Manual Part No. 0D9057

SERVICE

MANUAL

SERIES IMPACT 36 PLUS II

Models 940-2 & 941-2

Generac Power Systems 941-2 — Models 940-2 & 941-2 diagram (page 1)
Fig. 1 · Models 940-2 & 941-2
  • P.O. Box 297
  • Whitewater, WI
  • 53190 Phone: (262) 473-5514 Fax: (262) 472-6505

Printed in U.S.A Revision A - 07/15/03

Page 2 of the Generac Power Systems 941-2 user manual — REPLACEMENT PARTS
Page 2 · click to enlarge
Page 2

SAFETY

Throughout this publication, "DANGER!" and "CAUTION!" blocks are used to alert the mechanic to special instructions concerning a particular service or operation that might be hazardous if performed incorrectly or carelessly. PAY CLOSE ATTENTION TO THEM.

!

!

These "Safety Alerts" alone cannot eliminate the hazards that they signal. Strict compliance with these spe- cial Instructions plus "common sense" are major accident prevention measures.

NOTICE TO USERS OF THIS MANUAL

This SERVICE MANUAL has been written and published by Generac to aid our dealers' mechanics and com- pany service personnel when servicing the products described herein. It is assumed that these personnel are familiar with the servicing procedures for these products, or like or similar products manufactured and marketed by Generac. That they have been trained in the recommended servicing procedures for these products, including the use of common hand tools and any special Generac tools or tools from other suppliers. Generac could not possibly know of and advise the service trade of all conceivable procedures by which a service might be performed and of the possible hazards and/or results of each method. We have not under- taken any such wide evaluation. Therefore, anyone who uses a procedure or tool not recommended by Generac must first satisfy himself that neither his nor the products safety will be endangered by the service procedure selected. All information, illustrations and specifications in this manual are based on the latest product information available at the time of publication. When working on these products, remember that the electrical system and engine ignition system are capa- ble of violent and damaging short circuits or severe electrical shocks. If you intend to perform work where electrical terminals could be grounded or touched, the battery cables should be disconnected at the battery. Any time the intake or exhaust openings of the engine are exposed during service, they should be covered to prevent accidental entry of foreign material. Entry of such materials will result in extensive damage when the engine Is started. During any maintenance procedure, replacement fasteners must have the same measurements and strength as the fasteners that were removed. Metric bolts and nuts have numbers that indicate their strength. Customary bolts use radial lines to indicate strength while most customary nuts do not have strength mark- ings. Mismatched or incorrect fasteners can cause damage, malfunction and possible injury.

REPLACEMENT PARTS

Components on Generac recreational vehicle generators are designed and manufactured to comply with Recreational Vehicle Industry Association (RVIA) Rules and Regulations to minimize the risk of fire or explo- sion. The use of replacement parts that are not in compliance with such Rules and Regulations could result in a fire or explosion hazard. When servicing this equipment, It is extremely important that all components be properly installed and tightened. If Improperly Installed and tightened, sparks could Ignite fuel vapors from fuel system leaks.

Page 3 of the Generac Power Systems 941-2 user manual — Table of Contents
Page 3 · Contents
Contents

Contents

Page 5 of the Generac Power Systems 941-2 user manual — Series Impact 36 Plus II
Page 5 · click to enlarge
Page 5
SECTIONTITLE 1.1GENERATOR FUNDAMENTALS 1.2GENERATOR MAJOR COMPONENTS 1.3OPERATIONAL ANALYSIS 1.4INSULATION RESISTANCE 1.5COMPONENTS TESTING 1.6CONTROL PANEL 1.7SHEET METAL

PART 1 GENERAL INFORMATION

COMPUTER CONTROLLED

VARIABLE SPEED RV GENERATORS

Series Impact 36 Plus II

Page 6 of the Generac Power Systems 941-2 user manual — NOTES
Page 6 · click to enlarge
Page 6

NOTES

Page 7 of the Generac Power Systems 941-2 user manual — ELECTROMAGNETIC FIELDS
Page 7 · click to enlarge
Page 7

Section 1.1 GENERATOR FUNDAMENTALS

MAGNETISM

Magnetism can be used to produce electricity and electricity can be used to produce magnetism. Much about magnetism cannot be explained by our present knowledge. However, there are certain pat- terns of behavior that are known. Application of these behavior patterns has led to the development of gen- erators, motors and numerous other devices that uti- lize magnetism to produce and use electrical energy. See Figure 1. The space surrounding a magnet is permeated by magnetic lines of force called "flux". These lines of force are concentrated at the magnet's north and south poles. They are directed away from the magnet at its north pole, travel in a loop and re- enter the magnet at its south pole. The lines of force form definite patterns which vary in intensity depend- ing on the strength of the magnet. The lines of force never cross one another. The area surrounding a magnet in which its lines of force are effective is called a "magnetic field". Like poles of a magnet repel each other, while unlike poles attract each other.

Generac Power Systems 941-2 — Section 1.1 GENERATOR FUNDAMENTALS diagram (page 7)
Fig. 2 · Section 1.1 GENERATOR FUNDAMENTALS

Figure 2. The Right Hand Rule

Generac Power Systems 941-2 — Section 1.1 GENERATOR FUNDAMENTALS diagram (page 7)
Fig. 3 · Section 1.1 GENERATOR FUNDAMENTALS

ELECTROMAGNETIC INDUCTION

An electromotive force (EMF) or voltage can be pro- duced in a conductor by moving the conductor so that it cuts across the lines of force of a magnetic field. Similarly, if the magnetic lines of force are moved so that they cut across a conductor, an EMF (voltage) will be produced in the conductor. This is the basic principal of the revolving field generator. Figure 3, below, illustrates a simple revolving field generator. The permanent magnet (Rotor) is rotated so that its lines of magnetic force cut across a coil of wires called a Stator. A voltage is then induced into the Stator windings. If the Stator circuit is completed by connecting a load (such as a light bulb), current will flow in the circuit and the bulb will light.

Figure 1. Magnetic Lines of Force

ELECTROMAGNETIC FIELDS

  • All conductors through which an electric current Is flowing have a magnetic field surrounding them. This field is always at right angles to the conductor. If a compass is placed near the conductor, the compass needle will move to a right angle with the conductor. The following rules apply:
  • The greater the current flow through the conductor, the stronger the magnetic field around the conductor.
  • The increase in the number of lines of force is directly proportional to the increase in current flow and the field is distributed along the full length of the conductor.
  • The direction of the lines of force around a conductor can be determined by what is called the "right hand rule". To apply this rule, place your right hand around the conductor with the thumb pointing in the direction of current flow. The fingers will then be pointing in the direction of the lines of force.
Generac Power Systems 941-2 — ELECTROMAGNETIC FIELDS diagram (page 7)
Fig. 4

Figure 3. A Simple Revolving Field Generator

Page 8 of the Generac Power Systems 941-2 user manual — ELECTRICAL UNITS
Page 8 · click to enlarge
Page 8

Section 1.1 GENERATOR FUNDAMENTALS

Generac Power Systems 941-2 — Section 1.1 GENERATOR FUNDAMENTALS diagram (page 8)
Fig. 5 · Section 1.1 GENERATOR FUNDAMENTALS

Figure 4. Operation of a Simple Generator

ALTERNATING CURRENT

mum negative value. Two reversals of current flow is called a cycle. The number of cycles per second is called frequency and is usually stated in "Hertz".

A simple generator consists of a coil of wires called a Stator and a magnetic field called a Rotor. As the Rotor's magnetic field cuts across the Stator coil, a voltage is induced into the Stator windings. The amount of induced voltage is equal to the strength of the magnetic field. See Figure 4. The current alternates according to the position of the Rotor's poles in relation to the position of the Stator. At 0° and again at 180°, no current flow is produced. At 90° of Rotor rotation, current flow reaches a maximum positive value. Rotor rotation to 270° brings another maximum flow of current. However, at 270° the current flow has reversed in polarity and now flows in the opposite direction.

Generac Power Systems 941-2 — ALTERNATING CURRENT diagram (page 8)
Fig. 6

ELECTRICAL UNITS

AMPERE: The rate of electron flow in a circuit is represented by the AMPERE. The ampere is the number of electrons flowing past a given point at a given time. One AMPERE is equal to just slightly more than six thou- sand million billion electrons per second. With alternating current (AC), the electrons flow first in one direction, then reverse and move in the oppo- site direction. They will repeat this cycle at regular intervals. A wave diagram, called a "sine wave" shows that current goes from zero to maximum posi- tive value, then reverses and goes from zero to maxi-

Figure 5. Alternating Current Sine Wave

VOLT: The VOLT is the unit used to measure electrical PRESSURE, or the difference in electrical potential that causes electrons :o flow. Very few electrons will flow when voltage is weak. More electrons will flow as voltage becomes stronger. VOLTAGE may be consid- ered to be a state of unbalance and current flow as an attempt to regain balance. One volt is the amount of EMF that will cause a current of 1 ampere to flow through 1 ohm of resistance.

Page 9 of the Generac Power Systems 941-2 user manual — AMPERES = VOLTS
Page 9 · click to enlarge
Page 9

Section 1.1 GENERATOR FUNDAMENTALS

If OHMS is unknown but VOLTS and AMPERES are known, use the following:

Generac Power Systems 941-2 — Section 1.1 GENERATOR FUNDAMENTALS diagram (page 9)
Fig. 7 · Section 1.1 GENERATOR FUNDAMENTALS

OHMS = VOLTS AMPERES

REACTANCE IN AC CIRCUITS

GENERAL: When direct current (DC) is flowing, the only opposi- tion to current flow that must be considered is resis- tance (ohms). This is also true of alternating current (AC) when only resistance type loads such as heating and lamp elements are on the circuit. In such a case, current will be in phase with voltage- that is, the cur- rent sine wave will coincide in time with the voltage sine wave. However, two factors in AC circuits called INDUC- TIVE and CAPACITIVE REACTANCE will prevent the voltage and current sine waves from being in phase.

Figure 6. Electrical Units

OHM: The OHM is the unit of RESISTANCE. In every circuit there is a natural resistance or opposition to the flow of electrons. When an EMF is applied to a complete circuit, the electrons are forced to flow in a single direction rather than their free or orbiting pattern. The resistance of a conductor depends on (a) its physical makeup, (b) its cross-sectional area, (c) its length, and (d) its temperature. As the conductor's tempera- ture increases, its resistance increases in direct pro- portion. One (1) ohm of resistance will permit one (1) ampere of current to flow when one (1) volt of electro- motive force (EMF) is applied.

INDUCTIVE REACTANCE: This condition exists when current lags behind volt- age (Figure 8). As current flows in a circuit, magnetic lines of force are created at right angles to the con- ductor. The continuous changes in current value (from positive to negative) cause these magnetic lines to collapse and build up continuously. The magnetic field around the conductor induces electromotive forces that cause current to keep on flowing while voltage drops. The result is a condition in which voltage leads current. When a conductor is formed into a coil, the magnetic lines of force are con- centrated in the center of the coil. This increased den- sity causes an increase in magnetically Induced EMF without increasing current Thus, coils cause inductive reactance. Inductive reactance can also be caused by placing an induction motor on the circuit which utilizes the cur- rent's magnetic field for excitation.

OHM'S LAW

A definite and exact relationship exists between VOLTS, OHMS and AMPERES. The value of one can be calculated when the value of the other two are known. Ohm's Law states that in any circuit the current will increase when voltage increases but resistance remains the same, and current will decrease when resistance Increases and voltage remains the same.

Generac Power Systems 941-2 — OHM'S LAW diagram (page 9)
Fig. 8
Generac Power Systems 941-2 — OHM'S LAW diagram (page 9)
Fig. 9

Figure 7.

If AMPERES is unknown while VOLTS and OHMS are known, use the following formula:

AMPERES = VOLTS

OHMS If VOLTS is unknown while AMPERES and OHMS are known, use the following formula:

Figure 8. Inductive Reactance

VOLTS = AMPERES x OHMS

Page 10 of the Generac Power Systems 941-2 user manual — Section 1.1 GENERATOR FUNDAMENTALS
Page 10 · click to enlarge
Page 10

Section 1.1 GENERATOR FUNDAMENTALS

CAPACITIVE REACTANCE: This condition occurs when current leads voltage (Figure 9). It might be thought of as the ability to oppose change in voltage. Capacitance exists in a circuit when certain devices are ~a) capable of storing electrical charges as voltage increases and (b) discharging these stored charges when the voltage decreases.

  • trolled by the inverter and is maintained at a steady 60 Hz signal throughout the load range. Computer controlled generator units have the ability to operate the engine over a wide range of speeds, while conventional generators will deliver correct AC frequency and voltage only at a fixed rpm. Unlike conventional AC generators, the Impact Plus unit can match engine speed to load requirements. This provides several advantages, as follows:
  • Smaller engines can be used to produce more power than on a conventional generator, since it can be allowed to run at a higher speed.
  • When the load is reduced, the engine can run at slower than the usual speeds. This improves fuel economy and reduces engine noise.
  • The Impact Plus unit can be operated closer to its peak power point at all times, because output voltage and current are functions of engine speed. This allows for a much more compact generator design.
Generac Power Systems 941-2 — Section 1.1 GENERATOR FUNDAMENTALS diagram (page 10)
Fig. 10 · Section 1.1 GENERATOR FUNDAMENTALS

IMPACT PLUS SYSTEM OVERVIEW: Figure 10 is a block diagram of the Impact Plus sys- tem. The major elements of the system are represent- ed in the diagram. Operation of the system may be described briefly as follows:

Figure 9. Capacitive Reactance

WHAT IS AN "IMPACT PLUS" UNIT?: The Impact Plus is a computer controlled generator that uses an inverter to create a superior sine wave and maintain a steady frequency. These units are dif- ferent from conventional generators in that the perfor- mance of the engine and AC generator are more accurately matched over a wide range of power needs. The Impact Plus computer controlled genera- tor provides greater efficiency of both the engine and the generator while maintaining electrical output with- in an acceptable voltage range. The frequency is con-

1. The engine is directly coupled to a permanent magnet type Rotor, so the Rotor runs at the same speed as the engine.
2. As the Rotor turns, its magnetic field cuts across the Stator windings to induce a voltage into the Stator.

Figure 10. Block Diagram of the Impact 36 Plus System

Page 11 of the Generac Power Systems 941-2 user manual — WHY VARIABLE SPEED CONTROL?
Page 11 · click to enlarge
Page 11

Section 1.1 GENERATOR FUNDAMENTALS

3. When the generator circuit breaker is turned to the “ON” position, AC voltage is delivered to the Full Bridge Rectifier. The AC voltage is rectified to DC and thus becomes DC Link voltage.

WHY VARIABLE SPEED CONTROL?

Most electrical loads will operate satisfactorily only within a relatively small voltage band. In order to pro- vide useful voltage at larger load currents, it is neces- sary to increase engine speed. In conventional AC generators, some form of voltage regulation is needed to provide correct voltage in the full range of load current. This is often accomplished by regulating excitation current to the Rotor (field) which then regulates the strength of the Rotor's mag- netic field. The voltage induced into the Stator wind- ings is proportional to the strength of the Rotor's mag- netic field. The Impact Plus computer controlled generator uses a Rotor having a fixed and permanent magnetic field. The strength of this magnetic field is fixed and cannot be regulated. The output voltage on Impact Plus computer con- trolled generators tends to droop with increasing elec- trical loads. The SYSTEM CONTROLLER maintains a constant AC output voltage by increasing engine and Rotor speed as the load current increases, to off- set this inherent voltage droop.

4. AC voltage from the stator PS1/PS2 is delivered to the inverter. This is used as the power supply for the inverter circuit board.
5. AC voltage from the stator TIM1/TIM2 is delivered to the system controller. This is used for engine speed sensing.
6. The system controller sends signals to the inverter for inverter operation.
7. The system controller senses load voltage and signals stepper motor operation to achieve required engine speed for correct voltage output.
Page 12 of the Generac Power Systems 941-2 user manual — Section 1.1 GENERATOR FUNDAMENTALS
Page 12 · click to enlarge
Page 12

Section 1.1 GENERATOR FUNDAMENTALS

Page 13 of the Generac Power Systems 941-2 user manual — !
Page 13 · click to enlarge
Page 13

Section 1.2 MAJOR GENERATOR COMPONENTS

INTRODUCTION

UPPER FAN HOUSING

Major components of the generator proper are shown in Figure 1, below. External sheet metal and other unrelated components are omitted from the drawing for clarity. These parts are:

As its name implies, this component houses and shields the upper cooling fan. See Figure 1, Item 1.

UPPER COOLING FAN

Item Description 1 Upper Fan Housing 2 Upper Cooling Fan 3 Permanent Magnet Rotor 4 Rotor Hub 5 Stator Retaining Ring 6 Stator Assembly 7 Stator Adapter 8 Engine 9 Lower Fan & Flywheel 10 Stepper Motor

The Cooling Fan draws air into the generator through slots in the Upper Fan Housing. It is fastened to and rotates with the Permanent Magnet Rotor.

PERMANENT MAGNET ROTOR

Sixteen permanent magnets have been affixed to the Rotor. A starter ring gear is welded to the Rotor. The Rotor and Hub are balanced at the factory as an assembly and must be replaced as an assembly. NOTE: The hub MUST be properly aligned during reassembly. The mounting bolt, housing opening and magnet must be properly aligned. In addition, match marks between the Hub and Rotor must be' aligned as indicated by an "ALIGN MARKS FOR BALANCE" decal. During assembly, use care to avoid damage to the Ignition Sensor.

Generac Power Systems 941-2 — PERMANENT MAGNET ROTOR diagram (page 13)
Fig. 11

!

Generac Power Systems 941-2 — ! diagram (page 13)
Fig. 12

Figure 1. Exploded View of Generator Proper

Figure 2 Permanent Magnet Rotor Assembly

Page 14 of the Generac Power Systems 941-2 user manual — ENGINE
Page 14 · click to enlarge
Page 14

Section 1.2 MAJOR GENERATOR COMPONENTS

ROTOR HUB

STEPPER MOTOR

See Figure 2 on previous page. The Rotor Hub is bal- anced with the Rotor and must be replaced with the Rotor as an assembly. Part of the engine ignition sys- tem is pressed onto the Hub and can be replaced only as part of the Rotor and Hub assembly.

The Stepper Motor (Figure 3) consists of a stepper motor along with a gear and cam arrangement which allows motor movement to change the engine carbu- retor throttle setting. The Motor is controlled by output signals from the Computer Control Circuit Board, which calculates the number of steps the stepper needs to take and generates the required signals to the Motor. The circuit board signals the Motor to actu- ate in response to changes in AC output voltage. Thus, in response to decreasing AC output voltages, the Motor will increase the throttle setting and engine speed will increase. Conversely, Increasing AC out- put voltages will cause the Motor to decrease throttle setting and engine speed will decrease.

STATOR RETAINING RING

The Stator Retaining Ring is made of die-cast alu- minum. Four hex head capscrews with lockwashers pass through holes in the Retaining Ring, to retain the Stator Assembly to the Stator Adapter (Item 7, Figure 1).

STATOR ASSEMBLY

Generac Power Systems 941-2 — STATOR ASSEMBLY diagram (page 14)
Fig. 13

The 2-phase Stator is made up of six (6) windings, with leads brought out as shown in figure 4. Figure 5 is a schematic representation of each stator winding. Note that there are two (2) power phase windings (Leads AC1, AC2, SL1 and SL2 ); a timing winding (Leads TIM1 and TIM2); a power supply winding (Leads PSI, PS2); and a dual battery charge winding (Leads 55, 66, 77).

STATOR ADAPTER

The Adapter is retained to the engine by means of four hex head capscrews. The Stator is retained to the Stator Adapter and is "sandwiched" between the Adapter and the Stator Retaining Ring.

LOWER FAN & FLYWHEEL

Figure 3. The Stepper Motor

The Lower Fan and Flywheel are retained to the engine PTO shaft by means of a conical washer and an M16-1.50 hex nut. When assembling, tighten the flywheel nut to 75 foot-pounds.

ENGINE

The engine is a single cylinder, 220 cc, overhead valve type manufactured by Generac® Power Systems, Inc.

Figure 4. Stator Pictorial View

Page 15 of the Generac Power Systems 941-2 user manual — Section 1.2 MAJOR GENERATOR COMPONENTS
Page 15 · click to enlarge
Page 15

Section 1.2 MAJOR GENERATOR COMPONENTS

Generac Power Systems 941-2 — Section 1.2 MAJOR GENERATOR COMPONENTS diagram (page 15)
Fig. 14 · Section 1.2 MAJOR GENERATOR COMPONENTS

Figure 5. Schematic- Stator Windings

Page 16 of the Generac Power Systems 941-2 user manual — Section 1.2 MAJOR GENERATOR COMPONENTS
Page 16 · click to enlarge
Page 16

Section 1.2 MAJOR GENERATOR COMPONENTS

Page 17 of the Generac Power Systems 941-2 user manual — OPERATIONAL DESCRIPTION
Page 17 · click to enlarge
Page 17

Section 1.3 OPERATIONAL ANALYSIS

GENERAL

b.The STATOR POWER SUPPLY WINDING with

output leads PS1-PS2. c. The STATOR TIMING WINDING (output leads

Figure 1, below, is a block diagram of the Impact Plus computer controlled RV generator. The diagram is Intended only for the purpose of illustrating generator operation. Refer to the actual wiring diagram for wiring interconnections.

TIM1-TIM2). d.STATOR BATTERY CHARGE WINDING with

output leads 55, 66 and 77.

3. STATOR BATTERY CHARGE WINDING output is delivered to the unit battery via a BATTERY CHARGE RECTIFIER (BCR) and a 1 OHM, 50 WATT RESISTOR. The circuit is completed through the battery to frame ground and back to the BATTERY CHARGE WINDING via Wire 55.

OPERATIONAL DESCRIPTION

1. The Impact Plus is a computer controlled generator that uses an inverter to create a superior sine wave and maintain a steady frequency of 60 Hz. The PERMANENT MAGNET ROTOR is directly coupled to the ENGINE and rotates at the same speed as the engine.
4. Stator timing winding output is delivered to the A6060 circuit board. The timing winding output is used to determine engine rpm.
2. As the ROTOR turns, its magnetic field cuts across a number of STATOR windings, to induce a voltage into those windings. A voltage is induced into the following STATOR windings:
5. The stator power supply winding output is delivered to the inverter. This is the power supply for operation of the inverter.
6. Stator power winding output (phase 1 and 2) is delivered to two separate bridge rectifiers, where it is rectified to DC. This becomes the DC link voltage and is delivered to the inverter.

a.Phase 1 and 2 of the STATOR POWER WIND-

INGS (output leads AC1-AC2 and SL1-SL2).

Figure 1. Block Diagram- A Generator System

Page 18 of the Generac Power Systems 941-2 user manual — Section 1.3 OPERATIONAL ANALYSIS
Page 18 · click to enlarge
Page 18

Section 1.3 OPERATIONAL ANALYSIS

OPERATIONAL DESCRIPTION (CONTINUED)

7. The A6060 circuit board controls all functions of the generator, i.e.:

a.Engine DC control system b.Stepper motor operation

(1) If voltage is low, the board will signal a

STEPPER MOTOR to change engine throt- tle setting and increase speed until the desired voltage level is reached. (2) If voltage goes high, the board will signal

the STEPPER MOTOR to reduce engine throttle setting until the desired voltage level is obtained. c. Output signals for operation of inverter.

Page 19 of the Generac Power Systems 941-2 user manual — PREPARATION FOR TESTS
Page 19 · click to enlarge
Page 19

Section 1.4 INSULATION RESISTANCE

DIRT AND MOISTURE

!

If moisture is permitted to remain in contact with the generator Stator windings, some of it will be retained in voids and cracks of the winding insulation. This can eventually cause a reduction in insulation resistance and generator output may be affected. Winding insulation in Generac generators is moisture resistant. However, prolonged exposure to water, high humidity, salt air, etc., will gradually reduce the resistance of winding insulation. Dirt can make the problem even worse, since it tends to hold moisture into contact with the windings. Salt, as from sea air, can also worsen the problem, since salt tends to absorb moisture from the air. When salt and moisture combine, they make a good electrical conductor. Because of the detrimental effects of water, dirt and salt, the generator should be kept as dry and as clean as possible. Stator windings should be tested periodi- cally using a Hi-Pot tester or a Megohmmeter. If insu- lation resistance is low, drying of the unit may be nec- essary. If resistance is still low after drying, the defec- tive Stator should be replaced.

STATOR LEADS

The following leads are brought out of the Stator and connected to various components in the unit:

WIRE# COLOR CONNECTS TO AC1 Grey CB1A AC2 Yellow BR1 SL1 Orange CB1B SL2 Brown BR3 TIM1 Orange A6060 Circuit Board TIM2 Grey A6060 Circuit Board PS1 Red J1 PS2 Black J1 77 Brown Battery Charge Rectifier BCR 66 Brown Battery Charge Rectifier BCR 55 Black Grounding Terminal

INSULATION RESISTANCE TESTERS

One kind of insulation resistance tester is shown in Figure 1, below. Other types are commercially avail- able. The type shown has a "Breakdown" lamp which turns on to indicate an insulation breakdown during the test. One common type of tester is the "Megohmmeter" which measures resistance in "Megohms".

Figure 2. Stator Leads

PREPARATION FOR TESTS

See Stator leads CHART above. Disconnect and iso- late all Stator leads. ALL STATOR LEADS MUST BE DISCONNECTED AND ISOLATED BEFORE START- ING THE TESTS.

Figure 1. One Kind of Hi-Pot Tester

Page 20 of the Generac Power Systems 941-2 user manual — CLEANING THE GENERATOR
Page 20 · click to enlarge
Page 20

Section 1.4 INSULATION RESISTANCE

TEST ALL STATOR WINDINGS TO GROUND

4. POWER PHASE TO BATTERY CHARGE WINDINGS:Connect one tester probe to Stator Lead AC1, the other probe to Stator lead No. 55. Apply 1000 volts. If breakdown Is indicated, the windings are shorted together. Repeat again with stator lead SL1.

Connect the ends of all Stator leads together. Make sure none of the leads are touching any terminal or any part of the generator. Connect one Tester probe to the junction of all Stator leads; the other Tester probe to a clean frame ground on the Stator. Apply a voltage of 1000 volts for about 1 second. Follow the tester manufacturer's instructions carefully. Some "Hi-Pot" testers are equipped with a "Breakdown" light which will turn ON to indicate an insulation breakdown. A "Megger" (Megohmmeter) will indicate the "megohms" of resistance. Normal Stator winding insulation resistance is on the order of "millions of ohms" or "megohms". The MINIMUM acceptable insulation resistance reading for Stators can be calcu- lated using the following formula.

5. TIMING TO POWER SUPPLY WINDING:- Connect one tester probe to Stator lead No. TM1, the other test probe to Stator lead No. PS1. Apply 1000 volts. If breakdown is indicated, the windings are shorted together.
6. TIMING TO BATTERY CHARGE WINDING:- Connect one test probe to Stator lead No. TIM1, the other test probe to Stator lead No. 55. Apply 1000 volts. If breakdown is indicated the windings are shorted together.
7. POWER SUPPLY TO BATTERY CHARGE WINDING:Connect one test probe to Stator lead No. PS1, the other probe to Stator lead No. 55. Apply 1000 volts. If breakdown is indicated, the windings are shorted together.

MINIMUM INSULATION = GENERATOR RATED VOLTS +1 RESISTANCE 1000 (in “megohms”)

EXAMPLE: Generator rated voltage Is "120 VAC". Divide 120 by 1000 to obtain "0.12". Add "1" to obtain "1.12". Minimum Insulation resistance for the unit Is "1.12 megohms".

RESULTS OF TESTS

1. If testing indicates that Stator windings are shorted to ground, the Stator should be cleaned and dried. The insulation resistance tests should then be repeated. If, after cleaning and drying, the Stator again fails the test, replace the Stator assembly.

TEST FOR SHORTS BETWEEN WINDINGS

Figure 2 on the previous page shows the Stator leads that are brought out of the Stator. Figure 3 is a schematic representation of the eight (8) Stator wind- ings. To test for shorts between windings, proceed as follows:

2. If testing indicates that a short between windings exists, clean and dry the Stator. Then, repeat the tests. If Stator fails a second test (after cleaning and drying), replace the Stator assembly.
1. Make sure all Stator output leads are isolated from each other and from the frame.

CLEANING THE GENERATOR

2. POWER PHASE TO TIMING WINDINGS:- Connect one tester probe to Stator lead AC1, the other test probe to Stator lead TIM1. Apply a voltage of 1000 volts. The Tester will indicate a breakdown if the windings are shorted together. Repeat again with stator lead SL1.

GENERAL: If testing indicates that the insulation resistance is below a safe value, the winding should be cleaned. Proper cleaning can be accomplished only while the generator is disassembled. The cleaning method used should be determined by the type of dirt to be removed. Be sure to dry the unit after it has been cleaned. An electric motor repair shop may be able to assist with cleaning. Such shops are often experi- enced in special problems (sea coast, marine, wet- land applications, etc.).

3. POWER PHASE TO POWER SUPPLY WINDINGS: Connect one tester probe to Stator lead AC1, the other tester probe to Stator lead PS1. Apply 1000 volts. If a breakdown Is indicated, the windings are shorted together. Repeat again with stator lead SL1.
Page 21 of the Generac Power Systems 941-2 user manual — DRYING THE GENERATOR
Page 21 · click to enlarge
Page 21

Section 1.4 INSULATION RESISTANCE

Generac Power Systems 941-2 — Section 1.4 INSULATION RESISTANCE diagram (page 21)
Fig. 15 · Section 1.4 INSULATION RESISTANCE

!

!

DRYING THE GENERATOR

GENERAL: If testing indicates that the insulation resistance of a winding Is below a safe value, the winding should be dried before operating the unit Some recommended drying methods include (a) heating units and (b) forced air.

Figure 3. Schematic - Stator Windings

HEATING UNITS: If drying is needed, the generator can be enclosed in a covering. Heating units can then be installed to raise the temperature about 15°-18° F. (8°-10° C.) above ambient.

USING SOLVENTS FOR CLEANING: A solvent is generally required when dirt contains oil or grease. Only petroleum distillates should be used to clean electrical components. Recommended are safety type petroleum solvents having a flash point greater than 100° F. (38° C.). Use a soft brush or cloth to apply the solvent. Use care to avoid damaging magnet wire or winding insu- lation. After cleaning, dry all components thoroughly with moisture-free, low pressure compressed air.

FORCED AIR: Portable forced air heaters can be used to dry the generator. Direct the heated air into the generator's air intake openings. Run the unit at no-load. Air tem- perature at the point of entry into the generator should not exceed 150° F. (66° C.).

Page 22 of the Generac Power Systems 941-2 user manual — Section 1.4 INSULATION RESISTANCE
Page 22 · click to enlarge
Page 22

Section 1.4 INSULATION RESISTANCE

Page 23 of the Generac Power Systems 941-2 user manual — TESTING POWER PHASE WINDINGS:
Page 23 · click to enlarge
Page 23

Section 1.5 COMPONENTS TESTING

INTRODUCTION

1.Disconnect the following wires: a. Lead "AC1" (Grey) at CB1A. b. Lead "AC2" (Yellow) at BR1. c. Lead "SL1 " (Orange) at CB1B. d. Lead "SL2" (Brown) at BR3. 2.Make sure all of the disconnected leads are iso- lated from each other and are not touching the frame during the test. 3.Set a VOM to its "Rx1" scale and zero the meter. 4.Connect one test lead to AC1 and one test lead to AC2. Note the resistance reading. 5.Connect one test lead to SL1 and one test lead to SL2. Note the resistance reading.

Problems that occur In the computer-controlled RV generator generally involve the following systems or components:

1. The engine.
2. The Speed Control System.
3. The AC Generator.
4. Battery Charge Circuit.
5. A6060 Circuit Board.
6. Wiring Harness and Front Panel.

This Section will discuss test procedures for the fol- lowing components. Also see Part 8 of this Manual, "TROUBLESHOOTING".

NOMINAL RESISTANCEPOWER PHASE WINDINGS

0.414 to 0.465 ohm

1. The AC Generator (Stator).
2. Battery Charge Circuit.
3. A6060 Circuit Board.

STATOR ASSEMBLY

GENERALFor additional information on the Stator, refer to the following:
1. "Stator Assembly" on Page 1.2-2.
2. Section 1.4, "INSULATION RESISTANCE".

SYMPTOMS OF STATOR FAILURE: If the engine starts but the Stepper Motor does not move, and shutdown occurs after several seconds, look for broken or shorted timing windings (Wires TIM1 and TIM2).

Figure 1. Stator Leads

B.To test the Power Phase windings for a "short-to-ground" con-

  • TESTING THE STATOR WITH A VOM: A Volt-Ohm-Milliammeter (VOM) can be used to test the Stator windings for the following faults:
  • An open circuit condition.
  • A "short-to-ground" condition.
  • A short circuit between windings. NOTE: The resistance of Stator windings Is very low. Some meters will not read such a low resistance and will simply Indicate "continuity" Recommended Is a high quality, digital type meter capable of reading very low resistances.

dition, proceed as follows:

1.Make sure all leads are Isolated from each other and are not touching the frame. 2.Set a VOM to its "Rx10,000" or "Rx1K" scale and zero the meter. 3.Connect one VOM test lead to the terminal end of Stator Lead "AC1”, the other test lead to a clean frame ground on the Stator. a. The meter should read "infinity". b. Any reading other than "infinity" indicates a "short-to-ground" condition. c. Repeat #3 again using Stator Lead “SL1.”

TESTING POWER PHASE WINDINGS:

A.Refer to Figures 1 and 2 on this page and the next. To test the

Power Phase windings for an open circuit condition, proceed as follows:

Page 24 of the Generac Power Systems 941-2 user manual — NOMINAL RESISTANCE POWER SUPPLY WINDING
Page 24 · click to enlarge
Page 24

Section 1.5 COMPONENTS TESTING

STATOR ASSEMBLY (CONTINUED)

TESTING THE TIMING WINDING:

A.To test the Stator Timing winding for an open circuit condition,

Generac Power Systems 941-2 — Section 1.5 COMPONENTS TESTING diagram (page 24)
Fig. 16 · Section 1.5 COMPONENTS TESTING

proceed as follows:

1.Disconnect the 2-pin connector from "J5" of the A6060 circuit board. See Figure 3. a. Stator lead TIM1 (Orange) connects to Pin 1 of the “J5” connector. b. Stator lead TIM2 (Gray) connects to Pin 2 of the “J5” connector. 2.Set a VOM to its "Rx1" scale and zero the meter. 3.Connect one VOM test lead to Pin 1 (Lead TIM1 Orange); connect the. other test lead to Pin 2 (Lead TIM2- Gray). The meter should Indicate the Stator Timing winding resistance.

NOMINAL RESISTANCE STATOR TIMING WINDING

0.102-0.116 ohm

B.To test the Timing winding for a "short-to-ground" condition,

proceed as follows:

1.Set the VOM to its "Rx10,000" or "Rx1 K" scale and zero the meter. 2.Connect one VOM test lead to Pin 1 of the 2-pin connector (Lead TIM1-Orange). 3.Connect the other test lead to a clean frame ground on the Stator. The meter should read "infinity". Any reading other than "infinity" indi- cates the Timing winding is shorted to ground.

Figure 2. Schematic- Stator Windings

TESTING POWER SUPPLY WINDINGS:

A.To test the Power Supply winding for an open circuit condition,

proceed as follows:

1.Disconnect the 2-wire power supply from the generator. See Figure 3. 2.Set a VOM to its "Rx1" scale and zero the meter. 3.Connect one VOM test lead to Lead PS1- Red, the other test lead to Lead PS2 - Black. The meter should indicate the resistance of the Power Supply winding.

SHORT CIRCUIT BETWEEN WINDINGSTo test for a short circuit between windings, proceed as follows:

1.Set a VOM to its "Rx10,000" or "Rx1K" scale and zero the meter. 2.Connect one meter test lead to Stator lead PSi (Red). 3.Connect the remaining test lead to Stator lead AC1 (Grey). The meter should read "infinity". Any reading other than "infinity" indicates a shorted condition and the Stator should be replaced. 4.Connect one VOM test lead to Stator lead AC1, the other test lead to Stator lead 77. The VOM should read "infinity". 5.Connect one VOM test lead to Stator lead AC1, the other test lead to Stator lead TIM1. The meter should read "infinity". 6.Connect one test lead to Stator lead PSI, the other to Stator lead TIM1. "Infinity" should be indicated.

NOMINAL RESISTANCE POWER SUPPLY WINDING

0.206-0.227 ohm

B.To test the Power Supply winding for a "short-to-ground" condi-

tion, proceed as follows:

1.Set the VOM to its "Rx10,000" or "Rx1 K" scale and zero the meter. 2.Connect one VOM test lead to Lead PS1 - Red. Connect the other test lead to a clean frame ground on the Stator. The meter should read "infinity.”

Page 25 of the Generac Power Systems 941-2 user manual — TESTING THE BATTERY CHARGE CIRCUIT
Page 25 · click to enlarge
Page 25

Section 1.5 COMPONENTS TESTING

7.Connect one test lead to Stator lead PS1, the other to Stator lead 77. The VOM should read "infinity". 8.Connect one VOM test lead to Stator lead TIM1, the other test lead to Stator lead 77. "Infinity" should be Indicated.

Generac Power Systems 941-2 — Section 1.5 COMPONENTS TESTING diagram (page 25)
Fig. 17 · Section 1.5 COMPONENTS TESTING

TESTING THE BATTERY CHARGE CIRCUIT

GENERAL: The Stator is equipped with dual battery charge wind- ings. These windings deliver an AC output to a Battery Charge Rectifier (BCR) which rectifies it (changes it to direct current or DC). The direct current is delivered to the unit battery, to maintain the battery in a charged state while the unit is running.

Figure 4. Battery Charge Circuit

TESTING THE BATTERY CHARGE CIRCUITTest the Battery Charge winding as follows:
Generac Power Systems 941-2 — TESTING THE BATTERY CHARGE CIRCUIT diagram (page 25)
Fig. 18
1. Disconnect Wire 77 at the Battery Charge Rectifier (BCR).
2. Disconnect Stator output Wire 66 at the Battery Charge Rectifier (BCR).
3. Disconnect Wire 55.
4. Set a VOM to its "Rx1 " scale and zero the meter.
5. Connect the VOM test leads across Wires 77 and 55, then across Wires 66 and 55. Note the resistance reading in both cases. Replace Stator Assembly, if defective.

BATTERY CHARGE WINDING RESISTANCE ACROSS WIRES 66 TO 55 = 0.095-0.108 Ohm ACROSS WIRES 77 TO 55 = 0.095-0.108 Ohm

Figure 3. Battery Charge Windings and Rectifier

SYMPTOMS OF CIRCUIT FAILURE: It is difficult to determine if the battery charge circuit is operating without testing for correct voltage. If you suspect the battery charge circuit Is defective, the fol- lowing symptoms will usually point to a cause of the problem. See Figure 4.

6. Use a VOM to measure AC voltage at the Wires 66 and 77 terminals of the Battery Charge Rectifier, with the unit running. If no AC voltage is measured, an open circuit exists in the wire 66 or 77 circuit.
7. With engine running, use a VOM to check for DC voltage between the Battery Charge Rectifiers Wire 55 and frame ground. If AC voltage was present in step 6, but DC voltage is NOT present in this step, the Battery Charge Rectifier (BCR) is defective.
1. If no AC voltage can be measured across Stator connections at the Battery Charge Rectifier (BCR), an open circuit condition probably exists in Wire 66 (Brown), or Wire 77 (Brown).
2. If AC voltage (s available to the Wire 66 and 77 terminals at the battery Charge Rectifier, but no voltage or a low voltage is measured between the BCR's Wire 55 terminal and ground, the Battery Charge Rectifier (BCR) is defective.
Page 26 of the Generac Power Systems 941-2 user manual — Section 1.5 COMPONENTS TESTING
Page 26 · click to enlarge
Page 26

Section 1.5 COMPONENTS TESTING

Page 27 of the Generac Power Systems 941-2 user manual — **ITEMS #49, 65 & 66-HARNESSESNOT SHOWN FOR CLARITY
Page 27 · click to enlarge
Page 27

Section 1.6 CONTROL PANEL

CONSTRUCTION

COMPONENTS

The panel is constructed of sheet metal and includes a panel box, a panel back cover and a front control panel. The panel box is retained to an engine-genera- tor divider plate by five M5 screws. Removal of these screws will permit the panel to be removed from the divider plate and set out of the way with connecting wires still attached. This will allow access to compo- nents housed in the control panel.

A heat sink bracket is attached to the engine-genera- tor divider plate, for attachment of a heat sink to which four diode assemblies are mounted. See Items 26 and 31 in the Exploded View of Control Panel. Other components are also shown in the Exploded View. Many of these components are part of the "ENGINE ELECTRICAL SYSTEM" (Part 6 of this manual).

3 4 41 16

25 23 22 21

**ITEMS #49, 65 & 66-HARNESSESNOT SHOWN FOR CLARITY

ITEM QTY. DESCRIPTION 1 7 M5-0.8 x 12MM PHILLIPS PAN HD. MACH. SCR. 2 1 BOX, CONTROL TOP 3 1 BOX, CONTROL PANEL 4 1 #10-32 x 1" PHILLIPS PAN HD. MACH. SCR. 5 1 #10-32 HEX NUT 6 8 TAPTITE M5- .8 x 10MM 7 1 SNAP BUSHING 10 1 CIRCUIT BREAKER,15A. 13 6 LOCK WASHER-M5 14 10 M4-0.7 x 16MM 16 2 M4-0.7 HEX NUT 18 4 M4 FLAT WASHER 19 8 M5 FLAT WASHER 20 1 CONTROL PANEL, FRONT 21 1 RUBBER GROMMET 22 1 SWITCH, SPDT ROCKER 23 1 SWITCH, SPSTMOM ROCKER 24 1 FUSE, 7.5A. AGC 25 1 FUSE HOLDER 26 1 EXTRUSION, CONTROLLER 27 1 RECTIFIER, BATTERY CHARGE 28 14 LOCK WASHER-M4 30 1 PANEL DECAL 31 4 DIODE, DUAL 30A 32 1 ASSEMBLY, PCB CCG 33 4 PHMS M3-.05 x 10MM 34 4 LOCK WASHER-M3 35 1 RESISTOR, POWER 1 OHM

ITEM QTY. DESCRIPTION 36 2 BUS BAR, OUTER 37 4 TAPTITE M6- 1.0 x 10MM 38 1 BRACKET, HEAT SINK-PCB 41 1 TERMINAL BLOCK 43 4 BUS BAR, INNER 44 1 GROUND WIRE 45 1 DC POWER HARNESS 46 1 REMOTE PANEL HARNESS 47 1 SNAP BUSHING 48 1 CLAMP, CONTROL PANEL HARNESS 49 1 HARNESS, CONTROL PANEL 50 4 #6-32 x 1/4" PHILLIPS ROUND HD. MACH. SCREW 51 1 RUBBER U-CHANNEL 3.5 FT 52 4 M4-0.7 x 10MM HEX HEAD CAPSCREW 53 1 HOUR METER 57 4 PPHMS 10-32 x 3/8" LG 58 1 BUS BAR, CENTER 59 1 BLACK TIE WRAP, 7" LG 60 4 SHAKEPROOF EXT. #10 61 1 INVERTER ASSEMBLY 62 1 WIRE HARNESS 63 2 M6 FLAT WASHER 64 1 WIRE HARNESS-HEATSINK TO PCBI 65 1 HARNESS-PCBI TO PANEL 66 1 HARNESS-HEATSINK TO TERM. BLOCK 69 2 M3-0.5 NUT

Figure 1. Exploded View of Control Panel

Show 4 more labels / short text on this page
36 43 44 · 20 24 25 · 60 10 50 · 1 13 30
Page 28 of the Generac Power Systems 941-2 user manual — Section 1.6 CONTROL PANEL
Page 28 · click to enlarge
Page 28

Section 1.6 CONTROL PANEL

Page 29 of the Generac Power Systems 941-2 user manual — Section 1.7 SHEET METAL
Page 29 · click to enlarge
Page 29

Section 1.7 SHEET METAL

GENERAL

See "Exploded View of Sheet Metal" on next page. A DIVIDER PLATE (Item 1) separates the AC generator components from the engine. The engine Itself is enclosed by a BASE HOUSING WRAPPER (Item 4), a FRAME (Item 24), and a BELLY PAN (Item 23). These components are sealed by means of rubber SEALS (Items 3), to prevent

The LOWER FAN attaches to the engine shaft and is enclosed in a LOWER FAN HOUSING (Item 19). Air is drawn Into the enclosed area around the engine and forced out of the LOWER FAN HOUSING. Removal of sheet metal will be necessary for many repairs and for replacement of most parts.

Generac Power Systems 941-2 — Section 1.7 SHEET METAL diagram (page 29)
Fig. 19 · Section 1.7 SHEET METAL

Impact Plus Generator

Page 30 of the Generac Power Systems 941-2 user manual — Section 1.7 - SHEET METAL
Page 30 · click to enlarge
Page 30
Generac Power Systems 941-2 — Section 1.7 - SHEET METAL diagram (page 30)
Fig. 20 · Section 1.7 - SHEET METAL
Page 31 of the Generac Power Systems 941-2 user manual — Section 1.7 SHEET METAL
Page 31 · click to enlarge
Page 31

Section 1.7 SHEET METAL

PARTS LIST FOR SHEET METAL (GASOLINE UNITS)

ITEM QTY DESCRIPTION 1 1 PLATE, DIVIDER 2 2 M6-1.0 HEX NUT 3 1 SEAL RUBBER EXTRUSION 3.5 FT 4 1 WRAPPER, BOX 5 31 TAPTITE, M5- .8 x 10MM LONG 6 2 MOUNTING RAILS 7 12 M8 LOCK WASHER 8 4 M8-1.25 x 35MM HEX HD. CAPSCR. 9 2 HHCS M5-0.8 x 40MM 12 1 SPARK ARRESTOR 13 1 U-BOLT, W/SADDLE & NUTS 17 1 DEFLECTOR, AIR OUT 18 1 ASSEMBLY, MUFFLER 19 1 HOUSING, LOWER FAN 20 1 SKIRT, CARB. BAFFLE 21 1 COVER, ROCKER COVER 22 1 SKIRT, SPARK PLUG SIDE 23 1 PAN, BELLY 24 1 FRAME 25 1 GROUND STRAP 26 1 PLATE, BASE COVER 27 1 PUMP, FUEL 28 1 BARBED 90 1/8" x 1/4" 29 3 HEX NUT 1/4"-20 30 7 LOCK WASHER-1/4"-M6 31 1 CONTACTOR, STARTER 32 1 BOOT, CONTACTOR 33 1 SEAL, OIL FILTER HOLE 34 1 RETAINER, SEAL 35 4 M8 FLAT WASHER 36 1 1/4" FUEL LINE-4" LONG 37 5 1/4" HOSE CLAMP 38 1 SNAP BUSHING 39 4 SPECIAL LOCK WASHER, M5 40 2 #8 HEX NUT 41 2 #8 LOCK WASHER

ITEM QTY DESCRIPTION 42 2 HEX HD. CAPSCR. M6-1.0 x 16MM- W/LOCKWASHER 44 3 SPECIAL LOCK WASHER, M6 45 1 GROUND STRAP, UNIT 47 1 1/8" x 3/16" NPT 90 DEG. BARBED FITTING 48 1 BRACKET, MUFFLER HANGER 49 1 1/4" FUEL LINE (8" LONG) 50 1 3/16" CARBURETOR LINE (4" LONG) 51 1 FUEL FILTER 53 1 STARTER CONTACTOR GROUND WIRE 54 1 SEAL, WASHER EXHAUST PIPE 57 1 PANEL, WRAPPER BOX 59 13 CRIMPTITE #10-24 x 1/2" 60 1 HEX HD. CAPSCR., M5-0.8 x 12 G8.8 61 2 CUSTOMER MOUNTING BRACKET 62 4 VIBRATION MOUNT 63 2 EARTHING STRAP 64 8 HEX NUT M8 65 3 VIBRATION MOUNT 67 2 TAPTITE 1/4"-20 x 1-1/4" 68 2 TAG, REMOVE BOLT 69 6 FLAT WASHER #10-M5 70 1 BRACKET, IGNITION SYSTEM 71 2 SPACER, IGNITION COIL 72 1 MODULE, IGNITION 73 1 ASSEMBLY, IGNITION COIL 74 2 M6-1.0 x 35MM HEX HD. CAPSCREW 75 4 M6-1.0 HEX NUT 76 2 M5-0.8 x 12MM-PPHMS 77 2 M5-0.8 HEX NUT 78 4 LOCK WASHER M5 79 1 RUBBER "U" CHANNEL 0.5 FT 80 1 CRIMPTITE #10-24 x 3/8" 81 1 COVER, IGNITION SYSTEM

Page 32 of the Generac Power Systems 941-2 user manual — Section 1.7 - SHEET METAL
Page 32 · click to enlarge
Page 32
Generac Power Systems 941-2 — Section 1.7 - SHEET METAL diagram (page 32)
Fig. 21 · Section 1.7 - SHEET METAL
Page 33 of the Generac Power Systems 941-2 user manual — Section 1.7 SHEET METAL
Page 33 · click to enlarge
Page 33

Section 1.7 SHEET METAL

PARTS LIST FOR SHEET METAL (GASOLINE UNITS)

ITEM QTY DESCRIPTION 1 1 PLATE, DIVIDER 2 32 CRIMPTITE 10-24 x 1/2" 3 3.5' SEAL, RUBBER EXTRUSION 4 1 BOX, WRAPPER 5 31 TAPTITE, M5-.8 x 10MM 6 2 MOUNTING RAILS 7 12 M8 LOCK WASHER 8 4 M8-1.25 x 35MM HEX HD. CAPSCR. 9 3 HHCS M5-0.8 x 40MM 11 1 WRAPPER, END PANEL 12 1 SPARK ARRESTER 17 1 DEFLECTOR, AIR OUT 18 1 ASSEMBLY, MUFFLER 19 1 HOUSING, LOWER FAN 20 1 SKIRT, CARB. BAFFLE 21 1 COVER, ROCKER COVER 22 1 SKIRT, SPARK PLUG SIDE 23 1 PAN, BELLY 24 1 FRAME 25 1 GROUND STRAP 26 1 PLATE, BASE COVER 27 1 BARBED EL 90 3/8NPT X 3/8 VS 29 5 HEX NUT, 1/4"-20 30 9 LOCK WASHER-1/4"-M6 31 1 CONTACTOR, STARTER 32 1 BOOT, CONTACTOR 33 1 SEAL, OIL FILTER HOLE 34 1 RETAINER, SEAL 35 4 FLAT WASHER-M8 36 1 REGULATOR 37 1 HOSE CLAMP #5.5 38 1 SNAP BUSHING 39 2 SPECIAL LOCK WASHER, M5 40 2 #8-32 HEX NUT 41 2 #8 LOCK WASHER 42 2 HEX HD. CAPS., M6-1.0 x 16MM-W/L- WASHER 43 7 FLAT WASHER #10/M5

ITEM QTY DESCRIPTION 44 3 SPECIAL LOCK WASHER, M6 45 1 GROUND STRAP, UNIT 47 1 HOSE-3/8" I.D. x 11-1/2" LONG 48 1 BRACKET, MUFFLER HANGER 49 2 STREET ELBOW 45 DEG. 3/4" NPT 50 1 PIPE NIPPLE 3/4" x 2" 51 2 U BOLT W / SADDLE & 2-NUTS 53 1 STARTER CONTACTOR GROUND WIRE 54 1 SEAL, WASHER EXHAUST PIPE 55 1 FUEL SOLENOID 12V DC 57 2 5/16" FLAT WASHER 58 1 BRACKET L/P 59 2 CAPSCR., HEX HD.-1/4"-20 x 1/2" 60 1 LP HOOK-UP FITTING 61 2 CUSTOMER MOUNTING BRACKET 62 4 VIBRATION MOUNT 63 2 EARTHING STRAP 64 8 HEX NUT-M8 65 3 VIBRATION MOUNT 66 1 COVER, IGNITION BRACKET 67 1 1/4"-20 TAPTITE 1-1/4" 68 1 TAG, BOLT REMOVAL 70 1 BRACKET, IGNITION SYSTEM 71 2 SPACER, IGNITION COIL 72 1 MODULE, IGNITION 73 1 ASSEMBLY, IGNITION COIL 74 2 M6-1.0 x 35MM HEX HD. CAPSCREW 75 4 M6-1.0 HEX NUT 76 2 M5-0.8 x 12MM PHILLIPS PAN HD. MACH. SCR. 77 2 M5-0.8 HEX NUT 78 5 LOCK WASHER, M5 79 .5 RUBBER "U" CHANNEL 80 1 CRIMPTITE #10-24 x 3/8" 81 1 WIRE ASSEMBLY, BLOCKING DIODE

Page 34 of the Generac Power Systems 941-2 user manual — Section 1.7 SHEET METAL
Page 34 · click to enlarge
Page 34

Section 1.7 SHEET METAL

Page 35 of the Generac Power Systems 941-2 user manual — SECTION TITLE
Page 35 · click to enlarge
Page 35

PART 2 ENGINE MECHANICAL

SECTION TITLE

2.1 GENERAL INFORMATION

2.2 VALVE TRAIN

2.3 PISTON, RINGS, CONNECTING ROD

COMPUTER CONTROLLED

2.4 CRANKSHAFT & CAMSHAFT

VARIABLE SPEED RV GENERATORS

Series Impact 36 Plus

Page 36 of the Generac Power Systems 941-2 user manual — NOTES
Page 36 · click to enlarge
Page 36

NOTES

Page 37 of the Generac Power Systems 941-2 user manual — 4-CYCLE ENGINE THEORY
Page 37 · click to enlarge
Page 37

Section 2.1 GENERAL INFORMATION

INTRODUCTION

Generac Power Systems 941-2 — Section 2.1 GENERAL INFORMATION diagram (page 37)
Fig. 22 · Section 2.1 GENERAL INFORMATION

The engine used on Impact 36 plus Series recreational vehicle AC generators is a Generac Series GV-220, vertical shaft, single cylinder, overhead valve type. These engines are not equipped with a mechanical engine governor. Instead. variable engine speeds are controlled by a computer circuit board. The circuit board signals a stepper motor to move the carburetor throttle linkage.

4-CYCLE ENGINE THEORY

Figure 1. Intake Stroke

GENERAL: Series GV-220 engines require four (4) strokes or cycles to complete one power cycle. This is often called the "4-stroke, 5-event" cycle. The 4 strokes and 5 events that occur are (1) Intake, (2) compression, (3) Ignition, (4) power and (5) exhaust

Generac Power Systems 941-2 — 4-CYCLE ENGINE THEORY diagram (page 37)
Fig. 23

INTAKE STROKE (FIGURE 1): The intake valve is open. The exhaust valve is closed. The piston travels downward, creating a suction which draws the air-fuel mixture from the carburetor into the cylinder and just above the piston.

COMPRESSION STROKE (FIGURE 2): As the piston reaches bottom dead center (BDC), the intake valve closes. The exhaust valve remains closed, as well. The piston starts to move outward in the cylinder. Since both valves are closed, the air-fuel mixture in the cylinder is compressed.

Figure 2. Compression Stroke

Generac Power Systems 941-2 — 4-CYCLE ENGINE THEORY diagram (page 37)
Fig. 24

POWER STROKE (FIGURE 3): Both valves remain closed. At some point before the piston reached top dead center (TDC), the spark plug fires to Ignite the fuel-air mixture. The piston moves to its top dead center position and the burning, expand- ing gases of combustion force the piston downward.

EXHAUST STROKE (FIGURE 4): The expanding gases of combustion force the piston downward to its bottom dead center (BDC) position. The exhaust valve then opens, as the piston starts its movement toward top dead center (TDC). Piston movement then forces the exhaust gases out through the open exhaust valve. The 4-stroke cycle of events then starts over again.

Figure 3. Power Stroke

Generac Power Systems 941-2 — 4-CYCLE ENGINE THEORY diagram (page 37)
Fig. 25

Figure 4. Exhaust Stroke

Page 38 of the Generac Power Systems 941-2 user manual — !
Page 38 · click to enlarge
Page 38

Section 2.1 GENERAL INFORMATION

TIMING: Valve timing and ignition timing must be precisely controlled if the engine is to operate properly and effi- ciently. Intake and exhaust valves must open and close in a precise timed sequence if the four strokes are to occur. Ignition must occur at exactly the correct piston position, just prior to the start of the power stroke. Timing of valve opening and closing, as well as of spark occurrence, is given in relation to the pis- ton position and the degrees of crankshaft rotation. Ignition Is timed to occur several degrees before top dead center (TDC) of the piston, to allow time for the air-fuel mixture to ignite and start to bum before the piston reaches top dead center There must be no leakage past the valves in their closed position or compression will not develop. Likewise, there must be no leakage past the piston

  • GASEOUS FUEL SYSTEMS: Some RV generator models may be equipped with an LP or natural gas fuel system. The use of such gaseous fuels may result in a slight power loss as compared to gasoline. However, that disadvantage is usually compensated for by the many advantages offered by such fuels. Some of these advantages are:
  • A low residue content which results in minimum carbon formation in the engine.
  • Reduced sludge buildup in the engine oil.
  • Reduced burning of valves as compared to gasoline. No "washdown" of the engine cylinder wall during cranking and startup.
  • Excellent anti-knock qualities.
  • A nearly homogenous mixture in the engine cylinder.
  • Fuel can be stared for long periods without breakdown.

RECOMMENDED FUELS

DANGER! GASEOUS FUELS ARE HIGHLY VOLATILE AND THEIR VAPORS ARE EXPLO- SIVE. LP GAS IS HEAVIER THAN AIR AND WILL SETTLE IN LOW AREAS. NATURAL GAS IS LIGHTER THAN AIR AND WILL ACCU- MULATE IN HIGH AREAS. EVEN THE SLIGHT- EST SPARK CAN IGNITE THESE FUELS AND CAUSE AN EXPLOSION. THE USE OF LEAK DETECTORS IS RECOMMENDED WHEN GASEOUS FUELS ARE USED. ALL CODES, STANDARDS AND REGULATIONS PERTAIN- ING TO THE INSTALLATION AND USE OF GASEOUS FUELS MUST BE COMPLIED WITH.

!

GASOLINE FUEL SYSTEMS: For models equipped with a gasoline fuel system, the use of clean, fresh, UNLEADED, regular grade gaso- line is recommended. Unleaded gasoline burns clean- er, extends engine life, and promotes better starting by reducing carbon deposits in the combustion chamber. Leaded "Regular" grade gasoline may be used if unleaded gasoline is not available. The use of gasohol is NOT recommended. If it must be used, it should not contain more than 10 percent ethanol. When gasoline containing ethanol is used, special care is required when preparing the unit for storage (see "Storage Instructions" NOTE: DO NOT USE GASOLINE CONTAINING METHANOL. NOTE: DO NOT MIX OIL WITH THE GASOLINE.

RECOMMENDED ENGINE OIL

  • Use a clean, high quality, detergent oil that is classified "For Service SC, SD, SE, SF or SG". Use no special additives with the oil.
  • During summer months (above 32° F. or 0° C.), use SAE 30 oil. SAE 10W-30 oil is an acceptable substitute.
  • During winter months (below 32° F. or 0° C.), use SAE 5W-20 or 5W-30 oil.
  • DO NOT USE SAE 10W-40 OIL.

!

Page 39 of the Generac Power Systems 941-2 user manual — ENGINE TUNE-UP
Page 39 · click to enlarge
Page 39

Section 2.1 GENERAL INFORMATION

Engine crankcase oil capacity without oil filter change is about 29 fluid ounces (850m. Engine crankcase oil capacity (with oil filter change) is about 1 U.S. quart (946m1). Change engine oil and the oil filter after the first eight (8) hours of operation. Thereafter, change engine oil and oil filter every 50 operating hours. NOTE: Additional Information on the engine oil system can be found in Part 5 of this manual, "Engine Oil and Cooling System".

2. Check the battery. Fill all battery cells to the proper level with distilled water. DO NOT USE TAP WATER IN THE BATTERY. If necessary, recharge the battery to a 100 percent state of charge or replace it, if defective.
3. Turn OFF all electrical loads. Start the engine at no load and let it warm up.
4. Apply electrical loads to at least 50% of the unit's rated capacity.
5. When engine is thoroughly warmed up, turn off or disconnect all electrical loads. Then, shut the engine down.

STORAGE INSTRUCTIONS

THE UNIT IS NOW READY FOR SERVICE.

PREPARATION FOR STORAGE: The engine should be started at least once every seven (7) days and allowed to run for at least thirty (30) minutes. If this cannot be done and the engine is to remain unused longer than thirty (30) days, it must be prepared for storage. To prepare the unit for stor- age, proceed as follows:

ENGINE TUNE-UP

The following procedure may be used as a minor tune-up. On completion of the procedure, the engine should run properly. If it does not run properly, addi- tional checks and repairs are required.

1. Start the engine and let it warm up.
1. Service and repair engine air cleaners, as necessary.
2. After engine is thoroughly warmed up, shut it down.
2. Check engine oil level and condition of oil. Add or change oil as required.
3. Remove shrouding and clean away dirt from the engine cylinder head and cooling fins.
3. While engine is still warm from running, completely drain the oil. Then, refill with the recommended oil. See "Recommended Engine Oil".
4. Check fuel filters and clean or replace as necessary.
5. Replace the spark plug with a Champion RC12YC (or equivalent) plug.
4. Attach a tag to the engine indicating the viscosity and classification of the oil in the crankcase.

a.Set spark plug gap to 0.030 inch (0.76mm). b.Install new plug and tighten to 13 foot-pounds

5. Remove the spark plug and pour about one (1) ounce (15m1) of clean, fresh engine oil into the spark plug threaded opening. Crank the engine several times to distribute the oil, then install and tighten the spark plug.

(1.8 N-m). c. If a torque wrench is not available, tighten spark

plug as tight as possible with fingers and then (1) If plug Is RE-USED, tighten about 1/4 turn

more with a wrench. (2) If plug is NEW, tighten it about 1/2 turn

6. Remove the battery and store it in a cool, dry room on a wooden board. Never store the battery on any concrete or wood floor.

more with a wrench.

6. Check that wiring is free of breaks, abrasions and are properly routed.
7. Clean and wipe the generator exterior surfaces.
RETURN TO SERVICE AFTER STORAGETo return the unit to service after storage, proceed as follows:
7. Check for spark as outlined in "Ignition" section of Part 6 of this manual.
8. Run engine, adjust carburetor if necessary and check operation.
1. Verify that the correct oil is in the engine crankcase by checking the tag on the engine (see "Recommended Engine Oil".) If necessary, drain oil and refill with the recommended oil.
Page 40 of the Generac Power Systems 941-2 user manual — Section 2.1 GENERAL INFORMATION
Page 40 · click to enlarge
Page 40

Section 2.1 GENERAL INFORMATION

EXPLODED VIEW OF ENGINE LONG BLOCK

ITEM QTY DESCRIPTION 1 1 Connecting Rod 2 1 Piston Pin 3 1 Piston Ring Set (STD) 4 2 1/4" Pipe Plug 5 1 Breather Cover 6 1 Piston 7 2 Piston Pin Retainer 8 1 Crankshaft & Gear Assembly 10 1 Oil Breather Separator 11 1 Crankcase Assembly 12 1 Sleeve Bearing 13 2 Crankshaft Oil Seal 14 1 Breather Baffle Cup 15 4 M6 Screw 16 4 Lockwasher 17 3 Dowel Sleeve 18 1 Camshaft Assembly 19 1 Crank Case Flange Gasket 21 1 Cylinder Head Gasket 22 1 Oil Pressure Spring Retainer 23 1 Oil Pressure Spring 24 1 Oil Pressure Relief Valve Ball 25 1 Thread Forming Bolt 26 4 M6 Screw & Lockwasher 27 1 Oil Filter Adapter 28 6 M8-1.25 Capscrew 29 1 Oil Pressure Switch 30 2 Valve Spring Retainer NOTE 2:- Use a Champion RC12YC (or equivalent) spark plug with gap set to 0.030 inch (0.76mm).

ITEM QTY DESCRIPTION 31 2 valve Spring 32 1 Dowel Pin 33 1 Inner Oil Pump Rotor 34 2 Connecting Rod Bolt 36 1 Cylinder Head (see NOTE 1) 37 1 Exhaust Valve 38 1 Intake Valve 39 2 Push Rod 40 2 Tappet 41 1 Oil Pickup Screen 42 1 Rocker Cover Gasket 43 2 Pivot Ball Stud 44 2 Rocker Arm 45 2 Rocker Arm Nut 46 1 Push Rod Guide Plate 47 5 Head Bolt 48 1 Rocker Cover 49 2 Breather Gasket 50 2 Bolt 51 1 Outer Oil Pump Rotor 52 1 Oil Sump Assembly 53 2 Valve Spring Wear Washer 54 1 Intake Valve Seal 55 1 Oil Temperature Switch 56 2 M3 Screw 57 2 M3 Lockwasher 58 1 Spark Plug (see NOTE 2) 59 1 Oil Filter Adapter Gasket 60 1 1/4" NPT Pipe Plug NOTE 1:- Item 36 Includes valve seats and guides.

Generac Power Systems 941-2 — Section 2.1 GENERAL INFORMATION diagram (page 40)
Fig. 26 · Section 2.1 GENERAL INFORMATION
Page 41 of the Generac Power Systems 941-2 user manual — VALVE COMPONENTS REMOVAL
Page 41 · click to enlarge
Page 41

Section 2.2 VALVE TRAIN

VALVE TRAIN COMPONENTS

Generac Power Systems 941-2 — Section 2.2 VALVE TRAIN diagram (page 41)
Fig. 27 · Section 2.2 VALVE TRAIN

Valve train components are listed below and shown in Figure 1, below.

ITEM QTY DESCRIPTION 1 2 Tappet 2 2 Push Rod 3 2 Rocker Arm 4 2 Pivot Ball Stud 5 2 Rocker Arm Jam Nut 6 1 Push Rod Guide Plate 7 2 Valve Spring 8 2 Valve Spring Retainer 9 2 Valve Spring Washer 10 1 Exhaust Valve 11 1 Intake Valve

Figure 2. Removal of Rocker Arm over

2. Loosen the rocker arm jam nuts on the pivot ball studs. Then, loosen the pivot ball studs. Remove the two pivot ball studs, the rocker arms and the jam nuts. Also remove the push rod guide plate.
Generac Power Systems 941-2 — Section 2.2 VALVE TRAIN diagram (page 41)
Fig. 28 · Section 2.2 VALVE TRAIN
Generac Power Systems 941-2 — Section 2.2 VALVE TRAIN diagram (page 41)
Fig. 29 · Section 2.2 VALVE TRAIN

Figure 1. Valve Train Components

VALVE COMPONENTS REMOVAL

Figure 3. Rocker Arm, Push Rod & Guide Plate

1. The ROCKER ARM COVER is retained by four M6-1.00 x 12mm screws and lockwashers. Remove the four screws and lockwashers, then remove the ROCKER ARM COVER and its gasket.
3. Remove the push rods. 4. Remove the cylinder head bolts, then remove the cylinder head and head gasket.
Page 42 of the Generac Power Systems 941-2 user manual — !
Page 42 · click to enlarge
Page 42

Section 2.2 VALVE TRAIN

VALVES: Replace valves If they are damaged, distorted or if the margin is ground to less than 0.039 inch (1.0mm). If the valves are in useable condition, use a valve grinder to grind the faces to a 45' angle. Check valve stem diameter. After the valves have been reconditioned, they should be lapped with a suitable lapping tool and valve lap- ping compound.

VALVE SERVICE

Figure 4. Cylinder Head Removal

VALVE MARGIN (GV-220) DESIGN MARGIN0.034-0.04 inch (0.87-1.13mm)

!

WEAR LIMIT0.020 inch (0.50mm) Maximum

INTAKE VALVE STEM DIAMETER (GV-220) DESIGN DIAMETER: 0.274-0.275 inch (6.965-0.980mm)

5. See Figure 5, next page. Hold the valve with your fingers while compressing the spring with your thumb, then proceed as follows:
WEAR LIMIT0.273 Inch (6.934mm) Minimum

EXHAUST VALVE STEM DIAMETER (GV-220) DESIGN DIAMETER: 0.273-0.274 inch (6.945-6.960mm)

a.While the spring is compressed, slide the larger

WEAR LIMIT: 0.272 inch (6.909mm) Minimum NOTE: Design sizes and wear limits of valve train components can also be found in Part 9 of this Manual ("SPECIFICATIONS & CHARTS").

hole of the valve spring retainer toward the valve stem. b.With the larger spring retainer hole around the

valve stem, release the spring. c. Remove the valve spring retainer, the spring

VALVE SEATS: Valve seats are NOT replaceable. If burned or pitted, seats can be reground. Grind seats at a 45' angle and to a width of 0.039 inch (1.Mm).

and the spring washer.

Generac Power Systems 941-2 — ! diagram (page 42)
Fig. 30

Figure 7. Valve Seat

VALVE SEAT WIDTH GV-220) DESIGN WIDTH: 0.034-0.044 inch (0.87-1.13mm)

WEAR LIMIT0.064 inch (1.63mm) Maximum

VALVE GUIDES: Valve guides are permanently installed in the cylinder head and cannot be replaced. If the guides become worn beyond the wear limit, they can be reamed to accommodate a 0.020 inch (0.50mm) oversize valve stem. Use a straight shank hand reamer or a low speed drill press to ream valve guides.

Figure 5. Removal of Valve Spring

6. Remove the intake and exhaust valves.
7. Clean all parts. Remove carbon from valve heads and stems.
8. Inspect the valves and valve seats. Service parts as outlined under "Valve Service".
VALVE GUIDES (GV-220) DESIGN DIAMETER0.237-0.2364 inch (6.02-6.005mm)
WEAR LIMIT0.238 inch (6.045mm) Maximum
Page 43 of the Generac Power Systems 941-2 user manual — VALVE COMPONENTS INSTALLATION
Page 43 · click to enlarge
Page 43

Section 2.2 VALVE TRAIN

Figure 10. Valve Spring

VALVE SPRING FREE LENGTH

GV-2202.0741inch (52.69mm)

Figure 8. Valve Guides

FORCE REQUIRED TO COMPRESS SPRING TO 1.39

INCH (35.2MM) GV-220:19.8-21.81lbs (9.0-9.9kg)

VALVE TAPPETS: Valve tappets can be removed during removal of the engine camshaft. Intake and exhaust valve tappets are identical. However, once a wear pattern has been established the two tappets should not be Interchanged.

VALVE COMPONENTS INSTALLATION

After the valve train parts have been inspected and (if necessary) serviced, install them as follows:

1. Lubricate the valve stems and the valve guides with engine oil.
Generac Power Systems 941-2 — VALVE COMPONENTS INSTALLATION diagram (page 43)
Fig. 31
2. Install the intake and exhaust valves through their respective valve guides In the cylinder head.

a.The exhaust valve has the smaller head with a

diameter of 1.053 inches (26.75mm). b.The intake valve has the larger head, having a

diameter of 1.171 inches (29.75mm). c. Valve seat sizes in the cylinder head will match

their respective head sizes.

Figure 10. Valve Tappet

Generac Power Systems 941-2 — VALVE COMPONENTS INSTALLATION diagram (page 43)
Fig. 32

VALVE SPRINGS: Inspect the valve springs. Measure the spring free length. Also, check the amount of force required to compress the spring to a length of 1.39 inch (35.2 mm). Replace any damaged or defective spring.

Figure 11. Installation of Intake and Exhaust Valves

Page 44 of the Generac Power Systems 941-2 user manual — ADJUSTING VALVE CLEARANCE
Page 44 · click to enlarge
Page 44

Section 2.2 VALVE TRAIN

VALVE COMPONENTS INSTALLATION

6. Place the push rod guide plate into position on the head. Then, install the rocker arm and the pivot ball stud. The rocker arm jam nut must be on far enough to hold the guide plate In position.

(CONTINUED)

3. Install the valve spring washers, valve springs and valve spring retainers over the valve guides.

a.Hold the valve with your fingers and use your

thumbs to compress the spring. b.When the spring is compressed sufficiently,

Generac Power Systems 941-2 — (CONTINUED) diagram (page 44)
Fig. 33

slide the spring retainer small opening over the valve stem. c. With the smaller retainer opening around the

valve stem, release the spring.

Generac Power Systems 941-2 — (CONTINUED) diagram (page 44)
Fig. 34

Figure 14. Install Rocker Arm & Pivot Ball stud

7. install the push rod with either end against the tappet.

a.Place the push rod between the guide plate

tabs. b.Place the rocker arm socket onto end of push

rod. c. Alignment is correct when push rod ball rests In

Figure 12. Installing Valve Spring Washers

the rocker arm socket.

4. After both valves have been retained in the cylinder head, position a new head gasket and install the cylinder head.
Generac Power Systems 941-2 — (CONTINUED) diagram (page 44)
Fig. 35
5. Install cylinder head bolts. Tighten the head bolts in the sequence shown to the recommended tightness.

TIGHTENING TORQUE

CYLINDER HEAD GV-22029 foot-pounds
Generac Power Systems 941-2 — TIGHTENING TORQUE diagram (page 44)
Fig. 36

Figure 15. Push Rod Installation

ADJUSTING VALVE CLEARANCE

When adjusting valve clearance, the engine should be at room temperature and the piston should be at top dead center (TDC) of Its compression stroke (both valves closed).

Figure 13. Head Bolts Tightening Sequence

Page 45 of the Generac Power Systems 941-2 user manual — JAM NUT TIGHTENING TORQUE
Page 45 · click to enlarge
Page 45

Section 2.2 VALVE TRAIN

VALVE CLEARANCE GV-220 ENGINE INTAKE VALVE: 0.001-0.0022 inch (0.03-0.056mm) EXHAUST VALVE: 0.0018-0.003 inch (0.046-0.07mm) Adjust the valve clearance as follows:

Generac Power Systems 941-2 — Section 2.2 VALVE TRAIN diagram (page 45)
Fig. 37 · Section 2.2 VALVE TRAIN
1. Rotate the crankshaft until the piston is at top dead center (TDC) of its compression stroke. Both valves should be closed.
2. Loosen the rocker arm jam nut.
3. Use an alien wrench to turn the pivot ball stud while checking the clearance between the rocker arm and the valve stem with a feeler gauge.
Generac Power Systems 941-2 — Section 2.2 VALVE TRAIN diagram (page 45)
Fig. 38 · Section 2.2 VALVE TRAIN

Figure 17. Tightening Pivot Ball Jam Nut

Generac Power Systems 941-2 — Section 2.2 VALVE TRAIN diagram (page 45)
Fig. 39 · Section 2.2 VALVE TRAIN

Figure 16. Adjusting Valve Clearance

4. When valve clearance is correct, hold the pivot ball stud with the alien wrench while tightening the rocker arm jam nut with a crow's foot. Tighten the jam nut to the specified torque. After tightening the jam nut, recheck the valve clearance to make sure it did not change.

Figure 18. Rocker Arm Cover Installation

JAM NUT TIGHTENING TORQUE

ROCKER ARM COVER INSTALLATION

GV-2206.3 foot-pounds

Place a new rocker arm cover gasket into place. Then, install the rocker arm cover. Finally, retain the cover with M6-1.00 x 12mm screws.

Page 46 of the Generac Power Systems 941-2 user manual — Section 2.2 VALVE TRAIN
Page 46 · click to enlarge
Page 46

Section 2.2 VALVE TRAIN

Page 47 of the Generac Power Systems 941-2 user manual — PISTON
Page 47 · click to enlarge
Page 47

Section 2.3 PISTON, RINGS, CONNECTING ROD

OVERSIZE PISTON & RINGS

Generac Power Systems 941-2 — Section 2.3 PISTON, RINGS, CONNECTING ROD diagram (page 47)
Fig. 40 · Section 2.3 PISTON, RINGS, CONNECTING ROD

Worn or scored cylinders may be rebored to 0.010 (0.25mm) or 0.020 (0.50mm) oversize. Pistons and piston rings of matching oversize are available to fit the rebored cylinder.

F figure 2. Piston Pin Removal

CHECK FOR PISTON WEAR: The piston is slightly elliptical. It's smaller diameter is in line with the wrist pin boss. It's larger diameter is 90° from the wrist pin boss. NOTE: An assembly mark Is provided on the pis- ton. This mark should face the flywheel end of the crankshaft (3:00 position) during reassembly.

Figure 1. Piston, Rings and Connecting Rod

PRIOR TO REMOVAL

Before removing pistons, rings and connecting rod, clean all carbon from the cylinder bore. Carbon buildup in the cylinder bore can cause ring breakage during piston removal.

REMOVAL

Remove the connecting rod CAP BOLTS and the connecting rod CAP. Then, push the piston and con- necting rod out through top of cylinder.

Figure 3. Elliptical Shape of Piston

PISTON

To check the piston for wear, proceed as follows:

REMOVE FROM CONNECTING ROD: NOTE: An oil hole in the wrist pin area of the pis- ton helps distribute oil to assist in cooling. The oil hole also provides an assist In removing the wrist pin snap ring. To remove the piston from the connecting rod, pro- ceed as follows:

1. Minor Diameter: At a position directly in line with the wrist pin hole, measure from top of piston down to a distance of 1.4-1.6 inches (35.5-40.5mm). This is the "minor" diameter. Measure at this point to check for wear.
2. Major Diameter: At a point 90° from the wrist pin bore, measure down 1.4-1.6 inches (35.5-40.5mm). This is the "major" diameter. Measure at this point to check for piston wear. Replace the piston if wear limits are exceeded.
1. Move the snap ring around until Its protruding end is aligned with the notched out oil hole. Use needle nose pliers to turn the snap ring and pull it toward you.
3. Check wrist Pin for Looseness: A rough check for wear in the wrist pin, wrist pin bore in the piston, or wrist pin bore in the connecting rod is to check for looseness or play with the piston assembled to the rod. Looseness or play indicates a worn wrist pin, or a worn bore in the piston or connecting rod.
2. With one snap ring removed, slide the wrist pin out of the piston boss. This will separate the piston from the connecting rod.
Page 48 of the Generac Power Systems 941-2 user manual — PISTON RINGS
Page 48 · click to enlarge
Page 48

Section 2.3 PISTON, RINGS, CONNECTING ROD

5. Ring to Groove Side Clearance:- Clean carbon from piston ring grooves as. Install new rings. Use a feeler gauge to measure the side clearance between the rings and ring grooves. If ring-togroove side clearance exceeds the stated limits, replace the piston.
Generac Power Systems 941-2 — Section 2.3 PISTON, RINGS, CONNECTING ROD diagram (page 48)
Fig. 41 · Section 2.3 PISTON, RINGS, CONNECTING ROD

RING TO GROOVE SIDE CLEARANCE (GV-220)

0.0004-0.0014 inch (0.012-0.034mm)

Generac Power Systems 941-2 — RING TO GROOVE SIDE CLEARANCE (GV-220) diagram (page 48)
Fig. 42

Figure 4. Piston Minor Diameter

PISTON MINOR DIAMETER GV-220) Design DIAMETER: 2.747-2.748 inch (69.789-69.809mm)

Generac Power Systems 941-2 — RING TO GROOVE SIDE CLEARANCE (GV-220) diagram (page 48)
Fig. 43

Figure 6. Ring to Groove Side Clearance

Figure 5. Piston Major Diameter

PISTON MAJOR DIAMETER GV-220) Design DIAMETER: 2.753-2.754 inch (69.939-69.959mm) NOTE: Always apply engine oil to wrist pin and its bores during Installation. Wrist pin fit is very close.

PISTON RINGS

  • GENERAL: The following rules pertaining to piston rings must always be complied with:
  • Always replace piston rings in sets.
  • When removing rings, use a ring expander to prevent breakage. Do not spread the rings too far or they will break.
  • When installing the piston into the cylinder, use a ring compressor. This wilt prevent ring breakage and/or cylinder damage.
  • When installing new rings, deglaze the cylinder wall with a commercially available deglazing tool.
4. Check Wrist Pin for Wear: Measure the outside diameter of the wrist pin. Also measure the inside diameter of the wrist pin bore in the piston and in the connecting rod. Also check wrist pin length. Replace any component that Is worn excessively.

WRIST PIN OUTSIDE DIAMETER (GV-220) DESIGN DIAMETER: 0.708-0.709 inch (17.989-18.000mm)

WEAR LIMIT0.707 inch (17.969mm) Minimum

WRIST PIN LENGTH (GV-220) DESIGN LENGTH: 2.196-2.213 inch (55.8-56.2mm)

WEAR LIMIT2.193 inch (55.7mm) Minimum

WRIST PIN BORE IN PISTON (GV-220) DESIGN DIAMETER: 0.708-0.709 inch (18.000-18.011mm)

  • RING DESCRIPTION: A piston ring SET consists of (a) a top compression ring, (b) a second compression ring, and (c) an oil ring assembly. When installing rings, pay close attention to the following:
  • The OIL RING is a 3-piece assembly which consists of two oil rails and an oil spacer ring. Oil rails have a rounded face and can be installed with either side up.
  • The second compression ring has an inside chamfer which must face UP when installing the ring.
  • The top compression ring has a barrel-shaped face and can be installed with either side up.
WEAR LIMIT0.710 inch (18.026mm) Maximum

CONNECTING ROD SMALL END I.D. (GV-220) DESIGN DIAMETER: 0.709-0.710 inch (18.02-18.03mm

WEAR LIMIT0.711 inch (18.05mm) Maximum
Page 49 of the Generac Power Systems 941-2 user manual — ASSEMBLY AND INSTALLATION
Page 49 · click to enlarge
Page 49

Section 2.3 PISTON, RINGS, CONNECTING ROD

CONNECTING ROD

Generac Power Systems 941-2 — Section 2.3 PISTON, RINGS, CONNECTING ROD diagram (page 49)
Fig. 44 · Section 2.3 PISTON, RINGS, CONNECTING ROD

The connecting rod is manufactured of die cast alu- minum. Alignment marks are provided on the rod and on the connecting rod cap. Be sure to align these marks when assembling the rod to the crankshaft. Connecting rod bolts are of the "washerless" type. The connecting rod and the connecting rod cap are a matched set and must be replaced as a matched set.

Generac Power Systems 941-2 — Section 2.3 PISTON, RINGS, CONNECTING ROD diagram (page 49)
Fig. 45 · Section 2.3 PISTON, RINGS, CONNECTING ROD

Figure 7. Ring Locations in Piston Grooves

CHECKING PISTON RING END GAPTo check piston rings end gap, proceed as follows (see Figure 8):
1. Locate a point inside the cylinder that is 2.75 inches (70mm) down from top of cylinder. This is approximately half-way down.

Figure 9. Connecting Rod

2. Place the ring into the cylinder. Use the piston to push the ring squarely into the cylinder to the proper depth.

ASSEMBLY AND INSTALLATION

3. Use a feeler gauge to measure the ring end gap. If end gap is excessive, rebore the cylinder to take oversize parts.

ASSEMBLY: Use a ring expander when installing rings into the pis- ton ring grooves. Install the OIL RING ASSEMBLY first. Then, install the second compression ring with its Inside chamfer facing up. Finally, install the top compression ring. When assembling the piston, connecting rod and wrist pin, the assembly marks on the piston must be toward the flywheel side of the engine. Coat the wrist pin, wrist pin bore in piston, and wrist pin bore in the rod with engine oil. Install one snap ring into the piston's wrist pin bore. Then, assemble the piston to the rod. Slide the wrist pin through one piston bore, through the rod bore, and through the second piston bore until it contacts the snap ring. Then, install the second snap ring into the piston bore.

TOP RING END GAP (GV-220) DESIGN GAP: 0.005-0.016 inch (0.15-0.40mm)

WEAR LIMIT0.024 inch (0.60mm) Maximum

SECOND RING END GAP (GV-220) DESIGN GAP: 0.006-0.016 inch (0.15-0.40mm)

WEAR LIMIT0.024 inch (0.60mm) Maximum

OIL RING END GAP (GV-220) DESIGN GAP: 0.015-0.055 inch (0.38-1.40mm)

WEAR LIMIT0.062 inch (1.60mm) Maximum
Generac Power Systems 941-2 — ASSEMBLY AND INSTALLATION diagram (page 49)
Fig. 46

INSTALLATION: Coat the cylinder walls with engine oil, as well as the crank throw, connecting rod bearing and connecting rod cap bearing. Then, install the rod and piston assembly as follows:

1. Use a ring compressor to compress the rings into the piston ring grooves. MAKE SURE ALL RINGS ARE FULLY COMPRESSED INTO THEIR GROOVES.
2. Guide the connecting rod into the cylinder, with assembly mark on piston toward the flywheel side of engine.

Figure 8. Ring End Gap

3. When the ring compressor contacts top of cylinder, use a wood
Page 50 of the Generac Power Systems 941-2 user manual — CYLINDER SERVICE
Page 50 · click to enlarge
Page 50

Section 2.3 PISTON, RINGS, CONNECTING ROD

hammer handle to gently tap the piston down into the cylinder.

Always resize the cylinder bore to EXACTLY 0.010 inch or 0.020 inch (0.25 or 0.50mm) over the stan- dard cylinder dimensions. If this Is done accurately, the service oversize ring and piston will fit and correct clearances will be maintained.

4. Check that the connecting rod's large diameter bearing is coated with oil, as well as the crank throw and the connecting rod cap.

STANDARD CYLINDER BORE DIAMETER

5. Guide the large end of the connecting rod onto the crankshaft. Install the connecting rod cap. The match mark on the cap must be aligned with an identical mark on the rod (Figure 10).

MINIMUM: 2.7560 inches (70.000mm) MAXIMUM: 2.7570 Inches (70.025mm) To rebore the cylinder, use a commercial hone of suitable size chucked In a drill press having a spindle speed of about 600 rpm. Use the stones and lubrica- tion recommended by the hone manufacturer to pro- duce the proper cylinder bore finish. Proceed as fol- lows:

6. Install the connecting rod cap bolts and tighten to the proper torque.

TIGHTENING TORQUE CONNECTING ROD CAP BOLTS (GV-220)

10 foot-pounds (1.36 N-m) NOTE: The connecting rod can be installed in either direction. That is, the cap marks on the rod and cap may face toward the installer or away from the installer. The only requirement is that the assembly mark on top of piston be toward the fly- wheel side of engine.

1. Start with coarse stones. Center the cylinder under the drill press spindle. Lower the hone so that the lowest end of the stone contacts the lowest point in the cylinder bore.
2. Begin honing at bottom of cylinder. Move the hone up or down at about 50 strokes per minute, to avoid cutting ridges In the cylinder wall. Every fourth or fifth stroke, move the hone far enough to extend it one (1) Inch beyond the top and bottom of the cylinder bore.
Generac Power Systems 941-2 — TIGHTENING TORQUE CONNECTING ROD CAP BOLTS (GV-220) diagram (page 50)
Fig. 47
3. Every 30 or 40 strokes, check the bore for size and straightness. If stones collect metal, clean them with a wire brush.
4. Hone with coarse stones until the cylinder bore is within 0.002 inch (0.05mm) of the desired finish size. Then, replace the coarse stones with burnishing stones and continue until bore is within 0.0005 inch (0.01 mm) of the desired size.
5. Install finishing stones and polish the cylinder to its final size.
6. Clean the cylinder with soap and water. Dry thoroughly.

Figure 10. Match Marks on Rod and Cap

7. Replace the piston and rings with parts of correct oversize.

CYLINDER SERVICE

INSPECTION: Check the cylinder for dirty, broken or cracked fins. Also look for worn or scored bearings, or a scored cylinder wall. Check the cylinder head mounting sur- face for warpage. If the head is warped, it must be replaced. If the cylinder bore is worn (as evidenced by excessive ring end gap), the cylinder should be replaced or rebored to 0.010 or 0.020 (0.25 or 0.50mm) oversize. After reboring the cylinder to a specific oversize, install an identically oversize piston along with identi- cally oversized rings.

Page 51 of the Generac Power Systems 941-2 user manual — CAMSHAFT REMOVAL
Page 51 · click to enlarge
Page 51

Section 2.4 CRANKSHAFT AND CAMSHAFT

GENERAL

CRANKSHAFT REMOVAL

Prior to removal of the crankcase cover, gain access to the engine and generator by removing surrounding sheet metal as required. See Section 1.6.

See Figure 3. To remove the crankshaft, proceed as follows:

1. The engine flywheel must be removed before the crankshaft can be removed.

CRANKCASE COVER REMOVAL

2. The piston and connecting rod must be removed.

Before attempting to remove the crankcase cover, remove rust, paint and burrs from the power takeoff (PTO) end of the crankshaft. This will reduce the pos- sibility of damaging the oil seal in the crankcase cover or the bearing during cover removal. To remove the crankcase cover, proceed as follows:

3. Remove the crankshaft by pulling it straight out of the crankcase.
Generac Power Systems 941-2 — CRANKCASE COVER REMOVAL diagram (page 51)
Fig. 48
1. Drain oil from the crankcase.
2. Remove the engine cylinder head, push rods and push rod guide plate. See Section 2.2.
3. Remove all bolts that retain the crankcase cover to the crankcase.
4. Remove the crankcase cover. If necessary, tap lightly with a soft hammer on alternate sides of the cover.
Generac Power Systems 941-2 — CRANKCASE COVER REMOVAL diagram (page 51)
Fig. 49

Figure 2. Camshaft Removal

Generac Power Systems 941-2 — CRANKCASE COVER REMOVAL diagram (page 51)
Fig. 50

Figure 1. Crankcase Cover Removal

CAMSHAFT REMOVAL

See Figure 2. Remove the camshaft as follows:

1. Tip the engine over onto the flywheel end of the crankshaft. Support the engine to prevent end of crankshaft from resting on the workbench.

Figure 3. Crankshaft Removal

2. Reach in with two fingers and hold the tappets up so they are clear of the camshaft lobes. Then, remove the camshaft.
3. Remove the two tappets.
4. Remove the outer and inner oil pump rotors.

(Continued)

Page 52 of the Generac Power Systems 941-2 user manual — CRANKSHAFT INSPECTION
Page 52 · click to enlarge
Page 52

Section 2.4 CRANKSHAFT AND CAMSHAFT

CAMSHAFT INSPECTION

  • Inspect the crankpin for damage, nicks, scratches, etc. Small nicks and scratches may be polished out using fine emery cloth. ALL EMERY RESIDUE MUST BE REMOVED. Use a solvent (such as kerosene) to remove emery residue.
  • Carefully measure the outside diameter (O.D.) of the crankpin, crankshaft journal at flywheel end, and crankshaft journal at PTO end. Replace the crankshaft if it is worn smaller than the stated limits. NOTE: DO NOT regrind the crankpin to any smaller diameter. Undersize connecting rods are NOT available for the GV-220 engines.
  • Inspect oil passage. Use a length of wire to make sure it is open. Inspect threaded ends of crankshaft.

Carefully inspect the entire camshaft for wear, nicks, damage. All areas indicated in Figure 4 should be checked for wear.

Generac Power Systems 941-2 — Section 2.4 CRANKSHAFT AND CAMSHAFT diagram (page 52)
Fig. 51 · Section 2.4 CRANKSHAFT AND CAMSHAFT

CRANKPIN OUTSIDE DIAMETER DESIGN DIAMETER: 1.180-1.181 inch (29.99-30.01mm)

WEAR LIMIT1.179 inch (29.96mm) Minimum

CRANKSHAFT BEARING JOURNAL (FLYWHEEL END)

DESIGN DIAMETER1.102-1.103 inch (28.000-28.012mm)
WEAR LIMIT1.100 inch (27.95mm) Minimum

CRANKSHAFT BEARING JOURNAL (PTO END) DESIGN DIAMETER: 1.102-1.103 inch (28.000-28.012mm)

WEAR LIMIT1.186 inch (27.95mm) Minimum

Figure 4. Points to Check on Camshaft

Generac Power Systems 941-2 — CRANKSHAFT BEARING JOURNAL (FLYWHEEL END) diagram (page 52)
Fig. 52

The following should be measured carefully to check for wear:

MAIN CAMSHAFT BEARING DIAMETER

(FLYWHEEL END) DESIGN DIAMETER1.022-1.023 inch (25.96-25.98mm)
WEAR LIMIT1.020 inch (25.91mm) Minimum

MAIN CAMSHAFT BEARING DIAMETER (PTO END) DESIGN DIAMETER: 1.297-1.298 inch (32.96-32.98mm)

WEAR LIMIT1.295 inch (32.89mm) Minimum

CAMSHAFT BEARING BORE IN CRANKCASE DESIGN DIAMETER: 1.024-1.025 Inch (26.00-26.03mm)

WEAR LIMIT 1.026 inch (26.06mm) Maximum

CAMSHAFT BEARING BORE IN CRANKCASE COVER DESIGN DIAMETER: 1.299-1.300 inch (33.00-33.03mm)

WEAR LIMIT1.302 inch (33.06mm) Maximum
CAM LIFT DESIGN LIFT0.210-0.212 inch (5.34-5.38mm)

Figure 5. Points to Check on Crankshaft

WEAR LIMIT0.206 inch (5.24mm) Minimum

Check the crankshaft bearing bore in the crankcase cover. If limits are exceeded, replace the crankcase cover.

CRANKSHAFT INSPECTION

CRANKSHAFT BEARING BORE IN CRANKCASE

  • CRANKSHAFT PROPER: Use a commercial solvent to clean the crankshaft. After cleaning, inspect the crankshaft as follows:
  • Inspect keyways in crankshaft, make sure they are not worn or spread. Remove burrs from edges of keyway, to prevent scratching the bearing.
  • Inspect timing gear teeth for chipping or cracking. If the timing gear is damaged, the crankshaft assembly must be replaced.
COVER DESIGN DIAMETER1.104-1.105 inch (28.040-28.065mm)
WEAR LIMIT1.106 inch (28.092mm) Maximum
Page 53 of the Generac Power Systems 941-2 user manual — INSTALLING THE CAMSHAFT
Page 53 · click to enlarge
Page 53

Section 2.4 CRANKSHAFT AND CAMSHAFT

Generac Power Systems 941-2 — Section 2.4 CRANKSHAFT AND CAMSHAFT diagram (page 53)
Fig. 53 · Section 2.4 CRANKSHAFT AND CAMSHAFT
Generac Power Systems 941-2 — Section 2.4 CRANKSHAFT AND CAMSHAFT diagram (page 53)
Fig. 54 · Section 2.4 CRANKSHAFT AND CAMSHAFT

Figure 6. Bearing Bore in Crankcase Cover

Figure 8. Measuring Compression Release Lift

INSTALLING THE CRANKSHAFT

COMPRESSION RELEASE MECHANISM

A mechanical compression release is provided on the camshaft. See Figure 7. A PIN extends over the cam lobe. This PIN pushes on the tappet, to lift the valve and relieve compression for easier cranking. When the engine starts, centrifugal force moves the FLY- WEIGHT outward against SPRING force. The PIN will then drop back and allow the engine to run at full compression. Measure the amount of compression release lift at the tappet (Figure 8).

Before installing the crankshaft, lubricate all bearing surfaces with engine oil. Use oil seal protectors, to prevent damage to seals during installation. Install the crankshaft as follows:

1. Lubricate all bearing surfaces with engine oil.
2. Install the valve tappets.
3. Support both ends of the crankshaft and carefully install into the crankcase.

COMPRESSION RELEASE LIFT FOR GV-220 ENGINE

4. Rotate the crankshaft until the timing mark (Figure 9) is toward the cam gear side of the crankcase.
(MEASURED AT TAPPET) DESIGN LIFT0.020-0.047 inch (0.50-1.20mm)
WEAR LIMIT0.016 inch (0.406mm) Minimum

INSTALLING THE CAMSHAFT

Generac Power Systems 941-2 — INSTALLING THE CAMSHAFT diagram (page 53)
Fig. 55

Apply engine oil to the camshaft main bearing and to bearing bore in crankcase. Carefully install the camshaft into the crankcase camshaft bore. Hold the tappets out of the way during installation. Align timing mark on camshaft gear with timing mark on crankshaft gear (piston will be at top dead center). See Figure 10. NOTE: For Installation of the oil pump assembly, oil pickup assembly and crankcase cover, see Part 5 "ENGINE OIL & COOLING SYSTEM".

Figure 7. Compression Release Mechanism on

Camshaft

Page 54 of the Generac Power Systems 941-2 user manual — Section 2.4 CRANKSHAFT AND CAMSHAFT
Page 54 · click to enlarge
Page 54

Section 2.4 CRANKSHAFT AND CAMSHAFT

Generac Power Systems 941-2 — Section 2.4 CRANKSHAFT AND CAMSHAFT diagram (page 54)
Fig. 56 · Section 2.4 CRANKSHAFT AND CAMSHAFT
Generac Power Systems 941-2 — Section 2.4 CRANKSHAFT AND CAMSHAFT diagram (page 54)
Fig. 57 · Section 2.4 CRANKSHAFT AND CAMSHAFT

Figure 9. Timing Mark on Crankshaft Gear Figure 10. Alignment of Timing Marks

Page 55 of the Generac Power Systems 941-2 user manual — SECTION TITLE
Page 55 · click to enlarge
Page 55

PART 3 GASOLINE FUEL

SECTION TITLE

3.1 INTRODUCTION TO FUEL SYSTEM

3.2 AIR CLEANER & AIR INTAKE

SYSTEM

3.3 FILTER & FUEL PUMP

3.4 CARBURETOR

COMPUTER CONTROLLED

3.5 AUTOMATIC CHOKE

3.6 SPEED CONTROL SYSTEM

VARIABLE SPEED RV GENERATORS

Series Impact 36 Plus

Page 56 of the Generac Power Systems 941-2 user manual — NOTES
Page 56 · click to enlarge
Page 56

NOTES

Page 57 of the Generac Power Systems 941-2 user manual — EVAPORATION CONTROL SYSTEMS
Page 57 · click to enlarge
Page 57

Section 3.1 INTRODUCTION TO FUEL SYSTEM

GENERAL

!

Recreational vehicle generators equipped with a gasoline fuel system are usually installed so that they share the fuel supply tank with the vehicle engine. When this is done, the generator Installer must never tee off the vehicle fuel supply line to deliver fuel to the generator. When the generator fuel supply line is teed off the vehicle's fuel supply line, the more powerful vehicle engine's fuel pump will starve the generator when both are running. In addition, when the vehicle engine is not running the generator fuel pump will draw all of the gasoline from the vehicle engine line or even from the vehicle engine carburetor. This will result in hard starting of the vehicle engine. One method of sharing the same fuel supply tank is to Install a special fitting at the tank outlet so that two fuel dip tubes can be fitted In the tank (Figure 1). Another method Is to install a new outlet In the tank. If the tank has an unused outlet, It can be used. A second fuel dip tube can be installed in the original tank outlet if the tank outlet is large enough to accom- modate two dip tubes. The required fittings can be made at a machine shop. To install a second fuel out- let on the tank means removing the tank to braze or weld a new fitting into place.

RECOMMENDED FUEL

Use a high quality UNLEADED gasoline. Leaded REGULAR grade gasoline is an acceptable substi- tute. Do NOT use any fuel containing alcohol, such as "gasohol". If gasoline containing alcohol is used, it must not contain more than 10% ethanol and it must be removed from the generator fuel system during storage. do NOT use fuel containing methanol. If any fuel containing alcohol Is used, the system must be inspected more frequently for leakage and other abnormalities.

Generac Power Systems 941-2 — RECOMMENDED FUEL diagram (page 57)
Fig. 58

!

The generator's fuel dip tube in the tank should be shorter than the vehicle engine's dip tube. This will prevent the generator from consuming the entire fuel supply.

!

Figure 1. Sharing a Fuel Supply Tank

EVAPORATION CONTROL SYSTEMS

Federal and state laws have imposed strict evapora- tive controls on gasoline fuel systems. The recreation- al vehicle industry has complied with such strict regu- lations by using specially designed fuel tanks, tank filler tubes and gas caps. Special canisters are often used to collect the gasoline vapors rather than let them escape into the atmosphere. Such systems are designed to operate within very critical pressure ranges. For that reason, the vehicle manufacturer's fuel supply system design must not be

Page 58 of the Generac Power Systems 941-2 user manual — Section 3.1 INTRODUCTION TO FUEL SYSTEM
Page 58 · click to enlarge
Page 58

Section 3.1 INTRODUCTION TO FUEL SYSTEM

altered. Service technicians working on the RV gener- ator systems must not do anything that might change the vehicle fuel system design.

Generac Power Systems 941-2 — Section 3.1 INTRODUCTION TO FUEL SYSTEM diagram (page 58)
Fig. 59 · Section 3.1 INTRODUCTION TO FUEL SYSTEM

Figure 2. Typical Gasoline Fuel System

Page 59 of the Generac Power Systems 941-2 user manual — Section 3.2 AIR CLEANER AND INTAKE
Page 59 · click to enlarge
Page 59

Section 3.2 AIR CLEANER AND INTAKE

AIR CLEANER

4. Clean the air cleaner BASE and COVER, then install the new PAPER FILTER Into COVER.

DESCRIPTION: The air cleaner assembly consists of (a) an air clean- er BASE, (b) a PAPER FILTER, and (c) a COVER. See Figure 1.

5. Install COVER with PAPER FILTER. Retain to BASE with two screws. AIR INTAKE See Figure 2. Air is drawn into the air cleaner, passes through the air cleaner filter, and is then ported to the carburetor air inlet through an air intake hose. Periodically inspect the air intake hose for condition, damage, holes, perforations, etc. Replace hose, if necessary. Inspect air intake hose clamps for tightness, condition. Tighten or replace as necessary.
Generac Power Systems 941-2 — Section 3.2 AIR CLEANER AND INTAKE diagram (page 59)
Fig. 60 · Section 3.2 AIR CLEANER AND INTAKE
Generac Power Systems 941-2 — Section 3.2 AIR CLEANER AND INTAKE diagram (page 59)
Fig. 61 · Section 3.2 AIR CLEANER AND INTAKE

Figure 1. Engine Air Cleaner

SERVICING THE AIR CLEANER: Clean or replace the PAPER FILTER every 25 hours of operation or once each year, whichever comes first.

Figure 2. Air Intake Components

1. Loosen the two screws that retain the air cleaner COVER and remove the COVER.
2. Remove the PAPER FILTER.
3. Clean the PAPER FILTER by tapping gently on a flat surface. If PAPER FILTER is extremely dirty, replace it.
Page 60 of the Generac Power Systems 941-2 user manual — Section 3.2 AIR CLEANER AND INTAKE
Page 60 · click to enlarge
Page 60

Section 3.2 AIR CLEANER AND INTAKE

Page 61 of the Generac Power Systems 941-2 user manual — FUEL PUMP
Page 61 · click to enlarge
Page 61

Section 3.3 FUEL FILTER AND FUEL PUMP

FUEL FILTER

TESTING THE PUMP:

1. The pump coil can be tested for an open or shorted condition as follows:

The fuel filter should be removed and replaced every 100 hours of operation or once each year, whichever occurs first.

a.Test for "Open":

(1) Disconnect the RED pump wire at its "bul-

let" lug. (2) Set a VOM to its "Rx1 " scale and zero the

Generac Power Systems 941-2 — Section 3.3 FUEL FILTER AND FUEL PUMP diagram (page 61)
Fig. 62 · Section 3.3 FUEL FILTER AND FUEL PUMP

meter. (3) Connect one meter test probe to the RED

pump wire, the other test probe to terminal end of the pump's BLACK lead. The VOM should Indicate pump coil resistance.

FUEL PUMP NOMINAL COIL RESISTANCE

ABOUT 29.5 kW

b.Test for "Shorted" condition:

(1) Disconnect the RED and the BLACK fuel

pump leads. (2) Set a VOM to its "Rx10,000" or "Rx1 K"

Figure 1. Fuel Filter (Typical)

scale and zero the meter. (3) Connect one VOM test lead to the pump

FUEL PUMP

RED lead, the other test probe to the pump body. The meter should read "infinity".

  • DESCRIPTION: The 12 volts DC electric fuel pump has a zinc plate finish. Flow through the pump is positively shut off when It is not operating. The pump is actually rated at a voltage of 8 to 16 VDC, but has a nominal voltage rating of 12 VDC. Current draw of the pump at nominal voltage is approximately 1.4 amperes maximum. Pressure rating of the pump at zero delivery is 2.0 to 3.5 psi. Two wires are brought out from the pump. The black wire Is grounded by connecting it to a pump mounting bolt The red wire Is identified as Wire No. 14A. The pump will operate whenever:
  • The FUEL PRIME switch on the generator panel is actuated to its "ON" position.
  • During engine startup and running conditions when the A6060 circuit board energizes the Wire No. 14 circuit.
2. Pump operation can be tested as follows:

a.Disconnect the fuel line from the outlet side of

the fuel pump. b.Make sure a supply of fuel is available to the

Inlet side of the pump. c. The RED lead from the pump must be connect-

ed properly into the circuit The pump's BLACK lead must be connected at the pump mounting bolt. d.Actuate the Fuel Prime switch on the generator

panel. The pump should operate and should pump fuel from the outlet side.

Generac Power Systems 941-2 — FUEL PUMP diagram (page 61)
Fig. 63

Figure 2. Electric Fuel Pump

Page 62 of the Generac Power Systems 941-2 user manual — Section 3.3 FUEL FILTER AND FUEL PUMP
Page 62 · click to enlarge
Page 62

Section 3.3 FUEL FILTER AND FUEL PUMP

Page 63 of the Generac Power Systems 941-2 user manual — DESCRIPTION
Page 63 · click to enlarge
Page 63

Section 3.4 CARBURETOR

GENERAL INFORMATION

CARBURETOR OPERATION

Proper engine performance depends on the carbure- tion system. The use of clean, fresh gasoline and a well-maintained air cleaner are extremely important to proper operation, as well as engine reliability and power. Most causes of carburetion problems are related to the use of stale, gummy fuel and the ingestion of dirt. Before servicing the carburetor, be sure to check for evidence of these conditions. Gasoline that is left in the fuel lines for long periods can form gum or varnish deposits that will adversely affect carburetor opera- tion. NOTE: A commercial fuel stabilizer (such as STA- BIL®) will minimize the formation of um deposits during storage. Add the stabilizer- to the gasoline In the fuel tank or In the storage container. Follow the ratio recommended on the stabilizer contain- er. Run the engine for about 10 minutes after adding stabilizer, to allow It to enter the carbure- tor. "STABIL®" Is a brand name fuel stabilizer that can be purchased In most automotive repair facili- ties or in lawn and garden centers.

FLOAT OPERATION: A hollow plastic float maintains fuel level in the float bowl. As fuel is used, the float moves downward to move an inlet needle valve off its seat. When the needle valve moves off its seat, fuel can flow into the bowl. As the fuel level rises, the float moves upward to force the needle valve against its seat and stop the flow into the bowl.

Generac Power Systems 941-2 — Section 3.4 CARBURETOR diagram (page 63)
Fig. 64 · Section 3.4 CARBURETOR

DESCRIPTION

The carburetor used on GV-220 engines is a float type with fixed main jet. Carburetor throttle position and engine speed are controlled by an electric stepper motor. The stepper motor moves the throttle in response to signals received from the A6060 circuit board. The circuit board senses load voltage, establish- es the correct engine speed to obtain correct voltage and delivers an output signal to the stepper motor. The stepper motor adjusts the engine throttle to change engine speed and establish correct output voltage.

Figure 2. Carburetor Sectional View

CHOKE POSITION: The choke valve is closed to restrict the flow of air into the engine. As the engine cranks, air pressure in the cylinder is reduced. Since the air intake passage is partially blocked by the choke valve, fuel is drawn from the main nozzle and from the idle discharge port. This creates the very rich fuel mixture required for starting a cold engine.

Generac Power Systems 941-2 — DESCRIPTION diagram (page 63)
Fig. 65

IDLE OPERATION: The throttle valve is nearly closed to shut off the fuel supply from all ports except the primary idle fuel dis- charge port. Engine suction then draws fuel only from that port.

HIGH SPEED OPERATION: The throttle valve is wide open. This allows a large volume of air to pass through the carburetor at a high velocity. The high velocity air flow past the carburetor venturi results in a drop in air pressure at the venturi throat. This reduced air pressure draws fuel through the main nozzle that opens into the venturi which then mixes with the air in the air passage.

Figure 1. Carburetor

Page 64 of the Generac Power Systems 941-2 user manual — CLEANING AND INSPECTION
Page 64 · click to enlarge
Page 64

Section 3.4 CARBURETOR

CARBURETOR DISASSEMBLY

Generac Power Systems 941-2 — Section 3.4 CARBURETOR diagram (page 64)
Fig. 66 · Section 3.4 CARBURETOR

See Figure 3. The carburetor can be disassembled as follows:

1. Remove the BOWL NUT (Item 3) and the FIBER WASHER (Item 4). Then, remove the FLOAT BOWL (Item 5).
2. Remove the FLOAT PIN (Item 6). Then, remove the FLOAT (Item 7) and the INLET VALVE (Item 8).
3. Remove the IDLE SPEED SCREW (Item 20) with SPRING (Item 19).
4. Rotate the THROTTLE VALVE (Item 10) to its closed position and remove the SCREW (Item 9). Remove the THROTTLE VALVE.
5. Remove the THROTTLE SHAFT (Item 14), along with the THROTTLE SHAFT SPRING (Item 13) and the THROTTLE SHAFT SEAL (Item 12).
6. Remove the CHOKE VALVE SPRING RETAINER (Item 18). Remove the CHOKE VALVE (Item 17). Remove the CHOKE SHAFT (Item 15) and the SHAFT SEAL (Item 16).

CLEANING AND INSPECTION

1. Separate all non-metallic parts.
2. Clean metallic parts in a solvent or a commercial cleaner. Soak the parts no longer than about 30 minutes.
3. Inspect throttle lever and plate. Replace if worn or damaged.
4. The float bowl must be free of dirt and corrosion. Use a new float bowl gasket when assembling the bowl.

Figure 3. Carburetor Exploded View

3. Bowl Nut 4. Fiber Washer 5. Float Bowl 6. Float Pin 7. Float 8. Inlet Valve 9. Screw 10. Throttle Valve 11. Body 12. Throttle Shaft Seal 13. Throttle Shaft Spring 14. Throttle Shaft 15. Choke Shaft 16. Choke Shaft Seal 17. Choke Valve 18. Choke Valve Spring Retainer 19. Idle Speed Screw Spring 20. Idle Speed Screw
5. Check the float for damage. Replace, If damaged. The float setting is fixed and non-adjustable.
6. The carburetor body contains a main jet tube that is pressed in to a fixed depth. Do NOT attempt to remove this tube. Tube movement will adversely affect carburetor metering characteristics.
7. After soaking in solvent, blow out all passages with compressed air.
Page 65 of the Generac Power Systems 941-2 user manual — !
Page 65 · click to enlarge
Page 65

Section 3.4 CARBURETOR

ADJUSTMENT

Generac Power Systems 941-2 — Section 3.4 CARBURETOR diagram (page 65)
Fig. 67 · Section 3.4 CARBURETOR

The carburetor used on the GV-220 engine has a FIXED, NON-ADJUSTABLE Low Speed Jet.

ENGINE SPEED

Engine speed is controlled by the A6060 circuit board. That circuit board signals a stepper motor which moves the throttle linkage. Engine speed will vary in response to changes in generator AC output voltage. The circuit board monitors the demand for power and adjusts the engine speed accordingly. This permits the engine to deliver only the power needed. NOTE: Do NOT attempt to accelerate the engine manually by, grasping the throttle or throttle link- age. This win cause the system to enter a fault condition and terminate generator AC output.

Figure 4. Set Gap Between Stop Tab and Stop Block

Generac Power Systems 941-2 — ENGINE SPEED diagram (page 65)
Fig. 68

THROTTLE LINKAGE ADJUSTMENT

  • If necessary, the length of the linkage between the stepper motor and the carburetor throttle lever arm can be adjusted. This adjustment helps to establish the proper travel relationship of the linkage. If the adjustment is not correct, the A6060 board will not be able to control the full range of engine speed. The following conditions might occur:
  • If the throttle linkage is set too short, the system will not be able to provide wide open throttle or full power conditions.
  • If the linkage is set too long, the system will not be able to provide closed throttle or no power conditions. Use the following procedure to ensure the linkage rod is properly adjusted:
1. Start the engine and immediately shut it down. As the engine coasts to a stop, observe from above the engine as the carburetor throttle lever rotates counterclockwise.

Figure 5. Adjusting Throttle Linkage

2. There should be a gap of about 0.003 inch (0.08-0.5mm) between the stop tab on the throttle lever arm and the stop block on the carburetor casting. See Figure 4.

CARBURETOR REMOVAL

To remove the carburetor from the engine, proceed as follows (see Figure 6, next page):

1. Disconnect the carburetor fuel inlet line.

!

2. Loosen the clamp and disconnect the carburetor air inlet hose.
3. Remove the two M6-1.00 x 90mm screws that retain the carburetor.
3. Use pliers to lightly compress the spring clip on the carburetor lever arm (Figure 5). This permits the linkage rod to slide freely through the clip. With the clip compressed, rotate the throttle lever in the appropriate direction until there is a 0.003 inch (0.08-0.5mm) gap.
4. Remove the carburetor air inlet adapter, the air inlet adapter gasket, carburetor and carburetor to skirt gasket.
5. Remove the sheet metal carburetor skirt.
4. Release the spring clip to lock in the adjustment.
6. Remove two gaskets and the carburetor spacer.
Page 66 of the Generac Power Systems 941-2 user manual — Section 3.4 CARBURETOR
Page 66 · click to enlarge
Page 66

Section 3.4 CARBURETOR

Generac Power Systems 941-2 — Section 3.4 CARBURETOR diagram (page 66)
Fig. 69 · Section 3.4 CARBURETOR

Figure 6. Carburetor Removal

Page 67 of the Generac Power Systems 941-2 user manual — OPERATION
Page 67 · click to enlarge
Page 67

Section 3.5 AUTOMATIC CHOKE

GENERAL

OPERATIONAL CHECK AND ADJUSTMENT

The GV-220 vertical shaft engines are equipped with an automatic choke. A choke solenoid is attached to the carburetor choke shaft by means of a choke con- trol link. Solenoid operation is controlled by the A6060 circuit board. The circuit board energizes and de- energizes the solenoid cyclically at a rate dependent on ambient temperature during engine cranking only.

OPERATIONAL CHECK: Crank the engine. During cranking, the choke sole- noid should pull in about every 2 to 5 seconds. If it does NOT pull in, try adjusting the choke.

PRE-CHOKE ADJUSTMENT: With the solenoid NOT pulled in, the carburetor choke valve (choke plate) should be about 1/8 inch from its full open position. If necessary, use needle nose pli- ers to bend the tip of the BI-METAL until a 1/8 inch setting is obtained.

DESCRIPTION

See Figure 1. The CHOKE SOLENOID is retained to a CHOKE COVER by two No. 4-40 SCREWS, LOCK- WASHERS and FLATWASHERS. The two screw holes in the COVER are slotted to provide for axial adjustment of the CHOKE SOLENOID. A COTTER PIN retains a CHOKE LINK to the SOLENOID. A CHOKE BI-METAL & HEATER is retained to the SOLENOID by two No. 4-40 SCREWS, LOCKWASH- ERS and FLATWASHERS.

CHOKE SOLENOID ADJUSTMENT: Loosen the two screws that retain the choke solenoid to its cover. Adjust axial movement of the solenoid plunger by sliding the solenoid in the slotted screw holes of the cover. Adjust plunger axial movement until (with the carbure- tor choke valve closed) the plunger is bottomed in the solenoid coil. That is, until the plunger is at its full actuated position. With the choke valve (choke plate) closed and the plunger bottomed in its coil, tighten the two screws.

Generac Power Systems 941-2 — DESCRIPTION diagram (page 67)
Fig. 70
Generac Power Systems 941-2 — DESCRIPTION diagram (page 67)
Fig. 71

Figure 1. Choke Solenoid Parts

OPERATION

NOTE: Also see Part 6, "ENGINE ELECTRICAL SYSTEM". The section on DC control system includes additional information on choke opera- tion and the A6060 circuit board. When the engine is being cranked, A6060 circuit board action energizes the choke solenoid in regular timed cycles. Each time the choke solenoid is ener- gized, it closes the carburetor choke valve. The circuit board's choke timer circuit energizes the choke sole- noid (pulls it in) about every 2 to 5 seconds. When the engine starts, cranking is terminated. The choke action is then terminated and the choke setting is determined by a choke heater (CH).

Figure 2. Choke Adjustment

Page 68 of the Generac Power Systems 941-2 user manual — Section 3.5 AUTOMATIC CHOKE
Page 68 · click to enlarge
Page 68

Section 3.5 AUTOMATIC CHOKE

Page 69 of the Generac Power Systems 941-2 user manual — STEPPER MOTOR PROBLEMS
Page 69 · click to enlarge
Page 69

Section 3.6 SPEED CONTROL SYSTEM

GENERAL

  • Electrical connections to stepper motor broken or disconnected.
  • Electrical leads to stepper motor are connected wrong.

The AC generator's output voltage is controlled by a "computerized" speed control system. This system changes engine speed in response to changes in the AC output voltage at varying engine loads. The speed control system consists of (a) the A6060 circuit board and (b) a stepper motor.

THROTTLE LINKAGE: Check throttle linkage and carburetor throttle shaft for binding, disconnected linkage. This type of problem will usually result in the carburetor throttle lever not moving. If the throttle lever does not move, the throttle may be stuck at a permanently open throttle or a per- manently closed throttle as follows:

A6060 CIRCUIT BOARD

This circuit board utilizes a closed-loop, proportional- derivative controller circuit which regulates the gener- ator's RMS voltage by changing engine speed. The system attempts to maintain an output voltage of about 115 volts at the lowest rpm and 120 volts up to the maximum rpm. The A6060 circuit board controls a stepper motor by calculating the number of steps the motor needs to take and then supplying the necessary signals to the motor to take those steps.

1. If the throttle is open, engine will start but will accelerate quickly and uncontrollably. It will shut down when speed exceeds about 4200 rpm.
2. If the throttle is closed, engine will not accelerate under load.

STEPPER MOTOR FAILED OR SEIZED: The engine will start but stepper motor will not turn. If an open throttle condition exists, either of the follow- ing might occur:

STEPPER MOTOR PROBLEMS

1. Engine may accelerate and shut down at 4200 rpm.
  • INTRODUCTION: Some stepper motor problems that might occur include the following:
  • Throttle linkage or carburetor throttle shaft sticking, or linkage disconnected.
  • Stepper motor failed or seized.
2. Engine may shut down after 15 seconds due to an overvoltage condition.

If throttle is closed, engine will be unable to acceler- ate under load and AC output will be low. A failed stepper motor may also turn erratically. If this is the case, engine speed and AC output voltage will be erratic under constant load.

Figure 1. Speed Control System

Page 70 of the Generac Power Systems 941-2 user manual — TESTING THE STEPPER MOTOR
Page 70 · click to enlarge
Page 70

Section 3.6 SPEED CONTROL SYSTEM

ELECTRICAL CONNECTIONS BROKEN: If one or more of the electrical connections to the stepper motor are broken or disconnected, either of the following might occur:

Approximately 19-21 ohms should be indicated. b.To the YELLOW wire connector pin. About 19-

21 ohms should be read. c. To the BROWN wire pin for a reading of 19-21

1. The stepper motor may not turn at all.
2. The stepper motor may turn erratically.

ohms. d.To the BLACK wire connector pin for a reading

If the stepper motor does not turn, symptoms will be the same as for a failed or seized stepper motor. LEADS CONNECTED WRONG: Incorrectly connected electrical leads to the stepper motor can result in any one of the following:

of about 19-21 ohms.

TESTING FOR SHORTED CONDITION:

1. Set the VOM to its "Rx10,000" or "Rx1 K" scale and zero the meter.
1. Stepper motor may not turn at all.
2. Connect one VOM test probe to the RED wire connector pin, the other test probe to the Stepper Motor case. The meter should read infinity". Any reading other than "infinity" indicates a shorted winding.
2. Stepper motor may turn erratically.
3. Stepper motor may turn backwards.

If the stepper motor does not turn, engine will start and the following may occur:

Replace the Stepper Motor if it fails any part of the test.

1. If throttle is open, engine will accelerate and shut down when speed reaches 4200 rpm or after 15 seconds due to overvoltage condition.
Generac Power Systems 941-2 — TESTING FOR SHORTED CONDITION: diagram (page 70)
Fig. 72
2. If throttle is closed, engine will be unable to accelerate under load.

If the stepper motor turns erratically, engine speed and AC output voltage will be erratic under a constant load. The AC output will not terminate. If the stepper motor is turning backwards, engine will accelerate and shut down at 4200 rpm.

Figure 2. The Stepper Motor Connector

TESTING THE STEPPER MOTOR

Generac Power Systems 941-2 — TESTING THE STEPPER MOTOR diagram (page 70)
Fig. 73

GENERAL: The Stepper Motor consists of an electric motor plus a small gearbox. It is shown pictorially and schemati- cally in Figure 3. The four (4) motor windings can be tested for (a) continuity and (b) shorts to the case. It is difficult to perform an operational test of the motor since the amount of motor arm movement is so small.

TESTING FOR OPEN CONDITIONTo test the motor windings for an open circuit condition, proceed as follows:
1. Unplug the Stepper Motor connector from its receptacle on the A6060 circuit board.
2. Set a volt-ohm-milliammeter (VOM) to its "Rx1" scale and zero the meter.
3. Connect one VOM test probe to the connector pin to which the RED wire attaches. This is the +DC side of all windings. Then, connect the other VOM test probe as follows:

Figure 3. The Stepper Motor

a.To the ORANGE wire connector pin.

Page 71 of the Generac Power Systems 941-2 user manual — Series Impact 36 Plus
Page 71 · click to enlarge
Page 71

PART 4 GASEOUS FUEL

SECTION TITLE

4.1 INTRODUCTION TO FUEL SYSTEM

SYSTEM

4.2 SHUTOFF VALVE & REGULATOR

4.3 CARBURETOR

COMPUTER CONTROLLED

VARIABLE SPEED RV GENERATORS

Series Impact 36 Plus

Page 72 of the Generac Power Systems 941-2 user manual — NOTES
Page 72 · click to enlarge
Page 72

NOTES

Page 73 of the Generac Power Systems 941-2 user manual — IMPORTANT CONSIDERATIONS
Page 73 · click to enlarge
Page 73

Section 4.1 INTRODUCTION TO FUEL SYSTEM

GENERAL INFORMATION

  • A nearly homogeneous mixture in the engine cylinders.
  • Fuel can be stored for long periods without breakdown.

Some RV generator models are equipped with fuel systems that utilize LP gas as a fuel. The initials "LP" stand for "liquefied petroleum". This gas is highly volatile and can be dangerous if handled or stored carelessly. All applicable laws, codes and regulations pertaining to the storage and handling of LP gas must be com- plied with. The installation of such fuel systems must also be in compliance with such laws, codes and reg- ulations. Service technicians who work on these sys- tems must do nothing that might cause the system to be in non-compliance with regulations. Regulations established by the Recreational Vehicle Industry Association (RVIA) must be followed in the installation, use and servicing of such systems.

FUEL SYSTEM COMPONENTS

When the generator set is shipped from the factory, the following fuel system components are included with the unit:

1. A Fuel Lockoff Solenoid
2. The LP Gas Regulator
3. The carburetor.
4. Interconnecting lines and fittings.

DANGER! LP GAS IS HIGHLY EXPLOSIVE. THE GAS IS HEAVIER THAN AIR AND TENDS TO SETTLE IN LOW AREAS. EVEN THE LIGHTEST SPARK CAN IGNITE THE GAS AND CAUSE AN EXPLOSION. ONLY COMPETENT, QUALIFIED GAS SERVICE TECHNICIANS SHOULD BE ALLOWED TO INSTALL, TEST, ADJUST OR SERVICE THE GASEOUS FUEL SYSTEM. INSTALLATION OF A GASEOUS FUEL SYSTEM MUST BE IN STRICT COMPLIANCE WITH APPLICA- BLE CODES. FOLLOWING INSTALLATION NOTHING MUST BE DONE THAT MIGHT RENDER THE SYSTEM IN NONCOMPLI- ANCE WITH SUCH CODES.

Components that must be added by the generator installer include the following:

!

1. A VAPOR WITHDRAWAL type fuel tank.
2. A PRIMARY REGULATOR that will deliver a fuel pressure to the Fuel Lockoff Solenoid of about 11” water column.
3. Interconnecting lines and fittings.

VAPOR WITHDRAWAL

LP gas is stored in pressure tanks as a liquid. Gaseous fuel system components installed on the generator are designed for "vapor withdrawal" type systems. Such systems use the gas vapors that form above the liquid fuel in the tank. Do not attempt to use any "liquid withdrawal" type tank with the RV generator. NOTE: "Liquid withdrawal" type systems use the liquid fuel from the tank. The liquid fuel must be vaporized before it reaches the carburetor. Fuel vaporization is usually accomplished by porting the liquid fuel through some kind of heating device.

!

IMPORTANT CONSIDERATIONS

ADVANTAGES OF GASEOUS FUELS

  • When servicing the gaseous fuel system the following rules apply:
  • All lines, fittings, hoses and clamps must be free of leaks. Apply pipe sealant to threads when assembling threaded connectors to reduce the possibility of leakage.
  • Following any service, the system must be tested for leaks using APPROVED test methods.
  • Optimum gas pressure at the inlet to the fuel lockoff solenoid and secondary regulator is 11 inches of water column. Do NOT exceed 14 inches water column.
  • The use of gaseous fuels may result in a slight power loss, as compared to gasoline. However, that disadvantage is usually compensated for by the many advantages of gaseous fuels. Some of these advantages are:
  • A low residue content results in minimum carbon formation in the engine.
  • Reduced sludge buildup in the engine oil.
  • Reduced burning of valves as compared to gasoline.
  • No wash-down of engine cylinder walls during cranking and startup.
  • Excellent anti-knock qualities.
Page 74 of the Generac Power Systems 941-2 user manual — EXCESS FLOW VALVE
Page 74 · click to enlarge
Page 74

Section 4.1 INTRODUCTION TO FUEL SYSTEM

IMPORTANT CONSIDERATIONS (CONTINUED)

  • Gaseous fuel lines and primary regulators must be properly sized to deliver adequate fuel flow to the generator engine. The generator requires at least 67 cubic feet of gas per hour for its operation. NOTE: An existing primary regulator may be used to deliver gas to the fuel lockoff solenoid provided It has sufficient flow capacity for the generator and other gas appliances in the circuit. If the existing primary regulator does not have a sufficient capacity (a) replace it with one that has adequate flow capacity, or (b) install a separate primary regulator having at least a 67 cubic feet per hour capacity.
  • NOTE: A PRIMARY REGULATOR, between the tank and the fuel lockoff solenoid, is required to ensure that correct gas pressure is delivered to the lockoff solenoid.
  • The generator installer's connection point is at the fuel lockoff solenoid which has a 3/4 inch (female) connection.
  • A length of flexible hose is required between the fuel lockoff solenoid and rigid fuel piping, to allow for vibration and/or shifting of the unit. This line must be at least six (6) inches longer than necessary.

EXCESS FLOW VALVE

FUEL SUPPLY LINES

Rules established by the National Fire Protection Association (NFPA) and the Recreation Vehicle Industry Association (RVIA) require that the LP gas tank be equipped with an excess flow valve. This valve and the gaseous fuel lines must be carefully sized so the excess flow valve will close in the event of line breakage. Shutoff valves on the fuel supply tank and elsewhere in the system must be fully open when operating the generator. The excess flow valve will function proper- ly only if all valves are fully open and fuel lines are properly sized.

  • When servicing or repairing the gaseous fuel system, the following rules apply to gaseous fuel supply lines:
  • The LP gas lines must be accessible but must also be protected against possible damage.
  • Do NOT connect electrical wiring to any gaseous fuel line. Do NOT route electrical wiring alongside the gaseous fuel lines.
  • Route the gaseous fuel lines AWAY from hot engine exhaust mufflers and piping.
  • Gas lines should be retained with metal clamps that do not have any sharp edges.
Generac Power Systems 941-2 — EXCESS FLOW VALVE diagram (page 74)
Fig. 74

Figure 1. A Typical LP Gas Fuel System

Page 75 of the Generac Power Systems 941-2 user manual — !
Page 75 · click to enlarge
Page 75

Section 4.1 INTRODUCTION TO FUEL SYSTEM

GASEOUS CARBURETION

LEAKAGE TESTING

Gas at positive pressure is delivered from the fuel lockoff solenoid to the inlet of the regulator (about 11- 14 inches of water). As the engine piston moves downward on its intake stroke, air is drawn into the area above the piston through the carburetor venturi. A negative pressure is created at the venturi which is proportional to the amount of air that is flowing. The negative pressure at the carburetor venturi acts on the regulator diaphragm to pull the diaphragm toward the source of low pressure. A lever, attached to the diaphragm, opens a metering valve which allows gas to enter and flow through the carburetor. The greater the air flow through the carburetor ven- turi, the lower the pressure at the venturi throat. The lower the pressure at the venturi throat, the greater the movement of the diaphragm and the more the metering valve opens.

Whenever any lines, fittings or other components of the fuel system have been removed and replaced, the system should be carefully checked for leaks before it is placed into service. To check for leakage, start the engine and let it run. Then use a soap and water solution or an approved commercial leak detector solution to determine if any leakage exists. No leakage is permitted.

DANGER! DO NOT USE FLAME TO CHECK FOR LEAKAGE. GASEOUS FUEL LINES BETWEEN THE TANK AND SECONDARY REGULATOR ARE UNDER A POSITIVE PRES- SURE (ABOUT 11 INCHES OF WATER COL- UMN). HOWEVER, GAS PRESSURE AT THE OUTLET SIDE OF THE SECONDARY REGU- LATOR IS A NEGATIVE PRESSURE (ABOUT 1 INCH WATER COLUMN). THIS NEGATIVE PRESSURE CAN DRAW FLAME INSIDE A LINE OR FITTING AND CAUSE AN EXPLO- SION.

!

Generac Power Systems 941-2 — ! diagram (page 75)
Fig. 75

Figure 2. Gas Carburetion Diagram

  • The following requirements of the secondary regulator must be emphasized:
  • It must be sensitive to pressure changes in the carburetor venturi throughout the entire operating range.
  • It must positively stop the flow of gas when the engine is not running.
  • The slightest air flow through the carburetor venturi must move the regulator valve off its seat and permit gas flow.
Page 76 of the Generac Power Systems 941-2 user manual — Section 4.1 INTRODUCTION TO FUEL SYSTEM
Page 76 · click to enlarge
Page 76

Section 4.1 INTRODUCTION TO FUEL SYSTEM

Page 77 of the Generac Power Systems 941-2 user manual — TESTING THE FUEL LOCKOFF SOLENOID
Page 77 · click to enlarge
Page 77

Section 4.2 SHUTOFF VALVE AND REGULATOR

GENERAL

ADJUSTMENTS

See Figure 1. The fuel shutoff valve (lockoff solenoid) and the secondary regulator are retained to a flat mounting bracket which, in turn, mounts to the gener- ator base cover. The fuel lockoff solenoid is retained to the mounting bracket by means of a u-bolt. The secondary regulator is retained to the mounting bracket with two 1/4"-20 x 3/4" long capscrews.

There are no adjustments on the fuel lockoff solenoid or the secondary regulator. This system is NOT equipped with a load block.

THE LP GAS REGULATOR

The secondary regulator is a GARRETSON® Model KN. It is designed for simplicity and simple operation. The regulator is suitable for use with low pressure vaporized gaseous fuels where dependable starting is a requirement. Recommended inlet pressure to the regulator is 11 inches water column. The regulator comes with a 3l4 inch NPT fuel inlet and a 3/8 inch NPT fuel outlet. The LOCKOFF ADJUSTMENT SCREW shown in Figure 2 has been preset at the factory. No additional adjustment is authorized.

ITEM QTY DESCRIPTION

1 1 LP Gas Regulator

2 1 Fuel Lockoff Solenoid

3 1 U-Bolt-1.25" wide (5/16"-i 8)

4 2 3/4" NPT Street Elbow

5 1 3/4" NPT Close Nipple

6 1 3/8" NPT Street Elbow

7 1 1/2" x 3/8" NPT Fitting

8 1 Hose Clamp

9 1 1/2" ID Hose (11.5" long)

Generac Power Systems 941-2 — ITEM QTY DESCRIPTION diagram (page 77)
Fig. 76

10 2 1/4"-20 x 3/4" Capscrew

11 2 1/4" Lockwasher

12 2 5/16" Lockwasher

13 2 5/16"-18 Hex Nut

14 1 Regulator Mounting Bracket

15 1 Sleeving (9" long)

Generac Power Systems 941-2 — ITEM QTY DESCRIPTION diagram (page 77)
Fig. 77

Figure 2. LP Gas Regulator

!

TESTING THE FUEL LOCKOFF SOLENOID

GENERAL: The fuel lockoff solenoid is energized open by 12 volts DC power from the A6060 circuit board during engine cranking. The solenoid can also be energized open without cranking by actuating the fuel primer switch on the generator panel.

Figure 1. Shutoff Valve & Regulator

(Continued)

Page 78 of the Generac Power Systems 941-2 user manual — RESULTS OF TEST:
Page 78 · click to enlarge
Page 78

Section 4.2 SHUTOFF VALVE AND REGULATOR

TEST PROCEDURE:

Generac Power Systems 941-2 — Section 4.2 SHUTOFF VALVE AND REGULATOR diagram (page 78)
Fig. 78 · Section 4.2 SHUTOFF VALVE AND REGULATOR
1. Set a volt-ohm-milliammeter (VOM) to read battery voltage (12 VDC).
2. Connect the VOM test leads across Wire 14 (Red) at the solenoid and a clean frame ground. 3. Set the fuel primer switch on the generator panel to its ON position. a. The meter should indicate battery voltage. b. The solenoid should energize open.

RESULTS OF TEST:

1. If battery voltage is Indicated but the solenoid does NOT energize, replace the lockoff solenoid.
2. If battery voltage is NOT Indicated, a problem exists In the DC control system. See Parts 6, "ENGINE ELECTRICAL SYSTEM". Figure 3. Fuel Lockoff Solenoid
Page 79 of the Generac Power Systems 941-2 user manual — CARBURETOR REMOVAL
Page 79 · click to enlarge
Page 79

Section 4.3 CARBURETOR

GENERAL

DISASSEMBLY AND REASSEMBLY

The carburetor is designed for use with LP gas in its vapor form. The following specifications apply:

The carburetor is replaced as an entire assembly. Disassembly and reassembly is not required.

Carburetor Inlet Diameter 1.02inch (26mm) Carburetor Outlet Diameter 0.78 inch (20mm) Venturi Diameter 0.63 inch (16mm)

Generac Power Systems 941-2 — Section 4.3 CARBURETOR diagram (page 79)
Fig. 79 · Section 4.3 CARBURETOR

Number 370 Measured Size 0.145 inch (3.7mm)

CARBURETION

Refer to "Gaseous Carburetion" in Section 4.1 (Page 4.1-3).

CARBURETOR ADJUSTMENT

The LP gas carburetor used on Impact Plus generator sets is equipped with a fixed jet and is non-adjustable.

CARBURETOR REMOVAL

Figure 1. LP Gas Carburetor

Refer to Part 3, Section 3.4, Page 3.4-3 for carburetor removal procedures.

Main Jet Diameter

Page 80 of the Generac Power Systems 941-2 user manual — Section 4.3 CARBURETOR
Page 80 · click to enlarge
Page 80

Section 4.3 CARBURETOR

Page 81 of the Generac Power Systems 941-2 user manual — SECTION TITLE
Page 81 · click to enlarge
Page 81

PART 5 ENGINE OIL & COOLING SYSTEM

SECTION TITLE

5.1 ENGINE OIL SYSTEM

5.2 ENGINE COOLING SYSTEM

COMPUTER CONTROLLED

VARIABLE SPEED RV GENERATORS

Series Impact 36 Plus

Page 82 of the Generac Power Systems 941-2 user manual — NOTES
Page 82 · click to enlarge
Page 82

NOTES

Page 83 of the Generac Power Systems 941-2 user manual — OIL PICKUP SCREEN
Page 83 · click to enlarge
Page 83

Section 5.1 ENGINE OIL SYSTEM

INTRODUCTION TO OIL SYSTEM

INSPECTION: To gain access to the screen, remove the oil filter support and its gasket. Pull the screen off its tubular protrusion. Clean the screen in solvent, then inspect for damage. Replace the screen if necessary.

  • The engine oil system serves to (a) reduce friction between parts, (b) cool the engine, and (c) establish a slightly negative pressure in the crankcase to prevent oil leakage. Major components that will be discussed in this section include the following:
  • Oil Pickup Screen.
  • Oil Pump.
  • Crankshaft Oil Seals.
  • Pressure Relief Valve.
  • Breather Assembly.
  • Oil Sump.
  • Oil Filter Support Assembly.

OIL PUMP

DESCRIPTION: The oil pump is of the trochoid type. Its inner rotor rotates on a shaft provided in the camshaft bore of the oil sump. The outer rotor is installed over two drive pins on the end of the camshaft and is driven by camshaft rotation.

Generac Power Systems 941-2 — OIL PUMP diagram (page 83)
Fig. 80

OIL FLOW

See Figure 1. The oil pump draws oil from the oil sump through an oil pickup screen and delivers it to the areas requiring lubrication as follows:

1. Through a cored channel in the oil sump to the crankcase journal at one end of the crankshaft.
2. Through the hollow camshaft to the camshaft bearing.
3. Through a cored passage in the crankcase to the crankshaft journal.
4. Through the crankshaft to the crankpin and connecting rod bearing.

Figure 2. Oil Pump

INSPECTION: See Figure 3. Inspect the inner and outer rotors of the pump for damage and wear. Use a feeler gauge to check tip clearance of the rotor (measured on the shaft in the oil sump). Check the bore inner diameter and the thickness of the inner rotor. If wear limits are exceeded, replace the appropriate part(s).

Generac Power Systems 941-2 — OIL FLOW diagram (page 83)
Fig. 81

PUMP TIP CLEARANCE (MEASURED ON SHAFT IN OIL SUMP) DESIGN CLEARANCE: 0.0000-0.0010 inch

(0.000-0.025mm) WEAR LIMIT0.004 inch (0.105mm) Maximum

INNER PUMP ROTOR BORE DESIGN BORE: 0.354-0.355 inch (9.000-9.019mm)

Figure 1. Oil System Diagram

WEAR LIMIT0.357 inch (9.034mm) Maximum
INNER ROTOR THICKNESS DESIGN THICKNESS0.312-0.315 inch (7.95-8.00mm)

OIL PICKUP SCREEN

WEAR LIMIT0.311 inch (7.90mm) Minimum

Replace any part that is damaged or worn excessive- ly. The shaft on which the inner rotor rotates is NOT replaceable (oil sump must be replaced).

DESCRIPTION: The oil pickup screen consists of a cylindrical screen which is open at one end only. The screen's open end fits over a tubular protrusion in the oil sump, just behind the oil filter support. Also see "Oil Filter Support Assembly".

Page 84 of the Generac Power Systems 941-2 user manual — BREATHER ASSEMBLY
Page 84 · click to enlarge
Page 84

Section 5.1 ENGINE OIL SYSTEM

OIL PUMP (CONTINUED)

PRESSURE RELIEF VALVE

INSPECTION (CONT'D): Inspect the outer drive pins on the camshaft. Look for breakage, bending, other damage. These are roll pins which can be removed and replaced.

DESCRIPTION: A ball type pressure relief valve is located in a bore of the crankcase. The ball and spring are retained in the crankcase bore by a spring retainer. The Relief Valve serves to limit oil pressure to a maxi- mum value. The ball will remain against its seat as long as oil pressure in the crankcase ail passage is below approximately 30 psi (29 kg/cm ). Should oil pressure increase above that value, the ball will be forced off its seat to relieve excess pressure into the crankcase.

Generac Power Systems 941-2 — Section 5.1 ENGINE OIL SYSTEM diagram (page 84)
Fig. 82 · Section 5.1 ENGINE OIL SYSTEM

1. SCREW 2. RETAINER 3. SPRING 4. BALL

Figure 3. Oil Pump Check Points

CRANKSHAFT OIL SEALS

An oil seal is provided in the crankcase and in the oil sump, to prevent leakage past the crankshaft jour- nals. See Figure 4. A defective or leaking seal can be replaced. If the crankshaft has been removed from the engine, old seals can be removed by tapping out with a screw- driver or punching them out from inside. Oil seal pullers are available commercially, for seal removal with the crankshaft installed. Always use a seal protector when installing the crank- shaft into its crankcase bore and when installing the oil sump over the crankshaft.

Figure 5. Oil Pressure Relief Valve

INSPECTION: Remove the 8mm screw that retains the spring RETAINER to the crankcase interior. Remove the RETAINER, SPRING and BALL. Clean all parts in solvent. Inspect the BALL and RETAINER for damage, exces- sive wear. Replace any damaged or worn compo- nents. Inspect the SPRING and replace if damaged or worn. Apply a known test load to the SPRING, sufficient to compress the spring to a length of 1.03 inch (26.3mm). The amount of the test load at the stated spring length should be as follows:

Generac Power Systems 941-2 — CRANKSHAFT OIL SEALS diagram (page 84)
Fig. 83

FORCE REQUIRED TO COMPRESS RELIEF VALVE SPRING TO 1.03 INCH (26.3mm)

0.86-0.95 pounds (0.43-0.39 kg) If the test load at the stated length is not within limits, replace the SPRING.

BREATHER ASSEMBLY

DESCRIPTION: A crankcase breather is located in the crankcase assembly.

Figure 4. Crankshaft Oil Seals

Page 85 of the Generac Power Systems 941-2 user manual — OIL SUMP
Page 85 · click to enlarge
Page 85

Section 5.1 ENGINE OIL SYSTEM

The breather serves to maintain a partial vacuum in the engine crankcase, to prevent oil from being forced past oil seals, gaskets or rings. See Figure 6. A reed type breather valve permits excess pressure to be vented out of the crankcase and to atmosphere through a breather tube. A breather retainer limits the movement of the breather valve. Two small oil return holes in the breather cup allow condensed oil vapors to drain back to the crankcase. A "steel wool" type breather separator separates the breather cup from the breather cover and breather tube opening.

INSPECTION: Clean the oil sump and blow dry with compressed air. Use compressed air to blow out all oil passages. Inspect the sump for cracks, damage, etc. Check the following bores in the oil sump for wear:

CRANKSHAFT BEARING BORE DIAMETER

GV-220 ENGINE DESIGN DIAMETER1.104-1.105 inch (28.040-28.065mm)
WEAR LIMIT1.106 inch (28.092mm) Maximum

CAMSHAFT BEARING BORE DIAMETER

GV-220 ENGINE DESIGN DIAMETER1.299-1.300 inch (33.00-33.03mm)
Generac Power Systems 941-2 — CAMSHAFT BEARING BORE DIAMETER diagram (page 85)
Fig. 84
WEAR LIMIT1.302 inch (33.06mm) Maximum

OIL PUMP INNER ROTOR SHAFT DIAMETER

GV-220 ENGINE DESIGN DIAMETER0.353-0.354 inch (8.969-8.987mm)
WEAR LIMIT0.352 inch (8.949mm) Minimum

OIL FILTER SUPPORT

An oil filter support and its gasket are retained to the oil sump by four (4) M6-1.00 bolt. A threaded bore is provided in the support for a low oil pressure switch. This switch will protect the engine against damaging low oil pressure by shutting the engine down automatically if oil pressure should drop below a pre-set low limit. A high oil temperature switch is retained to the sup- port by two (2) M5 screws and lockwashers. This thermal sensor will protect the engine against damag- ing high temperature conditions through automatic shutdown.

Figure 6. Breather Assembly

INSPECTION: Remove the breather hose. Inspect it for cracks, dam- age, hardening. Replace, if necessary. Clean the breather cover and breather cup in com- mercial solvent. Check that the two small drain holes in the breather cup are open; open with a length of wire, if necessary. Inspect the rivets that retain the reed type breather valve, make sure they are tight. Also check that the valve seats flat on the breather cup around the entire surface of the valve.

Generac Power Systems 941-2 — OIL FILTER SUPPORT diagram (page 85)
Fig. 85

OIL SUMP

DESCRIPTION: The die cast aluminum oil sump is retained to the crankcase with six (6) flanged head bolts. Install a new gasket between the oil sump and crankcase each time the oil sump is removed. Bores are provided in the oil sump for (a) oil pump rotors and camshaft, (b) crankshaft, (c) governor gear assembly, (d) oil pickup. Cored oil passages are pro- vided from the pickup to the pump and from the pump to the crankshaft bore.

Figure 7. Oil Filter Support

Page 86 of the Generac Power Systems 941-2 user manual — Section 5.1 ENGINE OIL SYSTEM
Page 86 · click to enlarge
Page 86

Section 5.1 ENGINE OIL SYSTEM

Page 87 of the Generac Power Systems 941-2 user manual — COOLING AIR INLET OPENINGS
Page 87 · click to enlarge
Page 87

Section 5.2 ENGINE COOLING SYSTEM

It is absolutely essential that an adequate flow of air for cooling, ventilating and engine combustion be sup- plied to the generator set. Without sufficient air flow, the engine-generator quickly overheats. Such over- heating can cause serious operating difficulties and may also cause fire and personal injury. The installer must make sure that sufficient air is available to the generator for cooling, ventilating and combustion. The installer must also provide for a path for exhausting the cooling air to the exterior of a compartment, if so equipped.

10 SQUARE INCHES (OPTIONAL OPENINGS)

40 SQUARE INCHES (MINIMUM OPENING)

GENERATOR AIR FLOW

Engine operation drives cooling fans for the 2-stage cooling air system. A pressure fan draws cooling air into the top of generator and into the side of the con- trol panel (Figure 1). This air flow cools the engine- generator and electronic components. The second part of cooling system, a suction fan, draws air that is heated from a hot engine into a collector pan at the base of the unit. This heated air (although cooler than exhaust muffler) is directed across the muffler to cool it. The heated air flow is then deflected out the bottom toward the ground.

Figure 2 — Air Inlet in Compartment Door

IMPORTANT: IF YOU PLAN TO INSTALL THE GENERATOR IN A COMPARTMENT, BE SURE TO LEAVE AT LEAST ONE INCH (2” recom- mended) OF CLEARANCE BETWEEN THE GEN- ERATOR AND COMPARTMENT WALLS AND CEILING. INCLUDE 26 GAUGE GALVANIZED STEEL LINING AND SOUND INSULATION WHEN YOU MEASURE FOR THIS 1 INCH (2” recom- mended) CLEARANCE. When the unit is installed on a suspended mounting system, one of several different methods of supplying air flow may be used as follows: • Provide a door in the vehicle skirt having an air inlet opening (Figure 3, next page).

Generac Power Systems 941-2 — 10 SQUARE INCHES (OPTIONAL OPENINGS) diagram (page 87)
Fig. 86
  • Using ductwork (Figure 4 on next page). The installer must be sure air is available to the top of the generator since air inlets are located at the top.
  • By providing an opening in the vehicle skirt and space above the generator for cooling air flow (Figure 5 on next page). Recommended clearance above the top of the generator is at least 2 inches.

Figure 1 — Air Flow Through Engine-Generator

COOLING AIR INLET OPENINGS

Ideally, you should provide three air inlet openings, whether the generator is housed in a conventional compartment or not. Two of the openings should be 10 square inches and located as shown in Figure 2. The third opening should provide for a minimum of 40 square inches unrestricted and be located lower on the compartment door.

Page 88 of the Generac Power Systems 941-2 user manual — TESTING THE INSTALLATION
Page 88 · click to enlarge
Page 88

Section 5.2 ENGINE COOLING SYSTEM

COMPENSATING FOR RESTRICTIONS

Generac Power Systems 941-2 — Section 5.2 ENGINE COOLING SYSTEM diagram (page 88)
Fig. 87 · Section 5.2 ENGINE COOLING SYSTEM

Such materials as screening, louvers, or expanded metal can restrict the free flow of air. Compensate for this restriction by making the actual air opening pro- portionately larger. Some materials may offer only a 60 percent “free air inlet area.” Other more efficient materials may provide up to a 90 percent free air inlet area. The percentage of free air inlet opening is usually available from the material supplier or manufacturer. TO DETERMINE THE ACTUAL AIR INLET OPEN- ING SIZE REQUIRED, DIVIDE 40 SQUARE INCHES BY THE PERCENTAGE OF FREE AIR INLET AREA FOR THE MATERIAL YOU WILL USE. For example: If you plan to use screening with an 80% free air inlet area, divide 40 by 0.8, which results in 50 square inches. Minimum actual size of air inlet opening in this case is 50 square inches. An opening that measures 4 inches wide by 12-1/2 inches long provides the required air flow (4 x 12.5 = 50 square inches).

Figure 3 — Suspended Mount Inlet Door

Generac Power Systems 941-2 — Section 5.2 ENGINE COOLING SYSTEM diagram (page 88)
Fig. 88 · Section 5.2 ENGINE COOLING SYSTEM

INVERTER LOCATION

In order for the inverter to work effectively, it should be located in a dry, well ventilated area. Approximately eight inches of space should be allowed at each end of the inverter for adequate ven- tilation. The sensing harnesses supplied with the inverter have a maximum length of 12 feet. If the cables are longer than needed, coil the excess near the inverter unit. If a greater length is needed, contact Generac. DO NOT ATTEMPT TO SHORTEN OR LENGTHEN THE SUPPLIED sensing harnesses. The DC power wires may be cut to the required length. Allow enough length to make connection. Coil excess inside J-Box.

Figure 4. Ductwork

Generac Power Systems 941-2 — INVERTER LOCATION diagram (page 88)
Fig. 89

!

TESTING THE INSTALLATION

Generac recommends testing the installation to be sure adequate cooling air flow is available to the unit before placing the unit into service. If the unit shows signs of overheating, you will need to enlarge the air openings. Never place a unit into service until absolutely certain that cooling and ven- tilation is adequate. IMPORTANT: YOU MUST TEST THE INSTALLA- TION ESPECIALLY IF YOU BRING IN AIR FROM BELOW THE GENERATOR SET.

Figure 5 — Air Inlet in Vehicle Skirt

Page 89 of the Generac Power Systems 941-2 user manual — SECTION TITLE
Page 89 · click to enlarge
Page 89

PART 6 ENGINE ELECTRICAL

SECTION TITLE

6.1 ENGINE DC CONTROL SYSTEM

6.2 A6060 CIRCUIT BOARD

SYSTEM

6.3 ENGINE CRANKING SYSTEM

6.4 ENGINE IGNITION SYSTEM

COMPUTER CONTROLLED

6.5 ENGINE SHUTDOWN FEATURES

6.6 OPTIONAL REMOTE PANEL

VARIABLE SPEED RV GENERATORS

Series Impact 36 Plus

Page 90 of the Generac Power Systems 941-2 user manual — NOTES
Page 90 · click to enlarge
Page 90

NOTES

Page 91 of the Generac Power Systems 941-2 user manual — Section 6.1 ENGINE DC CONTROL SYSTEM
Page 91 · click to enlarge
Page 91

Section 6.1 ENGINE DC CONTROL SYSTEM

GENERAL

3. Engine Ignition System Components.

a.Ignition Module (IM). b.Ignition Sensor (IS). c. Ignition Coil (IC). d.Spark Plug (SP).

The engine DC control system consists of all those electrical components required for cranking, starting and running the engine. These components include the following:

1. Engine cranking system components
4. Engine Protective Devices a. Low Oil Pressure Switch (LOP). b. High Oil Temperature Switch (HTO).

a.A 12 VDC battery. b.A Start-Run-Stop Switch (SW1). c. A Starter Contactor (Starter Relay)-(SC). d.A Starter Motor (SM).

5. An optional Remote Panel.
2. Fuel system components..

a.A Fuel Primer Switch (SW2). b.Fuel Pump (FP).

Generac Power Systems 941-2 — Section 6.1 ENGINE DC CONTROL SYSTEM diagram (page 91)
Fig. 90 · Section 6.1 ENGINE DC CONTROL SYSTEM

Figure 1. Schematic- Engine DC Control System

(continued)

Page 92 of the Generac Power Systems 941-2 user manual — ENGINE NOT RUNNING:
Page 92 · click to enlarge
Page 92

Section 6.1 ENGINE DC CONTROL SYSTEM

HOW IT WORKS

ENGINE NOT RUNNING:

1. Battery output (12VDC) is available to the contacts of a starter contactor (SC). However, the contacts are open.

RUNNING: With fuel flow and ignition available, the engine starts and runs. The operator releases the Start-Run-Stop switch to its "RUN" position.

2. Battery output is delivered to Terminals J2 - 5 of the A6060 circuit board, via Wire 13, a 15 amp fuse, and Wire 15. Circuit board action holds this circuit open.
1. The Wire 18 circuit is now open to ground. Circuit board action terminates the 12 VDC to the Starter Contactor (SC). The SC contacts open and cranking ends.
3. Battery output is available to a Battery Charge Rectifier (BCR) via Wire 13, 15 amp Fuse (F1), Wire 15, a Resistor (R1) and Wire 15A.
2. Choking action ends and the carburetor choke plate is positioned by the Choke Heater (CH).

PRIMING: When the Primer Switch (SW2) is closed, battery volt- age is delivered to the engine Fuel Pump via Wire 13, 7.5 Amp Fuse (F1), the Switch contacts (SW2) and Wire 14A. The Fuel Pump will operate to draw fuel from the tank and "prime" the fuel lines. NOTE: On units with LP gas fuel system, the Fuel Lockoff Solenoid (FS) will be turned on by closing the Primer Switch.

3. Circuit board action continues to power the Wire 14 circuitfuel flow and ignition continue.

NORMAL SHUTDOWN: When the Start-Run-Stop switch is held at "STOP", the Wire 18 circuit is connected to frame ground. A6060 circuit board action then terminates the DC flow to the Wire 14 circuit.

1. Fuel Pump (FP) shuts down.

CRANKING: When the Start-Run-Stop Switch is held at "START", the Wire 17 circuit from the A6060 circuit board is connected to frame ground. Circuit board action then initiates the following events:

2. Ignition terminates.
3. Engine shuts down.

ENGINE PROTECTIVE DEVICE SHUTDOWN: Refer to "Oil Filter Support" on Page 5.1-3 and Section 6.5. The engine mounts a Low Oil Pressure Switch (LOP) and a High Oil Temperature Switch. Section 6.5 also lists several other shutdown capabili- ties of the Impact Plus generator system.

1. Battery voltage is delivered to the Starter Contactor (SC) coil via Wire 56.

a.The SC coil energizes and its contacts (SC)

close after a few seconds. b.Closure of SC contacts deliver battery voltage to

the Starter Motor (SM1) via Wire 16. The engine cranks.

2. Battery voltage is delivered to the Wire 14 circuit.

a.The Fuel Pump (FP) turns on. b.Power is available to the Ignition Module (IM)

and ignition occurs. c. Power is available to the Inverter Fan for opera-

tion.

3. A6060 circuit board action operates the automatic choke through Wire 90.
Page 93 of the Generac Power Systems 941-2 user manual — CIRCUIT BOARD CONNECTIONS
Page 93 · click to enlarge
Page 93

Section 6.2 A6060 CIRCUIT BOARD

GENERAL

The A6060 circuit board controls all phases of engine operation including cranking, starting, running and shutdown. The circuit board interconnects with other compo- nents of the engine electrical system. The board Is powered by fused 12 VDC battery out- put, available to the board via Wire 15.

Figure 2. Receptacle J2

PIN WIRE FUNCTION

1 — Not Used

3 85 When grounded by Low Oil Pressure or High Oil Temperature Switch, the circuit board will shut down the engine

4 17 When Wire 17 is connected to ground by holding Start-Run Stop Switch at START, cranking will occur.

Figure 1. A6060 Circuit Board

5 15 Fused battery voltage. The Wire 15 circuit is electrically hot at all times (provided the unit battery is connected).

CIRCUIT BOARD CONNECTIONS

RECEPTACLE J1: The A6060 circuit board mounts an 8-pin receptacle J1. An 8-pin connector plug connects to the A6060. This harness then connects to a 9-pin connector plug on the outside panel of the control box. This becomes the 9-wire harness that connects to the inverter. Signals from the A6060 circuit board control the func- tions of the inverter.

6 0 Common frame ground.

7 90 Delivers 12 VDC to automatic choke solenoid coil while cranking only.

8 56 Delivers 12 VDC to starter contactor while cranking only.

9 14 Delivers 12 VDC (during cranking and run ning) to (a) Engine Fuel System, (b) Engine Ignition System and (c) Remote Panel Lamp if so equipped.

RECEPTACLE J2: The A6060 circuit board mounts a 10-pin receptacle J2. A 10-pin connector plug connects to this recepta- cle to interconnect the board with other components and circuits. This 10-pin receptacle is shown in Figure 2, along with a chart that Identifies each pin, wire and function. Wire 14 connects to Terminal J2-9. This terminal and wire are electrically hot (12 volts DC) only when the engine is cranking or running. Battery voltage is deliv- ered to Terminal J2-9 when circuit board action ener- gizes a board-mounted run relay while cranking or running. Wire 14 DC output is delivered to (a) the engine fuel pump and (b) the engine ignition system. If an option- al remote panel Is used, Wire 14 DC output will turn on a "RUN" lamp on that panel. Wire 15 connects to Terminal J2-5. This Is fused bat- tery voltage. The Wire 15 circuit is electrically hot at all times (provided the unit battery Is connected).

10 — Not Used

RECEPTACLE J3: The A6060 circuit board mounts a 6-pin receptacle J3. A 6-pin connector plug connects to the A6060. This harness then connects to Stepper Motor. Signals from the A6060 circuit board control the Stepper Motor operation. Refer to page 3.6-1 for test proce- dures.

(continued)

Page 94 of the Generac Power Systems 941-2 user manual — Section 6.2 A6060 CIRCUIT BOARD
Page 94 · click to enlarge
Page 94

Section 6.2 A6060 CIRCUIT BOARD

CIRCUIT BOARD CONNECTIONS

(CONTINUED)

RECEPTACLE J4: The A6060 circuit board mounts a 3-pin receptacle J4. A 3-pin connector plug connects to the A6060. This harness then connects to Bridge Rectifier. DC Link Voltage is supplied to the circuit board for volt- age sensing.

RECEPTACLE J5: The A6060 circuit board mounts a 2-pin receptacle J5. A 2-pin connector plug connects to the A6060. This harness then connects to TIM1/TIM2. The A6060 circuit board uses this signal for speed sensing.

Page 95 of the Generac Power Systems 941-2 user manual — BATTERY CABLE CONNECTIONS:
Page 95 · click to enlarge
Page 95

Section 6.3 ENGINE CRANKING SYSTEM

INTRODUCTION

BATTERY

  • COMPONENTS: The engine cranking system is shown schematically in Figure 1, below. The system consists of the following components:
  • A 12 volts Battery.
  • A Start-Run-Stop Switch (SW1).
  • A Starter Contactor (SC).
  • A Starter Motor (SM1).
  • A6060 Circuit Board.
  • Interconnecting wires.
  • RECOMMENDED BATTERY: The battery is generally supplied by the customer. Recommended is a battery that meets the following requirements:
  • Use a 12 VDC automotive type storage battery.
  • For prevailing ambient temperatures above 32° F. (0° C.), use a battery rated at 70 amp-hours and capable of delivering 360 cold-cranking amperes.
  • For prevailing ambient temperatures below 32° F. (0° C.), use a battery rated 95 amp-hours and capable of delivering 450 cold-cranking amperes.

OPERATION:

BATTERY CABLES: Battery cables should be as short as possible and of adequate diameter. Cables that are too long or too small in diameter can result in voltage drop. The volt- age drop between battery terminals and the connec- tion point at generator should not exceed 0.121 volts per 100 amperes of cranking current. The cables should be carefully selected based on (a) cable length and (b) prevailing ambient temperatures. Generally, the longer the cable and the colder the ambient temperature, the larger the required cable size. The following chart applies:

1. Holding the Start-Run-Stop switch (SW1) at "START" connects Wire 17 from the A6060 circuit board to frame ground.

a.A6060 circuit board action energizes a crank

relay on the board after a three second delay. b.Closure of the crank relay's contacts delivers 12

VDC to Wire 56 and to a Starter Contactor (SC). The Starter Contactor (SC) energizes and its contacts close.

2. Closure of the the Starter Contractor (SC) contacts delivers battery voltage to the Starter Motor (SM1). The Motor energizes and the engine is cranked.

CABLE LENGTH CABLE SIZE Feet (Meters) 0 to 10 (0 to 3) 2* 11 to 15 (3.4-4.5) 0 16 to 20 (4.5 to 6) 000

* For warm weather use No. 2 cable up to 20 feet.

BATTERY CABLE CONNECTIONS:

1. Connect the cable from the large Starter Contactor (SC) lug to the battery post indicated by a POSITIVE, POS or (+).
2. Connect the cable from its FRAME GROUND connection to the battery post indicated by a NEGATIVE, NEG or (-).

Figure 1. Schematic - Cranking Circuit

(continued)

Page 96 of the Generac Power Systems 941-2 user manual — START-RUN-STOP SWITCH (SW1)
Page 96 · click to enlarge
Page 96

Section 6.3 ENGINE CRANKING SYSTEM

BATTERY (CONTINUED)

1. Set the VOM to its "Rx1 " scale and zero the meter.
2. Connect the VOM test leads across the Wire 17 terminal and the center (Wire 0) terminals.

TESTING A BATTERY: The best method of testing a battery is with an auto- motive type battery hydrometer. Some "Maintenance Free" batteries cannot be tested with a hydrometer. Most batteries can be tested for both STATE OF CHARGE and CONDITION as follows:

a.Hold the switch at "START" and the VOM

should indicate "continuity". b.Hold switch at "STOP" and meter should read

"infinity".

3. Now, connect the meter test leads across the center and Wire 18 terminals.
1. Test for State of Charge:

a.Follow the hydrometer manufacturer's instruc-

tions carefully. Test the specific gravity of the fluid in all battery cells. b.If the hydrometer does not have a "Percentage

a.With switch at "START" VOM should indicate

"infinity". b.With switch at "STOP", meter should read "con-

of Charge" scale, compare the readings obtained with the following:

tinuity".

Replace the switch if it is defective.

SPECIFIC GRAVITY PERCENTAGE OF CHARGE

1.260 100%

STARTER CONTACTOR

1.230 75%

1.200 50%

WIRE AND CABLE CONNECTIONS: The red (positive) battery cable connects to one of the starter contactor's large terminal lugs. The unit's 15 amp fuse also attaches to this lug, via Wire 13. The starter motor (SM1) cable (16) attaches to the second terminal lug. Wire 56, from the A6060 circuit board, attaches to one of the small contactor terminals.

1.170 25%

If the battery State of Charge is less than 100%, use an automotive type battery charger to recharge it to a 100% State of Charge.

2. Test for Condition:

a.If the difference in specific gravity between the

highest and lowest reading cell is greater than 0.050 (50 points), the battery is nearing the end of its useful life and should be replaced. b.However, if the highest reading cell is less than

TESTING THE STARTER CONTACTORTo test the installed Starter Contactor, proceed as follows:
1. Set a volt-ohm-milliammeter (VOM) to read battery voltage (12 VDC).

1.230, recharge the battery and repeat the test.

2. Connect the VOM test leads across the Wire 56 terminal of the Contactor and frame ground. The meter should indicate "zero" volts.

START-RUN-STOP SWITCH (SW1)

Wires 17 and 18 connect to the two outer terminals of the switch. Wire 0 (ground) connects to the switch center termi- nal. The switch can be tested using a volt-ohm-milliamme- ter (VOM) as follows:

3. Hold the Start-Run-Stop switch at "START" and the VOM should read battery voltage and the Contactor should energize. After reading the voltage, release the switch. If battery voltage is NOT indicated, a problem exists elsewhere in the circuit.
Generac Power Systems 941-2 — START-RUN-STOP SWITCH (SW1) diagram (page 96)
Fig. 91
4. Connect the VOM test leads across the Wire 16 terminal lug and frame ground.

a.Hold the Start-Run-Stop switch at "START". The

Contactor should actuate and the meter should indicate battery voltage. b.If battery voltage is not indicated, replace the

Starter Contactor. c. If battery voltage is indicated but engine does

Figure 2.

not crank, check the Starter Motor and its cable.

Page 97 of the Generac Power Systems 941-2 user manual — Section 6.3 ENGINE CRANKING SYSTEM
Page 97 · click to enlarge
Page 97

Section 6.3 ENGINE CRANKING SYSTEM

STARTER MOTOR

Generac Power Systems 941-2 — Section 6.3 ENGINE CRANKING SYSTEM diagram (page 97)
Fig. 92 · Section 6.3 ENGINE CRANKING SYSTEM

DESCRIPTION: The Starter Motor is a 12 volts negative ground type. It is capable of operating on heavy duty battery input at temperatures as low as -30 F. without any signifi- cant change in performance. Its pinion is a 10-tooth type having a 20- pressure angle.

TESTING: Connect the test leads of a VOM across the Starter Motor terminal and case. Hold the Start-Run-Stop switch at "START". The VOM should read battery voltage and the Starter Motor should turn. If VOM reads 12 volts DC and the Motor does not turn, the Motor is probably defective. Remove the Motor and test with a 12 volts DC power source. Replace the Starter Motor if defective.

Figure 3. Starter Contactor

Generac Power Systems 941-2 — Section 6.3 ENGINE CRANKING SYSTEM diagram (page 97)
Fig. 93 · Section 6.3 ENGINE CRANKING SYSTEM

Figure 4. Starter Motor

Page 98 of the Generac Power Systems 941-2 user manual — Section 6.3 ENGINE CRANKING SYSTEM
Page 98 · click to enlarge
Page 98

Section 6.3 ENGINE CRANKING SYSTEM

Page 99 of the Generac Power Systems 941-2 user manual — IGNITION MODULE
Page 99 · click to enlarge
Page 99

Section 6.4 ENGINE IGNITION SYSTEM

INTRODUCTION

As the generator's Permanent Magnet Rotor turns during operation, magnets on the Ignition Cage rotate past the Ignition Sensor to induce a timed low voltage pulse into the Sensor. This voltage pulse is delivered to an Ignition Module and serves as a timing pulse for the Module.

  • The engine ignition system consists of the following major components:
  • Ignition Cage Assembly.
  • Ignition Sensor Assembly.
  • Ignition Module (IM).
  • Ignition Coil (IC).
  • Spark Plug (SP1).
Generac Power Systems 941-2 — Section 6.4 ENGINE IGNITION SYSTEM diagram (page 99)
Fig. 94 · Section 6.4 ENGINE IGNITION SYSTEM

IGNITION CAGE ASSEMBLY

An IGNITION CAGE ASSEMBLY is factory installed onto the permanent magnet rotor hub. Two magnets are installed in the cage as shown in Figure 1 (50° apart), so that the north pole of one magnet faces away from the cage outer periphery and the north pole of the other magnet faces toward the cage outer periphery. A special fixture is used to install the cage onto the rotor hub so that the center line of the first magnet is 68° away from the Rotor Hub mounting hole as shown. NOTE: Placement of the magnets on the Rotor Hub at the exact position stated above results in an ignition timing of 29 ° BTDC. The Ignition Cage assembly cannot be replaced. The entire Rotor Hub must be replaced. Replacement Rotor Hubs will include a factory installed Ignition Cage assembly, and Magnetic Housing Assembly. NOTE: Also refer to "Permanent Magnet Rotor" in Section 1.2 (Page 1.2-1).

Figure 2. Ignition Sensor

See Figure 3. The Sensor circuit board mounts solid state components which are sensitive to magnetism. Magnets in the Ignition Cage rotate past the Sensor, causing the base of a transistor to be "pulsed". The transistor acts much like a "switch" or a set of "con- tact points". Pulsing the transistor base causes the "switch" to close and connect the "OUT" lead to the "GND" lead. This triggers the Ignition Module to deliv- er a primary ignition current to the Ignition Coil at timed intervals.

Generac Power Systems 941-2 — IGNITION CAGE ASSEMBLY diagram (page 99)
Fig. 95
Generac Power Systems 941-2 — IGNITION CAGE ASSEMBLY diagram (page 99)
Fig. 96

Figure 3. Ignition Sensor Schematic

Figure 1. Ignition Cage Assembly

IGNITION MODULE

IGNITION SENSOR

While cranking and running, battery voltage is deliv- ered to the Ignition Module via Wire 14 from the A6060 circuit board. The Module will deliver this bat- tery voltage to the Ignition Coil based on the "timing" signal it receives from the Ignition Sensor. The Ignition Module is retained in the generator con- trol panel by two capscrews.

The Ignition Sensor is retained to the AC generator's Stator Adapter by means of two M4-0.70 x 8mm screws and lockwashers. The Sensor housing houses a circuit board. The entire housing cavity is filled with potting material.

Page 100 of the Generac Power Systems 941-2 user manual — TESTING THE SYSTEM
Page 100 · click to enlarge
Page 100

Section 6.4 ENGINE IGNITION SYSTEM

IGNITION MODULE (CONTINUED)

Clean the Spark Plug and reset its gap to 0.030 inch (0.76mm) every 100 hours of operation. Clean by scraping or wire brushing and washing with commer- cial solvent. DO NOT blast clean the spark plug.

Generac Power Systems 941-2 — Section 6.4 ENGINE IGNITION SYSTEM diagram (page 100)
Fig. 97 · Section 6.4 ENGINE IGNITION SYSTEM

SUMMARY OF OPERATION

See Figure 6. As the generator's permanent magnet rotor turns, magnets in the Rotor hub's Ignition Cage rotate past an Ignition Sensor at fixed intervals. Battery voltage is delivered to an Ignition Module dur- ing cranking and running, via Wire 14. From the Ignition Module, battery voltage is also delivered to the Ignition Sensor via the RED (+) lead. The Ignition Sensor acts as a "trigger" mechanism, causing the Ignition Module to deliver its output to the Ignition Coil at timed intervals. Current flows through the primary coil of the Ignition Coil and then collapses to induce a high voltage into the Ignition Coil's secondary coil. This high voltage (about 25,000 volts) is delivered to the park Plug to fire the spark plug gap. Components encapsulated in the Ignition Module pro- vide an automatic spark advance. At cranking speeds, ignition will occur at about 15'-18' BTDC. At higher speeds, ignition can occur up to 29° BTDC.

Figure 4. Ignition Module

IGNITION COIL

Primary ignition voltage (12 VDC) is delivered from the Ignition Module to the Ignition Coil. The Coil boosts the voltage and delivers the high voltage to the engine Spark Plug.

Generac Power Systems 941-2 — IGNITION COIL diagram (page 100)
Fig. 98
Generac Power Systems 941-2 — IGNITION COIL diagram (page 100)
Fig. 99

Figure 5. Ignition Coil

Figure 7. Ignition System Diagram

SPARK PLUG

The Spark Plug on the GV-220 engine is a Champion RC12YC (or equivalent).

IGNITION TIMING

Ignition timing is fixed and non-adjustable.

Generac Power Systems 941-2 — IGNITION TIMING diagram (page 100)
Fig. 100

TESTING THE SYSTEM

GENERAL: Solid state components inside the Ignition Sensor, Ignition Module and Ignition Coil are not accessible and cannot be serviced. If any of these components is defective, the entire component must be replaced. The system does not include an armature and there is no air gap to adjust, or breaker points to adjust or replace.

Figure 6. Setting Spark Plug Gap

Page 101 of the Generac Power Systems 941-2 user manual — !
Page 101 · click to enlarge
Page 101

Section 6.4 ENGINE IGNITION SYSTEM

TESTING FOR SPARK: To test the ignition system, a suitable spark tester may be used. Such spark testers are commercially available. Test the system as follows:

CHECK POWER SUPPLY: When the engine is being cranked, battery voltage should be available from the A6060 circuit board to a 4-terminal connector via Wire 14. From the 4-terminal connector, battery voltage should be available to the Ignition Module via Wire 14 (RED wire). And battery voltage should be available from the Ignition Module to the Ignition Sensor via a RED wire. If this 12 VDC power supply is not available, the ignition system will not function. To check the power supply, proceed as follows using a volt-ohm-milliammeter (VOM):

!

1. Disconnect the high tension lead from the spark plug.
2. Attach the spark plug high tension lead to the spark tester terminal.
1. Gain access to the control panel interior.
2. In the panel, locate the 3-pin connector that interconnects the Ignition Module and the Ignition Sensor.
3. Connect the spark tester clamp to the engine cylinder head.
4. Crank the engine rapidly. Engine must be turning at 350 rpm or more. If spark jumps the tester gap, you may assume the ignition system is operating satisfactorily.
3. Press down on the connector lock tang and disconnect the two connector halves.

If sparking across the tester gap does NOT occur, go to “CHECK POWER SUPPLY.”

Generac Power Systems 941-2 — ! diagram (page 101)
Fig. 101
4. Set the VOM to a scale that will allow battery voltage to be read (about 12 volts DC).
5. Connect the meter test leads across the center FEMALE pin (RED wire) and frame ground.
6. Hold the Start-Run-Stop switch at "START". The meter should read battery voltage.
Generac Power Systems 941-2 — ! diagram (page 101)
Fig. 102

Figure 8. Testing for Spark

CHECKING ENGINE MISS: To determine if an engine miss is ignition related, connect the spark tester in series with the spark plug's high tension lead and the spark plug. Then, start the engine. If spark jumps the tester gap at regu- lar intervals but the engine miss continues, the prob- lem is in the spark plug or in the fuel system.

Figure 10.

If battery voltage is NOT indicated, go to Step 7. If battery voltage IS indicated, go to "CHECK IGNITION SENSOR." 7. Now locate the 4-terminal connector in the panel. Connect the VOM test leads across the terminal and frame ground. Crank the engine and the VOM should read battery voltage.

Generac Power Systems 941-2 — ! diagram (page 101)
Fig. 103

a.If battery voltage is indicated now but was NOT

indicated in Step 6, test Wire 14 (RED) between the 4-terminal connector and the Ignition Module. If wire is bad, repair or replace as necessary.

Figure 9. Checking Engine Miss

(continued)

Page 102 of the Generac Power Systems 941-2 user manual — CHECK IGNITION SENSOR:
Page 102 · click to enlarge
Page 102

Section 6.4 ENGINE IGNITION SYSTEM

TESTING THE SYSTEM (CONTINUED)

b.Connect the VOM test leads across the two

male pins of the 2-pin connector. Primary coil resistance should be about 0.5 to 1.5 ohms.

CHECK POWER SUPPLY (CONT’D):

3. To read SECONDARY coil resistance:

b.If battery voltage is NOT indicated in Step 7,

test Wire 14 between the 4-terminal connector and the A6060 circuit board. Repair or replace as necessary.

a.Set the VOM to its "Rx10,000" or "Rx1 K" scale

and zero the meter. b.Unplug the high tension lead from the Spark

CHECK IGNITION SENSOR:

Plug. c. Connect one VOM test lead to the white wire

1. In the 3-pin connector plug half from the Ignition Module, locate FEMALE Pin 1 to which the BROWN wire connects.

connector pin. d.Connect the other VOM test lead into the Spark

2. Connect a jumper wire from FEMALE Pin 1 (BROWN wire) to frame ground.

Plug lead rubber boot so it contacts the lead's metal terminal end. The VOM should read approximately 16,000-17,000 ohms (16.0-17.0 k-Ohms).

3. Connect the Spark Plug high tension lead to a spark tester (Figure 8) and the spark tester clamp to ground.

Replace the Ignition Coil if defective. If the Ignition Coil tested good, go to "TESTING IGNITION MOD- ULE".

4. Crank the engine and observe the spark tester for sparking.

TESTING IGNITION MODULE: If a problem was indicated under "TESTING FOR SPARK", you should have completed the tests under "CHECK POWER SUPPLY", under "CHECK IGNITION SENSOR" and under "TESTING IGNITION COIL". If these components tested good, replace the Ignition Module.

Generac Power Systems 941-2 — CHECK IGNITION SENSOR: diagram (page 102)
Fig. 104
Generac Power Systems 941-2 — CHECK IGNITION SENSOR: diagram (page 102)
Fig. 105

Figure 12. Testing Ignition Sensor

If sparking occurs with the BROWN wire grounded but did NOT occur under "TESTING FOR SPARK", the Ignition Sensor is probably defective and should be replaced. NOTE: The Ignition Sensor is mounted to the gen- erator's Stator Adapter. To replace the Sensor, disassembly of the generator and removal of the Stator will be necessary. If sparking does NOT occur with the BROWN wire grounded and did NOT occur under "TESTING FOR SPARK", either the Ignition Module or the Ignition Coil is defective. Go to "TESTING IGNITION COIL".

Figure 13. Testing Ignition Coil

Generac Power Systems 941-2 — CHECK IGNITION SENSOR: diagram (page 102)
Fig. 106

TESTING IGNITION COIL: The Ignition Coil is housed in the generator control panel. To test the coil, proceed as follows:

1. Unplug the two halves of the 2-pin connector plug from the Ignition Coil. The red and white wires are the primary coil leads.
2. To read PRIMARY coil resistance:

Figure 14. Testing Ignition Module

a.Set a volt-ohm-milliammeter (VOM) to its "Rx1 "

scale and zero the meter.

Page 103 of the Generac Power Systems 941-2 user manual — OIL TEMPERATURE SWITCH
Page 103 · click to enlarge
Page 103

Section 6.5 SHUTDOWN FEATURES

GENERAL

Generac Power Systems 941-2 — Section 6.5 SHUTDOWN FEATURES diagram (page 103)
Fig. 107 · Section 6.5 SHUTDOWN FEATURES

The engine mounts an Oil Pressure Switch (LOP) and an Oil Temperature Switch (HTO). These two switch- es, in conjunction with the A6060 circuit board, pro- tect the engine against (a) low oil pressure and (b) high oil temperature. The engine protective circuit Is shown in Figure 1.

OIL PRESSURE SWITCH

DESCRIPTION: The Oil Pressure Switch has normally-closed contacts which are held open by engine oil pressure during cranking and running. Should oil pressure drop below approximately 5 psi, the switch contacts will close to complete the Wire 85 circuit to ground. A6060 circuit board action will then de-energize the Wire 14 circuit and the engine will shut down. The A6060 circuit board provides a time delay to allow oil pressure to build during startup, to prevent premature shutdown.

Figure 2. Engine Protective Devices

Generac Power Systems 941-2 — OIL PRESSURE SWITCH diagram (page 103)
Fig. 108

TESTING THE SWITCH: Use a volt-ohm-milliammeter (VOM) to test the oil pressure switch. Connect the VOM test leads across the switch terminal and the switch body. With the engine shut down, the meter should read "continuity" (a very small resistance is acceptable). With engine running, the meter should read "infinity".

OIL TEMPERATURE SWITCH

DESCRIPTION: This thermostatic switch has normally-open contacts. Should engine oil temperature exceed a preset safe value (about 293° F.), the switch contacts will close. On closure of the Switch contacts, the Wire 85 circuit will be connected to frame ground. Engine shutdown will then occur.

Figure 3. Testing the Oil Temperature Switch

TESTING: See Figure 3. Remove the switch and place its sens- ing tip into oil. Place a thermometer Into the oil. Connect the test leads of a VOM across the switch terminals. The meter should read "Infinity". Heat the oil. When oil temperature reaches approximately 287°-296° F. (142°-147° C.), the meter should read "continuity" (a small resistance is acceptable).

Generac Power Systems 941-2 — OIL TEMPERATURE SWITCH diagram (page 103)
Fig. 109

Figure 1. Engine Protective Circuit

(continued)

Page 104 of the Generac Power Systems 941-2 user manual — Section 6.5 SHUTDOWN FEATURES
Page 104 · click to enlarge
Page 104

Section 6.5 SHUTDOWN FEATURES

ADDITIONAL SHUTDOWN FEATURES

The A6060 Circuit Board also incorporates the follow- ing protective shutdown features:

LOSS OF 12-PIN CABLE SIGNALS TO INVERTER: The generator will shutdown if the 12-pin connector is disconnected from the inverter when CB1 is turned to ON. This shutdown will occur after approximately 5-7 seconds.

LOSS OF TIM1/TIM2 INPUT TO A6060 CIRCUIT BOARD: If Timing Winding input is lost, the generator will immediately shutdown.

LOSS OF PS1/PS2 TO INVERTER: A loss of voltage from PS1/PS2 windings to the inverter will simulate a 12-pin signal failure and cause a shutdown when CB1 is turned to ON. This shutdown will occur after approximately 5-7 seconds.

OVERSPEED OF ENGINE: Overspeed of the engine will result in an immediate shutdown. This automatic generator shutdown will occur at engine speed above 4200 rpm.

SHORT CIRCUIT PROTECTION: If the inverter senses a short circuit on the AC output side it will automatically shut the generator down.

INVERTER OVERHEAT CONDITION: If the inverter overheats, AC output will be shut off. The engine will continue to run for approximately two minutes and then shut down. The maximum ambient temperature rating is 120°F.

DC LINK VOLTAGE GREATER THAN 600 VDC: If DC link voltage exceeds 600 VDC, the inverter will shut off AC power output.

DC LINK UNDER-VOLTAGE SHUTDOWN: If DC link voltage drops below 100 VDC, the inverter will shut off AC power output.

Page 105 of the Generac Power Systems 941-2 user manual — WIRE #18
Page 105 · click to enlarge
Page 105

Section 6.6 OPTIONAL REMOTE PANEL

GENERAL

  • The remote panels mount a rocker type start/stop switch, a “Generator Run” advisory lamp and an hourmeter. The hourmeter should be used in conjunction with the maintenance operations found in Part I of this manual.
  • Model 004057 includes the remote panel and a 10 foot long, 4 wire harness.
  • Model 004184 includes the remote panel and a 30 foot long, 4 wire harness.

An optional remote-mounted Start-Stop panel is avail- able. This panel will permit the generator to be started and stopped from some convenient remote location in the recreational vehicle.

REMOTE PLUG-IN RECEPTACLE A plug-in receptacle (Figure 2.24) is provided on the generator set, near the DC power wires. Use this receptacle to connect an optional remote-mounted start/stop panel to the generator. Installation of such a panel will permit you to start and stop the generator engine from any convenient location inside the vehi- cle.

WIRE #18

WIRE #14 (ENGINE RUN

WIRE #17

WIRE #10 (GROUND)

(STOP)

(CRANK)

SIGNAL)

Figure 1. Remote Panel Plug-In Receptacle

REMOTE START/STOP PANEL A remote mounted Start/Stop panel (Figure 2.25) is available that allows the user to start and stop the generator engine conveniently from inside the vehicle. The remote panel includes a Start/Stop switch, hourmeter, generator run lamp and a wire harness.

Figure 2. Optional Remote Panel

(Models 004057 and 004184)

Page 106 of the Generac Power Systems 941-2 user manual — Section 6.6 OPTIONAL REMOTE PANEL
Page 106 · click to enlarge
Page 106

Section 6.6 OPTIONAL REMOTE PANEL

Page 107 of the Generac Power Systems 941-2 user manual — SECTION TITLE
Page 107 · click to enlarge
Page 107

PART 7 TROUBLESHOOTING

SECTION TITLE

7.1 GENERATOR & SPEED CONTROL

7.2 ENGINE DC CONTROL SYSTEM/

AC TROUBLESHOOTING

COMPUTER CONTROLLED

VARIABLE SPEED RV GENERATORS

Series Impact 36 Plus

Page 108 of the Generac Power Systems 941-2 user manual — NOTES
Page 108 · click to enlarge
Page 108

NOTES

Page 109 of the Generac Power Systems 941-2 user manual — Section 7.1 GENERATOR & SPEED CONTROL SYSTEM
Page 109 · click to enlarge
Page 109

Section 7.1 GENERATOR & SPEED CONTROL SYSTEM

TROUBLESHOOTING REFERENCE CHART

PROBLEM POSSIBLE CAUSE REMEDY PAGE

1. Engine starts, accelerates, a. Carburetor linkage sticking with a. Repair sticking throttle 3.4-3 shuts down at 4500 rpm throttle stuck open. b. Stepper Motor failed or seized. b. Replace Stepper Motor. 3.6-1 c. Stepper Motor wire connections c. Reconnect or repair. 3.6-1 broken or disconnected. d. Stepper Motor not properly connected. d. Reconnect wires. 3.6-1
2. Overvoltage condition and a. Carburetor linkage sticking with a. Repair sticking throttle. 3.4-3 speed control system cannot throttle stuck partly open. reduce output voltage. b. Stepper Motor failed or seized. b. Replace Stepper Motor. 3.6-1 c. Connection to Stepper Motor is c. Repair or replace connections. 3.6-1 broken/disconnected with throttle open. d. Stepper Motor not properly connected. d. Reconnect Stepper Motor wires. 3.6-1
3. Engine speed is maintained a. Carburetor linkage sticking with a. Repair sticking throttle. 3.4-3 and no-load voltage is good. throttle partly open. However, when load is applied b. Stepper Motor failed or seized. b. Replace Stepper Motor. 3.6-1 output voltage drops. c. Connection to Stepper Motor c. Repair or replace connections. 3.6-1 Motor broken or disconnected. d. Stepper Motor not properly d. Reconnect Stepper Motor. 3.6-1 connected.
4. Engine does not accelerate a. Carburetor linkage sticking a. Repair sticking throttle. 3.4-3 when load is applied. with throttle stuck closed. b. Stepper Motor failed or seized. b. Replace Stepper Motor. 3.6-1 c. Stepper Motor not properly c. Reconnect Stepper Motor. 3.6-1 connected.
5. Engine speed and AC output a. Stepper Motor failure. a. Replace Stepper Motor. 3.6-1 voltage erratic under constant b. Connection to Stepper Motor b. Repair or replace connections. 3.6-1 load. AC output does not turn broken or disconnected. off intermittently. c. Stepper Motor not properly c. Reconnect Stepper Motor. 3.6-1 connected
6. Engine starts but Stepper a. Stator Timing winding is open. a. Repair/replace bad wire(s) 1.5-2 Motor does not move. Shut down TIM1/TIM2 or replace Stator. occurs after several seconds. b. Timing winding in Stator shorted b. Replace Stator. 1.5-2 to ground.
Page 110 of the Generac Power Systems 941-2 user manual — Section 7.1 GENERATOR & SPEED CONTROL SYSTEM
Page 110 · click to enlarge
Page 110

Section 7.1 GENERATOR & SPEED CONTROL SYSTEM

Page 111 of the Generac Power Systems 941-2 user manual — PROBLEM 1PRIMING FUNCTION DOES NOT WORK
Page 111 · click to enlarge
Page 111

Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING

INTRODUCTION

This Section contains troubleshooting information pertaining to the engine DC control system. The section is divided into two parts, i.e., troubleshooting flow charts and diagnostic test procedures. Use the flow charts and the test procedures in conjunction with one another. The first step in troubleshooting is to identify the problem. After identifying the problem, go to the flow chart that best describes it. Perform each test in the flow chart and follow the flow chart arrows and instructions. If you need instructions for any test, refer to the applicable diagnostic test procedure. Problem solving on the computer controlled generator is somewhat more complex than problem solving on con- ventional units. The A6060 circuit board, in addition to its voltage and frequency control functions, has engine shutdown capability. See “AUTOMATIC SHUTDOWNS” on Page 1.2-5. The A6060 circuit board, part of the engine’s DC control system, also has engine shutdown capability. Fortunately, neither the generator proper nor the engine DC control system has a large number of parts. When a problem is encountered, its solution can usually be found after only a few tests.

PROBLEM 1PRIMING FUNCTION DOES NOT WORK

Page 112 of the Generac Power Systems 941-2 user manual — Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING
Page 112 · click to enlarge
Page 112
Generac Power Systems 941-2 — Section 7.2 - ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING diagram (page 112)
Fig. 110 · Section 7.2 - ENGINE DC CONTROL SYSTEM / AC TROUBLES…

Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING

PROBLEM 3 - ENGINE CRANKS BUT WILL NOT START

Page 113 of the Generac Power Systems 941-2 user manual — Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING
Page 113 · click to enlarge
Page 113
Generac Power Systems 941-2 — Section 7.2 - ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING diagram (page 113)
Fig. 111 · Section 7.2 - ENGINE DC CONTROL SYSTEM / AC TROUBLES…

Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING

PROBLEM 3 - ENGINE CRANKS BUT WILL NOT START (CONTINUED)

Page 114 of the Generac Power Systems 941-2 user manual — Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING
Page 114 · click to enlarge
Page 114
Generac Power Systems 941-2 — Section 7.2 - ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING diagram (page 114)
Fig. 112 · Section 7.2 - ENGINE DC CONTROL SYSTEM / AC TROUBLES…

Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING

PROBLEM 4 - ENGINE STARTS HARD AND RUNS ROUGH

Page 115 of the Generac Power Systems 941-2 user manual — PROBLEM 5 - ENGINE STARTS THEN SHUTS DOWN AFTER A FEW SECONDS
Page 115 · click to enlarge
Page 115

Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING

Generac Power Systems 941-2 — Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING diagram (page 115)
Fig. 113 · Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHO…

PROBLEM 5 - ENGINE STARTS THEN SHUTS DOWN AFTER A FEW SECONDS

Page 116 of the Generac Power Systems 941-2 user manual — PROBLEM 7 - GENERATOR CIRCUIT BREAKER TRIPS / NO AC VOLTAGE
Page 116 · click to enlarge
Page 116
Generac Power Systems 941-2 — Section 7.2 - ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING diagram (page 116)
Fig. 114 · Section 7.2 - ENGINE DC CONTROL SYSTEM / AC TROUBLES…

Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING

Generac Power Systems 941-2 — Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING diagram (page 116)
Fig. 115 · Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHO…

PROBLEM 7 - GENERATOR CIRCUIT BREAKER TRIPS / NO AC VOLTAGE

Page 117 of the Generac Power Systems 941-2 user manual — PROBLEM 9 - GENERATOR LOSES AC POWER THEN SHUTS DOWN
Page 117 · click to enlarge
Page 117

Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING

Generac Power Systems 941-2 — Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING diagram (page 117)
Fig. 116 · Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHO…
Generac Power Systems 941-2 — Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING diagram (page 117)
Fig. 117 · Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHO…

PROBLEM 9 - GENERATOR LOSES AC POWER THEN SHUTS DOWN

Page 118 of the Generac Power Systems 941-2 user manual — Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING
Page 118 · click to enlarge
Page 118

Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING

Generac Power Systems 941-2 — Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING diagram (page 118)
Fig. 118 · Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHO…
Page 119 of the Generac Power Systems 941-2 user manual — Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING
Page 119 · click to enlarge
Page 119
Generac Power Systems 941-2 — Section 7.2 - ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING diagram (page 119)
Fig. 119 · Section 7.2 - ENGINE DC CONTROL SYSTEM / AC TROUBLES…

Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING

Page 120 of the Generac Power Systems 941-2 user manual — RESULTS:
Page 120 · click to enlarge
Page 120

Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING

TEST 1CHECK 7.5 AMP FUSE

Generac Power Systems 941-2 — Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING diagram (page 120)
Fig. 120 · Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHO…

DISCUSSION: The panel-mounted 7.5 amp fuse is connected in series with the 12 VDC power supply to the engine DC control system. A blown fuse will prevent engine priming, cranking and running.

TEST PROCEDURE: Push in on fuse holder cap and turn it counterclock- wise to remove cap and fuse. Check the fuse visually. If the fuse metal element has melted open, replace the fuse. If the visual check is uncertain, use a VOM to check fuse.

Figure 2. Primer Switch

TEST 3CHECK POWER TO FUEL PUMP

RESULTS:

1. If fuse is good

DISCUSSION: When the rocker type primer switch is held at ON", position, fused battery voltage is delivered to the elec- tric fuel pump. The pump should then turn on and prime the carburetor. During cranking and startup, the A6060 circuit board will deliver battery voltage to the Wire 14 circuit and to the Fuel Pump. The pump should turn on and run.

a.And if priming function does not work, go to

Test 2. b.And if engine will not crank, go to Step 4. 2. If

fuse is bad, replace it.

Generac Power Systems 941-2 — TEST 3CHECK POWER TO FUEL PUMP diagram (page 120)
Fig. 121
Generac Power Systems 941-2 — TEST 3CHECK POWER TO FUEL PUMP diagram (page 120)
Fig. 122

Figure 1. 7.5 Amp Fuse

TEST 2CHECK POWER TO PRIMER SWITCH

Figure 3. Fuel Pump

DISCUSSION: This is a check of the PRIMER SWITCH on the panel. When the switch is actuated to its "PRIME" position, fused battery voltage is delivered directly to the elec- tric fuel pump on units with gasoline fuel system. On units with gaseous fuel system, battery voltage is delivered to the fuel lockoff solenoid.

TEST PROCEDURE: Locate the red Wire 14A that connects to the fuel pump. A wiring connector connects the wires near the pump. Separate the wire, then check for DC power as follows:

1. Set VOM to read battery voltage.

TEST PROCEDURE: Set a VOM to read battery voltage (12 VDC). Connect the meter test leads across the Wire 15 terminal of the Primer Switch and frame ground. The meter should read battery voltage.

2. Connect the VOM test leads across the Wire 14A from the Primer Switch and frame ground.
3. Hold the Primer Switch at °ON" (Prime). Meter should read battery voltage.

RESULTS:

4. Hold the panel Start-Run-Stop switch at "START". The meter should read battery voltage.
1. If battery voltage is indicated, go to Test 3.
2. If battery voltage is NOT indicated, go to Test 4.
Page 121 of the Generac Power Systems 941-2 user manual — TEST 5TEST FUEL PUMP
Page 121 · click to enlarge
Page 121

Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING

RESULTS:

TEST 6TEST PRIMER SWITCH

1. If unit is being tested because the priming function doesn't work:

a.!f battery voltage is good but the pump doesn't

DISCUSSION: See Figure 2 on facing page. When this rocker type switch is held at "PRIME" position, fused battery volt- age is delivered to the Fuel Pump to prime the carbu- retor. With the switch set to "OFF", battery voltage is deliv- ered to the Fuel Pump from the A6060 circuit board during cranking and running (via Wire 14).

work, go to Test 5. b.!f battery voltage is NOT indicated, go to Test 6.

2. If engine cranks but will not start:

a.!f battery voltage is good but the pump doesn't

work, go to Test 5. b.If DC power to pump is good and pump works,

go to Test 22.

TEST PROCEDURE:

1. Disconnect Wires 15,14 and 14A from the switch terminal to prevent interaction.

TEST 4CHECK BATTERY/BATTERY CIRCUIT

2. Set a VOM to its "Rx1" scale and zero the meter.

DISCUSSION: The battery circuit includes the red battery cable that extends from the units 12 volt battery to the Starter Contactor. The circuit also includes Wire 13 (RED) from the Starter Contactor to the 15 amp Fuse. It includes one Wire 15 from the Fuse to the Primer Switch and a Wire 15 from the Fuse to the A6060 cir- cuit board.

3. Connect the VOM test leads across the Wire 15 terminal and the Wire 14A terminal. The meter should read "infinity". Set the switch to "ON" or "PRIME" and the meter should indicate "continuity.
4. Connect the VOM test leads across the Wires 14 and 14A terminals. The meter should read "continuity". Set the switch to "ON" or "PRIME" and the VOM should read "infinity".

TEST PROCEDURE: Inspect the battery terminals and cables carefully. Clean cables and cable connections if necessary. Replace any bad cable(s), including the battery nega- tive cable, if necessary. Check Wires 13 and 15 for an open or shorted condition. Repair, reconnect or replace bad wire(s) as necessary. Use a battery hydrometer to test the battery for "state of charge" and for "condition". Follow the hydrometer manufacturer's instructions carefully. If the hydrome- ter used does not have a "percentage of charge" scale, use the following as a reference:

RESULTS:

1. Replace switch if it fails the test. 2. If the switch is good, go to Test 7.

TEST 7CHECK WIRE 14A TO FUEL PUMP

DISCUSSION: If no power was available to the Fuel Pump in Test 3, either the Primer Switch is defective or Wire 14A is open.

SPECIFIC GRAVITY PERCENTAGE OF CHARGE

1.260 100%

TEST PROCEDURE: Inspect Wire 14A between the fuel pump and primer switch for proper connections. Check for open condi- tion with a VOM.

1.230 75%

1.200 50%

1.170 25%

RESULTS: Repair, reconnect or replace Wire 14A as necessary.

RESULTS:

1. Repair, reconnect or replace any open or shorted wi re(s).
2. If necessary, recharge the battery to a 100% state of charge. Disconnect the battery cables before recharging the battery.

TEST 8CHECK POWER SUPPLY TO

STARTER MOTOR

3. If (after recharging) the difference in specific gravity between the highest and lowest reading cells is greater than 0.050 (50 points) the battery is nearing the end of its useful life and should be replaced.

DISCUSSION: When the Start-Run-Stop switch is set to "START", Wire 17 is connected to ground. A6060 circuit board action then delivers a DC voltage to the Starter Contactor coil and the Contactor's normally-open con- tacts close. On closure of the contacts, battery power is delivered directly to the Starter Motor to crank the engine.

TEST 5TEST FUEL PUMP

Refer to Page 3.3-1.

Page 122 of the Generac Power Systems 941-2 user manual — TEST PROCEDURE:
Page 122 · click to enlarge
Page 122

Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING

This test will determine if battery voltage is available to the Starter Motor for cranking the engine.

3. Set the Start-Run-Stop switch to "START". The meter should indicate battery voltage.

TEST PROCEDURE:

RESULTS:

1. Set a VOM to read battery voltage (12 VDC).
1. No power to Wire 56 terminal, go to Test 10.
2. Connect the meter test leads across the starter terminal and frame ground.
2. If power to Starter Contactor is good, go to Test 11.
3. Hold the Start-Run-Stop switch at "START". The VOM should read battery voltage and the engine should crank.
Generac Power Systems 941-2 — TEST PROCEDURE: diagram (page 122)
Fig. 123

RESULTS:

1. If power supply is good and engine cranks, stop tests.
2. If power supply is good but engine does NOT crank, replace the Starter.
3. If power supply is bad, go on to Test 9.
4. If voltage drops during cranking (i.e. from 12 VDC to 9.5 VDC or lower), then check battery condition and cable sizes per the installation manual. Verify that proper grounding of the generator exists.

Figure 5. Starter Contactor

Generac Power Systems 941-2 — RESULTS: diagram (page 122)
Fig. 124

TEST 10CHECK A6060 CIRCUIT BOARD

POWER SUPPLY

DISCUSSION: Fused battery voltage is delivered to the A6060 circuit board via Wire 15. If this power (12 VDC) is not avail- able to the board, cranking and startup will not be possible. This test will determine if battery voltage is available to the circuit board for its operation.

TEST PROCEDURE: Set a VOM to read battery voltage (12 VDC). Connect one VOM test lead to the Wire 15 terminal J2-5 on the A6060 circuit board. Connect the other test lead to frame ground. The meter should indicate battery voltage.

Figure 4. Starter Motor

TEST 9CHECK WIRE 56 POWER TO

STARTER CONTACTOR

DISCUSSION: When the Start-Run-Stop switch is set to "START", the A6060 circuit board must react by delivering bat- tery voltage to the Starter Contactor coil, via Wire 56. Without this battery voltage, the Contactor will not energize and battery output will not be delivered to the Starter Motor. The engine will not crank.

RESULTS:

1. If battery voltage is NOT indicated, check Wire 15 between the 7.5 amp fuse and the A6060 circuit board. Repair, reconnect or replace the wire as needed.
2. If Battery Voltage was indicated, test for proper ground from the A6060 circuit board. Set a VOM to read Resistance. Measure from terminal J2-6 to the generator frame ground. A “Continuity” reading should exist. If open or high resistance is measured, repair wires or ground connections.

TEST PROCEDURE:

1. Set a VOM to read battery voltage (12 VDC).
2. Connect the meter test leads across the Wire 56 starter contactor terminal and frame ground.
3. If 12 VDC was indicated, go to Test 12.
Page 123 of the Generac Power Systems 941-2 user manual — RESULTS:
Page 123 · click to enlarge
Page 123

Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING

TEST 11TEST STARTER CONTACTOR

2. If engine stops when Wire 18 is grounded but will not shut down with Start-Stop switch, replace the Switch.

DISCUSSION: See "Starter Contactor" on Page 6.3-2. Replace Starter Contactor if bad.

3. If engine will not crank when Wire 17 is grounded, replace the A6060 circuit board.
4. If engine will not stop when Wire 18 is grounded, replace the A6060 circuit board.

TEST 12TEST START-STOP SWITCH

TEST 13CHECK FUEL SUPPLY

DISCUSSION: Engine cranking and startup are initiated when the Start-Stop switch is held at "START" to ground Wire 17. Engine shutdown is normally initiated when the Start- Stop switch is set to "STOP" to ground Wire 18. A defective switch can prevent normal startup or nor- mal shutdown.

DISCUSSION: If the engine cranks but won't start, don't overlook the obvious. The engine won't start without fuel.

TEST PROCEDURE: Check fuel level.

RESULTS:

Generac Power Systems 941-2 — RESULTS: diagram (page 123)
Fig. 125
1. If fuel level is low, replenish fuel supply.
2. If fuel quantity is good, go to Test 14.

TEST 14CHECK FUEL FILTER

Refer to Section 3.3.

TEST 15CHECK IGNITION SPARK

Refer to Section 6.4, "ENGINE IGNITION SYSTEM".

TEST 16CHECK SPARK PLUG

DISCUSSION: A badly fouled spark plug can prevent the engine from starting. A defective spark plug may allow the engine to be started, but rough operation or an "engine miss" may be observed. A commercially available spark tester can be used to check for ignition spark. When the spark tester is con- nected in series with the spark plug and its high ten- sion lead, the cause of an engine miss can be nar- rowed down to either (a) the ignition system, or (b) the spark plug or fuel system. Use of the spark tester is discussed in Test 16.

Figure 7. Start-Stop Switch

TEST PROCEDURE:

1. Carefully inspect Wire 0 (Ground) between the Start-Stop switch and the ground terminal. Repair, reconnect or replace the wire if necessary.
2. Disconnect Wire 17 from its terminal on the Start-Stop switch. Connect Wire 17 to a clean frame ground. The engine should crank.
3. Start the engine, using the Start-Stop switch or by grounding Wire 17.

TEST PROCEDURE: Remove the spark plug. Clean by scraping or wire brushing and by using a commercial solvent. DO NOT BLAST CLEAN THE PLUG. Set spark plug gap to 0.030 inch (0.76mm). Replace spark plug if badly fouled, if ceramic is cracked, or if damaged.

4. Stop the engine by holding the Start-Stop switch at "STOP". If engine will not shut down with switch at "STOP", ground Wire 18 to stop engine.

RESULTS:

1. If engine cranks when Wire 17 is grounded, but won't crank with Start-Stop switch, replace the Start-Stop switch.
Page 124 of the Generac Power Systems 941-2 user manual — OUTPUT TO WIRE 14
Page 124 · click to enlarge
Page 124

Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING

2. Connect the VOM test leads across the 4-tab connector and frame ground.
Generac Power Systems 941-2 — Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING diagram (page 124)
Fig. 126 · Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHO…
3. Hold the engine Start-Stop switch at "START".

The meter should read battery voltage.

RESULTS:

1. If DC voltage is NOT indicated, go to Test 21.
2. If DC voltage is good, go on to Test 18.

Figure 8. Checking Spark Plug Gap

TEST 18CHECK IGNITION SENSOR

RESULTS:

1. Clean and regap or replace spark plug as necessary.

DISCUSSION: Refer to Section 6.4, "ENGINE IGNITION SYSTEM".

2. If spark plug is good but engine will not start, go to Test 3.
3. If spark plug is good but engine misses or runs rough,. go to Test 23.

TEST PROCEDURE: See Section 6.4.

RESULTS:

TEST 17CHECK IGNITION POWER SUPPLY

1. Replace Sensor, if bad.

DISCUSSION: During startup, the A6060 circuit board delivers DC power to the Ignition Module via Wire 14. If the engine cranks but won't start, one possible cause is loss of this power supply. The DC power from the A6060 Circuit Board is deliv- ered to a 4-tab terminal connector. From that connec- tor, it is routed to the Ignition Module. These components are all housed in the control panel.

2. If Sensor checks good, go to Test 19.

TEST 19CHECK IGNITION COIL

DISCUSSION: See Section 6.4, "ENGINE IGNITION SYSTEM".

TEST PROCEDURE: See Section 6.4.

Generac Power Systems 941-2 — TEST 19CHECK IGNITION COIL diagram (page 124)
Fig. 127

RESULTS:

1. Replace Ignition Coil if bad.
2. If coil is good, go to Test 20.

TEST 20TEST IGNITION MODULE

DISCUSSION: See Section 6.4, "ENGINE IGNITION SYSTEM".

TEST PROCEDURE: Refer to Section 6.4.

RESULTS: Replace Ignition Module if bad.

Figure 9. Ignition Module & 4-Tab Connector

TEST 21 - CHECK A6060 CIRCUIT BOARD

TEST PROCEDURE: In the control panel, inspect the Wire 14 connections at the 4-tab connector. Check Wire 14. Check the power supply as follows:

OUTPUT TO WIRE 14

DISCUSSION: If the engine cranks when the Start-Stop switch is set to "START", battery voltage must be available to the A6060 circuit board.

1. Set a VOM to read battery voltage.
Page 125 of the Generac Power Systems 941-2 user manual — RESULTS:
Page 125 · click to enlarge
Page 125

Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING

If the engine cranks but won't start, it is possible that a failure in the circuit board has occurred and DC power is not being delivered to the Wire 14 circuit. This test will determine if circuit board action will deliver battery voltage to the necessary engine components.

TEST 23CHECK CARBURETION

DISCUSSION: If the engine won't start or if it starts hard and runs rough, one possible cause of the problem is carburetion.

PROCEDURE: Set a VOM to read battery voltage. Connect the meter test leads across Pin J2-9 of the A6060 circuit board and Pin J2-6 of the circuit board connector (to which common ground Wire 0 connects). Crank the engine and the meter should read battery voltage.

  • PROCEDURE: Before making a carburetion check, make sure the fuel tank has an ample supply of clean fresh gasoline (gasoline fuel systems) or gaseous fuel. The installer may have installed a gas or gasoline shutoff valve in the fuel supply system. Make sure all shutoff valves are open. Make sure the automatic choke is working properly and that the choke closes completely. If the engine will not start, remove the spark plug and inspect it. If the plug is WET, look for the following:
  • Overchoking.
  • Water in fuel.
  • Excessively rich fuel mixture.
  • Intake valve stuck open. If the spark plug is DRY, look for the following:
  • Carburetor gasket(s) leaking.
  • Fuel line plugged or shutoff valve not opening.
  • Intake valve stuck closed.
  • Inoperative fuel pump.
  • Clogged fuel filter.

RESULTS:

1. If DC voltage was NOT indicated in Test 17, but IS indicated now, repair, reconnect or replace Wire 14 between board and Ignition Module.
2. If no DC voltage in Test 3 but good voltage now, replace Wire 14 between board and fuel pump.
3. If there is no DC output from the circuit board to Wire 14, replace the A6060 circuit board.

RESULTS: Adjust or repair carburetor or fuel system as necessary.

TEST 24CHECK ENGINE

DISCUSSION: An engine that will not start or one that starts hard and runs rough may be caused by a failure in the engine's mechanical system.

Figure 10. Receptacle J2

TEST 22-TEST AUTOMATIC CHOKE

PROCEDURE: The first step in checking for an engine problem is to perform a compression check. To check engine com- pression, proceed as follows:

DISCUSSION: Refer to Section 3.5, "AUTOMATIC CHOKE".

TEST PROCEDURE: See Section 3.5.

1. Remove the spark plug.
2. Insert an automotive type compression gauge into the spark plug hole.

RESULTS:

1. Adjust or repair choke system as necessary.
3. Crank the engine until there is no further in-crease in pressure. The highest reading obtained is the engine's compression pressure.
2.!f choke is good, go to Test 23.

(continued)

Page 126 of the Generac Power Systems 941-2 user manual — RESULTS:
Page 126 · click to enlarge
Page 126

Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING

ENGINE COMPRESSION PRESSURE

TEST 27TEST OIL TEMPERATURE SWITCH

NOMINAL PRESSURE: 60 psi MINIMUM ALLOWABLE: 55 psi NOTE: Full compression pressure cannot be obtained at cranking speeds, due to the action of a compression release mechanism.

DISCUSSIONSee Section 6.5, "ENGINE SHUTDOWN FEATURES.”

TEST PROCEDURE: See Section 6.5.

RESULTSIf compression is poor, look for one or more of the following possible causes:

RESULTS: NOTE: The generator will shutdown if the 12-pin connector is disconnected and the circuit breaker is turned on. In order to perform the running diagnostic tests, you must jump pin #10 to pin #11. This will enable the unit to continue to run with the circuit breaker turned to the “ON” posi- tion (See Figure 10 on page 7.2-17).

1. Loose cylinder head bolts.
2. Failed cylinder head gasket.
3. Burned valves or valve seals.
4. Insufficient valve clearance.
5. Warped cylinder head.

TEST 28 - DC LINK VOLTAGE TEST

6. Warped valve stem.
7. Worn or broken piston ring(s).
1. Disconnect the 12-pin connector from the inverter. Disconnect the Red-Black-Blue-Green DC Link wires from the inverter.
8. Worn or damaged cylinder bore.
9. Broken connecting rod.
2. On units with A6060 circuit board revision “D” or higher software, jump pin #10 to pin #11 on the 12-pin cable previously removed from the inverter. The 12 position cable should be connected to the 12-pin socket on the generator control panel. This will enable the generator to run with CB1 turned ON.

TEST 26TEST OIL PRESSURE SWITCH

DISCUSSIONSee Section 6.5, "ENGINE SHUTDOWN FEATURES.”

TEST PROCEDURE: See Section 6.5. If necessary, connect an external oil pressure gauge to the oil pressure switch port.

3. Turn CB1 to ON position. Start generator. The engine should run at approximately 3300 rpm.

4. Set VOM to DC. Measure DC Link voltage between the Red and Blue wires, place Red test lead to red wire and Black test lead to the Blue wire. DC voltage should be approximately 375 VDC. Measure DC link voltage between the Red wire and Black wire, place Red test lead to Red wire and Black test lead to Black wire, DC voltage should read +175 VDC. Measure DC link voltage between the Blue wire and the Black wire, place Red test lead to Blue wire and Black test lead to Black wire. DC voltage should read –175 VDC.

RESULTS:

1. Replace oil pressure switch if it is defective or repair Wire 85 circuit as necessary.
2. If oil pressure is actually low as indicated by the external gauge, see Section 5.1, "ENGINE OIL SYSTEM".
3. If oil pressure is good and oil pressure switch is good, go to Test 27.
Page 127 of the Generac Power Systems 941-2 user manual — TEST PROCEDURE:
Page 127 · click to enlarge
Page 127

Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING

TEST 29 - 12 POSITION HARNESS

2. On units with A6060 circuit board revision “D” or higher software, jump pin #10 to pin #11 on the 12 position cable previously removed from the inverter. The 12 position cable should be connected to the 12 position socket on the generator control panel. This will enable the generator to run with CB1 turned ON.

CONTINUITY TEST

1. Set VOM to measure Resistance.
2. Measure from pin location #1 on one end of the 12 position harness to pin location #1 on the opposite end of the harness. A reading of “Continuity” should be measured. Repeat procedure for each pin position on the 12-wire harness. If an open condition is detected, replace the defective harness as necessary.
3. Turn CB1 to ON position. Start generator. The engine should run at approximately 3300rpm.
4. Set a DVOM to DC volts. Measure from the free end of the 12 position harness according to the chart below. Connect the negative and positive test leads as indicated in the chart.
3. If needed, check for continuity on the A6060 circuit board wire harness in the control panel. This connection is at location J1 on the circuit board. Follow the same procedure as steps 1 and 2 above.
(NoteFluke 87 true RMS meter used in test.)
5. Set a DVOM to AC volts. Measure the the free end of the 9Wire harness according to the chart below. Connect the negative and positive test leads as indicated in the chart.

TEST 30 - 12 POSITION HARNESS SIGNALS TEST

  • ASSUMPTION:
  • Engine runs
  • Inverter not connected

TEST PROCEDURE:

1. Disconnect the 12-wire cable from the inverter. Disconnect the Red-Black-Blue-Green DC Link wires from the inverter.

Figure 10 Free End of 12 Position Harness

Test With DVOM Set At DC Volts Connect negative lead to: Connect positive lead to: Reading should be:

Inverter Signals Ground Pin 9 (0 v) Pin 2 (En/Com) < 0.10 vdc

Inverter Signal Pin 2 (En/Com) Pin 1 (PWM1) 2.5 v ± 0.15 vdc

Inverter Signal Pin 2 (En/Com) Pin 3 (PWM2) 2.5 v ± 0.15 vdc

Temperature Voltage Pin 9 (0 v) Pin 10 (TEMP) 5.0 v ± 0.1 vdc

Inverter Fan Voltage Pin 9 (0 v) Pin 4 (Wire #14) 12 v ± 1.0 vdc

Shield Wire Test for Ground Pin 12 (SHIELD) Pin 4 (Wire #14) 12 v ± 1.0 vdc

Test With DVOM Set At AC Volts Connect negative lead to: Connect positive lead to: Reading should be:

Inverter Signal Pin 2 (En/Com) Pin 1 (PWM1) 2.5 v ± 2.0 vac*

Inverter Signal Pin 2 (En/Com) Pin 3 (PWM2) 2.5 v ± 2.0 vac*

* Tolerance is large because readings will vary, depending on type of meter used.

Page 128 of the Generac Power Systems 941-2 user manual — TEST 33 - TIMING WINDING TEST
Page 128 · click to enlarge
Page 128

Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING

TEST 31 - STATIC TESTS ON INVERTER

STATOR TESTS

  • ASSUMPTION:
  • Inverter not connected to generator.
  • Inverter has been disconnected for at least 5 minutes from running genset to allow capacitors to discharge.

TEST 32 - POWER SUPPLY WINDING TEST

1. Disconnect the 12 position cable from the inverter.
2. Start the unit with CB1 in the OFF position.

TEST PROCEDURE:

3. Set a VOM to measure AC. Measure voltage across Pin #6 and Pin #7. The power supply voltage should be approximately 25-30 VAC at approximately 2700 rpm.
1. Set a DVOM to DIODE RANGE . Measure the 12 position connector on the inverter according to the chart below. Connect the negative and positive test leads as indicated in the chart.
4. Turn CB1 to the ON position.
2. Set a DVOM to RESISTANCE RANGE . Measure the 12 position connector on the inverter according to the chart below. Connect the negative and positive test leads as indicated in the chart.
5. Voltage across the floating power supply should be approximately 30 to 34VAC at approximately 3400rpm.
6. If results are lower, there is a possible stator problem. Proceed to Test 34.

TEST 33 - TIMING WINDING TEST

1. Disconnect the timing winding from receptacle J5 on the A6060 circuit board (orange and grey wires).
2. Disconnect the 12 position harness from the inverter.
3. Two jumper wires with alligator clips are required.
4. Attach a jumper from Wire #15 (located at the fuse holder) to Wire #14 (located at the four tab terminal block in the control panel). This will enable fuel and ignition functions.

Figure 11. 12 Position Connector on Inverter

1. Test With DVOM Set At Diode Range Connect negative lead to: Connect positive lead to: Reading should be:

Signal Circuit Pin 2 (En/Com) Pin 1 (PWM1) 1.25 to 1.5 v

Signal Circuit Pin 2 (En/Com) Pin 3 (PWM2) 1.25 to 1.5 v

2. Test With DVOM Set At Resistance Range Connect negative lead to: Connect positive lead to: Reading should be:

Temperature Circuit Pin 9 (0 V) Pin 10 (TEMP) *10 kOhm @ 25°C ±500 Ohms

Sense Circuit Pin 9 (0 V) Pin 11 (SENSE) 20 kOhm ± 200 Ohm

*NTC thermistor; if inverter is hot, resistance may be several kOhm lower. If inverter is cold, resistance may be several kOhm higher

3. Test With DVOM Set At AC Volts Connect negative lead to: Connect positive lead to: Reading should be:

Fan Test Pin 9 (0 V) Pin 4 (Wire #14) See Note

Page 129 of the Generac Power Systems 941-2 user manual — TEST 35 - BRIDGE RECTIFIER TEST
Page 129 · click to enlarge
Page 129

Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING

5. Momentarily jump Wire #15 (located at the fuse holder) to Wire #56 (located at the Starter Contactor). This will initiate cranking of the engine. The generator will start, but the throttle will need to be controlled manually. Hold the throttle at about a half load setting.
4. Instal paper clips in connector to use as a test point.
5. Set a VOM to the DIODE test range.
6. Attach the negative test lead of the VOM to the Red Wire and the positive test lead to the Blue Wire.
7. The voltage measured across the Bridge Rectifier should be approximately 1.000 VDC. Any voltage reading higher or lower indicates a defective diode assembly. Disassemble the Bridge Rectifier and test each diode individually.
6. Set a VOM to measure AC. Measure the AC voltage at the timing winding connector (orange and grey wires). The voltage should be between 15 and 20 VAC.
7. If results are lower, there is a possible stator problem. Proceed to Test 34.

TEST 36 - AC POWER WINDING TEST

AC1/AC2/SL1/SL2

TEST 34 -STATOR RESISTANCE VALUES

1. Turn CB1 to the OFF position.

Refer to Part 1, Section 1.4 and 1.5 for test procedures.

2. Set a VOM to measure AC Volts.

AC1 to AC2 0.414 to 0.465 ohms

3. Connect one test lead to the bottom Grey wire (AC1) on CB1. Connect the other test lead to the Yellow wire (AC2) located on the Bridge Rectifier.

SL1 to SL2 0.414 to 0.465 ohms

#55 to #66 0.095 to .108 ohms

#55 to #77 0.095 to 0.108 ohms

4. Start the generator.

TIM1 to TIM2 0.102 to 0.116 ohms

5. The measured AC voltage reading should be approximately 187 VAC.

PS1 to PS2 0.206 to 0.227 ohms

6. Connect one test lead to the bottom Orange Wire (SL1) on CB1. Connect the other test lead to the Brown wire (SL2) located on the Bridge Rectifier.

TEST 35 - BRIDGE RECTIFIER TEST

1. Disconnect the Red-Black-Blue-Green DC Link wires from either the connection in the control panel or at the inverter. Isolate the DC Link wires.
7. Start the generator.
8. The measured AC voltage reading should be approximately 187 VAC.
2. Turn CB1 to the OFF position.
3. Disconnect the 3-pin connector at J4 on the A6060 circuit board.
9. If a lower voltage is measured, proceed to Test 34.
Page 130 of the Generac Power Systems 941-2 user manual — Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING
Page 130 · click to enlarge
Page 130

Section 7.2 ENGINE DC CONTROL SYSTEM / AC TROUBLESHOOTING

Page 131 of the Generac Power Systems 941-2 user manual — Series Impact 36 Plus
Page 131 · click to enlarge
Page 131

PAGE TITLE

PART 8 SPECIFICATIONS

8-1 Nominal Resistances of

AND CHARTS

COMPUTER CONTROLLED

8-4 to 8-8 Engine Specifications

8-9 Engine Torque Specifications

VARIABLE SPEED RV GENERATORS

8-10 Major Features and Dimensions

Series Impact 36 Plus

Show 4 more labels / short text on this page
8-1 General Specifications · Generator Windings · 8-2 Electrical Schematic · 8-3 Wiring Diagram
Page 132 of the Generac Power Systems 941-2 user manual — NOTES
Page 132 · click to enlarge
Page 132

NOTES

Page 133 of the Generac Power Systems 941-2 user manual — ENGINE SPEEDS AND VOLTAGE SPECIFICATIONS
Page 133 · click to enlarge
Page 133

Part 8 SPECIFICATIONS & CHARTS

TYPE Impact 36 G Impact 36 LP

MODEL 0940 0941

TYPE OF ROTOR Permanent Magnet Type Permanent Magnet Type

RATED WATTS 3600 3400

RATED VOLTS 115 115

RATED MAXIMUM 30.0 28.3 LOAD AMPERES

RATED FREQUENCY 60 Hz 60 Hz

OPERATING SPEED Variable Variable (See NOTE 1)

ENGINE MODEL GV-220 GV-220

TYPE OF ENGINE Vertical Shaft Vertical Shaft

FUEL SYSTEM Gasoline LP Gas

COOLING SYSTEM Air-Cooled Air-Cooled

OIL SYSTEM Pressure Pressure

OIL PUMP Trochoid Type Trochoid Type

AIR CLEANER Paper element Paper element w/foam pre-cleaner w/foam pre-cleaner

STARTER 12 VDC electric 12 VDC electric

IGNITION SYSTEM Solid State Solid State

SPARK PLUG Champion RC12YC Champion RC12YC (or equivalent) (or equivalent)

SPARK PLUG GAP 0.030 inch 0.030 inch (0.76mm) (0.76mm)

NOMINAL RESISTANCES OF GENERATOR WINDINGS

Stator Power Phase Windings

Lead AC1 0.414 to 0.465 ohm Lead AC2 0.414 to 0.465 ohm Lead SL1 0.414 to 0.465 ohm Lead SL2 0.414 to 0.465 ohm

Lead TIM1 (orange) to TIM2 (grey) 0.102 to 0.116 ohm

Stator Battery Charge Windings

Lead 55 to 77 0.095 to 0.108 ohm Lead 55 to 66 0.095 to 0.108 ohm

Stator Power Phase Winding

Lead PS1 0.206 to 0.227 ohm

ENGINE SPEEDS AND VOLTAGE SPECIFICATIONS

Listed below are normal running voltages, load voltages, engine speeds and frequency ranges.

LOAD % VOLTAGE (VAC) FREQUENCY (Hz) ENGINE SPEED (rpm)

0 121-112 61-59 2800-2400

50 120-109 61-59 3500-3000

100 120-109 61-59 4000-3500

PHASE 1-Phase 1-Phase · Stator Timing Winding

Page 134 of the Generac Power Systems 941-2 user manual — PCB1
Page 134 · click to enlarge
Page 134

Part 8 SPECIFICATIONS & CHARTS

ELECTRICAL SCHEMATIC (DRAWING NO. 0D4947-B)

1 OF 2

CUSTOMER SUPPLIED

BATTERY

SC

16 SM

F1

SW2

14A FP 0

HM HM

REMOTE

(LP ONLY)

PANEL

CONNECTOR

CH

SW1 17

START

STOP

BROWN

YELLOW

WHITE

GREEN

IM

IS

18 14 17 0

85 HTO

R1

LOP

SP1

15A

85 BCR

BATTERY CHARGE WINDING 66

STOP STOP

START START

SL2 SL1

POWER

WINDING

HM HM

AC2

TIMING

POWER SUPPLY

TIM2 TIM1

PS1 PS2 AC1 17 85

CB1

(OPTIONAL) (OPTIONAL) REMOTE PANEL REMOTE PANEL

GRN

RED 1 2

BLU

BR1 BR2 BR3 BR4

AC AC

BLK RED

J4

BLU

INV

J3

T1

J1

M

J2

TB

GRN

DC DC

J2

3 2 1 6 5 4 2 1 J3 J5

8 SHIELD

1 2 3 4 5 6 7

SENSE

11 10 9 4

J1

FAN+ FANTEMP

PWM2

PWM1

RTN

10 9 8 7 6 5 4 3 2 1

PCB1

J2

WHITE

T2

J4

SC

GRN

BLK

T1

BLU RED

CUSTOMER AC CONNECTION

18 85 17

Page 135 of the Generac Power Systems 941-2 user manual — - LUG, BARREL
Page 135 · click to enlarge
Page 135

Part 8 SPECIFICATIONS & CHARTS

WIRING DIAGRAM (DRAWING NO. 0D4947-B)

2 OF 2

CUSTOMER SUPPLIED

REMOTE PANEL CONNECTOR

1 2 3 4 J3

12V BATTERY

IS

GRD

RED

BLK

RED

SHLD

BLK

SM

GRD

VIO

HTO

LOP F1

BLK

SP1

RED

RED

0 GRN

BRN

SC

SW2

14A

17 ORG

ORG

RED

RED

18 VIO

VIO

WHT

SW1

J2

GENERATOR CONTROL

RED

RED

RED

BLK

RED

DK BLU

IM

GRN

R1

RED

RED

RED

CH

GRN

14 VIO

RED

GRD 2

BLK

BLK

BLK

15A

RED

PCB1

J2

TC

1 J1

PWM1

BLK

RTN PWM2

RED WHT

FAN+

GRN

FANTEMP SENSE

ORG BLU RED/BLK

11 J3

2 1 3 J4 SHIELD 8

J5

SHLD

5 6 4 2 3 1

RED

FP

BLK

BLK RED

BLK

BRN

YEL

ORG

RED

DC DC

J3

HM

J1

(LP ONLY)

FAN

+DC BUS

RED

RTN

BLK

BLUE

BLK RED

-DC BUS

BLU

BR1

EARTH

GRN

BR2

CB1A

ORG

J2

J3

J1

J8-1

J8-2

J2

TB

GRN

PWM1 J11-7 J11-4 J11-3 J11-2 J11-1 J11-6 J11-5

BR3

RTN

FAN+

PWM2

CB1B 10A

GRY

M

FAN-

BR4

INVERTER CONTROL

TEMP

SENSE

RED

SHIELD

6 PS2

PS1

YEL

BLK

J9

BCR

ORG

RED

J10

BRN

GRY

J4

BRN BLK

J5

J4

J6

J7

BRN

TIM1 PS2

BLK BLK

TIM2

AC1 PS1

IND

SL1 AC2

SL2

CHASSIS INVERTER

AC

NEUTRAL CONNECTION BY CUSTOMER

T1 T2

STATOR

CUSTOMER

WHITE

GREEN

BLACK

AC CONNECTION

LEGEND

BCR - BATTERY CHARGE RECTIFIER

BR1 - BRIDGE RECTIFIER

IM - IGNITION MODULE IS - IGNITION SENSOR L1 - LIGHT, RUN (OPTIONAL) LOP - SWITCH, LOW OIL PRESSURE (CLOSES ON LOW PRESSURE) M - STEPPER MOTOR THROTTLE CONTROL

IND - INDUCTOR ASSEMBLY

ENGINE GENERATOR

BR3 - BRIDGE RECTIFIER BR2 - BRIDGE RECTIFIER

BR4 - BRIDGE RECTIFIER

CB1 - CIRCUIT BREAKER, 10A, 2-POLE

CC - CHOKE COIL CH - CHOKE HEATER F1 - FUSE FP - FUEL PUMP ON GASOLINE

PCB1CONTROL CIRCUIT BOARD

R1 - 1 OHM, 50 WATTS SC - STARTER CONTACTOR SM - STARTER MOTOR SW1 - SWITCH, START/STOP SW2 - SWITCH, FUEL PUMP PRIME SP1 - SPARK PLUG

SHUT-OFF VALVE ON L/P INV - INVERTER BOX

HM - HOUR METER HTO - SWITCH, HIGH TEMPERATURE OIL (CLOSES ON HIGH TEMPERATURE) IC - IGNITION COIL

- LUG, BARREL

TC - TERMINAL, CONNECTOR 4 TAB

TB - TERMINAL BLOCK

- +

Page 136 of the Generac Power Systems 941-2 user manual — CRANKSHAFT END PLAY
Page 136 · click to enlarge
Page 136

Part 8 SPECIFICATIONS & CHARTS

GENERAL SPECIFICATIONS

MODEL GV-220 BORE 2.95 inches (75mm) STROKE 1.93 inches (49mm) DISPLACEMENT 216.5cc OIL CAPACITY W/O FILTER CHANGE 21 ounces (620ml) WITH FILTER CHANGE 29.5 ounces (870 ml)

VALVE TRAIN

MODEL GV-220 VALVE SEAT WIDTH: DESIGN WIDTH 0.034-0.044 inch (0.87-1.13mm) VALVE SEAT ANGLE 45 degrees VALVE MARGIN: DESIGN MARGIN 0.034-0.044 inch (0.87-1.13mm) INTAKE VALVE STEM DIAMETER: DESIGN DIAMETER 0.274-0.275 inch (6.965-6.980mm) EXHAUST VALVE STEM DIAMETER: DESIGN DIAMETER 0.273-0.274 inch 6.965-6.980mm) TAPPET DIAMETER INTAKE AND EXHAUST: DESIGN DIAMETER 0.293-0.294 inch (7.457-7.475mm) VALVE SPRINGS: FREE LENGTH 2.074 inch (52.69mm) FORCE REQUIRED TO COMPRESS SPRING TO 1.39 INCH (35.2mm) 19.8-21.8 pounds (9.0-9.9kg) VALVE CLEARANCE: INTAKE 0.001-0.0022 inch (0.03O.056mm) EXHAUST 0.0018-0.003 in. (0.07-0.046mm) VALVE GUIDES: DESIGN DIAMETER 0.237-0.2364 inch (6.02-6.005mm)

CRANKSHAFT END PLAY

ALLOWABLE END PLAY 0.006-0.023 inch (0.14-0.60mm)

Page 137 of the Generac Power Systems 941-2 user manual — CRANKCASE COVER ASSEMBLY
Page 137 · click to enlarge
Page 137

Part 8 SPECIFICATIONS & CHARTS

CRANKCASE ASSEMBLY

MODEL GV-220 CYLINDER BORE: DESIGN DIAMETER 2.953-2.954 inch (75.000-75.025mm) VALVE TAPPET BORE: DESIGN DIAMETER 0.295-0.296 inch (7.494-7.520mm) CRANKSHAFT SLEEVE BEARING: DESIGN DIAMETER 1.104-1.106 inch *(WHERE APPLICABLE) (28.044-28.099mm) GOVERNOR ARM BORE: DESIGN DIAMETER 0.239-0.240 inch (6.07-6.10mm) CAMSHAFT BEARING: DESIGN DIAMETER 1.024-1.025 inch (26.00-26.03mm) GOVERNOR ARM DIAMETER: DESIGN DIAMETER: 0.235-0.237 inch (5.97-6.03mm)

*Later model small frame GN engines have no crankshaft sleeve bearing.

CRANKCASE COVER ASSEMBLY

MODEL GV-220

CRANKSHAFT BEARING BOREDESIGN DIAMETER 1.104-1.105 inch (28.040-28.065mm)
CAMSHAFT BEARING BOREDESIGN DIAMETER 1.299-1.300 inch (33.00-33.03mm)

GOVERNOR GEAR SHAFT DIAMETER 0.236-0.237 inch (6.004-6.012mm)

OIL PUMP INNER ROTOR SHAFT DIAMETER: DESIGN DIAMETER 0.353-0.354 inch (8.969-8.987mm)

Page 139 of the Generac Power Systems 941-2 user manual — Part 8 SPECIFICATIONS & CHARTS
Page 139 · click to enlarge
Page 139

Part 8 SPECIFICATIONS & CHARTS

PISTON (CONTINUED)

MODEL GV-220 WRIST PIN BORE DIAMETER: DESIGN DIAMETER 0.708-0.709 inch (18.000-18.011mm) TOP RING GROOVE WIDTH: DESIGN WIDTH 0.059-0.061 inch (1.52-1.54mm) SECOND RING GROOVE WIDTH: DESIGN WIDTH 0.059-0.061 inch (1.52-1.54mm) OIL CONTROL RING GROOVE WIDTH: DESIGN WIDTH 0.118-0.119 inch (3.01-3.03mm) TOP RING WIDTH: DESIGN WIDTH 0.057-0.059 inch (1.47-1.49mm) TOP RING END GAP: * DESIGN END GAP 0.005-0.016 inch (0.15-0.40mm) SECOND RING WIDTH: DESIGN WIDTH 0.057-0.059 inch ( 1.465-1.490mm) SECOND RING END GAP: * DESIGN END GAP 0.006-0.016 inch (0.15-0.40mm) OIL CONTROL RING WIDTH: DESIGN WIDTH 0.111-0.118 inch (2.825-3.003mm) OIL CONTROL RING END GAP: * DESIGN END GAP 0.015-0.055 inch ( 0.38-1.40mm)

*NOTE 1Measure end gap with ring pushed down in cylinder to depth of 2.75 inches
Page 140 of the Generac Power Systems 941-2 user manual — OIL PUMP
Page 140 · click to enlarge
Page 140

Part 8 SPECIFICATIONS & CHARTS

CAMSHAFT ASSEMBLY

MODEL GV-220 MAIN CAMSHAFT BEARING DIAMETER (FLYWHEEL END): DESIGN DIAMETER 1.022-1.023 inch (25.96-25.98mm) MAIN CAMSHAFT BEARING DIAMETER (PTO END): DESIGN DIAMETER 1.297-1.298 inch (32.96-32.98mm) CAM LIFT: DESIGN LIFT 0.210-0.212 inch (5.34-5.38mm) BASE CIRCLE DIAMETER OF CAM: DESIGN DIAMETER 0.978-0.990 inch (24.85-25.15mm) COMPRESSION RELEASE LIFT (MEASURED AT TAPPET): DESIGN LIFT 0.027-0.055 inch (0.70-1.40mm)

OIL PUMP

MODEL GV-220 PUMP TIP CLEARANCE *: DESIGN CLEARANCE 0.0000-0.0010 inch (0.000-0.025mm) INNER ROTOR BORE: DESIGN BORE 0.354-0.355 inch (9.000-9.019mm) INNER ROTOR THICKNESS: DESIGN THICKNESS 0.312-0.315 inch (7.95-8.00mm) OUTER ROTOR OUTSIDE DIAMETER: DESIGN DIAMETER 1.296-1.297 inch (32.92-32.95mm) OUTER ROTOR THICKNESS: DESIGN THICKNESS 0.314-0.316 inch (8.000-8.025mm)

*NOTE 2: Measure pump tip clearance on shaft in crankcase cover.

Page 141 of the Generac Power Systems 941-2 user manual — TORQUE SPECIFICATIONS
Page 141 · click to enlarge
Page 141

Part 8 SPECIFICATIONS & CHARTS

OIL PUMP (CONTINUED)

MODEL GV-220 OIL PRESSURE RELIEF VALVE SPRING: Force required to compress 0.85-0.95 pounds spring to 1.035 inch (0.39-0.43kg) (26.3mm)

COMPRESSION PRESSURE

MODEL GV-220 WHILE CRANKING (COLD ENGINE) 60 psi min.

TORQUE SPECIFICATIONS

MODEL GV-220 Rocker Cover Screws 4 ft-lbs (48 in-lbs)

Rocker Arm Jam Nut 14.5 ft-lbs (174 in-lbs)

Cylinder Head Bolts 22 ft-lbs (264 in-lbs)

Connecting Rod Bolts 10 ft-lbs (120 in-lbs)

Flywheel Nut 75 ft-lbs (900 in-lbs)

Crankcase Cover Bolts 18 ft-lbs (216 in-lbs)

Ignition Coil Bolts 5 ft-lbs (60 in-lbs)

Spark Plug 13 ft-lbs (156 in-lbs)

Rewind Starter Screws 5 ft-lbs (60 in-lbs)

Starter Motor Bolts 18 ft-lbs (216 in-lbs)

Intake Manifold Screws 4 ft-lbs (50 in-lbs)

Carburetor to Intake Manifold 3.3 ft-lbs (40 in-lbs)

Air Cleaner Box (to Carburetor) 4 ft-lbs (50 in-lbs)

Blower Housing Screws 7 ft-lbs (84 in-lbs)

Upper and Lower Shroud Screws 4 ft-lbs (48 in-lbs)

Governor Lever Clamp Bolt 5.8 ft-lbs (70 in-lbs)

Oil Filter Adapter Bolts 9 ft-lbs (108 in-lbs)

Low Oil Switch 9 ft-lbs (108 in-lbs)

Page 142 of the Generac Power Systems 941-2 user manual — Part 8 SPECIFICATIONS & CHARTS
Page 142 · click to enlarge
Page 142

Part 8 SPECIFICATIONS & CHARTS

Generac Power Systems 941-2 — Part 8 SPECIFICATIONS & CHARTS diagram (page 142)
Fig. 128 · Part 8 SPECIFICATIONS & CHARTS
Page 143 of the Generac Power Systems 941-2 user manual — Part 8 SPECIFICATIONS & CHARTS
Page 143 · click to enlarge
Page 143

Part 8 SPECIFICATIONS & CHARTS

Generac Power Systems 941-2 — Part 8 SPECIFICATIONS & CHARTS diagram (page 143)
Fig. 129 · Part 8 SPECIFICATIONS & CHARTS
Page 144 of the Generac Power Systems 941-2 user manual — PART 8 - SPECIFICATIONS AND CHARTS
Page 144 · click to enlarge
Page 144
Page 144 of the Generac Power Systems 941-2 user manual — PART 8 - SPECIFICATIONS AND CHARTS
Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Display codes

Error codes

What the fault codes shown on the display mean and how to clear them.

CodeMeaningFix
CB1Connect the other test lead to the Brown wire (SL2) locat- p.129
Fix-it

Troubleshooting

Common problems, likely causes, and what to do.

ProblemPossible causeRemedy
1. Engine starts, accelerates, shuts down at 4500 rpma. Carburetor linkage sticking with throttle stuck open. b. Stepper Motor failed or seized. c. Stepper Motor wire connections broken or disconnected. d. Stepper Motor not properly connected.a. Repair sticking throttle b. Replace Stepper Motor. c. Reconnect or repair. d. Reconnect wires. p.109
2. Overvoltage condition and speed control system cannot reduce output voltage.a. Carburetor linkage sticking with throttle stuck partly open. b. Stepper Motor failed or seized. c. Connection to Stepper Motor is broken/disconnected with throttle open. d. Stepper Motor not properly connected.a. Repair sticking throttle. b. Replace Stepper Motor. c. Repair or replace connections. d. Reconnect Stepper Motor wires. p.109
3. Engine speed is maintained and no-load voltage is good. However, when load is applied output voltage drops.a. Carburetor linkage sticking with throttle partly open. b. Stepper Motor failed or seized. c. Connection to Stepper Motor Motor broken or disconnected. d. Stepper Motor not properly connected.a. Repair sticking throttle. b. Replace Stepper Motor. c. Repair or replace connections. d. Reconnect Stepper Motor. p.109
4. Engine does not accelerate when load is applied.a. Carburetor linkage sticking with throttle stuck closed. b. Stepper Motor failed or seized. c. Stepper Motor not properly connected.a. Repair sticking throttle. b. Replace Stepper Motor. c. Reconnect Stepper Motor. p.109
5. Engine speed and AC output voltage erratic under constant load. AC output does not turn off intermittently.a. Stepper Motor failure. b. Connection to Stepper Motor broken or disconnected. c. Stepper Motor not properly connecteda. Replace Stepper Motor. b. Repair or replace connections. c. Reconnect Stepper Motor. p.109
6. Engine starts but Stepper Motor does not move. Shut down occurs after several seconds.a. Stator Timing winding is open. b. Timing winding in Stator shorted to ground.a. Repair/replace bad wire(s) TIM1/TIM2 or replace Stator. b. Replace Stator. p.109
Test With DVOM Set At DC Volts p.127
Inverter Signals Ground p.127
Inverter Signal p.127
Temperature Voltage p.127
Inverter Fan Voltage p.127
Shield Wire Test for Ground p.127
Shield Wire Test for Ground p.127
Test With DVOM Set At AC Volts p.127
* Tolerance is large because readings will vary, depending on type of meter used. p.127
* Tolerance is large because readings will vary, depending on type of meter used. p.127

Ask about the Generac Power Systems 941-2

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Generac Power Systems 941-2

Be the first to ask — other owners or our team will answer.

Original document

Generac Power Systems 941-2 manual PDF

144 pages·4.7 MB·Portable Generator·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…