Thank you for selecting an MGE UPS SYSTEMS product to protect your electrical equipment.
The Upsilon STS range has been designed with the upmost care. We recommend that you take the time to read this manual to take full advantage of the many features of your new equipment.
MGE UPS SYSTEMS pays great attention to the environmental impact of its products. Measures that have made Upsilon STS a reference in environmental protection include:
◗ the eco-design approach used in product development,
◗ production on an industrial site certified ISO 14001,
◗ recycling of Upsilon STS at the end of its service life.
To discover the entire range of MGE UPS SYSTEMS products and the options available for the Upsilon STS range, we invite you to visit our web site at www.mgeups.com or contact your MGE UPS SYSTEMS representative.
All products in the Upsilon STS range are protected by patents. They implement original technology not available to competitors of MGE UPS SYSTEMS.
To take into account evolving standards and technology, equipment may be modified without notice. Indications concerning technical characteristics and dimensions are not binding unless confirmed by MGE UPS SYSTEMS.
This document may be copied only with the written consent of MGE UPS SYSTEMS. Authorised copies must be marked "Upsilon STS Installation and User Manual, nr 3402011300".

Using this document
Information may be found primarily by consulting:
◗ the index.
Go up or down one page
Up / down selection
Select date for event log consultation
Interrupt manual transfer without break
E S C D E L
Return to previous display





1.1 Upsilon STS 30 - 60 - 100 - 160 - 250 A (cabinet 1400 mm high)

0.45 m2
1.2 Upsilon STS 30 - 60 - 100 - 160 - 250 - 400 - 600 A (cabinet 1900 mm high)

0.57 m2

1.3 Access to control and connections
Upsilon STS 30 - 60 - 100 - 160 - 250 A (cabinet 1400 mm high)

Switch Q1 for Source S1
Circuit breaker Q5 for control electronics power supply
Circuit breaker Q6 for control electronics power supply
Switch Q2 for Source S2
Bypass switch Q1BP for Source S1
Emergency power off terminal block
Bypass switch Q2BP for Source S2
Upsilon STS 30 - 60 - 100 - 160 - 250 - 400 - 600 A (cabinet 1900 mm high)
Switch Q1 for Source S1
Circuit breaker Q5 for control electronics power supply
Circuit breaker Q6 for control electronics power supply
Switch Q2 for Source S2
Bypass switch Q1BP for Source S1
Bypass switch Q2BP for Source S2
Emergency power off terminal block


I1 17 A I2 9 A I3 2 A
U12 413 V U23 414 V U31 414 V 50.0 Hz
U12 412 V U23 415 V U31 413 V 50.0 Hz
UPS galaxy deuxième étage, salle 13 UPS galaxy deuxième étage, salle 14
Menu button Preferred source S2 Help button Status of switch Q1
Status of switch Q2 Status of source S1 (green, orange, red) Status of source S2 (green, orange, red)
Status of static switch 1 (green, red) Status of static switch 2 (green, red) Status of bypass switch Q2BP Status of switch Q3
Status of bypass switch Q1BP
Status of system output to the load (green, red)

1.5 Relay communication card
Screws to secure the cover
1 2 3 4 5 6
Screws to block cables

Upsilon STS 30 - 60 - 100 - 160 - 250 A (cabinet 1400 mm high)

Upsilon STS 30 - 60 - 100 - 160 - 250 - 400 - 600 A (cabinet 1900 mm high)

See section 6.1 for information on sizing protection devices and cables (Appendix, Technical data).
Two cables maximum may be used per phase.
Upsilon STS 30 to 250 A Input: 3 phases + PEN Output: 3 phases + PEN

See section 1.3 for information on accessing the connections. Connections are made using lugs connected to threaded studs (diameter 8 mm). The cables are tied to the earth bar.
N L1 L2 L3 N L1 L2 L3 N L1 L2 L3
Upsilon STS 30 to 250 A Input: 3 phases + PEN Output: 3 phases + PE + Neutral

See section 1.3 for information on accessing the connections. Connections are made using lugs connected to threaded studs (diameter 8 mm). The cables are tied to the earth bar.
N L1 L2 L3 N L1 L2 L3 N L1 L2 L3
275 mm · 275 mm

Upsilon STS 30 to 250 A Input: 3 phases + PEN Output: 3 phases + PE

See section 1.3 for information on accessing the connections. Connections are made using lugs connected to threaded studs (diameter 8 mm). The cables are tied to the earth bar.
N L1 L2 L3 N L1 L2 L3 N L1 L2 L3
Upsilon STS 30 to 250 A Input: 3 phases + PE + Neutral Output: 3 phases + PE + Neutral

See section 1.3 for information on accessing the connections. Connections are made using lugs connected to threaded studs (diameter 8 mm). The cables are tied to the earth bar.
N L1 L2 L3 N L1 L2 L3 N L1 L2 L3
Upsilon STS 30 to 250 A Input: 3 phases + PE Output: 3 phases + PE

See section 1.3 for information on accessing the connections. Connections are made using lugs connected to threaded studs (diameter 8 mm). The cables are tied to the earth bar.
N L1 L2 L3 N L1 L2 L3 N L1 L2 L3
275 mm · 275 mm · 275 mm

See section 6.1 for information on sizing protection devices and cables (Appendix, Technical data).
A maximum of four cables may be used per phase.
Upsilon STS 400 to 600 A Input: 3 phases + PEN Output: 3 phases + PEN

See section 1.3 for information on accessing the connections. Connections are made using lugs connected to two threaded studs per phase (diameter 10 mm). The cables are tied to the earth bar.
N L1 L2 L3 N L1 L2 L3 N L1 L2 L3
Upsilon STS 400 to 600 A Input: 3 phases + PEN Output: 3 phases + PE + Neutral

See section 1.3 for information on accessing the connections. Connections are made using lugs connected to two threaded studs per phase (diameter 10 mm). The cables are tied to the earth bar.
N L1 L2 L3 N L1 L2 L3 N L1 L2 L3

Upsilon STS 400 to 600 A Input: 3 phases + PEN Output: 3 phases + PE

See section 1.3 for information on accessing the connections. Connections are made using lugs connected to two threaded studs per phase (diameter 10 mm). The cables are tied to the earth bar.
N L1 L2 L3 N L1 L2 L3 N L1 L2 L3
Upsilon STS 400 to 600 A Input: 3 phases + PE + Neutral Output: 3 phases + PE + Neutral

See section 1.3 for information on accessing the connections. Connections are made using lugs connected to two threaded studs per phase (diameter 10 mm). The cables are tied to the earth bar.
N L1 L2 L3 N L1 L2 L3 N L1 L2 L3
Upsilon STS 400 to 600 A Input: 3 phases + PE Output: 3 phases + PE

See section 1.3 for information on accessing the connections. Connections are made using lugs connected to two threaded studs per phase (diameter 10 mm). The cables are tied to the earth bar.
N L1 L2 L3 N L1 L2 L3 N L1 L2 L3

Cable running for cables entering through the top of the Upsilon STS 30 to 250 A cabinet

Cable gland plate that must be drilled to cable size



Tie the cables to the cable way on the door.
Do not run the control wires with the power cables.
Two slots are available in the card cage 5 for additional cards.
1 2 3 4 5
6 7 8 9

For information on using the communication card, see the JBUS communication card manual.
Only one communication port (the RS232 OR the RS485) may be used at a time.

Before proceeding, disconnect all power sources connected to the card. Do not mix very low safety voltage (VLSV) and non-VLSV circuits on the card outputs.


Characteristics of the output contacts: Permissible voltage: 250 V AC, 30 V DC Permissible current: 2 A Cable: 4 x 0.93 mm2, Ø 6.6 mm ± 0.3 mm.
Characteristics of the input contacts: Switched voltage: 5 V DC Current drawn: 10 mA Cable: 4 x 0.34 mm2, Ø 5 mm ± 0.5 mm.
General alarm (fault on one of the sources or on the STS)
Command to disable transfer (transfer to alternate source inhibited)
Load-supplied status condition (presence or absence of power to the load)
Memorised faults reset command

Make sure that the voltages and frequencies of the two sources S1 and S2 are identical.
Make sure that the voltages of the two sources S1 and S2 are the same as the rated voltage (400 V) of Upsilon STS, otherwise see section 3.5 (Customization).

The load is supplied by Source 1 via the bypass.
The load is supplied by Source 1.
If LED 33 is red or off, if LEDs
31 and/or 32 are orange or red: see section "Maintenance".

The load is not supplied with power.

3.3 Normal mode. Operation on preferred source S1 Operation on the preferred source

During normal operation on the preferred source S1, LEDs 24 , 29 , 30 , 31 , 32 ,
33 , 36 and 38 are on in green.
If LED 38 is orange, there is an overload. If LED 38 is red, the load is no more supplied.
The load is automatically transferred to the source offering the highest level of power quality.
For example, if the preferred source S1 goes outside tolerances, LED 31 goes orange or red. The buzzer beeps. Upsilon STS automatically transfers the load to the alternate source S2. LEDs 24 ,
29 , 30 , 32 , 34 , 36 and 38 are on.
Upsilon STS transfers the load back to the preferred source S1 as soon as it returns to within tolerances.
To stop the buzzer, press the
function button marked .
The load is supplied by alternate Source 2.
Transfer is authorised only if the two sources are within tolerances (voltage, frequency) and their phase displacement is within the set limits. If these two conditions are not met, the transfer order is stored in memory and executed when the voltages cross zero. If transfer does not take place within thirty minutes, the order is cancelled.

When the two sources are not in phase, it is possible to force manual transfer using the commands on the screen, after entering a password. 1 - Enter the password (see section 3.5, Customization). 2 - Follow the instructions provided on the screen.
Q1BP
Q2BP Q3

3.4 Display screens
MAIN MENU
I1 17 A I2 9 A I3 2 A
PF 0.3
UPS 1
UPS 2
0 1 0 1 1 0 1 0 0 1 0 1
V1 244 V V2 230 V V3 232 V 50.0 Hz
V1 232 V V2 229 V V3 230 V 50.0 Hz
ALARMS
STATUS
CURRENT MEASUREMENTS
EVENT LOG
VOLTAGE MEASUREMENTS
STATISTICS
FREQUENCY MEASUREMENTS
POWER MEASUREMENTS
LOAD MEASUREMENTS
SETUP
LANGUAGE
ADJUST DATE AND TIME
CONTRAST
BUZZER VOLUME
MAINTENANCE
DISPLAY TEST
SOURCE NAMES
NEW PASSWORD
UNIT ON BYPASS
PERSONALIZATION
DRY CONTACT SETTINGS

3.5 Upsilon STS customization
The password Ø Ø Ø is set in the factory.
Select "Setup", then "Password" to personalise the password.
The monitoring parameters must be identical for the two sources. These parameters depend on the tolerances of the connected loads.
Nominal voltage Overvoltage threshold Undervoltage threshold Nominal frequency Overfrequency threshold Underfrequency threshold Phase sync tolerance Retransfer
400 V 10% 10% 50 Hz 5% 5% 15° YES
Return to preferred source after transfer
Un +5% to Un +20% in 1% steps
Un -5% to Un -20% in 1% steps
50 / 60 Hz
+1% to +10% -1% to -10% in 0.5% steps
Phase error tolerance between the two sources
±1° to ±45° in 1° steps

3.6 Customization of the relay communication card
Inputs Signals available on each contact
- Memorised faults reset command.
1.A - Memorised faults reset command.
- Selection command for source S1.
- Selection command for source S2.
- Selection command for the authorised automatic retransfer mode.
- Command to disable transfer. 1.B
- Selection command for the inhibited automatic retransfer mode.
- Command to authorise transfer.
- Command to disable transfer.
- EPO command (enables the opening command for switches Q1 and Q2).
Outputs Signals available on each contact
1.1 - Load-supplied status condition (presence or absence of power to the load).
- Load-supplied status condition (presence or absence of power to the load). - General alarm (fault on one of the sources or on the Upsilon STS). - Upsilon STS fault. - Source S1 status condition (within or outside tolerances). - Source S2 status condition (within or outside tolerances). - Phase-error condition between the two sources (within or outside tolerances). - Source S1 status condition (active or inactive). - Source S2 status condition (active or inactive). - Preferred-source status condition (S1 inactive and S2 active). - Automatic-transfer status condition (authorised or not). - Overload status condition.
- General alarm (fault on one of the sources or on the Upsilon STS).
- Upsilon STS fault.
- Overload status condition.
- Source S1 status condition (active or inactive).
- Source S2 status condition (active or inactive).
Factory setting · Factory setting

4.1 Identification of anomalies
S1 31 or S2 32
Static-switch LED 33 or 34
LED
LED 38
Internal STS fault.
Source outside tolerances, load still supplied.
Source outside tolerances, no voltage. The load cannot be supplied by this source.
Static-switch fault.
Overload.
Load not supplied.
The meaning of all these anomalies are detailed on the display: Select the alarm: the corresponding informations are displayed.
Transfer to the manual bypass for source S1:
The load is supplied by source S1 via the bypass.
The operation for source S2 is identical, using switches Q2 and Q2BP.
Interlocking of the bypass lines is ensured by use of a single key that must be inserted on the bypass switch to be operated.
Q1BP Q2BP Q3

This product has been designed to respect the environment It does not contain CFCs or HCFCs. It is manufactured on a production site certified ISO 14001.
UPS recycling at the end of service life MGE UPS SYSTEMS undertakes to recycle, by certified companies and in compliance with all applicable regulations, all products recovered at the end of their service life (contact your MGE UPS SYSTEMS branch office).
Packing Packing materials must be recycled in compliance with all applicable regulations.

6.1 Technical data Output currents and voltage
Rated output current:
60 A 100 A 160 A 250 A 400 A 600 A
Input and output voltage:
◗ Rated operating voltage:
380 V / 400 V / 415 V 498 V (415 V +20%) 247 V (380 V -35%) 50 or 60 Hz (45 Hz minimum, 66 Hz maximum)
◗ Maximum voltage:
◗ Minimum voltage:
◗ Rated frequency:
Heat losses (1):
◗ at rated power:
295 W 195 W
430 W 260 W
615 W 350 W
920 W 495 W
1420 W 735 W
2150 W 1070 W
◗ at 50% rated power:
Required ventilation:
350 m3/h
350 m3/h
350 m3/h
1600 m3/h
1600 m3/h
2300 m3/h
2300 m3/h
(1) These characteristics are calculated for a voltage of 400 V and a power factor of 0.8.
Noise in dB (ISO 3746):
55 55 55 59
Type of circuit breaker:
◗ TNS system:
NS100H 4P 4D
NS160H
NS250H
NS400H
NS630H
4P 4D NS160H
4P 4D NS250H
4P 4D NS400H
4P 4D NS630H
◗ TNC system:
3P
3P
3P
3P
Trip unit:
STR22SE
STR22SE
STR23SE
STR23SE
≤1.05 In
≤1.05 In
≤1.05 In
≤1.05 In
Thermal setting:
1.05 In
Magnetic setting:
0.01 s 0.1 s 1 s 10 s 100 s 1000 s
◗ During an overload, transfer between sources is disabled.
◗ Overloads higher than 1.5 In are stored in memory. The alarm must be reset to return to normal operation.

6.2 Simplified diagrams Upsilon STS simplified diagram
Source 2 Source 1
Upsilon STS
Q1
Q2
Q3 Q2BP Q1BP
Simplified diagram of an installation
Alternate sources Preferred sources
Upsilon STS Upsilon STS Upsilon STS
Static-switch control/monitoring · To the load · To the load

6.3 Glossary
Alternate source Backup source that steps in if the preferred source fails.
JBUS communication card Internal card implementing the JBus protocol on a serial link to supply the user with system information.
Load Device(s) or system(s) connected the Upsilon STS output.
Manual bypass Q1BP, Q3 and Q2BP switches, accessible to the user, that may be used to directly supply the load from Source S1 or S2. The bypass enables servicing on the equipment without interrupting the supply of power to the load.
Normal mode Operating mode during which the load is supplied by the preferred source.
Preferred source Source selected as the normal source of power.
Relay communication card Internal card implementing contacts to supply the user with system information.
Static switch Electronic switch ensuring instantaneous switching.