MGE UPS Systems EX 5RT

72 pages·3.9 MB·Power Supply·PDF·ENDEFRITNLJA
MGE UPS Systems EX 5RT
Table of Contents 80 sections EX 5RT / EX 7RT/ EX 11RT System · 86-86000-00 A01 · IMPORTANT SAFETY INSTRUCTIONS · Certification Standards · … ShowHide
EX 5RT / EX 7RT/ EX 11RT Systemp.186-86000-00 A01p.1IMPORTANT SAFETY INSTRUCTIONSp.2Certification Standardsp.2Safety of Personsp.3Product Safetyp.3Special Precautionsp.3How to use this manual and Symbol Usagep.3CAUTION: Record All Serial Numbers!p.4KEEP THIS MANUAL IN A PLACE WHERE YOU CAN REFERENCE THE SERIALp.4NUMBERS IF SERVICE IS REQUIRED!p.4EX 5RT System EX 7RT System EX 11RT Systemp.4Power Module SERIAL NUMBER: ___________________________________________________p.4Battery Module SERIAL NUMBER: ____________________________________________________p.4Transformer SERIAL NUMBER: ______________________________________________________p.4ADDITIONAL MODULES SERIAL NUMBERS:p.4____________________________ ______________________________p.4EX 5/7/11 RT System Installation and User Manualp.5Revision Historyp.5Section 2 Setup and Installationp.8Section 3 Operationp.8Section 4 Maintenancep.9Section 5 Appendixp.9MGE Warranty & Propriety Rightsp.9Warranty and Product Registrationp.9Technical Support and Field Servicep.9Glossary G — 1p.9Reorder Form RO — 1p.9Figuresp.10Figures (continued)p.11Tablesp.11Introductionp.131.0 Scopep.131.3.2 Battery Module EXB 5/7/11 RT With Emergency Power Off (EPO) Functionp.181.5 Optional Accessoriesp.201.5.1 Power Module Rail Kitp.201.5.2 Battery/ Transformer/CLA Module Rail Kitp.201.5.3 Battery Module with Remote Emergency Power Off (REPO) Functionp.21Optional Configurationsp.21EXB 5 RTp.21EX 5/7/11RT EXB 5/7/11RTp.21+ + +p.21+ +p.21EXB 11 RTp.211.5.4 Battery Extension Cable Kitp.21Setup and Installationp.252.0 Scopep.252.1 Unpacking and Parts Checkp.252.2 Contents of EX 5/7/11 RT Systemp.262 — 2 86-86000-00 A01p.26E X 1 1 R Tp.27OFFp.2736 (see 1.5.1) 37p.27IP= MAC=00E0D8FF855Ep.271 2 ONp.27ETHERNET RS232p.27E X B R Tp.272.4 Installation in Rack Mounting Configurationp.29OFF ONp.29FINISHED PANEL (rack orientation) 1p.292.6 Power or Battery Module Rack Mountingp.312.6.1 Rear Support Brackets Installationp.322.6.2 Input/Output Box Bracket System Installationp.322.7 Communication Portsp.332.7.1 Connecting the RS232 Communication Portp.332.7.2 Connecting the Dry (Relay) Contact Communication Portp.34NOp.34NO NC NO NOp.34commonp.342.7.3 Installation of Optional Network Management Cardp.342.7.4 Remote Emergency Power Off (REPO) Communication Portp.36RJ11p.362.8 Connecting the Input and Output Power Cables to the Input/Output Boxp.372.8.1 Flexible Cordage and Conduit Installationsp.37I/O BOXp.37OFF Op.37OFF 0 OFF 0p.372.8.2 System Connections with Common Normal and Bypass AC Sourcesp.392.8.4 System Connections with Separate Normal and Bypass AC Sourcesp.41UPSp.41
Page 1 of the MGE UPS Systems EX 5RT user manual — 86-86000-00 A01
Page 1 · click to enlarge
Page 1
MGE UPS Systems EX 5RT — EX 5RT / EX 7RT/ EX 11RT System diagram (page 1)
Fig. 1 · EX 5RT / EX 7RT/ EX 11RT System

w w w . m g e u p s . c o m

MGE UPS Systems EX 5RT — EX 5RT / EX 7RT/ EX 11RT System diagram (page 1)
Fig. 2 · EX 5RT / EX 7RT/ EX 11RT System

EX 5RT / EX 7RT/ EX 11RT System

86-86000-00 A01

Page 2 of the MGE UPS Systems EX 5RT user manual — Certification Standards
Page 2 · click to enlarge
Page 2

IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS – This manual contains important instructions for MGE UPS SYSTEMS, INC. products that must be followed during operation and maintenance of the equipment.

This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at user's own expense.

Certification Standards

◗ IEEE 587-1980/ANSI C62.41 1980 Standards for Surge Withstand Ability

◗ FCC rules and regulations of Part 15, Subpart J, Class A

◗ UL listed under 1778, Standards for Uninterruptible Power Supply Equipment

◗ IEC 61000-4-2 (ESD) : level4.

◗ IEC 61000-4-3 (Radiated field) : level 3.

IEC 61000-4-4 (EFT) : level4.

◗ IEC 61000-4-5 (Fast transients) : level4.

◗ IEEE-C6241 Category B (ring wave).

◗ IEC 61000-4-6 (electromagnetic field).

◗ IEC 61000-4-8 (conducted magnetic field).

Page 3 of the MGE UPS Systems EX 5RT user manual — How to use this manual and Symbol Usage
Page 3 · click to enlarge
Page 3

Safety of Persons

◗ The UPS has its own internal power source (the battery). Consequently, the power outlets may be energized even if the UPS is disconnected from the AC power source.

◗ The UPS must be properly grounded.

◗ The battery supplied with the UPS contains small amounts of toxic materials. To avoid accidents, the directives listed below must be observed:

- Never burn the battery (risk of explosion).

- Do not attempt to open the battery (the electrolyte is dangerous for the eyes and skin).

- Comply with all applicable regulations for the disposal of the battery.

- Batteries constitute a danger (electrical shock, burns). The short-circuit current may be very high. Precautions must be taken for all handling: remove watches, rings, bracelets and any other metal objects, use tools with insulated handles.

- Do not lay tools or metal parts on top of batteries.

Product Safety

◗ A protection circuit breaker must be installed upstream and be easily accessible..

◗ The UPS can be disconnected from the AC power source by opening the input circuit breaker.

◗ UPS must be connected to a nearby power source that is easily accessible.

◗ Never block the ventilation grates of the UPS.

◗ The UPS must be installed in a controlled environment.

Special Precautions

◗ The UPS connection instructions and operation described in the manual must be followed in the indicated order.

◗ Check that the indications on the rating plate correspond to your AC powered system and to the actual electrical consumption of all the equipment to be connected to the UPS.

◗ Before and after the installation, if the UPS remains de-energized for a long period, the UPS must be energized for a period of 24 hours, at least once every 6 months (for a normal storage temperature less than 25°C). This charges the battery, thus avoiding possible irreversible damage.

How to use this manual and Symbol Usage

This manual is designed for ease of use and easy location of information.

Typographical conventions use “< >” angle brackets in procedures to denote a prompt for User action:

For example: 1. After the selections are complete, click on the button.

This manual uses four icon symbols with text to convey important information and tips.

Safety of Persons iii 86-86000-00 A01

Page 4 of the MGE UPS Systems EX 5RT user manual — EX 5RT System EX 7RT System EX 11RT System
Page 4 · click to enlarge
Page 4

CAUTION: Record All Serial Numbers!

RECORD ALL SERIAL NUMBERS FOR EX 5/7/11 RT AND ACCESSORIES.

THESE SERIAL NUMBERS WILL BE REQUIRED IF YOUR SYSTEM NEEDS SERVICE.

KEEP THIS MANUAL IN A PLACE WHERE YOU CAN REFERENCE THE SERIAL

NUMBERS IF SERVICE IS REQUIRED!

EX 5RT System EX 7RT System EX 11RT System

Power Module SERIAL NUMBER: ___________________________________________________

Battery Module SERIAL NUMBER: ____________________________________________________

Transformer SERIAL NUMBER: ______________________________________________________

ADDITIONAL MODULES SERIAL NUMBERS:

____________________________ ______________________________

____________________________ ______________________________

____________________________ ______________________________

____________________________ ______________________________

____________________________ ______________________________

____________________________ ______________________________

____________________________ ______________________________

____________________________ ______________________________

____________________________ ______________________________

____________________________ ______________________________

iv 86-86000-00 A01

Page 5 of the MGE UPS Systems EX 5RT user manual — Revision History
Page 5 · click to enlarge
Page 5

EX 5/7/11 RT System Installation and User Manual

Revision History

EX 5RT / EX 7RT / EX 11RT System Installation and User Manual 86-86000-00

RevisionA00 Initial Release 07/2004

Copyright © 2004 MGE UPS SYSTEMS, INC. All rights reserved. Printed in U.S.A.

MGE UPS SYSTEMS, INC. 1660 Scenic Avenue Costa Mesa, CA 92626 (714) 557-1636

For Service Call1 (800) 438-7373

v 86-86000-00 A01

Page 6 of the MGE UPS Systems EX 5RT user manual — EX 5/7/11 RT System Installation and User Manual
Page 6 · click to enlarge
Page 6

(This page left blank intentionally)

vi 86-86000-00 A01

Page 7 of the MGE UPS Systems EX 5RT user manual — EX 5/7/11 RT System Installation and User Manual
Page 7 · click to enlarge
Page 7
Page 7 of the MGE UPS Systems EX 5RT user manual — EX 5/7/11 RT System Installation and User Manual
Page 8 of the MGE UPS Systems EX 5RT user manual — Section 3 Operation
Page 8 · click to enlarge
Page 8

Section 2 Setup and Installation

section description page

2.0 Scope 2 — 1 2.1 Unpacking and Parts Check 2 — 1 2.2 Contents of EX 5/7/11 RT System 2 — 2 2.3 Installation in Tower Configuration 2 — 4 2.4 Installation in Rack Mounting Configuration 2 — 5 2.4.1 Adjustment of Front Panel Logo and control panel for Rack Orientation 2 — 5 2.5 Prepare Battery Module for Rack Mounting 2 — 6 2.6 Power or Battery Module Rack Mounting 2 — 7 2.6.1 Rear Support Brackets Installation 2 — 8 2.6.2 Input/Output Box Bracket System Installation 2 — 8 2.7 Communication Ports 2 — 9 2.7.1 Connecting the RS232 Communication Port 2 — 9 2.7.2 Connecting the Dry (Relay) Contact Communication Port 2 — 10 2.7.3 Installation of Optional Network Management Card 2 — 10 2.7.4 Remote Emergency Power Off (REPO) Communication Port .2 — 12 2.8 Connecting the Input and Output Power Cables to the Input/Output Box 2 — 13 2.8.1 Flexible Cordage and Conduit Installations 2 — 13 2.8.2 System Connections with Common Normal and Bypass AC Sources 2 — 15 2.8.3 Connecting EX RT Transformer 2 — 16 2.8.4 System Connections with Separate Normal and Bypass AC Sources 2 — 17 2.8.5 System Connections as Frequency Converter (without Bypass AC Source) 2 — 18 2.9 Connection of Battery Module, EXB 2 — 19 2.10 Connection of CLA Module 2 — 20

Section 3 Operation

section description page

3.0 Scope 3 — 1 3.1 Initial Startup 3 — 1 3.2 UPS Personalization 3 — 2 3.2.1 Accessing personalization with front panel buttons 3 — 2 3.2.2 Accessing personalization through external software 3 — 4 3.2.3 Final startup sequence 3 — 4 3.3 Operating Modes 3 — 5 3.3.1 Normal (double conversion) Mode 3 — 5 3.3.2 ECO Modes 3 — 6 3.4 Operation on battery power 3 — 7 3.4.1 Transfer to Battery Power 3 — 7 3.5 Return of Normal AC source 3 — 8 3.6 Shutdown 3 — 8

Contents c ii 86-86000-00 A01

Page 9 of the MGE UPS Systems EX 5RT user manual — Glossary G — 1
Page 9 · click to enlarge
Page 9

Section 4 Maintenance

section description page

4.0 Scope 4 — 1 4.1 Information Technology (IT) Network and Industrial Operating Modes 4 — 1 4.2 Troubleshooting 4 — 2 4.3 Hot Swapping the Power Module 4 — 4 4.4 Re-connecting the power module 4 — 5 4.5 Hot Swapping the Battery Module 4 — 6 4.5.1 Disconnecting the Battery Module 4 — 6 4.5.2 Re-connecting the Battery Module 4 — 6

Section 5 Appendix

section description page

5.0 Electrical Specifications 5 — 1 5.1 System Input/Output Power Ratings 5 — 1 5.2 System Overload Characteristics 5 — 1 5.3 System Backup Characteristics 5 — 1 5.4 System Short Circuit Protection 5 — 2 5.5 Accessories Electrical Characteristics 5 — 2 5.6 Heat Rejection 5 — 2 5.7 Environmental Characteristics 5 — 2

MGE Warranty & Propriety Rights

MGE Warranty Proprietary Rights Statement

Warranty and Product Registration

User Information Product information Warranty Extension (Warranty+) not available on products

Technical Support and Field Service

MGE Service and Repair Who to Contact Scheduling Field Service Engineer Support Return for Repair (RMA)

Glossary G — 1

Reorder Form RO — 1

Contents c iii 86-86000-00 A01

Page 10 of the MGE UPS Systems EX 5RT user manual — Figures
Page 10 · click to enlarge
Page 10

Figures

figure description page

1-1: Tower Configurations with Power Module, Battery Module, and optional Transformer Module 1 — 4 1-2: Rack Configurations with Power Module, Battery Module, and Transformer Module 1 — 5 1-3: Rear panel of the Power Module 1 — 6 1-4: Rear Panel of the Battery Module 1 — 6 1-5: Rear Panel of the optional Transformer Module. (PN 86003) 1 — 7 1-6: View of typical control panel interface 1 — 7 1-7: Power Module Rack Mounting Kit 1 — 8 1-8: Telescopic rails for the Battery/Transformer/CLA module Rack mounting 1 — 8 1-9: Typical back-up time with multiple EXB’s at full load 1 — 9 1-10: Typical Battery Integration kit with casters setup 1 — 10 1-11: Typical Transformer Module contents and connections 1 — 11 1-12: Connection for CLA Module and EX 5/7/11 RT 1 — 12

2-1: Contents of Standard HV EX 5RT (PN 86050) / EX 7RT (PN 86070) / EX 11RT (PN 86110) System 2 — 3 2-2: Tower Configuration of Standard System and Optional Transformer Module 2 — 4 2-3: Typical orientation of the logo and control panel. (Power Module shown) 2 — 5 2-4: Accessing Battery Pack 2 — 6 2-6: Rack mounting of the power module onto the rails 2 — 7 2-7a: Rear Support Brackets 2 — 8 2-7b: Input/Output Box Bracket System 2 — 8 2-8: RS232 Communication Cable Connection 2 — 9 2-9: Relay Pin Connections for Communication Port 2 — 10 2-10: Communication Card Slot with SNMP/Web Network Management Card installed 2 — 10 2-10a: Activation of remote power off function using a contact normally open switch 2 — 12 2-10b: Activation of remote power off function using a contact normally closed switch 2 — 12 2-12a: Step 1 & 2; Typical plastic and metal coupling installations 2 — 13 2-12b: Step 3; Typical Straight Metal Conduit installation 2 — 14 2-12c: I/O Box Terminal Block Diagram 2 — 14 2-13: Normal AC Input and Output Cables installation 2 — 15 2-14: View of EX RT transformer connected downstream for 120/208/240 Vac outputs (shown with one EXB) 2 — 16 2-15: Normal AC Input, Bypass AC, and Output Cables Installation 2 — 17 2-16: Accessing Terminal Blocks for Input and Output power cables 2 — 18 2-17: Rear view of battery module cable connections 2 — 19 2-18: Rear view of CLA module cable battery and AC input connections. . .2 — 20

Contents c iv 86-86000-00 A01

Page 11 of the MGE UPS Systems EX 5RT user manual — Tables
Page 11 · click to enlarge
Page 11

Figures (continued)

figure description page

3-1: Initial Startup Display 3 — 1 3-2: Control Panel with scroll up and down buttons 3 — 2 3-3: Configuration used to provide full redundancy (2N) to critical loads 3 — 3 3-4: Normal (double conversion) mode 3 — 5 3-5: ECO mode display 3 — 6 3-6: Transfer, Threshold and End of backup time 3 — 7 3-7: Shutdown display, circuit breaker, and AC source switch 3 — 8

4-1: Disconnecting the power module 4 — 4 4-2: Reconnect the power module 4 — 5 4-3: Rear view of the battery module 4 — 6

5-1: Power supplied as a function of input voltage (left), and Permissible UPS overloads as a function of time (right) 5— 1

Tables

table description page

1: EX RT Model Descriptions and Contents 1 — 2 2: Optional Accessories (See section 1.5 for description) 1 — 3 3: Power Module Ratings 1 — 4 4: Battery Module Ratings 1 — 4 5: Battery backup time chart 1 — 12

3-1: Local Settings 3 — 3 3-2: Output features 3 — 3 3-3: ON/OFF features 3 — 4 3-4: Battery features 3 — 4

4-1: Network and Industrial Modes of Operation 4 — 1 4-2: Troubleshooting not requiring MGE after-sales support 4 — 2 4-3: Troubleshooting requiring MGE after-sales support 4 — 3

5-1: EX 5/7/11 RT Input and Output Characteristics 5 — 1 5-2: Back-up Time ( in minutes) 5 — 1 5-3: Battery Recharge time to recover 90% of the rated backup time after discharge at full load 5 — 2 5-4: Full load heat rejection in BTU’s/hr 5 — 2

Contents c v 86-86000-00 A01

Page 12 of the MGE UPS Systems EX 5RT user manual — Figures (continued)
Page 12 · click to enlarge
Page 12

(This page left blank intentionally)

c vi 86-86000-00 A01

Page 13 of the MGE UPS Systems EX 5RT user manual — 1.0 Scope
Page 13 · click to enlarge
Page 13

Introduction

1.0 Scope

Thank you for selecting an MGE UPS SYSTEMS, INC. (MGE) product to protect your electrical equipment.

The product you selected is a part of the EX RT series.The EX RT series is a family of Uninterruptible Power Supply (UPS) designed to provide safe, and reliable AC power backup for sensitive electrical equipment. To discover the entire range of MGE products, we invite you to visit our website at www.mgeups.com or contact your representative at (800) 523-0142.

This manual describes the installation and operation of standard HV EX 5/7/11RT systems within the EX RT product family. For a complete description of the EX RT product family and its available options, please refer to the tables below:

Introduction is a general description of system configurations of the EX 5/7/11 RT, and its mechanical ,electrical characteristics. Additionally there is an optional accessories section with important information on MGE products that will enhance the performance of the EX 5/7/11RT. Please contact your MGE representative for detailed information on these options.

2 Setup and Installation

Setup and Installation guides the user through tools and equipment required for connecting the EX 5/7/11 RT and battery installation or replacement. Included are assembly instructions, power cable connections with wire diagrams for configuring the product to hardware specifications.

Operation describes the EX 5/7/11RT system characteristics of indicators and controls, modes and specifications. The user procedures include performing software programming that will maintain optimal performance.

Maintenance includes a troubleshooting guide of symptoms and possible solutions, hot swapping the power module, battery module, and testing scenarios.

Electrical and Mechanical specifications for the EX 5/7/11 RT.

A Glossary provides definitions of abbreviations and terms used in this manual.

1 — 1 86-86000-00 A01 Introduction

Show 4 more labels / short text on this page
1 Introduction · 3 Operation · 4 Maintenance · 5 Appendix
Page 14 of the MGE UPS Systems EX 5RT user manual — Introduction
Page 14 · click to enlarge
Page 14
Table 1EX RT Model Descriptions and Contents

Model Part Power Module Battery Module Transformer Power Module Battery Module SNMP/Web

Number 86055 86075 86115 86079 86119 Module Rail Kit 86001 Rail Kit 86002 Network

(120/208/240Vac) Mgt. Card

86003 66074 5kVA 86050 X X HV EX 5RT

5kVA 86052 X HV EX 5RT Network Pack

5kVA 86050-01 X X X LV EX 5RT

5kVA 86052-01 X (x2) X LV EX 5RT Network Pack

7kVA 86070 X X HV EX 7RT

7kVA 86072 X HV EX 7RT Network Pack

7kVA 86070-01 X X X LV EX 7RT

7kVA 86072-01 X (x2) X LV EX 7RT Network Pack

11kVA 86110 X X HV EX 11RT

11kVA 86112 X HV EX 11RT Network Pack

11kVA 86110-01 X X X LV EX 11RT

11kVA 86112-01 X (x2) X LV EX 11RT Network Pack

Introduction 1 — 2 86-86000-00 A01

System Description Contents

Page 15 of the MGE UPS Systems EX 5RT user manual — Introduction
Page 15 · click to enlarge
Page 15
Table 2Optional Accessories (See section 1.5 for description)

86001 Rail Kit for Power Module EX 5/7/11 RT

86002 Rail Kit for Battery/Transformer/CLA Module

86005 Battery Integration Kit with Casters

86006 Battery Extension Cable Kit

86008 Battery Chassis Empty EXB RT W/EPO

86009 I/O Box 5/7kVA UL/US

86010 I/O Box 11kVA UL/US

86012 I/O Box Bracket System

86013 Rear Bracket Supports

Introduction 1 — 3 86-86000-00 A01

Part Number Description

Page 16 of the MGE UPS Systems EX 5RT user manual — Introduction
Page 16 · click to enlarge
Page 16
MGE UPS Systems EX 5RT — Introduction diagram (page 16)
Fig. 3 · Introduction

Apparent Power, kVA 5 7 10@ 200/208/250 VAC Output 11@ 220/230/240 VAC Output

Active Power, kW 4 4.9 8@ 200/208/250 VAC Output 7.3@ 220/230/240 VAC Output

The EX 5/7/11 RT systems can be set up in tower and rack configurations.

Figure 1-1: Tower Configurations with Power Module, Battery Module, and optional Transformer Module.

E X B R T E X 1 1 R T

Introduction 1 — 4 86-86000-00 A01

Page 17 of the MGE UPS Systems EX 5RT user manual — Introduction
Page 17 · click to enlarge
Page 17
MGE UPS Systems EX 5RT — Introduction diagram (page 17)
Fig. 4 · Introduction

Figure 1-2: Rack Configurations with Power Module, Battery Module, and Transformer Module.

EX 5RT/7RT (3U) 5.16” x 17.49” x 25” 49.6 lbs (22.5 kg) (131 x 444 x 635mm)

EX 11RT (3U) 5.16” x 17.49” x 25” 60.6 lbs (27.6 kg) (131 x 444 x 635mm)

EXB 5 RT/ 7 RT (3U) 5.16” x 17.49” x 25” 142 lbs (64.5 kg) (131 x 444 x 635mm)

EXB 11RT (3U) 5.16” x 17.49” x 25” 151 lbs (68.5 kg) (131 x 444 x 635mm)

EX RT (3U) 5.16” x 17.49” x 25” 173 lbs (78.5 kg) Transformer (131 x 444 x 635mm)

Page 18 of the MGE UPS Systems EX 5RT user manual — 1.3.2 Battery Module EXB 5/7/11 RT With Emergency Power Off (EPO) Function
Page 18 · click to enlarge
Page 18
MGE UPS Systems EX 5RT — 1.3.2 Battery Module EXB 5/7/11 RT With Emergency Power Off (EPO) Function diagram (page 18)
Fig. 5 · 1.3.2 Battery Module EXB 5/7/11 RT With Emergency Po…

EX 5RT Power Module part number 86055 EX 7RT Power Module part number 86075 EX 11RT Power Module part number 86115

Knockout for entry of Bypass AC source conduit. 11

1.3.2 Battery Module EXB 5/7/11 RT With Emergency Power Off (EPO) Function

Connectors for automatic detection of additional battery module(s) (to the UPS or to other battery modules).

Battery power connectors (to the UPS or to other battery modules).

Battery Circuit Breaker with Remote Emergency Power Off (REPO) shunt trip.

Page 19 of the MGE UPS Systems EX 5RT user manual — 1.3.2 Battery Module EXB 5/7/11 RT With Emergency Power Off (EPO) Function
Page 19 · click to enlarge
Page 19
MGE UPS Systems EX 5RT — 1.3.2 Battery Module EXB 5/7/11 RT With Emergency Power Off (EPO) Function diagram (page 19)
Fig. 6 · 1.3.2 Battery Module EXB 5/7/11 RT With Emergency Po…
Figure 1-5Rear Panel of the optional Transformer Module. (PN 86003)

UPS ON button (or function button in personalization mode). 23

Page 20 of the MGE UPS Systems EX 5RT user manual — 1.5.2 Battery/ Transformer/CLA Module Rail Kit
Page 20 · click to enlarge
Page 20

1.5 Optional Accessories

Optional Accessories describes the options available for upgrades and enhancement of the EX 5/7/11RT system. Detailed installation of the unit is described in following sections.

To ensure a successful installation, all procedures should be followed in their correct sequence. Note that any unauthorized installation may cause damage to the UPS(s) and void the MGE warranty.

1.5.1 Power Module Rail Kit

This kit is for rack mounting the power module in a 19" enclosure. See section 2.6 for rack installation of power module.

Figure 1-7: Power Module Rack Mounting Kit.

Front mounting brackets.

Rear support brackets, part number 86013.

Telescopic rails, 695 mm to 1015 mm

length (27.36" to 39.96").

Input/Output Box bracket system, part

number 86012.

1.5.2 Battery/ Transformer/CLA Module Rail Kit

This kit is for rack mounting of the battery/step-down transformer/CLA module in 19" enclosure. See section 2.6 for rack installation of power module.

Figure 1-8: Telescopic rails for the Battery/Transformer/CLA module Rack mounting.

Front mounting brackets.

Rear support brackets, part number

length (27.36" to 39.96"). 26

Telescopic rails, 695 mm to 1015 mm

Introduction 1 — 8 86-86000-00 A01

(Part Number 86001) · (Part number 86002)

Page 21 of the MGE UPS Systems EX 5RT user manual — 1.5.4 Battery Extension Cable Kit
Page 21 · click to enlarge
Page 21

1.5.3 Battery Module with Remote Emergency Power Off (REPO) Function

(EXB 5/7 RT; PN 86079, EXB 11RT; PN 86119)

Standard HV EX 5/7/11RT system (one Power Module, EX 5/7/11 RT, and one Battery Module, EXB 5/7/11RT) offers a standard backup time of 5 to 12 minutes at full load.

To increase backup time, it is possible to connect up to 5 additional EXB 5/7/11 RT modules to the EX 5/7/11 RT module. See section 2.10 for connections between Power Module (EX 5/7/11 RT) and Battery Module (EXB 5/7/11 RT)

Figure 1-9: Typical back-up time with multiple EXB’s at full load.

Standard HV EX 5/7/11RT system

Optional Configurations

EXB 5 RT

EXB 5 RT

EXB 5 RT

EXB 5 RT

EXB 5 RT

EX 5/7/11RT EXB 5/7/11RT

EXB 7 RT EXB 7 RT EXB 7 RT EXB 7 RT EXB 7 RT

+ + +

+ +

EXB 11 RT

EXB 11 RT

EXB 11 RT

EXB 11 RT

EXB 11 RT

5 kVA12 min 30 min 55 min 75 min 98 min 118 min
7 kVA11 kVA: 7 min 5 min 20 min 14 min 32 min 22 min

45 min 30 min 57 min 42 min 70 min 53 min

See Appendix for additional Back-up time information.

1.5.4 Battery Extension Cable Kit

( 6 ft / 1.8 m, Part number 86006)

This extended battery cable kit will be used instead of the standard battery cable when battery modules (EXBs) are distant from each other (located in two different enclosures, for instance).

The battery extension cable kit includes a 6 ft long, straight connector battery power cable and a 6 ft. long battery detection cable.

Introduction 1 — 9 86-86000-00 A01

Show 5 more labels / short text on this page
/ · / · / · / · /
Page 22 of the MGE UPS Systems EX 5RT user manual — 1.5.3 Battery Module with Remote Emergency Power Off (REPO) Function
Page 22 · click to enlarge
Page 22
MGE UPS Systems EX 5RT — 1.5.3 Battery Module with Remote Emergency Power Off (REPO) Function diagram (page 22)
Fig. 7 · 1.5.3 Battery Module with Remote Emergency Power Off…

Battery Integration Kit is a cart, designed to hold up to 8 modules. It has swivel wheels with brakes, leveling feet, seismic floor mount panels, plates to lock modules and hardware included. Modules not included.

Figure 1-10: Typical Battery Integration kit with casters setup.

- I/O Box 5/7kVA Part number 86009 - I/O Box 11kVA Part number 86010

Introduction 1 — 10 86-86000-00 A01

Page 23 of the MGE UPS Systems EX 5RT user manual — 1.5.3 Battery Module with Remote Emergency Power Off (REPO) Function
Page 23 · click to enlarge
Page 23
MGE UPS Systems EX 5RT — 1.5.3 Battery Module with Remote Emergency Power Off (REPO) Function diagram (page 23)
Fig. 8 · 1.5.3 Battery Module with Remote Emergency Power Off…
Page 24 of the MGE UPS Systems EX 5RT user manual — 1.5.3 Battery Module with Remote Emergency Power Off (REPO) Function
Page 24 · click to enlarge
Page 24
MGE UPS Systems EX 5RT — 1.5.3 Battery Module with Remote Emergency Power Off (REPO) Function diagram (page 24)
Fig. 9 · 1.5.3 Battery Module with Remote Emergency Power Off…

Extended back-up time (up to 8 hours at full load) requires a high power battery cabinet connected to the EX 5/7/11RT via the CLA module.

Figure 1-12: Connection for CLA Module and EX 5/7/11 RT.

Total battery voltage : 240 VDC (20 x 12VDC, one string).

The battery capacity must be set within the UPS (5 Ah increment possible, see UPS Personalization section 3.2.

Introduction 1 — 12 86-86000-00 A01

Page 25 of the MGE UPS Systems EX 5RT user manual — 2.1 Unpacking and Parts Check
Page 25 · click to enlarge
Page 25

Setup and Installation

2.0 Scope

Installation guides the user through tools and equipment required for making input/output power and communica- tion cable connections, and battery installation and replacement. It provides assembly instructions, power cable connections with wire diagrams for configuring the product to hardware specifications.

2.1 Unpacking and Parts Check

Once the EX 5/7/11RT system has been inspected and received from the shipping courier, the unit should be moved to a position as close to the final installation location as possible. See Figures 2-1on page 2-3.

All Modules are shipped in separate boxes.

Prior to any installation, the following items should be observed upon receipt of the EX 5/7/11 RT.

1. Inspect shipment for any damage prior to receipt. Damage claims should be filed directly with the courier. Replacements for damaged components should be ordered through MGE Customer Support Services at 1-800-438-7373.
2. Remove wrapping and foam corners to verify that the equipment nameplate (located on the rear of the units) details a system that corresponds with the equipment ordered.

2 — 1 86-86000-00 A01 Installation

Page 26 of the MGE UPS Systems EX 5RT user manual — 2 — 2 86-86000-00 A01
Page 26 · click to enlarge
Page 26

2.2 Contents of EX 5/7/11 RT System

Contents of Power ModuleContents of Battery Module :

EX 5RT /EX 7RT/ EX 11RT. Stabilizer Bracket and hardware.

Two sets of tower stands. EXB 5/7/11 RT.

RS232 communication cable. Tower stand expanders.

Product documentation. Battery Power cable.

Input/Output Box. (With 9 insulated ferrules for Battery/EX RT transformer/CLA

stranded wires.) module rack mounting kit, PN 86002.

(PN 86009 for EX 5/7RT; 86010 for EX 11RT)

Battery detection cable.

Solution-Pac CD. EXB Documentation.

Power Module rack mounting kit, PN 86001 Bezel hex drive.

(optional, but standard with Network Pack version).

SNMP/Web Network Management Card, PN 66074.

(optional, or standard with Network Pack version)

2 — 2 86-86000-00 A01

Installation

Page 27 of the MGE UPS Systems EX 5RT user manual — E X B R T
Page 27 · click to enlarge
Page 27

Figure 2-1: Contents of Standard HV EX 5RT (PN 86050) / EX 7RT (PN 86070) / EX 11RT (PN 86110) System.

- EX 5RT Power Module Part number 86055 - EX 7RT Power Module Part number 86075 - EX 11RT Power Module Part number 86115

E X 1 1 R T

OFF

O

- I/O Box 5/7kVA Part number 86009 - I/O Box 11kVA Part number 86010

36 (see 1.5.1) 37

IP= MAC=00E0D8FF855E

1 2 ON

ETHERNET RS232

Standard only with Network Pack option. - EX 5RT network Pack Part number 86052-01 - EX 7RT network Pack Part number 86072-01 - EX 11RT network Pack Part number 86112-01

39 40 42

E X B R T

41 43 44

- EXB 5RT Battery Module Part number 86079 - EXB 7RT Battery Module Part number 86079 - EXB 11RT Battery Module Part number 86119

Standard only with Network Pack version. See 1.5.2.

Installation 2 — 3 86-86000-00 A01

Show 4 more labels / short text on this page
UPS data Reset · Card Settings · RS232 Download 66074 · (not to scale)
Page 28 of the MGE UPS Systems EX 5RT user manual — E X 1 1 R T
Page 28 · click to enlarge
Page 28
MGE UPS Systems EX 5RT — E X 1 1 R T diagram (page 28)
Fig. 10

Follow the numerical sequence to assemble tower stands and tower stand expanders, shown in Figure 2-2.

Figure 2-2: Tower Configuration of Standard System and Optional Transformer Module.

E X B R T E X 1 1 R T

Use the same procedure for tower mounting multiple battery modules, if applicable.

E X B R T E X 1 1 R T

Page 29 of the MGE UPS Systems EX 5RT user manual — E X 1 1 R T
Page 29 · click to enlarge
Page 29

2.4 Installation in Rack Mounting Configuration

2.4.1 Adjustment of Front Panel Logo and control panel for Rack Orientation.

To prepare the front panel logo and LCD display for rack orientation, of all modules. (including transformer or CLA module, if equipped).

Proceed as follows:

1. Unclip logo plate, and pull the LCD display from front panel.
2. Rotate them 90 degree counter clockwise as shown.
3. Place items back onto the panel.
Figure 2-3Typical orientation of the logo and control panel. (Power Module shown)

E X 1 1 R T

OFF ON

E X 1 1 R T

OFF ON

www.mgeups.com

www.mgeups.com

FINISHED PANEL (rack orientation) 1

E X 1 1 R T

OFF ON

www.mgeups.com

www.mgeups.com

E X 1 1 R T

OFF ON

Installation 2 — 5 86-86000-00 A01

Page 30 of the MGE UPS Systems EX 5RT user manual — 2.4 Installation in Rack Mounting Configuration
Page 30 · click to enlarge
Page 30
MGE UPS Systems EX 5RT — 2.4 Installation in Rack Mounting Configuration diagram (page 30)
Fig. 11 · 2.4 Installation in Rack Mounting Configuration

The battery module is very heavy. To ease its rack mounting, we strongly recommend to remove the battery pack from the battery module, as explained below. See Section 1.2.2 for battery module weight.

1. Unscrew the six screws securing front panel using Bezel Hex Driver .
4. Unscrew the brackets securing the battery pack. Remove battery bracket pack covers.
5. Pull the left and right battery packs out and set aside for reinstalling after the battery module cabinet has been rack mounted.

Installation 2 — 6 86-86000-00 A01

Page 31 of the MGE UPS Systems EX 5RT user manual — 2.6 Power or Battery Module Rack Mounting
Page 31 · click to enlarge
Page 31

2.6 Power or Battery Module Rack Mounting

(optional rack mounting kits required, part number: 86001 and 86002)

The rails and necessary mounting hardware are supplied by MGE UPS SYSTEMS, INC.

Proceed as follows:

1. Attach both front mounting ear brackets to power module or battery module with supplied screws. (For this step, it is possible to adjust the position of both front mounting ears.)
2. Attach rails together and secure with wing nuts, and finger tighten.
3. Attach both rails to rear and front of rack chassis with supplied screws (as shown).
4. Use caution when sliding unit into rack mount, secure unit to rack with supplied screws. (For this step, it is possible to adjust the position of both front mounting brackets.)

Figure 2-6: Rack mounting of the power module onto the rails.

Installation 2 — 7 86-86000-00 A01

Page 32 of the MGE UPS Systems EX 5RT user manual — OFF
Page 32 · click to enlarge
Page 32

2.6.1 Rear Support Brackets Installation

(Part number 86013, included with rack mounting kits, part numbers: 86001 and 86002)

These brackets prevent the power module from moving when the entire rack enclosure is moved.

Proceed as follows:

1. Attach the brackets to the I/O Box and power module.
2. Secure brackets to rails.

Figure 2-7a: Rear Support Brackets.

2.6.2 Input/Output Box Bracket System Installation

(Part number 86012 included with power module rack mounting kit, part numbers: 86001)

This bracket system keeps the I/O Box stationary while hot swapping the power module. It will then be easier to slide the replacement module into the connectors of the I/O Box.

1. Secure small bracket to larger bracket from the underside .

2 & 3. Secure large bracket (with supplied screws) to rails at the rear of module.

4. Secure small attached bracket (with supplied screws) to the I/O Box.

Figure 2-7b: Input/Output Box Bracket System.

OFF

Installation 2 — 8 86-86000-00 A01

Page 33 of the MGE UPS Systems EX 5RT user manual — 2.7.1 Connecting the RS232 Communication Port
Page 33 · click to enlarge
Page 33

2.7 Communication Ports

EX 5/7/11RT provides 3 communication methods that can be used simultaneously:

◗ The COM port provides RS232 communications using MGE Serial HID UPS Transfer (SHUT)protocol. This COM Port is compatible with Personal Solution Pac (PSP) to shutdown one computer. Personal Solution Pac is included in the Solution Pac CD-Rom. For Network Management or multiple computer shutdowns an optional network card must be purchased.

◗ The Dry Contact Port is used for basic signaling or for protection of IT systems like IBM iSeries (formerly AS400) and more.

◗ The slot is compatible with any MGE UPS SYSTEMS, INC. communication card (check www.mgeups.com web site for the complete list of compatible cards)

2.7.1 Connecting the RS232 Communication Port

1. Connect the RS 232 communications cable to the serial port on the computer.
2. Connect the other end of the communications cable to the RS 232 communications port on the EX 5/7/11 RT.

The EX 5/7/11 RT System can now communicate with Personal Solution Pac for power management. UPS config- uration settings are done by Personal Solution Pac for Windows.

Figure 2-8: RS232 Communication Cable Connection.

MGE UPS Systems EX 5RT — 2.7.1 Connecting the RS232 Communication Port diagram (page 33)
Fig. 12 · 2.7.1 Connecting the RS232 Communication Port

Installation 2 — 9 86-86000-00 A01

Page 34 of the MGE UPS Systems EX 5RT user manual — 2.7.3 Installation of Optional Network Management Card
Page 34 · click to enlarge
Page 34

2.7.2 Connecting the Dry (Relay) Contact Communication Port

The system status is indicated by the connection of common pin (Pin 5) to the appropriate pins. Refer to the pin explanations below for details.

Figure 2-9: Relay Pin Connections for Communication Port.

Pin 1, 2: not used.

Pin 3: Remote Power Off signal (5 to 27 VDC, 10 mA max).

Pin 4Operation on mains (not on battery). (48VDC, 2A max.)

1 2 3 4 5

Pin 5: User common.

6 7 8 9

Pin 6: Operation on automatic bypass.

Pin 7: Low battery.

Pin 8Load protected

NO

NO NC NO NO

Pin 9: Operation on battery.

Legend:

common

NO: contact normally open.

NC: contact normally closed.

2.7.3 Installation of Optional Network Management Card

It is not necessary to shut down the UPS to install the optional communications card, except for USB card. Following is a typical installation of the Network Management Card, (PN 66074, standard with the network pack option.)

Proceed as follows:

1. Remove the slot cover secured by two screws.
2. Insert the card into the slot.
3. Secure the card with both screws.

Figure 2-10: Communication Card Slot with SNMP/Web Network Management Card installed.

Installation 2 — 10 86-86000-00 A01

Page 35 of the MGE UPS Systems EX 5RT user manual — 2.7.2 Connecting the Dry (Relay) Contact Communication Port
Page 35 · click to enlarge
Page 35

A wide range of optional cards will allow your UPS to talk to nearly all equipment management systems, making integration faster and easier. All these cards can plug directly into the UPS, saving time and money on your next UPS project. (Meta UPS Card and U-Talk /Basic Acquisition Cards are used exclusively with Multi-slot.)

Dual U-Talk/Basic Card (66060) Provides two communications ports that may be configured

for serial link or AS/400 type dry contacts.

ModBus Card (66061) Interface your UPS with a Building Management System.

Dual COM Ports Card (66066) This card has two independent RS232 communication ports on which it can be connected.One for connecting monitoring software (included) and one for remote control panel UPS control.

USB Card (66067) Take advantage of the latest and fastest communication protocol for Microsoft Windows 2000/XP or Mac OSX.

Dual Volt Free Contacts (66068) The two ports are used to supply UPS status information

Card for AS/400 or one port can be used as a Remote Power Off (REPO) port.

Alarm Relay Card (66069) Six output relays show UPS status and two status inputs are used with the Galaxy 3000 UPS.

XML-Web Card (66073) XML-Web Card acts as a web page for your UPS information. Used along with XML-ClientTM software, up to 50 servers or workstations will be protected and can monitor the UPS with a simple web browser. Security is handled with the SSL protocol, used by many websites to safeguard sensitive password information.

SNMP-Web Card (66074) The SNMP/Web 10/100BT communications card is both an SNMP agent and an HTTP/Web server. Therefore, it enables UPS supervision from any Network Monitoring System using SNMP traps or simply from any web browser (Internet Explorer, Netscape Navigator, etc.) Orderly system shutdown of up to 32 protected servers can be established using MGE’s Solution-Pac/WAN software suite.

Installation 2 — 11 86-86000-00 A01

Page 36 of the MGE UPS Systems EX 5RT user manual — RJ11
Page 36 · click to enlarge
Page 36

2.7.4 Remote Emergency Power Off (REPO) Communication Port

The end user is responsible for the installation of an emergency power off function. Installation must be carried out in compliance with local code regulations.

To shutdown the entire system completely in case of emergency:

Disconnect the AC input to the power module.

Turn off the circuit breaker of the battery module connecting to the power module.

Turn off the circuit breaker of the subsequent battery modules, if applicable.

All these steps above should be performed via a single device.

To simplify the last two steps above, the power module provides an RJ-45 connector on the back panel, called Remote Emergency Power Off (REPO) port. Upon applying a voltage source (5-27VDC, 10mA max.) to pins 2, 4 of this port, the power module will send a signal to trip off the shunt trip on each circuit breaker of all battery modules via the battery detection cable simultaneously. Refer to the diagram below for details.

Figure 2-10a: Activation of remote power off function using a contact normally open switch.

RJ11

5 4 3 2 1 6

Figure 2-10b: Activation of remote power off function using a contact normally closed switch.

RJ11

5 4 3 2 1 6

Signal:

Activation voltage5VDC to 27VDC

Current 10 mA (max)

Installation 2 — 12 86-86000-00 A01

Page 37 of the MGE UPS Systems EX 5RT user manual — OFF O
Page 37 · click to enlarge
Page 37

2.8 Connecting the Input and Output Power Cables to the Input/Output Box

Before carrying out any connections, check that battery circuit breaker is OFF and that the upstream protection devices (Normal and Bypass AC sources) are open (OFF).

EX 5/7/11 RT UPS always comes from factory with Normal and Bypass AC inputs already connected together, using a shunt.

2.8.1 Flexible Cordage and Conduit Installations

Figure 2-12a: Step 1 & 2; Typical plastic and metal coupling installations.

1 1. Knockout die stamp circles.

Outer circle is for Plastic strain relief

I/O BOX

OFF

O

Inner circle is for Metal strain relief

Knockout die stamp circles (on terminal block cover) have two sizes that fit

either plastic or metal coupling. Plastic coupling is for

flexible cordage and metal coupling is for solid wires. Knock out appropriate circle for your application.

OFF O

2. Remove bottom cover plate as shown.
3. Typical plastic strain relief installation:

a) Secure strain relief body onto the knockout plate.

3. Typical Flexible Cordage Installation

b) Strip the jacket back to expose the three wires. Strip the insulation of each wire back 1/2”. Insert the ferrules as shown to each wire.

OFF 0 OFF 0

OFF O

c) Slide the cordage into the strain relief and secure the wires into the terminal blocks using the guide printed on bottom of I/O box.

4. Typical 90 ° Metal Conduit Installation

d) Secure the cordage retainer nut.

OFF O

OFF O

4. Typical 90° metal conduit installation.

a) Secure strain relief body to knockout plate as shown.

b) Insert three wires through flexible conduit and bend 90°.

c) Strip the insulation back 1/2” to expose solid wire and secure three wires into the terminal block using guide printed on bottom of I/O box.

d) Install strain relief cover using two screws.

Installation 2 — 13 86-86000-00 A01

Show 8 more labels / short text on this page
Terminal Block Cover · (b) · (c) · (a) · (d) · (b) (c) · (a) · (d)
Page 38 of the MGE UPS Systems EX 5RT user manual — 2.8 Connecting the Input and Output Power Cables to the Input/Output Box
Page 38 · click to enlarge
Page 38
MGE UPS Systems EX 5RT — 2.8 Connecting the Input and Output Power Cables to the Input/Output Box diagram (page 38)
Fig. 13 · 2.8 Connecting the Input and Output Power Cables to…

Figure 2-12b: Step 3; Typical Straight Metal Conduit installation.

a) Secure strain relief onto the terminal block cover as shown.

c) Strip the insulation of each wire back 1/2” to expose solid wire.

d) Secure three wires into the terminal block using guide printed on bottom of I/O box.

e) Twist the conduit onto the coupling body as shown.

Output 200/208/220/230/240Vac Normal AC Source 200/208/220/230/240Vac Bypass AC Source 200/208/220/230/240Vac

Installation 2 — 14 86-86000-00 A01

Page 39 of the MGE UPS Systems EX 5RT user manual — 2.8.2 System Connections with Common Normal and Bypass AC Sources
Page 39 · click to enlarge
Page 39
MGE UPS Systems EX 5RT — 2.8.2 System Connections with Common Normal and Bypass AC Sources diagram (page 39)
Fig. 14 · 2.8.2 System Connections with Common Normal and Bypa…

2.8.2 System Connections with Common Normal and Bypass AC Sources

Figure 2-13: Normal AC Input and Output Cables installation.

1. Remove the I/O box from EX 5/7/11RT by loosening three screws. Knockout appropriate circle for your wire style.
1. See section 2.8.1 to install normal AC source and output wires per I/O Box Terminal diagram. Re-install the cover plate under the I/O Box.
Page 40 of the MGE UPS Systems EX 5RT user manual — 2.8.2 System Connections with Common Normal and Bypass AC Sources
Page 40 · click to enlarge
Page 40
MGE UPS Systems EX 5RT — 2.8.2 System Connections with Common Normal and Bypass AC Sources diagram (page 40)
Fig. 15 · 2.8.2 System Connections with Common Normal and Bypa…

This module is to provide isolated 120/208/240 VAC outputs to the protected loads.

Figure 2-14: View of EX RT transformer connected downstream for 120/208/240 Vac outputs (shown with one EXB).

Terminal Block Transformer Module Connection diagram (located on bottom of Transformer I/O Box)

Terminal Block capability : AWG 4 solid or stranded wire.

Page 41 of the MGE UPS Systems EX 5RT user manual — UPS
Page 41 · click to enlarge
Page 41

2.8.4 System Connections with Separate Normal and Bypass AC Sources

Figure 2-15: Normal AC Input, Bypass AC, and Output Cables Installation.

Proceed as follows:

1. Remove the cover plate under the I/O Box. Loosen the terminal blocks L1 and L3, and remove the jumper.

OFF

O

earth ground wire first.

2. See section 2.8.1 and I/O Box terminal diagram for installation of Normal AC Input, Bypass AC source, and Output cable with different wire style.
3. Reinstall the cover plate under the I/O Box with four screws.

OFF

O

4. Secure the I/O Box to the power module using three screws.

See section 2.8.3 for connecting EX RT Transformer, if applicable.

OFF

O

data Reset 100 10

UPS

ETHERNET

MAC=00E0D8FF855E

1 2 ON

IP=

Installation 2 — 17 86-86000-00 A01

Show 7 more labels / short text on this page
Bypass · Normal · 3 Output · RS232 Download 66074 · Card Settings · To Step-Down · Transformer (if applicable)
Page 42 of the MGE UPS Systems EX 5RT user manual — 2.8.5 System Connections as Frequency Converter (without Bypass AC Source)
Page 42 · click to enlarge
Page 42
MGE UPS Systems EX 5RT — 2.8.4 System Connections with Separate Normal and Bypass AC Sources diagram (page 42)
Fig. 16 · 2.8.4 System Connections with Separate Normal and By…

2.8.5 System Connections as Frequency Converter (without Bypass AC Source)

Figure 2-16: Accessing Terminal Blocks for Input and Output power cables.

1. Remove the cover plate under the I/O Box.
2. Refer to section 2.8.1 to install normal AC source and output wires per I/O Box Terminal diagram. Reinstall the cover plate under the I/O Box.
3. Secure the I/O Box to power module with three screws.

See section 2.8.3 for connecting EX RT Transformer, if necessary.

Installation 2 — 18 86-86000-00 A01

Page 43 of the MGE UPS Systems EX 5RT user manual — 2.8.4 System Connections with Separate Normal and Bypass AC Sources
Page 43 · click to enlarge
Page 43
MGE UPS Systems EX 5RT — 2.8.4 System Connections with Separate Normal and Bypass AC Sources diagram (page 43)
Fig. 17 · 2.8.4 System Connections with Separate Normal and By…
1. Check that the battery circuit breaker is OFF (“0”) position.
2. Connect the battery power cable to the connectors and of the power and battery modules.
3. Connect the battery detection cable between connectors and of the power and battery modules.

Figure 2-17: Rear view of battery module cable connections.

Page 44 of the MGE UPS Systems EX 5RT user manual — 2.8.4 System Connections with Separate Normal and Bypass AC Sources
Page 44 · click to enlarge
Page 44
MGE UPS Systems EX 5RT — 2.8.4 System Connections with Separate Normal and Bypass AC Sources diagram (page 44)
Fig. 18 · 2.8.4 System Connections with Separate Normal and By…
1. Connect the battery power cable and battery detection cable (provided with the CLA module) between the power module and the CLA module.
2. Connect the DC Input of the CLA to high power battery cabinet.

◗ DC Input Cable cross-section (not provided): maximum 4 AWG solid or stranded wire.

3. Connect the AC input cable of the CLA module to the utility AC input:

◗ AC input cable cross-section (not provided): maximum 16 AWG solid or stranded wires.

Figure 2-18: Rear view of CLA module cable battery and AC input connections.

Installation 2 — 20 86-86000-00 A01

Page 45 of the MGE UPS Systems EX 5RT user manual — OFF ON
Page 45 · click to enlarge
Page 45

Operation

3.0 Scope

Operation describes EX 5/7/11RT system characteristics of indicators and controls, modes and specifications and theory of operating the EX 5/7/11RT. The user procedures include performing software programming that will maintain smooth performance. Refer to Figure 1.6 for descriptions of circled numbers.

3.1 Initial Startup

1. Check that the manual bypass switch is on Normal position.
2. Set the normal AC source circuit breaker to the ON position.
3. Set the battery circuit breaker to the ON position.

The load is powered via the bypass AC source, but not protected by the UPS.

Batteries are recharging, an eight-hour recharge period is necessary to get full backup time.

LED is ON.

Figure 3-1: Initial Startup Display.

OFF ON

3 — 1 86-86000-00 A01 Operation

Page 46 of the MGE UPS Systems EX 5RT user manual — UPS SET UP EXIT ENT
Page 46 · click to enlarge
Page 46

3.2 UPS Personalization

It is possible to enter this mode through the front panel buttons or the Personal Solution-Pac software for Windows included in the MGE UPS SYSTEMS, INC. Solution- Pac power management suite CD-ROM.

3.2.1 Accessing personalization with front panel buttons

◗ Press "scroll up" and "scroll down" function buttons together for more than 3 sec- onds.

◗ Press the function button placed under the “ENT” word to enter the set up mode and follow the LCD messages using the buttons now defined as select keys. See Tables: 3-1, 3-2, 3-3, and 3-4 for settings.

Figure 3-2: Control Panel with scroll up and down buttons.

UPS SET UP EXIT ENT

OFF ON

Operation 3 — 2 86-86000-00 A01

Page 47 of the MGE UPS Systems EX 5RT user manual — NORMAL AC
Page 47 · click to enlarge
Page 47

Table 3-1: Local Settings.

Display Factory setting Options

Language English French, Spanish, German, Italian

Date / time format International format US format

(DD-MM-YYYY/HH:MM) (MM-DD-YYYY/HH:MM AM/PM)

Date / time change GMT (Greenwich Mean Time) MM-DD-YYYY/HH:MM adjustable

Audible alarm Quick beeps Slow beeps

Table 3-2: Output features.

Display Factory setting Options Comments

Output voltage 208 Volts AC 200/208/220/230/240/250

Frequency converter Disabled Enabled Bypass AC source disabled

Output frequency Auto ranging 50/60 Hz User selectable under frequency converter mode

Eco mode Disabled Enabled See glossary

Hot standby Disabled Enabled Full redundancy (see Figure 3-3)

Operating mode IT Network Industrial (*) See Section 4.1

Bypass When bypass OK (**) When bypass NOK (**) (*) Transfer

Interrupt time 10 ms 10 to 200 ms Interrupt time calibration during (by steps of 10 ms) during load transfer on Bypass AC source out of tolerances

Overload level 102% 50/70%

(*) : - Select "IT Network" for computer loads.

- Select "Industrial" when bypass NOK in case of absolute need for service continuity (with potential

10 ms interrupt).

(**) UPS will switch to Bypass AC Source if it is within the set tolerances.

Figure 3-3: Configuration used to provide full redundancy (2N) to critical loads.

BYPASS AC

Full redundancy configuration offers better protection to critical load, whereas the first UPS acts as the Bypass AC Source for the second UPS.

NORMAL AC

NORMAL AC

LOAD

Operation 3 — 3 86-86000-00 A01

Protective Device · Utility AC Source · Protective Device

Page 48 of the MGE UPS Systems EX 5RT user manual — 3.2.3 Final startup sequence
Page 48 · click to enlarge
Page 48

Table 3-3: ON/OFF features.

Display Factory setting Options Comments

Cold start Disabled Enabled Start on battery.

Forced reboot Enabled Disabled Enables automatic restart of the system even if normal AC source is restored before the end of the shutdown sequence.

Automatic restart Enabled Disabled UPS restarts automatically when normal AC source is restored.

Sleep mode Disabled Enabled Automatic shutdown on battery if output load level

Remote Command Enabled Disabled Enables shutdown or restart orders from software.

Table 3-4: Battery features.

Display Factory setting Options Comments

Battery test Every week No test/daily/monthly

Pre-Alarm 20% 0 to 100% Low battery signal;1% increment

Runtime choice UPS reads # and type From 65 to 400 Ah Requires EX 5/7/11RT CLA if of battery using options (see section 1.5.4 modules connected. “Battery extensions cable kit”)

Battery deep discharge Enabled Disabled If disabled, loss of protection MGE UPS SYSTEMS,INC. warranty.

3.2.2 Accessing personalization through external software

Insert the Solution-Pac CD ROM in your CD drive.

◗ At the first Navigator Screen, select "Installation" and follow the instructions to install Personal Solution-Pac for Windows.

◗ If nothing appears, launch startup.exe

◗ Then go to "Advanced settings" and "UPS settings".

Please note that the Linux/Unix/MacOS versions of Personal Solution-Pac do not include this feature.

3.2.3 Final startup sequence

Press the button more than 3 seconds.

◗ After UPS internal test sequence, the green LED goes on.

Operation 3 — 4 86-86000-00 A01

Page 49 of the MGE UPS Systems EX 5RT user manual — 2.8.4 System Connections with Separate Normal and Bypass AC Sources
Page 49 · click to enlarge
Page 49
MGE UPS Systems EX 5RT — 2.8.4 System Connections with Separate Normal and Bypass AC Sources diagram (page 49)
Fig. 19 · 2.8.4 System Connections with Separate Normal and By…

This is the standard operating mode, set by the factory.

Scroll up and scroll down function buttons allow you to read the UPS measurements (Normal AC source voltage, Bypass AC source voltage, operating mode, battery capacity and UPS Serial Number).

The load is now powered by the UPS battery.

Page 50 of the MGE UPS Systems EX 5RT user manual — 2.8.4 System Connections with Separate Normal and Bypass AC Sources
Page 50 · click to enlarge
Page 50
MGE UPS Systems EX 5RT — 2.8.4 System Connections with Separate Normal and Bypass AC Sources diagram (page 50)
Fig. 20 · 2.8.4 System Connections with Separate Normal and By…

The main advantage of the ECO mode (see glossary) is that it reduces the consumption of electrical power.

The load is supplied with AC power but not protected in ECO mode.

The load is automatically supplied in Normal mode via the Normal AC input.

3. Both Normal and Bypass AC sources not available or out of tolerance:

The load is powered by the battery power from the UPS.

Operation 3 — 6 86-86000-00 A01

Page 51 of the MGE UPS Systems EX 5RT user manual — 2.8.4 System Connections with Separate Normal and Bypass AC Sources
Page 51 · click to enlarge
Page 51
MGE UPS Systems EX 5RT — 2.8.4 System Connections with Separate Normal and Bypass AC Sources diagram (page 51)
Fig. 21 · 2.8.4 System Connections with Separate Normal and By…

Figure 3-6: Transfer, Threshold and End of backup time.

The load continues to be protected by the UPS when the Normal AC source is not available. Power is supplied by the battery.

◗ This indicate the load is supplied by the battery.

◗ The display indicates the battery remaining backup time.

◗ Low battery warning on display. There is very little remaining battery backup time. Close all appli- cations because UPS automatic shutdown is pending.

◗ The load is transferred to the Bypass AC source if available. In this case:

Page 52 of the MGE UPS Systems EX 5RT user manual — 2.8.4 System Connections with Separate Normal and Bypass AC Sources
Page 52 · click to enlarge
Page 52
MGE UPS Systems EX 5RT — 2.8.4 System Connections with Separate Normal and Bypass AC Sources diagram (page 52)
Fig. 22 · 2.8.4 System Connections with Separate Normal and By…

After an outage, the UPS restarts automatically when AC power is restored (unless this function has been disabled via UPS personalization).

Figure 3-7: Shutdown display, circuit breaker, and AC source switch.

1. Press the OFF button more than 3 seconds.

The load is no longer protected by the UPS. It is powered via the bypass AC source. If the UPS is set in frequency converter mode, the load will not be powered.

If the bypass AC source is out of tolerance, the UPS will generate a calibrated 10msec output interrupt.

4. For a full shutdown of UPS and connected load, the upstream circuit breaker (not included) should be set to the OFF position.

Operation 3 — 8 86-86000-00 A01

Page 53 of the MGE UPS Systems EX 5RT user manual — Symptoms IT network mode Industrial mode
Page 53 · click to enlarge
Page 53

Maintenance

4.0 Scope

Maintenance includes a troubleshooting guide of symptoms and possible solutions, Hot swapping the power module and Battery Module, and testing scenarios.

4.1 Information Technology (IT) Network and Industrial Operating Modes

Table 4-1: Network and Industrial Modes of Operation.

Symptoms IT network mode Industrial mode

Overload, and Bypass Load is transferred to Bypass AC source. Same as I/T network mode, but AC source in tolerance. UPS returns to normal mode if overload to the UPS does not return to is removed. normal mode if overload is removed.

Overload, and Bypass The UPS shuts down and load is not Load is transferred to Bypass AC source not in tolerance. transferred to Bypass AC source. AC source with 10 milli- seconds output break. The UPS does not return to normal mode if overload is removed. Output short circuit and Bypass The load remains powered by the UPS. Load is transferred to Bypass AC source in tolerance. The UPS shuts down after 3 minutes AC source, the UPS returns to if the short circuit remains normal mode if the short circuit is removed.

Output short circuit and Bypass The load remains powered by the UPS. The load is transferred to AC source not in tolerance. The UPS shuts down after 3 minutes Bypass AC source with if the short circuit remains. 10 milliseconds output break. The UPS does not return to normal mode if the short circuit is removed.

4 — 1 86-86000-00 A01 Maintenance

Page 54 of the MGE UPS Systems EX 5RT user manual — 4.2 Troubleshooting
Page 54 · click to enlarge
Page 54

4.2 Troubleshooting

◗ If any of LED's or is on, there is an operating anomaly or an alarm.

◗ Use "scroll up" or "scroll down" function button to reset the audible alarm.

◗ Troubleshooting not requiring MGE UPS SYSTEMS, INC. after-sales support:

Table 4-2: Troubleshooting not requiring MGE after-sales support.

LED is on, and Bypass AC AC source is not connected Rewire correctly the normal AC source is present to the correct terminals. source. the alphanumeric display shows BAD CONNECTION REWIRE AC NORMAL

LED is on, Load supplied by bypass AC source. Push the ON button for more than 3 the alphanumeric display shows: seconds. LOAD LEVEL XX kW / XX KVA

LED is on, and Bypass AC UPS overload Check if any device is shorted or failed. source is present the alphanumeric display shows: THERMAL OVERLOAD 1XX%

LED is on, Short circuit conditions on output Check if any device is shorted or devices. failed. the alphanumeric display shows: CURRENT OVERLOAD

LED is on, 180° degree phase shift between Check if bypass source is correctly bypass and normal AC source. wired but the alphanumeric display shows: (in case of upstream transformer use). BYPASS REVERSE REWIRE BYPASS Audible alarm is on, Input/Output box not Check if the Input/Output box the alphanumeric display shows: installed correctly. is correctly installed. See section 2.8. I/O BOX REMOVED

Maintenance 4 — 2 86-86000-00 A01

Symptom Indication Correction

Page 55 of the MGE UPS Systems EX 5RT user manual — 2.8.4 System Connections with Separate Normal and Bypass AC Sources
Page 55 · click to enlarge
Page 55

Table 4-3: Troubleshooting requiring MGE after-sales support.

LED and are on, Internal fault Call the after sales support department. Bypass AC Source is present and transfer of load and audible alarm is on. on bypass AC source the alphanumeric display shows: xxx FAULT

LED is on, and audible alarm Battery fault during the battery test. Call the after sales support department. is on, the alphanumeric display shows BATTERY FAULT

LED is on, Static switch failure Call the after sales support department. the alphanumeric display shows: SHUTDOWN STATIC SW FAILED

Audible alarm is on, Batteries may have exceeded Follow the battery replacement procedure the alphanumeric display shows: their rated life period. Battery in section 4.5. END OF WARRANTY capacity is severely reduced.

Maintenance 4 — 3 86-86000-00 A01

Symptom Indication Correction

Page 56 of the MGE UPS Systems EX 5RT user manual — 2.8.4 System Connections with Separate Normal and Bypass AC Sources
Page 56 · click to enlarge
Page 56
MGE UPS Systems EX 5RT — 2.8.4 System Connections with Separate Normal and Bypass AC Sources diagram (page 56)
Fig. 23 · 2.8.4 System Connections with Separate Normal and By…

This operation can be performed without interrupting the load.

1. Stop the UPS with the OFF button (press more than 3 seconds).

LED is on (If LED is not on, do not turn the manual bypass and call the after sales support department).

2. Turn the manual bypass switch to the BYPASS position.
3. Switch the battery circuit breaker(s) to the OFF position.
4. Loosen three screws to remove the Input/Output box.
5. Disconnect the battery cables and from the power module.

The connected equipment is powered by the Bypass AC source.

Maintenance 4 — 4 86-86000-00 A01

Page 57 of the MGE UPS Systems EX 5RT user manual — OFF ON
Page 57 · click to enlarge
Page 57

4.4 Re-connecting the power module

This operation can be performed without interrupting the load.

Figure 4-2: Reconnect the power module.

1. Secure the Input/Output junction box using the three screws.
2. Reconnect the cables and to the

power module.

3. Switch the battery circuit breaker(s) to the ON position.

LOAD LEVEL

4 kW/ 5 kVA

OFF ON

4. Check if Normal AC source circuit breaker

is on the ON position.

5. Check that the LED is on.
6. Turn the manual bypass switch from the BYPASS to the NORMAL position.
7. Follow initial start up sequence (see section 3.1) in order to personalize the UPS.
8. Push the ON button for more than 3 seconds.

The green LED is on, and the connected equipment is now protected by the UPS.

Maintenance 4 — 5 86-86000-00 A01

Page 58 of the MGE UPS Systems EX 5RT user manual — 2.8.4 System Connections with Separate Normal and Bypass AC Sources
Page 58 · click to enlarge
Page 58
MGE UPS Systems EX 5RT — 2.8.4 System Connections with Separate Normal and Bypass AC Sources diagram (page 58)
Fig. 24 · 2.8.4 System Connections with Separate Normal and By…
1. Switch the battery circuit breaker(s) to the OFF position.

The connected equipment is powered by the UPS, but not protected.

It is also possible to replace battery pack instead of battery module.

1. First, switch the battery circuit breaker(s) to the OFF position.

See section 2.5 and follow instructions for battery pack replacement.

1. Reconnect the battery cables and to the power module.
2. Switch the battery circuit breaker(s) to the ON position.

Maintenance 4 — 6 86-86000-00 A01

Page 59 of the MGE UPS Systems EX 5RT user manual — 120V U 160V 280V
Page 59 · click to enlarge
Page 59

Appendix

5.0 Electrical Specifications

5.1 System Input/Output Power Ratings

Table 5-1: EX 5/7/11 RT Input and Output Characteristics.

Source Voltage Frequency

Normal AC Source 208 to 240 Volts AC 40 to 70 Hz

Bypass AC Source 208 to 240 Volts AC* 48 to 52 Hz**

Load Output 120/240Vac Volts AC 50/60 Hz autoranging (120/208/240Vac (or frequency converter) are possible with transformer module)

(*): depends on output voltage setting, can be modified by software. (**): set to +/- 4% by default, (1,2,4,8% are possible values), can be modified by software.

5.2 System Overload Characteristics

Figure 5-1: Power supplied as a function of input voltage (left), and Permissible UPS overloads as a function of time (right).

0.5s t 30s

120V U 160V 280V

5.3 System Backup Characteristics

Table 5-2: Back-up Time ( in minutes).

System Load Percentage 30% 50% 70% 100% Standard 11kVA 25 14 9 5 Standard 11kVA + 1 EXB 61 30 20 14 Standard 11kVA + 2 EXB 96 53 34 22 Standard 11kVA + 3 EXB 135 84 51 30 Standard 11kVA + 4 EXB 172 102 67 42 Standard 11kVA + 5 EXB 201 113 87 53 Standard 7kVA 37 21 12 7 Standard 7kVA + 1 EXB 80 53 30 20 Standard 7kVA + 2 EXB 124 83 55 32 Standard 7kVA + 3 EXB 185 108 75 45 Standard 7kVA + 4 EXB 245 132 98 57 Standard 7kVA + 5 EXB 287 164 118 72 Standard 5kVA 37 31 21 12 Standard 5kVA + 1 EXB 90 70 53 30 Standard 5kVA + 2 EXB 140 112 83 55 Standard 5kVA + 3 EXB 185 156 108 75 Standard 5kVA + 4 EXB 255 207 132 98 Standard 5kVA + 5 EXB 306 260 164 118

Appendix 5 — 1 86-86000-00 A01

Show 5 more labels / short text on this page
Load Percentage · Load Percentage · 100% · 70% · 60s 120s
Page 60 of the MGE UPS Systems EX 5RT user manual — System Operation Mode On-line On Battery
Page 60 · click to enlarge
Page 60

Table 5-3: Battery Recharge time to recover 90% of the rated backup time after discharge at full load.

Configuration for Configuration for Configuration for 2 hours backup time 4 hours backup time 8 hours backup time

EX 5 7 hours 15 hours 24 hours

EX 7 5 hours 12 hours 20 hours

EX 11 7 hours 15 hours 24 hours

5.4 System Short Circuit Protection Short circuit current provided by EX 5/7/11RT in normal or battery mode: EX5/7 RT 110A for 80ms EX11 RT 190A for 80ms

5.5 Accessories Electrical Characteristics

EX RT Transformer Nominal power 11 kVA Nominal current 63 A Input voltage 208-240Vac Output Voltage 120/208/240Vac Frequency 50/60 Hz (+/-10%) Isolation (EN 61558-1-2-4) 3.75 kV / 5 M ohms Operating temperature From 0° to +40°C Max. operating rel. humidity 95% Derating / altitude Pn-10% > 1000 m Dimensions HxWxD (tower) 17.5 x 5.15 x 25 inches (444 x 131 x 635 mm) Dimensions HxWxD (rack 3U) 5.15 x 17.5 x 25 inches (131 x 444 x 635 mm) Weight 151 lbs. (68.5 kg)

EX RT CLA module AC input voltage 156-280 Volts AC Input frequency 40-70 Hz Battery charge current 6 A DC

5.6 Heat Rejection

Table 5-4: Full load heat rejection in BTU’s/hr.

System Operation Mode On-line On Battery

5.7 Environmental Characteristics

◗ The operating temperature is 0 to 40°C (8 hours at 45°C), however optimum operation is within the +20 to +25°C range and at 5-95% humidity, non-condensing at altitude up to 3280ft without de-rating.

◗ The storage temperature : -20 to 40°C. Humidity : 5-95%, non condensing.

◗ Battery backup time is adversely affected by high and low temperatures. It is significantly reduced at tempera- tures under 10°C. Above 25°C, battery service life is cut in half every 10°C. Above 40°C, battery manufacturers no longer guarantee operation due to the risk of thermal runaway.

◗ Air enters through the front air vent grills and exits through the back. Always keep air vent grills unobstructed.

Appendix 5 — 2 86-86000-00 A01

5kVA 1327 1944 · 7kVA 1858 2722 · 11kVA 2919 4278

Page 61 of the MGE UPS Systems EX 5RT user manual — Proprietary Rights Statement
Page 61 · click to enlarge
Page 61

MGE Warranty & Proprietary Rights for Single Phase Products

MGE Warranty

The liability of MGE UPS SYSTEMS, INC. hereunder is limited to replacing or repairing at MGE UPS SYSTEMS, INC.’s factory or on the job site at MGE UPS SYSTEMS, INC.’s option, any part or parts which are defective, including labor, for a period of 24 months from the date of purchase. The MGE UPS SYSTEMS, INC. shall have the sole right to determine if the parts are to be repaired at the job site or whether they are to be returned to the factory for repair or replacement. All items returned to MGE UPS SYSTEMS, INC. for repair or replacement must be sent freight prepaid to its factory. Purchaser must obtain MGE UPS SYSTEMS, INC.’s Return Materials Authorization prior to returning items. The above conditions must be met if warranty is to be valid. MGE UPS SYSTEMS, INC. will not be liable for any damage done by unauthorized repair work, unauthorized replacement parts, from any misapplication of the item, or for damage due to accident, abuse, or Act of God.

In no event shall the MGE UPS SYSTEMS, INC. be liable for loss, damage, or expense directly or indirectly arising from the use of the units, or from any other cause, except as expressly stated in this warranty. MGE UPS SYSTEMS, INC. makes no warranties, express or implied, including any warranty as to merchantability or fitness for a particular purpose or use. MGE UPS SYSTEMS, INC. is not liable for and Purchaser waives any right of action it has or may have against MGE UPS SYSTEMS, INC. for any consequential or special damages arising out of any breach of warranty, and for any damages Purchaser may claim for damage to any property or injury or death to any person arising out of its purchase of the use, operation or maintenance of the product. MGE UPS SYSTEMS, INC. will not be liable for any labor subcontracted or performed by Purchaser for preparation of warranted item for return to MGE UPS SYSTEMS, INC.’s factory or for preparation work for field repair or replacement. Invoicing of MGE UPS SYSTEMS, INC. for labor either performed or subcontracted by Purchaser will not be considered as a liability by the MGE UPS SYSTEMS, INC.

This warranty shall be exclusive of any and all other warranties express or implied and may be modified only by a writing signed by an officer of the MGE UPS SYSTEMS, INC. This warranty shall extend to the Purchaser but to no one else. Accessories supplied by MGE UPS SYSTEMS, INC., but manufactured by others, carry any warranty the manufacturers have made to MGE UPS SYSTEMS, INC. and which can be passed on to Purchaser.

MGE UPS SYSTEMS, INC. makes no warranty with respect to whether the products sold hereunder infringe any patent, U.S. or foreign, and Purchaser represents that any specially ordered products do not infringe any patent. Purchaser agrees to indemnify and hold MGE UPS SYSTEMS, INC. harmless from any liability by virtue of any patent claims where Purchaser has ordered a product conforming to Purchaser’s specifications, or conforming to Purchaser’s specific design.

Purchaser has not relied and shall not rely on any oral representation regarding the Product sold hereunder and any oral representation shall not bind MGE UPS SYSTEMS, INC. and shall not be part of any warranty.

There are no warranties which extend beyond the description on the face hereof. In no event shall MGE UPS SYSTEMS, INC. be responsible for consequential damages or for any damages except as expressly stated herein.

Proprietary Rights Statement

The information in this manual is the property of MGE UPS SYSTEMS, INC., and represents a proprietary article in which MGE UPS SYSTEMS, INC., retains any and all patent rights, including exclusive rights of use and/or manufac- ture and/or sale. Possession of this information does not convey any permission to reproduce, print, or manufacture the article or articles shown herein. Such permission may be granted only by specific written authorization, signed by an officer of MGE UPS SYSTEMS, INC.

IBM, PC-AT, ES/9000, and AS/400 are trademarks of International Business Machines Corporation. MGE and MGE UPS SYSTEMS are trademarks of MGE UPS SYSTEMS, INC. Other trademarks that may be used herein are owned by their respective companies and are referred to in an editorial fashion only.

Page 62 of the MGE UPS Systems EX 5RT user manual — Warranty Extension (Warranty+) not available on products
Page 62 · click to enlarge
Page 62

Warranty and Product Registration

Thank you for choosing MGE UPS SYSTEMS, INC. for your power protection, distribution, and quality requirements. We are pleased to have you join our increasing family of users.

In order to maximize the value you receive from this product, and to ensure that you are kept informed of product or software updates, we recommend that you take a few minutes to register your new purchase. You may register online at the URL noted below. Should you not have Internet access, you may mail or fax this form back (attn: Warranty Registration) as indicated at the bottom of the page.

Register your UPS athttp://www.mgeups.com/email/warranty/menu.htm

Please be prepared with the following information to register and validate your UPS warranty, keep informed on software and product updates, and register your extension "Warranty+" if purchased with the UPS.

User Information

Product information

Date of purchase

Warranty Extension (Warranty+) not available on products

I have purchased a warranty extension (Warranty+)

Reference_____________________ Contract Number: _________________

Thank you from all of us at MGE.

MGE UPS SYSTEMS, INC., 1660 Scenic Avenue, Costa Mesa, CA 92626, USA

Tel714-557-1636 Fax: 714-557-9788

41-000154-53 Rev B00 9/2003

Show 13 more labels / short text on this page
Last name ________________________________________ · First name ________________________________________ · Company name ________________________________________ · Address ________________________________________ · Zip code ________________________________________ · City ________________________________________ · State/Province ________________________________________ · Country ________________________________________ · Tel ________________________________________ · Fax * ________________________________________ · Email* ________________________________________ · Model ________________________________________ · Serial Number ________________________________________
Page 63 of the MGE UPS Systems EX 5RT user manual — Return Policy for Repair (RMA)
Page 63 · click to enlarge
Page 63

MGE Customer Care Center

Technical Support and Product Services

Technical questions? If you encounter a problem while following the instructions in this manual, or have

?

questions about the operation, repair, or servicing of your equipment, please direct calls to MGE UPS

SYSTEMS, INC. Customer Care Center or visit our web site www.mgeups.com for complete service information.

To insure that your questions are correctly answered, please obtain the part number, assembly number, and serial

number of the unit and include them in any discussions or correspondence.

Part Number_____________________________________________________________________
Assembly Number_____________________________________________________________________
Serial number_____________________________________________________________________

Who To Contact

Customer Care Center: 1-800523-0142, extension 1113 (USA and Canada Only)

Field Service Engineer1-800-438-7373 (USA and Canada Only)
Customer FAQ or International calls1-714-557-1636 (Ask for Technical Support Group, TSG)

Commitment: MGE UPS SYSTEMS, INC. is committed to providing easy to access factory trained experts that will provide responses to any questions that you might have.

Scheduling Field Service Engineer Support

Scheduling of the MGE Field Service Engineers typically should be done 7 to 10 days before they are required on-site. If the startup of the UPS is critical to maintaining your schedule, please call the MGE toll free telephone number at 1-800-438-7373, to insure a safe installation and startup that will maintain the MGE warranty and insure smooth performance

Return Policy for Repair (RMA)

Should you require factory service for your equipment, contact MGE’s Customer Support Services and obtain a Return Materials Authorization (RMA) prior to shipping your unit. Never ship equipment to MGE without first obtaining an RMA.

Date______________________________________________________
RMA Number______________________________________________________
Contact Name______________________________________________________
Page 64 of the MGE UPS Systems EX 5RT user manual — W—4 86-86000-00 A01
Page 64 · click to enlarge
Page 64

(This page left blank intentionally)

W—4 86-86000-00 A01

Page 65 of the MGE UPS Systems EX 5RT user manual — Term used Definition / Meaning
Page 65 · click to enlarge
Page 65

Glossary

Term used Definition / Meaning

@ At.

/ And/or.

+/- Plus or Minus.

≤ Equal to or less than.

# Number.

°C Degree Celsius.

°F Degree Fahrenheit.

Ø Phase angle.

Ω Ohm; unit of resistance.

® Trade Mark.

2nd Second.

AC or ac Alternating current, also implies root-mean-square (rms).

Ambient Temp. Temperature of surrounding air.

Ambient noise Acoustical noise of surrounding environment.

ANSI American National Standard Institute.

AWG American Wire Gauge.

Breaker Electrical circuit interrupter.

BTU or Btu British thermal unit. Defined as the amount of heat required to raise the tempera- ture of one pound of water by 1°F.

BYPASS See “Static Transfer switch”.

BYPASS mode See “off-line mode”.

Carrier The company or individual responsible for delivering goods from one location to another.

C Common.

CB Circuit breaker.

cm Centimeter.

dB Decibels.

DC Direct current.

Conduit A flexible or rigid tube enclosing electrical conductors.

C.S.S. Customer Support Service.

Glossary G — 1 86-86000-00 A01

Page 66 of the MGE UPS Systems EX 5RT user manual — 2.8.4 System Connections with Separate Normal and Bypass AC Sources
Page 66 · click to enlarge
Page 66

Current rating The maximum current that a conductor or equipment can carry reliably without damage.

dBA Decibel Adjusted.

dBrnC Decibel above reference noise.

DC or dc Direct current, or voltage.

Digital Meter The LCD display on the front panel of inverter system.

Earth ground A ground circuit that has contact with the earth.

ECO Mode Operating mode by which the load is supplied directly by the AC source if it is within the tolerances defined by the user. This mode reduces the consumption of electrical power.

Electrician Refers to an installation electrician qualified to install heavy-duty electrical components in accordance with local codes and regulations. Not necessarily qualified to maintain or repair electrical or electronic equipment.

FET Field effect transistor.

Freq. Frequency.

Frequency slew rate The change in frequency per unit of time. Given in term of Hz per second (Hz/sec.).

GND Ground (safety).

Hz Hertz, frequency measurement unit, 1Hz is one cycle per second.

Inverter mode See “on-line” mode.

I Current.

IEC International Electrotechnical Commission.

IEEE Institute of Electrical and Electronic Engineers.

Input branch circuit The input circuit from the building power panel to the equipment.

Inverter An electrical circuit that generates an AC voltage source from a DC voltage source.

IGBT Insulated gate bipolar transistors.

I/O Input/Output.

I/T or IT Information Technology.

kVA KiloVolt-Ampere; is equal to 1000 Volt-Ampere.

L Line.

LCD Liquid-Crystal Display unit.

LED Light Emitting Diode.

Mains or Mains 1 Main AC input source.

Mains 2 Bypass AC input source.

mA Milliampere.

MAX. Maximum.

MCM Thousand circular mil; standard wire sizes for multiple stranded conductors over 4/0 AWG in diameter. M is from Roman numerical system indicating 1000.

Module Refers to individual power inverter module.

N Neutral.

Glossary G — 2 86-86000-00 A01

Page 67 of the MGE UPS Systems EX 5RT user manual — 2.8.4 System Connections with Separate Normal and Bypass AC Sources
Page 67 · click to enlarge
Page 67

NC Normally closed.

NO Normally open.

NEC National Electrical Code.

NFPA National Fire Protection Association.

PN Part number.

On-line mode Inverter output power is the primary energy source to load.

Off-line mode Inverter output is off, and the load connected at the inverter output receives power from utility line via a static transfer switch or maintenance bypass relay.

OSHA Occupational Safety and Health Agency.

PCA Printed circuit assembly.

PCB Printed circuit board.

PWM Pulse Width Modulation.

SCR Silicon controlled rectifier.

Shipping damage Any damage done to an article while it is in transit.

SPDT Single Pole Double Throw.

Static Transfer An solid state switching mechanism electronically controlled to pass AC power directly from the utility to an output load.

Technician Refers to an electronic technician qualified to maintain and repair electronic equipment. Not necessarily qualified to install electrical wiring.

Test connector DB-9 type connector on the LCD panel allowing MGE UPS SYSTEMS Customer Support Service technician to access programmable and diagnostic features of the system.

VA Volt-amps, unit for apparent power measurement, equal V x I.

VAC or Vac Voltage of AC type.

VDC or Vdc Voltage of DC type.

ve Battery voltage.

Via By way of.

Glossary G — 3 86-86000-00 A01

V Volts · VA Volt amperes

Page 68 of the MGE UPS Systems EX 5RT user manual — G — 4 86-86000-00 A01
Page 68 · click to enlarge
Page 68

(This page left blank intentionally)

G — 4 86-86000-00 A01

Page 69 of the MGE UPS Systems EX 5RT user manual — 86-86000-00 A01
Page 69 · click to enlarge
Page 69

Reorder Form

1660 Scenic Avenue Costa Mesa, CA 92626

Use this form to report any errors, omissions, or other problems you have experienced, or to order additional hardcopies of this document. A free copy of this document may be downloaded from the proprietary MGE Rep Web site. Please contact your MGE UPS SYSTEMS,INC. Representative for assistance.

NAME

COMPANY ___________________________________________________________________________________

STREET ADDRESS ____________________________________________________________________________

CITY ________________________________________ STATE __________________ ZIP ___________________

I would like to order (quantity @ $75.00 each) additional copies of the:

86-86000-00 A01

I would like to report the following problems with this document:

Page 70 of the MGE UPS Systems EX 5RT user manual — 2.8.4 System Connections with Separate Normal and Bypass AC Sources
Page 70 · click to enlarge
Page 70
Page 70 of the MGE UPS Systems EX 5RT user manual — 2.8.4 System Connections with Separate Normal and Bypass AC Sources
Page 71 of the MGE UPS Systems EX 5RT user manual — 2.8.4 System Connections with Separate Normal and Bypass AC Sources
Page 71 · click to enlarge
Page 71
Page 71 of the MGE UPS Systems EX 5RT user manual — 2.8.4 System Connections with Separate Normal and Bypass AC Sources
Page 72 of the MGE UPS Systems EX 5RT user manual — Latin America and Other International
Page 72 · click to enlarge
Page 72
MGE UPS Systems EX 5RT — 2.8.4 System Connections with Separate Normal and Bypass AC Sources diagram (page 72)
Fig. 25 · 2.8.4 System Connections with Separate Normal and By…

w w w . m g e u p s . c o m

Contact MGE

United States

MGE UPS SYSTEMS 1660 Scenic Ave. Costa Mesa, CA 92626

Tel(714) 557-1636 (800) 523-0142 Fax: (714) 557-9788 email: info@ mgeups.com www: mgeups.com

Canada

MGE UPS SYSTEMS #9, 2789 Thamesgate Drive Mississauga, ON L4T 4E8

Tel(905) 672-0990 (877) 672-0990 Fax: (905) 672-7667 email: info@ mgeups.com www: mgeups.com

Latin America and Other International

MGE UPS SYSTEMS 1660 Scenic Ave. Costa Mesa, CA 92626

Tel(714) 513-7831 (800) 523-0142 ext. 7831 Fax: (714) 434-0199 email: info@ mgeups.com www: mgeups.com

1660 Scenic Avenue, Costa Mesa, California 92626 • (714) 557-1636

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the MGE UPS Systems EX 5RT

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the MGE UPS Systems EX 5RT

Be the first to ask — other owners or our team will answer.