





5.4 Modbus Slave Functions 21 5.4.1 Data Type 21 5.4.2 Function Code Support 22 5.4.3 Read/Write Holding Registers (0x03, 0x06, 0x10) 22 5.4.4 Read Input Registers (0x04) 22 5.4.5 Read, Set Coil Status (0x01, 0x05, 0x0F) 22 5.4.6 Read Input Status (0x02) 23 5.4.7 Error Handling 23 5.5 RTU Framing Examples 24 5.5.1 Read Registers (Function Code 0x03 & 0x04) 24 5.5.2 Write single holding register (Function Code 0x06) 24
6.0 NIC SETUP AND TESTING 25 6.1 Jumper Placement 25 6.2 Testing the Network 26 6.3 Service Terminal Troubleshooting 26 6.4 SNMP Troubleshooting 26 6.5 Web Troubleshooting 27 6.6 Modbus Troubleshooting 27
7.0 FIRMWARE UPDATES 28 7.1 Establishing Communication—Necessary Components 28 7.2 Establishing Communication—Service Terminal Settings 29 7.3 Firmware Update Procedure 30
8.0 EXTERNAL ENCLOSURES 33 8.1 Power Connection 33 8.2 Communication Connection 33
9.0 RETROFIT INSTALLATION 34 9.1 Environmental Installation 34 9.1.1 Deluxe System/3 34 9.2 System Wiring (SM, AM, AG Microprocessors) 37

9.3 Power Connection (SM, AM, AG Microprocessors) 37 9.3.1 Power Connection (Level 0 and Level 10 Microprocessors) 37 9.3.2 Communication Connection (SM, AM, AG Microprocessor) 38 9.3.3 Communication Connection (Level 0 and Level 10 Microprocessors) 38 9.4 Himod (LNA) 38 9.4.1 System Wiring (Himod) 39 9.4.2 Power Connection (Himod) 39 9.4.3 Communication Connection (HiMod) 39 9.5 Mini-Mate2 39 9.6 Emerson Network Power (CEMS100 / LECS15) 40 9.7 UPS Installation 40 9.8 Npower 40 9.8.1 Power Connection for NPower 40 9.8.2 Communication Connection for NPower 40 9.9 7200 UPS 42 9.10 HiPulse UPS 44 9.11 Static Switch2 46 9.12 STS 47 9.13 PDU and DataWave with PMP & EPMP 47


The OpenComms NIC Card transforms Liebert units into manageable nodes within your Network, NMS, and BMS systems. The OpenComms NIC Card contains a standard Ethernet and EIA-485 (2-wire) port designed to support viewing and management through:
Figure 1 Typical installation of OpenComms NIC card

Introduction

1.1 OpenComms Compatibility The OpenComms NIC may be installed and used with these units: Environmental Units
Introduction

Table 1 OpenComms availability
1 Requires an external enclosure assembly 2 Contact your sales / service representative or liebert global services for installation. 3 For Australian units, contact the international sales department @ YC.KOK@emersonnetwork.com.au
Retrofit Kits are designed specifically for individual units. Consult your local Emerson and Liebert sales representative for pricing, part numbers and installation help.
Introduction

Introduction · Table 2 Specifications

The OpenComms NIC card may be ordered as a factory-installed option, and it may be installed as a kit for field retrofit to existing Lie- bert units or as a self-contained unit in its own enclosure. If ordered as a factory-installed option, proceed to 2.3 - User Connec- tions for OpenComms NIC.
2.1 Retrofit Kit As a retrofit kit, the circuit board is secured to a metal mounting plate. The mounting plate then is attached to a flat metal surface in a low-voltage section of the Liebert unit.
2.2 Self-Contained Unit The self-contained model packages the interface card inside a steel enclosure, for mounting external to the Liebert unit. A low-voltage transformer is also provided.
Input Power (Input to TB3)
Network Port for NMS and Web access

DTE Serial Port for Configuration Modbus Output for BMS

2.3 User Connections for OpenComms NIC The OpenComms NIC can use simultaneous connections, sometimes requiring three user connections:
2.3.1 Network Port Consult with the network administrator or other responsible party for arranging a network drop to the Liebert equipment. The OpenComms NIC communicates via standard 10 Base-T Ethernet network connec- tion. Route the 10 Base-T cable to the Liebert unit and connect to J3, the RJ45 jack on the interface card. The OpenComms Network card will operate with any 10 Base-T Ethernet, regardless of operating sys- tem used.
2.3.2 BMS Port The Modbus 485 connection will use the terminals marked “Repeater.” (TB2) The Modbus server uses RTU protocol and will allow for a maxi- mum of 32 units on 4000ft. of wire on a common line. EIA-485 repeat- ers may be necessary to accommodate additional units or longer cables. Point availability may be referenced in the document, “NIC Reference Library,” which may be downloaded at www.liebert.com under the OpenComms product family.
2.3.3 Configuration Port / Service Terminal A temporary serial connection to the interface card is necessary for configuration and setup. Using a DB9F-DB9F null-modem cable, connect the “DTE Serial Port” P18 to an ASCII terminal or computer running terminal emulation application. HyperTerminal® and Procomm® are examples of termi- nal emulation applications running on Microsoft Windows® operating systems. All trademarks are property of their respective owners.
Installation

Accessing the Configuration Port What you will need:
Figure 3 Null modem cable diagram
Null Connection DTE Device Receive Rx (pin2)
DTE Device Receive Rx (pin2)


Installation · Transmit Tx (pin3) · Transmit Tx (pin3)

the Enter key on your keyboard. This will initiate communications with the card and the following screen should be displayed.
Figure 4 NIC main menu in HyperTerminal

(You can also cycle power on the OpenComms NIC card. This will also initiate communications and provide information on current revision status.) 6. When the message “Initializing Network…” appears, hit the Enter key on your keyboard. (Additional network information may appear)
! CAUTION Cycling power on either the 7200 or the HiPulse UPS is not recommended unless the unit is in bypass mode. Consult the UPS user manual for further instructions.
Installation

3.1 DIP Switch Settings A four-position DIP switch is provided, but no user configuration via DIP switches is necessary at this time.
3.2 Service Terminal Refer to Accessing the Configuration Port on page 7 for explicit details on accessing the service terminal / configuration port. By default, the service terminal communication parameters are:
! CAUTION Cycling power on either the 7200 or the HiPulse UPS is not recommended unless the unit is in bypass mode. Consult the UPS user manual for further instructions.
System Configuration

Table 3 Service terminal navigation
Main Menu 1. System Information 1.1 Name 1.2 Contact 1.3 Location 1.4 Description 2. Network Settings 2.1 Boot / IP Settings 2.1.1 Boot Mode 2.1.1.1 Static 2.1.1.2 BootP 2.1.1.3 DHCP 2.1.2 IP Address 2.1.3 Netmask 2.1.4 Default Gateway 2.2 SNMP Communications 2.2.1 SNMP agent (enable/disable) 2.2.2 Authentication Traps (enable/disable) 2.2.3 Display / Modify Communities 2.2.4 Display / Modify Trap Communities 2.3 Web Server 2.3.1 Web Server (enable/disable) 2.3.2 Configuration Control (enable/disable) 2.3.3 Refresh rate 2.4 Telnet Server 2.4.1 Telnet server (enable/disable)
System Configuration

System Information Menu The System Information Menu seeks descriptive input to enable the unit to be identified. This data is readable via SNMP queries. The (“) character is not permitted in any of the descriptive fields
Network Settings Menu The Network Settings Menu configures network parameters essential for proper network operation. The network administrator or other per- sonnel responsible for the network should be consulted for the proper parameters to be entered in this menu. In the static mode, the IP address is entered. Use the standard four- part dotted decimal format. The NetMask and Default Gateway should also be entered in dotted decimal format. The NetMask, also known as subnet mask, delineates devices on the same physical net- work segment, versus devices that require the services of a network router for access to other networks. The Default Router is the address of default router on the local segment.
! CAUTION Consult your network administrator to ascertain the parameters appropriate to your network.
BOOTP and DHCP Mode The OpenComms NIC supports DHCP and BOOTP if a DCHP or BOOTP server must exist on the network. When this feature is enabled, at boot-up the card will perform a DHCP or BOOTP request for configuration information, including automatic assignment of an IP address. If the card receives the information, no further requests are made. If, at boot-up, a response is not received, the card will con- tinue to send a request approximately every 30 seconds until a response is received. When this condition is encountered, pushing the key returns the unit to the service terminal mode.
SNMP Communications Menu The SNMP (Simple Network Management Protocol) Communications Menu specifies parameters particular to the SNMP interface. Commu- nities are used as a means of security for SNMP v1; only specified hosts with the appropriate community name(s) are allowed to perform particular SNMP operations. Up to 20 different communities can be assigned. For each community, specify the dotted decimal IP address of the remote host, the privilege level (read or read/write), and community name. Trap Communities specify the recipient(s) of SNMP trap mes- sages generated by the OpenComms Network Interface Card. Typi- cally; the recipient is the management station of the NMS. Specify the
System Configuration

destination IP address, and the community name for that host. Up to 20 trap communities can be assigned. For Communities and Trap Communities, the information can be entered as a “complex” line — all parameters space-delimited on the command line. Otherwise, the menu items will prompt for each individual parameter.
Authentication failure traps may be enabled, so that the network management system can be warned when unauthorized access (i.e.: incorrect community name) is attempted.
Web Server The Web Server section will allow the user to disable / enable the HTTP session for the card. Disabling the Web Server means that web browsers will not be able to access the devices status graphical page (GUI).
Telnet This section allows users to enable or disable the Telnet session.
Change User Name / Password This section allows users to set or change the default user name and password.
Firmware Updates Menu The Firmware Update Menu is intended for Liebert service personnel only. No user configurable parameters are accessed in this selection. If entered, to escape, power must be cycled on the card.
Factory Settings Menu The Factory Settings Menu displays the manufacture date, serial number and MAC address of the card. These parameters are read- only. Once all parameters have been entered, press Escape to return to the Main menu; then press x to save configuration, exit and reboot to enable the new configuration. All parameters are stored in non-vol- atile flash memory. Pressing q after Escape will abort all changes. Neither selection is case-sensitive.
System Configuration

Auxiliary Communications The Auxiliary Communications Menu allows the user to set up the parameters necessary for Modbus communications. The user can enable / disable the Modbus sessions as well as assign the slave ID. Q. <q> will abort all changes. X. <x> will save configuration changes.
Once all parameters have been entered, press to return to the Main menu; then press exit and reboot using the new con- figuration. All parameters are stored in non-volatile flash mem- ory. Neither selection is case-sensitive.
System Configuration

4.1 SNMP The OpenComms Network Interface Card supports “get,” “getnext,” “set,” “response” and “trap” packets of SNMP (Simple Network Man- agement Protocol). The OpenComms NIC supports MIB-II, RFC1628 and Liebert Global Products MIBs. The terms “alarms” and “condi- tions” will be used interchangeably through out this description. Alarms are generated and maintained through the RFC 1628 UPS MIB. Conditions are generated and maintained through the Liebert Global Products MIB. The RFC 1628 UPS MIB provides information for the supported UPS devices. The Liebert Global Products MIB provides information for the supported environmental devices. All conditions that are listed are dependent upon what the unit itself supports. When a condition occurs within the unit, it is logged into the condition table within the appropriate MIB and a unique ID is assigned. A description of the con- dition along with the value of the system up-time when the condition was generated is placed into the table as well. A trap is then sent out to the monitoring system.
4.2 Liebert Global Products MIB Environmental units log conditions in the Liebert Global Products MIB. Traps for the environmental units are generated out of the Lie- bert Global Products MIB. Currently, there are only two traps that are sent for environmental units through the MIB: Event Condition Entry Added and Event Condition Entry Removed. The Event Condition Entry Added is sent each time a condition is inserted into the condi- tions table. This trap provides the condition ID, the condition descrip- tion, and the condition time. The Event Condition Entry Removed is sent each time a condition is removed from the conditions table. This trap provides the condition ID, the condition description, and the con- dition time.
Operation

4.3 RFC 1628 UPS MIB UPS units log alarms in the RFC 1628 UPS MIB. Traps for the UPS units are generated out of the RFC 1628 UPS MIB. There are four traps that may be sent for the UPS units: Trap On Battery, Trap Test Completed, Trap Alarm Entry Added and Trap Alarm Entry Removed. The trap On Battery is sent when the UPS is operating on battery power. This trap will be sent once a minute until the UPS either shuts down or is no longer running on battery power. This trap provides the Estimated Minutes Remaining on Battery, the Seconds on Battery and the Configured Low Battery Time. The Trap Test Completed is sent when a UPS diagnostic test is completed. This trap provides the Test ID of the test that has been performed, the Test Spin Lock, the Test Results Summary, the Test Results Detail, the Test Start Time and the Test Elapsed Time. The Trap Alarm Entry Added is sent when an alarm is placed into the alarm table and provides the alarm ID and the alarm description. This trap is not sent on the following alarms: On Battery and Test In Progress. The Trap Alarm entry Removed is sent when an alarm is removed from the alarm table and provides the alarm ID and the alarm description. This trap is not sent out when the Test In Progress alarm is removed from the alarm table.
4.3.1 SNMP Traps Below is the definition on how events are handled in RFC1628. * Two similar event traps (notifications) are sent to their destination or NMS system. The event traps are differentiated by their trap type. Type 3 = Condition ADDED to the event table, Type 4 = Condition REMOVED from the event table. *Each event trap contains the following three bindings of information: 1. Trap ID. The ID represents the location or placeholder in the table to find event information. 2. The OID reference of the well-known alarm. Note: Below are the OID references for RFC1628 alarms. These are not Liebert-unit specific, but rather RFC1628 specific. 3. Time ticks or system uptime that represents when an event occurred.
Operation
![Page 22 of the Emerson MONITORING OpenComms user manual — [OIDALARMS]](/cdn/reader/05/056b245c34abd994a3b34e46cdd1ba7b39db5ba881018087cfdae6b75cc308a4/images/page-22.webp?w=400)
1.3.6.1.2.1.33.1.6.3.1:upsAlarmBatteryBad{} 1.3.6.1.2.1.33.1.6.3.2:upsAlarmOnBattery{} 1.3.6.1.2.1.33.1.6.3.3:upsAlarmLowBattery{} 1.3.6.1.2.1.33.1.6.3.4:upsAlarmDepletedBattery{} 1.3.6.1.2.1.33.1.6.3.5:upsAlarmTempBad{} 1.3.6.1.2.1.33.1.6.3.6:upsAlarmInputBad{} 1.3.6.1.2.1.33.1.6.3.7:upsAlarmOutputBad{} 1.3.6.1.2.1.33.1.6.3.8:upsAlarmOutputOverload{} 1.3.6.1.2.1.33.1.6.3.9:upsAlarmOnByPass{} 1.3.6.1.2.1.33.1.6.3.10:upsAlarmBypassBad{} 1.3.6.1.2.1.33.1.6.3.11:upsAlarmOutputOffAsRequested{} 1.3.6.1.2.1.33.1.6.3.12:upsAlarmUpsOffAsRequested{} 1.3.6.1.2.1.33.1.6.3.13:upsAlarmChargerFailed{} 1.3.6.1.2.1.33.1.6.3.14:upsAlarmUpsOutputOff{} 1.3.6.1.2.1.33.1.6.3.15:upsAlarmUpsSystemOff{} 1.3.6.1.2.1.33.1.6.3.16:upsAlarmFanFailure{} 1.3.6.1.2.1.33.1.6.3.17:upsAlarmFuseFailure{} 1.3.6.1.2.1.33.1.6.3.18:upsAlarmGeneralFault{} 1.3.6.1.2.1.33.1.6.3.19:upsAlarmDiagnosticTestFailed{} 1.3.6.1.2.1.33.1.6.3.20:upsAlarmCommunicationsLost{} 1.3.6.1.2.1.33.1.6.3.21:upsAlarmAwaitingPower{} 1.3.6.1.2.1.33.1.6.3.22:upsAlarmShutdownPending{} 1.3.6.1.2.1.33.1.6.3.23:upsAlarmShutdownImminent{} 1.3.6.1.2.1.33.1.6.3.24:upsAlarmTestInProgress{} To summarize, event traps generally are parsed by the NMS for any of the information contained in the trap. A process should be put in place by the NMS to recognize whether the event trap is a new condition or a cleared condition by looking at the trap type. Likewise, the NMS should be able to extract the second binding of the trap notification to see the OID of the well-known alarm. This OID reference will allow the NMS to extract the well-known name or description of the event.
Operation

4.4 MIB The Management Information Base (MIB) is a formal document declaring the specifics of the information supported by the SNMP implementation. The administrator for the NMS (or other applications utilizing SNMP to communicate with the Liebert units will need the MIB in order to integrate the Liebert units into the monitoring sys- tem. The MIB files are contained on the CD that ships with the product. Alternatively, the MIBs for the OpenComms Network Interface Card are available for download at www.liebert.com. Navigate through Products, then Site Monitoring & Software and proceed to the Open- Comms support information area. The RCF 1628 MIB can be down- loaded at www.ietf.org.
4.5 HTTP Status and alarm information can be queried by Web browsers via HTTP v1.1 (Hyper Text Transfer Protocol). The data is shown in an intuitive graphical format, akin to the unit’s front bezel controls. These browsers have been tested and are supported:
4.6 Modbus RTU See 5.0 - Modbus Communications and Connectivity for a com- plete explanation of the Modbus slave.
4.7 System Reset The OpenComms Network card contains an on-board real time clock and watchdog circuitry. The card is self-monitoring and self-correct- ing. However, a push button is provided to permit a manual system reset. The reset push button is labeled S1 on the interface card: press and hold it for 3 seconds before to releasing to initiate hardware reset.
Operation

4.8 Diagnostics A number of LEDs are provided on the interface card to provide infor- mation for diagnostic purposes. The following table summarizes their indications:
DS1 Ethernet Port Collision
DS2 Ethernet Port Receive
DS3 Ethernet Port Transmit
DS4 Ethernet Port Link
DS7 Repeater Port Receive
DS8 IGM Port Receive
DS9 Microprocessor in Operation
DS10 Serial Port Receive
DS11 Serial Port Transmit
DS12 Repeater Port Transmit
DS13 IGM Port Transmit
Figure 5 LED locations
DS9
DS13 DS8

Modbus Communications and Connectivity
This section describes the Modbus communications protocol as sup- ported by the OpenComms NIC card. It includes information on how to pass information to and from the OpenComms NIC card via Mod- bus. It is also intended to help facilitate answering questions regard- ing supported types, frame format, function code support etc.
5.1 Implementation Basics Protocol controls the language structure or message format between devices in other words, the rules for communication. The rules for communication include how master and slave devices initiate commu- nications, as well as unit identification, message handling and error checking. Modbus protocol simply refers to the control of the query and response cycles between master and slave devices. The OpenComms NIC module is configured to act as a slave device on a common network. The common network is a multi-drop or “daisy chain” configuration over EIA-485, where multiple slaves reside on a common wire or loop.
5.1.1 Constraints The OpenComms NIC communicates with local database and there- fore is subject to the time delay resulting from the local database updating policies. Use of “Preset Multiple Holding Registers” and “Preset a single Holding Register” functions requires accessing the Liebert device connected and to the OpenComms NIC card database service. Users should be aware that the Modbus application coexists with other on-board application servers (HTTP and SNMP specifi- cally) and competes for the database service and CPU time. This may lead to uncertainty of responding time of the OpenComms NIC. The user or third party integrator may have to compensate for the delay time if HTTP, SNMP and Modbus are going to be utilized simulta- neously.
5.2 Transmission Format The OpenComms NIC module supports Modbus RTU (Remote Termi- nal Unit) transmission modes. The OpenComms NIC communication rate is fixed at 9600 baud, 8 data bits, No parity, 1 Stop bit. The com- munication media is fixed using EIA-485 standards.

Modbus Communications and Connectivity
5.3 Physical Connection A Modbus network should consist of one, and only one, host client, and up to 255 slaves uniquely identifiable by their slave ID. The slave ID of each OpenComms NIC is set through the service terminal (configu- ration) port. (See section 3, System Configuration for more details.) The OpenComms NIC supports multi-drop connection over RS485. On the OpenComms NIC, a client should connect to the OpenComms NIC as a multi-drop connection via the RS485 “Repeater” port (TB2), (Pin1 as minus and Pin2 as plus. J28-1 and J28-2 should be shorted.) The OpenComms NIC card is designed to reside on a maximum com- mon line of 32 devices with a total cable length of 4000 feet. In a “nor- mal environment” all devices should be connected in “daisy-chain” fashion, with “star configurations” or branches, being used at a mini- mum. See Figure 6 for details. A “normal environment” consists of an installation where noise or electrical interference is minimal. This is typical of communication wiring run in properly grounded conduit or in areas where high voltage or radio transmissions are not present. Otherwise, these conditions are designated as “noisy.”
Figure 6 Typical maximum installation
The recommended cable characteristics are: Normal Environments:

Modbus Communications and Connectivity
Figure 7 Exceeding maximum specifications

The maximum specification may be exceeded if measures are taken to drive or boost the EIA-485 communication line. Two wire EIA485 repeaters are available through the Liebert Corporation. SiteScan’s “REPOPT” will work sufficiently for this application. Consult the SiteScan price book for pricing schedule and alternative solutions.
5.4.1 Data Type The OpenComms NIC supports data in a register block as one of the following types: Signed integer (16 bit) / Unsigned integer (16 bit) / Signed long (32 bit); IEEE floating-point (32 bit); Null terminated String. A datum should consist of one or multiple registers. The leftmost byte contains the MSB and the rightmost byte contains the LSB.

Modbus Communications and Connectivity
5.4.2 Function Code Support The OpenComms NIC implements the following Modbus functions. However, integrators will use function code 0x03, and 0x06 most often due to the type of data to be acquired.
0x01 Read Coil Status
0x02 Read Input Status
0x03 Read Holding Registers
0x04 Read Input Registers
0x06 Write Single Holding Register
0x0F Force Multiple Coils
0x10 Preset Multiple Holding Registers
5.4.3 Read/Write Holding Registers (0x03, 0x06, 0x10) A holding register is a 16-bit message unit. In principle, a message in a holding register is write / readable, but holding registers can be used by read-only data as well. Holding registers are mapped into 40001-49999 logic address range. Holding registers can be read by function code 0x03. A maximum of 125 registers can be read by a single query. Function code 0x06 requests the server to change the content of a sin- gle holding register, and function code 0x10 requests server to change the contents of multiple holding registers adjacent to each other.
5.4.4 Read Input Registers (0x04) The input register block contains read-only data accessible to the user. A datum in the input register block occupies one or multiple registers such as described in the previous section. The input registers are mapped into 30000-39999 of the logic address range. Up to 125 input registers can be read by a single query using function code 0x04.
5.4.5 Read, Set Coil Status (0x01, 0x05, 0x0F) Coil status contains bit-mapped status accessible to the users. In prin- ciple, a coil status can be read, set or cleared by the host client. Multi- ple coil status can be read by specifying the index of bits of the first coil and the number of consecutive coils in a single query. Coil status can be read by function code 0x01. Function code 0x05 set or clear a single coil, and function code 0x0F set or clear multiple coils.

Modbus Communications and Connectivity
5.4.6 Read Input Status (0x02) The input status block contains read-only status accessible to the users. It can be read by using function code 0x02 in the same as read- ing coil status.
5.4.7 Error Handling According to the Modbus specification, the OpenComms NIC composes the following exception responses to the client if an exception or error occurs.
Table 4 Exception response
1 byte 1 byte 1 bytes 2 bytes
Exception codes are:
Modbus Packet Formats Each Modbus packet consists of the following fields:

Modbus Communications and Connectivity
the OpenComms NIC module primarily uses Function Code 3 (Read Holding Registers) and Function Code 6 (Preset Single Register). Data Field(s) The data field varies in length depending on whether the message is a request or a response to a packet. This field typically contains infor- mation required by the slave device to perform the command specified or to pass back data to the master device. Error Check Field The Error Check Field consists of a 16-bit (2 byte) Cyclical Redun- dancy Check (CRC16). It allows the receiving device to detect a packet that has been corrupted with transmission errors.
5.5.1 Read Registers (Function Code 0x03 & 0x04) Query: for reading holding /input registers (requested by a client)
Number of registers to
Index of starting register
1 byte 1 byte 2 bytes 2 bytes 2 bytes
1 byte 1 byte 1 byte 2*m bytes (= Byte Count) 2 bytes
5.5.2 Write single holding register (Function Code 0x06) Query: for writing a single holding register (requested by a client)
Index of the register
16 bit value to be written
1 byte 1 byte 2 bytes 2 bytes 2 bytes
Index of the register
16 bit value been written
1 byte 1 byte 2 bytes 2 bytes 2 bytes



NIC Setup and Testing
6.2 Testing the Network “Ping” is a tool used to test the network. At the command prompt, type, “ping ”. Ping will respond that it received a reply from the card if the card is functioning properly on the network. If the card is not functioning properly or is not connecting to the net- work, ping will respond that the request it sent to the card has timed out. If the ping request times out, go to the Service Terminal to verify that the card initialized the network when it powered up. If the card is sit- ting at the text “Initializing network…” then the card has not con- nected to the network. Hit to go into the Service Terminal. Select No. 2 for the Network Interface Menu. Verify that you have the boot mode set up correctly. If you choose a static IP Address, verify that the IP Address is valid for your network. If you obtain your network information from a BootP or DHCP server, verify that the server is valid and that it is responding to requests. Once the information has been verified, press to return to the main menu and select “x” to exit out of the card. Then, reboot the card. The card may be rebooted by pressing switch S1 on the card for approximately 2 seconds until the DS9 link light turns off. If the card still does not connect to the network, or ping still does not receive a reply from the card, verify proper set up on the card itself. DS4 should be illuminated if the card detects the network. Verify that the network cable is connected to Ethernet port J3 and that the hub/ router/switch to which the card is connected is operating correctly. Once this information is verified, reboot the card.
6.3 Service Terminal Troubleshooting If the card does not bring up a Service Terminal, check link light DS9. DS9 should be illuminated within approximately 0.5 seconds of appli- cation of power. If DS9 is not illuminated and no other LED's are on, verify that power has been applied to the card. If power has been applied, verify wiring connected to TB3 is correct. TB3 should have 24VAC or 12 VDC applied. Reboot the card once the power to the card has been verified.
6.4 SNMP Troubleshooting If SNMP is not functioning, first make sure that the card powers up, the Service Terminal is functioning and the card is connected to the network (verified by using ping). If all of those conditions are met, ver- ify that the community strings are set up correctly. To do this, go into the Service Terminal and select number 3 for SNMP Communications.

NIC Setup and Testing
Then, select number 2 for Display/Modify Communities. Verify that the IP Addresses listed are valid for your network. Verify that you are typing in the correct community name when trying to access SNMP. The community name is case sensitive. Once this information is verified, reboot the card and try to access SNMP again.
6.5 Web Troubleshooting If the card does not serve up a web page, but the Service Terminal is functioning, SNMP is functioning, and the card is connected to the network (verified through ping), then reboot the card. In this case, the web server has been lost and needs to be restarted. If the card serves up a web page, but the web page only displays “Dis- covering connected device…” verify that the card is connected to the desired device. Verify that the link lights DS13 and DS8 are blinking on and off. DS13 indicates that the card is receiving from the con- nected device. DS8 indicates that the card is transmitting to the con- nected device. If neither of the link lights is blinking, check the connection between TB1 and P3. TB1 is used to interface to the Environmental units and to some UPS’s. P3 is used to interface with some UPS’s. If DS13 is blinking and DS8 is not, this indicates a communication problem between the card and the connected device. When this occurs, replace the NIC card and retry connecting to the Web. If the problem persists, change the card in the device that the NIC card is trying to interface with. Try to reconnect to the Web.
6.6 Modbus Troubleshooting If the card does not respond to Modbus requests, verify that DS7, “repeater port receive” is flashing during a request. In proper commu- nications DS12 will also be flashing indicating, “repeater port trans- mit.” Verify proper wiring on the EIA 485 network. OpenComms NIC cards should observe a “plus to plus” and “minus to minus” daisy chain con- figuration. Also verify that the proper slave ID has been set in service terminal. Refer to 3.2 - Service Terminal for initiating a service terminal ses- sion.

The firmware in the OpenComms NIC card can be updated to take advantage of the latest release of software that may contain feature enhancements, new unit compatibility or service patches. The firm- ware is updated through the OpenComms NIC cards’ serial port, using a terminal emulation program like HyperTerminal in MS Windows Operating Systems. This procedure has multiple steps and requires that 3 files be downloaded to the OpenComms NIC card. The latest firmware can be found at this link on the Liebert Web site: http://www.liebert.com/dynamic/displayprod- uct.asp?id=998&cycles=60Hz
! CAUTION Read all instructions before to attempting a firmware download.
Firmware Updates

Firmware Updates

Firmware Updates


11. The screen at right will appear when the download begins. The screen will display the download progress, disappearing when the download is complete. 12. Once the file has completed downloading, a prompt will ask whether you with to continue. Select Y to continue. 13. Select option 2 for Xmodem1K to facilitate a faster download for the remaining files. Press Enter twice to initiate the download of the second firmware file. 14. Select Transfer – Send File… from the HyperTerminal menu. 15. Select 1K Xmodem for the protocol and browse to the location of: OCNIC_REVx.x00.0_BLDxxx_FILE2.s19 16. Select Send; a progress prompt will be displayed. Repeat Steps 11 through 16 to download the third firmware file. It is named OCNIC_REVx.x00.0_BLDxxx_FILE3.s19 The last file is the largest of the three and will take approximately 20 minutes to download.


Firmware Updates

Once the last file is downloaded, the screen at right will appear.

Repeat Steps 2 through 4 to change the baud rate back to 9600 bps as show in the illustration below right. After the communication settings are adjusted, hit the Enter key on your key- board. The screen at right will appear. You can also cycle power on the Open- Comms NIC card. This action will also initiate communications and provide information on current revision status. Once the “Initializing Network…” line appears, hit the Enter key on your key- board. Select X and the card will reboot. To ensure that the latest firmware is downloaded to the OpenComms NIC card, cycle power by removing and restoring the power connection at TB3. The information below will appear.


Firmware Updates

8.1 Power Connection Power for the OpenComms Network card should be sourced from the supplied wall-plug transformer. Use field-supplied wiring to connect the outer terminals on the transformer to the screw connectors at TB3 on the Network Interface card. A field-supplied ground wire attaches to the center terminal on the transformer and connects to the ground- ing stud in the lower corner of the enclosure.
Figure 9 NIC-ENCL1 internal view

To SiteScan connection terminals on unit
Field-supplied use 18AWG Refer to specific unit installation communication connection
8.2 Communication Connection Communications to the OpenComm Network Card is generally estab- lished by using the unit’s SiteScan interface port. The specifics on location and wiring details can be found in the respective unit’s user manual. The unit’s communications port is EIA-422, which measures ~3-5VDC between the positive and negative terminals. The connection is polar- ity sensitive, so use a voltmeter to verify polarity. The connection is positive-to-positive and, negative-tonegative-. The result when the card and the unit are connected together, a voltmeter will measure ~ 3-5 VDC. Once proper communication has been established, voltage readings will fluctuate.
External Enclosures

9.1 Environmental Installation Retrofit kits are designed specifically for individual units. Consult your local Liebert representative for pricing, part numbers and instal- lation help.
9.1.1 Deluxe System/3 Position the OpenComms card in the low voltage/control cavity of the Liebert Deluxe System 3 unit. Refer to Figures 10, 11 and 12 for typ- ical positioning. Use three #8 x 1/2" sheet metal screws to affix mount- ing plate to the environmental unit.
Figure 10 Deluxe System 3 NIC installation

TB2 - Connects to screw terminals 77 and 78 (see schematic)
P25
Retrofit Installation · NIC Board

Figure 11 Deluxe System 3 chilled water control cavity
P25 P43

TB2 - Connects to screw terminals 77 and 78; (see schematic)
Figure 12 ICS control cavity

TB2 - Connects to screw terminals 77 and 78; (see schematic)
P25
Retrofit Installation

Figure 13 Challenger installation location

TB3

TB2 - Connects to screw terminals 77 and 78; (see schematic)
The OpenComms Network card mounts on the Challenger’s L-plate.
Retrofit Installation · Electric Panel

9.2 System Wiring (SM, AM, AG Microprocessors) Two wiring harnesses are included with the retrofit kit, one for the power connection and the second for communications. They are of suf- ficient length for use with the Deluxe System/3 and ICS units and the microprocessors listed above. For the Challenger product series, use the longer wiring harnesses included with the NIC-K-Chall kit.
9.3 Power Connection (SM, AM, AG Microprocessors) The harness supplied with the OpenComms Network Interface Card (p/n 159084G1) is equipped with three connectors, one at either end of the harness and one in the middle. The harness taps power from the 24 VAC input to the control board of the environmental unit. To con- nect this power to the NIC: 1. 1. Locate the connector containing the two red wires plugged into P43 on the control board and unplug it. Reconnect it to the connector in the middle of the supplied harness. 2. 2. Plug one end of this harness into P43 on the control board and the other end into TB3 of the OpenComms card.
9.3.1 Power Connection (Level 0 and Level 10 Microprocessors) To connect power to the NIC, wire as described above. However, some field modification of the wiring harnesses is necessary for connection to legacy systems. Level 0: Remove the power connector normally plugged into P43 and wire to terminal connections 1-5 (24V)/1-10 (ground).
! CAUTION Do NOT tap power from the auxiliary 24VAC terminals T5/G5 on the SM/AM/AG environmental controllers. Damage to controller and interface card may occur.
Retrofit Installation

9.3.2 Communication Connection (SM, AM, AG Microprocessor) The second wiring harness provided (p/n 159083G1) has a connector fitted at either end and is the communications connection between the unit microprocessor and the NIC. To put it in the system: 1. Remove the existing wire located on P25 of the environmental controller, cut off the red connector and reconnect the wires to TB2 of the interface card. Ensure correct polarity. 2. Connect one end of the wire harness to TB1 of the interface card; the other end connects to P25 of the environmental controller.
9.3.3 Communication Connection (Level 0 and Level 10 Microprocessors) To connect communications wire to the NIC, wire as described above. Some field modifications of the wiring harnesses are necessary for con- nection to legacy systems. Level 0 and Level 10: Remove the red con- nector normally plugged into P25. Wire to terminal connection P25.
9.4 Himod (LNA) Position the OpenComms card in the low voltage/control cavity of the Liebert Himod unit. Refer to the drawing below for typical positioning. Use three #8 x ½” sheet metal screws to affix mounting plate to the Environmental unit.
Figure 14 Himod NIC installation location
Retrofit Installation

9.4.1 System Wiring (Himod) Two wiring harnesses are included with the retrofit kit, one for the power connection and the second for communications. They are of suf- ficient length for use with the Himod unit.
9.4.2 Power Connection (Himod) The harness supplied with the OpenComms Network Interface Card (p/n 159084G1) is equipped with three connectors, one at either end of the harness and one in the middle. The harness taps power from the 24 VAC input to the control board of the environmental unit. To con- nect this power to the NIC: 1. Locate the connector containing the two red wires plugged into P43 on the control board and unplug it. Reconnect it to the connector in the middle of the supplied harness. 2. Plug one end of this harness into P43 on the control board and the other end into TB3 of the OpenComms card.
9.4.3 Communication Connection (HiMod) The second wiring harness provided (p/n 159083G1) has a connector fitted at either end and is the communications connection between the unit microprocessor and the NIC. To put it in the system: 1. Remove the existing wire located on P25 of the environmental controller, cut off the red connector and reconnect the wires to TB2 of the interface card. Ensure correct polarity. 2. Connect one end of the wire harness to TB1 of the interface card; the other end connects to P25 of the environmental controller.
9.5 Mini-Mate2 An enclosure is recommended for use with ceiling-mounted environ- mental units or where internal mounting of the Network Interface Card is not feasible. Older-generation Deluxe and Challenger units may also require external mounting.
Retrofit Installation

9.6 Emerson Network Power (CEMS100 / LECS15) The kit includes a special cable to allow simple interconnection between the controller and the OpenComms NIC. Questions about the retrofit kits should be directed to the Interna- tional Sales department. Contact: yc.kok@emersonnetwork.com.au
9.7 UPS Installation Retrofit kits are designed specifically for individual units. Consult your local sales / service representative for pricing, part numbers and installation help.
9.8 Npower As a minimum there will be an IFM board (communications interface) mounted at the mid-point on the door. Other options may also have been previously installed. The Option boards mount on the inside of the option door. Options can be located in any available option slot, however the OpenComms NIC should be mounted in the bottom most (bottom cable entry) posi- tion.
9.8.1 Power Connection for NPower After mounting the NIC card in the uppermost or lowermost option position, per the instructions above, route the wire harness from TB3 on the lower left of the NIC card to the power supply board on the back of the control door. Follow the routing path indicated in Figure 7.
9.8.2 Communication Connection for NPower Connect the 2-wire harness from TB1 on the bottom center of the NIC card to TB55 on the IFM card. The board is now ready to connect cus- tomer inputs, which should be routed from either the top or bottom cable entry points. Refer to the NPower option manual for any further details on installa- tion. See Figure 15 for single line detail.
Retrofit Installation

Figure 15 NPower UPS NIC installation

OpenComms NIC location (see detail)

9.9 7200 UPS Retrofit Kits are designed specifically for individual units. Consult your local sales / service representative for pricing, part numbers and installation help.
Before installing the kit P/N 4645114G for Network Interface Card (P/N 4590063X), in the 7200 Series UPS, it is necessary to power down that unit. To maintain continuity of supply, the load should first be transferred to the maintenance bypass circuit following the procedure given in the UPS user manual.
Refer to the UPS user manual for more details. If you encounter any problems with the procedures contained in this manual contact your local Liebert representative or Liebert's Cus- tomer Service and Support Department at:
Liebert Hiross Service Customer Service and Support Department Fourth Avenue Globe Park Marlow Buckinghamshire SL71YG Telephone: +44 (0) 1628 403 200 Fax: +44 (0) 1628 403 296
Retrofit Installation

Figure 16 7200 UPS NIC installation


9.10 HiPulse UPS Retrofit Kits are designed specifically for individual units. Consult your local sales / service representative for pricing, part numbers and installation help.
! CAUTION Before installing the kit P/N 4645114D for Network Interface Card (P/N 4590063X), in the HiPulse UPS, it is necessary to power down that unit. To maintain continuity of supply, the load should first be transferred to the maintenance bypass circuit following the procedure given in the UPS user manual.
Refer to the UPS or Network Interface Card user manual for more details. If you encounter any problems with the procedures contained in this manual contact your local Liebert representative or Liebert's Cus- tomer Service and Support Department at:
Liebert Hiross Service Customer Service and Support Department Fourth Avenue Globe Park Marlow Buckinghamshire SL71YG Telephone +44 (0) 1628 403 200 Fax +44 (0) 1628 403 296
Retrofit Installation

Figure 17 HiPulse installation

Retrofit Installation

9.11 Static Switch2 Retrofit kits are designed specifically for individual units. Consult your local sales / service representative for pricing, part numbers and installation help.
Figure 18 STS2 typical NIC location
RS-232 (DB-9 connector) for setup only. Uses standard computer serial port cable
P18
Ethernet Network RJ-45 connector See Notes 1 & 2
NETWORK INTERFACE
+ - See Note 2
Customer-supplied interconnecting cable to Modbus
Figure 19 STS2 NIC installation, 800-1000A units
BOARD (OPTION) PROGRAMMABLE RELAY
PROGRAMMABLE RELAY
BOARD (OPTION)
INPUT CONTACT ISOLATOR
BOARD (OPTION)
CARD (NIC) (OPTION) NETWORK INTERFACE
CONTROL WIRING
Front View With Front Door Removed
EXTERNAL AND INTERNAL
MODEM INTERFACE (OPTION)

Figure 20 STS2 NIC installation, 100 - 600A units
BOARD (OPTION) PROGRAMMABLE RELAY
PROGRAMMABLE RELAY
BOARD (OPTION)
INPUT CONTACT ISOLATOR
BOARD (OPTION)
CARD (NIC) (OPTION) NETWORK INTERFACE
CONTROL WIRING
Front View With Front Door Removed
EXTERNAL AND INTERNAL
MODEM INTERFACE (OPTION)
9.12 STS Retrofit kits are designed specifically for individual units. Consult your local sales / service representative for pricing, part numbers and installation help. STS units require the use of an external enclosure. Consult the corre- sponding section of this manual regarding installation details.
9.13 PDU and DataWave with PMP & EPMP Retrofit Kits are designed specifically for individual units. Consult your local sales / service representative for pricing, part numbers and installation help. All compatible PDU’s and DataWave’s require the use of an external enclosure. Consult the corresponding section of this manual regarding installation details.

Retrofit Installation



Web Site www.liebert.com
Monitoring 800-222-5877 monitoring@liebert.com Outside the US: 614-841-6755
800-222-5877 upstech@liebert.com Outside the US: 614-841-6755
800-543-2378 powertech@liebert.com Environmental Systems
800-543-2778 Outside the United States
614-888-0246 Locations United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229
Italy Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) +39 049 9719 111 Fax: +39 049 5841 257
Asia 23F, Allied Kajima Bldg. 138 Gloucester Road Wanchai Hong Kong +852 2 572 2201 Fax: +852 2 831 0114
Technical Support/Service · Single-Phase UPS · Three-Phase UPS
Pages referenced in this manual — manufacturer, support and downloads.
Owners and our team usually reply within a day — and your question helps the next person too.
Be the first to ask — other owners or our team will answer.