8.5 Shut Down the Liebert GXT3 24
8.6 Disconnecting Input Power from the Liebert GXT3 24
8.7 Maintenance Bypass 24
8.8 IT Power System Configuration 25
9.0 COMMUNICATION 26 9.1 Communication Interface Port 26
9.2 Terminal Block Communication 26
9.2.1 Any Mode Shutdown 26 9.2.2 Battery Mode Shutdown 27 9.2.3 On Battery 27 9.2.4 Low Battery 27 9.3 Liebert IntelliSlot® Communication Cards 27
9.3.1 Liebert MultiLink® 28
9.4 Remote Emergency Power Off 28
10.0 MAINTENANCE 29 10.1 Replacing the Internal Battery Pack 29
10.1.1 Battery Replacement Procedures 29 10.2 Battery Charging 30
10.3 Precautions 30
10.4 Checking UPS Status 31
10.5 Checking UPS Functions 31
11.0 TROUBLESHOOTING 32 11.1 UPS Symptoms 32
11.1.1 Indicators 32 11.1.2 Audible Alarm 33 11.2 Troubleshooting 33
12.0 SPECIFICATIONS 35 12.1 Auto-Learning Battery Run Times 39




SAVE THESE INSTRUCTIONS
This manual contains important safety instructions. Read all safety and operating instructions before operating the uninterruptible power system (UPS). Adhere to all warnings on the unit and in this manual. Follow all operating and user instructions. This equipment can be operated by individuals without previous training.
This product is designed for commercial/industrial use only. It is not intended for use with life support and other designated “critical” devices. Maximum load must not exceed that shown on the UPS rating label. The UPS is designed for data processing equipment. If uncertain, consult your dealer or local Emerson Network Power® representative.
This UPS is designed for use on a properly earthed (grounded), 220-240 VAC, 50Hz or 60Hz supply, for installation by qualified personnel. A qualified electrician must review and approve customer supplied wiring, circuit breakers, intended loads and verify correct input, output and earth connections to ensure compliance with technical standards and local electrical codes of practice. Installation instructions and warning notices only for use by qualified personnel are located after the UPS operator instructions in this manual.
If this UPS is supplied from an “IT” electrical power system, the jumper on the rear panel must be disconnected. See 8.8 - IT Power System Configuration for details. If connecting to an “IT” system, the installer must provide a 2-pole upstream circuit breaker. Refer to all local and national codes when installing the upstream breaker.

ELECTROMAGNETIC COMPATIBILITY—The Liebert GXT3 complies with the limits of Category C2, pursuant to IEC/EN/AS 62040-2. Operation is subject to the following conditions:
The Liebert GXT3 series complies with the requirements of EMC Directive 2004/108/EC and the published technical standards. Continued compliance requires installation in accordance with these instructions and use of accessories approved by Emerson®.
This is a Category C2 UPS product. In a residential environment, this product may cause radio interference, in which case the user may be required to take additional measures.
Operate the UPS in an indoor environment only in an ambient temperature range of 0-40°C (32-104°F). Install it in a clean environment, free from moisture, flammable liquids, gases and corrosive substances.
This UPS contains no user-serviceable parts except the internal battery pack. The UPS On/Off push buttons do not electrically isolate internal parts. Under no circumstances attempt to gain access internally, due to the risk of electric shock or burn.
Do not continue to use the UPS if the front panel indications are not in accordance with these operating instructions or the UPS performance alters in use. Refer all faults to your dealer.
Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from the batteries. Proper disposal of batteries is required. Refer to your local laws and regulations for disposal requirements.
Never block or insert any object into the ventilation holes or other openings.
DO NOT CONNECT equipment that could overload the UPS or demand DC current from the UPS, for example: electric drills, vacuum cleaners, laser printers, hair dryers or any appliance using half- wave rectification.
Storing magnetic media on top of the UPS may result in data loss or corruption.
Turn Off and isolate the UPS before cleaning it. Use only a soft cloth, never liquid or aerosol cleaners.
UPS SERVICING—This UPS makes use of components dangerous for the environment (electronic cards, electronic components). The components removed must be taken to specialized collection and disposal centers.
The “crossed-out wheelie bin” symbol at right is placed on this product to encourage you to recycle wherever possible. Please be environmentally responsible and recycle this product through your recycling facility at its end of life. Do not dispose of this product as unsorted municipal waste. Follow local municipal waste ordinances for proper disposal provisions to reduce the environmental impact of waste electrical and electronic equipment (WEEE).
For information regarding the scrapping of this equipment, please browse http://www.eu.emersonnetworkpower.com (“Products session” or “Contact us” session) or call our worldwide technical support.

Risk of electrical shock
Indicates caution followed by important instructions
Requests the user to consult the manual
Indicates the unit contains a valve-regulated lead acid battery
ON/Alarm Silence/Manual Battery Test

Congratulations on your choice of the Liebert GXT3 uninterruptible power system (UPS). The Liebert GXT3 comes in nominal power ratings of 5000VA, 6000VA and 10,000VA. It is designed to provide conditioned power to microcomputers and other sensitive electronic equipment.
When it is generated, alternating current is clean and stable. However, during transmission and distribution it may be subject to voltage sags, spikes and complete power failure that may interrupt computer operations, cause data loss and even damage equipment. The Liebert GXT3 protects equipment from these disturbances.
The Liebert GXT3 is a compact, on-line UPS that continuously conditions and regulates its output voltage, whether mains power is present or not. It supplies connected equipment with clean sinewave power. Sensitive electronic equipment operates best from sinewave power.
For ease of use, the Liebert GXT3 features a light-emitting diode (LED) display to indicate both load percentage and battery capacity. It also provides self-diagnostic tests, a combination ON/Alarm Silence/Manual Battery Test button, a Standby/Manual Bypass button and a configuration program.
The Liebert GXT3 has a Liebert IntelliSlot® port for communication between the UPS and a network server or other computer systems. This port provides detailed operating information including voltages, currents and alarm status to the host system when used in conjunction with Liebert MultiLink®. Liebert MultiLink can also remotely control UPS operation.
Introduction



N
N


G
2.1 Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters
These UPS components provide surge protection and filter both electromagnetic interference (EMI) and radio frequency interference (RFI). They minimize any surges or interference present in the mains line and keep the sensitive equipment protected.
In normal operation, the rectifier/power factor correction (PFC) circuit converts mains AC power to regulated DC power for use by the inverter while ensuring that the waveshape of the input current used by the UPS is near ideal. Extracting this sinewave input current achieves two objectives:
This results in cleaner power being available to other devices in the building not being protected by the Liebert GXT3.
In normal operation, the inverter utilizes the DC output of the power factor correction circuit and inverts it into precise, regulated sinewave AC power. Upon a mains power failure, the inverter receives its required energy from the battery through the DC-to-DC converter. In both modes of operation, the UPS inverter is on-line and continuously generating clean, precise, regulated AC output power.
The battery charger utilizes energy from the mains power and precisely regulates it to continuously float charge the batteries. The batteries are being charged whenever the Liebert GXT3 is connected to mains power.

The DC-to-DC converter utilizes energy from the battery system and raises the DC voltage to the optimum operating voltage for the inverter. This allows the inverter to operate continuously at its optimum efficiency and voltage, thus increasing reliability.
The Liebert GXT3 utilizes valve-regulated, nonspillable, lead acid batteries. To maintain battery design life, operate the UPS in an ambient temperature of 15°C to 25°C (59°F to 77°F). Optional external battery cabinets are available to extend battery run times. For run times, see Table 11.
The Liebert GXT3 provides an alternate path for mains power to the connected load in the unlikely event of a UPS malfunction. Should the UPS have an overload, overtemperature or any other UPS failure condition, the UPS automatically transfers the connected load to bypass. Bypass operation is indicated by an audible alarm and illuminated amber Bypass LED (other LEDs may be illuminated to indicate the diagnosed problem). To manually transfer the connected load from the inverter to bypass, press the Standby/Manual Bypass button once and hold it for about 2 seconds.
System Description

The Liebert GXT3 is composed of three major assemblies to provide easier handling, installation and versatility.
The cabinet is shipped with internal batteries installed and a basic, hardwire distribution box attached and ready to install.
Figure 1 Liebert GXT3 5000VA and 6000VA, front view


Status Indicators and Controls
Lower Bezel and Battery Access Door
10,000VA model’s front layout is identical; the battery compartment is larger.
Major Components · Upper Bezel

Figure 2 Liebert GXT3, rear view
Liebert GXT3, 5,000 & 6000VA

C19 Output Power Receptacles Liebert IntelliSlot® Port USB Port
IT Power System Access Cover
Removable Power Distribution Box factory-attached in bottom-left corner
Knockouts for Hardwired Power Input

IT Power System Access Cover Output Circuit Breakers
Removable Power Distribution Box factory-attached in bottom-left corner
Knockouts for Hardwired Power Input

The UPS has two internal battery packs behind a battery access door on the front of the unit. Each internal battery pack is fitted with a connector to link to the UPS.
Figure 3 Internal battery pack with connector

GXT3 10,000 Battery Pack shown; 5000 and 6000VA battery packs have same features
Front of Battery Pack
The UPS arrives with a power distribution pack installed. This box always contains the UPS input circuit breaker.


Outer Surface View Power Distribution
Box for 5000VA and 6000VA models
Figure 5 Power distribution box for GXT3 10,000VA model


Inner Surface View Power Distribution Box for 10000VA model
Front View Power Distribution Box for 10000VA model
PD2-CE10HDWRMBS

The Liebert GXT3 is shipped with the following items:
What’s Included

Do NOT attempt to start the UPS, turn on any circuit breaker or energize the input power until instructed to do so in 8.2 - Initial Startup and Electrical Checks.
Visually inspect the UPS for freight damage. Report any damage to the carrier and your local dealer or Emerson® representative.
! CAUTION The UPS is heavy (see 12.0 - Specifications). Take proper precautions when lifting or moving it.
Install the Liebert GXT3 indoors in a controlled environment, where it cannot be accidentally turned off. Place it where air flows unrestricted around the unit. The installation location must be free of water, flammable liquids, gases, corrosives and conductive contaminants. Maintain a minimum clearance of 100mm (4 inches) in the front and rear of the UPS. Maintain an ambient temperature range of 0 to 40°C (32 -104°F).
The Liebert GXT3 may be installed in either a tower configuration or in a rack, depending on available space and use considerations. Determine the type of installation and follow the appropriate instructions in either 5.1.1 - Tower UPS Installation or 5.1.2 - Rack-Mount UPS Installation.
To install the Liebert GXT3 as a tower:
Figure 6 Support bases


2. If optional Liebert external battery cabinets will be connected to the Liebert GXT3, take out the spacers shipped with the battery cabinet. 3. Connect the spacers and the support bases as shown in Figure 6. Each Liebert GXT3 needs two assembled support bases, one in the front and one in the rear. 4. Adjust the direction of the operation and display panel and logo on the Liebert GXT3. a. Remove the front plastic bezel cover as shown in Figure 7.
Figure 7 Remove the front plastic bezel cover


b. Pull the operation and display panel gently, rotate it 90 degrees clockwise and snap it back into position, as shown in Figure 8.
Figure 8 Rotate the operation and display panel

Operation and Display Panel Rotated Clockwise 90 Degrees
c. Pull the logo on the front plastic bezel cover gently, rotate it 90 degrees clockwise and snap it back into position. The rotated front plastic bezel cover is shown in Figure 8. d. Replace the front plastic bezel cover on the Liebert GXT3. At this point, the UPS operation and display panel and logo have been rotated 90 degrees clockwise, which provides upright viewing for users. 5. Place the Liebert GXT3 and any battery cabinets on the support bases. Each Liebert GXT3 needs two support assemblies, as shown in the lower half of Figure 1.
When using the Liebert GXT3 in a rack-mount configuration, the UPS must be supported by a slide kit, fixed rails or a shelf.
When using the optional Adjustable Rack Mount Kit, you will use the following instructions. The figures accompanying 5.1.3 - Installing the Adjustable Rack-Mount Kit—Sold Separately shows the positioning of the rack-mounting brackets. Emerson® recommends taking the internal batteries out of the UPS during rack installation. This will make the UPS cabinet lighter and easier to handle.
! CAUTION The GXT3 is heavy; see 12.0 - Specifications. The UPS must be installed as near the bottom of a rack as possible. If placed too high, it can make the rack top-heavy and prone to tipping over.
This kit contains parts needed to mount several different models of UPS and external battery cabinets into EIA310-D standard four-post racks that are 18-32" deep (457-813mm). The weight limit per pair of adjustable rack-mounting brackets is 91 kg (200lb).
Parts included are:
Rear bracket members 2
Front bracket members 2
Inner bracket members 2
M4 machine screws 16
M4 locking hex nuts 8
M5 machine screws 8
Tools needed for installation are:
Installation and Configuration · Item Quantity

The adjustable rack-mounting brackets (Part#: RMKIT18-32) feature retaining latches to prevent users from inadvertently sliding the UPS or battery cabinet out of the rack.
To install the rack mount brackets:

! CAUTION Reduce the risk of tipping the rack enclosure by placing the UPS or battery cabinet in the lowest possible rack position.
Front rack mounting rails

3. Install the rear member of each bracket assembly into the rack enclosure with two (2) M5 screws provided in this kit (see figure at right). The return flanges on the bracket assembly fit to the inside of rack mounting rails. Insert screws loosely (finger-tight) into the top and bottom holes of the return flange on the rear member. Extend the bracket assembly by sliding the front member forward until it touches the front rack mounting rail. Insert two (2) M5 screws loosely (finger-tight) into the top and bottom holes of the return flange on each front member. Make sure that the bracket assemblies are at the same mounting height on all four (4) rack mounting rails. 4. Get eight (8) M4 screws and eight (8) M4 nuts from the hardware pack in this kit. Each nut has a locking, nylon insert that begins gripping the screw when it is halfway tight. Make sure to tighten the nut and screw completely to ensure locking action. Fasten the rear member and the front member together using (4) screws and (4) nuts per bracket assembly as shown in at right. For maximum support, insert fasteners for each bracket assembly as far apart as possible, depending on rack depth, while still joining both members (see figures at right). Check alignment of bracket assemblies and TIGHTEN ALL SCREWS FROM Steps 2 3. 5. Prepare the UPS or battery cabinet (the “equipment”) for rack mounting by following instructions in the equipment’s user manual. The equipment may require additional parts to be added or parts to be removed for rack mounting. After it is prepared, lay the equipment in rack-mounting position. Fasten the inner members from Step 1 to the equipment on both sides as shown at right with eight (8) M4 screws provided in the kit. Make sure retaining latch is near the rear of the equipment as shown (see figure at right).

457mm (18") rack depth

813mm (32") rack depth

UPS or battery cabinet


UPS or battery cabinet
! CAUTION Lifting equipment into the rack may be a two-person job, depending on the weight of the equipment. Emerson® recommends taking the internal batteries out of the UPS during rack installation. This will make the UPS cabinet lighter and easier to handle. For the weight of the UPS, see Table 7; for the battery cabinet’s weight, see Table 10. Factory-supplied rack handles are not intended to be used to lift the UPS. These are intended to be used to slide the UPS into and out of the rack.

Insert the UPS into the front members, lift the front and push it into the rack.
7. Insert the equipment, with inner members attached in Step 5, into the bracket assemblies by inserting the top and bottom edges of the inner members into the top and bottom curved tracks of the front members and sliding the equipment into the rack (see figure at right). Ends of inner members are tapered to allow the rear of the equipment to be angled upward before insertion, if space allows. Then the rear, bottom edges of the inner members can be placed into the front edge of the bottom tracks and the front of the equipment can be tipped up so they are level to insert the top edges of the inner members before sliding the equipment into the rack (see figure below right). The equipment should move smoothly into the bracket assemblies. If it does not, recheck the alignment of the front and rear members from Steps 2 3. 8. Secure the front of the equipment to the rack mounting rails to prevent the equipment from sliding out of position. If securing holes are provided on the front of the equipment that align with the center holes on the return flange of the front members, you can use the four (4) extra M5 screws provided in the kit to secure the equipment. Otherwise, the equipment should be secured to the front of the rack with four (4) customer-supplied fasteners.
Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery run time. External battery cabinets are designed to be placed on one side of the UPS or stacked beneath the UPS. External battery cabinets can be used in either a rack-mount or tower configuration.
! CAUTION The external battery cabinet(s) are heavy (see 12.0 - Specifications). Take proper precautions when lifting them.
Installation and Configuration · Apply grease · Apply grease (inside)

Figure 9 External battery cabinets connected to 10,000VA Liebert GXT3

Cables connecting battery cabinets to 10,000VA Liebert GXT3
1. Visually inspect the external battery cabinet for freight damage. Report damage to the carrier and your local dealer or Emerson® representative. 2. For slide rail installations, first remove the top/side fin. Top/side fin slides forward and then lift up to remove. Optional rack-mount handles are shipped with the external battery cabinet and may be installed at this time if desired. 3. Securing hardware and slide rails are sold separately. Please contact your local dealer or Emerson representative for these additional options and any assistance needed. Fasten the slides into position with the screws per the instructions included with the slide rails. 4. Use the enclosed support bases for the tower option to prevent tip-over. One additional set of support base extensions ships with each external battery cabinet. 5. Put the UPS in Bypass Mode by pressing the bypass button on the front of the unit and holding it about 2 seconds. 6. Verify the External Battery Cabinet breaker is in the Off position. 7. Connect the supplied external battery cabinet cable to the rear of the external battery cabinet, then to the rear of the UPS. 8. Turn the External Battery Cabinet breaker to the On position. 9. Press the On button on the front of the UPS for 4 seconds to return the unit to Inverter Mode. 10. Verify the circuit breaker on the External Battery Cabinet is in the On position. 11. Use the included configuration program to program the UPS for the number of external battery cabinets connected. Instructions for the configuration program are in 6.0 - Configuration Program. 12. The UPS is now equipped with additional backup battery run time. For approximate battery run times, refer to Table 11.
Installation and Configuration · 10,000VA Liebert GXT3 · Battery Cabinets

Figure 10 Power Distribution box removal—captive screws and maintenance bypass breaker


The UPS should arrive with the power distribution box attached. If the box needs to be removed for maintenance or replacement, follow these instructions to remove and install the power distribution pack.
To remove:
The load is unprotected from disturbances in the power supply while the UPS is on bypass.
To install:

Electrical connections are made through a removable power distribution box that attaches to the rear of the UPS.
The installer must provide an upstream branch circuit breaker. The input circuit breaker on the distribution box and the output circuit breaker on the rear of the power distribution box disconnect all power between the main cabinet and the distribution box.
Models equipped with a manual bypass breaker pass bypass power directly to the bypass breaker from the input terminal block. The input circuit breaker on the distribution box does not disconnect power from the manual bypass breaker.
Table 1 Branch circuit breaker ratings
Unit Rating Maximum Breaker Rating
5000VA D Type 32A 6000VA D Type 32A 10,000VA D Type 63A
Figure 11 Distribution box electrical connections diagram
PD2-CE6HDWRMBS
Terminal Block Connections—PD2-CE6HDWRMBS and PD2-CE10HDWRMBS Conduit entry holes are provided on the rear and side of the box. Input and output wiring should not share the same conduit. Emerson® recommends using strain relief when installing the wire.
Table 2 Electrical specifications
Recommended (Maximum) External Overcurrent Protection
Recommended Wire (Including ground wire)
Accepted by Terminal Block
GXT3-5000RT230 GXT3-6000RT230 32A 4mm2 (10AWG) 6mm2 (8AWG) 2.26 Nm (20 in-lb) GXT3-10000RT230 63A 10mm2 (6AWG) 16mm2 (4AWG)

Figure 12 Terminal block connections—PD2-CE6HDWRMBS and PD2-CE10HDWRMBS
INPUT OUTPUT N N L L
N N L L
INPUT OUTPUT
NOTE The installer must provide circuit breaker protection according to local codes. The mains disconnect should be within sight of the UPS or have an appropriate lock-out. Maintain service space around the UPS or use flexible conduit. The installer must provide output distribution panels, circuit breaker protection or emergency disconnects according to local codes. Output circuits must not share a common conduit with any other wiring.
Installation and Configuration

The final step of installation may require custom configuration of your UPS using the enclosed configuration program. Some configuration settings may be changed only while the UPS is off. These should be set before the UPS is put into full-time service powering the critical load.
For most users operating with 230VAC and with no external batteries, the factory default settings will be adequate.
In addition to the Liebert GXT3 UPS, you will need the configuration program CD and USB cable included in the UPS accessory box. A Windows 95® or later computer, desktop or laptop, is also required to set up and run the configuration program.
Configuration Program


This button controls output power to connected load(s) and has three functions:
Manual Battery Test - To initiate a manual battery test, press the ON button for at least one second while operating from mains power with no alarm conditions present.
This button controls output power to connected load(s) and has dual functions: Standby and Manual Bypass.
Pressing the Standby/Manual Bypass button once will transfer the load to bypass power and the load will be unprotected from disturbances in utility supply. Pressing the Standby/Manual Bypass button twice within 4 seconds while on Bypass will cut
Controls and Indicators

off power to the output sockets and connected loads. Perform all necessary shutdown procedures on connected loads before pressing this button twice.
The load level indicator is composed of five sets of LED bars that illuminate to indicate the relative load on the UPS output in 25% increments (±5%). The load level indicator will illuminate as shown in Figure 13.
The load level indicators display the approximate electrical load placed upon the UPS at all times.
Figure 13 Load level indicators.
ON ON ON ON ON
7.4 Battery Level Indicators (5 Green)
The battery level indicator is composed of five sets of LED bars that illuminate and flash to indicate the battery capacity level. The Liebert GXT3 battery capacity level is shown in 20% increments (±5%). The battery level indicators will illuminate as shown in Figure 14
The battery level indicators display approximate battery capacity at all times.
The Liebert GXT3 is equipped with automatic and remote battery test features. The default setting is for the automatic test to occur every 14 days (this option is user-configurable) if mains has not been interrupted. Should the battery fail this test, the red Fault indicator LED along with the A and C diagnostic LEDs will illuminate and an alarm will sound (refer to 11.0 - Troubleshooting). The remote test feature functions with Liebert MultiLink® and can remotely initiate the battery test.
Controls and Indicators · Overload

Figure 14 Battery level indicators.

UPS status is indicated by five symbols: fault indicator, AC input indicator, battery indicator, inverter indicator and bypass indicator. Table 3 shows the symbols and their meanings.
Table 3 UPS status indicators

Fault Indicator Red On if the UPS has detected a fault; Off if there is no fault
AC input Indicator Green On when the mains input power is normal; Off during mains failure
Battery Indicator Amber On when the battery is supplying power; Off when the battery is not supplying power
Inverter Indicator Green On when the inverter is supplying power; Off when the inverter is not supplying power
On when the bypass is supplying power; Off when the bypass is not supplying power; flashing when mains power is outside specifications
Controls and Indicators

This section describes checks to be made before starting the UPS, how to start the UPS, manual battery test, manual bypass, shutting down the UPS and disconnecting the mains power from the UPS.
Before starting the UPS, perform these checks:
___ 1. Check that the input plugs and loads are connected properly and reliably.
___ 2. Check that the battery cable is connected properly.
___ 3. Check that the communication cables are connected properly.
8.2 Initial Startup and Electrical Checks 1. Verify that the Input Output circuit breakers are off. 2. During initial system checks, disconnect all loads (open load disconnects). 3. Inspect all wiring, cables and connection. 4. If external battery cabinets are used, verify that the battery interconnect cables are fully inserted in the sockets. 5. Place the manual bypass breaker in BYPASS position. 6. Turn on the branch circuit disconnect to apply voltage to the input terminal block. 7. Using a voltmeter, verify the expected L1-N voltage. Verify that the same voltages appear at the Output terminals. The Bypass lamp by the switch will light. 8. After verifying proper input voltage to the UPS terminal block, turn off the branch circuit power, close all access panels to the distribution box and reapply input power. 9. Close the Input circuit breaker located on the distribution box. The green AC INPUT lamp should illuminate on the front panel. 10. Press the ON button for four seconds. After several seconds, the UPS ON lamp will turn on continuously. If the batteries are determined to be charged above 80%, an automatic battery test will run for about 15 seconds. 11. Close the Output circuit breaker on the rear of the power distribution box. The light by the input breaker will illuminate. 12. Return the manual breaker to the Inverter position. The output terminal block will be powered at this time. 13. Connect all loads for normal operation.
Operation

To initiate a manual battery test, press the On/Alarm Silence/Manual Battery Test button for at least half a second while operating from mains power with no alarm conditions present.
Press the Standby/Manual Bypass button and hold it for about 2 seconds while the UPS is in Mains (AC) Mode. The UPS will transfer the connected loads to the internal bypass. If the internal bypass is not available because of mains power problems, pressing this button once will be ignored. Bypass operation is indicated by an audible alarm and illuminated amber Bypass indicator. (If other indicators are illuminated, refer to 11.0 - Troubleshooting.)
8.5 Shut Down the Liebert GXT3 1. Transfer the UPS to manual bypass by pressing the Standby/Manual Bypass button and holding it for about 2 seconds. If manual bypass is not available, disregard the first step. 2. Press the Standby/Manual Bypass button twice within four seconds, each time holding it for about two seconds.
Power to the connected loads is now Off.
8.6 Disconnecting Input Power from the Liebert GXT3 1. After the UPS has been shut down as detailed in 8.5 - Shut Down the Liebert GXT3, turn off the Output Circuit Breaker. 2. Wait 30 seconds and verify that all indicators have turned Off and the fan has stopped; this indicates that the power-off is complete. 3. Turn the external battery cabinet breaker switch to the Off position if the UPS has an external battery cabinet.
After powering off the UPS, the UPS ceases output and the load is powered Off.
Maintenance Bypass Mode is used when maintenance or replacement is required. To place the unit in Maintenance Bypass:
1. Place the UPS on internal bypass. This may be done by either of the following methods: a. Press the Off button on the front panel one time. b. Slide the bracket away from the manual bypass breaker on the rear of the UPS. This requires loosening the captive screw and sliding the bracket up and away from the Manual Bypass Breaker. 2. Move the Manual Bypass Breaker on the rear of the UPS to the bypass position. This requires loosening the captive screw and sliding the bracket up and away from the manual bypass breaker.
Operation

8.8 IT Power System Configuration 1. Remove screws on the IT Power System Access Cover as shown in Figure 15. 2. Disconnect the connectors as shown in figure. 3. Install IT Power System Access Cover and screws.
Figure 15 Remove cover from IT Power System Connectors compartment


Remove Screws IT Power System Connectors


Operation

The Liebert GXT3 UPS has a terminal block on the rear of the UPS unit. Several signals are provided on this port and are assigned as follows.
The terminal block includes eight pins, as shown in Figure 16.
Figure 16 Terminal block communication terminals
The purpose of Any Mode Shutdown is to shut down the UPS output by turning Off the rectifier, inverter and static switch so that there is no power to the loads.
Any Mode Shutdown can be operated locally or remotely:
Activation of the Any Mode Shutdown will be logged as an event in the event history log.
! WARNING When the Auto-enable output option is selected and the UPS output is disabled using the pins in Set 3, the Liebert GXT3’s output can turn On automatically and without warning if the connection to the pins in Set 3 is changed.

Battery Mode Shutdown permits shutting down the UPS by turning off the rectifier, inverter and static switch so that there is no power to the load when the UPS is On Battery. The auxiliary power for the UPS will still be active.
Battery Mode Shutdown can be performed locally or remotely:
Activation of the Battery Mode Shutdown will be logged as an event in the event history log.
The current limited source for this optocoupler (+12VDC, 50mA) will be available from UPS.
The connection to the Liebert GXT3 for remote connection will be via terminal block connector.
Battery Mode Shutdown wiring must conform to all national, regional and local wiring codes and laws.
This signal must last for 1.5 seconds or longer.
A battery shutdown signal will not cause an immediate shutdown. It will start a 2-minute shutdown timer. This timer cannot be stopped once triggered. If the utility power returns during this countdown, the Liebert GXT3 will still shut down and must remain shut down for 10 seconds. Whether the UPS turns back On when the power is restored depends on the auto-restart setting.
On Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power from the battery this dry contact will be closed.
Low Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power from the battery and has reached the Low Battery Warning time selected in the configuration program, this dry contact will be closed.
The Liebert IntelliSlot port on the UPS accepts three optional cards:
The Liebert IntelliSlot SNMP Card provides SNMP monitoring and control of the UPS across the network.
The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom-wired applications and delivers support for built-in shutdown for AS/400 systems.
The Liebert IntelliSlot 485 Card is used to connect the UPS and a BMS.
Follow instructions provided with the Liebert IntelliSlot card to configure Liebert MultiLink®, the UPS or any additional ancillary product for the Liebert GXT3. These instructions are available at multilink.liebert.com
Communication

Liebert MultiLink continually monitors the UPS and can shut down your computer or server in the event of an extended power failure.
Liebert MultiLink can also be configured for use without the USB cable when the Liebert IntelliSlot® SNMP/Web card is installed in the UPS. Additionally, Liebert MultiLink can be configured to coordinate shutdown across the network with other computers running Liebert MultiLink when you purchase a Liebert MultiLink License Kit. For more information about the Liebert IntelliSlot SNMP/Web Card and Liebert MultiLink License Kits, visit our Web site (www.liebert.com) or contact your local dealer or Emerson® representative.
Several option cards are available for use in the Liebert IntelliSlot® port of the Liebert GXT3. The Liebert IntelliSlot SNMP/Web Card provides SNMP and Web-based monitoring and control of the UPS across the network.
The Liebert IntelliSlot MultiPort 4 Card allows installing Liebert MultiLink software on four computers and coordinate shutdown in the event of a power failure.
The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom wired applications and delivers support for built-in shutdown for AS/400 systems.
! CAUTION To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables should be shielded and run separate from all other power cables, where applicable.
The UPS is equipped with a Remote Emergency Power Off (REPO) connector.
The user must supply a means of interfacing with the REPO circuit to allow disconnecting the UPS input feeder breaker to remove all sources of power to the UPS and connected equipment to comply with national and local wiring codes and regulations.
UPS ships with REPO jumper installed allowing the UPS to operate
Opening the REPO connection will disable the UPS. Manual restart using the front panel is required after the REPO connection is closed again.
Normally closed switch system (fail-safe)
! CAUTION To maintain safety (SELV) barriers and electromagnetic compatibility, signal cables should be shielded and run separately from power cables.
Communication

This section describes replacing the internal battery pack, precautions, checking the Liebert GXT3’s status and checking UPS functions.
The Liebert GXT3 is designed to allow the user to replace the internal battery pack safely. Read the safety cautions before proceeding. Contact your local dealer or Emerson® representative to obtain the part number and pricing of the appropriate replacement battery pack.
10.1.1 Battery Replacement Procedures 1. Gently remove the front plastic bezel cover from the UPS. 2. Loosen and remove the six screws on the battery door, as shown in Figure 17. 3. Lay the battery door and screws aside for reassembly.
Figure 17 Removing the front plastic bezel cover and battery door

10,000VA model shown; other model arrangement is similar
Figure 18 Disconnecting the battery plug and battery receptacle (front view)

6000VA model shown; other model arrangement is similar
Battery Connector Battery Receptacle Battery Connector

Figure 19 Pulling out the battery packs
5000 & 6000 VA models 10,000VA model


Each model has two battery packs
Pull Out with Battery Handle
Pull Out with Battery Handle
6. Unpack a new internal battery pack. Take care not to destroy the packing. Compare the new and old internal battery packs to make sure they are the same type and model. If they are the same, proceed with Step 7; if they are different, stop and contact your local Emerson® representative or Emerson Channel Support. 7. Line up and slide in the new internal battery pack. 8. Repeat Steps 6 7 if replacing both battery packs. Each model has two battery packs 9. Reconnect the battery plugs and battery receptacles. 10. Gently push the battery wire into the UPS battery compartment. 11. Reattach the front battery door with the six screws. 12. Reattach the front plastic bezel cover to the UPS.
The batteries are valve-regulated, nonspillable, lead acid and should be kept charged to attain their design life. The Liebert GXT3 charges the batteries continuously when it is connected to the mains input power.
If the Liebert GXT3 will be stored for a long time, Emerson recommends connecting the UPS to input power for at least 24 hours every four to six months to ensure full recharge of the batteries.
Although the Liebert GXT3 has been designed and manufactured to ensure personal safety, improper use can result in electrical shock or fire. To ensure safety, observe the following precautions:

Emerson® recommends checking the UPS operation status every six months.
Emerson recommends checking the UPS functions once every six months.
Back up the load data before conducting the UPS functions check. Procedures are as follows:
Maintenance

This section indicates various UPS symptoms a user may encounter and provides a troubleshooting guide in the event the UPS develops a problem. Use the following information to determine whether external factors caused the problem and how to remedy the situation.
The following symptoms indicate the Liebert GXT3 is malfunctioning:
In addition to the fault indicator being illuminated, one or more of LED segments of battery level indicator will also be illuminated to provide a diagnostic aid to the user, as shown in Figure 20. The descriptions are listed in Table 4.
Figure 20 Battery level indicator
Table 4 Indicator descriptions
A - E On bypass from output overload (half-second beep every half second)
A On bypass due to overtemperature condition (1-second beep every 4 seconds)
B On bypass due to DC bus overvoltage (1-second beep every 4 seconds)
C On bypass due to DC/DC power supply failure (1-second beep every 4 seconds)
D PFC failure (1-second beep every 4 seconds).
E On bypass due to inverter failure (1-second beep every 4 seconds)
A&C UPS failed battery test (2-second beep every 60 seconds)
C&E UPS shutdown by command from communication (USB port or Liebert IntelliSlot® port) (no audible)
A&B UPS Failure (includes dual-fan failure, single-fan failure under certain conditions and battery charger failure) and continuous alarm
Internal Battery source not available (continuous horn); check battery connection, power down and reboot UPS.
Bypass Indicator Flashing Mains power voltage or frequency is out of tolerance; bypass is unavailable
A - E indicators are shown in Figure 20
Troubleshooting · Indicator Diagnosis/Audible alarm · Battery Indicator Flashing

An audible alarm will sound in conjunction with the visual indicators to indicate a change in UPS operating status. The audible alarm will sound as described in Table 5.
Table 5 Audible alarm description
Battery discharge Half-second beep every 10 seconds
Low battery Two half-second beeps every 5 seconds
UPS fault, load on bypass 1-second beep every 4 seconds
UPS fault, no power to load Continuous
Overload Half-second beep every half second
Battery replacement 2-second beep every 60 seconds
Wiring problem (loss of proper grounding for UPS) Continuous
Bypass reminder 1-second beep every 2 minutes
In the event of an issue with the UPS, refer to Table 6 to determine the cause and solution. If the fault persists, contact Emerson® Channel Support.
Table 6 Troubleshooting table
UPS fails to start when the On/Alarm Silence/Manual Battery Test button is pressed
Ensure UPS is Off. Disconnect all loads and ensure nothing is lodged in output receptacles. Ensure loads are not defective or shorted internally.
UPS is short-circuited or overloaded
UPS is not plugged in UPS is operating from battery mode. Ensure UPS is securely plugged into the wall receptacle.
UPS input protection fuse has blown/opened
UPS is operating from battery mode. Save data and close applications. Replace UPS input fuse, then restart UPS.
Battery indicator is illuminated
UPS is operating from battery mode. Save data and close applications. Ensure mains supply voltage is within acceptable limits for UPS.
Mains power is out of tolerance
Batteries are not fully charged Keep UPS plugged in continuously at least 24 hours to recharge batteries.
UPS is overloaded Check load level indicator and reduce the load on the UPS.
UPS has reduced battery backup time
Replace batteries. Contact your local dealer, Emerson representative or Emerson Channel Support for replacement battery kit.
Batteries may not be able to hold a full charge due to age
Fault and Bypass indicators and all LED segments of battery level indicator are illuminated
Check load level indicator and remove non-essential loads. Recalculate the load and reduce number of loads connected to UPS. Check load for faults.
UPS is overloaded or load is faulty
Ensure UPS is not overloaded, ventilation holes are not blocked and room ambient temperature is not excessive. Wait 30 minutes to allow UPS to cool, then restart UPS. If UPS cannot restart, contact your local dealer, Emerson representative or Emerson Channel Support.
Fault and Bypass indicators and diagnostic A indicator are illuminated
UPS has been shut down due to temperature condition; load is on bypass power
Fault and Bypass indicators and diagnostic B indicator are illuminated
UPS internal DC bus overvoltage
UPS requires service. Contact your local dealer, Emerson representative or Emerson Channel Support.

Table 6 Troubleshooting table (continued)
Fault and Bypass indicators and diagnostic C indicator are illuminated
UPS DC/DC fault UPS requires service. Contact your local dealer, Emerson® representative or Emerson Channel Support.
Fault indicator and diagnostic D indicator are illuminated
UPS PFC (Power Factor Correction Circuit) fault
UPS requires service. Contact your local dealer, Emerson representative or Emerson Channel Support.
Fault and Bypass indicators and diagnostic E indicator are illuminated
UPS inverter fault UPS requires service. Contact your local dealer, Emerson representative or Emerson Channel Support.
Fault indicator and diagnostic A and C indicators are illuminated
UPS failed the battery test Replace batteries. Contact your local dealer, Emerson representative or Emerson Channel Support.
Your UPS has received a signal or command from the attached computer. If this was inadvertent, ensure the communication cable used is correct for your system. For assistance, contact your local dealer, Emerson representative or Emerson Channel Support.
Fault and Bypass indicators and diagnostic C and E indicators are illuminated
UPS has been shut down by a command from the communications port(s)
UPS failure (includes dual-fan failure, single-fan failure under certain conditions and battery charger failure) and continuous alarm
Fault indicator and diagnostic A and B indicators are illuminated
Ensure fan is not blocked up. If the fault is not removed, contact your local dealer, Emerson representative or Emerson Channel Support.
UPS detected a line-to-neutral reversal or a loss of proper grounding for UPS; continuous horn and UPS cannot start up in standby status. This is active only when power is first applied to the input. Once the UPS is running, the AC input indicator will flash, unless the input wiring is correctly changed.
AC input indicator is flashing.
Contact a qualified electrician to verify site wiring.
Check battery connections, completely power down and restart UPS. NOTE: If the battery circuit opens while the UPS is running, it will be detected when the next battery test is performed.
Battery indicator is flashing. Battery source is not available; continuous horn.
The AC input powers the PFC input and serves as the bypass source. If the AC is present but the voltage or frequency exceeds the acceptable range for safe operation with a load, the bypass will be disabled and this indicator will flash, indicating that the bypass is unavailable.
Because the voltage or frequency is outside acceptable limits, the bypass is disabled.
Bypass indicator is flashing.
When reporting a UPS issue to Emerson, include the UPS model and serial number. These are on the top panel of the Liebert GXT3.
Troubleshooting · Problem Cause Solution

Table 7 UPS specifications
Model # GXT3-5000RT230 GXT3-6000RT230 GXT3-10000RT230
Rating 5000VA/4000W 6000VA/4800W 10000VA/9000W
Unit, W x D x H 430 x 574 x 217 (16.9 x 22.4 x 8.5) 430 x 581 x 261 (16.9 x 22.9 x 10.3)
Shipping, W x D x H 516 x 745 x 530 (20.3 x 29.3 x 20.9) 530 x 745 x 563 (20.9 x 29.3 x 22.2)
Unit 60 (132.2) 70 (154.3)
Shipping 71 (156.5) 92 (202.8)
Operating Frequency, Nom 50 or 60Hz (Factory Default = 50)
Factory Default VAC 230VAC
User-Configurable VAC 220/230/240VAC (May be modified using included configuration program) Operating Voltage Range Without Battery Operation 176 - 280VAC
Maximum Allowable VAC 280VAC Input Frequency Without
Battery Operation 40 - 70Hz
Input Power Connection PD2-CE6HDWRMBS Standard (See 3.3 - Removable Power Distribution Box)
(See 3.3 - Removable Power
Distribution Box) Output AC Parameters
AC-AC Efficiency 92% AC-AC
Factory Default VAC 230VAC
Output Connections PD2-CE6HDWRMBS Standard (See 3.3 - Removable Power Distribution Box)
(See 3.3 - Removable Power
Distribution Box) Frequency 50Hz or 60Hz, Nominal
Main Mode Overload >200% for 5 cycles; 151 - 200% for 1 seconds; 131-150% 10 seconds; 105 - 130% 1 minute
Charger Current 1.3 2.6
Type Valve-regulated, non-spillable, lead acid
Quantity x V 20 x 12V
Battery Mfr. / Part # 5AH battery, CSB HR1221W or YUASA NPH5-12 9AH battery, CSB HR1234W or Panasonic UP-RW1245 Backup Time See Table 11 - Battery run time, minutes, all models Recharge Time (Internal
Batteries) 3 hr. to 90% capacity after full discharge into 100% load
Disable Bypass Operation If input voltage exceeds ±15% of the nominal voltage Re-Enable Bypass
Operation If input voltage returns to within ±10% of nominal output voltage
Disable Bypass operation When the input frequency prevents synchronous operation
°C (°F) 0 to 40 (32 to 104) see Table 8 - Operating temperature parameters
°C (°F) -15 to 50 (5 to 122)

Table 7 UPS specifications (continued)
Model # GXT3-5000RT230 GXT3-6000RT230 GXT3-10000RT230
Relative Humidity 0-95% non-condensing
Operating Elevation Up to 1000m (3281 ft) at 25°C (77°F) without derating
Audible Noise
Safety IEC62040-1:2008 version, GS mark
EMI/EMC/C-Tick EMC IEC/EN/AS 62040-2 2nd Ed (Cat 2 – Table 6)
ESD IEC/EN EN61000-4-2, Level 4, Criteria A
Radiated Susceptibility IEC/EN EN61000-4-3, Level 3, Criteria A
Electrical Fast Transient IEC/EN EN61000-4-4, Level 4, Criteria A
Surge Immunity IEC/EN EN61000-4-5, Level 3, Criteria A
Transportation ISTA Procedure 1A
Table 8 Operating temperature parameters
Ambient Temperature, °C (°F) pf @30°C ±3°C (pf @ 86°F ±5.4°F)
pf @40°C ±3°C (pf @ 104°F ±5.4°F)
5000RT230, 6000RT230 0.8pf 0.8pf
10000RT230 0.9pf 0.8pf
Table 9 Power distribution specifications
Model Number PD2-CE6HDWRMBS PD2-CE10HDWRMBS
Amp Rating 32 Amps 63 Amps
Input Power Connection Single-phase (L-N-G) hard-wired, 6-10mm2 (8-10AWG)
Output Power Connection Single-phase (L-N-G) hard-wired, 6-10mm2 (8-10AWG)
Two IEC320 C19 16A/250V Sockets
Four IEC320 C19 16A/250V Sockets,
Includes:
Six C13 10A/250V Sockets Manual Bypass Switch with Indicator Lamps
Four C13 10A/250V Sockets Manual Bypass Switch with Indicator Lamps
Input Branch Circuit Breaker, Supplied by User 32A 63A
Specifications · Agency

Table 10 External battery cabinet specifications
Model Number GXT3-240VBATTCE GXT3-240RTVBATT
Used with UPS Model
Dimensions, W x D x H, mm (in.)
Unit (with bezel) 430 x 574 x 130 (16.9 x 22.6 x 5.8) 430 x 581 x 173 (16.9 x 22.9 x 6.8) Shipping 530 x 745 x 407 (20.9 x 20.3 x 16.0) 530 x 745 x 475 (20.9 x 29.3 x 18.7)
Unit 43 (94.8) 65 (143.3) Shipping 54 (119) 76 (167.6) Battery Parameters
Type Valve-regulated, non-spillable, lead acid Quantity x V 1 x 20 x 12V Battery Manufacturer, Part # CSB HR1221W CSB HR 1234W
Backup Time See Table 11
Operating Temp, °C (°F) 0 to 40 (32 to 104) see Table 8 - Operating temperature parameters
Storage Temp, °C (°F) -15 to 50 (5 to 122)
Relative Humidity 0-95% non-condensing
Operating Elevation Up to 1000m (3280.83 ft.) at 25°C (77°F)
Safety IEC62040-1:2008 version Transportation ISTA Procedure 1A

Table 11 Battery run time, minutes, all models
10% 105 97 81
20% 52 47 39
30% 40 33 22
40% 27 22 15
50% 21 17 11
60% 17 14 9
70% 14 11 7
80% 12 9 5
90% 10 8 4
100% 9 6 3
10% 187 158 149
20% 106 97 82
30% 78 65 50
40% 53 48 39
Internal Battery + 1 External Battery Cabinet
50% 47 40 28
60% 40 33 22
70% 34 26 17
80% 28 22 15
90% 23 19 13
100% 21 17 11
10% 217 205 191
20% 146 123 128
30% 106 97 82
40% 91 74 60
Internal Battery + 2 External Battery Cabinets
50% 71 53 47
60% 53 48 39
70% 49 43 32
80% 45 38 26
90% 41 33 22
100% 37 28 18
10% 360 223 224
20% 188 158 150
30% 132 110 112
40% 106 97 82
Internal Battery + 3 External Battery Cabinets
50% 95 78 66
60% 79 66 50
70% 68 52 45
80% 53 48 40
90% 50 44 34
100% 47 41 28

Table 11 Battery run time, minutes, all models
10% 460 360 316
20% 205 191 163
30% 159 138 137
40% 124 108 107
Internal Battery + 4 External Battery Cabinets
50% 106 97 82
60% 98 81 69
70% 83 71 52
80% 75 61 48
90% 66 51 44
100% 53 48 40
Using the configuration program, the user may specify the number of GXT3-240VBATT external battery cabinets attached to the UPS. The factory default is programmed for internal batteries only.
Table 11 shows the estimated run times at different loads.
As batteries age, the estimated run times may become less accurate. The Liebert GXT3 is programmed to “learn” from a full battery discharge and modify the estimated runtime for the measured battery capacity. This can improve accuracy and compensate for aging batteries or batteries that operate at different ambient temperatures.
The UPS will update the anticipated run time calculation only under certain conditions.
If all conditions are not met, the run time calculation will not be modified.
If the configuration program is used to change the number of battery cabinets, then the values in the battery above table will be restored. This will override any value that is Auto-Learned.

Specifications



Ensuring The High Availability Of Mission-Critical Data And Applications.
Emerson Network Power, a business of Emerson (NYSE:EMR), is the global leader in enabling Business-Critical Continuity™
Technical Support / Service
Web Site www.liebert.com
from grid to chip for telecommunication networks, data centers, health care and industrial facilities. Emerson Network Power provides innovative solutions and expertise in areas including AC and DC power and precision cooling systems, embedded computing and power, integrated racks and enclosures, power switching and controls, infrastructure management, and connectivity. All solutions are supported globally by local Emerson Network Power service technicians. Liebert AC power, precision cooling and monitoring products and services from Emerson Network Power deliver Efficiency Without Compromise™ by helping customers optimize their data center infrastructure to reduce costs and deliver high availability.
Monitoring liebert.monitoring@emerson.com
Single-Phase UPS & Server Cabinets
liebert.upstech@emerson.com
Three-Phase UPS & Power Systems
Locations United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229
Europe Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy +39 049 9719 111 Fax: +39 049 5841 257
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2010 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
Asia 29/F, The Orient Square Building F. Ortigas Jr. Road, Ortigas Center
Philippines +63 2 687 6615 Fax: +63 2 730 9572
Emerson Network Power. The global leader in enabling Business-Critical Continuity™ EmersonNetworkPower.com
Embedded Computing Embedded Power
Racks & Integrated Cabinets Services
Power Switching & Controls Precision Cooling
Infrastructure Management & Monitoring
Emerson, Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks of Emerson Electric Co. or one of its affiliated companies. ©2010 Emerson Electric Co.
Pages referenced in this manual — manufacturer, support and downloads.
Common problems, likely causes, and what to do.
| Problem | Possible cause | Remedy | |
|---|---|---|---|
| UPS fails to start when the On/Alarm Silence/Manual Battery Test button is pressed | UPS is short-circuited or overloaded | Ensure UPS is Off. Disconnect all loads and ensure nothing is lodged in output receptacles. Ensure loads are not defective or shorted internally. | p.39 |
| Battery indicator is illuminated | UPS is not plugged in | UPS is operating from battery mode. Ensure UPS is securely plugged into the wall receptacle. | p.39 |
| Battery indicator is illuminated | UPS input protection fuse has blown/opened | UPS is operating from battery mode. Save data and close applications. Replace UPS input fuse, then restart UPS. | p.39 |
| Battery indicator is illuminated | Mains power is out of tolerance | UPS is operating from battery mode. Save data and close applications. Ensure mains supply voltage is within acceptable limits for UPS. | p.39 |
| UPS has reduced battery backup time | Batteries are not fully charged | Keep UPS plugged in continuously at least 24 hours to recharge batteries. | p.39 |
| UPS has reduced battery backup time | UPS is overloaded | Check load level indicator and reduce the load on the UPS. | p.39 |
| UPS has reduced battery backup time | Batteries may not be able to hold a full charge due to age | Replace batteries. Contact your local dealer, Emerson representative or Emerson Channel Support for replacement battery kit. | p.39 |
| Fault and Bypass indicators and all LED segments of battery level indicator are illuminated | UPS is overloaded or load is faulty | Check load level indicator and remove non-essential loads. Recalculate the load and reduce number of loads connected to UPS. Check load for faults. | p.39 |
| Fault and Bypass indicators and diagnostic A indicator are illuminated | UPS has been shut down due to temperature condition; load is on bypass power | Ensure UPS is not overloaded, ventilation holes are not blocked and room ambient temperature is not excessive. Wait 30 minutes to allow UPS to cool, then restart UPS. If UPS cannot restart, contact your local dealer, Emerson representative or Emerson Channel Support. | p.39 |
| Fault and Bypass indicators and diagnostic B indicator are illuminated | UPS internal DC bus overvoltage | UPS requires service. Contact your local dealer, Emerson representative or Emerson Channel Support. | p.39 |
| Fault and Bypass indicators and diagnostic C indicator are illuminated | UPS DC/DC fault | UPS requires service. Contact your local dealer, Emerson® representative or Emerson Channel Support. | p.40 |
| Fault indicator and diagnostic D indicator are illuminated | UPS PFC (Power Factor Correction Circuit) fault | UPS requires service. Contact your local dealer, Emerson representative or Emerson Channel Support. | p.40 |
| Fault and Bypass indicators and diagnostic E indicator are illuminated | UPS inverter fault | UPS requires service. Contact your local dealer, Emerson representative or Emerson Channel Support. | p.40 |
| Fault indicator and diagnostic A and C indicators are illuminated | UPS failed the battery test | Replace batteries. Contact your local dealer, Emerson representative or Emerson Channel Support. | p.40 |
| Fault and Bypass indicators and diagnostic C and E indicators are illuminated | UPS has been shut down by a command from the communications port(s) | Your UPS has received a signal or command from the attached computer. If this was inadvertent, ensure the communication cable used is correct for your system. For assistance, contact your local dealer, Emerson representative or Emerson Channel Support. | p.40 |
| Fault indicator and diagnostic A and B indicators are illuminated | UPS failure (includes dual-fan failure, single-fan failure under certain conditions and battery charger failure) and continuous alarm | Ensure fan is not blocked up. If the fault is not removed, contact your local dealer, Emerson representative or Emerson Channel Support. | p.40 |
| AC input indicator is flashing. | UPS detected a line-to-neutral reversal or a loss of proper grounding for UPS; continuous horn and UPS cannot start up in standby status. This is active only when power is first applied to the input. Once the UPS is running, the AC input indicator will flash, unless the input wiring is correctly changed. | Contact a qualified electrician to verify site wiring. | p.40 |
| Battery indicator is flashing. | Battery source is not available; continuous horn. | Check battery connections, completely power down and restart UPS. NOTE: If the battery circuit opens while the UPS is running, it will be detected when the next battery test is performed. | p.40 |
| Bypass indicator is flashing. | Because the voltage or frequency is outside acceptable limits, the bypass is disabled. | The AC input powers the PFC input and serves as the bypass source. If the AC is present but the voltage or frequency exceeds the acceptable range for safe operation with a load, the bypass will be disabled and this indicator will flash, indicating that the bypass is unavailable. | p.40 |