Instruction/ maintenance manual of the product 1850 Aprilaire
Go to page of 28
Model 1 8 3 0, 1 8 5 0 & 1 8 5 0 W Dehumidifier Installation Instructions READ AND SA VE THESE INSTRUCTIONS CAUTION 1. Read all instructions before beginning installation. 2. Improper installation may cause property damage or injury . Installation, service, and maintenance must be performed by a qualified service technician.
T ABLE OF CONTENTS Safety Instructions ...................................................................................................... 1 Specifications ............................................................................................
SPECIFICA TIONS Model 1830 Model 1850 & 1850W Weight 67 lbs. 70 lbs. Capacity AHAM DH-1-2008 80°F , 60% RH Conditions 70 pints per day @ 160 CFM 95 pints per day @ 265 CFM Power 115 V AC, Single Phase, 60Hz 6.
STANDARD BASEMENT AND ATTIC INSTALLATIONS (FULLY DUCTED) • Use thescrews intheparts bagto attachthe ductcollars to the inlet and outlet ofthe dehumidifier . Theoutlet collar has a backflow damper .
CONTROL P ANEL COVER CONTROL CONTROL CONTROL P ANEL COVER FIL TER ACCESS DOOR SET UP DEHUMIDIFIER FOR INST ALLA TION (CONTINUED) CONTROL LOCATION The on-board control can be located on the top of the dehumidifier or can be relocated to the front of the dehumidifier if the control can not be seen/accessed in the top orientation.
HARD WIRING WARNING ELECTRICAL SHOCK HAZARD: 115-volts may cause serious injury or death from electrical shock. Disconnect and tag electrical service before starting installation or field-service. Leave electrical service disconnected until installation or field-service is complete.
LINE VOL TAGE NEUTRAL GROUND 115V AC WIRING TERMINALS GROUND LUG FITTING AS REQUIRED LINE SERVICE CABLE/CONDUIT ELECTRICAL SERVICE BOX SIDE P ANEL ELECTRICAL SERVICE BOX POWER CORD STRAIN RELIEF FIGURE 6 – Electrical Service Box Location FIGURE 7 – Hard Wire to 115 VAC Service 90-1900 90-1902 HARD WIRING (CONTINUED) WIRING INSTRUCTIONS 1.
LOCA TION CONSIDERA TIONS TOP VIEW FIL TER MINIMUM CLEARANCE FOR FIL TER (EITHER SIDE) 13" 6" MINIMUM CLEARANCE FOR PROPER AIR FLOW ELECTRICAL SERVICE ACCESS THIS SIDE 6 FT .
0.38" MIN 2.00" MAX 3/4” DRAIN FLOA T Switch DH DH NORMAL LY CLOSED FLO AT SWITCH DRAIN INST ALLA TION LEVELING CONDENSATE PAN, CONDENSATE PUMP AND FLOAT SWITCH The feet can be adjusted to level the unit, and if required, to accommodate drain fittings and a secondary condensate pan.
DUCTING TO HV AC SYSTEM – BASEMENT AND A TTIC INST ALLA TIONS The Preferred Installation is to duct the dehumidifier to pull air from and return dehumidified air to the HVAC return duct. This installation will ensure warm, dehumidified air is thoroughly mixed with the HV AC system air before being discharged into the living space.
HV AC Model 1 830 0.4” w. c. MAX Model 18 50 (W) 0.6” w. c. MAX HV AC DUCTING TO HV AC SYSTEM – CLOSET INST ALLA TIONS The dehumidifier in these applications is typically installed under or next to the HV AC equipment.
T O/ FROM SECONDARY ZONE SUPPL Y DUCT RETURN DUCT NORMALL Y CLOSED DAMPER NORMALL Y CLOSED DAMPER SUPPL Y TO PRIMARY ZONE RETURN FROM PRIMARY ZONE NORMALL Y OPEN DAMPER NORMALL Y OPEN DAMPER 6 ft MIN .
+- AB ODT Sensor Remote Gh Rf Cf Gs Y W HVAC EQUIP . MODEL 76 CONTROL FLOA T Switch DH DH VENT DEH Dampers NC NO NO/NC SWITCH DH DH R/+ C/- B A MODEL 76 – EXTERNAL CONTROL OR CRA WL SP ACE / SEALED A TTIC CONTROL AND WIRING NOTE: Use 18-22 AWG wire for control wiring.
WIRING TO THE HVAC SYSTEM WIRING TO ZONE DAMPERS When the dehumidifier is ducted to the HV AC system, it is recommended that it also be wired to the HV AC system as shown in Figure 22 .
SYSTEM SET -UP & CHECKOUT If dehumidifier installation does not include ventilation or zoning and will not be wired to an external control, remote control or the HV AC system, proceed to Installer T est Mode section on page 17. 1. Check all wiring.
DEH W/AC 90-1854 T o allow dehumidification during active air conditioning, select ENABLED and press MODE. 90-1854 T o disable dehumidification when the air conditioning is on, select DISABLED and Press MODE.
SYSTEM SET -UP & CHECKOUT (CONTINUED) Dehumidification Only 90-1854 If the dehumidifier is not already OFF , press the ON/OFF button to turn it off. 90-1854 Press and hold the ON/OFF button and MODE buttons for 3 seconds. The measured humidity , AIR SAMPLING and TEST will show on the display .
ST ART UP AND SEQUENCE OF OPERA TION SINGLE ZONE WHOLE HOUSE OR STAND ALONE USING THE DEHUMIDIFIER CONTROL SINGLE ZONE WHOLE HOUSE OR STAND ALONE USING MODEL 76 EXTERNAL CONTROL CRAWL SPACE OR SEALED ATTIC (REMOTE) CONTROL USING MODEL 76 TWO ZONE – PRIMARY AND SECONDARY 1.
VENTILA TION The dehumidifier can activate a normally closed damper to bring in outdoor air through a fresh air intake duct. This feature can not be used when a Model 76 has been installed in a Remote Control application, and is not recommended for two-zone installations.
VENTILA TION (CONTINUED) VENT-AUTO & VENT-TIMED OUTDOOR TEMPERATURE SENSOR INSTALLATION The dehumidifier can ventilate in four modes. V ent-T imed: V entilation occurs based only on time setting; no temperature restrictions. V ent-Auto-B: V entilation prevented when outdoor temperature is below 0°F and above 100°F .
DETERMINE FRESH AIR DELIVERY RATE 1. Measure the negative static pressure of the return system at the location where the fresh air intake duct enters the return duct or dehumidifier inlet. 2. See T able 2 for estimated inlet airflow in CFM, based on duct type, length and available negative pressure.
T ABLE 3 – Cycle T ime Setting (minutes) for Airflow Delivered vs. Airflow Required for 1 hour Cycle CFM Delivered CFM Required 20 30 40 50 60 70 80 90 100 60 20 30 40 50 60 70 80 90 100 80 15 25 30.
SEQUENCE OF OPERATION When wired as shown in Figure 26 , the ventilation damper will open whenever there is an HV AC heating (W), cooling (Y) or fan (Gs) call, allowing fresh air to be brought in when the HV AC blower is running (see VENTILA TION WITH AN EXTERNAL CONTROL section below for exceptions).
TROUBLESHOOTING T echnical Support is available Monday through Friday , 7:00 a.m. to 5:00 p.m. CST , at (800) 334-6011. Use the guides on the following pages to identify and correct system faults. Contact T echnical Support before replacing the unit or any components and for additional troubleshooting.
TROUBLESHOOTING (CONTINUED) T ABLE 4 – Diagnostic Codes (continued) Diagnostic Code Failure Mode Action Reset E7 Float Switch Open 1. Empty the condensate pan. 2. Check the float switch connection at the control board. 3. If not using a float switch, verify jumper is between float switch terminals on dehumidifier control board.
T ABLE 5 – T roubleshooting Guide Symptom Possible Reason T roubleshooting Procedure Dehumidifier does not turn on/run. No power to unit. • Checkthat the dehumidifieris plugged in. • Checkthat the powerswitch is turned ON.
SERVICE P ARTS 8 7 3 4 5 9 1 6 2 13 10 18 11 14 17 19 16 12 15 No. Part Description Part No. 1 Filter , 10” x 12”x 1” EZK 5443 2 Internal Control Board, Deh 5444 3 User Interfa.
P.O.Box1467•Madison,WI53701-1467•Phone:800/334-6011 •Fax:608/257-4357• www.aprilairepartners.com 10010759 2.
An important point after buying a device Aprilaire 1850 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Aprilaire 1850 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Aprilaire 1850 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Aprilaire 1850 you will learn all the available features of the product, as well as information on its operation. The information that you get Aprilaire 1850 will certainly help you make a decision on the purchase.
If you already are a holder of Aprilaire 1850, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Aprilaire 1850.
However, one of the most important roles played by the user manual is to help in solving problems with Aprilaire 1850. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Aprilaire 1850 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center