operation be copied and posted in potential hazard areas. Safety should be stressed to all operators, potential operators, and service and repair technicians for this equipment.
contains chemicals known to the state
of California to cause cancer, birth defects or other reproductive harm.
This product contains or emits chemicals known to the state of California to cause cancer, birth defects or other reproductive harm.
Study these SAFETY RULES carefully before install- ing, operating or servicing this equipment. Become familiar with this Owner’s Manual and with the unit. The generator can operate safely, efficiently and reli- ably only if it is properly installed, operated and maintained. Many accidents are caused by failing to follow simple and fundamental rules or precautions.
The manufacturer cannot anticipate every possible circumstance that might involve a hazard. The warn- ings in this manual, and on tags and decals affixed to the unit are, therefore, not all inclusive. If a pro- cedure, work method or operating technique is used that the manufacturer does not specifically recom- mend, ensure that it is safe for others. Also make sure the procedure, work method or operating tech- nique utilized does not render the generator unsafe.
operating this equipment imprudently, neglect- ing its maintenance or being careless can cause possible injury or death. Permit only responsible and capable persons to install, operate or main- tain this equipment. Potentially lethal voltages are generated by
these machines. Ensure all steps are taken to render the machine safe before attempting to work on the generator. Parts of the generator are rotating and/or hot
during operation. Exercise care near running generators.
Safety 001 Rev. 0 08/05

FIRE HAZARDS • Keep a fire extinguisher near the generator at all times. Do NOT use any carbon tetra-chloride type extinguisher. Its fumes are toxic, and the liquid can deteriorate wiring insulation. Keep the extin- guisher properly charged and be familiar with its use. If there are any questions pertaining to fire extinguishers, consult the local fire department.
Safety 001 Rev. 0 08/05

INTRODUCTION Thank you for purchasing this model of the standby generator set product line.
This symbol points out potential fire hazard.
Every effort was expended to make sure that the information and instructions in this manual were both accurate and current at the time the manual was written. However, the manufacturer reserves the right to change, alter or otherwise improve this product(s) at any time without prior notice.
hazard. The operator is responsible for proper and safe use of the equipment. The manufacturer strongly recom- mends that the operator read this Owner's Manual and thoroughly understand all instructions before using this equipment. The manufacturer also strong- ly recommends instructing other users to properly start and operate the unit. This prepares them if they need to operate the equipment in an emergency.
READ THIS MANUAL THOROUGHLY
If any portion of this manual is not understood, con- tact the nearest Authorized Service Dealer for start- ing, operating and servicing procedures.
OPERATION AND MAINTENANCE
It is the operator's responsibility to perform all safety checks, to make sure that all maintenance for safe operation is performed promptly, and to have the equipment checked periodically by an Authorized Service Dealer. Normal maintenance service and replacement of parts are the responsibility of the owner/operator and, as such, are not considered defects in materials or workmanship within the terms of the warranty. Individual operating habits and usage contribute to the need for maintenance service.
Throughout this publication, and on tags and decals affixed to the generator, DANGER, WARNING, CAUTION and NOTE blocks are used to alert person- nel to special instructions about a particular service or operation that may be hazardous if performed incorrectly or carelessly. Observe them carefully. Their definitions are as follows:
Proper maintenance and care of the generator ensure a minimum number of problems and keep operating expenses at a minimum. See an Authorized Service Dealer for service aids and accessories.
strictly complied with, will result in personal injury or property damage.
Operating instructions presented in this manual assume that the standby electric system has been installed by an Authorized Service Dealer or other competent, qualified contractor. Installation of this equipment is not a “do-it-yourself” project.
strictly complied with, may result in personal injury or property damage.
HOW TO OBTAIN SERVICE
strictly complied with, could result in damage to equipment and/or property.
When the generator requires servicing or repairs, simply contact an Authorized Service Dealer for assistance. Service technicians are factory-trained and are capable of handling all service needs.
After this heading, read explanatory statements
that require special emphasis.
When contacting an Authorized Service Dealer or the factory about parts and service, always supply the complete model number of the unit as given on the front cover of this manual or on the DATA LABEL affixed to the unit.
These safety warnings cannot eliminate the hazards that they indicate. Common sense and strict compli- ance with the special instructions while performing the service are essential to preventing accidents.
Four commonly used safety symbols accompany the DANGER, WARNING and CAUTION blocks. The type of information each indicates is as follows: This symbol points out important safety infor-
To locate the nearest AUTHORIZED SERVICE DEALER, please call this number:
mation that, if not followed, could endanger personal safety and/or property of others. This symbol points out potential explosion
www.generac.com
hazard.
Safety 001 Rev. 0 08/05

IDENTIFICATION RECORD
DATA LABEL
Every generator set has a DATA LABEL that contains important information pertinent to the generator. The data label, which can be found attached to the gen- erator’s lower connection box, lists the unit’s serial number and its rated voltage, amps, wattage capacity, phase, frequency, rpm, power factor, etc.
Generator Model and Serial Number This number is the key to numerous engineering and manufacturing details pertaining to your unit. Always supply this number when requesting service, order- ing parts or seeking information.
Data Label
GENERATOR SET DATA
MODEL
SERIAL
RATED KW
RATED KVA
PHASE
RATED VOLTAGE
RATED AMPS
POWER FACTOR
HERTZ
ALT RPM
ENGINE RPM
PRODUCTION DATE
ALTERNATOR SUBTRANSIENT REACTANCE
ALTERNATOR TRANSIENT REACTANCE
CLASS
ROTOR STATOR WINDING INSULATION AT 25 ° C AMBIENT
GENERAC POWER SYSTEMS, INC.
Identy 002 Rev. A 12/05

EQUIPMENT DESCRIPTION This equipment is a revolving field, alternating cur- rent generator set. It is powered by a gaseous fueled engine operating at 1800 rpm for 4-pole direct drive units, 3600 rpm for 2-pole direct drive units and 2300 - 3000 rpm for quiet drive gear units. See the Specifications section for exact numbers. The unit comes complete with a sound attenuated enclosure, internally mounted muffler, control console, main- line circuit breaker, battery charger, and protective alarms as explained in the following paragraph.
COOLANT RECOMMENDATIONS Use a mixture of half low silicate ethylene glycol base anti-freeze and deionized water. Cooling system capacity is listed in the specifications. Use only deion- ized water and only low silicate anti-freeze. If desired, add a high quality rust inhibitor to the recommended coolant mixture. When adding coolant, always add the recommended 50-50 mixture.
All AC connections, including the power leads from the alternator, 120 volt battery charger input and control connections to the transfer switch are avail- able in the main connection box.
with ethylene glycol base anti-freeze or chro- mium hydroxide (“green slime”) forms and will cause overheating. Engines that have been oper- ated with a chromate base rust inhibitor must be chemically cleaned before adding ethylene glycol base anti-freeze. Using any high silicate anti-freeze boosters or additives will also cause overheating. The manufacturer also recommends that any soluble oil inhibitor is NOT used for this equipment.
the engine is hot or serious burns from boiling liquid or steam could result. Ethylene glycol base antifreeze is poisonous.
ENGINE OIL RECOMMENDATIONS The unit has been filled with 15W-40 engine oil at the factory. Use a high-quality detergent oil classified “For Service CC, SD, SE, SF.” Detergent oils keep the engine cleaner and reduce carbon deposits. Use oil having the following SAE viscosity rating, based on the ambient temperature range anticipated before the next oil change:
Do not use mouth to siphon coolant from the radiator, recovery bottle or any container. Wash hands thoroughly after handling. Never store used antifreeze in an open container because animals are attracted to the smell and taste of antifreeze even though it is poisonous to them.
it has been properly serviced with the recom- mended oil may result in an engine failure.
For temperatures below 32° F, it is strongly recom- mended to use the optional Cold Weather Start Kit (part number listed in the Specification Section). The oil grade for temperatures below 32° F is 5W- 30 synthetic oil.
Equip001 Rev. 0 08/05

ENGINE PROTECTIVE DEVICES The standby generator may be required to operate for long periods of time without an operator on hand to monitor such engine conditions as coolant tempera- ture, oil pressure or rpm. For that reason, the engine has several devices designed to protect it against potentially damaging conditions by automatically shutting down the unit when the oil pressure is too low, the coolant temperature is too high, the coolant level is too low, or the engine is running too fast.
OVERCRANK SHUTDOWN
After a prespecified duration of cranking, this func- tion ends the cranking if the engine has failed to start. The overcrank LED will turn ON. Turn OFF the AUTO/OFF/MANUAL switch, then turn switch back to AUTO to reset the generator control board.
If the fault is not corrected, the overcrank feature will continue to activate.
Engine protective switches and sensors are men- tioned here for the reader’s convenience. Also refer to the applicable control panel manual for additional automatic engine shutdown informa- tion.
HIGH COOLANT TEMPERATURE SWITCH
This switches contacts close if the temperature should exceed approximately 140° C (284° F), initiating an engine shutdown. The generator will automatically restart and the LED will reset once the temperature has returned to a safe operating level.
OVERSPEED SHUTDOWN
A speed circuit controls engine cranking, start-up, operation and shutdown. Engine speed signals are delivered to the circuit board whenever the unit is running. Should the engine overspeed above a safe, preset value, the circuit board initiates an automatic engine shutdown. Contact the nearest Authorized Dealer if this failure occurs.
LOW COOLANT LEVEL SENSOR
Should the engine coolant level drop below the level of the high coolant temperature switch, it is possible for the engine to overheat without automatic shut- down. To prevent such overheating, the engine has a low coolant level sensor. If the level of engine coolant drops below the level of the low coolant level sensor, the engine automatically shuts down.
RPM SENSOR LOSS SHUTDOWN
If the speed signal to the control panel is lost, engine shutdown will occur.
DC FUSE
LOW OIL PRESSURE SWITCH
This fuse is located inside of the control panel. It protects the panel wiring and components from damaging overload. Always remove this fuse before commencing work on the generator. The unit will not start or crank if the fuse is blown. Replace the fuse with one of the same size, type, and rating. (See the exploded views and parts lists at the end of this manual for replacement part number.)
This switch has normally closed contacts that are held open by engine oil pressure during cranking and operating. Should oil pressure drop below the 8 psi range, switch contacts close, and the engine shuts down. The unit should not be restarted until oil is added, and the AUTO/OFF/MANUAL switch must be turned to OFF and then back to AUTO.
EngProt001 Rev. 0 08/05

FUEL SYSTEM
PROPANE VAPOR WITHDRAWAL FUEL SYSTEM
This type of system utilizes the vapors formed above the liquid fuel in the supply tank. Approximately 10 to 20 percent of the tank capacity is needed for fuel expansion from the liquid to the vapor state. The vapor withdrawal system is generally best suited for smaller engines that require less fuel. The installer should be aware of the following:
FUEL REQUIREMENTS
The standby generator may be equipped with one of the following fuel systems:
Recommended fuels should have a Btu content of at least 1,000 Btus per cubic foot for natural gas; or at least 2,520 Btus per cubic foot for LP gas. Ask the fuel supplier for the Btu content of the fuel.
Required fuel pressure for natural gas is 5 inches to 14 inches water column (0.18 to 0.5 psi); and for liquid propane, 5 inches to 14 inches of water column (0.18 to 0.5 psi).
LP FUEL SYSTEM
LP is supplied as a liquid in pressure tanks. It is usually made up of propane, butane, or a mixture of the two gases. Propane tends to vaporize readily even at temperatures as low as -20° F (-29° C). However, butane reverts to its liquid state when temperatures drop below 32° F (0° C).
LP in a liquid withdrawal system must be converted to its gaseous state before it is introduced into the engine carburetor. A vaporizer-converter is generally used to accomplish this. In such a converter, heated engine coolant is ported through the converter to provide the necessary heat for conversion of the fuel from a liquid to a gaseous state.
NATURAL GAS FUEL SYSTEM
Natural gas is supplied in its vapor state. In most cases, the gas distribution company provides piping from the main gas distribution line to the standby generator site. The following information applies to natural gas fuel systems.
FuelSys001 Rev. 0 08/05

SPECIFICATIONS
COOLING SYSTEM
Type Pressurized Closed Recovery Water Pump Belt Driven Fan Speed 2150 rpm Fan Diameter 22 inches Fan Mode Puller Air Flow (inlet air including alternator and combustion air) 3200 ft3/min. Coolant Capacity (2.5 U.S. gal.) Heat Rejection to Coolant 134,000 Btu/h Maximum Operating Air Temp. on Radiator 60° C (150° F) Maximum Ambient Temperature 50° C (140° F)
GENERATOR Type Synchronous Rotor Insulation Class H Stator Insulation Class H Total Harmonic Distortion < 3.5% Telephone Interference Factor (TIF) < 50 Alternator Output Leads 3-phase 4-wire Bearings Sealed Ball Coupling Flexible Disc Load Capacity (Standby Rating) 35kW* * NOTE: Generator rating and performance in accordance with ISO8528-5, BS5514, SAE J1349, ISO3046 and DIN 6271 Standards. KW rating is based on LPG fuel and may derate with natural gas. Excitation System Direct Generator Output Voltage/kW - 60 Hz kW Amp CB Size 120/240V, 1-phase, 1.0 pf 35 146 175 120/208V, 3-phase, 0.8 pf 35 121 150 277/480V, 3-phase, 0.8 pf 35 53 60 Generator Locked Rotor KVA Available @ Voltage Dip of 35% Single-phase or 208, 3-phase 69 KVA 480V, 3-phase 76 KVA
FUEL SYSTEM Type of Fuel Natural Gas, Propane Vapor Carburetor Down Draft Secondary Fuel Regulator Standard Fuel Shut-off Solenoid Standard Operating Fuel Pressure 5 in. - 14 in. Water Column
Fuel Consumption - ft3/hr (Natural Gas/LPV) Exercise 25% 50% 75% 100% Cycle Load 87/34.5 150/59.6 291/115.7 405/160.8 560/222.3
ENGINE Make Generac Model In Line Cylinders and Arrangement 4 Displacement 2.4 Liter Bore 3.41 in. Stroke 3.94 in. Compression Ratio 8.5-to-1 Air Intake System Naturally Aspirated Valve Seats Hardened Lifter Type Hydraulic
ELECTRICAL SYSTEM Battery Charge Alternator 12V, 30 Amp Static Battery Charger 2 Amp Recommended Battery Group 26, 525CCA System Voltage 12 Volts
Voltage Regulator Type Electronic Sensing Single-phase Regulation ± 1% Features V/F Adjustable, Adjustable
Engine Parameters Rated Synchronous RPM 60 Hz, 3600 HP at rated kW 60 Hz, 55
Power Adjustment for Ambient Conditions Temperature Deration 3% for every 10° C above °C 40 1.65% for every 10° above °F 104 Altitude Deration 1% for every 100 m above m 915 3% for every 1000 ft. above ft 3000
Exhaust System Exhaust Flow at Rated Output 60 Hz 360 cfm Exhaust Temperature at Rated Output 1050° F
Combustion Air Requirements (Natural Gas) Flow at rated power, 60 Hz 129 cfm
Governor Type .................................................................................. Electronic Frequency Regulation ...................................................Isochronous Steady State Regulation ......................................................± 0.25%
Engine Lubrication System Type of Oil Pump Gear Oil Filter Full Flow Spin-on, Cartridge Crankcase Oil Capacity 4 U.S. qts.
GenSpec019 Rev. 0 02/06

Figure 1 — Interconnections
NEUTRAL
TO ALTERNATOR
Gen N1 N2 23 194
N1 N2 23 194
GENERATOR CONNECTION BOX
GROUND
TO GENERATOR CONNECTION BOX
120 Volt + Neutral Grd
To Generator Control Panel
CIRCUIT BREAKER SIZE KW VOLTS / AMPS LUG SIZE 35 240 1 Ø 175 #6 to 300 mcm 35 208 3 Ø 150 #6 to 300 mcm 35 480 3 Ø 60 #6 to 300 mcm
Ground Level Concrete Slab STUB-UP AREA See Install Dwg for
COLD WEATHER KIT
For cold climates, optional cold weather kit (part number 0F6148) is recommended. The kit includes:
RECONFIGURING THE FUEL SYSTEM
All models are configured for natural gas or LP vapor from the factory.
1. Turn the main gas supply off. 2. Remove the carburetor fuel hose from the outlet port (Port 1) of the demand regulator (Figure 6.2). 3. Remove the brass hose fitting from the outlet port (Port 1) of the demand regulator. 4. Remove the brass hose fitting with solenoid from Port 2. 5. Install brass hose fitting into Port 2. 6. Install the brass hose fitting with solenoid into Port 1. 7. Connect carburetor gas hose to brass fitting. 8. Tighten all clamps and plugs. 9. Make sure fuel supply is of the proper pressure and type for configuration.
Port 1 is for NG only and Port 2 is for LP vapor only. No provision for dual fuel has been made.
figured properly. Please consult an Authorized Service Dealer with any questions.
GenSpec019 Rev. 0 02/06

GENERATOR AC LEAD CONNECTIONS See “Voltage Codes”. This generator may be rated at any one of three voltages, either single-phase or three-phase. The electrical wires in the unit’s AC con- nection (lower) panel should be installed according to the number of leads and the voltage/phase required for the application. If there are any questions regard- ing lead connection, refer to the wiring diagrams at the back of this manual.
3-PHASE ALTERNATORS
The generator is designed to supply 3-phase electri- cal loads. Electric power is produced in the alterna- tor power windings. These windings were connected at the factory to the main circuit breaker with a “Y” configuration as shown in Figures 7.2 and 7.3.
Voltage codes apply to the type of stator assembly installed on a particular generator.
The rated voltage between circuit breaker terminals E1-E2, E1-E3 and E2-E3 is either 480V or 208V depending on the model.
FOUR-LEAD, SINGLE-PHASE STATOR
Four-lead generators (see Figure 7.1) are designed to supply electrical loads with voltage code “A” (240V, 1-phase, 60 Hz). Electrical power is produced in the stator power windings. These windings were con- nected at the factory to the main circuit breaker as shown in Figure 7.1.
The rated voltage between each circuit breaker termi- nal and the neutral point 00 is either 277V or 120V depending on the model.
The rated voltage between each circuit breaker ter- minal is 240V. The rated voltage between each circuit breaker terminal and the neutral point 00 is 120V.
Figure 7.1 — Four-lead, Single-phase Stator
INTERNAL CONNECTIONS
L-L S4
S6
NEUTRAL
S5
E3 S3
E2 S2
L-N
Figure 7.3 — Stator Power Winding Connections - 3-phase, 120/208V (6 Lead)
E1
S1 S1
S4 S4
00 (NEUTRAL)
S6
S5
S6 S3
S5 S2
E3 E2
S3
S2
L-N
ACConn001 Rev. 0 08/05

INSTALLATION Refer to the separate “Installation Guide QT Product Line” supplied with the unit.
PRIOR TO INITIAL START-UP
PREPARATION BEFORE START-UP The instructions in this section assume that the standby generator has been properly installed, ser- viced, tested, adjusted and otherwise prepared for use by a competent, qualified installation contractor. Be sure to read the “Safety Rules”, as well as all other safety information in this manual, before attempting to operate this (and related) equipment.
be properly prepared for use. Any attempt to crank or start the engine before it has been properly serviced with the recommended types and quantities of engine fluids (oil, coolant, fuel, etc.) may result in an engine failure.
ENGINE COOLANT
Have the engine cooling system properly filled with the recommended coolant mixture. Check the system for leaks and other problems. See “Specifications” and “Coolant” sections.
Before starting the generator for the first time, the installer must complete the following procedures. For follow-up maintenance information and/or service intervals, please refer to the “Maintenance” section and the “Service Schedule”.
BELT TENSION
TRANSFER SWITCH
Check-the engine-fan belt tension and condition prior to placing the unit into service and at recommended intervals. Belt tension is correct when a force of approximately 22 pounds (10 kg), applied midway between pulleys, deflects the belt about 3/8- to 5/8- inch (10 to 16 mm).
If this generator is used to supply power to any elec- trical system normally powered by an electric utility, the National Electrical Code requires that a transfer switch be installed. The transfer switch prevents elec- trical backfeed between two different electrical sys- tems. (For additional information, see the applicable transfer switch manual for this unit.) The transfer switch, as well as the generator and other standby components, must be properly located and mounted in strict compliance with applicable codes, standards and regulations.
ELECTRICAL SYSTEM
Make sure the generator is properly connected to an approved earth ground.
Make sure the generator battery is fully charged, properly installed and interconnected, and ready for use.
FUEL SYSTEM
Check to ensure that there are no loose electrical con- nections. Restrain any loose wires to keep them clear of any moving generator set components.
Make sure the fuel supply system to the genera- tor (a) delivers the correct fuel at the correct pres- sure and (b) is properly purged and leak tested according to code. No fuel leakage is permitted. See “Specifications” for more information.
INITIAL INSPECTION FOR QT GENSET STARTUP Inspect for the following.
GENERATOR SET LUBRICATION
Check the engine crankcase oil level before operating and add oil to the proper level – the dipstick “FULL” mark. Never operate the engine with the oil level below the dipstick “ADD” mark. See “Specifications” and “Engine Oil Recommendations”.
This engine is shipped from the manufacturer with “break-in” oil. This oil should be changed after 30 hours of operation.
Check the oil level in the generator gearbox (if so equipped) prior to initial use and at the intervals indicated by the “Service Schedule.” The recom- mended oil is SAE 90 gear lubricant.
Also, if the engine is equipped with a mechanical gov- ernor, make sure the governor is properly lubricated with clean engine oil.
Install001 Rev. B 01/06

START-UP CHECKLIST
PREPARATION FOR START-UP
Make certain all 3-phase loads are functioning correctly (correct phase rotation). • Reconnect Utility power Transfer switch will transfer back to Utility and
START-UP INSPECTION
When a start-up is performed by an Authorized Service Dealer, a standard three-part form titled “Start-up Inspection for Standby Power Systems” (part no. 067377), should be completed by the instal- lation technician or engineer. See page 1-3 for infor- mation on locating the nearest Authorized Service Dealer. The installer should complete the form and disseminate copies as follows:
Install001 Rev. B 01/06

GENERATOR CONTROL AND OPERATION Refer to the appropriate control panel operator’s manual for this unit.
OPERATING UNIT WITH MANUAL TRANSFER SWITCH If the generator was installed in conjunction with a transfer switch capable of manual operation only, the following procedure applies. A manually operated transfer switch is one that will not provide automatic start-up and does not include an intelligence circuit.
ENGINE START-UP AND TRANSFER
RETRANSFER AND SHUTDOWN
For additional information, refer to the applicable control panel manual for this unit, as well as any lit- erature pertaining to the specific transfer switch.
For additional information, refer to the applicable control panel manual for this unit, as well as any lit- erature pertaining to the specific transfer switch.
To transfer the load back to the utility power source and shut down the generator, follow these direc- tions:
AUTO/OFF/MANUAL switches (if so equipped) must be set properly, or the generator will crank and start as soon as the utility power to the transfer switch is turned off. Refer to applicable control panel and transfer switch manuals for more information. Do not proceed until certain that utility source
voltage is available to the transfer switch and the transfer switch main contacts are set to UTILITY. Do not attempt manual operation until all power
supplies to the transfer switch have been posi- tively turned off, or extremely dangerous - pos- sibly lethal - electrical shock will result. Transfer switch enclosure doors should be kept
OPERATING UNIT WITH AUTOMATIC TRANSFER SWITCH If the generator has been installed with an automatic transfer switch, such as an RTS, HTS, or GTS-type transfer switch, the engine may be started and stopped automatically or manually.
closed and locked. Only authorized personnel should be allowed access to the transfer switch interior. Extremely high and dangerous voltages are present in the transfer switch. In order to transfer load from the utility source to the generator, follow these directions:
Refer to the applicable manual for your trans- fer switch and to “Transfer Switch Start Signal Connections”. In addition, please note the dangers under “Engine Start-up and Transfer.”
Oper001 Rev. 0 08/05

MAINTENANCE PERFORMED BY AUTHORIZED SERVICE FACILITIES
COOLING SYSTEM Air intake and outlet openings in the generator com- partment must be open and unobstructed for contin- ued proper operation. This includes such obstruc- tions as high grass, weeds, brush, leaves and snow.
Without sufficient cooling and ventilating air flow, the engine/generator quickly overheats, which causes it to shut down. (See the installation diagram.)
extremely hot and remains hot after shutdown. High grass, weeds, brush, leaves, etc. must remain clear of the exhaust. Such materials may ignite and burn from the heat of the exhaust system.
EVERY THREE MONTHS
OVERLOAD PROTECTION FOR ENGINE DC ELECTRICAL SYSTEM Engine cranking, start up and running are controlled by a solid state Engine Controller circuit board. Battery voltage is delivered to that circuit board via a 15 amp fuse. These overcurrent protection devices will open if the circuit is overloaded.
ONCE EVERY SIX MONTHS
ONCE ANNUALLY
melts, find the cause of the overload before resetting the circuit breaker or replacing the fuse.
FIRST 30 OPERATING HOURS
CHECKING FLUID LEVELS
CHECK ENGINE OIL
FIRST 100 OPERATING HOURS
Check engine crankcase oil level (Figure 10.1) at least every 20 hours of operation, or prior to use.
EVERY 500 OPERATING HOURS
EVERY 800 OPERATING HOURS
Maint012 Rev. 0 04/06

Figure 10.1 - Oil Dipstick and Oil Fill Cap
EXERCISE SYSTEM
Start the generator engine at least once every seven days and let it run at least 20 minutes. See “Weekly Exercise Cycle”.
INSPECT COOLING SYSTEM
Oil Dipstick
CHECK ENGINE COOLANT LEVEL
See “Checking Fluid Levels”.
PERFORM VISUAL INSPECTION
BATTERY FLUID
Complete a thorough visual inspection of the entire engine-generator monthly. Look for obvious damage, loose, missing or corroded nuts, bolts and other fas- teners. Look for fuel, oil or coolant leaks.
Check battery electrolyte fluid based on the Maintenance Schedule. Fluid should cover separa- tors in all battery cells. If fluid level is low, add dis- tilled water to cover tops of separators. DO NOT USE TAP WATER IN BATTERY.
INSPECT EXHAUST SYSTEM
Inspect the exhaust system at least once every three months. Check all exhaust system pipes, mufflers, clamps, etc. for condition, tightness, leaks, security, damage.
ENGINE COOLANT
Check coolant level in coolant recovery bottle. See Specifications.
CHECK FAN BELT
INSPECT ENGINE GOVERNOR
MAINTENANCE OWNER/ OPERATOR CAN PERFORM
Visually inspect electronic governor.
CHECK ENGINE OIL LEVEL
qualified service facilities should adjust the governor. Excessively high operating speeds are dangerous and increase the risk of personal injury. Low speeds impose a heavy load on the engine when adequate engine power is not available and may shorten engine life. Correct rated frequency and voltage are supplied only at the proper governed speed. Some connected electrical load devices may be damaged by incor- rect frequency and/or voltage. Only qualified service technicians should adjust the governed speed.
Refer to “Checking Fluid Levels”.
CHECK BATTERY
Maint012 Rev. 0 04/06

CHANGING ENGINE OIL
Figure 10.3 – Engine Air Cleaner
Refer to maintenance performed by authorized service facilities for engine oil and filter change frequencies.
Drain the oil while the engine is still warm from run- ning. This means warm up the engine, shut it down and drain immediately as follows:
(Doors Removed for Clarity)
SPARK PLUGS
Reset the spark plug gap or replace the spark plugs as necessary (Figure 10.4).
1. Clean the area around the base of the spark plugs to keep dirt and debris out of the engine. Clean by scraping or washing using a wire brush and commercial solvent. Do not blast the spark plugs to clean. 2. Remove the spark plugs and check the condition. Replace the spark plugs if worn or if reuse is questionable. See the “Service Schedule,” Section 6, for recommended inspection. 3. Check the spark plug gap using a wire feeler gauge. Adjust the gap to 1.07-1.17 mm (0.042- 0.046 inch) by carefully bending the ground elec- trode (Figure 10.4).
(0.042 - 0.046 inch)
After refilling the crankcase with oil, always
check oil level on dipstick. NEVER OPERATE ENGINE WITH OIL BELOW THE DIPSTICK “ADD” MARK. 7. Start engine and check for oil leaks.
CHANGING THE ENGINE AIR CLEANER
COOLANT CHANGE
To replace the engine air cleaner, remove the air cleaner cover and replace the air filter making sure it is positioned properly before reattaching the cover (Figure 10.3).
Every year, have an Authorized Service Facility drain, flush and refill the cooling system. See “Specifications” for cooling system recommendations.
See the “Service Schedule,” for air cleaner mainte- nance.
Maint012 Rev. 0 04/06
Air Cleaner

MISCELLANEOUS MAINTENANCE
BATTERY MAINTENANCE
The battery should be inspected per Section 4.7, Scheduled Maintenance. The following procedure should be followed for inspection:
CLEANING THE GENERATOR
Keep the generator as clean and as dry as possible. Dirt and moisture that accumulates on internal gen- erator windings have an adverse effect on insulation resistance.
Periodically clean generator exterior surfaces. A soft brush may be used to loosen caked on dirt. Use a vacuum system or dry, low pressure air to remove any accumulations of dirt. The generator is housed inside an all-weather enclosure, clean the enclosure with a soft, damp cloth or sponge and water.
Once each year have the generator cleaned and inspected by an Authorized Service Dealer. That dealer will use dry, low pressure air to clean internal windings. Parts inside the control console should be cleaned and inspected at this time as well.
gas. This gas can form an explosive mixture around the battery for several hours after charg- ing. The slightest spark can ignite the gas and cause an explosion. Such an explosion can shat- ter the battery and cause blindness or other injury. Any area that houses a storage battery must be properly ventilated. Do not allow smok- ing, open flame, sparks or any spark producing tools or equipment near the battery. Battery electrolyte fluid is an extremely corro-
Finally, have the insulation resistance of stator and rotor windings checked. If insulation resistances are excessively low, the generator may require drying.
BATTERY
All lead-acid storage batteries discharge when not in use. Refer to specific instructions and warnings that accompany the battery. If such information is not available, observe the following precautions when handling a battery:
sive sulfuric acid solution that can cause severe burns. Do not permit fluid to contact eyes, skin, clothing, painted surfaces, etc. Wear protective goggles, protective clothing and gloves when handling a battery. If fluid is spilled, flush the affected area immediately with clear water. Do not use any jumper cables or booster battery
to crank and start the generator engine. If the battery has completely discharged, remove it from the generator for recharging.
the OFF position, before connecting the battery cables. If the switch is set to AUTO or MANUAL, the generator can crank and start as soon as the battery cables are connected. Be sure the 120VAC power supply to the battery
is turned OFF, or sparking may occur at the bat- tery posts as the cables are attached and cause an explosion.
BATTERY REPLACEMENT
When replacing batteries, use the same number and the type of battery that follows:
BCI Group No. CCA 26 525 @ 0 deg. F
The BCI number should be located directly on the battery.
Maint012 Rev. 0 04/06

SERVICE SCHEDULE
30 KW - 150 KW STANDBY GAS ENGINE DRIVEN GENERATOR SETS
The following is a recommended maintenance schedule for standby gas engine driven generator sets from 30kW to 150 kW in size. The established intervals in the schedule are the maximum recommended when the unit is used in an average service application. They will need to be decreased (performed more frequently) if the unit is used in a severe application. Use calendar time, from the previous maintenance interval to determine the next required maintenance interval.
1 An early inspection of the generator set to insure it is ready to operate when required and to identify any poten- tial problem areas.
This inspection may be performed by the end user providing the following safety steps are taken to prevent the engine from starting automatically without warning:
To prevent injury, perform the following steps in the order indicated before starting any maintenance:
The battery charger must be turned off BEFORE removing the battery cable to prevent an over current condition from burning out sensitive control panel components and circuits.
Following all maintenance, reverse these steps to insure the unit is returned to standby setup for normal
operation when required.
2 A wear-in service inspection of the generator set to insure it is ready to operate and carry the load when required, and to identify any potential problem areas.
Performed ONLY ONCE following the first three months or the first 30 hours of operation after purchase of the unit.
This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge to accomplish and should be performed only by an Authorized Service Dealer.
3 An operational inspection of the generator set to insure it is ready to operate and carry the load when required, and to identify any potential problem areas.
Performed semi-annually or following each 50 hours of operation of the unit.
This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge to accomplish and should be performed only by an Authorized Service Dealer.
4 A mid-level inspection of the generator set to insure it is ready to operate and carry the load when required, and to identify any potential problem areas.
Performed annually or following each 100 hours of operation of the unit.
This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge to accomplish and should be performed only by an Authorized Service Dealer.
5 A comprehensive inspection of the generator set to insure it is properly serviced and ready to operate and carry the load when required, and to identify any potential problem areas.
Performed annually or following each 250 hours of operation of the unit.
This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge to accomplish and should be performed only by an Authorized Service Dealer.
SrvSchd001 Rev. A 09/05

Maintenance Level 1 Level 2 Level 3 Level 4 Level5 Tasks Recom- Task Required Task Required Task Task Required Task mended Comp. to be done Comp. to be done Comp. Required Comp. to be done Comp. to be done (Date- 3 months/ (Date- Semi- (Date- to be done (Date- Bi- (Date- monthly/ Initials) Break-in Initials) annually/ Initials) Annually/ Initials) annually/ Initials) 10 hrs. 30 hrs. 50 hrs. 100 hrs. 250 hrs. 1. Disable the unit from operating per the first page warning. 2. Check the engine oil level. Adjust as necessary. 3. Check the engine coolant level. Adjust as necessary. 4. Check the engine coolant thermal protection level. Correct as necessary. 5. Check the natural gas delivery system for leaks and correct pressure on gas engine driven units. Tighten connections as necessary. 6. Check the air inlets and outlets for debris. Clean as necessary. 7. Check the battery electrolyte level and specific gravity if accessible. Adjust as necessary. 8. Check the battery posts, cables, and charger for loose connections, corrosion, and proper operation. Correct as necessary. 9. Check the unit wiring for loose connections, corrosion, and damage. Correct as necessary.
SrvSchd001 Rev. A 09/05

Maintenance Level 1 Level 2 Level 3 Level 4 Level5 Tasks Recom- Task Required Task Required Task Task Required Task mended Comp. to be done Comp. to be done Comp. Required Comp. to be done Comp. to be done (Date- 3 months/ (Date- Semi- (Date- to be done (Date- Bi- (Date- monthly/ Initials) Break-in Initials) annually/ Initials) Annually/ Initials) annually/ Initials) 10 hrs. 30 hrs. 50 hrs. 100 hrs. 250 hrs. 10. Check the engine accessory drive belts and fan coupling device if equipped for correct tension, wear, weather cracking, and damage. Replace as necessary. 11. Check the engine valve clearance. Adjust as necessary. 12. Visually inspect the unit looking for leaks, wear or damage, loose connections or components, and corrosion. Correct as necessary. 13. Test the engine and transfer switch safety devices. Correct and/or adjust as necessary. 14. Initiate an automatic start and transfer of the unit to site load and exercise it for at least 1 hour looking for leaks, loose connections or components, and abnormal operating conditions. Correct as necessary. 15. Replace the engine accessory drive belts. 16. Check gearbox oil level (if equipped). 17. Change gearbox oil (if equipped).
SrvSchd001 Rev. A 09/05

Maintenance Level 1 Level 2 Level 3 Level 4 Level5 Tasks Recom- Task Required Task Required Task Task Required Task mended Comp. to be done Comp. to be done Comp. Required Comp. to be done Comp. to be done (Date- 3 months/ (Date- Semi- (Date- to be done (Date- Bi- (Date- monthly/ Initials) Break-in Initials) annually/ Initials) Annually/ Initials) annually/ Initials) 10 hrs. 30 hrs. 50 hrs. 100 hrs. 250 hrs. 18. Start and exercise the unit at full rated load (use a load bank if the site load is not enough) for at least 2 hours looking for leaks, loose connections or components, and abnormal operating conditions. Correct as necessary. 19. Perform an engine oil analysis (send a sample to a lab for results). Change the engine oil and filters if the analysis results indicate this is required. 20. Change the engine oil. 21. Replace the engine oil filter(s). 22. Replace engine spark plugs. Clean and re-gap or replace as necessary. 23. Replace the engine air filter(s). 24. Perform a 5 minute no-load operational run of the unit looking for any post service problems. 25. Return the unit to standby setup for operation when required.
SrvSchd001 Rev. A 09/05

TROUBLESHOOTING GUIDE
PROBLEM CAUSE CORRECTION
Engine won’t crank. 1. 15 amp fuse blown. 1. Replace fuse. 2. Loose or corroded or defective 2. Tighten, clean or replace battery cables. battery cables as necessary. 3. Defective starter contactor. 3. Replace contactor.* 4. Defective starter motor. 4. Replace starter motor.* 5. Dead or Defective Battery. 5. Remove, change or replace battery. 6. 5 amp fuse blown. 6. Replace fuse.* Engine cranks but won't start 1. Out of fuel. 1. Replenish fuel. 2. Fuel solenoid (FS) is defective 2. Replace solenoid.* 3. Open Wire #14A from Engine Control 3. Reconnect wire. circuit board. 4. Spark plugs defective. 4. Clean, regap or replace plugs. 5. Door on tank not closed. 5. Close door on tank. Engine starts hard, runs rough. 1. Flame arrestor (air cleaner) plugged or 1. Clean or replace as needed. damaged. 2. Plugged fuel line. 2. Unclog fuel line. 3. Defective spark plugs. 3. Clean, regap or replace plugs. 4. Fuel pressure incorrect. 4. Confirm fuel pressure to regulator is as recommended in SPECIFICATIONS. Engine starts then shuts down. 1. Engine oil level is low. 1. Check oil and add oil as needed. 2. Engine is overheated. 2. Check cooling system for leaks. 3. Defective Low Oil Pressure Switch 3. Replace switch.* 4. Defective Coolant Temperature Switch 4. Replace switch.* 5. Defective Control Module circuit board. 5. Replace board.* 6. Coolant Level is Low. 6. Repair leak - Add coolant. 7. Defective Low Coolant Level Switch 7. Replace Switch.* AUTO/OFF/MANUAL Switch at OFF, 1. Defective AUTO/OFF/MANUAL switch 1. Replace switch.* engine continues to run 2. Open/disconnected wire #15A between 2. Reconnect/close wire. AUTO/OFF/MANUAL switch and Control Module circuit board. 3. Defective Control Module circuit board 3. Replace board.* No AC output from generator. 1. Check main line circuit breaker. 1. Reset to ON or CLOSED. 2. Check circuit breaker & fuses. 2. Reset and replace, if necessary. 3. Transfer switch set to NORMAL position 3. Set to GENERATOR position. 4. Generator internal failure. 4. * 5. Thermal circuit breaker open. 5. Auto-reset - Wait 5 min. and attempt restart.
*Contact the nearest Authorized Dealer for assistance.
Trblsht001 Rev. 0 08/05






1 0F3137 1 PAN CB CONN BOX 2 0F3188 1 STAND RH CONTROL 3 0F3189 1 STAND LH CONTROL 4 023484N 1 BUSHING SNAP SB-2.5-31 (3) 5 0F6366B 1 / 2 XFMR DUAL 120V/16V (FOR 120/240V & 277/480V UNITS) 0F6366A 1 XFMR DUAL 104V/16V (FOR 120/208V UNITS) (3) 6 043180 2 / 4 WASHER FLAT M4 (3) 7 022264 2 / 4 WASHER LOCK #8-M4 (3) 8 0C3990 2 / 4 SCREW PHTT M4-0.7 X 10 ZYC (1) 9 057701 REF BLOCK TERM 20A 8 X 6 X 1100V 10 022155 4 WASHER LOCK #6 11 0C2428 4 SCREW PHTT #6-32 X 1/2 ZYC 12 0F3824 1 DECAL UTIL SENSE/CUST CONN 13 0A9457 1 DECAL NEUTRAL 14 057073 2 JUNCTION BLOCK 3/8-16 (2) 15 0D5466 REF BUS BAR NEUTRAL BLOCK 390 (2) 16 0A7822 REF LUG SLDLSS 600/250-1/0 X 1/4-28 17 022237 2 WASHER LOCK 3/8 18 022241 2 NUT HEX 3/8-16 STEEL 19 049226 4 WASHER LOCK M5 20 0C2266 4 SCREW PHTT M5-0.8 X 16 ZYC 21 0C2454 8 SCREW THF M6-1 X 16 N WA Z/JS 23 022473 8 WASHER FLAT 1/4-M6 ZINC 24 022097 4 WASHER LOCK M6-1/4 (1) 26 0D4698 REF BLOCK TERM 20A 6 X 3 X 1100V 27 0F4464 1 DECAL CUST CONN 120V UTILITY 28 025433 1 LUG SLDLSS #6-14 X 13/64 CU 29 024469 1 SCREW HHTT #10-32 X 3/8 CZ 30 067210A 1 DECAL GROUND LUG 31 0D6029 4 SCREW HHTT M6-1.0 X 16 ZYC 32 081008 1 GROMMET 1.25 X .25 X .75 33 077043J 1 CONDUIT FLEX 2.0" ID (36” LG) 34 051713 2 WASHER FLAT M5 35 0F6156 1 PLATE WIRE SNGL GALV 36 029289 1 TAPE ELEC 1/2 FOAM (AS REQ’D) 37 047411 4 SCREW HHC M6-1.0 X 16 G8.8 (4) 38 064153B 2 WIRE JUMPER TRANSFORMER (NOT SHOWN) (5) 39 0G0770 1 HARNESS, TRANSFORMER ADAPTER
3) UL CIRCUIT BREAKER (JD+LD) A 0F3329 1 COVER JD/LD CB SHRT STAND B 065469 1 DECAL DANGER HIGH VOLTAGE C 0D5577 1 CB 0300A 3P 600V S JD6 LL D 0F2353 2 INSULATOR CIRCUIT BR. JD/LD E 022770 4 SCREW RHM 1/4-20 X 3 F 022473 4 WASHER FLAT 1/4-M6 ZINC G 022097 4 WASHER LOCK M6-1/4 H 022127 4 NUT HEX 1/4-20 STEEL J 0C2454 7 SCREW THF M6-1 X 16 N WA Z/JS K 029289 1 TAPE ELEC 1/2 FOAM (AS REQ’D) L 0F1733 1 DECAL CUSTOMER CONNECT INSIDE
4) UL CIRCUIT BREAKER (QN) A 0F8135 1 COVER QN FRM CB B 065469 1 DECAL, DANGER HIGH VOLTAGE C 0E7283 - CB 0150A 2P 240V S QN2 LL 0E7284 - CB 0175A 2P S QN2 LL 240V D 0E3664 1 BASE, QN CIRCUIT BREAKER E 074908 2 SCREW HHTT M5-0.8 X 10 BP F 0F8140 1 COVER QN CB DISH G 036261 4 RIVET POP .125 X .275 SS H 0C2454 7 SCREW THF M6-1X16 N WA Z/JS J 029289 1 TAPE ELEC 1/2 FOAM (AS REQ’D) K 0F1733 1 DECAL CUSTOMER CONNECT INSIDE
(1) ITEM INCLUDED WITH HARNESS (2) ITEM INCLUDED WITH 0D5464B (3) ITEM QTY. DOUBLES FOR 277/480V (4) ITEM USED WITH 277/480V UNITS ONLY (5) ITEM USED WITH 208V UNITS ONLY
1) UL CIRCUIT BREAKER (ED) A 0F3328 1 COVER ED CB SHORT STND B 065469 1 DECAL DANGER HIGH VOLTAGE C 0D5552 1 CB 0050A 3P 480V S ED4 LL 0D5554 - CB 0070A 3P 480V S ED4 LL 0D5556 - CB 0090A 3P 480V S ED4 LL 0D9693 - CB 0125A 3P 480V S ED4 LL D 0F0492 1 INSULATOR CB S (ED-3P) E 048927 4 SCREW RHM #10-32 X 4-1/2 F 023897 4 WASHER FLAT #10 ZINC G 022152 4 WASHER LOCK #10 H 022158 4 NUT HEX #10-32 STEEL J 0C2454 7 SCREW THF M6-1 X 16 N WA Z/JS K 029289 1 TAPE ELEC 1/2 FOAM (AS REQ’D) L 0F1733 1 DECAL CUSTOMER CONNECT INSIDE
2) UL CIRCUIT BREAKER (FD) A 0F3138 1 COVER CB CONN BOX B 065469 1 DECAL DANGER HIGH VOLTAGE C 0D5572 1 CB 0150A 3P 600V S FD6 LL 0D5573 - CB 0175A 3P 600V S FD6 LL 0D5574 - CB 0200A 3P 600V S FD6 LL 0D5575 - CB 0225A 3P 600V S FD6 LL 0D5576 - CB 0250A 3P 600V S FD6 LL D 0F0199 1 INSULATOR CB FD FRAME 30MIL E 081320 4 SCREW SHC 1/4-20 X 4.5 G8.8 NZ F 022473 4 WASHER FLAT 1/4-M6 ZINC G 022097 4 WASHER LOCK M6-1/4 H 022127 4 NUT HEX 1/4-20 STEEL J 0C2454 7 SCREW THF M6-1 X 16 N WA Z/JS K 029289 1 TAPE ELEC 1/2 FOAM (AS REQ’D) L 0F1733 1 DECAL CUSTOMER CONNECT INSIDE



5) UL CIRCUIT BREAKER (QJ-2P) A 0F8137 1 COVER QJ 2P FRM CB B 065469 1 DECAL, DANGER HIGH VOLTAGE C 0E7994 - CB 0225A 240V 2P S QJ22 D 0F8136 1 COVER QJ 2P CB DISH E 036261 4 RIVET POP .125 X .275 SS F 022473 2 WASHER FLAT 1/4-M6 ZINC G 022097 2 WASHER LOCK M6-1/4 H 022127 2 NUT HEX 1/4-20 STEEL J 0F8139 1 INSUL CB 2P QJ K 0C2454 7 SCREW THF M6-1 X 16 N WA Z/JS L 022237 2 WASHER LOCK 3/8 M 048527 2 SCREW SHC 3/8-16 X 3/4 G8.8 NZ N 029289 1 TAPE ELEC 1/2 FOAM (AS REQ’D) P 022770 2 SCREW RHM 1/4-20 X 3 Q 0F1733 1 DECAL CUSTOMER CONNECT INSIDE
(1) HARDWARE FOR MTG. CB TERMINAL COVERS IS SUPPLIED WITH CIRCUIT BREAKERS.
(2) 2/3 QTY. 2 POLE & 3 POLE CB.
6) UL CIRCUIT BREAKER (225AF) A 0F4185 1 COVER CB C2-C4 225AF B 065469 1 DECAL DANGER HIGH VOLTAGE C 0F4165$ REF CIRCUIT BREAKERS 200A FRAME D 0F4186 1 COVER CB DISH 225AF E 036261 4 RIVET POP .125 X .275 SS F 053640 4 SCREW RHM #8-32 X 3-1/4 G 038150 4 WASHER FLAT #8 ZINC H 022264 4 WASHER LOCK #8-M4 J 022471 4 NUT HEX #8-32 STEEL K 029289 2 TAPE ELEC 1/2 FOAM L 0F1733 1 DECAL CUSTOMER CONNECT INSIDE M 022129 9 WASHER LOCK M8-5/16 N 0F8432 1 INSULATOR CB 225AF P 0C2454 7 SCREW THF M6-1 X 16 N WA Z/JS R 0F8451 3 LUG SLDLSS 300 MCM-6 AL/CU S 049897 9 SCREW SHC M8-1.25 X 20 G8 T 022145 6 WASHER FLAT 5/16-M8 ZINC U 045771 3 NUT HEX M8-1.25 G8 CLEAR ZINC V 0F8843 3 BUS BAR 200A LUG ADAPTOR (1) W W/CB 2 TERMINAL COVER CB
7) UL CIRCUIT BREAKER (400AF) A 0F4187 1 COVER CB C2-C4 400AF B 065469 1 DECAL DANGER HIGH VOLTAGE C 0F4166$ REF CIRCUIT BREAKERS 400A FRAME D 0F1733 1 DECAL CUSTOMER CONNECT INSIDE E 042419 4 SCREW RHM 10-32 X 4 F 023897 4 WASHER FLAT #10 ZINC G 022152 4 WASHER LOCK #10 H 022158 4 NUT HEX #10-32 STEEL J 0C2454 7 SCREW THF M6-1 X 16 N WA Z/JS K 029289 1 TAPE ELEC 1/2 FOAM (2) L 052647 2/3 SCREW SHC M10-1.5 X 25 G12.9 (2) M 046526 2/3 WASHER LOCK M10 N W/CB 3 BUS BAR CB ADAPTER 225-400 A P 0A7822 3 LUG SLDLSS 600/250-1/0 X 1/4-28 (1) S W/CB 2 TERM COVER CB T 023334 6 SCREW HHC 1/4-28 X 1/2 G5 U 022097 6 WASHER LOCK M6-1/4 V 022473 6 WASHER FLAT 1/4-M6 ZINC (2) W W/CB 2/3 SCREW SHC M10-1.5 X 25 G12.9 (2) X W/CB 2/3 WASHER LOCK M10






COMPONENTS INCLUDED IN 0F9696E 1 0F1823A 1 ENCL HSB CONTROL PANEL 2 0F3078 1 COVER CONTROL PANEL 3 0F2606 1 HINGE CONTINUOUS H-PANEL 4 036261 6 RIVET POP .125 X .275 SS 5 043181 4 SCREW PHM M3-0.5 X 10MM 6 052777 7 WASHER FLAT M3 7 0F8710B 1 ASSY PCB CPL2 CTRLR 3600 RPM 8 0F1262 4 HOLDER, FUSE WICKMANN 178.6150 9 0F1263 1 ADPTR,RH SIDE WICKMAN 178.6191 10 0F1264 1 ADPTR,LH SIDE WICKMAN 178.6192 11 0F1725C 1 ASSY PCB 2AMP 12V UL BATT CHGR 12 067680 1 ASSY VOLTAGE REGULATOR 60HZ 13 0E6875A 2 RELAY, 12VDC C FORM W/DIODE 14 055911 1 BLOCK TERM 20A 12 X 6 X 1100V 15 0F5459 1 DECAL CPL CONTROL PANEL FUSES 16 0E3161 1 ASSY PCB BOSCH GOV DRIVER 17 0F5090 1 ASSY PCB SCR BRIDGE 18 0F5462 1 DECAL CPL 3.9L TB1 19 0A5062J 4 SPACER 9.5H 3.2 ID 20 029673 1 DIO BRIDGE 25A 600V 21 048467 1 CIRCT BRK 7 X 1 ETA 46-500-P 22 0F1958 1 PLATE,HARNESS CLAMP 23 082573 1 SWITCH RKR DPST 125V SPD 24 0E4494 1 SWITCH RKR DPDT ON-OFF-ON 25 0F3215 1 DECAL, CONTROL HSB 26 0F6305 3 SEAL COVER 3.18X12.7X382 27 0F6305A 1 SEAL COVER 3.18X12.7X283 28 0F5886 3 SCREW HHPM M5-0.8 X 12 29 051713 12 WASHER FLAT M5 30 049226 12 WASHER LOCK M5 31 0F5752F 1 RES WW 15R 5% 25W QK CONN 32 0F5884 2 SCREW PHTT M3.5-0.6 X 10 33 0F5896 2 SCREW PHTT M3.5-0.6 X 16 34 0C2265 4 SCREW PHTT M4-0.7 X 12 ZYC 35 0C3990 2 SCREW PHTT M4-0.7 X 10 ZYC 36 091526 4 SCREW PPHM M5-0.8 X 12 ZNC 37 051716 9 NUT HEX M5-0.8 G8 CLEAR ZINC 38 079224 2 SCREW PPHM M5-0.8 X 30 SS 39 075476 2 SCREW PPHM M4-0.7 X 16 40 043180 2 WASHER FLAT M4 41 022264 2 WASHER LOCK #8-M4 42 051715 2 NUT HEX M4-0.7 G8 YEL CHR 43 043182 7 WASHER LOCK M3 44 051714 7 NUT HEX M3-0.5 G8 YEL CHR 45 0F3192 1 SUPPORT ANGLE PCB 46 0E7403C 1 FUSE ATO TYPE 15 AMP (BLUE) 47 0F9785 1 HARN 3600RPM R200 CONTROL PNL
COMPONENTS INSTALLED PER THIS DRAWING A 056739 1 RELAY SOLENOID 12VDC PNL MNT B 022287 2 SCREW HHC 1/4-20 X 3/4 G5 C 022473 4 WASHER FLAT 1/4-M6 ZINC D 022097 2 WASHER LOCK M6-1/4 E 022127 2 NUT HEX 1/4-20 STEEL F 0F6145 A/R SEAL WEATHER .45"DIA G 0F2627A 1 COVER CONTROL PANEL SIDE H 091526 4 SCREW PPHM M5-0.8 X 12 ZNC J 049226 4 WASHER LOCK M5 K 051713 4 WASHER FLAT M5




COMPONENTS INCLUDED IN 0G1290E 1 0F1823A 1 ENCL HSB CONTROL PANEL 2 0F3078 1 COVER CONTROL PANEL 3 0F2606 1 HINGE CONTINUOUS H-PANEL 4 036261 6 RIVET POP .125 X .275 SS 5 043181 4 SCREW PHM M3-0.5 X 10MM 6 052777 7 WASHER FLAT M3 7 0G1303B 1 ASSY PCB CPL2A CTRLR 3600 RPM 8 0F1262 4 HOLDER, FUSE WICKMANN 178.6150 9 0F1263 1 ADPTR,RH SIDE WICKMAN 178.6191 10 0F1264 1 ADPTR,LH SIDE WICKMAN 178.6192 11 0F1725C 1 ASSY PCB 2AMP 12V UL BATT CHGR 12 067680 1 ASSY VOLTAGE REGULATOR 60HZ 13 0E6875A 2 RELAY, 12VDC C FORM W/DIODE 14 055911 1 BLOCK TERM 20A 12 X 6 X 1100V 15 0F5459 1 DECAL CPL CONTROL PANEL FUSES 16 0E3161 1 ASSY PCB BOSCH GOV DRIVER 17 0F5090 1 ASSY PCB SCR BRIDGE 18 0F5462 1 DECAL CPL 3.9L TB1 19 0A5062J 4 SPACER 9.5H 3.2 ID 20 029673 1 DIO BRIDGE 25A 600V 21 048467 1 CIRCT BRK 7 X 1 ETA 46-500-P 22 0F1958 1 PLATE,HARNESS CLAMP 23 082573 1 SWITCH RKR DPST 125V SPD 24 0E4494 1 SWITCH RKR DPDT ON-OFF-ON 25 0F3215 1 DECAL, CONTROL HSB 26 0F6305 2 SEAL COVER 3.18X12.7X382 27 0F6305A 1 SEAL COVER 3.18X12.7X283 28 0F5886 3 SCREW HHPM M5-0.8 X 12 29 051713 12 WASHER FLAT M5 30 049226 12 WASHER LOCK M5 31 0F5752F 1 RES WW 15R 5% 25W QK CONN 32 0F5884 2 SCREW PHTT M3.5-0.6 X 10 33 0F5896 2 SCREW PHTT M3.5-0.6 X 16 34 0C2265 4 SCREW PHTT M4-0.7 X 12 ZYC 35 0C3990 2 SCREW PHTT M4-0.7 X 10 ZYC 36 091526 4 SCREW PPHM M5-0.8 X 12 ZNC 37 051716 9 NUT HEX M5-0.8 G8 CLEAR ZINC 38 079224 2 SCREW PPHM M5-0.8 X 30 SS 39 075476 2 SCREW PPHM M4-0.7 X 16 40 043180 2 WASHER FLAT M4 41 022264 2 WASHER LOCK #8-M4 42 051715 2 NUT HEX M4-0.7 G8 YEL CHR 43 043182 7 WASHER LOCK M3 44 051714 7 NUT HEX M3-0.5 G8 YEL CHR 45 0F3192 1 SUPPORT ANGLE PCB 46 0E7403C 1 FUSE ATO TYPE 15 AMP (BLUE) 47 0F9785 1 HARN 3600RPM R200 CONTROL PNL
COMPONENTS INSTALLED PER THIS DRAWING A 056739 1 RELAY SOLENOID 12VDC PNL MNT B 022287 2 SCREW HHC 1/4-20 X 3/4 G5 C 022473 4 WASHER FLAT 1/4-M6 ZINC D 022097 2 WASHER LOCK M6-1/4 E 022127 2 NUT HEX 1/4-20 STEEL F 0F6145 A/R SEAL WEATHER .45"DIA G 0F2627A 1 COVER CONTROL PANEL SIDE H 091526 4 SCREW PPHM M5-0.8 X 12 ZNC J 049226 4 WASHER LOCK M5 K 051713 4 WASHER FLAT M5




1 0F9517 1 WELDMENT FRAME 2.4L C2 2 052860 4 NUT FLANGED HEX M12-1.75 3 052251 5 DAMPENER VIBRATION 40 BLUE 4 052257 5 SPACER .49 X .62 X 1.87 PWDR/ZNC 5 052252 5 DAMPENER VIBRATION 6 052259 5 WASHER FLAT M12 7 052891 5 SCREW HHC M12-1.75 X 80 G8.8 8 0536210410 1 ASSY WIRE 14.00" 9 042909 1 SCREW HHC M8-1.25 X 30 G8.8 10 047411 1 SCREW HHC M6-1.0 X 16 G8.8 11 055414 1 LUG SLDLSS #2-#8 X 17/64 CU 12 022447 1 WASHER SHAKEPROOF INT 1/4 13 022097 1 WASHER LOCK M6-1/4 14 022473 2 WASHER FLAT M6-1/4 ZINC 15 049813 1 NUT HEX M6 -1.0 G8 YEL CHR 16 022261 1 WASHER SHAKEPROOF INT 3/8 17 0F9597A 1 SUPPORT LH ENGINE 2.4L 18 045764 1 SCREW HHTT M4-0.7 X 8 BP 19 062963 4 SCREW HHC M10-1.25 X 30 G8.8 20 022302 4 WASHER LOCK 7/16 21 022131 4 WASHER FLAT 3/8-M10 ZINC 22 065852 1 SPRING CLIP HOLDER .37-.62 23 0F9597 1 SUPPORT RH ENGINE 2.4L 24 022129 1 WASHER LOCK M8-5/16 25 026204 1 WASHER SHAKEPROOF INT 5/16 26 022145 1 WASHER FLAT 5/16-M8 ZINC 27 045771 1 NUT HEX M8-1.25 G8 CLEAR ZINC 29 0F9596 1 SPACER ENGINE MOUNT (2.4L G1) 0F9596A 1 SPACER LH ENGINE MOUNT (2.4L G2)




1 0F3408B 1 BATTERY TRAY C1 CPL 2 0F3411 1 STRAP BATTERY RETAINMENT 3 025507 REF WASHER SHAKEPROOF EXT 7/16 STL 4 052212 REF SCREW HHC M10-1.25 X 25 G8.8 5 046526 REF WASHER LOCK M10 6 022131 REF WASHER FLAT 3/8-M10 ZINC 7 050331A REF BATTERY POST COVER RED + 8 050331 REF BATTERY POST COVER BLACK - 9 038805Y 1 CABLE BATTERY BLACK #1 X 18.00 10 03880400AE 1 CABLE BATT RED #1 X 18.00 11 045771 REF NUT HEX M8-1.25 G8 YEL CHR 12 022129 REF WASHER LOCK M8-5/16 14 0F3976 1 BOOT CONTACTOR CABLES 15 0C2454 4 SCREW THF M6-1 X 16 N WA Z/JS 16 022145 REF WASHER FLAT 5/16-M8 ZINC 17 077483 REF BATTERY 12VDC 75-AH 26




1 0E6586 1 GASKET BOSCH 32 & 40 2 0E0519A 1 ADAPTER CARBURETOR W/PVC CONN 3 0C8127 1 ELEMENT AIR CLEANER 4 052619 4 SCREW HHC M5-0.8 X 20 G8.8 5 022127 1 NUT HEX 1/4-20 STEEL 6 062974 1 STUD TH 1/4-20 X 4-1/2 G2 ZNC 7 0G0190 1 PLATE, AIR CLEANER TOP 2.4L 8 037561 1 NUT WING 1/4-20 NYLK 9 022097 1 WASHER LOCK M6-1/4





1 0F9529 1 WELDMENT RADIATOR SUPPORT 2.4L 2 0F2608 1 RADIATOR 598 X 568 X 49 CPL RH 3 0F5263 1 V-BELT 31/64" X 57-3/8" 4 046526 5 WASHER LOCK M10 5 059981 4 SCREW HHC M10-1.5 X 30 G10.9 6 022222 2 SCREW HHC 5/16-24 X 1-1/2 G5 7 0F5050 1 SHIELD RADIATOR C5 8 042568 8 SCREW HHC M6-1.0 X 20 G8.8 9 0F2573 1 PULLEY FAN V-GROOVE 9" 10 0F4011 1 FAN COOL 22" DIA 10 BLADE LH
11 0F2572 1 ARM TENSIONER 12 045757 1 SCREW HHC M6-1.0 X 25 G8.8 13 0F2862 1 SPRING TENSION CPL 14 0F2560 1 PULLEY V-BELT 4" FLANGED 15 022131 5 WASHER FLAT 3/8-M10 ZINC 16 0E2507 1 PROBE COOLANT LEVEL 3/8NPTF 17 035685 4 CLAMP HOSE #28 1.32-2.25 18 0F2561 1 HUB FLEX PLATE 19 0C8145 8 WASHER FLEX (THIN) 20 052250 2 TAPE FOAM 1 X 1 (26.75” LG) 21 0C7043 12 DISK FLEX 22 043790 1 BARBED EL 90 3/8 NPT X 3/8 23 022473 16 WASHER FLAT 1/4-M6 ZINC 24 0C8146 2 SCREW HHC 5/16-24 X 1.124 25 022097 16 WASHER LOCK M6-1/4 26 076749 1 TANK COOLANT RECOVERY 27 048031C 1 CLAMP HOSE BAND 1/4 28 031971 1 BEARING #6205 2NSE C3 E SRI2 S 29 0F4496 1 PULLEY 4.5" DIA MACHINED 30 042911 1 SCREW HHC M10-1.5 X 30 G8.8 31 0F2872 1 SCREW HHC 1/2-13 X 2" G8 32 022304 2 WASHER FLAT 1/2 ZINC 33 022195 1 WASHER LOCK 1/2 34 022196 1 NUT HEX 1/2-13 STEEL 35 0F8651 9 SCREW HHFC M8-1.25 X 20 W/M6 36 052857 1 NUT TOP LOCK FL M6-1.0 37 0F9867 1 SHAFT FAN DRIVE 38 0F2461 1 RETAINER BEARING 39 022145 3 WASHER FLAT 5/16-M8 ZINC 40 022129 10 WASHER LOCK M8-5/16 41 039414 1 SCREW HHC M8-1.25 X 35 G8.8 42 082774 1 KEY WOODRUFF 4 X 19D 43 0G0795 1 HOSE LOWER RADIATOR G2 44 0G0816 1 HOSE UPPER RADIATOR G2 45 049813 8 NUT HEX M6 X 1.0 G8 YEL CHR 46 052644 1 SPACER .5 X 1.5 X .25 STL/ZINC 47 0C8566 8 SCREW HHFC M6-1.0 X 20 G8.8 48 0C2454 2 SCREW THF M6-1 X 16 N WA Z/JS 49 090283 1 CAP RADIATOR 13 PSI 50 080713 1 BRACKET COOLANT TANK 51 045764 1 SCREW HHTT M4-0.7 X 8 BP 52 065852 1 SPRING CLIP HOLDER .37-.62 53 * 069811 REF. CAP HEX 1/4 NPT BRASS 54 069860C 1 HOSE OIL DRAIN ASSY 21" 55 0C7649 1 CLAMP HOSE .38-.87 56 0F8575 1 SPACER .25 X .50 X .300
* ITEM 53 IS INCLUDED WITH ITEM 64.
BEARING PRESS NOTE: APPLY LOCTITE 620 BEARING RETAINMENT COMPOUND TO BEARING SURFACE ON ITEM 37 PRIOR TO PRESSING ITEM 28 ONTO ITEM 37. ALSO APPLY LOCTITE 620 BEARING RETAINMENT COMPOUND TO THE OUTSIDE OF 28 PRIOR TO INSTALLING ITEM 28 INTO ITEM 38.




1 026915 2 NIPPLE CLOSE 3/4 X 1.375 2 075580 1 FLANGE FUEL INLET 3 0F6390B 1 REGULATOR ASSY 2.4L 4 039253 2 SCREW HHC M8-1.25 X 20 G8.8 5 022145 2 WASHER FLAT 5/16-M8 ZINC 6 022129 2 WASHER LOCK M8-5/16 7 045771 2 NUT HEX M8-1.25 G8 CLEAR ZINC 8 040173 2 CLAMP HOSE #5.5 .62-.62 9 0E8286 1 STREET EL 45D 1/2 NPT BRASS 10 026812 2 ELBOW 90D 3/4 NPT 11 0F8379 1 NIPPLE PIPE 3/4 NPT X 7 12 0F3869 1 (REF) SWITCH PRESSURE GAS 5" RISE (INCLUDED WITH I/N 3) 13 057823 2 CLAMP HOSE #10 .56 - 1.06 14 059057 1 HOSE 3/4 ID SAE-30R2 (18” LG) 15 047527 1 BARBED STR 1/2 NPT X 3/4 16 0D1509 1 DECAL INLET PRESSURE 17 * 050279 1 DECAL FUEL INLET NG (NATURAL GAS APPLICATION) 050280 1 DECAL FUEL INLET LPG (LP VAPOR APPLICATION) 18 0F2119 1 O-RING 45.63 ID X 2.62 WIDTH 19 0E6586 1 GASKET BOSCH 32 20 0E4394 1 ACTUATOR BOSCH 40 GOVERNOR (45KW) 0E4395 1 ACTUATOR BOSCH 32 GOVERNOR (35KW) 21 040105 1 HOSE COOL 2 IN ID 20R4 (45KW) 057753B 1 HOSE 1.5 ID X 2 LG 20R4 (35KW) 22 0E6382B 1 VENTURI HOLDER W/40MM ACTUATOR (45KW) 0E6382C 1 VENTURI HOLDER W/32MM ACTUATOR (35KW) 23 0F7790E 1 VENTURI THROTTLE 26MM 24 0E7121 1 O-RING 47.625 ID X 2.38 WIDTH 25 089617 1 (REF) BARBED STR 1/4 NPT X 1/4 MALE 26 022097 4 WASHER LOCK M6-1/4 27 046580 4 SCREW SHC M6-1.0 X 45 G12.9 28 035685 2 CLAMP HOSE #28 1.32-2.25 29 0F6155 1 HARNESS CPL FUEL JUMPER 30 047290 1 HOSE 3/8 ID SINGLE BRAID (18” LG) 31 030340 1 HOSE 1/4 ID SAE 30R7 (12” LG) 32 057823 2 CLAMP HOSE #10 .56-1.06
NOTES: 1. REGULATOR (I/N 3) AS SHOWN IN ILLUSTRATION IS SET UP FOR NATURAL GAS APPLICATION. 2. TO CONFIGURE REGULATOR FOR LP VAPOR, SWITCH HOSE BARB, HOSE CLAMP (I/N 13) AND HOSE (I/N 14) FROM “OUT-1” TO “OUT-2”. REPLACE PIPE PLUG FROM “OUT-2” TO “OUT-1”. USE PIPE SEALANT ON HOSE BARB AND PIPE PLUG. MAKE SURE TO KEEP PORTS FREE FROM DEBRIS DURING RECONFIGURATION PROCESS. 3*. FOR LP VAPOR APPLICATION SUBSTITUE LPG FUEL INLET DECAL P/N 050280 FOR NG FUEL INLET DECAL P/N 050279 (ITEM17). 4 . WHEN SWITCHING FUEL TYPES, THE PROPER DIP SWITCH SITTINGS MUST BE MADE TO THE CONTROL PANEL. SEE OWNERS MANUAL, FUEL SECTION FOR MORE DETAILS.




1 0G0045 (XX) 1 REAR WRAP C2 CPL 2 0C2454 54 SCREW THF M6-1 X 16 N WA Z/JS 3 0F5849 (XX) 2 DOOR C2 4 087233 2 RIVET POP .1875 X .450 SS 5 0E3257 4 SCREW TH-FRM M6 W/CAP SHKPRF W 6 0F5852 (XX) 2 DISCHARGE DUCT LH & RH SIDE C2 7 0F9833 (XX) 2 FRONT CORNERS C2 8 0F5851 (XX) 1 DISCHARGE CENTER DUCT C2 9 049813 2 NUT HEX M6 X 1.0 G8 YEL CHR 10 * 077992 21 NUT HEX LOCK M6-1.0 SS NY INS 11 0F9835 (XX) 1 ROOF C2 12 0F2786 2 SLITTER C4 13 0F2785 1 SPLITTER LOWER C4 14 0F3364 1 SPLITTER STINGER C2 15 0F4880 2 SUPPORT SPLITTER LH C2 16 0F5049 2 TAB PULL 17 0C2634A 1 ASSEMBLY COVER ACCESS 18 022473 3 WASHER FLAT 1/4-M6 ZINC 19 022097 1 WASHER LOCK M6-1/4 20 022127 1 NUT HEX 1/4-20 STEEL 21 0F3072 16 INSULATION RETAINMENT HANGER 22 078115 52 WASHER SELF LOCKING DOME 23 0F4051 2 INSULATION DOOR C2 24 0F4051A 1 INSULATION ROOF TOP 25 0F5048D 2 VISE-ACTION LATCH SLOTTED CIR 26 0E5968 1 GASKET EXTRUDED TRIM (440.64” LG) 27 0F3760K 2 INSULATION SPLITTER 28 0F3760E 2 INSULATION SPLITTER 29 0F4051C 2 INSULATION DUCT 30 0F3890B 10 RETAINER INSULATION (820) 31 0F4051B 2 INSULATION DUCT SIDES 32 0F3890 4 RETAINER INSULATION (450) 33 0F3890A 3 RETAINER INSULATION (740) 34 0F3760L 1 INSULATION LOWER SPLITTER 35 042568 2 SCREW HHC M6-1.0 X 20 G8.8 36 0912970094 2 ASSY WIRE 14 AWG 34.8" GRN/YEL 37 022447 2 WASHER SHAKEPROOF INT 1/4 38 0F4051E 1 INSULATION REAR WRAP 39 0F8869D 1 KEY VISE-ACTION LATCH SLOT CIR
OPTIONAL COMPARTMENT MATERIALS: ALL P/N’S WITH AN (XX) SUFFIX INDICATE A MULTIPLE MATERIAL AND COLOR OPTION. USE THE FOLLOWING LEGEND TO IDENTIFY THE CORRECT PART NUMBER:
PART NO. MATERIAL COLOR 0XXXXXSN STEEL TAN 0XXXXXAN ALUMINUM TAN 0XXXXXSG STEEL GRAY 0XXXXXAG ALUMINUM GRAY
* ALUMINUM ENCLOSURE NOTE: ALL ENCLOSURE PANELS THAT FASTEN TO THE BASE FRAME MUST BE SECURED USING ITEM 2 & 5 THREAD FORMING FASTENER AND ITEM 39 LOCK NUT. LOCK NUT IS TO BE INSTALLED AFTER THREAD FORMING FASTENER HAS PENETRATED THROUGH EXTRUSIONS IN ENCLOSURE PANELS. ALL ROOF PANELS ARE TO BE SECURED IN THE SAME MANNER.




1 0F9794 2 MUFFLER 7" X 9" X 18-1/2" 2" IN/OUT 2 0G0113 1 EXHAUST ELBOW 2 1/4 OD 2 1/2OD 3 0G1007 1 BRACKET MUFFLER 4 0F2830 2 MUFFLER BRACKET STIFFENER 5 0F2962 2 MUFFLER STRAP 6 080762 5 BOLT U 3/8-16 X 2.62 7 0E0170A 1 EXHAUST BLANKET 988MM (C2) 8 0C2454 4 SCREW THF M6-1 X 16 N WA Z/JS 9 0G0776 1 PIPE EXHAUST G2 10 0G0007 1 DIFFUSER EXHAUST WELDMENT 11 044149 1 GASKET EXHAUST RING 12 085917 2 WASHER LOCK 3/8 SS 13 0D2611 2 SCREW HHC 3/8-16 X 1-3/4 SS 14 0E8816 1 EXHAUST FLANGE 2" PIPE 15 049721 4 SCREW HHC M6-1.0 X 35 G8.8 BLK 16 022097 4 WASHER LOCK M6-1/4 17 022473 4 WASHER FLAT 1/4-M6 ZINC 18 036797 1 BOLT U 5/16-18 X 2.25 19 022259 2 NUT HEX 5/16-18 STEEL 20 070006 2 WASHER LOCK M8 SS 21 088775 2 WASHER FLAT 3/8 SS 22 022241 10 NUT HEX 3/8-16 STEEL 23 085917 10 WASHER LOCK 3/8 SS 24 0F2809 1 PIPE, EXHAUST CROSSOVER 25 0F2808B 1 PIPE, EXHAUST MUFFLER OUT




























1.) C2 UNITS A 0F9832 1 SHIELD CONN BOX C2 0F9832GGS0R 1 SHIELD CONTROL STAND C2 B 0C2454 3 SCREW THF M6-1 X 16 N WA Z/JS
2.) C3 UNITS A 0F9832B 1 SHIELD CONTROL STAND C3 0F9832KGS0R 1 SHIELD CONTROL STAND C3 B 0C2454 3 SCREW THF M6-1 X 16 N WA Z/JS
3.) C4 UNITS A 0F9832A 1 SHIELD CONTROL STAND C4 B 0C2454 2 SCREW THF M6-1 X 16 N WA Z/JS
4.) C5 UNITS A 0F9832C 1 SHIELD CONTROL STAND C5 0F9832D 1 SHIELD CONTROL STAND C5 0F9832EGS0R 1 SHIELD CONTROL STAND C5 0F9832HGS0R 1 SHIELD CONTROL STAND C5 0F9832JGS0R 1 SHIELD CONTROL STAND C5 B 0F9832FGS0R 1 SHIELD CONTROL STAND C5 C 0C2464 3 SCREW THF M6-1 X 16 N WA Z/JS

GENERAC POWER SYSTEMS STANDARD LIMITED WARRANTY FOR HOME STANDBY/LIGHT COMMERCIAL PRODUCT 45kW AND BELOW
For a period of two (2) years from the date of sale, or start-up by Authorized/Certified Generac Power Systems Dealer, or branch thereof, Generac Power Systems, Inc. will, at its option, repair or replace any part(s) which, upon examination, inspection, and testing by Generac Power Systems or an Authorized/Certified Generac Power Systems Dealer, or branch thereof, is found to be defective under normal use and service, in accordance with the warranty schedule set forth below. Any equipment that the purchaser/owner claims to be defective must be examined by the nearest Authorized/ Certified Generac Power Systems Dealer, or branch thereof. This warranty applies only to Generac Power Systems Generators used in "Standby" applications, as Generac Power Systems, Inc. has defined Standby, provided said generator has been properly installed and inspected on-site by appropriate personnel. Scheduled maintenance, as outlined by the generator owner's manual, is highly recommended. This should be performed by an Authorized/Certified Generac Power Systems Dealer, or branch thereof. This will verify service has been performed on the unit throughout the warranty period.
THIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING: 1. Any unit built/manufactured prior to January 1, 2005. 2. Costs of normal maintenance (i.e. tune-ups, associated part(s), adjustments, loose/leaking clamps, installation and start-up). 3. Any failure caused by contaminated fuels, oils, coolants/antifreeze or lack of proper fuels, oils or coolants/antifreeze. 4. Units sold, rated or used for "Prime Power", "Trailer Mounted" or "Rental Unit" applications as Generac Power Systems have defined Prime Power,
Trailer Mounted or Rental Unit. Contact a Generac Power Systems Distributor for Prime Power, Trailer Mounted or Rental Unit definition and warranty. 5. Units used for prime power in place of existing utility power where utility is present or in place of utility power where utility power service does not
normally exist. 6. Failures caused by any external cause or act of God such as, but not limited to, collision, fire, theft, freezing, vandalism, riot or wars, lightning,
earthquake, windstorm, hail, volcanic eruption, water or flood, tornado, hurricane, terrorist acts or nuclear holocaust. 7. Products that are modified or altered in a manner not authorized by Generac Power Systems in writing. 8. Failures due, but not limited to, normal wear and tear, accident, misuse, abuse, negligence, or improper installation or sizing. 9. Any incidental, consequential or indirect damages caused by defects in materials or workmanship, or any delay in repair or replacement of the
defective part(s). 10. Failure due to misapplication, misrepresentation, or bi-fuel conversion. 11. Telephone, facsimile, cell phone, satellite, internet, or any other communication expenses. 12. Rental equipment used while warranty repairs are being performed (i.e. rental generators, cranes, etc.). 13. Overtime, holiday, or emergency labor. 14. Planes, ferries, railroad, busses, helicopters, snowmobiles, snow-cats, off-road vehicle or any other mode of transportation deemed abnormal. 15. Any and all expenses incurred investigating performance complaints unless defective Generac materials and/or workmanship were the direct
cause of the problem. 16. Starting batteries, fuses, light bulbs, engine fluids, and overnight freight cost for replacement part(s).
THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, SPECIFICALLY, GENERAC POWER SYSTEMS MAKES NO OTHER WARRANTIES AS TO THE MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to purchaser/owner.
GENERAC POWER SYSTEMS ONLY LIABILITY SHALL BE THE REPAIR OR REPLACEMENT OF PART(S) AS STATED ABOVE. IN NO EVENT SHALL GENERAC POWER SYSTEMS BE LIABLE FOR ANY INCIDENTAL, OR CONSEQUENTIAL DAMAGES, EVEN IF SUCH DAMAGES ARE A DIRECT RESULT OF GENERAC POWER SYSTEMS, INC. NEGLIGENCE.
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations may not apply to purchaser/ owner. Purchaser/owner agrees to make no claims against Generac Power Systems, Inc. based on negligence. This warranty gives purchaser/owner specific legal rights. Purchaser/owner also may have other rights that vary from state to state.
Bulletin 0171360SVE / Printed in U.S.A. 7.05
Printed in U.S.A.
What the fault codes shown on the display mean and how to clear them.
| Code | Meaning | Fix | |
|---|---|---|---|
| QT100 | QT150. | p.13 |