Table of Contents 24 sections Standby Generators Liquid-Cooled Gas Engine · INCLUDES: · Standby Power Rating · FEATURES · … ShowHide
Page 1 of the Generac QT08046AVAX user manual — FEATURES
Page 1 · click to enlarge
Page 1
Generac QT08046AVAX — Standby Generators Liquid-Cooled Gas Engine diagram (page 1)
Fig. 1 · Standby Generators Liquid-Cooled Gas Engine

Standby Generators Liquid-Cooled Gas Engine

INCLUDES:

Standby Power Rating

Model QT070 (Aluminum - Bisque) - 70 kW 60 Hz Model QT080 (Aluminum - Bisque) - 80 kW 60 Hz Model QT100 (Aluminum - Bisque) - 100 kW 60 Hz Model QT130 (Aluminum - Bisque) - 130 kW 60 Hz Model QT150 (Aluminum - Bisque) - 150 kW 60 Hz

  • Two Line LCD Tri-Lingual Digital Nexus™ Controller
  • Isochronous Electronic Governor
  • Sound Attenuated Enclosure
Generac QT08046AVAX — INCLUDES: diagram (page 1)
Fig. 2
  • Closed Coolant Recovery System
  • Smart Battery Charger
  • UV/Ozone Resistant Hoses
  • ±1% Voltage Regulation
  • Natural Gas or LP Operation
  • 2 Year Limited Warranty
  • UL 2200 Listed

Meets EPA Emission Regulations 70, 100, 130 & 150 kW meet CA/MA emissions requirement with optional catalyst 80 kW not for sale in CA/MA

FEATURES

¡ INNOVATIVE DESIGN & PROTOTYPE TESTING are key components of GENERAC’S success in “IMPROVING POWER BY DESIGN.” But it doesn’t stop there. Total commitment to component testing, reliability testing, environmental testing, destruction and life testing, plus testing to applicable CSA, NEMA, EGSA, and other standards, allows you to choose GENERAC POWER SYSTEMS with the confidence that these systems will provide superior performance.

¡ SOLID-STATE, FREQUENCY COMPENSATED VOLTAGE REGULATION. This state-of-the-art power maximizing regulation system is standard on all Generac models. It provides optimized FAST RESPONSE to changing load conditions and MAXIMUM MOTOR STARTING CAPABILITY by electronically torque-matching the surge loads to the engine. Digital voltage regulation at ±1%.

¡ SINGLE SOURCE SERVICE RESPONSE from Generac’s extensive dealer network provides parts and service know-how for the entire unit, from the engine to the smallest electronic component.

¡ TEST CRITERIAPROTOTYPE TESTED NEMA MG1-22 EVALUATION SYSTEM TORSIONAL TESTED MOTOR STARTING ABILITY

¡ GENERAC TRANSFER SWITCHES. Long life and reliability are synonymous with GENERAC POWER SYSTEMS. One reason for this confidence is that the GENERAC product line includes its own transfer systems and controls for total system compatibility.

Generac QT08046AVAX — FEATURES diagram (page 1)
Fig. 3
Page 2 of the Generac QT08046AVAX user manual — FUEL SYSTEM
Page 2 · click to enlarge
Page 2
  • 70
  • 80
  • 100
  • 130
  • 150 kW application & engineering data

GENERATOR SPECIFICATIONS

ENGINE SPECIFICATIONS: 80 kW

TypeSynchronous Rotor Insulation ClassH Stator Insulation ClassH Telephone Interference Factor (TIF)<50 Alternator Output Leads 1-Phase4 wire Alternator Output Leads 3-Phase6 wire (70, 80 & 150 kW) or 12 wire (100 & 130 kW) BearingsSealed Ball CouplingFlexible Disc (70, 80 & 150 kW) or Gear Drive (100 & 130 kW) Excitation SystemBrushless
MakeGenerac ModelV-Type Cylinders8 Displacement (Liters)4.6 Bore (in/mm)3.55/90.2 Stroke (in/mm)3.54/89.9 Compression Ratio9.4:1 Intake Air SystemNaturally Aspirated Lifter TypeHydraulic

ENGINE SPECIFICATIONS: 70, 100, 130 & 150 kW

MakeGenerac ModelV-Type Cylinders10 Displacement (Liters)6.8 Bore (in/mm)3.55/90.2 Stroke (in/mm)4.17/105.9 Compression Ratio9:1 Intake Air SystemNaturally Aspirated Lifter TypeHydraulic

VOLTAGE REGULATION

TypeElectronic SensingSingle Phase Regulation± 1%

GOVERNOR SPECIFICATIONS

TypeElectronic Frequency RegulationIsochronous Steady State Regulation± 0.25%

ELECTRICAL SYSTEM

ENGINE LUBRICATION SYSTEM

Battery Charge Alternator12 Volt 30 Amp Static Battery Charger2 Amp Recommended BatteryGroup 24F, 525 CCA (70, 80 & 150 kW) or Group 27F, 700 CCA (100 & 130 kW) System Voltage12 Volts
Oil Pump TypeGear Oil Filter TypeFull flow spin-on cartridge Crankcase Capacity (quarts/liters)5/4.7 (70, 100, 130 & 150 kW) or 6/5.7 (80 kW)

ENGINE COOLING SYSTEM

TypeClosed Water PumpBelt driven Fan Speed (rpm)2300 - 70 kW 1600 - 80 kW 1670 - 100 kW 1950 - 130 kW 2200 - 150 kW Fan Diameter (in/mm)22/558.8 (70 kW) or 26/660.4 (80, 100, 130 & 150 kW) Fan ModePusher (70 kW) or Puller (80, 100, 130 & 150 kW)

GENERATOR FEATURES

Revolving field heavy duty generator Directly connected to the engine Operating temperature rise 120 °C above a 40 °C ambient Class H insulation is rated at 150 °C rise at 25 °C ambient All models fully prototyped tested

ENCLOSURE FEATURES

Aluminum weather protective enclosureEnsures protection against mother nature. Electrostatically applied textured epoxy paint for added durability. Enclosed critical grade mufflerQuiet, critical grade muffler is mounted inside the unit to prevent injuries. Small, compact, attractiveMakes for an easy, eye appealing installation. SAESound attenuated enclosure ensures quiet operation.

FUEL SYSTEM

Fuel TypeNatural gas, propane vapor CarburetorDown Draft Secondary Fuel RegulatorStandard Fuel Shut Off SolenoidStandard Operating Fuel Pressure11” - 14” HO 2

(All ratings in accordance with BS5514, ISO3046, ISO8528, SAE J1349 and DIN6271)

Page 3 of the Generac QT08046AVAX user manual — GENERATOR SPECIFICATIONS
Page 3 · click to enlarge
Page 3
  • 70
  • 80
  • 100
  • 130
  • 150 kW operating data
GENERATOR OUTPUT VOLTAGE/kW - 60Hz kW LPG Amp LPG kW Nat. Gas Amp Nat. Gas CB Size (Both) QT070120/240 V, 1Ø, 1.0 pf6729264267300 120/208 V, 3Ø, 0.8 pf7024367232300 120/240 V, 3Ø, 0.8 pf7021167201250 277/480 V, 3Ø, 0.8 pf7010567101125 QT080120/240 V, 1Ø, 1.0 pf7733377333400 120/208 V, 3Ø, 0.8 pf8027880278300 120/240 V, 3Ø, 0.8 pf8024180240300 277/480 V, 3Ø, 0.8 pf8012080120150 QT100120/240 V, 1Ø, 1.0 pf10041789371500 120/208 V, 3Ø, 0.8 pf10034794326400 120/240 V, 3Ø, 0.8 pf10030194283350 277/480 V, 3Ø, 0.8 pf10015094141175 QT130120/240 V, 1Ø, 1.0 pf130542117488600 120/208 V, 3Ø, 0.8 pf130451122423500 120/240 V, 3Ø, 0.8 pf130391122367450 277/480 V, 3Ø, 0.8 pf130195122183225 QT150120/240 V, 1Ø, 1.0 pf144625136567700 120/208 V, 3Ø, 0.8 pf150520142493600 120/240 V, 3Ø, 0.8 pf150451142427500 277/480 V, 3Ø, 0.8 pf150225142214250
SURGE CAPACITY IN AMPS Voltage Dip @ < .4 pf 15% 30% QT070120/240 V, 1Ø129356 120/208 V, 3Ø194471 120/240 V, 3Ø168408 277/480 V, 3Ø83201 QT080120/240 V, 1Ø174435 120/208 V, 3Ø186466 120/240 V, 3Ø161404 277/480 V, 3Ø70175 QT100120/240 V, 1Ø150413 120/208 V, 3Ø186452 120/240 V, 3Ø161392 277/480 V, 3Ø107261 QT130120/240 V, 1Ø236648 120/208 V, 3Ø364885 120/240 V, 3Ø315767 277/480 V, 3Ø161390 QT150120/240 V, 1Ø4861214 120/208 V, 3Ø5341334 120/240 V, 3Ø4631156 277/480 V, 3Ø250624
ENGINE FUEL CONSUMPTION Natural Gas Propane (ft³/hr) (m³/hr) (gal/hr) (l/hr) QT070Exercise cycle1103.11.24.6 25% of rated load2607.42.8510.8 50% of rated load50014.25.4620.8 75% of rated load69619.87.6229.1 100% of rated load10202911.1742.6 QT080Exercise cycle1313.71.455.5 25% of rated load3128.93.4513.1 50% of rated load60017.16.6425 75% of rated load83523.79.2534.9 100% of rated load115432.812.7848.2 QT100Exercise cycle1303.71.45.4 25% of rated load37110.54.115.5 50% of rated load71320.37.929.8 75% of rated load99128.21141.5 100% of rated load126035.813.952.6 QT130Exercise cycle1353.81.45.7 25% of rated load48213.75.320 50% of rated load92726.310.338.7 75% of rated load129236.714.354 100% of rated load178650.819.874.6 QT150Exercise cycle1554.41.76.5 25% of rated load55615.86.0923.2 50% of rated load107030.411.7244.7 75% of rated load149142.416.3362.3 100% of rated load206158.622.5786.1

For Btu content, multiply ft3/hr x 2520 (LP) or ft3/hr x 1000 (NG).

For megajoule content, multiple m³/hr x 93.89 (LP) or m³/hr x 37.26 (NG).

Refer to "Emissions Data Sheets" for maximum fuel flow for EPA and SCAQMD permitting purposes.

STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice.

Page 4 of the Generac QT08046AVAX user manual — CONTROLLER FEATURES
Page 4 · click to enlarge
Page 4
  • 70
  • 80
  • 100
  • 130
  • 150 kW operating data

ENGINE COOLING

70 kW 80 kW 100 kW 130 kW 150 kW

Air flow (inlet air including alternator and combustion air in ft³/min)5200/147.25300/150.15500/155.76450/182.67800/220.9 System coolant capacity (gal/liters)4.5/174/15.14.5/174.5/174.5/17 Heat rejection to coolant (BTU/hr)287,000/302.8316,000/333.4342,000/360.8496,000/523.3568,000/599.3 Maximum operation air temperature on radiator (°C/°F)60/150 Maximum ambient temperature (°C/°F)50/140
Generac QT08046AVAX — ENGINE COOLING diagram (page 4)
Fig. 4

COMBUSTION REQUIREMENTS

Flow at rated power (cfm/cmm) 205/5.8 250/7.1 262/7.4 336/9.5 410/11.6

SOUND EMISSIONS

Sound output in dB(A) at 23 ft (7 m) with generator in exercise mode*6764616566 Sound output in dB(A) at 23 ft (7 m) with generator operating at normal load*7274727579

*Sound levels are taken from the front of the generator. Sound levels taken from other sides of the generator may be higher depending on installation parameters.

EXHAUST

Exhaust flow at rated output (cfm/cmm)557/15.8720/20.4888/25.11119/31.71535/43.5 Exhaust temperature at muffler outlet (°C/°F)477/890449/840516/960521/970593/1100

ENGINE PARAMETERS

Rated Synchronous rpm 1800 3600 2300 2970 3600

POWER ADJUSTMENT FOR AMBIENT CONDITIONS

Temperature Deration 3% for every 10 °C above 25 °C or 1.65% for every 10 °F above 77 °F Altitude Deration (70,100,130 & 150) 1% for every 100 m above 183 m or 3% for every 1000 ft above 600 ft Altitude Deration (80 kW) 1% for every 100 m above 915 m or 3% for every 1000 ft above 3000 ft

CONTROLLER FEATURES

2-Line Plain Text LCD Display Simple user interface for ease of operation. Mode Switch: Auto Automatic Start on Utility failure. 7 day exerciser

Off Stops unit. Power is removed. Control and charger still operate. Manual Start with starter control, unit stays on. If utility fails, transfer to load takes place. Programmable start delay between 10-30 seconds Standard Engine Start Sequence Cyclic cranking: 16 sec on, 7 rest (90 sec maximum duration) Engine Warm-up 5 sec Engine Cool-Down 1 min Starter Lock-out Starter cannot re-engage until 5 sec after engine has stopped. Smart Battery Charger Standard Automatic Voltage Regulation with Over and Under Voltage Protection Standard Automatic Low Oil Pressure Shutdown Standard Overspeed Shutdown Standard, 72 Hz High Temperature Shutdown Standard Overcrank Protection Standard Safety Fused Standard Failure to Transfer Protection Standard Low Battery Protection Standard 50 Event Run Log Standard Future Set Capable Exerciser Standard Incorrect Wiring Protection Standard Internal Fault Protection Standard Common External Fault Capability Standard Governor Failure Protection Standard

Page 5 of the Generac QT08046AVAX user manual — ENGINE COOLING
Page 5 · click to enlarge
Page 5
  • 70
  • 80
  • 100
  • 130
  • 150 kW available accessories
Model #ProductDescription 005632-0 - 70, 80 & 150 kW 005633-0 - 100 & 130 kWCold Weather KitIf the temperature regularly falls below 32 °F (0 °C), install a cold weather kit to maintain optimal battery temperature. Kit consists of battery warmer with thermostat built into the wrap. 005620-0 - 70, 100 & 130 kW 005619-0 - 80 kW 005667-0 - 150 kWExtreme Cold Weather KitRecommended where the temperature regularly falls below 32 °F (0 °C) for extended periods of time. For liquid cooled units only. 005651-0Base Plug KitAdd base plugs to the base of the generator to keep out debris. 005703-0Paint KitIf the generator enclosure is scratched or damaged, it is important to touch-up the paint to protect from future corrosion. The paint kit includes the necessary paint to properly maintain or touch-up a generator enclosure. 005660-0 - 70, 100, 130 & 150 kW 005985-0 - 80 kWScheduled Maintenance KitThe Liquid-Cooled Scheduled Maintenance Kits offer all the hardware necessary to perform complete maintenance on Generac liquid-cooled generators. 005928-0Wireless RemoteCompletely wireless and battery powered, Generac's wireless remote monitor provides you with instant status information without ever leaving the house. 005951-0Advanced Wireless RemoteRemotely control generator functions with the advanced model’s LCD display. In addition to remote testing of the generator, set the exercise cycle and maintenance interval reminders. 006199-0PMM Starter KitThe PMM Starter Kit consists of a 24 VAC, field installed transformer that enables the use of the 24 VAC Power Management Modules (PMMs) and one PMM. The standard controller (without starter kit) can control two HVAC loads with no additional hardware. Not compatible with pre-wired switches. 006186-0Power Management Module (50 Amps)Power Management Modules are used in conjunction with the Smart Switch to increase its power management capabilities. It gives the Smart Switch additional power management flexibility not found in any other transfer switch. Not compatible with pre-wired switches. Note: PMM Starter Kit required. 006463-0Mobile Link™Generac's Mobile Link allows you to check the status of your generator from anywhere that you have access to an Internet connection from a PC or with any smart device. You will even be notified when a change in the generator’s status occurs via e-mail or text message. Note: Harness Adapter Kit required. 006478-0Harness Adapter KitThe Harness Adapter Kit is required to make liquid-cooled units compatible with Mobile Link™.
Page 6 of the Generac QT08046AVAX user manual — ENGINE COOLING
Page 6 · click to enlarge
Page 6
  • 70
  • 80
  • 100
  • 130
  • 150 kW interconnections
Generac QT08046AVAX — ENGINE COOLING diagram (page 6)
Fig. 5
Page 7 of the Generac QT08046AVAX user manual — 70 kW installation layout
Page 7 · click to enlarge
Page 7

70 kW installation layout

Generac QT08046AVAX — 70 kW installation layout diagram (page 7)
Fig. 6 · 70 kW installation layout
Page 8 of the Generac QT08046AVAX user manual — 80 kW installation layout
Page 8 · click to enlarge
Page 8

80 kW installation layout

Generac QT08046AVAX — 80 kW installation layout diagram (page 8)
Fig. 7 · 80 kW installation layout
Page 9 of the Generac QT08046AVAX user manual — 80 kW installation layout
Page 9 · click to enlarge
Page 9
  • 100
  • 130
  • 150 kW installation layout
Generac QT08046AVAX — 80 kW installation layout diagram (page 9)
Fig. 8 · 80 kW installation layout
  • Generac Power Systems, Inc.
  • S45 W29290 HWY. 59, Waukesha, WI 53189
  • <a href="http://generac.com" rel="nofollow noopener" target="_blank">generac.com</a>

©2013 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0199370SBY-B Printed in U.S.A. 07/30/13

Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the Generac QT08046AVAX

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Generac QT08046AVAX

Be the first to ask — other owners or our team will answer.

Original document

Generac QT08046AVAX manual PDF

9 pages·2.1 MB·Portable Generator·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…