This manual must only be used by a qualified heating installer / service technician. Read all instructions, including this manual and the Knight XL Installation and Operation Manual, before installing. Perform steps in the order given. Failure to comply could result in severe personal injury, death, or substantial property damage.
Save this manual for future reference.
KBXII-SER Rev C


Installer – Read all instructions, including this manual and the Knight XL Installation and Operation Manual, before installing. Perform steps in the order given.
When calling or writing about the boiler – Please have the boiler model and serial number from the boiler rating plate.
Consider piping and installation when determining boiler location (see the Knight XL Installation and Operation Manual).
User – This manual is for use only by a qualified heating installer/service technician. Refer to the Knight XL User’s Information Manual for your reference.
Any claims for damage or shortage in shipment must be filed immediately against the transportation company by the consignee.
Have this boiler serviced/inspected by a qualified service technician at least annually.
Failure to comply with the above could result in severe personal injury, death or substantial property damage.
The combustion chamber insulation in this appliance contains ceramic fiber material. Ceramic fibers can be converted to cristobalite in very high temperature applications. The International Agency for Research on Cancer (IARC) has concluded, “Crystalline silica inhaled in the form of quartz or cristobalite from occupational sources is carcinogenic to humans (Group 1).” Normal operating temperatures in this appliance are below the level to convert ceramic fibers to cristobalite. Abnormal operating conditions would have to be created to convert the ceramic fibers in this appliance to cristobalite.
The ceramic fiber material used in this appliance is an irritant; when handling or replacing the ceramic materials it is advisable that the installer follow these safety guidelines.
Avoid breathing dust and contact with skin and eyes. • Use NIOSH certified dust respirator (N95). This type of respirator is based on the OSHA requirements for cristobalite at the time this document was written. Other types of respirators may be needed depending on the job site conditions. Current NIOSH recommendations can be found on the NIOSH website at http://www.cdc.gov/niosh/homepage.html NIOSH approved respirators, manufacturers, and phone numbers are also listed on this website.
Apply enough water to the combustion chamber lining to prevent airborne dust.
Remove the combustion chamber lining from the appliance and place it in a plastic bag for disposal.
Wash potentially contaminated clothes separately from other clothing. Rinse clothes washer thoroughly.
NIOSH stated First Aid.
Eye: Irrigate immediately. Breathing: Fresh air.


Near boiler piping • Typical system components
The Knight XL display • Display panel readout, buttons and their functions
Control module inputs • Control module inputs and options
Control module outputs • Control module outputs and options
Control panel menu access • Accessing programming mode and locating menus (See separate guide covering the interface.)
Control panel parameter access • Accessing and changing parameters from the display panel
Quick start information -- parameter table • An index of available adjustments and readouts, where to access them and where to find detailed information.

This piping reference is included to specify the Near Boiler Piping specific to the Knight XL. This piping scheme is important for proper operation of the SMART SYSTEM control. See the Knight XL Installation and Operation Manual for more detailed piping diagrams.



The information on the bottom of the display shows the functions of the two SELECT keys (on either corner), and the NAVIGATION dial (in the center):
MENU = Left SELECT Key SETPOINTS = NAVIGATION Dial - Pressing Down SHDN = Right SELECT Key





How the boiler operates
The Knight XL uses an advanced stainless steel heat exchanger and an electronic control module that allows fully condensing operation. The blower pulls in gas and air and pushes flue products out of the boiler through the heat exchanger and flue piping. The control module regulates blower speed to control boiler firing rate. The gas valve senses the amount of air flowing into the boiler and allows only the right amount of gas to flow.
The user can adjust space heating and tank target temperatures by pressing the NAVIGATION dial when “SETPOINTS” is flashing at the bottom of the display. The date and time, and the temperature units can also be changed.
Most parameters are available only to the installer, accessible by entering the installer password (5309).
How the control module operates
Saving parameters (reference the Parameter Table - Table 1-4 on pages 15 - 18 of this manual)
The Knight XL control module receives input from boiler sensors. The control module activates and controls the blower and gas valve to regulate heat input and switches boiler, DHW and system pumps on and off as needed. The user/installer programs the module to meet system needs by adjusting control parameters. These parameters set operating temperatures and boiler operating modes. Boiler operation can be based on boiler outlet water temperature, boiler return water temperature or system supply temperature, depending on the parameter setting.
Please note that the brackets ([]) denote screen status. NOTICE
To save parameters and exit programming:
Press the RIGHT SELECT [SAVE] key and then press the RIGHT SELECT [HOME] key.
To enter a parameter and continue programming:
Press the RIGHT SELECT [SAVE] key 1 time to return to the parameter listings; press again to return to the menu listings. Remember to press the RIGHT SELECT [HOME] key when finished programming in order to save the changes made.
Table 1-1 shows control module normal sequences of operation for space heating and DHW operation. The combined operation sequence is for a typical application, programmed to provide DHW priority.

Table 1-1 Sequence of Operation






Table 1-1 (continued from previous page) Sequence of Operation






Table 1-2 Use this procedure to access menus from the display panel

[MENU] Press and hold the LEFT SELECT soft key [MENU] for five (5) seconds.
Rotate the NAVIGATION dial clockwise until 5 is displayed (first digit on the left).
Press the NAVIGATION dial to select the next digit. Rotate the NAVIGATION dial clockwise until 3 is shown in the display.
Press the NAVIGATION dial 2 times to move to the last digit. Rotate the NAVIGATION dial counterclockwise until 9 is displayed.
Rotate the NAVIGATION dial counterclockwise to select a category.

Table 1-3 This is a typical example of accessing a parameter, shown for parameter Temperature Settings, MIN SH Setpt

This example shows how to access parameter Temperature Settings. The first display shown is at the beginning of the menu listings, after entering the installer access code.
Rotate the NAVIGATION dial counterclockwise until the arrow (>) is next to TEMPERATURE SETTINGS.
Rotate the NAVIGATION dial counterclockwise until the arrow (>) is next to MIN SETPT.
[SAVE] Press the RIGHT SELECT soft key [SAVE] one time.
[EXIT] Press the LEFT SELECT soft key [EXIT] if all desired changes have been made.

Table 1-4 This table lists SMART SYSTEM control module parameters and where to access them

Software Version (read only) 19 No No Yes No
SH Night Setback Offset 19 No No Yes Yes
SH Night Setback On Times 19 No No Yes Yes
SH Night Setback Off Times 19 No No Yes Yes
DHW Night Setback Offset 19 No No Yes Yes
DHW Night Setback On Times 19 No No Yes Yes
DHW Night Setback Off Times 19 No No Yes Yes
Minimum SH Set Point 20 No No Yes Yes
Maximum SH Set Point 20 No No Yes Yes
Freeze Protection Pump On 20 No No Yes Yes
Freeze Protection Burner On 20 No No Yes Yes
Freeze Protection Burner Differential 20 No No Yes Yes

Table 1-4 (continued from previous page) This table lists SMART SYSTEM control module parameters and where to access them

DHW Boiler Set Point 21 No No Yes Yes
Tank Set Point Differential 21 No No Yes Yes
Tank Minimum Set Point 21 No No Yes Yes
Tank Maximum Set Point 21 No No Yes Yes
Fan Speed Limiting for DHW 21 No No Yes Yes
Set Point 1 at Low Outdoor Temp 1 22 No No Yes Yes
Set Point 1 at High Outdoor Temp 1 22 No No Yes Yes
Outdoor Air Shutdown SH1 22 No No Yes Yes
Outdoor Air Shutdown Differential SH1 23 No No Yes Yes
Shift Reset Curve SH1 23 No No Yes Yes
Set Point 2 at Low Outdoor Temp 2 22 No No Yes Yes
Set Point 2 at High Outdoor Temp 2 22 No No Yes Yes
Outdoor Air Shutdown SH2 22 No No Yes Yes
Outdoor Air Shutdown Differential SH2 23 No No Yes Yes
Shift Reset Curve SH2 23 No No Yes Yes
Set Point 3 at Low Outdoor Temp 3 22 No No Yes Yes
Set Point 3 at High Outdoor Temp 3 22 No No Yes Yes
Outdoor Air Shutdown SH3 22 No No Yes Yes
Outdoor Air Shutdown Differential SH3 23 No No Yes Yes
Shift Reset Curve SH3 23 No No Yes Yes

Table 1-4 (continued from previous page) This table lists SMART SYSTEM control module parameters and where to access them

Max Cascade Set Point 25 No No Yes Yes
Min Next On Time 25 No No Yes Yes
Boiler Pump Anti-Seize Delay 26 No No Yes Yes
Boiler Pump Min Voltage 26 No No Yes Yes
DHW Pump Anti-Seize Delay 26 No No Yes Yes
System Pump Anti-Seize Delay 26 No No Yes Yes

Table 1-4 (continued from previous page) This table lists SMART SYSTEM control module parameters and where to access them

Rate at Min Volts 26 No No Yes Yes
Rate at Max Volts 26 No No Yes Yes
Set Point at Min Volts 27 No No Yes Yes
Set Point at Max Volts 27 No No Yes Yes
Service Notification Running Time 27 No No Yes Yes
Service Name and Phone Number 27 No No Yes Yes

Space Heating (SH) and Domestic Hot Water (DHW) Night Setback On Times
This is the time in which the SH Night Setback Offset becomes active. There are 7 start times and 7 stop times each for the space heating and DHW night setback features. Both may be set to any time within a 7-day week. These settings are referred to as triggers. Multiple start or stop triggers may be set within a single day, if desired. When a start trigger and a stop trigger are set to the same time, the stop trigger has priority. The installer may adjust the space heating night setback start triggers by accessing the SH Night Setback On Times parameter. The DHW start triggers in the DHW Night Setback On Times parameter. This screen shows the start trigger number, the day of the week, and the time of day.
The control uses an internal clock for the night setback feature and for logging of events. For these features to work correctly, the clock must be set when the boiler is first installed or anytime the boiler has been powered off for more than four (4) hours. This parameter must be accessed to set the clock.
1. When the screen is first accessed, start trigger number 1 is shown. If a different trigger number is desired, the installer can rotate the NAVIGATION dial until the desired trigger number is displayed. Once the desired trigger number is selected, the installer can press the NAVIGATION dial and the day of the week will start to flash. 2. The installer can adjust the day of the week to the one he wishes to set. Once the day is set, the installer can press the NAVIGATION dial and the hour will begin to flash. 3. After setting the hour, the installer can press the NAVIGATION dial and the minutes will flash. Once all settings have been made, the installer can press the RIGHT SELECT [SAVE] key. The installer can now select a different trigger and adjust the settings for that trigger. 4. Once all adjustments are made, the installer can press the RIGHT SELECT [SAVE] key to save all of the new settings and return to the General menu, or press the LEFT SELECT [EXIT] key to return to the General menu without saving the changes.
The software version allows the user to view the software version in use by the control. This software controls the operation of the boiler. When a new software version becomes available, the existing control can be replaced with a new control to update the software.
Software version is read only.
Temperature units (°C / °F)
The control can be configured to display temperature in either °C or °F. This parameter can be changed by the user or the installer by accessing the Temperature Units parameter. The default is °F.
Space Heating (SH) and Domestic Hot Water (DHW) Night Setback Offset
Once the unit’s internal clock has been set correctly, the Night Setback feature can be used to program a lower set point during unoccupied times. Both the space heating and DHW can be programmed for night setback. When in night setback, the control reduces the set point by a fixed amount. For space heating, it subtracts the space heating night setback offset from each of the SH user set points (SH1, 2, and 3 Set point parameters), or the calculated outdoor reset set point (if lower). For DHW, it subtracts the DHW night setback offset from the tank set point (Tank Set point parameter).
Space Heating (SH) and Domestic Hot Water (DHW) Night Setback Off Times The corresponding space heating night setback stop triggers are set by accessing the SH Night Setback Off Times parameter. The stop triggers for the DHW night setback feature can be adjusted by accessing the DHW Night Setback Off Times parameter. The adjustment procedure for these parameters is identical to the space heating start triggers described above.
Night Setback Override Any Night Setback On trigger currently active or scheduled within the next seven (7) days can be skipped. To skip a trigger, press the MENU key for 5 seconds, enter the user password, and press the SAVE key. Rotate the NAVIGATION dial to NSB OVERRIDE, and press the NAVIGATION dial. A list of the current (if active) and upcoming NSB On triggers will appear.
The installer may adjust the space heating night setback offset by accessing the SH Night Setback Offset parameter and the DHW night setback offset by accessing the DHW Night Setback Offset parameter. The minimum setting is 0°F (0°C) and the maximum setting is 90°F (50°C).
General · Time and Date · Software Version

Rotate the NAVIGATION dial to select the trigger you wish to skip and press the NAVIGATION dial. “SK” will appear next to that trigger. You can rotate the NAVIGATION dial again to select another trigger if you wish. If you wish to reinstate a skipped trigger, re-select that trigger and press the NAVIGATION dial again. The “SK” next to that trigger will disappear. Press the HOME key to save these skipped triggers. If you selected any currently active trigger(s), the current Night Setback will be cancelled.
SH1 - SH3 Differential Set Point The SH differential sets how many degrees below the offset the temperature has to drop before the boiler turns back on. This parameter can only be changed by the installer by accessing the SH1, 2 and 3 Differential Set point parameters. The range is 0°F to 60°F. The default is 20°F.
Reset log errors The reset log errors function clears the last 10 errors log.
Functions Service Mode Delay By pressing the pin button on the front of the display for five (5) seconds, the control will be placed in Service Mode. This will override all other heat demands. The Service Mode allows the installer to set the unit to any firing rate for the purpose of combustion analysis. The delay sets the length of time the boiler will stay in the Service Mode if no keys have been pressed before going back to its original state. This parameter can only be changed by the installer by accessing the Service Mode Delay parameter. The time range of this parameter is 1 to 10 minutes. The default value is 10 minutes.
This is the time in which the display remains illuminated. The range is 10 seconds to 10 minutes. The default is 3 minutes.
Space Heating (SH1, SH2, SH3) Set Point
There are three (3) individual user set points for better zone control. These are listed as SH1 Set Point through SH3 Set Point. If multiple set points are calling for heat the highest set point has priority. The range is SH Minimum Set point to SH Maximum Set point. The default is 125°F (52°C).
Freeze Protection Pump On The SMART SYSTEM control will turn on the boiler and system pump outputs whenever the inlet temperature drops below this setting. This is done to prevent the water in the heat exchanger from freezing. Certain low-temperature applications (such as snow melt) can operate at temperatures around freezing, so this setting needs to be lowered in these cases. The installer can adjust the temperature at which the pump outputs are turned on by accessing Freeze Protection Pump On parameter. The minimum setting is -3°F (-19°C), and the maximum setting is 45°F (7.2°C). The default setting is 45°F (7.2°C).
Space Heating (SH) Minimum Set Point
The SH minimum set point sets the minimum water temperature set point that can be used for space heating operation. The user or installer will not be able to program the control with a lower SH set point. This parameter can only be changed by the installer by accessing Minimum SH Set point parameter. The temperature range of this parameter is 32°F (0°C) to the space heating maximum set point. The default value is 32°F (21°C).
Space Heating (SH) Maximum Set Point
The SH maximum set point sets the maximum water temperature set point that can be used for space heating. The user or installer will not be able to program the control with a higher SH set point. This parameter can only be changed by the installer by accessing Maximum SH Set point parameter. The temperature range of this parameter is the space heating minimum set point to 180°F (82°C). The default value is 180°F (82°C).
Freeze Protection Burner On If running the pumps does not prevent the inlet temperature from falling closer to freezing, the SMART SYSTEM control will fire the burner at low fire. The installer can adjust the temperature at which the burner fires by adjusting the Freeze Protection Burner On parameter. The minimum setting is -3°F (-19°C), and the maximum setting is 45°F (7.2°C). The default setting is 37°F (2.8°C).
SH1 - SH3 Offset Set Point
The SH offset sets how many degrees above set point the temperature has to go before the boiler will shut off. This parameter can only be changed by the installer by accessing parameters SH1, 2 and 3 Offset Set point parameters. The temperature range of these parameters is 0°F to 20°F. The default value is 10°F.
Freeze Protection Burner Differential Once the burner has started firing due to a low inlet temperature, the inlet temperature must increase by this amount before the burner turns back off. The installer can adjust this differential by accessing the Freeze Protection Burner Differential parameter. The minimum setting is 0°F, and the maximum is 20°F. The default setting is 5°F (2.8°C).
Data Logging · Display Timeout · Temperature Settings

DHW Boiler Set Point
When a boiler has a DHW demand and it receives a space heating demand, the SMART SYSTEM control will start a timer. Once the timer expires, it will stop the DHW demand and service the space heating demand. The installer can adjust the length of time the boiler will service the DHW demand by accessing the DHW/SW Switching Time parameter. The minimum setting is 0 minutes and the maximum setting is 50 minutes. The default setting is 30 minutes.
When a DHW call for heat becomes active, the control will use the DHW boiler set point to determine the firing rate of the boiler based on the boiler outlet water temperature, or system temperature when DHW is programmed as a zone.
This parameter can be changed by the installer by accessing the DHW Boiler Set point parameter. The temperature range of this parameter is 68°F (20°C) to 180°F (82°C). The default value is 180°F (82°C).
Tank Minimum Set Point
DHW Tank Set Point
This setting controls the minimum tank set point for the tank temperature. The installer can adjust this by accessing the Tank Minimum Set point parameter. The minimum setting is 60°F (16°C) and the maximum setting is the maximum tank set point (Tank Maximum Set point parameter). The default value is 60° (16°C).
By installing a tank sensor, the SMART SYSTEM control can perform the tank thermostat function. The SMART SYSTEM control automatically detects the presence of this sensor, and generates a DHW call for heat when the tank temperature drops below the tank set point differential (Tank Set point Differential parameter), and finishes the call for heat when the tank temperature reaches tank set point + offset. This parameter can be changed by the installer by accessing the DHW Tank Set point parameter. The temperature range of this parameter tank minimum set point to tank maximum set point. The default value is 125°F (52°C).
Tank Maximum Set Point
This setting controls the maximum tank set point for the tank temperature. The installer can adjust this by accessing the Tank Maximum Set point parameter. The minimum setting is the minimum tank set point (Tank Minimum Set point parameter) and the maximum setting is 190°F (88°C). The default value is 140°F (60°C).
Tank Set Point Differential
When a tank sensor is installed, the tank temperature must drop this amount below the tank set point (DHW Tank Set point parameter) before the boiler turns back on. The installer can adjust this setting by accessing the Tank Set point Differential parameter. The minimum setting is 0° (0°C), and the maximum is 40°F (22°C). The default setting is 6°F (3°C).
This parameter determines whether the Knight XL boiler treats the indirect DHW tank as a separate load, or as a zone on the primary loop. When programmed as a separate load, the boiler will turn on the DHW pump and then turn off the boiler pump when an indirect DHW demand begins. When programmed as a zone, the boiler will turn on the DHW pump, leave the boiler pump on and change the system set point to the DHW boiler set point (DHW Boiler Set point parameter).
This parameter reflects the degrees above DHW boiler set point the temperature has to go before the boiler will shut off. The range is 0°F (0°C) to 40°F (22°C). The default setting is 10°F (6°C).
This setting may be changed by the installer by accessing the DHW Type parameter. The choices are NORMAL and ZONE. The default setting is NORMAL.
This parameter reflects the degrees below DHW boiler set point the temperature has to go before the boiler turns back on. The range is 0°F (0°C) to 60°F (33°C). The default setting is 20°F (13°C).
Fan Speed Limiting for Indirect DHW Tank
This parameter determines the maximum fan speed (and therefore the maximum rate) to be used when heating an indirect DHW tank. This setting may be used when the tank is unable to accept all of the BTU’s available from the boiler. This parameter may be adjusted by the installer by accessing the Fan Speed Limiting for Indirect DHW Tank parameter. The default value is the maximum fan speed for that model.
When a boiler has a space heating demand and it receives a DHW demand, it will immediately switch to the DHW demand and start a timer. Once the timer has expired, the boiler will switch back to the space heating demand and start another timer. Once this timer expires, it will switch back to the DHW demand. The installer can adjust the length of time the boiler will service the space heating demand by accessing SH/DHW Switching Time parameter. The minimum setting is 0 minutes and the maximum setting is 50 minutes. The default time is 30 minutes.

Set Point (1 - 3) at Low Outdoor Temperature
When the outdoor air temperature drops to the Outdoor (1 - 3) Low parameters, the calculated set point will be at this setting (FIG. 1-1). If the outdoor air temperature drops further, the set point will continue to increase above this setting. However, if SH1, SH2, and SH3 are set lower, the water temperature will be limited by these set points instead. These parameters can be changed by the installer by accessing the Set point 1 at Low Outdoor Temp 1, Set point 2 at Low Outdoor Temp 2 and Set point 3 at Low Outdoor Temp 3 parameters. The temperature range of this parameter is 68°F (20°C) to 180°F (82°C). The default value is 180°C (82°C).
The option of controlling up to three (3) different outdoor resets for low outdoor temperatures is available.
Outdoor (1 - 3) Low
When the outdoor air temperature drops to this point, the water temperature will be at the Set point 1 at Low Outdoor Temp 1, Set point 2 at Low Outdoor Temp 2 and Set point 3 at Low Outdoor Temp 3 parameters (FIG. 1-1). If the outdoor air temperature drops further, the set point will continue to increase above this setting. This parameter can be changed by the installer by accessing the Outdoor (1-3) Low parameter. The temperature range of this parameter is -39°F (-39°C) to high outdoor temperature set point. The default value is 25°F (-4°C).
Set Point (1 - 3) at High Outdoor Temperature When the outdoor air temperature rises to or above Outdoor (1 - 3) High parameters, the calculated set point will be at this setting (FIG. 1-1). These parameters can be changed by the installer by accessing the Set point 1 at High Outdoor Temp 1, Set point 2 at High Outdoor Temp 2 and Set point 3 at High Outdoor Temp 3 parameters. The temperature range of this parameter is 68°F (20°C) to 190°F (88°C). The default value is 70°F (21°C).
Outdoor (1 - 3) High
When the outdoor air temperature rises to or above this point, the water temperature will be at the Set point 1 at High Outdoor Temp 1, Set point 2 at High Outdoor Temp 2 and Set point 3 at High Outdoor Temp 3 parameters (FIG. 1-1). This parameter can be changed by the installer by accessing the Outdoor (1-3) High parameter. The temperature range of this parameter is low outdoor temperature set point to 104°F (40°C). The default value is 70°F (21°C).
Outdoor Air Shutdown (SH1 - SH3)
When the outdoor temperature rises above this point, the control will block all SH demands (DHW demands will still be active). These parameters can be changed by the installer by accessing the Outdoor Air Shutdown SH1, SH2, and SH3 parameters. The temperature range of this parameter is 32°F (0°C) to 104°F (40°C). The default value is 70°F (21°C).
Figure 1-1 Outdoor Air Reset Curve

Outdoor Reset

Outdoor Air Shutdown Differential (SH1 - SH3)
The outdoor air shutdown differential parameter is the number of degrees below Outdoor Air Shutdown SH1, SH2, and SH3 parameters the outdoor air temperature must go before the boiler will respond to a SH demand. These parameters can be changed by the installer by accessing the Outdoor Air Shutdown Differential SH1, SH2, and SH3 parameters The temperature range of this parameter is 0°F (0°C) to 54°F (30°C). The default value is 10°F (6°C).
Once a SH demand has been satisfied, a set amount of time must elapse before the control will respond to a new SH demand. The control will block the new heat demand and anti-cycling will be shown in the display until the time has elapsed or the water temperature drops below the Anti-Cycling Override Differential parameter. This parameter can be changed by the installer by accessing the Anti-Cycling Time parameter. The time range for this parameter is 1 minute to 10 minutes. The default value is 1 minute.
Shift Reset Curve (SH1 - SH3)
There is a shift reset curve for each outdoor reset. The shift reset curve parameter shifts the actual set point above or below the calculated set point by the number of degrees in this parameter. These parameters can be changed by the installer by accessing the Shift Reset Curve SH1, SH2, and SH3 parameters. The temperature range of this parameter is -17°F (-10°C) to 18°F (10°C). The default value is 0°F (0°C). This feature will be active if this parameter is set to anything other than 0°F (0°C).
The control will bypass the anti-cycling time if the inlet water temperature drops too much. The control will use the inlet water temperature the boiler was at when it shut off as the starting point. If the inlet temperature drops below the temperature parameter the control will abort anti-cycling and allow the boiler to fire. This parameter can be changed by the installer by accessing the Anti-Cycling Override Differential parameter. The temperature range of this parameter is 0°F (0°C) to 54°F (30°C). The default value is 10°F (6°C).
If a SH demand lasts longer than the programmed time delay setting and there have been no DHW demands, the control will increase the water temperature set point by the amount in this parameter. If the SH demand continues through another time period, the set point will be increased again. This will continue until either the SH demand ends, a maximum of 20 increases has occurred, or SH1, SH2, SH3 maximum set point has been reached. Once the SH demand has been satisfied the set point will revert back to its calculated setting. The boost temperature can be changed by the installer by accessing the Boost Temperature parameter. The temperature range of this parameter is 0°F (0°C) to 25°F (14°C). The default value is 0°F (0°C). This feature will be active if this parameter is set to anything other than 0°F (0°C).
Ramp Delay (Enable / Disable)
This parameter allows the installer to enable or disable the SH ramp delay. The default setting is disabled.
The boost time parameter sets the amount of time that must elapse with a SH demand before the water temperature calculated set point will be increased. This parameter can be changed by the installer by accessing the Boost Time parameter. The time range for this parameter is 0 minute to 50 minutes. The default value is 0 minutes.

Please note that the brackets ([]) denote screen status. NOTICE
The SH controlling sensor parameter selects the sensor the control will use to regulate the boiler firing rate. This parameter is adjustable by the installer by accessing the Controlling Sensor parameter. The sensor selections are as follows: The outlet sensor regulates the firing rate based on the outlet water temperature of the boiler and the inlet sensor regulates the firing rate based on the inlet water temperature of the boiler. If the outlet sensor is selected, and the optional system supply sensor is connected, the control will regulate the firing rate based on the system supply sensor temperature. The default sensor is the Outlet Sensor.
The SMART SYSTEM control can be programmed to limit the firing rate for a fixed period of time at the start of a space heating demand. There are six (6) possible limits, each with their own time delay. The first limit applies as soon as the burner starts. Once its time delay expires, the second limit is applied and its timer begins. The control steps through these limits until the 6th (sixth) limit expires. Note, however, that the 6th limit will also limit the rate for the rest of that heat demand. The installer can adjust the firing limits and time delays by accessing the Ramp Settings parameter. Once this parameter is selected, the screen will show the step number, the time delay for that step and the limit value corresponding with that step. If the installer wishes to adjust one of the values in that step, he can press the NAVIGATION dial until the value he wishes to change is flashing. The installer can then rotate the NAVIGATION dial to adjust that value. If the installer presses the RIGHT SELECT [SAVE] key while the limit value is flashing, the step value will flash again. The installer can then select the next step and adjust the delay and limit values corresponding with that step.
When controlling the boiler through the 0 - 10V BMS input or through ModBus, the boiler can be enabled one of two ways. With the BMS Thermostat Input parameter set to ACTIVE, the boiler will be enabled by closing the Heat/Loop Demand 1 input. When set to INACTIVE, the boiler will be enabled by the voltage level on the 0 - 10V input (in the case of 0 - 10V BMS control), or the 0 - 10V input value received through ModBus. The default value is INACTIVE.
When finished, the installer can press the RIGHT SELECT [SAVE] key to store the new settings, or the LEFT SELECT [EXIT] key to return to the Anti-Cycling parameter list without saving the changes. The delay value can be set between 0 minutes and 20 minutes. The limit value can be set between 0% and 100%.
The set point or modulation of the boiler may be controlled through the 0 - 10V BMS input or through ModBus. When the BMS parameter is set to INACTIVE, the 0 - 10V input will be ignored. When set to ACTIVE, the set point or modulation will be controlled by the voltage on the 0 - 10V input (in the case of 0 - 10V BMS control), or the 0 - 10V input value received through ModBus. The default value is INACTIVE.
Figure 1-2 Ramp Delay Interval


ModBus When BMS is set to ACTIVE (see BMS Active / Inactive) and the boiler is being controlled through ModBus, set ModBus parameter to ACTIVE. Otherwise, set the ModBus parameter to INACTIVE. Note that the boiler can still be monitored by ModBus with this parameter set to INACTIVE. The default value is INACTIVE.
As the calculated load increases further and both boilers ramp up to 90%, it lowers the rate of the first two (2) boilers to 60% and brings the next boiler on at 60%. The three (3) boilers then modulate together. As the calculated load decreases, the boilers will reach a lower threshold (default = 30%), at which time the last boiler (the third in our example) will turn off and the Cascade will increase the rates of the remaining boilers to provide the equivalent total output as before ((3 x 30%) / 2 = 45% in our example).
ModBus T/O The amount of time the unit controls will wait to receive a communication string from the BMS controller before reverting back to its own internal parameters. This parameter is adjustable by the installer by accessing the ModBus T/O parameter. The adjustment range of this parameter is 5 seconds to 2 minutes. The default value is 10 seconds.
Maximum Cascade Set Point This parameter determines the set point used by the individual boilers in a Cascade. When a boiler is commanded to fire by the Leader boiler, it will attempt to achieve this temperature at its outlet. The Leader boiler will limit the modulation of the last boiler to fire in order to hold the temperature at the system supply sensor to the user set point. If any of the boiler outlet temperatures reach the maximum cascade set point, the boiler will then modulate down on its own in order to keep its outlet temperature within the maximum cascade set point. Therefore, this parameter can be used to limit the outlet temperatures of all the boilers in a Cascade. Note that this parameter does not apply when the boiler is heating an indirect DHW tank. This parameter is adjustable by the installer by accessing the Maximum Cascade Set Point parameter. The temperature range of this parameter is 32° (0°C) to 190°F (88°C). The default maximum cascade set point is 185°F (85°C).
Cascade Address The boiler designated as the Leader needs to be programmed with address 0. All the Member boilers require addresses from 1 to 7, and the addresses must be different for each Member. The addresses can be in any order, regardless of the order in which the units are wired together. This parameter is adjustable by the installer by accessing the Cascade Address parameter. The outdoor air (if used) and system supply sensor must be connected to the Leader boiler. The default address is 1.
Cascade Offset This parameter determines how much the temperature must go above set point before the lead boiler will turn off. This parameter can be adjusted by the installer by accessing the Cascade Offset parameter. The temperature range of this parameter is 0° to 20°F (11°C) The default value is 10°F (6°C).
If installing the boilers in an existing system, the new boilers should be programmed as the Leader and/or the higher number addresses.
Cascade Type (L/L / EFF) There are two (2) options for the way a Cascade divides the load between its heaters. The first is Lead/Lag, designated as L/L in the menu. This method is used when it is desired to have the least amount of total flow through the boilers. This method will modulate the last two (2) boilers. This provides for smooth transitions when a boiler turns on or off. When the last boiler reaches 100% and the calculated load is still increasing, it will start the next boiler at 20% and reduce the previous boiler to 80%, thus eliminating the sudden jump in total output of the Cascade. When the calculated load is decreasing and the last boiler gets down to 20% fire, it will hold it there and start lowering the firing rate on the next-to-last boiler. When the next-to-last boiler reaches 20%, it will turn the last boiler off and raise the rate of the next-to-last boiler to 40%, thus eliminating the sudden drop in total output of the Cascade.
Cascade Differential This parameter determines how much the temperature must go below the turn off temperature (Set point + Offset) before the lead boiler turns on. This parameter can be adjusted by the installer by accessing the Cascade Differential parameter. The temperature range of this parameter is 0°F to 60°F (33°C) The default value is 20°F (11°C).
Minimum On/Off Time In order to prevent units in a Cascade from short cycling, this parameter defines the minimum ON and OFF time for each unit. The installer can adjust this time by accessing the Minimum On/Off Time parameter. The minimum setting is 0 seconds and the maximum setting is 10 minutes. The default is 30 seconds.
The other Cascade divider method is Efficiency Optimization, designated as EFF in the menu. This method is used, as the name implies, when it is desired to have the most efficient system. When the first boiler reaches a certain rate (default = 90%), it lowers its rate to 45% and turns on the next boiler at 45%. The two (2) boilers then modulate at the same rate.
Minimum Next On Time In order to reduce the risk of temperature overshoot with a Cascade, this parameter defines the minimum time delay from starting one unit until the next unit may be started. The installer can adjust this time delay by accessing the Minimum Next On Time parameter. The minimum setting is 0 minutes and the maximum setting is 10 minutes. The default is 60 seconds.

DHW Pump Anti-Seize Delay
If the boiler pump does not run for 24 hours, it will be turned on briefly to prevent it from seizing. The length of time it runs is determined by the DHW Pump Anti-Seize Delay parameter. The range of this setting is 0 seconds to 50 minutes. The default setting is 20 seconds.
The system pump delay parameter sets the length of time the system pump (if connected) will run after a SH demand has been satisfied. This parameter is adjustable by the installer by accessing the System Pump Delay parameter. The time range for this parameter is 1 second to 40 minutes. The default time is 30 seconds.
System Pump Anti-Seize Delay
If the boiler pump does not run for 24 hours, it will be turned on briefly to prevent it from seizing. The length of time it runs is determined by the System Pump Anti-Seize Delay parameter. The range of this setting is 0 seconds to 50 minutes. The default setting is 20 seconds.
The SH pump delay parameter sets the length of time the boiler pump will run after a SH demand has been satisfied. Setting the delay time to 0 will disable the pump. This parameter is adjustable by the installer by accessing the Boiler Pump Delay parameter. The time range for this parameter is 1 second to 40 minutes. The default time is 30 seconds.
When programmed for BMS control through the 0 - 10V BMS input or through ModBus, the 0 - 10V signal can be interpreted as either a modulation command or a set point. When the BMS Type parameter is set to POWER, the 0 - 10V signal will control the modulation. When set to SETPOINT, the 0 - 10V signal will control the SH set point. The default setting is SETPOINT.
The DHW pump delay parameter sets the length of time the DHW pump (if connected) will run after a DHW demand has been satisfied. This parameter is adjustable by the installer by accessing the DHW Pump Delay parameter. The time range for this parameter is 10 seconds to 40 minutes. The default time is 1 minute.
Boiler Pump Anti-Seize Delay
When programmed for BMS control through the 0 - 10V BMS input or through ModBus, the Volts at Minimum parameter should be set to the minimum voltage signal sent to the SMART SYSTEM control. The range of this parameter is 0.0V to the Volts at Maximum value. The default setting is 2.0V.
If the boiler pump does not run for 24 hours, it will be turned on briefly to prevent it from seizing. The length of time it runs is determined by the Boiler Pump Anti-Seize Delay parameter. The range of this setting is 0 seconds to 50 minutes. The default setting is 20 seconds.
Boiler Pump Minimum Voltage
The speed of the boiler pump can be controlled by the SMART SYSTEM control in order to maintain a minimum T through the heat exchanger. Thus, as the firing rate decreases, the speed of the boiler pump can decrease as well. The SMART SYSTEM control outputs a 0 - 10V signal to the boiler pump to control its speed. The Boiler Pump Minimum Voltage parameter determines the minimum voltage given to the boiler pump, thereby setting its minimum speed. The range of this setting is 2.5V to 10V. The default setting is 3.5V.
When programmed for BMS control through the 0 - 10V BMS input or through ModBus, the Volts at Maximum parameter should be set to the maximum voltage signal sent to the SMART SYSTEM control. The range of this parameter is the Volts at Minimum value to 10.0V. The default value is 10.0V.
Rate at Minimum Volts
When programmed for BMS control through the 0 - 10V BMS input or through ModBus and the BMS Type is programmed as POWER, the modulation percentage represented by the Volts at Minimum parameter is set by the Rate at Minimum Volts parameter. The minimum value is 0% and the maximum is the Rate at Maximum Volts setting. The default value is 20%.
The system pump can be programmed to operate in response to any of the Room Thermostat inputs, or to run continuously until the boiler goes into Outdoor Shutdown. To program the system pump to operate only with a space heating call for heat, set the System Pump Type parameter to CFH. To program the system pump to run continuously until outdoor shutdown starts, set the System Pump Type parameter to WWSD. The default setting is CFH.
Rate at Maximum Volts
When programmed for BMS control through the 0 - 10V BMS input or through ModBus and the BMS Type is programmed as POWER, the modulation percentage represented by the Volts at Maximum parameter is set by the Rate at Maximum Volts parameter. The minimum value is the Rate at Minimum Volts setting and the maximum is 100%. The default value is 100%.

Set Point at Minimum Volts
When programmed for BMS control through the 0 - 10V BMS input or through ModBus and the BMS Type is programmed as SETPOINT, the set point represented by the Volts at Minimum parameter is set by the Set Point at Maximum Volts parameter. The minimum value is 32°F (0°C) and the maximum is the Set Point at Maximum Volts setting. The default value is 70°F (21°C).
When the boiler control determines that a scheduled service is due based on the number of boiler cycles, the boiler display will alternate the standard boiler display text with the message SERVICE DUE every 5 seconds. This parameter is adjustable by the installer by accessing the Service Notification Cycles parameter. The range for this parameter is 0 cycles to 100,000 cycles. The default is 50,000 cycles.
Set Point at Maximum Volts
When programmed for BMS control through the 0 - 10V BMS input or through ModBus and the BMS Type is programmed as SETPOINT, the set point represented by the Volts at Maximum parameter is set by the Set Point at Maximum Volts parameter. The minimum value is the Set Point at Minimum Volts setting and the maximum is 190°F (88°C). The default value is 180°F (82°C).
Once servicing has been completed, the service notification counter should be reset. This parameter can be reset by the installer by accessing the Reset Maintenance Reminder parameter. Once accessed, press the RESET key to reset the service notification counter.
Service Name and Phone Number
When programmed for BMS control through the 0 - 10V BMS input or through ModBus and the BMS Thermostat Input is set to INACTIVE, the On Volts parameter determines the 0 - 10V BMS input voltage at which the boiler is enabled. The minimum value is 0.5V and the maximum is 10.0V. The default value is 2.0V.
Please note that the brackets ([]) denote screen status. NOTICE
When a Maintenance Reminder timer or counter has expired, a Maintenance Reminder screen will appear on the display. By programming the installer’s name and phone number, this information will appear on the Maintenance Reminder Screen at that time. This can be programmed by accessing the Service Name and Phone Number parameter. When selected, another menu will appear with PHONE and NAME.
When programmed for BMS control through the 0 - 10V BMS input or through ModBus and the BMS Thermostat Input is set to INACTIVE, the Off Differential Volts parameter determines how far below the On Volts setting the 0 - 10V BMS input voltage must be in order to disable the boiler. The minimum value is 0.2V and the maximum is the On Volts setting. The default value is 1.0V.
Service Notification in Months
When the boiler control determines that a scheduled service is due based on days of installation, the boiler display will alternate the standard boiler display text with the message SERVICE DUE every 5 seconds. This parameter is adjustable by the installer by accessing the Service Notification in Months parameter. The time range for this parameter is 0 months to 100 months. The default time is 12 months.
This feature has been disabled by the manufacturer. To enable this feature change parameter K1 to the desired time range.
Service Notification Running Time
When the boiler control determines that a scheduled service is due based on the hours of actual operation, the boiler display will turn yellow and a new status screen will appear informing the installer that maintenance is required. This parameter is adjustable by the installer by accessing the Service Notification Running Time parameter. The time range for this parameter is 0 hours to 17,500 hours. The default time is 8,760 hours.

Maintenance and annual startup
Table 2-1 Service and Maintenance Schedules
Service technician (see the following pages for instructions)
Periodically • Test low water cutoff (if used)
instructions)

Follow the Service and maintenance procedures given throughout this manual and in component literature shipped with the boiler. Failure to perform the service and maintenance could result in damage to the boiler or system. Failure to follow the directions in this manual and component literature could result in severe personal injury, death, or substantial property damage.
WARNING
The boiler should be inspected annually only by a qualified service technician. In addition, the maintenance and care of the boiler designated in Table 2-1 and explained on the following pages must be performed to assure maximum boiler efficiency and reliability. Failure to service and maintain the boiler and system could result in equipment failure.
Electrical shock hazard – Turn off power to the boiler before any service operation on the boiler except as noted otherwise in this instruction manual. Failure to turn off electrical power could result in electrical shock, causing severe personal injury or death.
Address reported problems
Figure 2-1 Condensate Trap

The condensate trap must be filled with water during all times of boiler operation to avoid flue gas emission from the condensate drain line. Failure to fill the trap could result in severe personal injury or death.
Check all piping for leaks
Eliminate all system or boiler leaks. Continual fresh makeup water will reduce boiler life. Minerals can build up in sections, reducing heat transfer, overheating heat exchanger, and causing heat exchanger failure. Leaking water may also cause severe property damage.

Safety relief valves should be re-inspected AT LEAST ONCE EVERY THREE YEARS, by a licensed plumbing contractor or authorized inspection agency, to ensure that the product has not been affected by corrosive water conditions and to ensure that the valve and discharge line have not been altered or tampered with illegally. Certain naturally occurring conditions may corrode the valve or its components over time, rendering the valve inoperative. Such conditions are not detectable unless the valve and its components are physically removed and inspected. This inspection must only be conducted by a plumbing contractor or authorized inspection agency – not by the owner. Failure to re-inspect the boiler relief valve as directed could result in unsafe pressure buildup, which can result in severe personal injury, death, or substantial property damage.
Failure to inspect for the above conditions and have them repaired can result in severe personal injury or death.
Following installation, the valve lever must be operated AT LEAST ONCE A YEAR to ensure that waterways are clear. Certain naturally occurring mineral deposits may adhere to the valve, rendering it inoperative. When manually operating the lever, water will discharge and precautions must be taken to avoid contact with hot water and to avoid water damage. Before operating lever, check to see that a discharge line is connected to this valve directing the flow of hot water from the valve to a proper place of disposal. Otherwise severe personal injury may result. If no water flows, valve is inoperative. Shut down the boiler until a new relief valve has been installed.

Figure 2-2 Burner Assembly - Model 400

Figure 2-3 Burner Assembly - Model 501

Figure 2-4 Burner Assembly - Models 601 - 801


water. Rinse out debris with a low pressure water supply.
Table 2-2 Heat Exchanger Cleaning Kits

For recommended materials; including brush, appropriate extension(s), refractory cover, and detailed instructions see Table 2-2 - Heat Exchanger Cleaning Kits.
* Do NOT use a metal brush. Only use the kit provided brush or an equivalent replacement nylon brush.
Figure 2-5 Rope Gasket - Heat Exchanger Door

The boiler contains ceramic fiber materials. Use care when handling these materials per instructions on page 3 of this manual. Failure to comply could result in severe personal injury.
boiler heating surfaces. Do not use any solvent.

Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Always disconnect power to the boiler before servicing. Failure to comply could result in severe personal injury, death, or substantial property damage.
ALWAYS check control module fuses before replacing control module or any major components (blower, etc.). If one of these fuses is blown, it can prevent the control module or other components from operating.
Never jumper (bypass) any device except for momentary testing as outlined in the Troubleshooting chart. Severe personal injury, death, or substantial property damage can result.
Figure 3-1 Control Module Fuses

a. Voltmeter that can check 120 VAC, 24 VAC, and 12 VDC. b. Continuity checker. c. Contact thermometer.
F3 - .80 AMP FUSE 24V DC POWER SUPPLY
Do not jumper fuse or replace with any fuse except as specified. Failure to comply could result in severe personal injury, death, or substantial property damage.

Table 3-1 Troubleshooting Chart - No Display
- No 120 vac supplied to unit.
- No voltage through the switch. • Replace switch.
- Bad display board. • Replace board.
- Bad main control board. • Replace the main control board.
- Blown fuse. • Replace fuse F3 on the main control board, see page 33 of this manual.
- Main control board temperature set point satisfied. • Review temperature setting.
- Remote thermostat satisfied. • Review remote thermostat setting.
- Outside air temperature above Warm Weather Shutdown (WWSD) set point for main control board.
- Unit locked out on fault.
- Unit in Shutdown Mode. • Take unit out of Shutdown Mode.
- Ramp delay active.
Unit Does Not Modulate
- Boiler controlled by BMS. • Check BMS parameter settings. Optional PC software required.
- Flue sensor open.

The boiler temperature sensors (inlet water, outlet water, system water, flue, and outdoor air) are all resistance type devices. The following tables show the correct values for the sensors at various temperatures. Use an ohmmeter to read the resistance of the sensor at a known temperature. If the resistance of the sensor does not closely match its corresponding table, replace the sensor
It is important to note that the flue and outlet water sensors have two temperature sensing devices in one housing. These devices are designated as S1a/S1b, outlet sensor and S3a/S3b, flue sensor. Please reference the wiring diagram in the Knight XL Installation and Operation Manual for correct terminal location.
Table 3-2A - Inlet Water/System Sensor Resistance vs. Temperature
Table 3-2B - Outdoor Air Sensor Resistance vs. Temperature

-50 490,813 20 46,218 -40 336,606 30 34,558 -30 234,196 40 26,099 -20 165,180 50 19,900 10 118,018 60 15,311 0 85,362 70 11,883 10 62,465 80 9,299
Table 3-2C - Outlet Water Sensor Resistance vs. Temperature

50 19,553 158 2,004 50 40,030 158 3,478 68 12,690 176 1,464 68 25,030 176 2,492 86 8,406 194 1,084 86 16,090 194 1,816 104 5,715 212 816 104 10,610 212 1,344 122 3,958 122 7,166 140 2,786 140 4,943
Table 3-2D - Flue Sensor Resistance vs. Temperature

50 40,030 158 3,478 50 258,500 158 16,870 68 25,030 176 2,492 68 125,500 176 12,000 86 16,090 194 1,816 86 80,220 194 8,674 104 10,610 212 1,344 104 52,590 212 6,369 122 7,166 122 35,270 140 4,943 140 24,160

Table 3-3 Troubleshooting Chart - Noisy System
- Supply gas problem. Natural gas pressures should be between 4 inches w.c. and 14 inches w.c. LP gas pressures should be between 8 inches w.c. and 14 inches w.c.
- Gas/air mixture problem. • Refer to the Gas Valve Adjustment Procedure on page 47 of this manual for the proper gas valve setting. Verify that the vent/air intake lengths do not exceed the maximum listed in the General Venting section of the Knight XL Installation and Operation Manual.
- Dirty/damaged burner. • Refer to page 31 in this manual for the burner removal and inspection procedure. Clean or replace the burner as necessary.
- Low water flow through the heat exchanger. • Refer to Section 6 - Hydronic Piping of the
Knight XL Installation and Operation Manual for minimum flow rates. Verify that the boiler is piped in a primary/secondary fashion and that the boiler and system pump are running on a call for heat.
- Air in the piping system. • Properly purge all air from the piping system.
- Low system water pressure. • Verify system pressure is a minimum of 12 psi.
No Pump Operation - Boiler Pump System Pump
- Blown fuse. • Replace fuse F1 on the control board, see page 33 of this manual.
- Faulty pump. • Replace pump.
- Internal fault on control board. • Replace main control board.
- System pressure exceeds relief valve setting.

Table 3-4 Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
- Either the optional manual reset low gas pressure switch or the optional manual reset high gas pressure switch tripped.
(will require a manual reset once the condition has been corrected. Press
the RESET button on the SMART SYSTEM display
to reset.)
- The gas pressure switch contacts on the Low Voltage Connection Board are open.
LWCO (will require a manual reset once condition has
- Either the optional flow switch or the optional low water cutoff is not making.
been corrected. Press the RESET button on the SMART SYSTEM display
to reset.)
- Blown fuse. • Replace fuse F3 on the control board, see page 33 of this manual.
(will require a manual reset once condition has
The blocked drain switch has detected excessive condensate build up inside the unit.
been corrected. Press the RESET button on the SMART SYSTEM display
to reset.)
Gas Pressure SW · Flow Switch/ · Blocked Drain SW

Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
APS:
Open (will require a manual reset once the condition
Either the air pressure switch contacts are open, or the O-temp heat exchanger switch has opened.
has been corrected. Press the RESET button on the SMART SYSTEM
display to reset.)
The main control board has received a call for heat too quickly after the previous call for heat has ended.
Flame Fail Ign (will require a manual reset once the condition
has been corrected. Press the RESET button on the SMART SYSTEM
The unit has failed to prove main burner ignition after four (4) attempts.
display to reset.)
Temp Sw · Anti-cycling

Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
The unit has failed to prove main burner ignition after four (4) attempts.
(cont’d) (will require a manual reset once the condition
has been corrected. Press the RESET button on the SMART SYSTEM
display to reset.)
(will require a manual reset once the condition
The flame detector circuit is seeing a flame signal while no flame is present.
has been corrected. Press the RESET button on the SMART SYSTEM
display to reset.)
Flame Fail Ign · Flame Sequence

Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
The outlet water temperature has exceeded the setting of the automatic reset high limit.
Outlet MRHL (will require a manual reset once the condition
has been corrected.
The outlet water temperature has exceeded the setting of the manual reset high limit.
Press the RESET button on the SMART
reset.)
Outlet ARHL · SYSTEM display to

Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
(cont’d) (will require a manual reset once the condition has been corrected. Press
The outlet water temperature has exceeded the setting of the manual reset high limit.
the RESET button on the SMART SYSTEM display
to reset.)
OR Fan Speed Low/
The actual fan RPM is 30% lower than what is being called for.
High (will require a manual reset once the condition has been corrected. Press
the RESET button on the SMART SYSTEM display
to reset.)
Blown fuse. • Replace fuse F2 on the control board, see page 33 of this manual.
Fail (will require a manual reset once the condition has been corrected. Press
The main control board did not detect the gas valve.
the RESET button on the SMART SYSTEM display
to reset.)
Sensor Open (will require a manual reset once the condition has been corrected. Press
Either the inlet water or outlet water temperature sensor has been disconnected.
the RESET button on the SMART SYSTEM display
to reset.)
Outlet MRHL · Fan Low/High · GV/Relay

Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
Sensor Shorted (will require a manual reset once the condition has been
Either the inlet water or outlet water temperature sensor has been shorted.
corrected. Press the RESET
button on the SMART SYSTEM display to reset.)
Sw (will require a manual reset once the condition has been
An optional remote proving switch is not making.
corrected. Press the RESET
button on the SMART SYSTEM display to reset.)
Fault (will require a manual reset once the condition has been
The control reads the inlet sensor as open or shorted.
corrected. Press the RESET
button on the SMART SYSTEM display to reset.)
Fault (will require a manual reset once the condition has been
The control reads the inlet sensor as open or shorted.
corrected. Press the RESET
button on the SMART SYSTEM display to reset.)
Outlet Temp Diff (will require a manual reset once the condition has been
The control module reads an excessive temperature difference between the two sensors.
corrected. Press the RESET
button on the SMART SYSTEM display to reset.)
Louver Proving · Inlet Sensor · Outlet Sensor

Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
Flue Sensor Fault (will require a manual reset once the condition has been
The control reads the flue sensor as open or shorted.
corrected. Press the RESET
button on the SMART SYSTEM display to reset.)
Flue Temp Diff (will require a manual reset once the condition has been
The control module reads an excessive temperature difference between the two sensors.
corrected. Press the RESET
button on the SMART SYSTEM display to reset.)
Flue Temp Limit (will require a manual reset once the condition has been
The stack temperature has exceeded the Flue Temp Limit set parameters.
corrected. Press the RESET
button on the SMART SYSTEM display to reset.)
Fatal Error The control module has detected parameter settings that are out of range.
Memory Error A lockout occurs at the same time as a power outage. • Reset control module.

Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
The stack temperature has exceeded the set parameters for the boiler.
Delta T High The temperature rise across the heat exchanger has exceeded the set parameters for the boiler.
Outlet water temperature has exceeded the maximum outlet water temperature.
Flue Temp High · Outlet Temp · High

Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
Rem Ctrl Flt External control is cycling too often.
Progr (will require a manual reset once the condition has been corrected. Press
After downloading parameters from a laptop, the main control board must be reset.
the RESET button on the SMART SYSTEM display
to reset.)
Service Blk While the unit is in Service Mode, the outlet temperature has exceeded 185°F.
Low 24 vac 120 vac input to the main control board has dropped below 80 vac.
Watch Dog Error The main control board has detected an internal fault. • Replace the main control board.
The main control board has detected an internal fault. • Replace the main control board.
CRC Parameters The main control board has detected an internal fault. • Replace the main control board.
No Error Stored The main control board has detected an internal fault. • Replace the main control board.
Parameters · Write EEProm

Table 3-5 Flue Products
8.0% - 10% 3.0% - 6.5% 9.0% - 11% 4.1% - 6.9%
You must replace the flue gas temperature sensor to prevent flue gas spillage into the room. Failure to comply could result in severe personal injury, death, or substantial property damage.
If the combustion is not within the specified range, reference the chart below for possible causes and corrective actions.
Table 3-6 Troubleshooting Chart - Combustion Levels
Gas Supply Pressure • Refer to Section 7 - Gas Connections of the Knight XL Installation and Operation Manual for the proper gas supply for the Knight XL boiler.
Dirty/Damaged Burner • Refer to page 31 of this manual for burner removal and cleaning procedures.
Gas Valve Adjustment • Refer to page 47 of this manual for the gas valve adjustment procedure.
Natural Gas Propane · Vent/Air Intake Length · or Obstruction

If adjustment of the gas valve is deemed necessary, use the following procedures: (Note: The procedures below are model specific.)

Locate the throttle adjustment screw on the top of the gas valve, see FIG. 3-2. Using a screwdriver, turn the screw 1/8 turn counterclockwise to increase CO2 levels or 1/8 turn clockwise to decrease CO2 levels. After one adjustment on the valve, follow the Combustion Analysis Procedure on page 46 of this manual to measure the combustion.
If combustion is still not within the specified range, repeat the procedure. This procedure SHOULD NOT be performed more than four (4) times. If after four (4) adjustments and the combustion is still not within the specified range, revisit the possible causes in Table 3-6 on page 46 or replace the gas valve.
Models 601 - 801
Locate the throttle adjustment screw on top of the gas valve, see FIG. 3-4. Using an Allen wrench, turn the screw a 1/4 turn counterclockwise to increase CO2 levels or a 1/4 turn clockwise to decrease CO2 levels. After one adjustment on the valve, follow the Combustion Analysis Procedure on page 46 of this manual to measure the combustion.
SCREW
If combustion is still not within the specified range, repeat the procedure. This procedure SHOULD NOT be performed more than four (4) times. If after four (4) adjustments and the combustion is still not within the specified range, revisit the possible causes in Table 3-6 on page 46 or replace the gas valve.


Locate the throttle adjustment screw on top of the gas valve, see FIG. 3-3. Using a screwdriver, turn the screw a 1/4 turn counterclockwise to increase CO2 levels or a 1/4 turn clockwise to decrease CO2 levels. After one adjustment on the valve, follow the Combustion Analysis Procedure on page 46 of this manual to measure the combustion.
If combustion is still not within the specified range, repeat the procedure. This procedure SHOULD NOT be performed more than four (4) times. If after four (4) adjustments and the combustion is still not within the specified range, revisit the possible causes in Table 3-6 on page 46 or replace the gas valve.
Model 400 · Model 501


Revision Notes: Revision A (ECO #C05747) initial release. Reflects the new model numbers for the Knight XL upgrade.
Revision B (ECO #C06234) reflects changes made to the Service Notification parameter.
Revision C (ECO #C07981) reflects changes made to the parameter table, parameter descriptions, updates to the troubleshooting chart, and the addition of the O-temp HEX switch. .
Common problems, likely causes, and what to do.
| Problem | Possible cause | Remedy | |
|---|---|---|---|
| No Display | - No 120 vac supplied to unit. | • Check external line switch, fuse, or breaker. • Check position of ON/OFF switch. Turn switch to the ON position. • Check 120 vac through the ON/OFF switch. • Check wiring harness connection between display board and main control board. Connect harness at both points. | p.34 |
| No Display | - No voltage through the switch. | • Replace switch. | p.34 |
| No Display | - Bad display board. | • Replace board. | p.34 |
| No Display | - Bad main control board. | • Replace the main control board. | p.34 |
| No Display | - Blown fuse. | • Replace fuse F3 on the main control board, see page 33 of this manual. | p.34 |
| No Burner Operation | - Main control board temperature set point satisfied. | • Review temperature setting. | p.34 |
| No Burner Operation | - Remote thermostat satisfied. | • Review remote thermostat setting. | p.34 |
| No Burner Operation | - Outside air temperature above Warm Weather Shutdown (WWSD) set point for main control board. | • Check location of outside air sensor. Check resistance of outdoor air sensor and compare to Table 3-2B on page 35 of this manual. | p.34 |
| No Burner Operation | - Unit locked out on fault. | • Consult display for specific fault. Refer to fault descriptions on page 37 of this manual for corrective actions. | p.34 |
| No Burner Operation | - Unit in Shutdown Mode. | • Take unit out of Shutdown Mode. | p.34 |
| Unit Does Not Modulate Above 50% | - Ramp delay active. | • Check ramp delay parameter settings. Optional PC software required. | p.34 |
| Unit Does Not Modulate Above 50% | • Turn ramp delay feature off. See page 23 of this manual for instructions on how to turn this feature off. | p.34 | |
| Unit Does Not Modulate Above 50% | - Boiler controlled by BMS. | • Check BMS parameter settings. Optional PC software required. | p.34 |
| Unit Does Not Modulate Above 50% | - Flue sensor open. | • Verify that the flue sensor is located in the flue outlet. | p.34 |
| Unit Does Not Modulate Above 50% | • Check wiring connections at the flue sensor. | p.34 | |
| Unit Does Not Modulate Above 50% | • Check the resistance of the flue sensor and compare to Table 3-2D on page 35 of this manual. | p.34 | |
| Noisy Operation | - Supply gas problem. Natural gas • pressures should be between 4 inches w.c. and 14 inches w.c. LP gas pressures should be between 8 inches w.c. and 14 inches w.c. | Refer to Section 7 - Gas Connections of the Knight XL Installation and Operation Manual for detailed information concerning the gas supply. | p.36 |
| Noisy Operation | - Gas/air mixture problem. • | Refer to the Gas Valve Adjustment Procedure on page 47 of this manual for the proper gas valve setting. Verify that the vent/air intake lengths do not exceed the maximum listed in the General Venting section of the Knight XL Installation and Operation Manual. | p.36 |
| Noisy Operation | - Dirty/damaged burner. • | Refer to page 31 in this manual for the burner removal and inspection procedure. Clean or replace the burner as necessary. | p.36 |
| Noisy Operation | - Low water flow through the heat exchanger. • | Refer to Section 6 - Hydronic Piping of the Knight XL Installation and Operation Manual for minimum flow rates. Verify that the boiler is piped in a primary/secondary fashion and that the boiler and system pump are running on a call for heat. | p.36 |
| Noisy Operation | - Air in the piping system. • | Properly purge all air from the piping system. | p.36 |
| Noisy Operation | - Low system water pressure. • | Verify system pressure is a minimum of 12 psi. | p.36 |
| No Pump Operation - Boiler Pump System Pump or DHW Pump | - Blown fuse. • | Replace fuse F1 on the control board, see page 33 of this manual. Note: Make sure pump amperage does not exceed 1.8 amps. | p.36 |
| No Pump Operation - Boiler Pump System Pump or DHW Pump | - Faulty pump. • | Replace pump. | p.36 |
| No Pump Operation - Boiler Pump System Pump or DHW Pump | - Internal fault on control board. • | Replace main control board. | p.36 |
| Relief Valve Opening | -System pressure exceeds relief valve • setting. • | Lower the system pressure below the 30 psi rating of the supplied relief valve or replace the standard relief valve with a higher rated valve up to the maximum pressure of the heat exchanger. Improperly sized expansion tank. | p.36 |
| Gas Pressure SW (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.) | • Reset the pressure switches. • Measure the supply gas pressure to determine cause of failure. Natural gas pressures should be between 4 - 14 inches w.c. and LP gas pressures should be between 8 - 14 inches w.c. • Refer to Section 7 - Gas Connections of the Knight XL Installation and Operation Manual for detailed information concerning the gas supply. • Correct the supply gas pressure if necessary. • Check for a loose or misplaced jumper if pressure switches are not installed. | p.37 | |
| Gas Pressure SW (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.) | • Check for a loose or misplaced jumper on the Low Voltage Connection Board. • Check for the addition of a device wired across the gas pressure switch terminals on the Low Voltage Connection Board. | p.37 | |
| Flow Switch/ LWCO (will require a manual reset once condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.) | • Check boiler pump operation on a call for heat. • Check for closed valves or obstructions in the boiler piping. • Verify system is full of water and all air has been purged from the system. • Check for loose or misplaced jumpers if flow switch or LWCO is not installed. | p.37 | |
| Flow Switch/ LWCO (will require a manual reset once condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.) | • Replace fuse F3 on the control board, see page 33 of this manual. | p.37 | |
| Blocked Drain SW (will require a manual reset once condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.) | • Check condensate tube from unit to floor drain for proper installation and obstructions. • Inspect condensate trap for blockage. Clean if necessary. • Check for loose wiring connection at wire harness plug. • Bad blocked drain switch. Replace switch. | p.37 | |
| APS / HEX Temp Sw Open (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.) | APS: Check the wiring connections to switch. Wires should be connected to the common and normally closed terminals. Air intake lengths exceed the maximum allowed lengths. Refer to Section 3 - General Venting of the Knight XL Installation and Operation Manual for proper lengths. Check for obstruction or blockage in the air intake pipes or at terminations. Check reference hoses connected to the air pressure switch for blockage or obstruction. Inspect the burner. Reference page 31 of this manual for removal and cleaning procedures. Replace if necessary. Inspect the heat exchanger. Reference page 32 of this manual for removal and cleaning procedures. Replace if necessary. Faulty air pressure switch. Replace switch. | p.38 | |
| APS / HEX Temp Sw Open (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.) | O-TEMP HEX SWITCH Inspect the back of the inner combustion chamber at burner level for refractory breakdown / missing. Replace heat exchanger if refractory is broken and unit has fired. Check continuity across two contacts. Wires should be connected at both poles of the normally closed switch. Faulty O-Temp HEX Switch. Replace switch. | p.38 | |
| Anti-cycling | The control board will release the call for heat after a set time period. The control board will release the call for heat if the outlet temperature drops too quickly. | p.38 | |
| Flame Fail Ign (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.) | Inspect spark electrode and associated wiring for damage and connection. Reference page 31 of this manual for removal and cleaning procedures. Replace if necessary. Check for proper electrical grounding of the unit. Check incoming supply gas pressure. Natural gas pressures should be between 4 - 14 inches w.c. and LP gas pressures should be between 8 - 14 inches w.c. Refer to Section 7 - Gas Connections of the Knight XL Installation and Operation Manual for detailed information concerning the gas supply. | p.38 | |
| Flame Fail Ign (cont’d) (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.) | Verify that the plastic hose from the gas valve to the air inlet is connected and is not damaged. Verify that the vent/air intake pipes are correctly installed and that there are no obstructions. Check for 24 vac to the gas valve at the 2-pin connection on the side of the main control board during the ignition attempt. If no voltage is present, replace the main control board. If 24 vac is present at the main control board, check the wiring between the main control board and the gas valve. Replace the wiring if necessary. Do not disconnect the wiring from the gas valve and attempt to measure voltage at that point. The main control board can detect if the gas valve is not connected and will display the Gas Valve or Gas Valve Fail fault. If 24 vac is present, check the outlet of the valve to ensure the valve is flowing gas. With a manometer connected to the outlet tap of the gas valve, when the unit is in the prepurge period, there should be a negative pressure present. When the valve is energized a change in pressure should occur. If the pressure change does not occur, the gas valve is not opening. Replace the gas valve. Inspect flame sensor and associated wiring. Reference page 31 of this manual for removal and cleaning procedures. Replace if necessary. Inspect and clean the heat exchanger as necessary. Reference page 32 of this manual for cleaning procedures. Inspect the burner. Reference page 31 of this manual for removal and cleaning procedures. Replace if necessary. Replace the main control board. | p.39 | |
| Flame Sequence (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.) | Check supply voltage for proper polarity. Check external wiring for voltage feedback. Check the flame rod and make sure it is clean. Check the internal wiring for bad connections. Replace main control board. | p.39 | |
| Outlet ARHL | Adjust the set point of the auto reset limit to a higher setting up to a maximum of 200°F. Reference the Knight XL Installation and Operation Manual for adjusting procedures. Verify that the system is full of water and that all air has been properly purged from the system. Verify that the boiler is piped properly into the heating system. Refer to Section 6 - Hydronic Piping of the Knight XL Installation and Operation Manual for the proper piping methods for the Knight XL boiler. Check 120 vac to boiler pump motor on a call for heat. If voltage is not present, check wiring back to the main control board. Replace the main control board if necessary. If 120 vac is present on a call for heat and the boiler pump is not operating, replace the pump. If the system pump is a variable speed pump, ensure that the system flow is not less than the boiler flow. If operating on something other than an outlet sensor, check temperature setting of the main control board. If the optional manual reset high limit has tripped, check setting of the device. Check resistance of water sensors and compare to Table 3-2A on page 35 of this manual. Replace sensor if necessary. Replace high limit. | p.40 | |
| Outlet MRHL (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.) | Adjust the set point of the manual reset limit to a higher setting up to a maximum of 210°F. Reference the Knight XL Installation and Operation Manual for adjusting procedures. Verify that the system is full of water and that all air has been properly purged from the system. Verify that the boiler is piped properly into the heating system. Refer to Section 6 - Hydronic Piping of the Knight XL Installation and Operation Manual for the proper piping methods for the Knight XL boiler. Check 120 vac to boiler pump motor on a call for heat. If voltage is not present, check wiring back to the main control board. | p.40 | |
| Outlet MRHL (cont’d) (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.) | • Replace the main control board if necessary. • If 120 vac is present on a call for heat and the boiler pump is not operating, replace the pump. • If the system pump is a variable speed pump, ensure that the system flow is not less than the boiler flow. • If operating on something other than an outlet sensor, check temperature setting of the main control board. • If the optional manual reset high limit has tripped, check setting of the device. • Check resistance of water sensors and compare to Table 3-2A on page 35 of this manual. Replace sensor if necessary. • Replace high limit. | p.41 | |
| Fan Low/High OR Fan Speed Low/ High (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.) | • Vent/air intake lengths exceed the maximum allowed lengths. Refer to Section 3 - General Venting of the Knight XL Installation and Operation Manual for proper lengths. • Check for obstruction or blockage in the vent/air intake pipes or at terminations. • Check the wiring connections at the fan and at the main control board. • Replace the fan. • Replace the main control board. | p.41 | |
| Fan Low/High OR Fan Speed Low/ High (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.) | • Replace fuse F2 on the control board, see page 33 of this manual. | p.41 | |
| GV/Relay Fail (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.) | • Check wiring harness connection at the gas valve and at the main control board. • Replace the gas valve wire harness. • Replace the gas valve. • Replace the main control board. | p.41 | |
| Sensor Open (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.) | • Check the sensors and their associated wiring. Repair or replace the sensor or wiring if damaged. • Measure the resistance of the sensors and compare the resistance to the tables on page 35 of this manual. • Replace the sensor if necessary. | p.41 | |
| Sensor Shorted (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.) | • Check the sensors and their associated wiring. Repair or replace the sensor or wiring if damaged. • Measure the resistance of the sensors and compare the resistance to the tables on page 35 of this manual. • Replace the sensor if necessary. | p.42 | |
| Louver Proving Sw (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.) | • Check function of remote devices. • Check for loose or misplaced jumper if auxiliary proving switch is not installed. | p.42 | |
| Inlet Sensor Fault (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.) | • Check wiring to sensor. Make sure wiring is connected and not damaged. Reconnect / repair wiring if necessary. • Measure the resistance of the sensor and compare to the resistance in Table 3-2A on page 35 of this manual. Replace sensor if necessary. • Replace control module. | p.42 | |
| Outlet Sensor Fault (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.) | • Check wiring to sensor. Make sure wiring is connected and not damaged. Reconnect / repair wiring if necessary. • Measure the resistance of the sensor and compare to the resistance in Table 3-2C on page 35 of this manual. Replace sensor if necessary. • Replace control module. | p.42 | |
| Outlet Temp Diff (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.) | • Check wiring to sensor. Make sure wiring is connected and not damaged. Reconnect / repair wiring if necessary. • Measure the resistance of the sensor and compare to the resistance in Table 3-2C on page 35 of this manual. Replace sensor if necessary. • Restore control parameter defaults from optional PC software. • Replace control module. | p.42 | |
| Flue Sensor Fault (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.) | • Check wiring to sensor. Make sure wiring is connected and not damaged. Reconnect / repair wiring if necessary. • Measure the resistance of the sensor and compare to the resistance in Table 3-2D on page 35 of this manual. Replace the sensor if necessary. • Replace control module. | p.43 | |
| Flue Temp Diff (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.) | • Check wiring to sensor. Make sure wiring is connected and not damaged. Reconnect / repair wiring if necessary. • Measure the resistance of the sensor and compare to the resistance in Table 3-2D on page 35 of this manual. Replace sensor if necessary. • Restore control parameter defaults from optional PC software. • Replace control module. | p.43 | |
| Flue Temp Limit (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.) | • Inspect the heat exchanger. Reference page 32 of this manual for the procedure on how to clean the flue side of the heat exchanger. • Inspect the flue sensor and associated wiring. Measure the resistance of the flue sensor and compare to Table 3-2D on page 35 of this manual. Replace the sensor if necessary. • Verify that the vent/air intake pipes are properly installed and that there are no obstructions. • Replace the main control board. | p.43 | |
| Fatal Error | • Restore the parameter defaults from the optional PC software. • Replace control module. | p.43 | |
| Memory Error | • Reset control module. | p.43 | |
| Flue Temp High | • Inspect the heat exchanger. Reference page 32 of this manual for the procedure on how to clean the flue side of the heat exchanger. • Inspect the flue sensor and associated wiring. Measure the resistance of the flue sensor and compare to Table 3-2D on page 35 of this manual. Replace the sensor if necessary. • Verify that the vent/air intake pipes are properly installed and that there are no obstructions. • Replace the main control board. | p.44 | |
| Delta T High | • Verify that the system is full of water and that all air has been properly purged from the system. • Verify that the boiler is piped properly into the heating system. Refer to Section 6 - Hydronic Piping of the Knight XL Installation and Operation Manual for the proper piping methods for the Knight XL boiler. • Check for 120 vac to the boiler pump motor on a call for heat. If voltage is not present, check the wiring back to the main control board. Replace the main control board if necessary. • If 120 vac is present on a call for heat and the boiler pump is not operating, replace the pump. • Verify that the boiler pump is set to the proper speed or that the pump is the proper size. Reference Section 6 - Hydronic Piping of the Knight XL Installation and Operation Manual for boiler pump specifications. | p.44 | |
| Outlet Temp High | • Verify that the system is full of water and that all air has been properly purged from the system. • Verify that the boiler is piped properly into the heating system. Refer to Section 6 - Hydronic Piping of the Knight XL Installation and Operation Manual for the proper piping methods for the Knight XL boiler. • Check for 120 vac to the boiler pump motor on a call for heat. If voltage is not present, check wiring back to the main control board. Replace the main control board if necessary. • If 120 vac is present on a call for heat and the boiler pump is not operating, replace the pump. | p.44 | |
| Outlet Temp High | • Verify that the boiler pump is set to the proper speed or that the boiler pump is the proper size. Reference Section 6 - Hydronic Piping of the Knight XL Installation and Operation Manual for boiler pump specifications. • Replace the main control board. | p.44 | |
| Rem Ctrl Flt | • Check set point of the external control. • Check the wiring between the external control and the unit. • Replace the control. | p.45 | |
| Parameters Progr (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.) | • Press the ENTER/RESET button on the SMART SYSTEM display panel. | p.45 | |
| Service Blk | • Establish a heating load to remove the heat from the boiler loop. • Verify that the system is full of water and that all air has been properly purged from the system. • Verify that the boiler is piped properly into the heating system. Refer to Section 6 - Hydronic Piping of the Knight XL Installation and Operation Manual for the proper piping methods for the Knight XL boiler. • Check 120 vac to the boiler pump motor on a call for heat. If voltage is not present, check the wiring back to the main control board. Replace the main control board if necessary. • If 120 vac is present on a call for heat and the boiler pump is not operating, replace the pump. • Verify that the boiler pump is set to the proper speed or that the boiler pump is the proper size. Reference Section 6 - Hydronic Piping of the Knight XL Installation and Operation Manual for boiler pump specifications. | p.45 | |
| Low 24 vac | • Check 120 vac supply to the transformer. • Check wiring connections at the low voltage terminal strip. • Check the wire size/length to remote devices. • Replace the transformer. | p.45 | |
| Watch Dog Error | • Replace the main control board. | p.45 | |
| Write EEProm | • Replace the main control board. | p.45 | |
| CRC Parameters | • Replace the main control board. | p.45 | |
| No Error Stored | • Replace the main control board. | p.45 |