Kenmore Oil Boiler (4EW1.50)

41 pages·1.5 MB·Boiler·PDF·ENFRITNLJA
Kenmore Oil Boiler (4EW1.50)
Table of Contents 80 sections Owner'sManual · 3E W.65 · 3EW. 75 · 3EWI';O0 · … ShowHide
Page 1 of the Kenmore Oil Boiler (4EW1.50) user manual — Save this manual
Page 1 · click to enlarge
Page 1
Kenmore Oil Boiler (4EW1.50) — Owner'sManual diagram (page 1)
Fig. 1 · Owner'sManual

[

Owner'sManual

MODELNO.

3E W.65

3EW. 75

3EWI';O0

4EW.90

4EWl ;25 4EW1.50

5EWl.20

5EW1.75

5EW2.00

Off-Fired HotWater

Boiler

  • Installation
  • Operation
  • Repair Parts

CAUTION Read aftinstructions

carefully before starting the installation.

Save this manual

for reference.

Page 2 of the Kenmore Oil Boiler (4EW1.50) user manual — SEARS ROEBUCK AND COMPANY
Page 2 · click to enlarge
Page 2
Kenmore Oil Boiler (4EW1.50) — SEARS INSTALLATION WARRANTY diagram (page 2)
Fig. 2

KENNMORE CAST IRON BOILERS FULL ONE YEAR WARRANTY ON HOT WATERAND GAS STEAM CAST IRON BOILERS

For one (1) year from the date of installation,when this boiler is installed and maintained in accordance with our instructions. Sears will repair defects in material or workmanship in the boiler, free of charge.

LIMITED 12 YEAR WARRANTY ON STEAM CAST IRON BOILERS

After one (1} year and through twelve (12) years from the date of installation,Sears will furnish a replacement

heat exchanger, if the heat exchanger in the boiler is defective. YOU PAY FOR LABOR.

LIMITED 20 YEAR WARRANTY ON HOT WATER CAST IRON BOILERS After one (!) year and through twenty (20) years from the date of installation,Sears will furnish a replacement heat exchanger if the heat exchanger in the boiler is defective. YOU PAY FOR LABOR.

SEARS INSTALLATION WARRANTY

tn addition to any warranty extended to you on the Sears merchandise involved, which warranty becomes effective the date the merchandise is installed, should the workmanship of any Sears arranged installation

prove faulty within one year, Sears will, upon notice from you, cause such faults to be corrected at no additional cost to you

FOR WARRANTY SERVICE, SIMPLY CONTACT THE NEAREST SEARS STORE OR SERVICE CENTER THROUGHOUT THE UNITED STATES. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.

IMPORTANT

The following are the responsibilities of the user and are not covered by the Warranty

5. If the unit is removed from the place it was originally installed, this Warranty becomes void.

1 Filter clearing or replacement

6 Damage to the unit caused by accident, abuse, negligence, misuse, riot, fire, flood, or acts of God

2 Damage to unit or unsatisfactory operation due to improper cleaning or use of unit in corroswe atmosphere

3 Damage to unit or unsatisfactory operation due to blown fuses or inadequate or _nterrupted electrical protective devices

SEARS ROEBUCK AND COMPANY

4 Damage to unit caused by the use of components or other accessones not compatible with the unit

D/817WA Hoffman Estates, IL 60179

Page 3 of the Kenmore Oil Boiler (4EW1.50) user manual — '_ WATIER
Page 3 · click to enlarge
Page 3
Kenmore Oil Boiler (4EW1.50) — INTRODUCTION diagram (page 3)
Fig. 3

INTRODUCTION

The Empire Water boiler is a natural draft oil fired hot water boiler comprised of cast iron sections. The Empire

Water boiler is available with 3, 4, or 5 cast iron sections. These sections are held together by cast iron push nipples.

The Empire Water boiler is capable of firing #2 fuel oil from 0.65 gph up to 2.00 gph. Boilers may be purchased with or without the following options: a Beckett AFG, Carlin EZ, or Rie[lo 40 oil burner, a Taco or Grundfos circulator with isolation valves, a tankless coil for domestic hot water. All packaged boilers include a swing door, Honeywell aquastat, temperature and pressure gage, relief valve, drain valve, 2 Delevan oil nozzles for multiple firing rates (only when purchasing a burner), flue brush, and an extra boiler tap for an expansion tank or air elimination.

,7.l/a"

A

RIEU.O

GAUGIE

T3 3/4"

BIECKETT

PRIESSUR_

OR CARUN

UMIT

RIEUIEF

t I P-'f I I I--.-.I

'_ WATIER

OPTIONAL TANKLESS

OUTLET

VALVIE "_ OUTLET

J COIL WATIER HEATER WITH 1/2" NPT CONNECTIONS

LIMIT

CONTROL

BURN

DRAIN

1/4" RETURN NIPPLE

RIGHT SIDE VIEW WITH SWING DOOR

BACK VIEW

FRONT VIEW

& RIEDUCING

TEE

Show 12 more labels / short text on this page
--*-- 2o I/2" · TIE_ml · r i · j CONTROL · (W_lh=_t · Tanklos= · 36" · oll) · (_Bh · Tonkiel= · co==) · VALVE (Furnished)
Page 4 of the Kenmore Oil Boiler (4EW1.50) user manual — 5[-W2 00"[ SEW200Z
Page 4 · click to enlarge
Page 4
Kenmore Oil Boiler (4EW1.50) — BOILER RATINGS AND CAPACITIES diagram (page 4)
Fig. 4

BOILER RATINGS AND CAPACITIES

BOIIiR MOI)EI.NO Wlill WIIIIOU I

NET DIMENSIONS (inches) I=B:R HRING A t: tJ I MINIMUM RA'I IN(i RA'II_ _+ CHIMNEY

NO INPUI **llliA'[ ING

IANK[ISS IANKIESS ('Oil ('OIl niw (_5I ¸ 3[!W65Z -

Sli(' +M[_II ( APA('IIY

*MBH

*MBH +GPH SIZE / HEIGHT A B C

70 0.65 863 8" X 8" X 15' 14+1/2 6 8 80 075 852 8" X 8"X 15' 14-1/2 6 8 103 100 83 4 8" X 8" X 15' 14-1/2 6 8

31,W 751 3EW 75Z

31!WI OttI ¸ 3EWI IRIZ 4[iw 90T 4EW 99Z

3 140 II9

4 126 II[

97 090 860 8" X 8" X 15' 17-3/4 6 9-5/8

41!WI 251 4EWI 25Z

4 175 150 4 210 178

130 I +25 839 8" X 8" X 15' 17-314 6 9-5/8 155 150 82.4 8" X 8" X ] 5' 17-3/4 6 9-5/8

41LWl 501 4EWl 50Z

5EWI 20'I 5EWI 20Z 5EWI.75 I 5EWI 75Z

128 1+20 865 8" X 8" X 15' 21 6 1 I-I/2

5 245 209 5 280 236

182 1.75 836 8" X 8" X 15' 21 6 11-1/2 205 2 00 820 8" X 8" X 20' 21 6 [ I-I/2

5[-W2 00"[ SEW200Z

*MBH 1,000 BTU per hour BTU British Thermal Unit +'*Heating Capacity based on 13% CO2 with a -0.02" w.c draft over fire, and a #1 smoke or less. Testing was done in accordance with the D.O.E.

(Department of Energy) test procedure. _GPB Gallons per hour oil at 140,000 BTU per gallon + _A F U E. = Annual Fuel Utilization Efficiency based upon DOE test procedure.

These low pressure oil fired hot water boilers are constructed and hydrostatically tested for a maximum working pressure of 50 psig (pounds per square inch gage) in accordance with A.S.M.E. (American Society of Mechanical Engineers) Boiler and Pressure Vessel Code Section IV Standards for heating boilers.

The Heating Capacity indicates the amount of heat available after subtracting the losses up the stack. Most of this remaining heat is available to heat water. A small portion is heat from the jacket and surfaces of the boiler, and it is assumed that this heat stays in the structure. The Net I=B=R Rating represents the portion of the remaining heat that can be applied to heat the radiation or terminal units (i.e. finned tube baseboard, cast iron radiators, radiant floor, etc.). The difference between the Heating Capacity and the Net I=B=R Rating, called the piping and pickup allowance, establishes a reserve for heating the volume of water in the system and offsetting heat losses from the system piping. The Net I=B-R Ratings shown are based on a piping and pickup factor of 1.15 in accordance with the I-B-R Standard as published by the Hydronics Institute. The Net I=B=R Rating of the boiler selected should be greater than or equal to the calculated peak heating load (heat loss) for the building or area(s) served by the boiler and associated hot water heating systems. The manufacturer should be consulted before selecting a boiler for installations having unusual piping and pickup requirements.

Boilers with the same number of sections are identical to each other except for their firing rate. The firing rate is

deternuned by the nozzle size in the oil burner and the oil pressure at the nozzle. For example: Models 3E.65Z, 3E.75Z, and 3El .00Z are the same boiler, without a tankless coil, except for the firing rate of the oil burner.

Models 4E.90T, 4El .25T, and 4El.50T are the same boiler, with a tankless coil, except for the firing rate of the oil burner.

Each boiler rating plate shows three possible model nutnbcrs for a given boiler configuration. The actual model tmnaber is determined by the firing rate of the oil burner. Boilers that are factory packaged include two nozzles for two firing rates. These boilers operate on #2 Heating Oil.

3 91 80 · 3 105 92 · 5 168 147

Page 5 of the Kenmore Oil Boiler (4EW1.50) user manual — WARNING
Page 5 · click to enlarge
Page 5
Kenmore Oil Boiler (4EW1.50) — RULES FOR SAFE INSTALLATION AND OPEIL_TION diagram (page 5)
Fig. 5

RULES FOR SAFE INSTALLATION AND OPEIL_TION

1. Read the Owner's Manual for Safe Operation carefidly. Failure to tbllow tile rules tbr sale operation and the instructions can cause a malflmction of the boiler and resuh in death, serious bodily injury, and/or property damage. 2. Check your local codes and utility requirements before installation. The installation nmst be in accordance with their directives, or follow NFPA 31 - Installation of Oil Burning Eqnipment, latest revision. 3. Before serTicing, allow boiler to cool. Always shut offany electricity and oil to boiler when working on it. 4. Inspect oil line and connections for leaks. 5. Be certain oil burner nozzle is the size required. Overfiring will result in early failure of the boiler sections. This will cause dangerous operation. 6. Never vent this boiler into an enclosed space. Always vent to the outside. Never vent to another room or inside a building. 7. Be sure there is adequate air supply for complete combustion. 8. Follow a regular service and maintenance schedule for efficient and safe operation. 9. Keep boiler area clean and free of combustible material, gasoline and other flammable vapors and liquids. 10. Oil burners are not do-it yourself items. This boiler must be installed and serviced by qualified professionals using combustion test instruments. 11. Be aware when piping the relief valve that if the system pressure exceeds the safe limit of 30 pounds per square inch, the relief valve will automatically lift open. Lifting of the relief valve can discharge large quantities of steam and hot water, which may damage the surroundings. Before installing the relief valve read the manufacturer's instructions and maintenance section of the manual on relief valves.

12. Installation and sizing of the expansion tank must consider the heating systems total water volume, temperature, boiler initial fill pressure, and system arrangement. An improperly installed and sized expansion tank may result in frequent lifting of the relief valve or other heating system problems. For proper installation, sizing, and maintenance of the expansion tank follow the guidelines established by Dunkirk Radiator Corporation and the expansion tank manufacturer. 13. Expansion tank performance and life expectancy can be hindered by overfilling the boiler. Dunkirk Radiator Corporation recommends an initial fill pressure of 10-12 psig. For higher fill pressures the expansion tank's air charge will need to be increased to match the fill pressure. Consult the manufacturer's guidelines for sizing and selection. 14. Purging the heating system of air and gases when first putting the boiler's into service is critical for proper circulation and quiet performance. Once the air and gases are purged, for boiler installations using float type vents, the air vents should be closed for normal operation. If air is heard or noticed by a loss of heat, purge the system and open the vents for a short period of time.

WARNING

This boiler has been designed for residential installations. If used for commercial applications,

all jurisdictional requirements must be met. This may require wiring and/or piping modifications. The manufacturer is not responsible for any changes to the original design.

I DO NOT USE GASOLINE CRANKCASE DRAININGS OR ANY OIL CONTAINING GASOLINE. [

Page 6 of the Kenmore Oil Boiler (4EW1.50) user manual — O
Page 6 · click to enlarge
Page 6
Kenmore Oil Boiler (4EW1.50) — BEFORE YOU START diagram (page 6)
Fig. 6

BEFORE YOU START

Complete all of the following prior to installing the boiler.

A. Check to be sure you have selected the right size boiler with the proper capacity. The I=B=R rating of the boiler

selected should be greater than or equal to the calculated peak heating load (heat loss) for the building or area(s) served by the boiler and associated hot water heating systems. See boiler rating and capacity table previously listed in this manual. Any heat loss calculations used should be based on approved methods. B. Boiler rdust be supplied with the proper oil supply and oil piping, sufficient fresh combustion air, and a suitable

electrical supply. C. Boiler must be connected to a suitable venting system and a piping system adequate to distribute the heating load. D. A thermostat must be properly located and installed for control of the heating system.

If there are any doubts as to the various requirements, check with local authorities and obtain professional help where needed. The OPERATING INSTRUCTIONS, FINAL CHECKS AND ADJUSTMENTS, and MAINTENANCE sections in this manual are vital to the proper and safe operation of the heating system. Take the time to be sure they are all done.

LOCATING THE BOILER

1. Place the boiler in a location centralized with the piping system and as close to the chimney as possible. 2. The boiler must be level. If necessary use metal shims beneath the boiler's feet. 3. Use a raised base if the floor can become wet or damp. 4. Maintain clearances for fire safety as well as servicing. An 18" clearance must be maintained at a side where

passage is required for access to another side for cleaning, servicing, inspection, or replacement of any parts that normally may require such attention. Boilers must be installed at least 6" from combustible material on all sides and above. Allow at least 24" front clearance for servicing. 5. Fresh air for combustion must be available at the front of the boiler. Fresh air for ventilation must be available to the front AND rear of the boiler. Air passages must be free of obstructions at all times. Ventilating and combustion air must enter boiler room without restrictions.

6. The floor supporting the boiler must be non-combustible and sufficiently stable. If it is combustible, place the boiler on 2" concrete patio blocks or 2" Cladlite TM Pad. The blocks or pad must be under the entire boiler to

protect the floor. 7. Be sure installation is in accordance with the requirements of the local authorities having jurisdiction. Compliance with these regulations is required. In the absence of local codes, follow NFPA 31 - Installation of Oil Burning

Equipment, latest revision.

MINIMUM CLEARANCE DIMENSIONS

,'x. _C

6" MIN.

41 24" MIN. +

_[ BOILER L 6" MIN.

v _FRONT t "q t

O

6" MIN. / 18" WITH COIL A_

f_ · co'

Page 7 of the Kenmore Oil Boiler (4EW1.50) user manual — OIL RLTER
Page 7 · click to enlarge
Page 7
Kenmore Oil Boiler (4EW1.50) — I_NSTALLATION REQUIRELMENTS 1 diagram (page 7)
Fig. 7

I_NSTALLATION REQUIRELMENTS 1

ALWAYS KEEP TILE NL_NUAL FUEL SUPPLY VALVE SHUT OFF, IF THE BUI_NER IS SHUT DOWN FOR AN EXTENDED PERIOD OF TIa_clE.

ELECTRIC LINE AUTOMATIC

FILL VALVE NOSHUTOFF

EXPANSION TANK

DRAFT REGULATO_

MIN 2" VENT PIPE

LINES TO OTHER APPLIANCES

RELIEF VAI

TO OUTSIDE

,TION

OIL TANK

,FROM RADIATION

CIRCULATIHG

SHUT OFF VALVE

RETURN LINE OR AbTER TI-I]£ EXPANSION TANK

OIL RLTER

2** · FI LL PiPE · VENT PiPE

Page 8 of the Kenmore Oil Boiler (4EW1.50) user manual — VENTILATING I GRILLE 1
Page 8 · click to enlarge
Page 8
Kenmore Oil Boiler (4EW1.50) — FRESH AIR FOR COMBUSTION diagram (page 8)
Fig. 8

FRESH AIR FOR COMBUSTION

combustion and assures that no hazard will develop due to the lack of oxygen.

I NOTE [ If you use a fireplace or a kitchen or a bathroom exhaust fan, you should install an

outside air intake. These devices will rob the boiler and water heater of combustion air.

You must provide enough flesh air to assure proper combustion. The fire in the boiler uses oxygen. It must have a continuous supply. The air in the house contains only enough oxygen to supply the burner for a short time. Outside

air must enter the house to replace the air used by the burner. Study the following examples 1 and 2 to determine your fresh air requirements.

EXAMPLE 1Boiler Located in Unconfined Space

If your boiler is in an open area (unpartitioned basement) in a conventional house, the air that leaks through the cracks around the doors and windows will usually be adequate to provide air for combustion. The doors should not fit tightly. Do not caulk the cracks around the windows.

An unconfined space is defined as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour of the total input rating of all appliances installed in that space.

EXAMPLE 2: Boiler Located in Confined Space

A. All Air from Inside the Building: The confined space shall be provided with two permanent openings communicating directly with an additional room(s) of sufficient volume so that the combined volume of all spaces meets the criteria for an unconfined space. The total input of all combustion equipment installed in the combined space shall be considered in making this determination. Each opening shall have a minimum free area of one square inch per 1,000 Btu per hour of the total input rating of all combustion equipment in the confined space, but not less than 100 square inches. One opening shall be within 12 inches of the top and one within 12 inches of the bottom of the enclosure.

Example: Your boiler is rated at 100,000 Btu per hour. The water heater is rated at 30,000 Btu per hour. The total is I30,000 Btu per hour. You need two grilles, each with 130 square inches of FREE opening. Metal grilles have about 60% FREE opening. To find the louvered area needed, multiply the free opening required by 1.7 (130 x 1.7 = 221.0 sq. in. louvered area). In this example, two grilles each having an 8" x 30" (24-0 sq. in.) louvered area would he used.

AIR OPENINGS FOR BOILER LOCATED IN CONFINED SPACE (CLOSET OR UTILITY ROOM)

VENTILATING I GRILLE 1

I I'

COMBUSTION AIR GRILLE

Page 9 of the Kenmore Oil Boiler (4EW1.50) user manual — FRESH AIR
Page 9 · click to enlarge
Page 9
Kenmore Oil Boiler (4EW1.50) — FRESH AIR diagram (page 9)
Fig. 9

B. All Air from Outdoors: The confined space shall be provided with two permanent openings, one commencing within 12 inches of the top and commencing within 12 inches of the bottom of the

enclosure. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.

1. When directly communicating with the outdoors, each opening shall have a minimum free area of

one square inch per 4,000 Btu per hour of total input rating of all equipment in the enclosure.

2. When communicating with the outdoors through vertical ducts, each opening shall have a minimum

flee, area of one square inch per 4,000 Btu per hour of total input rating of all equipment in the enclosure.

3. When communicating with the outdoors through horizontal ducts, each opening shall have a

minimum free area of one square inch per 2,000 Btu per hour of total input rating of all equipment in the enclosure.

4. When ducts are used, they shall be of the same cross-sectional area as the free area of the openings to which they connect. The minimum dimension of rectangular air ducts shall be not less than three inches.

FRESH AIR

FRESH AIRDUCTCAPACITIESFORDUCTSSUPPLYINGFRESH _RTOBOILERINTIGHTLY CONSTRUCTED HOUSES

Fresh Air Duct Size 3J/2 '" x 12" 8" x 8" 8" x 12" 8"x 16"

*Btuh = British Thermal Units per hour based on opening covered by ¼" mesh screen, wood louvers, or metal louvers.

Show 17 more labels / short text on this page
¼" Mesh Screen · Wood Louvers · Metal Louvers · (Btuh)* · (Btuh)* · (Btuh)* · 144,000 · 36,000 · 108,000 · 256,000 · 64,000 · 192,000 · 384,000 · 96,000 · 288,000 384,000 · 512,000 · 128,000
Page 10 of the Kenmore Oil Boiler (4EW1.50) user manual — DRAIN VALVE FOR POWER PURGING
Page 10 · click to enlarge
Page 10
Kenmore Oil Boiler (4EW1.50) — SYSTEM PIPING diagram (page 10)
Fig. 10

SYSTEM PIPING

I. When the installation of the boiler is for a new heating system, first instal! all of the radiation units (panels, radiators, baseboard, or tubing) and the supply and return mains. After all heating system piping and components have been installed, make final connection of the system piping to the boiler. It is recommended to mount the circulating pump on the supply side piping, such that it pumps away from the expansion tank. Refer to the figures on the next pages.

2. A hot water boiler installed above radiation level must be equipped with a low water cut off device. A periodic inspection is necessary, as is flushing of float type devices, per low water cut off manufacturers specific instructions.

. The packaged boiler unit is set up with 1-1/4" NPT supply and return piping from the front of the boiler. The boiler supply and return piping can be moved to the rear of the boiler. The boiler should not be piped return line to the front, supply line to the rear, or vice versa, as this will cause the boiler water to short circuit the heat exchanger. Piping connections may require additional fittings and parts.

, The relief valve is meant to be installed in the back side of the rear section using the 3/4" nipple and street ell provided in the parts bag. Connect a discharge pipe of the same pipe size (3/4") to carry any water away to a drain. Do not connect directly to a drain, but leave an air gap. No shutoffof any description shall be placed between the safety relief valve and the boiler, or on discharge pipes between such safety valves and the atmosphere. Installation on the safety relief valve shall conform to the ANSI/ASME Boiler and Pressure Vessel Code, Section IV. The manufacturer is not responsible for any water damage.

5. When connecting the cold water supply to the pressure reducing valve, make sure that a clean water supply is available. When the water supply is from a well or pump, a sand strainer should be installed at the pump.

. The minimum boiler supply water temperature setting on the aquastat is 140°F. If the boiler is used in a

heating system where supply water temperatures below 140°F are desired, a suitable method, such as, the

use of bypass piping shown in the figure below, a 3 way or 4 way mixing valve, or some other means needs to be used to ensure return water temperatures to the boiler are no less than 120°F. When the boiler is

operated with return water temperatures less than 120°F, condensation may form in the boiler and venting. This condensation is corrosive and can eventually cause severe damage to the boiler and venting system.

RETURN FROM SYSTEM

MAINTAINAT LEAST12O'F IN THE BOILER RETURN. THE THROTTLINGVALVES

i/_ADJUST THE TWOTHROTTLINGVALVESTO

ARE USED FOR BYPASSPIPING,IF REQUIRED.

DRAIN VALVE FOR POWER PURGING

MAIN SHUTOFF VALVE

AUTOMATIC FILL VALVE

SUPPLY TO SYSTEM

SHUTOFF VALVE BOILERSERVICE

ISOLATIONVALVES _FILL LINE WITH SHUTOFFVALVE FILLTROLWITH AIR PURGER

BOILER DRAIN VALVE 8

THROTTLINGVALVE l CIRCULATOR · PUMP l · OffUNG VALVE

Page 11 of the Kenmore Oil Boiler (4EW1.50) user manual — UNTEM,_I[R[O HOT WAT[R
Page 11 · click to enlarge
Page 11
Kenmore Oil Boiler (4EW1.50) — SYSTEM PIPING diagram (page 11)
Fig. 11
7. Boilers may be factory packaged with a tanMess heater coil see figure below. This coil provides instantaneous heating of water for domestic use - if proper burner and water supply line controls are used.

Tankless coils are meant to provide domestic hot water for intermittent draws, no_J continuous flow.

IMPORTANT

Do not use a tankless coil if your water is excessively hard with

lime or other deposits which will accumulate inside the coil.

When using a tankless coil, the boiler has been configured so the Honeywell L8124C Combination

Hi/Low Limit Aquastat Relay mounts on a thermowell (provided) which needs to be installed in the 3/4"

tapping on the tankless coil. By mounting the aquastat on the coil, the tankless coil performance is

maximized by making the burner respond more quickly to a call for domestic hot water. A tempering

valve (mixing valve) is also recommended as shown in figure below. A flow restrictor may be required on the tankless coil inlet piping so that flow rates are matched to boiler heat input (see table below).

Burner Firing Rate (gph)

(MBH)

Rating (gpm):_ 2.90

3EW.65T

0.65 0.75 1.00 0.90 1.25 1.50 1.20 1.75 2.00

3EW.75T

3EWI.00T

4EW.90T

4EW1.25T

4EW1.50T

5EW1.20T

5EW1.75T

5EW2.00T

28O

:_ Gallons of water per minute heated from 40°F to 140°F with 200°F boiler water temperature, intermittent draw

UNTEM,_I[R[O HOT WAT[R

TANKLESS COIL

OUT

OF COLO TAp -

L___'Np

Show 4 more labels / short text on this page
Boiler Model · Tankless · Input · CENTER LINE t
Page 12 of the Kenmore Oil Boiler (4EW1.50) user manual — COPPER PIPE STEEL PIPE PIPE SIZE FACTOR FACTOR
Page 12 · click to enlarge
Page 12
Kenmore Oil Boiler (4EW1.50) — SYSTEM PIPING diagram (page 12)
Fig. 12
8. Antifreeze addedto boilers must be non-toxic, and must be of a type specifically intended for use in closed b_ydronic heating systems. Under no circumstances should automotive antifreeze be used. Antifreeze used in any boiler may reduce capacity by 10% or more and increase fuel consumption. Tankless coil performance will fall as concentration of antifreeze is increased. Refer to boiler and piping water volumes tables in this manual.

BOILER WATER VOLUMES PIPING WATER VOLUMES

Number of Boiler Sections

COPPER PIPE STEEL PIPE PIPE SIZE FACTOR FACTOR

Y2" 82.5 63.5

¾" 40.0 36.0

1" 23.3 22.2

1-1/4" 15.3 12.8

1-1/2" 10.8 9.5

2" 6.2 5.8

Divide total length of piping in feet by appropriate factor in table to determine volume in gallons.

Total Volume · (Gallons)

Page 13 of the Kenmore Oil Boiler (4EW1.50) user manual — CHIMNEY CONNECTOR AND DRAFT REGULATOR
Page 13 · click to enlarge
Page 13
Kenmore Oil Boiler (4EW1.50) — SYSTEM PIPING diagram (page 13)
Fig. 13

I or oil-fired boilers for connections to vents or chimneys, vent installations shall be in accordance with applicable provisions of INSTALLATION OF OIL BURNING EQUIPMENT, NFPA-31 - latest revision, and applicable provisions of local building codes.

CHIMNEY AND CHIMNEY CONNECTIONS

This is a very important part of your heating system. No boiler, however efficient its design, can perform satisfactorily if the chimney that serves it is inadequate. Check your chimney to make certain that it is the right size, properly constructed and in sound condition.

It is cheaper to rebuild a poor chimney than to pay excessive fuel bills. If yours is an old chimney, a new

steel liner or a new prefabricated chimney may be the best solution. The following chart shows recommended minimum chimney sizes based on Table 3 and Figure 6 of the I=B=R Testing and Rating

Standard for Heating Boilers, Sixth Edition, June 1989.

RECOMMENDED MINIMUM CHIMNEY SIZES

NOMINAL ROUND LINER - SQUARE LINER - FIRING RATE CHIMNEY CHIMNEY INSIDE INSIDE (gph) HEIGHT (ft) AREA DIAMETER I DIMENSIONS

0.60 - 1.30 15 8" x 8" 6" I 6-3/4" x 6-3/4" 1.31 - 1.80 15 8" x 8" 7" 6-3/4" x 6-3/4" 1.81 - 2.00 20 8" x 8" 8" 6-3/4" x 6-3/4" :or elevations above 2,000 feet above sea level, add 3 feet to the chimney heights. See Figure below.

For additional chimney design and sizing information, consult the ASHRAE 1996 HVAC Systems and

Applications Handbook, Chapter 30, Gas Vent and Fireplace Systems; or the National Standard for

Chimneys, Fireplaces, Vents and Solid Fuel Burning Appliances, ANSI/NFPA 211.

CHIMNEY CONNECTOR AND DRAFT REGULATOR

Venting the boiler requires a 6" diameter chimney connector pipe and using the draft regulator packed with

the boiler. Properly installed, the regulator will control the draft automatically. It is better to install it in a horizontal section of pipe, but it may be installed in an angled or vertical section of pipe. Make certain that

the "top" of the regulator is at the top - and that the short pipe section which holds the vane is horizontal.

Even though locating the draft regulator close to the chimney reduces noise, install the draft regulator as

close as practicable to the boiler.

To install the chimney connector, start at the boiler with a vertical pipe and then elbow - then install the draft regulator making it horizontal. When the regulator is in place, start at the chimney and work back to the regulator. Join the two sections with a drawband. The horizontal pipe must slope up toward the chimney at least 1/4 inch per linear foot of venting. The chimney connector must not leak and must be firmly supported. Join each of the sections with at least two sheet-metal screws. Support every second section with a stovepipe wire.

Maintain a minimum vent pipe clearance of 18" from the surface of the vent to wood and other combustible materials.

Page 14 of the Kenmore Oil Boiler (4EW1.50) user manual — .TIGHT
Page 14 · click to enlarge
Page 14
Kenmore Oil Boiler (4EW1.50) — SYSTEM PIPING diagram (page 14)
Fig. 14

TYPICAL CHIMNEY CONNECTION

MUST BE REQUIRED MIN- IMUM HEIGHT• MUST RE AT LEAST 3 FT. HIGHER THAN HIGHEST PART QF PASSAGE THROUGH

ROOF. MUST BE AT LEAST 2 FT. HIGHER THAN ANY NEIGHBORING OBJECT. MUST HAVE AN UNOBSTRUCTED TOP OPENING.

MUST BE AT LEAST 4 INCHES THICK- AND BE TIGHT.

DRAFT REGULAT( VANE

MUST SLOPE UP AT LEAST 1/4 INCH PER FOOT OF

TIGHT, SMOOTH, CORRECTLY SIZED. I I !

HORIZONTAL RUN

CRIMPEDENO

BALANCED WEIGHT

DRAWBAND LAST PIECE INSTALLED

  • SEALED IN THIMBLE

.TIGHT

CLEAN-OUT

DOOR

ALTERNATE POSITIONS

. TOP

Page 15 of the Kenmore Oil Boiler (4EW1.50) user manual — ,_24 VOLT
Page 15 · click to enlarge
Page 15
Kenmore Oil Boiler (4EW1.50) — SYSTEM PIPING diagram (page 15)
Fig. 15

ELECTRICAL CONNECTIONS

Thermostat

Install a 24-volt thermostat (not provided) in a proper location. The location of the thermostat has an important effect on boiler system operation. BE SURE TO FOLLOW THE INSTRUCTIONS INCLUDED WITH THE THERMOSTAT.

Grounding Permanently ground the boiler according to local codes and the National Electrical Code. Run a 14 gauge or heavier copper wire from the boiler to a grounded connection in the service panel or a properly driven and electrically grounded ground rod. I

Electric Power Supply All electrical work must conform to your local codes as well as the National Electrical Code. If you are not familiar with wiring and codes in general, have a competent electrician do this job.

On packaged boilers, the boiler controls are all wired at the factory. You need only connect a 115 volt

electrical supply to the L1 and L2 terminals on the aquastat relay and two thermostat wires to the T and T

terminals on the same aquastat relay (see figure below).

Run a separate circuit from a separate overcurrent protection device in your electrical service entrance panel. This should be a 15 ampere circuit. Locate a shut-off switch at the boiler. It must be turned offduring any maintenance. Solder and tape or securely fasten these connections with wire nuts.

Oil Burner Wiring For boilers packaged with oil burners, the burners are wired at the factory. For boilers shipped knockdown or packaged without a burner, wiring connections are shown in the electrical wiring diagrams of this manua!.

115V 60 CYCLE N H SUPPLY It

,_24 VOLT

THERMOSTAT II

AQUASTAT

RELAY

Page 16 of the Kenmore Oil Boiler (4EW1.50) user manual — SEARS ROEBUCK AND COMPANY
Page 16 · click to enlarge
Page 16
Kenmore Oil Boiler (4EW1.50) — SYSTEM PIPING diagram (page 16)
Fig. 16

SE_/ARS

KENNMORE CAST IRON BOILERS

FULL ONE YEAR WARRANTY ON HOT WATER AND GAS STEAM CAST IRON BOILERS

For one (1} year from the date of installation,when this boiler is installed and maintained in accordance

with our instructions Sears will repair defects in material or workmanship in the boiler, free of charge.

LIMITED 12 YEAR WARRANTY ON STEAM CAST IRON BOILERS

%_ After one (1)year and through twelve (12)years from the date o| installation,Sears will furnish a replacement

heat exchanger, if the heat exchanger in the boiler is defective. YOU PAY FOR LABOR. __ LIMITED 20 YEAR WARRANTY ON HOT WATER CAST IRON BOILERS After one (! }year and through twenty (20) years from the date of installation,Searswill furnisha replacement

heat exchanger if the heat exchanger in the boiler is defective. YOU PAY FOR LABOR.

SEARS INSTALLATION WARRANTY In addition to any warranty extended to you on the Sears merchandise involved, which warranty becomes effective the date the merchandise is installed, should the workmanship of any Sears arranged installation prove faulty within one year, Sears will, upon notice from you, cause such faults to be corrected at

no additional cost to you

FOR WARRANTY SERVICE, SIMPLY CONTACT THE NEAREST SEARS STORE OR SERVICE CENTER THROUGHOUT THE UNITED STATES. This warranty gives you specific legal rights,and

you may also have other rights which vary from state to state

5 If the unit _s removed from the place it was originally installed, this Warranty becomes void

1 Filter clearing or replacement

6 Damage to the unit caused by accident, abuse, negligence, m_suse, riot, fire, flood, or acts of God

2 Damage to unit or unsatisfactory operation due to improper cleaning or use of unit in corrosive atmosphere

3 Damage to unit or unsatisfactory operation due to blown fuses or _nadequate or interrupted electrical protective devices

SEARS ROEBUCK AND COMPANY

D/817WA Hoffman Estates, IL 60179

4 Damage to unit caused by the use of components or other accessories not compatible with the unit

Page 17 of the Kenmore Oil Boiler (4EW1.50) user manual — SYSTEM PIPING
Page 17 · click to enlarge
Page 17
Kenmore Oil Boiler (4EW1.50) — SYSTEM PIPING diagram (page 17)
Fig. 17
MAIN AIR VENTfor down flow systems or diaphragm type expansion tanks (not provided)

Before a system is filled with water, there is air in the pipes and radiation units• Some of the air will be

trapped as the system is filled. It is possible to eliminate most of this air through the air vents on the radiation units• A main air vent will speed and simplify this process. The main air vent should be installed

on the highest point in the supply main when all radiation is below the top of the boiler.

AUTOMATIC FILL VALVE (not provided)

For safe, efficient operation, a hot water system must be filled with water. Adding new water, when needed can be done manually (by use of a hand valve in the water supply line). This requires regular attention to the system's needs. An automatic fill valve or pressure reducing valve accomplishes this without attention. It is installed in the supply line on hot water boilers only. The valve operates through water pressure differentials. It does not require an electrical connection.

BURNER SOLENOID VALVE (provided)

The Beckett and Carlin oil burner's use a standard solenoid valve. Upon burner shut down, a standard solenoid valve stops the flow of oil to the nozzle. Without the solenoid valve, the oil pump continues to pump oil to the burner nozzle until the burner motor winds down below the pumps cut-offspeed. The Riello oil burner has a dela£ solenoid valve. The delay solenoid valve provides the same shut down action as the standard solenoid valve, plus on burner start up the delay solenoid valve remains closed for an additional 15

seconds. This allows the burner fan motor to pre-purge the combustion chamber and the oil pump to bring the supply oil pressure up to its set point helping to provide a clean light off.

AQUASTAT RELAY CONTROL (provided)

The water temperature limit control in the aquastat relay is adjustable and may be set: as low as 140°F so long as return water temperatures to the boiler are no less than 120°F, or as high as 240°F so long as the boiler and heating system have adequate circulation to remove the heat from the boiler otherwise steam may be created in the boiler. Refer back to SYSTEM PIPING section for more information.

The drain valve is a manually operated valve that provides a means of draining all the water from the boiler and heating system. It should be installed in the reducing tee where the return line enters the boiler.

CIRCULATOR (provided) Every forced hot water system requires a circulator. A separate circulator or zone valve is required for each zone, if there are two or more zones. The circulator must have the capacity to provide the circulation required by the heating system. The circulator should be connected to the supply main and must be wired into the boiler's electrical system. See the SYSTEM PIPING section for piping configurations with the circulator located on the supply main piping using zone circulators or zone valves. When the piping is arranged with zone circulators and no bypass piping, the circulator provided with the boiler may be used as a zone circulator. Both piping arrangements allow the circulator to pump away from the expansion tank and show how the piping should be arranged to allow the heating system to be easily purged of air.

DRAIN VALVE (provided)

Page 18 of the Kenmore Oil Boiler (4EW1.50) user manual — FILLING THE SYSTEM WITH WATER
Page 18 · click to enlarge
Page 18
Kenmore Oil Boiler (4EW1.50) — SYSTEM PIPING diagram (page 18)
Fig. 18

FILLING THE BOILER

HOW A HOT WATER SYSTEM OPERATES

The entire heating system (boiler, piping, and radiation units) is filled with water. As the water in the boiler

is heated, it is circulated from the top of the boiler through the supply main to the radiation units. The cooler

water in the radiation units flows back through the return piping through the return main into the boiler. This

arrangement provides positive and rapid response to the thermostat.

FILLING THE SYSTEM WITH WATER

OPTION #1 - This method utilizes the boiler piping as shown in the figure on the previous page.

a) Close the main shutoffvalve, isolation valves, and zone valves (if applicable). If bypass piping is

installed, also close the two throttling valves. Leave the boiler service shutoffvalve (if installed) and the

balancing valves to each heating zone fully open.

b) Ooen the following valves in order: the drain valve for power purging, isolating valves before and after the boiler circulator (if applicable), both throttling valves (if applicable), and then open the fill line shutoff valve. Water will fill the bypass piping and push the air through the piping and out the power purging drain valve. When the power purging drain valve runs air free, close the bypass piping throttling valve (leaving the throttling valve to the supply piping f_lly open).

c) Next, ooen the isolation valve (or zone valve) to the first zone. Water will fill the piping and push any air out the power purging drain valve. When the power purging drain valve rims air free, close the isolation valve or zone valve). Repeat this procedure for the remaining heating zones.

d) Once all zones are filled with water and purged of air, close the power purging drain valve and fill line shut off valve, open the main shutoff valve, and adiust the throttling valves and balancing valves as required.

OPTION #2 - Close the air vents on all radiation units. Open the valves to the radiation units. Make sure

the boiler drain valve, expansion tank drain cock, and the air bleed screw "on the expansion tank drain fitting

are closed. Open the fill valve on the piping to the expansion tank. Open the water inlet to the boiler and leave it open. Open the air vent on the lowest radiation unit. When all the air has escaped and water starts to

flow from the vent, close it. Go to the next radiation unit, and repeat this process until finishing with the

highest radiation unit. If the heating system has automatic vents, this manual venting is unnecessary but it will speed up the proper filling of the system.

If the system is a closed expansion tank system, an automatic fill valve is needed. Leave the automatic fill valve open to refill the system automatically as needed. Note the initial fill pressure on the boiler's

temperature / pressure gauge, which should be 10-15 psig. Any lowering of the pressure from its initial fill pressure indicates a loss of water due to leakage. The automatic fill valve should then compensate for this

water pressure loss. If it does not, manually open this valve to refill the system until the needle is again

pointing to the same pressure reading. Instructions are packaged with the valve.

Page 19 of the Kenmore Oil Boiler (4EW1.50) user manual — RIELLO 40 OIL BURNER, NOZZLE_ AND AIR SETTINGS
Page 19 · click to enlarge
Page 19
Kenmore Oil Boiler (4EW1.50) — SYSTEM PIPING diagram (page 19)
Fig. 19

BECKETT OIL BURNER, NOZZLE, AND AIR SETTINGS

_BOILER

DELEVAN OIL NOZZLE

FIRING

HEAD-ADJ. OR SETTING

LOW FIRE

AIR SHUTTERIBAND

STATIC

OIL BURNER

MODEL

BAFFLE

PLATE

3EW 65* 3EW.75 3EW1.00

0.50-80°B 0.65-70°B 0.85-70°B

0.65 0.75 1.00

F0 - 1 1/8 F3 - 1 1/8 F3 - 1 1/8

YES

AFG F-HEAD AFG F-HEAD AFG F-HEAD

YES

NO

4EW.90 4EW1.25 4EW1.50

O.75-80OA

0.90 1.25 1.50

F31 1/8 F6 - 1 1/8

NO NO

AFG F-HEAD AFG F-HEAD

1.00-80°A 1.25-80°A

F6 - 1 1/8

NO

AFG F-HEAC

AFG 50 MD AFG 50 MD

5EW1.20 5EW1.75 5EW2.00

1.00-60°13 1.5045°B 1.65-60°B

1.20 1.75 2.00

NO NO NO

10/1.5 10/4 10/5

AFG 50 MD

*To fire the 3EW.65 on rate, the oil pressure must be increased to 175 psig. All Beckett oil burners for the EW boiler are factory preset at 140 psig.

CARLIN OIL BURNER 1 NOZZLE, AND AIR SETTINGS

BOILER DELEVAN FIRING HEAD AIR BAND CARLIN MODEL OIL NOZZLE RATE (gph) SETTING SET POINT BURNER* 3EW.65 0.55-700B 0.65 0.50 0.52 EZ-1 HP 3EW.75 0.65_600B 0.75 0.60 / 0.65 0.60 EZ-1 HP 3EW1.00 0.85-60°B 1.00 0.85 / 1.00 0.80 EZ-1 HP 4EW.90 0.75-60°B 0,90 0.75 0.75 EZ-1 HP 4EW1.25 1.00-60°B 1.25 0.85 / 1.00 0.90 EZ-1 HP 4EW1.50 1.25-60°B t.50 1.10 / 1.25 1.25 EZ-1 HP 5EW1.20 1.00-60°B 1.20 0.85 / 1.00 0.90 EZ-1 HP 5EW1.75 1,50-60°B 1.75 1.50 1.65 EZ-2 HP 5EW2.00 1.65-70°B 2.00 1.65 / 1.75 1.95 EZ-2 HP

*All Carlin EZ-1 HP and EZ-2 HP oi] burners are factory preset at 150 psig.

RIELLO 40 OIL BURNER, NOZZLE_ AND AIR SETTINGS

BOILER DELEVAN FIRING TURBULATOR / AIR OIL PRESSURE RIELLO 40

MODEL OIL NOZZLE RATE (gph) SHUTTER SETTING (PSIG)* BURNER MODEL 3EW.65 0.50-70°W 0.65 0.5 / 2.0 155 F5 3EW.75 0.65-70°W 0.75 2.0 / 2.2 150 F5 3EW1.00 0.85-70°W 1.00 2.0 / 3.2 170 F5 4EW.90 0.75-70°W 0.90 1.5 / 2.6 160 F5 4EW1.25 1.00-70°W 1.25 2.5 / 3.8 170 F5 4EW 1.50 1.25-70°W 1.50 4.0 / 7.0 175 F5 5EW1.20 1.00-70°W 1.20 2.5 / 3.5 150 F5 5EW1.75 1.50-70°W 1.75 2.0 / 38 155 F10 5EW2.00 1.75-70°W 2.00 2.5 / 4.1 155 F10

*All Riello 40 F5 and F10 oil burners are factory preset at 145 psig.

overfire draft of -0.02 inches w,c. The burner settings provided

I NOTEAll burners use an inserti°n depth °f 2-1/4'' and fired at a I

are intended for initial start up only. Final adjustment must be made

using combustion test instruments.

Show 7 more labels / short text on this page
RATE (gph) · 10/0 · 3-5/8 3-1/2 3-1/2 · 10/0 10/2 · 8/0 10/0 10/2 · 3-1/2 3-3/8 3-3/8 · 2-3/4 2-3/4 2-3/4
Page 20 of the Kenmore Oil Boiler (4EW1.50) user manual — use parts recommended by the burner manufacturer. I
Page 20 · click to enlarge
Page 20
Kenmore Oil Boiler (4EW1.50) — SYSTEM PIPING diagram (page 20)
Fig. 20

NOZZLES AND ELECTRODES: Use the proper size, spray angle, and spray pattern nozzle. Refer to the recommended nozzle selection charts at the end of this manual. To install a nozzle, remove the nozzle line electrode assembly, if necessary remove the retention ring assembly, and then install and tighten the nozzle. Be careful not to damage the electrode insulators or the bend the electrode tips. After installing the nozzle, reassemble the nozzle line electrode assembly and set the electrode tip spacing. Depending on the bumer purchased, the electrode tip spacing may need to be set prior to reassembling the nozzle line electrode assembly. Refer to the figures on the following pages for setting the electrode tip spacing on Beckett, Carlin, and Riello t_umers.

FINAL BURNER ADJUSTMENTS: Final burner adjustments must be made using combustion test instruments. Initial settings for the burner are shown at the back of this manual.

Set the burner accordingly. Check the draft over fire to verify that it is between M).01" WC and -0.02" WC, otherwise adjust the draft as necessary. After operating 10 minutes to warm up the boiler, use the combustion test equipment to take a smoke reading in the flue pipe between the boiler and the draft regulator. The smoke reading should be zero to a trace (Shell Bacharach Scale). At times a new boiler requires more than 10 minutes to burn clean due to the oil film on the new heat exchanger. If the smoke reading is zero, gradually close the burner's air adjustment to obtain a smoke reading showing a trace smoke reading. Once the smoke reading is a trace, measure the COz and as an insurance margin increase the air to sufficiently reduce the CO2 by 1/2% to 1%.

Ira clean fire cannot be obtained, it will be necessary to verify the burner head and electrode alignment. Proper electrode alignment figures are presented on the following pages. If the fire continues to be smoky, replace the nozzle with a correct replacement.

Once the burner is completely adjusted, the burner should be started and stopped several times to assure good operation with no fluttering or rumbling. Verify that there are no oil leaks and then record the nozzle size, oil pressure, combustion readings, and air settings on a tag or label that can be attached to the burner or boiler.

OIL BURNER MAINTENANCE: For the Becket/: AFG, Carlin EZ-1 or EZ-2, and the Riello 40 F3, F5, or F10 the following preventative maintenance items should be performed annually, preferably prior to the heating season.

1. Oil Burner Motor - For Beckett and Carlin burners, add 2 -3 drops of non-detergent electric motor oil to each oil cup located at the front and rear of the motor (Riello burners are permanently lubricated). Excessive oiling will shorten the life expectancy of the motor. 2. Fuel Filter - This should be replaced so as to prevent contaminated fuel from reaching the nozzle. A partially blocked fuel filter can cause premature failure of the fuel pump. 3. Fuel Pump Unit - Replace pump screen and clean pump unit to maintain fuel delivery to the nozzle. 4. Ignition Electrodes - Clean and adjust as per manufacturer's recommendations, so as to maintain reliable ignition of oil. 5. Nozzle - Replace so as to maintain safe and reliable combustion efficiency. Always replace with the exact nozzle as required in the charts in the back of this manual. 6. Fan and Blower Housing These must be kept clean, free of dirt, lint and oil so as to maintain the proper amount of air the fuel requires to burn. 7. Check the final burner adjustments.

use parts recommended by the burner manufacturer. I

I NOTEIf any component parts must be replaced, always I
Page 21 of the Kenmore Oil Boiler (4EW1.50) user manual — _ELECTROOE
Page 21 · click to enlarge
Page 21
Kenmore Oil Boiler (4EW1.50) — SYSTEM PIPING diagram (page 21)
Fig. 21

BECKETT AFG BURaNER ELECTRODE ADJUSTMENTS VARIABLE (VI) HEADS

BOILER MODEL 5EW

DIMENSION "'N" DIMENSION "H"

(electrode to nozzle) (head to nozzle) 1/16" 7/32" to 9/32"

lMENSION "}'1" SEE BELOW--\_

5132 ,,. CTROOE GAP " " _ ..,a

LI or VI HEAD _.. _DIMEMBION -N"

E B£LOW

BECKETT AFG VARIABLE (V1) HEAD ADJUSTMENTS AND SETTINGS

_Lfrl LOC:I w&Ja4_

/_" s_JUST,UK.( ).4[A0

A_lr T'Jll.(

BECKETT AFG BURNER ELECTRODE ADJUSTMENTS FHEADS

Burner F-Head Model DIMENS1ON"N" (head to nozzle) F0 thru F31 1/16"

_ELECTROOE

.E

Page 22 of the Kenmore Oil Boiler (4EW1.50) user manual — TO
Page 22 · click to enlarge
Page 22
Kenmore Oil Boiler (4EW1.50) — SYSTEM PIPING diagram (page 22)
Fig. 22

5/32" - 4 mm

,)-

5/64" to 7/64" or 2 to 2.5 m[__ "_

5/32" or 4 mm

E E

5/32" to 13/64" or 4 to 5 mm _ I _

TO

Page 23 of the Kenmore Oil Boiler (4EW1.50) user manual — ADJUST THERMOSTAT HEAT ANTICIPATOR TO: 0.2 AMPS
Page 23 · click to enlarge
Page 23
Kenmore Oil Boiler (4EW1.50) — SYSTEM PIPING diagram (page 23)
Fig. 23

CHECKING AND ADJUSTING CONTROLS

A boiler using a tankless coil is configured with a Honeywell L8124C Combination Hi/Low Limit Aquastat

Relay (refer back to the SYSTEM PIPING section for more details). A boiler not using a tankless coil is

configured with a Honeywell L8148A Hi Limit Aquastat Relay. Instructions for the control provided are included with the boiler.

ADJUST OPERATING CONTROLSFor both aqaustats, use the following settings for the first

adjustment:

High LimitBaseboard and Convectors - 200°F

Standing Radiators - 180°F

Low Limit (when used) - 140°F ( increase if hotter domestic water is required, but low limit set

point must be at least 20°F less than the high limit set point)

Differential (when used) - 10°F

ADJUST THERMOSTAT HEAT ANTICIPATOR TO: 0.2 AMPS

CHECK THERMOSTAT OPERATIONThe thermostat location has an important effect on the operation

of the boiler system. Be sure to FOLLOW THE INSTRUCTIONS included with your thermostat. Typically the thermostat is located about five feet above the floor on an inside wall. The thermostat should be located

to sense average room temperature, so avoid the following:

DEAD SPOTS - behind doors, corners, and alcoves

HOT SPOTS - concealed pipes, fireplace, TV sets, radios, lamps, direct sunlight, kitchens COLD SPOTS - concealed pipes or ducts, drafty stairwells or door ways, unheated room or wall of an unheated room

When the temperature on the thermostat is set above the indicated thermostat temperature, the boiler's burner should start. Make certain: once the room temperature reaches the selected temperature setting, the

thermostat should turn the boiler's burner off, and once the room temperature falls a few degrees the boiler

starts operating again. Do not start the burner unless all cleanout doors are secured in place.

unit is full of vapor, or when the combustion chamber is very hot. I

Do not attempt to start the burner when excess oil has accumulated, when the I

Page 24 of the Kenmore Oil Boiler (4EW1.50) user manual — MAINTENANCE
Page 24 · click to enlarge
Page 24
Kenmore Oil Boiler (4EW1.50) — SYSTEM PIPING diagram (page 24)
Fig. 24

MAINTENANCE

ANUALLY: To assure trouble-free operation, it is recommended that the flue passages, combustion chamber area (target wall, fire door insulation, durablanket), burner adjustment, operation of the controls, and boiler seals (fire door gasket or silicone seal, cast iron sectional seals, flue collector) be checked once each year by a competent Service Technician. Before the start of each heating season (or whenever the system has been shut down for extended periods of time) recheck the whole system for water, oil, and vent piping leaks. Replace or patch any leaks or seals that are faulty.

VENT PIPE: Visually inspect the entire venting system once a month for any signs of leakage, deterioration, or soot build up. If the vent pipe shows any signs of leaking or deterioration, replace it immediately. If it shows any signs of soot build up, clean the vent pipe and have the burner settings and combustion checked by a competent professional.

RELIEF VALVE: This valve should open automatically when the system pressure exceeds the pressure rating (usually 30 psi) of the relief valve. Should the valve ever fail to open under this condition, shut down the system. Drain the system until system pressure is reduced below the relief valve pressure rating. Then contact a competent Service Technician to replace the valve and inspect the heating system and determine the cause, as this problem may indicate an equipment malfunction. The relief valve should be tested monthly during the heating season. Prior to testing, make certain a discharge pipe is properly connected to the valve outlet and arranged so as to contain and safely dispose of boiler discharge. Hold the trip lever fully open for at least five seconds in order to flush free any sediment that may lodge on the valve seat. Then permit the valve to snap shut. Refer to the valve manufacturer's instructions packaged with the valve for more details.

CONVENTIONAL EXPANSION TANK: As noted in the EQUIPMENT AND OPTIONAL ACCESSORIES section, this tank may become water logged or may receive an excess of air. Frequent automatic opening of the relief valve indicates water logging. A high boiler temperature accompanied by unusually low radiation unit temperature (and "knocking" noises) indicates excess air in the tank. To correct either condition, close the valve between the boiler and the tank. Drain the tank until empty. Check all the tank plugs and fittings, tighten as necessary. Open the valve between the boiler and tank. Water will rise to the normal height in the tank if the system has an automatic _l valve, otherwise manually refill the system.

DIAPHRAGM EXPANSION TANK: As noted in the EQUIPMENT AND OPTIONAL ACCESSORIES section, this tank may become water logged. Frequent automatic opening of the relief valve indicates water logging. A high boiler temperature accompanied by unusually low radiation unit temperature (and "knocking" noises) indicates excess air in the tank. To correct this condition, replace the diaphragm expansion tank.

WATER SYSTEM: If the system is to remain out of service during freezing weather, always drain it completely (water left in to freeze will crack the pipes and/or boiler).

TANKLESS COIL (OR COVER PLATE) GASKET: This gasket should be checked at least twice a year for leakage and replaced if necessary. If the gasket is replaced, make sure that when the coil plate (or cover plate) is reattached that the ten nuts are torqued in an alternating pattern to ensure equal force is applied to the entire gasket creating a good seal. The nuts should be torqued such that the gasket does not squeeze out from behind the plate.

OIL BURNER: Oil burner maintenance is listed in this manual under OPERATING THE BOILER.

I Never burn garbage or paper in the unit, and I never leave combustible material around it. I

Page 25 of the Kenmore Oil Boiler (4EW1.50) user manual — IMPORTANT OPERATING AND MAINTENANCE REQUIREMENTS
Page 25 · click to enlarge
Page 25
Kenmore Oil Boiler (4EW1.50) — SYSTEM PIPING diagram (page 25)
Fig. 25

OIL BOILER / BURNER CLEANING INSTRUCTIONS

OIL BOILER CLEANING:

I. Shut off all electrical power to the boiler / burner and shut off fuel oil supply. 2. Remove the vent pipe from the top of the boiler. Inspect the pipe and chimney for signs of corrosion and deterioration. Clean out the base of the chimney. If the vent pipe shows any signs of corrosion or deterioration, replace it immediately. If chimney damage or deterioration is discovered, contact a c0mpet_nt professional. 3. Remove the top jacket panel screws (5), the brass wing nuts (2) holding the flue collector top, and then the flue collector top. Inspect the gasket on the underside of the flue collector and replace as necessary. 4. Befbre beginning to clean the flue passageways, ensure that the combustion chamber blanket is covered. If the blanket is not covered prior to cleaning, replace the blanket once cleaning is completed. 5. Now with access to the flue passageways, remove the soot from the fireside surfaces by brushing diagonally through the flue passages (see drawing below). Brushing can be made easier by cutting the end of the flue brush offand inserting it into a drill. When brushing, care should be taken so as not to damage the target wall with the flue brush. 6. Carefully vacuum the soot accumulations from the combustion chamber area, being particularly careful to not damage any of the refractory or blanket insulation. To gain access to the combustion chamber first double check that the shut offvalve on the fuel oil line is closed and then disconnect the fuel oil line. Then open the swing door by simply removing the whiz lock nut holding the door shut. 7. Now inspect the target wall, fire door refractory, and combustion chamber blanket (when included) for cracking and deterioration. If there is any signs of cracking or deterioration, replace the refractory or blanket before reassembling the burner / front plate. 8. Inspect the door's braided gasket for wear and damage. Replace when necessary with braided gasket of the same material and size. See repairs parts section of this manual. 9. Now inspect and clean the oil burner.

%r22"2.22./.'.'22:. " ot6o*mQ*ttJ*.*,

o6. .o..o 66 ... o

_, " °o'o'Z 4 °.°." ° °¢ °,'2.*.2.'-2.'.'.".'. " ° {!!{!H!!!{!!!

IMPORTANT OPERATING AND MAINTENANCE REQUIREMENTS

KEEP YOUR BOILER AND THE AREA AROUND IT CLEAN

NEVER BURN REFUSE OR ANY MATERIAL OTHER THAN THE SPECIFIED FUEL IN YOUR BOILER

[lAVE YOUR BOILER C|IECKED EACH YEAR BY A QUALIFIED TECHNICIAN

Page 26 of the Kenmore Oil Boiler (4EW1.50) user manual — OIL BURNER CLEANING:
Page 26 · click to enlarge
Page 26
Kenmore Oil Boiler (4EW1.50) — SYSTEM PIPING diagram (page 26)
Fig. 26

OIL BURNER CLEANING:

These are general instructions for cleaning an oil burner. For speci_'lcs, consult the buruer

manufacturer's instructions.

1. Make sure all electrical power to the boiler / burner and the fuel supply to the burner are shut off. 2. With the swing door open, clean any soot accumulations from the end of the burner and if applicable burner head.

3. Remove the burner drawer assembly, clean the electrodes and then reset the electrode spark gap per the manufacturer's recommendations. Refer back to the section in this manual on OPERATING THE BOILER - Nozzles and Electrodes. 4. Replace the oil nozzle with the exact same size and type recommended for use on this boiler. 5. Reinstall the burner drawer assembly making sure the head location (and size if applicable) are per the manufacturer's recommendations. If the burner being used has a damaged head, replace the head with the exact same head recommended for use on this boiler.

6. Inspect and clean the oil burner blower wheel. 7. Remove the oil pump cover and clean / replace the pump screen. Carefully reassemble ensuring the pump cover makes a proper seal. 8. Securely fasten the swing door shut. 9. Replace the fuel filter (if applicable). 10. Reconnect the electrical and fuel supplies. 11. Fire the burner, checking for proper combustion using combustion test equipment and making adjustments as necessary. Refer to the section in this manual on OPERATING THE BOILER - Final Burner Adjustments. 12. Insure that all safety controls and operating controls are functioning properly.

Page 27 of the Kenmore Oil Boiler (4EW1.50) user manual — SERVICE HINTS
Page 27 · click to enlarge
Page 27
Kenmore Oil Boiler (4EW1.50) — SYSTEM PIPING diagram (page 27)
Fig. 27

SERVICE HINTS

You may avoid inconvenience and service calls by checking these points before you call for service.

Reset thermostat above room temperature.

Thermostat is not set correctly

Boiler or Burner may be dirty

Clean all flue passages and the vent pipe. Have burner cleaned and readjusted.

Burner may not be firing at proper rate

Check nozzle size if there is any doubt. Have burner adjusted.

Burner may be short-cycling

Short-cycling (too frequent offand on) of burner will cause sooting. If boiler and!or burner become dirty at frequent intervals, after correcting the "dirty condition" also correct the aquastat control setting (or other cause of short- cycling). Check thermostat heat anticipator and correct setting, if necessary, per instruction sheet packaged with thermostat.

Check overcurrent protection. Check to be sure power supply circuit is "ON".

No power to boiler

Controls out of adjustments

Reset according to instructions packed with controls.

Open radiator vents to vent excess air. Check flow control valve (if used). It may be in closed position.

Circulating pump not running

Check relay operation.

Poor electrical contact.

Check all control terminals and wire joints.

Possible Cause 1 What to do [ Oil burner fan wheeI may be dirty ] Clean fan wheel with a stiffbrush and cleaning solvent. Readjust oil burner.

Draft regulator may be stuck Check to see if vane swings freely. Clean, if vane is stuck.

Possible Cause What to do Air in the system Open radiator vents to vent the air. Check expansion tank.

Possible Cause What to do

Dirt on seat Open valve manuaIly. Allow water to run and clear valve seat.

Water logged expansion tank Drain tank. see instructions.

HAVE YOUR SERVICE TECHNICIAN CHECK ANY PROBLEM YOU ARE UNABLE TO CORRECT.

Possible Cause · What to do · Radiators not heating

Page 28 of the Kenmore Oil Boiler (4EW1.50) user manual — .... F_LD MRING
Page 28 · click to enlarge
Page 28
Kenmore Oil Boiler (4EW1.50) — SYSTEM PIPING diagram (page 28)
Fig. 28

ELECTRICAL WIRING

BOILER WITH TANKLESS COIL AND

BOILER WITHOUT TANKLESS COIL

HONEYWELL L8124C AQUASTAT CONTROL (BECKETT AFG BURNER SHOWN)

HONEYWELL L8 !48A AQUASTAT CONTROL (BECKETT AFG BURNER SHOWN)

24 VOLT THERMOSTAT

24 VOlT THCRMO_fAT 9

POWER SUPPLY

NEUTRAL

SUPPLY ?

HOT .,_,_,_L/_,,_

NEUTRAL I I

120/60/I OV_RCURR_NT pROTECTED _SCONNECT

HOT _ BK W : :

-- )(

I_ -gL/4:X

PROTECTED OISCONNECT [_ ua12_c _ ®

C_OA COOC

B<-EU_X 0 -0R;C4GE

L8148A AQUASTAT

R--RED W -WMr_ -- U_[ _0LT_C,E

-- _ VqA.T,_CZ

-- aJ_S II. 24 _.1_

mUASTAT @j().@@ ,

Fll_l _ISeG

F_LD MRING

W

@

W

BK

IGN. TRANN

IGN. TRANS

OIL VALVE

CIRCULATOR

OIL 8URN[R

MOTOR

o

OIL BURNER MOTOR

CIRCULATOR

O CAD

Service Company:

Serviceman:

Address:

Telephone:

120V i I · w -m4qlE · ) (_

Page 29 of the Kenmore Oil Boiler (4EW1.50) user manual — AQUASTAT @J_'_(_
Page 29 · click to enlarge
Page 29
Kenmore Oil Boiler (4EW1.50) — SYSTEM PIPING diagram (page 29)
Fig. 29

BOILER WITH TANKLESS COIL AND

BOILER WITHOUT TANKLESS COIL

H ONEYWELL L8124C AQUASTAT CONTROL (CARLIN EZ BURNER SHOWN)

HONEYWELL L8148A AQUASTAT CONTROL

(CARLIN EZ BURNER SHOWN)

24 VOLT THERMOSTAT

POWER SUPPLy 24 VOLT TN[RMOSTAT

120V _ r _k POWER I i soP.LY _

N[UTRAL

N_UTRAL i i .oT _ eK w ] I

___/- B'

COLOR COOKE

81- - EC.UE

0. _*_E Y - YIDJ.OW W - _talt

L8124C _--_-'#'-(_@

-- OJ,_ a, 2,= rOt'p3

Rf_D W_IN_

AQUASTAT @J_'_(_

8K

IGN* TRAN$

IGN. TRAN$

8K BK

R W

OIL VALVE @

W OIL VALVE BK OIL BURNER

OIL BURNER

CIRCULATOR

MOTOR

BL

O CAD

0 CELL

Service Company:

Serviceman:

Address:

Telephone:

Show 8 more labels / short text on this page
t20/60/1 OVERCURRENT · RROT[CT[B DISCONNECT d · w - _ · 24 _ · L8148A _--q AQUASTAT · 8K m · k CIRCULATOR · w CELL
Page 30 of the Kenmore Oil Boiler (4EW1.50) user manual — 120/6O/I OVERCURREHT PROTECTED DISCONN[CT
Page 30 · click to enlarge
Page 30
Kenmore Oil Boiler (4EW1.50) — SYSTEM PIPING diagram (page 30)
Fig. 30

BOILERWITHOUTTANKLESSCOIL HONEYWELLL8148AAQUASTATCONTROL

BOILERWITHTANKLESSCOILAND HONEYWELLL8124CAQUASTATCONTROL

(RIELLO40BURNERSHOWN)

(RIELLO40BURNERSHOWN)

24 VOLT THERMOSTAT @

POWI[R 24 VOLT SUPPLY TH[RMOSTAT

COLO_ COOL

BKBLACX RRED

- BLACX

.oT ---_

Bt. - BLUE

E_ - 8K'G_m B.- 8U_

120/60/I OV[RCURRgNT _ I PROT[CTED D_CONNIECT L

-- LINE _.IAGI[

FI_J_ WAeK;

120/6O/I OVERCURREHT PROTECTED DISCONN[CT

L8124C AOUASTAT

L8148A AQUASTAT

E

BK

CAPACITOR

CIRCULATO R

BK

C TROL, 'AOO' W"'O 20f

COHTROL iS FACTORY WIRED Ire RIEkLO

Service Company:

Serviceman:

Address:

Telephone:

Show 7 more labels / short text on this page
tZOV · CotJ_ _ · W - ,_fqE · pOWER SUPPLY · w BK · wl · iI _ _CAPAC[TOR
Page 31 of the Kenmore Oil Boiler (4EW1.50) user manual — SEQUENCE OF OPERATION
Page 31 · click to enlarge
Page 31
Kenmore Oil Boiler (4EW1.50) — SYSTEM PIPING diagram (page 31)
Fig. 31

SEQUENCE OF OPERATION

BOILER WITH TANKLESS COIL:

INTERNAL WIRING FOR HONEYWELL AQUASTAT LS124C

Aquastat hiI_h limit controller:

The aquastat control's high limit contacts open and rum off the burner when the boiler water temperature reaches the control's high limit set point. The high limit contacts automatically reset alter the boiler water temperature drops past the set point by 10°F, which is a fixed_differential.

-- _,_=_'_ _, I 2 CN0.

Aquastat low limit and circulator control:

ILOW LtUff/I 2 T

  • With the adjustable differential at the minimum setting of 10°F:
  • On a boiler water temperature rise above the low limit set point, the burner circuit contacts (RB) break and the circulator circuit contacts (RW) make.
  • On a boiler water temperature drop of 10aF below the low limit set point, the RB contacts make and the RW contacts break.

With the adjustable differential setting greater than 10°F:

When the boiler water temperature is at (or below) the low limit set point, the RB contacts make and fire the

burner and the RW contacts break leaving the circulator off. The burner will fire until the boiler water temperature reaches the low limit set point _ the adjustable differential setting minus 10aF. At this point the RB contacts break stopping the burner and the RW contacts make. With no call for space heating, operating in this way keeps the circulator off and allows the boiler to give preference to the domestic water heating requirements. Example: Consider the boiler water temperature drops to 15OAF with the low limit set at 16OAF and the differential is set at 15°F. The burner will begin to fire. When the aquastat probe senses a boiler water temperature of l 65aF (15°F - lOaF = 5°F, then 160°F +5°F = 165°F) the RB contacts break and the RW contacts make.

When the boiler water temperature rises above the low limit / adjustable differential setting and the thermostat controls call for domestic space heating. The sequence of operation for the burner and circulator is as follows: 1. Thermostat calls for heat, completing circuit between terminals T & T on the aquastat controller, energizing the 1K relay coil.

2. With the IK relay coil energized, contacts IK1 and 1K2 are closed. Terminal B1 is energized, providing power to the oil burner primary control. This, in turn, powers the ignition coil and burner motor. 3. With the primary control energized, the burner operation starts and remains running as long as the cad cell senses flame. In the event of flame failure or the flame is not fully proven within the trial for ignition period, the primary control will lockout and open the burner circuit. This will require a manual startup of the burner. 4. As long as flame is proven through the cad cell relay, the burner will remain on until the circuit is interrupted by the boiler water temperature reaching the aquastat's high limit setting (opening high limit contacts RB), or the thermostat is satisfied breaking the T-T circuit. 5. Circulator pump is powered through terminal C1 and will mn when boiler water temperature is above the low limit setting and there is a call for heat from the thermostat. If the boiler water temperature reaches the aquastat's high limit setting and high limit contact RB is de-energized, the burner stops but the circulator pump will continue to run, as long as, the thermostat calls for heat.

6. Whenever the boiler water temperature reaches the aquastat's high limit setting, the high limit contact RB is de-energized shutting the burner off. Then the boiler water temperature must fall 10°F below the aquastat's high limit setting for the high limit contacts RB to close and the burner to be energized. 7 When the thermostat is satisfied, the call for domestic space heating is ended. Relay coil IK is de-energized, opening I K I and [K2 contacts• Both the burner and circulator pump operation stop.

[_cu_roR t_

Page 32 of the Kenmore Oil Boiler (4EW1.50) user manual — INTERNAL WIRING FOR HONEYWELL AOUASTAT L8148A
Page 32 · click to enlarge
Page 32
Kenmore Oil Boiler (4EW1.50) — SYSTEM PIPING diagram (page 32)
Fig. 32

SEQUENCE OF OPERATION

BOILER LESS TANKLESS COIL:

Aquastat high limit controller:

The aquastat control's high limit contacts open and turn offthe burner when the boiler water temperature reaches the control's high limit set point. The high limit contacts automatically reset after the boiler water temperature drops past the set point by 10°F, which is a fixed differential.

INTERNAL WIRING FOR HONEYWELL AOUASTAT L8148A

IKI

JUMPE_

IK2

-- UNE "¢OI.T_E

)

When the thermostat controls call for domestic space heating. The sequence of operation for the burner and circulator is as follows:

1. Thermostat calls for heat, completing circuit between terminals T & T on the aquastat controller, energizing the

1K relay coil.

2. With the 1K relay coil energized, contacts 1K1 and 1K2 are closed. Terminals C1 and C2 are energized

providing power to the circulator. Terminal B1 is energized, providing power to the oil burner primary control.

This, in turn, powers the ignition coil and burner motor. 3. With the primary control energized, the burner operation starts and remains running as long as the cad cell

senses flame. In the event of flame failure or the flame is not fully proven within the trial for ignition period,

the primary control will lockout and open the burner circuit. This will require a manual startup of the burner. 4. As long as flame is proven through the cad cell relay, the burner will remain on until the circuit is interrupted

by the boiler water temperature reaching the aquastat's high limit setting (opening high limit contacts BR), or

the thermostat is satisfied breaking the T-T circuit.

5. If the boiler water temperature reaches the aquastat's high limit setting, the high limit contact BR is de-

energized turning the burner off. However, the circulator pump will continue to run, as long as, the thermostat calls for heat.

6. After the high limit contact BR is de-energized, the boiler water temperature must fall 10°F below the

aquastat's high limit setting for the high limit contacts BR to close and energize the burner. 7. When the thermostat is satisfied, the call for domestic space heating is ended. Relay coil 1K is de-energized,

opening 1KI and 1K2 contacts. Both the burner and circulator pump operation stop.

-- CLa_ I,

Page 33 of the Kenmore Oil Boiler (4EW1.50) user manual — ITEM DESCRIPTION 3EW
Page 33 · click to enlarge
Page 33
Kenmore Oil Boiler (4EW1.50) — SYSTEM PIPING diagram (page 33)
Fig. 33

REPAIR PARTS

NOTES:

6ALLOON SYMBOL K_Y i

[_1 NO

_O0-F _CX _IUCQ_C _U88_R _or S_ewH i

©

ITEM DESCRIPTION 3EW

4EW

SEW ¢06-00-008 403-06-007 403`06-006 433-06-976 146-05-053 145-96-041 433-00-955 146-19-003 145-30-031 425-00-281 426-00-281 425-00-281 137-04-007 146-95-070 145-93-064 146-27-020 146-19-001 146-95-113 146-95-114 146-96-115 146-93-126 146-06-020

403-06-008 406-06-007 403*00-006 433-00-976 145-05-051 146÷95-041 433-00-955 146-19-003 146-30-031 426-00-280 425-O0-280 426-00-280 137-04-007 146-96-07(3 146-93`064 146-27-020 146-1 9-001 146-95-113 146-95-114 146-95-115 146-93-126 146-06-020

I Water Boiler Back Section (EW-3) ¢03-00-008 2 Water Boiler Mddle Section EW-2) 403-00-007 3 Empire Water Front SeclJon IEW-1) 403`00-006 4 Cast Iron Machined Nipples 2" 433-00-976 5 1/4" Tie Rods 1464354302 6 Tie Rod 1/4"-20 Hex Head Nut 146-95-041

7 5/16" x 70-1/2" Braided Rope 433-00-956 8 Target Wall 146-19-003 9 1/2" thick Ourablanket 146-30-031

10 Collector Base (plus items 11,12,13) 425-00-279 11 Insulation Tape (plus items 10,12,13) 425-09-279 12 Collector Top (plus items 10.1!,13) 425-00-279 13 8132" Brass Wing Nut 137-04-007 14 #14 x 3/4" Hex Washer Head Screw 146-96-070

15 Coil Housing Gasket 146-93-064 16 3 7 GPM Tankless Coil 146*27-020

17 Coi_ Housin 9 Cover Plate (not shown) 146-19-001 18 Stainless Steel 3/8"-16 x 1-1/2" Stud 146-95-113 19 Stainless Steel 3/8" Flat Washer 146-95-114

20 Stainless Steel 318"Top Lock Nut 146-95-115 21 1-1/4" Solid Plug Inot shown) 146-93-126 22 Black Silicone Sealant (not shown) 146-05-020

fk the appropriate boiler-- 6"x12" (3EW), 9"x20" (4EW). 12"x20" (SEW). Black silicone sealant is sold in 103 ounce cartridges.

Page 34 of the Kenmore Oil Boiler (4EW1.50) user manual — 1 2 3 4 5 6 7 8 9 10 11 12
Page 34 · click to enlarge
Page 34
Kenmore Oil Boiler (4EW1.50) — SYSTEM PIPING diagram (page 34)
Fig. 34

REPAIR PARTS

BALLOON SYMBOL KEY

NO.

&NTITY

ITEM

DESCRIPTION

Pa_ # 403-00-006 146-95-125 146-95-126 146-14-014 403-00-010 146-95-121 146-95-124 433-00-905 403-00-009 403-00-014 146-95-123 146-95-122

1 2 3 4 5 6 7 8 9 10 11 12

Empire Water Front Section (EW-1 3/8"-16 x 2-1/4" stud

Swing Door Hinge 1/4" x 2" Round Head Rivet

3/8" x 1" Hex Head Serrated Flange Bolt 3/8" x 48" Fiberfrax Round Braid

Swing Door ObServation Door

3/8" x 3/8" Shoulder Bolt 5/16"-18 Thread

Show 4 more labels / short text on this page
[_ ___1 · 3/8" Whizlock Nut · Swing Door Insulation · 5/16" Lock Washer
Page 35 of the Kenmore Oil Boiler (4EW1.50) user manual — REPAIR PARTS
Page 35 · click to enlarge
Page 35
Kenmore Oil Boiler (4EW1.50) — SYSTEM PIPING diagram (page 35)
Fig. 35

REPAIR PARTS

%

BALLOON 5YMBOL KEY

ITEM DESCRIPTION

3EW

4EW

5EW

1 Right Side iacket Panel

2 Back Jacket Panel

3 Top Jacket Panel

4 Left Side jacket Panel

5 Upper Front Jacket Panel

6 5/16" Acorn Nut

7 #10 x 1/2" Jacket Screw

9 Lower Front Jacket Panel {boiler w/swing door)

XX Complete Jacket for Boiler with Swing Door

Show 33 more labels / short text on this page
/ · / · //--_TD4 _oI · 425-00-244 · 425-00-245 · 425-00-246 · 425-00-269 · 425-00-269 · 425-00-269 · 425-00-254 · 425-00-255 · 425-00-256 · 425-00-264 · 425-00-265 · 425-00-266 · 425-00-267 · 425-00-267 · 425-00-267 · 146-95-04; · 146-95-042 · 146-95-042 · 146-95-074 · 146-95-074 · 146-95-103 · 146-95-103 · 8 Stand Off · 146-95-103 · 425-00-268 · 425-00-268 · 425-00-268 · 425-00-289 · 425-00-290 · 425-00-291
Page 36 of the Kenmore Oil Boiler (4EW1.50) user manual — .......... 146-19-006 146-19-010 146-19-010 146-19-01G
Page 36 · click to enlarge
Page 36
Kenmore Oil Boiler (4EW1.50) — SYSTEM PIPING diagram (page 36)
Fig. 36

REPAIR PARTS

WATER OUTLET

3a

OPTIONAL TANKLESS

COIL WATER HEATER WITH 1/2" NPT CONNECTIONS

Coil) 8

RIGHT SIDE VIEW

FRONT VIEW

ITEM DESCRIPTION

3EW 4EW 5EW

1 Beckett AFG F-Head Oil Burner

146-19-007 146-19-008

1 Beckett AFG Variable Head Oil Burner

146-19-009

Beckett AFG F-Head Low Fire Kit (0.65 _ph)

433-00-015 433-00-016

Beckett AFG F-Head Low Fire Kit (0.90 9ph) 1 Cadin EZ-1Oil Burner 1 Carlin EZ-2 Oil Burner

146-19-006 146-19-010 146-19-010 146-19-01G

1 Riello 40 F5 Oil Burner

1 Riello 40 F10 Oil Burner

146-19-011 433-00-521 433-00-521 433-00-521

2a L8148A-1124 Aquastat Control ( no tankless coil) 2b L8124C-!094 Aquastat Control (with tankless coil) 3a Taco 007 Circulator

146-26-047 146-26-047 146-26-047 146-26-048 146-26-048 146-26-048

3b 1-1/4" Isolation Valves

3c Taco Circulator Gaskets Taco 007 Circulator with Gaskets

146-26-050 146-26-050 146-26-050 433-00-047 433-00-047 433-00-047

4 Temperature / Pressure Gauge 2" Stem 5a 1-1/4" x 2-1/2" Pipe Nipple

146-23-003 146-23-003 146-23-003 146-07-044 146-07-044 146-07-044

146-93-049 146-93-049 146-93-049 146-22-000 146-22-000 146-22-000 146-22-011 146-22-011 146-22-011

5b 1-1/4" x 3/4" x 1-1/4" Reducing Tee 6 3/4" Drain Valve 7 3/4" Relief Valve

The temperature / pressure gauge connects to the boiler using a 3/4" x 1/4" bushing. The relief valve connects to the boiler using a 3/4" x 2" nipple and a 3/4" street elbow.

Show 8 more labels / short text on this page
j 3b · (Without · Tankle_= · colt) · 5a,5b · Tankle== · 146-19-005 146-19-005 146-19-005 · 146-62-022 146-62-022 146-62-022
Page 37 of the Kenmore Oil Boiler (4EW1.50) user manual — RIELLO 40 OIL BURNER_ NOZZLE, AND AIR SETTINGS
Page 37 · click to enlarge
Page 37
Kenmore Oil Boiler (4EW1.50) — SYSTEM PIPING diagram (page 37)
Fig. 37

BECKETT OIL BURNER_ NOZZLE, AND AIR SETTINGS

BOILER DELEVAN FIRING HEAD-ADJ, LOW FIRE AIR STATIC OIL

MODEL OIL NOZZLE RATE (gph) OR SETTING BAFFLE SHUTTER / BAND PLATE BURNER

3EW.65" 0.50-80°B 0 65 F0 - 1 1/8 YES 10 / 0 3-5/8 AFG F-HEAD 3EW 75 0.65-70°B 0.75 F3 - 1 1/8 YES 10 / 0 3-1/2 AFG F-HEAD 3EW1.00 0.85-70°B 1.00 F3 - 1 II8 NO 10 / 2 3-1/2 AFG F-HEAD

4EW.90 0.75-80°A 0.90 F3 - 1 1/8 NO 8 / 0 3-1!2 AFG F-HEAD 4EW1.25 1.00-80°A 1.25 F6 - 1 1/8 NO 10 / 0 3-3/8 AFG F-HEAD 4EW1.50 1.25-80°A 1.50 F6 - 1 1/8 NO 10 / 2 3-3/8 AFG F-HEAD

5EW1.20 1.00-60°B 1.20 0 NO 10 / 1.5 2-3/4 AFG 50 MD 5EW 1.75 1.50-45°B 1.75 2 NO 10 / 4 2-3/4 AFG 50 MD 5EW2.00 1.65-60°B 2.00 4 NO 10 / 5 2-3!4 AFG 50 MD

*To fire the 3EW.65 on rate, the oil pressure must be increased to 175 psig. All Beckett oil burners for the EW boiler are factory preset at 140 psig.

CARLIN OIL BURNER, NOZZLE, AND AIR SETTINGS

BOILER DELEVAN FIRING HEAD AIR BAND CARLIN MODEL OIL NOZZLE RATE (gph) SETTING SET POINT BURNER* 3EW,65 0.55-70°B 0.65 0.50 0.52 EZ-1 HP 3EW.75 0.65-60°B 0.75 0.60 / 0.65 0.60 EZ-1 HP 3EW1,00 0.85-60°B 1.00 0.85 / 1.00 0.80 EZ-1 HP 4EW.90 0.75-60°B 0.90 0.75 0.75 EZ-1 HP 4EW1.25 1.00-60°B 1.25 0.85 / 1.00 0.90 EZ-1 HP 4EW1.50 1.25-60°B 1.50 1.10 / 1,25 1.25 EZ-1 HP 5EW 1.20 1.00*60_B 1.20 0.85 / 1.00 0,90 EZ-1 HP 5EW1.75 1.50-60°B 1.75 1.50 1.65 EZ-2 HP 5EW2.00 1.65-70°B 2.00 1.65 / 1.75 1.95 EZ-2 HP

*All Carlin EZ-1 HP and EZ-2 HP oil burners are factory preset at 150 psig.

RIELLO 40 OIL BURNER_ NOZZLE, AND AIR SETTINGS

BOILER DELEVAN FIRING TURBULATOR / AIR OIL PRESSURE RIELLO 40

MODEL OIL NOZZLE RATE (gph)! SHUTTER SETTING (PSIG)* BURNER MODEL 3EW.65 0,50-70°W 0.65 0.5 / 2.0 155 F5 3EW.75 0.65-70°W 0.75 2.0 / 2.2 150 F5 3EW1.00 0.85-70°W 1.00 2.0 / 3.2 170 F5 4EW.90 0.75-70°W 0.90 1.5 / 2.6 160 F5 4EW1.25 1.00-70°W 1.25 2.5 / 3.8 170 F5 4EW1.50 1.25-70°W 1.50 4.0 / 7.0 175 F5 5EW1.20 1.00-70°W 1.20 2.5 / 3.5 150 F5 5EW1.75 1.50-70°W 1.75 2.0 / 3.8 155 F10 SEW2.00 1.75-70°W 2.00 2.5/4.1 155 F10

*All Riello 40 F5 and F10 oil burners are factory preset at 145 psig.

overfire draft of -0.02 inches w.c. The burner settings provided

I NOTEAll burners use an insertion depth of 2-1/4" and fired at a

are intended for initial start up only. Final adjustment must be made

using combustion test instruments,

Page 38 of the Kenmore Oil Boiler (4EW1.50) user manual — THEN RELAX
Page 38 · click to enlarge
Page 38
Kenmore Oil Boiler (4EW1.50) — SYSTEM PIPING diagram (page 38)
Fig. 38

Oi/-Fired Hot Water

Boiler

Owner's Manual

MODELNO.

3EW.65

Now that you have purchased your Bo_ler should a need ever exist for repair parts or serwce, simply coHtact an,! Sears Service Center Be sum to prowde all t:'_rt_r,,.,rll f,e_'tG when you call or ws_t

3EW.7+5

3EWI:00"

4EI/V.-90.

4EW.1_25

The model number of your Bo_ler 'wdl be tounc_ or', rl-,_ r_,_,.tel plate on the s_de of the Boder

4EWI'_50 5EW1.20

WHEN ORDERING REPAIR PARTS. ALWAYS GIVETHE FOLLOWING INFORMATION

5EWi".75

5EW2.00

=PART NUMBER

*PART DESCRIPTION

  • MODEL NUMBER

All parts hsted may be ordered from art.,, Sears Se_,,'_ce Center

If the parts you need are not slocked locally, your order

wdl be electronically transmitted to a Sears Repair Paqs

D_stnbubon Center for handhng

HOW TOORDER

When Sears arrar_ges the _nstaltat_on. you car_ be sure tl_e

REPAIRPARTS

job is done r_ghf We wdl arrange fc, r pr_Jlesslotlal

workmanship and we II take care ot th_ _.rCre proje{t

What's more dunng irislallat_orl you gel ,nstJted t_rr,lect_o¢_

TELL SEARS YOU WANTIT INSTALLED

against property damage arid also) a0ali_'_l acc_derrts

to workm(,ff-_ All yob haw to (J_) is talk t_,) yOIJ+ neare

THEN RELAX

store loday for ,ttelad,_d _lrl+)rmah_r_

eNAME OF ITEM · F_4-t_9

Ask about the Kenmore Oil Boiler (4EW1.50)

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Kenmore Oil Boiler (4EW1.50)

Be the first to ask — other owners or our team will answer.

Original document

Kenmore Oil Boiler (4EW1.50) manual PDF

41 pages·1.5 MB·Boiler·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…