No.0010578572 13 SEER 1.5 to 3.5 T on Models: HC18D2V AR Installation & Operation Manual HC42D2V AR HC30D2V AR HC24D2V AR HC36D2V AR The information contained in this booklet is subject to change without notice.
! W ARNING These instructions are intended as an aid to qualified, licensed service personnel for proper installation, adjustment and operation of this unit.
1 T ABLE OF CONTENT 1.Introduction --------------------------------------------------------------------------------------- 2.Nomenclature for Model Number ------------------------------------------------------------- 3.Specification ------------------------------------------------------------------------------------- 4.
15 20 25 30 30 Rated Load Amps 5.4 8.0 10.1 1 1.8 13.2 Compressor Locked Running Amps 36.0 53.5 61.0 78.0 78.0 Full Load Amps 0.86 0.86 1.4 1.6 1.6 Fan Motor Rated HP 1/8 1/8 1/4 1/3 1/3 Nominal RPM 1000 1000 1075 1 120 1120 Liquid Line OD - In (mm) 3/8"[9.
Figure 2 Central Air Conditioner Refrigerant Circuit 3 SERVICE V AL VE SE RVICE POR T INDOOR COIL DISTRIBUTOR SE RVICE V AL VE OUTDOOR COIL COMPRESSOR R E S N E D N O C R O T A R O P A V E DRIER(optional) SE RVICE POR T !W arning - The drier is strongly recommended to be installed by installer and replaced once tw o years.
4 4.UNIT INSPECTION This product has been inspected at the factory and released to the transportation agency without known damage. Inspect exterior of carton for evidence of rough handling in shipment. Unpack carefully . If damage is found, report immediately to the transportation agency .
Figure 3 Provide a level concrete slab. T o prevent transmission of noise or vibration, slab should not be connected to building structure. Some sort of sound-absorbing material should be placed between the condenser and the slab. A good material to use is rubber and cork pad.
OUTDOOR UNIT LIQUID LINE PITCH SUCTION LINE TOW ARD OUTDOOR UNIT 1/2" FRO EVER Y 10' OF LINE INDOOR UNIT ABOVE OR LEVEL TO OUTDOOR UNIT INDOOR UNIT OUTDOOR UNIT ADDITIONAL SUCTION LINE OIL T.
The factory charge is suf ficient for 25 feet of standard liquid line. For longer or shorter liquid line lengths, adjust the charge as follows: 1/4" Line +/- 0.3 oz. Per foot 5/16" Line +/- 0.4 oz. Per foot 3/8" Line +/- 0.6 oz. Per foot 1/2" Line +/- 1.
1.T ubing should be cut square. Make sure it is round and free of burrs at the connecting ends. Clean the tubing to prevent contamination from entering the system. 2.Make sure that both refrigerant stop valves at the outdoor unit are closed. 3.Push t he tubing in to the fitt ing until it stops.
9 Evacuation All new installations must be evacuated to a deep vacuum in order that all noncondensible gases and moisture are removed prior to charging the system. Air in a system causes high condensing pressure, which increases power consumption and reduces performance.
1.Fully open both shutoff valves. 2.Connect service gage manifold to the valve service ports, being sure to evacuate lines. 3.Startup the system (Refer to the Section 7 - "System Startup"). Run system at least 10 minutes to allo pressure to stabilize.
11 The condensing unit rating plate and the tables of "Physical and Electrical Specifications / Outdoor Units" (T able 1 and 2) provide pertinent data necessary for the selection of proper size electrical service and over-current protection devices.
1 2 8.OPERA TION Most single phase units are operated without start relay or start capacitor . Such systems should be off for a minimum of 5 minutes before restarting to allow equalization of pressures. The thermostat should not be moved to cycle unit without waiting 5 minutes.
13 Run or start capacitor defective Replace Loose connection Check and tighten all connections. Condenser fan runs, Compressor stuck, grounded or open W ait for 2 hours for overload to reset. compressor doesn't motor winding, open internal overload Replace compressor if still open.
5 PU EL E C T RIC HE A TER KI T RD BL Air Conditioner Wi ri ng Diagram RD 24VAC COMMON COMPRESSOR BL YL 208/230V 60Hz 1PH C BL BL YL YL Y 2 YL P3 P2 P1 6 RD R L1 GND L2 BK BK WH C S CC 4 RD YL 2 1 NC Opt i on al Low & Hig h Pr es sur e Sw i t ches LP S HPS Com p ress or Pr ot ec t 3 Min.
Made in P .R.C..
An important point after buying a device Haier HC18D2VAR (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Haier HC18D2VAR yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Haier HC18D2VAR - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Haier HC18D2VAR you will learn all the available features of the product, as well as information on its operation. The information that you get Haier HC18D2VAR will certainly help you make a decision on the purchase.
If you already are a holder of Haier HC18D2VAR, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Haier HC18D2VAR.
However, one of the most important roles played by the user manual is to help in solving problems with Haier HC18D2VAR. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Haier HC18D2VAR along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center