SECTION PAGE SAFETY RULES 1-1 INTRODUCTION 1-3 Read this Manual Thoroughly 1-3 Operation and Maintenance 1-3 How to Obtain Service 1-3 IDENTIFICATION RECORD 2-1 Data Label 2-1 EQUIPMENT DESCRIPTION 3-1 Equipment Description 3-1 Engine Oil Recommendations 3-1 Coolant Recommendations 3-1 ENGINE PROTECTIVE DEVICES 4-1 High Coolant Temperature Switch 4-1 Low Coolant Level Sensor 4-1 Low Oil Pressure Switch 4-1 Overcrank Shutdown 4-1 Overspeed Shutdown 4-1 RPM Sensor Loss Shutdown 4-1 DC Fuse 4-1 FUEL SYSTEMS 5-1 Fuel Requirements 5-1 Natural Gas Fuel System 5-1 Propane Vapor Withdrawal Fuel System 5-1 LP Fuel System 5-1 SPECIFICATIONS 6-1 Generator 6-1 Engine 6-1 Cooling System 6-1 Fuel System 6-1 Electrical System 6-1 Cold Weather Kit 6-2 Reconfiguring the Fuel System 6-2 GENERAL INFORMATION 7-1 Generator AC Lead Connections 7-1 Four-lead, Single-phase Stator 7-1 Alternator Power Winding Connections 7-1 3-phase Alternators 7-1 INSTALLATION 8-1 Installation 8-1 Preparation Before Start-up 8-1 Transfer Switch 8-1 Fuel System 8-1 Generator Set Lubrication 8-1 Prior to Initial Start-up 8-1 Engine Coolant 8-1 Belt Tension 8-1 Electrical System 8-1 Initial Inspection for QT Genset Start-up 8-1 Start-up Checklist 8-2 Preparation for Start-up 8-2 Start-up Inspection 8-2
OPERATION 9-1 Generator Control and Operation 9-1 Operating Unit with Manual Transfer Switch 9-1 Engine Start-up and Transfer 9-1 Retransfer and Shutdown 9-1 Operating Unit with Automatic Transfer Switch 9-1 MAINTENANCE 10-1 Maintenance Performed by Authorized Service Facilities 10-1 Every Three Months 10-1 Once Every Six Months 10-1 Once Annually 10-1 First 100 Operating Hours 10-1 Every 500 Operating Hours 10-1 Every 800 Operating Hours 10-1 Exhaust Manifold Procedure 10-1 Intake Manifold Procedure 10-1 Cylinder Head Procedure 10-1 Cooling System 10-2 Overload Protection for Engine DC Electrical System 10-2 Checking Fluid Levels 10-2 Check Engine Oil 10-2 Battery Fluid 10-2 Engine Coolant 10-2 Maintenance Owner/Operator Can Perform 10-3 Check Engine Oil Level 10-3 Check Battery 10-3 Exercise System 10-3 Inspect Cooling System 10-3 Check Engine Coolant Level 10-3 Perform Visual Inspection 10-3 Inspect Exhaust System 10-3 Check Fan Belt 10-3 Inspect Engine Governor 10-3 Changing Engine Oil 10-3 Changing the Engine Air Cleaner 10-3 Spark Plugs 10-4 Coolant Change 10-4 Miscellaneous Maintenance 10-4 Cleaning the Generator 10-4 Battery 10-4 Battery Maintenance 10-4 Battery Replacement 10-5 SERVICE SCHEDULE 11-1 TROUBLESHOOTING 12-1 Troubleshooting Guide 12-1 NOTES EXPLODED VIEWS & PARTS LISTS WIRING DIAGRAMS & SCHEMATICS WARRANTY
Content004 Rev. 0 09/05
Table of Contents

Standby Generator Sets Important Safety Instructions
SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe
operation be copied and posted in potential hazard areas. Safety should be stressed to all operators, potential operators, and service and repair technicians for this equipment.
The engine exhaust from this product
contains chemicals known to the state
of California to cause cancer, birth defects or other reproductive harm.
This product contains or emits chemicals known to the state of California to cause cancer, birth defects or other reproductive harm.
Study these SAFETY RULES carefully before install- ing, operating or servicing this equipment. Become familiar with this Owner’s Manual and with the unit. The generator can operate safely, efficiently and reli- ably only if it is properly installed, operated and maintained. Many accidents are caused by failing to follow simple and fundamental rules or precautions.
The manufacturer cannot anticipate every possible circumstance that might involve a hazard. The warn- ings in this manual, and on tags and decals affixed to the unit are, therefore, not all inclusive. If a pro- cedure, work method or operating technique is used that the manufacturer does not specifically recom- mend, ensure that it is safe for others. Also make sure the procedure, work method or operating tech- nique utilized does not render the generator unsafe.
Despite the safe design of this generator,
operating this equipment imprudently, neglect- ing its maintenance or being careless can cause possible injury or death. Permit only responsible and capable persons to install, operate or main- tain this equipment. Potentially lethal voltages are generated by
these machines. Ensure all steps are taken to render the machine safe before attempting to work on the generator. Parts of the generator are rotating and/or hot
during operation. Exercise care near running generators.
Safety 001 Rev. 0 08/05

Standby Generator Sets Important Safety Instructions
FIRE HAZARDS • Keep a fire extinguisher near the generator at all times. Do NOT use any carbon tetra-chloride type extinguisher. Its fumes are toxic, and the liquid can deteriorate wiring insulation. Keep the extin- guisher properly charged and be familiar with its use. If there are any questions pertaining to fire extinguishers, consult the local fire department.
Safety 001 Rev. 0 08/05

Standby Generator Sets Important Safety Instructions
INTRODUCTION Thank you for purchasing this model of the standby generator set product line.
This symbol points out potential fire hazard.
This symbol points out potential electrical shock
Every effort was expended to make sure that the information and instructions in this manual were both accurate and current at the time the manual was written. However, the manufacturer reserves the right to change, alter or otherwise improve this product(s) at any time without prior notice.
hazard. The operator is responsible for proper and safe use of the equipment. The manufacturer strongly recom- mends that the operator read this Owner's Manual and thoroughly understand all instructions before using this equipment. The manufacturer also strong- ly recommends instructing other users to properly start and operate the unit. This prepares them if they need to operate the equipment in an emergency.
If any portion of this manual is not understood, con- tact the nearest Authorized Service Dealer for start- ing, operating and servicing procedures.
It is the operator's responsibility to perform all safety checks, to make sure that all maintenance for safe operation is performed promptly, and to have the equipment checked periodically by an Authorized Service Dealer. Normal maintenance service and replacement of parts are the responsibility of the owner/operator and, as such, are not considered defects in materials or workmanship within the terms of the warranty. Individual operating habits and usage contribute to the need for maintenance service.
Throughout this publication, and on tags and decals affixed to the generator, DANGER, WARNING, CAUTION and NOTE blocks are used to alert person- nel to special instructions about a particular service or operation that may be hazardous if performed incorrectly or carelessly. Observe them carefully. Their definitions are as follows:
After this heading, read instructions that, if not
Proper maintenance and care of the generator ensure a minimum number of problems and keep operating expenses at a minimum. See an Authorized Service Dealer for service aids and accessories.
strictly complied with, will result in personal injury or property damage.
Operating instructions presented in this manual assume that the standby electric system has been installed by an Authorized Service Dealer or other competent, qualified contractor. Installation of this equipment is not a “do-it-yourself” project.
After this heading, read instructions that, if not
strictly complied with, may result in personal injury or property damage.
After this heading, read instructions that, if not
strictly complied with, could result in damage to equipment and/or property.
When the generator requires servicing or repairs, simply contact an Authorized Service Dealer for assistance. Service technicians are factory-trained and are capable of handling all service needs.
After this heading, read explanatory statements
that require special emphasis.
When contacting an Authorized Service Dealer or the factory about parts and service, always supply the complete model number of the unit as given on the front cover of this manual or on the DATA LABEL affixed to the unit.
These safety warnings cannot eliminate the hazards that they indicate. Common sense and strict compli- ance with the special instructions while performing the service are essential to preventing accidents.
Four commonly used safety symbols accompany the DANGER, WARNING and CAUTION blocks. The type of information each indicates is as follows: This symbol points out important safety infor-
To locate the nearest AUTHORIZED SERVICE DEALER, please call this number:
mation that, if not followed, could endanger personal safety and/or property of others. This symbol points out potential explosion
1-800-333-1322 or locate us on the web at:
hazard.
Safety 001 Rev. 0 08/05
· ·

Every generator set has a DATA LABEL that contains important information pertinent to the generator. The data label, which can be found attached to the gen- erator’s lower connection box, lists the unit’s serial number and its rated voltage, amps, wattage capacity, phase, frequency, rpm, power factor, etc.
Generator Model and Serial Number This number is the key to numerous engineering and manufacturing details pertaining to your unit. Always supply this number when requesting service, order- ing parts or seeking information.
GENERATOR SET DATA
MADE IN USA
MODEL QT
SERIAL
RATED KW
RATED KVA
PHASE
RATED VOLTAGE
RATED AMPS
POWER FACTOR
HERTZ
ALT RPM
ENGINE RPM
PRODUCTION DATE
ALTERNATOR SUBTRANSIENT REACTANCE
ALTERNATOR TRANSIENT REACTANCE
CLASS
ROTOR STATOR WINDING INSULATION AT 25 ° C AMBIENT
GENERAC POWER SYSTEMS, INC.
Identy 002 Rev. 0 09/05
General Information · ·

EQUIPMENT DESCRIPTION This equipment is a revolving field, alternating cur- rent generator set. It is powered by a gaseous fueled engine operating at 1800 rpm for 4-pole direct drive units, 3600 rpm for 2-pole direct drive units and 2300 - 3000 rpm for quiet drive gear units. See the Specifications section for exact numbers. The unit comes complete with a sound attenuated enclosure, internally mounted muffler, control console, main- line circuit breaker, battery charger, and protective alarms as explained in the following paragraph.
COOLANT RECOMMENDATIONS Use a mixture of half low silicate ethylene glycol base anti-freeze and deionized water. Cooling system capacity is listed in the specifications. Use only deion- ized water and only low silicate anti-freeze. If desired, add a high quality rust inhibitor to the recommended coolant mixture. When adding coolant, always add the recommended 50-50 mixture.
Do not use any chromate base rust inhibitor
All AC connections, including the power leads from the alternator, 120 volt battery charger input and control connections to the transfer switch are avail- able in the main connection box.
with ethylene glycol base anti-freeze or chro- mium hydroxide (“green slime”) forms and will cause overheating. Engines that have been oper- ated with a chromate base rust inhibitor must be chemically cleaned before adding ethylene glycol base anti-freeze. Using any high silicate anti-freeze boosters or additives will also cause overheating. The manufacturer also recommends that any soluble oil inhibitor is NOT used for this equipment.
The generator incorporates the following generator features:
Do not remove the radiator pressure cap while
the engine is hot or serious burns from boiling liquid or steam could result. Ethylene glycol base antifreeze is poisonous.
ENGINE OIL RECOMMENDATIONS The unit has been filled with 15W-40 engine oil at the factory. Use a high-quality detergent oil classified “For Service CC, SD, SE, SF.” Detergent oils keep the engine cleaner and reduce carbon deposits. Use oil having the following SAE viscosity rating, based on the ambient temperature range anticipated before the next oil change:
Do not use mouth to siphon coolant from the radiator, recovery bottle or any container. Wash hands thoroughly after handling. Never store used antifreeze in an open container because animals are attracted to the smell and taste of antifreeze even though it is poisonous to them.
Any attempt to crank or start the engine before
it has been properly serviced with the recom- mended oil may result in an engine failure.
For temperatures below 32° F, it is strongly recom- mended to use the optional Cold Weather Start Kit (part number listed in the Specification Section). The oil grade for temperatures below 32° F is 5W- 30 synthetic oil.
Equip001 Rev. 0 08/05
Equipment Description

Standby Generator Sets Engine Protective Devices
ENGINE PROTECTIVE DEVICES The standby generator may be required to operate for long periods of time without an operator on hand to monitor such engine conditions as coolant tempera- ture, oil pressure or rpm. For that reason, the engine has several devices designed to protect it against potentially damaging conditions by automatically shutting down the unit when the oil pressure is too low, the coolant temperature is too high, the coolant level is too low, or the engine is running too fast.
After a prespecified duration of cranking, this func- tion ends the cranking if the engine has failed to start. The overcrank LED will turn ON. Turn OFF the AUTO/OFF/MANUAL switch, then turn switch back to AUTO to reset the generator control board.
If the fault is not corrected, the overcrank feature will continue to activate.
Engine protective switches and sensors are men- tioned here for the reader’s convenience. Also refer to the applicable control panel manual for additional automatic engine shutdown informa- tion.
This switches contacts close if the temperature should exceed approximately 140° C (284° F), initiating an engine shutdown. The generator will automatically restart and the LED will reset once the temperature has returned to a safe operating level.
A speed circuit controls engine cranking, start-up, operation and shutdown. Engine speed signals are delivered to the circuit board whenever the unit is running. Should the engine overspeed above a safe, preset value, the circuit board initiates an automatic engine shutdown. Contact the nearest Authorized Dealer if this failure occurs.
Should the engine coolant level drop below the level of the high coolant temperature switch, it is possible for the engine to overheat without automatic shut- down. To prevent such overheating, the engine has a low coolant level sensor. If the level of engine coolant drops below the level of the low coolant level sensor, the engine automatically shuts down.
If the speed signal to the control panel is lost, engine shutdown will occur.
LOW OIL PRESSURE SWITCH
This fuse is located inside of the control panel. It protects the panel wiring and components from damaging overload. Always remove this fuse before commencing work on the generator. The unit will not start or crank if the fuse is blown. Replace the fuse with one of the same size, type, and rating. (See the exploded views and parts lists at the end of this manual for replacement part number.)
This switch has normally closed contacts that are held open by engine oil pressure during cranking and operating. Should oil pressure drop below the 8 psi range, switch contacts close, and the engine shuts down. The unit should not be restarted until oil is added, and the AUTO/OFF/MANUAL switch must be turned to OFF and then back to AUTO.
EngProt001 Rev. 0 08/05

This type of system utilizes the vapors formed above the liquid fuel in the supply tank. Approximately 10 to 20 percent of the tank capacity is needed for fuel expansion from the liquid to the vapor state. The vapor withdrawal system is generally best suited for smaller engines that require less fuel. The installer should be aware of the following:
The standby generator may be equipped with one of the following fuel systems:
Recommended fuels should have a Btu content of at least 1,000 Btus per cubic foot for natural gas; or at least 2,520 Btus per cubic foot for LP gas. Ask the fuel supplier for the Btu content of the fuel.
Required fuel pressure for natural gas is 5 inches to 14 inches water column (0.18 to 0.5 psi); and for liquid propane, 5 inches to 14 inches of water column (0.18 to 0.5 psi).
LP is supplied as a liquid in pressure tanks. It is usually made up of propane, butane, or a mixture of the two gases. Propane tends to vaporize readily even at temperatures as low as -20° F (-29° C). However, butane reverts to its liquid state when temperatures drop below 32° F (0° C).
LP in a liquid withdrawal system must be converted to its gaseous state before it is introduced into the engine carburetor. A vaporizer-converter is generally used to accomplish this. In such a converter, heated engine coolant is ported through the converter to provide the necessary heat for conversion of the fuel from a liquid to a gaseous state.
Natural gas is supplied in its vapor state. In most cases, the gas distribution company provides piping from the main gas distribution line to the standby generator site. The following information applies to natural gas fuel systems.
FuelSys001 Rev. 0 08/05

Engine Lubrication System Type of Oil Pump Gear Oil Filter Full Flow, Cartridge Crankcase Oil Capacity 4 U.S. qts.
GENERATOR Type Synchronous Rotor Insulation Class F Stator Insulation Class F Total Harmonic Distortion < 5% Telephone Interference Factor (TIF) < 50 Alternator Output Leads 3-phase 4-wire Bearings Sealed Ball Coupling Flexible Disc Load Capacity (Standby Rating) 20kW* * NOTE: Generator rating and perfomance in accordance with ISO8528-5, BS5514, SAE J1349, ISO3046 and DIN 6271 Standards. KW rating is based on LPG fuel and may derate with natural gas. Excitation System Direct Generator Output Voltage/kW - 60 Hz kW Amp CB Size 120/240V, 1-phase, 1.0 pf 20 83 100 120/208V, 3-phase, 0.8 pf 20 69 100 Generator Locked Rotor KVA Available @ Voltage Dip of 35% Single-phase or 208 3-phase 34 KVA
Type Closed Water Pump Belt Driven Fan Speed 2550 Fan Diameter 15 inches Fan Mode Pusher Air Flow (inlet air including alternator and combustion air) 1528 ft3/min. Coolant Capacity 2.0 U.S. gal. Heat Rejection to Coolant 107,000 Btu/h Maximum Operating Air Temp. on Radiator 60° C (150° F) Maximum Ambient Temperature 50° C (140° F)
FUEL SYSTEM Type of Fuel Natural Gas, Propane Vapor Carburetor Down Draft Secondary Fuel Regulator Standard Fuel Shut-off Solenoid Standard Operating Fuel Pressure 5 in. - 14 in. Water Column
ENGINE Make Generac Model In Line Cylinders and Arrangement 4 Displacement 1.5 Liter Bore 2.97 in. Stroke 3.23 in. Compression Ratio 9.4-to-1 Air Intake System Natually Aspirated Valve Seats Replaceable Lifter Type Hydraulic
Fuel Consumption - ft3/hr (Natural Gas/LPV) Exercise 25% 50% 75% 100% Cycle Load 60/24 124/49 188/75 250/99 515/125
ELECTRICAL SYSTEM Battery Charge Alternator 12V, 15 Amp Static Battery Charger 2 Amp Recommended Battery Group 26, 525CCA System Voltage 12 Volts
Engine Parameters Rated Synchronous RPM 60 Hz, 3600 HP at rated kW 60 Hz, 32
Voltage Regulator Type Electronic Sensing Single-phase Regulation ± 1% Features V/F Adjustable, Adjustable
Exhaust System Exhaust Flow at Rated Output 60 Hz 177 cfm Exhaust Temperature at Rated Output 910° F
Voltage and Gain LED Indicators
Combustion Air Requirements (Natural Gas) Flow at rated power, 60 Hz 70 cfm
Power Adjustment for Ambient Conditions Temperature Deration 3% for every 10° C above °C 25 1.65% for every 10° above °F 77 Altitude Deration 1% for every 100 m above m 182 3% for every 1000 ft. above ft 600
Governor Type Electronic Frequency Regulation Isochronous Steady State Regulation ± .25% Adjustments: Speed Selectable
Controller R-100 (0F7380D - 240V) (0F7381D - 208V)
GenSpec013 Rev. A 09/05

CONTROL PANEL
NEUTRAL
TO ALTERNATOR
Gen N1 N2 23 194
N1 N2 23 194
GENERATOR CONNECTION BOX
GROUND
TO GENERATOR CONNECTION BOX
120 Volt + Neutral Grd
To Generator Control Panel
CIRCUIT BREAKER SIZE KW VOLTS / AMPS LUG SIZE 20 240 1 Ø 100 #4 to 1/0 20 208 3 Ø 80 #4 to 1/0
Ground Level Concrete Slab STUB-UP AREA See Install Dwg for
For cold climates, optional cold weather kit (part number 0F6148) is recommended. The kit includes:
RECONFIGURING THE FUEL SYSTEM
Port 1 Port 2
FUEL HOSE
NOTE:
PLUG
BRASS HOSE FITTING
BRASS HOSE FITTING
PLUG
OUT PORT 1
All models are configured for natural gas or LP vapor from the factory.
HOUSING PORTS
HOUSING PORTS
To reconfigure the fuel system from NG to LP, follow these steps:
1. Turn the main gas supply off. 2. Remove the carburetor fuel hose from the outlet port (Port 1) of the demand regulator (Figure 6.2). 3. Remove the brass hose fitting from the outlet port (Port 1) of the demand regulator. 4. Remove pipe plug from Port 2. 5. Install brass hose fitting into Port 2. 6. Install pipe plug into Port 1. 7. Connect carburetor gas hose to brass fitting. 8. Tighten all clamps and plugs. 9. Make sure fuel supply is of the proper pressure and type for configuration.
NOTE:
Port 1 is for NG only and Port 2 is for LP vapor only. No provision for dual fuel has been made.
Serious injury or damage may occur if not con-
figured properly. Please consult an Authorized Dealer with any questions.
GenSpec013 Rev. A 09/05

GENERATOR AC LEAD CONNECTIONS See “Voltage Codes”. This generator may be rated at any one of three voltages, either single-phase or three-phase. The electrical wires in the unit’s AC con- nection (lower) panel should be installed according to the number of leads and the voltage/phase required for the application. If there are any questions regard- ing lead connection, refer to the wiring diagrams at the back of this manual.
The generator is designed to supply 3-phase electri- cal loads. Electric power is produced in the alterna- tor power windings. These windings were connected at the factory to the main circuit breaker with a “Y” configuration as shown in Figures 7.2 and 7.3.
Voltage codes apply to the type of stator assembly installed on a particular generator.
The rated voltage between circuit breaker terminals E1-E2, E1-E3 and E2-E3 is either 480V or 208V depending on the model.
Four-lead generators (see Figure 7.1) are designed to supply electrical loads with voltage code “A” (240V, 1-phase, 60 Hz). Electrical power is produced in the stator power windings. These windings were con- nected at the factory to the main circuit breaker as shown in Figure 7.1.
The rated voltage between each circuit breaker termi- nal and the neutral point 00 is either 277V or 120V depending on the model.
The rated voltage between each circuit breaker ter- minal is 240V. The rated voltage between each circuit breaker terminal and the neutral point 00 is 120V.
Figure 7.1 — Four-lead, Single-phase Stator
INTERNAL CONNECTIONS
L-L S4
S6
NEUTRAL
S5
E3 S3
E2 S2
L-N
Figure 7.3 — Stator Power Winding Connections - 3-phase, 120/208V (6 Lead)
E1
S1 S1
S4 S4
00 (NEUTRAL)
S6
S5
S6 S3
S5 S2
E3 E2
S3
S2
L-N
ACConn001 Rev. 0 08/05
General Information · ·

INSTALLATION Refer to the separate “Installation Guide QT Product Line” supplied with the unit.
Prior to initially starting the generator, it must
PREPARATION BEFORE START-UP The instructions in this section assume that the standby generator has been properly installed, ser- viced, tested, adjusted and otherwise prepared for use by a competent, qualified installation contractor. Be sure to read the “Safety Rules”, as well as all other safety information in this manual, before attempting to operate this (and related) equipment.
be properly prepared for use. Any attempt to crank or start the engine before it has been properly serviced with the recommended types and quantities of engine fluids (oil, coolant, fuel, etc.) may result in an engine failure.
Have the engine cooling system properly filled with the recommended coolant mixture. Check the system for leaks and other problems. See “Specifications” and “Coolant” sections.
Before starting the generator for the first time, the installer must complete the following procedures. For follow-up maintenance information and/or service intervals, please refer to the “Maintenance” section and the “Service Schedule”.
TRANSFER SWITCH
Check-the engine-fan belt tension and condition prior to placing the unit into service and at recommended intervals. Belt tension is correct when a force of approximately 22 pounds (10 kg), applied midway between pulleys, deflects the belt about 3/8- to 5/8- inch (10 to 16 mm).
If this generator is used to supply power to any elec- trical system normally powered by an electric utility, the National Electrical Code requires that a transfer switch be installed. The transfer switch prevents elec- trical backfeed between two different electrical sys- tems. (For additional information, see the applicable transfer switch manual for this unit.) The transfer switch, as well as the generator and other standby components, must be properly located and mounted in strict compliance with applicable codes, standards and regulations.
Make sure the generator is properly connected to an approved earth ground.
Make sure the generator battery is fully charged, properly installed and interconnected, and ready for use.
Check to ensure that there are no loose electrical con- nections. Restrain any loose wires to keep them clear of any moving generator set components.
Make sure the fuel supply system to the genera- tor (a) delivers the correct fuel at the correct pres- sure and (b) is properly purged and leak tested according to code. No fuel leakage is permitted. See “Specifications” for more information.
INITIAL INSPECTION FOR QT GENSET STARTUP Inspect for the following.
Check the engine crankcase oil level before operating and add oil to the proper level – the dipstick “FULL” mark. Never operate the engine with the oil level below the dipstick “ADD” mark. See “Specifications” and “Engine Oil Recommendations”.
This engine is shipped from the manufacturer with “break-in” oil. This oil should be changed after 30 hours of operation.
Check the oil level in the generator gearbox (if so equipped) prior to initial use and at the intervals indicated by the “Service Schedule.” The recom- mended oil is SAE 90 gear lubricant.
Also, if the engine is equipped with a mechanical gov- ernor, make sure the governor is properly lubricated with clean engine oil.
Install001 Rev. 0 08/05

Before working on the generator, ensure the fol-
Make certain all 3-phase loads are functioning correctly (correct phase rotation). • Reconnect Utility power Transfer switch will transfer back to Utility and
When a start-up is performed by an Authorized Service Dealer, a standard three-part form titled “Start-up Inspection for Standby Power Systems” (part no. 067377), should be completed by the instal- lation technician or engineer. See page 1-3 for infor- mation on locating the nearest Authorized Service Dealer. The installer should complete the form and disseminate copies as follows:
Install001 Rev. 0 08/05
Installation · ·

GENERATOR CONTROL AND OPERATION Refer to the appropriate control panel operator’s manual for this unit.
Do not crank the engine continuously for longer
OPERATING UNIT WITH MANUAL TRANSFER SWITCH If the generator was installed in conjunction with a transfer switch capable of manual operation only, the following procedure applies. A manually operated transfer switch is one that will not provide automatic start-up and does not include an intelligence circuit.
RETRANSFER AND SHUTDOWN
For additional information, refer to the applicable control panel manual for this unit, as well as any lit- erature pertaining to the specific transfer switch.
For additional information, refer to the applicable control panel manual for this unit, as well as any lit- erature pertaining to the specific transfer switch.
To transfer the load back to the utility power source and shut down the generator, follow these direc- tions:
The Maintenance Disconnect Switch and the
AUTO/OFF/MANUAL switches (if so equipped) must be set properly, or the generator will crank and start as soon as the utility power to the transfer switch is turned off. Refer to applicable control panel and transfer switch manuals for more information. Do not proceed until certain that utility source
voltage is available to the transfer switch and the transfer switch main contacts are set to UTILITY. Do not attempt manual operation until all power
supplies to the transfer switch have been posi- tively turned off, or extremely dangerous - pos- sibly lethal - electrical shock will result. Transfer switch enclosure doors should be kept
OPERATING UNIT WITH AUTOMATIC TRANSFER SWITCH If the generator has been installed with an automatic transfer switch, such as an RTS, HTS, or GTS-type transfer switch, the engine may be started and stopped automatically or manually.
closed and locked. Only authorized personnel should be allowed access to the transfer switch interior. Extremely high and dangerous voltages are present in the transfer switch. In order to transfer load from the utility source to the generator, follow these directions:
Refer to the applicable manual for your trans- fer switch and to “Transfer Switch Start Signal Connections”. In addition, please note the dangers under “Engine Start-up and Transfer.”
Oper001 Rev. 0 08/05
Operation · ·

COOLING SYSTEM Air intake and outlet openings in the generator com- partment must be open and unobstructed for contin- ued proper operation. This includes such obstruc- tions as high grass, weeds, brush, leaves and snow.
Before working on the generator, ensure the fol-
Without sufficient cooling and ventilating air flow, the engine/generator quickly overheats, which causes it to shut down. (See the installation diagram.)
The exhaust system parts from this product get
extremely hot and remains hot after shutdown. High grass, weeds, brush, leaves, etc. must remain clear of the exhaust. Such materials may ignite and burn from the heat of the exhaust system.
OVERLOAD PROTECTION FOR ENGINE DC ELECTRICAL SYSTEM Engine cranking, start up and running are controlled by a solid state Engine Controller circuit board. Battery voltage is delivered to that circuit board via a 15 amp fuse. These overcurrent protection devices will open if the circuit is overloaded.
If a circuit breaker opens or a fuse element
melts, find the cause of the overload before resetting the circuit breaker or replacing the fuse.
CHECKING FLUID LEVELS
Check engine crankcase oil level (Figure 10.1) at least every 20 hours of operation, or prior to use.
Maint006 Rev. 0 08/05

EXERCISE SYSTEM
Start the generator engine at least once every seven days and let it run at least 20 minutes. See “Weekly Exercise Cycle”.
OIL DIPSTICK
INSPECT COOLING SYSTEM
See “Checking Fluid Levels”.
BATTERY FLUID
Complete a thorough visual inspection of the entire engine-generator monthly. Look for obvious damage, loose, missing or corroded nuts, bolts and other fas- teners. Look for fuel, oil or coolant leaks.
Check battery electrolyte fluid based on the Maintenance Schedule. Fluid should cover separa- tors in all battery cells. If fluid level is low, add dis- tilled water to cover tops of separators. DO NOT USE TAP WATER IN BATTERY.
Inspect the exhaust system at least once every three months. Check all exhaust system pipes, mufflers, clamps, etc. for condition, tightness, leaks, security, damage.
Check coolant level in coolant recovery bottle. See Specifications.
MAINTENANCE OWNER/ OPERATOR CAN PERFORM
Visually inspect electronic governor.
Do not attempt to adjust the governor. Only
qualified service facilities should adjust the governor. Excessively high operating speeds are dangerous and increase the risk of personal injury. Low speeds impose a heavy load on the engine when adequate engine power is not available and may shorten engine life. Correct rated frequency and voltage are supplied only at the proper governed speed. Some connected electrical load devices may be damaged by incor- rect frequency and/or voltage. Only qualified service technicians should adjust the governed speed.
Refer to “Checking Fluid Levels”.
Maint006 Rev. 0 08/05

Figure 10.3 – Engine Air Cleaner
Refer to maintenance performed by authorized service facilities for engine oil and filter change frequencies.
Drain the oil while the engine is still warm from run- ning. This means warm up the engine, shut it down and drain immediately as follows:
(Doors Removed for Clarity)
SPARK PLUGS
Reset the spark plug gap or replace the spark plugs as necessary (Figure 10.4).
1. Clean the area around the base of the spark plugs to keep dirt and debris out of the engine. Clean by scraping or washing using a wire brush and commercial solvent. Do not blast the spark plugs to clean. 2. Remove the spark plugs and check the condition. Replace the spark plugs if worn or if reuse is questionable. See the “Service Schedule,” Section 6, for recommended inspection. 3. Check the spark plug gap using a wire feeler gauge. Adjust the gap to 0.5-0.6 mm (0.020-0.025 inch) by carefully bending the ground electrode (Figure 10.4).
SET PLUG GAP AT 0.5 - 0.6 mm
(0.020 - 0.025 inch)
After refilling the crankcase with oil, always
check oil level on dipstick. NEVER OPERATE ENGINE WITH OIL BELOW THE DIPSTICK “ADD” MARK. 7. Start engine and check for oil leaks.
COOLANT CHANGE
To replace the engine air cleaner, (part number 059402), simply remove the air cleaner cover and replace the air filter making sure it is positioned properly before reattaching the cover (Figure 10.3).
Every year, have an Authorized Service Facility drain, flush and refill the cooling system. See “Specifications” for cooling system recommendations.
See the “Service Schedule,” for air cleaner mainte- nance.
Maint006 Rev. 0 08/05

Keep the generator as clean and as dry as possible. Dirt and moisture that accumulates on internal gen- erator windings have an adverse effect on insulation resistance.
Periodically clean generator exterior surfaces. A soft brush may be used to loosen caked on dirt. Use a vacuum system or dry, low pressure air to remove any accumulations of dirt. The generator is housed inside an all-weather enclosure, clean the enclosure with a soft, damp cloth or sponge and water.
Storage batteries give off explosive hydrogen
gas. This gas can form an explosive mixture around the battery for several hours after charg- ing. The slightest spark can ignite the gas and cause an explosion. Such an explosion can shat- ter the battery and cause blindness or other injury. Any area that houses a storage battery must be properly ventilated. Do not allow smok- ing, open flame, sparks or any spark producing tools or equipment near the battery. Battery electrolyte fluid is an extremely corro-
Once each year have the generator cleaned and inspected by an Authorized Service Dealer. That dealer will use dry, low pressure air to clean internal windings. Parts inside the control console should be cleaned and inspected at this time as well.
sive sulfuric acid solution that can cause severe burns. Do not permit fluid to contact eyes, skin, clothing, painted surfaces, etc. Wear protective goggles, protective clothing and gloves when handling a battery. If fluid is spilled, flush the affected area immediately with clear water. Do not use any jumper cables or booster battery
Finally, have the insulation resistance of stator and rotor windings checked. If insulation resistances are excessively low, the generator may require drying.
All lead-acid storage batteries discharge when not in use. Refer to specific instructions and warnings that accompany the battery. If such information is not available, observe the following precautions when handling a battery:
to crank and start the generator engine. If the battery has completely discharged, remove it from the generator for recharging.
Be sure the AUTO/OFF/MANUAL switch is set to
the OFF position, before connecting the battery cables. If the switch is set to AUTO or MANUAL, the generator can crank and start as soon as the battery cables are connected. Be sure the 120VAC power supply to the battery
is turned OFF, or sparking may occur at the bat- tery posts as the cables are attached and cause an explosion.
When replacing batteries, use the same number and the type of battery that follows:
BCI Group No. CCA 26 525 @ 0 deg. F
The BCI number should be located directly on the battery.
PERIODIC REPLACEMENT PARTS Part Name Part Number Oil Filter # 0A4531A244 Radiator Cap # 046627 Air Cleaner # 059402 Spark Plug # 0A45310275
The battery should be inspected per Section 4.7, Scheduled Maintenance. The following procedure should be followed for inspection:
Maint006 Rev. 0 08/05

SERVICE SCHEDULE The following is a recommended maintenance schedule for small standby and residential generator sets. The established intervals in the schedule are the maximum recommended when the unit is used in an average service application. They will need to be decreased (performed more frequently) if the unit is used in a severe application. Use calendar time from the previous maintenance interval to determine the next required maintenance interval.
1 An early inspection of the generator set to insure it is ready to operate when required and to identify any poten- tial problem areas.
Performed monthly this requires approximately .5 man-hours per unit to complete.
This inspection may be performed by the end user providing the following safety steps are taken to prevent the engine from starting automatically without warning:
To prevent injury, perform the following steps in the order indicated before starting any maintenance:
The battery charger must be turned off BEFORE removing the battery cable to prevent an over current condition
from burning out sensitive control panel components and circuits.
Following all maintenance, reverse these steps to insure the unit is returned to standby setup for normal operation when required.
2 A break-in service inspection of the generator set to insure it is ready to operate and carry the load when required, and to identify any potential problem areas.
Performed ONLY ONCE following the first three months of operation after purchase of the unit and requires approximately 2.5 man-hours per unit to complete.
This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge to accomplish and should be performed only by an Authorized Service Dealer.
3 An operational inspection of the generator set to insure it is ready to operate and carry the load when required, and to identify any potential problem areas.
Performed semi-annually this requires approximately 1.5 man-hours per unit to complete.
This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge to accomplish and should be performed only by an Authorized Service Dealer.
4 A mid-level inspection of the generator set to insure it is ready to operate and carry the load when required, and to identify any potential problem areas.
Performed annually this requires approximately 4.0 man-hours per unit to complete.
This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge to accomplish and should be performed only by an Authorized Service Dealer.
SrvSchd002 Rev. A 09/05
Service Schedule

Maintenance Level 1 Level 2 Level 3 Level 4 Tasks Recom- Task Required Task Required Task Task mended Comp. to be done Comp. to be done Comp. Required Comp. to be done (Date- 3 months/ (Date- Semi- (Date- to be done (Date- monthly Initials) Break-in Initials) annually Initials) Annually Initials) 1. Disable the unit from operating per the first page warning. 2. Check the engine oil level. Adjust as necessary. 3. Check the engine coolant level. Adjust as necessary. 4. Check the engine coolant thermal protection level. Correct as necessary. 5. Check the natural gas delivery system on gas engine driven units. Tighten connections as necessary. 6. Check the air inlets and outlets for debris. Clean as necessary. 7. Check the battery electrolyte level if accessible. Adjust as necessary. 8. Check the battery posts, cables, and charger for loose connections, corrosion, and proper operation. Correct as necessary. 9. Check the unit wiring for loose connections, corrosion, and damage. Correct as necessary. 10. Check the engine accessory drive belts for wear, weather cracking, and damage. Replace as necessary. 11. Visually inspect the unit looking for leaks, wear or damage, loose connections or components, and corrosion. Correct as necessary. 12. Test the engine and transfer switch safety devices. Correct and/or adjust as necessary.
SrvSchd002 Rev. A 09/05
Service Schedule

Maintenance Level 1 Level 2 Level 3 Level 4 Tasks Recom- Task Required Task Required Task Task mended Comp. to be done Comp. to be done Comp. Required Comp. to be done (Date- 3 months/ (Date- Semi- (Date- to be done (Date- monthly Initials) Break-in Initials) annually Initials) Annually Initials) 13. Initiate an automatic start and transfer of the unit to site load and exercise it for at least 1 hour looking for leaks, loose connections or components, and abnormal operating conditions. Correct as necessary. 14. Start and exercise the unit at full rated load (use a load bank if the site load is not enough) for at least 2 hours looking for leaks, loose connections or components, and abnormal operating conditions. Correct as necessary. 15. Change the engine oil. 16. Replace the engine oil filter(s). 17. Replace the engine air filter(s). 18. Replace the engine fuel filter(s) on diesel engine driven units and re-prime the fuel system. 19. Check the engine spark plugs on gas engine driven units. Clean and re-gap or replace as necessary. 20. Perform a 5 minute no-load operational run of the unit looking for any post service problems. 21. Return the unit to standby setup for operation when required.
SrvSchd002 Rev. A 09/05
Service Schedule

PROBLEM CAUSE CORRECTION
Engine won’t crank. 1. 15 amp fuse blown. 1. Replace fuse. 2. Loose or corroded or defective 2. Tighten, clean or replace battery cables. battery cables as necessary. 3. Defective starter contactor. 3. Replace contactor.* 4. Defective starter motor. 4. Replace starter motor.* 5. Dead or Defective Battery. 5. Remove, change or replace battery. 6. 5 amp fuse blown. 6. Replace fuse.* Engine cranks but won't start 1. Out of fuel. 1. Replenish fuel. 2. Fuel solenoid (FS) is defective 2. Replace solenoid.* 3. Open Wire #14A from Engine Control 3. Reconnect wire. circuit board. 4. Spark plugs defective. 4. Clean, regap or replace plugs. 5. Door on tank not closed. 5. Close door on tank. Engine starts hard, runs rough. 1. Flame arrestor (air cleaner) plugged or 1. Clean or replace as needed. damaged. 2. Plugged fuel line. 2. Unclog fuel line. 3. Defective spark plugs. 3. Clean, regap or replace plugs. 4. Fuel pressure incorrect. 4. Confirm fuel pressure to regulator is as recommended in SPECIFICATIONS. Engine starts then shuts down. 1. Engine oil level is low. 1. Check oil and add oil as needed. 2. Engine is overheated. 2. Check cooling system for leaks. 3. Defective Low Oil Pressure Switch 3. Replace switch.* 4. Defective Coolant Temperature Switch 4. Replace switch.* 5. Defective Control Module circuit board. 5. Replace board.* 6. Coolant Level is Low. 6. Repair leak - Add coolant. 7. Defective Low Coolant Level Switch 7. Replace Switch.* AUTO/OFF/MANUAL Switch at OFF, 1. Defective AUTO/OFF/MANUAL switch 1. Replace switch.* engine continues to run 2. Open/disconnected wire #15A between 2. Reconnect/close wire. AUTO/OFF/MANUAL switch and Control Module circuit board. 3. Defective Control Module circuit board 3. Replace board.* No AC output from generator. 1. Check main line circuit breaker. 1. Reset to ON or CLOSED. 2. Check circuit breaker & fuses. 2. Reset and replace, if necessary. 3. Transfer switch set to NORMAL position 3. Set to GENERATOR position. 4. Generator internal failure. 4. * 5. Thermal circuit breaker open. 5. Auto-reset - Wait 5 min. and attempt restart.
*Contact the nearest Authorized Dealer for assistance.
Trblsht001 Rev. 0 08/05
Troubleshooting





1 0F7135 1 BREAKER TRAY BACK/BOTTOM 2 0F7022 1 SUPPORT CONTROL PANEL SIDE RH 3 0F7021 1 SUPPORT CONTROL PANEL SIDE LH 4 0F7260 1 COVER CIRCUIT BREAKER 2P 0F7136 1 COVER CIRCUIT BREAKER 3P 5 0F6156 1 PLATE WIRE SNGL GALV 6 0F4464 1 DECAL CUST CONN 120V UTILITY 7 0D4698 REF BLOCK TERM 20A 6 X 3 X 1100V 8 0F3824 1 DECAL UTIL SENSE/CUST CONN 9 057701 REF BLOCK TERM 20A 8 X 6 X 1100V 10 0F6146 1 HANG TAG 2 WIRE START (NOT SHOWN) 12 081008 1 GROMMET 1.25 X .25 X .75 13 0C2267 2 SCREW HHTT M5-0.8 X 12 BP 14 049226 2 WASHER LOCK M5 15 051713 2 WASHER FLAT M5 16 0C2212 11 SCREW PHTT M4-0.7 X 16 ZYC 17 022264 11 WASHER LOCK #8-M4 18 0F6366A 1 XFMR DUAL 104V/16V (1 PHASE) 0F6366B 1 XFMR DUAL 120V/16V (3 PHASE) 19 022241 1 NUT HEX 3/8-16 STEEL 20 022237 1 WASHER LOCK 3/8 21 057329 1 LUG SLDLSS 350-#6 X 13/32 AL/CU 22 057073 1 JUNCTION BLOCK 3/8-16 23 023484J 1 BUSHING SNAP SB-2000-26 24 0E3257 15 SCREW HWHTF M6-1.0 X 16 25 0E7890 REF BRKT CB MTG BACK 2P 0E6002 REF MTG TRACK BQ SIEMENS CB 3P 26 0D5544 REF CB 0100A 2P 240V S BQ2 LL (1.5L 2 POLE) 062812 REF CB 0080A 3P 240V S BQ3 LL (1.5L 3 POLE) 0A2077 REF CB 0125A 2P 240V S BQ2 LL (2.5L 2 POLE) 040532 REF CB 0100A 3P 240V S BQ3 LL (2.5L 3 POLE) 27 052619 REF SCREW HHC M5-0.8 X 20 G8.8 (NOT SHOWN) 28 023897 REF WASHER FLAT #10 ZINC (NOT SHOWN) 29 049226 REF WASHER LOCK M5 (NOT SHOWN) 30 051716 REF NUT HEX M5-0.8 G8 CLEAR ZINC (NOT SHOWN) 31 025433 1 LUG SLDLSS #6-14 X 13/64 CU 32 * 0A1354A REF REGULATOR - DC ALT 33 * 042568 REF SCREW HHC M6-1.0 X 20 G8.8 34 * 022473 REF WASHER FLAT 1/4-M6 ZINC 35 * 022097 REF WASHER LOCK M6-1/4 36 * 049813 REF NUT HEX M6 X 1.0 G8 YEL CHR 37 * 0F7194 REF BRACKET PANEL SUPPORT 1.5L C1 38 057593 1 CABLE TIE MOUNT BLACK
* USED ON 1.5L ONLY.




1 098675 1 ASSY ROTOR 20KW 2 0A5336A 1 HOUSING BLOWER 3 0A1659 1 SCREEN AIR OUTLET 4 020746 4 SCREW PPHM M5-0.8 X 8 ZINC 5 049226 4 WASHER LOCK M5 6 051713 4 WASHER FLAT M5 7 022129 4 WASHER LOCK M8-5/16 8 0F8218 1 ASSY STATOR 20KW 1PH A 0F8220 1 ASSY STATOR 20KW 3PH GJK 9 0A5382 1 BEARING CARRIER REAR 10 075591 1 ASSY HOLDER BRUSH 11 075476 4 SCREW PPHM M4-0.7 X 16 12 0A5601A 1 COVER REAR BEARING 13 075554B 4 BOLT STATOR X 16" LG 14 0A9375 4 SCREW RHM #10-24 X 2 15 022152 4 WASHER LOCK #10 16 097146 1 FAN & RING GEAR ASSEM. 17 042558 1 KEY SQ 3/8 X 1 STEEL 18 0A5061 1 SPACER-FLEX PLATE 19 0A4989 1 PLATE FLEX 20 053557 1 SCREW HHC M12-1.75 X 40 G8.8 21 051769 6 WASHER LOCK M12 22 049541 4 SCREW HHC M10-1.5 X 35 G8.8 23 046526 4 WASHER LOCK M10 24 045772 4 NUT HEX M10-1.5 G8 YEL CHR 26 * 087599 2 PLUG PLASTIC 3/8 NPT 27 077043E 1 FLEX CONDUIT 1" BLACK (NOT SHOWN) 28 022131 4 WASHER FLAT 3/8-M10 ZINC 29 072578 1 SPACER ROTOR SHAFT 30 0A7043 5 SCREW HHC M12-1.25 X 25 G8.8 31 049808 5 WASHER FLAT M12 32 058589 1 DECAL WARN ENG START 33 023365 4 WASHER SHAKEPROOF INT #8 35 0A8830 4 WASHER FLAT .34 ID X .75 OD 36 072080 1 DECAL DANGER STANBY UNITS




1 0F3408B 1 BATTERY TRAY C1 CPL 2 0F3411 1 STRAP BATTERY RETAINMENT 3 025507 REF WASHER SHAKEPROOF EXT 7/16 STL 4 052647 REF SCREW SHC M10-1.5 X 25 G12.9 5 046526 REF WASHER LOCK M10 6 022131 REF WASHER FLAT 3/8-M10 ZINC 7 050331A REF BATT POST COVER RED + 8 050331 REF BATT POST COVER BLK - 9 038805J 1 CABLE BATTERY BLK #1 X 30.00 10 038804U 1 CABLE BATTERY RED #1 X 28.00 11 045771 REF NUT HEX M8-1.25 G8 YEL CHR 12 022129 REF WASHER LOCK M8-5/16 13 027482 REF WASHER SHAKEPROOF EXT 5/16 STL 14 0F3976 3 BOOT CONTACTOR CABLES 15 0C2454 4 SCREW THF M6-1 X 16 N WA Z/JS 16 022145 REF WASHER FLAT 5/16-M8 ZINC 17 077483 REF BATTERY 12VDC 75-AH 26 18 0742600131 1 ASSY WIRE #16 RED 1.6




1 0F7155 1 MOUNTING BASE 1.5L C1 CPL 2 027482 2 WASHER SHAKEPROOF EXT 5/16 STL 3 070936 2 DAMPENER VIBRATION 4 070936C 2 VIB. ISO. 70-75 DURO 5 039253 8 SCREW HHC M8-1.25 X 20 G8.8 6 022145 12 WASHER FLAT 5/16 ZINC 7 022129 12 WASHER LOCK M8-5/16 8 045771 4 NUT HEX M8-1.25 G8 YEL CHR 9 071956 4 WASHER FLAT M8 10 051730 4 SCREW HHC M8-1.25 X 60 G8.8 11 021991 1 EARTH STRAP 12 0F7194 2 BRACKET PANEL SUPPORT 1.5L C1 13 026850 1 WASHER SHAKEPROOF EXT 1/4 STL 14 049813 5 NUT HEX M6 X 1.0 G8 YEL CHR 15 055414 1 LUG SLDLSS #2-#8 X 17/64 CU 16 047411 5 SCREW HHC M6-1.0 X 16 G8.8 17 022097 5 WASHER LOCK M6-1/4 18 022473 9 WASHER FLAT 1/4-M6 ZINC




1 0F7211 1 SUPPORT RADIATOR LH SIDE 2 0F7209 1 VENTURI 15" DIA FAN 3 0F7210 1 SUPPORT RADIATOR RH SIDE 4 0E9837A 1 RADIATOR 2.5L CPL 5 0E1936 1 FAN COOLING 15" 6 022129 1 WASHER LOCK M8-5/16 7 0F7166 1 RADIATOR HOSE LWR 1.5L C1 CPL 8 099502 4 CLAMP HOSE #24 B1.06-2.00 9 069860C 1 HOSE OIL DRAIN ASSY 21" 10 035461 1 BARBED STR 1/4 NPT X 3/8 11 0A6258 1 HOSE - UPPER RADIATOR 12 046627 1 CAP RADIATOR 13 052250 2 TAPE FOAM 1 X 1 (17” LG) 14 022473 8 WASHER FLAT 1/4-M6 ZINC 15 022097 16 WASHER LOCK M6-1/4 16 0C8566 8 SCREW HHFC M6-1.0 X 20 G8.8 17 049813 4 NUT HEX M6 X 1.0 G8 YEL CHR 18 0C2454 24 SCREW THF M6-1 X 16 N WA Z/JS 19 055816 4 SCREW HHC M6-1.0 X 70 G8.8 20 0F7594 4 GUARD FAN LH C1 CPL 21 0F7595 4 GUARD FAN RH C1 CPL 22 0C7649 1 CLAMP HOSE .38-.87 23 0F7320 1 BLOCK OFF UPPER 24 0F1433 1 BRACKET 2.5L FORD WATER BOTTLE 25 076749 1 TANK COOLANT RECOVERY 26 048031C 2 CLAMP HOSE BAND 1/4 27 029032 1 HOSE 9/32 ID (40” LG) 28 040976 1 SCREW SHC M8-1.25 X 20 G12.9 29 022145 1 WASHER FLAT 5/16-M8 ZINC 30 029107 1 GROMMET 7/8 X 3/16 X 5/8



1 098290 1 ASM MOTOR STEPPER 2 098941A 1 HOUSING GOVERNOR CONNECTOR 3 098958A 1 CONNECTOR INTERFACE ASSEMBLY 4 098942A 1 COVER CONNECTOR HOUSING 5 098225 2 SCREW FHM #2 X 5/8 SELF TAP 6 043146 3 SCREW HHC M6-1.0 X 10 G8.8 7 022097 5 WASHER LOCK M6-1/4 8 064526 2 SCREW TAP HWH #6-25 X 3/8 ZINC 9 098783 1 LEVER STEPPER MOTOR 10 037398 2 NUT LOCK HEX #10-32 NYL INS 11 0A7041 1 ASSEMBLY CARBURATOR LINKAGE 12 0A7106 1 BRACKET STEPPER MOTOR 13 074031 - LIQUID NEOPRENE 14 029333A 1 TIE WRAP 7.4"X.19" BLK UL 15 022507 2 SCREW HHC 1/4-20 X 1/2 G5 16 022473 2 WASHER FLAT 1/4 ZINC



1 0A4531 REF ENGINE-1.5L 2 022473 2 WASHER FLAT 1/4 ZINC 3 * 055934C 1 CLAMP VINYL .5 X .406 Z 4 0A45310258 REF. GASKET-EXHAUST MANIFOLD 5 0A4355 1 MANIFOLD-EXHAUST 6 0E2632 1 HEAT SHIELD EXH 1.5L 7 022097 4 WASHER LOCK M6-1/4 8 022507 2 SCREW HHC 1/4-20 X 1/2 G5 9 052212 4 SCREW HHC M10-1.25 X 25 G8.8 10 046526 4 WASHER-LOCK-M10 11 022131 20 WASHER FLAT 3/8 ZINC 12 0C2499 2 STAMPING ENG FOOT 13 055993 1 SPACER .41 X .75 X .12 STL/ZNC 14 045772 1 NUT HEX M10-1.5 G8 YEL CHR 15 023586 2 SCREW SHC 5/16-18 X 2 G8.8 NZ 16 020692 1 STARTER-12V 17 0A7005 2 SPACER .56 X 1 X .37 ST/ZNC 18 052243 1 SCREW HHC M10-1.5 X 60 G8.8 19 0A4772 1 ENGINE PLATE 20 070901 2 SLEEVE DOWEL BLHSG 21 051735 3 SCREW HHC M10-1.5 X 70 G8.8 22 056768 3 SCREW HHC M10-1.5 X 90 G8.8 23 022145 12 WASHER FLAT 5/16 ZINC 24 022129 19 WASHER LOCK M8-5/16 25 022259 2 NUT HEX 5/16-18 STEEL 26 052213 11 SCREW HHC M10-1.25 X 20 G8.8 27 047411 2 SCREW HHC M6-1.0 X 16 G8.8 28 052830 1 SCREW HHC M10-1.25 X 45 G8.8 30 045771 12 NUT HEX M8-1.25 G8 YEL CHR 31 058306 5 SCREW SHC M8-1.25 X 25 G12.9 32 030795 2 SCREW HHC 5/16-18 X 1 G5 33 0A2711A 1 ADAPTER-THERMOSTAT 34 048665 1 GASKET THERMOSTAT 35 075885 1 THERMOSTAT 195 DEG 36 0A45310257 REF. GASKET INLET MANIFOLD 37 0E1100 1 MANIFOLD INTAKE MACHINED 38 0E0561 1 ASSY WATER LEVEL SENSOR C/E PL 39 0A6751 1 SW-TMP 245 DEG 3/8 NPT 41 026925 2 PLUG STD PIPE 3/8 STEEL SQ HD 42 061012 1 PLUG STD PIPE 1/8 SCKT HD 43 039253 5 SCREW HHC M8-1.25 X 20 G8.8 44 0A5110 1 PIPE WATER-INLET 45 0A7006 1 O-RING 1-1/16 X 1-5/16 X 1/8 46 025507 2 WASHER SHAKEPROOF EXT 7/16 STL 47 022500B 2 SPACER .41 X .75 X .25 ST/ZNC 48 0A8584 1 SWITCH OIL PRESSURE 49 036277 1 ELBOW 90D STREET 1/8 50 042574 1 ADAPTOR 1/8 NPTF TO 1/8-28 51 026073A 1 PLUG STD PIPE 1/4 STEEL SQ HD 52 0A6701 1 SCREW HHC M10-1.5 X 110 G8.8 53 039414 1 SCREW HHC M8-1.25 X 35 G8.8 55 051769 1 WASHER LOCK M12 56 0A4800A 1 PULLEY-CRANKSHAFT (3600 RPM) 57 0A5839 1 BRACKET - ALT SUPPRT 58 0A1354B 1 DC ALTERNATOR-12V 59 0A4839 1 ARM ADJUST ALTERNATOR 60 069860C 1 HOSE ASM.-OIL DRAIN 61 0F3856 1 GUARD CRANKSHAFT 1.5L 62 058443 2 SCREW CRIMPTITE 1/4-20 X 5/8 63 0A2628 1 PULLEY - FAN 95 DIA 64 0A5586 1 V-BELT 3/8 X 28.9D 65 0A4814 1 SPACER PULLEY 66 0A45310244 REF. FILTER OIL 67 0C1852 1 ADAPTER DRAIN OIL 68 0912970066 1 GROUND WIRE (STARTER) 69 070928 1 CLAMP HOSE - OIL DRAIN 70 069860C 1 HOSE OIL DRAIN ASSY 21"
71 035473 1 CLAMP HOSE #12 .50-1.25 72 077996 1 CAP ANTIFREEZE RUBBER 73 069811 1 CAP HEX 1/4 NPT BRASS 74 ** 0A1354A 1 REGULATOR - DC ALT 75 ** 042568 2 SCREW HHC M6-1.0 X 20 G8.8 76 ** 022473 2 WASHER FLAT 1/4-M6 ZINC 77 ** 022097 2 WASHER LOCK M6-1/4 78 ** 049813 2 NUT HEX M6 X 1.0 G8 YEL CHR 79 0D2244M 1 ASSY MAGPICKUP (3/8-24 MALE)
** NOT SHOWN



1 026812 2 ELBOW 90D 3/4 NPT 2 075580 1 FLANGE FUEL INLET 3 0F6364A 1 FUEL RGLTR 1.5L REWORK 4 039253 4 SCREW HHC M8-1.25 X 20 G8.8 5 022145 2 WASHER FLAT 5/16 ZINC 6 022129 6 WASHER LOCK M8-5/16 7 045771 2 NUT HEX M8-1.25 G8 YEL CHR 8 * 0F1570 1 BODY CARBURETOR ASSEMBLY 9 032552 1 BARBED EL 90 5/16 X 1/8 NPT 10 029032 1 HOSE 9/32 ID 11 025424 1 NIPPLE PIPE 3/4 NPT X 6 12 0F0397 1 HOSE CRANKCASE BREATHER 13 0A5547 1 COVER AIR CLEANER 14 048031C 4 CLAMP HOSE BAND 1/4 15 0D1509 1 DECAL INLET PRESSURE 16 * 0E0591 1 ADAPTER CARB. TO AIR CLNR 17 059402 1 FILTER ELEMENT 18 037561 1 NUT WING 1/4-20 NYLK 19 0E1028C 1 ASSY CARBURETOR 1.5L C1 CPL 20 059401 1 CARBURETOR GASKET 21 * 091526 4 SCREW PPHM M5-0.8 X 12 ZNC 22 * 049226 4 WASHER LOCK M5 23 026915 2 NIPPLE CLOSE 3/4 X 1.375 24 062522 1 STUD TH 1/4-20 X 3 G2 ZNC FULL 25 022127 1 NUT HEX 1/4-20 STEEL 26 022259 2 NUT HEX 5/16-18 STEEL 27 ** 050279 1 DECAL FUEL INLET NG 050280 1 DECAL FUEL INLET LPG 28 0A6125 2 STUD 5/16-18 X 1.25 F THR 29 0F6155 1 HARNESS FUEL JUMPER SINGLE REG 30 * 0E1104 1 GASKET AIR CLEANER ADAPTER 31 * 0E0668 1 O-RING 2-028 1.38 X 1.50 X .06 32 * 0E0590 1 VENTURI 18MM 33 * 0C5133 1 O-RING 29.82 X 2.62 34 * 0E0665 1 SCREW THROTTLE PIN STOP 35 * 0E1108 1 THROTTLE ARM REWORK 36 * 033138 1 SCREW HHM #10-32 X 5/8 37 * 022152 1 WASHER LOCK #10 38 * 0E0645 1 LEVER THROTTLE STOP 39 * 034339 1 BARBED EL 90 3/8 NPT X 5/8 40 059194 1 HOSE 5/8 ID LPG & NG (24” LG) 41 057823 2 CLAMP HOSE #10 .56 - 1.06 42 040173 2 CLAMP HOSE #5.5 .62-.62 43 * 089617 1 BARBED STR 1/4 NPT X 1/4 MALE 44 030340 1 HOSE 1/4 ID SAE 30R7 45 0A7040 1 BRACKET-RAD HOSE
NOTES:
1. REGULATOR (I/N 3) AS SHOWN IN ILLUSTRATION IS SET UP FOR NATURAL GAS APPLICATION. 2. TO CONFIGURE REGULATOR FOR LP VAPOR, SWITCH HOSE BARB, HOSE CLAMP (I/N 41) AND HOSE (I/N 40) FROM “OUT-1” TO “OUT-2”. REPLACE PIPE PLUG FROM “OUT-2” TO “OUT-1”. USE PIPE SEALANT ON HOSE BARB AND PIPE PLUG. MAKE SURE TO KEEP PORTS FREE FROM DEBRIS DURING RECONFIGURATION PROCESS. 3.** FOR LP VAPOR APPLICATION SUBSTITUE LPG FUEL INLET DECAL P/N 050280 FOR NG FUEL INLET DECAL P/N 050279 (ITEM 27). 4 . WHEN SWITCHING FUEL TYPES, THE PROPER DIP SWITCH SITTINGS MUST BE MADE TO THE CONTROL PANEL. SEE OWNERS MANUAL, FUEL SECTION FOR MORE DETAILS.




1 0F7003 (XX) 1 ROOF C1 CPL 2 0F7004 (XX) 1 CORNER POST LH SIDE C1 CPL 3 0F7008 (XX) 1 DOOR REAR C1 CPL 4 0F7005 (XX) 1 CORNER POST RH SIDE C1 CPL 5 0F7007 (XX) 2 DOOR LH & RH SIDE C1 CPL 6 0F7006 (XX) 1 DUCT FRONT DISCHARGE C1 CPL 7 0C2634A 1 ASSEMBLY COVER ACCESS 8 0912970091 1 ASSY WIRE 14AWG 13.8" GRN/YEL 9 0912970090 2 ASSY WIRE 14AWG 33.5" GRN/YEL 10 0E5968 1 GASKET EXTRUDED TRIM (356” LG) 11 0E3257 6 SCREW HWHTF M6-1.0 X 16 12 ** 077992 18 NUT HEX LOCK M6-1.0 SS NY INS 13 0F5049 3 TAB PULL 14 0F5048 3 LATCH VISE ACTION 5/16 HEX SKT 15 022473 1 WASHER FLAT 1/4-M6 ZINC 16 022097 1 WASHER LOCK M6-1/4 17 022127 1 NUT HEX 1/4-20 STEEL 18 0C2454 24 SCREW THF M6-1 X 16 N WA Z/JS 19 078115 20 WASHER SELF LOCKING DOME 20 0F3890B 2 RETAINER INSULATION (820) 21 0F3890 4 RETAINER INSULATION (450) 22 0F7365 2 INSULATION SIDE DOOR C1 23 0F7365B 1 INSULATION REAR DOOR C1 CPL 24 0F7365A 1 INSULATION ROOF C1 CPL
OPTIONAL COMPARTMENT MATERIALS: ALL P/N’S WITH AN (XX) SUFFIX INDICATE A MULTIPLE MATERIAL AND COLOR OPTION. USE THE FOLLOWING LEGEND TO IDENTIFY THE CORRECT PART NUMBER:
PART NO. MATERIAL COLOR 0XXXXXSN STEEL TAN 0XXXXXAN ALUMINUM TAN 0XXXXXSG STEEL GRAY 0XXXXXAG ALUMINUM GRAY
** ALUMINUM ENCLOSURE NOTE: ALL ENCLOSURE PANELS THAT FASTEN TO THE BASE FRAME MUST BE SECURED USING ITEM 18 & 11 THREAD FORMING FASTENER AND ITEM 12 LOCK NUT. LOCK NUT IS TO BE INSTALLED AFTER THREAD FORMING FASTENER HAS PENETRATED THROUGH EXTRUSIONS IN ENCLOSURE PANELS. ALL ROOF PANELS ARE TO BE SECURED IN THE SAME MANNER.




1 0F7366 1 MUFFLER C1 2 0F7647 1 MUFFLER SADDLE 3 0F8095 1 PIPE EXHAUST OUTLET 4 0F7538 1 PIPE EXH INLET MUFLR SIDE 1.5L 5 0E3257 4 SCREW HWHTF M6-1.0 X 16 6 0F7644 2 MUFFLER STRAP 7 0C6119 1 BOLT U 5/16-18 X 2-1/4 8 036434 3 BOLT U 5/16-18 X 2.09 9 036449 3 SADDLE 2 INCH 10 022129 8 WASHER LOCK M8-5/16 11 022259 6 NUT HEX 5/16-18 STEEL 12 038750 1 SCREW HHC M6-1.0 X 30 G8.8 13 0F7539 1 PIPE EX INLET MANIFLD SIDE 1.5 14 0E0170 1 EXHAUST BLANKET 800MM 15 0E2844 1 NIPPLE TOE 1.5NPTX5.5 BLK IRON 16 049813 1 NUT HEX M6 X 1.0 G8 YEL CHR 17 022473 6 WASHER FLAT 1/4-M6 ZINC 18 022097 1 WASHER LOCK M6-1/4













GENERAC POWER SYSTEMS STANDARD LIMITED WARRANTY FOR HOME STANDBY/LIGHT COMMERCIAL PRODUCT 45kW AND BELOW
For a period of two (2) years from the date of sale, or start-up by Authorized/Certified Generac Power Systems Dealer, or branch thereof, Generac Power Systems, Inc. will, at its option, repair or replace any part(s) which, upon examination, inspection, and testing by Generac Power Systems or an Authorized/Certified Generac Power Systems Dealer, or branch thereof, is found to be defective under normal use and service, in accordance with the warranty schedule set forth below. Any equipment that the purchaser/owner claims to be defective must be examined by the nearest Authorized/ Certified Generac Power Systems Dealer, or branch thereof. This warranty applies only to Generac Power Systems Generators used in "Standby" applications, as Generac Power Systems, Inc. has defined Standby, provided said generator has been properly installed and inspected on-site by appropriate personnel. Scheduled maintenance, as outlined by the generator owner's manual, is highly recommended. This should be performed by an Authorized/Certified Generac Power Systems Dealer, or branch thereof. This will verify service has been performed on the unit throughout the warranty period.
THIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING: 1. Any unit built/manufactured prior to January 1, 2005. 2. Costs of normal maintenance (i.e. tune-ups, associated part(s), adjustments, loose/leaking clamps, installation and start-up). 3. Any failure caused by contaminated fuels, oils, coolants/antifreeze or lack of proper fuels, oils or coolants/antifreeze. 4. Units sold, rated or used for "Prime Power", "Trailer Mounted" or "Rental Unit" applications as Generac Power Systems have defined Prime Power,
Trailer Mounted or Rental Unit. Contact a Generac Power Systems Distributor for Prime Power, Trailer Mounted or Rental Unit definition and warranty. 5. Units used for prime power in place of existing utility power where utility is present or in place of utility power where utility power service does not
normally exist. 6. Failures caused by any external cause or act of God such as, but not limited to, collision, fire, theft, freezing, vandalism, riot or wars, lightning,
earthquake, windstorm, hail, volcanic eruption, water or flood, tornado, hurricane, terrorist acts or nuclear holocaust. 7. Products that are modified or altered in a manner not authorized by Generac Power Systems in writing. 8. Failures due, but not limited to, normal wear and tear, accident, misuse, abuse, negligence, or improper installation or sizing. 9. Any incidental, consequential or indirect damages caused by defects in materials or workmanship, or any delay in repair or replacement of the
defective part(s). 10. Failure due to misapplication, misrepresentation, or bi-fuel conversion. 11. Telephone, facsimile, cell phone, satellite, internet, or any other communication expenses. 12. Rental equipment used while warranty repairs are being performed (i.e. rental generators, cranes, etc.). 13. Overtime, holiday, or emergency labor. 14. Planes, ferries, railroad, busses, helicopters, snowmobiles, snow-cats, off-road vehicle or any other mode of transportation deemed abnormal. 15. Any and all expenses incurred investigating performance complaints unless defective Generac materials and/or workmanship were the direct
cause of the problem. 16. Starting batteries, fuses, light bulbs, engine fluids, and overnight freight cost for replacement part(s).
THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, SPECIFICALLY, GENERAC POWER SYSTEMS MAKES NO OTHER WARRANTIES AS TO THE MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to purchaser/owner.
GENERAC POWER SYSTEMS ONLY LIABILITY SHALL BE THE REPAIR OR REPLACEMENT OF PART(S) AS STATED ABOVE. IN NO EVENT SHALL GENERAC POWER SYSTEMS BE LIABLE FOR ANY INCIDENTAL, OR CONSEQUENTIAL DAMAGES, EVEN IF SUCH DAMAGES ARE A DIRECT RESULT OF GENERAC POWER SYSTEMS, INC. NEGLIGENCE.
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations may not apply to purchaser/ owner. Purchaser/owner agrees to make no claims against Generac Power Systems, Inc. based on negligence. This warranty gives purchaser/owner specific legal rights. Purchaser/owner also may have other rights that vary from state to state.
Bulletin 0171360SVE / Printed in U.S.A. 7.05
Printed in U.S.A.
Warranty
What the fault codes shown on the display mean and how to clear them.
| Code | Meaning | Fix | |
|---|---|---|---|
| QT100 | QT150. | p.13 |