Instruction/ maintenance manual of the product Smart UPS RT APC
Go to page of 23
990-2690 0 2/2006 User Manual English APC Smart-UPS ® RT 3000/500 0 VA 200-240 VAC Tower/Ra ck Mount 3U Uninterrupti ble Power Supply.
.
1 Introduction The APC Sm art-UPS® RT is a h igh-perf ormance, unint erruptible pow er supply (UPS) that prov ides protection for electron ic equipment from utilit y power blackouts, brownouts , sags and surges.
2 Wiring and Connecting the UPS 5000 VA XLI MODE LS O NLY : H ARDWIRING I NSTRUCTION S • Wi ring must be perf ormed by a qu alified elect rician. • In stall a high magnetic 30/3 2 A utility circuit breaker. • A dhere to all national and local electrical codes.
3 C ONNECTING THE B ATTE RY MODULES AND A TTACHING THE F RONT B EZEL .
4 B ASIC C ONNE CTORS serial com The serial connector is to be u sed for interf acing with APC Po w erChute software and terminal emulation software. Use only cables appro ved by APC. Any other interface cable will be incompatible with the UPS connector.
5 C ONNECTING E QUIPME NT AND P OWER TO TH E UPS 1. Connect equipmen t to the UPS (cables not included for XLJ/XLT/XLTW models ). 2. Avoid using ext ension cords. • 3000 VA XLJ/XLT/ XLI/XLTW and 5000 VA XLJ/XLT /XLTW models : Using a power cord, plug the UPS into a two- pole, thr ee-wire, grounded receptacle only .
6 O PERA TION Load S MART -U PS RT F RONT D ISPL AY Battery Charge Indicator Description Online The Online LED illuminat es when the UPS is drawing utility power and perf orming double con version to supply power to con nected equipment. On Battery The UPS is supplying battery po w er to the connected equ ipment.
7 Feature Function Cold Start When there is no utility po w er and the UPS is off, press and hold the button to power up th e UPS and connected equipment.
8 U SER C ONFIGU RA BLE I TEMS N OTE : S ETTINGS ARE MADE THROUGH SUPPLIED P OW E R C HUTE SOFTW ARE , OPTIONAL S MA R T S LOT ACCESSO RY CARDS , OR T ER MI NAL M ODE .
9 N OTE : S ETTINGS ARE MADE THROUGH SUPPLIED P OW E R C HUTE SOFTW ARE , OPTIONAL S MA R T S LOT ACCESSO RY CARDS , OR T ER MI NAL M ODE . F UNCTION F ACTORY D EFAULT U SER S ELECTABLE C HOICES D ESC.
10 C ONNECTING THE EPO (E MERGENCY P OWER O FF ) O PTI ON The output pow er can be disabled in an emergen cy b y clos ing a switch connected to the EPO. Adhere to National and local electrical codes wh en wiring the EPO. The EPO switch is intern ally po we red by the UPS for use with n on-po w ered switch circuit breakers.
11 T ERMI NAL M OD E TO C ONFIGURE UPS P ARAMETE RS 3000 VA m odels: Terminal Mode is a menu driven interface that enables configuration of the UPS by users not wi shing to use P o werChute ® soft ware o r an o ptio nal Net work Ma nage ment Card. Connect the serial cable to th e serial co m con nector on the back of the UPS.
12 5000 VA m odels: Terminal Mode is a menu driven interface that enables configuration of the UPS by users not using Pow erChute ® software or th e installed Netw ork Management Card in terfaces. Connect the serial cable to the serial port on the back of th e UP S.
13 • Press 2 and ENTE R to change the Battery Settings. • Type in the number of external battery packs (four batt ery modules per pack ), and press E NTE R. (Num ber of packs: 1 = 1 S URT192XLBP, 2 = 2 SURT192XL BP etc.) • Press 3 and ENTER to accept the changes.
14 M AI N T EN AN C E AN D T RA NSPOR T Replacing the Battery Module This UPS has an easy to replace, h ot-swappable battery module. Replacement is a safe procedure, isolated from electrical hazards. You may leave the UPS and connected equipm ent on during the procedure.
15 R EPLACING B ATTERY MODULES X Y Z [ ] ^ _ Disconnecting the Battery for Transport Alway s DISCONNECT THE BA TTERY(s) befo re shipping in co mpliance with U.S. Departm ent of Transportation (DOT) and I ATA regulations. The battery(s) m ay remain in the UPS.
16 T ROUBLESHOOTING , S ER VICE , AN D W A RRA NTY I NFORMA TION Use the table below to solve minor installation and op eration problems. Refer to the APC W eb site, www.apc.com for assistance with complex UPS problems. P ROBLEM AND P OSSI BLE C AUSE S OLUTION UPS WILL NOT TURN ON Batt ery not conn ected p roper ly.
17 P ROBLEM AND P OSSI BLE C AUSE S OLUTION BYPASS LED ILLUM INATE S The bypass swi tch ha s been turne d on m anually or throu gh an acce ssory . If bypa ss is t he chosen mode of oper ation, i gnore the illuminate d LED. If bypa ss is not the chos en mode of op erat ion move the b ypass switc h on the back o f the UPS , to th e normal posit ion.
18 Service If the UPS requires service do not return it to the dealer. Follow these s teps: 1. Revi e w the problems di scussed in th e Troubleshooti ng section of this manual to eliminate common problem s. 2. If th e problem persis ts, contact APC Cus tomer Support th rough the APC Web site, www.
19 R EGULA TOR Y Regulatory Agenc y Approvals a nd Radio F reque ncy Warnings 200, 208, 22 0, 230, 240 V MODELS This e quipm ent has bee n teste d and f ound to com ply with the limits f or a Class A digi tal de vice, p ursua nt to part 15 of t he FCC Ru les.
20 Declaration of Conformity.
21 A PC Worldwi de C ustomer Support Custom er support for th is or any other APC produ ct is available at n o charge in any of the following wa ys: • R efer to the APC Web site to access docum ents in the APC Knowledge Base and to su b m it customer su pport requests .
An important point after buying a device APC Smart UPS RT (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought APC Smart UPS RT yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data APC Smart UPS RT - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, APC Smart UPS RT you will learn all the available features of the product, as well as information on its operation. The information that you get APC Smart UPS RT will certainly help you make a decision on the purchase.
If you already are a holder of APC Smart UPS RT, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime APC Smart UPS RT.
However, one of the most important roles played by the user manual is to help in solving problems with APC Smart UPS RT. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device APC Smart UPS RT along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center