Instruction/ maintenance manual of the product SSZ 14 SEER Goodman
Go to page of 39
SSZ 14 SEER S plit System Heat Pump s • Refer to Service Manual RS6200005 for installation, operation, and troubleshooting information. • All safety information must be followed as provided in the Service Manual. • Refer to the appropriate Parts Catalog for part number information.
PRODUCT IDENTIFICA TION 2 The model number is used for positive identification of component parts used in manufacturing. Please use this number when requesting service or parts information. WARNING WARNING HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit.
PRODUCT IDENTIFICA TION 3 The United States Environmental Protection Agency (“EPA”) has issued various regulations re- garding the introduction and disposal of refrigerants introduced into this unit. Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines.
PRODUCT DESIGN 4 SSZ14 models are available in 1 1/2 through 5 ton sizes and use R-410A refrigerant. They are designed for 208/230 volt single phase applications. The condenser air is pulled through the condenser coil by a direct drive propeller fan. This condenser air is then dis- charged out of the top of the cabinet.
HEA T PUMP SPECIFICA TIONS 5 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.
HEA T PUMP SPECIFICA TIONS 6 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/ circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.
HEA T PUMP SPECIFICA TIONS 7 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.
HEA T PUMP SPECIFICA TIONS 8 NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/ circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.
9 COOLING PERFORMANCE DA T A SSZ140181A* EXP AN DE D PE RFORM ANCE DA T A C OOL I N G OP E R AT ION M O DE L : S S Z 1 40181A* / CA*F 3131*6A* + TX V / M BR800** - 1 O ut door Am bi e nt Te m pe r a t.
10 COOLING PERFORMANCE DA T A SSZ140181A* EXP AN DE D PERF O RM ANCE DATA C OOL I N G OP E R A T I ON M O DE L : S S Z 1 40181A* / CA*F 3131*6A* + TX V / M BR800 **-1 O ut door Am bi e nt Te m pe r at.
11 COOLING PERFORMANCE DA T A SSZ140241A* EXPANDED PERF O RM ANCE DATA C OOL I N G OP E R ATIO N M O DE L : S S Z 14 0241A* / CA*F3 636*6A*+ T X V / M B R800**-1 O utdoor Am bient Te m pe rature 65 75.
12 COOLING PERFORMANCE DA T A SSZ140241A* EX PANDED P ERF ORM ANCE DAT A C OOLIN G OP E R ATI ON M ODEL: S S Z 140241A* / CA*F3636*6A*+ T X V / M BR800**-1 O utdoor Am bi e nt Tem pe r at ur e 65 75 8.
13 COOLING PERFORMANCE DA T A SSZ140301A* EXPA NDED PERFO RM ANC E DA T A C OOLI N G OP E R ATI ON M O D EL: S S Z 140301A* / CA*F 3642*6A*+T X V / M BR1600**- 1 O utdoo r Am bi e nt Te m pe ra ture 6.
14 COOLING PERFORMANCE DA T A SSZ140301A* EX PANDED PERF O RM A NCE DATA C O O L IN G O P E R A T IO N M O D EL: S S Z 140301A* / CA*F 3642*6A*+ TX V / M BR1600**-1 O utdoor Am bient Te m pe r ature 6.
15 COOLING PERFORMANCE DA T A SSZ140361A* EXPA N DED PER FORM AN CE D ATA M ODEL: S S Z 140361A* / CA* F 4860*6A*+ TX V / M BR1600* *-1 O utdoor Am bie nt Te m pe r atur e 65 75 85 95 105 115 E n t e r in g In d o o r We t B u lb T e m p e r at u r e ID B Air flo w 59 63 67 71 59 63 67 71 59 6 3 67 71 59 63 67 71 59 63 67 71 5 9 63 67 71 M Bh 33.
16 COOLING PERFORMANCE DA T A SSZ140361A* EX PANDED PE RF O RM ANCE DAT A C OOL I N G OP E R AT I ON M ODEL: S S Z 140361A* / CA* F 4860*6A*+ TX V / M BR1600* *-1 O utdoor Am bie nt Te m pe r atur e 6.
17 COOLING PERFORMANCE DA T A SSZ140421A* EXPAN DED PERFORMAN C E DATA M ODEL : S S Z140421A* / CA*F 4860*6 A*+ T X V / M BR 2000**-1 O utdoor Am bi e nt Te m pe rature 65 75 85 95 105 115 E nter ing I ndoo r We t B ulb Te m pe rature ID B A ir flo w 59 63 67 71 59 63 67 71 5 9 63 6 7 71 59 63 67 71 59 63 6 7 71 59 63 67 71 M Bh 39.
18 COOLING PERFORMANCE DA T A SSZ140421A* EXPA NDED PER F O RM AN CE DA TA C OOL I N G OP E R AT I ON M O DE L : S S Z140421A* / CA*F 4860*6 A*+ TX V / M BR2000* *- 1 O u tdoor Am bi e nt Te m pe ratu.
19 COOLING PERFORMANCE DA T A SSZ140481A* EXPA ND ED PER FOR M AN CE D ATA C OOL I N G OP E R A TIO N M O DEL: S S Z 14 0481A* / CA*F 4860*6A* + T X V / M BR2000* *-1 O utdoor Am bi e nt Te m pe ratur.
20 COOLING PERFORMANCE DA T A SSZ140481A* EXPA ND ED PER FO RM AN CE D ATA C OOLIN G OP E R AT I O N M O DEL: S S Z 14 0481A* / CA*F 4860*6A* + T X V / M BR2000* *-1 O u tdoor Am bi e nt Te m pe ratur.
21 COOLING PERFORMANCE DA T A SSZ140601A* EXP AND E D PERF O RM ANCE DAT A C OOL I N G OP E R ATION M O DE L: S S Z 140601 A* / CA*F4860*6 A*+ T X V / M BE2 000**- 1 O utd oor Am bi e nt Tem pe r a tu.
22 COOLING PERFORMANCE DA T A SSZ140601A* EXP AND E D PERF ORM ANCE DAT A C OOL IN G OP E R ATION M ODEL: S S Z 140601A* / CA*F4860*6A *+ TX V / M BE 2000**- 1 O utdoo r Am bi e nt Tem pe ra ture 65 7.
23 COOLING PERFORMANCE DA T A SSZ140361B* E XPA NDED PERF ORM A NCE DA TA CO O L ING O PE RAT I ON M OD E L : SS Z 140 361 B* / AR *F 374 316 B* Outdoor Am bi ent Tempera t u r e 65 75 85 95 105 1 15 .
24 COOLING PERFORMANCE DA T A SSZ140361B* EX PAN DE D P ER FO R MANC E D ATA CO OLI NG O P ERATION MOD EL : SSZ 14 0 361 B* / AR *F 374 316 B* O utdoor Am bi e nt Tempe r at u re 65 75 85 95 105 1 15 .
25 PERFORMANCE DA T A Outdoor Te m p. ° F . Tot a l Bt uh S e ns ible Bt uh La te n t Btu h Tot a l Wat t s 75° 36, 330 24, 713 11, 617 2, 662 80° 35, 898 24, 729 11, 169 2, 742 85° 35, 465 24, 73.
26 SPLIT SYSTEM HEA TING PERFORMANCE H i gh pre s s u r e i s meas u red at th e s uc ti on s erv i c e v al v e ( t he l a r ge r v a l v e). Low pre s s u re i s me as ure d at t he gau ge po r t c on nec t i on . C a l c ula tio ns ar e b as ed on n om i n al C FM a nd 70 ° F indo or dry bul b.
27 SPLIT SYSTEM HEA TING PERFORMANCE EXP ANDED PERFORMANCE DA T A H i gh pre s s u r e i s meas u red at th e s uc ti on s erv i c e v al v e ( t he l a r ge r v a l v e). Low pre s s u re i s me as ure d at t he gau ge po r t c on nec t i on . C a l c ula tio ns ar e b as ed on n om i n al C FM a nd 70 ° F indo or dry bul b.
28 SPLIT SYSTEM HEA TING PERFORMANCE H i gh pre s s u r e i s meas u red at th e s uc ti on s erv i c e v al v e ( t he l a r ge r v a l v e). Low pre s s u re i s me as ure d at t he gau ge po r t c on nec t i on . C a l c ula tio ns ar e b as ed on n om i n al C FM a nd 70 ° F indo or dry bul b.
29 SPLIT SYSTEM HEA TING PERFORMANCE EXP ANDED PERFORMANCE DA T A H i gh pre s s u r e i s meas u red at th e s uc ti on s erv i c e v al v e ( t he l a r ge r v a l v e). Low pre s s u re i s me as ure d at t he gau ge po r t c on nec t i on . C a l c ula tio ns ar e b as ed on n om i n al C FM a nd 70 ° F indo or dry bul b.
30 SPLIT SYSTEM HEA TING PERFORMANCE H i gh pre s s u r e i s meas u red at th e s uc ti on s erv i c e v al v e ( t he l a r ge r v a l v e). Low pre s s u re i s me as ure d at t he gau ge po r t c on nec t i on . C a l c ula tio ns ar e b as ed on n om i n al C FM a nd 70 ° F indo or dry bul b.
31 SPLIT SYSTEM HEA TING PERFORMANCE EXP ANDED PERFORMANCE DA T A H i gh pre s s u r e i s meas u red at th e s uc ti on s erv i c e v al v e ( t he l a r ge r v a l v e). Low pre s s u re i s me as ure d at t he gau ge po r t c on nec t i on . C a l c ula tio ns ar e b as ed on n om i n al C FM a nd 70 ° F indo or dry bul b.
32 SPLIT SYSTEM HEA TING PERFORMANCE H i gh pre s s u r e i s meas u red at th e s uc ti on s erv i c e v al v e ( t he l a r ge r v a l v e). Low pre s s u re i s me as ure d at t he gau ge po r t c on nec t i on . C a l c ula tio ns ar e b as ed on n om i n al C FM a nd 70 ° F indo or dry bul b.
33 SPLIT SYSTEM HEA TING PERFORMANCE EXP ANDED PERFORMANCE DA T A H i gh pre s s u r e i s meas u red at th e s uc ti on s erv i c e v al v e ( t he l a r ge r v a l v e). Low pre s s u re i s me as ure d at t he gau ge po r t c on nec t i on . C a l c ula tio ns ar e b as ed on n om i n al C FM a nd 70 ° F indo or dry bul b.
34 HEA TING SPECIFICA TIONS capacit y btuh c.o.p. 4.8 9.6 14.4 19.2 65 22.63 4.23 39.01 55.39 71.77 88.16 60 21.42 4.09 37.80 54.18 70.57 86.95 55 20.16 3.93 36.54 52.92 69.31 85.69 50 18.85 3.75 35.23 51.61 67.99 84.38 45 17.44 3.54 33.82 50.21 66.59 82.
35 HEA TING SPECIFICA TIONS capaci t y btuh c. o.p . 4. 8 9. 6 14. 4 19 . 2 65 51.5 4 4 .44 67. 92 84. 30 1 00. 68 117 .07 60 48.7 9 4 .28 65. 17 8 1.55 9 7. 94 114. 32 55 45.9 2 4 .11 62. 30 7 8.68 9 5. 07 111. 45 50 42.9 3 3 .92 59. 31 7 5.69 9 2. 07 108.
36 PERFORMANCE DA T A PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor air cubic feet per minute (CFM) as listed in the Perfor- mance Data Sheets: If conditions vary from this, results will change as follows: 1.
WIRING DIAGRAMS 37 HIGH VOL T AGE! DIS CONNECT ALL POWER BEFORE SERVICING OR INST A LLIN G THIS UNIT . MUL T IPLE POW ER SOURCES MA Y BE PRESENT . F AI LURE TO DO SO MA Y CAUSE PROP ERTY DAMAGE, PERSONAL I NJURY OR DEA TH . Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
WIRING DIAGRAMS 38 HIGH VOL T AGE! DIS CONNECT ALL POWER BEFORE SERVICING OR INST A LLIN G THIS UNIT . MUL T IPLE POW ER SOURCES MA Y BE PRESENT . F AI LURE TO DO SO MA Y CAUSE PROP ERTY DAMAGE, PERSONAL I NJURY OR DEA TH . USE N.E.C. CLASS 2 WI R E NOTES: 1) TO I NDO OR UNI T LO W VOLT A GE TE RM INAL BL OC K & INDO O R TH ERM OS T A T .
WIRING DIAGRAMS 39 HIGH VOL T AGE! DIS CONNECT ALL POWER BEFORE SERVICING OR INST A LLIN G THIS UNIT . MUL T IPLE POW ER SOURCES MA Y BE PRESENT . F AI LURE TO DO SO MA Y CAUSE PROP ERTY DAMAGE, PERSONAL I NJURY OR DEA TH . SSZ140[18,30,42-60]1AG , 241AK, 361AH SSZ140361B* US E N.
An important point after buying a device Goodman SSZ 14 SEER (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Goodman SSZ 14 SEER yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Goodman SSZ 14 SEER - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Goodman SSZ 14 SEER you will learn all the available features of the product, as well as information on its operation. The information that you get Goodman SSZ 14 SEER will certainly help you make a decision on the purchase.
If you already are a holder of Goodman SSZ 14 SEER, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Goodman SSZ 14 SEER.
However, one of the most important roles played by the user manual is to help in solving problems with Goodman SSZ 14 SEER. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Goodman SSZ 14 SEER along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center