If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life. This appliance MUST NOT be installed in any location where gasoline or flammable vapors are likely to be present.


Save this manual for future reference.
WB-USER Rev D


The Knight Wall Mount Installation and Operation Manual along with the Knight Wall Mount Service Manual are for use only by a qualified heating installer/service technician. Refer only to this User’s Information Manual for your reference. Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury (exposure to hazardous materials) or loss of life. Installation and service must be performed by a qualified installer, service agency or the gas supplier (who must read and follow the supplied instruction before installing, servicing, or removing this boiler. This boiler contains materials that have been identified as carcinogenic, or possibly carcinogenic, to humans).
NOTICE
When calling or writing about the boiler – Please have the boiler model and serial number from the boiler rating plate.
Consider piping and installation when determining boiler location.
Any claims for damage or shortage in shipment must be filed immediately against the transportation company by the consignee.
Factory warranty (shipped with unit) does not apply to units improperly installed or improperly operated.
Failure to adhere to the guidelines on this page can result in severe personal injury, death, or substantial property damage.

Table 1A Corrosive Contaminants and Sources WARNING If the boiler combustion air inlet is located
in any area likely to cause contamination, or if products which would contaminate the air cannot be removed, you must have the combustion air and vent re-piped and terminated to another location. Contaminated combustion air will damage the boiler, resulting in possible severe personal injury, death, or substantial property damage.
Products to avoid:
Spray cans containing chloro/fluorocarbons
Chlorine-based swimming pool chemicals
Calcium chloride used for thawing
If the boiler combustion air inlet is located in a laundry room or pool facility, for example, these areas will always contain hazardous contaminants.
Sodium chloride used for water softening
Pool and laundry products and common household and hobby products often contain fluorine or chlorine compounds. When these chemicals pass through the boiler, they can form strong acids. The acid can eat through the boiler wall, causing serious damage and presenting a possible threat of flue gas spillage or boiler water leakage into the building.
Paint or varnish removers
Antistatic fabric softeners used in clothes dryers
Chlorine-type bleaches, detergents, and cleaning solvents found in household laundry rooms Adhesives used to fasten building products and other similar products
Please read the information listed in Table 1A. If contaminating chemicals will be present near the location of the boiler combustion air inlet, have your installer pipe the boiler combustion air and vent to another location, per the Knight Wall Mount Installation and Operation Manual.
Areas likely to have contaminants
Dry cleaning/laundry areas and establishments
To prevent the potential of severe personal injury or death, check for areas and products listed in Table 1A before installing the boiler or air inlet piping.
If contaminants are found, you MUST:
Furniture refinishing areas and establishments

(see the Knight Wall Mount Service Manual)
WARNING Follow the maintenance procedures given throughout this manual. Failure to perform the service and maintenance or follow the directions in this manual could result in damage to the boiler or system, resulting in severe personal injury, death, or substantial property damage.

Read the list of potential materials listed in Table 1A on page 4 of this manual. If any of these products are in the room from which the boiler takes its combustion air, they must be removed immediately or the boiler combustion air (and vent termination) must be relocated to another area.
Boiler must be serviced and maintained
WARNING The boiler must be inspected and started
annually at the beginning of the heating season by a qualified service technician. In addition, the maintenance and care of the boiler designated on page 5 of this manual and explained on pages 6 through 8 must be performed to assure maximum boiler efficiency and reliability. Failure to service and maintain the boiler and system could result in equipment failure, causing possible severe personal injury, death, or substantial property damage.
WARNING Failure to inspect the vent system as noted
above and have it repaired by a qualified service technician can result in vent system failure, causing severe personal injury or death. Check air piping
WARNING To prevent potential of severe personal
injury, death, or substantial property damage, eliminate all materials discussed below from the boiler vicinity and the vicinity of the boiler combustion air inlet. If contaminants are found:
Remove products immediately from the area. If they have been there for an extended period, call a qualified service technician to inspect the boiler for possible damage from acid corrosion.
If products cannot be removed, immediately call a qualified service technician to re-pipe vent and air piping and locate vent termination/air intake away from contaminated areas.
Check condensate drain system
Fill condensate trap with water

Use materials approved by the authority having jurisdiction. In the absence of other authority, PVC and CPVC pipe must comply with ASTM D1785 or D2845. Cement and primer must comply with ASME D2564 or F493. For Canada use CSA or ULC certified PVC or CPVC pipe, fittings, and cement.
WARNING The condensate trap (FIG. 2-1) must be
filled with water during all times of boiler operation to avoid flue gas emission from the condensate drain line. Failure to fill the trap could result in severe personal injury or death.
Figure 2-1 Condensate Trap
The condensate line must remain unobstructed, allowing free flow of condensate. If condensate is allowed to freeze in the line or if the line is obstructed in any other manner, condensate can exit from the boiler tee, resulting in potential water damage to property. Call your qualified service technician to inspect the boiler and system.


A Neutralizer Kit is available from the factory (Kit #3087). Call your qualified service technician to install.
Condensate disposal

WARNING Have leaks fixed at once by a qualified
service technician. Failure to comply could result in severe personal injury, death, or substantial property damage.
Figure 2-3 Air Vent
WARNING To avoid water damage or scalding due to

valve operation, a metal discharge line must be connected to the relief valve outlet and run to a safe place of disposal. This discharge line must be installed by a qualified heating installer or service technician in accordance with the instructions in the Knight Wall Mount Installation and Operation Manual. The discharge line must be terminated so as to eliminate possibility of severe burns or property damage should the valve discharge.
Test low water cutoff (if installed)
Reset button (low water cutoff)
Check boiler piping (gas and water)
Shut boiler down (unless boiler is used for Domestic Water)
Check air vents · Operate relief valve



Use the control panel (FIG. 4-1) to set temperatures, operating conditions, and monitor boiler operation.
Figure 4-1 Control Panel


The user can adjust space heating target temperature by using the UP and DOWN buttons (FIG. 4-1) at any time during normal operation. By entering the USER code (0704), the user can also change temperature units, time and date, and night setback settings. In User Mode, the following parameters can be viewed but not changed:
Most parameters are available only to the installer, accessible only by entering the installer access code. Have your qualified service technician reference the Knight Wall Mount Service Manual.
Saving parameters (reference parameter table on page 13 of this manual)
To save parameters and exit programming:
Press the ENTER/RESET button (FIG. 4-1).
To keep parameter settings only for a current operating cycle:
Press the MENU/EXIT button (FIG. 4-1) 3 times after making all desired parameter changes.
To enter a parameter and continue programming:
Press the MENU/EXIT button 1 time to return to the parameter listings; press again to return to the menu listings. Remember to press the ENTER/RESET button when finished programming in order to save the changes made.
Have your qualified service technician reference the Knight Wall Mount Service Manual for a detailed description of parameters and access modes.
Access modes · User · Installer


B 1 SH Set Point User 14 Yes

A: General
If parameter A6 is set to anything other than 32°F, the night setback feature becomes active. This will require start and stop times to be programmed for the days that reduced temperatures are required. These times can be changed by the user or the installer by accessing parameter A7. Each day of the week (Sunday through Saturday) will have an on and off time.
The control will display “Knight Boiler” as the model number because the same control is used on several models. This will be displayed when parameter A1 has been accessed. This parameter is not changeable.
Example: Monday ON: 22:30, Tuesday OFF: 6:45. If you wish to skip a day and have no night setback, leave the on and off times the same. The default times for each day will be 00:00 (midnight).
The User Code allows the user to access and change a limited number of control parameters. The access code can be changed by the user or the installer to a code of their choosing. To change the code, parameter A2 must be accessed. The default code is 0704. The code can be changed one digit at a time by using the arrow keys on the display.
B: Temperature settings
SH set point user
The SH set point user sets the water temperature set point for fixed operation or the maximum temperature set point when the outdoor air sensor is used. This parameter can be changed by the user or the installer by accessing parameter B1. The temperature range of this parameter is 50°F to 190°F. The default value is 125°F.
The control uses an internal clock for the night setback feature and for logging of events. For these features to work correctly, the clock must be set when the boiler is first installed or anytime the boiler has been powered off for more than 30 days. To set the clock, parameter A3 must be accessed. The date and time are displayed as “YY:MM:DD W hh:mm”. YY = year, MM = month, DD = date, W = day (1 = Sunday, 2 = Monday, etc.), hh = hour (24 hour time; 2:00 PM = 14:00), mm = minutes.
C: Data logging
The hours running SH parameter shows the total number of hours the boiler has been in the SH firing position. This parameter can be viewed by the user and the installer by accessing parameter C1.
The software version allows the user to view the software version in use by the control. This software controls the operation of the boiler. When a new software version becomes available, the existing control can be replaced with a new control to update the software.
The hours running DHW parameter shows the total number of hours the boiler has been in the DHW firing position. This parameter can be viewed by the user and the installer by accessing parameter C2.
The control can be configured to display temperature in either °C or °F. This parameter can be changed by the user or the installer by accessing parameter A5. The default is °F.
The ignition attempts parameter shows the total number of times the boiler has attempted to fire. This parameter can be viewed by the user and the installer by accessing parameter C3.
Once the internal clock has been set correctly, the night setback feature can be used to program a lower water temperature set point for space heating. This parameter can be changed by the user or the installer by accessing parameter A6. The temperature range for this parameter is 32°F to 140°F. The feature is turned off with a setting of 32°F. The default value is 32°F.
Show last 10 errors
The control will log the 10 most current errors with the date and time the error occurred. This parameter can be viewed by the user and the installer by accessing parameter C4.

E: DHW settings
If a SH demand lasts longer than the programmed time delay setting and there have been no DHW demands, the control will increase the water temperature set point by the amount in this parameter. If the SH demand continues through another time period, the set point will be increased again. This will continue until either the SH demand ends, a maximum of 20 increases has occurred, or the maximum set point has been reached. Once the SH demand has been satisfied the set point will revert back to its calculated setting. The boost temperature can be changed by the installer by accessing parameter F8. The temperature range of this parameter is 0°F to 45°F. The default value is 0°F. This feature will be active if this parameter is set to anything other than 0°F.
DHW boiler set point
When a DHW call for heat becomes active, the control will use the DHW boiler set point to determine the firing rate of the boiler based on the actual water temperature. This parameter can be changed by the installer by accessing parameter E1. The temperature range of this parameter is 50°F to 190°F. The default value is 180°F.
The SH/DHW switching time parameter sets the length of time the control will stay in DHW Mode when a SH call has been received. After this time period has expired the control will revert to SH Mode. If a DHW call is still active the timer will reset. After the time period has expired the control will revert back to DHW Mode. This will continue until one of the demands has been satisfied. This parameter can be changed by the installer by accessing parameter E2. The time range of this parameter is 10 minutes to 240 minutes. The default value is 30 minutes.
The boost time parameter sets the amount of time that must elapse with a SH demand before the water temperature set point will be increased. This parameter can be changed by the installer by accessing parameter F9. The time range for this parameter is 1 minute to 60 minutes. The default value is 20 minutes.
F: Outdoor air reset
When the outdoor air shutdown rises above this point, the control will block all SH demands (DHW demands will still be active). This parameter can be changed by the user or the installer by accessing parameter F5. The temperature range of this parameter is 0°F to 120°F. The default value is 80°F.
Outdoor air shutdown differential
The outdoor air shutdown differential parameter is the number of degrees below parameter F5 the outdoor air temperature must go before the boiler will respond to a SH demand. This parameter can be changed by the user or the installer by accessing parameter F6. The temperature range of this parameter is 0°F to 90°F. The default value is 10°F.

By using the Previous/Next (◁, ) arrow keys on the SMART SYSTEM display panel, you can navigate through the eight (8) display screens. Each screen will contain two (2) viewable items. The following is a description of the individual items and what they can display:
BLR: OFF The unit has been turned OFF by the Enter/Reset button on the SMART SYSTEM display panel.
Standby The unit has not received a call for heat from a remote thermostat nor has it received a call for heat from a DHW thermostat.
The unit has met the water temperature set point, but is still receiving a call for heat from either a remote thermostat or a DHW thermostat.
Prepurge The unit has initiated a 10 second purge period on a call for heat.
Ignition The unit has begun a 5 second spark period to ignite the main burner.
Run***% Rate The unit has fired and is running at the displayed percentage.
The call for heat has been satisfied and the unit runs the fan for an additional 10 seconds to clear the combustion chamber and vent system of residual flue products.
Service The unit has been placed in a temporary mode that will allow the unit to fire at 100% of rate for the purpose of combustion analysis.
When the outlet sensor has been selected as the control sensor (default), the control will display the outlet temperature as well as the set point in parenthesis.
***.*F If the outlet sensor has not been selected as the control sensor, only the outlet temperature will be displayed.
Open The control does not detect the outlet sensor.
Shorted The outlet sensor wires or the sensor itself has become shorted.
Press the Next arrow key on the SMART SYSTEM display to access Screen #2.
IN: ***.*F If the inlet sensor has not been selected as the control sensor, only the inlet temperature will be displayed.
***.*F (***) When the inlet sensor has been selected as the control sensor, the control will display the inlet temperature as well as the set point in parenthesis.
Open The control does not detect the inlet sensor.
Shorted The inlet sensor wires or the sensor itself has become shorted.
RISE: ***.*F The difference between the inlet temperature and the outlet temperature.
Press the Next arrow key on the SMART SYSTEM display to access Screen #3.
Set Point Met · Postpurge

By using the Previous/Next (◁, ) arrow keys on the SMART SYSTEM display panel, you can navigate through the eight (8) display screens. Each screen will contain two (2) viewable items. The following is a description of the individual items and what they can display:
SYS: ***.*F If the system supply sensor has not been selected as the control sensor, only the system temperature will be displayed.
***.*F (***) When the system supply sensor has been selected as the control sensor, the control will display the system temperature as well as the set point in parenthesis.
Open The control does not detect the system supply sensor.
Shorted The system supply sensor wires or the sensor itself has become grounded.
OUTDOOR: ***.*F The control will display the outdoor air temperature as sensed by the outdoor air sensor.
Open The control does not detect the outdoor air sensor.
Shorted The outdoor air sensor wires or the sensor itself has become shorted.
Press the Next arrow key on the SMART SYSTEM display to access Screen #4.
FLUE: ***.*F The control will display the flue temperature.
Open The control does not detect the flue sensor.
Shorted The flue sensor wires or the sensor itself has become shorted.
AUX: ***.*F The control will display the temperature.
Open The control does not detect the auxiliary sensor.
Shorted The auxiliary sensor wires or the sensor itself has become shorted.
Press the Next arrow key on the SMART SYSTEM display to access Screen #5.
FAN SPD: ****RPM The control will display the actual fan motor RPM.
FLAME SIG: **.*uA The control will display the flame signal in dc microamps.
Press the Next arrow key on the SMART SYSTEM display to access Screen #6.
SH CFH: OFF The control has not received a call for heat from a remote thermostat.
ON The control has received a call for heat from a remote thermostat.
DHW CFH: OFF The control has not received a call for heat from a SH remote thermostat.
ON The control has received a call for heat from a DHW thermostat.
Press the Next arrow key on the SMART SYSTEM display to access Screen #7.

By using the Previous/Next (◁, ) arrow keys on the SMART SYSTEM display panel, you can navigate through the eight (8) display screens. Each screen will contain two (2) viewable items. The following is a description of the individual items and what they can display:
DHW PUMP: OFF The control has not received a DHW call for heat and has not powered the DHW pump.
ON The control has received a DHW call for heat and has powered the DHW pump.
Delay The DHW call for heat has been satisfied and the DHW pump is running for a fixed time to remove any residual heat.
0-10V IN: **.Vdc The control will display a 0-10Vdc signal received from a Building Management System (BMS) connected to the unit.
Press the Next arrow key on the SMART SYSTEM display to access Screen #8.
SYS PUMP: OFF The control has not received a call for heat from a remote thermostat and has not powered the system pump.
ON The control has received a call for heat from a remote thermostat and has powered the system pump.
Delay The system call for heat has been satisfied and the system pump is running for a fixed time to remove any residual heat.
The control has either not received a call for heat from a remote thermostat, a remote thermostat is not connected to the unit and the water temperature has not dropped below the temperature set point of the control to initiate a call for heat, or the control has received a DHW call for heat from a DHW thermostat.
The control has received a call for heat from a remote thermostat or a remote thermostat is not connected and the water temperature has dropped below the temperature set point of the control to initiate a call for heat.
Delay The call for heat has been satisfied and the boiler pump is running for a fixed time to remove any residual heat.
Press the Next arrow key on the SMART SYSTEM display to access Screen #9.

Operation of the cascade
The boiler designated as the Leader will have two additional display screens that can be viewed. These screens will provide information regarding the operation of the Cascade. Each screen will contain two viewable items. The following is a description of the individual items and what they can display:
Cas: Off The Leader control has been turned off by the Enter/Reset button on the Smart System display.
Cas: Standby The Leader boiler has not received a call for heat from a remote thermostat.
Cas: 127.4F (130) The Cascade is now active. The system supply temperature will be displayed. The Cascade set point will be displayed in parenthesis.
Cas: Setpoint Met The Cascade has met the water temperature set point, but is still receiving a call for heat from a remote thermostat.
Cas: No Members The Leader control could not detect any Member controls to participate in the Cascade.
Cas: S6 Not Present The system supply sensor is not connected to the Leader boiler.
PMP: Off The Leader control has not received a call for heat from a remote thermostat and has not powered the system pump.
PMP: On The Leader control has received a call for heat from a remote thermostat and has powered the system pump.
PMP: Delay The system call for heat has been satisfied and the system pump is running for a fixed time to remove any residual heat.
Press the Next arrow key on the SMART SYSTEM display to access Screen #10.
The first percentage shows the firing rate that is being sent to the last boiler called on. The second percentage shows the total power available to the Cascade.
Shows the number of boilers connected to the Cascade. The Leader is designated as 0. Members will be designated 1 - 7. If a “-“ is used in place of a number, that boiler is either not connected, or in a lockout mode and not available for the Cascade. If a “d” is used in place of a number, that boiler is handling a DHW demand and is not available for the Cascade. If the number is flashing, then that boiler is providing heat to the Cascade. As the lead boiler is changed from day to day, that boiler’s address will be shown first in the string of numbers. In the example, boilers 0 - 3 are present, boiler 2 is the lead boiler, and boiler 0 is heating an indirect DHW tank.
Press the Next arrow key on the SMART SYSTEM display to roll back to Screen #1. At any point if you wish to access an earlier screen, press the Previous ◁arrow key on the SMART SYSTEM display.



Revision Notes: Revision B (ECO #C02545) reflects changes made to the “Check Air Piping” section on page 6 along with the addition of references to periodic cleaning of screens in vent terminations.
Revision C (ECO #C02940) reflects changing 0° to 32°F under the Night Setback Times section on page 13.
Revision D (ECO #C05672) reflects the change from automatic air vent to manual air vent. The chart on page 5 was updated and a new image of the air vent valve was inserted on page 8 (FIG. 3).
What the fault codes shown on the display mean and how to clear them.
| Code | Meaning | Fix | |
|---|---|---|---|
| B1 | The temperature range of this parameter is 50°F to 190°F. | p.13 |