MSH24WN MSZ-A24NA MS15TN MSY-A15NA MS17TN MSY-A17NA MS24WN MSY-A24NA
MSZ-A09NA MSZ-A09NA- 1 MSZ-A12NA MSZ-A12NA- 1 MSZ-A15NA MSZ-A15NA- 1 MSZ-A17NA MSZ-A17NA- 1
MSZ-A24NA MSZ-A24NA- 1 MSY-A15NA MSY-A15NA- 1 MSY-A17NA MSY-A17NA- 1 MSY-A24NA MSY-A24NA- 1

MSZ-A24NA MSY-A24NA

Air cleaning filter (Anti-Allergy Enzyme Filter, Blue bellows type)




7/16x13/16 Oblong hole 7/16x1 Oblong hole
2-3/16 2-3/16 8-7/8 8-7/8
Wall hole 2-9/16 Indoor unit
Liquid line 1/4 19-11/16 Gas line 3/8 16-15/16 Insulation 1-3/8 O.D 3/4 I.D {
Drain hose 5/8 (Connected part O.D)

Installation plate Indoor unit
3-7/8 6-13/16 16-5/16 16-5/16
Liquid line 1/4 19-11/16 Gas line 5/8 16-15/16 Insulation 1-15/16 O.D
Drain hose 5/8 (Connected part O.D)




MSZ-A15NA MSY-A15NA MSZ-A17NA MSY-A17NA
Refrigerant pipe ø1/2 (with heat insulator)
Refrigerant pipe ø3/8 (with heat insulator)


Refrigerant pipe ø1/4 (with heat insulator)
Refrigerant pipe ø1/4 (with heat insulator)
Refrigerant pipe ø5/8 (with heat insulator)

Refrigerant flow in cooling
Refrigerant pipe ø1/4 (with heat insulator)
Refrigerant flow in heating

7-1. TIMER SHORT MODE For service, set time can be shortened by short circuit of JPG and JPS the indoor electronic control P.C. board. The time will be shortened as follows. (Refer to 8-7.) Set time : 1-minute 1-second Set time : 3-minute 3-second (It takes 3 minutes for the compressor to start operation. However, the starting time is shortened by short circuit-of JPG and JPS.) 7-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION A maximum of 4 indoor units with wireless remote controllers can be used in a room. In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be modified according to the number of the indoor unit.
How to modify the remote controller P.C. board
Remove batteries before modification. The board has a print as shown below :

the batteries and press the OPERATE/STOP(ON/ OFF)button twice or 3 times at first. After finish modification, put back the batteries then press the RESET button.
The P.C. board has the print “J1” and “J2”. Solder “J1” and “J2” according to the number of indoor unit as shown in Table 1. After modification, press the RESET button.
How to set the remote controller exclusively for particular indoor unit After you turn the breaker ON, the first remote controller that sends the signal to the indoor unit will be regarded as the remote controller for the indoor unit. The indoor unit will only accept the signal from the remote controller that has been assigned to the indoor unit once they are set. The setting will be cancelled if the breaker has turned off, or the power supply has shut down. Please conduct the above setting once again after the power has restored.

7-3. AUTO RESTART FUNCTION When the indoor unit is controlled with the remote controller, the operation mode, the set temperature, and the fan speed are memorized by the indoor electronic control P.C. board. The “AUTO RESTART FUNCTION” sets to work the moment power has restored after power failure. Then, the unit will restart automatically. Operation
If the main power has been cut, the operation settings remain. After the power is restored, the unit restarts automatically according to the memory. (However, it takes at least 3 minutes for the compressor to start running.) How to release “AUTO RESTART FUNCTION” Turn off the main power of the unit. Solder the Jumper wire JR07 on the indoor electronic control P.C. board. (Refer to 8-7.)
CN151 CN211 CN112
CN211 CN112
CN152
JR07
CN101
CN151
JR07
BZ
BZ
NOTE:
current by adding to the system that allows the units to start one by one.
1) Before servicing the air conditioner, be sure to turn OFF the unit first with the remote controller, and then after confirm- ing the horizontal vane is closed, turn OFF the breaker and/or disconnect the power plug. 2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board. 3) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components. 4) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
Lead wiring Housing point

1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing ON and OFF to indicate an abnormality. To make sure, check how many times the abnormality indication is flashing ON and OFF before starting service work. 2) Before servicing check that the connector and terminal are connected properly. 3) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the components for bursting and discoloration. 4) When troubleshooting, refer to 8-2., 8-3. and 8-4. 4. How to replace batteries
Weak batteries may cause the remote controller malfunction. In this case, replace the batteries to operate the remote controller normally.
or the like, and then use the remote controller. Remove the front lid and insert batteries. Then reattach the front lid.
Press RESET button with tip end of ball point pen
Insert the negative pole of the batteries first. Check if the polarity of the batteries is correct.
INFORMATION FOR MULTI SYSTEM AIR CONDITIONER OUTDOOR UNIT : MXZ series
Multi system air conditioner can connect two or more indoor units with one outdoor unit.
Lighted Blinking Not lighted
RESET button

Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (8-4.) disappears, the memorized failure details can be recalled. This mode is very useful when the unit needs to be repaired for the abnormality which doesn't recur.
Those figures show about MSZ-A09/12/15/17.
The cause of abnormality cannot be found because the abnormality doesn't recur.
Setting up the failure mode recall function
Turn ON the power supply.
While pressing both OPERATION SELECT button and TOO COOL button on the
remote controller at the same time, press RESET button. First, release RESET button. And release the other two buttons after all LCD in operation display section of the
remote controller is displayed after 3 seconds.
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1
Does the left lamp of OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: Either indoor or outdoor unit is abnormal. Beep is emit-
Indoor unit is normal. But the outdoor unit might be abnormal because there are some abnor- malities that can't be recalled with this way. Confi rm if outdoor unit is abnormal according to the detailed outdoor unit failure mode recall function.
ted at the same timing as the blinking of the left lamp of OPERATION INDICATOR lamp. 2
Judgment of indoor/outdoor abnormality
Before blinking, does the left lamp of OPERATION INDICA- TOR lamp stay ON for 3 seconds? Stays ON for 3 seconds (without beep): The outdoor unit is abnormal.
The indoor unit is abnormal. Check the blinking pattern, and confi rm the abnormal point with the indoor unit failure mode table. (8-2.2.) Make sure to check at least two consecutive blinking cycles. 2
The outdoor unit is abnormal. Check the blinking pattern, and confi rm the abnormal point with the outdoor unit failure mode table. (Refer to outdoor unit service manual.) Make sure to check at least two consecutive blinking cycles. 3
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller.
Repair the defective parts.
Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" mentioned above. Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed)
with the remote controller headed towards the indoor unit. Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. Release the failure mode recall function according to "Releasing the failure mode recall function"
mentioned above.
2.5-second OFF Blinking at 0.5- second interval
2.5-second OFF Blinking at 0.5- second interval


Left lamp of OPERATION
(Failure mode) Condition Correspondence
Not lighted Normal — —
The room temperature thermistor short or open circuit is detected every 8 seconds dur- ing operation.
1-time fl ash every 0.5-second Room temperature thermistor
Refer to the characteristics of the room temperature thermistor (8-7.).
2-time fl ash 2.5-second OFF Indoor coil thermistor
Refer to the characteristics of the main indoor coil ther- mistor, the sub indoor coil thermistor (8-7.). 3-time fl ash 2.5-second OFF Serial signal The serial signal from outdoor unit is not re- ceived for a maximum of 6 minutes.
The indoor coil thermistor short or open circuit is detected every 8 seconds during operation.
Refer to 8-6. "How to check miswiring and serial signal error".
The rotational frequency feedback signal is not emit during the 12 seconds the indoor fan operation.
11-time fl ash 2.5-second OFF Indoor fan motor
Refer to 8-6. "Check of indoor fan motor".
It cannot properly read data in the nonvolatile memory of the indoor electronic control P.C. board.
12-time fl ash 2.5-second OFF Indoor control system
Replace the indoor electronic control P.C. board.
Abnormal point · INDICATOR lamp

Indoor unit oper- ates. Outdoor unit doesn't operate.
Indoor unit operates. Outdoor unit doesn't operate normally.
Indoor unit doesn't receive the signal from remote controller.
OPERATION INDICATOR lamp on the indoor unit is fl ashing on and off.
If blinking of OPERATION INDI- CATOR lamp cannot be checked, it can be checked with failure mode recall function.
Outdoor unit operates only in Test Run operation.
Outdoor unit doesn't operate even in Test Run operation.
Unit doesn't operate nor- mal operation in COOL or HEAT mode.
Indoor unit operates, when EMERGENCY OPERATION switch is pressed.
Indoor unit doesn't operate, when EMER- GENCY OPERA- TION switch is pressed.
"Test Run operation" means
the operation within 30 minutes after EMERGENCY OPERA- TION switch is pressed.
Check room temperature thermistor. Refer to 8-7. "Test point diagram and voltage".
Refer to "How to check inverter/com- pressor".
Refer to "Check of R.V. coil".
Refer to 8-6. "Check of remote controller and receiver P.C. board".
Refer to outdoor unit service manual.
Left lamp Flash on and off at 0.5-sec- ond intervals Cause: Indoor/Outdoor unit • Miswiring or trouble of serial signal
Left lamp 2-time fl ash Cause: Indoor unit • Trouble of room temperature / indoor coil thermistor
Left lamp 3-time fl ash Cause: Indoor unit • Trouble of indoor fan motor
Left lamp 4-time fl ash Cause: Indoor unit • Trouble of indoor unit control system
Left lamp 5-time fl ash Cause: Outdoor unit • Outdoor power system abnormality
Left lamp 6-time fl ash Cause: Outdoor unit • Trouble of thermistor in outdoor unit
Left lamp 7-time fl ash Cause: Outdoor unit • Trouble of outdoor con- trol system
Left lamp 14-time fl ash Cause: Outdoor unit • Other ab- normality
Refer to 8-6.
Check room temperature thermistor and indoor coil thermis- tor. Refer to 8-7."Test point diagram and voltage".
Refer to 8-6.
Replace the indoor elec- tronic control P.C. board.
Refer to "How to check inverter/com- pressor".
Refer to "Check of outdoor ther- mistors".
Replace the inverter P.C. board or the outdoor electronic control P.C. board.
Check "Flow chart of the detailed outdoor unit failure mode recall func- tion."
"How to check mis- wiring and serial signal error".
"Check of indoor fan motor".
Start

8-4. TROUBLESHOOTING CHECK TABLE Before taking measures, make sure that the symptom reappears for accurate troubleshooting. When the indoor unit has started operation and detected an abnormality of the following condition (the first detection after the power ON), the indoor fan motor turns OFF and OPERATION INDICATOR lamp flashes.
Lighted Blinking Not lighted
No. Abnormal
point Operation indicator lamp Symptom Condition Correspondence
Left lamp fl ashes. 0.5-second ON
1 Miswiring or serial signal
The serial signal from the outdoor unit is not received for 6 minutes.
Refer to 8-6. "How to check miswiring and serial signal er- ror".
0.5-second OFF
Left lamp fl ashes. 2-time fl ash
Refer to 8-7. the characteristics of indoor coil thermistor, and the room temperature thermis- tor.
The indoor coil or the room temperature ther- mistor is short or open circuit.
2.5-second OFF
Left lamp fl ashes. 3-time fl ash
3 Indoor fan motor
The rotational frequency feedback signal is not emitted during the indoor fan operation.
Refer to 8-6. "Check of in- door fan motor". •
2.5-second OFF
Left lamp fl ashes. 4-time fl ash
It cannot properly read data in the nonvolatile memory of the indoor electronic control P.C. board.
4 Indoor con- trol system
Replace the indoor electronic control P.C. board. •
2.5-second OFF
Indoor unit and outdoor unit do not operate.
Left lamp fl ashes. 5-time fl ash
It consecutively occurs 3 times that the com- pressor stops for overcurrent protection or start-up failure protection within 1 minute after start-up.
Refer to "How to check of in- verter/compressor". Refer to outdoor unit service manual Check the stop valve.
5 Outdoor power sys- tem
2.5-second OFF
Left lamp fl ashes. 6-time fl ash
Refer to "Check of outdoor thermistor". Refer to outdoor unit service manual.
The outdoor thermistors short or open circuit during the compressor operation.
2.5-second OFF
Left lamp fl ashes. 7-time fl ash
Replace the inverter P.C. board or the outdoor electronic con- trol P.C. board. Refer to outdoor unit service manual.
7 Outdoor control sys- tem
It cannot properly read data in the nonvolatile memory of the inverter P.C. board or the out- door electronic control P.C. board.
2.5-second OFF
Left lamp fl ashes. 14-time fl ash
Check the stop valve. Confi rm the abnormality in detail using the failure mode recall function for outdoor unit.
An abnormality other than above mentioned is detected.
2.5-second OFF
Outdoor control system MSZ-A09/12 /15/17 MSY-A15/17
Check the blinking pattern of the LED on the inverter P.C. board or the outdoor electronic control P.C. board.
Outdoor unit does not oper- ate
It cannot properly read data in the nonvolatile memory of the inverter P.C. board or the out- door electronic control P.C. board.
Left lamp lights up

No. Abnormal
point Operation indicator lamp Symptom Condition Correspondence
Left lamp lights and lower lamp fl ashes. Lower lamp fl ashes.
The operation mode of the each indoor unit is differently set to COOL (includes DRY) and HEAT at the same time, the operation mode of the indoor unit that has operated at fi rst has the priority.
MXZ type Operation mode setting
Outdoor unit operates but indoor unit does not operate.
Unify the operation mode. Refer to outdoor unit service manual.
2.5-second OFF
8-5. TROUBLE CRITERION OF MAIN PARTS MSZ-A09NA MSZ-A12NA MSZ-A15NA MSZ-A17NA MSZ-A24NA MSY-A15NA MSY-A17NA MSY-A24NA
Part name Check method and criterion Figure
Room temperature thermistor(RT11) Measure the resistance with a tester.
Refer to 8-7. "Test point diagram and voltage", "Indoor electronic control P.C. board", the chart of thermistor.. Indoor coil thermistor (RT12(MAIN),RT13(SUB))
Indoor fan motor(MF) Check 8-6. .
Measure the resistance between the terminals with a tester. (Part temperature 50 ~ 86°F)
Horizontal vane motor(MV) MSZ-A09/12/15/17NA MSY-A15/17NA
Color of the lead wire Normal
BRN-other one 235 ~ 255 Ω
Measure the resistance between the terminals with a tester. (Part temperature 50 ~ 86°F)
Horizontal vane motor(MV1) Vertical vane motor(MV2) MSZ-A24NA MSY-A24NA
ROTOR
Color of the lead wire Normal
BRN-other one 282 ~ 306 Ω
•

A Check of indoor fan motor
The indoor fan motor error has occurred, and the indoor fan doesn't operate.
Turn OFF the power supply.
Pay careful attention to the high voltage on the fan motor connector CN211.
Turn ON the power supply, wait 5 seconds or more, and then press EMERGENCY OPERATION switch. Measure the supply voltage as follows within 12 seconds after EMER- GENCY OPERATION switch is pressed. If more than 12 seconds passes by, turn OFF the power supply and turn ON it again, then measure the voltage. 1. Measure the voltage between CN211 (+) and (-). 2. Measure the voltage between CN211 (+) and (-).
Is there any foreign matter that interferes the rotation of the line fl ow fan?
Remove the foreign matter and adjust the line fl ow fan.
If more than 12 seconds passes after EMERGENCY OPERATION switch
is pressed, the voltage mentioned above 2 goes 0 VDC although the indoor electronic control P.C. board is normal
Is there 294/325 VDC between CN211 (+) and (-), and does the voltage between CN211 (+) and (-) rise to the range of 3 to 6 VDC within 12 seconds after EMERGENCY OPERATION switch is pressed?
CN211 Indoor electronic control P.C. board Yes
Replace the indoor fan motor.
Replace the indoor electronic control P.C. board.
The indoor fan motor error has occurred, and the indoor fan repeats "12-second ON and 30-second OFF" 3 times, and then stops.
Measure the voltage between CN211
Is it unchanged holding 0 or 15 VDC? No (Changed)
(+) and (-) while the fan motor is rotating.
Replace the indoor electronic control P.C. board.
Replace the indoor fan motor.

Check if the remote controller is exclusive for this air conditioner.
button on the remote controller.
Is LCD display on the remote controller visible?
Replace the batteries. (Refer to 8-1.4.)
Remove the batteries, then set them back and press RESET button. (Refer to 8-1.4.) Check if the unit operates with the remote controller.
Does the unit operate with the remote controller?
Turn ON a radio to AM and press OP- ERATE/STOP (ON/OFF) button on the remote controller.
Is noise heard from radio?
No Replace the remote controller.
Are there any fl uorescent lights of inverter or rapid-start type within the range of 3.28 ft.? Yes
MSZ-A24NA MSY-A24NA
Measure the voltage between receiver P.C. board connector CN301 No.2(+) and No.3(-) when the remote controller button is pressed.
Replace the indoor electronic control P.C. board.
Is the voltage approx. 4 VDC?
Yes No (5 or 0 VDC)
Replace the receiver P.C. board.

Turn OFF the power supply. Remove indoor fan motor connector CN211 and vane motor connector CN151 from the indoor electronic control P.C. board and turn ON the power supply.
Measure the resistance between CN211 and of the indoor fan motor connector.
Short/open circuit: Replace the indoor fan motor.
Does the unit operate with the remote controller? Does OPERATION INDICATOR lamp light up by pressing EMERGENCY OPERATION switch?
Measure the resistance of the horizon- tal vane motor coil. (Refer to 8-5.)
Short/open circuit: Replace the horizontal vane motor and the indoor electronic control P.C. board.
Replace the indoor electronic control P.C. board.
Are the varistor (NR11) burnt and the fuse (F11) blown? No
Turn OFF the power supply. Check both “parts side” and “pattern side” of the indoor electronic control P.C. board visually.
Be sure to check both the fuse and the varistor in any case.
Is the fuse (F11) blown only?
Measure the resistance between (+) and (-) of the indoor fan motor connector (to CN211 on the indoor electronic control P.C. board). 1, 2
Is the resistance 1 MΩ or more?
Replace indoor electronic control P.C. board and the indoor fan motor. No
Replace indoor electronic control P.C. board.
Measure the resistance of cement resistor (R111) on the indoor elec- tronic control P.C. board.
Is the resistance approx. 4 Ω? No
Replace the indoor electronic control P.C. board and the indoor fan motor.
Replace the indoor electronic control P.C. board.
Indoor electronic control P.C.Board

Turn OFF the power supply.
Is there rated voltage in the power supply?
Check the power supply.
Turn ON the power supply.
Is there rated voltage between outdoor terminal block S1 and S2? No Check the wiring.
Press EMERGENCY OPERATION switch once.
Does the left lamp of OPERATION INDICA- TOR lamp light up?
Is there any miswiring, poor contact, or wire disconnec- tion of the indoor/outdoor connecting wire?
Is serial signal error indicated 6 minutes later?
Yes Correct them.
Turn OFF the power supply. Check once more if the indoor/outdoor connecting wire is not miswiring. Short-circuit outdoor terminal block S2 and S3. 1
B 1. Miswiring may damage indoor electronic control P.C. board during the operation. Be sure to confi rm the wiring is correct before the opera- tion starts. 3. Be sure to check this within 3 minutes after turning ON. After 3 minutes, LED blinks 6 times. Even when the inverter P.C. board or the outdoor electronic control P.C. board is normal, LED blinks 6 times after 3 minutes. (Except for outdoor unit of multi system type)
Turn ON the power supply.
Does the LED on the inverter P.C. board or the outdoor electronic control P.C. board repeat "3.6-second-OFF and 0.8-second- ON quick blinking"? 3 Yes
Replace the inverter P.C. board or the outdoor electronic control P.C. board.
No (Lighted or not lighted)
Is there any error of the in- door/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact to the terminal block?
Replace the indoor/ outdoor connecting wire. Turn OFF inverter-controlled lighting equipment. Turn OFF the power supply and then turn ON again. Press EMERGENCY OPERATION switch.
Is there any error of the in- door/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact to the terminal block?
Is there rated voltage between indoor terminal block S1 and S2?
Replace the indoor/ outdoor connecting wire.
Reinstall either the unit or the light each other away. Attach a fi lter on remote control receiving section of the indoor unit.
Is serial signal error indicated 6 minutes later?
Replace the indoor electronic control P.C. board.
Be sure to release the failure-mode recall function after checking.

Is the unit grounded? No Ground the unit.
Is the distance between the antennas and the indoor unit within 9.91 ft., or is the distance between the antennas and the outdoor unit within 9.91 ft.?
Extend the distance between the antennas and the indoor unit, and/or the antennas and the outdoor unit.
Is the distance between the TV sets or radios and the indoor unit within 3.28 ft., or is the distance between the TV sets or radios and the outdoor unit within 9.91 ft.?
Extend the distance between the TV sets and/or radios and the indoor unit, or the TV sets or radios and the outdoor unit.
Are the antennas damaged? Is the coaxial cable damaged? Is there any poor contact in the anten- na wiring?
Replace or repair the antenna. Replace or repair the coaxial cable.
Is the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas close? Yes
Extend the distance between the indoor/outdoor connecting wire of the air conditioner and the wir- ing of the antennas.
Even if all of the above conditions are fulfi lled, the electromagnetic noise may enter, depending on the electric fi eld strength or the installation condition (combination of specifi c conditions such as antennas or wiring). Check the followings before asking for service. 1. Devices affected by the electromagnetic noise TV sets, radios (FM/AM broadcast, shortwave) 2. Channel, frequency, broadcast station affected by the electromagnetic noise 3. Channel, frequency, broadcast station unaffected by the electromagnetic noise 4. Layout of ; indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, grounding wire, antennas, wiring from antennas, receiver 5. Electric fi eld intensity of the broadcast station affected by the electromagnetic noise 6. Presence or absence of amplifi er such as booster 7. Operation condition of air conditioner when the electromagnetic noise enters in 1) Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic noise. 2) Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button on the remote controller for power ON, and check for the electromagnetic noise. 3) After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the elec- tromagnetic noise. 4) Press OPERATE/STOP (ON/OFF) button on the remote controller for power OFF, when the outdoor unit stops but the indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise.

MSZ-A09NA MSZ-A12NA MSZ-A15NA MSZ-A17NA MSY-A15NA MSY-A17NA Indoor electronic control P.C. board
208/230 VAC Fuse (F11) 250 V 3.15 A

Indoor fan motor (CN211)
(-) Fiducial terminal of cathode side on measur- ing high-voltage DC
(+)3-6 VDC
Release of Auto restart function Solder the Jumper wire to JR07 (Refer to 7-3.)
(+)0 or 15 VDC

Indoor coil thermistor RT12(MAIN) RT13(SUB) (CN112)
Room temperature thermistor (RT11)
Timer short mode point JPG, JPS (Refer to 7-1.)
Power monitor receiver P.C. board 12 VDC
Indoor coil thermistor [RT12 (MAIN), RT13 (SUB)] Room temperature thermistor (RT11)
SW P.C. board

Release of Auto restart function Solder the Jumper wire to JR07 (Refer to 6-3.)
208/230 VAC Fuse (F11) 250 V 3.15 A


Indoor fan motor (CN211)
(-) Fiducial terminal of cathode side on measur- ing high-voltage DC
Display P.C. board
(+)3-6 VDC
(+)0 or 15 VDC

Indoor coil thermis- tor RT12(MAIN) RT13(SUB)
Horizontal vane motor (CN151)
Room temperature thermistor (RT11)
Timer short mode point JPG, JPS (Refer to 7-1.) Vertical vane motor (CN152)
Receiver P.C. board
Indoor coil thermistor [RT12 (MAIN), RT13 (SUB)] Room temperature thermistor (RT11)
SW P.C. board

The terminal which has the locking mechanism can be detached as shown below. There are two types ( Refer to (1) and (2)) of the terminal with locking mechanism. The terminal without locking mechanism can be detached by pulling it out. Check the shape of the terminal before detaching.
(1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector has the locking mechanism.
Slide the sleeve. Pull the terminal while pushing the locking lever.
Hold the sleeve, and pull out the terminal slowly.
OPERATING PROCEDURE PHOTOS
screws. (Photo 1) (3) Hold the lower part of both ends on the panel and pull
it slightly toward you, and then remove the panel by pushing it upward.

Screws of the panel

Screw of the conduit cover

Screw of the conduit cover


(1) Remove the horizontal vane, the panel (refer to 1.) and the
corner box. (2) Remove the screw of the conduit cover, and conduit cover.
(Photo 2 or Photo 3) (3) Remove the indoor/outdoor connecting wire. (4) Remove the switch holder from the electrical cover. (Photo
electrical cover. (Photo 4) (6) Remove the ground wire connected to the indoor electronic
Screw of the electrical cover.
control P.C. board from the electrical box. (Photo 5) (7) Unhook the power monitor receiver P.C. board holder from
the catch. (Photo 4) (8) Open the rear cover of the power monitor receiver P.C.
Power monitor receiver P.C. board holder
board holder and pull out the power monitor receiver P.C. board. (9) Open the switch holder and pull out SW P.C. board. (10) Pull the electronic control P.C. board slightly toward you
from the electrical box, and disconnect TAB3 and all the connectors on the electronic control P.C. board. (LD101 and LD105 are direct-mounted to the electronic control P.C. board.) (11) Pull out the electronic control P.C. board from the electrical

Indoor fan motor connector (CN211)
Indoor coil thermistor connector (CN112)
box. (12) Remove the ground wire connected to the heat exchanger
from the electrical box. (Photo 5) (13) Unhook the catches of the electrical box, and pull out the
Vane motor connector (CN151)
electrical box. (14) Remove the screw of the terminal block cover, and then
remove the terminal block cover and the terminal block holder. (Photo 6) (15) Remove the terminal block by sliding it.
Photo 6 3. Removing the electrical box (1) Remove the horizontal vane, the panel (refer to 1.) and the

corner box. (2) Remove the screw of Conduit cover, and then the indoor/
outdoor connecting wire. (Photo 2 or Photo 3) (3) Remove the switch holder and the electrical cover. (Photo 4) (4) Remove the ground wire connected to the heat exchang-
er from the electrical box. (Photo 5) (5) Disconnect the following connectors on the electronic
control P.C. board; the fan motor connector , the indoor coil thermistor connector , the vane motor connector . (Photo 5) (6) Unhook the catches of the electrical box, and pull out the
electrical box.
Switch holder · Ground wire · Screw

corner box. (2) Remove the screws of the horizontal vane motor unit, and

Screws of the horizontal vane motor unit
pull out the horizontal vane motor unit. (Photo 7) (3) Disconnect the connector from the horizontal vane motor
unit.
corner box. (2) Remove the switch holder and the electrical box. (Refer to 3.) (3) Remove the drain hose from the nozzle assembly, and

remove the nozzle assembly. (4) Remove the screws fixing the motor bed. (Photo 8) (5) Loosen the screw fixing the line flow fan. (Photo 9) (6) Remove the motor bed together with fan motor and motor
band. (7) Release the hooks of the motor band, and remove the
motor band then pull out the indoor fan motor. (8) Remove the screws fixing the left side of the heat exchang-
Screws of the motor bed
er. (Photo 10) (9) Lift the heat exchanger, and pull out the line flow fan to the
lower-left.

Screw of the line flow fan

Screws of the left side of the heat exchanger
Motor band

OPERATING PROCEDURE PHOTOS
screws. (2) Pull the panel down to your side slightly and unhook the
catches at the top.

Screw of the ground wire

Indoor electronic control P.C. board
mounted to the electronic control P.C. board. (5) Remove the R.L holder. (6) Remove the screw of the conduit cover. (7) Remove the conduit cover. (8) While pulling the electronic control P.C. board forward little
T.B. SW cover
by little, disconnect all the connectors from the board. (9) Remove the electronic control P.C. board. (10) Open the R.L holder, remove the receiver P.C. board and
Screw of T.B. SW cover
Screw of the electrical cover
the display P.C. board.
Receiver P.C. board
R.L holder
Screw of conduit cover
Screw of the ground wire

the vane motor connector (CN151 and CN152) on the elec- tronic control P.C. board. (5) Remove the screw of ground wire to the heat exchanger. (6) Remove the fan motor lead wire and indoor coil thermistor
from the electrical box. (7) Remove the lead wire of vane motor from the bottom of
Screw of the electrical box
electrical box. (8) Remove the screw fixing the electrical box and remove the
electrical box.

Vane motors Screws of the vane motor

the nozzle assembly. (6) Remove the screws of the vane motor and disconnect the
connector. (7) Remove the vane motor.
Screws of the vane motor


remove the nozzle assembly. (4) Remove the water cut. (5) Slide the hole cover and remove the hole cover. (6) Remove the hexagon socket set screw from the line flow fan. (7) Remove the screws fixing the motor bed and remove the fan
Screws fixing the left side of the heat exchanger
motor. (Be careful not to drop the fan motor because it is heavy.) (8) Remove the screws fixing the left side of the heat exchang-
er. (9) Lift the left side of the heat exchanger. (10) Remove the line flow fan.


Screws of the motor bed
Vane motor · Water cut · Hole cover

10-1. PARTS LIST (non-RoHS compliant) MSZ-A09NA MSY-A15NA MSZ-A12NA MSY-A17NA MSZ-A15NA MSZ-A17NA 1. INDOOR UNIT STRUCTURAL PARTS 2. ACCESSORY AND REMOTE CONTROLLER 1

No. Part No. Part name
Remarks MSZ- MSY- A09NA A12NA A15NA A17NA A15NA A17NA 1 E02 A32 234 BOX 1 2 E02 A49 000 PANEL ASSEMBLY 1 Including No.3,4 3 E02 913 067 SCREW CAP 2 PC/SET 4 E02 915 010 FRONT PANEL 1 5 E02 915 100 CATECHIN AIR FILTER (LEFT) 1 6 E02 916 100 CATECHIN AIR FILTER (RIGHT) 1 7 — AIR CLEANING FILTER 1 MAC-415FT-E 8 E02 A32 975 CORNER BOX (RIGHT) 1 9 E02 913 970 INSTALLATION PLATE 10 E02 A49 978 CONDUIT PLATE 1
11 E02 A54 426 REMOTE CONTROLLER 1 KM06A E02 A49 426 1 1 KM06C
12 E02 527 083 REMOTE CONTROLLER HOLDER 1
Q'ty/unit · Symbol in Wiring · Diagram

3. INDOOR UNIT ELECTRICAL PARTS AND FUNCTIONAL PARTS
16 14 15 17
No. Part No. Part name
Remarks MSZ- MSY- A09NA A12NA A15NA A17NA A15NA A17NA 1 E02 751 509 BEARING MOUNT 1 2 E02 001 504 SLEEVE BEARING 1 3 E02 897 702 DRAIN HOSE 1
4 E02 A54 235 NOZZLE ASSEMBLY 1 1 E02 A56 235 1
5 E02 897 303 VANE MOTOR UNIT (HORIZONTAL) MV 1 UP & DOWN
6 E02 913 040 HORIZONTAL VANE 1
7 E02 915 095 POWER MONITOR RECEIVER P.C. BOARD HOLDER 1
8 E02 A49 979 CONDUIT COVER 1 9 E02 A49 780 TERMINAL BLOCK COVER 10 E02 A49 779 TERMINAL BLOCK HOLDER 11 E02 913 375 TERMINAL BLOCK TB 1
1 E02 A55 452 1 E02 A56 452 1 E02 A57 452 1 E02 A51 452 1 E02 A52 452 1
13 E02 897 308 ROOM TEMPERATURE THERMISTOR RT11
1 1 E02 A56 307 15 E02 915 782 SWITCH HOLDER 16 E02 A54 300 INDOOR FAN MOTOR W2 MF 1 RC0J30-□□ 17 E02 897 333 MOTOR BAND 18 E02 897 302 LINE FLOW FAN 1 Including SW P.C. BOARD and POWER MONITOR RECEIVER P.C. BOARD 2 Including FAN MOTOR RUBBER MOUNT (2 PC/SET)
Symbol in Wiring · Q'ty/unit · Diagram

4. INDOOR UNIT HEAT EXCHANGER
No. Part No. Part name
1 E02 A54 620 INDOOR HEAT EXCHANGER 1 1 E02 A56 620 1
2 E02 815 666 UNION (GAS) 1 1 ø3/8 E02 155 666 1 ø1/2 3 E02 151 667 UNION (LIQUID) 1 ø1/4
Model Part No.
MSY-A15/17NA MAC-415FT-E
Replacement of the air cleaning filter
(1) Remove the catechin air filter (left one). The air cleaning filter is not attached to the right side catechin air filter.
(2) Remove the air cleaning filter (Blue bel-
lows type) from the catechin air filter.
Air cleaning filter (Blue bellows type)


No. Part No. Part Name
1 E02 527 970 INSTALLATION PLATE 1 1 2 E02 685 234 BOX 1 1 3 E02 888 000 FRONT PANEL ASSEMBLY 1 1 Including No.5,6 4 E02 408 142 CATCH 4 4 4 PC/SET 5 E02 685 067 SCREW CAP 3 3 3 PC/SET 6 E02 888 010 GRILLE 1 1 7 E02 534 100 CATECHIN AIR FILTER 2 2 1 PC/SET 8 E02 685 975 CORNER BOX (RIGHT) 1 1 9 -— AIR CLEANING FILTER 2 2 MAC-2300FT 10 E02 888 007 LAMP PANEL 1 1



No. Part No. Part Name
1 E02 527 302 LINE FLOW FAN 1 1 2 E02 408 509 BEARING MOUNT 1 1 3 E02 001 504 SLEEVE BEARING 1 1 4 E02 408 702 DRAIN HOSE 1 1 5 E02 A58 235 NOZZLE 1 1 6 E02 685 040 VANE UPPER 1 1 7 E02 685 041 VANE LOWER 1 1 8 E02 527 034 VANE CRANK SET 1 1 9 E02 A58 300 INDOOR FAN MOTOR ASSEMBLY 1 MF 1 1 RC0J56-□□ 10 E02 448 303 VANE MOTOR (VERTICAL) MV2 2 2 RIGHT & LEFT 11 E02 408 303 VANE MOTOR (HORIZONTAL) MV1 1 1 UP & DOWN 12 E02 918 333 MOTOR BAND 1 1 13 E02 918 329 DISPLAY P.C. BOARD 1 1 14 E02 918 468 RECEIVER P.C. BOARD 1 1
15 E02 A58 452 ELECTRONIC CONTROL P.C. BOARD 2 1 E02 A53 452 1 16 E02 527 308 ROOM TEMPERATURE THERMISTOR RT117 E02 A58 375 TERMINAL BLOCK TB 1 1
RT13 1 1
19 E02 528 034 VANE MOTOR SUPPORT SET(RIGHT) 1 1 20 E02 529 034 VANE MOTOR SUPPORT SET(LEFT) 1 1 1 Including FAN MOTOR RUBBER MOUNT 2 Including SW P.C. BOARD
21 E02 A58 426 REMOTE CONTROLLER 1 KM06B E02 A53 426 1 KM06D 22 E02 527 083 REMOTE CONTROLLER HOLDER 1 1

Model Part No.
Air cleaning filter (Anti-allergy enzyme filter:blue bellows type)

10-2. RoHS PARTS LIST (RoHS compliant) MSZ-A09NA MSY-A15NA MSZ-A12NA MSY-A17NA MSZ-A15NA MSZ-A17NA 1. INDOOR UNIT STRUCTURAL PARTS 2. ACCESSORY AND REMOTE CONTROLLER 1

Remarks MSZ-A MSY-A 09NA 12NA 15NA 17NA 15NA 17NA - 1 - 1 - 1 - 1 - 1 - 1 1 G E12 A32 234 BOX 1
No.
Part No. Part name
2 G E12 A49 000 PANEL ASSEMBLY 1 Including No.3,4 3 G E12 913 067 SCREW CAP 2 PC/SET 4 G E12 915 010 FRONT PANEL 1
5 G E12 915 100 CATECHIN AIR FILTER (LEFT) 1
6 G E12 916 100 CATECHIN AIR FILTER (RIGHT) 1
7 G — AIR CLEANING FILTER 1 MAC-415FT-E
8 G E12 A32 975 CORNER BOX (RIGHT) 1
9 G E12 913 970 INSTALLATION PLATE 10 G E12 A49 978 CONDUIT PLATE 1
1 KM06A G E12 A49 426 1 1 KM06C G E12 C30 426 1 1 KM07L G E12 C22 426 1 KM07J
12 G E12 527 083 REMOTE CONTROLLER HOLDER
1

3. INDOOR UNIT ELECTRICAL PARTS AND FUNCTIONAL PARTS
17 16 15 18
Remarks MSZ-A MSY-A 09NA 12NA 15NA 17NA 15NA 17NA - 1 - 1 - 1 - 1 - 1 - 1 1 G E12 751 509 BEARING MOUNT 1 2 G E12 001 504 SLEEVE BEARING 1 3 G E12 897 702 DRAIN HOSE 1
No.
Part No. Part name
4 G E12 A54 235 NOZZLE ASSEMBLY 1 G E12 A56 235 1 5 G E12 897 303 VANE MOTOR UNIT (HORIZONTAL) MV 1 UP & DOWN 6 G E12 913 040 HORIZONTAL VANE 1
7 G E12 915 095 POWER MONITOR RECEIVER P.C. BOARD HOLDER 1
8 G E12 A49 979 CONDUIT COVER 1 9 G E12 C30 979 CONDUIT COVER 1
1 G E12 C30 780 1
1 G E12 C30 779 12 G E12 913 375 TERMINAL BLOCK TB 1
1 1 G E12 A55 452 1 1 G E12 A56 452 1 1 G E12 A57 452 1 1 G E12 A51 452 1 1 G E12 A52 452 1 1 14 G E12 897 308 ROOM TEMPERATURE THERMISTOR RT11
ELECTRONIC CONTROL P.C. BOARD 1
15 G E12 A54 307 INDOOR COIL THERMISTOR
1 G E12 A56 307 16 G E12 915 782 SWITCH HOLDER 17 G E12 A54 300 INDOOR FAN MOTOR 2 MF 1 RC0J30-□□ 18 G E12 897 333 MOTOR BAND 19 G E12 897 302 LINE FLOW FAN 1 Including SW P.C. BOARD and POWER MONITOR RECEIVER P.C. BOARD 2 Including FAN MOTOR RUBBER MOUNT (2 PC/SET)
RT13

4. INDOOR UNIT HEAT EXCHANGER
Remarks MSZ-A MSY-A 09NA 12NA 15NA 17NA 15NA 17NA - 1 - 1 - 1 - 1 - 1 - 1
No.
Part No. Part name
1 G E12 A56 620 1
2 G E12 815 666 UNION (GAS) 1 ø3/8 G E12 155 666 1 ø1/2 3 G E12 151 667 UNION (LIQUID) 1 ø1/4
Model Part No.
MSY-A15/17NA MAC-415FT-E
Replacement of the air cleaning filter
(1) Remove the catechin air filter (left one). The air cleaning filter is not attached to the right side catechin air filter.
(2) Remove the air cleaning filter (Blue bel-
lows type) from the catechin air filter.
Air cleaning filter (Blue bellows type)


No.
Remarks MSZ-A24NA MSY-A24NA - 1 - 1 1 G E12 527 970 INSTALLATION PLATE 1 2 G E12 685 234 BOX 1 3 G E12 888 000 FRONT PANEL ASSEMBLY 1 Including No.5,6 4 G E12 408 142 CATCH 4 PC/ SET 5 G E12 685 067 SCREW CAP 3 PC/ SET 6 G E12 888 010 GRILLE 1 7 G E12 534 100 CATECHIN AIR FILTER 2 1 PC/ SET 8 G E12 685 975 CORNER BOX (RIGHT) 1 9 G — AIR CLEANING FILTER 2 MAC-2300FT 10 G E12 888 007 LAMP PANEL 1
Part No. Part Name

21 22 17 2
No.
Remarks MSZ-A24NA MSY-A24NA - 1 - 1 1 G E12 527 302 LINE FLOW FAN 1 2 G E12 408 509 BEARING MOUNT 1 3 G E12 001 504 SLEEVE BEARING 1 4 G E12 408 702 DRAIN HOSE 1 5 G E12 A58 235 NOZZLE 1 6 G E12 685 040 VANE UPPER 1 7 G E12 685 041 VANE LOWER 1 8 G E12 527 034 VANE CRANK SET 1
Part No. Part Name
9 G E12 A58 300 INDOOR FAN MOTOR ASSEMBLY 1 MF 1 RC0J56-□□
10 G E12 448 303 VANE MOTOR (VERTICAL) MV2 RIGHT & LEFT 11 G E12 408 303 VANE MOTOR (HORIZONTAL) MV1 UP & DOWN 12 G E12 918 333 MOTOR BAND 13 G E12 918 329 DISPLAY P.C. BOARD 14 G E12 918 468 RECEIVER P.C. BOARD 1
15 G E12 A58 452 ELECTRONIC CONTROL P.C. BOARD 2
16 G E12 527 308 ROOM TEMPERATURE THERMISTOR RT11
17 G E12 A58 375 TERMINAL BLOCK TB 18 G E12 918 307 INDOOR COIL THERMISTOR RT12, RT13 19 G E12 528 034 VANE MOTOR SUPPORT SET (RIGHT) 1 20 G E12 529 034 VANE MOTOR SUPPORT SET (LEFT) 1 Including FAN MOTOR RUBBER MOUNT 2 Including SW P.C. BOARD
1 KM06B G E12 A53 426 1 KM06D G E12 C26 426 1 KM07K G E12 C29 426 1 KM07M 22 G E12 527 083 REMOTE CONTROLLER HOLDER 1
REMOTE CONTROLLER

Model Part No.
Air cleaning filter (Anti-allergy enzyme filter:blue bellows type)


Once the operation mode is set, the same operation mode can be repeated by simply turning OPERATE/STOP (ON/OFF) button ON. Indoor unit receives the signal with a beep tone. When the system turns off, 3-minute time delay will operate to protect system from overload and compressor will not restart for 3 minutes.
Operation Indicator lamp The operation indicator at the right side of the indoor unit indicates the operation state. •The following indication applies regardless of shape of shape of the indication.

This shows that the air conditioner is operating to reach the target temperature. Please wait until the target temperature is obtained.
This shows that the room temperature is approaching the target temperature. Approx. 4°F or less
This shows a state of standby for operation. (For multi system air conditioner) —
Lighted · Blinking · Not lighted

11-1. COOL ( ) OPERATION (1) Press OPERATE/STOP (ON/OFF) button. OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone. (2) Select COOL mode with OPERATION SELECT button. (3) Press TEMPERATURE buttons (TOO WARM or TOO COOL button) to select the desired temperature. The setting range is 61 ~ 88°F.
11-2. DRY ( ) OPERATION (1) Press OPERATE/STOP (ON/OFF) button. OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone. (2) Select DRY mode with OPERATION SELECT button. (3) The set temperature is determined from the initial room temperature.
11-3. HEAT ( ) OPERATION (MSZ) (1) Press OPERATE/STOP (ON/OFF) button. OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone. (2) Select HEAT mode with OPERATION SELECT button. (3) Press TEMPERATURE buttons (TOO WARM or TOO COOL button) to select the desired temperature. The setting range is 61 ~ 88°F.
1. Cold air prevention control When the compressor is not operating or is starting, and the temperature of indoor heat exchanger and/or the room tem- perature is low or when defrosting is being done, the indoor fan will stop or rotate in Very Low speed. 2. High pressure protection In HEAT operation the compressor operational frequency is controlled by the temperature of the indoor heat exchanger to prevent the condensing pressure from increasing excessively. 3. Defrosting Defrosting starts when the temperature of outdoor heat exchanger becomes too low. The indoor/outdoor fans stop, the 4-way valve reverses, and the compressor starts. This mode continues until the temperature of outdoor heat exchanger rises or the fixed time passes.
11-4. FAN( )OPERATION (MSY) (1) Press OPERATE/STOP (ON/OFF) button. OPERATION INDICATOR lamp of the indoor unit turns ON with a beep tone. (2) Select FAN mode with OPERATION SELECT button. (3) Select the desired fan speed. When AUTO, it becomes Low. Only indoor fan operates. Outdoor unit does not operate.
11-5. “I FEEL CONTROL” ( ) OPERATION (MSY) (1) Press OPERATE/STOP (ON/OFF) button on the remote
Initial room temperature Mode
controller. OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone. (2) Select “I FEEL CONTROL” mode with OPERATION
75 °F or more COOL mode of "I FEEL CONTROL"
SELECT button. (3) The operation mode is determined by the room tempera-
less than 75 °F DRY mode of "I FEEL CONTROL"

(4) The initial set temperature is decided by the initial room temperature.
Model Initial room temperature Initial set temperature
79 °F or more 75°F 1 77 °F to 79 °F Initial room temperature minus 4 °F
COOL mode of "I FEEL CONTROL"
DRY mode of "I FEEL CONTROL" less than 77 °F Initial room temperature minus 4 °F
1 When the system is restarted with the remote controller, the system operates with the previous set temperature regard- less of room temperature at restart. The set temperature is calculated by the previous set temperature.
In “I FEEL CONTROL” ( ) mode, set temperature is decided by the microprocessor based on the room temperature. In addition, set temperature can be controlled by TOO WARM or TOO COOL buttons when you feel too cool or too warm. Each time the TOO WARM or TOO COOL button is pressed, the indoor unit receives the signal and emits a beep tone. • Fuzzy control When the TOO COOL or TOO WARM button is pressed, the microprocessor changes the set temperature, considering the room temperature, the frequency of pressing TOO COOL or TOO WARM button and the user’s preference to heat or cool. So this is called “Fuzzy control”, and works only in “I FEEL CONTROL” mode. In DRY mode of “I FEEL CONTROL”, the set temperature doesn’t change.
…To raise the set temperature 2~4 °F
…To lower the set temperature 2~4 °F
11-6. AUTO CHANGE OVER ··· AUTO MODE OPERATION (MSZ) Once desired temperature is set, unit operation is switched automatically between COOL and HEAT operation. Mode selection
COOL mode changes to HEAT mode when about 15 minutes have passed with the room temperature 4°F below the set temperature. HEAT mode changes to COOL mode when about 15 minutes have passed with the room temperature 4°F above the set temperature.
(5) TEMPERATURE buttons · (1) Initial mode · (2) Mode change

MSZ-A24 MSY-A24
(3) Positioning The vane is once pressed to the vane stopper to confirm the standard position and then set to the desired angle. Confirming of standard position is performed in the following cases. (a) When the operation starts or finishes (including timer operation). (b) When the test run starts. (c) When multi-standby starts or finishes.
(4) VANE AUTO ( ) mode In VANE AUTO mode, the microprocessor automatically determines the vane angle and operation to make the optimum room-temperature distribution.
(1) COOL and DRY operation Vane angle is fixed to Horizontal position or Angle 1.
(2) HEAT operation (MSZ) Vane angle is fixed to Angle 4.
(5) STOP (operation OFF) and ON-TIMER standby
In the following cases, the horizontal vane returns to the closed position. (a) When OPERATE/STOP (ON/OFF) button is pressed (POWER OFF). (b) When the operation is stopped by the emergency operation. (c) When ON-TIMER is ON standby. (6) Dew prevention
During COOL or DRY operation with the vane angle at Angle 2 ~ 4 (A09 ~ 17) / Angle 3 ~ 5 (A24) when the compressor cumulative operation time exceeds 1 hour, the vane angle automatically changes to Angle 1 for dew prevention. (7) SWING MODE ( )
By selecting SWING mode with VANE CONTROL button, the horizontal vane swings vertically. The remote controller displays “ ”.
(8) Cold air prevention in HEAT operation (MSZ)
The horizontal vane position is set to Upward.
this control doesn’t work in the indoor unit.
Upward

(9) To change the airfl ow direction not to blow directly onto your body. (MSZ-A09/12/15/17, MSY-A15/17)
To change the airfl ow direc-
tion When to use this function? COOL/DRY HEAT (For MSZ) Pressing and holding VANE CONTROL button for 2 seconds or more cause the horizontal vane to reverse and move to horizontal posi- tion.
Use this function if you don’ t want the air from the indoor unit to blow directly onto your body. • Depending on the shape of the room, the air may blow directly onto your body.
The air conditioner starts the cooling or drying opera- tion approx. 3 minutes after the vane has moved to the horizontal position. • When VANE CONTROL button is pressed again, the vane returns to the previously-set position and the air conditioner starts the cool or dry operation in approx. 3 minutes.
The air conditioner starts heating operation approx. 3 minutes after the vane has moved to the horizon- tal position. • Sometimes the area around your feet may not warm. To warm the area around the feet, set the hori- zontal vane to (AUTO) or the downward-blowing position.
(10) ECONO COOL ( ) operation (ECONOmical operation) When ECONO COOL button is pressed in COOL mode, set temperature is automatically set 3.6°F higher than that in COOL mode. Also the horizontal vane swings in various cycle. SWING operation makes you feel cooler than set temperature. So, even though the set temperature is higher than that in COOL mode, the air conditioner can keep comfort. As a result, energy can be saved. ECONO COOL operation is cancelled when ECONO COOL button is pressed once again or VANE CONTROL button is pressed or change to other operation mode. (11) POWERFUL ( ) operation
The air conditioner automatically adjusts the fan speed and the set temperature, and operates the POWERFUL mode. The POWERFUL mode is automatically released 15 minutes after operation starts, and the operation mode returns to the mode prior to POWERFUL operation.
(3) Positioning The vane is once pressed to the vane stopper to confirm the standard position and then set to the desired angle. Confirming of standard position is performed in the following cases. (a) When OPERATE/STOP (ON/OFF) button is pressed (POWER ON/OFF). (b) When SWING is started or finished. (c) When the power supply turns ON. (4) SWING MODE ( ) By selecting SWING mode with WIDE VANE button, the vertical vane swings horizontally. The remote controller displays “ ”.
Horizontal · position

(5) WIDE MODE ( ) By selecting WIDE mode with WIDE VANE button, indoor fan speed becomes faster than setting fan speed on the remote controller ( ). The remote controller displays “ ”. NOTE : The position of vane angle 3, angle 4 and angle 5 are different in COOL operation and HEAT operation.
Indoor fan speed becomes faster than setting fan speed on the remote controller even when or is selected.
11-8. TIMER OPERATION 1. How to set the time (1) Press OPERATE/STOP (ON/OFF) button to start the air conditioner. (2) Check that the current time is set correctly. NOTE : Timer operation will not work without setting the current time. Initially “0:00” blinks at the current time display of
TIME MONITOR, so set the current time correctly with CLOCK SET button.
(1) Press ON-TIMER button( ) during operation. (2) Set the time of the timer using TIME SET buttons ( and ) .
(1) Press OFF-TIMER button ( ) during operation. (2) Set the time of the timer using TIME SET buttons ( and ). Each time FORWARD button ( ) is pressed, the set time increases by 10 minutes; each time BACKWARD button ( ) is pressed, the set time decreases by 10 minutes. 2. Cancel
To cancel ON timer, press ON-TIMER button ( ). To cancel OFF timer, press OFF-TIMER button( ). TIMER is cancelled and the display of set time disappears.
(Example 1) The current time is 8:00 PM.
(Example 2) The current time is 11:00 AM.
The unit turns off at 11:00 PM, and on at 6:00 AM.
The unit turns on at 5:00 PM, and off at 9:00 PM.


ting is cancelled. As these models are equipped with an auto restart function, the air conditioner starts operating with timer cancelled when power is restored.
ON timer setting · OFF timer setting

11-9. EMERGENCY/TEST OPERATION In case of test run operation or emergency operation, use EMERGENCY OPERATION switch on the front of the indoor unit. Emergency operation is available when the remote controller is missing, has failed or the batteries of the remote controller run down. The unit will start and OPERATION INDICATOR lamp will light. The first 30 minutes of operation is the test run operation. This operation is for servicing. The Indoor fan speed runs at High speed and the system is in continuous operation (with thermostat ON). After 30 minutes of test run operation the system shifts to EMERGENCY COOL/HEAT MODE with a set temperature of 75°F. The fan speed shifts to Med. All protective operations such as the coil frost prevention works even in emergency operation. In the test run or emergency operation, the horizontal vane operates in VANE AUTO ( ) mode. Emergency operation continues until EMERGENCY OPERATION switch is pressed once or twice or the unit receives any signal from the remote controller. In case of latter normal operation will start.

The operation mode is indicated by the Operation Indicator lamp as following
COOL
STOP
11-10. Changing temperature indication (°F/°C)
The preset unit is °F. Press RESET button while the temperature buttons are pressed.
Press RESET button gently using a thin stick.
Copyright 2006 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD Distributed in Jun. 2008. No. OB450 REVISED EDITION-C 6 Distributed in May 2007. No. OB450 REVISED EDITION-B 7 Distributed in Dec. 2006. No. OB450 REVISED EDITION-A 7 Distributed in Apr. 2006. No. OB450 7 Made in Japan
New publication, effective Jun. 2008 Specifications subject to change without notice.