SPECIFICATIONS

Models:

C645B Pressure Switches—break a circuit when pressure

C645A,C,D Pressure Switches—break a circuit when

rises to scale setting. Refer to Table 1. C645E—breaks circuit when pressure falls to scale setting

pressure falls to scale setting minus the differential. Refer to Table 1.

minus the differential. Refer to Table 1.

Table 1. Pressure switch model selection.

Scale RangeScale RangeNatural or LPSwitchingSwitch PositionDifferential Range (in. wc)Differential Range (kPa)Maximum Surge PressureMaximum Surge PressureCover Models(in. wc)(kPa)GasAirActionIndicatorNom.Max.Nom.Max.(psi)(kPa)Window C645A3 to 210.7 to 5.2YesYesAuto Recycle or LockoutaOptional130.20.7534.5Optional 5 to 351.2 to 8.7YesYesc140.21.0534.5Yes C645B3 to 210.7 to 5.2YesYesLockoutbYes130.20.7534.5Optional 5 to 351.2 to 8.7YesYesYes140.21.0534.5Yes C645C0.6 to 5.30.1 to 1.3NoYesAuto Recycle or LockoutaOptional0.20.80.050.021.510.3No 2 to 20d0.5 to 5NoYesAuto RecycleNo130.20.7534.5No C645D3 to 210.7 to 5.2NoYesAuto RecycleNo130.20.7534.5No C645E3 to 210.7 to 5.2NoYesAuto RecycleNo130.20.7534.5No
Honeywell C645A-E — SPECIFICATIONS diagram (page 2)
Fig. 1

Alternate Electrical Ratings when used with Honeywell Flame Safeguard Programmers (all C645 models):

Model120 Vac240 Vac C645AFull Load7.43.7 C645BLocked Rotor44.422.2 C645D C645CFull Load8.05.1 Locked Rotor48.030.6 C645EFull Load7.43.7 Locked Rotor44.422.2
Ignition Transformer540 VA Pilot Valve50 Main Valve250 VA with 10 times inrush. 400 VA with 2-1/2 times inrush.

ORDERING INFORMATION When purchasing replacement and modernization products from your TRADELINE® wholesaler or your distributor, refer to the TRADELINE® catalog or price sheets for complete ordering number, or specify—

1. Order number. 3. Optional specifications. 2. Air or gas control on C645A,B models. 4. Accessories, if desired.

If you have additional questions, need further information, or would like to comment on our products or services please write or phone:

1. Your local Honeywell Home and Building Control Sales Office (check white pages of your phone directory). 2. Honeywell Home and Building Control Customer Relations Honeywell, 1885 Douglas Drive North Minneapolis, Minnesota 55422-4386

In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9. International sales and service offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

60-2159—8 2

Page 3 of the Honeywell C645A-E user manual — 1/4-18 NPT
Page 3 · click to enlarge
Page 3

Switching: Spdt Micro Switch snap-acting switch (Fig. 3).

Canadian Standards Association listed: C645A-E, File no.

LR1620-369, Guide no. 140-A-2; for use subject to same ambient temperature restrictions as Underwriters Laboratories Inc. Factory Mutual Approved. Industrial Risk Insurers: C645A-D models with window in

Minimum Ambient Temperature: -20°F (- 29°C).

Maximum Ambient Temperature: 125°F (52°C).

cover approvable for applications on burners over 5 million Btuh (5 thousand cfh) input.

Connections:

Optional Specifications:

1/4-18 NPT female tapping for main or high pressure connection. 1/8-27 NPT female tapping for venting or low-pressure connection.

1. C645A with position indicator and manual reset. 2. C645A operation to 1.5 in. WC with position indicator and manual reset. 3. C645B with position indicator and manual reset. 4. C645C with position indicator and manual reset. 5. C645D with 2 in. (50.8 mm) differential.

Approvals:

Underwriters Laboratories Inc. listedC645AE File

no. MP2168, Guide no. MFHX; for use in ambient temperatures normally prevailing in occupiable spaces, which usually are not higher than 77°F (25°C) but can occasionally be as high as 104°F (40°C) for brief periods.

Accessories:

1. C645A,B,D: Mounting Bracket: part no. 15865AC. 2. C645C: Mounting Bracket: part no. 112657A. 3. C645A: Cover with Window: part no. 137637B. 4. C645B: Cover with Window: part no. 137637C.

3-1/2 (88.9)

MOUNTING BRACKET (OPTIONAL)

3/16 (2) (4.8)

4 (101.6)

3-1/2 (88.9)

4-3/4 (120.6)

1/4-18 NPT

1/8-27 NPT

3/8 (9.5)

5/8 (15.9)

3/8 (9.5) 1-1/8 (28.6)

2-1/2 (63.5) 1-5/16 (33.3)

Fig. 1. Dimensions of C645A,B,D, and E in in. (mm).

2-7/8 (73) · 60-2159—8 3

Page 4 of the Honeywell C645A-E user manual — INSTALLATION
Page 4 · click to enlarge
Page 4

3-7/8 (98.4)

Honeywell C645A-E — 9/32 (7.1) DIA. (2) diagram (page 4)
Fig. 2

9/32 (7.1) DIA. (2)

Fig. 2. Dimensions of C645C in in. (mm).

INSTALLATION

When Installing this Product . . .

Mounting The C645 has a hexagonal fitting with a 1/4 in. NPT tapping, which is the high pressure connection in differential applications. The bleed fitting is 1/8 in. NPT female tapped. In differential pressure control applications using air, connect the lower pressure to the bleed fitting (Fig. 3 and 4). In applications using combustible gases, vent the bleed tapping according to applicable standard code or jurisdictional authority.

Read these instructions carefully. Failure to follow them

could damage the product or cause a hazardous condition. Check the ratings given in the instructions and on the

product to make sure the product is suitable for your application. Installer must be a trained, experienced service

technician. After installation is complete, check out product

operation as provided in these instructions.

The C645A,B,D can be mounted in any position but are more accurate when mounted horizontally. The C645C is mounted with the diaphragm vertical and the bleed fitting at the bottom.

3-5/8 (92) · 5 (127) · 60-2159—8 4

Page 5 of the Honeywell C645A-E user manual — MANUAL RESET LEVER ON LOCKOUT MODELS ONLY
Page 5 · click to enlarge
Page 5

The C645E1002 Distillate Fuel Oil Pressure Switch is the same as the C645A1006 Gas Pressure Switch except that it does not have a 0.015 in. (0.38 mm) diameter (nominal) orifice in its 1/4 in. NPT main (high pressure) connection. (This orifice is required in a C645A Gas Pressure Switch to restrict gas leakage, but it is too small for oil applications.) The C645E1002 has a 0.125 in. (3.18 mm) diameter (nominal) opening in its 1/4 in. NPT main connection into its pressure chamber.

OPENING FOR 1/2 INCH CONDUIT MANUAL RESET LEVER ON LOCKOUT MODELS ONLY

Honeywell C645A-E — COVER SCREW diagram (page 5)
Fig. 3

Wiring Disconnect power supply before connecting wiring to prevent electrical shock and equipment damage.

COVER SCREW

SET POINT ADJUSTMENT SCREW

SCALE PLATE

BLEED FITTING

All wiring must agree with applicable codes, ordinances, and regulations. An opening is provided to accommodate rigid conduit or armored cable for line voltage operation (Fig. 3 and 4). Do not overload the switch contacts (see Switch Ratings in Specifications section). The switching schematic is shown in Fig. 5.

Fig. 4. C645C with cover removed.

SET POINT ADJUSTMENT SCREW

Honeywell C645A-E — SET POINT ADJUSTMENT SCREW diagram (page 5)
Fig. 4

SCALE PLATE

BLEED FITTING

COVER SCREW OPENING FOR 1/2 INCH CONDUIT

W

B

MICRO SWITCH

R

C645A,C,D BREAKS R-W, MAKE R-B ON PRESSURE FALL. MANUAL RESET MODELS LOCK OUT.

MANUAL RESET LEVER ON LOCKOUT MODELS ONLY

C645B BREAKS R-B, MAKES R-W ON PRESSURE RISE AND LOCKS OUT. M7565

Fig. 3. C645A,B,D with cover removed.

Fig. 5. Schematic showing switch in zero

pressure condition.

60-2159—8 5

Page 6 of the Honeywell C645A-E user manual — To Adjust Scaleplate Stop
Page 6 · click to enlarge
Page 6

SETTINGS AND ADJUSTMENTS

Pressure Setpoint Adjustment Tables 2 through 4 give the pressure and switching for each setpoint. To adjust the pressure setting, turn the setpoint adjustment screw (Fig. 3 and 4) clockwise to increase the pressure setting and counterclockwise to decrease the pressure setting.Table 4. C645C Control Points. Pressure Pressure Setpoint Switching in. of Water kPa 1a R-W makes 1 0.25 R-B makes 0.8 0.2 3b R-W makes 3 0.75 R-B makes 2.6 0.64 5b R-W makes 5 1.24 R-B makes 4.3 1.2 Top Scalec R-W makes 6 1.50 R-B makes 5.2 1.3 a Nominal differential—0.2 in. of water (0.05 kPa). Table 2. C645A,D,E control points. Pressure Pressure Setpoint Switching in. of Water kPa 3a R-W makes 3 0.8 R-B makes 2 0.5 9b R-W makes 9 2.2 15b R-W makes 15 3.7 21c R-W makes 21 5.2 R-B makes 18 4.5 35d R-W makes 35 8.7 R-B makes 31 7.7 a Nominal differential—1 in. of water (0.2 kPa). b Differential between 0.2 and 0.8 in. of water (0.05 and 1.2 kPa). c Maximum differential—0.8 in. of water (0.2 kPa). C645B1047 Scaleplate Stop Adjustment The C645B1047 is the same as the C645B1013 except for a
Honeywell C645A-E — SETTINGS AND ADJUSTMENTS diagram (page 6)
Fig. 5
SetpointSwitchingPressure in. of WaterPressure kPa 1aR-W makes10.25 R-B makes0.80.2 3bR-W makes30.75 R-B makes2.60.64 5bR-W makes51.24 R-B makes4.31.2 Top ScalecR-W makes61.50 R-B makes5.21.3
SetpointSwitchingPressure in. of WaterPressure kPa 3aR-W makes30.8 R-B makes20.5 9bR-W makes92.2 15bR-W makes153.7 21cR-W makes215.2 R-B makes184.5 35dR-W makes358.7 R-B makes317.7

Specifications Scaleplate Stop: Limits maximum setting, factory-set at 5-1/4 in. of water (1.31 kPa).

Honeywell C645A-E — SETTINGS AND ADJUSTMENTS diagram (page 6)
Fig. 6
SetpointSwitchingPressure in. of WaterPressure kPa 3aR-W makes30.8 R-B makes20.5 9bR-W makes92.2 15bR-W makes153.7 21cR-W makes215.2 R-B makes184.5 35dR-W makes358.7 R-B makes317.7 45eR-W makes4511.2 R-B makes399.8

Scale Range: 3 to 21 in. of water (0.75 to 5.23 kPa).

Adjusting Wrench: Part no. 23466 included with the C645B1047.

To Adjust Scaleplate Stop

Remove cover. Loosen scaleplate stop locking screw about 1/2 turn

counterclockwise with the 23466 Adjusting Wrench. Move scaleplate stop until bottom edge is aligned with

desired maximum setting. Tighten scaleplate stop locking screw clockwise . Replace cover.

60-2159—8 6

Page 7 of the Honeywell C645A-E user manual — C645E1002—Distillate Fuel Oil Switch
Page 7 · click to enlarge
Page 7

23466 ADJUSTING WRENCH

The C645B spring-loaded diaphragm actuates the Micro Switch snap-acting switch which breaks a control circuit, locks out, and turns on an alarm (if so wired) when the pressure rises to the scale setting. When pressure falls to the scale setting minus the differential, the switch lockout can be manually reset, turning off the alarm

LOCKING SCREW

Honeywell C645A-E — LOCKING SCREW diagram (page 7)
Fig. 7

Checkout C645A,B—Gas or Air Switch

Set cutoff pressure. Open main supply line. Depress reset lever on lockout

models until switch makes R-W. Set controller and limit switch to call for heat. For C645A—close main shutoff valve. Valve should

close when pressure reaches cutoff point. For C645B—wait a few minutes for the pressure to rise; then lower the scale setting until the switch makes R-W and locks out.

SCALEPLATE STOP

SET POINT INDICATOR

Fig. 6. Adjusting C645B1047 scaleplate stop.

Manual Resetting The C645A,C manual reset models lock out at scale setting minus the differential and require manual resetting after the pressure rises to scale setting to resume normal operation.

For C645A—reconnect the control valve, open the

shutoff valve, press the reset lever (if necessary), and return the pressure switch to its original setting. For C645B—raise setting to normal. Depress reset lever. Allow system to operate through at least one complete

The C645B locks out at scale setting and requires manual resetting after the pressure falls to scale setting minus the differential to resume normal operation. To reset, push the reset button as far as it will go; then release.

cycle to make certain all components are functioning properly.

IMPORTANT

C645C,D—Air Switch Only

Lockout models cannot be made to recycle automatically by permanently holding in the reset lever.

Set cutoff pressure. Turn on fan. If using a manual rest C645, depress and hold lever

until switch makes R-W. Block fan inlet or filter area. Switch should break R-W,

OPERATION AND CHECKOUT

make R-B when pressure drops to cutoff point. Manual reset models lock out. Remove obstruction. Depress reset lever and allow

Operation The C645A,C,D,E spring-loaded diaphragm actuates the Micro Switch snap-acting switch to break a control circuit when pressure falls to scale setting minus differential. The switch can be wired to turn on an alarm at the same time. When the pressure rises to the scale setting, the control circuit requires manual resetting to reset and turn off alarm. Optional C645A model will recycle automatically when the control circuit returns to scale setting.

system to operate through at least one complete cycle to make certain all components are functioning properly.

C645E1002—Distillate Fuel Oil Switch

The C645E1002 is the same as the C645A1006 Gas

Pressure Switch except the C645E1002 has a 0.125 in. NPT main connection in its pressure chamber. See Checkout for C645A.

60-2159—8 7

Page 8 of the Honeywell C645A-E user manual — 23466 ADJUSTING WRENCH
Page 8 · click to enlarge
Page 8

Home and Building Control Honeywell Inc. 1985 Douglas Drive North Golden Valley, Minnesota 55422

Home and Building Control Honeywell Limited-Honeywell Limitée 35 Dynamic Drive Scarborough, Ontario M1V 4Z9

60-2159—8 F.P. Rev. 5-95 www.honeywell.com/bbc

60-2159—8 8

Ask about the Honeywell C645A-E

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Honeywell C645A-E

Be the first to ask — other owners or our team will answer.

Original document

Honeywell C645A-E manual PDF

8 pages·1000 KB·Switch·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…