operation be copied and posted in potential hazard areas. Safety should be stressed to all operators, potential operators, and service and repair technicians for this equipment.
contains chemicals known to the state
of California to cause cancer, birth defects or other reproductive harm.
This product contains or emits chemicals known to the state of California to cause cancer, birth defects or other reproductive harm.
Study these SAFETY RULES carefully before install- ing, operating or servicing this equipment. Become familiar with this Owner’s Manual and with the unit. The generator can operate safely, efficiently and reli- ably only if it is properly installed, operated and maintained. Many accidents are caused by failing to follow simple and fundamental rules or precautions.
The manufacturer cannot anticipate every possible circumstance that might involve a hazard. The warn- ings in this manual, and on tags and decals affixed to the unit are, therefore, not all inclusive. If a pro- cedure, work method or operating technique is used that the manufacturer does not specifically recom- mend, ensure that it is safe for others. Also make sure the procedure, work method or operating tech- nique utilized does not render the generator unsafe.
operating this equipment imprudently, neglect- ing its maintenance or being careless can cause possible injury or death. Permit only responsible and capable persons to install, operate or main- tain this equipment. Potentially lethal voltages are generated by
these machines. Ensure all steps are taken to render the machine safe before attempting to work on the generator. Parts of the generator are rotating and/or hot
during operation. Exercise care near running generators.
Safety 001 Rev. 0 08/05

FIRE HAZARDS • Keep a fire extinguisher near the generator at all times. Do NOT use any carbon tetra-chloride type extinguisher. Its fumes are toxic, and the liquid can deteriorate wiring insulation. Keep the extin- guisher properly charged and be familiar with its use. If there are any questions pertaining to fire extinguishers, consult the local fire department.
Safety 001 Rev. 0 08/05

INTRODUCTION Thank you for purchasing this model of the standby generator set product line.
This symbol points out potential fire hazard.
Every effort was expended to make sure that the information and instructions in this manual were both accurate and current at the time the manual was written. However, the manufacturer reserves the right to change, alter or otherwise improve this product(s) at any time without prior notice.
hazard. The operator is responsible for proper and safe use of the equipment. The manufacturer strongly recom- mends that the operator read this Owner's Manual and thoroughly understand all instructions before using this equipment. The manufacturer also strong- ly recommends instructing other users to properly start and operate the unit. This prepares them if they need to operate the equipment in an emergency.
READ THIS MANUAL THOROUGHLY
If any portion of this manual is not understood, con- tact the nearest Authorized Service Dealer for start- ing, operating and servicing procedures.
OPERATION AND MAINTENANCE
It is the operator's responsibility to perform all safety checks, to make sure that all maintenance for safe operation is performed promptly, and to have the equipment checked periodically by an Authorized Service Dealer. Normal maintenance service and replacement of parts are the responsibility of the owner/operator and, as such, are not considered defects in materials or workmanship within the terms of the warranty. Individual operating habits and usage contribute to the need for maintenance service.
Throughout this publication, and on tags and decals affixed to the generator, DANGER, WARNING, CAUTION and NOTE blocks are used to alert person- nel to special instructions about a particular service or operation that may be hazardous if performed incorrectly or carelessly. Observe them carefully. Their definitions are as follows:
Proper maintenance and care of the generator ensure a minimum number of problems and keep operating expenses at a minimum. See an Authorized Service Dealer for service aids and accessories.
strictly complied with, will result in personal injury or property damage.
Operating instructions presented in this manual assume that the standby electric system has been installed by an Authorized Service Dealer or other competent, qualified contractor. Installation of this equipment is not a “do-it-yourself” project.
strictly complied with, may result in personal injury or property damage.
HOW TO OBTAIN SERVICE
strictly complied with, could result in damage to equipment and/or property.
When the generator requires servicing or repairs, simply contact an Authorized Service Dealer for assistance. Service technicians are factory-trained and are capable of handling all service needs.
After this heading, read explanatory statements
that require special emphasis.
When contacting an Authorized Service Dealer or the factory about parts and service, always supply the complete model number of the unit as given on the front cover of this manual or on the DATA LABEL affixed to the unit.
These safety warnings cannot eliminate the hazards that they indicate. Common sense and strict compli- ance with the special instructions while performing the service are essential to preventing accidents.
Four commonly used safety symbols accompany the DANGER, WARNING and CAUTION blocks. The type of information each indicates is as follows: This symbol points out important safety infor-
To locate the nearest AUTHORIZED SERVICE DEALER, please call this number:
mation that, if not followed, could endanger personal safety and/or property of others. This symbol points out potential explosion
www.generac.com
hazard.
Safety 001 Rev. 0 08/05

IDENTIFICATION RECORD
Identification Code Use this code to obtain important information about the generator. For example, if the code is:
DATA LABEL
Every generator set has a DATA LABEL that contains important information pertinent to the generator. The data label, which can be found attached to the gen- erator’s lower connection box, lists the unit’s serial number and its rated voltage, amps, wattage capacity, phase, frequency, rpm, power factor, etc.
M Q T 1 0 0 5 4 A N S N A
M — Designates generators capable of paralleling.
MADE IN USA
MODEL
SERIAL
RATED KW
RATED KVA
PHASE
G = 120/208, Three-phase; K = 277/480, Three-phase; J = 120/240, Three-phase; L = 346/600, Three-phase N — Fuel: N = Natural Gas; V = Vapor Propane S — Enclosure Material: A = Aluminum; S
RATED AMPS
POWER FACTOR
HERTZ
ALT RPM
ENGINE RPM
PRODUCTION DATE
ALTERNATOR SUBTRANSIENT REACTANCE
ALTERNATOR TRANSIENT REACTANCE
= Steel (Corrosion Resistant Aluminum Enclosure Material, Steel is Standard) N — Emission Equipment: N = No Equipment;
ROTOR STATOR WINDING INSULATION AT 25°C AMBIENT
GENERAC POWER SYSTEMS, INC.
Y = Catalytic Converter and Air/Fuel Ratio Controller A — Industrial Dealer Product
Voltage Codes The identification code letter following the unit’s engine size is the generator’s “voltage code.”
Groups and Assembly Numbers The manual drawing listing lists the groups and cor- responding assembly numbers for each unit. The assembly numbers refer to exploded view drawing numbers that are applicable to the specific generator model. These drawings are located in the back half of this manual.
Generator Model and Serial Number This number is the key to numerous engineering and manufacturing details pertaining to your unit. Always supply this number when requesting service, order- ing parts or seeking information.
Identy001 Rev. C 04/06

EQUIPMENT DESCRIPTION This equipment is a revolving field, alternating cur- rent generator set. It is powered by a gaseous fueled engine operating at 1800 rpm for 4-pole direct drive units, 3600 rpm for 2-pole direct drive units and 2300 - 3000 rpm for quiet drive gear units. See the Specifications section for exact numbers. The unit comes complete with a sound attenuated enclosure, internally mounted muffler, control console, main- line circuit breaker, battery charger, and protective alarms as explained in the following paragraph.
COOLANT RECOMMENDATIONS Use a mixture of half low silicate ethylene glycol base anti-freeze and deionized water. Cooling system capacity is listed in the specifications. Use only deion- ized water and only low silicate anti-freeze. If desired, add a high quality rust inhibitor to the recommended coolant mixture. When adding coolant, always add the recommended 50-50 mixture.
All AC connections, including the power leads from the alternator, 120 volt battery charger input and control connections to the transfer switch are avail- able in the main connection box.
with ethylene glycol base anti-freeze or chro- mium hydroxide (“green slime”) forms and will cause overheating. Engines that have been oper- ated with a chromate base rust inhibitor must be chemically cleaned before adding ethylene glycol base anti-freeze. Using any high silicate anti-freeze boosters or additives will also cause overheating. The manufacturer also recommends that any soluble oil inhibitor is NOT used for this equipment.
the engine is hot or serious burns from boiling liquid or steam could result. Ethylene glycol base antifreeze is poisonous.
ENGINE OIL RECOMMENDATIONS The unit has been filled with 15W-40 engine oil at the factory. Use a high-quality detergent oil classified “For Service CC, SD, SE, SF.” Detergent oils keep the engine cleaner and reduce carbon deposits. Use oil having the following SAE viscosity rating, based on the ambient temperature range anticipated before the next oil change:
Do not use mouth to siphon coolant from the radiator, recovery bottle or any container. Wash hands thoroughly after handling. Never store used antifreeze in an open container because animals are attracted to the smell and taste of antifreeze even though it is poisonous to them.
it has been properly serviced with the recom- mended oil may result in an engine failure.
For temperatures below 32° F, it is strongly recom- mended to use the optional Cold Weather Start Kit (part number listed in the Specification Section). The oil grade for temperatures below 32° F is 5W- 30 synthetic oil.
Equip001 Rev. 0 08/05

ENGINE PROTECTIVE DEVICES The standby generator may be required to operate for long periods of time without an operator on hand to monitor such engine conditions as coolant tempera- ture, oil pressure or rpm. For that reason, the engine has several devices designed to protect it against potentially damaging conditions by automatically shutting down the unit when the oil pressure is too low, the coolant temperature is too high, the coolant level is too low, or the engine is running too fast.
OIL PRESSURE SENSING
An analog Oil Pressure Sender (OPS) is used for monitoring the engine oil pressure. This sender allows the control panel to measure and display the Engine oil pressure.
The OPS is a resistive device, whose resistance changes based on engine oil pressure. The resistance of the sender results in a voltage being developed across the sender. As the oil pressure increases, the resistance will decrease, causing the voltage to decrease. This changing voltage is converted to 4- 20mA signal by a signal conditioner module. The corresponding 4-20mA signal is read by the control panel and displayed as the oil pressure.
Engine protective switches and sensors are men- tioned here for the reader's convenience. Also refer to the applicable control panel manual for addi- tional automatic engine shutdown information.
The control panel will monitor and display oil pres- sure anytime the DC input to the control panel is present.
COOLANT TEMPERATURE SENSING
An analog Water Temperature Sender (WTS) is locat- ed in the engine's cooling system. This sender is con- nected to the panel and allows the panel to monitor and display the temperature of the coolant system.
Should the oil pressure drop below the 8 psi range, the engine shutdown is initiated. The unit should not be restarted until oil is added. Turn the AUTO/OFF/ MANUAL switch to the OFF position, then back to AUTO to restart.
The WTS is a resistive device whose resistance chang- es based on coolant temperature. The resistance of the sender results in a voltage being developed across the sender. As the Coolant temperature increases, the resistance will decrease, causing the voltage to decrease. This changing voltage is converted to 4- 20mA signal by a signal conditioner module. The corresponding 4-20mA signal is read by the control panel and displayed as the coolant temperature.
OVERCRANK SHUTDOWN
When the control panel receives a start signal, it ini- tiates the programmed starting sequence. The start sequence consists of the number of crank attempts, the length of each crank attempt, and the rest time between each crank attempt. If the engine has not started by the end of the final crank attempt, an Overcrank alarm is generated, the control panel will sound the alarm and display the message "Failed to start".
The control panel will monitor and display the cool- ant temperature anytime the DC input to the control panel is present.
If the temperature exceeds approximately 140° C (284° F), the engine shutdown will be initiated. The generator will automatically restart and the display will reset once the temperature has returned to an operating level.
OVERSPEED SHUTDOWN
A speed circuit controls engine cranking, start-up, operation and shutdown. Engine speed signals are delivered to the circuit board whenever the unit is running. Should the engine over speed above a safe, preset value, the circuit board initiates an automatic engine shutdown. Contact the nearest Authorized Dealer if this failure occurs.
LOW COOLANT LEVEL
A Low Coolant Level (LCL) sensor is placed in the generators coolant system. This sensor allows the panel to detect a Low Coolant Level condition.
RPM SENSOR LOSS SHUTDOWN
The LCL is a resistive device whose resistance changes rapidly based on the presence or absence of coolant.
If the speed signal to the control panel is lost, engine shutdown will occur.
The resistance of the LCL results in a voltage being developed across the LCL. This voltage changes as the resistance changes. This changing voltage is con- verted to 4-20mA signal by a signal conditioner mod- ule. The corresponding 4-20mA signal is read by the control panel and displayed as the low coolant level.
This fuse is located inside of the control panel. It protects the panel wiring and components from damaging overload. Always remove this fuse before commencing work on the generator. The unit will not start or crank if the fuse is blown. Replace the fuse with one of the same size, type, and rating. (See the exploded views and parts lists at the end of this manual for replacement part number.)
If the level of the engine coolant drops below the level of the low coolant level sensor, the engine shutdown will be initiated.
EngProt002 Rev. B 10/05

FUEL SYSTEM
PROPANE VAPOR WITHDRAWAL FUEL SYSTEM
This type of system utilizes the vapors formed above the liquid fuel in the supply tank. Approximately 10 to 20 percent of the tank capacity is needed for fuel expansion from the liquid to the vapor state. The vapor withdrawal system is generally best suited for smaller engines that require less fuel. The installer should be aware of the following:
FUEL REQUIREMENTS
The standby generator may be equipped with one of the following fuel systems:
Recommended fuels should have a Btu content of at least 1,000 Btu's per cubic foot for natural gas; or at least 2,520 Btu's per cubic foot for LP gas. Ask the fuel supplier for the Btu content of the fuel.
Required fuel pressure for natural gas is 11 inches to 14 inches water column (0.4 to 0.5 psi); and for liquid propane, 11 inches to 14 inches of water column (0.4 to 0.5 psi).
LP FUEL SYSTEM
LP is supplied as a liquid in pressure tanks. It is usually made up of propane, butane, or a mixture of the two gases. Propane tends to vaporize readily even at temperatures as low as -20° F (-29° C). However, butane reverts to its liquid state when temperatures drop below 32° F (0° C).
LP in a liquid withdrawal system must be converted to its gaseous state before it is introduced into the engine carburetor. A vaporizer-converter is generally used to accomplish this. In such a converter, heated engine coolant is ported through the converter to provide the necessary heat for conversion of the fuel from a liquid to a gaseous state.
NATURAL GAS FUEL SYSTEM
Natural gas is supplied in its vapor state. In most cases, the gas distribution company provides piping from the main gas distribution line to the standby generator site. The following information applies to natural gas fuel systems.
FuelSys002 Rev. A 05/06

SPECIFICATIONS
Engine Lubrication System Type of Oil Pump Gear Oil Filter Full Flow, Cartridge Crankcase Oil Capacity 5 U.S. qts.
GENERATOR Type Synchronous Rotor Insulation Class H Stator Insulation Class H Total Harmonic Distortion < 3.5% Telephone Interference Factor (TIF) < 50 Alternator Output Leads 3-phase 6-wire Bearings Sealed Ball Coupling Flexible Disc Load Capacity (Standby Rating) 100kW* * NOTE: Generator rating and performance in accordance with ISO8528-5, BS5514, SAE J1349, ISO3046 and DIN 6271 Standards. KW rating is based on LPG fuel and may derate with natural gas. Excitation System Brushless Generator Output Voltage/kW - 60 Hz kW Amp CB Size 120/240V, 1-phase, 1.0 pf 100 417 500 120/208V, 3-phase, 0.8 pf 100 347 400 277/480V, 3-phase, 0.8 pf 100 150 200 Generator Locked Rotor KVA Available @ Voltage Dip of 35% Single-phase or 208 3-phase 190 KVA 480V, 3-phase 225 KVA
COOLING SYSTEM
Type Closed Water Pump Belt Driven Fan Speed 1700 Fan Diameter 26 inches Fan Mode Puller Air Flow (inlet air including alternator and combustion air) 4800 ft3/min. Coolant Capacity (4.0 U.S. gal.) Heat Rejection to Coolant 376,000 Btu/h Maximum Operating Air Temp. on Radiator 60° C (150° F) Maximum Ambient Temperature 50° C (140° F)
FUEL SYSTEM Type of Fuel Natural Gas Carburetor Down Draft Secondary Fuel Regulator Standard Fuel Shut-off Solenoid Standard Operating Fuel Pressure 11 in. - 14 in. Water Column
ENGINE Make Generac Model V-type Cylinders and Arrangement 8 Displacement 5.4 Liter Bore 3.55 in. Stroke 4.17 in. Compression Ratio 9-to-1 Air Intake System Naturally Aspirated Valve Seats Hardened Lifter Type Hydraulic
Fuel Consumption - ft3/hr (Natural Gas/LPV) Exercise 25% 50% 75% 100% Cycle Load 140/56 371/149 713/287 994/400 1374/553
* Engine is not field convertible between natural gas and propane. Jet size and ignition timing are factory set for the specific fuel.
ELECTRICAL SYSTEM Battery Charge Alternator 12V, 30 Amp Static Battery Charger 12V, 2 Amp Recommended Battery 24F 525CCA System Voltage 12 Volts
Engine Parameters Rated Synchronous RPM 60 Hz, 3600 HP at rated kW 60 Hz, 175
Voltage Regulator Type Full Digital Sensing 3-phase Regulation ± 1/4% Features Built into H-100 Control Panel
Exhaust System Exhaust Flow at Rated Output 60 Hz 953 cfm Exhaust Temperature at Rated Output 1000° F
Combustion Air Requirements (Natural Gas) Flow at rated power, 60 Hz 325 cfm
Power Adjustment for Ambient Conditions Temperature Deration 3% for every 10° C above °C 25 1.65% for every 10° above °F 77 Altitude Deration 1% for every 100 m above m 183 3% for every 1000 ft. above ft 600
Governor Type Electronic Frequency Regulation Isochronous Steady State Regulation ± 1/2% Adjustments: Speed Selectable
GenSpec007 Rev. C 11/05



For cold climates, optional cold weather kit (part num- ber 0F6148A) is recommended. The kit includes:

5.4L & 6.8L IGNITION DESCRIPTION This single-fire Ignition is intended to operate with a 10-cylinder, 6.8L engine and an 8-cylinder, 5.4L engine.
The ignition cover does not need to be removed to see the LED.
The 6.8L engine uses a 40-1 crank sensor, a mag- pickup CAM sensor and individual coil-on-plug coils for each spark-plug.
IGNITION SHUTDOWN ON LOSS OF CRANK OR CAM SIGNALS
The ignition will stop firing the coils immediately fol- lowing the loss of the crank signal. The ignition will stop firing the coils after approx. 3 seconds following the loss of the cam signal.
The 5.4L engine uses a 36-1 crank sensor, a mag- pick-up CAM sensor and individual coil-on-plug coils for each spark-plug.
With a single-fire ignition, each high-voltage coil out- put is connected to one spark plug resulting in that spark plug being fired only during the compression cycle.
DIAGNOSTIC BLINK PATTERNS (RED LED LOCATED ON THE IGNITION CONTROL BOARD)
During normal ignition operation the RED LED flashes at a 0.5 sec ON and a 0.5 sec OFF rate. This is considered one (1) blink.
RPM NG/LP Engine Timing (BTDC) 1800 rpm 22 degrees 3600 rpm 24 degrees Engine Timing versus Engine Speed for the 5.4L engine is:
RPM NG/LP Engine Timing (BTDC) 1800 rpm 26 degrees 3600 rpm 26 degrees
IGNITION POWER-UP INPUT ("56 LINE INPUT")
When battery voltage is applied to this input the igni- tion will power-up. For the ignition to power itself down, battery voltage must be removed from this input.
The ignition cover does not need to be removed to see the LED.
IGNITION ENABLE ("14 LINE INPUT")
This input must be connected to the +12V battery for the ignition to turn-on the coils. If this input is con- nected to battery ground the ignition will stop firing the coils and will power down within approximately 2 seconds. In the event that an ignition fault has occurred, however, the ignition will wait 60 seconds before powering down. This allows time to view the diagnostic LED located on the ignition board.
GenSpec007 Rev. C 11/05

GENERATOR AC LEAD CONNECTIONS See “Voltage Codes”. This generator may be rated at any one of three voltages, either single-phase or three-phase. The electrical wires in the unit’s AC con- nection (lower) panel should be installed according to the number of leads and the voltage/phase required for the application. If there are any questions regard- ing lead connection, refer to the wiring diagrams at the back of this manual.
3-PHASE ALTERNATORS
The generator is designed to supply 3-phase electri- cal loads. Electric power is produced in the alterna- tor power windings. These windings were connected at the factory to the main circuit breaker with a “Y” configuration as shown in Figures 7.2 and 7.3.
Voltage codes apply to the type of stator assembly installed on a particular generator.
The rated voltage between circuit breaker terminals E1-E2, E1-E3 and E2-E3 is either 480V or 208V depending on the model.
FOUR-LEAD, SINGLE-PHASE STATOR
Four-lead generators (see Figure 7.1) are designed to supply electrical loads with voltage code “A” (240V, 1-phase, 60 Hz). Electrical power is produced in the stator power windings. These windings were con- nected at the factory to the main circuit breaker as shown in Figure 7.1.
The rated voltage between each circuit breaker termi- nal and the neutral point 00 is either 277V or 120V depending on the model.
The rated voltage between each circuit breaker ter- minal is 240V. The rated voltage between each circuit breaker terminal and the neutral point 00 is 120V.
Figure 7.1 — Four-lead, Single-phase Stator
INTERNAL CONNECTIONS
L-L S4
S6
NEUTRAL
S5
E3 S3
E2 S2
L-N
Figure 7.3 — Stator Power Winding Connections - 3-phase, 120/208V (6 Lead)
E1
S1 S1
S4 S4
00 (NEUTRAL)
S6
S5
S6 S3
S5 S2
E3 E2
S3
S2
L-N
ACConn001 Rev. 0 08/05

INSTALLATION Refer to the separate “Installation Guide QT Product Line” supplied with the unit.
PRIOR TO INITIAL START-UP
PREPARATION BEFORE START-UP The instructions in this section assume that the standby generator has been properly installed, ser- viced, tested, adjusted and otherwise prepared for use by a competent, qualified installation contractor. Be sure to read the “Safety Rules”, as well as all other safety information in this manual, before attempting to operate this (and related) equipment.
be properly prepared for use. Any attempt to crank or start the engine before it has been properly serviced with the recommended types and quantities of engine fluids (oil, coolant, fuel, etc.) may result in an engine failure.
ENGINE COOLANT
Have the engine cooling system properly filled with the recommended coolant mixture. Check the system for leaks and other problems. See “Specifications” and “Coolant” sections.
Before starting the generator for the first time, the installer must complete the following procedures. For follow-up maintenance information and/or service intervals, please refer to the “Maintenance” section and the “Service Schedule”.
BELT TENSION
TRANSFER SWITCH
Check-the engine-fan belt tension and condition prior to placing the unit into service and at recommended intervals. Belt tension is correct when a force of approximately 22 pounds (10 kg), applied midway between pulleys, deflects the belt about 3/8- to 5/8- inch (10 to 16 mm).
If this generator is used to supply power to any elec- trical system normally powered by an electric utility, the National Electrical Code requires that a transfer switch be installed. The transfer switch prevents elec- trical backfeed between two different electrical sys- tems. (For additional information, see the applicable transfer switch manual for this unit.) The transfer switch, as well as the generator and other standby components, must be properly located and mounted in strict compliance with applicable codes, standards and regulations.
ELECTRICAL SYSTEM
Make sure the generator is properly connected to an approved earth ground.
Make sure the generator battery is fully charged, properly installed and interconnected, and ready for use.
FUEL SYSTEM
Check to ensure that there are no loose electrical con- nections. Restrain any loose wires to keep them clear of any moving generator set components.
Make sure the fuel supply system to the genera- tor (a) delivers the correct fuel at the correct pres- sure and (b) is properly purged and leak tested according to code. No fuel leakage is permitted. See “Specifications” for more information.
INITIAL INSPECTION FOR QT GENSET STARTUP Inspect for the following.
GENERATOR SET LUBRICATION
Check the engine crankcase oil level before operating and add oil to the proper level – the dipstick “FULL” mark. Never operate the engine with the oil level below the dipstick “ADD” mark. See “Specifications” and “Engine Oil Recommendations”.
This engine is shipped from the manufacturer with “break-in” oil. This oil should be changed after 30 hours of operation.
Check the oil level in the generator gearbox (if so equipped) prior to initial use and at the intervals indicated by the “Service Schedule.” The recom- mended oil is SAE 90 gear lubricant.
Also, if the engine is equipped with a mechanical gov- ernor, make sure the governor is properly lubricated with clean engine oil.
Install001 Rev. C 05/06

START-UP CHECKLIST
PREPARATION FOR START-UP
Make certain all 3-phase loads are functioning correctly (correct phase rotation). • Reconnect Utility power Transfer switch will transfer back to Utility and
START-UP INSPECTION
When a start-up is performed by an Authorized Service Dealer, a standard three-part form titled “Start-up Inspection for Standby Power Systems” (part no. 067377), should be completed by the instal- lation technician or engineer. See page 1-3 for infor- mation on locating the nearest Authorized Service Dealer. The installer should complete the form and disseminate copies as follows:
Install001 Rev. C 05/06

GENERATOR CONTROL AND OPERATION Refer to the appropriate control panel operator’s manual for this unit.
OPERATING UNIT WITH MANUAL TRANSFER SWITCH If the generator was installed in conjunction with a transfer switch capable of manual operation only, the following procedure applies. A manually operated transfer switch is one that will not provide automatic start-up and does not include an intelligence circuit.
ENGINE START-UP AND TRANSFER
RETRANSFER AND SHUTDOWN
For additional information, refer to the applicable control panel manual for this unit, as well as any lit- erature pertaining to the specific transfer switch.
For additional information, refer to the applicable control panel manual for this unit, as well as any lit- erature pertaining to the specific transfer switch.
To transfer the load back to the utility power source and shut down the generator, follow these direc- tions:
AUTO/OFF/MANUAL switches (if so equipped) must be set properly, or the generator will crank and start as soon as the utility power to the transfer switch is turned off. Refer to applicable control panel and transfer switch manuals for more information. Do not proceed until certain that utility source
voltage is available to the transfer switch and the transfer switch main contacts are set to UTILITY. Do not attempt manual operation until all power
supplies to the transfer switch have been posi- tively turned off, or extremely dangerous - pos- sibly lethal - electrical shock will result. Transfer switch enclosure doors should be kept
OPERATING UNIT WITH AUTOMATIC TRANSFER SWITCH If the generator has been installed with an automatic transfer switch, such as an RTS, HTS, or GTS-type transfer switch, the engine may be started and stopped automatically or manually.
closed and locked. Only authorized personnel should be allowed access to the transfer switch interior. Extremely high and dangerous voltages are present in the transfer switch. In order to transfer load from the utility source to the generator, follow these directions:
Refer to the applicable manual for your trans- fer switch and to “Transfer Switch Start Signal Connections”. In addition, please note the dangers under “Engine Start-up and Transfer.”
Oper001 Rev. 0 08/05

MAINTENANCE PERFORMED BY AUTHORIZED SERVICE FACILITIES
extremely hot and remain hot after shutdown. High grass, weeds, brush, leaves, etc. must remain clear of the exhaust. Such materials may ignite and burn from the heat of the exhaust system.
CHECK ENGINE OIL
Check engine crankcase oil level (Figure 10.1) at least every 20 hours of operation, or prior to use.
EVERY THREE MONTHS
ONCE EVERY SIX MONTHS
ONCE ANNUALLY
Oil Fill
FIRST 100 OPERATING HOURS
Oil Dipstick
EVERY 500 OPERATING HOURS
COOLING SYSTEM Air intake and outlet openings in the generator com- partment must be open and unobstructed for contin- ued proper operation. This includes such obstruc- tions as high grass, weeds, brush, leaves and snow.
BATTERY FLUID
Check battery electrolyte fluid at least once weekly. Fluid should cover separators in all battery cells. If fluid level is low, add distilled water to cover tops of separators. DO NOT USE TAP WATER IN BATTERY.
Without sufficient cooling and ventilating air flow, the engine/generator quickly overheats, which causes it to shut down.
Maint003 Rev. 0 08/05

ENGINE COOLANT
CHECK FAN BELT
Check coolant level in coolant recovery bottle. See the “Specifications” section.
INSPECT ENGINE GOVERNOR
Visually inspect electronic governor.
MAINTENANCE OWNER/ OPERATOR CAN PERFORM
qualified service facilities should adjust the governor. Excessively high operating speeds are dangerous and increase the risk of personal injury. Low speeds impose a heavy load on the engine when adequate engine power is not available and may shorten engine life. Correct rated frequency and voltage are supplied only at the proper governed speed. Some connected electrical load devices may be damaged by incor- rect frequency and/or voltage. Only qualified service technicians should adjust the governed speed.
CHECK ENGINE OIL LEVEL
Refer to the “Checking Fluid Levels” section.
CHECK BATTERY
CHANGING ENGINE OIL
Refer to maintenance performed by authorized ser- vice facilities for engine oil and filter change frequen- cies.
EXERCISE SYSTEM
Start the generator engine at least once every seven days and let it run at least 20 minutes. See the “Weekly Exercise Cycle” section.
Drain the oil while the engine is still warm from run- ning. This means warm up the engine, shut it down and drain immediately as follows:
INSPECT COOLING SYSTEM
1. Remove OIL DRAIN HOSE from its retaining clip. 2. Loosen and remove OIL DRAIN HOSE CAP. Drain oil completely into suitable container. 3. When all oil has drained, install and tighten OIL DRAIN HOSE CAP, and re-install into its retaining clip. 4. Turn OIL FILTER (Figure 10.2) counterclockwise and remove. Dispose of old filter. 5. Apply light coating of new engine oil to seal of new oil filter.-Install FILTER and tighten by hand only. DO NOT OVERTIGHTEN. 6. Remove OIL FILL CAP. Add recommended oil (see SPECIFICATIONS). DO NOT FILL ABOVE THE DIPSTICK “FULL” MARK. Crankcase oil capacity is listed in the “Specifications”.
CHECK ENGINE COOLANT LEVEL
See the “Checking Fluid Levels” section.
PERFORM VISUAL INSPECTION
Complete a thorough visual inspection of the entire engine-generator monthly. Look for obvious damage, loose, missing or corroded nuts, bolts and other fas- teners. Look for fuel, oil or coolant leaks.
INSPECT EXHAUST SYSTEM
Inspect the exhaust system at least once every three months. Check all exhaust system pipes, mufflers, clamps, etc. for condition, tightness, leaks, security, damage.
check oil level on dipstick. NEVER OPERATE ENGINE WITH OIL BELOW THE DIPSTICK “ADD” MARK.
Maint003 Rev. 0 08/05

SPARK PLUGS
Reset the spark plug gap or replace the spark plugs as necessary.
1. Clean the area around the base of the spark plugs to keep dirt and debris out of the engine. Clean by scraping or washing using a wire brush and commercial solvent. Do not blast the spark plugs to clean. 2. Remove the spark plugs and check the condition. Replace the spark plugs if worn or if reuse is questionable. See the “Service Schedule” section for recommended inspection. 3. Check the spark plug gap using a wire feeler gauge. Adjust the gap to 1.14 mm (0.045 inch) by carefully bending the ground electrode (Figure 10.4).
Oil Filter
CHANGING THE ENGINE AIR CLEANER
(0.045 inch)
To replace the engine air cleaner, (part number 0A4637), remove the air cleaner cover and replace the air filter making sure it is positioned properly before reattaching the cover.
Air Filter
COOLANT CHANGE
Every year, have an Authorized Service Facility drain, flush and refill the cooling system. See the “Specifications” section for cooling system recom- mendations.
CLEANING THE GENERATOR
Keep the generator as clean and as dry as possible. Dirt and moisture that accumulates on internal gen- erator windings have an adverse effect on insulation resistance.
Periodically clean generator exterior surfaces. A soft brush may be used to loosen caked on dirt. Use a vacuum system or dry, low pressure air to remove any accumulations of dirt. The generator is housed inside an all-weather enclosure, clean the enclosure with a soft, damp cloth or sponge and water.
See the “Service Schedule” section for air cleaner maintenance.
Once each year, have the generator cleaned and inspected by an Authorized Service Dealer. That dealer will use dry, low pressure air to clean internal windings. Parts inside the control console should be cleaned and inspected at this time as well.
Maint003 Rev. 0 08/05

Finally, have the insulation resistance of stator and rotor windings checked. If insulation resistances are excessively low, the generator may require drying.
gas. This gas can form an explosive mixture around the battery for several hours after charg- ing. The slightest spark can ignite the gas and cause an explosion. Such an explosion can shat- ter the battery and cause blindness or other injury. Any area that houses a storage battery must be properly ventilated. Do not allow smok- ing, open flame, sparks or any spark producing tools or equipment near the battery. Battery electrolyte fluid is an extremely caus-
BATTERY
All lead-acid storage batteries discharge when not in use. Refer to specific instructions and warnings that accompany the battery. If such information is not available, observe the following precautions when handling a battery:
tic sulfuric acid solution that can cause severe burns. Do not permit fluid to contact eyes, skin, clothing, painted surfaces, etc. Wear protective goggles, protective clothing and gloves when handling a battery. If the fluid is spilled, flush the affected area immediately with clear water. Do not use any jumper cables or booster battery
to crank and start the generator engine. If the battery has completely discharged, remove it from the generator for recharging.
the OFF position before connecting the battery cables. If the switch is set to AUTO or MANUAL, the generator can crank and start as soon as the battery cables are connected. Be sure the 120VAC power supply to the battery
BATTERY MAINTENANCE
is turned OFF, or sparking may occur at the bat- tery posts as the cables are attached and cause an explosion.
The battery should be inspected per the “Service Schedule” section. The following procedure should be followed for inspection:
BATTERY REPLACEMENT
When replacing batteries, use the same number and the type of battery that follows:
BCI Group No. CCA 24F-6 525 @ 0 deg. F
The BCI number should be located directly on the battery.
REPAIR PARTS The latter portion of this manual consists of exploded views, parts lists and electrical data pertaining to this generator set. The parts lists consist of (a) an item number, (b) a part number, (c) the quantity required, and (d) a description of the part. The item number corresponds to an identical number on the exploded view drawing.
Maint003 Rev. 0 08/05

SERVICE SCHEDULE
30 KW - 150 KW STANDBY GAS ENGINE DRIVEN GENERATOR SETS
The following is a recommended maintenance schedule for standby gas engine driven generator sets from 30kW to 150 kW in size. The established intervals in the schedule are the maximum recommended when the unit is used in an average service application. They will need to be decreased (performed more frequently) if the unit is used in a severe application. Use calendar time, from the previous maintenance interval to determine the next required maintenance interval.
1 An early inspection of the generator set to insure it is ready to operate when required and to identify any poten- tial problem areas.
This inspection may be performed by the end user providing the following safety steps are taken to prevent the engine from starting automatically without warning:
To prevent injury, perform the following steps in the order indicated before starting any maintenance:
The battery charger must be turned off BEFORE removing the battery cable to prevent an over current condition from burning out sensitive control panel components and circuits.
Following all maintenance, reverse these steps to insure the unit is returned to standby setup for normal
operation when required.
2 A wear-in service inspection of the generator set to insure it is ready to operate and carry the load when required, and to identify any potential problem areas.
Performed ONLY ONCE following the first three months or the first 30 hours of operation after purchase of the unit.
This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge to accomplish and should be performed only by an Authorized Service Dealer.
3 An operational inspection of the generator set to insure it is ready to operate and carry the load when required, and to identify any potential problem areas.
Performed semi-annually or following each 50 hours of operation of the unit.
This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge to accomplish and should be performed only by an Authorized Service Dealer.
4 A mid-level inspection of the generator set to insure it is ready to operate and carry the load when required, and to identify any potential problem areas.
Performed annually or following each 100 hours of operation of the unit.
This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge to accomplish and should be performed only by an Authorized Service Dealer.
5 A comprehensive inspection of the generator set to insure it is properly serviced and ready to operate and carry the load when required, and to identify any potential problem areas.
Performed annually or following each 250 hours of operation of the unit.
This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge to accomplish and should be performed only by an Authorized Service Dealer.
SrvSchd001 Rev. A 09/05

Maintenance Level 1 Level 2 Level 3 Level 4 Level5 Tasks Recom- Task Required Task Required Task Task Required Task mended Comp. to be done Comp. to be done Comp. Required Comp. to be done Comp. to be done (Date- 3 months/ (Date- Semi- (Date- to be done (Date- Bi- (Date- monthly/ Initials) Break-in Initials) annually/ Initials) Annually/ Initials) annually/ Initials) 10 hrs. 30 hrs. 50 hrs. 100 hrs. 250 hrs. 1. Disable the unit from operating per the first page warning. 2. Check the engine oil level. Adjust as necessary. 3. Check the engine coolant level. Adjust as necessary. 4. Check the engine coolant thermal protection level. Correct as necessary. 5. Check the natural gas delivery system for leaks and correct pressure on gas engine driven units. Tighten connections as necessary. 6. Check the air inlets and outlets for debris. Clean as necessary. 7. Check the battery electrolyte level and specific gravity if accessible. Adjust as necessary. 8. Check the battery posts, cables, and charger for loose connections, corrosion, and proper operation. Correct as necessary. 9. Check the unit wiring for loose connections, corrosion, and damage. Correct as necessary.
SrvSchd001 Rev. A 09/05

Maintenance Level 1 Level 2 Level 3 Level 4 Level5 Tasks Recom- Task Required Task Required Task Task Required Task mended Comp. to be done Comp. to be done Comp. Required Comp. to be done Comp. to be done (Date- 3 months/ (Date- Semi- (Date- to be done (Date- Bi- (Date- monthly/ Initials) Break-in Initials) annually/ Initials) Annually/ Initials) annually/ Initials) 10 hrs. 30 hrs. 50 hrs. 100 hrs. 250 hrs. 10. Check the engine accessory drive belts and fan coupling device if equipped for correct tension, wear, weather cracking, and damage. Replace as necessary. 11. Check the engine valve clearance. Adjust as necessary. 12. Visually inspect the unit looking for leaks, wear or damage, loose connections or components, and corrosion. Correct as necessary. 13. Test the engine and transfer switch safety devices. Correct and/or adjust as necessary. 14. Initiate an automatic start and transfer of the unit to site load and exercise it for at least 1 hour looking for leaks, loose connections or components, and abnormal operating conditions. Correct as necessary. 15. Replace the engine accessory drive belts. 16. Check gearbox oil level (if equipped). 17. Change gearbox oil (if equipped).
SrvSchd001 Rev. A 09/05

Maintenance Level 1 Level 2 Level 3 Level 4 Level5 Tasks Recom- Task Required Task Required Task Task Required Task mended Comp. to be done Comp. to be done Comp. Required Comp. to be done Comp. to be done (Date- 3 months/ (Date- Semi- (Date- to be done (Date- Bi- (Date- monthly/ Initials) Break-in Initials) annually/ Initials) Annually/ Initials) annually/ Initials) 10 hrs. 30 hrs. 50 hrs. 100 hrs. 250 hrs. 18. Start and exercise the unit at full rated load (use a load bank if the site load is not enough) for at least 2 hours looking for leaks, loose connections or components, and abnormal operating conditions. Correct as necessary. 19. Perform an engine oil analysis (send a sample to a lab for results). Change the engine oil and filters if the analysis results indicate this is required. 20. Change the engine oil. 21. Replace the engine oil filter(s). 22. Replace engine spark plugs. Clean and re-gap or replace as necessary. 23. Replace the engine air filter(s). 24. Perform a 5 minute no-load operational run of the unit looking for any post service problems. 25. Return the unit to standby setup for operation when required.
SrvSchd001 Rev. A 09/05

TROUBLESHOOTING GUIDE
PROBLEM CAUSE CORRECTION
Engine won’t crank. 1. 15 amp fuse blown. 1. Replace fuse. 2. Loose or corroded or defective 2. Tighten, clean or replace battery cables. battery cables as necessary. 3. Defective starter contactor. 3. Replace contactor.* 4. Defective starter motor. 4. Replace starter motor.* 5. Dead or Defective Battery. 5. Remove, change or replace battery. 6. 5 amp fuse blown. 6. Replace fuse.* Engine cranks but won't start 1. Out of fuel. 1. Replenish fuel. 2. Fuel solenoid (FS) is defective 2. Replace solenoid.* 3. Open Wire #14A from Engine Control 3. Reconnect wire. circuit board. 4. Spark plugs defective. 4. Clean, regap or replace plugs. 5. Door on tank not closed. 5. Close door on tank. Engine starts hard, runs rough. 1. Flame arrestor (air cleaner) plugged or 1. Clean or replace as needed. damaged. 2. Plugged fuel line. 2. Unclog fuel line. 3. Defective spark plugs. 3. Clean, regap or replace plugs. 4. Fuel pressure incorrect. 4. Confirm fuel pressure to regulator is as recommended in SPECIFICATIONS. Engine starts then shuts down. 1. Engine oil level is low. 1. Check oil and add oil as needed. 2. Engine is overheated. 2. Check cooling system for leaks. 3. Defective Low Oil Pressure Switch 3. Replace switch.* 4. Defective Coolant Temperature Switch 4. Replace switch.* 5. Defective Control Module circuit board. 5. Replace board.* 6. Coolant Level is Low. 6. Repair leak - Add coolant. 7. Defective Low Coolant Level Switch 7. Replace Switch.* AUTO/OFF/MANUAL Switch at OFF, 1. Defective AUTO/OFF/MANUAL switch 1. Replace switch.* engine continues to run 2. Open/disconnected wire #15A between 2. Reconnect/close wire. AUTO/OFF/MANUAL switch and Control Module circuit board. 3. Defective Control Module circuit board 3. Replace board.* No AC output from generator. 1. Check main line circuit breaker. 1. Reset to ON or CLOSED. 2. Check circuit breaker & fuses. 2. Reset and replace, if necessary. 3. Transfer switch set to NORMAL position 3. Set to GENERATOR position. 4. Generator internal failure. 4. * 5. Thermal circuit breaker open. 5. Auto-reset - Wait 5 min. and attempt restart.
*Contact the nearest Authorized Dealer for assistance.
Trblsht001 Rev. 0 08/05







1 0F2885 1 PANEL CB CONN BOX 2 0F2883 1 STAND RH CONTROL 0F9637 (4) 1 STAND RH CONTROL, TWO HOLE (FOR 5.4L 100KW & 4.6L 80KW 1PHASE) 3 0F3685 1 STAND LH CONTROL C5 GRBX 4 023484N 1 BUSHING SNAP SB-2.5-31 023484N 2 BUSHING SNAP SB-2.5-31 (FOR 5.4L 100KW & 4.6L 80KW 1PHASE) 5 086961 1 INTERFACE 1PH 240V 067617030A - INTERFACE 3PHS 416/480V 067617030B - INTERFACE 3PHS 208/240V 6 043180 4 WASHER FLAT M4 7 022264 4 WASHER LOCK #8-M4 8 0C3990 4 SCREW PHTT M4-0.7 X 10 ZYC (1) 9 057701 REF. BLOCK TERM 20A 8 X 6 X 1100V 10 022155 2 WASHER LOCK #6 11 0C2428 2 SCREW PHTT #6-32 X 1/2 ZYC 12 0F3618 1 DECAL CPL CUST CONN H CTRL 13 0A9457 1 DECAL NEUTRAL 14 057073 2 JUNCTION BLOCK 3/8-16 (2) 15 0D5466 REF. BUS BAR NEUTRAL BLOCK 390 (2) 16 0A7822 REF. LUG SLDLSS 600/250-1/0 X 1/4-28 17 022237 4 WASHER LOCK 3/8 18 022241 4 NUT HEX 3/8-16 STEEL 19 049226 6 WASHER LOCK M5 20 0C2266 6 SCREW PHTT M5-0.8 X 16 ZYC 21 0C2454 10 SCREW THF M6-1 X 16 N WA Z/JS 22 042568 4 SCREW HHC M6-1.0 X 20 G8.8 23 022473 12 WASHER FLAT 1/4-M6 ZINC 24 022097 8 WASHER LOCK M6-1/4 25 049813 4 NUT HEX M6 X 1.0 G8 YEL CHR (1) 26 0D4698 1 BLOCK TERM 20A 6 X 3 X 1100V 27 0F4464 1 DECAL CUST CONN 120V UTILITY 28 025433 1 LUG SLDLSS #6-14 X 13/64 CU 29 024469 1 SCREW HHTT #10-32 X 3/8 CZ 30 067210A 1 DECAL GROUND LUG 31 0D6029 4 SCREW HHTT M6-1.0 X 16 ZYC 32 051713 2 WASHER FLAT M5 33 081008 1 GROMMET 1.25 X .25 X .75 34 077043J 3 CONDUIT FLEX 2.0" ID 077043J 4 CONDUIT FLEX 2.0" ID (FOR 5.4L 100KW & 4.6L 80KW 1 PHASE) 35 0F6156 1 PLATE WIRE SNGL GALV 36 029289 1 TAPE ELEC 1/2 FOAM (AS REQ’D) (3) 37 0F8656 REF ASSY PCB 4.6L IGNITION MODULE 0F3113 REF ASSY PCB HSB CTRL IGN MODULE (ALL OTHER APPLICATIONS EXCEPT 4.6L G3) 38 047411 4 SCREW HHC M6-1.0 X 16 G8.8 39 036943 2 SCREW PPHM #10/32 X 2 40 023897 2 WASHER FLAT #10 ZINC 41 022152 2 WASHER LOCK #10 42 022158 2 NUT HEX #10-32 STEEL
1.) UL CIRCUIT BREAKER (FD) A 0F2887 1 COVER FD FRM CB B 065469 1 DECAL DANGER HIGH VOLTAGE C 0D5572 - CB 0150A 3P 600V S FD6 LL 0D5573 - CB 0175A 3P 600V S FD6 LL 0D5575 - CB 0225A 3P 600V S FD6 LL 0D5576 - CB 0250A 3P 600V S FD6 LL D 0F0199 1 INSULATOR CB FD FRAME 30MIL E 065960 4 SCREW SHC 1/4-20 X 4 G8.8 NZ F 022473 4 WASHER FLAT 1/4-M6 ZINC G 022097 4 WASHER LOCK M6-1/4 H 022127 4 NUT HEX 1/4-20 STEEL J 0C2454 4 SCREW THF M6-1 X 16 N WA Z/JS K 029289 1 TAPE ELEC 1/2 FOAM (AS REQ’D) L 0F1733 1 DECAL CUSTOMER CONNECT INSIDE
2.) UL CIRCUIT BREAKER (JD+LD) A 0F2721 1 COVER CIR BRKR JD/LD B 065469 1 DECAL DANGER HIGH VOLTAGE C 0D5577 - CB 0300A 3P 600V S JD6 LL 0D5578 - CB 0350A 3P 600V S JD6 LL 0D5579 - CB 0400A 3P 600V S JD6 LL 0D5581 - CB 0600A 3P 600V S LD6 0D5585 - CB 0450A 3P 600V S LD6 LL D 0F2353 2 INSULATOR CIRCUIT BR. JD/LD E 022770 4 SCREW RHM 1/4-20 X 3 F 022473 4 WASHER FLAT 1/4-M6 ZINC G 022097 4 WASHER LOCK M6-1/4 H 022127 4 NUT HEX 1/4-20 STEEL J 0C2454 7 SCREW THF M6-1 X 16 N WA Z/JS K 029289 1 TAPE ELEC 1/2 FOAM (AS REQ’D) L 0F1733 1 DECAL CUSTOMER CONNECT INSIDE
(1) ITEM INCLUDED WITH HARNESS.
(2) ITEM INCLUDED WITH 0D5464B.
(3) ITEM IS PART OF 9R.
(4) ROUTE ONE SET (11, 22, 33, 44) THROUGH ONE HOLE; AND ROUTE THE SECOND SET (11, 22, 33, 44) THROUGH THE OTHER HOLE.



3.) UL CIRCUIT BREAKER (225AF) A 0F4173 1 COVER CB C5 225AF B 065469 1 DECAL DANGER HIGH VOLTAGE C 0F4165$ REF CIRCUIT BREAKERS 200A FRAME D 0F4186 1 COVER CB DISH 225AF E 036261 4 RIVET POP .125 X .275 SS F 053640 4 SCREW RHM #8-32 X 3-1/4 G 038150 4 WASHER FLAT #8 ZINC H 022264 4 WASHER LOCK #8-M4 J 022471 4 NUT HEX #8-32 STEEL K 029289 2 TAPE ELEC 1/2 FOAM L 0F1733 1 DECAL CUSTOMER CONNECT INSIDE M 022129 9 WASHER LOCK M8-5/16 N 0F8432 1 INSULATOR CB 225AF P 0C2454 7 SCREW THF M6-1 X 16 N WA Z/JS R 0F8451 3 LUG SLDLSS 300 MCM-6 AL/CU S 049897 9 SCREW SHC M8-1.25 X 20 G8 T 022145 6 WASHER FLAT 5/16-M8 ZINC U 045771 3 NUT HEX M8-1.25 G8 CLEAR ZINC V 0F8843 3 BUS BAR 200A LUG ADAPTOR (1) W W/CB 2 TERMINAL COVER CB
5.) UL CIRCUIT BREAKER (800AF) A 0F4176 1 COVER CB C5 800AF B 065469 1 DECAL DANGER HIGH VOLTAGE C 0F4167$ REF CIRCUIT BREAKERS 800A FRAME D 0F8433 2 INSULATOR CB 800AF E 024196 4 SCREW RHM 1/4-20 X 3-1/2 F 022473 4 WASHER FLAT 1/4-M6 ZINC G 022097 4 WASHER LOCK M6-1/4 H 022127 4 NUT HEX 1/4-20 STEEL J 0C2454 7 SCREW THF M6-1X16 N WA Z/JS K 029289 2 TAPE ELEC 1/2 FOAM L 060619 3 SCREW SHC M10-1.50 X 40 G12.9 M 022131 9 WASHER FLAT 3/8-M10 ZINC N 022237 6 WASHER LOCK 3/8 P 045772 6 NUT HEX M10-1.5 G8 YEL CHR R 0F8452 3 LUG SLDLSS 500-750 X 2 MCM AL/CU S 097950 3 SCREW SHC M10-1.25 X 70 G8.8 T 0F1733 1 DECAL CUSTOMER CONNECT INSIDE (1) U W/CB 2 TERM COVER VITZROTECH 400AF CB
6.) NEUTRAL BLOCK 390 / 200-400A A 0D5466 2 BUS BAR NEUTRAL BLOCK 390 B 039287 1 SCREW HHC M8-1.25 X 45 G8.8 FT C 022145 1 WASHER FLAT 5/16-M8 ZINC D 022129 1 WASHER LOCK M8-5/16 E 045771 1 NUT HEX M8-1.25 G8 YEL CHR F 045335 2 SCREW HHC 1/4-28 X 3/4 G5 G 022097 2 WASHER LOCK M6-1/4 H 0A7822 1 LUG SLDLSS 600/250-1/0X1/4-28
4.) UL CIRCUIT BREAKER (400AF) A 0F4175 1 COVER CB C5 400AF B 065469 1 DECAL DANGER HIGH VOLTAGE C 0F4166$ REF CIRCUIT BREAKERS 400A FRAME D 0F1733 1 DECAL CUSTOMER CONNECT INSIDE E 042419 4 SCREW RHM 10-32 X 4 F 023897 4 WASHER FLAT #10 ZINC G 022152 4 WASHER LOCK #10 H 022158 4 NUT HEX #10-32 STEEL J 0C2454 7 SCREW THF M6-1 X 16 N WA Z/JS K 029289 1 TAPE ELEC 1/2 FOAM (2) L 052647 2/3 SCREW SHC M10-1.5 X 25 G12.9 (2) M 046526 2/3 WASHER LOCK M10 N W/CB 3 BUS BAR CB ADAPTER 225-400 A P 0A7822 3 LUG SLDLSS 600/250-1/0 X 1/4-28 R 022131 3 WASHER FLAT 3/8-M10 ZINC (1) S W/CB 2 TERM COVER CB T 023334 6 SCREW HHC 1/4-28 X 1/2 G5 U 022097 6 WASHER LOCK M6-1/4 V 022473 6 WASHER FLAT 1/4-M6 ZINC (2) W W/CB 2/3 SCREW SHC M10-1.5 X 25 G12.9 (2) X W/CB 2/3 WASHER LOCK M10
(1) HARDWARE FOR MTG. CB TERMINAL COVERS IS SUPPLIED WITH CIRCUIT BREAKERS.
(2) 2/3 QTY. 2POLE & 3 POLE CB.



1 0F2885 1 PANEL CB CONN BOX 2 0G0171 1 STAND, RH CONTROL CPL C5 0G0171A 1 STAND RH CONTROL CPL C5 2 HOLE 3 0G0172 1 STAND, LH CONTROL CPL C5 4 023484N 1 BUSHING SNAP SB-2.5-31 5 0F4677 1 ASSY PCB INTERFACE 1PH 240V 067617030A - INTERFACE 3PHS 416/480V 067617030B - INTERFACE 3PHS 208/240V 6 043180 4 WASHER FLAT M4 7 022264 4 WASHER LOCK #8-M4 8 0C3990 4 SCREW PHTT M4-0.7 X 10 ZYC 9 * 057701 REF. BLOCK TERM 20A 8 X 6 X 1100V 10 022155 2 WASHER LOCK #6 11 0C2428 2 SCREW PHTT #6-32 X 1/2 ZYC 12 0F3618 1 DECAL CPL CUST CONN H CTRL 13 0A9457 1 DECAL NEUTRAL 14 057073 2 JUNCTION BLOCK 3/8-16 15 ** 0D5466 REF. BUS BAR NEUTRAL BLOCK 390 16 ** 0A7822 REF. LUG SLDLSS 600/250-1/0 X 1/4-28 17 022237 4 WASHER LOCK 3/8 18 022241 4 NUT HEX 3/8-16 STEEL 19 049226 6 WASHER LOCK M5 20 0C2266 6 SCREW PHTT M5-0.8 X 16 ZYC 21 0C2454 10 SCREW THF M6-1 X 16 N WA Z/JS 22 042568 4 SCREW HHC M6-1.0 X 20 G8.8 23 022473 12 WASHER FLAT 1/4-M6 ZINC 24 022097 8 WASHER LOCK M6-1/4 25 049813 4 NUT HEX M6 X 1.0 G8 YEL CHR 26 * 0D4698 1 BLOCK TERM 20A 6 X 3 X 1100V 27 0F4464 1 DECAL CUST CONN 120V UTILITY 28 025433 1 LUG SLDLSS #6-14 X 13/64 CU 29 024469 1 SCREW HHTT #10-32 X 3/8 CZ 30 067210A 1 DECAL GROUND LUG 31 0D6029 4 SCREW HHTT M6-1.0 X 16 ZYC 32 051713 2 WASHER FLAT M5 33 081008 1 GROMMET 1.25 X .25 X .75 34 077043J 3 CONDUIT FLEX 2.0" ID 35 0F6156 1 PLATE WIRE SNGL GALV
36 029289 1 TAPE ELEC 1/2 FOAM (AS REQ’D) 37*** 0F3113 REF ASSY PCB HSB CTRL IGN MODULE 38 047411 4 SCREW HHC M6-1.0 X 16 G8.8 39 036943 2 SCREW PPHM #10/32 X 2 40 023897 2 WASHER FLAT #10 ZINC 41 022152 2 WASHER LOCK #10 42 022158 2 NUT HEX #10-32 STEEL
1.) UL CIRCUIT BREAKER (800AF) A 0G0173 1 COVER, CB 803 C5 B 065469 1 DECAL DANGER HIGH VOLTAGE C 0F4167$ REF CIRCUIT BREAKERS 800A FRAME D 0F8433 2 INSUL CB 800AF E 022477 4 SCREW RHM 1/4-20 X 1-1/2 F 022473 4 WASHER FLAT 1/4-M6 ZINC G 022097 4 WASHER LOCK M6-1/4 H 022127 4 NUT HEX 1/4-20 STEEL J 0F1733 1 DECAL CUSTOMER CONNECT INSIDE K 029289 2 TAPE ELEC 1/2 FOAM L 060619 3 SCREW SHC M10-1.50 X 40 G12.9 M 022131 9 WASHER FLAT 3/8-M10 ZINC N 022237 6 WASHER LOCK 3/8 P 045772 6 NUT HEX M10-1.5 G8 YEL CHR R 0F8452 3 LUG SLDLSS 500-750X2 MCM AL/CU S 0D2576 3 SCREW SHC M10-1.5 X 70 G10.9 T**** W/CB 2 TERM. COVER VITZROTECH 400AF CB
2.) NEUTRAL BLOCK 390 / 200-400A A 0D5466 1 BUS BAR NEUTRAL BLOCK 390 B 039287 1 SCREW HHC M8-1.25 X 45 G8.8 FT C 022145 1 WASHER FLAT 5/16-M8 ZINC D 022129 1 WASHER LOCK M8-5/16 E 045771 1 NUT HEX M8-1.25 G8 YEL CHR F 045335 2 SCREW HHC 1/4-28 X 3/4 G5 G 083896 2 WASHER LOCK 1/4-M6 SS H 0A7822 1 LUG SLDLSS 600/250-1/0 X 1/4-28
* ITEM INCLUDED WITH HARNESS ** ITEM INCLUDED WITH 0D5464B *** ITEM IS PART OF 9R. **** HARDWARE FOR MTG. CB TERMINAL COVERS IS SUPPLIED WITH CIRCUIT BREAKERS.




1 0F2687 1 WELDMENT RADIATOR SUPPORT150 2 0F2611 1 RADIATOR 680 X 680 X 70 CPL 3 0F5254 1 V-BELT 31/64" X 62-3/8" 0F5253 1 V-BELT 31/64" X 61-3/8" (5.4L 100KW ONLY) 0F7077 1 V-BELT 1/2" X 63-3/8" (6.8L 100 130KW) 4 046526 12 WASHER LOCK M10 5 051756 8 SCREW HHC M10-1.5 X 20 G8.8 6 0C2454 2 SCREW THF M6-1 X 16 N WA Z/JS 7 052250 2 TAPE FOAM 1 X 1 (26.75” LG) 8 076749 1 TANK COOLANT RECOVERY 9 0F2573 1 PULLEY FAN V-GROOVE 9" 10 0F2610 1 FAN 26" LH ROTATION 11 0F2572 1 ARM TENSIONER 12 0F5689 1 SCREW SHC SHLDR LKG M8 X 16 LG 13 0F2862 1 SPRING TENSION CPL 14 0F2560 1 PULLEY V-BELT 4" FLANGED 15 022131 14 WASHER FLAT 3/8-M10 ZINC 16 039414 1 SCREW HHC M8-1.25 X 35 G8.8 17 052625 3 SCREW SHC M10-1.5 X 35 G12.9 18 0F2561 1 HUB FLEX PLATE 19 0C8165 5 NUT HEX LOCK 5/16-24 NY INS 20 0D6795 1 SCREW HHC M12-1.5 X 60 G8.8 21 0C7043 12 DISK FLEX 22 0E8909 1 COUPLING HUB FLEX (MACH) 23 048031C 1 CLAMP HOSE BAND 1/4 24 0C8146 4 SCREW HHC 5/16-24 X 1.124 25 082774 2 KEY WOODRUFF 4 X 19D 26 0F2686 1 HOSE RADIATOR UPPER CPL 27 0F5463 1 HOSE LOWER RAD CPL C5 6.8L 28 0F8695 1 ASSY BRG/SHAFT CPL FANDRIVE 29 0F4028 1 PULLEY 6.5" DIA MACHINED (6.8L 100KW) 0F4030 1 PULLEY 6" DIA MACHINED (6.8L 130KW) 0F4032 1 PULLEY 5.5" DIA MACHINED (5.4L 80KW & 6.8L 150KW) 0F4496 1 PULLEY 4.5" DIA MACHINED (5.4L 100KW) 30 042911 1 SCREW HHC M10-1.5 X 30 G8.8 31 0F2872 1 SCREW HHC 1/2-13 X 2" G8 32 022304 2 WASHER FLAT 1/2 ZINC 33 022195 1 WASHER LOCK 1/2 34 022196 1 NUT HEX 1/2-13 STEEL 35 049813 8 NUT HEX M6 X 1.0 G8 YEL CHR 36 049820 1 NUT HEX LOCK M8-1.25 NY INS 39 022145 1 WASHER FLAT 5/16-M8 ZINC 40 022129 1 WASHER LOCK M8-5/16 42 035685 4 CLAMP HOSE #28 1.32-2.25 43 045764 1 SCREW HHTT M4-0.7 X 8 BP 44 065852 1 SPRING CLIP HOLDER .37-.62 45 0C7649 1 CLAMP HOSE .38-.87 46 055596 1 BARBED STR 3/8 NPT X 3/8 47 069860E 1 HOSE DRAIN ASSY 28" 48 * 069811 REF CAP HEX 1/4 NPT BRASS 49 080713 1 BRACKET COOLANT TANK 50 022473 16 WASHER FLAT 1/4-M6 ZINC 51 022097 16 WASHER LOCK M6-1/4 52 042568 8 SCREW HHC M6-1.0 X 20 G8.8 53 0F5050 1 SHIELD RADIATOR C5 54 039253 1 SCREW HHC M8-1.25 X 20 G8.8 55 051769 1 WASHER LOCK M12 56 0C8145 8 WASHER FLEX (THIN) 57 0E2507 1 PROBE, COOLANT LEVEL 3/8 NPTF 58 090283 1 CAP RADIATOR 13 PSI 59 0C8566 8 SCREW HHFC M6-1.0 X 20 G8.8 60 0F2776A 1 BRACKET, SIGNAL CONDITIONER 61 052644 1 SPACER .5 X 1.5 X .25 STL/ZINC
* ITEM 48 IS INCLUDED WITH 47.




1 0F3099 1 MTG BASE CP 5.4L 100KW DD 2 065852 1 SPRING CLIP HOLDER .37-.62 3 052252 5 DAMPENER VIBRATION 4 052257 5 SPACER .49 X .62 X 1.87 PWDR/ZINC 5 052259 5 WASHER FLAT M12 6 055597 5 SCREW HHC M12-1.75 X 85 G8.8 7 052251A 5 DAMPENER VIBRATION 50 WHITE 8 052860 4 NUT LOCKING M12-1.75 9 0F2895 2 SUPPORT ENG 5.4L LH/RH 6.8L RH 10 045764 1 SCREW HHTT M4-0.7 X 8 BP 11 022447 1 WASHER SHAKEPROOF INT 1/4 12 061383 1 LUG SOLDERLESS 3/0-#4 X 13/32 CU 13 043107 1 SCREW HHC M8-1.25 X 25 G8.8 14 022473 1 WASHER FLAT 1/4-M6 ZINC 15 049813 1 NUT HEX M6 X 1.0 G8 YEL CHR 16 057192 8 SCREW SHC M10-1.5 X 30 G12.9 17 022131 8 WASHER FLAT 3/8-M10 ZINC 18 046526 8 WASHER LOCK M10 19 0536210360 1 WIRE ASSEM #4GA GRD 20 042909 1 SCREW HHC M8-1.25 X 30 G8.8 21 022261 2 WASHER SHAKEPROOF INT 3/8 22 022129 1 WASHER LOCK M8-5/16 23 022145 2 WASHER FLAT 5/16-M8 ZINC 24 045771 2 NUT HEX M8-1.25 G8 YEL CHR 25 038750 1 SCREW HHC M6-1.0 X 30 G8.8 26 022097 1 WASHER LOCK M6-1/4



1 0F3408 1 TRAY BATTERY 2 0F3411 1 STRAP BATTERY RETAINMENT 3 058208 1 BATT 12VDC 24F 625 4 022131 1 WASHER FLAT 3/8-M10 ZINC 5 050331A 1 BATT POST COVER RED + 6 050331 1 BATT POST COVER BLK - 7 038805U 1 CABLE BATT BLK #1 X 18.00 8 038804U 1 CABLE BATT RED #1 X 28.00 9 045771 1 NUT HEX M8-1.25 G8 YEL CHR 10 022129 1 WASHER LOCK M8-5/16 11 027482 1 WASHER SHAKEPROOF EXT 5/16 STL 12 075763 1 BOOT BATTERY CABLE 13 0C2454 8 SCREW THF M6-1X16 N WA Z/JS 14 0F3409 1 SUPPORT BATTERY TRAY




COMPONENTS INCLUDED IN 0F1826E 1 0F1823 1 ENCL H CONTROL PANEL 2 0F1824 1 COVER CONTROL PANEL 3 0F2606 1 HINGE CONTINUOUS H-PNL 4 036261 6 RIVET POP .125 X .275 SS 5 0F5763 1 ASSY PROGRAMMED PM H-100 6 0F1732 1 DECAL FUSES LOCATED INSIDE 7 0E9764 1 RAIL SNAPTRACK PCB HOLDER BULK (12” LG) 8 0F1725C 1 ASSY PCB 2AMP 12V UL BATT CHGR 9 0F1958 1 PLATE HARNESS CLAMP 10 0F2256 1 ASSY PCB PWR AVR W/AMP HEADER 11 0E3161 1 ASSY PCB BOSCH GOV DRIVER 12 029673 1 DIO BRIDGE 25A 600V 13 049226 8 WASHER LOCK M5 14 079224 4 SCREW PPHM M5-0.8 X 30 SS 15 051713 8 WASHER FLAT M5 16 0F5886 3 SCREW HHPM M5-0.8 X 12 17 051716 5 NUT HEX M5-0.8 G8 CLEAR ZINC 18 0C3990 3 SCREW PHTT M4-0.7 X 10 ZYC 19 043280 3 WASHER FLAT M4 20 055014 10 SCREW PPHM M4-0.7 X 8 BLK OX 21 043184 10 WASHER LOCK M4 22 0F2557 1 DECAL WARNING BATT CHRG 12/24V 23 0F5884 1 SCREW PHTT M3.5-0.6 X 10 24 0C2265 4 SCREW PHTT M4-0.7 X 12 ZYC 25 0F4333 1 CONN DUST CAP W/CHAIN DB9 26 0F5883 1 WASHER FLAT M3.5 27 0F6305 2 SEAL COVER 3.18 X 12.7 X 382 28 0F6305A 1 SEAL COVER 3.18 X 12.7 X 283 29 0F6277 1 ASSY HARNESS H-PNL SW (NOT SHOWN) COMPONENTS INCLUDED IN WIRE HARNESS A 0F1263 1 ADPTR RH SIDE WICKMAN 178.6191 B 0F1262 4 HOLDER FUSE WICKMANN 178.6150 C 0F1264 1 ADPTR LH SIDE WICKMAN 178.6192 D 0E9049B 1 ASSY PCB G-PANEL RELAY 12VDC E 055911 1 BLOCK TERM 20A 12 X 6 X 1100V COMPONENTS NOT INCLUDED IN 0F1826E OR WIRE HARNESS 50 056739 1 RELAY SOLENOID 12VDC PNL MNT 51 - 1 DPE BREAKER SEE DRAWING 0F9280 52 - 1 BOOST RESISTOR SEE DRAWING 0F9280 53 0F2627A 1 COVER CONTROL PANEL SIDE 54 022287 2 SCREW HHC 1/4-20 X 3/4 G5 55 022473 4 WASHER FLAT 1/4-M6 ZINC 56 022097 2 WASHER LOCK M6-1/4 57 043182 3 WASHER LOCK M3 58 051714 3 NUT HEX M3-0.5 G8 YEL CHR 59 052777 3 WASHER FLAT M3 60 0C2323 2 SCREW PHTT #6-32 X 5/8 ZYC 61 0F5459 1 DECAL CPL CONTROL PANEL FUSES 62 0F5461 1 DECAL 5.4/6.8L TB3 63 022127 2 NUT HEX 1/4-20 STEEL 64 0F5460 1 DECAL CPL 5.4/6.8L RELAY BOARD 65 0E7403C 1 FUSE ATO TYPE 15 AMP (BLUE) 66 0E7403B 2 FUSE ATO TYPE 10 AMP (RED) 67 0F6145 A/R SEAL WEATHER .45" DIA 68 091526 4 SCREW PPHM M5-0.8 X 12 ZNC 69 0C2699 2 SCREW PHTT #6-32 X 3/8 ZYC 70 051713 4 WASHER FLAT M5 71 049226 4 WASHER LOCK M5



1 0F2807C 1 PIPE EXH MAN R/H 6.8L G/B CPL (6.8L C5) 0F2807E 1 PIPE EXH MAN R/H 5.4L G/B & 2P (5.4L C5) 0F9207 1 PIPE EXH MANIFOLD 4.6L RH 2 0F2807B 1 PIPE EXH MAN L/H 6.8L G/B CPL (6.8L C5) 0F2807D 1 PIPE EXH MAN L/H 5.4L G/B & 2P (5.4L C5) 0F9208 1 PIPE EXH MANIFOLD 4.6L LH 3 0F4505 REF GLASS PACK 23.5" LG 2.5" IN/OUT 4 0A6765 2 RING GASKET 2.5 DIA 5 0F4710 6 WASHER LOCK M10 SS 6 0F7200 6 SCREW HHC M10-1.5 X 50 SS FTH 7 080762 8 BOLT U 3/8-16 X 2.62 8 0F2809 1 PIPE EXHAUST CROSSOVER 9 0F2981A 2 MFLR 7" X 9" X 25" (2) 2.5" IN/2.5" OUT 10 0F2962 2 MUFFLER STRAP 11 0C2454 4 SCREW THF M6-1 X 16 N WA Z/JS 12 022097 8 WASHER LOCK M6-1/4 13 0F2830 2 MUFFLER BRACKET STIFFENER 14 0F4462 REF RAIN CAP ALUM FOR 2-1/2" PIPE 15 0C2454 REF SCREW THF M6-1 X 16 N WA Z/JS 16 0F4367 REF HEAT SHIELD EXHAUST STACK 17 0F4368 REF CAP HEAT SHIELD EXHAUST STACK 18 0F2773C 2 EXHAUST BLANKET 900MM LONG (6.8L C5) 0F2773D 2 EXHAUST BLANKET 850MM LONG (5.4L C5) 19 0D3159 2 FLANGE EXHAUST 20 088775 6 WASHER FLAT 3/8 SS 21 0F2808 2 EXHUAST OUTLET PIPE CPL 22 0F5447 1 BRKT MUFFLER 23 022473 12 WASHER FLAT 1/4-M6 ZINC 24 0F6214 2 PIPE ELBOW EXHAUST MUFFLER 25 080762 REF BOLT U 3/8-16 X 2.62 26 0F6803 4 MUFFLER STRAP UPPER/LOWER 27 049813 4 NUT HEX M6 X 1.0 G8 YEL CHR 28 049721 8 SCREW HHC M6-1.0 X 35 G8.8 BLK 29 088510 6 NUT HEX M10-1.5 SS
* PARTS INCLUDED IN 0F6322 KIT, GLASS PACK SHIP LOOSE.




1 0D2513D 1 AIR CLNR BTM PLT W/CPLR 8.1L 2 0F5419 1 ELEMENT AIR FILTER 3 0F4268 1 TOP PLATE VENTURI 4 0F4270A 1 HOLD DOWN AIR CLEANER PLATED 5 0F6977 1 PLATE AIR CLEAN TOP 5.4L/6.8L 6 037561 1 NUT WING 1/4-20 NYLK 7 047411 4 SCREW HHC M6-1.0 X 16 G8.8 8 022097 4 WASHER LOCK M6-1/4 9 049811 4 WASHER FLAT M6 10 0F4269 1 GASKET MIXER BODY 11 022473 1 WASHER FLAT 1/4-M6 ZINC



(2) 1 0F5873 1 REAR WRAP C5 (2) 2 0F5868 4 DOOR C5 (2) 3 0F5872 2 CENTER SUPPORT C5 (2) 4 0F5871 2 DISCHARGE DUCT LH & RH SIDE C5 (2) 5 0F5869 2 FRONT CORNERS C5 (2) 6 0F5870 1 DISCHARGE CENTER DUCT C5 (2) 7 0F5867 1 ROOF C5 ALUM
11 0C2454 78 SCREW THF M6-1 X 16 N WA Z/JS 12 0F2766 2 SPLITTER 13 0F3181 4 SPLITTER SHORT 14 0F3185 2 STRINGER SPLITTER C3 15 0F3416 2 SUPPORT SPLITTER C5 130KW 16 0F3949 2 INSULATION CORNER POST 17 0C2634A 1 ASSEMBLY COVER ACCESS 18 022473 5 WASHER FLAT 1/4-M6 ZINC 19 022097 1 WASHER LOCK M6-1/4 20 022127 1 NUT HEX 1/4-20 STEEL 21 0F3072 20 INSULATION RETAINMENT HANGER 22 078115 70 WASHER SELF LOCKING DOME 23 0F3949B 3 INSULATION SPLITTER 24 0F3949A 4 INSULATION SHORT LOUVER 25 0F5048D 4 VISE-ACTION LATCH SLOTTED CIR 26 0E5968 1 GASKET EXTRUDED TRIM (566” LG) 27 0F5049 4 TAB PULL 28 0F3949L 2 INSULATION SPLITTER SML 29 0F3949E 1 INSULATION ROOF TOP REAR 30 0F3890A 8 RETAINER INSULATION (740) 31 087233 2 RIVET POP .1875 X .450 SS 32 0F3949C 1 INSULATION ROOF TOP 33 0F3949D 4 INSULATION DOOR 34 0F3949G 1 INSULATION DISCHARGE DUCT 35 0F3949J 2 INSULATION CENTER SUPPORT 36 0F3949K 1 INSULATION DISCHARGE DUCT TOP 37 0F3949F 2 INSULATION INNER DUCT SIDE 38 0F3890B 4 RETAINER INSULATION (820) 39 0F3890 14 RETAINER INSULATION (450) 40 042568 4 SCREW HHC M6-1.0 X 20 G8.8 41 0912970088 2 ASSY WIRE 14 AWG 20.9" GRN/YEL 42 022447 4 WASHER SHAKEPROOF INT 1/4 43 049813 4 NUT HEX M6 X 1.0 G8 YEL CHR (1)44 077992 28 NUT HEX LOCK M6-1.0 SS NY INS 45 0912970094 2 ASSY WIRE 14 AWG 34.8" GRN/YEL 46 0F2766A 1 SPLITTER C5 47 0F3949M 1 INSULATION SPLITTER SHRT MPS 48 0F8869D 1 KEY VISE-ACTION LATCH SLOT CIR 49 0E3257 6 SCREW TH-FRM M6 W/CAP SHKPRF W
(1) ALUMINUM ENCLOSURE NOTE: ALL ENCLOSURE PANELS THAT FASTEN TO THE BASE FRAME MUST BE SECURED USING ITEM 11 & 49 THREAD FORMING FASTENER AND ITEM 44 LOCK NUT. LOCK NUT IS TO BE INSTALLED AFTER THREAD FORMING FASTENER HAS PENETRATED THROUGH EXTRUSIONS IN ENCLOSURE PANELS. ALL ROOF PANELS ARE TO BE SECURED IN THE SAME MANNER.
(2) I/N’S 1 THRU 7, REFER TO CHART BELOW FOR ENCLOSURE COLOR & MATERIAL TYPE.





































GENERAC POWER SYSTEMS STANDARD LIMITED WARRANTY FOR
COMMERCIAL PRODUCT 50kW AND ABOVE
For a period of two (2) years from the date of sale, or start-up by Authorized/Certified Generac Power Systems Dealer, or branch thereof, Generac Power Systems, Inc. will, at its option, repair or replace any part(s) which, upon examination, inspection, and testing by Generac Power Systems or an Authorized/Certified Generac Power Systems Dealer, or branch thereof, is found to be defective under normal use and service, in accordance with the warranty schedule set forth below. Any equipment that the purchaser/owner claims to be defective must be examined by the nearest Authorized/ Certified Generac Power Systems Dealer, or branch thereof. This warranty applies only to Generac Power Systems Generators used in "Standby" applications, as Generac Power Systems, Inc. has defined Standby, provided said generator has been properly installed and inspected on-site by appropriate personnel. Scheduled maintenance, as outlined by the generator owner's manual, is highly recommended. This should be performed by an Authorized/ Certified Generac Power Systems Dealer, or branch thereof. This will verify service has been performed on the unit throughout the war- ranty period.
THIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING: 1. Any unit built/manufactured prior to March 1, 2005. 2. Costs of normal maintenance (i.e. tune-ups, associated part(s), adjustments, loose/leaking clamps, installation and start-up). 3. Any failure caused by contaminated fuels, oils, coolants/antifreeze or lack of proper fuels, oils or coolants/antifreeze. 4. Units sold, rated or used for "Prime Power", "Trailer Mounted" or "Rental Unit" applications as Generac Power Systems have defined Prime Power,
Trailer Mounted or Rental Unit. Contact a Generac Power Systems Distributor for Prime Power, Trailer Mounted or Rental Unit definition and warranty. 5. Units used for prime power in place of existing utility power where utility is present or in place of utility power where utility power service does not
normally exist. 6. Failures caused by any external cause or act of God such as, but not limited to, collision, fire, theft, freezing, vandalism, riot or wars, lightning,
earthquake, windstorm, hail, volcanic eruption, water or flood, tornado, hurricane, terrorist acts or nuclear holocaust. 7. Products that are modified or altered in a manner not authorized by Generac Power Systems in writing. 8. Failures due, but not limited to, normal wear and tear, accident, misuse, abuse, negligence, or improper installation or sizing. 9. Any incidental, consequential or indirect damages caused by defects in materials or workmanship, or any delay in repair or replacement of the
defective part(s). 10. Failure due to misapplication, misrepresentation, or bi-fuel conversion. 11. Telephone, facsimile, cell phone, satellite, internet, or any other communication expenses. 12. Rental equipment used while warranty repairs are being performed (i.e. rental generators, cranes, etc.). 13. Overtime, holiday, or emergency labor. 14. Planes, ferries, railroad, busses, helicopters, snowmobiles, snow-cats, off-road vehicle or any other mode of transportation deemed abnormal. 15. Any and all expenses incurred investigating performance complaints unless defective Generac materials and/or workmanship were the direct
cause of the problem. 16. Starting batteries, fuses, light bulbs, engine fluids, and overnight freight cost for replacement part(s).
THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, SPECIFICALLY, GENERAC POWER SYSTEMS MAKES NO OTHER WARRANTIES AS TO THE MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to purchaser/owner.
GENERAC POWER SYSTEMS ONLY LIABILITY SHALL BE THE REPAIR OR REPLACEMENT OF PART(S) AS STATED ABOVE. IN NO EVENT SHALL GENERAC POWER SYSTEMS BE LIABLE FOR ANY INCIDENTAL, OR CONSEQUENTIAL DAMAGES, EVEN IF SUCH DAMAGES ARE A DIRECT RESULT OF GENERAC POWER SYSTEMS, INC. NEGLIGENCE.
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations may not apply to purchaser/ owner. Purchaser/owner agrees to make no claims against Generac Power Systems, Inc. based on negligence. This warranty gives purchaser/owner specific legal rights. Purchaser/owner also may have other rights that vary from state to state
Bulletin 0171370SVE / Printed in U.S.A. 7.05
Printed in U.S.A.