Smart-UPS ® RT Uninterruptible Power Supply SURT 8000/10000 VA 200-240 VAC Tower/Rack-Mount 6U English © 2012 APC by Schneider Electric. APC, the APC logo, Sm art-UPS and PowerChute are owned by Schneider Electric Industries S.A.S., American Power Conversi on Corporation, or affiliated companies.
.
Introduction The APC ® by Schneider Electric Sm art-UPS ® RT is a high-performance, uninterruptible power supply (UPS) that provides protection for electronic equipment from utility power blackouts, brownouts, sags and su rges.
Hardwiring Wiring must be performed by a qualified electrician. 1. Install a utility circuit breaker in accordance with local electrical codes (see tables below) for input wiring. 2. Switch the UP S input circui t breaker (see A ) and utility circuit breakers OFF.
7. XLI mo del only: For three-phase input, set the Input Phase Selector switch (see C ) to ‘3’. For single-phase input, leave switch in default position of ‘1’. 8. Switch the circuit breakers ON. 9. Check line voltages. 10. Replace the ac cess panel.
Installing and Connecti ng the Batteries and Attaching the Front Bezel 4.
C ONNECTING P OWER AND E QUIPMENT TO THE UPS 1. Hardwire the UPS (see Hardwiring ). 2. Connect equipment to th e UPS (cables not included for XLT/XLJ/XLTW models). 3. Turn on all connected equipm ent. To use the UPS as a m aster on/off switch, be sure that all connected equipm ent is switched ON.
B ASIC C ONNECTORS Serial Port Power m anagement software and inte rface kits can be used with the UPS. Use only inter face kits suppli ed or approved b y APC.
O PERA TION F RONT D ISPLAY P ANEL Indicator Description Online The UPS is drawing utility power and performin g double conversion to sup ply power to connected equipm ent (see Troubl eshootin g ). On Battery The UPS is supplying batter y powe r to the connected equi pment.
Feature Function Normal /Bypass Manually switch connected eq uipment to bypass mode, so that utility power is sent directly to connected equipment. Battery op eration is not available while the UPS is in bypass mode. (See Troubleshooting. ) Cold Start This is not a normal condition.
U SER C ONFIGURABLE I TEMS N OTE : S ETTINGS ARE MADE THROUGH SUPPLIED P OWER C HUTE SOFTWARE , N ETWORK M ANAG E ME NT CAR D , OPTIONAL S MA RT S LOT A CCESSORY CARDS OR T ERMINA L M ODE .
N OTE : S ETTINGS ARE MADE THROUGH SUPPLIED P OWER C HUTE SOFTWARE , N ETWORK M ANAG E ME NT CAR D , OPTIONAL S MA RT S LOT A CCESSORY CARDS OR T ERMINA L M ODE .
EPO (Emergency Power Off) Option The output power can be disabled i n an emerge ncy by closing a switch connected to t he EPO. Adhere to national an d local electrical codes when wiring. The switch should be connected in a normally open switch contact.
Terminal Mode to Configure UPS Parameters Terminal Mode is a me nu driven interface that enables enhanced c onfiguration of the UPS. Connect the serial cable to the se rial port on the back of the UPS.
M AINTENANCE , S ERVICE , W ARRANTY , AND T RANS PORTING Replacing the Battery Module(s) This UPS has e asy to replace, hot -swappable ba ttery m odules. Replacement is a sa fe procedure, isolated from electrical hazards. You may leave the UPS and connected eq uipment on during the procedure.
T ROUBLESHOOTING Use the table below to solve minor installation and operation problems. Refer to the APC Web site, www.apc.com for assistance with complex UPS problems. P ROBLEM AND P OSSIBLE C AUS E S OLUTION UPS WILL NOT TURN ON Batteries are not connected properly.
15 P ROBLEM AND P OSSIBLE C AUS E S OLUTION BYPASS LED ILLUMINATES The bypass switch has been turned on manually or through an accessory. If bypass is the chosen mode of ope ration, ignore the illuminated LED. If bypass is not the chosen mode of operation move the bypass switch on the back of the UPS, to the normal position.
Service If the UPS requires service do not return it to the dealer. Follow these step s: 1. Review the pr oblems di scussed in the Tr oubleshoot ing section of this manual to eliminate common pr oblems. 2. If the pro blem persists, co ntact APC C ustomer Su pport thro ugh the APC Web site, ww w.
17 R ADIO F REQU ENCY W ARNINGS This equipment has been tested and found to comply with the li m its for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable pr otection against harmful interf erence when the equipment is operated in a commercial environment.
An important point after buying a device APC SURT8000XLI+LE600I (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought APC SURT8000XLI+LE600I yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data APC SURT8000XLI+LE600I - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, APC SURT8000XLI+LE600I you will learn all the available features of the product, as well as information on its operation. The information that you get APC SURT8000XLI+LE600I will certainly help you make a decision on the purchase.
If you already are a holder of APC SURT8000XLI+LE600I, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime APC SURT8000XLI+LE600I.
However, one of the most important roles played by the user manual is to help in solving problems with APC SURT8000XLI+LE600I. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device APC SURT8000XLI+LE600I along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center