Models: 80 - 285 Starting Serial #H07H10040039

WARNING

If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life. This appliance MUST NOT be installed in any location where gasoline or flammable vapors are likely to be present.

  • WHAT TO DO IF YOU SMELL GAS
  • Do not try to light any appliance.
  • Do not touch any electric switch; do not use any phone in your building.
  • Immediately call your gas supplier from a near by phone. Follow the gas supplier’s instructions.
  • If you cannot reach your gas supplier, call the fire department.
  • Installation and service must be performed by a qualified installer, service agency, or the gas supplier.

Save this manual for future reference.

Page 3 of the Lochinvar 80 - 285 user manual — Freeze protection fluids –
Page 3 · click to enlarge
Page 3

Please read before proceeding

The Knight Boiler Installation and Operation Manual along with the Knight Boiler Service Manual are for use only by a qualified heating installer/service technician. Refer only to this User’s Information Manual for your reference. Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury (exposure to hazardous materials) or loss of life. Installation and service must be performed by a qualified installer, service agency or the gas supplier (who must read and follow the supplied instruction before installing, servicing, or removing this boiler. This boiler contains materials that have been identified as carcinogenic, or possibly carcinogenic, to humans).

Boiler service and maintenance –

NOTICE

  • To avoid electric shock, disconnect electrical supply before performing maintenance.
  • To avoid severe burns, allow boiler to cool before performing maintenance.

Boiler operation –

  • Do not block flow of combustion or ventilation air to the boiler. This boiler is equipped with a control which will automatically shut down the boiler should air or vent be blocked. If vent or air blockage is easily accessible and removable, remove it. The boiler should attempt to restart. If blockage is not obvious or cannot be removed, have the boiler and system checked by a qualified service technician.
  • Should overheating occur or gas supply fail to shut off, do not turn off or disconnect electrical supply to the circulator. Instead, shut off the gas supply at a location external to the appliance.

When calling or writing about the boiler – Please have the boiler model and serial number from the boiler rating plate.

NOTICE

Consider piping and installation when determining boiler location.

  • Do not use this boiler if any part has been under water. The possible damage to a flooded appliance can be extensive and present numerous safety hazards. Any appliance that has been under water must be replaced.

Any claims for damage or shortage in shipment must be filed immediately against the transportation company by the consignee.

Boiler water –

Factory warranty (shipped with unit) does not apply to units improperly installed or improperly operated.

  • Thoroughly flush the system (without boiler connected) to remove sediment. The high-efficiency heat exchanger can be damaged by build-up or corrosion due to sediment.

Failure to adhere to the guidelines on this page can result in severe personal injury, death, or substantial property damage.

WARNING

  • Do not use petroleum-based cleaning or sealing compounds in the boiler system. Gaskets and seals in the system may be damaged. This can result in substantial property damage.
  • Do not use “homemade cures” or “boiler patent medicines”. Serious damage to the boiler, personnel, and/or property may result.
  • Continual fresh make-up water will reduce boiler life. Mineral buildup in the heat exchanger reduces heat transfer, overheats the stainless steel heat exchanger, and causes failure. Addition of oxygen carried in by makeup water can cause internal corrosion. Leaks in boiler or piping must be repaired at once to prevent makeup water.

Freeze protection fluids –

  • NEVER use automotive antifreeze. Use only inhibited propylene glycol solutions, which are specifically formulated for hydronic systems. Ethylene glycol is toxic and can attack gaskets and seals used in hydronic systems.
Page 4 of the Lochinvar 80 - 285 user manual —  WARNING
Page 4 · click to enlarge
Page 4

1 Prevent combustion air contamination

Table 1 Corrosive Contaminants and Sources WARNING If the boiler combustion air inlet is located

in any area likely to cause contamination, or if products which would contaminate the air cannot be removed, you must have the combustion air and vent re-piped and terminated to another location. Contaminated combustion air will damage the boiler, resulting in possible severe personal injury, death, or substantial property damage.

Products to avoid:

Spray cans containing chloro/fluorocarbons

Chlorine-based swimming pool chemicals

If the boiler combustion air inlet is located in a laundry room or pool facility, for example, these areas will always contain hazardous contaminants.

Calcium chloride used for thawing

WARNING

Sodium chloride used for water softening

Paint or varnish removers

Pool and laundry products and common household and hobby products often contain fluorine or chlorine compounds. When these chemicals pass through the boiler, they can form strong acids. The acid can eat through the boiler wall, causing serious damage and presenting a possible threat of flue gas spillage or boiler water leakage into the building.

Antistatic fabric softeners used in clothes dryers

Chlorine-type bleaches, detergents, and cleaning solvents found in household laundry rooms Adhesives used to fasten building products and other similar products

Please read the information listed in Table 1. If contaminating chemicals will be present near the location of the boiler combustion air inlet, have your installer pipe the boiler combustion air and vent to another location, per the Knight Boiler Installation and Operation Manual.

Areas likely to have contaminants

Dry cleaning/laundry areas and establishments

To prevent the potential of severe personal injury or death, check for areas and products listed in Table 1 before installing the boiler or air inlet piping.

WARNING

If contaminants are found, you MUST:

  • Remove contaminants permanently. —OR—
  • Relocate air inlet and vent terminations to other areas.

Furniture refinishing areas and establishments

Show 15 more labels / short text on this page
Permanent wave solutions · Chlorinated waxes/cleaners · Refrigerant leaks · Hydrochloric acid/muriatic acid · Cements and glues · Swimming pools · Metal fabrication plants · Beauty shops · Refrigeration repair shops · Photo processing plants · Auto body shops · Plastic manufacturing plants · New building construction · Remodeling areas · Garages with workshops
Page 5 of the Lochinvar 80 - 285 user manual — If combustion or performance indicate need:
Page 5 · click to enlarge
Page 5

2 Maintenance schedule

Owner maintenance (see pages 6 - 8 for detailed instructions) Daily• Check boiler area • Check pressure/temperature gauge Monthly• Check vent piping • Check air piping • Check air and vent termination screens • Check relief valve • Check condensate drain system • Check automatic air vents Periodically• Test low water cutoff (if used) • Reset button (low water cutoff) Every 6 months• Check boiler piping (gas and water) for leaks • Operate relief valve End of season months•Shut boiler down (unless boiler used for domestic hot water)

Service technician

(see the Knight Boiler Service Manual)

General:

  • Reported problems
  • Inspect interior; clean and vacuum if necessary
  • Clean condensate trap and fill with fresh water
  • Check for leaks (water, gas, flue, condensate)
  • Verify flue and air lines in good condition and sealed tight
  • Check system water pressure/system piping/expansion tank

ANNUAL START-UP

  • Check control settings
  • Ignition and flame sense electrodes (sand off any deposits; clean and reposition)
  • Wiring and connections
  • Perform start-up checkout and performance verification per Section 10 in the Knight Installation and Operation Manual.
  • Flame inspection (stable, uniform)
  • Flame signal (at least 4 mA)
  • Clean the heat exchanger if flue temperature is more than 54°F above return water temperature.

If combustion or performance indicate need:

  • Clean heat exchanger
  • Remove and clean burner using compressed air only
  • Clean the blower wheel

WARNING Follow the maintenance procedures given throughout this manual. Failure to perform the service and maintenance or follow the directions in this manual could result in damage to the boiler or system, resulting in severe personal injury, death, or substantial property damage.

Page 6 of the Lochinvar 80 - 285 user manual — Maintenance procedures
Page 6 · click to enlarge
Page 6

2 Maintenance schedule

Maintenance procedures

Read the list of potential materials listed in Table 1 on page 4 of this manual. If any of these products are in the room from which the boiler takes its combustion air, they must be removed immediately or the boiler combustion air (and vent termination) must be relocated to another area.

Boiler must be serviced and maintained

WARNING The boiler must be inspected and started

annually at the beginning of the heating season by a qualified service technician. In addition, the maintenance and care of the boiler designated on page 5 of this manual and explained on pages 6 through 8 must be performed to assure maximum boiler efficiency and reliability. Failure to service and maintain the boiler and system could result in equipment failure, causing possible severe personal injury, death, or substantial property damage.

1. Make sure the pressure reading on the boiler pressure/ temperature gauge does not exceed 24 psi. Higher pressure may indicate a problem with the expansion tank.
2. Contact a qualified service technician if problem persists.
1. Visually inspect the flue gas vent piping for any signs of blockage, leakage, or deterioration of the piping. Notify your qualified service technician at once if you find any problems.

WARNING Failure to inspect the vent system as noted

above and have it repaired by a qualified service technician can result in vent system failure, causing severe personal injury or death.

WARNING To prevent potential of severe personal

injury, death, or substantial property damage, eliminate all materials discussed below from the boiler vicinity and the vicinity of the boiler combustion air inlet. If contaminants are found:

1. Visually inspect the air inlet termination to be sure it is unobstructed. Inspect the entire length of air piping to ensure piping is intact and all joints are properly sealed.
2. Call your qualified service technician if you notice any problems.

Remove products immediately from the area. If they have been there for an extended period, call a qualified service technician to inspect the boiler for possible damage from acid corrosion.

1. Inspect the boiler relief valve and the relief valve discharge pipe for signs of weeping or leakage.

If products cannot be removed, immediately call a qualified service technician to re-pipe vent and air piping and locate vent termination/air intake away from contaminated areas.

2. If the relief valve often weeps, the expansion tank may not be working properly. Immediately contact your qualified service technician to inspect the boiler and system.

Check condensate drain system

1. Combustible/flammable materials -- Do not store combustible materials, gasoline or any other flammable vapors or liquids near the boiler. Remove immediately if found.
1. Inspect the condensate drain line, condensate PVC fittings and condensate trap.

Fill condensate trap with water

2. Air contaminants -- Products containing chlorine or fluorine, if allowed to contaminate the boiler intake air, will cause acidic condensate in the boiler. This will cause significant damage to the boiler if allowed to continue.
1. Remove the PVC cap retaining screw from the PVC cap (FIG. 1).
2. Remove the 2" PVC cap with the switch located at the top of the trap (FIG. 1).
Show 5 more labels / short text on this page
Check pressure/temperature gauge · Check vent piping · Check boiler area · Check air piping · Check relief valve
Page 7 of the Lochinvar 80 - 285 user manual — NOTICE
Page 7 · click to enlarge
Page 7

2 Maintenance schedule (continued)

3. Fill with fresh water until the water begins to pour out of the drain.

Use materials approved by the authority having jurisdiction. In the absence of other authority, PVC and CPVC pipe must comply with ASTM D1785 or D2845. Cement and primer must comply with ASME D2564 or F493. For Canada use CSA or ULC certified PVC or CPVC pipe, fittings, and cement.

NOTICE

4. Replace the cap. Press the cap onto the trap until the cap makes contact with the drain.
5. Replace the retaining screw.

WARNING The condensate trap (FIG. 1) must be filled

with water during all times of boiler operation to avoid flue gas emission from the condensate drain line. Failure to fill the trap could result in severe personal injury or death.

Figure 1 Condensate Trap

The condensate line must remain unobstructed, allowing free flow of condensate. If condensate is allowed to freeze in the line or if the line is obstructed in any other manner, condensate can exit from the boiler tee, resulting in potential water damage to property. Call your qualified service technician to inspect the boiler and system.

Lochinvar 80 - 285 — NOTICE diagram (page 7)
Fig. 2
8. A condensate removal pump is required if the boiler is below the drain. When installing a condensate pump, select one approved for use with condensing boilers and furnaces. The pump should have an overflow switch to prevent property damage from condensate spillage. Call your qualified service technician to inspect the boiler and system.

Figure 2 Condensate Disposal

1. This boiler is a high efficiency appliance that produces condensate.
Lochinvar 80 - 285 — NOTICE diagram (page 7)
Fig. 3
2. The side of the boiler has a 1/2 inch PVC union for connection of a 1/2 inch PVC pipe (FIG. 2).
3. Slope condensate tubing down and away from the boiler into a drain or condensate neutralizing filter. Condensate from the Knight boiler will be slightly acidic (typically with a pH from 3 to 5). Install a neutralizing filter if required by local codes. Call your qualified service technician to inspect the boiler and system.

A Neutralizer Kit is available from the factory (Kit #4004). Call your qualified service technician to install.

4. Install the 1/2 inch PVC tee assembly (shipped with the unit) as shown in FIG. 2. Call your qualified service technician to inspect the boiler and system.
5. Leave the top of the 1/2 inch tee OPEN. This is needed as a vacuum break.
6. Do not expose condensate line to freezing temperatures.
7. Use only plastic tubing or piping as a condensate drain line (FIG. 2).

Condensate disposal

Page 8 of the Lochinvar 80 - 285 user manual — 2 Maintenance schedule
Page 8 · click to enlarge
Page 8

2 Maintenance schedule

Check automatic air vents

WARNING Have leaks fixed at once by a qualified

service technician. Failure to comply could result in severe personal injury, death, or substantial property damage.

1. Reference FIG. 3 below.
2. Remove the caps (FIG. 3 – “A”) from the automatic air vents in the system and check operation by slightly depressing valve “B” (FIG. 3) with the tip of a screwdriver.
3. Replace the front access door.
1. Before proceeding, verify that the relief valve outlet has been piped to a safe place of discharge, avoiding any possibility of scalding from hot water.
3. If the air vent valve appears to be working freely and not leaking, replace cap “A”, twisting the cap all the way on.
4. Loosen cap “A” one turn to allow vent to operate.

WARNING To avoid water damage or scalding due to

valve operation, a metal discharge line must be connected to the relief valve outlet and run to a safe place of disposal. This discharge line must be installed by a qualified heating installer or service technician in accordance with the instructions in the Knight Boiler Installation and Operation Manual. The discharge line must be terminated so as to eliminate possibility of severe burns or property damage should the valve discharge.

5. Have the automatic air vent(s) replaced if it does not operate correctly.

Figure 3 Automatic Air Vent

Lochinvar 80 - 285 — 2 Maintenance schedule diagram (page 8)
Fig. 4 · 2 Maintenance schedule
2. Read the boiler pressure/temperature gauge to make sure the system is pressurized. Lift the relief valve top lever slightly, allowing water to relieve through the valve and discharge piping.
3. If water flows freely, release the lever and allow the valve to seat. Watch the end of the relief valve discharge pipe to ensure that the valve does not weep after the line has had time to drain. If the valve weeps, lift the seat again to attempt to clean the valve seat. If the valve continues to weep afterwards, contact your qualified service technician to inspect the valve and system.

Test low water cutoff (if installed)

1. If the system is equipped with a low water cutoff, test the low water cutoff periodically during the heating season, following the low water cutoff manufacturer’s instructions.
4. If water does not flow from the valve when you lift the lever completely, the valve or discharge line may be blocked. Immediately shut down the boiler, following the operating instructions on page 9 of this manual. Call your qualified service technician to inspect the boiler and system.

Reset button (low water cutoff)

1. Testing the low water cutoff shuts the unit off. Press the RESET button on the low water cutoff to turn the unit back on.

Check boiler piping (gas and water)

Shut boiler down (unless boiler is used for Domestic Water)

1. Remove the boiler front access door and perform a gas leak inspection per steps 1 through 7 of the Operating Instructions on page 9. If gas odor or leak is detected, immediately shut down the boiler following the procedures on page 9. Call a qualified service technician.
1. Follow “To Turn Off Gas to Appliance” on page 9 of this manual.
2. Do not drain the system unless exposure to freezing temperatures will occur.
2. Visually inspect for leaks around water piping. Also inspect the circulators, relief valve, and fittings. Immediately call a qualified service technician to repair any leaks.
3. Do not drain the system if it is filled with an antifreeze solution.
4. DO NOT shut down boilers used for domestic water heating, they must operate year-round.

Operate relief valve

Page 9 of the Lochinvar 80 - 285 user manual — 3 Operating instructions
Page 9 · click to enlarge
Page 9

3 Operating instructions

Lochinvar 80 - 285 — 3 Operating instructions diagram (page 9)
Fig. 5 · 3 Operating instructions
Page 10 of the Lochinvar 80 - 285 user manual — Knight boiler control module
Page 10 · click to enlarge
Page 10

Knight boiler control module

Use the control panel (FIG. 4) to set temperatures, operating conditions, and monitor boiler operation.

Figure 4 Control Panel

Lochinvar 80 - 285 — Knight boiler control module diagram (page 10)
Fig. 6 · Knight boiler control module
Page 11 of the Lochinvar 80 - 285 user manual — Knight boiler control module
Page 11 · click to enlarge
Page 11

The user can adjust space heating target temperature by using the UP and DOWN buttons (FIG. 4) at any time during normal operation. By entering the USER code (0704), the user can also change temperature units, time and date, and night setback settings. In User Mode, the following parameters can be viewed but not changed:

  • Boiler outlet water target temperature in DHW Mode
  • Boiler model number
  • Software version
  • Total operating hours
  • Total cycles

Most parameters are available only to the installer, accessible only by entering the installer access code. Have your qualified service technician reference the Knight Boiler Service Manual.

Saving parameters (reference parameter table on page 12 of this manual)

To save parameters and exit programming:

Press the ENTER/RESET button (FIG. 4).

To keep parameter settings only for a current operating cycle:

Press the MENU/EXIT button (FIG. 4) 3 times after making all desired parameter changes.

To enter a parameter and continue programming:

Press the MENU/EXIT button 1 time to return to the parameter listings; press again to return to the menu listings. Remember to press the ENTER/RESET button when finished programming in order to save the changes made.

Have your qualified service technician reference the Knight Boiler Service Manual for a detailed description of parameters and access modes.

Access modes · User · Installer

Page 12 of the Lochinvar 80 - 285 user manual — Parameter table
Page 12 · click to enlarge
Page 12

Parameter table

Lochinvar 80 - 285 — Parameter table diagram (page 12)
Fig. 7 · Parameter table
GENERALMENUSUB ITEMDESCRIPTIONSEE PAGEUSER ACCESSINSTALLER ACCESS DISPLAYMODIFYDISPLAYMODIFY A1Boiler Model14YesNoYesNo 2User Code14YesYesYesYes 3Date and Time14YesYesYesYes 4Software Version14YesNoYesNo 5Temperature Units14YesYesYesYes 6Night Setback Temperature14YesYesYesYes 7Night Setback Times14YesYesYesYes

B 1 SH Set Point User 14 Yes

ATAD GNIGGOLC1Hours Running SH14YesNoYesNo 2Hours Running DHW14YesNoYesNo 3Ignition Attempts14YesNoYesNo 4Show Last 10 Errors14YesNoYesNo
E1DHW Boiler Set Point15YesYesYesYes 2SH/DHW Switching Time15YesYesYesYes
F5Outdoor Air Shutdown15YesYesYesYes 6Outdoor Air Shutdown Differential15YesYesYesYes 8Boost Temperature15YesYesYesYes 9Boost Time15YesYesYesYes
Page 13 of the Lochinvar 80 - 285 user manual — 4 SMART SYSTEM control module (continued)
Page 13 · click to enlarge
Page 13

4 SMART SYSTEM control module (continued)

A: General

If parameter A6 is set to anything other than 32°F, the night setback feature becomes active. This will require start and stop times to be programmed for the days that reduced temperatures are required. These times can be changed by the user or the installer by accessing parameter A7. Each day of the week (Sunday through Saturday) will have an on and off time.

The control will display “Knight Boiler” as the model number because the same control is used on several models. This will be displayed when parameter A1 has been accessed. This parameter is not changeable.

Example: Monday ON: 22:30, Tuesday OFF: 6:45. If you wish to skip a day and have no night setback, leave the on and off times the same. The default times for each day will be 00:00 (midnight).

The User Code allows the user to access and change a limited number of control parameters. The access code can be changed by the user or the installer to a code of their choosing. To change the code, parameter A2 must be accessed. The default code is 0704. The code can be changed one digit at a time by using the arrow keys on the display.

B: Temperature settings

SH set point user

The SH set point user sets the water temperature set point for fixed operation or the maximum temperature set point when the outdoor air sensor is used. This parameter can be changed by the user or the installer by accessing parameter B1. The temperature range of this parameter is 50°F to 190°F. The default value is 125°F.

The control uses an internal clock for the night setback feature and for logging of events. For these features to work correctly, the clock must be set when the boiler is first installed or anytime the boiler has been powered off for more than 30 days. To set the clock, parameter A3 must be accessed. The date and time are displayed as “YY:MM:DD W hh:mm”. YY = year, MM = month, DD = date, W = day (1 = Sunday, 2 = Monday, etc.), hh = hour (24 hour time; 2:00 PM = 14:00), mm = minutes.

C: Data logging

The hours running SH parameter shows the total number of hours the boiler has been in the SH firing position. This parameter can be viewed by the user and the installer by accessing parameter C1.

The software version allows the user to view the software version in use by the control. This software controls the operation of the boiler. When a new software version becomes available, the existing control can be replaced with a new control to update the software.

The hours running DHW parameter shows the total number of hours the boiler has been in the DHW firing position. This parameter can be viewed by the user and the installer by accessing parameter C2.

The control can be configured to display temperature in either °C or °F. This parameter can be changed by the user or the installer by accessing parameter A5. The default is °F.

The ignition attempts parameter shows the total number of times the boiler has attempted to fire. This parameter can be viewed by the user and the installer by accessing parameter C3.

Once the internal clock has been set correctly, the night setback feature can be used to program a lower water temperature set point for space heating. This parameter can be changed by the user or the installer by accessing parameter A6. The temperature range for this parameter is 32°F to 140°F. The feature is turned off with a setting of 32°F. The default value is 32°F.

Show last 10 errors

The control will log the 10 most current errors with the date and time the error occurred. This parameter can be viewed by the user and the installer by accessing parameter C4.

Show 10 more labels / short text on this page
Night setback times · Boiler model · User code · Date and time · Hours running SH · Software version · Hours running DHW · Temperature units · Ignition attempts · Night setback temperature
Page 14 of the Lochinvar 80 - 285 user manual — 4 SMART SYSTEM control module (continued)
Page 14 · click to enlarge
Page 14

E: DHW settings

If a SH demand lasts longer than the programmed time delay setting and there have been no DHW demands, the control will increase the water temperature set point by the amount in this parameter. If the SH demand continues through another time period, the set point will be increased again. This will continue until either the SH demand ends, a maximum of 20 increases has occurred, or the maximum set point has been reached. Once the SH demand has been satisfied the set point will revert back to its calculated setting. The boost temperature can be changed by the installer by accessing parameter F8. The temperature range of this parameter is 0°F to 45°F. The default value is 0°F. This feature will be active if this parameter is set to anything other than 0°F.

DHW boiler set point

When a DHW call for heat becomes active, the control will use the DHW boiler set point to determine the firing rate of the boiler based on the actual water temperature. This parameter can be changed by the installer by accessing parameter E1. The temperature range of this parameter is 50°F to 190°F. The default value is 180°F.

The SH/DHW switching time parameter sets the length of time the control will stay in DHW Mode when a SH call has been received. After this time period has expired the control will revert to SH Mode. If a DHW call is still active the timer will reset. After the time period has expired the control will revert back to DHW Mode. This will continue until one of the demands has been satisfied. This parameter can be changed by the installer by accessing parameter E2. The time range of this parameter is 10 minutes to 240 minutes. The default value is 30 minutes.

The boost time parameter sets the amount of time that must elapse with a SH demand before the water temperature set point will be increased. This parameter can be changed by the installer by accessing parameter F9. The time range for this parameter is 1 minute to 60 minutes. The default value is 20 minutes.

F: Outdoor air reset

When the outdoor air shutdown rises above this point, the control will block all SH demands (DHW demands will still be active). This parameter can be changed by the user or the installer by accessing parameter F5. The temperature range of this parameter is 0°F to 120°F. The default value is 80°F.

Outdoor air shutdown differential

The outdoor air shutdown differential parameter is the number of degrees below parameter F5 the outdoor air temperature must go before the boiler will respond to a SH demand. This parameter can be changed by the user or the installer by accessing parameter F6. The temperature range of this parameter is 0°F to 90°F. The default value is 10°F.

Show 4 more labels / short text on this page
Boost temperature · SH/DHW switching time · Boost time · Outdoor air shutdown
Page 15 of the Lochinvar 80 - 285 user manual — #2
Page 15 · click to enlarge
Page 15

4 SMART SYSTEM control module (continued)

Status Display Screens By using the Previous/Next (◁, ) arrow keys on the SMART SYSTEM display panel, you can navigate through the eight (8) display screens. Each screen will contain two (2) viewable items. The following is a description of the individual items and what they can display:

Screen Display shows: Description

BLR: OFF The unit has been turned OFF by the Enter/Reset button on the SMART SYSTEM display panel.

Standby The unit has not received a call for heat from a remote thermostat nor has it received a call for heat from a DHW thermostat.

The unit has met the water temperature set point, but is still receiving a call for heat from either a remote thermostat or a DHW thermostat.

Prepurge The unit has initiated a 10 second purge period on a call for heat.

Ignition The unit has begun a 5 second spark period to ignite the main burner.

SH***% Rate The unit has fired and is running at the displayed percentage.

#1

The call for heat has been satisfied and the unit runs the fan for an additional 10 seconds to clear the combustion chamber and vent system of residual flue products.

Service The unit has been placed in a temporary mode that will allow the unit to fire at 100% of rate for the purpose of combustion analysis.

When the outlet sensor has been selected as the control sensor (default), the control will display the outlet temperature as well as the set point in parenthesis.

OUT: ***.*F(***)

***.*F If the outlet sensor has not been selected as the control sensor, only the outlet temperature will be displayed.

Open The control does not detect the outlet sensor.

Shorted The outlet sensor wires or the sensor itself has become shorted.

Press the Next arrow key on the SMART SYSTEM display to access Screen #2.

IN: ***.*F If the inlet sensor has not been selected as the control sensor, only the inlet temperature will be displayed.

***.*F (***) When the inlet sensor has been selected as the control sensor, the control will display the inlet temperature as well as the set point in parenthesis.

#2

Open The control does not detect the inlet sensor.

Shorted The inlet sensor wires or the sensor itself has become shorted.

RISE: ***.*F The difference between the inlet temperature and the outlet temperature.

Press the Next arrow key on the SMART SYSTEM display to access Screen #3.

Set Point Met · Postpurge

Page 16 of the Lochinvar 80 - 285 user manual — #6
Page 16 · click to enlarge
Page 16

Status Display Screens (cont’d)

By using the Previous/Next (◁, ) arrow keys on the SMART SYSTEM display panel, you can navigate through the eight (8) display screens. Each screen will contain two (2) viewable items. The following is a description of the individual items and what they can display:

Screen Display shows: Description

SYS: ***.*F If the system supply sensor has not been selected as the control sensor, only the system temperature will be displayed.

***.*F (***) When the system supply sensor has been selected as the control sensor, the control will display the system temperature as well as the set point in parenthesis.

Open The control does not detect the system supply sensor.

#3

Shorted The system supply sensor wires or the sensor itself has become shorted.

OUTDOOR: ***.*F The control will display the outdoor air temperature as sensed by the outdoor air sensor.

Open The control does not detect the outdoor air sensor.

Shorted The outdoor air sensor wires or the sensor itself has become shorted.

Press the Next arrow key on the SMART SYSTEM display to access Screen #4.

FLUE: ***.*F The control will display the flue temperature.

Open The control does not detect the flue sensor.

Shorted The flue sensor wires or the sensor itself has become shorted.

#4

AUX: ***.*F The control will display the temperature.

Open The control does not detect the auxiliary sensor.

Shorted The auxiliary sensor wires or the sensor itself has become shorted.

Press the Next arrow key on the SMART SYSTEM display to access Screen #5.

FAN SPD: ****RPM The control will display the actual fan motor RPM.

#5

FLAME SIG: **.*uA The control will display the flame signal in dc microamps.

Press the Next arrow key on the SMART SYSTEM display to access Screen #6.

SH CFH: OFF The control has not received a call for heat from a remote thermostat.

ON The control has received a call for heat from a remote thermostat.

#6

DHW CFH: OFF The control has not received a call for heat from a SH remote thermostat.

ON The control has received a call for heat from a DHW thermostat.

Press the Next arrow key on the SMART SYSTEM display to access Screen #7.

Page 17 of the Lochinvar 80 - 285 user manual — ON
Page 17 · click to enlarge
Page 17

4 SMART SYSTEM control module (continued)

Status Display Screens (cont’d)

By using the Previous/Next (◁, ) arrow keys on the SMART SYSTEM display panel, you can navigate through the eight (8) display screens. Each screen will contain two (2) viewable items. The following is a description of the individual items and what they can display:

Screen Display shows: Description

DHW PUMP: OFF The control has not received a DHW call for heat and has not powered the DHW pump.

ON The control has received a DHW call for heat and has powered the DHW pump.

#7

Delay The DHW call for heat has been satisfied and the DHW pump is running for a fixed time to remove any residual heat.

0-10V IN: **.Vdc The control will display a 0-10Vdc signal received from a Building Management System (BMS) connected to the unit.

Press the Next arrow key on the SMART SYSTEM display to access Screen #8.

SYS PUMP: OFF The control has not received a call for heat from a remote thermostat and has not powered the system pump.

ON The control has received a call for heat from a remote thermostat and has powered the system pump.

Delay The system call for heat has been satisfied and the system pump is running for a fixed time to remove any residual heat.

The control has either not received a call for heat from a remote thermostat, a remote thermostat is not connected to the unit and the water temperature has not dropped below the temperature set point of the control to initiate a call for heat, or the control has received a DHW call for heat from a DHW thermostat.

#8

BLR PUMP: OFF

The control has received a call for heat from a remote thermostat or a remote thermostat is not connected and the water temperature has dropped below the temperature set point of the control to initiate a call for heat.

ON

Delay The call for heat has been satisfied and the boiler pump is running for a fixed time to remove any residual heat.

Press the Next arrow key on the SMART SYSTEM display to access Screen #9.

Page 18 of the Lochinvar 80 - 285 user manual — #10
Page 18 · click to enlarge
Page 18

Status Display Screens (cont’d)

Operation of the cascade

The boiler designated as the Leader will have two additional display screens that can be viewed. These screens will provide information regarding the operation of the Cascade. Each screen will contain two viewable items. The following is a description of the individual items and what they can display:

Screen Display shows: Description

Cas: Off The Leader control has been turned off by the Enter/Reset button on the Smart System display.

Cas: Standby The Leader boiler has not received a call for heat from a remote thermostat.

Cas: 127.4F (130) The Cascade is now active. The system supply temperature will be displayed. The Cascade set point will be displayed in parenthesis.

Cas: Setpoint Met The Cascade has met the water temperature set point, but is still receiving a call for heat from a remote thermostat.

Cas: No Members The Leader control could not detect any Member controls to participate in the Cascade.

#9

Cas: S6 Not Present The system supply sensor is not connected to the Leader boiler.

PMP: Off The Leader control has not received a call for heat from a remote thermostat and has not powered the system pump.

PMP: On The Leader control has received a call for heat from a remote thermostat and has powered the system pump.

PMP: Delay The system call for heat has been satisfied and the system pump is running for a fixed time to remove any residual heat.

Press the Next arrow key on the SMART SYSTEM display to access Screen #10.

The first percentage shows the firing rate that is being sent to the last boiler called on. The second percentage shows the total power available to the Cascade.

Cas Pow***% ***%

Shows the number of boilers connected to the Cascade. The Leader is designated as 0. Members will be designated 1 - 7. If a “-“ is used in place of a number, that boiler is either not connected, or in a lockout mode and not available for the Cascade. If a “d” is used in place of a number, that boiler is handling a DHW demand and is not available for the Cascade. If the number is flashing, then that boiler is providing heat to the Cascade. As the lead boiler is changed from day to day, that boiler’s address will be shown first in the string of numbers. In the example, boilers 0 - 3 are present, boiler 2 is the lead boiler, and boiler 0 is heating an indirect DHW tank.

Present01234567

#10

ExamplePresent: 23----d1

Press the Next arrow key on the SMART SYSTEM display to roll back to Screen #1. At any point if you wish to access an earlier screen, press the Previous ◁arrow key on the SMART SYSTEM display.

Page 19 of the Lochinvar 80 - 285 user manual — Notes
Page 19 · click to enlarge
Page 19

Notes

Page 20 of the Lochinvar 80 - 285 user manual — Notes
Page 20 · click to enlarge
Page 20
Lochinvar 80 - 285 — Notes diagram (page 20)
Fig. 8 · Notes

Revision Notes: Revision 3 (KB-USER-03) reflects the addition of the Dungs information to the manual.

Revision 4 (ECO #C02545) reflects changes made to the “Check Air Piping” section on page 6 along with the removal of Models 399 - 500 and the addition of references to periodic cleaning of screens in vent terminations.

Revision 5 (ECO #C02940) reflects changing 0° to 32°F under the Night Setback Times section on page 13. KB-USER-05

Display codes

Error codes

What the fault codes shown on the display mean and how to clear them.

CodeMeaningFix
B1The temperature range of this parameter is 50°F to 190°F. p.13

Ask about the Lochinvar 80 - 285

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Lochinvar 80 - 285

Be the first to ask — other owners or our team will answer.

Original document

Lochinvar 80 - 285 manual PDF

20 pages·829 KB·Boiler·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…