Solid Core and Split Core Adjustable Current “Status” Switches CSS-O, CSS-C; CSP-O, CSP-C

INSTALLATION INSTRUCTIONS

SAFETY

The current switch may be mounted in any position using the (2) #8 x 3/4 in. (19 mm) Tek screws and the mounting holes in the base or snapped directly on to the 1-3/8 in. (35 mm) DIN rail (See Figures 1 and 2). Leave a minimum distance of 1 in. (25 mm) between the current switch and any other magnetic devices, such as contactors and transformers.

WARNING

For CSS-O,C ensure that all power sources are disconnected and locked out before installation as severe injury or death may result from electrical shock due to contact with high voltage wires.

For applications in which the normal operating current is below the 0.8/2.0 Amps trip point (See Fig. 3), the conductor being monitored may be looped through the sensor 6/12 times giving you a total operating current of 6/12 times the original current.

CAUTION

This product is not intended to be used for life or safety applications.

Example:

A small fan operating at 0.2 Amps can be wrapped through the sensor 6 times to give you a total operating current of 1.2 Amps flowing through the CSS-O-A300-001. Another option is to use CSS-O- A200-001. A small fan operating at 0.2 Amps can be wrapped through the sensor 16 times to give you a total operating current of 3.2 Amps flowing through the CSP-O-A300-001. Another option is to use the CSP-O-A200-001.

CAUTION

This product is not intended for use in any hazardous or classified locations.

INSTALLATION

Make sure that all installations are in compliance with all national and local electrical codes. Only qualified individuals that are familiar with codes, standards and proper safety procedures for high voltage installations should attempt installation. The current switches will not require external power, since the power for the current switch is induced from the conductor being monitored.

Honeywell CSS-O — INSTALLATION diagram (page 1)
Fig. 1

WARNING

Never rely on the LEDs to determine whether power is present at the current switch. The red LED will indicate whether the current is above the adjustable trip point. The green LED will indicate whether the current is below the adjustable trip point.

IMPORTANT

The current switch should be used on insulated conductors only!

Fig. 1. Sensor placed on DIN rail

IND.CONT.EQ.

3JHX

62-0242—01

Page 2 of the Honeywell CSS-O user manual — WARNING
Page 2 · click to enlarge
Page 2

SOLID CORE AND SPLIT CORE ADJUSTABLE CURRENT “STATUS” SWITCHES

For applications in which the normal operating current is greater than 250 Amps or for conductor diameters larger that 3/4 in. (19 mm) in diameter, and external 5 Amps Current Transformer (C.T.) must be used as shown in Fig. 4.

Honeywell CSS-O — Latch Operation diagram (page 2)
Fig. 2 · Latch Operation
Honeywell CSS-O — Latch Operation diagram (page 2)
Fig. 3 · Latch Operation

EXAMPLE: FOR CURRENTS UP TO 600 AMPS, USE A 600:5 RATIO C.T. AS SHOWN.

Fig. 4. Current transformer Latch Operation Pressing down on the two (2) side tabs and swinging the cover open opens the split core current switch as shown in Fig. 5. Lifting up the latch with a flat-tip screwdriver as shown in Fig. 6 can also open the unit. Press down firmly on the cover to close the current switch. An audible “click” will be heard as the tab slides over the tongue on the base.

Fig. 2. Sensor removed from DIN rail

Honeywell CSS-O — Latch Operation diagram (page 2)
Fig. 4 · Latch Operation

Mating surfaces of the magnetic core are exposed when the sensor is open. Silicone grease, present on the cores to prevent rust, can capture grit and dirt if care is not exercised. Operation can be impaired if anything prevents good contact between pole pieces. Visually check the mating parts of the core before closing the current sensor.

Fig. 3. Wires through sensors

WARNING

The secondary of the 5 Amps Current Transformer must be shorted together before the power may be turned on to the monitored device.

Honeywell CSS-O — WARNING diagram (page 2)
Fig. 5

Fig. 5. Opening sensor by hand

62-0242—01 2

Page 3 of the Honeywell CSS-O user manual — 24 VAC COIL
Page 3 · click to enlarge
Page 3

SOLID CORE AND SPLIT CORE ADJUSTABLE CURRENT “STATUS” SWITCHES

Honeywell CSS-O — Wiring diagram (page 3)
Fig. 6 · Wiring

Wiring Honeywell recommends the use of a 2 conductor 16 to 22 AWG (1.3 to 0.3 mm2) shielded cable or twisted wire, copper wire only, for all current switch output applications. A maximum wire length of less than 98.4 feet (30 meters) should be used between the current switches and the Building Management System or controller.

When removing the shield from the sensor end, make sure to properly trim the shield so as to prevent any chance of shorting. The current switch output terminals represent a solid-state switch for controlling AC and DC loads and is not polarity sensitive. The recommended torque to be used on the terminal block connections is 5.93 in-lbs. (0.67 Nm). The aperture (hole) size of the current switch is 3/4 in. (19 mm) and will accept a maximum cable diameter of 350 MCM (17.3 mm). See Fig. 7 for use as a digital input to a building management system and Fig. 8 for use as a pilot relay application.

Fig. 6. Opening with a screwdriver

OPERATING SPECIFICATIONS

Max Sensing Current Voltage600 Vac

Table 1. Specifications by Product Number.

Product NumberCore TypeNormal PositionAdjustable Trip PointOutput Switch RatingMax. Current Cont.Max. Current for 6 secs.Max. Current for 1 sec. CSS-O-A300-001 SolidN.O.1.0-250 Amps0.30 Amps @ 200 Vac/Vdc250 Amps500 Amps1,000 Amps CSS-O-A200-001 SolidN.O.0.50-250 Amps0.30 Amps @ 200 Vac/Vdc250 Amps500 Amps1,000 Amps CSS-C-A300-001 SolidN.C.1.0-250 Amps0.15 Amps @ 300 Vac/Vdc250 Amps500 Amps1,000 Amps CSP-O-A300-001 SplitN.O.3.0-200 Amps0.30 Amps @ 200 Vac/Vdc200 Amps400 Amps800 Amps CSP-O-A200-001 SplitN.O.2.0-200 Amps0.30 Amps @ 200 Vac/Vdc200 Amps400 Amps800 Amps CSP-C-A300-001 SplitN.C.3.0-250 Amps0.15 Amps @ 300 Vac/Vdc250 Amps500 Amps1,000 Amps CSP-C-A200-001 SplitN.C.2.5-250 Amps0.15 Amps @ 300 Vac/Vdc250 Amps500 Amps1,000 Amps

DDC CONTROLLER

DI (STATUS)

DIGITAL INPUT #1

DO (RELAY COIL OR CONTACTOR)

BUILDING MANAGEMENT

SYSTEM

RELAY CONDITIONER

M25302

TRANSFORMER

Fig. 7. Digital circuit

24 VAC COIL

24 VAC COIL

120 VAC LINE

M23933

Fig. 8. Analog circuit

3 62-0242—01

Page 4 of the Honeywell CSS-O user manual — TROUBLESHOOTING
Page 4 · click to enlarge
Page 4

SOLID CORE AND SPLIT CORE ADJUSTABLE CURRENT “STATUS” SWITCHES

Calibration of Adjustable Trip Point The adjustable current switch has an operating range of 0-200 Amps or 0-250 Amps. Do not exceed! The adjustable current switch comes with its fifteen-turn adjustable potentiometer set counter-clockwise to its maximum position. The adjustable current switch can monitor Under load, Normal load and Overload conditions, depending on how it's set. The procedure below is for Normal load condition for part numbers CSS-O-A300-001 and CSS-O-A200-001.

Normal loads With power on and the adjustable current switch on the proper range, turn the fifteen-turn adjustment potentiometer clockwise until the red LED turns on and stop immediately. The adjustment switch is now tripped. The adjustable current switch Hysteresis (Dead Band) is 10% of the trip point typically.

TROUBLESHOOTING

ProblemSolution Red LED is on but the current switch didn’t activate.Disconnect the wires from the current switch output. Measure the resistance across the contacts with an Ohmmeter. See Table 2 below for resistance readings for a good unit. Red LED didn’t turn on and the current switch didn’t activateVerify that the conductor you are monitoring is above the adjustable trip point. If the sensor is monitoring less than the adjustable trip point, looping the wire may be required. See Fig. 3. Sensor doesn’t switch at all, regardless of current level.Adjustment potentiometer is probably set to its maximum or minimum position. Turn the potentiometer clockwise all the way and verify if the LED switches from red to green.

Table 2. Resistance Readings For Good Unit.

Product NumberResistance if switch is openResistance if switch is closed CSS-O-A300-001Greater than 1 Meg ohmsApproximately 2 ohms CSS-O-A200-001Greater than 1 Meg ohmsApproximately 2 ohms CSS-C-A300-001Greater than 1 Meg ohmsApproximately 12 ohms CSP-O-A300-001Greater than 1 Meg ohmsApproximately 2 ohms CSP-O-A200-001Greater than 1 Meg ohmsApproximately 2 ohms CSP-C-A300-001Greater than 1 Meg ohmsApproximately 12 ohms CSP-C-A200-001Greater than 1 Meg ohmsApproximately 12 ohms

Automation and Control Solutions

Honeywell International Inc. Honeywell Limited-Honeywell Limitée

1985 Douglas Drive North 35 Dynamic Drive

Golden Valley, MN 55422 Toronto, Ontario M1V 4Z9

customer.honeywell.com

® U.S. Registered Trademark © 2007 Honeywell International Inc. 62-0242—01 C.H. Rev. 06-07

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Fix-it

Troubleshooting

Common problems, likely causes, and what to do.

ProblemPossible causeRemedy
Red LED is on but the current switch didn’t activate.Disconnect the wires from the current switch output. Measure the resistance across the contacts with an Ohmmeter. See Table 2 below for resistance readings for a good unit. p.4
Red LED didn’t turn on and the current switch didn’t activateVerify that the conductor you are monitoring is above the adjustable trip point. If the sensor is monitoring less than the adjustable trip point, looping the wire may be required. See Fig. 3. p.4
Sensor doesn’t switch at all, regardless of current level.Adjustment potentiometer is probably set to its maximum or minimum position. Turn the potentiometer clockwise all the way and verify if the LED switches from red to green. p.4

Ask about the Honeywell CSS-O

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Honeywell CSS-O

Be the first to ask — other owners or our team will answer.

Original document

Honeywell CSS-O manual PDF

4 pages·602 KB·Switch·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…