Generac Power Systems 0043734

64 pages·4.3 MB·Portable Generator·PDF·ENDEFRITNLJA
Generac Power Systems 0043734
Table of Contents 80 sections Liquid-cooled, Prepackaged · Standby Generators · Models: 0043733, 0043734 & 0043735 (40 kW/Single-phase w/ 200 Amp Transfer Switch) · Not intended for use in critical life support applications. ! ! · … ShowHide
Liquid-cooled, Prepackagedp.1Standby Generatorsp.1Models: 0043733, 0043734 & 0043735 (40 kW/Single-phase w/ 200 Amp Transfer Switch)p.1Not intended for use in critical life support applications. ! !p.1CONTENTSp.2READ THIS MANUAL THOROUGHLYp.2OPERATION AND MAINTENANCEp.2DANGERp.2HOW TO OBTAIN SERVICEp.2NOTE:p.2Model No. ____________ Serial No. ______________p.2AUTHORIZED DEALER LOCATIONp.21-800-333-1322p.2ELECTRICAL HAZARDSp.5FIRE HAZARDSp.5EXPLOSION HAZARDSp.5Figure 1.1 – Single-phase Generator AC Connection Systemp.61.1.1 LIFTING THE GENERATORp.61.8.2 GENERATOR AND LOAD COMPATIBILITYp.81.8.3 ENGINEp.81.9.1 CONVERSION TO LP GAS VAPORp.8Fuel Consumptionp.8Figure 1.3 – Conversion to LP Gas Vaporp.8Figure 1.4 - Emissions Control Systemp.91.12.1 AIR FUEL RATIO CONTROLLERp.9STANDBY GENERATOR INSTALLATIONp.10OTHER PUBLISHED STANDARDSp.10NFPA STANDARDSp.10Figure 2.1 – Basic Standby Electric Systemp.11Figure 2.2 – Generator Grounding Lug (typical)p.112.6 TRANSFER SWITCH START SIGNAL CONNECTIONSp.112.6.1 PRE-PACKAGED TYPE SWITCHp.112.6.2 “GTS” Type Engineered Switchp.112.7.1 VENTED BATTERIESp.122.7 BATTERY INSTALLATIONp.122.8.1 PRIOR TO INITIAL START-UPp.132.8.6 BELT TENSIONp.132.8.7 ELECTRICAL SYSTEMp.132.8.2 TRANSFER SWITCHp.132.8.8 RODENT PROTECTIONp.132.8.3 FUEL SYSTEMp.13Figure 2.3 - Base Frame Cap Plugsp.132.8.4 GENERATOR SET LUBRICATIONp.132.8.5 ENGINE COOLANTp.133.1.6 AUTO/OFF/MANUAL SWITCHp.143.1.7 FAULT INDICATOR LAMPp.14Figure 3.1 – Control Consolep.143.1.8 15-AMP FUSEp.143.1.9 7.5 AMP INLINE FUSE (NOT SHOWN)p.143.1.1 AC VOLTMETERp.143.1.2 AC AMMETERp.143.1.10 VOLTAGE-PHASE SELECTOR SWITCHp.143.1.3 AC FREQUENCY METERp.143.1.11 SET EXERCISE TIME SWITCHp.143.2 USING THE AUTO/OFF/MANUAL SWITCHp.143.1.4 DC VOLTMETERp.143.2.1 “AUTO” POSITIONp.143.1.5 HOURMETERp.143.2.2 “OFF” POSITIONp.153.2.3 “MANUAL” POSITIONp.153.3 AUTOMATIC TRANSFER OPERATION To select automatic operation, do the following:p.15Figure 3.2 – Engine Block Heaterp.16OUTLETp.16Figure 3.3 – “Set Exercise” Switch on Control Panelp.16INLETp.16Figure 4.1 – Oil Dipstick and Fillp.17Figure 4.2 – Oil Filterp.174.2 CHANGING THE ENGINE OIL AND FILTERp.174.2.1 ENGINE OIL RECOMMENDATIONSp.174.2.2 OIL AND FILTER CHANGE PROCEDUREp.17Figure 4.3 – Engine Air Cleanerp.18Figure 4.4 – Setting the Spark Plug Gapp.180.045 inch (1.1 mm)p.184.5.1 BATTERY REPLACEMENTp.184.10 MISCELLANEOUS MAINTENANCEp.194.10.1 CLEANING THE GENERATORp.194.10.2 RODENT PROTECTIONp.19Figure 4.4 – Location of 15-amp Fusep.194.11.2 RETURN TO SERVICEp.204.11 OUT OF SERVICE PROCEDUREp.20
Page 1 of the Generac Power Systems 0043734 user manual — Not intended for use in critical life support applications. ! !
Page 1 · click to enlarge
Page 1
Generac Power Systems 0043734 — Liquid-cooled, Prepackaged diagram (page 1)
Fig. 1 · Liquid-cooled, Prepackaged

Liquid-cooled, Prepackaged

Standby Generators

Models: 0043733, 0043734 & 0043735 (40 kW/Single-phase w/ 200 Amp Transfer Switch)

Generac Power Systems 0043734 — Liquid-cooled, Prepackaged diagram (page 1)
Fig. 2 · Liquid-cooled, Prepackaged

0046262, 0046263 & 0046264 (40 kW/Single-phase w/ 200 Amp Transfer Switch California Emissions)

Not intended for use in critical life support applications. ! !

Page 2 of the Generac Power Systems 0043734 user manual — Table of Contents
Page 2 · Contents
Contents

Contents

Liquid-cooled, Prepackagedp.1Standby Generatorsp.1Models: 0043733, 0043734 & 0043735 (40 kW/Single-phase w/ 200 Amp Transfer Switch)p.1Not intended for use in critical life support applications. ! !p.1CONTENTSp.2READ THIS MANUAL THOROUGHLYp.2OPERATION AND MAINTENANCEp.2DANGERp.2HOW TO OBTAIN SERVICEp.2NOTE:p.2Model No. ____________ Serial No. ______________p.2AUTHORIZED DEALER LOCATIONp.21-800-333-1322p.2ELECTRICAL HAZARDSp.5FIRE HAZARDSp.5EXPLOSION HAZARDSp.5Figure 1.1 – Single-phase Generator AC Connection Systemp.61.1.1 LIFTING THE GENERATORp.61.8.2 GENERATOR AND LOAD COMPATIBILITYp.81.8.3 ENGINEp.81.9.1 CONVERSION TO LP GAS VAPORp.8Fuel Consumptionp.8Figure 1.3 – Conversion to LP Gas Vaporp.8Figure 1.4 - Emissions Control Systemp.91.12.1 AIR FUEL RATIO CONTROLLERp.9STANDBY GENERATOR INSTALLATIONp.10OTHER PUBLISHED STANDARDSp.10NFPA STANDARDSp.10Figure 2.1 – Basic Standby Electric Systemp.11Figure 2.2 – Generator Grounding Lug (typical)p.112.6 TRANSFER SWITCH START SIGNAL CONNECTIONSp.112.6.1 PRE-PACKAGED TYPE SWITCHp.112.6.2 “GTS” Type Engineered Switchp.112.7.1 VENTED BATTERIESp.122.7 BATTERY INSTALLATIONp.122.8.1 PRIOR TO INITIAL START-UPp.132.8.6 BELT TENSIONp.132.8.7 ELECTRICAL SYSTEMp.132.8.2 TRANSFER SWITCHp.132.8.8 RODENT PROTECTIONp.132.8.3 FUEL SYSTEMp.13Figure 2.3 - Base Frame Cap Plugsp.132.8.4 GENERATOR SET LUBRICATIONp.132.8.5 ENGINE COOLANTp.133.1.6 AUTO/OFF/MANUAL SWITCHp.143.1.7 FAULT INDICATOR LAMPp.14Figure 3.1 – Control Consolep.143.1.8 15-AMP FUSEp.143.1.9 7.5 AMP INLINE FUSE (NOT SHOWN)p.143.1.1 AC VOLTMETERp.143.1.2 AC AMMETERp.143.1.10 VOLTAGE-PHASE SELECTOR SWITCHp.143.1.3 AC FREQUENCY METERp.143.1.11 SET EXERCISE TIME SWITCHp.143.2 USING THE AUTO/OFF/MANUAL SWITCHp.143.1.4 DC VOLTMETERp.143.2.1 “AUTO” POSITIONp.143.1.5 HOURMETERp.143.2.2 “OFF” POSITIONp.153.2.3 “MANUAL” POSITIONp.153.3 AUTOMATIC TRANSFER OPERATION To select automatic operation, do the following:p.15Figure 3.2 – Engine Block Heaterp.16OUTLETp.16Figure 3.3 – “Set Exercise” Switch on Control Panelp.16INLETp.16Figure 4.1 – Oil Dipstick and Fillp.17Figure 4.2 – Oil Filterp.174.2 CHANGING THE ENGINE OIL AND FILTERp.174.2.1 ENGINE OIL RECOMMENDATIONSp.174.2.2 OIL AND FILTER CHANGE PROCEDUREp.17Figure 4.3 – Engine Air Cleanerp.18Figure 4.4 – Setting the Spark Plug Gapp.180.045 inch (1.1 mm)p.184.5.1 BATTERY REPLACEMENTp.184.10 MISCELLANEOUS MAINTENANCEp.194.10.1 CLEANING THE GENERATORp.194.10.2 RODENT PROTECTIONp.19Figure 4.4 – Location of 15-amp Fusep.194.11.2 RETURN TO SERVICEp.204.11 OUT OF SERVICE PROCEDUREp.20
Page 5 of the Generac Power Systems 0043734 user manual — EXPLOSION HAZARDS
Page 5 · click to enlarge
Page 5
  • Inspect the generator regularly, and promptly repair or replace all worn, damaged or defective parts using only factory-approved parts.
  • Before performing any maintenance on the generator, disconnect its battery cables to prevent accidental start-up. Disconnect the cable from the battery post indicated by a NEGATIVE, NEG or (–) first. Reconnect that cable last.
  • Never use the generator or any of its parts as a step. Stepping on the unit can stress and break parts, and may result in dangerous operating conditions from leaking exhaust gases, fuel leakage, oil leakage, etc.
  • Generators installed with an automatically transfer switch will crank and start automatically when normal (utility) source voltage is removed or is below an acceptable preset level. To prevent such automatic start-up and possible injury to personnel, disable the generator’s automatic start circuit (battery cables, etc.) before working on or around the unit. Then, place a “Do Not Operate” tag on the generator control panel and on the transfer switch.
  • In case of accident caused by electric shock, immediately shut down the source of electrical power. If this is not possible, attempt to free the victim from the live conductor. AVOID DIRECT CONTACT WITH THE VICTIM. Use a nonconducting implement, such as a dry rope or board, to free the victim from the live conductor. If the victim is unconscious, apply first aid and get immediate medical help.
  • Never wear jewelry when working on this equipment. Jewelry can conduct electricity resulting in electric shock, or may get caught in moving components causing injury.

ELECTRICAL HAZARDS

  • All generators covered by this manual produce dangerous electrical voltages and can cause fatal electrical shock. Utility power delivers extremely high and dangerous voltages to the transfer switch as does the standby generator when it is in operation. Avoid contact with bare wires, terminals, connections, etc., while the unit is running. Ensure all appropriate covers, guards and barriers are in place before operating the generator. If work must be done around an operating unit, stand on an insulated, dry surface to reduce shock hazard.
  • Do not handle any kind of electrical device while standing in water, while barefoot, or while hands or feet are wet. DANGEROUS ELECTRICAL SHOCK MAY RESULT.
  • If people must stand on metal or concrete while installing, operating, servicing, adjusting or repairing this equipment, place insulative mats over a dry wooden platform. Work on the equipment only while standing on such insulative mats.
  • The National Electrical Code (NEC) requires the frame and external electrically conductive parts of the generator to be connected to an approved earth ground and/or grounding rods. This grounding will help prevent dangerous electrical shock that might be caused by a ground fault condition in the generator set or by static electricity. Never disconnect the ground wire.
  • Wire gauge sizes of electrical wiring, cables and cord sets must be adequate to handle the maximum electrical current (ampacity) to which they will be subjected to.
  • Before installing or servicing this (and related) equipment, make sure that all power voltage supplies are positively turned off at their source. Failure to do so will result in hazardous and possibly fatal electrical shock.
  • Connecting this unit to an electrical system normally supplied by an electric utility shall be by means of a transfer switch so as to isolate the genrator electric system from the utility electric system while in operation. Failure to isolate the two electric system power sources from each other by such means will result in damage to the generator and may also result in injury or death to utility power workers due to backfeed of electrical energy.

FIRE HAZARDS

  • Keep a fire extinguisher near the generator at all times. DO NOT use any carbon tetra-chloride type extinguisher. Its fumes are toxic, and the liquid can deteriorate wiring insulation. Keep the extinguisher properly charged and be familiar with its use. If there are any questions pertaining to fire extinguishers, consult the local fire department.

EXPLOSION HAZARDS

  • Properly ventilate any room or building housing the generator to prevent build-up of explosive gas.
  • Do not smoke around the generator. Wipe up any fuel or oil spills immediately. Ensure that no combustible materials are left in the generator compartment, or on or near the generator, as FIRE or EXPLOSION may result. Keep the area surrounding the generator clean and free from debris.
  • Generac generator sets may operate using one of several types of fuels. All fuel types are potentially FLAMMABLE and/orEXPLOSIVE and should be handled with care. Comply with all laws regulating the storage and handling of fuels. Inspect the unit’s fuel system frequently and correct any leaks immediately. uel supply lines must be properly installed, purged and leak tested according to applicable fuel-gas codes before placing this equipment into service.
  • Diesel fuels are highly FLAMMABLE. Gaseous fluids such as natural gas and liquid propane (LP) gas are extremely EXPLOSIVE. Natural gas is lighter than air, and LP gas is heavier than air; install leak detectors accordingly.
Page 6 of the Generac Power Systems 0043734 user manual — !
Page 6 · click to enlarge
Page 6

Section 1 — General Information

1.1 UNPACKING/INSPECTION After unpacking, carefully inspect the contents for dam- age.

When the two windings are connected in series, a 240- volt, 60-Hertz AC output results. Typically, the two “hot” leads in the circuit are Wires 11 and 44. The neutral leads are the junction of Wires 22 and 33.

  • This standby generator set has been factory installed in an all-weather, metal enclosure that is intended exclusively for outdoor installation.

Figure 1.1 – Single-phase Generator AC Connection System

If this generator is used to power electrical load circuits normally powered by a utility power source, code requires to install a transfer switch. The transfer switch must effectively isolate the electrical system from the utility distribution sys- tem when the generator is operating (NEC 701). Failure to isolate an electrical system by such means will result in damage to the generator and also may result in injury or death to utility power workers due to backfeed of electrical energy. If any loss or damage is noted at time of delivery, have the person(s) making the delivery note all damage on the freight bill or affix his or her signature under the consignor's memo of loss or damage.

1.4 PREPACKAGED TRANSFER SWITCH The transfer switch shipped with this generator is rated 200 amps maximum at 120/240 volts AC single-phase. The enclosure of the transfer switch is NEMA 3R. This type of enclosure is intended for indoor or outdoor use.

If there is loss or damage after delivery, separate the damaged materials and contact the carrier for claim procedures.

Follow these rules:

  • Install the transfer switch on a firm, sturdy supporting structure.
  • To prevent switch distortion, level the switch if necessary. This can be done by placing washers between the switch enclosure and mounting surface.
  • Never install the switch where any corrosive substance might drop onto the enclosure.
  • Where practical, protect the switch against excessive moisture, dust, dirt, lint, and construction grit. Always prevent corrosive vapors from coming in contact with enclosure.

“Concealed damage” is understood to mean damage to the contents of a package that is not in evidence at the time of delivery, but is discovered later.

‹

1.1.1 LIFTING THE GENERATOR

When lifting or hoisting equipment is used, be careful not to touch overhead power lines.

The generator’s weight of more than 2,000 pounds requires proper tools and equipment, and qualified personnel to be used in all phases of handling and unpacking.

!

1.5 AUTOMATIC SYSTEM OPERATION When this generator, along with its transfer switch, has been installed and interconnected, a circuit board in the generator panel continuously monitors utility power source voltage. Should that voltage drop below a preset value, and remain at such a low state for a preset amount of time, the generator cranks and starts. After the gener- ator starts, the transfer switch transfers load circuits so the generator can power them.

1.2 THE GENERATOR This liquid-cooled, Guardian generator set is designed to supply electrical power to operate critical electrical loads during utility power failure. Use this generator as a source of electrical power for the operation of 120 and/or 240-volt, single-phase loads.

When utility source voltage has been restored, the switch transfers back to the utility source voltage, and the generator then shuts down after a brief cool-down time.

1.3 GENERATOR AC CONNECTION SYSTEMS Figure 1.1 represents a single-phase, four-wire genera- tor AC connection system. The stator assembly in this system consists of a pair of stationary windings with two leads brought out of each winding. Each single winding can supply a 120-volt, 60-Hertz AC output.

Neutral Block

Page 7 of the Generac Power Systems 0043734 user manual — Figure 1.1 – Single-phase Generator AC Connection System
Page 7 · click to enlarge
Page 7

Section 1 — General Information

1.6 MAIN CIRCUIT BREAKER ‹ 1.7.3 LOW COOLANT LEVEL SWITCH The generator’s main circuit breaker is included with the Should the engine coolant level drop below the level unit as shipped from the factory. The breaker for each high coolant temperature switch, it is possible f unit is described as follows: engine to overheat without automatic shut down. T vent such overheating without automatic shut dow Model Number Circuit Breaker Rating engine has a low coolant level sensor. If the engine c 0043733, 0043734, 0043735 200-amp breaker drops too low, the engine automatically shuts 0046262, 0046263, 0046264 200-amp breaker (Figure 1.2). 1.7 ENGINE PROTECTIVE DEVICES ‹ 1.7.4 OVERSPEED SHUTDOWN The engine has several safety switches that cause it to automatically shut down under the following condiThe control module assembly (CMA) circuit boa tions: low oil pressure, high coolant temperature, low liquid-cooled units receives AC frequency (rpm) s coolant level, engine overspeed and overcrank. directly from the stator AC power windings. Shou frequency exceed approximately 72 Hertz, circuit ‹ 1.7.1 LOW OIL PRESSURE SWITCH action will automatically shut down the engine. This switch is normally closed (N.C.) but is held open by ‹ 1.7.5 OVERCRANK SHUTDOWN engine oil pressure during engine running. Should operating oil pressure drop below approximately 10 psi (68 After 90 seconds of crank-rest cycles (about seve kPa), the switch contacts close, and the engine shuts down onds cranking/seven seconds at rest), this function automatically (Figure 1.2). cranking if the engine fails to start in that 90-s span. Figure 1.2 – Engine Protective Devices ‹ 1.7.6 DC FUSE This fuse is located on the front panel of the contr tem. It protects the panel wiring and components damaging overload. Always remove this fuse commencing work on the generator. The unit w start or crank if the fuse is blown. Replace the fus one of the same size, type, and rating. Generac u AGC fuse rated at 15 amps. 1.8 SPECIFICATIONS ◆ 1.8.1 GENERATOR Models 0043733, 0043734,, 004 0046262, 0046263, 004 Rated Maximum Continuous AC Power Output (kW)* Rated Voltage (volts) 12 Rated Maximum Continuous Current at 240 Volts, Single-phase (amps) Number of Rotor Poles Driven Speed of Rotor (rpm) ‹ 1.7.2 HIGH COOLANT TEMPERATURE SWITCH Type of Stator Fou This normally open (N.O.) thermostatic switch has a Rotor Excitation System Direct E sensing tip that is immersed in captive coolant. Should Brush-type the coolant temperature exceed approximately 121° C Stator Insulation Clas (250° F), the switch contacts close, which causes the Rotor Insulation Cla engine to shut down automatically (Figure 1.2). *Rated power of generator is subject to and limited by such factors as ambient t ture, altitude, engine condition and other factors. Engine power will decrease ab percent for each 1,000 feet above sea level; and also will decrease an additional 1 for each 6° C (10° F) above 15.5° C (60° F) ambient. Maximum output power of t ator is limited by maximum engine power.‹1.7.3 LOW COOLANT LEVEL SWITCH Generac® Power Systems, Inc.
Model NumberCircuit Breaker Rating 0043733, 0043734, 0043735 200-amp breaker 0046262, 0046263, 0046264 200-amp breaker
Page 8 of the Generac Power Systems 0043734 user manual — Fuel Consumption
Page 8 · click to enlarge
Page 8

Section 1 — General Information

‹

1.8.2 GENERATOR AND LOAD COMPATIBILITY

1.9 FUEL REQUIREMENTS AND RECOMMENDATIONS With LP gas, use only the vapor withdrawal system. This type of system uses the vapors formed above the liquid fuel in the storage tank.

The generator must be fully compatible with the rated voltage, number of phases and frequency of the con- nected electrical loads. The generator, connected elec- trical devices, or both, can be damaged if voltage, num- ber of phases and frequency are not compatible.

Recommended fuels should have a Btu content of at least 1,000 Btus per cubic foot for natural gas; or at least 2,520 Btus per cubic foot for LP gas. Ask your fuel supplier for the Btu content of your fuel.

NOTE:

This manual assumes that the standby generator has been properly selected, installed and interconnected by a competent, qualified electrician or installation contractor. Once the installation is complete, do nothing that may result in noncompatibility between the generator and connected electrical loads.

Fuel pressure for both natural gas and liquid propane setups should be 11 inches to 14 inches of water column (0.6 psi) at all load ranges.

‹

1.8.3 ENGINE

Gaseous fuels such as natural gas and liquid propane (LP) gas are highly explosive. Even the slightest spark can ignite such fuels and cause an explosion. No leakage of fuel is permitted. Natural gas, which is lighter than air, tends to collect in high areas; LP gas is heavier than air and tends to settle in low areas – install leak detectors accord- ingly.

Make General Motors Displacement 4.3 liters (262 cu. in.) Cylinder Arrangement V-6 Valve Arrangement Overhead Valves Firing Order 1-6-5-4-3-2 Number of Main Bearings 4 Compression Ratio 9.4-to-1 No. of Teeth on Flywheel 168 Ignition System Electronic Ignition Timing at 1,800 rpm 40 degrees BTDC Rated Horsepower at 1,800 rpm 67 Spark Plug Gap 0.045 inch (1.1 mm) Recommended Spark Plugs AC 41-932 or equivalent Oil Pressure 30-50 psi Crankcase Oil Capacity 4.5 U.S. quarts (4.25 L) Recommended Engine Oil SAE 15W-40 Type of Cooling System Pressurized, closed recovery Cooling Fan Pusher Type Cooling System Capacity 4.5 U.S. gallons (17 L) Recommended Coolant Use a 50-50 mixture of

‹

1.9.1 CONVERSION TO LP GAS VAPOR

The generator is shipped from the factory configured for using natural gas as fuel. To convert the fuel system to LP gas, proceed as follows (Figure 1.3). 1. Remove end cap from the pressure reducer valve. 2. Turn the tension screw counterclockwise until all ten- sion is removed from the inner spring. 3. Install and tighten the end cap. 4. Invert the pressure reducer valve. In other words, turn it upside down (end cap facing downward). 5. Purge and leak test the entire fuel system according to gaseous fuel codes. NO LEAKS can appear at any point in the system.

ethylene glycol and soft water.

Fuel Consumption

Figure 1.3 – Conversion to LP Gas Vapor

Natural Gas 720 cfh LP Gas 288 cfh/7.9gph

Page 9 of the Generac Power Systems 0043734 user manual — !
Page 9 · click to enlarge
Page 9

Section 1 — General Information

1.10 ENGINE OIL RECOMMENDATIONS The unit has been filled with 15W-40 engine oil at the factory. Use a high-quality detergent oil classified “For Service CC, SD, SE or SF.” Detergent oils keep the engine cleaner and reduce carbon deposits. Use oil hav- ing the following SAE viscosity rating, based on the ambient temperature range anticipated before the next oil change:

1.12 EMISSIONS CONTROL SYSTEM (MODELS 0046262, 0046263 & 0046264) This model is equipped with an active exhaust emis- sions control system to comply with certain California air district regulations for natural gas emergency gener- ating sets, including the South Coast Air Quality Management District. Do not tamper with or disable any part of this system, including the exhaust catalyst, carburetor, oxygen sensor, air-fuel ratio controller, sole- noid valve and gas regulator. These items are not sub- ject to periodic maintenance or adjustment.

TemperatureOil Grade(Recommended) Above 80º F (27º C)SAE 30W or 15W-40 32º to 80º F (-1º C to 27º C)SAE 20W-20 or 15W-40 Below 32º F (0º C)SAE 10W or 15W-40

This model is of a size (greater than 50 brakehorse- power) that may require a review by air permitting authorities prior to installation and operation. Consult the local air management district for details and spe- cific requirements.

Any attempt to crank or start the engine before it has been properly serviced with the recommended oil may result in an engine failure.

!

Figure 1.4 - Emissions Control System

1.11 COOLANT Use a mixture of half low silicate, ethylene glycol base antifreeze and half soft water. Use only soft water and only low silicate antifreeze. If desired, add a high quali- ty rust inhibitor to the recommended coolant mixture. When adding coolant, always add the recommended 50- 50 mixture.

Generac Power Systems 0043734 — Figure 1.4 - Emissions Control System diagram (page 9)
Fig. 3 · Figure 1.4 - Emissions Control System

DANGER

Do not remove the radiator pressure cap while the engine is hot or serious burns from boiling liquid or steam could result.

!

‹

1.12.1 AIR FUEL RATIO CONTROLLER

Ethylene glycol base antifreeze is poisonous. Do not use mouth to siphon coolant from the radia- tor, recovery bottle or any container. Wash hands thoroughly after handling. Never store used antifreeze in an open container because animals are atracted to the smell and taste of antifreeze even though it is poisonous to them.

!

The air fuel ratio controller is an advanced micro- processor designed to work with a three-way catalyst and a feedback (rich bias) carburetor to provide close- loop fuel management. Its digital adaptive control is able to compensate for variations in fuel mixtures and engine tunes. It is time based activated. (For example, it will activate after 45 seconds from receiving the power signal.) The part number for the air fuel ratio controller is 0D4221.

Do not use any chromate base rust inhibitor with ethylene glycol base antifreeze, or chromi- um hydroxide (“green slime”) will form and cause overheating. Engines that have been oper- ated with a chromate base rust inhibitor must be chemically cleaned before adding ethylene glycol base antifreeze. Using any high silicate antifreeze boosters or additives also will cause overheating. Generac also recommends that any soluble oil inhibitor NOT be used for this equip- ment.

!

Principle of Operation: The oxygen sensor, installed on the exhaust pipe, between the engine and the cat- alytic muffler (closer to the engine), continuously moni- tors the exhaust gas composition. A feedback signal is sent from the oxygen sensor to the air fuel ratio con- troller, which controls the fuel system to maintain the optimal, stoichiometric air fuel ratio. The air fuel mix- ture to the engine is controlled by biasing the diaphragm in the fuel regulator using vacuum (from the carburetor). This vacuum signal is directed to the fuel regulator via the control valve. The air fuel ratio con- troller determines the amount of vacuum signal sent to the fuel regulator. The more vacuum sent to the regula- tor, the more restricted the fuel flow will be, therefore the leaner the air fuel mixture.

Page 10 of the Generac Power Systems 0043734 user manual — ◆
Page 10 · click to enlarge
Page 10

Section 2 — Installation

STANDBY GENERATOR INSTALLATION

DANGER

Connecting this generator to an electrical system normally supplied by an electric utility shall be by means of a transfer switch (such as the Generac “GTS” type transfer switch), so as to isolate the electric system from the utility distribution system when the generator is operating. Failure to isolate the electric system by these means will result in damage to the generator and may also result in injury or death to utility workers due to backfeed of electrical energy.

◆

OTHER PUBLISHED STANDARDS

In addition to NFPA standards, the following informa- tion pertaining to the installation and use of standby electric systems is available:

If an open bottom is used, the engine-generator is to be installed over non-combustible materials and should be located such that combustible materials are not capable of accumulating under the generator set. Only qualified, competent installation contractors or electricians thoroughly familiar with applicable codes, standards and regulations should install this standby electric power system. The installation must comply strictly with all codes, standards and regulations per- taining to the installation. This genset must be installed on a level surface. The base frame must be level within two (2) inches all around.

  • Article X, NATIONAL BUILDING CODE, available from the American Insurance Association, 85 John Street, New York, N.Y. 10038.
  • AGRICULTURAL WIRING HANDBOOK, obtainable from the Food and Energy Council, 909 University Avenue, Columbia, MO, 65201.
  • ASAE EP-364.2, INSTALLATION AND MAINTENANCE OF FARM STANDBY ELECTRIC POWER, available from the American Society of Agricultural Engineers, 2950 Niles Road, St. Joseph, MI 49085.
  • A52.1, AMERICAN NATIONAL STANDARD FOR CHIMNEYS, FIREPLACES AND VENTING SYSTEMS, available from the American National Standard Institute, 1430 Broadway, New York, N.Y. 10018.
  • NEC HANDBOOK available from the National Fire Protection Association, 1 Batterymarch Park, PO Box 9146, Quincy, MA 02269-9959. 2.1 BASIC STANDBY ELECTRIC SYSTEM Figure 2.1 shows a schematic diagram of a basic standby electric system. Both the UTILITY power supply and the STANDBY (generator) output are connected to an approved transfer switch. The transfer switch is required by electrical code and serves the following functions:

After the system has been installed, you must not do anything that might render the installation in noncom- pliance with such codes, standards and regulations.

◆

NFPA STANDARDS

The following published standards booklets pertaining to standby electric systems are available form the National Fire Protection Association (NFPA), Batterymarch Park, Quincy, MA 02269:

  • Permits the LOAD circuits to be connected to only one power supply at a time.
  • Prevents electrical backfeed between STANDBY power and the UTILITY power circuits. Notice that both the STANDBY and the UTILITY power supplies to the transfer switch are protected against overload by a main line circuit breaker.
  • NFPA No. 37, STATIONARY COMBUSTION ENGINES AND GAS TURBINES.
  • NFPA No. 76A, ESSENTIAL ELECTRICAL SYSTEMS FOR HEALTH CARE FACILITIES.
  • NFPA No. 220, STANDARD TYPES OF BUILDING CONSTRUCTION
  • NFPA No. 68, GUIDE FOR EXPLOSION VENTING
  • NFPA No. 70, NATIONAL ELECTRICAL CODE.
  • NFPA No. 30, FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE.
  • NFPA No. 10, INSTALLATION, MAINTENANCE AND USE OF PORTABLE FIRE EXTINGUISHERS.
Page 11 of the Generac Power Systems 0043734 user manual — ‹
Page 11 · click to enlarge
Page 11

Section 2 — Installation

Figure 2.1 – Basic Standby Electric System

DANGER

Do not connect the ground wire to any pipe that carries a flammable or explosive substance – FIRE or an EXPLOSION may result. Proper grounding helps protect personnel against electri- cal shock in the event of a ground fault condition in the generator or in connected electrical devices. In addition, grounding helps dissipate static electricity that often builds up in ungrounded devices.

Figure 2.2 – Generator Grounding Lug (typical)

2.2 EMERGENCY CIRCUIT ISOLATION METHOD This prevents overloading the generator by keeping elec- trical loads below the wattage/amperage capacity of the generator. If the generator is powering only critical loads, within its wattage/amperage capacity, during util- ity power outages, consider using the emergency circuit isolation method.

Critical electrical loads are grouped together and wired into a separate “Emergency Distribution Panel.” Load circuits powered by that panel are within the wattage/amperage capacity of the generator set. When this method is used, it is difficult to overload the gener- ator. The transfer switch must meet the following requirements:

2.5 GENERATOR AC NEUTRAL CONNECTIONS Generac uses an UNGROUNDED AC neutral. Grounding is recommended only at the main service entrance.

  • It must have an ampere rating equal to or greater than the total amperage rating of the emergency distribution panel circuit.
  • It must be installed between the building’s main distribution panel and the emergency distribution panel. 2.3 TOTAL CIRCUIT ISOLATION METHOD When a generator capable of powering all electrical loads in the circuit is to be installed, use the “Total Circuit Isolation Method.” It is possible for the generator to be overloaded when this isolation method is employed. The following apply to the transfer switch in this type of system.

2.6 TRANSFER SWITCH START SIGNAL CONNECTIONS

‹

2.6.1 PRE-PACKAGED TYPE SWITCH

Connect the six signal wires from the automatic trans- fer switch to the engine generator control, which is located on the upper right side and inside the lower control panel. Match wires 23, 194, N1, N2, T1 and T2 in the transfer switch to the corresponding wires on the terminal strip in the lower panel. The conductors for these wires should be in a seperate conduit from the main AC output wires. If the control wires are run in the same conduit, the control wires must be a shielded cable.

  • Ampere rating of the transfer switch must be equal to or greater than the ampere rating of the normal incoming utility service.
  • The transfer switch must be installed between the utility service entrance and the building distribution panel. 2.4 GROUNDING THE GENERATOR The National Electrical Code requires the frame and external electrically conductive parts of this equipment to be properly connected to an approved earth ground and/or grounding rods. For that purpose, a GROUND LUG (Figure 2.2) is provided on the generator mounting base. Consult a qualified electrician for grounding requirements in your area. Grounding procedures must meet local regulations.

‹

2.6.2 “GTS” Type Engineered Switch

Connect the two-wire start signal from the automatic transfer switch to the automatic start connection, which is located in the right hand corner inside the lower panel. Match wires 178 and 183 in the transfer switch to 178 and 183 on the terminal strip in the control panel. The conductors for the two-wire start circuit must be in their own conduit. If the control wires are run in the same conduit, the control wires must be a shielded cable.

Page 12 of the Generac Power Systems 0043734 user manual — NOTE:
Page 12 · click to enlarge
Page 12

Section 2 — Installation

‹

2.7.1 VENTED BATTERIES

  • The electrolyte is a dilute sulfuric acid that is harmful to the skin and eyes. It is electrically conductive and corrosive. The following procedures are to be observed:
  • Wear full eye protection and protective clothing,
  • Where electrolyte contacts the skin, wash it off immediately with water,
  • Where electrolyte contacts the eyes, flush thoroughly and immediately with water and seek medical attention, and
  • Spilled electrolyte is to be washed down with an acidneutralizing agent. A common practice is to use a solution of one pound (500 grams) bicarbonate of soda to one gallon (4 liters) of water. The bicarbonate of soda solution is to be added until the evidence of reaction (foaming) has ceased. The resulting liquid is to be flushed with water and the area dried.

!

2.7 BATTERY INSTALLATION

DANGER

Standby generators installed with automatic trans- fer switches will crank and start automatically when normal (utility) source voltage is removed or is below an acceptable preset level. To prevent such automatic start-up and possible injury to per- sonnel, do not connect battery cables until the normal source voltage at the transfer switch is cor- rect and the system is ready to be placed into operation.

!

Storage batteries give off explosive hydrogen gas. This gas can form an explosive mixture around the battery for several hours after charging. The slightest spark can ignite the gas and cause an explosion. Such an explosion can shatter the bat- tery and cause blindness or other injury. Any area that houses a storage battery must be properly ventilated. Do not allow smoking, open flame, sparks or any spark producing tools or equipment near the battery.

  • Lead acid batteries present a risk of fire because they generate hydrogen gas. The following procedures are to be followed:
  • DO NOT SMOKE when near batteries,
  • DO NOT cause flame or spark in battery area, and
  • Discharge static electricity from body before touching batteries by first touching a grounded metal surface. Servicing of batteries is to be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries.

Battery electrolyte fluid is an extremely caustic sulfuric acid solution that can cause severe burns. Do not permit fluid to contact eyes, skin, clothing, painted surfaces, etc. Wear protective goggles, protective clothing and gloves when handling a battery. If fluid is spilled, flush the affected area immediately with clear water.

!

For recommended batteries, see Section 4.5, “Battery Maintenance”. All batteries must be at 100 percent state- of-charge before they are installed on the generator.

When using maintenance-free batteries, it is not neces- sary to check the specific gravity or electrolyte level. Have these procedures performed at the intervals spec- ified in Section 4, “Maintenance.” A negative ground sys- tem is used. Battery connections are shown on the wiring diagrams. Make sure all batteries are correctly connected and terminals are tight. Observe battery polarity when connecting batteries to the generator set.

Do not dispose of the battery in a fire. The battery is capable of exploding.

Do not open or mutilate the battery. Released electrolyte can be toxic and harmful to the skin and eyes.

!

NOTE:

The battery represents a risk of high short circuit current. When working on the battery, always remove watches, rings or other metal objects, and only use tools that have insulated handles.

Damage will result if the battery connections are reversed.

2.8 PREPARATION BEFORE START-UP The instructions in this section assume that the standby generator has been properly installed, serviced, tested, adjusted and otherwise prepared for use by a competent, qualified installation contractor. Be sure to read the “Safety Rules” on Pages 2 and 3, as well as all other safe- ty information in this manual, before attempting to oper- ate this (and related) equipment.

Page 13 of the Generac Power Systems 0043734 user manual — ‹
Page 13 · click to enlarge
Page 13

Section 2 — Installation

‹

2.8.1 PRIOR TO INITIAL START-UP

‹

2.8.6 BELT TENSION

Check the engine fan belt tension and condition prior to placing the unit into service and at recommended intervals. Belt tension is correct when a force of approx- imately 22 pounds (10 kg), applied midway between pulleys, deflects the belt about 3/8- to 5/8-inch (10 to 16 mm).

Prior to initially starting the generator, it must be properly prepared for use. Any attempt to crank or start the engine before it has been properly serviced with the recommended types and quanti- ties of engine fluids (oil, coolant, fuel, etc.) may result in an engine failure. Before starting the generator for the first time, the installer must complete the following procedures. For follow-up maintenance information and/or service inter- vals, please refer to Section 4, “Maintenance.”

!

‹

2.8.7 ELECTRICAL SYSTEM

Make sure the generator is properly connected to an approved earth ground and/or ground rod.

Make sure the generator battery is fully charged, proper- ly installed and interconnected, and ready for use.

‹

2.8.2 TRANSFER SWITCH

Check to ensure that there are no loose electrical con- nections. Restrain any loose wires to keep them clear of any moving generator set components.

If this generator is used to supply power to any electri- cal system normally powered by an electric utility, the National Electrical Code requires that a transfer switch be installed. The transfer switch prevents electrical backfeed between two different electrical systems. (For additional information, see the applicable transfer switch manual for this unit.) The transfer switch, as well as the generator and other standby components, must be properly located and mounted in strict compli- ance with applicable codes, standards and regulations.

‹

2.8.8 RODENT PROTECTION

Make sure the four 3-inch diameter cap plugs (part # 0A8785) are properly installed in the tie-down holes in the side rails of the unit’s base frame (Figure 2.3). The cap plugs are shipped in a plastic bag located in the lower connection box. These plugs are needed to pre- vent rodents from accessing the interior of the genera- tor set. On acoustic units, cap plugs also are needed to stay within noise specification limits.

‹

2.8.3 FUEL SYSTEM

Make sure the fuel supply system to the generator (a) delivers the correct fuel at the correct pressure and (b) is properly purged and leak tested according to code. No fuel leakage is permitted. See Section 1.8, “Specifications”, for more information.

Figure 2.3 - Base Frame Cap Plugs

‹

2.8.4 GENERATOR SET LUBRICATION

Check the engine crankcase oil level before operating and add oil to the proper level – the dipstick “FULL” mark. Never operate the engine with the oil level below the dipstick “ADD” mark. See Section 1.8, “Specifications” and Section 1.10, “Engine Oil Recommendations”.

NOTE:

This engine is shipped from the manufacturer with SAE 15W-40 oil. This oil should be changed after 30 hours of operation.

‹

2.8.5 ENGINE COOLANT

Have the engine cooling system properly filled with the recommended coolant mixture. Check the system for leaks and other problems. See Section 1.8, “Specifications” and Section 1.11, “Coolant”.

Page 14 of the Generac Power Systems 0043734 user manual — ‹
Page 14 · click to enlarge
Page 14

Section 3 — Operation

3.1 CONTROL CONSOLE COMPONENTS The components of a liquid-cooled generator control console (Figure 3.1) are as follows:

‹

3.1.6 AUTO/OFF/MANUAL SWITCH

See Section 3.2.

‹

3.1.7 FAULT INDICATOR LAMP

Figure 3.1 – Control Console

This lamp goes ON when one or more of the following engine faults occurs and when engine shuts down.

  • Low oil pressure
  • High coolant temperature
  • Low coolant level
  • Overcrank
  • Overspeed

‹

3.1.8 15-AMP FUSE

This fuse protects the control console’s DC control cir- cuit against electrical overload. If the fuse has melted open because of an overload, engine cranking and start- up cannot occur. Replace the fuse with an identical AGC 15-amp replacement fuse.

‹

3.1.9 7.5 AMP INLINE FUSE (NOT SHOWN)

‹

3.1.1 AC VOLTMETER

This inline fuse is connected in the 15A line that runs between the Auto/Off/Manual switch and position 10 of the 76009A PCB. This fuse protects the start, fuel, field boost, and transfer outputs from the PCB and will open if there is excessive current draw on any one of these outputs.

The voltmeter displays generator AC output voltage dur- ing operation. Voltage is regulated by a solid-state volt- age regulator and is proportional to AC frequency. Refer to the unit’s DATA PLATE for rated AC voltage.

‹

3.1.2 AC AMMETER

This indicates current draw of connected electrical loads during operation. DO NOT EXCEED THE UNIT’S RATED MAXIMUM CONTINUOUS CURRENT. Refer to the unit DATA PLATE.

‹

3.1.10 VOLTAGE-PHASE SELECTOR SWITCH

This switch permits selection between either line-to-line or line-to-neutral voltage and amperage readings on the console AC voltmeter and AC ammeter.

‹

3.1.3 AC FREQUENCY METER

‹

3.1.11 SET EXERCISE TIME SWITCH

This indicates generator AC output frequency in Hertz (cycles per second). Frequency is proportional to engine speed. Units with a four-pole rotor, supply 60 Hertz at 1,800 rpm. The frequency reading with no electrical loads connected (no-load condition) should be between 60-62 Hertz.

This switch allows to program the generator to start and exercise automatically. (See Section 3.6)

3.2 USING THE AUTO/OFF/MANUAL SWITCH

‹

3.1.4 DC VOLTMETER

‹

3.2.1 “AUTO” POSITION

The generator is equipped with a belt-driven DC alter- nator, which maintains battery state of charge when the engine operates. The control module assembly (CMA) also incorporates a trickle charge circuit that maintains battery state of charge during nonoperating periods. Battery voltage should read approximately12.5 to 14.5 volts DC. A low battery voltage indicates the battery is discharging.

Selecting this switch position activates fully automatic system operation. It also allows the unit to start and exercise the engine every seven days with the setting of the exercise timer.

‹

3.1.5 HOURMETER

This indicates the time the engine-generator has operat- ed, in hours and tenths of hours. Use the hourmeter along with the periodic maintenance schedule for your generator set.

Page 15 of the Generac Power Systems 0043734 user manual — 3.3 AUTOMATIC TRANSFER OPERATION To select automatic operation, do the following:
Page 15 · click to enlarge
Page 15

Section 3 — Operation

‹

3.2.2 “OFF” POSITION

Upon restoration of utility source voltage above a preset level, generator circuit board action signals the transfer switch to transfer loads back to that power supply. After retransfer, the engine is signalled to shut down.

This switch position shuts down the engine. This posi- tion also prevents operation.

The actual sequence of operation is controlled by sensors and timers on a control logic circuit board, as follows:

‹

3.2.3 “MANUAL” POSITION

Set the switch to Manual to crank and start the engine. Transfer to standby power will not automatically occur unless there is a utility failure.

A.Utility Voltage Dropout Sensor

  • This sensor monitors utility source voltage.
  • If utility source voltage drops below about 60 percent of the nominal supply voltage, the sensor energizes a 15-second timer.
  • Once the timer has expired, the engine will crank and start. B.Engine Warm-up Time Delay

!

With the switch set to AUTO, the engine may crank and start at any time without warning. Such automatic starting normally occurs when utility power source voltage drops below a preset level or during the normal exercise cycle. To pre- vent possible injury that might be caused by such sudden starts, always set the switch to OFF and remove the fuse before working on or around the generator or transfer switch. Then, place a “Do Not Operate” tag on the generator panel and on the transfer switch.

  • This mechanism lets the engine warm up for about 10 seconds before the load is transferred to a standby source. C.Standby Voltage Sensor
  • This sensor monitors generator AC output voltage. When the voltage has reached 50 percent of the nominal rated voltage, transfer to standby can occur. D.Utility Voltage Pickup Sensor

3.3 AUTOMATIC TRANSFER OPERATION To select automatic operation, do the following:

  • This sensor monitors utility power supply voltage. When that voltage is restored above 80 percent of the nominal source voltage, a retransfer time delay starts timing. E.Retransfer Time Delay

1. Make sure the transfer switch main contacts are set to their “Utility” position, i.e., loads connected to the utility power source. 2. Be sure that normal utility power source voltage is available to transfer switch terminal lugs N1 and N2. 3. Set the generator’s Auto/Off/Manual switch to AUTO. 4. Set the generator’s main circuit breaker to its ON (or closed) position. With the preceding steps complete, the generator will start automatically when utility source voltage drops below a preset level. After the unit starts, loads are transferred to the standby power source. Refer to “Sequence of Automatic Operation.”

  • This timer runs for about 15 seconds.
  • At end of a 15-second delay, circuit board action deenergizes transfer relay in the transfer switch.
  • Retransfer to utility power source then occurs. F. Engine Cool-down Timer
  • When the load is transferred back to utility power source, the engine cool-down timer starts timing.
  • The timer will run for about one minute, and the generator will then shut down.

3.5 ENGINE HEATER This Generac standby generator comes equipped with a block heater (Figure 3.2, page 14) that is similar to the block heaters used in automotive applications. The block heater must be connected to a customer supplied 120V AC circuit.

3.4 SEQUENCE OF AUTOMATIC OPERATION The generator’s control panel houses a control logic cir- cuit board. This board constantly monitors utility power source voltage. Should that voltage drop below a preset level, circuit board action will signal the engine to crank and start. After the engine starts, the circuit board signals the transfer switch to activate and connect load circuits to the standby power supply (load terminal lugs T1/T2 connect to terminal lugs E1/E2).

Page 16 of the Generac Power Systems 0043734 user manual — !
Page 16 · click to enlarge
Page 16

Section 4 — Maintenance

Figure 3.2 – Engine Block Heater

  • Place a sign on the generator’s control panel and on the transfer switch that indicates the day and time the generator will be exercising.

OUTLET

NOTE:

If the battery terminals are disconnected or the con- trol panel fuse is removed, the exercise timer needs to be reset for automatic exercise operation.

Figure 3.3 – “Set Exercise” Switch on Control Panel

INLET

Refer to applicable wiring diagram(s) and electrical schematic(s) at the back of this manual for wiring con- nections.

3.6 WEEKLY EXERCISE CYCLE The generator will start and exercise once every seven days. During this weekly exercise, the unit runs for approximately 20 minutes and shuts down. Transfer of loads to generator output does not occur during the exercise unless power is lost during the exercise period.

4.1 CHECKING THE ENGINE OIL LEVEL For oil capacities, see “Specifications,” Section 1.8. For engine oil recommendations, see Section 4.2.1. To check the engine oil level, proceed as follows (Figure 4.1):

To select the day of the week and time of day for exer- cising, proceed as follows:

  • Set the Auto/Off/Manual switch to OFF.
  • Set generator’s main circuit breaker to its OFF (or open) position.
  • Locate the rocker switch on the control panel identified with the words “Set Exercise Time” (Figure 3.3).
  • Push “Set Exercise Time” switch to the ON position for 20 to 30 seconds and then release. The switch will spring back into its original position when released.
  • Wait 30 seconds before setting the Auto/Off/ Manual switch to the AUTO position.
1. Remove the dipstick and wipe it dry with a clean cloth. 2. Install the dipstick cap; then, remove it again. The oil level should be at the dipstick “Full” mark. If necessary, add oil to the “Full” mark only. DO NOT FILL ABOVE THE “FULL” MARK. 3. Install the dipstick.

Never operate the engine with the oil level below the “Add” mark on the dipstick. Doing this could damage the engine.!

NOTE:

The unit will exercise 20 minutes before it is set. Example: Set – Noon; Exercise – 11:40 a.m.

  • If you switch the Auto/Off/Manual switch is switched too soon, the engine may start. If engine does start, it will shut down automatically in about two (2) minutes.
  • Set the generator’s main circuit breaker to its ON (or closed) position.
  • The generator is now programmed to start and exercise every seven days thereafter, on the day and at the time of day the switch was activated.

!

Page 17 of the Generac Power Systems 0043734 user manual — ‹
Page 17 · click to enlarge
Page 17

Section 4 — Maintenance

Figure 4.1 – Oil Dipstick and Fill

Figure 4.2 – Oil Filter

4.2 CHANGING THE ENGINE OIL AND FILTER

5. Apply a light coating of engine oil to the seal of new oil filter. Install the filter and tighten by hand only. DO NOT OVERTIGHTEN. 6. Remove the oil fill cap (Figure 4.1). Add the recommended oil (see Section 4.2.1). DO NOT FILL ABOVE THE DIPSTICK “FULL” MARK. Crankcase oil capacity is 4.5 U.S. quarts (4.25 L).

‹

4.2.1 ENGINE OIL RECOMMENDATIONS

Use oil of API Service Class SG, SH or SJ. The recommended oil grade for the engine is SAE 15W-40.

NOTE:

After refilling the crankcase with oil, always check the oil level on the dipstick. Never operate the engine with the oil level below the “Add” mark on the dipstick. Doing this could damage the engine. 7. Start the engine and check for oil leaks. 8. Check the oil level after checking for leaks to ensure that the oil is filled to the proper level.

The unit is supplied with “break-in” oil. See the “Service Schedule,” Section 4.12 (Page 19), for the first required oil change.

!

Any attempt to crank or start the engine before it has been properly serviced with the recom- mended oil may result in an engine failure.

!

4.3 CHANGING THE ENGINE AIR CLEANER To replace the engine air cleaner, (Generac part num- ber 0A4637, simply remove the air cleaner cover and replace the air filter making sure it is positioned properly before reattaching the cover. (See Figure 4.3, page 16).

‹

4.2.2 OIL AND FILTER CHANGE PROCEDURE

To change the oil and filter, proceed as follows:

Refer to the “Service Schedule,” (Section 4.12, Page 19) for engine oil and filter change frequencies.

Drain the oil while the engine is still warm from run- ning. This means, warm up the engine, shut it down and drain it immediately as follows:

1. Remove the oil drain hose from its retaining clip, located on the generator base frame. 2. Loosen and remove the oil drain hose cap, located on the base frame end of the hose. Drain the oil completely into a suitable container. 3. When all of the oil has drained, install and tighten the oil drain hose cap. 4. Turn the oil filter (Generac part number 0A37970001, Figure 4.2) counterclockwise and remove it. Properly dispose of the old filter.
Show 4 more labels / short text on this page
· · ·
Page 18 of the Generac Power Systems 0043734 user manual — NOTE:
Page 18 · click to enlarge
Page 18

Section 4 — Maintenance

Figure 4.3 – Engine Air Cleaner

DANGER

Standby generators installed with automatic transfer switches will crank and start automatical- ly when normal (utility) source voltage is removed or is below an acceptable preset level. To prevent such automatic start-up and possible injury to per- sonnel, do not connect battery cables until the normal source voltage at the transfer switch is correct and the system is ready to be placed into operation.

!

Storage batteries give off explosive hydrogen gas. This gas can form an explosive mixture around the battery for several hours after charging. The slightest spark can ignite the gas and cause an explosion. Such an explosion can shatter the bat- tery and cause blindness or other injury. Any area that houses a storage battery must be properly ventilated. Do not allow smoking, open flame, sparks or any spark producing tools or equipment near the battery.

See the “Service Schedule,” Section 4.12, for recom- mended air cleaner maintenance.

4.4 SPARK PLUGS Reset the spark plug gap or replace the spark plugs as necessary. See Section 4.12.

1. Clean the area around the base of the spark plugs to keep dirt and debris out of the engine. Clean the plugs by scraping using a wire brush. Do not “blast” the spark plugs to clean. 2. Remove the spark plugs and check the condition. Replace the spark plugs if worn or if reuse is ques- tionable. See the “Service Schedule,” Section 4.12, for recommended inspection. 3. Check the spark plug gap using a feeler gauge. Adjust the gap to 0.045 inch (1.1 mm) by carefully bending the ground electrode (Figure 4.4).

Battery electrolyte fluid is an extremely caustic sulfuric acid solution that can cause severe burns. Do not permit fluid to contact eyes, skin, clothing, painted surfaces, etc. Wear protective goggles, protective clothing and gloves when handling a battery. If fluid is spilled, flush the affected area immediately with clear water.

!

Do not dispose of the battery in a fire. The bat- tery is capable of exploding.

Figure 4.4 – Setting the Spark Plug Gap

Do not open or mutilate the battery. Released electrolyte can be toxic and harmful to the skin and eyes.

0.045 inch (1.1 mm)

!

The battery represents a risk of high short circuit current. When working on the battery, always remove watches, rings or other metal objects, and only use tools that have insulated handles.

‹

4.5.1 BATTERY REPLACEMENT

Generac uses a Group 27F vented type battery that has 600 CCA @ 0º F. Generac’s part number is 058665.

4.5 BATTERY MAINTENANCE The battery should be inspected per the “Service Schedule,” Section 4.12. The following procedure should be followed for inspection:

NOTE:

The BCI number should be located directly on the battery.

1. Inspect the battery posts and cables for tightness and corrosion. Tighten and clean as necessary. 2. Check the battery fluid level of unsealed batteries and, if necessary, fill with DISTILLED WATER ONLY. DO NOT USE TAP WATER IN BATTERIES. 3. Have the state of charge and condition checked. This should be done with an automotive-type battery hydrometer or load test.

Air Cleaner

Page 19 of the Generac Power Systems 0043734 user manual — Figure 4.4 – Location of 15-amp Fuse
Page 19 · click to enlarge
Page 19

Section 4 — Maintenance

4.6 COOLING SYSTEM Air intake and outlet openings in the generator compart- ment must be open and unobstructed for continued prop- er operation. This includes such obstructions as high grass, weeds, brush, leaves and snow.

4.9 ENGINE COOLANT Check the coolant level in the coolant recovery bottle.

  • Add the recommended coolant mixture as necessary, see Section 1.10.
  • Periodically remove the radiator pressure cap to make sure the coolant recovery system is functioning properly. Coolant should be at the bottom of the radiator filler neck. If the coolant level is low, inspect the gasket in the radiator pressure cap. Replace the cap, if necessary. To have the pressure cap tested, contact a Generac/Guardian Authorized Dealer. Inspect the cooling system and coolant recovery system for leaks.

Without sufficient cooling and ventilating air flow, the engine/generator quickly overheats, which causes it to shut down.

The exhaust system of this product gets extremely hot and remains hot after shutdown. High grass, weeds, brush, leaves, etc. must remain clear of the exhaust. Such materials may ignite and burn from the heat of the exhaust system.

4.10 MISCELLANEOUS MAINTENANCE

‹

4.10.1 CLEANING THE GENERATOR

4.7 OVERLOAD PROTECTION FOR ENGINE DC ELECTRICAL SYSTEM Engine cranking, start-up and running are controlled by a solid-state engine controller circuit board. Battery voltage is delivered to that circuit board via a 15-amp fuse. These overcurrent protection devices will open if the circuit is overloaded.

Keep the generator as clean and as dry as possible. Dirt and moisture that accumulate on internal generator windings have an adverse effect on insulation resist- ance.

Periodically, clean the generator’s exterior surfaces. A soft brush may be used to loosen caked on dirt. Use a vacuum system or dry, low pressure air to remove any accumulations of dirt. The generator is housed inside an all-weather enclosure; clean the enclosure with a soft, damp cloth or sponge and water.

If a circuit breaker opens or a fuse element melts, you should find the cause of the overload before resetting the circuit breaker or replacing the fuse.

Once each year, have the generator cleaned and inspect- ed by a Generac/Guardian Authorized Dealer. Service technicians will use dry, low pressure air to clean inter- nal windings. Parts inside the control console should be cleaned and inspected at this time as well.

4.8 DC FUSE The generator panel’s 15-amp AGC fuse (Figure 4.4) pro- tects the DC control circuit against overload. The fuse is wired in series with the battery output lead to the panel. If the fuse element has melted open, cranking or starting the engine cannot occur. Replace the fuse using only an identical 15-amp AGC replacement.

Finally, have the insulation resistance of stator and rotor windings checked. If insulation resistances are excessively low, the generator may require drying.

‹

4.10.2 RODENT PROTECTION

The intrusion of rodents into the generator set can cause a wide range of problems, from failure of the unit to start, to personal injury and, in extreme circum- stances, short circuit or fire. Although the unit was designed to limit this problem, further precautions can be taken by the owner to help minimize both the chance of rodent entry and the extent of any damage. The fol- lowing inspection should be performed.

Figure 4.4 – Location of 15-amp Fuse

1. The base frame of the unit contains an optional fuel inlet location and four lifting holes that are capped at the factory. These caps are sometimes removed for transportation during installation but always should be replaced afterwards. Check that they are secured in place. The same applies for any access ports in the roof of the enclosure. If any of these caps are missing, contact a Generac/Guardian Authorized Dealer.
Page 20 of the Generac Power Systems 0043734 user manual — ‹
Page 20 · click to enlarge
Page 20

Section 4 — Maintenance

2. Inside the generator set, the chance of rodent entry into the control panel is greatly reduced by the inclusion of adjustable wire connectors. Check that the wire connector screws are tight, thus closing off any gap between the access holes and the wires.

‹

4.11.2 RETURN TO SERVICE

To return the unit to service after storage, proceed as follows:

1. Verify that utility power is turned off to the transfer switch and that the Auto/Off/Manual switch is set to OFF. 2. Check the tag on the engine for oil viscosity and classification. Verify that the correct recommended oil is used in engine, see Section 4.2.1. If necessary, drain and refill with the proper oil. 3. Check the battery. Fill all cells to the proper level with distilled water. DO NOT USE TAP WATER IN THE BATTERY. Remove the battery before charging. Recharge the battery to 100 percent state of charge, or, if defective, replace the battery with a 12-volt DC Group 27F battery rated for 90 amp hours (part # 058665). 4. Clean and wipe the entire generator. 5. Reconnect the battery. Observe battery polarity. Damage may occur if the battery is connected incor- rectly. 6. Open the fuel shutoff valve. 7. Start the unit by moving the Auto/Off/Manual switch to MANUAL. Allow the unit to warm up thoroughly. 8. Stop the unit and set the Auto/Off/Manual switch to AUTO. 9. Turn on the utility power to the transfer switch. 10. The generator is now ready for service.

4.11 OUT OF SERVICE PROCEDURE

‹

4.11.1 REMOVAL FROM SERVICE

If the generator cannot exercise every seven days, and it is to be out of service longer than 90 days, prepare the generator for storage as follows:

1. Start the engine and let it warm up. 2. Close the fuel shutoff valve in the fuel supply line and allow the unit to shut down. 3. Once the unit has shut down, it will signal a fault on the control panel. 4. Set the Auto/Off/Manual switch to OFF and turn off the utility power to the transfer switch. 5. While the engine is still warm from running, drain the oil completely. Refill the crankcase with SAE 15W-40 oil having API Service Class SG, SH or SJ. 6. Attach a tag to the engine indicating the viscosity and classification of the oil in the crankcase. 7. Remove the spark plug(s) and spray fogging agent into the spark plug(s) threaded openings. Reinstall and tighten the spark plug(s). 8. Remove the battery and store it in a cool, dry room on a wooden board. Never store the battery on any concrete or earthen floor. 9. Clean and wipe the entire generator.

Page 21 of the Generac Power Systems 0043734 user manual — SYSTEM/COMPONENT PROCEDURE FREQUENCY
Page 21 · click to enlarge
Page 21

Section 4 — Maintenance

4.12 SERVICE SCHEDULE

SYSTEM/COMPONENT PROCEDURE FREQUENCY

X = Action Inspect Change Clean W = Weekly R = Replace/Adjust as Needed M = Monthly * = Notify Dealer Y = Yearly if Repair is Needed. H = Hours

FUEL Fuel lines and connections* X EVERY 3 M LUBRICATION Oil level X M Oil X FIRST 9 H, EVERY 150 H / 6 M Oil filter X FIRST 9 H, EVERY 150 H / 6 M Oil line leakage* X 100 H COOLING Engine cooling system* X M Coolant X Y Enclosure louvers X X W EXHAUST Exhaust system X EVERY 3 M Retorque Exhaust Manifold* X FIRST 100 H AND

EVERY 800 H BATTERY Charge and condition X R X EVERY 3 M FAN BELT Tension and condition* X R EVERY 3 M ENGINE Retorque cylinder head* X FIRST 100 H AND

EVERY 800 H Retorque intake manifold* X FIRST 100 H AND

EVERY 800 H Starter motor* X R EVERY 500 H DC alternator* X R EVERY 500 H AND Y Air cleaner* X R EVERY 500 H Compression* X EVERY 800 H Valve clearance* X R EVERY 800 H Governor* X R Y Safety devices* X R EVERY 6 M Spark plugs X R 500 H AND Y Ignition system* X R EVERY 3 M GENERAL Overall condition X X M Exercise system W COMPLETE TUNE-UP* TO BE COMPLETED BY A GENERAC/ Y GUARDIAN AUTHORIZED DEALER

Page 22 of the Generac Power Systems 0043734 user manual — 5.1 TROUBLESHOOTING GUIDE
Page 22 · click to enlarge
Page 22

Section 5 — Troubleshooting

5.1 TROUBLESHOOTING GUIDE

PROBLEM CAUSE CORRECTION

The engine will not crank. 1. Fuse blown 1. Replace fuse. 2. Loose, corroded or defective 2. Tighten, clean or replace battery cables as necessary. 3. Defective starter contactor 3. * 4. Defective starter motor 4. * 5. Dead Battery 5. Charge or replace battery.

The engine cranks but 1. Out of fuel 1. Replenish fuel. will not start. 2. Defective fuel solenoid (FS) 2. * 3. Open #14 wire from 3. * engine control board 4. Defective spark plug(s) 4. Clean, re-gap or replace plug(s). 5. Dirty/Blocked air filter 5. Clean or replace as required.

The engine starts hard 1. Air cleaner 1. Check, clean or replace air cleaner. and runs rough. plugged or damaged 2. Defective spark plug(s) 2. Clean, re-gap or replace plug(s). 3. Dirty/Blocked air filter 3. Clean or replace as required.

The engine starts, but then 1. Engine oil level low 1. Check oil and add oil as needed. shuts down. 2. Defective low oil 2. * pressure switch 3. Defective high temperature 3. * switch 4. Defective control board 4. * 5. Low coolant level 5. Check coolant level, repair leaks and refill.

The Auto/Off/Manual switch 1. Defective switch 1. * is set to OFF, but the engine 2. Defective control board 2. * continues to run.

There is no AC output from 1. Generator main line circuit 1. Reset circuit breaker the generator. breaker open to ON (or closed). 2. Generator internal failure 2. *

There is no transfer to 1. Generator main line circuit 1. Reset circuit breaker standby after utility breaker open to ON (or closed). source failure. 2. Defective transfer switch coil 2. * 3. Defective transfer relay 3. * 4. Transfer relay circuit open 4. * 5. Defective control logic board 5. *

*Contact your nearest Generac/Guardian Authorized Dealer for assistance.

Page 23 of the Generac Power Systems 0043734 user manual — 4.11.2 RETURN TO SERVICE
Page 23 · click to enlarge
Page 23

Section 6 — Electrical Data

Guardian Liquid-cooled 40 kW Generator Mounting Dimensions - Drawing No. 0D5335

Generac Power Systems 0043734 — 4.11.2 RETURN TO SERVICE diagram (page 23)
Fig. 4

MODIFICATIONS REQUIRED FOR (SEE LEFT SIDE VIEW). SMALL FUEL SYSTEM FUEL SYSTEM SET UP WITH OUTSIDE STUB UPS

2. CONNECTION POINTS FOR AC LOAD LEADS, TRANSFER SWITCH, AND 1. STANDARD BLOCK HEATER REQUIRES 120V AC CONNECTION
3. EXHAUST MUFFLER SUPPORT BRACKETS SUPPLIED WITH OPTIONAL COMPARTMENT.
BATTERY TRAY INSIDE DIMENSIONS178 X 342.5 [7" X 13.5"]
6. MAIN LINE CIRCUIT BREAKER. 5. 2.5" I.D. FLEX EXHAUST
7. DOORS MUST BE OPENED 90 DEG. TO BE REMOVED. 8. A1 MAY BE USED FOR CIRCUIT BREAKER STUB-UP LOCATION.
9. SEE DRAWING C3850 FOR DUCT REMOVAL. REMOVAL OF FRONT DUCT WILL PROVIDE ACCESS TO MUFFLER FOR SERVICING.

OIL DRAIN = 1/2" NPT COUPLING INLET NATURAL GAS = 3/4" NPT COUPLING

Page 24 of the Generac Power Systems 0043734 user manual — 4.11.2 RETURN TO SERVICE
Page 24 · click to enlarge
Page 24
Generac Power Systems 0043734 — 4.11.2 RETURN TO SERVICE diagram (page 24)
Fig. 5

(Model No. 0043733, 0043734 & 0043735) Guardian Liquid-cooled 40 kW Generator Electrical Schematic (Stepper Motor) – Drawing No. 0A5858

Page 25 of the Generac Power Systems 0043734 user manual — 4.11.2 RETURN TO SERVICE
Page 25 · click to enlarge
Page 25
Generac Power Systems 0043734 — 4.11.2 RETURN TO SERVICE diagram (page 25)
Fig. 6

(Model No. 0043733, 0043734 & 0043735) Guardian Liquid-cooled 40 kW Generator

Wiring Diagram — Pre-pack Panel (4.3L) – Drawing No. 0D4992-A

14 17 16 15 13 12 11 5 8 10 9 7 6 4 3 2 1

Page 26 of the Generac Power Systems 0043734 user manual — 4.11.2 RETURN TO SERVICE
Page 26 · click to enlarge
Page 26

Section 6 — Electrical Data

(Model No. 0043733, 0043734 & 0043735) Guardian Liquid-cooled 40 kW Generator Electrical Schematic — Pre-pack Panel (4.3L) – Drawing No. 0D4993-A

Generac Power Systems 0043734 — 4.11.2 RETURN TO SERVICE diagram (page 26)
Fig. 7

INSULATE UNUSED WIRE END USE YELLOW WIRE FOR 208V, 3 PHASE USE BLUE WIRE FOR 240V, 1 PHASE

PCB - CIRCUIT BOARD CONTROLLER L1 - LIGHT, FAULT INDICATOR

SW2 - SWITCH, SET EXERCISE SW1 - SWITCH, AUTO/OFF/MANUAL

Page 27 of the Generac Power Systems 0043734 user manual — 4.11.2 RETURN TO SERVICE
Page 27 · click to enlarge
Page 27

Section 6 — Electrical Data

Guardian Liquid-cooled 40 kW Generator Wiring Diagram/Schematic – Lower Panel – Drawing No. 0D5997

Generac Power Systems 0043734 — 4.11.2 RETURN TO SERVICE diagram (page 27)
Fig. 8

FROM STANDARD GENERAC GTS 178 183 2-WIRE START CONNECTION

CB2 = CIRCUIT BREAKER - MAIN AS = ALTERNATOR STATOR

Page 28 of the Generac Power Systems 0043734 user manual — 4.11.2 RETURN TO SERVICE
Page 28 · click to enlarge
Page 28

Section 6 — Electrical Data

(Model No. 0046262, 0046263 & 0046264) Guardian Liquid-cooled 40 kW Generators Wiring Diagram - Control Panel - Drawing No. 0D6974

Generac Power Systems 0043734 — 4.11.2 RETURN TO SERVICE diagram (page 28)
Fig. 9

11 15 16 17 13 12 6 7 9 10 1 2

Page 29 of the Generac Power Systems 0043734 user manual — 4.11.2 RETURN TO SERVICE
Page 29 · click to enlarge
Page 29

Section 6 — Electrical Data

(Model No. 0046262, 0046263 & 0046264) Guardian Liquid-cooled 40 kW Generators

Electrical Schematic - Control Panel - Drawing No. 0D6975

Generac Power Systems 0043734 — 4.11.2 RETURN TO SERVICE diagram (page 29)
Fig. 10

SW2 - SWITCH, SET EXERCISE SW1 - SWITCH, AUTO/OFF/MANUAL

X INDICATES CLOSED 19 - 14 19 - 16 15 - 18

2. 11 2 - 7 2 - 3
Page 30 of the Generac Power Systems 0043734 user manual — 4.11.2 RETURN TO SERVICE
Page 30 · click to enlarge
Page 30

Section 6 — Electrical Data

Guardian Liquid-cooled 40 kW Generators Wiring Diagram - Drawing No. 0E2966

Generac Power Systems 0043734 — 4.11.2 RETURN TO SERVICE diagram (page 30)
Fig. 11
Page 31 of the Generac Power Systems 0043734 user manual — 4.11.2 RETURN TO SERVICE
Page 31 · click to enlarge
Page 31

Section 6 — Electrical Data

Guardian Liquid-cooled 40 kW Generators

Wiring Diagram - Drawing No. 0E2967

Generac Power Systems 0043734 — 4.11.2 RETURN TO SERVICE diagram (page 31)
Fig. 12
Page 32 of the Generac Power Systems 0043734 user manual — 4.11.2 RETURN TO SERVICE
Page 32 · click to enlarge
Page 32

Guardian Liquid-cooled 40 kW Generators Mounting Base - Drawing No. 0E2384-A

Generac Power Systems 0043734 — 4.11.2 RETURN TO SERVICE diagram (page 32)
Fig. 13
Page 33 of the Generac Power Systems 0043734 user manual — ITEM PART NO. QTY. DESCRIPTION
Page 33 · click to enlarge
Page 33

Guardian Liquid-cooled 40 kW Generators

Mounting Base - Drawing No. 0E2384-A

ITEM PART NO. QTY. DESCRIPTION

1 0C3250 1 ASSEMBLY BASE MOUNTING (DIRECT-COUPLED) 2 038804T 1 CABLE BATT RED #1 X 31.00 3 055414 1 LUG SLDLSS #2-#8 X 17/64 CU 4 0A4084 2 MOUNT ENGINE (R&L) 5 022129 2 WASHER LOCK M8-5/16 6 045771 2 NUT HEX M8-1.25 G8 YEL CHR 7 022237 7 WASHER LOCK 3/8 8 029745 6 SCREW HHC 3/8-16 X 1 G5 9 023152 1 SCREW HHC 3/8-16 X 3/4 G5 10 043107 2 SCREW HHC M8-1.25 X 25 G8.8 11 022145 2 WASHER FLAT 5/16 ZINC 12 027482 3 WASHER SHAKEPROOF EXT 5/16 STL 13 055597 4 SCREW HHC M12-1.75 X 85 G8.8 14 052251 2 DAMPENER VIBRATION 40 BLUE 15 052257 4 SPACER .49 X .62 X 1.87 PWDR/ZINC 16 052252 4 DAMPENER VIBRATION 17 052259 4 WASHER FLAT M12 18 052860 4 NUT LOCKING M12-1.75 19 0536210098 1 ASSEMBLY GROUNDWIRE 10"/3/8 20 052251A 2 DAMPENER VIBRATION 50 WHITE 21 044118 1 BARBED STRAIGHT 1/2 NPT X 5/8 22 057823 2 CLAMP HOSE #10 .56 - 1.06 23 057448 1 HOSE 5/8 ID TYPE 3 SINGLE (11"LG) 24 024310 1 PLUG STD PIPE 1/2 STEEL SQ HD 25 0D4239 1 KIT VARMIT GUARD (FOR N/G, L/P VAPOR OR DUAL FUEL, N/G-LP LIQUID UNITS) 0D4239A 1 KIT VARMIT GUARD (FOR L/P LIQUID UNITS) 0D4239B 1 KIT VARMIT GUARD (FOR DUAL FUEL N/G-L/P VAPOR UNITS) 26 038805H 1 CABLE BATT BLK #1 X 23.00 27 022131 1 WASHER FLAT 3/8-M10 ZINC 28 025507 1 WASHER SHAKEPROOF EXT 7/16 STL 29 061902 1 HOLD DOWN BATTERY 30 022413 1 SCREW HHC 1/4-20 X 1 G5 31 022473 1 WASHER FLAT 1/4 ZINC 32 022097 1 WASHER LOCK M6-1/4 33 022127 1 NUT HEX 1/4-20 STEEL 34 0A4010 2 SCREW HHC M8-1.25 X 60 G8.8 FT 35 052858 2 NUT LOCK FL M8-1.25 36 058665 1 BATT 12VDC 90-AH 27F 37 059473 1 HOLD DOWN BATTERY 38 049820 2 NUT LOCK HEX M8-1.25 NYL INSRT 39 075763 1 BOOT BATTERY CABLE

Page 34 of the Generac Power Systems 0043734 user manual — 4.11.2 RETURN TO SERVICE
Page 34 · click to enlarge
Page 34

Guardian Liquid-cooled 40 kW Generators Compartment - Drawing No. 0D8992

Generac Power Systems 0043734 — 4.11.2 RETURN TO SERVICE diagram (page 34)
Fig. 14
Page 35 of the Generac Power Systems 0043734 user manual — ITEM PART NO. QTY. DESCRIPTION
Page 35 · click to enlarge
Page 35

Guardian Liquid-cooled 40 kW Generators

Compartment - Drawing No. 0D8992

ITEM PART NO. QTY. DESCRIPTION

1 0C3594 10 ASSEMBLY M6 HINGE 3 0A3359 40 SCREW BHSC M6-1.0 X 16 SS 4 0A3360 40 SHAKEPROOF INT M6 SS 5 0C2522 (A) 5 DOOR SMALL STD. WELD 6 0C2527 (A) 1 CORNER POST LH REAR 7 0C2528 (A) 1 CORNER POST RH REAR 8 0C2535 (A) 1 CORNER POST LH FRONT 9 0C2536 (A) 1 CORNER POST RH FRONT 10 0C2547 (A) 2 REAR BRACE TOP & BOTTOM 11 0C2550 (A) 4 SIDE BRACE TOP & BOTTOM 12 0C2555 (A) 2 SIDE SUPPORT 13 0C2560 (A) 1 ROOF ONE-PIECE WLDMT 15 0D7904 (A) 1 FRONT BRACE TOP 16 0C2633 5 PLATE STRIKER 17 0C6749 20 SCREW PPHM M4-0.7 X 12 SS 18 060069 5 PADDLE HANDLE LOCK 19 0C6748 20 NUT LOCK HEX M4-0.7 SS NYL INS 20 080490 20 WASHER FLAT #8 SS 21 087233 5 RIVET POP 3/16 X 1/4 22 0C4065 (A) 1 DUCT FRONT LH 23 0C4064 (A) 1 DUCT FRONT RH 24 0C4066 (A) 1 DUCT BOTTOM 25 0C4067 (A) 1 DUCT FRONT PANEL 26 0C4117 (A) 1 DUCT FRONT TOP RH 28 0C2634A 1 ASSEMBLY COVER ACCESS 29 0C2454 76 SCREW TH-FRM M6-1X16 N WA Z/JS 30 022129 2 WASHER LOCK M8-5/16 31 042907 2 SCREW HHC M8-1.25 X 16 G8.8 32 022473 15 WASHER FLAT M6-1/4 ZINC 33 022097 1 WASHER LOCK M6-1/4 34 022127 1 NUT HEX 1/4-20 STEEL 35 0A9881 49.1 FT. GASKET DOOR RUBBER 36 0C3393 2 SCREW SHOULDER 39 0C3400 (A) 1 COVER EXHAUST HOLE 42 0C3397 4 FASTENER RATCHET 43 066760 39-3/8" STRIP SEALANT 1/8 X 1 44 022145 2 WASHER FLAT 5/16 ZINC

OPTIONAL COMPARTMENT MATERIALS:ALL P/N'S WITH AN "A" SUFFIX INDICATEALUMINUM MATERIAL OPTION.

Page 36 of the Generac Power Systems 0043734 user manual — 4.11.2 RETURN TO SERVICE
Page 36 · click to enlarge
Page 36

(Model No. 0043733, 0043734 & 0043735) Guardian Liquid-cooled 40 kW Generator Control Panel 4.3L – Drawing No. 0D4995-F

Generac Power Systems 0043734 — 4.11.2 RETURN TO SERVICE diagram (page 36)
Fig. 15
Page 37 of the Generac Power Systems 0043734 user manual — * PART OF CONTROL PANEL WIRE HARNESS
Page 37 · click to enlarge
Page 37

(Model No. 0043733, 0043734 & 0043735) Guardian Liquid-cooled 40 kW Generator

Control Panel 4.3L – Drawing No. 0D4995-F

ITEM PART NO. QTY. DESCRIPTION

ITEM PART NO. QTY. DESCRIPTION

1 0D5488 1 PANEL BTM & BACK CONTROL PANEL 2 0D1521A 1 CONTROL PANEL, FRONT W/ SILK SCREEN 3 0D1522 2 PANEL,SIDE COVER CONTROL PANEL 4 067680 1 ASSY VOLTAGE REGULATOR 60HZ 5 0C8243 1 WASHER LOCK HDPDEUTSCH 6 0C8244 1 NUT, HDP DEUTSCH 8 048467 1 CIRCT BRK 7 X 1 ETA 46-500-P 9 057907 1 RES WW LUG 10R 10% 25W 10 064008 1 COVER CON PNL TOP (NOT SHOWN) 12 055444 1 HEATSINK 13 030468 1 WASHER STEP NYLON .20 14 049939 1 RECTIFIER MSC 12A 600V 1N1206R 15 070370 1 WASHER MICA .203 16 022158 1 NUT HEX #10-32 STEEL 17 023762 1 WASHER SHAKEPROOF EXT #10 STL 18 023897 15 WASHER FLAT #10 ZINC 19 076009A 1 PP LOGIC ASM 50/60HZ 20 040213 4 PCB SUPPORT SNAP-IN 1/4" 21 027744 1 GROMMET 3/4 X 5/32 X 5/16 22 082573 1 SWITCH ROCKER DPST 125V SPD 23 076020 1 SWITCH TOG DPDT 15/10 SP 24 032300 1 HOLDER FUSE 25 022676 1 FUSE 15A X AGC15 26 064009 1 LIGHT 12VDC .02A LED RED PILOT 27 061945 1 SWITCH SELECTOR 6A AMP/V 28 076037 1 VOLTMETER DC 8-18V 29 070081 1 HOURMETER 30 070043 1 VOLTMETER AC 0-300 31 070045 1 AMMETER AC 0-200

32 070042 1 FREQUENCY METER 240V 55-65HZ 33 081988 1 DECAL EXERCISE INFO 34 0C1229 1 DECAL CUST CONN BOX 35 098647 REF. ASSY L.C. ELECT GOV 36 0A3968 1 CAPACITOR FILTER ASY 37 048766 REF BLOCK TERM 20A 2 X 6 X 1100V 39 083264 1 TFMR ASM,CMA 240/12V 41 057335 REF BLOCK TERM 20A 20 X 6 X 1100V 42 076061 1 DECAL, TERM. STRIP 43 029333 6 TIE WRAP 7.4" X .19" NATL UL 45 040479 4 VIB MNT 1.0 X 1.0 X 1/4-20 46 022507 4 SCREW HHC 1/4-20 X 1/2 G5 47 022127 4 NUT HEX 1/4-20 STEEL 48 022097 4 WASHER LOCK M6-1/4 49 033121 14 SCREW HHC #10-32 X 1/2 50 022152 14 WASHER LOCK #10 51 036902 4 SCREW PPHM #6-32 X 1/2 52 022155 6 WASHER LOCK #6 53 022985 6 WASHER FLAT #6 ZINC 54 036918 4 SCREW PPHM #8-32 X 1/2 55 022264 4 WASHER LOCK M4 56 038150 4 WASHER FLAT #8 ZINC 57 022471 4 NUT HEX #8-32 STEEL 58 022188 6 NUT HEX #6-32 STEEL 59 036908 2 SCREW PPHM #6-32 X 1-1/4 60 0C2428 4 SCREW PHTT #6-32 X 1/2 ZYC 61 0C2323 4 SCREW PHTT #6-32 X 5/8 ZYC 62* 0D5324 REF. FUSE & HOLDER LITTEL 7.5A 63* 0A9611 REF. FUSE 7.5AXBK/AGC7.5NX W/22670 64 074908 1 SCREW HHTT M5-0.8 X 10 BP 65 0E3783 1 DECAL, WARNING REMOVE FUSE

* PART OF CONTROL PANEL WIRE HARNESS

Page 38 of the Generac Power Systems 0043734 user manual — 4.11.2 RETURN TO SERVICE
Page 38 · click to enlarge
Page 38

(Model No. 0046262, 0046263 & 0046264) Guardian Liquid-cooled 40 kW Generator Control Panel – Drawing No. 0D6978-C

Generac Power Systems 0043734 — 4.11.2 RETURN TO SERVICE diagram (page 38)
Fig. 16
Page 39 of the Generac Power Systems 0043734 user manual — * PART OF CONTROL PANEL WIRE HARNESS
Page 39 · click to enlarge
Page 39

(Model No. 0046262, 0046263 & 0046264) Guardian Liquid-cooled 40 kW Generator

Control Panel – Drawing No. 0D6978-C

ITEM PART NO. QTY. DESCRIPTION

ITEM PART NO. QTY. DESCRIPTION

1 0D7397 1 PNL BTM & BACK CNTL PNL 04626 2 0D1521A 1 CONTROL PANEL FRONT W/ SILK SCREEN 3 0D1522 1 PANEL SIDE COVER CONTROL PANEL 4 067680 1 ASSY VOLTAGE REGULATOR 60HZ 5 0C8243 1 WASHER LOCK HDP DEUTSCH 6 0C8244 1 NUT, HDP DEUTSCH 7 0A6321 1 PANEL LEFT SIDE E 8 048467 1 CIRCT BRK 7 X 1 ETA 46-500-P 9 057907 1 RES WW LUG 10R 10% 25W 10 064008 1 COVER CON PNL TOP (NOT SHOWN) 11 0E3550 1 CHASSIS, UNIVERSAL 12 055444 1 HEATSINK 13 030468 1 WASHER STEP NYLON .20 14 049939 1 RECTIFIER MSC 12A 600V 1N1206R 15 070370 1 WASHER MICA .203 16 022158 1 NUT HEX #10-32 STEEL 17 023762 1 WASHER SHAKEPROOF EXT #10 STL 18 023897 15 WASHER FLAT #10 ZINC 19 076009A 1 PP LOGIC ASM 50/60HZ 20 040213 4 PCB SUPPORT SNAP-IN 1/4" 21 0A3394 1 GROMMET 3/4 X 5/32 X 5/16 22 082573 1 SWITCH ROCKER DPST 125V SPD 23 076020 1 SWITCH TOG DPDT 15/10 SP 24 032300 1 HOLDER FUSE 25 022676 1 FUSE 15A X AGC15 26 064009 1 LIGHT 12VDC .02A LED RED PILOT 27 061945 1 SWITCH SELECTOR 6A AMP/V 28 076037 1 VOLTMETER DC 8-18V 29 070081 1 HOURMETER 30 070043 1 VOLTMETER AC 0-300 31 070045 1 AMMETER AC 0-200 32 070042 1 FREQUENCY METER 240V 55-65HZ

33 081988 1 DECAL EXERCISE INFO 34 0C1229 1 DECAL CUST CONN BOX 35 0D3440 1 CONTROLLER, B-C #DPG-2103 36 0A3968 1 CAPACITOR FILTER ASY 37 048766 REF BLOCK TERM 20A 2 X 6 X 1100V 38 0A1441B 1 COVER PLATE AVR 39 083264 1 TFMR ASM,CMA 240/12V 40 0A1441C 1 COVER PLATE EGOV 41 057335 REF BLOCK TERM 20A 20 X 6 X 1100V 42 076061 1 DECAL TERM. STRIP 43 029333 6 TIE WRAP 7.4" X .19" NATL UL 44 040479 4 VIB MNT 1.0 X 1.0 X 1/4-20 45 022507 4 SCREW HHC 1/4-20 X 1/2 G5 46 022127 4 NUT HEX 1/4-20 STEEL 47 022097 4 WASHER LOCK M6-1/4 48 033121 14 SCREW HHC #10-32 X 1/2 49 022152 14 WASHER LOCK #10 50 036902 4 SCREW PPHM #6-32 X 1/2 51 022155 6 WASHER LOCK #6 52 022985 8 WASHER FLAT #6 ZINC 53 036918 8 SCREW PPHM #8-32 X 1/2 54 022264 8 WASHER LOCK M4 55 038150 8 WASHER FLAT #8 ZINC 56 022471 8 NUT HEX #8-32 STEEL 57 022188 6 NUT HEX #6-32 STEEL 58 0C2428 8 SCREW PHTT #6-32 X 1/2 ZYC 59 0C2323 4 SCREW PHTT #6-32 X 5/8 ZYC 60 0A2284 4 SCREW SWAGE 8-32 X 1/2 Z/YC 61 0C1127 1 DECAL AVR COVER 62* 0D5324 4 FUSE & HOLDER LITTEL 7.5A 63* 0A9611 1 FUSE 7.5AXBK/AGC7.5NX W/22670 64 074908 4 SCREW HHTT M5-0.8 X 10 BP 65 0E3783 1 DECAL, WARNING REMOVE FUSE

* PART OF CONTROL PANEL WIRE HARNESS

Page 40 of the Generac Power Systems 0043734 user manual — 4.11.2 RETURN TO SERVICE
Page 40 · click to enlarge
Page 40

Guardian Liquid-cooled 40 kW Generators Connection Box – Drawing No. 0D8848-B

Generac Power Systems 0043734 — 4.11.2 RETURN TO SERVICE diagram (page 40)
Fig. 17

FOR CIRCUIT BREAKER AND NEUTRAL BLOCK RECOMMENDED TERMINAL TIGHTENING TORQUES

Page 41 of the Generac Power Systems 0043734 user manual — ITEM PART NO. QTY. DESCRIPTION
Page 41 · click to enlarge
Page 41

Guardian Liquid-cooled 40 kW Generators

Connection Box – Drawing No. 0D8848-B

ITEM PART NO. QTY. DESCRIPTION

1 068115 1 LOWER PANEL 15 2 0D5489 1 COVER LOWER CONNECTION BOX 4 023484N 2 BUSHING SNAP SB-2.5-31 6 056739 1 RELAY SOLENOID 12VDC PNL MNT 9 0D3388 1 DECAL REMOTE START CONNECTION 10 058710 2 TRANSFORMER 200A TO 5A 5VA 11 0D5492 1 HARNESS LOWER PANEL 4.3L GRDN (048766) REF. BLOCK TERM 20A 2 X 6 X 1100V 12 022985 2 WASHER FLAT #6 ZINC 13 068116 1 COVER LOWER PANEL 15 18 0D5840 1 DECAL CUSTOMER CONNECTN FOR TS 29 022264 2 WASHER LOCK M4 30 0C2212 2 SCREW PHTT M4-0.7 X 16 ZYC 31 022142 4 SCREW HHC 5/16-18 X 3/4 G5 32 022145 4 WASHER FLAT 5/16 ZINC 33 022129 4 WASHER LOCK M8-5/16 34 045771 4 NUT HEX M8-1.25 G8 YEL CHR 35 022287 19 SCREW HHC 1/4-20 X 3/4 G5 36 022473 23 WASHER FLAT 1/4 ZINC 37 022097 23 WASHER LOCK M6-1/4 38 022127 4 NUT HEX 1/4-20 STEEL 40 0D5574 1 CB 0200A 3P 600V S FD6 LL 42 0D5689 1 PLATE CB MOUNT S (FD) 390S 43 0D5693 1 COVER CB TERMINALS S (FD 3P) 44 022097 12 WASHER LOCK M6-1/4 45 022287 8 SCREW HHC 1/4-20 X 3/4 G5 46 022127 12 NUT HEX 1/4-20 STEEL 47 022473 4 WASHER FLAT 1/4 ZINC 48 081320 4 SCREW SHC 1/4-20 X 4.5 G8.8 NZ 49 022237 3 WASHER LOCK 3/8 50 048527 3 SCREW SHC 3/8-16 X 3/4 G5 52 0D5464B 1 NEUTRAL BLOCK 390/200-400A 53 057073 2 JUNCTION BLOCK 3/8-16 54 022152 4 WASHER LOCK #10 55 033530 4 SCREW PHM #10-32 X 5/8 CAD 56 022237 2 WASHER LOCK 3/8 57 022241 2 NUT HEX 3/8-16 STEEL 58 022145 2 WASHER FLAT 5/16 ZINC 59 022129 1 WASHER LOCK M8-5/16 60 045771 1 NUT HEX M8-1.25 G8 YEL CHR

Page 42 of the Generac Power Systems 0043734 user manual — 4.11.2 RETURN TO SERVICE
Page 42 · click to enlarge
Page 42

Guardian Liquid-cooled 40 kW Generators Generator – Drawing No. 0D9490

Generac Power Systems 0043734 — 4.11.2 RETURN TO SERVICE diagram (page 42)
Fig. 18
Page 43 of the Generac Power Systems 0043734 user manual — * ROTOR REPLACEMENT PARTS
Page 43 · click to enlarge
Page 43

Guardian Liquid-cooled 40 kW Generators

Generator – Drawing No. 0D9490

ITEM PART NO. QTY. DESCRIPTION

1 051768 7 SCREW HHC M12-1.75 X 25 G8.8 2 051769 7 WASHER LOCK M12 3 0A8240 2 FLEX PLATE SAE10 4 039253 6 SCREW HHC M8-1.25 X 20 G8.8 5 022129 7 WASHER LOCK M8-5/16 6 082130D 1 ASSEMBLY MAG PICKUP 72" 7 0C4286 1 ASSEMBLY FAN W/PRESS DISC 10.75 X 3 8 * 0A2601 1 SCREW HHC M16-2.0 X 45 G8.8 9 * 0A2602 1 WASHER FLAT .688 ID X 3.25 OD 10 * 0A1138 1 KEY SQ 3/8 X 2-1/2 STEEL 11 * 021941 1 COUPLER 390 SAE 12 020808A 1 ROTOR 390 40 1P DIRECT 13 * 052624 1 BEARING BALL 6212 SEALED 14 * 070892 1 SLIP RING -MACHINED- 15 0A5580 4 SCREW HHC M14-2.0 X 140 G8.8 16 0A1633 4 WASHER 390 SAE ALT. 17 020729A 1 STATOR 390 40 AD2 SAE 18 022131 12 WASHER FLAT 3/8-M10 ZINC 19 022237 11 WASHER LOCK 3/8 20 022511 11 SCREW HHC 3/8-16 X 1-1/4 G5 21 068113 1 CARRIER REAR BEARING 15" 22 068115 1 LOWER PANEL 15 23 043123 4 WASHER LOCK M14 24 051779 4 NUT HEX M14-2.0 G8 YEL CHR 25 046852 1 SCREW HHTT #10-32 X 1/4 CZ 26 022145 1 WASHER FLAT 5/16 ZINC 27 039287 4 SCREW HHC M8-1.25 X 45 G8.8 FT 28 071641 1 BRUSH HOLDER ASSEMBLY 29 071639 1 HOLDER BRUSH SUPPORT 30 0A2110 2 SCREW SWAGE 1/4-20 X 1/2 Z/YC 31 022473 8 WASHER FLAT 1/4 ZINC 32 022746 1 SCREW HHC 3/8-16 X 1-3/4 G5 33 031980 2 TIE WRAP UL 14.6 X .14 NATL 34 083549 1 SLEEVE RUBBER 35 0A4089 1 ASSEMBLY SCROLL 390 SAE KIT 0A4089 PARTS 36 0A2491 2 SHROUD ALTERNATOR SHEET METAL 37 0A2497 2 SCREEN SHROUD SAE 38 0A2496 2 BRACKET TENSIONER SAE SCROLL 39 056326 8.4 FT TRIM VINYL BLACK 1/8 GP 40 022097 6 WASHER LOCK M6-1/4 41 045757 2 SCREW HHC M6-1.0 X 25 G8.8 42 047411 4 SCREW HHC M6-1.0 X 16 G8.8 43 0A2110 12 SCREW SWAGE 1/4-20 X 1/2 Z/YC

* ROTOR REPLACEMENT PARTS

Page 44 of the Generac Power Systems 0043734 user manual — 4.11.2 RETURN TO SERVICE
Page 44 · click to enlarge
Page 44

Guardian Liquid-cooled 40 kW Generators Engine – Drawing No. 0D6980-B

Generac Power Systems 0043734 — 4.11.2 RETURN TO SERVICE diagram (page 44)
Fig. 19
Page 45 of the Generac Power Systems 0043734 user manual — ITEM PART NO. QTY. DESCRIPTION
Page 45 · click to enlarge
Page 45

Guardian Liquid-cooled 40 kW Generators

Engine – Drawing No. 0D6980-B

ITEM PART NO. QTY. DESCRIPTION

1 0A9046 1 ENGINE 4.3L GM 2 0A9118A 1 FLYWHL 4.3L GM SAE 3 070022 1 WASHER STAR M12 EXT 4 0A6021 6 SCREW HHC 7/16-20 X 1 G8 6 059056A 1 STARTER 5.7L/7.4L GM 8 0A9050 2 BOLT STARTER 4.3L 9 022237 17 WASHER LOCK 3/8 10 045772 1 NUT HEX M10-1.5 G8 YEL CHR 11 049226 1 WASHER LOCK M5 12 051716 1 NUT HEX M5-0.8 G8 YEL CHR 13 0A4244 1 CONNECTOR COIL TO DISTRIBUTOR 14 0A4215 1 DIP STICK 4.3L GM 15 0A4231 1 TUBE DIP STICK 4.3L 16 059057 10" HOSE 3/4 ID SAE-30R2 17 0A2440 2 GASKET THERMOSET 18 026568 2 SCREW HHC 3/8-16 X 2-3/4 G5 19 099729A 1 HOUSING THERM IMPREX 20 061012 1 PLUG STD PIPE 1/8 SOCKET HEAD 21 069939 1 HOUSING THERMOSTAT/WATER INLET 22 035606 1 SENSOR HI COOLANT SHUTDOWN 23 0A4930B 1 HEAT SHIELD RIGHT 24 0A4084 1 MOUNT ENGINE 25 029745 3 SCREW HHC 3/8-16 X 1 G5 26 044101 2 BRACKET SUPPORT SPARK PLUG WIRE 27 023152 2 SCREW HHC 3/8-16 X 3/4 G5 28 022131 2 WASHER FLAT 3/8-M10 ZINC 29 058030 2 RETAINER PLUG WIRES 30 0A4085 1 GASKET EXHAUST MANIFOLD 31 0A3928 1 MANIFOLD RIGHT EXHAUST 32 0C7947 2 BOLT U 3/8-16 X 2.50 33 057794 2 RETAINER SPARK PLUG WIRES 34 0A4277 1 WIRES SPARK PLUG 4.3L 35 022241 4 NUT HEX 3/8-16 STEEL 36 057795 1 CONNECTOR C/C VENT 37 048191 2 PIN DOWEL M10 X 24 38 032303 6 SCREW HHC 3/8-16 X 3-1/2 G5 39 0A3852 3 PLATE FLEX GM 40 098239 1 CASTING ADAPTOR 41 057522 1 SENSOR COOLANT LEVEL 42 0D2244M 1 ASSY MAGPICKUP (3/8-24 MALE) (MODEL 004626 0NLY) 43 075885 1 THERMOSTAT 195 DEG

* 0D6979 1 40KW GUARDIAN WIRE HARNESS (NOT SHOWN FOR MOD. 004626-0) * 0A4308 1 HARNESS 4.3L STD WIRE (NOT SHOWN FOR MOD. 004373-1)

Page 46 of the Generac Power Systems 0043734 user manual — 4.11.2 RETURN TO SERVICE
Page 46 · click to enlarge
Page 46

Guardian Liquid-cooled 40 kW Generators Engine – Drawing No. 0A4304-L

Generac Power Systems 0043734 — 4.11.2 RETURN TO SERVICE diagram (page 46)
Fig. 20
Page 47 of the Generac Power Systems 0043734 user manual — ITEM PART NO. QTY. DESCRIPTION
Page 47 · click to enlarge
Page 47

Guardian Liquid-cooled 40 kW Generators

Engine – Drawing No. 0A4304-L

ITEM PART NO. QTY. DESCRIPTION

1 0A9046 1 ENGINE 4.3L GM 2 0A4084 2 MOUNT, ENGINE (R & L) 3 0A4239 1 PULLEY CRANKSHAFT 4 0A4240 1 PULLEY WATER PUMP 5 0A5640 1 SPACER FAN 50MM 4.3L (35KW UNITS ONLY) 0A5640A 1 SPACER FAN 62MM (45KW UNITS ONLY) 6 0A5639 1 FAN 17" REVRS ROT (35KW UNITS ONLY) 0D3293A 1 FAN COOLING 22" DIA REVRS ROT (45KW UNITS ONLY) 7 077996 1 CAP HOSE 8 057823 1 CLAMP HOSE #10 .56 - 1.06 9 035579 1 BUSHING REDUCER 1/4 TO 1/8 10 037065 1 SCREW HHC 7/16-20 X 2-1/4 G5 11 022302 1 WASHER LOCK 7/16 12 0A8584 1 SWITCH OIL PRESSURE 13 052644 1 SPACER .5 X 1.5 X .25 STL/ZINC 14 0A4278A 1 BELT SERPENTNE 72.5" 15 0A4930A 1 HEAT SHIELD LEFT 16 0A4085 1 GASKET EXHAUST MANIFOLD 17 0A3927 1 MANIFOLD LEFT EXHAUST 18 0C7947 2 BOLT U 3/8-16 X 2.50 19 0A1232 1 DC ALTERNATOR ASSEMBLY 20 0A7801B 1 PULLEY PLOY-V 82 OD. 21 021928 1 BRACKET ALT. SUPPORT 22 0C6239 1 BRACKET MOUNTING WELD ASSEMBLY 23 0A4241 1 PULLEY GROOVED IDLER 24 0C2885 1 PULLEY TENSIONER 25 0A5737C 1 SPACER DC ALTERNATOR 34MM 26 022131 8 WASHER FLAT 3/8-M10 ZINC 27 077456 1 ADAPTOR M12-1.75 3/8 NPT 28 044117 1 BARBED STRAIGHT 3/8 NPT X 5/8 29 057823 1 CLAMP HOSE #10 .56 - 1.06 30 057448 1 HOSE 5/8 ID TYPE 3 SINGLE (12") 31 022129 8 WASHER LOCK M8-5/16 32 022142 4 SCREW HHC 5/16-18 X 3/4 G5 (45KW) 33 048614 4 SCREW HHC 5/16-24 X 3/4 G5 34 022237 12 WASHER LOCK 3/8 35 029745 4 SCREW HHC 3/8-16 X 1 G5 36 042633 3 SCREW HHC 3/8-24 X 1 G5 37 033819 1 SCREW HHC 3/8-16 X 4 G5 38 022241 4 NUT HEX 3/8-16 STEEL 39 0A5768 1 WASHER FLAT HEAVY DUTY 40 046526 5 WASHER LOCK M10 41 049814 2 SCREW HHC M10-1.5 X 25 G8.8 42 0C3756 1 BOLT TENSIONER PULLEY 43 045772 2 NUT HEX M10-1.5 G8 YEL CHR 44 0D2514 8 SPARK PLUG 5.7L GM 45 052259 1 WASHER FLAT M12 46 055934D 1 CLAMP VINYL 1.06 X .406 Z 47 0A37970001 1 FILTER OIL

Page 48 of the Generac Power Systems 0043734 user manual — 4.11.2 RETURN TO SERVICE
Page 48 · click to enlarge
Page 48

Guardian Liquid-cooled 40 kW Generators 4.3L Radiator – Drawing No. 0D7992-D

Generac Power Systems 0043734 — 4.11.2 RETURN TO SERVICE diagram (page 48)
Fig. 21
Page 49 of the Generac Power Systems 0043734 user manual — ITEM PART NO. QTY. DESCRIPTION
Page 49 · click to enlarge
Page 49

Guardian Liquid-cooled 40 kW Generators

4.3L Radiator – Drawing No. 0D7992-D

ITEM PART NO. QTY. DESCRIPTION

1 0D7825 1 RADIATOR COPPER BRASS 2 0D8251 1 FAN GUARD BOTTOM 3 0D8252 1 FAN GUARD TOP 4 024655 4 SCREW HHTT 1/4-20 X 1 CZ 5 022097 4 WASHER LOCK M6-1/4 6 022473 4 WASHER FLAT 1/4 ZINC 7 0D7174 1 VENTURI 4.3L 22" FAN 0D7174A 1 VENTURI 4.3L 17" FAN 9 0D7870 1 RADIATOR HOSE LOWER 10 035685 4 CLAMP HOSE #28 1.32 - 2.25 11 047290 1 HOSE 3/8 ID SINGLE BRAID 12 040173 2 CLAMP HOSE #5.5 .62 - .62 14 036865 1 DRAINCOCK 15 029032 1 HOSE 9/32 ID (64" LG) 16 052250 3 TAPE FOAM 1 X 1 (29" LG) 17 058443 10 SCREW CRIMPTITE 1/4-20 X 5/8 18 029745 4 SCREW HHC 3/8-16 X 1 G5 19 022237 4 WASHER LOCK 3/8 20 022131 4 WASHER FLAT 3/8-M10 ZINC 21 0D7850 1 RADIATOR HOSE UPPER 22 076749 1 BOTTLE COOLANT RECOVERY 23 0D7975 1 WATER BOTTLE BRACKET 24 090388 1 SCREW HHTT M6-1.0 X 12 YC 27 048031C 1 CLAMP HOSE BAND 1/4 29 0C4341 2 SUPPORT RADIATOR A GRP 30 * 0A6984 1 BRACKET AIR DUCT TOP/BOT 31 * 0D7942 1 SUPPORT AIR DUCT RH SIDE 32 * 0D7943 1 SUPPORT AIR DUCT LH SIDE 33 * 022413 8 SCREW HHC 1/4-20 X 1 G5 34 * 022097 8 WASHER LOCK M6-1/4 35 * 022473 8 WASHER FLAT 1/4 ZINC 36 ** 0D7924 1 SCREEN FRONT 37 ** 024655 4 SCREW HHTT 1/4-20 X 1 CZ 38 ** 022097 4 WASHER LOCK M6-1/4 39 ** 022473 4 WASHER FLAT 1/4 ZINC 40 090283 1 CAP RADIATOR 13 PSI-FOR SERVICE ONLY

* OPTIONAL WITH KIT 0D7948 ** OPTIONAL WITH KIT 0D7947

Page 50 of the Generac Power Systems 0043734 user manual — 2.5" DIA. CLAMP ASSEMBLY
Page 50 · click to enlarge
Page 50

(Model No. 0043733, 0043734 & 0043735) Guardian Liquid-cooled 40 kW Generators 4.3L Exhaust – Drawing No. 0E0704-A

2.5" DIA. CLAMP ASSEMBLY

TO

FRONT COMPARTMENT

TO ENGINE

TO ENGINE

ITEM PART NO. QTY. DESCRIPTION

ITEM PART NO. QTY. DESCRIPTION

1 059902A 1 CAP RAIN 2.50 / 2.69 2 0C9641 1 TUBE STRAIGHT 'A' GROUP 3 0C9650 1 MUFFLER 2-1/2" INLET/OUTLET 4 0C4114A 2 CLAMP BAND MUFFLER 6.5" 5 0C4126 2 BRACKET MUFFLER MOUNTING 6 0D5787 1 TUBE ELBOW 90 DEG 2.5" 7 0A5215B 2 PIPE FLEX 2.5" 8 0E0699 1 TUBE, CROSS OVER 9 0E0698 1 TUBE, 90 ELBOW 10 0C4170 2 BRACKET EXHAUST SHIELD 11 0C4305 1 SHIELD A-GRP HEAT 12 0C2454 2 SCREW TH-FRM M6-1 X 16 N WA Z/JS

13 0C3433A 4 CLAMP BAND 2.5" 14 022129 12 WASHER LOCK M8-5/16 15 022145 12 WASHER FLAT 5/16 ZINC 16 0C9748 1 PLUG M18-1.5 18 042907 12 SCREW HHC M8-1.25 X 16 G8.8 19 080762 6 BOLT U 3/8-16 X 2.62 20 022237 12 WASHER LOCK 3/8 21 022241 12 NUT HEX 3/8-16 STEEL 22 0E0701 1 SHIELD, CROSSOVER HEAT 23 0E0700 1 SHIELD, EXHAUST HEAT 24 022131 8 WASHER FLAT 3/8-M10 ZINC

Page 51 of the Generac Power Systems 0043734 user manual — ITEM PART NO. QTY. DESCRIPTION
Page 51 · click to enlarge
Page 51

Guardian Liquid-cooled 40 kW Generators

4.3L Air Cleaner – Drawing No. 0E0712

ITEM PART NO. QTY. DESCRIPTION

1 037561 1 NUT WING 1/4-20 NYLK 2 0A4632A 1 PLATE AIR CLEANER TOP 3 0A4637 1 FILTER AIR 11.5" CA326 4 0A4632B 1 PLATE,AIR CLEANR BOT 5 062522 1 STUD TH 1/4-20 X 3 G2 ZNC FULL 6 022127 1 NUT HEX 1/4-20 STEEL 7 057796 1 GROMMET 8 057795 1 CONNECTOR C/C VENT

Page 52 of the Generac Power Systems 0043734 user manual — 4.11.2 RETURN TO SERVICE
Page 52 · click to enlarge
Page 52

(Model No. 0043733, 0043734 & 0043735) Guardian Liquid-cooled 40 kW Generators 4.3L Nat. Gas Fuel System – Drawing No. 0E0714

Generac Power Systems 0043734 — 4.11.2 RETURN TO SERVICE diagram (page 52)
Fig. 22
Page 53 of the Generac Power Systems 0043734 user manual — ITEM PART NO. QTY. DESCRIPTION
Page 53 · click to enlarge
Page 53

(Model No. 0043733, 0043734 & 0043735) Guardian Liquid-cooled 40 kW Generators

4.3L Nat. Gas Fuel System – Drawing No. 0E0714

ITEM PART NO. QTY. DESCRIPTION

1 065907 1 SUPPORT SOLENOID NAT GAS 2 026812 4 ELBOW 90D 3/4NPT 3 076691 1 NIPPLE PIPE 3/4 NPT X 4.5 BLK IRN 4 0C7598 1 ASSY NATURAL GAS SOLENOID 5 026490 1 NIPPLE PIPE 3/4 NPT X 2 6 026577 2 BUSHING REDUCER 1 TO 3/4 7 055944 1 REGULATOR NAT GAS LPG VAPOR 8 067018 1 SUPPORT REGULATOR 9 0C2775 1 BRACKET REGULATOR 4.3L 10 061910 4 SCREW HHTT #10-24 X 3/4 YC 11 022145 4 WASHER FLAT 5/16 ZINC 12 022129 8 WASHER LOCK M8-5/16 13 030795 4 SCREW HHC 5/16-18 X 1 G5 14 025655 1 PLUG STD PIPE 3/4 STEEL SQ HD 15 022132 2 WASHER FLAT 9/16 ZINC 16 051778 2 SCREW HHC M14-2.0 X 25 G8.8 17 028641 2 NIPPLE TOE 3/4 NPT X 2 18 057824 2 CLAMP HOSE #16 .87 - 1.50 19 057422 1 HOSE 1IN ID LP GAS (42"LG) 20 043123 2 WASHER LOCK M14 21 051779 2 NUT HEX M14-2 G8 YEL CHR 23 050279 1 DECAL FUEL INLET NG 24 026915 4 NIPPLE CLOSE 3/4 X 1.375 25 055934P 1 CLAMP VINYL 1.62 X .486 Z 26 0A5737C 1 SPACER, D.C. ALT. (29MM LONG) (NOT SHOWN) 27 0D1509 1 DECAL INLET PRESSURE 28 061258 1 GASKET AIR CLEANER 29 0A7631 1 CARB. REWORK 4.3L 30 029745 2 SCREW HHC 3/8-16 X 1 G5 31 022237 2 WASHER LOCK 3/8 32 052865 1 GASKET CARBURETOR 33 033212 2 SCREW HHC 5/16-18 X 1-1/4 G5 34 0A4120 1 ADAPTOR CARBURETOR W/INLET 35 064945 1 GASKET CARBURETOR ADAPTOR 36 0A6344 1 BARBED ELBOW 90 DEG 1/8 NPT X 3/8 37 0A4121 1 VALVE PCV 38 047290 1 HOSE 3/8 ID SINGLE BRAID (10") 39 036409 1 NUT HEX 1/4-28 STEEL 40 022097 1 WASHER LOCK M6-1/4 41 0A5763 1 ARM THROTTLE-REWORK 42 082508 1 BALL JOINT PLA .25-28

Page 54 of the Generac Power Systems 0043734 user manual — 4.11.2 RETURN TO SERVICE
Page 54 · click to enlarge
Page 54

(Model No. 0046262, 0046263 & 0046264) Guardian Liquid-cooled 40 kW Generators 4.3L Nat. Gas Fuel System – Drawing No. 0E1338

Generac Power Systems 0043734 — 4.11.2 RETURN TO SERVICE diagram (page 54)
Fig. 23
Page 55 of the Generac Power Systems 0043734 user manual — **NOT SHOWN
Page 55 · click to enlarge
Page 55

(Model No. 0046262, 0046263 & 0046264) Guardian Liquid-cooled 40 kW Generators

4.3L Nat. Gas Fuel System – Drawing No. 0E1338

ITEM PART NO. QTY. DESCRIPTION

1 065907 1 SUPPORT SOLENOID NAT GAS 2 026812 4 ELBOW 90D 3/4NPT 3 076691 1 NIPPLE PIPE 3/4 NPT X 4.5 BLK IRN 4 0C7598 1 ASSY NATURAL GAS SOLENOID 5 026490 1 NIPPLE PIPE 3/4 NPT X 2 6 026577 2 BUSHING REDUCER 1 TO 3/4 7 0D2758 1 REGULATOR, N/G (R600S) 8 0E0521 1 SUPPORT REGULATOR 9 0C2775 1 BRACKET REGULATOR 4.3L 10 028238 2 BOLT U 5/16-18 X 1.50 11 022145 8 WASHER FLAT 5/16 ZINC 12 022129 12 WASHER LOCK M8-5/16 13 030795 4 SCREW HHC 5/16-18 X 1 G5 14 025655 1 PLUG STD PIPE 3/4 STEEL SQ HD 15 022132 2 WASHER FLAT 9/16 ZINC 16 051778 2 SCREW HHC M14-2.0 X 25 G8.8 17 028641 2 NIPPLE TOE 3/4 NPT X 2 18 057824 2 CLAMP HOSE #16 .87 - 1.50 19 057422 1 HOSE 1IN ID LP GAS (44"LG) 20 043123 2 WASHER LOCK M14 21 051779 2 NUT HEX M14-2 G8 YEL CHR 22 0C7820 1 MACHINING, CARBURETOR ADAPTOR 23 050279 1 DECAL FUEL INLET LPG 24 026915 4 NIPPLE CLOSE 3/4 X 1.375 25 055934P 1 CLAMP VINYL 1.62 X .486 Z 26** 0A5737C 1 SPACER, D.C. ALT. (29MM LONG) 27 0D1509 1 DECAL INLET PRESSURE 28 061258 1 GASKET AIR CLEANER 29 0C7650A 1 MIXER (EMISSIONS) NATURAL GAS 30 029745 2 SCREW HHC 3/8-16 X 1 G5 31 022237 2 WASHER LOCK 3/8 32 0C7059 1 GASKET GOVERNOR THROTTLE BODY 33 033212 4 SCREW HHC 5/16-18 X 1-1/4 G5 34 0A4120 1 ADAPTOR CARBURETOR W/INLET 35 064945 1 GASKET CARBURETOR ADAPTOR 36 0A6344 1 BARBED ELBOW 90 DEG 1/8 NPT X 3/8 37 0A4121 1 VALVE PCV 38 047290 1 HOSE 3/8 ID SINGLE BRAID (10") 39 0C7060 1 GASKET CARBURETOR ADAPTOR 40 0D3485 1 ASSY THROTTLE PF42 WIRE CONN 41 022152 4 WASHER LOCK #10 42 0C7908 4 SCREW SHC #10-32 X 5/8 G8.8 NZ 43 0A6613 1 GASKET CARB IMPCO 225 44 064090 4 SCREW PHM SEMS #12-24 X 5/8 EX 45 022259 4 NUT HEX 5/16-18 STEEL 46 028237 2 SADDLE 1-3/8

**NOT SHOWN

Page 56 of the Generac Power Systems 0043734 user manual — 4.11.2 RETURN TO SERVICE
Page 56 · click to enlarge
Page 56

(Model No. 0046262, 0046263 & 0046264) Guardian Liquid-cooled 40 kW Generators Exhaust – Drawing No. 0E1347-A

Generac Power Systems 0043734 — 4.11.2 RETURN TO SERVICE diagram (page 56)
Fig. 24
Page 57 of the Generac Power Systems 0043734 user manual — *NOTE: COMPONENT INSTALLED AT WAUKESHA FACILITY
Page 57 · click to enlarge
Page 57

(Model No. 0046262, 0046263 & 0046264) Guardian Liquid-cooled 40 kW Generators

Exhaust – Drawing No. 0E1347-A

ITEM PART NO. QTY. DESCRIPTION

1 059902A 1 CAP RAIN 2.50 / 2.69 2 0C9641 1 TUBE STRAIGHT 'A' GROUP 3 0D4208 1 MUFFLER CATALYST 4.3L 4 0D5061 4 MOUNTING BAND A-GRP CATALYST 5 0C4126 2 BRACKET MUFFLER MOUNTING 6 0D5787 1 TUBE ELBOW 90 DEG 2.5" 7 0A5215B 2 PIPE FLEX 2.5" 8 0E0699 1 TUBE, CROSS OVER 9 0E0698 1 TUBE, 90 ELBOW 10 0C4170 2 BRACKET EXHAUST SHIELD 11 0C4305 1 SHIELD A-GRP HEAT 12 0C2454 2 SCREW TH-FRM M6-1 X 16 N WA Z/JS 13 0C3433A 4 CLAMP BAND 2.5" 14 022129 16 WASHER LOCK M8-5/16 15 022145 20 WASHER FLAT 5/16 ZINC 16 045771 4 NUT HEX M8-1.25 G8 YEL CHR 18 042907 16 SCREW HHC M8-1.25 X 16 G8.8 19 080762 6 BOLT U 3/8-16 X 2.62 20 022237 12 WASHER LOCK 3/8 21 022241 12 NUT HEX 3/8-16 STEEL 22 0E0701 1 SHIELD, CROSSOVER HEAT 23 0E0700 1 SHIELD, EXHAUST HEAT 24 077879 1 HOSE VACUUM 5/32 (36"LG) 25 0D4221 1 KIT AIR/FUEL RATIO CONTROLLER 26 0D4512 1 BRACKET AIR/FUEL CONTROLLER 27 043116 2 SCREW HHC M6-1.0 X 12 G8.8 28 022471 5 NUT HEX #8-32 STEEL 29 022264 5 WASHER LOCK #8-M4 30 038150 8 WASHER FLAT #8 ZINC 31 036918 5 SCREW PPHM #8-32 X 1/2 32 049811 2 WASHER FLAT M6 33 022097 2 WASHER LOCK M6-1/4 34 049813 2 NUT HEX M6 X 1.0 G8 YEL CHR 35 0D8780 1 DECAL IMPORTANT EXHAUST EMISSION INFO 36 022131 8 WASHER FLAT 3/8-M10 ZINC

*NOTE: COMPONENT INSTALLED AT WAUKESHA FACILITY

Page 58 of the Generac Power Systems 0043734 user manual — ITEM PART NO. QTY. DESCRIPTION
Page 58 · click to enlarge
Page 58

(Model No. 0043733, 0043734 & 0043735) Guardian Liquid-cooled 40 kW Generators Electronic Governor – Drawing No. 0A2615-F

ITEM PART NO. QTY. DESCRIPTION

1 098290 1 ASSEMBLY MOTOR STEPPER 2 0A3439 1 BRACKET GOVERNOR MOUNTING 3 098958A 1 CONNECTOR INTERFACE ASSEMBLY 4 021888 1 LEVER STEPPER MOTOR 5 082508 2 BALL JOINT 1/4-28 9 036409 2 NUT HEX 1/4-28 STEEL 11 043146 3 SCREW HHC M6-1.0 X 10 G8.8 12 098941A 2 HOUSING GOVERNOR CONNECT 13 098942A 2 COVER CONN HOUSING 14 098225 4 SCREW FHM #2 X 5/8 SELF TAP 15 022097 4 WASHER LOCK M6-1/4 16 064526 1 SCREW TAP HWH #6-25 X 3/8 ZINC 17 029333A 1 TIE WRAP 7.4" X .19" BLACK UL 18 074031 - NEOPRENE LIQUID COATING (NOT SHOWN) 19 051716 2 NUT HEX M5-0.8 G8 YEL CHR 20 049226 2 WASHER LOCK M5 21 076040 2 SCREW PPHM M5-0.8 X 16 22 098647 1 ASSEMBLY L.C. ELECTRONIC GOVERNOR 23 036409 2 NUT HEX 1/4-28 STEEL 24 0C2184 1 STUD THR 1/4-28 X 3-1/2 G2 ZINC

Page 59 of the Generac Power Systems 0043734 user manual — TO THERMOSTAT HOUSING
Page 59 · click to enlarge
Page 59

Guardian Liquid-cooled 40 kW Generators Engine Coolant Heater – Drawing No. 0E2352

TO THERMOSTAT HOUSING

6 7 TO ENGINE BLOCK

ITEM PART NO. QTY. DESCRIPTION

1 **0C4905 1 BARBED EL 45 FITTING 2 **057822 2 CLAMP HOSE #8 .53-1.00 3 **077043E 1 CONDUIT FLEX 1" BLACK (15"LG) 4 **050967 1 HOSE 5/8 ID RIA 250F (46"LG) 5 0A6283 1 HOSE PREFORMED BLOCK HEATER 6 057822 2 CLAMP HOSE #8 .53-1.00 7 053660 1 BARBED STR 1/4 NPT X 5/8 8 042568 4 SCREW HHC M6-1.0 X 20 G8.8 9 022473 4 WASHER FLAT 1/4-M6 ZINC 10 084918A 1 HEATER ENG 1000W 120V *084918B 1 HEATER BLOCK 1000W 240V 11 084427 1 BRACKET HEATER W/WELDNUTS 12 022097 4 WASHER LOCK M6-1/4 13 049813 2 NUT HEX M6 X 1.0 G8 YEL CHR 14 055934D 1 CLAMP VINYL 1.06 X .406 Z (NOT SHOWN) 15 077043A 1 CONDUIT FLEX .38 ID (42"LG) (NOT SHOWN) (USED ON HEATER CORD)

*USED ON 50HZ VOLTAGE GENERATORS ONLY. **USED ON NATURAL GAS & L/P VAPOR UNITS ONLY.

Page 60 of the Generac Power Systems 0043734 user manual — 4.11.2 RETURN TO SERVICE
Page 60 · click to enlarge
Page 60

Section 8 – Notes

Guardian Liquid-cooled 40 kW Generators

Page 61 of the Generac Power Systems 0043734 user manual — 4.11.2 RETURN TO SERVICE
Page 61 · click to enlarge
Page 61

Section 8 – Notes

Guardian Liquid-cooled 40 kW Generators

Page 62 of the Generac Power Systems 0043734 user manual — ATTENTION WARRANTY DEPARTMENT
Page 62 · click to enlarge
Page 62

Section 9 – Warranty

Guardian Liquid-cooled 40 kW Generators

CALIFORNIA EMISSION CONTROL WARRANTY STATEMENT

YOUR WARRANTY RIGHTS AND OBLIGATIONS

The California Air Resources Board (CARB) and Generac Power Systems, Inc. (Generac) are pleased to explain the Emission Control System Warranty on your new engine.* In California, new utility, and lawn and garden equipment engines must be designed, built and equipped to meet the state’s stringent anti-smog standards. Generac will warrant the emission control system on your engine for the periods of time listed below provided there has been no abuse, neglect, unapproved modifi- cation or improper maintenance of your engine.

Your emission control system may include parts such as the carburetor, ignition system and exhaust system. Generac will repair your engine at no cost to you for diagnosis, replacement parts and labor, should a warrantable condition occur.

MANUFACTURER’S EMISSION CONTROL SYSTEM WARRANTY COVERAGE:

Emissions control systems on 1995 and later model year engines are warranted for two years as hereinafter noted. If, dur- ing such warranty period, any emission-related component or system on your engine is found to be defective in materials or workmanship, repairs or replacement will be performed by a Generac Authorized Warranty Service Facility.

PURCHASER’S/OWNER’S WARRANTY RESPONSIBILITIES:

As the engine purchaser/owner, you are responsible for the completion of all required maintenance as listed in your factory supplied Owner’s Manual. For warranty purposes, Generac recommends that you retain all receipts covering maintenance on your engine. However, Generac cannot deny warranty solely due to the lack of receipts or for your failure to ensure the completion of all scheduled maintenance.

As the engine purchaser/owner, you should, however, be aware that Generac may deny any and/or all warranty coverage or responsibility if your engine, or a part/component thereof, has failed due to abuse, neglect , improper maintenance or unap- proved modifications, or the use of counterfeit and/or “grey market” parts not made, supplied or approved by Generac.

You are responsible for presenting your engine to a Generac Authorized Warranty Service Facility as soon as a prob- lem occurs. The warranty repairs should be completed in a reasonable amount of time, not to exceed 30 days.

Warranty service can be arranged by contacting either your selling dealer or a Generac Authorized Warranty Service Facility. To locate the Generac Authorized Warranty Service Facility nearest you, call our toll-free number:

1-800-333-1322

IMPORTANT NOTE: This warranty statement explains your rights and obligations under the Emission Control System Warranty (ECS Warranty), which is provided to you by Generac pursuant to California law. See also the “Generac Limited Warranties for Generac Power Systems, Inc.,” which is enclosed herewith on a separate sheet, also provided to you by Generac. The ECS Warranty applies only to the emission control system of your new engine. If there is any conflict in terms between the ECS Warranty and the Generac Warranty, the ECS Warranty shall apply except in circumstances where the Generac Warranty may provide a longer warranty period. Both the ECS Warranty and the Generac Warranty describe impor- tant rights and obligations with respect to your new engine.

Warranty service can be performed only by a Generac Authorized Warranty Service Facility. When requesting warranty serv- ice, evidence must be presented showing the date of the sale to the original purchaser/owner.

If you have any questions regarding your warranty rights and responsibilities, you should contact Generac at the fol- lowing address:

ATTENTION WARRANTY DEPARTMENT

P.O. BOX 297 WHITEWATER, WI 53190

Part 1

Page 63 of the Generac Power Systems 0043734 user manual — EMISSION RELATED PARTS INCLUDE THE FOLLOWING:
Page 63 · click to enlarge
Page 63

Section 9 – Warranty

Guardian Liquid-cooled 40 kW Generators

EMISSION CONTROL SYSTEM WARRANTY

Emission Control System Warranty (ECS Warranty) for 1995 and later model year engines:

(a) Applicability: This warranty shall apply to 1995 and later model year engines. The ECS Warranty Period shall begin on

the date the new engine or equipment is purchased by/delivered to its original, end-use purchaser/owner and shall con- tinue for 24 consecutive months thereafter.

(b) General Emissions Warranty CoverageGenerac warrants to the original, end-use purchaser/owner of the new engine or

equipment and to each subsequent purchaser/owner that each of its engines is ... (1) Designed, built and equipped so as to conform with all applicable regulations adopted by the CARB pursuant to its

authority, and (2) Free from defects in materials and workmanship which, at any time during the ECS Warranty Period, may cause a war-

ranted emissions-related part to fail to be identical in all material respects to the part as described in the engine man- ufacturer’s application for certification. (c) The ECS Warranty only pertains to emissions-related parts on your engine, as follows:

(1) Any warranted, emissions-related parts that are not scheduled for replacement as required maintenance in the Owner’s

Manual shall be warranted for the ECS Warranty Period. If any such part fails during the ECS Warranty Period, it shall be repaired or replaced by Generac according to Subsection (4) below. Any such part repaired or replaced under the ECS Warranty shall be warranted for the remainder of the ECS Warranty Period. (2) Any warranted, emissions-related part that is scheduled only for regular inspection as specified in the Owner’s Manual

shall be warranted for the ECS Warranty Period. A statement in such written instructions to the effect of “repair or replace as necessary” shall not reduce the ECS Warranty Period. Any such part repaired or replaced under the ECS Warranty shall be warranted for the remainder of the ECS Warranty Period. (3) Any warranted, emissions-related part that is scheduled for replacement as required maintenance in the Owner’s

Manual shall be warranted for the period of time prior to the first scheduled replacement point for that part. If the part fails prior to the first scheduled replacement, the part shall be repaired or replaced by Generac according to Subsection (4) below. Any such emissions-related part repaired or replaced under the ECS Warranty shall be warranted for the remainder of the ECS Warranty Period prior to the first scheduled replacement point for such emissions-related part. (4) Repair or replacement of any warranted, emissions-related part under this ECS Warranty shall be performed at no

charge to the owner at a Generac Authorized Warranty Service Facility. (5) When the engine is inspected by a Generac Authorized Warranty Service Facility, the owner shall not be held responsi-

ble for diagnostic costs if the repair is deemed warrantable. (6) Generac shall be liable for damages to other original engine components or approved modifications proximately caused

by a failure under warranty of any emission-related part covered by the ECS Warranty. (7) Throughout the ECS Warranty Period, Generac shall maintain a supply of warranted emission-related parts sufficient

to meet the expected demand for such emission-related parts. (8) Any Generac authorized and approved emission-related replacement part may be used in the performance of any ECS

Warranty maintenance or repairs and will be provided without charge to the owner. Such use shall not reduce Generac ECS Warranty obligations. (9) Unapproved, add-on, modified, counterfeit and/or “grey market” parts may not be used to modify or repair a Generac

engine. Such use voids this ECS Warranty and shall be sufficient grounds for disallowing an ECS Warranty claim. Generac shall not be held liable hereunder for failures of any warranted parts of a Generac engine caused by the use of such an unapproved, add-on, modified, counterfeit and/or “grey market” part.

EMISSION RELATED PARTS INCLUDE THE FOLLOWING:

1. Fuel Metering System: 1.2) LPG/Natural Gas carburetion assembly and its internal components. a) Fuel controller (if so equipped) b) Mixer and its gaskets (if so equipped) c) Carburetor and its gaskets (if so equipped) d) Primary gas regulator (if so equipped) e) LP liquid vaporizer (if so equipped) 2) Air Induction System including: a) Intake pipe/manifold b) Air cleaner
3. Ignition System including: a) Spark plug b) Ignition module 4) Catalytic Muffler Assembly (if so equipped) including: a) Muffler gasket b) Exhaust manifold 5) Crankcase Breather Assembly including: a) Breather connection tube

*Generac engine types covered by this warranty statement include the following: 1) Prepackaged Standby Generator 2) Auxiliary Power Unit (APU) Generator 3) Standby Generator

Part 2

Page 64 of the Generac Power Systems 0043734 user manual — P.O. BOX 297 WHITEWATER, WI 53190
Page 64 · click to enlarge
Page 64

Section 9 – Warranty

Guardian Liquid-cooled 40 kW Generators

GENERAC POWER SYSTEMS STANDARD "TWO YEAR" LIMITED WARRANTY FOR

GUARDIAN “EMERGENCY AUTOMATIC STANDBY GENERATORS”

For a period of two years from the date of original sale, Generac Power Systems, Inc. (Generac) will, at its option, repair or replace any part which, upon examination, inspection and testing by Generac or a Generac Authorized Warranty Service Dealer, is found to be defective under normal use and service, in accordance with the warranty schedule set forth below. Any equip- ment that the purchaser/owner claims to be defective must be returned to and examined by the nearest Generac Authorized Warranty Service Dealer. All transportation costs under the warranty, including return to the factory, are to be borne and pre- paid by the purchaser/owner. This warranty applies only to Generac emergency automatic standby generators sold and rated for use in "Standby" applications.

WARRANTY SCHEDULE

YEARS ONE and TWO - 100% (one hundred percent) transferable coverage on Labor and Part(s) listed (proof of purchase and maintenance is required):

  • Engine - All Components
  • Alternator - All Components
  • Transfer System - All Components All warranty expense allowances are subject to the conditions defined in Generac's Warranty Policies, Procedures and Flat Rate Manual.

THIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING:

  • Generac generators that utilize non-Generac replacement parts.
  • Generac/Guardian generators utilizing non-Generac/Guardian automatic transfer switches.
  • Any Generac generators used as rental or trailer mounted applications.
  • Units used for prime power in place of existing utility power where utility power is present or in place of utility power where utility power service does not normally exist.
  • Costs of normal maintenance, adjustments, installation and start-up.
  • Failures caused by any contaminated fuels, oils, coolants or lack of proper fluid amounts.
  • Failures due, but not limited, to normal wear and tear, accident, misuse, abuse, negligence or improper installation. As with all mechanical devices, the Generac engines need periodic part(s) service and replacement to perform well. This warranty will not cover repair when normal use has exhausted the life of a part(s) or engine.
  • Failures caused by any external cause or act of God, such as collision, theft, vandalism, riot or wars, nuclear holocaust, fire, freezing, lightning, earthquake, windstorm, hail, volcanic eruption, water or flood, tornado or hurricane.
  • Damage related to rodent infestation.
  • Products that are modified or altered in a manner not authorized by Generac in writing.
  • Any incidental, consequential or indirect damages caused by defects in materials or workmanship, or any delay in repair or replacement of the defective part(s).
  • Failure due to misapplication.
  • Telephone, cellular phone, facsimile, internet access or other communication expenses.
  • Living or travel expenses of person(s) performing service, except as specifically included within the terms of a specific unit warranty period.
  • Expenses related to "customer instruction" or troubleshooting where no manufacturing defect is found.
  • Rental equipment used while warranty repairs are being performed.
  • Overnight freight costs for replacement part(s).
  • Overtime labor.
  • Starting batteries, fuses, light bulbs and engine fluids.

USE OF NON-GENERAC/GUARDIAN TRANSFER SWITCHES SHALL VOID THIS WARRANTY WITH RESPECT TO ALL GENERAC PRODUCT.

THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED. SPECIFICALLY, GENERAC MAKES NO OTHER WARRANTIES AS TO THE MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.

GENERAC'S ONLY LIABILITY SHALL BE THE REPAIR OR REPLACEMENT OF PART(S) AS STATED ABOVE. IN NO EVENT SHALL GENERAC BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES, EVEN IF SUCH DAMAGES ARE A DIRECT RESULT OF GENERAC'S NEGLIGENCE. Some states do not allow the exclusion or limitation of incidental or conse- quential damages, so the above limitation may not apply to you.

This warranty gives you specific legal rights. You also have other rights from state to state.

P.O. BOX 297 WHITEWATER, WI 53190

Part No. 0E1780 Revision D (05/09/03) Printed in U.S.A.

Fix-it

Troubleshooting

Common problems, likely causes, and what to do.

ProblemPossible causeRemedy
Generac® Power Systems, Inc. p.2
Part No. 0E1780 p.64

Ask about the Generac Power Systems 0043734

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Generac Power Systems 0043734

Be the first to ask — other owners or our team will answer.

Original document

Generac Power Systems 0043734 manual PDF

64 pages·4.3 MB·Portable Generator·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…