EN
Linear logo
Official user manual

Linear DVS-2400

44 pages·2.3 MB·Home Security System·PDF·ENDEFRITNLJA
Linear DVS-2400
Table of Contents 80 sections SECURITY · SUPERVISED WIRELESS SECURITY CONSOLE · Installation & Programming Instructions · INTRODUCTION · … ShowHide
SECURITYp.1SUPERVISED WIRELESS SECURITY CONSOLEp.1Installation & Programming Instructionsp.1INTRODUCTIONp.21. THE DVS-2400 SECURITY SYSTEMp.4DXT-41 & DXT-42p.4DXT-21 & DXT-23p.4REMOTESp.4REMOTES †p.4DXT-61 REMOTE †p.4DVS-2400 CONSOLE DXS-10 WIRELESSp.4DXS-62A REMOTEp.4KEYPADp.4DXS-73 SMOKE DETECTORp.4DXS-31 DOOR/WINDOWp.4DXS-32 MINI DOOR/WINDOWp.4DXS-81 BILL TRAP †p.4DXS-54p.4DXS-91 GLASS BREAK DETECTOR †p.4PIRp.4SENSORp.4DXT-21‡ DXS-21‡ DXT-23‡ DXS-23‡ DXS-62Ap.5DXS-10p.5DXS-81‡p.5DXS-73p.5DXT-41 DXT-61‡ DXT-42p.5DXS-91‡p.52. SECURITY SYSTEM FLOOR PLANp.6EXAMPLE SYSTEMp.6DESIGN THE INSTALLATIONp.6ESp.63. TYPICAL SYSTEM SENSORSp.7DOOR/WINDOW SENSORp.7WIRELESS KEYPADp.74. CONSOLE FEATURESp.83 MODE INDICATORSp.84 CONSOLE STATUS INDICATORSp.8POWER LIGHTp.8BATTERIES LIGHTp.8TROUBLE LIGHTp.81 24-HOUR BUTTONSp.85 SIREN SPEAKERp.82 MODE BUTTONSp.8OFFp.86 STATUS INDICATORSp.8CHIMEp.87 CASE ACCESS SCREW (HIDDEN)p.88 KEYPADp.8TESTp.810 AUXILIARY FUSEp.919 RADIO TEST POINTSp.920 MICROPHONE (WITH MODEL VB-2 INSTALLED ONLY)p.911 MAIN TERMINAL BLOCKp.921 ANNUNCIATOR VOLUME CONTROLp.912 BATTERY FUSEp.922 DIGITAL VOICE SYNTHESIS MODULE (OPTIONAL)p.913 TELEPHONE TERMINAL BLOCKp.914 INTERNAL SPEAKER CONNECTORp.915 ANTENNA TERMINALSp.916 OPTIONAL BACKUP BATTERYp.917 WIRING ACCESS HOLEp.918 WALL-MOUNT SLOTSp.95. CONSOLE INSTALLATIONp.10CONSOLE LOCATIONp.10REMOVE CASE LOCKING SCREW TO ACCESS INTERNAL COMPONENTSp.10CASE LOCKING SCREWp.10WALL MOUNTINGp.10EXTERNAL CONSOLE SPEAKER CONNECTIONp.11EXTERNAL ALARM SIREN CONNECTIONp.11TELEPHONE LINE CONNECTIONp.12TELEPHONEp.12TERMINALp.12SEIZED RING (R1) SEIZED TIP (T1)p.12LINE RING (R) LINE TIP (T)p.12CONNECT TELEPHONE LINE TO THE TELEPHONE TERMINAL BLOCKp.12AUTOMATION OUTPUT CONNECTION (OPTIONAL)p.12MAIN TERMINALp.12BLOCKp.12EXAMPLE AUTOMATION OUTPUT HOOK-UPSp.12LINEAR RB-90 RELAY MODULE YOUR LOADp.12
Page 1 of the Linear DVS-2400 user manual — Installation & Programming Instructions
Page 1 · click to enlarge
Page 1
Linear DVS-2400 — SECURITY diagram (page 1)
Fig. 1

SECURITY

SUPERVISED WIRELESS SECURITY CONSOLE

Linear DVS-2400 — SECURITY diagram (page 1)
Fig. 2

Installation & Programming Instructions

USA & Canada (800) 421-1587 & (800) 392-0123

(760) 438-7000 - Toll Free FAX (800) 468-1340

www.linearcorp.com

Page 2 of the Linear DVS-2400 user manual — INTRODUCTION
Page 2 · click to enlarge
Page 2

INTRODUCTION

CONGRATULATIONS for selecting Linear’s DVS-2400 Security System. The DVS-2400 Console incorporates many advanced and sophisticated features. The system can be expanded and customized to fi t the installation’s specifi c needs.

Linear DVS-2400 — INTRODUCTION diagram (page 2)
Fig. 3

The DVS-2400 Console and its accessories are designed and manufactured by the oldest wireless security company in North America. You can look ahead to many years of reliable service with this Console and its accessories.

Many insurance companies offer discounts on homeowners and renters policies when a security system is installed. Discount credits vary with different companies and generally increase in savings with an increase in the level of protection. Inform the user to ask their insurance agent about savings available.

The DVS-2400 Console is UL Listed. For a UL smoke alarm system, there must be at least one smoke detector programmed into the Console to meet National Fire Protection Association (NFPA) Rule 72 Chapter 2 and UL 217 requirements. Many insurance companies require you to meet these requirements to qualify for a discount. Only use the Model DXS-73 smoke detector with this Console for a UL smoke alarm system.

UL Listed as a Single Station Smoke Detector Accessory, also suitable as a

System Control Unit. UL Category CCN UTGT & NBSX

In this manual, the bullets preceding the text help to defi ne the information. For example:

✦ This symbol indicates a feature.

❏ This symbol indicates an action to perform

and provides a box to check when the action is completed.

✴ This symbol is for lit indications or system sounds.

✎ This symbol is for important notes.

Household Burglar-Alarm

Page 3 of the Linear DVS-2400 user manual — INTRODUCTION
Page 3 · click to enlarge
Page 3
Page 3 of the Linear DVS-2400 user manual — INTRODUCTION
Page 4 of the Linear DVS-2400 user manual — DXS-31 DOOR/WINDOW
Page 4 · click to enlarge
Page 4

1. THE DVS-2400 SECURITY SYSTEM

Linear DVS-2400 — 1. THE DVS-2400 SECURITY SYSTEM diagram (page 4)
Fig. 4

DXT-41 & DXT-42

DXT-21 & DXT-23

REMOTES

REMOTES †

DXT-61 REMOTE †

DVS-2400 CONSOLE DXS-10 WIRELESS

DXS-62A REMOTE

KEYPAD

DXS-73 SMOKE DETECTOR

† NOTEThese accessories

are not listed by UL.

DXS-31 DOOR/WINDOW

DXS-32 MINI DOOR/WINDOW

DXS-81 BILL TRAP †

DXS-54

DXS-91 GLASS BREAK DETECTOR †

PIR

SENSOR

SENSOR

CONSOLE The DVS-2400 Console is the heart of the system. It monitors all of the system’s wireless sensors and controls the alarm sirens.

The Console has 24-hour capabilities that are always ready to operate, even when the Console is disarmed. They can be triggered by buttons on the Console, the Wireless Keypad, portable remote controls, carbon monoxide detectors, and smoke detectors. Pressing the EMERGENCY or FIRE button for two seconds will cause an immediate siren and call the central station. IMPORTANT: For personal emergency use only. Not for use as a UL Listed Medical Alert System.

The Console constantly monitors the condition of the system’s sensors, displaying which protected doors and windows are open or closed. If an alarm occurs, the Console displays which sensor(s) caused it. When a sensor has a low battery, the Console displays which sensor needs a new battery. Sensors that send hourly status transmissions keep the Console informed of their operating condition.

The Console’s Environmental Zone is a 24-hour zone that can be triggered with sensors connected to devices such as water fl ow detectors, over/under temperature sensors, fl ood sensors, etc. The Environmental Zone activates the chime annunciator without sounding the siren. The Environmental Zone does not send communicator reports.

Up to eight different custom user codes can be used to operate the system. For security, a user code must be entered to disarm (turn off) the system. The system can be armed (turned on) by entering a user code, or with the unique “Quick Arm” feature. The fi ve restricted user codes and the special page alert user code can only arm and disarm the system, no programming changes are allowed. The master user code is allowed to program the Console, and a duress code can be selected for emergency disarming of the system with a duress report to the Central Station. The page alert user code can dial a pager number to inform the pager wearer when the Console is disarmed.

An Automation Output in the Console provides an easy way to connect external devices to the Console. The output is fully programmable to activate on a variety of conditions, such as when the system is armed, during alarms, and during exit/entry delays. The Automation Output can connect to lighting control modules, relays, noisemakers, and indicators. The Console’s and wireless keypad’s key and transmitters can control the Automation Output.

The Console’s memory will retain the user codes and all of the system’s programming, even during a total power loss. An optional backup battery can be installed to power the system during short power failures.

The Console can be programmed locally using its own keypad or remotely, over the telephone, using Linear’s Model RA-2400 Remote Access software program. The RA-2400 upload/ download program is a Windows® application that runs on a personal computer and communicates with the Console through a modem connected directly to the Console, or through the telephone line.

The built-in digital communicator connects the Console to a Central Alarm Monitoring Station through the telephone. With a monitored system, the central station can dispatch authorities in case of burglary, fi re or other emergency. The central station can also call family, friends, neighbors, or anyone else designated on a custom call list.

A total of 24 sensors of the types listed on the next page can be used with each DVS-2400 Console. Each burglary sensor can trigger the siren (and report to the Central Station) once per arming cycle. 24-hour sensors have unlimited alarm and reporting capacity.

Each sensor can report directly to the Central Station using the digital communicator’s Point ID feature. If a sensor triggers an alarm or experiences supervisory trouble, a unique report code can be sent for immediate identifi cation of the event.

The optional Model VB-2 digital voice synthesis module can be installed in the Console. The VB-2 module provides three exciting features: 2-way audio monitoring capability at the Central Station through the communicator, local voice prompts from the Console’s speaker, and voice prompted remote system control using in-house or off-site pushbutton telephones.

Page 5 of the Linear DVS-2400 user manual — DXS-91‡
Page 5 · click to enlarge
Page 5

DOOR/WINDOW SENSORS The DXS-31 and DXS-32 sensors monitor doors and windows. They send radio signals to the Console. One type of signal is sent when the door or window is opened, and a different type of signal is sent when the door or window is closed. If the Console is armed, a sensor can trigger the Console's burglary siren when its door or window is opened. Both sensors are supervised, send hourly status reports, and monitor their battery condition.

PANIC BUTTONS The DXT-21, DXS-21 single-button, and DXT-23, DXS-23 two-button transmitters can be used as portable “panic buttons”. Pressing the front or top button on the DXT-21 or DXS-21 at any time will trigger the emergency siren. Pressing both front buttons simultaneously on the DXT-23 or DXS-23 at any time will trigger the emergency siren. These transmitters can be programmed to activate various other system functions. The DXT-21 and DXT-23 transmitters are not supervised. The DXS-21 and DXS-23 transmitters are supervised.

Linear DVS-2400 — DXT-21‡ DXS-21‡ DXT-23‡ DXS-23‡ DXS-62A diagram (page 5)
Fig. 5

The DXS-62A transmitter is typically used as a portable “panic button”. Pressing the button on a DXS-62A at any time will trigger the emergency siren. This transmitter can send hourly status signals and low battery signals if the battery is low.

WIRELESS KEYPAD The DXS-10 wireless keypad is used to operate the Console remotely. It can be placed in a convenient spot so the user doesn't have to go to the Console to control the system. The wireless keypad can also trigger the emergency or fi re siren and actuate the Automation Output. Pressing will cause the Console to sound Beeps corresponding to the current operating mode. The DXS-10 is supervised, it sends hourly status reports and monitors its battery condition. IMPORTANT: For personal emergency use only. Not for use as a UL Listed Medical Alert System.

DXT-21‡ DXS-21‡ DXT-23‡ DXS-23‡ DXS-62A

BILL TRAP The DXS-81 bill trap can be used with the Console in non-UL small commercial hold-up installations. The unit is concealed in a cash drawer under a stack of currency, with a single “bait” bill secured in its money clip. During a hold-up, the cashier removes the stack of currency along with the “bait” bill. When a “bait” bill is removed, the transmitter sends a signal to the Console. Four additional signals are sent within the fi rst minute after the “bait” bill is removed. When the “bait” bill is replaced, a restore signal is sent. The DXS-81 is supervised, it can send hourly status reports (optional) and monitors its battery condition.

DXS-10

SMOKE DETECTOR The DXS-73 is a high quality smoke detector with a built-in radio transmitter. As soon as smoke is detected, the unit will sound its local noisemaker. Then, 20 seconds after the local noisemaker sounds, the transmitter sends an alarm signal to the Console. The alarm signal will be repeated every 20 seconds as long as smoke is still present. A restoral signal will be sent when the smoke detection chamber clears. The DXS-73 is supervised, it sends hourly status reports, and monitors its battery condition.

DXS-81‡

PASSIVE INFRARED MOTION DETECTOR The DXS-54 is a passive infrared (PIR) motion detector with a built-in radio transmitter. The PIR detects motion in its detection pattern by measuring the infrared emission levels of objects that it “sees”. If the infrared levels change quickly, as when a person moves across the detection pattern, the PIR will recognize the change as an intrusion and send an alarm signal to the Console. An alarm will be triggered if the system is in the Away Mode. The DXS-54 is supervised, it sends hourly status reports and monitors its battery condition.

DXS-73

☞ NOTE: A Model DXS-73 Smoke Detector is required to create a UL Listed smoke alarm system. See Page 13 for details on adding a smoke detector sensor to the system.

REMOTE CONTROLS The DXT-41, DXT-61 single-button and DXT-23, DXT-42 multi-button remote controls can be used to remotely arm and disarm the Console. The DXT-42’s left button will arm and the right button will disarm the Console. Pressing both buttons simultaneously will trigger the emergency siren. Alternately the Console can be programmed to respond to the DXT-42 by arming and disarming with the left button, and activating the automation output with the right button. These transmitters can also be programmed to activate various other Console zones. These transmitters are not supervised.

DXS-54

DXT-41 DXT-61‡ DXT-42

GLASS BREAK DETECTOR The DXS-91 is a glass break detector with an audio sound discriminator and a built-in radio transmitter. The unit “listens” for the sound of breaking glass. When glass breakage is detected, the unit sends an alarm signal to the Console. The DXS-91 is supervised, it sends hourly status reports and monitors its battery condition.

‡ NOTEThese accessories not listed by UL

DXS-91‡

Page 6 of the Linear DVS-2400 user manual — ES
Page 6 · click to enlarge
Page 6

2. SECURITY SYSTEM FLOOR PLAN

EXAMPLE SYSTEM

✦ The example shows a typical DVS-2400 system.

✦ Any or all of the accessories shown can be used.

✦ A total of 24 sensors can be used with each

Console.

DESIGN THE INSTALLATION

1. Draw a fl oor plan for the installation.
2. Consider the security needs of the premises.
3. Determine which doors and windows are vulnerable to intrusion.
4. Figure which interior areas an intruder might go to if unlawful entrance is gained.
5. Indicate locations for door/window sensors, interior motion detectors, keypads, glass break detectors and external siren speakers.
6. Decide on a centralized location for the security Console .

ES

Linear DVS-2400 — ES diagram (page 6)
Fig. 6

CON - CONSOLE S - DOOR/WINDOW SENSOR WK - WIRELESS KEYPAD MD - MOTION DETECTOR ES - EXTERNAL SIREN SD - SMOKE DETECTOR CO - CARBON MONOXIDE DETECTOR GB - GLASS BREAK SENSOR MS - HARDWIRED MAGNETIC SWITCH

Example Residential Security System Floor Plan

Page 7 of the Linear DVS-2400 user manual — KEYPAD
Page 7 · click to enlarge
Page 7

3. TYPICAL SYSTEM SENSORS

DOOR/WINDOW SENSOR

✦ Sensor mounts on door or window with adjacent

magnet.

✦ Opening door or window moves magnet away,

triggering sensor.

Linear DVS-2400 — DOOR/WINDOW SENSOR diagram (page 7)
Fig. 7

✦ Pressing the case causes sensor to send a test

signal.

✦ Jumper inside for INSTANT or DELAYED alarm

setting.

✦ Press the case for testing, the red transmit light

shows that battery is in good condition.

✦ Internal lithium batteries are monitored by the

Console.

✦ Sends hourly status reports to the Console.

✦ Up to 3 years battery life (depends on frequency of

activation). (UL tested for 1 year minimum.)

✦ Sensor contains internal terminals for connection to

glass break detector and external switches.

WIRELESS KEYPAD

✦ For controlling the system remotely without having

to go to the Console.

Linear DVS-2400 — WIRELESS KEYPAD diagram (page 7)
Fig. 8

✦ Green operation light.

✦ Internal 9-volt battery is monitored by the Console.

✦ Keypad's beeper will buzz during transmissions

when the battery is low.

✦ Up to 3 years battery life (depends on frequency of

activation). (UL tested for 1 year minimum.)

KEYPAD

✦ Sends hourly status reports to the Console.

✦ Press to activate the automation output.

ABOUT SENSOR STATUS SUPERVISION All DXS Format sensors transmit hourly status reports. All DXT Format sensors do not transmit hourly status reports. Both sensor formats can be used with the Console.

✦ Pressing clears the keypad.

✦ Pressing for two seconds sounds the mode Beeps from the Console.

✔ Off Mode: 1 “Gong”.

When a sensor is programmed into the Console, the system will set the sensor as non-supervised or supervised. Sensors set as non-supervised are not expected to send hourly status reports. Sensors set as supervised are expected to send hourly status reports. If a status report is not received in 8 hours from a sensor set as supervised, the TROUBLE indicator will fl ash.

✔ Chime Mode: 1 “Gong” & 1 “Beep”.

✔ Home Mode: 1 “Gong” & 2 “Beeps”.

✔ Away Mode: 1 “Gong” & 3 “Beeps”.

✔ Test Mode: 1 “Gong” & 4 “Beeps”.

When sensors are programmed into the Console, ALL STATIONARY SENSORS ARE SET AS SUPERVISED, ALL PORTABLE SENSORS ARE SET AS NON-SUPERVISED.

✦ Emergency and fi re alarm can be triggered from the

wireless keypad at any time.

If stationary DXT Format sensors have been programmed into the Console, be sure to change their setting to non-supervised to prevent TROUBLE indications. This will not prevent low battery monitoring.

✎ UL NOTEFor personal emergency use only. Not

for use as a UL Listed Medical Alert System.

If portable DXS Format sensors have been programmed into the Console, and the installation requires supervision for specifi c portable sensor(s), change the selected portable sensors setting to supervised.

After programming the sensors, if changes are required, refer to “Changing a Sensors Supervision” on Page 26 for details on changing the way a sensor’s supervision is set.

Page 8 of the Linear DVS-2400 user manual — TEST
Page 8 · click to enlarge
Page 8

4. CONSOLE FEATURES

3 MODE INDICATORS

Linear DVS-2400 — 3 MODE INDICATORS diagram (page 8)
Fig. 9

★ Specifi c indicator will light showing the mode the Console is in. ★ HOME indicator will blink during Secure Exit and Home Instant modes. ★ AWAY indicator will blink during the exit delay in the Away Mode.

4 CONSOLE STATUS INDICATORS

★ Shows the current status of the Console.

POWER LIGHT

★ Glows when AC power is on. ★ Blinks when AC power is off and backup battery is installed. ★ Blinks when the backup battery is low, recharging or missing. ★ Off when AC power is off and no backup battery is installed (system disabled).

BATTERIES LIGHT

★ Blinks when one or more sensors have a low battery. ★ Press for one second to view sensor status. Sensor status indicator for any sensor with a low battery will light along with the BATTERIES indicator. Any trouble indications will follow during the fi ve second status cycle. ★ Switch to Test Mode after replacing the sensor battery and completely test the

system (see Test Mode). Switching to Test Mode clears the low battery indication.

TROUBLE LIGHT

★ Blinks when one or more sensors have not reported status during the eight hour

status time period. ★ Press for one second to view sensor status. Sensor status indicator for any sensor that has not reported in will light along with the TROUBLE indicator. Any low battery indications will follow during the fi ve second status cycle. ★ Switch to Test Mode after servicing the sensor and completely test the system

1 24-HOUR BUTTONS

★ Pressing FIRE for two seconds sounds the fi re siren and sends a “fi re” message

to a central monitoring station through the digital communicator (if the system is monitored). ★ Pressing EMERGENCY for two seconds sounds the emergency siren and sends

(see Test Mode). Switching to Test Mode clears the trouble indication.

an “emergency” message to a central monitoring station through the digital communicator (if the system is monitored). ★ Both work even when system is disarmed. ★ IMPORTANT: For personal emergency use only. Not for use as a UL Listed

5 SIREN SPEAKER

★ Makes unique sounds for burglary, fi re and emergencies. ★ Alarm sirens stop automatically after fi ve minutes. ★ Sounds advisory tones to confi rm keystrokes from the Console. ★ Sounds mode selection tones. ★ Sounds alarm memory tones. ★ Beeps when Automation Output is activated. ★ Speaks the system status information when optional VB-2 digital voice synthesis

Medical Alert System.

2 MODE BUTTONS

★ Used to operate the system.

OFF

module is installed. ★ Terminals available for an external siren.

★ Off Mode disarms the system. ★ Switching to Off Mode stops the alarm siren.

6 STATUS INDICATORS

✓ Multiple Beeps sound and sensor status indicators fl ash if an alarm has

occurred. ☞ Multiple Beeps mean caution. AN INTRUDER MAY STILL BE PRESENT.

★ Indicates the status of each of the system’s sensors. ★ Lights show which doors and windows are open. ★ Lights fl ash to display sensors that have caused an alarm. ★ Stick-on labels are provided to identify the custom sensor locations.

CHIME

★ Chime Mode disarms the system. ★ Switching to Chime Mode stops the alarm siren.

7 CASE ACCESS SCREW (HIDDEN)

✓ Multiple Beeps sound and sensor status indicators fl ash if an alarm has

★ Remove clear display window and sensor identifi cation card to gain access to

occurred. ☞ Multiple Beeps mean caution. AN INTRUDER MAY STILL BE PRESENT. ★ Chime Mode is for monitoring doors and windows.

the screw. ★ Remove case access screw to unlock case. Case hinges open to the left.

8 KEYPAD

✓ Use this mode as an “automatic door chime” when at home. ✓ Opening any protected door or window causes the Console to “ding-dong”.

★ Backlit keys for easy viewing in low light conditions. ★ For entering the user's user code (numerically or alphabetically). ★ Used when programming system options. ★ Press to activate the Automation Output. ★ Press to clear keypad if the wrong key is pressed. ★ Press for one second to view sensor battery and supervisory status (see BATTERIES and TROUBLE indicator description).

★ Home Mode arms the perimeter sensors, but not the interior sensors.

✓ Use this mode when anyone is staying behind. ✓ Interior motion detectors and interior door sensors are not armed. ✓ Home secure mode makes all delayed perimeter sensors instant. ✓ Secure exit mode starts an exit delay while remaining in Home Mode. ✓ Re-entering during the exit delay restarts the exit delay (one time only).

★ Away Mode arms the entire system.

✓ Use this mode when leaving home. ✓ Door sensors set for delayed will have a time delay that allows the user to

leave and enter the premises without sounding the alarm. ✓ Re-entering during the exit delay restarts the exit delay (one time only). ✓ Entry Delay Beeps warn the user to disarm the system before the siren

starts.

TEST

★ Test Mode is for testing the system sensors.

✓ All sensor status lights blink when the Test Mode is entered. ✓ Each sensor status light will stop blinking when its sensor is tested. ★ Hold the TEST button down to test all of the Console's indicator lights.

Page 9 of the Linear DVS-2400 user manual — 18 WALL-MOUNT SLOTS
Page 9 · click to enlarge
Page 9
Linear DVS-2400 — 10 AUXILIARY FUSE diagram (page 9)
Fig. 10

10 AUXILIARY FUSE

19 RADIO TEST POINTS

★ Type 2AG, 1-amp fuse. ★ Protects the external relay output when used with wet contacts (12 VDC

★ Used to monitor the Console's radio receiver during troubleshooting. ★ Provides connection for an audio amplifi er to listen to the receiver's output. ★ Helpful to determine sources of radio interference.

switched out). ★ Fuse will blow when load exceeds 1 amp. ✎ WARNING: For continued protection against the risk of fi re, replace only

20 MICROPHONE (WITH MODEL VB-2 INSTALLED ONLY)

with the same type and rating of fuse.

★ High sensitivity microphone. ★ Detects room audio when communicator is reporting to the Central Station

11 MAIN TERMINAL BLOCK

in 2-way audio mode (Model VB-2 digital voice synthesis module must be installed).

★ Terminals for connection to the plug-in AC transformer. ★ Terminals for connection to an external siren speaker. ★ Automation Output to connect to an automation controller. ★ External relay output for “wet” contacts (switched 12 volts) or “dry” contacts

21 ANNUNCIATOR VOLUME CONTROL

★ Varies the volume of the advisory tones that come from the speaker. ★ Does not affect internal or external sirens (they are always full volume).

(normally open 1 amp @ 24 volts maximum).

12 BATTERY FUSE

22 DIGITAL VOICE SYNTHESIS MODULE (OPTIONAL)

★ Type 2AG, 3-amp fuse for the backup battery. ★ If the POWER light is fl ashing and the optional backup battery is installed and

★ The Model VB-2 gives the Consoles's digital communicator listen-only, manual

2-way and full duplex 2-way audio capability with the Central Station. ★ The module allows remote command of the system using a standard pushbutton

charged, check this fuse. ✎ WARNING: For continued protection against the risk of fi re, replace only

telephone, on or off site. ★ The module provides optional voice prompts from the Console’s speaker. ★ Units programmed for two-way duplex can still be controlled manually by

with the same type and rating of fuse.

13 TELEPHONE TERMINAL BLOCK

pressing the “1” or “3” key. ★ The Central Station can now return the unit to two-way duplex by pressing the

★ Provides telephone connections for the digital communicator. ★ Provides telephone connection for voice prompted telephone remote control

“8” key.

(optional VB-2 digital voice response module required). ★ Provides seized ring and tip connections for local telephone instruments.

Communicator will disconnect local telephones while on-line.

14 INTERNAL SPEAKER CONNECTOR

★ Connects the internal speaker to the Console circuit board. ★ 2-pin connector, non-polarized.

15 ANTENNA TERMINALS

★ Antenna and ground terminals for receiving signals from the system's sensors. ★ Pre-wired to the Console's internal wire dipole antenna. ★ Alternately connects to the Model LA-P local whip and remote antenna kit.

16 OPTIONAL BACKUP BATTERY

★ Space for 12-volt, 1.2 amp/hour backup battery. (Highly recommended.) ★ Backup battery is automatically charged and monitored by the Console. ★ Backup battery can power the Console for up to 6 hours. ★ UL NOTE: Normal estimated battery life should be 3 to 4 years.

17 WIRING ACCESS HOLE

★ Provides access to recessed wiring trough in base of Console. ★ Route cables for power, telephone, external speaker, etc. through this hole. ★ Loop for zip-tie strain relief provided next to hole.

18 WALL-MOUNT SLOTS

★ Used when mounting Console recessed in the wall. ★ Two mounting brackets (supplied) slide through slots and are retained by

screws, clamping the unit to the wall.

Page 10 of the Linear DVS-2400 user manual — WALL MOUNTING
Page 10 · click to enlarge
Page 10

5. CONSOLE INSTALLATION

CONSOLE LOCATION

✎ NOTEWireless sensor signals must be able to
Linear DVS-2400 — CONSOLE LOCATION diagram (page 10)
Fig. 11

reach the Console.

✔ Try to centrally locate the Console.

✔ Keep Console away from large metal

USE A PAPER CLIP TO REMOVE THE CLEAR DISPLAY WINDOW

appliances.

✔ Maximum recommended sensor range is 400

feet (system tested at 1000 feet).

✎ NOTEIf you don't use the Wireless Keypad, the

Console should be easily accessible to the usual entrance.

✔ When the Console is set in the Away Mode,

Linear DVS-2400 — CONSOLE LOCATION diagram (page 10)
Fig. 12

the user has 30 seconds to switch to Off Mode before the burglary siren sounds.

REMOVE CASE LOCKING SCREW TO ACCESS INTERNAL COMPONENTS

✎ NOTEMake sure the Console is in a place where

the alarm can be heard during the night hours.

✔ Optional remote external sirens (up to 150 feet

from the Console) can be used to make alarms louder and remote the sound location.

1. Locate the Console near a 115 VAC outlet that's not controlled by a light switch.
2. Locate the Console near a telephone outlet (if using the digital communicator).

CASE LOCKING SCREW

Linear DVS-2400 — CASE LOCKING SCREW diagram (page 10)
Fig. 13

✦ To access the Console’s internal components or

to prepare the Console for wall mounting, the case locking screw needs removing.

CUT A 10" x 6 3/4" HOLE CENTERED BETWEEN STUDS IN MOUNTING WALL AT A CONVENIENT HEIGHT

1. Use a paper clip to remove the clear plastic display window.
2. Remove the sensor number nameplate.
3. Remove the case locking screw.

WALL MOUNTING

✦ If desired, the Console can be surface mounted or

recessed into the wall.

Linear DVS-2400 — WALL MOUNTING diagram (page 10)
Fig. 14
1. For surface mounting, use the Console’s case bottom as a template and mark the locations for the four mounting screws.
2. Use four screws and appropriate screw anchors to temporarily mount the unit to the wall (the unit will need to be removed to complete the recessed wiring hook up).
1. For recessed wall mounting, cut a 10” by 6-3/4” hole, centered between studs, in the mounting wall at a convenient height.
Linear DVS-2400 — WALL MOUNTING diagram (page 10)
Fig. 15
2. Slide the unit into the mounting hole and temporarily secure it with the two retaining clamps and screws provided (the unit will need to be removed to complete the recessed wiring hook up).

SECURE CONSOLE TO WALL USING THE TWO CLAMPS AND SCREWS PROVIDED

Surface Mounting · Recessed Mounting

Page 11 of the Linear DVS-2400 user manual — EXTERNAL ALARM SIREN CONNECTION
Page 11 · click to enlarge
Page 11

EXTERNAL CONSOLE SPEAKER CONNECTION

Linear DVS-2400 — EXTERNAL CONSOLE SPEAKER CONNECTION diagram (page 11)
Fig. 16

✦ An external console speaker sounds system tones

and alerts occupants with a loud siren during alarm.

✦ With the VB-2 module installed, the Central Station

can talk to the occupants through the external console speaker.

✦ Use an 8-ohm, 10 watt minimum rated speaker. Do

not use a horn/siren with a built-in siren driver.

✦ Up to two 8-ohm speakers can be used with each

Console.

AC AC EXT. SPKR (-) H/A - H/A + RELAY N.O. RELAY DRY

✦ Up to 150 feet of 22 AWG wire can be used with

each speaker.

✦ The system tone volume can be adjusted with the

annunciator volume control.

1. Mount the external speaker.
2. Route the speaker wires from the external speaker to the Console.
3. Open the Console top cover and locate the main terminal block.
4. Route the speaker wires up through the wiring access hole.
5. Remove the wire jumper from the EXT. SPKR & (-) terminals.
6. Connect the speaker wires to the EXT. SPKR & (-) terminals.

CONNECT SPEAKER LEADS TO EXT. SPKR & (-) TERMINALS

✎ NOTEIf connecting two external speakers,

connect the second speaker in parallel, to the same EXT. SPKR & (-) terminals as the fi rst speaker.

Linear DVS-2400 — EXTERNAL CONSOLE SPEAKER CONNECTION diagram (page 11)
Fig. 17

EXTERNAL ALARM SIREN CONNECTION

✦ An external siren alerts occupants and neighbors

with a loud siren during alarm.

✦ Use a 12 volt, 1 amp maximum rated weather-

resistant horn speaker with a built-in siren driver. Do not use a plain speaker.

✎ NOTEConnection of an electromechanical bell or

motor bell is not recommended because of the radio interference generated when the bell is running.

AC AC EXT. SPKR (-) H/A - H/A + RELAY N.O. RELAY DRY

✎ UL NOTE: Not for use in UL installations.

1. Mount the external siren.
2. Route the wires from the external siren to the Console.
3. Open the Console top cover and locate the main terminal strip.
4. Route the siren wires up through the wiring access hole.
5. Connect the siren wires to the RELAY N.O. & (-) terminals.
✎ NOTEBy removing the Console’s auxiliary fuse,

the relay contacts will become isolated. Use the RELAY N.O. & RELAY DRY terminals to switch an externally powered load.

CONNECT SIREN LEADS TO (-) & RELAY N.O. TERMINALS

Page 12 of the Linear DVS-2400 user manual — POWER SOURCE
Page 12 · click to enlarge
Page 12

TELEPHONE LINE CONNECTION

Linear DVS-2400 — TELEPHONE LINE CONNECTION diagram (page 12)
Fig. 18

TELEPHONE

✦ Connect the Console to the telephone line if the

TERMINAL

system is monitored, requires 2-way audio, or requires telephone remote command.

✦ Telephone RING & TIP terminals are for connection

to the incoming telephone line.

✦ Seized telephone ring & tip are for connection

to local telephone sets. When the communicator activates, all the local telephone sets will be disconnected to prevent an off-hook telephone on the premises from blocking the communicator call.

SEIZED RING (R1) SEIZED TIP (T1)

LINE RING (R) LINE TIP (T)

1. Install a USOC RJ31-X or RJ38-X jack to the telephone system near the Console.
Linear DVS-2400 — SEIZED RING (R1) SEIZED TIP (T1) diagram (page 12)
Fig. 19
2. Route an appropriate modular telephone line cord from the jack to the Console.
3. Route the line cord through the Console’s wiring access hole.
4. Connect the incoming telephone line wires to the Console's telephone terminal block TIP and RING terminals.
8-POSITIO USOC RJ3 (OR RJ38- JACK

T R R1 T1 SHORTING BAR SHORT REMOVED ON PLUG INSERTION

5. Connect the local telephone set wires to the Console’s telephone terminal block SEIZED TIP and SEIZED RING terminals.

✦ When directly connecting (without a telephone line)

to the DVS-2400 with the RA-2400 remote access software (Version 1.3 or later), disconnect the incoming telephone line and connect the modem to the panel's TIP and RING terminals (with the modem's red & green phone line wires). Press the EMERGENCY key while in Test Mode to cause the panel to connect to the modem.

CONNECT TELEPHONE LINE TO THE TELEPHONE TERMINAL BLOCK

AUTOMATION OUTPUT CONNECTION (OPTIONAL)

Linear DVS-2400 — CONNECT TELEPHONE LINE TO THE TELEPHONE TERMINAL BLOCK diagram (page 12)
Fig. 20

✦ The Console provides a Automation Output to

MINUS H/A TERMINAL WILL SWITCH TO GROUND WHEN AUTOMATION OUTPUT IS ACTIVATED

control lights, devices and appliances.

✦ Automation Output can connect to most popular

AC AC EXT. SPKR (-) H/A - H/A + RELAY N.O. RELAY DRY

home automation devices and other simple electronic devices (see fi gure).

MAIN TERMINAL

✦ Press to turn the Automation Output on, press

BLOCK

again to turn it off.

POSITIVE H/A TERMINAL PROVIDES +12 VOLTS DC AND IS CURRENT LIMITED AT 30 MILLIAMPS MAXIMUM

✦ There are many programmable options for the

Automation Output.

✦ The Automation Output can be programmed for a

EXAMPLE AUTOMATION OUTPUT HOOK-UPS

variety of useful functions, such as: fl ashing during alarm, fl ashing after an alarm, on while armed, or, on during exit/entry delays.

X-10 BURGLAR ALARM INTERFACE (CAN CONTROL HOUSE LIGHTS THROUGH X-10 SYSTEM)

LINEAR RB-90 RELAY MODULE YOUR LOAD

LIGHT EMITTING DIODE (L.E.D.)

✦ See the “Advanced Programming” section of this

manual for details on changing the function of the Automation Output.

POWER SOURCE

H/A + H/A - H/A + H/A - H/A + H/A -

Programmable Options

Page 13 of the Linear DVS-2400 user manual — ✎ WARNING: DO NOT REVERSE THE BATTERY
Page 13 · click to enlarge
Page 13

CONSOLE POWER CONNECTION

Linear DVS-2400 — CONSOLE POWER CONNECTION diagram (page 13)
Fig. 21

✦ The Console is powered by a low voltage plug-in

transformer.

AC AC EXT. SPKR (-) H/A - H/A + RELAY N.O. RELAY DRY

✦ Use up to 25 feet of 20 AWG or larger

two-conductor wire to connect the transformer to the Console.

MAIN TERMINAL

BLOCK

1. Route the power wires from the plug-in transformer to the Console.
2. Connect the wires to the transformer terminals (do not plug the transformer in until the wiring is complete) .
Linear DVS-2400 — MAIN TERMINAL diagram (page 13)
Fig. 22
3. Route the power wires through the Console's wiring access hole.
4. Connect the power wires from the transformer to the Console's main terminal block AC & AC terminals.
5. Secure all of the wires entering the Console with a zip-tie to the Console’s strain relief loop.

CONNECT TRANSFORMER LEADS TO AC POWER TERMINALS

6. Plug transformer into an unswitched AC outlet.
7. Secure transformer with screw to prevent unplugging.
Linear DVS-2400 — CONNECT TRANSFORMER LEADS TO AC POWER TERMINALS diagram (page 13)
Fig. 23

PLUG TRANSFORMER INTO 115 VAC OUTLET THAT IS NOT CONTROLED BY A LIGHT SWITCH

BACKUP BATTERY INSTALLATION (OPTIONAL)

✦ A 12-volt backup battery may be installed and is

highly recommended.

✦ The backup battery will power the Console for up to

6 hours during AC power loss.

Linear DVS-2400 — BACKUP BATTERY INSTALLATION (OPTIONAL) diagram (page 13)
Fig. 24

✦ The backup battery is automatically charged by the

Console when AC power is present.

✦ A low backup battery will cause the Console POWER

indicator to fl ash as it is being charged.

1. To install the battery, slide the battery between the retaining clamps and under the battery holder.
2. Position the battery until the clamps snap in place. The battery terminals should be facing the center of the Console case bottom.
Linear DVS-2400 — BACKUP BATTERY INSTALLATION (OPTIONAL) diagram (page 13)
Fig. 25

CONNECT RED BATTERY LEAD TO RED TERMINAL CONNECT BLACK BATTERY LEAD TO BLACK TERMINAL

3. Connect the black battery lead to the negative battery terminal.
4. Connect the red battery lead to the positive battery terminal.

✎ WARNING: DO NOT REVERSE THE BATTERY

LEADS! THE BATTERY FUSE WILL BLOW.

Page 14 of the Linear DVS-2400 user manual — DONE
Page 14 · click to enlarge
Page 14

6. BASIC CONSOLE PROGRAMMING

✦ In a new installation, when power is fi rst applied

the system's master user code is “1234”.

CREATE THE MASTER USER CODE

✎ NOTELocal programming must be entered on

the Console's keypad, not on a wireless remote keypad.

ENTERING

SETTING A NEW MASTER

SETUP

MODE

USER CODE

1. Press (clears keypad if any other keys have been pressed).

START IN OFF

START IN SETUP

CLEARS KEYPAD

2. Place the Console in Test Mode (enter 1234 and press TEST .

PROGRAMMING STEP #99

✴ A “gong” and four “beeps” will sound. 3. Enter the Setup Mode from Test Mode, enter 1234 then press TEST again.

DEFAULT MASTER USER CODE

✴ A “gong” and fi ve “beeps” will sound. The system is now in

Test Mode. 4. Enter 99 then press HOME.

NEW MASTER USER CODE

5. Enter any combination of 1-5 digits for the master user code, then press AWAY .

1 GONG & 4 BEEPS (TEST MODE)

✎ NOTEFor maximum security, a three to fi ve digit

code is recommended.

6. Press and hold the OFF key for 3 seconds to exit program mode.

DEFAULT MASTER USER CODE

STORE CODE

7. Test the new master user code by entering it then pressing TEST .

HOLD FOR 3 SECONDS TO EXIT SETUP

8. Log the master user code in the box below.

1 GONG & 5 BEEPS (SETUP MODE)

MASTER USER CODE:

DONE

✎ NOTEThe master user code can be used to enter

Setup Mode. The restricted user codes cannot. To create restricted user codes, see the “Advanced Programming” section of this manual.

PROGRAM THE SENSORS INTO THE CONSOLE’S MEMORY

✦ Each wireless sensor that is going to be used

START IN TEST

with the Console must be programmed into the Console’s memory.

1. Start with the Console in Test Mode (enter any user code and press TEST ).

MASTER USER CODE

2. Enter the Setup Mode from Test Mode , enter the master user code then press TEST again.

✴ A “Gong” and fi ve “Beeps” will sound. ✴ The sensor status indicators will light for any sensors

programmed into the Console. 3. Enter an unused sensor number from 01-24 (you must enter two digits, example: 5 = 05).

1 GONG & 5 BEEPS

TEST

✴ The sensor indicator light will fl ash for the sensor number

NEW SENSOR NUMBER

selected. 4. Activate the sensor by sending a test or alarm signal (be sure the sensor's battery is connected or that its battery protection strip is removed).

✴ A single “Bing” tone will sound and the sensor status

ACTIVATE SENSOR

indicator for that sensor will stay lit.

5. Enter another sensor number or exit Setup Mode by pressing the OFF key for three seconds.

DONE

Page 15 of the Linear DVS-2400 user manual — LEFT = ARM/DISARM RIGHT = AUTOMATION
Page 15 · click to enlarge
Page 15

PROGRAMMING DIFFERENT SENSOR TYPES

Linear DVS-2400 — PROGRAMMING DIFFERENT SENSOR TYPES diagram (page 15)
Fig. 26

✦ Follow the instructions on the previous page to

select a sensor number to program the sensor into. ✎ NOTE: A sensor can be programmed into more

than one location. Be sure to choose an UNUSED sensor number. If a sensor gets entered into more than one location, delete the duplicates using the remove sensor function. ✦ To add DXS-10 wireless keypads, press and hold the

keypad's key until programmed into the Console. ✦ For DXS-31 and DXS-32 door/window sensors,

move the magnet away from the side of the sensor.

✎ IMPORTANT NOTEThe DXS-31 & DXS-32 door/

window sensors are pre-set at the factory for delayed burglary response. If the sensor is going to be used on a non-entry portal (window, sliding glass door, etc.) a jumper can be changed in the sensor to select instant response. The jumper should be changed before programming the sensor so the Console will assign the sensor to the proper sensor function. See the “Basic Sensor Installation” section of this manual or the sensor’s instructions for details on changing the jumper. ✦ For DXS-81, DXS-91, DXS-54, & DXS-73

accessory sensors, simply send a test transmission (refer to the sensor's instructions for details on sending a test transmission).

✦ For DXT-61, DXT-21, DXS-21, DXT-41, & DXS-62A

single-button remotes, simply press the unit's button. ✎ NOTE: After the Console recognizes the

transmitter, single-button remotes must be re-programmed as “panic buttons” or home automation controllers. Refer to the “Customizing the System” section of this manual. ✦ For DXT-23, DXS-23, & DXT-42 multi-button

remotes: Learn the transmitter by pressing the left button. The remote will arm the Console with the left button and disarm with the right button. Labels are provided with the DXT-42 for identifying the buttons. ✎ NOTE: After the Console “learns” the transmitter,

multi-button remotes can easily be re-programmed to have the left button arm/disarm the Console and the right button activate/deactivate the Home Automation output. Refer to the “Advanced Programming” section of this manual.

SEND SIGNAL WITH LEFT BUTTON

For All Models:

✴ A single “Bing” tone will sound and the sensor status

indicator will stay lit when the sensor is programmed into the Console. ✴ A “Buzz” tone will sound if there is already another sensor

programmed to that sensor number. ✦ Exit Setup Mode by pressing the key then press OFF for three seconds. Reminder: The Console will automatically exit the Setup Mode and return to Off Mode after three minutes of keypad inactivity.

LEFT = ARM/DISARM RIGHT = AUTOMATION

✎ NOTETo remove sensors from the Control Panel's

memory, see the “Customizing the System” section of this manual.

Page 16 of the Linear DVS-2400 user manual — WALL MOUNT USE
Page 16 · click to enlarge
Page 16

7. BASIC SENSOR INSTALLATION

✦ Each accessory sensor is packaged with its own

set of installation instructions specifi c to the model of sensor.

Linear DVS-2400 — 7. BASIC SENSOR INSTALLATION diagram (page 16)
Fig. 27

✦ Refer to the sensor's instructions for details on

installing, operating, and testing of the sensor.

FROM TOP OF CASE TWIST SCREWDRIVER BETWEEN CASE HALVES UNTIL IT POPS OPEN

✦ Following are basic instructions for installing two

popular DVS-2400 accessories: The Model DXS-10 Wireless Remote Keypad and the Model DXS-31 or DXS-32 Door/Window Transmitters.

DXS-10 WIRELESS KEYPAD

✦ The DXS-10 is used to remotely command the

Console.

✦ The keypad can be simply set on a table or

mounted to a fl at surface.

TABLE-TOP USE

✦ Four anti-mar pads are provided as a scratch

deterrent “feet” for the keypad.

✎ NOTEDo not use the adhesive “feet” if the keypad

is going to be wall mounted.

1. Peel off the adhesive tape backing on the pads and stick them to the back of the keypad.

✦ The wireless keypad can be used as a portable

keypad. Because of the hourly supervisory transmissions, if the unit is taken out of range from the Console for more than eight hours, the Console will indicate “radio trouble” for the keypad. The keypad's sensor number can be programmed for “non-supervised” if required. See the “Advanced Programming” section of this manual.

USE THE FOUR SCRATCH DETERRENT PADS PROVIDED FOR TABLE-TOP USE

Linear DVS-2400 — TABLE-TOP USE diagram (page 16)
Fig. 28

WALL MOUNT USE

✦ The wireless keypad can be wall mounted in a

convenient location.

1. Open the keypad by inserting a small screwdriver in one of the top slots in the keypad case. Gently twist the screwdriver until the case pops open.
2. Attach the rear case to the wall using the two screws provided.
✎ NOTEFor best signal transmission, the keypad

should be mounted at least three feet above ground level.

3. Hook the top edge of the keypad case together and snap the keypad onto the rear case.

ATTACH REAR CASE TO WALL WITH THE TWO SCREWS PROVIDED

✎ WARNINGThe wireless keypad is designed for

indoor use only.

MOUNT AT A CONVENIENT LOCATION NEAR PRIMARY ENTRY/EXIT DOOR

Page 17 of the Linear DVS-2400 user manual — TEST SENSORS
Page 17 · click to enlarge
Page 17

DXS-31 & DXS-32 DOOR/WINDOW SENSORS

EXAMPLE INSTALLATION (WITH DXS-31 SHOWN)

✦ The DXS-31 and DXS-32 sensors can be used

Linear DVS-2400 — DXS-31 & DXS-32 DOOR/WINDOW SENSORS diagram (page 17)
Fig. 29

to monitor doors, windows, cabinets, crawl space doors, gates, freezer doors, and many other moving objects that could be used for intrusion or need to be monitored.

✦ A built-in magnetic switch triggers the sensor when

its magnet (mounted on the moving part or the door or window) moves away from the sensor.

✦ The DXS-31 sensor can be wired to external

normally closed switches for remote triggering.

✦ The DXS-31 sensor can connect directly to a glass

break detector.

SET SENSOR JUMPER

✦ A jumper inside the door/window sensor selects

INSTANT/DELAY OPTION JUMPER

ANTENNA

instant or delayed response.

MAGNET ALIGNMENT MARK

INPUT SELECT JUMPER

TWO TYPE 2032 BATTERIES

1A. If the sensor is going to be used on the primary entry/exit door make sure that the jumper is in the DELAY position.

BATTERY CLAMP SCREW

TRANSMIT INDICATOR

1B. If the sensor is going to be used on a window or a door that is not going to be used to enter and exit the premises, set the jumper to the INSTANT position.

BATTERY CLAMP

TEST SWITCH

EXTERNAL INPUT TERMINALS

CHOOSE MOUNTING METHOD

INSTANT/DELAY OPTION JUMPER

2A. Apply double-stick tape (supplied) to back of sensors and magnets.

SELECTS INSTANT

2B. Screws are also provided to mount sensors and magnets. Screws are preferred over the double-stick tape in permanent installations.

✎ UL NOTEDouble-stick tape is not allowed in UL

SELECTS DELAY

installations.

ATTACH SENSORS AND MAGNETS

✦ Allow a maximum of 1/2" between magnet and

ATTACH MOUNTING PLATES USING THE SCREWS OR DOUBLE-STICK TAPE PROVIDED

sensor when door/window is closed.

✦ The magnet height is adjustable and an optional

magnet spacer is provided for uneven surfaces.

3B. On doors, mount sensor to door frame and magnet to door.

3B. On windows, mount sensor to window frame and magnet to window.

✎ NOTEMagnet must line up with mark on sensor

case both horizontally & vertically.

4. Snap sensor onto mounting plate.

TEST SENSORS

✴ In Chime Mode, the Console should “ding-dong” when the

Linear DVS-2400 — TEST SENSORS diagram (page 17)
Fig. 30

sensor sends a signal.

5. Open door or window.

✴ Verify that light on the sensor (if there is one) glows

momentarily when door/window is opened.

✴ Status indicator on the Console should remain lit for each

door/window sensor that is left open.

Page 18 of the Linear DVS-2400 user manual — LABELING THE SENSORS
Page 18 · click to enlarge
Page 18

8. CUSTOMIZING THE CONSOLE

Linear DVS-2400 — 8. CUSTOMIZING THE CONSOLE diagram (page 18)
Fig. 31

✦ The Console can be customized for the specifi c

✦ A label sheet with sensor location names is

identifi cation of where a door or window is open, where any alarms have occurred, where a sensor with a low battery is, or where a sensor with trouble is.

LABELING THE SENSORS

Linear DVS-2400 — LABELING THE SENSORS diagram (page 18)
Fig. 32
1. Use a paper clip to remove the clear display window.
2. Bend down the tabs on the sensor number card and fi t it onto the Console.
3. Open one protected door/window to light its sensor status light on the Console.
4. Choose a label that describes the sensor location, or write the location on a blank label, and stick it in the area to the right of the sensor light.
5. Close the protected opening that you just labeled.
6. Repeat for each protected opening.
7. Stick the WIRELESS KEYPAD label in the sensor number location for the wireless keypad (if used).
8. Replace the clear display window when fi nished.

OPEN DOOR OR WINDOW TO LIGHT SENSOR STATUS INDICATOR ON CONSOLE

APPLY SENSOR IDENTIFICATION LABELS TO THE APPROPRIATE SENSOR LOCATIONS

Linear DVS-2400 — LABELING THE SENSORS diagram (page 18)
Fig. 33
Page 19 of the Linear DVS-2400 user manual — 1 GONG & 1 BEEP
Page 19 · click to enlarge
Page 19

9. CONSOLE OPERATING MODES

OFF MODE

✦ Use this mode to disarm the burglary portion of the

system.

✦ Switching to Off Mode stops any alarms in

progress.

OFF MODE

✦ The 24-hour functions are still active in Off Mode

and can be triggered by pressing the FIRE or EMERGENCY button.

START HERE

1. Switch to Off Mode by entering the user code, and pressing OFF .

(OPTIONAL)

✴ When the system is disarmed to Off Mode, the Console will

sound one “Gong”.

YOUR USER CODE

✴ If an alarm has occurred, multiple Beeps will sound after

disarming and the sensor indicator for the sensor(s) that caused the alarm will fl ash.

✎ NOTEIn Off Mode, protected doors and windows

cannot trigger the burglary alarm.

1 GONG

OFF

DONE

CHIME MODE

CHIME MODE

START HERE

✦ Chime Mode is for monitoring entries and exits

without causing alarms.

(OPTIONAL)

✦ Use Chime Mode as an “automatic door chime”

when at home.

✴ Opening any protected door or window causes the Console

YOUR USER CODE

to sound a “ding-dong”.

1A. Select the Chime Mode by entering a user code, then press CHIME.

1B. The user can enter Chime Mode from Off Mode by pressing CHIME for two seconds.

1 GONG & 1 BEEP

✴ When the system is switched to the Chime Mode, the

CHIME

keypad(s) will sound a “Gong” and one “Beep”.

✦ Switching to Chime Mode disarms the system

DONE

and stops any alarms in progress.

✴ If an alarm has occurred, multiple Beeps will sound after

disarming and the sensor indicator for the sensor(s) that caused the alarm will fl ash.

START IN OFF

HOLD DOWN

✎ NOTEIn Chime Mode, protected doors and

CHIME

windows cannot trigger the burglary alarm.

1 GONG & 1 BEEP

DONE

Page 20 of the Linear DVS-2400 user manual — DONE
Page 20 · click to enlarge
Page 20

HOME MODE

MANUAL BYPASSING OF SENSORS

✦ Use this mode when sleeping or when anyone is

✦ Manual bypassing of sensors in the Home Mode

staying inside.

allows arming of the system at night with open windows, while still having perimeter protection with other closed doors and windows.

✦ Home Mode causes an instant alarm when any

perimeter sensor is triggered.

1. The Console will resist arming with open door or window sensors.

✦ Home Mode causes a delayed alarm when any exit/

entry sensor is triggered (except in Home Instant Mode when they are instant).

✴ Four high-low Beeps to warn the user that something is

open and the system will remain in the previous mode.

✦ Alarm siren stops automatically after fi ve minutes

and the system will remain armed.

✴ Lit sensor status indicators show which sensors are open.

✦ Home Mode ignores all interior sensors (motion

2. To manually bypass the open sensors, arm the system again within fi ve seconds.

detectors, etc.).

1A. Arm to Home Mode by entering a user code, and pressing HOME.

✴ A “Gong” and two “Beeps” will sound, the HOME indicator

will light, and the open sensors will be bypassed.

1B. The user can “Quick Arm” to Home Mode from Off or Chime Mode by pressing HOME for two seconds. (Quick arming can be disabled; see the “Advanced Programming” section of this manual.)

✎ WARNINGBypassed sensors cannot cause an

alarm. Closing the sensor removes the bypass.

✴ When the system is armed to the Home Mode, the

keypad(s) will sound a “Gong” and two “Beeps”.

2. Enter a user code and press OFF or CHIME to disarm from Home Mode and/or stop the alarm siren.

✴ If an alarm has occurred, multiple Beeps will sound after

disarming and the sensor indicator for the sensor(s) that caused the alarm will fl ash (switch to Off Mode again or re-arm the system to stop the fl ashing alarm memory light).

SECURE EXIT

HOME MODE

SECURE EXIT

1. If the system is already in the Home Mode and the user wants to exit the premises while leaving someone inside with the system still in Home Mode , enter a user code and press the HOME key.

START IN OFF OR CHIME MODE

START IN HOME MODE

(OPTIONAL)

(OPTIONAL)

✴ The HOME light will blink for 60 seconds. No exit delay

Beeps will sound during the Exit Delay.

2A. The user can leave through a door with a delayed perimeter sensor during the 60 second Exit Delay without causing the Console to begin an Entry Delay.

YOUR USER CODE

YOUR USER CODE

2B. Re-entering during the silent Exit Delay will extend the Exit Delay another 60 seconds (one time only).

1 GONG & 2 BEEPS

1 GONG & 2 BEEPS

✎ NOTEThe Exit Delay time can be changed; see the

“Advanced Programming” section of this manual.

HOME INSTANT MODE

DONE

DONE

1. If the system is already in the Home Mode and the user wants to make all exit/entry sensors instant, press HOME for two seconds.

✴ Two “Gongs” and two “Beeps” will sound and the HOME

HOME INSTANT

light will blink continuously.

QUICK ARM

MODE

START IN OFF OR CHIME MODE

2. Because all exit/entry sensors will now cause an instant alarm when in Home Mode, the Console must be disarmed before opening any exit/entry delay door.

START IN HOME MODE

HOLD DOWN HOME

HOLD DOWN

1 GONG & 2 BEEPS

2 GONGS & 2 BEEPS

✎ NOTEIf quick arming is disabled the Home Instant

Mode is unavailable.

DONE

DONE

Page 21 of the Linear DVS-2400 user manual — DONE
Page 21 · click to enlarge
Page 21

AWAY MODE

MANUAL BYPASSING OF SENSORS

✦ Use this mode when no one will be staying home.

✦ Manual bypassing of sensors in the Away Mode

✦ Each burglary sensor can trigger the siren once per

allows arming of the system with open doors and windows, while still having perimeter protection with other closed doors and windows.

arming period.

✦ Away Mode causes an instant alarm when any

1. The Console will resist arming with open door or window sensors.

perimeter sensor is triggered.

✦ Away Mode causes a delayed alarm when any

✴ Four high-low Beeps to warn the user that something is

exit/entry sensor is triggered.

open and the system will remain in the previous mode.

✦ Away Mode causes an instant alarm when any

✴ Lit sensor status indicators show which sensors are open.

interior sensors (motion detectors, etc.) are triggered. The interior sensors will be delayed if a perimeter delayed sensor is triggered fi rst.

2. To manually bypass the open sensors, arm the system again within fi ve seconds .

✦ Alarm siren stops automatically after fi ve minutes

✴ A “Gong” and three “Beeps” will sound, the AWAY indicator

and the system will remain armed.

will light, and the open sensors will be bypassed.

1A. Arm to Away Mode by entering a user code, and pressing AWAY.

✎ WARNINGBypassed sensors cannot cause an

alarm. Closing the sensor removes the bypass.

1B. The user can “Quick Arm” to Away Mode from Home, Chime or Off Mode by pressing AWAY for two seconds. (Quick arming can be disabled; see the “Advanced Programming” section of this manual.)

EXIT DELAY (For Leaving the Premises)

✴ When the system is armed to the Away Mode, the Console

will sound a “Gong” and three “Beeps”.

✴ During the 60 second Exit Delay, the Console will sound

AWAY MODE

“Beeps” (double Beeps last 10 seconds) and the AWAY light will blink.

START HERE

2A. The Exit Delay gives the user 60 seconds to leave the premises through an exit/entry door without triggering an alarm.

(OPTIONAL)

2B. Re-entering during the Exit Delay will extend the Exit Delay another 60 seconds (one time only).

✴ When the Exit Delay is over, the Console will sound one

YOUR USER CODE

“Gong” to warn the user that the system is fully armed.

✎ NOTEThe Exit Delay time can be changed; see the

“Advanced Programming” section of this manual.

ENTRY DELAY (For Entering the Premises) 3A. The Entry Delay gives the user 30 seconds to enter the premises through an exit/entry door without triggering an alarm.

1 GONG & 3 BEEPS

3B. If a exit/entry sensor is triggered, starting the Entry Delay, the interior sensors will also become delayed (this allows motion in the premises during the Entry Delay).

DONE

✴ During the 30 second Entry Delay, the Console will sound

QUICK ARM

“Beeps”.

4. When the Entry Delay is over, the Console will go into full alarm and sound the siren if it is not disarmed to the Off or Chime Mode.

START HERE

HOLD DOWN

✴ If an alarm has occurred while the user was gone, multiple

1 GONG & 3 BEEPS

Beeps will sound after disarming and the sensor light for the sensor(s) that caused the alarm will fl ash (switch to Off Mode again or re-arm the Console to stop the fl ashing alarm memory light).

DONE

✎ NOTEThe Entry Delay time can be changed; see the

“Advanced Programming” section of this manual.

Page 22 of the Linear DVS-2400 user manual — TEST MODE
Page 22 · click to enlarge
Page 22

TEST MODE

✎ NOTEIf the Console is left unattended in Test

Mode, it will automatically switch back to Off Mode after three minutes.

✦ Even though this is a self-monitoring supervised

system, the National Burglar and Fire Alarm Association recommends that all security systems should be tested manually on a regular basis.

✦ When directly connecting (without a telephone

line) to the DVS-2400 with the RA-2400 remote access software (Version 1.3 or later), press the EMERGENCY key while in Test Mode to cause the Console to connect to the modem.

1. The Console must be in Off Mode before switching to Test Mode.
2. Switch the Console into Test Mode by entering a user code and pressing TEST .

✴ When the system is switched to the Test Mode, the Console

will sound a “Gong” and four “Beeps”.

TEST MODE

3. Holding down the TEST button in Test Mode will light all of the Console’s indicators.
Linear DVS-2400 — TEST MODE diagram (page 22)
Fig. 34

✴ The sensor status indicators will fl ash for each sensor

programmed into the Console.

4. Go to each sensor and press its test button or open and close the protected opening.
5. To test the wireless keypad, press the wireless keypad’s key.

✴ The Console will make a “Bing” sound as each sensor is

tested, followed by 1-3 beeps indicating signal strength with 3 beeps being the strongest signal.

✴ As each sensor is tested, the sensor status indicator for the

sensor will stop fl ashing and return to showing the current status of the sensor.

6. Continue testing until there are no fl ashing sensor status indicators.
Linear DVS-2400 — TEST MODE diagram (page 22)
Fig. 35

SENSOR TYPE OFF MODE CHIME MODE HOME MODE AWAY MODE

2-BUTTON ARM/DISARM (LEFT) 2-BUTTON AUTOMATION (RIGHT) EMERGENCY (BOTH BUTTONS)

LEFT BUTTON SWITCHES SYSTEM TO AWAY MODE † IF ALARM MEMORY IS ACTIVE, SWITCHES SYSTEM TO OFF MODE ‡ LEFT BUTTON SWITCHES SYSTEM TO OFF MODE ‡

2-BUTTON ARM (LEFT) 2-BUTTON DISARM (RIGHT) EMERGENCY (BOTH BUTTONS)

LEFT BUTTON SWITCHES SYSTEM TO AWAY MODE † IF ALARM MEMORY IS ACTIVE, SWITCHES SYSTEM TO OFF MODE ‡ RIGHT BUTTON SWITCHES SYSTEM TO OFF MODE ‡

† CAN BE HOME MODE USING PROGRAMMING STEP 50

‡ CAN BE CHIME MODE USING PROGRAMMING STEP 51 Console Zone Table

Page 23 of the Linear DVS-2400 user manual — TROUBLE INDICATOR
Page 23 · click to enlarge
Page 23

10. SYSTEM TROUBLE INDICATIONS

✦ The DVS-2400 Console is a self-monitoring

supervised wireless system.

✦ If the Console detects a problem with any of the

supervised system sensors or with its power, it will display the appropriate trouble indication and, if monitored, report the trouble to the Central Station through the communicator (depending on communicator programming).

CONSOLE LOW BATTERY

✦ The Console constantly charges and monitors the

optional backup battery (if installed).

POWER INDICATOR

Linear DVS-2400 — POWER INDICATOR diagram (page 23)
Fig. 36

✦ If the backup battery condition is abnormal, the

ON WITH AC POWER AND CHARGED BACKUP BATTERY

Console's POWER light will indicate the trouble.

BLINKS WITH LOW, RECHARGING OR MISSING BACKUP BATTERY

✴ The POWER indicator normally glows when AC power is on.

✴ With a charged backup battery installed, if the Console

DIM WHEN AC POWER IS ABSENT AND CONSOLE IS RUNNING ON BACKUP BATTERY

looses AC power, the POWER indicator will dim as the Console runs on the backup battery.

✴ If the backup battery is low, recharging, or not installed, the

POWER indicator blinks when AC power is present.

✴ If the AC power is off and no backup battery is installed, the

POWER indicator will be off (in this case, the system has no power and is disabled).

✦ Normal battery life for the type of backup battery

used in the Console is 3-4 years. If the battery does not take a charge in 72 hours, it should be replaced.

SENSOR LOW BATTERIES

✴ If the BATTERIES indicator on the Console blinks, one or

more sensors have a low battery.

BATTERIES INDICATOR

BLINKS WHEN ONE OR MORE SENSORS HAVE A LOW BATTERY

1. Press for one second to view sensor status. The sensor status indicator for any sensor with a low battery will light along with the BATTERIES indicator. Any trouble indications will follow during the fi ve second status cycle.

LIGHTS WITH SENSOR INDICATOR DURING LOW BATTERY STATUS CHECK (PRESS FOR 1 SECOND)

2. Replace the sensor's battery as described in its instructions.
3. Switch to Test Mode after replacing the sensor battery and completely test the system (see Test Mode). Switching to Test Mode clears the low battery indication.

SENSOR RADIO TROUBLE

✴ When the TROUBLE indicator blinks, one or more sensors

TROUBLE INDICATOR

have not reported status during the eight hour status time window.

BLINKS WHEN ONE OR MORE SENSORS HAVE NOT REPORTED STATUS DURING THE EIGHT HOUR STATUS TIME WINDOW

1. Press for one second to view sensor status. The sensor status indicator for any sensor that has not reported in will light along with the TROUBLE indicator. Any low battery indications will follow during the fi ve second status cycle.

LIGHTS WITH SENSOR INDICATOR DURING TRANSMITTER STATUS CHECK (PRESS FOR 1 SECOND)

2. Switch to Test Mode after servicing the sensor and completely test the system (see Test Mode). Switching to Test Mode clears the trouble indication.
Page 24 of the Linear DVS-2400 user manual — DONE
Page 24 · click to enlarge
Page 24

11. CUSTOMIZING THE SYSTEM

✦ Adding additional sensors will increase the

protection provided by the system.

✦ All ground-level perimeter openings and accessible

upper-story openings need protection.

✦ Motion detectors can protect interior areas and

areas where valuables are kept.

ADDING SENSORS TO THE SYSTEM

1. Always start with the Console in Test Mode (enter a user code and press TEST ).
2. Enter the master user code then press TEST .

START IN TEST

✴ A “Gong” and fi ve “Beeps” will sound.

✴ The sensor status indicators will light for each sensor

programmed into the Console.

MASTER USER CODE

3. Enter an unused sensor number from 01-24 (you must enter two digits, example: 5 = 05).
✎ NOTEA sensor can be programmed into more

than one location. Be sure to choose an UNUSED sensor number. If a sensor gets entered into more than one location, delete the duplicates using the remove sensor function.

1 GONG & 5 BEEPS

TEST

✴ The sensor status indicator light will fl ash for the sensor

number selected.

NEW SENSOR NUMBER

4. Activate the sensor. (To add a wireless keypad, press the keypad's key.)

✴ A “Bing” tone will sound when the sensor is programmed

ACTIVATE SENSOR

into the Console and the sensor status indicator will stay lit.

✴ A “Buzz” tone will sound if there is already another sensor

programmed to that sensor number.

DONE

5. Enter another sensor number, or exit Setup Mode by pressing the key then press OFF for three seconds.

REMOVING SENSORS FROM THE SYSTEM

✦ If a previously programmed sensor isn't going to be

used with the system anymore, or it's a duplicate that has been entered into more than one sensor location, it should be removed from the Console's memory.

START IN TEST

1. Start with the Console in Test Mode.

MASTER USER CODE

2. Enter the master user code then press TEST .

✴ A “Gong” and fi ve “Beeps” will sound.

✴ The sensor status indicators will light for each sensor

programmed into the Console.

1 GONG & 5 BEEPS

3. Enter the sensor number (from 01-24) that you want to remove (you must enter two digits, example: 5 = 05).

TEST

✴ The sensor status indicator light will fl ash for the sensor

SENSOR NUMBER TO REMOVE

number selected.

4. Press TEST .

✴ A “Bing” tone will sound when the sensor has been removed

TEST 1 BING

and the sensor status indicator will turn off.

5. Enter another sensor number, or exit Setup Mode by pressing the key then press OFF for three seconds.

DONE

Page 25 of the Linear DVS-2400 user manual — DONE
Page 25 · click to enlarge
Page 25

MAKING A SENSOR A 24-HOUR DOOR CHIME

START IN TEST

✦ Sensors can be programmed to cause the Console

to chime any time they're activated.

✦ Chime-only sensors will not be able to trigger the

alarm in any Console mode.

MASTER USER CODE

✦ The sensor must have already been programmed

into the Console (see “Adding Sensors to the System” for details).

1. Start with the Console in Test Mode.
2. Enter the master user code then press TEST .

1 GONG & 5 BEEPS

TEST

✴ A “Gong” and fi ve “Beeps” will sound.

✴ The sensor status indicators will light for each sensor

SENSOR NUMBER FOR CHIME

programmed into the Console.

3. Enter the sensor number from 01-24 (you must enter two digits, example: 5 = 05).

✴ The sensor status indicator light will fl ash for the sensor

number selected.

4. Press HOME , 8 , then AWAY .

8 TUV 8 FOR CHIME ZONE

✴ A “Bing” tone will sound and the sensor status indicator will

light steady.

5. Enter another sensor number, or exit Setup Mode by pressing the key then press OFF for three seconds.

1 BING

DONE

MAKING A SENSOR INTERIOR

✦ Wireless motion detectors are automatically

programmed as interior sensors. Any other sensor can also be programmed as an interior sensor.

START IN TEST

✦ Interior sensors can only trigger an alarm when the

Console is in the Away Mode.

MASTER USER CODE

✦ “Home Interior” sensors can trigger an alarm when

the Console is in the Home or Away mode.

✦ The sensor must have already been programmed

into the Console (see “Adding Sensors to the System” for details).

1 GONG & 5 BEEPS

TEST

1. Start with the system in Test Mode.
2. Enter the master user code then press TEST .

SENSOR NUMBER FOR INTERIOR

✴ A “Gong” and fi ve “Beeps” will sound.

✴ The sensor status indicators will light for each sensor

programmed into the Console.

3. Enter the sensor number from 01-24 (you must enter two digits, example: 5 = 05).

✴ The sensor status indicator light will fl ash for the sensor

number selected.

7 FOR INTERIOR ZONE

7 PRS

4. Press HOME , 7 , then AWAY .

✴ A “Bing” tone will sound and the sensor status indicator will

light steady.

1 BING

5. Enter another sensor number, or exit Setup Mode by pressing the key then press OFF for three seconds.

DONE

Page 26 of the Linear DVS-2400 user manual — MAKING A SENSOR PERFORM A DIFFERENT FUNCTION
Page 26 · click to enlarge
Page 26

MAKING A SENSOR PERFORM A DIFFERENT FUNCTION

✦ Sensors can be reprogrammed to perform different

Linear DVS-2400 — MAKING A SENSOR PERFORM A DIFFERENT FUNCTION diagram (page 26)
Fig. 37

sensor functions.

✦ The sensor must have already been programmed

into the Console (see “Adding sensors to the System” for details).

1. Start with the Console in Test Mode.
2. Enter the master user code then press TEST .

✴ A “Gong” and fi ve “Beeps” will sound.

✴ The sensor status indicators will light for each sensor

programmed into the Console.

3. Enter the sensor number from 01-24 (you must enter two digits, example: 5 = 05).

✴ The sensor status indicator light will fl ash for the sensor

number selected.

4. Choose a sensor function number from the Sensor Function Table.
5. Press HOME , the new sensor function number, then AWAY .

✴ A “Bing” tone will sound and the sensor status indicator will

light steady.

6. Enter another sensor number or exit Setup Mode by pressing the key then press OFF for three seconds.
Linear DVS-2400 — MAKING A SENSOR PERFORM A DIFFERENT FUNCTION diagram (page 26)
Fig. 38

FUNC- TION # SENSOR FUNCTION OFF MODE CHIME MODE HOME MODE AWAY MODE

3 PANIC ARMED 24-HOURS - TRIGGERS SILENT PANIC ALARM

INSTANT BURGLARY ALARM UNLESS ACTIVATED DURING AN ENTRY DELAY, THEN IT IS

9 2-BUTTON ARM/DISARM (LEFT) 2-BUTTON AUTOMATION (RIGHT) EMERGENCY (BOTH BUTTONS)

LEFT BUTTON SWITCHES SYSTEM TO AWAY MODE † IF ALARM MEMORY IS ACTIVE, SWITCHES SYSTEM TO OFF MODE ‡ LEFT BUTTON SWITCHES SYSTEM TO OFF MODE ‡

10 2-BUTTON ARM (LEFT) 2-BUTTON DISARM (RIGHT) EMERGENCY (BOTH BUTTONS)

LEFT BUTTON SWITCHES SYSTEM TO AWAY MODE † IF ALARM MEMORY IS ACTIVE, SWITCHES SYSTEM TO OFF MODE ‡ RIGHT BUTTON SWITCHES SYSTEM TO OFF MODE ‡

SENSOR FUNCTION TABLE † CAN BE HOME MODE USING PROGRAMMING STEP 50

‡ CAN BE CHIME MODE USING PROGRAMMING STEP 51

Page 27 of the Linear DVS-2400 user manual — 87 REMOTE ACCESS PASSWORD 6 DIGITS 987654
Page 27 · click to enlarge
Page 27

12. ADVANCED PROGRAMMING

✦ To perform any of the advanced programming

SETUP MODE

steps, the Console must be in the Setup Mode.

1. Start with the Console in Test Mode (Setup Mode cannot be reached from any other mode).

✦ Each programming function is performed with

similar keystrokes. After the Console is in Setup Mode, enter the programming step number, press HOME, then enter the new value and press AWAY. For reference, follow the fi gures next to the programming steps.

2. From Test Mode, enter the master user code then press TEST .
✎ NOTEOnly the master user code can be used to

put the system into the Setup Mode. The restricted user codes cannot access Setup Mode, only Code Mode.

✴ If the new value is accepted, a “bing” will sound. If the new

value is not accepted, a “double buzz” will sound.

✴ A “Gong” and fi ve “Beeps” will sound, signaling that the

system is in Setup Mode.

Linear DVS-2400 — SETUP MODE diagram (page 27)
Fig. 39
3. After programming changes are complete, press the OFF key for three seconds to exit Setup Mode.
✎ NOTEIf the system is left unattended in Setup

Mode, it will automatically switch back to Off Mode after three minutes.

CONSOLE PROGRAMMING OPTIONS

STEP # PROGRAMMING FUNCTIONS POSSIBLE VALUES FACTORY VALUE INSTALLATION VALUE

25 ENTRY DELAY 20-255 SECONDS 30

26 EXIT DELAY 20-255 SECONDS 60

30 BURGLARY SIREN TIME 1-30 MINUTES 5

31 EMERGENCY SIREN TIME 1-30 MINUTES 5

32 FIRE SIREN TIME 1-30 MINUTES 5

40 AUTOMATION OUTPUT TIME 0-2500 SECONDS (0 = TOGGLE ON/OFF) 0

50 REMOTE ARMING MODE 2 = HOME MODE; 3 = AWAY MODE 3

51 REMOTE DISARMING MODE 0 = OFF MODE; 1 = CHIME MODE 0

61 ENTRY DELAY BEEPS 0 = OFF; 1 = ON 1

62 EXIT DELAY BEEPS 0 = OFF; 1 = ON 1

63 SILENT BURGLARY ALARM 0 = AUDIBLE; 1 = SILENT 0

64 SILENT EMERGENCY ALARM 0 = AUDIBLE; 1 = SILENT 0

65 QUICK ARMING 0 = OFF; 1 = ON 1

66 AUTO RESTORE 0 = OFF; 1 = ON 1

67 AUTO BYPASS 0 = OFF; 1 = ON 0

68 AUTOMATION MODE DURING ALARM 0 = FLASH (ENABLED BY FUNCTION 72) 1 = STEADY (ENABLED BY FUNCTION 72) 0

69 AUTOMATION BING TOME 0 = NO BINGS 1 = BINGS 1

70 REMOTE ARM/DISARM CHIRP 0 = NO CHIRPS 1 = CHIRPS (1 CHIRP = ARMED, 2 CHIRPS = DISARMED) 1

71 AUTOMATION FLASHES AFTER ALARM 0 = STANDARD 1 = FLASHING AFTER ALARM 0

0 = STANDARD 1 = AUTOMATION ACTIVE DURING ALARM (FLASH OR STEADY PROGRAMMED BY FUNCTION 68)

72 AUTOMATION ACTIVE DURING ALARM

73 AUTOMATION ON WHILE ARMED 0 = STANDARD 1 = ON WHILE ARMED 0

74 AUTOMATION ON DURING EXIT/ENTRY 0 = STANDARD 1 = ON DURING EXIT/ENTRY DELAY 0

75 AUTOMATION POLARITY 0 = + WHEN OFF; 1 = + WHEN ON 1

87 REMOTE ACCESS PASSWORD 6 DIGITS 987654

92 DURESS CODE 1-5 DIGITS REMOVED

93 RESTRICTED USER CODE #1 1-5 DIGITS REMOVED

94 RESTRICTED USER CODE #2 1-5 DIGITS REMOVED

95 RESTRICTED USER CODE #3 1-5 DIGITS REMOVED

96 RESTRICTED USER CODE #4 1-5 DIGITS REMOVED

97 RESTRICTED USER CODE #5 1-5 DIGITS REMOVED

98 PAGE ALERT USER CODE 1-5 DIGITS REMOVED

99 MASTER USER CODE 1-5 DIGITS 1234

Console Programming Table

Page 28 of the Linear DVS-2400 user manual — TIME IN MINUTES (1-30)
Page 28 · click to enlarge
Page 28

CHANGING A SENSORS SUPERVISION

✦ When a sensor is programmed, the Console

SENSOR NUMBER TO CHANGE

automatically recognizes it as supervised or non-supervised.

✦ The Console expects hourly status transmissions

from any sensor programmed as supervised.

16 FOR NON-SUPERVISED 17 FOR SUPERVISED

✦ Any sensor can be programmed as supervised or

non-supervised.

✎ NOTEDon't program a sensor that doesn't send

status transmissions as supervised.

CHANGING A SENSORS RESTORE REQUIREMENTS

✦ When a sensor is programmed, the Console

automatically recognizes it as manual or automatic restoring.

SENSOR NUMBER TO CHANGE

✦ The Console expects restoral signals from any

wireless sensor programmed as manual restore.

18 FOR MANUAL RESTORE 19 FOR AUTO RESTORE

✦ Any sensor can be programmed as manual or

automatic restore.

✎ NOTEDon't program a sensor that doesn't send

restoral transmissions as manual restore.

ENTRY DELAY TIME

✦ The factory-set Entry Delay time is 30 seconds.

PROGRAMMING STEP #25

STEP #25 The Entry Delay time can be adjusted from 20 to

JKL

255 seconds using this step.

❑ Write the new Entry Delay time in the User's Guide.

TIME IN SECONDS (20-255)

✎ NOTEDon't make the Entry Delay too short. The

user may not have enough time to disarm the system before an alarm.

EXIT DELAY TIME

✦ The factory-set Exit Delay time is 60 seconds.

PROGRAMMING STEP #26

STEP #26 The Exit Delay time can be adjusted from 20 to 255

seconds using this step.

❑ Write the new Exit Delay time in the User's Guide.

TIME IN SECONDS (20-255)

BURGLARY SIREN TIME

✦ The factory-set burglary siren time is fi ve minutes

3 DEF

PROGRAMMING STEP #30

(UL installation maximum).

STEP #30 The burglary siren time can be adjusted from one to

30 minutes using this step.

TIME IN MINUTES (1-30)

EMERGENCY SIREN TIME

3 DEF

✦ The factory-set emergency siren time is fi ve

PROGRAMMING STEP #31

minutes (UL installation maximum).

STEP #31 The emergency siren time can be adjusted from

one to 30 minutes using this step.

TIME IN MINUTES (1-30)

Page 29 of the Linear DVS-2400 user manual — PROGRAMMING STEP #62
Page 29 · click to enlarge
Page 29

FIRE SIREN TIME

3 DEF

✦ The factory-set fi re siren time is fi ve minutes (UL

PROGRAMMING STEP #32

installation maximum).

2 ABC

STEP #32 The fi re siren time can be adjusted from one to 30

minutes using this step.

TIME IN MINUTES (1-30)

AUTOMATION OUTPUT TIME

✦ The factory setting causes the Automation Output

4 GHI

PROGRAMMING STEP #40

to toggle between on and off with each activation.

STEP #40 The Automation Output can be programmed to turn

on, then automatically turn off after one to 2500 seconds (42 minutes), or toggle on & off, using this step.

TIME IN SECONDS (1-2500) 0 = TOGGLE ON & OFF

REMOTE CONTROL ARMING LEVEL

✦ The factory setting causes the portable remote

5 JKL

controls to arm to the Away Mode.

PROGRAMMING STEP #50

STEP #50 The portable remote controls can be changed to

arm to the Home Mode using this step.

2 FOR HOME MODE 3 FOR AWAY MODE

✎ NOTEChanging this setting will affect all the

portable remote controls used with the system.

REMOTE CONTROL DISARMING LEVEL

✦ The factory setting causes the portable remote

5 JKL

controls to disarm to the Off Mode.

PROGRAMMING STEP #51

STEP #51 The remote controls can be changed to disarm to

the Chime Mode using this step.

0 FOR OFF MODE 1 FOR CHIME MODE

✎ NOTEChanging this setting will affect all the

portable remote controls used with the system.

ENTRY DELAY BEEPS

✦ The factory setting causes the Console to beep

6 MNO

PROGRAMMING STEP #61

during Entry Delays.

STEP #61 The Entry Delay beeps can be silenced using this

step.

0 FOR ENTRY BEEPS OFF 1 FOR ENTRY BEEPS ON

✦ With the Entry Delay beeps off, the Console will be

silent after a delayed sensor is triggered until the Entry Delay expires, then the alarm siren will sound.

EXIT DELAY BEEPS

✦ The factory setting causes the Console to beep

6 MNO

during Exit Delays.

PROGRAMMING STEP #62

2 ABC

STEP #62 The Exit Delay beeps can be silenced using this

step.

0 FOR EXIT BEEPS OFF 1 FOR EXIT BEEPS ON

✦ With the Exit Delay beeps off, the Console will be

silent after arming to the Away Mode until the Exit Delay expires, then a single “Gong” tone will sound.

Page 30 of the Linear DVS-2400 user manual — 7 PRS
Page 30 · click to enlarge
Page 30

SILENT BURGLARY ALARMS

✦ The factory setting causes audible burglary alarms.

6 MNO

STEP #63 The Console can be programmed for silent burglary

PROGRAMMING STEP #63

3 DEF

alarms using this step.

0 FOR AUDIBLE BURG 1 FOR SILENT BURG

SILENT EMERGENCY ALARMS

✦ The factory setting causes audible emergency

6 MNO

alarms.

PROGRAMMING STEP #64

4 GHI

STEP #64 The Console can be programmed for silent

emergency alarms using this step.

0 FOR AUDIBLE EMERGENCY 1 FOR SILENT EMERGENCY

DISABLING QUICK ARMING

✦ The factory setting allows quick arming of the

Console by pressing down the mode keys for two seconds.

6 MNO

PROGRAMMING STEP #65

STEP #65 The Console can be programmed to not allow quick

5 JKL

arming using this step. If quick arming is disabled, a user code must be entered before pressing the mode buttons.

0 FOR QUICK ARMING OFF 1 FOR QUICK ARMING ON

✎ NOTEFor commercial installations with retail

traffi c, it is recommended to disable quick arming to prevent customers from arming the system. ✎ NOTE: If quick arming is disabled the Home Instant

Mode is unavailable.

AUTOMATIC RESTORAL OF BYPASSED SENSORS

✦ Bypassed sensors are ignored by the Console and

cannot cause an alarm.

✦ The factory setting causes the Console to

6 MNO

automatically restore (remove the bypass from) sensors that close. After it's restored, the sensor is ready to cause an alarm the next time it is opened.

PROGRAMMING STEP #66

6 MNO

STEP #66 The Console can be programmed to not

0 FOR AUTO RESTORAL OFF 1 FOR AUTO RESTORAL ON

automatically restore any bypassed sensor when the sensor closes using this step. Bypassed sensors will then remain bypassed until the system is disarmed.

✎ NOTE: This setting affects all sensors.

AUTOMATIC BYPASSING OF OPEN SENSORS

✦ The factory setting requires the user to manually

bypass any open sensors when the system is armed.

6 MNO

PROGRAMMING STEP #67

✴ If arming is attempted with open sensors, the Console will

7 PRS

sound fi ve two-tone Beeps and will not arm.

✦ Arming to the same mode again within fi ve seconds

0 FOR AUTO BYPASS OFF 1 FOR AUTO BYPASS ON

will bypass any open sensors and arm the Console.

STEP #67 The Console can be programmed to automatically

bypass any open sensors when the system is armed using this step.

✎ NOTE: This setting affects all sensors.

Page 31 of the Linear DVS-2400 user manual — 2 ABC
Page 31 · click to enlarge
Page 31

AUTOMATION OUTPUT MODE DURING ALARM

✦ The factory setting causes the Automation Output

6 MNO

to fl ash if it is programmed to activate during or after an alarm.

PROGRAMMING STEP #68

8 TUV

✎ NOTEFor the Automation Output to activate

during or after an alarm, that function must be enabled with Programming Step 71 or 72. STEP #68 The output can be programmed to be a steady

0 FOR FLASHING OUTPUT ON ALARM 1 FOR STEADY OUTPUT ON ALARM

output using this step.

AUTOMATION ACTIVATION TONE

✦ The factory setting causes the Console to sound a

6 MNO

“Bing” when the Automation Output is activated by pressing the key, or when it's triggered with a two-button remote control.

PROGRAMMING STEP #69

9 WXY

STEP #69 This sound can be silenced using this step.

0 FOR BING TONE OFF 1 FOR BING TONE ON

REMOTE CONTROL ARM/DISARM CHIRP

✦ When arming with the portable remote control, the

factory setting causes the Console to “chirp” once when armed, twice when disarmed, and three times when arming with sensors bypassed.

7 PRS

PROGRAMMING STEP #70

STEP #70 These chirps can be silenced using this step.

0 FOR CHIRPS OFF 1 FOR CHIRPS ON

✎ NOTEIf these chirps are silenced, it is

recommended to program the Automation Output to be active when the system is armed, so a light can be triggered displaying the arming status of the Console.

AUTOMATION OUTPUT ON DURING AND AFTER ALARM

✦ The factory setting causes the Console's

Automation Output to activate when pressing the

7 PRS

key, or when it's triggered with a two-button remote control.

PROGRAMMING STEP #71

STEP #71 The Console can be programmed to activate the

0 FOR STANDARD TRIGGER 1 FOR FLASHING DURING & AFTER ALARM

Automation Output during and after any alarms as well as when normally triggered using this step.

✎ NOTEThe output will continue until the fl ashing

sensor status lights are cleared.

AUTOMATION OUTPUT ON DURING ALARM

✦ The factory setting causes the Console's

Automation Output to activate when pressing the

7 PRS

PROGRAMMING STEP #72

key, or when it's triggered with a two-button remote control.

2 ABC

STEP #72 The Console can be programmed to activate the

0 FOR STANDARD TRIGGER 1 FOR OUTPUT DURING ALARM

Automation Output during alarms as well as when normally triggered using this step.

✎ NOTEThe Automation Output can be programmed

to fl ash or be steady during alarm, see Programming Step 68.

Page 32 of the Linear DVS-2400 user manual — MASTER USER CODE:
Page 32 · click to enlarge
Page 32

AUTOMATION OUTPUT WHILE ARMED

✦ The factory setting causes the Console's

7 PRS

Automation Output to activate when pressing the

PROGRAMMING STEP #73

3 DEF

key, or when it's triggered with a two-button remote control.

STEP #73 The Console can be programmed to activate the

0 FOR STANDARD TRIGGER 1 FOR OUTPUT WHEN ARMED

Automation Output when the system is armed as well as when normally triggered using this step.

AUTOMATION OUTPUT DURING EXIT/ENTRY DELAYS

✦ The factory setting causes the Console's

7 PRS

Automation Output to activate when pressing the

PROGRAMMING STEP #74

4 GHI

key, or when it's triggered with a two-button remote control.

0 FOR STANDARD TRIGGER 1 FOR OUTPUT DURING EXIT/ENTRY DELAYS

STEP #74 The Console can be programmed to activate the

Automation Output during the exit and Entry Delays as well as when normally triggered using this step.

AUTOMATION OUTPUT POLARITY

✦ The factory setting causes the Console's

7 PRS

Automation Output to provide a current limited voltage source when activated.

PROGRAMMING STEP #75

5 JKL

STEP #75 The Console can be programmed so the

Automation Output provides a current limited voltage source when deactivated using this step.

0 FOR VOLTAGE WHEN OFF 1 FOR VOLTAGE WHEN ON

REMOTE ACCESS PASSWORD

✦ This password is used to gain access to the Console

8 TUV

PROGRAMMING STEP #87

when using the RA-2400 remote access software. The password must be 6-digits long.

7 PRS

STEP #87 Use this step to enter a new remote access

password then log the password in the box below.

6-DIGIT REMOTE ACCESS PASSWORD

REMOTE ACCESS PASSWORD:

DURESS CODE

9 WXY

✦ The duress code will disarm the system, without

PROGRAMMING STEP #92

2 ABC

any special indications or sounds, but will send the programmed duress code to the Central Station. The code should be two or more digits different than any user code

1-5 DIGIT DURESS CODE (3-5 DIGITS RECOMMENDED)

STEP #92 Use this step to enter the duress code then log the

code in the box below.

DURESS CODE:

MASTER USER CODE

✦ The master user code is 1234 when power is fi rst

9 WXY

PROGRAMMING STEP #99

applied to the Console.

9 WXY

✦ The master user code can be changed to any 1-5

digit code. Only the master user can access Setup Mode, restricted users cannot.

1-5 DIGIT MASTER CODE (3-5 DIGITS RECOMMENDED)

✎ NOTEFor maximum security, a 3-5 digit code is

recommended. STEP #99 Use this step to enter the new master user code

then log the code in the box below.

MASTER USER CODE:

Page 33 of the Linear DVS-2400 user manual — TEST
Page 33 · click to enlarge
Page 33

ADDING ADDITIONAL USER CODES

PROGRAMMING STEPS #93 TO 98

✦ The Console can be programmed with fi ve restricted

user codes and one page alert user code.

✦ The restricted user codes operate the system as

usual, but cannot access Setup Mode.

1-5 DIGIT CODE (3-5 DIGITS RECOMMENDED)

✦ The restricted user codes can access a special

Code Mode that can be used to change or remove any of the fi ve restricted user codes, the page alert user code, or the duress code.

✦ The page alert user code dials the supervisory

number (programmed for a pager) when it is used to arm or disarm the system.

STEP CODE FUNCTION CODE ENTERED

STEP #93 RESTRICTED USER CODE #1

STEP #94 RESTRICTED USER CODE #2

✦ A restricted user code is appropriate to give any

STEP #95 RESTRICTED USER CODE #3

user that should be restricted from programming the Console.

STEP #96 RESTRICTED USER CODE #4

✎ NOTEFor maximum security, a 3-5 digit code is

STEP #97 RESTRICTED USER CODE #5

recommended. ✎ WARNINGNEVER PROGRAM ANY RESTRICTED

STEP #98 PAGE ALERT USER CODE

USER CODE THE SAME AS THE MASTER USER CODE! STEPS #93-98 Create any additional user codes using these

steps then log the codes in the boxes to the right.

REMOVING ADDITIONAL USER CODES

KEYPAD CODE PROGRAMMING STEPS #92 TO 98

STEPS #93-98 Any additional user code can be removed

9 WXY

from the Console by entering the appropriate step number and pressing TEST. ✦ Because access to programming would be impossible

TEST

REMOVE

without a master user code, it cannot be removed using these steps. The master user code can be changed using programming STEP #99. ✎ NOTE: The master user code can be set to the

factory default using the Console master reset programming step, although all other system programming will be reset to factory values and all sensors programmed will be erased.

CONSOLE MASTER RESET

START IN TEST

✦ Master resetting the Console will set all of the

programming options back to the factory values. The master user code will be reset to 1234.

MASTER USER CODE

✎ CAUTIONMaster resetting the Console will erase the

user codes and remove all programmed sensors. All Console and communicator programming values will be reset to the factory defaults. 1. Start with the system in Test Mode (Setup Mode cannot be reached from any other mode).

1 GONG & 5 BEEPS

TEST

9 WXY

STEP #999 FOR MASTER RESET

2. From Test Mode, enter the master user code then press TEST .

9 WXY

USE THESE EXACT KEYSTROKES TO PERFORM A MASTER RESET

9 WXY

✴ A “Gong” and fi ve “Beeps” will sound, signaling that the

system is in Setup Mode. 3. Enter programming STEP #999 then press TEST.

PRESS TEST

TEST

4. Enter 999 again then press TEST again.

9 WXY

✴ A “Bing” will sound to indicate the beginning of the reset

ENTER 999 TO OK THE MASTER RESET

process. This process will take up to 10 seconds while the memory is being reset. ✦ The system will revert to the fi rst time power-up

9 WXY

9 WXY

condition and the new master user code will be 1234. Go to the “Basic Console Programming” section of this manual to begin re-programming the system.

PRESS TEST, 1 BING SOUNDS, WAIT ABOUT 10 SECONDS

TEST

DONE

Page 34 of the Linear DVS-2400 user manual — GENERAL COMMUNICATOR OPTIONS
Page 34 · click to enlarge
Page 34

13. COMMUNICATOR PROGRAMMING

✦ To perform any of the communicator programming

steps, the Console must be in the Setup Mode.

✦ Each programming function is performed with

similar keystrokes. After the Console is in Setup Mode, enter the programming step number and press HOME, then enter the new value and press AWAY. For reference, follow the fi gures next to the programming steps.

SETUP MODE

✴ If the new value is accepted, a “Bing” will sound. If the new

value is not accepted, a “Double Buzz” will sound.

START IN TEST

SETUP MODE

1. Start with the Console in Test Mode (Setup Mode cannot be reached from any other mode).

MASTER USER CODE

2. From Test Mode, enter the master user code then press TEST .
✎ NOTEOnly the master user code can be used

to put the Console into the Setup Mode. The restricted user codes cannot access Setup Mode, only Code Mode.

1 GONG & 5 BEEPS TEST

✴ A “Gong” and fi ve “Beeps” will sound, signaling that the

system is in Setup Mode.

3. After programming changes are complete, press the OFF key for three seconds to exit Setup Mode.
✎ NOTEIf the Console is left unattended in Setup

Mode, it will automatically switch back to Off Mode after three minutes.

GENERAL COMMUNICATOR OPTIONS

STEP # PROGRAMMING

POSSIBLE

FACTORY

INSTALLATION

FUNCTION

VALUES

VALUE

VALUE

76 2-WAY AUDIO 0= NONE; 1 = LISTEN; 2 = 2-WAY MANUAL; 3 = 2-WAY FULL DUPLEX 0

78 VOICE RESPONSE FROM KEYPAD SPEAKER 0 = VOICE RESPONSE DISABLED 1 = VOICE RESPONSE ENABLED 0

100 REMOTE PROGRAMMING LOCKOUT 0 = UNLOCK; 1 = LOCK 0

101 CALL LIMITER 0 = OFF; 1 = FIVE CALLS PER ARMING PERIOD 0

103 DIALING DELAY 0 = NO DELAY; 1 = 30 SECOND DELAY 0

104 DIALING METHOD 0 = TONE; 1 = PULSE 0

107 COMMUNICATOR ENABLE 0 = COMMUNICATOR OFF; 1 = COMMUNICATOR ON 0

General Communicator Programming Table

Page 35 of the Linear DVS-2400 user manual — 0 FOR UNLOCK 1 FOR LOCK
Page 35 · click to enlarge
Page 35

GENERAL COMMUNICATOR OPTIONS

COMMUNICATOR ENABLE

✦ The factory setting for the Console disables

the communicator. If the system is going to be a non-monitored, local alarm only, leave the communicator disabled.

PROGRAMMING STEP #107

7 PRS

STEP #107 If the system is going to be monitored by a

Central Station, enable the communicator with this programming step.

0 FOR COMMUNICATOR OFF 1 FOR COMMUNICATOR ON

2-WAY AUDIO ✦ When the Model VB-2 voice module is installed, the

7 PRS

PROGRAMMING STEP #76

communicator can provide 2-way audio capability.

6 MNO

✦ The audio module can be programmed for

listen-only, 2-way manual operation (using a pushbutton telephone at the Central Station), and 2-way full duplex hands free operation.

0 FOR NO AUDIO MONITORING 1 FOR LISTEN-ONLY 2 FOR 2-WAY MANUAL 3 FOR 2-WAY FULL DUPLEX

✦ Refer to the VB-2 installation instructions for details

on operating the audio module.

✎ NOTEThe Model VB-2 digital voice response

module must be installed for this option to function. ✦ The factory setting for the VB-2 audio module is OFF.

STEP #76 The audio module can be set for (1) listen-only, (2)

2-way manual, (3) 2-way full duplex using this step.

✎ NOTEFor safety, 2-way audio will not activate if

the system is disarmed with the duress code. ✎ NOTE:Units programmed for two-way duplex can

still be controlled manually by pressing the “1” or “3” key. In addition, the Central Station can return the unit to two-way duplex by pressing the “8” key.

VOICE RESPONSE

✦ The Console can be programmed to allow the

speaker to play audio produced by the VB-2 digital voice response module.

✦ This selection can also be used when a remote

7 PRS

PROGRAMMING STEP #78

speaker is connected to the Console.

8 TUV

✦ The factory setting is to disable the speaker from

playing voice module audio.

STEP #78 The Console can be programmed to enable voice

0 FOR NO VOICE RESPONSE 1 FOR VOICE RESPONSE

module audio using this step.

✎ NOTETurning voice response OFF with this

programming step will only effect the audio produced by the voice module. It will not stop the Console’s speaker from sounding local sirens and tones. ✎ NOTE: A Model VB-2 digital voice response module

must be installed for this option to function.

REMOTE LOCKOUT

✦ The factory setting for the communicator allows

remote connection to the Console with Linear's RA-2400 Remote Access Software and a modem (unlocked).

PROGRAMMING STEP #100

STEP #100 The Console can be programmed to not answer

incoming calls, thereby, not allowing remote access (locked) using this step.

0 FOR UNLOCK 1 FOR LOCK

Page 36 of the Linear DVS-2400 user manual — 0 FOR TONE DIALING 1 FOR PULSE DAILING
Page 36 · click to enlarge
Page 36

CALL LIMITER

✦ The factory setting for the call limiter is OFF. This

allows the communicator to report burglary alarms, once for each sensor, as many times as they are triggered.

PROGRAMMING STEP #101

STEP #101 The Console can be programmed to only allow fi ve

burglary reports total per arming period using this step.

0 FOR OFF (UNLIMITED) 1 FOR ON (5 VIOLATIONS)

✎ NOTESensors programmed for 24-hour functions

(Emergency, Panic, Fire) always send a Central Station report and always sound the local siren regardless of the Call Limiter setting.

DIALING DELAY

✦ The factory setting will cause the communicator to

dial the Central Station instantly when an alarm or supervisory event occurs.

PROGRAMMING STEP #103

3 DEF

STEP #103 The communicator can be programmed to wait 30

seconds before dialing using this step. This gives the user time to disarm the system and prevent communications in the case of a subscriber generated false alarm.

0 FOR NO DELAY 1 FOR 15 SECOND DELAY

DIALING METHOD

✦ The factory setting causes the communicator to

PROGRAMMING STEP #104

dial using DTMF (dual-tone multi-frequency) tone dialing.

4 GHI

STEP #104 The communicator can be programmed to use

pulse (rotary) dialing using this step. Use this option if the telephone line in the installation does not support tone dialing.

0 FOR TONE DIALING 1 FOR PULSE DAILING

Page 37 of the Linear DVS-2400 user manual — 86 CALL ROUTING
Page 37 · click to enlarge
Page 37
Linear DVS-2400 — TELEPHONE LINE CONNECTION diagram (page 37)
Fig. 40

COMMUNICATOR REPORTING OPTIONS

report using the 4 BY 2 FORMAT. This format allows four-digit account numbers from 0000 to 9999 and provides two-digit alarm codes.

STEP #105 ADEMCO CONTACT ID can be chosen as a reporting

format using this step. This format allows 4-digit account numbers from 0000 to 9999 and provides verbose report descriptions with Ademco Contact ID compatible Central Stations.

0 FOR 4 BY 2 1 FOR ADEMCO CONTACT ID

CALL ROUTING

✦ The communicator can be programmed with three

telephone numbers; primary, secondary, and supervisory.

8 TUV

PROGRAMMING STEP #86

✦ The factory setting for the communicator is to

6 MNO

route all calls to the primary telephone number. If communication is unsuccessful after fi ve attempts to the primary number, the secondary number will be dialed for an additional fi ve attempts. If the secondary number cannot be reached, the communicator will “sleep” for fi ve minutes before starting the call process over again. A total of four sleep cycles (50 call attempts) can occur before the communicator stops calling.

0 FOR ALL TO PRIMARY/SECONDARY 1 FOR ALARMS ONLY TO PRIMARY/SECONDARY

STEP #86 The communicator can be programmed to report

supervisory events (low battery, trouble, AC failure, etc.) to the supervisory telephone number instead of the primary or secondary telephone numbers using this step.

✎ CAUTIONIf the page alert user code feature

is going to be used, the supervisory number is reserved for the pager number. DO NOT SET THE CALL ROUTING OPTION TO “1”.

✎ NOTETo disable supervisory reports, set call

routing option to “1” and remove the supervisory telephone number.

✎ NOTEDo not program the primary and secondary

telephone numbers the same. See the FCC Telephone Rules and Regulations on the rear cover of this manual.

COMMUNICATOR REPORTING OPTIONS

STEP

PROGRAMMING

POSSIBLE

FACTORY

INSTALLATION

FUNCTION

VALUES

VALUE

VALUE

0 = ALL CALLS TO PRIMARY OR SECONDARY NUMBER 1 = ALL ALARM CALLS TO PRIMARY OR SECONDARY NUMBER AND ALL OTHERS TO SUPERVISORY NUMBER

86 CALL ROUTING

88 ACCOUNT NUMBER 4 DIGITS EMPTY

89 PRIMARY PHONE NUMBER UP TO 20 DIGITS EMPTY

90 SECONDARY PHONE NUMBER UP TO 20 DIGITS EMPTY

91 SUPERVISORY/PAGER PHONE NUMBER UP TO 20 DIGITS EMPTY

PRESSING THE (A) KEY INSERTS A 1-SECOND DELAY THE [FIRE] KEY INSERTS A 5-SECOND DELAY FOR ALL PHONE NUMBERS ⇒ ⇒ ⇒ THE [CHIME] KEY INSERTS A “*” THE (A) KEY INSERTS A “#” IF IT IS THE LAST DIGIT OF THE PHONE NUMBER

105 REPORTING FORMAT 0 = 4 BY 2; 1 = ADEMCO 0

108 REPORT SYSTEM TROUBLE 0 = NO; 1 = YES 0

110 REPORT FORCE ARMING 0 = NO; 1 = YES 0

111 OPEN/CLOSE 0 = NO; 1 = YES; 2 = MASTER PAC ONLY 0

113 POINT ID REPORTING FOR 4 BY 2 FORMAT 0 = NO; 1 = YES 1

Communicator Reporting Option Table

#

Page 38 of the Linear DVS-2400 user manual — ADDS A POUND (#) CHARACTER (END OF NUMBER)
Page 38 · click to enlarge
Page 38

ACCOUNT NUMBER

✦ The account number entered for the communicator

8 TUV

must be 4-digits long.

PROGRAMMING STEP #88

8 TUV

✦ The factory setting for the account number is 0000.

STEP #88 Enter an account number from 0000 to 9999 using

4 DIGIT ACCOUNT NUMBER

this step.

PRIMARY TELEPHONE NUMBER

✦ The primary Central Station telephone number can

8 TUV

be up to 20-digits long.

PROGRAMMING STEP #89

9 WXY

✦ Digits 0-9 can be used.

✦ Delays and special characters can be entered in the

ENTER UP TO 20 DIGITS FOR PRIMARY NUMBER

telephone number (see below).

STEP #89 Enter the primary telephone number using this step.

SECONDARY TELEPHONE NUMBER

✦ The secondary Central Station telephone number

can be up to 20-digits long.

9 WXY

PROGRAMMING STEP #90

✦ Digits 0-9 can be used.

✦ Delays and special characters can be entered in the

telephone number (see below).

ENTER UP TO 20 DIGITS FOR SECONDARY NUMBER

STEP #90 Enter the secondary telephone number using this

step.

✎ NOTETo remove the secondary telephone

number, enter step number 90 then press TEST.

SUPERVISORY OR PAGER TELEPHONE NUMBER

✦ The supervisory Central Station or pager telephone

number can be up to 20-digits long.

✦ Digits 0-9 can be used.

✦ Delays and special characters can be entered in

9 WXY

the telephone number (see below). If this is a pager number, enter enough delays for the phone to answer. Then, enter the number to be dialed.

PROGRAMMING STEP #91

✦ End a pager number with the completion character

ENTER UP TO 20 DIGITS FOR SUPERVISORY NUMBER

(usually a pound (#) character).

STEP #91 Enter the supervisory or pager telephone number

using this step.

✎ NOTETo remove the supervisory/pager telephone

number, enter step number 91 then press TEST.

TELEPHONE NUMBER DELAYS AND SPECIAL CHARACTERS

✦ When creating telephone numbers with

programming Steps 89, 90, & 91, use the following keys to add dialing delays or special characters. ✦ Press the key to place a 1-second dialing delay at the start or anywhere in the middle of the telephone number. ✦ Pressing the key as the last digit of the telephone number will place a pound character at the end of the telephone number. ✦ Press the FIRE key to place a 5-second dialing delay

ADDS A 1-SECOND DELAY (START OR MIDDLE OF NUMBER)

ADDS A POUND (#) CHARACTER (END OF NUMBER)

ADDS A 5-SECOND DELAY (ANYWHERE IN NUMBER)

ADDS A STAR ( ) CHARACTER (ANYWHERE IN NUMBER)

anywhere in the telephone number. ✦ Press the CHIME key to place a star character anywhere in the telephone number.

Page 39 of the Linear DVS-2400 user manual — PROGRAMMING STEP #113
Page 39 · click to enlarge
Page 39

REPORT CONSOLE TROUBLE

✦ The factory setting does not report Console trouble

PROGRAMMING STEP #108

events to the Central Station.

STEP #108 The communicator can be programmed to report

Console trouble events using this step. These include all conditions that light the Console’s BATTERIES or TROUBLE indicator. It also includes low Console backup battery.

0 FOR NO CONSOLE TROUBLE 1 FOR CONSOLE TROUBLE

REPORT FORCE ARMING

✦ The factory setting does not send force arming

reports.

STEP #110 The communicator can be programmed to report

PROGRAMMING STEP #110

force arming anytime the Console is armed with one or more bypassed sensors using this step.

✦ The factory set reporting code for force arming is

“65” (Code 574 with Ademco).

0 FOR NO FORCE ARMING RPTS. 1 FOR FORCE ARMING RPTS.

✎ NOTEIf force arming is enabled, and the Console

is force armed (armed with an open sensor) remotely by telephone, or with the RA-2400 Remote Access software, the caller will be disconnected if the communicator is enabled.

OPENING AND CLOSING REPORTS

✦ The factory setting does not send opening and

closing reports.

STEP #111 The communicator can be programmed to send an

opening report when the system is disarmed, and a closing report when the system is armed for all users, or just the master user using this step.

PROGRAMMING STEP #111

✎ NOTE 1For commercial installations with retail

traffi c using opening and closing reports, it is recommended to disable quick arming to prevent customers from arming the system. ✎ NOTE 2: The reporting codes are fi xed for opening

0 FOR NO OPEN/CLOSE REPORTS 1 FOR O/C RPTS. FOR ALL USERS 2 FOR O/C RPTS. FROM MASTER USER ONLY

and closing. A unique code is reserved for the master user code and each of the fi ve restricted user codes. ✎ NOTE 3: Arming or disarming with the page

alert user code dials the supervisory number, no opening or closing report is sent.

POINT ID REPORTING

✦ The factory setting enables Point ID and allows the

communicator to send two-digit alarm and trouble codes for each sensor. The individual sensor that causes an alarm or trouble report can be identifi ed at the Central Station.

PROGRAMMING STEP #113

STEP #113 Point ID can be disabled using this step. The

0 FOR GENERAL REPORTS ONLY 1 FOR POINT ID REPORTING

Central Station will only receive general alarm and trouble reports.

Page 40 of the Linear DVS-2400 user manual — 0 - 99 FOR GENERAL ALARM REPORTING CODE
Page 40 · click to enlarge
Page 40

COMMUNICATOR REPORTING CODES ✦ The 4 by 2 two-digit communicator reporting code

for each event has a factory set value. These values may be customized to fi t the specifi c installation and the reporting requirements of the Central Station monitoring the system.

ADEMCO REPORTING CODES

EVENT ALARM CODE EXTENDED CODE

SENSOR EMERGENCY E120 C0xx

CONSOLE EMERGENCY E120 C026

✦ If Point ID reporting is enabled (the factory default

SENSOR FIRE E111 C0xx

setting), each sensor can report a unique alarm and trouble code.

CONSOLE FIRE E110 C025

BURGLARY ALARM E130 C0xx

✦ If Point ID is disabled, the “general” reporting codes

SILENT PANIC E122 C0xx

for each event type will be used.

FORCE ARM E574 C000

✦ Each programming function is performed with

DURESS E121 C000

similar keystrokes. After the system is in Setup Mode, enter the programming step number and press HOME, then enter the new value and press AWAY. For reference, follow the fi gures next to the programming steps.

CANCEL E406 C000

SENSOR LOW BATTERY E384 C0xx

SENSOR STATUS TROUBLE E381 C0xx

CONSOLE LOW BATTERY E302 C000

CONSOLE BATTERY RESTORE R302 C000

✴ If the new value is accepted, a “Bing” will sound. If the new

2-WAY AUDIO E606 C000

value is not accepted, a “Double Buzz” will sound.

✦ Making a value 0 causes the event not to

xx = SENSOR NUMBER IN EXTENDED REPORT

communicate to the Central Station.

HOME TEST = PROGRAM = REMOVE

✎ NOTEThe reporting codes are fi xed for opening

and closing. A unique code is reserved for the master and the fi ve restricted user codes. See the Opening & Closing Reporting Codes Table.

AWAY = STORE

GENERAL REPORTING CODES

✦ Use program Steps #201 - 206 to change the

2 ABC

communicator reporting codes when Point ID is disabled.

PROGRAMMING STEPS #201 TO #206

✦ Refer to the General Reporting Codes table to view/

edit the reporting codes for each of the fi ve events. The factory settings are listed, along with a blank area to write in the new installation values.

0 - 99 FOR GENERAL ALARM REPORTING CODE

STEPS #201-206

Any value from 0-99 can be programmed for each event using these steps (enter “0” to stop an event from reporting).

✎ NOTEBe careful not to duplicate codes unless the

Central Station requires specifi c codes for certain types of events.

Linear DVS-2400 — 0 - 99 FOR GENERAL ALARM REPORTING CODE diagram (page 40)
Fig. 41

STEP # PROGRAMMING FUNCTION POSSIBLE 4 BY 2 VALUES FACTORY 4 BY 2 VALUES INSTALLATION 4 BY 2 VALUE

201 GENERAL FIRE REPORT CODE 0 - 99 1

202 GENERAL EMERGENCY REPORT CODE 0 - 99 2

203 GENERAL SILENT PANIC REPORT CODE 0 - 99 3

204 GENERAL BURGLARY REPORT CODE 0 - 99 4

206 GENERAL TROUBLE REPORT CODE 0 - 99 6

General Reporting Codes Table

Page 41 of the Linear DVS-2400 user manual — 6 MNO
Page 41 · click to enlarge
Page 41

SYSTEM REPORTING CODES

✦ Refer to the System Reporting Codes table to

2 ABC

view/edit the reporting codes for the keypad FIRE and EMERGENCY buttons and for each of the four Console conditions. The factory settings are listed, along with a blank area to write in the new installation values.

6 MNO

PROGRAMMING STEPS #261 TO #266

0 - 99 FOR CONSOLE REPORTING CODE

STEPS #261-266

Any value from 0-99 can be programmed for each event using these steps (enter “0” to stop an event from reporting).

Linear DVS-2400 — 6 MNO diagram (page 41)
Fig. 42

✦ The factory set reporting code for force arming is

STEP #258 Any value from 0-99 can be programmed for this

✦ The factory set reporting code for Duress is “66”

STEP #259 Any value from 0-99 can be programmed for this

✎ NOTEFor duress code reporting a keypad duress
Linear DVS-2400 — 6 MNO diagram (page 41)
Fig. 43

STEP # PROGRAMMING FUNCTION POSSIBLE 4 BY 2 VALUES

258 FORCE ARMING REPORT CODE 0 - 99 65 574

259 DURESS REPORT CODE 0 - 99 66 121

261 SYSTEM FIRE REPORT CODE 0 - 99 68 110

262 SYSTEM EMERGENCY REPORT CODE 0 - 99 69 120

263 SYSTEM TEST/CANCEL REPORT CODE 0 - 99 70 406

264 SYSTEM LOW BATTERY RESTORAL REPORT CODE 0 - 99 71 R302

265 SYSTEM LOW BATTERY CODE 0 - 99 73 E302

System Reporting Codes Table

Linear DVS-2400 — 6 MNO diagram (page 41)
Fig. 44

MASTER USER CODE1 74 82 R401 C000 E401 C000

RESTRICTED USER CODE #1 75 83 R401 C001 E401 C001

RESTRICTED USER CODE #2 76 84 R401 C002 E401 C002

RESTRICTED USER CODE #3 77 85 R401 C003 E401 C003

RESTRICTED USER CODE #4 78 86 R401 C004 E401 C004

RESTRICTED USER CODE #5 79 87 R401 C005 E401 C005

PAGE ALERT USER CODE (DIALS PAGE NUMBER ONLY, NO CODES REPORTED)

Opening & Closing Reporting Codes Table

Page 42 of the Linear DVS-2400 user manual — 2 ABC
Page 42 · click to enlarge
Page 42

4 BY 2 FORMAT POINT ID REPORTING CODES

4 BY 2 FORMAT POINT ID ALARM REPORT CODES ✦ Refer to the 4 by 2 Format Point ID Reporting

Code table to view/edit the alarm reporting codes for each of the 24 sensors. The communicator will send these codes if Point ID is enabled and any sensor triggers an alarm. The factory settings are listed, along with a blank area to write in the new installation values.

2 ABC

PROGRAMMING STEPS #210 TO #233

✦ Use program Steps #210 - 233 to change the 4 by 2

0. 99 FOR SENSOR ALARM CODE (0 = NO REPORT)

Point ID alarm reporting codes.

✎ NOTEBe careful not to duplicate codes unless the

Central Station requires specifi c codes for certain types of sensors. STEPS #210-233

Any value from 0-99 can be programmed for each event using these steps (enter “0” to stop an event from reporting).

4 BY 2 FORMAT POINT ID TROUBLE REPORT CODES ✦ Refer to the 4 by 2 Format Point ID Reporting Code

table to view/edit the trouble reporting codes for each of the 24 sensors. The communicator will send these codes if Point ID is enabled and any sensor has a low battery or trouble condition. The factory settings are listed, along with a blank area to write in the new installation values.

2 ABC

PROGRAMMING STEPS #234 TO #257

✦ Use program Steps #234 - 257 to change the 4 by 2

0. 99 FOR SENSOR TROUBLE CODE (0 = NO REPORT)

Point ID trouble reporting codes.

✎ NOTEBe careful not to duplicate codes unless the

Central Station requires specifi c codes for certain types of sensors. STEPS #234-257

Any value from 0-99 can be programmed for each event using these steps (enter “0” to stop an event from reporting).

Page 43 of the Linear DVS-2400 user manual — TELEPHONE LINE CONNECTION
Page 43 · click to enlarge
Page 43
Linear DVS-2400 — TELEPHONE LINE CONNECTION diagram (page 43)
Fig. 45

STEP # PROGRAMMING FUNCTION POSSIBLE 4 BY 2 VALUES FACTORY 4 BY 2 VALUE INSTALLATION 4 BY 2 VALUE

210 SENSOR 1 ALARM REPORT CODE 0 - 99 11

211 SENSOR 2 ALARM REPORT CODE 0 - 99 12

212 SENSOR 3 ALARM REPORT CODE 0 - 99 13

213 SENSOR 4 ALARM REPORT CODE 0 - 99 14

214 SENSOR 5 ALARM REPORT CODE 0 - 99 15

215 SENSOR 6 ALARM REPORT CODE 0 - 99 16

216 SENSOR 7 ALARM REPORT CODE 0 - 99 17

217 SENSOR 8 ALARM REPORT CODE 0 - 99 18

218 SENSOR 9 ALARM REPORT CODE 0 - 99 19

219 SENSOR 10 ALARM REPORT CODE 0 - 99 20

220 SENSOR 11 ALARM REPORT CODE 0 - 99 21

221 SENSOR 12 ALARM REPORT CODE 0 - 99 22

222 SENSOR 13 ALARM REPORT CODE 0 - 99 23

223 SENSOR 14 ALARM REPORT CODE 0 - 99 24

224 SENSOR 15 ALARM REPORT CODE 0 - 99 25

225 SENSOR 16 ALARM REPORT CODE 0 - 99 26

226 SENSOR 17 ALARM REPORT CODE 0 - 99 27

227 SENSOR 18 ALARM REPORT CODE 0 - 99 28

228 SENSOR 19 ALARM REPORT CODE 0 - 99 29

229 SENSOR 20 ALARM REPORT CODE 0 - 99 30

230 SENSOR 21 ALARM REPORT CODE 0 - 99 31

231 SENSOR 22 ALARM REPORT CODE 0 - 99 32

232 SENSOR 23 ALARM REPORT CODE 0 - 99 33

233 SENSOR 24 ALARM REPORT CODE 0 - 99 34

234 SENSOR 1 TROUBLE REPORT CODE 0 - 99 41

235 SENSOR 2 TROUBLE REPORT CODE 0 - 99 42

236 SENSOR 3 TROUBLE REPORT CODE 0 - 99 43

237 SENSOR 4 TROUBLE REPORT CODE 0 - 99 44

238 SENSOR 5 TROUBLE REPORT CODE 0 - 99 45

239 SENSOR 6 TROUBLE REPORT CODE 0 - 99 46

240 SENSOR 7 TROUBLE REPORT CODE 0 - 99 47

241 SENSOR 8 TROUBLE REPORT CODE 0 - 99 48

242 SENSOR 9 TROUBLE REPORT CODE 0 - 99 49

243 SENSOR 10 TROUBLE REPORT CODE 0 - 99 50

244 SENSOR 11 TROUBLE REPORT CODE 0 - 99 51

245 SENSOR 12 TROUBLE REPORT CODE 0 - 99 52

246 SENSOR 13 TROUBLE REPORT CODE 0 - 99 53

247 SENSOR 14 TROUBLE REPORT CODE 0 - 99 54

248 SENSOR 15 TROUBLE REPORT CODE 0 - 99 55

249 SENSOR 16 TROUBLE REPORT CODE 0 - 99 56

250 SENSOR 17 TROUBLE REPORT CODE 0 - 99 57

251 SENSOR 18 TROUBLE REPORT CODE 0 - 99 58

252 SENSOR 19 TROUBLE REPORT CODE 0 - 99 59

253 SENSOR 20 TROUBLE REPORT CODE 0 - 99 60

254 SENSOR 21 TROUBLE REPORT CODE 0 - 99 61

255 SENSOR 22 TROUBLE REPORT CODE 0 - 99 62

256 SENSOR 23 TROUBLE REPORT CODE 0 - 99 63

257 SENSOR 24 TROUBLE REPORT CODE 0 - 99 64

4 by 2 Format Point ID Reporting Code Table

Page 44 of the Linear DVS-2400 user manual — 14. IMPORTANT INFORMATION
Page 44 · click to enlarge
Page 44

14. IMPORTANT INFORMATION

LINEAR LIMITED WARRANTY This Linear product is warranted against defects in material and workmanship for twelve (12) months. This warranty extends only to wholesale customers who buy direct from Linear or through Linear's normal distribution channels. Linear does not warrant this product to consumers. Consumers should inquire from their selling dealer as to the nature of the dealer's warranty, if any. There are no obligations or liabilities on the part of Linear LLC for consequential damages arising out of or in connection with use or performance of this product or other indirect damages with respect to loss of property, revenue, or profi t, or cost of removal, installation, or reinstallation. All implied warranties, including implied warranties for merchantability and implied warranties for fi tness, are valid only until the warranty expires. This Linear LLC Warranty is in lieu of all other warranties express or implied. All products returned for warranty service require a Return Product Authorization Number (RPA#). Contact Linear Technical Services at 1-800-421-1587 for an RPA# and other important details.

FIRE EVACUATION PLANNING For systems that include fi re protection, UL requires that the following information be available to the users of the system.

✶ Draw up a fl oor plan showing two exits for each room.

The following procedures are to be discussed with the family:

➀ Status of bedroom doors. ➁ Familiarity with alarm signals. ➂ Testing of door during a fi re and use of alternate escape route if door

is hot to touch. ➃ Crawling and holding breath. ➄ Escape fast. No stopping for packing. ➅ Meet at designated outdoor spot. ➆ Emphasize that no one is to return to a burning house. ➇ Fire department notifi cation from a neighbor's phone. ➈ Periodic rehearsal is to be conducted.

WIRELESS PRODUCT NOTICE Linear radio controls provide a reliable communications link and fi ll an important need in portable wireless signaling. However, there are some limitations which must be observed.

INDUSTRY CANADA NOTICES NOTICE: The ringer equivalence number (REN) assigned to each terminal device provides an indication of the maximum number of terminals allowed to be connected to a telephone interface. The termination on an interface may consist of any combination of devices subject only to the requirement that the sum of the ringer equivalence numbers of all the devices does not exceed 5. NOTICE: The Industry Canada label identifi es certifi ed equipment. This certifi cation means that the equipment meets certain telecommunications network protective, operational and safety requirements. The Department does not guarantee the equipment will operate to the user's satisfaction. Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of the local telecommunications company. The equipment must also be installed using an acceptable method of connection. The customer should be aware that compliance with the above conditions may not prevent degradation of service in some situations. Repairs to certifi ed equipment should be made by an authorized Canadian maintenance facility designated by the supplier. Any repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the telecommunications company cause to request the user to disconnect the equipment. Users should ensure for their own protection that the electrical ground connections of the power utility, telephone lines and internal metallic water pipe system, if present, are connected together. This precaution may be particulary important in rural areas. CAUTION: Users should not attempt to make such connections themselves, but should contact the appropriate electric inspection authority, or electrician, as appropriate.

✶ For U.S. installations onlyThe radios are required to comply with

FCC Rules and Regulations as Part 15 devices. As such, they have limited transmitter power and therefore limited range. ✶ A receiver cannot respond to more than one transmitted signal at a

time and may be blocked by radio signals that occur on or near their operating frequencies, regardless of code settings. ✶ Changes or modifi cations to the device may void FCC compliance. ✶ Infrequently used radio links should be tested regularly to protect

against undetected interference or fault. ✶ A general knowledge of radio and its vagaries should be gained prior

to acting as a wholesale distributor or dealer, and these facts should be communicated to the ultimate users.

FCC NOTICE This equipment generates and uses radio frequency energy and if not installed and used properly, that is, in strict accordance with the manufacturer's instructions, may cause interference to radio and television reception. It has been type tested and found to comply with the limits for a Class B computing device in accordance with Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference in a residential installation. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

✶ Relocate the Console away from the TV/radio receiver. ✶ Plug the Console into a different wall outlet so that the Console is on

a different branch circuit. ✶ Re-orient the TV/radio antenna. ✶ If necessary, the user should consult the dealer or an experienced

radio/television technician for additional suggestions.

FCC TELEPHONE RULES AND REGULATIONS The FCC requires that this alarm dialer system not make more than 15 repetitive dialing attempts to a single telephone number. There are no limitations when the calls are made sequentially to two or more alternative numbers, or when these calls are spaced 10 minutes apart to a single number. The FCC Rules and Regulations do not specify the re-attempt period as this can vary for specifi c applications. When setting this period, take into consideration local, interstate, foreign and special network call completion characteristics, network processing time, a suffi cient number of rings and busy/don't answer modes.

Copyright © 2008 Linear LLC 212734 H

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the Linear DVS-2400

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Linear DVS-2400

Be the first to ask — other owners or our team will answer.

Original document

Linear DVS-2400 manual PDF

44 pages·2.3 MB·Home Security System·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…