Product Specification/Installation Sheet
Description

The Universal Monitor is a microprocessor with multi- sensing, remote monitoring and remote control capabilities. Its advanced technology provides high- availability monitoring around the clock.
The Universal Monitor can operate as an independent, stand-alone controller or in conjunction with Liebert’s SiteScan Web Enterprise Monitoring System.
The enclosure of the Universal Monitor makes it suited for various applications in both new construction and retrofit jobs. The Universal Monitor can be mounted on a wall’s surface or recessed within a wall.
The keypad display on the face of the panel is a standard part of the Universal Monitor.
Battery pack Power On/Off switch

The display, the gateway to all configuration and monitoring, is password-protected.
Manual override switch (outputs)
The Universal Monitor has a standard, on-board modem for remote monitoring via a telephone line.
OUTPUT2 OUTPUT3 OUTPUT4 OUTPUT5 OUTPUT6 OUTPUT7 OUTPUT8 CTRLLOCK SENLOCK CMN ALR
MOP F PROG 574 TX 574 RX 485 RX 485 TX
The modem is preconfigured to work with the panel, eliminating configuration and setup requirements.
Serial interface connector (RS232/EIA574)
SiteScan Web connector (EIA422)
*Transformer module comes standard in large enclosure only

Two sizes of enclosures provide flexibility and expansion to meet evolving application needs. Both sizes of enclosures come standard with a liquid crystal display (LCD) and controller board. In addition, the large Universal Monitor has an internal Transformer Module.
The enclosure features a key lock for added security and is made of metal to accommodate secure conduit fittings and protect components against environmental debris. The enclosure is designed for easy wire routing and terminations, with top and bottom access slots for communication cables and network wires. The enclosure is 2-3/4" deep, allowing for recess mounting in a wall.
Transformer Module

The keypad display is a user interface mounted on the enclosure door of each Universal Monitor. The display provides for complete monitoring and configuration of the panel and is password-protected.

The large Universal Monitor comes with either 115VAC or 230VAC Transformer Module.
Keypad

The keypad display provides the ability for the Universal Monitor to operate as a complete standalone panel.
The controller board supports 22 points:
The Transformer Module may be ordered separately as an option for the small Universal Monitor—or any device requiring 24VAC—and mounted outside the enclosure.
The digital inputs are dry contacts. The analog inputs are 4-20mA inputs. The digital outputs and Common Alarm outputs are Form C contact relays.
The point terminations are made using removable terminal blocks. This allows for easier access to the terminators, streamlining the process of connecting external devices to the Universal Monitor.
The Universal Monitor I/O Expansion Module, pur- chased separately, has connectors for 16 digital inputs and eight digital outputs, as shown below. The board has light emitting diodes (LEDs) to dis- play the status of monitored output devices, commu- nications ports for connection to the Universal Monitor, power connections and other features nec- essary to monitor and protect your operation.
The battery supplies power to the modem for a mini- mum of 10 minutes, providing the capability to send out a loss-of-power alarm to all configured pagers.
Flash ROM may be easily upgraded at the job site, simplifying the process of installing new firmware as it becomes available.
& Key Features
An RS232 operator terminal port is included with each controller board for easy interface to a laptop or desktop PC for setup and device monitoring.
Digital output connectors (8)

An integrated on-board modem is included with each controller board for remote access to the Universal Monitor. An RJ11 phone modem jack is also included. The modem is factory-configured, eliminat- ing field configuration and wiring requirements.
Digital output fuses (8)
EIA485 + (to UM-) 0V EIA485 - (to UM+)
Digital output DIP switch
An IGM422 connection is included with each control- ler to connect the Universal Monitor to Liebert’s SiteScan Web Enterprise Monitoring System. This connection allows information and alarms to be mon- itored from a centrally located command center.
Digital input connectors (16) EIA485 connector
24VAC power connector


SMALL ENCLOSURE & I/O EXPANSION MODULE
(115V & 230V)

14" (355.6mm)
3.83" (97.2mm)
2.65" (67.3mm)
Wiring Specifications


© 2005 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice.
® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
SL-31061 (2/05) Rev. 1