Instruction/ maintenance manual of the product ZQ08B10 Friedrich
Go to page of 28
Room Air Conditioner Ser vice and P ar ts Man ual ZQ08/10;CP08/10/12 (06/05) Z Q 08 B 1 0 Z Q 10 B 1 0 C P 08 A 1 0 C P 10 A 1 0 C P 1 2 A 1 0.
—2— 1. PREF A CE 1.1 SAFETY PRECAUTIONS ................................2 1.2 INSULATION RESISTANCE TEST .................2 1.3 SPECIFICATIONS ...........................................3 1.4 FEATURES...............................................
7, 800 10, 000 7, 800 1 2 , 0 0 0 80 0 1 , 02 0 7 3 0 1 , 1 1 0 7 . 6 9 . 2 6 . 6 1 0 . 2 9 . 7 1 0 . 8 2 6 . 7 ( D B ) * 1 9 . 4 ( W B ) * * 3 5 ( D B ) * 2 3 . 9 ( W B ) ** 3 0 0 g( 1 0 . 6o z ) 5 2 0 g( 1 8 . 3o z ) 5 2 5 g( 1 8 . 5o z ) 5 1 0 g( 1 8 .
— 4 — 1.4 FEA TURES • Designed for COOLING ONLY. • Powerful and whispering cooling. • Slide-in and slide-out chassis for the simple installation and service. • Low air-intake, top cooled-air discharge. 1.5 CONTR OL LOCA TIONS • THERMOSTAT (Fig A) Thermostat will automatically control the temperature of the discharge air.
— 5 — Precaution: The Remote Control unit will not function properly if strong light strikes the sensor window of the air conditioner or if there are obstacles between the Remote Control unit and the air conditioner. POWER BUTTON To turn the air conditioner ON.
— 6 — 2.1 MECHANICAL P AR TS 2.1.1 FRONT GRILLE 1. Open the lnlet grille downward and remove the air filter. 2. Remove the screw which fastens the front grille.(See Figure 1) 3. Pull the front grille from the right side. 4. Remove the front grille.
— 7 — 2.2 AIR HANDLING P AR TS 2.2.1 AIR GUIDE AND TURBO F AN 1. Remove the front grille. (Refer to section 2.1.1) 2. Remove the cabinet. (Refer to section 2.1.2) 3. Remove the control box. (Refer to section 2.1.3) 4. Remove the 4 screws which fasten the brace.
— 8 — 2.2.3 SHROUD 1. Remove the fan. (Refer to section 2.2.2) 2. Remove the shroud. (See Figure 8) 3. Re-install the components by referring to the removal procedure, above. 2.3 ELECTRICAL P AR TS 2.3.1 O VERLO AD PRO TECT OR 1. Remove the cabinet.
— 9 — 2.3.3 CAP A CIT OR 1. Remove the control box. (Refer to section 2.1.3) 2. Open the top cover from the control box. (See Figure 11) 3. Pull out the capacitor from the control box. 4. Disconnect all the leads of capacitor terminals. 5. Re-install the components by referring to the removal procedure, above.
— 10 — 2.3.5 MO T OR 1. Remove the cabinet. (Refer to section 2.1.2) 2. Remove the turbo fan. (Refer to section 2.2.1) 3. Remove the fan. (Refer to section 2.2.2) 4. Remove the 4 screws which fasten the motor to the air guide. (See Figure 13) 5. Remove the motor.
— 11 — — Replacement of the refrigeration cycle. 1. When replacing the refrigeration cycle, be sure to Discharge the refrigerant system using a Freon TM recovery System. If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the Freon TM .
— 12 — Equipment needed: Vacuum pump, Charging cylinder, Manifold gauge, Brazing equipment. Pin ch- off tool capable of making a vapor-proof seal, Leak detector, Tubing cutter, Hand Tools to remove components, Service valve.
DEFROST HEAT COOL INDOOR DESIRED ENERGY SAVER AIR PURYFIER AUTO RESTART FAN FAN DRY 354(13 / ") 29 490(19 / ) 3 8" 29(1 / ) 5 32" 18( / ) 23 32" 126.
— 1 4 — 3 .2 PIPING SYSTEM Figure 17 is a brief description of the important components and their function in what is called the refrigeration system. This will help you to understand the refrigeration cycle and the flow of the refrigerant in the cooling cycle.
— 1 5 — 3 .3 T R OUBLESHO O TING GUIDE In general, possible trouble is classified in two kinds. The one is called Starting Failure which is caused from an electrical defect, and the other is ineffective Air Conditioning caused by a defect in the refrigeration circuit and improper application.
— 16 — Fails to Start Check circuit breaker and fuse. Gas leakage of feeler bulb of thermostat Check control switch. Fan only fails to start. Improper wiring. Defect of fan motor capacitor . Irregular motor resistance ( ). Irregular motor insulation ( ).
— 17 — COMPLAINT CAUSE REMEDY Check voltage at outlet. Correct if none. Check voltage to rotary switch. If none, check power supply cord. Replace cord if circuit is open. Check switch continuity. Refer to wiring diagram for terminal identification.
— 18 — COMPLAINT CAUSE REMEDY Check the position of knob . If not at the coldest setting, advance the knob to this setting and restart unit. Check continuity of the thermostat. Replace thermostat if circuit is open. Check the capacitor. Replace if not within ±10% of manufacturers rating.
MOTOR ASSY CAPACITOR COMPRESSOR OVERLOAD PROTECTOR DC PCB ASSEMBLY AC PCB ASSEMBLY THERMISTOR THERMOSTAT ROTARY SWITCH 1 2 3 4 5 6 7 8 9 1 1 1 1 1 1 1 1 1 S S S S S S S S S LOCATION NO. DESCRIPTION RE- MARKS Q'TY PER SET 4 . SCHEM A TIC DI A GRAM — 19 — MOTO R COMP .
5. EXPLODED VIEW — 2 0— 130910 149980 346811 359012 W48602 349001 352390-2 352390-1 W0CZZ 135500 147581 147582-2 559011 349480 352113 352113 W48602 148000 354210 152302 264110 249950 149410 266003.
— 2 1 — 6. REPL A CEMENT P A R TS LIST R: Service Parts N: Non Service Parts Z Q 08 B 1 0 Z Q 10 B 1 0 C P 08 A 1 0 C P 10 A 1 0 C P 1 2 A 1 0 Loc No FRIEDRICH Description 130410 67302924 BASE ASS.
— 2 2 — Loc No FRIEDRICH Description 130410 67302913 BASE ASSEMBLY,SINGLE 130910 67303711 CABINET ASSEMBLY,SINGLE 135312 67306014 GRILLE ASSEMBLY,FRONT(SINGLE) 135313 67306109 GRILLE,INLET 135500 .
— 2 3 — Loc No FRIEDRICH Description 130410 67302913 BASE ASSEMBLY,SINGLE 130910 67303711 CABINET ASSEMBLY,SINGLE 135312 67306014 GRILLE ASSEMBLY,FRONT(SINGLE) 135313 67306109 GRILLE,INLET 135500 .
— 2 4 — Loc No FRIEDRICH Description 130410 67302923 BASE ASSEMBLY,SINGLE 130910 67303710 CABINET ASSEMBLY,SINGLE 135312 67306013 GRILLE ASSEMBLY,FRONT(SINGLE) 135313 67306108 GRILLE,INLET 135500 .
— 2 5 — Loc No FRIEDRICH Description 130410 67302922 BASE ASSEMBLY,SINGLE 130910 67303710 CABINET ASSEMBLY,SINGLE 135312 67306013 GRILLE ASSEMBLY,FRONT(SINGLE) 135313 67306108 GRILLE,INLET 135500 .
— 2 6 — MEMO.
— 2 7 — MEMO.
Post Office Box 1540 • 4200 N. Pan Am Expressway • San Antonio, Texas 78295-1540 • (210) 357-4400 • FAX (210) 357-4490 FRIEDRICH AIR CONDITIONING CO.
An important point after buying a device Friedrich ZQ08B10 (or even before the purchase) is to read its user manual. We should do this for several simple reasons:
If you have not bought Friedrich ZQ08B10 yet, this is a good time to familiarize yourself with the basic data on the product. First of all view first pages of the manual, you can find above. You should find there the most important technical data Friedrich ZQ08B10 - thus you can check whether the hardware meets your expectations. When delving into next pages of the user manual, Friedrich ZQ08B10 you will learn all the available features of the product, as well as information on its operation. The information that you get Friedrich ZQ08B10 will certainly help you make a decision on the purchase.
If you already are a holder of Friedrich ZQ08B10, but have not read the manual yet, you should do it for the reasons described above. You will learn then if you properly used the available features, and whether you have not made any mistakes, which can shorten the lifetime Friedrich ZQ08B10.
However, one of the most important roles played by the user manual is to help in solving problems with Friedrich ZQ08B10. Almost always you will find there Troubleshooting, which are the most frequently occurring failures and malfunctions of the device Friedrich ZQ08B10 along with tips on how to solve them. Even if you fail to solve the problem, the manual will show you a further procedure – contact to the customer service center or the nearest service center