 2 2
Nominal motor hp HP 5 7.5 10 27.5 210
Locked rotor current Amps 59.5 83.4 95.2 83.4 95.2
Normal run current (AS1861) Amps 7.65 11.7 15.62 211.74 215.22
Swept volume cc/rev 101.92 177.45 221.8 2177.45 2221.8
Bore mm 49.78 55.58
Stroke mm 26.19 18.29 22.86 18.29 22.86
Number of cylinders 2 4
Oil charge ml 2,070 3,250 23,250
Type of oil Calumet R015 or Witco 3GS
Crankcase heater watts 40 70 270
Refrigerant charge per circuit kg 3.6 4.6 5.8 24.6 25.8
Number of refrigerant controls 1 1 1 2 2
Refrigerant control Capillary tube
Reverse cycle valve (Only PRH-YA,PRH-YA-L) 4-Way valve
Defrost system (Only PRH-YA,PRH-YA-L) Reverse cycle defrost
[EVAPORATOR] Quantity 1 1 1 2 2
Face area sq.m 0.53 0.69 20.65
Rows deep 3 3 4 3 4
Rows high 26 26 26 30 30
Finned length mm 800 1,046 2850
Face velocity m/s 1.7 2.0 2.4 2.2 2.4
Fins per meter 512 512 512 473 512
Fin material thickness mm 0.12
Fin material Aluminium Fins pitch mm 1.95 1.95 1.95 2.11 1.95
Tube diameter mm 9.52
Gauge of copper tube mm 0.35
Number of circuits 10 13 17 11 15
![Page 51 of the Mitsubishi Electronics Air Conditioner (10) user manual — [ENCLOSURE AND FRAME]](/cdn/reader/f4/f482ffcff7ed24c47bb6d0aa982706bf2ecc7560f4e404ac48d6e77b2209599f/images/page-51.webp?w=400)
[PRODUCT] ROOFTOP PACKAGE AIR COOLED HEATPUMP AND COOLING ONLY UNITS
Product type PRH SERIES
Number of blowers 1 2
Diameter of blowers mm 253 393
Width of blowers mm 182 282
Blower drive Belt drive
Fan motor output kW 0.75 1.1 1.5 2.2 3.0
Normal fan motor run current A 2.26 2.90 3.28 4.72 6.06
Air quantity L/s 900 1,400 1,660 2,800 3,160
External static pressure Pa 100 200
Supply air dimensions (h w) mmmm 300 850 300 1,150 428 1,820
Return air dimensions (h w) mmmm 410 900 410 1,200 464 1,879
Quantity 1 1 1 2 2
Face area sq.m 1.3 1.12 1.46 21.07 21.32
Rows deep 3
Rows high 30 23 30 30 37
Finned length mm 1,700 1,920 21,400
Face velocity m/s 1.2 2.8 2.1 2.9 2.3
Fins per meter 473
Fin material thickness mm 0.12
Fins pitch mm 2.11
Tube diameter mm 9.52
Gauge of copper tube mm 0.35
Number of circuits 11 11 15 11 14
Number of fans 1 1 1 2 2
Diameter of fans mm 600 800
Pitch of fans mm - - - 990
Fan drive Direct drive
Fan motor output kw 0.15 0.35 0.35 20.35 20.35
Quantity 1 1 1 2 2
Normal fan motor run current Amps 0.6 1.3 1.3 21.3 21.3
Fan motor speed rpm 650 645
Air quantity L/s 1,583 3,083 23,083
height mm 1,000 1,200
Dimension width mm 1,000 1,300 1,990
depth mm 1,600 1,840
Panel thickness mm 1.2
Condensate drain size mm 25.4
Weight kg 299 393 413 698 729
Sound power level dbA 73 75 75 79 79
Sound pressure level dbA 62 64 64 68 68
Fin material Aluminium · Color Munsell 5Y8/1

All series of air conditioners are designed for outdoor installations and are to be placed on a slab or rooftop, however if the air conditioner is to be installed in a plant room application, please contact your equipment supplier prior to installation. Access for both service and installation must be provided to the compressors, control wiring and fans as shown below.
(1) Care must be taken to prevent recirculation of

the condenser air. To stabilize compressor condensing pressures it is recommended that wherever possible the condenser air inlet side be faced away from prevailing winds. (2) For rooftop installation, the type of mounting
plates for rigging and hoisting of the unit. The hoisting plates are located in the base of the unit. When hoisting the unit with a crane, spreader bars must be used to prevent damage to side panels by the supporting cables.
base depends on the roof construction. A built- up roof may not support the weight of the unit and so it may be necessary to support the unit by adding structural members below it.


2.Roof Mounting (1) The figure shows the use of the roof curb available
for mounting these units. (2) The curb should be sealed and fixed to the roof by
weather stripping. A suggested means of sealing the unit and roof curb is shown below.

supply and return air openings. Duct connection to the unit should be made with duct flanges and secured directly to the air openings with flexible duct connectors to avoid normal noise transmission.
Insulation
(2) For vertical air supply, a field supply plenum should
be used. The figure below shows the recommended method for duct connection.
(3) To prevent air leakage, all duct seams should be
Roof line
taped. Ducts run in air spaces that are not air-conditioned must be insulated and provided with a vapor barrier. Ducts exposed to the outside must be weatherproofed. For quiet operation, we recommend that the insulation on the supply duct be placed inside, lining the duct.
Duct connection with a vertical air plenum
(4) Where ducts from the outside enter a building, the
duct openings in the building should be sealed with weather stripping to prevent rain, duct, sand,etc. from entering the building.
provision within the unit, however the filters may be installed in the return air.
(1) A 1 FPT condensate drain fitting is provided. The
B
drain pipe can be led out at the right or left side. Under standard specifications, it is led out at the left side and the right side is covered.
A C
= = =
Drain piping
(2) The drain pipe must be provided with a trap on the
Drain trap
The drain pipe should extend below this level.
outside of the unit and also installed at an incline for proper drainage, as shown below.
(3) To prevent condensate formation and leakage,
Drain trap for condensate
provide the drain pipe with insulation to safeguard against sweating.
is no leakage and that the water drains off properly.

5.Electrical Wiring Remove the panel on the right side (PR,PRH-5 10) or the rear side (PR,PRH-15,20) of the unit and connect the units power supply wiring to the proper terminals in the control box, as shown below.
PR-5YC PRH-5YA PRH-5YA-L
PR-8YC PRH-8YA PRH-8YA-L
PR-10YC PRH-10YA PRH-10YA-L
PR-15YC PRH-15YA PRH-15YA-L
MODEL
INDOOR FAN MOTOR OUTPUT
<kW> < mm > < mm > < A >
1.1 1.5 5.5 5.5 50
1.5 2.2 2.2 3.0
3.0 4.0 22 22 100
WIRING POWER SUPPLY
22 22 100
EARTH
MAIN SWITCH
Std.
Terminal block
Control box
power supply
power supply
Wiring for PR,PRH-5 10(right side view)
Wiring for PR,PRH-15,20(rear view)
TN-NET SYSTEM (For European models only)
6.Final Checks After having installed the unit, check that: (1) The unit is fixed securely. (2) The unit is installed properly. (3) The drain pipe is provided with a drain trap. (4) The electrical wiring has been connected correctly and the terminal screws have been properly
tightened. (5) The duct work has been performed correctly.
7.Trial Operation (1) Before turning the unit on, measure the resistance between the terminals of the electrical parts and
ground with a 500V megger and check that the value is at least 1MΩ. If the measured value is below 1MΩ, do not operate the unit. (2) Check the operation of the high pressure switch by activating it. Operation should stop when the two leads
of the outdoor unit fan motor are removed from the contactor and cooling continues for 5~10min. (3) Check that the indoor and outdoor fans are rotating in the proper direction. (4) After having checked the above points, proceed with a trial operation of the unit.

1.CHECK POINTS FOR OPERATION
Check the following points before you operate your air conditioner.
(1) Check that there is nothing blocking the flow of air from the air outlet into the air inlet.
Inlet grille
Ceiling
Ceiling
Obstacle blocking air inlet
Obstacle blocking air inlet
Outdoor Unit
Obstacle blocking air inlet
(2) Make sure the air conditioner is properly grounded by checking the ground terminal .

Keep the following points in mind to safeguard against failures and breakdowns.
(1) This air conditioner does not restart within 3min.
after shut down. (These models have a crankcase heater in the compressor. If the air conditioner is shut down for a short time, please do not turn the power switch to OFF, but turn the operation switch to OFF.) (2) If the air conditioner is shut down by a power failure,
set the operation switch to OFF. When the power is restored, normal air conditioner operation can be resumed. (3) Do not stick rods or other objects through the air
outlet during operation since this may result in equipment damage or personal injury.
3.MAINTENANCE For superior performance and lasting durability, please do not forget to conduct proper and regular maintenance.
3.1 Cleaning the Air Filter Clean the air filter about once a week with a neutral cleanser and leave it to dry in a shady location. Clean more regularly if the air filter gets very dirty.
If the filter gets blocked, air will not be sucked in properly, and the cooling effect will deteriorate. Failure to clean the air filter may result in equipment breakdown or malfunctions.
3.2 Cleaning panels Clean dirt off front panel as follows. Use a household neutral cleanser such as for dishes or vegetables. Moisten a soft cloth with the cleanser, then wipe lightly. Next,wipe three or four times with another soft cloth moisten with water. Finally, wipe off all the remaining cleanser with a soft cloth.
Neutral Cleanser
Grease
Moisten a soft cloth with the alcohol, then wipe off lightly. Isopropyl alcohol is sold at stores as reagents in small quantities.
Isopropyl alcohol
Note:
Alcohol is highly combustible. Take extreme care when handling. Also, do not use paint or adhesive thinner.
3.3 Cleaning the Outdoor Unit Heat Exchanger If you use your air conditioner for prolonged periods, the outdoor heat exchanger will become dirty, impairing its function and reducing air conditioners performance. Consult your equipment supplier or air conditioning contractor on how to clean the heat exchanger.
Heat exchanger

cooling / heating operation. This allows the compressors to come up to the correct operation temperatures. Failure to do this, could cause compressor failure.
5.PREPARING FOR PROLONGED SHUTDOWN After the usage season is over, prepare the air conditioner for later use by: (1)Setting the power switch to OFF. (2)Consulting your Air conditioning specialist for detailed information.
If any trouble occurs, turn the operation (start or run) switch off immediately.
Remedy Possible cause Symptom
Wait for power supply recovery. Power failure. Both fan and compressor
Contact your Air conditioning specialist. Blown fuse of power source switch.
do not run.
Ask your electric power company. Excessively low power source voltage.
Fan runs but compressor
does not run. Can not be operated as it is out of temperature control range.
Remove blocking matter. Air outlet and inlet are blocked.
Fan runs but stops immediately.
Clean it. The filter installed in the field is clogged with dust.
Close them. Windows and doors are being opened.
Remove blocking matter. Air outlet and inlet are blocked.
cooling/heating.
Insufficient refrigerant charge.
Contact your Air conditioning specialist.
Runs but without

Please supply and install a one piece, air to air reverse cycle air conditioning system.
The system shall be completely assembled, tested and have a complete refrigeration charge ready for installation and operation from the factory.
The system shall operate at outdoor ambient temperatures as high as 46˚C.
The system shall have a total cooling capacity of kW or greater with an indoor air quantity of L/s at ˚C db and ˚C wb entering indoor coil temperature with a ˚C temperature entering the outdoor coil.
The system shall have a sensible heat capacity of kW or greater with a room db temperature of ˚C.
The total heating capacity (without electric element heaters) shall be kW or greater at ˚Cdb, ˚C wb outdoor air conditions, with ˚C of indoor air entering indoor coil at ˚C db. One kW electric heater element (accessory) shall be furnished.
The compressors shall be a welded high efficiency hermetic type with internal vibration isolation and be equipped with a crankcase heater.
Compressors shall be protected by a factory installed anti-cycle device and provide a 3 minute delay before compressor can restart.
Coils shall be of non-ferrous construction with mechanically bonded aluminium plate fins. Outdoor coils shall be made, of 9.52mm OD, 0.35mm thick seamless copper tubes mechanically bonded to 0.12mm thick aluminium plate fins.
Coils with multiple stage refrigeration systems shall consist of independent circuits. Face area of the coil shall not be less than M2. The coil shall be factory pressure and leak tested at 3,233 kPa pressure. The indoor coil face area shall be not less than M2.
Multi-wing propeller type fans shall be fitted at the condenser and shall be dynamically balanced, to ensure smooth airflow and shall discharge vertically and be direct driven by a weatherproof three phase squirrel cage kW induction motor.
The system shall be factory wired and all electrical wiring must comply with the Local wiring code. (Controls and control wiring shall be supplied by the contractor). Compressors and fan motors shall have both internal and current sensitive overload devices.
An automatic defrost control shall be included to accomplish defrosting (only if required) every
minutes for a period of minutes.
A low voltage transformer (24V) shall be factory installed in the unit for an external control circuit.
High pressure switch (pre-set) shall be factory installed.
The enclosure shall be a single, enclosed, weatherproof casing constructed of phosphatised, zinc coated steel with acrylic resin primer and ivory white baked enamel finish.
The unit shall be provided with hoisting plates for rigging and hoisting the unit. The hoisting plates shall be located in the base of the unit.
The unit shall have a 25mm OD male drain connection provided. The drain pipe shall be accessible from either the left or right side of the unit. A blanking cap shall be provided to cap the drain outlet not being used.
The duct (field supply) shall be fully insulated with fiber glass insulation to prevent sweating and to minimize sound.
Each unit shall have a drain pan of 1mm thick steel coated with epoxy resin enamel.
The enclosure shall have openings provided for power connections. Access for both service and installation shall be provided to compressors, control wiring, filters, electric heaters (when fitted) and fans.
Side panels and top panels shall be removable for easy service access.
The unit maximum dimensions shall be : height: mm, width: mm and depth: mm.
Due to continuous product development, these guidelines are subject to change.


HEAD OFFICE DENKI BLDG., MARUNOUCHI,TOKYO 100,TELEX J24532 CABLE MELCO TOKYO MITSUBISHI ELECTRIC CORPORATION
Issuued in January. 1999 MEE98K036 Printed in Japan.
New publication effective Jan. 1999. Specifications subject to change without notice.
Common problems, likely causes, and what to do.
| Problem | Possible cause | Remedy | |
|---|---|---|---|
| Both fan and compressor do not run. | Power failure. | Wait for power supply recovery. | p.57 |
| Both fan and compressor do not run. | Blown fuse of power source switch. | Contact your Air conditioning specialist. | p.57 |
| Both fan and compressor do not run. | Excessively low power source voltage. | Ask your electric power company. | p.57 |
| Fan runs but compressor does not run. | The set temperature of thermostat is • excessively high for cooling. • excessively low for heating. | For temperature control, • decrease the set temperature at cooling. • increase the set temperature at heating. | p.57 |
| Fan runs but compressor does not run. | The room temperature is • excessively low for cooling. • excessively high for heating. | Can not be operated as it is out of temperature control range. | p.57 |
| Fan runs but stops immediately. | Air outlet and inlet are blocked. | Remove blocking matter. | p.57 |
| Runs but without cooling/heating. | The filter installed in the field is clogged with dust. | Clean it. | p.57 |
| Runs but without cooling/heating. | Windows and doors are being opened. | Close them. | p.57 |
| Runs but without cooling/heating. | Air outlet and inlet are blocked. | Remove blocking matter. | p.57 |
| Runs but without cooling/heating. | The set temperature of thermostat is • excessively high for cooling. • excessively low for heating. | For temperature control, • decrease the set temperature at cooling. • increase the set temperature at heating. | p.57 |
| Runs but without cooling/heating. | Insufficient refrigerant charge. | Contact your Air conditioning specialist. | p.57 |