w w w . m g e u p s . c o m


SAVE THESE INSTRUCTIONS – This manual contains important instructions for MGE UPS SYSTEMS, INC. products that must be followed during operation and maintenance of the equipment.
This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at user's own expense.
◗ IEEE 587-1980/ANSI C62.41 1980 Standards for Surge Withstand Ability
◗ FCC rules and regulations of Part 15, Subpart J, Class A
◗ UL listed under 1778, Standards for Uninterruptible Power Supply Equipment
◗ IEC 61000-4-2 (ESD) : level4.
◗ IEC 61000-4-3 (Radiated field) : level 3.
IEC 61000-4-4 (EFT) : level4.
◗ IEC 61000-4-5 (Fast transients) : level4.
◗ IEEE-C6241 Category B (ring wave).
◗ IEC 61000-4-6 (electromagnetic field).
◗ IEC 61000-4-8 (conducted magnetic field).

◗ The UPS has its own internal power source (the battery). Consequently, the power outlets may be energized even if the UPS is disconnected from the AC power source.
◗ The UPS must be properly grounded.
◗ The battery supplied with the UPS contains small amounts of toxic materials. To avoid accidents, the directives listed below must be observed:
- Never burn the battery (risk of explosion).
- Do not attempt to open the battery (the electrolyte is dangerous for the eyes and skin).
- Comply with all applicable regulations for the disposal of the battery.
- Batteries constitute a danger (electrical shock, burns). The short-circuit current may be very high. Precautions must be taken for all handling: remove watches, rings, bracelets and any other metal objects, use tools with insulated handles.
- Do not lay tools or metal parts on top of batteries.
◗ A protection circuit breaker must be installed upstream and be easily accessible..
◗ The UPS can be disconnected from the AC power source by opening the input circuit breaker.
◗ UPS must be connected to a nearby power source that is easily accessible.
◗ Never block the ventilation grates of the UPS.
◗ The UPS must be installed in a controlled environment.
◗ The UPS connection instructions and operation described in the manual must be followed in the indicated order.
◗ Check that the indications on the rating plate correspond to your AC powered system and to the actual electrical consumption of all the equipment to be connected to the UPS.
◗ Before and after the installation, if the UPS remains de-energized for a long period, the UPS must be energized for a period of 24 hours, at least once every 6 months (for a normal storage temperature less than 25°C). This charges the battery, thus avoiding possible irreversible damage.
This manual is designed for ease of use and easy location of information.
Typographical conventions use “< >” angle brackets in procedures to denote a prompt for User action:
For example: 1. After the selections are complete, click on the button.
This manual uses four icon symbols with text to convey important information and tips.
Safety of Persons iii 86-86000-00 A01

RECORD ALL SERIAL NUMBERS FOR EX 5/7/11 RT AND ACCESSORIES.
THESE SERIAL NUMBERS WILL BE REQUIRED IF YOUR SYSTEM NEEDS SERVICE.
NUMBERS IF SERVICE IS REQUIRED!
Power Module SERIAL NUMBER: ___________________________________________________
Battery Module SERIAL NUMBER: ____________________________________________________
Transformer SERIAL NUMBER: ______________________________________________________
ADDITIONAL MODULES SERIAL NUMBERS:
____________________________ ______________________________
____________________________ ______________________________
____________________________ ______________________________
____________________________ ______________________________
____________________________ ______________________________
____________________________ ______________________________
____________________________ ______________________________
____________________________ ______________________________
____________________________ ______________________________
____________________________ ______________________________
iv 86-86000-00 A01

EX 5RT / EX 7RT / EX 11RT System Installation and User Manual 86-86000-00
Copyright © 2004 MGE UPS SYSTEMS, INC. All rights reserved. Printed in U.S.A.
MGE UPS SYSTEMS, INC. 1660 Scenic Avenue Costa Mesa, CA 92626 (714) 557-1636
v 86-86000-00 A01

(This page left blank intentionally)
vi 86-86000-00 A01



section description page
2.0 Scope 2 — 1 2.1 Unpacking and Parts Check 2 — 1 2.2 Contents of EX 5/7/11 RT System 2 — 2 2.3 Installation in Tower Configuration 2 — 4 2.4 Installation in Rack Mounting Configuration 2 — 5 2.4.1 Adjustment of Front Panel Logo and control panel for Rack Orientation 2 — 5 2.5 Prepare Battery Module for Rack Mounting 2 — 6 2.6 Power or Battery Module Rack Mounting 2 — 7 2.6.1 Rear Support Brackets Installation 2 — 8 2.6.2 Input/Output Box Bracket System Installation 2 — 8 2.7 Communication Ports 2 — 9 2.7.1 Connecting the RS232 Communication Port 2 — 9 2.7.2 Connecting the Dry (Relay) Contact Communication Port 2 — 10 2.7.3 Installation of Optional Network Management Card 2 — 10 2.7.4 Remote Emergency Power Off (REPO) Communication Port .2 — 12 2.8 Connecting the Input and Output Power Cables to the Input/Output Box 2 — 13 2.8.1 Flexible Cordage and Conduit Installations 2 — 13 2.8.2 System Connections with Common Normal and Bypass AC Sources 2 — 15 2.8.3 Connecting EX RT Transformer 2 — 16 2.8.4 System Connections with Separate Normal and Bypass AC Sources 2 — 17 2.8.5 System Connections as Frequency Converter (without Bypass AC Source) 2 — 18 2.9 Connection of Battery Module, EXB 2 — 19 2.10 Connection of CLA Module 2 — 20
section description page
3.0 Scope 3 — 1 3.1 Initial Startup 3 — 1 3.2 UPS Personalization 3 — 2 3.2.1 Accessing personalization with front panel buttons 3 — 2 3.2.2 Accessing personalization through external software 3 — 4 3.2.3 Final startup sequence 3 — 4 3.3 Operating Modes 3 — 5 3.3.1 Normal (double conversion) Mode 3 — 5 3.3.2 ECO Modes 3 — 6 3.4 Operation on battery power 3 — 7 3.4.1 Transfer to Battery Power 3 — 7 3.5 Return of Normal AC source 3 — 8 3.6 Shutdown 3 — 8
Contents c ii 86-86000-00 A01

section description page
4.0 Scope 4 — 1 4.1 Information Technology (IT) Network and Industrial Operating Modes 4 — 1 4.2 Troubleshooting 4 — 2 4.3 Hot Swapping the Power Module 4 — 4 4.4 Re-connecting the power module 4 — 5 4.5 Hot Swapping the Battery Module 4 — 6 4.5.1 Disconnecting the Battery Module 4 — 6 4.5.2 Re-connecting the Battery Module 4 — 6
section description page
5.0 Electrical Specifications 5 — 1 5.1 System Input/Output Power Ratings 5 — 1 5.2 System Overload Characteristics 5 — 1 5.3 System Backup Characteristics 5 — 1 5.4 System Short Circuit Protection 5 — 2 5.5 Accessories Electrical Characteristics 5 — 2 5.6 Heat Rejection 5 — 2 5.7 Environmental Characteristics 5 — 2
MGE Warranty Proprietary Rights Statement
User Information Product information Warranty Extension (Warranty+) not available on products
MGE Service and Repair Who to Contact Scheduling Field Service Engineer Support Return for Repair (RMA)
Reorder Form RO — 1
Contents c iii 86-86000-00 A01

figure description page
1-1: Tower Configurations with Power Module, Battery Module, and optional Transformer Module 1 — 4 1-2: Rack Configurations with Power Module, Battery Module, and Transformer Module 1 — 5 1-3: Rear panel of the Power Module 1 — 6 1-4: Rear Panel of the Battery Module 1 — 6 1-5: Rear Panel of the optional Transformer Module. (PN 86003) 1 — 7 1-6: View of typical control panel interface 1 — 7 1-7: Power Module Rack Mounting Kit 1 — 8 1-8: Telescopic rails for the Battery/Transformer/CLA module Rack mounting 1 — 8 1-9: Typical back-up time with multiple EXB’s at full load 1 — 9 1-10: Typical Battery Integration kit with casters setup 1 — 10 1-11: Typical Transformer Module contents and connections 1 — 11 1-12: Connection for CLA Module and EX 5/7/11 RT 1 — 12
2-1: Contents of Standard HV EX 5RT (PN 86050) / EX 7RT (PN 86070) / EX 11RT (PN 86110) System 2 — 3 2-2: Tower Configuration of Standard System and Optional Transformer Module 2 — 4 2-3: Typical orientation of the logo and control panel. (Power Module shown) 2 — 5 2-4: Accessing Battery Pack 2 — 6 2-6: Rack mounting of the power module onto the rails 2 — 7 2-7a: Rear Support Brackets 2 — 8 2-7b: Input/Output Box Bracket System 2 — 8 2-8: RS232 Communication Cable Connection 2 — 9 2-9: Relay Pin Connections for Communication Port 2 — 10 2-10: Communication Card Slot with SNMP/Web Network Management Card installed 2 — 10 2-10a: Activation of remote power off function using a contact normally open switch 2 — 12 2-10b: Activation of remote power off function using a contact normally closed switch 2 — 12 2-12a: Step 1 & 2; Typical plastic and metal coupling installations 2 — 13 2-12b: Step 3; Typical Straight Metal Conduit installation 2 — 14 2-12c: I/O Box Terminal Block Diagram 2 — 14 2-13: Normal AC Input and Output Cables installation 2 — 15 2-14: View of EX RT transformer connected downstream for 120/208/240 Vac outputs (shown with one EXB) 2 — 16 2-15: Normal AC Input, Bypass AC, and Output Cables Installation 2 — 17 2-16: Accessing Terminal Blocks for Input and Output power cables 2 — 18 2-17: Rear view of battery module cable connections 2 — 19 2-18: Rear view of CLA module cable battery and AC input connections. . .2 — 20
Contents c iv 86-86000-00 A01

figure description page
3-1: Initial Startup Display 3 — 1 3-2: Control Panel with scroll up and down buttons 3 — 2 3-3: Configuration used to provide full redundancy (2N) to critical loads 3 — 3 3-4: Normal (double conversion) mode 3 — 5 3-5: ECO mode display 3 — 6 3-6: Transfer, Threshold and End of backup time 3 — 7 3-7: Shutdown display, circuit breaker, and AC source switch 3 — 8
4-1: Disconnecting the power module 4 — 4 4-2: Reconnect the power module 4 — 5 4-3: Rear view of the battery module 4 — 6
5-1: Power supplied as a function of input voltage (left), and Permissible UPS overloads as a function of time (right) 5— 1
table description page
1: EX RT Model Descriptions and Contents 1 — 2 2: Optional Accessories (See section 1.5 for description) 1 — 3 3: Power Module Ratings 1 — 4 4: Battery Module Ratings 1 — 4 5: Battery backup time chart 1 — 12
3-1: Local Settings 3 — 3 3-2: Output features 3 — 3 3-3: ON/OFF features 3 — 4 3-4: Battery features 3 — 4
4-1: Network and Industrial Modes of Operation 4 — 1 4-2: Troubleshooting not requiring MGE after-sales support 4 — 2 4-3: Troubleshooting requiring MGE after-sales support 4 — 3
5-1: EX 5/7/11 RT Input and Output Characteristics 5 — 1 5-2: Back-up Time ( in minutes) 5 — 1 5-3: Battery Recharge time to recover 90% of the rated backup time after discharge at full load 5 — 2 5-4: Full load heat rejection in BTU’s/hr 5 — 2
Contents c v 86-86000-00 A01

(This page left blank intentionally)
c vi 86-86000-00 A01

Thank you for selecting an MGE UPS SYSTEMS, INC. (MGE) product to protect your electrical equipment.
The product you selected is a part of the EX RT series.The EX RT series is a family of Uninterruptible Power Supply (UPS) designed to provide safe, and reliable AC power backup for sensitive electrical equipment. To discover the entire range of MGE products, we invite you to visit our website at www.mgeups.com or contact your representative at (800) 523-0142.
This manual describes the installation and operation of standard HV EX 5/7/11RT systems within the EX RT product family. For a complete description of the EX RT product family and its available options, please refer to the tables below:
Introduction is a general description of system configurations of the EX 5/7/11 RT, and its mechanical ,electrical characteristics. Additionally there is an optional accessories section with important information on MGE products that will enhance the performance of the EX 5/7/11RT. Please contact your MGE representative for detailed information on these options.
2 Setup and Installation
Setup and Installation guides the user through tools and equipment required for connecting the EX 5/7/11 RT and battery installation or replacement. Included are assembly instructions, power cable connections with wire diagrams for configuring the product to hardware specifications.
Operation describes the EX 5/7/11RT system characteristics of indicators and controls, modes and specifications. The user procedures include performing software programming that will maintain optimal performance.
Maintenance includes a troubleshooting guide of symptoms and possible solutions, hot swapping the power module, battery module, and testing scenarios.
Electrical and Mechanical specifications for the EX 5/7/11 RT.
A Glossary provides definitions of abbreviations and terms used in this manual.
1 — 1 86-86000-00 A01 Introduction

Model Part Power Module Battery Module Transformer Power Module Battery Module SNMP/Web
Number 86055 86075 86115 86079 86119 Module Rail Kit 86001 Rail Kit 86002 Network
(120/208/240Vac) Mgt. Card
86003 66074 5kVA 86050 X X HV EX 5RT
5kVA 86052 X HV EX 5RT Network Pack
5kVA 86050-01 X X X LV EX 5RT
5kVA 86052-01 X (x2) X LV EX 5RT Network Pack
7kVA 86070 X X HV EX 7RT
7kVA 86072 X HV EX 7RT Network Pack
7kVA 86070-01 X X X LV EX 7RT
7kVA 86072-01 X (x2) X LV EX 7RT Network Pack
11kVA 86110 X X HV EX 11RT
11kVA 86112 X HV EX 11RT Network Pack
11kVA 86110-01 X X X LV EX 11RT
11kVA 86112-01 X (x2) X LV EX 11RT Network Pack
Introduction 1 — 2 86-86000-00 A01
System Description Contents

86001 Rail Kit for Power Module EX 5/7/11 RT
86002 Rail Kit for Battery/Transformer/CLA Module
86005 Battery Integration Kit with Casters
86006 Battery Extension Cable Kit
86008 Battery Chassis Empty EXB RT W/EPO
86009 I/O Box 5/7kVA UL/US
86010 I/O Box 11kVA UL/US
86012 I/O Box Bracket System
86013 Rear Bracket Supports
Introduction 1 — 3 86-86000-00 A01
Part Number Description


Apparent Power, kVA 5 7 10@ 200/208/250 VAC Output 11@ 220/230/240 VAC Output
Active Power, kW 4 4.9 8@ 200/208/250 VAC Output 7.3@ 220/230/240 VAC Output
The EX 5/7/11 RT systems can be set up in tower and rack configurations.
Figure 1-1: Tower Configurations with Power Module, Battery Module, and optional Transformer Module.
E X B R T E X 1 1 R T
Introduction 1 — 4 86-86000-00 A01


Figure 1-2: Rack Configurations with Power Module, Battery Module, and Transformer Module.
EX 5RT/7RT (3U) 5.16” x 17.49” x 25” 49.6 lbs (22.5 kg) (131 x 444 x 635mm)
EX 11RT (3U) 5.16” x 17.49” x 25” 60.6 lbs (27.6 kg) (131 x 444 x 635mm)
EXB 5 RT/ 7 RT (3U) 5.16” x 17.49” x 25” 142 lbs (64.5 kg) (131 x 444 x 635mm)
EXB 11RT (3U) 5.16” x 17.49” x 25” 151 lbs (68.5 kg) (131 x 444 x 635mm)
EX RT (3U) 5.16” x 17.49” x 25” 173 lbs (78.5 kg) Transformer (131 x 444 x 635mm)


EX 5RT Power Module part number 86055 EX 7RT Power Module part number 86075 EX 11RT Power Module part number 86115
Knockout for entry of Bypass AC source conduit. 11
Connectors for automatic detection of additional battery module(s) (to the UPS or to other battery modules).
Battery power connectors (to the UPS or to other battery modules).
Battery Circuit Breaker with Remote Emergency Power Off (REPO) shunt trip.


UPS ON button (or function button in personalization mode). 23

Optional Accessories describes the options available for upgrades and enhancement of the EX 5/7/11RT system. Detailed installation of the unit is described in following sections.
To ensure a successful installation, all procedures should be followed in their correct sequence. Note that any unauthorized installation may cause damage to the UPS(s) and void the MGE warranty.
This kit is for rack mounting the power module in a 19" enclosure. See section 2.6 for rack installation of power module.
Figure 1-7: Power Module Rack Mounting Kit.
Front mounting brackets.
Rear support brackets, part number 86013.
Telescopic rails, 695 mm to 1015 mm
length (27.36" to 39.96").
Input/Output Box bracket system, part
number 86012.
This kit is for rack mounting of the battery/step-down transformer/CLA module in 19" enclosure. See section 2.6 for rack installation of power module.
Figure 1-8: Telescopic rails for the Battery/Transformer/CLA module Rack mounting.
Front mounting brackets.
Rear support brackets, part number
length (27.36" to 39.96"). 26
Telescopic rails, 695 mm to 1015 mm
Introduction 1 — 8 86-86000-00 A01
(Part Number 86001) · (Part number 86002)

(EXB 5/7 RT; PN 86079, EXB 11RT; PN 86119)
Standard HV EX 5/7/11RT system (one Power Module, EX 5/7/11 RT, and one Battery Module, EXB 5/7/11RT) offers a standard backup time of 5 to 12 minutes at full load.
To increase backup time, it is possible to connect up to 5 additional EXB 5/7/11 RT modules to the EX 5/7/11 RT module. See section 2.10 for connections between Power Module (EX 5/7/11 RT) and Battery Module (EXB 5/7/11 RT)
Figure 1-9: Typical back-up time with multiple EXB’s at full load.
Standard HV EX 5/7/11RT system
EXB 5 RT
EXB 5 RT
EXB 5 RT
EXB 5 RT
EX 5/7/11RT EXB 5/7/11RT
EXB 7 RT EXB 7 RT EXB 7 RT EXB 7 RT EXB 7 RT
+ +
EXB 11 RT
EXB 11 RT
EXB 11 RT
EXB 11 RT
45 min 30 min 57 min 42 min 70 min 53 min
See Appendix for additional Back-up time information.
( 6 ft / 1.8 m, Part number 86006)
This extended battery cable kit will be used instead of the standard battery cable when battery modules (EXBs) are distant from each other (located in two different enclosures, for instance).
The battery extension cable kit includes a 6 ft long, straight connector battery power cable and a 6 ft. long battery detection cable.
Introduction 1 — 9 86-86000-00 A01


Battery Integration Kit is a cart, designed to hold up to 8 modules. It has swivel wheels with brakes, leveling feet, seismic floor mount panels, plates to lock modules and hardware included. Modules not included.
Figure 1-10: Typical Battery Integration kit with casters setup.
- I/O Box 5/7kVA Part number 86009 - I/O Box 11kVA Part number 86010
Introduction 1 — 10 86-86000-00 A01




Extended back-up time (up to 8 hours at full load) requires a high power battery cabinet connected to the EX 5/7/11RT via the CLA module.
Figure 1-12: Connection for CLA Module and EX 5/7/11 RT.
Total battery voltage : 240 VDC (20 x 12VDC, one string).
The battery capacity must be set within the UPS (5 Ah increment possible, see UPS Personalization section 3.2.
Introduction 1 — 12 86-86000-00 A01

Installation guides the user through tools and equipment required for making input/output power and communica- tion cable connections, and battery installation and replacement. It provides assembly instructions, power cable connections with wire diagrams for configuring the product to hardware specifications.
Once the EX 5/7/11RT system has been inspected and received from the shipping courier, the unit should be moved to a position as close to the final installation location as possible. See Figures 2-1on page 2-3.
All Modules are shipped in separate boxes.
Prior to any installation, the following items should be observed upon receipt of the EX 5/7/11 RT.
2 — 1 86-86000-00 A01 Installation

EX 5RT /EX 7RT/ EX 11RT. Stabilizer Bracket and hardware.
Two sets of tower stands. EXB 5/7/11 RT.
RS232 communication cable. Tower stand expanders.
Product documentation. Battery Power cable.
Input/Output Box. (With 9 insulated ferrules for Battery/EX RT transformer/CLA
stranded wires.) module rack mounting kit, PN 86002.
(PN 86009 for EX 5/7RT; 86010 for EX 11RT)
Battery detection cable.
Solution-Pac CD. EXB Documentation.
Power Module rack mounting kit, PN 86001 Bezel hex drive.
(optional, but standard with Network Pack version).
SNMP/Web Network Management Card, PN 66074.
(optional, or standard with Network Pack version)
Installation

Figure 2-1: Contents of Standard HV EX 5RT (PN 86050) / EX 7RT (PN 86070) / EX 11RT (PN 86110) System.
- EX 5RT Power Module Part number 86055 - EX 7RT Power Module Part number 86075 - EX 11RT Power Module Part number 86115
OFF
O
- I/O Box 5/7kVA Part number 86009 - I/O Box 11kVA Part number 86010
1 2 ON
ETHERNET RS232
Standard only with Network Pack option. - EX 5RT network Pack Part number 86052-01 - EX 7RT network Pack Part number 86072-01 - EX 11RT network Pack Part number 86112-01
41 43 44
- EXB 5RT Battery Module Part number 86079 - EXB 7RT Battery Module Part number 86079 - EXB 11RT Battery Module Part number 86119
Standard only with Network Pack version. See 1.5.2.
Installation 2 — 3 86-86000-00 A01


Follow the numerical sequence to assemble tower stands and tower stand expanders, shown in Figure 2-2.
Figure 2-2: Tower Configuration of Standard System and Optional Transformer Module.
E X B R T E X 1 1 R T
Use the same procedure for tower mounting multiple battery modules, if applicable.
E X B R T E X 1 1 R T

2.4.1 Adjustment of Front Panel Logo and control panel for Rack Orientation.
To prepare the front panel logo and LCD display for rack orientation, of all modules. (including transformer or CLA module, if equipped).
Proceed as follows:
OFF ON
E X 1 1 R T
OFF ON
OFF ON
OFF ON
Installation 2 — 5 86-86000-00 A01


The battery module is very heavy. To ease its rack mounting, we strongly recommend to remove the battery pack from the battery module, as explained below. See Section 1.2.2 for battery module weight.
Installation 2 — 6 86-86000-00 A01

(optional rack mounting kits required, part number: 86001 and 86002)
The rails and necessary mounting hardware are supplied by MGE UPS SYSTEMS, INC.
Proceed as follows:
Figure 2-6: Rack mounting of the power module onto the rails.
Installation 2 — 7 86-86000-00 A01

(Part number 86013, included with rack mounting kits, part numbers: 86001 and 86002)
These brackets prevent the power module from moving when the entire rack enclosure is moved.
Proceed as follows:
Figure 2-7a: Rear Support Brackets.
(Part number 86012 included with power module rack mounting kit, part numbers: 86001)
This bracket system keeps the I/O Box stationary while hot swapping the power module. It will then be easier to slide the replacement module into the connectors of the I/O Box.
2 & 3. Secure large bracket (with supplied screws) to rails at the rear of module.
Figure 2-7b: Input/Output Box Bracket System.
Installation 2 — 8 86-86000-00 A01

EX 5/7/11RT provides 3 communication methods that can be used simultaneously:
◗ The COM port provides RS232 communications using MGE Serial HID UPS Transfer (SHUT)protocol. This COM Port is compatible with Personal Solution Pac (PSP) to shutdown one computer. Personal Solution Pac is included in the Solution Pac CD-Rom. For Network Management or multiple computer shutdowns an optional network card must be purchased.
◗ The Dry Contact Port is used for basic signaling or for protection of IT systems like IBM iSeries (formerly AS400) and more.
◗ The slot is compatible with any MGE UPS SYSTEMS, INC. communication card (check www.mgeups.com web site for the complete list of compatible cards)
The EX 5/7/11 RT System can now communicate with Personal Solution Pac for power management. UPS config- uration settings are done by Personal Solution Pac for Windows.
Figure 2-8: RS232 Communication Cable Connection.

Installation 2 — 9 86-86000-00 A01

The system status is indicated by the connection of common pin (Pin 5) to the appropriate pins. Refer to the pin explanations below for details.
Figure 2-9: Relay Pin Connections for Communication Port.
Pin 1, 2: not used.
Pin 3: Remote Power Off signal (5 to 27 VDC, 10 mA max).
Pin 5: User common.
Pin 6: Operation on automatic bypass.
Pin 7: Low battery.
NO NC NO NO
Pin 9: Operation on battery.
Legend:
NO: contact normally open.
NC: contact normally closed.
It is not necessary to shut down the UPS to install the optional communications card, except for USB card. Following is a typical installation of the Network Management Card, (PN 66074, standard with the network pack option.)
Proceed as follows:
Figure 2-10: Communication Card Slot with SNMP/Web Network Management Card installed.
Installation 2 — 10 86-86000-00 A01

A wide range of optional cards will allow your UPS to talk to nearly all equipment management systems, making integration faster and easier. All these cards can plug directly into the UPS, saving time and money on your next UPS project. (Meta UPS Card and U-Talk /Basic Acquisition Cards are used exclusively with Multi-slot.)
Dual U-Talk/Basic Card (66060) Provides two communications ports that may be configured
for serial link or AS/400 type dry contacts.
ModBus Card (66061) Interface your UPS with a Building Management System.
Dual COM Ports Card (66066) This card has two independent RS232 communication ports on which it can be connected.One for connecting monitoring software (included) and one for remote control panel UPS control.
USB Card (66067) Take advantage of the latest and fastest communication protocol for Microsoft Windows 2000/XP or Mac OSX.
Dual Volt Free Contacts (66068) The two ports are used to supply UPS status information
Card for AS/400 or one port can be used as a Remote Power Off (REPO) port.
Alarm Relay Card (66069) Six output relays show UPS status and two status inputs are used with the Galaxy 3000 UPS.
XML-Web Card (66073) XML-Web Card acts as a web page for your UPS information. Used along with XML-ClientTM software, up to 50 servers or workstations will be protected and can monitor the UPS with a simple web browser. Security is handled with the SSL protocol, used by many websites to safeguard sensitive password information.
SNMP-Web Card (66074) The SNMP/Web 10/100BT communications card is both an SNMP agent and an HTTP/Web server. Therefore, it enables UPS supervision from any Network Monitoring System using SNMP traps or simply from any web browser (Internet Explorer, Netscape Navigator, etc.) Orderly system shutdown of up to 32 protected servers can be established using MGE’s Solution-Pac/WAN software suite.
Installation 2 — 11 86-86000-00 A01

The end user is responsible for the installation of an emergency power off function. Installation must be carried out in compliance with local code regulations.
To shutdown the entire system completely in case of emergency:
Disconnect the AC input to the power module.
Turn off the circuit breaker of the battery module connecting to the power module.
Turn off the circuit breaker of the subsequent battery modules, if applicable.
All these steps above should be performed via a single device.
To simplify the last two steps above, the power module provides an RJ-45 connector on the back panel, called Remote Emergency Power Off (REPO) port. Upon applying a voltage source (5-27VDC, 10mA max.) to pins 2, 4 of this port, the power module will send a signal to trip off the shunt trip on each circuit breaker of all battery modules via the battery detection cable simultaneously. Refer to the diagram below for details.
Figure 2-10a: Activation of remote power off function using a contact normally open switch.
5 4 3 2 1 6
Figure 2-10b: Activation of remote power off function using a contact normally closed switch.
5 4 3 2 1 6
Signal:
Current 10 mA (max)
Installation 2 — 12 86-86000-00 A01

Before carrying out any connections, check that battery circuit breaker is OFF and that the upstream protection devices (Normal and Bypass AC sources) are open (OFF).
EX 5/7/11 RT UPS always comes from factory with Normal and Bypass AC inputs already connected together, using a shunt.
Figure 2-12a: Step 1 & 2; Typical plastic and metal coupling installations.
1 1. Knockout die stamp circles.
Outer circle is for Plastic strain relief
OFF
O
Inner circle is for Metal strain relief
Knockout die stamp circles (on terminal block cover) have two sizes that fit
either plastic or metal coupling. Plastic coupling is for
flexible cordage and metal coupling is for solid wires. Knock out appropriate circle for your application.
a) Secure strain relief body onto the knockout plate.
b) Strip the jacket back to expose the three wires. Strip the insulation of each wire back 1/2”. Insert the ferrules as shown to each wire.
OFF O
c) Slide the cordage into the strain relief and secure the wires into the terminal blocks using the guide printed on bottom of I/O box.
d) Secure the cordage retainer nut.
OFF O
a) Secure strain relief body to knockout plate as shown.
b) Insert three wires through flexible conduit and bend 90°.
c) Strip the insulation back 1/2” to expose solid wire and secure three wires into the terminal block using guide printed on bottom of I/O box.
d) Install strain relief cover using two screws.
Installation 2 — 13 86-86000-00 A01


Figure 2-12b: Step 3; Typical Straight Metal Conduit installation.
a) Secure strain relief onto the terminal block cover as shown.
c) Strip the insulation of each wire back 1/2” to expose solid wire.
d) Secure three wires into the terminal block using guide printed on bottom of I/O box.
e) Twist the conduit onto the coupling body as shown.
Output 200/208/220/230/240Vac Normal AC Source 200/208/220/230/240Vac Bypass AC Source 200/208/220/230/240Vac
Installation 2 — 14 86-86000-00 A01


Figure 2-13: Normal AC Input and Output Cables installation.


This module is to provide isolated 120/208/240 VAC outputs to the protected loads.
Figure 2-14: View of EX RT transformer connected downstream for 120/208/240 Vac outputs (shown with one EXB).
Terminal Block Transformer Module Connection diagram (located on bottom of Transformer I/O Box)
Terminal Block capability : AWG 4 solid or stranded wire.

Figure 2-15: Normal AC Input, Bypass AC, and Output Cables Installation.
Proceed as follows:
O
earth ground wire first.
O
See section 2.8.3 for connecting EX RT Transformer, if applicable.
O
data Reset 100 10
ETHERNET
MAC=00E0D8FF855E
1 2 ON
IP=
Installation 2 — 17 86-86000-00 A01


Figure 2-16: Accessing Terminal Blocks for Input and Output power cables.
See section 2.8.3 for connecting EX RT Transformer, if necessary.
Installation 2 — 18 86-86000-00 A01


Figure 2-17: Rear view of battery module cable connections.


◗ DC Input Cable cross-section (not provided): maximum 4 AWG solid or stranded wire.
◗ AC input cable cross-section (not provided): maximum 16 AWG solid or stranded wires.
Figure 2-18: Rear view of CLA module cable battery and AC input connections.
Installation 2 — 20 86-86000-00 A01

Operation describes EX 5/7/11RT system characteristics of indicators and controls, modes and specifications and theory of operating the EX 5/7/11RT. The user procedures include performing software programming that will maintain smooth performance. Refer to Figure 1.6 for descriptions of circled numbers.
The load is powered via the bypass AC source, but not protected by the UPS.
Batteries are recharging, an eight-hour recharge period is necessary to get full backup time.
LED is ON.
Figure 3-1: Initial Startup Display.
3 — 1 86-86000-00 A01 Operation

It is possible to enter this mode through the front panel buttons or the Personal Solution-Pac software for Windows included in the MGE UPS SYSTEMS, INC. Solution- Pac power management suite CD-ROM.
◗ Press "scroll up" and "scroll down" function buttons together for more than 3 sec- onds.
◗ Press the function button placed under the “ENT” word to enter the set up mode and follow the LCD messages using the buttons now defined as select keys. See Tables: 3-1, 3-2, 3-3, and 3-4 for settings.
Figure 3-2: Control Panel with scroll up and down buttons.
OFF ON
Operation 3 — 2 86-86000-00 A01

Table 3-1: Local Settings.
Language English French, Spanish, German, Italian
Date / time format International format US format
Date / time change GMT (Greenwich Mean Time) MM-DD-YYYY/HH:MM adjustable
Audible alarm Quick beeps Slow beeps
Table 3-2: Output features.
Output voltage 208 Volts AC 200/208/220/230/240/250
Frequency converter Disabled Enabled Bypass AC source disabled
Output frequency Auto ranging 50/60 Hz User selectable under frequency converter mode
Eco mode Disabled Enabled See glossary
Hot standby Disabled Enabled Full redundancy (see Figure 3-3)
Operating mode IT Network Industrial (*) See Section 4.1
Bypass When bypass OK (**) When bypass NOK (**) (*) Transfer
Interrupt time 10 ms 10 to 200 ms Interrupt time calibration during (by steps of 10 ms) during load transfer on Bypass AC source out of tolerances
Overload level 102% 50/70%
(*) : - Select "IT Network" for computer loads.
- Select "Industrial" when bypass NOK in case of absolute need for service continuity (with potential
10 ms interrupt).
(**) UPS will switch to Bypass AC Source if it is within the set tolerances.
Figure 3-3: Configuration used to provide full redundancy (2N) to critical loads.
Full redundancy configuration offers better protection to critical load, whereas the first UPS acts as the Bypass AC Source for the second UPS.
NORMAL AC
LOAD
Operation 3 — 3 86-86000-00 A01
Protective Device · Utility AC Source · Protective Device

Table 3-3: ON/OFF features.
Cold start Disabled Enabled Start on battery.
Forced reboot Enabled Disabled Enables automatic restart of the system even if normal AC source is restored before the end of the shutdown sequence.
Automatic restart Enabled Disabled UPS restarts automatically when normal AC source is restored.
Sleep mode Disabled Enabled Automatic shutdown on battery if output load level
Remote Command Enabled Disabled Enables shutdown or restart orders from software.
Table 3-4: Battery features.
Battery test Every week No test/daily/monthly
Pre-Alarm 20% 0 to 100% Low battery signal;1% increment
Runtime choice UPS reads # and type From 65 to 400 Ah Requires EX 5/7/11RT CLA if of battery using options (see section 1.5.4 modules connected. “Battery extensions cable kit”)
Battery deep discharge Enabled Disabled If disabled, loss of protection MGE UPS SYSTEMS,INC. warranty.
Insert the Solution-Pac CD ROM in your CD drive.
◗ At the first Navigator Screen, select "Installation" and follow the instructions to install Personal Solution-Pac for Windows.
◗ If nothing appears, launch startup.exe
◗ Then go to "Advanced settings" and "UPS settings".
Please note that the Linux/Unix/MacOS versions of Personal Solution-Pac do not include this feature.
Press the button more than 3 seconds.
◗ After UPS internal test sequence, the green LED goes on.
Operation 3 — 4 86-86000-00 A01


This is the standard operating mode, set by the factory.
Scroll up and scroll down function buttons allow you to read the UPS measurements (Normal AC source voltage, Bypass AC source voltage, operating mode, battery capacity and UPS Serial Number).
The load is now powered by the UPS battery.


The main advantage of the ECO mode (see glossary) is that it reduces the consumption of electrical power.
The load is supplied with AC power but not protected in ECO mode.
The load is automatically supplied in Normal mode via the Normal AC input.
The load is powered by the battery power from the UPS.
Operation 3 — 6 86-86000-00 A01


Figure 3-6: Transfer, Threshold and End of backup time.
The load continues to be protected by the UPS when the Normal AC source is not available. Power is supplied by the battery.
◗ This indicate the load is supplied by the battery.
◗ The display indicates the battery remaining backup time.
◗ Low battery warning on display. There is very little remaining battery backup time. Close all appli- cations because UPS automatic shutdown is pending.
◗ The load is transferred to the Bypass AC source if available. In this case:


After an outage, the UPS restarts automatically when AC power is restored (unless this function has been disabled via UPS personalization).
Figure 3-7: Shutdown display, circuit breaker, and AC source switch.
The load is no longer protected by the UPS. It is powered via the bypass AC source. If the UPS is set in frequency converter mode, the load will not be powered.
If the bypass AC source is out of tolerance, the UPS will generate a calibrated 10msec output interrupt.
Operation 3 — 8 86-86000-00 A01

Maintenance includes a troubleshooting guide of symptoms and possible solutions, Hot swapping the power module and Battery Module, and testing scenarios.
Table 4-1: Network and Industrial Modes of Operation.
Overload, and Bypass Load is transferred to Bypass AC source. Same as I/T network mode, but AC source in tolerance. UPS returns to normal mode if overload to the UPS does not return to is removed. normal mode if overload is removed.
Overload, and Bypass The UPS shuts down and load is not Load is transferred to Bypass AC source not in tolerance. transferred to Bypass AC source. AC source with 10 milli- seconds output break. The UPS does not return to normal mode if overload is removed. Output short circuit and Bypass The load remains powered by the UPS. Load is transferred to Bypass AC source in tolerance. The UPS shuts down after 3 minutes AC source, the UPS returns to if the short circuit remains normal mode if the short circuit is removed.
Output short circuit and Bypass The load remains powered by the UPS. The load is transferred to AC source not in tolerance. The UPS shuts down after 3 minutes Bypass AC source with if the short circuit remains. 10 milliseconds output break. The UPS does not return to normal mode if the short circuit is removed.
4 — 1 86-86000-00 A01 Maintenance

◗ If any of LED's or is on, there is an operating anomaly or an alarm.
◗ Use "scroll up" or "scroll down" function button to reset the audible alarm.
◗ Troubleshooting not requiring MGE UPS SYSTEMS, INC. after-sales support:
Table 4-2: Troubleshooting not requiring MGE after-sales support.
LED is on, and Bypass AC AC source is not connected Rewire correctly the normal AC source is present to the correct terminals. source. the alphanumeric display shows BAD CONNECTION REWIRE AC NORMAL
LED is on, Load supplied by bypass AC source. Push the ON button for more than 3 the alphanumeric display shows: seconds. LOAD LEVEL XX kW / XX KVA
LED is on, and Bypass AC UPS overload Check if any device is shorted or failed. source is present the alphanumeric display shows: THERMAL OVERLOAD 1XX%
LED is on, Short circuit conditions on output Check if any device is shorted or devices. failed. the alphanumeric display shows: CURRENT OVERLOAD
LED is on, 180° degree phase shift between Check if bypass source is correctly bypass and normal AC source. wired but the alphanumeric display shows: (in case of upstream transformer use). BYPASS REVERSE REWIRE BYPASS Audible alarm is on, Input/Output box not Check if the Input/Output box the alphanumeric display shows: installed correctly. is correctly installed. See section 2.8. I/O BOX REMOVED
Maintenance 4 — 2 86-86000-00 A01
Symptom Indication Correction

Table 4-3: Troubleshooting requiring MGE after-sales support.
LED and are on, Internal fault Call the after sales support department. Bypass AC Source is present and transfer of load and audible alarm is on. on bypass AC source the alphanumeric display shows: xxx FAULT
LED is on, and audible alarm Battery fault during the battery test. Call the after sales support department. is on, the alphanumeric display shows BATTERY FAULT
LED is on, Static switch failure Call the after sales support department. the alphanumeric display shows: SHUTDOWN STATIC SW FAILED
Audible alarm is on, Batteries may have exceeded Follow the battery replacement procedure the alphanumeric display shows: their rated life period. Battery in section 4.5. END OF WARRANTY capacity is severely reduced.
Maintenance 4 — 3 86-86000-00 A01
Symptom Indication Correction


This operation can be performed without interrupting the load.
LED is on (If LED is not on, do not turn the manual bypass and call the after sales support department).
The connected equipment is powered by the Bypass AC source.
Maintenance 4 — 4 86-86000-00 A01

This operation can be performed without interrupting the load.
Figure 4-2: Reconnect the power module.
power module.
4 kW/ 5 kVA
is on the ON position.
The green LED is on, and the connected equipment is now protected by the UPS.
Maintenance 4 — 5 86-86000-00 A01


The connected equipment is powered by the UPS, but not protected.
It is also possible to replace battery pack instead of battery module.
See section 2.5 and follow instructions for battery pack replacement.
Maintenance 4 — 6 86-86000-00 A01

5.1 System Input/Output Power Ratings
Table 5-1: EX 5/7/11 RT Input and Output Characteristics.
Normal AC Source 208 to 240 Volts AC 40 to 70 Hz
Bypass AC Source 208 to 240 Volts AC* 48 to 52 Hz**
Load Output 120/240Vac Volts AC 50/60 Hz autoranging (120/208/240Vac (or frequency converter) are possible with transformer module)
(*): depends on output voltage setting, can be modified by software. (**): set to +/- 4% by default, (1,2,4,8% are possible values), can be modified by software.
Figure 5-1: Power supplied as a function of input voltage (left), and Permissible UPS overloads as a function of time (right).
0.5s t 30s
5.3 System Backup Characteristics
Table 5-2: Back-up Time ( in minutes).
System Load Percentage 30% 50% 70% 100% Standard 11kVA 25 14 9 5 Standard 11kVA + 1 EXB 61 30 20 14 Standard 11kVA + 2 EXB 96 53 34 22 Standard 11kVA + 3 EXB 135 84 51 30 Standard 11kVA + 4 EXB 172 102 67 42 Standard 11kVA + 5 EXB 201 113 87 53 Standard 7kVA 37 21 12 7 Standard 7kVA + 1 EXB 80 53 30 20 Standard 7kVA + 2 EXB 124 83 55 32 Standard 7kVA + 3 EXB 185 108 75 45 Standard 7kVA + 4 EXB 245 132 98 57 Standard 7kVA + 5 EXB 287 164 118 72 Standard 5kVA 37 31 21 12 Standard 5kVA + 1 EXB 90 70 53 30 Standard 5kVA + 2 EXB 140 112 83 55 Standard 5kVA + 3 EXB 185 156 108 75 Standard 5kVA + 4 EXB 255 207 132 98 Standard 5kVA + 5 EXB 306 260 164 118
Appendix 5 — 1 86-86000-00 A01

Table 5-3: Battery Recharge time to recover 90% of the rated backup time after discharge at full load.
Configuration for Configuration for Configuration for 2 hours backup time 4 hours backup time 8 hours backup time
EX 5 7 hours 15 hours 24 hours
EX 7 5 hours 12 hours 20 hours
EX 11 7 hours 15 hours 24 hours
5.4 System Short Circuit Protection Short circuit current provided by EX 5/7/11RT in normal or battery mode: EX5/7 RT 110A for 80ms EX11 RT 190A for 80ms
EX RT Transformer Nominal power 11 kVA Nominal current 63 A Input voltage 208-240Vac Output Voltage 120/208/240Vac Frequency 50/60 Hz (+/-10%) Isolation (EN 61558-1-2-4) 3.75 kV / 5 M ohms Operating temperature From 0° to +40°C Max. operating rel. humidity 95% Derating / altitude Pn-10% > 1000 m Dimensions HxWxD (tower) 17.5 x 5.15 x 25 inches (444 x 131 x 635 mm) Dimensions HxWxD (rack 3U) 5.15 x 17.5 x 25 inches (131 x 444 x 635 mm) Weight 151 lbs. (68.5 kg)
EX RT CLA module AC input voltage 156-280 Volts AC Input frequency 40-70 Hz Battery charge current 6 A DC
Table 5-4: Full load heat rejection in BTU’s/hr.
5.7 Environmental Characteristics
◗ The operating temperature is 0 to 40°C (8 hours at 45°C), however optimum operation is within the +20 to +25°C range and at 5-95% humidity, non-condensing at altitude up to 3280ft without de-rating.
◗ The storage temperature : -20 to 40°C. Humidity : 5-95%, non condensing.
◗ Battery backup time is adversely affected by high and low temperatures. It is significantly reduced at tempera- tures under 10°C. Above 25°C, battery service life is cut in half every 10°C. Above 40°C, battery manufacturers no longer guarantee operation due to the risk of thermal runaway.
◗ Air enters through the front air vent grills and exits through the back. Always keep air vent grills unobstructed.
Appendix 5 — 2 86-86000-00 A01
5kVA 1327 1944 · 7kVA 1858 2722 · 11kVA 2919 4278

The liability of MGE UPS SYSTEMS, INC. hereunder is limited to replacing or repairing at MGE UPS SYSTEMS, INC.’s factory or on the job site at MGE UPS SYSTEMS, INC.’s option, any part or parts which are defective, including labor, for a period of 24 months from the date of purchase. The MGE UPS SYSTEMS, INC. shall have the sole right to determine if the parts are to be repaired at the job site or whether they are to be returned to the factory for repair or replacement. All items returned to MGE UPS SYSTEMS, INC. for repair or replacement must be sent freight prepaid to its factory. Purchaser must obtain MGE UPS SYSTEMS, INC.’s Return Materials Authorization prior to returning items. The above conditions must be met if warranty is to be valid. MGE UPS SYSTEMS, INC. will not be liable for any damage done by unauthorized repair work, unauthorized replacement parts, from any misapplication of the item, or for damage due to accident, abuse, or Act of God.
In no event shall the MGE UPS SYSTEMS, INC. be liable for loss, damage, or expense directly or indirectly arising from the use of the units, or from any other cause, except as expressly stated in this warranty. MGE UPS SYSTEMS, INC. makes no warranties, express or implied, including any warranty as to merchantability or fitness for a particular purpose or use. MGE UPS SYSTEMS, INC. is not liable for and Purchaser waives any right of action it has or may have against MGE UPS SYSTEMS, INC. for any consequential or special damages arising out of any breach of warranty, and for any damages Purchaser may claim for damage to any property or injury or death to any person arising out of its purchase of the use, operation or maintenance of the product. MGE UPS SYSTEMS, INC. will not be liable for any labor subcontracted or performed by Purchaser for preparation of warranted item for return to MGE UPS SYSTEMS, INC.’s factory or for preparation work for field repair or replacement. Invoicing of MGE UPS SYSTEMS, INC. for labor either performed or subcontracted by Purchaser will not be considered as a liability by the MGE UPS SYSTEMS, INC.
This warranty shall be exclusive of any and all other warranties express or implied and may be modified only by a writing signed by an officer of the MGE UPS SYSTEMS, INC. This warranty shall extend to the Purchaser but to no one else. Accessories supplied by MGE UPS SYSTEMS, INC., but manufactured by others, carry any warranty the manufacturers have made to MGE UPS SYSTEMS, INC. and which can be passed on to Purchaser.
MGE UPS SYSTEMS, INC. makes no warranty with respect to whether the products sold hereunder infringe any patent, U.S. or foreign, and Purchaser represents that any specially ordered products do not infringe any patent. Purchaser agrees to indemnify and hold MGE UPS SYSTEMS, INC. harmless from any liability by virtue of any patent claims where Purchaser has ordered a product conforming to Purchaser’s specifications, or conforming to Purchaser’s specific design.
Purchaser has not relied and shall not rely on any oral representation regarding the Product sold hereunder and any oral representation shall not bind MGE UPS SYSTEMS, INC. and shall not be part of any warranty.
There are no warranties which extend beyond the description on the face hereof. In no event shall MGE UPS SYSTEMS, INC. be responsible for consequential damages or for any damages except as expressly stated herein.
The information in this manual is the property of MGE UPS SYSTEMS, INC., and represents a proprietary article in which MGE UPS SYSTEMS, INC., retains any and all patent rights, including exclusive rights of use and/or manufac- ture and/or sale. Possession of this information does not convey any permission to reproduce, print, or manufacture the article or articles shown herein. Such permission may be granted only by specific written authorization, signed by an officer of MGE UPS SYSTEMS, INC.
IBM, PC-AT, ES/9000, and AS/400 are trademarks of International Business Machines Corporation. MGE and MGE UPS SYSTEMS are trademarks of MGE UPS SYSTEMS, INC. Other trademarks that may be used herein are owned by their respective companies and are referred to in an editorial fashion only.

Thank you for choosing MGE UPS SYSTEMS, INC. for your power protection, distribution, and quality requirements. We are pleased to have you join our increasing family of users.
In order to maximize the value you receive from this product, and to ensure that you are kept informed of product or software updates, we recommend that you take a few minutes to register your new purchase. You may register online at the URL noted below. Should you not have Internet access, you may mail or fax this form back (attn: Warranty Registration) as indicated at the bottom of the page.
Please be prepared with the following information to register and validate your UPS warranty, keep informed on software and product updates, and register your extension "Warranty+" if purchased with the UPS.
Product information
Date of purchase
I have purchased a warranty extension (Warranty+)
Thank you from all of us at MGE.
MGE UPS SYSTEMS, INC., 1660 Scenic Avenue, Costa Mesa, CA 92626, USA
41-000154-53 Rev B00 9/2003

Technical questions? If you encounter a problem while following the instructions in this manual, or have
questions about the operation, repair, or servicing of your equipment, please direct calls to MGE UPS
SYSTEMS, INC. Customer Care Center or visit our web site www.mgeups.com for complete service information.
To insure that your questions are correctly answered, please obtain the part number, assembly number, and serial
number of the unit and include them in any discussions or correspondence.
Customer Care Center: 1-800523-0142, extension 1113 (USA and Canada Only)
Commitment: MGE UPS SYSTEMS, INC. is committed to providing easy to access factory trained experts that will provide responses to any questions that you might have.
Scheduling of the MGE Field Service Engineers typically should be done 7 to 10 days before they are required on-site. If the startup of the UPS is critical to maintaining your schedule, please call the MGE toll free telephone number at 1-800-438-7373, to insure a safe installation and startup that will maintain the MGE warranty and insure smooth performance
Should you require factory service for your equipment, contact MGE’s Customer Support Services and obtain a Return Materials Authorization (RMA) prior to shipping your unit. Never ship equipment to MGE without first obtaining an RMA.

(This page left blank intentionally)

@ At.
/ And/or.
+/- Plus or Minus.
≤ Equal to or less than.
# Number.
°C Degree Celsius.
°F Degree Fahrenheit.
Ø Phase angle.
Ω Ohm; unit of resistance.
® Trade Mark.
2nd Second.
AC or ac Alternating current, also implies root-mean-square (rms).
Ambient Temp. Temperature of surrounding air.
Ambient noise Acoustical noise of surrounding environment.
ANSI American National Standard Institute.
AWG American Wire Gauge.
Breaker Electrical circuit interrupter.
BTU or Btu British thermal unit. Defined as the amount of heat required to raise the tempera- ture of one pound of water by 1°F.
BYPASS See “Static Transfer switch”.
BYPASS mode See “off-line mode”.
Carrier The company or individual responsible for delivering goods from one location to another.
C Common.
CB Circuit breaker.
cm Centimeter.
dB Decibels.
DC Direct current.
Conduit A flexible or rigid tube enclosing electrical conductors.
C.S.S. Customer Support Service.
Glossary G — 1 86-86000-00 A01

Current rating The maximum current that a conductor or equipment can carry reliably without damage.
dBA Decibel Adjusted.
dBrnC Decibel above reference noise.
DC or dc Direct current, or voltage.
Digital Meter The LCD display on the front panel of inverter system.
Earth ground A ground circuit that has contact with the earth.
ECO Mode Operating mode by which the load is supplied directly by the AC source if it is within the tolerances defined by the user. This mode reduces the consumption of electrical power.
Electrician Refers to an installation electrician qualified to install heavy-duty electrical components in accordance with local codes and regulations. Not necessarily qualified to maintain or repair electrical or electronic equipment.
FET Field effect transistor.
Freq. Frequency.
Frequency slew rate The change in frequency per unit of time. Given in term of Hz per second (Hz/sec.).
GND Ground (safety).
Hz Hertz, frequency measurement unit, 1Hz is one cycle per second.
Inverter mode See “on-line” mode.
I Current.
IEC International Electrotechnical Commission.
IEEE Institute of Electrical and Electronic Engineers.
Input branch circuit The input circuit from the building power panel to the equipment.
Inverter An electrical circuit that generates an AC voltage source from a DC voltage source.
IGBT Insulated gate bipolar transistors.
I/O Input/Output.
I/T or IT Information Technology.
kVA KiloVolt-Ampere; is equal to 1000 Volt-Ampere.
L Line.
LCD Liquid-Crystal Display unit.
LED Light Emitting Diode.
Mains or Mains 1 Main AC input source.
Mains 2 Bypass AC input source.
mA Milliampere.
MAX. Maximum.
MCM Thousand circular mil; standard wire sizes for multiple stranded conductors over 4/0 AWG in diameter. M is from Roman numerical system indicating 1000.
Module Refers to individual power inverter module.
N Neutral.
Glossary G — 2 86-86000-00 A01

NC Normally closed.
NO Normally open.
NEC National Electrical Code.
NFPA National Fire Protection Association.
PN Part number.
On-line mode Inverter output power is the primary energy source to load.
Off-line mode Inverter output is off, and the load connected at the inverter output receives power from utility line via a static transfer switch or maintenance bypass relay.
OSHA Occupational Safety and Health Agency.
PCA Printed circuit assembly.
PCB Printed circuit board.
PWM Pulse Width Modulation.
SCR Silicon controlled rectifier.
Shipping damage Any damage done to an article while it is in transit.
SPDT Single Pole Double Throw.
Static Transfer An solid state switching mechanism electronically controlled to pass AC power directly from the utility to an output load.
Technician Refers to an electronic technician qualified to maintain and repair electronic equipment. Not necessarily qualified to install electrical wiring.
Test connector DB-9 type connector on the LCD panel allowing MGE UPS SYSTEMS Customer Support Service technician to access programmable and diagnostic features of the system.
VA Volt-amps, unit for apparent power measurement, equal V x I.
VAC or Vac Voltage of AC type.
VDC or Vdc Voltage of DC type.
ve Battery voltage.
Via By way of.
Glossary G — 3 86-86000-00 A01
V Volts · VA Volt amperes

(This page left blank intentionally)

1660 Scenic Avenue Costa Mesa, CA 92626
Use this form to report any errors, omissions, or other problems you have experienced, or to order additional hardcopies of this document. A free copy of this document may be downloaded from the proprietary MGE Rep Web site. Please contact your MGE UPS SYSTEMS,INC. Representative for assistance.
COMPANY ___________________________________________________________________________________
STREET ADDRESS ____________________________________________________________________________
CITY ________________________________________ STATE __________________ ZIP ___________________
I would like to order (quantity @ $75.00 each) additional copies of the:
I would like to report the following problems with this document:






w w w . m g e u p s . c o m
MGE UPS SYSTEMS 1660 Scenic Ave. Costa Mesa, CA 92626
MGE UPS SYSTEMS #9, 2789 Thamesgate Drive Mississauga, ON L4T 4E8
MGE UPS SYSTEMS 1660 Scenic Ave. Costa Mesa, CA 92626