www.mgeups.comp.1Galaxy 3000 10 - 30 kVAp.1MGE UPS SYSTEMSp.1Upsilon STS 30A-60A-100A-160A 250A-400A-600Ap.1Installation and user manualp.1P R Op.1W Ep.1L Ep.1P Tp.1T E Rp.1LE SAVOIR FAIRE MERLIN GERINp.1Introductionp.3Forewordp.4Using this documentp.4Pictograms Documentp.4Displayp.417 maip.488.8 8.88p.4STOPp.4E S C D E Lp.4VOLTp.41. Presentationp.7Dimensions in mmp.7Weight in kgp.7Footprintp.71.3 Access to control and connectionsp.81.5 Relay communication cardp.10A Bp.101.6 JBus communication cardp.102.1 Positioningp.112.2 Power connectionsp.122.3 Connection of the emergency power off terminal blockp.162.4 Connection of the communication cardsp.172.5 Connection of the JBUS communication cardp.172.6 Connection of the relay communication cardp.183. Operationp.193.1 Start-upp.193.2 Shutdownp.19Manual transfer to an out-of-phase alternate sourcep.21S1 S2p.21Q1 Q2p.21Q1BPp.21Q2BP Q3p.213.4 Display screensp.22DOWNGRADED MODEp.22MAIN MENUp.221 KW 6 KVAp.22PF 0.3p.22UPS 1p.22UPS 2p.22E S C VOLTp.22MANUAL TRANSFERTp.22ALARMSp.22STATUSp.22CURRENT MEASUREMENTSp.22EVENT LOGp.22VOLTAGE MEASUREMENTSp.22STATISTICSp.22FREQUENCY MEASUREMENTSp.22POWER MEASUREMENTSp.22LOAD MEASUREMENTSp.22SETUPp.22LANGUAGEp.22ADJUST DATE AND TIMEp.22CONTRASTp.22BUZZER VOLUMEp.22MAINTENANCEp.22DISPLAY TESTp.22SOURCE NAMESp.22NEW PASSWORDp.22UNIT ON BYPASSp.22PERSONALIZATIONp.22DRY CONTACT SETTINGSp.223.5 Upsilon STS customizationp.23E S Cp.23380 / 400 / 415 Vp.233.6 Customization of the relay communication cardp.244. Maintenancep.254.1 Identification of anomaliesp.25LED 21p.25
Page 1 of the MGE UPS Systems 30A user manual — R
Page 1 · click to enlarge
Page 1
MGE UPS Systems 30A — www.mgeups.com diagram (page 1)
Fig. 1 · www.mgeups.com

www.mgeups.com

Galaxy 3000 10 - 30 kVA

MGE UPS SYSTEMS

Upsilon STS 30A-60A-100A-160A 250A-400A-600A

MGE UPS Systems 30A — www.mgeups.com diagram (page 1)
Fig. 2 · www.mgeups.com

Installation and user manual

R

D

E

P R O

R

W E

O

P

L E

B

P T

U

R

T E R

N

N

U

E

H

LE SAVOIR FAIRE MERLIN GERIN

T

Page 2 of the MGE UPS Systems 30A user manual — www.mgeups.com
Page 2 · click to enlarge
Page 2
Page 2 of the MGE UPS Systems 30A user manual — www.mgeups.com
Page 3 of the MGE UPS Systems 30A user manual — Introduction
Page 3 · click to enlarge
Page 3

Introduction

Thank you for selecting an MGE UPS SYSTEMS product to protect your electrical equipment.

The Upsilon STS range has been designed with the upmost care. We recommend that you take the time to read this manual to take full advantage of the many features of your new equipment.

MGE UPS SYSTEMS pays great attention to the environmental impact of its products. Measures that have made Upsilon STS a reference in environmental protection include:

◗ the eco-design approach used in product development,

◗ production on an industrial site certified ISO 14001,

◗ recycling of Upsilon STS at the end of its service life.

To discover the entire range of MGE UPS SYSTEMS products and the options available for the Upsilon STS range, we invite you to visit our web site at www.mgeups.com or contact your MGE UPS SYSTEMS representative.

All products in the Upsilon STS range are protected by patents. They implement original technology not available to competitors of MGE UPS SYSTEMS.

To take into account evolving standards and technology, equipment may be modified without notice. Indications concerning technical characteristics and dimensions are not binding unless confirmed by MGE UPS SYSTEMS.

This document may be copied only with the written consent of MGE UPS SYSTEMS. Authorised copies must be marked "Upsilon STS Installation and User Manual, nr 3402011300".

Page 4 of the MGE UPS Systems 30A user manual — VOLT
Page 4 · click to enlarge
Page 4

Foreword

Using this document

Information may be found primarily by consulting:

◗ the index.

Pictograms Document

Display

Go up or down one page

Up / down selection

17 mai

Select date for event log consultation

88.8 8.88

Interrupt manual transfer without break

STOP

E S C D E L

Return to previous display

VOLT

Show 35 more labels / short text on this page
◗ the contents, · Information, advice, help · Other selection · Visual indication · Confirm · Increase · Action · Details · Reduce · Audio indication · Scrolling menu · Save · LED off · Graphic display · Enter characters · Phase-to-neutral measurements · LED flashing · Graphic display · Phase-to-phase measurements · LED on green · Graphic display · LED on orange · Digital display · Transfer · LED on red · Earth cables · Alarm · Delete · 0101 1010 0101 · Other cables · Access to measurements · Status conditions · Buzzer off · Settings · Maintenance
Page 5 of the MGE UPS Systems 30A user manual — Foreword
Page 5 · click to enlarge
Page 5
Page 5 of the MGE UPS Systems 30A user manual — Foreword
Page 6 of the MGE UPS Systems 30A user manual — Foreword
Page 6 · click to enlarge
Page 6
Page 6 of the MGE UPS Systems 30A user manual — Foreword
Page 7 of the MGE UPS Systems 30A user manual — Footprint
Page 7 · click to enlarge
Page 7

1. Presentation

1.1 Upsilon STS 30 - 60 - 100 - 160 - 250 A (cabinet 1400 mm high)

MGE UPS Systems 30A — 1. Presentation diagram (page 7)
Fig. 3 · 1. Presentation

Dimensions in mm

HeightWidthDepth 1400600500

Weight in kg

Upsilon STS 30 - 60 - 100 A157 kg 160 - 250 A174 kg

Footprint

0.45 m2

1.2 Upsilon STS 30 - 60 - 100 - 160 - 250 - 400 - 600 A (cabinet 1900 mm high)

MGE UPS Systems 30A — Footprint diagram (page 7)
Fig. 4 · Footprint

Dimensions in mm

HeightWidthDepth 1900715800

Weight in kg

Upsilon STS 30 - 60 - 100 A215 kg 160 - 250 A225 kg 400 - 600 A327 kg

Footprint

0.57 m2

Page 8 of the MGE UPS Systems 30A user manual — 1. Presentation
Page 8 · click to enlarge
Page 8

1. Presentation

1.3 Access to control and connections

Upsilon STS 30 - 60 - 100 - 160 - 250 A (cabinet 1400 mm high)

MGE UPS Systems 30A — 1. Presentation diagram (page 8)
Fig. 5 · 1. Presentation

Switch Q1 for Source S1

Circuit breaker Q5 for control electronics power supply

Circuit breaker Q6 for control electronics power supply

Switch Q2 for Source S2

Bypass switch Q1BP for Source S1

Emergency power off terminal block

Bypass switch Q2BP for Source S2

Upsilon STS 30 - 60 - 100 - 160 - 250 - 400 - 600 A (cabinet 1900 mm high)

Switch Q1 for Source S1

Circuit breaker Q5 for control electronics power supply

Circuit breaker Q6 for control electronics power supply

Switch Q2 for Source S2

Bypass switch Q1BP for Source S1

Bypass switch Q2BP for Source S2

Emergency power off terminal block

Show 18 more labels / short text on this page
Communication card cage · Output switch Q3 · Source S2 connection · Output connections · Source S1 connection · Earth bar · Connection cover · Base panels · Adjustable foot pads · Communication card cage · Output switch Q3 · Source S2 connection · Output connections · Source S1 connection · Earth bar · Connection cover · Base panels · Adjustable foot pad
Page 9 of the MGE UPS Systems 30A user manual — 1. Presentation
Page 9 · click to enlarge
Page 9

1. Presentation

MGE UPS Systems 30A — 1. Presentation diagram (page 9)
Fig. 6 · 1. Presentation

I1 17 A I2 9 A I3 2 A

U12 413 V U23 414 V U31 414 V 50.0 Hz

U12 412 V U23 415 V U31 413 V 50.0 Hz

UPS galaxy deuxième étage, salle 13 UPS galaxy deuxième étage, salle 14

Menu button Preferred source S2 Help button Status of switch Q1

Status of switch Q2 Status of source S1 (green, orange, red) Status of source S2 (green, orange, red)

Status of static switch 1 (green, red) Status of static switch 2 (green, red) Status of bypass switch Q2BP Status of switch Q3

Status of bypass switch Q1BP

Status of system output to the load (green, red)

Show 5 more labels / short text on this page
General alarm · Graphic display · Function buttons · Preferred source S1 · Manual transfer button
Page 10 of the MGE UPS Systems 30A user manual — 1.6 JBus communication card
Page 10 · click to enlarge
Page 10

1. Presentation

1.5 Relay communication card

Screws to secure the cover

1 2 3 4 5 6

A B

Screws to block cables

1.6 JBus communication card

Show 7 more labels / short text on this page
Card fixing holes · Protection cover · Openings for cables · Output terminal block · Input terminal block · 48 RS232 connector · RS485 connector
Page 11 of the MGE UPS Systems 30A user manual — 2.1 Positioning
Page 11 · click to enlarge
Page 11

2.1 Positioning

Upsilon STS 30 - 60 - 100 - 160 - 250 A (cabinet 1400 mm high)

MGE UPS Systems 30A — 2.1 Positioning diagram (page 11)
Fig. 7 · 2.1 Positioning
1. Unclip the base panels 14 . 2 - Set the cabinet to a level position using the adjustable foot pads 15 . 3 - Put the base panels 14 back in place.

Upsilon STS 30 - 60 - 100 - 160 - 250 - 400 - 600 A (cabinet 1900 mm high)

1. Unclip the base panels 14 . 2 - Set the cabinet to a level position using the adjustable foot pads 15 . 3 - Put the base panels 14 back in place.
Page 12 of the MGE UPS Systems 30A user manual — 2.2 Power connections
Page 12 · click to enlarge
Page 12

2.2 Power connections

See section 6.1 for information on sizing protection devices and cables (Appendix, Technical data).

Two cables maximum may be used per phase.

Upsilon STS 30 to 250 A Input: 3 phases + PEN Output: 3 phases + PEN

MGE UPS Systems 30A — 2.2 Power connections diagram (page 12)
Fig. 8 · 2.2 Power connections

See section 1.3 for information on accessing the connections. Connections are made using lugs connected to threaded studs (diameter 8 mm). The cables are tied to the earth bar.

N L1 L2 L3 N L1 L2 L3 N L1 L2 L3

Upsilon STS 30 to 250 A Input: 3 phases + PEN Output: 3 phases + PE + Neutral

MGE UPS Systems 30A — 2.2 Power connections diagram (page 12)
Fig. 9 · 2.2 Power connections

See section 1.3 for information on accessing the connections. Connections are made using lugs connected to threaded studs (diameter 8 mm). The cables are tied to the earth bar.

N L1 L2 L3 N L1 L2 L3 N L1 L2 L3

275 mm · 275 mm

Page 13 of the MGE UPS Systems 30A user manual — 2.2 Power connections
Page 13 · click to enlarge
Page 13

Upsilon STS 30 to 250 A Input: 3 phases + PEN Output: 3 phases + PE

MGE UPS Systems 30A — 2.2 Power connections diagram (page 13)
Fig. 10 · 2.2 Power connections

See section 1.3 for information on accessing the connections. Connections are made using lugs connected to threaded studs (diameter 8 mm). The cables are tied to the earth bar.

N L1 L2 L3 N L1 L2 L3 N L1 L2 L3

Upsilon STS 30 to 250 A Input: 3 phases + PE + Neutral Output: 3 phases + PE + Neutral

MGE UPS Systems 30A — 2.2 Power connections diagram (page 13)
Fig. 11 · 2.2 Power connections

See section 1.3 for information on accessing the connections. Connections are made using lugs connected to threaded studs (diameter 8 mm). The cables are tied to the earth bar.

N L1 L2 L3 N L1 L2 L3 N L1 L2 L3

Upsilon STS 30 to 250 A Input: 3 phases + PE Output: 3 phases + PE

MGE UPS Systems 30A — 2.2 Power connections diagram (page 13)
Fig. 12 · 2.2 Power connections

See section 1.3 for information on accessing the connections. Connections are made using lugs connected to threaded studs (diameter 8 mm). The cables are tied to the earth bar.

N L1 L2 L3 N L1 L2 L3 N L1 L2 L3

275 mm · 275 mm · 275 mm

Page 14 of the MGE UPS Systems 30A user manual — 2.2 Power connections
Page 14 · click to enlarge
Page 14

See section 6.1 for information on sizing protection devices and cables (Appendix, Technical data).

A maximum of four cables may be used per phase.

Upsilon STS 400 to 600 A Input: 3 phases + PEN Output: 3 phases + PEN

MGE UPS Systems 30A — 2.2 Power connections diagram (page 14)
Fig. 13 · 2.2 Power connections

See section 1.3 for information on accessing the connections. Connections are made using lugs connected to two threaded studs per phase (diameter 10 mm). The cables are tied to the earth bar.

N L1 L2 L3 N L1 L2 L3 N L1 L2 L3

Upsilon STS 400 to 600 A Input: 3 phases + PEN Output: 3 phases + PE + Neutral

MGE UPS Systems 30A — 2.2 Power connections diagram (page 14)
Fig. 14 · 2.2 Power connections

See section 1.3 for information on accessing the connections. Connections are made using lugs connected to two threaded studs per phase (diameter 10 mm). The cables are tied to the earth bar.

N L1 L2 L3 N L1 L2 L3 N L1 L2 L3

Page 15 of the MGE UPS Systems 30A user manual — 2.2 Power connections
Page 15 · click to enlarge
Page 15

Upsilon STS 400 to 600 A Input: 3 phases + PEN Output: 3 phases + PE

MGE UPS Systems 30A — 2.2 Power connections diagram (page 15)
Fig. 15 · 2.2 Power connections

See section 1.3 for information on accessing the connections. Connections are made using lugs connected to two threaded studs per phase (diameter 10 mm). The cables are tied to the earth bar.

N L1 L2 L3 N L1 L2 L3 N L1 L2 L3

Upsilon STS 400 to 600 A Input: 3 phases + PE + Neutral Output: 3 phases + PE + Neutral

MGE UPS Systems 30A — 2.2 Power connections diagram (page 15)
Fig. 16 · 2.2 Power connections

See section 1.3 for information on accessing the connections. Connections are made using lugs connected to two threaded studs per phase (diameter 10 mm). The cables are tied to the earth bar.

N L1 L2 L3 N L1 L2 L3 N L1 L2 L3

Upsilon STS 400 to 600 A Input: 3 phases + PE Output: 3 phases + PE

MGE UPS Systems 30A — 2.2 Power connections diagram (page 15)
Fig. 17 · 2.2 Power connections

See section 1.3 for information on accessing the connections. Connections are made using lugs connected to two threaded studs per phase (diameter 10 mm). The cables are tied to the earth bar.

N L1 L2 L3 N L1 L2 L3 N L1 L2 L3

Page 16 of the MGE UPS Systems 30A user manual — 2.3 Connection of the emergency power off terminal block
Page 16 · click to enlarge
Page 16

Cable running for cables entering through the top of the Upsilon STS 30 to 250 A cabinet

MGE UPS Systems 30A — 2.3 Connection of the emergency power off terminal block diagram (page 16)
Fig. 18 · 2.3 Connection of the emergency power off terminal b…

Cable gland plate that must be drilled to cable size

2.3 Connection of the emergency power off terminal block

MGE UPS Systems 30A — 2.3 Connection of the emergency power off terminal block diagram (page 16)
Fig. 19 · 2.3 Connection of the emergency power off terminal b…
1. Remove the jumper from terminal block 16 . 2 - Connect the emergency power off NC contact to terminals 1 and 2. 3 - Tie the cable down as illustrated in section 2.4.
Page 17 of the MGE UPS Systems 30A user manual — 2.5 Connection of the JBUS communication card
Page 17 · click to enlarge
Page 17

2.4 Connection of the communication cards

MGE UPS Systems 30A — 2.4 Connection of the communication cards diagram (page 17)
Fig. 20 · 2.4 Connection of the communication cards

Tie the cables to the cable way on the door.

Do not run the control wires with the power cables.

Two slots are available in the card cage 5 for additional cards.

2.5 Connection of the JBUS communication card

1 2 3 4 5

6 7 8 9

MGE UPS Systems 30A — 2.5 Connection of the JBUS communication card diagram (page 17)
Fig. 21 · 2.5 Connection of the JBUS communication card
RS232Pin 2: Rxd (or Txd) Pin 3: Txd (or Rxd) Pin 5: Earth
RS485Pin 4: RPin 5: TPin 8: R+ Pin 9: T+

For information on using the communication card, see the JBUS communication card manual.

Only one communication port (the RS232 OR the RS485) may be used at a time.

Page 18 of the MGE UPS Systems 30A user manual — 2.6 Connection of the relay communication card
Page 18 · click to enlarge
Page 18

2.6 Connection of the relay communication card

Before proceeding, disconnect all power sources connected to the card. Do not mix very low safety voltage (VLSV) and non-VLSV circuits on the card outputs.

MGE UPS Systems 30A — 2.6 Connection of the relay communication card diagram (page 18)
Fig. 22 · 2.6 Connection of the relay communication card
1. Remove the screws 41 and the protection cover 43 . 2 - Run the communication cables through the openings 44 . 3 - Connect the cables to the input terminal block 46 and the output terminal block 45 .
4. Put the cover back in place and secure it with the screws 41 . 5 - Secure the cables using the screws 47 . 6 - Note the position of the power sources on the labels. 7 - Insert the card in its slot. 8 - Secure the card using the two screws 42 .
MGE UPS Systems 30A — 2.6 Connection of the relay communication card diagram (page 18)
Fig. 23 · 2.6 Connection of the relay communication card

Characteristics of the output contacts: Permissible voltage: 250 V AC, 30 V DC Permissible current: 2 A Cable: 4 x 0.93 mm2, Ø 6.6 mm ± 0.3 mm.

Characteristics of the input contacts: Switched voltage: 5 V DC Current drawn: 10 mA Cable: 4 x 0.34 mm2, Ø 5 mm ± 0.5 mm.

General alarm (fault on one of the sources or on the STS)

Command to disable transfer (transfer to alternate source inhibited)

Load-supplied status condition (presence or absence of power to the load)

Memorised faults reset command

Page 19 of the MGE UPS Systems 30A user manual — 3.2 Shutdown
Page 19 · click to enlarge
Page 19

3. Operation

Make sure that the voltages and frequencies of the two sources S1 and S2 are identical.

Make sure that the voltages of the two sources S1 and S2 are the same as the rated voltage (400 V) of Upsilon STS, otherwise see section 3.5 (Customization).

3.1 Start-up

MGE UPS Systems 30A — 3.1 Start-up diagram (page 19)
Fig. 24 · 3.1 Start-up
1. Check that the two sources are energised (voltage present).
2. Set circuit breakers Q5 2 and Q6 3 to the ON position (position 1).
3. Turn switch Q1BP 6 to the ON position (position 1). LEDs 37 and 38 go on.

The load is supplied by Source 1 via the bypass.

4. Set switches Q1 1 and Q3 7 to the ON position (position 1). LEDs 29 , 31 , and 36 go on.
5. Turn switch Q1BP 6 back to the OFF position (position 0). LED 37 goes off.
6. Set switch Q2 4 to the ON position (position 1). LEDs 30 and 32 go on.

The load is supplied by Source 1.

If LED 33 is red or off, if LEDs

31 and/or 32 are orange or red: see section "Maintenance".

3.2 Shutdown

MGE UPS Systems 30A — 3.2 Shutdown diagram (page 19)
Fig. 25 · 3.2 Shutdown
1. Set switches Q1 1 , Q2 4 and Q3 7 to the OFF position (position 0). 2 - Set circuit breakers Q5 2 and Q6 3 to the OFF position (position 0). All LEDs should go off.

The load is not supplied with power.

Page 20 of the MGE UPS Systems 30A user manual — 3. Operation
Page 20 · click to enlarge
Page 20

3. Operation

3.3 Normal mode. Operation on preferred source S1 Operation on the preferred source

MGE UPS Systems 30A — 3. Operation diagram (page 20)
Fig. 26 · 3. Operation

During normal operation on the preferred source S1, LEDs 24 , 29 , 30 , 31 , 32 ,

33 , 36 and 38 are on in green.

If LED 38 is orange, there is an overload. If LED 38 is red, the load is no more supplied.

The load is automatically transferred to the source offering the highest level of power quality.

For example, if the preferred source S1 goes outside tolerances, LED 31 goes orange or red. The buzzer beeps. Upsilon STS automatically transfers the load to the alternate source S2. LEDs 24 ,

29 , 30 , 32 , 34 , 36 and 38 are on.

Upsilon STS transfers the load back to the preferred source S1 as soon as it returns to within tolerances.

To stop the buzzer, press the

function button marked .

1. Press the manual transfer button 25 :
2. Confirm the order by pressing the grey function button 23 marked on the screen. LEDs 24 and 27 flash. After the transfer, the green LED 27 goes on.

The load is supplied by alternate Source 2.

Transfer is authorised only if the two sources are within tolerances (voltage, frequency) and their phase displacement is within the set limits. If these two conditions are not met, the transfer order is stored in memory and executed when the voltages cross zero. If transfer does not take place within thirty minutes, the order is cancelled.

Page 21 of the MGE UPS Systems 30A user manual — Q1 Q2
Page 21 · click to enlarge
Page 21

3. Operation

Manual transfer to an out-of-phase alternate source

S1 S2

When the two sources are not in phase, it is possible to force manual transfer using the commands on the screen, after entering a password. 1 - Enter the password (see section 3.5, Customization). 2 - Follow the instructions provided on the screen.

Q1 Q2

Q1BP

Q2BP Q3

Page 22 of the MGE UPS Systems 30A user manual — MANUAL TRANSFERT
Page 22 · click to enlarge
Page 22

3. Operation

3.4 Display screens

DOWNGRADED MODE

MAIN MENU

I1 17 A I2 9 A I3 2 A

1 KW 6 KVA

PF 0.3

UPS 1

UPS 2

0 1 0 1 1 0 1 0 0 1 0 1

E S C VOLT

V1 244 V V2 230 V V3 232 V 50.0 Hz

V1 232 V V2 229 V V3 230 V 50.0 Hz

MANUAL TRANSFERT

ALARMS

STATUS

CURRENT MEASUREMENTS

EVENT LOG

VOLTAGE MEASUREMENTS

STATISTICS

FREQUENCY MEASUREMENTS

POWER MEASUREMENTS

LOAD MEASUREMENTS

SETUP

LANGUAGE

ADJUST DATE AND TIME

CONTRAST

BUZZER VOLUME

MAINTENANCE

DISPLAY TEST

SOURCE NAMES

NEW PASSWORD

UNIT ON BYPASS

PERSONALIZATION

DRY CONTACT SETTINGS

Show 17 more labels / short text on this page
Initial screen · Main screen · Transfer · Alarms · preferred · Status · Measurements · synchro · Setup · Maintenance · = 64° · Transfer Alarms · Transfer without break · Transfer with break · Measurements Status · Setup · Maintenance
Page 23 of the MGE UPS Systems 30A user manual — 380 / 400 / 415 V
Page 23 · click to enlarge
Page 23

3. Operation

3.5 Upsilon STS customization

1. Press the menu button 26 .
2. Select "Setup", then "Customization" using the function buttons 23 marked or .
3. Confirm the order by pressing the function button 23 marked .
4. Enter the password.

The password Ø Ø Ø is set in the factory.

Select "Setup", then "Password" to personalise the password.

The monitoring parameters must be identical for the two sources. These parameters depend on the tolerances of the connected loads.

PERSONALIZATION

Nominal voltage Overvoltage threshold Undervoltage threshold Nominal frequency Overfrequency threshold Underfrequency threshold Phase sync tolerance Retransfer

400 V 10% 10% 50 Hz 5% 5% 15° YES

E S C

Return to preferred source after transfer

380 / 400 / 415 V

Un +5% to Un +20% in 1% steps

Un -5% to Un -20% in 1% steps

50 / 60 Hz

+1% to +10% -1% to -10% in 0.5% steps

Phase error tolerance between the two sources

±1° to ±45° in 1° steps

Show 15 more labels / short text on this page
Current settings · Factory setting · Customization · Automatic · Manual / Automatic · Nominal source voltage · Overvoltage threshold · Un +10% · Undervoltage threshold · Un -10% · Nominal source frequency · 50 Hz · ±5% · Frequency tolerances · ±15°
Page 24 of the MGE UPS Systems 30A user manual — 3. Operation
Page 24 · click to enlarge
Page 24

3. Operation

3.6 Customization of the relay communication card

Inputs Signals available on each contact

- Memorised faults reset command.

1.A - Memorised faults reset command.

- Selection command for source S1.

- Selection command for source S2.

- Selection command for the authorised automatic retransfer mode.

- Command to disable transfer. 1.B

- Selection command for the inhibited automatic retransfer mode.

- Command to authorise transfer.

- Command to disable transfer.

- EPO command (enables the opening command for switches Q1 and Q2).

Outputs Signals available on each contact

1.1 - Load-supplied status condition (presence or absence of power to the load).

- Load-supplied status condition (presence or absence of power to the load). - General alarm (fault on one of the sources or on the Upsilon STS). - Upsilon STS fault. - Source S1 status condition (within or outside tolerances). - Source S2 status condition (within or outside tolerances). - Phase-error condition between the two sources (within or outside tolerances). - Source S1 status condition (active or inactive). - Source S2 status condition (active or inactive). - Preferred-source status condition (S1 inactive and S2 active). - Automatic-transfer status condition (authorised or not). - Overload status condition.

- General alarm (fault on one of the sources or on the Upsilon STS).

- Upsilon STS fault.

- Overload status condition.

- Source S1 status condition (active or inactive).

- Source S2 status condition (active or inactive).

Factory setting · Factory setting

Page 25 of the MGE UPS Systems 30A user manual — Q1 Q5 Q6 Q2
Page 25 · click to enlarge
Page 25

4. Maintenance

4.1 Identification of anomalies

S1 31 or S2 32

Static-switch LED 33 or 34

LED 21

LED

LED 38

Internal STS fault.

Source outside tolerances, load still supplied.

Source outside tolerances, no voltage. The load cannot be supplied by this source.

Static-switch fault.

Overload.

Load not supplied.

The meaning of all these anomalies are detailed on the display: Select the alarm: the corresponding informations are displayed.

4.2 Transfer to the manual bypass

Q1 Q5 Q6 Q2

Transfer to the manual bypass for source S1:

1. Manually transfer the load to source S1.
2. Set switch Q2 4 to the OFF position (position 0).

Q1BP Q2BP Q3

3. Set switch Q1BP 6 to the ON position (position 1).

The load is supplied by source S1 via the bypass.

Q1 Q5 Q6 Q2

4. Set switches Q1 1 and Q3 7 to the OFF position (position 0).

Q1BP Q2BP Q3

The operation for source S2 is identical, using switches Q2 and Q2BP.

Interlocking of the bypass lines is ensured by use of a single key that must be inserted on the bypass switch to be operated.

Q1 Q5 Q6 Q2

Q1BP Q2BP Q3

Show 8 more labels / short text on this page
General-alarm · Buzzer · System output · Meaning · Beeps · Beeps · Beeps · Beeps
Page 26 of the MGE UPS Systems 30A user manual — 5. Environment
Page 26 · click to enlarge
Page 26

5. Environment

This product has been designed to respect the environment It does not contain CFCs or HCFCs. It is manufactured on a production site certified ISO 14001.

UPS recycling at the end of service life MGE UPS SYSTEMS undertakes to recycle, by certified companies and in compliance with all applicable regulations, all products recovered at the end of their service life (contact your MGE UPS SYSTEMS branch office).

Packing Packing materials must be recycled in compliance with all applicable regulations.

Web sitewww.mgeups.com
Page 27 of the MGE UPS Systems 30A user manual — Permissible-overload curve
Page 27 · click to enlarge
Page 27

6. Appendix

6.1 Technical data Output currents and voltage

Rated output current:

30 A

60 A 100 A 160 A 250 A 400 A 600 A

Input and output voltage:

◗ Rated operating voltage:

380 V / 400 V / 415 V 498 V (415 V +20%) 247 V (380 V -35%) 50 or 60 Hz (45 Hz minimum, 66 Hz maximum)

◗ Maximum voltage:

◗ Minimum voltage:

◗ Rated frequency:

Thermal characteristics

Heat losses (1):

◗ at rated power:

195 W 150 W

295 W 195 W

430 W 260 W

615 W 350 W

920 W 495 W

1420 W 735 W

2150 W 1070 W

◗ at 50% rated power:

Required ventilation:

350 m3/h

350 m3/h

350 m3/h

1600 m3/h

1600 m3/h

2300 m3/h

2300 m3/h

(1) These characteristics are calculated for a voltage of 400 V and a power factor of 0.8.

Noise level

Noise in dB (ISO 3746):

55 55 55 59

Cable sizes

Cross-sectional area in mm 250 50 50 120 120 240 240

Recommended protection devices upstream of Upsilon STS

Type of circuit breaker:

◗ TNS system:

C60L 32A

NS100H 4P 4D

NS160H

NS250H

NS400H

NS630H

4P 4D NS160H

4P 4D NS250H

4P 4D NS400H

4P 4D NS630H

◗ TNC system:

NS100H 3P

3P

3P

3P

3P

Trip unit:

STR22SE

STR22SE

STR22SE

STR23SE

STR23SE

≤1.05 In

≤1.05 In

≤1.05 In

≤1.05 In

Thermal setting:

1.05 In

Magnetic setting:

Permissible-overload curve

0.01 s 0.1 s 1 s 10 s 100 s 1000 s

◗ During an overload, transfer between sources is disabled.

◗ Overloads higher than 1.5 In are stored in memory. The alarm must be reset to return to normal operation.

Show 15 more labels / short text on this page
curve C · ≤1,05 In · 10xIn · ≤10xIn · ≤10xIn · ≤10xIn · ≤10xIn · ≤10xIn · 32 In · 16 In · 8 In · 4 In · 2 In · t(s) · In
Page 28 of the MGE UPS Systems 30A user manual — S1 S2
Page 28 · click to enlarge
Page 28

6. Appendix

6.2 Simplified diagrams Upsilon STS simplified diagram

Source 2 Source 1

S1 S2

Upsilon STS

Q1

Q2

Q3 Q2BP Q1BP

Simplified diagram of an installation

Alternate sources Preferred sources

Upsilon STS Upsilon STS Upsilon STS

Static-switch control/monitoring · To the load · To the load

Page 29 of the MGE UPS Systems 30A user manual — 6. Appendix
Page 29 · click to enlarge
Page 29

6. Appendix

6.3 Glossary

Alternate source Backup source that steps in if the preferred source fails.

JBUS communication card Internal card implementing the JBus protocol on a serial link to supply the user with system information.

Load Device(s) or system(s) connected the Upsilon STS output.

Manual bypass Q1BP, Q3 and Q2BP switches, accessible to the user, that may be used to directly supply the load from Source S1 or S2. The bypass enables servicing on the equipment without interrupting the supply of power to the load.

Normal mode Operating mode during which the load is supplied by the preferred source.

Preferred source Source selected as the normal source of power.

Relay communication card Internal card implementing contacts to supply the user with system information.

Static switch Electronic switch ensuring instantaneous switching.

Page 30 of the MGE UPS Systems 30A user manual — 4. Maintenance
Page 30 · click to enlarge
Page 30
Page 30 of the MGE UPS Systems 30A user manual — 4. Maintenance
Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the MGE UPS Systems 30A

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the MGE UPS Systems 30A

Be the first to ask — other owners or our team will answer.

Original document

MGE UPS Systems 30A manual PDF

30 pages·1.9 MB·Power Supply·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…