User Manual
Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or service center.
Copyright © 2005 by Emerson Network Power Co., Ltd.
All rights reserved. The contents in this document are subject to change without notice.
Emerson Network Power Co., Ltd.
E-mail: [email protected]

To avoid accident, read the safety precautions very carefully before operation. The "Caution, Notice, Warning, Danger" in this manual do not represent all the safety points to be observed. Therefore, the installation and operation personnel must be strictly trained and master the correct operations and all the safety points before actual operation.
When operating Emerson products, the safety rules in the industry, the general safety precautions and special safety instructions must be strictly observed.
Some components of the power system carry hazardous voltage in operation, direct contact or indirect contact through moist objects with these components will result in fatal injury.
Safety rules in the industry must be observed when installing the power system. The installation personnel must be licensed to operate high voltage and AC power.
In operation, be sure to remove conductive objects, such as watch, bracelet, ring, and so on.
When water or moisture is found on the cabinet, turn off the power immediately. In moist environment, take precautions to keep moisture out of the power system.
"Prohibit" warning label must be attached to the switches and buttons which are not permitted to be operated on during installation.
High voltage operation may cause fire and electric shock. The connection and wiring of AC cables must be in compliance with the local codes and regulations. Only those who are licensed to operate high voltage and AC power can perform high voltage operations.
In high voltage and AC operation, special tools must be used. No common or homemade tools should be used.
Never operate on high voltage, AC, iron tower or mast on a day with thunderstorm.

In thunderstorms, a strong electromagnetic field will be generated in the air. Therefore the equipment should be well-earthed in time to avoid damage by lightning strikes.
The static electricity generated by the human body will damage the static sensitive elements on PCBs, such as large-scale ICs. Before touching any plug-in board, PCB or IC chip, ESD wrist strap must be worn to prevent body static from damaging the sensitive elements. The other end of the ESD wrist strap must be well earthed.
During operation, never short the positive and negative terminals of the MFU of the system or the non-earthing terminal and the earth. The power system is a constant voltage DC power equipment, short circuit will result in equipment burning and endanger human safety.
Check carefully the polarity of the cable and connection terminal when performing DC live operations.
Never wear a watch, bracelet, ring, or other conductive objects during operation.
Insulated tools must be used.
Before any operation on battery, read very carefully the safety precautions for battery transportation and the correct battery connection method.
Non-standard operation on the battery will cause danger. In operation, precautions should be taken to prevent battery short circuit and overflow of electrolyte. The overflow of electrolyte will pose potential threat to the equipment, it will erode the metal objects and PCBs, thus causing equipment damage and short circuit of PCBs.
Before any operation on battery, pay attention to the following points:
Remove the watch, bracelet, bangle, ring, and other metal objects on the wrist.
Use special insulated tools.
Wear an eye protection device, and take preventive measures.
Wear rubber gloves and apron to guard against electrolyte overflow.
In battery transportation, the electrode of the battery should always be kept facing upward. Never put the battery upside down or slanted.
5 Short-circuit

The equipment has multi power inputs;
The equipment shall be installed on cement ground.
Please use the same model fuse to replace the fuse in the DC Power System.
When moving equipment by hand, wear protective gloves to avoid injury by sharp object.
Please verify the compliance of the cable and cable label with the actual installation prior to cable connection.
The signal cables should be installed separately far away from heavy current and high voltage cables, with distance at least 150mm.
1 Safety requirement













Chapter 1 System Description 1
1.1 Abbreviation
SCU Standard Controller Unit
BCU Battery Connection Unit
CSU Central Supervision Unit
HVSD High Voltage Shutdown
MCB Miniature Circuit Breaker
APFC Active Power Factor Correction
The ACTURA Flex 48330 Power system consists of 50A rectifiers, Control Unit, Multi-Function Unit (MFU), rectifier shelf and BCU (optional).
The product is used in base station, small exchange station, satellite communication, data communication, and so on, with a strong adaptability to power network fluctuation.
This system is used as a power supply for telecom equipment with system nominal voltage of -48V and positive terminal earthed.
The DC power system is easy-to-operate, easy-to-install and easy-to-maintain. Its main features are:
z Rectifier uses APFC technology and therefore its PF is up to 0.99;
z Wide AC input voltage range of 85~290V;
z Rectifier efficiency is at least 90%;
z Extra low EMI of rectifier and excellent EMC performance;
AC Alternate Current · DC Direct Current · MFU Multi-Function Unit

2 Chapter 1 System Description
z High power density of rectifier;
z Rectifier has damage-free hot plugging/unplugging function, the replacement
time is less than 1min;
z Rectifier has two kinds of over-voltage protection methods;
z Perfect battery management with BLVD function;
z Up to 200 PCS of historical alarms can be stored in SCU;
z Provide RS232, Modem and dry contacts communication interfaces;
The outline of the DC Power System is illustrated in Figure 1-1:

There are three kinds of DC Power Systems, and their detail configurations are as shown in Table 1-1:
Multi-function unit · Door · Figure 1-1 Outline

Chapter 1 System Description 3
Table 1-1 Configurations of Actura Flex 48330 Power System
2.0 % 0.6 % 0.6 m3 2.0 % 0.6 % 0.4 m3 0.7 % 0.6 % 0.4 m3
3P+N/380V AC input with SPD
3P+N/380V AC input without SPD
1P+N/220V AC input with SPD
1P+N/220V AC input without SPD
L1+L2/220V AC input with SPD
L1+L2/220V AC input without SPD
3P/220V AC input with SPD
3P/220V AC input without SPD
5 2P AC input MCBs
Individual AC cables with just terminals
DC distribution Up to 28 13mm-wide MCB, or 20 18mm-wide MCB
Rectifier Up to 5 rectifiers
Control unit 1 SCU
BCU 1 BCU with up to 5 battery circuit breakers
Hawker 12V82F:
Hawker SBSC11 and 3U space:
Hawker 12V 105Ah FT and 6U space:
Hawker 12V82F( no BCU):
Dimensions (H×W ×D) mm 2000×600×600 2000×600×400 700×600×400

4 Chapter 1 System Description
The outline of the Rectifier Shelf is illustrated in Figure 1-2:
Terminal connecting 50A Rectifier


(a) Actual appearance (front view)



(b) Actual appearance (rear view)
Figure 1-2 Rectifier shelf outline
The shelf can accommodate 5 rectifiers and a control unit as shown in Figure 1-3. The user can mount the rectifier shelf into cabinets with widths of 600mm and depths of 400mm. The rectifier shelf has a height of 3U (132.5mm).

Figure 1-3 Rectifier shelf with rectifiers and CU

Chapter 1 System Description 5
The Dimension of Rectifier Shelf are given in Table 1-2
Table 1-2 Dimensions of rectifier shelf
Manufacture type W(mm) ×D(mm) ×H(mm) Note
PSS485023/C 584.2×327×132.5 23’’ with controller
The backboard has the functions below:
z DC power source feed for controller and the connector board.
z DC input filter and input fuse.
z All the ingoing and outgoing signals of the controller
The backboard also contains system internal connectors below:
z 10 Distribution unit fuses alarm signal measurement input
z 4 battery fuse alarm signal measurement input
z 2 battery current shunt measurement inputs
z 1 load Current shunt measurement input
z System bus-bar DC Voltage measurement input
z Three-phase from two mains AC Voltage measurement inputs
z CAN communication between rectifiers and controller
z AC alarm module signals
z System fault indicator drivers
z LLVD & BLVD mono contactor driver outputs
z The entire signal outgoing to the connector board
Connector board is a user interface board and has the functions below:
z 8-channel relay outputs
z 8-channel digital inputs
z One power source feed terminal (for digital inputs)
z 2-channel temperature sensor inputs
z 2-channel RS232 parallel connection outputs
z LLVD & BLVD bistable contactor driver circuits and outputs

6 Chapter 1 System Description
z One Ethernet output
z One RS485 output
z One console output for ECU debug
z The connector board can be hot plug and has enough space for
accommodating all the interface cables.
z The connector board should space the hollow to the SCU convection for air
z The connector board is mounted in the room 1U×2U at the top of the SCU.
z The shelf has a 1U×2U panel for the connector board.
z One RS232 and Ethernet ports are located at the front of the connector board.
z The shelf has two rails for supporting the connector board
The appearance and dimensions (unit: mm) of the rectifier are illustrated in the following figure.

Dimensions (H × W % D): 124.3mm % 84mm % 287mm
The functions of the indicators in front panel are listed in Table 1-3.
flowing · Figure 1-4 Dimensions

Chapter 1 System Description 7
Table 1-3 Function of indicators
LED Normal Abnormal Cause of abnormality
OFF No AC Mains Supply Power indicator (green) ON
Blinking Rectifier is under control by SCU
ON AC input over/under voltage, PFC over/under voltage and over temperature Protection indicator (yellow) OFF
Blinking Communication of rectifier with SCU failure
ON Output Over-voltage Alarm indicator (red) OFF

Figure 1-5 Outline of SCU
Dimension (H % W % D):132mm % 85mm % 287mm
SCU communicates with MC (Main Computer) through the RS232/MODEM communication port and 8 groups of alarm dry contacts on the Signal Junction Board.
SCU supports both China Telecom Communication Protocol and EEM Protocol. Make sure that the baud rates for receiving and transmitting are set to be consistent when using SCU.
RS232 communication mode is mainly used for short-distance point-to-point communication. The communication distance shall be less than 15m. If SCU communicates with MC through RS232, just connect SCU RS232 port to the RS232 port of MC.
Blinking Fan Failure

8 Chapter 1 System Description
When SCU communicates with MC through MODEM or ES-MOD, it uses PSTN to realize long-distance monitoring. Power supply cables and communication cables shall be prepared for the communication through MODEM.
SCU has 8 dry-contact outputs. Every dry-contact output has NC (normally closed) and NO (normally-open) contacts. Every dry-contact output shall be configured before the alarm event occurs. Different dry-contact output can trigger different alarms. Once the alarm event occurs, the dry-contact will close or open to generate the alarm.
If the user has other intelligent equipment to be monitored by SCU, the user can connect the dry contacts to the interface of the intelligent equipment, and control the intelligent equipment through these dry contacts.
In RS232 and MODEM communication modes, the MC can fulfill the following functions through SCU:
2. SCU has PLC functions in the alarm management. The PLC is to realize simple logic operation, i.e. the "And", "Or" and "Not" operations. The PLC inputs are all the possible alarm signals, and the PLC outputs can be used to select one of the 8 dry contacts. The alarm categories can be configured flexibly for every dry-contact output through MC. The PLC settings for every dry-contact have three alarm inputs, and two relation flag. The SN of three alarm categories and the mutual logic relationships need to be configured.
PLC can be set to “Disabled”. If PLC functions and alarm co-relation are enabled at the same time, the dry contact will act to activate an alarm when any alarm event occurs.

Chapter 1 System Description 9
The users must input the correct password before they conduct “Maintenance” and “Settings” operations. The password has 3 levels: user, operator or administrator. The authorities of the 3 levels are the same while conducting “Maintenance”, but different in conducting “Settings”. The operator can see 3 more pages than the user, which are “resetting system”, “resetting password” and “modifying system type”. The administrator can see 2 more pages than the operator, which are “modifying password of all levels” and “controlling alarm sound volume”. In addition, the administrator can browse the rectifier parameter serial No., software version and the setting of internal switches. See the following table:
Table 1-4 Authority and default password
Level Authority Default password
User Configuration of general parameters 123456
Operator User’s authority, plus resetting system, resetting password and modifying system type. 654321
Operator’s authority, plus modifying password of all levels, controling alarm sound volume, browsing system parameters that can be set only through the host
The outline and the components of the MFU are illustrated in the following figure.
PE bus OV DC bus
LLVD contactor Bypass bar
Rectifier AC input MCB
Low prior load bus
Figure 1-6 Outline and components of MFU

10 Chapter 1 System Description
Table 1-5 Configuration of MFU
No. Component Description
1 SPD Norminal Dischage Current(8/20μS) 20kA; Ue=385V
2 AC input terminals Rating Current 150A 3 Rectifier AC input MCB Rating Current 25A 4 BLVD contactor 200A or 400A optional 5 LLVD contactor 200A or 400A optional 6 Shunt 300A/75mV 7 Battery MCB 100A MCB (up to 5 battery MCBs can be selected to configure) 8 Load MCB Selected according to user’s requirement
The user can mount the distribution unit into cabinets with widths of 600mm and depths of 400mm and 600mm. It has a height of 4.5U (200mm).
The outline of the Battery Connection Unit (BCU) is illustrated in Figure1-7.
Figure 1-7 Outline of battery connection unit (BCU)
Battery Connection Unit (BCU) can be installed in cabinets with widths of 600mm and depths of 400mm and 600mm. BCU has a maximum height of 1.5U (67mm).
BCU contains 2 to 5 circuit breakers, each with ratings of 100A and 200A.
The BCU will generate an alarm if a battery circuit breaker is off. This alarm shall be possible to connect to the connector board for display in the Controller. It shall be possible to combine the alarms from 2 BCUs to generate a single alarm in the controller. It shall also be possible to combine the alarm from the BCU with an
Enclosure · Battery MCB · -48V DC Bus

Chapter 1 System Description 11
alarm generated from battery circuit breakers that are switched off in the BCU (for example when using a BCU in an extension battery cabinet and battery circuit breakers in the BCU in a main cabinet).
The BCU configuration is as shown in Table 1-6:
Table 1-6 BCU configuration
Item Function unit Amount
100A CB for battery input 2/3/4/5 Battery connection unit
200A CB for battery input 2/3/4/5
There are three kinds of cabinets. Their dimensions are 2.0m % 0.6m % 0.6m, 2.0m
% 0.6m % 0.4m and 0.7m % 0.6m % 0.4m respectively.
2.0m % 0.6m % 0.6m cabinet
This cabinet is installed with 1 % MFU, 1 % Rectifier Sub-rack, 1 % BCU and the following combination of units:
z 16 Blocks of Telion 12V 165Ah FT batteries or 16 % Hawker 12V 155Ah FT
z 20 Blocks of Hawker 12V 105Ah FT batteries
z 16 Blocks of Telion 12V 100Ah FT batteries (20 blocks is preferred, if possible)
z 16 Blocks of Hawker 12V 105Ah Ft batteries and 6U of unspecified equipment
(such as DC/DC converters or similar)
2.0m % 0.6m % 0.4m cabinet
This cabinet accommodates 1 % MFU,1 % Rectifier Sub-rack, 1 % BCU and the following combination of units:
z 16 Blocks of Hawker 12V82F batteries or 16 Blocks of Hawker SBSC11 and
3U available for additional equipment such as DC/DC converters
z 20 Blocks of EB4 batteries
20 blocks of Hawker 12V82F batteries (20 blocks and BCU is preferred, if possible)
0.7m % 0.6m % 0.4m cabinet
This cabinet accommodates 1 % MFU, 1 % Rectifier Sub-racks and 1 % BCU. There shall be 3U available for the mounting of additional equipment such as DC/DC converters. The cabinet should not be installed any battery.
batteries

12 Chapter 2 Installation
2.1 Installation Preparation
Make sure the following environmental conditions are satisfied when selecting the installation site:
Table 2-1 Environmental conditions in power room
Environmental conditions Recommended range
-5~50°C (If ambient temperature > 45°C, for the cabinet with 400mm depth, it should demount the front door of cabinet to ensure the normal operation of the system.)
Sunlight No direct sunlight
Corrosives No pollutants, such as salt, acid, and smoke, etc.
Shake ≤1.5m/s
Insects, pests, and termites None
Fire protection No flammable on the top/bottom of the cabient.
The DC Power system will be damaged if dust or sand accumulates in it. The following measures are recommended for dusty environment:
1.The system should be installed in an airtight and air-conditioned power room. The air-conditioner filter should be well serviced without being obstructed. To reduce the dust in the power room, un-attendance in the power room is recommended.
2.The air filter should be cleaned periodically.
3.The product should be installed on a cement ground.
AC power supply for communication uses AC mains as its main power source. Backup batteries and generator should be configured according to the actual power supply situation. The AC power supply system composed of AC mains and generator should adopt centralized power supply mode to supply power, while low

Chapter 2 Installation 13
voltage AC power supply system should adopt three-phase five-line or single-phase three-line modes.
The AC power cable should adopt copper core cable, and the cable section should suit the load. It is recommended that the power cable outside the power room be buried directly under the ground or by means of cable pipe. Power cable should be wired separately from signal line.
The AC mains voltage shall be within the range of the voltage input range of rectifiers.
The DC power system has a circuit breaker that can cut the AC mains power to it.
The power room must be surveyed prior to installation, which should be focused on:
AC cables: this system uses 3-phase or single-phase AC power. Copper-core flame-retardant PVC insulated cable and PVC sleeve soft cable, such as NH-BVR, are recommended for the AC cables, whose sectional area should suit the load. When the wiring distance is less than 30 meters, take 2.5A/mm2 of economical current density to calculate the sectional area of the AC cables.
The sectional area of the DC load cables and battery cables should be calculated using the following formula:

14 Chapter 2 Installation
In this formula: A is the sectional area of the lead (mm2), ΣI is the total current (A)
flowing through the lead, L is the length (m) of the lead loop, △U is the permitted
voltage drop on the lead, while K is the conductivity. Kcopper=57. For safety, the voltage drop on the cables connecting battery and load cannot exceed 3.2V.
The sectional area of the lightning protection earth cable should not be less than 6mm2, and that of the DC operation earth cable, usually between 35-50mm2, is determined by user. Take the greatest sectional area among the above 3 earth cables as that of the cable connecting the user earth bar.
To ensure smooth installation, the power equipment must be carefully inspected when it is unpacked.
The equipment unpacking and inspection are allowed only after it arrives the installation site. The inspection is co-accomplished by the user representative and representative from Emerson Network Power Co., Ltd.
When inspecting the equipment, first open the packing case with packing list put in it, take out the packing list, and conduct inspection against the packing label, including the customer name, customer address, machine No., total amount, case No., contract No., etc.
Unpacking and inspection: after opening the packing case, check the goods one by one according to the goods list on the packing label. The checking should include:

Chapter 2 Installation 15
Determine the installation position of the power supply cabinet in the power room according to the installation chart. Based on the mechanical specifications (see Fig. 2-1) of the installation holes of the power supply cabinet, determine the accurate position of the center points of the installation holes on the floor, and mark them with a pencil or oil pen.
(Applicable to the cabinet with 600mm depth)
(Applicable to the cabinet with 600mm depth)
Figure 2-1 Installation dimensions of the cabinet base
The expansive pipes delivered with the power system are M10%55mm, therefore,
use electric drill with drill bit Φ12 and depth 70mm to drill holes at the center points of the installation holes marked on the ground. To avoid being off-center, be careful

16 Chapter 2 Installation
not to shake the drill, and try to keep as vertical as possible to the ground, as shown in Figure 2-2.
Clean the dust, and insert the expansive pipe into the reserve hole, knock it down gently using a hammer until the top of the expansive pipe is level with the ground, as shown in Figure 2-2.


Figure 2-2 Installing expansive pipe
Move the cabinet to the installation position aligning the installation holes of the cabinet to the expansive pipe on the ground.
After the cabinet is in position, make some horizontal and vertical adjustments. Insert some iron pieces under the lower edge and corner of the cabinet to adjust the vertical obliquity of the cabinet within 5 degrees. Finally, screw down the tap bolt with plain washer and spring washer into the expansive pipe, and tighten it with wrench. The cabinet fixation is illustrated in Figure 2-3.

Figure 2-3 Fixing cabinet with Tap

Chapter 2 Installation 17
The AC input terminals, SPD, rectifier AC input switch, PE bus and PE terminals are illustrated in Figure 1-6. SPD is just adjacent to the AC input terminals and has been connected in before delivery. PE bus is at the top of the MFU and is connected to the DC Power Cabinet through screws. PE bus is connected PE terminal through a cable.
The AC mains is connected to the AC input terminals directly. There are 6 AC input modes as shown in Table 2-2:
Table 2-2 AC input modes
Item Function unit Amount
1P+N /220V AC input
Terminals only - for individual rectifier AC feeds
2P MCB only - for individual rectifier AC feeds
Strip the insulation layer of one end of the AC input cable, and then mounted the cable end with an H terminal.
The cable mounted with an H terminal is shown in Figure 2-4.
Figure 2-4 Cable mounted with H terminal
After attaching the H terminal to the AC input cable, connect the AC input cable to the AC input terminals as shown in Figure 2-5:

18 Chapter 2 Installation



Figure 2-5 Connection of input terminals
The AC input cable is fed to the system through the top cover of the cabinet, as shown in Figure 2-6:


Cable bracket Top cover
Figure 2-6 Top cover
There is a cable bracket on the top cover. The input cables are bound to the cable bracket with a cable tie.
There are 4 AC input terminals. For 3-phase AC power input, just connect the AC input cables as shown in Figure 2-7:

Figure 2-7 Connection of 3-phase AC power input
AC input terminals · AC input cable · AC input terminals

Chapter 2 Installation 19
For single-phase AC power input, connect the AC input cables as in Figure 2-8:
Figure 2-8 Connection of single-phase AC power input
If the AC input is single phase, the second and fourth terminals are not connected.
For dual-phase AC power input, connect the AC input cables as in Figure 2-9:
Figure 2-9 Connection of dual-phase AC power input
If the AC input is dual-phase, the second and fourth terminals are not connected.
The yellow, green, red, and light blue AC cables correspond respectively to the AC phase L1, L2, L3 and neutral lines. If the cables are the same color, they should be identified with labels.
The AC cables should be laid separately from the DC cables.
No splice, damage, or scratch on the cables is permitted.
The rectifier AC input cables have already been connected in factory.
1.To insure AC input cable has enough bearing current capability, the section area of the AC input cable for 3-phase AC power input should not be less than 10mm2; and for single-phase AC power input and dual-phase AC power, it should not be less than 25mm2. The section area of input earth line should not be less than 35mm2.
AC Input Terminals · AC Input Terminals

20 Chapter 2 Installation
Loads are connected to the MCB with suitable capacity to avoid their failure to function in the case of overload. The capacity of the MCBs is recommended to be about 1.5 times of the peak value of the load capacity. The load circuit breakers are shown in Figure 1-7. The circuit breakers can be ABB or CBI circuit breakers.
We take the CBI circuit breakers of 13mm for example to illustrate the load cable connection, as shown in the Figure 2-10.

connected with high-priority load busbar
connected with low-priority load busbar

High-priority load busbar Battery –48V busbar
Figure 2-10 Connection of load cables
Explanation: the load MCBs and battery MCBs can be configured flexible according to the actual requirements. Their setting range is shown in the following table.
Table 2-3 Configuration number of load MCBs and battery MCBs

Total number of the load should not exceed 20 with 18mm-width MCB or not exceed 28 with 13mm-width MCB.
Battery -48V busbar 0~5 High-priority load busbar 0~19 Low-priority load busbar 0~28
Cable connection to MCB: strip the power cable end, crimp-connect the copper core to an H terminal, See Figure 2-4 for the cable mounted with a H terminal. After attaching the H terminal to the cable, insert the cable into the wiring hole of the MCB, then tighten the screw to fix the copper core, as shown in Figure 2-11:

Figure 2-11 Cable connection to MCB
Low-priority load busbar

Chapter 2 Installation 21
DC output branch should match the load capacity. It is highly recommended to connect priority load to BLVD branch, and normal load to LLVD branch.
There is a connector board in the rectifier shelf. The board is shown in Figure 2-12:

J11

Figure 2-12 Connector board in rectifier shelf
There is an Ethernet port and a DB9 RS232 port on the front panel. For the connection of communication cables, first connect the Ethernet port to the transmission equipment, and then connect the DB9 RS232 port to the Main Computer.
Ethernet Port

22 Chapter 2 Installation

Figure 2-13 Layout of connector board S6415X2

Chapter 2 Installation 23
Table 2-4 Interface definition of connector board S6415X2
Connector Pin Signal name Mark number Logic relation
1 Relay output 1 normal close DO1_NC 2 Relay output 2 normal close DO2_NC 3 Relay output 1 common DO1_COM 4 Relay output 2 common DO2_COM 5 Relay output 1 normal open DO1_NO
6 Relay output 2 normal open DO2_NO 1 Relay output 3 normal close DO3_NC 2 Relay output 4 normal close DO4_NC 3 Relay output 3 common DO3_COM 4 Relay output 4 common DO4_COM 5 Relay output 3 normal open DO3_NO
6 Relay output 4 normal open DO4_NO 1 Relay output 5 normal close DO5_NC 2 Relay output 6 normal close DO6_NC 3 Relay output 5 common DO5_COM 4 Relay output 6 common DO6_COM 5 Relay output 5 normal open DO5_NO
6 Relay output 6 normal open DO6_NO 1 Relay output 7 normal close DO7_NC 2 Relay output 8 normal close DO8_NC 3 Relay output 7 common DO7_COM 4 Relay output 8 common DO8_COM 5 Relay output 7 normal open DO7_NO
6 Relay output 8 normal open DO8_NO 1 Digital circuits power +5V 2 Temperature signal 1 input TEMP1 4~20mA J10
3 Analog ground GND 1 Digital circuits power +5V 2 Temperature signal 2 input TEMP2 4~20mA J11
3 Analog ground GND 1 Data Carrier Detect DCD232 2 Receive Data RXD232 3 Transmit Data TXD232 4 Data Terminal Ready DTR232 5 Data Communication ground DGND 6 Empty 7 Request To Send RTS232
8,9 Empty 1 Ethernet TX+ NETTX+ 2 Ethernet TX- NETTX- 3 Ethernet TR+ NETTR+ 4 Empty 5 Empty 6 Ethernet TR- NETTR-
7~12 Empty

24 Chapter 2 Installation
Connector Pin Signal name Mark number Logic relation
1 RS485 communication+ E485+ 2 RS485 communication- E485- J14
3 Protection ground PGNG 1 48V+ POWER+ J19 2 48V- POWER-
There are two 3-pin terminals on the connector board in rectifier shelf. These two terminals are J11 and J10 respectively. They are used to connect the temperature sensors. The locations of J11 and J10 are as shown in Figure 2-12.
The user can connect the temperature sensor cables to J11 and J10.
Take e-TEK TD-5648DC MODEM for example to illustrate the connection.
Figure 2-14 Input/output interfaces of TD-5648DC MODEM
MODEM connects with M500D monitoring module through connector board S6415X2:
When the cabinet has a front door, before connecting the RS232 terminal, pull out the S6415X2 board first, pass the RS232 terminal through the opening on the right side of the rectifier subrack and connect it with the J18 terminal on the S6415X2 board, then insert the S6415X2 board.
Power

Chapter 2 Installation 25
The M500D monitoring module provides 8 sets of alarm dry contacts through the J3-J6 sockets on the connector board S6415X2. Each set has a normally open contact and a normally closed contact. Once the corresponding alarm event occurs, the dry contact will act to report alarms under the control of M500D monitoring module. Through the dry contact networking, the system can realize the level isolation transmission of fault signals.
When delivery, each set of dry contacts is corresponding to one default alarm type, and users can reset it as other alarm types.
After peeling the signal cable terminal, insert it into the dry contact terminal, then tighten the hold-down bolt to compress the signal cable.
The DC Power System with standard configuration has 4 battery strings. The DC Power System with non-standard configuration can connect to up to 5 battery strings. In the system cabinet, there are 5 levels and each battery string is installed in one level. One battery string has four +12V battery blocks.
Procedures to install battery:
The cabinet with four battery strings installed is shown in Figure 2-15:

26 Chapter 2 Installation
Battery(4 in a string)
Figure 2-15 Cabinet with four battery strings installed
To satisfy the safety requirement of the whole equipment, the fire-retardant class of the battery materials should not be lower than V-2.
Insure that the charge/discharge current of single battery group is not bigger than 100A, and the total charge/discharge current of the all battery groups are not bigger than 200A.
The battery connection for the cabinet with standard configuration is different from that of the cabinet with non-standard configuration.
The DC Power System with standard configuration has no BCU. The system has four battery strings. The negative battery cable is of blue color and the positive one
is of black color. There are two connection methods, one is for the cabinet of 600 %
400 % 700(mm), and another is for the cabinets of 600 % 400 % 2000(mm) and
600 % 600 % 2000(mm).
The four left-most circuit breakers in the MFU connect to the negative battery cables (blue) respectively as shown in Figure 2-16. Another end of the negative
Battery Connection Unit(BCU) · Battery Shelf

Chapter 2 Installation 27
battery cable is connected to the negative terminals of the battery string in each level as shown in Figure 2-16:
4 Battery Circuit Breakers
Figure 2-16 Connection of battery cables.
The connection is show in Figure 2-17:


Figure 2-17 Positive and negative battery cables in each level
One end of positive battery cable is connected to the neutral bus of the DC power cabinet. Another end of the positive battery cable is connected to the positive terminal of the battery string in each level as shown in Figure 2-17.
Negative Battery Cables · Negative battery cable · Positive battery cable

28 Chapter 2 Installation
The actual number of battery circuit breakers in MFU may be 0~5 according to the user’s need.
The DC power system with non-standard configuration has a BCU. The connection of positive cables is the same with that of the system with standard configuration. The only difference is that there are five positive battery cables because the system has five battery strings. One end of positive battery cable is connected to the neutral bus of the DC power cabinet. Another end of the positive battery cable is connected to the positive terminal of the battery string in each level as shown in Figure 2-17.
One end of negative battery cable is connected to the negative terminal of the battery string in each level as shown in Figure 2-17. Another end is connected to the BCU as shown in Figure 2-18. The connection has already been done in factory.

Figure 2-18 Negative battery cables connection in BCU
Since the battery voltage decreases in discharge, hence the sectional area of the cable connecting the battery and the MFU or BCU should be relatively big to keep the voltage drop on the cable within 0.5V.
Negative Battery Cables(Blue)

Chapter 2 Installation 29
In order to prolong the backup time of battery, the battery capacity should be increased. Another cabinet can be connected in parallel with the DC power system cabinet. The expanded cabinet has no rectifier shelf and Multi-Function Unit. It is only installed with battery strings and a BCU. So, it is actually the battery cabinet. BCU in Extension Unit connects to Main Unit through cables. The parallel connection of the DC power system cabinet with the battery cabinet is shown in Figure 2-19:
Figure 2-19 Parallel connection of DC power system cabinet with battery cabinet
The DC cables are connected to the output of the rectifier shelf in the MFU.
Up to two Battery Connection Units (BCUs) can be connected in the DC Power System – up to one BCU in the main cabinet and up to one BCU in an extension battery cabinet.
SCU can display the alarm signals from these two BCUs.
The user can connect the MFU to an additional extension MFU (only for additional load circuit breakers) through suitably rated cables.
Main cabinet · Extension cabinet · Batteries

30 Chapter 3 Startup
3.1 Checking Before Startup
Check the DC Power System according to Table 3-1 before startup.
Table 3-1 System checklist before startup
Item Action Result Comments (fill in
1 Check all the circuit breakers of the shelf and BCU They should be switched off.
2 Check the mains supply fuses/circuit breakers. They should be removed/switched off.
3 Check with an ohmmeter between the positive and negative terminals of battery.
They must be no short circuit (>50ohms)
4 Check with an ohmmeter between the battery terminals and shelf chassis.
They must be no short circuit (>50ohms)
5 Check the battery block voltage and total battery voltage.
The voltages shall correspond to the values given by battery manufacturer.
6 Check the mains phase voltage. The voltage shall be within the rectifier input voltage range (85Vac~290Vac).
7 Check the connection of cables. The cables shall be connected to their correct terminals firmly.
“Ok” or not)

Chapter 3 Startup 31
Item Action Result Comments (Fill
in “OK” or not) The LEDs on the rectifiers and the controller will emit light.
The rectifier fans will start.
The LVD contactors will operate. 1 Connect/switch on the mains supply fuses/circuit breakers of the DC shelf.
The green LEDs of the rectifiers and the controller will flash for about 10 s. and then emit steady light.
The voltage should be close to what has been set in the controller. If temperature compensated charging is activated, the difference may be ±3 V from the set value.
2 Check the DC voltage on the test outlet marked U in the supervision unit.
If temperature compensated charging is activated, warn the sensor on the battery with your hand and observe the system voltage.
The voltage should start to drop.
The battery voltage will increase and reach the system voltage. (Might take hours, depending on the charging state of the battery.)
4 Switch on the battery circuit breakers.
5 Switch on the circuit breakers in MFU. The loads will get DC supply.
6 Check all the LEDs of the shelf. Only the green LEDs are On should emit light. No LED shall flash.
After start up the DC Power System, following parameters need to be configured:
Password, AC parameters, DC parameters, rectifier parameters, battery parameters, time and communication parameters.
Refer to Chapter 5 on how to configure the parameters.

32 Chapter 4 Testing
4.1 Testing MFU
Measure the L-N voltage at the input terminals with a multi-meter to check if it is normal.
If all of the rectifiers can operate normally, switch them on. In case of rectifier malfunction, take the rectifier out and inspect it.
When the rectifiers are operating normally, switch on the SCU, the SCU should start and display the start screen. If the system self-test is normal, seconds later, SCU displays Initial Screen with System Information:
There are default system parameter settings in the SCU, including the AC voltage alarm points, DC voltage alarm points, battery management parameters, which are available on the parameter card delivered with the system. If the battery capacity or charging parameters set by user are different from those on the parameter card, or if user has different BLVD management requirements, please reset the system parameters according to the actual situation, and record the new settings on the parameter card.
2004-09-16

Chapter 4 Testing 33
The BCU can connect to a single battery via suitably sized cables from the Distribution Unit.
The BCU can connect to up to five battery strings via suitably sized cables.
The user can route the battery cables via the left hand side and via the right hand side of the BCU. A maximum of 7 cables can be routed via the left hand side of the BCU and a maximum of 5 cables via the right hand side of the BCU.
The user can mount the BCU 15mm or more above a Front terminal battery. Care shall be taken to connect the battery to the BCU via cables in this orientation.
The user can safely connect battery cables on a live system with only front access. BCU can be partially slid out in order for this to be achieved.
The user can safely install or replace a battery circuit breaker on a live system with only front access. BCU can be partially slid out in order for this to be achieved.
Before connecting load to the system, check with a multi-meter if the connection polarity of the load and the power system is correct and the voltage is normal.

SCU has a LCD with backlight, keys, LEDs and a latch, as shown in Figure 5-1:

Figure 5-1 SCU Front Panel
Functions of LED indicators are illustrated in Table 5-1
Table 5-1 Functions of LED indicators

Critical alarm (Red) Off On There are major or critical alarms
SCU controller uses a 128×64 dot-matrix LCD unit. It has 6 functional keys. Its interface is easy-to-use and supports multi-language display. The panel of the controller is easy-to-remove. The functions of these 6 keys are shown in Table 5-2:
Table 5-2 Functions of SCU keys

Pressing ESC and ENT simultaneously can reset the monitoring module
ENT Enter the main menu or confirm the menu operation
To change a character string whose digits needs setting separately, use
Change values at a value setting interface. At the first page of system information, use these two keys to change LCD contrast.
““ and ““ to move the curso left or
right, or “” and “” to set each digit.

After the system is powered on for the first time, you should set the system type according to the actual configuration. The monitoring module will restart after the system type is changed. In that case, you should re-configure those parameters whose default values are inconsistent with the actual situation. Only after that can the monitoring module operate normally.
After configuring the system parameters, you can carry out various operations directly without resetting the parameter values. As for those important parameters related to battery management, such as BLVD, you should be fully aware of their influence upon the system before you change their values.
For the exact meanings of the abbreviations used in LCD displayer, see Appendix E Glossary.
You can use “”, “”, “” or “” to select the language you want, and press “ENT” to confirm.
Waiting
The system information is shown in many pages. You can repeatedly press “” to view other system information pages in a cycle.
English

Main Menu Status Maintenance Settings
You can press “” or “” repeatedly to select a sub-menu, and press “ENT” to enter the sub-menu. Press “ESC” to return to the menu of higher level.
Including rectifier information, active alarm information and alarm history information.
The maintenance operation can be conducted only when the battery management mode is set to “Manual”. The maintenance includes battery FC, BC and test, load power off/on, battery power off/on and rectifier voltage trimming, current limit, switch control and resetting.
Including the setting of alarm parameter, battery parameter, AC/DC parameter, rectifier parameter and system parameter.
The first system information page contains the major system operation information, including date/time, busbar voltage, total load current, system operation state (normal or alarm), battery management mode (AUTO or MANUAL) and battery state.
Among which, the battery state include FC, temperature compensation, BC, Cyclic Boost, test, short test and scheduled test. The current time are displayed in two pages shifting at the interval of 2s. One page shows year, month and date, the

other shows hour, minute and second. The year is displayed with 4 digits; other time units are in 2 digits.
10:09:16 53.5V 125 A System: No alarm Auto /BC
The system information is shown in many pages. The default page of the monitoring module after the system power on is the system information first page. You can press “” or “” to scroll up or down to view more operation information, as shown in the following page:
They represent respectively the current of the battery that battery shunt 1 and shunt 2 is connected to. If the “Shunt Coeff” of a certain battery group is set to “No”, this situation will be reflected at the battery information page by “Not connected”, and no actual capacity will be displayed.
There is only one current shunt in the system, that is “shunt 1”.

The monitoring module can approximately calculate the remaining battery capacity in real time. Through configuration at the host, the remaining battery capacity can be displayed in the mode of percentage, remaining Ah or remaining time, etc. The default is the percentage.
During the normal BC/FC management, the monitoring module regards the rated capacity as the capacity that each battery group can reach. When the battery discharges, the monitoring module will calculate the battery remaining capacity according to the discharge current, discharge time and the preset “battery discharge curve”. When the battery is being charged, the monitoring module will calculate the real-time battery capacity according to the detected charge current, charge time and preset “battery charge efficiency”. If the calculated battery remaining capacity is higher than the rated capacity, the monitoring module will automatically change the calculated battery remaining capacity to the rated capacity.
There is no AC data acquisition board in ACTURA Flex 48330 Power System,so
the configuration of “AC Input” can only be set to “None”.
System Power:
23% Cyc BC After:
Bat. Temp:
If the monitoring module bans BC and no temperature sensor is configured, this page will not be displayed.
The first line of the information page displays the BC prompts, which will be different with different systems, including:
55h

The 2nd and 3rd rows of the page are the temperature information detected by the temperature sensor. The display will vary with different parameter settings (see 4.7 for parameter setting). If the temperature sensor is not connected or is faulty, system will prompt invalid. Meanwhile, the 4th row will display “Check Temp Sensor”.
The rectifier information includes the rectifier serial No., voltage, current, current limit, mains situation, rectifier power limit and temperature power limit.
Active Alarm Alarm History
The information of every rectifier is displayed in two pages. The information in the first page includes: rectifier serial No., output voltage and current, AC/DC on/off state and AC input voltage. The information in the second page includes: rectifier serial No., current limit, the states of “AC Derated” and “Temp Derated”. Press “” to scroll to the next page, or “” to return to the last.
At most 48 pieces of rectifier’s information can be displayed. If the rectifier does not exist, there will be no information. If the rectifier communication is interrupted, the information will be displayed in high light.
Status Rectifiers

The monitoring module can locate and record the system fault according to the collected data, as well as raise audible/visual alarms and output through dry contact according to the preset alarm level. Meanwhile, it reports the alarms to the host.
You can query historical alarms and active alarms through the LCD of the monitoring module.
When a new alarm is raised, and there is no operation on monitoring module keypad within 2 minutes, the LCD of the monitoring module will prompt automatically the active alarm.
If there are multiple alarms in the current system, you can query alarms through the following steps:
Active Alarm Alarm History
Status Rectifiers · Active Alarm! None

1 Major Alarm AC! Ph-A Failure 040412 12:30:23
The information in the active alarm information pages includes: alarm serial No., alarm level, alarm name and time (year, month, day, hour, minute and second). The alarm raising time determines the sequence it is displayed, with the latest alarm displayed first. Use “” or “” to view all active alarms.
While querying rectifier alarms, press “”, and the rectifier ID will be displayed, and the “Run” indicator of the corresponding rectifier will blink.
Rect ID 02030405
In the case of battery test alarm or maintenance time alarm, press “” to display the prompt information.
In the prompt page, press “ENT” to confirm the alarm.
Active Alarm! 3

Active Alarm Alarm History
If there is no historical alarm, the prompt will be “Alarm History: None”.
The historical alarms of the monitoring module are stored in cyclic order. Up to 200 alarms will be recorded. Above that, the earliest alarm will be cleared automatically.
1Alarm SPD Fault 040411 20:08:30 040411 22:08:30
At the monitoring module, the displayed historical alarm information includes: alarm serial No., alarm name and alarm start/end time (year, month, day, hour, minute, second).
If it is a rectifier that raised the alarm, the ID of that rectifier will be displayed.
Status Rectifiers · ALARM HISTORY None

Table 5-3 Alarm type table
No. Alarm Description Default alarm level
1 Input MCB Trip The system AC input MCB tripped Critical None 2 SPD Fault The SPD circuit is faulty Critical 8 Only in a system with AC sampling board
In a system with AC sampling board, you can name 2 routes; in a system without AC sampling, you can name 8 routes 4 DC/DC Failure Including DC/DC converter fault Critical None
The alarm name is user defined, not longer than 10 characters. The high/low level alarm can be set in the alarm mode.
3 Digit Input Fault
The system AC input voltage is higher than the set value of parameter “OverVolt”
5 AC Over Volt
Critical None Over-voltage alarm
The system AC input voltage is lower than the set value of parameter “LowVolt”
6 Ph-X Volt Low
Critical None Under-voltage alarm
7 Phase failure The AC input voltage of the power system is lower than 80V Critical None
In double-AC auto-switchover system: 1. All AC voltage inputs are lower than 80V. 2. Both AC inputs 1 and 2 are broken. In single AC input system or double-AC manual-switchover system, the AC voltage of all rectifiers are lower than 80V
System DC output voltage is higher than the set value of parameter “Temp Threshold: Over”
9 DC Voltage High
Critical 2 Over-voltage alarm
System DC output voltage is lower than the set value of parameter “Temp Threshold: Under”
Critical 2 Under-voltage alarm
System DC output voltage is lower than the set value of parameter “Temp Threshold: Low”
11 DC Voltage Low
Observation 2 Low-voltage alarm
Battery temperature is higher than the set value of parameter “Temp Threshold: Over Temp”
Major None Over-temperature alarm point
Battery temperature is higher than the set value of parameter “Temp Threshold: High Temp”
Observation None High temperature alarm point
13 Batt Temp High

No. Alarm Description Default alarm level
Battery temperature is lower than the set value of parameter “Temp Threshold: Low Temp”
Observation None Low temperature alarm point
14 Batt Temp Low
15 Amb Temp High Ambient temperature is higher than the set alarm point Observation None
16 Amb Temp Low Ambient temperature is lower than the alarm point Observation None
17 No TempSensor1 Temperature sensor 1 has been set, but no sensor is actually connected Critical None
18 No TempSensor2 Temperature sensor 2 has been set, but no sensor is actually connected Critical None
Temperature sensor 1 detected unreasonable temperature Critical None
20 TempSensor2 Err Temperature sensor 2 detected unreasonable temperature Critical None
21 LLVD 1. Load disconnection 2. Manual load disconnection Critical 5 LLVD enabled
Critical 4 BLVD enabled
23 Load 1 Faiure Over-load, short circuit, manual disconnection or alarm circuit faulty Critical 6
24 Load 2 Faiure Over-load, short circuit, manual disconnection or alarm circuit faulty Critical 6
25 Load 3 Faiure Over-load, short circuit, manual disconnection or alarm circuit faulty Critical 6
26 Load 4 Faiure Over-load, short circuit, manual disconnection or alarm circuit faulty Critical 6
27 Load 5 Faiure Over-load, short circuit, manual disconnection or alarm circuit faulty Critical 6
28 Load 6 Faiure Over-load, short circuit, manual disconnection or alarm circuit faulty Critical 6
29 Load 7 Faiure Over-load, short circuit, manual disconnection or alarm circuit faulty Critical 6
30 Load 8 Faiure Over-load, short circuit, manual disconnection or alarm circuit faulty Critical 6
31 Load 9 Faiure Over-load, short circuit, manual disconnection or alarm circuit faulty Critical 6
32 Aux Load Fails The last route faulty Critical 6
33 Batt1 Failure Over-load, short circuit, manual disconnection or alarm circuit faulty Critical None
34 Batt2 Failure Over-load, short circuit, manual disconnection or alarm circuit faulty Critical None
35 Batt3 Failure Over-load, short circuit, manual disconnection or alarm circuit faulty Critical None

No. Alarm Description Default alarm level
36 Batt4 Failure Over-load, short circuit, manual disconnection or alarm circuit faulty Critical None
The charge current of battery group 1 is bigger than the set value of parameter “Over”
The charge current of battery group 2 is bigger than the set value of parameter “Over”
39 Rect Vac Err All AC voltages are lower than the AC low-volt point Major 3
40 Rect Over Temp Rectifier internal temperature higher than 90°C Observation None
41 Rect Failure Rectifier over-voltage, higher than rectifier high threshold Critical 3
42 Rect Protect AC over-voltage (ƒ295V) or
under-voltage (80V) Observation 3
43 Rect Fan Fails Fan faulty Major 3
AC voltage lower than 176V, with rectifier internal higher than 85°C or temperature at inlet higher than 45°C
45 Rect Com Failure Rectifier and monitoring module communication interrupted Major 3
46 Multi Rect Fail More than 2 rectifiers raised alarms Critical None
47 Self-detect error Error is detected through hardware self-detection No alarm None
48 Manual Mode Battery management in the manual state No alarm None
49 Non-FC Status Including auto-BC, Cyclic Boost, constant current test and short test No alarm 7
50 Batt Discharge Battery being discharging No alarm None
In a system with load shunt, the detected load current plus battery current differs sharply from the rectifier output current
No alarm None Not existent in this
52 Batt Test Error Battery discharge time unexpectedly short Observation None
During the short test, the two batteries discharged more than the set value
53 Short Test Fault
The maintenance FC voltage different from the busbar voltage, or the reported data. The difference is more than 1V
55 System Maintain The pre-set system maintenance time is due Observation None
56 Alarm Block Alarms sent to the host are blocked, valid in EEM-M protocol No alarm None

When the DC load 9 and its above (load 10, load 11 …) have circuit fault alarm, the monitoring module all display “Load 9 Failure” or “Aux Load Fails”.
There are different audible/visual alarms and call back modes for alarms of different levels. For the products in China market, the alarming mode for major alarms and critical alarms are the same.
Table 5-4 Changing audible/visual alarm and alarm call back plan

Critical ON / ON Y Callback No. can be set
Major ON / ON Y Callback No. can be set
Therefore, changing the alarm level of different alarms may change their audible/visual alarm mode and call back plan too.
Pressing any key on the monitoring module can silence the alarm sound. The sound will disappear and alarm indicator will be off when all alarms are cleared.
You can configure how long an alarm sound will last, or choose to make no alarm sound. For details, see 5.7.11 Alarms Settings.
As one of the alarm type parameter, “Related Relay” refers to the serial No. of the dry contract corresponding to the alarm type, whose value is either 1 ~ 8 or “None”. “None” means there is no corresponding dry contact. For details, see 4.7.11 Alarms Settings.
The Programmable Logic Control (PLC) is configured through the host software.
The way to configure the PLC function is:
C = A (Status) * B (Status)
C: The dry contract serial No. of the corresponding output. Range: 1 ~ 8.
A, B: The input alarm type. Status: Whether the alarm has been raised.

*: The logic relationship between the two alarms. Options: “And”/”Or”.
The optional alarm types are listed in the following table:
Table 5-5 Optional alarm types
Alarm Block Load route 1 Load route 2 Load route 3 Load route 4 Load route 5 Load route 6 Load route 7 Load route 8 Load route 9 Auxiliary load route SPD faulty AC input MCB tripped AC route 1 in operation AC route 2 in operation DC/DC faulty
Valid in the double AC inputs auto-switchover power system
Digit Input (DI) 7 DI 8 DC voltage Phase A of AC route 1 Phase B of AC route 1 Phase C of AC route 1 Phase A of AC route 2 Phase B of AC route 2 Phase C of AC route 2
Valid in the double AC inputs auto-switchover power system
Load current Valid in the system with load shunt Battery 1 current Valid in the system with battery shunt Battery 2 current Valid in the system with battery shunt Fuse of battery 1 Fuse of battery 2 Fuse of battery 3 Fuse of battery 4 Temperature detection 1 Temperature detection 2 Monitoring module in operation Used for monitoring module power off Module self test Manual mode Non-FC state of battery Battery discharge Current imbalance Battery short test Battery test alarm LLVD
Alarm type Remark

BLVD Output voltage abnormal AC power off Multiple rectifiers alarm Time for system maintenance (replace the fan) Any rectifier comm interrupted Any rectifier AC power off Any rectifier over-temperature Any rctifier faulty Any rectifier in protection Any rectifier fan faulty Any AC derated rectifier Any temperature derated rectifier
For example: To make dry contact No.3 act when battery route 1 is broken but AC power is still on, the PLC should be configured like this:
A: battery route 1, with “status” set as “Alarm”.
B: AC power off, with “status” set as “No alarm”.
C: Dry contact No.3
*: “AND”.
Connect the serial port of MC to the RS-232 port of SCU, then configure the alarm types that correspond to the dry contact outputs through MC.
An 8 (row) % 6 (column) logic matrix is used in configuring these 8 dry contacts. Every row in the matrix corresponds to one dry contact. The setting of one dry contact has 6 bytes.
Byte 0: The dry contact is disabled if byte 0 is set to 0, and enabled if byte0 is set to 1.
Bytes 1, 3 and 5 are the SN of the 3 alarms respectively. The range of SN is 0-56, see section “5.5.3 Alarm List” for details.
Bytes 2 and 4 define the logic relationship between 3 alarms. The setting of byte 2 or 4 is 0-3. If the setting is 0, the logic is “AND”; If the setting is “1”, the logic is “NOT”; If the setting is “2”, the logic is “OR”; and if the setting is “3”, the logic is “AND”.
Alarm type Remark

Table 5-6 Logic matrix used for configuring 8 dry contacts

Setting 0,1 Alarm SN Logic Alarm SN Logic Alarm SN
The format of PLC setting is AlarmPLC[A][B]=C.
Where, “A” is the row No., and “B” is the column No., and “C” is the value of the matrix element. An example is shown in the following table:
Table 5-7 Example of PLC setting

AlarmPLC[3][0]=1 Elemant value of Row 3 and Column 0 is 1. Use Dry Contact 3
AlarmPLC[3][1]=1 Elemant value of Row 3 and Column 1 is 1. Alarm SN of Fuse 1 Blow up
AlarmPLC[3][2]=3 Elemant value of Row 3 and Column 2 is 3. AND Logic
AlarmPLC[3][3]=2 Elemant value of Row 3 and Column 3 is 2. Alarm SN of Fuse 2 Blow up
AlarmPLC[3][4]=3 Elemant value of Row 3 and Column 4 is 3. OR Logic
AlarmPLC[3][5]=43 Elemant value of Row 3 and Column 5 is 43. Alarm SN of LLVD
For the above PLC setting: When alarms of “Fuse 1 Blow up” and “Fuse 2 Blow up” occur at the same time, or LLVD occurs, dry contact 3 will output the alarm signal.
Relationship between PLC SN and Alarm:
Table 5-8 PLC SN and Alarm

0 Alarm Block Disabled for China Market, Enabled for rest of world

SN
6 Load 6 Failure
7 Load 7 Failure
8 Load 8 Failure
9 Load 9 Failure
10 Aux Load Fails Load 10 is Auxiliary Load for China Market
11 SPD Fault Enabled when an AC Signal Acquisition Board is installed.
12 Input MCB Trip Enabled when an AC Signal Acquisition Board is installed.
13 Flag of Effective AC Input Flag of Effective AC Input
14 Flag of Effective AC Input Flag of Effective AC Input
15 DC/DC Failure Enabled when an AC Signal Acquisition Board is installed.
16 Digital Input 6
17 Digital Input 7
18 Digital Input 8
20 Phase A of AC 1 Enabled when an AC Signal Acquisition Board is installed.
21 Phase B of AC 1 Enabled when an AC Signal Acquisition Board is installed.
22 Phase C of AC 1 Enabled when an AC Signal Acquisition Board is installed.
23 Phase A of AC 2 Enabled when an AC Signal Acquisition Board is installed.
24 Phase B of AC 2 Enabled when an AC Signal Acquisition Board is installed.
25 Phase C of AC 2 Enabled when an AC Signal Acquisition Board is installed.
26 Load Current Enabled when a load shunt is connected in DC Power System
27 Batt1 Curr Enabled when a battery shunt is connected in DC Power System
28 Batt2 Curr Enabled when a battery shunt is connected in DC Power System
35 SCU Working For LVD
40 Curr Imbalance Only for China Market

SN
41 Short Test Error
44 BLVD
47 Multi-Rect Fails Disabled for China Market, Enabled for rest of world
48 Rect Fan Fails
49 Rect Com Failure
50 Rect Vac Err
51 Rect Over Temp
54 Rect Fan Fails
Operation Procedures:
You cannot enter the system Maintenance menu if the “Battery Management” is set to “Auto”.

To input the password, use “” or “” to modify numbers, and use “” or “” to move the cursor. After the input, press “ENT” to confirm.
If the password is incorrect, system will prompt “password incorrect”. If the password is less than 6 digits, end it with a “#”.
You can choose to enter the “Maintenance” menu by using either the user, operator or administrator password, for in this menu, all users have the same authority.
There are two pages:
“Start”: The options include “FC”, “BC” and “Test”. If system is not configured with any battery, the control would be invalid. If there is AC power off alarm, or the busbar voltage is too low, the BC and battery test control will not be executed by the system. No battery test control can be conducted when the rectifier communication is interrupted. Finally, after the battery test, the battery management mode will be changed from “Manual” to “Auto” automatically.
“Battery”: The options include “Reconnect” and “Disconnect”. If there is no battery, or there is a battery alarm, the battery operations will be invalid.
“Load”: The options include “Reconnect” and “Disconnect”.
The following maintenance over the rectifier can be conducted only when the power system is in the FC state.
”RectTrim”: Range: 42V ~ 58V. It can be used to improve the current sharing among rectifiers. Note that the value of this parameter cannot exceed the over-voltage alarm point, or the parameter will be invalid.
”RectLimit”: Range: 10% ~ 121%.

The maintenance operations over a single rectifier include: “DC ON/OFF”, “AC ON/OFF” and “Reset”. The operation method is:
① Use “” or ”” to select the rectifier parameter, and “” or “” to change the
rectifier serial No. Then press “ENT” to confirm. The bottom line of the page displays the rectifier ID.
② Use “” or “” to move the cursor to the maintenance operation area, and
“” or “” to select the value.
If the rectifier voltage is too high, you can select “Reset” to restore the output voltage of that rectifier to normal.
Press ENT to Run Other Key Quit
No Maintain! ESC Quit
Press “ESC” to return to the menu of higher level.
Battery parameters are very important, for they are related to the life of battery. Before delivery, the battery parameters have been initialized. Without any special needs, you only need to reset the battery group number and battery capacity, and accept the defaults for other parameters.
MAIN MENU status
Maintenance Settings

Settings Alarms Settings
Battery Settings AC Settings
Parameter Set DC Settings Rect Settings Sys Settings
Users with different password levels have different authorities. See the following table:
Table 5-9 Password levels and authorities
Level Authority Default password
User Configuration of general parameters 123456
Operator User’s authority, plus resetting system, resetting password and modifying system type. 654321
Operator’s authority, plus modifying password of all levels, controling alarm sound volume, browsing system parameters that can be set only through the host
As shown in the above figure, the monitoring module divides the parameters to be set into 6 kinds: alarms parameter, battery parameter, AC parameter, DC parameter, rectifier parameter and system parameter.
Among which, the battery parameters are divided into 5 kinds: basic, BLVD, charging management, battery test, temperature coefficient, and they are displayed in two pages, as shown below:
Administrator

Battery Setting Batt. Selection
LVD Setting Charge
Battery Setting Batt. Test
What follows is the description of the parameter functions and values by dividing them into 5 small categories and 5 big categories.
Use “” or “” to select the page and the parameter to be set, and “” or “” to select the proper value for the parameter. Press “ENT” to confirm.
After setting the “Battery Type”, the following prompt will appear, asking you to name a certain type of battery for the sake of identifying them:
To name a rectifier, you can use “” or “” to change the number, and “” or “” to move the cursor left or right. Press “ENT” to confirm afterwards.
Temp Comp

Table 5-10 Value description of the basic battery parameters
Parameter Range Defaults Value description
In normal situation, it should be in the “Auto” mode, which enables the monitoring module manage the whole power system automatically, including: Automatic FC/BC switchover, LLVD and BLVC. In the manual mode, you can do operations like BC, FC, test and battery on/off, as well as enabling automatic battery BC time protection and capacity calculation. Upon the system DC under-voltage alarm, system can automatically switch to the “Auto” mode, lest wrong manual operation should damage the system Batt String (number of battery strings)
Mgmt Mode (Management mode)
0 ~ 4 4 You should set this parameter according to the actual battery configuration. If “Batt Shunt” is set as “Y”, there should be batteries actually configured Rated AH (rated capacity) 50 ~ 5000Ah 300Ah The capacity of a single battery string. You should set this parameter according to the actual battery configuration. BTT Name 1# ~ 11# 1# Battery Name 10 characters Name different battery types to identify them Batt Shunt1 Yes
Select “Y” when a corresponding shunt is configured, otherwise, select “N”. Battery management aims at only the batteries connected to the shunt Shunt Coeff (shunt coefficient)
Batt Shunt2 Yes, No No
In the system type setting, if the parameter “Shunt” is set to “Y”, this parameter will be displayed. Otherwise this parameter will take the default value, and is the same for both battery strings.
Dependent on system type
LLVD means the monitoring module opens the LLVD contactor, so that the non-priority load will be powered off. In this way, the battery remaining capacity can sustain the priority load longer.
BLVD means the monitoring module opens the BLVD contactor. In this way, the battery will stop powering the load, preventing over-discharge.
Auto, Manual Auto

Use “” or “” to select one page or one of the parameters, and “” or “” to select the parameter value. Press “ENT” to confirm and save.
Generally you do not need to set the LVD parameters’ value. The defaults will do.
Table 5-11 Value description of the LVD parameters
Parameter Range Default Value description
LLVD Enable Select “Y” to enable LLVD function BLVD Enable Y, N Y Select “Y” to disable the BLVD function
LLVD Mode Time, voltage Voltage
Select “Voltage”, when the monitoring module detects that the battery voltage is lower than the prestet “LLVD Volt”, the load will be disconnected, and so is the battery when the battery voltage is lower than the preset ‘BLVD Volt”. Select “Time”, when the discharge time reaches the preset “LLVD Time”, the monitoring module will disconnect the load; when the discharge time reaches the preset “BLVD Time”, it will disconnect the battery
LLVD Volt 44.0V BLVD Volt 40V ~ 60V 43.2V LLVD Time 300min
3 ~ 1,000 min 600min
· · BLVD Time

Use “” or “” to select one page or one of the parameters, and “” or “” to select the parameter value. Press “ENT” to confirm and save.
Generally you do not need to set the management value. The defaults will do.
· ·

Table 5-12 Charging management parameter value description
Parameter Range Default Value description
Float 53.5V In the FC state, all rectifiers output voltage according to the set “Float”
The “Boost” must be higher than the “Float”
42V ~ 58V 56.4V In the BC state, all rectifiers output voltage according to the set “Boost”
When the monitoring module detects that the battery charging current is higher than the “Limit”, it will control the current of the rectifiers, through which it can limit the battery charging current. C10 is the battery rated capacity, generally set to 10 ~ 20% of the rated capacity of one battery string.
Limit (current limit) 0.1 ~ 0.25C10 0.1C10
When the monitoring module detects that the battery charging current is higher than the “Over”, it will raise the battery charge over-current alarm.
Over (over current point) 0.3C10 ~ 1.0C10 0.300C10
Automatic Boost Select “Y”, and BC will be conducted when conditions allow
Select “Y”, and the monitoring module will control the system to enter the Cyclic Boost when the FC time reaches the “Cyclic Boost Interval”. The battery charging voltage is the preset “Boost”, and the time is the preset “Cyclic Boost Time”
Cyclic Boost Interval 48 ~ 8760h 2400h
Cyclic Boost Time 30 ~ 2880min 720min
To Boost Current 0.50 ~ 0.80C10 0.06C10
The monitoring module will control the system enter the BC state when the battery capacity decreases to the value of “To Boost Capacity”, or when the charge current reaches the “To Boost Current”. The charge voltage will be the “Boost”. Constant BC Curr 0.02 ~ 0.99C10 0.01C10 Duration (of constant BC) 30 ~ 1440min 180min
To Boost Capacity 0.1 ~ 0.95 0.80
The system in the BC state will enter the FC state when the charge current decreases to the “Constant BC Curr” and after the “Duration”. The battery charge voltage then will be the “Float”.
To ensure safety, the monitoring module will forcefully control the system to enter the FC state if during the BC state, the BC time reaches the “Boost Limit”, or abnormalities occur (such as AC failure and battery route faulty, etc.).
Boost Limit 60 ~ 2880min 1080min

Figure 5-2 BC/FC switchover diagram
Boost · Yes, No Y · Cyclic Boost

Use “” or “” to select one page or one of the parameters, and “” or “” to select the parameter value. Press “ENT” to confirm and save.

Table 5-13 Value description of the battery test parameters
Parameter Range Default Value description
The monitoring module can do battery test, and record 10 sets of test data (accessible only through the host). The battery test has to be started manually, then monitoring module will control the rectifier output voltage, make it lower than the battery voltage, and the battery discharge will begin. Monitoring module will stop the test if the battery voltage reaches the “Battery test voltage”, or the discharge time reaches “Battery test time”, or the battery capacity reaches “Test End Cap”. Afterwards, it will restore the rectifier output voltage to the normal FC voltage, begin the battery charge and switch the system to battery auto-management. Meanwhile the test start time/voltage and end time/voltage and battery remaining capacity will be recorded. The records can be queried through the host. During the battery test, if abnormalities occur, the monitoring module will stop the battery test automatically. Scheduled Test Y, N Y Planned Test 1 00:00, Jan. 1st Planned Test 2 00:00, April 1st Planned Test 3 00:00, July 1st Planned Test 4
Battery test time 5 ~ 1440min 300min
Test End Cap (capacity)
0 .95C 10 0.7C 10
When the parameter “Scheduled Test” is set to “Y”, the monitoring module will test the battery according to the 4 sets of test time. You can set at most 12 sets of test time through the host.
00:00, Oct. 1st
Alarm Current 1A ~ 100A 10A ShortTest Cycle 24h ~ 8,760h 720h
If the battery have not discharged within the “ShortTest Cycle”, the monitoring module will start a short test, whose operation time is set by the parameter “ShortTest Duration”. By the end of the test, if the difference in the discharge currents of batteries is bigger than the “Alarm Current”, the battery discharge imbalance alarm will be raised. This alarm will automatically end after 5min of delay. Also you can end it by confirming it. StableTest Enable Y, N
ShortTest Duration 1 ~ 60min 5min
The stable test is conducted with constant battery current, whose value is set through the parameter “StableTest Current”. If the parameter “StableTest Enable” is set to “Y”, and the test will be started once the battery satisfies the test condition
StableTest Current 0 ~ 9999A 9999A
Rectifier output voltage lower than
Battery Auto-management Manually start battery test
battery voltage Battery discharges
"Test End Cap" is
"Test End Time" is
Figure 5-3 Schematic diagram of the test function

Use “” or “” to select one page or one of the parameters, and “” or “” to select the parameter value. Press “ENT” to confirm and save.
Table 5-14 Value description of temperature compensation coefficient
Parameter Range Default Value description
The “Ambient Temp” and “Battery Temp” refer to the measurement of the ambient or battery temperature sensor at the local power system. “None” means there is no measurement input. You should set the parameter according to the actual situation. The temperature measurement data will be displayed in the system operation information screen. Center Temp 10°C ~40°C 25°C When Temp 1 or Temp 2 is set to “Battery Temp”
Ambient Temp, None, Battery Temp None
Batteries are sensitive to temperature. To ensure battery’s capacity and life, its FC voltage should change together with the temperature: lower FC voltage for higher temperature, and vice versa.
The default is 72mV/°C for 48V system and 36mV/°C for 24V system.
Upon alarms such as “Rect Com Failure”, “DC Under-volt” and “DC Voltage High”, the monitoring module will not do temperature compensation to the battery FC voltage. Set this parameter according to the actual battery technical parameters

Parameter Range Default Value description
When Temp 1 or Temp 2 is set to “Battery Temp”
Over 10 C ~ 100 C 50°C When the detected battery temperature is higher than the “Over”, the monitoring module will raise an alarm
The “High” must not be higher than the “Over”
High 10°C ~ 100°C 50°C When the detected battery temperature is higher than the “High”, the monitoring module will raise an alarm
Low -40°C ~ 10°C 0°C The monitoring module will raise an alarm when the detected battery temperature is lower than the “Low”
Use “” or “” to select one page or one of the parameters, and “” or “” to select the parameter value. Press “ENT” to confirm and save.
Table 5-15 Value description of AC settings
Parameter Range Default Value description
OverVolt 50V ~ 300V 280V The monitoring module will raise an alarm when the AC input voltage is higher than the “OverVolt”
The “OverVolt” must be higher than the “LowVolt”. To avoid alrm disorder, it is suggested to use the default values
LowVolt 50V ~ 300V 170V The monitoring module will raise an alarm when the AC input voltage is lower than the “LowVolt”.
The monitoring module will raise an alarm when the AC voltage of an operating route is lower than the “UnderVolt”, but there will be no alarm when the AC voltage of the standby route is lower than the “UnderVolt”
UnderVolt 50V ~ 300V 80V
The “UnderVolt” must be lower than the “LowVolt”.
3-phase, Single Phase, None
Dependat on system type
Set this parameter according to the actual situation. In a system with an AC sampling board, you can only select “Single Phase” or “3-phase”; in a system without an AC sampling board, you can select only “None”.
AC Input

Load Shunt None Shunt Coeff: None
Use “” or “” to select one page or one of the parameters, and “” or “” to select the parameter value. Press “ENT” to confirm and save.
Table 5-16 Value description of DC settings
Parameter Range Default Value description
Over (over-voltage) 58.5V The “DC Over Voltage” alarm will be raised when the system DC output voltage is higher than the value of “Over”
The values of these three parameters should be: Over > Low > Under
Low (low-voltage) 45.0V The DC low voltage alarm will be raised when the system DC output voltage is lower than the value of “Low”
45.0V The DC under voltage alarm will be raised when the system DC output voltage is lower than the value of “Under”
10°C ~ 100°C 40°C The high temperature alarm will be raised when the detected ambient temperature is higher than the value of “High”
The value of parameter “High” must be higher than that of parameter “Low”
The low temperature alarm will be raised when the detected ambient temperature is lower than the value of “Low”
Load shunt Y, None None Set according to the system actual situation
Shunt Coeff Dependent on system type
In the system with a load shunt, this parameter can be set only when the parameter “Shunt” (as a system type) is set to “Set”.
Under (under-voltage) · High (high temperature) · Low (low temperature)

Walk-in Enabled N Walk-in Time: 8s
Fan Speed Full Speed HVSD Time: 300s
Use “” or “” to select one page or one of the parameters, and “” or “” to select the parameter value. Press “ENT” to confirm and save.
Table 5-17 Value description of rectifier settings
Parameter Range Default Value description
Rect Over Volt 56V ~ 59V 59V The rectifier over voltage alarm will be raised when the rectifier output voltage is higher than the “Rect Over Volt” Default Volt 48V ~ 58V 53.5V
The “Default Volt” must be lower than the “Rect Over Volt”
Walkin Enabled Y, N N Walkin Time 8s ~ 128s 10s The output soft start function means the rectifier voltage will rise from 0V to the “Default Volt” after the “Walkin Time”
When set to “Half Speed”, the rectifier will regulate the fan speed according to the temperature. When set to “Full Speed”, the fan will operate at full speed
Fan Speed Full Speed, Half Speed
The rectifier will shut off automatically upon over-voltage, and restart after a certain delay to see whether it is still over-voltage then. That delay is set through the parameter “HVSD Time”. If the rectifier’s output voltage is normal within the delay, the rectifier is regarded normal; otherwise, the rectifier will be locked out and auto-restart function will be disabled
HVSD Time 50s ~ 300s 300s
Half speed

Users of different password levels have different authorities.
17:30:30
Use “” or “” to select one page or one of the parameters, and “” or “” to select the parameter value. Press “ENT” to confirm and save.
When the “CommMode” is “modem” or “EEM-M”, the “CallBack Number” and “CallBack Num” (how many times should callback be made) should be set.
Use “” or “” to change the number, and “” or “” to move the cursor left or right. Press “ENT” to confirm.

There will be a prompt when resetting the system:
Change Password:
Code Con Alarm Voice:
You can change the value of “Change Password” and press “ENT” to confirm.
Use “” or “” to change the number, and “” or “” to move the cursor left or right. Press “ENT” to confirm. You should input the same number twice to complete the setting.
1 Hour · Input Again!

Table 5-18 Value description of system settings
Parameter Range Default Value description
Text Chinese, English and Spanish Chinese Set according to your need
Address 1 ~ 254 The addresses of power systems that are at the same monitored office should be different
“MODEM”: Through modem and based on the Telecom protocol. “EEM-M”: Through modem and based on the EES protocol. “RS-232”: Through a transparent serial port and based on the Telecom protocol
CommMode modem, EEM-M, RS-232
BaudRate 1200bps, 2400bps, 4800bps, 9600bps Make sure the baud rates of both the sending and receiving parties are the same
CallBack Num. 1 ~ 10 3 When “CommMode ” is set to “MODEM” or “EEM-M”
Set according to the actual need. In a extension system, sometimes you need to put a “,” between the main number and extension number. When the callback number is less than 19 digits, end it with a “#”
CallBack Number 19 digits at most
Set Date 2,000 ~ 2,099
Set the time according to the current actual time, regardless of whether it is a leap year or not
Set Time Hour, min, sec
Initialize password Y, N N Selecting “Y” can reset the user level and administrator level passwords to the defaults Operator level or above
When the system parameters cannot be set normally, and the usual resetting methods do not work, you can set the “Init Param” to Y, and all the system parameters will be restored to defaults. Alarms may be raised for the defaults may fail to meet the actual situation. Set the parameters according to the actual situation then.
Init Param (Initialize parameter s)

Parameter Range Default Value description
Operator level or above
24V/75A/500/NONE 24V/75A/500/MAN 24V/75A/500/AUTO 24V/50A/500/NONE 24V/50A/500/MAN 24V/50A/500/AUTO 48V/50A/500/NONE 48V/50A/500/MAN 48V/50A/500/AUTO 48V/50A/300/NONE 48V/50A/300/MAN 48V/50A/300/AUTO 48V/30A/300/NONE 48V/30A/300/MAN 48V/30A/300/AUTO 48V/30A/100/NONE 48V/30A/100/MAN 48V/30A/100/AUTO 48V/15A/100/NONE 48V/15A/100/MAN 48V/15A/100/AUTO 48V/100A/SET/NON 48V/100A/SET/MAN 48V/100A/SET/AUT 48V/50A/SET/NONE 48V/30A/SET/NONE
This parameter has been set according to the actual situation upon delivery and needs not to be changed. However, when a new monitoring module is used, its “System Type” should be set according to the actual situation. After this parameter is changed, the monitoring module will restart automatically, and other parameters of the monitoring module will be changed to the defaults of the corresponding system type. You should change some parameters according to the actual situation.
Change Password User, Operator, Admin The password can be 6 digits long at most. If it is shorte than 6 digits, end it with a “#”
3min, 10min, 1h, 4h, constant Contstant The period that an alarm sound will last
Serial The production serial No. of the monitoring module. This parameter cannot be changed
SW Ver The software version No. of the monitoring module. This parameter cannot be changed Administrator
Reflecting the jumper status of a hardware switch within the monitoring module. If this parameter is set to ”N”, you are not allowed to use the jumper, nor change any parameter except the battery management mode. The maintenance over the monitoring module will not be affected
No AC data acquisition board
System shunt coefficient:
Figure 5-4 System model description
System Type · Con Alarm Voice · Set Enable

The relationship between the system model and system type is listed in the following table:
Table 5-19 Relationship between system model and system type
Power system model System type
PS48400-3/2900, Single AC Input 48V/50A/300/NONE PS48400-3/2900, Double AC Inputs, Manual Switchover 48V/50A/300/MAN PS48400-3/2900, Double AC Inputs, Auto Switchover 48V/50A/300/AUTO PS48600-3/2900, Single AC Input 48V/50A/500/NONE PS48600-3/2900, Double AC Inputs, Manual Switchover 48V/50A/500/MAN PS48600-3/2900, Double AC inputs, Auto Switchover 48V/50A/500/AUTO
SCU can monitor multiple power systems made by Emerson. If the system type is not set correctly, unpredictable faults may occur.
Alarm Settings Alarm Type
Alarm Mode Alarm Control
There are 3 submenus. Use “” or “” to select one, and use “ENT” to confirm.

Use “” or “” to select one page or one of the parameters, and “” or “” to select the parameter value. Press “ENT” to confirm and save.
DI Name Digital 1
Use “” or “” to change the number, and “” or “” to move the cursor left or right. Press “ENT” to confirm.
Table 5-20 Value description of alarm settings
Parameter Range Default Value description
Alarm Type 56 names of alarm events
Alarms of different types have different levels and different Relate Relays
Select those alarm events whose levels and relate relays should be reset
Level Critical, Major, Observation, None
There are different audible/visual alarm modes and callback modes for alarm events of different levels
“Empty”: The corresponding dry contact will not output alarm information upon an alarm event “No. 1 ~ 8”: There will be a dry contact in the range of No.1 ~ 8 that outputs the alarm information upon an alarm event
Relate Relay Empty, No.1 ~ 8
DI No. No. 1 ~ 8 1 The 8 corresponding connecting terminals, queued up in the order that the hardware switches are put
“High”: alarm upon high level; “Low”: alarm upon low level. Set according to the actual situation
Alarm Mode High, Low Low
Effective only to self-defined DI alarms
Set DI Name 1# ~ 8# 1# Serial No. of the connecting terminal for DI input
When there are DI alarms, this parameter shows the alarm name you have actually defined. In the system with an AC sampling board, you can define by yourself the DIs of routes No.7 and No.8. In the system without an AC sampling board, you can define all DIs
DI Name Figures or letters, 10 at most Digital
Clear His Alarm Y, N N “Y”: Delete historical alarms
Block Alarm Y, N N “Y”: The active alarms will not be sent to the host (valid in EEM protocol)

72 Chapter 6 Routine Maintenance
6.1 Maintenance Of Rectifier
The fan of rectifier shall be maintained periodically.
The fan shall be replaced if it does not work due to faults.
Follow the procedures below to replace the fan:
If any SCU fault affects the normal operation of DC power system, just turn off the SCU.
If some of the loads have short circuit fault, just turn off the circuit breakers in the MFU to disconnect the power to the loads.
When MFU short-circuit occurs, disconnect the AC power supply, isolate the batteries from the system, and then use battery or rectifier to directly supply power to load.

Chapter 6 Routine Maintenance 73
The Multi-Function Unit has a cover plate to protect the load and battery circuit breakers and to create a neat finish. This cover plate is easy to open/remove in order to switch on or off a circuit breaker, or to connect additional loads. The cover plate can be opened or removed without the need of using special tools. The DC section of the Distribution Unit is made safe for a “User” to access, which follows the “Look and Feel” guidelines.
During storage, the capacity of the battery decreases because of self-discharging. When using a stored battery, always carry out supplementary charging before use. Refer to the battery user manual or follow battery manufacturer’s advices to perform supplementary charging.
Store the battery in a cool dry place.
Any physical defects (e.g., a cracked or deformed container cover);
Any abnormal heat generation.
The total voltage of the batteries should not deviate from the recommended 2.25 V per cell (54V in a 48V DC power system at reference temperature). If it deviates, check your system to see that the setting is correct and that the temperature compensation is correct.

74 Chapter 6 Routine Maintenance
After one year of operation, all the units should be within the range of 13.50±0.48V.
Replace the battery if its capacity measured during the battery test is less than 80% of the battery rated capacity. The capacity measured during the battery test shall be evaluated at a discharge rate close to its actual use.
The battery is expendable, and has a certain life cycle. Considering the use condition and ambient temperature, the new battery should replace the old battery before it reaches its design life to ensure the normal and safety operation of the DC power system. For instance, in an environment where the mean temperature is 35°C, it is necessary to replace the battery every 5-year operation.

Chapter 7 Troubleshooting 75
7.1 Troubleshooting Rectifier
The usual fault symptoms of the rectifier include: power indicator (green) off, protection indicator (yellow) on, protection indicator (yellow) blinking, alarm indicator (red) on, and alarm indicator (red) blinking.
No input voltage Make sure there is input voltage
Replace the fuse with a new one of the same model or reconnect the input power with correct polarity.
Power indicator (green) off Input polarity reversed or input fuse blown
AC input voltage outside the normal range
Ensure the AC input voltage remain within normal range
PFC over-voltage Replace the rectifier
Current sharing function is disabled Replace the rectifier
Rectifier over-temperature protection, which is caused by:
Protection indicator (yellow) on
Rectifier not inserted into the slot completely Insert the rectifier again properly
Protection indicator (yellow) blinking Rectifier communication failure Check the communication cables
Remove the rectifier from the DC power system, restart the rectifier, and replace the rectifier if over-voltage still occurs.
Alarm indicator (red) on Rectifier over-voltage
Alarm indicator (red) blinking Fan not running Replace the fan
When multiple rectifiers are in parallel connection and the unbalance of current sharing among them is bigger than 3%, check if the communication cables are correctly connected.
Table 7-1 Troubleshooting · Symptom Cause Suggestion

76 Chapter 7 Troubleshooting
If the current sharing is still unsuccessful after the correction, replace the rectifier of which the current sharing function is disabled.
Mains failure often occurs in power system operation. Batteries will provide backup DC power in case of short-period of mains failure. If the cause of mains failure remains unknown or the failure lasts too long, the generator should be started to provide mains supply to the system. It is suggested that the generator should supply power to the power system at least 5 minutes after it is started so as to reduce the effect of the start process on the power system.
Disastrous accidents such as lightning strike, flood, earthquake and fire lead to the communication equipment faults. For the disasters that will severely affect the safety of communications, efforts should be mainly made to prevention actions. Meanwhile, communication stations should have adequate human and material resources and work out effective countermeasures to cope with these disasters. They should also have emergency management regulations and serious accidents emergency plans.

Appendix 1 System Technical Parameters 77
AC input over-voltage alarm point Default: 280 ! 5Vac, cofigurable through monitoring module
AC input over-voltage recovery point
AC input alarm and protection
over-voltage alarm point AC input under-voltage alarm point Default: 180 ! 5Vac, configurable through monitoring module
AC input under-voltage recovery point
under-voltage alarm point DC output over-voltage protection point Default: 59.0 ! 0.2Vdc
DC output over-voltage alarm point
DC output over-voltage recovery point
DC output under-voltage alarm point
DC output alarm and protection
DC output under-voltage recovery point
Output delay Output voltage can rise slowly upon rectifier start up. The rise time is configurable
Fan speed adjustable Rectifier fan speed can be set to half or full speed.
CS RS EN300386 2001, Class A
Immunity to EFT EN61000-4-4, Level 3 Immunity to ESD Air discharge: 8kV. Contact discharge: 4kV. EN61000-4-2
Immunity to Surges EN61000-4-5, Level 4
The AC input side can withstand 10/700μs simulated
lightning voltage 5kV for !5 times, or 8/20μs simulated
Lightning protection features At AC side
lightning surge current 20kA for !5 times, or 8/20μs
simulated lightning surge current 40kA once. The test interval is not smaller than 1 minute.
Acoustic noise 55dB (A) Others
At temperature of 15°C ~ 35°C and relative humidity not higher than 90%RH, apply a test voltage of 500Vdc. The insulation resistances between AC circuit and earth, between DC circuit and earth, or between AC and DC circuits are no less than 10MΩ

78 Appendix 1 System Technical Parameters
(Remove the SPD, monitoring module and rectifiers from the system before the test.) AC to DC circuits, AC circuit to earth: 50Hz, 3,000Vac (RMS). DC circuit to earth: 50Hz, 1,000Vac (RMS). Assistant circuit (not directly connected to the host circuit): 50Hz, 500Vac (RMS). For all the three tests above, there should be no breakdown or flashover within 1min, with leakage current not bigger than 10mA.
Size (mm) 600 (W) % 600 (D)
600 (W) % 400 (D)
% 700 (H) Mechanica
(D) % 2000 (H)
Weight

Appendix 2 Engineering Design Diagram 79
Appendix 2.1 Engineering Design Diagram For
2000mm % 600mm % 600mm Cabinet


80 Appendix 2 Engineering Design Diagram
2000mm % 600mm % 400mm Cabinet

Appendix 2 Engineering Design Diagram 81


AC input terminal H cable terminals, 2-4 pcs (cable section 35mm2)
1 big wire connectors, (cable section 25mm2)
Positive bus bar 4 M8blots, 6 big wire connectors, (cable section 25mm2)
23 small wire connectors, (cable section 16mm2) DC Power distribution
Output route MCB H cable terminals (cable section 25mm2)

Appendix 3 System Circuit Diagram 82

Appendix 3.1 System Electric Schematic Diagram

Appendix 3 System Circuit Diagram 83


Appendix 3 System Circuit Diagram 84


Appendix 3 System Circuit Diagram 85

86 Appendix 4 Glossary
Amb.Temp Ambient Temperature Batt Battery BC Boost Charging BLVD Battery Lower Voltage Disconnection Cap Capacity CommMode Communication Mode CurrLimit Current Limit CycBC Cyclic Boost Charging Con Alarm Voice Control Alarm Voice Hist Alarm Historical alarm HVSD High Voltage Shutdown InitParam Initialize Parameters InitPWD Initialize Password LLVD Load Low Voltage Disconnection LVD Low Voltage Disconnection Ph-A Phase A PWD Password Rect Rectifier Shunt coeff Shunt Coefficient SPD Surge Protection Device SW Version Software Version Sys System Temp Temperature Temp Comp Temperature Compensation Volt Voltage
Abbreviation Full word
Common problems, likely causes, and what to do.
| Problem | Possible cause | Remedy | |
|---|---|---|---|
| Power indicator (green) off | No input voltage | p.85 | |
| Power indicator (green) off | Input polarity reversed or input fuse blown | p.85 | |
| Protection indicator (yellow) on | AC input voltage outside the normal range | p.85 | |
| Protection indicator (yellow) on | PFC over-voltage | p.85 | |
| Protection indicator (yellow) on | Current sharing function is disabled | p.85 | |
| Protection indicator (yellow) on | Rectifier over-temperature protection, which is caused by: | p.85 | |
| Protection indicator (yellow) on | 1. Fan blocked | p.85 | |
| Protection indicator (yellow) on | 2. Ventilation blocked: the inlet or outlet blocked | p.85 | |
| Protection indicator (yellow) on | 3. Ambient temperature too high or rectifier inlet too close to an heater | p.85 | |
| Protection indicator (yellow) on | Rectifier not inserted into the slot completely | p.85 | |
| Protection indicator (yellow) blinking | Rectifier communication failure | p.85 | |
| Alarm indicator (red) on | Rectifier over-voltage | p.85 | |
| Alarm indicator (red) blinking | Fan not running | p.85 |