ACTURA Flex 48330 Power Systemp.1User Manualp.1Version: V1.0 Revision date: May 20, 2005 BOM: 31011084p.1Homepage: www.emersonnetworkpower.com.cnp.1E-mail: [email protected]p.1Safety Precautionsp.2Electrical Safetyp.24. ESDp.3Batteryp.3Special Safe Requirements of This Equipmentp.4Othersp.4Chapter 1 System Descriptionp.111.1 Abbreviationp.111.2 Introductionp.111.3 Featuresp.111.4 System Configurationp.121.5 Componentsp.141.5.1 Rectifier Shelfp.14Outlinep.14Backboardp.15Connector boardp.151.5.2 Rectifierp.161.5.3 SCUp.17Multi-Communication modep.17Functions fulfilled by SCU and MCp.18Alarm category settings for dry contact outputp.18Password protection for important operationsp.191.5.4 Multi-Function Unit (MFU)p.19Outline and componentsp.19SPDp.191.5.5 Battery Connection Unit (BCU)p.20Physical sizep.20Alarm outputp.20BCU configurationp.211.5.6 System Cabinetp.21Chapter 2 Installationp.222.1 Installation Preparationp.222.1.1 Environmental Conditionsp.222.1.2 Power Supplyp.222.1.3 Site Surveyp.232.1.4 Tools & Materialp.23A= Σ I×L/K △ Up.232.1.5 Unpackingp.242.2 Installation Proceduresp.252.2.1 Cabinet Installationp.25Installation on the floorp.252.3 External Electrical Connection Interfacep.272.3.1 Connection Of Input Cablesp.27Connection requirementsp.27Connection methodp.27Different cable connection modesp.28L1 L2 L3 Np.28N Lp.29Notep.292.3.2 Connection Of Load Cablesp.302.3.3 Connection Of Communication Cablesp.31J10p.31J11p.312.3.4 Layout Of Connector Board S6415X2p.322.3.5 Interface Definition Of Connector Board S6415X2p.33J3p.33J4p.33J5p.33J6p.33J12, J18p.33J13p.332.3.6 Connection Of Temperature Sensor Cablesp.342.3.7 Connection With MODEMp.34Conneting modem with M500D control unitp.342.3.8 Connection With Dry Contactsp.35Connecting methodp.352.4 Battery Installation And Cablingp.352.4.1 Battery Installationp.352.4.2 Battery Cable Connectionp.36Standard configurationp.36Non-standard configurationp.382.5 Parallel Connection Of Cabinetsp.39BCUp.39DC/Parallel connectionsp.39Chapter 3 Startupp.40
Page 1 of the Emerson 48330 user manual — Homepage: www.emersonnetworkpower.com.cn
Page 1 · click to enlarge
Page 1

ACTURA Flex 48330 Power System

User Manual

Version: V1.0 Revision date: May 20, 2005 BOM: 31011084

Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or service center.

Copyright © 2005 by Emerson Network Power Co., Ltd.

All rights reserved. The contents in this document are subject to change without notice.

Emerson Network Power Co., Ltd.

AddressNo.1 Kefa Rd., Science & Industry Park, Nanshan District 518057, Shenzhen China

Homepage: www.emersonnetworkpower.com.cn

E-mail: [email protected]

Page 2 of the Emerson 48330 user manual — Electrical Safety
Page 2 · click to enlarge
Page 2

Safety Precautions

To avoid accident, read the safety precautions very carefully before operation. The "Caution, Notice, Warning, Danger" in this manual do not represent all the safety points to be observed. Therefore, the installation and operation personnel must be strictly trained and master the correct operations and all the safety points before actual operation.

When operating Emerson products, the safety rules in the industry, the general safety precautions and special safety instructions must be strictly observed.

Electrical Safety

1. Hazardous voltage

Some components of the power system carry hazardous voltage in operation, direct contact or indirect contact through moist objects with these components will result in fatal injury.

Safety rules in the industry must be observed when installing the power system. The installation personnel must be licensed to operate high voltage and AC power.

In operation, be sure to remove conductive objects, such as watch, bracelet, ring, and so on.

When water or moisture is found on the cabinet, turn off the power immediately. In moist environment, take precautions to keep moisture out of the power system.

"Prohibit" warning label must be attached to the switches and buttons which are not permitted to be operated on during installation.

High voltage operation may cause fire and electric shock. The connection and wiring of AC cables must be in compliance with the local codes and regulations. Only those who are licensed to operate high voltage and AC power can perform high voltage operations.

2. Tools

In high voltage and AC operation, special tools must be used. No common or homemade tools should be used.

3. Thunderstorm

Never operate on high voltage, AC, iron tower or mast on a day with thunderstorm.

Page 3 of the Emerson 48330 user manual — Battery
Page 3 · click to enlarge
Page 3

In thunderstorms, a strong electromagnetic field will be generated in the air. Therefore the equipment should be well-earthed in time to avoid damage by lightning strikes.

4. ESD

The static electricity generated by the human body will damage the static sensitive elements on PCBs, such as large-scale ICs. Before touching any plug-in board, PCB or IC chip, ESD wrist strap must be worn to prevent body static from damaging the sensitive elements. The other end of the ESD wrist strap must be well earthed.

During operation, never short the positive and negative terminals of the MFU of the system or the non-earthing terminal and the earth. The power system is a constant voltage DC power equipment, short circuit will result in equipment burning and endanger human safety.

Check carefully the polarity of the cable and connection terminal when performing DC live operations.

Never wear a watch, bracelet, ring, or other conductive objects during operation.

Insulated tools must be used.

Battery

Before any operation on battery, read very carefully the safety precautions for battery transportation and the correct battery connection method.

Non-standard operation on the battery will cause danger. In operation, precautions should be taken to prevent battery short circuit and overflow of electrolyte. The overflow of electrolyte will pose potential threat to the equipment, it will erode the metal objects and PCBs, thus causing equipment damage and short circuit of PCBs.

Before any operation on battery, pay attention to the following points:

Remove the watch, bracelet, bangle, ring, and other metal objects on the wrist.

Use special insulated tools.

Wear an eye protection device, and take preventive measures.

Wear rubber gloves and apron to guard against electrolyte overflow.

In battery transportation, the electrode of the battery should always be kept facing upward. Never put the battery upside down or slanted.

5 Short-circuit

Page 4 of the Emerson 48330 user manual — Others
Page 4 · click to enlarge
Page 4

Special Safe Requirements of This Equipment

The equipment has multi power inputs;

The equipment shall be installed on cement ground.

Others

Please use the same model fuse to replace the fuse in the DC Power System.

2. Sharp object

When moving equipment by hand, wear protective gloves to avoid injury by sharp object.

3. Cable connection

Please verify the compliance of the cable and cable label with the actual installation prior to cable connection.

4. Binding the signal cables

The signal cables should be installed separately far away from heavy current and high voltage cables, with distance at least 150mm.

1 Safety requirement

Page 5 of the Emerson 48330 user manual — Special Safe Requirements of This Equipment
Page 5 · click to enlarge
Page 5
Page 5 of the Emerson 48330 user manual — Special Safe Requirements of This Equipment
Page 6 of the Emerson 48330 user manual — Special Safe Requirements of This Equipment
Page 6 · click to enlarge
Page 6
Page 6 of the Emerson 48330 user manual — Special Safe Requirements of This Equipment
Page 7 of the Emerson 48330 user manual — Special Safe Requirements of This Equipment
Page 7 · click to enlarge
Page 7
Page 7 of the Emerson 48330 user manual — Special Safe Requirements of This Equipment
Page 8 of the Emerson 48330 user manual — Special Safe Requirements of This Equipment
Page 8 · click to enlarge
Page 8
Page 8 of the Emerson 48330 user manual — Special Safe Requirements of This Equipment
Page 9 of the Emerson 48330 user manual — Special Safe Requirements of This Equipment
Page 9 · click to enlarge
Page 9
Page 9 of the Emerson 48330 user manual — Special Safe Requirements of This Equipment
Page 10 of the Emerson 48330 user manual — Special Safe Requirements of This Equipment
Page 10 · click to enlarge
Page 10
Page 10 of the Emerson 48330 user manual — Special Safe Requirements of This Equipment
Page 11 of the Emerson 48330 user manual — 1.3 Features
Page 11 · click to enlarge
Page 11

Chapter 1 System Description 1

Chapter 1 System Description

1.1 Abbreviation

SCU Standard Controller Unit

BCU Battery Connection Unit

CSU Central Supervision Unit

HVSD High Voltage Shutdown

MCB Miniature Circuit Breaker

APFC Active Power Factor Correction

1.2 Introduction

The ACTURA Flex 48330 Power system consists of 50A rectifiers, Control Unit, Multi-Function Unit (MFU), rectifier shelf and BCU (optional).

The product is used in base station, small exchange station, satellite communication, data communication, and so on, with a strong adaptability to power network fluctuation.

This system is used as a power supply for telecom equipment with system nominal voltage of -48V and positive terminal earthed.

1.3 Features

The DC power system is easy-to-operate, easy-to-install and easy-to-maintain. Its main features are:

z Rectifier uses APFC technology and therefore its PF is up to 0.99;

z Wide AC input voltage range of 85~290V;

z Rectifier efficiency is at least 90%;

z Extra low EMI of rectifier and excellent EMC performance;

AC Alternate Current · DC Direct Current · MFU Multi-Function Unit

Page 12 of the Emerson 48330 user manual — 1.4 System Configuration
Page 12 · click to enlarge
Page 12

2 Chapter 1 System Description

z High power density of rectifier;

z Rectifier has damage-free hot plugging/unplugging function, the replacement

time is less than 1min;

z Rectifier has two kinds of over-voltage protection methods;

z Perfect battery management with BLVD function;

z Up to 200 PCS of historical alarms can be stored in SCU;

z Provide RS232, Modem and dry contacts communication interfaces;

1.4 System Configuration

The outline of the DC Power System is illustrated in Figure 1-1:

Emerson 48330 — 1.4 System Configuration diagram (page 12)
Fig. 1 · 1.4 System Configuration

There are three kinds of DC Power Systems, and their detail configurations are as shown in Table 1-1:

Multi-function unit · Door · Figure 1-1 Outline

Page 13 of the Emerson 48330 user manual — 1.4 System Configuration
Page 13 · click to enlarge
Page 13

Chapter 1 System Description 3

Table 1-1 Configurations of Actura Flex 48330 Power System

2.0 % 0.6 % 0.6 m3 2.0 % 0.6 % 0.4 m3 0.7 % 0.6 % 0.4 m3

3P+N/380V AC input with SPD

3P+N/380V AC input without SPD

1P+N/220V AC input with SPD

1P+N/220V AC input without SPD

L1+L2/220V AC input with SPD

L1+L2/220V AC input without SPD

3P/220V AC input with SPD

3P/220V AC input without SPD

5 2P AC input MCBs

Individual AC cables with just terminals

DC distribution Up to 28 13mm-wide MCB, or 20 18mm-wide MCB

Rectifier Up to 5 rectifiers

Control unit 1 SCU

BCU 1 BCU with up to 5 battery circuit breakers

Telion 12V 165Ah FT16 Blocks

Hawker 12V82F:

Hawker 12V 155Ah FT16 Blocks

Hawker SBSC11 and 3U space:

Hawker 12V 105Ah FT20 Blocks
EB420 Blocks

Hawker 12V 105Ah FT and 6U space:

Hawker 12V82F( no BCU):

Dimensions (H×W ×D) mm 2000×600×600 2000×600×400 700×600×400

Show 8 more labels / short text on this page
Cabinet dimension Configuration · AC distribution · 16 Blocks · Battery · 16 Blocks · No battery · 16 Blocks · 20 Blocks
Page 14 of the Emerson 48330 user manual — Outline
Page 14 · click to enlarge
Page 14

4 Chapter 1 System Description

1.5 Components

1.5.1 Rectifier Shelf

Outline

The outline of the Rectifier Shelf is illustrated in Figure 1-2:

Terminal connecting 50A Rectifier

Emerson 48330 — Outline diagram (page 14)
Fig. 2 · Outline
Emerson 48330 — Outline diagram (page 14)
Fig. 3 · Outline

(a) Actual appearance (front view)

Emerson 48330 — Outline diagram (page 14)
Fig. 4 · Outline
Emerson 48330 — Outline diagram (page 14)
Fig. 5 · Outline
Emerson 48330 — Outline diagram (page 14)
Fig. 6 · Outline

(b) Actual appearance (rear view)

Figure 1-2 Rectifier shelf outline

The shelf can accommodate 5 rectifiers and a control unit as shown in Figure 1-3. The user can mount the rectifier shelf into cabinets with widths of 600mm and depths of 400mm. The rectifier shelf has a height of 3U (132.5mm).

Emerson 48330 — Outline diagram (page 14)
Fig. 7 · Outline

Figure 1-3 Rectifier shelf with rectifiers and CU

Show 4 more labels / short text on this page
Chassis Connector Board · Ear Bracket · Bus Bar · Back Board
Page 15 of the Emerson 48330 user manual — Connector board
Page 15 · click to enlarge
Page 15

Chapter 1 System Description 5

The Dimension of Rectifier Shelf are given in Table 1-2

Table 1-2 Dimensions of rectifier shelf

Manufacture type W(mm) ×D(mm) ×H(mm) Note

PSS485023/C 584.2×327×132.5 23’’ with controller

Backboard

The backboard has the functions below:

z DC power source feed for controller and the connector board.

z DC input filter and input fuse.

z All the ingoing and outgoing signals of the controller

The backboard also contains system internal connectors below:

z 10 Distribution unit fuses alarm signal measurement input

z 4 battery fuse alarm signal measurement input

z 2 battery current shunt measurement inputs

z 1 load Current shunt measurement input

z System bus-bar DC Voltage measurement input

z Three-phase from two mains AC Voltage measurement inputs

z CAN communication between rectifiers and controller

z AC alarm module signals

z System fault indicator drivers

z LLVD & BLVD mono contactor driver outputs

z The entire signal outgoing to the connector board

Connector board

Connector board is a user interface board and has the functions below:

z 8-channel relay outputs

z 8-channel digital inputs

z One power source feed terminal (for digital inputs)

z 2-channel temperature sensor inputs

z 2-channel RS232 parallel connection outputs

z LLVD & BLVD bistable contactor driver circuits and outputs

Page 16 of the Emerson 48330 user manual — Outline
Page 16 · click to enlarge
Page 16

6 Chapter 1 System Description

z One Ethernet output

z One RS485 output

z One console output for ECU debug

z The connector board can be hot plug and has enough space for

accommodating all the interface cables.

z The connector board should space the hollow to the SCU convection for air

z The connector board is mounted in the room 1U×2U at the top of the SCU.

z The shelf has a 1U×2U panel for the connector board.

z One RS232 and Ethernet ports are located at the front of the connector board.

z The shelf has two rails for supporting the connector board

1.5.2 Rectifier

Outline

The appearance and dimensions (unit: mm) of the rectifier are illustrated in the following figure.

Emerson 48330 — Outline diagram (page 16)
Fig. 8 · Outline
Weight≤3.5kg

Dimensions (H × W % D): 124.3mm % 84mm % 287mm

The functions of the indicators in front panel are listed in Table 1-3.

flowing · Figure 1-4 Dimensions

Page 17 of the Emerson 48330 user manual — Multi-Communication mode
Page 17 · click to enlarge
Page 17

Chapter 1 System Description 7

Table 1-3 Function of indicators

LED Normal Abnormal Cause of abnormality

OFF No AC Mains Supply Power indicator (green) ON

Blinking Rectifier is under control by SCU

ON AC input over/under voltage, PFC over/under voltage and over temperature Protection indicator (yellow) OFF

Blinking Communication of rectifier with SCU failure

ON Output Over-voltage Alarm indicator (red) OFF

1.5.3 SCU

Outline

Emerson 48330 — Outline diagram (page 17)
Fig. 9 · Outline

Figure 1-5 Outline of SCU

Dimension (H % W % D):132mm % 85mm % 287mm

Weight0.76kg

Multi-Communication mode

SCU communicates with MC (Main Computer) through the RS232/MODEM communication port and 8 groups of alarm dry contacts on the Signal Junction Board.

SCU supports both China Telecom Communication Protocol and EEM Protocol. Make sure that the baud rates for receiving and transmitting are set to be consistent when using SCU.

1. Communication through RS232

RS232 communication mode is mainly used for short-distance point-to-point communication. The communication distance shall be less than 15m. If SCU communicates with MC through RS232, just connect SCU RS232 port to the RS232 port of MC.

2. Communication through MODEM or ES-MOD

Blinking Fan Failure

Page 18 of the Emerson 48330 user manual — Alarm category settings for dry contact output
Page 18 · click to enlarge
Page 18

8 Chapter 1 System Description

When SCU communicates with MC through MODEM or ES-MOD, it uses PSTN to realize long-distance monitoring. Power supply cables and communication cables shall be prepared for the communication through MODEM.

3. Dry Contacts Output

SCU has 8 dry-contact outputs. Every dry-contact output has NC (normally closed) and NO (normally-open) contacts. Every dry-contact output shall be configured before the alarm event occurs. Different dry-contact output can trigger different alarms. Once the alarm event occurs, the dry-contact will close or open to generate the alarm.

If the user has other intelligent equipment to be monitored by SCU, the user can connect the dry contacts to the interface of the intelligent equipment, and control the intelligent equipment through these dry contacts.

Capacity of dry contacts2A@30Vdc; 05A@125Vac;
Maximum power dissipation60W

Functions fulfilled by SCU and MC

In RS232 and MODEM communication modes, the MC can fulfill the following functions through SCU:

1. Remote acquisition of analog and digital values: MC can acquire the real-time analog and digital values of DC Power System through SCU;
2. Remote control functions: MC can shut down the rectifiers, change the boost charge status to float charge status (or in reverse), silence the alarm and stop/start the battery test through SCU.

Alarm category settings for dry contact output

1. Through setting the parameter of “Relate Relay”, the user can configure the alarm category for every dry-contact output. Every dry-contact output has been configured to correspond to an alarm category before SCU is delivered to customer.

2. SCU has PLC functions in the alarm management. The PLC is to realize simple logic operation, i.e. the "And", "Or" and "Not" operations. The PLC inputs are all the possible alarm signals, and the PLC outputs can be used to select one of the 8 dry contacts. The alarm categories can be configured flexibly for every dry-contact output through MC. The PLC settings for every dry-contact have three alarm inputs, and two relation flag. The SN of three alarm categories and the mutual logic relationships need to be configured.

PLC can be set to “Disabled”. If PLC functions and alarm co-relation are enabled at the same time, the dry contact will act to activate an alarm when any alarm event occurs.

Page 19 of the Emerson 48330 user manual — SPD
Page 19 · click to enlarge
Page 19

Chapter 1 System Description 9

Password protection for important operations

The users must input the correct password before they conduct “Maintenance” and “Settings” operations. The password has 3 levels: user, operator or administrator. The authorities of the 3 levels are the same while conducting “Maintenance”, but different in conducting “Settings”. The operator can see 3 more pages than the user, which are “resetting system”, “resetting password” and “modifying system type”. The administrator can see 2 more pages than the operator, which are “modifying password of all levels” and “controlling alarm sound volume”. In addition, the administrator can browse the rectifier parameter serial No., software version and the setting of internal switches. See the following table:

Table 1-4 Authority and default password

Level Authority Default password

User Configuration of general parameters 123456

Operator User’s authority, plus resetting system, resetting password and modifying system type. 654321

Operator’s authority, plus modifying password of all levels, controling alarm sound volume, browsing system parameters that can be set only through the host

1.5.4 Multi-Function Unit (MFU)

Outline and components

The outline and the components of the MFU are illustrated in the following figure.

PE bus OV DC bus

LLVD contactor Bypass bar

SPD

Rectifier AC input MCB

Low prior load bus

Figure 1-6 Outline and components of MFU

Show 8 more labels / short text on this page
Administrator · Shunt · AC input terminals · BLVD contactor · Battery MCB · Battery -48V bus · Load MCB · Prior load bus
Page 20 of the Emerson 48330 user manual — Alarm output
Page 20 · click to enlarge
Page 20

10 Chapter 1 System Description

Table 1-5 Configuration of MFU

No. Component Description

1 SPD Norminal Dischage Current(8/20μS) 20kA; Ue=385V

2 AC input terminals Rating Current 150A 3 Rectifier AC input MCB Rating Current 25A 4 BLVD contactor 200A or 400A optional 5 LLVD contactor 200A or 400A optional 6 Shunt 300A/75mV 7 Battery MCB 100A MCB (up to 5 battery MCBs can be selected to configure) 8 Load MCB Selected according to user’s requirement

The user can mount the distribution unit into cabinets with widths of 600mm and depths of 400mm and 600mm. It has a height of 4.5U (200mm).

1.5.5 Battery Connection Unit (BCU)

Outline

The outline of the Battery Connection Unit (BCU) is illustrated in Figure1-7.

Figure 1-7 Outline of battery connection unit (BCU)

Physical size

Battery Connection Unit (BCU) can be installed in cabinets with widths of 600mm and depths of 400mm and 600mm. BCU has a maximum height of 1.5U (67mm).

BCU contains 2 to 5 circuit breakers, each with ratings of 100A and 200A.

Alarm output

The BCU will generate an alarm if a battery circuit breaker is off. This alarm shall be possible to connect to the connector board for display in the Controller. It shall be possible to combine the alarms from 2 BCUs to generate a single alarm in the controller. It shall also be possible to combine the alarm from the BCU with an

Enclosure · Battery MCB · -48V DC Bus

Page 21 of the Emerson 48330 user manual — 1.5.6 System Cabinet
Page 21 · click to enlarge
Page 21

Chapter 1 System Description 11

alarm generated from battery circuit breakers that are switched off in the BCU (for example when using a BCU in an extension battery cabinet and battery circuit breakers in the BCU in a main cabinet).

BCU configuration

The BCU configuration is as shown in Table 1-6:

Table 1-6 BCU configuration

Item Function unit Amount

100A CB for battery input 2/3/4/5 Battery connection unit

200A CB for battery input 2/3/4/5

1.5.6 System Cabinet

There are three kinds of cabinets. Their dimensions are 2.0m % 0.6m % 0.6m, 2.0m

% 0.6m % 0.4m and 0.7m % 0.6m % 0.4m respectively.

2.0m % 0.6m % 0.6m cabinet

This cabinet is installed with 1 % MFU, 1 % Rectifier Sub-rack, 1 % BCU and the following combination of units:

z 16 Blocks of Telion 12V 165Ah FT batteries or 16 % Hawker 12V 155Ah FT

z 20 Blocks of Hawker 12V 105Ah FT batteries

z 16 Blocks of Telion 12V 100Ah FT batteries (20 blocks is preferred, if possible)

z 16 Blocks of Hawker 12V 105Ah Ft batteries and 6U of unspecified equipment

(such as DC/DC converters or similar)

2.0m % 0.6m % 0.4m cabinet

This cabinet accommodates 1 % MFU,1 % Rectifier Sub-rack, 1 % BCU and the following combination of units:

z 16 Blocks of Hawker 12V82F batteries or 16 Blocks of Hawker SBSC11 and

3U available for additional equipment such as DC/DC converters

z 20 Blocks of EB4 batteries

20 blocks of Hawker 12V82F batteries (20 blocks and BCU is preferred, if possible)

0.7m % 0.6m % 0.4m cabinet

This cabinet accommodates 1 % MFU, 1 % Rectifier Sub-racks and 1 % BCU. There shall be 3U available for the mounting of additional equipment such as DC/DC converters. The cabinet should not be installed any battery.

batteries

Page 22 of the Emerson 48330 user manual — 2.1.2 Power Supply
Page 22 · click to enlarge
Page 22

12 Chapter 2 Installation

Chapter 2 Installation

2.1 Installation Preparation

2.1.1 Environmental Conditions

Make sure the following environmental conditions are satisfied when selecting the installation site:

Table 2-1 Environmental conditions in power room

Environmental conditions Recommended range

-5~50°C (If ambient temperature > 45°C, for the cabinet with 400mm depth, it should demount the front door of cabinet to ensure the normal operation of the system.)

Sunlight No direct sunlight

Corrosives No pollutants, such as salt, acid, and smoke, etc.

Shake ≤1.5m/s

Insects, pests, and termites None

Fire protection No flammable on the top/bottom of the cabient.

The DC Power system will be damaged if dust or sand accumulates in it. The following measures are recommended for dusty environment:

1.The system should be installed in an airtight and air-conditioned power room. The air-conditioner filter should be well serviced without being obstructed. To reduce the dust in the power room, un-attendance in the power room is recommended.

2.The air filter should be cleaned periodically.

3.The product should be installed on a cement ground.

2.1.2 Power Supply

AC power supply for communication uses AC mains as its main power source. Backup batteries and generator should be configured according to the actual power supply situation. The AC power supply system composed of AC mains and generator should adopt centralized power supply mode to supply power, while low

Show 5 more labels / short text on this page
Ambient temperature · Humidity ≤90%RH, non-condensing · Dust ≤1mg/m · Mildew None · Moisture Water proof
Page 23 of the Emerson 48330 user manual — A= Σ I×L/K △ U
Page 23 · click to enlarge
Page 23

Chapter 2 Installation 13

voltage AC power supply system should adopt three-phase five-line or single-phase three-line modes.

The AC power cable should adopt copper core cable, and the cable section should suit the load. It is recommended that the power cable outside the power room be buried directly under the ground or by means of cable pipe. Power cable should be wired separately from signal line.

The AC mains voltage shall be within the range of the voltage input range of rectifiers.

The DC power system has a circuit breaker that can cut the AC mains power to it.

2.1.3 Site Survey

The power room must be surveyed prior to installation, which should be focused on:

1. Checking the wiring device, including cable chute, wiring rack, floor, wiring holes.
2. Checking the environmental conditions, including temperature, humidity, dust.
3. Checking the conditions for implementing the installation, including power supply and lighting.

2.1.4 Tools & Material

1. Tools required for power equipment installation include electric drill, wire cutter, wire presser, various wrenches, screwdriver, electrician knife, and steel saw. The tools must be insulated and antistatic handled before they are used.
2. Power cables for electrical connection include AC cables, DC load cables, battery cables, earth cables, earth bar and lighting connection cables. Their design specifications should be in accordance with relevant specifications in the electrical industry and the materials should be purchased according to the design material list.

AC cables: this system uses 3-phase or single-phase AC power. Copper-core flame-retardant PVC insulated cable and PVC sleeve soft cable, such as NH-BVR, are recommended for the AC cables, whose sectional area should suit the load. When the wiring distance is less than 30 meters, take 2.5A/mm2 of economical current density to calculate the sectional area of the AC cables.

The sectional area of the DC load cables and battery cables should be calculated using the following formula:

A= Σ I×L/K △ U

Page 24 of the Emerson 48330 user manual — 2.1.5 Unpacking
Page 24 · click to enlarge
Page 24

14 Chapter 2 Installation

In this formula: A is the sectional area of the lead (mm2), ΣI is the total current (A)

flowing through the lead, L is the length (m) of the lead loop, △U is the permitted

voltage drop on the lead, while K is the conductivity. Kcopper=57. For safety, the voltage drop on the cables connecting battery and load cannot exceed 3.2V.

The sectional area of the lightning protection earth cable should not be less than 6mm2, and that of the DC operation earth cable, usually between 35-50mm2, is determined by user. Take the greatest sectional area among the above 3 earth cables as that of the cable connecting the user earth bar.

3. Purchase materials according to the materials list and inspect the materials, for example, check the heat durability, moisture resistance, flame resistance, and voltage resistance of the cable.
4. The auxiliary materials for power supply installation include expansive bolts, binding strips, and insulating tape.

2.1.5 Unpacking

To ensure smooth installation, the power equipment must be carefully inspected when it is unpacked.

The equipment unpacking and inspection are allowed only after it arrives the installation site. The inspection is co-accomplished by the user representative and representative from Emerson Network Power Co., Ltd.

When inspecting the equipment, first open the packing case with packing list put in it, take out the packing list, and conduct inspection against the packing label, including the customer name, customer address, machine No., total amount, case No., contract No., etc.

Unpacking and inspection: after opening the packing case, check the goods one by one according to the goods list on the packing label. The checking should include:

1. The number and serial number marked on the packing cases according to the actual number of the packing cases.
2. The correctness of the equipment packing according to the packing list.
3. The number and model of the accessories according to the accessory list.
4. The completeness of the equipment set according to the system configuration.
5. The condition of the goods through visual inspection. For example, check if the cabinet is damaged, if the cabinet has regained moisture; shake gently the rectifiers and monitoring module to see if the parts and connections have been loosened during delivery.
Page 25 of the Emerson 48330 user manual — Installation on the floor
Page 25 · click to enlarge
Page 25

Chapter 2 Installation 15

2.2 Installation Procedures

2.2.1 Cabinet Installation

Installation on the floor

1. mark the position where the power system is to be installed.

Determine the installation position of the power supply cabinet in the power room according to the installation chart. Based on the mechanical specifications (see Fig. 2-1) of the installation holes of the power supply cabinet, determine the accurate position of the center points of the installation holes on the floor, and mark them with a pencil or oil pen.

(Applicable to the cabinet with 600mm depth)

(Applicable to the cabinet with 600mm depth)

Figure 2-1 Installation dimensions of the cabinet base

2. drill reserve holes.

The expansive pipes delivered with the power system are M10%55mm, therefore,

use electric drill with drill bit Φ12 and depth 70mm to drill holes at the center points of the installation holes marked on the ground. To avoid being off-center, be careful

Page 26 of the Emerson 48330 user manual — 2.2 Installation Procedures
Page 26 · click to enlarge
Page 26

16 Chapter 2 Installation

not to shake the drill, and try to keep as vertical as possible to the ground, as shown in Figure 2-2.

3. install expansive pipes.

Clean the dust, and insert the expansive pipe into the reserve hole, knock it down gently using a hammer until the top of the expansive pipe is level with the ground, as shown in Figure 2-2.

Emerson 48330 — 2.2 Installation Procedures diagram (page 26)
Fig. 10 · 2.2 Installation Procedures
Emerson 48330 — 2.2 Installation Procedures diagram (page 26)
Fig. 11 · 2.2 Installation Procedures
3. Knock it into place 1) Drill vertically 2) Clean the dust 4) Tighten the bolt

Figure 2-2 Installing expansive pipe

4. place cabinet in position

Move the cabinet to the installation position aligning the installation holes of the cabinet to the expansive pipe on the ground.

5. fix the cabinet

After the cabinet is in position, make some horizontal and vertical adjustments. Insert some iron pieces under the lower edge and corner of the cabinet to adjust the vertical obliquity of the cabinet within 5 degrees. Finally, screw down the tap bolt with plain washer and spring washer into the expansive pipe, and tighten it with wrench. The cabinet fixation is illustrated in Figure 2-3.

Emerson 48330 — 2.2 Installation Procedures diagram (page 26)
Fig. 12 · 2.2 Installation Procedures

Figure 2-3 Fixing cabinet with Tap

Show 8 more labels / short text on this page
Power cabinet · Expansive pipe · Tap bolt · Plain washer · Spring washer · Cabinet base · Ground · Expansive pipe
Page 27 of the Emerson 48330 user manual — Connection method
Page 27 · click to enlarge
Page 27

Chapter 2 Installation 17

2.3 External Electrical Connection Interface

2.3.1 Connection Of Input Cables

The AC input terminals, SPD, rectifier AC input switch, PE bus and PE terminals are illustrated in Figure 1-6. SPD is just adjacent to the AC input terminals and has been connected in before delivery. PE bus is at the top of the MFU and is connected to the DC Power Cabinet through screws. PE bus is connected PE terminal through a cable.

Connection requirements

The AC mains is connected to the AC input terminals directly. There are 6 AC input modes as shown in Table 2-2:

Table 2-2 AC input modes

Item Function unit Amount

1P+N /220V AC input

Terminals only - for individual rectifier AC feeds

2P MCB only - for individual rectifier AC feeds

Connection method

Strip the insulation layer of one end of the AC input cable, and then mounted the cable end with an H terminal.

The cable mounted with an H terminal is shown in Figure 2-4.

Figure 2-4 Cable mounted with H terminal

After attaching the H terminal to the AC input cable, connect the AC input cable to the AC input terminals as shown in Figure 2-5:

Show 6 more labels / short text on this page
3P+N/380V AC input · L1+L2/220V AC input · AC distribution · 3P/220V AC input · H Terminal · AC Input Cable
Page 28 of the Emerson 48330 user manual — L1 L2 L3 N
Page 28 · click to enlarge
Page 28

18 Chapter 2 Installation

Emerson 48330 — Different cable connection modes diagram (page 28)
Fig. 13 · Different cable connection modes
Emerson 48330 — Different cable connection modes diagram (page 28)
Fig. 14 · Different cable connection modes
Emerson 48330 — Different cable connection modes diagram (page 28)
Fig. 15 · Different cable connection modes

Figure 2-5 Connection of input terminals

The AC input cable is fed to the system through the top cover of the cabinet, as shown in Figure 2-6:

Emerson 48330 — Different cable connection modes diagram (page 28)
Fig. 16 · Different cable connection modes
Emerson 48330 — Different cable connection modes diagram (page 28)
Fig. 17 · Different cable connection modes

Cable bracket Top cover

Figure 2-6 Top cover

There is a cable bracket on the top cover. The input cables are bound to the cable bracket with a cable tie.

Different cable connection modes

There are 4 AC input terminals. For 3-phase AC power input, just connect the AC input cables as shown in Figure 2-7:

Emerson 48330 — Different cable connection modes diagram (page 28)
Fig. 18 · Different cable connection modes

L1 L2 L3 N

Figure 2-7 Connection of 3-phase AC power input

AC input terminals · AC input cable · AC input terminals

Page 29 of the Emerson 48330 user manual — Note
Page 29 · click to enlarge
Page 29

Chapter 2 Installation 19

For single-phase AC power input, connect the AC input cables as in Figure 2-8:

N L

Figure 2-8 Connection of single-phase AC power input

If the AC input is single phase, the second and fourth terminals are not connected.

For dual-phase AC power input, connect the AC input cables as in Figure 2-9:

Figure 2-9 Connection of dual-phase AC power input

If the AC input is dual-phase, the second and fourth terminals are not connected.

The yellow, green, red, and light blue AC cables correspond respectively to the AC phase L1, L2, L3 and neutral lines. If the cables are the same color, they should be identified with labels.

The AC cables should be laid separately from the DC cables.

No splice, damage, or scratch on the cables is permitted.

The rectifier AC input cables have already been connected in factory.

Note

1.To insure AC input cable has enough bearing current capability, the section area of the AC input cable for 3-phase AC power input should not be less than 10mm2; and for single-phase AC power input and dual-phase AC power, it should not be less than 25mm2. The section area of input earth line should not be less than 35mm2.

2. The external AC input MCB of cabinet must be sure to disconnect all the AC input lines (including live lines, zero line), but input earth line can not be disconnected by any breaking device. It is recommended that the rated current of the AC input MCB is not less than 125A.

AC Input Terminals · AC Input Terminals

Page 30 of the Emerson 48330 user manual — 2.3.2 Connection Of Load Cables
Page 30 · click to enlarge
Page 30

20 Chapter 2 Installation

2.3.2 Connection Of Load Cables

Loads are connected to the MCB with suitable capacity to avoid their failure to function in the case of overload. The capacity of the MCBs is recommended to be about 1.5 times of the peak value of the load capacity. The load circuit breakers are shown in Figure 1-7. The circuit breakers can be ABB or CBI circuit breakers.

We take the CBI circuit breakers of 13mm for example to illustrate the load cable connection, as shown in the Figure 2-10.

Emerson 48330 — 2.3.2 Connection Of Load Cables diagram (page 30)
Fig. 19 · 2.3.2 Connection Of Load Cables

connected with high-priority load busbar

connected with low-priority load busbar

Emerson 48330 — 2.3.2 Connection Of Load Cables diagram (page 30)
Fig. 20 · 2.3.2 Connection Of Load Cables

High-priority load busbar Battery –48V busbar

Figure 2-10 Connection of load cables

Explanation: the load MCBs and battery MCBs can be configured flexible according to the actual requirements. Their setting range is shown in the following table.

Table 2-3 Configuration number of load MCBs and battery MCBs

Emerson 48330 — 2.3.2 Connection Of Load Cables diagram (page 30)
Fig. 21 · 2.3.2 Connection Of Load Cables

Total number of the load should not exceed 20 with 18mm-width MCB or not exceed 28 with 13mm-width MCB.

Battery -48V busbar 0~5 High-priority load busbar 0~19 Low-priority load busbar 0~28

Cable connection to MCB: strip the power cable end, crimp-connect the copper core to an H terminal, See Figure 2-4 for the cable mounted with a H terminal. After attaching the H terminal to the cable, insert the cable into the wiring hole of the MCB, then tighten the screw to fix the copper core, as shown in Figure 2-11:

Emerson 48330 — 2.3.2 Connection Of Load Cables diagram (page 30)
Fig. 22 · 2.3.2 Connection Of Load Cables

Figure 2-11 Cable connection to MCB

Low-priority load busbar

Page 31 of the Emerson 48330 user manual — J10
Page 31 · click to enlarge
Page 31

Chapter 2 Installation 21

Note

1. The cable should not be spliced. The load cable, signal cable and AC cables should be wired separately as possible to avoid them affecting each other.
2. If the power supply system is in operation, switch off the DC output MCB before connecting the cables.
3. The rated current of the output cable should be bigger than that of the corresponding MCB connected with it.

DC output branch should match the load capacity. It is highly recommended to connect priority load to BLVD branch, and normal load to LLVD branch.

2.3.3 Connection Of Communication Cables

There is a connector board in the rectifier shelf. The board is shown in Figure 2-12:

Emerson 48330 — 2.3.3 Connection Of Communication Cables diagram (page 31)
Fig. 23 · 2.3.3 Connection Of Communication Cables

J10

J11

Emerson 48330 — J10 diagram (page 31)
Fig. 24

Figure 2-12 Connector board in rectifier shelf

There is an Ethernet port and a DB9 RS232 port on the front panel. For the connection of communication cables, first connect the Ethernet port to the transmission equipment, and then connect the DB9 RS232 port to the Main Computer.

Ethernet Port

Page 32 of the Emerson 48330 user manual — 2.3.4 Layout Of Connector Board S6415X2
Page 32 · click to enlarge
Page 32

22 Chapter 2 Installation

2.3.4 Layout Of Connector Board S6415X2

Emerson 48330 — 2.3.4 Layout Of Connector Board S6415X2 diagram (page 32)
Fig. 25 · 2.3.4 Layout Of Connector Board S6415X2

Figure 2-13 Layout of connector board S6415X2

Page 33 of the Emerson 48330 user manual — J13
Page 33 · click to enlarge
Page 33

Chapter 2 Installation 23

2.3.5 Interface Definition Of Connector Board S6415X2

Table 2-4 Interface definition of connector board S6415X2

Connector Pin Signal name Mark number Logic relation

1 Relay output 1 normal close DO1_NC 2 Relay output 2 normal close DO2_NC 3 Relay output 1 common DO1_COM 4 Relay output 2 common DO2_COM 5 Relay output 1 normal open DO1_NO

J3

6 Relay output 2 normal open DO2_NO 1 Relay output 3 normal close DO3_NC 2 Relay output 4 normal close DO4_NC 3 Relay output 3 common DO3_COM 4 Relay output 4 common DO4_COM 5 Relay output 3 normal open DO3_NO

J4

6 Relay output 4 normal open DO4_NO 1 Relay output 5 normal close DO5_NC 2 Relay output 6 normal close DO6_NC 3 Relay output 5 common DO5_COM 4 Relay output 6 common DO6_COM 5 Relay output 5 normal open DO5_NO

J5

6 Relay output 6 normal open DO6_NO 1 Relay output 7 normal close DO7_NC 2 Relay output 8 normal close DO8_NC 3 Relay output 7 common DO7_COM 4 Relay output 8 common DO8_COM 5 Relay output 7 normal open DO7_NO

J6

6 Relay output 8 normal open DO8_NO 1 Digital circuits power +5V 2 Temperature signal 1 input TEMP1 4~20mA J10

3 Analog ground GND 1 Digital circuits power +5V 2 Temperature signal 2 input TEMP2 4~20mA J11

3 Analog ground GND 1 Data Carrier Detect DCD232 2 Receive Data RXD232 3 Transmit Data TXD232 4 Data Terminal Ready DTR232 5 Data Communication ground DGND 6 Empty 7 Request To Send RTS232

J12, J18

8,9 Empty 1 Ethernet TX+ NETTX+ 2 Ethernet TX- NETTX- 3 Ethernet TR+ NETTR+ 4 Empty 5 Empty 6 Ethernet TR- NETTR-

J13

7~12 Empty

Page 34 of the Emerson 48330 user manual — Note
Page 34 · click to enlarge
Page 34

24 Chapter 2 Installation

Connector Pin Signal name Mark number Logic relation

1 RS485 communication+ E485+ 2 RS485 communication- E485- J14

3 Protection ground PGNG 1 48V+ POWER+ J19 2 48V- POWER-

2.3.6 Connection Of Temperature Sensor Cables

There are two 3-pin terminals on the connector board in rectifier shelf. These two terminals are J11 and J10 respectively. They are used to connect the temperature sensors. The locations of J11 and J10 are as shown in Figure 2-12.

The user can connect the temperature sensor cables to J11 and J10.

2.3.7 Connection With MODEM

Take e-TEK TD-5648DC MODEM for example to illustrate the connection.

Figure 2-14 Input/output interfaces of TD-5648DC MODEM

Conneting modem with M500D control unit

MODEM connects with M500D monitoring module through connector board S6415X2:

1. Connect telephone line to the “LINE” port of MODEM.
2. Connect the 48V “POWER” terminal of MODEM with the J19 socket of connector board S6415X2.
3. Connect “RS-232” (DB25 female) communication port of MODEM with the J12 or J18 terminal (DB9 male) of connector board S6415X2 using a communication cable.

Note

When the cabinet has a front door, before connecting the RS232 terminal, pull out the S6415X2 board first, pass the RS232 terminal through the opening on the right side of the rectifier subrack and connect it with the J18 terminal on the S6415X2 board, then insert the S6415X2 board.

Power

Page 35 of the Emerson 48330 user manual — 2.4.1 Battery Installation
Page 35 · click to enlarge
Page 35

Chapter 2 Installation 25

2.3.8 Connection With Dry Contacts

The M500D monitoring module provides 8 sets of alarm dry contacts through the J3-J6 sockets on the connector board S6415X2. Each set has a normally open contact and a normally closed contact. Once the corresponding alarm event occurs, the dry contact will act to report alarms under the control of M500D monitoring module. Through the dry contact networking, the system can realize the level isolation transmission of fault signals.

When delivery, each set of dry contacts is corresponding to one default alarm type, and users can reset it as other alarm types.

Connecting method

After peeling the signal cable terminal, insert it into the dry contact terminal, then tighten the hold-down bolt to compress the signal cable.

2.4 Battery Installation And Cabling

2.4.1 Battery Installation

The DC Power System with standard configuration has 4 battery strings. The DC Power System with non-standard configuration can connect to up to 5 battery strings. In the system cabinet, there are 5 levels and each battery string is installed in one level. One battery string has four +12V battery blocks.

Procedures to install battery:

1. Install the batteries in the cabinet from low level to high level;
2. Place the battery on the level and push it inward until the battery is blocked;
3. Connect the positive and negative battery cable to the battery string.

The cabinet with four battery strings installed is shown in Figure 2-15:

Page 36 of the Emerson 48330 user manual — Standard configuration
Page 36 · click to enlarge
Page 36

26 Chapter 2 Installation

Battery(4 in a string)

Figure 2-15 Cabinet with four battery strings installed

Note

To satisfy the safety requirement of the whole equipment, the fire-retardant class of the battery materials should not be lower than V-2.

Insure that the charge/discharge current of single battery group is not bigger than 100A, and the total charge/discharge current of the all battery groups are not bigger than 200A.

2.4.2 Battery Cable Connection

The battery connection for the cabinet with standard configuration is different from that of the cabinet with non-standard configuration.

Standard configuration

The DC Power System with standard configuration has no BCU. The system has four battery strings. The negative battery cable is of blue color and the positive one

is of black color. There are two connection methods, one is for the cabinet of 600 %

400 % 700(mm), and another is for the cabinets of 600 % 400 % 2000(mm) and

600 % 600 % 2000(mm).

1. Batter Connection for Cabinet of 600 % 400 % 700(mm)

The four left-most circuit breakers in the MFU connect to the negative battery cables (blue) respectively as shown in Figure 2-16. Another end of the negative

Battery Connection Unit(BCU) · Battery Shelf

Page 37 of the Emerson 48330 user manual — 2.4.2 Battery Cable Connection
Page 37 · click to enlarge
Page 37

Chapter 2 Installation 27

battery cable is connected to the negative terminals of the battery string in each level as shown in Figure 2-16:

4 Battery Circuit Breakers

Figure 2-16 Connection of battery cables.

2. Batter Connection for Cabinets of 600 % 400 % 2000(mm) and 600 % 600 % 2000(mm)

The connection is show in Figure 2-17:

Emerson 48330 — 2.4.2 Battery Cable Connection diagram (page 37)
Fig. 26 · 2.4.2 Battery Cable Connection
Emerson 48330 — 2.4.2 Battery Cable Connection diagram (page 37)
Fig. 27 · 2.4.2 Battery Cable Connection

Figure 2-17 Positive and negative battery cables in each level

One end of positive battery cable is connected to the neutral bus of the DC power cabinet. Another end of the positive battery cable is connected to the positive terminal of the battery string in each level as shown in Figure 2-17.

Negative Battery Cables · Negative battery cable · Positive battery cable

Page 38 of the Emerson 48330 user manual — Note
Page 38 · click to enlarge
Page 38

28 Chapter 2 Installation

Note

The actual number of battery circuit breakers in MFU may be 0~5 according to the user’s need.

Non-standard configuration

The DC power system with non-standard configuration has a BCU. The connection of positive cables is the same with that of the system with standard configuration. The only difference is that there are five positive battery cables because the system has five battery strings. One end of positive battery cable is connected to the neutral bus of the DC power cabinet. Another end of the positive battery cable is connected to the positive terminal of the battery string in each level as shown in Figure 2-17.

One end of negative battery cable is connected to the negative terminal of the battery string in each level as shown in Figure 2-17. Another end is connected to the BCU as shown in Figure 2-18. The connection has already been done in factory.

Emerson 48330 — Non-standard configuration diagram (page 38)
Fig. 28 · Non-standard configuration

Figure 2-18 Negative battery cables connection in BCU

Note

1. Before connecting the battery cables, the corresponding battery fuse or the battery switch must be disconnected.
2. Be careful not to reverse connect the battery, otherwise, the battery and the power supply system will be damaged!

Since the battery voltage decreases in discharge, hence the sectional area of the cable connecting the battery and the MFU or BCU should be relatively big to keep the voltage drop on the cable within 0.5V.

Negative Battery Cables(Blue)

Page 39 of the Emerson 48330 user manual — DC/Parallel connections
Page 39 · click to enlarge
Page 39

Chapter 2 Installation 29

2.5 Parallel Connection Of Cabinets

In order to prolong the backup time of battery, the battery capacity should be increased. Another cabinet can be connected in parallel with the DC power system cabinet. The expanded cabinet has no rectifier shelf and Multi-Function Unit. It is only installed with battery strings and a BCU. So, it is actually the battery cabinet. BCU in Extension Unit connects to Main Unit through cables. The parallel connection of the DC power system cabinet with the battery cabinet is shown in Figure 2-19:

BCU

Figure 2-19 Parallel connection of DC power system cabinet with battery cabinet

DC/Parallel connections

The DC cables are connected to the output of the rectifier shelf in the MFU.

Up to two Battery Connection Units (BCUs) can be connected in the DC Power System – up to one BCU in the main cabinet and up to one BCU in an extension battery cabinet.

SCU can display the alarm signals from these two BCUs.

The user can connect the MFU to an additional extension MFU (only for additional load circuit breakers) through suitably rated cables.

Main cabinet · Extension cabinet · Batteries

Page 40 of the Emerson 48330 user manual — Chapter 3 Startup
Page 40 · click to enlarge
Page 40

30 Chapter 3 Startup

Chapter 3 Startup

3.1 Checking Before Startup

Check the DC Power System according to Table 3-1 before startup.

Table 3-1 System checklist before startup

Item Action Result Comments (fill in

1 Check all the circuit breakers of the shelf and BCU They should be switched off.

2 Check the mains supply fuses/circuit breakers. They should be removed/switched off.

3 Check with an ohmmeter between the positive and negative terminals of battery.

They must be no short circuit (>50ohms)

4 Check with an ohmmeter between the battery terminals and shelf chassis.

They must be no short circuit (>50ohms)

5 Check the battery block voltage and total battery voltage.

The voltages shall correspond to the values given by battery manufacturer.

6 Check the mains phase voltage. The voltage shall be within the rectifier input voltage range (85Vac~290Vac).

7 Check the connection of cables. The cables shall be connected to their correct terminals firmly.

“Ok” or not)

Page 41 of the Emerson 48330 user manual — 3.3 Parameters Configuration
Page 41 · click to enlarge
Page 41

Chapter 3 Startup 31

3.2 Startup Process

Item Action Result Comments (Fill

in “OK” or not) The LEDs on the rectifiers and the controller will emit light.

The rectifier fans will start.

The LVD contactors will operate. 1 Connect/switch on the mains supply fuses/circuit breakers of the DC shelf.

The green LEDs of the rectifiers and the controller will flash for about 10 s. and then emit steady light.

The voltage should be close to what has been set in the controller. If temperature compensated charging is activated, the difference may be ±3 V from the set value.

2 Check the DC voltage on the test outlet marked U in the supervision unit.

If temperature compensated charging is activated, warn the sensor on the battery with your hand and observe the system voltage.

The voltage should start to drop.

The battery voltage will increase and reach the system voltage. (Might take hours, depending on the charging state of the battery.)

4 Switch on the battery circuit breakers.

5 Switch on the circuit breakers in MFU. The loads will get DC supply.

6 Check all the LEDs of the shelf. Only the green LEDs are On should emit light. No LED shall flash.

3.3 Parameters Configuration

After start up the DC Power System, following parameters need to be configured:

Password, AC parameters, DC parameters, rectifier parameters, battery parameters, time and communication parameters.

Refer to Chapter 5 on how to configure the parameters.

Page 42 of the Emerson 48330 user manual — Auto /BC
Page 42 · click to enlarge
Page 42

32 Chapter 4 Testing

Chapter 4 Testing

4.1 Testing MFU

Measure the L-N voltage at the input terminals with a multi-meter to check if it is normal.

4.2 Testing Rectifier

1. Turn on one rectifier input MCB in the MFU to feed AC supply to the corresponding rectifier, the rectifier should operate normally;
2. Turn off this MCB, and turn on the other rectifier input MCBs one by one to check if all the other rectifiers operate normally.

If all of the rectifiers can operate normally, switch them on. In case of rectifier malfunction, take the rectifier out and inspect it.

4.3 Testing SCU

When the rectifiers are operating normally, switch on the SCU, the SCU should start and display the start screen. If the system self-test is normal, seconds later, SCU displays Initial Screen with System Information:

53.5V 300 A

SystemAlarm

Auto /BC

There are default system parameter settings in the SCU, including the AC voltage alarm points, DC voltage alarm points, battery management parameters, which are available on the parameter card delivered with the system. If the battery capacity or charging parameters set by user are different from those on the parameter card, or if user has different BLVD management requirements, please reset the system parameters according to the actual situation, and record the new settings on the parameter card.

2004-09-16

Page 43 of the Emerson 48330 user manual — 4.6 Load Breaker Test
Page 43 · click to enlarge
Page 43

Chapter 4 Testing 33

4.4 Battery Breaker Test

1. Before turning on the battery circuit breaker, confirm with a multi-meter that the battery is not reverse-connected.
2. When connecting the battery, be careful not to short the two battery terminals.
3. When connecting two batteries, be careful to avoid battery mutual charging due to unequal terminal voltages of the two batteries.

4.5 BCU Test

The BCU can connect to a single battery via suitably sized cables from the Distribution Unit.

The BCU can connect to up to five battery strings via suitably sized cables.

The user can route the battery cables via the left hand side and via the right hand side of the BCU. A maximum of 7 cables can be routed via the left hand side of the BCU and a maximum of 5 cables via the right hand side of the BCU.

The user can mount the BCU 15mm or more above a Front terminal battery. Care shall be taken to connect the battery to the BCU via cables in this orientation.

The user can safely connect battery cables on a live system with only front access. BCU can be partially slid out in order for this to be achieved.

The user can safely install or replace a battery circuit breaker on a live system with only front access. BCU can be partially slid out in order for this to be achieved.

4.6 Load Breaker Test

Before connecting load to the system, check with a multi-meter if the connection polarity of the load and the power system is correct and the voltage is normal.

1. Close the load MCB, DC power should be fed to the load ;
2. Adjust the system parameters through the SCU, and make sure that the information viewing and output control functions are normal.
Page 44 of the Emerson 48330 user manual — 5.1 Operation Panel
Page 44 · click to enlarge
Page 44

5.1 Operation Panel

SCU has a LCD with backlight, keys, LEDs and a latch, as shown in Figure 5-1:

Emerson 48330 — 5.1 Operation Panel diagram (page 44)
Fig. 29 · 5.1 Operation Panel

Figure 5-1 SCU Front Panel

Functions of LED indicators are illustrated in Table 5-1

Table 5-1 Functions of LED indicators

Emerson 48330 — 5.1 Operation Panel diagram (page 44)
Fig. 30 · 5.1 Operation Panel

Critical alarm (Red) Off On There are major or critical alarms

SCU controller uses a 128×64 dot-matrix LCD unit. It has 6 functional keys. Its interface is easy-to-use and supports multi-language display. The panel of the controller is easy-to-remove. The functions of these 6 keys are shown in Table 5-2:

Table 5-2 Functions of SCU keys

Emerson 48330 — 5.1 Operation Panel diagram (page 44)
Fig. 31 · 5.1 Operation Panel

Pressing ESC and ENT simultaneously can reset the monitoring module

ENT Enter the main menu or confirm the menu operation

To change a character string whose digits needs setting separately, use

Change values at a value setting interface. At the first page of system information, use these two keys to change LCD contrast.

““ and ““ to move the curso left or

right, or “” and “” to set each digit.

Page 45 of the Emerson 48330 user manual — 英文
Page 45 · click to enlarge
Page 45

5.2 Operation Procedures

After the system is powered on for the first time, you should set the system type according to the actual configuration. The monitoring module will restart after the system type is changed. In that case, you should re-configure those parameters whose default values are inconsistent with the actual situation. Only after that can the monitoring module operate normally.

After configuring the system parameters, you can carry out various operations directly without resetting the parameter values. As for those important parameters related to battery management, such as BLVD, you should be fully aware of their influence upon the system before you change their values.

Note

For the exact meanings of the abbreviations used in LCD displayer, see Appendix E Glossary.

1. The LCD will prompt you to select a language once the monitoring module is powered on.

英文

You can use “”, “”, “” or “” to select the language you want, and press “ENT” to confirm.

2. The monitoring module will prompt you to wait, and start initialization.

Waiting

3. The first system information page appears
2004-09-16 53.5V 125 A SystemNo alarm Auto /BC

The system information is shown in many pages. You can repeatedly press “” to view other system information pages in a cycle.

English

Page 46 of the Emerson 48330 user manual — 5.3.1 First Page Of System Information
Page 46 · click to enlarge
Page 46
4. At any system information page, press “ENT” to enter the “MAIN MENU” page, which contains 3 sub-menus: “Status”, “Maintenance” and “Settings”.

Main Menu Status Maintenance Settings

You can press “” or “” repeatedly to select a sub-menu, and press “ENT” to enter the sub-menu. Press “ESC” to return to the menu of higher level.

1. Status

Including rectifier information, active alarm information and alarm history information.

2. Maintenance

The maintenance operation can be conducted only when the battery management mode is set to “Manual”. The maintenance includes battery FC, BC and test, load power off/on, battery power off/on and rectifier voltage trimming, current limit, switch control and resetting.

3. Settings

Including the setting of alarm parameter, battery parameter, AC/DC parameter, rectifier parameter and system parameter.

5.3 Querying System Status

5.3.1 First Page Of System Information

1. At the main menu page, press “ESC” to return to the first system information page.
2. If no operation is conducted on the monitoring module keypad for 8 minutes, the LCD will return to the first system information page and shut down the backlight to protect the screen. Pressing any key will turn on the back light.

The first system information page contains the major system operation information, including date/time, busbar voltage, total load current, system operation state (normal or alarm), battery management mode (AUTO or MANUAL) and battery state.

Among which, the battery state include FC, temperature compensation, BC, Cyclic Boost, test, short test and scheduled test. The current time are displayed in two pages shifting at the interval of 2s. One page shows year, month and date, the

Page 47 of the Emerson 48330 user manual — Note
Page 47 · click to enlarge
Page 47

other shows hour, minute and second. The year is displayed with 4 digits; other time units are in 2 digits.

10:09:16 53.5V 125 A System: No alarm Auto /BC

2004-09-16 53.5V 125 A SystemNo alarm Auto /BC

Note

1. At this page, you may use “ ” and “ " to adjust the LCD contrast (7-level).
2. If there has been no keypad operation for 8 minutes, the monitoring module will return to the first system information page. The time of that return will be recorded automatically, and can be queried through the host.

5.3.2 Other System Information Screen

The system information is shown in many pages. The default page of the monitoring module after the system power on is the system information first page. You can press “” or “” to scroll up or down to view more operation information, as shown in the following page:

Battery information page

Batt1295 A Actual: 99.1% Batt2: 0 A Remain: 0%
1. Battery 1, battery 2

They represent respectively the current of the battery that battery shunt 1 and shunt 2 is connected to. If the “Shunt Coeff” of a certain battery group is set to “No”, this situation will be reflected at the battery information page by “Not connected”, and no actual capacity will be displayed.

Note

There is only one current shunt in the system, that is “shunt 1”.

Page 48 of the Emerson 48330 user manual — BC prompt and temperature information page
Page 48 · click to enlarge
Page 48
2. Actual battery capacity

The monitoring module can approximately calculate the remaining battery capacity in real time. Through configuration at the host, the remaining battery capacity can be displayed in the mode of percentage, remaining Ah or remaining time, etc. The default is the percentage.

During the normal BC/FC management, the monitoring module regards the rated capacity as the capacity that each battery group can reach. When the battery discharges, the monitoring module will calculate the battery remaining capacity according to the discharge current, discharge time and the preset “battery discharge curve”. When the battery is being charged, the monitoring module will calculate the real-time battery capacity according to the detected charge current, charge time and preset “battery charge efficiency”. If the calculated battery remaining capacity is higher than the rated capacity, the monitoring module will automatically change the calculated battery remaining capacity to the rated capacity.

AC information page

There is no AC data acquisition board in ACTURA Flex 48330 Power System,so

the configuration of “AC Input” can only be set to “None”.

BC prompt and temperature information page

System Power:

23% Cyc BC After:

Bat. Temp:

25°C Amb. Temp5°C

If the monitoring module bans BC and no temperature sensor is configured, this page will not be displayed.

The first line of the information page displays the BC prompts, which will be different with different systems, including:

1. Prompt the time of next Cyclic Boost according to the battery state
2. If BC is going on, the “Charging” will be prompted
3. If BC is disabled, this row will be empty

55h

Page 49 of the Emerson 48330 user manual — 5.4 Querying Rectifier Status
Page 49 · click to enlarge
Page 49

The 2nd and 3rd rows of the page are the temperature information detected by the temperature sensor. The display will vary with different parameter settings (see 4.7 for parameter setting). If the temperature sensor is not connected or is faulty, system will prompt invalid. Meanwhile, the 4th row will display “Check Temp Sensor”.

5.4 Querying Rectifier Status

The rectifier information includes the rectifier serial No., voltage, current, current limit, mains situation, rectifier power limit and temperature power limit.

1. At any page of the system information, press “ENT” to enter the main menu.
2. Use “ ” or “ ” keys to select the “Status” sub-menu in the main menu, and press “ENT” to confirm.

Active Alarm Alarm History

3. Use “ ” or “ ” to select the “Rect Info” submenu, as shown in the above figure. Press “ENT” to confirm.
Rect 101234567 54.1V 30.2A AC On DC on
AC Volt220V
Rect 101234567 CurrLimit: 34% AC Derated: Y Temp Derated: N

The information of every rectifier is displayed in two pages. The information in the first page includes: rectifier serial No., output voltage and current, AC/DC on/off state and AC input voltage. The information in the second page includes: rectifier serial No., current limit, the states of “AC Derated” and “Temp Derated”. Press “” to scroll to the next page, or “” to return to the last.

4. Press “ ” or “ ” to query other rectifier’s information.

At most 48 pieces of rectifier’s information can be displayed. If the rectifier does not exist, there will be no information. If the rectifier communication is interrupted, the information will be displayed in high light.

Status Rectifiers

Page 50 of the Emerson 48330 user manual — 5.5.1 Querying Active Alarm
Page 50 · click to enlarge
Page 50
5. At any rectifier information page, press “ESC” repeatedly and you can return to the higher-level menus.

5.5 Querying Alarms And Setting Alarm Plans

The monitoring module can locate and record the system fault according to the collected data, as well as raise audible/visual alarms and output through dry contact according to the preset alarm level. Meanwhile, it reports the alarms to the host.

You can query historical alarms and active alarms through the LCD of the monitoring module.

5.5.1 Querying Active Alarm

When a new alarm is raised, and there is no operation on monitoring module keypad within 2 minutes, the LCD of the monitoring module will prompt automatically the active alarm.

If there are multiple alarms in the current system, you can query alarms through the following steps:

1. At any system information page, press “ENT” to enter the main menu
2. Use “ ” or “ ” to select the “Status” submenu in the main menu and press “ENT” to confirm.

Active Alarm Alarm History

3. Press “ ” or “ ” to select the “Active Alarm”, as shown in the above figure, and press “ENT” to confirm.
1. If there is no active alarm, “Active Alarm: None” will be displayed

Status Rectifiers · Active Alarm! None

Page 51 of the Emerson 48330 user manual — 5.5.2 Query Alarm History
Page 51 · click to enlarge
Page 51
2. If there is any alarm, the display will be like the following:

1 Major Alarm AC! Ph-A Failure 040412 12:30:23

The information in the active alarm information pages includes: alarm serial No., alarm level, alarm name and time (year, month, day, hour, minute and second). The alarm raising time determines the sequence it is displayed, with the latest alarm displayed first. Use “” or “” to view all active alarms.

While querying rectifier alarms, press “”, and the rectifier ID will be displayed, and the “Run” indicator of the corresponding rectifier will blink.

Rect ID 02030405

In the case of battery test alarm or maintenance time alarm, press “” to display the prompt information.

In the prompt page, press “ENT” to confirm the alarm.

4. At any active alarm information page, press “ESC” repeatedly and you can return to the higher-level menus.

5.5.2 Query Alarm History

1. At any system information page, press “ENT” to enter the main menu
2. Press “ ” or “ ” to select the “Status” submenu, and press “ENT” to confirm.

Active Alarm! 3

Page 52 of the Emerson 48330 user manual — Chapter 3 Startup
Page 52 · click to enlarge
Page 52

Active Alarm Alarm History

3. Use “ ” or “ ” to select the “Alarm History”, as shown in the above figure and press “ENT” to confirm.

If there is no historical alarm, the prompt will be “Alarm History: None”.

The historical alarms of the monitoring module are stored in cyclic order. Up to 200 alarms will be recorded. Above that, the earliest alarm will be cleared automatically.

1Alarm SPD Fault 040411 20:08:30 040411 22:08:30

At the monitoring module, the displayed historical alarm information includes: alarm serial No., alarm name and alarm start/end time (year, month, day, hour, minute, second).

If it is a rectifier that raised the alarm, the ID of that rectifier will be displayed.

4. At any Alarm History information page, press “ESC” repeatedly to return to the higher-level menus.

Status Rectifiers · ALARM HISTORY None

Page 53 of the Emerson 48330 user manual — 5.5.3 Alarm Type Table
Page 53 · click to enlarge
Page 53

5.5.3 Alarm Type Table

Table 5-3 Alarm type table

No. Alarm Description Default alarm level

1 Input MCB Trip The system AC input MCB tripped Critical None 2 SPD Fault The SPD circuit is faulty Critical 8 Only in a system with AC sampling board

In a system with AC sampling board, you can name 2 routes; in a system without AC sampling, you can name 8 routes 4 DC/DC Failure Including DC/DC converter fault Critical None

The alarm name is user defined, not longer than 10 characters. The high/low level alarm can be set in the alarm mode.

3 Digit Input Fault

The system AC input voltage is higher than the set value of parameter “OverVolt”

5 AC Over Volt

Critical None Over-voltage alarm

The system AC input voltage is lower than the set value of parameter “LowVolt”

6 Ph-X Volt Low

Critical None Under-voltage alarm

7 Phase failure The AC input voltage of the power system is lower than 80V Critical None

In double-AC auto-switchover system: 1. All AC voltage inputs are lower than 80V. 2. Both AC inputs 1 and 2 are broken. In single AC input system or double-AC manual-switchover system, the AC voltage of all rectifiers are lower than 80V

System DC output voltage is higher than the set value of parameter “Temp Threshold: Over”

9 DC Voltage High

Critical 2 Over-voltage alarm

System DC output voltage is lower than the set value of parameter “Temp Threshold: Under”

Critical 2 Under-voltage alarm

System DC output voltage is lower than the set value of parameter “Temp Threshold: Low”

11 DC Voltage Low

Observation 2 Low-voltage alarm

Battery temperature is higher than the set value of parameter “Temp Threshold: Over Temp”

Major None Over-temperature alarm point

Battery temperature is higher than the set value of parameter “Temp Threshold: High Temp”

Observation None High temperature alarm point

13 Batt Temp High

Show 10 more labels / short text on this page
Default related · Serial · Related parameter · configuration · relay · No alarm None · 8 Power Failure · Major 1 · 10 DC Under-volt · 12 Batt Overtemp
Page 54 of the Emerson 48330 user manual — 22 BLVD
Page 54 · click to enlarge
Page 54

No. Alarm Description Default alarm level

Battery temperature is lower than the set value of parameter “Temp Threshold: Low Temp”

Observation None Low temperature alarm point

14 Batt Temp Low

15 Amb Temp High Ambient temperature is higher than the set alarm point Observation None

16 Amb Temp Low Ambient temperature is lower than the alarm point Observation None

17 No TempSensor1 Temperature sensor 1 has been set, but no sensor is actually connected Critical None

18 No TempSensor2 Temperature sensor 2 has been set, but no sensor is actually connected Critical None

Temperature sensor 1 detected unreasonable temperature Critical None

20 TempSensor2 Err Temperature sensor 2 detected unreasonable temperature Critical None

21 LLVD 1. Load disconnection 2. Manual load disconnection Critical 5 LLVD enabled

1. When battery discharges till its voltage is lower than the “BLVD Volt”, or the discharge time is longer than the “BLVD Time”, the BLVD contactor will be open automatically 2. BLVD through manual operation

22 BLVD

Critical 4 BLVD enabled

23 Load 1 Faiure Over-load, short circuit, manual disconnection or alarm circuit faulty Critical 6

24 Load 2 Faiure Over-load, short circuit, manual disconnection or alarm circuit faulty Critical 6

25 Load 3 Faiure Over-load, short circuit, manual disconnection or alarm circuit faulty Critical 6

26 Load 4 Faiure Over-load, short circuit, manual disconnection or alarm circuit faulty Critical 6

27 Load 5 Faiure Over-load, short circuit, manual disconnection or alarm circuit faulty Critical 6

28 Load 6 Faiure Over-load, short circuit, manual disconnection or alarm circuit faulty Critical 6

29 Load 7 Faiure Over-load, short circuit, manual disconnection or alarm circuit faulty Critical 6

30 Load 8 Faiure Over-load, short circuit, manual disconnection or alarm circuit faulty Critical 6

31 Load 9 Faiure Over-load, short circuit, manual disconnection or alarm circuit faulty Critical 6

32 Aux Load Fails The last route faulty Critical 6

33 Batt1 Failure Over-load, short circuit, manual disconnection or alarm circuit faulty Critical None

34 Batt2 Failure Over-load, short circuit, manual disconnection or alarm circuit faulty Critical None

35 Batt3 Failure Over-load, short circuit, manual disconnection or alarm circuit faulty Critical None

Show 6 more labels / short text on this page
Default related · Serial · Related parameter · configuration · relay · 19 TempSensor1 Err
Page 55 of the Emerson 48330 user manual — Chapter 3 Startup
Page 55 · click to enlarge
Page 55

No. Alarm Description Default alarm level

36 Batt4 Failure Over-load, short circuit, manual disconnection or alarm circuit faulty Critical None

The charge current of battery group 1 is bigger than the set value of parameter “Over”

The charge current of battery group 2 is bigger than the set value of parameter “Over”

39 Rect Vac Err All AC voltages are lower than the AC low-volt point Major 3

40 Rect Over Temp Rectifier internal temperature higher than 90°C Observation None

41 Rect Failure Rectifier over-voltage, higher than rectifier high threshold Critical 3

42 Rect Protect AC over-voltage (ƒ295V) or

under-voltage (80V) Observation 3

43 Rect Fan Fails Fan faulty Major 3

AC voltage lower than 176V, with rectifier internal higher than 85°C or temperature at inlet higher than 45°C

45 Rect Com Failure Rectifier and monitoring module communication interrupted Major 3

46 Multi Rect Fail More than 2 rectifiers raised alarms Critical None

47 Self-detect error Error is detected through hardware self-detection No alarm None

48 Manual Mode Battery management in the manual state No alarm None

49 Non-FC Status Including auto-BC, Cyclic Boost, constant current test and short test No alarm 7

50 Batt Discharge Battery being discharging No alarm None

In a system with load shunt, the detected load current plus battery current differs sharply from the rectifier output current

No alarm None Not existent in this

52 Batt Test Error Battery discharge time unexpectedly short Observation None

During the short test, the two batteries discharged more than the set value

53 Short Test Fault

The maintenance FC voltage different from the busbar voltage, or the reported data. The difference is more than 1V

55 System Maintain The pre-set system maintenance time is due Observation None

56 Alarm Block Alarms sent to the host are blocked, valid in EEM-M protocol No alarm None

Show 16 more labels / short text on this page
Default related · Serial · Related parameter · configuration · relay · 37 Batt1 Over-curr · Observation None · 38 Batt2 Over-curr · Observation None · 44 Rect PowerLimit · Observation 3 · 51 Curr Imbalance · power system series · Observation None · 54 Outvolt Fault · Observation None
Page 56 of the Emerson 48330 user manual — 5.5.6 Setting Alarm Type For Dry Contacts
Page 56 · click to enlarge
Page 56

Note

When the DC load 9 and its above (load 10, load 11 …) have circuit fault alarm, the monitoring module all display “Load 9 Failure” or “Aux Load Fails”.

5.5.4 Changing Audible/Visual Alarm And Alarm Call Back Plan

There are different audible/visual alarms and call back modes for alarms of different levels. For the products in China market, the alarming mode for major alarms and critical alarms are the same.

Table 5-4 Changing audible/visual alarm and alarm call back plan

Emerson 48330 — 5.5.4 Changing Audible/Visual Alarm And Alarm Call Back Plan diagram (page 56)
Fig. 32 · 5.5.4 Changing Audible/Visual Alarm And Alarm Call B…

Critical ON / ON Y Callback No. can be set

Major ON / ON Y Callback No. can be set

Therefore, changing the alarm level of different alarms may change their audible/visual alarm mode and call back plan too.

Pressing any key on the monitoring module can silence the alarm sound. The sound will disappear and alarm indicator will be off when all alarms are cleared.

You can configure how long an alarm sound will last, or choose to make no alarm sound. For details, see 5.7.11 Alarms Settings.

5.5.5 Changing Alarm Types Of Dry Contacts

As one of the alarm type parameter, “Related Relay” refers to the serial No. of the dry contract corresponding to the alarm type, whose value is either 1 ~ 8 or “None”. “None” means there is no corresponding dry contact. For details, see 4.7.11 Alarms Settings.

5.5.6 Setting Alarm Type For Dry Contacts

The Programmable Logic Control (PLC) is configured through the host software.

The way to configure the PLC function is:

C = A (Status) * B (Status)

C: The dry contract serial No. of the corresponding output. Range: 1 ~ 8.

A, B: The input alarm type. Status: Whether the alarm has been raised.

Page 57 of the Emerson 48330 user manual — Chapter 3 Startup
Page 57 · click to enlarge
Page 57

*: The logic relationship between the two alarms. Options: “And”/”Or”.

The optional alarm types are listed in the following table:

Table 5-5 Optional alarm types

Alarm Block Load route 1 Load route 2 Load route 3 Load route 4 Load route 5 Load route 6 Load route 7 Load route 8 Load route 9 Auxiliary load route SPD faulty AC input MCB tripped AC route 1 in operation AC route 2 in operation DC/DC faulty

Valid in the double AC inputs auto-switchover power system

Digit Input (DI) 7 DI 8 DC voltage Phase A of AC route 1 Phase B of AC route 1 Phase C of AC route 1 Phase A of AC route 2 Phase B of AC route 2 Phase C of AC route 2

Valid in the double AC inputs auto-switchover power system

Load current Valid in the system with load shunt Battery 1 current Valid in the system with battery shunt Battery 2 current Valid in the system with battery shunt Fuse of battery 1 Fuse of battery 2 Fuse of battery 3 Fuse of battery 4 Temperature detection 1 Temperature detection 2 Monitoring module in operation Used for monitoring module power off Module self test Manual mode Non-FC state of battery Battery discharge Current imbalance Battery short test Battery test alarm LLVD

Alarm type Remark

Page 58 of the Emerson 48330 user manual — 5.5.7 Set the Alarm Names Through PLC Function
Page 58 · click to enlarge
Page 58

BLVD Output voltage abnormal AC power off Multiple rectifiers alarm Time for system maintenance (replace the fan) Any rectifier comm interrupted Any rectifier AC power off Any rectifier over-temperature Any rctifier faulty Any rectifier in protection Any rectifier fan faulty Any AC derated rectifier Any temperature derated rectifier

For example: To make dry contact No.3 act when battery route 1 is broken but AC power is still on, the PLC should be configured like this:

A: battery route 1, with “status” set as “Alarm”.

B: AC power off, with “status” set as “No alarm”.

C: Dry contact No.3

*: “AND”.

5.5.7 Set the Alarm Names Through PLC Function

Connect the serial port of MC to the RS-232 port of SCU, then configure the alarm types that correspond to the dry contact outputs through MC.

An 8 (row) % 6 (column) logic matrix is used in configuring these 8 dry contacts. Every row in the matrix corresponds to one dry contact. The setting of one dry contact has 6 bytes.

Byte 0: The dry contact is disabled if byte 0 is set to 0, and enabled if byte0 is set to 1.

Bytes 1, 3 and 5 are the SN of the 3 alarms respectively. The range of SN is 0-56, see section “5.5.3 Alarm List” for details.

Bytes 2 and 4 define the logic relationship between 3 alarms. The setting of byte 2 or 4 is 0-3. If the setting is 0, the logic is “AND”; If the setting is “1”, the logic is “NOT”; If the setting is “2”, the logic is “OR”; and if the setting is “3”, the logic is “AND”.

Alarm type Remark

Page 59 of the Emerson 48330 user manual — Chapter 3 Startup
Page 59 · click to enlarge
Page 59

Table 5-6 Logic matrix used for configuring 8 dry contacts

Emerson 48330 — Chapter 3 Startup diagram (page 59)
Fig. 33 · Chapter 3 Startup

Setting 0,1 Alarm SN Logic Alarm SN Logic Alarm SN

The format of PLC setting is AlarmPLC[A][B]=C.

Where, “A” is the row No., and “B” is the column No., and “C” is the value of the matrix element. An example is shown in the following table:

Table 5-7 Example of PLC setting

Emerson 48330 — Chapter 3 Startup diagram (page 59)
Fig. 34 · Chapter 3 Startup

AlarmPLC[3][0]=1 Elemant value of Row 3 and Column 0 is 1. Use Dry Contact 3

AlarmPLC[3][1]=1 Elemant value of Row 3 and Column 1 is 1. Alarm SN of Fuse 1 Blow up

AlarmPLC[3][2]=3 Elemant value of Row 3 and Column 2 is 3. AND Logic

AlarmPLC[3][3]=2 Elemant value of Row 3 and Column 3 is 2. Alarm SN of Fuse 2 Blow up

AlarmPLC[3][4]=3 Elemant value of Row 3 and Column 4 is 3. OR Logic

AlarmPLC[3][5]=43 Elemant value of Row 3 and Column 5 is 43. Alarm SN of LLVD

For the above PLC setting: When alarms of “Fuse 1 Blow up” and “Fuse 2 Blow up” occur at the same time, or LLVD occurs, dry contact 3 will output the alarm signal.

Relationship between PLC SN and Alarm:

Table 5-8 PLC SN and Alarm

Emerson 48330 — Chapter 3 Startup diagram (page 59)
Fig. 35 · Chapter 3 Startup

0 Alarm Block Disabled for China Market, Enabled for rest of world

Page 60 of the Emerson 48330 user manual — PLC
Page 60 · click to enlarge
Page 60

PLC

SN

6 Load 6 Failure

7 Load 7 Failure

8 Load 8 Failure

9 Load 9 Failure

10 Aux Load Fails Load 10 is Auxiliary Load for China Market

11 SPD Fault Enabled when an AC Signal Acquisition Board is installed.

12 Input MCB Trip Enabled when an AC Signal Acquisition Board is installed.

13 Flag of Effective AC Input Flag of Effective AC Input

14 Flag of Effective AC Input Flag of Effective AC Input

15 DC/DC Failure Enabled when an AC Signal Acquisition Board is installed.

16 Digital Input 6

17 Digital Input 7

18 Digital Input 8

20 Phase A of AC 1 Enabled when an AC Signal Acquisition Board is installed.

21 Phase B of AC 1 Enabled when an AC Signal Acquisition Board is installed.

22 Phase C of AC 1 Enabled when an AC Signal Acquisition Board is installed.

23 Phase A of AC 2 Enabled when an AC Signal Acquisition Board is installed.

24 Phase B of AC 2 Enabled when an AC Signal Acquisition Board is installed.

25 Phase C of AC 2 Enabled when an AC Signal Acquisition Board is installed.

26 Load Current Enabled when a load shunt is connected in DC Power System

27 Batt1 Curr Enabled when a battery shunt is connected in DC Power System

28 Batt2 Curr Enabled when a battery shunt is connected in DC Power System

35 SCU Working For LVD

40 Curr Imbalance Only for China Market

Show 12 more labels / short text on this page
Alarm description Remark · 19 DC Voltage · 29 Batt1 Fuse · 30 Batt2 Fuse · 31 Batt3 Fuse · 32 Batt4 Fuse · 33 Measured Temp1 · 34 Measured Temp2 · 36 Self-detect Error · 37 Manual Mode · 38 Non-FC Status · 39 Batt Discharge
Page 61 of the Emerson 48330 user manual — Note
Page 61 · click to enlarge
Page 61

PLC

SN

41 Short Test Error

43 LLVD

44 BLVD

47 Multi-Rect Fails Disabled for China Market, Enabled for rest of world

48 Rect Fan Fails

49 Rect Com Failure

50 Rect Vac Err

51 Rect Over Temp

54 Rect Fan Fails

5.6 Maintenance

Note

1. This operation can be conducted only when the battery management is set to “Manual”.
2. Be careful! BLVD operations may result in power interruption.

Operation Procedures:

1. At any information page, press “ENT” to enter the main menu.
2. Press “ ” to select the “Maintenance” menu.

You cannot enter the system Maintenance menu if the “Battery Management” is set to “Auto”.

3. Press “ENT” and input the correct operation password. Press “ENT” again to enter the “Maintenance” menu.
Enter Password123456
Show 8 more labels / short text on this page
Alarm description Remark · 42 BattTest Error · 45 Outvolt Error · 46 Power Failure · 52 Rect Failure · 53 Rect Protect · 55 Rect PowerLimit · 56 Derateby Temp
Page 62 of the Emerson 48330 user manual — Note
Page 62 · click to enlarge
Page 62

To input the password, use “” or “” to modify numbers, and use “” or “” to move the cursor. After the input, press “ENT” to confirm.

If the password is incorrect, system will prompt “password incorrect”. If the password is less than 6 digits, end it with a “#”.

Note

You can choose to enter the “Maintenance” menu by using either the user, operator or administrator password, for in this menu, all users have the same authority.

4. Press “ ” or “ ” to scroll to the operation page you need.

There are two pages:

Maintenance StartBC Batt: Reconnect Load: Disconnect
RectTrim53.5V CurrLimit: 110% Rect 1: DC On ID 01234567
5. Press " " and " " to select the needed action.

“Start”: The options include “FC”, “BC” and “Test”. If system is not configured with any battery, the control would be invalid. If there is AC power off alarm, or the busbar voltage is too low, the BC and battery test control will not be executed by the system. No battery test control can be conducted when the rectifier communication is interrupted. Finally, after the battery test, the battery management mode will be changed from “Manual” to “Auto” automatically.

“Battery”: The options include “Reconnect” and “Disconnect”. If there is no battery, or there is a battery alarm, the battery operations will be invalid.

“Load”: The options include “Reconnect” and “Disconnect”.

The following maintenance over the rectifier can be conducted only when the power system is in the FC state.

”RectTrim”: Range: 42V ~ 58V. It can be used to improve the current sharing among rectifiers. Note that the value of this parameter cannot exceed the over-voltage alarm point, or the parameter will be invalid.

”RectLimit”: Range: 10% ~ 121%.

Page 63 of the Emerson 48330 user manual — 5.7.1 Parameter Setting Method
Page 63 · click to enlarge
Page 63

The maintenance operations over a single rectifier include: “DC ON/OFF”, “AC ON/OFF” and “Reset”. The operation method is:

① Use “” or ”” to select the rectifier parameter, and “” or “” to change the

rectifier serial No. Then press “ENT” to confirm. The bottom line of the page displays the rectifier ID.

② Use “” or “” to move the cursor to the maintenance operation area, and

“” or “” to select the value.

If the rectifier voltage is too high, you can select “Reset” to restore the output voltage of that rectifier to normal.

6. There will be prompts as the confirmation of control commands. If the maintenance operation is valid, system will prompt you press “ENT” to confirm and execute the operation, or “ESC” to abort the operation. Otherwise, system will prompt you the operation is invalid, and press “ESC” to quit.

Press ENT to Run Other Key Quit

No Maintain! ESC Quit

Press “ESC” to return to the menu of higher level.

5.7 Setting System Parameters

Battery parameters are very important, for they are related to the life of battery. Before delivery, the battery parameters have been initialized. Without any special needs, you only need to reset the battery group number and battery capacity, and accept the defaults for other parameters.

5.7.1 Parameter Setting Method

1. At any system information page, press “ENT” to enter the main menu.

MAIN MENU status

Maintenance Settings

Page 64 of the Emerson 48330 user manual — Chapter 3 Startup
Page 64 · click to enlarge
Page 64
2. Use “ ” or “ ” to select the submenu “Settings” and press “ENT” to confirm. System will then prompt you to input the password.
Enter Password 123456
3. Press " " or " " to select the number of password digits. Enter the password digit by digit using “ ” or “ ”. Press “ENT” to confirm and enter the parameter setting submenu.

Settings Alarms Settings

Battery Settings AC Settings

Parameter Set DC Settings Rect Settings Sys Settings

Users with different password levels have different authorities. See the following table:

Table 5-9 Password levels and authorities

Level Authority Default password

User Configuration of general parameters 123456

Operator User’s authority, plus resetting system, resetting password and modifying system type. 654321

Operator’s authority, plus modifying password of all levels, controling alarm sound volume, browsing system parameters that can be set only through the host

4. There are two pages of “Settings”. Shift page by using “ ” or “ ”, and select the parameter by using “ ” or “ ”. Press “ENT” to confirm.

As shown in the above figure, the monitoring module divides the parameters to be set into 6 kinds: alarms parameter, battery parameter, AC parameter, DC parameter, rectifier parameter and system parameter.

Among which, the battery parameters are divided into 5 kinds: basic, BLVD, charging management, battery test, temperature coefficient, and they are displayed in two pages, as shown below:

Administrator

Page 65 of the Emerson 48330 user manual — Y
Page 65 · click to enlarge
Page 65

Battery Setting Batt. Selection

LVD Setting Charge

Battery Setting Batt. Test

What follows is the description of the parameter functions and values by dividing them into 5 small categories and 5 big categories.

5.7.2 Batt. Selection

1. The first page of the Batt. Selection is shown below:
ModeManual Batt String: 1 Capacity: 300Ah Batt Name: 1#

Use “” or “” to select the page and the parameter to be set, and “” or “” to select the proper value for the parameter. Press “ENT” to confirm.

After setting the “Battery Type”, the following prompt will appear, asking you to name a certain type of battery for the sake of identifying them:

Battery Name Batt1

To name a rectifier, you can use “” or “” to change the number, and “” or “” to move the cursor left or right. Press “ENT” to confirm afterwards.

2. If setting parameter “System Type” does not require setting the battery shunt coefficient, the second page of the basic battery settings is as follows:
Batt Shunt1 Y Batt Shunt2:

Y

Temp Comp

Page 66 of the Emerson 48330 user manual — 5.7.3 LVD Parameter Description
Page 66 · click to enlarge
Page 66
3. If setting parameter “System Type” requires setting the battery shunt coefficient, the second page of the basic battery settings is as follows:
Batt Shunt1Yes Batt Shunt2: No Shunt Coeff: 300A / 75mV
4. The value description of the basic battery parameters is listed below:

Table 5-10 Value description of the basic battery parameters

Parameter Range Defaults Value description

In normal situation, it should be in the “Auto” mode, which enables the monitoring module manage the whole power system automatically, including: Automatic FC/BC switchover, LLVD and BLVC. In the manual mode, you can do operations like BC, FC, test and battery on/off, as well as enabling automatic battery BC time protection and capacity calculation. Upon the system DC under-voltage alarm, system can automatically switch to the “Auto” mode, lest wrong manual operation should damage the system Batt String (number of battery strings)

Mgmt Mode (Management mode)

0 ~ 4 4 You should set this parameter according to the actual battery configuration. If “Batt Shunt” is set as “Y”, there should be batteries actually configured Rated AH (rated capacity) 50 ~ 5000Ah 300Ah The capacity of a single battery string. You should set this parameter according to the actual battery configuration. BTT Name 1# ~ 11# 1# Battery Name 10 characters Name different battery types to identify them Batt Shunt1 Yes

Select “Y” when a corresponding shunt is configured, otherwise, select “N”. Battery management aims at only the batteries connected to the shunt Shunt Coeff (shunt coefficient)

Batt Shunt2 Yes, No No

In the system type setting, if the parameter “Shunt” is set to “Y”, this parameter will be displayed. Otherwise this parameter will take the default value, and is the same for both battery strings.

Dependent on system type

5.7.3 LVD Parameter Description

1. Function description

LLVD means the monitoring module opens the LLVD contactor, so that the non-priority load will be powered off. In this way, the battery remaining capacity can sustain the priority load longer.

BLVD means the monitoring module opens the BLVD contactor. In this way, the battery will stop powering the load, preventing over-discharge.

2. There are 3 related pages, as shown below:

Auto, Manual Auto

Page 67 of the Emerson 48330 user manual — 5.7.4 Charging Management Parameters
Page 67 · click to enlarge
Page 67
LLVD EnableY BLVD Enable: Y LVD Mode: Voltage
LVD Vlotage LLVD44.0 BLVD: 43.2
LVD Time LLVD300min BLVD: 600min

Use “” or “” to select one page or one of the parameters, and “” or “” to select the parameter value. Press “ENT” to confirm and save.

Note

Generally you do not need to set the LVD parameters’ value. The defaults will do.

3. The value description of the LVD parameters is listed below.

Table 5-11 Value description of the LVD parameters

Parameter Range Default Value description

LLVD Enable Select “Y” to enable LLVD function BLVD Enable Y, N Y Select “Y” to disable the BLVD function

LLVD Mode Time, voltage Voltage

Select “Voltage”, when the monitoring module detects that the battery voltage is lower than the prestet “LLVD Volt”, the load will be disconnected, and so is the battery when the battery voltage is lower than the preset ‘BLVD Volt”. Select “Time”, when the discharge time reaches the preset “LLVD Time”, the monitoring module will disconnect the load; when the discharge time reaches the preset “BLVD Time”, it will disconnect the battery

LLVD Volt 44.0V BLVD Volt 40V ~ 60V 43.2V LLVD Time 300min

3 ~ 1,000 min 600min

5.7.4 Charging Management Parameters

1. There are 6 related pages, as shown below:
Float53.5 Boost: 56.4 Limit: 0.100C10 Over: 0.300c10

· · BLVD Time

Page 68 of the Emerson 48330 user manual — Note
Page 68 · click to enlarge
Page 68

Automatic Boost Y Cyclic Boost: Y

To Boost Current80% Capacity: 0.06C10
Constant Boost Current0.01C10 Duration: 180min
Cyclic Boost Interval400h Duration: 300min
Boost Limit Time300min

Use “” or “” to select one page or one of the parameters, and “” or “” to select the parameter value. Press “ENT” to confirm and save.

Note

Generally you do not need to set the management value. The defaults will do.

2. The charging management parameter value description is listed below:

· ·

Page 69 of the Emerson 48330 user manual — Chapter 3 Startup
Page 69 · click to enlarge
Page 69

Table 5-12 Charging management parameter value description

Parameter Range Default Value description

Float 53.5V In the FC state, all rectifiers output voltage according to the set “Float”

The “Boost” must be higher than the “Float”

42V ~ 58V 56.4V In the BC state, all rectifiers output voltage according to the set “Boost”

When the monitoring module detects that the battery charging current is higher than the “Limit”, it will control the current of the rectifiers, through which it can limit the battery charging current. C10 is the battery rated capacity, generally set to 10 ~ 20% of the rated capacity of one battery string.

Limit (current limit) 0.1 ~ 0.25C10 0.1C10

When the monitoring module detects that the battery charging current is higher than the “Over”, it will raise the battery charge over-current alarm.

Over (over current point) 0.3C10 ~ 1.0C10 0.300C10

Automatic Boost Select “Y”, and BC will be conducted when conditions allow

Select “Y”, and the monitoring module will control the system to enter the Cyclic Boost when the FC time reaches the “Cyclic Boost Interval”. The battery charging voltage is the preset “Boost”, and the time is the preset “Cyclic Boost Time”

Cyclic Boost Interval 48 ~ 8760h 2400h

Cyclic Boost Time 30 ~ 2880min 720min

To Boost Current 0.50 ~ 0.80C10 0.06C10

The monitoring module will control the system enter the BC state when the battery capacity decreases to the value of “To Boost Capacity”, or when the charge current reaches the “To Boost Current”. The charge voltage will be the “Boost”. Constant BC Curr 0.02 ~ 0.99C10 0.01C10 Duration (of constant BC) 30 ~ 1440min 180min

To Boost Capacity 0.1 ~ 0.95 0.80

The system in the BC state will enter the FC state when the charge current decreases to the “Constant BC Curr” and after the “Duration”. The battery charge voltage then will be the “Float”.

To ensure safety, the monitoring module will forcefully control the system to enter the FC state if during the BC state, the BC time reaches the “Boost Limit”, or abnormalities occur (such as AC failure and battery route faulty, etc.).

Boost Limit 60 ~ 2880min 1080min

3. The BC/FC switchover diagram is shown below:
Emerson 48330 — Chapter 3 Startup diagram (page 69)
Fig. 36 · Chapter 3 Startup

Figure 5-2 BC/FC switchover diagram

Boost · Yes, No Y · Cyclic Boost

Page 70 of the Emerson 48330 user manual — N
Page 70 · click to enlarge
Page 70

5.7.5 Battery Test Parameters

1. There are 7 related pages, as shown below:
Battery Test Voltage45.2 Time: 300min
Test End Cap 0.700C10 Planned Test:

N

Planned Test101.02 12Hr Planned Test2: 04.02 12Hr
Planned Test307.02 12Hr Planned Test4: 07.02 12Hr
Short Test Enable: Y Alarm Current 10A
Short TestCyclye: 300h Duration: 5min
Stable Test EnableY Current: 9999A

Use “” or “” to select one page or one of the parameters, and “” or “” to select the parameter value. Press “ENT” to confirm and save.

Page 71 of the Emerson 48330 user manual — 0.01C 10 ~
Page 71 · click to enlarge
Page 71
2. The value description of the parameters is listed below:

Table 5-13 Value description of the battery test parameters

Parameter Range Default Value description

The monitoring module can do battery test, and record 10 sets of test data (accessible only through the host). The battery test has to be started manually, then monitoring module will control the rectifier output voltage, make it lower than the battery voltage, and the battery discharge will begin. Monitoring module will stop the test if the battery voltage reaches the “Battery test voltage”, or the discharge time reaches “Battery test time”, or the battery capacity reaches “Test End Cap”. Afterwards, it will restore the rectifier output voltage to the normal FC voltage, begin the battery charge and switch the system to battery auto-management. Meanwhile the test start time/voltage and end time/voltage and battery remaining capacity will be recorded. The records can be queried through the host. During the battery test, if abnormalities occur, the monitoring module will stop the battery test automatically. Scheduled Test Y, N Y Planned Test 1 00:00, Jan. 1st Planned Test 2 00:00, April 1st Planned Test 3 00:00, July 1st Planned Test 4

43.1V ~ 57.9V 45.2V

Battery test time 5 ~ 1440min 300min

Test End Cap (capacity)

0.01C 10 ~

0 .95C 10 0.7C 10

When the parameter “Scheduled Test” is set to “Y”, the monitoring module will test the battery according to the 4 sets of test time. You can set at most 12 sets of test time through the host.

00:00, Oct. 1st

Alarm Current 1A ~ 100A 10A ShortTest Cycle 24h ~ 8,760h 720h

If the battery have not discharged within the “ShortTest Cycle”, the monitoring module will start a short test, whose operation time is set by the parameter “ShortTest Duration”. By the end of the test, if the difference in the discharge currents of batteries is bigger than the “Alarm Current”, the battery discharge imbalance alarm will be raised. This alarm will automatically end after 5min of delay. Also you can end it by confirming it. StableTest Enable Y, N

ShortTest Duration 1 ~ 60min 5min

The stable test is conducted with constant battery current, whose value is set through the parameter “StableTest Current”. If the parameter “StableTest Enable” is set to “Y”, and the test will be started once the battery satisfies the test condition

StableTest Current 0 ~ 9999A 9999A

3. The schematic diagram of the test function is shown below:

Rectifier output voltage lower than

Battery Auto-management Manually start battery test

battery voltage Battery discharges

"Test End Cap" is

"Test End Time" is

Figure 5-3 Schematic diagram of the test function

Show 7 more labels / short text on this page
Battery test voltage · Month,day, hour · "Test End Voltage" · is reached · reached · Rectifier hot standby · reached
Page 72 of the Emerson 48330 user manual — 5.7.6 Temperature Compensation Coefficient Parameters
Page 72 · click to enlarge
Page 72

5.7.6 Temperature Compensation Coefficient Parameters

1. The first page of the setting interface is shown below:
Temp 1 Ambient Temp 2: Battery
2. If the “Temperature1” or “Temperature2” is set to “Battery Temp”, you need to set the following parameters:
Center Temp 25°C Temp. Comp: 70mV / °C /Str
Batt Temp Alarm Over70°C High: 50°C Low: 0°C

Use “” or “” to select one page or one of the parameters, and “” or “” to select the parameter value. Press “ENT” to confirm and save.

3. The value description of the parameters is listed below:

Table 5-14 Value description of temperature compensation coefficient

Parameter Range Default Value description

The “Ambient Temp” and “Battery Temp” refer to the measurement of the ambient or battery temperature sensor at the local power system. “None” means there is no measurement input. You should set the parameter according to the actual situation. The temperature measurement data will be displayed in the system operation information screen. Center Temp 10°C ~40°C 25°C When Temp 1 or Temp 2 is set to “Battery Temp”

Ambient Temp, None, Battery Temp None

Batteries are sensitive to temperature. To ensure battery’s capacity and life, its FC voltage should change together with the temperature: lower FC voltage for higher temperature, and vice versa.

The default is 72mV/°C for 48V system and 36mV/°C for 24V system.

Upon alarms such as “Rect Com Failure”, “DC Under-volt” and “DC Voltage High”, the monitoring module will not do temperature compensation to the battery FC voltage. Set this parameter according to the actual battery technical parameters

Show 4 more labels / short text on this page
Temp 1 · Temp 2 · Temp Comp · 0~ 500mV/°C
Page 73 of the Emerson 48330 user manual — 5.7.7 AC Settings
Page 73 · click to enlarge
Page 73

Parameter Range Default Value description

When Temp 1 or Temp 2 is set to “Battery Temp”

Over 10 C ~ 100 C 50°C When the detected battery temperature is higher than the “Over”, the monitoring module will raise an alarm

The “High” must not be higher than the “Over”

High 10°C ~ 100°C 50°C When the detected battery temperature is higher than the “High”, the monitoring module will raise an alarm

Low -40°C ~ 10°C 0°C The monitoring module will raise an alarm when the detected battery temperature is lower than the “Low”

5.7.7 AC Settings

1. The configuration interface is shown below:
OverVolt240V LowVolt: 210V UnderVolt: 200V AC Input: None

Use “” or “” to select one page or one of the parameters, and “” or “” to select the parameter value. Press “ENT” to confirm and save.

2. The value description of the parameters is listed below:

Table 5-15 Value description of AC settings

Parameter Range Default Value description

OverVolt 50V ~ 300V 280V The monitoring module will raise an alarm when the AC input voltage is higher than the “OverVolt”

The “OverVolt” must be higher than the “LowVolt”. To avoid alrm disorder, it is suggested to use the default values

LowVolt 50V ~ 300V 170V The monitoring module will raise an alarm when the AC input voltage is lower than the “LowVolt”.

The monitoring module will raise an alarm when the AC voltage of an operating route is lower than the “UnderVolt”, but there will be no alarm when the AC voltage of the standby route is lower than the “UnderVolt”

UnderVolt 50V ~ 300V 80V

The “UnderVolt” must be lower than the “LowVolt”.

3-phase, Single Phase, None

Dependat on system type

Set this parameter according to the actual situation. In a system with an AC sampling board, you can only select “Single Phase” or “3-phase”; in a system without an AC sampling board, you can select only “None”.

AC Input

Page 74 of the Emerson 48330 user manual — -40°C ~ 10°C -5°C
Page 74 · click to enlarge
Page 74

5.7.8 DC Setting

1. There are three related pages, as shown below:
DC Volt Alarm Over58.5V Low: 45.0V Under: 45.0V
Amb. Temp Alarm High25°C Low: 0°C

Load Shunt None Shunt Coeff: None

Use “” or “” to select one page or one of the parameters, and “” or “” to select the parameter value. Press “ENT” to confirm and save.

2. The value description of the parameters is listed below:

Table 5-16 Value description of DC settings

Parameter Range Default Value description

Over (over-voltage) 58.5V The “DC Over Voltage” alarm will be raised when the system DC output voltage is higher than the value of “Over”

The values of these three parameters should be: Over > Low > Under

Low (low-voltage) 45.0V The DC low voltage alarm will be raised when the system DC output voltage is lower than the value of “Low”

40V ~ 60V

45.0V The DC under voltage alarm will be raised when the system DC output voltage is lower than the value of “Under”

10°C ~ 100°C 40°C The high temperature alarm will be raised when the detected ambient temperature is higher than the value of “High”

The value of parameter “High” must be higher than that of parameter “Low”

The low temperature alarm will be raised when the detected ambient temperature is lower than the value of “Low”

-40°C ~ 10°C -5°C

Load shunt Y, None None Set according to the system actual situation

Shunt Coeff Dependent on system type

In the system with a load shunt, this parameter can be set only when the parameter “Shunt” (as a system type) is set to “Set”.

Under (under-voltage) · High (high temperature) · Low (low temperature)

Page 75 of the Emerson 48330 user manual — 5.7.9 Rect Settings
Page 75 · click to enlarge
Page 75

5.7.9 Rect Settings

1. There are three related pages, as shown below:
Rect Over Volt59.0V Default Volt: 42.0V

Walk-in Enabled N Walk-in Time: 8s

Fan Speed Full Speed HVSD Time: 300s

Use “” or “” to select one page or one of the parameters, and “” or “” to select the parameter value. Press “ENT” to confirm and save.

2. The value description of the parameters is listed below:

Table 5-17 Value description of rectifier settings

Parameter Range Default Value description

Rect Over Volt 56V ~ 59V 59V The rectifier over voltage alarm will be raised when the rectifier output voltage is higher than the “Rect Over Volt” Default Volt 48V ~ 58V 53.5V

The “Default Volt” must be lower than the “Rect Over Volt”

Walkin Enabled Y, N N Walkin Time 8s ~ 128s 10s The output soft start function means the rectifier voltage will rise from 0V to the “Default Volt” after the “Walkin Time”

When set to “Half Speed”, the rectifier will regulate the fan speed according to the temperature. When set to “Full Speed”, the fan will operate at full speed

Fan Speed Full Speed, Half Speed

The rectifier will shut off automatically upon over-voltage, and restart after a certain delay to see whether it is still over-voltage then. That delay is set through the parameter “HVSD Time”. If the rectifier’s output voltage is normal within the delay, the rectifier is regarded normal; otherwise, the rectifier will be locked out and auto-restart function will be disabled

HVSD Time 50s ~ 300s 300s

Half speed

Page 76 of the Emerson 48330 user manual — 5.7.10 System Settings
Page 76 · click to enlarge
Page 76

5.7.10 System Settings

Users of different password levels have different authorities.

1. For the user level password (123456), there are 2 related pages, as shown below:
Adress1 Text: Chinese CommMode:Modem Baud: 9600
Set Date 2004-05-01 Set Time:

17:30:30

Use “” or “” to select one page or one of the parameters, and “” or “” to select the parameter value. Press “ENT” to confirm and save.

When the “CommMode” is “modem” or “EEM-M”, the “CallBack Number” and “CallBack Num” (how many times should callback be made) should be set.

Call back Num 5 Call back Set Code1
CallBack Number 01234567901234 56789

Use “” or “” to change the number, and “” or “” to move the cursor left or right. Press “ENT” to confirm.

2. For the operator level password (by default: 654321) or administrator level password (by default: 640275), you can see the following pages, besides the pages above, as shown below:
Page 77 of the Emerson 48330 user manual — Chapter 3 Startup
Page 77 · click to enlarge
Page 77
System Type48V/50A/300/NONE Serial No: 2004051025252

There will be a prompt when resetting the system:

3. For administrator level password (by default: 640275), you can see the following pages, besides all those above, as shown below:

Change Password:

Code Con Alarm Voice:

Serial12345689101112 SW Ver: 1.00 Set Enable: Y

You can change the value of “Change Password” and press “ENT” to confirm.

Enter New PWD 000000

Use “” or “” to change the number, and “” or “” to move the cursor left or right. Press “ENT” to confirm. You should input the same number twice to complete the setting.

4. The value description of the parameters is listed below:

1 Hour · Input Again!

Page 78 of the Emerson 48330 user manual — Y, N N
Page 78 · click to enlarge
Page 78

Table 5-18 Value description of system settings

Parameter Range Default Value description

Text Chinese, English and Spanish Chinese Set according to your need

Address 1 ~ 254 The addresses of power systems that are at the same monitored office should be different

“MODEM”: Through modem and based on the Telecom protocol. “EEM-M”: Through modem and based on the EES protocol. “RS-232”: Through a transparent serial port and based on the Telecom protocol

CommMode modem, EEM-M, RS-232

BaudRate 1200bps, 2400bps, 4800bps, 9600bps Make sure the baud rates of both the sending and receiving parties are the same

CallBack Num. 1 ~ 10 3 When “CommMode ” is set to “MODEM” or “EEM-M”

Set according to the actual need. In a extension system, sometimes you need to put a “,” between the main number and extension number. When the callback number is less than 19 digits, end it with a “#”

CallBack Number 19 digits at most

Set Date 2,000 ~ 2,099

Set the time according to the current actual time, regardless of whether it is a leap year or not

Set Time Hour, min, sec

Initialize password Y, N N Selecting “Y” can reset the user level and administrator level passwords to the defaults Operator level or above

When the system parameters cannot be set normally, and the usual resetting methods do not work, you can set the “Init Param” to Y, and all the system parameters will be restored to defaults. Alarms may be raised for the defaults may fail to meet the actual situation. Set the parameters according to the actual situation then.

Init Param (Initialize parameter s)

Y, N N

Page 79 of the Emerson 48330 user manual — 100/300/500/SET
Page 79 · click to enlarge
Page 79

Parameter Range Default Value description

Operator level or above

24V/75A/500/NONE 24V/75A/500/MAN 24V/75A/500/AUTO 24V/50A/500/NONE 24V/50A/500/MAN 24V/50A/500/AUTO 48V/50A/500/NONE 48V/50A/500/MAN 48V/50A/500/AUTO 48V/50A/300/NONE 48V/50A/300/MAN 48V/50A/300/AUTO 48V/30A/300/NONE 48V/30A/300/MAN 48V/30A/300/AUTO 48V/30A/100/NONE 48V/30A/100/MAN 48V/30A/100/AUTO 48V/15A/100/NONE 48V/15A/100/MAN 48V/15A/100/AUTO 48V/100A/SET/NON 48V/100A/SET/MAN 48V/100A/SET/AUT 48V/50A/SET/NONE 48V/30A/SET/NONE

This parameter has been set according to the actual situation upon delivery and needs not to be changed. However, when a new monitoring module is used, its “System Type” should be set according to the actual situation. After this parameter is changed, the monitoring module will restart automatically, and other parameters of the monitoring module will be changed to the defaults of the corresponding system type. You should change some parameters according to the actual situation.

Change Password User, Operator, Admin The password can be 6 digits long at most. If it is shorte than 6 digits, end it with a “#”

3min, 10min, 1h, 4h, constant Contstant The period that an alarm sound will last

Serial The production serial No. of the monitoring module. This parameter cannot be changed

SW Ver The software version No. of the monitoring module. This parameter cannot be changed Administrator

Reflecting the jumper status of a hardware switch within the monitoring module. If this parameter is set to ”N”, you are not allowed to use the jumper, nor change any parameter except the battery management mode. The maintenance over the monitoring module will not be affected

5. The model description is shown below:

48V / 30A / 300 / NONE

No AC data acquisition board

System shunt coefficient:

100/300/500/SET

Rectifier rated output current15A/30A/50A/75A/100A
Rectifier rated output voltage48V/24V

Figure 5-4 System model description

System Type · Con Alarm Voice · Set Enable

Page 80 of the Emerson 48330 user manual — 5.7.11 Alarm Settings
Page 80 · click to enlarge
Page 80

The relationship between the system model and system type is listed in the following table:

Table 5-19 Relationship between system model and system type

Power system model System type

PS48400-3/2900, Single AC Input 48V/50A/300/NONE PS48400-3/2900, Double AC Inputs, Manual Switchover 48V/50A/300/MAN PS48400-3/2900, Double AC Inputs, Auto Switchover 48V/50A/300/AUTO PS48600-3/2900, Single AC Input 48V/50A/500/NONE PS48600-3/2900, Double AC Inputs, Manual Switchover 48V/50A/500/MAN PS48600-3/2900, Double AC inputs, Auto Switchover 48V/50A/500/AUTO

Note

SCU can monitor multiple power systems made by Emerson. If the system type is not set correctly, unpredictable faults may occur.

5.7.11 Alarm Settings

1. The first page of the setting interface is show below:

Alarm Settings Alarm Type

Alarm Mode Alarm Control

There are 3 submenus. Use “” or “” to select one, and use “ENT” to confirm.

2. The three submenus are shown below:
Alarm Type Alarm Block LevelMajor Relate Relay: 1
Alarm Mode DI No1# Mode: High Set DI Name: 2#
Clear His. AlarmN Block Alarm: Y
Page 81 of the Emerson 48330 user manual — Chapter 3 Startup
Page 81 · click to enlarge
Page 81

Use “” or “” to select one page or one of the parameters, and “” or “” to select the parameter value. Press “ENT” to confirm and save.

3. After setting the “Set DI Name” and confirming it, the system will prompt you to name the DI:

DI Name Digital 1

Use “” or “” to change the number, and “” or “” to move the cursor left or right. Press “ENT” to confirm.

4. The value description of the parameter is listed below:

Table 5-20 Value description of alarm settings

Parameter Range Default Value description

Alarm Type 56 names of alarm events

Alarms of different types have different levels and different Relate Relays

Select those alarm events whose levels and relate relays should be reset

Level Critical, Major, Observation, None

There are different audible/visual alarm modes and callback modes for alarm events of different levels

“Empty”: The corresponding dry contact will not output alarm information upon an alarm event “No. 1 ~ 8”: There will be a dry contact in the range of No.1 ~ 8 that outputs the alarm information upon an alarm event

Relate Relay Empty, No.1 ~ 8

DI No. No. 1 ~ 8 1 The 8 corresponding connecting terminals, queued up in the order that the hardware switches are put

“High”: alarm upon high level; “Low”: alarm upon low level. Set according to the actual situation

Alarm Mode High, Low Low

Effective only to self-defined DI alarms

Set DI Name 1# ~ 8# 1# Serial No. of the connecting terminal for DI input

When there are DI alarms, this parameter shows the alarm name you have actually defined. In the system with an AC sampling board, you can define by yourself the DIs of routes No.7 and No.8. In the system without an AC sampling board, you can define all DIs

DI Name Figures or letters, 10 at most Digital

Clear His Alarm Y, N N “Y”: Delete historical alarms

Block Alarm Y, N N “Y”: The active alarms will not be sent to the host (valid in EEM protocol)

Page 82 of the Emerson 48330 user manual — 6.3 Maintenance Of MFU
Page 82 · click to enlarge
Page 82

72 Chapter 6 Routine Maintenance

Chapter 6 Routine Maintenance

6.1 Maintenance Of Rectifier

The fan of rectifier shall be maintained periodically.

The fan shall be replaced if it does not work due to faults.

Follow the procedures below to replace the fan:

1. Loosen the 3 screws on the baffle and remove the baffle.
2. Unplug the power cable of the fan and remove the fan.
3. Replace the fan.
4. Plug the fan power cable back into the corresponding socket.
5. Push back the fan (the side with the tag facing inward).
6. Mount the front baffle and fix it with screws.

6.2 Maintenance Of SCU

If any SCU fault affects the normal operation of DC power system, just turn off the SCU.

6.3 Maintenance Of MFU

1. Short-circuit of load

If some of the loads have short circuit fault, just turn off the circuit breakers in the MFU to disconnect the power to the loads.

2. MFU short-circuit

When MFU short-circuit occurs, disconnect the AC power supply, isolate the batteries from the system, and then use battery or rectifier to directly supply power to load.

Page 83 of the Emerson 48330 user manual — 6.5.2 Daily Inspection
Page 83 · click to enlarge
Page 83

Chapter 6 Routine Maintenance 73

6.4 Cover Plates

The Multi-Function Unit has a cover plate to protect the load and battery circuit breakers and to create a neat finish. This cover plate is easy to open/remove in order to switch on or off a circuit breaker, or to connect additional loads. The cover plate can be opened or removed without the need of using special tools. The DC section of the Distribution Unit is made safe for a “User” to access, which follows the “Look and Feel” guidelines.

6.5 Battery Maintenance

6.5.1 Storage And Supplementary

During storage, the capacity of the battery decreases because of self-discharging. When using a stored battery, always carry out supplementary charging before use. Refer to the battery user manual or follow battery manufacturer’s advices to perform supplementary charging.

Store the battery in a cool dry place.

6.5.2 Daily Inspection

1. Check the battery regularly. The battery needs to be replaced if any abnormal condition occurs, such as:

Any physical defects (e.g., a cracked or deformed container cover);

Any abnormal heat generation.

2. Clean any dust contamination with a wet cloth. Never use organic solvents (gasoline or thinners), otherwise the container or cover may crack.
3. Voltage checks.

The total voltage of the batteries should not deviate from the recommended 2.25 V per cell (54V in a 48V DC power system at reference temperature). If it deviates, check your system to see that the setting is correct and that the temperature compensation is correct.

Show 4 more labels / short text on this page
Any voltage abnormalities; · Any electrolyte leakage; · Total voltage · Unit voltage
Page 84 of the Emerson 48330 user manual — 6.5.3 Replacement
Page 84 · click to enlarge
Page 84

74 Chapter 6 Routine Maintenance

After one year of operation, all the units should be within the range of 13.50±0.48V.

6.5.3 Replacement

1. Replacing Criterion

Replace the battery if its capacity measured during the battery test is less than 80% of the battery rated capacity. The capacity measured during the battery test shall be evaluated at a discharge rate close to its actual use.

2. Replacement Interval

The battery is expendable, and has a certain life cycle. Considering the use condition and ambient temperature, the new battery should replace the old battery before it reaches its design life to ensure the normal and safety operation of the DC power system. For instance, in an environment where the mean temperature is 35°C, it is necessary to replace the battery every 5-year operation.

Page 85 of the Emerson 48330 user manual — Chapter 7 Troubleshooting
Page 85 · click to enlarge
Page 85

Chapter 7 Troubleshooting 75

Chapter 7 Troubleshooting

7.1 Troubleshooting Rectifier

1. Troubleshoot Rectifier according to LED Indication

The usual fault symptoms of the rectifier include: power indicator (green) off, protection indicator (yellow) on, protection indicator (yellow) blinking, alarm indicator (red) on, and alarm indicator (red) blinking.

No input voltage Make sure there is input voltage

Replace the fuse with a new one of the same model or reconnect the input power with correct polarity.

Power indicator (green) off Input polarity reversed or input fuse blown

AC input voltage outside the normal range

Ensure the AC input voltage remain within normal range

PFC over-voltage Replace the rectifier

Current sharing function is disabled Replace the rectifier

Rectifier over-temperature protection, which is caused by:

Protection indicator (yellow) on

1. Fan blocked 1. Remove the obstacle that blocks the fan
2. Ventilation blocked: the inlet or outlet blocked
2. Remove the objects that blocks the inlet or outlet
3. Ambient temperature too high or rectifier inlet too close to an heater
3. Remove the heater, lower the ambient temperature

Rectifier not inserted into the slot completely Insert the rectifier again properly

Protection indicator (yellow) blinking Rectifier communication failure Check the communication cables

Remove the rectifier from the DC power system, restart the rectifier, and replace the rectifier if over-voltage still occurs.

Alarm indicator (red) on Rectifier over-voltage

Alarm indicator (red) blinking Fan not running Replace the fan

2. Rectifier Current Sharing Unbalanced

When multiple rectifiers are in parallel connection and the unbalance of current sharing among them is bigger than 3%, check if the communication cables are correctly connected.

Table 7-1 Troubleshooting · Symptom Cause Suggestion

Page 86 of the Emerson 48330 user manual — 7.3 Disastrous Accidents
Page 86 · click to enlarge
Page 86

76 Chapter 7 Troubleshooting

If the current sharing is still unsuccessful after the correction, replace the rectifier of which the current sharing function is disabled.

7.2 Mains Failure

Mains failure often occurs in power system operation. Batteries will provide backup DC power in case of short-period of mains failure. If the cause of mains failure remains unknown or the failure lasts too long, the generator should be started to provide mains supply to the system. It is suggested that the generator should supply power to the power system at least 5 minutes after it is started so as to reduce the effect of the start process on the power system.

7.3 Disastrous Accidents

Disastrous accidents such as lightning strike, flood, earthquake and fire lead to the communication equipment faults. For the disasters that will severely affect the safety of communications, efforts should be mainly made to prevention actions. Meanwhile, communication stations should have adequate human and material resources and work out effective countermeasures to cope with these disasters. They should also have emergency management regulations and serious accidents emergency plans.

Page 87 of the Emerson 48330 user manual — EMC
Page 87 · click to enlarge
Page 87

Appendix 1 System Technical Parameters 77

Appendix 1 System Technical Parameters

AC input over-voltage alarm point Default: 280 ! 5Vac, cofigurable through monitoring module

Default270 ! 5Vac, 10Vac lower than the AC input

AC input over-voltage recovery point

AC input alarm and protection

over-voltage alarm point AC input under-voltage alarm point Default: 180 ! 5Vac, configurable through monitoring module

AC input under-voltage recovery point

Default190 ! 5Vac, 10Vac higher than the AC input

under-voltage alarm point DC output over-voltage protection point Default: 59.0 ! 0.2Vdc

DC output over-voltage alarm point

Default58.5 ! 0.2Vdc, configurable through monitoring

DC output over-voltage recovery point

Default58 ! 0.2Vdc, 0.5Vdc lower than the over-voltage

DC output under-voltage alarm point

Default45.0 ! 0.2Vdc, configurable through monitoring

DC output alarm and protection

DC output under-voltage recovery point

Default45.5 ! 0.2Vdc, 0.5Vdc higher than the under-voltage
LLVD Default44 ! 0.2Vdc, configurable through monitoring module
BLVD Default43.2 ! 0.2Vdc, configurable through monitoring

Output delay Output voltage can rise slowly upon rectifier start up. The rise time is configurable

Fan speed adjustable Rectifier fan speed can be set to half or full speed.

CS RS EN300386 2001, Class A

EMC

Immunity to EFT EN61000-4-4, Level 3 Immunity to ESD Air discharge: 8kV. Contact discharge: 4kV. EN61000-4-2

Immunity to Surges EN61000-4-5, Level 4

The AC input side can withstand 10/700μs simulated

lightning voltage 5kV for !5 times, or 8/20μs simulated

Lightning protection features At AC side

lightning surge current 20kA for !5 times, or 8/20μs

simulated lightning surge current 40kA once. The test interval is not smaller than 1 minute.

Acoustic noise 55dB (A) Others

At temperature of 15°C ~ 35°C and relative humidity not higher than 90%RH, apply a test voltage of 500Vdc. The insulation resistances between AC circuit and earth, between DC circuit and earth, or between AC and DC circuits are no less than 10MΩ

Show 7 more labels / short text on this page
Parameter category Note · module · alarm point · module · alarm point · module · Insulation resistance
Page 88 of the Emerson 48330 user manual — % 2000 (H)
Page 88 · click to enlarge
Page 88

78 Appendix 1 System Technical Parameters

(Remove the SPD, monitoring module and rectifiers from the system before the test.) AC to DC circuits, AC circuit to earth: 50Hz, 3,000Vac (RMS). DC circuit to earth: 50Hz, 1,000Vac (RMS). Assistant circuit (not directly connected to the host circuit): 50Hz, 500Vac (RMS). For all the three tests above, there should be no breakdown or flashover within 1min, with leakage current not bigger than 10mA.

Size (mm) 600 (W) % 600 (D)

600 (W) % 400

600 (W) % 400 (D)

% 700 (H) Mechanica

% 2000 (H)

(D) % 2000 (H)

Weight

Show 6 more labels / short text on this page
Parameter category Note · Others · Dielectric strength · MTBF 250,000hr · <125kg (without rectifiers) · <60kg (without rectifiers)
Page 89 of the Emerson 48330 user manual — Appendix 2 Engineering Design Diagram
Page 89 · click to enlarge
Page 89

Appendix 2 Engineering Design Diagram 79

Appendix 2 Engineering Design Diagram

Appendix 2.1 Engineering Design Diagram For

2000mm % 600mm % 600mm Cabinet

Emerson 48330 — Appendix 2 Engineering Design Diagram diagram (page 89)
Fig. 37 · Appendix 2 Engineering Design Diagram
Page 90 of the Emerson 48330 user manual — Appendix 2.2 Engineering Design Diagram For
Page 90 · click to enlarge
Page 90

80 Appendix 2 Engineering Design Diagram

Appendix 2.2 Engineering Design Diagram For

2000mm % 600mm % 400mm Cabinet

Page 91 of the Emerson 48330 user manual — Appendix 2.4 System Input And Output Connector Specs
Page 91 · click to enlarge
Page 91

Appendix 2 Engineering Design Diagram 81

Appendix 2.3 Engineering Design Diagram For

Emerson 48330 — Appendix 2.3 Engineering Design Diagram For diagram (page 91)
Fig. 38 · Appendix 2.3 Engineering Design Diagram For

Appendix 2.4 System Input And Output Connector Specs

Emerson 48330 — Appendix 2.4 System Input And Output Connector Specs diagram (page 91)
Fig. 39 · Appendix 2.4 System Input And Output Connector Specs

AC input terminal H cable terminals, 2-4 pcs (cable section 35mm2)

1 big wire connectors, (cable section 25mm2)

Positive bus bar 4 M8blots, 6 big wire connectors, (cable section 25mm2)

23 small wire connectors, (cable section 16mm2) DC Power distribution

Output route MCB H cable terminals (cable section 25mm2)

Page 92 of the Emerson 48330 user manual — Appendix 3 System Circuit Diagram
Page 92 · click to enlarge
Page 92

Appendix 3 System Circuit Diagram 82

Emerson 48330 — Chapter 3 Startup diagram (page 92)
Fig. 40 · Chapter 3 Startup

Appendix 3 System Circuit Diagram

Appendix 3.1 System Electric Schematic Diagram

Page 93 of the Emerson 48330 user manual — Appendix 3.2 System Wiring Diagram
Page 93 · click to enlarge
Page 93

Appendix 3 System Circuit Diagram 83

Emerson 48330 — Chapter 3 Startup diagram (page 93)
Fig. 41 · Chapter 3 Startup

Appendix 3.2 System Wiring Diagram

Page 94 of the Emerson 48330 user manual — Appendix 3.3 MFU Electric Wiring Diagram
Page 94 · click to enlarge
Page 94

Appendix 3 System Circuit Diagram 84

Emerson 48330 — Chapter 3 Startup diagram (page 94)
Fig. 42 · Chapter 3 Startup

Appendix 3.3 MFU Electric Wiring Diagram

Page 95 of the Emerson 48330 user manual — Appendix 3.4 BCU Electric Wiring Diagram
Page 95 · click to enlarge
Page 95

Appendix 3 System Circuit Diagram 85

Appendix 3.4 BCU Electric Wiring Diagram

Page 96 of the Emerson 48330 user manual — Appendix 4 Glossary
Page 96 · click to enlarge
Page 96

86 Appendix 4 Glossary

Appendix 4 Glossary

Amb.Temp Ambient Temperature Batt Battery BC Boost Charging BLVD Battery Lower Voltage Disconnection Cap Capacity CommMode Communication Mode CurrLimit Current Limit CycBC Cyclic Boost Charging Con Alarm Voice Control Alarm Voice Hist Alarm Historical alarm HVSD High Voltage Shutdown InitParam Initialize Parameters InitPWD Initialize Password LLVD Load Low Voltage Disconnection LVD Low Voltage Disconnection Ph-A Phase A PWD Password Rect Rectifier Shunt coeff Shunt Coefficient SPD Surge Protection Device SW Version Software Version Sys System Temp Temperature Temp Comp Temperature Compensation Volt Voltage

Abbreviation Full word

Fix-it

Troubleshooting

Common problems, likely causes, and what to do.

ProblemPossible causeRemedy
Power indicator (green) offNo input voltage p.85
Power indicator (green) offInput polarity reversed or input fuse blown p.85
Protection indicator (yellow) onAC input voltage outside the normal range p.85
Protection indicator (yellow) onPFC over-voltage p.85
Protection indicator (yellow) onCurrent sharing function is disabled p.85
Protection indicator (yellow) onRectifier over-temperature protection, which is caused by: p.85
Protection indicator (yellow) on1. Fan blocked p.85
Protection indicator (yellow) on2. Ventilation blocked: the inlet or outlet blocked p.85
Protection indicator (yellow) on3. Ambient temperature too high or rectifier inlet too close to an heater p.85
Protection indicator (yellow) onRectifier not inserted into the slot completely p.85
Protection indicator (yellow) blinkingRectifier communication failure p.85
Alarm indicator (red) onRectifier over-voltage p.85
Alarm indicator (red) blinkingFan not running p.85

Ask about the Emerson 48330

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.