Table of Contentsp.2SECTION PAGEp.2OPERATION ...........................................................9-1p.2SAFETY RULES ................................................ 1-1p.2INTRODUCTION .....................................................1-3p.2MAINTENANCE .....................................................10-1p.2IDENTIFICATION RECORD .....................................2-1p.2EQUIPMENT DESCRIPTION ...................................3-1p.2ENGINE PROTECTIVE DEVICES ............................4-1p.2FUEL SYSTEMS .....................................................5-1p.2SPECIFICATIONS ...................................................6-1p.2GENERAL INFORMATION .......................................7-1p.2SERVICE SCHEDULE ...........................................11-1p.2TROUBLESHOOTING ...........................................12-1p.2INSTALLATION .......................................................8-1p.2NOTESp.2EXPLODED VIEWS & PARTS LISTSp.2WIRING DIAGRAMS & SCHEMATICSp.2WARRANTYp.2Standby Generator Sets Important Safety Instructionsp.3SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safep.3WARNING:p.3DANGERp.3Despite the safe design of this generator,p.3This symbol points out potential electrical shockp.5READ THIS MANUAL THOROUGHLYp.5OPERATION AND MAINTENANCEp.5After this heading, read instructions that, if notp.5HOW TO OBTAIN SERVICEp.5NOTE:p.5After this heading, read explanatory statementsp.5AUTHORIZED SERVICE DEALER LOCATIONp.51-800-333-1322 or locate us on the web at:p.5www.generac.comp.5General Informationp.6IDENTIFICATION RECORDp.6DATA LABELp.6GENERATOR SET DATAp.6MADE IN USAp.6MODELp.6SERIALp.6RATED KWp.6RATED KVAp.6PHASEp.6RATED VOLTAGEp.6RATED AMPSp.6POWER FACTORp.6HERTZp.6ALT RPMp.6ENGINE RPMp.6PRODUCTION DATEp.6ALTERNATOR SUBTRANSIENT REACTANCEp.6ALTERNATOR TRANSIENT REACTANCEp.6CLASSp.6ROTOR STATOR WINDING INSULATION AT 25 ° C AMBIENTp.6WAUKESHA, WIp.6Equipment Descriptionp.7Do not use any chromate base rust inhibitorp.7Do not remove the radiator pressure cap whilep.7Any attempt to crank or start the engine beforep.7Standby Generator Sets Engine Protective Devicesp.8OVERCRANK SHUTDOWNp.8HIGH COOLANT TEMPERATURE SWITCHp.8OVERSPEED SHUTDOWNp.8LOW COOLANT LEVEL SENSORp.8RPM SENSOR LOSS SHUTDOWNp.8DC FUSEp.8LOW OIL PRESSURE SWITCHp.8Fuel Systemsp.9FUEL SYSTEMp.9PROPANE VAPOR WITHDRAWAL FUEL SYSTEMp.9FUEL REQUIREMENTSp.9LP FUEL SYSTEMp.9NATURAL GAS FUEL SYSTEMp.9Specificationsp.10COOLING SYSTEMp.10Controller .................................................R-100p.10Figure 1 — Interconnectionsp.11COLD WEATHER KITp.11Figure 6.2 — Reconfigure the Fuel Systemp.11
Page 1 of the Generac Power Systems 005221-0 user manual
Page 1 · click to enlarge
Page 1
Generac Power Systems 005221-0 diagram (page 1)
Fig. 1
Serial Number QT 3.9L 40kW Model: 005221-0 STANDBY GENERATOR OWNER'S MANUAL A new standard of reliability —CAUTION— ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS SHOULD ATTEMPT INSTALLATION! This manual should remain with the unit. Part No. 0F7924Cover026 Rev. 0 09/05
Page 2 of the Generac Power Systems 005221-0 user manual — Table of Contents
Page 2 · Contents
Contents

Contents

Table of Contentsp.2SECTION PAGEp.2OPERATION ...........................................................9-1p.2SAFETY RULES ................................................ 1-1p.2INTRODUCTION .....................................................1-3p.2MAINTENANCE .....................................................10-1p.2IDENTIFICATION RECORD .....................................2-1p.2EQUIPMENT DESCRIPTION ...................................3-1p.2ENGINE PROTECTIVE DEVICES ............................4-1p.2FUEL SYSTEMS .....................................................5-1p.2SPECIFICATIONS ...................................................6-1p.2GENERAL INFORMATION .......................................7-1p.2SERVICE SCHEDULE ...........................................11-1p.2TROUBLESHOOTING ...........................................12-1p.2INSTALLATION .......................................................8-1p.2NOTESp.2EXPLODED VIEWS & PARTS LISTSp.2WIRING DIAGRAMS & SCHEMATICSp.2WARRANTYp.2Standby Generator Sets Important Safety Instructionsp.3SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safep.3WARNING:p.3DANGERp.3Despite the safe design of this generator,p.3This symbol points out potential electrical shockp.5READ THIS MANUAL THOROUGHLYp.5OPERATION AND MAINTENANCEp.5After this heading, read instructions that, if notp.5HOW TO OBTAIN SERVICEp.5NOTE:p.5After this heading, read explanatory statementsp.5AUTHORIZED SERVICE DEALER LOCATIONp.51-800-333-1322 or locate us on the web at:p.5www.generac.comp.5General Informationp.6IDENTIFICATION RECORDp.6DATA LABELp.6GENERATOR SET DATAp.6MADE IN USAp.6MODELp.6SERIALp.6RATED KWp.6RATED KVAp.6PHASEp.6RATED VOLTAGEp.6RATED AMPSp.6POWER FACTORp.6HERTZp.6ALT RPMp.6ENGINE RPMp.6PRODUCTION DATEp.6ALTERNATOR SUBTRANSIENT REACTANCEp.6ALTERNATOR TRANSIENT REACTANCEp.6CLASSp.6ROTOR STATOR WINDING INSULATION AT 25 ° C AMBIENTp.6WAUKESHA, WIp.6Equipment Descriptionp.7Do not use any chromate base rust inhibitorp.7Do not remove the radiator pressure cap whilep.7Any attempt to crank or start the engine beforep.7Standby Generator Sets Engine Protective Devicesp.8OVERCRANK SHUTDOWNp.8HIGH COOLANT TEMPERATURE SWITCHp.8OVERSPEED SHUTDOWNp.8LOW COOLANT LEVEL SENSORp.8RPM SENSOR LOSS SHUTDOWNp.8DC FUSEp.8LOW OIL PRESSURE SWITCHp.8Fuel Systemsp.9FUEL SYSTEMp.9PROPANE VAPOR WITHDRAWAL FUEL SYSTEMp.9FUEL REQUIREMENTSp.9LP FUEL SYSTEMp.9NATURAL GAS FUEL SYSTEMp.9Specificationsp.10COOLING SYSTEMp.10Controller .................................................R-100p.10Figure 1 — Interconnectionsp.11COLD WEATHER KITp.11Figure 6.2 — Reconfigure the Fuel Systemp.11
Page 3 of the Generac Power Systems 005221-0 user manual — Despite the safe design of this generator,
Page 3 · click to enlarge
Page 3

Standby Generator Sets Important Safety Instructions

SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe

operation be copied and posted in potential hazard areas. Safety should be stressed to all operators, potential operators, and service and repair technicians for this equipment.

WARNING:

  • GENERAL HAZARDS
  • For safety reasons, the manufacturer recommends that this equipment be installed, serviced and repaired by an Authorized Service Dealer or other competent, qualified electrician or installation technician who is familiar with applicable codes, standards and regulations. The operator also must comply with all such codes, standards and regulations.
  • Installation, operation, servicing and repair of this (and related) equipment must always comply with applicable codes, standards, laws and regulations. Adhere strictly to local, state and national electrical and building codes. Comply with regulations the Occupational Safety and Health Administration (OSHA) has established. Also, ensure that the generator is installed, operated and serviced in accordance with the manufacturer’s instructions and recommendations. Following installation, do nothing that might render the unit unsafe or in noncompliance with the aforementioned codes, standards, laws and regulations.
  • The engine exhaust fumes contain carbon monoxide gas, which can be DEADLY. This dangerous gas, if breathed in sufficient concentrations, can cause unconsciousness or even death. For that reason, adequate ventilation must be provided. Exhaust gases must be piped safely away from any building or enclosure that houses the generator to an area where people, animals, etc., will not be harmed. This exhaust system must be installed properly, in strict compliance with applicable codes and standards.
  • Keep hands, feet, clothing, etc., away from drive belts, fans, and other moving or hot parts. Never remove any drive belt or fan guard while the unit is operating.
  • Adequate, unobstructed flow of cooling and ventilating air is critical in any room or building housing the generator to prevent buildup of explosive gases and to ensure correct generator operation. Do not alter the installation or permit even partial blockage of ventilation provisions, as this can seriously affect safe operation of the generator.
  • Keep the area around the generator clean and uncluttered. Remove any materials that could become hazardous.
  • When working on this equipment, remain alert at all times. Never work on the equipment when physically or mentally fatigued.
  • Inspect the generator regularly, and promptly repair or replace all worn, damaged or defective parts using only factory-approved parts.

The engine exhaust from this product

contains chemicals known to the state

of California to cause cancer, birth defects or other reproductive harm.

WARNING:

This product contains or emits chemicals known to the state of California to cause cancer, birth defects or other reproductive harm.

Study these SAFETY RULES carefully before install- ing, operating or servicing this equipment. Become familiar with this Owner’s Manual and with the unit. The generator can operate safely, efficiently and reli- ably only if it is properly installed, operated and maintained. Many accidents are caused by failing to follow simple and fundamental rules or precautions.

The manufacturer cannot anticipate every possible circumstance that might involve a hazard. The warn- ings in this manual, and on tags and decals affixed to the unit are, therefore, not all inclusive. If a pro- cedure, work method or operating technique is used that the manufacturer does not specifically recom- mend, ensure that it is safe for others. Also make sure the procedure, work method or operating tech- nique utilized does not render the generator unsafe.

DANGER

Despite the safe design of this generator,

operating this equipment imprudently, neglect- ing its maintenance or being careless can cause possible injury or death. Permit only responsible and capable persons to install, operate or main- tain this equipment. Potentially lethal voltages are generated by

these machines. Ensure all steps are taken to render the machine safe before attempting to work on the generator. Parts of the generator are rotating and/or hot

during operation. Exercise care near running generators.

Safety 001 Rev. 0 08/05

Page 4 of the Generac Power Systems 005221-0 user manual — Standby Generator Sets Important Safety Instructions
Page 4 · click to enlarge
Page 4

Standby Generator Sets Important Safety Instructions

  • Before performing any maintenance on the generator, disconnect its battery cables to prevent accidental start-up. Disconnect the cable from the battery post indicated by a NEGATIVE, NEG or (–) first. Reconnect that cable last.
  • Never use the generator or any of its parts as a step. Stepping on the unit can stress and break parts, and may result in dangerous operating conditions from leaking exhaust gases, fuel leakage, oil leakage, etc.
  • Generators installed with an automatic transfer switch will crank and start automatically when normal (utility) source voltage is removed or is below an acceptable preset level. To prevent such automatic start-up and possible injury to personnel, disable the generator’s automatic start circuit (battery cables, etc.) before working on or around the unit. Then, place a “Do Not Operate” tag on the generator control panel and on the transfer switch.
  • In case of accident caused by electric shock, immediately shut down the source of electrical power. If this is not possible, attempt to free the victim from the live conductor. AVOID DIRECT CONTACT WITH THE VICTIM. Use a nonconducting implement, such as a dry rope or board, to free the victim from the live conductor. If the victim is unconscious, apply first aid and get immediate medical help.
  • Never wear jewelry when working on this equipment. Jewelry can conduct electricity resulting in electric shock, or may get caught in moving components causing injury.
  • ELECTRICAL HAZARDS
  • All generators covered by this manual produce dangerous electrical voltages and can cause fatal electrical shock. Utility power delivers extremely high and dangerous voltages to the transfer switch as well as the standby generator. Avoid contact with bare wires, terminals, connections, etc., on the generator as well as the transfer switch, if applicable. Ensure all appropriate covers, guards and barriers are in place before operating the generator. If work must be done around an operating unit, stand on an insulated, dry surface to reduce shock hazard.
  • Do not handle any kind of electrical device while standing in water, while barefoot, or while hands or feet are wet. DANGEROUS ELECTRICAL SHOCK MAY RESULT.
  • If personnel must stand on metal or concrete while installing, operating, servicing, adjusting or repairing this equipment, place insulative mats over a dry wooden platform. Work on the equipment only while standing on such insulative mats.
  • The National Electrical Code (NEC) requires the frame and external electrically conductive parts of the generator to be connected to an approved earth ground. This grounding will help prevent dangerous electrical shock that might be caused by a ground fault condition in the generator set or by static electricity. Never disconnect the ground wire.
  • Wire gauge sizes of electrical wiring, cables and cord sets must be adequate to handle the maximum electrical current (ampacity) to which they will be subjected.
  • Before installing or servicing this (and related) equipment, make sure that all power voltage supplies are positively turned off at their source. Failure to do so will result in hazardous and possibly fatal electrical shock.
  • Connecting this unit to an electrical system normally supplied by an electric utility shall be by means of a transfer switch so as to isolate the generator electric system from the electric utility distribution system when the generator is operating. Failure to isolate the two electric system power sources from each other by such means will result in damage to the generator and may also result in injury or death to utility power workers due to backfeed of electrical energy.

FIRE HAZARDS • Keep a fire extinguisher near the generator at all times. Do NOT use any carbon tetra-chloride type extinguisher. Its fumes are toxic, and the liquid can deteriorate wiring insulation. Keep the extin- guisher properly charged and be familiar with its use. If there are any questions pertaining to fire extinguishers, consult the local fire department.

  • EXPLOSION HAZARDS
  • Properly ventilate any room or building housing the generator to prevent build-up of explosive gas.
  • Do not smoke around the generator. Wipe up any fuel or oil spills immediately. Ensure that no combustible materials are left in the generator compartment, or on or near the generator, as FIRE or EXPLOSION may result. Keep the area surrounding the generator clean and free from debris.
  • These generator sets may operate using one of several types of fuels. All fuel types are potentially FLAMMABLE and/or EXPLOSIVE and should be handled with care. Comply with all laws regulating the storage and handling of fuels. Inspect the unit’s fuel system frequently and correct any leaks immediately. Fuel supply lines must be properly installed, purged and leak tested according to applicable fuel-gas codes before placing this equipment into service.
  • Diesel fuels are highly FLAMMABLE. Gaseous fluids such as natural gas and liquid propane (LP) gas are extremely EXPLOSIVE. Natural gas is lighter than air, and LP gas is heavier than air; install leak detectors accordingly.

Safety 001 Rev. 0 08/05

Page 5 of the Generac Power Systems 005221-0 user manual — 1-800-333-1322 or locate us on the web at:
Page 5 · click to enlarge
Page 5

Standby Generator Sets Important Safety Instructions

INTRODUCTION Thank you for purchasing this model of the standby generator set product line.

This symbol points out potential fire hazard.

This symbol points out potential electrical shock

Every effort was expended to make sure that the information and instructions in this manual were both accurate and current at the time the manual was written. However, the manufacturer reserves the right to change, alter or otherwise improve this product(s) at any time without prior notice.

hazard. The operator is responsible for proper and safe use of the equipment. The manufacturer strongly recom- mends that the operator read this Owner's Manual and thoroughly understand all instructions before using this equipment. The manufacturer also strong- ly recommends instructing other users to properly start and operate the unit. This prepares them if they need to operate the equipment in an emergency.

‹

READ THIS MANUAL THOROUGHLY

If any portion of this manual is not understood, con- tact the nearest Authorized Service Dealer for start- ing, operating and servicing procedures.

‹

OPERATION AND MAINTENANCE

It is the operator's responsibility to perform all safety checks, to make sure that all maintenance for safe operation is performed promptly, and to have the equipment checked periodically by an Authorized Service Dealer. Normal maintenance service and replacement of parts are the responsibility of the owner/operator and, as such, are not considered defects in materials or workmanship within the terms of the warranty. Individual operating habits and usage contribute to the need for maintenance service.

Throughout this publication, and on tags and decals affixed to the generator, DANGER, WARNING, CAUTION and NOTE blocks are used to alert person- nel to special instructions about a particular service or operation that may be hazardous if performed incorrectly or carelessly. Observe them carefully. Their definitions are as follows:

DANGER

After this heading, read instructions that, if not

Proper maintenance and care of the generator ensure a minimum number of problems and keep operating expenses at a minimum. See an Authorized Service Dealer for service aids and accessories.

strictly complied with, will result in personal injury or property damage.

Operating instructions presented in this manual assume that the standby electric system has been installed by an Authorized Service Dealer or other competent, qualified contractor. Installation of this equipment is not a “do-it-yourself” project.

After this heading, read instructions that, if not

strictly complied with, may result in personal injury or property damage.

‹

After this heading, read instructions that, if not

HOW TO OBTAIN SERVICE

strictly complied with, could result in damage to equipment and/or property.

When the generator requires servicing or repairs, simply contact an Authorized Service Dealer for assistance. Service technicians are factory-trained and are capable of handling all service needs.

NOTE:

After this heading, read explanatory statements

that require special emphasis.

When contacting an Authorized Service Dealer or the factory about parts and service, always supply the complete model number of the unit as given on the front cover of this manual or on the DATA LABEL affixed to the unit.

These safety warnings cannot eliminate the hazards that they indicate. Common sense and strict compli- ance with the special instructions while performing the service are essential to preventing accidents.

Four commonly used safety symbols accompany the DANGER, WARNING and CAUTION blocks. The type of information each indicates is as follows: This symbol points out important safety infor-

AUTHORIZED SERVICE DEALER LOCATION

To locate the nearest AUTHORIZED SERVICE DEALER, please call this number:

mation that, if not followed, could endanger personal safety and/or property of others. This symbol points out potential explosion

1-800-333-1322 or locate us on the web at:

www.generac.com

hazard.

Safety 001 Rev. 0 08/05

Page 6 of the Generac Power Systems 005221-0 user manual — WAUKESHA, WI
Page 6 · click to enlarge
Page 6

General Information

IDENTIFICATION RECORD

‹

DATA LABEL

Every generator set has a DATA LABEL that contains important information pertinent to the generator. The data label, which can be found attached to the gen- erator’s lower connection box, lists the unit’s serial number and its rated voltage, amps, wattage capacity, phase, frequency, rpm, power factor, etc.

Generator Model and Serial Number This number is the key to numerous engineering and manufacturing details pertaining to your unit. Always supply this number when requesting service, order- ing parts or seeking information.



Data Label

GENERATOR SET DATA

MADE IN USA

MODEL

SERIAL

RATED KW

RATED KVA

PHASE

RATED VOLTAGE

RATED AMPS

POWER FACTOR

HERTZ

ALT RPM

ENGINE RPM

PRODUCTION DATE

ALTERNATOR SUBTRANSIENT REACTANCE

ALTERNATOR TRANSIENT REACTANCE

CLASS

ROTOR STATOR WINDING INSULATION AT 25 ° C AMBIENT

GENERAC POWER SYSTEMS, INC.

WAUKESHA, WI

Identy 002 Rev. A 12/05

Page 7 of the Generac Power Systems 005221-0 user manual — NOTE:
Page 7 · click to enlarge
Page 7

Equipment Description

EQUIPMENT DESCRIPTION This equipment is a revolving field, alternating cur- rent generator set. It is powered by a gaseous fueled engine operating at 1800 rpm for 4-pole direct drive units, 3600 rpm for 2-pole direct drive units and 2300 - 3000 rpm for quiet drive gear units. See the Specifications section for exact numbers. The unit comes complete with a sound attenuated enclosure, internally mounted muffler, control console, main- line circuit breaker, battery charger, and protective alarms as explained in the following paragraph.

COOLANT RECOMMENDATIONS Use a mixture of half low silicate ethylene glycol base anti-freeze and deionized water. Cooling system capacity is listed in the specifications. Use only deion- ized water and only low silicate anti-freeze. If desired, add a high quality rust inhibitor to the recommended coolant mixture. When adding coolant, always add the recommended 50-50 mixture.

Do not use any chromate base rust inhibitor

All AC connections, including the power leads from the alternator, 120 volt battery charger input and control connections to the transfer switch are avail- able in the main connection box.

with ethylene glycol base anti-freeze or chro- mium hydroxide (“green slime”) forms and will cause overheating. Engines that have been oper- ated with a chromate base rust inhibitor must be chemically cleaned before adding ethylene glycol base anti-freeze. Using any high silicate anti-freeze boosters or additives will also cause overheating. The manufacturer also recommends that any soluble oil inhibitor is NOT used for this equipment.

The generator incorporates the following generator features:

  • Rotor and Stator insulation is Class H rated as defined by NEMA MG1-32.6, NEMA MG1-1.66. The generator is self ventilated and drip-proof constructed.
  • The voltage waveform deviation, total harmonic content of the AC waveform and telephone influence factor have been evaluated and are acceptable according to NEMA MG1-32.

DANGER

Do not remove the radiator pressure cap while

the engine is hot or serious burns from boiling liquid or steam could result. Ethylene glycol base antifreeze is poisonous.

ENGINE OIL RECOMMENDATIONS The unit has been filled with 15W-40 engine oil at the factory. Use a high-quality detergent oil classified “For Service CC, SD, SE, SF.” Detergent oils keep the engine cleaner and reduce carbon deposits. Use oil having the following SAE viscosity rating, based on the ambient temperature range anticipated before the next oil change:

Do not use mouth to siphon coolant from the radiator, recovery bottle or any container. Wash hands thoroughly after handling. Never store used antifreeze in an open container because animals are attracted to the smell and taste of antifreeze even though it is poisonous to them.

TemperatureOil Grade (Recommended) Above 80° F (27° C)SAE 30W or 15W-40 32° to 80° F (0° to 27° C)SAE 20W-20 or 15W-40 Below 32° F (0° C)See Note

Any attempt to crank or start the engine before

it has been properly serviced with the recom- mended oil may result in an engine failure.

NOTE:

For temperatures below 32° F, it is strongly recom- mended to use the optional Cold Weather Start Kit (part number listed in the Specification Section). The oil grade for temperatures below 32° F is 5W- 30 synthetic oil.

Equip001 Rev. 0 08/05

Page 8 of the Generac Power Systems 005221-0 user manual — ‹
Page 8 · click to enlarge
Page 8

Standby Generator Sets Engine Protective Devices

ENGINE PROTECTIVE DEVICES The standby generator may be required to operate for long periods of time without an operator on hand to monitor such engine conditions as coolant tempera- ture, oil pressure or rpm. For that reason, the engine has several devices designed to protect it against potentially damaging conditions by automatically shutting down the unit when the oil pressure is too low, the coolant temperature is too high, the coolant level is too low, or the engine is running too fast.

‹

OVERCRANK SHUTDOWN

After a prespecified duration of cranking, this func- tion ends the cranking if the engine has failed to start. The overcrank LED will turn ON. Turn OFF the AUTO/OFF/MANUAL switch, then turn switch back to AUTO to reset the generator control board.

NOTE:

If the fault is not corrected, the overcrank feature will continue to activate.

NOTE:

  • Approximate Crank Cycle Times
  • 15 seconds ON
  • 7 seconds OFF
  • 7 seconds ON
  • 7 seconds OFF
  • Repeat for 45 seconds Approximately 90 seconds total.

Engine protective switches and sensors are men- tioned here for the reader’s convenience. Also refer to the applicable control panel manual for additional automatic engine shutdown informa- tion.

‹

HIGH COOLANT TEMPERATURE SWITCH

This switches contacts close if the temperature should exceed approximately 140° C (284° F), initiating an engine shutdown. The generator will automatically restart and the LED will reset once the temperature has returned to a safe operating level.

‹

OVERSPEED SHUTDOWN

A speed circuit controls engine cranking, start-up, operation and shutdown. Engine speed signals are delivered to the circuit board whenever the unit is running. Should the engine overspeed above a safe, preset value, the circuit board initiates an automatic engine shutdown. Contact the nearest Authorized Dealer if this failure occurs.

‹

LOW COOLANT LEVEL SENSOR

Should the engine coolant level drop below the level of the high coolant temperature switch, it is possible for the engine to overheat without automatic shut- down. To prevent such overheating, the engine has a low coolant level sensor. If the level of engine coolant drops below the level of the low coolant level sensor, the engine automatically shuts down.

‹

RPM SENSOR LOSS SHUTDOWN

If the speed signal to the control panel is lost, engine shutdown will occur.

‹

DC FUSE

‹

LOW OIL PRESSURE SWITCH

This fuse is located inside of the control panel. It protects the panel wiring and components from damaging overload. Always remove this fuse before commencing work on the generator. The unit will not start or crank if the fuse is blown. Replace the fuse with one of the same size, type, and rating. (See the exploded views and parts lists at the end of this manual for replacement part number.)

This switch has normally closed contacts that are held open by engine oil pressure during cranking and operating. Should oil pressure drop below the 8 psi range, switch contacts close, and the engine shuts down. The unit should not be restarted until oil is added, and the AUTO/OFF/MANUAL switch must be turned to OFF and then back to AUTO.

EngProt001 Rev. 0 08/05

Page 9 of the Generac Power Systems 005221-0 user manual — ‹
Page 9 · click to enlarge
Page 9

Fuel Systems

FUEL SYSTEM

‹

PROPANE VAPOR WITHDRAWAL FUEL SYSTEM

This type of system utilizes the vapors formed above the liquid fuel in the supply tank. Approximately 10 to 20 percent of the tank capacity is needed for fuel expansion from the liquid to the vapor state. The vapor withdrawal system is generally best suited for smaller engines that require less fuel. The installer should be aware of the following:

‹

FUEL REQUIREMENTS

The standby generator may be equipped with one of the following fuel systems:

  • Natural gas fuel system
  • Propane vapor (PV) fuel system The Manual Drawing Listing that is affixed to the unit includes the “Identification Code,” which may be used to identify the type of fuel system installed on the unit.
  • The natural gas and LP gas systems are similar. However, the natural gas system delivers gas at a pressure of approximately five inches water column to the carburetor.
  • When ambient temperatures are low and engine fuel consumption is high, the vapor withdrawal system may not function efficiently.
  • Ambient temperatures around the supply tank must be high enough to sustain adequate vaporization, or the system will not deliver the needed fuel volume.
  • In addition to the cooling effects of ambient air, the vaporization process itself provides an additional cooling effect.

Recommended fuels should have a Btu content of at least 1,000 Btus per cubic foot for natural gas; or at least 2,520 Btus per cubic foot for LP gas. Ask the fuel supplier for the Btu content of the fuel.

Required fuel pressure for natural gas is 5 inches to 14 inches water column (0.18 to 0.5 psi); and for liquid propane, 5 inches to 14 inches of water column (0.18 to 0.5 psi).

‹

LP FUEL SYSTEM

LP is supplied as a liquid in pressure tanks. It is usually made up of propane, butane, or a mixture of the two gases. Propane tends to vaporize readily even at temperatures as low as -20° F (-29° C). However, butane reverts to its liquid state when temperatures drop below 32° F (0° C).

LP in a liquid withdrawal system must be converted to its gaseous state before it is introduced into the engine carburetor. A vaporizer-converter is generally used to accomplish this. In such a converter, heated engine coolant is ported through the converter to provide the necessary heat for conversion of the fuel from a liquid to a gaseous state.

‹

NATURAL GAS FUEL SYSTEM

Natural gas is supplied in its vapor state. In most cases, the gas distribution company provides piping from the main gas distribution line to the standby generator site. The following information applies to natural gas fuel systems.

  • Gas pressure in a building is usually regulated by national, state and local codes.
  • To reduce gas pressure to a safe level before the gas enters a building, a primary regulator is needed. The natural gas supplier may or may not supply such a regulator.
  • It is the responsibility of the gas supplier to make sure sufficient gas pressure is available to operate the primary regulator.
  • Gas pressure at the inlet to the fuel shutoff solenoid should not exceed approximately 14 inches water column (0.5 psi). Optimum pressure at the fuel shutoff solenoid is 11 inches water column (0.4 psi).

FuelSys001 Rev. 0 08/05

Page 10 of the Generac Power Systems 005221-0 user manual — Controller .................................................R-100
Page 10 · click to enlarge
Page 10

Specifications

SPECIFICATIONS

Engine Lubrication System Type of Oil Pump Gear Oil Filter Full Flow Spin-on, Cartridge Crankcase Oil Capacity 4 U.S. qts.

GENERATOR Type Synchronous Rotor Insulation Class H Stator Insulation Class H Total Harmonic Distortion < 3.5% Telephone Interference Factor (TIF) < 50 Alternator Output Leads 3-phase 4-wire Bearings Sealed Ball Coupling Flexible Disc Load Capacity (Standby Rating) 40kW* * NOTE: Generator rating and performance in accordance with ISO8528-5, BS5514, SAE J1349, ISO3046 and DIN 6271 Standards. KW rating is based on LPG fuel and may derate with natural gas. Excitation System Direct Generator Output Voltage/kW - 60 Hz kW Amp CB Size 120/240V, 1-phase, 1.0 pf (LP) 40 167 175 120/240V, 1-phase, 1.0 pf (NG) 37 154 175 120/208V, 3-phase, 0.8 pf (LP) 40 139 150 277/480V, 3-phase, 0.8 pf (LP) 40 60 70 Generator Locked Rotor KVA Available @ Voltage Dip of 35% Single-phase or 208V, 3-phase 80 KVA 480V, 3-phase 90 KVA

‹

‹

COOLING SYSTEM

Type Pressurized Closed Recovery Water Pump Belt Driven Fan Speed 2060 rpm Fan Diameter 22 inches Fan Mode Pusher Air Flow (inlet air including alternator and combustion air) 2725 ft3/min. Coolant Capacity (3.0 U.S. gal.) Heat Rejection to Coolant 154,000 Btu/h Maximum Operating Air Temp. on Radiator 60° C (150° F) Maximum Ambient Temperature 50° C (140° F)

FUEL SYSTEM Type of Fuel Natural Gas, Propane Vapor Carburetor Down Draft Secondary Fuel Regulator Standard Fuel Shut-off Solenoid Standard Operating Fuel Pressure 5 in. - 14 in. Water Column

‹

ENGINE Make Generac Model V-type Cylinders and Arrangement 6 Displacement 3.9 Liter Bore 3.91 in. Stroke 3.31 in. Compression Ratio 9.1-to-1 Air Intake System Naturally Aspirated Valve Seats Precision Ground Lifter Type Overhead Valve Push Rod/Hydraulic Lifter

‹

Fuel Consumption - ft3/hr (Natural Gas/LPV) Exercise 25% 50% 75% 100% Cycle Load 82/33 148/59 285/114 397/160 550/221

‹

ELECTRICAL SYSTEM Battery Charge Alternator 12V, 30 Amp Static Battery Charger 2 Amp Recommended Battery 24F 525CCA System Voltage 12 Volts

Voltage Regulator Type Electronic Sensing Single-phase Regulation ± 1% Features V/F Adjustable, Adjustable Voltage and Gain LED Indicators

Engine Parameters Rated Synchronous RPM 60 Hz, 1800 HP at rated kW (LP/NG) 60 Hz, 64/59

Exhaust System Exhaust Flow at Rated Output 60 Hz 318 cfm Exhaust Temperature at Rated Output 938° F

Power Adjustment for Ambient Conditions Temperature Deration 3% for every 10° C above °C 25 1.65% for every 10° above °F 77 Altitude Deration 1% for every 100 m above m 183 3% for every 1000 ft. above ft 600

Combustion Air Requirements (Natural Gas) Flow at rated power, 60 Hz 118 cfm

Governor Type Electronic Frequency Regulation Isochronous Steady State Regulation ± 0.25%

Controller R-100

GenSpec001 Rev. D 11/05

Page 11 of the Generac Power Systems 005221-0 user manual — NOTE:
Page 11 · click to enlarge
Page 11

Specifications

Figure 1 — Interconnections

‹

COLD WEATHER KIT

10. Reverse the procedure to convert back to natural gas. 11. The Dip switch inside the control panel must be in the LP or NG position when switching to different fuels.

For cold climates, optional cold weather kit (part number 0F6148) is recommended. The kit includes:

  • Battery Warmer
  • 4” Junction Box with hardware
  • 6 qt. pack 5W-30 synthetic oil (engine)

Figure 6.2 — Reconfigure the Fuel System

‹

RECONFIGURING THE FUEL SYSTEM

Port 1 Port 2

FUEL HOSE

FUEL HOSE

NOTE:

PLUG

BRASS HOSE FITTING

BRASS HOSE FITTING

PLUG

All models are configured for natural gas or LP vapor from the factory.

OUT PORT 1

OUT PORT 2

HOUSING PORTS

HOUSING PORTS

To reconfigure the fuel system from NG to LP, follow these steps:

1. Turn the main gas supply off. 2. Remove the carburetor fuel hose from the outlet port (Port 1) of the demand regulator (Figure 6.2). 3. Remove the brass hose fitting from the outlet port (Port 1) of the demand regulator. 4. Remove pipe plug from Port 2. 5. Install brass hose fitting into Port 2. 6. Install pipe plug into Port 1. 7. Connect carburetor gas hose to brass fitting. 8. Tighten all clamps and plugs. 9. Make sure fuel supply is of the proper pressure and type for configuration.

NG FUEL SYSTEM LP FUEL SYSTEM

NOTE:

Port 1 is for NG only and Port 2 is for LP vapor only. No provision for dual fuel has been made.

NOTE:

For LP vapor application substitue LPG fuel inlet decal P/N 050280 for NG fuel inlet decal P/N 050279.

GenSpec001 Rev. D 11/05

Page 12 of the Generac Power Systems 005221-0 user manual — S1 E1
Page 12 · click to enlarge
Page 12

General Information

GENERATOR AC LEAD CONNECTIONS See “Voltage Codes”. This generator may be rated at any one of three voltages, either single-phase or three-phase. The electrical wires in the unit’s AC con- nection (lower) panel should be installed according to the number of leads and the voltage/phase required for the application. If there are any questions regard- ing lead connection, refer to the wiring diagrams at the back of this manual.

ALTERNATOR POWER WINDING CONNECTIONS

‹

3-PHASE ALTERNATORS

The generator is designed to supply 3-phase electri- cal loads. Electric power is produced in the alterna- tor power windings. These windings were connected at the factory to the main circuit breaker with a “Y” configuration as shown in Figures 7.2 and 7.3.

Voltage codes apply to the type of stator assembly installed on a particular generator.

The rated voltage between circuit breaker terminals E1-E2, E1-E3 and E2-E3 is either 480V or 208V depending on the model.

‹

FOUR-LEAD, SINGLE-PHASE STATOR

Four-lead generators (see Figure 7.1) are designed to supply electrical loads with voltage code “A” (240V, 1-phase, 60 Hz). Electrical power is produced in the stator power windings. These windings were con- nected at the factory to the main circuit breaker as shown in Figure 7.1.

The rated voltage between each circuit breaker termi- nal and the neutral point 00 is either 277V or 120V depending on the model.

Figure 7.2 — Stator Power Winding Connections - 3-phase, 277/480V (6 Lead)

The rated voltage between each circuit breaker ter- minal is 240V. The rated voltage between each circuit breaker terminal and the neutral point 00 is 120V.

S1 E1

Figure 7.1 — Four-lead, Single-phase Stator

INTERNAL CONNECTIONS

L-L S4

S6

NEUTRAL

S5

E3 S3

E2 S2

L-N

Figure 7.3 — Stator Power Winding Connections - 3-phase, 120/208V (6 Lead)

E1

S1 S1

S4 S4

00 (NEUTRAL)

S6

S5

S6 S3

S5 S2

E3 E2

S3

S2

L-N

ACConn001 Rev. 0 08/05

Page 13 of the Generac Power Systems 005221-0 user manual — NOTE:
Page 13 · click to enlarge
Page 13

Installation

INSTALLATION Refer to the separate “Installation Guide QT Product Line” supplied with the unit.

‹

PRIOR TO INITIAL START-UP

Prior to initially starting the generator, it must

PREPARATION BEFORE START-UP The instructions in this section assume that the standby generator has been properly installed, ser- viced, tested, adjusted and otherwise prepared for use by a competent, qualified installation contractor. Be sure to read the “Safety Rules”, as well as all other safety information in this manual, before attempting to operate this (and related) equipment.

be properly prepared for use. Any attempt to crank or start the engine before it has been properly serviced with the recommended types and quantities of engine fluids (oil, coolant, fuel, etc.) may result in an engine failure.

‹

ENGINE COOLANT

Have the engine cooling system properly filled with the recommended coolant mixture. Check the system for leaks and other problems. See “Specifications” and “Coolant” sections.

Before starting the generator for the first time, the installer must complete the following procedures. For follow-up maintenance information and/or service intervals, please refer to the “Maintenance” section and the “Service Schedule”.

‹

BELT TENSION

‹

TRANSFER SWITCH

Check-the engine-fan belt tension and condition prior to placing the unit into service and at recommended intervals. Belt tension is correct when a force of approximately 22 pounds (10 kg), applied midway between pulleys, deflects the belt about 3/8- to 5/8- inch (10 to 16 mm).

If this generator is used to supply power to any elec- trical system normally powered by an electric utility, the National Electrical Code requires that a transfer switch be installed. The transfer switch prevents elec- trical backfeed between two different electrical sys- tems. (For additional information, see the applicable transfer switch manual for this unit.) The transfer switch, as well as the generator and other standby components, must be properly located and mounted in strict compliance with applicable codes, standards and regulations.

‹

ELECTRICAL SYSTEM

Make sure the generator is properly connected to an approved earth ground.

Make sure the generator battery is fully charged, properly installed and interconnected, and ready for use.

‹

FUEL SYSTEM

Check to ensure that there are no loose electrical con- nections. Restrain any loose wires to keep them clear of any moving generator set components.

Make sure the fuel supply system to the genera- tor (a) delivers the correct fuel at the correct pres- sure and (b) is properly purged and leak tested according to code. No fuel leakage is permitted. See “Specifications” for more information.

INITIAL INSPECTION FOR QT GENSET STARTUP Inspect for the following.

‹

GENERATOR SET LUBRICATION

Check the engine crankcase oil level before operating and add oil to the proper level – the dipstick “FULL” mark. Never operate the engine with the oil level below the dipstick “ADD” mark. See “Specifications” and “Engine Oil Recommendations”.

  • Freight Damage.
  • Manuals present.
  • Fluid Levels ( Oil, coolant, battery, Gear Drive).
  • Correct fuel piping.
  • Correct muffler installation for QT50, QT70, QT100 - QT150.
  • Adequate air flow, clearances and ventilation per installation drawings and applicable codes.
  • Correct AC and DC wire size, connections and grounding. Control and communication wiring to/ from the transfer switch must be run in a separate conduit from the AC power leads.
  • Battery charger connection to 120 VAC.
  • Communication wires connected between transfer switch and generator (HTS only).
  • Unit secured to pad.

NOTE:

This engine is shipped from the manufacturer with “break-in” oil. This oil should be changed after 30 hours of operation.

Check the oil level in the generator gearbox (if so equipped) prior to initial use and at the intervals indicated by the “Service Schedule.” The recom- mended oil is SAE 90 gear lubricant.

Also, if the engine is equipped with a mechanical gov- ernor, make sure the governor is properly lubricated with clean engine oil.

Install001 Rev. A 11/05

Page 14 of the Generac Power Systems 005221-0 user manual — ‹
Page 14 · click to enlarge
Page 14

Installation

START-UP CHECKLIST

  • Check voltage at the generator terminals.
  • For 3-phase units, check phase rotation at the transfer switch terminals. The generator phase rotation must match the utility phase rotation.
  • Check for coolant, fuel, oil, and exhaust leaks.
  • Close the generators main line circuit breaker.
  • Turn the generator set off.
  • Connect the UTILITY supply to the transfer switch.
  • Set the AUTO/OFF/MANUAL switch to AUTO.
  • Disconnect utility power before the transfer switch. Engine should start, transfer to load. Run at least 15 minutes on generator power.

Before working on the generator, ensure the fol-

  • lowing:
  • The AUTO/OFF/MANUAL switch is in the OFF position.
  • The 120VAC supply to the battery charger is switched OFF.

‹

PREPARATION FOR START-UP

  • Ensure that the 120VAC circuit breaker to the battery charger is open.
  • Remove the fuse from the the control panel. For the H-100 and R-100: Open the front door of the control box and remove the 15 Amp ATO fuse in the lower left-hand corner of the control box.
  • Connect the battery cables to the battery. Attach negative battery cable last.
  • Close the 120VAC circuit breaker to the battery charger.
  • Measure the voltage at the battery before and after the charger is turned on.
  • Verify all AC electrical connections are tight at the circuit breaker and transfer switch.
  • Visually inspect entire area looking for loose paper, plastic wrappings, leaves, etc.
  • Check all hoses clamps fittings for leaks or damage.
  • Check all electrical plugs throughout the generator. Ensure each plug is seated correctly and fully inserted into its receptacle.
  • Verify the AUTO/OFF/MANUAL switch is in OFF position.
  • Open the valve to the engine fuel line.
  • Bleed the fuel system of air. (necessary for long fuel lines).
  • Open the generator main line circuit breaker.
  • Connect a manometer to the gas line and record the static pressure. It must be as listed in the Specifications.
  • Insert the fuse into the control panel.
  • Move the AUTO/OFF/MANUAL switch to the MANUAL position. The engine should now crank and start.

Make certain all 3-phase loads are functioning correctly (correct phase rotation). • Reconnect Utility power Transfer switch will transfer back to Utility and

  • engine will shut down within the given time parameters set up for the specific transfer switch and controller.
  • Install all covers, access plates and door panels.
  • Put the Owners Manual in a safe and accessible place.
  • Make certain the AUTO/OFF/MANUAL switch is in the AUTO position.

‹

START-UP INSPECTION

When a start-up is performed by an Authorized Service Dealer, a standard three-part form titled “Start-up Inspection for Standby Power Systems” (part no. 067377), should be completed by the instal- lation technician or engineer. See page 1-3 for infor- mation on locating the nearest Authorized Service Dealer. The installer should complete the form and disseminate copies as follows:

  • White copy: Mail to Generac Warranty Department, P.O. Box 340, 211 Murphy Dr., Eagle, WI 531192062.
  • Pink Copy: For service file of installing dealer.
  • Yellow Copy: For the customer’s records.

Install001 Rev. A 11/05

Page 15 of the Generac Power Systems 005221-0 user manual — NOTE:
Page 15 · click to enlarge
Page 15

Operation

GENERATOR CONTROL AND OPERATION Refer to the appropriate control panel operator’s manual for this unit.

Do not crank the engine continuously for longer

  • than 30 seconds, or the heat may damage the starter motor.
  • Let engine stabilize and warm up.
  • Check all applicable instrument and gauge readings. When certain that all readings are correct, move the transfer switch manual handle to its STANDBY (GENERATOR) position, i.e., load circuits supplied by the generator.
  • Set the standby generator’s main line circuit breaker to its ON (or CLOSED) position.
  • Load circuits are now powered by the standby generator.

OPERATING UNIT WITH MANUAL TRANSFER SWITCH If the generator was installed in conjunction with a transfer switch capable of manual operation only, the following procedure applies. A manually operated transfer switch is one that will not provide automatic start-up and does not include an intelligence circuit.

‹

ENGINE START-UP AND TRANSFER

‹

RETRANSFER AND SHUTDOWN

For additional information, refer to the applicable control panel manual for this unit, as well as any lit- erature pertaining to the specific transfer switch.

For additional information, refer to the applicable control panel manual for this unit, as well as any lit- erature pertaining to the specific transfer switch.

DANGER

To transfer the load back to the utility power source and shut down the generator, follow these direc- tions:

The Maintenance Disconnect Switch and the

AUTO/OFF/MANUAL switches (if so equipped) must be set properly, or the generator will crank and start as soon as the utility power to the transfer switch is turned off. Refer to applicable control panel and transfer switch manuals for more information. Do not proceed until certain that utility source

  • Set the standby generator’s main line circuit breaker to its OFF (or OPEN) position.
  • Manually move the transfer switch handle to its UTILITY (NORMAL) position, i.e., load circuits connected to the utility.
  • Turn ON the utility power supply to the transfer switch, using the means provided (such as the utility power source main line circuit breaker).
  • Let the generator run at no-load for a few minutes to stabilize internal temperatures.
  • Shut down the generator.

voltage is available to the transfer switch and the transfer switch main contacts are set to UTILITY. Do not attempt manual operation until all power

supplies to the transfer switch have been posi- tively turned off, or extremely dangerous - pos- sibly lethal - electrical shock will result. Transfer switch enclosure doors should be kept

OPERATING UNIT WITH AUTOMATIC TRANSFER SWITCH If the generator has been installed with an automatic transfer switch, such as an RTS, HTS, or GTS-type transfer switch, the engine may be started and stopped automatically or manually.

closed and locked. Only authorized personnel should be allowed access to the transfer switch interior. Extremely high and dangerous voltages are present in the transfer switch. In order to transfer load from the utility source to the generator, follow these directions:

NOTE:

  • Turn OFF or disconnect the utility power circuit to the transfer switch, using the means provided (such as the utility source main line circuit breaker).
  • Set the transfer handle to its UTILITY (NORMAL) position with load circuits connected to the utility power supply.
  • Set the standby generator’s main line circuit breaker to its OFF (or OPEN) position.
  • Start the generator.

Refer to the applicable manual for your trans- fer switch and to “Transfer Switch Start Signal Connections”. In addition, please note the dangers under “Engine Start-up and Transfer.”

Oper001 Rev. 0 08/05

Page 16 of the Generac Power Systems 005221-0 user manual — BATTERY FLUID
Page 16 · click to enlarge
Page 16

Maintenance

MAINTENANCE PERFORMED BY AUTHORIZED SERVICE FACILITIES

The exhaust system parts from this product get

extremely hot and remain hot after shutdown. High grass, weeds, brush, leaves, etc. must remain clear of the exhaust. Such materials may ignite and burn from the heat of the exhaust system.

Before working on the generator, ensure the fol-

  • lowing:
  • The AUTO/OFF/MANUAL switch is in the OFF position.
  • The 15A fuse has been removed from the control box.
  • The 120VAC supply to the battery charger is switched OFF.

CHECKING FLUID LEVELS

‹

CHECK ENGINE OIL

Check engine crankcase oil level (Figure 10.1) at least every 20 hours of operation, or prior to use.

‹

EVERY THREE MONTHS

  • Remove oil dipstick and wipe dry with a clean, lintfree cloth.
  • Install oil dipstick, then remove again.
  • Oil should be between FULL and ADD marks.
  • If oil level is below the dipstick ADD mark, remove oil fill cap. Add the recommended oil to bring oil level up to the FULL mark. DO NOT FILL ABOVE THE “FULL” MARK. See “Engine Oil Recommendations” for recommended oils.
1. Check battery state of charge and condition. 2. Inspect and test fuel system. 3. Check transfer switch. 4. Inspect exhaust system. 5. Check engine ignition system. 6. Check fan belts.

‹

ONCE EVERY SIX MONTHS

1. Test Engine Safety Devices (low oil pressure, low coolant level, high coolant temperature).

Figure 10.1 - Oil Dipstick and Oil Fill Cap

‹

ONCE ANNUALLY

Oil Dipstick Oil Fill

1. Test engine governor. Adjust or repair, if needed. 2. Clean, inspect generator. 3. Flush cooling system.

‹

FIRST 100 OPERATING HOURS

1. Change engine oil and oil filter. (After initial change, service engine oil and filter at 150 operating hours or 6 months, whichever comes first.)

‹

EVERY 500 OPERATING HOURS

‹

1. Service air cleaner. 2. Check starter. 3. Check engine DC alternator.

BATTERY FLUID

Check battery electrolyte fluid at least once weekly. Fluid should cover separators in all battery cells. If fluid level is low, add distilled water to cover tops of separators. DO NOT USE TAP WATER IN BATTERY.

COOLING SYSTEM Air intake and outlet openings in the generator com- partment must be open and unobstructed for contin- ued proper operation. This includes such obstruc- tions as high grass, weeds, brush, leaves and snow.

Without sufficient cooling and ventilating air flow, the engine/generator quickly overheats, which causes it to shut down.

Maint002 Rev. 0 08/05

Oil Filter

Page 17 of the Generac Power Systems 005221-0 user manual — After refilling the crankcase with oil, always
Page 17 · click to enlarge
Page 17

Maintenance

‹

ENGINE COOLANT

‹

CHECK FAN BELT

Check coolant level in coolant recovery bottle. See the “Specifications” section.

  • Inspect fan belts every three months. Replace any damaged, deteriorated, worn or otherwise defective belt.
  • Check fan belt tension. Thumb pressure, exerted midway between pulleys, should deflect about 3/8 to 5/8 inch. Adjust belt tension as required.
  • Add recommended coolant mixture as necessary.
  • Periodically remove radiator pressure cap to make sure the coolant recovery system is functioning properly. Coolant should be at bottom of radiator filler neck. If coolant level is low, inspect gasket in radiator pressure cap. Replace cap, if necessary. To have pressure cap tested, contact an Authorized Service Dealer. Inspect cooling system and coolant recovery system for leaks.

‹

INSPECT ENGINE GOVERNOR

Visually inspect electronic governor.

DANGER

Do not attempt to adjust the governor. Only

MAINTENANCE OWNER/ OPERATOR CAN PERFORM

qualified service facilities should adjust the governor. Excessively high operating speeds are dangerous and increase the risk of personal injury. Low speeds impose a heavy load on the engine when adequate engine power is not available and may shorten engine life. Correct rated frequency and voltage are supplied only at the proper governed speed. Some connected electrical load devices may be damaged by incor- rect frequency and/or voltage. Only qualified service technicians should adjust the governed speed.

‹

CHECK ENGINE OIL LEVEL

Refer to the “Checking Fluid Levels” section.

‹

CHECK BATTERY

  • Check battery fluid level each week as outlined under “Check Fluid Levels”.
  • Check battery cables for condition, tightness, corrosion or damage. Clean, tighten or replace as necessary.

‹

CHANGING ENGINE OIL

‹

EXERCISE SYSTEM

Refer to maintenance performed by authorized service facilities for engine oil and filter change frequencies.

Start the generator engine at least once every seven days and let it run at least 20 minutes. See the “Weekly Exercise Cycle” section.

Drain the oil while the engine is still warm from run- ning. This means warm up the engine, shut it down and drain immediately as follows:

‹

INSPECT COOLING SYSTEM

1. Remove OIL DRAIN HOSE from its retaining clip. 2. Loosen and remove OIL DRAIN HOSE CAP. Drain oil completely into suitable container. 3. When all oil has drained, install and tighten OIL DRAIN HOSE CAP, and re-install into its retaining clip. 4. Turn OIL FILTER (Figure 10.2) counterclockwise and remove. Dispose of old filter. 5. Apply light coating of new engine oil to seal of new oil filter.-Install FILTER and tighten by hand only. DO NOT OVERTIGHTEN. 6. Remove OIL FILL CAP. Add recommended oil (see SPECIFICATIONS). DO NOT FILL ABOVE THE DIPSTICK “FULL” MARK. Crankcase oil capacity is 4.0 U.S. quarts (3.8 liters).

  • Inspect engine cooling system at least once each month.
  • Check hoses for damage, deterioration, leaks, etc. Correct any discrepancies found.
  • Check hose clamps for tightness.

‹

CHECK ENGINE COOLANT LEVEL

See the “Checking Fluid Levels” section.

‹

PERFORM VISUAL INSPECTION

Complete a thorough visual inspection of the entire engine-generator monthly. Look for obvious damage, loose, missing or corroded nuts, bolts and other fas- teners. Look for fuel, oil or coolant leaks.

‹

INSPECT EXHAUST SYSTEM

After refilling the crankcase with oil, always

Inspect the exhaust system at least once every three months. Check all exhaust system pipes, mufflers, clamps, etc. for condition, tightness, leaks, security, damage.

check oil level on dipstick. NEVER OPERATE ENGINE WITH OIL BELOW THE DIPSTICK “ADD” MARK.

Maint002 Rev. 0 08/05

Page 18 of the Generac Power Systems 005221-0 user manual — SET PLUG GAP AT 1.01 mm
Page 18 · click to enlarge
Page 18

Maintenance

7. Start engine and check for oil leaks.

‹

COOLANT CHANGE

Every year, have an Authorized Service Facility drain, flush and refill the cooling system. See the “Specifications” section for cooling system recom- mendations.

Figure 10.2 - Oil Filter

MISCELLANEOUS MAINTENANCE

‹

CLEANING THE GENERATOR

Keep the generator as clean and as dry as possible. Dirt and moisture that accumulates on internal gen- erator windings have an adverse effect on insulation resistance.

Oil Filter

Periodically clean generator exterior surfaces. A soft brush may be used to loosen caked on dirt. Use a vacuum system or dry, low pressure air to remove any accumulations of dirt. The generator is housed inside an all-weather enclosure, clean the enclosure with a soft, damp cloth or sponge and water.

‹

CHANGING THE ENGINE AIR CLEANER

To replace the engine air cleaner, (part number 0A4637), remove the air cleaner cover and replace the air filter making sure it is positioned properly before reattaching the cover.

Once each year, have the generator cleaned and inspected by an Authorized Service Dealer. That dealer will use dry, low pressure air to clean internal windings. Parts inside the control console should be cleaned and inspected at this time as well.

See the “Service Schedule” section for air cleaner maintenance.

Finally, have the insulation resistance of stator and rotor windings checked. If insulation resistances are excessively low, the generator may require drying.

‹

SPARK PLUGS

Reset the spark plug gap or replace the spark plugs as necessary.

‹

BATTERY

1. Clean the area around the base of the spark plugs to keep dirt and debris out of the engine. Clean by scraping or washing using a wire brush and commercial solvent. Do not blast the spark plugs to clean. 2. Remove the spark plugs and check the condition. Replace the spark plugs if worn or if reuse is questionable. See the “Service Schedule” section for recommended inspection. 3. Check the spark plug gap using a wire feeler gauge. Adjust the gap to 1.01 mm (0.040 inch) by carefully bending the ground electrode (Figure 10.3).

All lead-acid storage batteries discharge when not in use. Refer to specific instructions and warnings that accompany the battery. If such information is not available, observe the following precautions when handling a battery:

  • DO NOT use jumper cables and a booster battery to crank or start the generator engine.
  • DO NOT recharge a weak battery while it is installed in the generator. Remove battery from generator and recharge in a well-ventilated area, away from fuel vapors, sparks, heat or flames.
  • Battery electrolyte fluid is an extremely caustic sulfuric solution that can cause severe burns. DO NOT permit fluid to contact eyes, skin, clothing, painted surfaces, wiring insulation, etc. If any battery fluid is spilled, flush the affected area with clear water immediately.
  • Always wear safety glasses, rubber apron and gloves when handling a battery.
  • Batteries give off explosive hydrogen gas while charging. The gas can form an explosive mixture around the battery for several hours after charging. Any spark, heat or flames can ignite the gas and cause an explosion which can shatter the battery, causing blindness or other serious injury.

Figure 10.3 – Setting the Spark Plug Gap

SET PLUG GAP AT 1.01 mm

(0.040 inch)

Maint002 Rev. 0 08/05

Page 19 of the Generac Power Systems 005221-0 user manual — Part Name Part Number
Page 19 · click to enlarge
Page 19

Maintenance

‹

BATTERY MAINTENANCE

The battery should be inspected per the “Service Schedule” section. The following procedure should be followed for inspection:

Be sure the AUTO/OFF/MANUAL switch is set to

the OFF position before connecting the battery cables. If the switch is set to AUTO or MANUAL, the generator can crank and start as soon as the battery cables are connected. Be sure the 120VAC power supply to the battery

1. Inspect the battery posts and cables for tightness and corrosion. Tighten and clean as necessary. 2. Check the battery fluid level of unsealed batteries and, if necessary, fill with DISTILLED WATER ONLY. DO NOT USE TAP WATER IN BATTERIES. 3. Have the state of charge and condition checked. This should be done with an automotive-type battery hydrometer.

is turned OFF, or sparking may occur at the bat- tery posts as the cables are attached and cause an explosion.

‹

BATTERY REPLACEMENT

DANGER

When replacing batteries, use the same number and the type of battery that follows:

Storage batteries give off explosive hydrogen

BCI Group No. CCA 24F-6 535 @ 0 deg. F

gas. This gas can form an explosive mixture around the battery for several hours after charg- ing. The slightest spark can ignite the gas and cause an explosion. Such an explosion can shat- ter the battery and cause blindness or other injury. Any area that houses a storage battery must be properly ventilated. Do not allow smok- ing, open flame, sparks or any spark producing tools or equipment near the battery. Battery electrolyte fluid is an extremely caus-

NOTE:

The BCI number should be located directly on the battery.

REPAIR PARTS The latter portion of this manual consists of exploded views, parts lists and electrical data pertaining to this generator set. The parts lists consist of (a) an item number, (b) a part number, (c) the quantity required, and (d) a description of the part. The item number corresponds to an identical number on the exploded view drawing.

tic sulfuric acid solution that can cause severe burns. Do not permit fluid to contact eyes, skin, clothing, painted surfaces, etc. Wear protective goggles, protective clothing and gloves when handling a battery. If the fluid is spilled, flush the affected area immediately with clear water. Do not use any jumper cables or booster battery

Periodic Replacement Parts

to crank and start the generator engine. If the battery has completely discharged, remove it from the generator for recharging.

Part Name Part Number

Oil Filter # 0E7415 Radiator Cap # 046627 Air Cleaner # 0A4637 Spark Plug Champion # RC12LC4

Maint002 Rev. 0 08/05

Page 20 of the Generac Power Systems 005221-0 user manual — Service Maintenance Interval Information:
Page 20 · click to enlarge
Page 20

Service Schedule

SERVICE SCHEDULE

30 KW - 150 KW STANDBY GAS ENGINE DRIVEN GENERATOR SETS

The following is a recommended maintenance schedule for standby gas engine driven generator sets from 30kW to 150 kW in size. The established intervals in the schedule are the maximum recommended when the unit is used in an average service application. They will need to be decreased (performed more frequently) if the unit is used in a severe application. Use calendar time, from the previous maintenance interval to determine the next required maintenance interval.

Service Maintenance Interval Information:

The various service maintenance intervals are designated by interval numbers as follows:

1 An early inspection of the generator set to insure it is ready to operate when required and to identify any poten- tial problem areas.

This inspection may be performed by the end user providing the following safety steps are taken to prevent the engine from starting automatically without warning:

To prevent injury, perform the following steps in the order indicated before starting any maintenance:

  • Disable the generator set from starting and/or connecting to the load by setting the control panel Auto/Off/
  • Manual switch to the “OFF” position.
  • Remove the 15 amp control panel fuse.
  • Turn off the battery charger.
  • Remove the negative battery cable.

The battery charger must be turned off BEFORE removing the battery cable to prevent an over current condition from burning out sensitive control panel components and circuits.

Following all maintenance, reverse these steps to insure the unit is returned to standby setup for normal

operation when required.

2 A wear-in service inspection of the generator set to insure it is ready to operate and carry the load when required, and to identify any potential problem areas.

Performed ONLY ONCE following the first three months or the first 30 hours of operation after purchase of the unit.

This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge to accomplish and should be performed only by an Authorized Service Dealer.

3 An operational inspection of the generator set to insure it is ready to operate and carry the load when required, and to identify any potential problem areas.

Performed semi-annually or following each 50 hours of operation of the unit.

This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge to accomplish and should be performed only by an Authorized Service Dealer.

4 A mid-level inspection of the generator set to insure it is ready to operate and carry the load when required, and to identify any potential problem areas.

Performed annually or following each 100 hours of operation of the unit.

This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge to accomplish and should be performed only by an Authorized Service Dealer.

5 A comprehensive inspection of the generator set to insure it is properly serviced and ready to operate and carry the load when required, and to identify any potential problem areas.

Performed annually or following each 250 hours of operation of the unit.

This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge to accomplish and should be performed only by an Authorized Service Dealer.

SrvSchd001 Rev. A 09/05

Page 21 of the Generac Power Systems 005221-0 user manual — Service Schedule
Page 21 · click to enlarge
Page 21

Service Schedule

Maintenance Level 1 Level 2 Level 3 Level 4 Level5 Tasks Recom- Task Required Task Required Task Task Required Task mended Comp. to be done Comp. to be done Comp. Required Comp. to be done Comp. to be done (Date- 3 months/ (Date- Semi- (Date- to be done (Date- Bi- (Date- monthly/ Initials) Break-in Initials) annually/ Initials) Annually/ Initials) annually/ Initials) 10 hrs. 30 hrs. 50 hrs. 100 hrs. 250 hrs. 1. Disable the unit from operating per the first page warning. 2. Check the engine oil level. Adjust as necessary. 3. Check the engine coolant level. Adjust as necessary. 4. Check the engine coolant thermal protection level. Correct as necessary. 5. Check the natural gas delivery system for leaks and correct pressure on gas engine driven units. Tighten connections as necessary. 6. Check the air inlets and outlets for debris. Clean as necessary. 7. Check the battery electrolyte level and specific gravity if accessible. Adjust as necessary. 8. Check the battery posts, cables, and charger for loose connections, corrosion, and proper operation. Correct as necessary. 9. Check the unit wiring for loose connections, corrosion, and damage. Correct as necessary.

SrvSchd001 Rev. A 09/05

Page 22 of the Generac Power Systems 005221-0 user manual — Service Schedule
Page 22 · click to enlarge
Page 22

Service Schedule

Maintenance Level 1 Level 2 Level 3 Level 4 Level5 Tasks Recom- Task Required Task Required Task Task Required Task mended Comp. to be done Comp. to be done Comp. Required Comp. to be done Comp. to be done (Date- 3 months/ (Date- Semi- (Date- to be done (Date- Bi- (Date- monthly/ Initials) Break-in Initials) annually/ Initials) Annually/ Initials) annually/ Initials) 10 hrs. 30 hrs. 50 hrs. 100 hrs. 250 hrs. 10. Check the engine accessory drive belts and fan coupling device if equipped for correct tension, wear, weather cracking, and damage. Replace as necessary. 11. Check the engine valve clearance. Adjust as necessary. 12. Visually inspect the unit looking for leaks, wear or damage, loose connections or components, and corrosion. Correct as necessary. 13. Test the engine and transfer switch safety devices. Correct and/or adjust as necessary. 14. Initiate an automatic start and transfer of the unit to site load and exercise it for at least 1 hour looking for leaks, loose connections or components, and abnormal operating conditions. Correct as necessary. 15. Replace the engine accessory drive belts. 16. Check gearbox oil level (if equipped). 17. Change gearbox oil (if equipped).

SrvSchd001 Rev. A 09/05

Page 23 of the Generac Power Systems 005221-0 user manual — Service Schedule
Page 23 · click to enlarge
Page 23

Service Schedule

Maintenance Level 1 Level 2 Level 3 Level 4 Level5 Tasks Recom- Task Required Task Required Task Task Required Task mended Comp. to be done Comp. to be done Comp. Required Comp. to be done Comp. to be done (Date- 3 months/ (Date- Semi- (Date- to be done (Date- Bi- (Date- monthly/ Initials) Break-in Initials) annually/ Initials) Annually/ Initials) annually/ Initials) 10 hrs. 30 hrs. 50 hrs. 100 hrs. 250 hrs. 18. Start and exercise the unit at full rated load (use a load bank if the site load is not enough) for at least 2 hours looking for leaks, loose connections or components, and abnormal operating conditions. Correct as necessary. 19. Perform an engine oil analysis (send a sample to a lab for results). Change the engine oil and filters if the analysis results indicate this is required. 20. Change the engine oil. 21. Replace the engine oil filter(s). 22. Replace engine spark plugs. Clean and re-gap or replace as necessary. 23. Replace the engine air filter(s). 24. Perform a 5 minute no-load operational run of the unit looking for any post service problems. 25. Return the unit to standby setup for operation when required.

SrvSchd001 Rev. A 09/05

Page 24 of the Generac Power Systems 005221-0 user manual — Troubleshooting
Page 24 · click to enlarge
Page 24

Troubleshooting

TROUBLESHOOTING GUIDE

PROBLEM CAUSE CORRECTION

Engine won’t crank. 1. 15 amp fuse blown. 1. Replace fuse. 2. Loose or corroded or defective 2. Tighten, clean or replace battery cables. battery cables as necessary. 3. Defective starter contactor. 3. Replace contactor.* 4. Defective starter motor. 4. Replace starter motor.* 5. Dead or Defective Battery. 5. Remove, change or replace battery. 6. 5 amp fuse blown. 6. Replace fuse.* Engine cranks but won't start 1. Out of fuel. 1. Replenish fuel. 2. Fuel solenoid (FS) is defective 2. Replace solenoid.* 3. Open Wire #14A from Engine Control 3. Reconnect wire. circuit board. 4. Spark plugs defective. 4. Clean, regap or replace plugs. 5. Door on tank not closed. 5. Close door on tank. Engine starts hard, runs rough. 1. Flame arrestor (air cleaner) plugged or 1. Clean or replace as needed. damaged. 2. Plugged fuel line. 2. Unclog fuel line. 3. Defective spark plugs. 3. Clean, regap or replace plugs. 4. Fuel pressure incorrect. 4. Confirm fuel pressure to regulator is as recommended in SPECIFICATIONS. Engine starts then shuts down. 1. Engine oil level is low. 1. Check oil and add oil as needed. 2. Engine is overheated. 2. Check cooling system for leaks. 3. Defective Low Oil Pressure Switch 3. Replace switch.* 4. Defective Coolant Temperature Switch 4. Replace switch.* 5. Defective Control Module circuit board. 5. Replace board.* 6. Coolant Level is Low. 6. Repair leak - Add coolant. 7. Defective Low Coolant Level Switch 7. Replace Switch.* AUTO/OFF/MANUAL Switch at OFF, 1. Defective AUTO/OFF/MANUAL switch 1. Replace switch.* engine continues to run 2. Open/disconnected wire #15A between 2. Reconnect/close wire. AUTO/OFF/MANUAL switch and Control Module circuit board. 3. Defective Control Module circuit board 3. Replace board.* No AC output from generator. 1. Check main line circuit breaker. 1. Reset to ON or CLOSED. 2. Check circuit breaker & fuses. 2. Reset and replace, if necessary. 3. Transfer switch set to NORMAL position 3. Set to GENERATOR position. 4. Generator internal failure. 4. * 5. Thermal circuit breaker open. 5. Auto-reset - Wait 5 min. and attempt restart.

*Contact the nearest Authorized Dealer for assistance.

Trblsht001 Rev. 0 08/05

Page 25 of the Generac Power Systems 005221-0 user manual — Notes
Page 25 · click to enlarge
Page 25

Notes

Page 26 of the Generac Power Systems 005221-0 user manual — Figure 1 — Interconnections
Page 26 · click to enlarge
Page 26
Generac Power Systems 005221-0 — Figure 1 — Interconnections diagram (page 26)
Fig. 2 · Figure 1 — Interconnections
Page 27 of the Generac Power Systems 005221-0 user manual — ** ITEM INCLUDED WITH 0D5464B
Page 27 · click to enlarge
Page 27

1 0F3137 1 PAN CB CONN BOX 2 0F3188 1 STAND RH CONTROL 3 0F3189 1 STAND LH CONTROL 4 023484N 1 BUSHING SNAP SB-2.5-31 5 *** 0F6366B 1 / 2 XFMR DUAL 120V/16V (FOR 120/240V & 277/480V UNITS) 0F6366A 1 XFMR DUAL 104V/16V (FOR 120/208V UNITS) 6 *** 043180 2 / 4 WASHER FLAT M4 7 *** 022264 2 / 4 WASHER LOCK #8-M4 8 *** 0C3990 2 / 4 SCREW PHTT M4-0.7 X 10 ZYC 9 * 057701 REF BLOCK TERM 20A 8 X 6 X 1100V 10 022155 4 WASHER LOCK #6 11 0C2428 4 SCREW PHTT #6-32 X 1/2 ZYC 12 0F3824 1 DECAL UTIL SENSE/CUST CONN 13 0A9457 1 DECAL NEUTRAL 14 057073 2 JUNCTION BLOCK 3/8-16 15 ** 0D5466 REF BUS BAR NEUTRAL BLOCK 390 16 ** 0A7822 REF LUG SLDLSS 600/250-1/0 X 1/4-28 17 022237 2 WASHER LOCK 3/8 18 022241 2 NUT HEX 3/8-16 STEEL 19 049226 7 WASHER LOCK M5 20 0C2266 6 SCREW PHTT M5-0.8 X 16 ZYC 21 0C2454 8 SCREW THF M6-1 X 16 N WA Z/JS 23 022473 8 WASHER FLAT 1/4-M6 ZINC 24 022097 4 WASHER LOCK M6-1/4 26 * 0D4698 REF BLOCK TERM 20A 6 X 3 X 1100V 27 0F4464 1 DECAL CUST CONN 120V UTILITY 28 025433 1 LUG SLDLSS #6-14 X 13/64 CU 29 024469 1 SCREW HHTT #10-32 X 3/8 CZ 30 067210A 1 DECAL GROUND LUG 31 0D6029 4 SCREW HHTT M6-1.0 X 16 ZYC 32 081008 1 GROMMET 1.25 X .25 X .75 33 077043J 1 CONDUIT FLEX 2.0" ID (36” LG) 34 051713 2 WASHER FLAT M5 35 0F6156 1 PLATE WIRE SNGL GALV 36 029289 1 TAPE ELEC 1/2 FOAM (AS REQ’D) 37 047411 4 SCREW HHC M6-1.0 X 16 G8.8 38 **** 064153B 2 WIRE JUMPER TRANSFORMER (NOT SHOWN)

B 065469 1 DECAL DANGER HIGH VOLTAGE C 0D5577 1 CB 0300A 3P 600V S JD6 LL D 0F2353 2 INSULATOR CIRCUIT BR. JD/LD E 022770 4 SCREW RHM 1/4-20 X 3 F 022473 4 WASHER FLAT 1/4-M6 ZINC G 022097 4 WASHER LOCK M6-1/4 H 022127 4 NUT HEX 1/4-20 STEEL J 0C2454 7 SCREW THF M6-1 X 16 N WA Z/JS K 029289 1 TAPE ELEC 1/2 FOAM (AS REQ’D) L 0F1733 1 DECAL CUSTOMER CONNECT INSIDE

4) UL CIRCUIT BREAKER (QN) A 0F8135 1 COVER QN FRM CB B 065469 1 DECAL, DANGER HIGH VOLTAGE C 0E7283 - CB 0150A 2P 240V S QN2 LL 0E7284 - CB 0175A 2P S QN2 LL 240V D 0E3664 1 BASE, QN CIRCUIT BREAKER E 074908 2 SCREW HHTT M5-0.8 X 10 BP F 0F8140 1 COVER QN CB DISH G 036261 4 RIVET POP .125 X .275 SS H 0C2454 7 SCREW THF M6-1X16 N WA Z/JS J 029289 1 TAPE ELEC 1/2 FOAM (AS REQ’D) K 0F1733 1 DECAL CUSTOMER CONNECT INSIDE

5) UL CIRCUIT BREAKER (QJ-2P) A 0F8137 1 COVER QJ 2P FRM CB B 065469 1 DECAL, DANGER HIGH VOLTAGE C 0E7994 - CB 0225A 240V 2P S QJ22 D 0F8136 1 COVER QJ 2P CB DISH E 036261 4 RIVET POP .125 X .275 SS F 022473 2 WASHER FLAT 1/4-M6 ZINC G 022097 2 WASHER LOCK M6-1/4 H 022127 2 NUT HEX 1/4-20 STEEL J 0F8139 1 INSUL CB 2P QJ K 0C2454 7 SCREW THF M6-1X16 N WA Z/JS L 022237 2 WASHER LOCK 3/8 M 048527 2 SCREW SHC 3/8-16 X 3/4 G8.8 NZ N 029289 1 TAPE ELEC 1/2 FOAM (AS REQ’D) P 022770 2 SCREW RHM 1/4-20 X 3 Q 0F1733 1 DECAL CUSTOMER CONNECT INSIDE

1) UL CIRCUIT BREAKER (ED) A 0F3328 1 COVER ED CB SHORT STND B 065469 1 DECAL DANGER HIGH VOLTAGE C 0D5552 1 CB 0050A 3P 480V S ED4 LL 0D5554 - CB 0070A 3P 480V S ED4 LL 0D5556 - CB 0090A 3P 480V S ED4 LL 0D9693 - CB 0125A 3P 480V S ED4 LL D 0F0492 1 INSULATOR CB S (ED-3P) E 048927 4 SCREW RHM #10-32 X 4-1/2 F 023897 4 WASHER FLAT #10 ZINC G 022152 4 WASHER LOCK #10 H 022158 4 NUT HEX #10-32 STEEL J 0C2454 7 SCREW THF M6-1 X 16 N WA Z/JS K 029289 1 TAPE ELEC 1/2 FOAM (AS REQ’D) L 0F1733 1 DECAL CUSTOMER CONNECT INSIDE

6. NEUTRAL BLOCK 390 / 200-400A A 0D5466 2 BUS BAR NEUTRAL BLOCK 390 B 039287 1 SCREW HHC M8-1.25 X 45 G8.8 FT C 022145 1 WASHER FLAT 5/16-M8 ZINC D 022129 1 WASHER LOCK M8-5/16 E 045771 1 NUT HEX M8-1.25 G8 YEL CHR F 022473 2 WASHER FLAT 1/4-M6 ZINC G 022097 2 WASHER LOCK M6-1/4 H 045335 2 SCREW HHC 1/4-28 X 3/4 G5 J 0A7822 1 LUG SLDLSS 600/250-1/0 X 1/4-28

* ITEM INCLUDED WITH HARNESS

2) UL CIRCUIT BREAKER (FD) A 0F3138 1 COVER CB CONN BOX B 065469 1 DECAL DANGER HIGH VOLTAGE C 0D5572 1 CB 0150A 3P 600V S FD6 LL 0D5573 - CB 0175A 3P 600V S FD6 LL 0D5574 - CB 0200A 3P 600V S FD6 LL 0D5575 - CB 0225A 3P 600V S FD6 LL 0D5576 - CB 0250A 3P 600V S FD6 LL D 0F0199 1 INSULATOR CB FD FRAME 30MIL E 081320 4 SCREW SHC 1/4-20 X 4.5 G8.8 NZ F 022473 4 WASHER FLAT 1/4-M6 ZINC G 022097 4 WASHER LOCK M6-1/4 H 022127 4 NUT HEX 1/4-20 STEEL J 0C2454 7 SCREW THF M6-1 X 16 N WA Z/JS K 029289 1 TAPE ELEC 1/2 FOAM (AS REQ’D) L 0F1733 1 DECAL CUSTOMER CONNECT INSIDE

** ITEM INCLUDED WITH 0D5464B

*** ITEM QTY DOUBLES FOR 277/480V

**** ITEM USED WITH 277/480V UNITS ONLY

3. UL CIRCUIT BREAKER (JD+LD) A 0F3329 1 COVER JD/LD CB SHRT STAND
Page 28 of the Generac Power Systems 005221-0 user manual — Figure 1 — Interconnections
Page 28 · click to enlarge
Page 28
Generac Power Systems 005221-0 — Figure 1 — Interconnections diagram (page 28)
Fig. 3 · Figure 1 — Interconnections
Page 29 of the Generac Power Systems 005221-0 user manual — * ROTOR REPLACEMENT PARTS
Page 29 · click to enlarge
Page 29
Generac Power Systems 005221-0 — Figure 1 — Interconnections diagram (page 29)
Fig. 4 · Figure 1 — Interconnections

1 0F3438 1 RTR 390 30AD1 CPL 0F3440 1 RTR 390 40AD2 CPL HI-EF 0F6188 1 ASSY RTR 390 30KD1 CPL 0F6190 1 ASSY RTR 390 40KD2 CPL 2 0F3439 1 STR 390 30AD1 CPL 0F3441 1 STR 390 40AD2 CPL 0F6189 1 STR 390 30GD1 CPL 0F6199 1 STR 390 40GD2 CPL 0F6655 1 ASSY STR 390 30KD1 CPL 0F6656 1 ASSY STR 390 40KD2 CPL 3 0C9708 1 INSTR HYPOT TEST 4 SEE ENGINE EV REF ENGINE ADAPTER 5 SEE ENGINE EV REF FLEXPLATE 6 0F5536 1 ASSY FLYWHEEL C2 CPL 7 0E5706 1 REAR BEARING CARRIER 390/DRCT 8 0F7874 1 ASSY BRUSH HOLDER 390/HSB 9 0F6124 1 GUARD REAR BEARING CARRIER CPL 3.0L 30KW 0F6123 1 GUARD REAR BEARING CARRIER CPL 3.9L 40KW 10 0E6076 1 REVCOR FAN 12.63 X 2 W/PRESSDISK 11 023454 1 KEY WOODRUFF #E 12 077043F 1 CONDUIT FLEX 1-1/4" (30” LG) 13 04576100BU 4 STUD M14-2.0 570 G5 ZINC (30KW) 04576100AQ 4 STUD M14-2.0 X 615 G5 ZINC 14 052646 4 WASHER FLAT M14 15 043123 4 WASHER LOCK M14 16 051779 4 NUT HEX M14-2.0 G8 YEL CHR 17 0A2601 1 SCREW HHC M16-2.0 X 45 G8.8 18 0A2602 1 WASHER FLAT .688 ID X 3.25 OD 19 0F3398 8 SCREW SHC M10-1.5 X 16 G10.9 20 046526 8 WASHER LOCK M10 21 0C3993 4 SCREW HHTT M4-0.7 X 25 BP 22 022264 4 WASHER LOCK #8-M4 23 038150 4 WASHER FLAT #8 ZINC 24 * 047248 1 BALL BEARING-45 MM 25 * 070892 1 SLIP RING MACHINED

* ROTOR REPLACEMENT PARTS

Page 30 of the Generac Power Systems 005221-0 user manual — Figure 1 — Interconnections
Page 30 · click to enlarge
Page 30
Generac Power Systems 005221-0 — Figure 1 — Interconnections diagram (page 30)
Fig. 5 · Figure 1 — Interconnections
Page 31 of the Generac Power Systems 005221-0 user manual — Figure 1 — Interconnections
Page 31 · click to enlarge
Page 31
Generac Power Systems 005221-0 — Figure 1 — Interconnections diagram (page 31)
Fig. 6 · Figure 1 — Interconnections

COMPONENTS INCLUDED IN 01827E 1 0F1823A 1 ENCL HSB CONTROL PANEL 2 0F3078 1 COVER CONTROL PANEL 3 0F2606 1 HINGE CONTINUOUS H-PANEL 4 036261 6 RIVET POP .125 X .275 SS 5 043181 4 SCREW PHM M3-0.5 X 10MM 6 052777 7 WASHER FLAT M3 7 0F4245E 1 ASSY PCB CPL CTRLR 1800 RPM 8 0F1262 4 HOLDER FUSE WICKMANN 178.6150 9 0F1263 1 ADPTR RH SIDE WICKMAN 178.6191 10 0F1264 1 ADPTR LH SIDE WICKMAN 178.6192 11 0F1725C 1 ASSY PCB 2AMP 12V UL BATT CHGR 12 067680 1 ASSY VOLTAGE REGULATOR 60HZ 13 0E6875A 2 RELAY 12VDC C FORM W/DIODE 14 055911 1 BLOCK TERM 20A 12 X 6 X 1100V 15 0E3161 1 ASSY PCB BOSCH GOV DRIVER 16 0F5459 1 DECAL CPL CONTROL PANEL FUSES 17 0F5462 1 DECAL CPL 3.9L TB1 18 0A5062J 4 SPACER 9.5H 3.2 ID 19 029673 1 DIO BRIDGE 25A 600V 20 048467 1 CIRCT BRK 7 X 1 ETA 46-500-P 21 0F1958 1 PLATE,HARNESS CLAMP 22 082573 1 SWITCH RKR DPST 125V SPD 23 0E4494 1 SWITCH RKR DPDT ON-OFF-ON 24 0F3215 1 DECAL CONTROL HSB 25 0F5886 3 SCREW HHPM M5-0.8 X 12 26 051713 12 WASHER FLAT M5 27 049226 12 WASHER LOCK M5 28 0F5752F 1 RES WW 15R 5% 25W QK CONN 29 0F5884 2 SCREW PHTT M3.5-0.6 X 10 30 0F5896 2 SCREW PHTT M3.5-0.6 X 16 31 0C2265 4 SCREW PHTT M4-0.7 X 12 ZYC 32 0C3990 2 SCREW PHTT M4-0.7 X 10 ZYC 33 091526 4 SCREW PPHM M5-0.8 X 12 ZNC 34 051716 9 NUT HEX M5-0.8 G8 CLEAR ZINC 35 079224 2 SCREW PPHM M5-0.8 X 30 SS 36 043182 7 WASHER LOCK M3 37 051714 7 NUT HEX M3-0.5 G8 YEL CHR 38 0F3192 1 SUPPORT ANGLE PCB 39 0E7403C 1 FUSE ATO TYPE 15 AMP (BLUE) 40 0F4416 1 HARN 1800RPM R-100 CONTROL PNL (NOT SHOWN) 41 0F6305 2 SEAL COVER 3.18 X 12.7 X 382 42 0F6305A 1 SEAL COVER 3.18 X 12.7 X 283

COMPONENTS INCLUDED IN 0F7376D A 056739 1 RELAY SOLENOID 12VDC PNL MNT B 047411 2 SCREW HHC M6-1.0 X 16 G8.8 C 022473 4 WASHER FLAT 1/4-M6 ZINC D 022097 2 WASHER LOCK M6-1/4 E 049813 2 NUT HEX M6 X 1.0 G8 YEL CHR F 0F6145 A/R SEAL WEATHER .45"DIA G 0F2627A 1 COVER CONTROL PANEL SIDE H 049815 4 SCREW HHC M5-0.8 X 16 G8.8 J 049226 4 WASHER LOCK M5 K 023897 4 WASHER FLAT #10 ZINC

Page 32 of the Generac Power Systems 005221-0 user manual — Figure 1 — Interconnections
Page 32 · click to enlarge
Page 32
Generac Power Systems 005221-0 — Figure 1 — Interconnections diagram (page 32)
Fig. 7 · Figure 1 — Interconnections
Page 34 of the Generac Power Systems 005221-0 user manual — Figure 1 — Interconnections
Page 34 · click to enlarge
Page 34
Generac Power Systems 005221-0 — Figure 1 — Interconnections diagram (page 34)
Fig. 8 · Figure 1 — Interconnections
Page 35 of the Generac Power Systems 005221-0 user manual — Figure 1 — Interconnections
Page 35 · click to enlarge
Page 35

1 0F3408 1 TRAY BATTERY 2 0F3411 1 STRAP BATTERY RETAINMENT 3 058208 REF BATT 12VDC 24F 625 4 036833 1 SCREW HHC 3/8-16 X 1 G8 5 022237 1 WASHER LOCK 3/8 6 022131 1 WASHER FLAT 3/8-M10 ZINC 7 050331A 1 BATT POST COVER RED + 8 050331 1 BATT POST COVER BLK - 9 038805H 1 CABLE BATT BLK #1 X 23.00 10 038804Y 1 CABLE BATT RED #1 X 35.00 11 045771 1 NUT HEX M8-1.25 G8 YEL CHR 12 022129 1 WASHER LOCK M8-5/16 13 027482 2 WASHER SHAKEPROOF EXT 5/16 STL 14 075763 1 BOOT BATTERY CABLE 15 0C2454 6 SCREW THF M6-1 X 16 N WA Z/JS

Page 36 of the Generac Power Systems 005221-0 user manual — Figure 1 — Interconnections
Page 36 · click to enlarge
Page 36
Generac Power Systems 005221-0 — Figure 1 — Interconnections diagram (page 36)
Fig. 9 · Figure 1 — Interconnections
Page 37 of the Generac Power Systems 005221-0 user manual — Figure 1 — Interconnections
Page 37 · click to enlarge
Page 37

1 0E5048A 1 FLEXPLATE HSB 3.9L CHRYSLER (1800RPM) 0F3903A 1 FLEX PLATE 2 POLE 3.9L CHRY (3600RPM) 2 0F2982 1 ENG ADAPTER MACH 3.9L HSB NSPS 3 0E6703 1 COVER FLYWHEEL ACCESS 4 0F3795 REF ENGINE INSERTED VALVE 3.9L (3600 RPM) 0E8336 REF MAKE 3.9L CHRYSLER ENGINE (1800 RPM) 5 0E7841 2 GASKET THERMOSTAT ADAPTOR 6 0E7254 1 MACH THERM ADAPTOR 3.9L CHRY 7 0E7956 1 BRACKET IGNITION COIL 8 0E7953 1 COIL IGNITION 3.9L CHRYSLER 9 047411 4 SCREW HHC M6-1.0 X 16 G8.8 10 0E8615 6 BOLT 7/16-20 X 7/8 11 0E9868A 1 D.C. ALTERNATOR W/OUT PULLEY 12 054455 1 ADP OIL DRN 1/2-20 13 022097 7 WASHER LOCK M6-1/4 14 022473 10 WASHER FLAT 1/4-M6 ZINC 15 049721 2 SCREW HHC M6-1.0 X 35 G8.8 BLK

16 049813 3 NUT HEX M6 X 1.0 G8 YEL CHR 17 036833 11 SCREW HHC 3/8-16 X 1 G8 18 022131 15 WASHER FLAT 3/8-M10 ZINC 19 022237 19 WASHER LOCK 3/8 20 0E6729 1 STARTER 12V 21 022129 19 WASHER LOCK M8-5/16 22 049821 3 SCREW SHC M8-1.25 X 30 G12.9 23 043790 1 BARBED EL 90 3/8 NPT X 3/8 24 052677 1 WASHER NYLON .50 X .87 X .06 25 0F1444A 1 HEAT SHEILD L/H SIDE 26 0E9975 1 CAP VINYL 1/4" ID X 1" DP BLK 27 0F5114 1 DECAL REFER TO OWNERS MANUAL 28 0D2244M 1 ASSY MAGPICKUP (3/8-24 MALE) 29 0E0992B REF PLUG EXPANSION 21/32" O.D. (WATER PUMP) (QTY 1) 30 0E0992A REF PLUG EXPANSION 14.1 O.D. (INJCTOR HOLE) (QTY 6) 31 0F5806 1 SPACER FLEX PLATE 3.9L C4 CPL (3600 RPM) 0E8731 1 PLATE FLEX DISK SPACER (1800 RPM) 32 052647 2 SCREW SHC M10-1.5 X 25 G12.9 33 0E7855 1 TENSIONER W/BRACKET 34 0F2694A 1 PULLEY CRANKSHAFT (3600 RPM) 0E7952 1 PULLEY CRANKSHAFT 3.9L CRYSLR (1800 RPM) 35 035606 1 SENSOR HI COOLANT SHUTDOWN 36 0A8584 1 SWITCH OIL PRESSURE 10 PSI 2 POL 37 061012 REF PLUG STD PIPE 1/8 SOCKET HEAD 38 0F1444 1 HEAT SHIELD R/H SIDE 39 050873A REF PLUG PIPE 1/4 CSK W/ VIBRA SL 40 031919 REF PLUG STD PIPE 3/8 COUNTERSUNK 41 022145 15 WASHER FLAT 5/16-M8 ZINC 42 030231 6 SCREW HHC 5/16-18 X 1-1/2 G5 (3600 RPM) 030795 6 SCREW HHC 5/16-18 X 1 G5 (1800 RPM) 43 048031J REF HOSE CLAMP BAND 5/8" 44 069860E 1 HOSE DRAIN ASSY 28" 45 0E7954 1 CABLE IGN COIL 3.9L CHRYSLER 46 057824 1 CLAMP HOSE #16 .87-1.50 (3600 RPM) 47 023645 5 SCREW SHC 3/8-16 X 1.25 G8.8 Z 48 022403 2 SCREW HHC 5/16-18 X 2 G5 49 0E7950 1 TUBE DIPSTICK 3.9L CHRYSLER 50 0E7951 1 DIPSTICK OIL LEVEL 3.9L CHRYSLER 51 0E8445 1 BRACKET DIPSTICK TUBE 52 0E7415 1 OIL FILTER 3.9L CHRYSLER 53 042568 1 SCREW HHC M6-1.0 X 20 G8.8 54 0F3447 1 BRKT L/H SIDE D.C. ALTERNATOR 55 0F3446 1 BRKT R/H SIDE D.C. ALTERNATOR 56 0F3216C 1 PULLEY 132 OD DC ALTERNATOR (3600 RPM) 0F3216 1 PULLEY 80 OD DC ALTERNATOR (1800 RPM) 57 039253 1 SCREW HHC M8-1.25 X 20 G8.8 58 022241 1 NUT HEX 3/8-16 STEEL 59 022746 1 SCREW HHC 3/8-16 X 1-3/4 G5 60 0F3641 1 HARN ENG 3.9L 3600 RPM FLEX PNL (NOT SHOWN)(3600 RPM) 0F4272 1 HARN ENG 3.9L 1800 RPM FLEX PNL (NOT SHOWN)(1800 RPM) 61 0F3217 1 SPACER DC ALTERNATOR PULLEY 62 0D3488H 1 SERPENTINE BELT (60.5") 63 022532 1 SCREW HHC 5/16-18 X 2-1/2 G5 64 0F3844 6 WASHER FLAT .45 X 1.00 65 026925 1 PLUG STD PIPE 3/8 STEEL SQ HD 66 0F4110 1 BYPASS ORIFICE 3.9L CHRYSLER (3600 RPM) 67 0F5454 1 PLATE MAG PICK-UP ADAPTOR 68 0F6027 2 SHIELD HT RR (C4 3600RPM ONLY) (BOTH SIDES) 69 0F6029 2 SHIELD HT FRT (C4 3600RPM ONLY) (BOTH SIDES) 70 045771 5 NUT HEX M8-1.25 G8 CLEAR ZINC (C4 3600 RPM ONLY) 71 0F5928 6 REFLEX WRAP 13MM X 153.3MM (C4 3600 RPM ONLY) 72 087173 1 SCREW HHC M8-1.25 X 45 G8.8 73 0F6480 1 BRKT L/H SIDE DC ALTERNATOR 74 0F6715 2 SPACER .41 X .75 X .18 AL 75 0E0561 1 ASSY WATER LEVEL SENSOR C/E PL 76 059057 1 HOSE 3/4 ID SAE-30R2 (17” LG) 77 057822 1 CLAMP HOSE #8 .53-1.00 78 057795A 1 BARBED EL 90 3/4 PLASTIC 79 057796 1 GROMMET

Page 38 of the Generac Power Systems 005221-0 user manual — Figure 1 — Interconnections
Page 38 · click to enlarge
Page 38
Generac Power Systems 005221-0 — Figure 1 — Interconnections diagram (page 38)
Fig. 10 · Figure 1 — Interconnections
Page 39 of the Generac Power Systems 005221-0 user manual — Figure 1 — Interconnections
Page 39 · click to enlarge
Page 39

1 0F3203 1 WELDMENT RAD SUPPORT 3.9L C2 2 035685 4 CLAMP HOSE #28 1.32-2.25 3 0F2608 1 RADIATOR 598 X 568 X 49 CPL RH 4 0F4413 1 HOSE UPPER RAD CPL C2 3.9L 5 0F4414 1 HOSE LOWER RAD CPL C2 3.9L 6 0E7854 1 CLUTCH COOLING FAN 7 0F2820 1 FAN 22" DIA 10 BLADE 8 051756 4 SCREW HHC M10-1.5 X 20 G8.8 9 046526 4 WASHER LOCK M10 10 022131 4 WASHER FLAT 3/8-M10 ZINC 11 0F3312 1 DUCT INNER DISCHARGE TOP C2 12 0C2454 13 SCREW THF M6-1 X 16 N WA Z/JS 13 0F8651 8 SCREW HHFC M8-1.25 X 20 W/M6 14 022129 8 WASHER LOCK M8-5/16 17 022097 8 WASHER LOCK M6-1/4 18 0C8566 8 SCREW HHFC M6-1.0 X 20 G8.8 19 0E3257 4 SCREW HWHTF M6-1.0 X 16 20 0F3313 1 DUCT INNER DISCHARGE C2 21 080712 1 BRKT COOLANT RECOVERY TANK 22 076749 1 TANK COOLANT RECOVERY 23 048031C 1 CLAMP HOSE BAND 1/4 24 0F4051D 3 INSULATION INNER DUCT 25 0F4073C 1 INSUL DUCT SIDE OR INNER DUCT 26 0F3890 3 RETAINER INSULATION (450) 27 0F3890C 2 RETAINER INSULATION (220) 28 0F3072 10 INSULATION RETAINMENT HANGER 29 078115 10 WASHER SELF LOCKING DOME 30 089961 1 FOAM STRIP 3/4" WIDE X 3/16" THK (46” LG) 31 052250 2 TAPE FOAM 1 X 1 (22.5” LG) 32 0F4767 1 TUBE FAN CLUTCH PREHTR UPPR C2 33 0F8085 1 GUARD FAN C2 CPL, BOTTOM 34 0F4765 1 FTG CMPN BLKHD 3/8" OD TUBE BRS 35 089514 1 FTG CMPR 3/8TUBE X 3/8 NPT W/FERL 36 055596 1 BARBED STR 3/8 NPT X 3/8 37 0C7649 1 CLAMP HOSE .38-.87 38 069860E 1 HOSE DRAIN ASSY 28" 39 * 069811 REF. CAP HEX 1/4 NPT BRASS 40 065852 1 SPRING CLIP HOLDER .37-.62 41 045764 1 SCREW HHTT M4-0.7 X 8 BP 43 089685 1 GROMMET .75 X .12 X .50 44 0F4768 1 TUBE FAN CLUTCH PREHTR LOWR C2 45 0F8085A 1 GUARD FAN C2 CPL, TOP 46 090283 1 CAP RADIATOR 13 PSI

* ITEM #39 IS INCLUDED WITH ITEM #38.

Page 40 of the Generac Power Systems 005221-0 user manual — Figure 1 — Interconnections
Page 40 · click to enlarge
Page 40
Generac Power Systems 005221-0 — Figure 1 — Interconnections diagram (page 40)
Fig. 11 · Figure 1 — Interconnections
Page 41 of the Generac Power Systems 005221-0 user manual — Figure 1 — Interconnections
Page 41 · click to enlarge
Page 41

1 0F6504 1 PIPE R/H SIDE MUFFLER 2 0F3127 1 PIPE L/H SIDE 3.9L CPL 3 0F2808B 1 PIPE EXHAUST MUFFLER OUT 4 0F0738 1 MUFFLER 7" X 9"-(2) 2" IN/2.5" OUT 5 0F2962 1 MUFFLER STRAP 6 0F2830 1 MUFFLER BRACKET STIFFENER 7 047411 2 SCREW HHC M6-1.0 X 16 G8.8 8 022097 2 WASHER LOCK M6-1/4 9 022473 2 WASHER FLAT 1/4-M6 ZINC 10 080762 1 BOLT U 3/8-16 X 2.62 11 0D9832 4 SCREW HHC M12-1.75 X 75 SS 12 087171 8 WASHER FLAT 1/2 SS 13 083215 4 WASHER LOCK 1/2 SS 14 051548 4 NUT HEX M12-1.75 G8 SS 15 0F3794 1 EXHAUST BLANKET 549MM LONG (R/H) 16 0F3794A 1 EXHAUST BLANKET 448MM LONG (L/H) 17 0E8816 1 EXHAUST FLANGE 2" PIPE 19 036797 4 BOLT U 5/16-18 X 2.25 20 024114 8 NUT HEX 5/16-24 STEEL 21 022129 8 WASHER LOCK M8-5/16 22 0F5078 1 PIPE L/H SIDE MUFFLER 23 0F3133 1 PIPE R/H SIDE 3.9L CPL

Page 42 of the Generac Power Systems 005221-0 user manual — Figure 1 — Interconnections
Page 42 · click to enlarge
Page 42
Generac Power Systems 005221-0 — Figure 1 — Interconnections diagram (page 42)
Fig. 12 · Figure 1 — Interconnections
Page 43 of the Generac Power Systems 005221-0 user manual — Figure 1 — Interconnections
Page 43 · click to enlarge
Page 43
Generac Power Systems 005221-0 — Figure 1 — Interconnections diagram (page 43)
Fig. 13 · Figure 1 — Interconnections

1 0F6322 1 BOTTOM PLATE, AIR CLEANER 3.9L 2 0F5418 1 ELEMENT AIR FILTER 3 0E6406 1 HOLDER VENTURI 4 0E7702 1 HOLD DOWN AIR CLEANER 5 0F6323 1 PLATE, AIR CLEANER TOP 3.9L 6 037561 1 NUT WING 1/4-20 NYLK 7 049815 4 SCREW HHC M5-0.8 X 16 G8.8 8 049226 4 WASHER LOCK M5 9 051713 4 WASHER FLAT M5 10 0E6586 1 GASKET BOSCH 32 & 40

Page 44 of the Generac Power Systems 005221-0 user manual — Figure 1 — Interconnections
Page 44 · click to enlarge
Page 44
Generac Power Systems 005221-0 — Figure 1 — Interconnections diagram (page 44)
Fig. 14 · Figure 1 — Interconnections
Page 45 of the Generac Power Systems 005221-0 user manual — Figure 1 — Interconnections
Page 45 · click to enlarge
Page 45
Generac Power Systems 005221-0 — Figure 1 — Interconnections diagram (page 45)
Fig. 15 · Figure 1 — Interconnections
Page 46 of the Generac Power Systems 005221-0 user manual — Figure 1 — Interconnections
Page 46 · click to enlarge
Page 46
Generac Power Systems 005221-0 — Figure 1 — Interconnections diagram (page 46)
Fig. 16 · Figure 1 — Interconnections
Page 47 of the Generac Power Systems 005221-0 user manual — Figure 1 — Interconnections
Page 47 · click to enlarge
Page 47

1 033212 4 SCREW HHC 5/16-18 X 1-1/4 G5 2 075580 1 FLANGE FUEL INLET 3 0F6390 1 REGULATOR ASSEMBLY DUAL FUEL 4 039253 2 SCREW HHC M8-1.25 X 20 G8.8 5 022145 2 WASHER FLAT 5/16-M8 ZINC 6 022129 6 WASHER LOCK M8-5/16 7 045771 2 NUT HEX M8-1.25 G8 CLEAR ZINC 9 0E8286 1 STREET EL 45 DEG 1/2" NPT BRASS 10 026812 2 ELBOW 90D 3/4 NPT 11 0F8379 1 NIPPLE PIPE 3/4 NPT X 7” 12 0F3869 1 (REF.) SWITCH PRESSURE GAS 5" RISE (INCLUDED WITH I/N 3) 13 057823 2 CLAMP HOSE #10 .56-1.06 14 059194 1 HOSE 5/8 ID LPG & NG (31.5” LG) 15 064945 1 GASKET CARB ADAPTOR 16 0D1509 1 DECAL INLET PRESSURE 17 * 050279 1 DECAL FUEL INLET NG (NATURAL GAS APPLICATION) 050280 1 DECAL FUEL INLET LPG (LP VAPOR APPLICATION) 18 0E7839 1 MACHINING CARBURETOR ADAPTOR 19 0E6586 1 GASKET BOSCH 32 & 40 20 0E4394 1 ACTUATOR BOSCH 40 GOVERNOR 21 040105 1 HOSE COOL 2IN ID 20R4 (2” LG) 22 0E6382B 1 (REF) VENTURI HOLDER W/40MM ACTUATOR 23 0E7121 1 (REF) O-RING 47.625 ID X 2.38 WIDTH 24 0E6376B 1 (REF) VENTURI 28 ID THROTTLE W/CHOKE 25 042561 2 CLAMP HOSE #36 1.88-2.75 26 0E9295 1 ASSY THROTTLE 28MM 27 061012 1 PLUG STD PIPE 1/8 SOCKET HEAD 28 022097 4 WASHER LOCK M6-1/4 29 044118 1 BARBED STR 1/2 NPT X 5/8 30 046580 4 SCREW SHC M6-1.0 X 45 G12.9 31 026915 2 NIPPLE CLOSE 3/4 X 1.375 33 0F6155 1 HARNESS CPL FUEL JUMPER

NOTES: 1. REGULATOR (I/N 3) AS SHOWN IN ILLUSTRATION IS SET UP FOR NATURAL GAS APPLICATION. 2. TO CONFIGURE REGULATOR FOR LP VAPOR, SWITCH HOSE BARB, HOSE CLAMP (I/N 13) AND HOSE (I/N 14) FROM “OUT-1” TO “OUT-2”. REPLACE PIPE PLUG FROM “OUT-2” TO “OUT-1”. USE PIPE SEALANT ON HOSE BARB AND PIPE PLUG. MAKE SURE TO KEEP PORTS FREE FROM DEBRIS DURING RECONFIGURATION PROCESS. 3*. FOR LP VAPOR APPLICATION SUBSTITUE LPG FUEL INLET DECAL P/N 050280 FOR NG FUEL INLET DECAL P/N 050279 (ITEM17). 4 . WHEN SWITCHING FUEL TYPES, THE PROPER DIP SWITCH SITTINGS MUST BE MADE TO THE CONTROL PANEL. SEE OWNERS MANUAL, FUEL SECTION FOR MORE DETAILS.

Page 48 of the Generac Power Systems 005221-0 user manual — Figure 1 — Interconnections
Page 48 · click to enlarge
Page 48
Generac Power Systems 005221-0 — Figure 1 — Interconnections diagram (page 48)
Fig. 17 · Figure 1 — Interconnections
Page 49 of the Generac Power Systems 005221-0 user manual — *** 3.0L ONLY
Page 49 · click to enlarge
Page 49
Generac Power Systems 005221-0 — Figure 1 — Interconnections diagram (page 49)
Fig. 18 · Figure 1 — Interconnections

1 0F5853 (XX) 1 REAR WRAP C2 2 0C2454 68 SCREW THF M6-1 X 16 N WA Z/JS 3 0F5849 (XX) 2 DOOR C2 4 087233 2 RIVET POP .1875 X .450 SS 5 0E3257 4 SCREW TH-FRM M6 W/CAP SHKPRF W 6 0F5852 (XX) 2 DISCHARGE DUCT,LH & RH SIDE C2 7 0F5850 (XX) 2 FRONT CORNERS C2 8 0F5851 (XX) 1 DISCHARGE CENTER DUCT C2 9 0F3313 1 (REF.) DUCT INNER DISCHARGE C2 10 0F3312 1 (REF.) DUCT INNER DISCHARGE TOP C2 11 0F5848 1 ROOF C2 ALUM 12 0F2786 2 SLITTER C4 13 0F2785 1 SPLITTER LOWER C4 14 0F3364 1 SPLITTER STINGER C2 15 0F4880 2 SUPPORT SPLITTER LH C2 16 0F5049 2 TAB PULL 17 0C2634A 1 ASSEMBLY COVER ACCESS 18 022473 3 WASHER FLAT 1/4-M6 ZINC 19 022097 1 WASHER LOCK M6-1/4 20 022127 1 NUT HEX 1/4-20 STEEL 21 0F3072 16 INSULATION RETAINMENT HANGER 22 078115 48 WASHER SELF LOCKING DOME 23 0F4051 2 INSULATION DOOR C2 24 0F4051A 1 INSULATION ROOF TOP 25 0F5048 2 LATCH VISE ACTION 5/16HEX SOCK 26 0E5968 1 GASKET EXTRUDED TRIM (440.64” LG) 27 0F3760K 2 INSULATION SPLITTER 28 0F3760E 2 INSULATION SPLITTER 29 0F4051C 2 INSULATION DUCT 30 0F3890B 8 RETAINER INSULATION (820) 31 0F4051B 2 INSULATION DUCT SIDES 32 0F3890 4 RETAINER INSULATION (450) 33 0F3890A 3 RETAINER INSULATION (740) 34 0F3760L 1 INSULATION LOWER SPLITTER 35 042568 2 SCREW HHC M6-1.0 X 20 G8.8 36 0912970094 2 ASSY WIRE 14 AWG 34.8" GRN/YEL 37 022447 2 WASHER SHAKEPROOF INT 1/4 38 049813 2 NUT HEX M6 X 1.0 G8 YEL CHR 39 ** 077992 21 NUT HEX LOCK M6-1.0 SS NY INS 40 * 0F6321 1 ROOF RAIN DEFLECTOR 43 *** 0C3397 4 FASTENER RATCHET

OPTIONAL COMPARTMENT MATERIALS: ALL P/N’S WITH AN (XX) SUFFIX INDICATE A MULTIPLE MATERIAL AND COLOR OPTION. USE THE FOLLOWING LEGEND TO IDENTIFY THE CORRECT PART NUMBER:

PART NO. MATERIAL COLOR 0XXXXXSN STEEL TAN 0XXXXXAN ALUMINUM TAN 0XXXXXSG STEEL GRAY 0XXXXXAG ALUMINUM GRAY

* 3.9L ONLY

** ALUMINUM ENCLOSURE NOTE: ALL ENCLOSURE PANELS THAT FASTEN TO THE BASE FRAME MUST BE SECURED USING ITEM 2 & 5 THREAD FORMING FASTENER AND ITEM 39 LOCK NUT. LOCK NUT IS TO BE INSTALLED AFTER THREAD FORMING FASTENER HAS PENETRATED THROUGH EXTRUSIONS IN ENCLOSURE PANELS. ALL ROOF PANELS ARE TO BE SECURED IN THE SAME MANNER.

*** 3.0L ONLY

Page 50 of the Generac Power Systems 005221-0 user manual — Figure 1 — Interconnections
Page 50 · click to enlarge
Page 50
Generac Power Systems 005221-0 — Figure 1 — Interconnections diagram (page 50)
Fig. 19 · Figure 1 — Interconnections
Page 51 of the Generac Power Systems 005221-0 user manual — Figure 1 — Interconnections
Page 51 · click to enlarge
Page 51
Generac Power Systems 005221-0 — Figure 1 — Interconnections diagram (page 51)
Fig. 20 · Figure 1 — Interconnections
Page 52 of the Generac Power Systems 005221-0 user manual — Figure 1 — Interconnections
Page 52 · click to enlarge
Page 52
Generac Power Systems 005221-0 — Figure 1 — Interconnections diagram (page 52)
Fig. 21 · Figure 1 — Interconnections
Page 53 of the Generac Power Systems 005221-0 user manual — Figure 1 — Interconnections
Page 53 · click to enlarge
Page 53
Generac Power Systems 005221-0 — Figure 1 — Interconnections diagram (page 53)
Fig. 22 · Figure 1 — Interconnections
Page 54 of the Generac Power Systems 005221-0 user manual — Figure 1 — Interconnections
Page 54 · click to enlarge
Page 54
Generac Power Systems 005221-0 — Figure 1 — Interconnections diagram (page 54)
Fig. 23 · Figure 1 — Interconnections
Page 55 of the Generac Power Systems 005221-0 user manual — Figure 1 — Interconnections
Page 55 · click to enlarge
Page 55
Generac Power Systems 005221-0 — Figure 1 — Interconnections diagram (page 55)
Fig. 24 · Figure 1 — Interconnections
Page 56 of the Generac Power Systems 005221-0 user manual — Figure 1 — Interconnections
Page 56 · click to enlarge
Page 56
Generac Power Systems 005221-0 — Figure 1 — Interconnections diagram (page 56)
Fig. 25 · Figure 1 — Interconnections
Page 57 of the Generac Power Systems 005221-0 user manual — Figure 1 — Interconnections
Page 57 · click to enlarge
Page 57
Generac Power Systems 005221-0 — Figure 1 — Interconnections diagram (page 57)
Fig. 26 · Figure 1 — Interconnections
Page 58 of the Generac Power Systems 005221-0 user manual — Figure 1 — Interconnections
Page 58 · click to enlarge
Page 58
Generac Power Systems 005221-0 — Figure 1 — Interconnections diagram (page 58)
Fig. 27 · Figure 1 — Interconnections
Page 59 of the Generac Power Systems 005221-0 user manual — Figure 1 — Interconnections
Page 59 · click to enlarge
Page 59
Generac Power Systems 005221-0 — Figure 1 — Interconnections diagram (page 59)
Fig. 28 · Figure 1 — Interconnections
Page 60 of the Generac Power Systems 005221-0 user manual — Ph: (262) 544-4811 • Fax: (262) 544-4851
Page 60 · click to enlarge
Page 60

Warranty

GENERAC POWER SYSTEMS STANDARD LIMITED WARRANTY FOR HOME STANDBY/LIGHT COMMERCIAL PRODUCT 45kW AND BELOW

For a period of two (2) years from the date of sale, or start-up by Authorized/Certified Generac Power Systems Dealer, or branch thereof, Generac Power Systems, Inc. will, at its option, repair or replace any part(s) which, upon examination, inspection, and testing by Generac Power Systems or an Authorized/Certified Generac Power Systems Dealer, or branch thereof, is found to be defective under normal use and service, in accordance with the warranty schedule set forth below. Any equipment that the purchaser/owner claims to be defective must be examined by the nearest Authorized/ Certified Generac Power Systems Dealer, or branch thereof. This warranty applies only to Generac Power Systems Generators used in "Standby" applications, as Generac Power Systems, Inc. has defined Standby, provided said generator has been properly installed and inspected on-site by appropriate personnel. Scheduled maintenance, as outlined by the generator owner's manual, is highly recommended. This should be performed by an Authorized/Certified Generac Power Systems Dealer, or branch thereof. This will verify service has been performed on the unit throughout the warranty period.

  • WARRANTY SCHEDULE YEARS ONE and TWO — Limited comprehensive coverage on mileage, labor, and parts listed.
  • - ALL COMPONENTS *Start-up and/or On-line Registration, or Registration Card, along with Proof of Purchase, must be performed and/or sent in. Guidelines:
  • Any and all warranty repairs and/or concerns, must be performed and/or addressed by an Authorized/Certified Generac Power Systems Dealer, or branch thereof.
  • A Generac Power Systems, Inc. Transfer Switch is highly recommended to be used in conjunction with the genset. If a Non - Generac Power Systems, Inc. Transfer Switch is substituted for use and directly causes damage to the genset, no warranty coverage shall apply.
  • All warranty expense allowances are subject to the conditions defined in Generac Power Systems Warranty, Policies, and Procedures Flat Rate Manual.
  • Units that have been resold are not covered under the Generac Power Systems Warranty, as this Warranty is not transferable.
  • Unit enclosure is only covered against rust or corrosion the first year of the warranty provision.
  • Use of Non-Generac replacement part(s) will void the warranty in its entirety.
  • Engine coolant heaters (block-heaters), heater controls and circulating pumps are only covered during the first year of the warranty provision (If applicable).

THIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING: 1. Any unit built/manufactured prior to January 1, 2005. 2. Costs of normal maintenance (i.e. tune-ups, associated part(s), adjustments, loose/leaking clamps, installation and start-up). 3. Any failure caused by contaminated fuels, oils, coolants/antifreeze or lack of proper fuels, oils or coolants/antifreeze. 4. Units sold, rated or used for "Prime Power", "Trailer Mounted" or "Rental Unit" applications as Generac Power Systems have defined Prime Power,

Trailer Mounted or Rental Unit. Contact a Generac Power Systems Distributor for Prime Power, Trailer Mounted or Rental Unit definition and warranty. 5. Units used for prime power in place of existing utility power where utility is present or in place of utility power where utility power service does not

normally exist. 6. Failures caused by any external cause or act of God such as, but not limited to, collision, fire, theft, freezing, vandalism, riot or wars, lightning,

earthquake, windstorm, hail, volcanic eruption, water or flood, tornado, hurricane, terrorist acts or nuclear holocaust. 7. Products that are modified or altered in a manner not authorized by Generac Power Systems in writing. 8. Failures due, but not limited to, normal wear and tear, accident, misuse, abuse, negligence, or improper installation or sizing. 9. Any incidental, consequential or indirect damages caused by defects in materials or workmanship, or any delay in repair or replacement of the

defective part(s). 10. Failure due to misapplication, misrepresentation, or bi-fuel conversion. 11. Telephone, facsimile, cell phone, satellite, internet, or any other communication expenses. 12. Rental equipment used while warranty repairs are being performed (i.e. rental generators, cranes, etc.). 13. Overtime, holiday, or emergency labor. 14. Planes, ferries, railroad, busses, helicopters, snowmobiles, snow-cats, off-road vehicle or any other mode of transportation deemed abnormal. 15. Any and all expenses incurred investigating performance complaints unless defective Generac materials and/or workmanship were the direct

cause of the problem. 16. Starting batteries, fuses, light bulbs, engine fluids, and overnight freight cost for replacement part(s).

THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, SPECIFICALLY, GENERAC POWER SYSTEMS MAKES NO OTHER WARRANTIES AS TO THE MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to purchaser/owner.

GENERAC POWER SYSTEMS ONLY LIABILITY SHALL BE THE REPAIR OR REPLACEMENT OF PART(S) AS STATED ABOVE. IN NO EVENT SHALL GENERAC POWER SYSTEMS BE LIABLE FOR ANY INCIDENTAL, OR CONSEQUENTIAL DAMAGES, EVEN IF SUCH DAMAGES ARE A DIRECT RESULT OF GENERAC POWER SYSTEMS, INC. NEGLIGENCE.

Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations may not apply to purchaser/ owner. Purchaser/owner agrees to make no claims against Generac Power Systems, Inc. based on negligence. This warranty gives purchaser/owner specific legal rights. Purchaser/owner also may have other rights that vary from state to state.

  • Generac Power Systems, Inc.
  • P.O. Box 8
  • Waukesha, WI 53187

Ph: (262) 544-4811 • Fax: (262) 544-4851

Bulletin 0171360SVE / Printed in U.S.A. 7.05

Printed in U.S.A.

Display codes

Error codes

What the fault codes shown on the display mean and how to clear them.

CodeMeaningFix
QT100QT150. p.13
Fix-it

Troubleshooting

Common problems, likely causes, and what to do.

ProblemPossible causeRemedy
1-3 p.5
8-1 p.13

Ask about the Generac Power Systems 005221-0

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.