RECREATIONAL VEHICLE GENERATOR
ModelS 5410, 5411, 5412,
5413, 5414 & 5415

Throughout this publication, “DANGER!” and “CAUTION!” blocks are used to alert the mechanic to special instructions concerning a particular service or operation that might be hazardous if performed incorrectly or carelessly. PAY CLOSE ATTENTION TO THEM. *
DANGER! UNDER THIS HEADING WILL BE FOUND SPECIAL INSTRUCTIONS WHICH, IF NOT COMPLIED
WITH, COULD RESULT IN PERSONAL INJURY OR DEATH.
CAUTION! Under this heading will be found special instructions which, if not complied with, could result
in damage to equipment and/or property.
These “Safety Alerts” alone cannot eliminate the hazards that they signal. Strict compliance with these special Instructions plus “common sense” are major accident prevention measures.
This SERVICE MANUAL has been written and published by Generac to aid our dealers’ mechanics and com pany service personnel when servicing the products described herein. It is assumed that these personnel are familiar with the servicing procedures for these products, or like or similar products manufactured and marketed by Generac. That they have been trained in the recommended servicing procedures for these products, including the use of common hand tools and any special Generac tools or tools from other suppliers. Generac could not possibly know of and advise the service trade of all conceivable procedures by which a service might be performed and of the possible hazards and/or results of each method. We have not under taken any such wide evaluation. Therefore, anyone who uses a procedure or tool not recommended by Generac must first satisfy himself that neither his nor the products safety will be endangered by the service procedure selected. All information, illustrations and specifications in this manual are based on the latest product information available at the time of publication. When working on these products, remember that the electrical system and engine ignition system are capa ble of violent and damaging short circuits or severe electrical shocks. If you intend to perform work where electrical terminals could be grounded or touched, the battery cables should be disconnected at the battery. Any time the intake or exhaust openings of the engine are exposed during service, they should be covered to prevent accidental entry of foreign material. Entry of such materials will result in extensive damage when the engine Is started. During any maintenance procedure, replacement fasteners must have the same measurements and strength as the fasteners that were removed. Metric bolts and nuts have numbers that indicate their strength. Customary bolts use radial lines to indicate strength while most customary nuts do not have strength mark ings. Mismatched or incorrect fasteners can cause damage, malfunction and possible injury.
Components on Generac recreational vehicle generators are designed and manufactured to comply with Recreational Vehicle Industry Association (RVIA) Rules and Regulations to minimize the risk of fire or explo sion. The use of replacement parts that are not in compliance with such Rules and Regulations could result in a fire or explosion hazard. When servicing this equipment, It is extremely important that all components be properly installed and tightened. If Improperly Installed and tightened, sparks could Ignite fuel vapors from fuel system leaks.


Test 10 – Check Rotor Assembly 42 Test 11 – Check Main Circuit Breaker 43 Test 12 – Check Load Voltage & Frequency 43 Test 13 – Check Load Watts & Amperage 43 Test 14 – Try Cranking the Engine 44 Test 15 – Check Fuel Pump 44 Test 16 – Check 7.5 Amp Fuse 45 Test 17 – Check Battery & Cables 45 Test 18 – Check Power Supply to Printed Circuit Board 45 Test 19 – Check Continuity of Wire 17 46 Test 20 – Check Start-Stop Switch 46 Test 21 – Check Power Supply to Wire 56 47 Test 22 – Check Starter Contactor Relay 47 Test 23 – Check Starter Contactor 48 Test 24 – Check Starter Motor 48 Test 25 – Check Fuel Supply 51 Test 26 – Check Wire 14 Power Supply 52 Test 27 – Check Wire 18 53 Test 28 – Check Fuel Solenoid (Gasoline Models) 53 Test 29 – Check Ignition Spark 54 Test 30 – Check Spark Plugs 55 Test 31 – Check and Adjust Ignition Magnetos 55
Test 32 – Check Valve Adjustment 57 Test 33 – Check Carburetion 58 Test 34 – Check Choke Solenoid 58 Test 35 – Check Engine / Cylinder Leak Down Test / Compression Test 59 Test 36 – Check Oil Pressure Switch 60 Test 37 – Test Wire 86 for Continuity 61 Test 38 – Test Oil Temperature Switch 61 Test 39 – Test Wire 85 for Continuity 62 Test 40 – Test Choke Heater 62 Test 41 – Check LPG Fuel Solenoid 63
Base & Pulley Drawing 64 Enclosure Drawing 66 Control Panel Drawing 68 Engine Accessories Drawing 70 530 RV Engine Drawing 72 Rotor and Stator Drawing 74
Major Features And Dimensions 76 Generator Specifications 77 Nominal Resistances of Generator Windings at 68°F 77 Torque Requirements 77
Electrical Schematic and Wiring Diagram 78

Magnetism can be used to produce electricity and electricity can be used to produce magnetism. Much about magnetism cannot be explained by our present knowledge. However, there are certain pat terns of behavior that are known. Application of these behavior patterns has led to the development of gen erators, motors and numerous other devices that uti lize magnetism to produce and use electrical energy. See Figure 1-1. The space surrounding a magnet is permeated by magnetic lines of force called “flux”. These lines of force are concentrated at the magnet’s north and south poles. They are directed away from the magnet at its north pole, travel in a loop and re- enter the magnet at its south pole. The lines of force form definite patterns which vary in intensity depend ing on the strength of the magnet. The lines of force never cross one another. The area surrounding a magnet in which its lines of force are effective is called a “magnetic field”. Like poles of a magnet repel each other, while unlike poles attract each other.
Figure 1-2. – The Right Hand Rule
An electromotive force (EMF) or voltage can be pro duced in a conductor by moving the conductor so that it cuts across the lines of force of a magnetic field. Similarly, if the magnetic lines of force are moved so that they cut across a conductor, an EMF (voltage) will be produced in the conductor. This is the basic principal of the revolving field generator. Figure 1-3, below, illustrates a simple revolving field generator. The magnetic field (Rotor) is rotated so that its lines of magnetic force cut across a coil of wires called a Stator. A voltage is then induced into the Stator windings. If the Stator circuit is completed by connecting a load (such as a light bulb), current will flow in the circuit and the bulb will light.
Figure 1-1. – Magnetic Lines of Force
STATOR
LOAD
Figure 1-3. – A Simple Revolving Field Generator

Figure 1-4 shows a very simple AC Generator. The generator consists of a rotating magnetic field called a ROTOR and a stationary coil of wire called a STATOR. The ROTOR is a permanent magnet which consists of a SOUTH magnetic pole and a NORTH magnetic pole. As the ROTOR turns, its magnetic field cuts across the stationary STATOR. A voltage is induced Into the STATOR windings. When the magnet’s NORTH pole passes the STATOR, current flows in one direc tion. Current flows in the opposite direction when the magnet’s SOUTH pole passes the STATOR. This con stant reversal of current flow results in an alternating current (AC) waveform that can be diagrammed as shown in Figure 1-5. The ROTOR may be a 2-pole type having a single NORTH and a single SOUTH magnetic pole. Some ROTORS are 4-pole type with two SOUTH and two NORTH magnetic poles. The following apply: 1. The 2-pole ROTOR must be turned at 3600 rpm to produce an AC frequency of 60 Hertz, or at 3000 rpm to deliver an AC frequency of 50 Hertz.
ONE CYCLE
Figure 1-5. – Alternating Current Sine Wave
Figure 1-6 represents a more sophisticated generator. A regulated direct current is delivered into the ROTOR windings via carbon BRUSHES AND SLIP RINGS. This results in the creation of a regulated magnetic field around the ROTOR. As a result, a regulated volt age is induced into the STATOR. Regulated current delivered to the ROTOR is called “EXCITATION” cur rent.
STATOR 240 V
STATOR
STATOR
BRUSHES
ROTOR
SLIP RINGS
Figure 1-6. – A More Sophisticated Generator
See Figure 1-7 (next page). The revolving magnet ic field (ROTOR) is driven by the engine at a con stant speed. This constant speed is maintained by a mechanical engine governor. Units with a 2-pole rotor require an operating speed of 3600 rpm to deliver a 60 Hertz AC output. Engine governors are set to maintain approximately 3720 rpm when no electrical loads are connected to the generator.
Figure 1-4. – A Simple AC Generator
(+) · 0 180 360 · (-)


NOTE: AC output frequency at 3720 rpm will be about 60 Hertz. The “No-Load” is set slightly high to prevent excessive rpm, frequency and voltage droop under heavy electrical loading. Generator operation may be described briefly as fol lows: 1. Some “residual” magnetism is normally present in the Rotor and is sufficient to induce approximately 7 to 12 volts AC Into the STATOR’s AC power windings.
b. An “Actual” (“sensing”) voltage is delivered to
the Voltage Regulator via sensing leads from the Stator AC power windings. c. The Regulator “compares” the actual (sens
ing) voltage to its pre-set reference voltage. (1) If the actual (sensing) voltage is great er than the pre-set reference voltage, the Regulator will decrease the regulated current flow to the Rotor. (2) If the actual (sensing) voltage is less than the pre-set reference voltage, the Regulator will increase the regulated current flow to the Rotor. (3) In the manner described, the Regulator maintains an actual (sensing) voltage that is equal to the pre-set reference voltage.
a. The battery voltage is called “Field Boost”. b. Flow of direct current through the ROTOR
increases the strength of the magnetic field above that of “residual” magnetism alone. 3. “Residual” plus “Field Boost” magnetism induces a voltage into the Stator excitation (DPE) and AC Power windings.
a. A “Reference” voltage has been preset into
the Voltage Regulator.

When the engine is cranked during startup, the starter contactor is energized closed. Battery voltage is then delivered to the starter motor and the engine cranks. During cranking, battery voltage flows through a resis tor and a field boost diode in the Printed Circuit Board, then to the Rotor via brushes and slip rings. This is called “Field Boost” voltage. Field boost voltage is delivered to the Rotor only while the engine is cranking. The effect is to “flash the field” every time the engine is cranked. Field boost voltage helps ensure that sufficient “pickup” voltage is avail able on every startup to turn the Voltage Regulator on and build AC output voltage. NOTE: Loss of the Field Boost function may or may not result in loss of AC power winding output. If Rotor residual magnetism alone is sufficient to turn the Regulator on, loss of Field Boost may go unnoticed. However, if residual magnetism alone is not enough to turn the Regulator on, loss of the Field Boost function will result in loss of AC power winding output to the load. The AC output voltage will then drop to a value commensurate with the Rotor’s residual magnetism (about 7-12 VAC).
Caution! Do not overload the generator. Some
installations may require that electrical loads be alternated to avoid overloading. Applying excessively high electrical loads may damage the generator and may shorten its life. Add up the rated watts of all electrical lighting, appli ance, tool and motor loads the generator will power at one time. This total should not be greater than the wattage capacity of the gen erator. If an electrical device nameplate gives only volts and amps, multiply volts times amps to obtain watts (volts x amps = watts). Some electric motors require more watts of power (or amps of current) for starting than for continuous operation.
These air-cooled generator sets are equipped with dual stator AC power windings. These two stator wind ings supply electrical power to customer electrical loads by means of a dual 2-wire connection system. Generators may be installed to provide the following outputs: 1. 120 VAC loads only — one load with a maximum total wattage requirement equal to the generator’s rated power output (in watts), and 120 VAC across the generator output terminals. Figure 1-8, page 7, shows the generator lead wire connections for 120 VAC ONLY.
Line breakers (120 Volts Only): Protects generator’s AC output circuit against overload, i.e., prevents unit from exceeding wattage/ amperage capacity. The circuit breaker ratings are as follows:

CB1
T2 WHITE
Figure 1-8. – Connection for 120 Volts Only
GROUNDED NEUTRAL STATOR WINDINGS
Reconnection for Dual Voltage Output: When connected for dual voltage output, Stator output leads 11 and 44 form two “hot” leads (T1 – Red, and T3 – Black). The junction of leads 22 and 33 form the “Neutral” line (T2 – White). For dual voltage output, the “Neutral” line remains grounded. NOTE: For units with two 20 amp or two 30 amp main breakers, the existing breakers may be re- used when reconnecting for dual voltage output. However, on units with a 30 amp and a 20 amp main breaker, you may wish to install a 2-pole breaker that is rated closer to the unit’s rated capacity (use two 25 amp main breakers).
Figure 1-9 - Connection for 120/240 Volts
T3 BLACk

2. UPPER BEARING CARRIER
3. STATOR
4. ROTOR
5. LOWER BEARING CARRIER
6. ENGINE
7. PULLEYS AND BELT
8. FANS
Figure 2-1. Exploded View of Generator
Stator Assembly
The Rotor is sometimes called the “revolving field”, since it provides the magnetic field that induces a voltage into the stationary Stator windings. Slip rings on the Rotor shaft allow excitation current from the voltage regulator to be delivered to the Rotor wind ings. The Rotor is driven by the engine at a constant speed through a pulley and belt arrangement. All generator models in this manual utilize a 2-pole Rotor, i.e., one having a single north and a single south pole. This type of Rotor must be driven at 3600 rpm for a 60 Hertz AC output, or at 3000 rpm for a 50 Hertz output. Slip rings may be cleaned. If dull or tarnished, clean them with fine sandpaper (a 400 grit wet sandpaper is recom mended). DO NOT USE ANY MATERIAL CONTAINING METALLIC GRIT TO CLEAN SLIP RINGS.
The Stator is “sandwiched” between the upper and lower bearing carriers and retained in that position by four Stator studs. A total of eight (8) leads are brought out of the Stator as follows: 1. Four (4) Stator power winding output leads (Wires No. 11, 22, 33 and 44). These leads deliver power to connected electrical loads.

11S
11S
22S
22S
22S
VOLTAGE
REGULATOR
6 2 4 0
DPE WINDING
FIELD
22S
BA
Leads 2 & 6 = Stator Excitation Winding Leads 11S & 22S = Voltage Sensing Leads Leads 11 & 22, 33 & 44 = AC Power Windings
Figure 2-2. – Stator Output Leads
The brush holder is retained in the rear bearing car rier by two M5 screws. It retains two brushes, which contact the Rotor slip rings and allow current flow from stationary parts to the revolving Rotor. The posi tive (+) brush is located nearest the Rotor bearing.
BRUSHES
Figure 2-3. – Brush Holder
Figure 2-7. – Voltage Regulator
The regulator mounts a “VOLTAGE ADJUST” potentiometer, used for adjustment of the pre-set REFERENCE voltage. A lamp (LED) will turn on to indicate that SENSING voltage is available to the regulator and that the regulator is turned on.
GENERAL: During operation, the Rotor’s magnetic field induces a voltage and current flow into the Stator excitation winding. This results in AC output delivered to a volt age regulator via Wires 2 and 6.
Adjustment procedure: With the frequency set at 60 Hertz and no load on the generator, slowly turn the voltage adjust pot on the volt age regulator until 122-126 VAC is measured. If voltage is not adjustable, proceed to Section 6 – Troubleshooting.
0 + · Stator · VOLTAGE ADjUST POT

NOTE: If, for any reason, sensing voltage to the regulator is lost, the regulator will shut down and excitation output to the Rotor will be lost. The AC output voltage will then drop to a value that is commensurate with Rotor residual magnetism (about 7-12 VAC). Without this automatic shut down feature, loss of sensing (actual) voltage to the regulator would result in a “full field” or “full excitation” condition and an extremely high AC output voltage. NOTE: Adjustment of the regulator’s “VOLTAGE ADJUST” potentiometer must be done only when the unit is running at its correct governed no-load speed. Speed is correct when the unit’s no-load AC output frequency is about 60.0-60.5 Hertz. At the stated frequency, AC output voltage should be about 124 volts.
DESCRIPTION: The crankcase breather is equipped with a reed valve to control and maintain a partial vacuum in the crank case. The breather is vented to the airbox. The breath er chamber contains a removable oil vapor collector. Oil vapor is condensed on the collector material and drains back into the crankcase, which minimizes the amount of oil vapor entering the breather.
Check Breather: 1. Disconnect breather tube and remove two screws and breather. Discard gasket.
Install Breather: 1. Install oil vapor collector and retainer.
a. Torque screws to 5-8 ft-lbs. 3. Assemble breather tube to intake elbow.
OIL VAPOR COLLECTOR
Figure 2-8. – Crankcase Breather

STARTER CONTACTOR RELAY (SCR)
TERMINAL BLOCK (TB)
“4-TAB CONNECTOR”
CONTROL BOARD (PCB)
WITH J1 CONNECTOR
GOVERNOR ACTUATOR
J2 CONNECTOR
VOLTAGE REGULATOR
(VR) WITH RED LED
START/STOP SWITCH (SW1)
WITH RED LED
7.5 AMP DC FUSE (F1) CIRCUIT BREAKERS
(CB1 & CB2)
ENGINE CONNECTOR (C1)
6 WIRE GROUND TERMINAL
REAR VIEW
Figure 2-9. – Control Panel Components

MEGOHMMETERS ARE A SOURCE OF HIGH AND DANGEROUS ELECTRICAL VOLTAGE. FOLLOW THE TESTER MANUFACTURER’S INSTRUCTIONS CAREFULLY. USE COMMON SENSE TO AVOID DANGEROUS ELECTRICAL SHOCK
Moisture and dirt are detrimental to the continued good operation of any generator set. If moisture is allowed to remain in contact with the Stator and Rotor windings, some of the moisture will be retained in voids and cracks of the winding insula tion. This will result in a reduced Insulation resistance and, eventually, the unit’s AC output will be affected. Insulation used in the generator is moisture resistant. However, prolonged exposure to moisture will gradu ally reduce the resistance of the winding insulation. Dirt can make the problem worse, since it tends to hold moisture Into contact with the windings. Salt, as from sea air, contributes to the problem since salt can absorb moisture from the air. When salt and moisture combine, they make a good electrical conductor. Because of the detrimental affects of dirt and mois ture, the generator should be kept as clean and as dry as possible. Rotor and Stator windings should be tested periodically with an insulation resistance tester (such as a megohmmeter or hi-pot tester). If the Insulation resistance is excessively low, drying may be required to remove accumulated moisture. After drying, perform a second insulation resistance test. If resistance is still low after drying, replacement of the defective Rotor or Stator may be required.
GENERAL: If tests indicate the insulation resistance of a winding is below a safe value, the winding should be dried before operating the generator. Some recommended drying procedures include (a) heating units and (b) forced air.
HEATING UNITS: If drying is needed, the generator can be enclosed in a covering. Heating units can then be installed to raise the temperature about 15°-18° F (8°-10° C) above ambient temperature.
FORCED AIR: Portable forced air heaters can be used to dry the generator. Direct the heated air into the generator’s air intake openings. Remove the voltage regulator and run the unit at no-load. Air temperature at the point of entry into the generator should not exceed 150° F. (66° C.).
Figure 3-1 shows one kind of hi-pot tester. The tester shown has a “Breakdown” lamp that will glow during the test procedure to indicate an insulation breakdown in the winding being tested.
GENERAL: The generator can be cleaned properly only while it is disassembled. The cleaning method used should be determined by the type of dirt to be removed. Be sure to dry the unit after it has been cleaned. NOTE: A shop that repairs electric motors may be able to assist you with the proper cleaning of generator windings. Such shops are often expe rienced in special problems such as a sea coast environment, marine or wetland applications, min ing, etc.
USING SOLVENTS FOR CLEANING: If dirt contains oil or grease a solvent is generally required. Only petroleum distillates should be used to clean electrical components. Recommended are safe ty type petroleum solvents having a flash point greater than 100° F. (38° C.).
Figure 3-1. – One Type of Hi-Pot Tester
*
or polyester base winding varnishes. Use sol

vents that will not attack such materials.
STATOR SHORT-TO-GROUND TESTS: See Figure 3-2. To test the Stator for a short-to-ground condition, proceed as follows: 1. Disconnect and Isolate all Stator leads as follows:
Use a soft brush or cloth to apply the solvent. Be careful to avoid damage to wire or winding insulation. After cleaning, dry all components thoroughly using moisture-free, low-pressure compressed air. *
a. Disconnect sensing leads 11S and 22S from
the voltage regulator. b. Disconnect excitation winding lead No. 6 from
WITH SOLVENTS IN ANY ENCLOSED AREA. PROVIDE ADEQUATE VENTILATION WHEN WORKING WITH SOLVENTS. WITHOUT ADEQUATE VENTILATION, FIRE, EXPLOSION OR HEALTH HAZARDS MAY EXIST . WEAR EYE PROTECTION. WEAR RUBBER GLOVES TO PROTECT THE HANDS.
the voltage regulator. c. Disconnect excitation lead No. 2 from the volt
age regulator (VR). e. At the main circuit breakers, disconnect AC
power leads No. 11 and 33. f. At the 4-tab ground terminal (GRD2), discon nect Stator power leads No. 22 and 44. 2. When all leads have been disconnected as out lined in Step 1 above, test for a short-to-ground condition as follows:
CLOTH OR COMPRESSED AIR: For small parts or when dry dirt is to be removed, a dry cloth may be sufficient. Wipe the parts clean, then use low pressure air at 30 psi (206 Kpa) to blow dust away.
a. Connect the terminal ends of all Stator leads
together (11S, 22S, 11, 22, 33, 44, 2, & 6). b. Follow the tester manufacturer’s instructions
BRUSHING AND VACUUM CLEANING: Brushing with a soft bristle brush followed by vacuum cleaning is a good method of removing dust and dirt. Use the soft brush to loosen the dirt, then remove it with the vacuum.
carefully. Connect the tester leads across all Stator leads and to frame ground on the Stator can. Apply a voltage of 1500 volts. Do NOT apply voltage longer than one (1) sec ond.
If the test indicates a breakdown in insulation, the Stator should be cleaned, dried and re-tested. If the winding fails the second test (after cleaning and dry ing), replace the Stator assembly.
GENERAL: Insulation resistance is a measure of the integrity of the insulating materials that separate electrical wind ings from the generator’s steel core. This resistance can degrade over time due to the presence of con taminants, dust, dirt, grease and especially moisture. The normal insulation resistance for generator wind ings is on the order of “millions of ohms” or “mego hms”. When checking the insulation resistance, follow the tester manufacturer’s Instructions carefully. Do NOT exceed the applied voltages recommended in this manual. Do NOT apply the voltage longer than one (1) second. *
TEST BETWEEN ISOLATED WINDINGS: 1. Follow the tester manufacturer’s instructions care fully. Connect the tester test leads across Stator leads No. 11 and 2. Apply a voltage of 1500 volts- DO NOT EXCEED 1 SECOND.
a. Across Wires No. 33 and 2. b. Across Wires No. 11 and 33. c. Across Wires No. 11 and 2.
If a breakdown in the insulation between isolated windings is indicated, clean and dry the Stator. Then, repeat the test. If the Stator fails the second test, replace the Stator assembly.
or Megohmmeter test leads to any leads that are routed into the generator control panel. Connect the tester leads to the Stator or Rotor leads only.
TEST BETWEEN PARALLEL WINDINGS: Connect the tester leads across Stator leads No. 11 and 33. Apply a voltage of 1500 volts. If an insula tion breakdown is indicated, clean and dry the Stator. Then, repeat the test between parallel windings. If the Stator fails the second test, replace it.

If an insulation breakdown is indicated, clean and dry the Rotor then repeat the test. Replace the Rotor if it fails the second test (after cleaning and drying).
GENERAL: A megohmmeter, often called a “megger”, consists of a meter calibrated in megohms and a power sup ply. Use a power supply of 1500 volts when testing Stators; or 1000 volts when testing the Rotor. DO NOT APPLY VOLTAGE LONGER THAN ONE (1) SECOND.
22S
Leads 2 & 6 = Stator Excitation Winding Leads 11S & 22S = Voltage Sensing Leads Leads 11 & 22, 33 & 44 = AC Power Windings
TESTING STATOR INSULATION: All parts that might be damaged by the high meg ger voltages must be disconnected before testing. Isolate all Stator leads (Figure 3-2) and connect all of the Stator leads together. FOLLOW THE MEGGER MANUFACTURER’S INSTRUCTIONS CAREFULLY. Use a megger power setting of 1500 volts. Connect one megger test lead to the junction of all Stator leads, the other test lead to frame ground on the Stator can. Read the number of megohms on the meter.
Figure 3-2. – Stator Leads
To test the Rotor for insulation breakdown, proceed as follows: 1. Disconnect wires from the Rotor brushes or remove the brush holders with brushes.
MINIMUM INSULATION GENERATOR RATED VOLTS RESISTANCE = +1 (in “Megohms”) 1000
The MINIMUM acceptable megger reading for Stators may be calculated using the following formula: EXAMPLE: Generator is rated at 120 volts AC. Divide “120” by “1000” to obtain “0.12”. Then add “1” to obtain “1.12” megohms. Minimum Insulation resistance for a 120 VAC Stator Is 1.12 megohms. If the Stator insulation resistance is less than the cal culated minimum resistance, clean and dry the Stator. Then, repeat the test. If resistance is still low, replace the Stator. Use the Megger to test for shorts between isolated windings as outlined “Stator Insulation Resistance”. Also test between parallel windings. See “Test Between Parallel Windings” on this page.
TESTING ROTOR INSULATION: Apply a voltage of 1000 volts across the Rotor pos itive (+) slip ring (nearest the rotor bearing), and a clean frame ground (i.e. the Rotor Shaft). DO NOT EXCEED 1000 VOLTS AND DO NOT APPLY VOLTAGE LONGER THAN 1 SECOND. FOLLOW THE MEGGER MANUFACTURER’S INSTRUCTIONS CAREFULLY.
Figure 3-3. – Rotor Test Points
1.5 megohms
Stator

Measuring AC Voltage
Devices used to measure electrical properties are called meters. Meters are available that allow one to measure (a) AC voltage, (b) DC voltage, (c) AC frequency, and (d) resistance in ohms. The following apply: ❏ To measure AC voltage, use an AC voltmeter. ❏ To measure DC voltage, use a DC voltmeter. ❏ Use a frequency meter to measure AC frequency In
An accurate AC voltmeter or a VOM may be used to read the generator’s AC output voltage. The following apply: 1. Always read the generator’s AC output voltage only at the unit’s rated operating speed and AC frequency.
“Hertz” or “cycles per second”.. ❏ Use an ohmmeter to read circuit resistance, in
“ohms”.
A meter that will permit both voltage and resistance to be read is the “volt-ohm-milliammeter” or “VOM”. Some VOM’s are of the “analog” type (not shown). These meters display the value being measured by physically deflecting a needle across a graduated scale. The scale used must be interpreted by the user. “Digital” VOM’s (Figure 4-1) are also available and are generally very accurate. Digital meters display the measured values directly by converting the values to numbers. NOTE: Standard AC voltmeters react to the AVERAGE value of alternating current. When working with AC, the effective value is used. For that reason a different scale is used on an AC voltmeter. The scale is marked with the effective or “rms” value even though the meter actually reacts to the average value. That is why the AC voltmeter will give an incorrect reading if used to measure direct current (DC).
AND DANGEROUS VOLTAGES. CONTACT WITH HIGH VOLTAGE TERMINALS WILL RESULT IN DANGEROUS AND POSSIBLY LETHAL ELECTRICAL SHOCK.
A DC voltmeter or a VOM may be used to measure DC voltages. Always observe the following rules: 1. Always observe correct DC polarity.
a. Some VOM’s may be equipped with a polarity
switch. b. On meters that do not have a polarity switch,
DC polarity must be reversed by reversing the test leads. 2. Before reading a DC voltage, always set the meter to a higher voltage scale than the anticipat ed reading. If in doubt, start at the highest scale and adjust the scale downward until correct read ings are obtained.
a. The “current flow” theory assumes that direct
current flows from the positive (+) to the nega tive (-). b. The “electron flow” theory assumes that cur
rent flows from negative (-) to positive (+).
The generator’s AC output frequency is proportional to Rotor speed. Generators equipped with a 2-pole Rotor must operate at 3600 rpm to supply a frequency of 60 Hertz. Units with 4-pole Rotor must run at 1800 rpm to deliver 60 Hertz.
Figure 4-1. – Digital VOM

Correct engine and Rotor speed is maintained by a stepper motor governor. For models rated 60 Hertz, the governor is generally set to maintain a no-load fre quency of about 60 Hertz with a corresponding output voltage of about 124 volts AC line-to-neutral.
To read the current flow, in AMPERES, a clamp-on ammeter may be used. This type of meter indicates current flow through a conductor by measuring the strength of the magnetic field around that conductor. The meter consists essentially of a current trans former with a split core and a rectifier type instrument connected to the secondary. The primary of the cur rent transformer is the conductor through which the current to be measured flows. The split core allows the Instrument to be clamped around the conductor without disconnecting it. Current flowing through a conductor may be mea sured safely and easily. A line-splitter can be used to measure current in a cord without separating the conductors.
Figure 4-3. – A Line-Splitter
The volt-ohm-milliammeter may be used to measure the resistance in a circuit. Resistance values can be very valuable when testing coils or windings, such as the Stator and Rotor windings. When testing Stator windings, keep in mind that the resistance of these windings is very low. Some meters are not capable of reading such a low resistance and will simply read “continuity”. If proper procedures are used, the following condi tions can be detected using a VOM: ❏ A “short-to-ground” condition in any Stator or Rotor
winding. ❏ Shorting together of any two parallel Stator wind
ings. ❏ Shorting together of any two isolated Stator wind
ings. ❏ An open condition in any Stator or Rotor winding. Component testing may require a specific resistance value or a test for “infinity” or “continuity.” Infinity is an OPEN condition between two electrical points, which would read as no resistance on a VOM. Continuity is a closed condition between two electrical points, which would be indicated as very low resistance or “ZERO” on a VOM.
Figure 4-2. – Clamp-On Ammeter

OHM: The OHM is the unit of RESISTANCE. In every circuit there is a natural resistance or opposition to the flow of electrons. When an EMF is applied to a complete circuit, the electrons are forced to flow in a single direction rather than their free or orbiting pattern. The resistance of a conductor depends on (a) its physical makeup, (b) its cross-sectional area, (c) its length, and (d) its temperature. As the conductor’s tempera ture increases, its resistance increases in direct pro portion. One (1) ohm of resistance will permit one (1) ampere of current to flow when one (1) volt of electro motive force (EMF) is applied.
AMPERE: The rate of electron flow in a circuit is represented by the AMPERE. The ampere is the number of elec trons flowing past a given point at a given time. One AMPERE is equal to just slightly more than six thou sand million billion electrons per second. With alternating current (AC), the electrons flow first in one direction, then reverse and move in the oppo site direction. They will repeat this cycle at regular intervals. A wave diagram, called a “sine wave” shows that current goes from zero to maximum positive value, then reverses and goes from zero to maximum negative value. Two reversals of current flow is called a cycle. The number of cycles per second is called frequency and is usually stated in “Hertz”.
A definite and exact relationship exists between VOLTS, OHMS and AMPERES. The value of one can be calculated when the value of the other two are known. Ohm’s Law states that in any circuit the current will increase when voltage increases but resis tance remains the same, and current will decrease when resistance Increases and voltage remains the same.
VOLT: The VOLT is the unit used to measure electrical PRESSURE, or the difference in electrical potential that causes electrons to flow. Very few electrons will flow when voltage is weak. More electrons will flow as voltage becomes stronger. VOLTAGE may be consid ered to be a state of unbalance and current flow as an attempt to regain balance. One volt is the amount of EMF that will cause a current of 1 ampere to flow through 1 ohm of resistance.
(E)
AMPS
OHMS
Conductor of a Circuit
(R)
OHM - Unit measuring resistance
or opposition to flow
Figure 4-5.
If AMPERES is unknown while VOLTS and OHMS are known, use the following formula: AMPERES = VOLTS OHMS If VOLTS is unknown while AMPERES and OHMS are known, use the following formula:
AMPERE - Unit measuring rate of
current flow (number of electrons past a given point)
vOLT - Unit measuring force or
difference in potential causing current flow
VOLTS = AMPERES x OHMS If OHMS is unknown but VOLTS and AMPERES are known, use the following: OHMS = VOLTS AMPERES
Figure 4-4. – Electrical Units

CIRCUIT CONDITION – Rest:
Battery voltage is available to the Printed Circuit Board (PCB) from the vehicle BATTERY via the positive (RED) battery cable to the isolated positive (RED) terminal stud, located in the control panel. The power is supplied to Wire 13, a 7.5 amp FUSE (F1), the STARTER CONTACTOR RELAY (SCR) and Wire 15/Pin 4 on the PCB. However, PCB action is holding the circuits open, and no action can occur.
The engine DC control system includes all com ponents necessary for the operation of the engine. Operation includes rest, priming, cranking, starting, running and shutdown. The system is shown sche matically.
Printed Circuit Board action (only) allows voltage to be supplied to Wires 17 and 18 for start and stop actions on the START-STOP SWITCH (SW1) and remote panel connector.
ACTUATOR GOVERNOR
SCR
CONTROL
PRINTED CIRCUIT BOARD
0 13 16 56
IM1
FS
SP1
J1
1 2 3 4 5 6 7 8 10 9 11 13 14
18 15 17 712 86 90 14 85 56 0 18A 4
BLK RED 18A 0 86 0 85
LED
START PRIME STOP
CS
SW1
CH
SC 0
RED
REMOTE PANEL CONNECTOR
SC
F1
BATTERY +
A 0
SM
H
B 18
G
F
D E
BLACK
WHITE
GREEN
11S
11S
11S
22S
22S
22S
CB1
VOLTAGE
CUSTOMER
CB2
REGULATOR
AC CONNECTION
NEUTRAL CONNECTION
11S
22S 22
6 2 4 0 44
GREEN WHITE
FIELD BLACK RED
POWER WINDINGS
DPE WINDING
BA
LEGEND
BA - BRUSH ASSEMBLY CB 1 / CB 2 - SEE CHART
IMS - IGNITION MODULE STUD IM2 - IGNITION MODULE, CYL. 2
= AC VOLTAGE
CH - CHOKE HEATER CS - CHOKE SOLENOID
LED - ALARM INDICATOR LOP - LOW OIL PRESSURE SWITCH
= GROUND
FS - FUEL SOLENOID FP - FUEL PUMP F1 - FUSE, 7.5A
= DC CONTROL VOLTAGE (PCB)
= GROUND CONTROL (PCB)
SCR - STARTER CONTACTOR RELAY SM - STARTER MOTOR
GRD1 - CONTROL PANEL GROUND GRD2 - UNIT GROUND STUD
SP2 - SPARK PLUG, CYL. 2 SP1 - SPARK PLUG, CYL. 1
= FIELD BOOST
HTO - HIGH OIL TEMPERATURE SWITCH IM1 - IGNITION MODULE, CYL. 1
= VOLTAGE REGULATOR DC OUTPUT
TB - TERMINAL BLOCK, 4 TAB
+

When the STARTER CONTACTOR RELAY (SCR) closes, battery voltage is also delivered to PCB Pin 13 . This voltage is reduced for use as field boost and is output from PCB Pin 13 to the rotor. While cranking, the CHOKE SOLENOID (CS) is energized by grounding Wire 90 cyclically by PCB action (two seconds on, two seconds off). Also while cranking, PCB action energizes Pin 5, and delivers battery voltage to the Wire 14 circuit. This energizes the FUEL PUMP (FP) via a Red wire, FUEL SOLENOID (FS) via Wire 241 and CHOKE HEATER (CH) via Wire 14. Battery voltage is also delivered to an optional light or hour meter in the Remote Panel, if equipped. PCB action now holds open Wire 18A to common ground, and the Magneto will induce a spark during cranking.
When the START-STOP SWITCH (SW1) or REMOTE PANEL START SWITCH is momentarily held in the “START” position and then released, Wire 17 from the Printed Circuit Board (PCB ) is connected to frame Ground. PCB action will then deliver battery voltage to a STARTER CONTACTOR RELAY (SCR) via Wire 56, and to an auto matic CHOKE SOLENOID (CS) via Wire 14.
When battery voltage energizes the STARTER CONTACTOR RELAY (SCR), it’s contacts close and battery output is delivered to the STARTER CONTACTOR (SC) via Wire 16. When the STARTER CONTACTOR (SC) energizes, it’s contacts close, and battery out put is delivered to the STARTER MOTOR (SM) via Wire 16. The STARTER MOTOR energizes and the engine cranks.
ACTUATOR GOVERNOR
SCR
CONTROL
PRINTED CIRCUIT BOARD
0 13 16 56
IM1
FS
SP1
J1
1 2 3 4 5 6 7 8 10 9 11 13 14
SP2
18 15 17 712 86 90 14 85 56 0 18A 4
LED
START PRIME STOP
CS
SW1
CH
SC 0
RED
SC
REMOTE PANEL CONNECTOR
F1
BATTERY +
A 0
H
SM
G
B 18
F
D E
BLACK
WHITE
GREEN
11S
11S
11S
22S
22S
22S
CB1
CUSTOMER
CB2
REGULATOR
VOLTAGE
AC CONNECTION
NEUTRAL CONNECTION
BY CUSTOMER
11S
22S 22
6 2 4 0 44
FIELD BLACK RED
POWER WINDINGS
DPE WINDING
BA
LEGEND
BA - BRUSH ASSEMBLY CB 1 / CB 2 - SEE CHART
IMS - IGNITION MODULE STUD IM2 - IGNITION MODULE, CYL. 2
= AC VOLTAGE
CH - CHOKE HEATER CS - CHOKE SOLENOID
LED - ALARM INDICATOR LOP - LOW OIL PRESSURE SWITCH
= GROUND
FS - FUEL SOLENOID FP - FUEL PUMP F1 - FUSE, 7.5A
SCR - STARTER CONTACTOR RELAY SM - STARTER MOTOR
= GROUND CONTROL (PCB)
GRD1 - CONTROL PANEL GROUND GRD2 - UNIT GROUND STUD
SP2 - SPARK PLUG, CYL. 2 SP1 - SPARK PLUG, CYL. 1
= FIELD BOOST
HTO - HIGH OIL TEMPERATURE SWITCH IM1 - IGNITION MODULE, CYL. 1
= VOLTAGE REGULATOR DC OUTPUT
TB - TERMINAL BLOCK, 4 TAB
+

Printed Circuit Board action terminates DC output to the STARTER CONTACTOR RELAY (SCR), which then de-energizes to end crank ing. PCB action terminates DC output to the CHOKE SOLENOID (CS).
With the FUEL PUMP (FP) and FUEL SOLENOID (FS) operating and ignition occurring, the engine should start, and the START- STOP SWITCH (SW1) is released. This voltage is delivered to the PCB via Wire 18A to prevent STARTER MOTOR engagement above a certain rpm.
The choke will go to a position determined by the CHOKE HEATER (CH).
The LOW OIL PRESSURE SWITCH (LOP) is normally closed. After startup, engine oil pressure will open the LOP.
ACTUATOR GOVERNOR
SCR
CONTROL
PRINTED CIRCUIT BOARD
0 13 16 56
IM1
FS
SP1
J1
1 2 3 4 5 6 7 8 10 9 11 13 14
18 15 17 712 86 90 14 85 56 0 18A 4
BLK RED 18A 0 86 0 85
LED
START PRIME STOP
CS
SW1
CH
SC 0
RED
REMOTE PANEL CONNECTOR
SC
F1
BATTERY +
A 0
SM
H
B 18
G
F
D E
BLACK
WHITE
GREEN
11S
11S
11S
22S
22S
22S
CB1
CB2
VOLTAGE
CUSTOMER
REGULATOR
AC CONNECTION
NEUTRAL CONNECTION
11S
22S 22
6 2 4 0 44
GREEN WHITE
FIELD BLACK RED
POWER WINDINGS
DPE WINDING
BA
LEGEND
BA - BRUSH ASSEMBLY CB 1 / CB 2 - SEE CHART
IMS - IGNITION MODULE STUD IM2 - IGNITION MODULE, CYL. 2
= AC VOLTAGE
CH - CHOKE HEATER CS - CHOKE SOLENOID
LED - ALARM INDICATOR LOP - LOW OIL PRESSURE SWITCH
= GROUND
FS - FUEL SOLENOID FP - FUEL PUMP F1 - FUSE, 7.5A
= DC CONTROL VOLTAGE (PCB)
= GROUND CONTROL (PCB)
SCR - STARTER CONTACTOR RELAY SM - STARTER MOTOR
GRD1 - CONTROL PANEL GROUND GRD2 - UNIT GROUND STUD
SP2 - SPARK PLUG, CYL. 2 SP1 - SPARK PLUG, CYL. 1
= FIELD BOOST
HTO - HIGH OIL TEMPERATURE SWITCH IM1 - IGNITION MODULE, CYL. 1
= VOLTAGE REGULATOR DC OUTPUT
TB - TERMINAL BLOCK, 4 TAB
+

Should engine oil temperature exceed a preset value, the switch con tacts will close. Wire 85 from the Printed Circuit Board will connect to frame ground. PCB action will then initiate a shutdown and will cause the red led light on SW1 to flash 6 times then repeat.
Setting the START-STOP SWITCH (SW1) or the REMOTE PANEL START-STOP SWITCH to its “STOP” position connects the Wire 18 circuit to frame ground. Printed Circuit Board action then closes the circuit to Wire 18A, grounding the ignition magneto. PCB action de-energizes DC output to J1 plug to the FUEL PUMP (FP), FUEL SOLENOID (FS) and CHOKE HEATER (CH) are de-energized by the loss of DC to Wire 14. Ignition and fuel flow are terminated, and the engine shuts down.
Should engine oil pressure drop below a safe pre-set value, the LOP switch contacts will close. On contact closure, Wire 86 will be connect ed to frame ground and PCB action will initiate an engine shutdown and will cause the red led light on SW1 to flash 5 times then repeat.
The PCB has a built-in time delay for the Wire 85 fault shutdown. At STARTUP ONLY the circuit board will wait approximately 6 seconds before looking at the Wire 85 fault shutdowns. Once running, after the 6 second time delay, grounding Wire 85 through either switch will cause an immediate shutdown.
The engine mounts a HIGH OIL TEMPERATURE SWITCH (HTO) and a LOW OIL PRESSURE SWITCH (LOP).
ACTUATOR GOVERNOR
2 Flashes = Low Battery
3 Flashes = Overcrank
CONTROL
0 13 16 56
4 Flashes = Overspeed
FS
SP1
J1
5 Flashes = Low Oil Pressure
1 2 3 4 5 6 7 8 10 9 11 13 14
6 Flashes = High Oil Temperature
18 15 17 712 86 90 14 85 56 0 18A 4
SP2
LED
CS
START PRIME STOP
SW1
CH
SC 0
RED
REMOTE PANEL CONNECTOR
F1
BATTERY +
SC
H
A 0
SM
B 18
G
F
D E
BLACK
WHITE
GREEN
11S
11S
11S
22S
22S
22S
CB1
CB2
VOLTAGE
CUSTOMER
REGULATOR
NEUTRAL CONNECTION
AC CONNECTION
BY CUSTOMER
11S
22S 22
6 2 4 0 44
FIELD BLACK RED
POWER WINDINGS
DPE WINDING
BA
LEGEND
= 12 VOLTS DC
= AC VOLTAGE
BA - BRUSH ASSEMBLY CB 1 / CB 2 - SEE CHART
IMS - IGNITION MODULE STUD IM2 - IGNITION MODULE, CYL. 2
LED - ALARM INDICATOR LOP - LOW OIL PRESSURE SWITCH
= GROUND
FS - FUEL SOLENOID FP - FUEL PUMP F1 - FUSE, 7.5A
SCR - STARTER CONTACTOR RELAY SM - STARTER MOTOR
= GROUND CONTROL (PCB)
GRD1 - CONTROL PANEL GROUND GRD2 - UNIT GROUND STUD
SP2 - SPARK PLUG, CYL. 2 SP1 - SPARK PLUG, CYL. 1
= FIELD BOOST
HTO - HIGH OIL TEMPERATURE SWITCH IM1 - IGNITION MODULE, CYL. 1
= VOLTAGE REGULATOR DC OUTPUT
TB - TERMINAL BLOCK, 4 TAB
+

DIP SWITCH
J1 CONNECTOR
GENERAL: The Printed Circuit Board (PCB) mounted inside the generator control panel is responsible for crank ing, startup, running and shutdown operations. The board interconnects with other components of the DC control system to turn them on and off at the proper times. It is powered by fused 12 VDC power from the unit battery.
CIRCUIT BOARD CONNECTIONS: The circuit board mounts a 14-pin receptacle (J1) and a six pin terminal (J2, see Figure 5-2). Figure 5-1 shows the 14-pin receptacle (J1), the associated wires and the function(s) of each pin and wire.
PIN WIRE FUNCTION
1 N/A NOT USED
2 18 To Start-Stop switch. When grounded by setting Start-Stop switch to “STOP” engine shuts down
DIP SWITCHES ARE FACTORY SET IN THE “OFF” (DOWN) POSITION
3 17 To Start-Stop switch. When grounded by setting the Start-Stop switch to “START” the engine start cycle begins.
Figure 5-2. – Printed Circuit Board
4 15 Delivers fused 12 VDC to PCB
5 14 PCB control. During cranking and running, supplies 12 VDC to fuel pump, choke solenoid, choke heater, fuel solenoid
6 86 Low Oil Pressure switch / Safety shut down
7 85 High Temperature switch / Safety shut down
8 712 PCB control/Alarm led
9 56 Delivers 12 VDC to Starter Contactor (SC) (cranking only)
10 90 To Choke Solenoid. When grounded by the PCB the choke operates at two sec onds ON , two second OFF intervals (cranking only)
Figure 5-3. – J1 Connector, Harness End
11 0 Common Ground
12 N/A Not Used
13 4 Field Boost DC to the Voltage Regulator and to the Rotor Winding
RECOMMENDED BATTERY: When anticipated ambient temperatures will be con sistently above 32° F (0° C), use a 12 volts automotive type storage battery rated 70 amp-hours and capable of delivering at least 400 cold cranking amperes. If ambient temperatures will be below 32° F (0° C), use a 12 volt battery rated 95 amp-hours and having a cold cranking capacity of 400 amperes.
14 18A Ground to Magneto for Shutdown Figure 5-1. – Receptacle J1
CIRCUIT BOARD Dip Switches: The circuit board mounts a pair of dip switches which are factory set in the “OFF” (down) position. These dip switches should remain in the factory setting.
BATTERY CABLES: Use of battery cables that are too long or too small in diameter will result in excessive voltage drop. For best

cold weather starting, voltage drop between the bat tery and starter should not exceed 0.12 volt per 100 amperes of cranking current. Select the battery cables based on total cable length and prevailing ambient temperature. Generally, the longer the cable and the colder the weather, the larger the required cable diameter. The following chart applies:
acid solution that can cause severe burns. For that reason, the following precautions must be observed: ❏ The area in which the battery is being charged must
be well ventilated. When charging a battery, an explosive gas mixture forms in each cell. ❏ Do not smoke or break a live circuit near the top of
the battery. Sparking could cause an explosion. ❏ Avoid spillage of battery fluid. If spillage occurs, flush
the affected area with clear water immediately. ❏ Wear eye protection when handling a battery.
0-10 No. 2
11-15 No. 0
16-20 No. 000
This panel-mounted Fuse protects the DC control circuit against overload and possible damage. If the Fuse has melted open due to an overload, neither the priming function nor the cranking function will be available.
EFFECTS OF TEMPERATURE: Battery efficiency is greatly reduced by a decreased electrolyte temperature. Such low temperatures have a decided numbing effect on the electrochemical action. Under high discharge rates (such as cranking), battery voltage will drop to much lower values in cold temperatures than in warmer temperatures. The freez ing point of battery electrolyte fluid is affected by the state of charge of the electrolyte as indicated below:
1.220 -35° F. (-37° C.)
1.200 --20° F. (-29° C.)
1.160 0° F. (-18° C.)
ADDING WATER: Water is lost from a battery as a result of charging and discharging and must be replaced. If the water is not replaced and the plates become exposed, they may become permanently sulfated. In addition, the plates cannot take full part in the battery action unless they are completely immersed in electrolyte. Add only DISTILLED WATER to the battery. DO NOT USE TAP WATER. NOTE: Water cannot be added to some “mainte nance-free” batteries.
Figure 5-4. – Typical Fuse
The Start-Stop Switch allows the operator to control cranking, startup and shutdown. The top half of this momentary switch is pushed and held for one (1) sec ond and then released. An indicator light on the switch begins to flash. The fuel pump engages automatically for a three (3) to five (5) second delay before the start er motor cranks the engine for 16 seconds or until the engine starts. If the engine does not start, the starter will cool for seven (7) seconds and crank the engine again for 16 seconds. If the engine does not start, the starter will cool for seven (7) seconds before cranking for seven (7) seconds to a maximum cycle total of 90 seconds. Once started, the light on the switch stays on continuously. If the generator does not start at the end of the start sequence, a fault code will flash on the switch (see Diagnostics). The switch center position is the RUN position. A running engine is stopped by momentarily pressing the bottom half of the switch to kill the ignition. The following wires connect to the Start-Stop Switch: 1. Wire No. 17 from the Printed Circuit Board. This Is the CRANK and START circuit. When the Switch is set to “START”, Wire 17 is connected to frame ground via Wire 0.
CHECKING BATTERY STATE OF CHARGE: Use an automotive type battery hydrometer to test the battery state of charge. Follow the hydrometer manufacturer’s instructions carefully. Generally, a bat tery may be considered fully charged when the spe cific gravity of its electrolyte is 1.260. If the hydrometer used does not have a “Percentage of Charge” scale, compare the readings obtained with the following:
1.260 100%
1.230 75%
1.200 50%
1.170 25%
CHARGING A BATTERY: Use an automotive type battery charger to recharge a battery. Battery fluid is an extremely corrosive, sulfuric

a. With Wire 17 grounded, a Crank Relay on the
Wire 16 will supply battery power to the starter contactor and to the Printed Circuit Board for field flash when the starter contactor relay is energized. Attached to the starter contactor relay coil is Wire 56 (positive supply during cranking) and Wire 0 (ground). When the Start-Stop switch is set to “START”, the circuit board delivers battery voltage to the Starter Contactor Relay via Wire 56. The Starter Contactor Relay energizes, its contacts close and the Starter Contactor is energized via wire 16. Its contacts close and battery voltage is available to the starter motor, and the engine cranks.
circuit board energizes and battery voltage is delivered to the Starter Contactor Relay via Wire 56. The Starter Contactor Relay energizes, its contacts close and the Starter Contactor is energized via wire 16. Its con tacts close and the engine cranks. b. With Wire 17 grounded, a Run Relay on the
circuit board energizes and battery voltage is delivered to the Wire 14 circuit. Battery voltage is delivered to the Fuel Pump, Fuel Solenoid, Choke Heater and the Remote Harness. 2. Wire 18 from the Printed Circuit Board. This Is the ENGINE STOP circuit. When the Start-Stop Switch is set to “STOP”, Wire 18 is connected to frame ground via Wire No. 0. Circuit board action then opens the circuit to Wire 14, and grounds Wire 18A. Fuel flow to the carburetor and igni tion are terminated.
Figure 5-6. – Starter Motor
COM NO
START PRIME STOP
SW1
Figure 5-5. – Start-Stop Switch
Figure 5-7. – Starter Contactor Relay
& Starter Motor
The positive (+) battery cable attaches to the large lug on the starter contactor. Wire 13 then attach es to one side of the starter contactor relay contact, from this point Wire 13 attaches to the fuse F1 to supply battery voltage to the DC control system. The opposite side of the starter contactor relay con tact is connected to Wire 16.

The “Flow Charts” in this section may be used in conjunction with the “Diagnostic Tests” of Section 7. Numbered tests in the Flow Charts correspond to identically numbered tests of Section 7.
Problems 1 through 4 apply to the AC generator only. Beginning with Problem 5, the engine DC control sys tem is dealt with.
TEST 1 – CHECK NO-LOAD VOLTAGE
& FREQUENCY
VOLTAGE & FREQUENCY BOTH
FREQUENCY GOOD –
FREQUENCY GOOD –
NO-LOAD VOLTAGE
VOLTAGE HIGH
ZERO OR RESIDUAL
& FREQUENCY
HIGH OR LOW
OR VOLTAGE LOW
VOLTAGE
GOOD
GO TO PROBLEM 1 GO TO VOLTAGE REGULATOR ADUST-
Problem 1 – Voltage & Frequency Are Both High or Low
TEST 2 – CHECK STEPPER MOTOR
FREQUENCY GOOD.
LOW OR RESIDUAL
CONTROL
AC VOLTAGE
NO-LOAD FREQUENCY & VOLTAGE GOOD BUT THEY
GO TO PROBLEM 4
DROOP TO MUCH WHEN
LOAD IS APPLIED
GO TO VOLTAGE
FREQUENCY IS GOOD BUT
REGULATOR ADJUSTMENT,
NO-LOAD VOLTAGE IS HIGH OR VOLTAGE IS LOW
MENT, PAGE xx

Problem 2 – Generator Produces Zero Voltage or Residual Voltage (5-12VAC)
MAIN CIRCUIT
GOOD
BREAKER
RESET TO
“ON” OR REPLACE
IF BAD
TEST 4 – PERFORM FIXED EXCITATION TEST
/ ROTOR AMP DRAW D A
C B
TEST 8 – CHECK
BAD
BRUSH LEADS
GOOD
TEST 6 – TEST
TEST 5 – CHECK
STATOR DPE
BAD
FIELD BOOST
TEST 9 –
WINDING
CHECK BRUSHES &
BAD
REPAIR
GOOD
SLIP RINGS
BAD
OR REPLACE
REPAIR OR
REPLACE THEN RE-TEST
REPAIR
INSULATION RESISTANCE TEST, PAGE 13
GOOD
OR REPLACE
BAD GOOD
REPLACE VOLTAGE REGULATOR
TEST 10 – CHECK ROTOR
BAD
ASSEMBLY
TEST 7 – CHECK SENSING LEADS / POWER WINDINGS
GOOD
REPAIR
GOOD
OR REPLACE
TEST ROTOR
INSULATION RESISTANCE TEST, PAGE 13
INSULATION,
BAD
BAD

Problem 2 – Generator Produces Zero Voltage or ResidualVoltage (5-12VAC)
TEST 4 – PERFORM FIXED EXCITATION TEST
E
/ ROTOR AMP DRAW
G
CHECK VOM FUSES –
REPLACE FUSES
VERIFY AMP METER
– THEN RE-TEST
FUNCTIONS
F
TEST 10 – CHECK ROTOR
(PERFORM BOTH TEST 7 & 8)
ASSEMBLY TEST 7 – CHECK SENSING LEADS / POWER WINDINGS
TEST 6 – TEST
REPAIR
STATOR DPE
EITHER OR
OR REPLACE REPAIR
BOTH BAD
WINDING
OR REPLACE
GOOD GOOD
INSULATION RESISTANCE TEST, PAGE 13 TEST ROTOR
BAD BAD
INSULATION,
Problem 3 – Excessive Voltage/Frequency Droop When Load is Applied
(Underspeed Warning – 4 Flashes on SW1 LED)
TEST 13 – CHECK
TEST 12 – CHECK LOAD VOLTAGE &
AMPERAGE BAD
LOAD WATTS &
NOT OVERLOADED
FREQUENCY
GOOD
OVERLOADED REDUCE LOAD
END TEST
GO TO PROBLEM 8 TEST 2 – CHECK STEPPER MOTOR
GOOD
CONTROL
BOARD

Problem 4 – Engine Overspeed Warning Code Flashing on SW1 LEd (4 Flashes)
TEST 2 – CHECk STEPPER MOTOR
TEST 31 – CHECk &
GOOD GOOD GOOD CHECk WIRE 18A
CONTROL
BAD BAD
BAD
REPLACE STEPPER MOTOR
REPAIR OR
REPLACE PRINTED CIRCUIT
REPLACE
REPLACE
BOARD
Proble 5 – Priming Function Does Not Work (Gasoline Models)
TEST 14 – TRY
ENGINE CRANKS NORMALLY
STILL WON’T PRIME
TEST 20 – CHECK
CRANKING THE ENGINE
START-STOP SWITCH (SW1)
WON’T CRANK
BAD
REPLACE BAD SWITCH
GOOD
GO TO PROBLEM 6
TEST 15 – CHECK
REPLACE FUEL PUMP
FUEL PUMP OPERATION
BAD
IF DEFECTIVE
REPLACE PRINTED CIRCUIT
GOOD
BOARD
ADjUST IGNITION · ADjUST, REPAIR OR

Problem 6 - Engine Will Not Crank
TEST 16 – CHECk 7.5 AMP FUSE
TEST 17 – CHECk BATTERY & CABLES
(CHECk SW1 LED FOR LOW BATTERY
FUSE BAD
RECHARGE OR REPLACE BATTERY
– CLEAN, REPAIR OR REPLACE
BAD
BAD CABLE(S)
REPLACE FUSE
FUSE BLOWS
GO TO PROBLEM 10
GOOD
TEST 18 – CHECk
POWER SUPPLY
GOOD GOOD
TO PRINTED CIRCUIT BOARD
SWITCH
REPLACE DEFECTIVE
BAD
BAD
SWITCH
CHECk WIRING AND WIRE CONNECTIONS. REPAIR, RECONNECT
OR REPLACE BAD WIRES AS REqUIRED
TEST 21 – CHECk
TEST 22 – CHECk
POWER SUPPLY
GOOD
TO WIRE 56
RELAY
BAD
REPLACE BAD
REPLACE PRINTED CIRCUIT
STARTER CONTACTOR
BAD
RELAY
BOARD
TEST 23 – CHECk
STARTER CONTACTOR
TEST 24 – CHECk STARTER MOTOR
GOOD
REPLACE STARTER
CONTACTOR
REPLACE STARTER MOTOR IF DEFECTIVE
CHECk FOR MECHANICAL BINDING
ROTOR
CHECk START-STOP

(Overcrank Warning Code on SW1 LED – 3 Flashes)
TEST 25 – CHECK FUEL
TEST 26 – CHECK
TEST 20 – CHECK
O.K.
GOOD
START-STOP
SUPPLY
SUPPLY
SWITCH
REPLACE PRINTED CIRCUIT
BAD BAD
LOW FUEL
BOARD
REPLACE
BAD SWITCH
REPLENISH FUEL SUPPLY
GOOD
TEST 15 – CHECK
TEST 28 – CHECK FUEL
FUEL PUMP OPERATION
GOOD GOOD
SOLENOID
BAD
REPLACE SOLENOID
BAD
TEST 29 –
CHECK IGNITION
REPLACE
FUEL PUMP
SPARK TEST 30 – CHECK SPARK
GOOD GOOD
PLUGS
WEAK SPARK / NO SPARK /
INTERMITTENT SPARK
TEST 31 – CHECK
AND ADJUST
IGNITION MAGNETOS
CLEAN AND REGAP OR REPLACE SPARK PLUG
BAD
REPLACE MAGNETOS
TEST 33 – CHECK
TEST 34 – CHECK
CARBURETION
GOOD
CHOKE SOLENOID
GOOD
ADJUST OR REPAIR ADJUST OR REPAIR
BAD
TEST 35 – CHECK ENGINE / CYLINDER
CHECK FLYWHEEL KEY
TEST 32 – CHECK
VALVE ADJUSTMENT
NO START
LEAK DOWN TEST / COMPRESSION TEST
GOOD
– SEE TEST 31
ON PAGE 57
BAD
BAD
ADJUST VALVES
REPAIR OR REPLACE
AS NECESSARY

(Overcrank Warning Code on SW1 LED – 3 Flashes)
TEST 25 – CHECK FUEL
TEST 26 – CHECK
TEST 20 – CHECK
O.K.
GOOD
START-STOP
SUPPLY
SUPPLY
SWITCH
REPLACE PRINTED CIRCUIT
LOW LP PRESSURE
BAD BAD
BOARD
REPLACE
BAD SWITCH
REPLENISH FUEL SUPPLY
GOOD
TEST 41 – CHECK
LPG FUEL SOLENOID
GOOD
BAD
TEST 29 –
CHECK IGNITION
REPAIR OR
REPLACE
SPARK
TEST 30 – CHECK SPARK
GOOD GOOD
PLUG
WEAK SPARK / NO SPARK /
INTERMITTENT SPARK
CLEAN AND REGAP OR REPLACE SPARK PLUG
TEST 31 – CHECK
AND ADJUST
IGNITION MAGNETOS
REPLACE MAGNETOS
BAD
TEST 35 – CHECK ENGINE / CYLINDER
CHECK FLYWHEEL KEY
TEST 32 – CHECK
VALVE ADJUSTMENT
NO START
GOOD
LEAK DOWN TEST / COMPRESSION TEST
– SEE TEST 31
ON PAGE 57
BAD
BAD
ADJUST VALVES
REPAIR OR REPLACE
AS NECESSARY

TEST 25 –
TEST 29 –
TEST 30 –
CHECK
CHECK IGNITION
CHECK
FUEL SUPPLY
GOOD
GOOD GOOD
SPARK PLUGS
SPARK
BAD
LOW FUEL ENGINE MISS IS APPARENT
CLEAN AND REGAP OR REPLACE SPARK PLUG
REPLENISH
TEST 31 – CHECK
FUEL SUPPLY
AND ADJUST
IGNITION MAGNETOS
BAD
REPLACE MAGNETOS
TEST 33 – CHECK
TEST 34 – CHECK
CARBURETION
GOOD
CHOKE SOLENOID
GOOD
ENGINE RUNS O.K. NOW
ADJUST, REPAIR OR
BAD
REPLACE AS NECESSARY
STOP TESTS
REPAIR OR REPLACE
BAD
TEST 40 – TEST CHOKE HEATER
GOOD
CHECK FLYWHEEL KEY
TEST 35 – CHECK ENGINE / CYLINDER
TEST 32 – CHECK
VALVE ADJUSTMENT
GOOD GOOD
– SEE TEST 31
LEAK DOWN TEST / COMPRESSION TEST
ON PAGE 57
BAD
BAD
REPAIR OR REPLACE
ADJUST VALVES
AS NECESSARY

TEST 29 –
TEST 25 –
TEST 30 –
CHECK
CHECK IGNITION
CHECK
FUEL SUPPLY
GOOD
GOOD GOOD
SPARK
SPARK PLUGS
BAD
LOW FUEL ENGINE MISS IS APPARENT
CLEAN AND REGAP OR REPLACE SPARK PLUG
REPLENISH
TEST 31 – CHECK
FUEL SUPPLY
AND ADJUST
IGNITION MAGNETOS
BAD
REPLACE MAGNETOS
CHECK FLYWHEEL KEY
TEST 35 – CHECK ENGINE / CYLINDER
TEST 32 – CHECK
VALVE ADJUSTMENT
GOOD GOOD
LEAK DOWN TEST / COMPRESSION TEST
– SEE TEST 31
ON PAGE 57
BAD
BAD
GOOD
REPAIR OR REPLACE
ADJUST VALVES
AS NECESSARY
CHECK FUEL REGULATOR AND
CARBURETOR

Problem 9 – High Oil Temperature Fault (6 Flashes)
or Low Oil Pressure Fault (5 Flashes)
TEST 25 – CHECK FUEL
CHECK ENGINE OIL
GOOD
5 FLASHES ON SW1 LED
SUPPLY
LEVEL
NO FUEL
OIL LEVEL LOW
GOOD
REPLENISH FUEL
REPLENISH OIL
TEST 36 – CHECK
TEST 37 – CHECK
REPLACE PRINTED CIRCUIT
OIL PRESSURE
GOOD GOOD
WIRE 86 FOR
SWITCH
CONTINUITY
BOARD
BAD
BAD
REPLACE SWITCH
REPAIR OR REPLACE
HIGH OIL TEMPERATURE
CHECK ENGINE OIL
TEST 38 – CHECK OIL TEMPERATURE
OIL LEVEL O.K.
LEVEL
SWITCH
OIL LEVEL LOW
BAD
GOOD
REPLENISH OIL
REPLACE SWITCH
TEST 39 – CHECK
REPLACE PRINTED CIRCUIT
WIRE 85 FOR
GOOD
CONTINUITY
BOARD
BAD
REPAIR OR REPLACE

Problem 10 – 7.5A (F1) Fuse Blowing
INSTALL NEW 7.5 AMP FUSE
FUSE BLOWS UPON
HOLDER IS NOT
PASS
INSTALLATION
GROUNDED
FAIL
REPLACE HOLDER
REMOVE WIRE 15 FROM JI HARNESS
CONNECTOR. DOES FUSE BLOW?
REPLACE PRINTED CIRCUIT
NOTE A: Disconnect harness from engine controller circuit board. Gently bend red tabs outward and remove red plastic pin guide. Using a small flathead screwdriver, slide black retainer tabs out away from Wire 15 pin (orange). Gently push pin out of harness and pull wire out from back of plug, noting it’s location for reinstallation later. Replace red pin guide and plug J1 harness back into engine controller circuit board. Replace fuse. If fuse does not blow, replace engine controller circuit board. If fuse still blows, continue to next section of Problem 10 flow chart.
NO
BOARD
YES
CHECK WIRE 15
FOR SHORT TO
GROUND
FUSE IS GOOD BUT BLOWS WHEN START-
CHECK REMOTE HARNESS WIRE 15
STOP SWITCH IS
FOR SHORT TO
PRESSED
GROUND
PERFORM RESISTANCE TESTS ON FUEL PUMP, FUEL SOLENOID, CHOKE HEATER AND REMOTE HARNESS WIRE 14 (SEE * BELOW). ALSO CHECK WIRE 14 TO EACH COMPONENT FOR SHORT TO GROUND.
YES
FROM ENGINE CONTROLLER CIRCUIT BOARD AND
CHECK WIRE 14 FOR SHORT TO GROUND. IS CONTINUITY PRESENT?
* CHECK FOR CONTINUITY TO FRAME GROUND. CONNECT ONE TEST LEAD TO THE POSITIVE WIRE FOR EACH COMPONENT. CONNECT THE OTHER TEST LEAD TO FRAME GROUND. RESISTANCE SHOULD BE MEASURED. IF CONTINUITY “0” IS MEASURED TO GROUND, THAT COMPONENT OR WIRE IS SHORTED.
ALSO, REFER TO THE INDIVIDUAL TESTS FOR EACH COMPONENT IN SECTION 7, UNDER “PROCEDURE – SHORT TO GROUND”.
REPLACE COMPONENT OR WIRE
STARTER CONTACTOR
CHECK WIRE 56
RELAY PIN LOCATION J1-1 TEST TO GROUND
FAIL
FOR SHORT TO
CHECK CHOKE SOLENOID AND
GROUND
REPAIR OR REPLACE COMPONENT OR WIRE
STARTER CONTACTOR
RELAY
CHOKE SOLENOID PIN LOCATION J1-2
CHECK WIRE 90
FAIL
FOR SHORT TO
TEST TO GROUND
GROUND

The “Diagnostic Tests” in this chapter may be per formed in conjunction with the “Flow Charts” of Section 6. Test numbers in this chapter correspond to the numbered tests in the “Flow Charts”. Tests 1 through 13 are procedures involving problems with the generator’s AC output voltage and frequency (Problems 1 through 3 in the “Flow Charts”). Tests 14 through 41 are procedures involving prob lems with engine operation (Problems 3 through 10 in the “Troubleshooting Flow Charts”). You may wish to read Section 4, “Measuring Electricity”. NOTE: Test procedures in this Manual are not nec essarily the only acceptable methods for diagnos ing the condition of components and circuits. All possible methods that might be used for system diagnosis have not been evaluated. If you use any diagnostic method other than the method presented in this Manual, you must ensure that neither your safety nor the product’s safety will be endangered by the procedure or method you have selected.
*
Caution! Do not stand in front of carburetor
when checking the stepper motor movement due to possible backfire from the carburetor.
PROCEDURE: 1. Remove air cleaner cover to access stepper motor.
Frequency
DISCUSSION: The first step in analyzing any problem with the AC generator is to determine the unit’s AC output volt age and frequency. Once that has been done, you will know how to proceed with specific diagnostic tests.
a. Press the Start-Stop switch (SW1) to “START”
and watch for stepper motor movement. It should move to the wide open (down) position during cranking. Once the unit starts the stepper motor should move the throttle to a position to maintain 60.0-60.5 Hertz.
PROCEDURE: 1. Set a volt-ohm-milliammeter (VOM) to read AC voltage. Connect the meter test leads across cus tomer connection leads T1 (Red) and T2 (White).
ARM
OPEN
RESULTS: For units rated 60 Hertz, no-load voltage and fre quency should be approximately 122-126 VAC and 60.0-60.5 Hertz respectively. 1. If AC voltage and frequency are BOTH corre spondingly high or low, go to Test 2.
LINKAGE
STEPPER
MOTOR
Figure 7-1. Throttle Position

trol panel cover. Verify the six pin connector (J2) on the Printed Circuit Board is seated properly, remove the connector and then replace it and test again. Verify the dip switches are correctly set.
DISCUSSION: The fixed excitation test consists of applying bat tery voltage (12 VDC) to the Rotor windings. This allows that portion of the excitation circuit between the Voltage Regulator and the Rotor (including the Rotor itself) to be checked as a possible cause of the problem. When battery voltage is applied to the Rotor, the resulting magnetic field around the Rotor should induce a Stator power winding voltage equal to about one-half the unit’s rated output voltage.
BROWN
RED TEST LEAD
YELLOW
BLACK TEST LEAD
VOLTAGE REGULATOR
ORANGE
RED
EMPTY
Figure 7-2. Six Pin J2 Connector Wire Colors
22S
11S
a. Connect one meter lead to Red, connect the
remaining test lead to Orange, approximately 10 ohms should be measured. b. Connect one meter lead to Red, connect the
WIRES 4 REMOVED FROM VOLTAGE REGULATOR
remaining test lead to Yellow, approximately 10 ohms should be measured. c. Connect one meter lead to Red, connect the
Figure 7-3. – Fixed Excitation Test, Step A
remaining test lead to Brown, approximately 10 ohms should be measured. d. Connect one meter lead to Red, connect the
PROCEDURE: 1. Disconnect Wire 4 from the Voltage Regulator (VR). (Third terminal from the right side of VR).
remaining test lead to Black, approximately 10 ohms should be measured. e. Connect one meter lead to Red, connect the
remaining test to the stepper motor case. No resistance should be measured (“Infinity” or Open).
RESULTS: 1. If the stepper motor fails any part of Step 5 replace the stepper motor.

A B C D E F G
VOLTAGE RESULTS WIRE 2 & 6 EXCITATION WINDING
ABOVE 60 VAC ABOVE 60 VAC BELOW
60 VAC ZERO OR RESIDUAL
BELOW BELOW
60 VAC ABOVE 60 VAC
VOLTAGE (5-12 VAC)
VOLTAGE RESULTS WIRE 11S & 22S POWER WINDING SENSE LEADS
60 VAC ABOVE 60 VAC ZERO OR RESIDUAL
BELOW BELOW
60 VAC ABOVE 60 VAC
VOLTAGE (5-12 VAC)
ROTOR AMP DRAW RV45 (MODEL 5410/5411)
1.1 A ± 20%
1.1 A ± 20%
1.1 A ± 20%
ZERO CURRENT
1.4 A .85 A ± 20%
ZERO CURRENT
DRAW
DRAW
ROTOR AMP DRAW RV55 (MODEL 5412/5413)
.85 A ± 20%
.85 A ± 20%
.85 A ± 20%
ZERO CURRENT
1.2 A .85 A ± 20%
ZERO CURRENT
DRAW
DRAW
ROTOR AMP DRAW RV65 (MODEL 5414/5415)
1.2 A ± 20%
1.2 A ± 20%
1.2 A ± 20%
ZERO CURRENT
1.5 A 1.2 A ± 20%
ZERO CURRENT
DRAW
DRAW
(MATCH RESULTS WITH LETTER AND REFER TO FLOW CHART – Problem 2 on Pages 28 & 29)
105 VAC
RED TEST LEAD
BLACK TEST LEAD 95 VAC
VOLTAGE REGULATOR
VOLTAGE REGULATOR
BLACK TEST LEAD
22S
11S 15
JUMPER WIRE
JUMPER WIRE
22S
11S
FUSE HOLDER (F1)
WIRES 4 REMOVED FROM VOLTAGE REGULATOR
FUSE HOLDER (F1)
WIRES 4 REMOVED FROM VOLTAGE REGULATOR
Figure 7-4. – Fixed Excitation Test, Step B
Figure 7-5. – Fixed Excitation Test, Step C

Loss of the field boost function may or may not result in a problem with AC output voltage. If the Rotor’s residual magnetism is sufficient to turn the Regulator on, loss of the function may go unnoticed. However, if the Rotor’s residual magnetism is not enough to turn the Regulator on, loss of field boost can result in fail ure of the unit to generate an output voltage.
1.11 Amp
PROCEDURE: 1. Set VOM to measure DC voltage.
22S
FUSE HOLDER (F1)
Results: 1. If field boost checks good, replace the Voltage Regulator.
Figure 7-6. – Fixed Excitation Test, Step D
11S
22S
22S
REGULATOR
BA
Results:
AC Voltage across Wires 2 and 6 =
Figure 7-7. – The Field Boost Circuit
AC Voltage across Wires 11S and 22S =
Proceed to “TEST 4 RESULTS” (top of page 40). Match all results to corresponding column in the chart. The column letter refers to the Problem 4 flow charts on pages 28 and 29.
DISCUSSION: An open circuit in the Stator excitation windings will result in a loss of unregulated excitation current to the Voltage Regulator. The flow of regulated excitation cur rent to the Rotor will then terminate and the unit’s AC output voltage will drop to a value that is commensurate with the rotor’s residual magnetism (about 5 - 12 VAC).
DISCUSSION: Field boost current is delivered to the Rotor only while the engine is being cranked. This current helps ensure that adequate “pickup” voltage is available to turn the Voltage Regulator on and build AC output voltage.

c. Connect one VOM test lead to Stator lead 2 the
other test lead to Stator lead 33. “Infinity” should be indicated.
RESULTS: 1. If the Stator excitation (DPE) windings are open or shorted, replace the Stator assembly.
2 2 6 6
Windings
A. Schematic B. Pictorial
DISCUSSION: The Voltage Regulator “regulates” excitation current flow to the Rotor by electronically comparing sensing voltage to a pre-set reference voltage. The sensing voltage is delivered to the Voltage Regulator via Wires 11S and 22S. If an open circuit exists in sensing leads 11S or 22S, the normal reaction of an unprotected Regulator would be to increase the excitation current to the Rotor in an effort to increase the actual AC output voltage. This would result in a “full field” condition and an extremely high AC output voltage. To protect the system against such a high AC output voltage, the Voltage Regulator will shut down if sens ing voltage signals are lost. If the regulator shuts down, the generator’s AC output voltage will decrease to a value that is commensurate with the Rotor’s residual magnetism (about 5-12 VAC).
Figure 7-8. – Stator Excitation Winding
PROCEDURE: 1. Disconnect Wire 2 from the Voltage Regulator.
MODEL OHMS
RV45 (5410/5411) 2.59 Ω
RV55 (5412/5413) 1.41 Ω − 1.63Ω
PROCEDURE: Gain access to the generator control panel interior. Test the Stator power windings, as follows: 1. From main breaker, disconnect Wires 11 and 33.
* Resistance values In ohms (Ω) at 20°C. (68°F.). Actual readings may vary depending on ambient temperature. A tolerance of plus or minus 5% is allowed.
a. Connect one meter test lead to Stator lead No.
2, the other test lead to a clean frame ground. b. The meter should read “Infinity”. Any other read
ing indicates a “short-to-ground” condition and the Stator should be replaced. 6. Test for a short between windings as follows:
a. Meter should be set to its “Rx1 K” or “Rx10,000”
scale. b. Connect one meter test lead to Stator lead 2,
the other test lead to Stator lead 11. The meter should read “Infinity”.

AC POWER WINDING RESISTANCE * RV45 (Model 5410/5411)
11 & 22 0.396 Ω
11S & 22S 0.396 Ω
33 & 44 0.396 Ω
CB1
CB2
AC POWER WINDING RESISTANCE * RV55 (Model 5412/5413)
11S 22S 22
11 & 22 0.28 Ω − 0.32Ω
11S & 22S 0.28 Ω − 0.32Ω
33 & 44 0.28 Ω − 0.32Ω
AC POWER WINDING RESISTANCE * RV65 (Model 5414/5415)
11 & 22 0.209 Ω − 0.242Ω
11S & 22S 0.209 Ω − 0.242Ω
Figure 7-9. – Stator Power Winding Leads
* Resistance values In ohms at 20° C. (68° F.). Actual readings may vary depending on ambient temperature. A tolerance of plus or minus 5% is allowed.
DISCUSSION: In Test 4, if application of battery voltage to the Rotor did NOT result in an output of about one-half rated voltage, the brush leads could be one possible cause of the problem. This test will check Wires 4 and 0 for an open circuit condition.
PROCEDURE: 1. Set a VOM to its “Rx1” scale and zero the meter.
RESULTS: 1. If the Stator passes all steps except Step 7, repair, re-connect or replace Sensing leads 11S and 22S.
RESULTS: 1. Repair, reconnect or replace any defective wire(s).
11 33 44 · BLACk RED

RESULTS: 1. Replace bad brushes. Clean slip rings, if neces sary.
DISCUSSION: During the “Test 4 – Fixed Excitation Test,” if AC out put voltage did not come up to about one-half rated volts, one possible cause might be a defective Rotor. The Rotor can be tested for an open or shorted condi tion using a volt-ohm-milliammeter (VOM). Also see Chapter Three, “INSULATION RESISTANCE TESTS”.
Figure 7-10. – Brush Leads
PROCEDURE: Gain access to the brushes and slip rings. Disconnect Wire 4 and Wire 0 from their respective brushes and remove the brush holder. Then, test the Rotor as fol lows: 1. Set a VOM to its “Rx1” scale and zero the meter.
DISCUSSION: Brushes and slip rings are made of special materials that will provide hundreds of hours of service with little wear. However, when the generator has been idle for some time, an oxide film can develop on the slip rings. This film acts as an insulator and impedes the flow of excitation current to the Rotor. If Test 4 resulted in less than one-half rated output voltage, it is possible that the brushes and slip rings are at fault.
MODEL OHMS
RV45 5410/5411 13.4 Ω
PROCEDURE: 1. Gain access to the brushes and slip rings.
RV65 5414/5415 10.81 Ω
* Resistance values In ohms at 20° C. (68° F.). Actual readings may vary depending on ambient temperature. A tolerance of plus or minus 5% is allowed.
a. If slip rings appear dull or tarnished they may be
cleaned and polished with fine sandpaper. DO NOT USE ANY METALLIC GRIT TO CLEAN SLIP RINGS. (A 400 grit wet sandpaper is rec ommended). b. After cleaning slip rings, blow away any sandpa
RESULTS: 1. Replace the Rotor if it fails the test.
per residue.

Frequency
DISCUSSION: If engine speed appears to drop off excessively when electrical loads are applied to the generator, the load voltage and frequency should be checked.
Figure 7-11. – Rotor Assembly
PROCEDURE: Perform this test in the same manner as Test 1, but apply a load to the generator equal to its rated capac ity. With load applied check voltage and frequency. Frequency should not drop below about 60 Hertz with the load applied. Voltage should not drop below about 120 VAC with load applied.
DISCUSSION: The main circuit breaker on the generator panel must be closed or no output to the load will be available. A defective breaker may not be able to pass current even though it is in the “ON” position.
RESULTS: 1. If voltage and/or frequency drop excessively when the load is applied, go to Test 13.
CB2
RED
Test 13 – Check Load Watts &
Amperage
DISCUSSION: This test will determine if the generator’s rated watt age/amperage capacity has been exceeded. Continuous electrical loading should not be greater than the unit’s rated capacity.
PROCEDURE: Add up the wattages or amperages of all loads pow ered by the generator at one time. If desired, a clamp- on ammeter may be used to measure current flow. See “Measuring Current” on Page 16.
Figure 7-12. – Main Breaker (Typical)
PROCEDURE: Set the coach main breaker to it’s “OFF” position. Check that the appropriate main breaker on the gen erator panel is set to its “ON” (closed) position. Set a VOM to measure resistance and use it to check for continuity across the breaker terminals.
RESULTS: 1. If the unit is overloaded, reduce the load.
RESULTS: 1. If breaker is “ON” and “Continuity” is measured, go to Test 3.
33 11 BLACk

Short to Ground:
DISCUSSION: If the Start-Stop Switch on the generator panel is actuated, but the Fuel Pump does not run (priming function doesn’t work), perhaps battery voltage is not available.
PROCEDURE: Hold the Start-Stop Switch at “START”. The engine should crank and start.
RESULTS: 1. If the engine cranks normally, but the priming function still doesn’t work, go to Test 20.
DISCUSSION: An inoperative Fuel Pump will (a) prevent the priming function from working and (b) prevent the engine from starting.
Figure 7-13. – Electric Fuel Pump
RESULTS: 1. If “Continuity” was not measured in Step 4, repair or replace Wire 0 between Connector 2 and the ground terminal.
PROCEDURE: 1. Remove Fuel Filter and verify that filter is not clogged. Replace filter if necessary.
PIN 2 - BLACk WIRE
Figure 7-14. – Harness to Fuel Pump

DISCUSSION: If the panel-mounted 7.5 amp fuse (F1) has blown, engine cranking will not be possible.
Printed Circuit Board
DISCUSSION: If battery voltage is not available to the Printed Circuit Board (PCB), engine cranking and running will not be possible. If battery voltage is available to the PCB, but no DC output is delivered to the board’s Wire 56 terminal while attempting to crank, either the Printed Circuit Board is defective or the Start-Stop Switch has failed. This test will determine if battery voltage is available to the Printed Circuit Board. Test 20 will check the Start-Stop Switch. Test 21 will check the DC power supply to the Printed Circuit Board’s Wire 56 terminal (J1 Connector, Pin 9).
Figure 7-15. – 7.5 Amp Fuse
PROCEDURE: Push In on fuse holder cap and turn counterclockwise. Then, remove the cap with fuse. Inspect the Fuse.
RESULTS: If the Fuse element has melted open, replace the Fuse with an identical size fuse. If Fuse is good, go to Test 17.
PROCEDURE: 1. Disconnect J1 Connector from the PCB.
DISCUSSION: If the engine won’t crank or cranks too slowly, the battery may be weak or discharged. See “Battery” on Page 22.
PROCEDURE: 1. Inspect the battery cables and battery posts or terminals for corrosion or tightness. Measure the voltage at the terminal of the starter contac tor and verify 11-12 volts DC is available to the generator during cranking. If voltage is below 11 volts DC, measure at the battery terminals dur ing cranking. If battery voltage is below 11 volts DC, recharge/replace battery. If battery voltage is above 11 volts DC, check for proper battery cable sizing (see “BATTERY CABLES” on Page 24). If battery or cables are still suspected, connect an alternate battery and cables to the generator and retest.
a. Wire 13 between Starter Contactor and
Starter Contactor Relay. b. Wire 13 between Starter Contactor Relay and
7.5 Amp Fuse (F1). c. Wire 15 to Wire 13 on the 7.5 Amp fuse hold
er (F1). Repair, reconnect or Replace bad wiring as nec essary.
RESULTS: 1. Clean battery posts and cables as necessary. Make sure battery cables are tight.

DISCUSSION: A faulty condition in Wire 17 could prevent the unit from cranking when the Start-Stop switch is held in the “Start” position.
PROCEDURE: 1. Disconnect Wire 17 from its Switch terminal and connect it to frame ground. The engine should crank. If unit cranks, proceed to Step 2. If unit does not crank when grounding Wire 17, go back to Test 18 “Check Power Supply to Printed Circuit Board”, then repeat Step 1. If unit cranks, proceed to Test 20.
SW1
Figure 7-16. – Start-Stop Switch
RESULTS: 1. If “Continuity” is not measured in Step 5, repair or replace Wire 17.
DISCUSSION: Engine cranking and startup is initiated when Wire 17 from the Printed Circuit Board (PCB) is connected to frame ground by setting the Start-Stop Switch to “START”. Engine shutdown occurs when Wire 18 from the PCB is connected to frame ground by the Start-Stop Switch. A defective Start-Stop Switch can result in (a) failure to crank when the switch is set to “START”, and/or (b) failure to shut down when the switch is set to “STOP”.
DEPRESSED AWAY FROM TERMINAL BEING TESTED
PROCEDURE: Refer to Problem 6 (Section 6). 1. Set a VOM to its “Rx1” scale and zero the meter.
Figure 7-17. – Test 20, Step 5

RESULTS: 1. If battery voltage was measured in Step 6, but not in Step 4, repair or replace Wire 56 between the Printed Circuit Board and Starter Contactor Relay.
Test 22 – Check Starter Contactor
Relay
Figure 7-18. – Test 20, Step 6
DISCUSSION: If battery voltage is available to Wire 56 but the engine won’t crank, the possible cause could be a failed Starter Contactor Relay.
RESULTS: 1. If “Continuity” is not measured in Step 3, repair, reconnect or replace Wire 0 (between Start-Stop Switch and ground terminal) as necessary.
Wire 56
DISCUSSION: If battery voltage is available to the Printed Circuit Board in Test 18, then DC voltage should be deliv ered to Wire 56 when the Start-Stop Switch is set to “START” (Test 20). This test will check to see if the Printed Circuit Board is delivering battery voltage to the Wire 56 terminal.
Figure 7-19. – Starter Contactor Relay
PROCEDURE: 1. Set a VOM to measure DC voltage (12 VDC).
PROCEDURE: 1. Set the VOM to measure resistance (“R x 1” scale). Remove Wire 0 from the Starter Contactor Relay (SCR). Connect one meter test lead to Wire 0, and connect the other meter test lead to frame ground. “Continuity” should be measured. Reconnect Wire 0.

“Infinity” should be measured. Set the Start-Stop Switch to “START”. The meter should now read “Continuity”.
PROCEDURE: 1. Carefully inspect the starter motor cable that runs from the Battery to the Starter Motor. Cable con nections should be clean and tight. If connections are dirty or corroded, remove cable and clean cable terminals and studs. Replace any cable that is defective or badly corroded. Set the VOM to measure DC voltage. Connect the positive (+) meter test lead to the Starter Contactor stud that the battery cable is connected to. Connect the negative (-) meter test lead to a clean frame ground. Battery voltage should be measured (see Figure 7-20, STEP 1 TEST POINT).
Short to Ground:
RESULTS: 1. If “Continuity” is not measured in Step 1, repair or replace Wire 0 between the Starter Contactor Relay and the ground terminal.
RESULTS: 1. If battery voltage was not measured in Step 1, repeat Test 17.
DISCUSSION: The Starter Contactor (SC) must energize and it’s heavy duty contacts must close or the engine will not crank. This test will determine if the Starter Contactor is in working order. The Starter Contactor is connect ed to the Starter Motor (see Figure 7-20).
3 If battery voltage was measured in Step 1, but not in Step 3, replace the Starter Contactor.
SWITCH
BATTERY
CONNECTING
DIAGRAM
Conditions Affecting Starter Motor Performance: 1. A binding or seizing condition in the Starter Motor bearings.
STEP 1 TEST POINT
STARTER CONTACTOR
a. Shorted, armature (wire insulation worn and
wires touching one another). Will be indicated by low or no RPM. b. Open armature (wire broken) will be indicated
STARTER
by low or no RPM and excessive current draw. c. Grounded armature (wire insulation worn and
wire touching armature lamination or shaft). Will
Figure 7-20. – The Starter Contactor (SC)

be indicated by excessive current draw or no RPM. 3. A defective Starter Motor switch.
DISCUSSION: Test 21 verified that Printed Circuit Board action is delivering DC voltage to the Starter Contactor Relay (SCR). Test 22 verified the operation of the SCR. Test 23 verified the operation of the Starter Contactor (SC). Another possible cause of an “engine won’t crank” problem is a failure of the Starter Motor.
Figure 7-21. – Starter Motor (SM)
PROCEDURE: The battery should have been checked prior to this test and should be fully charged. Set a VOM to measure DC voltage (12 VDC). Connect the meter positive (+) test lead to the Starter Contactor stud which has the small jumper wire con nected to the Starter. Connect the common (-) test lead to the Starter Motor frame.
CHECKING THE PINION: When the Starter Motor is activated, the pinion gear should move and engage the flywheel ring gear. If the pinion does not move normally, inspect the pinion for binding or sticking.
Set the Start-Stop Switch to its “Start” position and observe the meter. Meter should Indicate battery volt age, Starter Motor should operate and engine should crank.
RESULTS: 1. If battery voltage is indicated on the meter but Starter Motor did not operate, remove and bench test the Starter Motor (see following test).
If engine turns over slightly, go to Test 32 “Check and Adjust Valves.” NOTE: If a starting problem is encountered, the engine itself should be thoroughly checked to eliminate it as the cause of starting difficulty. It is a good practice to check the engine for freedom of rotation by removing the spark plugs and turn ing the crankshaft over slowly by hand, to be sure it rotates freely. *
Figure 7-22. – Check Pinion Gear Operation
TOOLS FOR STARTER PERFORMANCE TEST: The following equipment may be used to complete a performance test of the Starter Motor: ❏ A clamp-on ammeter. ❏ A tachometer capable of reading up to 10,000 rpm. ❏ A fully charged 12-volt battery.
ELECTRIC STARTER WITH SPARK PLUGS REMOVED. ARCING AT THE SPARK PLUG ENDS MAY IGNITE THE GASOLINE VAPOR EXITING THE SPARK PLUG HOLE.
Measuring Current: To read the current flow, in AMPERES, a clamp-on ammeter may be used. This type of meter indicates current flow through a conductor by measuring the strength of the magnetic field around that conductor.

Remove Starter Motor: It is recommended that the Starter Motor be removed from the engine when testing Starter Motor perfor mance. Assemble starter to test bracket and clamp test bracket in vise (Figure 7-26).
Testing Starter Motor: 1. A fully charged 12 volt battery is required.
Figure 7-23. – Clamp-On Ammeter
Tachometer: A tachometer is available from your Generac Power Systems source of supply. Order as P/N 042223. The tachometer measures from 800 to 50,000 RPM (see Figure 7-24).
Maximum Amps 50

STARTER CONTACTOR STARTER
Figure 7-24. – Tachometer
Test Bracket: A starter motor test bracket may be made as shown in Figure 7-25.
METAL STOCk 1/4" THICk STEEL
0.5"
2.625"
0.5"
3.5"
12 VOLT BATTERY
1.0" 4"
DRILL TWO HOLES — 1/2" FOR STARTER MOUNTING BRACkET
Figure 7-26. – Testing Starter Motor Performance
DRILL TWO HOLES — 1/2" FOR MOUNTING TACHOMETER TAP FOR 1/4-20 NC SCREWS
Figure 7-25. – Test Bracket
12" · 2"

DISCUSSION (Gasoline Models): If the engine cranks but won’t start, don’t overlook the obvious. The fuel supply may be low. Many RV gener ator installations “share” the fuel tank with the vehicle engine. When such is the case, the Installer may have used a generator fuel pickup tube that is shorter than the vehicle engine’s pickup tube. Thus, the generator will run out of gas before the vehicle engine.
PROCEDURE: Check fuel level in the supply tank. Attach a fresh fuel supply if necessary and restart. Fuel may be stale, causing a hard start.
RESULTS: 1. If necessary, replenish fuel supply.
CAUTION! Use only approved components in
the fuel supply system. All components must be properly installed in accordance with appli cable codes. Improper installation or use of unauthorized components may result in fire or an explosion. Follow approved methods to test the system for leaks. No leakage is per mitted. Do not allow fuel vapors to enter the vehicle interior.
DISCUSSION (LPG Models): LP gas is stored in pressure tanks as a liquid. The gas systems used with these generators were designed only for vapor withdrawal type systems. Vapor with drawal systems use the gas vapors that form above the liquid fuel in the tank. Do NOT attempt to use the generator with any liquid withdrawal type system.
LP gas vapors should be supplied to the second ary regulator inlet at about 11 inches water column (positive pressure). The engine pistons draw air in during the intake stroke (Figure 7-28). This air passes through a carburetor venturi, which creates a low pressure that is proportional to the quantity of air being pumped. The low pressure from the carburetor venturi acts on the regulator diaphragm to pull the diaphragm toward the source of low pressure. A lever attached to the diaphragm opens a valve to permit gas glow through the carburetor.
REGULATOR PRIMARY REGULATOR
TO CARBURETOR
GAS IN
CARBURETOR VAPOR WITHDRAWAL TANk
Figure 7-27 – Typical Propane Gas Fuel System
Gas pressure delivered to the solenoid valve must be properly regulated by means of a primary gas regula tor. Mount the primary regulator at the gas tank outlet or in the supply line from the gas tank. The following rules apply:
Figure 7-28 – LP Gas Carburetion Diagram

DISCUSSION: When the engine is cranked, Printed Circuit Board action must deliver battery voltage to the Wire 14 cir cuit, or the engine will not start. This is because the Wire 14 circuit will operate the Fuel Pump and Fuel Solenoid on Gasoline models. On LP models it oper ates the LPG Shut-off valve.
Procedure: A water manometer or a gauge that is calibrated in “ounces per square inch” may be used to measure the fuel pressure. Fuel pressure at the inlet side of the LPG Shut Off Valve should be between 11-14 inches water column as measured with a manometer. The LP system must be able to maintain 11-14 inches water column under all load requirements. 1. Turn LP supply to generator off.
Figure 7-30. – The 4-tab Connector
GAS PRESSURE
TAP
RESULTS: 1. If the meter indicated battery voltage, go to Test 20 “Check Start-Stop Switch”.
Figure 7-29. – Fuel Regulator
RESULTS: 1. If the LP gas pressure is less than 11-14 inches water column the fuel supply system must be corrected in order to maintain 11-14 inches water column.
a. Repair, reconnect or replace Wire 14 as neces
sary. 3. If battery voltage was not indicated in Step 5, replace the Printed Circuit Board.

Test 28 – Check Fuel Solenoid
(Gasoline Models)
DISCUSSION: Wire 18 controls sending the STOP signal to the Printed Circuit Board. Coach manufacturers some times install a 15 to 30 foot remote harness. If unit shuts down or will not start, a possible ground exists on Wire 18.
DISCUSSION: If the Fuel Solenoid fails to open, the engine will not start.
PROCEDURE: 1. Remove Control Panel cover. Remove Wire 56 from the Starter Contactor Relay. This will prevent the unit from cranking during test (see Figure 7- 19, Page 47).
PROCEDURE: 1. Disconnect the customer installed remote harness connector from the generator. Then press the gen erator Start-Stop switch to the “Start” position. If generator starts and continues to run, a short is present in the coach remote harness. Repair or replace the remote harness.
H A B C D
G
E
Figure 7-31. – Remote Harness Connector
Short to Ground:
7. Set the VOM to measure resistance. Disconnect the bullet connector going to the Fuel Solenoid. Connect one meter test lead to the Red Wire going to the Fuel Solenoid. Connect the other meter test lead to the Fuel Solenoid housing. A reading of 38.0 ohms should be measured. If very low resistance is measured, a short to ground exists. (Fuel Solenoid coil resistance is approximately 38.0 ohms. Current draw of the Fuel Solenoid at nominal voltage is approximately 331 milliamps or 0.331 amps).
RESULTS: 1. If “Continuity” is measured in Step 2, repair or replace shorted Wire 18 between J1 Connector and Start-Stop Switch.
RESULTS: 1. If the Fuel Solenoid passes Steps 4 & 5 but does NOT operate in Step 3, replace or repair Fuel Solenoid.

SPARk TESTER CLAMP CONNECTED TO SPARk PLUG SPARk TESTER
PROCEDURE: 1. Disconnect a high tension lead from a spark plug.
Figure 7-33. – Checking Engine Miss
RESULTS: 1. If no spark or if engine miss is apparent, go to Test 31.
Cylinder Balance Test: If the engine is hard starting, runs rough, misses or lacks power, perform a cylinder balance test to deter mine whether both cylinders are operating to their full potential.
SPARk TESTER CLAMP GROUNDED TO CYLINDER HEAD
Tools Required:Two Ignition Testers (Generac P/N 0C5969) Attach an ignition tester between the spark plug lead and each spark plug (Figure 7-33). Start and run engine running at top no load speed and note spark at ignition testers. If the spark is equal at both ignition testers, the problem is not ignition related. A spark miss will be readily apparent. Now note RPM of engine. Ground out one cylinder by con tacting ignition tester and a good ground on engine as shown in Figure 7-34. Note RPM loss. Reattach plug wire then repeat procedure with the other cylinder. Note the RPM loss. If the difference between the two cylinders does not exceed 75 RPM, the amount of work the two cylinders are doing should be consid ered equal. If the RPM loss is greater than 75 RPM this indicates that the grounded cylinder with the least RPM loss is the weakest of the two cylinders. Look to that cylinder for a problem. Example:
Figure 7-32. – Testing Ignition System
ing at 350 rpm or more. If spark jumps the tester gap, you may assume the ignition system is work ing properly. Repeat on remaining cylinder spark plug.
Engine RPM - Both Cylinders = 2570 RPM Engine RPM - No. 1 Cylinder Grounded = 2500 RPM Engine RPM - No. 2 Cylinder Grounded = 2300 RPM Conclusion: No. 1 cylinder is weakest of the two cylinders.
SPARk PLUG BOOT · SPARk TESTER · SPARk PLUG BOOT


Magnetos
DISCUSSION: The ignition system used on GT-530 engines is a solid-state (breakerless) type. The system utilizes a magnet on the engine flywheel to induce a relatively low voltage into an ignition magneto assembly. Ignition magneto internal components increase the voltage and deliver the resulting high voltage across the spark plug gap. The ignition magneto houses a solid state-circuit board that controls ignition timing. Timing is fixed and spark advance is automatic. Major components of the ignition system include (a) two ignition magneto assemblies, (b) the spark plugs, (c) the engine control printed circuit board and (d) the engine flywheel. Solid-state components encapsulated in the ignition magneto are not accessible and cannot be serviced. If the magneto is defective, the entire assembly must be replaced. The air gap between the magneto and the flywheel magnet is between 0.012” to 0.015”. The ignition magneto assembly (Figure 7-36) consists of (a) ignition magneto, (b) spark plug high tension lead and (c) spark plug boot.
Figure 7-34. – Cylinder Balance Test
The cylinder balance test will also detect a cylinder that is not functioning. When grounding out one cylin der there will be no RPM loss. When the other cylin der is grounded out the engine will stop.
DISCUSSION: During Test 29, if spark jumped the tester gap, the ignition system must be functioning properly. However, if the engine misses the spark plug itself may be fouled.
SPARk PLUG HIGH TENSION LEAD
PROCEDURE: Remove spark plugs. Clean with a commercial sol vent. DO NOT BLAST CLEAN SPARK PLUGS. Replace spark plugs if badly fouled, if ceramic is cracked, or if badly worn or damaged. Set gap to 0.030 inch (0.76mm). Use a NGK BPR6HS (or equiv alent) replacement spark plug.
SET PLUG GAP AT 0.030 inch
(0.76 mm)
Figure 7-36. – Ignition Magneto Assembly
In Test 29, a spark tester was used to check for engine ignition. If sparking or weak spark occurred, one possible cause might be the ignition magneto(s). This test consists of adjusting the air gap between the ignition magneto(s) and the flywheel. The flywheel and flywheel key will also be checked during this test. If no sparking occurs, the ground harness may be at fault.
Figure 7-35 – Setting Spark Plug Gap
Procedure: 1. Disconnect the J1 connector from the Printed Circuit Board. Carefully remove Wire 18A from Pin Location J1-14. Connect the J1 connector back to the Printed Circuit Board. Repeat Test 29 “Check Ignition Spark”. If the unit now produces spark go
RESULTS: 1. Clean and regap or replace sparks plug as neces sary.
SPARk PLUG BOOT

to Step 2. If the unit does not produce spark or has weak spark go to Step 4.
a. Set a VOM to measure resistance. Connect
the positive (+) meter test lead to Wire 18A (Wire 18A still removed from the J1 connec tor) Connect the negative (-) meter test lead to a clean frame ground. “Infinity” should be measured, or 0.5 to 1M ohms, depending upon the type of VOM used. If “Continuity” is measured proceed to Step 12. b. Set a VOM to the diode test range. Attach the
negative (-) meter test lead to Pin Location J1-14 on the Printed Circuit Board. (Wire 18A still removed from the J1 connector) Attach the positive (+) meter test lead to frame ground. Set the Start-Stop Switch to “start”. “Infinity” should be measure during crank ing and running. If the VOM does not have a diode test range, set VOM to measure resis tance again. “Infinity” should be measured. 3. If Step 1 produced spark and Step 2 tested good, set the VOM to measure DC voltage. Connect one test lead to Wire 15 (J1-4) on PCB. Connect the other test lead to frame ground. Battery voltage should be measured. Verify that Wire 15 is con nected to J1 and that Wire 14 is connected to J1- 5; if reversed the unit will produce no spark.
Results: 1. If “Infinity” was not measured in Step 2b, replace the Printed Circuit Board.
Note: If VOM was set to Diode test, a reading of 0.5 volts would be observed when the Start-Stop Switch is set to “STOP”. If the VOM was set to resistance, a reading of 0.5 to 1.5M ohms would be measured. During cranking and running this reading should go to “Infinity”. Verify that the meter leads were properly connected as per Step 2 instructions. 2. If battery voltage was not measured in Step 3, reconnect Wire 15 and Wire 14 to their correct terminal locations.

ENGINE GROUND HARNESS
TEST LEAD
B
A
Figure 7-37. – Setting Ignition Magneto
TEST LEAD
pull the magneto down against the thickness gauge.
Figure 7-38. – Engine Ground Harness Test Points
(Armature) Air Gap

ROCKER ARM JAM NUT 174 inch-pounds
CHECKING FLYWHEEL MAGNET: The flywheel magnet rarely loses its magnetism. If you suspect a magnet might be defective, a rough test can be performed as follows: 1. Place the flywheel on a wooden surface.

FLYWHEEL KEY: In all cases, the flywheel taper is locked on the crank shaft taper by the torque of the flywheel nut. A keyway is provided for alignment only and theoretically carries no load. If the flywheel key becomes sheared or even partially sheared, ignition timing can change. Incorrect timing can result in hard starting or failure to start. Remove and inspect flywheel key for damage.
ALLEN WRENCH
Figure 7-39 – Adjusting Valve Clearance
Test 32 – Check Valve Adjustment
Discussion: The valve lash must be adjusted correctly in order to pro vide the proper air/fuel mixture to the combustion chamber.

Adjusting Valve Clearance: Adjust valve clearance with the engine at room tem perature. The piston should be at top dead center (TDC) of its compression stroke (both valves closed). An alternative method is to turn the engine over and position the intake valve fully open (intake valve spring compressed) and adjust the exhaust valve clearance. Turn the engine over and position the exhaust valve fully open (exhaust valve spring compressed) and adjust the intake valve clearance. Correct valve clearance is given below, in INCHES (MILLIMETERS).
Figure 7-40 – Tightening the Jam Nut
Install Rocker Arm Cover 1. Use a new rocker arm cover gasket. Install the rocker arm cover and retain with four screws.
Results: Adjust valves to specification and retest. If problem continues, go to Test 35.

Test 34 – Check Choke Solenoid
DISCUSSION: If the engine cranks but will not start, one possible cause of the problem might be the carburetion system.
DISCUSSION: The automatic choke is active only during cranking. When the Start-Stop Switch is held at “START”, a crank relay on the Printed Circuit Board is energized closed to (a) crank the engine and (b) deliver a cyclic voltage to the Choke Solenoid via Wire 14. The Choke Solenoid will be pulled in for about two seconds, then deactivate for about two seconds. This cyclic choking action will continue as long as the engine is being cranked.
PROCEDURE: Before making a carburetion check, be sure the fuel sup ply tank has an ample supply of fresh, clean gasoline. Check that all shutoff valves are open and fuel flows freely through the fuel line. Make sure the automatic choke operates properly. If the engine will not start, remove and inspect the spark plug. If the spark plug is wet, look for the following: ❏ Overchoking. ❏ Excessively rich fuel mixture. ❏ Water in fuel. ❏ Intake valve stuck open. ❏ Needle/float stuck open. If the spark plug is dry look for the following: ❏ Leaking carburetor mounting gaskets. ❏ Intake valve stuck closed. ❏ Inoperative fuel pump. ❏ Plugged fuel filter(s). ❏ Varnished carburetor If the engine starts hard or will not start, look for the following: ❏ Physical damage to the AC generator. Check the
PROCEDURE: 1. Operational Check: Crank the engine. While cranking, the choke solenoid should pull in about every 2 seconds (2 seconds ON, 2 seconds OFF). If the choke solenoid does not pull in, try adjusting the choke as follows.
Rotor for contact with the Stator. ❏ Starting under load. Make sure all loads are discon
nected or turned off before attempting to crank and start the engine. ❏ Check that the automatic choke is working properly.
STEPPER
MOTOR
RESULTS: If problem has not been solved, go to Test 34. If car buretor is varnished, clean or replace. 1. Remove fuel line at carburetor and ensure that there is an adequate amount of fuel entering the carburetor.
Figure 7-41. – Automatic Choke Assembly
Shelf life on gasoline is 30 days. Proper procedures need to be taken for carburetors so that the fuel doesn’t varnish over time. A fuel stabilizer must be used at all times in order to ensure that the fuel is fresh at all times.

in its coil, tighten the two screws. Verify that the choke solenoid plunger and linkage move freely without any drag or resistance that may restrict movement.
PLUNGER
Short to Ground:
RESULTS: 1. If Choke operation is good, go to Test 32 for Problem 7, “Engine Cranks but Won’t Start” (Section 6). Go to Test 41 for Problem 8, “Engine Starts Hard and Runs Rough”.
Figure 7-42. – Choke Solenoid Adjustment
Down Test / Compression Test
GENERAL: Most engine problems may be classified as one or a combination of the following: ❏ Will not start. ❏ Starts hard. ❏ Lack of power. ❏ Runs rough. ❏ Vibration. ❏ Overheating. ❏ High oil consumption.
SOLENOID
Figure 7-43. – Connector 3
PANEL TO CHOkE

Discussion: The Cylinder Leak Down Tester checks the sealing (compression) ability of the engine by measuring air leakage from the combustion chamber. Compression loss can present many different symptoms. This test is designed to detect the section of the engine where the fault lies before disassembling the engine.
PROCEDURE: 1. Remove both spark plugs.
Procedure: 1. Remove a spark plug.
RESULTS: The difference in pressure between the two cylinders should not exceed 25 percent. If the difference is greater than 25 percent, loss of compression in the lowest reading cylinder is indicated. Example 1: If the pressure reading of cylinder #1 is 165 psi and of cylinder #2, 160 psi, the difference is 5 psi. Divide “5” by the highest reading (165) to obtain the percentage of 3.0 percent. Example 2: No. 1 cylinder reads 160 psi; No. 2 cylinder reads 100 psi. The difference is 60 psi. Divide “60” by “160” to obtain “37.5” percent. Loss of compression in No. 2 cylinder is indicated. If compression is poor, look for one or more of the fol lowing causes: ❏ Loose cylinder head bolts. ❏ Failed cylinder head gasket. ❏ Burned valves or valve seats. ❏ Insufficient valve clearance. ❏ Warped cylinder head. ❏ Warped valve stem. ❏ Worn or broken piston ring(s). ❏ Worn or damaged cylinder bore. ❏ Broken connecting rod. ❏ Worn valve seats or valves. ❏ Worn valve guides. NOTE: Refer to Engine Service manual P/N xxxxxx for further engine service information.
Results: ❏ Air escapes at the carburetor – check intake valve. ❏ Air escapes through the exhaust – check exhaust
valve. ❏ Air escapes through the breather – check piston
rings. ❏ Air escapes from the cylinder head – the head gas
ket should be replaced.
Check Compression: Lost or reduced engine compression can result in (a) failure of the engine to start, or (b) rough operation. One or more of the following will usually cause loss of compression: ❏ Blown or leaking cylinder head gasket. ❏ Improperly seated or sticking-valves. ❏ Worn Piston rings or cylinder. (This will also result in
DISCUSSION: Also see “Operational Analysis” on Pages 18-23. The Low Oil Pressure Switch is normally-closed, but is held open by engine oil pressure during cranking and startup. Should oil pressure drop below a safe level, the switch contacts will close to ground the Wire 85 circuit. Printed Circuit Board action will then initiate an automatic shutdown. If the switch fails closed, the engine will crank and start, but will then shut down after a few seconds. If the switch fails open, low oil pressure will not result in automatic shutdown.
high oil consumption). NOTE: It is extremely difficult to obtain an accu rate compression reading without special equip ment. For that reason, compression values are not published for the V-Twin engine. Testing has proven that an accurate compression indication can be obtained using the following method.

RESULTS: 1. If “Continuity” is not indicated, repair or replace Wire 86.
Figure 7-44. – Oil Pressure Switch
PROCEDURE: 1. Check engine oil level. If necessary, replenish oil level to the dipstick “FULL” mark.
DISCUSSION: If the engine cranks, starts and then shuts down, one possible cause of the problem may be a high oil temperature condition. Protective shutdown is a nor mal occurrence if the oil temperature switch exceeds approximately 270° F for gasoline units, or 284° F for LP units.
RESULTS: 1. In Step 3, if “Continuity” is not indicated, replace the switch.
Figure 7-45. – Oil Temperature Switch
PROCEDURE: 1. Remove Wire 85 from Oil Temperature Switch terminal and start the generator. If engine starts and runs now, but shuts down when Wire 85 is connected to the switch terminal, the following possibilities exist:
a. Oil temperature is too high. b. The oil temperature switch has failed closed or
PROCEDURE: 1. Disconnect the J1 Connector from the Printed Circuit Board.
is shorted to ground. 2. Remove the switch and place its sensing tip into oil (Figure 7-46). Place a thermometer into the oil.

RESULTS: 1. If “Continuity” is not indicated, repair or replace Wire 85.
DISCUSSION: The Choke Heater is a sensitive heating element wrapped around a temperature sensitive Bi-Metal strip. The Bi-Metal Heater Assembly positions the Choke Plate during startup. Once running, the Bi- Metal Heater Assembly will also allow the Choke Plate to fully open. Power for the heater element is supplied from Wire 14 to assist the Bi-Metal Heater Assembly in opening the Choke Plate after starting. Failure of the Choke Plate to open will cause an excessively rich fuel-air mixture and engine performance will suffer.

PROCEDURE: 1. Verify that the Choke Plate on the carburetor is mechanically free to move and is not binding. If the engine runs rough, check the operation of the Bi-Metal Heater Assembly. Allow the engine to run for five minutes, then inspect the choke position. The Bi-Metal strip should have been heated by the Choke Heater and should have expanded to allow the Choke Plate to open fully.
Figure 7-46. – Testing Oil Temperature Switch
RESULTS: 1. If the Oil Temperature Switch fails Step 3 or Step 4, replace the Oil Temperature Switch.
2. If the Oil Temperature Switch is good, an overheat condition may be occurring. Verify that the installa tion of the generator is within specified tolerances. The generator must receive the proper amount of incoming air, and also be able to exhaust the cooling air with NO RESTRICTIONS. Check to be sure that the exhaust pipe is not under the air intake. Refer to the Owner’s and Installation Manual for proper installation specifications. If installation is correct, go to Test 20.
PROCEDURE: 1. Disconnect the J1 Connector from the Printed Circuit Board.
Short to Ground: Set the VOM to measure resistance. Connect one meter test lead to Wire 14 (Connector 3, Pin 3) going to the Bi-Metal Heater Assembly. Connect the other meter test lead to the exposed steel portion of the Bi- Metal Heater Assembly. Approximately 37 ohms (±20%) should be measured. (Current draw of the Bi-Metal Heater Assembly at nominal voltage is approximately 340 milliamps or 0.340 amps). If “Continuity” is present the Bi-Metal Heater Assembly has a short to ground.

Results: 1. If Choke Plate is binding in Step 1, repair or replace binding Choke Plate. If Bi-Metal Heater Assembly tests good, go to Test 32.
RESULTS: 1. If the solenoid energized in Step 1, proceed to Test 29.
DISCUSSION: If the LPG Fuel Solenoid (FS) fails to open, fuel will not be available to the engine and it will not start.
PROCEDURE: 1. Place one hand on the top of the LPG Fuel Solenoid. Activate the Fuel Prime Switch. You should be able to feel as well as hear the solenoid energize. If solenoid energizes discontinue testing.
Figure 7-49. – Fuel Solenoid
Short to Ground: Set VOM to measure resistance. Disconnect Wire 14A from the LPG Fuel Solenoid. Connect one meter test lead to LPG Fuel Solenoid. terminal that Wire 14A was just removed from. Connect the other meter test lead to a clean frame ground. LPG Fuel Solenoid. Coil resistance of approximately 30-32 ohms Should be measured. Current draw of the LPG Fuel Solenoid at nominal voltage Is approximately 380 milliamps or 0.380 amps.




27 1.5ft TAPE ELEC UL FOAM 1/8 X 1/2

Enclosure – Drawing No. 0G3881-C




Control Panel – Drawing No. 0G5489-D
REAR VIEW OG3530
TO AIRBOX
TO "A" 29 30
33,34 · 9 14 13


5 1 NUT HEX M6 X 1.0 G8 YEL CHR
49 1 CIRCT BRK 20X1 MAG 10-32 CARL (4500W)
50 1 CIRCT BRK 20X1 MAG 10-32 CARL (4500W)
52 1 NYLON SPACER .26 X 1.00 X 1.73
53 1 B U L K H E A D A D A P T E R F I T T I N G (5410-1/5412-1/5414-1 ONLY)
54 1 B A R B E D 9 0 E L B OW ¼ X ¼ N P T (5410-1/5412-1/5414-1 ONLY)
55 1 PLUG STD. PIPE ¼ COUNTERSINK (5410-1/5412-1/5414-1 ONLY)

Engine Accessories – Drawing No. 0G7718-B



41 4 SCREW HHTT M6-1.0 X 10 YELLOW CHROME
46 1 90 DEGREE ELBOW 3/8 NPT X 3/8 BARBED

530 RV Engine – Drawing No. 0G7719-B

52 53 54 · 1,24,39,44,48 48,49 · 24,27,28,29,30,31,32,33,34,35,36,39,41 24,27,28,29,30,31,32,33,34,35,39,41,46


3 9 SCREW HHFC M8 – 1.25 X 45

Rotor & Stator – Drawing No. 0G3953-b
10 11 1



Major Features and Dimensions – Drawing No. 0G5519-b
FRONT DOOR ACCESS FOR
REQUIRED MAINTENANCE
OIL FILTER ACCESS
EXHAUST OUTLET
31.8 [1 1/4"]
853.4 [33 5/8"]
COOLING
AIR IN
424.8 [16 3/4"]
EVAPORATIVE
PORT FITTING
REMOTE START CONNECTION
BATTERY CONNECTION
TYP.
INLET
FUEL
109.1 [4 5/16"]
41.1 [1 5/8"]
HARNESS
543.8 [21 7/16"]
469.9 [18 1/2"]
3/8"-16 THD. (4 PLACES)
50 [1 15/16"]


TYPE OF ENGINE Vertical Shaft Vertical Shaft Vertical Shaft
OIL SYSTEM Pressurized with Filter Pressurized with Filter Pressurized with Filter
STARTER 12 VDC electric 12 VDC electric 12 VDC electric
SPARK PLUG GAP 0.030 inch (0.76mm) 0.030 inch (0.76mm) 0.030 inch (0.76mm)
Power Windings Lead 11 to 22 Lead 11S to 22S Lead 33 to 44
0.376 - 0.416 ohms 0.28 - 0.32 ohms 0.209 - 0.242 ohms
Excitation “DPE” Winding Lead 2 to 6 2.59 ohms 1.41 - 1.63 ohms 1.59 - 1.84 ohms
Rotor Winding Slip Ring to Slip Ring 13.4 ohms 14.88 ohms 10.81 ohms
Stator Bolts 8 ft-lbs Alternator Pulley 38 ft-lbs Engine Pulley 38 ft-lbs Oil Adaptor Bolt 4.5 ft-lbs Oil Lines 70 in-lbs Intake Manifold 18 ft-lbs Exhaust Manifold 18 ft-lbs M5-0.8 taptite screw into aluminum 25-50 in-lbs M5-0.8 taptite screw into pierced hole 25-50 in-lbs
M6-1.0 taptite screw into aluminum 50-96 in-lbs M6-1.0 taptite screw into pierced hole 50-96 in-lbs M6-1.0 taptite screw into weldnut 50-96 in-lbs M8-1.25 taptite screw into aluminum 12-18 ft-lbs M6-1.0 nylok nut onto stud 16-65 in-lbs Dipstick Casting Oil Line 250 in-lbs

Electrical Schematic and Wiring Diagram – Drawing No. 0G4221-B

Electrical Schematic and Wiring Diagram – Drawing No. 0G4221-B

P/N OG7515 REV. A PRINTED IN THE USA / 03.08