Dehumidifier SER VICE MANUAL MODEL: DH3010B(DHA3012DL) DH4010B(DHA4012DL) DH5010B(DHA5012DL) CAUTION - BEFORE SER VICING THE UNIT , READ THE SAFETY PRECAUTIONS IN THIS MANUAL. - ONL Y FOR AUTHORIZED SERVICE. http://biz.LGservice.com http://www .LGservice.
—2— 1. PREF ACE 1.1 SAFETY PRECAUTIONS ........................................................................................................................... 3 1.2 FEATURES .....................................................................
—3— 1. PREF ACE This Service Manual provides various service information, containing the mechanical and electrical parts etc. This dehumidifier was manufactured and assembled under the strict quality control system. The refrigerant is charged at the factory.
— 4 — 1.4 SPECIFICA TIONS CAPACITY (Pint/Day) 30 40 50 POWER SUPPLY (Phase, V, Hz) 1 ø , 115V, 60Hz REFRIGERANT R134a R22 REFRIGERANT CHARGE, oz(g) 4.76(135) 5.11(145) 7.05(200) CONTROL, DEFROST THERMOSTAT HUMIDISTAT CONTROL RANGE : 20% ~ 80% RH NORMAL SETTING : 42 ± 5% RH COMPRESSOR MODEL NO.
1.6.1 HOW DOES THE DEHUMIDIFIER WORK? Moist, humid air is drawn over a cold refrigerated dehumidifying coil. Moisture in the air condenses on this coil and drains into a bucket (or through the bucket into a hose and drain).
1.6.5 HUMIDIST A T Humidistat controls constant relative humidity in the room automatically. When the relative humidity in the room increases to the selected level, the dehumidifier starts automatically. And the relative humidity drops to the selected level, the dehumidifier stops automatically.
— 7 — 2. CIRCUIT DIAGRAM • MODEL : DH3010B/DHA3012DL LAMP, NEON TERMINAL BLOCK WIRING DIAGRAM 3854A20015H CONTROL, DEFROST O.L.P. SWITCH, ROTARY C BR YL BR BR BR 6 4 1 1 HUMIDISTAT 2 BK BK M S 5 6 3 4 C COMP. BK WH OR(COM) RD(LO) BK(HI) OR RD(L) BK(HI) GR/YL BL N.
— 8 — • MODEL : DH4010B/DHA4012DL, DH5010B/DHA5012DL(DEFROST CONTROL TYPE) LAMP, NEON WIRING DIAGRAM 3854A20015G CONTROL, DEFROST O.L.P. SWITCH, ROTARY C BR YL BR BR BR 6 4 1 1 HUMIDISTAT 2 BK RD BK RD BK S R C COMP. BK WH OR OR C H RD(LO) BK(HI) RD BK GR/YL GR/YL BL N.
— 9 — • MODEL : DH4010B/DHA4012DL, DH5010B/DHA5012DL(THERMOST A T CONTROL TYPE) BK WH SWITCH, ROT ARY SWITCH, LAMP BK C H BR BK LAMP , NEON THERMOST A T O.L.P WIRING DIA GRAM 3854A20015M BL BK RD BK BR BR RD COMP R C S RD OR OR 4 6 1 GR/YL GR/YL M OTO R C N.
3.1 MECHANICAL P ARTS 3.1.1 BUCKET AND AIR FIL TER 1. Disconnect the power supply. 2. Turn the Humidity Control off. 3. Remove the bucket. (See Figure 5) 4. Flex the filter at the lower right corner and take it off. (See Figure 5) 3.1.2 FRONT GRILLE 1.
3.2 CONTROL P ARTS 3.2.1 ROT AR Y SWITCH, HUMIDISA T AND NEON LAMP 1. Unfasten screws located in the bottom side of control box (see Figure 9) and fasten capacitor clamp. (DH5010B/DH4010B) And then unfold two sides of control box. (See Figure 9) 2. Disconnect housing and all leads of rotary switch, humidistat and neon lamp.
3.2.7 F AN AND MOTOR 1. Turn the nut left and full out the Fan by hands carefully. 2. Remove 2 screws that fasten Heat Exchange. 3. Lift the H/E and open the H/E around 45 degree clockwise carefully. (See Figure 14) 4. Unfasten 3 screws that secure the Motor and earth wire.
— 13 — 3.3 REFRIGERA TING CYCLE 3.3.1 CONDENSER, EV APORA TOR AND CAPILLAR Y TUBE(HEA T EXCHANGE ASSEMBL Y) 1. Remove the insulation on the H/E assembly 2. Pierce the pinch-off tube to discharge the refrigerant, using a FREON TM recovery system. 3.
1. Remove the cabinet. (Refer to section 3.1.3) 2. Remove a screw or a nut which fastens the terminal cover 3. Disconnect the lead wire from the overload protector or P.T.C. assembly. 4. Remove the overload protector(O.L.P) or P.T.C. assembly. (See Figure 20) 3.
— 15 — 1. When replacing the refrigeration cycle, be sure to discharge the refrigerant system by using a refrigerant recovery system. 2. After discharging the unit completely, remove the desired component, and unbrace the pinch-off tubes. 3. Solder service valves into the pinch-off tube ports, leaving the valves open.
— 16 — Equipment needed: Vacuum pump, charging cylinder, manifold gauge, brazing equipment. pinch-off tool capable of making a vapor-proof seal, leak detector, tubing cutter, hand tools to remove components, service valve.
—17— Dehumidifier does not dr y the air as it should. The fuse is blo wn/circuit breaker is tripped. Make sure the dehumidifier's plug is pushed completely into the outlet. Dehumidifier does not star t. Ineff ective dehumidifying Noise Repair gas leak.
CONDITION 1. Dehumidifier does not start. (Both compressor and fan motor do not operate.) 2. Motor runs but compressor does not run. 3. Does not defrost control. 4. Insufficient dehumidification CAUSE No power Poor plug contact at outlet. Bucket is full.
— 19 — CONDITION 5. Noisy operating 6. Water drips 7. Compressor cycles on overload protector. (O.L.P.) CAUSE Fan Some material plunged and rattle. Tube hits frame. Fan blade hits frame Internal compressor noise. Loose set screws Worn bearings of Motor Assembly The bucket is not installed properly.
5. EXPLODED VIEW - INTRODUCTION • MODEL: DH3010B/DHA3012DL — 20 — 266011 269120 266140 266003 252160 149410 135312 264110 249950 W6640 152302 147910 550140 554030 552111 130900 130411 148380 354.
— 21 — • MODEL: DH4010B/DHA4012DL, DH5010B/DHA5012DL(DEFROST CONTROL TYPE) 269130 266003 252160 149410 135312 264110 W0CZZ 152302 147910 266011 567502 554160 550140 554030 552111 130900 130411 1.
— 22 — • MODEL: DH4010B/DHA4012DL, DH5010B/DHA5012DL(THERMOST A T CONTROL 149410 135312 152302 147910 266011 567502 554160 550140 554030 552111 130900 130411 148380 354211 346811 349600 549990 3.
— 23 — 6. REPLACEMENT P ARTS LIST • MODEL: DH3010B, DHA3012DL 130411 BASE ASSY, WELD(SINGLE) 3041AD2007B 130900 CABINET 3090A10001J 135312 GILLE ASSY, FRONT 3531A20012B 147910 BARRIER ASSY 4791A.
130411 BASE ASSY, WELD(SINGLE) 3041AD2007C 130900 CABINET 3090A10001J 135312 GILLE ASSY, FRONT 3531A20012B 147910 BARRIER ASSY 4791A10002A ALT)4791A10002B 148380 TANK, BUCKET 4838A20005A 149410 KNOB A.
— 25 — 130411 BASE ASSY, WELD(SINGLE) 3041AD2007C 130900 CABINET 3090A10001J 135312 GILLE ASSY, FRONT 3531A20012B 147910 BARRIER ASSY 4791A10002A ALT)4791A10002B 148380 TANK, BUCKET 4838A20005A 14.
• MEMO • — 26 —.
P/No : 3828A30039T March, 2001 Printed in Korea.
An important point after buying a device Goldstar DHA3012DL (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Goldstar DHA3012DL yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Goldstar DHA3012DL - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Goldstar DHA3012DL you will learn all the available features of the product, as well as information on its operation. The information that you get Goldstar DHA3012DL will certainly help you make a decision on the purchase.
If you already are a holder of Goldstar DHA3012DL, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Goldstar DHA3012DL.
However, one of the most important roles played by the user manual is to help in solving problems with Goldstar DHA3012DL. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Goldstar DHA3012DL along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center