Pulsar EX treme 2000/3000 VA

Installation and user manual

D

E

R

P R O

W E

R

O

P

L E

B

P T

U

R

T E R

N

N

U

E

H

T

Page 2 of the MGE UPS Systems 2000 user manual — Introduction
Page 2 · click to enlarge
Page 2

Introduction

Thank you for selecting an MGE UPS SYSTEMS product to protect your electrical equipment.

The Pulsar EXtreme range has been designed with the utmost care. We recommend that you take the time to read this manual to take full advantage of the many features of your UPS.

MGE UPS SYSTEMS pays great attention to the environmental impact of its products. Measures that have made Pulsar EXtreme a reference in environmental protection include:

◗ Production in an ISO 14001 certified factory,

◗ Recycling of Pulsar EXtreme at the end of its service life.

To discover the entire range of MGE UPS SYSTEMS products and the options available for the Pulsar EXtreme range:

◗ We invite you to visit our Web site at www.mgeups.com (page: www.mgeups.com/products/pdt230/smallups/extreme/extrem10.htm),

◗ Or contact your MGE UPS SYSTEMS representative.

Page 3 of the MGE UPS Systems 2000 user manual — Pictograms
Page 3 · click to enlarge
Page 3

Foreword

Using this document

Information may be found primarily by consulting:

◗ The index.

Pictograms

Information, advice, help.

Visual indication.

Action.

Audio indication.

In the illustrations on the following pages, the symbols below are used:

LED off.

LED on.

LED flashing.

◗ The contents,

Page 4 of the MGE UPS Systems 2000 user manual — Foreword
Page 4 · click to enlarge
Page 4
Page 4 of the MGE UPS Systems 2000 user manual — Foreword
Page 5 of the MGE UPS Systems 2000 user manual — Foreword
Page 5 · click to enlarge
Page 5
Page 5 of the MGE UPS Systems 2000 user manual — Foreword
Page 6 of the MGE UPS Systems 2000 user manual — Rack model
Page 6 · click to enlarge
Page 6

1. Presentation

1.1 Pulsar EX treme range

Tower model

Dimensions in mm (H x W x D) EXtreme 2000 - 3000443 x 173 x 465 Weight in kg Pulsar EXtreme 200029

Pulsar EXtreme 3000

Rack model

Dimensions in mm (H x W x D) EXtreme 2000 - 3000177 (4U) x 483 x 462 Weight in kg Pulsar EXtreme 200031 Pulsar EXtreme 300038
Page 7 of the MGE UPS Systems 2000 user manual — Install
Page 7 · click to enlarge
Page 7

1. Presentation

1.2 Connection modules

Fault tolerant

MGE UPS Systems 2000 — Fault tolerant diagram (page 7)
Fig. 2 · Fault tolerant

Socket for connection to AC-power source.

Outlets for direct connection to protected equipment.

Manual bypass switch.

Input terminal block with cable clamp.

Output terminal block with cable clamp.

Hot swap

MGE UPS Systems 2000 — Hot swap diagram (page 7)
Fig. 3 · Hot swap

Different types of sockets available on Fault tolerant and Hot swap

connection modules:

AC input cordOutlet socketsPower cords to equipment USEDIN plug, 2.5m cable, IEC320C20 cable4 USE outlets (16A) DINDIN plug, 2.5m cable, IEC320C20 cable4 DIN outlets (16A) BSBS plug, 2.5m cable, IEC320C20 cable4 BS outlets (13A) IECIEC320C20 plug (not supplied)4 IEC320C13 outlets (10A) protected by 10A circuit breaker and 1 IEC320C20 outlet (16A)2 x IEC320C13 plug, 2.5m cable, IEC320C13 plug NEMANEMA plug, 2.5m cable, IEC320C20 cable4 NEMA outlets (15A / 250V) SWITZERLANDSwiss plug, 2.5m cable, IEC320C20 cable4 IEC320C13 outlets (10A) protected by 10A circuit breaker and 1 IEC320C20 outlet (16A)2 x IEC320C13 plug, 2.5m cable, IEC320C13 plug AUSTRALIAAUSTRALIAN plug, 2.5m cable, IEC320C20 cable4 AUSTRALIAN outlets (16A)
MGE UPS Systems 2000 — Hot swap diagram (page 7)
Fig. 4 · Hot swap

Install

MGE UPS Systems 2000 — Install diagram (page 7)
Fig. 5 · Install
Page 8 of the MGE UPS Systems 2000 user manual — 1.3 Back
Page 8 · click to enlarge
Page 8

1. Presentation

1.3 Back

Slot for communications-card option.

Battery module connector.

Battery circuit breaker.

Rating plate.

Connector for connection modules.

RS232 communications port.

Page 9 of the MGE UPS Systems 2000 user manual — Battery extensions for UPS backup times of 66 minutes
Page 9 · click to enlarge
Page 9

1. Presentation

1.4 Options

Transformer for galvanic isolation or earthing arrangement change

MGE UPS Systems 2000 — Transformer for galvanic isolation or earthing arrangement change diagram (page 9)
Fig. 6 · Transformer for galvanic isolation or earthing arran…
Pulsar EXtreme Transformer Nominal power3 kVA Nominal current16 A Input voltage230V (+15%, -20%) Voltage drop< 3% Frequency50/60 Hz (+/-10%) Isolation (EN 61558-1-2-4)3.75 kV / 5 M ohms Operating temperatureFrom 0° to +40°C Max. operating rel. humidity95% Derating / altitudePn-10% > 1000 m Natural ventilationIP20 ANAN Dimensions HxWxD (tower)443 x 173 x 465 mm Dimensions HxWxD (rack 4U)177 x 483 x 462 mm Weight (tower)24 kg Weight (rack)28 kg
MGE UPS Systems 2000 — Transformer for galvanic isolation or earthing arrangement change diagram (page 9)
Fig. 7 · Transformer for galvanic isolation or earthing arran…

Battery extensions for UPS backup times of 66 minutes

Battery extensions for Pulsar EXtreme:

Pulsar EXtreme offers a standard backup time of 9 minutes. To increase backup time, it is possible to connect Pulsar EXtreme EXB modules to the UPSs. Visit our Web site: www.mgeups.com/ products/pdt230/smallups/extreme/ guide.htm.

MGE UPS Systems 2000 — Battery extensions for UPS backup times of 66 minutes diagram (page 9)
Fig. 8 · Battery extensions for UPS backup times of 66 minute…

9 min 20 min 36 min 66 min

The Pulsar EXtreme EXB modules are available in "tower" and in "rack" models. The Pulsar EXtreme EXB modules come with their connection cables.

Page 10 of the MGE UPS Systems 2000 user manual — 1. Presentation
Page 10 · click to enlarge
Page 10

1. Presentation

CLA module (Long backup time charger) for backup times of 2 to 8 hours

Very long backup times, from 2 to 8 hours at full load, require a Pulsar EXtreme CLA module (2000VA or 3000VA). Visit our Web site: www.mgeups.com/products/pdt230/smallups/extreme/cla/cla2.htm.

MGE UPS Systems 2000 — 1. Presentation diagram (page 10)
Fig. 9 · 1. Presentation
Page 11 of the MGE UPS Systems 2000 user manual — 1.5 Control panel
Page 11 · click to enlarge
Page 11

1. Presentation

1.5 Control panel

MGE UPS Systems 2000 — 1.5 Control panel diagram (page 11)
Fig. 10 · 1.5 Control panel

Ambient temp. > 40°C

Hold down to display percent load.

Lamp test or buzzer OFF.

Operation on manual bypass.

Operation on automatic bypass.

Operation in ON-LINE mode.

Operation on battery power.

ON/OFF.

Show 15 more labels / short text on this page
Alarms · % battery · % load · remaining · UPS overload · 100% · 100% · Electronics fault · 80% · 80% · Battery fault · 50% · 50% · 20% · 20%
Page 12 of the MGE UPS Systems 2000 user manual — Tower model
Page 12 · click to enlarge
Page 12

2. Installation

2.1 Unpacking and checks

Tower model

MGE UPS Systems 2000 — Tower model diagram (page 12)
Fig. 11 · Tower model

RS 232 communications cable.

CD ROM with "Solution Pac" and "UPS Driver" softwares.

Quick Start documentation.

Installation and user manual.

Electrical power cord (except INSTALL version and version with IEC outlets).

Page 13 of the MGE UPS Systems 2000 user manual — Rack model
Page 13 · click to enlarge
Page 13

2. Installation

Rack model

MGE UPS Systems 2000 — Rack model diagram (page 13)
Fig. 12 · Rack model

RS 232 communications cable.

CD ROM with "Solution Pac" and "UPS Driver" softwares.

Quick Start documentation.

Installation and user manual.

Electrical power cord (except INSTALL version and version with IEC outlets).

Telescopic rails for mounting in 19" bay with mounting hardware.

Page 14 of the MGE UPS Systems 2000 user manual — 2.2 Installation of the rack version
Page 14 · click to enlarge
Page 14

2. Installation

2.2 Installation of the rack version

Rack mounting diagram with rails.

MGE UPS Systems 2000 — 2.2 Installation of the rack version diagram (page 14)
Fig. 13 · 2.2 Installation of the rack version

The rails and the necessary mounting hardware are supplied with the UPS in the package.

Page 15 of the MGE UPS Systems 2000 user manual — 2.4 Installation of the communications-card option
Page 15 · click to enlarge
Page 15

2. Installation

2.3 Connection to the RS 232 communications port (optional)

MGE UPS Systems 2000 — 2.3 Connection to the RS 232 communications port (optional) diagram (page 15)
Fig. 14 · 2.3 Connection to the RS 232 communications port (op…
1. Connect the RS 232 communications cable to the serial port on the computer.
2. Connect the RS 232 communications cable to the RS 232 communications port on the UPS .

The UPS can now communicate with all MGE UPS SYSTEMS supervision, set-up or safety software.

MGE UPS Systems 2000 — 2.3 Connection to the RS 232 communications port (optional) diagram (page 15)
Fig. 15 · 2.3 Connection to the RS 232 communications port (op…

Pin-out diagram for the RS 232 communications port on the UPS.

2.4 Installation of the communications-card option

MGE UPS Systems 2000 — 2.4 Installation of the communications-card option diagram (page 15)
Fig. 16 · 2.4 Installation of the communications-card option

Slot for the communications-card option.

It is not necessary to shut down the UPS to install the communications card:

1. Remove the slot cover.
2. Insert the card in the slot.
3. Secure the card with the two screws.
Page 16 of the MGE UPS Systems 2000 user manual — Fault tolerant
Page 16 · click to enlarge
Page 16

2. Installation

2.5 Securing and connecting the connection modules

Securing the connection modules

MGE UPS Systems 2000 — Securing the connection modules diagram (page 16)
Fig. 17 · Securing the connection modules
1. Insert the connection module in the connector .
2. Secure the connection module to the UPS using the two screws .

Fault tolerant

Before carrying out any connections, check that the battery circuit breaker is OFF and that the electrical power cord to the AC-power source is disconnected.

Connection of equipment:

MGE UPS Systems 2000 — Fault tolerant diagram (page 16)
Fig. 18 · Fault tolerant

Connect the protected equipment directly to the outlets 2 .

MGE UPS Systems 2000 — Fault tolerant diagram (page 16)
Fig. 19 · Fault tolerant
MGE UPS Systems 2000 — Fault tolerant diagram (page 16)
Fig. 20 · Fault tolerant

Connection to the AC-power source:

1. Connect the electrical power cord to the socket for connection to AC-power source.
2. Connect the other end of the electrical power cord to an AC-power outlet.
Page 17 of the MGE UPS Systems 2000 user manual — Hot swap
Page 17 · click to enlarge
Page 17

2. Installation

Hot swap

Before carrying out any connections, check that the battery circuit breaker is OFF and that the electrical power cord to the AC-power source is disconnected.

MGE UPS Systems 2000 — Hot swap diagram (page 17)
Fig. 21 · Hot swap

Connection of equipment to outlets Plug your equipment into the outlets .

Connection of equipment to a terminal block: This type of connection must be carried out by qualified electrical personnel.

1. Remove the terminal-block cover . 2. Insert the cable supplying the equipment through the cable clamp . 3. Connect the three wires to the output terminal block .
MGE UPS Systems 2000 — Hot swap diagram (page 17)
Fig. 22 · Hot swap

Always connect the earthing wire first.

4. Remove the terminal-block cover. 5. Tighten the nut on the cable clamp .

The overall cable diameter and the cross-sectional area of the three wires depends on the UPS rating.

MGE UPS Systems 2000 — Hot swap diagram (page 17)
Fig. 23 · Hot swap

From 9 to 12 mm From 9 to 12 mm

1 to 4 mm2 1,5 to 4 mm2

Recommended upstream circuit breaker ◗ Nominal rating (47 to 63Hz, 230V)

MGE UPS Systems 2000 — Hot swap diagram (page 17)
Fig. 24 · Hot swap

Connection to the AC-power source: 1. Connect the electrical power cord to the socket for connection to AC-power source. 2. Connect the other end of the electrical power cord to an AC-power outlet.

Page 18 of the MGE UPS Systems 2000 user manual — Install
Page 18 · click to enlarge
Page 18

2. Installation

Install

This type of connection must be carried out by qualified electrical personnel.

Before carrying out any connections, check that the battery circuit breaker is OFF and that the upstream protection devices (AC distribution system) are open (OFF).

The overall cable diameter and the cross-sectional area of the three wires depends on the UPS rating.

MGE UPS Systems 2000 — Install diagram (page 18)
Fig. 25 · Install
MGE UPS Systems 2000 — Install diagram (page 18)
Fig. 26 · Install

From 9 to 12 mm From 9 to 12 mm

1 to 4 mm2 1,5 to 4 mm2

Recommended upstream circuit breaker ◗ Nominal rating (47 to 63Hz, 230V)

Power and equipment connections: 1. Remove the terminal-block cover . 2. Insert the cable supplying the equipment and the power cable through the cable clamps . 3. Connect the three wires of the equipment cable to the output terminal block .

Always connect the earthing wire first.

4. Connect the three wires of the power cable to the input terminal block . 5. Refit the terminal-block cover. 6. Tighten the nut on the cable clamp .
Page 19 of the MGE UPS Systems 2000 user manual — 3.1 ON-LINE operating mode
Page 19 · click to enlarge
Page 19

3. Operation

3.1 ON-LINE operating mode

This is the normal operating mode for the UPS.

Two possible cases:

LED is ON: AC input power is available. Power is drawn from the distribution system and supplied to the protected equipment via the UPS.

LED is ON: AC input power is not available. Power is drawn from the battery and supplied to the protected equipment.

bypass · bypass

Page 20 of the MGE UPS Systems 2000 user manual — 3.2 Start-up
Page 20 · click to enlarge
Page 20

3. Operation

3.2 Start-up

Prior to initial start-up, check the UPS voltage settings. The frequency of the output voltage (50 or 60 Hz) is automatically set to that of the input source.

MGE UPS Systems 2000 — 3.2 Start-up diagram (page 20)
Fig. 27 · 3.2 Start-up

1. Close the upstream device (ON position) controlling the supply of AC power to the UPS. 2. Set the battery circuit breaker(s) to ON. The buzzer beeps three times. If the supply frequency is different than the default value set on the UPS, the new value is set and the buzzer beeps 4 times. 3. Press the ON / OFF button . All the equipment connected to the UPS is now energised, however it takes another 30 seconds before the UPS is fully operational.

After this time, the equipment connected to the UPS is protected.

◗ If LED or do not go ON or if one of LED , , or flash, there is a fault (see section 4.1).

14 15 16 17

◗ In order to detect any wiring errors, it is essential that the AC-power source be present at the first switch-on. Subsequently, the device may be switched-on without the presence of the AC-power source.

1. Remaining backup time in percent.
2. Percent load drawn by the protected equipment, when button is pressed.
3. Operating faults (flashing LED and beeps):

Overload.

UPS fault.

Battery fault.

Excessive ambient temperature.

Page 21 of the MGE UPS Systems 2000 user manual — Return of AC input power
Page 21 · click to enlarge
Page 21

3. Operation

3.4 Failure of AC input power and operation on battery power AC input power is not available, the battery steps in to supply the protected equipment.

Transfer to battery power

MGE UPS Systems 2000 — Transfer to battery power diagram (page 21)
Fig. 28 · Transfer to battery power

When AC-power source goes outside tolerances or fails completely, LED goes ON and the buzzer beeps three times.

The low-battery shutdown warning threshold can be set by the user, with the "UPS Driver" software (default setting equal to 20% of full backup time). LED flashes when the setted level is reached. The buzzer beeps every three seconds when less than 10% of backup time remains.

There is very little remaining battery backup time. Close all applications because UPS automatic shutdown is imminent.

End of backup time

The buzzer sounds continuously. Press button to turn the buzzer OFF.

The equipment is no longer supplied with power.

Sleep mode

This operating mode may be personalized using the "UPS Driver" software (see section 3.5). It saves battery power when no equipment is connected to the UPS. Shutdown occurs after 5 minutes. The UPS automatically restarts when the AC-power source returns to within tolerances.

Return of AC input power

If, in spite of the return of AC input power, the UPS does not restart, check that the automatic-restart function (activated by return of AC input power) has not been disabled (see section 3.5).

Page 22 of the MGE UPS Systems 2000 user manual — "ON / OFF conditions" tab
Page 22 · click to enlarge
Page 22

3. Operation

3.5 Personalization

Function

Personalization parameters can be set and modified using the "UPS Driver" software installed on a computer that is connected to the UPS (see section 2.3 Connection to the RS 232 communications port).

Check that the RS 232 cable is correctly connected and that the battery circuit breaker is closed.

"UPS Driver" installation:

1. Insert the Solution-Pac CD-ROM containing the UPS Driver software in the drive of a PC running Windows. 2 - Open the Windows File manager or Explorer and select the CD-ROM drive. 3 - Double-click "\Emb\Index.htm", then "UPS Driver" .

Once "UPS Driver" has been installed, UPS parameters can be modified in a window containing a number of tabs, each presenting a set of parameters.

"ON / OFF conditions" tab

Cold start (battery power)

UPS ON / OFF via software

Show 10 more labels / short text on this page
Personalizable function · Default setting · Automatic start · Enabled · Enabled · Forced shutdown · Enabled · Sleep mode · Disabled · Enabled
Page 23 of the MGE UPS Systems 2000 user manual — "By-pass" tab
Page 23 · click to enlarge
Page 23

3. Operation

"Battery" tab

Once a week Once a month

"Low-battery shutdown warning" threshold

CLA (2, 4 or 8 hours)

"Output" tab

Rated AC-power source voltage (see figure 1)

200 V-208 V-220 V-240 V

Rated AC-power source frequency

Tolerance for AC-power source frequency

± 1% to ± 10% , in 1% steps

0 to 100%, in 10% steps

UPS restart after a short-circuit

Enabled (click to add check)

"By-pass" tab

Authorized voltage range for transfer to bypass

187 V to 265 V (for 230 V rated voltage)

187 V to 265 V, in 1V steps

if fault or overload

Authorized frequency range for transfer to bypass

± 1% to ± 10%, in 1% steps

if fault or overload

Transfer to bypass if overload

Disabled (click to remove check)

Transfer to bypass following a fault, whatever

Enabled (click to add check)

the conditions on the AC-power source

The value selected for the rated UPS voltage impacts on the power available at UPS output (see the diagram below).

Available power as a percentage of the rated power

Show 25 more labels / short text on this page
Personalizable function · Default setting · Options · "Battery test" intervals · Every day · No test · 20% remaining battery · 40% remaining battery · backup time · backup time · Charger · Standard · 50 Hz · 60 Hz · ± 5% · Overload alarm level · 100% · Disabled · ± 10% · Enabled · Disabled · 100% 95% 90% · 66% · 50% · Voltage in V
Page 24 of the MGE UPS Systems 2000 user manual — Complete shutdown of the UPS
Page 24 · click to enlarge
Page 24

3. Operation

3.6 Shutdown

Shutdown of connected equipment

1. Press button (return to the OFF position).

The connected equipment is no longer supplied with power, but the battery is maintened charged if AC-power source is present.

If the AC source fails, even though the connected equipment is no longer supplied, the UPS operates on battery power and therefore reduces the available backup time.

Complete shutdown of the UPS

1. Press button (return to the OFF position).

The connected equipment is no longer supplied with power.

2. Open the upstream device (OFF position) controlling the supply of AC power to the UPS . 3. Switch the battery circuit breaker(s) to OFF position.

The UPS is now de-energised and the batteries are no longer recharged.

Page 25 of the MGE UPS Systems 2000 user manual — 4.1 Troubleshooting
Page 25 · click to enlarge
Page 25

4. Maintenance

4.1 Troubleshooting

If one or more LEDs , , or flash, there is a operating anomaly or an alarm.

14 15 16 17

If a LED flashes, the bargraph data is no longer displayed.

Troubleshooting not requiring MGE after-sales support

LEDs , , , flash and the buzzer beeps.

17 14 15 16

The UPS has detected a problem concerning the wiring of the connection module input.

Shut down the UPS and check that the input power cable is properly connected to the input terminal block and the load to the output terminal block (see p. 18). After correcting any wiring errors, restart the UPS as indicated on page 20. If the problem persists, call MGE after-sales support.

LED flashes and the buzzer beeps.

UPS overload. Overload is too long or too high. The UPS cuts the supply of power to the connected equipment and the buzzer beeps continuously.

Check the power drawn by the equipment and disconnect any non-priority devices.

LED flashes.

The ambient temperature is higher than 35° C.

Install the UPS in a room where the ambient temperature is not greater than 35° C.

The UPS is not designed to operate more than eight hours under these conditions.

LED is ON.

The UPS is in maintenance mode (manual bypass)

See point 3 to 6 of in the "Hot-swap and Install connection modules" part of section 4.2.

Indication · Signification · Correction

Page 26 of the MGE UPS Systems 2000 user manual — 4. Maintenance
Page 26 · click to enlarge
Page 26

4. Maintenance

Troubleshooting requiring MGE after-sales support

LED flashes and the buzzer beeps.

UPS electronics have detected a UPS fault. Depending on the UPS personalization parameters (see section 3.5), there are two possibilities:

For UPSs equipped with Hot swap or Install connection modules, follow the UPS replacement procedure (see section 4.2).

◗ the equipment connected to the UPS continues to be supplied, but directly from the AC-power source (via the automatic bypass for a maximum of 8 hours (LED ON);

Call the after-sales support department.

◗ the connected equipment is no longer supplied.

The equipment connected to the UPS is no longer protected.

LED flashes.

A battery fault was detected during the battery test.

Call the after-sales support department because the batteries need replacing.

Indication · Signification · Correction

Page 27 of the MGE UPS Systems 2000 user manual — Fault-tolerant connection module
Page 27 · click to enlarge
Page 27

4. Maintenance

4.2 UPS replacement

Fault-tolerant connection module

Before carrying out this operation, the supply of power to the connected equipment must be cut. The equipment will therefore no longer be powered.

MGE UPS Systems 2000 — Fault-tolerant connection module diagram (page 27)
Fig. 29 · Fault-tolerant connection module

Disconnection: 1. Shut down the UPS by pressing button (return to the OFF position). 2. Open the battery circuit breaker(s) . 3. Open the upstream device (OFF position) controlling the supply of AC power to the UPS. 4. Remove the two fixing screws and the connection module from the UPS.

Reconnection: 1. Insert the connection module in the connector and secure using the two screws . 2. Close the upstream device (ON position) controlling the supply of AC power to the UPS. 3. Close the battery circuit breaker(s) .

MGE UPS Systems 2000 — Fault-tolerant connection module diagram (page 27)
Fig. 30 · Fault-tolerant connection module

Check that UPS personalization settings still correspond to the equipment to be supplied (see section 3.5).

4. Start the UPS by pressing button .

The connected equipment is again protected by the UPS.

Page 28 of the MGE UPS Systems 2000 user manual — NORMAL BY-PASS
Page 28 · click to enlarge
Page 28

4. Maintenance

Hot-swap and Install connection modules

Before turning the switch,

Disconnection: 1. Turn the manual bypass switch , located behind the UPS (see section 2.5), from the NORMAL to the intermediate position. 2. Check that LED is ON before continuing to the BYPASS position.

NORMAL BY-PASS

If LED is not ON, do not switch to the BYPASS position and call the after-sales support department.

3. Turn the manual bypass switch from the intermediate position to the BYPASS position.

The connected equipment is supplied by the AC- power source, via the manual bypass.

4. Shut down the UPS by pressing button (return to the OFF position). 5. Open the battery circuit breaker(s) . 6. Remove the two fixing screws and the connection module from the electronic module (see next page).

Before turning the switch,

NORMAL BY-PASS

The UPS can be replaced. The connected equipment is supplied by the AC-power source.

see the manual · bypass · see the manual

Page 29 of the MGE UPS Systems 2000 user manual — 4. Maintenance
Page 29 · click to enlarge
Page 29

4. Maintenance

Reconnection: 1. Insert the connection module in the connector and secure using the two screws . 2. Switch the battery circuit breaker(s) to the ON position and check that LED is ON.

MGE UPS Systems 2000 — 4. Maintenance diagram (page 29)
Fig. 31 · 4. Maintenance

Check that UPS personalization settings still correspond to the equipment to be supplied (see section 3.5).

3. Press button and wait 20 seconds. 4. Check that LED is ON.

If LED is not ON, do not switch to the intermediate position and call the after-sales support department.

5. Turn the manual bypass switch from the BYPASS position to the intermediate position and check that LED is ON. 6. Turn the manual bypass switch from the intermediate position to the NORMAL position. LED goes OFF and LED goes ON.

The connected equipment is again protected by the UPS.

Page 30 of the MGE UPS Systems 2000 user manual — 5. Environment
Page 30 · click to enlarge
Page 30

5. Environment

This product has been designed to respect the environment:

It does not contain CFCs or HCFCs. It was manufactured in a factory certified ISO 14001.

UPS recycling at the end of service life:

MGE UPS SYSTEMS undertakes to recycle, by certified companies and in compliance with all applicable regulations, all UPS products recovered at the end of their service life (contact your branch office).

Packing:

UPS packing materials must be recycled in compliance with all applicable regulations.

This product contains lead-acid batteries. Lead is a dangerous substance for the environment if it is not correctly recycled by specialized companies.

Web sitewww.mgeups.com
Page 31 of the MGE UPS Systems 2000 user manual — 6.1 Glossary
Page 31 · click to enlarge
Page 31

6. Appendices

6.1 Glossary

Authorized voltage Upper and lower voltage thresholds within which the UPS can operate range for transfer to on the automatic bypass in the event of a UPS fault or overload. bypass if fault or overload

Automatic bypass Automatic switch controlled by the UPS, used to connect the equipment directly to the AC-power source.

Automatic start following When AC input power returns following shutdown at the end of the battery return of AC input power backup time, UPS automatic start can be enabled or disabled.

Backup time Time that the connected equipment can operate on battery power.

Bargraph Device on the front panel indicating the percent remaining backup time or the percent load.

Battery test Internal UPS test on battery status.

CLA (Long backup- Module incorporating a charger for long backup times. The charger is powerful time charger) enough to charge battery extension modules offering very long backup times.

Cold start See "Start on battery power".

Connection module Unit grouping the receptacles for connection to the AC-power source and the equipment.

Dialog box A window in a computer program displayed for selection by the user of various options and parameter settings.

Double conversion The power supplied to the connected equipment is completely regenerated by continuous double conversion, i.e. the AC power from the AC-power source is rectified (AC - DC), then converted back (DC - AC) to AC power.

Equipment Devices or systems connected to the UPS output.

Fault tolerant Connection module (without manual bypass) offering receptacles for connection to the AC-power source and the equipment.

Forced shutdown Allows a "clean" of computer operating systems depending on the low battery threshold setting. If the input source is restored during the time period between the shutdown order and actual system shutdown, it causes a voluntary interruption of the supply of power to the connected equipment (lasting 10 seconds) after system shutdown.

Page 32 of the MGE UPS Systems 2000 user manual — 6. Appendices
Page 32 · click to enlarge
Page 32

6. Appendices

Out of tolerance The AC input source is either absent or its voltage or frequency is outside the set limits.

Hot swap Connection module (with manual bypass) offering a socket for connection to the AC-power source and outlets or a terminal block for connection to the equipment.

Install Connection module (with manual bypass) offering terminal blocks for connection to the AC-power source and the equipment.

Manual bypass Rotary switch controlled by the user, used to connect the equipment directly to the AC-power source. Transfer of the load to the manual bypass enables UPS maintenance or replacement, without interrupting the supply of power to the connected equipment.

ON-LINE mode The normal UPS operating mode, by which the AC-power source supplies the UPS, which in turn, following double conversion of the AC power, supplies the connected equipment.

Percent load Ratio between the power drawn by the connected equipment and the total power that the UPS can supply.

Personalization A number of UPS functions can be modified using the "UPS Driver" software to better meet the user's needs.

Sleep mode This function shuts down the UPS after 5 minutes when it operates on battery power and no load is detected on the UPS output. The UPS restarts automatically as soon as the AC input source is restored.

Start on battery power This function makes it possible to energize the connected equipment even when AC input power is not available (operation exclusively on battery power).

Tolerance for AC-power The range of frequency supplied by the AC-power source within which source frequency the UPS can operate in ON-LINE mode (double conversion).

UPS Uninterruptible Power Supply.

UPS ON / OFF It is possible to enable or disable use of UPS ON / OFF controls via software by the computer-system protection software.

Page 33 of the MGE UPS Systems 2000 user manual — 6.2 Index
Page 33 · click to enlarge
Page 33

6. Appendices

6.2 Index

Failure 21 Frequency tolerance 23 Rated frequency 23 Rated voltage 23 Return 21

Lamp test 11

ON LINE mode 11, 19

B Bargraph 20 Battery

O Overload 11, 23, 25

Battery test 23 End of backup time 21 Fault 11, 20 Low-battery shutdown warning 21 Recycling 30 Transfer to battery power 21 Buzzer 3, 11, 21 By-pass

P Personalization 22

Battery 23 ON / OFF conditions 22 Output 23

R Rack 6, 14

Automatic bypass 19, 26 Manual bypass 11, 27

C Communication 15 Connection

Forced shutdown 22 UPS ON / OFF via software 22 UPS shutdown 11, 24 Sleep mode 21-22 Software

Communications card 15 Connection modules 17-18 RS 232 communications port 15

UPS Driver 12-13, 22 Start-up

F Fault (UPS)

Automatic start 22

Load 11 Transfer to automatic bypass 26 Fault tolerant 7, 16, 27

Excessive ambient temp 11, 20, 25

H Hot swap 7, 17, 28-29

U UPS Driver 12-13, 22

I Install 7, 18, 28-29

Show 5 more labels / short text on this page
A AC power · L LEDs · M Mode · S Shutdown · T Temperature
Page 34 of the MGE UPS Systems 2000 user manual — 6.2 Index
Page 34 · click to enlarge
Page 34
Page 34 of the MGE UPS Systems 2000 user manual — 6.2 Index
Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the MGE UPS Systems 2000

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the MGE UPS Systems 2000

Be the first to ask — other owners or our team will answer.

Original document

MGE UPS Systems 2000 manual PDF

34 pages·1.3 MB·Power Supply·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…