Made in USA Made in USA
User’s Manual
Models 3 & 4

1660 Scenic Avenue Costa Mesa, CA 92626
(714) 557-1636 www.mgeups.com
Revision History Esprit Rack UPS User's Manual
86-153301-03 Copyright © 2000 MGE UPS Systems
All rights reserved. Printed in USA Revision A00 New Release 10/00

This manual contains important safety instructions for the Esprit Models 3 and 4 that should be followed during installation and maintenance of the UPS and Batteries.
The UPS and battery module contains voltages which are potentially hazardous. All repairs should be performed by qualified service personnel only.
Q Do not attempt to power the UPS from any receptacle other than a 2-pole, 3-wire grounded receptacle for models 3 and 4.
Q To reduce the risk of fire, connect Esprit to a circuit provided with the following maximum branch circuit protection in accordance with NEC, ANSI/NFPA70:
Model 3: 30 ampere branch circuit protection; Model 4: 50 ampere branch circuit protection. Q Do not place Esprit near water or in an environment of excessive humidity.
Q Do not allow liquids or foreign objects to get inside Esprit.
Q Do not block air vents in front, on top, or on bottom of Esprit.
Q Do not plug any household appliances such as hair dryers into Esprit receptacles.
Q Do not place Esprit in direct sunlight or close to heat emitting sources.
Q The AC power receptacle should be near the equipment and easily accessible. To isolate Esprit from AC input, remove the input cord from the AC power receptacle.
Q Esprit contains lead-acid batteries that should be disposed of or recycled in accordance with local applicable laws.
Q Prior to installation, store Esprit in a dry location.
Q Storage temperatures must be between -4° to +113°F (-20° to +45°C);
Q Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions to handle high voltages. Keep unauthorized personnel away from batteries.
: risk of electric shock symbol

Q Remove watches, rings, or other metal objects.
Q Use tools with insulated handles.
Q Do not lay tools or metal parts on top of batteries.
Q Disconnect the charging power source prior to connecting or disconnecting battery terminals.
Q Wear rubber gloves, boots, and safety glasses.
Q Determine if the battery is inadvertently grounded.
Q Please dispose of the packaging in accordance with applicable laws.
Note: This equipment has been tested and found to comply with Class A limits of Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when equipment is operated in an industrial environment. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Properly shielded and grounded cables and connectors must be used in order to meet FCC emission limits.


6A. Entering/Exiting Configuration Mode 6—1 6B Using Configuration Mode 6—1 6C Configuration Options 6—2
7A. Maintenance 7—1 Maintenance Log 7—1 Places to Contact for Service and Questions 7—1 7B. Recycling Your UPS 7—2
Other Fine MGE Products inside back cover
2a. Rear View of Models 3 and 4 With Rack Kit and Extended Batteries 2—2 2b. Optional Rack Mounting Kit 2—2 2c. Typical Front Views of Models 3, 4, Extended Battery, Label Placement 2—2 3a. RS232, Contact Closures and Remote Shutdown 3—2 3b. Communication Ports (USB and RS232 serial port) 3—3 3c. AC Line Cord of the Extended Battery 3—3 4a. Front Panel Indicators and Controls 4—1
3a. UPS Wiring Information 3—3 5a. Esprit Models 3 and 4 Rack UPS Specifications 5—1

Thank you for your purchase of the Esprit rack "UPS" from MGE. The Esprit "UPS" will provide many years of, trouble-free power protection for critical high availability servers and other devices. Please read this manual fully, to familiarize yourself with the safety instructions and Esprit features. MGE UPS Systems
The Esprit UPS is comprised of three major systems: the inverter, the battery/battery charger and the bypass.
All logic and supervision in the UPS is provided by a state-of-the-art micro-controller.
Inverter The inverter is the heart of the UPS and inverts direct current (DC) from the battery into alternating current (AC) at 120 volts. The DC voltage from the batteries is converted into a pseudo-sine wave by a pulse width modulated (PWM) inverter. This unique MGE technique, eliminates all bulky 60 HZ components, reduces heat, and greatly enhances reliability.
MGE, one of the largest UPS manufacturers in the world, has a power protection solution for every power problem. Our product range includes UPSs from 250 VA to over 4.5 MVA in single and three phase configurations. Other products include Power Management Software, DC to AC inverters, line conditioners and isolation transformers. Contact your sales representative today for additional information about MGE’s other fine products. Why the Need for Uninterruptible Power?
Battery The battery provides the energy source for back-up when a power failure occurs. The battery is a recombinant, sealed, lead acid-type battery which provides the high current required for UPS use and long life. It requires no addition of water during its life.
Servers and other electronic devices do not store sufficient energy to overcome the power outages and short interruptions that occur on a daily basis. Any interruption of the utility power may stop the operation of a computer and cause loss of data, potential hardware damage, and inconvenience.
Battery Charger The battery charger maintains the battery. The battery charger converts 120 volt AC utility power to filtered and regulated DC current specific for battery charging.
A "UPS" is an uninterruptible power supply. The UPS has an internal battery to provide power back-up if the utility power is lost or a short outage occurs. In addition, the Esprit UPS provides surge protection from indirect lightning strikes, power surges and short high voltage transients (spikes) created by machinery or other common equip- ment. Theory of Operation
Bypass The bypass is the electro-mechanical hardware providing a transfer to or from the inverter. This is done rapidly and synchronized to the utility power sine wave in order to provide continuity to the critical device and not cause a re-boot. Make Sure You Have the Following:
Esprit normally operates in the bypass mode. Surge suppression and filtering are also provided in this mode.
Q Esprit Rack UPS Q MGE P3 Policy
Q Solution Pac CD ROM Q Warranty Card
The UPS instantly transfers the load to the battery when a power failure occurs. If the power returns before the battery is exhausted, the operation returns to normal and the battery is recharged.
Q Cables (RS232 & USB) Q Warranty Statement
Q Quick Start Guide Q Esprit Label
Q Stabilizing Feet (2) Q Rack “ears” (2)
Q Mounting Screws & Nuts



2A. Product Features & Benefits
Q Plug in operation Low installation cost
Q Modular concept Greater flexibility Add batteries as needed
Q High efficiency Longer life and back-up time Up to 93% on battery, 98% on utility
Q 2/3 components reduction Longer life, higher reliability Unique MGE design
Q Many user selectable Tailor the UPS to Front panel button accessible parameters environment
Q Built-in receptacles Easier to specify Most common NEMA receptacles are included
Q Quiet operation Allows placement in "library Small fan only runs while in type" environments battery mode
Q Standard HID Provides the latest and fastest Other communications optional communications communications possible
Q Network-based power Multiple server shutdown and management software supervision
Q Web management New standard for web Easier to use than HTML and via XML management provides additional features
Q Extended distribution Provides additional Optional options receptacles for critical loads Call factory for availability
(US and Canadian Models)
Dimensions/Weights and Part Numbers
Model Dimensions (H W D) Weight (lbs.) Part Number UPC
Esprit 3 SLR 5.25 x 17 x 20 75 ESP030 635760894318 Esprit 4 SLR 5.25 x 17 x 20 75 ESP040 635760894455 SLR Extended Battery 5.25 x 17 x 20 60 ESP001 635760894004 Rack rail kit 5 x 5 x 17 6 ESP104 635760894042 AS/400 DB9 cable 12 x 12 x 1 1 ESP105 635760894059 AS/400 DB15 cable 12 x 12 x 1 1 ESP107 635760894073
Features Benefits Comments

Figure 2a. Rear View of Models 3 and 4 With Rack Kit and Extended Batteries
Model 3 Model 4
Utilization en atmosphere controlee Intended for use in a controlled environment Utilización preuista en un amblento controlado.
Utilization en atmosphere controlee Intended for use in a controlled environment Utilización preuista en un amblento controlado. COM1 USB SW4
Do not disconnect under load
Do not disconnect under load
Overload protection, push to reset
Overload protection, push to reset
Overload protection, push to reset
Overload protection, push to reset
144Vdc / 4 Amp hr. Continuous amps: 25
144Vdc / 5 Amp hr. Continuous amps: 33.3
Intended for computer loads only
Intended for computer loads only
Extended Battery Extended Battery
Figure 2b. Optional Rack Mounting Kit Figure 2c. Typical Front Views of Models
(ESP104) 3, 4, Extended Battery, Label
Models 3 and 4
mounting screws & nuts

3A. Storing the UPS and Recharging the Battery
Always store the equipment in its original packaging.
The battery is of the sealed lead-acid type. Battery recharge requires that the battery module be plugged into an energized NEMA 5-15 receptacle for 6-8 hours. The battery may be charged in the box by pulling the AC cord out through the bottom.
Battery storage or prolonged shutdown should never exceed 6 months or 68°F (20°C), for a battery initially at 100% charge. The battery warranty is void if the 6 month recharge interval is not adhered to.
It is recommended that the equipment be unpacked in an area close to its installation location.
Two people are required to lift the unit.
Remove the Solution-Pac CD, RS232 cable, and USB cable from the box and set aside for later use. Fold the box flaps outward. Gently rotate the box on its side and slide the unit out of the box. Gently rotate the unit upright and then remove the packing material. Save packaging for future shipment of UPS to MGE for recycling.
Choose a location out of direct sunlight with adequate ventilation. The operating ambient temperature range is 32° to 104°F (0° to 40°C). Temperatures above 77°F (25°C) should be avoided as battery life is reduced.
Ensure that there is clearance around the intake vents in the front of the UPS and that the rear is unob- structed. Six inches of clearance at the rear of the unit is required. Units may be placed vertically or hor- izontally with zero clearance. Use the supplied stabilizing feet when vertically mounting the UPS and/or extended battery. Rack Mounting
Optional rack mounting hardware is available for rack mounting. Instructions for their use are included in the rack kit. See Figure 2a.
The following accessories are available for use with your equipment. Refer to each accessories' manual for full installation, operation and maintenance instructions.
Q Rack Rail Kit Q AS/400 Cables (for contacts) Q Multi-slot Communication Cabinet Q Extended distribution Q Extended batteries (no additional manual necessary)

Plug the DC battery cable into the UPS module as shown in Figure 2a. The cable plug is keyed, so make sure to align the plug properly to the receptacle. Do not force the cable on, nor attempt to reverse the connection. To do so, will damage the equipment and void the warranty. Plug the AC line cord into an AC line receptacle. See Figure 3f.
Turn off the UPS module by depressing the “Off” red button if the “inverter on” or "utility power present" (bottom LED) is lit. Unplug the AC line cord for the battery module. Unplug the DC battery cord. For extended batteries unplug AC line cord and DC battery cord. 3G. Connecting to the Communication Ports
If you plan to utilize Solution-Pac HID ("human interface device" protocol), read the Solution-Pac HID manual on the Solution-Pac CD for a full description of its features.
To connect to your computer, you will need the RS232 serial port or a USB (Universal Serial Bus) port. The connection will be made between your computer’s serial or USB port and the serial or USB port on the rear of the UPS module as shown in Figure 3d. Cables are supplied for this purpose.
A slide switch is provided for either RS232 or USB communication. The slide switch (shown in Figure 3d) is preset for RS232. Push the switch down for USB communication.
If communication does not operate, check the position of the slide switch.
The RS232 port also contains two low voltage (24 VDC)/low current (5MA) contact closures. See Figure 3d below. To use these an optional cable is available. These can be used by AS/400 computers or for special uses.
Figure 3a. RS232, Contact Closures and Remote Shutdown
OV
RX
TX OV
PNP
+8 to +15VDC

The transistor resistance is 27 ohms and the maximum current allowed is 140mA AC or DC with ambient temperature of up to 40°C.
In order to get a "logic low" you have to limit the current to: logic low voltage required divided by 27, logic low voltage = 0.5V. I max = 0.5/27=0.0185A=18mA.
If you intend to use other forms of communication, an optional Multi-slot Communication is available that will convert the RS232 serial commands into the following formats:
Q Ethernet, SNMP Q J-Bus/RS422 Q High voltage/current relay contacts
Figure 3b. Communication Ports (USB and RS232 serial port)
Utilization en atmospher Intended for use in a co Utilización preuista en u
Do not disconnect under load
Plug the AC line cord of the UPS module into an AC 2-pole, 3-wire grounded receptacle for models 3 and 4. There should be no other loads on this branch circuit. To do so may result in a circuit overload. Refer to National Electrical Code (NEC) specifications for requirements in your area or ask your electrician.
Table 3a. UPS Wiring Information Figure 3c. AC Line Cord of the Extended Battery
Utilization en atmosphere controlee Intended for use in a controlled environment Utilización preuista en un amblento controlado.
Do not disconnect under load
G
144Vdc / 5 Amp hr. Continuous amps: 25
3I. Connecting the Loads
Utilize the receptacles on the rear of the UPS module to connect your critical loads. If you need more, you may want to consider the addition of MGE's optional distribution extension.


Solution Pac software allows you to interface your computer with the UPS. The software is loaded on your computer and through the communication port, can access and react to status information from the UPS. Refer to the Solution Pac manual on the CD for a full description of its operation.

4A. UPS Startup
You are ready to start the equipment after installing the UPS module, optional battery module(s), any options, and the communication cable (if used).
Follow these simple steps:
Your UPS has auto-frequency and voltage sensing and will automatically configure itself to 120, 50 or 60 Hz.
Your equipment is now receiving protected power from the UPS.
Figure 4a. Front Panel Indicators and Controls
6 Status LEDs Control Buttons
Alarm Silence (Controls audible alarm
LED operation is described fully in section 4E.
Your UPS will perform internal diagnostics as well as check utility power.
After depressing the green "On" button and starting your UPS for the first time, you will hear an audible "beep" confirming the button has been depressed, and your UPS will perform the following diagnostic tests:
! · & alarm/fault handling) · !

If desired, the UPS can be set up to operate at a known, fixed frequency regardless of the detected utility frequency. Fixed-frequency operation is often desirable in installations that make use of cold-start capability. Discussion on this is in the Advanced Configuration Section (section 6) of this manual.
If utility power is present and within specifications, your UPS will start up in bypass mode. Power will be supplied to your computer loads and will be protected from a utility loss. The utility power present, green indicator " ", will be lit.
If utility power is not present, your UPS will start on battery until utility power is restored. No diagnostics will be performed in this case.
Battery Mode: Utility power is outside specifications and computer loads are now powered On by UPS battery source.
Flashes grey push button. Immediately save your work and shut down connected
computer loads to prevent data loss. The actual time to reach "low battery" can vary significantly depending on the critical loads and condition of the batteries.
At any time, your UPS may be shut down by depressing the "Off" red button. Make sure to hold the button down for 2 seconds (prevents accidentally turning off your UPS). You will hear an audible "beep" confirming the button has been depressed.
There are six status LEDs, arranged in a vertical column just above the control buttons. Icons to the right of each indicator indicate the function. The status indicated by each LED is listed below, in the order that they appear on the front panel (top to bottom):
!

1. Fault The UPS is operating The UPS has detected a The UPS has detected an Detected normally. No faults new operating fault. The operating fault that has been (yellow) have been detected. FAULT indicator will continue acknowledged by the user. to flash until the fault has been acknowledged by pressing the grey silence alarm button. 2. Replace The UPS battery is O.K. The result of the last battery Battery test indicates that the UPS (red) battery cannot provide at least half of its rated run time. The battery should be replaced. This could also indicate an inverter problem. 3. Battery The UPS battery is The charger is not operating The UPS battery is not yet Charging charged within 80% of properly. Check that the fully charged and cannot Indicator its full capacity. battery module power cord deliver its full rated run time if (green) is plugged into a source a power failure occurs. other than the UPS itself.
4. Output The UPS is capable of The UPS is heavily The UPS is slightly over-loaded. Overload supporting the load overloaded. Automatic The UPS will continue to sup- (yellow) connected to it. shutdown is imminent. port the load but it may not be able to provide its full rated run time if the UPS has to run on battery power. Reduce the load. 5. Utility Utility power is not Utility power is present but Utility power is present, stable Power connected to the UPS. is either unstable or the line and within acceptable voltage Present voltage is too high or too low limits. In this state, the UPS (green) to allow operation in utility will be operating on utility power mode. In this state, power mode. the UPS will normally be operating on battery power. 6. Inverter The UPS is not The UPS is operating on The UPS is operating on on/UPS operating on battery battery power and battery power. The inverter on battery power. The inverter is performing its periodic is running. power turned off. inverter/battery test. The (green) battery test is started once every 28 days of operation and lasts for up to 60 seconds.
Off Flashing On

The "Fault Detected" LED turns on and acts as described above for ANY system alarm, including those that have their own status indicators (e.g. overload, replace battery).
There are 3 buttons present on the front panel:
Q The grey, " " top button controls the audible alarm and alarm/fault handling.
Q The green, " " center button turns the UPS on.
Q The red " ", bottom button turns the UPS off. The internal microprocessor can directly read the state of the top (alarm silence) and bottom (power off) buttons. The UPS is capable of distinguishing between a “short” and “long” depression and can perform different actions based on how long a button or combination of buttons is depressed. A “short” button press is defined as pressing and releasing a button within a 2-second time frame. A “long” button press is recognized if a button is pressed and held for more than 2 seconds.
When a button is pressed, the UPS responds by beeping the horn. If the button is held down longer than 2 seconds the UPS responds by beeping the horn again. The action assigned to a short button press is carried out AFTER the button is released. Actions assigned to a long button press are carried out immediately after the 2-second timeout, even if the button is not released after this time.
The UPS is capable of decoding six distinct “button states”:

Although six button states are detectable, not every button combination has an assigned task. button states/combinations that have no assigned task will simply be ignored.
The “Utility Power Present” does NOT reflect the state of the UPS output. If, for example, the UPS has shut down due to an output overload, the Utility Power Present LED may be solidly ON but the UPS output could be turned off (due to the overload).
LED Status Audible Alarm Pattern UPS Action
Fault " " LED flashes until Low Run time Warning Warning when there is less than alarm is acknowledged or (short-long-short beep) 3 minutes of back-up time cleared. remaining.
Fault " " LED flashes until Low Battery Warning/Shutdown Occurs within 1 minute of UPS alarm is acknowledged or (short-long-long beep) shutdown. Could also indicate cleared. a faulty battery charger.
Fault " " LED flashes until High Battery Warning There is a problem with the alarm is acknowledged or (short-short-short-long beep) battery system. problem is corrected.
Fault " " LED and Charge Charger Problem Warning The battery system may not be " " LED flashes until alarm (long-short-long-short beep) plugged into an AC source or is acknowledged or problem there is a charger problem. is corrected.
Fault " " LED Battery Fail Battery/Inverter Test Failure Indicates failed battery/inverter " " LED flashes until alarm (long-short-short-short beep) test performed every 28 days. is acknowledged or cleared. Clear fault and recharge battery for 8 hours. Manually initiate test again. If fault recurs, call for service.
Fault " " LED flashes until Output Voltage Low Output shuts down to protect alarm is acknowledged or (on inverter, load from low voltage. cleared. short-long-short-short beep)
Fault " " LED flashes until Output Voltage High Output shuts down to protect alarm is acknowledged or (on inverter, load from high voltage. cleared. short-short-short-short beep)
Fault " " LED and Overload Output Overload Flashes when load exceeds " " LED flashes until alarm Warning/Shutdown 105%, solid when overload is is acknowledged or problem (long-long-long beep) 101-105%, automatically clears corrected, flashes when when load is reduced. shutdown is imminent, and solid if warning only.



Table 5a. Esprit Models 3 and 4 Rack UPS Specifications
Item Specification Comment Output VA 2880/4000 Output W 2016/3150 Surge protection, joule rating 420 joules per system Each battery cabinet adds 210 joules Waveform Stepped approximation of sine wave Pseudo-sine wave on back-up only Nominal input voltage 120 VAC (opt. 100 or 127 VAC) +10%, -15% Maximum input voltage (VAC) 140 Low voltage transfer (VAC) 102 Adjustable to 96 Low line return (VAC) 109 Adjustable to 99 High line transfer (VAC) 132 High line return (VAC) 126 Input current (A) 24/33 maximum Input frequency (HZ) 50 or 60 + or - 2.5 HZ Auto-select at start-up Input protection Customer provided, branch Transfer time 4-8 ms. To or from battery Overload protection, line mode Output disabled at >120% load Overload protection, battery mode Output disabled at >120% load Efficiency, on utility >98% Efficiency, on battery >93% Battery mode voltage 120 VAC + or - 5% (120 VAC mode) Battery life expectancy 3-5 years Output frequency regulation Nominal + or - 0.5 HZ On battery Battery mode output protection Electronic current limit Self-protected Battery 12 each 5 Ah 144 VDC nominal bus Maximum charge current 0.7 A With 100% discharge Float voltage 2.25 VDC/cell (162 VDC) Backup time 5 minutes 100% load Battery protection Current limiting fuses 1 internal, 1 w/extended battery Recharge time 8 hrs.. to 90%, 4 hrs.. to 80% Full discharge Battery charger ripple current 0.05C maximum Low battery alarm level 1.75 v/cell, no load (126 VDC) Low battery shutdown level 1.65 v/cell, full load (119 VDC) Faulty battery alarm level 1.8 v/cell (130 VDC) Low battery alarm level 3 minutes before end of discharge Charger protection Overload, current protected Max. # of extended batteries Unlimited Controls Start, stop, alarm reset switches Communications RS232 or USB + two contact HID on RS232 or USB closures included (selectable RS232 or USB) Temperature 0-40 C Air flow 30 CFM on battery Heat: ESP030 40-141W Humidity 0-95% non-condensing Heat: ESP040 60-211W Noise 45 dBA maximum

Table 5a. Esprit Models 3 and 4 Rack UPS Specifications (Continued)
Item Specification Comment Design standards Safety; UL, cUL 1778, Emissions; FCC A, Surge protection; ANSI C62.41, Transportation; (drop test), IEC 68 level 1, (vibration), IEC 68.2-6 level 3, testing; PowerCet tested Input connection NEMA 5-30/50 w/ six foot cord Output connections 1 NEMA 5 30/50 and 4 5-15 Auxiliary DC input 1 each special female connector on Provides additional battery time UPS (18" cord and male connector on optional battery) Size 1 each (UPS, battery) 5.25" X 7.25" X 19" Weight 65/70 lbs.. total MTBF 200K hours

Unix Server 1 2 3 4 server servers servers servers PC Server 1 2 3 4 5 6 7 8 server servers VA 500 1000 1500 2000 2500 3000 3500 4000 Esprit 3 SLR 90 40 28 19 11 6 Esprit 3 SLR + 1 Ext. Batt. 240 90 40 28 19 15 Esprit 3 SLR + 2 Ext. Batt. 360 150 90 60 45 38 Esprit 4 SLR 120 50 30 20 15 12 9 7 Esprit 4 SLR + 1 Ext. Batt. 240 100 72 45 35 28 24 18 Esprit 4 SLR + 2 Ext. Batt. 360 180 110 75 55 45 35 29
Extended Batteries (Qty.) 1 2 3 4 Model Esprit 3 12 30 45 60 Esprit 4 15 25 38 49

Esprit Front Panel Configuration Mode Usage and Instructions For advanced users only!
The Esprit UPS is shipped from the factory with a configuration that is suitable for most applications. However, there are some circumstances where modification of the UPS operating parameters is required. A special configuration mode, accessible from the front panel, has been provided for this purpose. This section of the manual describes how to use the front panel configuration mode and describes the UPS parameters that can be changed by the user.
The Esprit front panel configuration mode is entered by simultaneously depressing the top (Alarm silence) and bottom (Power OFF) buttons for approximately 1-2 seconds. The Esprit will acknowledge entry into configuration mode by sounding the buzzer and slowly flashing the AC PRESENT indicator. The AC PRESENT indicator blinks slowly during the time that the Esprit is in configuration mode.
To exit configuration mode, press and hold both top and bottom buttons again. The AC PRESENT indicator will stop flashing, and the remaining indicators will resume their normal function. Any changes to the Esprit configuration made by the user will be permanently saved.
The Esprit incorporates a timer that automatically terminates configuration mode if no activity is detected for 30 seconds. This feature prevents the unit from remaining in the vulnerable offline state for a long period if the configuration mode is accidentally entered.
When configuration mode is activated, the usage of the front panel status indicators changes. The top 4 indicators (GENERAL FAULT, BATTERY FAULT, BATTERY CHARGING, and OVERLOAD) are now used to indicate the internal feature being viewed or modified. The AC PRESENT indicator blinks slowly to indicate that the Esprit is in configuration mode. The bottom-most ON BATTERY indicator shows the state (on/enabled or off/disabled) of the currently active feature.
In configuration mode, the topmost button (Alarm silence) is used to advance to the next configuration setting. The top 4 indicators, which light in unique patterns to indicate which option is being viewed/modified, cycle forward each time the top button is pressed. The bottom button (power off) is used to toggle the current option ON or OFF. The ON BATTERY indicator toggles on and off each time the bottom button is pressed.

It is possible to cycle backward through the configuration options by pressing and holding the top button. A given option setting can be forced to its factory default state by pressing and holding the bottom button.
The middle (Power ON) button is not used in configuration mode.
To leave configuration mode, simultaneously depress and hold in both the top and bottom buttons until the buzzer sounds and the AC PRESENT indicator stops flashing. Any changes made to the Esprit configuration will now be permanently saved.
The table below lists the options that can be changed by the user in configuration mode, and shows which front panel indicators will be on for each option.
Option Indicators Number Fault Batt Fail Charge Overload Option affected 0 — Extended Battery switch A 1 * — — — Extended Battery switch B 2 — * — — Extended Battery switch C 3 * * — — Operating voltage switch A 4 — — * — Operating voltage switch B 5 * — * — Input voltage tolerance switch A 6 — * * — Input voltage tolerance switch B 7 * * * — Test alarm 8 — — — * Limit run time on battery power 9 * — — * Cold start enable 10 — * — * Auto restart after low battery shutdown 11 * * — * UPS mode (On=Normal, Off=Line condition) 12 — — * * Automatic frequency detect on powerup 13 * — * * Operating frequency (0=50 Hz, 1=60 Hz) 14 — * * * Comm port mode (0=Normal, 1=Tuning/factory) 15 * Power-on inverter test
) = Option On/illuminated, ( — ) = Option Off/dark

These three option switches should be changed as shown in the table below when new battery cabinet(s) are added to the UPS. The standard setting for these options are all OFF, selecting the single/internal battery module option.
Option Setting Number of battery cabinets installed 0 (A) 1 (B) 2 (C) Esprit 3 & 4
— * — 2 * * — 3
— — * 4 * — * 5
— * * 6 * * * 7
Indicators: ( *
) = Option On/illuminated ( — ) = Option Off/dark
These two options select the nominal operating voltage of the UPS as shown in the table below. The factory setting is 3=Off, 4=Off, which configures the Esprit for 120V (230V) operation.
Switch Setting Nominal Operating Voltage 3 (A) 4 (B) Low Voltage
— * 127 V * * Custom
Indicators: ( *
) = Option On/illuminated ( — ) = Option Off/dark
Do not select the "Custom" setting (Option 3 & 4 both ON) unless you are instructed to do so by MGE service.
(SlimLine)

Use these two option switches to select the Esprit’s sensitivity to low/high input voltage conditions. The Esprit will switch to battery power when the utility voltage falls outside the range selected. The percentages shown in the table below are subtracted/added to the nominal voltage setting as set by options 4, 5. The factory setting is 5=OFF, 6=OFF which selects the –15/+10% range.
Switch Setting Input Voltage Tolerance 5 (A) 6 (B) Low limit High limit
— * - 10% + 10% * * Custom
Indicators: ( *
) = Option On/illuminated ( — ) = Option Off/dark
Do not select the "Custom" setting (Option 5 & 6 both ON) unless you are instructed to do so by MGE service. Option 7 – Test Alarm
The normal state of this option is OFF. Turning it on will instruct the Esprit to issue a "User Test Fault". This condition does NOT affect the UPS operation in any way, but it does close the Low Battery contact on the DB9 communication port, and activates the FAULT indicator and audible alarm (pattern short-short-long). You can use this option switch to test hardware connected to the Low Battery contact without actually running the Esprit battery down.
To clear the User Test Fault, set this option to OFF, or follow the "Alarm Clear" procedure. Press and hold the top button. Option 8 – Limit run time on battery power
The normal setting for this option is OFF, which allows the UPS to operate on battery for the maximum time possible. The Esprit run time on battery is limited only by the capacity of it’s battery system and the battery state of charge.
If Option 8 is turned on, the Esprit will run a maximum of 15 minutes on battery power before turning itself off. Actual run time may be less, depending on size of battery system and load. Option 9 – Cold Start (allow UPS to run on battery power on startup)
When Option 9 is turned ON (factory setting), the UPS is allowed to start up on battery power if the AC input voltage is not present or not of satisfactory quality. The ability to run on battery power immediately upon startup is known as "cold start" capability.
If this option is turned OFF, the UPS will start up with its output OFF if input AC is not present or usable. The output will not be turned on until input AC is present and usable. Once the UPS turns on it’s output, a subsequent loss/disturbance of input AC will cause the UPS to run on battery power as usual.

The factory setting for this option is ON, which allows the UPS to automatically turn its output back on following a Low Battery shutdown once input AC is present. This setting is the usual one for applications where the UPS is connected to automated or unattended equipment that is capable of restarting itself without direct human intervention.
If the load connected to the UPS requires special attention when it is powered up, this option should be turned OFF. When Auto Restart is turned off, the UPS output will stay turned off until it is manually restarted by pressing and holding the top silence/restart button on the front panel. Option 11 – Automatic UPS mode
The default setting for Option 11 is ON, which allows the Esprit to act like a typical UPS. The UPS will automatically switch from utility to backup power as needed.
If this option is turned off, the Esprit acts like a line conditioner. The battery backup system is disabled. If the input utility power is acceptable, the Esprit will pass it through to the load. If the input power is unacceptably low or high, the load power is removed. The Esprit will NOT operate on battery power if Option 11 is turned off! Option 12 – Automatic Frequency Detect
When this option is set the factory default ON setting, the Esprit will analyze the input power when it is turned on, and configure itself to operate at the proper frequency (50 or 60 Hz). If utility power is not present when the Esprit is turned on, it will configure itself based on the frequency setting in place when the unit was last turned off (see option 13 setting).
If this option is turned OFF, the Esprit will configure itself to operate using a utility power frequency set by Option 13. Power-up input AC frequency analysis is not performed. Option 13 – Operating Frequency selection
This option setting is only effective if Option 12, Automatic Frequency Detect is turned off. If Option 12 is turned off, this option (13) setting can be used to select the Esprit’s nominal oper- ating frequency. If this option is OFF, 50 Hz operation is selected. If ON, 60 Hz operation is selected.
The factory setting for this option is ON, selecting 60 Hz operation at startup. Note, however, that the setting of this option is overwritten by the UPS logic if option 12 (Automatic Frequency Detect) is enabled. If the Esprit is powered up from a 50 Hz source with option 12 enabled, the setting of this option (13) will be forced to OFF. Option 14 – Communication Mode Selection
This option should be left in it’s factory-standard OFF setting unless you are instructed to turn it ON by MGE Service. If this option is inadvertently turned ON, the Esprit may be rendered incapable of operating with UPS monitoring and control software, including MGE’s Solution-Pac software.

When this option is set to the factory default ON setting, the Esprit will perform a short battery/inverter test shortly after it is turned on. This test is only performed only if the UPS is able to power up the load from utility power first. If the POIT is enabled, the UPS will power up the load from utility power, then briefly switch to battery power approximately 5-7 seconds after it is powered up. The UPS runs on battery for only 3-5 seconds, so no significant drain on the battery will occur.
The POIT is disabled if this option is turned OFF. The setting of this option has no effect on the scheduling and execution of the monthly inverter/battery test, which runs less frequently than the POIT but is considerably more exhaustive.

7A. Maintenance
Clean the UPS with a dry cloth after turning off all power to the UPS and switching off the power switch.
The UPS performs monthly automatic battery tests. However, it is recommended that a 6 month test be performed on the UPS for battery condition. Perform all tests off peak hours with applications shut down.
UPS serial number Date of installation Location Notes
In USA or Canada, call 1-800-438-7373 M - F 24 hours. For service outside USA or Canada, call your local distributor. You may also visit our web site at: www.mgeups.com


In USA or Canada, call 1-714-557-1636, M - F, 6:00 A.M. to 5:00 P.M. PST. Ask for a return goods authorization for free UPS or battery recycling. MGE does not cover return freight charges for recycling and will not accept items without a return goods authorization number.

Problem Possible cause Required User Action
Q UPS does not turn on. Q UPS is not plugged in. Q Plug UPS into a working outlet. Q Wall socket is dead. Q Test wall socket, repair as required. Q UPS has not been activated. Q Press Output ON (1) button for
one second, then release.
Q There is no power to Q Confirm that the UPS is on. Q See above. the computer load. Q Output circuit breaker is Q Disconnect load and check. If tripped. okay, reset circuit breaker. Q Load plugs are not seated Q Remove and reseat plugs. properly.
Q Battery Online indicator Q Utility line is out of Q Test wall socket, repair as remains on, even though specification. required. line voltage is present.
Q UPS beeps occasionally. Q UPS is on battery. Q None - UPS is protecting your
system.
Q UPS does not provide Q Battery capacity is low. Q Allow battery to charge for 24 the expected backup time. hours, then retest. Q Protected equipment power Q Reduce load, then retest. requirements exceed UPS capacity.
Q Overload indicator flashes. Q Protected equipment power Q Reduce the load. requirements exceed UPS capacity.
Q Battery Fault indicator is lit. Q Battery is weak or charger is Q Make sure battery is connected. faulty. If battery is properly connected, allow the battery to charge for 24 hours. Retest. Have batteries replaced if condition persists. Make sure battery charger is plugged into a functioning outlet.




Eclipse Surge Suppressors Ellipse 300-1200 VA

ESV+ UPS ESV+ Rack UPS 780-2200 VA 780-2200 VA

EX UPS EX Rack UPS 700-3000 VA 700-3000 VA

Call MGE for many more power solutions:
(714) 557-1636 or (800) 523-0142
Esprit UPS 3 - 13.5 kVA
MGE GREEN SWEEP Call MGE to return your UPS for free recycling to a US EPA-certified recycling center and help protect our environment.


USA (headquarters) 1660 Scenic Avenue Costa Mesa, CA 92626 tel: (800) 523-0142
Pages referenced in this manual — manufacturer, support and downloads.
Owners and our team usually reply within a day — and your question helps the next person too.
Be the first to ask — other owners or our team will answer.