INSTALLATION INSTRUCTIONS FOR COMMERCIAL HEATING & COOLING 3 TON - 6 TON PACKAGE GAS UNIT CPG SERIES

This Forced Air Central Unit Design Complies With Requirements Embodied in The American National Standard / National Standard of Canada Shown Below.
RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.

Prior to installation, thoroughly familiarize yourself with this Installation Manual. Observe all safety warnings.
During installation or repair, caution is to be observed.
It is your responsibility to install the product safely and to educate the customer on its safe use.
All information contained herein is subject to change without notice.
Goodman Manufacturing Company, L.P. IO-353D 5151 Felipe, Suite 500, Houston, TX 77056 6/11 www.goodmanmfg.com www.amana-hac.com © 2009-2011 Goodman Manufacturing Company, L.P.
®



DO NOT CONNECT TO OR USE ANY DEVICE THAT IS NOT DESIGN CERTIFIED BY GOODMAN FOR USE WITH THIS UNIT. SERIOUS PROPERTY DAMAGE, PERSONAL INJURY, REDUCED UNIT PERFORMANCE AND/OR HAZARDOUS CONDITIONS MAY RESULT FROM THE USE OF SUCH NON-APPROVED DEVICES.
FAILURE TO KEEP THIS COMPARTMENT CLOSED EXCEPT WHEN SERVICING COULD RESULT IN CARBON MONOXIDE POISONING OR DEATH.
AVERTISSEMENT
T HIS PRODUCT CONTAINS OR PRODUCES A CHEMICAL OR CHEMICALS WHICH
RISQUE D'EMPOISONNEMENT AU MONOXYDE DE CARBONE
MAY CAUSE SERIOUS ILLNESS OR DEATH AND WHICH ARE KNOWN TO THE STATE OF CALIFORNIA TO CAUSE CANCER, BIRTH DEFECTS OR OTHER
SI CE COMPARTMENT N'EST PAS FERME EN TOUT TEMPS, SAUF EN CAS DE REPARATION, IL Y A RISQUE D'EMPOISONNEMENT OU MONOXYDE DE CARBONE OU DE MORT.
CE COMPARTIMENT DOIT ETRE FERME SAUF AU MOMENT DE L'ENTRETIEN.
ADVERTENCIA
THIS UNIT IF ANY PART HAS BEEN UNDER WATER. IMMEDIATELY CALL A
QUALIFIED SERVICE TECHNICIAN TO INSPECT THE FURNACE AND TO REPLACE
ANY PART OF THE CONTROL SYSTEM AND ANY GAS CONTROL HAVING BEEN
EL FRACASO DE NO MANTENER COMPARTIMIENTO CERRADO MENOS DURANTE, ATENDER, PODRIA TENER COMO RESULTADO ENVENENAR DE MONOXIDO DE CARBONO O MUERTE. ESTE COMPARTIMIENTO DEBE CERRADO MENOS AL ATENDER
UNDER WATER.
THIS UNIT MUST NOT BE USED AS A "CONSTRUCTION HEATER" DURING THE FINISHING PHASES OF CONSTRUCTION ON A NEW STRUCTURE. THIS TYPE OF USE MAY RESULT IN PREMATURE FAILURE OF THE UNIT DUE TO EXTREMELY LOW RETURN AIR TEMPERATURE AND EXPOSURE TO CORROSIVE OR VERY DIRTY ATMOSPHERES.
WARNING
WARNING
EXPLOSIONS, SMOKE, SOOT, CONDENSATION, ELECTRIC SHOCK OR CARBON
HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
MONOXIDE, THIS UNIT MUST BE PROPERLY INSTALLED, REPAIRED, OPERATED,
AND MAINTAINED.
This unit is approved for outdoor installation ONLY. To assure that your unit operates safely and efficiently, it must be installed, operated, and maintained in accordance with these installation and operating instructions, all local building codes and ordinances, or in their absence, with the latest edition of the National Fuel Gas Code NFPA54/ANSI Z223.1 and National Standard of Canada CAN/CSA B149 Installa- tion Codes.
DO NOT STORE COMBUSTIBLE MATERIALS OR USE GASOLINE OR OTHER
FLAMMABLE LIQUIDS OR VAPORS IN THE VICINITY OF THIS APPLIANCE.
The heating and cooling capacities of the unit should be greater than or equal to the design heating and cooling loads of the area to be conditioned. The loads should be calculated by an approved method or in accordance with ASHRAE Guide or Manual J - Load Calculations published by the Air Condi- tioning Contractors of America.
HIGH VOLTAGE! INSTALLATION AND REPAIR OF THIS UNIT SHOULD BE PERFORMED ONLY BY INDIVIDUALS MEETING THE REQUIREMENTS OF AN “ENTRY LEVEL TECHNICIAN” AS SPECIFIED BY THE AIR CONDITIONING AND REFRIGERATION INSTITUTE (ARI). ATTEMPTING TO INSTALL OR REPAIR THIS UNIT WITHOUT SUCH BACKGROUND MAY RESULT IN PRODUCT DAMAGE, PERSONAL INJURY OR DEATH.
American National Standards Institute
1430 Broadway New York, NY 10018 System design and installation should also, where applicable, follow information presented in accepted industry guides such as the ASHRAE Handbooks. The manufacturer assumes no

responsibility for equipment installed in violation of any code or regulation. The mechanical installation of the packaged roof top units consists of making final connections between the unit and building services; supply and return duct con- nections; and drain connections (if required). The internal systems of the unit are completely factory-installed and tested prior to shipment.
Proper installation of the unit ensures trouble-free operation. Improper installation can result in problems ranging from noisy operation to property or equipment damages, danger- ous conditions that could result in injury or personal property damage and that are not covered by the warranty. Give this booklet to the user and explain it’s provisions. The user should retain these instructions for future reference.
Units are generally installed on a steel roof mounting curb assembly which has been shipped to the job site for installa- tion on the roof structure prior to the arrival of the unit. The model number shown on the unit’s identification plate identi- fies the various components of the unit such as refrigeration tonnage, heating input and voltage.
Carefully inspect the unit for damage including damage to the cabinetry. Any bolts or screws which may have loosened in transit must be re-tightened. In the event of damage, the receiver should:
bond. b. Original paid freight bill or indemnity in lieu thereof. c. Original invoice or certified copy thereof, showing
trade and other discounts or reductions. d. Copy of the inspection report issued by carrier
representative at the time damage is reported to the carrier. The carrier is responsible for making prompt inspection of damage and for a thorough investigation of each claim. The distributor or manufacturer will not accept claims from dealers for transportation damage. NOTE: When inspecting the unit for transportation damage, remove all packaging materials. Recycle or dispose of the packaging material according to local codes.
Carefully read all instructions for the installation prior to in- stalling unit. Ensure each step or procedure is understood and any special considerations are taken into account be- fore starting installation. Assemble all tools, hardware and supplies needed to complete the installation. Some items may need to be purchased locally.
WARNING
INJURY OR DEATH, THE FOLLOWING BULLET POINTS MUST BE OBSERVED
WHEN INSTALLING THE UNIT. IMPORTANT NOTE: Remove wood shipping rails prior to installation of the unit.

Full perimeter roof curbs are available from the factory and are shipped unassembled. Field assembly, squaring, level- ing and mounting on the roof structure are the responsibility of the installing contractor. All required hardware necessary for the assembly of the sheet metal curb is included in the curb accessory.

INJURY OR DEATH, THE FOLLOWING BULLET POINTS MUST BE OBSERVED

ALL CURBS LOOK SIMILAR. TO AVOID INCORRECT CURB POSITIONING, CHECK JOB PLANS CAREFULLY AND VERIFY MARKINGS ON CURB ASSEMBLY. INSTRUCTIONS MAY VARY IN CURB STYLES AND SUPERSEDES INFORMATION SHOWN.
See the manual shipped with the roof curb for assembly and installation instructions.

Curb installatons must comply with local codes and should be done in accordance with the established guidelines of the National Roofing Contractors Association.
Proper unit installation requires that the roof curb be firmly and permanently attached to the roof structure. Check for adequate fastening method prior to setting the unit on the curb.

Adequate clearance around the unit should be kept for safety, service, maintenance, and proper unit operation. A total clear- ance of 75” on the main control panel side of the unit is rec- ommended to facilitate possible fan shaft, coil, electric heat and gas furnace removal. A clearance of 48” is recommended on all other sides of the unit to facilitate possible compressor removal, to allow service access and to insure proper venti- lation and condenser airflow. The unit must not be installed beneath any obstruction. The unit should be installed re- mote from all building exhausts to inhibit ingestion of exhaust air into the unit fresh air intake.
IF PROTRUSIONS EXIST, DO NO ATTEMPT TO SET UNIT ON CURB.
Install all duct connections on the unit before placing the unit on rooftop.
For horizontal discharge, remove the supply and return duct covers and place them over the vertical discharge return and supply openings. Install with insulation facing up, using the longer screws provided in the literature package.

Ensure that the top of the duct connection frame is flush with the top of the roof curb.
Flexible duct connectors between the unit and ducts are rec- ommended. Insulate and weatherproof all external ductwork and joints as required and in accordance with local codes.

ROOF CURB POST-INSTALLATION CHECKS After installation, check the top of the curb, duct connection frame and duct flanges to make sure gasket has been ap- plied properly. Gasket should be firmly applied to the top of the curb perimeter, duct flanges and any exposed duct con- nection frame. If gasket is loose, re-apply using strong weather resistant adhesive.
P ROTRUSION
Inspect curb to ensure that none of the utility services (elec- tric) routed through the curb protrude above the curb.


POSITION DURING ALL RIGGING AND MOVING OPERATIONS. T O FACILITATE
LIFTING AND MOVING WHEN A CRANE IS USED, PLACE THE UNIT IN AN
IF UNITS ARE LIFTED TWO AT A TIME, THE FORK HOLES ON THE CONDENSER END OF THE UNIT MUST NOT BE USED. MINIMUM FORK LENGTH IS 42” TO PREVENT DAMAGE TO THE UNIT; HOWEVER, 48” IS RECOMMENDED.
Provisions for forks have been included in the unit base frame. No other fork locations are approved.

INJURY OR DEATH, THE FOLLOWING BULLET POINTS MUST BE OBSERVED
Refer to the Roof Curb Installation Instructions for proper curb installation. Curbing must be installed in compliance with the National Roofing Contractors Association Manual.
Lower unit carefully onto roof mounting curb. While rigging unit, center of gravity will cause condenser end to be lower than supply air end.




* Weights shown are belt drive with no accessories.

TO PREVENT SEVERE DAMAGE TO THE BOTTOM OF THE UNIT, DO NOT FORK LIFT UNIT AFTER WOOD STRUTS HAVE BEEN REMOVED.
Bring condenser end of unit into alignment with the curb. With condenser end of the unit resting on curb member and using curb as a fulcrum, lower opposite end of the unit until entire unit is seated on the curb. When a rectangular cantilever curb is used, care should be taken to center the unit. Check for proper alignment and orientation of supply and return openings with duct.

TO PREVENT DAMAGE TO THE UNIT, DO NOT ALLOW CRANE HOOKS AND SPREADER BARS TO REST ON THE ROOF OF THE UNIT.
Remove spreader bars, lifting cables and other rigging equipment.

Electrical Code. If long wires are required, it may be neces- sary to increase the wire size to prevent excessive voltage drop. Wires should be sized for a maximum of 3% voltage drop.
HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
ONLY COPPER CONDUCTORS.
CAUTION
HIGH VOLTAGE! TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK, DO NOT TAMPER WITH FACTORY WIRING. THE INTERNAL POWER AND CONTROL WIRING OF THESE UNITS ARE FACTORY-INSTALLED AND HAVE BEEN THOROUGHLY TESTED PRIOR TO SHIPMENT. CONTACT YOUR LOCAL REPRESENTATIVE IF ASSISTANCE IS REQUIRED.
LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS. VERIFY PROPER OPERATION AFTER SERVICING.
Ensure the data plate is not covered by the field-supplied disconnect switch.
TO PREVENT DAMAGE TO THE WIRING, PROTECT WIRING FROM SHARP EDGES. FOLLOW NATIONAL ELECTRICAL CODE AND ALL LOCAL CODES AND ORDINANCES. DO NOT ROUTE WIRES THROUGH REMOVABLE ACCESS PANELS.
CONDUIT AND FITTINGS MUST BE WEATHER-TIGHT TO PREVENT WATER ENTRY INTO THE BUILDING.
For unit protection, use a fuse or HACR circuit breaker that is in excess of the circuit ampacity, but less than or equal to the maximum overcurrent protection device. DO NOT EXCEED THE MAXIMUM OVERCURRENT DEVICE SIZE SHOWN ON UNIT DATA PLATE.

All line voltage connections must be made through weather- proof fittings. All exterior power supply and ground wiring must be in approved weatherproof conduit.
The main power supply wiring to the unit and low voltage wiring to accessory controls must be done in accordance with these instructions, the latest edition of the National Electriacl Code (ANSI/NFPA 70), and all local codes and ordinances. All field wiring shall conform with the temperature limitations for Type T wire (63°F/35°C rise).
The main power supply for the CPG036XXX3,4,7 through CPG072 shall be three-phase, three wire. The power sup- ply for the CPG036XXX1 through CPG060 shall be single- phase, two wire. The unit is factory wired for the voltage shown on the unit’s data plate.

FAILURE OF UNIT DUE TO OPERATION ON IMPROPER LINE VOLTAGE OR WITH EXCESSIVE PHASE UNBALANCE CONSTITUTES PRODUCT ABUSE AND WILL VOID YOUR WARRANTY AND MAY CAUSE SEVERE DAMAGE TO THE UNIT ELECTRICAL COMPONENTS.
Main power wiring should be sized for the minimum wire ampacity shown on the unit’s database. Size wires in accor- dance with the ampacity tables in Article 310 of the National

2. Locate thermostat or remote sensor in the conditioned space where it will sense average temperature. Do not locate the device where it may be directly exposed to supply air, sunlight or other sources of heat. Follow installation instructions packaged with the thermostat. 3. Use #18 AWG wire for 24V control wiring runs not exceeding 75 feet. Use #16 AWG wire for 24V control wiring runs not exceeding 125 feet. Use #14 AWG wire for 24V control wiring runs not exceeding 200 feet. Low voltage wiring may be National Electrical Code (NEC) Class 2 where permitted by local codes. 4. Route thermostat wires from sub-base terminals to the unit. Control wiring should enter through the condenser end of unit or through curb. Connect thermostat and any accessory wiring to low voltage terminal block TB1 in the main control box.
It is recommended that an independant 115V power source be brought to the vicinity of the roof top unit for portable lights and tools used by the service mechanic.
Main power and low voltage wiring may enter the unit through the condenser end of unit or through the roof curb. Install conduit connectors at the desired entrance locations. Exter- nal connectors must be weatherproof. All holes in the unit base must be sealed (including those around conduit nuts) to prevent water leakage into building. All required conduit and fittings are to be field supplied.
Supply voltage to roof top unit must not vary by more than 10% of the value indicated on the unit data plate. Phase voltage unbalance must not exceed 2%. Contact your local power company for correction of improper voltage or phase unbalance.

LEAD THERMOSTAT Red R (24V) Green G (Fan) Yellow Y1 (High Cool) Purple Y2 (Low Cool) Blue Common (if req'd) White W1 (Heat) Brown W2 (High Heat)
* (6 Ton - 34 1/4”)
GAS SUPPLY PIPING


TO PREVENT PERSONAL INJURY OR DEATH DUE TO IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE, REFER TO THIS MANUAL. FOR ADDITIONAL ASSISTANCE OR INFORMATION, CONSULT A QUALIFIED INSTALLER, SERVICE AGENCY OR THE GAS SUPPLIER.

TO AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH WHEN EITHER USING PROPANE GAS ALONE OR AT HIGHER ALTITUDES, OBTAIN AND INSTALL THE PROPER CONVERSION KIT(S). FAILURE TO DO SO CAN RESULT IN UNSATISFACTORY OPERATION AND/OR EQUIPMENT DAMAGE. HIGH ALTITUDE KITS ARE FOR U.S. INSTALLATIONS ONLY AND ARE NOT APPROVED FOR USE IN CANADA.
Electrical Entrance and Thru Curb Unit is equipped with a Low Voltage Terminal Block and has Single Point wiring to the contactor.
The rating plate is stamped with the model number, type of gas and gas input rating. Make sure the unit is equipped to operate on the type of gas available. Conversion to propane

(LP) gas is permitted with the use of the factory authorized conversion kit (see the unit Technical Manual for the appro- priate kit). For High Altitude derates, refer to the latest edition of the National Fuel Gas Code NFPA 54/ANSI Z223.1.
IInlet Gas Pressure Must Not Exceed the Maximum Value Shown in Table Above.
The minimum supply pressure should not vary from that shown in the table above because this could prevent the unit from having dependable ignition. In addition, gas input to the burners must not exceed the rated input shown on the rating plate. Overfiring of the unit could result in premature heat exchanger failure.
The rating plate is stamped with the model number, type of gas and gas input rating. Make sure the unit is equipped to operate on the type of gas available. The gas line installation must comply with local codes, or in the absence of local codes, with the latest edition of the National Fuel Gas Code NFPA 54/ANSI Z223.1.

Natural Gas Connection

Natural Gas Capacity of Pipe in Cubic Feet of Gas Per Hour (CFH)
Proper Piping Practice
on 0.60 Specific Gravity Gas)
Refer to the Proper Piping Practice drawing for the general layout at the unit. The following rules apply:

FOLLOWING INSTRUCTIONS MUST BE PERFORMED REGARDING GAS
CONNECTIONS AND PRESSURE TESTING:
FIRE, NEVER USE A MATCH OR OPEN FLAME TO TEST FOR LEAKS. NEVER
Complete information regarding tank sizing for vaporization, recommended regulator settings and pipe sizing is available from most regulator manufacturers and propane gas suppliers. Since propane gas will quickly dissolve white lead or most standard commercial compounds, special pipe dope must be used. Shellac base compounds resistant to the actions of liquefied petroleum gases such as Gasolac®, Stalactic®, Clyde’s® or John Crane® are satisfactory. See below for typical propane gas piping.
DAMAGE GAS VALVE AND CAUSE OVERFIRING WHICH MAY RESULT IN
PREMATURE HEAT EXCHANGE FAILURE.
THE GAS SUPPLY DURING ANY PRESSURE TESTING OF THAT SYSTEM AT
TEST PRESSURES IN EXCESS OF 1/2 PSIG (3.48 KPA).
TESTING OF THE GAS SUPPLY PIPING SYSTEM AT TEST PRESSURES
EQUAL TO OR LESS THAN 1/2 PSIG (3.48 KPA).
TO AVOID PROPERTY DAMAGE OR PERSONAL INJURY, BE SURE THERE IS NO OPEN FLAME IN THE VICINITY DURING AIR BLEEDING.
5 to 15 PSIG (20 PSIG Max.)
11" W.C.
There will be air in the gas supply line after testing for leaks on a new installation. Therefore, the air must be bled from the line by loosening the ground joint union until pure gas is expelled. Tighten union and wait for five minutes until all gas has been dissipated in the air. Be certain there is no open flame in the vicinity during air bleeding procedure. The unit is placed in operation by closing the main electrical disconnect switch for the unit.
R OOF T OP L OCATION AND I NSTALLATION
PROPANE GAS INSTALLATIONS
The gas supply piping location and installation for roof top units must be in accordance with local codes or, in the ab- sence of locals codes, with ordinances of the latest edition of the National Fuel Gas Code (ANSI Z223.1).
TO AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO FIRE OR EXPLOSION CAUSED BY A PROPANE GAS LEAK, INSTALL A GAS DETECTING WARNING DEVICE. SINCE RUST CAN REDUCE THE LEVEL
A manual gas shutoff valve must be field installed external to the roof top unit. In addition, a drip leg must be installed near the inlet connection. A ground joint union connection is re- quired between the external shutoff valve and the unit con- nection to the gas valve to permit removal of the burner as- sembly for servicing.
OF ODORANT IN PROPANE GAS, A GAS DETECTING WARNING DEVICE IS THE ONLY RELIABLE WAY TO DETECT A PROPANE GAS LEAK. CONTACT A LOCAL PROPANE GAS SUPPLIER ABOUT INSTALLING A
GAS DETECTING WARNING DEVICE.
1. Route gas piping to unit so that it does not interfere with the removal of access panels. Support and align piping to prevent strains or misalignment of the manifold assembly. 2. All units are furnished with standard female NPT pipe connections. Connection pipe sizes for CPG036 through 072 units is 1/2" NPT on 045 to 140 mBH units. The size of the gas supply piping to the unit must be based on length of run, number of units on the system, gas characteristics, BTU requirement and available supply pressure. All piping must be done in accordance with local codes or, in the absence of local codes, with the latest edition of the National Fuel Gas Code (ANSI Z223.1).
All propane gas equipment must conform to the safety standards of the National Board of Fire Underwriters (See NBFU Manual 58).
For satisfactory operation, propane gas supply pressure must be within 9.7 - 10.3 inches W.C. at the manifold with all gas appliances in operation. Maintaining proper gas pressure depends on three main factors:

NOTE: The gas connection size at the unit does NOT establish the size of the supply line. 3. These units are designed for either natural or propane (LP) gas and are specifically constructed at the factory for only one of these fuels. The fuels are NOT interchangeable. However, the furnace can be converted in the field from natural gas to LP gas with the appropriate factory kit (see unit Technical Manual for the appropriate kit). Only a qualified contractor, experienced with natural and propane gas systems, should attempt conversion. Kit instructions must be followed closely to assure safe and reliable unit operation. 4. With all units on a common line operating under full fire, natural gas main supply pressure should be adjusted to approximately 7.0" w.c., measured at the unit gas valve. If the gas pressure at the unit is greater than 10.5" w.c., the contractor must furnish and install an external type positive shutoff service pressure regulator. The unit will not function satisfactorily if supply gas pressure is less than 5.5" w.c. or greater than 10.5" w.c.. NOTE: A minimum horizontal distance of 48" between the regulator and the furnace flue discharge is required. 5. With all units on a common line operating under full LP gas main supply pressure should be at least 11.0" w.c. and must be no greater than 13.0" w.c., measured at the unit gas valve. Unit will not function satisfactorily if supply gas pressure is less than 11.0" w.c. or greater than 13.0" w.c.. 6. All pipe connections should be sealed with a pipe thread compound, which is resistant to the fuel used with the furnace. A soapy water solution should be used to check all joints for leaks. A tap is located on the entering side of the gas valve for test gauge connection to measure supply (main) gas pressure. Another tap is provided on the manifold side of the gas valve for checking manifold pressure.
D UCTWORK
The supply duct should be provided with an access panel large enough to inspect the air chamber downstream of the heat exchanger. A cover should be tightly attached to pre- vent air leaks.
Ductwork dimensions are shown in the roof curb installation manual.
If desired, supply and return duct connections to the unit may be made with flexible connections to reduce possible unit operating sound transmission.
C ONDENSATE D RAIN C ONNECTION
A 3/4” NPT drain connection is supplied for condensate pip- ing. An external trap must be installed for proper condensate drainage.

Drain Connection Install condensate drain trap as shown. Use 3/4" drain line and fittings or larger. Do not operate without trap.

THIS UNIT AND ITS INDIVIDUAL SHUTOFF VALVE MUST BE DISCONNECTED FROM THE GAS SUPPLY SYSTEM DURING ANY PRESSURE TESTING OF THAT SYSTEM AT TEST PRESSURES IN EXCESS OF 1/2 PSIG (13.8” W.C.).
Drainage of condensate directly onto the roof may be ac- ceptable; refer to local code. It is recommended that a small drip pad of either stone, mortar, wood or metal be provided to prevent any possible damage to the roof.
Due to the fact that drain pans in any air conditioning unit will have some moisture in them, algae and fungus will grow due to airborne bacteria and spores. Periodic clean- ing is necessary to prevent this build-up from plugging the drain.
THIS UNIT MUST BE ISOLATED FROM THE GAS SUPPLY PIPING SYSTEM BY CLOSING ITS INDIVIDUAL MANUAL SHUTOFF VALVE DURING ANY PRESSURE TESTING EQUAL TO OR LESS THAN 1/2 PSIG.

T OOLS R EQUIRED
Refrigeration gauge and manifold Voltmeter Clamp-on ammeter Ohmmeter Test lead (Minimum #16 AWG with insulated alligator clips) Manometer for verifying gas pressure 0 to 20" w.c. Air temperature measuring device General refrigeration mechanics’ tools
TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK, B
OND THE FRAME OF THIS UNIT TO THE BUILDING ELECTRICAL GROUND BY USE OF THE GROUNDING TERMINAL PROVIDED OR OTHER ACCEPTABLE MEANS. DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT.
T EMPORARY H EATING O R C OOLING
If the unit is to be used for temporary heating or cooling, a “Startup, Adjustments, and Checks” must first be performed in accordance with this manual. Failure to comply with this requirement will void the warranty. After the machines are used for temporary heating or cooling, inspect the coils, fans, and motors for unacceptable levels of construction dust and dirt and install new filters.
TO PREVENT PROPERTY DAMAGE OR PERSONAL INJURY, DO NOT START THE UNIT UNTIL ALL NECESSARY PRE-CHECKS AND TESTS HAVE BEEN PERFORMED.
Prior to the beginning of Startup, Adjustments, and Checks procedures, the following steps should be completed in the building.
THERMOSTAT . Set the thermostat in the conditioned
space at a point at least 10°F below zone temperature. Set the thermostat system switch on COOL and the fan switch on AUTO.
MOVING MACHINERY HAZARD! TO PREVENT POSSIBLE PERSONAL INJURY OR DEATH, DISCONNECT POWER TO THE UNIT AND PADLOCK IN THE “OFF” POSITION BEFORE SERVICNG FANS.
H EATING S TARTUP
Inspect the roof curb for correct installation. The unit and curb assembly should be level. Inspect the flashing of the roof mounting curb to the roof, especially at the corners, for good workmanship. Also check for leaks around gaskets. Note any deficiencies in a separate report and forward to the contrac- tor.
This unit is equipped with an electronic ignition device to au- tomatically light the main burners. It also has a power vent blower to exhaust combustion products.
On new installations, or if a major component has been re- placed, the operation of the unit must be checked.
Check unit operation as outlined in the following instructions. If any sparking, odors, or unusual sounds are encountered, shut off electrical power and recheck for wiring errors, or ob- structions in or near the blower motors. Duct covers must be removed before operating unit.
Remove any extraneous construction and shipping materi- als that may be found during this procedure. Rotate all fans manually to check for proper clearances and that they rotate freely. Check for bolts and screws that may have jarred loose during shipment to the jobsite. Retighten if necessary. Re- tighten all electrical connections.
The Startup, Adjustments, and Checks procedure provides a step-by-step sequence which, if followed, will assure the proper startup of the equipment in the minimum amount of time. Air balancing of duct system is not considered part of this procedure. However, it is an important phase of any air conditioning system startup and should be performed upon completion of the Startup, Adjustments, and Checks proce- dure. The Startup, Adjustments, and Checks procedure at outside ambients below 55°F should be limited to a readi- ness check of the refrigeration system with the required final check and calibration left to be completed when the outside ambient rises above 55°F.
It is important to your safety that the unit has been properly grounded during installation. Check ground lug connection in main control box for tightness prior to closing circuit breaker or disconnect switch. Verify that supply voltage on line side of disconnect agrees with voltage on unit identification plate and is within the utilization voltage range as indicated in Appendix C Electrical Data.

System Voltage - That nominal voltage value assigned to a circuit or system for the purpose of designating its voltage class.
Actual RPM’s must be set and verified with a tachometer or strobe light. Refer to Appendices A and B for basic unit fan RPM. Refer also to “Airflow” section of this manual. With disconnect switch open, disconnect thermostat wires from terminals Y and W. This will prevent heating and mechanical cooling from coming on. Place a jumper wire across termi- nals R and G at TB1 terminal block. Close disconnect switch; evaporator fan motor will operate so RPM can be checked.
Nameplate Voltage - That voltage assigned to a piece of equipment for the purpose of designating its voltage class and for the purpose of defining the minimum and maximum voltage at which the equipment will operate.
Utilization Voltage - The voltage of the line terminals of the equipment at which the equipment must give fully satisfac- tory performance. Once it is established that supply voltage will be maintained within the utilization range under all sys- tem conditions, check and calculate if an unbalanced condi- tion exists between phases. Calculate percent voltage un- balance as follows.
For gas heat units, the airflow must be adjusted so that the air temperature rise falls within the ranges given stated on Data Plate (see Appendix A - Blower Performance).
Correct belt tension is very important to the life of your belt. Too loose a belt will shorten its life; too tight, premature mo- tor and bearing failure will occur. Check you belt drive for adequate “run-in” belt tension by measuring the force required to deflect the belt at the midpoint of the span length. Belt tension force can be measured using a belt tension gauge, available through most belt drive manufacturers.
2) MAXIMUM VOLTAGE DEVIATIONS FROM AVERAGE VOLTAGE
3) PERCENT VOLTAGE UNBALANCE
= 100 X
1) AVERAGE VOLTAGE
HOW TO USE THE FORMULA: EXAMPLE: With voltage of 220, 216, and 213 1) Average Voltage = 220+216+213=649 / 3 = 216 2) Maximum Voltage Deviations from Average Voltage = 220 - 216 = 4

4 216 400 216
Percent voltage unbalance MUST NOT exceed 2%.
Verify that all duct connections are tight and that there is no air bypass between supply and return.
With disconnect switch in the open “OFF” position, discon- nect blue wire from low voltage transformer TRANS1. Close the disconnect switch to energize TRANS1 control trans- former. Check primary and secondary (24V) of control trans- former TRANS1.
Belt Tension Adjustment t = Span length, inches C = Center distance, inches D = Larger sheave diameter, inches d = Smaller sheave diameter, inches h = Deflection height, inches
With disconnect switch open and blue wire disconnected from TRANS1 transformer, attach one lead of ohmmeter to termi- nal R on TB1 terminal block. Touch, in order, the other ohm- meter lead to terminals Y1, Y2 and G at TB1 terminal block. There must be continuity from terminal R to terminals Y and G. R to Y indicates cool. R to G indicates fan (auto). Replace blue wire on TRANS1 transformer.
DEFLECTION
FORCE (lbs) TYPE DEFLECTION
(in)
(in)
BELT DRIVE USED NEW AX Standard 3.0 to 4.0 4.2 ± 0.5 5.5 ± 0.5 0.313
New V-belts will drop rapidly during the first few hours of use. Check tension frequently during the first 24 hours of opera- tion. Tension should fall between the minimum and maximum force. To determine the deflection distance from a normal position, measure the distance from sheave to sheave using a straightedge or a cord. This is your reference line. On mul- tiple belt drives, an adjacent undeflected belt can be used as a reference.
Remove filter section access panels and check that filters are properly installed. Note airflow arrows on filter frames.
Prior to energizing any fans, check and make sure that all setscrews are tight so that bearings are properly secured to shafts.

EVAPORATOR FAN ROTATION CHECK (THREE PHASE MODELS ONLY)
If the power to the unit is interrupted during the heating cycle, it may cause the secondary limit to trip. Once the blower com- partment temperature drops below the limit reset tempera- ture, the limit will automatically reset. The unit will restart after one (1) hour.
Check that fan rotates clockwise when viewed from the drive side of unit and in accordance with rotation arrow shown on blower housing. If it does not, reverse any two incoming power cables at Single Point Power Block. In this case, repeat bear- ing check.
1. Close the manual gas valve external to the unit. 2. Turn off the electrical power supply to the unit. 3. Set the room thermostat to its lowest possible setting. 4. Remove the heat exchanger door on the side of the unit by removing screws. 5. This unit is equipped with an ignition device which automatically lights the main burner. DO NOT try to light burner by any other method. 6. Move the gas control valve switch to the OFF position. Do not force. 7. Wait five minutes to clear out any gas. 8. Smell for gas, including near the ground. This is important because some types of gas are heavier than air. If you have waited five minutes and you do smell gas, immediately follow the warnings on page 3 of this manual. If having waited for five minutes and no gas smell is noted, move the gas control valve switch to the ON position. 9. Replace the heat exchanger door on the side of the unit. 10. Open the manual gas valve external to the unit. 11. Turn on the electrical power supply to the unit. 12. Set the thermostat to desired setting.
Do not attempt to change load side wiring. Internal wiring assures all motors and compressors will rotate in correct di- rection once evaporator fan motor rotation check has been made.
Make preliminary check of evaporator fan ampere draw and verify that motor nameplate amps are not exceeded. A final check of amp draw should be made upon completion of air balancing of the duct system (see Appendix C).
With disconnect switch open, remove jumper wire from ter- minals R and G at TB1 terminal block, and reconnect ther- mostat wires to terminals Y and W.
Ensure the hold-down bolts on the compressor are secure and have not vibrated loose during shipment. Check that vi- bration grommets have been installed. Visually check all pip- ing and clamps. The entire refrigeration system has been factory charged and tested, making it unnecessary to field charge. Factory charges are shown in Appendix C and on the unit nameplate.
Gas supply pressure and manifold pressure with the burners operating must be as specified on the rating plate.
Install service manifold hoses. Gauges should read satura- tion pressure corresponding to ambient temperature. Charge should be checked to obtain 12° to 15° of sub-cooling per system (i.e. compressor circuits).
Gas inlet pressure must be checked and adjusted in accor- dance to the type of fuel being consumed.
Rollout Protection Control
The rollout protection device opens, cutting power to the gas valve, if the flames from the burners are not properly drawn into the heat exchanger. The rollout protection device is located on the burner bracket. The reason for elevated temperatures at the control should be determined and repaired prior to resetting this manual reset control.
T O AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO FIRE
NATURAL Min. 5.0" W.C., Max. 10.0" W.C.
OR EXPLOSION, A QUALIFIED SERVICER MUST INVESTIGATE THE REASON FOR
PROPANE Min. 11.0" W.C., Max. 14.0" W.C.
THE ROLLOUT PROTECTION DEVICE TO OPEN BEFORE MANUALLY RESETTING
THE ROLLOUT PROTECTION DEVICE.
The secondary limit control is located on the top of the blower scroll assembly. This control opens when elevated tempera- tures are sensed. Elevated temperatures at the control are normally caused by blower failure. The reason for the open- ing should be determined and repaired prior to resetting.
If operating pressures differ from above, make necessary pressure regulator adjustments, check piping size, etc., and/ or consult with local utility.

The gas valve has a tapped opening to facilitate measure- ment of the manifold pressure. A “U” Tube manometer hav- ing a scale range from 0 to 12 inches of water should be used for this measurement. The manifold pressure must be measured with the burners operating.
Flames should be stable, soft and blue (dust may cause or- ange tips but they must not be yellow) and extending directly outward from the burner without curling, floating or lifting off.
1. With disconnect switch open, remove field connected thermostat wire from terminal R, W1 and W2 on TB1. Place jumper wire between R, W1 and W2 to engage high stage heat. (note on 045 kbtu/hr units W2 is not used, only jumper R to W1). 2. See Figure in input rating section for gas valve adjustment. To adjust the pressure regulator, remove the adjustment screw or cover on the gas valve. Turn out (counterclockwise) to decrease pressure, turn in (clockwise) to increase pressure. Only small variations in gas flow should be made by means of the pressure regulator adjustment. In no case should the final manifold pressure vary more than plus or minus 0.3 inches water column from the specified nominal pressure. Any major changes in flow should be made by changing the size of the burner orifices. The measured input rate to the furnace must not exceed the rating specified on the unit rat- ing plate.
Verify that the alignment of the NOx screens is at 6 o' clock. In jurisdictions that do not require low NOx emissions, NOx screens may be removed.
Check the temperature rise through the unit by placing ther- mometers in supply and return air registers as close to the unit as possible. Thermometers must not be able to sample temperature directly from the unit heat exchangers, or false readings could be obtained.
For natural gas, the high stage manifold pressure must be between 3.2 and 3.8 inches water column (3.5 nominal). Low stage manifold pressure must be between 1.7 to 2.3 inches water column (2.0 nominal).
With a properly designed system, the proper amount of tem- perature rise will normally be obtained when the unit is oper- ated at rated input with the recommended blower speed.
If the correct amount of temperature rise is not obtained, it may be necessary to change the blower speed. A higher blower speed will lower the temperature rise. A slower blower speed will increase the temperature rise.
R EFRIGERATION S EQUENCE C HECK
With the disconnect switch open, remove the field connected thermostat wire from terminal R on TB1 terminal block. Place a jumper across terminals R and G, and across R and Y on TB1 terminal block. Close the disconnect switch. The follow- ing operational sequence should be observed.
To measure the gas input use a gas meter and proceed as follows: 1. Turn off gas supply to all other appliances except the unit. 2. With the unit operating, time the smallest dial on the meter for one complete revolution. If this is a 2 cubic foot dial, divide the seconds by 2; if it is a 1 cubic foot dial, use the seconds as is. This gives the seconds per cubic foot of gas being delivered to the unit. 3. INPUT=GAS HTG VALUE x 3600 / SEC. PER CUBIC FOOT Example: Natural gas with a heating value of 1000 BTU per cubic foot and 34 seconds per cubic foot as determined by Step 2, then:
1. Current through primary winding of transformer TRANS1 energizes the 24-volt control circuit. 2. To simulate a mechanical call for cooling from the wall thermostat, place a jumper across terminals R and Y of terminal block TB1. The cooling is energized when the room temperature is above the thermostat set- point for cooling. The thermostat makes R to Y. 3. UNIT WITH ECONOMIZER OPTION: The compressor circuit is interlocked through terminals 3 and 4 of the economizer module. If the outdoor air enthalpy (temperature and humidity) is not suitable for cooling, the economizer terminals will be closed permitting compressor to be energized.
Input = 1000 x 3600 / 34 = 106,000 BTU per Hour. NOTE: BTU content of the gas should be obtained from the gas supplier. This measured input must not be greater than shown on the unit rating plate.

4. The belt drive blower contactor closes its contacts L1, L2 and L3 to T1, T2 and T3 to provide power to the supply fan motor. PSC Motor Adjust the CFM for the unit by changing the speed tap of the indoor blower motor at the EBTDR “com” connection with one of the speed taps on “M1” or “M2”. (Black-High Speed, Blue-Medium Speed, Red-Low Speed.) EEM Motor Adjust the CFM for the unit by changing the position of the low voltage leads on the motor terminal block. White is for fan only and gas heat, Yellow is for cooling. Refer to Appendix A for blower performance at each speed tap. NOTE: If more than one lead is energized simultaneously, the motor will run at the higher speed. 5. Check supply fan rotation. If the supply fan is rotating in the wrong direction, disconnect and lock off Single Point Power Block. Do not attempt to change load side wiring. Internal wiring is set at the factory to assure that the supply fan and compressors all rotate in the proper direction. Verification of correct supply fan rotation at initial startup will also indicate correct compressor rotation. Reconnect power and check for proper operation. 6. Compressor contactor closes its contacts L1, L2 and L3 to T1, T2 and T3 to provide power to the compressor motor COMP. 1. In addition, contactor C1 closes its contact L3 to T3 , energizing the condenser fan motor.
7. Disconnecting the jumper wire between R and Y and between R and G on TB1 terminal block will simulate a satisfied thermostat. The compressor will cycle off and IIC (pin 12) will initiate its time delay cycle. The compressor and the supply fan will cycle off. 8. After a time delay of approximately 3 minutes, the compressor control circuits will be ready to respond to a subsequent call for cooling from the wall thermostat. 9. Open disconnect switch. Reconnect the field thermostat wire at terminal R on terminal block TB1.
Under normal summertime (full load) operating conditions, superheat should be between 8°F and 12°F and sub-cooling measured at the condenser outlet should be 15°F (nominal). A 25°F to 35°F temperature difference should exist between the entering condenser air and the temperature correspond- ing to the compressor saturated discharge pressure. Check that compressor RLA corresponds to values shown in Ap- pendix C. RLA draw can be much lower than values listed at low load conditions and low ambient condensing tempera- tures. Values in Appendix C can slightly exceed at high load conditions and high ambient condensing temperatures.
WARNING
SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL TO SHUT OFF, TURN OFF THE MANUAL GAS SHUTOFF VALVE EXTERNAL TO THE UNIT BEFORE TURNING OFF THE ELECTRICAL SUPPLY.
WARNING
TO AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH, DO NOT FIRE GAS UNIT WITH FLUE BOX COVER REMOVED.
The first step in checking out the gas-fired furnace is to test the gas supply piping to the unit for tightness and purge the system of air using methods outlined in the latest edition of the National Fuel Gas Code ANSI Z223.1. Verify that the disconnect switch is in the “OFF” position. A soapy water solution should be used to check for gas leaks. Since the unit is subject to considerable jarring during shipment, it is ex- tremely important that all gas connections and joints be tested for tightness. Gas piping downstream from the unit inlet should be checked for leaks during the subsequent sequence check.
The supply gas pressure should be adjusted to 7.0" w.c. on natural gas and 11.0" on LP gas with the gas burners operat- ing. If there is more than one unit on a common gas line, the pressures should be checked with all units under full fire. A

supply pressure tap is provided on the upstream side of the gas valve. A manifold pressure tap is provided on the gas valve. The normal manifold pressure for full input is 3.5" w.c. on natural gas and 9.5" w.c. for propane gas. Low fire natu- ral gas 2.0” w.c., 6.0” low fire propane gas. Minimum gas supply pressure is 5.5" w.c. for natural gas and 11.0" for pro- pane gas. In order to obtain rating, gas supply pressure must be 11.0" w.c. for propane gas.
The pressure regulator on LP gas models is adjusted for 9.5" w.c. manifold pressure and is intended to prevent over-firing only. Do not attempt adjustment of the built-in pressure regu- lator unless the supply pressure is at least 7.0" w.c. on natu- ral gas or 13.0" w.c. on propane gas. Check the location of the ignition electrode and the flame sensor for correct gap setting.
H EATING
This unit has one (RS) Manual Reset Limit Control Switch. Check the limit to make sure it has not tripped. The limit may arrive at the job site tripped as a result of shipping shock.
If the ventermotor comes on, but the unit does not attempt ignition, check if the ALS (Auxiliary High Limit Control Switch) requires resetting.

1. With electricity and gas turned on, the system switch in the “HEAT” or “AUTO” position and the fan switch in the “AUTO” position, the thermostat will close the circuit between unit terminals R and W (R-W) when the temperature falls below the thermostat setting. 2. D1 on IIC energizes relay IDMR. 3. Relay IDMR energizes the ventermotor IDM. 4. Operation of the ventermotor closes the pressure switch PS located in the burner compartment. Unless excessive temperatures or shipping shock have opened high limit control ALS, power is fed to the integrated ignition control, which then initiates a 15- second pre-purge time delay. During this period, the ventermotor will clear the combustion chamber of any residual gas. 5. After the pre-purge period, the ignition control energizes the Wl-C gas valve and simultaneously initiates a “three (3)-try” spark ignition sequence. 6. When the burners are ignited, a minimum one (1) micro-amp DC current will flow through the flame between the sensor electrode and the grounded burner. 7. When the controller proves that the flame has been established, it will keep the gas valve energized and discontinue the ignition spark. High stage manifold pressure will be approximately 3.5" w.c. for natural gas and 10.0" w.c. for propane (LP). Low fire natural gas is 2.0” w.c.; low fire propane 6.0” w.c. 8. If the control is unable to ignite the burners after its initial attempt, it will initiate another purge and spark sequence. A third purge and spark sequence will be initiated if the second attempt is unsuccessful. If the third attempt is unsuccessful, the controller will close the gas valve and lock itself out. It may be reset by momentarily interrupting power. This may be accomplished by briefly lowering the room thermostat set-point below room temperature, or by shutting off the main power to the unit. (See TP-105 for more details.)

NOTE: Gas appliances located more than 2000 feet above sea level must be derated 4% per 1000 feet of total elevation and that variance in gas heating value and specific gravity require change in manifold pressure to obtain rating, it is mandatory that the input be adjusted at the installation site. All installations should be made as outlined in the latest edition of the National Fuel Gas Code ANSI Z223.1,section “Procedures To Be Followed To Place An Appliance in Operation”. Refer also to the “User’s Information Manual” supplied with the unit for additional information on the gas furnace.

9. Integrated ignition control will close its normally open contacts after a delay of approximately 30 seconds. This action energizes contactor BC and starts the supply fan motor. Operation of the supply fan circulates air across the heat exchanger and delivers heated air to the conditioned space. 10. When the space temperature rises, the thermostat will open R-W. Opening R-W will cause the gas valve to close, and the furnace to shut down. 11. The furnace has three high temperature limit controls, which can shut down the burner. They do not shut down the ventermotor.
An external lockout occurs if the integrated ignition control determines that a measurable combustion cannot be estab- lished within three (3) consecutive ignition attempts. If flame is not established within the seven (7) second trial for igni- tion, the gas valve is deenergized, 15 second inter-purge cycle is completed, and ignition is reattempted. The control will repeat this routine three times if a measurable combustion is not established. The control will then shut off the induced draft blower and go into a lockout state.
If flame is established but lost, the control will energize the circulator blower at the heat speed and then begin a new ignition sequence. If flame is established then lost on subse- quent attempts, the control will recycle for four (4) consecu- tive ignition attempts (five attempts total) before locking out.
Located in the burner compartment on the heat exchanger, its sensing element projects through the blower section bulk- head and senses the temperature at the rear of the furnace. It will cycle the furnace off if the temperature exceeds 100°F plus maximum rise.
The diagnostic fault code is 1 flash for a lockout due to failed ignition attempts or flame dropouts. The integrated control will automatically reset after one hour, or it can be reset by removing the thermostat signal or disconnecting the electri- cal power supply for over five seconds. If the diagnostic LED indicates an external lockout, perform the following checks:
Located in the blower compartment on the blower housing, it senses air temperature within the blower compartment and protects the filters from excessive temperature. It will shut down the furnace if it senses excessive temperatures.
Located in the burner compartment at the top of the burner assembly, it senses high temperature that could occur if the heat exchanger tubes were plugged and the flame was roll- ing out instead of entering the tubes. It has a manual push- button reset that cannot be actuated until the limit control has cooled.
I GNITION C ONTROL E RROR C ODES
The following presents probable causes of questionable unit operation. Refer to Diagnostic Indicator Chart for an inter- pretation of the signal and to this section for an explanation.
Remove the control box access panel and note the number of diagnostic LED flashes. Refer to Diagnostic Indicator Chart for an interpretation of the signal and to this section for an explanation.
If the integrated ignition control in this unit encounters an in- ternal fault, it will go into a “hard” lockout and turn off the diagnostic LED. If diagnostic LED indicates an internal fault, check power supply to unit for proper voltage, check all fuses, circuit breakers and wiring. Disconnect electric power for five seconds. If LED remains off after restoring power, re- place control.

INPUT RATING
A pressure switch stuck open can be caused by a faulty pres- sure switch, faulty wiring, a disconnected or damaged hose, a blocked or restricted flue, or a faulty induced draft blower.
It is the responsibility of the contractor to adjust the gas input to the unit. The input rate can be calculated by using the formula:
If the control senses an open pressure switch during the pre- purge cycle, the induced draft blower only will be energized. If the pressure switch opens after ignition has begun the gas valve is deenergized, the circulator blower heat off cycle be- gins, and the induced draft blower remains on. The diagnos- tic fault code is two flashes.
INPUT Btu/Hr = 3600 x HV T WHERE: HV = Heating value of fuel = Btu/ft of gas T = Time in seconds per ft of gas flow as read from gas meter
Adjust input rate by varying the adjustment of the gas pres- sure regulator on the gas valve. All adjustments must be made with furnace operating at high fire and at normal operating temperature. Clockwise (P) rotation of the pressure regula- tor screw increases pressure and gas flow rate. Turn screw counterclockwise (Q) to decrease pressure and gas flow rate. After adjustment the furnace temperature rise must be within the range specified on the unit data plate. NOTE: Thermal efficiency of the furnace is a product efficiency rating deter- mined under continuous operating conditions independent of any installed system.
A stuck closed pressure switch can be caused by a faulty pressure switch or faulty wiring. If the control encounters a pressure switch stuck closed, the induced draft blower re- mains off. The diagnostic LED code for this fault is three (3) flashes.
If the primary limit switch opens, the gas valve is immediately deenergized, the induced draft and air circulating blowers are energized. The induced draft and air circulator blowers remain energized until the limit switch recloses. The diag- nostic fault code for an open limit is four (4) flashes.

A primary limit will open due to excessive supply air tempera- tures. This can be caused by a dirty filter, excessive duct static, insufficient air flow, or a faulty limit. Check filters, total external duct static, blower motor, blower motor speed tap (see wiring diagram), and limit. This limit will automatically reset once the temperature falls below a preset level.
If flame is detected with the gas valve deenergized, the com- bustion and air circulator blowers are energized. The diag- nostic fault code is five (5) flashes for this condition. The control can be reset by removing the power supply to the unit or it will automatically reset after one hour. Miswiring is the probable cause for this fault.

The automatic ignition control has a built-in feature that pre- vents damage to the compressor in short cycling situations. In the event of intermittent power losses or intermittent ther- mostat operation, the ignition control will delay output to the compressor contactor for three minutes from the time power is restored. (Compressor is off a total of three minutes). The diagnostic LED will flash six (6) times to indicate the com- pressor contactor output is being delayed.
Pressure Adjustments

EEM Motor
Adjust the CFM for the unit by changing the position of the low voltage leads on the motor terminal block. Green is for Fan Only. Yellow is for Cooling and Heat Pump Heating. Re- fer to Appendix A for blower performance at each speed tap. NOTE: If more than one lead is energized simultaneously, the motor will run at the higher speed.
VL, VM, & 2VP VARIABLE PITCH KEY TYPE MOTOR SHEAVES
The driving and driven motor sheaves should be in align- ment with each other and the shafts parallel.
1. Loosen set screw “B” using a 5/32" Allen key. 2. Making half or full turns from closed position, adjust sheave pitch diameter for desired speed. DO NOT OPEN MORE THAN FIVE FULL TURNS. 3. Tighten set screw “B” securely over flat. 4. Carefully put on belts and adjust belt tension. DO NOT FORCE BELTS OVER GROOVES. 5. Ensure all keys are in place and the set screws tight before starting drive. Recheck set screws and belt tension after 24 hours service.
TO PREVENT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE, THE GAS MANIFOLD PRESSURE MUST BE AS SPECIFIED ON THE UNIT RATING PLATE. ONLY MINOR ADJUSTMENTS SHOULD BE MADE BY ADJUSTING THE GAS VALVE PRESSURE REGULATOR.
The drive on the supply fan is typically set in the middle of the RPM range. The drive motor sheave pitch diameter is field adjustable for the required airflow. Refer to “Drive Adjustments” section below.
When the final adjustments are complete, the current draw of the motor should be checked and compared to the full load current rating of the motor. The amperage must not ex- ceed the service factor stamped on the motor nameplate. The total airflow must not be less than that required for op- eration of the electric heaters or the furnace.

If an economizer is installed, check the unit operating bal- ance with the economizer at full outside air and at minimum outside air. Upon completion of the air flow balancing, we recommend replacing the variable pitched motor sheave with a properly-sized fixed sheave. A matching fixed sheave will provide longer belt and bearing life and vibration free opera- tion. Initially, it is best to have a variable pitched motor sheave for the purpose of airflow balancing, but once the balance has been achieved, fixed sheaves maintain alignment and minimize vibration more effectively. For direct drive units, move fan speed wire.
VL & VM
Sheave
PSC M OTOR
HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
Adjust the CFM for the unit by changing the speed tap of the indoor blower motor at the heat or cool tap on the control board connection with the one of the speed taps on “M1” or “M2” (Black-High Speed, Blue-Medium Speed, Red-Low Speed).

Disposable return air filters are supplied with this unit. See the unit Specification Sheet or Technical Manual for the cor- rect size and part number. To remove the filters, remove the filter access panel on return side of the unit.
TO PREVENT PERSONAL INJURY OR DEATH DUE TO IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE, REFER TO THIS MANUAL. FOR ADDITIONAL ASSISTANCE OR INFORMATION, CONSULT A QUALIFIED INSTALLER, SERVICE AGENCY OR THE GAS SUPPLIER.
Use a fine grade automotive wax on the cabinet finish to maintain the finish’s original high luster. This is especially important in installations with extended periods of direct sun- light.
SHEET METAL PARTS, SCREWS, CLIPS AND SIMILAR ITEMS INHERENTLY HAVE SHARP EDGES, AND IT IS NECESSARY THAT THE INSTALLER AND SERVICE PERSONNEL EXERCISE CAUTION.
CLEAN OUTSIDE COIL (QUALIFIED SERVICER ONLY)
The coil with the outside air flowing over it should be inspected annually and cleaned as frequently as necessary to keep the finned areas free of lint, hair and debris.
Preventive maintenance is the best way to avoid unneces- sary expense and inconvenience. Have this system inspected at regular intervals by qualified service personnel, at least twice a year. Routine maintenance should cover the follow- ing items:
CONDENSER, EVAPORATOR, AND INDUCED DRAFT MOTORS
Bearings on the air circulating blower motor, condenser mo- tor and the combustion fan motor are permanently lubricated. No additional oiling is required.
1. Tighten all belts, set screws, and wire connections. 2. Clean evaporator and condenser coils mechanically or with cold water, if necessary. Usually any fouling is only matted on the entering air face of the coil and can be removed by brushing. 3. Lubricate motor bearings. 4. Align or replace belts as needed. 5. Replace filters as needed (see below). 6. Check for blockage of condensate drain. 7. Check power and control voltages. 8. Check running amperage. 9. Check operating temperatures and pressures. 10. Check and adjust temperature and pressure controls. 11. Check and adjust damper linkages. 12. Check operation of all safety controls. 13. Examine gas furnaces (see below and the User’s Information Manual). 14. Check condenser fans and tighten set screws.
A drop in the flame current can be caused by a nearly invis- ible coating on the flame sensor. This coating, created by the fuel or combustion air supply, can be removed by carefully cleaning the flame sensor with steel wool.
At the start of each heating season, inspect and, if neces- sary, clean the unit flue passage.
The fan shaft bearings, the 1 to 2 HP supply fan motors the condenser fan motors and compressors are permanently lu- bricated.
I NSPECTION & C LEANING
CAUTION
All flue product carrying areas of the furnace, its vent sys- tem, and main burners should be examined by a qualified service agency before the start of each heating season. This examination is necessary for continued safe operation. Par- ticular attention should be given to deterioration from corro- sion or other sources. This examination is accomplished in the following manner.
TO PREVENT PROPERTY DAMAGE DUE TO FIRE AND LOSS OF EQUIPMENT EFFICIENCY OR EQUIPMENT DAMAGE DUE TO DUST AND LINT BUILD UP ON INTERNAL PARTS, NEVER OPERATE UNIT WITHOUT AN AIR
FILTER INSTALLED IN THE RETURN AIR SYSTEM.
Every application may require a different frequency of replace- ment of dirty filters. Filters must be replaced at least every three (3) months during operating seasons.
Dirty filters are the most common cause of inadequate heat- ing or cooling performance. Filter inspection should be made at least every two months; more often if necessary because of local conditions and usage.
which wires are connected to each terminal.
Dirty throwaway filters should be discarded and replaced with a new, clean filter.


electrode. c. Disconnect the gas piping at the union. d. The entire burner assembly can now be removed
DO NOT REMOVE ANY INTERNAL COMPARTMENT COVERS OR ATTEMPT ANY
from the unit.
At least once a year, prior to or during the heating season, make a visual check of the burner flames.
3 Inspect and periodically clean the vent outlet (bird screen) on the access panel.
If a strong wind is blowing, it may alter the airflow pattern within the unit enough that an inspection of the burner flames is not possible.
Flames should be stable, soft and blue (dust may cause or- ange tips but must not be yellow). The flames must extend directly outward from the burner without curling, floating or lifting off.
Refer to the unit Parts Catalog for a list of functional parts. Parts are available from your distributor.
Check the burner flames for: 1. Good adjustment 2. Stable, soft and blue 3. Not curling, floating, or lifting off.

DIRECT DRIVE
CPG036 DOWN SHOT AND HORIZONTAL

0.10 1313 1.68 356 748 0.20 1247 1.63 344 786 0.30 1178 1.59 334 832 0.40 1094 1.55 324 869 0.50 1002 1.50 312 913 0.60 919 1.45 296 940
0.10 1471 2.11 454 830 0.20 1400 2.06 440 863 0.30 1354 2.02 432 896 0.40 1271 1.95 416 929 0.50 1188 1.90 398 957 0.60 1083 1.82 378 984 0.70 955 1.74 356 1012
0.30 1470 2.37 510 935 0.40 1390 2.31 492 957 0.50 1310 2.25 476 978 0.60 1206 2.17 454 1000 0.70 1098 2.09 436 1023 0.80 966 1.99 412 1045

0.10 1293 1.72 364 715 0.20 1235 1.67 354 759 0.30 1173 1.62 342 803 0.40 1124 1.58 330 841 0.50 1056 1.54 316 880 0.60 978 1.47 298 913
0.10 1500 2.13 462 808 0.20 1434 2.10 448 838 0.30 1381 2.04 436 869 0.40 1318 2.00 424 902 0.50 1238 1.94 406 929 0.60 1163 1.88 392 951 0.70 1055 1.80 370 990
0.80 936 1.72 350 1017 0.40 1441 2.35 504 940 0.50 1355 2.28 484 962 0.60 1264 2.21 468 989 0.70 1157 2.13 446 1012 0.80 1027 2.03 418 1034 0.90 840 1.90 388 1067
Tables represent dry coil without filter, to compensate for filter add 0.08" to measured E.S.P. SCFM correction for wet coil = 4 %.
3 Ton models are shipped from the factory with speed tap set on LOW.

DIRECT DRIVE
CPG048 DOWN SHOT AND HORIZONTAL

0.10 1592 2.54 543 815 0.20 1528 2.43 521 858 0.30 1464 2.32 499 901 0.40 1380 2.21 475 930 0.50 1296 2.10 451 959
0.10 1828 3.08 665 892 0.20 1700 2.75 601 924 0.30 1606 2.61 563 966 0.40 1531 2.48 537 990 0.50 1401 2.32 503 1023 0.60 1287 2.22 477 1045 0.70 1123 2.05 441 1073
0.10 1926 3.34 740 937 0.20 1825 3.18 700 965 0.30 1712 3.03 660 989 0.40 1598 2.87 626 1015 0.50 1482 2.76 596 1032 0.60 1357 2.62 564 1049

0.10 1612 2.60 554 789 0.20 1548 2.49 532 832 0.30 1484 2.38 510 875 0.40 1400 2.27 486 904 0.50 1316 2.16 462 933
0.10 1846 3.14 676 866 0.20 1718 2.81 612 898 0.30 1624 2.67 574 940 0.40 1549 2.54 548 964 0.50 1419 2.38 514 997 0.60 1305 2.28 488 1019 0.70 1141 2.11 452 1047
0.10 1954 3.43 758 924 0.20 1853 3.27 718 952 0.30 1740 3.12 678 976 0.40 1626 2.96 644 1002 0.50 1510 2.85 614 1019 0.60 1385 2.71 582 1036
Tables represent dry coil without filter, to compensate for filter add 0.08" to measured E.S.P. SCFM correction for wet coil = 4 %.
4 Ton models are shipped from the factory with speed tap set on MED.

DIRECT DRIVE
CPG060 DOWN SHOT
SPEED
STANDARD
PRESSURE (ESP)
CFM AMPS WATTS RPM
TAP
in w.c.
0.10 1237 1.64 180 638 0.20 1191 1.75 194 682 0.30 1127 1.80 200 715 0.40 1065 1.89 214 753 0.50 994 1.97 220 797
0.10 1437 2.13 248 687 0.20 1384 2.24 254 726 0.30 1312 2.29 262 759 0.40 1245 2.42 280 803 0.50 1185 2.54 294 847
0.10 1988 4.49 558 885 0.20 1942 4.58 574 907 0.30 1882 4.69 582 935 0.40 1847 4.80 600 962 0.50 1784 4.87 612 990 0.60 1762 4.97 626 1008 0.70 1688 5.05 642 1039
0.10 2106 5.14 650 924 0.20 2050 5.26 670 951 0.30 1993 5.32 678 969 0.40 1960 5.47 696 1001 0.50 1920 5.54 706 1021 0.60 1880 5.61 726 1041 0.70 1810 5.73 736 1072 0.80 1760 5.81 750 1093 0.90 1694 5.84 752 1122
0.10 2199 5.87 762 968 0.20 2146 5.96 772 989 0.30 2121 6.06 788 1012 0.40 2066 6.15 804 1039 0.50 2010 6.21 814 1056 0.60 1978 6.32 834 1084 0.70 1919 6.28 830 1102 0.80 1837 6.22 814 1122 0.90 1738 6.04 786 1127
Tables represent dry coil without filter, to compensate for filter add 0.08" to measured E.S.P. SCFM correction for wet coil = 4 %. 5 Ton models are shipped from the factory with speed tap set on T4.

DIRECT DRIVE
CPG060 HORIZONTAL
SPEED
STANDARD
PRESSURE (ESP)
CFM AMPS WATTS RPM
TAP
in w.c.
0.10 1416 1.63 176 588 0.20 1295 1.61 174 621 0.30 1200 1.68 186 660 0.40 1133 1.79 196 704 0.50 1045 1.90 208 753
0.10 1543 2.00 220 627 0.20 1485 2.12 236 671 0.30 1425 2.20 250 698 0.40 1352 2.26 258 748 0.50 1304 2.39 274 786
0.10 2107 4.02 502 797 0.20 2031 4.13 518 819 0.30 1980 4.27 536 858 0.40 1954 4.37 554 880 0.50 1887 4.48 572 913 0.60 1839 4.58 582 940 0.70 1782 4.72 602 968
0.10 2224 4.73 592 832 0.20 2165 4.79 612 860 0.30 2123 4.91 630 891 0.40 2079 5.01 642 913 0.50 2029 5.14 666 946 0.60 1978 5.26 676 969 0.70 1926 5.38 698 1001 0.80 1872 5.48 712 1028 0.90 1817 5.58 722 1056
0.10 2318 5.42 700 874 0.20 2296 5.55 720 903 0.30 2228 5.66 734 929 0.40 2193 5.76 748 950 0.50 2145 5.90 766 979 0.60 2097 5.99 784 1012 0.70 2054 6.10 798 1034 0.80 1991 6.15 810 1050 0.90 1952 6.26 826 1079
Tables represent dry coil without filter, to compensate for filter add 0.08" to measured E.S.P. SCFM correction for wet coil = 4 %. 5 Ton models are shipped from the factory with speed tap set on T4.

BELT DRIVE
STANDARD DOWN SHOT

CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.4 1628 0.41 1396 0.32 1171 0.24 900 0.16
0.6 1541 0.43 1284 0.32 1024 0.23 714 0.14

CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.4 2002 0.65 1708 0.49 1438 0.36 1167 0.22
0.6 1910 0.67 1612 0.50 1330 0.37 1030 0.23
0.8 1813 0.69 1571 0.54 1222 0.36 989 0.25

CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.2 2460 0.96 2251 0.80 2073 0.65 1862 0.51
0.4 2408 1.00 2206 0.84 1982 0.68 1808 0.55 1572 0.41
0.6 2402 1.08 2173 0.89 1943 0.72 1701 0.55 1511 0.43

CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.2 2625 1.18 2486 1.02 2322 0.83 2152 0.68
0.4 2765 1.52 2596 1.28 2476 1.09 2327 0.94 2159 0.75 1938 0.59
0.6 2650 1.43 2452 1.18 2325 1.00 2070 0.80 1898 0.64
0.8 2443 1.29 2251 1.06 2068 0.86 1868 0.71
Tables represent dry coil without filter, to compensate for filter add 0.08" to measured E.S.P. SCFM correction for wet coil = 4 %.

BELT DRIVE
STANDARD HORIZONTAL

CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.4 1628 0.41 1396 0.32 1171 0.24 900 0.16
0.6 1541 0.43 1284 0.32 1024 0.23 714 0.14

CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.4 2002 0.65 1708 0.49 1438 0.36 1167 0.22
0.6 1910 0.67 1612 0.50 1330 0.37 1030 0.23
0.8 1813 0.69 1571 0.54 1222 0.36 989 0.25

CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.2 2460 0.96 2251 0.80 2073 0.65 1862 0.51
0.4 2408 1.00 2206 0.84 1982 0.68 1808 0.55 1572 0.41
0.6 2402 1.08 2173 0.89 1943 0.72 1701 0.55 1511 0.43

CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.4 2680 1.22 2544 1.06 2346 0.84 2164 0.68
0.6 2655 1.31 2498 1.10 2306 0.92 2094 0.72 1890 0.57
0.8 2703 1.47 2486 1.20 2263 0.97 2076 0.81
Tables represent dry coil without filter, to compensate for filter add 0.08" to measured E.S.P. SCFM correction for wet coil = 4 %.

BELT DRIVE
HIGH STATIC DOWN SHOT

H2O 4 5 0 1 2 3
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.8 1640 0.571 1342 0.426 1035 0.289 775 0.19
1.0 1638 0.632 1326 0.471 1002 0.317 713 0.192

CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.8 1929 0.788 1662 0.631 1384 0.469 1106 0.329
1.0 1952 0.876 1622 0.665 1335 0.494 1056 0.345
1.2 1897 0.93 1611 0.726 1315 0.543 1008 0.357

CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.6 2262 1.161 2051 0.948 1851 0.763 1657 0.60
0.8 2277 1.271 2070 1.048 1852 0.837 1646 0.656
1.0 2304 1.387 2089 1.153 1872 0.931 1647 0.722

CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.6 2793 1.645 2575 1.367 2407 1.155 2250 0.963
0.8 2775 1.762 2638 1.526 2407 1.253 2226 1.045 2011 0.835
1.0 2821 1.894 2660 1.668 2407 1.358 2194 1.116 2012 0.923
1.2 2696 1.787 2497 1.54 2228 1.235 1977 0.985
Tables represent dry coil without filter, to compensate for filter add 0.08" to measured E.S.P. SCFM correction for wet coil = 4 %.

BELT DRIVE - HIGH STATIC HORIZONTAL

CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP

CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP

CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.8 2215 1.04 1956 0.82 1697 0.62 1.0 2240 1.15 1957 0.90 1681 0.67

CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.6 2677 1.29 2486 1.07 0.8 2690 1.42 2529 1.20 2263 0.94
1.0 2740 1.60 2471 1.27 2246 1.02 1972 0.79
1.2 2748 1.74 2518 1.44 2255 1.13 1970 0.87
1.4 2797 1.87 2562 1.59 2273 1.27 2025 0.99
Tables represent dry coil without filter, to compensate for filter add 0.08" to measured E.S.P. SCFM correction for wet coil = 4 %.

VOLTAGE LIMITATION
INDOOR
INDOOR FAN MOTOR
MODELS VOLTAGE (NAMEPLATE)
MOTOR APPLICATION
MIN. MAX. QTY RLA LRA QTY HP RLA HP FLA
208/230-60-1 187 253 1 16.67 79 1 1/4 1.40 DD STD STATIC 1/3 2.5
1 10.45 73.0 1 187 253
1/4 1.40
BD STD STATIC 1.0 3.8
460-60-3 414 506 1 5.77 38.0 1 1/4 0.80 BD STD STATIC 1.0 1.9
575-60-3 518 633 1 3.8 37.0 1 1/4 0.60 BD STD STATIC 1.5 2.3
208/230-60-1 187 253 1 19.87 109 1 1/4 1.40 DD STD STATIC 1/2 2.9
208/230-60-3 187 253 1 13.14 83.1
1 1/4 1.40
BD STD STATIC 1.0 3.8
460-60-3 414 506 1 6.09 41.0 1 1/4 0.80 BD STD STATIC 1.0 1.9
575-60-3 518 633 1 4.4 33.0 1 1/4 0.60 BD STD STATIC 1.5 2.3
208/230-60-1 187 253 1 26.41 134 1 1/4 1.40 DD STD STATIC 1.0 7.6
187 253 1/4 1.40 1 15.96 110.0 1
BD STD STATIC 1.0 3.8
460-60-3 414 506 1 7.76 52.0 1 1/4 0.80 BD STD STATIC 1.0 1.9
575-60-3 518 633 1 5.71 38.9 1 1/4 0.60 BD STD STATIC 1.5 2.3
208/230-60-3 187 253 1 19 123 1 1/3 1.92 BD STD STATIC 1.5 5.0
460-60-3 414 506 1 9.70 62.0 1 1/3 1.20 BD STD STATIC 1.5 2.5
575-60-3 518 633 1 7.4 50.0 1 1/3 0.90 BD STD STATIC 1.5 2.3
208/230-60-3 · 208/230-60-3





HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
PU ALTERNATE MOTOR 6-WIRES SEE NOTE 6 & 7
36 Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.

HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
COMPONENT LEGEND
FACTORY WIRING
COMP ALS
AUXILIARY LIMIT SWITCH
LINE VOLTAGE
COMPRESSOR
LOW VOLTAGE
CM CONDENSER MOTOR
OPTIONAL HIGH VOLTAGE
CONTACTOR
C T1
R
EVAPORATOR MOTOR FUSE F
S H C
FIELD WIRING
FS GND
EQUIPMENT GROUND FLAME SENSOR
CM F
HIGH VOLTAGE
LOW VOLTAGE
GV
HPS HIGH PRESSURE SWITCH
HEAT
IGN IIC
INTEGRATED IGNITION CONTROL
WIRE CODE
IGNITOR
BK BLACK
FC PCB
LS LIMIT SWITCH
BL BLUE
LPS LOW PRESSURE SWITCH
BR BROWN
PCB
PS PLF
FEMALE PLUG/CONNECTOR
COOL
GR GREEN
VM LI
DI
PRESSURE SWITCH
OR ORANGE
RUN CAPACITOR FOR CONDENSER FAN RCCF
PU PURPLE PK PINK
TB1 RS
TERMINAL BLOCK (24V SIGNAL) ROLLOUT SWITCH
RD RED
YL YELLOW TB1
TR TRANSFORMER
VMR VM
VENT MOTOR RELAY VENT MOTOR
WH WHITE
IGN
IIC FS
BLOWER CAPACITOR BC
BL/PK BLUE WITH PINK STRIP YL/PK YELLOW WITH PINK STRIP
NOTES
RS ALS
GV
W
WH GR
W
G
G
HPS LPS
BK - HIGH SPEED BL - MED. SPEED RD - LOW SPEED 3 SPEED MOTOR
R
Y1
Y
G R
Y1 W Y2
PLF C
TO THERMOSTAT TERMINAL BLOCK
STAT
USE NEC CLASS 2 WIRE. 5. USE COPPER CONDUCTORS ONLY.
INSTALLER/SERVICEMAN
W
W
R G
CHECK
STATUS LIGHT
EQUIP. STATUS
Y1
Y
ON
NORMAL OPERATION
Y/Y2
OFF
NO POWER OR INTERNAL CONTROL
1 BLINK
IGNITION FAILURE
GAS FLOW
STAT
OR
GAS PRESSURE
OPEN ROLLOUT
SWITCH
FLAME SENSOR
2 STAGE COOLING
OR
FLAME ROLLOUT
OPEN AUX. LIMIT
BAD SWITCH AUX. LIMIT OPEN
W
W
SWITCH
G
G R
2 BLINKS
PRESSURE SWITCH
CHECK
SEE UNIT RATING PLATE FOR TYPE AND SIZE OF OVERCURRENT PROTECTION.
PRESSURE SWITCH
R RD
3 BLINKS
CHECK
Y1
Y1
WITHOUT INDUCER ON
PRESSURE SWITCH
4 BLINKS
OPEN LIMIT SWITCH
MAIN LIMIT OPEN
Y/Y2
Y2
BAD SWITCH
5 BLINKS
FALSE FLAME SENSED
6 BLINKS
COMPRESSOR
3 MIN. COMP.
OUTPUT DELAY
208-240/1/60 0140L00510 REV A
37 Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.


HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
PU ALTERNATE MOTOR 6-WIRES SEE NOTE 6 & 7
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.

HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
COMPONENT LEGEND
FACTORY WIRING
AUXILIARY LIMIT SWITCH
COMP ALS
LINE VOLTAGE
COMPRESSOR
LOW VOLTAGE
CM CONDENSER MOTOR
CONTACTOR
OPTIONAL HIGH VOLTAGE
C T1
R
EVAPORATOR MOTOR FUSE F
S H C
FIELD WIRING
FS GND
EQUIPMENT GROUND FLAME SENSOR
HIGH VOLTAGE
CM F
LOW VOLTAGE
GV
HPS HIGH PRESSURE SWITCH
HEAT
IGN IIC
INTEGRATED IGNITION CONTROL
WIRE CODE
IGNITOR
BK BLACK
FC PCB
LS LIMIT SWITCH
BL BLUE
LPS LOW PRESSURE SWITCH
PCB
PLF
FEMALE PLUG/CONNECTOR
BR BROWN
COOL
GR GREEN
VM LI
DI RUN CAPACITOR FOR CONDENSER FAN RCCF
OR ORANGE
PRESSURE SWITCH
TB1 RS
TERMINAL BLOCK (24V SIGNAL) ROLLOUT SWITCH
PU PURPLE PK PINK
RD RED
TR TRANSFORMER
YL YELLOW TB1
VMR VM
VENT MOTOR RELAY VENT MOTOR
WH WHITE
IIC FS
IGN
BLOWER CAPACITOR BC
BL/PK BLUE WITH PINK STRIP YL/PK YELLOW WITH PINK STRIP
NOTES
LS 4
THERMOSTAT FIELD WIRING
W
WH GR
W
BK - HIGH SPEED BL - MED. SPEED RD - LOW SPEED 3 SPEED
G
G
HPS LPS
R
R
Y1
Y
G R
Y1 W Y2
PLF C
TO THERMOSTAT TERMINAL BLOCK
STAT
USE NEC CLASS 2 WIRE. 5. USE COPPER CONDUCTORS ONLY.
INSTALLER/SERVICEMAN
W
GR G
R G
7. SPEED TAP TERMINATIONS SHOWN ON
R
STATUS LIGHT
EQUIP. STATUS
CHECK
DIAGRAM ARE REPRESENTATIVE, BUT ACTUAL FACTORY SETTING MAY BE DIFFERENT BASED ON HEATING VALUE AND CAPACITY OF UNIT.
Y
ON
NORMAL OPERATION
Y/Y2
OFF
NO POWER OR INTERNAL CONTROL
1 BLINK
IGNITION FAILURE
GAS FLOW
STAT
OR
GAS PRESSURE
OPEN ROLLOUT
SWITCH
FLAME SENSOR
2 STAGE COOLING
OR
FLAME ROLLOUT
OPEN AUX. LIMIT
BAD SWITCH AUX. LIMIT OPEN
W
W
SWITCH
G R
2 BLINKS
PRESSURE SWITCH
CHECK
R RD
OPEN
PRESSURE SWITCH
3 BLINKS
CHECK
Y1
Y1
WITHOUT INDUCER ON
PRESSURE SWITCH
4 BLINKS
OPEN LIMIT SWITCH
MAIN LIMIT OPEN
Y/Y2
Y2
BAD SWITCH
SEE UNIT RATING PLATE FOR TYPE AND SIZE OF OVERCURRENT PROTECTION.
FALSE FLAME SENSED
6 BLINKS
COMPRESSOR
3 MIN. COMP.
208-240/1/60 0140L00506 REV A
STAT
39 Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.


HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
40 Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.

HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
COMPONENT LEGEND
FACTORY WIRING
COMP ALS
AUXILIARY LIMIT SWITCH
LINE VOLTAGE
COMPRESSOR
LOW VOLTAGE
CM CONDENSER MOTOR
OPTIONAL HIGH VOLTAGE
C T1
CONTACTOR
R
EVAPORATOR MOTOR
S H C
FUSE F
FIELD WIRING
FS GND
EQUIPMENT GROUND FLAME SENSOR
CM C
HIGH VOLTAGE
LOW VOLTAGE
GV
HIGH PRESSURE SWITCH HPS
EM L N
IGN IIC
INTEGRATED IGNITION CONTROL
VMR
IGNITOR
WIRE CODE
BK BLACK
LOW PRESSURE SWITCH LPS
LS LIMIT SWITCH
BL BLUE
PS PLF
FEMALE PLUG/CONNECTOR
BR BROWN
PRESSURE SWITCH
GR GREEN
RCCF
RUN CAPACITOR FOR COMPRESSOR/FAN
OR ORANGE
IGN NOTE 6 L1
TB1 RS
TERMINAL BLOCK (24V SIGNAL) ROLLOUT SWITCH
PU PURPLE PK PINK
TR TRANSFORMER
FS
FS
RD RED
F
H C
VMR VM
VENT MOTOR RELAY VENT MOTOR
WH WHITE
C EM
YL YELLOW
BL/PK BLUE WITH PINK STRIP YL/PK YELLOW WITH PINK STRIP
NOTES
RS ALS
GV
W
WH GR
W
G R
G R
COOLING SPEED (YELLOW WIRE)
T3 - LOW SPEED T4 - HIGH SPEED
RD Y1
LPS HPS
HEATING SPEED (WHITE WIRE)
Y/Y2
Y C
PLF 4
T5 - HIGH SPEED (140) T2 - MED. SPEED T1 - LOW SPEED (070)
G R
W2
TO THERMOSTAT TERMINAL BLOCK
WITH ECONOMIZER OPTION
INSTALLER/SERVICEMAN
W
W
USE NEC CLASS 2 WIRE. 5. USE COPPER CONDUCTORS ONLY.
R G
R
STATUS LIGHT
EQUIP. STATUS
CHECK
Y
ON
NORMAL OPERATION
Y/Y2
OFF
NO POWER OR INTERNAL CONTROL
FAULT
1 BLINK
IGNITION FAILURE
GAS FLOW
OR
GAS PRESSURE
OPEN ROLLOUT
SWITCH
FLAME SENSOR
2 STAGE COOLING
OR
FLAME ROLLOUT
OPEN AUX. LIMIT
BAD SWITCH AUX. LIMIT OPEN
W
W
SWITCH
G
G R
2 BLINKS
PRESSURE SWITCH
CHECK
R RD
OPEN
PRESSURE SWITCH
3 BLINKS
CHECK
Y1
Y1
WITHOUT INDUCER ON
PRESSURE SWITCH
SEE UNIT RATING PLATE FOR TYPE AND SIZE OF OVER
Y2
4 BLINKS
OPEN LIMIT SWITCH
MAIN LIMIT OPEN
BAD SWITCH
CURRENT PROTECTION .
FALSE FLAME SENSED
6 BLINKS
COMPRESSOR
3 MIN. COMP.
240/1/60 0140L00429 REV B
STAT
41 Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.


HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
42 Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.


HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
43 Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.


HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
44 Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.

HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
COMPONENT LEGEND
FACTORY WIRING
COMP ALS
AUXILLARY LIMIT SWITCH
LINE VOLTAGE
COMPRESSOR
CM CONDENSER MOTOR
LOW VOLTAGE
OPTIONAL HIGH VOLTAGE
C T2
CONTACTOR
C T1
EVAPORATOR MOTOR
FUSE F
T3 T3
FC
FAN CAPACITOR
FIELD WIRING
FS GND
EQUIPMENT GROUND FLAME SENSOR
HIGH VOLTAGE
FC
CM
LOW VOLTAGE
GV
HPS HIGH PRESSURE SWITCH
WIRE CODE
HEAT
IGN IIC
INTEGRATED IGNITION CONTROL
IGNITOR
BK BLACK
LS LIMIT SWITCH
BL BLUE
FC PCB
BR BROWN
PCB
LPS LOW PRESSURE SWITCH
PS PLF
FEMALE PLUG/CONNECTOR
GR GREEN
COOL
DI
PRESSURE SWITCH
OR ORANGE
TB1 RS
TERMINAL BLOCK (24V SIGNAL) ROLLOUT SWITCH
PU PURPLE PK PINK
TR TRANSFORMER
RD RED
VMR VM
VENT MOTOR RELAY VENT MOTOR
WH WHITE
IGN
IIC FS
YL YELLOW
FS F
BLOWER CAPACITOR BC
BL/PK BLUE WITH PINK STRIP YL/PK YELLOW WITH PINK STRIP
RS ALS
GV
W
WH GR
W
G
G
HPS LPS
BK - HIGH SPEED BL - MED. SPEED RD - LOW SPEED 3 SPEED MOTOR
R
Y1
Y
G R
Y1 W Y2
PLF C
TO THERMOSTAT TERMINAL BLOCK
STAT
USE NEC CLASS 2 WIRE. 5. USE COPPER CONDUCTORS ONLY.
INSTALLER/SERVICEMAN
W
W
G
R
STATUS LIGHT
EQUIP. STATUS
CHECK
Y1
Y
ON
NORMAL OPERATION
Y/Y2
OFF
NO POWER OR INTERNAL CONTROL
1 BLINK
IGNITION FAILURE
GAS FLOW
STAT
OR
GAS PRESSURE
OPEN ROLLOUT
SWITCH
FLAME SENSOR
2 STAGE COOLING
OR
FLAME ROLLOUT
W
W
OPEN AUX. LIMIT
BAD SWITCH AUX. LIMIT OPEN
SWITCH
G
G
2 BLINKS
PRESSURE SWITCH
CHECK
OPEN
PRESSURE SWITCH
R RD
R
SEE UNIT RATING PLATE FOR TYPE AND SIZE OF OVERCURRENT PROTECTION.
CHECK
Y1
Y1
WITHOUT INDUCER ON
PRESSURE SWITCH
4 BLINKS
OPEN LIMIT SWITCH
MAIN LIMIT OPEN
Y/Y2
Y2
BAD SWITCH
5 BLINKS
FALSE FLAME SENSED
6 BLINKS
COMPRESSOR
3 MIN. COMP.
OUTPUT DELAY
208-240/3/60 0140L00512 REV B
45 Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.


HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
46 Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.

HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
COMPONENT LEGEND
FACTORY WIRING
COMP ALS
AUXILIARY LIMIT SWITCH
LINE VOLTAGE
COMPRESSOR
CM CONDENSER MOTOR
LOW VOLTAGE
OPTIONAL HIGH VOLTAGE
C T2
CONTACTOR
C T1
EVAPORATOR MOTOR
FUSE F
T3 T3
FC
FAN CAPACITOR
FIELD WIRING
FS GND
EQUIPMENT GROUND FLAME SENSOR
HIGH VOLTAGE
FC
CM
LOW VOLTAGE
GV
HPS HIGH PRESSURE SWITCH
WIRE CODE
HEAT
IGN IIC
INTEGRATED IGNITION CONTROL
IGNITOR
BK BLACK
LS LIMIT SWITCH
BL BLUE
FC PCB
LPS LOW PRESSURE SWITCH
BR BROWN
PCB
PS PLF
FEMALE PLUG/CONNECTOR
GR GREEN
COOL
DI
PRESSURE SWITCH
OR ORANGE
TB1 RS
TERMINAL BLOCK (24V SIGNAL) ROLLOUT SWITCH
PU PURPLE PK PINK
TR TRANSFORMER
RD RED
VMR VM
VENT MOTOR RELAY VENT MOTOR
WH WHITE
IGN
IIC FS
YL YELLOW
FS F
BLOWER CAPACITOR BC
BL/PK BLUE WITH PINK STRIP YL/PK YELLOW WITH PINK STRIP
RS ALS
GV
W
WH GR
W
G
G
HPS LPS
BK - HIGH SPEED BL - MED. SPEED RD - LOW SPEED 3 SPEED MOTOR
R
Y1
Y
G R
Y1 W Y2
PLF C
TO THERMOSTAT TERMINAL BLOCK
STAT
USE NEC CLASS 2 WIRE. 5. USE COPPER CONDUCTORS ONLY.
INSTALLER/SERVICEMAN
W
W
G
R
STATUS LIGHT
EQUIP. STATUS
CHECK
Y1
Y
ON
NORMAL OPERATION
Y/Y2
OFF
NO POWER OR INTERNAL CONTROL
1 BLINK
IGNITION FAILURE
GAS FLOW
STAT
OR
GAS PRESSURE
OPEN ROLLOUT
SWITCH
FLAME SENSOR
2 STAGE COOLING
OR
FLAME ROLLOUT
W
OPEN AUX. LIMIT
BAD SWITCH AUX. LIMIT OPEN
W
SWITCH
G
2 BLINKS
PRESSURE SWITCH
CHECK
OPEN
PRESSURE SWITCH
R RD
R
3 BLINKS
CHECK
Y1
Y1
WITHOUT INDUCER ON
PRESSURE SWITCH
Y2
4 BLINKS
OPEN LIMIT SWITCH
MAIN LIMIT OPEN
SEE UNIT RATING PLATE FOR TYPE AND SIZE OF OVERCURRENT PROTECTION.
BAD SWITCH
5 BLINKS
FALSE FLAME SENSED
6 BLINKS
COMPRESSOR
3 MIN. COMP.
OUTPUT DELAY
208-240/3/60 0140L00507 REV B
47 Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.


HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
48 Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.

HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
COMPONENT LEGEND
ALS
AUXILIARY LIMIT SWITCH
T2 T1
FACTORY WIRING
BC BLOWER CONTACTOR
LINE VOLTAGE
COMP
COMPRESSOR
CONDENSER MOTOR CM
LOW VOLTAGE
C CM
OPTIONAL HIGH VOLTAGE
FC
CONTACTOR
EVAPORATOR MOTOR
BC
F FUSE FC
FAN CAPACITOR
FIELD WIRING
BC
BC
HIGH VOLTAGE
GND FS
FLAME SENSOR EQUIPMENT GROUND
VMR
LOW VOLTAGE
GV
WIRE CODE
HPS HIGH PRESSURE SWITCH
BK BLACK
IBR INDOOR BLOWER RELAY
BL BLUE
OR BK
IIC IGN
INTEGRATED IGNITION CONTROL
IGNITOR
BR BROWN
LPS LOW PRESSURE SWITCH
GR GREEN
OR ORANGE
LIMIT SWITCH LS
PLF PS
FEMALE PLUG/CONNECTOR
PU PURPLE PK PINK
PRESSURE SWITCH
RS TB1
ROLLOUT SWITCH TERMINAL BLOCK (24V SIGNAL)
RD RED
FS IGN
BC IIC
FS F
WH WHITE
TRANSFORMER TR
YL YELLOW
H C
VM VMR
VENT MOTOR VENT MOTOR RELAY
BL/PK BLUE WITH PINK STRIP YL/PK YELLOW WITH PINK STRIP
VMR
THERMOSTAT FIELD WIRING
LS
ALS
RS
NOTES
NO ECONOMIZER
GV
WH GR
W
G R
G R
Y/Y2
Y C
USE NEC CLASS 2 WIRE.
Y Y2 W Y1
R G
W
W
G
R G
R
INSTALLER/SERVICEMAN
Y1
Y
Y/Y2
STATUS LIGHT
EQUIP. STATUS
CHECK
ON
NORMAL OPERATION
STAT
OFF
NO POWER OR
2 STAGE COOLING
INTERNAL CONTROL
W
W
1 BLINK
IGNITION FAILURE
GAS FLOW
GAS PRESSURE
G
G R
OPEN ROLLOUT
R RD
SWITCH
FLAME SENSOR
FLAME ROLLOUT
Y1
Y1
OPEN AUX. LIMIT
BAD SWITCH
SWITCH
AUX. LIMIT OPEN
Y/Y2
Y2
SEE UNIT RATING PLATE FOR TYPE AND
2 BLINKS
PRESSURE SWITCH
CHECK
SIZE OF OVER CURRENT PROTECTION.
PRESSURE SWITCH
3 BLINKS
CHECK
OPEN LIMIT SWITCH WITHOUT INDUCER ON
PRESSURE SWITCH
STAT
4 BLINKS
MAIN LIMIT OPEN
BAD SWITCH
5 BLINKS
FALSE FLAME SENSED
6 BLINKS
COMPRESSOR
3 MIN. COMP.
460-575/3/60 0140L00870 REV B
49 Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.


HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
50 Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.

HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
COMPONENT LEGEND
ALS
AUXILIARY LIMIT SWITCH
FACTORY WIRING
LINE VOLTAGE
BC BLOWER CONTACTOR
COMP
COMPRESSOR
LOW VOLTAGE
CONDENSER MOTOR CM
OPTIONAL HIGH VOLTAGE
T2 T1 T1
CONTACTOR
EVAPORATOR MOTOR
F FUSE FC
FIELD WIRING
C CM
FAN CAPACITOR
FC
HIGH VOLTAGE
GND FS
FLAME SENSOR EQUIPMENT GROUND
LOW VOLTAGE
BC
GV
WIRE CODE
BC
BC
HPS HIGH PRESSURE SWITCH
BK BLACK
IBR INDOOR BLOWER RELAY
BL BLUE
IIC IGN
INTEGRATED IGNITION CONTROL
BR BROWN
IGNITOR
3 VMR
LPS LOW PRESSURE SWITCH
GR GREEN
OR ORANGE
LIMIT SWITCH LS
PU PURPLE PK PINK
PLF PS
FEMALE PLUG/CONNECTOR
PRESSURE SWITCH
RD RED
FS IGN
BC IIC
RS TB1
ROLLOUT SWITCH TERMINAL BLOCK (24V SIGNAL)
FS F
WH WHITE
TRANSFORMER TR
YL YELLOW
H C
VM VMR
VENT MOTOR VENT MOTOR RELAY
BL/PK BLUE WITH PINK STRIP YL/PK YELLOW WITH PINK STRIP
VMR
THERMOSTAT FIELD WIRING
LS
ALS
RS
NOTES
NO ECONOMIZER
GV
WH GR
W
G R
G R
Y/Y2
Y C
LPS HPS
USE NEC CLASS 2 WIRE. 4. USE COPPER CONDUCTORS ONLY.
6 PLF
R G
Y Y2 W Y1
W2
W
W
G
R G
INSTALLER/SERVICEMAN
Y1
Y
Y/Y2
STATUS LIGHT
EQUIP. STATUS
CHECK
STAT
ON
NORMAL OPERATION
OFF
NO POWER OR
INTERNAL CONTROL
2 STAGE COOLING
W
W
1 BLINK
IGNITION FAILURE
GAS FLOW
G
G R
GAS PRESSURE
OPEN ROLLOUT
R RD
SWITCH
FLAME SENSOR
FLAME ROLLOUT
Y1
Y1
OPEN AUX. LIMIT
BAD SWITCH
SWITCH
AUX. LIMIT OPEN
Y/Y2
Y2
2 BLINKS
PRESSURE SWITCH
CHECK
OPEN
PRESSURE SWITCH
3 BLINKS
CHECK
STAT
OPEN LIMIT SWITCH WITHOUT INDUCER ON
PRESSURE SWITCH
4 BLINKS
MAIN LIMIT OPEN
BAD SWITCH
5 BLINKS
FALSE FLAME SENSED
208-240/3/60 0140L00981 REV B
6 BLINKS
COMPRESSOR
3 MIN. COMP.
51 Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
208-240/3/60


HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
52 Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.


HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
YL/PK YELLOW WITH PINK STRIP BL/PK BLUE WITH PINK STRIP
53 Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.


HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
54 Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.


HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
BL/PK BLUE WITH PINK STRIP YL/PK YELLOW WITH PINK STRIP
USE NEC CLASS 2 WIRE. 4. USE COPPER CONDUCTORS ONLY.
SEE UNIT RATING PLATE FOR TYPE AND SIZE OF OVER
55 Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.

www.goodmanmfg.com www.amana-hac.com
© 2009-2011 Goodman Manufacturing Company, L.P.