HE500TIU050 HE500TIU100
IC300TIU101 HE500TIU102 HE500TIU103 HE500TIU110
IC300TIU111 HE500TIU112 HE500TIU113 HE500TIU200
IC300TIU201 HE500TIU202 HE500TIU203 And SmartStack Modules
Operator Station Hardware Manual

PREFACE 06 Apr 2000 PAGE 3
In situations where inattention could cause either personal injury or damage to equipment, a Warning notice is used.
This document is based on information available at the time of its publication. While efforts have been made to be accurate, the information contained herein does not purport to cover all details or variations in hardware or software, nor to provide for every possible contingency in connection with installation, operation, or maintenance. Features may be described herein which are not present in all hardware and software systems. GE Fanuc Automation assumes no obligation of notice to holders of this document with respect to changes subsequently made.
GE Fanuc Automation makes no representations or warranty, expressed, implied, or statutory with respect to, and assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein. No warranties of merchantability or fitness for purpose shall apply.
The following are trademarks of GE Fanuc Automation North America, Inc.
Alarm Master CIMSTAR Helpmate PROMACRO Series Six CIMPLICITY GEnet Logicmaster Series One Series 90 CIMPLICITY 90 – ADS Genius ModelMaster Series Three VuMaster CIMPLICITY Power TRAC Genius PowerTRAC ProLoop Series Five Workmaster
The following are trademarks of Horner Electric, APG, LLC.
Copyright 2000 GE Fanuc Automation North America, Inc.
Cscape SmartStack CsCAN · All Rights Reserved

PAGE 4 06 Apr 2000 PREFACE GFK-1819
Any example programs and program segments in this manual or provided on accompanying diskettes are included solely for illustrative purposes. Due to the many variables and requirements associated with any particular installation, GE Fanuc cannot assume responsibility or liability for actual use based on the examples and diagrams. It is the sole responsibility of the system designer utilising the Operator Station to appropriately design the end system, to appropriately integrate the Operator Station and to make safety provisions for the end equipment as is usual and customary in industrial applications as defined in any codes or standards which apply.
Declares that the products Models: HE500TIU050, HE500TIU100, IC300TIU101, HE500TIU102, HE500TIU110, IC300TIU111, HE500TIU200, IC300TIU201 and HE500TIU202. Conforms to the following EMC standards:
Supplementary Information:
The above conformity only relates to the products in a stand-alone capacity. The products are used as part of a system and are therefore classified as a component. As a component, the products are prohibited by EC regulations to carry a CE Mark for EMC conformity. Static discharge tests only apply to normal operation of the keyboards via the front panel. We would stress that the use of our products within your system, while helping to ensure compliance of your system to the same directives, do not necessarily guarantee that compliance will be achieved. We would also like to point out that the interpretation of the law concerning CE marking and its application to sub-assemblies and components is open to interpretation.



PAGE 6 06 Apr 2000 PREFACE GFK-1819
7.1.2 Display Test 35 7.1.3 Keyboard Test 35 7.1.4 RAM Test 35 7.1.5 Serial Loop-back Tests 35 7.2 Updating the Protocol 36 7.3 Updating the Operating System 36 CHAPTER 8 : NETWORKS 37
8.1 Scope 37 8.2 Controller Area Network (CAN) Overview 37 8.2.1 CAN Features 37 8.3 CsCAN Network Overview 37 8.3.1 CsCAN Network Features 37 8.3.2 CsCAN Network Operation 37 8.4 DeviceNet Overview 38 8.4.1 DeviceNet Features 38 8.4.2 DeviceNet Protocol 39 8.4.3 DeviceNet Operation 39 8.5 CAN Wiring Rules 40 8.6 Profibus 41 8.6.1 Profibus Wiring 41 CHAPTER 9: SMARTSTACK 43
9.1 Scope 43 9.2 Installing and Removing a SmartStack Module 43 9.2.1 Installing SmartStack Modules 43 9.2.2 Removing SmartStack Modules 43

1.1 Scope The Operator Station (TIU050/10X/11X/20X) is an Operator Station (OS) that provides extensive monitoring and control in an extremely small package. The Operator Station “OS” product line offers four distinct categories of products as described in Table 1.1.

PAGE 8 06 Apr 2000 CH. 1: INTRODUCTION GFK-1819
The front panel of the OS has a bright and clear display (LCD with adjustable back lit) and easy-to-use push buttons. On the back panel are communication ports for connection to automation equipment (programmable logic controller, drive, weighing equipment or other equipment) and a PC (IBM or compatible computer). Also located on the back panel or end of the back panel depending on the model, the OS has clearly displayed features such as power input, PC and PLC port, Tx and Rx LEDs. Also, depending on the model, a network port is provided for connection to whichever OS network you have chosen.
The OS supports a variety of protocols. Various protocols can be downloaded through the PC port and stored in the unit’s flash memory. The operating system can also be downloaded through the PC port.
The OS range supports 3 network options. CsCAN (TIUXX1) and Device (TIUXX3) and Profibus with the TIUXX2 range.

* System keys can be programmed to be function keys at specific times in the project. See Function keys in CBREEZE Software Manual MAN0023
** The TIU100/110 is available with two non-standard features: 20mA current loop communication and a real-time clock (RTC). Both can be ordered at the time of purchase. The current loop can be re-fit by the user later. The RTC requires factor re-fit. The TIU050 is only available with the real-time clock option.
*** The TIU20X provides for the display of both text and full graphics and has a Numeric/Function Keypad. It also allows the use of a wide range of SmartStack I/O options.
1.2 Equipment Needed 1. The current version of CBREEZE software install on a PC running Windows 95, Windows 98 or Windows NT. 2. TIU050/10X/11X/20X Interface Unit.

PAGE 10 06 Apr 2000 CH. 1: INTRODUCTION GFK-1819


PAGE 12 06 Apr 2000 CH. 1: INTRODUCTION GFK-1819
1.4 Upgrade Revision Software & Firmware
1.4.1 Scope To avail of any new features that are included in this new release on units that were purchased previous to this release, both software and firmware require updating by the user. Any new unit will be set-up for the latest version released.
1.4.2 Software Upgrade To update the software requires that the user install the new version of software from the installation CD. You may install the new software over any previous version installed. See section 1.4 Software Installation Instructions. To update existing projects simple open the project from the newly installed version of the software. Once the project is saved to disk the update is complete. For backup reasons we recommend that you save the new version of your project in a different location or under a different file name.
1.4.3 Firmware Upgrade The following steps assume that a project or configuration is loaded to the Operator Station and that the user is running the latest version of software.
a) Upload the project/configuration from the unit. b) If a customised character set is loaded to the unit then upload the character set also. c) Choose Automation Device from main menu Configure/Communication Settings. d) From File menu choose Update TIU Operating System. (See Updating Operating System for more
details). e) From File menu choose Update TIU Protocol. If you are updating from firmware version 2.00 or later
then you just have to update to the latest protocol file. However if you are updating from firmware version 1.24 or earlier you most update to a Upgrade.1xx protocol file first, then update to the latest firmware revision. See Note. (See updating protocol for further information). f) Choose Download Character Sets to TIU from File menu. g) Choose Download Project to TIU from File menu.


PAGE 14 06 Apr 2000 CH. 1: INTRODUCTION GFK-1819

2.1 Scope The TIU050 is a 2 line text only display terminal. The hardware description is detailed in this chapter.

2 AB C 3 DE F 4 GH I 5 JKL F2 F3 F4 F5
2.2 TIU050 Button Selection Actions a) PAUSE key selects data for editing OR exits from data editing. b) PAUSE & DOWN keys pressed together, enters sub menu pages. c) PAUSE & UP keys pressed together, exits sub menus to the parent menu pages. d) UP key selects the previous menu page, sub menu page, alarms, and increments data e) DOWN key selects the next menu page, sub menu page, alarms and also decrements data. f) ENTER key sends data to the automation equipment, accepts alarms, and displays accepted alarms. g) ALPHANUMERIC KEYPAD and FUNCTION KEYS can be used to enter data or can be used to
preform some pre-programmed action.
2.3 TIU050 Contrast Adjustment On menu page 1 (after the start-up screen), hold the ENTER key and press the UP or DOWN key to adjust the contrast. The contrast setting is stored and not lost after removing power.
CONTRAST BAND - allows the user to set the lower and upper limits of contrast. Adjust the lower limit using the UP or DOWN key and press Enter when done. Do the same for the upper limit. WARNING: - Changes to the lower or upper limits may allow the user to set the contrast to a setting where the display may appear blank. It is recommended that the factory setting are used (Min 8A, Max FE).

PAGE 16 06 Apr 2000 CH. 2: TIU050 GFK-1819
2.4 TIU050 Ports

2.4.1 TIU050 Configuration of the RS-485 Port

ON
SW 1
Figure 2.3 – Power Connector Powered by +24VDC and Ground.
Figure 2.4 – Configuration Bank
The configuration bank (shown in Figure 2.5) sets the parameters of the RS-485 port as described in Table 2.1.

Table 2.1 – Configuration Bank Switch 1 ON: Pull-up (must be used together with switch 3) OFF: no Pull-up Switch 2 ON: 120Ω termination OFF: no termination Switch 3 ON: Pull-down (must be used together with switch 1) OFF: no Pull-down Switch 4 Reserved for future use NOTE: Switch 1 and 3 must be used together. Either both pull-up and pull-down are used or neither is used.

Pull-up and Pull-down switches are used to increase the signal level on the RS-485 bus. This is useful if there is a long bus and a significant amount of attenuation is anticipated.
Termination resistance of 120Ω must be placed across each end of the RS-485 bus. With switch 2 ON, a 120Ω resistance is placed across the bus. This is only used if the TIU050/100/110 is the last device at either end of the bus.
2.5 TIU050 Dimensions
5.95” [151mm]
3.27” [83 mm] +0.02 -0.00
+0.5 -0.0
UP TO 0.04”[1mm] CORNER RADIUS IS ACCEPTABLE
TOLERANCES ARE +/- 0.01” [0.3mm] UNLESS STATED OTHERWISE
Figure 2.5 – TIU050 Cutout

PAGE 18 06 Apr 2000 CH. 2: TIU050 GFK-1819

3.1 Scope The TIU10X 128 x 64 pixel display, which allows for some graphics and various fonts to be displayed. . The hardware description is detailed in this chapter.

3.2 TIU10X Button Selection Actions a) PAUSE key selects data for editing OR exits from data editing. b) PAUSE & DOWN keys pressed together, enters sub menu pages. c) PAUSE & UP keys pressed together, exits sub menus to the parent menu pages. d) UP key selects the previous menu page, sub menu page, alarms, and increments data e) DOWN key selects the next menu page, sub menu page, alarms and also decrements data. f) ENTER key sends data to the automation equipment, accepts alarms, and displays accepted alarms.
3.3 TIU10X Contrast Adjustment On menu page 1 (after the start-up screen), hold the ENTER key and press the UP or DOWN key to adjust the contrast. The contrast setting is stored and not lost after removing power.
CONTRAST BAND - allows the user to set the lower and upper limits of contrast. Adjust the lower limit using the UP or DOWN key and press Enter when done. Do the same for the upper limit. WARNING: - Changes to the lower or upper limits may allow the user to set the contrast to a setting where the display may appear blank. It is recommended that the factory setting are used (Min 8A, Max FE).

PAGE 20 06 Apr 2000 CH.3: TIU100/101/102/103 GFK-1819
3.4 TIUX Rear View

3.5 TIU100 Ports


Rx
Tx
Tx
Serial Port
PC Port
Figure 3.4 – Automation Equipment Port Receive &
Figure 3.5 – PC Port Receive &
Transmit LEDs The LED’s flash when the PC is communicating with the TIU10X
Transmit LEDs The LED’s flash when the TIU10X
is communicating with the AE.
Figure 3.3 – Automation Equipment Serial Port
3.5.1 TIU10X Configuration of the RS-485 Port The configuration bank (shown in Figure 3.8) sets the parameters of the RS-485 port as described in Table 3.1.
Table 3.1 – Configuration Bank Switch 1 ON: Pull-up (must be used together with switch 3) OFF: no Pull-up Switch 2 ON: 120Ω termination OFF: no termination Switch 3 ON: Pull-down (must be used together with switch 1) OFF: no Pull-down Switch 4 Reserved for future use NOTE: Switch 1 and 3 must be used together. Either both pull-up and pull-down are used or neither is used.
Pull-up and Pull-down switches are used to increase the signal level on the RS-485 bus. This is useful if there is a long bus and a significant amount of attenuation is anticipated.

PAGE 22 06 Apr 2000 CH.3: TIU100/101/102/103 GFK-1819

Figure 3.6 – Power Connector Powered by +24VDC and Ground.
Termination resistance of 120Ω must be placed across each end of the RS-485 bus. With switch 2 ON, a 120Ω resistance is placed across the bus. This should only be used if the TIU050/100/110 is the last device at either end of the bus.
3.6 TIU10X Dimensions

3.27” [83 mm] + 0.02 -0.00
+ 0.5 -0.0
TOLERANCES ARE +/- 0.01” [0.3mm] UNLESS STATED OTHERWISE
Figure 3.8 – TIU10X Cutout

4.1 Scope The TIU11X 128 x 64 pixel display, which allows for some graphics and various fonts to be displayed. The hardware description is detailed in this chapter.

Figure 4.1 – Front View of TIU110
4.2 TIU11X Button Selection Actions a) PAUSE key selects data for editing OR exits from data editing. b) PAUSE & DOWN keys pressed together, enters sub menu pages. c) PAUSE & UP keys pressed together, exits sub menus to the parent menu pages. d) UP key selects the previous menu page, sub menu page, alarms, and increments data e) DOWN key selects the next menu page, sub menu page, alarms and also decrements data. f) ENTER key sends data to the automation equipment, accepts alarms, and displays accepted alarms. g) ALPHANUMERIC KEYPAD and PROGRAMMABLE KEYS can be used to enter data or can be
used to preform some pre-programmed action.
4.3 TIU11X Contrast Adjustment On menu page 1 (after the start-up screen), hold the ENTER key and press the UP or DOWN key to adjust the contrast. The contrast setting is stored and not lost after removing power.
CONTRAST BAND - allows the user to set the lower and upper limits of contrast. Adjust the lower limit using the UP or DOWN key and press Enter when done. Do the same for the upper limit. WARNING: - Changes to the lower or upper limits may allow the user to set the contrast to a setting where the display may appear blank. It is recommended that the factory setting are used (Min 8A, Max FE).

PAGE 24 06 Apr 2000 CH. 4: TIU110/111/112/113 GFK-1819
4.4 TIU11X Rear View

4.5 TIU110 Ports


Rx
Tx
Tx
Serial Port
PC Port
Figure 4.4 – Automation Equipment Port Receive &
Figure 4.5 – PC Port Receive &
Transmit LEDs The LED’s flash when the PC is communicating with the TIU110
Transmit LEDs The LED’s flash when the TIU110
is communicating with the AE.
ON
SW 1
Figure 4.6 – Power Connector Powered by +24VDC and Ground. Figure 4.7 – Configuration Bank

PAGE 26 06 Apr 2000 CH. 4: TIU110/111/112/113 GFK-1819
4.5.1 TIU11X Configuration of the RS-485 Port
The configuration bank (shown in Figure 4.8) sets the parameters of the RS-485 port as described in Table 4.1.
Table 4.1 – Configuration Bank Switch 1 ON: Pull-up (must be used together with switch 3) OFF: no Pull-up Switch 2 ON: 120Ω termination OFF: no termination Switch 3 ON: Pull-down (must be used together with switch 1) OFF: no Pull-down Switch 4 Reserved for future use NOTE: Switch 1 and 3 must be used together. Either both pull-up and pull-down are used or neither is used.
Pull-up and Pull-down switches are used to increase the signal level on the RS-485 bus. This is useful if there is a long bus and a significant amount of attenuation is anticipated.
Termination resistance of 120Ω must be placed across each end of the RS-485 bus. With switch 2 ON, a 120Ω resistance is placed across the bus. This should only be used if the TIU050/100/110 is the last device at either end of the bus.
4.6 TIU11X Dimensions
5.95” [151mm]
3.27” [83 mm] +0.02 -0.00
+0.5 -0.0
UP TO 0.04”[1mm] CORNER RADIUS IS ACCEPTABLE
TOLERANCES ARE +/- 0.01” [0.3mm] UNLESS STATED OTHERWISE
Figure 4.8 – TIU11X Cutout

5.1 Scope The TIU20X is 240 x 128 pixel display which allows for full graphic screen. The hardware description is cover under the following chapter

F 9 F 1 0 F 11 F 1 3 F 1 2
F 1 4 F 1 5 F 1 6 F 1 7 F 1 8
5.2 TIU20X Button Selection Actions a) PAUSE key selects data for editing OR exits from data editing. b) PAUSE & DOWN keys pressed together, enters sub menu pages. c) PAUSE & UP keys pressed together, exits sub menus to the parent menu pages. d) UP key selects the previous menu page, sub menu page, alarms, and increments data e) DOWN key selects the next menu page, sub menu page, alarms and also decrements data. f) ENTER key sends data to the automation equipment, accepts alarms, and displays accepted alarms. g) ALPHANUMERIC KEYPAD can be used to enter data h) PROGRAMMABLE KEYS can be used to preform some pre-programmed action.

PAGE 28 06 Apr 2000 CH. 5: TIU200/201/202/203 GFK-1819
5.3 TIU20X Contrast Adjustment On menu page 1 (after the start-up screen), hold the ENTER key and press the UP or DOWN key to adjust the contrast. The contrast setting is stored and not lost after removing power.
CONTRAST BAND - allows the user to set the lower and upper limits of contrast. Adjust the lower limit using the UP or DOWN key and press Enter when done. Do the same for the upper limit. WARNING: - Changes to the lower or upper limits may allow the user to set the contrast to a setting where the display may appear blank. It is recommended that the factory setting are used (Min 8A, Max FE).
5.4 TIU20X Rear View

5.5 TIU20X Ports


Rx
Tx
Tx
Serial Port
PC Port
Figure 5.4 – Automation Equipment Port Receive &
Figure 5.5 – PC Port Receive &
Transmit LEDs The LED’s flash when the PC is communicating with the TIU20X
Transmit LEDs The LED’s flash when the TIU20X
is communicating with the AE.

ON
SW 1
Figure 5.7 – Configuration Bank
Figure 5.6 – Power Connector Powered by +24VDC and Ground.

PAGE 30 06 Apr 2000 CH. 5: TIU200/201/202/203 GFK-1819
5.5.1 TIU20X Configuration of the RS-485 Port
The configuration bank (shown in Figure 2.23) sets the parameters of the RS-485 port as described in Table 5.1.
Table 5.1 – Configuration Bank Switch 1 ON: Pull-up (must be used together with switch 3) OFF: no Pull-up Switch 2 ON: 120Ω termination OFF: no termination Switch 3 ON: Pull-down (must be used together with switch 1) OFF: no Pull-down Switch 4 Reserved for future use NOTE: Switch 1 and 3 must be used together. Either both pull-up and pull-down are used or neither is used.
Pull-up and Pull-down switches are used to increase the signal level on the RS-485 bus. This is useful if there is a long bus and a significant amount of attenuation is anticipated.
Termination resistance of 120Ω must be placed across each end of the RS-485 bus. With switch 2 ON, a 120Ω resistance is placed across the bus. This should only be used if the TIU050/10X/11X/20X is the last device at either end of the bus.
5.6 TIU20X Dimensions
+0.02
µ > PP@
+0.02 -0.00
+0.5 -0.0
µ > PP@
83 72 µ &RUQHU >5$',86 ,6 $&&(37$%/(PP@
72/(5$1&(6 $5( µ >PP@ 81/(66 67$7(' 27+(5:,6(
Figure 5.8 – TIU20X Cutout

6.1 PC to Operator Station Communications The serial pin connections for transmit (Tx), receive (Rx) and ground are displayed below.

Figure 6.1 – PC Programming Serial Port & Connection Detail
6.2 Automation Equipment (AE) Communications Connections 6.2.1 Recommended Automation Equipment Communication Cables Horner Electric recommends the following cables for automation equipment communication:
Belden No. 8105, 9807 or 9832 – General Purpose Belden No. 8165 – Heavy Noise Environment
6.3 RS-232 Connection

TIU050/101/102/103/111/112/113/20X


PAGE 32 06 Apr 2000 CH. 6: COMMUNICATIONS GFK-1819
6.4 RS-422/485 Four-Wire

(4-wire)
0.1uF Ceramic

Automated Equipment RS422/485 Connections See Note Below
0.1uF Ceramic
(Section of 13-pin · (Section of 8-pin

6.5 RS-485 Two-Wire

(2-w ire)
0.1uF Ceramic

(2-w ire)
0.1uF Ceramic
Figure 6.3 – RS-485 Two-Wire

PAGE 34 06 Apr 2000 CH. 6: COMMUNICATIONS GFK-1819
6.6 Current Loop
The following diagram shows the connection to a device with an active 20mA current loop. The current loop on the TIU100/110 is passive. Either the PLC must provide the 20mA source or an external current source must be supplied.
T+
20m A Loop 10 11
T-
R+
ST -
R-
Figure 6.4 – Current Loop
20mA Loop

7.1 Self-Test Power up the unit with the UP and ENTER keys pressed at the same time. The unit enters a self-test mode. The self-test consists of the following four checks:
7.1.1 Contrast Band This test allows the user to set the lower and upper limits of contrast. Adjust the lower limit using the UP or DOWN key and press Enter when done. Do the same for the upper limit. WARNING: - Changes to the lower or upper limits may allow the user to set the contrast to a setting where the display may appear blank. It is recommended that the factory setting are used (Min 8A, Max FE).
7.1.2 Display Test The display test continuously blinks all pixels on (black) to off. Look for any pixels stuck on or off. Exit this test by pressing and holding any key for approximately two seconds.
7.1.3 Keyboard Test
As each key is pressed, an indication *** appears above that key. In the case of units with a numeric keypad, press the key and a message appears indicating the key press. Check for keys indicating multiple presses or not reporting presses. Exit this test by pressing and holding any key for approximately two seconds.
7.1.4 RAM Test Test either segment 0000 or segment 1000 (on the TIU100/110) of the RAM. The segment 1000 test performs a base 3 repeating test. This test detects shorted address lines and damaged memory bits. The segment 0000 test performs a Read-Modify-Write test on each byte of RAM, detecting damaged memory bits. Exit this test by selecting DONE.
7.1.5 Serial Loop-back Tests Tests the PC port and the Serial Port in each of it’s three modes for serial loop-back. Pre-made plugs are required to link the pins of a particular port. This takes the following form:
Table 7.1 Loop-back Test Plugs Port Tested Product Type of Connector Pins to Short PC (J2) TIU100/110 Pin male D link connector pin 2 to pin 3 RS-232 (J3) TIU100/110 13-pin phoenix connection pin 6 to pin 8 RS-422/485 (J3) TIU100/110 13-pin phoenix connection pin 2 to pin 4 and pin 3 to pin 5. Current Loop TIU100/110 13-pin phoenix connection pin 1 to 9, pin 10 to 11 and pin 12 to 7 PC TIU050/101/102/1 03/112/113/20X Pin male D link connector pin 2 to pin 3
RS-232 TIU050/101/102/1 03/112/113/20X 8-pin phoenix connection Pin 5 to pin 7
RS-422/485 TIU050/101/102/1 03/112/113/20X 8-pin phoenix connection Pin 1 to pin 3, Pin 2 to pin 4 NOTE: current loop in not installed on standard models, as such a standard model will fail the current loop-back test. Current Loop is not an option on the TIU050/20X.
After starting the test, the OK counter begins to count up. Exit this test by selecting DONE.

PAGE 36 06 Apr 2000 CH. 7: GETTING STARTED GFK-1819
7.2 Updating the Protocol When the software is installed the user decides where the main CBREEZE folder resides. During installation the following folders are created: -

In the protocol directory 3 folders are created, TIU0xx, TIU1xx and TIU2xx. The protocol files for the different terminal is loaded into these folders. The protocol files for the TIU050 are loaded into Tiu0xx, the protocol files for the TIU10X are loaded into Tiu10x and the protocol files for the TIU20X are loaded into Tiu20x. The name of the protocol file is broken up into three section, the protocol, the main software revsion and the terminal type that protocol file is for.
Protocol Name _ Software Revision . Terminal Type
Example snp_R4.1xx This is the protocol file for release 4 software for the GE FANUC PLC, for the TIU10X df1_R4.2xx This is the protocol file for release 4 software for Allen Brabley PLC, for the TIU20X
To Update Protocol File 1. Set Terminal Type 2. Set the required Automation Equipment in Communications Settings 3. Select Update TIU Protocol from the File menu. 4. Select the folder of the terminal you have connected to the PC. The correct file will appear for the terminal type selected and the Automation Equipment selected. Select that file and click OK. 5. A status bar appears indicating download progress. 6. After the transfer, the TIU050/10X/11X/20X resets itself. The correct PLC type is displayed on the TIU050/10X/11X/20X. 7. Next, the project loaded runs.
7.3 Updating the Operating System 1. Select Update Operating System from the File menu. 2. Choose the updated file with the “BIN” extension. Click OK. 3. A status bar appears indicating download progress. 4. During the download process, TIU050/10X/11X/20X displays the message “SYSTEM SHUTDOWN”.

8.1 Scope This chapter gives a brief introduction into the networking hardware available on the Operator Station range. The part numbers of the various options are available in the Introduction Chapter of this manual. For information on programming the various network options see GFK-1818, User Manual for the CBREEZE Software.
8.2 Controller Area Network (CAN) Overview The controller area network (or CAN bus) is a serial communications bus that was originally developed in the late 1980’s by a German company (Robert Bosch) for use in the automotive industry. CAN is an ISO (International Standards Organisation) - defined serial communications bus for real-time applications. Established in 1947, the International Standards Organisation (ISO) is a multinational body dedicated to worldwide agreement on international standards. Specifically, CAN is documented in ISO 11898 (for high-speed applications) and ISO 11519 (for lower-speed applications).
8.2.1 CAN Features CAN-based open automation technology successfully competes on the market of distributed automation systems because of the special features of the CAN protocol. The special features are CAN’s producer- consumer-oriented (or peer-to-peer) principle of data transmission and its multi-master capability. The general design of CAN originally specified a high bit rate, high immunity to electrical interference and an ability to detect any errors produced. CAN networks have the following general attributes:
8.3 CsCAN Network Overview The CsCAN Network was first developed in 1993 by Horner Electric. It was developed for use in a project that Horner Electric completed for the United States Post Office. Horner Electric developed its own network, because it needed a network that had a specific set of powerful peer-to-peer and host-to-node capabilities. The CsCAN Network has a “pass-through” feature whereby PC-based programs access other nodes connected to a network by passing the programming command through the serial port to the network port. (For a more detailed description, see below.) Horner Electric found that by developing its own network, it satisfied several important needs. Horner Electric continues CsCAN Network development to satisfy the requirements of today and the requirements of the future.
8.3.1 CsCAN Network Features The CsCAN Network is based on CAN, which has many desirable features such as ruggedness, ease of configuration, etc. With Horner Electric Controllers, data is passed at 125Kbps using a differential pair of wires plus a ground. It is important to note that the data rate is not limited to 125Kbps. The maximum data rate is 1Mbps (limited by the speed of light). The CAN implementation in the CsCAN controller allows up to 64 controllers to be networked with no additional hardware and up to 253 controllers with three CAN repeaters. For the programmer, little knowledge of networking procedures is needed. However for troubleshooting and optimizing, the following information is helpful. Instead of using master/slave or token passing, the hardware self-arbitrates based on the Network ID. Controllers with lower Network ID numbers are given a higher priority than controllers with higher Network ID numbers.
8.3.2 CsCAN Network Operation When a controller needs to send data over the network, it first waits for the network to be idle (currently a maximum of 900uS). If two controllers start broadcasting information on the network at the same time, the

PAGE 38 06 Apr 2000 CH. 8: NETWORKS GFK-1819
"self-arbitration" causes the controller with the greater Network ID number to cease broadcasting without affecting the message-in-progress of the other controller.
In applications with a large number of networked controllers, better results may be achieved by assigning lower Network IDs to controllers that have more critical network data than other controllers. By assigning higher Network IDs to controllers that provide numerous network updates, the controllers are prevented from monopolising the bus time.
Each controller is capable of broadcasting Global Digital Output bits (%QG) and Global Analog Output bits (%AQG), which are periodically broadcasted to the other controllers on the network. The coil representations %QG and %AQG may be used in CBREEZE like any other coil or internal register reference.
All digital global outputs are broadcast to the network each time one of them has a state change. In addition, if a controller has not transmitted its global data for specific time period, the controller's programmable network timer may expire, which in turn results in a global data broadcast. Finally, as part of its power-up initialisation sequence, another controller can explicitly request a controller to broadcast its global data.
8.4 DeviceNet Overview DeviceNet is an open network. The specification and the protocol are open. Vendors are not required to purchase hardware, software or licensing rights to connect devices to a system.
8.4.1 DeviceNet Features DeviceNet is a low-cost communications link to connect industrial devices. It allows the interchangeability of simple devices while making interconnectivity of more complex devices possible. DeviceNet is based on CAN. It is an application layer protocol (ISO layer 7) and is defined in terms of an abstract object model, which represents the available communication services and the external visible behaviour of a DeviceNet node. The DeviceNet Model is application independent. DeviceNet provides the communication services needed by various types of applications. Many of today's lower level industrial control devices must retain their low cost/low resource characteristics even when directly connected to a network. DeviceNet takes this into consideration by defining a specific instance of the DeviceNet Model for communications typically seen in a Master/Slave application. This is referred to as the Predefined Master/Slave Connection Set. Some of the features and functionality of the DeviceNet network are described Table 8.1.
Table 8.1 - DeviceNet Features and Functionality Network Size Up to 64 Nodes Network Length Selectable end-to end network distance varies with speed
125 Kbps 500m (1,640 feet) 250 Kbps 250m (820 feet) 500 Kbps 100m (328 feet) Data Packets 0-8 bytes Bus Topology Linear (trunkline/dropline); power and signal on the same network cable Bus Addressing Peer-to-Peer with Multi-Cast (one-to-many); Multi-Master and Master/Slave special case; polled or change-of-state (exception-based) System Features
Removal and replacement of devices from the network under power
Baud Rate Distance

8.4.2 DeviceNet Protocol Some of the communication protocol features of DeviceNet consist of the following:
8.4.3 DeviceNet Operation The following restrictions are placed on operations when using an OS that is configured as a DeviceNet slave. 1. Currently, communication between the PC and the controller is only possible to the device physically connected to the PCs’ serial port. Project downloads, uploads, monitoring, and configuration cannot currently take place over a DeviceNet network. 2. The HE200CGM40x gateway card can not currently be used with DeviceNet communications. Horner Electric is providing a special Gateway device that is based on the OCS hardware. The Gateway device makes it possible to connect the PC serial port with the DeviceNet network. 3. DeviceNet network nodes are in a range from 0 to 63. The controller is able to observe network responses (polled connections) from any slave to the DeviceNet Master. The first 16-words of these observed responses are made available for mapping on the Network Input Assignments page. These correspond to the available nodes 0 to 63 and registers AQG1 to AQG16. Node 64 is used for a special case. When data is sent to a controller from a DeviceNet Master (via the polled connection) this data is mapped to node 64. Relative addressing is limited to -64 to +64.

PAGE 40 06 Apr 2000 CH. 8: NETWORKS GFK-1819
8.5 CAN Wiring Rules
SH IELD
SH IELD
SH IELD
C N_H
C N_H
C N_H
C N_H
C N_L
C N_L
C N_L
C N_L
V+
V+
V+
V+

SH IE LD
SH IE LD
C N _ L
C N _ H
C N _ L
C N _ H
C N _ L
C N _ H
C N _ L
C N _ H
V +
V +
V +
V +

1. Wire the CAN network in a daisy-chained fashion such that there are exactly two physical end-points on the network. 2. The two nodes at the physical end-points need to have 121 ohm 1% terminating resistors connected across the CN_L and CN_H terminals. 3. Use data conductors (CN_L and CN_H) that are 24 AWG shielded twisted pair for “thin cable” and 22 AWG shielded twisted pair for “thick cable”. They must also have 120-ohm characteristic impedance. In typical industrial environments, use a Belden wire #3084A (“thin”). Use #3082A (“thick”) for environments where noise is a concern. 4. Use power conductors (V- and V+) that are 18 AWG twisted-pair for “thin cable” and 15 AWG twisted- pair for “thick cable”. 5. Connect the V- power conductor to a good earth ground at one place only on the network, preferably physical endpoints. 6. For a section of cable between two nodes, the cable shield is connected to the cable shield input at one end of the cable only. 7. A CAN network (without repeaters) is limited to 64 nodes (with 63 cable segments) with a maximum cable length of 1500 ft. 8. Up to four CAN network segments, which adhere to the above rules, may be connected together using three CAN repeaters. In this manner, a CAN network may be extended to 253 nodes with a total cable distance of 6000 ft.

8.6 Profibus Profibus utilises a Master-Slave type of communication with the TIUXX2 functioning as a slave device. Decentralised Peripherals (Slave) Baud rates of up to 12 MBd can be obtained through Profibus.
Up to 32 devices 9master or slaves) can be connected in one segment without using repeaters, or up to 64 devices can be connected using repeaters.
Master devices are used to determine the data communication on the bus. One master can service several slaves. Several Masters can participate on the bus simultaneously, but only one Master can write outputs to a slave.
The slave devices are peripheral devices. Slaves do not have bus access rights and can only acknowledge received messages or send messages to the master when requested to do so. Any master can read data from the slave devices. All connected Slaves have the same priority.
For further information on the Profibus Network, visit their website at www.profibus.com
8.6.1 Profibus Wiring The TIUXX2 uses a 9 pin D-sub plug connector for its Profibus port. The pin assignment of the plug connector and the wiring are show below.
Rxd/TxD -P 3
V+ 6
D G nd 5
RxD /TxD -N 8
Protective G round
Figure 8.4 Profibus Port Pinout

PAGE 42 06 Apr 2000 CH. 8: NETWORKS GFK-1819
R x D /T xD -N 8
R x D /T xD -N 8
R x D /T xD -N 8
R x D/Tx D -P 3
R x D/Tx D -P 3
R x D/Tx D -P 3
D G N D 5
D G N D 5
V + 6
V + 6
V + 6

Its is necessary to terminate both ends of the network. Both terminations must have power to them to insure proper operation of the network. The following diagram illustrates the correct connection for the termination resistors.

L in e term in atio n 3 90 O h m
A -L in e (3 )
2 20 O h m
B -L in e (8 )
3 90 O h m
Figure 8.6 – Profibus termination resistors

9.1 Scope Horner has now added the SmartStack modules from the OCS Range to the TIU20X range. The SmartStack system is a method of allowing I/O expansion on an HMI. A wide range of modules is available including Digital and Analogue.
9.2 Installing and Removing a SmartStack Module The following section describes how to install and remove a SmartStack Module.
9.2.1 Installing SmartStack Modules
9.2.2 Removing SmartStack Modules

Figure 9.1 – Installing a SmartStack Module in an OCS.

PAGE 44 06 Apr 2000 CH. 9: SMARTSTACK GFK-1819