Dehumidifier SERVICE MANUAL
MODELS: DH300EY5/DH305Y5/DH300MY5
LD40Y5/DH400MY5 DH404EY5/DH400EY5/LD40EY5 DH504ELY5/LD50ELY5 LD65ELY5
CAUTION
- BEFORE SERVICING THE UNIT,
READ THE SAFETY PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORIZED SERVICE.


This Service Manual provides various service information, including the mechanical and electrical parts. This dehumidifier was manufactured and assembled under the strict quality control procedures. The refrigerant is charged at the factory. Be sure to read the safety precaution prior to servicing the unit.
385 (15 5 /32 )
340 (13 3 /8 )
Continuous On.
4Hr. On/Off
2Hr. On/Off
HUMIDITY CONTROL BUCKET
FULL
FAN SPEED TIMER
HUMIDITY SETTING
POWER
ENERGY STAR
540 (21 1/4 )
High · Low

*NOTE:Specifications are subject to minor change without notice for further improvement.

Fan Speed Humidity Control
Fan Speed • The fan control adjusts the fan speed. Set the fan control to HIGH for maximum moisture removal. When the humidity has been reduced and quiet operation is preferred, set the fan control to LOW.
Bucket Full Indicator • This light glows when the water bucket is full and needs to be emptied.
Constantly On.
4hr. On/Off
2hr. On/Off
AUTO RESTART
FAN SPEED TIMER
HUMIDITY
POWER
Power • Operation starts when this button is pressed and stops when the button is pressed again.
Auto Restart • Once power is restored after a power outage, the unit returns to its previous operation setting after a 2 minute delay. The fan runs immediately when the power is restored.

1.6.1 HOW DOES THE DEHUMIDIFIER WORK? Moist, humid air is drawn over a cold refrigerated dehumidifying coil. Moisture in the air condenses on this coil and drains into a bucket (or through the bucket into a hose and drain). Dry, clean air is drawn over the condenser where it is actually heated several degrees and discharged out the rear grill into the room. (See Figure 4) I It is normal for the surrounding air to become

slightly warmer as the dehumidifier operates. This warming effect further reduces the relative humidity of the surrounding air.
1.6.2 LOCATION FOR THE DEHUMIDIFIER Allow at least 12 inches of space on all sides of the unit for good air circulation. (See Figure 5) I The dehumidifier must be operated in an enclosed

area to be most effective. I Close all doors, windows and other outside
openings to the room. Place the dehumidifier in a location that does not restrict air flow into the front grille or out the rear grille.
The operation of dehumidifier in a basement will have little or no effect in drying an adjacent enclosed storage area, such as a closet, unless there is adequate circulation of air in and out of the area.
1.6.3 MICRO SWITCH The micro switch assembly, which is located on the drain pan of inside unit, automatically shuts off the dehumidifier when the bucket is full (note, the Auto Shut Off lights, to indicate bucket must be emptied). The bucket replaces in its place, the unit again turns itself on.
1.6.4 AUTO DEFROST When frost builds up on the cooling coils, the unit will automatically cycle off until the frost disappears. The fan continues to run.
operated in low temperature conditions frost can form in the evaporator coil and the unit will cycle ON/OFF repeatedly. In this case, please check your room temperature conditions and stop the unit.
a temperature of 42°F(6°C).

42% R.H 40%
The humidity control can be set anywhere between Off and Max for normal operation.
If you need more dehumidification, turn the Humidity Control toward Max. If you need less dehumidification, turn the Humidity Control toward Off.
The relative humidity range is from 20% to 80%. (See Figure 6)
Turn the Humidity Control to Off to stop the unit manually.
Max. Off DEAD DIAL
The humidity control can be set 'on' or 35%-70% RH(Relative Humidity) for normal operation. (See Figure 7) If you need drier air, press the Humidity Control button. If you need moister air, press the Humidity Control button.
HUMIDITY
Press the Power button to stop the unit manually.



S: SERVICE PARTS A: ALTERNATE PARTS N: NOT SERVICE PARTS



S: SERVICE PARTS A: ALTERNATE PARTS N: NOT SERVICE PARTS



S: SERVICE PARTS A: ALTERNATE PARTS N: NOT SERVICE PARTS



S: SERVICE PARTS A: ALTERNATE PARTS N: NOT SERVICE PARTS



S: SERVICE PARTS A: ALTERNATE PARTS N: NOT SERVICE PARTS




3.1.3. CABINET AND CONTROL BOX



3.2.4 CAPACITOR 1. Remove the screw that fastens the capacitor. (See Figure 17) 2. Disconnect all leads from the capacitor and then remove it from control box.



3.2.6.1 CONTROL PANEL - Mechanical Type (DH305Y5/DH300MY5/DH400MY5/LD40Y5) 1. Disconnect housing and all leads of the rocker switch, SWITCH ASSEMBLY, ROTARY and PWB(PCB) ASSEMBLY, DISPLAY from PWB(PCB) ASSEMBLY, MAIN (3.1.3) 2. Pull out the knob assembly. 3. Remove the nut which fastens the SWITCH ASSEMBLY, ROTARY. 4. Remove the knob of the rotary switch by pulling it upward. 5. Pull out the rocker switch by pushing the hooks on the both sides of rocker switch. 6. Pull out the PWB(PCB) ASSEMBLY, DISPLAY after turning over both hooks of the display cover.


3.2.6.2 CONTROL PANEL - Electronic Type (DH300EY5/DH404EY5/DH400EY5/LD40EY5/DH504ELY5/


1. Discharge the refrigerant by using a refrigerant Recovery System. 2. After purging the unit completely, unbrace the Discharge and the Suction tube connected compressor carefully. 3. Remove 2 screws that fasten the H/E. 4. Unfasten 2 screws that secure the shroud on the sides and then lift shroud from the drain pan. (See Figure 24) 5. Unfasten 2 screws that secure the drain pan to base pan. (See Figure 25) 6. Pull the drain pan backward then take it up from the base. (See Figure 25)


3.3.1 CONDENSER, EVAPORATOR AND CAPILLARY TUBE 1. Remove the insulation on the Heater/Evaporator (H/E) assembly 2. Pierce the pinch-off tube to discharge the refrigerant, using a refrigerant recovery system. 3. After discharging the refrigerant completely, remove 2 screws between the housing assembly and the H/E. (See Figure 26) 4. Lift the H/E and open the H/E around 45 degree counterclockwise carefully. 5. Unbraze each of interconnecting tubes of the evaporator and condenser carefully. 6. Remove the H/E assembly from the orifice. (See Figure 27) 7. Unbraze the capillary tube at the connections of the condenser and evaporator. (See Figure 28) 8. Remove 4 screws between the condenser and evaporator. (See Figure 28)


Using Rotary Compressor models

1. When replacing a refrigeration component, be sure to discharge the refrigerant system by using a refrigerant recovery system. 2. After discharging the unit completely, remove the desired component, and unbraze the pinch-off tubes. 3. Solder service valves into the pinch-off tube ports, leaving the valves open. 4. Solder the pinch-off tubes with service valves. 5. After doing the above procedures, the valve must be closed and left in place on the system for any subsequent procedures. 6. Evacuate as follows. 1) Connect the vacuum pump, as illustrated in Figure 31A. 2) Start the vacuum pump, slowly open manifold valves A and B two full turns counterclockwise and leave the valves open. The vacuum pump is now pulling through valves A and B to valve C by means of the manifold and entire system.
7. Recharge as follows : 1) Refrigeration cycle systems are charged from the High-side. If the total charge cannot be put in the High-side, the balance will be put in the suction line through the access valve which you installed as the system was opened. 2) Connect the charging cylinder as shown in Figure 31B. With valve C open, discharge the hose at the manifold connection. 3) Open valve A and allow the proper charge to enter the system. Valve B is still closed. 4) If more charge is required, the high-side will not take it. Close valve A. 5) With the unit running, open valve B and add the balance of the charge. a. Do not add the liquid refrigerant to the Low-
side. b. Watch the Low-side gauge; allow pressure to
rise to 30 lbs. c. Turn off valve B and allow pressure to drop. d. Repeat steps B and C until the balance of the
charge is in the system. 6) When satisfied the unit is operating correctly, use the pinch-off tool with the unit still running and clamp on to the pinch-off tube. Using a tube cutter, cut the pinch-off tube about 2 inches from the pinch-off tool. Use sil-fos solder and solder pinch-off tube closed. Turn off the unit, allow it to set for a while, and then test the leakage of the pinch-off connection.
If high vacuum equipment is used, just crack valves A and B for a few minutes, then open slowly with the two full turns counterclockwise. This will keep oil from foaming and being drawn into the vacuum pump.
the vacuum pump. 4) Remove the hose from the vacuum pump and place it on the charging cylinder. See Figure 31B. Open valve C. Discharge the line at the manifold connection. 5) The system is now ready for final charging.

Equipment needed: Vacuum pump, charging cylinder, manifold gauge, brazing equipment. pinch-off tool capable of making a vapor-proof seal, leak detector, tubing cutter, hand tools to remove components, service valve.


CAUSE
REMEDY
Check power supply at outlet. Correct if none.
Poor plug contact at outlet.
Install plug properly or replace it.
Bucket is full.
If Auto Shut Off lights, empty the bucket and replace properly.
Humidity control is at Off position
Turn the humidity control switch toward Max.
Wire disconnected or loose
Connect wire. Refer to wiring diagram for terminal identification. Repair or replace loose terminal.
Capacitor. (Discharge capacitor before testing.)
Test capacitor. Replace if not within ±10% of manufacturer's rating. Replace if shorted, open, or damaged.
Voltage (115V ± 10%)
It must be between 103.5V and 126.5V. If not within limits, call an electrician
Check the wire connections; If loose, repair or replace the terminal. If the wires are disconnected, refer to wiring diagram for identification, and replace the wires. Check the wire connections; If not according to the wiring diagram, correct the connections.
Check for continuity, refer to the wiring diagram for terminal identification. Replace the switch if the circuit is open.
The Defrost Control senses frost build-up on the evaporator coil and automatically shuts off the compressor. The fan continues to run, drawing air across the coil, and melting the frost. When the coil is defrosted, the compressor automatically restarts, and dehumidifying resumes.
Capacitor (Discharge capacitor before servicing.)
Check the capacitor. Replace if not within ±10% of manufacturer's rating. Replace if shorted, open, or damaged.
Check the compressor for open circuit or ground. If open or grounded, replace the compressor.
Check the compressor OLP if externally mounted. Replace if open. (If the compressor temperature is high, remove OLP, cool, and retest.)
Defrost control is defective.
Check defrost control, replace it.
Turn dehumidifier off.
Move dehumidifier to obtain free and unobstructed air circulation.
H/E clogged with dust and dirt
Clean evaporator and/or condenser assembly
Air filter is dirty.
Clean it.
Motor is not operating.
Check Motor, repair or replace it.

CAUSE
REMEDY
If cracked, out of balance, or partially missing, replace it
Loose foreign material inside the housing.
Remove it.
Tube hits frame.
Adjust tubing routine carefully.
Fan blade hits frame
Check Motor Mount. If loose, tighten it.
Internal compressor noise.
Replace compressor.
Tighten them.
Worn bearings of Motor Assembly
If knocking sounds continue when running or loose, replace the motor. If the motor hums or noise appears to be internal while running, replace motor assembly.
The bucket is not installed properly.
The bucket should be properly positioned on the hangers of the drain pan.
Connection may be loose.
Check connection and repair.
Replace bucket.
Water drips when bucket removed for emptying.
Before removing bucket, the unit should be turned off.
Bucket overflows.
Check micro switch and float.
High or low line voltage. (115V ± 10%)
Check line voltage. It must be between 103.5V and 126.5V volts. If intermittent, provide new supply.
Poor air circulation.
Move dehumidifier for free and unobstructed air flow.
Heat Exchange clogged with dust or dirt.
Clean dust or dirt on the Heat Exchange.
If not running, determine the cause. Replace if required.
Short circuit or ground in electrical circuit
Check electrical circuit. Repair.
Unit pressures not equalized
Allow 2 or 3 minutes for pressure to equalize before starting compressor.
Test the capacitor.
Check the terminals. If loose, repair or replace.
Check the system for a restriction.
Check compressor, replace compressor
Check OLP, if externally mounted. Replace if open. (If the compressor temperature is high, remove the OLP, cool, and retest.)


l o r t n o C y ti d i m u H




d e e p S n a F m u H o C y ti d i l o r t n






Common problems, likely causes, and what to do.
| Problem | Possible cause | Remedy | |
|---|---|---|---|
| 1. Dehumidifier does not start. (Both compressor and fan motor do not operate.) | No power | Check power supply at outlet. Correct if none. | p.20 |
| 1. Dehumidifier does not start. (Both compressor and fan motor do not operate.) | Poor plug contact at outlet. | Install plug properly or replace it. | p.20 |
| 1. Dehumidifier does not start. (Both compressor and fan motor do not operate.) | Bucket is full. | If Auto Shut Off lights, empty the bucket and replace properly. | p.20 |
| 1. Dehumidifier does not start. (Both compressor and fan motor do not operate.) | Humidity control is at Off position | Turn the humidity control switch toward Max. | p.20 |
| 1. Dehumidifier does not start. (Both compressor and fan motor do not operate.) | Wire disconnected or loose | Connect wire. Refer to wiring diagram for terminal identification. Repair or replace loose terminal. | p.20 |
| 1. Dehumidifier does not start. (Both compressor and fan motor do not operate.) | Capacitor. (Discharge capacitor before testing.) | Test capacitor. Replace if not within ±10% of manufacturer's rating. Replace if shorted, open, or damaged. | p.20 |
| 2. Motor runs but compressor does not run. | Voltage (115V ± 10%) | It must be between 103.5V and 126.5V. If not within limits, call an electrician | p.20 |
| 2. Motor runs but compressor does not run. | Wiring | Check the wire connections; If loose, repair or replace the terminal. If the wires are disconnected, refer to wiring diagram for identification, and replace the wires. Check the wire connections; If not according to the wiring diagram, correct the connections. | p.20 |
| 2. Motor runs but compressor does not run. | Rotary switch | Check for continuity, refer to the wiring diagram for terminal identification. Replace the switch if the circuit is open. | p.20 |
| 2. Motor runs but compressor does not run. | Defrost control | The Defrost Control senses frost build-up on the evaporator coil and automatically shuts off the compressor. The fan continues to run, drawing air across the coil, and melting the frost. When the coil is defrosted, the compressor automatically restarts, and dehumidifying resumes. | p.20 |
| 2. Motor runs but compressor does not run. | Capacitor (Discharge capacitor before servicing.) | Check the capacitor. Replace if not within ±10% of manufacturer's rating. Replace if shorted, open, or damaged. | p.20 |
| 2. Motor runs but compressor does not run. | Compressor | Check the compressor for open circuit or ground. If open or grounded, replace the compressor. | p.20 |
| 2. Motor runs but compressor does not run. | Overload protector (OLP) | Check the compressor OLP if externally mounted. Replace if open. (If the compressor temperature is high, remove OLP, cool, and retest.) | p.20 |
| 3. Does not defrost control. | Defrost control is defective. | Check defrost control, replace it. | p.20 |
| 4. Insufficient dehumidification | Low relative humidity | Turn dehumidifier off. | p.20 |
| 4. Insufficient dehumidification | Poor air circulation | Move dehumidifier to obtain free and unobstructed air circulation. | p.20 |
| 4. Insufficient dehumidification | H/E clogged with dust and dirt | Clean evaporator and/or condenser assembly | p.20 |
| 4. Insufficient dehumidification | Air filter is dirty. | Clean it. | p.20 |
| 4. Insufficient dehumidification | Motor is not operating. | Check Motor, repair or replace it. | p.20 |