

SUPERVISED WIRELESS SECURITY CONSOLE

USA & Canada (800) 421-1587 & (800) 392-0123
(760) 438-7000 - Toll Free FAX (800) 468-1340

CONGRATULATIONS for selecting Linear’s DVS-2400 Security System. The DVS-2400 Console incorporates many advanced and sophisticated features. The system can be expanded and customized to fi t the installation’s specifi c needs.

The DVS-2400 Console and its accessories are designed and manufactured by the oldest wireless security company in North America. You can look ahead to many years of reliable service with this Console and its accessories.
Many insurance companies offer discounts on homeowners and renters policies when a security system is installed. Discount credits vary with different companies and generally increase in savings with an increase in the level of protection. Inform the user to ask their insurance agent about savings available.
The DVS-2400 Console is UL Listed. For a UL smoke alarm system, there must be at least one smoke detector programmed into the Console to meet National Fire Protection Association (NFPA) Rule 72 Chapter 2 and UL 217 requirements. Many insurance companies require you to meet these requirements to qualify for a discount. Only use the Model DXS-73 smoke detector with this Console for a UL smoke alarm system.
UL Listed as a Single Station Smoke Detector Accessory, also suitable as a
System Control Unit. UL Category CCN UTGT & NBSX
In this manual, the bullets preceding the text help to defi ne the information. For example:
✦ This symbol indicates a feature.
❏ This symbol indicates an action to perform
and provides a box to check when the action is completed.
✴ This symbol is for lit indications or system sounds.
✎ This symbol is for important notes.
Household Burglar-Alarm




DXT-21 & DXT-23
REMOTES
REMOTES †
DXT-61 REMOTE †
DVS-2400 CONSOLE DXS-10 WIRELESS
DXS-62A REMOTE
KEYPAD
DXS-73 SMOKE DETECTOR
are not listed by UL.
DXS-32 MINI DOOR/WINDOW
DXS-81 BILL TRAP †
DXS-54
DXS-91 GLASS BREAK DETECTOR †
PIR
SENSOR
SENSOR
CONSOLE The DVS-2400 Console is the heart of the system. It monitors all of the system’s wireless sensors and controls the alarm sirens.
The Console has 24-hour capabilities that are always ready to operate, even when the Console is disarmed. They can be triggered by buttons on the Console, the Wireless Keypad, portable remote controls, carbon monoxide detectors, and smoke detectors. Pressing the EMERGENCY or FIRE button for two seconds will cause an immediate siren and call the central station. IMPORTANT: For personal emergency use only. Not for use as a UL Listed Medical Alert System.
The Console constantly monitors the condition of the system’s sensors, displaying which protected doors and windows are open or closed. If an alarm occurs, the Console displays which sensor(s) caused it. When a sensor has a low battery, the Console displays which sensor needs a new battery. Sensors that send hourly status transmissions keep the Console informed of their operating condition.
The Console’s Environmental Zone is a 24-hour zone that can be triggered with sensors connected to devices such as water fl ow detectors, over/under temperature sensors, fl ood sensors, etc. The Environmental Zone activates the chime annunciator without sounding the siren. The Environmental Zone does not send communicator reports.
Up to eight different custom user codes can be used to operate the system. For security, a user code must be entered to disarm (turn off) the system. The system can be armed (turned on) by entering a user code, or with the unique “Quick Arm” feature. The fi ve restricted user codes and the special page alert user code can only arm and disarm the system, no programming changes are allowed. The master user code is allowed to program the Console, and a duress code can be selected for emergency disarming of the system with a duress report to the Central Station. The page alert user code can dial a pager number to inform the pager wearer when the Console is disarmed.
An Automation Output in the Console provides an easy way to connect external devices to the Console. The output is fully programmable to activate on a variety of conditions, such as when the system is armed, during alarms, and during exit/entry delays. The Automation Output can connect to lighting control modules, relays, noisemakers, and indicators. The Console’s and wireless keypad’s key and transmitters can control the Automation Output.
The Console’s memory will retain the user codes and all of the system’s programming, even during a total power loss. An optional backup battery can be installed to power the system during short power failures.
The Console can be programmed locally using its own keypad or remotely, over the telephone, using Linear’s Model RA-2400 Remote Access software program. The RA-2400 upload/ download program is a Windows® application that runs on a personal computer and communicates with the Console through a modem connected directly to the Console, or through the telephone line.
The built-in digital communicator connects the Console to a Central Alarm Monitoring Station through the telephone. With a monitored system, the central station can dispatch authorities in case of burglary, fi re or other emergency. The central station can also call family, friends, neighbors, or anyone else designated on a custom call list.
A total of 24 sensors of the types listed on the next page can be used with each DVS-2400 Console. Each burglary sensor can trigger the siren (and report to the Central Station) once per arming cycle. 24-hour sensors have unlimited alarm and reporting capacity.
Each sensor can report directly to the Central Station using the digital communicator’s Point ID feature. If a sensor triggers an alarm or experiences supervisory trouble, a unique report code can be sent for immediate identifi cation of the event.
The optional Model VB-2 digital voice synthesis module can be installed in the Console. The VB-2 module provides three exciting features: 2-way audio monitoring capability at the Central Station through the communicator, local voice prompts from the Console’s speaker, and voice prompted remote system control using in-house or off-site pushbutton telephones.

DOOR/WINDOW SENSORS The DXS-31 and DXS-32 sensors monitor doors and windows. They send radio signals to the Console. One type of signal is sent when the door or window is opened, and a different type of signal is sent when the door or window is closed. If the Console is armed, a sensor can trigger the Console's burglary siren when its door or window is opened. Both sensors are supervised, send hourly status reports, and monitor their battery condition.
PANIC BUTTONS The DXT-21, DXS-21 single-button, and DXT-23, DXS-23 two-button transmitters can be used as portable “panic buttons”. Pressing the front or top button on the DXT-21 or DXS-21 at any time will trigger the emergency siren. Pressing both front buttons simultaneously on the DXT-23 or DXS-23 at any time will trigger the emergency siren. These transmitters can be programmed to activate various other system functions. The DXT-21 and DXT-23 transmitters are not supervised. The DXS-21 and DXS-23 transmitters are supervised.

The DXS-62A transmitter is typically used as a portable “panic button”. Pressing the button on a DXS-62A at any time will trigger the emergency siren. This transmitter can send hourly status signals and low battery signals if the battery is low.
WIRELESS KEYPAD The DXS-10 wireless keypad is used to operate the Console remotely. It can be placed in a convenient spot so the user doesn't have to go to the Console to control the system. The wireless keypad can also trigger the emergency or fi re siren and actuate the Automation Output. Pressing will cause the Console to sound Beeps corresponding to the current operating mode. The DXS-10 is supervised, it sends hourly status reports and monitors its battery condition. IMPORTANT: For personal emergency use only. Not for use as a UL Listed Medical Alert System.
BILL TRAP The DXS-81 bill trap can be used with the Console in non-UL small commercial hold-up installations. The unit is concealed in a cash drawer under a stack of currency, with a single “bait” bill secured in its money clip. During a hold-up, the cashier removes the stack of currency along with the “bait” bill. When a “bait” bill is removed, the transmitter sends a signal to the Console. Four additional signals are sent within the fi rst minute after the “bait” bill is removed. When the “bait” bill is replaced, a restore signal is sent. The DXS-81 is supervised, it can send hourly status reports (optional) and monitors its battery condition.
SMOKE DETECTOR The DXS-73 is a high quality smoke detector with a built-in radio transmitter. As soon as smoke is detected, the unit will sound its local noisemaker. Then, 20 seconds after the local noisemaker sounds, the transmitter sends an alarm signal to the Console. The alarm signal will be repeated every 20 seconds as long as smoke is still present. A restoral signal will be sent when the smoke detection chamber clears. The DXS-73 is supervised, it sends hourly status reports, and monitors its battery condition.
PASSIVE INFRARED MOTION DETECTOR The DXS-54 is a passive infrared (PIR) motion detector with a built-in radio transmitter. The PIR detects motion in its detection pattern by measuring the infrared emission levels of objects that it “sees”. If the infrared levels change quickly, as when a person moves across the detection pattern, the PIR will recognize the change as an intrusion and send an alarm signal to the Console. An alarm will be triggered if the system is in the Away Mode. The DXS-54 is supervised, it sends hourly status reports and monitors its battery condition.
☞ NOTE: A Model DXS-73 Smoke Detector is required to create a UL Listed smoke alarm system. See Page 13 for details on adding a smoke detector sensor to the system.
REMOTE CONTROLS The DXT-41, DXT-61 single-button and DXT-23, DXT-42 multi-button remote controls can be used to remotely arm and disarm the Console. The DXT-42’s left button will arm and the right button will disarm the Console. Pressing both buttons simultaneously will trigger the emergency siren. Alternately the Console can be programmed to respond to the DXT-42 by arming and disarming with the left button, and activating the automation output with the right button. These transmitters can also be programmed to activate various other Console zones. These transmitters are not supervised.
DXT-41 DXT-61‡ DXT-42
GLASS BREAK DETECTOR The DXS-91 is a glass break detector with an audio sound discriminator and a built-in radio transmitter. The unit “listens” for the sound of breaking glass. When glass breakage is detected, the unit sends an alarm signal to the Console. The DXS-91 is supervised, it sends hourly status reports and monitors its battery condition.

✦ The example shows a typical DVS-2400 system.
✦ Any or all of the accessories shown can be used.
✦ A total of 24 sensors can be used with each
Console.

CON - CONSOLE S - DOOR/WINDOW SENSOR WK - WIRELESS KEYPAD MD - MOTION DETECTOR ES - EXTERNAL SIREN SD - SMOKE DETECTOR CO - CARBON MONOXIDE DETECTOR GB - GLASS BREAK SENSOR MS - HARDWIRED MAGNETIC SWITCH
Example Residential Security System Floor Plan

✦ Sensor mounts on door or window with adjacent
magnet.
✦ Opening door or window moves magnet away,
triggering sensor.

✦ Pressing the case causes sensor to send a test
signal.
✦ Jumper inside for INSTANT or DELAYED alarm
setting.
✦ Press the case for testing, the red transmit light
shows that battery is in good condition.
✦ Internal lithium batteries are monitored by the
Console.
✦ Sends hourly status reports to the Console.
✦ Up to 3 years battery life (depends on frequency of
activation). (UL tested for 1 year minimum.)
✦ Sensor contains internal terminals for connection to
glass break detector and external switches.
✦ For controlling the system remotely without having
to go to the Console.

✦ Green operation light.
✦ Internal 9-volt battery is monitored by the Console.
✦ Keypad's beeper will buzz during transmissions
when the battery is low.
✦ Up to 3 years battery life (depends on frequency of
activation). (UL tested for 1 year minimum.)
✦ Sends hourly status reports to the Console.
✦ Press to activate the automation output.
ABOUT SENSOR STATUS SUPERVISION All DXS Format sensors transmit hourly status reports. All DXT Format sensors do not transmit hourly status reports. Both sensor formats can be used with the Console.
✦ Pressing clears the keypad.
✦ Pressing for two seconds sounds the mode Beeps from the Console.
✔ Off Mode: 1 “Gong”.
When a sensor is programmed into the Console, the system will set the sensor as non-supervised or supervised. Sensors set as non-supervised are not expected to send hourly status reports. Sensors set as supervised are expected to send hourly status reports. If a status report is not received in 8 hours from a sensor set as supervised, the TROUBLE indicator will fl ash.
✔ Chime Mode: 1 “Gong” & 1 “Beep”.
✔ Home Mode: 1 “Gong” & 2 “Beeps”.
✔ Away Mode: 1 “Gong” & 3 “Beeps”.
✔ Test Mode: 1 “Gong” & 4 “Beeps”.
When sensors are programmed into the Console, ALL STATIONARY SENSORS ARE SET AS SUPERVISED, ALL PORTABLE SENSORS ARE SET AS NON-SUPERVISED.
✦ Emergency and fi re alarm can be triggered from the
wireless keypad at any time.
If stationary DXT Format sensors have been programmed into the Console, be sure to change their setting to non-supervised to prevent TROUBLE indications. This will not prevent low battery monitoring.
for use as a UL Listed Medical Alert System.
If portable DXS Format sensors have been programmed into the Console, and the installation requires supervision for specifi c portable sensor(s), change the selected portable sensors setting to supervised.
After programming the sensors, if changes are required, refer to “Changing a Sensors Supervision” on Page 26 for details on changing the way a sensor’s supervision is set.


★ Specifi c indicator will light showing the mode the Console is in. ★ HOME indicator will blink during Secure Exit and Home Instant modes. ★ AWAY indicator will blink during the exit delay in the Away Mode.
★ Shows the current status of the Console.
★ Glows when AC power is on. ★ Blinks when AC power is off and backup battery is installed. ★ Blinks when the backup battery is low, recharging or missing. ★ Off when AC power is off and no backup battery is installed (system disabled).
★ Blinks when one or more sensors have a low battery. ★ Press for one second to view sensor status. Sensor status indicator for any sensor with a low battery will light along with the BATTERIES indicator. Any trouble indications will follow during the fi ve second status cycle. ★ Switch to Test Mode after replacing the sensor battery and completely test the
system (see Test Mode). Switching to Test Mode clears the low battery indication.
★ Blinks when one or more sensors have not reported status during the eight hour
status time period. ★ Press for one second to view sensor status. Sensor status indicator for any sensor that has not reported in will light along with the TROUBLE indicator. Any low battery indications will follow during the fi ve second status cycle. ★ Switch to Test Mode after servicing the sensor and completely test the system
★ Pressing FIRE for two seconds sounds the fi re siren and sends a “fi re” message
to a central monitoring station through the digital communicator (if the system is monitored). ★ Pressing EMERGENCY for two seconds sounds the emergency siren and sends
(see Test Mode). Switching to Test Mode clears the trouble indication.
an “emergency” message to a central monitoring station through the digital communicator (if the system is monitored). ★ Both work even when system is disarmed. ★ IMPORTANT: For personal emergency use only. Not for use as a UL Listed
★ Makes unique sounds for burglary, fi re and emergencies. ★ Alarm sirens stop automatically after fi ve minutes. ★ Sounds advisory tones to confi rm keystrokes from the Console. ★ Sounds mode selection tones. ★ Sounds alarm memory tones. ★ Beeps when Automation Output is activated. ★ Speaks the system status information when optional VB-2 digital voice synthesis
Medical Alert System.
★ Used to operate the system.
module is installed. ★ Terminals available for an external siren.
★ Off Mode disarms the system. ★ Switching to Off Mode stops the alarm siren.
✓ Multiple Beeps sound and sensor status indicators fl ash if an alarm has
occurred. ☞ Multiple Beeps mean caution. AN INTRUDER MAY STILL BE PRESENT.
★ Indicates the status of each of the system’s sensors. ★ Lights show which doors and windows are open. ★ Lights fl ash to display sensors that have caused an alarm. ★ Stick-on labels are provided to identify the custom sensor locations.
★ Chime Mode disarms the system. ★ Switching to Chime Mode stops the alarm siren.
✓ Multiple Beeps sound and sensor status indicators fl ash if an alarm has
★ Remove clear display window and sensor identifi cation card to gain access to
occurred. ☞ Multiple Beeps mean caution. AN INTRUDER MAY STILL BE PRESENT. ★ Chime Mode is for monitoring doors and windows.
the screw. ★ Remove case access screw to unlock case. Case hinges open to the left.
✓ Use this mode as an “automatic door chime” when at home. ✓ Opening any protected door or window causes the Console to “ding-dong”.
★ Backlit keys for easy viewing in low light conditions. ★ For entering the user's user code (numerically or alphabetically). ★ Used when programming system options. ★ Press to activate the Automation Output. ★ Press to clear keypad if the wrong key is pressed. ★ Press for one second to view sensor battery and supervisory status (see BATTERIES and TROUBLE indicator description).
★ Home Mode arms the perimeter sensors, but not the interior sensors.
✓ Use this mode when anyone is staying behind. ✓ Interior motion detectors and interior door sensors are not armed. ✓ Home secure mode makes all delayed perimeter sensors instant. ✓ Secure exit mode starts an exit delay while remaining in Home Mode. ✓ Re-entering during the exit delay restarts the exit delay (one time only).
★ Away Mode arms the entire system.
✓ Use this mode when leaving home. ✓ Door sensors set for delayed will have a time delay that allows the user to
leave and enter the premises without sounding the alarm. ✓ Re-entering during the exit delay restarts the exit delay (one time only). ✓ Entry Delay Beeps warn the user to disarm the system before the siren
starts.
★ Test Mode is for testing the system sensors.
✓ All sensor status lights blink when the Test Mode is entered. ✓ Each sensor status light will stop blinking when its sensor is tested. ★ Hold the TEST button down to test all of the Console's indicator lights.


19 RADIO TEST POINTS
★ Type 2AG, 1-amp fuse. ★ Protects the external relay output when used with wet contacts (12 VDC
★ Used to monitor the Console's radio receiver during troubleshooting. ★ Provides connection for an audio amplifi er to listen to the receiver's output. ★ Helpful to determine sources of radio interference.
switched out). ★ Fuse will blow when load exceeds 1 amp. ✎ WARNING: For continued protection against the risk of fi re, replace only
with the same type and rating of fuse.
★ High sensitivity microphone. ★ Detects room audio when communicator is reporting to the Central Station
in 2-way audio mode (Model VB-2 digital voice synthesis module must be installed).
★ Terminals for connection to the plug-in AC transformer. ★ Terminals for connection to an external siren speaker. ★ Automation Output to connect to an automation controller. ★ External relay output for “wet” contacts (switched 12 volts) or “dry” contacts
★ Varies the volume of the advisory tones that come from the speaker. ★ Does not affect internal or external sirens (they are always full volume).
(normally open 1 amp @ 24 volts maximum).
22 DIGITAL VOICE SYNTHESIS MODULE (OPTIONAL)
★ Type 2AG, 3-amp fuse for the backup battery. ★ If the POWER light is fl ashing and the optional backup battery is installed and
★ The Model VB-2 gives the Consoles's digital communicator listen-only, manual
2-way and full duplex 2-way audio capability with the Central Station. ★ The module allows remote command of the system using a standard pushbutton
charged, check this fuse. ✎ WARNING: For continued protection against the risk of fi re, replace only
telephone, on or off site. ★ The module provides optional voice prompts from the Console’s speaker. ★ Units programmed for two-way duplex can still be controlled manually by
with the same type and rating of fuse.
pressing the “1” or “3” key. ★ The Central Station can now return the unit to two-way duplex by pressing the
★ Provides telephone connections for the digital communicator. ★ Provides telephone connection for voice prompted telephone remote control
“8” key.
(optional VB-2 digital voice response module required). ★ Provides seized ring and tip connections for local telephone instruments.
Communicator will disconnect local telephones while on-line.
★ Connects the internal speaker to the Console circuit board. ★ 2-pin connector, non-polarized.
★ Antenna and ground terminals for receiving signals from the system's sensors. ★ Pre-wired to the Console's internal wire dipole antenna. ★ Alternately connects to the Model LA-P local whip and remote antenna kit.
★ Space for 12-volt, 1.2 amp/hour backup battery. (Highly recommended.) ★ Backup battery is automatically charged and monitored by the Console. ★ Backup battery can power the Console for up to 6 hours. ★ UL NOTE: Normal estimated battery life should be 3 to 4 years.
★ Provides access to recessed wiring trough in base of Console. ★ Route cables for power, telephone, external speaker, etc. through this hole. ★ Loop for zip-tie strain relief provided next to hole.
★ Used when mounting Console recessed in the wall. ★ Two mounting brackets (supplied) slide through slots and are retained by
screws, clamping the unit to the wall.


reach the Console.
✔ Try to centrally locate the Console.
✔ Keep Console away from large metal
USE A PAPER CLIP TO REMOVE THE CLEAR DISPLAY WINDOW
appliances.
✔ Maximum recommended sensor range is 400
feet (system tested at 1000 feet).
Console should be easily accessible to the usual entrance.
✔ When the Console is set in the Away Mode,

the user has 30 seconds to switch to Off Mode before the burglary siren sounds.
the alarm can be heard during the night hours.
✔ Optional remote external sirens (up to 150 feet
from the Console) can be used to make alarms louder and remote the sound location.

✦ To access the Console’s internal components or
to prepare the Console for wall mounting, the case locking screw needs removing.
CUT A 10" x 6 3/4" HOLE CENTERED BETWEEN STUDS IN MOUNTING WALL AT A CONVENIENT HEIGHT
✦ If desired, the Console can be surface mounted or
recessed into the wall.


SECURE CONSOLE TO WALL USING THE TWO CLAMPS AND SCREWS PROVIDED
Surface Mounting · Recessed Mounting


✦ An external console speaker sounds system tones
and alerts occupants with a loud siren during alarm.
✦ With the VB-2 module installed, the Central Station
can talk to the occupants through the external console speaker.
✦ Use an 8-ohm, 10 watt minimum rated speaker. Do
not use a horn/siren with a built-in siren driver.
✦ Up to two 8-ohm speakers can be used with each
Console.
AC AC EXT. SPKR (-) H/A - H/A + RELAY N.O. RELAY DRY
✦ Up to 150 feet of 22 AWG wire can be used with
each speaker.
✦ The system tone volume can be adjusted with the
annunciator volume control.
CONNECT SPEAKER LEADS TO EXT. SPKR & (-) TERMINALS
connect the second speaker in parallel, to the same EXT. SPKR & (-) terminals as the fi rst speaker.

✦ An external siren alerts occupants and neighbors
with a loud siren during alarm.
✦ Use a 12 volt, 1 amp maximum rated weather-
resistant horn speaker with a built-in siren driver. Do not use a plain speaker.
motor bell is not recommended because of the radio interference generated when the bell is running.
AC AC EXT. SPKR (-) H/A - H/A + RELAY N.O. RELAY DRY
✎ UL NOTE: Not for use in UL installations.
the relay contacts will become isolated. Use the RELAY N.O. & RELAY DRY terminals to switch an externally powered load.
CONNECT SIREN LEADS TO (-) & RELAY N.O. TERMINALS


✦ Connect the Console to the telephone line if the
system is monitored, requires 2-way audio, or requires telephone remote command.
✦ Telephone RING & TIP terminals are for connection
to the incoming telephone line.
✦ Seized telephone ring & tip are for connection
to local telephone sets. When the communicator activates, all the local telephone sets will be disconnected to prevent an off-hook telephone on the premises from blocking the communicator call.
LINE RING (R) LINE TIP (T)

T R R1 T1 SHORTING BAR SHORT REMOVED ON PLUG INSERTION
✦ When directly connecting (without a telephone line)
to the DVS-2400 with the RA-2400 remote access software (Version 1.3 or later), disconnect the incoming telephone line and connect the modem to the panel's TIP and RING terminals (with the modem's red & green phone line wires). Press the EMERGENCY key while in Test Mode to cause the panel to connect to the modem.
AUTOMATION OUTPUT CONNECTION (OPTIONAL)

✦ The Console provides a Automation Output to
MINUS H/A TERMINAL WILL SWITCH TO GROUND WHEN AUTOMATION OUTPUT IS ACTIVATED
control lights, devices and appliances.
✦ Automation Output can connect to most popular
AC AC EXT. SPKR (-) H/A - H/A + RELAY N.O. RELAY DRY
home automation devices and other simple electronic devices (see fi gure).
✦ Press to turn the Automation Output on, press
again to turn it off.
POSITIVE H/A TERMINAL PROVIDES +12 VOLTS DC AND IS CURRENT LIMITED AT 30 MILLIAMPS MAXIMUM
✦ There are many programmable options for the
Automation Output.
✦ The Automation Output can be programmed for a
variety of useful functions, such as: fl ashing during alarm, fl ashing after an alarm, on while armed, or, on during exit/entry delays.
X-10 BURGLAR ALARM INTERFACE (CAN CONTROL HOUSE LIGHTS THROUGH X-10 SYSTEM)
LIGHT EMITTING DIODE (L.E.D.)
✦ See the “Advanced Programming” section of this
manual for details on changing the function of the Automation Output.
H/A + H/A - H/A + H/A - H/A + H/A -
Programmable Options


✦ The Console is powered by a low voltage plug-in
transformer.
AC AC EXT. SPKR (-) H/A - H/A + RELAY N.O. RELAY DRY
✦ Use up to 25 feet of 20 AWG or larger
two-conductor wire to connect the transformer to the Console.
BLOCK


PLUG TRANSFORMER INTO 115 VAC OUTLET THAT IS NOT CONTROLED BY A LIGHT SWITCH
✦ A 12-volt backup battery may be installed and is
highly recommended.
✦ The backup battery will power the Console for up to
6 hours during AC power loss.

✦ The backup battery is automatically charged by the
Console when AC power is present.
✦ A low backup battery will cause the Console POWER
indicator to fl ash as it is being charged.

CONNECT RED BATTERY LEAD TO RED TERMINAL CONNECT BLACK BATTERY LEAD TO BLACK TERMINAL
LEADS! THE BATTERY FUSE WILL BLOW.

✦ In a new installation, when power is fi rst applied
the system's master user code is “1234”.
the Console's keypad, not on a wireless remote keypad.
SETTING A NEW MASTER
SETUP
MODE
USER CODE
START IN SETUP
CLEARS KEYPAD
✴ A “gong” and four “beeps” will sound. 3. Enter the Setup Mode from Test Mode, enter 1234 then press TEST again.
✴ A “gong” and fi ve “beeps” will sound. The system is now in
Test Mode. 4. Enter 99 then press HOME.
code is recommended.
STORE CODE
MASTER USER CODE:
DONE
Setup Mode. The restricted user codes cannot. To create restricted user codes, see the “Advanced Programming” section of this manual.
✦ Each wireless sensor that is going to be used
with the Console must be programmed into the Console’s memory.
✴ A “Gong” and fi ve “Beeps” will sound. ✴ The sensor status indicators will light for any sensors
programmed into the Console. 3. Enter an unused sensor number from 01-24 (you must enter two digits, example: 5 = 05).
TEST
✴ The sensor indicator light will fl ash for the sensor number
selected. 4. Activate the sensor by sending a test or alarm signal (be sure the sensor's battery is connected or that its battery protection strip is removed).
✴ A single “Bing” tone will sound and the sensor status
indicator for that sensor will stay lit.


✦ Follow the instructions on the previous page to
select a sensor number to program the sensor into. ✎ NOTE: A sensor can be programmed into more
than one location. Be sure to choose an UNUSED sensor number. If a sensor gets entered into more than one location, delete the duplicates using the remove sensor function. ✦ To add DXS-10 wireless keypads, press and hold the
keypad's key until programmed into the Console. ✦ For DXS-31 and DXS-32 door/window sensors,
move the magnet away from the side of the sensor.
window sensors are pre-set at the factory for delayed burglary response. If the sensor is going to be used on a non-entry portal (window, sliding glass door, etc.) a jumper can be changed in the sensor to select instant response. The jumper should be changed before programming the sensor so the Console will assign the sensor to the proper sensor function. See the “Basic Sensor Installation” section of this manual or the sensor’s instructions for details on changing the jumper. ✦ For DXS-81, DXS-91, DXS-54, & DXS-73
accessory sensors, simply send a test transmission (refer to the sensor's instructions for details on sending a test transmission).
✦ For DXT-61, DXT-21, DXS-21, DXT-41, & DXS-62A
single-button remotes, simply press the unit's button. ✎ NOTE: After the Console recognizes the
transmitter, single-button remotes must be re-programmed as “panic buttons” or home automation controllers. Refer to the “Customizing the System” section of this manual. ✦ For DXT-23, DXS-23, & DXT-42 multi-button
remotes: Learn the transmitter by pressing the left button. The remote will arm the Console with the left button and disarm with the right button. Labels are provided with the DXT-42 for identifying the buttons. ✎ NOTE: After the Console “learns” the transmitter,
multi-button remotes can easily be re-programmed to have the left button arm/disarm the Console and the right button activate/deactivate the Home Automation output. Refer to the “Advanced Programming” section of this manual.
For All Models:
✴ A single “Bing” tone will sound and the sensor status
indicator will stay lit when the sensor is programmed into the Console. ✴ A “Buzz” tone will sound if there is already another sensor
programmed to that sensor number. ✦ Exit Setup Mode by pressing the key then press OFF for three seconds. Reminder: The Console will automatically exit the Setup Mode and return to Off Mode after three minutes of keypad inactivity.
memory, see the “Customizing the System” section of this manual.

✦ Each accessory sensor is packaged with its own
set of installation instructions specifi c to the model of sensor.

✦ Refer to the sensor's instructions for details on
installing, operating, and testing of the sensor.
FROM TOP OF CASE TWIST SCREWDRIVER BETWEEN CASE HALVES UNTIL IT POPS OPEN
✦ Following are basic instructions for installing two
popular DVS-2400 accessories: The Model DXS-10 Wireless Remote Keypad and the Model DXS-31 or DXS-32 Door/Window Transmitters.
✦ The DXS-10 is used to remotely command the
Console.
✦ The keypad can be simply set on a table or
mounted to a fl at surface.
✦ Four anti-mar pads are provided as a scratch
deterrent “feet” for the keypad.
is going to be wall mounted.
✦ The wireless keypad can be used as a portable
keypad. Because of the hourly supervisory transmissions, if the unit is taken out of range from the Console for more than eight hours, the Console will indicate “radio trouble” for the keypad. The keypad's sensor number can be programmed for “non-supervised” if required. See the “Advanced Programming” section of this manual.
USE THE FOUR SCRATCH DETERRENT PADS PROVIDED FOR TABLE-TOP USE

✦ The wireless keypad can be wall mounted in a
convenient location.
should be mounted at least three feet above ground level.
ATTACH REAR CASE TO WALL WITH THE TWO SCREWS PROVIDED
indoor use only.
MOUNT AT A CONVENIENT LOCATION NEAR PRIMARY ENTRY/EXIT DOOR

EXAMPLE INSTALLATION (WITH DXS-31 SHOWN)
✦ The DXS-31 and DXS-32 sensors can be used

to monitor doors, windows, cabinets, crawl space doors, gates, freezer doors, and many other moving objects that could be used for intrusion or need to be monitored.
✦ A built-in magnetic switch triggers the sensor when
its magnet (mounted on the moving part or the door or window) moves away from the sensor.
✦ The DXS-31 sensor can be wired to external
normally closed switches for remote triggering.
✦ The DXS-31 sensor can connect directly to a glass
break detector.
✦ A jumper inside the door/window sensor selects
ANTENNA
instant or delayed response.
INPUT SELECT JUMPER
TWO TYPE 2032 BATTERIES
1A. If the sensor is going to be used on the primary entry/exit door make sure that the jumper is in the DELAY position.
TRANSMIT INDICATOR
1B. If the sensor is going to be used on a window or a door that is not going to be used to enter and exit the premises, set the jumper to the INSTANT position.
TEST SWITCH
EXTERNAL INPUT TERMINALS
CHOOSE MOUNTING METHOD
INSTANT/DELAY OPTION JUMPER
2A. Apply double-stick tape (supplied) to back of sensors and magnets.
2B. Screws are also provided to mount sensors and magnets. Screws are preferred over the double-stick tape in permanent installations.
installations.
✦ Allow a maximum of 1/2" between magnet and
ATTACH MOUNTING PLATES USING THE SCREWS OR DOUBLE-STICK TAPE PROVIDED
sensor when door/window is closed.
✦ The magnet height is adjustable and an optional
magnet spacer is provided for uneven surfaces.
3B. On doors, mount sensor to door frame and magnet to door.
3B. On windows, mount sensor to window frame and magnet to window.
case both horizontally & vertically.
✴ In Chime Mode, the Console should “ding-dong” when the

sensor sends a signal.
✴ Verify that light on the sensor (if there is one) glows
momentarily when door/window is opened.
✴ Status indicator on the Console should remain lit for each
door/window sensor that is left open.


✦ The Console can be customized for the specifi c
✦ A label sheet with sensor location names is
identifi cation of where a door or window is open, where any alarms have occurred, where a sensor with a low battery is, or where a sensor with trouble is.

OPEN DOOR OR WINDOW TO LIGHT SENSOR STATUS INDICATOR ON CONSOLE
APPLY SENSOR IDENTIFICATION LABELS TO THE APPROPRIATE SENSOR LOCATIONS


✦ Use this mode to disarm the burglary portion of the
system.
✦ Switching to Off Mode stops any alarms in
progress.
✦ The 24-hour functions are still active in Off Mode
and can be triggered by pressing the FIRE or EMERGENCY button.
✴ When the system is disarmed to Off Mode, the Console will
sound one “Gong”.
✴ If an alarm has occurred, multiple Beeps will sound after
disarming and the sensor indicator for the sensor(s) that caused the alarm will fl ash.
cannot trigger the burglary alarm.
OFF
DONE
CHIME MODE
CHIME MODE
START HERE
✦ Chime Mode is for monitoring entries and exits
without causing alarms.
✦ Use Chime Mode as an “automatic door chime”
when at home.
✴ Opening any protected door or window causes the Console
to sound a “ding-dong”.
1A. Select the Chime Mode by entering a user code, then press CHIME.
1B. The user can enter Chime Mode from Off Mode by pressing CHIME for two seconds.
✴ When the system is switched to the Chime Mode, the
keypad(s) will sound a “Gong” and one “Beep”.
✦ Switching to Chime Mode disarms the system
and stops any alarms in progress.
✴ If an alarm has occurred, multiple Beeps will sound after
disarming and the sensor indicator for the sensor(s) that caused the alarm will fl ash.
HOLD DOWN
windows cannot trigger the burglary alarm.
DONE

MANUAL BYPASSING OF SENSORS
✦ Use this mode when sleeping or when anyone is
✦ Manual bypassing of sensors in the Home Mode
staying inside.
allows arming of the system at night with open windows, while still having perimeter protection with other closed doors and windows.
✦ Home Mode causes an instant alarm when any
perimeter sensor is triggered.
✦ Home Mode causes a delayed alarm when any exit/
entry sensor is triggered (except in Home Instant Mode when they are instant).
✴ Four high-low Beeps to warn the user that something is
open and the system will remain in the previous mode.
✦ Alarm siren stops automatically after fi ve minutes
and the system will remain armed.
✴ Lit sensor status indicators show which sensors are open.
✦ Home Mode ignores all interior sensors (motion
detectors, etc.).
1A. Arm to Home Mode by entering a user code, and pressing HOME.
✴ A “Gong” and two “Beeps” will sound, the HOME indicator
will light, and the open sensors will be bypassed.
1B. The user can “Quick Arm” to Home Mode from Off or Chime Mode by pressing HOME for two seconds. (Quick arming can be disabled; see the “Advanced Programming” section of this manual.)
alarm. Closing the sensor removes the bypass.
✴ When the system is armed to the Home Mode, the
keypad(s) will sound a “Gong” and two “Beeps”.
✴ If an alarm has occurred, multiple Beeps will sound after
disarming and the sensor indicator for the sensor(s) that caused the alarm will fl ash (switch to Off Mode again or re-arm the system to stop the fl ashing alarm memory light).
HOME MODE
SECURE EXIT
START IN HOME MODE
(OPTIONAL)
(OPTIONAL)
✴ The HOME light will blink for 60 seconds. No exit delay
Beeps will sound during the Exit Delay.
2A. The user can leave through a door with a delayed perimeter sensor during the 60 second Exit Delay without causing the Console to begin an Entry Delay.
YOUR USER CODE
2B. Re-entering during the silent Exit Delay will extend the Exit Delay another 60 seconds (one time only).
1 GONG & 2 BEEPS
“Advanced Programming” section of this manual.
DONE
DONE
✴ Two “Gongs” and two “Beeps” will sound and the HOME
light will blink continuously.
MODE
START IN OFF OR CHIME MODE
HOLD DOWN HOME
HOLD DOWN
1 GONG & 2 BEEPS
2 GONGS & 2 BEEPS
Mode is unavailable.
DONE

MANUAL BYPASSING OF SENSORS
✦ Use this mode when no one will be staying home.
✦ Manual bypassing of sensors in the Away Mode
✦ Each burglary sensor can trigger the siren once per
allows arming of the system with open doors and windows, while still having perimeter protection with other closed doors and windows.
arming period.
✦ Away Mode causes an instant alarm when any
perimeter sensor is triggered.
✦ Away Mode causes a delayed alarm when any
✴ Four high-low Beeps to warn the user that something is
exit/entry sensor is triggered.
open and the system will remain in the previous mode.
✦ Away Mode causes an instant alarm when any
✴ Lit sensor status indicators show which sensors are open.
interior sensors (motion detectors, etc.) are triggered. The interior sensors will be delayed if a perimeter delayed sensor is triggered fi rst.
✦ Alarm siren stops automatically after fi ve minutes
✴ A “Gong” and three “Beeps” will sound, the AWAY indicator
and the system will remain armed.
will light, and the open sensors will be bypassed.
1A. Arm to Away Mode by entering a user code, and pressing AWAY.
alarm. Closing the sensor removes the bypass.
1B. The user can “Quick Arm” to Away Mode from Home, Chime or Off Mode by pressing AWAY for two seconds. (Quick arming can be disabled; see the “Advanced Programming” section of this manual.)
EXIT DELAY (For Leaving the Premises)
✴ When the system is armed to the Away Mode, the Console
will sound a “Gong” and three “Beeps”.
✴ During the 60 second Exit Delay, the Console will sound
“Beeps” (double Beeps last 10 seconds) and the AWAY light will blink.
2A. The Exit Delay gives the user 60 seconds to leave the premises through an exit/entry door without triggering an alarm.
2B. Re-entering during the Exit Delay will extend the Exit Delay another 60 seconds (one time only).
✴ When the Exit Delay is over, the Console will sound one
“Gong” to warn the user that the system is fully armed.
“Advanced Programming” section of this manual.
ENTRY DELAY (For Entering the Premises) 3A. The Entry Delay gives the user 30 seconds to enter the premises through an exit/entry door without triggering an alarm.
3B. If a exit/entry sensor is triggered, starting the Entry Delay, the interior sensors will also become delayed (this allows motion in the premises during the Entry Delay).
✴ During the 30 second Entry Delay, the Console will sound
“Beeps”.
HOLD DOWN
✴ If an alarm has occurred while the user was gone, multiple
Beeps will sound after disarming and the sensor light for the sensor(s) that caused the alarm will fl ash (switch to Off Mode again or re-arm the Console to stop the fl ashing alarm memory light).
“Advanced Programming” section of this manual.

Mode, it will automatically switch back to Off Mode after three minutes.
✦ Even though this is a self-monitoring supervised
system, the National Burglar and Fire Alarm Association recommends that all security systems should be tested manually on a regular basis.
✦ When directly connecting (without a telephone
line) to the DVS-2400 with the RA-2400 remote access software (Version 1.3 or later), press the EMERGENCY key while in Test Mode to cause the Console to connect to the modem.
✴ When the system is switched to the Test Mode, the Console
will sound a “Gong” and four “Beeps”.

✴ The sensor status indicators will fl ash for each sensor
programmed into the Console.
✴ The Console will make a “Bing” sound as each sensor is
tested, followed by 1-3 beeps indicating signal strength with 3 beeps being the strongest signal.
✴ As each sensor is tested, the sensor status indicator for the
sensor will stop fl ashing and return to showing the current status of the sensor.

SENSOR TYPE OFF MODE CHIME MODE HOME MODE AWAY MODE
2-BUTTON ARM/DISARM (LEFT) 2-BUTTON AUTOMATION (RIGHT) EMERGENCY (BOTH BUTTONS)
LEFT BUTTON SWITCHES SYSTEM TO AWAY MODE † IF ALARM MEMORY IS ACTIVE, SWITCHES SYSTEM TO OFF MODE ‡ LEFT BUTTON SWITCHES SYSTEM TO OFF MODE ‡
2-BUTTON ARM (LEFT) 2-BUTTON DISARM (RIGHT) EMERGENCY (BOTH BUTTONS)
LEFT BUTTON SWITCHES SYSTEM TO AWAY MODE † IF ALARM MEMORY IS ACTIVE, SWITCHES SYSTEM TO OFF MODE ‡ RIGHT BUTTON SWITCHES SYSTEM TO OFF MODE ‡
† CAN BE HOME MODE USING PROGRAMMING STEP 50
‡ CAN BE CHIME MODE USING PROGRAMMING STEP 51 Console Zone Table

✦ The DVS-2400 Console is a self-monitoring
supervised wireless system.
✦ If the Console detects a problem with any of the
supervised system sensors or with its power, it will display the appropriate trouble indication and, if monitored, report the trouble to the Central Station through the communicator (depending on communicator programming).
✦ The Console constantly charges and monitors the
optional backup battery (if installed).

✦ If the backup battery condition is abnormal, the
Console's POWER light will indicate the trouble.
✴ The POWER indicator normally glows when AC power is on.
✴ With a charged backup battery installed, if the Console
DIM WHEN AC POWER IS ABSENT AND CONSOLE IS RUNNING ON BACKUP BATTERY
looses AC power, the POWER indicator will dim as the Console runs on the backup battery.
✴ If the backup battery is low, recharging, or not installed, the
POWER indicator blinks when AC power is present.
✴ If the AC power is off and no backup battery is installed, the
POWER indicator will be off (in this case, the system has no power and is disabled).
✦ Normal battery life for the type of backup battery
used in the Console is 3-4 years. If the battery does not take a charge in 72 hours, it should be replaced.
✴ If the BATTERIES indicator on the Console blinks, one or
more sensors have a low battery.
BLINKS WHEN ONE OR MORE SENSORS HAVE A LOW BATTERY
LIGHTS WITH SENSOR INDICATOR DURING LOW BATTERY STATUS CHECK (PRESS FOR 1 SECOND)
✴ When the TROUBLE indicator blinks, one or more sensors
have not reported status during the eight hour status time window.
BLINKS WHEN ONE OR MORE SENSORS HAVE NOT REPORTED STATUS DURING THE EIGHT HOUR STATUS TIME WINDOW
LIGHTS WITH SENSOR INDICATOR DURING TRANSMITTER STATUS CHECK (PRESS FOR 1 SECOND)

✦ Adding additional sensors will increase the
protection provided by the system.
✦ All ground-level perimeter openings and accessible
upper-story openings need protection.
✦ Motion detectors can protect interior areas and
areas where valuables are kept.
✴ A “Gong” and fi ve “Beeps” will sound.
✴ The sensor status indicators will light for each sensor
programmed into the Console.
than one location. Be sure to choose an UNUSED sensor number. If a sensor gets entered into more than one location, delete the duplicates using the remove sensor function.
TEST
✴ The sensor status indicator light will fl ash for the sensor
number selected.
✴ A “Bing” tone will sound when the sensor is programmed
into the Console and the sensor status indicator will stay lit.
✴ A “Buzz” tone will sound if there is already another sensor
programmed to that sensor number.
✦ If a previously programmed sensor isn't going to be
used with the system anymore, or it's a duplicate that has been entered into more than one sensor location, it should be removed from the Console's memory.
✴ A “Gong” and fi ve “Beeps” will sound.
✴ The sensor status indicators will light for each sensor
programmed into the Console.
✴ The sensor status indicator light will fl ash for the sensor
number selected.
✴ A “Bing” tone will sound when the sensor has been removed
and the sensor status indicator will turn off.

START IN TEST
✦ Sensors can be programmed to cause the Console
to chime any time they're activated.
✦ Chime-only sensors will not be able to trigger the
alarm in any Console mode.
✦ The sensor must have already been programmed
into the Console (see “Adding Sensors to the System” for details).
TEST
✴ A “Gong” and fi ve “Beeps” will sound.
✴ The sensor status indicators will light for each sensor
programmed into the Console.
✴ The sensor status indicator light will fl ash for the sensor
number selected.
✴ A “Bing” tone will sound and the sensor status indicator will
light steady.
DONE
MAKING A SENSOR INTERIOR
✦ Wireless motion detectors are automatically
programmed as interior sensors. Any other sensor can also be programmed as an interior sensor.
✦ Interior sensors can only trigger an alarm when the
Console is in the Away Mode.
✦ “Home Interior” sensors can trigger an alarm when
the Console is in the Home or Away mode.
✦ The sensor must have already been programmed
into the Console (see “Adding Sensors to the System” for details).
TEST
✴ A “Gong” and fi ve “Beeps” will sound.
✴ The sensor status indicators will light for each sensor
programmed into the Console.
✴ The sensor status indicator light will fl ash for the sensor
number selected.
7 PRS
✴ A “Bing” tone will sound and the sensor status indicator will
light steady.

✦ Sensors can be reprogrammed to perform different

sensor functions.
✦ The sensor must have already been programmed
into the Console (see “Adding sensors to the System” for details).
✴ A “Gong” and fi ve “Beeps” will sound.
✴ The sensor status indicators will light for each sensor
programmed into the Console.
✴ The sensor status indicator light will fl ash for the sensor
number selected.
✴ A “Bing” tone will sound and the sensor status indicator will
light steady.

FUNC- TION # SENSOR FUNCTION OFF MODE CHIME MODE HOME MODE AWAY MODE
3 PANIC ARMED 24-HOURS - TRIGGERS SILENT PANIC ALARM
INSTANT BURGLARY ALARM UNLESS ACTIVATED DURING AN ENTRY DELAY, THEN IT IS
9 2-BUTTON ARM/DISARM (LEFT) 2-BUTTON AUTOMATION (RIGHT) EMERGENCY (BOTH BUTTONS)
LEFT BUTTON SWITCHES SYSTEM TO AWAY MODE † IF ALARM MEMORY IS ACTIVE, SWITCHES SYSTEM TO OFF MODE ‡ LEFT BUTTON SWITCHES SYSTEM TO OFF MODE ‡
10 2-BUTTON ARM (LEFT) 2-BUTTON DISARM (RIGHT) EMERGENCY (BOTH BUTTONS)
LEFT BUTTON SWITCHES SYSTEM TO AWAY MODE † IF ALARM MEMORY IS ACTIVE, SWITCHES SYSTEM TO OFF MODE ‡ RIGHT BUTTON SWITCHES SYSTEM TO OFF MODE ‡
SENSOR FUNCTION TABLE † CAN BE HOME MODE USING PROGRAMMING STEP 50
‡ CAN BE CHIME MODE USING PROGRAMMING STEP 51

✦ To perform any of the advanced programming
steps, the Console must be in the Setup Mode.
✦ Each programming function is performed with
similar keystrokes. After the Console is in Setup Mode, enter the programming step number, press HOME, then enter the new value and press AWAY. For reference, follow the fi gures next to the programming steps.
put the system into the Setup Mode. The restricted user codes cannot access Setup Mode, only Code Mode.
✴ If the new value is accepted, a “bing” will sound. If the new
value is not accepted, a “double buzz” will sound.
✴ A “Gong” and fi ve “Beeps” will sound, signaling that the
system is in Setup Mode.

Mode, it will automatically switch back to Off Mode after three minutes.
STEP # PROGRAMMING FUNCTIONS POSSIBLE VALUES FACTORY VALUE INSTALLATION VALUE
26 EXIT DELAY 20-255 SECONDS 60
30 BURGLARY SIREN TIME 1-30 MINUTES 5
31 EMERGENCY SIREN TIME 1-30 MINUTES 5
32 FIRE SIREN TIME 1-30 MINUTES 5
40 AUTOMATION OUTPUT TIME 0-2500 SECONDS (0 = TOGGLE ON/OFF) 0
50 REMOTE ARMING MODE 2 = HOME MODE; 3 = AWAY MODE 3
51 REMOTE DISARMING MODE 0 = OFF MODE; 1 = CHIME MODE 0
61 ENTRY DELAY BEEPS 0 = OFF; 1 = ON 1
62 EXIT DELAY BEEPS 0 = OFF; 1 = ON 1
63 SILENT BURGLARY ALARM 0 = AUDIBLE; 1 = SILENT 0
64 SILENT EMERGENCY ALARM 0 = AUDIBLE; 1 = SILENT 0
65 QUICK ARMING 0 = OFF; 1 = ON 1
66 AUTO RESTORE 0 = OFF; 1 = ON 1
67 AUTO BYPASS 0 = OFF; 1 = ON 0
68 AUTOMATION MODE DURING ALARM 0 = FLASH (ENABLED BY FUNCTION 72) 1 = STEADY (ENABLED BY FUNCTION 72) 0
69 AUTOMATION BING TOME 0 = NO BINGS 1 = BINGS 1
70 REMOTE ARM/DISARM CHIRP 0 = NO CHIRPS 1 = CHIRPS (1 CHIRP = ARMED, 2 CHIRPS = DISARMED) 1
71 AUTOMATION FLASHES AFTER ALARM 0 = STANDARD 1 = FLASHING AFTER ALARM 0
0 = STANDARD 1 = AUTOMATION ACTIVE DURING ALARM (FLASH OR STEADY PROGRAMMED BY FUNCTION 68)
73 AUTOMATION ON WHILE ARMED 0 = STANDARD 1 = ON WHILE ARMED 0
74 AUTOMATION ON DURING EXIT/ENTRY 0 = STANDARD 1 = ON DURING EXIT/ENTRY DELAY 0
75 AUTOMATION POLARITY 0 = + WHEN OFF; 1 = + WHEN ON 1
92 DURESS CODE 1-5 DIGITS REMOVED
93 RESTRICTED USER CODE #1 1-5 DIGITS REMOVED
94 RESTRICTED USER CODE #2 1-5 DIGITS REMOVED
95 RESTRICTED USER CODE #3 1-5 DIGITS REMOVED
96 RESTRICTED USER CODE #4 1-5 DIGITS REMOVED
97 RESTRICTED USER CODE #5 1-5 DIGITS REMOVED
98 PAGE ALERT USER CODE 1-5 DIGITS REMOVED
99 MASTER USER CODE 1-5 DIGITS 1234
Console Programming Table

✦ When a sensor is programmed, the Console
automatically recognizes it as supervised or non-supervised.
✦ The Console expects hourly status transmissions
from any sensor programmed as supervised.
✦ Any sensor can be programmed as supervised or
non-supervised.
status transmissions as supervised.
✦ When a sensor is programmed, the Console
automatically recognizes it as manual or automatic restoring.
✦ The Console expects restoral signals from any
wireless sensor programmed as manual restore.
✦ Any sensor can be programmed as manual or
automatic restore.
restoral transmissions as manual restore.
✦ The factory-set Entry Delay time is 30 seconds.
STEP #25 The Entry Delay time can be adjusted from 20 to
255 seconds using this step.
❑ Write the new Entry Delay time in the User's Guide.
user may not have enough time to disarm the system before an alarm.
✦ The factory-set Exit Delay time is 60 seconds.
STEP #26 The Exit Delay time can be adjusted from 20 to 255
seconds using this step.
❑ Write the new Exit Delay time in the User's Guide.
BURGLARY SIREN TIME
✦ The factory-set burglary siren time is fi ve minutes
PROGRAMMING STEP #30
(UL installation maximum).
STEP #30 The burglary siren time can be adjusted from one to
30 minutes using this step.
EMERGENCY SIREN TIME
3 DEF
✦ The factory-set emergency siren time is fi ve
minutes (UL installation maximum).
STEP #31 The emergency siren time can be adjusted from
one to 30 minutes using this step.

3 DEF
✦ The factory-set fi re siren time is fi ve minutes (UL
installation maximum).
STEP #32 The fi re siren time can be adjusted from one to 30
minutes using this step.
AUTOMATION OUTPUT TIME
✦ The factory setting causes the Automation Output
PROGRAMMING STEP #40
to toggle between on and off with each activation.
STEP #40 The Automation Output can be programmed to turn
on, then automatically turn off after one to 2500 seconds (42 minutes), or toggle on & off, using this step.
TIME IN SECONDS (1-2500) 0 = TOGGLE ON & OFF
✦ The factory setting causes the portable remote
controls to arm to the Away Mode.
STEP #50 The portable remote controls can be changed to
arm to the Home Mode using this step.
portable remote controls used with the system.
✦ The factory setting causes the portable remote
controls to disarm to the Off Mode.
STEP #51 The remote controls can be changed to disarm to
the Chime Mode using this step.
portable remote controls used with the system.
✦ The factory setting causes the Console to beep
PROGRAMMING STEP #61
during Entry Delays.
STEP #61 The Entry Delay beeps can be silenced using this
step.
0 FOR ENTRY BEEPS OFF 1 FOR ENTRY BEEPS ON
✦ With the Entry Delay beeps off, the Console will be
silent after a delayed sensor is triggered until the Entry Delay expires, then the alarm siren will sound.
✦ The factory setting causes the Console to beep
during Exit Delays.
2 ABC
STEP #62 The Exit Delay beeps can be silenced using this
step.
0 FOR EXIT BEEPS OFF 1 FOR EXIT BEEPS ON
✦ With the Exit Delay beeps off, the Console will be
silent after arming to the Away Mode until the Exit Delay expires, then a single “Gong” tone will sound.

✦ The factory setting causes audible burglary alarms.
STEP #63 The Console can be programmed for silent burglary
3 DEF
alarms using this step.
SILENT EMERGENCY ALARMS
✦ The factory setting causes audible emergency
alarms.
4 GHI
STEP #64 The Console can be programmed for silent
emergency alarms using this step.
DISABLING QUICK ARMING
✦ The factory setting allows quick arming of the
Console by pressing down the mode keys for two seconds.
PROGRAMMING STEP #65
STEP #65 The Console can be programmed to not allow quick
arming using this step. If quick arming is disabled, a user code must be entered before pressing the mode buttons.
0 FOR QUICK ARMING OFF 1 FOR QUICK ARMING ON
traffi c, it is recommended to disable quick arming to prevent customers from arming the system. ✎ NOTE: If quick arming is disabled the Home Instant
Mode is unavailable.
✦ Bypassed sensors are ignored by the Console and
cannot cause an alarm.
✦ The factory setting causes the Console to
automatically restore (remove the bypass from) sensors that close. After it's restored, the sensor is ready to cause an alarm the next time it is opened.
6 MNO
STEP #66 The Console can be programmed to not
0 FOR AUTO RESTORAL OFF 1 FOR AUTO RESTORAL ON
automatically restore any bypassed sensor when the sensor closes using this step. Bypassed sensors will then remain bypassed until the system is disarmed.
✎ NOTE: This setting affects all sensors.
✦ The factory setting requires the user to manually
bypass any open sensors when the system is armed.
PROGRAMMING STEP #67
✴ If arming is attempted with open sensors, the Console will
sound fi ve two-tone Beeps and will not arm.
✦ Arming to the same mode again within fi ve seconds
0 FOR AUTO BYPASS OFF 1 FOR AUTO BYPASS ON
will bypass any open sensors and arm the Console.
STEP #67 The Console can be programmed to automatically
bypass any open sensors when the system is armed using this step.
✎ NOTE: This setting affects all sensors.

✦ The factory setting causes the Automation Output
to fl ash if it is programmed to activate during or after an alarm.
8 TUV
during or after an alarm, that function must be enabled with Programming Step 71 or 72. STEP #68 The output can be programmed to be a steady
0 FOR FLASHING OUTPUT ON ALARM 1 FOR STEADY OUTPUT ON ALARM
output using this step.
✦ The factory setting causes the Console to sound a
“Bing” when the Automation Output is activated by pressing the key, or when it's triggered with a two-button remote control.
9 WXY
STEP #69 This sound can be silenced using this step.
0 FOR BING TONE OFF 1 FOR BING TONE ON
✦ When arming with the portable remote control, the
factory setting causes the Console to “chirp” once when armed, twice when disarmed, and three times when arming with sensors bypassed.
PROGRAMMING STEP #70
STEP #70 These chirps can be silenced using this step.
recommended to program the Automation Output to be active when the system is armed, so a light can be triggered displaying the arming status of the Console.
✦ The factory setting causes the Console's
Automation Output to activate when pressing the
key, or when it's triggered with a two-button remote control.
STEP #71 The Console can be programmed to activate the
0 FOR STANDARD TRIGGER 1 FOR FLASHING DURING & AFTER ALARM
Automation Output during and after any alarms as well as when normally triggered using this step.
sensor status lights are cleared.
✦ The factory setting causes the Console's
Automation Output to activate when pressing the
PROGRAMMING STEP #72
key, or when it's triggered with a two-button remote control.
STEP #72 The Console can be programmed to activate the
0 FOR STANDARD TRIGGER 1 FOR OUTPUT DURING ALARM
Automation Output during alarms as well as when normally triggered using this step.
to fl ash or be steady during alarm, see Programming Step 68.

✦ The factory setting causes the Console's
Automation Output to activate when pressing the
3 DEF
key, or when it's triggered with a two-button remote control.
STEP #73 The Console can be programmed to activate the
0 FOR STANDARD TRIGGER 1 FOR OUTPUT WHEN ARMED
Automation Output when the system is armed as well as when normally triggered using this step.
✦ The factory setting causes the Console's
Automation Output to activate when pressing the
4 GHI
key, or when it's triggered with a two-button remote control.
0 FOR STANDARD TRIGGER 1 FOR OUTPUT DURING EXIT/ENTRY DELAYS
STEP #74 The Console can be programmed to activate the
Automation Output during the exit and Entry Delays as well as when normally triggered using this step.
✦ The factory setting causes the Console's
Automation Output to provide a current limited voltage source when activated.
5 JKL
STEP #75 The Console can be programmed so the
Automation Output provides a current limited voltage source when deactivated using this step.
0 FOR VOLTAGE WHEN OFF 1 FOR VOLTAGE WHEN ON
✦ This password is used to gain access to the Console
PROGRAMMING STEP #87
when using the RA-2400 remote access software. The password must be 6-digits long.
STEP #87 Use this step to enter a new remote access
password then log the password in the box below.
REMOTE ACCESS PASSWORD:
DURESS CODE
9 WXY
✦ The duress code will disarm the system, without
2 ABC
any special indications or sounds, but will send the programmed duress code to the Central Station. The code should be two or more digits different than any user code
STEP #92 Use this step to enter the duress code then log the
code in the box below.
MASTER USER CODE
✦ The master user code is 1234 when power is fi rst
PROGRAMMING STEP #99
applied to the Console.
✦ The master user code can be changed to any 1-5
digit code. Only the master user can access Setup Mode, restricted users cannot.
recommended. STEP #99 Use this step to enter the new master user code
then log the code in the box below.

PROGRAMMING STEPS #93 TO 98
✦ The Console can be programmed with fi ve restricted
user codes and one page alert user code.
✦ The restricted user codes operate the system as
usual, but cannot access Setup Mode.
✦ The restricted user codes can access a special
Code Mode that can be used to change or remove any of the fi ve restricted user codes, the page alert user code, or the duress code.
✦ The page alert user code dials the supervisory
number (programmed for a pager) when it is used to arm or disarm the system.
STEP #93 RESTRICTED USER CODE #1
STEP #94 RESTRICTED USER CODE #2
✦ A restricted user code is appropriate to give any
user that should be restricted from programming the Console.
USER CODE THE SAME AS THE MASTER USER CODE! STEPS #93-98 Create any additional user codes using these
steps then log the codes in the boxes to the right.
KEYPAD CODE PROGRAMMING STEPS #92 TO 98
STEPS #93-98 Any additional user code can be removed
from the Console by entering the appropriate step number and pressing TEST. ✦ Because access to programming would be impossible
REMOVE
without a master user code, it cannot be removed using these steps. The master user code can be changed using programming STEP #99. ✎ NOTE: The master user code can be set to the
factory default using the Console master reset programming step, although all other system programming will be reset to factory values and all sensors programmed will be erased.
START IN TEST
✦ Master resetting the Console will set all of the
programming options back to the factory values. The master user code will be reset to 1234.
user codes and remove all programmed sensors. All Console and communicator programming values will be reset to the factory defaults. 1. Start with the system in Test Mode (Setup Mode cannot be reached from any other mode).
TEST
9 WXY
STEP #999 FOR MASTER RESET
USE THESE EXACT KEYSTROKES TO PERFORM A MASTER RESET
✴ A “Gong” and fi ve “Beeps” will sound, signaling that the
system is in Setup Mode. 3. Enter programming STEP #999 then press TEST.
TEST
✴ A “Bing” will sound to indicate the beginning of the reset
process. This process will take up to 10 seconds while the memory is being reset. ✦ The system will revert to the fi rst time power-up
9 WXY
condition and the new master user code will be 1234. Go to the “Basic Console Programming” section of this manual to begin re-programming the system.
PRESS TEST, 1 BING SOUNDS, WAIT ABOUT 10 SECONDS
DONE

✦ To perform any of the communicator programming
steps, the Console must be in the Setup Mode.
✦ Each programming function is performed with
similar keystrokes. After the Console is in Setup Mode, enter the programming step number and press HOME, then enter the new value and press AWAY. For reference, follow the fi gures next to the programming steps.
✴ If the new value is accepted, a “Bing” will sound. If the new
value is not accepted, a “Double Buzz” will sound.
SETUP MODE
to put the Console into the Setup Mode. The restricted user codes cannot access Setup Mode, only Code Mode.
✴ A “Gong” and fi ve “Beeps” will sound, signaling that the
system is in Setup Mode.
Mode, it will automatically switch back to Off Mode after three minutes.
STEP # PROGRAMMING
POSSIBLE
FACTORY
INSTALLATION
FUNCTION
VALUES
VALUE
VALUE
76 2-WAY AUDIO 0= NONE; 1 = LISTEN; 2 = 2-WAY MANUAL; 3 = 2-WAY FULL DUPLEX 0
78 VOICE RESPONSE FROM KEYPAD SPEAKER 0 = VOICE RESPONSE DISABLED 1 = VOICE RESPONSE ENABLED 0
100 REMOTE PROGRAMMING LOCKOUT 0 = UNLOCK; 1 = LOCK 0
101 CALL LIMITER 0 = OFF; 1 = FIVE CALLS PER ARMING PERIOD 0
103 DIALING DELAY 0 = NO DELAY; 1 = 30 SECOND DELAY 0
104 DIALING METHOD 0 = TONE; 1 = PULSE 0
107 COMMUNICATOR ENABLE 0 = COMMUNICATOR OFF; 1 = COMMUNICATOR ON 0
General Communicator Programming Table

COMMUNICATOR ENABLE
✦ The factory setting for the Console disables
the communicator. If the system is going to be a non-monitored, local alarm only, leave the communicator disabled.
7 PRS
STEP #107 If the system is going to be monitored by a
Central Station, enable the communicator with this programming step.
2-WAY AUDIO ✦ When the Model VB-2 voice module is installed, the
PROGRAMMING STEP #76
communicator can provide 2-way audio capability.
✦ The audio module can be programmed for
listen-only, 2-way manual operation (using a pushbutton telephone at the Central Station), and 2-way full duplex hands free operation.
0 FOR NO AUDIO MONITORING 1 FOR LISTEN-ONLY 2 FOR 2-WAY MANUAL 3 FOR 2-WAY FULL DUPLEX
✦ Refer to the VB-2 installation instructions for details
on operating the audio module.
module must be installed for this option to function. ✦ The factory setting for the VB-2 audio module is OFF.
STEP #76 The audio module can be set for (1) listen-only, (2)
2-way manual, (3) 2-way full duplex using this step.
the system is disarmed with the duress code. ✎ NOTE:Units programmed for two-way duplex can
still be controlled manually by pressing the “1” or “3” key. In addition, the Central Station can return the unit to two-way duplex by pressing the “8” key.
✦ The Console can be programmed to allow the
speaker to play audio produced by the VB-2 digital voice response module.
✦ This selection can also be used when a remote
PROGRAMMING STEP #78
speaker is connected to the Console.
✦ The factory setting is to disable the speaker from
playing voice module audio.
STEP #78 The Console can be programmed to enable voice
0 FOR NO VOICE RESPONSE 1 FOR VOICE RESPONSE
module audio using this step.
programming step will only effect the audio produced by the voice module. It will not stop the Console’s speaker from sounding local sirens and tones. ✎ NOTE: A Model VB-2 digital voice response module
must be installed for this option to function.
✦ The factory setting for the communicator allows
remote connection to the Console with Linear's RA-2400 Remote Access Software and a modem (unlocked).
STEP #100 The Console can be programmed to not answer
incoming calls, thereby, not allowing remote access (locked) using this step.

✦ The factory setting for the call limiter is OFF. This
allows the communicator to report burglary alarms, once for each sensor, as many times as they are triggered.
STEP #101 The Console can be programmed to only allow fi ve
burglary reports total per arming period using this step.
0 FOR OFF (UNLIMITED) 1 FOR ON (5 VIOLATIONS)
(Emergency, Panic, Fire) always send a Central Station report and always sound the local siren regardless of the Call Limiter setting.
✦ The factory setting will cause the communicator to
dial the Central Station instantly when an alarm or supervisory event occurs.
3 DEF
STEP #103 The communicator can be programmed to wait 30
seconds before dialing using this step. This gives the user time to disarm the system and prevent communications in the case of a subscriber generated false alarm.
0 FOR NO DELAY 1 FOR 15 SECOND DELAY
✦ The factory setting causes the communicator to
dial using DTMF (dual-tone multi-frequency) tone dialing.
STEP #104 The communicator can be programmed to use
pulse (rotary) dialing using this step. Use this option if the telephone line in the installation does not support tone dialing.


report using the 4 BY 2 FORMAT. This format allows four-digit account numbers from 0000 to 9999 and provides two-digit alarm codes.
STEP #105 ADEMCO CONTACT ID can be chosen as a reporting
format using this step. This format allows 4-digit account numbers from 0000 to 9999 and provides verbose report descriptions with Ademco Contact ID compatible Central Stations.
0 FOR 4 BY 2 1 FOR ADEMCO CONTACT ID
✦ The communicator can be programmed with three
telephone numbers; primary, secondary, and supervisory.
PROGRAMMING STEP #86
✦ The factory setting for the communicator is to
route all calls to the primary telephone number. If communication is unsuccessful after fi ve attempts to the primary number, the secondary number will be dialed for an additional fi ve attempts. If the secondary number cannot be reached, the communicator will “sleep” for fi ve minutes before starting the call process over again. A total of four sleep cycles (50 call attempts) can occur before the communicator stops calling.
0 FOR ALL TO PRIMARY/SECONDARY 1 FOR ALARMS ONLY TO PRIMARY/SECONDARY
STEP #86 The communicator can be programmed to report
supervisory events (low battery, trouble, AC failure, etc.) to the supervisory telephone number instead of the primary or secondary telephone numbers using this step.
is going to be used, the supervisory number is reserved for the pager number. DO NOT SET THE CALL ROUTING OPTION TO “1”.
routing option to “1” and remove the supervisory telephone number.
telephone numbers the same. See the FCC Telephone Rules and Regulations on the rear cover of this manual.
STEP
PROGRAMMING
POSSIBLE
FACTORY
INSTALLATION
FUNCTION
VALUES
VALUE
VALUE
0 = ALL CALLS TO PRIMARY OR SECONDARY NUMBER 1 = ALL ALARM CALLS TO PRIMARY OR SECONDARY NUMBER AND ALL OTHERS TO SUPERVISORY NUMBER
88 ACCOUNT NUMBER 4 DIGITS EMPTY
89 PRIMARY PHONE NUMBER UP TO 20 DIGITS EMPTY
90 SECONDARY PHONE NUMBER UP TO 20 DIGITS EMPTY
91 SUPERVISORY/PAGER PHONE NUMBER UP TO 20 DIGITS EMPTY
PRESSING THE (A) KEY INSERTS A 1-SECOND DELAY THE [FIRE] KEY INSERTS A 5-SECOND DELAY FOR ALL PHONE NUMBERS ⇒ ⇒ ⇒ THE [CHIME] KEY INSERTS A “*” THE (A) KEY INSERTS A “#” IF IT IS THE LAST DIGIT OF THE PHONE NUMBER
105 REPORTING FORMAT 0 = 4 BY 2; 1 = ADEMCO 0
108 REPORT SYSTEM TROUBLE 0 = NO; 1 = YES 0
110 REPORT FORCE ARMING 0 = NO; 1 = YES 0
111 OPEN/CLOSE 0 = NO; 1 = YES; 2 = MASTER PAC ONLY 0
113 POINT ID REPORTING FOR 4 BY 2 FORMAT 0 = NO; 1 = YES 1
Communicator Reporting Option Table
#

✦ The account number entered for the communicator
must be 4-digits long.
8 TUV
✦ The factory setting for the account number is 0000.
STEP #88 Enter an account number from 0000 to 9999 using
this step.
✦ The primary Central Station telephone number can
be up to 20-digits long.
9 WXY
✦ Digits 0-9 can be used.
✦ Delays and special characters can be entered in the
telephone number (see below).
STEP #89 Enter the primary telephone number using this step.
✦ The secondary Central Station telephone number
can be up to 20-digits long.
PROGRAMMING STEP #90
✦ Digits 0-9 can be used.
✦ Delays and special characters can be entered in the
telephone number (see below).
STEP #90 Enter the secondary telephone number using this
step.
number, enter step number 90 then press TEST.
✦ The supervisory Central Station or pager telephone
number can be up to 20-digits long.
✦ Digits 0-9 can be used.
✦ Delays and special characters can be entered in
the telephone number (see below). If this is a pager number, enter enough delays for the phone to answer. Then, enter the number to be dialed.
✦ End a pager number with the completion character
(usually a pound (#) character).
STEP #91 Enter the supervisory or pager telephone number
using this step.
number, enter step number 91 then press TEST.
✦ When creating telephone numbers with
programming Steps 89, 90, & 91, use the following keys to add dialing delays or special characters. ✦ Press the key to place a 1-second dialing delay at the start or anywhere in the middle of the telephone number. ✦ Pressing the key as the last digit of the telephone number will place a pound character at the end of the telephone number. ✦ Press the FIRE key to place a 5-second dialing delay
ADDS A 1-SECOND DELAY (START OR MIDDLE OF NUMBER)
ADDS A 5-SECOND DELAY (ANYWHERE IN NUMBER)
ADDS A STAR ( ) CHARACTER (ANYWHERE IN NUMBER)
anywhere in the telephone number. ✦ Press the CHIME key to place a star character anywhere in the telephone number.

✦ The factory setting does not report Console trouble
events to the Central Station.
STEP #108 The communicator can be programmed to report
Console trouble events using this step. These include all conditions that light the Console’s BATTERIES or TROUBLE indicator. It also includes low Console backup battery.
0 FOR NO CONSOLE TROUBLE 1 FOR CONSOLE TROUBLE
✦ The factory setting does not send force arming
reports.
STEP #110 The communicator can be programmed to report
force arming anytime the Console is armed with one or more bypassed sensors using this step.
✦ The factory set reporting code for force arming is
“65” (Code 574 with Ademco).
0 FOR NO FORCE ARMING RPTS. 1 FOR FORCE ARMING RPTS.
is force armed (armed with an open sensor) remotely by telephone, or with the RA-2400 Remote Access software, the caller will be disconnected if the communicator is enabled.
✦ The factory setting does not send opening and
closing reports.
STEP #111 The communicator can be programmed to send an
opening report when the system is disarmed, and a closing report when the system is armed for all users, or just the master user using this step.
traffi c using opening and closing reports, it is recommended to disable quick arming to prevent customers from arming the system. ✎ NOTE 2: The reporting codes are fi xed for opening
0 FOR NO OPEN/CLOSE REPORTS 1 FOR O/C RPTS. FOR ALL USERS 2 FOR O/C RPTS. FROM MASTER USER ONLY
and closing. A unique code is reserved for the master user code and each of the fi ve restricted user codes. ✎ NOTE 3: Arming or disarming with the page
alert user code dials the supervisory number, no opening or closing report is sent.
✦ The factory setting enables Point ID and allows the
communicator to send two-digit alarm and trouble codes for each sensor. The individual sensor that causes an alarm or trouble report can be identifi ed at the Central Station.
STEP #113 Point ID can be disabled using this step. The
0 FOR GENERAL REPORTS ONLY 1 FOR POINT ID REPORTING
Central Station will only receive general alarm and trouble reports.

COMMUNICATOR REPORTING CODES ✦ The 4 by 2 two-digit communicator reporting code
for each event has a factory set value. These values may be customized to fi t the specifi c installation and the reporting requirements of the Central Station monitoring the system.
EVENT ALARM CODE EXTENDED CODE
SENSOR EMERGENCY E120 C0xx
✦ If Point ID reporting is enabled (the factory default
SENSOR FIRE E111 C0xx
setting), each sensor can report a unique alarm and trouble code.
BURGLARY ALARM E130 C0xx
✦ If Point ID is disabled, the “general” reporting codes
SILENT PANIC E122 C0xx
for each event type will be used.
✦ Each programming function is performed with
similar keystrokes. After the system is in Setup Mode, enter the programming step number and press HOME, then enter the new value and press AWAY. For reference, follow the fi gures next to the programming steps.
SENSOR LOW BATTERY E384 C0xx
SENSOR STATUS TROUBLE E381 C0xx
CONSOLE BATTERY RESTORE R302 C000
✴ If the new value is accepted, a “Bing” will sound. If the new
value is not accepted, a “Double Buzz” will sound.
✦ Making a value 0 causes the event not to
xx = SENSOR NUMBER IN EXTENDED REPORT
communicate to the Central Station.
and closing. A unique code is reserved for the master and the fi ve restricted user codes. See the Opening & Closing Reporting Codes Table.
GENERAL REPORTING CODES
✦ Use program Steps #201 - 206 to change the
communicator reporting codes when Point ID is disabled.
✦ Refer to the General Reporting Codes table to view/
edit the reporting codes for each of the fi ve events. The factory settings are listed, along with a blank area to write in the new installation values.
STEPS #201-206
Any value from 0-99 can be programmed for each event using these steps (enter “0” to stop an event from reporting).
Central Station requires specifi c codes for certain types of events.

STEP # PROGRAMMING FUNCTION POSSIBLE 4 BY 2 VALUES FACTORY 4 BY 2 VALUES INSTALLATION 4 BY 2 VALUE
201 GENERAL FIRE REPORT CODE 0 - 99 1
202 GENERAL EMERGENCY REPORT CODE 0 - 99 2
203 GENERAL SILENT PANIC REPORT CODE 0 - 99 3
204 GENERAL BURGLARY REPORT CODE 0 - 99 4
206 GENERAL TROUBLE REPORT CODE 0 - 99 6
General Reporting Codes Table

✦ Refer to the System Reporting Codes table to
view/edit the reporting codes for the keypad FIRE and EMERGENCY buttons and for each of the four Console conditions. The factory settings are listed, along with a blank area to write in the new installation values.
PROGRAMMING STEPS #261 TO #266
0 - 99 FOR CONSOLE REPORTING CODE
STEPS #261-266
Any value from 0-99 can be programmed for each event using these steps (enter “0” to stop an event from reporting).

✦ The factory set reporting code for force arming is
STEP #258 Any value from 0-99 can be programmed for this
✦ The factory set reporting code for Duress is “66”
STEP #259 Any value from 0-99 can be programmed for this

STEP # PROGRAMMING FUNCTION POSSIBLE 4 BY 2 VALUES
258 FORCE ARMING REPORT CODE 0 - 99 65 574
259 DURESS REPORT CODE 0 - 99 66 121
261 SYSTEM FIRE REPORT CODE 0 - 99 68 110
262 SYSTEM EMERGENCY REPORT CODE 0 - 99 69 120
263 SYSTEM TEST/CANCEL REPORT CODE 0 - 99 70 406
264 SYSTEM LOW BATTERY RESTORAL REPORT CODE 0 - 99 71 R302
265 SYSTEM LOW BATTERY CODE 0 - 99 73 E302
System Reporting Codes Table

MASTER USER CODE1 74 82 R401 C000 E401 C000
RESTRICTED USER CODE #1 75 83 R401 C001 E401 C001
RESTRICTED USER CODE #2 76 84 R401 C002 E401 C002
RESTRICTED USER CODE #3 77 85 R401 C003 E401 C003
RESTRICTED USER CODE #4 78 86 R401 C004 E401 C004
RESTRICTED USER CODE #5 79 87 R401 C005 E401 C005
PAGE ALERT USER CODE (DIALS PAGE NUMBER ONLY, NO CODES REPORTED)
Opening & Closing Reporting Codes Table

4 BY 2 FORMAT POINT ID ALARM REPORT CODES ✦ Refer to the 4 by 2 Format Point ID Reporting
Code table to view/edit the alarm reporting codes for each of the 24 sensors. The communicator will send these codes if Point ID is enabled and any sensor triggers an alarm. The factory settings are listed, along with a blank area to write in the new installation values.
PROGRAMMING STEPS #210 TO #233
✦ Use program Steps #210 - 233 to change the 4 by 2
Point ID alarm reporting codes.
Central Station requires specifi c codes for certain types of sensors. STEPS #210-233
Any value from 0-99 can be programmed for each event using these steps (enter “0” to stop an event from reporting).
4 BY 2 FORMAT POINT ID TROUBLE REPORT CODES ✦ Refer to the 4 by 2 Format Point ID Reporting Code
table to view/edit the trouble reporting codes for each of the 24 sensors. The communicator will send these codes if Point ID is enabled and any sensor has a low battery or trouble condition. The factory settings are listed, along with a blank area to write in the new installation values.
PROGRAMMING STEPS #234 TO #257
✦ Use program Steps #234 - 257 to change the 4 by 2
Point ID trouble reporting codes.
Central Station requires specifi c codes for certain types of sensors. STEPS #234-257
Any value from 0-99 can be programmed for each event using these steps (enter “0” to stop an event from reporting).


STEP # PROGRAMMING FUNCTION POSSIBLE 4 BY 2 VALUES FACTORY 4 BY 2 VALUE INSTALLATION 4 BY 2 VALUE
210 SENSOR 1 ALARM REPORT CODE 0 - 99 11
211 SENSOR 2 ALARM REPORT CODE 0 - 99 12
212 SENSOR 3 ALARM REPORT CODE 0 - 99 13
213 SENSOR 4 ALARM REPORT CODE 0 - 99 14
214 SENSOR 5 ALARM REPORT CODE 0 - 99 15
215 SENSOR 6 ALARM REPORT CODE 0 - 99 16
216 SENSOR 7 ALARM REPORT CODE 0 - 99 17
217 SENSOR 8 ALARM REPORT CODE 0 - 99 18
218 SENSOR 9 ALARM REPORT CODE 0 - 99 19
219 SENSOR 10 ALARM REPORT CODE 0 - 99 20
220 SENSOR 11 ALARM REPORT CODE 0 - 99 21
221 SENSOR 12 ALARM REPORT CODE 0 - 99 22
222 SENSOR 13 ALARM REPORT CODE 0 - 99 23
223 SENSOR 14 ALARM REPORT CODE 0 - 99 24
224 SENSOR 15 ALARM REPORT CODE 0 - 99 25
225 SENSOR 16 ALARM REPORT CODE 0 - 99 26
226 SENSOR 17 ALARM REPORT CODE 0 - 99 27
227 SENSOR 18 ALARM REPORT CODE 0 - 99 28
228 SENSOR 19 ALARM REPORT CODE 0 - 99 29
229 SENSOR 20 ALARM REPORT CODE 0 - 99 30
230 SENSOR 21 ALARM REPORT CODE 0 - 99 31
231 SENSOR 22 ALARM REPORT CODE 0 - 99 32
232 SENSOR 23 ALARM REPORT CODE 0 - 99 33
233 SENSOR 24 ALARM REPORT CODE 0 - 99 34
234 SENSOR 1 TROUBLE REPORT CODE 0 - 99 41
235 SENSOR 2 TROUBLE REPORT CODE 0 - 99 42
236 SENSOR 3 TROUBLE REPORT CODE 0 - 99 43
237 SENSOR 4 TROUBLE REPORT CODE 0 - 99 44
238 SENSOR 5 TROUBLE REPORT CODE 0 - 99 45
239 SENSOR 6 TROUBLE REPORT CODE 0 - 99 46
240 SENSOR 7 TROUBLE REPORT CODE 0 - 99 47
241 SENSOR 8 TROUBLE REPORT CODE 0 - 99 48
242 SENSOR 9 TROUBLE REPORT CODE 0 - 99 49
243 SENSOR 10 TROUBLE REPORT CODE 0 - 99 50
244 SENSOR 11 TROUBLE REPORT CODE 0 - 99 51
245 SENSOR 12 TROUBLE REPORT CODE 0 - 99 52
246 SENSOR 13 TROUBLE REPORT CODE 0 - 99 53
247 SENSOR 14 TROUBLE REPORT CODE 0 - 99 54
248 SENSOR 15 TROUBLE REPORT CODE 0 - 99 55
249 SENSOR 16 TROUBLE REPORT CODE 0 - 99 56
250 SENSOR 17 TROUBLE REPORT CODE 0 - 99 57
251 SENSOR 18 TROUBLE REPORT CODE 0 - 99 58
252 SENSOR 19 TROUBLE REPORT CODE 0 - 99 59
253 SENSOR 20 TROUBLE REPORT CODE 0 - 99 60
254 SENSOR 21 TROUBLE REPORT CODE 0 - 99 61
255 SENSOR 22 TROUBLE REPORT CODE 0 - 99 62
256 SENSOR 23 TROUBLE REPORT CODE 0 - 99 63
257 SENSOR 24 TROUBLE REPORT CODE 0 - 99 64
4 by 2 Format Point ID Reporting Code Table

LINEAR LIMITED WARRANTY This Linear product is warranted against defects in material and workmanship for twelve (12) months. This warranty extends only to wholesale customers who buy direct from Linear or through Linear's normal distribution channels. Linear does not warrant this product to consumers. Consumers should inquire from their selling dealer as to the nature of the dealer's warranty, if any. There are no obligations or liabilities on the part of Linear LLC for consequential damages arising out of or in connection with use or performance of this product or other indirect damages with respect to loss of property, revenue, or profi t, or cost of removal, installation, or reinstallation. All implied warranties, including implied warranties for merchantability and implied warranties for fi tness, are valid only until the warranty expires. This Linear LLC Warranty is in lieu of all other warranties express or implied. All products returned for warranty service require a Return Product Authorization Number (RPA#). Contact Linear Technical Services at 1-800-421-1587 for an RPA# and other important details.
FIRE EVACUATION PLANNING For systems that include fi re protection, UL requires that the following information be available to the users of the system.
✶ Draw up a fl oor plan showing two exits for each room.
The following procedures are to be discussed with the family:
➀ Status of bedroom doors. ➁ Familiarity with alarm signals. ➂ Testing of door during a fi re and use of alternate escape route if door
is hot to touch. ➃ Crawling and holding breath. ➄ Escape fast. No stopping for packing. ➅ Meet at designated outdoor spot. ➆ Emphasize that no one is to return to a burning house. ➇ Fire department notifi cation from a neighbor's phone. ➈ Periodic rehearsal is to be conducted.
WIRELESS PRODUCT NOTICE Linear radio controls provide a reliable communications link and fi ll an important need in portable wireless signaling. However, there are some limitations which must be observed.
INDUSTRY CANADA NOTICES NOTICE: The ringer equivalence number (REN) assigned to each terminal device provides an indication of the maximum number of terminals allowed to be connected to a telephone interface. The termination on an interface may consist of any combination of devices subject only to the requirement that the sum of the ringer equivalence numbers of all the devices does not exceed 5. NOTICE: The Industry Canada label identifi es certifi ed equipment. This certifi cation means that the equipment meets certain telecommunications network protective, operational and safety requirements. The Department does not guarantee the equipment will operate to the user's satisfaction. Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations. Repairs to certifi ed equipment should be made by an authorized Canadian maintenance facility designated by the supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the telecommunications company cause to request the user to disconnect the equipment. Users should ensure for their own protection that the electrical ground connections of the power utility, telephone lines and internal metallic water pipe system, if present, are connected together. This precaution may be particulary important in rural areas. CAUTION: Users should not attempt to make such connections themselves, but should contact the appropriate electric inspection authority, or electrician, as appropriate.
FCC Rules and Regulations as Part 15 devices. As such, they have limited transmitter power and therefore limited range. ✶ A receiver cannot respond to more than one transmitted signal at a
time and may be blocked by radio signals that occur on or near their operating frequencies, regardless of code settings. ✶ Changes or modifi cations to the device may void FCC compliance. ✶ Infrequently used radio links should be tested regularly to protect
against undetected interference or fault. ✶ A general knowledge of radio and its vagaries should be gained prior
to acting as a wholesale distributor or dealer, and these facts should be communicated to the ultimate users.
FCC NOTICE This equipment generates and uses radio frequency energy and if not installed and used properly, that is, in strict accordance with the manufacturer's instructions, may cause interference to radio and television reception. It has been type tested and found to comply with the limits for a Class B computing device in accordance with Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference in a residential installation. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
✶ Relocate the Console away from the TV/radio receiver. ✶ Plug the Console into a different wall outlet so that the Console is on
a different branch circuit. ✶ Re-orient the TV/radio antenna. ✶ If necessary, the user should consult the dealer or an experienced
radio/television technician for additional suggestions.
FCC TELEPHONE RULES AND REGULATIONS The FCC requires that this alarm dialer system not make more than 15 repetitive dialing attempts to a single telephone number. There are no limitations when the calls are made sequentially to two or more alternative numbers, or when these calls are spaced 10 minutes apart to a single number. The FCC Rules and Regulations do not specify the re-attempt period as this can vary for specifi c applications. When setting this period, take into consideration local, interstate, foreign and special network call completion characteristics, network processing time, a suffi cient number of rings and busy/don't answer modes.
Copyright © 2008 Linear LLC 212734 H
Pages referenced in this manual — manufacturer, support and downloads.
Owners and our team usually reply within a day — and your question helps the next person too.
Be the first to ask — other owners or our team will answer.