536636-UIM-D-1211 SINGLE PIECE V ARIABLE SPEED AIR HANDLERS MODELS: A V*(C) SERIES INSTALLATION MANUAL ISO 9001 Certified Quality Management System LIST OF SECTIONS GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
536636-UIM-D-1211 2 Johnson Controls Unitary Products 1. Install this air handler only in a location and position as specified in SECTION III of these instructions. 2. Always install the air handler to operate within the air handler’s intended maximum outlet air t emperature.
536636-UIM-D-1211 Johnson Controls Unitary Produ cts 3 DOWNFL OW AND HORIZONT AL CONVERSION (A V ONL Y) These air handler units are supplied ready to be installed in a upflow and right hand horizontal position. If unit requires left hand positioning, the unit must have the coil assembly repositioned.
536636-UIM-D-1211 4 Johnson Controls Unitary Products CLADDING CONFIGURA TION FOR DOWNF LO W INST ALLA TION (IF USED) T o reconfigure the cladding parts, remove the grille by pulling gently at the top. Once the grille is removed, the circuit breaker cover can also be removed.
536636-UIM-D-1211 Johnson Controls Unitary Produ cts 5 DUCT CONNECTIONS Air supply and return may be handled in one of several ways best suited to the installation.
536636-UIM-D-1211 6 Johnson Controls Unitary Products TXV METERING D EVICES If the model (C) numb er is of the following format: 4F , 4G , 4H, 4J, and 4K will have the coil with R410A TXV metering device installed at the factory .
536636-UIM-D-1211 Johnson Controls Unitary Produ cts 7 DRAIN CONNECTIONS All drain lines should be trapped a minimum of three inches, should be pitched away from unit drain pan and should be no smaller than the coil drain connection.
536636-UIM-D-1211 8 Johnson Controls Unitary Products CONVENTIONAL L OW V OL T AGE CONTROL WIRING (24 V AC) The 24 volt power supply is provi ded by an int ernally wired low voltage transformer which .
536636-UIM-D-1211 Johnson Controls Unitary Produ cts 9 . * Optional dehumidificat ion hu midistat switch cont acts open on humidit y rise. NOTES : 1. “Y/Y2” T erminal on air handler control board must be con nected for full CFM and appli cations requiring 60 second blower of f delay for SEER enhancement.
536636-UIM-D-1211 10 Johnson Controls Unitary Products The low voltage connections may be connected to the screw terminals or the quick connect terminals. T he screw terminals and t he quick con- nect terminals are phy sically connected o n the control board.
536636-UIM-D-1211 Johnson Controls Unitary Produ cts 11 The control energizes the fir st stage of electric heat immediately , the second stage 10 seconds after the call for second st age heat, and the third stage 20 seconds after the call for third stage heat.
536636-UIM-D-1211 12 Johnson Controls Unitary Products SECTION VIII: AIRFLO W AND COMFORT SETTING SELECTION AIRFLOW SELECTION The airflow and comfort setting se lection jumpers must be set properly at the time of installation for proper system operation.
536636-UIM-D-1211 Johnson Controls Unitary Produ cts 13 * May be 0 (no breaker) or 1 (with breaker). TA B L E 8 : Elect rical Data - Cool ing Only (60 Hz) Models T otal Motor Amp s Minimum Circuit Ampacity Max. O.C.P . Amps/T ype 1 Minimum Wire Size A.
536636-UIM-D-1211 14 Johnson Controls Unitary Products * May be 0 (no breaker) or 1 (with breaker). TA B L E 11 : Electrical Data - (For Single Source Power Supply) - Copper W ire - 208/23 0-1-60 Models Heater Models* Heater Amps 240V Field Wiring Min.
536636-UIM-D-1211 Johnson Controls Unitary Produ cts 15 T ABLE 13: Electrical Data - 208/230-3 -60 Models Heat Kit - Three Phase Max. Stat ic Min. Spe ed Ta p To t a l H e a t 1 kW S taging kW MBH W1 Only W2 Only W1 + W2 208V 230V 208V 230V 208V 230V 208V 230V 208V 230V 24B 4HK06501025 0.
536636-UIM-D-1211 16 Johnson Controls Unitary Products T ABLE 16: Air Handler Air Flow Data HIGH/LOW SPEED COOLING AND HEA T PUMP AIRFLOW CFM m 3 /min JUMPER SETTINGS 24B 36C 24B 36C High Low High Low High Low High Low COOL T ap ADJ T ap 1088 707 1387 905 30.
536636-UIM-D-1211 Johnson Controls Unitary Produ cts 17 SECTION X: MAINTENANCE Filters must be cleaned or replaced when they become dirty . Inspect at least once per month. Th e frequency of cleaning depends upon the hours of operation and the local atmospheric conditions.
Subject to change without not ice. Published in U.S.A. 536636-UIM-D-1211 Copyright © 201 1 by Johnson Controls, In c. All ri ghts reserved. Supersedes: 536636-UIM-C-1010 Johnson Contro ls Unit a r y .
An important point after buying a device Johnson Controls AV*(C) Series (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Johnson Controls AV*(C) Series yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Johnson Controls AV*(C) Series - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Johnson Controls AV*(C) Series you will learn all the available features of the product, as well as information on its operation. The information that you get Johnson Controls AV*(C) Series will certainly help you make a decision on the purchase.
If you already are a holder of Johnson Controls AV*(C) Series, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Johnson Controls AV*(C) Series.
However, one of the most important roles played by the user manual is to help in solving problems with Johnson Controls AV*(C) Series. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Johnson Controls AV*(C) Series along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center