EN
Emerson logo
Official user manual

Emerson 7ATB

16 pages·563 KB·Power Supply·PDF·ENDEFRITNLJA
Emerson 7ATB
Table of Contents 6 sections 132f0 · 132fp · 132f1 · 132f2 · … ShowHide
Page 1 of the Emerson 7ATB user manual — TABLE OF CONTENTS
Page 1 · click to enlarge
Page 1

7000 Series 7ATB Automatic Transfer & Bypass–Isolation Switches G design 1000 through 4000 amp. sizes

Operator’s

Manual

Refer to the outline and wiring drawings provided with your 7000 Series ATB for all installation and connection details and accessories.

Refer to Group 5 Controller User’s Guide 381333–126 for ATS status display messages, time delays, pickup & dropout settings, and adjustments.

An experienced licensed electrician must install the 7ATB. Rating Label

Each 7000 Series 7ATB contains a rating label to define the loads and fault circuit withstand/closing ratings. Refer to the label on the Transfer Switch for specific values.

Emerson 7ATB — Operator’s diagram (page 1)
Fig. 1 · Operator’s

Do not exceed the values on the rating label. Exceeding the rating can cause personal injury or serious equipment damage.

Nameplate The Transfer Switch nameplate includes data for each specific 7000 Series ATB. Use the switch only within the limits shown on this nameplate. A typical Catalog Number is shown below with its elements explained:

TABLE OF CONTENTS

section-page INSTALLATION Mounting 1-1 Power Connections 1-2 Engine Starting & Auxiliary Circuits 1-2 Functional Test 1-3, 1-4

TESTING & SERVICE Transfer Test 2-1 Preventive Maintenance 2-1 Disconnecting the Controller 2-1 Manual Load Transfer 2-2 Trouble-Shooting 2-2

BYPASSING & ISOLATING Bypassing the ATS 3-1 Isolating the ATS 3-2 Return to Service 3-3, 3-4

4000 amp. size

INDEX back cover

381333–132 F 50 Hanover Road, Florham Park, New Jersey 07932–1591 USA For sales or service call 1 800 800–2726 (ASCO) www.ascopower.com

ASCO POWER TECHNOLOGIES CANADA PO Box 1238, 17 Airport Road, Brantford, Ontario, Canada N3T 5T3

Page 2 of the Emerson 7ATB user manual — 132f0
Page 2 · click to enlarge
Page 2
Page 2 of the Emerson 7ATB user manual — 132f0
Page 3 of the Emerson 7ATB user manual — G7ATB C 3 4000 N 5 C
Page 3 · click to enlarge
Page 3

Catalog Number Identification Typical 7000 Series ATB catalog no. for overlapping neutral, 3 pole, 4000 amp., 480 V, in Type 1 enclosure:

G7ATB C 3 4000 N 5 C

Voltage Controller Enclosure A 115 J 400 5 – standard C – type 1 B 120 K 415 5X – if F – type 3R C 208 L 440 accessories G – type 4 ordered D 220 M 460 L – type 12 E N 230 480 blank – open type F P 240 550 G Q 277 575 H R 380 600 Voltage A 115 B 120 C 208 D 220 E 230 F 240 G 277 H 380J 400 K 415 L 440 M 460 N 480 P 550 Q 575 R 600
3. three Ø 2 – single Ø
Emerson 7ATB — G7ATB C 3 4000 N 5 C diagram (page 3)
Fig. 2

G7ATB 4000 A with the lower doors open (transfer switch shown)

Show 15 more labels / short text on this page
Phase Poles Neutral · A – solid · C – overlapping · blank – none · 3000 4000 · Status Lights · & Engine Control · Transfer Control · & Lights · Bypass · Handle · Group 5 Controller · Isolation · Handle · Transfer Switch
Page 4 of the Emerson 7ATB user manual — 132fp
Page 4 · click to enlarge
Page 4
Page 4 of the Emerson 7ATB user manual — 132fp
Page 5 of the Emerson 7ATB user manual — Mounting
Page 5 · click to enlarge
Page 5

SECTION 1 INSTALLATION

The ASCO 7000 Series Automatic Transfer & Bypass–Isolation Switch (ATB) consists of an upper bypass–isolation switch, a lower transfer switch, a monitoring and transfer controller, and door–mounted controls. The ATB is factory wired and tested. Installation requires removal of the shipping skid then securing the enclosure to the supporting foundation.

Remove Shipping Brackets / Angles

from the Transfer Switch

Open the lower front door(s). The Transfer Switch carriage is secured to the frame for shipment. Remove the three or four shipping brackets or L–angles (1 upper left, 1 upper right, 1 lower right, or 2 lower on 4000 A).

Remove the Shipping Skid

To prevent serious damage, remove 3 shipping angles from the transfer switch carriage. Do not turn the Isolation Handle until they are removed!

Open the front lower door and remove the two front lag screws securing the enclosure to the wood skid. Next remove the rear lower panel and remove the two rear lag screws securing the enclosure to the wood skid.

Supporting Foundation

The supporting foundation for the enclosure must be level and straight. Allow at least 35 inches in front of the enclosure for draw out of the Transfer Switch. Refer to the enclosure outline drawing included with the ATB for all mounting details including door opening space.

If bottom cable entry is used, the foundation must be prepared so that the conduit stubs are located correctly. Refer to the appropriate enclosure outline drawing for specified cable entrance area and location. Provide cable bending space and clearance to live metal parts. When a concrete floor is poured, use interlocking conduit spacer caps or a wood or metal template to maintain proper conduit alignment.

remove 3 or 4 shipping brackets ( L–angles)

Mounting

Figure 1-1. On 1000–3000 A remove three shipping

Refer to the enclosure outline drawing furnished with this switch and mount the 7000 Series ATB according to the details and instructions shown on the drawing.

L–angles.

remove 2 upper shipping brackets

remove 2 lower shipping brackets

Figure 1-2. 4000 A remove four shipping L–angles.

Page 6 of the Emerson 7ATB user manual — Engine Starting Contacts
Page 6 · click to enlarge
Page 6

INSTALLATION (continued)

Bus Connections

If bus connection is used, use SAE grade 5 hardware to connect bus to appropriate terminal plates on bypass switching device. Wipe off bus surfaces before they are joined. If bus is dirty, gently clean surfaces with a non-flammable solvent. Avoid touching cleaned surfaces.

De–energize the conductors before making any line or auxiliary circuitry connections. Be sure that Normal and Emergency line connections are in proper phase rotation. Place engine gen- erator starting control in the OFF position. Make sure engine generator is not in operation.

Testing Power Conductors

Do not connect the power conductors to the ATB until they are tested. Installing power cables in conduit, cable troughs, and ceiling-suspended hangers often requires considerable force. The pulling of cables can damage insulation and stretch or break the conductor’s strands. For this reason, after the cables are pulled into position, and before they are connected they should be tested to verify that they are not defective or have been damaged during installation.

Do not breathe cleaning solvent vapors.

Use SAE grade 5 hardware and tighten the bolted joints to the torque specified in Table 2-1.

The reliability of the connection depends on how clean and how tight the joint is.

Table 2-1. Tightening torque values for bolted joints.

Protect the switch from construction grit and metal chips to prevent malfunction or shortened life of the 7ATB switch.

Bolt Diameter (Grade 5 hardware) in inchesRecommended Tightening Torque in foot pounds 5/1612 3/820 1/250 5/895

Connecting Power Conductors

A Wiring Diagram is furnished with the ATB. All wiring must be made in accordance with the local codes. After the power cables have been tested, connect them to the appropriate terminal lugs on the Bypass Switch as shown on the wiring diagram provided with this ATB. Make sure that the lugs provided are suitable for use with the cables being installed. Standard terminal lugs are solderless screw type and will accept the wire sizes listed on the drawings provided with the ATB. Be careful when stripping insulation from conductors; avoid nicking or ringing the conductor. Remove surface oxides from conductors by cleaning with a wire brush. Follow conductor manufacturer’s instructions when aluminum conductor is used. Apply joint compound to conductor, then carefully wipe away excess compound. Tighten the cable lugs to the torque specified on the rating label.

Harnesses

All internal connections are made at the factory. The bypass switch, transfer switch, and control panel are joined together by an interconnecting wire harness. The disconnect plugs are already engaged on enclosed switches. For open–type switches, the plugs must be engaged after installation is completed. Align harness plugs with sockets in the control and push them together until they are secure.

Engine Starting Contacts

and Auxiliary Circuits

The engine control contact signal connections and auxiliary circuits are located on terminal block TB as shown on the Wiring Diagram provided with the ATB. Connect the signal wires to the appropriate terminals.

Be sure that the Normal and Emergency power connections are in proper phase rotation.

Page 7 of the Emerson 7ATB user manual — 1 – Voltage Checks
Page 7 · click to enlarge
Page 7

INSTALLATION (continued)

Emerson 7ATB — INSTALLATION (continued) diagram (page 7)
Fig. 3 · INSTALLATION (continued)
Emerson 7ATB — INSTALLATION (continued) diagram (page 7)
Fig. 4 · INSTALLATION (continued)

Test HOLD FOR 15 SECONDS

GREEN

RED

RED GREEN

Figure 1-2. Standard controls and indicators.

1Close the normal source circuit breaker. The Transfer Switch Connected To Normal and the Normal Source Accepted lights should come on. 2Use an accurate voltmeter to check phase to phase and phase to neutral voltages present at the transfer switch normal source terminals. 3Close the emergency source circuit breaker. (Start generator, if necessary.) The Transfer Switch Connected To Normal & Emergency Source Accepted lights should come on. 4Use an accurate voltmeter to check phase to phase and phase to neutral voltages present at the transfer switch emergency source terminals.* 5Use a phase rotation meter to check phase rotation of emergency source; it must be the same as the normal source.A B C 6Shut down the engine–generator, if applicable. The Emergency Source Accepted light should go off. Then put the starting control selector switch (on the generator set) in the automatic position. Close enclosure door.
Emerson 7ATB — GREEN diagram (page 7)
Fig. 5

Functional Test

Read all instructions on the Wiring Diagrams and labels affixed to the ATB. Note the control features that are provided and review their operation before proceeding.

After installing the ATB check the following:

– Bypass Handle should be in the NORMAL position. – Isolation Handle should be in the CONN position. – TS transfer switch Normal contacts should be CLOSED

(Emergency contacts should be OPEN)

Emerson 7ATB — Functional Test diagram (page 7)
Fig. 6 · Functional Test

If handles are not in correct positions, follow instruc- tions for Bypassing and Isolating the automatic transfer switch in Section 3. Do not force the handles. Electrical interlocks prevent a wrong sequence of operation.

1 – Voltage Checks

First check nameplate on transfer switch; rated voltage must be the same as normal and emergency line voltages.

Use extreme caution when using a meter to measure voltages. Do not touch power terminals; shock, burns, or death could result !

Perform steps 1–6 at the right. Observe the status lights. See Figure 1–2.

Emerson 7ATB — 1 – Voltage Checks diagram (page 7)
Fig. 7 · 1 – Voltage Checks

Q Black square means light is on. S White square means light is off.

* If necessary, adjust voltage regulator on generator per the manufacturer’s recommendations. The ATB will respond only to rated voltage specified on the nameplate.

Now continue to 2 – Electrical Operation on next page.

Show 16 more labels / short text on this page
Transfer · Transfer Switch · Transfer Switch · Control · Connected · Connected · Transfer · To Normal · To Emergency · Retransfer · Delay Bypass · ( ) · observe these lights · Normal Source Accepted · Emergency · Source Accepted
Page 8 of the Emerson 7ATB user manual — Transfer Test
Page 8 · click to enlarge
Page 8

INSTALLATION (continued)

Test HOLD FOR 15 SECONDS

GREEN

RED

RED GREEN

Figure 1-3. Standard controls and indicators.

1The Transfer Switch Connected to Normal and Normal Source Accepted lights should be on. 2Turn and hold Transfer Control switch clockwise to Transfer Test until the engine starts and runs (within 15 sec.). The Emergency Source Accepted light should come on. 3Transfer switch will operate to the Emergency position after Feature 2B time delay. The Transfer Switch Connected To Emergency light should come on and Load Connected to Normal light goes off. 4Transfer switch will operate back to Normal position after Feature 3A time delay. For immediate retransfer turn Transfer Control counterclockwise to Retransfer Delay Bypass. The Transfer Switch Connected To Normal light should come on; Transfer Switch Connected to Emergency light should go off. 5The engine–generator will stop after the Feature 2E time delay (unloaded running engine cooldown). The Emergency Source Accepted light should go off.
Emerson 7ATB — GREEN diagram (page 8)
Fig. 8

2 – Electrical Operation

This procedure checks electrical operation of the ATS.

Be sure to close the enclosure door before proceeding to prevent personal injury in case of electrical system fault.

Emerson 7ATB — 2 – Electrical Operation diagram (page 8)
Fig. 9 · 2 – Electrical Operation

Transfer Test

The ATS should still be bypassed. Both normal and emergency sources must be available and the emergency source generator (if used) must be capable of being started; put engine starting control in automatic position. The Transfer Switch Connected to Normal light and the Normal Source Accepted light should be on.

Emerson 7ATB — Transfer Test diagram (page 8)
Fig. 10 · Transfer Test
1. Turn the Isolation Handle counterclockwise to the TEST position.
Emerson 7ATB — Transfer Test diagram (page 8)
Fig. 11 · Transfer Test
2. Perform steps 1–5 at right. Observe the status lights.

Q Black square means light is on. S White square means light is off.

3. Turn the Isolation Handle clockwise to the CONN (connected) position.
4. Push in the Bypass Handle and turn it counterclockwise to the OPEN position.

This completes the Functional Test of the ATB.

Show 17 more labels / short text on this page
Transfer · Transfer Switch · Transfer Switch · Control · Connected · Connected · Transfer · To Normal · To Emergency · Retransfer · Delay Bypass · ( ) · operate this switch · observe these lights · Normal Source Accepted · Emergency · Source Accepted
Page 9 of the Emerson 7ATB user manual — DISCONNECTING THE CONTROLLER
Page 9 · click to enlarge
Page 9

SECTION 2 TESTING & SERVICE

TRANSFER TEST

REPLACEMENT PARTS

Test the Automatic Transfer Switch portion of the 7000 Series ATB at least once a month. This procedure checks the electrical operation of the Transfer Switch and Controller. Put the engine–generator starting con- trol (at the engine–generator set) in automatic mode. In the following test the generator will start, the load will be transferred to the Emergency source, then back to the Normal source. An interruption to the load will occur, unless the the Transfer Switch contacts are by- passed before the test. See pages 3–1 and 3–2 for by- passing & isolating instructions if no interruption of load is required.

Replacement parts are available in kit form. When ordering parts provide the Serial No., Bill of Material No. (BOM), and Catalog No. from the transfer switch nameplate. For service call ASCO Services at 1–800–800–2726.

DISCONNECTING THE CONTROLLER

The harness disconnect plugs are furnished for repair purposes only and should not have to be unplugged. If the controller must be isolated, follow these steps:

Bypass–Isolation Switch is energized! Do not touch isolation contact fingers; shock, burns, or death could result!

Be sure to close the enclosure door before proceeding to prevent personal injury in case of electrical system fault.

Perform the five–step Electrical Operation – Transfer Test procedure on page 1–4.

1. Bypass and Isolate the Automatic Transfer Switch.
2. Open the upper enclosure door.

PREVENTIVE MAINTENANCE Reasonable care in preventive maintenance will insure high reliability and long life for the 7000 Series ATB. An annual preventive maintenance program is recom- mended.

3. Separate the two quick disconnect plugs by squeezing the latches. Do not pull on the harness wires.
1. The ATS should be still bypassed and isolated.
2. The two harness plugs and sockets are keyed. Carefully align the plugs with the sockets and press straight in until the latches click.

ASCO Services, Inc. (ASI) is ASCO Power Technologies’ national service organization. ASI can be contacted at 1–800–800–2726 for informa- tion on preventive maintenance agreements.

3. Close the enclosure doors.
4. Follow Return to Service instructions on page 3–3.

Checklist for Yearly Inspection

Hazardous voltage capable of causing shock, burns, or death is used in this switch. Deenergize both Normal – Emergency power sources before performing inspections!

S Clean the ATB enclosure. Brush and vacuum

away any excessive dust accumulation. Remove any moisture with a clean cloth. S Check the transfer switch contacts. Remove

transfer switch barriers and check the condition of the contacts. Replace contacts when pitted or worn excessively. Reinstall the barriers carefully. S Maintain transfer switch lubrication. If switch is

subjected to severe dust or abnormal operating conditions, renew factory lubrication on all move- ments and linkages. Relubricate solenoid operator if TS coil is replaced. Don’t use oil; order lubrica- tion kit 75-100. S Check all cable connections & retighten them.

Disconnecting the Plugs · Reconnecting the Plugs

Page 10 of the Emerson 7ATB user manual — MANUAL LOAD TRANSFER
Page 10 · click to enlarge
Page 10

TESTING & SERVICE (continued)

TROUBLE-SHOOTING

Hazardous voltage capable of causing shock, burns, or death is used in this switch. Do not touch the power or load terminals of the bypass switch or transfer switch!

Table 2-1. Trouble-Shooting Checks.

CHECK IN NUMERICAL SEQUENCE PROBLEM1 OPERATION2 GEN-SET3 VOLTAGE Engine–generator set does not start when the Transfer Control switch is turned and held in Transfer Test position or when normal source fails.Hold Transfer Test switch 15 seconds or the outage must be long enough to allow for Feature 1C time delay plus engine cranking and starting.Starting control must be in the automatic position. Batteries must be charged and connected. Check wiring to engine starting contacts.– Transfer switch does not transfer the load to the emergency source after the engine–generator set starts.Wait for Feature 2B time delay to time out.Generator output circuit breaker must be closed. Generator frequency must be at least 95% of nominal (57 Hz for a 60 Hz system.) *Voltmeter should read at least 90% of nominal phase to phase voltage between transfer switch terminals EA & EC (or EL1 & EL2 for 2 pole)* Transfer switch does not transfer the load to normal source when normal returns or when the Transfer Control switch is released.Wait for Feature 3A time delay to time out.–Voltmeter should read at least 90% of nominal phase to phase voltage between transfer switch terminals NB & NC, NC & NA, & NA & NB (or NL1 & NL2 for 2 pole). Engine–generator-set does not stop after load retransfer to the normal source.Wait for Feature 2E time delay to time out.Starting control must be in the automatic position.–

* These are factory settings. Refer to Controller’s User’s Guide. If the problem is isolated to circuits on the controller or the transfer switch, call your local ASCO Power Technolo- gies sales office or ASI: in the United States, call 1–800–800–2726. Furnish the Serial No., Catalog No., and Bill of Material (BOM) No. from the transfer switch nameplate.

MANUAL LOAD TRANSFER

MAINTENANCE HANDLE

This procedure manually transfers load to other source if the Transfer Switch or Controller are out of service.

Bypass and isolate the Transfer Switch before using the maintenance handle! See pages 3–1 and 3–2. Remove the maintenance handle after using it and store it on the frame.

Close enclosure doors to prevent personal injury in case of electrical system fault.

Turn counterclockwise to Emergency.

1. Be sure that the BypassHandle is CLOSED oneither Emergency or Normal (see page 3–1).
2. Be sure that the Isolation Handle is in the TEST or ISOLATE position (see page 3–2).

Turn clockwise to Normal.

3. Turn the Bypass Handle counterclockwise to OPEN the Bypass Switch. Then Bypass to the other source (see page 3–1).

slide hub onto shaft

insert handle into hole

Grasp handle firmly

Page 11 of the Emerson 7ATB user manual — To Bypass Normal Source*
Page 11 · click to enlarge
Page 11

SECTION 3 BYPASSING & ISOLATING

BYPASSING THE ATS*

This procedure explains how to Bypass the closed automatic transfer switch contacts. Bypassing is required before the ATS can be tested or isolated. The Bypass Handle must be in the OPEN position (green indicator) and the Isolation Handle must be in the CLOSED position (window). See Figures 3–1, 3–2, and 3–3.

You can only bypass to the same source that the Transfer Switch is connected. Solenoid interlock prevents incorrect operation.

1. Observe which Transfer Switch Connected To light is on ( Normal or Emergency) on the door. This is the position of the automatic transfer switch. 2. Bypass to the same source as connected to transfer switch as follows (select Normal or Emergency).
Emerson 7ATB — BYPASSING THE ATS* diagram (page 11)
Fig. 12

yellow O EMERGENCY CLOSED when ATS is bypassed to Emergency or

yellow O NORMAL CLOSED when ATS is bypassed to Normal Source.

green O OPEN when the ATS is not bypassed.

To Bypass Normal push in handle all the way & turn it clockwise.*

To Bypass Emergency pull out han- dle all the way & turn it clockwise.*

Figure 3–1. Bypass Handle and position indicators.

To Bypass Normal Source*

To Bypass Emergency Source*

(Load connected to Normal Source) The Transfer Switch Connected To Normal light is on and Transfer Switch Connected To Emergency light is off.

(Load connected to Emergency Source) The Transfer Switch Connected To Emergency light is on

and Transfer Switch Connected To Normal light is off.

Push in* the Bypass Handle all the way, then turn it clockwise until Bypass Switch Position shows CLOSED on NORMAL (yellow indicator). The red light Unit Not In Automatic will flash.

Pull out* the Bypass Handle all the way, then turn it clockwise until Bypass Switch Position shows CLOSED on EMERGENCY (yellow indicator). The red light Unit Not In Automatic will flash.

Push in Bypass Handle

Emerson 7ATB — To Bypass Normal Source* diagram (page 11)
Fig. 13 · To Bypass Normal Source*
Emerson 7ATB — To Bypass Normal Source* diagram (page 11)
Fig. 14 · To Bypass Normal Source*

& turn it clockwise.

& turn it clockwise.

Figure 3–2. Bypass to Normal.

Figure 3–3. Bypass to Emergency.

The automatic transfer switch can now be put in the TEST or OPEN position. See ISOLATING on page 3–2.

* NOTE: When Accessory 66A (reversed Normal & Emergency connections) is specified, the handle push–pull operation is reversed. Follow instructions on the door.

Page 12 of the Emerson 7ATB user manual — ISOLATING THE ATS
Page 12 · click to enlarge
Page 12

ISOLATING THE ATS

Emerson 7ATB — ISOLATING THE ATS diagram (page 12)
Fig. 15

Isolating is required before any service work can be performed on the automatic transfer switch (ATS). Refer to Figures 3–4, 3–5, 3–6, and 3–7.

1. Bypass the closed automatic transfer switchcontacts. See BYPASSING on page 3–1.

Align position indicator. Do not leave the handle in an intermediate position.

2. Turn the Isolation Handle counterclockwise (approx. 16 turns, approx. 12 turns for 4000 A) until window shows TEST . The ATS can be tested now without load interruption (see page 2–1).

Figure 3–6. Isolation Handle. NOTE: In the TEST position the transfer switching device solenoid operator circuit is energized through secondary disconnects.

Emerson 7ATB — ISOLATING THE ATS diagram (page 12)
Fig. 16

Turn crank counter- clockwise until window shows TEST.

Hazardous voltage capable of causing electrical shock, burns, or death; do not touch any control circuit terminals.

Figure 3–4. CONNECTED to TEST position. 3. Continue turning Isolation Handle counterclock- wise (approx. 7 turns, approx. 8 turns for 4000 A) until the window shows ISOLATE.

Emerson 7ATB — ISOLATING THE ATS diagram (page 12)
Fig. 17

Figure 3–7a. 1000–3000 A transfer switch

Turn crank counter- clockwise until window shows ISOLATE.

isolated and pulled out for inspection. See page 2–2 for maintenance handle use. For 1000–3000 A lifting yoke kit 607064 is available to facilitate lifting by using an overhead crane or similar equipment. For 4000 A use lifting yoke 835745–001.

Emerson 7ATB — ISOLATING THE ATS diagram (page 12)
Fig. 18

1000–3000 A switches weighs 350–450 lbs; use lifting yoke 607064. 4000 A switches weigh approx. 600 lb; use lifting yoke 835745--001 or other device capable of lifting this weight to avoid personal injury or equipment damage.

Figure 3–5. TEST to ISOLATE position. 4. Open the lower enclosure door(s). Pull out the side rail carriage. On 4000 A extend two support legs; see Figure 3–7b. Then roll out the transfer switch. It can be safely inspected in this position. The transfer switch can also be removed for easier maintenance operations.

To avoid personal injury and equipment damage on 4000 A switches, two support legs must be extended as shown in Figure 3–7b. Substantial initial force is required to pull out the transfer switch (there are detents on rails).

Page 13 of the Emerson 7ATB user manual — 132f3
Page 13 · click to enlarge
Page 13
Emerson 7ATB — 132f3 diagram (page 13)
Fig. 19 · 132f3

locking pin with clevis pin

locking pin with clevis pin

adjust length to touch floor

adjust length to touch floor Drawout procedure

1. Bypass and Isolate the ATS, then open both lower doors. 2. Pull out the rail support carriage all the way. 3. Remove left & right clevis and locking pins, drop two support legs, reinstall locking and clevis pins (to lock in place), and adjust both leg lengths to extend to the floor. 4. Stand directly in front of transfer switch. Grasp both handles, and pull straight out (detents on the rails require high initial force to overcome resistance).

Figure 3–7b. 4000 amp transfer switch isolated and pulled out for inspection.

To avoid personal injury and equipment damage on 4000 A switches, two support legs must be extended as shown in Figure 3–8. Substantial initial force is required to pull out the transfer switch (there are detents on rails).

The 4000 A transfer switch weighs 600 lb. Use lifting yoke 835745–001 or other device capable of lifting this weight to avoid personal injury or equipment damage.

Show 5 more labels / short text on this page
grasp two handles · rail support · carriage · left support leg · right support leg
Page 14 of the Emerson 7ATB user manual — To change the position of transfer switch
Page 14 · click to enlarge
Page 14

RETURN TO SERVICE

This procedure explains how to return the automatic transfer switch (ATS) to service after inspection and maintenance. Observe the Bypass Switch Position indicator and lights). Refer to Figures 3–7a, 3–7b, 3–8, 3–9, and 3–10.

Solenoid interlock prevents you from closing the isolation contacts until the ATS is in the same position as the Bypass Switch.

3. Observe which Bypass Switch Position indicator is black ( NORMAL or EMERGENCY ) at the Bypass Switch Handle. This indicates the source connected to the load. 4. Observe which Transfer Switch Connected To light is on ( Normal or Emergency ) on the door. This is the position of the Transfer Switch. If it is not in the same position as the Bypass Handle change the position of the Transfer Switch as follows:
1. Slide the transfer switch (ATS) into the enclosure (isolation contacts facing inward) until its crank pins engage the latch plates on both sides. On 4000 A substantial force is required to overcome detents on the rails. Next push in side rail carriage. On 4000 A first retract the two legs and lock them in place. See Figure 3–7b. Then close enclosure door.
Emerson 7ATB — RETURN TO SERVICE diagram (page 14)
Fig. 20

To change the position of transfer switch

Close the enclosure door to prevent personal injury in case of electrical system fault.

Emerson 7ATB — To change the position of transfer switch diagram (page 14)
Fig. 21 · To change the position of transfer switch

Operate to NORMAL OperatetoEMERGENCY Turn Transfer Control switch to Retransfer Delay Bypass.

Turn Transfer Control switch to Transfer Test (hold 15 seconds).*

Align position indicator. Do not leave the handle in an intermediate position.

* If Feature 2B time delay is used, there will be a delay before transfer to Emergency.

Emerson 7ATB — To change the position of transfer switch diagram (page 14)
Fig. 22 · To change the position of transfer switch

Do not close the isolation contacts unless the Transfer Switch (ATS) and Bypass Switch are in the same position!

5. When the transfer switch is in the same position as the Bypass Switch handle, continue turning the Isolation Handle clockwise (approx. 16 turns, approx. 12 turns for 4000 A) until the window shows CONN (connected).

Figure 3–8. Isolation Handle. 2. Turn the Isolation Handle clockwise (approx. 7 turns, approx. 8 turns for 4000 A) until the window shows TEST. The ATS can be tested now without load interruption (see page 2–1).

Emerson 7ATB — To change the position of transfer switch diagram (page 14)
Fig. 23 · To change the position of transfer switch
Emerson 7ATB — To change the position of transfer switch diagram (page 14)
Fig. 24 · To change the position of transfer switch

Turn crank clockwise until window shows TEST.

Turn crank clockwise until window shows CONN (connected). ATS

Figure 3–10. TEST to CONNECTED position.

Figure 3–9. ISOLATE to TEST position.

Now continue to the next page for instructions on how to return the Bypass Handle to the OPEN postition.

Page 15 of the Emerson 7ATB user manual — To Un–Bypass Normal Source*
Page 15 · click to enlarge
Page 15

RETURN TO SERVICE continued*

This procedure explains how to return the Bypass Switch Handle to the OPEN position. The Bypass Handle must be in the CLOSED position (yellow indicator on NORMAL or EMERGENCY) and the Isolation Handle must be in the TEST position (window). If the handles are not in these positions, refer to Return to Service on page 3–3. See Figures 3–11, 3–12, and 3–13.

You can only bypass to the same source that the ATS is connected. Solenoid interlock prevents incorrect operation.

1 Observe which Bypass Switch Position indicator is yellow (NORMAL or EMERGENCY) at the Bypass Switch Handle. This indicates the source connected to the load. 2 Un–Bypass to same source as the Bypass Switch Position as follows (select Normal or Emergency).

Emerson 7ATB — 132f3 diagram (page 15)
Fig. 25 · 132f3

yellow O EMERGENCY CLOSED when ATS is bypassed to Emergency or

yellow O NORMAL when ATS is bypassed to Normal Source.

green O OPEN when the ATS is not bypassed.

To un–Bypass Normal push in handle all the way & turn it counterclockwise.*

Figure 3–11. Bypass Handle and position indicators.

To Un–Bypass Normal Source*

To Un–Bypass Emergency Source*

(Load connected to Normal Source) The Transfer Switch Connected To Normal light is on and Transfer Switch Connected To Emergency light is off.

(Load connected to Emergency Source) The Transfer Switch Connected To Emergency light is on

and Transfer Switch Connected To Normal light is off.

Push in* the Bypass Handle then turn it counterclock- wise until Bypass Switch Position shows OPEN (green indicator). The Unit Not in Automatic light should be off.

Pull out* the Bypass Handle then turn it counterclock- wise until Bypass Switch Position shows OPEN (green indicator). The Unit Not in Automatic light should be off.

Emerson 7ATB — To Un–Bypass Normal Source* diagram (page 15)
Fig. 26 · To Un–Bypass Normal Source*
Emerson 7ATB — To Un–Bypass Normal Source* diagram (page 15)
Fig. 27 · To Un–Bypass Normal Source*

Push in Bypass Handle

& turn it counter- clockwise.

& turn it counter- clockwise.

Figure 3–12. Un–Bypass Normal.

Figure 3–13. Un–Bypass Emergency.

The Automatic Transfer & Bypass–Isolation Switch should be left in this position.

* NOTE: When Accessory 66A (reversed Normal & Emergency connections) is specified, the handle push–pull operation is reversed. Follow instructions on the door.

Page 16 of the Emerson 7ATB user manual — HELP
Page 16 · click to enlarge
Page 16

INDEX

A

R

removal of shipping angles, 1–1

B

removal of shipping skid, 1–1

isolating the ATS, 3–2

bypassing the ATS, 3–1

return to service, 3–4, 3–5

S

load connected to emergency, 1–4

catalog number, inside cover

ASCO Services, Inc. (ASI), 2–1

load connected to normal, 1–4

see Controller User’s Guide

M

disconnecting, 2–1 see Controller User’s Guide

support legs on 4000 A, 3–3

D

T

drawout, transfer switch, 3–2, 3–3

manual load transfer, 2–2

test, functional, 1–3, 1–4

testing power cables, 1–2

see Controller User’s Guide

Emergency Source Accepted light,

Transfer Control selector switch

Normal Source Accepted light, 1–3

Retransfer Delay Bypass, 1–4 Transfer Test, 1–4

Engine Control selector switch

O

Transfer Switch Connected To

engine starting contacts, 1–2

F

Transfer Switch Connected To

electrical, 1–4 manual, 2–2

transfer test, 1–3, 2–1

transfer to emergency, 1–4, 2–1

functional test, 1–3, 1–4

transfer to normal, 1–4, 2–1

P

H

phase rotation check, 1–3

HELP

customercare@asco.com 800–800–ASCO

voltage, pickup and dropout settings

see Controller User’s Guide

Printed in U.S.A. E ASCO Power Technologies, L.P. 2009

Show 34 more labels / short text on this page
auxiliary circuits, 1–2 · inspection, 3–1 · rating label, cover · installation, 1–1 · bus connections, 1–2 · replacement parts, 2–1 · lights, 1–3, 1–4 · service · cleaning, 2–1 · settings · connections · lubrication, 2–1 · power, 1–2 · shipping angles, 1–1 · controller · maintenance, preventive, 2–1 · shipping skid, 1–1 · maintenance handle, 2–2 · electrical operation, 1–4 · time delays, 2–1 · nameplate, cover · Auto position, 2–1 · Emergency light, 1–4 · operation · Normal light, 1–4 · foundation, 1–1 · frequency, generator, 2–2 · troubleshooting, 2–2 · parts, 2–1 · harness, 1–2 · disconnect plugs, 2–1 · voltage checks, 1–3 · preventive maintenance, 2–1 · problem, 2–2
Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the Emerson 7ATB

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Emerson 7ATB

Be the first to ask — other owners or our team will answer.

Original document

Emerson 7ATB manual PDF

16 pages·563 KB·Power Supply·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…