This manual must only be used by a qualified heating installer / service technician. Read all instructions, including this manual and the Crest Installation and Operation Manual, before installing. Perform steps in the order given. Failure to comply could result in severe personal injury, death, or substantial property damage.
Save this manual for future reference.
FB-SER Rev B


Installer – Read all instructions, including this manual and the Crest Installation and Operation Manual, before installing. Perform steps in the order given.
When calling or writing about the boiler – Please have the boiler model and serial number from the boiler rating plate.
Consider piping and installation when determining boiler location (see the Crest Installation and Operation Manual).
User – This manual is for use only by a qualified heating installer/service technician. Refer to the Crest User’s Information Manual for your reference.
Any claims for damage or shortage in shipment must be filed immediately against the transportation company by the consignee.
Have this boiler serviced/inspected by a qualified service technician at least annually.
Failure to comply with the above could result in severe personal injury, death or substantial property damage.
The combustion chamber insulation in this appliance contains ceramic fiber material. Ceramic fibers can be converted to cristobalite in very high temperature applications. The International Agency for Research on Cancer (IARC) has concluded, “Crystalline silica in the form of quartz or cristobalite from occupational sources is carcinogenic to humans (Group 1).” Normal operating temperatures in this appliance are below the level to convert ceramic fibers to cristobalite. Abnormal operating conditions would have to be created to convert the ceramic fibers in this appliance to cristobalite.
The ceramic fiber material used in this appliance is an irritant; when handling or replacing the ceramic materials it is advisable that the installer follow these safety guidelines.
Avoid breathing dust and contact with skin and eyes. • Use NIOSH certified dust respirator (N95). This type of respirator is based on the OSHA requirements for cristobalite at the time this document was written. Other types of respirators may be needed depending on the job site conditions. Current NIOSH recommendations can be found on the NIOSH website at http://www.cdc.gov/niosh/homepage.html NIOSH approved respirators, manufacturers, and phone numbers are also listed on this website.
Apply enough water to the combustion chamber lining to prevent airborne dust.
Remove the combustion chamber lining from the appliance and place it in a plastic bag for disposal.
Wash potentially contaminated clothes separately from other clothing. Rinse clothes washer
thoroughly.
NIOSH stated First Aid.
Eye: Irrigate immediately. Breathing: Fresh air.


Near boiler piping • Typical system components
The Crest boiler display • Display panel readout, buttons and their functions
Control module inputs • Control module inputs and options
Control module outputs • Control module outputs and options
Control panel menu access • Accessing programming mode and locating menus (See separate guide covering the PC interface.)
Control panel parameter access • Accessing and changing parameters from the display panel
Quick start information -- parameter table • An index of available adjustments and readouts, where to access them and where to find detailed information.

This piping reference is included to specify the Boiler Piping specific to the Crest boiler. This piping scheme is important for proper operation of the SMART TOUCH control. See the Crest Installation and Operation Manual for more detailed piping diagrams.
Single Boiler - Recommended - Primary / Secondary Piping with a Hot Water Generator

Single Boiler - Alternate - Full Flow System Piping


The Home Screen displays status, modulation rate, outlet water temperature, inlet water temperature, flue temperature, system supply temperature, system return temperature, outdoor air temperature, and domestic hot water tank temperature.
The boiler can be started and stopped by pressing the ON/OFF button. The Boiler Status Screen and Main Menu Screen can be accessed by pressing the appropriate button.

When the ON/OFF switch is turned to the ON position, the first screen visible on the LCD display will be the Home Screen. This screen displays the current status of the Crest boiler. The following items can be viewed or interacted with on the Home Screen:
HWG Temperature - This is the temperature as measured by the tank sensor in the hot water storage tank (if connected).
Flue Temperature - Temperature measured by the flue sensor.
Time - The time is displayed in the lower left-hand corner of the display. Reference this manual for Night Setback parameters and more information regarding adjusting the date and time.
On/Off button - Pressing this button allows the boiler to be placed in either Manual Shutdown Mode or Standby Mode.
Boiler Status button - Pressing this button brings up the Boiler Status Screen. This screen shows the status of the various safeties, inputs, and outputs to the control module. Reference this manual for more information regarding this screen.
Status - This line shows the current operating status of the Crest boiler and the current set point.
Outlet Water Temperature - This is the boiler outlet temperature.
Main Menu button - Pressing this button brings up the Main Menu Screen. From this screen navigation to nine (9) other screens is possible.
Inlet Water Temperature - This is the boiler inlet temperature.
System Supply Temperature - This is the water temperature as measured by the system supply sensor located in the downstream piping (if connected).
Modulation button - Pressing this button brings up the Modulation Screen. This screen shows overall boiler modulation, individual fan speeds, and flame currents.
System Return Temperature - This is the water temperature measured by the system return sensor located in the upstream piping (if connected).
Modulation Percentage - Displays the current boiler firing rate.
Outside Air Temperature - This is the outdoor air temperature (if connected).
Home Screen





Figure 1-1 Home Screen
How the boiler operates

The Crest uses an advanced stainless steel heat exchanger and electronic control module that allows fully condensing operation. The blowers pull in air and push flue products out of the boiler through the heat exchanger and flue piping. The control module regulates blower speeds to control the boiler firing rate. The gas valves sense the amount of air flowing into the boiler and allow only the right amount of gas to flow.
How the control modules operate
The Crest boiler is equipped with a SMART TOUCH control module. The SMART TOUCH control module receives inputs from boiler sensors and external devices. The control module activates and controls the blowers and gas valves to regulate heat input and switches the boiler, Hot Water Generator (HWG), and system pumps on and off as needed. The user programs the control module to meet system needs by adjusting control parameters. These parameters set operating temperatures and boiler operating modes.
Figure 1-2 Main Menu Screen

Table 1A (page 12) shows control module normal sequences of operation for space heating and HWG operation. The combined operation sequence is for a typical application, programmed to provide HWG priority.
The USER can adjust various space heating and HWG operating variables:
- Navigate to the Initial Setup Screen (FIG. 1-5). - From the Home Screen (FIG. 1-1), press MAIN MENU, then press SETUP on the Main Menu Screen (FIG. 1-2). - Press ENTER on the Password Screen (FIG. 1-3) (do not enter any values) and then press INITIAL SETUP on the Setup Screen (FIG. 1-4).
Figure 1-3 Password Screen

The USER can set the date and time and adjust temperature set points, and outdoor reset points.
Under the ADVANCED SETUP menu, the USER can change the TEMPERATURE UNITS and the LCD BACKLIGHT TIMER.
Most parameters are available only to the INSTALLER, accessible only by entering the installer password (5309) in the Password Screen (see the User Section).

Saving parameters (reference the Parameter Table - Table 1B on pages 13 - 17 of this manual)
Figure 1-4 Setup Screen

To adjust and save parameters (reference FIG. 1-5):
To change a parameter, use the arrows next to the parameter list on the Menu Screen to highlight the desired parameter, then press SELECT. A short description of the parameter and its current setting are then displayed on the bottom half of the screen. To adjust the setting, use the buttons to the left and right of the current setting.
Press the SAVE button after adjusting a parameter value. Additional parameter settings can then be adjusted or other navigation buttons can be used to return to previous screens or the Home Screen (FIG. 1-1).
Figure 1-5 Initial Setup Screen


Table 1A Sequence of Operation

Table 1B This table lists SMART TOUCH control module parameters and where to access them

3 SH Setpoint 18 32 185 120 Yes Yes
4 HWG Tank Setpoint 18 32 185 120 Yes Yes
5 MRHL Setpoint 18 32 205 205 Yes Yes
6 ARHL Setpoint 18 32 200 200 Yes Yes
7 SH Setpoint at Low Outdoor Temp. 19 32 185 180 Yes Yes
8 SH Setpoint at High Outdoor Temp. 19 32 185 68 Yes Yes
9 Low Outdoor Temperature 19 -22 86 23 Yes Yes
10 High Outdoor Temperature 19 -22 86 86 Yes Yes
11 Boiler Pump Mode 24 N/A N/A N/A No Yes
12 System Pump Mode 24 N/A N/A N/A No Yes
1 SH Min User Setpoint 18 32 185 32 No Yes
2 SH Max User Setpoint 18 32 185 185 No Yes
3 SH Setpoint 18 32 185 125 Yes Yes
4 SH Offset 18 0 36 9.9 No Yes
5 SH Differential 18 0 72 19.8 No Yes
6 HWG Tank Setpoint 18 32 185 120 Yes Yes
7 HWG Tank Differential 18 0 10 6.3 No Yes
8 MRHL Setting 18 32 205 204.8 Yes Yes
9 ARHL Setting 18 32 200 199.4 Yes Yes
10 HWG Minimum User Setpoint 19 32 185 60 No Yes
11 HWG Maximum User Setpoint 19 32 185 185 No Yes
12 HWG Boiler Setpoint 19 32 185 180 No Yes
13 HWG Boiler Offset 19 0 36 9.9 No Yes
14 HWG Boiler Differential 19 0 72 185 No Yes
1 SH Setpoint at Low Outdoor Temp. 19 32 185 180 Yes Yes
2 SH Setpoint at High Outdoor Temp 19 32 185 68 Yes Yes
3 Low Outdoor Temperature 19 -22 86 23 Yes Yes
4 High Outdoor Temperature 19 -22 86 86 Yes Yes
5 Outdoor Air Shutdown 19 32 122 79.7 No Yes
6 OA Shutdown Differential 20 32 122 79.7 No Yes

Table 1B (continued from previous page) This table lists SMART TOUCH control module parameters and where to access them
Min Max Default User Installer
Parameter Name (as shown on the LCD screen)
Value Value Value Access Access
7 Boost Time 20 0 250 20 No Yes
8 Boost Temperature 20 0 25 0 No Yes
9 Shift OA Reset Curve 20 -27 27 0 No Yes
1 Ramp Delay Mode 20 N/A N/A N/A No Yes
2 Ramp Delay Time #1 20 1 40 2 No Yes
3 Ramp Delay Time #2 20 1 40 2 No Yes
4 Ramp Delay Time #3 20 1 40 2 No Yes
5 Ramp Delay Time #4 20 1 40 1 No Yes
6 Ramp Delay Time #5 20 1 40 1 No Yes
7 Ramp Delay Time #6 20 1 40 1 No Yes
8 Ramp Delay Limit #1 20 10 100 20 No Yes
9 Ramp Delay Limit #2 20 10 100 30 No Yes
10 Ramp Delay Limit #3 20 10 100 40 No Yes
11 Ramp Delay Limit #4 20 10 100 55 No Yes
12 Ramp Delay Limit #5 20 10 100 75 No Yes
13 Ramp Delay Limit #6 20 10 100 100 No Yes
1 BMS Active/Inactive 21 ACTIVE INACTIVE INACTIVE No Yes
2 BMS Mode 21 POWER SETPOINT POWER No Yes
3 BMS Volts at Min Rate 21 0 10 2 No Yes
4 BMS Volts at Max Rate 21 0 10 10 No Yes
5 BMS Rate at Min Volts 21 4 100 4 No Yes
6 BMS Rate at Max Volts 21 0 100 100 No Yes
7 BMS Volts at Min Setpoint 21 0 10 2 No Yes
8 BMS Volts at Max Setpoint 21 0 10 10 No Yes
9 BMS Setpoint at Min Volts 21 32 185 68.9 No Yes
10 BMS Setpoint at Max Volts 21 32 185 178.7 No Yes
11 BMS Volts to Enable 21 0 10 2 No Yes
12 Differential to Stop BMS Demand 21 0 10 0.5 No Yes
13 BMS Enable Mode 21 ENABLE VOLTAGE VOLTAGE No Yes
Menu Sub Item · See Page

Table 1B (continued from previous page) This table lists SMART TOUCH control module parameters and where to access them
Min Max Default User Installer
Parameter Name (as shown on the LCD screen)
Value Value Value Access Access
1 Temperature Units 21 °F °C °F Yes Yes
2 LCD Backlight Time 21 0 255 240 Yes Yes
3 Freeze Protection; Pump On 21 -22 45 44.6 No Yes
4 Freeze Protection; Burner On 22 -22 45 37.4 No Yes
5 Freeze Protection; Burner Diff 22 0 20 5 No Yes
6 HWG to SH Switching Time 22 0 240 30 No Yes
7 SH to HWG Switching Time 22 0 240 30 No Yes
8 Anti-Cycling Time 22 0 40 10 No Yes
9 Anti-Cycling Differential 22 0 40 1 No Yes
10 HWG Rate Limiting 22 10 100 100 No Yes
11 Service Mode Timeout 22 0 40 40 No Yes
12 Controlling Sensor 22 0 4 2 No Yes
13 Inlet Control Time Delay 22 0 40 3 No Yes
1 SH Night Setback Offset Temp 22 0 90 0 No Yes
2 SH Night Setback Mon End 22 N/A N/A N/A No Yes
3 SH Night Setback Mon Begin 22 N/A N/A N/A No Yes
4 SH Night Setback Tue End 22 N/A N/A N/A No Yes
5 SH Night Setback Tue Begin 22 N/A N/A N/A No Yes
6 SH Night Setback Wed End 22 N/A N/A N/A No Yes
7 SH Night Setback Wed Begin 22 N/A N/A N/A No Yes
8 SH Night Setback Thur End 22 N/A N/A N/A No Yes
9 SH Night Setback Thur Begin 22 N/A N/A N/A No Yes
10 SH Night Setback Fri End 22 N/A N/A N/A No Yes
11 SH Night Setback Fri Begiin 22 N/A N/A N/A No Yes
12 SH Night Setback Sat End 22 N/A N/A N/A No Yes
13 SH Night Setback Sat Begin 22 N/A N/A N/A No Yes
14 SH Night Setback Sun End 22 N/A N/A N/A No Yes
15 SH Night Setback Sun Begin 22 N/A N/A N/A No Yes
Menu Sub Item · See Page

Table 1B (continued from previous page) This table lists SMART TOUCH control module parameters and where to access them
Min Max Default User Installer
Parameter Name (as shown on the LCD screen)
Value Value Value Access Access
1 HWG Night Setback Offset Temp 22 0 90 0 No Yes
2 HWG Night Setback Mon End 22 N/A N/A N/A No Yes
3 HWG Night Setback Mon Begin 22 N/A N/A N/A No Yes
4 HWG Night Setback Tue End 22 N/A N/A N/A No Yes
5 HWG Night Setback Tue Begin 22 N/A N/A N/A No Yes
6 HWG Night Setback Wed End 22 N/A N/A N/A No Yes
7 HWG Night Setback Wed Begin 22 N/A N/A N/A No Yes
8 HWG Night Setback Thur End 22 N/A N/A N/A No Yes
9 HWG Night Setback Thur Begin 22 N/A N/A N/A No Yes
10 HWG Night Setback Fri End 22 N/A N/A N/A No Yes
11 HWG Night Setback Fri Begin 22 N/A N/A N/A No Yes
12 HWG Night Setback Sat End 22 N/A N/A N/A No Yes
13 HWG Night Setback Sat Begin 22 N/A N/A N/A No Yes
14 HWG Night Setback Sun End 22 N/A N/A N/A No Yes
15 HWG Night Setback Sun Begin 22 N/A N/A N/A No Yes
1 ModBus Active / Inactive 23 ACTIVE INACTIVE INACTIVE No Yes
2 ModBus Out of Order Timer 23 5 120 30 No Yes
1 Cascade Active / Inactive 23 ACTIVE INACTIVE INACTIVE No Yes
2 Cascade Address 23 0 7 1 No Yes
3 Cascade Offset 23 0 40 10 No Yes
4 Cascade Differential 23 0 72 20 No Yes
5 Max Boiler Setpoint for Cascade 23 32 185 185 No Yes
6 Cascade Type 23 N/A N/A N/A No Yes
7 Block Time Switching Boiler On / Off 23 0 255 60 No Yes
8 Minimum Next On Time 24 0 255 60 No Yes
9 Rate % to Switch On Next Boiler 24 1 100 80 No Yes
10 Rate % to Switch Off Last Boiler 24 1 100 10 No Yes
11 Number of Boiler Pumps Always On 24 0 8 0 No Yes
Menu Sub Item · See Page

Table 1B (continued from previous page) This table lists SMART TOUCH control module parameters and where to access them

1 Boiler Pump Delay 24 0.5 2400 30 No Yes
2 Boiler Pump Anti-Seize Time 24 0 40 0.33 No Yes
3 Boiler Pump Mode 24 N/A N/A N/A No Yes
4 System Pump Mode 24 N/A N/A N/A No Yes
5 System Pump Delay 24 0.5 2400 30 No Yes
6 System Pump Anti-Seize Time 24 0 40 0.33 No Yes
7 HWG Pump Delay 24 0.5 2400 30 No Yes
8 HWG Pump Anti-Seize Time 24 0 40 0.33 No Yes
9 Delta T Setpoint 24 0 60 0 No Yes
1 Maintenance Notice - Months 25 0 36 12 No Yes
2 Maintenance Notice - Running Hours 25 0 100,000 10,000 No Yes
3 Maintenance Notice - Cycles 25 0 100,000 10,000 No Yes
4 Service Contact Number 25 N/A N/A N/A No Yes
5 Service Contact Name 25 N/A N/A N/A No Yes

The SH offset sets how many degrees above set point the temperature can go before the boiler will shut off. This parameter can only be changed by the installer by accessing parameter B4.
A: Initial Setup
The control uses an internal clock for the night setback feature and for logging of events. For these features to work correctly, the clock must be set when the boiler is first installed or anytime the boiler has been powered off for more than four (4) hours. This parameter must be accessed to set the clock. Parameter A2 sets the date.
The SH differential sets how many degrees below the offset the temperature has to drop before the boiler turns back on. This parameter can only be changed by the installer by accessing parameter B5.
HWG Tank Set Point
By installing a tank sensor, the SMART TOUCH control can perform the tank thermostat function. The SMART TOUCH control automatically detects the presence of this sensor, and generates a call for heat when the tank temperature drops below the tank set point minus the differential (parameter B7), and finishes the call for heat when the tank temperature reaches tank set point. This parameter can be changed by the installer by accessing parameter B6.
Parameters A3 - A12 shown in the Initial Setup Menu are grouped here for convenience. For a detailed explanation of each parameter, reference the specific menu for each parameter.
B: Set Points
Space Heating (SH) Minimum Set Point
The SH minimum set point sets the minimum water temperature set point that can be used for space heating operation. The user or installer will not be able to program the control with a lower SH set point. This parameter can only be changed by the installer by accessing parameter B1.
When a tank sensor is installed, the tank temperature must drop this amount below the tank set point (parameter B6) before the boiler will turn on. The installer can adjust this setting by accessing the parameter B7.
Manual Reset High Limit
Space Heating (SH) Maximum Set Point
The SMART TOUCH control contains an integral Manual Reset High Limit (MRHL) on the outlet of the heat exchanger. Once the outlet temperature exceeds the MRHL set point, the boiler will shut down and lock out. Once the outlet temperature has dropped below this set point, the RESET button on the LCD display must be pressed to clear this lockout. This set point can be adjusted by accessing parameter B8.
The SH maximum set point sets the maximum water temperature set point that can be used for space heating. The user or installer will not be able to program the control with a higher SH set point. This parameter can only be changed by the installer by accessing parameter B2.
Space Heating (SH) Set Point
Auto Reset High Limit
The SH set point sets the water temperature set point used during space heating calls. This parameter can be changed by the installer by accessing parameter B3.
The SMART TOUCH control contains an integral Auto Reset High Limit (ARHL) on the outlet of the heat exchanger. Once the outlet temperature exceeds the ARHL set point, the boiler will shut down and lock out. Once the outlet temperature has dropped below this set point, the RESET button on the LCD display can be pressed to reset this lockout. If RESET is not pressed, the control will automatically reset the lockout after five (5) minutes. This set point can be adjusted by accessing parameter B9.

C: Outdoor Reset
HWG Minimum User Set Point
SH Set Point at Low Outdoor Temperature
This setting controls the minimum user set point for the tank temperature. The installer can adjust this by accessing parameter B10.
When the outdoor air temperature drops to or below the Low Outdoor Temperature setting (parameter C3), the water temperature will be at this setting (see FIG. 1-6). However, if the user set point is set lower, the water temperature will be limited by the user set point instead. This parameter can be changed by accessing parameter C1.
HWG Maximum User Set Point
This setting controls the maximum user set point for the tank temperature. The installer can adjust this by accessing parameter B11.
SH Set Point at High Outdoor Temperature
When the outdoor air temperature rises to or above the High Outdoor Temperature setting (parameter C4), the water temperature will be at this setting (see FIG. 1-6). This parameter can be changed by accessing parameter C2.
HWG Boiler Set Point
When a HWG call for heat becomes active, the control will use the HWG boiler set point to determine the firing rate of the boiler based on the boiler outlet water temperature.
This parameter can be changed by the installer by accessing parameter B12.
When the outdoor air temperature drops to its minimum (C3), the water temperature will be at parameter C1 (FIG. 1-6). As the outdoor temperature continues to drop, the water temperature set point will continue to rise. However, if the user set point is set lower, the water temperature will be limited by the user set point instead. This parameter can be changed by accessing parameter C3.
This parameter reflects the degrees above HWG boiler set point the outlet temperature can go before the boiler will shut off. This parameter can be changed by the installer by accessing parameter B13.
High Outdoor Temperature When the outdoor air temperature rises to or above this set point, the water temperature will be at parameter C2 (FIG. 1-6). This parameter can be changed by the installer by accessing parameter C4.
This parameter reflects the degrees below HWG boiler offset the outlet temperature has to go before the boiler turns on. This parameter can be changed by the installer by accessing parameter B14.
When the outdoor temperature rises above this point, the control will block all SH demands (HWG demands will still be active). This parameter can be changed by the installer by accessing parameter C5.
Figure 1-6 Outdoor Air Reset Curve


Outdoor Air Shutdown Differential
Shift OA Reset Curve
The outdoor air shutdown differential parameter is the number of degrees below parameter C5 the outdoor air temperature must go before the boiler will respond to a SH demand. This parameter can be changed by the installer by accessing parameter C6.
The shift reset curve parameter shifts the actual set point above or below the calculated set point by the number of degrees in this parameter. This parameter can be changed by the installer by accessing parameter C9.
D: Ramp Delay
Ramp Delay (Enable / Disable)
The boost time parameter sets the amount of time that must elapse with a SH demand before the water temperature calculated set point will be increased. This parameter can be changed by the installer by accessing parameter C7.
This parameter allows the installer to enable or disable the SH ramp delay by accessing parameter D1.
The SMART TOUCH control can be programmed to limit the firing rate for a fixed period of time at the start of a space heating demand. There are six (6) possible limits, each with their own time delay. The first limit applies as soon as the burner starts. Once its time delay expires, the second limit is applied and its timer begins. The control steps through these limits until the 6th (sixth) limit expires. Note, however, that the 6th limit will also limit the rate for the rest of that heat demand. The installer can adjust the firing limits and time delays by accessing parameters D2 through D13.
If a SH demand lasts longer than the programmed boost time delay setting (C7) and there have been no HWG demands, the control will increase the water temperature set point by the amount in this parameter. If the SH demand continues through another time period, the set point will be increased again. This will continue until either the SH demand ends, a maximum of 20 increases has occurred, or the maximum set point has been reached. Once the SH demand has been satisfied the set point will revert back to its calculated setting. The boost temperature can be changed by the installer by accessing parameter C8.
Figure 1-7 Ramp Delay Interval

Boost Time · SH Ramp Delay · Boost Temperature

BMS Set Point at Maximum Volts
When programmed for BMS control through the 0 - 10V BMS input or through ModBus and the BMS Type is programmed as SETPOINT, the set point represented by the Volts at Maximum parameter (E8) is set by parameter E10.
BMS (Active / Inactive)
The set point or modulation of the boiler may be controlled through the 0 - 10V BMS input or through ModBus. When parameter E1 set to INACTIVE, the 0 - 10V input will be ignored. When set to ACTIVE, the set point or modulation will be controlled by the voltage on the 0 - 10V input (in the case of 0 - 10V BMS control), or the 0 - 10V input value received through ModBus.
BMS Volts to Enable
When programmed for BMS control through the 0 - 10V BMS input or through ModBus and the BMS Enable Mode is set to INACTIVE, parameter E11 determines the 0 - 10V BMS input voltage at which the boiler is enabled.
BMS Mode (Power / Set Point)
When programmed for BMS control through the 0 - 10V BMS input or through ModBus, the 0 - 10V signal can be interpreted as either a modulation command or a set point. When parameter E2 is set to POWER, the 0 - 10V signal will control the modulation. When set to SETPOINT, the 0 - 10V signal will control the SH set point.
Differential to Stop BMS Demand
When programmed for BMS control through the 0 - 10V BMS input or through ModBus and the BMS Enable Mode is set to INACTIVE, parameter E12 determines how far below the On Volts setting E11 the 0 - 10V BMS input voltage must be in order to disable the boiler.
BMS Volts at Minimum (Rate or Set Point)
When programmed for BMS control through the 0 - 10V BMS input or through ModBus, parameters E3 or E7 should be set to the minimum voltage signal sent to the SMART TOUCH control.
When controlling the boiler through the 0 - 10V BMS input or through ModBus, the boiler can be enabled one of two ways. With parameter E13 set to ACTIVE, the boiler will be enabled by closing the Enable input. When parameter E13 is set to INACTIVE, the boiler will be enabled by the voltage level on the 0 - 10V input (in the case of 0 - 10V BMS control), or the 0 - 10V input value received through ModBus.
BMS Volts at Maximum (Rate or Set Point)
When programmed for BMS control through the 0 - 10V BMS input or through ModBus, parameter E4 or E8 should be set to the maximum voltage signal sent to the SMART TOUCH control.
F: Advanced Setup
Temperature units (°C / °F)
BMS Rate at Minimum Volts
The control can be configured to display temperature in either °C or °F. This parameter can be changed by the user or the installer by accessing parameter F1.
When programmed for BMS control through the 0 - 10V BMS input or through ModBus and the BMS Type is programmed as POWER, the modulation percentage represented by the Volts at Minimum parameter (E3) is set by parameter E5.
Display Timeout (LCD Backlight Time)
This is the time in which the display remains illuminated. This parameter can be changed by the user or the installer by accessing parameter F2.
BMS Rate at Maximum Volts
When programmed for BMS control through the 0 - 10V BMS input or through ModBus and the BMS Type is programmed as POWER, the modulation percentage represented by the Volts at Maximum parameter (E4) is set by parameter E6.
Freeze Protection Pump On
The SMART TOUCH control will turn on the boiler and system pump outputs whenever the inlet temperature drops below this setting. This is done to prevent the water in the heat exchanger from freezing. Certain low-temperature applications (such as snow melt) can operate at temperatures around freezing, so this setting needs to be lowered in these cases. The installer can adjust the temperature at which the pump outputs are turned on by accessing parameter F3.
BMS Set Point at Minimum Volts
When programmed for BMS control through the 0 - 10V BMS input or through ModBus and the BMS Type is programmed as SETPOINT, the set point represented by the Volts at Minimum parameter (E7) is set by parameter E9.
BMS Enable Mode

Freeze Protection Burner On
HWG Rate Liming (NOT AVAILABLE AT THIS TIME)
This parameter determines the maximum rate to be used when heating a HWG tank. This setting may be used when the tank is unable to accept all of the BTU’s available from the boiler. This parameter may be adjusted by the installer by accessing parameter F10.
If running the pumps does not prevent the inlet temperature from falling closer to freezing, the SMART TOUCH control will fire the burner at low fire if in the ON state. The installer can adjust the temperature at which the burner fires by adjusting parameter F4.
Freeze Protection Burner Differential
The Service Mode allows the installer to set the unit to any firing rate for the purpose of combustion analysis. The delay sets the length of time the boiler will stay in the Service Mode if no keys have been pressed before going back to its original state. This parameter can only be changed by the installer by accessing parameter F11.
Once the burner has started firing due to a low inlet temperature, the inlet temperature must increase by this amount before the burner turns back off. The installer can adjust this differential by accessing parameter F5.
When a boiler has a HWG demand and it receives a space heating demand, the SMART TOUCH control will start a timer. Once the timer expires, it will stop the HWG demand and service the space heating demand. The installer can adjust the length of time the boiler will service the HWG demand by accessing parameter F6.
The SH controlling sensor parameter selects the sensor the control will use to regulate the boiler firing rate. This parameter is adjustable by the installer by accessing parameter F12. The sensor selections are as follows: The outlet sensor regulates the firing rate based on the outlet water temperature of the boiler and the inlet sensor regulates the firing rate based on the inlet water temperature of the boiler. If the outlet sensor is selected, and the optional system supply sensor is connected, the control will regulate the firing rate based on the system supply sensor temperature.
When a boiler has a space heating demand and it receives a HWG demand, it will immediately switch to the HWG demand and start a timer. Once the timer has expired, the boiler will switch back to the space heating demand and start another timer. Once this timer expires, it will switch back to the HWG demand. The installer can adjust the length of time the boiler will service the space heating demand by accessing parameter F7.
Inlet Control Time Delay
When the inlet sensor is selected as the controlling sensor, the SMART TOUCH control will start by controlling the outlet/ system supply temperature to the SH set point. After a time delay, the control will start to increase and regulate the system supply temperature in order to maintain the inlet/system return temperature to the SH set point. This time delay should be long enough for the heated water to work its way through the system loop and be measured by the inlet/system return sensor. This time delay is adjustable by the installer by accessing parameter F13.
Once a SH demand has been satisfied, a set amount of time must elapse before the control will respond to a new SH demand. The control will block the new heat demand and anti-cycling will be shown in the display until the time has elapsed or the water temperature drops below parameter F9. This parameter can be changed by the installer by accessing parameter F8.
The installer may adjust the space heating night setback offset by accessing parameter G1 and the HWG night setback offset by accessing parameter H1.
The control will bypass the anti-cycling time if the inlet water temperature drops too much. The control will use the inlet water temperature at the time the boiler shut off as the starting point. If the inlet temperature drops below this temperature parameter the control will abort anti- cycling and allow the boiler to fire. This parameter can be changed by the installer by accessing parameter F9.
Once the internal clock has been set correctly, the SH night setback feature can be used to program a lower set point. The value of this parameter will be subtracted from the normal set point to determine the set point used during night setback. This parameter can be changed by the user or the installer by accessing parameters G2 through G15 and H2 through H15. The temperature range for this parameter is 0°F to 90°F (50°C). The feature is turned off with a setting of 0°F.

I: ModBus
ModBus (Active / Inactive)
This parameter determines how much the temperature must go below the turn off temperature (Set point + Offset) before the lead boiler turns on. This parameter can be adjusted by the installer by accessing parameter J4.
When BMS is set to ACTIVE (see BMS Active / Inactive) and the boiler is being controlled through ModBus, set parameter I1 to ACTIVE. Otherwise, set the ModBus parameter to INACTIVE. Note that the boiler can still be monitored by ModBus with this parameter set to INACTIVE.
Maximum Boiler Set Point for Cascade
This parameter determines the set point used by the individual boilers in a Cascade. When a boiler is commanded to fire by the Leader boiler, it will attempt to achieve this temperature at its outlet. If any of the boiler outlet temperatures reach the maximum cascade set point, the boiler will then modulate down on its own in order to keep its outlet temperature within the maximum cascade set point. Therefore, this parameter can be used to limit the outlet temperatures of all the boilers in a Cascade. Note that this parameter does not apply when the boiler is heating an indirect HWG tank. This parameter is adjustable by the installer by accessing parameter J5.
ModBus Out of Order Timer
When the boiler is being provided with certain commands and temperatures through ModBus, this information must be updated frequently. If it is not updated before this timer expires, the boiler will revert back to its own internal readings and control. This parameter is adjustable by the installer by accessing parameter I2.
J: Cascade
Cascade Type The Cascade divider method is Efficiency Optimization, designated as EFF in the menu. This method is used, as the name implies, when it is desired to have the most efficient system. When the first boiler reaches a certain rate (default = 80%), it lowers its rate to 40% and turns on the next boiler at 40%. The two (2) boilers then modulate at the same rate. As the calculated load increases further and both boilers ramp up to 80%, it lowers the rate of the first two (2) boilers to 53% and brings the next boiler on at 53%. The three (3) boilers then modulate together. As the calculated load decreases, the boilers will reach a lower threshold (default = 10%), at which time the last boiler (the third in our example) will turn off and the Cascade will increase the rates of the remaining boilers to provide the equivalent total output as before ((3 x 10%) / 2 = 15% in our example). This parameter can be adjusted by the installer by accessing parameter J6.
Cascade Active / Inactive
The boiler is part of a group of units sequenced together. The designated Leader unit determines the total output needed from the group based on the set point and controlling sensor reading. It assigns portions of the output to itself (Leader) and the Member units. When Cascade is active, each boiler in the group requires a unique address. This setting is adjustable by the installer by accessing parameter J1.
The boiler designated as the Leader needs to be programmed with address 0. All the Member boilers require addresses from 1 to 7, and the addresses must be different for each Member. The addresses can be in any order, regardless of the order in which the units are wired together. This parameter is adjustable by the installer by accessing parameter J2. The outdoor air (if used) and system supply sensor must be connected to the Leader boiler.
In order to prevent units in a Cascade from short cycling, this parameter defines the minimum ON and OFF time for each unit. The installer can adjust this time by accessing parameter J7.
This parameter determines how much the temperature can go above set point before the lead boiler will turn off. This parameter can be adjusted by the installer by accessing parameter J3.
Cascade Off-On Differential · Cascade Address

Minimum Next On Time
In order to reduce the risk of temperature overshoot with a Cascade, this parameter defines the minimum time delay from starting one unit until the next unit may be started. The installer can adjust this time delay by accessing parameter J8.
The SMART TOUCH control is able to control the system pump in 5 different ways. The options are as follows:
Rate % to Switch on Next Boiler
When the Cascade is programmed in the Efficiency Optimization Mode, the currently running boilers must ramp up to a certain firing rate before the next boiler in the Cascade will start. This percentage can be adjusted by accessing parameter J9.
For options 2 and 4, the speed of the system pump is controlled by a separate control system. The System Pump Mode can be adjusted by accessing parameter K4.
Rate % to Switch off Last Boiler
When the Cascade is programmed in the Efficiency Optimization Mode, the currently running boiler will stop. This percentage can be adjusted by accessing parameter J10.
The system pump delay parameter sets the length of time the system pump (if connected) will run after a SH demand has been satisfied. This parameter is adjustable by the installer by accessing parameter K5.
Number of Boiler Pumps Always On
When multiple Crest boilers are connected in a Cascade, the SMART TOUCH control can keep a minimum number of the boiler pumps running, regardless of how many of the boilers are firing. This is useful in full flow systems where the system flow is provided by the individual boiler pumps. This number can be adjusted by accessing parameter J11.
System Pump Anti-Seize Delay
If the boiler pump does not run for 24 hours, it will be turned on briefly to prevent it from seizing. The length of time it runs is determined by parameter K6.
K: Pumps
The HWG pump delay parameter sets the length of time the HWG pump (if connected) will run after a HWG demand has been satisfied. This parameter is adjustable by the installer by accessing parameter K7.
The SH pump delay parameter sets the length of time the boiler pump will run after a SH demand has been satisfied. This parameter is adjustable by the installer by accessing parameter K1.
HWG Pump Anti-Seize Delay
If the boiler pump does not run for 24 hours, it will be turned on briefly to prevent it from seizing. The length of time it runs is determined by parameter K8.
Boiler Pump Anti-Seize Time
If the boiler pump does not run for 24 hours, it will be turned on briefly to prevent it from seizing. The length of time it runs is determined by parameter K2.
ΔT Set Point
The SMART TOUCH control includes a 0 - 10Vdc output for controlling the speed of a variable speed boiler pump. The speed is regulated in order to, among other things, maintain a minimum delta T across the heat exchanger. This helps reduce the electrical consumption of the boiler pump when the boiler is firing at less than its maximum rate. (This feature is active only when a system supply sensor is installed). This set point can be adjusted by accessing parameter K9.
The SMART TOUCH control is able to control the boiler pump in 3 different ways. The options are as follows:
The Boiler Pump Mode can be adjusted by accessing parameter K3.

L: Service Notification
Service Notification in Months
When the boiler control determines that a scheduled service is due based on the months of installation, the boiler display will turn yellow and a new status screen will appear informing the installer that maintenance is required. This parameter is adjustable by the installer by accessing parameter L1.
Service Notification Running Hours
When the boiler control determines that a scheduled service is due based on the hours of actual operation, the boiler display will turn yellow and a new status screen will appear informing the installer that maintenance is required. This parameter is adjustable by the installer by accessing parameter L2.
When the boiler control determines that a scheduled service is due based on the number of boiler cycles, the boiler display will turn yellow and a new status screen will appear informing the installer that maintenance is required. This parameter is adjustable by the installer by accessing parameter L3.
Installer Name and Phone Number
When a Maintenance Reminder timer or counter has expired, a Maintenance Reminder screen will appear on the display. By programming the installer’s name and phone number, this information will appear on the Maintenance Reminder Screen at that time. This can be programmed by accessing parameters L4 and L5. When selected, another menu will appear with PHONE and NAME.
Service Notification Cycles

Figure 1-8 Cascade Screen

The Cascade Screen provides the status of the Cascade System. This screen is only accessible when the boiler is the Leader of an active Cascade. There are many items displayed on the Cascade Screen. Among them is the Boiler Power Level Indicators. For each boiler present in the Cascade a power level indicator will be present above its corresponding Cascade address. The level of the indicator will rise and fall indicating the approximate power level of the boiler. The display box above each power level will display the following:

Graph Screen
The Graph Screen consists of two (2) different screens. The First screen is the Parameter Selection Screen. By pressing the up and down arrow keys the desired parameter can be selected. When the SELECT button is pressed the parameter will appear in the bottom half of the fi rst screen. If a parameter is selected by mistake, it can be de-selected by highlighting the parameter and pressing the SELECT button. A maximum of fi ve (5) items can be graphed at one time.
Figure 1-9 Graph Screen_Parameter Selection

The Second screen is accessed by pressing the GRAPH button. Once the items to be graphed are selected, press the GRAPH button to view the graph. Each item graphed will have a different color line to represent it. The items selected will be shown below the graph along with their corresponding color. Press the BACK button to return to the Parameter Selection Screen.
Figure 1-10 Graph Screen


The History Screen shows the status of various counters and faults. Within the History Screen there are three separate screens. These screens are the “Lockout Faults”, “Blocking Faults” and “Runtime History”.
The default screen is the “Lockout Faults” screen. This screen allows you to view the last ten (10) lockout faults. Preceded by each fault is the date and time of when the fault occurred. The lockout faults can be reset by pressing the RESET FAULTS button.
Figure 1-11 History Screen_Lockout Faults

The next screen is the “Blocking Faults” Screen. This screen allows you the view the last ten (10) blocking faults. Preceded by each fault is the date and time of when the fault occurred. The blocking faults can be reset by pressing the RESET FAULTS button.
Figure 1-12 Graph Screen_Blocking Faults


History Screen
The third screen is the “Runtime History”. There are several pieces of information that are displayed on this screen. Items that can be viewed on this screen are as follows:
Figure 1-13 History Screen_Runtime History


Service Screen
The Service Screen allows the integrated control to override all other heat demands and operate Valve 1 and Valve 2 at high fi re and low fi re conditions. To place the boiler into Service Mode, press the START button. As specifi ed above the integrated control will override all other heat demands, however, all safeties will be active. If no buttons are pressed, the integrated control will automatically revert back to its original status after the “Remaining time in Servicer” counter expires.
Once the boiler has been placed into Service Mode it will light and modulate to low fi re. At any time after that point there are two (2) ways to adjust the fi ring rate. The fi rst way is by pressing one of the six (6) preset buttons. The second way is by manually adjusting the fi ring percentage using the “+” and “-“ buttons. When Service Mode is no longer needed press the STOP button to return to normal operation.
Figure 1-14 Service Screen


Maintenance and annual startup
Table 2A Service and Maintenance Schedules
Owner maintenance (see the Crest User’s Information Manual for
months
instructions)

Follow the service and maintenance procedures given throughout this manual and in component literature shipped with the boiler. Failure to perform the service and maintenance could result in damage to the boiler or system. Failure to follow the directions in this manual and component literature could result in severe personal injury, death, or substantial property damage.
WARNING
The boiler should be inspected annually only by a qualified service technician. In addition, the maintenance and care of the boiler designated in Table 2A and explained on the following pages must be performed to assure maximum boiler efficiency and reliability. Failure to service and maintain the boiler and system could result in equipment failure.
Electrical shock hazard – Turn off power to the boiler before any service operation on the boiler except as noted otherwise in this instruction manual. Failure to turn off electrical power could result in electrical shock, causing severe personal injury or death.
Address reported problems
Figure 2-1 Condensate Trap

FROM CONDENSATE DRAIN ON BOILER TO FLOOR DRAIN OR NEUTRALIZER KIT 1” PVC / CPVC CONNECTION
Eliminate all system or boiler leaks. Continual fresh makeup water will reduce boiler life. Minerals can build up, reducing heat transfer, overheating heat exchanger, and causing heat exchanger failure. Leaking water may also cause severe property damage.
Inspect boiler interior
Flush condensate trap with water

Safety relief valves should be re-inspected AT LEAST ONCE EVERY THREE YEARS, by a licensed plumbing contractor or authorized inspection agency, to ensure that the product has not been affected by corrosive water conditions and to ensure that the valve and discharge line have not been altered or tampered with illegally. Certain naturally occurring conditions may corrode the valve or its components over time, rendering the valve inoperative. Such conditions are not detectable unless the valve and its components are physically removed and inspected. This inspection must only be conducted by a plumbing contractor or authorized inspection agency – not by the owner. Failure to re-inspect the boiler relief valve as directed could result in unsafe pressure buildup, which can result in severe personal injury, death, or substantial property damage.
Failure to inspect for the above conditions and have them repaired can result in severe personal injury or death.
Following installation, the valve lever must be operated AT LEAST ONCE A YEAR to ensure that waterways are clear. Certain naturally occurring mineral deposits may adhere to the valve, rendering it inoperative. When manually operating the lever, water will discharge and precautions must be taken to avoid contact with hot water and to avoid water damage. Before operating lever, check to see that a discharge line is connected to this valve directing the flow of hot water from the valve to a proper place of disposal. Otherwise severe personal injury may result. If no water flows, valve is inoperative. Shut down the boiler until a new relief valve has been installed.

Figure 2-2 Burner Assembly


Review with owner 1. Review the Crest User’s Information Manual with the owner. 2. Emphasize the need to perform the maintenance schedule specified in the Crest User’s Information Manual (and in this manual as well). 3. Remind the owner of the need to call a licensed contractor should the boiler or system exhibit any unusual behavior. 4. Remind the owner to follow the proper shutdown procedure and to schedule an annual start-up at the beginning of the next heating season.
WARNING
The combustion chamber insulation in this appliance contains ceramic fiber material. Ceramic fibers can be converted to cristobalite in very high temperature applications. The International Agency for Research on Cancer (IARC) has concluded, “Crystalline silica in the form of quartz or cristobalite from occupational sources is carcinogenic to humans (Group 1).” Normal operating temperatures in this appliance are below the level to convert ceramic fibers to cristobalite. Abnormal operating conditions would have to be created to convert the ceramic fibers in this appliance to cristobalite.
The ceramic fiber material used in this appliance is an irritant; when handling or replacing the ceramic materials it is advisable that the installer follow these safety guidelines. Avoid breathing dust and contact with skin
The boiler contains ceramic fiber materials. Use care when handling these materials per instructions on this page. Failure to comply could result in severe personal injury.
6. Use a vacuum cleaner to remove any accumulation on the tube sheet surfaces. Do not use any solvent. 7. Brush the heat exchanger (tube sheet, combustion chamber walls, and tube entry) while dry using a nylon bristle brush. Caution: DO NOT use a metal brush. Re-vacuum the heat exchanger. 8. Finish cleaning using a clean cloth dampened with warm water. 9. Temporarily remove the condensate drain line from the condensate trap and route directly to a drain. 10. Rinse out debris with a low pressure water supply. The water will drain through the condensate connection. 11. Allow the heat exchanger to thoroughly dry. 12. Reconnect the condensate drain line to the condensate trap. 13. Close isolation valves on piping to isolate boiler from system. Attach a hose to the boiler drain and flush boiler thoroughly with clean water by using purging valves to allow water to flow through the water make-up line to the boiler. 14. When securing the burner, be sure to tighten the nuts, but DO NOT over-tighten. Tighten the nuts to a torque setting of no more than 6.2 ft.-lbs. When securing the burner mounting plate be sure to tighten the nuts, but DO NOT over-tighten. Tighten the nuts to a torque setting of no more than 15.5 ft.-lbs.
chamber lining to prevent airborne dust. Remove the combustion chamber lining
from the boiler and place it in a plastic bag for disposal. Wash potentially contaminated clothes
separately from other clothing. Rinse clothes washer thoroughly.
NIOSH stated First Aid.
Eye: Irrigate immediately. Breathing: Fresh air.

Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Always disconnect power to the boiler before servicing. Failure to comply could result in severe personal injury, death, or substantial property damage.
ALWAYS check control module fuses before replacing control module or any major components (blower, etc.). If one of these fuses is blown, it can prevent the control module or other components from operating.
Never jumper (bypass) any device except for momentary testing as outlined in the Troubleshooting chart. Severe personal injury, death, or substantial property damage can result.
Figure 3-1 Control Module Fuses

Do not jumper fuse or replace with any fuse except as specified. Failure to comply could result in severe personal injury, death, or substantial property damage.

Table 3A Troubleshooting Chart - No Display
- No 120 vac supplied to unit. • Check external line switch, fuse, or breaker.
- No voltage through the switch. • Replace switch.
- Bad display board. • Replace board.
- Bad main control board. • Replace the main control board.
- Blown fuse. • Replace fuse F2 on the main control board, see page 38 of this manual.
- Main control board temperature set point satisfied.
- Remote thermostat satisfied. • Review remote thermostat setting.
- Outside air temperature above Warm Weather Shutdown (WWSD) set point for main control board.
- Unit locked out on fault. • Consult display for specific fault. Refer to fault descriptions on page 40 of this manual for corrective actions.
- Ramp delay active. • Check ramp delay parameter settings. Optional PC software required.
Modulate Up to 100%
- Boiler controlled by BMS. • Check BMS parameter settings.

The boiler temperature sensors (inlet water, outlet water, system water, flue, and outdoor air) are all resistance type devices. The following tables show the correct values for the sensors at various temperatures. Use an ohmmeter to read the resistance of the sensor at a known temperature. If the resistance of the sensor does not closely match its corresponding table, replace the sensor
It is important to note that the flue and outlet inlet air - S11/S13 #1 and S12/S14 #2 water sensors have two temperature sensing devices in one housing. These devices are designated as S1/S9, outlet sensor and S3/S10, flue sensor. Please reference the wiring diagram in the Crest Installation and Operation Manual for correct terminal location.
Table 3B - Inlet Water/System Sensor Resistance vs. Temperature
Table 3C - Outdoor Air Sensor Resistance vs. Temperature

-50 490,813 20 46,218 -40 336,606 30 34,558 -30 234,196 40 26,099 -20 165,180 50 19,900 10 118,018 60 15,311 0 85,362 70 11,883 10 62,465 80 9,299
Table 3D - Outlet Water Sensor Resistance vs. Temperature

Pre-Mix Air 1 S11 GY/Y Pre-Mix Air 1 S13 BR/Y
Pre-Mix Air 2 S12 BK/Y Pre-Mix Air 2 S14 T/Y
50 19,553 158 2,004 50 40,030 158 3,478 68 12,690 176 1,464 68 25,030 176 2,492 86 8,406 194 1,084 86 16,090 194 1,816 104 5,715 212 816 104 10,610 212 1,344 122 3,958 122 7,166 140 2,786 140 4,943
Table 3E - Flue Sensor Resistance vs. Temperature

50 40,030 158 3,478 50 258,500 158 16,870 68 25,030 176 2,492 68 125,500 176 12,000 86 16,090 194 1,816 86 80,220 194 8,674 104 10,610 212 1,344 104 52,590 212 6,369 122 7,166 122 35,270 140 4,943 140 24,160

Table 3F Troubleshooting Chart - Noisy System
- Supply gas problem. Natural and LP gas pressures should be between 4 inches w.c. (1.0 kPa) and 14 inches w.c. (3.5 kPa).
- Gas/air mixture problem. • Refer to the Gas Valve Adjustment Procedure on page 53 of this manual for the proper gas valve setting. Verify that the vent/air intake lengths do not exceed the maximum listed in the General Venting section of the Crest Installation and Operation Manual.
- Dirty/damaged burner. • Refer to page 34 in this manual for the burner removal and inspection procedure. Clean or replace the burner as necessary.
- Air in the piping system. • Properly purge all air from the piping system.
- Blown fuse.
No Pump Operation - Boiler Pump System Pump
- Faulty pump. • Replace pump.
- Internal fault on control board. • Replace main control board.
- Faulty pump relay. • Replace relay.
- Incorrect parameter setting.
- System pressure exceeds relief valve setting.

Table 3G Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
Open (will require a manual reset once the condition has been corrected. Press
Either the low gas pressure switch or one of the high gas pressure switches tripped.
the RESET button on the SMART TOUCH display
to reset.)
Low Water Cutoff Open (will require a manual reset once condition has
The low water cutoff is not making.
been corrected. Press the RESET button on the SMART TOUCH display
to reset.)
Blown fuse. • Replace fuse F2 on the control board, see page 38 of this manual.
Open (will require a manual reset once condition has
The blocked drain switch has detected excessive condensate build up inside the unit.
been corrected. Press the RESET button on the SMART TOUCH display
to reset.)
APS Open (will require a manual reset once the condition has been corrected. Press
Blocked flue/inlet pressure switch contacts are open.
the RESET button on the SMART TOUCH display
to reset.)
Gas Pressure SW · Blocked Drain SW

Table 3G (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
The main control board has received a call for heat too quickly after the previous call for heat has ended.
The unit has failed to prove main burner ignition. It will require a manual reset before attempting to fire again.
Ignition (will require a manual reset once the condition
has been corrected. Press the RESET button on the SMART TOUCH
display to reset.)
Anti-cycling · Flame Failure

Table 3G (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
Sequence 1 (will require a manual reset once the condition
The flame detector 1 circuit is seeing a flame signal while no flame is present.
has been corrected. Press the RESET button on the SMART TOUCH
display to reset.)
Sequence 2 (will require a manual reset once the condition
The flame detector 2 circuit is seeing a flame signal from burner 1.
has been corrected. Press the RESET button on the SMART TOUCH
display to reset.)
Running 1 (will require a manual reset once the condition
The unit was running and lost the flame signal.
has been corrected. Press the RESET button on the SMART TOUCH
display to reset.)
Flame Out of · Flame Out of · Flame Failure

Table 3G (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
Running 2 (will require a manual reset once the condition has been corrected. Press
The unit was running and lost the flame signal.
the RESET button on the SMART TOUCH display
to reset.)
Gas Valve / Relay
Failure 1 (will require a manual reset once the condition has been corrected. Press
The main control board did not detect gas valve 1.
the RESET button on the SMART TOUCH display
to reset.)
Gas Valve / Relay
Failure 2 (will require a manual reset once the condition has been corrected. Press
The main control board did not detect gas valve 2.
the RESET button on the SMART TOUCH display
to reset.)
Flame Failure

Table 3G (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
The outlet water temperature has exceeded the setting of the automatic reset high limit.
Manual Reset High Limit Open
(will require a manual reset once the condition has been corrected. Press
The outlet water temperature has exceeded the setting of the high limit.
the RESET button on the SMART TOUCH display
to reset.)
Auto Reset · High Limit

Table 3G (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
Fan Speed Low 1
(will require a manual reset once the condition has been corrected. Press
The actual fan 1 RPM is 30% lower than what is being called for.
the RESET button on the SMART TOUCH display
to reset.)
Blown fuse. • Replace fuse F2 on the control board, see page 36 of this manual.
Fan Speed Low 2
(will require a manual reset once the condition has been corrected. Press
The actual fan 2 RPM is 30% lower than what is being called for.
the RESET button on the SMART TOUCH display
to reset.)
Blown fuse. • Replace fuse F2 on the control board, see page 36 of this manual.
Fan Speed High 1
(will require a manual reset once the condition has been corrected. Press
The actual fan 1 RPM is 30% higher than what is being called for.
the RESET button on the SMART TOUCH display
to reset.)
Fan Speed High 2
(will require a manual reset once the condition has been corrected. Press
The actual fan 2 RPM is 30% higher than what is being called for.
the RESET button on the SMART TOUCH display
to reset.)

Table 3G (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
Sw Open (will require a manual reset once the condition has been corrected. Press
An optional remote proving switch is not making.
the RESET button on the SMART TOUCH display
to reset.)
The stack temperature has exceeded the set parameters for the boiler.
Delta T High The temperature rise across the heat exchanger has exceeded the set parameters for the boiler.
High Outlet water temperature has exceeded the maximum outlet water temperature.
Louver Proving · Flue Temp High · Outlet Temp

Table 3G (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
Outlet water temperature has exceeded the maximum outlet water temperature.
Rem Ctrl Flt External control is cycling too often.
Saved (will require a manual reset once the condition has been corrected. Press
After downloading parameters from a laptop, the main control board must be reset.
the RESET button on the SMART TOUCH display
to reset.)
While the unit is in Service Mode, the outlet temperature has exceeded 185°F.

Table 3G (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
Sensor Open (will require a manual reset once the condition has been corrected. Press
Either the inlet water or outlet water temperature sensor has been disconnected.
the RESET button on the
display to reset.)
(will require a manual reset once the condition has been corrected. Press
Either the inlet water or outlet water temperature sensor has been shorted.
the RESET button on the
display to reset.)
Open (will require a manual reset once the condition has been corrected. Press
The flue sensor has been disconnected or removed from the flue.
the RESET button on the
display to reset.)
Shorted (will require a manual reset once the condition has been corrected. Press
The flue sensor has been shorted.
the RESET button on the
display to reset.)
Sensors equipped with an internal limit (such as the Lochinvar Squire® Indirect Tank), the limit has opened due to temperature (195°F) or the sensor has become disconnected.
Switch Open 1 (will require a manual reset once the condition has been corrected. Press
Blower proving pressure switch 1 contacts are open.
the RESET button on the
display to reset.)

Table 3G (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
Switch Open 2 (will require a manual reset once the condition has been corrected. Press
Pressure switch contacts are open.
the RESET button on the
display to reset.)
Differential (will require a manual reset once the condition has been corrected. Press
Combustion air to burner 1 temperature is higher than combustion air to burner 2 temperature or vice versa.
the RESET button on the
display to reset.)
High 1 (will require a manual reset once the condition has been corrected. Press
Combustion air temperature is very high.
the RESET button on the
display to reset.)
High 2 (will require a manual reset once the condition has been corrected. Press
Combustion air temperature is very high.
the RESET button on the
display to reset.)

Table 3G (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
Too Many Resets - Try Later
Too many manual resets have occurred during a 15 minute period.
The main control board has detected an internal fault. • Replace the main control board.
The main control board has detected an internal fault. • Replace the main control board.
Shutdown The stack temperature has exceeded the set parameters for the boiler.
The temperature rise across the heat exchanger has exceeded the set parameters for the boiler.

Table 3G (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
Shutdown Outlet water temperature has exceeded the maximum outlet water temperature.
Watch Dog Error The main control board has detected an internal fault. • Replace the main control board.
Write EEProm The main control board has detected an internal fault. • Replace the main control board.
CRC Parameters The main control board has detected an internal fault. • Replace the main control board.
No Error Stored The main control board has detected an internal fault.
Outlet Temp

Table 3I Flue Products
You must replace the flue gas temperature sensor to prevent flue gas spillage into the room. Failure to comply could result in severe personal injury, death, or substantial property damage.
Table 3H Troubleshooting Chart - Combustion Levels
Gas Supply Pressure • Refer to Section 6 - Gas Connections of the Crest Installation and Operation Manual for the proper gas supply for the Crest boiler.
Gas Valve Adjustment • Refer to page 53 of this manual for the gas valve adjustment procedure.


Locate the throttle adjustment screw on the gas valve. For Models 1.5 and 2.0 see FIG. 3-2, for Model 2.5 see FIG. 3-3 and for Models 3.0 and 3.5 see FIG. 3-4. Using a screwdriver, turn the screw a 1/4 turn counterclockwise to increase CO2 levels or a 1/4 turn clockwise to decrease CO2 levels. After one adjustment on the valve, follow the Combustion Analysis Procedure on page 52 of this manual to measure the combustion.
If combustion is still not within the specified range, repeat the procedure. This procedure SHOULD NOT be performed more than four (4) times. If after four (4) adjustments and the combustion is still not within the specified range, revisit the possible causes in Table 3H on page 52 or replace the gas valve.


NOTES


Revision Notes: Revision A (ECO #C08179) initial release.
Revision B (ECO C08436) reflects changes made to the parameter table, notice added to the parameter descriptions, changed out the screens on FIG.’s 1-8 and 1-14.
FB-SER Rev B · 7/11
What the fault codes shown on the display mean and how to clear them.
| Code | Meaning | Fix | |
|---|---|---|---|
| F2 | 3.15 AMP | p.36 |
Common problems, likely causes, and what to do.
| Problem | Possible cause | Remedy | |
|---|---|---|---|
| No Display | - No 120 vac supplied to unit. | • Check external line switch, fuse, or breaker. • Check position of ON/OFF switch. Turn switch to the ON position. • Check 120 vac through the ON/OFF switch. • Check wiring harness connection between display board and main control board. Connect harness at both points. | p.37 |
| No Display | - No voltage through the switch. | • Replace switch. | p.37 |
| No Display | - Bad display board. | • Replace board. | p.37 |
| No Display | - Bad main control board. | • Replace the main control board. | p.37 |
| No Display | - Blown fuse. | • Replace fuse F2 on the main control board, see page 38 of this manual. | p.37 |
| No Burner Operation | - Main control board temperature set point satisfied. | • Review temperature setting. | p.37 |
| No Burner Operation | - Remote thermostat satisfied. | • Review remote thermostat setting. | p.37 |
| No Burner Operation | - Outside air temperature above Warm Weather Shutdown (WWSD) set point for main control board. | • Check location of outside air sensor. Check resistance of outdoor air sensor and compare to Table 3C on page 38 of this manual. | p.37 |
| No Burner Operation | - Unit locked out on fault. | • Consult display for specific fault. Refer to fault descriptions on page 40 of this manual for corrective actions. | p.37 |
| Unit Does Not Modulate Up to 100% | - Ramp delay active. | • Check ramp delay parameter settings. Optional PC software required. | p.37 |
| Unit Does Not Modulate Up to 100% | • Turn ramp delay feature off. See page 20 of this manual for instructions on how to turn this feature off. | p.37 | |
| Unit Does Not Modulate Up to 100% | - Boiler controlled by BMS. | • Check BMS parameter settings. | p.37 |
| Noisy Operation | - Supply gas problem. Natural and LP gas pressures should be between 4 inches w.c. (1.0 kPa) and 14 inches w.c. (3.5 kPa). | • Refer to Section 6 - Gas Connections of the Crest Installation and Operation Manual for detailed information concerning the gas supply. | p.39 |
| Noisy Operation | - Gas/air mixture problem. | • Refer to the Gas Valve Adjustment Procedure on page 53 of this manual for the proper gas valve setting. Verify that the vent/air intake lengths do not exceed the maximum listed in the General Venting section of the Crest Installation and Operation Manual. | p.39 |
| Noisy Operation | - Dirty/damaged burner. | • Refer to page 34 in this manual for the burner removal and inspection procedure. Clean or replace the burner as necessary. | p.39 |
| Noisy Operation | - Air in the piping system. | • Properly purge all air from the piping system. | p.39 |
| No Pump Operation - Boiler Pump System Pump or HWG Pump | - Blown fuse. | • Replace fuse F4 on the control board, see page 36 of this manual. | p.39 |
| No Pump Operation - Boiler Pump System Pump or HWG Pump | - Faulty pump. | • Replace pump. | p.39 |
| No Pump Operation - Boiler Pump System Pump or HWG Pump | - Internal fault on control board. | • Replace main control board. | p.39 |
| No Pump Operation - Boiler Pump System Pump or HWG Pump | - Faulty pump relay. | • Replace relay. | p.39 |
| No Pump Operation - Boiler Pump System Pump or HWG Pump | - Incorrect parameter setting. | • Reference the Boiler Pump Mode and System Pump Mode parameters in the Service section of this manual. | p.39 |
| Relief Valve Opening | -System pressure exceeds relief valve setting. | • Lower the system pressure below the rating of the supplied relief valve or replace the standard relief valve with a higher rated valve up to the maximum pressure of the heat exchanger 160 psi (40 kPa). • Improperly sized expansion tank. | p.39 |
| Gas Pressure SW Open (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART TOUCH display to reset.) | • Measure the supply gas pressure to determine cause of failure. Natural and LP gas pressures should be between 4 - 14 inches w.c. (1.0 - 3.5 kPa). • Refer to Section 6 - Gas Connections of the Crest Installation and Operation Manual for detailed information concerning the gas supply. • Correct the supply gas pressure if necessary. | p.40 | |
| Low Water Cutoff Open (will require a manual reset once condition has been corrected. Press the RESET button on the SMART TOUCH display to reset.) | • Reset the LWCO from the RESET button on the front control panel. • Verify system is full of water and all air has been purged from the system. • Check for loose or misplaced jumpers if flow switch or LWCO is not installed. | p.40 | |
| Low Water Cutoff Open (will require a manual reset once condition has been corrected. Press the RESET button on the SMART TOUCH display to reset.) | • Replace fuse F2 on the control board, see page 38 of this manual. | p.40 | |
| Blocked Drain SW Open (will require a manual reset once condition has been corrected. Press the RESET button on the SMART TOUCH display to reset.) | • Check condensate tube from unit to floor drain for proper installation and obstructions. • Inspect condensate trap for blockage. Clean if necessary. • Check for loose wiring connection at wire harness plug. • Bad blocked drain switch. Replace switch. | p.40 | |
| APS Open (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART TOUCH display to reset.) | • Check the wiring connections to switch. Wires should be connected to the common and normally closed terminals. • Vent/air intake lengths exceed the maximum allowed lengths. Refer to Section 2 - General Venting of the Crest Installation and Operation Manual for proper lengths. • Check for obstruction or blockage in the vent/air intake pipes or at terminations. • Check reference hose and tubing connected to the pressure switch for blockage or obstruction. • Inspect the burner. Reference page 34 of this manual for removal and cleaning procedures. Replace if necessary. • Inspect the heat exchanger. Reference page 35 of this manual for removal and cleaning procedures. Replace if necessary. • Faulty air pressure switch. Replace switch. • Verify combustion air blower is operating. Replace if necessary. | p.40 | |
| Anti-cycling | • The control board will release the call for heat after a set time period. • The control board will release the call for heat if the outlet temperature drops too quickly. | p.41 | |
| Flame Failure Ignition (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART TOUCH display to reset.) | • Inspect spark electrode and associated wiring for damage and connection. Reference page 34 of this manual for removal and cleaning procedures. Replace if necessary. • Visually check for presence of a spark from the view port. • Check for proper electrical grounding of the unit. • Check incoming supply gas pressure. Natural and LP gas pressures should be between 4 - 14 inches w.c. (1.0 - 3.5 kPa). Refer to Section 6 - Gas Connections of the Crest Installation and Operation Manual for detailed information concerning the gas supply. • Verify that the plastic hose from gas valve 1 to the air inlet is connected and is not damaged. • Verify that the vent/air intake pipes are correctly installed and that there are no obstructions. • If 120 vac is present at the main control board, check the wiring between the main control board and the gas valve. Replace the wiring if necessary. Do not disconnect the wiring from the gas valve and attempt to measure voltage at that point. The main control board can detect if the gas valve is not connected and will display the Gas Valve / Connection fault. • If 120 vac is present, check the outlet of the valve to ensure the valve is flowing gas. With a manometer connected to the outlet tap of the gas valve, when the unit is in the prepurge period, there should be a negative pressure present. When the valve is energized a change in pressure should occur. If the pressure change does not occur, the gas valve is not opening. Replace the gas valve. • Inspect flame sensor and associated wiring. Reference page 34 of this manual for removal and cleaning procedures. Replace if necessary. • Inspect the burner. Reference page 34 of this manual for removal and cleaning procedures. Replace if necessary. | p.41 | |
| Flame Out of Sequence 1 (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART TOUCH display to reset.) | • Check supply voltage for proper polarity. • Check external wiring for voltage feedback. • Check the internal wiring for bad connections. | p.42 | |
| Flame Out of Sequence 2 (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART TOUCH display to reset.) | • Check combustion of burner 1 and adjust valve 1 if necessary. • Check supply voltage for proper polarity. • Check external wiring for voltage feedback. • Check the flame rod and make sure it is clean. • Check internal wiring for bad connections. • Remove and inspect the burner. | p.42 | |
| Flame Failure Running 1 (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART TOUCH display to reset.) | • Inspect flame rod 1 and associated wiring for damage and connection. Reference page 34 of this manual for removal and cleaning procedures. Replace if necessary. • Check for proper electrical grounding of unit. • Check incoming supply gas pressure. Natural and L.P. gas pressures should be between 4 - 14 inches w.c. (1.0 - 3.5 kPa). Refer to Section 6 - Gas Connections of the Crest Installation and Operation Manual for detailed information concerning the gas supply. • Verify that the plastic hose from the gas valve to the air inlet is connected and is not damaged. • Verify that the vent/air intake pipes are installed correctly and there are no obstructions. • Inspect flame sensor and associated wiring. Reference page 34 of this manual for removal and cleaning procedures. Replace if necessary. • Check combustion. • Inspect the burner. Reference page 34 of this manual for removal and cleaning procedures. Replace if necessary. | p.42 | |
| Flame Failure Running 2 (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART TOUCH display to reset.) | • Inspect flame rod 2 and associated wiring for damage and connection. Reference page 34 of this manual for removal and cleaning procedures. Replace if necessary. • Check for proper electrical grounding of unit. • Check incoming supply gas pressure. Natural and L.P. gas pressures should be between 4 - 14 inches w.c. (1.0 - 3.5 kPa). Refer to Section 6 - Gas Connections of the Crest Installation and Operation Manual for detailed information concerning the gas supply. • Verify that the plastic hose from the gas valve to the air inlet is connected and is not damaged. • Verify that the vent/air intake pipes are installed correctly and there are no obstructions. • Inspect flame sensor and associated wiring. Reference page 34 of this manual for removal and cleaning procedures. Replace if necessary. • Check combustion. • Inspect the burner. Reference page 34 of this manual for removal and cleaning procedures. Replace if necessary. | p.43 | |
| Gas Valve / Relay Failure 1 (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART TOUCH display to reset.) | • Check wiring harness connection at the gas valve and at the main control board. • Replace the gas valve wire harness. • Replace the gas valve. | p.43 | |
| Gas Valve / Relay Failure 2 (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART TOUCH display to reset.) | • Check wiring harness connection at the gas valve and at the main control board. • Replace the gas valve wire harness. • Replace the gas valve. | p.43 | |
| Auto Reset High Limit | • Verify that the system is full of water and that all air has been properly purged from the system. • Verify that the boiler is piped properly into the heating system. Refer to Section 5 - Hydronic Piping of the Crest Installation and Operation Manual for the proper piping methods for the Crest boiler. • Check 120 vac to boiler pump motor on a call for heat. If voltage is not present, check wiring back to the main control board. • Check the ARHL set point. • If 120 vac is present on a call for heat and the boiler pump is not operating, replace the pump. • If the system pump is a variable speed pump, ensure that the system flow is not less than the boiler flow. • If operating on something other than an outlet sensor, check temperature setting of the main control board. • If the optional manual reset high limit has tripped, check setting of the device. • Check resistance of water sensors and compare to Table 3B on page 38 of this manual. Replace sensor if necessary. • Replace the main control board. | p.44 | |
| Manual Reset High Limit Open (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART TOUCH display to reset.) | • Verify that the system is full of water and that all air has been properly purged from the system. • Verify that the boiler is piped properly into the heating system. Refer to Section 5 - Hydronic Piping of the Crest Installation and Operation Manual for the proper piping methods for the Crest boiler. • Check voltage to boiler pump motor on a call for heat. If voltage is not present, check wiring back to the main control board. • Replace the pump relay if necessary. • If 120 vac is present on a call for heat and the boiler pump is not operating, replace the pump. • If the system pump is a variable speed pump, ensure that the system flow is not less than the boiler flow. • If operating on either an inlet or system supply sensor, check temperature setting of the main control board. • If the high limit has tripped, check setting of the device and the MRHL set point. • Check resistance of water sensors and compare to Table 3B on page 38 of this manual. Replace sensor if necessary. • Replace high limit (if equipped). • Replace main control board. | p.44 | |
| Fan Speed Low 1 (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART TOUCH display to reset.) | • Vent/air intake lengths exceed the maximum allowed lengths. Refer to Section 2 - General Venting of the Crest Installation and Operation Manual for proper lengths. • Check for obstruction or blockage in the vent/air intake pipes or at terminations. • Check the wiring connections at fan 1 and at the main control board. • Replace the fan. | p.45 | |
| Fan Speed Low 1 (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART TOUCH display to reset.) | • Replace fuse F2 on the control board, see page 36 of this manual. | p.45 | |
| Fan Speed Low 2 (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART TOUCH display to reset.) | • Vent/air intake lengths exceed the maximum allowed lengths. Refer to Section 2 - General Venting of the Crest Installation and Operation Manual for proper lengths. • Check for obstruction or blockage in the vent/air intake pipes or at terminations. • Check the wiring connections at fan 2 and at the main control board. • Replace the fan. | p.45 | |
| Fan Speed Low 2 (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART TOUCH display to reset.) | • Replace fuse F2 on the control board, see page 36 of this manual. | p.45 | |
| Fan Speed High 1 (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART TOUCH display to reset.) | • Vent/air intake lengths exceed the maximum allowed lengths. Refer to Section 2 - General Venting of the Crest Installation and Operation Manual for proper lengths. • Check for obstruction or blockage in the vent/air intake pipes or at terminations. • Check the wiring connections at the fan and at the main control board. • Replace the fan. | p.45 | |
| Fan Speed High 2 (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART TOUCH display to reset.) | • Vent/air intake lengths exceed the maximum allowed lengths. Refer to Section 2 - General Venting of the Crest Installation and Operation Manual for proper lengths. • Check for obstruction or blockage in the vent/air intake pipes or at terminations. • Check the wiring connections at the fan and at the main control board. • Replace the fan. | p.45 | |
| Louver Proving Sw Open (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART TOUCH display to reset.) | • Check function of remote devices. • Check for loose or misplaced jumper if proving switch is not installed. | p.46 | |
| Flue Temp High | • Inspect the heat exchanger. Reference page 35 of this manual for the procedure on how to clean the flue side of the heat exchanger. • Inspect the flue sensor and associated wiring. Measure the resistance of the flue sensor and compare to Table 3E on page 38 of this manual. Replace the sensor if necessary. • Verify that the vent/air intake pipes are properly installed and that there are no obstructions. | p.46 | |
| Delta T High | • Verify that the system is full of water and that all air has been properly purged from the system. • Verify that the boiler is piped properly into the heating system. Refer to Section 5 - Hydronic Piping of the Crest Installation and Operation Manual for the proper piping methods for the Crest boiler. • Check for 120 vac to the boiler pump motor on a call for heat. If voltage is not present, check the wiring back to the main control board. Replace the main control board if necessary. • If 120 vac is present on a call for heat and the boiler pump is not operating, replace the pump. • Verify that the boiler pump is set to the proper speed or that the pump is the proper size. Reference Section 5 - Hydronic Piping of the Crest Installation and Operation Manual for boiler pump specifications. • Inspect the inlet and outlet sensors and associated wiring. Measure the resistance of the sensors and compare to the tables on page 38 of this manual. | p.46 | |
| Outlet Temp High | • Verify that the system is full of water and that all air has been properly purged from the system. • Verify that the boiler is piped properly into the heating system. Refer to Section 5 - Hydronic Piping of the Crest Installation and Operation Manual for the proper piping methods for the Crest boiler. • Check for 120 vac to the boiler pump motor on a call for heat. If voltage is not present, check wiring back to the main control board. Replace the main control board if necessary. • If 120 vac is present on a call for heat and the boiler pump is not operating, replace the pump. | p.46 | |
| Outlet Temp High (continued) | • Verify that the boiler pump is set to the proper speed or that the boiler pump is the proper size. Reference Section 5 - Hydronic Piping of the Knight Boiler Installation and Operation Manual for boiler pump specifications. • Inspect the outlet sensors and associated wiring. Measure the resistance of the sensors and compare to the tables on page 38 of this manual. | p.47 | |
| Rem Ctrl Flt | • Check set point of the external control. • Check the wiring between the external control and the unit. • Replace the control. | p.47 | |
| Parameters Saved (will require a manual reset once the condition has been corrected. Press the RESET button on the SMART TOUCH display to reset.) | • Press the RESET button on the SMART TOUCH display panel. | p.47 | |
| Service Blk | • Establish a heating load to remove the heat from the boiler loop. • Verify that the system is full of water and that all air has been properly purged from the system. • Verify that the boiler is piped properly into the heating system. Refer to Section 5 - Hydronic Piping of the Crest Installation and Operation Manual for the proper piping methods for the Crest boiler. • Check 120 vac to the boiler pump motor on a call for heat. If voltage is not present, check the wiring back to the main control board. Replace the main control board if necessary. • If 120 vac is present on a call for heat and the boiler pump is not operating, replace the pump. • Verify that the boiler pump is set to the proper speed or that the boiler pump is the proper size. Reference Section 5 - Hydronic Piping of the Crest Installation and Operation Manual for boiler pump specifications. | p.47 | |
| Sensor Open (will require a manual reset once the condition has been corrected. Press the RESET button on the display to reset.) | • Check the sensors and their associated wiring. Repair or replace the sensor or wiring if damaged. • Measure the resistance of the sensors and compare the resistance to the tables on page 38 of this manual. • Replace the sensor if necessary. | p.48 | |
| Sensor Shorted (will require a manual reset once the condition has been corrected. Press the RESET button on the display to reset.) | • Check the sensors and their associated wiring. Repair or replace the sensor or wiring if damaged. • Measure the resistance of the sensors and compare the resistance to the tables on page 38 of this manual. • Replace the sensor if necessary. | p.48 | |
| Flue Sensor Open (will require a manual reset once the condition has been corrected. Press the RESET button on the display to reset.) | • Check the sensor and its associated wiring. Repair or replace the sensor or wiring if damaged. • Measure the resistance of the sensors and compare the resistance to the tables on page 38 of this manual. • Replace the sensor in flue. • Replace the sensor if necessary. | p.48 | |
| Flue Sensor Shorted (will require a manual reset once the condition has been corrected. Press the RESET button on the display to reset.) | • Check the sensor and its associated wiring. Repair or replace the sensor or wiring if damaged. • Measure the resistance of the sensors and compare the resistance to the tables on page 38 of this manual. • Replace the sensor if necessary. | p.48 | |
| Tank Open | • Check the tank temperature. • Repair or replace the sensor wiring if damaged. • Replace the sensor if necessary. | p.48 | |
| Blower Proving Switch Open 1 (will require a manual reset once the condition has been corrected. Press the RESET button on the display to reset.) | • Check the wiring connections to switch. Wires should be connected to the common and normally open terminals. • Remove switch and check for blockage in the orifice. • Vent/air intake lengths exceed the maximum allowed lengths. Refer to Section 2 - General Venting of the Crest Installation and Operation Manual for proper lengths. • Check for obstruction or blockage in the vent/air intake pipes or at terminations. • Inspect the burner. Reference page 34 of this manual for removal and cleaning procedures. Replace if necessary. • Verify combustion air blower 1 is operating. Replace if necessary. • Inspect the heat exchanger. Reference page 35 of this manual for removal and cleaning procedures. • Faulty pressure switch. Replace switch. | p.48 | |
| Blower Proving Switch Open 2 (will require a manual reset once the condition has been corrected. Press the RESET button on the display to reset.) | • Check the wiring connections to switch. Wires should be connected to the common and normally open terminals. • Remove switch and check for blockage in the orifice. • Vent/air intake lengths exceed the maximum allowed lengths. Refer to Section 2 - General Venting of the Crest Installation and Operation Manual for proper lengths. • Check for obstruction or blockage in the vent/air intake pipes or at terminations. • Inspect the burner. Reference page 34 of this manual for removal and cleaning procedures. Replace if necessary. • Verify combustion air blower 2 is operating. Replace if necessary. • Inspect the heat exchanger. Reference page 35 of this manual for removal and cleaning procedures. • Faulty pressure switch. Replace switch. | p.49 | |
| Burner Supply Temperature Differential (will require a manual reset once the condition has been corrected. Press the RESET button on the display to reset.) | • Inspect the combustion air temperature sensor and associated wiring. • Measure the resistance of the combustion air temperature sensor and compare to Table 3E on page 38 of this manual • Replace the sensor if necessary. • Verify that the vent / air intake pipes are properly installed and that there are no obstructions. | p.49 | |
| Burner Supply Temperature High 1 (will require a manual reset once the condition has been corrected. Press the RESET button on the display to reset.) | • Check if the vent backflow preventer is installed for boilers commonly vented. • Check if the vent backflow preventer is stuck open while the unit is off. • Inspect the combustion air temperature sensor and associated wiring. • Measure the resistance of the combustion air temperature sensor and compare to Table 3E on page 38 of this manual. • Replace the sensor if necessary. | p.49 | |
| Burner Supply Temperature High 2 (will require a manual reset once the condition has been corrected. Press the RESET button on the display to reset.) | • Check if the vent backflow preventer is installed for boilers commonly vented. • Check if the vent backflow preventer is stuck open while the unit is off. • Inspect the combustion air temperature sensor and associated wiring. • Measure the resistance of the combustion air temperature sensor and compare to Table 3E on page 38 of this manual. • Replace the sensor if necessary. | p.49 | |
| Too Many Resets - Try Later | • Wait 15 minutes and try again. • Turn power off to unit, wait 30 seconds and then turn power back on. | p.50 | |
| Internal Fault | • Replace the main control board. | p.50 | |
| Writing to Memos | • Replace the main control board. | p.50 | |
| Flue Temp Shutdown | • Inspect the heat exchanger. Reference page 35 of this manual for the procedure on how to clean the flue side of the heat exchanger. • Inspect the flue sensor and associated wiring. Measure the resistance of the flue sensor and compare to Table 3E on page 38 of this manual. Replace the sensor if necessary. • Verify that the vent/air intake pipes are properly installed and that there are no obstructions. • Replace the main control board. | p.50 | |
| Delta T Shutdown | • Verify that the system is full of water and that all air has been properly purged from the system. • Verify that the boiler is piped properly into the heating system. Refer to Section 5 - Hydronic Piping of the Crest Installation and Operation Manual for the proper piping methods for the Crest boiler. • Check for voltage to the boiler pump motor on a call for heat. If voltage is not present, check the wiring back to the pump relay. Replace the pump relay if necessary. • If 120 VAC is present on a call for heat and the boiler pump is not operating, replace the pump. • Verify that the boiler pump is set to the proper speed or that the pump is the proper size. Reference Section 5 - Hydronic Piping of the Crest Installation and Operation Manual for boiler pump specifications. | p.50 | |
| Outlet Temp Shutdown | • Verify that the system is full of water and that all air has been properly purged from the system. • Verify that the boiler is piped properly into the heating system. Refer to Section 5 - Hydronic Piping of the Crest Installation and Operation Manual for the proper piping methods for the Crest boiler. • Check for voltage to the boiler pump motor on a call for heat. If voltage is not present, check wiring back to the pump relay. Replace the pump relay if necessary. • If 120 VAC is present on a call for heat and the boiler pump is not operating, replace the pump. | p.51 | |
| Watch Dog Error | • Replace the main control board. | p.51 | |
| Write EEProm | • Replace the main control board. | p.51 | |
| CRC Parameters | • Replace the main control board. | p.51 | |
| No Error Stored | • Press the RESET button on the SMART TOUCH display panel. | p.51 |