Lochinvar 400

48 pages·2.1 MB·Boiler·PDF·ENDEFRITNLJA
Lochinvar 400
Table of Contents 80 sections Models: 400 - 801 · WARNING · Contents · Hazard definitions · … ShowHide
Models: 400 - 801p.1 WARNINGp.1Contentsp.2Hazard definitionsp.2 DANGERp.2 CAUTIONp.2CAUTIONp.2NOTICEp.2Please read before proceedingp.3 WARNING NOTICEp.3Handling ceramic fiber materialsp.3REMOVAL OF COMBUSTION CHAMBER LININGp.3When servicing boiler –p.4Boiler operation –p.4Boiler water –p.4Freeze protection fluids –p.4What is in this manual?p.5Maintenancep.5Troubleshootingp.5Near boiler pipingp.61 Service (continued)p.7The Knight XL displayp.7NAVIGATION DIALp.7Control inputsp.8Control outputsp.9General Operationp.101 Service 1 Service (continued)p.11Display panel menu accessp.13Display panel parameter accessp.14Parameter tablep.15Viewable and changeable control parametersp.19BMSp.242 Maintenancep.28Maintenance and annual startupp.28Owner maintenance (see the Knight XL User’s Information Manual forp.28Service technician (see the following pages for instructions)p.28General:p.28Dailyp.28ANNUAL START-UPp.28Monthlyp.28Every 6 monthsp.28If combustion or performance indicate need:p.28End of seasonp.28monthsp.282 Maintenance (continued)p.29Address reported problemsp.29Inspect boiler areap.29Inspect boiler interiorp.29Clean condensate trapp.29Check all piping for leaksp.29Flue vent system and air pipingp.30Check water systemp.30Check expansion tankp.30Check boiler relief valvep.30Inspect ignition and flame sense electrodesp.31Check ignition ground wiringp.31Check all boiler wiringp.31Check control settingsp.31Perform start-up and checksp.31Check burner flamep.31Check flame signalp.32Review with ownerp.32Cleaning boiler heat exchangerp.323 Troubleshootingp.33Check control module fusesp.33Before troubleshooting:p.33Check the following:p.33FAULT CAUSE CORRECTIVE ACTIONp.343 Troubleshooting (continued)p.35Checking temperature sensorsp.35FAULT DESCRIPTION CORRECTIVE ACTIONp.37APS:p.38APS / HEXp.38O-TEMP HEX SWITCHp.38Combustion Analysis Procedurep.46CO 2 O 2 CO 2 O 2p.46POSSIBLE CAUSE CORRECTIVE ACTIONp.46Gas valve adjustment procedurep.47THROTTLE ADJUSTMENTp.47SCREWp.47
Page 1 of the Lochinvar 400 user manual —  WARNING
Page 1 · click to enlarge
Page 1
Lochinvar 400 — Models: 400 - 801 diagram (page 1)
Fig. 1 · Models: 400 - 801

Models: 400 - 801

WARNING

This manual must only be used by a qualified heating installer / service technician. Read all instructions, including this manual and the Knight XL Installation and Operation Manual, before installing. Perform steps in the order given. Failure to comply could result in severe personal injury, death, or substantial property damage.

Save this manual for future reference.

KBXII-SER Rev C

Page 2 of the Lochinvar 400 user manual — Table of Contents
Page 2 · Contents
Contents

Contents

Models: 400 - 801p.1 WARNINGp.1Contentsp.2Hazard definitionsp.2 DANGERp.2 CAUTIONp.2CAUTIONp.2NOTICEp.2Please read before proceedingp.3 WARNING NOTICEp.3Handling ceramic fiber materialsp.3REMOVAL OF COMBUSTION CHAMBER LININGp.3When servicing boiler –p.4Boiler operation –p.4Boiler water –p.4Freeze protection fluids –p.4What is in this manual?p.5Maintenancep.5Troubleshootingp.5Near boiler pipingp.61 Service (continued)p.7The Knight XL displayp.7NAVIGATION DIALp.7Control inputsp.8Control outputsp.9General Operationp.101 Service 1 Service (continued)p.11Display panel menu accessp.13Display panel parameter accessp.14Parameter tablep.15Viewable and changeable control parametersp.19BMSp.242 Maintenancep.28Maintenance and annual startupp.28Owner maintenance (see the Knight XL User’s Information Manual forp.28Service technician (see the following pages for instructions)p.28General:p.28Dailyp.28ANNUAL START-UPp.28Monthlyp.28Every 6 monthsp.28If combustion or performance indicate need:p.28End of seasonp.28monthsp.282 Maintenance (continued)p.29Address reported problemsp.29Inspect boiler areap.29Inspect boiler interiorp.29Clean condensate trapp.29Check all piping for leaksp.29Flue vent system and air pipingp.30Check water systemp.30Check expansion tankp.30Check boiler relief valvep.30Inspect ignition and flame sense electrodesp.31Check ignition ground wiringp.31Check all boiler wiringp.31Check control settingsp.31Perform start-up and checksp.31Check burner flamep.31Check flame signalp.32Review with ownerp.32Cleaning boiler heat exchangerp.323 Troubleshootingp.33Check control module fusesp.33Before troubleshooting:p.33Check the following:p.33FAULT CAUSE CORRECTIVE ACTIONp.343 Troubleshooting (continued)p.35Checking temperature sensorsp.35FAULT DESCRIPTION CORRECTIVE ACTIONp.37APS:p.38APS / HEXp.38O-TEMP HEX SWITCHp.38Combustion Analysis Procedurep.46CO 2 O 2 CO 2 O 2p.46POSSIBLE CAUSE CORRECTIVE ACTIONp.46Gas valve adjustment procedurep.47THROTTLE ADJUSTMENTp.47SCREWp.47
Page 3 of the Lochinvar 400 user manual —  WARNING
Page 3 · click to enlarge
Page 3

Please read before proceeding

WARNING NOTICE

Installer – Read all instructions, including this manual and the Knight XL Installation and Operation Manual, before installing. Perform steps in the order given.

When calling or writing about the boiler – Please have the boiler model and serial number from the boiler rating plate.

Consider piping and installation when determining boiler location (see the Knight XL Installation and Operation Manual).

User – This manual is for use only by a qualified heating installer/service technician. Refer to the Knight XL User’s Information Manual for your reference.

Any claims for damage or shortage in shipment must be filed immediately against the transportation company by the consignee.

Have this boiler serviced/inspected by a qualified service technician at least annually.

Failure to comply with the above could result in severe personal injury, death or substantial property damage.

Handling ceramic fiber materials

REMOVAL OF COMBUSTION CHAMBER LINING

The combustion chamber insulation in this appliance contains ceramic fiber material. Ceramic fibers can be converted to cristobalite in very high temperature applications. The International Agency for Research on Cancer (IARC) has concluded, “Crystalline silica inhaled in the form of quartz or cristobalite from occupational sources is carcinogenic to humans (Group 1).” Normal operating temperatures in this appliance are below the level to convert ceramic fibers to cristobalite. Abnormal operating conditions would have to be created to convert the ceramic fibers in this appliance to cristobalite.

WARNING

The ceramic fiber material used in this appliance is an irritant; when handling or replacing the ceramic materials it is advisable that the installer follow these safety guidelines.

Avoid breathing dust and contact with skin and eyes. • Use NIOSH certified dust respirator (N95). This type of respirator is based on the OSHA requirements for cristobalite at the time this document was written. Other types of respirators may be needed depending on the job site conditions. Current NIOSH recommendations can be found on the NIOSH website at http://www.cdc.gov/niosh/homepage.html NIOSH approved respirators, manufacturers, and phone numbers are also listed on this website.

  • Wear long-sleeved, loose fitting clothing, gloves, and eye protection.

Apply enough water to the combustion chamber lining to prevent airborne dust.

Remove the combustion chamber lining from the appliance and place it in a plastic bag for disposal.

Wash potentially contaminated clothes separately from other clothing. Rinse clothes washer thoroughly.

NIOSH stated First Aid.

Eye: Irrigate immediately. Breathing: Fresh air.

Page 4 of the Lochinvar 400 user manual — Freeze protection fluids –
Page 4 · click to enlarge
Page 4

Please read before proceeding

When servicing boiler –

  • To avoid electric shock, disconnect electrical supply before performing maintenance.
  • To avoid severe burns, allow boiler to cool before performing maintenance.

Boiler operation –

  • Do not block flow of combustion or ventilation air to the boiler.
  • Should overheating occur or gas supply fail to shut off, do not turn off or disconnect electrical supply to circulator. Instead, shut off the gas supply at a location external to the appliance.
  • Do not use this boiler if any part has been under water. The possible damage to a flooded appliance can be extensive and present numerous safety hazards. Any appliance that has been under water must be replaced.

Boiler water –

  • Thoroughly flush the system (without boiler connected) to remove sediment. The high-efficiency heat exchanger can be damaged by build-up or corrosion due to sediment.
  • Do not use petroleum-based cleaning or sealing compounds in the boiler system. Gaskets and seals in the system may be damaged. This can result in substantial property damage.
  • Do not use “homemade cures” or “boiler patent medicines”. Serious damage to the boiler, personnel, and/or property may result.
  • Continual fresh make-up water will reduce boiler life. Mineral buildup in the heat exchanger reduces heat transfer, overheats the stainless steel heat exchanger, and causes failure. Addition of oxygen carried in by makeup water can cause internal corrosion. Leaks in boiler piping must be repaired at once to prevent the introduction of makeup water.

Freeze protection fluids –

  • NEVER use automotive antifreeze. Use only inhibited propylene glycol solutions which are specifically formulated for hydronic systems. Ethylene glycol is toxic and can attack gaskets and seals used in hydronic systems.
Page 5 of the Lochinvar 400 user manual — Troubleshooting
Page 5 · click to enlarge
Page 5

What is in this manual?

Maintenance

Near boiler piping • Typical system components

  • Service and maintenance schedules
  • Address reported problems
  • Inspect boiler area and boiler interior
  • Clean condensate trap
  • Check all piping for leaks
  • Check air openings
  • Flue vent system and air piping
  • Check water system
  • Check expansion tank
  • Check boiler relief valve
  • Inspect ignition electrode
  • Check ignition ground wiring
  • Check all boiler wiring
  • Check control settings
  • Perform start-up and checks
  • Check burner flame
  • Check flame signal
  • Check flue gas temperature
  • General maintenance
  • Review with owner
  • Cleaning boiler heat exchanger
  • Oiled bearing circulators

The Knight XL display • Display panel readout, buttons and their functions

Control module inputs • Control module inputs and options

Control module outputs • Control module outputs and options

  • General
  • How the boiler operates
  • How the control module operates
  • Access modes -- user and installer
  • Sequence of operation -- Domestic Hot Water (DHW)/space heating

Control panel menu access • Accessing programming mode and locating menus (See separate guide covering the interface.)

Troubleshooting

Control panel parameter access • Accessing and changing parameters from the display panel

  • Troubleshooting table - No display
  • Checking temperature sensors
  • Sensor tables
  • Troubleshooting table - Fault messages displayed on boiler interface
  • Combustion analysis procedure
  • Gas valve adjustment procedure

Quick start information -- parameter table • An index of available adjustments and readouts, where to access them and where to find detailed information.

  • Knight XL operation
  • A: General
  • B: Temperature Setting
  • C: Data Logging
  • D: Functions
  • E: DHW Settings
  • F: Outdoor Reset
  • G: Anti-cycling
  • H: Control Modes
  • I: Circulation Pumps
  • J: Building Management System (BMS)
  • K: Service Notification
Page 6 of the Lochinvar 400 user manual — Near boiler piping
Page 6 · click to enlarge
Page 6

Near boiler piping

This piping reference is included to specify the Near Boiler Piping specific to the Knight XL. This piping scheme is important for proper operation of the SMART SYSTEM control. See the Knight XL Installation and Operation Manual for more detailed piping diagrams.

Lochinvar 400 — Near boiler piping diagram (page 6)
Fig. 2 · Near boiler piping
Page 7 of the Lochinvar 400 user manual — NAVIGATION DIAL
Page 7 · click to enlarge
Page 7

1 Service (continued)

The Knight XL display

Lochinvar 400 — The Knight XL display diagram (page 7)
Fig. 3 · The Knight XL display

NAVIGATION DIAL

The information on the bottom of the display shows the functions of the two SELECT keys (on either corner), and the NAVIGATION dial (in the center):

MENU = Left SELECT Key SETPOINTS = NAVIGATION Dial - Pressing Down SHDN = Right SELECT Key

Page 8 of the Lochinvar 400 user manual — Control inputs
Page 8 · click to enlarge
Page 8

Control inputs

Lochinvar 400 — Control inputs diagram (page 8)
Fig. 4 · Control inputs
Page 9 of the Lochinvar 400 user manual — Control outputs
Page 9 · click to enlarge
Page 9

1 Service (continued)

Control outputs

Lochinvar 400 — Control outputs diagram (page 9)
Fig. 5 · Control outputs
Page 10 of the Lochinvar 400 user manual — General Operation
Page 10 · click to enlarge
Page 10

General Operation

How the boiler operates

The Knight XL uses an advanced stainless steel heat exchanger and an electronic control module that allows fully condensing operation. The blower pulls in gas and air and pushes flue products out of the boiler through the heat exchanger and flue piping. The control module regulates blower speed to control boiler firing rate. The gas valve senses the amount of air flowing into the boiler and allows only the right amount of gas to flow.

The user can adjust space heating and tank target temperatures by pressing the NAVIGATION dial when “SETPOINTS” is flashing at the bottom of the display. The date and time, and the temperature units can also be changed.

Most parameters are available only to the installer, accessible by entering the installer password (5309).

How the control module operates

Saving parameters (reference the Parameter Table - Table 1-4 on pages 15 - 18 of this manual)

The Knight XL control module receives input from boiler sensors. The control module activates and controls the blower and gas valve to regulate heat input and switches boiler, DHW and system pumps on and off as needed. The user/installer programs the module to meet system needs by adjusting control parameters. These parameters set operating temperatures and boiler operating modes. Boiler operation can be based on boiler outlet water temperature, boiler return water temperature or system supply temperature, depending on the parameter setting.

Please note that the brackets ([]) denote screen status. NOTICE

To save parameters and exit programming:

Press the RIGHT SELECT [SAVE] key and then press the RIGHT SELECT [HOME] key.

To enter a parameter and continue programming:

Press the RIGHT SELECT [SAVE] key 1 time to return to the parameter listings; press again to return to the menu listings. Remember to press the RIGHT SELECT [HOME] key when finished programming in order to save the changes made.

Table 1-1 shows control module normal sequences of operation for space heating and DHW operation. The combined operation sequence is for a typical application, programmed to provide DHW priority.

Show 4 more labels / short text on this page
Access modes · User · Installer · Sequence of operation
Page 11 of the Lochinvar 400 user manual — 1 Service 1 Service (continued)
Page 11 · click to enlarge
Page 11

1 Service 1 Service (continued)

Table 1-1 Sequence of Operation

OPERATIONDISPLAY 1. Upon a call for heat, the gas pressure switch(es) must be closed. 2. Once the gas pressure switch(es) are closed, the control turns on the appropriate pumps (system and boiler pumps for space heating, DHW pump for DHW). The flow switch and/or LWCO must close. 3. The control turns on power to the louver relay. The louver proving switch, air pressure switch, and blocked drain switch must close. 4. The control starts a 15 second prepurge cycle by initiating the blower. 5. The control starts a 4 second trial for ignition by firing the spark electrode and opening the gas valve. 6. If flame is not detected within 1 second after the sparking ends, the control will perform a 10 second post-purge, then start another prepurge cycle and try to light the burner again. On the 501 and larger models, the control will lock out if this second attempt also fails. On the 400 model, the control will perform a total of 4 attempts before locking out. 7. If flame is detected, it holds the firing rate steady for 5 seconds to let the flame stabilize, then it begins to modulate the firing rate based on a set point or some other command (such as a 0-10V BMS signal).
Lochinvar 400 — 1 Service 1 Service (continued) diagram (page 11)
Fig. 6 · 1 Service 1 Service (continued)
Lochinvar 400 — 1 Service 1 Service (continued) diagram (page 11)
Fig. 7 · 1 Service 1 Service (continued)
Lochinvar 400 — 1 Service 1 Service (continued) diagram (page 11)
Fig. 8 · 1 Service 1 Service (continued)
Lochinvar 400 — 1 Service 1 Service (continued) diagram (page 11)
Fig. 9 · 1 Service 1 Service (continued)
Lochinvar 400 — 1 Service 1 Service (continued) diagram (page 11)
Fig. 10 · 1 Service 1 Service (continued)
Page 12 of the Lochinvar 400 user manual — 1 Service 1 Service (continued)
Page 12 · click to enlarge
Page 12

Table 1-1 (continued from previous page) Sequence of Operation

OPERATIONDISPLAY 8. If the space heating call for heat is active, and the tank thermostat or sensor starts a DHW call for heat, the boiler will switch to the DHW mode. If programmed for normal DHW operation (not as a zone), the DHW pump will turn on first, then the boiler pump will turn off 2 seconds later. This will divert the boiler’s outlet water from the heating system and send it to the tank coil instead. The control will then modulate to maintain the outlet temperature to the DHW boiler set point. 9. If the boiler is not part of a Cascade, and both the space heating and DHW calls for heat remain active long enough, the boiler will switch back and forth between the two heating modes until one of them is satisfied. 10. Once both calls for heat are satisfied, the control will turn off the burner. The blower will continue to run during a 10 second postpurge. 11. Any pumps that are running will continue to run for their respective pump delay times before turning off, unless programmed to remain on continuously. A 60 second anti-cycle period will start, which will delay any new call for heat until it times out. 12. In Standby, ready to start a new cycle.
Lochinvar 400 — 1 Service 1 Service (continued) diagram (page 12)
Fig. 11 · 1 Service 1 Service (continued)
Lochinvar 400 — 1 Service 1 Service (continued) diagram (page 12)
Fig. 12 · 1 Service 1 Service (continued)
Lochinvar 400 — 1 Service 1 Service (continued) diagram (page 12)
Fig. 13 · 1 Service 1 Service (continued)
Lochinvar 400 — 1 Service 1 Service (continued) diagram (page 12)
Fig. 14 · 1 Service 1 Service (continued)
Lochinvar 400 — 1 Service 1 Service (continued) diagram (page 12)
Fig. 15 · 1 Service 1 Service (continued)
Page 13 of the Lochinvar 400 user manual — Display panel menu access
Page 13 · click to enlarge
Page 13

1 Service (continued)

Display panel menu access

Table 1-2 Use this procedure to access menus from the display panel

Lochinvar 400 — Display panel menu access diagram (page 13)
Fig. 16 · Display panel menu access

[MENU] Press and hold the LEFT SELECT soft key [MENU] for five (5) seconds.

Rotate the NAVIGATION dial clockwise until 5 is displayed (first digit on the left).

Press the NAVIGATION dial to select the next digit. Rotate the NAVIGATION dial clockwise until 3 is shown in the display.

Press the NAVIGATION dial 2 times to move to the last digit. Rotate the NAVIGATION dial counterclockwise until 9 is displayed.

Rotate the NAVIGATION dial counterclockwise to select a category.

Page 14 of the Lochinvar 400 user manual — Display panel parameter access
Page 14 · click to enlarge
Page 14

Display panel parameter access

Table 1-3 This is a typical example of accessing a parameter, shown for parameter Temperature Settings, MIN SH Setpt

Lochinvar 400 — Display panel parameter access diagram (page 14)
Fig. 17 · Display panel parameter access

This example shows how to access parameter Temperature Settings. The first display shown is at the beginning of the menu listings, after entering the installer access code.

Rotate the NAVIGATION dial counterclockwise until the arrow (>) is next to TEMPERATURE SETTINGS.

Rotate the NAVIGATION dial counterclockwise until the arrow (>) is next to MIN SETPT.

[SAVE] Press the RIGHT SELECT soft key [SAVE] one time.

[EXIT] Press the LEFT SELECT soft key [EXIT] if all desired changes have been made.

Page 15 of the Lochinvar 400 user manual — Parameter table
Page 15 · click to enlarge
Page 15

1 Service (continued)

Parameter table

Table 1-4 This table lists SMART SYSTEM control module parameters and where to access them

Lochinvar 400 — Parameter table diagram (page 15)
Fig. 18 · Parameter table

Software Version (read only) 19 No No Yes No

SH Night Setback Offset 19 No No Yes Yes

SH Night Setback On Times 19 No No Yes Yes

SH Night Setback Off Times 19 No No Yes Yes

DHW Night Setback Offset 19 No No Yes Yes

DHW Night Setback On Times 19 No No Yes Yes

DHW Night Setback Off Times 19 No No Yes Yes

Minimum SH Set Point 20 No No Yes Yes

Maximum SH Set Point 20 No No Yes Yes

Freeze Protection Pump On 20 No No Yes Yes

Freeze Protection Burner On 20 No No Yes Yes

Freeze Protection Burner Differential 20 No No Yes Yes

Page 16 of the Lochinvar 400 user manual — Parameter table
Page 16 · click to enlarge
Page 16

Parameter table

Table 1-4 (continued from previous page) This table lists SMART SYSTEM control module parameters and where to access them

Lochinvar 400 — Parameter table diagram (page 16)
Fig. 19 · Parameter table

DHW Boiler Set Point 21 No No Yes Yes

Tank Set Point Differential 21 No No Yes Yes

Tank Minimum Set Point 21 No No Yes Yes

Tank Maximum Set Point 21 No No Yes Yes

Fan Speed Limiting for DHW 21 No No Yes Yes

Set Point 1 at Low Outdoor Temp 1 22 No No Yes Yes

Set Point 1 at High Outdoor Temp 1 22 No No Yes Yes

Outdoor Air Shutdown SH1 22 No No Yes Yes

Outdoor Air Shutdown Differential SH1 23 No No Yes Yes

Shift Reset Curve SH1 23 No No Yes Yes

Set Point 2 at Low Outdoor Temp 2 22 No No Yes Yes

Set Point 2 at High Outdoor Temp 2 22 No No Yes Yes

Outdoor Air Shutdown SH2 22 No No Yes Yes

Outdoor Air Shutdown Differential SH2 23 No No Yes Yes

Shift Reset Curve SH2 23 No No Yes Yes

Set Point 3 at Low Outdoor Temp 3 22 No No Yes Yes

Set Point 3 at High Outdoor Temp 3 22 No No Yes Yes

Outdoor Air Shutdown SH3 22 No No Yes Yes

Outdoor Air Shutdown Differential SH3 23 No No Yes Yes

Shift Reset Curve SH3 23 No No Yes Yes

Page 17 of the Lochinvar 400 user manual — Parameter table
Page 17 · click to enlarge
Page 17

1 Service (continued)

Parameter table

Table 1-4 (continued from previous page) This table lists SMART SYSTEM control module parameters and where to access them

Lochinvar 400 — Parameter table diagram (page 17)
Fig. 20 · Parameter table

Max Cascade Set Point 25 No No Yes Yes

Min Next On Time 25 No No Yes Yes

Boiler Pump Anti-Seize Delay 26 No No Yes Yes

Boiler Pump Min Voltage 26 No No Yes Yes

DHW Pump Anti-Seize Delay 26 No No Yes Yes

System Pump Anti-Seize Delay 26 No No Yes Yes

Page 18 of the Lochinvar 400 user manual — Parameter table
Page 18 · click to enlarge
Page 18

Parameter table

Table 1-4 (continued from previous page) This table lists SMART SYSTEM control module parameters and where to access them

Lochinvar 400 — Parameter table diagram (page 18)
Fig. 21 · Parameter table

Rate at Min Volts 26 No No Yes Yes

Rate at Max Volts 26 No No Yes Yes

Set Point at Min Volts 27 No No Yes Yes

Set Point at Max Volts 27 No No Yes Yes

Service Notification Running Time 27 No No Yes Yes

Service Name and Phone Number 27 No No Yes Yes

Page 19 of the Lochinvar 400 user manual — Viewable and changeable control parameters
Page 19 · click to enlarge
Page 19

1 Service (continued)

Viewable and changeable control parameters

Space Heating (SH) and Domestic Hot Water (DHW) Night Setback On Times

This is the time in which the SH Night Setback Offset becomes active. There are 7 start times and 7 stop times each for the space heating and DHW night setback features. Both may be set to any time within a 7-day week. These settings are referred to as triggers. Multiple start or stop triggers may be set within a single day, if desired. When a start trigger and a stop trigger are set to the same time, the stop trigger has priority. The installer may adjust the space heating night setback start triggers by accessing the SH Night Setback On Times parameter. The DHW start triggers in the DHW Night Setback On Times parameter. This screen shows the start trigger number, the day of the week, and the time of day.

The control uses an internal clock for the night setback feature and for logging of events. For these features to work correctly, the clock must be set when the boiler is first installed or anytime the boiler has been powered off for more than four (4) hours. This parameter must be accessed to set the clock.

1. When the screen is first accessed, start trigger number 1 is shown. If a different trigger number is desired, the installer can rotate the NAVIGATION dial until the desired trigger number is displayed. Once the desired trigger number is selected, the installer can press the NAVIGATION dial and the day of the week will start to flash. 2. The installer can adjust the day of the week to the one he wishes to set. Once the day is set, the installer can press the NAVIGATION dial and the hour will begin to flash. 3. After setting the hour, the installer can press the NAVIGATION dial and the minutes will flash. Once all settings have been made, the installer can press the RIGHT SELECT [SAVE] key. The installer can now select a different trigger and adjust the settings for that trigger. 4. Once all adjustments are made, the installer can press the RIGHT SELECT [SAVE] key to save all of the new settings and return to the General menu, or press the LEFT SELECT [EXIT] key to return to the General menu without saving the changes.

The software version allows the user to view the software version in use by the control. This software controls the operation of the boiler. When a new software version becomes available, the existing control can be replaced with a new control to update the software.

Software version is read only.

Temperature units (°C / °F)

The control can be configured to display temperature in either °C or °F. This parameter can be changed by the user or the installer by accessing the Temperature Units parameter. The default is °F.

Space Heating (SH) and Domestic Hot Water (DHW) Night Setback Offset

Once the unit’s internal clock has been set correctly, the Night Setback feature can be used to program a lower set point during unoccupied times. Both the space heating and DHW can be programmed for night setback. When in night setback, the control reduces the set point by a fixed amount. For space heating, it subtracts the space heating night setback offset from each of the SH user set points (SH1, 2, and 3 Set point parameters), or the calculated outdoor reset set point (if lower). For DHW, it subtracts the DHW night setback offset from the tank set point (Tank Set point parameter).

Space Heating (SH) and Domestic Hot Water (DHW) Night Setback Off Times The corresponding space heating night setback stop triggers are set by accessing the SH Night Setback Off Times parameter. The stop triggers for the DHW night setback feature can be adjusted by accessing the DHW Night Setback Off Times parameter. The adjustment procedure for these parameters is identical to the space heating start triggers described above.

Night Setback Override Any Night Setback On trigger currently active or scheduled within the next seven (7) days can be skipped. To skip a trigger, press the MENU key for 5 seconds, enter the user password, and press the SAVE key. Rotate the NAVIGATION dial to NSB OVERRIDE, and press the NAVIGATION dial. A list of the current (if active) and upcoming NSB On triggers will appear.

The installer may adjust the space heating night setback offset by accessing the SH Night Setback Offset parameter and the DHW night setback offset by accessing the DHW Night Setback Offset parameter. The minimum setting is 0°F (0°C) and the maximum setting is 90°F (50°C).

General · Time and Date · Software Version

Page 20 of the Lochinvar 400 user manual — Viewable and changeable control parameters
Page 20 · click to enlarge
Page 20

Rotate the NAVIGATION dial to select the trigger you wish to skip and press the NAVIGATION dial. “SK” will appear next to that trigger. You can rotate the NAVIGATION dial again to select another trigger if you wish. If you wish to reinstate a skipped trigger, re-select that trigger and press the NAVIGATION dial again. The “SK” next to that trigger will disappear. Press the HOME key to save these skipped triggers. If you selected any currently active trigger(s), the current Night Setback will be cancelled.

SH1 - SH3 Differential Set Point The SH differential sets how many degrees below the offset the temperature has to drop before the boiler turns back on. This parameter can only be changed by the installer by accessing the SH1, 2 and 3 Differential Set point parameters. The range is 0°F to 60°F. The default is 20°F.

Reset log errors The reset log errors function clears the last 10 errors log.

Functions Service Mode Delay By pressing the pin button on the front of the display for five (5) seconds, the control will be placed in Service Mode. This will override all other heat demands. The Service Mode allows the installer to set the unit to any firing rate for the purpose of combustion analysis. The delay sets the length of time the boiler will stay in the Service Mode if no keys have been pressed before going back to its original state. This parameter can only be changed by the installer by accessing the Service Mode Delay parameter. The time range of this parameter is 1 to 10 minutes. The default value is 10 minutes.

This is the time in which the display remains illuminated. The range is 10 seconds to 10 minutes. The default is 3 minutes.

Space Heating (SH1, SH2, SH3) Set Point

There are three (3) individual user set points for better zone control. These are listed as SH1 Set Point through SH3 Set Point. If multiple set points are calling for heat the highest set point has priority. The range is SH Minimum Set point to SH Maximum Set point. The default is 125°F (52°C).

Freeze Protection Pump On The SMART SYSTEM control will turn on the boiler and system pump outputs whenever the inlet temperature drops below this setting. This is done to prevent the water in the heat exchanger from freezing. Certain low-temperature applications (such as snow melt) can operate at temperatures around freezing, so this setting needs to be lowered in these cases. The installer can adjust the temperature at which the pump outputs are turned on by accessing Freeze Protection Pump On parameter. The minimum setting is -3°F (-19°C), and the maximum setting is 45°F (7.2°C). The default setting is 45°F (7.2°C).

Space Heating (SH) Minimum Set Point

The SH minimum set point sets the minimum water temperature set point that can be used for space heating operation. The user or installer will not be able to program the control with a lower SH set point. This parameter can only be changed by the installer by accessing Minimum SH Set point parameter. The temperature range of this parameter is 32°F (0°C) to the space heating maximum set point. The default value is 32°F (21°C).

Space Heating (SH) Maximum Set Point

The SH maximum set point sets the maximum water temperature set point that can be used for space heating. The user or installer will not be able to program the control with a higher SH set point. This parameter can only be changed by the installer by accessing Maximum SH Set point parameter. The temperature range of this parameter is the space heating minimum set point to 180°F (82°C). The default value is 180°F (82°C).

Freeze Protection Burner On If running the pumps does not prevent the inlet temperature from falling closer to freezing, the SMART SYSTEM control will fire the burner at low fire. The installer can adjust the temperature at which the burner fires by adjusting the Freeze Protection Burner On parameter. The minimum setting is -3°F (-19°C), and the maximum setting is 45°F (7.2°C). The default setting is 37°F (2.8°C).

SH1 - SH3 Offset Set Point

The SH offset sets how many degrees above set point the temperature has to go before the boiler will shut off. This parameter can only be changed by the installer by accessing parameters SH1, 2 and 3 Offset Set point parameters. The temperature range of these parameters is 0°F to 20°F. The default value is 10°F.

Freeze Protection Burner Differential Once the burner has started firing due to a low inlet temperature, the inlet temperature must increase by this amount before the burner turns back off. The installer can adjust this differential by accessing the Freeze Protection Burner Differential parameter. The minimum setting is 0°F, and the maximum is 20°F. The default setting is 5°F (2.8°C).

Data Logging · Display Timeout · Temperature Settings

Page 21 of the Lochinvar 400 user manual — 1 Service (continued)
Page 21 · click to enlarge
Page 21

1 Service (continued)

DHW Boiler Set Point

When a boiler has a DHW demand and it receives a space heating demand, the SMART SYSTEM control will start a timer. Once the timer expires, it will stop the DHW demand and service the space heating demand. The installer can adjust the length of time the boiler will service the DHW demand by accessing the DHW/SW Switching Time parameter. The minimum setting is 0 minutes and the maximum setting is 50 minutes. The default setting is 30 minutes.

When a DHW call for heat becomes active, the control will use the DHW boiler set point to determine the firing rate of the boiler based on the boiler outlet water temperature, or system temperature when DHW is programmed as a zone.

This parameter can be changed by the installer by accessing the DHW Boiler Set point parameter. The temperature range of this parameter is 68°F (20°C) to 180°F (82°C). The default value is 180°F (82°C).

Tank Minimum Set Point

DHW Tank Set Point

This setting controls the minimum tank set point for the tank temperature. The installer can adjust this by accessing the Tank Minimum Set point parameter. The minimum setting is 60°F (16°C) and the maximum setting is the maximum tank set point (Tank Maximum Set point parameter). The default value is 60° (16°C).

By installing a tank sensor, the SMART SYSTEM control can perform the tank thermostat function. The SMART SYSTEM control automatically detects the presence of this sensor, and generates a DHW call for heat when the tank temperature drops below the tank set point differential (Tank Set point Differential parameter), and finishes the call for heat when the tank temperature reaches tank set point + offset. This parameter can be changed by the installer by accessing the DHW Tank Set point parameter. The temperature range of this parameter tank minimum set point to tank maximum set point. The default value is 125°F (52°C).

Tank Maximum Set Point

This setting controls the maximum tank set point for the tank temperature. The installer can adjust this by accessing the Tank Maximum Set point parameter. The minimum setting is the minimum tank set point (Tank Minimum Set point parameter) and the maximum setting is 190°F (88°C). The default value is 140°F (60°C).

Tank Set Point Differential

When a tank sensor is installed, the tank temperature must drop this amount below the tank set point (DHW Tank Set point parameter) before the boiler turns back on. The installer can adjust this setting by accessing the Tank Set point Differential parameter. The minimum setting is 0° (0°C), and the maximum is 40°F (22°C). The default setting is 6°F (3°C).

This parameter determines whether the Knight XL boiler treats the indirect DHW tank as a separate load, or as a zone on the primary loop. When programmed as a separate load, the boiler will turn on the DHW pump and then turn off the boiler pump when an indirect DHW demand begins. When programmed as a zone, the boiler will turn on the DHW pump, leave the boiler pump on and change the system set point to the DHW boiler set point (DHW Boiler Set point parameter).

This parameter reflects the degrees above DHW boiler set point the temperature has to go before the boiler will shut off. The range is 0°F (0°C) to 40°F (22°C). The default setting is 10°F (6°C).

This setting may be changed by the installer by accessing the DHW Type parameter. The choices are NORMAL and ZONE. The default setting is NORMAL.

This parameter reflects the degrees below DHW boiler set point the temperature has to go before the boiler turns back on. The range is 0°F (0°C) to 60°F (33°C). The default setting is 20°F (13°C).

Fan Speed Limiting for Indirect DHW Tank

This parameter determines the maximum fan speed (and therefore the maximum rate) to be used when heating an indirect DHW tank. This setting may be used when the tank is unable to accept all of the BTU’s available from the boiler. This parameter may be adjusted by the installer by accessing the Fan Speed Limiting for Indirect DHW Tank parameter. The default value is the maximum fan speed for that model.

When a boiler has a space heating demand and it receives a DHW demand, it will immediately switch to the DHW demand and start a timer. Once the timer has expired, the boiler will switch back to the space heating demand and start another timer. Once this timer expires, it will switch back to the DHW demand. The installer can adjust the length of time the boiler will service the space heating demand by accessing SH/DHW Switching Time parameter. The minimum setting is 0 minutes and the maximum setting is 50 minutes. The default time is 30 minutes.

Show 6 more labels / short text on this page
DHW Settings · DHW/SH Switching Time · DHW Type · DHW Boiler Offset · DHW Boiler Differential · SH/DHW Switching Time
Page 22 of the Lochinvar 400 user manual — Viewable and changeable control parameters
Page 22 · click to enlarge
Page 22

Set Point (1 - 3) at Low Outdoor Temperature

When the outdoor air temperature drops to the Outdoor (1 - 3) Low parameters, the calculated set point will be at this setting (FIG. 1-1). If the outdoor air temperature drops further, the set point will continue to increase above this setting. However, if SH1, SH2, and SH3 are set lower, the water temperature will be limited by these set points instead. These parameters can be changed by the installer by accessing the Set point 1 at Low Outdoor Temp 1, Set point 2 at Low Outdoor Temp 2 and Set point 3 at Low Outdoor Temp 3 parameters. The temperature range of this parameter is 68°F (20°C) to 180°F (82°C). The default value is 180°C (82°C).

The option of controlling up to three (3) different outdoor resets for low outdoor temperatures is available.

Outdoor (1 - 3) Low

When the outdoor air temperature drops to this point, the water temperature will be at the Set point 1 at Low Outdoor Temp 1, Set point 2 at Low Outdoor Temp 2 and Set point 3 at Low Outdoor Temp 3 parameters (FIG. 1-1). If the outdoor air temperature drops further, the set point will continue to increase above this setting. This parameter can be changed by the installer by accessing the Outdoor (1-3) Low parameter. The temperature range of this parameter is -39°F (-39°C) to high outdoor temperature set point. The default value is 25°F (-4°C).

Set Point (1 - 3) at High Outdoor Temperature When the outdoor air temperature rises to or above Outdoor (1 - 3) High parameters, the calculated set point will be at this setting (FIG. 1-1). These parameters can be changed by the installer by accessing the Set point 1 at High Outdoor Temp 1, Set point 2 at High Outdoor Temp 2 and Set point 3 at High Outdoor Temp 3 parameters. The temperature range of this parameter is 68°F (20°C) to 190°F (88°C). The default value is 70°F (21°C).

Outdoor (1 - 3) High

When the outdoor air temperature rises to or above this point, the water temperature will be at the Set point 1 at High Outdoor Temp 1, Set point 2 at High Outdoor Temp 2 and Set point 3 at High Outdoor Temp 3 parameters (FIG. 1-1). This parameter can be changed by the installer by accessing the Outdoor (1-3) High parameter. The temperature range of this parameter is low outdoor temperature set point to 104°F (40°C). The default value is 70°F (21°C).

Outdoor Air Shutdown (SH1 - SH3)

When the outdoor temperature rises above this point, the control will block all SH demands (DHW demands will still be active). These parameters can be changed by the installer by accessing the Outdoor Air Shutdown SH1, SH2, and SH3 parameters. The temperature range of this parameter is 32°F (0°C) to 104°F (40°C). The default value is 70°F (21°C).

Figure 1-1 Outdoor Air Reset Curve

Lochinvar 400 — Viewable and changeable control parameters diagram (page 22)
Fig. 22 · Viewable and changeable control parameters

Outdoor Reset

Page 23 of the Lochinvar 400 user manual — 1 Service (continued)
Page 23 · click to enlarge
Page 23

1 Service (continued)

Outdoor Air Shutdown Differential (SH1 - SH3)

The outdoor air shutdown differential parameter is the number of degrees below Outdoor Air Shutdown SH1, SH2, and SH3 parameters the outdoor air temperature must go before the boiler will respond to a SH demand. These parameters can be changed by the installer by accessing the Outdoor Air Shutdown Differential SH1, SH2, and SH3 parameters The temperature range of this parameter is 0°F (0°C) to 54°F (30°C). The default value is 10°F (6°C).

Once a SH demand has been satisfied, a set amount of time must elapse before the control will respond to a new SH demand. The control will block the new heat demand and anti-cycling will be shown in the display until the time has elapsed or the water temperature drops below the Anti-Cycling Override Differential parameter. This parameter can be changed by the installer by accessing the Anti-Cycling Time parameter. The time range for this parameter is 1 minute to 10 minutes. The default value is 1 minute.

Shift Reset Curve (SH1 - SH3)

There is a shift reset curve for each outdoor reset. The shift reset curve parameter shifts the actual set point above or below the calculated set point by the number of degrees in this parameter. These parameters can be changed by the installer by accessing the Shift Reset Curve SH1, SH2, and SH3 parameters. The temperature range of this parameter is -17°F (-10°C) to 18°F (10°C). The default value is 0°F (0°C). This feature will be active if this parameter is set to anything other than 0°F (0°C).

The control will bypass the anti-cycling time if the inlet water temperature drops too much. The control will use the inlet water temperature the boiler was at when it shut off as the starting point. If the inlet temperature drops below the temperature parameter the control will abort anti-cycling and allow the boiler to fire. This parameter can be changed by the installer by accessing the Anti-Cycling Override Differential parameter. The temperature range of this parameter is 0°F (0°C) to 54°F (30°C). The default value is 10°F (6°C).

If a SH demand lasts longer than the programmed time delay setting and there have been no DHW demands, the control will increase the water temperature set point by the amount in this parameter. If the SH demand continues through another time period, the set point will be increased again. This will continue until either the SH demand ends, a maximum of 20 increases has occurred, or SH1, SH2, SH3 maximum set point has been reached. Once the SH demand has been satisfied the set point will revert back to its calculated setting. The boost temperature can be changed by the installer by accessing the Boost Temperature parameter. The temperature range of this parameter is 0°F (0°C) to 25°F (14°C). The default value is 0°F (0°C). This feature will be active if this parameter is set to anything other than 0°F (0°C).

Ramp Delay (Enable / Disable)

This parameter allows the installer to enable or disable the SH ramp delay. The default setting is disabled.

The boost time parameter sets the amount of time that must elapse with a SH demand before the water temperature calculated set point will be increased. This parameter can be changed by the installer by accessing the Boost Time parameter. The time range for this parameter is 0 minute to 50 minutes. The default value is 0 minutes.

Show 5 more labels / short text on this page
Anti-Cycling · Anti-Cycling Time · Anti-Cycling Override Differential · Boost Temperature · Boost Time
Page 24 of the Lochinvar 400 user manual — BMS
Page 24 · click to enlarge
Page 24

Please note that the brackets ([]) denote screen status. NOTICE

The SH controlling sensor parameter selects the sensor the control will use to regulate the boiler firing rate. This parameter is adjustable by the installer by accessing the Controlling Sensor parameter. The sensor selections are as follows: The outlet sensor regulates the firing rate based on the outlet water temperature of the boiler and the inlet sensor regulates the firing rate based on the inlet water temperature of the boiler. If the outlet sensor is selected, and the optional system supply sensor is connected, the control will regulate the firing rate based on the system supply sensor temperature. The default sensor is the Outlet Sensor.

The SMART SYSTEM control can be programmed to limit the firing rate for a fixed period of time at the start of a space heating demand. There are six (6) possible limits, each with their own time delay. The first limit applies as soon as the burner starts. Once its time delay expires, the second limit is applied and its timer begins. The control steps through these limits until the 6th (sixth) limit expires. Note, however, that the 6th limit will also limit the rate for the rest of that heat demand. The installer can adjust the firing limits and time delays by accessing the Ramp Settings parameter. Once this parameter is selected, the screen will show the step number, the time delay for that step and the limit value corresponding with that step. If the installer wishes to adjust one of the values in that step, he can press the NAVIGATION dial until the value he wishes to change is flashing. The installer can then rotate the NAVIGATION dial to adjust that value. If the installer presses the RIGHT SELECT [SAVE] key while the limit value is flashing, the step value will flash again. The installer can then select the next step and adjust the delay and limit values corresponding with that step.

When controlling the boiler through the 0 - 10V BMS input or through ModBus, the boiler can be enabled one of two ways. With the BMS Thermostat Input parameter set to ACTIVE, the boiler will be enabled by closing the Heat/Loop Demand 1 input. When set to INACTIVE, the boiler will be enabled by the voltage level on the 0 - 10V input (in the case of 0 - 10V BMS control), or the 0 - 10V input value received through ModBus. The default value is INACTIVE.

BMS

When finished, the installer can press the RIGHT SELECT [SAVE] key to store the new settings, or the LEFT SELECT [EXIT] key to return to the Anti-Cycling parameter list without saving the changes. The delay value can be set between 0 minutes and 20 minutes. The limit value can be set between 0% and 100%.

The set point or modulation of the boiler may be controlled through the 0 - 10V BMS input or through ModBus. When the BMS parameter is set to INACTIVE, the 0 - 10V input will be ignored. When set to ACTIVE, the set point or modulation will be controlled by the voltage on the 0 - 10V input (in the case of 0 - 10V BMS control), or the 0 - 10V input value received through ModBus. The default value is INACTIVE.

Figure 1-2 Ramp Delay Interval

Lochinvar 400 — BMS diagram (page 24)
Fig. 23
Show 4 more labels / short text on this page
Ramp Settings · Control modes · Controlling Sensor · BMS Thermostat Input
Page 25 of the Lochinvar 400 user manual — 1 Service (continued)
Page 25 · click to enlarge
Page 25

1 Service (continued)

ModBus When BMS is set to ACTIVE (see BMS Active / Inactive) and the boiler is being controlled through ModBus, set ModBus parameter to ACTIVE. Otherwise, set the ModBus parameter to INACTIVE. Note that the boiler can still be monitored by ModBus with this parameter set to INACTIVE. The default value is INACTIVE.

As the calculated load increases further and both boilers ramp up to 90%, it lowers the rate of the first two (2) boilers to 60% and brings the next boiler on at 60%. The three (3) boilers then modulate together. As the calculated load decreases, the boilers will reach a lower threshold (default = 30%), at which time the last boiler (the third in our example) will turn off and the Cascade will increase the rates of the remaining boilers to provide the equivalent total output as before ((3 x 30%) / 2 = 45% in our example).

ModBus T/O The amount of time the unit controls will wait to receive a communication string from the BMS controller before reverting back to its own internal parameters. This parameter is adjustable by the installer by accessing the ModBus T/O parameter. The adjustment range of this parameter is 5 seconds to 2 minutes. The default value is 10 seconds.

Maximum Cascade Set Point This parameter determines the set point used by the individual boilers in a Cascade. When a boiler is commanded to fire by the Leader boiler, it will attempt to achieve this temperature at its outlet. The Leader boiler will limit the modulation of the last boiler to fire in order to hold the temperature at the system supply sensor to the user set point. If any of the boiler outlet temperatures reach the maximum cascade set point, the boiler will then modulate down on its own in order to keep its outlet temperature within the maximum cascade set point. Therefore, this parameter can be used to limit the outlet temperatures of all the boilers in a Cascade. Note that this parameter does not apply when the boiler is heating an indirect DHW tank. This parameter is adjustable by the installer by accessing the Maximum Cascade Set Point parameter. The temperature range of this parameter is 32° (0°C) to 190°F (88°C). The default maximum cascade set point is 185°F (85°C).

Cascade Address The boiler designated as the Leader needs to be programmed with address 0. All the Member boilers require addresses from 1 to 7, and the addresses must be different for each Member. The addresses can be in any order, regardless of the order in which the units are wired together. This parameter is adjustable by the installer by accessing the Cascade Address parameter. The outdoor air (if used) and system supply sensor must be connected to the Leader boiler. The default address is 1.

Cascade Offset This parameter determines how much the temperature must go above set point before the lead boiler will turn off. This parameter can be adjusted by the installer by accessing the Cascade Offset parameter. The temperature range of this parameter is 0° to 20°F (11°C) The default value is 10°F (6°C).

If installing the boilers in an existing system, the new boilers should be programmed as the Leader and/or the higher number addresses.

Cascade Type (L/L / EFF) There are two (2) options for the way a Cascade divides the load between its heaters. The first is Lead/Lag, designated as L/L in the menu. This method is used when it is desired to have the least amount of total flow through the boilers. This method will modulate the last two (2) boilers. This provides for smooth transitions when a boiler turns on or off. When the last boiler reaches 100% and the calculated load is still increasing, it will start the next boiler at 20% and reduce the previous boiler to 80%, thus eliminating the sudden jump in total output of the Cascade. When the calculated load is decreasing and the last boiler gets down to 20% fire, it will hold it there and start lowering the firing rate on the next-to-last boiler. When the next-to-last boiler reaches 20%, it will turn the last boiler off and raise the rate of the next-to-last boiler to 40%, thus eliminating the sudden drop in total output of the Cascade.

Cascade Differential This parameter determines how much the temperature must go below the turn off temperature (Set point + Offset) before the lead boiler turns on. This parameter can be adjusted by the installer by accessing the Cascade Differential parameter. The temperature range of this parameter is 0°F to 60°F (33°C) The default value is 20°F (11°C).

Minimum On/Off Time In order to prevent units in a Cascade from short cycling, this parameter defines the minimum ON and OFF time for each unit. The installer can adjust this time by accessing the Minimum On/Off Time parameter. The minimum setting is 0 seconds and the maximum setting is 10 minutes. The default is 30 seconds.

The other Cascade divider method is Efficiency Optimization, designated as EFF in the menu. This method is used, as the name implies, when it is desired to have the most efficient system. When the first boiler reaches a certain rate (default = 90%), it lowers its rate to 45% and turns on the next boiler at 45%. The two (2) boilers then modulate at the same rate.

Minimum Next On Time In order to reduce the risk of temperature overshoot with a Cascade, this parameter defines the minimum time delay from starting one unit until the next unit may be started. The installer can adjust this time delay by accessing the Minimum Next On Time parameter. The minimum setting is 0 minutes and the maximum setting is 10 minutes. The default is 60 seconds.

Page 26 of the Lochinvar 400 user manual — BMS
Page 26 · click to enlarge
Page 26

DHW Pump Anti-Seize Delay

If the boiler pump does not run for 24 hours, it will be turned on briefly to prevent it from seizing. The length of time it runs is determined by the DHW Pump Anti-Seize Delay parameter. The range of this setting is 0 seconds to 50 minutes. The default setting is 20 seconds.

The system pump delay parameter sets the length of time the system pump (if connected) will run after a SH demand has been satisfied. This parameter is adjustable by the installer by accessing the System Pump Delay parameter. The time range for this parameter is 1 second to 40 minutes. The default time is 30 seconds.

System Pump Anti-Seize Delay

If the boiler pump does not run for 24 hours, it will be turned on briefly to prevent it from seizing. The length of time it runs is determined by the System Pump Anti-Seize Delay parameter. The range of this setting is 0 seconds to 50 minutes. The default setting is 20 seconds.

The SH pump delay parameter sets the length of time the boiler pump will run after a SH demand has been satisfied. Setting the delay time to 0 will disable the pump. This parameter is adjustable by the installer by accessing the Boiler Pump Delay parameter. The time range for this parameter is 1 second to 40 minutes. The default time is 30 seconds.

BMS

When programmed for BMS control through the 0 - 10V BMS input or through ModBus, the 0 - 10V signal can be interpreted as either a modulation command or a set point. When the BMS Type parameter is set to POWER, the 0 - 10V signal will control the modulation. When set to SETPOINT, the 0 - 10V signal will control the SH set point. The default setting is SETPOINT.

The DHW pump delay parameter sets the length of time the DHW pump (if connected) will run after a DHW demand has been satisfied. This parameter is adjustable by the installer by accessing the DHW Pump Delay parameter. The time range for this parameter is 10 seconds to 40 minutes. The default time is 1 minute.

Boiler Pump Anti-Seize Delay

When programmed for BMS control through the 0 - 10V BMS input or through ModBus, the Volts at Minimum parameter should be set to the minimum voltage signal sent to the SMART SYSTEM control. The range of this parameter is 0.0V to the Volts at Maximum value. The default setting is 2.0V.

If the boiler pump does not run for 24 hours, it will be turned on briefly to prevent it from seizing. The length of time it runs is determined by the Boiler Pump Anti-Seize Delay parameter. The range of this setting is 0 seconds to 50 minutes. The default setting is 20 seconds.

Boiler Pump Minimum Voltage

The speed of the boiler pump can be controlled by the SMART SYSTEM control in order to maintain a minimum T through the heat exchanger. Thus, as the firing rate decreases, the speed of the boiler pump can decrease as well. The SMART SYSTEM control outputs a 0 - 10V signal to the boiler pump to control its speed. The Boiler Pump Minimum Voltage parameter determines the minimum voltage given to the boiler pump, thereby setting its minimum speed. The range of this setting is 2.5V to 10V. The default setting is 3.5V.

When programmed for BMS control through the 0 - 10V BMS input or through ModBus, the Volts at Maximum parameter should be set to the maximum voltage signal sent to the SMART SYSTEM control. The range of this parameter is the Volts at Minimum value to 10.0V. The default value is 10.0V.

Rate at Minimum Volts

When programmed for BMS control through the 0 - 10V BMS input or through ModBus and the BMS Type is programmed as POWER, the modulation percentage represented by the Volts at Minimum parameter is set by the Rate at Minimum Volts parameter. The minimum value is 0% and the maximum is the Rate at Maximum Volts setting. The default value is 20%.

The system pump can be programmed to operate in response to any of the Room Thermostat inputs, or to run continuously until the boiler goes into Outdoor Shutdown. To program the system pump to operate only with a space heating call for heat, set the System Pump Type parameter to CFH. To program the system pump to run continuously until outdoor shutdown starts, set the System Pump Type parameter to WWSD. The default setting is CFH.

Rate at Maximum Volts

When programmed for BMS control through the 0 - 10V BMS input or through ModBus and the BMS Type is programmed as POWER, the modulation percentage represented by the Volts at Maximum parameter is set by the Rate at Maximum Volts parameter. The minimum value is the Rate at Minimum Volts setting and the maximum is 100%. The default value is 100%.

Show 8 more labels / short text on this page
Circulation pumps · System Pump Delay · Boiler Pump Delay · BMS Type · DHW Pump Delay · Volts at Minimum · Volts at Maximum · System Pump Type
Page 27 of the Lochinvar 400 user manual — 1 Service (continued)
Page 27 · click to enlarge
Page 27

1 Service (continued)

Set Point at Minimum Volts

When programmed for BMS control through the 0 - 10V BMS input or through ModBus and the BMS Type is programmed as SETPOINT, the set point represented by the Volts at Minimum parameter is set by the Set Point at Maximum Volts parameter. The minimum value is 32°F (0°C) and the maximum is the Set Point at Maximum Volts setting. The default value is 70°F (21°C).

When the boiler control determines that a scheduled service is due based on the number of boiler cycles, the boiler display will alternate the standard boiler display text with the message SERVICE DUE every 5 seconds. This parameter is adjustable by the installer by accessing the Service Notification Cycles parameter. The range for this parameter is 0 cycles to 100,000 cycles. The default is 50,000 cycles.

Set Point at Maximum Volts

When programmed for BMS control through the 0 - 10V BMS input or through ModBus and the BMS Type is programmed as SETPOINT, the set point represented by the Volts at Maximum parameter is set by the Set Point at Maximum Volts parameter. The minimum value is the Set Point at Minimum Volts setting and the maximum is 190°F (88°C). The default value is 180°F (82°C).

Once servicing has been completed, the service notification counter should be reset. This parameter can be reset by the installer by accessing the Reset Maintenance Reminder parameter. Once accessed, press the RESET key to reset the service notification counter.

Service Name and Phone Number

When programmed for BMS control through the 0 - 10V BMS input or through ModBus and the BMS Thermostat Input is set to INACTIVE, the On Volts parameter determines the 0 - 10V BMS input voltage at which the boiler is enabled. The minimum value is 0.5V and the maximum is 10.0V. The default value is 2.0V.

Please note that the brackets ([]) denote screen status. NOTICE

When a Maintenance Reminder timer or counter has expired, a Maintenance Reminder screen will appear on the display. By programming the installer’s name and phone number, this information will appear on the Maintenance Reminder Screen at that time. This can be programmed by accessing the Service Name and Phone Number parameter. When selected, another menu will appear with PHONE and NAME.

When programmed for BMS control through the 0 - 10V BMS input or through ModBus and the BMS Thermostat Input is set to INACTIVE, the Off Differential Volts parameter determines how far below the On Volts setting the 0 - 10V BMS input voltage must be in order to disable the boiler. The minimum value is 0.2V and the maximum is the On Volts setting. The default value is 1.0V.

1. Rotate the NAVIGATION dial to point to the name/phone number to program and press the NAVIGATION dial. The screen will now display the selected item (either PHONE or NAME).
2. Press the NAVIGATION dial again. A cursor will appear at the bottom of the screen. By rotating the NAVIGATION dial, various numbers and characters will appear. When the desired number/character is found, press the NAVIGATION dial. The cursor will move to the next position.

Service Notification in Months

When the boiler control determines that a scheduled service is due based on days of installation, the boiler display will alternate the standard boiler display text with the message SERVICE DUE every 5 seconds. This parameter is adjustable by the installer by accessing the Service Notification in Months parameter. The time range for this parameter is 0 months to 100 months. The default time is 12 months.

3. Repeat this procedure until the entire message is entered. If you make a mistake and wish to back up one character, rotate the NAVIGATION dial until the back arrow ( ) character is displayed and press the NAVIGATION dial.

This feature has been disabled by the manufacturer. To enable this feature change parameter K1 to the desired time range.

4. When finished, press the RIGHT SELECT [SAVE] key to return to the previous menu.

Service Notification Running Time

When the boiler control determines that a scheduled service is due based on the hours of actual operation, the boiler display will turn yellow and a new status screen will appear informing the installer that maintenance is required. This parameter is adjustable by the installer by accessing the Service Notification Running Time parameter. The time range for this parameter is 0 hours to 17,500 hours. The default time is 8,760 hours.

Show 5 more labels / short text on this page
Service Notification Cycles · Reset Maintenance Reminder · On Volts · Off Differential Volts · Service Notification
Page 28 of the Lochinvar 400 user manual — months
Page 28 · click to enlarge
Page 28

2 Maintenance

Maintenance and annual startup

Table 2-1 Service and Maintenance Schedules

Owner maintenance (see the Knight XL User’s Information Manual for

Service technician (see the following pages for instructions)

General:

  • Address reported problems
  • Check boiler area
  • Inspect interior; clean and vacuum if necessary;

Daily

  • Check pressure/temperature gauge
  • Clean condensate trap and fill with fresh water
  • Check for leaks (water, gas, flue, condensate)
  • Verify flue and air lines in good condition and sealed tight
  • Check vent piping

ANNUAL START-UP

  • Check system water pressure/system piping/expansion tank
  • Check air piping

Monthly

  • Check air and vent termination screens
  • Check control settings
  • Check ignition and flame sense electrodes (sand off any deposits; clean and reposition)
  • Check relief valve
  • Check condensate drain system
  • Check wiring and connections
  • Check air vents
  • Perform start-up checkout and performance verification per Section 10 in the Knight XL Installation and Operation Manual.

Periodically • Test low water cutoff (if used)

  • Reset button (low water cutoff)
  • Flame inspection (stable, uniform)
  • Flame signal (at least 10 microamps at high fire)

Every 6 months

  • Check boiler piping (gas and water) for leaks
  • Clean the heat exchanger if flue temperature is more than 54°F (30°C) above return water temperature.
  • Operate relief valve

If combustion or performance indicate need:

  • Shut boiler down (unless boiler used for domestic hot water)

End of season

  • Clean heat exchanger
  • Remove and clean burner using compressed air only

months

  • Clean the blower wheel

instructions)

Page 29 of the Lochinvar 400 user manual —  WARNING
Page 29 · click to enlarge
Page 29

2 Maintenance (continued)

Follow the Service and maintenance procedures given throughout this manual and in component literature shipped with the boiler. Failure to perform the service and maintenance could result in damage to the boiler or system. Failure to follow the directions in this manual and component literature could result in severe personal injury, death, or substantial property damage.

WARNING

WARNING

The boiler should be inspected annually only by a qualified service technician. In addition, the maintenance and care of the boiler designated in Table 2-1 and explained on the following pages must be performed to assure maximum boiler efficiency and reliability. Failure to service and maintain the boiler and system could result in equipment failure.

Electrical shock hazard – Turn off power to the boiler before any service operation on the boiler except as noted otherwise in this instruction manual. Failure to turn off electrical power could result in electrical shock, causing severe personal injury or death.

WARNING

Address reported problems

Figure 2-1 Condensate Trap

1. Inspect any problems reported by the owner and correct before proceeding.
Lochinvar 400 —  WARNING diagram (page 29)
Fig. 24

Inspect boiler area

1. Verify that boiler area is free of any combustible materials, gasoline and other flammable vapors and liquids.
2. Verify that air intake area is free of any of the contaminants listed in Section 1 of the Knight XL Installation and Operation Manual. If any of these are present in the boiler intake air vicinity, they must be removed. If they cannot be removed, reinstall the air and vent lines per this manual and the Knight XL Installation and Operation Manual.

Inspect boiler interior

1. Remove the front access cover and inspect the interior of the boiler.

The condensate trap must be filled with water during all times of boiler operation to avoid flue gas emission from the condensate drain line. Failure to fill the trap could result in severe personal injury or death.

2. Vacuum any sediment from inside the boiler and components. Remove any obstructions.

Clean condensate trap

Check all piping for leaks

1. Inspect the condensate drain line, condensate PVC fittings, and condensate trap.

Eliminate all system or boiler leaks. Continual fresh makeup water will reduce boiler life. Minerals can build up in sections, reducing heat transfer, overheating heat exchanger, and causing heat exchanger failure. Leaking water may also cause severe property damage.

WARNING

2. Remove the PVC cap retaining screw from the PVC cap (FIG. 2-1).
3. Remove the 2 inch PVC cap with the switch located at the top of the trap (FIG. 2-1).
4. Remove any sediment in the trap.
1. Inspect all water and gas piping and verify to be leak free.
5. Fill with fresh water until the water begins to pour out of the drain.
2. Look for signs of leaking lines and correct any problems found.
6. Replace the cap. Press the cap onto the trap until the cap makes contact with the drain.
3. Check gas line using the procedure found in Section 7 - Gas Connections of the Knight XL Installation and Operation Manual.
7. Replace the retaining screw.
Page 30 of the Lochinvar 400 user manual — Check boiler relief valve
Page 30 · click to enlarge
Page 30

2 Maintenance

Flue vent system and air piping

Safety relief valves should be re-inspected AT LEAST ONCE EVERY THREE YEARS, by a licensed plumbing contractor or authorized inspection agency, to ensure that the product has not been affected by corrosive water conditions and to ensure that the valve and discharge line have not been altered or tampered with illegally. Certain naturally occurring conditions may corrode the valve or its components over time, rendering the valve inoperative. Such conditions are not detectable unless the valve and its components are physically removed and inspected. This inspection must only be conducted by a plumbing contractor or authorized inspection agency – not by the owner. Failure to re-inspect the boiler relief valve as directed could result in unsafe pressure buildup, which can result in severe personal injury, death, or substantial property damage.

WARNING

1. Visually inspect the entire flue gas venting system and air piping for blockage, deterioration or leakage. Repair any joints that show signs of leakage. Verify that air inlet pipe is connected and properly sealed.
2. Verify that boiler vent discharge and air intake are clean and free of obstructions.

WARNING

Failure to inspect for the above conditions and have them repaired can result in severe personal injury or death.

Check water system

1. Verify all system components are correctly installed and operational.
2. Check the cold fill pressure for the system. Verify it is correct (must be a minimum of 12 psi (82.7 kPa)).
3. Watch the system pressure as the boiler heats up (during testing) to ensure pressure does not rise too high. Excessive pressure rise indicates expansion tank sizing or performance problem.

WARNING

Following installation, the valve lever must be operated AT LEAST ONCE A YEAR to ensure that waterways are clear. Certain naturally occurring mineral deposits may adhere to the valve, rendering it inoperative. When manually operating the lever, water will discharge and precautions must be taken to avoid contact with hot water and to avoid water damage. Before operating lever, check to see that a discharge line is connected to this valve directing the flow of hot water from the valve to a proper place of disposal. Otherwise severe personal injury may result. If no water flows, valve is inoperative. Shut down the boiler until a new relief valve has been installed.

4. Inspect automatic air vents and air separators. Remove air vent caps and briefly press push valve to flush vent. Replace caps. Make sure vents do not leak. Replace any leaking vents.

Check expansion tank

1. Expansion tanks provide space for water to move in and out as the heating system water expands due to temperature increase or contracts as the water cools. Tanks may be open, closed or diaphragm or bladder type. See Section 6 - Hydronic Piping of the Knight XL Installation and Operation Manual for suggested best location of expansion tanks and air eliminators.
2. After following the above warning directions, if the relief valve weeps or will not seat properly, replace the relief valve. Ensure that the reason for relief valve weeping is the valve and not over-pressurization of the system due to expansion tank waterlogging or undersizing.

Check boiler relief valve

1. Inspect the relief valve and lift the lever to verify flow. Before operating any relief valve, ensure that it is piped with its discharge in a safe area to avoid severe scald potential. Read Section 6 - Hydronic Piping of the Knight XL Installation and Operation Manual before proceeding further.
Page 31 of the Lochinvar 400 user manual — Check burner flame
Page 31 · click to enlarge
Page 31

2 Maintenance (continued)

Inspect ignition and flame sense electrodes

Figure 2-2 Burner Assembly - Model 400

Lochinvar 400 — Inspect ignition and flame sense electrodes diagram (page 31)
Fig. 25 · Inspect ignition and flame sense electrodes
1. Remove the ignition and flame sense electrodes from the boiler heat exchanger access cover.
2. Remove any deposits accumulated on the ignition/flame sense electrode using sandpaper. If the electrodes cannot be cleaned satisfactorily, replace with new ones.
3. Replace ignition/flame sense electrode, making sure gasket is in good condition and correctly positioned.

Check ignition ground wiring

1. Inspect boiler ground wire from the heat exchanger access cover to ground terminal strip.
2. Verify all wiring is in good condition and securely attached.
3. Check ground continuity of wiring using continuity meter.

Figure 2-3 Burner Assembly - Model 501

Lochinvar 400 — Check ignition ground wiring diagram (page 31)
Fig. 26 · Check ignition ground wiring
4. Replace ground wires if ground continuity is not satisfactory.

Check all boiler wiring

1. Inspect all boiler wiring, making sure wires are in good condition and securely attached.

Check control settings

1. Set the SMART SYSTEM control module display to Parameter Mode and check all settings. See Section 1 of this manual. Adjust settings if necessary. See Section 1 of this manual for adjustment procedures.
2. Check settings of external limit controls (if any) and adjust if necessary.

Perform start-up and checks

Figure 2-4 Burner Assembly - Models 601 - 801

1. Start boiler and perform checks and tests specified in Section 10 - Start-up of the Knight XL Installation and Operation Manual.
Lochinvar 400 — Perform start-up and checks diagram (page 31)
Fig. 27 · Perform start-up and checks
2. Verify cold fill pressure is correct and that operating pressure does not go too high.

Check burner flame

1. Inspect flame through observation window.
2. If the flame is unsatisfactory at either high fire or low fire, turn off boiler and allow boiler to cool down. Remove the burner and clean it thoroughly using a vacuum cleaner or compressed air. Do not use compressed air to clean burner if performed inside a building.
3. Remove the burner, reference FIG.’s 2-2 thru 2-4.
4. When replacing the burner, ensure gasket is in good condition and positioned correctly (FIG.’s 2-2 thru 2-4).
Page 32 of the Lochinvar 400 user manual —  WARNING
Page 32 · click to enlarge
Page 32

2 Maintenance

Check flame signal

7. Brush the heat exchanger while dry using a nylon bristle brush. Caution: DO NOT use a metal brush. Re-vacuum the heat exchanger.
1. At high fire the flame signal shown on the display should be at least 10 microamps. 2. A lower flame signal may indicate a fouled or damaged flame sense electrode. If cleaning the flame sense electrode does not improve, ground wiring is in good condition, and ground continuity is satisfactory, replace the flame sense electrode. 3. See Section 3 - Troubleshooting in this manual for other procedures to deal with low flame signal.
8. Finish cleaning using a clean cloth dampened with warm

water. Rinse out debris with a low pressure water supply.

9. Allow the heat exchanger to thoroughly dry.
10. Remove the field supplied rear refractory cover from the back of the combustion chamber of the heat exchanger and reassemble.
11. Close isolation valves on piping to isolate boiler from system. Attach a hose to the boiler drain and flush boiler thoroughly with clean water by using purging valves to allow water to flow through the water make-up line to the boiler.

Review with owner

1. Review the Knight XL User’s Information Manual with the owner. 2. Emphasize the need to perform the maintenance schedule specified in the Knight XL User’s Information Manual (and in this manual as well). 3. Remind the owner of the need to call a licensed contractor should the boiler or system exhibit any unusual behavior. 4. Remind the owner to follow the proper shutdown procedure and to schedule an annual start-up at the beginning of the next heating season.
12. Perform start-up and check-out procedures in the Check Flame and Combustion - Section 10 - Startup of the Installation and Operation Manual.
13. Replace the access cover and restore boiler to operation.

Table 2-2 Heat Exchanger Cleaning Kits

Lochinvar 400 — Review with owner diagram (page 32)
Fig. 28 · Review with owner

Cleaning boiler heat exchanger

For recommended materials; including brush, appropriate extension(s), refractory cover, and detailed instructions see Table 2-2 - Heat Exchanger Cleaning Kits.

  • 1. Shut down boiler:
  • Follow the “To Turn Off Gas to Appliance” instructions for the boiler in Section 10 - Startup of the Installation and Operation Manual.
  • Do not drain the boiler unless it will be exposed to freezing temperatures. If using freeze prevention fluid in system, do not drain.

* Do NOT use a metal brush. Only use the kit provided brush or an equivalent replacement nylon brush.

2. Allow time for the boiler to cool to room temperature if it has been firing.
3. Remove the nuts securing the heat exchanger access cover to the heat exchanger and set aside.

Figure 2-5 Rope Gasket - Heat Exchanger Door

Lochinvar 400 — Cleaning boiler heat exchanger diagram (page 32)
Fig. 29 · Cleaning boiler heat exchanger
4. Remove the heat exchanger access cover, burner, and gas/air arm assembly.

WARNING

The boiler contains ceramic fiber materials. Use care when handling these materials per instructions on page 3 of this manual. Failure to comply could result in severe personal injury.

5. Remove the condensate hose from the heat exchanger end. Connect a field supplied 3/4” diameter hose to a drain pan. Using field supplied means, cover the refractory in the back of the combustion chamber of the heat exchanger.
6. Use a vacuum cleaner to remove any accumulation on the

boiler heating surfaces. Do not use any solvent.

Page 33 of the Lochinvar 400 user manual —  WARNING
Page 33 · click to enlarge
Page 33

3 Troubleshooting

Check control module fuses

Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Always disconnect power to the boiler before servicing. Failure to comply could result in severe personal injury, death, or substantial property damage.

WARNING

ALWAYS check control module fuses before replacing control module or any major components (blower, etc.). If one of these fuses is blown, it can prevent the control module or other components from operating.

NOTICE

1. Turn OFF the power to the boiler at the external line switch.

Never jumper (bypass) any device except for momentary testing as outlined in the Troubleshooting chart. Severe personal injury, death, or substantial property damage can result.

WARNING

2. Remove top access cover.
3. Remove the control module cover.
4. Inspect fuses F1, F2, and F3, see FIG 3-1 below.

Figure 3-1 Control Module Fuses

Before troubleshooting:

Lochinvar 400 — Before troubleshooting: diagram (page 33)
Fig. 30 · Before troubleshooting:
1. Have the following items:

a. Voltmeter that can check 120 VAC, 24 VAC, and 12 VDC. b. Continuity checker. c. Contact thermometer.

F3 - .80 AMP FUSE 24V DC POWER SUPPLY

2. Check for 120 VAC (minimum 102 VAC to maximum 132 VAC) to boiler.
3. Make sure thermostat is calling for heat and contacts (including appropriate zone controls) are closed. Check for 24 VAC between thermostat wire nuts and ground.
5. The boiler is shipped with three (3) spare fuses in a plastic bag attached to the control module cover.
4. Make sure all external limit controls are installed and operating.
6. If necessary, replace open fuse (F3 is .80 amps, F2 is 3.15 amps and F1 is 5 amps).

Check the following:

1. Wire connectors to control module are securely plugged in at the module and originating control.

Do not jumper fuse or replace with any fuse except as specified. Failure to comply could result in severe personal injury, death, or substantial property damage.

WARNING

2. Gas pressures:
  • Maximum: 14 inches w.c. (3.5 kPa) (natural and LP) with no flow (lockup) or with boiler on
  • Minimum: 4 inches w.c. (1.0 kPa) (natural), 8 inches w.c. (2.0 kPa) (LP) with gas flowing (verify during boiler startup)
7. Install control module cover and top access cover after fuse inspection.
8. Restore power to the boiler at the external line switch and verify boiler operation (Section 10 - Start-up in the Knight XL Installation and Operation Manual) after completing boiler service.
Page 34 of the Lochinvar 400 user manual — FAULT CAUSE CORRECTIVE ACTION
Page 34 · click to enlarge
Page 34

3 Troubleshooting

Table 3-1 Troubleshooting Chart - No Display

FAULT CAUSE CORRECTIVE ACTION

  • Check external line switch, fuse, or breaker.

- No 120 vac supplied to unit.

  • Check position of ON/OFF switch. Turn switch to the ON position.
  • Check 120 vac through the ON/OFF switch.
  • Check wiring harness connection between display board and main control board. Connect harness at both points.

- No voltage through the switch. • Replace switch.

- Bad display board. • Replace board.

- Bad main control board. • Replace the main control board.

- Blown fuse. • Replace fuse F3 on the main control board, see page 33 of this manual.

- Main control board temperature set point satisfied. • Review temperature setting.

- Remote thermostat satisfied. • Review remote thermostat setting.

- Outside air temperature above Warm Weather Shutdown (WWSD) set point for main control board.

  • Check location of outside air sensor. Check resistance of outdoor air sensor and compare to Table 3-2B on page 35 of this manual.
  • Consult display for specific fault. Refer to fault descriptions on page 37 of this manual for corrective actions.

- Unit locked out on fault.

- Unit in Shutdown Mode. • Take unit out of Shutdown Mode.

  • Check ramp delay parameter settings. Optional PC software required.

- Ramp delay active.

  • Turn ramp delay feature off. See page 23 of this manual for instructions on how to turn this feature off.

Unit Does Not Modulate

- Boiler controlled by BMS. • Check BMS parameter settings. Optional PC software required.

  • Verify that the flue sensor is located in the flue outlet.
  • Check wiring connections at the flue sensor.

- Flue sensor open.

  • Check the resistance of the flue sensor and compare to Table 3-2D on page 35 of this manual.
Show 4 more labels / short text on this page
No Display · No Burner · Operation · Above 50%
Page 35 of the Lochinvar 400 user manual — Checking temperature sensors
Page 35 · click to enlarge
Page 35

3 Troubleshooting (continued)

Checking temperature sensors

The boiler temperature sensors (inlet water, outlet water, system water, flue, and outdoor air) are all resistance type devices. The following tables show the correct values for the sensors at various temperatures. Use an ohmmeter to read the resistance of the sensor at a known temperature. If the resistance of the sensor does not closely match its corresponding table, replace the sensor

It is important to note that the flue and outlet water sensors have two temperature sensing devices in one housing. These devices are designated as S1a/S1b, outlet sensor and S3a/S3b, flue sensor. Please reference the wiring diagram in the Knight XL Installation and Operation Manual for correct terminal location.

Table 3-2A - Inlet Water/System Sensor Resistance vs. Temperature

Table 3-2B - Outdoor Air Sensor Resistance vs. Temperature

Lochinvar 400 — Checking temperature sensors diagram (page 35)
Fig. 31 · Checking temperature sensors

-50 490,813 20 46,218 -40 336,606 30 34,558 -30 234,196 40 26,099 -20 165,180 50 19,900 10 118,018 60 15,311 0 85,362 70 11,883 10 62,465 80 9,299

Table 3-2C - Outlet Water Sensor Resistance vs. Temperature

Lochinvar 400 — Checking temperature sensors diagram (page 35)
Fig. 32 · Checking temperature sensors

50 19,553 158 2,004 50 40,030 158 3,478 68 12,690 176 1,464 68 25,030 176 2,492 86 8,406 194 1,084 86 16,090 194 1,816 104 5,715 212 816 104 10,610 212 1,344 122 3,958 122 7,166 140 2,786 140 4,943

Table 3-2D - Flue Sensor Resistance vs. Temperature

Lochinvar 400 — Checking temperature sensors diagram (page 35)
Fig. 33 · Checking temperature sensors

50 40,030 158 3,478 50 258,500 158 16,870 68 25,030 176 2,492 68 125,500 176 12,000 86 16,090 194 1,816 86 80,220 194 8,674 104 10,610 212 1,344 104 52,590 212 6,369 122 7,166 122 35,270 140 4,943 140 24,160

Page 36 of the Lochinvar 400 user manual — FAULT CAUSE CORRECTIVE ACTION
Page 36 · click to enlarge
Page 36

3 Troubleshooting

Table 3-3 Troubleshooting Chart - Noisy System

FAULT CAUSE CORRECTIVE ACTION

- Supply gas problem. Natural gas pressures should be between 4 inches w.c. and 14 inches w.c. LP gas pressures should be between 8 inches w.c. and 14 inches w.c.

  • Refer to Section 7 - Gas Connections of the Knight XL Installation and Operation Manual for detailed information concerning the gas supply.

- Gas/air mixture problem. • Refer to the Gas Valve Adjustment Procedure on page 47 of this manual for the proper gas valve setting. Verify that the vent/air intake lengths do not exceed the maximum listed in the General Venting section of the Knight XL Installation and Operation Manual.

- Dirty/damaged burner. • Refer to page 31 in this manual for the burner removal and inspection procedure. Clean or replace the burner as necessary.

- Low water flow through the heat exchanger. • Refer to Section 6 - Hydronic Piping of the

Knight XL Installation and Operation Manual for minimum flow rates. Verify that the boiler is piped in a primary/secondary fashion and that the boiler and system pump are running on a call for heat.

- Air in the piping system. • Properly purge all air from the piping system.

- Low system water pressure. • Verify system pressure is a minimum of 12 psi.

No Pump Operation - Boiler Pump System Pump

- Blown fuse. • Replace fuse F1 on the control board, see page 33 of this manual.

- Faulty pump. • Replace pump.

- Internal fault on control board. • Replace main control board.

- System pressure exceeds relief valve setting.

  • Lower the system pressure below the 30 psi rating of the supplied relief valve or replace the standard relief valve with a higher rated valve up to the maximum pressure of the heat exchanger.
  • Improperly sized expansion tank.
Show 4 more labels / short text on this page
Noisy Operation · or DHW Pump · Relief Valve · Opening
Page 37 of the Lochinvar 400 user manual — FAULT DESCRIPTION CORRECTIVE ACTION
Page 37 · click to enlarge
Page 37

3 Troubleshooting (continued)

Table 3-4 Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

FAULT DESCRIPTION CORRECTIVE ACTION

  • Reset the pressure switches.
  • Measure the supply gas pressure to determine cause of failure. Natural gas pressures should be between 4 - 14 inches w.c. and LP gas pressures should be between 8 - 14 inches w.c.

- Either the optional manual reset low gas pressure switch or the optional manual reset high gas pressure switch tripped.

  • Refer to Section 7 - Gas Connections of the Knight XL Installation and Operation Manual for detailed information concerning the gas supply.

(will require a manual reset once the condition has been corrected. Press

  • Correct the supply gas pressure if necessary.

the RESET button on the SMART SYSTEM display

  • Check for a loose or misplaced jumper if pressure switches are not installed.

to reset.)

  • Check for a loose or misplaced jumper on the Low Voltage Connection Board.

- The gas pressure switch contacts on the Low Voltage Connection Board are open.

  • Check for the addition of a device wired across the gas pressure switch terminals on the Low Voltage Connection Board.
  • Check boiler pump operation on a call for heat.
  • Check for closed valves or obstructions in the boiler piping.

LWCO (will require a manual reset once condition has

- Either the optional flow switch or the optional low water cutoff is not making.

  • Verify system is full of water and all air has been purged from the system.
  • Check for loose or misplaced jumpers if flow switch or LWCO is not installed.

been corrected. Press the RESET button on the SMART SYSTEM display

to reset.)

- Blown fuse. • Replace fuse F3 on the control board, see page 33 of this manual.

  • Check condensate tube from unit to floor drain for proper installation and obstructions.

(will require a manual reset once condition has

  • Inspect condensate trap for blockage. Clean if necessary.

The blocked drain switch has detected excessive condensate build up inside the unit.

been corrected. Press the RESET button on the SMART SYSTEM display

  • Check for loose wiring connection at wire harness plug.

to reset.)

  • Bad blocked drain switch. Replace switch.

Gas Pressure SW · Flow Switch/ · Blocked Drain SW

Page 38 of the Lochinvar 400 user manual — O-TEMP HEX SWITCH
Page 38 · click to enlarge
Page 38

3 Troubleshooting

Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

FAULT DESCRIPTION CORRECTIVE ACTION

APS:

  • Check the wiring connections to switch. Wires should be connected to the common and normally closed terminals.
  • Air intake lengths exceed the maximum allowed lengths. Refer to Section 3 - General Venting of the Knight XL Installation and Operation Manual for proper lengths.
  • Check for obstruction or blockage in the air intake pipes or at terminations.

APS / HEX

  • Check reference hoses connected to the air pressure switch for blockage or obstruction.

Open (will require a manual reset once the condition

  • Inspect the burner. Reference page 31 of this manual for removal and cleaning procedures. Replace if necessary.

Either the air pressure switch contacts are open, or the O-temp heat exchanger switch has opened.

has been corrected. Press the RESET button on the SMART SYSTEM

  • Inspect the heat exchanger. Reference page 32 of this manual for removal and cleaning procedures. Replace if necessary.

display to reset.)

  • Faulty air pressure switch. Replace switch.

O-TEMP HEX SWITCH

  • Inspect the back of the inner combustion chamber at burner level for refractory breakdown / missing. Replace heat exchanger if refractory is broken and unit has fired.
  • Check continuity across two contacts. Wires should be connected at both poles of the normally closed switch.
  • Faulty O-Temp HEX Switch. Replace switch.
  • The control board will release the call for heat after a set time period.

The main control board has received a call for heat too quickly after the previous call for heat has ended.

  • The control board will release the call for heat if the outlet temperature drops too quickly.
  • Inspect spark electrode and associated wiring for damage and connection. Reference page 31 of this manual for removal and cleaning procedures. Replace if necessary.

Flame Fail Ign (will require a manual reset once the condition

  • Check for proper electrical grounding of the unit.

has been corrected. Press the RESET button on the SMART SYSTEM

The unit has failed to prove main burner ignition after four (4) attempts.

  • Check incoming supply gas pressure. Natural gas pressures should be between 4 - 14 inches w.c. and LP gas pressures should be between 8 - 14 inches w.c. Refer to Section 7 - Gas Connections of the Knight XL Installation and Operation Manual for detailed information concerning the gas supply.

display to reset.)

Temp Sw · Anti-cycling

Page 39 of the Lochinvar 400 user manual — FAULT DESCRIPTION CORRECTIVE ACTION
Page 39 · click to enlarge
Page 39

3 Troubleshooting (continued)

Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

FAULT DESCRIPTION CORRECTIVE ACTION

The unit has failed to prove main burner ignition after four (4) attempts.

  • Verify that the plastic hose from the gas valve to the air inlet is connected and is not damaged.
  • Verify that the vent/air intake pipes are correctly installed and that there are no obstructions.
  • Check for 24 vac to the gas valve at the 2-pin connection on the side of the main control board during the ignition attempt. If no voltage is present, replace the main control board.
  • If 24 vac is present at the main control board, check the wiring between the main control board and the gas valve. Replace the wiring if necessary. Do not disconnect the wiring from the gas valve and attempt to measure voltage at that point. The main control board can detect if the gas valve is not connected and will display the Gas Valve or Gas Valve Fail fault.

(cont’d) (will require a manual reset once the condition

  • If 24 vac is present, check the outlet of the valve to ensure the valve is flowing gas. With a manometer connected to the outlet tap of the gas valve, when the unit is in the prepurge period, there should be a negative pressure present. When the valve is energized a change in pressure should occur. If the pressure change does not occur, the gas valve is not opening. Replace the gas valve.

has been corrected. Press the RESET button on the SMART SYSTEM

display to reset.)

  • Inspect flame sensor and associated wiring. Reference page 31 of this manual for removal and cleaning procedures. Replace if necessary.
  • Inspect and clean the heat exchanger as necessary. Reference page 32 of this manual for cleaning procedures.
  • Inspect the burner. Reference page 31 of this manual for removal and cleaning procedures. Replace if necessary.
  • Replace the main control board.
  • Check supply voltage for proper polarity.

(will require a manual reset once the condition

  • Check external wiring for voltage feedback.

The flame detector circuit is seeing a flame signal while no flame is present.

has been corrected. Press the RESET button on the SMART SYSTEM

  • Check the flame rod and make sure it is clean.
  • Check the internal wiring for bad connections.
  • Replace main control board.

display to reset.)

Flame Fail Ign · Flame Sequence

Page 40 of the Lochinvar 400 user manual — FAULT DESCRIPTION CORRECTIVE ACTION
Page 40 · click to enlarge
Page 40

3 Troubleshooting

Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

FAULT DESCRIPTION CORRECTIVE ACTION

  • Adjust the set point of the auto reset limit to a higher setting up to a maximum of 200°F. Reference the Knight XL Installation and Operation Manual for adjusting procedures.
  • Verify that the system is full of water and that all air has been properly purged from the system.
  • Verify that the boiler is piped properly into the heating system. Refer to Section 6 - Hydronic Piping of the Knight XL Installation and Operation Manual for the proper piping methods for the Knight XL boiler.
  • Check 120 vac to boiler pump motor on a call for heat. If voltage is not present, check wiring back to the main control board.

The outlet water temperature has exceeded the setting of the automatic reset high limit.

  • Replace the main control board if necessary.
  • If 120 vac is present on a call for heat and the boiler pump is not operating, replace the pump.
  • If the system pump is a variable speed pump, ensure that the system flow is not less than the boiler flow.
  • If operating on something other than an outlet sensor, check temperature setting of the main control board.
  • If the optional manual reset high limit has tripped, check setting of the device.
  • Check resistance of water sensors and compare to Table 3-2A on page 35 of this manual. Replace sensor if necessary.
  • Replace high limit.
  • Adjust the set point of the manual reset limit to a higher setting up to a maximum of 210°F. Reference the Knight XL Installation and Operation Manual for adjusting procedures.

Outlet MRHL (will require a manual reset once the condition

  • Verify that the system is full of water and that all air has been properly purged from the system.

has been corrected.

The outlet water temperature has exceeded the setting of the manual reset high limit.

  • Verify that the boiler is piped properly into the heating system. Refer to Section 6 - Hydronic Piping of the Knight XL Installation and Operation Manual for the proper piping methods for the Knight XL boiler.

Press the RESET button on the SMART

reset.)

  • Check 120 vac to boiler pump motor on a call for heat. If voltage is not present, check wiring back to the main control board.

Outlet ARHL · SYSTEM display to

Page 41 of the Lochinvar 400 user manual — FAULT DESCRIPTION CORRECTIVE ACTION
Page 41 · click to enlarge
Page 41

3 Troubleshooting (continued)

Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

FAULT DESCRIPTION CORRECTIVE ACTION

  • Replace the main control board if necessary.
  • If 120 vac is present on a call for heat and the boiler pump is not operating, replace the pump.
  • If the system pump is a variable speed pump, ensure that the system flow is not less than the boiler flow.

(cont’d) (will require a manual reset once the condition has been corrected. Press

  • If operating on something other than an outlet sensor, check temperature setting of the main control board.

The outlet water temperature has exceeded the setting of the manual reset high limit.

the RESET button on the SMART SYSTEM display

  • If the optional manual reset high limit has tripped, check setting of the device.

to reset.)

  • Check resistance of water sensors and compare to Table 3-2A on page 35 of this manual. Replace sensor if necessary.
  • Replace high limit.
  • Vent/air intake lengths exceed the maximum allowed lengths. Refer to Section 3 - General Venting of the Knight XL Installation and Operation Manual for proper lengths.

OR Fan Speed Low/

  • Check for obstruction or blockage in the vent/air intake pipes or at terminations.

The actual fan RPM is 30% lower than what is being called for.

High (will require a manual reset once the condition has been corrected. Press

  • Check the wiring connections at the fan and at the main control board.
  • Replace the fan.

the RESET button on the SMART SYSTEM display

  • Replace the main control board.

to reset.)

Blown fuse. • Replace fuse F2 on the control board, see page 33 of this manual.

  • Check wiring harness connection at the gas valve and at the main control board.

Fail (will require a manual reset once the condition has been corrected. Press

The main control board did not detect the gas valve.

  • Replace the gas valve wire harness.
  • Replace the gas valve.

the RESET button on the SMART SYSTEM display

  • Replace the main control board.

to reset.)

Sensor Open (will require a manual reset once the condition has been corrected. Press

  • Check the sensors and their associated wiring. Repair or replace the sensor or wiring if damaged.

Either the inlet water or outlet water temperature sensor has been disconnected.

  • Measure the resistance of the sensors and compare the resistance to the tables on page 35 of this manual.

the RESET button on the SMART SYSTEM display

to reset.)

  • Replace the sensor if necessary.

Outlet MRHL · Fan Low/High · GV/Relay

Page 42 of the Lochinvar 400 user manual — FAULT DESCRIPTION CORRECTIVE ACTION
Page 42 · click to enlarge
Page 42

3 Troubleshooting

Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

FAULT DESCRIPTION CORRECTIVE ACTION

  • Check the sensors and their associated wiring. Repair or replace the sensor or wiring if damaged.

Sensor Shorted (will require a manual reset once the condition has been

Either the inlet water or outlet water temperature sensor has been shorted.

  • Measure the resistance of the sensors and compare the resistance to the tables on page 35 of this manual.

corrected. Press the RESET

button on the SMART SYSTEM display to reset.)

  • Replace the sensor if necessary.

Sw (will require a manual reset once the condition has been

  • Check function of remote devices.

An optional remote proving switch is not making.

  • Check for loose or misplaced jumper if auxiliary proving switch is not installed.

corrected. Press the RESET

button on the SMART SYSTEM display to reset.)

  • Check wiring to sensor. Make sure wiring is connected and not damaged. Reconnect / repair wiring if necessary.

Fault (will require a manual reset once the condition has been

The control reads the inlet sensor as open or shorted.

  • Measure the resistance of the sensor and compare to the resistance in Table 3-2A on page 35 of this manual. Replace sensor if necessary.

corrected. Press the RESET

button on the SMART SYSTEM display to reset.)

  • Replace control module.
  • Check wiring to sensor. Make sure wiring is connected and not damaged. Reconnect / repair wiring if necessary.

Fault (will require a manual reset once the condition has been

The control reads the inlet sensor as open or shorted.

  • Measure the resistance of the sensor and compare to the resistance in Table 3-2C on page 35 of this manual. Replace sensor if necessary.

corrected. Press the RESET

button on the SMART SYSTEM display to reset.)

  • Replace control module.
  • Check wiring to sensor. Make sure wiring is connected and not damaged. Reconnect / repair wiring if necessary.

Outlet Temp Diff (will require a manual reset once the condition has been

  • Measure the resistance of the sensor and compare to the resistance in Table 3-2C on page 35 of this manual. Replace sensor if necessary.

The control module reads an excessive temperature difference between the two sensors.

corrected. Press the RESET

button on the SMART SYSTEM display to reset.)

  • Restore control parameter defaults from optional PC software.
  • Replace control module.

Louver Proving · Inlet Sensor · Outlet Sensor

Page 43 of the Lochinvar 400 user manual — FAULT DESCRIPTION CORRECTIVE ACTION
Page 43 · click to enlarge
Page 43

3 Troubleshooting (continued)

Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

FAULT DESCRIPTION CORRECTIVE ACTION

  • Check wiring to sensor. Make sure wiring is connected and not damaged. Reconnect / repair wiring if necessary.

Flue Sensor Fault (will require a manual reset once the condition has been

The control reads the flue sensor as open or shorted.

  • Measure the resistance of the sensor and compare to the resistance in Table 3-2D on page 35 of this manual. Replace the sensor if necessary.

corrected. Press the RESET

button on the SMART SYSTEM display to reset.)

  • Replace control module.
  • Check wiring to sensor. Make sure wiring is connected and not damaged. Reconnect / repair wiring if necessary.

Flue Temp Diff (will require a manual reset once the condition has been

  • Measure the resistance of the sensor and compare to the resistance in Table 3-2D on page 35 of this manual. Replace sensor if necessary.

The control module reads an excessive temperature difference between the two sensors.

corrected. Press the RESET

button on the SMART SYSTEM display to reset.)

  • Restore control parameter defaults from optional PC software.
  • Replace control module.
  • Inspect the heat exchanger. Reference page 32 of this manual for the procedure on how to clean the flue side of the heat exchanger.

Flue Temp Limit (will require a manual reset once the condition has been

  • Inspect the flue sensor and associated wiring. Measure the resistance of the flue sensor and compare to Table 3-2D on page 35 of this manual. Replace the sensor if necessary.

The stack temperature has exceeded the Flue Temp Limit set parameters.

corrected. Press the RESET

button on the SMART SYSTEM display to reset.)

  • Verify that the vent/air intake pipes are properly installed and that there are no obstructions.
  • Replace the main control board.
  • Restore the parameter defaults from the optional PC software.

Fatal Error The control module has detected parameter settings that are out of range.

  • Replace control module.

Memory Error A lockout occurs at the same time as a power outage. • Reset control module.

Page 44 of the Lochinvar 400 user manual — FAULT DESCRIPTION CORRECTIVE ACTION
Page 44 · click to enlarge
Page 44

3 Troubleshooting

Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

FAULT DESCRIPTION CORRECTIVE ACTION

  • Inspect the heat exchanger. Reference page 32 of this manual for the procedure on how to clean the flue side of the heat exchanger.
  • Inspect the flue sensor and associated wiring. Measure the resistance of the flue sensor and compare to Table 3-2D on page 35 of this manual. Replace the sensor if necessary.

The stack temperature has exceeded the set parameters for the boiler.

  • Verify that the vent/air intake pipes are properly installed and that there are no obstructions.
  • Replace the main control board.
  • Verify that the system is full of water and that all air has been properly purged from the system.
  • Verify that the boiler is piped properly into the heating system. Refer to Section 6 - Hydronic Piping of the Knight XL Installation and Operation Manual for the proper piping methods for the Knight XL boiler.
  • Check for 120 vac to the boiler pump motor on a call for heat. If voltage is not present, check the wiring back to the main control board. Replace the main control board if necessary.

Delta T High The temperature rise across the heat exchanger has exceeded the set parameters for the boiler.

  • If 120 vac is present on a call for heat and the boiler pump is not operating, replace the pump.
  • Verify that the boiler pump is set to the proper speed or that the pump is the proper size. Reference Section 6 - Hydronic Piping of the Knight XL Installation and Operation Manual for boiler pump specifications.
  • Verify that the system is full of water and that all air has been properly purged from the system.
  • Verify that the boiler is piped properly into the heating system. Refer to Section 6 - Hydronic Piping of the Knight XL Installation and Operation Manual for the proper piping methods for the Knight XL boiler.
  • Check for 120 vac to the boiler pump motor on a call for heat. If voltage is not present, check wiring back to the main control board. Replace the main control board if necessary.

Outlet water temperature has exceeded the maximum outlet water temperature.

  • If 120 vac is present on a call for heat and the boiler pump is not operating, replace the pump.
  • Verify that the boiler pump is set to the proper speed or that the boiler pump is the proper size. Reference Section 6 - Hydronic Piping of the Knight XL Installation and Operation Manual for boiler pump specifications.
  • Replace the main control board.

Flue Temp High · Outlet Temp · High

Page 45 of the Lochinvar 400 user manual — FAULT DESCRIPTION CORRECTIVE ACTION
Page 45 · click to enlarge
Page 45

3 Troubleshooting (continued)

Table 3-4 (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

FAULT DESCRIPTION CORRECTIVE ACTION

  • Check set point of the external control.
  • Check the wiring between the external control and the unit.

Rem Ctrl Flt External control is cycling too often.

  • Replace the control.

Progr (will require a manual reset once the condition has been corrected. Press

After downloading parameters from a laptop, the main control board must be reset.

  • Press the ENTER/RESET button on the SMART SYSTEM display panel.

the RESET button on the SMART SYSTEM display

to reset.)

  • Establish a heating load to remove the heat from the boiler loop.
  • Verify that the system is full of water and that all air has been properly purged from the system.
  • Verify that the boiler is piped properly into the heating system. Refer to Section 6 - Hydronic Piping of the Knight XL Installation and Operation Manual for the proper piping methods for the Knight XL boiler.

Service Blk While the unit is in Service Mode, the outlet temperature has exceeded 185°F.

  • Check 120 vac to the boiler pump motor on a call for heat. If voltage is not present, check the wiring back to the main control board. Replace the main control board if necessary.
  • If 120 vac is present on a call for heat and the boiler pump is not operating, replace the pump.
  • Verify that the boiler pump is set to the proper speed or that the boiler pump is the proper size. Reference Section 6 - Hydronic Piping of the Knight XL Installation and Operation Manual for boiler pump specifications.
  • Check 120 vac supply to the transformer.
  • Check wiring connections at the low voltage terminal strip.

Low 24 vac 120 vac input to the main control board has dropped below 80 vac.

  • Check the wire size/length to remote devices.
  • Replace the transformer.

Watch Dog Error The main control board has detected an internal fault. • Replace the main control board.

The main control board has detected an internal fault. • Replace the main control board.

CRC Parameters The main control board has detected an internal fault. • Replace the main control board.

No Error Stored The main control board has detected an internal fault. • Replace the main control board.

Parameters · Write EEProm

Page 46 of the Lochinvar 400 user manual — POSSIBLE CAUSE CORRECTIVE ACTION
Page 46 · click to enlarge
Page 46

3 Troubleshooting

Combustion Analysis Procedure

Table 3-5 Flue Products

1. Turn the main power off to the boiler by placing the “On/ Off” switch in the OFF position.

CO 2 O 2 CO 2 O 2

2. Remove the flue temperature sensor from the flue pipe connection. Note: Combustion measurements will be made at this point.

8.0% - 10% 3.0% - 6.5% 9.0% - 11% 4.1% - 6.9%

8. Once the combustion analysis is complete, test the safety shutoff device by turning the manual shutoff valve to the OFF position and ensuring that the boiler shuts down and registers an alarm. Open the manual shutoff valve, reset the control, and return to Service Mode.
3. Turn the main power on to the boiler by placing the “On/Off” switch in the ON position.
4. Place the boiler into the active position by pressing the RIGHT SELECT [ON] key (see page 7).
5. Locate the pinhole button below the RESET button on the display board (see page 7). Insert a thin wire (such as a paper clip) into the hole and press the button once and hold for 5 seconds to place the boiler into Service Mode. In Service Mode the boiler will fire at ignition speed and will then modulate up to full fire.
9. Turn the main power off to the boiler and replace the flue temperature sensor into the flue pipe connection.
10. Place the boiler back into normal operation.

You must replace the flue gas temperature sensor to prevent flue gas spillage into the room. Failure to comply could result in severe personal injury, death, or substantial property damage.

WARNING

6. Remove the flue temperature sensor. Insert the probe from a combustion analyzer into the hole left by the removal of the flue temperature sensor.
7. Once the boiler has modulated up to full fire, measure the combustion. The values should be in the range listed in Table 3-5 above. The CO levels should be less than 150 ppm for a properly installed unit.

If the combustion is not within the specified range, reference the chart below for possible causes and corrective actions.

Table 3-6 Troubleshooting Chart - Combustion Levels

POSSIBLE CAUSE CORRECTIVE ACTION

  • Refer to Section 3 - General Venting of the Knight XL Installation and Operation Manual for the proper venting and air intake methods for the Knight XL boiler.
  • Check for obstructions at the vent/air intake terminals.

Gas Supply Pressure • Refer to Section 7 - Gas Connections of the Knight XL Installation and Operation Manual for the proper gas supply for the Knight XL boiler.

Dirty/Damaged Burner • Refer to page 31 of this manual for burner removal and cleaning procedures.

  • Replace burner if necessary.

Gas Valve Adjustment • Refer to page 47 of this manual for the gas valve adjustment procedure.

Natural Gas Propane · Vent/Air Intake Length · or Obstruction

Page 47 of the Lochinvar 400 user manual — SCREW (REMOVE BLUE CAP)
Page 47 · click to enlarge
Page 47

3 Troubleshooting (continued)

Gas valve adjustment procedure

Figure 3-3 Gas Valve AdjustmentModel 501

If adjustment of the gas valve is deemed necessary, use the following procedures: (Note: The procedures below are model specific.)

Lochinvar 400 — Gas valve adjustment procedure diagram (page 47)
Fig. 34 · Gas valve adjustment procedure

Locate the throttle adjustment screw on the top of the gas valve, see FIG. 3-2. Using a screwdriver, turn the screw 1/8 turn counterclockwise to increase CO2 levels or 1/8 turn clockwise to decrease CO2 levels. After one adjustment on the valve, follow the Combustion Analysis Procedure on page 46 of this manual to measure the combustion.

If combustion is still not within the specified range, repeat the procedure. This procedure SHOULD NOT be performed more than four (4) times. If after four (4) adjustments and the combustion is still not within the specified range, revisit the possible causes in Table 3-6 on page 46 or replace the gas valve.

Models 601 - 801

Locate the throttle adjustment screw on top of the gas valve, see FIG. 3-4. Using an Allen wrench, turn the screw a 1/4 turn counterclockwise to increase CO2 levels or a 1/4 turn clockwise to decrease CO2 levels. After one adjustment on the valve, follow the Combustion Analysis Procedure on page 46 of this manual to measure the combustion.

Figure 3-2 Gas Valve AdjustmentModel 400

THROTTLE ADJUSTMENT

SCREW

If combustion is still not within the specified range, repeat the procedure. This procedure SHOULD NOT be performed more than four (4) times. If after four (4) adjustments and the combustion is still not within the specified range, revisit the possible causes in Table 3-6 on page 46 or replace the gas valve.

Lochinvar 400 — THROTTLE ADJUSTMENT diagram (page 47)
Fig. 35
Figure 3-4 Gas Valve AdjustmentModels 601 - 801
Lochinvar 400 — THROTTLE ADJUSTMENT diagram (page 47)
Fig. 36

THROTTLE ADJUSTMENT

Locate the throttle adjustment screw on top of the gas valve, see FIG. 3-3. Using a screwdriver, turn the screw a 1/4 turn counterclockwise to increase CO2 levels or a 1/4 turn clockwise to decrease CO2 levels. After one adjustment on the valve, follow the Combustion Analysis Procedure on page 46 of this manual to measure the combustion.

SCREW (REMOVE BLUE CAP)

If combustion is still not within the specified range, repeat the procedure. This procedure SHOULD NOT be performed more than four (4) times. If after four (4) adjustments and the combustion is still not within the specified range, revisit the possible causes in Table 3-6 on page 46 or replace the gas valve.

Model 400 · Model 501

Page 48 of the Lochinvar 400 user manual — Gas valve adjustment procedure
Page 48 · click to enlarge
Page 48
Lochinvar 400 — Gas valve adjustment procedure diagram (page 48)
Fig. 37 · Gas valve adjustment procedure

Revision Notes: Revision A (ECO #C05747) initial release. Reflects the new model numbers for the Knight XL upgrade.

Revision B (ECO #C06234) reflects changes made to the Service Notification parameter.

Revision C (ECO #C07981) reflects changes made to the parameter table, parameter descriptions, updates to the troubleshooting chart, and the addition of the O-temp HEX switch. .

Display codes

Error codes

What the fault codes shown on the display mean and how to clear them.

CodeMeaningFix
F3.80 AMP FUSE p.33
F15 AMP FUSE p.33
F23.15 AMP FUSE p.33
Fix-it

Troubleshooting

Common problems, likely causes, and what to do.

ProblemPossible causeRemedy
No Display- No 120 vac supplied to unit.• Check external line switch, fuse, or breaker. • Check position of ON/OFF switch. Turn switch to the ON position. • Check 120 vac through the ON/OFF switch. • Check wiring harness connection between display board and main control board. Connect harness at both points. p.34
No Display- No voltage through the switch.• Replace switch. p.34
No Display- Bad display board.• Replace board. p.34
No Display- Bad main control board.• Replace the main control board. p.34
No Display- Blown fuse.• Replace fuse F3 on the main control board, see page 33 of this manual. p.34
No Burner Operation- Main control board temperature set point satisfied.• Review temperature setting. p.34
No Burner Operation- Remote thermostat satisfied.• Review remote thermostat setting. p.34
No Burner Operation- Outside air temperature above Warm Weather Shutdown (WWSD) set point for main control board.• Check location of outside air sensor. Check resistance of outdoor air sensor and compare to Table 3-2B on page 35 of this manual. p.34
No Burner Operation- Unit locked out on fault.• Consult display for specific fault. Refer to fault descriptions on page 37 of this manual for corrective actions. p.34
No Burner Operation- Unit in Shutdown Mode.• Take unit out of Shutdown Mode. p.34
Unit Does Not Modulate Above 50%- Ramp delay active.• Check ramp delay parameter settings. Optional PC software required. p.34
Unit Does Not Modulate Above 50%• Turn ramp delay feature off. See page 23 of this manual for instructions on how to turn this feature off. p.34
Unit Does Not Modulate Above 50%- Boiler controlled by BMS.• Check BMS parameter settings. Optional PC software required. p.34
Unit Does Not Modulate Above 50%- Flue sensor open.• Verify that the flue sensor is located in the flue outlet. p.34
Unit Does Not Modulate Above 50%• Check wiring connections at the flue sensor. p.34
Unit Does Not Modulate Above 50%• Check the resistance of the flue sensor and compare to Table 3-2D on page 35 of this manual. p.34
Noisy Operation- Supply gas problem. Natural gas • pressures should be between 4 inches w.c. and 14 inches w.c. LP gas pressures should be between 8 inches w.c. and 14 inches w.c.Refer to Section 7 - Gas Connections of the Knight XL Installation and Operation Manual for detailed information concerning the gas supply. p.36
Noisy Operation- Gas/air mixture problem. •Refer to the Gas Valve Adjustment Procedure on page 47 of this manual for the proper gas valve setting. Verify that the vent/air intake lengths do not exceed the maximum listed in the General Venting section of the Knight XL Installation and Operation Manual. p.36
Noisy Operation- Dirty/damaged burner. •Refer to page 31 in this manual for the burner removal and inspection procedure. Clean or replace the burner as necessary. p.36
Noisy Operation- Low water flow through the heat exchanger. •Refer to Section 6 - Hydronic Piping of the Knight XL Installation and Operation Manual for minimum flow rates. Verify that the boiler is piped in a primary/secondary fashion and that the boiler and system pump are running on a call for heat. p.36
Noisy Operation- Air in the piping system. •Properly purge all air from the piping system. p.36
Noisy Operation- Low system water pressure. •Verify system pressure is a minimum of 12 psi. p.36
No Pump Operation - Boiler Pump System Pump or DHW Pump- Blown fuse. •Replace fuse F1 on the control board, see page 33 of this manual. Note: Make sure pump amperage does not exceed 1.8 amps. p.36
No Pump Operation - Boiler Pump System Pump or DHW Pump- Faulty pump. •Replace pump. p.36
No Pump Operation - Boiler Pump System Pump or DHW Pump- Internal fault on control board. •Replace main control board. p.36
Relief Valve Opening-System pressure exceeds relief valve • setting. •Lower the system pressure below the 30 psi rating of the supplied relief valve or replace the standard relief valve with a higher rated valve up to the maximum pressure of the heat exchanger. Improperly sized expansion tank. p.36
Gas Pressure SW (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.)• Reset the pressure switches. • Measure the supply gas pressure to determine cause of failure. Natural gas pressures should be between 4 - 14 inches w.c. and LP gas pressures should be between 8 - 14 inches w.c. • Refer to Section 7 - Gas Connections of the Knight XL Installation and Operation Manual for detailed information concerning the gas supply. • Correct the supply gas pressure if necessary. • Check for a loose or misplaced jumper if pressure switches are not installed. p.37
Gas Pressure SW (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.)• Check for a loose or misplaced jumper on the Low Voltage Connection Board. • Check for the addition of a device wired across the gas pressure switch terminals on the Low Voltage Connection Board. p.37
Flow Switch/ LWCO (will require a manual reset once condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.)• Check boiler pump operation on a call for heat. • Check for closed valves or obstructions in the boiler piping. • Verify system is full of water and all air has been purged from the system. • Check for loose or misplaced jumpers if flow switch or LWCO is not installed. p.37
Flow Switch/ LWCO (will require a manual reset once condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.)• Replace fuse F3 on the control board, see page 33 of this manual. p.37
Blocked Drain SW (will require a manual reset once condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.)• Check condensate tube from unit to floor drain for proper installation and obstructions. • Inspect condensate trap for blockage. Clean if necessary. • Check for loose wiring connection at wire harness plug. • Bad blocked drain switch. Replace switch. p.37
APS / HEX Temp Sw Open (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.)APS: Check the wiring connections to switch. Wires should be connected to the common and normally closed terminals. Air intake lengths exceed the maximum allowed lengths. Refer to Section 3 - General Venting of the Knight XL Installation and Operation Manual for proper lengths. Check for obstruction or blockage in the air intake pipes or at terminations. Check reference hoses connected to the air pressure switch for blockage or obstruction. Inspect the burner. Reference page 31 of this manual for removal and cleaning procedures. Replace if necessary. Inspect the heat exchanger. Reference page 32 of this manual for removal and cleaning procedures. Replace if necessary. Faulty air pressure switch. Replace switch. p.38
APS / HEX Temp Sw Open (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.)O-TEMP HEX SWITCH Inspect the back of the inner combustion chamber at burner level for refractory breakdown / missing. Replace heat exchanger if refractory is broken and unit has fired. Check continuity across two contacts. Wires should be connected at both poles of the normally closed switch. Faulty O-Temp HEX Switch. Replace switch. p.38
Anti-cyclingThe control board will release the call for heat after a set time period. The control board will release the call for heat if the outlet temperature drops too quickly. p.38
Flame Fail Ign (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.)Inspect spark electrode and associated wiring for damage and connection. Reference page 31 of this manual for removal and cleaning procedures. Replace if necessary. Check for proper electrical grounding of the unit. Check incoming supply gas pressure. Natural gas pressures should be between 4 - 14 inches w.c. and LP gas pressures should be between 8 - 14 inches w.c. Refer to Section 7 - Gas Connections of the Knight XL Installation and Operation Manual for detailed information concerning the gas supply. p.38
Flame Fail Ign (cont’d) (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.)Verify that the plastic hose from the gas valve to the air inlet is connected and is not damaged. Verify that the vent/air intake pipes are correctly installed and that there are no obstructions. Check for 24 vac to the gas valve at the 2-pin connection on the side of the main control board during the ignition attempt. If no voltage is present, replace the main control board. If 24 vac is present at the main control board, check the wiring between the main control board and the gas valve. Replace the wiring if necessary. Do not disconnect the wiring from the gas valve and attempt to measure voltage at that point. The main control board can detect if the gas valve is not connected and will display the Gas Valve or Gas Valve Fail fault. If 24 vac is present, check the outlet of the valve to ensure the valve is flowing gas. With a manometer connected to the outlet tap of the gas valve, when the unit is in the prepurge period, there should be a negative pressure present. When the valve is energized a change in pressure should occur. If the pressure change does not occur, the gas valve is not opening. Replace the gas valve. Inspect flame sensor and associated wiring. Reference page 31 of this manual for removal and cleaning procedures. Replace if necessary. Inspect and clean the heat exchanger as necessary. Reference page 32 of this manual for cleaning procedures. Inspect the burner. Reference page 31 of this manual for removal and cleaning procedures. Replace if necessary. Replace the main control board. p.39
Flame Sequence (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.)Check supply voltage for proper polarity. Check external wiring for voltage feedback. Check the flame rod and make sure it is clean. Check the internal wiring for bad connections. Replace main control board. p.39
Outlet ARHLAdjust the set point of the auto reset limit to a higher setting up to a maximum of 200°F. Reference the Knight XL Installation and Operation Manual for adjusting procedures. Verify that the system is full of water and that all air has been properly purged from the system. Verify that the boiler is piped properly into the heating system. Refer to Section 6 - Hydronic Piping of the Knight XL Installation and Operation Manual for the proper piping methods for the Knight XL boiler. Check 120 vac to boiler pump motor on a call for heat. If voltage is not present, check wiring back to the main control board. Replace the main control board if necessary. If 120 vac is present on a call for heat and the boiler pump is not operating, replace the pump. If the system pump is a variable speed pump, ensure that the system flow is not less than the boiler flow. If operating on something other than an outlet sensor, check temperature setting of the main control board. If the optional manual reset high limit has tripped, check setting of the device. Check resistance of water sensors and compare to Table 3-2A on page 35 of this manual. Replace sensor if necessary. Replace high limit. p.40
Outlet MRHL (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.)Adjust the set point of the manual reset limit to a higher setting up to a maximum of 210°F. Reference the Knight XL Installation and Operation Manual for adjusting procedures. Verify that the system is full of water and that all air has been properly purged from the system. Verify that the boiler is piped properly into the heating system. Refer to Section 6 - Hydronic Piping of the Knight XL Installation and Operation Manual for the proper piping methods for the Knight XL boiler. Check 120 vac to boiler pump motor on a call for heat. If voltage is not present, check wiring back to the main control board. p.40
Outlet MRHL (cont’d) (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.)• Replace the main control board if necessary. • If 120 vac is present on a call for heat and the boiler pump is not operating, replace the pump. • If the system pump is a variable speed pump, ensure that the system flow is not less than the boiler flow. • If operating on something other than an outlet sensor, check temperature setting of the main control board. • If the optional manual reset high limit has tripped, check setting of the device. • Check resistance of water sensors and compare to Table 3-2A on page 35 of this manual. Replace sensor if necessary. • Replace high limit. p.41
Fan Low/High OR Fan Speed Low/ High (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.)• Vent/air intake lengths exceed the maximum allowed lengths. Refer to Section 3 - General Venting of the Knight XL Installation and Operation Manual for proper lengths. • Check for obstruction or blockage in the vent/air intake pipes or at terminations. • Check the wiring connections at the fan and at the main control board. • Replace the fan. • Replace the main control board. p.41
Fan Low/High OR Fan Speed Low/ High (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.)• Replace fuse F2 on the control board, see page 33 of this manual. p.41
GV/Relay Fail (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.)• Check wiring harness connection at the gas valve and at the main control board. • Replace the gas valve wire harness. • Replace the gas valve. • Replace the main control board. p.41
Sensor Open (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.)• Check the sensors and their associated wiring. Repair or replace the sensor or wiring if damaged. • Measure the resistance of the sensors and compare the resistance to the tables on page 35 of this manual. • Replace the sensor if necessary. p.41
Sensor Shorted (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.)• Check the sensors and their associated wiring. Repair or replace the sensor or wiring if damaged. • Measure the resistance of the sensors and compare the resistance to the tables on page 35 of this manual. • Replace the sensor if necessary. p.42
Louver Proving Sw (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.)• Check function of remote devices. • Check for loose or misplaced jumper if auxiliary proving switch is not installed. p.42
Inlet Sensor Fault (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.)• Check wiring to sensor. Make sure wiring is connected and not damaged. Reconnect / repair wiring if necessary. • Measure the resistance of the sensor and compare to the resistance in Table 3-2A on page 35 of this manual. Replace sensor if necessary. • Replace control module. p.42
Outlet Sensor Fault (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.)• Check wiring to sensor. Make sure wiring is connected and not damaged. Reconnect / repair wiring if necessary. • Measure the resistance of the sensor and compare to the resistance in Table 3-2C on page 35 of this manual. Replace sensor if necessary. • Replace control module. p.42
Outlet Temp Diff (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.)• Check wiring to sensor. Make sure wiring is connected and not damaged. Reconnect / repair wiring if necessary. • Measure the resistance of the sensor and compare to the resistance in Table 3-2C on page 35 of this manual. Replace sensor if necessary. • Restore control parameter defaults from optional PC software. • Replace control module. p.42
Flue Sensor Fault (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.)• Check wiring to sensor. Make sure wiring is connected and not damaged. Reconnect / repair wiring if necessary. • Measure the resistance of the sensor and compare to the resistance in Table 3-2D on page 35 of this manual. Replace the sensor if necessary. • Replace control module. p.43
Flue Temp Diff (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.)• Check wiring to sensor. Make sure wiring is connected and not damaged. Reconnect / repair wiring if necessary. • Measure the resistance of the sensor and compare to the resistance in Table 3-2D on page 35 of this manual. Replace sensor if necessary. • Restore control parameter defaults from optional PC software. • Replace control module. p.43
Flue Temp Limit (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.)• Inspect the heat exchanger. Reference page 32 of this manual for the procedure on how to clean the flue side of the heat exchanger. • Inspect the flue sensor and associated wiring. Measure the resistance of the flue sensor and compare to Table 3-2D on page 35 of this manual. Replace the sensor if necessary. • Verify that the vent/air intake pipes are properly installed and that there are no obstructions. • Replace the main control board. p.43
Fatal Error• Restore the parameter defaults from the optional PC software. • Replace control module. p.43
Memory Error• Reset control module. p.43
Flue Temp High• Inspect the heat exchanger. Reference page 32 of this manual for the procedure on how to clean the flue side of the heat exchanger. • Inspect the flue sensor and associated wiring. Measure the resistance of the flue sensor and compare to Table 3-2D on page 35 of this manual. Replace the sensor if necessary. • Verify that the vent/air intake pipes are properly installed and that there are no obstructions. • Replace the main control board. p.44
Delta T High• Verify that the system is full of water and that all air has been properly purged from the system. • Verify that the boiler is piped properly into the heating system. Refer to Section 6 - Hydronic Piping of the Knight XL Installation and Operation Manual for the proper piping methods for the Knight XL boiler. • Check for 120 vac to the boiler pump motor on a call for heat. If voltage is not present, check the wiring back to the main control board. Replace the main control board if necessary. • If 120 vac is present on a call for heat and the boiler pump is not operating, replace the pump. • Verify that the boiler pump is set to the proper speed or that the pump is the proper size. Reference Section 6 - Hydronic Piping of the Knight XL Installation and Operation Manual for boiler pump specifications. p.44
Outlet Temp High• Verify that the system is full of water and that all air has been properly purged from the system. • Verify that the boiler is piped properly into the heating system. Refer to Section 6 - Hydronic Piping of the Knight XL Installation and Operation Manual for the proper piping methods for the Knight XL boiler. • Check for 120 vac to the boiler pump motor on a call for heat. If voltage is not present, check wiring back to the main control board. Replace the main control board if necessary. • If 120 vac is present on a call for heat and the boiler pump is not operating, replace the pump. p.44
Outlet Temp High• Verify that the boiler pump is set to the proper speed or that the boiler pump is the proper size. Reference Section 6 - Hydronic Piping of the Knight XL Installation and Operation Manual for boiler pump specifications. • Replace the main control board. p.44
Rem Ctrl Flt• Check set point of the external control. • Check the wiring between the external control and the unit. • Replace the control. p.45
Parameters Progr (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART SYSTEM display to reset.)• Press the ENTER/RESET button on the SMART SYSTEM display panel. p.45
Service Blk• Establish a heating load to remove the heat from the boiler loop. • Verify that the system is full of water and that all air has been properly purged from the system. • Verify that the boiler is piped properly into the heating system. Refer to Section 6 - Hydronic Piping of the Knight XL Installation and Operation Manual for the proper piping methods for the Knight XL boiler. • Check 120 vac to the boiler pump motor on a call for heat. If voltage is not present, check the wiring back to the main control board. Replace the main control board if necessary. • If 120 vac is present on a call for heat and the boiler pump is not operating, replace the pump. • Verify that the boiler pump is set to the proper speed or that the boiler pump is the proper size. Reference Section 6 - Hydronic Piping of the Knight XL Installation and Operation Manual for boiler pump specifications. p.45
Low 24 vac• Check 120 vac supply to the transformer. • Check wiring connections at the low voltage terminal strip. • Check the wire size/length to remote devices. • Replace the transformer. p.45
Watch Dog Error• Replace the main control board. p.45
Write EEProm• Replace the main control board. p.45
CRC Parameters• Replace the main control board. p.45
No Error Stored• Replace the main control board. p.45

Ask about the Lochinvar 400

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Lochinvar 400

Be the first to ask — other owners or our team will answer.