990-3467A 02/2009 Smart-UPS ® RT Uninterruptible Power Supply S t ack/Rack-Mount 12U SUR T14000/18000 V A 200 V ac SUR T15000/20000 V A 208/240 V ac English.
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Va c 15000/20000 VA 208/240 Vac 3 Introduction Overview The American Power Conversion (APC ® ) Smart-UPS ® R T is a high performance uninterruptible power supply (UPS) that provides protection fo r electronic equipment (load) from utility power black outs, brownouts, sags and surges.
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 150 00/20000 VA 208/240 Vac 4 Accessories Install accessories prior to connecting power to the UPS. Refer to the APC W eb site, www .
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Va c 15000/20000 VA 208/240 Vac 5 Physical Specifications continued Front and rear UPS p anels Dimensions UPS width 482 mm (19 in) with rack-mount brackets 432 mm (17 in) without rack-mount br ackets heigh t 263 mm (10.
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 150 00/20000 VA 208/240 Vac 6 St ack and rack-mount installation Batteries must be r emoved from battery pack and XLBP(s) prior to installing units in stack or rack-mount configurat ions. Refer to the instructio ns on packaging for details on removing batteries.
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Va c 15000/20000 VA 208/240 Vac 7 Install rails in rack For details on rail installation refer to instructions included in rail kit package. Inst all units in rack Secure UPS and battery pack in rack using cage nuts and ornamental screws included in package.
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 150 00/20000 VA 208/240 Vac 8 Communication port s Display interface inst allation Prior to attaching the di splay interface to the UPS: 1. Loosen two bracket screws on rear of display interface. a. Slide bracket to the posit ion that wil l accommodate screw holes on the UPS.
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Va c 15000/20000 VA 208/240 Vac 9 Route network cable Network cable wiring fro nt pane l access The NMC is installed in the SmartSlot located on the front of the UPS. Connect a network cable (not supplied), t o the network p ort on the NMC.
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 150 00/20000 VA 208/240 Vac 10 Emergency Power Off (EPO) The system power can be disabled in an emerge ncy by closing a switch connected to the EPO. Wiring must be performed by a qualified electrician. Adher e to all local and national electrical codes.
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Va c 15000/20000 VA 208/240 Vac 11 Wiring Specifications Wir e gauges may vary . Adher e to national an d local electrical codes wh en wiring this unit . * T erminal screw tightening torque: 40 lb-in (4.5 N-m ) Acceptable input frequency range is 40 to 70 Hz.
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 150 00/20000 VA 208/240 Vac 12 Input wiring Wiring must be perfor med by a qualified electrician. Adhere to all national and local electrical code s. 1. Install a utility circu it breaker in accordance with local electrical codes.
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Va c 15000/20000 VA 208/240 Vac 13 Input hardwiring Inst all input wiring tray in UPS L1 N/L 2 su0154a su01 55a Ground Neutral/L2 L1 Lug A Lug B Lug A Lug B Ensure ground wire con ductor and insulator are securely fastened.
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 150 00/20000 VA 208/240 Vac 14 Output wiring Wiring must be perfor med by a qualified electrician. Adhere to all national and local electrical code s. Failure to follow these instructions may resu lt in personal injury or equipment damage.
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Va c 15000/20000 VA 208/240 Vac 15 Hardwire the load 1. Remove appropriate circular knoc kout from output wirin g tray . 2. Install appropriate strain relief (not supplied ), for hardwire cables. 3. Connect ground terminal first .
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 150 00/20000 VA 208/240 Vac 16 Connect PDU to output wiring tray 1. Remove the five screws securing the strain relief bar on the output wiring tray . 2. Connect the PDU on the external battery pack to the output wiring tray .
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Va c 15000/20000 VA 208/240 Vac 17 Star t - U p Connect battery modules Connect all eight battery mo dules. Failure t o do so may cause equipm ent damage. Replace battery compartment doors. T ighten the screws to secure battery compartment doors.
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 150 00/20000 VA 208/240 Vac 18 Operation Normal operation During normal operation, the UPS doubl e converts ut ility power to conditioned power for th e connected load.
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Va c 15000/20000 VA 208/240 Vac 19 Display interface The four LEDs to the left of the LCD indicate the operational st atus of the UPS.
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 150 00/20000 VA 208/240 Vac 20 Navigating menu screens Navigating sub menu screens Use UP/DOWN arrow keys to scroll through the list of functions and commands on a sub menu screen. after last entry on a sub menu, indicates a continuation of fun ction/command list.
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Va c 15000/20000 VA 208/240 Vac 21 Configuration UPS configuration options ca n be adjusted through t he display interface or NMC Configurables Factory Def.
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 150 00/20000 VA 208/240 Vac 22 Setup/Settings/Alarms Alarm Thr eshol ds/Loa d 14 kV A 14 kV A 2, 4, 6, 8, 10, 12, 14 kV A, Never If the connected load exceeds the load alarm threshold an alarm is activated.
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Va c 15000/20000 VA 208/240 Vac 23 Menu screens map Refer to the Configuratio n table on the previous pages for specific sy stem configuration settings.
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 150 00/20000 VA 208/240 Vac 24 View Log C lear Log V iew Statistics xxx Tr an sf er s- >B at . xxx Tr an sf er s- >b yp .
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Va c 15000/20000 VA 208/240 Vac 25 Language Contrast Beeper Setup Display Setup Cont rol Stat us Setu p Batt eries Logg ing Disp lay Diag s Help Beep at Vo.
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 150 00/20000 VA 208/240 Vac 26 T roubleshooting display messages Use the table below to solve minor installation and operatio n problems. Refer to the APC W eb site, www .apc.com for assistance with complex UPS problems.
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Va c 15000/20000 VA 208/240 Vac 27 Threshold Alarm Load Power Is Above Alarm Limit. The load has exceeded the user- specified load alarm threshold. Option 1) Use the display i nterface to raise the alarm threshold.
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 150 00/20000 VA 208/240 Vac 28 General Fault Shutdown Due T o Low Battery . The UPS shutdown while on battery operation. No corrective action is necessary . Note: Should this situatio n reoccur , consider increasing battery capacity .
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Va c 15000/20000 VA 208/240 Vac 29 Maintenance and service Replace battery modules This UPS has easy-to-replace, hot-sw appable battery modules. Replacement is a safe procedure, isolated from electrical hazards.
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 150 00/20000 VA 208/240 Vac 30 T wo-Y ear W arranty The limited warranty pr ovided by American Power Conversion (APC®) in th is statement of Limited Factory W arranty applies only to products you p urchase for your com mercial or indus trial use in the ordinary course of your business.
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Va c 15000/20000 VA 208/240 Vac 31 Cont act information APC W orldwide Customer Support Customer support for this or any other APC product is available at .
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 150 00/20000 VA 208/240 Vac 32.
An important point after buying a device APC SURT20KRMXLT (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought APC SURT20KRMXLT yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data APC SURT20KRMXLT - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, APC SURT20KRMXLT you will learn all the available features of the product, as well as information on its operation. The information that you get APC SURT20KRMXLT will certainly help you make a decision on the purchase.
If you already are a holder of APC SURT20KRMXLT, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime APC SURT20KRMXLT.
However, one of the most important roles played by the user manual is to help in solving problems with APC SURT20KRMXLT. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device APC SURT20KRMXLT along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center