Emerson 480V

108 pages·9.2 MB·Power Supply·PDF·ENDEFRITNLJA
Emerson 480V
Table of Contents 256 sections Important Safety Instructions · SAVE THESE INSTRUCTIONS · Battery Cabinet Precautions · Glossary of Symbols · … ShowHide
Important Safety Instructionsp.9SAVE THESE INSTRUCTIONSp.9Battery Cabinet Precautionsp.10Glossary of Symbolsp.111.0 Installationp.121.1 External Inspectionsp.121.2 Internal Inspectionsp.131.2.1 Storing for Delayed Installationp.131.3 Preliminary Checksp.131.3.1 Identificationp.131.4 UPS Locationp.131.4.1 Positioning the UPSp.131.4.2 Environmental Considerationsp.13Battery Locationp.141.4.3 Special Considerations for Parallel Systemsp.141.5 Considerations in Moving the Liebert NXp.14Final Positionp.141.6 Mechanical Considerationsp.141.6.1 Clearancesp.151.6.2 Floor Installationp.151.6.3 Cable Entryp.15System Compositionp.151.6.4 Optional Cabinetsp.15Figure 1 Cabinet arrangement-Liebert NX units and battery cabinetsp.16Figure 2 Cabinet arrangement-Liebert NX units, battery cabinets and Liebert FPCp.172.0 Electrical Connectionsp.182.1 Power Cablingp.182.1.1 Cable Ratingp.18Lug Size and Torque Requirementsp.182.1.2 UPS Input Configurationp.19Figure 3 Single module block diagram-dual input configurationp.192.1.3 Cabling Guidelinesp.192.1.4 Cable Connectionsp.20Figure 4 Input and output busbarsp.202.1.5 Safety Groundp.212.1.6 Protective Devicesp.21UPS Rectifier and Bypass Input Supplyp.212.1.7 Cabling Procedurep.22Common Input Connectionsp.22Dual Input Connectionsp.22Output System Connections-Ensure Correct Phase Rotationp.22Frequency Converter Modep.232.2 Control Cablesp.232.2.1 Monitor Board Featuresp.23Figure 5 Monitor board U2p.23Figure 6 Auxiliary terminal block detail (Monitoring Board)p.242.3 Dry Contactsp.242.3.1 Input Dry Contactsp.25Figure 7 Input dry contactsp.25Table 1 Input dry contacts at X3p.252.3.2 Maintenance Bypass Cabinet Interfacep.25Table 2 Maintenance bypass cabinet interfacep.252.3.3 BCB Control Interfacep.26Table 3 BCB control interfacep.26Figure 8 Jumper connection for BCB interface without a battery interface boardp.262.3.4 Output Dry Contactsp.27Figure 9 Output dry contacts and EPO wiring for firmware before M170p.27Table 4 Output dry contact relaysp.272.3.5 EPO Input-Optionalp.28Figure 10 EPO wiringp.28Table 5 EPO input contact relaysp.283.0 Battery Installationp.293.1 Introductionp.293.2 Safetyp.293.3 External Battery Cabinet Installationp.303.3.1 Battery Cabinetsp.30Figure 11 Battery cabinetp.303.3.2 Connecting the Batteriesp.31Figure 12 Battery cabinet-detailsp.313.3.3 Installation Considerationsp.31Figure 13 Battery tray and supportsp.323.3.4 Connecting the Battery Cabinet to the UPSp.323.4 Non-Standard Batteriesp.323.5 BCB Shunt Tripp.323.6 Alber Monitoring System-Optionalp.334.0 Optionsp.344.1 Load Bus Synchronizationp.344.1.1 Performance Requirementsp.344.1.2 LBS Cable and Settingsp.34Figure 14 Load Bus Synchronization cable connection in single module systemsp.34Figure 15 Load Bus Synchronization cable connection with multi-module systemsp.354.2 Configuring Parallel System Operationp.354.2.1 Generalp.354.2.2 Features of Parallel Systemp.35Figure 16 Parallel system block diagramp.364.2.3 Operating Principlesp.36Redundancy Parallelingp.364.2.4 Operation Modes Summaryp.364.3 Installing Parallel Systemp.364.3.1 Conditions for Parallel Systemp.374.3.2 Cabinet Installationp.374.3.3 Preliminary Checksp.374.3.4 Power Cablesp.374.3.5 Parallel Control Cablesp.37Parallel System Control Cablesp.37Figure 17 Connecting system parallel control cablesp.38Auxiliary Dry Contact Cablesp.38Figure 18 Auxiliary dry contact cables for output breaker in multi-module systemp.38Figure 19 Dry contacts, multiple UPS modules with distribution panelp.394.3.6 Emergency Power Off (EPO)p.40Figure 20 Connecting EPO push buttonp.405.0 UPS Specificationsp.415.1 Conformity and Standardsp.415.2 UPS Environmentalp.41Table 6 Environmental characteristicsp.415.3 UPS Mechanical Characteristicsp.41Table 7 UPS mechanical characteristicsp.415.4 UPS Electrical Characteristicsp.42Table 8 UPS terminalp.425.4.1 Input Rectifierp.43Table 9 Rectifier input powerp.43Table 10 Input voltage window with deratingp.43Table 11 Liebert approved replacement batteriesp.435.4.2 DC Intermediate Circuitp.44Table 12 DC intermediate circuitp.445.4.3 Inverter Outputp.44Table 13 Inverter outputp.445.4.4 Bypass Inputp.44Table 14 Bypass inputp.446.0 Installation Drawingsp.45Figure 21 Dimensional viewfront and left side viewsp.45Figure 22 Dimensions continued-top and bottom viewsp.46Figure 23 Main components-typical unitp.46Figure 24 Cable connectionsp.47Figure 25 Outline drawing, 33" battery power pack system, single cabinetp.48Figure 26 Terminal details, 33" battery power pack system, single cabinet Liebert NXp.49Figure 27 Battery connectionsp.50Figure 28 Battery cabinet interconnectionp.51Figure 29 Outline drawing, Liebert NX480V, 80-120kVA Type E and E2 parallel cabinetp.52Figure 30 Outline drawing, Liebert NX480V, 80-120kVA Type E1 parallel cabinetp.53Figure 31 Main component location drawing Liebert NX 480V, Type E parallel cabinetp.54Figure 32 Main component location drawing Liebert NX 480V, Type E1 parallel cabinetp.55Figure 33 Main component location drawing Liebert NX 480V, Type E2 parallel cabinetp.56Figure 34 Lineup detail-Parallel Type E connection to Liebert NXp.57Figure 35 Lineup detail-Parallel Type E1 connection to Liebert NXp.58Figure 36 Lineup detail-Parallel Type E2 connection to Liebert NXp.59Figure 37 Line-up detail, bolt together description, 40-120 kVA Liebert NXp.607.0 Operationp.617.1 General Descriptionp.61Figure 38 Single module block diagram (dual input configuration)p.617.1.1 Bypass Suppliesp.627.1.2 Operating Modesp.62Normal Modep.62Battery Modep.62Bypass Modep.62Maintenance Modep.63Parallel Redundancy Mode (System Expansion)p.63Frequency Converter Modep.638.0 Operator Control and Display Panelp.648.1 Operator Control Panelp.64Figure 39 Overview of control panelp.648.1.1 Display Panel Layoutp.64Figure 40 Detailed view of control panelp.658.2 Mimic Display Indicatorsp.66Figure 41 Mimic display indicators locationp.66Table 15 Mimic display status indicatorsp.668.3 Control Buttonsp.67Figure 42 Location of control buttonsp.67Table 16 Control buttonsp.678.4 Audible Buzzerp.68Figure 43 Buzzer locationp.688.5 LCD Overviewp.68Figure 44 Sections of the LCDp.688.6 Navigation Keysp.69Table 17 Icons for navigation keysp.698.7 UPS System Informationp.69Table 18 Description of items in UPS system windowp.698.8 LCD Menus and Data Itemsp.70Figure 45 Menu treep.70Table 19 Descriptions of UPS menus and data window itemsp.718.9 Language Selectionp.72Figure 46 Language selectionp.728.10 Current Date and Timep.73Figure 47 Set date and timep.738.11 UPS Status Messagesp.74Figure 48 Current status and history log recordsp.748.12 Types of LCD Screensp.758.12.1 Opening Displayp.75Figure 49 Opening displayp.758.12.2 Default Screenp.75Figure 50 Default screenp.758.12.3 UPS Help Screenp.76Figure 51 Help screenp.768.12.4 Screen Saver Windowp.76Figure 52 Screen saver windowp.768.13 Pop-Up Windowsp.778.13.1 From Bypass to Inverter Mode With Power Interruptionp.778.13.2 From Inverter to Bypass Mode With Interruptionp.778.13.3 System Self-Testp.778.13.4 Battery Capacity Test Confirmationp.778.13.5 Battery Self-Test Aborted, Condition Not Metp.778.13.6 Battery Refresh Charge Aborted, Condition Not Metp.779.0 Operating Instructionsp.789.1 Liebert NX Operating Modesp.78Table 20 UPS operating modesp.789.1.1 Circuit Breakersp.79Figure 53 Circuit breakersp.799.2 UPS Startupp.809.2.1 Startup Procedurep.809.2.2 Verify Switching Between Operation Modesp.81Switch from Normal Mode to Battery Modep.81Switch from Normal Mode to Bypass Modep.81Switch from Bypass Mode to Normal Modep.819.3 Maintenance Bypass Procedure and Powering Down the UPSp.829.4 Auto Restartp.839.5 Emergency Shutdown With EPOp.839.6 Reset After Shutdown for Emergency Stop (EPO Action) or Other Conditionsp.839.7 Battery Protectionp.849.7.1 Battery Undervoltage Pre-Warningp.849.7.2 Battery End-of-Discharge (EOD) Protectionp.849.8 Multi-Module System Proceduresp.849.8.1 Isolating One Module in a Multi-Module Systemp.84Figure 54 Typical parallel system block diagram with common input supply, with separate batteries and optional output / bypass distribution panelp.859.8.2 Inserting One Module into a Multi-Module Systemp.869.8.3 Shutdown Procedure-Complete UPS and Load Shutdownp.879.9 Commissioning a Parallel Systemp.879.10 Parallel System Start Upp.8810.0 Optionsp.8910.1 Communication and Other User Terminalsp.89Figure 55 Monitoring board (U2) auxiliary terminal block detailp.8910.1.1 Analog Input Interfacep.8910.1.2 Power Outputp.8910.1.3 Liebert IntelliSlot Communicationp.8910.1.4 Communication and Monitoringp.90Liebert IntelliSlot Web Card - SNMP/HTTP Network Interface Cardp.90Table 21 Liebert NX communication optionsp.9010.1.5 Configuring Baud Ratesp.91Figure 56 Liebert IntelliSlot Web card displayp.92Relay Cardp.93Table 22 Relay Card pin configurationp.93Table 23 Relay card jumper configurationp.93MultiPort 4 Cardp.94Figure 57 MultiPort 4 card pin assignmentp.9410.2 LBS Mode-Load Bus Synchronizationp.9510.2.1 Remote Alarm Monitorp.9510.3 Replacing Dust Filtersp.95Figure 58 Dust filter replacementp.9511.0 Specifications and Technical Datap.9611.1 Lug Size and Torque Requirementsp.96Table 24 Torque specificationsp.96Table 25 Battery torque ratingp.9611.2 Cable Lengths: Floor to Connection Point Inside UPSp.96Table 26 Distance to connection points on the Liebert NX UPSp.97Table 27 Parallel system current tablep.97Table 28 External cabinet dimensions, including side panelsp.98Table 29 Lead/Lag ratingsp.9811.3 Cable size and tightening torquesp.98Table 30 Cable size tightening torque at Liebert NX 40kVA UPS terminalsp.98Table 31 Cable size tightening torque at Liebert NX 60kVA UPS terminalsp.98Table 32 Cable size tightening torque at Liebert NX 80kVA UPS terminalsp.99Table 33 Cable size tightening torque at Liebert NX 100kVA UPS terminalsp.99Table 34 Cable size tightening torque at Liebert NX 120kVA UPS terminalsp.9911.4 Battery Run Timesp.100Table 35 Estimated battery run time, minutesp.100Appendix A - UPS Status Messagesp.101Table 36 UPS status messagesp.101
Page 1 of the Emerson 480V user manual
Page 1 · click to enlarge
Page 1
Emerson 480V diagram (page 1)
Fig. 1
Page 2 of the Emerson 480V user manual
Page 2 · click to enlarge
Page 2
Page 2 of the Emerson 480V user manual
Page 3 of the Emerson 480V user manual — Table of contents
Page 3 · click to enlarge
Page 3

Table of contents

Important Safety Instructionsp.9SAVE THESE INSTRUCTIONSp.9Battery Cabinet Precautionsp.10Glossary of Symbolsp.111.0 Installationp.121.1 External Inspectionsp.121.2 Internal Inspectionsp.131.2.1 Storing for Delayed Installationp.131.3 Preliminary Checksp.131.3.1 Identificationp.131.4 UPS Locationp.131.4.1 Positioning the UPSp.131.4.2 Environmental Considerationsp.13Battery Locationp.141.4.3 Special Considerations for Parallel Systemsp.141.5 Considerations in Moving the Liebert NXp.14Final Positionp.141.6 Mechanical Considerationsp.141.6.1 Clearancesp.151.6.2 Floor Installationp.151.6.3 Cable Entryp.15System Compositionp.151.6.4 Optional Cabinetsp.15Figure 1 Cabinet arrangement-Liebert NX units and battery cabinetsp.16Figure 2 Cabinet arrangement-Liebert NX units, battery cabinets and Liebert FPCp.172.0 Electrical Connectionsp.182.1 Power Cablingp.182.1.1 Cable Ratingp.18Lug Size and Torque Requirementsp.182.1.2 UPS Input Configurationp.19Figure 3 Single module block diagram-dual input configurationp.192.1.3 Cabling Guidelinesp.192.1.4 Cable Connectionsp.20Figure 4 Input and output busbarsp.202.1.5 Safety Groundp.212.1.6 Protective Devicesp.21UPS Rectifier and Bypass Input Supplyp.212.1.7 Cabling Procedurep.22Common Input Connectionsp.22Dual Input Connectionsp.22Output System Connections-Ensure Correct Phase Rotationp.22Frequency Converter Modep.232.2 Control Cablesp.232.2.1 Monitor Board Featuresp.23Figure 5 Monitor board U2p.23Figure 6 Auxiliary terminal block detail (Monitoring Board)p.242.3 Dry Contactsp.242.3.1 Input Dry Contactsp.25Figure 7 Input dry contactsp.25Table 1 Input dry contacts at X3p.252.3.2 Maintenance Bypass Cabinet Interfacep.25Table 2 Maintenance bypass cabinet interfacep.252.3.3 BCB Control Interfacep.26Table 3 BCB control interfacep.26Figure 8 Jumper connection for BCB interface without a battery interface boardp.262.3.4 Output Dry Contactsp.27Figure 9 Output dry contacts and EPO wiring for firmware before M170p.27Table 4 Output dry contact relaysp.272.3.5 EPO Input-Optionalp.28Figure 10 EPO wiringp.28Table 5 EPO input contact relaysp.283.0 Battery Installationp.293.1 Introductionp.293.2 Safetyp.293.3 External Battery Cabinet Installationp.303.3.1 Battery Cabinetsp.30Figure 11 Battery cabinetp.303.3.2 Connecting the Batteriesp.31Figure 12 Battery cabinet-detailsp.313.3.3 Installation Considerationsp.31Figure 13 Battery tray and supportsp.323.3.4 Connecting the Battery Cabinet to the UPSp.323.4 Non-Standard Batteriesp.323.5 BCB Shunt Tripp.323.6 Alber Monitoring System-Optionalp.334.0 Optionsp.344.1 Load Bus Synchronizationp.344.1.1 Performance Requirementsp.344.1.2 LBS Cable and Settingsp.34Figure 14 Load Bus Synchronization cable connection in single module systemsp.34Figure 15 Load Bus Synchronization cable connection with multi-module systemsp.354.2 Configuring Parallel System Operationp.354.2.1 Generalp.354.2.2 Features of Parallel Systemp.35Figure 16 Parallel system block diagramp.364.2.3 Operating Principlesp.36Redundancy Parallelingp.364.2.4 Operation Modes Summaryp.364.3 Installing Parallel Systemp.364.3.1 Conditions for Parallel Systemp.374.3.2 Cabinet Installationp.374.3.3 Preliminary Checksp.374.3.4 Power Cablesp.374.3.5 Parallel Control Cablesp.37Parallel System Control Cablesp.37Figure 17 Connecting system parallel control cablesp.38Auxiliary Dry Contact Cablesp.38Figure 18 Auxiliary dry contact cables for output breaker in multi-module systemp.38Figure 19 Dry contacts, multiple UPS modules with distribution panelp.394.3.6 Emergency Power Off (EPO)p.40Figure 20 Connecting EPO push buttonp.405.0 UPS Specificationsp.415.1 Conformity and Standardsp.415.2 UPS Environmentalp.41Table 6 Environmental characteristicsp.415.3 UPS Mechanical Characteristicsp.41Table 7 UPS mechanical characteristicsp.415.4 UPS Electrical Characteristicsp.42Table 8 UPS terminalp.425.4.1 Input Rectifierp.43Table 9 Rectifier input powerp.43Table 10 Input voltage window with deratingp.43Table 11 Liebert approved replacement batteriesp.435.4.2 DC Intermediate Circuitp.44Table 12 DC intermediate circuitp.445.4.3 Inverter Outputp.44Table 13 Inverter outputp.445.4.4 Bypass Inputp.44Table 14 Bypass inputp.446.0 Installation Drawingsp.45Figure 21 Dimensional viewfront and left side viewsp.45Figure 22 Dimensions continued-top and bottom viewsp.46Figure 23 Main components-typical unitp.46Figure 24 Cable connectionsp.47Figure 25 Outline drawing, 33" battery power pack system, single cabinetp.48Figure 26 Terminal details, 33" battery power pack system, single cabinet Liebert NXp.49Figure 27 Battery connectionsp.50Figure 28 Battery cabinet interconnectionp.51Figure 29 Outline drawing, Liebert NX480V, 80-120kVA Type E and E2 parallel cabinetp.52Figure 30 Outline drawing, Liebert NX480V, 80-120kVA Type E1 parallel cabinetp.53Figure 31 Main component location drawing Liebert NX 480V, Type E parallel cabinetp.54Figure 32 Main component location drawing Liebert NX 480V, Type E1 parallel cabinetp.55Figure 33 Main component location drawing Liebert NX 480V, Type E2 parallel cabinetp.56Figure 34 Lineup detail-Parallel Type E connection to Liebert NXp.57Figure 35 Lineup detail-Parallel Type E1 connection to Liebert NXp.58Figure 36 Lineup detail-Parallel Type E2 connection to Liebert NXp.59Figure 37 Line-up detail, bolt together description, 40-120 kVA Liebert NXp.607.0 Operationp.617.1 General Descriptionp.61Figure 38 Single module block diagram (dual input configuration)p.617.1.1 Bypass Suppliesp.627.1.2 Operating Modesp.62Normal Modep.62Battery Modep.62Bypass Modep.62Maintenance Modep.63Parallel Redundancy Mode (System Expansion)p.63Frequency Converter Modep.638.0 Operator Control and Display Panelp.648.1 Operator Control Panelp.64Figure 39 Overview of control panelp.648.1.1 Display Panel Layoutp.64Figure 40 Detailed view of control panelp.658.2 Mimic Display Indicatorsp.66Figure 41 Mimic display indicators locationp.66Table 15 Mimic display status indicatorsp.668.3 Control Buttonsp.67Figure 42 Location of control buttonsp.67Table 16 Control buttonsp.678.4 Audible Buzzerp.68Figure 43 Buzzer locationp.688.5 LCD Overviewp.68Figure 44 Sections of the LCDp.688.6 Navigation Keysp.69Table 17 Icons for navigation keysp.698.7 UPS System Informationp.69Table 18 Description of items in UPS system windowp.698.8 LCD Menus and Data Itemsp.70Figure 45 Menu treep.70Table 19 Descriptions of UPS menus and data window itemsp.718.9 Language Selectionp.72Figure 46 Language selectionp.728.10 Current Date and Timep.73Figure 47 Set date and timep.738.11 UPS Status Messagesp.74Figure 48 Current status and history log recordsp.748.12 Types of LCD Screensp.758.12.1 Opening Displayp.75Figure 49 Opening displayp.758.12.2 Default Screenp.75Figure 50 Default screenp.758.12.3 UPS Help Screenp.76Figure 51 Help screenp.768.12.4 Screen Saver Windowp.76Figure 52 Screen saver windowp.768.13 Pop-Up Windowsp.778.13.1 From Bypass to Inverter Mode With Power Interruptionp.778.13.2 From Inverter to Bypass Mode With Interruptionp.778.13.3 System Self-Testp.778.13.4 Battery Capacity Test Confirmationp.778.13.5 Battery Self-Test Aborted, Condition Not Metp.778.13.6 Battery Refresh Charge Aborted, Condition Not Metp.779.0 Operating Instructionsp.789.1 Liebert NX Operating Modesp.78Table 20 UPS operating modesp.789.1.1 Circuit Breakersp.79Figure 53 Circuit breakersp.799.2 UPS Startupp.809.2.1 Startup Procedurep.809.2.2 Verify Switching Between Operation Modesp.81Switch from Normal Mode to Battery Modep.81Switch from Normal Mode to Bypass Modep.81Switch from Bypass Mode to Normal Modep.819.3 Maintenance Bypass Procedure and Powering Down the UPSp.829.4 Auto Restartp.839.5 Emergency Shutdown With EPOp.839.6 Reset After Shutdown for Emergency Stop (EPO Action) or Other Conditionsp.839.7 Battery Protectionp.849.7.1 Battery Undervoltage Pre-Warningp.849.7.2 Battery End-of-Discharge (EOD) Protectionp.849.8 Multi-Module System Proceduresp.849.8.1 Isolating One Module in a Multi-Module Systemp.84Figure 54 Typical parallel system block diagram with common input supply, with separate batteries and optional output / bypass distribution panelp.859.8.2 Inserting One Module into a Multi-Module Systemp.869.8.3 Shutdown Procedure-Complete UPS and Load Shutdownp.879.9 Commissioning a Parallel Systemp.879.10 Parallel System Start Upp.8810.0 Optionsp.8910.1 Communication and Other User Terminalsp.89Figure 55 Monitoring board (U2) auxiliary terminal block detailp.8910.1.1 Analog Input Interfacep.8910.1.2 Power Outputp.8910.1.3 Liebert IntelliSlot Communicationp.8910.1.4 Communication and Monitoringp.90Liebert IntelliSlot Web Card - SNMP/HTTP Network Interface Cardp.90Table 21 Liebert NX communication optionsp.9010.1.5 Configuring Baud Ratesp.91Figure 56 Liebert IntelliSlot Web card displayp.92Relay Cardp.93Table 22 Relay Card pin configurationp.93Table 23 Relay card jumper configurationp.93MultiPort 4 Cardp.94Figure 57 MultiPort 4 card pin assignmentp.9410.2 LBS Mode-Load Bus Synchronizationp.9510.2.1 Remote Alarm Monitorp.9510.3 Replacing Dust Filtersp.95Figure 58 Dust filter replacementp.9511.0 Specifications and Technical Datap.9611.1 Lug Size and Torque Requirementsp.96Table 24 Torque specificationsp.96Table 25 Battery torque ratingp.9611.2 Cable Lengths: Floor to Connection Point Inside UPSp.96Table 26 Distance to connection points on the Liebert NX UPSp.97Table 27 Parallel system current tablep.97Table 28 External cabinet dimensions, including side panelsp.98Table 29 Lead/Lag ratingsp.9811.3 Cable size and tightening torquesp.98Table 30 Cable size tightening torque at Liebert NX 40kVA UPS terminalsp.98Table 31 Cable size tightening torque at Liebert NX 60kVA UPS terminalsp.98Table 32 Cable size tightening torque at Liebert NX 80kVA UPS terminalsp.99Table 33 Cable size tightening torque at Liebert NX 100kVA UPS terminalsp.99Table 34 Cable size tightening torque at Liebert NX 120kVA UPS terminalsp.9911.4 Battery Run Timesp.100Table 35 Estimated battery run time, minutesp.100Appendix A - UPS Status Messagesp.101Table 36 UPS status messagesp.101
Page 4 of the Emerson 480V user manual
Page 4 · click to enlarge
Page 4

3.4 Non-Standard Batteries 24 3.5 BCB Shunt Trip 24 3.6 Alber Monitoring System—Optional 25 4.0 OPTIONS 26 4.1 Load Bus Synchronization 26 4.1.1 Performance Requirements 26 4.1.2 LBS Cable and Settings 26 4.2 Configuring Parallel System Operation 27 4.2.1 General 27 4.2.2 Features of Parallel System 27 4.2.3 Operating Principles 28 4.2.4 Operation Modes Summary 28 4.3 Installing Parallel System 28 4.3.1 Conditions for Parallel System 29 4.3.2 Cabinet Installation 29 4.3.3 Preliminary Checks 29 4.3.4 Power Cables 29 4.3.5 Parallel Control Cables 29 4.3.6 Emergency Power Off (EPO) 32 5.0 UPS SPECIFICATIONS 33 5.1 Conformity and Standards 33 5.2 UPS Environmental 33 5.3 UPS Mechanical Characteristics 33 5.4 UPS Electrical Characteristics 34 5.4.1 Input Rectifier 35 5.4.2 DC Intermediate Circuit 36 5.4.3 Inverter Output 36 5.4.4 Bypass Input 36 6.0 INSTALLATION DRAWINGS 37 7.0 OPERATION 53 7.1 General Description 53 7.1.1 Bypass Supplies 54 7.1.2 Operating Modes 54 8.0 OPERATOR CONTROL AND DISPLAY PANEL 56 8.1 Operator Control Panel 56 8.1.1 Display Panel Layout 56 8.2 Mimic Display Indicators 58 8.3 Control Buttons 59 8.4 Audible Buzzer 60 8.5 LCD Overview 60 8.6 Navigation Keys 61 8.7 UPS System Information 61 8.8 LCD Menus and Data Items 62 8.9 Language Selection 64

Page 5 of the Emerson 480V user manual
Page 5 · click to enlarge
Page 5

8.10 Current Date and Time 65 8.11 UPS Status Messages 66 8.12 Types of LCD Screens 67 8.12.1 Opening Display 67 8.12.2 Default Screen 67 8.12.3 UPS Help Screen 68 8.12.4 Screen Saver Window 68 8.13 Pop-Up Windows 69 8.13.1 From Bypass to Inverter Mode With Power Interruption 69 8.13.2 From Inverter to Bypass Mode With Interruption 69 8.13.3 System Self-Test 69 8.13.4 Battery Capacity Test Confirmation 69 8.13.5 Battery Self-Test Aborted, Condition Not Met 69 8.13.6 Battery Refresh Charge Aborted, Condition Not Met 69 9.0 OPERATING INSTRUCTIONS 70 9.1 Liebert NX Operating Modes 70 9.1.1 Circuit Breakers 71 9.2 UPS Startup 72 9.2.1 Startup Procedure 72 9.2.2 Verify Switching Between Operation Modes 73 9.3 Maintenance Bypass Procedure and Powering Down the UPS 74 9.4 Auto Restart 75 9.5 Emergency Shutdown With EPO 75 9.6 Reset After Shutdown for Emergency Stop (EPO Action) or Other Conditions 75 9.7 Battery Protection 76 9.7.1 Battery Undervoltage Pre-Warning 76 9.7.2 Battery End-of-Discharge (EOD) Protection 76 9.8 Multi-Module System Procedures 76 9.8.1 Isolating One Module in a Multi-Module System 76 9.8.2 Inserting One Module into a Multi-Module System 78 9.8.3 Shutdown Procedure—Complete UPS and Load Shutdown 79 9.9 Commissioning a Parallel System 79 9.10 Parallel System Start Up 80 10.0 OPTIONS 81 10.1 Communication and Other User Terminals 81 10.1.1 Analog Input Interface 81 10.1.2 Power Output 81 10.1.3 Liebert IntelliSlot Communication 81 10.1.4 Communication and Monitoring 82 10.1.5 Configuring Baud Rates 83 10.2 LBS Mode—Load Bus Synchronization 87 10.2.1 Remote Alarm Monitor 87 10.3 Replacing Dust Filters 87

Page 6 of the Emerson 480V user manual — Table of contents
Page 6 · click to enlarge
Page 6

Table of contents

Important Safety Instructionsp.9SAVE THESE INSTRUCTIONSp.9Battery Cabinet Precautionsp.10Glossary of Symbolsp.111.0 Installationp.121.1 External Inspectionsp.121.2 Internal Inspectionsp.131.2.1 Storing for Delayed Installationp.131.3 Preliminary Checksp.131.3.1 Identificationp.131.4 UPS Locationp.131.4.1 Positioning the UPSp.131.4.2 Environmental Considerationsp.13Battery Locationp.141.4.3 Special Considerations for Parallel Systemsp.141.5 Considerations in Moving the Liebert NXp.14Final Positionp.141.6 Mechanical Considerationsp.141.6.1 Clearancesp.151.6.2 Floor Installationp.151.6.3 Cable Entryp.15System Compositionp.151.6.4 Optional Cabinetsp.15Figure 1 Cabinet arrangement-Liebert NX units and battery cabinetsp.16Figure 2 Cabinet arrangement-Liebert NX units, battery cabinets and Liebert FPCp.172.0 Electrical Connectionsp.182.1 Power Cablingp.182.1.1 Cable Ratingp.18Lug Size and Torque Requirementsp.182.1.2 UPS Input Configurationp.19Figure 3 Single module block diagram-dual input configurationp.192.1.3 Cabling Guidelinesp.192.1.4 Cable Connectionsp.20Figure 4 Input and output busbarsp.202.1.5 Safety Groundp.212.1.6 Protective Devicesp.21UPS Rectifier and Bypass Input Supplyp.212.1.7 Cabling Procedurep.22Common Input Connectionsp.22Dual Input Connectionsp.22Output System Connections-Ensure Correct Phase Rotationp.22Frequency Converter Modep.232.2 Control Cablesp.232.2.1 Monitor Board Featuresp.23Figure 5 Monitor board U2p.23Figure 6 Auxiliary terminal block detail (Monitoring Board)p.242.3 Dry Contactsp.242.3.1 Input Dry Contactsp.25Figure 7 Input dry contactsp.25Table 1 Input dry contacts at X3p.252.3.2 Maintenance Bypass Cabinet Interfacep.25Table 2 Maintenance bypass cabinet interfacep.252.3.3 BCB Control Interfacep.26Table 3 BCB control interfacep.26Figure 8 Jumper connection for BCB interface without a battery interface boardp.262.3.4 Output Dry Contactsp.27Figure 9 Output dry contacts and EPO wiring for firmware before M170p.27Table 4 Output dry contact relaysp.272.3.5 EPO Input-Optionalp.28Figure 10 EPO wiringp.28Table 5 EPO input contact relaysp.283.0 Battery Installationp.293.1 Introductionp.293.2 Safetyp.293.3 External Battery Cabinet Installationp.303.3.1 Battery Cabinetsp.30Figure 11 Battery cabinetp.303.3.2 Connecting the Batteriesp.31Figure 12 Battery cabinet-detailsp.313.3.3 Installation Considerationsp.31Figure 13 Battery tray and supportsp.323.3.4 Connecting the Battery Cabinet to the UPSp.323.4 Non-Standard Batteriesp.323.5 BCB Shunt Tripp.323.6 Alber Monitoring System-Optionalp.334.0 Optionsp.344.1 Load Bus Synchronizationp.344.1.1 Performance Requirementsp.344.1.2 LBS Cable and Settingsp.34Figure 14 Load Bus Synchronization cable connection in single module systemsp.34Figure 15 Load Bus Synchronization cable connection with multi-module systemsp.354.2 Configuring Parallel System Operationp.354.2.1 Generalp.354.2.2 Features of Parallel Systemp.35Figure 16 Parallel system block diagramp.364.2.3 Operating Principlesp.36Redundancy Parallelingp.364.2.4 Operation Modes Summaryp.364.3 Installing Parallel Systemp.364.3.1 Conditions for Parallel Systemp.374.3.2 Cabinet Installationp.374.3.3 Preliminary Checksp.374.3.4 Power Cablesp.374.3.5 Parallel Control Cablesp.37Parallel System Control Cablesp.37Figure 17 Connecting system parallel control cablesp.38Auxiliary Dry Contact Cablesp.38Figure 18 Auxiliary dry contact cables for output breaker in multi-module systemp.38Figure 19 Dry contacts, multiple UPS modules with distribution panelp.394.3.6 Emergency Power Off (EPO)p.40Figure 20 Connecting EPO push buttonp.405.0 UPS Specificationsp.415.1 Conformity and Standardsp.415.2 UPS Environmentalp.41Table 6 Environmental characteristicsp.415.3 UPS Mechanical Characteristicsp.41Table 7 UPS mechanical characteristicsp.415.4 UPS Electrical Characteristicsp.42Table 8 UPS terminalp.425.4.1 Input Rectifierp.43Table 9 Rectifier input powerp.43Table 10 Input voltage window with deratingp.43Table 11 Liebert approved replacement batteriesp.435.4.2 DC Intermediate Circuitp.44Table 12 DC intermediate circuitp.445.4.3 Inverter Outputp.44Table 13 Inverter outputp.445.4.4 Bypass Inputp.44Table 14 Bypass inputp.446.0 Installation Drawingsp.45Figure 21 Dimensional viewfront and left side viewsp.45Figure 22 Dimensions continued-top and bottom viewsp.46Figure 23 Main components-typical unitp.46Figure 24 Cable connectionsp.47Figure 25 Outline drawing, 33" battery power pack system, single cabinetp.48Figure 26 Terminal details, 33" battery power pack system, single cabinet Liebert NXp.49Figure 27 Battery connectionsp.50Figure 28 Battery cabinet interconnectionp.51Figure 29 Outline drawing, Liebert NX480V, 80-120kVA Type E and E2 parallel cabinetp.52Figure 30 Outline drawing, Liebert NX480V, 80-120kVA Type E1 parallel cabinetp.53Figure 31 Main component location drawing Liebert NX 480V, Type E parallel cabinetp.54Figure 32 Main component location drawing Liebert NX 480V, Type E1 parallel cabinetp.55Figure 33 Main component location drawing Liebert NX 480V, Type E2 parallel cabinetp.56Figure 34 Lineup detail-Parallel Type E connection to Liebert NXp.57Figure 35 Lineup detail-Parallel Type E1 connection to Liebert NXp.58Figure 36 Lineup detail-Parallel Type E2 connection to Liebert NXp.59Figure 37 Line-up detail, bolt together description, 40-120 kVA Liebert NXp.607.0 Operationp.617.1 General Descriptionp.61Figure 38 Single module block diagram (dual input configuration)p.617.1.1 Bypass Suppliesp.627.1.2 Operating Modesp.62Normal Modep.62Battery Modep.62Bypass Modep.62Maintenance Modep.63Parallel Redundancy Mode (System Expansion)p.63Frequency Converter Modep.638.0 Operator Control and Display Panelp.648.1 Operator Control Panelp.64Figure 39 Overview of control panelp.648.1.1 Display Panel Layoutp.64Figure 40 Detailed view of control panelp.658.2 Mimic Display Indicatorsp.66Figure 41 Mimic display indicators locationp.66Table 15 Mimic display status indicatorsp.668.3 Control Buttonsp.67Figure 42 Location of control buttonsp.67Table 16 Control buttonsp.678.4 Audible Buzzerp.68Figure 43 Buzzer locationp.688.5 LCD Overviewp.68Figure 44 Sections of the LCDp.688.6 Navigation Keysp.69Table 17 Icons for navigation keysp.698.7 UPS System Informationp.69Table 18 Description of items in UPS system windowp.698.8 LCD Menus and Data Itemsp.70Figure 45 Menu treep.70Table 19 Descriptions of UPS menus and data window itemsp.718.9 Language Selectionp.72Figure 46 Language selectionp.728.10 Current Date and Timep.73Figure 47 Set date and timep.738.11 UPS Status Messagesp.74Figure 48 Current status and history log recordsp.748.12 Types of LCD Screensp.758.12.1 Opening Displayp.75Figure 49 Opening displayp.758.12.2 Default Screenp.75Figure 50 Default screenp.758.12.3 UPS Help Screenp.76Figure 51 Help screenp.768.12.4 Screen Saver Windowp.76Figure 52 Screen saver windowp.768.13 Pop-Up Windowsp.778.13.1 From Bypass to Inverter Mode With Power Interruptionp.778.13.2 From Inverter to Bypass Mode With Interruptionp.778.13.3 System Self-Testp.778.13.4 Battery Capacity Test Confirmationp.778.13.5 Battery Self-Test Aborted, Condition Not Metp.778.13.6 Battery Refresh Charge Aborted, Condition Not Metp.779.0 Operating Instructionsp.789.1 Liebert NX Operating Modesp.78Table 20 UPS operating modesp.789.1.1 Circuit Breakersp.79Figure 53 Circuit breakersp.799.2 UPS Startupp.809.2.1 Startup Procedurep.809.2.2 Verify Switching Between Operation Modesp.81Switch from Normal Mode to Battery Modep.81Switch from Normal Mode to Bypass Modep.81Switch from Bypass Mode to Normal Modep.819.3 Maintenance Bypass Procedure and Powering Down the UPSp.829.4 Auto Restartp.839.5 Emergency Shutdown With EPOp.839.6 Reset After Shutdown for Emergency Stop (EPO Action) or Other Conditionsp.839.7 Battery Protectionp.849.7.1 Battery Undervoltage Pre-Warningp.849.7.2 Battery End-of-Discharge (EOD) Protectionp.849.8 Multi-Module System Proceduresp.849.8.1 Isolating One Module in a Multi-Module Systemp.84Figure 54 Typical parallel system block diagram with common input supply, with separate batteries and optional output / bypass distribution panelp.859.8.2 Inserting One Module into a Multi-Module Systemp.869.8.3 Shutdown Procedure-Complete UPS and Load Shutdownp.879.9 Commissioning a Parallel Systemp.879.10 Parallel System Start Upp.8810.0 Optionsp.8910.1 Communication and Other User Terminalsp.89Figure 55 Monitoring board (U2) auxiliary terminal block detailp.8910.1.1 Analog Input Interfacep.8910.1.2 Power Outputp.8910.1.3 Liebert IntelliSlot Communicationp.8910.1.4 Communication and Monitoringp.90Liebert IntelliSlot Web Card - SNMP/HTTP Network Interface Cardp.90Table 21 Liebert NX communication optionsp.9010.1.5 Configuring Baud Ratesp.91Figure 56 Liebert IntelliSlot Web card displayp.92Relay Cardp.93Table 22 Relay Card pin configurationp.93Table 23 Relay card jumper configurationp.93MultiPort 4 Cardp.94Figure 57 MultiPort 4 card pin assignmentp.9410.2 LBS Mode-Load Bus Synchronizationp.9510.2.1 Remote Alarm Monitorp.9510.3 Replacing Dust Filtersp.95Figure 58 Dust filter replacementp.9511.0 Specifications and Technical Datap.9611.1 Lug Size and Torque Requirementsp.96Table 24 Torque specificationsp.96Table 25 Battery torque ratingp.9611.2 Cable Lengths: Floor to Connection Point Inside UPSp.96Table 26 Distance to connection points on the Liebert NX UPSp.97Table 27 Parallel system current tablep.97Table 28 External cabinet dimensions, including side panelsp.98Table 29 Lead/Lag ratingsp.9811.3 Cable size and tightening torquesp.98Table 30 Cable size tightening torque at Liebert NX 40kVA UPS terminalsp.98Table 31 Cable size tightening torque at Liebert NX 60kVA UPS terminalsp.98Table 32 Cable size tightening torque at Liebert NX 80kVA UPS terminalsp.99Table 33 Cable size tightening torque at Liebert NX 100kVA UPS terminalsp.99Table 34 Cable size tightening torque at Liebert NX 120kVA UPS terminalsp.9911.4 Battery Run Timesp.100Table 35 Estimated battery run time, minutesp.100Appendix A - UPS Status Messagesp.101Table 36 UPS status messagesp.101
Page 7 of the Emerson 480V user manual — Table of contents
Page 7 · click to enlarge
Page 7

Table of contents

Important Safety Instructionsp.9SAVE THESE INSTRUCTIONSp.9Battery Cabinet Precautionsp.10Glossary of Symbolsp.111.0 Installationp.121.1 External Inspectionsp.121.2 Internal Inspectionsp.131.2.1 Storing for Delayed Installationp.131.3 Preliminary Checksp.131.3.1 Identificationp.131.4 UPS Locationp.131.4.1 Positioning the UPSp.131.4.2 Environmental Considerationsp.13Battery Locationp.141.4.3 Special Considerations for Parallel Systemsp.141.5 Considerations in Moving the Liebert NXp.14Final Positionp.141.6 Mechanical Considerationsp.141.6.1 Clearancesp.151.6.2 Floor Installationp.151.6.3 Cable Entryp.15System Compositionp.151.6.4 Optional Cabinetsp.15Figure 1 Cabinet arrangement-Liebert NX units and battery cabinetsp.16Figure 2 Cabinet arrangement-Liebert NX units, battery cabinets and Liebert FPCp.172.0 Electrical Connectionsp.182.1 Power Cablingp.182.1.1 Cable Ratingp.18Lug Size and Torque Requirementsp.182.1.2 UPS Input Configurationp.19Figure 3 Single module block diagram-dual input configurationp.192.1.3 Cabling Guidelinesp.192.1.4 Cable Connectionsp.20Figure 4 Input and output busbarsp.202.1.5 Safety Groundp.212.1.6 Protective Devicesp.21UPS Rectifier and Bypass Input Supplyp.212.1.7 Cabling Procedurep.22Common Input Connectionsp.22Dual Input Connectionsp.22Output System Connections-Ensure Correct Phase Rotationp.22Frequency Converter Modep.232.2 Control Cablesp.232.2.1 Monitor Board Featuresp.23Figure 5 Monitor board U2p.23Figure 6 Auxiliary terminal block detail (Monitoring Board)p.242.3 Dry Contactsp.242.3.1 Input Dry Contactsp.25Figure 7 Input dry contactsp.25Table 1 Input dry contacts at X3p.252.3.2 Maintenance Bypass Cabinet Interfacep.25Table 2 Maintenance bypass cabinet interfacep.252.3.3 BCB Control Interfacep.26Table 3 BCB control interfacep.26Figure 8 Jumper connection for BCB interface without a battery interface boardp.262.3.4 Output Dry Contactsp.27Figure 9 Output dry contacts and EPO wiring for firmware before M170p.27Table 4 Output dry contact relaysp.272.3.5 EPO Input-Optionalp.28Figure 10 EPO wiringp.28Table 5 EPO input contact relaysp.283.0 Battery Installationp.293.1 Introductionp.293.2 Safetyp.293.3 External Battery Cabinet Installationp.303.3.1 Battery Cabinetsp.30Figure 11 Battery cabinetp.303.3.2 Connecting the Batteriesp.31Figure 12 Battery cabinet-detailsp.313.3.3 Installation Considerationsp.31Figure 13 Battery tray and supportsp.323.3.4 Connecting the Battery Cabinet to the UPSp.323.4 Non-Standard Batteriesp.323.5 BCB Shunt Tripp.323.6 Alber Monitoring System-Optionalp.334.0 Optionsp.344.1 Load Bus Synchronizationp.344.1.1 Performance Requirementsp.344.1.2 LBS Cable and Settingsp.34Figure 14 Load Bus Synchronization cable connection in single module systemsp.34Figure 15 Load Bus Synchronization cable connection with multi-module systemsp.354.2 Configuring Parallel System Operationp.354.2.1 Generalp.354.2.2 Features of Parallel Systemp.35Figure 16 Parallel system block diagramp.364.2.3 Operating Principlesp.36Redundancy Parallelingp.364.2.4 Operation Modes Summaryp.364.3 Installing Parallel Systemp.364.3.1 Conditions for Parallel Systemp.374.3.2 Cabinet Installationp.374.3.3 Preliminary Checksp.374.3.4 Power Cablesp.374.3.5 Parallel Control Cablesp.37Parallel System Control Cablesp.37Figure 17 Connecting system parallel control cablesp.38Auxiliary Dry Contact Cablesp.38Figure 18 Auxiliary dry contact cables for output breaker in multi-module systemp.38Figure 19 Dry contacts, multiple UPS modules with distribution panelp.394.3.6 Emergency Power Off (EPO)p.40Figure 20 Connecting EPO push buttonp.405.0 UPS Specificationsp.415.1 Conformity and Standardsp.415.2 UPS Environmentalp.41Table 6 Environmental characteristicsp.415.3 UPS Mechanical Characteristicsp.41Table 7 UPS mechanical characteristicsp.415.4 UPS Electrical Characteristicsp.42Table 8 UPS terminalp.425.4.1 Input Rectifierp.43Table 9 Rectifier input powerp.43Table 10 Input voltage window with deratingp.43Table 11 Liebert approved replacement batteriesp.435.4.2 DC Intermediate Circuitp.44Table 12 DC intermediate circuitp.445.4.3 Inverter Outputp.44Table 13 Inverter outputp.445.4.4 Bypass Inputp.44Table 14 Bypass inputp.446.0 Installation Drawingsp.45Figure 21 Dimensional viewfront and left side viewsp.45Figure 22 Dimensions continued-top and bottom viewsp.46Figure 23 Main components-typical unitp.46Figure 24 Cable connectionsp.47Figure 25 Outline drawing, 33" battery power pack system, single cabinetp.48Figure 26 Terminal details, 33" battery power pack system, single cabinet Liebert NXp.49Figure 27 Battery connectionsp.50Figure 28 Battery cabinet interconnectionp.51Figure 29 Outline drawing, Liebert NX480V, 80-120kVA Type E and E2 parallel cabinetp.52Figure 30 Outline drawing, Liebert NX480V, 80-120kVA Type E1 parallel cabinetp.53Figure 31 Main component location drawing Liebert NX 480V, Type E parallel cabinetp.54Figure 32 Main component location drawing Liebert NX 480V, Type E1 parallel cabinetp.55Figure 33 Main component location drawing Liebert NX 480V, Type E2 parallel cabinetp.56Figure 34 Lineup detail-Parallel Type E connection to Liebert NXp.57Figure 35 Lineup detail-Parallel Type E1 connection to Liebert NXp.58Figure 36 Lineup detail-Parallel Type E2 connection to Liebert NXp.59Figure 37 Line-up detail, bolt together description, 40-120 kVA Liebert NXp.607.0 Operationp.617.1 General Descriptionp.61Figure 38 Single module block diagram (dual input configuration)p.617.1.1 Bypass Suppliesp.627.1.2 Operating Modesp.62Normal Modep.62Battery Modep.62Bypass Modep.62Maintenance Modep.63Parallel Redundancy Mode (System Expansion)p.63Frequency Converter Modep.638.0 Operator Control and Display Panelp.648.1 Operator Control Panelp.64Figure 39 Overview of control panelp.648.1.1 Display Panel Layoutp.64Figure 40 Detailed view of control panelp.658.2 Mimic Display Indicatorsp.66Figure 41 Mimic display indicators locationp.66Table 15 Mimic display status indicatorsp.668.3 Control Buttonsp.67Figure 42 Location of control buttonsp.67Table 16 Control buttonsp.678.4 Audible Buzzerp.68Figure 43 Buzzer locationp.688.5 LCD Overviewp.68Figure 44 Sections of the LCDp.688.6 Navigation Keysp.69Table 17 Icons for navigation keysp.698.7 UPS System Informationp.69Table 18 Description of items in UPS system windowp.698.8 LCD Menus and Data Itemsp.70Figure 45 Menu treep.70Table 19 Descriptions of UPS menus and data window itemsp.718.9 Language Selectionp.72Figure 46 Language selectionp.728.10 Current Date and Timep.73Figure 47 Set date and timep.738.11 UPS Status Messagesp.74Figure 48 Current status and history log recordsp.748.12 Types of LCD Screensp.758.12.1 Opening Displayp.75Figure 49 Opening displayp.758.12.2 Default Screenp.75Figure 50 Default screenp.758.12.3 UPS Help Screenp.76Figure 51 Help screenp.768.12.4 Screen Saver Windowp.76Figure 52 Screen saver windowp.768.13 Pop-Up Windowsp.778.13.1 From Bypass to Inverter Mode With Power Interruptionp.778.13.2 From Inverter to Bypass Mode With Interruptionp.778.13.3 System Self-Testp.778.13.4 Battery Capacity Test Confirmationp.778.13.5 Battery Self-Test Aborted, Condition Not Metp.778.13.6 Battery Refresh Charge Aborted, Condition Not Metp.779.0 Operating Instructionsp.789.1 Liebert NX Operating Modesp.78Table 20 UPS operating modesp.789.1.1 Circuit Breakersp.79Figure 53 Circuit breakersp.799.2 UPS Startupp.809.2.1 Startup Procedurep.809.2.2 Verify Switching Between Operation Modesp.81Switch from Normal Mode to Battery Modep.81Switch from Normal Mode to Bypass Modep.81Switch from Bypass Mode to Normal Modep.819.3 Maintenance Bypass Procedure and Powering Down the UPSp.829.4 Auto Restartp.839.5 Emergency Shutdown With EPOp.839.6 Reset After Shutdown for Emergency Stop (EPO Action) or Other Conditionsp.839.7 Battery Protectionp.849.7.1 Battery Undervoltage Pre-Warningp.849.7.2 Battery End-of-Discharge (EOD) Protectionp.849.8 Multi-Module System Proceduresp.849.8.1 Isolating One Module in a Multi-Module Systemp.84Figure 54 Typical parallel system block diagram with common input supply, with separate batteries and optional output / bypass distribution panelp.859.8.2 Inserting One Module into a Multi-Module Systemp.869.8.3 Shutdown Procedure-Complete UPS and Load Shutdownp.879.9 Commissioning a Parallel Systemp.879.10 Parallel System Start Upp.8810.0 Optionsp.8910.1 Communication and Other User Terminalsp.89Figure 55 Monitoring board (U2) auxiliary terminal block detailp.8910.1.1 Analog Input Interfacep.8910.1.2 Power Outputp.8910.1.3 Liebert IntelliSlot Communicationp.8910.1.4 Communication and Monitoringp.90Liebert IntelliSlot Web Card - SNMP/HTTP Network Interface Cardp.90Table 21 Liebert NX communication optionsp.9010.1.5 Configuring Baud Ratesp.91Figure 56 Liebert IntelliSlot Web card displayp.92Relay Cardp.93Table 22 Relay Card pin configurationp.93Table 23 Relay card jumper configurationp.93MultiPort 4 Cardp.94Figure 57 MultiPort 4 card pin assignmentp.9410.2 LBS Mode-Load Bus Synchronizationp.9510.2.1 Remote Alarm Monitorp.9510.3 Replacing Dust Filtersp.95Figure 58 Dust filter replacementp.9511.0 Specifications and Technical Datap.9611.1 Lug Size and Torque Requirementsp.96Table 24 Torque specificationsp.96Table 25 Battery torque ratingp.9611.2 Cable Lengths: Floor to Connection Point Inside UPSp.96Table 26 Distance to connection points on the Liebert NX UPSp.97Table 27 Parallel system current tablep.97Table 28 External cabinet dimensions, including side panelsp.98Table 29 Lead/Lag ratingsp.9811.3 Cable size and tightening torquesp.98Table 30 Cable size tightening torque at Liebert NX 40kVA UPS terminalsp.98Table 31 Cable size tightening torque at Liebert NX 60kVA UPS terminalsp.98Table 32 Cable size tightening torque at Liebert NX 80kVA UPS terminalsp.99Table 33 Cable size tightening torque at Liebert NX 100kVA UPS terminalsp.99Table 34 Cable size tightening torque at Liebert NX 120kVA UPS terminalsp.9911.4 Battery Run Timesp.100Table 35 Estimated battery run time, minutesp.100Appendix A - UPS Status Messagesp.101Table 36 UPS status messagesp.101
Page 8 of the Emerson 480V user manual — Table of contents
Page 8 · click to enlarge
Page 8

Table of contents

Important Safety Instructionsp.9SAVE THESE INSTRUCTIONSp.9Battery Cabinet Precautionsp.10Glossary of Symbolsp.111.0 Installationp.121.1 External Inspectionsp.121.2 Internal Inspectionsp.131.2.1 Storing for Delayed Installationp.131.3 Preliminary Checksp.131.3.1 Identificationp.131.4 UPS Locationp.131.4.1 Positioning the UPSp.131.4.2 Environmental Considerationsp.13Battery Locationp.141.4.3 Special Considerations for Parallel Systemsp.141.5 Considerations in Moving the Liebert NXp.14Final Positionp.141.6 Mechanical Considerationsp.141.6.1 Clearancesp.151.6.2 Floor Installationp.151.6.3 Cable Entryp.15System Compositionp.151.6.4 Optional Cabinetsp.15Figure 1 Cabinet arrangement-Liebert NX units and battery cabinetsp.16Figure 2 Cabinet arrangement-Liebert NX units, battery cabinets and Liebert FPCp.172.0 Electrical Connectionsp.182.1 Power Cablingp.182.1.1 Cable Ratingp.18Lug Size and Torque Requirementsp.182.1.2 UPS Input Configurationp.19Figure 3 Single module block diagram-dual input configurationp.192.1.3 Cabling Guidelinesp.192.1.4 Cable Connectionsp.20Figure 4 Input and output busbarsp.202.1.5 Safety Groundp.212.1.6 Protective Devicesp.21UPS Rectifier and Bypass Input Supplyp.212.1.7 Cabling Procedurep.22Common Input Connectionsp.22Dual Input Connectionsp.22Output System Connections-Ensure Correct Phase Rotationp.22Frequency Converter Modep.232.2 Control Cablesp.232.2.1 Monitor Board Featuresp.23Figure 5 Monitor board U2p.23Figure 6 Auxiliary terminal block detail (Monitoring Board)p.242.3 Dry Contactsp.242.3.1 Input Dry Contactsp.25Figure 7 Input dry contactsp.25Table 1 Input dry contacts at X3p.252.3.2 Maintenance Bypass Cabinet Interfacep.25Table 2 Maintenance bypass cabinet interfacep.252.3.3 BCB Control Interfacep.26Table 3 BCB control interfacep.26Figure 8 Jumper connection for BCB interface without a battery interface boardp.262.3.4 Output Dry Contactsp.27Figure 9 Output dry contacts and EPO wiring for firmware before M170p.27Table 4 Output dry contact relaysp.272.3.5 EPO Input-Optionalp.28Figure 10 EPO wiringp.28Table 5 EPO input contact relaysp.283.0 Battery Installationp.293.1 Introductionp.293.2 Safetyp.293.3 External Battery Cabinet Installationp.303.3.1 Battery Cabinetsp.30Figure 11 Battery cabinetp.303.3.2 Connecting the Batteriesp.31Figure 12 Battery cabinet-detailsp.313.3.3 Installation Considerationsp.31Figure 13 Battery tray and supportsp.323.3.4 Connecting the Battery Cabinet to the UPSp.323.4 Non-Standard Batteriesp.323.5 BCB Shunt Tripp.323.6 Alber Monitoring System-Optionalp.334.0 Optionsp.344.1 Load Bus Synchronizationp.344.1.1 Performance Requirementsp.344.1.2 LBS Cable and Settingsp.34Figure 14 Load Bus Synchronization cable connection in single module systemsp.34Figure 15 Load Bus Synchronization cable connection with multi-module systemsp.354.2 Configuring Parallel System Operationp.354.2.1 Generalp.354.2.2 Features of Parallel Systemp.35Figure 16 Parallel system block diagramp.364.2.3 Operating Principlesp.36Redundancy Parallelingp.364.2.4 Operation Modes Summaryp.364.3 Installing Parallel Systemp.364.3.1 Conditions for Parallel Systemp.374.3.2 Cabinet Installationp.374.3.3 Preliminary Checksp.374.3.4 Power Cablesp.374.3.5 Parallel Control Cablesp.37Parallel System Control Cablesp.37Figure 17 Connecting system parallel control cablesp.38Auxiliary Dry Contact Cablesp.38Figure 18 Auxiliary dry contact cables for output breaker in multi-module systemp.38Figure 19 Dry contacts, multiple UPS modules with distribution panelp.394.3.6 Emergency Power Off (EPO)p.40Figure 20 Connecting EPO push buttonp.405.0 UPS Specificationsp.415.1 Conformity and Standardsp.415.2 UPS Environmentalp.41Table 6 Environmental characteristicsp.415.3 UPS Mechanical Characteristicsp.41Table 7 UPS mechanical characteristicsp.415.4 UPS Electrical Characteristicsp.42Table 8 UPS terminalp.425.4.1 Input Rectifierp.43Table 9 Rectifier input powerp.43Table 10 Input voltage window with deratingp.43Table 11 Liebert approved replacement batteriesp.435.4.2 DC Intermediate Circuitp.44Table 12 DC intermediate circuitp.445.4.3 Inverter Outputp.44Table 13 Inverter outputp.445.4.4 Bypass Inputp.44Table 14 Bypass inputp.446.0 Installation Drawingsp.45Figure 21 Dimensional viewfront and left side viewsp.45Figure 22 Dimensions continued-top and bottom viewsp.46Figure 23 Main components-typical unitp.46Figure 24 Cable connectionsp.47Figure 25 Outline drawing, 33" battery power pack system, single cabinetp.48Figure 26 Terminal details, 33" battery power pack system, single cabinet Liebert NXp.49Figure 27 Battery connectionsp.50Figure 28 Battery cabinet interconnectionp.51Figure 29 Outline drawing, Liebert NX480V, 80-120kVA Type E and E2 parallel cabinetp.52Figure 30 Outline drawing, Liebert NX480V, 80-120kVA Type E1 parallel cabinetp.53Figure 31 Main component location drawing Liebert NX 480V, Type E parallel cabinetp.54Figure 32 Main component location drawing Liebert NX 480V, Type E1 parallel cabinetp.55Figure 33 Main component location drawing Liebert NX 480V, Type E2 parallel cabinetp.56Figure 34 Lineup detail-Parallel Type E connection to Liebert NXp.57Figure 35 Lineup detail-Parallel Type E1 connection to Liebert NXp.58Figure 36 Lineup detail-Parallel Type E2 connection to Liebert NXp.59Figure 37 Line-up detail, bolt together description, 40-120 kVA Liebert NXp.607.0 Operationp.617.1 General Descriptionp.61Figure 38 Single module block diagram (dual input configuration)p.617.1.1 Bypass Suppliesp.627.1.2 Operating Modesp.62Normal Modep.62Battery Modep.62Bypass Modep.62Maintenance Modep.63Parallel Redundancy Mode (System Expansion)p.63Frequency Converter Modep.638.0 Operator Control and Display Panelp.648.1 Operator Control Panelp.64Figure 39 Overview of control panelp.648.1.1 Display Panel Layoutp.64Figure 40 Detailed view of control panelp.658.2 Mimic Display Indicatorsp.66Figure 41 Mimic display indicators locationp.66Table 15 Mimic display status indicatorsp.668.3 Control Buttonsp.67Figure 42 Location of control buttonsp.67Table 16 Control buttonsp.678.4 Audible Buzzerp.68Figure 43 Buzzer locationp.688.5 LCD Overviewp.68Figure 44 Sections of the LCDp.688.6 Navigation Keysp.69Table 17 Icons for navigation keysp.698.7 UPS System Informationp.69Table 18 Description of items in UPS system windowp.698.8 LCD Menus and Data Itemsp.70Figure 45 Menu treep.70Table 19 Descriptions of UPS menus and data window itemsp.718.9 Language Selectionp.72Figure 46 Language selectionp.728.10 Current Date and Timep.73Figure 47 Set date and timep.738.11 UPS Status Messagesp.74Figure 48 Current status and history log recordsp.748.12 Types of LCD Screensp.758.12.1 Opening Displayp.75Figure 49 Opening displayp.758.12.2 Default Screenp.75Figure 50 Default screenp.758.12.3 UPS Help Screenp.76Figure 51 Help screenp.768.12.4 Screen Saver Windowp.76Figure 52 Screen saver windowp.768.13 Pop-Up Windowsp.778.13.1 From Bypass to Inverter Mode With Power Interruptionp.778.13.2 From Inverter to Bypass Mode With Interruptionp.778.13.3 System Self-Testp.778.13.4 Battery Capacity Test Confirmationp.778.13.5 Battery Self-Test Aborted, Condition Not Metp.778.13.6 Battery Refresh Charge Aborted, Condition Not Metp.779.0 Operating Instructionsp.789.1 Liebert NX Operating Modesp.78Table 20 UPS operating modesp.789.1.1 Circuit Breakersp.79Figure 53 Circuit breakersp.799.2 UPS Startupp.809.2.1 Startup Procedurep.809.2.2 Verify Switching Between Operation Modesp.81Switch from Normal Mode to Battery Modep.81Switch from Normal Mode to Bypass Modep.81Switch from Bypass Mode to Normal Modep.819.3 Maintenance Bypass Procedure and Powering Down the UPSp.829.4 Auto Restartp.839.5 Emergency Shutdown With EPOp.839.6 Reset After Shutdown for Emergency Stop (EPO Action) or Other Conditionsp.839.7 Battery Protectionp.849.7.1 Battery Undervoltage Pre-Warningp.849.7.2 Battery End-of-Discharge (EOD) Protectionp.849.8 Multi-Module System Proceduresp.849.8.1 Isolating One Module in a Multi-Module Systemp.84Figure 54 Typical parallel system block diagram with common input supply, with separate batteries and optional output / bypass distribution panelp.859.8.2 Inserting One Module into a Multi-Module Systemp.869.8.3 Shutdown Procedure-Complete UPS and Load Shutdownp.879.9 Commissioning a Parallel Systemp.879.10 Parallel System Start Upp.8810.0 Optionsp.8910.1 Communication and Other User Terminalsp.89Figure 55 Monitoring board (U2) auxiliary terminal block detailp.8910.1.1 Analog Input Interfacep.8910.1.2 Power Outputp.8910.1.3 Liebert IntelliSlot Communicationp.8910.1.4 Communication and Monitoringp.90Liebert IntelliSlot Web Card - SNMP/HTTP Network Interface Cardp.90Table 21 Liebert NX communication optionsp.9010.1.5 Configuring Baud Ratesp.91Figure 56 Liebert IntelliSlot Web card displayp.92Relay Cardp.93Table 22 Relay Card pin configurationp.93Table 23 Relay card jumper configurationp.93MultiPort 4 Cardp.94Figure 57 MultiPort 4 card pin assignmentp.9410.2 LBS Mode-Load Bus Synchronizationp.9510.2.1 Remote Alarm Monitorp.9510.3 Replacing Dust Filtersp.95Figure 58 Dust filter replacementp.9511.0 Specifications and Technical Datap.9611.1 Lug Size and Torque Requirementsp.96Table 24 Torque specificationsp.96Table 25 Battery torque ratingp.9611.2 Cable Lengths: Floor to Connection Point Inside UPSp.96Table 26 Distance to connection points on the Liebert NX UPSp.97Table 27 Parallel system current tablep.97Table 28 External cabinet dimensions, including side panelsp.98Table 29 Lead/Lag ratingsp.9811.3 Cable size and tightening torquesp.98Table 30 Cable size tightening torque at Liebert NX 40kVA UPS terminalsp.98Table 31 Cable size tightening torque at Liebert NX 60kVA UPS terminalsp.98Table 32 Cable size tightening torque at Liebert NX 80kVA UPS terminalsp.99Table 33 Cable size tightening torque at Liebert NX 100kVA UPS terminalsp.99Table 34 Cable size tightening torque at Liebert NX 120kVA UPS terminalsp.9911.4 Battery Run Timesp.100Table 35 Estimated battery run time, minutesp.100Appendix A - UPS Status Messagesp.101Table 36 UPS status messagesp.101
Page 9 of the Emerson 480V user manual — I MPORTANT S AFETY I NSTRUCTIONS
Page 9 · click to enlarge
Page 9

I MPORTANT S AFETY I NSTRUCTIONS

SAVE THESE INSTRUCTIONS

This manual contains important instructions that should be followed during installation of your Liebert NX™ UPS and ancillary equipment.

Read this manual thoroughly, paying special attention to the sections that apply to your installation, before working with the UPS. Retain this manual for use by installing personnel.

! WARNING Exercise extreme care when handling UPS cabinets to avoid equipment damage or injury to personnel. The UPS module weight ranges from 1180 to 1290 lb. (535 to 585kg).

Determine unit weight and locate center of gravity symbols before handling the UPS. Test lift and balance the cabinet before transporting. Never tilt equipment more than 15 degrees from vertical.

Battery manufacturers supply details of the necessary precautions to be observed when working on, or in the vicinity of, a large bank of battery cells. These precautions should be followed implicitly at all times.

Follow all battery safety precautions when installing, charging or servicing batteries. In addition to the hazard of electric shock, gas produced by batteries can be explosive and sulfuric acid can cause severe burns. When connected, the nominal battery voltage is 480VDC and is potentially lethal.

In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or those approved for use in fighting electrical fires.

Extreme caution is required when performing maintenance. Be constantly aware that the UPS system contains high DC as well as AC voltages.

Check for voltage with both AC and DC voltmeters prior to making contact.

! WARNING As with other types of high power equipment, dangerous voltages are present within the UPS and battery enclosure. The risk of contact with these voltages is minimized as the live component parts are housed behind a hinged, lockable door. Further internal safety screens make the equipment protected to IP20 standards.

No risk exists to any personnel when operating the equipment in the normal manner, following the recommended operating procedures.

All equipment maintenance and servicing procedures involve internal access and should be carried out only by trained personnel.

! WARNING High ground leakage current: Ground connection is essential before connecting the input supply.

This equipment must be grounded in accordance with local electrical codes.

Maximum load must not exceed that shown on the UPS rating label.

! CAUTION This equipment is fitted with RFI suppression filters. Ground leakage current exceeds 3.5 mA and is less than 30 mA. Transient and steady-state ground leakage currents, which may occur when starting the equipment, should be taken into account when selecting instantaneous residual current circuit breakers (RCCBs) or residual current devices (RCDs). RCCBs must be selected sensitive to DC unidirectional pulses (Class A) and insensitive to transient current pulses. Note also that the ground leakage currents of the load will be carried by this RCCB or RCD.

Page 10 of the Emerson 480V user manual — Battery Cabinet Precautions
Page 10 · click to enlarge
Page 10

! WARNING Under typical operation and with all UPS doors closed, only normal safety precautions are necessary. The area around the UPS system should be kept free of puddles of water, excess moisture and debris. Special safety precautions are required for procedures involving handling, installation and maintenance of the UPS system and the batteries. Observe all safety precautions in this manual before handling or installing the UPS system. Observe all precautions in this manual, before as well as during performance of all maintenance procedures. Observe all battery safety precautions before working on or near the battery. This equipment contains several circuits that are energized with high voltage. Only test equipment designed for troubleshooting should be used. This is particularly true for oscilloscopes. Always check with an AC and DC voltmeter to ensure safety before making contact or using tools. Even when the power is turned Off, dangerously high electric charges may exist within the UPS. All power and control wiring should be installed by a qualified electrician. All power and control wiring must comply with the NEC and applicable local codes. ONLY qualified service personnel should perform maintenance on the UPS system. When performing maintenance with any part of the equipment under power, service personnel and test equipment should be standing on rubber mats. The service personnel should wear insulating shoes for isolation from direct contact with the floor (earth ground). Never work alone, even if all power is removed from the equipment. A second person should be standing by to assist and summon help in case an accident should occur.

! CAUTION This unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J of the FCC rules. These limits provide reasonable protection against harmful interference in a commercial environment. This unit generates, uses and radiates radio frequency energy and, if not installed and used in accordance with this instruction manual, may cause harmful interference to radio communications. This unit is not designed for use in a residential area. Operation of this unit in a residential area may cause harmful interference that the user must correct at his own expense.

Battery Cabinet Precautions The following warning applies to all battery cabinets supplied with UPS systems. Additional warn- ings and cautions applicable to battery cabinets may be found in 3.0 - Battery Installation.

  • ! WARNING Internal battery strapping must be verified by manufacturer prior to moving a battery cabinet (after initial installation).
  • Battery cabinets contain non-spillable batteries.
  • Keep units upright.
  • Do not stack.
  • Do not tilt. Failure to heed this warning could result in smoke, fire or electric hazard. Call 1-800-LIEBERT before moving battery cabinets (after initial installation).
Page 11 of the Emerson 480V user manual — R
Page 11 · click to enlarge
Page 11

G LOSSARY OF S YMBOLS

Risk of electrical shock

!

Indicates caution followed by important instructions

Requests the user to consult the manual

Indicates the unit contains a valve-regulated lead acid battery

R

Show 8 more labels / short text on this page
AC input · AC output · PbH2SO4 - + · Recycle · DC voltage · Equipment grounding conductor · Bonded to ground · AC voltage
Page 12 of the Emerson 480V user manual — 1.0 I NSTALLATION
Page 12 · click to enlarge
Page 12

1.0 I NSTALLATION

Liebert’s NX Uninterruptible Power Supply system provides continuous, high-quality AC power to your business-critical equipment, such as telecommunications and data processing equipment. The Liebert NX UPS supplies power that is free of the disturbances and variations in voltage and fre- quency common to utility power, which is subject to brownouts, blackouts, surges and sags.

The Liebert NX utilizes the latest in high-frequency, double-conversion pulse width modulation tech- nology and fully digital controls to enhance its reliability and increase the ease of use. This section describes the Liebert NX’s environmental requirements and mechanical considerations that must be taken into account when planning the positioning and cabling of the UPS equipment.

Because every site is unique, this section presents a guide to general procedures and practices that should be observed by the installing engineer, rather than step-by-step installation instructions.

! WARNING Do not apply electrical power to the UPS equipment before the arrival of the commissioning engineer.

! WARNING The UPS equipment should be installed by a qualified engineer in accordance with the information contained in this section.

! WARNING Special care should be taken when working with the batteries associated with this equipment. When connected together, the nominal battery voltage is 480VDC and is potentially lethal.

  • Eye protection should be worn to prevent injury from accidental electrical arcs.
  • Remove rings, watches and all other metal objects.
  • Use only tools with insulated handles.
  • Wear rubber gloves. If a battery leaks electrolyte or is otherwise physically damaged, it must be replaced, stored in a container resistant to sulfuric acid and disposed of in accordance with local regulations.

If electrolyte comes into contact with skin, the affected area should be washed immediately with large amounts of water.

1.1 External Inspections 1. While the UPS system is still on the truck, inspect the equipment and shipping container(s) for any signs of damage or mishandling. Do not attempt to install the system if damage is apparent. If any damage is noted, file a damage claim with the shipping agency within 24 hours and contact Liebert Global Services at 1-800-LIEBERT to inform them of the damage claim and the condition of the equipment. 2. Compare the contents of the shipment with the bill of lading. Report any missing items to the carrier and your local Liebert representative immediately.

Installation

Page 13 of the Emerson 480V user manual — 1.4.1 Positioning the UPS
Page 13 · click to enlarge
Page 13

1.2 Internal Inspections 1. Remove any packaging material, then visually examine the UPS and battery equipment for transit damage, both internally and externally. Report any such damage to the shipper and to Liebert immediately. 2. Check the nameplate inside the cabinet door to verify that the model number and rating correspond to the ones specified. Record the model number and serial number in the front of this installation manual. This information is necessary should service be required. 3. Check for loose connections or unsecured components in the cabinet. 4. Check for shipping damage to internal components.

1.2.1 Storing for Delayed Installation

If the equipment will not be installed immediately, it must be stored indoors where the humidity is no higher than 90% and the temperature is no higher than 104°F (40°C). The storage area must protect the Liebert NX from excessive moisture (see 5.2 - UPS Environmental).

! CAUTION If the battery cabinet must remain disconnected from power for more than six (6) months, the battery must be recharged before use. To charge the batteries, the battery cabinet must be connected to the Liebert NX UPS and the UPS must be connected to utility power and started up because the charger operates only while the Liebert NX UPS is operating.

! CAUTION When batteries are installed in a cabinet adjacent to the UPS unit, the battery—not the UPS—dictates the designed maximum ambient operating temperature.

1.3 Preliminary Checks

1.3.1 Identification The equipment supplied has an identification tag on the back of the main door listing the type and size of the UPS. 1.4 UPS Location

1.4.1 Positioning the UPS

Choose a location for the UPS that offers:

  • Easy connection to inputs, outputs and auxiliary equipment
  • Enough space to service the UPS
  • Air circulation sufficient to expel heat produced by UPS
  • Protection against moisture and excessive humidity
  • Protection against dust and other particulate matter
  • Compliance with fire prevention regulations and practices
  • Operating environment temperature of 74-80°F (23-27°C) for maximum battery efficiency 1.4.2 Environmental Considerations Before installing the Liebert NX, verify that the UPS room satisfies the environmental conditions stipulated in 5.2 - UPS Environmental , paying particular attention to the ambient temperature and air exchange system. The UPS unit should be installed in a cool, dry, clean-air environment with adequate ventilation to keep the ambient temperature within the specified operating range 32°F to 104°F (0°C to 40°C). For optimal UPS and battery system performance and service life, maintain the operating temperature within the range of 74-80°F, (23-27°C). The Liebert NX UPS cooled by internal fans. Cooling air enters the unit through the front of the unit and is exhausted out the top. To permit proper air flow and prevent overheating, do NOT block or cover the ventilation openings or blow air down onto the unit. Ventilation clearance above the unit must be a minimum of 8 in. (203mm). See Table 7 for details on heat dissipation.

Installation

Page 14 of the Emerson 480V user manual — 1.6 Mechanical Considerations
Page 14 · click to enlarge
Page 14

Battery Location

Batteries must be installed in Liebert NX 480V battery cabinets or battery room. Temperature is a major factor in determining battery life and capacity. Battery manufacturers recommend an operat- ing temperature of 77°F (25°C). Ambient temperatures higher than this reduce battery life; tempera- tures lower than this reduce battery capacity. In a typical installation, battery temperature should be maintained between 74°F and 80°F (23-27°C). Batteries should be placed where there are no main heat sources or air inlets to prevent portions of batteries from being either much warmer or much cooler than other parts of the batteries.

1.4.3 Special Considerations for Parallel Systems 1. Consider the grounding configuration of your system before finalizing module placement. For optimal ground performance, the Liebert NX modules should be close together. 2. For optimal load-sharing performance, the UPS output cables should be approximately the same length, plus or minus 20 percent. 3. Position modules in such a way as to minimize the length of power cables and control wiring between UPS modules and the paralleling cabinet. 1.5 Considerations in Moving the Liebert NX

Ensure that the UPS weight is within the designated surface weight loading (lb./ft2 or kg/cm2) of any handling equipment. See Table 7 for weights of various units.

To move the UPS and optional battery cabinets:

  • The Liebert NX may be rolled on its casters when moving the unit a short distance. For longer distances, move the UPS with a forklift or similar equipment to ease the relocation and to reduce vibration.

The optional battery cabinets should be moved with a forklift or similar equipment.

! WARNING Ensure that any equipment that will be used to move the Liebert NX has sufficient lifting capacity. The Liebert NX weight ranges from 1180 to 1290 lb. (535 to 585kg). See Table 7 for details. The UPS presents a tipping hazard. Do not tilt the Liebert NX further than 15 degrees from vertical.

The UPS is fitted with casters—take care to prevent movement when unbolting the equipment from its shipping pallet. Ensure adequate personnel and lifting equipment are available when taking the Liebert NX off its shipping pallet. Do not tilt the unit more than 15 degrees from center.

! WARNING The casters are strong enough for movement across even surfaces only. Casters may fail if they are subjected to shock loading, such as being dropped or rolled over holes in the floor or obstructions. Such failure may cause the unit to tip over, injuring personnel and damaging the equipment.

Care must be taken when maneuvering cabinets fitted with batteries. Keep such moves to a minimum. For further information, see Battery Cabinet Precautions on page 2.

Final Position

When the equipment has been finally positioned, ensure that the adjustable stops are set so that the UPS will remain stationary and stable (see 6.0 - Installation Drawings).

1.6 Mechanical Considerations

The Liebert NX is constructed with a steel frame and removable panels. Top and side panels are secured to the chassis by screws. The doors may be opened for access to power connections bars, aux- iliary terminal blocks and power switches.

The UPS comes with an operator control panel, which provides basic operational status and alarm information. Cooling is provided by internal fans. The unit sits on four casters. Adjustable stops are provided to prevent the UPS from moving once it has been moved to its final position.

Installation

Page 15 of the Emerson 480V user manual — 1.6.4 Optional Cabinets
Page 15 · click to enlarge
Page 15

1.6.1 Clearances

There are no ventilation grilles on the sides or rear of the UPS. The unit may be placed with the rear against a wall and optional cabinets on either side.

To enable routine tightening of power terminations within the UPS, make sure there is sufficient clearance in front of the Liebert NX to permit free passage of personnel with the door fully opened.

Leave a minimum of 8 in. (203mm) between the top of the UPS and the ceiling to permit adequate air circulation above the unit. Liebert recommends against using air conditioning or other systems that blow air onto the top of the unit.

1.6.2 Floor Installation

The diagrams in 6.0 - Installation Drawings show the location of holes in the base plate for bolting the equipment to the floor.

If the equipment is to be placed on a raised floor, it should be mounted on a pedestal that will support the equipment point loading. Refer to the bottom view in Figure 21 to design this pedestal.

1.6.3 Cable Entry

Cables can enter the Liebert NX from the top or bottom. Cable entry is made possible by removing a metal plate attached to the UPS.

These plates are designed to allow the personnel to punch holes for fitting and securing the conduit. Once the conduit holes are punched, these plates should be reattached to the UPS.

! CAUTION To reduce the risk of fire, connect only to a circuit provided with correct amperes maximum branch circuit overcurrent protection (see Table 8) in accordance with the National Electric Code, ANSI/NFPA 70.

System Composition

A UPS system can comprise a number of equipment cabinets, depending on the individual system design requirements—e.g., UPS cabinet with External Bypass cabinet and Maintenance Bypass cabi- net. In general, all cabinets used will be the same height and are designed to be positioned side-by- side to form an aesthetically appealing equipment suite.

1.6.4 Optional Cabinets

The Maintenance Bypass Cabinet must be cabled and bolted to the Liebert NX before the UPS and bypass cabinet are moved into their final position. Connect the input wiring to the Maintenance Bypass Cabinet ONLY after the units are connected and positioned.

Battery cabinets may be bolted to either side of the Liebert NX; see Figure 1.

Installation

Page 16 of the Emerson 480V user manual — Figure 1 Cabinet arrangement—Liebert NX units and battery cabinets
Page 16 · click to enlarge
Page 16

Figure 1 Cabinet arrangement—Liebert NX units and battery cabinets

Emerson 480V — Figure 1 Cabinet arrangement—Liebert NX units and battery cabinets diagram (page 16)
Fig. 2 · Figure 1 Cabinet arrangement—Liebert NX units and ba…

Installation

Page 17 of the Emerson 480V user manual — Figure 2 Cabinet arrangement—Liebert NX units, battery cabinets and Liebert FPC
Page 17 · click to enlarge
Page 17

Figure 2 Cabinet arrangement—Liebert NX units, battery cabinets and Liebert FPC

Emerson 480V — Figure 2 Cabinet arrangement—Liebert NX units, battery cabinets and Liebert FPC diagram (page 17)
Fig. 3 · Figure 2 Cabinet arrangement—Liebert NX units, batte…

Installation

Page 18 of the Emerson 480V user manual — Lug Size and Torque Requirements
Page 18 · click to enlarge
Page 18

2.0 E LECTRICAL C ONNECTIONS

The UPS requires both power and control cabling once it has been mechanically installed. All control cables must run separate from power cables in metal conduits or metal ducts that are electrically bonded to the metalwork of the cabinets to which they are connected.

! WARNING Before connecting input power to the Liebert NX, ensure that you are aware of the location and operation of the overcurrent protection devices that connect the UPS input/bypass supply to the power distribution panel.

De-energize and lockout or tagout all incoming high- and low-voltage power circuits before installing cables or making any electrical connections.

2.1 Power Cabling

2.1.1 Cable Rating

The main factors affecting the choice and size of cable are voltage, current (also taking into account overcurrent), room temperature and conditions of installation of the cable.

The power cables of the system must be sized with respect to the following description:

  • UPS input cables - The UPS input cables must be sized for the maximum input current, including the maximum battery recharge current, given in Table 8 , with respect to the unit rating and the input AC voltage.
  • UPS bypass and output cables - The bypass and output cables must be sized for the nominal output current, given in Table 8 , with respect to the unit rating and the output AC voltage.
  • Battery cables - When connecting an external battery cabinet, the battery cables must be sized for the battery discharge current at the end-of-discharge voltage, as given in Table 8 , with respect to the unit rating.

The power cables can be sized to suit the UPS unit rating according to Table 8.

Lug Size and Torque Requirements

Refer to Table 24 for lug size and torque requirements.

Electrical Connections

Page 19 of the Emerson 480V user manual — 2.1.3 Cabling Guidelines
Page 19 · click to enlarge
Page 19

2.1.2 UPS Input Configuration Figure 3 illustrates the Liebert NX in a split bypass (dual-input) configuration. In this configuration the Static Bypass and the Maintenance Bypass lines are supplied from a separate feed from the Main input. Both sources must be protected externally with properly sized protective devices. By default, the unit ships with internal links installed between the bypass input and main input (Single Input configuration). To wire the unit as a dual input UPS, remove the links and wire the bypass to the input bus bars, then wire the Main input directly to CB1 (see Figure 4).

Figure 3 Single module block diagram—dual input configuration

Emerson 480V — Figure 3 Single module block diagram—dual input configuration diagram (page 19)
Fig. 4 · Figure 3 Single module block diagram—dual input conf…

2.1.3 Cabling Guidelines

The following are guidelines only and are superseded by local regulations and codes of practice where applicable. Use wiring rated at 75°C or greater.

1. The ground conductor should be sized in accordance with the input overcurrent protection device data in Table 8. The ground cable connecting the UPS to the main ground system must follow the most direct route possible. Control wiring and power wiring must be run in separate conduit. Output and input cables must be run in separate conduit. 2. Consider using paralleled smaller cables for heavy currents—this can ease installation. 3. When sizing battery cables, a maximum voltage drop of 4VDC is permissible at the current ratings in UPS terminal. For terminal connection sizing, see Table 8. 4. In most installations, especially parallel multi-module systems, the load equipment is connected to a distribution network of individually protected busbars fed by the UPS output, rather than connected directly to the UPS itself. When this is the case, the UPS output cables can be rated to suit the individual distribution network demands rather than being fully load-rated.

5. When laying power cables, do not form coils; this will help avoid increasing formation of electromagnetic interference.

Electrical Connections

Page 20 of the Emerson 480V user manual — Figure 4 Input and output busbars
Page 20 · click to enlarge
Page 20

2.1.4 Cable Connections The rectifier input, bypass and output are easily accessible from the front of the unit for installation. All require lug type terminations. They are connected to busbars on the front side of the Liebert NX and below the circuit breaker, as shown in Figure 4. These busbars are accessible when the front side panel is removed. Busbars to connect external batteries are accessible from the front of the UPS.

Figure 4 Input and output busbars

Emerson 480V — Figure 4 Input and output busbars diagram (page 20)
Fig. 5 · Figure 4 Input and output busbars

Output Busbars (Phases are indicated by letters below the bars)

Rectifier Input Busbars (Phases are indicated by letters below the bars)

Bypass Input Busbars (Phases are indicated by letters below the bars)

Electrical Connections · Battery Input Connections · Ground Busbar

Page 21 of the Emerson 480V user manual — UPS Rectifier and Bypass Input Supply
Page 21 · click to enlarge
Page 21

2.1.5 Safety Ground

The safety ground busbar is located below the Maintenance Bypass circuit breaker as shown in Figure 4. The safety ground cable must be connected to the ground busbar and bonded to each cabi- net in the system.

All cabinets and cable conduit should be grounded in accordance with local regulations.

! WARNING Failure to follow proper grounding procedures can result in electric shock hazard to personnel or the risk of fire, should a ground fault occur.

2.1.6 Protective Devices

For safety, it is necessary to install circuit breakers in the input AC supply and external battery bat- tery cabinets, external to the UPS system. Given that every installation has its own characteristics, this section provides guidelines for qualified installation engineers with knowledge of operating prac- tices, regulatory standards and the equipment to be installed.

UPS Rectifier and Bypass Input Supply

  • Protection from excessive overcurrents and short circuits in power supply input External overcurrent protection for the AC output circuit is to be provided. See 5.4 - UPS Electrical Characteristics and Table 9 for overload capacity. When an external battery supply not made by Liebert is used, the customer must provide overcurrent protection for the battery circuit.
  • Dual Input When wiring the UPS with dual inputs, the Rectifier input and the Bypass input must be protected separately. Size the breakers according to the input currents shown in Table 8 . In dual input configuration, the neutral wire of each source should be connected together to guarantee dual source has the same voltage potential to earth.

Electrical Connections

Page 22 of the Emerson 480V user manual — 2.1.7 Cabling Procedure
Page 22 · click to enlarge
Page 22

2.1.7 Cabling Procedure

! CAUTION The operations described in this section must be performed by authorized electricians or qualified technical personnel. If you have any difficulties, contact your local Liebert representative or Liebert Global Services.

Once the equipment has been positioned and secured for operation, and the battery and ground col- lars have been connected (see 2.1.4 - Cable Connections), connect the power cables as described below. (Study the reference drawing in 6.0 - Installation Drawings.)

1. Verify that all incoming high and low voltage power circuits are de-energized and locked out or tagged out before installing cables or making any electrical connections. 2. Remove the front protective cover to gain easier access to the connections busbars. 3. Connect the safety ground and any easier bonding ground bus cables to the copper ground busbar located on the bottom of the equipment below the power connections. All cabinets in the UPS system must be connected to the user’s ground connection.

4. Identify and make power connections with incoming cables according to Steps 5 through 9 .

Common Input Connections 5. For common bypass and rectifier inputs, connect the AC input supply cables between the power distribution panel and the UPS input busbars (A-B-C terminals) and tighten the connections to 88 lb-in. (10 N-m) using the M8 bolt provided.

Dual Input Connections 6. For the bypass, connect the AC input supply cables between the power distribution panel and the UPS input busbars (A-B-C terminals) and tighten the connections to 88 lb-in. (10 N-m) using the M8 bolt provided. 7. For the Rectifier Input, connect AC input supply cables between the power distribution panel and the UPS input circuit breaker (A-B-C terminals).

Output System Connections—Ensure Correct Phase Rotation 8. Connect the system output cables between the UPS output busbars (A-B-C terminals) and the critical load and tighten the connections to 88 lb-in. (10 N-m) (M8 bolt).

! WARNING If the load equipment will not be ready to accept power on the arrival of the commissioning engineer, then ensure that the system output cables are safely isolated.

Observe the battery cable polarity. Be sure that the battery connector is made with the cor- rect polarity. 9. Refit all protective covers removed for cable installation

Electrical Connections

Page 23 of the Emerson 480V user manual — Figure 5 Monitor board U2
Page 23 · click to enlarge
Page 23

Frequency Converter Mode

If a frequency converter configuration is used, connect the AC input supply cables to the rectifier input busbars (A-B-C terminals). Torque to 88 lb-in (10N-m) for M8 bolts. Ensure correct phase rota- tion. There will not be any AC bypass supply cables to the bypass input (A-B-C terminals) and tighten the connections.

2.2 Control Cables

2.2.1 Monitor Board Features Based on your site’s specific needs, the UPS may require auxiliary connections to manage the battery system (external battery circuit breaker, battery temperature sensor), communicate with a personal computer or provide alarm signaling to external devices or for Remote Emergency Power Off (REPO). The monitor board, arranged for this purpose, is located on the rear of the operator access door. The main features are:

  • Input and Output dry contacts signal (one pair of contacts of relay)
  • Emergency Power Off control (EPO)
  • Environmental parameter input interface
  • User communication (for data setting and user background monitor)
  • Liebert IntelliSlot ® interface
  • Modem interface
  • Temperature detect interface Figure 5 shows the relationship and connection between the monitoring (U2) board and other boards in the UPS.

Figure 5 Monitor board U2

Emerson 480V — Figure 5 Monitor board U2 diagram (page 23)
Fig. 6 · Figure 5 Monitor board U2

Electrical Connections

Page 24 of the Emerson 480V user manual — X1 X2 X3
Page 24 · click to enlarge
Page 24

Figure 6 Auxiliary terminal block detail (Monitoring Board)

Emerson 480V — Figure 6 Auxiliary terminal block detail (Monitoring Board) diagram (page 24)
Fig. 7 · Figure 6 Auxiliary terminal block detail (Monitoring…

J8

J3 J1

LCD

J22

J23

J12

J9

J2

PWR MODEM SNMP CARD

J15

J16

J17

J13 J21 J25 J28 J4 J26 J30 J10

J24

BFP INV ACF EPO Dry in MBC BCB

X1 X2 X3

2.3 Dry Contacts

The UPS provides input dry contacts and output dry contacts.

Show 4 more labels / short text on this page
Electrical Connections · Liebert IntelliSlot 2 · Liebert IntelliSlot 1 · Liebert IntelliSlot 3
Page 25 of the Emerson 480V user manual — Table 2 Maintenance bypass cabinet interface
Page 25 · click to enlarge
Page 25

2.3.1 Input Dry Contacts There are several input dry contacts at the X3 slot.

Figure 7 Input dry contacts

Emerson 480V — Figure 7 Input dry contacts diagram (page 25)
Fig. 8 · Figure 7 Input dry contacts

Table 1 Input dry contacts at X3

Emerson 480V — Table 1 Input dry contacts at X3 diagram (page 25)
Fig. 9 · Table 1 Input dry contacts at X3
1. Must be configured using configuration software before becoming active. 2 - When activated, the charger current can be limited, via software, to a percentage of the full charger current (0-100%). 3 - Activating this feature turns the battery charger off.

2.3.2 Maintenance Bypass Cabinet Interface

J26 and J30 are the MBC interface.

Table 2 Maintenance bypass cabinet interface

Emerson 480V — Table 2 Maintenance bypass cabinet interface diagram (page 25)
Fig. 10 · Table 2 Maintenance bypass cabinet interface
1. Must be configured using configuration software before becoming active.

Electrical Connections

Page 26 of the Emerson 480V user manual — Figure 8 Jumper connection for BCB interface without a battery interface board
Page 26 · click to enlarge
Page 26

2.3.3 BCB Control Interface

J10 is the BCB box interface.

Table 3 BCB control interface

J10.1 DRV BCB Driver Signal

J10.2 FB BCB Contact State

J10.3 GND Power Ground

J10.4 OL BCB On-Line - Input - This pin will become active when BCB interface is connected. (N.O.)

Figure 8 Jumper connection for BCB interface without a battery interface board

J10

DRV

GND

FB

OL

OL

Aux – N.O. Aux – N.O.

Show 4 more labels / short text on this page
Electrical Connections · Position Name Description · UPS Monitoring Board · Battery Circuit Breaker
Page 27 of the Emerson 480V user manual — Table 4 Output dry contact relays
Page 27 · click to enlarge
Page 27

2.3.4 Output Dry Contacts There are three output dry contact relays at the X1 slot (see Figure 9 and Table 4).

Figure 9 Output dry contacts and EPO wiring for firmware before M170

J13

J21

J25

ACF_C

BFP_C

BFP_S

BFP_O

INV_C

INV_S

INV_O

ACF_S

ACF_O

Table 4 Output dry contact relays

J13.2 BFP_O Bypass feedback protection relay. Normally open. Closed when bypass SCR is shorted.

J13.3 BFP_S Bypass feedback protection relay center

J13.4 BFP_C Bypass feedback protection relay. Normally closed. Open when bypass SCR is shorted.

J21.2 INV_O Inverter mode relay. Normally open. Closed when UPS is in inverter mode.

J21.3 INV_S Inverter mode relay center

J21.4 INV_C Inverter mode relay. Normally closed. Open when UPS is in inverter mode.

J25.2 ACF_O Main input fault relay. Normally open. Closed when main input is in fault.

J25.3 ACF_S Main input fault relay center

J25.4 ACF_C Main input fault relay. Normally closed. Open when main input is in fault.

Electrical Connections · Position Name Description

Page 28 of the Emerson 480V user manual — EPO - NO EPO - NC
Page 28 · click to enlarge
Page 28

2.3.5 EPO Input—Optional

The UPS has an Emergency Power Off (EPO) function operated by a button on the control panel or by a remote contact provided by the user. The local EPO button is under a hinged, clear plastic shield.

The X2 slot, shown in Figure 10, is the remote EPO input interface. The EPO has a NO/NC contact point that becomes active when shorting terminals X2: 3 and 4 or open terminal connection X2: 2 and 1.

If an external Emergency Stop facility is required, it is connected terminals X2: 1 and 2 or X2: 3 and 4 of the auxiliary terminal block (X2). It also is connected to the Normally Open or Normally Closed remote stop switch between these two terminals using shielded cable (see Figure 10 and Table 5). If this function is not used, terminals X2: 3 and 4 must be opened and X2: 1 and 2 must be closed.

Figure 10 EPO wiring

J28 X2

EPO - NO EPO - NC

Table 5 EPO input contact relays

Emerson 480V — EPO - NO EPO - NC diagram (page 28)
Fig. 11

Electrical Connections

Page 29 of the Emerson 480V user manual — 3.2 Safety
Page 29 · click to enlarge
Page 29

3.0 B ATTERY I NSTALLATION

3.1 Introduction

If using multiple sets of batteries connected in parallel to provide the required battery backup run times, fit each set with an isolating device to permit working on one of the battery sets while leaving the others in service and providing backup protection.

When replacing batteries, replace with the same manufacturer and type, or equivalent. See your Lie- bert representative for a list of approved batteries.

3.2 Safety

Special care should be taken when working with the batteries associated with the Liebert NX system equipment. When all batteries are connected together, the battery terminal voltage may exceed 480V and is POTENTIALLY LETHAL.

  • ! WARNING The Liebert NX's internal batteries are connected and energized even if the UPS is turned Off. To minimize the risk of injury, a qualified service person should disconnect the batteries before any maintenance is performed on the unit. A battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed when working on batteries:
  • Remove watches, rings and other metal objects.
  • Use tools with insulated handles.
  • Wear rubber gloves and boots.
  • Do not lay tools or metal parts on top of batteries.
  • Disconnect charging source prior to connecting or disconnecting battery terminals.

! CAUTION To reduce the risk of fire, connect only to a circuit provided with DC amperes (see Table 12) maximum branch circuit overcurrent protection in accordance with the National Electric Code, ANSI/NFPA 70.

Battery Installation

Page 30 of the Emerson 480V user manual — 3.3.1 Battery Cabinets
Page 30 · click to enlarge
Page 30

3.3 External Battery Cabinet Installation

3.3.1 Battery Cabinets

Figure 11 Battery cabinet

Emerson 480V — 3.3.1 Battery Cabinets diagram (page 30)
Fig. 12 · 3.3.1 Battery Cabinets

Optional Alber Data Collector Module

Optional Alber Controller Module

BCB Plate and BCB

The same model battery cabinet may be installed in parallel in multiple cabinet strings for additional capacity. Battery run time depends on the cabinet model, the number of cabinets and the load on the UPS.

Handling—The battery cabinet has casters to facilitate movement over short distances. The bottoms of the battery cabinets are reinforced to permit movement by forklift over longer distances.

Inspection—Remove all panels and visually inspect the batteries, bus connections and cabinet for any damage. Exercise caution: voltage is present within the battery cabinet even before installation. If there are signs of damage, do not proceed. Call Liebert Global Services at 1-800-542-2378.

Storage—The batteries can be stored for up to six months without appreciable deterioration. If plan- ning to store a battery cabinet for longer than six months or at temperatures higher than 77°F (25°C), contact Liebert Global Services for recommended precautions.

! CAUTION Any battery system should be installed by qualified personnel.

When installing an external battery cabinet that is NOT a Liebert NX battery cabinet, the customer must provide overcurrent protection. See Table 8 for sizing of protection devices.

Battery Installation · Top Cable Entry · Battery Trays

Page 31 of the Emerson 480V user manual — Figure 12 Battery cabinet—details
Page 31 · click to enlarge
Page 31

3.3.2 Connecting the Batteries

If the Liebert NX battery cabinets are installed on a raised floor, the battery power cables and circuit breaker control cables may be routed to the UPS cabinet via the floor of the cabinet (bottom entry).

If the Liebert NX battery cabinets are installed adjacent to one another on a solid floor, these cables may be passed between the cabinets through lifting slots in the lower sides of the cabinets.

Intertray connections must be made before the battery cabinet can be used.

Figure 12 Battery cabinet—details

Emerson 480V — Figure 12 Battery cabinet—details diagram (page 31)
Fig. 13 · Figure 12 Battery cabinet—details

3.3.3 Installation Considerations Position— If the system includes a matching maintenance bypass cabinet (MBC), the MBC should be installed first and the battery cabinet installed on the opposite side of the UPS. Otherwise, left- side placement of the battery cabinet is preferable. The battery cabinet(s) are designed to be located conveniently next to each UPS module, and are also available in stand-alone configurations with painted side panels. The front access design eliminates side and rear service clearance requirements. Refer to Table 28 for battery cabinet dimensions and weights. Bolt-On Cabinets—Matching battery cabinets are designed to bolt onto the side of the UPS module cabinet. Use bolts that ship with each unit to connect cabinet frames at posts, two places in the front and two places in the rear. Service Clearance—Allow front access to the battery cabinet at all times for maintenance and ser- vicing. Electrical codes require that the battery cabinet be installed with no less than 3 feet (1m) of clearance at the front of the cabinet when operating. Side and rear panels do not require service clear- ance. Cables—Cables may be run between the cabinets through cutouts in the top of the cabinet, eliminat- ing the need for external conduit runs. Route cables before moving cabinets into final position for bolt- ing together. No top or bottom entry cables are required, except for remotely located cabinets which require conduits. Software—To allow the UPS to accurately display the battery run time, the number of battery cabi- nets must be noted when performing initial startup and setup using the configuration software. This is to be performed by the Liebert Global Services customer engineer when commissioning the unit. Casters and Adjustable Stops—The adjustable stops are not designed to bear the full weight of the cabinet. Lower the stops until they are finger-tight in contact with the floor. Then tighten a small amount with a wrench (less than two turns) to give a good friction fit. When mounting the battery cabinet on seismic stands, ensure that the casters are bearing the weight of the cabinet. Battery Support Tray—Be sure to connect the battery tray support to the front of the cabinet before sliding a battery tray out for connection or service. Without the support, the battery tray may fall out of the cabinet. See Figure 13 for details.

Show 4 more labels / short text on this page
Battery Installation · Insulated Post · Tray Handle · for Cabling
Page 32 of the Emerson 480V user manual — 3.5 BCB Shunt Trip
Page 32 · click to enlarge
Page 32

Figure 13 Battery tray and supports

Emerson 480V — Figure 13 Battery tray and supports diagram (page 32)
Fig. 14 · Figure 13 Battery tray and supports

Slot in support secured by screw-in connector at corner of battery tray ...

... and notched end of support slips into slot at top corner of battery compartment

3.3.4 Connecting the Battery Cabinet to the UPS After the battery cabinet equipment has been positioned and secured for operation and the batteries have been connected, connect the power cables as described below. (See Figure 28.) 1. Verify that all incoming high and low voltage power circuits are de-energized and locked out or tagged out before installing cables or making any electrical connections. 2. Remove the UPS front protective cover to gain access to the equipment ground busbar. 3. Connect the safety ground and any necessary bonding ground cables to the copper ground busbar. (example: UPS located on the bottom of the equipment below the power connections). All cabinets in the UPS system must be connected to the user's ground connection.

4. Connect the system battery cables. Be sure that the battery connections are made with the right polarity, and tighten the connections to 44 lb-in. (5 N-m) (M6 Bolt). Do not close the battery circuit breaker before the equipment has been commissioned. 5. Connect supplied auxiliary control cable to pins J10.2 and J10.3 on the U2 monitoring board (see 2.3 - Dry Contacts ).

3.4 Non-Standard Batteries

When batteries other than a matching battery cabinet are used, a remote battery disconnect switch with overcurrent protection is required per the National Electrical Code. Contact your local Liebert sales representative about this option. Install battery racks, cabinets and batteries in accordance with the manufacturer's instructions. Verify that the battery area has adequate ventilation and battery operating temperature complies with the manufacturer's specifications and with all applicable national and local codes. If you have any questions concerning batteries, battery racks or accessories, contact Liebert Global Services at 1-800-543-2378.

3.5 BCB Shunt Trip

The Liebert NX battery cabinet has the shunt trip installed in the circuit breaker. When a DC ground fault (using the optional DC Ground Fault kit), a battery overtemperature or EPO is activated, the shunt trip will open the circuit breaker.

Battery Installation

Page 33 of the Emerson 480V user manual — 3.6 Alber Monitoring System—Optional
Page 33 · click to enlarge
Page 33

3.6 Alber Monitoring System—Optional

The Liebert matching battery cabinet allows installing an optional Alber Battery monitoring system in the cabinet. The Alber Battery Monitoring by Liebert continuously checks all critical battery parameters, such as cell voltage, overall string voltage, current and temperature. Automatic periodic tests of internal resistance of each battery will verify the battery’s operating integrity. Additional capabilities include automatic internal DC resistance tests and trend analysis providing the ability to analyze performance and aid in troubleshooting.

The Alber monitoring system is installed inside the battery cabinet (see Figure 11). The monitoring system requires approximately 0.5A, single-phase 480V.

This power can come from the output terminals of the UPS, a distribution panel, or another UPS-protected source. This power is to be field supplied. See Figure 26 for wiring location.

For details about operating the Alber system, see the Alber Monitoring System manual.

Battery Installation

Page 34 of the Emerson 480V user manual — X1-1 X1-2
Page 34 · click to enlarge
Page 34

4.0 O PTIONS

4.1 Load Bus Synchronization

The Load Bus Synchronizer (LBS) keeps the output of two independent UPS systems or parallel UPS systems in synchronization even when the systems are operating in different modes and even when either or both systems are operating on batteries. When the LBS is used, one UPS system is desig- nated as master, the other as slave.

The LBS option is typically used with dual-corded equipment or with either the Liebert SmartSwitch or Static Transfer Switch (STS) for single-corded equipment.

4.1.1 Performance Requirements

The LBS operates under the following conditions:

  • Both master and slave are on inverter (either system may be on inverter through the rectifier or on inverter through the batteries)
  • Master on inverter and slave on bypass
  • Master on bypass and slave on inverter
  • Master and slave on bypass IF the bypass source is the same for both systems

4.1.2 LBS Cable and Settings

For Liebert NX-to-Liebert NX dual bus configuration, only one optional LBS cable is required, the built-in LBS will operate normally without an extra LBS control box or interface box. The LBS port is X4 on the parallel board (M3). The parallel board is on the interior of the Liebert NX, above and left of the power electronics; see Figure 23.

An optional, 9-pin LBS cable is used to connect two UPS systems through each system’s DB9 port on its parallel board. For two parallel systems, the LBS cable can be mounted between any two units belonging to different parallel systems. For information about the LBS kit or to order the optional equipment, see your local Liebert representative.

The LBS cable is connected as illustrated in Figures 14 and 15.

Figure 14 Load Bus Synchronization cable connection in single module systems

X2-1 X2-2

X2-1 X2-2

The parallel board is on the interior of the Liebert NX, above and left of the power electronics; see Figure 23

X1-1 X1-2

X1-1 X1-2

Show 8 more labels / short text on this page
Options · LBS Cable · Parallel Board · Parallel Board · UPS Module or · UPS Module or · System #1 · System #2
Page 35 of the Emerson 480V user manual — 4.2.2 Features of Parallel System
Page 35 · click to enlarge
Page 35

Figure 15 Load Bus Synchronization cable connection with multi-module systems

UPS

UPS

X3 P5

X3 P5

X3 P5

X3 P5

X2-2 X2-1

X2-2 X2-1

X2-2 X2-1

X2-2 X2-1

P2

P4 P1

P2

P4 P1

P2

P4 P1

P2

P4 P1

X1-1 X1-2

X1-1 X1-2

X1-1 X1-2

X1-1 X1-2

P3

P3

P3

P3

B Parallel System I Parallel System II

A

The LBS function is activated with configuration software; when the LBS takes effect, the graphic LCD will display “LBS active.”

4.2 Configuring Parallel System Operation

4.2.1 General

The Liebert NX uses intelligent and reliable decentralized technology to achieve parallel operation of two or more modules.

The parallel system is used to:

  • Increase the reliability of the system to ensure adequate power supply to the critical load connected.
  • Increase serviceability and allow the execution of maintenance operations and repairs without affecting the ordinary operating conditions of the system (depending on the redundancy level).

4.2.2 Features of Parallel System

  • The controls for parallel UPS module operation are standard in the Liebert NX, and the configuration can be set up by changing the settings in configuration software.
  • It is easy to install the parallel cables in a ring, providing high reliability and redundancy. And the intelligent paralleling logic provides the user with maximum flexibility. For example, shutting down or starting up the UPS modules in the parallel system can be done in any sequence. If an overload transfer occurs, the whole system can recover automatically from bypass mode after the overload is cleared.
  • The total load of the parallel system can be queried from each module’s liquid crystal display screen.
Show 6 more labels / short text on this page
Options · Parallel Board · Parallel Board · Parallel Board · Parallel Board · DBS Cable
Page 36 of the Emerson 480V user manual — 4.3 Installing Parallel System
Page 36 · click to enlarge
Page 36

Figure 16 Parallel system block diagram

480V 3W+G

480V 3W+G

CB 3

CB 3A

CB 1 CB 4

FPC

SBS

AC

AC

UPS

4.2.3 Operating Principles

Redundancy Paralleling

The parallel redundant system can noticeably improve system reliability. In normal condition, none of the UPS modules work at full load. That means that even if the load is increased, the system will not transfer to bypass. And when a UPS module shuts down due to any failure, the remaining UPS mod- ules can still power and protect the load. When redundancy is lost due to module failure or load increase, the parallel system will trigger an alarm.

4.2.4 Operation Modes Summary

The parallel system also has operation modes such as normal, battery, bypass and maintenance bypass. All UPS modules in the parallel system operate in coordination.

  • Normal Mode Operation The load is powered by the inverters of all the UPS modules in the system. If the frequency of bypass is within the synchronous range, the inverter will be synchronized with the bypass. Otherwise, the system will operate at nominal frequency.
  • Battery Mode Operation The batteries of all UPS modules power the load through their inverters. The system operates at nominal frequency.
  • Bypass Mode Operation The condition to transfer to bypass mode is essentially the same as that of single module system. The bypass of all the UPS modules powers the load.
  • Maintenance Bypass Mode Operation The sequence to transfer to maintenance bypass mode is the same as for transferring a singlemodule system. The maintenance bypass switches should be switched on as synchronously as possible. Thus the system can be repaired without interrupting the power supply to critical load.

4.3 Installing Parallel System

The basic installation procedure of parallel system is the same as that of single module system. The following sections introduce only the installation procedures specific to the parallel system.

Show 8 more labels / short text on this page
Options · Output Input · Tie breaker · Optional additional · Optional additional · systems · systems · I Line
Page 37 of the Emerson 480V user manual — 4.3.5 Parallel Control Cables
Page 37 · click to enlarge
Page 37

4.3.1 Conditions for Parallel System

  • Each UPS module must have the same bypass source.
  • The outputs of all UPS modules are connected altogether.
  • The main inputs can be from different sources, but the phase rotation sequence of main inputs, bypass inputs and outputs must be correct and the same.
  • The parallel logic cable and load sharing cable must be connected in a ring correctly (see Figure 17 ).

4.3.2 Cabinet Installation

Parallel system composed of two or more UPS modules using parallel cabinet

The UPS modules that will form the parallel system should be placed side-by-side. Each battery cabi- net is placed next to its corresponding UPS module.

The parallel cabinet should be placed in the middle of the system.

4.3.3 Preliminary Checks

Each UPS module should have the same firmware and the same hardware version. Refer to the instructions in 4.3.1 - Conditions for Parallel System.

4.3.4 Power Cables

Wiring of power cables is similar to that of a single module system (See 2.1 - Power Cabling). The bypass sources of all modules should be the same, and the outputs should be connected altogether cor- rectly.

Power cables are field-supplied. Power cables to the UPS’s of the paralleling cabinet must be routed through either the top or bottom entry access of the UPS.

4.3.5 Parallel Control Cables

Parallel System Control Cables

Make the connections listed below on the parallel logic board (M3) inside the Liebert NX. (See Figure 23 for the location of the parallel logic board):

Shielded and double-insulated control cables, available in lengths of up to 100 feet (30m), must be interconnected in a ring configuration between UPS modules as shown below. The ring configuration ensures high reliability of the control (refer to Figure 17).

Options

Page 38 of the Emerson 480V user manual — Figure 18 Auxiliary dry contact cables for output breaker in multi-module system
Page 38 · click to enlarge
Page 38

Figure 17 Connecting system parallel control cables

Emerson 480V — Figure 17 Connecting system parallel control cables diagram (page 38)
Fig. 15 · Figure 17 Connecting system parallel control cables
Emerson 480V — Figure 17 Connecting system parallel control cables diagram (page 38)
Fig. 16 · Figure 17 Connecting system parallel control cables

The external output breaker of each UPS must have Normally Open auxiliary contacts. These con- tacts must be wired to connector X3 on the Parallel Logic Board (M3). See Figures 18 and 19.

Figure 18 Auxiliary dry contact cables for output breaker in multi-module system

! CAUTION The auxiliary control wire must be installed to ensure proper operation of the system.

Options · Interconnecting · Cables

Page 39 of the Emerson 480V user manual — Figure 19 Dry contacts, multiple UPS modules with distribution panel
Page 39 · click to enlarge
Page 39

Figure 19 Dry contacts, multiple UPS modules with distribution panel

UPS 1

UPS 2

UPS N

X3 Ext. Maint. Ext. Out

X3 Ext. Maint. Ext. Out

X3 Ext. Maint. Ext. Out

Show 8 more labels / short text on this page
Options · Input Distribution · M 3 Board · M3 Board · M 3 Board · Q1Ext Q2Ext QnExt · QUPS QByp · To Load
Page 40 of the Emerson 480V user manual — Figure 20 Connecting EPO push button
Page 40 · click to enlarge
Page 40

4.3.6 Emergency Power Off (EPO)

The external emergency stop facility is identical to that described for the single unit installation— that an individual emergency stop button is provided for each unit.

Figure 20 Connecting EPO push button

UPS2

X2:3 X2:4 Monitor Board

X2:3

X2:4 Monitor Board

UPS1

Normally Open EPO

UPS2

X2:1 X2:2

Monitor Board

X2:1 X2:2

Monitor Board

UPS1

Normally Closed EPO

Options

Page 41 of the Emerson 480V user manual — Table 7 UPS mechanical characteristics
Page 41 · click to enlarge
Page 41

5.0 UPS S PECIFICATIONS

These specifications describe requirements for the Liebert NX UPS.

5.1 Conformity and Standards

The UPS has been designed to conform to the following standards:

  • IEEC 61000-4-5
  • ASME
  • CSA 22.2, No. 107.1
  • FCC Part 15, Class A
  • ISO 9001
  • National Electrical Code (NFPA-70)
  • NEMA PE-1
  • OSHA
  • UL Standard 1778

The UPS system has UL and c-UL approval.

5.2 UPS Environmental

The UPS is designed to operate under the following environmental conditions without damage or deg- radation in electrical operating characteristics:

Table 6 Environmental characteristics

Rated Power 40kVA 60/80kVA 100/120kVA

Operating Temperature, UPS 32°F to 104°F (0°C to 40°C)

Optimal Operating Temperature, Battery 68°F to 86°F (20°C to 30°C)

Relative Humidity 0 to 95%, non-condensing

Acoustical Noise, dBA at 39 in. (1m) 62 62 64

Altitude of Operation ≤1000m per IEC 62040/3

Storage-Transport Temperature, UPS, -4°F to 158°F (-20°C to 70°C)

Storage-Transport Temperature, Battery -4°F to 86°F (-20°C to 30°C)

5.3 UPS Mechanical Characteristics

Table 7 UPS mechanical characteristics

Width, in. (mm) 23.6 (600)

Depth, in. (mm) 38 (965)

Height, in. (mm) 78.5 (2000)

Heat Dissipation, BTU/H (kWH) 5200 (1.52) 5500 (1.61)

Airflow, CFM (m3/h) 1760 (2990) 1668 (2834)

Cable Entry Bottom or Top

Protection Grade (with open/closed front doors) IP 20

Weight, lb (kg) 1290 (585) 1422 (645)

UPS Specifications · Parameter 80kVA 120kVA · Color Black (Z-0350)

Page 42 of the Emerson 480V user manual — 40 48 66.8 70 8M 54106 ADR21
Page 42 · click to enlarge
Page 42

5.4 UPS Electrical Characteristics

Table 8 UPS terminal

Input (For Single-Input Unit)

Maximum Recommended Lug (Thomas & Betts part number)

2-Hole; 3/8" Bolt Mechanical

40 48 66.8 80.2 90 8M 54106 ADR21

60 72 100.2 120.3 125 8M 54108 ADR21

80 96 133.6 160.4 175 8M 54157 ADR21

100 120 167.1 200.5 225 8M 54167 ADR50

120 144 200.5 240.6 250 8M 54172-TB ADR50

Rectifier input (for dual input unit only)

Maximum Recommended Lug (Thomas & Betts part number)

2-Hole; 3/8" Bolt Mechanical

40 48 67.5 83 90 8M 54106 ADR21

60 72 101.3 124.5 125 8M 54108 ADR21

80 96 135 166 175 8M 54157 ADR21

100 120 168.8 207.6 225 8M 54167 ADR50

120 144 202.5 249.1 250 8M 54172-TB ADR50

Bypass input (for dual input units)

Maximum Recommended Lug (Thomas & Betts part number)

2-Hole; 3/8" Bolt Mechanical

40 48 66.8 70 8M 54106 ADR21

60 72 100.2 110 8M 54107 ADR21

80 96 133.6 150 8M 54152-TB ADR21

100 120 167.1 175 8M 54157 ADR21

120 144 200.5 225 8M 54167 ADR50

Maximum Recommended Lug (Thomas & Betts part number)

2-Hole; 3/8" Bolt Mechanical

40 48 66.8 70 8M 54106 ADR21

60 72 100.2 110 8M 54107 ADR21

80 96 133.6 150 8M 54152-TB ADR21

100 120 167.1 175 8M 54157 ADR21

120 144 200.5 225 8M 54167 ADR50

Show 40 more labels / short text on this page
UPS Specifications · Nominal · Maximum · OCP Device Rating · Compression · Unit Rating · Input Current · Input Current · OCP Current · Bolt Size · 2-Hole; · Nominal · Maximum · OCP Device Rating · Compression · Unit Rating · Input Current · Input Current · OCP Current · Bolt Size · 2-Hole · Nominal · Maximum · OCP Device Rating · Compression · Unit Rating · Input Current · Input Current · Bolt Size · 2-Hole · Output · Nominal · Maximum · OCP Device Rating · Compression · Unit Rating · Input Current · Input Current · Bolt Size · 2-Hole
Page 43 of the Emerson 480V user manual — Table 11 Liebert approved replacement batteries
Page 43 · click to enlarge
Page 43

Table 8 UPS terminal (continued)

Maximum Recommended Lug (Thomas & Betts Part Number)

2-Hole; 3/8" bolt Mechanical

40 82 at 480VDC 98 at 400VDC 70 8M 54106 ADR21

60 122 at 480VDC 146 at 400VDC 110 8M 54107 ADR21

80 163 at 480VDC 195 at 400VDC 150 8M 54152-TB ADR21

100 204 at 480VDC 244 at 400VDC 175 8M 54157 ADR21

120 244 at 480VDC 293 at 400VDC 225 8M 54167 ADR50

1. Nominal (Nom) current is based on full rated output load. 2. Maximum (Max) current (125% of nominal) is short duration for battery recharge conditions. 3. UPS input and bypass cables must be run in separate conduit from output cables. 4. Nominal battery voltage is shown at 2.0 volts/cell per NEC 480-2. 5. OCPD = Overcurrent Protection Device. Recommended AC input and AC output overcurrent protection represents 125% of nominal full load current (continuous) per NEC 215. 6. Minimum-sized grounding conductors to be per NEC 250-122. Parity-sized ground conductors are recommended. Neutral conductors to be sized for full capacity per NEC 310-15 (b)(4). References are per NEC 1999. 7. Wiring requirements: a. AC Input: 3-phase, 4-wire, plus ground output. b. AC Output: 3-phase, 3- or 4-wire, plus ground 8. All wiring is to be in accordance with national and local electric codes.

5.4.1 Input Rectifier

Table 9 Rectifier input power

Rated Power kVA 40 60 80 100 120

Rated Voltage, VAC 480

Supply 3-phase, 3-wire plus ground

Input Voltage Tolerance, VAC (without derating)

Power Factor > 0.99 at full load; >0.98 at half load

Harmonic Current Less than 3% at full rated UPS output load

See Table 8 for current ratings. Overload capacity of input current: 100% Imax

Table 10 Input voltage window with derating

Input Voltage Window

Percentage

Inverter Load,

Charger Load,

(L-L Voltage)

of Nominal

Percentage

Percentage

432VAC to 552VAC 90-115 100% 100%

431VAC to 384VAC 80-89 100% 30%

383VAC to 360VAC 75-79 100% 0%

359VAC to 288VAC 60-74 80% 0%

Table 11 Liebert approved replacement batteries

Battery Manufacturer Models Supplied

Enersys Yuasa HX205 — —

C&D Dynasty UPS12-100MR UPS12-150MR UPS12-210MR

Show 13 more labels / short text on this page
UPS Specifications · Battery · Nominal · Maximum · OCP Device Rating · Compression · Unit Rating · Input Current · Input Current · Bolt Size · 2-Hole; · 384-552 · Frequency, Hz 57-66
Page 44 of the Emerson 480V user manual — 5.4.4 Bypass Input
Page 44 · click to enlarge
Page 44

5.4.2 DC Intermediate Circuit

Table 12 DC intermediate circuit

Rated Power kVA 40 60 80 100 120

Recommended number of lead-acid batteries Total 40 battery blocks of 12VDC (240 cells of 2VDC)

will be supported by UPS

Recommended float charge voltage 2.27VDC *

Recommended boost charge voltage 2.4VDC *

Recommended end of discharge voltage 1.67 - 1.75 VDC

Maximum recharge battery current, A * 14.8 22.2 29.6 37.0 44.4

Maximum boost charge duration, min. * 1800

Boost-float threshold current, A * 0.1 C default

Temperature voltage compensation, mV/°C * From 0 to 5 mV/deg. C/cell. Default value is 3mV/deg. C/cell.*

Ripple voltage superimposed % ≤ 1

* Set by configuration software and based on usage of VLRA batteries.

See Table 8 for current ratings.

5.4.3 Inverter Output

Table 13 Inverter output

Rated Power kVA 40 60 80 100 120

Rated voltage, VAC 480

Supply 3-phase, 3-wire plus ground

Frequency, Hz 60 (50Hz in frequency converter mode)

Rated Power, kW 36 54 72 90 108

Three-phase transient overload, min. load

105% to 110% for 60 minutes 111% to 125% for 10 minutes

126% to 150% for 1 minute

Voltage Regulation % ±1.0% three-phase RMS average for a balanced three-phase load

±2.0% three-phase RMS average for a 100% unbalanced load

Frequency Regulation % Nominal frequency regulation is ±0.05% in single module mode,

and+/- 0.25% in parallel mode.

Maximum rate of change of frequency, Hz/sec For single mode, the slew rate is adjustable from 0.1Hz/s to 3Hz/s

See Table 8 for current ratings.

5.4.4 Bypass Input

Table 14 Bypass input

Rated Power, kVA 40 60 80 100 120

Rated voltage, VAC 480

Supply Three-phase, 3-wire plus ground

Bypass voltage tolerance % Upper limit: +10%, +15% or +20%; Upper limit default: +15% Lower limit: -10%, -20%, -30% or -40%; Lower limit default: -20%

Input frequency tolerance % ±2.5%, ±5%, ±10% and ±20%; default ±10%

Time Long-term operation:

Load

Bypass overload capacity (all ratings)

10 minutes100 milliseconds:

See Table 8 for current ratings.

UPS Specifications · Frequency, Hz 60

Page 45 of the Emerson 480V user manual — Front
Page 45 · click to enlarge
Page 45

6.0 I NSTALLATION D RAWINGS

The diagrams in this section illustrate the key mechanical and electrical characteristics of the Liebert NX UPS System cabinets.

Figure 21 Dimensional viewfront and left side views

Center of Gravity Without Internal Battery

600mm (23.6")

2000mm (78.7")

997mm (39.3")

301mm (11.9")

39.6mm (1.6")

360mm (14.2")

Front

Left Side

1. All dimensions are in millimeters (in.). 2. Eight-inch minimum clearance above unit required for air exhaust. 3. Keep cabinet within 15 deg. of vertical while handling. 4. Top and bottom cable entry available through removable access plates. Remove access plate, punch to suit conduit size and replace. 5. Color - black. 6. Unit bottom is structurally adequate for forklift handling. 7. Open door to replace air filter, washable type. 8. M10 threaded mounting holes used for seismic anchoring or floor stand. NOTE: If floor stand is used, the weight of the unit must be supported under all casters.

9. Each mounting location is supported by (2) 10ga. (.135") galvanized steel. The threaded insert is approx. 3/4" deep. Mounting holes are underneath unit base; mounting bolts must be threaded into unit. 10. Includes side panel. Side panels must be removed from adjacent units that are bolted together. 11. Leveling feet are not designed to carry the full weight of the cabinet. 12. Finger-tighten leveler against the floor, then tighten with a wrench less than 2 turns for friction fit against floor.

Installation Drawings · Liquid Crystal Display

Page 46 of the Emerson 480V user manual — Figure 23 Main components—typical unit
Page 46 · click to enlarge
Page 46

Figure 22 Dimensions continued—top and bottom views

Emerson 480V — Figure 22 Dimensions continued—top and bottom views diagram (page 46)
Fig. 17 · Figure 22 Dimensions continued—top and bottom views

Figure 23 Main components—typical unit

Emerson 480V — Figure 23 Main components—typical unit diagram (page 46)
Fig. 18 · Figure 23 Main components—typical unit

Installation Drawings

Page 47 of the Emerson 480V user manual — LEFT SIDE VIEW (with side panel removed) FRONT VIEW (with door removed)
Page 47 · click to enlarge
Page 47

Figure 24 Cable connections

Emerson 480V — Figure 24 Cable connections diagram (page 47)
Fig. 19 · Figure 24 Cable connections

LEFT SIDE VIEW (with side panel removed) FRONT VIEW (with door removed)

NOTES 1. All dimensions are millimeters (in.). 2. Top and bottom cable entry available through removable access plates. Remove, punch to accommodate conduit size and replace. 3. Control wiring and power wiring must be run in separate conduit. Output and input cables must be run in separate conduit. 4. Aluminum and copper-clad aluminum cables are not recommended. 5. All wiring is to be in accordance with national and local electrical codes.

Installation Drawings

Page 48 of the Emerson 480V user manual — U3819204
Page 48 · click to enlarge
Page 48

Figure 25 Outline drawing, 33" battery power pack system, single cabinet

896.6 (35.3)

169.5 (6.7)

372.7 (14.7)

172.1 (6.8)

26.8 (1.1)

609.3 (24)

474.3 (18.7)

322.9 (12.7)

575.9 (22.7)

322.9 (12.7)

779.1 (30.7)

872.2 (34.3)

Bottom (Viewed From Below)

Max. Door Swing120° 490.3 (19.3)

Top (Viewed From Above)

845 (33.2)

418.9 (16.5)

Leveling Feet (See Note #9)

2000 (78.7)

683 (26.9)

1. All dimensions are in millimeters (inches) 2. Minimum clearance 36" front and 8" top required for air exhaust. 3. Top and bottom cable entry available through removable access plates. 4. Keep cabinet within 15 deg. of vertical while handling. 5. Control wiring and power wiring must be run in separate conduit. 6. Aluminum and copper clad cables are not recommended. 7. All wiring is to be in accordance with national and local electrical codes. 8. Intercabinet wiring between the UPS and the external battery cabinet is field-supplied. 9. Leveling feet are not designed to carry the full weight of the cabinet. Finger-tight leveler against the floor, then tighten with a wrench less than 2 turns for friction fit against floor. 10. Side panels included. 11. M10 threaded mounting holes used for seismic anchoring or floor stand. NOTE: If floor stand is used the weight of the unit must be supported under all casters. Mounting holes same spacing front and rear. 13. Battery-support tray connects to the front of the cabinet with the support brackets. Without the support, the battery may fall out of the cabinet.

U3819204

Show 6 more labels / short text on this page
Installation Drawings · 965 (38) · Center of Gravity · Center of Gravity · Right Side · Front (Without Door)
Page 49 of the Emerson 480V user manual — Figure 26 Terminal details, 33" battery power pack system, single cabinet Liebert NX
Page 49 · click to enlarge
Page 49

Figure 26 Terminal details, 33" battery power pack system, single cabinet Liebert NX

Emerson 480V — Figure 26 Terminal details, 33" battery power pack system, single cabinet Liebert NX diagram (page 49)
Fig. 20 · Figure 26 Terminal details, 33" battery power pack s…

NOTES: 1. All dimensions are in millimeters (inches). 2. All cables should be routed before bolting cabinets together. 3. The cables between the battery cabinet and the UPS cabinet must be supplied by others. 4. All hardware supplied with battery cabinet for bolting cabinet to UPS use M6 hardware provided; assemble as shown in detail drawings. 5. All external wiring is to be in accordance with national and local electrical codes.

Installation Drawings

Page 50 of the Emerson 480V user manual — Figure 27 Battery connections
Page 50 · click to enlarge
Page 50

Figure 27 Battery connections

Emerson 480V — Figure 27 Battery connections diagram (page 50)
Fig. 21 · Figure 27 Battery connections

Installation Drawings

Page 51 of the Emerson 480V user manual — Figure 28 Battery cabinet interconnection
Page 51 · click to enlarge
Page 51

Figure 28 Battery cabinet interconnection

Emerson 480V — Figure 28 Battery cabinet interconnection diagram (page 51)
Fig. 22 · Figure 28 Battery cabinet interconnection
Emerson 480V — Figure 28 Battery cabinet interconnection diagram (page 51)
Fig. 23 · Figure 28 Battery cabinet interconnection

A UPS Battery Terminal Block First External Battery Cabinet Positive, Negative

Control Terminal Block UPS Monitoring Board Battery Breaker Auxiliary Contacts

Installation Drawings

Page 52 of the Emerson 480V user manual — 2000 (78.7)
Page 52 · click to enlarge
Page 52

Figure 29 Outline drawing, Liebert NX480V, 80-120kVA Type E and E2 parallel cabinet

800 (31.5)

965 (38)

Top

Right Side

NOTE:

1. All dimensions are in millimeters (in). 2. Eight-inch minimum clearance above unit required for air exhaust. 3. Keep cabinet within 15 deg. of vertical while handling. 4. Top and bottom cable entry available through removable access plates. Remove access plate, punch to suit conduit size and replace. 5. Color - black. 6. Unit bottom is structurally adequate for forklift handling. 7. M10 threaded mounting holes used for seismic anchoring or floor stand. NOTE: If floor stand is used, the weight of the unit must be supported under all casters. 8. Each mounting location is supported by two 10 ga. (.135") galvanized steel. The threaded insert is approximately 3/4" deep. Mounting holes are underneath unit base; mounting bolts must be threaded into unit. 9. Side panels must be removed from adjacent units that are bolted together. 10. Leveling feet are not designed to carry the full weight of the cabinet. Finger-tighten leveler against the floor, then tighten with a wrench less than 2 turns for friction fit against floor.

2000 (78.7)

Front

Installation Drawings

Page 53 of the Emerson 480V user manual — Figure 30 Outline drawing, Liebert NX480V, 80-120kVA Type E1 parallel cabinet
Page 53 · click to enlarge
Page 53

Figure 30 Outline drawing, Liebert NX480V, 80-120kVA Type E1 parallel cabinet

Emerson 480V — Figure 30 Outline drawing, Liebert NX480V, 80-120kVA Type E1 parallel cabinet diagram (page 53)
Fig. 24 · Figure 30 Outline drawing, Liebert NX480V, 80-120kVA…

1. All dimensions are in millimeters (in). 2. Eight-inch minimum clearance above unit required for air exhaust. 3. Keep cabinet within 15 deg. of vertical while handling. 4. Top and bottom cable entry available through removable access plates. Remove access plate punch to suit conduit size and replace. 5. Color - black. 6. Unit bottom is structurally adequate for forklift handling. 7. M10 threaded mounting holes used for seismic anchoring or floor stand. NOTE: If floor stand is used, the weight of the unit must be supported under all casters. 8. Each mounting location is supported by two 10 ga. (.135") galvanized steel. The threaded insert is approximately 3/4" deep. Mounting holes are underneath unit base; mounting bolts must be threaded into unit. 9. Side panels must be removed from adjacent units that are bolted together. 10. Leveling feet are not designed to carry the full weight of the cabinet. Finger-tighten leveler against the floor, then tighten with a wrench less than 2 turns for friction fit against floor.

Installation Drawings

Page 54 of the Emerson 480V user manual — Front Rear
Page 54 · click to enlarge
Page 54

Figure 31 Main component location drawing Liebert NX 480V, Type E parallel cabinet

System O/P Tie Breaker

Kirk - Key Fuse Disconnect

System Bypass Tie Breaker

Front Rear

Show 6 more labels / short text on this page
Installation Drawings · System Input · UPS Output Breaker · UPS Input Breakers · Ground Busbar · System Output Busbar
Page 55 of the Emerson 480V user manual — Rear Without Covers
Page 55 · click to enlarge
Page 55

Figure 32 Main component location drawing Liebert NX 480V, Type E1 parallel cabinet

System Input 1240 (48.8)

2000 (78.7)

Front (With Covers )

Rear Without Covers

Show 9 more labels / short text on this page
Installation Drawings · UPS Input · Ground Bus · Bypass Tie Breaker · Front Without Covers · Output Distribution · Bypass Tie Breaker · UPS Output · Rear With Covers
Page 56 of the Emerson 480V user manual — FRONT
Page 56 · click to enlarge
Page 56

Figure 33 Main component location drawing Liebert NX 480V, Type E2 parallel cabinet

System O/P Tie Breaker

FRONT

Show 5 more labels / short text on this page
Installation Drawings · UPS Output Breakers · Kirk-Key Fuse Disconnect · Bround Busbar · System Output Busbars
Page 57 of the Emerson 480V user manual — Figure 34 Lineup detail—Parallel Type E connection to Liebert NX
Page 57 · click to enlarge
Page 57

Figure 34 Lineup detail—Parallel Type E connection to Liebert NX

Emerson 480V — Figure 34 Lineup detail—Parallel Type E connection to Liebert NX diagram (page 57)
Fig. 25 · Figure 34 Lineup detail—Parallel Type E connection t…

A Utility Source Parallel Cabinet Ph A, B, C - System

C1-C4 UPS #1-UPS #4 Module AC Output Parallel Cabinet Ph A, B, C - UPS Outputs

D Parallel Cabinet Critical Loads Ph A, B, C - System

Installation Drawings

Page 58 of the Emerson 480V user manual — Figure 35 Lineup detail—Parallel Type E1 connection to Liebert NX
Page 58 · click to enlarge
Page 58

Figure 35 Lineup detail—Parallel Type E1 connection to Liebert NX

Emerson 480V — Figure 35 Lineup detail—Parallel Type E1 connection to Liebert NX diagram (page 58)
Fig. 26 · Figure 35 Lineup detail—Parallel Type E1 connection…

A Utility Source Parallel Cabinet Ph A, B, C - System Input

AC Input Ph A, B, C - UPS Inputs

AC Output Parallel Cabinet Ph A, B, C - UPS Outputs

D Parallel Cabinet Critical Loads Ph A, B, C - System Outputs

G1-G4 Parallel Cabinet UPS #1-UPS #4 Module UPS Parallel Logic Board (M3) Output Breaker Aux Contact

H1-H4 Parallel Cabinet UPS #1-UPS #4 Module UPS Parallel Logic Board (M3) UPS Bypass Detection

Installation Drawings

Page 59 of the Emerson 480V user manual — Figure 36 Lineup detail—Parallel Type E2 connection to Liebert NX
Page 59 · click to enlarge
Page 59

Figure 36 Lineup detail—Parallel Type E2 connection to Liebert NX

Emerson 480V — Figure 36 Lineup detail—Parallel Type E2 connection to Liebert NX diagram (page 59)
Fig. 27 · Figure 36 Lineup detail—Parallel Type E2 connection…
Emerson 480V — Figure 36 Lineup detail—Parallel Type E2 connection to Liebert NX diagram (page 59)
Fig. 28 · Figure 36 Lineup detail—Parallel Type E2 connection…

C1-C4 UPS #1-UPS #4 Module AC Output Parallel Cabinet Ph A, B, C - UPS Outputs

D Parallel Cabinet Critical Loads Ph A, B, C - System Outputs

E1-E4 Parallel Cabinet UPS #1-UPS #4 Module Gnd Ground - UPS

G1-G4 Parallel Cabinet UPS #1-UPS #4 Module UPS Parallel Logic Board (M3) Output Breaker Aux Contact

H1-H4 Parallel Cabinet UPS #1-UPS #4 Module UPS Parallel Logic Board (M3) UPS Bypass Detection

Installation Drawings

Page 60 of the Emerson 480V user manual — DETAIL A
Page 60 · click to enlarge
Page 60

Figure 37 Line-up detail, bolt together description, 40-120 kVA Liebert NX

LEFT SIDE (Without Exterior Panels)

LEFT SIDE (Isometric View)

965 (38 in.)

NOTES: 1. All dimensions are in millimeters (inches) 2. All cables should be routed before bolting cabinets together. 3. The cables between the auxillary cabinets and the UPS cabinet must be supplied by customer. 4. All hardware supplied with ancillary cabinets for bolting cabinet to UPS. 5. Use M6 hardware provided. Assemble as shown in detail drawing. 6. All external wiring is to be in accordance with national and local codes.

2000 (78.7 in)

Remove when cabinets are to be bolted together

DETAIL A

U3819301

A

RIGHT SIDE (Without Exterior Panels)

Installation Drawings

Page 61 of the Emerson 480V user manual — Figure 38 Single module block diagram (dual input configuration)
Page 61 · click to enlarge
Page 61

7.0 O PERATION

7.1 General Description

Liebert’s NX provides continuous, high-quality AC power to your business-critical equipment, such as telecommunications and data processing equipment. The Liebert NX UPS supplies power that is free of the disturbances and variations in voltage and frequency common to utility power, which is subject to brownouts, blackouts, surges and sags.

The Liebert NX utilizes the latest in high-frequency, double-conversion pulse width modulation tech- nology and fully digital controls to enhance its reliability and increase the ease of use. Specifically, the Liebert NX 480V utilizes soft-switching technology to greatly enhance efficiency.

As shown in Figure 38, the AC utility source is input at CB1 and the rectifier converts the AC utility into DC power. The inverter converts that DC power from the utility—or DC power from the batter- ies—into AC power for the load. The batteries power the load through the inverter in the event of a power failure. The utility source can also power the load through the static bypass.

If maintenance or repair of the UPS is necessary, the load can be switched without interruption in service to the maintenance bypass.

Figure 38 Single module block diagram (dual input configuration)

Emerson 480V — Figure 38 Single module block diagram (dual input configuration) diagram (page 61)
Fig. 29 · Figure 38 Single module block diagram (dual input co…

Operation

Page 62 of the Emerson 480V user manual — Bypass Mode
Page 62 · click to enlarge
Page 62

7.1.1 Bypass Supplies

The Liebert NX contains an electronically controlled switching circuit that enables the critical load to be connected to either the inverter output or to a bypass power source via the static bypass line. Dur- ing normal system operation the load is connected to the inverter and the inverter contactor is closed; but in the event of a UPS overload or an inverter failure, the load is automatically transferred to the static bypass line.

To provide a clean (no-break) load transfer between the inverter output and static bypass line, the bypass static switch activates, connecting the load to bypass. To achieve this, the inverter output and bypass supply must be fully synchronized during normal operating conditions. This is achieved through the inverter control electronics, which make the inverter frequency track that of the static bypass supply, provided that the bypass remains within an acceptable frequency window.

A manually controlled, maintenance bypass supply is incorporated into the UPS design. It enables the critical load to be powered from the utility (bypass) supply while the UPS is shut down for routine maintenance.

In dual input configuration, the neutrals of each source must be connected to each other, to guarantee that the dual source has the same voltage potential to earth.

7.1.2 Operating Modes

The UPS is designed to operate as an on-line, double-conversion, reverse-transfer system in the fol- lowing modes:

Normal Mode

Operating in normal mode, the Liebert NX’s rectifier derives power from a utility AC source and sup- plies regulated DC power to the inverter, which regenerates precise AC power to supply the connected equipment. The rectifier also uses the utility source power to charge the batteries.

Battery Mode

When utility AC power fails, the Liebert NX protects the critical load by instantaneously channeling battery power to the inverter, which continues supporting the critical load without interruption. When utility power returns and is within acceptable limits, the Liebert NX automatically shifts back to Normal mode, with the rectifier powering the critical load.

Bypass Mode

When the Liebert NX is in bypass mode, the load is directly supported by utility power and is without battery backup protection.

The Liebert NX’s inverter static switch and bypass static switch will shift the load from the inverter to bypass mode without an interruption in AC power if the inverter is synchronous with the bypass and any of the following occurs:

  • inverter fails
  • inverter overload capacity is exceeded
  • inverter is manually turned off by the user

Operation

Page 63 of the Emerson 480V user manual — Frequency Converter Mode
Page 63 · click to enlarge
Page 63

Maintenance Mode

For maintenance or repair, the Liebert NX may be operated in maintenance mode. To place the Lie- bert NX in maintenance mode, the load must be transferred to bypass and the inverter must be turned off. When those conditions are met, the CB3 may be turned on and the UPS may be shut down, permitting disconnecting the batteries for maintenance.

! CAUTION The internal maintenance bypass must not be used when the UPS system is in a parallel system.

! WARNING The UPS input and output must be protected with external overcurrent protection devices. In maintenance mode, the input and output busbars remain energized.

Parallel Redundancy Mode (System Expansion)

For higher capacity, higher reliability or both, the outputs of up to four UPS modules can be pro- grammed for directly paralleling while a built-in parallel controller in each UPS ensures automatic load-sharing.

Frequency Converter Mode

The Liebert NX can be programmed into frequency converter mode for either 50Hz or 60Hz stable output frequency. The input frequency may vary from 57Hz to 66Hz. In this mode, the static bypass operation is disabled and the battery becomes optional, depending on any requirement to operate in battery mode (stored energy mode).

Operation

Page 64 of the Emerson 480V user manual — INVERTER ON
Page 64 · click to enlarge
Page 64

Operator Control and Display Panel

8.0 O PERATOR C ONTROL AND D ISPLAY P ANEL

8.1 Operator Control Panel

The control panel and LCD on the front of the Liebert NX let the operator:

  • turn the UPS On or Off
  • transfer into the various operating modes
  • silence alarms
  • check the status of the UPS and its batteries, including all measured parameters, events and alarms

The main areas of the control panel are shown below in Figure 39 and detailed in Figure 40.

  • Mimic Display - view the status of the Liebert NX in single-line diagram format—indicators show status by changing color when ON, flashing or OFF
  • Liquid Crystal Display (LCD) and Navigation keys - view status and operational data from the Liebert NX in tabular format
  • Control buttons - turn the Liebert NX on or off, silence alarms

Figure 39 Overview of control panel

Liebert NX 2007-01-06 09:20:37 Single Normal 80kVA-3X3

Liquid Crystal Display (LCD)

L1-N/L2

L2-N/L 3

L3-N/L 1

LED1

L-N current(A) Frequency (HZ)

buttons Control Mimic display

59.9 480 0.99

480 0.99

480 0.99

EPO

LED2

LED4 LED5

INVERTER OFF FAULT CLEAR

Input disconnect closed 01-06 09:15

LED3

Output disconnect closed 01-06 09 :15

SILENCE ON/OFF

Bypass abnormal 01-06 09:15

INVERTER ON

STATUS

F2 F4 HELP F1 F3

8.1.1 Display Panel Layout

Figure 40 shows the control panel in greater detail, identifying individual items that are described in the rest of this section.

Show 8 more labels / short text on this page
Bypass Main · Output · L-L voltage (V) · PowerFactor · ? · Navigation · keys · 30kVA 3X3
Page 65 of the Emerson 480V user manual — Figure 40 Detailed view of control panel
Page 65 · click to enlarge
Page 65

Operator Control and Display Panel

Figure 40 Detailed view of control panel

1 3 2 4 5 6

8 9 10 11

Emerson 480V — Figure 40 Detailed view of control panel diagram (page 65)
Fig. 30 · Figure 40 Detailed view of control panel

14 15 16 17 18 19

Mimic indicators Control buttons Navigation keys 1. Rectifier indicator 8. Inverter Off Button 15. F1 2. Battery indicator 9. Emergency Power Off Button 16. F2 3. Inverter indicator 10. EPO Cover 17. F3 4. Bypass indicator 11. Fault Clear Button 18. F4 5. Load indicator 12. Silence On/Off Button 19. Help 6. Status indicator 13. Inverter On Button 7. Buzzer 14. LCD

Page 66 of the Emerson 480V user manual — Table 15 Mimic display status indicators
Page 66 · click to enlarge
Page 66

Operator Control and Display Panel

8.2 Mimic Display Indicators

The Mimic display on the front panel consists of six indicators arranged in a single-line diagram depicting the various paths of UPS power, as shown in Figure 41.

Figure 41 Mimic display indicators location

Liebert NX 2007-01-06 09:20:37 Single Normal 80kVA-3X3

L1-N/L 2

L 2-N/L3

L 3-N/L1

L-N current (A) Frequency (HZ)

LED2

LED4 LED5

59.9 480 0.99

EPO

480 0.99

480 0.99

INVERTER OFF FAULT CLEAR

LED3

Output disconnect closed 01-06 09:15

Input disconnect closed 01-06 09:15

SILENCE ON/OFF

Bypass abnormal 01-06 09 :15

STATUS

INVERTER ON

F2 F4 HELP F1 F3

The current operational status of the Liebert NX is indicated by the color of the indicators—green, amber or red—and whether they are ON (solid), flashing or OFF. Table 15 provides a guide to inter- preting the various states of the indicators.

Table 15 Mimic display status indicators

(see Figure 41) Green Flashing Green / Amber Red Off

Rectifier Load on rectifier Flashing Green: Utility normal, but rectifier not operating

Rectifier fault Rectifier is normal, but utility is abnormal

Battery powering the load

Flashing GreenBattery prewarning (low battery)

Battery or battery converter abnormal*

Battery and converter are normal, and battery is not discharging

Inverter Inverter powering the load normally

Flashing GreenInverter on standby

Inverter fault Inverter normal, but off

Bypass Load on Bypass power — Bypass out of normal range

Load UPS output on — UPS output overloaded

UPS no output power

Status No alarms—UPS working normally

AmberUPS has a general alarm

UPS has a serious alarm —

* Battery or battery converter abnormal events include these event messages (see Appendix A): No Battery, Battery Replaced, Battery Reverse, Batt. Conv. Over. Curr., Batt. Converter Fault, Batt. Converter Overtemp.

Show 15 more labels / short text on this page
Load indicator · Bypass indicator · Inverter indicator · Bypass Main LED1 · Output · Rectifier indicator · L-L voltage (V) · Battery indicator · PowerFactor · Buzzer · ? · Status indicator · Indicator · Battery · Bypass Normal
Page 67 of the Emerson 480V user manual — EPO
Page 67 · click to enlarge
Page 67

Operator Control and Display Panel

8.3 Control Buttons

The Control Buttons on the front panel may be used to shut down the UPS completely, turn the inverter On or Off, restart the UPS after a fault and silence the alarm, as shown in Figure 42. The function of each button is described in Table 16.

Figure 42 Location of control buttons

Button cover EPO button

Liebert NX 2007-01-06 09:20:37 Single Normal 80kVA-3X3

LED1

L1-N/L 2

L 2-N/L3

L 3-N/L1

70.8 59.9

71.3 59.9

LED2

LED4 LED5

59.9 480

EPO

L-L voltage (V) PowerFactor

480 0.99

480 0.99

INVERTER OFF FAULT CLEAR

Input disconnect closed 01-06 09:15

LED3

Output disconnect closed 01-06 09:15

SILENCE ON/OFF

Bypass abnormal 01-06 09 :15

STATUS

INVERTER ON

F2 F4 HELP F1 F3

Table 16 Control buttons

Button (see Figure 42) Function

Completely shuts down the UPS, including the static switch. CAUTION: Use caution before pressing the Emergency Power Off (EPO) button. This button completely shuts down the unit and cuts off power to the critical load.

EPO

Inverter Off Press this button to shut down the inverter during operation. The load will be transferred to static bypass.

Fault Clear After the UPS shuts down due to a fault and the alarm condition has been resolved, press this button to clear the fault and restart the UPS.

Press this button once to silence the alarm buzzer when an alarm is active. Any new fault will sound the buzzer again. If the alarm buzzer is not beeping, press this button to test the alarm sound.

Inverter On Press this button to start the inverter and transfer from static bypass to inverter. NOTE: If the inverter is not ready, this will not activate the UPS.

Show 10 more labels / short text on this page
Bypass Main · Output · Inverter Off button · L-N current (A) · Frequency (HZ) · Fault Clear button · Silence On/Off button · Inverter On button · ? · Silence On/Off
Page 68 of the Emerson 480V user manual — Navigation key icons
Page 68 · click to enlarge
Page 68

Operator Control and Display Panel

8.4 Audible Buzzer

The buzzer produces three types of sounds:

  • Single beep - when any control button is pressed
  • Single beep repeating every two seconds - the system has a general alarm
  • Continuous - the system has a serious fault

If the buzzer makes no sound, the system may be operating properly, or an alarm may have been silenced manually.

Figure 43 Buzzer location

Liebert NX 2007-01-06 09:20:37 Single Normal 80kVA-3X3

LED1

L 1-N/L2

L2-N/L3

L3-N/L1

L-N current (A) Frequency (HZ)

LED2

LED4 LED5

59.9 480 0.99

EPO

480 0.99

480 0.99

INVERTER OFF FAULT CLEAR

LED3

Output disconnect closed 01-06 09:15

Input disconnect closed 01-06 09:15

SILENCE ON/OFF

Bypass abnormal 01-06 09:15

STATUS

INVERTER ON

F2 F4 HELP F1 F3

8.5 LCD Overview

The LCD on the front panel has five main sections, as shown in Figure 44. Press the F1 key below the LCD to scroll through these sections.

  • UPS System Information - view UPS name and model, date and time, overall status (see Table 18 ).
  • LCD Menu - choose a category of data items to appear below the menus (see Table 19 ).
  • Data and Settings - view data items for the selected menu (see Table 19 ).
  • Current Status Messages - check any active UPS event and alarm messages (see Appendix A ).
  • Navigation Key Icons - look at the icon above each navigation key to determine how the key operates when pressed (see 8.6 - Navigation Keys ). The LCD displays alarm information in real time. After appearing in the current status section of the LCD, status messages are stored in the history log—512 records can be stored and retrieved.

Figure 44 Sections of the LCD

Liebert NX 2007-01-06 09:20:37 Single Normal 80kVA-3X3

UPS system information

Bypass Main LCD menu

L1-N/L2

L2-N/L3

L3-N/L1

L-N current(A) Frequency(HZ) L-L voltage(V) PowerFactor

71.4 59.9 480 0.99

70.8 59.9 480 0.99

71.3 59.9 480 0.99

Data and settings

Input disconnect closed 01-06 09:15

Current status messages

Output disconnect closed 01-06 09:15

Bypass abnormal 01-06 09:15

Navigation key icons

F2 F4 HELP F1 F3

Show 8 more labels / short text on this page
Bypass Main · Output · L-L voltage (V) · PowerFactor · Buzzer · ? · Output · ?
Page 69 of the Emerson 480V user manual — Table 18 Description of items in UPS system window
Page 69 · click to enlarge
Page 69

Operator Control and Display Panel

8.6 Navigation Keys

The navigation keys on the front panel—F1 through F4 and Help—are used to access the LCD to view the current status and other information about the Liebert NX.

Navigation key icons on the LCD appear above each key to indicate its operation (see Table 17). The keys are “soft keys” that can change functions according to the icon.

  • Use F1 either to move to a different portion of the LCD (Shift icon) or to escape to a previous view (ESC icon).
  • Use F2 and F3 as cursor keys to move left and right or up and down, depending on the icons displayed above the keys.
  • Use F4 as an Enter key to confirm a choice.
  • Use HELP to access help information on the LCD.

Table 17 Icons for navigation keys

Key F1 F2 F3 F4 HELP

? ESC

8.7 UPS System Information

The UPS system information displayed at the top of the LCD is detailed in Table 18.

Table 18 Description of items in UPS system window

Liebert NX UPS name 2007-10-12 Current date 12:30:36 Current time

080kVA-3x3 080 means UPS model is 80kVA; 3x3 means 3 by 3 system (three-phase input and three-phase output) Unit #1 #1 of 6 Paralleled changed to “Unit #1” Single UPS is configured as a single unit system running in Normal mode Normal UPS in normal operation, inverter powering load, no warnings Warning UPS has a general alarm Fault UPS has a serious fault

Show 5 more labels / short text on this page
Shift Left Right · Functions Available · Enter Help · Exit Up Down · Item Type Explanation
Page 70 of the Emerson 480V user manual — Figure 45 Menu tree
Page 70 · click to enlarge
Page 70

Operator Control and Display Panel

8.8 LCD Menus and Data Items

The LCD menus provide access to the following categories of information and settings for the UPS. Selecting a menu changes the information displayed in the UPS data items portion of the LCD. The menu choices are listed below and described in detail in Table 19.

  • Mains - view utility power input data: voltage, current, frequency and power factor
  • TX Input - view input transformer voltages
  • Bypass - view bypass data: voltage and frequency
  • Output - view output data: voltage, current, frequency and power factor
  • Load - view load data: load percent, output current, output power and crest factor (CF)
  • System - view system data
  • Battery - view battery characteristics—voltage, current, temperature and remaining time—and messages when the battery is boost/float charging or disconnected
  • Records - access the history log—displays all records in the log (newest records added at end)
  • Language - select a language for LCD text (choices appear in the native language)
  • Settings - configure UPS settings: adjust the display contrast, choose a format for date display, set the date and time, set up the UPS for modem communications (baud rate, address, mode and phone numbers to dial for alarm notifications) and change the password
  • Command - start or stop a battery maintenance test, battery capacity test or system test
  • Version - view firmware versions for the inverter, rectifier and software display board and the model information for the UPS Figure 45 shows a menu tree of the options available from the LCD menus.

Figure 45 Menu tree

L-N current (A) Frequency (Hz) L-L voltage (V) Power factor

Frequency (Hz) L-L voltage (V)

L-N current (A) Frequency (Hz) L-L voltage (V) Power factor

Sout (kVA) Pout (kW) Qout (kVAR) Loadlevel % Crest factor

Sout (kVA) Pout (kW) Qout (kVAR) Single unit, no parallel data

Battery voltage (V) Battery current (A) Battery temperature (°C) Remain Time Min. Battery boost charging Battery float charging Battery disconnected

Display contrast Date format set Date & time Comm1 baud rate Comm2 baud rate Comm3 baud rate Communication address Communication mode Callback times Phone No.1 Phone No.2 Phone No.3 Command password

Battery maintenance test Battery capacity test System test Stop testing Freshening Charge Stop Freshening Charge Modem auto-answer enable

UPS model Monitor version Rectifier version Inverter version

* When configured, input transformer voltages are displayed on the front LCD. When not activated, the values are hidden. ** When configured, output transformer voltages are displayed on the front LCD. When not activated, the values are hidden.

Show 17 more labels / short text on this page
Mains (input) · TX Input * · Bypass · Output · TX Output ** · L-L voltage (V) · L-L voltage (V) · Load · System · Battery · Records · (history log) · Language · Settings · Command · Version · (Choices for display)
Page 71 of the Emerson 480V user manual — Table 19 Descriptions of UPS menus and data window items
Page 71 · click to enlarge
Page 71

Operator Control and Display Panel

Table 19 Descriptions of UPS menus and data window items

Menu Type Item Type Explanation

L-N current (A) Phase current

Frequency (Hz) Input frequency

L-L voltage (v Line-line voltage

Power factor Power factor

TX Input L-L voltage (V) Line-line voltage

Bypass Frequency (Hz) Bypass frequency

L-L voltage (A) Line-line voltage

L-N current (A) Phase current

Frequency (Hz) Output frequency

L-L voltage (V) Line-line voltage

Power factor Power factor

TX Output L-L voltage (V) Line-line voltage

Sout (kVA) SoutApparent power
Pout (kW) PoutActive power
Qout (kVAR) QoutReactive power

Loadlevel % The percent of the UPS rating load

Crest factor Output current Crest Factor

Sout (kVA) SoutApparent power
Pout (kW) PoutActive power
Qout (kVAR) QoutReactive power

Single unit, no parallel data When configured as a single unit, UPS has only native load, no system load.

Battery voltage (V) Battery bus voltage

Battery current (A) Battery bus current

Battery temperature (°C) Internal battery temperature °C

Remain Time Min. Battery run time remaining

Battery boost charging Battery is boost charging

Battery float charging Battery is float charging

Battery disconnected Battery is not connected

Records (History Log) Displays all records in the history log

Language (choices for text displayed) User may select any of 12 languages for LCD text.

Display contrast Adjust the LCD contrast

Date format set Choose the format for date display: M/D/Y, D/M/Y, M/D/Y, Y/M/D

Date & time Set the date and time

Comm1 baud rate Communication baud rate setting for Liebert IntelliSlot 1

Comm2 baud rate Communication baud rate setting for Liebert IntelliSlot 2

Comm3 baud rate Communication baud rate setting for Liebert IntelliSlot 3

Communication address This setting is applicable to RS485 communication mode

Communication mode Communication Mode Setting

Callback times When Liebert IntelliSlot 1 Communication mode is Modem, this parameter sets the number of times a number is redialed to send an alarm notification.

Phone No.1 When Liebert IntelliSlot 1 Communication mode is Modem, this is the first phone number to be dialed (to send an alarm notification).

Phone No.2 When Liebert IntelliSlot 1 Communication mode is Modem, this is the second phone number to be dialed (to send an alarm notification).

Phone No.3 When Liebert IntelliSlot 1 Communication mode is Modem, this is the third phone number to be dialed (to send an alarm notification).

Command password User can modify the command password.

Show 6 more labels / short text on this page
Mains (input) · Output · Load · System · Battery · Settings
Page 72 of the Emerson 480V user manual — F2 F4 HELP F1 F3
Page 72 · click to enlarge
Page 72

Operator Control and Display Panel

Table 19 Descriptions of UPS menus and data window items (continued)

Menu Type Item Type Explanation

Battery maintenance test This test performs a partial discharge of the battery to obtain a rough estimate of the battery capacity. Load must be between 20% and 80%.

Battery capacity test This test performs a full discharge of the battery to obtain a precise measure of the battery capacity. Load must be between 20% and 80%.

System test This is a self-test of the UPS. When the user activates this function, a pop-up window appears about 5 seconds later to show the results.

Command (start/stop battery & system tests)

Stop testing Manually stops a battery maintenance test, battery capacity test or system test.

Freshening Charge Allows a temporary Equalize charge for the batteries. This charge is configurable for 1 to 36 hours.

Stop Freshening Charge Manually stops a Freshening Charge

Manually enable the modem’s auto-answer function.

UPS version Provides UPS firmware version numbers for the inverter, rectifier and software display board.

UPS model Provides UPS model information—for example, 480V-60Hz.

8.9 Language Selection

The LCD menus and data display are available in 12 languages (Chinese, Dutch, English, French, German, Italian, Japanese, Polish, Portuguese, Russian, Spanish and Swedish). To select a different language:

  • From the main menu, press the F1 (Shift) key to move the cursor to the menu at the top of the screen.
  • Press F2 and F3 (left and right arrows) as needed to select the Language menu.
  • Press F1 (shift) to move the cursor to the data and settings area of the LCD.
  • Use F2 and F3 (up and down) to select the required language.
  • Press the F4 (enter) key to accept the language selection.
  • Return to the main menu by repeatedly pressing F1 (ESC) as needed; all text on the LCD will now be displayed in the selected language.

Figure 46 Language selection

Liebert NX 2007-01-12 12:30:36 80KVA-3X3 Single Normal

POLSKI FRANCAIS

ITALIANO

ESPAÑOL

NEDERLANDS SVENSKA

Input disconnect closed 01-12 12:30 Output disconnect closed 01-12 12:30 Bypass disconnect open 01-12 12:30

?

F2 F4 HELP F1 F3

Show 5 more labels / short text on this page
Modem Auto-answer enable · Version · Language History Battery · English DEUTSCH · РУССКИЙ PORTUGUêS
Page 73 of the Emerson 480V user manual — F2 F4 HELP F1 F3
Page 73 · click to enlarge
Page 73

Operator Control and Display Panel

8.10 Current Date and Time

To change the system date and time:

  • From the main menu, press the F1 (shift) key to move the cursor to the menu at the top of the screen.
  • Press F2 and F3 (left and right arrows) as needed to select the Settings menu.
  • Press F1 (shift) to move the cursor to the data and settings area of the LCD.
  • Use F2 and F3 (up and down) to select the Date & Time option, then press F4 (enter).
  • Position the cursor on the row in which the date and time are displayed, then press F4 (enter).
  • Using the F2 and F3 (up and down) keys, enter the current time and date information.
  • Press F4 (enter) to save the settings, then press F1 (ESC) to return to the main menu.

Figure 47 Set date and time

Liebert NX 2007-01-12 12:30:36 80KVA-3X3 Single Normal

Y/M/D Y/M/D

M/D/Y D/M/Y

12:30:36

Input disconnect closed 01-12 12:30 Output disconnect closed 01-12 12:30 Bypass disconnect open 01-12 12:30

?

F2 F4 HELP F1 F3

Show 6 more labels / short text on this page
Language Setting · Command · LCD contrast · Date format · Date & Time · 2007-01-12
Page 74 of the Emerson 480V user manual — F2 F4 HELP F1 F3
Page 74 · click to enlarge
Page 74

Operator Control and Display Panel

8.11 UPS Status Messages

The Liebert NX displays status changes as they occur in the current status window of the LCD, then stores that data in the history log, as shown in Figure 48.

  • Current Status Window: The status messages are displayed chronologically and include the date and time of the events. Three status messages are visible in the window at a time. To see other messages, use the navigation keys to scroll up or down the list. A status message remains in the current status area of the LCD until the status changes, when it is moved to the history log.
  • History Log: When a record moves to the history log, the time the status changed is recorded. The history log can hold up to 512 records. History log records may be viewed by accessing the Records menu.

Figure 48 Current status and history log records

Liebert NX 2007-01-12 12:30:36 80KVA-3X3 Single Normal

2003-01-21 12 :21:12 2003-01-21 12 :21:12 UPS shutdown

2003-01-21 12 :21:12 2003-01-22 12 :30:16 Bypass abnormal

2003-01-21 12 :21:12 2003-01-21 12 :30:16

Input disconnect closed 01-12 12:30 Output disconnect closed 01-12 12:30 Bypass disconnect open 01-12 12:30

?

F2 F4 HELP F1 F3

See Appendix A for a complete list of status messages, along with a description and any recom- mended actions.

Show 7 more labels / short text on this page
Language Battery History · Inverter in setting · History Log · (records · menu) · Current · Status Messages
Page 75 of the Emerson 480V user manual — F2 F4 HELP F1 F3
Page 75 · click to enlarge
Page 75

Operator Control and Display Panel

8.12 Types of LCD Screens

This section provides a quick guide to the main types of LCD screens.

8.12.1 Opening Display

As the UPS begins powering up, the opening display appears, as shown in Figure 49.

Figure 49 Opening display

Emerson 480V — Figure 49 Opening display diagram (page 75)
Fig. 31 · Figure 49 Opening display

F2 F4 F1 F3

HELP

8.12.2 Default Screen

After the UPS has powered up and completed a self-test, the output screen appears, as shown in Figure 50. This window is the default screen.

Figure 50 Default screen

Liebert NX 2007-01-12 12:30:36 80KVA-3X3 Single Normal

L1-N/L2

L2-N/L3

L3-N/L1

70.8 59.9

71.3 59.9

59.9 480 0.99

480 0.99

480 0.99

Input disconnect closed 01-12 12:30 Output disconnect closed 01-12 12:30 Bypass disconnect open 01-12 12:30

?

F2 F4 HELP F1 F3

Show 4 more labels / short text on this page
Output Bypass Main · L-N current(A) · Frequency(HZ) L-L voltage(V) · PowerFactor
Page 76 of the Emerson 480V user manual — F2 F4 F5 F1 F3
Page 76 · click to enlarge
Page 76

Operator Control and Display Panel

8.12.3 UPS Help Screen

Press the HELP key below the LCD to display the Help window shown in Figure 51. (Press the HELP key again to exit the Help window.)

Figure 51 Help screen

Select the current record window

Select the previous menu item

Select the next menu item

Press ENTER key to view KVA history

Press ENTER key to view KVA history

Q3

Q2

Q1 Q5

Press help key back to main menu

Press help key back to main menu

?

F2 F4 HELP F1 F3

8.12.4 Screen Saver Window

If there has been no interaction with the Liebert NX’s LCD for 2 minutes, the screen saver window appears. It remains on the LCD for 2 minutes, then the screen will go dark. The LCD will become active again when any key is pressed.

Figure 52 Screen saver window

Liebert NX 2007-01-12 12:30:36 80KVA-3X3 Single Normal

Press any key back to main menu

F2 F4 F5 F1 F3

Help information

Page 77 of the Emerson 480V user manual — 8.13.6 Battery Refresh Charge Aborted, Condition Not Met
Page 77 · click to enlarge
Page 77

Operator Control and Display Panel

8.13 Pop-Up Windows

Pop-up prompt windows appear when the user must confirm a choice or perform an operation. This section describes the pop-up windows.

8.13.1 From Bypass to Inverter Mode With Power Interruption

If the bypass voltage or frequency exceeds the synchronized range and utility voltage or frequency is normal, the inverter cannot be in syn- chronization with the bypass, and the output can transfer to inverter only after an interruption of about 15ms when the user presses the INVERTER ON button. Before transferring, the system will let the user confirm whether the interruption can be accepted, as shown at right. If the bypass voltage returns to normal before the user makes confirmation, the UPS will transfer to inverter mode auto- matically. At the same time, the prompt window will close.

Transfer with Interrupt, please confirm or cancel

8.13.2 From Inverter to Bypass Mode With Interruption

If the bypass voltage or frequency exceeds the synchronized range and the UPS is in inverter mode, the user must confirm and accept the power interruption danger before pressing the INVERTER OFF but- ton to shut down the output of the inverter. The user can also cancel the shutdown operation, as shown at right. If the bypass voltage returns to normal before the user makes the confirmation, the UPS will transfer to bypass operation mode automatically, and at the same time the prompt window will close disappear soon.

This operation leads to

output shutdown, Confirm or cancel

8.13.3 System Self-Test

When a system self-test is completed, a pop-up window reports the results of the test, as shown at right.

  • Press the F4 (Enter) key and the pop-up window closes.

8.13.4 Battery Capacity Test Confirmation

When a battery capacity test is started from the Command menu, the battery will be discharged to low-battery warning level. The Liebert NX asks for confirmation before the test is started, as shown at right.

Battery will be depleted,

  • To confirm the choice and begin the battery capacity test, press the F4 (Enter) key and the pop-up window disappears.
  • To cancel the test, press the F1 (ESC) key. The pop-up window closes.

8.13.5 Battery Self-Test Aborted, Condition Not Met

When a battery capacity test is started from the Command menu and the battery self-test criteria are not met, the Liebert NX will not per- form a battery test. User should check whether the battery state is boost charging and whether the load level is greater than 20 percent.

  • Press the F4 (Enter) key and the pop-up window closes.

8.13.6 Battery Refresh Charge Aborted, Condition Not Met

When a battery refreshening charge is started from the Command menu and battery refreshening condition fails to meet requirements, the Liebert NX will not perform a battery refreshening charge. User should check if boost charging condition has not met the test criteria, such as (No battery, charger failed, etc.).

aborted, Conditions not met

  • Press the F4 (Enter) key and the pop-up window closes.
Show 6 more labels / short text on this page
System Self-Test finished, · Everything is OK · Confirm or cancel · Battery Self-Test aborted, · Conditions not met · Battery Refresh Charge
Page 78 of the Emerson 480V user manual — CB1:ON CB2:ON CB3:ON CB5:OFF
Page 78 · click to enlarge
Page 78

9.0 O PERATING I NSTRUCTIONS

9.1 Liebert NX Operating Modes

The Liebert NX can operate in any of four modes, as shown in Table 20. This section provides instructions on switching between modes, resetting the UPS, switching the inverter On and Off and performing other operations.

Table 20 UPS operating modes

Circuit Breaker State Description

CB1:ON CB2:ON CB3:OFF CB5:ON

The UPS is powering the load.

CB1:OFF CB2:OFF CB3:ON CB5:OFF

The UPS is shut down but the load is connected to utility power via the Maintenance Bypass Supply line. NOTE: The load is not protected against disturbances in AC input power in this mode.

CB1:ON CB2:ON CB3:ON CB5:OFF

No load power is supplied by the UPS. The load is connected to utility power via the Maintenance Bypass Supply line. NOTE: The load is not protected against disturbances in AC input power in this mode.

CB1:ON or OFF CB2:ON CB3:OFF CB5:ON

The load power is supplied through the static bypass line. This may be considered as a temporary mode during load transfers between inverter and maintenance bypass or supply under abnormal operating conditions.

Show 6 more labels / short text on this page
Operating Instructions · Operating Mode · Normal Operation · On Maintenance Bypass · On Test · On Static Bypass
Page 79 of the Emerson 480V user manual — Figure 53 Circuit breakers
Page 79 · click to enlarge
Page 79

9.1.1 Circuit Breakers

The UPS can be isolated by means of circuit breakers, mounted inside the cabinet and accessible after opening the front door.

The location of the UPS power switches is shown in Figure 53.

Figure 53 Circuit breakers

Emerson 480V — Figure 53 Circuit breakers diagram (page 79)
Fig. 32 · Figure 53 Circuit breakers

The UPS unit circuit breakers are CB1, CB2, CB3 and CB5.

  • CB1 —Main Input circuit breaker; connects the utility supply to the UPS main input.
  • CB2 —Bypass circuit breaker; connects the utility supply to the UPS bypass.
  • CB3 —Maintenance Bypass breaker; connects the utility supply to the UPS maintenance bypass.
  • CB5 —Output breaker; connects inverter or bypass to the external output transformer or power distribution panel.

Operating Instructions

Page 80 of the Emerson 480V user manual — F2 F4 F1 F3
Page 80 · click to enlarge
Page 80

9.2 UPS Startup

The Liebert NX must be fully installed and commissioned before startup, and external power isolators must be closed. Once those general conditions are met, the UPS may be started.

9.2.1 Startup Procedure

To start the UPS from a fully powered-down condition:

1. Open the UPS door to gain access to the main input circuit breakers.

! WARNING During this procedure the output terminals will become live.

If any load equipment is connected to the UPS output terminals, please check with the load user and ascertain whether it is safe to apply power to the load. If the load is not ready to receive power, then ensure that it is safely isolated from the UPS output terminals.

2. Close CB1, CB2 and CB3 (CB5 is open). The main input contactor closes automatically and the LCD begins to show start-up screens. The Rectifier indicator flashes green while the rectifier is starting up. It stops flashing and becomes solid green about 30 seconds after the rectifier enters the normal operation state. After initialization, the bypass SCR closes. Because the output circuit breaker is still open, the UPS channels power through the Maintenance Bypass Supply line (CB3). The bypass indicator extinguishes, provided that the bypass is normal. The opening display is shown in the figure at right. The UPS Mimic display indicators will be:

F2 F4 F1 F3

HELP

3. Close CB5 (CB1, CB2, CB3 and CB5 are closed). The Maintenance Bypass supply is now in parallel with the UPS Static Switch supply. 4. Verify that the Bypass indicator is Green, then open CB3. The UPS powers from static bypass instead of from maintenance bypass. The bypass and load indicators turn on. The design of the hardware and software ensures uninterrupted output. 5. Close external battery circuit breaker. After the UPS detects that the battery is connected, the red battery indicator extinguishes moments after the battery charger starts operation. The UPS Mimic display indicators will be

Show 15 more labels / short text on this page
Operating Instructions · Indicator State · Rectifier indicator Green · Battery indicator Red · Bypass indicator Off · Inverter indicator Off · Output indicator Off · Status indicator Off · Indicator State · Rectifier indicator Green · Battery indicator Off · Bypass indicator Green · Inverter indicator Off · Output indicator Green · Status indicator Amber
Page 81 of the Emerson 480V user manual — Switch from Bypass Mode to Normal Mode
Page 81 · click to enlarge
Page 81
6. Press the INVERTER ON control button for 2 seconds. The inverter will start and the inverter indicator will flash green. After the inverter is ready, the UPS will transfer from bypass to inverter, the bypass indicator will turn off and the inverter and load indicators will turn on. The UPS is operating normally. The UPS Mimic display indicators will:

9.2.2 Verify Switching Between Operation Modes

Switch from Normal Mode to Battery Mode

  • Open CB1 to enter battery mode. This breaks the utility connection to the Liebert NX. To return to normal mode, close CB1 after a few seconds. The rectifier will restart automatically after 10 seconds and resume feeding power to the inverter.

Switch from Normal Mode to Bypass Mode

  • Press the INVERTER OFF button to switch to bypass mode.

Switch from Bypass Mode to Normal Mode

  • In bypass mode, press the INVERTER ON button. When the inverter is ready, the UPS will switch to normal mode.
Show 8 more labels / short text on this page
Operating Instructions · Indicator State · Rectifier indicator Green · Battery indicator Off · Bypass indicator Off · Inverter indicator Green · Output indicator Green · Status indicator Green
Page 82 of the Emerson 480V user manual — 9.3 Maintenance Bypass Procedure and Powering Down the UPS
Page 82 · click to enlarge
Page 82

9.3 Maintenance Bypass Procedure and Powering Down the UPS

Follow the procedure below to transfer the load from the inverter output to the Maintenance Bypass line of the UPS.

! CAUTION Before performing this operation, read the messages on the LCD to be sure that bypass supply is regular and the inverter is synchronous with it. If those conditions are not present, there is a risk of a short interruption in powering the load.

This procedure assumes that the UPS is operating normally.

1. Press the INVERTER OFF button on the operator control panel for longer than 2 seconds. The Inverter indicator will turn off and the status indicator will turn amber and an audible alarm will sound. The load will transfer to static bypass and the inverter will shut off.

2. Close maintenance breaker CB3. The Maintenance Bypass supply is now in parallel with the UPS Static Switch supply. 3. Open output breaker CB5. This ends the bypass procedure. The load is now powered directly from the Maintenance Bypass supply. 4. Press the EPO (Emergency Power Off) button at the UPS front panel of this UPS module only. This will disable further Rectifier, Inverter, Static Switch and Battery operation. This will not affect the manual maintenance bypass power switch. If a Liebert NX battery cabinet is connected, the battery circuit breaker will shunt trip open. 5. Open the rectifier switch CB1 and bypass breaker CB2. All operator indicators and messages will turn off as the utility-driven internal power supplies decay. The unit will power down, but the load will continue to be supplied by the manual Mainte- nance bypass.

! WARNING Wait 5 minutes for the internal DC busbar capacitors to discharge before attempting to remove the internal protective barriers.

! WARNING Even with the UPS in maintenance bypass and “Off,” portions of the unit are still energized. Service is to be performed by qualified personnel only.

! CAUTION The load equipment is not protected from normal supply aberrations when operating in maintenance bypass mode.

6. To return unit to normal operation, follow the steps in 9.2.1 - Startup Procedure .

Operating Instructions

Page 83 of the Emerson 480V user manual — 9.6 Reset After Shutdown for Emergency Stop (EPO Action) or Other Conditions
Page 83 · click to enlarge
Page 83

9.4 Auto Restart

When the main and bypass sources fail, the UPS draws power from the battery system to supply the load until the batteries are depleted. When the UPS reaches its end of discharge (EOD) threshold, it will shut down.

The UPS will automatically restart and enable output power:

  • after utility power is restored
  • if “Auto Recovery after EOD Enabling” is enabled
  • after the “Auto Recovery after EOD Delay Time” expires (the default delay is 10 minutes) During the auto recovery delay, the Liebert NX will be charging its batteries to provide a safety margin for equipment shutdown if input power fails again.

If the “Auto Recovery after EOD Enabling” feature is disabled, the user must restart the system man- ually.

9.5 Emergency Shutdown With EPO

This circuit has been designed to switch off the UPS in emergency conditions (i.e., fire, flood, etc.). The system will turn off the rectifier and inverter and will stop powering the load immediately (including the inverter and bypass), and the battery stops charging or discharging. If a Liebert NX battery cabi- net is connected, the circuit breaker in the battery cabinet will shunt trip open.

If input utility power is present, the UPS’s controls will remain active; however, the output will be turned off. To remove all power from the UPS, open the external feeder breaker.

9.6 Reset After Shutdown for Emergency Stop (EPO Action) or Other Conditions

Once all appropriate measures have been taken to correct the problem indicated by the alarm mes- sage appearing on the operator control panel display, carry out this procedure to restore the UPS to regular operation following an EPO action or for the following reasons: Inverter Overtemperature, Cut-off Overload, Battery Overvoltage, excessive switching (BYP: XFER COUNT BLOCK), etc.

When the user confirms that the fault is cleared:

1. Press the FAULT CLEAR button to let the system exit the emergency-off state.
2. Press the INVERTER ON button on the right side of the operator control panel for longer than 2 seconds.

After the EPO button is pressed, if the input utility is removed, the UPS will shut down completely. When input utility is returned, if the Bypass input circuit breaker (CB2) and UPS output circuit breaker (CB5) are closed, the UPS will start up on Bypass. There will be power at the output termi- nals of the UPS.

! WARNING If the internal maintenance bypass circuit breaker (CB3) is closed and input utility is present, there will be power at the output terminals of the UPS.

Operating Instructions

Page 84 of the Emerson 480V user manual — 9.8 Multi-Module System Procedures
Page 84 · click to enlarge
Page 84

9.7 Battery Protection

9.7.1 Battery Undervoltage Pre-Warning

Before the end of discharge, the Liebert NX displays a Low Battery pre-warning. After this pre-warn- ing, the battery has the capacity for 5 minutes discharging with full load (default time). The Liebert NX can be user-configured to display this warning from 3 to 60 minutes before end-of-discharge.

9.7.2 Battery End-of-Discharge (EOD) Protection

If the battery voltage is lower than the end-of-discharge voltage, the battery converter will be shut down.

9.8 Multi-Module System Procedures

9.8.1 Isolating One Module in a Multi-Module System 1. Turn Off the inverter 2. Open External Output CB4 in Parallel Cabinet (see Figure 54). The UPS enters Isolation Status automatically, parallel signaling and communication become masked and output becomes inhibited. 3. Power Off the unit for maintenance. 4. Power On the unit. 5. Unit enters Test Mode by configuration software setting. 6. Diagnosis or testing. 7. The UPS exits Test Mode by configuration software setting. Output becomes inhibited because of Isolation Status. 8. Return all switches to the Normal position. 9. Close External Output CB4 in Parallel Cabinet (see Figure 54). The UPS exits Isolation Status automatically, parallel signaling and communication recovers, output becomes enabled but interlocking works now. 10. Turn On inverter and join the parallel system.

Operating Instructions

Page 85 of the Emerson 480V user manual — optional output / bypass distribution panel
Page 85 · click to enlarge
Page 85

Figure 54 Typical parallel system block diagram with common input supply, with separate batteries and

optional output / bypass distribution panel

480V 3W+G

480V 3W+G

CB 3

CB 3A

CB 1 CB 4

FPC

SBS

AC

AC

UPS

Show 8 more labels / short text on this page
Operating Instructions · Tie breaker · Output Input · Optional additional · Optional additional · systems · systems · I Line
Page 86 of the Emerson 480V user manual — ! WARNING
Page 86 · click to enlarge
Page 86

9.8.2 Inserting One Module into a Multi-Module System

This procedure outlines how to integrate a UPS module that has been previously isolated from other modules of a group of paralleled UPS modules. It is assumed that the installation is complete, the sys- tem has been commissioned by authorized personnel and the external power isolators are closed.

! WARNING

Mains voltage will be applied to UPS output terminals.

No operator serviceable parts are located behind covers that require a tool for their removal.

Only qualified service personnel are authorized to remove such covers.

1. Open the UPS door to gain access to the main circuit breakers. 2. Open (or confirm disabled) maintenance bypass circuit breaker CB3. 3. Close Input breaker CB1. The Rectifier indicator flashes on the UPS mimic panel during the startup of the rectifier and becomes steady green once the rectifier reaches normal operation state after about 30 seconds. 4. Close external battery circuit breaker. This breaker is inside the battery cabinet or is otherwise adjacent to the battery racks. 5. After the UPS detects the batteries, the red battery indicator extinguishes when the battery charger starts operation. 6. Close bypass circuit breaker CB2. 7. Press the INVERTER ON control button for 2 seconds. The inverter will start up and the inverter indicator flashes while it synchronizes to the load volt- age and frequency. After the inverter is ready, the UPS connects to the load, the inverter indicator becomes steady green and the output indicator turns green. 8. Check that no “Warning” message is displayed in the top right corner of the LCD and that the indicators have the status shown below.

# LED LED Function Status

1 Rectifier indicator Green

2 Battery indicator Off

3 Bypass indicator Off

4 Inverter indicator Green

5 Output indicator Green

6 Alarm indicator Off

The UPS is now operating in NORMAL mode.

Operating Instructions

Page 87 of the Emerson 480V user manual — 9.9 Commissioning a Parallel System
Page 87 · click to enlarge
Page 87

9.8.3 Shutdown Procedure—Complete UPS and Load Shutdown

This procedure must be followed to completely power down the UPS and the load. All power switches, isolators and circuit breakers will be opened and power will be removed from the load.

In multi-module systems, perform each step of the procedure in every UPS module before proceeding to the next step.

! CAUTION This procedure will shut off power to the load.

1. Press the EPO (Emergency Power Off) button at the UPS front panel only. This will disable Rectifier, Inverter, Static Switch and Battery operation. The load will be de-energized.

! CAUTION Except in an emergency situation, do not press any remote EPO button

2. Open the UPS door to gain access to the main circuit breakers. 3. Open the Rectifier input circuit breaker CB1. 4. Open external battery circuit breaker. This breaker is inside the battery cabinet or is otherwise adjacent to the battery racks. 5. Open Output circuit breaker CB5. 6. Open bypass input circuit breaker CB2. 7. Ensure maintenance bypass circuit breaker CB3 is open. 8. All mimic panel LED indications and messages will extinguish as the mains-driven, internal power supplies decay. 9. To completely isolate the UPS from the AC supplies, the main external power input isolator (both isolators, where dual supplies are provided for rectifier and bypass) and external output isolator must be opened and tagged with warning labels accordingly.

9.9 Commissioning a Parallel System

! CAUTION The operations described in this section must be performed by authorized electricians or qualified technical personnel. If you have any difficulty, call 1-800-LIEBERT for assistance.

Check the input and output wiring of each UPS module. Ensure that the phase rotation sequence of the main inputs and the bypass inputs and outputs of each UPS module are the same. Ensure that the parallel cables are connected firmly.

It is assumed that the installation is complete, the system has been commissioned by authorized per- sonnel and the external power isolators are closed. Disconnect the load before startup.

Operating Instructions

Page 88 of the Emerson 480V user manual — 9.10 Parallel System Start Up
Page 88 · click to enlarge
Page 88

9.10 Parallel System Start Up 1. Start each UPS normally as described in 9.2 - UPS Startup 2. Turn on the inverter of each UPS module one at a time. 3. Apply the load after the last UPS module transfers to inverter. The total load can be determined through the LCD of either UPS. 4. Verify the load rate of each UPS module. If the load rates are roughly the same, then the parallel system may be assumed to be operating normally.

NOTE If one module cannot transfer to inverter mode long after its inverter is on, its output connection may not be good or its output phase rotation may not be coincident with other modules. At this time, the LCD for the UPS module will display “inverter asynchronous” and the inverter indicator will flash continuously. If either UPS module makes abnormal noise after it transfers to inverter, its parallel cables may be incorrectly connected.

Operating Instructions

Page 89 of the Emerson 480V user manual — 10.1.3 Liebert IntelliSlot Communication
Page 89 · click to enlarge
Page 89

10.0 O PTIONS

Several items of optional equipment are available for connection to the Liebert NX UPS.

10.1 Communication and Other User Terminals

The UPS can be integrated into advanced networking environments via UPS monitoring software such as Windows-based UPS Monitor, MultiLink™, Nform™, SiteNet, Modbus / Jbus, SiteScan, SiteScan 2, SNMP, etc. They allow UPS status monitoring and automatic and safe shutdown of the server and PCs.

Figure 55 Monitoring board (U2) auxiliary terminal block detail

J8

J3 J1

J22

LCD

J23

J12

J9

J2

PWR MODEM SNMP CARD

J15

J16

J17

J13 J21 J25 J28 J4 J26 J30 J10

J24

BFP INV ACF EPO Dry in MBC BCB

X1 X2 X3

10.1.1 Analog Input Interface

At the X6 slot, there are two analog signal channels. Input range is from 0 to +5V, and the precision is 2 percent. “ENV-T” is used for environment temperature detecting.

  • X6 pin 1: Not used
  • X6 pin 2: +12V
  • X6 pin 3: ENV-T – environment temperature detection
  • X6 pin 4: GND

10.1.2 Power Output

The X5 slot can provide power for a modem or an external SNMP card. Available voltage is from 9V to 12V. The maximum current is 500mA.

10.1.3 Liebert IntelliSlot Communication

The Liebert NX has three Liebert IntelliSlot ports to allow field-installation of optional communica- tion cards. Liebert IntelliSlot cards communicate via Liebert’s proprietary ESP2 protocol to cards that translate the information into such protocols as SNMP, IGMnet, Modbus or Jbus. Other cards provide dry contact signals for external signaling of operating status.

The Liebert IntelliSlot communication ports may be installed or removed while the Liebert NX is operating.

Show 4 more labels / short text on this page
Options · Liebert IntelliSlot 2 · Liebert IntelliSlot 1 · Liebert IntelliSlot 3
Page 90 of the Emerson 480V user manual — 10.1.4 Communication and Monitoring
Page 90 · click to enlarge
Page 90

10.1.4 Communication and Monitoring

Liebert IntelliSlot Web Card - SNMP/HTTP Network Interface Card

This network interface card provides all real-time data and status information as SNMPv1 traps for connection to a 10/100-baseT Ethernet connection. The same card also will transmit the same status information and all measured parameters for display through a Web browser. Table 21 Liebert NX communication options

On the UPS LCD screen, under Settings,

controlled by:

Intellislot 2 (On Monitor

Liebert IntelliSlot WEB-LB 2400

Not simultaneous with Multilink in RS232-1; See 10.1.5 - Configuring Baud Rates

Modbus/Jbus 2400 See 10.1.5 - Configuring Baud Rates

Intellislot 1 (On Monitor

Liebert IntelliSlot WEB-LB 2400

See 10.1.5 - Configuring Baud Rates Not simultaneous with Multilink in RS232-2

Modbus/Jbus 2400 See 10.1.5 - Configuring Baud Rates

Intellislot 3 (On Monitor

Liebert IntelliSlot WEB-LB 2400 See 10.1.5 - Configuring Baud Rates

Modbus/Jbus 2400 See 10.1.5 - Configuring Baud Rates

Top DB9 port RS232-1 Comm 1

9600 Not simultaneous with Web card in top Liebert IntelliSlot.

Service Software (Reserved) 9600 Not simultaneous with Web card in middle Liebert IntelliSlot.

Bottom DB9 port RS232-2 Comm 2

Show 26 more labels / short text on this page
Options · Physical description · Labeled ID Name · Monitoring · Devices supported · Baud · of port · of Port · rate Comments · Multiport 4 any · Relaycard-int any · Top Liebert IntelliSlot · Comm 1 · Board) · Multiport 4 any · Relaycard-int any · Middle Liebert IntelliSlot · Comm 2 · Board) · Multiport 4 any · Relaycard-int any · Bottom · Liebert IntelliSlot · Comm 3 · Board) · MultiLink Serial
Page 91 of the Emerson 480V user manual — 10.1.5 Configuring Baud Rates
Page 91 · click to enlarge
Page 91

10.1.5 Configuring Baud Rates

The default baud rate for Liebert IntelliSlots is 9600. To communicate with the OCWEB-LB, Modbus/ Jbus, or the MultiLink cards, the baud rate must be set to 2400.

To change the baud rate (refer to Table 21):

1. Use the Navigation keys directly below the LCD to highlight the Settings Screen. 2. Press F1 to move the highlight into the Data & Settings area of the LCD. 3. Use the Navigation keys to scroll down to highlight the current baud rate across from the appropriate Comm Channel.
4. Press the Enter (F4) key to select the Comm Channel to change. 5. Navigate to underline the desired baud rate (2400). 6. Press the Enter (F4) key to lock in the new baud rate.

Options

Page 92 of the Emerson 480V user manual — Figure 56 Liebert IntelliSlot Web card display
Page 92 · click to enlarge
Page 92

Figure 56 Liebert IntelliSlot Web card display

Emerson 480V — Figure 56 Liebert IntelliSlot Web card display diagram (page 92)
Fig. 33 · Figure 56 Liebert IntelliSlot Web card display
Emerson 480V — Figure 56 Liebert IntelliSlot Web card display diagram (page 92)
Fig. 34 · Figure 56 Liebert IntelliSlot Web card display

Options

Page 93 of the Emerson 480V user manual — Table 23 Relay card jumper configuration
Page 93 · click to enlarge
Page 93

Relay Card

The relay card provides voltage-free contact closures for remote monitoring of alarm conditions.

Delivering On Battery, On Bypass, Low Battery, Summary Alarm, UPS Fault and On UPS sig- nals, the easy-to-install card integrates with AS/400 computers (additional cable required) and other relay contact monitoring systems.

The relay card is rated for 24 VAC/DC at 1A and supported in any of the three Liebert IntelliSlot bays on the Liebert NX.

Table 22 Relay Card pin configuration

1 UPS Fault Closed if no UPS failure

4 UPS Fault Closed if UPS fails

5 Summary Alarm** Closed if SUMMARY ALARM** occurs

6 Summary Alarm** Closed if no alarm conditions are present

7 Any Mode Shutdown return Not supported – use External EPO terminal

9 Common - Low Battery

10 Low Battery Closed if battery is OK

11 Low Battery Closed if LOW BATTERY point occurs

14 UPS Any Mode Shutdown Not supported – use External EPO terminal

15 On UPS Closed if ON UPS (inverter) power

16 On Battery Closed if ON BATTERY power (Utility failure)

17 Common - UPS Fault, Summary Alarm, On UPS, On Battery, On Bypass

18 On Battery Closed if not ON Battery power (Utility OK)

24 On Bypass Closed if ON BYPASS

**A Summary Alarm occurs when any of the following conditions exist: 1. Utility power is out of the acceptable range (voltage and/or frequency). 2. UPS is in BYPASS MODE (load not on Inverter power). 3. UPS Battery is LOW. 4. UPS fault has occurred.

Table 23 Relay card jumper configuration

JP01 Pin 9 to Pin 17 Allows all relay COMMONS to be tied together.

ANY JP02 Pin 7 to Pin 17 REMOVE - (Interconnects all relay COMMONS and the (not supported) MODE SHUTDOWN Return

Show 8 more labels / short text on this page
Options · Pin Function Operation · 2-3 Not Used · 8 Not Used · 12-13 Not Used · 19-23 Not Used · 25 Not Used · Number Connection Description
Page 94 of the Emerson 480V user manual — Figure 57 MultiPort 4 card pin assignment
Page 94 · click to enlarge
Page 94

MultiPort 4 Card

The MultiPort 4 card provides four sets of voltage-free contact closures for remote monitoring of alarm conditions UPS operation On Battery and Low Battery condition. A typical application is to allow a maximum of four computer systems to simultaneously monitor the status (e.g., utility power failure-low battery) of a single UPS.

This card is supported in any of the three Liebert IntelliSlot bays on the Liebert NX.

Figure 57 MultiPort 4 card pin assignment

Emerson 480V — Figure 57 MultiPort 4 card pin assignment diagram (page 94)
Fig. 35 · Figure 57 MultiPort 4 card pin assignment
Emerson 480V — Figure 57 MultiPort 4 card pin assignment diagram (page 94)
Fig. 36 · Figure 57 MultiPort 4 card pin assignment

Options

Page 95 of the Emerson 480V user manual — Figure 58 Dust filter replacement
Page 95 · click to enlarge
Page 95

10.2 LBS Mode—Load Bus Synchronization

The function of LBS is to keep the output of two independent UPS systems (single unit or multiple unit) in synchronization even when the two systems are operating in different modes (bypass/ inverter) or on batteries. It is usually used with a Static Transfer Switch connected to the critical load to achieve dual bus configuration.

10.2.1 Remote Alarm Monitor

Status and alarm conditions are available on an optional remote alarm monitor (RAM) panel, which is driven by volt-free alarm status contacts (from an optional relay alarm board).

10.3 Replacing Dust Filters 1. Open the UPS door. 2. The dust filters are behind the door. For each filter, there is a bracket on either side holding the dust filter in place, as shown in Figure 58. 3. Remove one bracket and loosen the other. The second bracket need not be removed. 4. Remove the old filter and replace with the new filter 5. Reinstall the bracket that was removed and tighten the other bracket.

Figure 58 Dust filter replacement

Emerson 480V — Figure 58 Dust filter replacement diagram (page 95)
Fig. 37 · Figure 58 Dust filter replacement

Options · Bracket · Bracket Sems screw

Page 96 of the Emerson 480V user manual — Table 25 Battery torque rating
Page 96 · click to enlarge
Page 96

Specifications and Technical Data

11.0 S PECIFICATIONS AND T ECHNICAL D ATA

11.1 Lug Size and Torque Requirements

Use commercially available solderless lugs for the wire size required for your application. Refer to Table 24. Connect wire to the lug using tools and procedures specified by the lug manufacturer.

Table 24 Torque specifications

Nut and Bolt CombinationS

Electrical Connections with Belleville Washers

Lb-in N-m Lb-in N-m

1/4 53 6.0 46 5.2 5/16 107 12 60 6.8 3/8 192 22 95 11 1/2 428 22 256 29

Circuit Breakers With Compression Lugs (For Power Wiring)

Wire Size or Range Lb-in N-m

#6 - #4 100 11 #3 - #1 125 14 1/0 - 2/0 150 17 3/0 - 200 MCM 200 23 250 - 400 MCM 250 28 500 - 700 MCM 300 34

Circuit Breakers With Compression Lugs (For Power Wiring)

Current Rating Lb-in N-m

400. 1200 Amps 300.00 34.00

Terminal Block Compression Lugs (For Control Wiring)

AWG Wire Size or Range Lb-in N-m

#22 -#14 3.5 to 5.3 0.4 to 0.6

Table 25 Battery torque rating

UPS12-100MR 40 (4.5)

UPS12-150MR 25 (2.8)

UPS12-210MR 25 (2.8)

UPS12-300MR 110 (12.4)

UPS12-350MR 110 (12.4)

UPS12-400MR 110 (12.4)

11.2 Cable Lengths: Floor to Connection Point Inside UPS

To help calculate the total cable length required, refer to Table 26 for the distance from the floor to selected connection points inside the Liebert NX. Determine the cable length required to reach the

Show 5 more labels / short text on this page
Grade 2 Standard · Bolt Shaft Size · Initial Torque · Battery · in-lb (N-m)
Page 97 of the Emerson 480V user manual — (VAC)
Page 97 · click to enlarge
Page 97

Specifications and Technical Data

Liebert NX, then add the appropriate length from the table and adequate slack for repair and mainte- nance.

Table 26 Distance to connection points on the Liebert NX UPS

From Top of Unit

Connection Point on UPS

in. (mm)

in. (mm)

Bypass AC input supply 13 (330) 66 (1676)

UPS output AC 13 (330) 66 (1676)

Battery power 13 (330) 66 (1676)

Auxiliary cablesMonitor board (U2) 67 (1702) 11 (279)

Liebert IntelliSlot Communications 60 (1524) 19 (483)

Ground 13 (330) 66 (1676)

Parallel Board 70 (1780) 11 (279)

Table 27 Parallel system current table

Output OCPCB Size (A)

System Max Input Current

(VAC)

(VAC)

80 480V 202.5 300 480V 144.3 200

E

120 480V 135.0 200 480V 96.2 125

80 480V 202.5 300 480V 144.3 200

E1

120 480V 135.0 200 480V 96.2 125

80 N/A N/A N/A 480V 144.3 200

E2

120 N/A N/A N/A 480V 96.2 125

80 480V 405.0 600 480V 288.7 400

E

120 480V 270.0 350 480V 192.5 250

80 480V 405.0 600 480V 288.7 400

E1

120 480V 270.0 350 480V 192.5 250

80 N/A N/A N/A 480V 288.7 400

E2

120 N/A N/A N/A 480V 192.5 250

80 480V 607.5 800 480V 433.0 600

E

120 480V 405.0 600 480V 288.7 400

80 480V 607.5 800 480V 433.0 600

E1

120 480V 405.0 600 480V 288.7 400

80 N/A N/A N/A 480V 433.0 600

E2

120 N/A N/A N/A 480V 288.7 400

Use wiring rated at 75°C or greater.

Show 14 more labels / short text on this page
Distance · From Floor · System I/P · System Input OCPCB · Nominal O/PCurrent · System · Voltage · O/P Voltage · Size Type kVA · Size (A) · Rating (A) · 1+1 · 2+1 · 3+1
Page 98 of the Emerson 480V user manual — Table 31 Cable size tightening torque at Liebert NX 60kVA UPS terminals
Page 98 · click to enlarge
Page 98

Specifications and Technical Data

Table 28 External cabinet dimensions, including side panels

Type E1 Parallel Cabinet

Unit Width Depth Height mm (inch) 1240 (48.8) 965 (38) 2000 (78.7)

Type E Parallel Cabinet

Unit Width Depth Height mm (inch) 845 (33.2) 965 (38) 1956 (77)

Unit Width Depth Height mm (inch) 845 (33.2) 965 (38) 1956 (77)

Table 29 Lead/Lag ratings

-0.5 100% 50%

-0.6 100% 60%

-0.7 100% 70%

-0.8 100% 80%

-0.9 100% 90%

Unity 1 90% 90%

-0.9 80% 72%

-0.8 77% 61%

-0.7 75% 52%

-0.6 74% 44%

-0.5 73% 36%

11.3 Cable size and tightening torques

Table 30 Cable size tightening torque at Liebert NX 40kVA UPS terminals

Cable Size (Copper Wire Only)

Torque to Tighten Terminal Bus & Lug Body

Main Input (Single Input) 4 10 N*m

Main Input (Dual Input) 4 10 N*m

Bypass Input (Dual Input) 4 10 N*m

Output 3 10 N*m

Table 31 Cable size tightening torque at Liebert NX 60kVA UPS terminals

Cable Size (Copper Wire Only)

Torque to Tighten Terminal Bus & Lug Body

Main Input (Single Input) 1 10N*m

Main Input (Dual Input) 1 10N*m

Bypass Input (Dual Input) 2 10N*m

Show 10 more labels / short text on this page
Matching Battery Cabinet · Load Power · kVA Rating · kW Rating · Factor · Lagging · Leading · Bus Type · Bus Type · Output 2 10N*m
Page 99 of the Emerson 480V user manual — Table 34 Cable size tightening torque at Liebert NX 120kVA UPS terminals
Page 99 · click to enlarge
Page 99

Specifications and Technical Data

Table 32 Cable size tightening torque at Liebert NX 80kVA UPS terminals

Cable Size (Copper Wire Only)

Torque to Tighten Terminal Bus & Lug Body

Main Input (Single Input) 2/0 10 N*m

Main Input (Dual Input) 2/0 10 N*m

Bypass Input (Dual Input) 1/0 10 N*m

Output 1/0 10 N*m

Table 33 Cable size tightening torque at Liebert NX 100kVA UPS terminals

Cable Size (Copper Wire Only)

Torque to Tighten Terminal Bus & Lug Body

Main Input (Single Input) 4/0 10 N*m

Main Input (Dual Input) 4/0 10 N*m

Bypass Input (Dual Input) 2/0 10 N*m

Output 2/0 10 N*m

Table 34 Cable size tightening torque at Liebert NX 120kVA UPS terminals

Cable Size (Copper Wire Only)

Torque to Tighten Terminal Bus & Lug Body

Main Input (Single Input) 250 10 N*m

Main Input (Dual Input) 250 10 N*m

Bypass Input (Dual Input) 4/0 10 N*m

Output 4/0 10 N*m

Bus Type · Bus Type · Bus Type

Page 100 of the Emerson 480V user manual — UPS12-100MR 5 18 32 47
Page 100 · click to enlarge
Page 100

Specifications and Technical Data

11.4 Battery Run Times

Table 35 Estimated battery run time, minutes

1 2 3 4

UPS12-100MR 5 18 32 47

UPS12-150MR 13 33 53 75

UPS12-210MR 21 51 81 123

UPS12-100MR - 9 18 27

UPS12-150MR 7 19 33 47

UPS12-210MR 11 31 51 73

UPS12-100MR - 5 11 18

UPS12-150MR - 13 22 33

UPS12-210MR 6 21 36 51

UPS12-100MR - - 8 12

UPS12-150MR - 9 17 25

UPS12-210MR - 15 27 38

UPS12-100MR - - 5 9

UPS12-150MR - 7 13 19

UPS12-210MR - 11 21 31

Show 7 more labels / short text on this page
Number of Cabinets · UPS Rating/Model · 40kVA UPS · 60kVA UPS · 80kVA UPS · 100kVA UPS · 120kVA UPS
Page 101 of the Emerson 480V user manual — Table 36 UPS status messages
Page 101 · click to enlarge
Page 101

A PPENDIX A - UPS S TATUS M ESSAGES

Table 36 shows all event messages as they appear in the current status area of the LCD and in the history log, along with a description and recommended actions, if any. For further information on the current status area and the history log, see 2.11 UPS Status Messages.

Table 36 UPS status messages

Event Message Description / Suggested Action (if any)

Inverter Comm. Fail The RS-485 communication between internal monitor and inverter has failed. Contact Liebert Global Services at 800-543-2378 for assistance.

Rectifier Comm. Fail The RS-485 communication between internal monitor and rectifier fails. Contact Liebert Global Services at 800-543-2378 for assistance.

The CAN communication between different UPS units within a parallel system has failed. Check if there are some UPS units not powered on in the parallel system. If so, power on these UPS units and check if the alarm disappears. Press Fault Clear push button. If alarm does not clear, contact Liebert Global Services at 800-543-2378

Parallel Comm. Fail

Battery Overtemp. The battery temperature is over limit. Check the battery temperature and ventilation

Ambient Overtemp. The ambient temperature is over limit. Check the ventilation of UPS room.

Replace Battery Battery should be replaced. Contact Liebert Global Services at 800-543-2378 for assistance.

Before the end of discharging, battery under-voltage pre-warning should occur. After this pre- warning, battery should have the capacity for 3 minutes discharging with full load. The time is user configured from 3 to 60 minutes. Shut down the load in time to prevent damage to equipment and data.

Battery End of Discharge Inverter turned off due to low battery voltage. Check the utility failure and try to recover it.

Mains Volt. Abnormal Mains voltage exceeds the upper or lower limit and results in rectifier shutdown. Check the input line-to-line voltage amplitude of rectifier.

Mains Undervoltage Mains voltage is undervoltage 288V~384V line to line voltage with derated load. Check the input line-to-line voltage amplitude of rectifier.

Mains Freq. Abnormal Mains frequency is out of limit range and results in rectifier shutdown. Check the rectifier’s input voltage frequency

Rectifier Fault Contact Liebert Global Services at 800-543-2378 for assistance.

The temperature of rectifier inductor of rectifier common mode inductor is too high to keep the rectifier running. Check the ambient temperature and ventilation; contact Liebert Global Services at 800-543-2378 for assistance.

Input Inductor Overtemp.

Rectifier Overtemp. The temperature of the heat sink is too high to keep the rectifier running. The UPS can recover automatically. Check the environment and ventilation.

Charger Fault The charger has a fault. Contact Liebert Global Services at 800-543-2378 for assistance.

Control Power 1 Fail Control Power 1 has failed or has been lost. Contact Liebert Global Services at 800-543-2378 for assistance.

Mains Phase Reversed Input phase sequence is inverse. Contact Liebert Global Services at 800-543-2378 for assistance.

Rectifier Overcurrent The current of rectifier is over limit. Contact Liebert Global Services at 800-543-2378 for assistance.

Soft Start Fail Rectifier could not start due to low DC bus voltage. Contact Liebert Global Services at 800-543-2378 for assistance.

UPS Status Messages · Battery Low Pre-warning

Page 102 of the Emerson 480V user manual — Table 36 UPS status messages
Page 102 · click to enlarge
Page 102

Table 36 UPS status messages

Event Message Description / Suggested Action (if any)

This alarm is triggered by an inverter software routine when the amplitude or frequency of bypass voltage is beyond the normal range. The amplitude threshold is fixed for positive and negative 10% rating. This alarm automatically resets once the bypass voltage goes normal. First verify that the bypass voltage and frequency displayed on the panel is within the selected range. Note here the rated voltage and frequency are specified by “Output voltage level” and “Output frequency level” respectively. If the displayed voltage is believed to be abnormal, then verify the bypass voltage and frequency presented to the UPS. Check the external supply if it is found to be faulty. Contact Liebert Global Services at 800-543-2378 for assistance.

Bypass Unable to Trace

This alarm is triggered by an inverter software routine when the amplitude or frequency of bypass voltage exceeds the limit. This alarm automatically resets once the bypass voltage goes normal. First check whether there are relevant alarms such as “Bypass disconnect open,” “Bypass phase reverse” and “Mains neutral lost.” If they appear, solve them first. Then verify that the bypass voltage and frequency displayed on the panel is within the bypass limit. Note here the rated voltage and frequency are specified by “Output voltage level” and “Output frequency level” respectively. If the displayed voltage is believed to be abnormal, then verify the bypass voltage and frequency presented to the UPS. Check the external bypass supply if it is found to be faulty. If the utility is likely to trigger this alarm frequently, the bypass limit can be increased through the configuration software according to the customer’s agreement. Contact Liebert Global Services at 800-543-2378 for assistance.

This alarm is triggered by an inverter software routine when the inverter and bypass waveforms are misaligned by more than 6 degrees in phase. This alarm resets automatically once the condition clears. First check if the alarm “Bypass unable to trace” or “Bypass abnormal” occurs. If so, solve it first. Verify the waveform of the bypass voltage. Contact Liebert Global Services at 800-543-2378 for assistance.

Inverter Fault This alarm indicates a fault condition exists within the inverter. Contact Liebert Global Services at 800-543-2378 for assistance.

Output Voltage Abnormal This alarm indicates the inverter voltage waveform is abnormal. Contact Liebert Global Services at 800-543-2378 for assistance.

Input Current Abnormal This alarm indicates the rectifier input current is abnormal. Contact Liebert Global Services at 800-543-2378 for assistance.

The temperature of the inverter filter inductor or inverter common mode inductor is too high to keep inverter running. This alarm is triggered by the signal from a thermostat mounted in the inverter filter inductor. The UPS would recover automatically after a 5 minute delay from the disappearance of the overtemperature signal. If the overtemperature condition is true then check for and verify: High ambient air temperature. Blocked cooling airway Any fan failure Prolonged inverter overload. Contact Liebert Global Services at 800-543-2378 for assistance.

Inv. Inductor Overtemp.

The temperature of the inverter heat sink is too high to keep inverter running. This alarm is triggered by the signal from a temperature monitoring thermostat on the inverter bridge heat sink. The UPS will recover automatically after a 5 minute delay from the disappearance of the overtemperature signal. If the overtemperature condition is true then check for and verify: high ambient air temperature. blocked cooling airway. any fan failure. prolonged inverter overload. Contact Liebert Global Services at 800-543-2378 for assistance.

Inverter Overtemp.

Fan Fault At least one of the cooling fans has failed. Contact Liebert Global Services at 800-543-2378 for assistance.

UPS Status Messages · Bypass Abnormal · Inverter Asynchronous

Page 103 of the Emerson 480V user manual — Table 36 UPS status messages
Page 103 · click to enlarge
Page 103

Table 36 UPS status messages

Event Message Description / Suggested Action (if any)

Inverter STS Fail At least one of the static switches of inverter side is open or short circuit. This fault is locked until power off. Contact Liebert Global Services for assistance at 800-543-2378 for assistance.

At least one of the static switches of bypass side is open or short-circuited. This fault is locked until power off. Contact Liebert Global Services at 800-543-2378 for assistance.

Output Fuse Fail At least one of the output fuses is open. Contact Liebert Global Services at 800-543-2378 for assistance.

Control Power 2 Fail Control Power 2 is abnormal or lost. Contact Liebert Global Services at 800-543-2378 for assistance.

The UPS is overloaded when the load arises above 105% nominal rating. The alarm automatically resets once the overload condition is removed. Confirm that the alarm is true by checking the load percent indicated on the LCD panel to determine which phase is being overloaded. If the alarm is true, measure the actual output current to verify that the indications are valid. Disconnect unnecessary load. In a parallel system, a severe load sharing error can also lead to the alarm. Contact Liebert Global Services at 800-543-2378 for assistance.

The UPS parallel system is overloaded when the total load arises above 105% nominal rating for the set basic number of UPS units. The alarm resets automatically once the overload condition is removed. Confirm that the alarm is true by checking the system load percent indicated on the LCD panel to determine which phase is being overloaded. If the alarm is true, measure the actual output current to verify that the indications are valid. Disconnect unnecessary load and ensure the safety. In a parallel system, a severe load sharing error can also leads to the alarm.

The UPS is overloaded and the overload times out. Note 1: The highest loaded phase will indicate overload timing-out first. Note 2: When the timer is active then alarm “unit overload” should also be active as the load is above nominal. Note 3: When the timer has expired, the inverter Static Switch is opened and the load transferred to bypass. The inverter shutdown and will restart after 1 seconds. Note 4: If the load decreases lower than 95% after 5 minutes, the system will transfer back to inverter mode. Confirm that the alarm is genuine by checking the load percent indicated on the LCD. If an overload is indicated then check the load, and investigate any additional load connected prior to the alarm (if applicable).

Inverter Overcurrent The current of inverter IGBT is over limit. If the fault will not reset, contact Liebert Global Services at 800-543-2378 for assistance.

The phase sequence direction of bypass voltage is reversed. Normally, the phase of Phase B lags 120 degrees behind Phase A, and the phase of Phase C lags 120 degrees behind Phase B. Verify that the phase rotation of the bypass supply presented to the UPS is correct, and rectify it if it is found to be in error. Contact Liebert Global Services at 800-543-2378 for assistance.

Load Impact Transfer A transfer to bypass occurred due to a large step load. The UPS should recover automatically. Turn on connected equipment in sequential order to reduce the step loading of the inverter.

The load is on bypass power due to excessive number of transfers that occurred within the last hour. The UPS will recover automatically and will transfer the load back to inverter power within an hour.

Load Sharing Fault UPS units working within a parallel system are not sharing load current correctly. Contact Liebert Global Services at 800-543-2378 for assistance.

DC Bus Abnormal Shut off inverter due to abnormal DC bus voltage. Contact Liebert Global Services at 800-543-2378 for assistance.

System Transfer The whole paralleled UPS system transferred to bypass at the same time. This message will appear on the UPS which passive transfer to bypass.

Parallel Board Fault Parallel board is not working correctly. Contact Liebert Global Services at 800-543-2378 for assistance.

Show 7 more labels / short text on this page
UPS Status Messages · Bypass STS Fail · Unit Overload · System Overload · Unit Overload Timeout · Bypass Phase Reversed · Transfer Timeout
Page 104 of the Emerson 480V user manual — Table 36 UPS status messages
Page 104 · click to enlarge
Page 104

Table 36 UPS status messages

Event Message Description / Suggested Action (if any)

Rectifier, inverter and battery converter were shut down because DC bus voltage is too high. Check whether there is a fault in rectifier side. If not, check whether overload occurs. Restart the inverter after resetting the fault. If fault does not clear, contact Liebert Global Services at 800-543-2378 for assistance.

The parallel cables are not connected correctly in a parallel system. Reset the fault by pressing the Fault Clear button, then restart the inverter by pressing the Inverter On button. If the UPS does not resume normal operation, contact Liebert Global Services at 800-543-2378 for assistance.

Bypass current is over limit above 135% rating. The UPS just alarms and does nothing. Refer to your installation documentation or contact Liebert Global Services at 800-543-2378 for assistance.

LBS Active The LBS setting is active. The UPS is acting as an LBS master or slave in a dual bus configuration.

Battery ground fault Battery ground fault from dry contact signal. Contact Liebert Global Services at 800-543-2378 for assistance.

Inverter turned On manually

Manual Turn On via front panel

Inverter turned Off manually

Manual Turn Off via front panel

EPO Emergency Power Off

Transfer Confirm Interrupted Transfer Confirm

Transfer Cancel Interrupted Transfer is cancel

Unit Off Confirm Unit Turned Off Confirm

System Off Confirm Parallel System Turned Off Confirm

Fault Reset Fault Reset

Alarm Silence Alarm Silence

Turn On Fail Turn On Fail

Alarm Reset Audible Alarm Reset

Bypass Mode UPS in Bypass Mode

Normal Mode UPS in Normal Mode

Battery Mode UPS in Battery Mode

Check UPS output UPS Shutdown, output power-down

Output Disabled UPS Output Disabled

Generator Connected Generator is connected and a signal is sent to UPS

Input CB Open Input CB is Open

Input CB Closed Input CB is Closed

Bypass CB Open Bypass CB is Open

Bypass CB Closed Bypass CB is Closed

Output CB Open Output CB is Open

Output CB Closed Output CB is Closed

Maint. CB Open Maintenance CB is Open

Maint. CB Closed Maintenance CB is Closed

Battery Reverse Connect the battery again and check the wiring of batteries

No Battery Check the battery and the wiring of batteries

Auto start After the UPS was shut down at end of discharge, inverter auto starts when utility is restored

BCB closed BCB closed from dry contact signal

BCB open BCB open from dry contact signal

Show 4 more labels / short text on this page
UPS Status Messages · DC Bus Overvoltage · Parallel Connect Fault · Bypass Overcurrent
Page 105 of the Emerson 480V user manual — Table 36 UPS status messages
Page 105 · click to enlarge
Page 105

Table 36 UPS status messages

Event Message Description / Suggested Action (if any)

Battery Float Charging Battery is float charging

Battery Boost Charging Battery is boost charging

Battery Discharging Battery is discharging

Battery Period Testing Battery is period self-testing.

Batt. Capacity Testing Battery is capacity self-testing.

Batt. Maint. Testing Battery is maintenance self-testing.

UPS System Testing UPS System is testing

Inverter in Setting Inverter is in parameter setting

Rectifier in Setting Rectifier is in parameter setting

Balancer Fault Internal VDC (+) and VDC (-) offset by over 50V exceeding the inverter DC offset compensation capacity. Inverter shuts down. Load transfers to bypass.

Operation Invalid This record is registered following an incorrect operation.

Byp. Abnormal Shutdown Both bypass and inverter voltages unavailable. Load interruption

Setting Save Error History records not saved (Reserved)

Protocol version clash Firmware incompatibility between monitor board and digital signal processor board

MBP-T cabinet Fan Fault Maintenance bypass cabinet fans fault

Ext Input TX Overtemp External input isolation transformer overtemperature

Ext Output TX Overtemp External output isolation transformer overtemperature

Battery Room Alarm Environment in Battery Room Needs Attention

Rec Flash Update Rectifier firmware is being updated

Inv Flash Update Inverter firmware is being updated

Monitor Flash Update Monitor firmware is being updated

Input contactor fault Input contactor fault

LBS abnormal LBS is abnormal

DSP firmware error The inverter firmware is not compatible with the rectifier firmware.

Fan power fail Fan power has failed

Keyboard fault Keyboard has a fault. Check the cable between keyboard with U2 board. Contact Liebert Global Services at 800-543-2378 for assistance.

KVA Invalid An invalid kVA has been configured in unit.Contact Liebert Global Services at 800-543-2378 for assistance.

KVA updated The capacity updating is successful.

Output ground fault Output Line is shorted with ground

UPS Status Messages

Page 106 of the Emerson 480V user manual — Appendix A - UPS Status Messages
Page 106 · click to enlarge
Page 106

UPS Status Messages

Page 107 of the Emerson 480V user manual — Appendix A - UPS Status Messages
Page 107 · click to enlarge
Page 107
Page 107 of the Emerson 480V user manual — Appendix A - UPS Status Messages
Page 108 of the Emerson 480V user manual — SL-25217_REV1_08-07
Page 108 · click to enlarge
Page 108

Ensuring The High Availability 0f Mission-Critical Data And Applications.

Emerson Network Power, the global leader in enabling business-critical continuity, ensures network resiliency and adaptability through a family of technologies—including Liebert power and cooling technologies—that protect and support business-critical systems. Liebert solutions employ an adaptive architecture that responds to changes in criticality, density and capacity. Enterprises benefit from greater IT system availability, operational flexibility and reduced capital equipment and operating costs.

Technical Support / Service

Web Site www.liebert.com

Monitoring 800-222-5877 monitoring@emersonnetworkpower.com

Outside the US614-841-6755

800-222-5877 upstech@emersonnetworkpower.com

Outside the US614-841-6755

800-543-2378 powertech@emersonnetworkpower.com

800-543-2778 Outside the United States

614-888-0246 Locations United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229

Europe Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy +39 049 9719 111 Fax: +39 049 5841 257

While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2007 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.

Asia 7/F, Dah Sing Financial Centre 108 Gloucester Road, Wanchai Hong Kong 852 2572220 Fax: 852 28029250

SL-25217_REV1_08-07

Emerson Network Power. The global leader in enabling Business-Critical Continuity.

EmersonNetworkPower.com

Embedded Computing Embedded Power Power Switching & Controls

Services Racks & Integrated Cabinets Outside Plant

Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.

©2007 Emerson Electric Co.

Show 8 more labels / short text on this page
Single-Phase UPS · Three-Phase UPS · Environmental Systems · AC Power Connectivity · DC Power · Monitoring · Precision Cooling · Surge Protection
Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Ask about the Emerson 480V

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Emerson 480V

Be the first to ask — other owners or our team will answer.

Original document

Emerson 480V manual PDF

108 pages·9.2 MB·Power Supply·PDF
Click any page above to open it here
Page 1 / …
100%
Loading pages…