Thank you for selecting the MONITOUCH V7 series.
For correct set-up of MONITOUCH, you are requested to read through this manual to understand more about the product.
For more information about the V7 series, refer to the following related manuals.
For further details about PLCs (programmable logic controllers), see the manual attached to each PLC.

MONITOUCH
In this manual, you will find various notes categorized under the following levels with the signal words “DANGER,” and “CAUTION.”
DANGER

[Notes on System Design]
- Avoid locations where there is a possibility that water, corrosive gas, flammable gas,
solvents, grinding fluids or cutting oil can come into contact with the unit.
- Avoid high temperature, high humidity, and outside weather conditions, such as wind, rain or
direct sunlight.
- Avoid locations where excessive dust, salt, and metallic particles are present.
- Avoid installing the unit in a location where vibration or physical shock may be transmitted.
[Notes on Cable Connection]
[Notes on Installation] · (To be continued)

[Notes on Maintenance and Operation]
F1
F2
If two or more positions are pressed at the same time, the switch located between the pressed positions activates. Please take note of this.
F4
F5
SWITCH
F6
F7
POWER
Pressing two positions at the same time activates the switch in the center.
[Notes on Disposal]





The V7 series inherits and heightens the features of the V6 series as described below.

1-2 2. Models and Peripheral Equipment
MONITOUCH Models
The model name consists of the following information.
D: 24 VDC specification (in compliance with CE/UL/cUL) None: 100-240 VAC specification
S: TFT color LCD (SVGA) T: TFT color LCD (VGA) C: STN color LCD (VGA)
i: High-performance type None: Standard type

The following models are available.
Model Name Specifications Remarks
V708SD TFT color, 800 × 600 dots, standard, DC power supply Compliant with CE/UL/cUL
V708iSD TFT color, 800 × 600 dots, high-performance, DC power supply
V708CD STN color, 640 × 480 dots, standard, DC power supply Compliant with CE/UL/cUL
V710T TFT color, 640 × 480 dots, standard, AC power supply
V710TD TFT color, 640 × 480 dots, standard, DC power supply Compliant with CE/UL/cUL
V710iT TFT color, 640 × 480 dots, high-performance, AC power supply
V710iTD TFT color, 640 × 480 dots, high-performance, DC power supply
V710S TFT color, 800 × 600 dots, standard, AC power supply
V710SD TFT color, 800 × 600 dots, standard, DC power supply Compliant with CE/UL/cUL
V710iS TFT color, 800 × 600 dots, high-performance, AC power supply
V710iSD TFT color, 800 × 600 dots, high-performance, DC power supply
V712S TFT color, 800 × 600 dots, standard, AC power supply
V712SD TFT color, 800 × 600 dots, standard, DC power supply Compliant with CE/UL/cUL
V712iS TFT color, 800 × 600 dots, high-performance, AC power supply
V712iSD TFT color, 800 × 600 dots, high-performance, DC power supply
The following options are available for using the V7 series more effectively.
Application software for editing display data for the V series. (Windows98/NT4.0/Me/2000/XP compatible) The V7 series is supported with ver. 2.00 and later.

1-4 2. Models and Peripheral Equipment
EU-xx (option unit) (* This option unit can only be mounted on the V7i model.)
Video images can be displayed on V7i directly. WAV files can be played at an external speaker. xx: 01 → RGB input + sound output unit
Screen images displayed on a CRT display can be shown on V7i. WAV files can be played at an external speaker. xx: 02 → RGB output + sound output unit
Screen images displayed on V7i can be shown on a CRT display. WAV files can be played at an external speaker. xx: 03 → Sound output unit
WAV files can be played at an external speaker.

Extension print circuit board to extend the memory for screen data. The capacity of FLASH memory is 8 Mbyte.
Extension print circuit board to back-up the memory for sampling data, V7 internal memory and memo pad. The capacity of an SRAM cassette is 512 kbyte.
Used for connection between the V7 series and a PLC at the RS-422/485 terminal block.
The card recorder creates a backup copy of screen data or works as an external memory storage system for memory manager and data logging functions.
Used with the card recorder when having a backup copy of screen data or saving data on an external medium for memory manager and data logging functions. SRAM 256 k, 512 k, 1 M, 2 M, 4 Mbyte FLASH ROM 256 k, 512 k, 1 M, 2 M, 4 M, 16 Mbyte


Application software for editing data stored on a memory card. (Windows98/NT4.0/Me/2000/XP compatible)
V-MDD (ACPU/QnACPU/FXCPU dual port interface)
Add-on connector with two ports, specifically designed for the connector on the MITSUBISHI’s ACPU/QnACPU/FXCPU programmer. Operability can be improved when directly connecting the V7 series to the ACPU/QnACPU/FXCPU programmer.
Used as an external I/O unit for PLC. It has 16 inputs and 16 outputs.
FG IN0 IN2 IN4 IN6 IN8 IN10 IN12 IN14 COM+ OUT0
OUT1 OUT3 OUT5 OUT7 OUT8 OUT10 OUT12 OUT14 COM2 DC24V
03 → Ethernet/FL-net (OPCN-2), 04 → PROFIBUS-DP, 05 → MELSECNET/10] (communication interface unit) Used for communications with each network. This unit enables connection of multiple V7 series to a single PLC. Since other devices on the same network can be connected, it brings about the reduction in costs of the whole system.

Used for connection between the V7 series and a personal computer, or a personal computer and the card recorder (CREC).
Used for connection between the V7 series and a printer.
Used for connection between the V7 series and a barcode reader.

1-6 2. Models and Peripheral Equipment

Used for Multi-Link 2 connection between the V7 master station and the V7slave station.
Used for connection between the V7 series and a temperature controller or a PLC via PLC2Way.
Used for connection between the V7 series and a PLC via PLC2Way.
This sheet protects the operation panel surface. (5 sheets/set)
12 → V712/V712i] (protective sheet) This anti-glare sheet protects the operation panel surface. (5 sheets/set)
Replacement lithium battery for the V7 series.
10S → V710S/V710iS, 12S → V712S/V712iS] (backlight for replacement)
Replacement backlight parts for the V7 series.

System Composition of V7 (Standard)
The following illustration shows possible system configurations using the V7 series (standard).
During operation (Link communication) V series Panel Editor

Transferring screen data Transferring recipe data Saving sampling data etc.
Transferring screen data Memory manager Data logging function CREC cable
Barcode reader

1-8 3. System Composition
The following illustration shows possible system configurations using the V7i series (high-performance).

Transferring screen data Transferring recipe data Saving sampling data etc.
Transferring screen data Memory manager Data logging function CREC cable
Personal computer (RGB input)
*1 The option unit (EU-xx) is required.
Display (RGB output) · Barcode reader

General Specifications
Model V708 V710 V712
Item DC power supply AC power supply DC power supply AC power supply DC power supply
Rated Voltage 24 VDC 100 - 240 VAC 24 VDC 100 - 240 VAC 24 VDC
Permissible Range of Voltage 24 VDC ±10% 100 - 240 VAC ±10% 24 VDC ±10% 100 - 240 VAC ±10% 24 VDC ±10%
Permissible Momentary Power Failure
Within 1 ms Within 20 ms Within 1 ms Within 20 ms Within 1 ms
V708C 15 W or less
Power Consumption (Maximum Rating)
60 VA or less 30 W or less 60 VA or less 30 W or less
22 W or less
Rush Current 25 A, 0.7 ms
30 A, 1 ms
Insulation Resistance 500 VDC, 10 MΩ or above
Ambient Temperature 0°C to +50°C
Storage Ambient Temperature −10°C to +60°C
Ambient Humidity 85%RH or less (without dew condensation)
Solvent Resistance No cutting oil or organic solvent attached to the unit
Atmosphere No corrosive gas or conductive dust
Vibration Resistance Vibration frequency: 10 to 150 Hz, Acceleration: 9.8 m/s2 (1.0G) Single amplitude: 0.075 mm, X, Y, Z: 3 directions for one hour
Shock Resistance Pulse shape: Sine half wave Peak acceleration: 147 m/s2 (15G), X, Y, Z: 3 directions six times each
Noise Resistance 1500Vp-p (pulse width 1 µs, rising time: 1 ns)
Static Electricity Discharge Resistance
Protection structure: front panel compliant with IP65 (when using gasket) rear case: compliant with IP20 Form: in a body Mounting procedure: inserted in a mounting panel
Cooling System Cooling naturally
Dimensions W × H × D (mm) 233 × 178 × 66.1 303.8 × 231.0 × 72.0 326.4 × 259.6 × 72.0
Panel Cut-out (mm) 220.5 × 165.5 289.0 × 216.2 313.0 × 246.2
+0.5 −0
+0.5 −0
+0.5 +0.5 −0
+0.5 −0
+0.5 −0
Case Color Black (Munsell N2.0)
Material PC/PS resin (Tarflon)

1-10 4. Specifications
Model Item V708C V708S V708iS V710T V710iT V710S V710iS V712S V712iS
Display Device STN color LCD TFT color LCD
Effective Display Area 7.7-inch 8.4-inch 10.4-inch 12.1-inch
Colors 128 colors +16-color blinks
32,768 colors +16-color blinks
Resolution W × H (dots) 640 × 480 800 × 600 640 × 480 800 × 600
Dot Pitch W × H (mm) 0.246 × 0.246 0.213 × 0.213 0.33 × 0.33 0.264 × 0.264 0.3075 × 0.3075
Brightness (cd/m2) 200 350 350 280 350
Angle of Vertical Visibility (°) +40, −30 +35, −55 +45, −55 +35, −45 +40, −45
Angle of Horizontal Visibility (°) ±50 ±50 ±70 ±50 ±55
Backlight Cold cathode rectifier (exchangeable by users)
Backlight Average Life *1
Approx. 40,000 h Approx. 50,000 h
Backlight Auto OFF Function Always ON, random setting
Contrast Adjustment Provided *2 Not provided
Brightness Adjustment Not provided 3 levels *2
POWER Lamp ON when the power is supplied
*1 When the normal temperature is 25°C, and the surface luminance of the display is 50% of the initial setting. *2 Adjustable with function switches
Method Analog resistance film type
Switch Resolution 1024 (W) × 1024 (H)
Mechanical Life One million activations or more
Surface Treatment Hard-coated, anti-glare treatment 5%
Item Specifications

Number of Switches 8
Mechanical Life One million activations or more
Serial Interface for PLC Connection (D-sub 25-pin, female)
RS-232C, RS-422/485 Asynchronous type Data length: 7, 8 bits Parity: even, odd, none Stop bit: 1, 2 bits Baud rate: 4800, 9600, 19200, 38400, 57600, 76800, 115 kbps
Serial Interface 1, 2 for Screen Data Transfer/External Connection (Modular jack, 8-pin)
RS-232C, RS-422/485 (2-wire connection)
CREC, Barcode, V-I/O, Multi-link 2, Temperature control network/PLC2Way, V-link, etc.
Printer Interface for Printer Connection
Compliant with Centronics, half-pitch 36-pin
NEC: PR201 EPSON: ESC/P-J84, ESC/P super function, ESC/P24-J84 CBM292/293 printer *1, HP PCL Level 3 Barcode printer MR400
CF Card Interface Compliant with CompactFlashTM
10BASE-T for Ethernet Connection (Standard with V7i)
Compliant with IEEE802.3
*1 The CBM292/293 printer cannot print screen hard copies.
Battery Specification Coin-type lithium primary cell
Backup Memory SRAM 64 kbyte
Backup Time Period 5 years (ambient temperature at 25°C)
Battery Voltage Drop Detection Provided (internal memory allocated)
Calendar Accuracy Monthly deviation ±90 sec (ambient temperature at 25°C)

1-12 4. Specifications
Drawing Method Exclusive drawing software
Drawing Tool Name of exclusive drawing software: V-SFT (Ver. 2.00 and later) Personal computer: Pentium II 450 MHz or above recommended OS: Windows98/Me/NT Ver. 4.0/2000/XP Capacity of hard disk required: Free space of approx. 460 Mbyte or more (For minimum installation: approx. 105 Mbyte) Display: Resolution 800 × 600 or above recommended
Display Language* Japanese English/ European
Characters 1/4-size 1-byte ANK code Latin 1 ASCII code ASCII code ASCII code
2-byte 16-dot JIS #1, #2 level −−−− Chinese Chinese (simplified)
2-byte 32-dot JIS #1 level −−−−
Character Size 1/4-size: 8 × 8 dots 1-byte: 8 × 16 dots 2-byte: 16 × 16 dots or 32 × 32 dots Enlarge: W: 1 to 8 times, H: 1 to 8 times
Number of Displayable Characters
Resolution 640 × 480 800 × 600
1/4-size 80 columns × 60 lines 100 columns × 75 lines
1-byte 80 columns × 30 lines 100 columns × 37 lines
2-byte 40 columns × 30 lines 50 columns × 37 lines
Display properties: Normal, reverse, blink, bold, shadow Colors: 32,768 colors + blink 16 colors (V708C: 128 colors + blink 16 colors)
Graphics Lines: Line, continuous line, box, parallelogram, polygon Circles: Circle, arc, sector, ellipse, elliptical arc Others: Tile patterns
Graphic Properties Line types: 6 (thin, thick, dot, chain, broken, two-dot chain) Tile patterns: 16 (incl. user-definable 8 patterns) Display properties: Normal, reverse, blink Colors: 32,768 colors + blink 16 colors (V708C: 128 colors + blink 16 colors) Color selection: Foreground, background, boundary (line)
* Refer to the Reference Manual (Operation) for HK fonts.

Screens Max. 1024
Switches 768 per screen
Switch Actions Set, reset, momentary, alternate, to light (Possible to press a function switch and a display switch at the same time)
Lamps Reverse, blink, exchange of graphics 768 per screen
Graphs Pie, bar, panel meter and closed area graph: No limitation within 256 kbyte per screen *1
Numerical Data Display No limitation within 256 kbyte per screen *1
Character Display No limitation within 256 kbyte per screen *1
Message Display Resolution: 640 × 480, max. 80 characters (1-byte) 800 × 600, max. 100 characters (1-byte) No limitation within 256 kbyte per screen *1
Sampling Sampling display of buffer data (Constant sample, bit synchronize, bit sample, relay sample, alarm function)
Graphic Library Max. 1024
Multi-Overlaps Max. 1024
Data Blocks Max. 2560
Messages Max. 6144 lines
Patterns Max. 1024
Macro Blocks Max. 1024
Page Blocks Max. 1024
Direct Blocks Max. 1024
Screen Blocks Max. 1024
Data Sheets Max. 1024
Screen Library Max. 1024
Animation (Frames) Max. 1023
Temperature Control Network/ PLC2Way Table
Max. 32
Hard Copy Screen hard copy function: provided
Auto OFF Function Always ON, random setting
Self-diagnostic Function Switch self-test function Communication parameter setting check function Communication check function
*1 The number of setting memory locations is limited to 1024 per screen. *2 Layer: 4 per screen (base + 3 overlaps)
Item Specifications · Data Setting

1-14 5. Dimensions and Panel Cut-out
V708/V708i External View and Dimensions

See operating or maintenance instruction for type of battery to be used.


See operating or maintenance instruction for type of battery to be used.

1-16 5. Dimensions and Panel Cut-out

See operating or maintenance instruction for type of battery to be used.

V708/V708i

See operating or maintenance instruction for type of battery to be used.

See operating or maintenance instruction for type of battery to be used.

1-18 6. Names and Functions of Components
CN5
MEMORY
See operating or maintenance instruction for type of battery to be used.
Battery replacement.
PRINTER MJ2 MJ1 CN1 LAN
100-240VAC L N
SYSTEM
F1 F2 F3 F4 F5 F6 F7
POWER
5 6 7 8 9
11 12 13


1-20 7. Mounting Procedure
Mounting Procedure



* When the V7 unit is attached to the mounting panel, the fixtures and frame grounds (FG) are connected. To prevent static electricity, be sure to connect the mounting panel to the frame ground.
Install the unit within the angle of 15° to 135° degrees as shown on the right.

- V708/V708i - V710/V710i/V712/V712i


See operating or maintenance instruction for type of battery to be used. Battery replacement.

Terminal Screw Model Screw Size Tightening Torque Crimp-style Terminal (Unit: mm)

1-22 8. Power Supply Cable Connection
- For V708/V708i:
- For V710/V710i/V712/V712i:
Attach the terminal cover (supplied) to the terminal block.
When closing the terminal cover, hold one end of the cover as shown below.
Press either end.
1.25 mm2 Twist the cables.
V7 series unit Other equipment
* When the V7 unit is attached to the mounting panel, the fixtures and frame grounds (FG) are connected. To detach the FG terminal from the ground, attach the insulating sheet to the fixtures and the mounting panel for insulation.


See operating or maintenance instruction for type of battery to be used.
See operating or maintenance instruction for type of battery to be used.
* The battery status is output to the internal memory $s167 of the V7 series. If the battery voltage drops before five years has elapsed, replace the battery immediately.
Battery replacement.
Enter a date five years from now.

1-24 9. Coin-type Lithium Battery
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
0
Reserved for memory cassette information (setting: 0)
Reserved for memory cassette information (setting: 0)
Main Menu V 7 1 0 i T D
FONT VER.1.300 / 1.000 / 1.000 ENGLISH
I/F DRV VER.1.300 MELSEC AnA/N/U
Editor:MJ1
Card Menu I/O Test
Battery Replacement
Safety Instructions on Handling the Battery
Lithium batteries contain combustible material such as lithium or organic solvent. Mishandling may cause heat, explosion or ignition resulting in fire or injury. To prevent accidents, pay attention to the following cautions when handling the lithium battery.

Replacement batteries are available from Hakko Electronics.
See operating or maintenance
instruction for type of battery
to be used.
Battery replacement.
“b” side Battery holder

1-26 10. DIP Switch Setting
DIP Switch (DIPSW) Setting
Set the terminating resistance for RS-422/485 connection with the DIP switch. When setting the DIP switch, turn the power off.
Side View Rear View
CN5
MEMORY
CF
100-240VAC L N LAN CN1 MJ1 MJ2 PRINTER
ON
1 2 3 4 5 6 7 8
MJ2 (modular jack 2) terminating resistance CN1 RD terminating resistance at pins 24 and 25 MJ1 (modular jack 1) terminating resistance Not used
* Set DIPSW2 to 5 (not used) to the OFF position.
- Master station for multi-link 2 connection - Temperature controller network/PLC2Way connection via RS-485 - Connection with the card recorder CREC (optional) - Connection with the serial extension I/O V-I/O (optional) - Connection to the V7 unit at the termination of V-link connection via RS-485
DIP switch · CF auto load

A screen data file saved on a CF card can be auto-loaded as described below.

1-28 11. Serial Connector (CN1)
Serial Connector for PLC Connection
Bottom View Bottom View
CN1 (D-sub 25-pin, female) Pin No. Signal Name Contents
1 FG Frame ground
2 SD RS-232C send data
3 RD RS-232C receive data
4 RS RS-232C request to send
5 CS RS-232C clear to send
7 SG Signal ground
9 +5V Use prohibited
10 0V Use prohibited
12 +SD RS-422 send data (+)
13 −SD RS-422 send data (−)
14 +RS RS-422 RS send data (+)
17 −RS RS-422 RS send data (−)
18 −CS RS-422 CS receive data (−)
19 +CS RS-422 CS receive data (+)
24 +RD RS-422 receive data (+)
25 −RD RS-422 receive data (−)

Modular Jack 1 (MJ1)/2 (MJ2)
Bottom View Bottom View
MJ1/2 Pin No. Signal Name Contents
1 +SD/RD RS-485 + data
2 −SD/RD RS-485 − data
3 +5V Externally supplied +5 V
MAX 150 mA 4 +5V
Signal ground 6 SG
7 RD RS-232C receive data
8 SD RS-232C send data
12345678
![Page 47 of the Epson Endeavor V7 user manual — [V-I/O] *4 [V-I/O] *4](/cdn/reader/b8/b8449522b609f1ec53cca0ce6668e2b08023edbd18c283275a97f522d49d7dd5/images/page-47.webp?w=400)
1-30 12. Modular Jack (MJ1/MJ2)
Modular Jack 1 Modular Jack 2
[Editor Port]*1 [Not used]
[Memory Card]*2 [Memory Card]*2
[Barcode]*3 [Barcode]*3
[Multi-Link]*5 [Multi-Link]*5
[Temp. CTRL/PLC2Way]*6 [Temp. CTRL/PLC2Way]*6
[V-Link]*7 [V-Link]*7
[Touch Switch]*8 [Touch Switch]*8
[Ladder Tool]*9 [Ladder Tool]*9
[Modbus Slave]*10 [Modbus Slave]*10
[Printer (Serial Port)]*11 [Serial Printer (Serial Port)]*11
*1 Refer to the next section “Transferring Screen Data.” *2 Select this option when connecting the card recorder (CREC). *3 Refer to the next section “Barcode Reader Connection.” *4 Select this option when connecting the serial extension I/O (V-I/O). *5 Select this open when “Multi-link 2” is selected for [Connection] and “1” is set for [Local Port] on the [Comm. Parameter] dialog. *6 Select this option when connecting the temperature controller network or PLC2Way. *7 Select this option for V-Link connection. *8 Refer to “EU-01 (RGB input + sound output unit).” *9 Select [Ladder Tool] when using the ladder transfer function with MITSUBISHI’s QnHCPU port (Q mode) selected for the PLC type. *10 Select this option for Modbus slave connection. *11 Select this option when connecting the printer with serial interface. Refer to page 1-37.

O: Usable at the same time, : Usable from system program Ver. 1.010, ×: Not usable at the same time
MJ1 MJ2
Multi- Link 2 CREC Barcode V-I/O
Temp. CTRL/PLC
2Way V-Link Touch Switch
Multi- Link 2 O × O
CREC O
Barcode O
V-I/O
Temp. CTRL/PLC 2Way O
V-Link O
Touch Switch O
Ladder Tool × O
Printer (Serial Port) O
can be used at the same time.
O: Usable at the same time, ×: Not usable at the same time
Temp. CTRL/PL
2 CREC Barcode V-I/O
CU-00 OPCN-1 × O
CU-01 T-LINK × O
CU-02 CC-Link × O
CU-03 Ethernet (FL-net) *1 O ×
CU-04 PROFIBUS-DP × O
CU-05 MELSECNET/10 × O
*1 This is not possible when the V7 series and the PLC are connected via Ethernet.

1-32 12. Modular Jack (MJ1/MJ2)
install a jumper to RTS and CTS. Otherwise the barcode reader may not work correctly. - The external power supply (+5 V) is max. 150 mA. (Refer to page 1-29.)
D-sub 9-pin (female) Barcode reader
1 2 3 4 5 6 7 8 9
* Install a jumper between CTS and RTS.
SG

13. 10BASE-T (LAN)
Hardware Specifications
The connector for 10BASE-T is provided as standard on V7i (high-performance). To connect Ethernet with V7 (standard), use the communication unit “CU-03.” If CU-03 is attached to V7i, it has priority over the built-in 10BASE-T; 10BASE-T cannot be used.
Side View Bottom View
LAN Pin No. Signal Name Contents
1 TX+ Ethernet send signal (+)
2 TX- Ethernet send signal (−)
3 RX+ Ethernet receive signal (+)
4 NC Not used
5 NC Not used
6 RX− Ethernet receive signal (−)
7 NC Not used
8 NC Not used
12345678

Notes on Wiring
UTP cable Straight or cross cable (For more information, refer the HUB specifications.)
HUB
Node Distance between the node and the HUB: 100 m maximum Maximum network nodes: 100 sets
Straight cable (with HUB) Cross cable (without HUB)
* Unshielded twist-pair cable * Unshielded twist-pair cable
Use the following recommended cable.

Recommended CF Card
CF cards in compliance with CompactFlashTM can be used. The following card is recommended.

Side View Side View


When the card is inserted, the eject button pops out.
Card backside

1-36 14. CF Card (CF)
1. Do not insert or remove the CF card during access. Doing so may destroy data on the CF card. The CF card can be inserted or removed safely when the Main Menu screen is displayed. However, if the [Card Menu] switch is pressed on the Main Menu screen and the CF card operation screen is displayed, it is not possible to insert or remove the CF card. Before mounting or removing the CF card, be sure to check that the CF card is not being accessed.

When the V7 series is connected to a printer, a screen hard copy, data sheet or sampling data can be printed. To connect a printer with parallel interface, insert the cable into the printer connector (PRINTER); to connect a printer with serial interface, insert the cable into a modular jack (MJ1/MJ2).
Bottom View Bottom View
PRINTER (half-pitch 20-pin) Pin No. Signal Name Contents
2 PD0 Data 0
3 PD1 Data 1
4 PD2 Data 2
5 PD3 Data 3
6 PD4 Data 4
7 PD5 Data 5
8 PD6 Data 6
9 PD7 Data 7
12 GND
13 SELECT
14 INTP# INP PROME#
15 PFAT# FAULT#
16 GND
17 GND
18 P+5V PRN+5
19 GND
20 GND
1 STB# Strobe · 11 BUSY# Busy

1-38 15. Printer Connection (PRINTER)
SYSTEM
F1
F2
F3
F4
F5
F6
F7
POWER
Half-pitch, 20-pin Centronics, 36-pin
Control code system:
Barcode printers: (It is not possible to print a screen hard copy, data sheet or sampling data.)
V7 series Printer


Initial Screen 1. Main Menu Screen 2. I/O Test 3. Card Menu Screen 4. Ethernet 5. SRAM/Clock 6. Extension Program Information 7. Extended Function Setting
Types [SYSTEM] Switch



Initial Screen
When the power of MONITOUCH is turned on for the first time, the Main Menu screen shown below on the left is displayed.
Initial screen displayed when power is
Main Menu screen after transferring screen data
turned on for the first time

Main Menu V 7 1 0 i T D
2002-4 -1 07:23:30
I/F DRV VER.1.240 MELSEC QnH Q CPU Port
Stop 1.00 sec 3
Retry :
Multi-Link2 Own Stat. No. : 1
Multi-Link2 Own Stat. No. :
1 2 10 115200
Connection :
19200 8 1 Odd 20msec
Stop Bit :
Ethernet Information Trans.Speed :
PORT : 10000 MAC : 050FF000035
Stat. No. :
Editor:MJ1
There are four methods for transferring screen data for the first time.

2-2 1. Operation of V7 Main Menu

Main Menu V 7 1 0 i T D
Main Menu screen

Font data versions, country/local/font V7 series model
Main Menu V 7 1 0 i T D
2002-4 -1 07:23:30
I/F DRV VER.1.240 MELSEC QnH Q CPU Port
PLC I/F driver version and model
Multi-link 2 or multi-link setting * Displayed when [Multi Link] or [Multi Link 2] is selected for [Connection] on the [Comm. Parameter] dialog
Multi-Link2 Own Stat. No. :
Connection :
19200 8 1 Odd 20msec
1 2 10 115200
Stop Bit :
Ethernet Information Trans.Speed :
Port name used for data transfer
Stat. No. :
Editor:MJ1
PLC model and file comment set for the screen data file
Ethernet setting * Displayed for V7i or communication interface unit (CU-03)
Initializes SRAM and adjusts calendar data. (See page 2-27.)
Indicates the driver setting and parameter setting for temperature controller/PLC2Way communication, ladder transfer function, Modbus slave communication, etc. (See page 2-28.)
Sets the IP address. (See page 2-23.)
Appears when the option unit EU-01 is provided. For more information, refer to the instruction manual for the EU-01 option unit.
Transfers screen data between the CF card and the V7 series. (See page 2-11.)
Checks the V7 interfaces and performs a touch switch test. (See page 2-4.)

2-4 1. Operation of V7 Main Menu
When the [I/O Test] switch on the Main Menu screen is pressed, the following “I/O Test” screen appears. This screen is used to check that there is no problem with the V7 interfaces and touch switch operation.
Moves back to the Main Menu screen. (See page 2-2.)
Performs a printer interface check. (See page 2-8.) Moves to the “Touch Switch” screen. (See page 2-9.)

Performs a CN1/MJ1/MJ2 interface check. (See page 2-5.)
Performs a function switch test. (See page 2-8.)
*1 When the serial extension I/O (V-I/O) is connected, use this button to check that the V-I/O works correctly. The [Ext. I/O Check] switch appears only when [V-I/O] is selected for a modular jack on the V-SFT editor.
*1

This is a signal test for communications through the CN1, MJ1 or MJ2 connector. Perform this test if the communication is not successful when transferring screen data through MJ1, connecting the PLC using CN1, or selecting multi-link 2, temperature controller/PLC2Way or PLC for MJ1/2, or connecting the card recorder or serial extension I/O.
CN1: RS-232C Signal Test
Turn the [CN1] and [RS232C] switches on.
MJ1 RS485
MJ2

* If the [NG] lamp lights up, consult your local distributor.

Communication Port

2-6 1. Operation of V7 Main Menu
Turn the [CN1] and [RS485] switches on.
MJ1 RS485
MJ2

* If the [NG] lamp lights up, consult your local distributor.

Communication Port

Turn the [MJ1] (or [MJ2]) and [RS232C] switches on.
MJ1 RS485
MJ2
MONITOUCH Operations
CN1 MJ1/2
CTS RTS
NG OK
NG OK
* If the [NG] lamp lights up, consult your local distributor.
If you would like to perform MJ1/2 RS-485 signal test, consult your local distributor.
Communication Port · Self-Loop Test · Self-Loop Test

2-8 1. Operation of V7 Main Menu
Check that the V7 series transmits the signals to the printer correctly.

!"#$%&@ 0123456789 ABCDEFGHIJKLMNO !"#$%&@ 0123456789 ABCDEFGHIJKLMNO !"#$%&@ 0123456789 ABCDEFGHIJKLMNO !"#$%&@ 0123456789 ABCDEFGHIJKLMNO !"#$%&@ 0123456789 ABCDEFGHIJKLMNO !"#$%&@ 0123456789 ABCDEFGHIJKLMNO !"#$%&@ 0123456789 ABCDEFGHIJKLMNO
Check operations of eight switches provided vertically on the right side of the V7 panel. Press the switch, and check that the lamp on the screen lights up while the switch is held down.


If a touch switch does not activate at all or if an operation is performed without pressing any touch switch, check that the touch switches on the V7 panel are working properly.



2-10 1. Operation of V7 Main Menu
If a position different from the pressed position turns white on the touch switch test screen, follow the steps described below to adjust the touch switch position.


F2
Touch the flickering corner. The last position you touched is the setting value.
Touch the flickering corner. The last position you touched is the setting value.
Touch the flickering corner. The last position you touched is the setting value.
Touch the flickering corner. The last position you touched is the setting value.

When the [Card Menu] switch on the Main Menu screen is pressed, the following “Card Menu” screen appears. This screen is used to transfer screen data between the V7 series and a CF card or a memory card.
Moves back to the Main Menu screen or the initial screen.
SRAM

2-12 1. Operation of V7 Main Menu
When the [CREC Menu] switch on the “Card Menu” screen is pressed, the following “CREC Menu” screen appears. This screen is used to transfer screen data between the V7 series and a memory card. The procedure for transferring data is described below.
Screen Data Font Data
I/F Driver Sys. Program


Sys. Program Version Font Date Version I/F Driver Version Screen PLC Type Screen Comment
: : -.--- : : -.--- / -.--- / -.--- : YOKOGAWA FA : 1.250 : YOKOGAWAFA-M3 :
Data selection Transfer selection

Sys. Program Version Font Date Version I/F Driver Version Screen PLC Type Screen Comment
: : -.--- : : -.--- / -.--- / -.--- : YOKOGAWA FA : 1.250 : YOKOGAWAFA-M3 :
Sys. Program Version Font Date Version I/F Driver Version Screen PLC Type Screen Comment
: : -.--- : : -.--- / -.--- / -.--- : YOKOGAWA FA : 1.250 : YOKOGAWAFA-M3 :
Modular Jack

2-14 1. Operation of V7 Main Menu

Sys. Program Version Font Date Version I/F Driver Version Screen PLC Type Screen Comment
: : -.--- : : -.--- / -.--- / -.--- : YOKOGAWA FA : 1.250 : YOKOGAWAFA-M3 :
Sys. Program Version Font Date Version I/F Driver Version Screen PLC Type Screen Comment
: : -.--- : : -.--- / -.--- / -.--- : YOKOGAWA FA : 1.250 : YOKOGAWAFA-M3 :
Sys. Program Version Font Date Version I/F Driver Version Screen PLC Type Screen Comment
: : -.--- : : -.--- / -.--- / -.--- : YOKOGAWA FA : 1.250 : YOKOGAWAFA-M3 :
Press the [OK] switch.

Folders in the CF card are configured as shown below.
Folder Name Folder Name File Name
AAAAAAAA
DSP
DSP0000.BIN
BBBBBBBB
CARD
MCMHEAD.BIN MCMxxxx.BIN
SRM0000.BIN
FFFFFFFF
MEMO
MEMxxxx.BIN
RECxxxx.CSV
*1 These are access folders set by the V-SFT editor. Any folder name within eight 1-byte characters can be given. *2 These folders are automatically created when access folders are created. The folder name cannot be changed. *3 The folder name for screen data auto uploading cannot be changed.
SMPxxxx.BIN SMPxxxx.CSV HDxxxx.JPG HDxxxx.BIN
BITMAP
BMPxxxx.BIN
xxxx.JPG JPxxxx.JPG
VDxxxx.JPG
WAxxxx.WAV
xxxx.FTD
xxxxxxxx.SHT xxxxxxxx.HTML xxxxxxxx.TXT
DSPDEF DSP
DSPDEF.BIN
Same as access folders
Folder Name Contents Folder Name Contents
BITMAP Saves pattern data (bitmap data) to reduce the screen data capacity.
RECIPE Reads and writes recipe data.
CARD Write recipe data from the V7 series using the V6-compatible memory manager function.
SAMPLE Saves history data of the data logging function.
DSP Reads and writes screen data. SNAP Saves video snap images.
FONT Saves Gothic fonts or language data to reduce the screen data capacity.
SRAM Saves backup data of SRAM.
HDCOPY Writes hard copy images in the JPEG file format from the V7 series (for V708C: BIN file).
WAV Saves WAV files for sound output to reduce the screen data capacity.
JPEG Saves JPEG files for display on the screen (except for V708C).
WEBSERV Saves files to be accessed from the Web browser.
MEMO Saves memo pad data drawn with the V7 series.
DSPDEF (screen data auto upload folder)
DSP Automatically reads screen data in this folder when the CF card is inserted in the V7 unit after the DIP switch is set.
(Other folders are the same as access folders.)
![Page 73 of the Epson Endeavor V7 user manual — When [Display <-- Card] is Selected:](/cdn/reader/b8/b8449522b609f1ec53cca0ce6668e2b08023edbd18c283275a97f522d49d7dd5/images/page-73.webp?w=400)
2-16 1. Operation of V7 Main Menu
The procedure of transferring data between the V7 series and a CF card is described below.
* Do not remove or insert the CF card in the later steps.

Data selection Transfer selection
Transfer screen data from the computer to the CF card.
Flashes during communication with the CF card.
![Epson Endeavor V7 — When [Display <-- Card] is Selected: diagram (page 73)](/cdn/reader/b8/b8449522b609f1ec53cca0ce6668e2b08023edbd18c283275a97f522d49d7dd5/images/fig-73-2.webp)
Indicates the name of the currently selected folder. The access folder that is set for screen data defaults. If there is no screen data, “DAT0000” defaults.
Sys. Program Version Font Date Version I/F Driver Version Screen PLC Type Screen Comment
Indicates the free space in the CF card.
: ENGLISH : 1.300 / 1.010 / 1.000 : GENERAL : 1.240 : GENERAL :
Used for checking or renaming folder names.
Starts transferring data [Display
Moves back to the previous screen.


Moves the cursor.
Indicates the details of the folder. Determines the folder selection.

Moves the cursor.
Scrolls with the [↑] / [↓] switch.
Moves back to the “Select Folder” screen.

2-18 1. Operation of V7 Main Menu

Sys. Program Version Font Date Version I/F Driver Version Screen PLC Type Screen Comment
: V710/V712 : 1.010 : ENGLISH : 1.300 / 1.010 / 1.000 : GENERAL : 1.240 : GENERAL :
Sys. Program Version Font Date Version I/F Driver Version Screen PLC Type Screen Comment
: V710/V712 : 1.010 : ENGLISH : 1.300 / 1.010 / 1.000 : GENERAL : 1.240 : GENERAL :
Select the desired data, and press the [Select Data] switch.

Access CF Card File Infomation Access Folder Name: AAAAAAAA
Sys. Program Version Font Date Version I/F Driver Version Screen PLC Type Screen Comment
: V710/V712 : 1.010 : ENGLISH : 1.300 / 1.010 / 1.000 : GENERAL : 1.240 : GENERAL :
Sys. Program Version Font Date Version I/F Driver Version Screen PLC Type Screen Comment
: V710/V712 : 1.010 : ENGLISH : 1.300 / 1.010 / 1.000 : GENERAL : 1.240 : GENERAL :
To cancel the [Data Selection] window, press the [Return] switch.
Work normally finished.
Press the [OK] switch. The “Card Menu” screen is displayed. If any other message is displayed, refer to page 2-23.

Flashes during communication with the CF card.
Indicates the name of the currently selected folder.
CF Card File Infomation Folder Name: AAAAAAAA
Indicates the free space in the CF card.
Sys. Program Version Font Date Version I/F Driver Version Screen PLC Type Screen Comment
: V710/V712 : 1.010 : ENGLISH : 1.300 / 1.010 / 1.000 : GENERAL : 1.240 : GENERAL :
Starts transferring data [Display --> Card].
Moves back to the previous screen.
Indicates the information of the currently selected folder. If there is no screen data, this field becomes blank.
2. Check the folder name and CF card file information, and press the [Start] switch. * When the access folder name of screen data is the same as that in the CF card, the CF card file information is indicated on the screen, and data in the V7 series overwrites the CF card data. Note that the CF card data is lost when data in the V7 series overwrites. When the CF card file information is blank, a new file “DSP0000.BIN” is created in the DSP folder.
Work normally finished.
Press the [OK] switch. The CF card file information shows data that has been transferred. If any other message is displayed, refer to page 2-23.

2-20 1. Operation of V7 Main Menu
Flashes during communication with the CF card.
Indicates the name of the currently selected folder.
CF Card File Infomation Folder Name: AAAAAAAA
Indicates the free space in the CF card.
Sys. Program Version Font Date Version I/F Driver Version Screen PLC Type Screen Comment
: V710/V712 : 1.010 : ENGLISH : 1.300 / 1.010 / 1.000 : GENERAL : 1.240 : GENERAL :
Starts transferring data [Display Card].
Moves back to the previous screen.
Indicates the information of the currently selected folder. If there is no screen data, this field becomes blank.
Work normally finished.
Press the [OK] switch. If any other message is displayed, refer to page 2-23.

In this section, the procedure for saving backup copies of the SRAM memory or V7EM-S (SRAM cassette) for battery replacement is explained.
Data selection Transfer selection

Flashes during communication with the CF card.
Indicates the name of the currently selected file.

Indicates the name of the currently selected folder.
Indicates the free space in the CF card.
Starts transferring data [Display --> Card].
Moves back to the previous screen.
Shows [Display Card] when [Display Card] is selected.

2-22 1. Operation of V7 Main Menu
Flashes during communication with the CF card.
Indicates the name of the currently selected file.
Indicates the name of the currently selected folder.
CF Card File Infomation Access Folder Name:CCCCCCCC
12:51:26 Indicates the free space in the CF card.
Used for checking or renaming folder names. Starts transferring data [Display
Moves back to the previous screen.
Work normally finished.
Press the [OK] switch. If any other message is displayed, refer to the next page.

If an error occurs during data transfer, the message window shown on the right is displayed.
MONITOUCH Operations
The kinds and the contents of the messages are shown below. The same messages are used for the memory card and CF card. When using the CF card, the “memory card” in the explanation should read as the “CF card.”
Work normally finished. The specified operation has been concluded normally.
CREC not connecting CREC is not connecting when selecting a modular jack.
CREC Communication Error A communication error occurred between V7 and CREC when selecting a modular jack.
Memory-Card not setting A memory card is not inserted.
Memory-Card Capacity over Cannot write the data into a memory card because the data size in V7 is larger than the capacity of a memory card.
Write Protect: ON Cannot write data into a memory card because the write protect switch in a memory card is ON.
Writing Error occurred. The error occurred while writing data into a memory card.
Selected data does not exist. The data in the reading target does not exist.
V7 type is different. The specified type of the data in V7 is different from the type of the memory card data.
Selected data can not be read. The data in a memory card cannot be read.
Reading Error occurred. The error occurred during writing data into a flash ROM of V7.
Data discrepant There is some discrepancy in data, when comparing data between a memory card and V7.
Screen data on V7 will be broken. Warning about data destruction in V7 that may occur when transferring the font data larger than the present data from a memory card to V7. (The [OK] switch continues transferring; the [Cancel] switch stops transferring.)
Undefined Error occurred. The error occurred due to some cause other than mentioned above.
Data discrepant · Messages Contents

2-24 1. Operation of V7 Main Menu
The “Ethernet” screen is displayed by pressing the [IP Address (English)] switch on the initial screen when transferring screen data via Ethernet for the first time, or by pressing the [Ethernet] switch on the Main Menu screen when transferring screen data to the V7 series. This screen is used for setting the IP address (a number that identifies the V7 series on the network) that is indispensable for Ethernet communications.
Depending on whether the LAN (10BASE-T) connector at V7i or the communication interface unit CU-03 for V7 is used, the “Ethernet” screen contents and the required settings vary as described below.
Selects [Not Use Network Table] or [Use Network Table].*1
Moves back to the Main Menu screen or the initial screen.
Not Use Network Table
It is not used when the gate way or the sub-mask is zero.
IP Address:
Gate Way:
[Increment/Decrement] switch for the value in the cursor position
Sub-mask:
Port No.
Determines the setting such as IP address, and moves back to the Main Menu screen.
Used for checking the 10BASE-T interface.
*1 Network Table Register IP addresses and other information for the V series, PLCs or computers that should be included for Ethernet communications on the V-SFT editor. ([System Setting] → [Network Table Setting] → [Ethernet] → Edit Network Table) The registered network table can be used or not used depending on the [Not Use Network Table/Use Network Table] switch.


In the following cases, select [Not Use Network Table].
When the network table is not set or is not used
Not Use Network Table
It is not used when the gate way or the sub-mask is zero.
IP Address:
Gate Way:
Sub-mask:
Port No.
: The cursor moves only in these sections for settings.
In the following cases, select [Use Network Table].
When the network table is used:
It is not used when the gate way or the sub-mask is zero.
IP Address:
Gate Way:
Sub-mask:
Port No.
Network Table No.:
Set the network table number.
Indicates the contents of the selected network table number.
· Use Network Table ·

2-26 1. Operation of V7 Main Menu
IP address, gateway and sub-mask settings
Moves back to the Main Menu screen.
Selects [10BASE-T] or [AUI].
It is not used when the gate way or the sub-mask is zero.
IP Address:
Gate Way:
[Increment/Decrement] switch for the value in the cursor position
Sub-mask:
Port No.
Determines the setting such as IP address, and moves back to the Main Menu screen.
Used for checking the 10BASE-T interface.

Port number to be set with the rotary switch on the communication interface unit CU-03


Main Menu V 7 1 0 i T D
Indicates the message, such as “Battery not set” or “Brownout Battery.”

D a t e a n d T i m e A d j u s t m e n t
F o r m a t o f S R A M
V7EM-S mounted: Extension V7EM-S not mounted: Built-in The above is displayed.
[SRAM/Clock] switch

2-28 1. Operation of V7 Main Menu
When the SRAM memory or cassette is initialized, the data contained is cleared. Double-check before initializing the SRAM memory or cassette.
When the [Extension] switch on the Main Menu screen is pressed, the following “Extension Program Info.” screen appears. The driver setting and parameter setting for temperature controller/PLC2Way communication, ladder transfer function, Modbus slave communication, etc. are displayed.
Main Menu Extension Program Info.
Temp./PLC2Way Control Drv VER. 1.100 RKC SR-Mini/CB
Temp. Control / PLC2Way Temp. Control / PLC2Way Comm. Parameter Comm. Parameter
Parity : None Retry Time : 3 Time-out : 100 msec Send Delay : 0 msec Return Time : 10 sec
Editor:MJ1

When the [Editor: MJ1] switch on the Main Menu screen is pressed, the following “Extended Function Setting” screen appears. Set the baud rate to be used when transferring screen data between the V7 series and a modem.
* The function switches and switches on the Main Menu screen are not valid for 15 seconds after the [Setting Finished] switch is pressed. * When the [Setting Finished] switch is pressed, an AT command is automatically sent to the modem and the baud rate used between the V7 series and the modem is set.
Tra s.Speed :
Stat. No. :
Editor:MJ1 PORT : 10000 MAC : 050FF000035
Main Menu Extended Function Setting
Pressing the [Editor: MJ1] switch brings up the “Extended Function Setting” screen.
Pressing the [Setting Finished] switch moves back to the Main Menu screen.
Stat. No. : 192.168 PORT: 10000 MAC: 0050FF000035
Editor:MJ1
![Page 87 of the Epson Endeavor V7 user manual — [SYSTEM] Switch](/cdn/reader/b8/b8449522b609f1ec53cca0ce6668e2b08023edbd18c283275a97f522d49d7dd5/images/page-87.webp?w=400)
2-30 2. Function Switches
Types
The [SYSTEM] switch works in “alternate” operations. When this switch is pressed once, the switch menu is displayed at the side of the function switches [F1] to [F5], and each function switch corresponds to the menu item displayed in the switch menu. When the [SYSTEM] switch is pressed again, the switch menu disappears, and the function switches [F1] to [F7] work as defined by the user.
Function switches for switch menu selection User-defined function switches User-defined function switches
![Epson Endeavor V7 — [SYSTEM] Switch diagram (page 87)](/cdn/reader/b8/b8449522b609f1ec53cca0ce6668e2b08023edbd18c283275a97f522d49d7dd5/images/fig-87-1.webp)
For V710T, V710iT, V710S, V710iS, V710iS, V712S and V712T

- Settings for each screen
[Edit] → [Local Function Switch Setting] → [Function Switch Setting] dialog
- Setting for all screens
[System Setting] → [Function Switch Setting] → [Function Switch Setting] dialog
F1 Mode Selects the operation mode between STOP ↔ RUN.
Contrast Adjustment Brightness Adjustment
Adjust the contrast. Holding down the switch for one second or more changes the contract rapidly.
Adjusts the screen brightness in three levels.
models V708C V710T, V710iT, V710S, V710iS,
F2 F3 F4
F2 F3 *1 F4 *1
Turn the backlight on and off. Backlight control should be set on the V-SFT editor. ([System Setting] → [Unit Setting] → [Unit Setting] dialog, [Backlight] tab window)
Always ON Auto 1/Auto 2 Manual/Manual 2
When the power is turned on:
ON → Backlight ON OFF → Backlight OFF The backlight will be in the above status.
*1 When a medium or dark brightness is set, the backlight service life may become shorter.

2-32 3. Errors Displayed on the V7 Series
There are five kinds of error messages displayed on the V series: 1. Communication Error 2. Check 3. Warning 4. SYSTEM ERROR 5. Touch switch is active
* When you go to [Comm. Parameter], bring up the [Detail] tab window and set [Continue] for [Comm. Error Handling], a screen like the one shown below is displayed.
Screen No. : Received Code No. :
R e t r y
Error Message Contents Solution Remarks
Time-Out Although a request to send is given to the PLC, no answer is returned within the specified time.
Parity An error occurred in parity check. 1) Check the cables and wiring. 1
Framing Although the stop bit must be [1], it is detected as [0].
Overrun After one character is received, the next character is received before internal processing is completed.
Check Code The check code in the PLC response was not correct.
* If the above error messages are displayed on the V7 series without establishing communication between V7 and PLC, test the solution of remark “1.” If the error occurs suddenly in communication, test the solution of remark “2.”
Time-Out · Communication Error Time-Out

Error Message Contents Solution
Error code received An error code was sent to the link unit by the CPU of the PLC.
Examine the CPU error code and solve the problem.
Break The PLC’s SD (TXD) remains at the low level.
Examine the connection between the PLC’s SD (TXD) and the V7’s RD (RXD).
Invalid memory (applicable to MITSUBISHI CPU)
You specified an address that exceeds the memory range of the PLC that you are linked to.
Check the type and range of memory that you set.
Invalid CPU model (applicable to MITSUBISHI CPU)
The PLC currently being supported does not have a corresponding CPU.
Confirm whether or not the CPU that you are using can be used with the V Series.
Format The code of the received data is invalid.
Check 1, 2, 3 described below.
Compare (applicable to HIDIC S10)
Transmission data and received data are different.
Check 1, 2, 3 described below.
NAK (applicable to Allen-Bradley PLC)
A NAK code is received. Check 1, 2, 3 described below.
TNS discrepant (applicable to Allen-Bradley PLC)
Transmitted TNS data and received TNS data are not in agreement.
Check 1, 2, 3 described below.
Communication Error An unclear communication error is detected.
Check 1, 2, 3 described below.
Count error (applicable to MITSUBISHI CPU/Q link unit)
The expected data amount is different from the count value.
Check 1, 2, 3 described below.
Command error (applicable to MITSUBISHI CPU/Q link unit)
The response code differs from the expected code.
Check 1, 2, 3 described below.
Invalid cassette (applicable to MITSUBISHI ACPU)
This cassette is not included in the memory cassettes currently being supported.
Contact your local distributor.
Password error (applicable to MITSUBISHI QCPU)
The password is incorrect. Contact your local distributor.
Solution 1. Confirm link unit settings. (After making settings, cut power to the PLC.) 2. Go to the editor (V-SFT) and confirm the settings in the [Comm. Parameter] dialog in the [System Setting] menu. 3. If errors only occur from time to time, it is possible that there is a noise-based communication error. * If you still cannot solve the error even after following the suggestions above, contact your local distributor.

2-34 3. Errors Displayed on the V7 Series
Error Message Contents Solution
Ethernet Error: XXXX The Ethernet status is saved at system memory address $s518 and a code other than “0” (normal) is received. XXXX: Error No.
For the contents and solution to each error number, refer to “Chapter 4 Network Communications/Error Display.”
Error Message Contents Solution
I/F Board Err The I/F unit for NET/10 has an error. Contact your local distributor.
Request Code Err The request command from NET/10 has an error.
Request Data Err The request data from NET/10 has an error.
Word Writing to Sp. Relay (MITSUBISHI: A Series)
Word writing to a special relay (M9000 and later) is attempted. (Notes: Only bit writing is possible for special relays when connecting with NET/10.)
Do not attempt to perform word writing to special relays.
Error Message Contents Solution
I/F Board Err The I/F unit for CC-LINK has an error. Contact your local distributor.
No. of Occupy Setting Err The number of occupy in [Comm. Parameter] is different from the number of occupy by switches.
Check the setting of the number of occupy.
Network I/O Access Err MONITOUCH is about to access exceeding the set number of input/output words.
Check the memory for the network I/O in the screen data file.
Station Number Err The port number set by a switch is not within the setting range (1 to 64).
Specify the port number within the setting range.
Word Writing to Sp. Relay Word writing to a special relay (M9000 and later) is attempted. (Notes: Only bit writing is possible for special relays when connecting with CC-LINK.)
Do not attempt to perform word writing to special relays.

Error Message Contents Solution
I/F Board Err The I/F unit for OPCN-1 has an error. Contact your local distributor.
Stat. No. out of range The port number set by a switch is not within the setting range (1 to 127).
Specify the port number within the setting range.
Network Link Error Cannot connect to the master station in the network.
Check the condition of the master station (PLC). Check the network connection.
Network I/O Access Err MONITOUCH is about to access exceeding the set number of input/output words.
Check the memory for the network I/O in the screen data file.
Waiting for Reply 1) Less than “Max_int” time (communication monitoring time for salve station) set on the PLC for OPCN-1 communications 2) Timeout on the V-SFT editor (The timeout time can be set from [System Setting] → [Comm. Parameter] on the V-SFT editor.) This error is indicated when the above 1) and 2) are present.
When the “Max_int” time is too long (infinite, for example) on the PLC, it is not possible to know whether or not the response from the PLC is correctly made. This error message disappears when a response from the PLC is received within the “Max_int” time.
Word Writing to Sp. Relay (MITSUBISHI: A Series)
Word writing to a special relay (M9000 and later) is attempted. (Notes: Only bit writing is possible for special relays when connecting with OPCN-1.)
Do not attempt to perform word writing to special relays.
Error Message Contents Solution
T-LINK I/F Board Err The I/F unit for T-LINK has an error. Contact your local distributor.
Network I/O Access Err MONITOUCH is about to access exceeding the set number of input/output words.
Check the memory for the network I/O in the screen data file.
Access denied by Loader The PLC loader is being accessed so that processing is not performed on V7. (This error occurs during program transfer from the PLC loader for most cases.)
Wait for the PLVC loader to finish processing, and press the [RETRY] switch on the V7 screen.
Communication Error Received Code No. 36
The number of monitor registration points is too small.
Correct the number of monitor registration points. For monitor registration, refer to the user manual of the PLC you are using.
Error Message Contents Solution
Time-Out “Check” is displayed 2 or 3 seconds before this error occurs when connecting V7 and PROFIBUS-DP in the RUN mode.
The setting for [Own Stat. No.] on V7 is discrepant with that for [Address] for [V7 series] on the SIMATIC Manager. Check and correct the setting.
A screen is displayed instantaneously (= communications performed) before this error occurs when connecting V7 and PROFIBUS-DP in the RUN mode.
The DB address set on the V7 screen may not exist on the PLC (memory over). Check the setting.

2-36 3. Errors Displayed on the V7 Series
Error Message Contents Solution
Screen No. Error There is no setting for the received screen.
At the start of communications, the V7 series regards the value in the read area “n + 2” as the screen number. Check that this value is an existing screen number on the PLC.
There is an error in the created screen data.
“Error : XX (XX : XXX)” indicates the edited screen and the contents of the error. For the error details and solutions, refer to “Reference Manual” and correct screen data.
Communication Error Check I/F driver
Screen No. Error
Error Message Contents Solution
Communication Error Check I/F driver
Although a request to send is given to the computer, no answer is returned within the specified time.
The I/F driver for simulator is transferred. If you don’t use the simulator, uncheck [Use Simulator] before transferring data.
An error may be displayed on the Main Menu screen during data transfer. This is a warning message. For the warning details and solutions, refer to the Reference Manual and correct screen data.

Stat. No. : 192.168.1.68 PORT : 10000 MAC : 0050FF000035
Check · Check

When a system error is detected, the following error screen is displayed.
SYSTEM ERROR : 32
TEA : XXXXXXXX
EXPEVT : XXXXXXXX
SSR : XXXXXXXX
SPC : XXXXXXXX
The source of the error could be one of the following three problems. Contact your local distributor.
If the power is turned off while a touch switch is activated, the following error screen is displayed. Remove your finger from the screen.
Touch Switch is active.
Keep hand off the screen.
Check

2-38 3. Errors Displayed on the V7 Series
Please use this page freely.





1 : 1 Connection

RS-232C or RS-422 (RS-485)


Prepare the communication cable with the PLC on your side. Refer to the following information for the cable. For more information on the connection to respective PLCs, refer to “Chapter 5 Connection to PLCs.”
To the PLC’s RS232C port
Signal Name Pin No.
SD
RD
RS
CS
SG 7
SG
To the PLC’s RS232C port
Signal Name Pin No.
SG
SD
RD
SG
RS
CS
SG 7

4-wire system:
Signal Name Pin No.
FG
+SD
- RD
Receive data (−)
Send data (−)
SG
2-wire system:
Signal Name Pin No.
FG
+SD
- RD
Send/receive data (−)
SG 7
SG
V-SFT Setting
For serial communications, the following settings on the V-SFT editor are required. The settings in the [Select PLC Type] and [Comm. Parameter] dialogs are shown on the Main Menu screen of the V7 series. (Refer to “Chapter 2 MONITOUCH Operations.”)

Select the PLC that is connected.
The communication parameter setting is essential for successful communications between the V series ↔ PLC. Check the communication parameter setting on the PLC before making the setting on MONITOUCH.
Select the type of connection between the V7 series and the PLC. There are four types available. Depending on the selected type, the setting items in the [Comm. Parameter] dialog or those for the memory vary. Select [1 : 1] for 1 : 1 connection.
- [Local No.]
Set the port number of the PLC.
- [Trans. Mode] (Trans. Mode 1/Trans. Mode 4)
When the PLC has a transmission mode setting, set the same on the V7 series. (This setting must be used for PLCs of MITSUBISHI, OMRON, HITACHI, YOKOGAWA, Toyoda Machinery and YASKAWA.)
- [Baud Rate] [Signal Level] [Data Length] [Stop Bit] [Parity]
Make the same setting as the PLC. (Refer to “Chapter 5 Connection to PLCs.”)
[Baud Rate] (4800, 9600, 19200, 38400, 57600, 76800, 115 kbps)
Set the same communication speed as the PLC.
Set the same communication interface as the PLC.
Choose either data length for communication.
Choose either stop bit for communication.
Choose any of the parity options for communication.
- [Send Delay Time] (0 to 255) (Unit: × 1 msec)
Set a time delay in sending the next command to the PLC after receipt of a response from the PLC. Normally use the default setting.
MONITOUCH
Send delay time “t”
Set a time delay in seconds in starting communications on the V7 series to avoid a delay in PLC processing that may occur when the V7 series and the PLC are turned on at the same time.

- Choose the action to be taken against communication errors.
[Comm. Error Handling]
Set error handling routine in the case that a communication error between the V7 series and the PLC occurs.
[Stop] If any communication error has arisen, the communications are stopped. When restoring, use the Retry switch (found on the error screen of the V7 series).
[Continuous] If any communication error has arisen, it is indicated at the top left
corner on the V7 screen. The V7 series conducts polling of the PLC, and if OK, the error state is automatically reset.
Supplemental Information: Polling “Polling” means to constantly monitor and check the state of the other station.
[Time-out Time] (0 to 999) (Unit: ×10 msec)
Specify a time for monitoring the receiving of a response from the PLC. If no response is received within the specified time, a retrial is attempted.
[Retrials] (1 to 255)
Specify the number of retrial times. When the problem persists even after as many retrials as specified, the system will start the error handling routine.
(LSB → MSB / MSB → LSB) When processing characters, choose either option for arranging 1st/2nd bytes in one word.
2nd byte 1st byte
1st byte 2nd byte [MSB → LSB]
Choose the code for entering numerical data. For some numerical data, such as those for data displays or data sampling in the sampling mode, this setting is not applied because BCD or DEC should be chosen for [Input Format].
- [Read Area] [Write Area]
Refer to the next section “System Memory.”
- [ Read/Write Area GD-80 Compatible] When converting screen data files created on GD-80 into those of the V7 series, this option is automatically checked. When this option is checked, GD-80 compatibility is supported by securing 2 words each for [Read Area] and [Write Area] in the same format as GD-80. For more information, refer to the GD-80 User’s Manual.
- [ Use Ethernet] When using Ethernet communications, check this option. For more information, refer to “Chapter 4 Network Communications/1. Ethernet.”
- [Text Processing] · - [Code] (DEC/BCD)

[Read Area]/[Write Area] of the system memory must be secured for communications between the V7 series and the PLC.
- This is the area where commands from the PLC are received for screen display
changes. Consecutive three words from the specified memory address are used as “read area.”

* When you have created screens with the following function,the number of required memory addresses vary. • When the sampling function is used:
Refer to the Reference Manual (Function).
Refer to the GD-80 User’s Manual. - Set “0” for all the bits not used in the read area.

15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
0
To forcibly change the bits for “free” area, the same data is written to CFMDATA in [Write Area] after the screen is displayed. Use this function for watch dog or display scanning.

15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00

15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
System reserved (setting [0])
Use example: To specify a screen number from the PLC: When “D0” is set for [Read Area], the screen number is written in “D2” of the PLC.
Problem example: The screen display does not change when a screen number is specified from the PLC. If the same number as the one specified for “n + 2” is already contained in this memory address, the screen display does not change even if it is specified again. For example, if screen No. 5 is specified from the PLC and it was once changed to screen No. 2 → No. 0 by internal switches, normally it cannot be returned to the former screen No. 5 that was specified by an external command, because the external screen command number (5) remains the same as before in the memory address (“D2” in the read area) for the screen number command.In such a case, it is possible to forcibly switch the screen to the screen number contained in “D2” in the read area at the leading edge [0 → 1] of bit 14 of the memory address for the screen status command (“D1” in the read area).

Read area “n + 2” = Screen number command
Data in the read area “n + 2” remains the same even if the actual screen has been switched internally.
To show screen No. 5 again using an external screen command, set [0→1] to bit 14 of read area “n + 1.”
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
0 1 0 5
Screen number

[Write Area] (3 words)*
This is an area where the screen status is written. Consecutive three words from the specified memory address are used as “write area.” * When you have converted GD-80 data to the V7 series data, the number of required memory addresses vary. Refer to the GD-80 User’s Manual.

n CFMDAT Same as data in read area “n”

15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
0

15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Screen number System reserved (setting [0])
Overlap 0 · Overlap 1

1 : n Connection
One V7 series is connected to multiple PLCs. (Maximum connectable PLCs: 32)

Maximum length (V7 series to the terminating PLC) = 500 m
For connecting information, refer to the instruction manual for the PLC.
Example:
The following example shows how one V7 series is connected to three PLCs made by MITSUBISHI. For more information, refer to the MITSUBISHI’s instruction manual for the PLC.

(OFF)
(OFF)
(ON)
* Use shielded twist-pair cables.

The following settings must be made on the V-SFT editor. Only the points different from those described in “1 : 1 Connection/V-SFT Setting” (page 3-3) are explained here.
Select the PLC that is connected. Check that the PLC to be connected is ready for 1 : n connection. Refer to the Appendix.
Set the port number of each PLC not in the [Comm. Parameter] dialog but in the [Memory Setting] dialog for each part.
Supplemental Information: Internal system memory The internal system memory is the one for the V7 series system.

Multi-link 2
V7 master station V7 slave station V7 slave station

Local Port 1 Local Port 2 Local Port 3 Local Port 4
V7 slave station

(a) (b) (c) (d) (e)
CN1 CN1
(= Local Port 1)
(= Local Port 2)
(= Local Port 3)
(= Local Port 4)
(a) Connection between PLC ↔ V7 master station The communication parameter setting and connecting method are the same as those for 1 : 1 connection. (Refer to “Chapter 5 Connection to PLCs.”)
(b)(c) Connection between V7 series master station ↔ V7 slave station
The connecting port for the V7 series master station depends on the selection for [Multi-Link] (either [Modular Jack 1] or [Modular Jack 2]) on the V-SFT editor. Selection of [Modular Jack 2] is recommended. ([Editor Port] is set as default for [Modular Jack 1].) The connecting port of the V7 series slave station should be CN1. It is recommended that CN1 be equipped with a terminal converter “TC485” (set to 2-wire connection). The multi-link 2 master cable (b) (V6-MLT) is 3 m long. If the distance (c) between the V7 series master station and the V7 series slave station is longer than 3 m, use a terminal block and connect the cables.
(d)(e) Connection between V7 series slave station ↔ V7 slave station
Use the RS-485 2-wire connection. It is recommended that CN1 be equipped with a terminal converter “TC485” (set to 2-wire connection).
(b)(c)(d)(e) The maximum length between V7 series should be 500 m.
* To avoid line-noise problems, connect one terminal only so that the shielded frame ground of each cable will not be connected between the V7 series. The shielded frame ground of V6-MLT must be connected to the V7 series master station. * When the terminal converter “TC485” is not used, install jumpers between +RD/+SD and −RD/−SD.


(ON)
(OFF)
(OFF)
(OFF)
Terminating Resistance Setting
1 2 3 4 5 6 7 8
MJ2 (modular jack 2) terminating resistance
Not used CN1 RD terminating resistance at pins 24 and 25
MJ1 (modular jack 1) terminating resistance
Terminating Resistance Setting Example


RS-422/485
CN1 CN1 CN1 CN1 MJ1/2
(= Local Port 1)
(= Local Port 2)
(= Local Port 3)
(= Local Port 4)
ON
ON
ON
When MJ1 is used:
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
When MJ2 is used:
1 2 3 4 5 6 7 8
The following settings must be made on the V-SFT editor. Only the points different from those described in “1. 1 : 1 Connection/V-SFT Setting” (page 3-3) are explained here.
Select the PLC that is connected.
Select [Multi-Link 2]. Click [Setting]. The [Multi-Link 2] dialog is displayed. Make the necessary settings. For the V7 series master station, set the following items. For the V7 series slave station, set the items marked with ♦.
[Local Port]♦ (1 to 4)
Set the port number of the V7 series. For the V7 series master station, set “1.” For the V7 series slave station, set “2” to “4.” Set the unique port number for each V7 series. If the number duplicates, communications will not be performed correctly.

[Send Delay Time] (0 to 255) (Unit: ×1 msec)
Set a time delay in sending the response to the PLC after receipt of data from the PLC. Normally use the default setting (0).
MONITOUCH
Send delay time “t”
[Total]♦ (2 to 4)
Set the total number of the V7 series included in the multi-link 2 connection.
[Retry Cycle] (×10)
Set the number of cycles before the master station sends an inquiry for restoration to the slave station that has a communication problem (= system down). When a slave station has a problem, it is temporarily removed from the communication targets, and the master station sends an inquiry for restoration every number of cycles specified for [Retry Cycle]. This setting does not affect the communication speed if no problem is occurring; however, if there is any problem, it does affect the communication speed.
Supplemental Information: [Retrials] in the [Detail] tab window of the [Comm. Parameter] dialog is the number of retrials that the V7 series master station sends an inquiry to the PLC.
[Baud Rate of Multi-Link] ♦ (4800, 9600, 19200, 38400, 57600, 76800, 115 kbps)
Set the baud rate used for communications between the V7 series. The setting must be the same as other V7 series on the same communication line. * For [Total] and [Baud Rate of Multi-Link], the same values must be set on all the V7 series that are connected in the same communication line.

Multi-link
V7 series No. 1 V7 series No. 2 V7 series No. 3 V7 series No. “n” (n = 1 to 32)

Maximum length (PLC to the terminating V7 series) = 500 m

Use the RS-485 2-wire connection. (It is recommended that Hakko Electronics’ optional terminal converter “TC485” be used.)
To the PLC’s RS422 port of the
TC485
TC485
TC485
- SD
- SD
FG
FG
- SD
FG
+SD
+SD
+SD
- RD
- RD
- RD
Send data (−)
+RD
+RD
Receive data (−)
SG
SG SG
(ON)
(OFF)
When no jumper is required on the PLC:
To the PLC’s RS422 port of the
TC485
TC485
- SD
- SD
- SD
FG
FG
FG
+SD
+SD
+SD
- RD
- RD
- RD
Send data (−)
+RD
+RD
SG
SG
SG
SG
(ON)
(OFF)

V7+TC485 V7+TC485
Pin No.
- SD
- SD
FG
FG
FG
+SD
+SD
- RD
- RD
+SD
- RD
+RD
+RD
+RD
+DSR
+DTR
SG
SG
SG
SG 7
- DSR 17
- DTR 18
(ON)
(OFF)
(OFF)
* Use shielded twist-pair cables.
Use the GD port of Hakko Electronics’ optional dual port interface V-MDD.
The following settings must be made on the V-SFT editor. Only the points different from those described in “1. 1 : 1 Connection/V-SFT Setting” (page 3-3) are explained here.
Select the PLC that is connected. Check that the PLC to be connected is ready for multi-link connection. Refer to the Appendix.
Select [Multi-Link]. Click [Setting]. The [Multi-Link] dialog is displayed. Make the necessary settings.
[Local Port] (1 to 32)
Set the port number of the V7 series. Set the unique port number for each V7 series. If the number duplicates, communications will not be performed correctly.
[Send Delay Time] (0 to 255) (Unit: ×1 msec)
Set a time delay in sending the response to the PLC after receipt of data from the PLC. (Default setting: 20 msec)
MONITOUCH
Send delay time “t”

[Total] (2 to 32)
Set the total number of the V7 series included in the connection.
[Retry Cycle] (×10)
When the V7 series has a problem, it is temporarily removed from the communication targets, and the master station sends an inquiry for restoration every number of cycles specified for [Retry Cycle]. This setting does not affect the communication speed if no problem is occurring; however, if there is any problem, it does affect the communication speed.
Supplemental Information: [Retrials] in the [Detail] tab window of the [Comm. Parameter] dialog is the number of retrials that the V7 series sends an inquiry to the PLC.
* For [Send Delay Time], [Total] and [Retry Cycle], the same values must be set on all the V7 series that are connected in the same communication line.

3-20 5. Universal Serial Communications
Universal Serial Communications

RS-232C or RS-422 (RS-485)

V7 series No. 1
V7 series No. 2 V7 series No. 3 V7 series No. “n” (n = 1 to 32)

V-Link


Dedicated commands · Read ·

3-22 6. V-Link
Use Hakko Electronics’ cable “V6-TMP” (3 m) for connection with a computer. The shielded frame ground of V6-TMP must be connected to the V7 series.
* Notes on Use of V6-TMP There are six wires in the V6-TMP cable as shown on the right. The wires to be used are determined depending on the connecting method. For the wires not used, be sure to properly insulate with tape, etc.
: 0V SG : RXD : TXD
: +SD/RD : - SD/RD
RS-232C (V7 series: 1 set)
RS-232C
MJ2/1
V7 Local Port 1
RS-232C RS-422 RS-485 PLC
Wiring example of above (a)
V7 series Modular jack, 8-pin
Computer D-sub 9-pin (female) Pin No.
Pin No. Signal Name
TXD 8 RD
RXD
SD
SG
SG
DR
RS 7
CS

RS-232C → RS485 conversion
Terminal block Terminal block Terminal block
V7 Local Port 1
V7 Local Port 2
V7 Local Port 31
CN1 CN1 CN1
RS-232C RS-422 RS-485 PLC PLC PLC
* 0.5 m recommended (1.0 m maximum)
Wiring example of above (a) and (b)
FG FG FG
SG SG SG
V7 Modular jack, 8-pin
V7 Modular jack, 8-pin
Pin No.
Signal Name Pin No.
SG 5 SG 5

3-24 6. V-Link
The V-SFT settings required for V-Link are explained.
Select the modular jack to be used. Modular Jack 1/Modular Jack 2
4800 / 9600 / 19200 / 38400 / 57600 / 115 kbps
[Local Port] (1 to 31)
Set the port number of the V7 series.
[Send Delay Time] (msec)
Set a time delay in sending a response after receipt of data.
RS-232C / RS-485 With RS-232C, one V7 series can be connected; with RS-485, a maximum of 31 V7 series can be connected.
Check this option when using a sum check.
Check this option when adding CR/LF.

E T X
S U M
Serial Communications
No.
F
1
2 18
A C K
E T X
S U M
No.
F
1 2 2 2
(When an error occurs)
N A K
E T X
S U M
No.
F
1 2 2 1 1 1 2
* Read target memory setting
V7 internal memory PLC memory within 16 bits Temperature cotrol/ PLC memory within 16 bits
PLC memory over 16 bits Temperature cotrol/ PLC memory over 16 bits
Station Number (in [n:1] connection)
Station Number (in [n:1] connection)
Record No.
File No.
2 2 4 10 2 4 2 2 2 4 2 4 4 4
2 8 2
e.g.
Reads the 2-word data, "ABCD" starting with the address $u0020(0014H) on the V7 of the station number 1.
E T X
S U M
Model Type Address Reserved for system
F
No.
01 H 02 H
00 H 20 H
30H32H 30H30H 30H30H 00H 0000000000H
30H30H30H30H30H30H30H30H30H30H 03H 0DH 0AH
30 H 30 H 31 H 34 H
38 H 46 H
S T X
A C K
E T X
S U M
R
F
A B C D
No.
30 H 31 H 01 H
30H30H 0DH 0AH 00H
02 H 03 H
34H31H 34H32H 34H33H 34H34H

3-26 6. V-Link
S T X
E T X
S U M
No.
F
1 2 18 4 4
A C K
E T X
S U M
No.
F
1 2 2 1 1 1 2
(When an error occurs)
N A K
E T X
S U M
No.
F
1 2 2 1 1 1 2
* Write target memory setting
V6 internal memory PLC memory within 16 bits Temperature cotrol/ PLC memory within 16 bits
PLC memory over 16 bits Temperature cotrol/ PLC memory over 16 bits
Station Number (in [n:1] connection)
Station Number (in [n:1] connection)
Record No.
File No.
2 2 4 10 2 4 2 2 2 4 2 2 2 4 4 4
2 8 2
e.g.
Writes "AB12" to the addresses D0100 to 101(0064 to 0065H) on the PLC connected to the V7 of the station number 1.
E T X
S U M
Model Type Address Reserved for system
F
No.
34H31H 34H32H 33H31H 33H32H 01H 02H
30H32H 30H31H 01H 00H
0064 H
30 H 31 H 02 H
32 H 31 H
30 H 30 H 36 H 34 H
30H30H30H30H30H30H30H30H30H30H 03H 0DH 0AH
S T X
A C K
E T X
S U M
R
F
No.
30H30H 0DH 0AH 00H
02 H 03 H
43 H 36 H

Signal Name Code (Hexadecimal) Contents
STX 02H Start of transmission block
ETX 03H End of transmission block
CR 0DH Carriage return
LF 0AH Line feed
Name Code (Hexadecimal) ASCII Contents
Read 20H 32 30 Read from memory
Write 21H 32 31 Write to memory
V7 series internal memory 00H 3030
Memory card 02H 3032

3-28 6. V-Link
Type Code (Hexadecimal) ASCII
$u (user memory) 00H 3030
$s (system memory) 01H 3031
$L (non-volatile word memory) 02H 3032
$LD (non-volatile double-word memory) 03H 3033
PLC memory Depends on the PLC to be used. Set the type number indicated for “Available Memory” of respective PLCs on the Hardware Specifications.
Depends on the PLC to be connected to the temperature controller and PLC2 function. Set the type number indicated for “Available Memory” of respective temperature controllers on the Temperature Control Network Manual. Set the type number indicated for “Available Memory” of respective PLCs on the Hardware Specifications when using the PLC2Way function.
Specify the memory address to be accessed.
Set the slot number of the SPU memory of the MITSUBISHI PLC or the CPU number of the YOKOGAWA PLC.
Example:
MITSUBISHI Slot No. 0: 00H MITSUBISHI Slot No. 1: 01H YOKOGAWA CPU No. 1: 00H YOKOGAWA CPU No. 2: 01H
* If no expansion code or port number is required, enter “00” (= 3030 in the ASCII code).
- File No.
Specify the file number set in the [Memory Card Setting] dialog of the V-SFT editor.
- Record No.
Specify the record number set in the [Memory Card Setting] dialog of the V-SFT editor.
Enter “0” (= 30 in the ASCII code) for the number of bytes. The number of bytes for “system reserved” varies depending on the model.
Example:
Model No. of Bytes Code (Hexadecimal) ASCII
V7 internal memory 10 0000000000H 30303030303030303030

Data is added up (SUM), and the lower one byte (8 bits) of the sum is converted into the 2-digit ASCII code (hexadecimal). A sum check code is shown below.
Command: 20 (data read) Address: 10 words from $u1000 (03E8H) When reading, a sum check will be performed as shown below.
STX V7 Port number Command Read Words
Type Address System reserved ETX SUM
01H 20H 0AH 00H 00H 03E8H 0H B9H
02H 30H31H 32H30H 30H41H 30H30H 30H30H 30H 33H 45H 38H 30H 03H 42H39H
02H + 30H + 31H + 32H + 30H + 30H + 41H + 30H + 30H + 30H + 30H + 30H + 33H + 45H + 38H
+ 30H + 30H + 30H + 30H + 30H + 30H + 30H + 30H + 30H + 30H + 03H = 4B9H
This code is received at normal termination. 00H (3030: ASCII)
This code is received at abnormal termination. (ASCII) Refer to the next page for more information.
02H: Overrun/Framing error An overrun or framing error is detected in the received data. Send the command again.
03H: Parity error A parity error is detected in the received data. Send the command again.
04H: Sum check error A sum error occurs with the received data.
0FH: ETX error No ETX code is found.
11H: Character error A character not used in the received data is found. (other than 0 to F) Check the character and send the command again.
12H: Command error An invalid command is given.
13H: Memory setting error The address or device number is invalid.
Memory · Memory · Model

3-30 6. V-Link
A B C D
SP
@
P
’
p
!
A
Q
a
q
"
B
R
b
r
#
S
s
$
D
T
d
t
%
E
U
e
u
&
F
f
’
G
W
g
w
(
H
h
)
Y
y
A
:
J
Z
j
z
B
+
;
K
[
k
{
,
<
|
D
=
M
]
m
}
E
>
N
^
n
~
F
/
?
O
_
o
Upper · Lower

PLC2Way

FA C T O R Y A C E

FA C T O R Y A C E
FA C T O R Y A C E
FA C T O R Y A C E
(2-wire connection)

3-32 7. PLC2Way
Connection at the CN1 connector is described in “1. 1 : 1 Connection” to “4. n : 1 Connection (Multi-link).” Hereunder the PLC connection at the MJ port and settings required for PLC2Way connection are described.
There are some limitations on the connection at the MJ port.
MITSUBISHI, OMRON, SHARP, YOKOGAWA, FUJI ELECTRIC For the applicable PLCs, refer to the “PLC2Way” column in “Available PLCs” in “Chapter 5 Connection to PLCs.” ( : Connectable ×: Not connectable)

Two kinds of cables are available for PLC2Way connection at the MJ port. Cable connections are explained.
F1
F2
F3
F4
F5
F6
(RS-232C, RS-485/RS-422) MJ2/1
MJ-D25
F7
POWER
* Notes on Use of V6-TMP There are six wires in the V6-TMP cable as shown on the right. The wires to be used are determined depending on the connecting method. For the wires not used, be sure to properly insulate with tape, etc.
: 0V SG : RXD : TXD
: +SD/RD : - SD/RD
V7 series Modular jack, 8-pin


3-34 7. PLC2Way
V7 series Modular jack, 8-pin
PLC FG
SDA
+SD/RD
SDB
SG
RDA
RDB
SG
* Use the shielded cable.
V7 series Modular jack, 8-pin
PLC
PLC
- SD/RD
FG
FG
FG
FG
SDA
SDA
SDA
+SD/RD
SDB
SDB
SDB
SG
RDA
RDA
RDA
RDB
RDB
RDB
(ON)
SG
SG
SG
* Use the shielded cable.
* Use shielded twist-pair cables.
* Use shielded twist-pair cables. Terminating
(OFF)
(ON)
Terminating Resistance Setting
1 2 3 4 5 6 7 8
MJ2 (modular jack 2) terminating resistance
Not used CN1 RD terminating resistance at pins 24 and 25
MJ1 (modular jack 1) terminating resistance

PLC model selection and parameter setting to be made on the V-SFT editor for the PLC2Way connection at the MJ port are explained.
Select the PLC model and make the parameter setting as described below.





3-36 7. PLC2Way


[Baud Rate] (4800, 9600, 19200, 38400, 57600, 115000, 115 kbps)
Select the communication speed with the PLC connected at the MJ port.
Select the parity setting for communications with the PLC connected at the MJ port.
Select the data length for communications with the PLC connected at the MJ port.
Select the stop bit setting for communications with the PLC connected at the MJ port.
Select the signal level for communications with the PLC connected at the MJ port.
Set the number of retrials to be attempted in the case that a communication error occurs.
[Time-out Time] (×100 msec)
Select the receive time of the response from the PLC connected at the MJ port. If no response is received within the specified time, a retrial is attempted.
[Send Delay Time] (× msec)
Set a time delay in sending the response to the PLC after receipt of data from the PLC connected at the MJ port.
![Page 134 of the Epson Endeavor V7 user manual — [LSB → MSB] MSB LSB](/cdn/reader/b8/b8449522b609f1ec53cca0ce6668e2b08023edbd18c283275a97f522d49d7dd5/images/page-134.webp?w=400)
[Return Time] (×10 sec)
When the PLC in the PLC2Way communication is turned off, data read from the PLC is temporarily prohibited. An inquiry for restoration is sent each time the specified return time has elapsed.
The following options may be set depending on the PLC model.
[Trans. Mode] (Trans. Mode 1/Trans. Mode 4)
Serial Communications
[Trans. Mode] (Trans. Mode 1/Trans. Mode 2)
[Trans. Mode] (with sum check/without sum check)
For the PLC connected at the MJ port, [Code] and [Text Processing] cannot be set in the [Temp. Control/PLC2Way Comm. Setting] dialog.
Manufacturer Model Code Text Processing
DEC
QnH (Q) series link
OMRON
BCD SYSMAC CV
SYSMAC CS1
LSB → MSB
SHARP
BCD JW100/70H COM Port
YOKOGAWA
DEC FA-M3R
FUJI ELECTRIC
2nd byte 1st byte

3-38 7. PLC2Way

The following operations are available when the temperature control network/PLC2Way table is used.


Set the temperature control network/PLC2Way table number (0 to 31) and click [OK].
The [Temp. Network/PLC2Way Table Edit] window is opened.

There are 32 tables of temperature control network/PLC2Way table No. 0 to 31. A maximum of 128 addresses of the PLC2 memory can be set for each table.

Click [Edit] → [Comment]. The [Comment Setting] dialog is displayed.



3-40 7. PLC2Way
Enter the desired comment and click [OK]. The entered comment is displayed at the top right corner.

Click.
Double-clicking brings up the default setting for the PLC2 memory, data type, etc.

(1) Click. (2) Click. (3) Double-click.


When (1) is clicked, the [Memory Input] dialog is displayed.
Set the memory address to be read from the PLC connected at the MJ port.
When (2) is clicked, a data type for the PLC2 memory can be set.
This is the data length setting for the memory address to be used. Numerical data of one word is handled. Data is transferred to the target memory address in the numerical data code of the PLC2 memory.
This is the data length setting for the memory address to be used. Numerical data of two words is handled. Data is transferred to the target memory address in the numerical data code of the PLC2 memory.
Data in the PLC2 memory is handled as bit information of one word. Data is transferred to the target memory address without conversion.
[Dummy Word] [Dummy Double]
The memory addresses for [Target PLC Memory] and [Target Internal Memory] are automatically allocated consecutively in the [Temp. CTRL/PLC2Way Table Setting] dialog. If you would like to skip any memory address, keep the cell in the [Temp. CTRL/PLC2 Mem.] column blank (no setting). It is regarded as a dummy word or double-word. In this case, “0” is stored in the target memory address.
[Word] · [Double Word] · [Bit]

When the data code in the target memory address is BCD:
The code (numerical data format) for the PLC2 memory is fixed as mentioned above. (Refer to page 3-37.) Normally the V7 series handles numerical data as “DEC with signs.” For numerical data to be handled on the PLC connected to the MJ port, select [Word] or [Double Word] for [Data Type]; for data to be handled as bits, select [Bit].
0 8 15 14 13 12 11 10 9 7 6 5 4 3 2 1
0 1
MSB LSB
DEC
0 8 15 14 13 12 11 10 9 7 6 5 4 3 2 1
0 1 0 0 1 0
BCD
0 8 15 14 13 12 11 10 9 7 6 5 4 3 2 1
0 1 0 0 1 0 (Depends on the communication parameter setting)
Not necessary to be aware
MSB LSB
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 1
(Depends on the communication parameter setting)
Not necessary to be aware
When (3) is double-clicked, the [Temp. CTRL/PLC2Way Table Setting] dialog is displayed.
Set the memory addresses of the target PLC memory and target internal memory at one time in the [Temp. CTRL/PLC2Way Table Setting] dialog.
Set the cycle of reading data in the PLC2 memory.
[Store Target PLC Memory]
When storing data read from the PLC2 memory into the PLC memory, check this box and set the desired memory address.
[Store Target Internal Memory]
When storing data read from the PLC2 memory into the V7 internal memory, check this box and set the desired memory address.
[Temp. CTRL/PLC2Way Comm. Setting]
Clicking this button brings up the [Temp. CTRL/PLC2Way Comm. Setting] dialog and allows you to review the setting.

3-42 7. PLC2Way
To perform data sampling in the PLC2 memory, the following settings are required.

[No. of Table]
Select the temperature control network/PLC2Way table number for sampling.
Specify the number of sampling times.
[Store Target] (Internal Buffer/SRAM/SF Card)
Choose the desired medium for storing sampling data. Internal Buffer: Stores data in the internal buffer of the V7 series. (RAM) SRAM: Stores data in the SRAM area. (SRAM mounted on the unit, V7EM-S, REC-MCARD SRAM) CF Card: Stores data in the CF card.
Choose the desired processing when the target medium space has been used up.
- Continuous: When [Sampling Time] has been exceeded, data from the oldest is discarded. - Stop: When [Sampling Time] has been exceeded, sampling is stopped.

1 sample = [Words*] + 2 words Buffer size = [Sampling Times] × 1 sample * [Words] here means the number of words in the memory addresses used in the temperature control network/PLC2Way table that is set for [No. of Table].
* The used memory capacity of SRAM and CF card can be calculated in the same way as the buffering area.


Select the tab of the same number.

3-44 7. PLC2Way
Trend sampling Data sampling

Data in the PLC2 memory can be transferred to the PLC memory, V7 internal memory or a memory card at one time. Conversely, it is also possible to transfer data in the PLC memory, V7 internal memory or a memory card to the PLC2 memory at one time. To perform butch data transfer from the PLC2 memory, the following settings are required.
Data in the PLC2 memory addresses set in the temperature control network/PLC2Way table specified for F1 is transferred to the memory addresses starting from F0.
PLC Memory Internal Memory
Control Table No.) Memory Card Indirect Designation
F1
[TEMP_WRITE]
Data in memory addresses starting from F1 is transferred to the PLC2 memory of the temperature control network/PLC2Way table specified for F0.
PLC Memory Internal Memory
Control Table No.) Memory Card Indirect Designation
F1


Indirect Memory Designation
It is possible to have access to the PLC2 memory using the indirect memory designation as a macro command. In this section, the indirect designation of the PLC2 memory is explained. The internal user memory ($u) is used for the indirect memory designation.
Less than 16 bits
16 to 32 bits
15 8 7 0
15 8 7 0
n + 0 Model Memory type
n + 0 Model Memory type
n + 1 Memory number (address)
n + 1 Memory number (address) upper
n + 2 00 Bit designation
n + 2 Memory number (address) lower
n + 3 00 Port number
n + 3 00 Bit designation
n + 4 00 Port number
Depends on the PLC model. Refer to “Chapter 5 Connection to PLCs/Available PLCs” when setting.
Set the port number of the PLC connected at the MJ port.
- Model · - Memory type · - Port number

3-46 7. PLC2Way
The user log set with YOKOGAWA’s PLC “FA-M3/FA-M3R” connected at the MJ port can be read using the macro command TEMP_CTL.
This macro command controls the operation set in the memory addresses starting from the one specified for F0 for the number of words specified for F1.
PLC Memory Internal Memory Constant (Words) Memory Card Indirect Designation
F1
F0 (= $u n) F1
n n + 1 n + 2 n + 3 n + 4 n + 5 n + 6 n + 7 n + 8 n + 9 n + 10 n + 11 Words
User log registration number read
CPU No. −1*1
number*2 − 3
Year Month Day Hour Minute Second Main code
CPU No. −1*1
Year Month Day Hour Minute Second Main code
CPU No. −1*1
Return data: Data stored from PLC2Way → V7 series *1 Set “0” for CPU No. 1. *2 The registration number is stored in special register Z105. *3 If there is no user log in the “n + 2” memory or there is an error in communications, [−1] is stored.

The processing cycle on the V7 series with the PLC2Way function is explained.
Fig. a. When the temperature control network/PLC2Way table is not used:
PLC data 1 connected at
PLC data “n” connected at
PLC data 1 PLC data 2
Fig. b. When the temperature control network/PLC2Way table is used:
PLC data 1 PLC data 2
1 screen data read cycle
PLC data 1 connected at
PLC data 2 connected at
PLC data “n” connected at
1 data read cycle from the PLC connected at the MJ port
When the temperature control network/PLC2Way table is not used (Fig. a), PLC data is not read while the data is read from the PLC connected at the MJ port. When the temperature control network/PLC2Way table is used (Fig. b), PLC data is read while the data is read from the PLC connected at the MJ port. Consequently, it is possible to communicate with the PLC connected at the MJ port without reducing the processing capacity between the V7 ↔ the PLC.
When the temperature control network/PLC2Way table is used:
If periodical reading of the PLC data is performed while the PLC connected at the MJ port is accessed using a macro command, the macro execution may be delayed. It is possible to temporarily stop periodical reading from the PLC connected at the MJ port using the system memory address ($s762). For more information, refer to page 3-51.

3-48 7. PLC2Way
When using the temperature control network/PLC2Way communications, it is necessary to transfer the temperature control/PLC2 program to the V7 series. When the temperature control network/PLC2Way setting has been made, the program is automatically transferred to the V7 series together with screen data. When [ Temp./PLC2] is selected in the [Transfer] dialog, only the temperature control/PLC2 program can be transferred to the V7 series.

When the Main Menu screen is displayed after transferring screen data, the [Extension] switch appears. If the [Extension] switch does not appear, transfer font data. Pressing the switch brings up the “Extension Program Info.” screen where the temperature control/PLC2Way driver setting and temperature control network/PLC2way setting can be reviewed. For more information, refer to “Chapter 2 MONITOUCH Operations.”

The status of the PLC connected at the MJ port for PLC2Way communications is output to the system memory ($s) of the V7 series. The memory addresses ($s730 to 763) of the PLC connected at the MJ port are explained.
731 Temperature controller/PLC2Way Station No. 01 status
732 Temperature controller/PLC2Way Station No. 02 status
733 Temperature controller/PLC2Way Station No. 03 status
734 Temperature controller/PLC2Way Station No. 04 status
735 Temperature controller/PLC2Way Station No. 05 status
736 Temperature controller/PLC2Way Station No. 06 status
737 Temperature controller/PLC2Way Station No. 07 status
738 Temperature controller/PLC2Way Station No. 08 status
739 Temperature controller/PLC2Way Station No. 09 status
740 Temperature controller/PLC2Way Station No. 10 status
741 Temperature controller/PLC2Way Station No. 11 status
742 Temperature controller/PLC2Way Station No. 12 status
743 Temperature controller/PLC2Way Station No. 13 status
744 Temperature controller/PLC2Way Station No. 14 status
745 Temperature controller/PLC2Way Station No. 15 status
746 Temperature controller/PLC2Way Station No. 16 status
747 Temperature controller/PLC2Way Station No. 17 status
748 Temperature controller/PLC2Way Station No. 18 status
749 Temperature controller/PLC2Way Station No. 19 status
750 Temperature controller/PLC2Way Station No. 20 status
751 Temperature controller/PLC2Way Station No. 21 status
752 Temperature controller/PLC2Way Station No. 22 status
753 Temperature controller/PLC2Way Station No. 23 status
754 Temperature controller/PLC2Way Station No. 24 status
755 Temperature controller/PLC2Way Station No. 25 status
756 Temperature controller/PLC2Way Station No. 26 status
757 Temperature controller/PLC2Way Station No. 27 status
758 Temperature controller/PLC2Way Station No. 28 status
759 Temperature controller/PLC2Way Station No. 29 status
760 Temperature controller/PLC2Way Station No. 30 status
761 Temperature controller/PLC2Way Station No. 31 status
Address Contents

3-50 7. PLC2Way
8001H Check code error
800BH Error code received from the PLC connected at the MJ port
Errors other than the above are stored as shown below.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0
Buffer-full error Parity error Overrun error Framing error Break detection
Timeout Although a request to send is given to the PLC connected at the MJ port, no answer is returned within the specified time.
Check 1, 2, 3 described below.
Check code error The check code in the PLC connected at the MJ port response was not correct.
Check 1, 3 described below.
Data error The code of the received data is invalid. Check 1, 2, 3 described below.
An error occurs at the PLC connected at the MJ port.
Refer to the instruction manual for the PLC.
Buffer full The V7 buffer is full. Contact your local distributor.
Parity An error occurred in parity check. Check 2, 3 described below.
Overrun After one character is received, the next character is received before internal processing is completed.
Check 1, 3 described below.
Framing Although the stop bit must be [1], it is detected as [0].
Check 1, 2, 3 described below.
Break detection SD (TXD) of the PLC connected at the MJ port remains at the low level.
Examine the connection between SD (TXD) of the PLC connected at the MJ port and RD (RXD) of the V7 series.
Solution 1. Check the parameter setting of the PLC connected at the MJ port and the setting in the [Temp. CTRL/PLC2Way Comm. Setting] dialog. 2. Check the cable connection. 3. Data may be disrupted because of noise. Fix noise. * If you still cannot solve the error even after following the suggestions above, contact your local distributor.

- [0]: Periodical reading is performed. - [Other than “0”]: Periodical reading is suspended.
If periodical reading of the temperature control network/PLC2Way table is performed while the PLC2 memory is being accessed using a macro command, the macro execution will be delayed (Fig. a). To avoid this, periodical reading can be suspended using memory address $s762 (Fig. b).
(Fig. a)
Execution of macro “a” Execution of macro “a”
Temperature control network/PLC2Way table periodical reading
TEMP_CTL $u100 2 TEMP_CTL $u110 2 TEMP_CTL $u120 2
TEMP_CTL $u100 2 TEMP_CTL $u110 2 TEMP_CTL $u120 2
Temperature control network/PLC2Way table periodical reading
(Fig. b)
Execution of macro “b” Execution of macro “b”
Temperature control network/PLC2Way table periodical reading
$s762=1 TEMP_CTL $u100 2 TEMP_CTL $u110 2 TEMP_CTL $u120 2
$s762=1 TEMP_CTL $u100 2 TEMP_CTL $u110 2 TEMP_CTL $u120 2
Temperature control network/PLC2Way table periodical reading
TEMP_CTL $u300 2 $s762=0
TEMP_CTL $u300 2 $s762=0
- [0]: When any station that has failed is included in the specified table, the macro command is not executed. - [Other than “0”]: The macro command is forcibly executed to the stations that are working properly.

3-52 8. Temperature Control Network
Temperature Control Network

V7 series · Temperature controller


6. T-LINK
7. PROFIBUS-DP



Ethernet

- “HKEtn10.dll” (for UDP/IP protocol) is provided so that the user can create an
original application by using Visual C++ or Visual Basic, etc. to allow the server to access the memory device, such as V7 internal memory, memory card or the PLC memory linked with the V7 series as a host (a)
- The macro command (SEND) enables the V7 series to access the server (b)

Server

4-2 1. Ethernet
- Screen data can be transferred from the V-SFT editor on the server to the V7 series.

- The V7 series can communicate with the PLC on the Ethernet.

FA C T O R Y A C E
* Ethernet-ready PLC only
- The V7 series can communicate with multiple PLCs on the Ethernet.

* Ethernet-ready PLC only
Server

IP Address for the V7 Series
To enable Ethernet communications on the V7 series, it is necessary to set the IP address for identification of the V7 series on the network. The IP address should be set on the Main Menu screen of the V7 series. For more information, refer to “Chapter 2 MONITOUCH Operations.”
Baud rate 10 Mbps
Transmission method Base band
Maximum network distance or maximum node interval
2500 m (5 segments) 925 m (5 segments) 500 m (4 HUBs)
Maximum segment length 500 m 185 m 100 m Between the node and the HUB
Maximum number of nodes 100/segment 30/segment 2/segment
Minimum node interval 2.5 m 0.5 m None
UTP (unshielded twisted pair) 22-26AWG
Connecting cable Ethernet coaxial cable (50 Ω)
RG58A/U, RG58C/U coaxial cable (50 Ω)
Specifications · Item AUI

4-4 1. Ethernet
10B-T RX TX LNK CI ADR - LOW - HI FUSE 0V
Name Contents On Off
RX Data receive status Currently receiving Not receiving
TX Data send status Currently sending Not sending
LNK Link status (for 10BASE-T only) Normal Error
Cl Collision Data collision Normal
* Make sure that each I/F unit on the network has a unique port number.
F
E
E
D
D
B
A
B
A
* It is not necessary to use 10BASE-T.

UTP cable Straight or cross cable (For more information, refer the HUB specifications.)
HUB
Network Communications
Distance between the node and the HUB: 100 m maximum Maximum network nodes: 100 sets
Straight cable (with HUB) Cross cable (without HUB)
* Unshielded twist-pair cable * Unshielded twist-pair cable

4-6 1. Ethernet
- Coaxial cable for 10BASE5 - AUI cable - N-type connector - N-type terminator - Transceiver - Power supply for the transceiver: 12 VDC
1 segment (max. 500 m, max. 100 nodes)
AUI cable (max 50 m)
2.5 m
To extend the length or increase the number of nodes, use repeaters.
PLC
*1: 12 V power supply is required for each transceiver.
Allied Telesis CentreCOM 107
* The I/F unit may be broken if the AUI connector is subject to strong force. Use the AUI cable when connecting the transceiver. * When the power lamp of the transceiver is not turned on, check the wiring of 12 VDC power supply, then replace the fuse (refer to page 4-4) of the I/F unit CU-03. For the replacement procedure, refer to the manual “CU-03 OPERATING INSTRUCTIONS,” attached to CU-03.
- Coaxial cable for 10BASE2 - AUI cable - T-type adaptor - Terminator for 10BASE2 - Transceiver - Power supply for the transceiver: 12VDC

1 segment (max. 185 m, max. 30 nodes)
AUI cable (max. 50 m)
0.5 m
To extend the segment distance or increase the number of nodes, use repeaters.
PLC
*1 The unit may have a built-in transceiver. Refer to the instruction manual for the unit. *2 12 V power supply is required for each transceiver.
Use the transceiver equipped with the SQE TEST function. (SQE TEST: Signal Quality Error Test)
Allied Telesis CentreCOM 107
* The I/F unit may be broken if the AUI connector is subject to strong force. Use the AUI cable when connecting the transceiver. * When the power lamp of the transceiver is not turned on, check the wiring of 12 VDC power supply, then replace the fuse (refer to page 4-4) of the I/F unit CU-03. For the replacement procedure, refer to the manual “CU-03 OPERATING INSTRUCTIONS,” attached to CU-03.

4-8 1. Ethernet
This section describes the procedure for transferring screen data from the V-SFT editor on the server to MONITOUCH via Ethernet. For the procedure using the V6-CP cable, refer to the Reference Manual (Operation).
When screen data is to be transferred for the first time via Ethernet or when the V7 series has been replaced due to trouble, the server cannot transfer screen data because the network table has not been transferred to the V7 series. In this case, the following setting must be made on the Main Menu screen:
- IP address - Default gateway - Subnet mask Note that this is the tentative setting. The port number must be “10000.” When the network table is transferred from the V-SFT editor, the above data is updated.
Main Menu V 7 1 0 i T D
2002-4 -1 07:23:30
FONT VER.1.300 / 1.000 / 1.000 ENGLISH
I/F DRV VER.1.310 YOKOGAWA FA-M3 Ethernet
Stat. No. : 192.168.1.68
Stat. No. : 192.168.1.68
Editor:MJ1




When a list is shown, select the IP address of the V7 series, and click the [


4-10 1. Ethernet

IP address for transfer target
To enable Ethernet communications on the V7 series, the following setting is required on the V-SFT editor.

There are two connecting methods between the V7 series and the PLC. (A) Connecting to the PLC through RS-232C or RS-485 interface (B) Connecting to the PLC on the Ethernet
Server

The contents of the system setting vary depending on the method selected. Check the connecting method and make the setting on the V-SFT editor.

(B) Connecting to the PLC on the Ethernet
PLC Model Section on V-SFT
Q2A, Q3A, Q4A Q2ASx
AUI cable QnH (Q) series (Ethernet)
QnH (Q mode) QJ71E71, QJ71E71-B2
F3LE01-5T, F3LE11-0T
*1 For AUI connection, a transceiver is required.
- The memory use is the same as the one for 1 : 1 connection. (Refer to “Chapter 5
Connection to PLCs.”
* The data code of the V7 series is fixed to the binary code. Be sure to set the binary code for the data code on the PLC.
PLC Unit Connection · QnA series (Ethernet) · FA-M3/FA-M3 R (Ethernet)

4-12 1. Ethernet

Network table No. 0 is displayed. It is not possible to select an option for [Connect To]. Select [System Setting] → [Network Table Setting] → [Ethernet]. The [Edit Network Table] window is displayed. Set the network table, and then go back to the communication parameter setting. For more information on network table editing, refer to page 4-14.
When the network table is set:

The IP addresses that are set on the network table are displayed. Select the IP address of the desired PLC.
Click here. A drop-down list is displayed.


Set the port number (network table number) of the PLC in the [Memory Input] dialog for each part. For more information on the network table, refer to page 4-14.


[Memory Input] · [Edit Network Table]

4-14 1. Ethernet
To enable Ethernet communications on the V7 series, the following network table setting is required on the V-SFT editor.


When [Use Ethernet] is selected in the [Comm. Parameter] dialog, be sure to edit the network table.
Server · Server


Menu and Icons
Each menu item corresponds to the icons as shown below.
- Import Network Table
Imports a network table saved as a file “∗.ntb.”
- Export Network Table
Exports a network table as a file “∗.ntb.”

- Use Monitor Registration
Only one V7 series can be registered as the monitor for Ethernet communications.

A mark is shown on the left of the network table number.
- Cancel Monitor Registration
Click this menu when canceling monitor registration.
[Close] button

4-16 1. Ethernet

Double-click the number.


The [Set Network Table No. *] dialog is displayed.
Set the name for the V7 series, etc. to be used on the Ethernet.
Set the IP address.
* When registering Ethernet-ready PLC, set the same IP address as that of the PLC. For the setting procedure of the IP address on the PLC, see the manual attached to each PLC. * When registering a computer as the server, set the same IP address as that of the computer. When setting the IP address on the computer, open [Property] of [TCP/IP] in [Network] on the Windows. * To connect to the intra-company network, consult with the network administrator.
[Host Name] · [IP Address]

This is an address that is used for recognizing each node on the Ethernet and should be unique. The IP address is 32-bit data which consists of the network address and the host address and can be classified into A to C depending on the network size.
Network address (14) Host address (16)
A string of 32-bit data is divided into four, and each segment delimited with a period is in decimal notation. Example: The IP address in class C shown below is represented as “192.128.1.50.” 11000000 10000000 00000001 00110010
Set the time-out time for the V7 series to send a command on the Ethernet.
[Port No.] (2049 to 65535) (Default: 10000)
Set the port number. The port number may be fixed depending on the PLC model. Refer to the instruction manual for the PLC. Example: YOKOGAWA FA-M3 12289: Fixed MITSUBISHI Q series auto-open UDP port 5000: Default (changeable by sequence)
Port No.
Multiple applications are running on each node, and communications are carried out for each application between the nodes. Consequently, it is necessary to have a means to identify the application that data should be transferred to. The port number works as this identifier. Each port number is 16-bit data (from 0 to 65535). However, since some numbers are already used, the setting range available with V7i is from 2049 to 65535. It is recommended to set a greater number.
Select either AUI or 10BASE-T. When connecting to the 10BASE-T connector (LAN) of V7i, select [10BASE-T]. Select either [10BASE-T] or [AUI] when CU-03 is mounted.
Attach a check mark ( ) when write-protecting the internal memory or memory card.
Attach a check mark ( ) when setting the default gateway.
A gateway and a router are used for communicating between different networks. The IP address of the gateway (router) should be set to communicate with the node(s) on other network.
Attach a check mark ( ) when setting the subnet mask. When this option is checked, it is set to [255.255.255.0].

4-18 1. Ethernet
A subnet mask is used for dividing one network address into multiple networks (subnet). The subnet is assigned by specifying a part of the host address in the IP address as a subnet address.
11111111 11111111 11111111 00000000
Network address Subnet address

This section explains the macro commands (SEND/EREAD/EWRITE) used for the Ethernet. For more information on macro commands, refer to the Reference Manual (Function).
Words from the F1 memory in the V7 series of the network table number specified for F3 are read into the F0 memory. F2 designates the number of words to be read.
![Epson Endeavor V7 — [EREAD] diagram (page 170)](/cdn/reader/b8/b8449522b609f1ec53cca0ce6668e2b08023edbd18c283275a97f522d49d7dd5/images/fig-170-1.webp)
The macro command for V7 (A) to read data from PLC (B) and transfer it to PLC (A) is shown below.
[Description] EREAD D200 = D100 C: 2 B
Top memory address of the source
Address of the source (Network table number)
Top memory address of the target
The number of words to be transferred
[Contents] Two words starting from D100 in PLC (B) are read into D200 in PLC (A).

FA C T O R Y A C E
Usable Devices
![Page 171 of the Epson Endeavor V7 user manual — [EWRITE]](/cdn/reader/b8/b8449522b609f1ec53cca0ce6668e2b08023edbd18c283275a97f522d49d7dd5/images/page-171.webp?w=400)
4-20 1. Ethernet
Words from the F2 memory are written into the F0 memory in the V7 series of the network table number specified for F1. F3 designates the number of words to be written.
![Epson Endeavor V7 — [EWRITE] diagram (page 171)](/cdn/reader/b8/b8449522b609f1ec53cca0ce6668e2b08023edbd18c283275a97f522d49d7dd5/images/fig-171-1.webp)
EWRITE F0 F1 = F2 C: F3 Example: Macro command at the V7 (A)
The macro command for V7 (A) to write data in V7 (A) to PLC (B) is shown below.
[Description] EWRITE D100 B = $u100 C: 2
Address of the target (Network table number)
The number of words to be transferred
Top memory address of the target
Top memory address of the source
[Contents] Two words starting from $u100 in V7 (A) are written into D100 in PLC (B).
![Epson Endeavor V7 — [EWRITE] diagram (page 171)](/cdn/reader/b8/b8449522b609f1ec53cca0ce6668e2b08023edbd18c283275a97f522d49d7dd5/images/fig-171-2.webp)
FA C T O R Y A C E
Usable Devices

Words from the F0 memory are transferred to the server of the network table number specified for F2. F1 designates the number of words to be transferred.
![Epson Endeavor V7 — [SEND] diagram (page 172)](/cdn/reader/b8/b8449522b609f1ec53cca0ce6668e2b08023edbd18c283275a97f522d49d7dd5/images/fig-172-1.webp)
The macro command for V7 (B) to transfer data to server (A) is shown below.
The number of words to be transferred
Top memory address of the source
Address of the target (Network table number)
[Contents] Two words starting from $u100 in V7 (B) are transferred to server (A).

Usable Devices · Server (A)

4-22 1. Ethernet
The Ethernet status is output to the system memory ($s) of the V7 series. This section explains the memory addresses ($s514 to 619) where the Ethernet status is output. For other memory addresses, refer to the Reference Manual (Function).
515 Result of executing the macro user request wait
520 Network table 0 status
521 Network table 1 status
522 Network table 2 status
523 Network table 3 status
524 Network table 4 status
525 Network table 5 status
526 Network table 6 status
527 Network table 7 status
528 Network table 8 status
529 Network table 9 status
530 Network table 10 status
531 Network table 11 status
532 Network table 12 status
533 Network table 13 status
534 Network table 14 status
535 Network table 15 status
536 Network table 16 status
537 Network table 17 status
538 Network table 18 status
539 Network table 19 status
540 Network table 20 status
541 Network table 21 status
542 Network table 22 status
543 Network table 23 status
544 Network table 24 status
545 Network table 25 status
546 Network table 26 status
547 Network table 27 status
548 Network table 28 status
Address Contents 518 Ethernet status

$s549 Network table 29 status
550 Network table 30 status
551 Network table 31 status
552 Network table 32 status
553 Network table 33 status
554 Network table 34 status
555 Network table 35 status
556 Network table 36 status
557 Network table 37 status
558 Network table 38 status
559 Network table 39 status
560 Network table 40 status
561 Network table 41 status
562 Network table 42 status
563 Network table 43 status
564 Network table 44 status
565 Network table 45 status
566 Network table 46 status
567 Network table 47 status
568 Network table 48 status
569 Network table 49 status
570 Network table 50 status
571 Network table 51 status
572 Network table 52 status
573 Network table 53 status
574 Network table 54 status
575 Network table 55 status
576 Network table 56 status
577 Network table 57 status
578 Network table 58 status
579 Network table 59 status
580 Network table 60 status
581 Network table 61 status
582 Network table 62 status
583 Network table 63 status
584 Network table 64 status
585 Network table 65 status
586 Network table 66 status
587 Network table 67 status
588 Network table 68 status
589 Network table 69 status
590 Network table 70 status
591 Network table 71 status
592 Network table 72 status
Address Contents

4-24 1. Ethernet
$s593 Network table 73 status
594 Network table 74 status
595 Network table 75 status
596 Network table 76 status
597 Network table 77 status
598 Network table 78 status
599 Network table 79 status
600 Network table 80 status
601 Network table 81 status
602 Network table 82 status
603 Network table 83 status
604 Network table 84 status
605 Network table 85 status
606 Network table 86 status
607 Network table 87 status
608 Network table 88 status
609 Network table 89 status
610 Network table 90 status
611 Network table 91 status
612 Network table 92 status
613 Network table 93 status
614 Network table 94 status
615 Network table 95 status
616 Network table 96 status
617 Network table 97 status
618 Network table 98 status
619 Network table 99 status
Address Contents

$s514: Sets the executing status of the macro.
In the case of “0,” the next step of the macro is executed without waiting for the completion of the command when a command request is given to the Ethernet. In the case of other than “0,” the wait status continues until the command completes, and then the next step of the macro is executed. $s515: Stores the result of macro execution. An error occurs if a value other than “0”
is stored. For more information, refer to the error codes (page 4-47). However, when $s514 is “0,” the data before the command request is stored.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Network table use status
Macro command execution status Command execution status
- Bit 0 (Network table use status)
[0]: Not used [1]: Used For the current station, “0” (not used) is input.
- Bit 1 (Macro command execution status)
Stores the execution status of macro command [SEND], [EREAD] or [EWRITE]. [0]: Waiting [1]: Executing
- Bit 2 (Command execution status)
Stores the execution status of the command from the server or other station. [0]: Waiting [1]: Executing (read/write command)
- Bit 3 (Macro command execution result)
Stores the execution result of macro command [SEND], [EREAD] or [EWRITE]. [0]: Normal [1]: Error
- Bits 4 to 15 (System reserved)
Not used at present. Always set “0.”
Not used · Command execution result
![Page 177 of the Epson Endeavor V7 user manual — [VBA]](/cdn/reader/b8/b8449522b609f1ec53cca0ce6668e2b08023edbd18c283275a97f522d49d7dd5/images/page-177.webp?w=400)
4-26 1. Ethernet
To enable Ethernet communications between the server and the V7 series, it is necessary to create an application based on HKEtn10.dll (for UDP/IP) provided by us, using Visual C++, Visual Basic, etc.
The “Sample” folder for Ethernet communications is included in the V-SFT CD-ROM. The [Ethernet] folder contains sample programs created using Visual C++, and the [VBA] folder contains those created using VBA. Refer to these sample program when creating an application. If necessary, you can copy and tailor the program to your requirements.
- ESmpl.dsp - ESmpl.h - ESmpl.cpp - ESmpl.rc - ESmpl.clw - MainFrm.h - MainFrm.cpp - ESmplDoc.h - ESmplDoc.cpp - ESmplView.h - ESmplView.cpp - StdAfx.h - StdAfx.cpp - Resource.h - ReadMe.txt - HKEtn10.h
- HKEtn10.dll - HKEtn10.lib
- ESmpl.ico - ESmpl.rc2 - Toolbar.bmp - ESmplDoc.ico
- HKEtn10.dll - VBA_Sample.xls
* To execute this program, copy the above files to the “C:\TEST” folder. Port No. 10000 and IP address 192.168.1.52 are set. When changing the copy target, the port number or the IP address, change the setting in the program accordingly.

DWORD
Network Communications
Data Type Bytes Data Range
BYTE 1 0 to 255
short 2 −32768 to 32767
unsigned short 2 0 to 65535
int 4 −2147483648 to 2147483647
long 4 −2147483648 to 2147483647
WORD 2 0 to 65535
DWORD 4 0 to 4294967295
char 1 −128 to 127
Data Type Bytes Data Range
Byte 1 0 to 255
Boolean 2 TRUE(0) / FALSE(−1)
Integer 2 −32768 to 32767
Long 4 −2147483648 to 2147483647
Double 8 4.94E−324 to 1.79E+308
String Variable 0 to 2 GB

4-28 1. Ethernet
int HKEtn_ReadPlcMemory(WORD *dp,unsigned short Wordcnt,int DeviceType,DWORD addr,char *lpAddr,int DFlag=1) Page 4-29
int HKEtn_ReadPlcMemory2(DWORD *dp,unsigned short Wordcnt,int DeviceType,DWORD addr,char *lpAddr,int DFlag=1) Page 4-30
int HKEtn_ReadInternalMemory(WORD *dp,unsigned short Wordcnt,int DeviceType,DWORD addr,char *lpAddr,int DFlag=1) Page 4-31
Memory card memory Word
int HKEtn_ReadCardMemory(WORD *dp,unsigned short Wordcnt,int FileNo,int RecordNo,DWORD addr,char *lpAddr,int DFlag=1) Page 4-32
int HKEtn_ReadPlcBitMemory(int *lpOnFlag,int DeviceType,DWORD addr,int BitNo,char *lpAddr) Page 4-33
int HKEtn_ReadInternalBitMemory(int *lpOnFlag,int DeviceType,DWORD addr,int BitNo,char *lpAddr)
Page 4-34 Memory card memory Bit
int HKEtn_ReadCardBitMemory(int *lpOnFlag,int FileNo,int RecordNo,DWORD addr,int BitNo,char *lpAddr)
PLC memory Word (block)
int HKEtn_ReadBlockMemory(WORD *sp,BYTE *pReadblockData,int BlockCnt,char *lpAddr) Page 4-34
int HKEtn_WritePlcMemory(WORD *sp,unsigned short Wordcnt,int DeviceType,DWORD addr,char *lpAddr,int DFlag=1) Page 4-35
int HKEtn_WritePlcMemory2(DWORD *sp,unsigned short Wordcnt,int DeviceType,DWORD addr,char *lpAddr,int DFlag=1) Page 4-36
int HKEtn_WriteInternalMemory(WORD *sp,unsigned short Wordcnt,int DeviceType,DWORD addr,char *lpAddr,int DFlag=1) Page 4-37
Memory card memory Word
int HKEtn_WriteCardMemory(WORD *sp,unsigned short Wordcnt,int FileNo,int RecordNo,DWORD addr,char *lpAddr,int DFlag=1) Page 4-38
int HKEtn_WritePlcBitMemory(int DeviceType,DWORD addr,int BitNo,int OnFlag,char *lpAddr) Page 4-39
int HKEtn_WriteInternalBitMemory(int DeviceType,DWORD addr,int BitNo,int OnFlag,char *lpAddr)
Page 4-40 Memory card memory Bit
int HKEtn_WriteCardBitMemory(int FileNo,int RecordNo,DWORD addr,int BitNo,int OnFlag,char *lpAddr)
Initialization function int HKEtn_Init(unsigned short Port=10000,int Retry=3,int RecvTime=2,int RecvTime2=10) Page 4-41 Receive wait from V7 int HKEtn_Recvfrom(BYTE *dp,short *lpCnt)
Cancel receive wait function void HKEtn_Cancel(void)
Request connection information int HKEtn_GetInf(struct inf *lpinf,char *lpAddr)
Close processing int HKEtn_Close()
Get source’s IP Address int HKEtn_GetSinAddr(char *lpAddr)
Get error contents int HKEtn_GetLastError() Page 4-43

int HKEtn_ReadPlcMemory(WORD *dp,unsigned short Wordcnt,int DeviceType,DWORD addr,char *lpAddr, int DFlag=1)
This function is retained until PLC data is transferred from the V7 series.
No. 1 1
No. 2 1
Wordcnt Word count to be read (max. 2000 words) DeviceType Address of the device to be read (Refer to “Chapter 5 Connection to PLCs.”) addr Top memory address to be read For YOKOGAWA or YASKAWA PLCs, specify a number “−1” for the address (addr). Example: D400 → 399 D25 → 24 *lpAddr IP address shown as a string of characters separated by dots Example: “192.168.XXX.XXX” DFlag 0, 1, 2 (Refer to the table below.)
DFlag Priority Communication Procedure
V7 PLC Memory card
V7 PLC Memory card

4-30 1. Ethernet
int HKEtn_ReadPlcMemory2(DWORD *dp,unsigned short Wordcnt,int DeviceType,DWORD addr,char *lpAddr, int DFlag=1)
This function is retained until PLC data is transferred from the V7 series.
No. 1 2
No. 2 2
Wordcnt Word count to be read (max. 1000 words)
DeviceType Address of the device to be read (Refer to “Chapter 5 Connection to PLCs.”) addr Top memory address to be read For YOKOGAWA or YASKAWA PLCs, specify a number “−1” for the address (addr). Example: D400 → 399 D25 → 24 *lpAddr IP address shown as a string of characters separated by dots Example: “192.168.XXX.XXX” DFlag 0, 1, 2 (Refer to page 4-29.)
Contents Word Count

int HKEtn_ReadInternalMemory(WORD *dp,unsigned short Wordcnt,int DeviceType,DWORD addr,char *lpAddr,int DFlag=1)
This function is retained until data is transferred from the V7 series.
No. 1 1
No. 2 1
Wordcnt Word count to be transferred (max. 2000 words) DeviceType 0: $u 1: $s addr Top memory address to be read *lpAddr IP address shown as a string of characters separated by dots Example: “192.168.XXX.XXX” DFlag 0, 1, 2 (Refer to page 4-29.)
Contents Word Count

4-32 1. Ethernet
int HKEtn_ReadCardMemory(WORD *dp,unsigned short Wordcnt,int FileNo,int RecordNo,DWORD addr,char *lpAddr,int DFlag=1)
This function is retained until data is transferred from the V7 series.
No. 1 1
No. 2 1
Wordcnt Word count to be transferred (max. 2000 words) FileNo File number RecordNo Record number addr Top memory address to be read *lpAddr IP address shown as a string of characters separated by dots Example: “192.168.XXX.XXX” DFlag 0, 1, 2 (Refer to page 4-29.)
Contents Word Count

int HKEtn_ReadPlcBitMemory(int *lpOnFlag,int DeviceType,DWORD addr,int BitNo,char *lpAddr)
This function is retained until PLC data is transferred from the V7 series.
DeviceType 0 addr 20 BitNo 5 Example 2: When accessing to M20 of MITSUBISHI PLC
20 ÷ 16 = 1 ... 4 DeviceType 6 addr 1 BitNo 4 *lpAddr IP address shown as a string of characters separated by dots Example:“192.168.XXX.XXX”
int HKEtn_ReadInternalBitMemory(int *lpOnFlag,int DeviceType,DWORD addr,int BitNo,char *lpAddr)
This function is retained until data is transferred from the V7 series.

4-34 1. Ethernet
int HKEtn_ReadCardBitMemory(int *lpOnFlag,int FileNo,int RecordNo,DWORD addr,int BitNo,char *lpAddr)
This function is retained until data is transferred from the V7 series.
int HKEtn_ReadBlockMemory(WORD *sp,BYTE *pReadblockData,int BlockCnt,char *lpAddr)
This function is retained until data is transferred from the V7 series.
Word Count 2 bytes
Source PLC memory 9 bytes
BlockCnt Block count to be read *lpAddr IP address shown as a string of characters separated by dots Example: “192.168.XXX.XXX”

int HKEtn_WritePlcMemory(WORD *sp,unsigned short Wordcnt,int DeviceType,DWORD addr,char *lpAddr, int DFlag=1)
This function is retained until write completion is received from the V7 series. (It is reset on receipt of write completion to the PLC memory.)
No. 1 1
No. 2 1
Wordcnt Word count to be transferred (max. 2000 words) DeviceType Address of the device to be written (Refer to “Chapter 5 Connection to PLCs.”) addr Top memory address to be written For YOKOGAWA or YASKAWA PLCs, specify a number “−1” for the address (addr). Example: D400 → 399 D25 → 24 *lpAddr IP address shown as a string of characters separated by dots Example: “192.168.XXX.XXX” DFlag 0, 1, 2 (Refer to page 4-29.)
Contents Word Count

4-36 1. Ethernet
int HKEtn_WritePlcMemory2(DWORD *sp,unsigned short Wordcnt,int DeviceType,DWORD addr,char *lpAddr, int DFlag=1)
This function is retained until write completion is received from the V7 series. (It is reset on receipt of write completion to the PLC memory.)
No. 1 2
No. 2 2
Wordcnt Word count to be transferred (max. 1000 words) DeviceType Address of the device to be written (Refer to “Connection to PLCs.”) addr Top memory address to be written For YOKOGAWA or YASKAWA PLCs, specify a number “−1” for the address (addr). Example: D400 → 399 D25 → 24 *lpAddr IP address shown as a string of characters separated by dots Example: “192.168.XXX.XXX” DFlag 0, 1, 2 (Refer to page 4-29.)
Contents Word Count

int HKEtn_WriteInternalMemory(WORD *sp,unsigned short Wordcnt,int DeviceType,DWORD addr,chr *lpAddr,int DFlag=1)
This function is retained until write completion is received from the V7 series. (It is reset on receipt of write completion to the internal memory.)
No. 1 1
No. 2 1
Wordcnt Word count to be transferred (max. 2000 words) DeviceType 0: $u 1: $s addr Top memory address to be written *lpAddr IP address shown as a string of characters separated by dots Example: “192.168.XXX.XXX” DFlag 0, 1, 2 (Refer to page 4-29.)
Contents Word Count

4-38 1. Ethernet
int HKEtn_WriteCardMemory(WORD *sp,unsigned short Wordcnt,int FileNo,int RecordNo,DWORD addr,char *lpAddr,int DFlag=1)
This function is retained until write completion is received from the V7 series. (It is reset on receipt of write completion to the memory card memory.)
No. 1 1
No. 2 1
Wordcnt Word count to be transferred (max. 2000 words) FileNo File number RecordNo Record number addr Top memory address to be written *lpAddr IP address shown as a string of characters separated by dots Example: “192.168.XXX.XXX” DFlag 0, 1, 2 (Refer to page 4-29.)
Contents Word Count

int HKEtn_WritePlcBitMemory(int DeviceType,DWORD addr,int BitNo,int OnFlag,char *lpAddr)
This function is retained until write completion is received from the V7 series. (It is reset on receipt of write completion to the PLC memory.)
DeviceType 0 addr 20 BitNo 5 Example 2: When accessing to M20 of MITSUBISHI PLC
20 ÷ 16 = 1 ... 4 DeviceType 6 addr 1 BitNo 4 OnFlag 0: OFF 1: ON *lpAddr IP address shown as a string of characters separated by dots Example: “192.168.XXX.XXX”

4-40 1. Ethernet
int HKEtn_WriteInternalBitMemory(int DeviceType,DWORD addr,int BitNo,int OnFlag,char *lpAddr)
This function is retained until write completion is received from the V7 series. (It is reset on receipt of write completion to the internal memory.)
int HKEtn_WriteCardBitMemory(int FileNo,int RecordNo,DWORD addr,int BitNo,int OnFlag,char *lpAddr)
This function is retained until write completion is received from the V7 series. (It is reset on receipt of write completion to the memory card memory.)

int HKEtn_Init(unsigned short Port=10000,int Retry=3,int RecvTime=2,int RecvTime2=10)
Creates a socket.
Receive Wait from V7
int HKEtn_Recvfrom(BYTE *dp,short *lpCnt)
This function is retained internally until data is received from the V7 series. The function returns a response and ends only when a command is received. The user should interpret the received data and create the next action. This function must be executed within the thread.
void HKEtn_Cancel(void)
Cancels the function in the receive wait status, such as Recvfrom().

4-42 1. Ethernet
int HKEtn_GetInf(struct inf *lpinf,char *lpAddr)
int HKEtn_Close()
Execute this function when ending HKEtn10.dll.
int HKEtn_GetSinAddr(char *lpAddr)
Execute this function after the recvfrom() function or receiving the data.

int HKEtn_GetLastError()
−1 Undefined command (receive timeout) Check the command.
−2 Undefined IP address Check the IP address.
−3 Target station busy Reduce the frequency of communications.
−4 Illegal packet bytes Check response processing at the target station.
−5 Packet bytes exceed the maximum number.
Reduce the send packet size.
−6 Local mode error Check that the target station is in the RUN mode.
−7 Preparing for communications Start communications when the target station is ready.
−8 Communication failure – Cannot access Check the target station.
−9 Cannot process due to short memory Check the memory space at the target station.
−10 Illegal received data Check the command.
−20 Socket initialization error Check parameters for initialization.
−50 Requested packet byte exceeds the maximum number.
Reduce the requested size.
−51 Address error Check the requested memory type.
−52 Communication failure – Cannot access Check the target station.
−54 Write protected Check write-protection of the card.
−55 Cannot process due to short memory Check the memory space at the target station.
−56 Sampling buffer error Check the command.
−100 Processing another command Continue retrying.
−101 Command control – Buffer over Reduce the frequency of communications.
−120 Communications aborted by the user Communications are forcedly aborted.
−121 Received during command processing Reduce the frequency of communications.
Code Contents Solution

4-44 1. Ethernet
(1) Execute the receive wait thread using
“int HKEtn_RecvFrom()” on the application of the server. (2) Send the command from the V7 series

to the server using macro command SEND. (3) The server analyzes the command
Packet bytes 2 + 2 + 1 + n bytes 2
(1) A request is sent from the application of the server to the V7 series. Use “int HKEtn_ReadPlcMemory()” for a memory request. (2) (3) The V7 series reads the PLC

memory. (4) The V7 series returns data read from the PLC memory to the server.
Server · Server

Error messages displayed on the V7 series and those stored in the system memory are explained.
The Ethernet status is stored in system memory address $s518 of the V7 series during Ethernet communications. The communication error occurs when a code other than “0” (normal) is stored in system memory address $s518.

* When [Continue] is selected for [Comm. Error Handling] in the [Detail] tab window of the [Comm. Parameter] dialog, a following screen is displayed.
Main Menu V 7 1 0 i T D

4-46 1. Ethernet
No. Contents Solution
200 Failed in send request Check cable connection and network table setting of the target station.
201 Send error Check that the setting on the target station is consistent with the network table setting.
202 Internal port error The communication unit is in the older version or is faulty.
The number of connections reaches the maximum, and no more connection is possible. Check the communication lines.
204 TCP connection over
205 TCP connection error Connection cannot be established. Check the communication lines, or turn the power off and on.
TCP communication disconnection has failed. Check that the communication partner with the V7 series is present on the line.
206 TCP connection end error
207 TCP send error TCP sending has failed. Check the communication lines.
350 Send buffer full The line is busy. Consult the network administrator of your company. The communication unit is in the older version or is faulty. 351 IC receive buffer overflow
352 Driver receive buffer overflow
Check the HUB or the link confirmation LED on the communication unit. If the LED is not on, check cable connection and the port setting on the network table.
801 Receive processing error, link down error
802 Transceiver error Check the transceiver and cable connection.
900 No IP address at local port Check that the IP address of the local port is set on the network table. Check if the same IP address is set on the network. 901 Duplicated IP address error
902 Send socket ID error (error that may occur when V7i LAN port is used)
Turn the power off and back it on. If the problem persists, contact your local distributor.
1000 Ethernet I/F unit not mounted
1001 Ethernet I/F unit not ready
1002 Ethernet I/F unit DPRAM error
1003 No response from Ethernet I/F unit
1004 Ethernet receive buffer over
Check whether the Ethernet I/F unit is mounted correctly, and then turn the power off and on. If the problem persists, contact your local distributor.
1005 Ethernet send registration error
1006 I/F unit unregistered interrupt
1100 - 1115 Initialization error (communication unit)
1120 Dual port access error
1201 Send/receive buffer area over
1202 MAC address error
1203 Port error Check whether the Ethernet I/F unit is mounted correctly, and then turn the power off and on. If the problem persists, contact your local distributor. 1301 Watch dog overflow
1302 JAVA error LANC error
0 Normal · 1200 Undefined register

The execution result of macro commands SEND/EREAD/EWRITE is stored in system memory address $s515.
−30 Timeout Check if an error is occurring to the target V7.
−31 The number of words being sent exceeds the limit.
Check the number of words that can be sent in macro editing.
−32 Specified table not used Check the setting on the network table.
−33 Cannot use the send command. Check the macro command in macro editing.
−34 Specified table being used Check that system memory address $s514 is set. If not, reduce the frequency of communications.
−35 Cannot process due to short memory Check the memory space at the target station.
−36 Illegal receive packet bytes Check the requested number of words.
−37 Memory access error Check the setting of the requested memory.
−38 Macro setting error Check the macro setting.
Code Contents Solution · 0 Normal

4-48 2. FL-net (OPCN-2)
FL-net (OPCN-2)


3. MELSECNET/10
MELSECNET/10
Control station (1Mp1) Normal station (1Ns2)

Normal station (1Ns4) Normal station (1Ns3)

Fiber-optic cable

Control station (1Mp1) Normal station (1Ns2)
below:

(Station that sends a request)

Transient transmission is slower than cyclic transmission (2- or 3-times longer response time than cyclic transmission). To achieve high-speed communications, use cyclic transmission.

CC-Link


5. OPCN-1
OPCN-1



6. T-LINK
T-LINK
Write request to the PLC

Read request to the PLC

7. PROFIBUS-DP
PROFIBUS

The V7 series can work as a slave station on PROFIBUS-DP. A maximum of 12 Mbps is available (automatically set to the BUS baud rate). The signal level is RS-485.
* The V7 series can only communicate with the master PLC.

Master · Slave


2. OMRON PLC*
3. SHARP PLC*
4. HITACHI PLC
5. MATSUSHITA PLC
6. YOKOGAWA PLC*
7. YASKAWA PLC
10. KOYO PLC
14. TOSHIBA MACHINE PLC
15. SIEMENS PLC
16. SHINKO PLC
17. SAMSUNG PLC
18. KEYENCE PLC
19. LG PLC
20. FANUC PLC
21. FATEK AUTOMATION PLC
22. IDEC PLC
23. MODICON PLC
24. YAMATAKE PLC
25. TAIAN PLC
26. SAIA PLC
27. MOELLER PLC
* Indicates manufacturers who support PLC2Way connection at the MJ port. For the applicable PLC models, refer to the “PLC2Way” column in “Available PLCs.” ( : connectable, ×: not connectable)



1. MITSUBISHI PLC
Available PLCs
A Series Link, QnA Series Link, QnH (Q) Series Link, A Link + Net10*1
Select PLC Type CPU Unit/Port Connection PLC2Way
A2A, A3A
AJ71C24-S8
AJ71UC24 RS-232C [Wiring Diagram 2]
AJ71C24
A1, A2, A3 A1N, A2N, A3N A3H, A3M, A73
Connection to PLCs
AJ71C24-S6
AJ71C24-S8 RS-422 [Wiring Diagram 5]
A0J2, A0J2H A0J2C214-S1
A1SJ71UC24-R2 RS-232C [Wiring Diagram 1]
A1SJ71UC24-R4 RS-422 [Wiring Diagram 5]
A1SJ71UC24-PRF RS-232C [Wiring Diagram 1]
A1SJ71C24-R2 RS-232C [Wiring Diagram 1]
A1SJ71C24-R4 RS-422 [Wiring Diagram 5]
A1SJ71C24-PRF RS-232C [Wiring Diagram 1]
A2CCPUC24 CPU built-in link port RS-232C [Wiring Diagram 1]
A1SJ71UC24-R2 RS-232C [Wiring Diagram 1]
A1SJ71UC24-R4 RS-422 [Wiring Diagram 5]
RS-232C [Wiring Diagram 2]
RS-422 [Wiring Diagram 5]
RS-232C [Wiring Diagram 2]
QnA series link Q2A, Q3A, Q4A Q2ASx
RS-422 [Wiring Diagram 5]
RS-232C [Wiring Diagram 1]
RS-422 [Wiring Diagram 5]
AJ71QC24-R4(CH1) RS-422 [Wiring Diagram 6]
AJ71QC24-R4(CH2) RS-422 [Wiring Diagram 5]
RS-232C [Wiring Diagram 1]
QnH (Q) series link QnH (Q mode) QJ71C24
RS-422 [Wiring Diagram 5]
A link + Net10 Communication link unit for A series link*1
*1 For more information on A link + Net10, refer to page 5-15.
A series link · QnH (A mode)

A Series CPU, QnA Series CPU, QnH Series CPU
Select PLC Type CPU Unit/Port Connection PLC2Way
A2A, A3A A2U, A3U, A4U A2US(H) A1N, A2N, A3N A3V, A73 A3H, A3M A0J2H A1S(H), A1SJ(H), A2S(H) A2CCPUC24 A1FX
Hakko Electronics’ cable “MB-CPUQ” or
QnA series CPU Q2A, Q3A, Q4A Q2AS(H)
QnH (A) series CPU Q06H-A
Q02, Q02H Q06H Q12H Q25H
Hakko Electronics’ cable “QCPU2” QnH (Q) series CPU
*1 For more information of V-MDD (dual port interface), refer to page 5-17. *2 For the ladder transfer function used when directly connecting the QnH series CPU, refer to page 5-18.

FX Series
Select PLC Type CPU Unit/Port Connection PLC2Way
Hakko Electronics’ cable “PC-CX24A” RS-422
FX1/2 Tool port*1
Hakko Electronics’ cable “MB-CPUQ”
RS-422
Hakko Electronics’ cable “MI4-FX” or Hakko Electronics’ cable “MB-CPUQ”
FX2NC
FX1S series CPU FX1S
+ MITSUBISHI’s conversion cable “FX-20P-CADP”
FX2N-232-BD RS-232C [Wiring Diagram 3]
FX2N-485-BD RS-485 [Wiring Diagram 8]
FX2N-422-BD RS-422 Hakko Electronics’ cable “MI4-FX”
FX1N-232-BD RS-232C [Wiring Diagram 3]
FX1N-485-BD RS-485 [Wiring Diagram 8]
FX series link (A Protocol)
FX1N-422-BD RS-422 Hakko Electronics’ cable “MI4-FX”
FX0N-232ADP RS-232C [Wiring Diagram 4]
FX0N-485ADP RS-485 [Wiring Diagram 8]
FX0N-232ADP RS-232C [Wiring Diagram 4]
FX0N-485ADP RS-485 [Wiring Diagram 8]
*1 For more information of V-MDD (dual port interface), refer to page 5-17.

Communication Setting
The recommended communication parameter settings of the PLC and the V7 series is as follows:
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 19200 bps 19200 bps
Port 0 for both stations ×10, ×1 0
RS-232C MODE1 Trans. Mode 1
RS-422 MODE5 Trans. Mode 1
Data length 7 7
Stop bit 1 1
Sumcheck Provided (fixed) −
Write while running Possible (fixed) −
Terminating resistance at sender Provided (fixed) −
Terminating resistance at receiver Provided (fixed) −
*1 Trans. Mode 1: without CR/LF, Trans. Mode 4: with CR/LF If [Trans. Mode 4] is selected for [Trans. Mode] in the [Comm. Parameter] dialog of the V7 series, select [MODE4] in the case of RS-232C, or [MODE8] in the case of RS-422.
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate* 19200 bps 19200 bps
Port 0 for both stations ×10, ×1 0
MODE5 (binary mode) (fixed) − RS-422
Data length 8 (fixed) −
Stop bit 1 1
Sumcheck Provided (fixed) −
Write while running Possible (fixed) −
* The maximum baud rate available with the V7 series is 115200 bps. Select the appropriate baud rate depending on the used PLC and environment.
Communication parameters for the V7 series are automatically set.

QnH (A) Series CPU, QnH(Q) Series CPU
Communication parameters for the V7 series except the baud rate are automatically set.
* The maximum baud rate available with the V7 series is 115200 bps. Select the appropriate baud rate depending on the used PLC and environment.
Communication parameters for the V7 series are automatically set.
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 19200 bps 19200 bps
Data length 7 7
Stop bit 1 1
Protocol Special protocol communication
H/W type*1 Normal/RS-232C RS-232C
Sumcheck Added (fixed) −
Transmission mode Mode 1 Trans. Mode 1
*1 Select RS-485 when the link unit FX2N-485-BD, FX2N-422-BD, FX1N-485-BD, FX1N-422-BD or FX0N-485-ADP is used. * We recommend to set 2 ms or above for [Send Delay Time] in the [Detail] tab window of the [Comm. Parameter] dialog of the V7 series.
Parity Even Even · Transmission code · (fixed) −

A Series Link, QnA Series Link: Switch Setting
The following is an example that shows the settings for both rotary DIP switches and DIP switches on the PLC.
ON
9 A B C D E
9 A B C D E
9 A B C D E
F
F 0
F
SW11
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
SW13
SW14
SW15
SW16
ON OFF
SW17
SW18
SW21
SW22
SW23
SW24
A1SJ71C24-R2, A1SJ71UC24-R2
ON
9 A B C D E
9 A B C D E
9 A B C D E
F
F
F
SW03
0 1 2 3 4 5 6 7 8
0 1 2 3 4 5 6 7 8
0 1 2 3 4 5 6 7 8
SW05
SW06
SW07
ON OFF
SW08
SW09
SW10
SW11
SW12
AJ71QC24, A1SJ71QC24, AJ71QC24N
ON
9 A B C D E
9 A B C D E
9 A B C D E
F
F
F
SW01
0 1 2 3 4 5 6 7 8
0 1 2 3 4 5 6 7 8
0 1 2 3 4 5 6 7 8
SW03
SW04
SW05
SW06
ON OFF
SW07
SW08
SW09
SW10
SW11
SW12

A1SJ71UC24-R4, A1SJ71C24-R4
ON
9 A B C D E
9 A B C D E
9 A B C D E
F
F
F
SW01
SW02
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
SW04
SW05
ON OFF
SW06
SW07
SW08
SW09
SW10
SW11
SW12
Connection to PLCs

Available Memory
The available memory setting range varies depending on the PLC model. Be sure to set within the range available with the PLC to be used. Use [TYPE] when assigning the indirect memory for macro programs.
A Series Link, QnA Series Link, QnH (Q) Series Link, A Series CPU, QnA Series CPU, QnH (A) Series CPU, QnH (Q) Series CPU, A Link + Net10
D (data register) 0
W (link register) 1
R (file register) 2 *1
TN (timer/current value) 3
CN (counter/current value) 4
SPU (special unit) 5 *2
M (internal relay) 6
L (latch relay) 7
B (link relay) 8
X (input relay) 9
Y (output relay) 10
H (link unit buffer memory) 15
SD (special register) 16 QnA, QnH (Q) series only (both link unit and CPU)
SM (special relay) 17 QnA, QnH (Q) series only (both link unit and CPU)
SB (special link relay) 18 QnA, QnH (Q) series only (both link unit and CPU)
SW (special link register) 19 QnA, QnH (Q) series only (both link unit and CPU)
ZR (file register (continuous access)) 20 QnA, QnH (Q) series only (both link unit and CPU)
*1 When the A series CPU is in ROM operation, R register cannot be used. *2 The unit number is required in addition to the memory type and address. Convert byte address into word address when entering the data on the V-SFT editor if the memory device of link unit is given byte address.

FX Series, FX1S Series
D (data register) 0
TN (timer/current value) 1
CN (counter/current value) 2
32CN (counter 32 bits) 3 *1
M (internal relay) 4
X (input relay) 6 Read only
Y (output relay) 7
DX (data register) 10 *2
*1 For numerical data format where double-words can be used (Num. Data Display, Graph, Sampling), data is processed as double-words. For those where bits or words can be used, data is processed as words consisting of lower 16 bits.
For input Upper 16 bits are ignored. For output “0” is written for upper 16 bits. *2 Use DX for D1000 to 2999.
D (data register) 0
TN (timer/current value) 1
CN (counter/current value) 2
32CN (counter 32 bits) 3 *1
M (internal relay) 4
X (input relay) 6 Read only
Y (output relay) 7
*1 For numerical data format where double-words can be used (Num. Data Display, Graph, Sampling), data is processed as double-words. For those where bits or words can be used, data is processed as words consisting of lower 16 bits.
For input Upper 16 bits are ignored. For output “0” is written for upper 16 bits.

FX Series (A Protocol)
D (data register) 0
TN (timer/current value) 1
CN (counter/current value) 2 *1
32CN (counter 32 bits) 3 *2
M (internal relay) 4
X (input relay) 6 Read only
Y (output relay) 7
*1 CN200 to CN255 equals 32CN (32-bit counter). *2 For numerical data format where double-words can be used (Num. Data Display, Graph, Sampling), data is processed as double-words. For those where bits or words can be used, data is processed as words consisting of lower 16 bits.
For input Upper 16 bits are ignored. For output “0” is written for upper 16 bits.

Wiring
Wiring diagrams with the PLC are shown below.
V7 (CN1)
CD 1
RD
RD
RS
SD
CS
SG
SG
DR
Connection to PLCs
RS
8 * Use shielded twist-pair cables.
V7 (CN1)
SD
RD
RD
RS
RS
CS
CS
SG
DR
SG
8 CD * Use shielded twist-pair cables.

V7 (CN1)
RD
RD
SD
RS
SG
CS
SG
* Use shielded twist-pair cables.
SD
RD
RD
RS
SG
CS
SG
* Use shielded twist-pair cables.
V7 (CN1)
PLC
SG
SDA
+SD
SDB
-SD
RDA
+RD
RDB
-RD
SG
* Use shielded twist-pair cables.

V7 (CN1)
RDA
+SD
SDA 3
-SD
DSRA
+RD
DTRA
-RD
SG
RDB
SDB 16
DSRB
DTRB
Connection to PLCs
* Use shielded twist-pair cables.
+SD
-SD
4 +DSR
+RTS
5 +DTR
-RTS
SG
-CTS
+CTS
+RD
17 -DSR
-RD
-DTR
* Use shielded twist-pair cables.

According to our noise tests, the attachment of a ferrite core improves noise voltage by 650 to 900 V and aids in preventing communication errors. • When connecting to the A/QnA series CPU directly, attach a ferrite core to the communication cable between the V7 series and A/QnA series CPU to avoid noise problems.
Ferrite core A/QnA series
PLC
SG
RDA
+SD
SDA 3
-SD
SG
+RD
RDB
-RD
SDB 16
* Use shielded twist-pair cables.
V7 series · Wiring Diagram 8 · D-sub 25-pin (male)

A Link + Net10
CPU equipped with the standard type link unit that is connected to the V7 series. (Available CPU No. 0 to 30) - With NET/10, the V7 series can have access to CPUs in the network (No. 1 in the
illustration below) of the CPU equipped with the standard type link unit that is connected to the V7 series as well as those in the other networks (Nos. 2 and 3 in the illustration below) that are connected. (Available CPU No. 1 to 30)
F1
F2
F3
F4
F5
Connection to PLCs
F6
F7
POWER
CPU (1-1)
CPU (2-1)
CPU (1-5)
CPU (2-5)
CPU (1-2) (2-2)
Network No. 1 Network No. 2
CPU (1-4)
CPU (1-3)
CPU (2-3) (3-1)
CPU (2-4)
CPU (3-2)
CPU (3-5)
Network No. 3
CPU (3-4)
When the V7 series reads from or writes to the CPU memory of the CPU number other than “31”: Transient transmission is performed and the response time is not fast. Please understand beforehand.
Standard type link · unit

n + 0 Always 0
n + 2 System code
n + 3 Network number
“n + 0” and “n + 1” are fixed to “0” and “2,” respectively. “n + 2” (system code) should be: 1: NET/10 2: NET II (/B) For “n + 3” (network number), set “0” when NET II (/B) is selected for “n + 2” (system code) or the network number to be accessed when NET/10 is selected.
Do not use this macro for any purpose other than OPEN macro for a screen. Doing so triggers network switching at the time of macro execution, resulting in a communication error.
For more information on the macro function, refer to the Reference Manual (Function). Also refer to the explanation on network registration contained in the operation manual for MITSUBISHI’s Standard Link/Multi-drop Link Unit.
For the available memory of the PLC to be accessed, refer to “Available Memory” page 5-8. Note that the CPU number must be set on the V-SFT editor.
Refer to the wiring diagram with the standard type link unit.
F1 memory

V-MDD (Dual Port Interface)
V-MDD is the add-on connector with two ports, specifically designed for the connector on MITSUBISHI’s A series, QnA series or FX series CPU programmer.

When connecting to the CPU of MITSUBISHI A/QnA series:
Insert the connector on the backside into the CPU port directly or use the MDD-CPU (optional) cable for connection. When connecting to the CPU of MITSUBISHI FX1/2 series:
Use the MDD-CPU cable (optional) for connection. When connecting to the CPU of MITSUBISHI FX2N/1N/0N/1S series:
MB-CPUQ cable (optional) Slide switch 1: A series 2: QnA series 3: FX series
* Set the slide switch before turning the power on.
V-MDD cannot be used with the MI4-FX cable.
MITSUBISHI A/QnA/FX series

Ladder Transfer Function
Up until now it was necessary to debug the data by removing and mounting two cables repeatedly as shown below when the V7 series is directly connected to MITSUBISHI’s QnHCPU equipped with only one RS-232C port.

When using the ladder transfer function by connecting the computer (PLC programming software) to the V7 series, it is possible to write ladder programs or monitor the PLC memory using the V7 series.

Q02, Q02H, Q06HCPU port (Q mode)
Connecting cable · MITSUBISHI PLCs

Connection

- When using two V6-CP cables:
When the computer has two COM ports, use one port for the V-SFT editor and the other port for the PLC programming software. Use the V6-CP cables. (It is not possible to transfer the V-SFT editor and the PLC programming software at the same time.)

software and the PLC Communications between the V-SFT editor and V7
- When using one V6-CP cable:
When using the V-SFT editor and the PLC programming software, it is not possible to use one COM port for both purposes at the same time. Stop using both software for communications.
COM1
MELSEC CN1 MJ1 RS-232C
GPPW (V-SFT)
SYSTEM
F1
F2
F3
F4
F5
RESET
F6
F7
POWER
V7 series Computer (PC) MITSUBISHI QnH series
disc

Settings and Communications

* On-line editing between the V-SFT editor and the V7 series is not possible. If attempted, communications between the PLC programming software and the PLC will not be performed correctly.
When communicating with the V-SFT editor, hold down the F2 switch for three seconds. [Editor: ...] changes to [Editor: MJ1] and communications with the V-SFT editor become possible.
Main Menu V 7 1 0 i T D
2002-4 -1 07:23:30
I/F DRV VER.1.240 MELSEC QnH Q CPU Port
Communications with the PLC programming software
Stat. No. : 192.168.1.68 PORT: 10000 MAC: 0050FF000035
Editor:MJ1
When the F2 switch is held down for three seconds, [Editor: MJ1] changes to [Editor: ...] and communications with the PLC programming software become possible.
V-SFT PLC programming software
Writing to V7 Communications disconnected (normal communications on completion of writing)
Reading from V7 Normal communications
Comparing with V7 Normal communications



2. OMRON PLC
Available PLCs
Type PLC Unit/Port Connection PLC2Way
CPU unit with built-in port (host link port)
RS-232C [Wiring Diagram 1]
RS-232C [Wiring Diagram 3]
RS-422 [Wiring Diagram 4]
C200H-LK201 C200H-LK201-V1 C200H-LK202 C200H-LK202-V1
RS-232C [Wiring Diagram 3]
RS-422 [Wiring Diagram 4]
C200HS-CPU21, 23 C200HS-CPU31, 33 CQM1-CPU21 CQM1-CPU41, 42, 43, 44
CPU unit with built-in port (host link port)
RS-232C [Wiring Diagram 2]
RS-232C [Wiring Diagram 3]
RS-422 [Wiring Diagram 4]
CPU unit with built-in port (host link port)
RS-232C [Wiring Diagram 2]
Mounted on the CPU slot (C200HW-COM02 to 06)
RS-232C [Wiring Diagram 2]
RS-422 [Wiring Diagram 5]
SRM1-C02 RS-232C interface RS-232C [Wiring Diagram 2]
CPM1A CPU unit (peripheral port)
OMRON’s cable [CQM1-CIF01]*1
RS-232C interface RS-232C [Wiring Diagram 2]
CPU unit (peripheral port)
OMRON’s cable [CQM1-CIF01]*1
OMRON’s adaptor unit [CPM2C-CIF01] + RS-232C [Wiring Diagram 2]
CPM2C CPU unit (peripheral port)
OMRON’s cable [CS1W-CN118] + RS-232C [Wiring Diagram 2]
Select PLC · (To be continued)

Type PLC Unit/Port Connection PLC2Way
CPU unit with built-in port (host link port)
RS-232C [Wiring Diagram 2]
RS-422 [Wiring Diagram 6]
RS-232C
SYSMAC CV
PORT1 [Wiring Diagram 3]
PORT2 [Wiring Diagram 2]
PORT2 [Wiring Diagram 5]
CPU unit (RS-232C port)
RS-232C [Wiring Diagram 2] CS1W-SCU21
Mounted on the CPU slot (CS1W-SCB21)
Mounted on the CPU slot (CS1W-SCB41) RS-422 [Wiring Diagram 7]
*1 Replace the shell on the D-sub 25-pin side before use. (Recommended part: DDK’s 17J-25) *2 For SYSMAC CS1 DNA, refer to page 5-29.
Select PLC

Communication Setting
The recommended communication parameter settings of the PLC and the V7 series is as follows:
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate* 19200 bps 19200 bps
Data length 7 (ASCII) 7
Stop bit 2 2
Command level 3 (fixed) −
Synchronizing switch Internal synchronization (fixed) −
CTS switch 0 V (always ON) (fixed) −
5 V supply switch OFF (fixed) −
Terminating resistance ON for RS-422 −
* The maximum baud rate available with the V7 series is 115200 bps. Select the appropriate baud rate depending on the used PLC and environment.
Set [Trans. Mode] in the [Detail] tab window of the [Comm. Parameter] dialog of the V-SFT editor.
Trans. Mode 1 BCD w/o sign
Trans. Mode 2 BCD w/ signs*1
*1 BCD w/ signs Data in the PLC memory can be shown as data with signs.
When higher 4 bits in the memory indicates [F] or [A], it is treated as negative.
[F]: Regards higher 4 bits as [−0]. [A]: Regards higher 4 bits as [−1].
PLC Memory Indication on V7
0000 to 9999 0 to 9999
F001 to F999 −1 to −999
A000 to A999 −1000 to −1999
00000000 to 99999999 0 to 99999999
F0000001 to F9999999 −1 to −9999999
A0000000 to A9999999 −10000000 to −19999999

Available Memory
The available memory setting range varies depending on the PLC model. Be sure to set within the range available with the PLC to be used. Use [TYPE] when assigning the indirect memory for macro programs.
DM (data memory) 0
CH (input/output relay) 1
HR (holding relay) 2
LR (latch relay) 3
AR (alarm relay) 4
T (timer/current value) 5
C (counter/current value) 6
EMn (extensional data memory) 7 *1
TU (timer/contact) 9 Read only
CU (counter/contact) 10 Read only
DM (data memory) 0
CH (input/output relay) 1
AR (alarm relay) 4
T (timer/current value) 5
C (counter/current value) 6 *1
EMn (extensional data memory) 7 Read only
TU (timer/contact) 9 Read only
DM (data memory) 0
CH (input/output relay) 1
H (holding relay) 2
A (alarm relay) 4
T (timer/current value) 5
C (counter/current value) 6
EMn (extensional data memory) 7 *1
W (internal relay) 8
TU (timer/contact) 9 Read only
CU (counter/contact) 10 Read only

*1 When using EMn (extended data memory), specify the bank number (CV: 0 to 7, CS1: 0 to C). The assigned memory is indicated when editing the screen as shown on the right.
Address Colon Bank number
Wiring diagrams with the PLC are shown below.
SD 2
SD
RD
RD 3
RS
RS
CS
CS
SG
SG
* Use shielded twist-pair cables.
SD 2
SD
RD
RD 3
RS
RS
CS
CS
SG
SG
* Use shielded twist-pair cables.

SD 2
SD
RD
RD 3
RS
RS
CS
CS
SG
SG
* Use shielded twist-pair cables.
Connection to PLCs
SG 7
RDB
+SD
SG 3
-SD
SDB
+RD
RDA
-RD
SDA
* Use shielded twist-pair cables.
SG 7 SG 9
+SD
RDB
-SD
RDA
+RD
SDB
-RD
SDA
* Use shielded twist-pair cables.

SG 7 SG 9
+SD
RDB
-SD
RDA
+RD
SDB
-RD
SDA
RS
CS * Use shielded twist-pair cables.
+SD
RDB
-SD
RDA
+RD
SDB
-RD
SDA
* Use shielded twist-pair cables.

SYSMAC CS1 DNA
When connecting the V7 series to CS1 on a network (Controller Link), the V7 series can also access another CS1 on the network.
CS1 (1-2)
Network No. 1 Network No. 2
CS1 (2-3)
CS1 (1-1)
CS1 (2-4)
SYSTEM
F1
F2
F3
F4
F5
F6
POWER
F7
Connection to PLCs
V-SFT Setting


Double-click.
V7 series

3. SHARP PLC
Available PLCs
Type CPU Unit/Port Connection PLC2Way
RS-422 [Wiring Diagram 4]
JW20 JW-31CUH JW-21CM RS-422 [Wiring Diagram 4]
JW70CU/JW100CU JW70CUH, JW100CUH Communication port on the CPU unit
RS-232C [Wiring Diagram 1]
JW22CU RS-422 [Wiring Diagram 3]
PG/COMM2
Communication port 1 on the CPU unit Communication port 2 on the CPU unit
RS-422
PG/COMM1
PG/COMM2
Communication Setting
The recommended communication parameter settings of the PLC and the V7 series is as follows:
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 19200 bps 19200 bps
Port 0 for STA.NO ×10, 1 for STA.NO ×1 1
RS-422 4-wire system (fixed) −
Data length 7 7
Stop bit 2 2
Error check Sumcheck (fixed) −
Transmission mode Command mode (fixed) −

JW Series: Link Unit Switch Setting
SW0 4 Command mode
SW1 1 Station address (lower half)
SW2 0 Station address (upper half)
SW3-1 OFF Not used
SW3-2 ON 4-wire system
SW3-3 OFF Not used
SW3-4 ON Even parity
SW7 ON Terminating resistance provided
JW100/70H COM Port, JW20 COM Port: System Memory Setting
The settings for communications with the V7 series should be made at the system memory as shown below.
System Memory Setting Contents
System Memory Setting Contents
- Communication port 2
System Memory Setting Contents

Available Memory
The available memory setting range varies depending on the PLC model. Be sure to set within the range available with the PLC to be used. Use [TYPE] when assigning the indirect memory for macro programs.
XXXXX (relay) 1 ] for word device
EXXXX (self diagnosis) 2
bXXXX (timer counter) 3
Fn (file register) 7 *1
*1 File Register Setting on V-SFT Editor Enter “file number” + “: (colon)” + address in order.
Address Colon File number
Memory TYPE Remarks · X9XXX (register) 0

Wiring
Wiring diagrams with the PLC are shown below.
SD 2
SXD
RD 3
RXD
RS
RTS 4
CS
CTS
SG
SG 7
Connection to PLCs
* Use shielded twist-pair cables.
SD 2
SD
RD
RD
RS
SG 7
CS
RTS
SG
CTS 12
* Use shielded twist-pair cables.

RS-422
+SD 12
+TXD
− SD
− TXD
+RD
+RXD 12
− RD
− RXD
* Use shielded twist-pair cables.
PLC
+SD 12
− SD
+RD
− RD
* Use shielded twist-pair cables.
+SD 12
+SD
− SD
+RD
+RD
− RD 10
− RD
− SD
* Use shielded twist-pair cables.

4. HITACHI PLC
Available PLCs
Select PLC Type PLC Unit/Port Connection
COMM-2H RS-232C [Wiring Diagram 1] RS-422 [Wiring Diagram 4]
Peripheral port 1 on the CPU module RS-232C [Wiring Diagram 1]
EH150 HITACHI’s EH-RS05 cable*1 + RS-232C [Wiring Diagram 1]
PERIPHERAL 1
RS-232C [Wiring Diagram 1] PERIPHERAL 2
On H-252C CPU module
HITACHI’s CNCOM-05cable*1 + RS-232C [Wiring Diagram 1]
S10 2α Interface on the CPU unit RS-422 [Wiring Diagram 5]
RS-232C connector on the CPU unit RS-232C [Wiring Diagram 2]
HIDIC-S10/2α S10 mini
LQE060 RS-232C [Wiring Diagram 3]
HIDIC-S10/ABS ABS*2 RS-422 [Wiring Diagram 5]
*1 When using the HITACHI’s EH-RS05 or CNCOM-05 cable, connect the cable shown in [Wiring Diagram 1] to the D-sub 15-pin side for communications with the V7 series. *2 Specify the absolute memory address. For more information, refer to the instruction manual for the PLC.
HIDIC H series

Communication Setting
The recommended communication parameter settings of the PLC and the V7 series is as follows:
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 19200 bps 19200 bps
Port 0 for both ST No ×10, ×1 0
RS-232C MODE7 Protocol 2 with port
RS-422 MODE9 Protocol 2 with port
Data length 7 (ASCII) 7
Stop bit 1 1
Sumcheck Provided (fixed) −
If the transmission mode is any type other than listed the above, set the mode as shown below.
Item Setting on PLC V7 Comm. Parameter Setting
Protocol 1 without port
Protocol 1 with port Protocol 2 without port
RS-422 MODE2 Protocol 1 with port*1
*1 Multi-link connection is not available.
The peripheral port setting should be “transmission control protocol 1 without port.” No other setting is available.
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 7 19200 bps

HIDIC-H: Switch Setting
Baud rate: 19200 bps MODE switch: To connect to both RS-232C and RS-422, set MODE switch to 9. RS-232C (protocol 2 without port) RS-422 (protocol 2 with port) ST No switch: “0” for both ×10, ×1 DIP switch
1 OFF Bit length
Same as that set on V7 (normally 19200 bps) 3 ON
5 ON With parity
7 OFF Stop bit 1
8 ON With sumcheck
Available Memory
The available memory setting range varies depending on the PLC model. Be sure to set within the range available with the PLC to be used. Use [TYPE] when assigning the indirect memory for macro programs.
WR (internal word output) 0
X (external bit input) 1 WX as word device
Y (external bit output) 2 WY as word device
L (bit CPU link area) 3 WL as word device
M (bit data area) 4 WM as word device
TC (timer counter/elapsed time) 5
TD (timer counter/contact) 7
WN (network input/output) 8

HIDIC-S10/2 α
FW (work register) 0
X (input relay) 1 XW as word device
Y (output relay) 2 YW as word device
R (internal relay) 3 RW as word device
G (global link) 4 GW as word device
K (keep relay) 5 KW as word device
T (on-delay timer contact) 6 TW as word device
U (one-shot timer contact) 7 UW as word device
C (up/down counter contact) 8 CW as word device
TS (on-delay timer set value) 9
TC (on-delay timer elapsed value) 10
US (one-short timer set value) 11
UC (one-shot timer elapsed value) 12
CS (up/down counter set value) 13
CC (up/down counter elapsed value) 14
DW (data register) 15
E (event register) 16 EW as word device
S (system register) 17 SW as word device
J (transfer register) 18 JW as word device
Q (receive register) 19 QW as word device
M (extensional internal register) 20 MW as word device
1A 4
1B 5
1D 7
Memory TYPE Remarks · Memory TYPE Remarks

Wiring
Wiring diagrams with the PLC are shown below.
SD 2
SD
RD
RD
CS
RS
SG 7
CS
DR
Connection to PLCs
PHL
SG
PV12
* Use shielded twist-pair cables.
FG
RD
RD
SD
RS
5 SG
CS
SG
* Use shielded twist-pair cables.

D-sub 25-pin (male) D-sub 9-pin (female)
CD 1
SD
RD
RD
SD
RS
ER
CS
SG
SG 7
DR
RS
CS
* Use shielded twist-pair cables.
FG 1
PLC
+SD 12
- RD
+RD
* Use shielded twist-pair cables.
Wiring Diagram 5 When connecting to the S10xα series, add a resistor of 50 Ω (1/2 W) as shown below.
PLC
+SD 12
UTX H
− SD
UTX L
+RD
URX H
− RD
URX L
* Use shielded twist-pair cables.

5. MATSUSHITA PLC
Available PLCs
Select PLC Type PLC Unit/Port Connection
FP1 RS-232C port on the CPU unit RS-232C [Wiring Diagram 1]
AFP3462 RS-232C [Wiring Diagram 1]
AFP3463 RS-422 [Wiring Diagram 4]
FP5 AFP5462 RS-232C [Wiring Diagram 1]
RS-232C tool port on the CPU unit RS-232C [Wiring Diagram 1]
AFP5462 RS-232C [Wiring Diagram 1]
RS-232C port on the CPU unit RS-232C [Wiring Diagram 1]
FP10S
AFP3462 RS-232C [Wiring Diagram 1]
AFP3463 RS-422 [Wiring Diagram 4]
RS-232C tool port on the CPU unit MATSUSHITA’s RS-232C cable AFC8513
RS-232C port on the CPU unit RS-232C [Wiring Diagram 3]
RS-232C tool port on the CPU unit MATSUSHITA’s RS-232C cable AFC8513
RS-232C port on the CPU unit RS-232C [Wiring Diagram 2]
The recommended communication parameter settings of the PLC and the V7 series is as follows:
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 19200 bps 19200 bps
Port [0] × 10, [1] × 1 1
Data bit 7 (ASCII) 7
Stop bit 1 1
Transmission mode Computer link function (fixed) −
Control signal Invalid (fixed) −
* If a tool port (the ladder port for RS-232C) is used, the range of PLC parameter setting is limited as below. Adjust the PLC parameter setting to communication parameter setting of the V7 series.
Baud rate: 9600, 19200bps (115 kbps available with FP2) Parity: Odd (fixed) Data bit: 8 (or 7, select “8” normally) Stop bit: 1 (fixed)
Parity Even Even · Transmission code

MEWNET: Link Unit Switch Setting
1 ON
Same as that set on V7 (normally 19200 bps) 2 OFF
5 ON With parity
7 OFF Stop bit 1
8 OFF CS, CD invalid
The available memory setting range varies depending on the PLC model. Be sure to set within the range available with the PLC to be used. Use [TYPE] when assigning the indirect memory for macro programs.
DT (data register) 0
X (external input relay) 1 WX as word device, read only
Y (external output relay) 2 WY as word device
R (internal relay) 3 WR as word device, including special relays
L (link relay) 4 WL as word device
LD (link register) 5
FL (file register) 6
SV (timer/counter set value) 7
EV (timer/counter elapsed time) 8
T (timer/contact) 9 Read only
C (counter/contact) 10 Read only
Switch Setting Contents · 6 ON Even · Memory TYPE Remarks

Wiring
Wiring diagrams with the PLC are shown below.
V7 (CN1)
SD
RD
RD 3
RS
RS 4
CS
CS 5
SG
SG
Connection to PLCs
CD
* Use shielded twist-pair cables.
V7 (CN1)
SD
RD
RD 3
RS
RS 4
CS
CS 5
SG
SG
* Use shielded twist-pair cables.
PLC
SD
SD
RD
RD
RS
SG
CS
SG
* Use shielded twist-pair cables.

RS-422
FG
PLC
+SD
- RD
+RD
* Use shielded twist-pair cables.
Wiring Diagram 4 · D-sub 25-pin (male) · +

6. YOKOGAWA PLC
Available PLCs
Select PLC Type CPU Unit/Port Connection PLC2Way
LC01-0N RS-232C [Wiring Diagram 1]
RS-232C [Wiring Diagram 1]
RS-422 [Wiring Diagram 3]
Programming tool port on the CPU module*1
YOKOGAWA’s ladder transfer cable “KM11-2N”
FA-M3 FA-M3
RS-232C [Wiring Diagram 2] F3LC11-1N
F3LC11-2N RS-422 [Wiring Diagram 3]
Programming tool port on the CPU module*1
YOKOGAWA’s ladder transfer cable “KM11-2N”
F3LC12-1F RS-232C [Wiring Diagram 2]
*1 The CPUs that can be connected directly to the programming tool port on the CPU module are “F3SP21-0N,” “F3SP25-2N,” “F3SP35-5N,” “F3SP28-3N,” “F3SP38-6N,” “F3SP53-4H” and “F3SP58-6H.” *2 When the link unit “F3LC01-1N” is used, the communication setting and available memory are the same as those for “FA-500.” However, B (common register) cannot be used.

Communication Setting
The recommended communication parameter settings of the PLC and the V7 series is as follows:
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 19200 bps 19200 bps
Data length 7 7
Stop bit 1 1
Sumcheck Provided (fixed) −
Terminal character None (fixed) −
Protection function None (fixed) −
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate*1 19200 bps 19200 bps
Data length*2 7 7
Stop bit 1 1
Terminal character None (fixed) −
Protection function None (fixed) −
*1 The maximum baud rate available with the V7 series is 115200 bps. Select the appropriate baud rate depending on the used PLC and environment. *2 When directing connecting to the programming tool port on the CPU module, the data length is fixed to “8.” Select [8-bit] for [Data Length] in the [comm. Parameter] dialog of the V7 series. Also, set “CPU Communication Port” of “Configuration” in the ladder creation tool as below.

Available Memory
The available memory setting range varies depending on the PLC model. Be sure to set within the range available with the PLC to be used. Use [TYPE] when assigning the indirect memory for macro programs.
D (data register) 0
B (common register) 1
TP (timer/current value) 2
TS (timer/set value) 3
CP (counter/current value) 4
CS (counter/set value) 5
X (input relay) 6
Y (output relay) 7
I (internal relay) 8
E (external relay) 9
D (data register) 0
R (common register) 1
V (index register) 2
W (link register) 3
Z (special register) 4
TP (down timer current value) 5
TS (timer set value) 6 Read only
CP (down counter current value) 7
CS (down counter set value) 8
X (input relay) 9
Y (output relay) 10
I (internal relay) 11
E (common relay) 12
L (link relay) 13
M (special relay) 14
B (file register) 15
* The CPU number is required in addition to the memory type and address. The assigned memory is indicated when editing the screen as shown on the right.
Address Memory type CPU number
Memory TYPE Remarks · Memory TYPE Remarks

Wiring
Wiring diagrams with the PLC are shown below.
SD
SD
RD
RD
RS
RS
CS
CS
SG 7
DR
SG
ER
* Use shielded twist-pair cables.
RD
RD
SD
RS
ER
CS
SG
SG
DR
RS
8 * Use shielded twist-pair cables.

RS-422
PLC
- SD
SG 7
RDB
+SD
RDA
- RD
SDB
+RD
SDA
SG
* Use shielded twist-pair cables.
Wiring Diagram 3 · D-sub 25-pin (male)

7. YASKAWA PLC
Available PLCs
Select PLC Type PLC Unit/Port Connection
RS-232C [Wiring Diagram 1]
JAMSC-IF612 JAMSC-IF613 RS-422 [Wiring Diagram 5]
Memobus port on the CPU module RS-232C [Wiring Diagram 1]
JAMSC-120NOM27100 RS-422 [Wiring Diagram 6]
PROGIC-8 PORT2 on the CPU unit RS-232C [Wiring Diagram 2]
RS-232C [Wiring Diagram 3] [Wiring Diagram 4] RS-422 [Wiring Diagram 7]
CP9200SH/MP900
Memobus port on the CPU module RS-232C [Wiring Diagram 1]
217IF RS-232C [Wiring Diagram 3] RS-422 [Wiring Diagram 8]
* Other PLCs can also be connected with Memobus.
The recommended communication parameter settings of the PLC and the V7 series is as follows:
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 19200 bps 19200 bps
Data length 8-bit RTU (fixed) −
Stop bit 1 1
Error check CRC (fixed) −
Port delay timer 0 (fixed) −
Select [TYPE 1] or [TYPE 2] for [Trans. Mode] in the [Comm. Parameter] dialog of the V-SFT editor.
PLC Model V7 Setting Contents
GL60 series, PROGIC-8 TYPE 1 Special binary code
GL120/130 series TYPE 2 Standard binary code

CP9200SH/MP900
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 19200 bps 19200 bps
Data length 8 8
Stop bit 1 1
Error check CRC (fixed) −
Port delay timer 0 (fixed) −
The available memory setting range varies depending on the PLC model. Be sure to set within the range available with the PLC to be used. Use [TYPE] when assigning the indirect memory for macro programs.
Memobus
4 (word device) 0
3 (input register) 1 Including constant register, read only
R (link register) 2
A (extension register) 3
D (link coil) 5
1 (input relay) 6 Read only
7 (constant register) 7
MW (holding register) 0
IW (input register) 1 Read only
IB (input relay) 6 Read only
When setting the MB/IB memory, set the bit numbers in the hexadecimal notation.
DEC Bit No.: HEX

Wiring
Wiring diagrams with the PLC are shown below.
SD
TXD
RD
RXD
RS
RTS
CS
CTS
SG 7
DSR
SGND
DTR
* Use shielded twist-pair cables.
SD
TXD
RD
RXD
RS
RTS
CS
CTS
SG 7
DSR
GND
DTR
* Use shielded twist-pair cables.

SD
SD
RD
RD
RS
RS
CS
CS
SG 7
DR
SG
9 * Use shielded twist-pair cables.
SD
SD
RD
RD
RS
RS
CS
CS
SG 7
DSR
SG
8 * Use shielded twist-pair cables.
RS-422
- SD
RXD -
SG 7
TXD+
+SD
RXD+
- RD
TXD -
+RD
SG
* Use shielded twist-pair cables.

- SD
SG 7
TXD+
RXD -
+SD
RXD+
- RD
RXDRT
+RD
TXD -
SG
TXRD
* Use shielded twist-pair cables.
- SD
CP217IF (CN3)
FG
+SD
- RD
RX+
+RD
TX+
* Use shielded twist-pair cables.
D-sub 25-pin (male) MR-8 (male)
- SD
SG 7
RX+ 2
TX -
+SD
RXR+
- RD
TRX+
+RD
TX+ 7
SG 8
* Use shielded twist-pair cables.

Available PLCs
Select PLC Type PLC Unit/Port Connection
TOYOPUC L2/PC2 series PC3J CMP-LINK RS-422 [Wiring Diagram 1]
The recommended communication parameter settings of the PLC and the V7 series is as follows:
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 19200 bps 19200 bps
Data length 7 (ASCII) 7
Stop bit 2 2
Set [Trans. Mode] in the [Detail] tab window of the [Comm. Parameter] dialog of the V-SFT editor.
- PC3J: Select [Single Data Area] or [Split Data Area]. - L2/PC2 series: Select [Single Data Area].
Single Data Area Data area is common.
Split Data Area Each PLC device is divided into program files.
SW1 0 Station address (lower half)
SW2 0 Station address (upper half)
Switch Short Bar Contents

5-56 8. Toyopuc PLC
The available memory setting range varies depending on the PLC model. Be sure to set within the range available with the PLC to be used. Use [TYPE] when assigning the indirect memory for macro programs.
D (data register) 0
R (link register) 1
B (file register) 2
N (current value register) 3
X (input relay) 4 WX as word device
Y (output relay) 5 WY as word device
M (internal relay) 6 WM as word device
K (keep relay) 7 WK as word device
L (link relay) 8 WL as word device
T (timer/contact) 9 WT as word device
C (counter/contact) 10 WC as word device
U (extensional data register) 11
H (extensional set value register) 12
EN (extensional current value register) 13
EX (extensional input relay) 14 WEX as word device
EY (extensional output relay) 15 WEY as word device
EM (extensional internal relay) 16 WEM as word device
EK (extensional keep relay) 17 WEK as word device
EL (extensional link relay) 18 WEL as word device
ET (extensional timer/contact) 19 WET as word device
EC (extensional counter/contact) 20 WEC as word device
V (special register) 21 WV as word device
When [Split Data Area] is selected for [Trans. Mode], the [PRG No] setting is available in the [Memory Input] dialog.

Memory TYPE Remarks

Wiring diagrams with the PLC are shown below.
PLC
- SD
SG 7
+SD
- RD
+RD
Connection to PLCs
* Use shielded twist-pair cables.
Wiring Diagram 1 · D-sub 25-pin (male) · +

9. FUJI PLC
Available PLCs
Select PLC Type PLC Unit/Port Connection PLC2Way
F55 NV1L-RS2 RS-232C [Wiring Diagram 1]
NC1L-RS2 RS-232C [Wiring Diagram 1]
MICREX-F series (MICREX-F series V4)
NC1L-RS4 RS-485 [Wiring Diagram 3]
FFU120B RS-232C [Wiring Diagram 1]
FFK120A RS-485 [Wiring Diagram 3]
NS-T NJRS-1 RS-232C [Wiring Diagram 1]
NJRS-2 RS-232C [Wiring Diagram 1]
NJRS-4 RS-485 [Wiring Diagram 3]
FLEX-PC CPU*2 FLEX-PC CPU port RS-485 Hakko Electronics’ cable “FU-CPUNS”
NJ-B16 RS-232C port RS-232C [Wiring Diagram 2]
FLEX-PC COM (T) FLEX-PC NJ-JM Computer link terminal block RS-422 [Wiring Diagram 4]
*1 To use FLEX-PC of Toyota version, select [FLEX-PC (T)]. *2 To use FLEX-PC CPU of Toyota version, select [FLEX-PC CPU (T)].
The recommended communication parameter settings of the PLC and the V7 series is as follows:
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 19200 bps 19200 bps
RS-232C 1 (asynchronous non-protocol by command) (fixed) −
RS-422 3 (asynchronous non-protocol by command) (fixed) −
Data length 7 (ASCII) 7
Stop bit 1 1
Terminating resistance at receiver Provided for RS-485 −

FLEX-PC CPU Port
Connect to the CPU port. Communication parameters for the V7 series are automatically set.
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 19200 bps 19200 bps
Data length 7 7
Stop bit 2 2
MODE switch: RS-232C: 1 RS-485: 3 RS-485 Port Setting SW: “0” for both ×10, ×1 RS-485 terminating resistance: ON Character switches
8 ON Switch Setting
7 ON With parity
5 ON 7 bits
4 ON 1 bit
Same as that set on V7 (normally 19200 bps) 2 ON

Available Memory
The available memory setting range varies depending on the PLC model. Be sure to set within the range available with the PLC to be used. Use [TYPE] when assigning the indirect memory for macro programs.
M (auxiliary relay) 0 WM as word device
K (keep relay) 1 WK as word device
B (input/output relay) 2 WB as word device
L (link relay) 9 WL as word device
F (special relay) 10 WF as word device
TS (timer/set value) 11 *1
TR (timer/current value) 12 *1
W9 (timer/current value 0.1) 13 *1
CS (counter/set value) 14 *1
CR (counter/current value) 15 *1
BD (data memory) 16 *1
WS (step control relay) 17 *2
Wn (file memory) 18 *3
*1 For numerical data format where double-words can be used (Num. Data Display, Graph, Sampling), data is processed as double-words. For those where bits or words can be used, data is processed as words consisting of lower 16 bits.
For input Upper 16 bits are ignored. For output “0” is written for upper 16 bits. *2 Byte device such as step relay is processed as described below.
For input Upper 8 bits are “0.” For output: Lower 8 bits are written. *3 To set up the file memory on the V-SFT editor, enter “file number” + “: (colon)” + address in order.
Address Colon File number
* Notes on V4 (or GD-80) data conversion When converting data of V4 (or GD-80) into the V7 data, [MICREX-F series V4] is automatically selected for the PLC type.
Memory TYPE Remarks

FLEX-PC Series, FLEX-PC CPU Port
Standard Memory Toyota Version TYPE Remarks
D (data register) D 0
W (link register) R 1
M (internal relay) M 2 WM as word device
L (latch relay) K 3 WL (WK) as word device
X (input relay) X 4 WX as word device
Y (output relay) Y 5 WY as word device
R (file register) W 6
TN (timer/current value) TN 7
CN (counter/current value) CN 8
T (timer/contact) T 9
C (counter/contact) C 10
WS (step relay) Not provided 11
FLEX-PC COM (T) (NJ Computer Link) Toyota Version
D (data register) 0
R (link register) 1
M (internal relay) 2 WM as word device
K (latch relay) 3 WK as word device
X (input relay) 4 WX as word device
Y (output relay) 5 WY as word device
W (file register) 6
TN (timer/current value) 7
CN (counter/current value) 8
Z (special register) 12
V (special relay) 13 WV as word device
Memory TYPE Remarks · T (timer/contact) 9 · C (counter/contact) 10

Wiring
Wiring diagrams with the PLC are shown below.
FG
SD
RD
RD
RS
RS
CS
CS
SG
DR
SG
CD
* Use shielded twist-pair cables.
FG
RD
RD
SD
RS
CTS
CS
RTS
SG
SG 7
* Use shielded twist-pair cables.

RS-485
PLC
- SD
SG 7
SDA
+SD
SDB
- RD
RDA
+RD
RDB
SG
* Use shielded twist-pair cables.
Connection to PLCs
PLC
- SD
SG 7
+SD
- RD
SG
+RD
* Use shielded twist-pair cables.

10. KOYO PLC
Available PLCs
Select PLC Type PLC Unit/Port Connection
SU-5/5E/6B/5M/6M U01-DM RS-232C [Wiring Diagram 1] RS-422 [Wiring Diagram 3]
SU-5E/6E Universal port 1 on CPU RS-232C [Wiring Diagram 1]
RS-422 [Wiring Diagram 7]
Universal port 3 on CPU RS-485 [Wiring Diagram 8]
Universal port 2 on CPU RS-232C
KOYO’s programmer connecting cable S-30JG-E
PORT2 on CPU (universal communication port)
+ KOYO’s conversion connector S-15CNJ
KOYO’s programmer connecting cable S-30JG-E
PORT2 on CPU (universal communication port)
+ KOYO’s conversion connector S-15CNJ
+ KOYO’s conversion connector S-15HCNP1
G01-DM RS-232C [Wiring Diagram 1] RS-422 [Wiring Diagram 4]
Port on CPU RS-232C [Wiring Diagram 1] RS-422 [Wiring Diagram 4]
Universal communication port on the CPU unit
RS-232C [Wiring Diagram 2] RS-485 [Wiring Diagram 6]
U01-DM RS-232C [Wiring Diagram 1] RS-422 [Wiring Diagram 3]
SR-T SR-6T (Toyota version)
G01-DM RS-232C [Wiring Diagram 1] RS-422 [Wiring Diagram 4]
SR-T (K protocol) SR-1T (Toyota version) Terminal block on the CPU unit RS-422 [Wiring Diagram 5]
(To be continued)

Select PLC Type PLC Unit/Port Connection
SU-5E/6B Universal port 1 on CPU RS-232C [Wiring Diagram 1]
RS-485 [Wiring Diagram 7]
Programmer port on CPU
KOYO’s programmer connecting cable S-30JG-E
Universal port 3 on CPU RS-485 [Wiring Diagram 8]
Universal port 2 on CPU
PORT1 on CPU (programmer port)
KOYO’s programmer connecting cable S-30JG-E
PORT2 on CPU (universal communication port)
+ KOYO’s conversion connector cable S-15CNJ
PORT1 on CPU (programmer port)
KOYO’s programmer connecting cable S-30JG-E
PORT2 on CPU (universal communication port)
+ KOYO’s conversion connector cable 15CNJ
+ KOYO’s conversion connector S-15HCNP1
The recommended communication parameter settings of the PLC and the V7 series is as follows:
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 19200 bps 19200 bps
Port [0] × 10, [1] × 1 1
Data length 8 8
Stop bit 1 1
Functions Host link function (fixed) −
Response delay time 0 (fixed) −
Timeout None (fixed) −
ASCII/HEX HEX (fixed) −
SU/SG (K-Sequence) · Parity Odd Odd · Transmission code

Available Memory
The available memory setting range varies depending on the PLC model. Be sure to set within the range available with the PLC to be used. Use [TYPE] when assigning the indirect memory for macro programs.
R (data register) 0
I (input relay) 1
Q (output relay) 2
M (internal relay) 3
GI (global input) 5
GQ (global output) 6
D (data register) 0
X (input relay) 1 Common to X/Y
Y (output relay) 2 Common to X/Y
M (internal relay) 3
K (keep relay) 5
L (link relay) 6

Switch Setting
U-01DM
On-line/Off-line switch: On-line UNIT ADR switch: “0” for ×10, “1” for ×1 SW4 DIP switch:
Same as that set on V7 Normally 19200 bps 2 ON
4 ON With parity
Response delay time 0 msec 7 OFF
Connection to PLCs
SW5 DIP switch:
1 OFF Master/slave control
3 OFF Communication timeout
4 OFF HEX mode

G-01DM
On-line/Off-line switch: On-line Short plug 1: open Short plug 2: RS-232C ENABLE RS-422 DISENABLE SW1 DIP switch:
2 OFF
3 OFF
4 OFF
Unit No. 1
6 OFF
7 OFF
8 OFF 1: N
SW2 DIP switch:
Same as that set on V7 Normally 19200 bps 2 ON
4 ON With parity
6 OFF Turn-around delay
Response delay time 0 msec 8 OFF
9 OFF HEX mode

Wiring
Wiring diagrams with the PLC are shown below.
SD
SD
RD
RD
RS
RS
CS
CS
7 SG 7
SG
Connection to PLCs
* Use shielded twist-pair cables.
SD
TXD
RD
RXD
RS
RTS
CS
CTS
7 SG 7
* Use shielded twist-pair cables.
*1 High-density D-sub 15-pin

RS-422
0V 7 SG 7
+SD
+RTS
− SD
− RTS
+RD
+CTS
− RD
− CTS
+OUT
− OUT
− IN
+IN
* Use shielded twist-pair cables.
+IN
0V 7 SG 7
+SD
+OUT
− SD
− OUT
+RD
− IN
− RD
+IN
* Use shielded twist-pair cables.
PLC
FG SG 7
+SD
T1
− SD
T2
+RD
T3
− RD
* Use shielded twist-pair cables.

RXD − 6 SG 7
+SD
− SD
TXD+
+RD
TXD −
− RD
RTS+
RTS −
RXD+
CTS+
* Use shielded twist-pair cables.
*1 High-density D-sub 15-pin
- SD
RXD -
SG 7 SG 7
+SD
RXD+
- RD
TXD1 -
+RD
CTS1+
TXD1+
RTS1 -
RTS1+
* Use shielded twist-pair cables.
- SD
TXD3 -
SG 7 SG 7
+SD
TXD3+
- RD
RXD3 -
+RD
RXD3+
* Use shielded twist-pair cables. SU-6M: Terminal block connectable

5-72 11. Allen-Bradley PLC
Available PLCs
Select PLC Type PLC Unit/Port Connection
1785-KE RS-232C [Wiring Diagram 1]
1770-KF2 RS-232C [Wiring Diagram 2] RS-422 [Wiring Diagram 6]
CPU (processor module) RS-232C channel RS-232C [Wiring Diagram 3]
SLC500 SLC 5/03 and later
1747-KE RS-232C [Wiring Diagram 4] RS-422 [Wiring Diagram 7]
A•B’s RS-232C Ladder transfer cable*1
Micro Logix 1000 Micro Logix 1000 Port on CPU
+ RS-232 [Wiring Diagram 5]
Control Logix Control Logix 1756 system Logix5550
*1 When using RS-232C ladder transfer cable made by Allen-Bradley, connect the cable shown in [Wiring Diagram 3] to the D-sub 9-pin side of the ladder transfer cable for communications with the V7 series.

The recommended communication parameter settings of the PLC and the V7 series is as follows:
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 19200 bps 19200 bps
RS-422 1785-KE not supported −
Data length 8 8
Stop bit 1 1
Protocol Full duplex (fixed) −
Error check BCC (fixed) −
Response NO (fixed) −
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 19200 bps 19200 bps
RS-422 Channel 0 not supported −
Data length 8 8
Stop bit 1 1
Protocol Full duplex (fixed) −
Error check BCC (fixed) −
Response NO (fixed) −
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 9600 bps 9600 bps
Parity None (fixed) Not provided
Data length 8 (fixed) 8
Stop bit 1 (fixed) 1
Error check CRC (fixed) −

5-74 11. Allen-Bradley PLC
The available memory setting range varies depending on the PLC model. Be sure to set within the range available with the PLC to be used. Use [TYPE] when assigning the indirect memory for macro programs.
T.ACC (timer/current value) 2
T.PRE (timer/set value) 3
C.ACC (counter/current value) 4
C.PRE (counter/set value) 5
R.LEN (control/data length) 12
R.POS (control/data position) 13
A (ASCII) 15

T.ACC (timer/current value) 2
T.PRE (timer/set value) 3
C.ACC (counter/current value) 4
C.PRE (counter/set value) 5
R.LEN (control/data length) 12
R.POS (control/data position) 13
D (BCD) 14
A (ASCII) 15
F (FLOAT) 16
ST (STRING) 17

5-76 11. Allen-Bradley PLC
1 ON
BCC, even, no 2 OFF
4 ON Duplicated message unacceptable
5 OFF Handshaking signal ignored
6 ON Execution of diagnosis command
Set the port number of 1785-KE. (This port should not be duplicated in the network.)
1st digit (octal) 2 ON
2nd digit (octal) 4 ON/OFF
6 ON/OFF
3rd digit (octal) 7 ON/OFF
SW3 (Network link communication speed)
Adjust to the settings of the network you are using.
Data highway (57.6 kbps) 2 ON
Link communication speed (19.2 kbps) 4 ON
6 ON Local/remote selection
1 OFF
For extension, always OFF 2 OFF
4 OFF

3 ON Duplicated message unacceptable
4 OFF Handshaking signal ignored
Set the port number of 1770-KF2. (This port should not be duplicated in the network.) SW5 (Network link communication speed) Adjust to the settings of the network you are using.
ON ON 57.6 kbps
Adjust to the settings of the V7 series.
9600 bps 2 ON
4 ON Execution of diagnosis command
ON OFF Peer transmission link
OFF ON RS232C
ON OFF RS422

5-78 11. Allen-Bradley PLC
Set up the parameters for CPU port channel 0 using the software specifically designed for this purpose.
Set up the parameters for 1747-KE using the software specifically designed for this purpose.
DF1 Port Setup Menu
DF1 Full-Duplex Setup Parameters
ACK Timeout (× 5 ms) : 90

Wiring diagrams with the PLC are shown below.
SD
TXD
RD
RXD
RS
RTS
CS
CTS
6 7 SG DSR
Connection to PLCs
SG 7
DCD
DTR
SG * Use shielded twist-pair cables.
FG
TXD
RD
RXD
RS
RTS
CS
CTS
SG 7
6 DSR
SG 7
DCD
DTR
* Use shielded twist-pair cables.

5-80 11. Allen-Bradley PLC
D-sub 25-pin (male) D-sub 9-pin (female)
DCD
SD
RXD
RD
TXD
RS
DTR
CS
5 COM
SG 7
DSR 6
RTS
CTS
* Use shielded twist-pair cables.
SD
RXD
RD
TXD
RS
DTR
CS
5 COM
SG 7 6
DSR
RTS
CTS * Use shielded twist-pair cables.
D-sub 25-pin (male) D-sub 9-pin (male)
CD 1
SD
RD
A •B’s RS-232C Ladder transfer
SD
RS
RS
CS
GND 5
SG
DR 6
RS 7
* Use shielded twist-pair cables.

PLC
FG
RTS
- RD
CTS
+RD
DSR
DCD
14 TDA
RDA 16
RDB
DTR
Connection to PLCs
TDB
* Use shielded twist-pair cables.
- SD
SG
+SD
9 TXD+ - RD 25
COM
+RD
RXD+
* Use shielded twist-pair cables.

5-82 12. GE Fanuc PLC
Available PLCs
Select PLC Type PLC Unit/Port Connection
90 series Series 90-30 Programmable coprocessor (PCM)
RS-232C [Wiring Diagram 1] RS-485 [Wiring Diagram 2]
Series 90 micro Series 90-30 CPU port RS-485 [Wiring Diagram 3]
The recommended communication parameter settings of the PLC and the V7 series is as follows:
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 19200 bps 19200 bps
Port 01 (“0” for ×10, “1” ×1) 1
Data length 8 8
Stop bit 1 1
Functions Host link function (fixed) −
Response delay time 0 (fixed) −
Timeout None (fixed) −
ASCII/HEX HEX (fixed) −
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 19200 bps 19200 bps
Data length 8 8
Stop bit 1 1
Functions SNP-X (fixed) −

The available memory setting range varies depending on the PLC model. Be sure to set within the range available with the PLC to be used. Use [TYPE] when assigning the indirect memory for macro programs.
R (data register) 0
R (data register) 0
M (internal relay) 3
G (global relay) 4
AI (analog input) 5
AQ (analog output) 6
T (temporary memory relay) 7
S (system status) 8 Read only
SA (system status) 9
SB (system status) 10
SC (system status) 11

5-84 12. GE Fanuc PLC
Wiring diagrams with the PLC are shown below.
SD
SD
RD
RD
RS
RS
CS
5 CS
SG 7 GND
* Use shielded twist-pair cables.
- SD
SG
+SD
SD(A)
- RD 25 13
RTS(A)
+RD
11 CTS(A)
RD(A)
SD(B)
RTS(B)
CTS(B)
RT
RD(B)
* Use shielded twist-pair cables.

- SD
SG
RTS(A)
+SD
- RD 25 10
CTS(B’)
+RD
9 RT
RD(A’)
RD(B’)
SD(A)
SD(B)
RTS(B)
Connection to PLCs
CTS(A’)
* Use shielded twist-pair cables.
Wiring Diagram 3 · D-sub 25-pin (male) · D-sub 15-pin (male)

13. TOSHIBA PLC
Available PLCs
Select PLC Type PLC Unit/Port Connection
T series T series Computer link port on CPU RS-422 [Wiring Diagram 1]
The recommended communication parameter settings of the PLC and the V7 series is as follows:
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 19200 bps 19200 bps
Data length 8 8
Stop bit 1 1
Baud rate 19200 bps
Data length 8 bits
Stop bit 1 bit

Available Memory
The available memory setting range varies depending on the PLC model. Be sure to set within the range available with the PLC to be used. Use [TYPE] when assigning the indirect memory for macro programs.
D (data register) 0
X (input register) 1 XW as word device
Y (output register) 2 YW as word device
R (auxiliary relay) 5 RW as word device
L (link relay) 6 LW as word device
W (link register) 7
F (file register) 8
TN (timer/current value) 9 Read only
CN (counter/current value) 10 Read only
TS (timer/contact) 11 Read only
CS (counter/contact) 12 Read only
Wiring diagrams with the PLC are shown below.
- SD
SG
RXA
+SD
TXA
- RD SG 7
CTSA
+RD
* R
RTSA 5
RXB
TXB
CTSB
* Use shielded twist-pair cables.
* R: 120 Ω 1/2 W

14. TOSHIBA MACHINE PLC
Available PLCs
Select PLC Type PLC Unit/Port Connection
Port on the CPU unit
RS-232C [Wiring Diagram 1] TCCMW TCCMO
Communication Setting
The recommended communication parameter settings of the PLC and the V7 series is as follows:
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 9600 bps 9600 bps
The available memory setting range varies depending on the PLC model. Be sure to set within the range available with the PLC to be used. Use [TYPE] when assigning the indirect memory for macro programs.
D (register 1) 0
B (register 2) 1
X (input relay) 2 XW as word device
Y (output relay) 5 YW as word device
R (temporary storage) 6 RW as word device
G (extension temporary storage 1) 7 GW as word device
H (extension temporary storage 2) 8 HW as word device
L (latch relay) 9 LW as word device
S (shift register) 10 SW as word device
E (edge relay) 11 EW as word device
P (timer counter current value) 12
V (timer counter set value) 13
T (timer) 14 TW as word device
C (counter) 15 CW as word device
A (special auxiliary relay) 16 AW as word device
TCmini − · Port 1 1 · Memory TYPE Remarks

Wiring
Wiring diagrams with the PLC are shown below.
SD
TXD
RD
RXD
RS
DTR
CS
GND
SG 7
DSR
Connection to PLCs
CTS
8 RTS
* Use shielded twist-pair cables.
Wiring Diagram 1 · D-sub 25-pin (male) · D-sub 9-pin (female)

15. SIEMENS PLC
Available PLCs
Select PLC Type PLC Unit/Port Connection
CP-521SI (3964R Transmission Protocol)
RS-232C [Wiring Diagram 1]
S5 (S5 V4)
CP-524 (3964R/RK512) CP-544 (3964R/RK512)
RS-232C [Wiring Diagram 1] RS-422 [Wiring Diagram 6]
Second serial interface (3964R Transmission Protocol)
SIEMENS’s 6ES5 734-1BD20 cable*
+ RS-232C [Wiring Diagram 3] S5 PG port S5 series Programming port on the CPU unit
S7-300 CP-341 (3964R/RK512) RS-232C [Wiring Diagram 2] RS-422 [Wiring Diagram 6] S7-400 CP-441 (3964R/RK512)
S7-200 PPI S7-200 series PPI RS-422 [Wiring Diagram 7]
SIEMENS’s HMI Adapter 6ES7 972 0CA11-0XA0 RS-232C [Wiring Diagram 5] S7-300MPI
(HMI ADP) S7-300/400 series (MPI port)
SIEMENS’s PC Adapter 6ES7 9720CA23-0XA0
TI500/505 (TI500/505 V4) TI545/555 CPU port (bulit-in) RS-232C [Wiring Diagram 4] RS-422 [Wiring Diagram 8]
* When using the 6ES5 734-1BD20 cable made by SIEMENS, connect the cable shown in [Wiring Diagram 3] to the D-sub 25-pin side of the 6ES5 734-1BD20 cable for communications with the V7 series.
The recommended communication parameter settings of the PLC and the V7 series is as follows:
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 9600 bps 9600 bps
Parity Even parity Even
Data length 8 8
Stop bit 1 1
Busy signal NO (fixed) −
Hand shake OFF (fixed) −
Transmission code

S5, S5 V4 (S5-115U, S5-135U, S5-155U, S7-300, S7-400)
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 9600 bps 9600 bps
Parity − Even (fixed)
Data length − 8 (fixed)
Stop bit − 1 (fixed)
Communication parameters are automatically set.
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 9600 bps 9600 bps
Parity Even (fixed) −
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 38400 bps HMI ADP 38400 bps (fixed)
PC ADP 38400 bps
Parity − Odd (fixed)
Data length − 8 (fixed)
Stop bit − 1 (fixed)
Local No. (PLC port number) 2 2
Source No. (V7 port number) 0
Set different numbers for [Source No.] and [Local No.], and make sure that [Source No] ≤ [Node Cnt]. [Node Cnt] is equivalent to [Local No.] of the PLC. (For example, if [Local No.] is “13,” [Node Cnt] is “15.”)

TI500/505, TI500/505 V4

The available memory setting range varies depending on the PLC model. Be sure to set within the range available with the PLC to be used. Use [TYPE] when assigning the indirect memory for macro programs.

DB (data register) 0 Use memory address DB1 and later for S7, or DB3 or later for S5.
I (input relay) 1 IW as word device, read only
Q (output relay) 2 QW as word device, read only
F (flag/internal relay)*1 3 FW as word device, read only, only in S5 series
M (flag/internal relay)*1 3 MW as word device, read only, only in S7 series
AS (absolute address) 6 Unavailable with the S7 series
*1 The assigned memory is indicated when editing the screen as shown on the right.
* Notes on V4 (or GD-80) data conversion

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Memory to be accessed to PLC by V4 (or GD-80)
Address Block number

S5 PG port
DB (data register) 0 Use memory address DB3 and later.
I (input relay) 1 IW as word device
Q (output relay) 2 QW as word device
F (flag/internal relay) 3 FW as word device
T (timer/current value) 4
C (counter/current value) 5
AS (absolute address) 6
The assigned memory is indicated when editing the screen as shown on the right.
V (data memory) 0 VW as word device
I (input) 1 IW as word device Possible to write to the unused area
Q (output) 2 QW as word device
M (bit memory) 3 MW as word device
T (timer/current value) 4
C (counter/current value) 5
TB (timer/contact) 6 Read only
CB (counter/contact) 7 Read only
HC (high-speed counter/contact) 8 Double-word usable
AIW (analog input) 9
AQW (analog output) 10
SM (special memory/special relay) 11 SMW as word device
S (stage) 12 SW as word device
DB (Data Word) 0 Use memory address DB1 and later.
I (input) 1 IW as word device
Q (output) 2 QW as word device
M (Marker Word) 3 MW as word device
T (timer/current value) 4
C (counter/current value) 5
The assigned memory is indicated when editing the screen as shown on the right.

TI500/505 (TI500/505 V4)
V (variable memory) 0
WX (word input) 1
WY (word output) 2
X (discrete input) 3
Y (discrete output) 4
CR (control relay) 5
TCP (timer, counter/set value) 6
TCC (timer, counter/current time) 7
DCP (drum count/set value) 8 *1
DCC (drum count/current value) 9 Read only
DSP (drum step/set value) 10
DSC (drum step/current value) 11
K (fixed memory) 12
STW (system state) 13
*1 In case of using DCP (drum count/setting value), set drum step No.1 to 16. The assigned memory is indicated when editing the screen as shown on the right.
Drum step number Colon Address
* Notes on V4 (or GD-80) data conversion
MSB LSB
High-order word Lower-order word
Lower-order word High-order word

Wiring
Wiring diagrams with the PLC are shown below.
SD
TXD
RD
RXD
RS
GND
CS
SG
Connection to PLCs
* Use shielded twist-pair cables.
SD
RXD
RD
TXD
RS
GND
CS
SG
* Use shielded twist-pair cables.
SD
TXD
RD
RXD
6ES5 734-1BD20 S5-95U
RS
CS
SG
7 GND
* Use shielded twist-pair cables.

D-sub 25-pin (male) D-sub 9-pin (female)
DCD
SD
RXD
RD
TXD
RS
DTR 4
CS
SG 5
SG
DSR
RTS
8 * Use shielded twist-pair cables.
RD
RD
SD
RS
SG
CS
RTS
CTS 8 SG 7
* Use shielded twist-pair cables.
SG
T(A)
+SD
R(A)
− SD
SG
+RD
T(B) 9
− RD
R(B) 11
* Use shielded twist-pair cables.

SG
SG
+SD
− SD
+RD
− RD
* Use shielded twist-pair cables.
- Terminating Resistance Setting
Set the DIP switch 7 and 8 of the V7 series to the OFF position. Connect terminating resistance to the serial connector (CN1) of the V7 series as shown below. If the terminating resistance is not connected, a communication error may occur.
SG
+SD 12
− SD
+RD
− RD 25
- SD
DI - 8
SG
GND
+SD
DI+
- RD
DO - 7
+RD
DO+ 1
* Use shielded twist-pair cables.

16. SHINKO PLC
Available PLCs
Select PLC Type PLC Unit/Port Connection
SELMART SELMART-100 and later Version O1M2-UCI-6 RS-232C [Wiring Diagram 1]
The recommended communication parameter settings of the PLC and the V7 series is as follows:
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 19200 bps 19200 bps
Data length 7 (ASCII) 7
Stop bit 1 1
Sumcheck Provided (fixed) −
The available memory setting range varies depending on the PLC model. Be sure to set within the range available with the PLC to be used. Use [TYPE] when assigning the indirect memory for macro programs.
D (data register) 0
Only D register of SELMART is available. No other devices can be used. Be sure to note the above though the setting on the V-SFT editor is possible.
Parity Even Even · Transmission code · Memory TYPE Remarks

Wiring
Wiring diagrams with the PLC are shown below.
SD
SD
RD
RD
RS
RS
CS
CS 5
SG
SG 7
Connection to PLCs
* Use shielded twist-pair cables.
Wiring Diagram 1 · D-sub 25-pin (male) · D-sub 25-pin (male)

17. SAMSUNG PLC
Available PLCs
Select PLC Type PLC Connection
SPC series SPC series RS-232C [Wiring Diagram 1] RS-422/485 [Wiring Diagram 2]
The recommended communication parameter settings of the PLC and the V7 series is as follows:
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 9600 bps 9600 bps
Parity Not provided Not provided
Stop bit 1 1
Terminating resistance ON for RS-485 −
The available memory setting range varies depending on the PLC model. Be sure to set within the range available with the PLC to be used. Use [TYPE] when assigning the indirect memory for macro programs.
L (link relay) 1
M (internal relay) 2
K (keep relay) 3
F (special relay) 4
W (data register) 5
Memory TYPE Remarks · R (input/output) 0

Wiring
Wiring diagrams with the PLC are shown below.
SD
TXD
RD
RXD
RS
5 GND
CS
SG
Connection to PLCs
* Use shielded twist-pair cables.
+SD
TR −
− SD
TR+
+RD
− RD
* Use shielded twist-pair cables.

18. KEYENCE PLC
Available PLCs
Select PLC Type PLC Unit/Port Connection
RS-232C [Wiring Diagram 1] Port 2
KZ series link KZ300 KZ350 KZ-L2
RS-232C [Wiring Diagram 2] RS-422 [Wiring Diagram 6]
RS-232C [Wiring Diagram 3] RS-422
CPU
+ Hakko Electronics’ cable “MB-CPUQ”
RS-232C [Wiring Diagram 4] Port 2
Mistubishi A series link KZ-L10
RS-232C [Wiring Diagram 2] RS-422 [Wiring Diagram 6]
RS-232C [Wiring Diagram 5] or KEYENCE’s cable “OP-26487”
KZ-10, 16, 24*1, 40, 80, 300, 350 KV series*2
+ Connector “OP-26485” RS-422
+ Hakko Electronics’ cable “MB-CPUQ”
CPU KZ-24, 300*1 CPU modular port RS-232C [Wiring Diagram 5] or KEYENCE’s cable “OP-26487”
CPU KV-10, 24*2 CPU modular port
CPU KV-700 CPU modular port
*1 To connect KZ-24, 300 via RS-232C, select [KZ24/300CPU] for the PLC type on the V-SFT editor. *2 To connect KZ-10, 24 via RS-232C, select [KV10, 24CPU] for the PLC type on the V-SFT editor.

Communication Setting
The recommended communication parameter settings of the PLC and the V7 series is as follows:
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 19200 bps 19200 bps
Data length 7 (ASCII) 7
Stop bit 2 2
Terminating resistance ON for RS-422 −
Set the port with the port setting switch, the terminating resistance with terminator, and the baud rate/data bit/parity/stop bit with SET B DIP switches.
KZ-A500 CPU (CPU Modular Port)
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 9600 bps 9600 bps*1
Data length 8 8
Stop bit 1 1
Terminating resistance ON for RS-422 −
*1 For signal level RS-422, baud rate is fixed to 9600 bps.
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 19200 bps 19200 bps
Data length 7 7
Stop bit 1 1
Terminating resistance ON for RS-422 −
Set the port with the port setting switch, the terminating resistance with terminator, and the baud rate/data bit/parity/stop bit with SET B DIP switches. For more information, refer to the instruction manual for KZ-L10.

KZ/KV Series CPU / KV-700 CPU
Communication parameters for the V7 series are automatically set.
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 38400 bps 38400 bps*1
Data length 8 −
Stop bit 1 −
Terminating resistance − −
*1 Maximum baud rate available is 38400 bps. If a higher baud rate is selected, communications are performed at 9600 bps.
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 57600 bps 57600 bps*1
Data length 8 −
Stop bit 1 −
Terminating resistance − −
*1 Maximum baud rate available is 57600 bps. If a higher baud rate is selected, communications are performed at 9600 bps.
The available memory setting range varies depending on the PLC model. Be sure to set within the range available with the PLC to be used. Use [TYPE] when assigning the indirect memory for macro programs.
DM (data memory) 0
CH (input/output relay) 1

KZ-A500 CPU, MITSUBISHI A Series Link
D (data register) 0
W (link register) 1
R (file register) 2
TN (timer/current value) 3
CN (counter/current value) 4
M (internal relay) 6
L (latch relay) 7
B (link relay) 8
X (input relay) 9
Y (output relay) 10
KZ/KV Series CPU, KZ24/300 CPU, KV10/24 CPU, KV-700 CPU
DM (data memory) 0
CH (input/output relay) 1
TC (timer/current value) 2
CC (counter/current value) 3
TS (timer/set value) 4
CS (counter/set value) 5
TM (temporary data memory) 8
CTH (high-speed counter/current value) 9 KV700 only
CTC (high-speed counter comparator/setting value)
CT (high-speed counter comparator/contact) 11 KV700 only
CR control relay 12 KV700 only
CM control relay 13 KV700 only

Wiring
Wiring diagrams with the PLC are shown below.
SD
SD
RD
RD
RS
4 RS
CS
CS
SG
SG
* Use shielded twist-pair cables.
PLC
SD
SD
RD
RD
RS 4
SG
CS 5
SG 7
* Use shielded twist-pair cables.
FG
CS
SD
SD
RD
SG
RS 4
RD
CS 5
RS
SG 7 1 2 3 4 5 6
* Use shielded twist-pair cables.

V7 (CN1)
SD
RD
RD
RS
RS
CS
CS
SG
DR
SG
8 CD * Use shielded twist-pair cables.
Connection to PLCs
PLC
FG
SD
RD
RD
SG
RS
SD
CS
1 2 3 4 5 6
* Use shielded twist-pair cables.
PLC
- SD 13
SG
SDB 7
+SD
12 SDA
- RD
RDB
+RD
RDA
SG
* Use shielded twist-pair cables.

19. LG PLC
Available PLCs
Select PLC Type PLC Connection
MASTER-K10/60/200 K10/60/200 RS-232C [Wiring Diagram 1]
MASTER-K500/1000 K500/1000 RS-232C [Wiring Diagram 2] RS-422 [Wiring Diagram 5]
MASTER-KxxxS K200S/K300S/K1000S CPU port RS-232C [Wiring Diagram 3]
MASTER-KxxxS CNET K4F-CUEA RS-232C [Wiring Diagram 4] RS-422 [Wiring Diagram 6] GLOFA CNET G4L-CUEA
The recommended communication parameter settings of the PLC and the V7 series is as follows:
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 9600 bps (fixed) −
Parity None (fixed) −
Data length 8 (fixed) −
Stop bit 1 (fixed) −
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 19200 bps*1 19200 bps
Parity None (fixed) −
Data length 8 (fixed) −
Stop bit 1 (fixed) −
*1 For signal level RS-422, baud rate is fixed to 9600 bps.
Transmission code · Transmission code

MASTER-KxxxS
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 38400 bps 38400 bps
Parity None (fixed) −
Data length 8 (fixed) −
Stop bit 1 (fixed) −
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 38400 bps 38400 bps
Parity Not provided Not provided
Data length 8 8
Stop bit 1 1
Available Memory
The available memory setting range varies depending on the PLC model. Be sure to set within the range available with the PLC to be used. Use [TYPE] when assigning the indirect memory for macro programs.
D (data register) 0
M (auxiliary relay) 1
K (keep relay) 3
TC (timer/current value) 4
CC (counter/current value) 5
TS (timer/set value) 6
CS (counter/set value) 7
Transmission code · Transmission code · Memory TYPE Remarks

MASTER-K500/1000
L (link relay) 2
K (keep relay) 3
F (special relay) 4 Read only
T (timer/current value) 5
C (counter/set value) 6
D (data register) 7
M (auxiliary relay) 1
L (link relay) 2
K (keep relay) 3
F (special relay) 4 Read only
T (timer/current value) 5
C (counter/set value) 6
D (data register) 7
P (input/output relay) 0 PW as word device, input: read only
M (auxiliary relay) 1 MW as word device
L (link relay) 2 LW as word device
K (keep relay) 3 KW as word device
F (special relay) 4 FW as word device, read only
T (timer/current value) 5
C (counter/setting value) 6
D (data register) 7

GLOFA CNET
M (internal memory) 0 MW as word device
Q (output) 1 QW as word device
I (input) 2 IW as word device
Wiring diagrams with the PLC are shown below.
SD
RXD 2
RD
3 TXD
SG 7 GND
* Use shielded twist-pair cables.
SD
TXD 2
RD
3 RXD
SG 7 GND
* Use shielded twist-pair cables.
SD
RXD 2
RD
3 TXD
RS 4 GND
CS 5
RTS
SG 7
CTS
* Use shielded twist-pair cables.

D-sub 25-pin (male) D-sub 25-pin (male)
CD 1
SD
RXD 2
RD
3 TXD
RS 4
DTR 4
5 CS 5
GND
SG 7
DSR 6
* Use shielded twist-pair cables.
CTS
RS-422
SD -
+SD
SD+
- RD
+RD
* Use shielded twist-pair cables.
- SD
SG 7 SG
+SD
RDA
- RD
RDB
+RD
SDA
SDB
* Use shielded twist-pair cables.

20. FANUC PLC
Available PLCs
Select PLC Type PLC Unit/Port Connection
Power Mate-Model H/D Port on the CPU unit (JD14)
RS-422 [Wiring Diagram 2]
Power Mate i Model H/D
JD42 RS-232C [Wiring Diagram 1]
JD40 RS-422 [Wiring Diagram 3]
The recommended communication parameter settings of the PLC and the V7 series is as follows:
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 19200 bps (fixed) −
Port 0 (fixed) −
Parity Even (fixed) −
Data length 8 (fixed) −
Stop bit 1 (fixed) −
The available memory setting range varies depending on the PLC model. Be sure to set within the range available with the PLC to be used. Use [TYPE] when assigning the indirect memory for macro programs.
D (data table) 0
X (input relay) 1 WX as word device
Y (output relay) 2 WY as word device
R (internal relay) 3 WR as word device
K (keep relay) 4 WK as word device

Wiring
Wiring diagrams with the PLC are shown below.
FG
SD
RDB
RD
SDB
RS
CS
SG
* Use shielded twist-pair cables.
FG
SG
RDB 7
+SD
12 RDA
− SD 13 SDB
+RD
SDA
− RD
* Use shielded twist-pair cables.
RDB
2 R
RDA
R: 120 Ω 1/2 W

FG
- SD 13 TXD
SG
RXD 7
+SD
*RXD
- RD
+RD
*TXD
5 RTS
*RTS
7 CTS
8 *CTS
* Use shielded twist-pair cables.

21. FATEK AUTOMATION PLC
Available PLCs
Select PLC Type PLC Unit/Port Connection
RS-232 [Wiring Diagram 1] [Wiring Diagram 2] RS-422 [Wiring Diagram 3]
FACON FB series FACON FB series FB-DTBR
The recommended communication parameter settings of the PLC and the V7 series is as follows:
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 9600 bps 9600 bps
Parity Even (fixed) −
Data length 7 (fixed) −
Stop bit 1 (fixed) −
The available memory setting range varies depending on the PLC model. Be sure to set within the range available with the PLC to be used. Use [TYPE] when assigning the indirect memory for macro programs.
HR (data register) 0
DR (data register) 1
X (input relay) 2
Y (output relay) 3
M (internal relay) 4
S (step relay) 5
T (timer contact) 6 Read only
C (counter contact) 7 Read only
RT (timer/current value) 8
RC (counter/current value) 9
DRC (32-bit counter/current value) 10
Transmission code · Memory TYPE Remarks

Wiring
Wiring diagrams with the PLC are shown below.
SD 2
RXD1
RD
TXD1 2
RS
RTS1
CS
CTS1
SG
SG
Connection to PLCs
* Use shielded twist-pair cables.
SD 2
RXD1
RD
TXD1 3
RS
RTS1
CS
CTS1
SG
SG
* Use shielded twist-pair cables.
D -
FG
- SD
SG 7
D+
+SD
- RD
SG
+RD
* Use shielded twist-pair cables.

22. IDEC PLC
Available PLCs
Select PLC Type PLC Unit/Port Connection
IDEC cable “FC2A-KC1” or IDEC cable “FC2A-KC2”*+ [Wiring Diagram 1]
MICRO3 MICRO3 Loader port
* When using RS-232C cable “FC2A-KC2” made by IDEC, connect the cable shown in [Wiring Diagram 3] to the D-sub 9-pin side of the FC2A-KC2 cable for communications with the V7 series.
The recommended communication parameter settings of the PLC and the V7 series is as follows:
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 9600 bps 9600 bps
Data length 7 7
Stop bit 1 1
The available memory setting range varies depending on the PLC model. Be sure to set within the range available with the PLC to be used. Use [TYPE] when assigning the indirect memory for macro programs.
D (data register) 0
M (internal relay) 3
R (shift register) 4
TS (timer/set value) 5
TN (timer/enumerated value) 6
T (timer/contact) 7 Read only
CS (counter/set value) 8
CN (counter/enumerated value) 9
C (counter/contact) 10 Read only

Wiring
Wiring diagrams with the PLC are shown below.
V7 (CN1) PLC
D-sub 25-pin (male) D-sub 9-pin (male)
CD 1
SD
SD
RD
RD
RS
ER
CS
GND 5
SG
DR 6
Connection to PLCs
RS 7
* Use shielded twist-pair cables.
Wiring Diagram 1

23. MODICON PLC
Available PLCs
Select PLC Type PLC Unit/Port Connection
Modbus RTU Modbus RTU Modbus RS-232C [Wiring Diagram 1]
The recommended communication parameter settings of the PLC and the V7 series is as follows:
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 9600 bps 9600 bps
Data length 8 8
Stop bit 1 1
The available memory setting range varies depending on the PLC model. Be sure to set within the range available with the PLC to be used. Use [TYPE] when assigning the indirect memory for macro programs.
4 (holding register) 0
3 (input register) 1
0 (output coil) 4
1 (input relay) 6 Read only

Wiring
Wiring diagrams with the PLC are shown below.
V7 (CN1)
RX
RD
TX
RS
DTR
CS
GND 5
SG
DSR 6
Connection to PLCs
RTS 7
* Use shielded twist-pair cables.
Wiring Diagram 1 · D-sub 25-pin (male) · D-sub 9-pin (male)

24. YAMATAKE PLC
Available PLCs
Select PLC Type PLC Unit/Port Connection
MX series MX200/MX50 ASCII connector RS-232C [Wiring Diagram 1]
The recommended communication parameter settings of the PLC and the V7 series is as follows:
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 9600 bps 9600 bps
Data length 8 8
Stop bit 1 1
The available memory setting range varies depending on the PLC model. Be sure to set within the range available with the PLC to be used. Use [TYPE] when assigning the indirect memory for macro programs.
R (data register) 0
M (auxiliary relay) 1
L (latch relay) 2
X (input relay) 3
Y (output relay) 4
TP (timer/current value) 5
TS (timer/setting value) 6
CP (counter/current value) 7
CS (counter/set value) 8
P (link register) 11

Wiring
Wiring diagrams with the PLC are shown below.
V7 (CN1)
SD
RD
RD
RS
RS
CS
CS 5
SG
SG 7
Connection to PLCs
* Use shielded twist-pair cables.
Wiring Diagram 1 · D-sub 25-pin (male) · D-sub 25-pin (male)

25. TAIAN PLC
Available PLCs
Select PLC Type PLC Unit/Port Connection
Communication Port (T/R+, T/R−) RS-422 [Wiring Diagram 1]
MMI Port (9pin) (4-5 Short Computer Link Mode)
RS-422 [Wiring Diagram 2]
The recommended communication parameter settings of the PLC and the V7 series is as follows:
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 19200 bps 19200 bps
Parity Not provided Not provided
Data length 7 7
Stop bit 1 1
The available memory setting range varies depending on the PLC model. Be sure to set within the range available with the PLC to be used. Use [TYPE] when assigning the indirect memory for macro programs.
D (data register timer•counter/contact) 0
WS (system register) 2
WC (constant register) 3
X (input relay) 4
Y (output relay) 5
C (internal relay) 6
SC (special register) 7

Wiring
Wiring diagrams with the PLC are shown below.
- SD
T/R -
SG
PLC
+SD
T/R+
- RD
SHLD
+RD
Connection to PLCs
* Use shielded twist-pair cables.
- SD
SG
RX+
+SD
TX+
- RD
RX - 7
PG/COM
TX - 8
+RD
GND 5
* Use shielded twist-pair cables.

26. SAIA PLC
Available PLCs
Select PLC Type PLC Unit/Port Connection
PGU port RS-232C [Wiring Diagram 1]
PCD7.F120 RS-232C [Wiring Diagram 2]
PCD4.F110 RS-485 [Wiring Diagram 3]
The recommended communication parameter settings of the PLC and the V7 series is as follows:
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 19200 bps 19200 bps
Data length 8 8
Stop bit 1 1
S-BUS Mode Parity GU Port Number 0 (PGU port), 1 (PCD7.F120, PCD4.F110)
The available memory setting range varies depending on the PLC model. Be sure to set within the range available with the PLC to be used. Use [TYPE] when assigning the indirect memory for macro programs.
R (register word) 0
T (timer-counter word) 2
C (timer-counter coil) 3
I (input bit) 4 read only
O (output bit) 5
F (flag bit) 6

Wiring
Wiring diagrams with the PLC are shown below.
V7 (CN1)
PLC
FG
SD
RX
RD
TX
SG
GND
* Use shielded twist-pair cables.
V7 (CN1)
PLC
FG
PCD7.F120
SD
TX
RD
RX
SG
GND
* Use shielded twist-pair cables.
V7 (CN1)
PLC
FG
PCD7.F110
SG
GND 10
T/R+
+SD
− SD
T/R −
+RD
− RD
* Use shielded twist-pair cables.

27. MOELLER PLC
Available PLCs
Select PLC Type PLC Connection
RS-232C [Wiring Diagram 1]
PS4 PS4-201-MM1 (PRG port)
+ ZB4-303-KB1 Cable made by MOELLER
The recommended communication parameter settings of the PLC and the V7 series is as follows:
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 9600 bps 9600 bps
Parity Not provided Not provided
Data length 8 8
Stop bit 1 1
The available memory setting range varies depending on the PLC model. Be sure to set within the range available with the PLC to be used. Use [TYPE] when assigning the indirect memory for macro programs.
M (marker) 0 MW as word device
Port 1 1 · Transmission code · Memory TYPE Remarks

Wiring
Wiring diagrams with the PLC are shown below.
V7 (CN1)
PLC
FG
SD
TX
RD
RX
SG
SG
* Use shielded twist-pair cables.
Wiring Diagram 1 · D-sub 25-pin (male) · D-sub 9-pin (male)

5-130 28. Telemecanique PLC
Available PLCs
Select PLC Type PLC Connection
TSX Micro TSX Micro RS-485 [Wiring Diagram 1]
The recommended communication parameter settings of the PLC and the V7 series is as follows:
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 9600 bps 9600 bps
Connection – Multi-Link (fixed)
Data length 8 (fixed) 8
Stop bit 1 1
The available memory setting range varies depending on the PLC model. Be sure to set within the range available with the PLC to be used. Use [TYPE] when assigning the indirect memory for macro programs.
MW (memory word) 0
KW (constant word) 1
M (bit memory) 2
Parity Odd Odd · Transmission code · Memory TYPE Remarks

Wiring diagrams with the PLC are shown below.
V7 (CN1)
PLC
FG
+SD
D+
− SD
D −
+RD
− RD
* Use shielded twist-pair cables.
Wiring Diagram 1 · D-sub 25-pin (male) · MiniDIN 9-pin (male)

5-132 29. Automationdirect PLC
Available PLCs
Select PLC Type PLC Unit/Port Connection
RS-232C [Wiring Diagram 1] RS-422 [Wiring Diagram 5] D4-440 Port 1 on a CPU unit
D4-450 Port 3 on a CPU unit RS-485 [Wiring Diagram 6]
Port 2 on a CPU unit
RS-232C [Wiring Diagram 2] D2-240 Port 2 on a CPU unit
D2-250 Port 2 on a CPU unit RS-232C [Wiring Diagram 3]
RS-232C [Wiring Diagram 1] RS-422 [Wiring Diagram 5] D4-440 Port 1 on a CPU unit
Port 0 on a CPU unit RS-232C [Wiring Diagram 4]
Port 3 on a CPU unit RS-485 [Wiring Diagram 6]
Port 2 on a CPU unit
Port 1 on a CPU unit
RS-232C [Wiring Diagram 2] D2-240
Port 2 on a CPU unit
Port 1 on a CPU unit
Port 2 on a CPU unit RS-232C [Wiring Diagram 3]
The recommended communication parameter settings of the PLC and the V7 series is as follows:
Item Setting on PLC V7 Comm. Parameter Setting
Baud rate 19200 bps 19200 bps
Port “0” for ×10, “1” for ×1 1
Data length 8 8
Stop bit 1 1
Function Host link system (fixed) −
Response delay time 0 (fixed) −
Time-out None (fixed) −
ASCII/HEX HEX (fixed) −

The available memory setting range varies depending on the PLC model. Be sure to set within the range available with the PLC to be used. Use [TYPE] when assigning the indirect memory for macro programs.
V (data register) 0
X (input relay) 1
Y (output relay) 2
C (internal relay) 3
GX (global inputs) 5
GY (global outputs) 6
Wiring
Wiring diagrams with the PLC are shown below.
V7 (CN1)
PLC
FG
SD
SD
RD
RD
RS
RS
CS
CS
7 SG 7
SG
* Use shielded twist-pair cables.

5-134 29. Automationdirect PLC
PLC
FG
SD
SG
RD
RS 4
CS 5
SG 7
* Use shielded twist-pair cables.
D-sub 15-pin (male) *1
FG
SD
TXD
RD
RXD
RS
RTS
CS
CTS
7 SG 7
* Use shielded twist-pair cables. *1 High density D-sub 15-pin
PLC
FG
SD
TXD
RD
RXD
RS
CS
SG 7
* Use shielded twist-pair cables.

V7 (CN1)
PLC
FG
SG 7 SG 7
+SD
RXD+
− SD
RXD −
+RD
CTS1+
− RD
TXD1+
TXD1 −
RTS1+
RTS1 −
* Use shielded twist-pair cables.
CTS1+
V7 (CN1)
PLC
FG
SG 7 SG 7
+SD
TXD3+
− SD
TXD3 −
+RD
RXD3+
− RD
RXD3 −
In case SU-6M, it is possible to use terminal blocks,
* Use shielded twist-pair cables.

5-136 29. Automationdirect PLC
Please use this page freely.

Hakko Electronics Co., Ltd.
238, Kamikashiwano-machi, Matto-shi, Ishikawa, 924-0035 Japan TEL (076)274-2144 FAX(076)274-5208
TEL (06)6385-8234 FAX(06)6385-7851 Osaka Office
TEL (052)789-0096 FAX(052)789-0098 Nagoya Office
209-2, Koh, Mameda-honmachi, Kanazawa-shi, Ishikawa, 920-0047 Japan
20903000 2010NE0
Sales · Tokyo Office · Head Office
What the fault codes shown on the display mean and how to clear them.
| Code | Meaning | Fix | |
|---|---|---|---|
| CN1 | It is recommended that CN1 be equipped with a terminal converter “TC485” | p.109 | |
| 0000H | Normal | p.147 | |
| 8001H | Check code error | p.147 | |
| 8002H | Data error | p.147 | |
| 800BH | Error code received from the PLC connected at the MJ port | p.147 | |
| −1 | Undefined command (receive timeout) | Check the command. | p.194 |
| −2 | Undefined IP address | Check the IP address. | p.194 |
| −3 | Target station busy | Reduce the frequency of communications. | p.194 |
| −4 | Illegal packet bytes | Check response processing at the target station. | p.194 |
| −5 | Packet bytes exceed the maximum number. | Reduce the send packet size. | p.194 |
| −6 | Local mode error | Check that the target station is in the RUN mode. | p.194 |
| −7 | Preparing for communications | Start communications when the target station is ready. | p.194 |
| −8 | Communication failure – Cannot access | Check the target station. | p.194 |
| −9 | Cannot process due to short memory | Check the memory space at the target station. | p.194 |
| −10 | Illegal received data | Check the command. | p.194 |
| −20 | Socket initialization error | Check parameters for initialization. | p.194 |
| −50 | Requested packet byte exceeds the maximum number. | Reduce the requested size. | p.194 |
| −51 | Address error | Check the requested memory type. | p.194 |
| −52 | Communication failure – Cannot access | Check the target station. | p.194 |
| −54 | Write protected | Check write-protection of the card. | p.194 |
| −55 | Cannot process due to short memory | Check the memory space at the target station. | p.194 |
| −56 | Sampling buffer error | Check the command. | p.194 |
| −100 | Processing another command | Continue retrying. | p.194 |
| −101 | Command control – Buffer over | Reduce the frequency of communications. | p.194 |
| −120 | Communications aborted by the user | Communications are forcedly aborted. | p.194 |
| −121 | Received during command processing | Reduce the frequency of communications. | p.194 |
| RS-232C | . . . ENABLE | p.275 | |
| RS-422 | . . . . . DISENABLE | p.275 |