Thank you for selecting an MGE UPS SYSTEMS product to protect your electrical equipment.
The Pulsar EXtreme range has been designed with the utmost care. We recommend that you take the time to read this manual to take full advantage of the many features of your UPS.
MGE UPS SYSTEMS pays great attention to the environmental impact of its products. Measures that have made Pulsar EXtreme a reference in environmental protection include:
◗ Production in an ISO 14001 certified factory,
◗ Recycling of Pulsar EXtreme at the end of its service life.
To discover the entire range of MGE UPS SYSTEMS products and the options available for the Pulsar EXtreme range:
◗ We invite you to visit our Web site at www.mgeups.com (page: www.mgeups.com/products/pdt230/smallups/extreme/extrem10.htm),
◗ Or contact your MGE UPS SYSTEMS representative.

Information may be found primarily by consulting:
◗ The index.
Information, advice, help.
Visual indication.
Action.
Audio indication.
In the illustrations on the following pages, the symbols below are used:
LED off.
LED on.
LED flashing.
◗ The contents,





Pulsar EXtreme 3000


Socket for connection to AC-power source.
Outlets for direct connection to protected equipment.
Manual bypass switch.
Input terminal block with cable clamp.
Output terminal block with cable clamp.

Different types of sockets available on Fault tolerant and Hot swap
connection modules:



Slot for communications-card option.
Battery module connector.
Battery circuit breaker.
Rating plate.
Connector for connection modules.
RS232 communications port.



Battery extensions for Pulsar EXtreme:
Pulsar EXtreme offers a standard backup time of 9 minutes. To increase backup time, it is possible to connect Pulsar EXtreme EXB modules to the UPSs. Visit our Web site: www.mgeups.com/ products/pdt230/smallups/extreme/ guide.htm.

9 min 20 min 36 min 66 min
The Pulsar EXtreme EXB modules are available in "tower" and in "rack" models. The Pulsar EXtreme EXB modules come with their connection cables.

CLA module (Long backup time charger) for backup times of 2 to 8 hours
Very long backup times, from 2 to 8 hours at full load, require a Pulsar EXtreme CLA module (2000VA or 3000VA). Visit our Web site: www.mgeups.com/products/pdt230/smallups/extreme/cla/cla2.htm.



Ambient temp. > 40°C
Hold down to display percent load.
Lamp test or buzzer OFF.
Operation on manual bypass.
Operation on automatic bypass.
Operation in ON-LINE mode.
Operation on battery power.
ON/OFF.


RS 232 communications cable.
CD ROM with "Solution Pac" and "UPS Driver" softwares.
Quick Start documentation.
Installation and user manual.
Electrical power cord (except INSTALL version and version with IEC outlets).


RS 232 communications cable.
CD ROM with "Solution Pac" and "UPS Driver" softwares.
Quick Start documentation.
Installation and user manual.
Electrical power cord (except INSTALL version and version with IEC outlets).
Telescopic rails for mounting in 19" bay with mounting hardware.

Rack mounting diagram with rails.

The rails and the necessary mounting hardware are supplied with the UPS in the package.


The UPS can now communicate with all MGE UPS SYSTEMS supervision, set-up or safety software.

Pin-out diagram for the RS 232 communications port on the UPS.

Slot for the communications-card option.
It is not necessary to shut down the UPS to install the communications card:


Before carrying out any connections, check that the battery circuit breaker is OFF and that the electrical power cord to the AC-power source is disconnected.
Connection of equipment:

Connect the protected equipment directly to the outlets 2 .


Connection to the AC-power source:

Before carrying out any connections, check that the battery circuit breaker is OFF and that the electrical power cord to the AC-power source is disconnected.

Connection of equipment to outlets Plug your equipment into the outlets .
Connection of equipment to a terminal block: This type of connection must be carried out by qualified electrical personnel.

Always connect the earthing wire first.
The overall cable diameter and the cross-sectional area of the three wires depends on the UPS rating.

From 9 to 12 mm From 9 to 12 mm
1 to 4 mm2 1,5 to 4 mm2
Recommended upstream circuit breaker ◗ Nominal rating (47 to 63Hz, 230V)

Connection to the AC-power source: 1. Connect the electrical power cord to the socket for connection to AC-power source. 2. Connect the other end of the electrical power cord to an AC-power outlet.

This type of connection must be carried out by qualified electrical personnel.
Before carrying out any connections, check that the battery circuit breaker is OFF and that the upstream protection devices (AC distribution system) are open (OFF).
The overall cable diameter and the cross-sectional area of the three wires depends on the UPS rating.


From 9 to 12 mm From 9 to 12 mm
1 to 4 mm2 1,5 to 4 mm2
Recommended upstream circuit breaker ◗ Nominal rating (47 to 63Hz, 230V)
Power and equipment connections: 1. Remove the terminal-block cover . 2. Insert the cable supplying the equipment and the power cable through the cable clamps . 3. Connect the three wires of the equipment cable to the output terminal block .
Always connect the earthing wire first.

This is the normal operating mode for the UPS.
Two possible cases:
LED is ON: AC input power is available. Power is drawn from the distribution system and supplied to the protected equipment via the UPS.
LED is ON: AC input power is not available. Power is drawn from the battery and supplied to the protected equipment.
bypass · bypass

Prior to initial start-up, check the UPS voltage settings. The frequency of the output voltage (50 or 60 Hz) is automatically set to that of the input source.

1. Close the upstream device (ON position) controlling the supply of AC power to the UPS. 2. Set the battery circuit breaker(s) to ON. The buzzer beeps three times. If the supply frequency is different than the default value set on the UPS, the new value is set and the buzzer beeps 4 times. 3. Press the ON / OFF button . All the equipment connected to the UPS is now energised, however it takes another 30 seconds before the UPS is fully operational.
After this time, the equipment connected to the UPS is protected.
◗ If LED or do not go ON or if one of LED , , or flash, there is a fault (see section 4.1).
14 15 16 17
◗ In order to detect any wiring errors, it is essential that the AC-power source be present at the first switch-on. Subsequently, the device may be switched-on without the presence of the AC-power source.
Overload.
UPS fault.
Battery fault.
Excessive ambient temperature.

3.4 Failure of AC input power and operation on battery power AC input power is not available, the battery steps in to supply the protected equipment.

When AC-power source goes outside tolerances or fails completely, LED goes ON and the buzzer beeps three times.
The low-battery shutdown warning threshold can be set by the user, with the "UPS Driver" software (default setting equal to 20% of full backup time). LED flashes when the setted level is reached. The buzzer beeps every three seconds when less than 10% of backup time remains.
There is very little remaining battery backup time. Close all applications because UPS automatic shutdown is imminent.
The buzzer sounds continuously. Press button to turn the buzzer OFF.
The equipment is no longer supplied with power.
This operating mode may be personalized using the "UPS Driver" software (see section 3.5). It saves battery power when no equipment is connected to the UPS. Shutdown occurs after 5 minutes. The UPS automatically restarts when the AC-power source returns to within tolerances.
If, in spite of the return of AC input power, the UPS does not restart, check that the automatic-restart function (activated by return of AC input power) has not been disabled (see section 3.5).

Personalization parameters can be set and modified using the "UPS Driver" software installed on a computer that is connected to the UPS (see section 2.3 Connection to the RS 232 communications port).
Check that the RS 232 cable is correctly connected and that the battery circuit breaker is closed.
"UPS Driver" installation:
Once "UPS Driver" has been installed, UPS parameters can be modified in a window containing a number of tabs, each presenting a set of parameters.
Cold start (battery power)
UPS ON / OFF via software

Once a week Once a month
"Low-battery shutdown warning" threshold
CLA (2, 4 or 8 hours)
Rated AC-power source voltage (see figure 1)
Rated AC-power source frequency
Tolerance for AC-power source frequency
± 1% to ± 10% , in 1% steps
0 to 100%, in 10% steps
UPS restart after a short-circuit
Enabled (click to add check)
Authorized voltage range for transfer to bypass
187 V to 265 V (for 230 V rated voltage)
187 V to 265 V, in 1V steps
if fault or overload
Authorized frequency range for transfer to bypass
± 1% to ± 10%, in 1% steps
if fault or overload
Transfer to bypass if overload
Disabled (click to remove check)
Transfer to bypass following a fault, whatever
Enabled (click to add check)
the conditions on the AC-power source
The value selected for the rated UPS voltage impacts on the power available at UPS output (see the diagram below).
Available power as a percentage of the rated power

The connected equipment is no longer supplied with power, but the battery is maintened charged if AC-power source is present.
If the AC source fails, even though the connected equipment is no longer supplied, the UPS operates on battery power and therefore reduces the available backup time.
The connected equipment is no longer supplied with power.
The UPS is now de-energised and the batteries are no longer recharged.

If one or more LEDs , , or flash, there is a operating anomaly or an alarm.
14 15 16 17
If a LED flashes, the bargraph data is no longer displayed.
Troubleshooting not requiring MGE after-sales support
LEDs , , , flash and the buzzer beeps.
17 14 15 16
The UPS has detected a problem concerning the wiring of the connection module input.
Shut down the UPS and check that the input power cable is properly connected to the input terminal block and the load to the output terminal block (see p. 18). After correcting any wiring errors, restart the UPS as indicated on page 20. If the problem persists, call MGE after-sales support.
LED flashes and the buzzer beeps.
UPS overload. Overload is too long or too high. The UPS cuts the supply of power to the connected equipment and the buzzer beeps continuously.
Check the power drawn by the equipment and disconnect any non-priority devices.
LED flashes.
The ambient temperature is higher than 35° C.
Install the UPS in a room where the ambient temperature is not greater than 35° C.
The UPS is not designed to operate more than eight hours under these conditions.
LED is ON.
The UPS is in maintenance mode (manual bypass)
See point 3 to 6 of in the "Hot-swap and Install connection modules" part of section 4.2.
Indication · Signification · Correction

Troubleshooting requiring MGE after-sales support
LED flashes and the buzzer beeps.
UPS electronics have detected a UPS fault. Depending on the UPS personalization parameters (see section 3.5), there are two possibilities:
For UPSs equipped with Hot swap or Install connection modules, follow the UPS replacement procedure (see section 4.2).
◗ the equipment connected to the UPS continues to be supplied, but directly from the AC-power source (via the automatic bypass for a maximum of 8 hours (LED ON);
Call the after-sales support department.
◗ the connected equipment is no longer supplied.
The equipment connected to the UPS is no longer protected.
LED flashes.
A battery fault was detected during the battery test.
Call the after-sales support department because the batteries need replacing.
Indication · Signification · Correction

Before carrying out this operation, the supply of power to the connected equipment must be cut. The equipment will therefore no longer be powered.

Disconnection: 1. Shut down the UPS by pressing button (return to the OFF position). 2. Open the battery circuit breaker(s) . 3. Open the upstream device (OFF position) controlling the supply of AC power to the UPS. 4. Remove the two fixing screws and the connection module from the UPS.
Reconnection: 1. Insert the connection module in the connector and secure using the two screws . 2. Close the upstream device (ON position) controlling the supply of AC power to the UPS. 3. Close the battery circuit breaker(s) .

Check that UPS personalization settings still correspond to the equipment to be supplied (see section 3.5).
The connected equipment is again protected by the UPS.

Before turning the switch,
Disconnection: 1. Turn the manual bypass switch , located behind the UPS (see section 2.5), from the NORMAL to the intermediate position. 2. Check that LED is ON before continuing to the BYPASS position.
If LED is not ON, do not switch to the BYPASS position and call the after-sales support department.
The connected equipment is supplied by the AC- power source, via the manual bypass.
Before turning the switch,
The UPS can be replaced. The connected equipment is supplied by the AC-power source.
see the manual · bypass · see the manual

Reconnection: 1. Insert the connection module in the connector and secure using the two screws . 2. Switch the battery circuit breaker(s) to the ON position and check that LED is ON.

Check that UPS personalization settings still correspond to the equipment to be supplied (see section 3.5).
If LED is not ON, do not switch to the intermediate position and call the after-sales support department.
The connected equipment is again protected by the UPS.

This product has been designed to respect the environment:
It does not contain CFCs or HCFCs. It was manufactured in a factory certified ISO 14001.
UPS recycling at the end of service life:
MGE UPS SYSTEMS undertakes to recycle, by certified companies and in compliance with all applicable regulations, all UPS products recovered at the end of their service life (contact your branch office).
Packing:
UPS packing materials must be recycled in compliance with all applicable regulations.
This product contains lead-acid batteries. Lead is a dangerous substance for the environment if it is not correctly recycled by specialized companies.

Authorized voltage Upper and lower voltage thresholds within which the UPS can operate range for transfer to on the automatic bypass in the event of a UPS fault or overload. bypass if fault or overload
Automatic bypass Automatic switch controlled by the UPS, used to connect the equipment directly to the AC-power source.
Automatic start following When AC input power returns following shutdown at the end of the battery return of AC input power backup time, UPS automatic start can be enabled or disabled.
Backup time Time that the connected equipment can operate on battery power.
Bargraph Device on the front panel indicating the percent remaining backup time or the percent load.
Battery test Internal UPS test on battery status.
CLA (Long backup- Module incorporating a charger for long backup times. The charger is powerful time charger) enough to charge battery extension modules offering very long backup times.
Cold start See "Start on battery power".
Connection module Unit grouping the receptacles for connection to the AC-power source and the equipment.
Dialog box A window in a computer program displayed for selection by the user of various options and parameter settings.
Double conversion The power supplied to the connected equipment is completely regenerated by continuous double conversion, i.e. the AC power from the AC-power source is rectified (AC - DC), then converted back (DC - AC) to AC power.
Equipment Devices or systems connected to the UPS output.
Fault tolerant Connection module (without manual bypass) offering receptacles for connection to the AC-power source and the equipment.
Forced shutdown Allows a "clean" of computer operating systems depending on the low battery threshold setting. If the input source is restored during the time period between the shutdown order and actual system shutdown, it causes a voluntary interruption of the supply of power to the connected equipment (lasting 10 seconds) after system shutdown.

Out of tolerance The AC input source is either absent or its voltage or frequency is outside the set limits.
Hot swap Connection module (with manual bypass) offering a socket for connection to the AC-power source and outlets or a terminal block for connection to the equipment.
Install Connection module (with manual bypass) offering terminal blocks for connection to the AC-power source and the equipment.
Manual bypass Rotary switch controlled by the user, used to connect the equipment directly to the AC-power source. Transfer of the load to the manual bypass enables UPS maintenance or replacement, without interrupting the supply of power to the connected equipment.
ON-LINE mode The normal UPS operating mode, by which the AC-power source supplies the UPS, which in turn, following double conversion of the AC power, supplies the connected equipment.
Percent load Ratio between the power drawn by the connected equipment and the total power that the UPS can supply.
Personalization A number of UPS functions can be modified using the "UPS Driver" software to better meet the user's needs.
Sleep mode This function shuts down the UPS after 5 minutes when it operates on battery power and no load is detected on the UPS output. The UPS restarts automatically as soon as the AC input source is restored.
Start on battery power This function makes it possible to energize the connected equipment even when AC input power is not available (operation exclusively on battery power).
Tolerance for AC-power The range of frequency supplied by the AC-power source within which source frequency the UPS can operate in ON-LINE mode (double conversion).
UPS Uninterruptible Power Supply.
UPS ON / OFF It is possible to enable or disable use of UPS ON / OFF controls via software by the computer-system protection software.

Failure 21 Frequency tolerance 23 Rated frequency 23 Rated voltage 23 Return 21
Lamp test 11
ON LINE mode 11, 19
B Bargraph 20 Battery
O Overload 11, 23, 25
Battery test 23 End of backup time 21 Fault 11, 20 Low-battery shutdown warning 21 Recycling 30 Transfer to battery power 21 Buzzer 3, 11, 21 By-pass
P Personalization 22
Battery 23 ON / OFF conditions 22 Output 23
R Rack 6, 14
Automatic bypass 19, 26 Manual bypass 11, 27
C Communication 15 Connection
Forced shutdown 22 UPS ON / OFF via software 22 UPS shutdown 11, 24 Sleep mode 21-22 Software
Communications card 15 Connection modules 17-18 RS 232 communications port 15
UPS Driver 12-13, 22 Start-up
F Fault (UPS)
Automatic start 22
Load 11 Transfer to automatic bypass 26 Fault tolerant 7, 16, 27
Excessive ambient temp 11, 20, 25
H Hot swap 7, 17, 28-29
U UPS Driver 12-13, 22
I Install 7, 18, 28-29