Instruction/ maintenance manual of the product TGC042C-3K-120 Heat Controller
Go to page of 35
T GC SERIES HIGH EFFICIENCY 13-SEER NOMINAL SIZES 3 -5 TONS P ACKAGE G AS E LECTRIC U NITS C VINTAGE ENGINEERING DESIGN GUIDE.
T ABLE OF CONTENTS Engineering Features ............................................................................... 4 Introduction ............................................................................................. 5 Selection Procedure .
MODEL NOMENCLATURE - TGC SERIES T G C Package Gas Electric Roofto p 036 Cooling Capacit y (BTUH Nominal) 036 = 36,000 042 = 42,000 048 = 48,000 060 = 60,000 C Vintage 1 Electrical Designation 1 = 208-.
ENGINEERING FEA TURES TGC Series Package Gas Electric Units 1. All models feature Copeland ® Scroll ® compressors offering maximum reliability , efficiency , and quiet operation. 2. Aluminized steel heat exchanger with in-shot burners helps eliminate corrosion.
These qualit y feature s are inc lude d in the Heat Controller P ac kage Gas Electric U nit Evaporator Coil/Filter Access • Return air filters, normally provided, are removed in this photo. T ubular Heat Exchanger • Aluminized steel (viewed from supply air side panel.
1. Determine cooling and heating requirements at design conditions. Example: T otal cooling capacity ........................43,600 BTUH Sensible cooling capacity ..................34,000 BTUH Heating capacity ................................96,000 BTUH Condenser entering air .
NOMINAL 3 TONS Model TGC036C-1K-120 TGC036C-3K-120 TGC036C-4K-120 Cooling Performance 1 Gross Cooling Capacity Btuh 37400 37400 37400 EER/SEER 2 11.7/13 11.
NOMINAL 3 .5 TONS Model TGC042C-1K-120 TGC042C-3K-120 TGC042C-4K-120 Cooling Performance 1 Gross Cooling Capacity Btuh 43000 43000 43000 EER/SEER 2 11.
NOMINAL 4 TONS Model TGC048C-1K-135 TGC048C-3K-135 TGC048C-4K-135 Cooling Performance 1 Gross Cooling Capacity Btuh 49000 49000 49000 EER/SEER 2 11.4/13.
NOMINAL 5 TONS Model TGC060C-1K-135 TGC060C-3K-135 TGC060C-4K-135 Cooling Performance 1 Gross Cooling Capacity Btuh 60000 60000 60000 EER/SEER 2 11.6/13 11.
GR OSS SYSTEM PERFORMANCE D A T A— TGC036C ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C] CFM [L/s] 1500 [707.9] 1200 [566.3] 900 [424.8] 1500 [707.9] 1200 [566.3] 900 [424.8] 1500 [707.9] 1200 [566.
GR OSS SYSTEM PERFORMANCE D A T A— TGC048C ENTERING INDOOR AIR @ 80°F [26.7°C] dbE ➀ wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C] CFM [L/s] 1940 [915.5] 1550 [731.5] 1160 [547.4] 1940 [915.5] 1550 [731.5] 1160 [547.4] 1940 [915.5] 1550 [731.
AIRFLOW PERFORMANC E — DIRECT DRIVE DIRECT -DRIVE 208 VOLT AIRFLO W PERFORMANCE External Static Pressure—Inches W .C. [kPa] CFM [L/s] Air Delivery/RPM/Watts—208 Volts Blower Size/ Motor HP [w] #.
AIRFLOW PERFORMANCE—DIRECT DRIVE External Static Pressure—Inches W .C. [kPa] CFM [L/s] Air Delivery/RPM/Watts—230 Volts Blower Size/ Motor HP [w] # of Speeds Unit Model 120,000 [35.
AIRFLOW PERFORMANCE—DIRECT DRIVE External Static Pressure—Inches W .C. [kPa] CFM [L/s] Air Delivery/RPM/Watts—460 Volts Blower Size/ Motor HP [w] # of Speeds Unit Model Motor Speed From Factory Manufacturer Recommended Air -Flow Range (Min/Max) CFM Motor Speed High CFM 1870 [883] 1830 [864] 1790 [845] 1730 [816] 80,000 [23.
Air Flow CFM [L/s] Capacity 5 T on [17.6 kW]—13 SEER Voltage 460—3 Phase 2100 [991] 860 615 915 655 955 705 1005 760 1040 820 1090 870 1130 910 1170 950 1210 995 1250 1020 1290 1060 1335 1100 1370.
ELECTRICAL DATA MODEL TGC036C-1K-120 TGC036C-3K-120 TGC036C-4K-120 TGC042C-1K-120 TGC042C-3K-120 TGC042C-4K-120 Unit Information Unit Operating Voltage Range 187-253 187-253 414-506 187-253 187-253 414-506 Minimum Circuit Ampacity 24/24 18/18 11 30/30 21/21 11 Max.
UNIT DIMENSIONS P A CKA GE GAS ELECTRIC UNITS TGR036C-TGR060C MODELS BO T T OM VIEW UNIT DIMENSIONS 18 Heat Controller, Inc. -18-.
UNIT DIMENSIONS P A CKA GE GAS ELECTRIC UNITS UNIT DIMENSIONS 19 Heat Controller, Inc. -19-.
Accessory 3-5 T on [10.6-17.6 kW] Economizer with Single Enthalapy 70 [32] Power Exhaust 19 [9] Fresh Air Damper (Manual) 11 [5] 9 [4] 16 [7] 60 [27] Fresh Air Damper (Motorized) 13 [6] Roof Curb 14&q.
*Voltage 1 = 208/230 V AC-1PH-60HZ 4 = 460 VAC-3PH-60HZ 3 = 208/230 V AC-3PH-60HZ NOTES: ➀ If a particular unit is to be converted to operate on LP (propane) for elevations above 2000 ft.
R OOFCURBS (Full Perimeter) ■ This roofcurb design can be utilized on 3 through 5 ton models. ■ T wo available heights (14" and 24" for ALL models. ■ Quick assembly corners for simple and fast assembly . ■ Opening provided in bottom pan to match the “Thru the Curb” electrical connection opening provided on the unit base pan.
■ Features Honeywell Analog Controls ■ Field installed accessory ■ Gear Driven Direct Drive Actuator ■ Fully Modulating (0-100%) ■ Low Leakage Dampers ■ Horizontal or Downflow Applications.
Illustration ST -A0903-01 FRESH AIR D AMPER RKNA 3-5 T on [10.6-17.6 kW] Models RXRF-FBA1 (Manual) RXRF-FBB1 (Motorized) INTEGRAL PO WER EXHA UST FOR ECONOMIZER RXRX-BFF04C— 208/230V - 1 phase ■ For Honeywell economizer . ■ Downflow or horizontal applications.
DUCT AD APTERS Rectangular to Round T ransitions (Downflo w) RXMC-CB03 sizes available 18" fit all units. Drops into and secures to RXKG- Series Roofcurbs.
SIDE DISCHARGE CONCENTRIC DIFFUSER RXRN-F A60 Model No. A B C D E F G H I J K Duct Size RXRN-F A60 47 5 / 8 " [1210 mm] 23 5 / 8 " [600 mm] 11 3 / 8 " [289 mm] 21 1 / 2 " [546 mm] .
FLUSH MOUNT CONCENTRIC DIFFUSER RXRN-F A70 DIMENSIONAL D A T A ENGINEERING D A T A Model No. A B C D E F G H Duct Size RXRN-F A70 47 5 / 8 " [1210 mm] 23 5 / 8 " [600 mm] 13 1 / 2 " [343 mm] 21" [533 mm] 45" [1143 mm] 22 1 / 2 " [572 mm] 11 1 / 4 " [286 mm] 10 1 / 2 " [267 mm] 18RD Model No.
THERMOST A TS GAS/ELECTRIC RECOMMENDED THERMOST A TS WITH AND W/O ECONOMIZER Single Stage Cool w/o Economizer T w o Stage Cool w/ Economizer Maple Chase—Model #09 70 Honeyw ell—Model #T7300-A1 0 0.
WIRING SCHEMA TIC—TGC060 C -1K w/X-13 29 Heat Controller, Inc. -29-.
WIRING SCHEMA TIC—TGC036/048 C -1K w/PSC 30 Heat Controller, Inc. -30-.
WIRING SCHEMA TIC—TGC036/060 C -3K w/PSC 31 Heat Controller, Inc. -31-.
WIRING SCHEMA TIC—TGC060C-3K w/X-13 32 Heat Controller, Inc. -32-.
WIRING SCHEMA TIC—TGC060C-4K w/BELT DRIVE 33 Heat Controller, Inc. -33-.
WIRING SCHEMA TICS—TGC036/048C-4K w/PSC 34 Heat Controller, Inc. -34-.
1900 Wellworth Ave Jacks on, Michigan 49203 • Ph. 517-787-2100 • Fax 517-787-9341 THE QU ALIT Y LEADER IN CON D ITIONING AIR www.heatcontroller.com Design, material, performance data and component s subject to change without notice.
An important point after buying a device Heat Controller TGC042C-3K-120 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Heat Controller TGC042C-3K-120 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Heat Controller TGC042C-3K-120 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Heat Controller TGC042C-3K-120 you will learn all the available features of the product, as well as information on its operation. The information that you get Heat Controller TGC042C-3K-120 will certainly help you make a decision on the purchase.
If you already are a holder of Heat Controller TGC042C-3K-120, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Heat Controller TGC042C-3K-120.
However, one of the most important roles played by the user manual is to help in solving problems with Heat Controller TGC042C-3K-120. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Heat Controller TGC042C-3K-120 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center