3.4 Non-Standard Batteries 24 3.5 BCB Shunt Trip 24 3.6 Alber Monitoring System—Optional 25 4.0 OPTIONS 26 4.1 Load Bus Synchronization 26 4.1.1 Performance Requirements 26 4.1.2 LBS Cable and Settings 26 4.2 Configuring Parallel System Operation 27 4.2.1 General 27 4.2.2 Features of Parallel System 27 4.2.3 Operating Principles 28 4.2.4 Operation Modes Summary 28 4.3 Installing Parallel System 28 4.3.1 Conditions for Parallel System 29 4.3.2 Cabinet Installation 29 4.3.3 Preliminary Checks 29 4.3.4 Power Cables 29 4.3.5 Parallel Control Cables 29 4.3.6 Emergency Power Off (EPO) 32 5.0 UPS SPECIFICATIONS 33 5.1 Conformity and Standards 33 5.2 UPS Environmental 33 5.3 UPS Mechanical Characteristics 33 5.4 UPS Electrical Characteristics 34 5.4.1 Input Rectifier 35 5.4.2 DC Intermediate Circuit 36 5.4.3 Inverter Output 36 5.4.4 Bypass Input 36 6.0 INSTALLATION DRAWINGS 37 7.0 OPERATION 53 7.1 General Description 53 7.1.1 Bypass Supplies 54 7.1.2 Operating Modes 54 8.0 OPERATOR CONTROL AND DISPLAY PANEL 56 8.1 Operator Control Panel 56 8.1.1 Display Panel Layout 56 8.2 Mimic Display Indicators 58 8.3 Control Buttons 59 8.4 Audible Buzzer 60 8.5 LCD Overview 60 8.6 Navigation Keys 61 8.7 UPS System Information 61 8.8 LCD Menus and Data Items 62 8.9 Language Selection 64

8.10 Current Date and Time 65 8.11 UPS Status Messages 66 8.12 Types of LCD Screens 67 8.12.1 Opening Display 67 8.12.2 Default Screen 67 8.12.3 UPS Help Screen 68 8.12.4 Screen Saver Window 68 8.13 Pop-Up Windows 69 8.13.1 From Bypass to Inverter Mode With Power Interruption 69 8.13.2 From Inverter to Bypass Mode With Interruption 69 8.13.3 System Self-Test 69 8.13.4 Battery Capacity Test Confirmation 69 8.13.5 Battery Self-Test Aborted, Condition Not Met 69 8.13.6 Battery Refresh Charge Aborted, Condition Not Met 69 9.0 OPERATING INSTRUCTIONS 70 9.1 Liebert NX Operating Modes 70 9.1.1 Circuit Breakers 71 9.2 UPS Startup 72 9.2.1 Startup Procedure 72 9.2.2 Verify Switching Between Operation Modes 73 9.3 Maintenance Bypass Procedure and Powering Down the UPS 74 9.4 Auto Restart 75 9.5 Emergency Shutdown With EPO 75 9.6 Reset After Shutdown for Emergency Stop (EPO Action) or Other Conditions 75 9.7 Battery Protection 76 9.7.1 Battery Undervoltage Pre-Warning 76 9.7.2 Battery End-of-Discharge (EOD) Protection 76 9.8 Multi-Module System Procedures 76 9.8.1 Isolating One Module in a Multi-Module System 76 9.8.2 Inserting One Module into a Multi-Module System 78 9.8.3 Shutdown Procedure—Complete UPS and Load Shutdown 79 9.9 Commissioning a Parallel System 79 9.10 Parallel System Start Up 80 10.0 OPTIONS 81 10.1 Communication and Other User Terminals 81 10.1.1 Analog Input Interface 81 10.1.2 Power Output 81 10.1.3 Liebert IntelliSlot Communication 81 10.1.4 Communication and Monitoring 82 10.1.5 Configuring Baud Rates 83 10.2 LBS Mode—Load Bus Synchronization 87 10.2.1 Remote Alarm Monitor 87 10.3 Replacing Dust Filters 87




SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during installation of your Liebert NX™ UPS and ancillary equipment.
Read this manual thoroughly, paying special attention to the sections that apply to your installation, before working with the UPS. Retain this manual for use by installing personnel.
! WARNING Exercise extreme care when handling UPS cabinets to avoid equipment damage or injury to personnel. The UPS module weight ranges from 1180 to 1290 lb. (535 to 585kg).
Determine unit weight and locate center of gravity symbols before handling the UPS. Test lift and balance the cabinet before transporting. Never tilt equipment more than 15 degrees from vertical.
Battery manufacturers supply details of the necessary precautions to be observed when working on, or in the vicinity of, a large bank of battery cells. These precautions should be followed implicitly at all times.
Follow all battery safety precautions when installing, charging or servicing batteries. In addition to the hazard of electric shock, gas produced by batteries can be explosive and sulfuric acid can cause severe burns. When connected, the nominal battery voltage is 480VDC and is potentially lethal.
In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or those approved for use in fighting electrical fires.
Extreme caution is required when performing maintenance. Be constantly aware that the UPS system contains high DC as well as AC voltages.
Check for voltage with both AC and DC voltmeters prior to making contact.
! WARNING As with other types of high power equipment, dangerous voltages are present within the UPS and battery enclosure. The risk of contact with these voltages is minimized as the live component parts are housed behind a hinged, lockable door. Further internal safety screens make the equipment protected to IP20 standards.
No risk exists to any personnel when operating the equipment in the normal manner, following the recommended operating procedures.
All equipment maintenance and servicing procedures involve internal access and should be carried out only by trained personnel.
! WARNING High ground leakage current: Ground connection is essential before connecting the input supply.
This equipment must be grounded in accordance with local electrical codes.
Maximum load must not exceed that shown on the UPS rating label.
! CAUTION This equipment is fitted with RFI suppression filters. Ground leakage current exceeds 3.5 mA and is less than 30 mA. Transient and steady-state ground leakage currents, which may occur when starting the equipment, should be taken into account when selecting instantaneous residual current circuit breakers (RCCBs) or residual current devices (RCDs). RCCBs must be selected sensitive to DC unidirectional pulses (Class A) and insensitive to transient current pulses. Note also that the ground leakage currents of the load will be carried by this RCCB or RCD.

! WARNING Under typical operation and with all UPS doors closed, only normal safety precautions are necessary. The area around the UPS system should be kept free of puddles of water, excess moisture and debris. Special safety precautions are required for procedures involving handling, installation and maintenance of the UPS system and the batteries. Observe all safety precautions in this manual before handling or installing the UPS system. Observe all precautions in this manual, before as well as during performance of all maintenance procedures. Observe all battery safety precautions before working on or near the battery. This equipment contains several circuits that are energized with high voltage. Only test equipment designed for troubleshooting should be used. This is particularly true for oscilloscopes. Always check with an AC and DC voltmeter to ensure safety before making contact or using tools. Even when the power is turned Off, dangerously high electric charges may exist within the UPS. All power and control wiring should be installed by a qualified electrician. All power and control wiring must comply with the NEC and applicable local codes. ONLY qualified service personnel should perform maintenance on the UPS system. When performing maintenance with any part of the equipment under power, service personnel and test equipment should be standing on rubber mats. The service personnel should wear insulating shoes for isolation from direct contact with the floor (earth ground). Never work alone, even if all power is removed from the equipment. A second person should be standing by to assist and summon help in case an accident should occur.
! CAUTION This unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J of the FCC rules. These limits provide reasonable protection against harmful interference in a commercial environment. This unit generates, uses and radiates radio frequency energy and, if not installed and used in accordance with this instruction manual, may cause harmful interference to radio communications. This unit is not designed for use in a residential area. Operation of this unit in a residential area may cause harmful interference that the user must correct at his own expense.
Battery Cabinet Precautions The following warning applies to all battery cabinets supplied with UPS systems. Additional warn- ings and cautions applicable to battery cabinets may be found in 3.0 - Battery Installation.

Risk of electrical shock
Indicates caution followed by important instructions
Requests the user to consult the manual
Indicates the unit contains a valve-regulated lead acid battery

Liebert’s NX Uninterruptible Power Supply system provides continuous, high-quality AC power to your business-critical equipment, such as telecommunications and data processing equipment. The Liebert NX UPS supplies power that is free of the disturbances and variations in voltage and fre- quency common to utility power, which is subject to brownouts, blackouts, surges and sags.
The Liebert NX utilizes the latest in high-frequency, double-conversion pulse width modulation tech- nology and fully digital controls to enhance its reliability and increase the ease of use. This section describes the Liebert NX’s environmental requirements and mechanical considerations that must be taken into account when planning the positioning and cabling of the UPS equipment.
Because every site is unique, this section presents a guide to general procedures and practices that should be observed by the installing engineer, rather than step-by-step installation instructions.
! WARNING Do not apply electrical power to the UPS equipment before the arrival of the commissioning engineer.
! WARNING The UPS equipment should be installed by a qualified engineer in accordance with the information contained in this section.
! WARNING Special care should be taken when working with the batteries associated with this equipment. When connected together, the nominal battery voltage is 480VDC and is potentially lethal.
If electrolyte comes into contact with skin, the affected area should be washed immediately with large amounts of water.
1.1 External Inspections 1. While the UPS system is still on the truck, inspect the equipment and shipping container(s) for any signs of damage or mishandling. Do not attempt to install the system if damage is apparent. If any damage is noted, file a damage claim with the shipping agency within 24 hours and contact Liebert Global Services at 1-800-LIEBERT to inform them of the damage claim and the condition of the equipment. 2. Compare the contents of the shipment with the bill of lading. Report any missing items to the carrier and your local Liebert representative immediately.
Installation

1.2 Internal Inspections 1. Remove any packaging material, then visually examine the UPS and battery equipment for transit damage, both internally and externally. Report any such damage to the shipper and to Liebert immediately. 2. Check the nameplate inside the cabinet door to verify that the model number and rating correspond to the ones specified. Record the model number and serial number in the front of this installation manual. This information is necessary should service be required. 3. Check for loose connections or unsecured components in the cabinet. 4. Check for shipping damage to internal components.
If the equipment will not be installed immediately, it must be stored indoors where the humidity is no higher than 90% and the temperature is no higher than 104°F (40°C). The storage area must protect the Liebert NX from excessive moisture (see 5.2 - UPS Environmental).
! CAUTION If the battery cabinet must remain disconnected from power for more than six (6) months, the battery must be recharged before use. To charge the batteries, the battery cabinet must be connected to the Liebert NX UPS and the UPS must be connected to utility power and started up because the charger operates only while the Liebert NX UPS is operating.
! CAUTION When batteries are installed in a cabinet adjacent to the UPS unit, the battery—not the UPS—dictates the designed maximum ambient operating temperature.
1.3.1 Identification The equipment supplied has an identification tag on the back of the main door listing the type and size of the UPS. 1.4 UPS Location
Choose a location for the UPS that offers:
Installation

Batteries must be installed in Liebert NX 480V battery cabinets or battery room. Temperature is a major factor in determining battery life and capacity. Battery manufacturers recommend an operat- ing temperature of 77°F (25°C). Ambient temperatures higher than this reduce battery life; tempera- tures lower than this reduce battery capacity. In a typical installation, battery temperature should be maintained between 74°F and 80°F (23-27°C). Batteries should be placed where there are no main heat sources or air inlets to prevent portions of batteries from being either much warmer or much cooler than other parts of the batteries.
1.4.3 Special Considerations for Parallel Systems 1. Consider the grounding configuration of your system before finalizing module placement. For optimal ground performance, the Liebert NX modules should be close together. 2. For optimal load-sharing performance, the UPS output cables should be approximately the same length, plus or minus 20 percent. 3. Position modules in such a way as to minimize the length of power cables and control wiring between UPS modules and the paralleling cabinet. 1.5 Considerations in Moving the Liebert NX
Ensure that the UPS weight is within the designated surface weight loading (lb./ft2 or kg/cm2) of any handling equipment. See Table 7 for weights of various units.
To move the UPS and optional battery cabinets:
The optional battery cabinets should be moved with a forklift or similar equipment.
! WARNING Ensure that any equipment that will be used to move the Liebert NX has sufficient lifting capacity. The Liebert NX weight ranges from 1180 to 1290 lb. (535 to 585kg). See Table 7 for details. The UPS presents a tipping hazard. Do not tilt the Liebert NX further than 15 degrees from vertical.
The UPS is fitted with casters—take care to prevent movement when unbolting the equipment from its shipping pallet. Ensure adequate personnel and lifting equipment are available when taking the Liebert NX off its shipping pallet. Do not tilt the unit more than 15 degrees from center.
! WARNING The casters are strong enough for movement across even surfaces only. Casters may fail if they are subjected to shock loading, such as being dropped or rolled over holes in the floor or obstructions. Such failure may cause the unit to tip over, injuring personnel and damaging the equipment.
Care must be taken when maneuvering cabinets fitted with batteries. Keep such moves to a minimum. For further information, see Battery Cabinet Precautions on page 2.
When the equipment has been finally positioned, ensure that the adjustable stops are set so that the UPS will remain stationary and stable (see 6.0 - Installation Drawings).
The Liebert NX is constructed with a steel frame and removable panels. Top and side panels are secured to the chassis by screws. The doors may be opened for access to power connections bars, aux- iliary terminal blocks and power switches.
The UPS comes with an operator control panel, which provides basic operational status and alarm information. Cooling is provided by internal fans. The unit sits on four casters. Adjustable stops are provided to prevent the UPS from moving once it has been moved to its final position.
Installation

There are no ventilation grilles on the sides or rear of the UPS. The unit may be placed with the rear against a wall and optional cabinets on either side.
To enable routine tightening of power terminations within the UPS, make sure there is sufficient clearance in front of the Liebert NX to permit free passage of personnel with the door fully opened.
Leave a minimum of 8 in. (203mm) between the top of the UPS and the ceiling to permit adequate air circulation above the unit. Liebert recommends against using air conditioning or other systems that blow air onto the top of the unit.
The diagrams in 6.0 - Installation Drawings show the location of holes in the base plate for bolting the equipment to the floor.
If the equipment is to be placed on a raised floor, it should be mounted on a pedestal that will support the equipment point loading. Refer to the bottom view in Figure 21 to design this pedestal.
Cables can enter the Liebert NX from the top or bottom. Cable entry is made possible by removing a metal plate attached to the UPS.
These plates are designed to allow the personnel to punch holes for fitting and securing the conduit. Once the conduit holes are punched, these plates should be reattached to the UPS.
! CAUTION To reduce the risk of fire, connect only to a circuit provided with correct amperes maximum branch circuit overcurrent protection (see Table 8) in accordance with the National Electric Code, ANSI/NFPA 70.
A UPS system can comprise a number of equipment cabinets, depending on the individual system design requirements—e.g., UPS cabinet with External Bypass cabinet and Maintenance Bypass cabi- net. In general, all cabinets used will be the same height and are designed to be positioned side-by- side to form an aesthetically appealing equipment suite.
The Maintenance Bypass Cabinet must be cabled and bolted to the Liebert NX before the UPS and bypass cabinet are moved into their final position. Connect the input wiring to the Maintenance Bypass Cabinet ONLY after the units are connected and positioned.
Battery cabinets may be bolted to either side of the Liebert NX; see Figure 1.
Installation


Installation


Installation

The UPS requires both power and control cabling once it has been mechanically installed. All control cables must run separate from power cables in metal conduits or metal ducts that are electrically bonded to the metalwork of the cabinets to which they are connected.
! WARNING Before connecting input power to the Liebert NX, ensure that you are aware of the location and operation of the overcurrent protection devices that connect the UPS input/bypass supply to the power distribution panel.
De-energize and lockout or tagout all incoming high- and low-voltage power circuits before installing cables or making any electrical connections.
The main factors affecting the choice and size of cable are voltage, current (also taking into account overcurrent), room temperature and conditions of installation of the cable.
The power cables of the system must be sized with respect to the following description:
The power cables can be sized to suit the UPS unit rating according to Table 8.
Refer to Table 24 for lug size and torque requirements.
Electrical Connections

2.1.2 UPS Input Configuration Figure 3 illustrates the Liebert NX in a split bypass (dual-input) configuration. In this configuration the Static Bypass and the Maintenance Bypass lines are supplied from a separate feed from the Main input. Both sources must be protected externally with properly sized protective devices. By default, the unit ships with internal links installed between the bypass input and main input (Single Input configuration). To wire the unit as a dual input UPS, remove the links and wire the bypass to the input bus bars, then wire the Main input directly to CB1 (see Figure 4).

The following are guidelines only and are superseded by local regulations and codes of practice where applicable. Use wiring rated at 75°C or greater.
1. The ground conductor should be sized in accordance with the input overcurrent protection device data in Table 8. The ground cable connecting the UPS to the main ground system must follow the most direct route possible. Control wiring and power wiring must be run in separate conduit. Output and input cables must be run in separate conduit. 2. Consider using paralleled smaller cables for heavy currents—this can ease installation. 3. When sizing battery cables, a maximum voltage drop of 4VDC is permissible at the current ratings in UPS terminal. For terminal connection sizing, see Table 8. 4. In most installations, especially parallel multi-module systems, the load equipment is connected to a distribution network of individually protected busbars fed by the UPS output, rather than connected directly to the UPS itself. When this is the case, the UPS output cables can be rated to suit the individual distribution network demands rather than being fully load-rated.
Electrical Connections

2.1.4 Cable Connections The rectifier input, bypass and output are easily accessible from the front of the unit for installation. All require lug type terminations. They are connected to busbars on the front side of the Liebert NX and below the circuit breaker, as shown in Figure 4. These busbars are accessible when the front side panel is removed. Busbars to connect external batteries are accessible from the front of the UPS.

Output Busbars (Phases are indicated by letters below the bars)
Rectifier Input Busbars (Phases are indicated by letters below the bars)
Bypass Input Busbars (Phases are indicated by letters below the bars)
Electrical Connections · Battery Input Connections · Ground Busbar

The safety ground busbar is located below the Maintenance Bypass circuit breaker as shown in Figure 4. The safety ground cable must be connected to the ground busbar and bonded to each cabi- net in the system.
All cabinets and cable conduit should be grounded in accordance with local regulations.
! WARNING Failure to follow proper grounding procedures can result in electric shock hazard to personnel or the risk of fire, should a ground fault occur.
For safety, it is necessary to install circuit breakers in the input AC supply and external battery bat- tery cabinets, external to the UPS system. Given that every installation has its own characteristics, this section provides guidelines for qualified installation engineers with knowledge of operating prac- tices, regulatory standards and the equipment to be installed.
Electrical Connections

! CAUTION The operations described in this section must be performed by authorized electricians or qualified technical personnel. If you have any difficulties, contact your local Liebert representative or Liebert Global Services.
Once the equipment has been positioned and secured for operation, and the battery and ground col- lars have been connected (see 2.1.4 - Cable Connections), connect the power cables as described below. (Study the reference drawing in 6.0 - Installation Drawings.)
1. Verify that all incoming high and low voltage power circuits are de-energized and locked out or tagged out before installing cables or making any electrical connections. 2. Remove the front protective cover to gain easier access to the connections busbars. 3. Connect the safety ground and any easier bonding ground bus cables to the copper ground busbar located on the bottom of the equipment below the power connections. All cabinets in the UPS system must be connected to the user’s ground connection.
Common Input Connections 5. For common bypass and rectifier inputs, connect the AC input supply cables between the power distribution panel and the UPS input busbars (A-B-C terminals) and tighten the connections to 88 lb-in. (10 N-m) using the M8 bolt provided.
Dual Input Connections 6. For the bypass, connect the AC input supply cables between the power distribution panel and the UPS input busbars (A-B-C terminals) and tighten the connections to 88 lb-in. (10 N-m) using the M8 bolt provided. 7. For the Rectifier Input, connect AC input supply cables between the power distribution panel and the UPS input circuit breaker (A-B-C terminals).
Output System Connections—Ensure Correct Phase Rotation 8. Connect the system output cables between the UPS output busbars (A-B-C terminals) and the critical load and tighten the connections to 88 lb-in. (10 N-m) (M8 bolt).
! WARNING If the load equipment will not be ready to accept power on the arrival of the commissioning engineer, then ensure that the system output cables are safely isolated.
Observe the battery cable polarity. Be sure that the battery connector is made with the cor- rect polarity. 9. Refit all protective covers removed for cable installation
Electrical Connections

If a frequency converter configuration is used, connect the AC input supply cables to the rectifier input busbars (A-B-C terminals). Torque to 88 lb-in (10N-m) for M8 bolts. Ensure correct phase rota- tion. There will not be any AC bypass supply cables to the bypass input (A-B-C terminals) and tighten the connections.
2.2.1 Monitor Board Features Based on your site’s specific needs, the UPS may require auxiliary connections to manage the battery system (external battery circuit breaker, battery temperature sensor), communicate with a personal computer or provide alarm signaling to external devices or for Remote Emergency Power Off (REPO). The monitor board, arranged for this purpose, is located on the rear of the operator access door. The main features are:

Electrical Connections


J3 J1
LCD
J22
J23
J12
J9
J2
PWR MODEM SNMP CARD
J15
J16
J17
J13 J21 J25 J28 J4 J26 J30 J10
J24
BFP INV ACF EPO Dry in MBC BCB
2.3 Dry Contacts
The UPS provides input dry contacts and output dry contacts.

2.3.1 Input Dry Contacts There are several input dry contacts at the X3 slot.


J26 and J30 are the MBC interface.

Electrical Connections

J10 is the BCB box interface.
J10.1 DRV BCB Driver Signal
J10.2 FB BCB Contact State
J10.3 GND Power Ground
J10.4 OL BCB On-Line - Input - This pin will become active when BCB interface is connected. (N.O.)
J10
DRV
GND
FB
OL
OL
Aux – N.O. Aux – N.O.

2.3.4 Output Dry Contacts There are three output dry contact relays at the X1 slot (see Figure 9 and Table 4).
J13
J21
J25
ACF_C
BFP_C
BFP_S
BFP_O
INV_C
INV_S
INV_O
ACF_S
ACF_O
J13.2 BFP_O Bypass feedback protection relay. Normally open. Closed when bypass SCR is shorted.
J13.3 BFP_S Bypass feedback protection relay center
J13.4 BFP_C Bypass feedback protection relay. Normally closed. Open when bypass SCR is shorted.
J21.2 INV_O Inverter mode relay. Normally open. Closed when UPS is in inverter mode.
J21.3 INV_S Inverter mode relay center
J21.4 INV_C Inverter mode relay. Normally closed. Open when UPS is in inverter mode.
J25.2 ACF_O Main input fault relay. Normally open. Closed when main input is in fault.
J25.3 ACF_S Main input fault relay center
J25.4 ACF_C Main input fault relay. Normally closed. Open when main input is in fault.
Electrical Connections · Position Name Description

The UPS has an Emergency Power Off (EPO) function operated by a button on the control panel or by a remote contact provided by the user. The local EPO button is under a hinged, clear plastic shield.
The X2 slot, shown in Figure 10, is the remote EPO input interface. The EPO has a NO/NC contact point that becomes active when shorting terminals X2: 3 and 4 or open terminal connection X2: 2 and 1.
If an external Emergency Stop facility is required, it is connected terminals X2: 1 and 2 or X2: 3 and 4 of the auxiliary terminal block (X2). It also is connected to the Normally Open or Normally Closed remote stop switch between these two terminals using shielded cable (see Figure 10 and Table 5). If this function is not used, terminals X2: 3 and 4 must be opened and X2: 1 and 2 must be closed.
J28 X2
Table 5 EPO input contact relays

Electrical Connections

3.1 Introduction
If using multiple sets of batteries connected in parallel to provide the required battery backup run times, fit each set with an isolating device to permit working on one of the battery sets while leaving the others in service and providing backup protection.
When replacing batteries, replace with the same manufacturer and type, or equivalent. See your Lie- bert representative for a list of approved batteries.
Special care should be taken when working with the batteries associated with the Liebert NX system equipment. When all batteries are connected together, the battery terminal voltage may exceed 480V and is POTENTIALLY LETHAL.
! CAUTION To reduce the risk of fire, connect only to a circuit provided with DC amperes (see Table 12) maximum branch circuit overcurrent protection in accordance with the National Electric Code, ANSI/NFPA 70.
Battery Installation

Figure 11 Battery cabinet

Optional Alber Data Collector Module
Optional Alber Controller Module
BCB Plate and BCB
The same model battery cabinet may be installed in parallel in multiple cabinet strings for additional capacity. Battery run time depends on the cabinet model, the number of cabinets and the load on the UPS.
Handling—The battery cabinet has casters to facilitate movement over short distances. The bottoms of the battery cabinets are reinforced to permit movement by forklift over longer distances.
Inspection—Remove all panels and visually inspect the batteries, bus connections and cabinet for any damage. Exercise caution: voltage is present within the battery cabinet even before installation. If there are signs of damage, do not proceed. Call Liebert Global Services at 1-800-542-2378.
Storage—The batteries can be stored for up to six months without appreciable deterioration. If plan- ning to store a battery cabinet for longer than six months or at temperatures higher than 77°F (25°C), contact Liebert Global Services for recommended precautions.
! CAUTION Any battery system should be installed by qualified personnel.
When installing an external battery cabinet that is NOT a Liebert NX battery cabinet, the customer must provide overcurrent protection. See Table 8 for sizing of protection devices.
Battery Installation · Top Cable Entry · Battery Trays

If the Liebert NX battery cabinets are installed on a raised floor, the battery power cables and circuit breaker control cables may be routed to the UPS cabinet via the floor of the cabinet (bottom entry).
If the Liebert NX battery cabinets are installed adjacent to one another on a solid floor, these cables may be passed between the cabinets through lifting slots in the lower sides of the cabinets.
Intertray connections must be made before the battery cabinet can be used.

3.3.3 Installation Considerations Position— If the system includes a matching maintenance bypass cabinet (MBC), the MBC should be installed first and the battery cabinet installed on the opposite side of the UPS. Otherwise, left- side placement of the battery cabinet is preferable. The battery cabinet(s) are designed to be located conveniently next to each UPS module, and are also available in stand-alone configurations with painted side panels. The front access design eliminates side and rear service clearance requirements. Refer to Table 28 for battery cabinet dimensions and weights. Bolt-On Cabinets—Matching battery cabinets are designed to bolt onto the side of the UPS module cabinet. Use bolts that ship with each unit to connect cabinet frames at posts, two places in the front and two places in the rear. Service Clearance—Allow front access to the battery cabinet at all times for maintenance and ser- vicing. Electrical codes require that the battery cabinet be installed with no less than 3 feet (1m) of clearance at the front of the cabinet when operating. Side and rear panels do not require service clear- ance. Cables—Cables may be run between the cabinets through cutouts in the top of the cabinet, eliminat- ing the need for external conduit runs. Route cables before moving cabinets into final position for bolt- ing together. No top or bottom entry cables are required, except for remotely located cabinets which require conduits. Software—To allow the UPS to accurately display the battery run time, the number of battery cabi- nets must be noted when performing initial startup and setup using the configuration software. This is to be performed by the Liebert Global Services customer engineer when commissioning the unit. Casters and Adjustable Stops—The adjustable stops are not designed to bear the full weight of the cabinet. Lower the stops until they are finger-tight in contact with the floor. Then tighten a small amount with a wrench (less than two turns) to give a good friction fit. When mounting the battery cabinet on seismic stands, ensure that the casters are bearing the weight of the cabinet. Battery Support Tray—Be sure to connect the battery tray support to the front of the cabinet before sliding a battery tray out for connection or service. Without the support, the battery tray may fall out of the cabinet. See Figure 13 for details.


Slot in support secured by screw-in connector at corner of battery tray ...
... and notched end of support slips into slot at top corner of battery compartment
3.3.4 Connecting the Battery Cabinet to the UPS After the battery cabinet equipment has been positioned and secured for operation and the batteries have been connected, connect the power cables as described below. (See Figure 28.) 1. Verify that all incoming high and low voltage power circuits are de-energized and locked out or tagged out before installing cables or making any electrical connections. 2. Remove the UPS front protective cover to gain access to the equipment ground busbar. 3. Connect the safety ground and any necessary bonding ground cables to the copper ground busbar. (example: UPS located on the bottom of the equipment below the power connections). All cabinets in the UPS system must be connected to the user's ground connection.
When batteries other than a matching battery cabinet are used, a remote battery disconnect switch with overcurrent protection is required per the National Electrical Code. Contact your local Liebert sales representative about this option. Install battery racks, cabinets and batteries in accordance with the manufacturer's instructions. Verify that the battery area has adequate ventilation and battery operating temperature complies with the manufacturer's specifications and with all applicable national and local codes. If you have any questions concerning batteries, battery racks or accessories, contact Liebert Global Services at 1-800-543-2378.
The Liebert NX battery cabinet has the shunt trip installed in the circuit breaker. When a DC ground fault (using the optional DC Ground Fault kit), a battery overtemperature or EPO is activated, the shunt trip will open the circuit breaker.
Battery Installation

The Liebert matching battery cabinet allows installing an optional Alber Battery monitoring system in the cabinet. The Alber Battery Monitoring by Liebert continuously checks all critical battery parameters, such as cell voltage, overall string voltage, current and temperature. Automatic periodic tests of internal resistance of each battery will verify the battery’s operating integrity. Additional capabilities include automatic internal DC resistance tests and trend analysis providing the ability to analyze performance and aid in troubleshooting.
The Alber monitoring system is installed inside the battery cabinet (see Figure 11). The monitoring system requires approximately 0.5A, single-phase 480V.
This power can come from the output terminals of the UPS, a distribution panel, or another UPS-protected source. This power is to be field supplied. See Figure 26 for wiring location.
For details about operating the Alber system, see the Alber Monitoring System manual.
Battery Installation

4.1 Load Bus Synchronization
The Load Bus Synchronizer (LBS) keeps the output of two independent UPS systems or parallel UPS systems in synchronization even when the systems are operating in different modes and even when either or both systems are operating on batteries. When the LBS is used, one UPS system is desig- nated as master, the other as slave.
The LBS option is typically used with dual-corded equipment or with either the Liebert SmartSwitch or Static Transfer Switch (STS) for single-corded equipment.
The LBS operates under the following conditions:
For Liebert NX-to-Liebert NX dual bus configuration, only one optional LBS cable is required, the built-in LBS will operate normally without an extra LBS control box or interface box. The LBS port is X4 on the parallel board (M3). The parallel board is on the interior of the Liebert NX, above and left of the power electronics; see Figure 23.
An optional, 9-pin LBS cable is used to connect two UPS systems through each system’s DB9 port on its parallel board. For two parallel systems, the LBS cable can be mounted between any two units belonging to different parallel systems. For information about the LBS kit or to order the optional equipment, see your local Liebert representative.
The LBS cable is connected as illustrated in Figures 14 and 15.
X2-1 X2-2
X2-1 X2-2
The parallel board is on the interior of the Liebert NX, above and left of the power electronics; see Figure 23
X1-1 X1-2

UPS
UPS
X3 P5
X3 P5
X3 P5
X3 P5
X2-2 X2-1
X2-2 X2-1
X2-2 X2-1
X2-2 X2-1
P2
P4 P1
P2
P4 P1
P2
P4 P1
P2
P4 P1
X1-1 X1-2
X1-1 X1-2
X1-1 X1-2
X1-1 X1-2
P3
P3
P3
P3
B Parallel System I Parallel System II
A
The LBS function is activated with configuration software; when the LBS takes effect, the graphic LCD will display “LBS active.”
The Liebert NX uses intelligent and reliable decentralized technology to achieve parallel operation of two or more modules.
The parallel system is used to:

480V 3W+G
480V 3W+G
CB 3
CB 3A
CB 1 CB 4
FPC
SBS
AC
AC
UPS
4.2.3 Operating Principles
Redundancy Paralleling
The parallel redundant system can noticeably improve system reliability. In normal condition, none of the UPS modules work at full load. That means that even if the load is increased, the system will not transfer to bypass. And when a UPS module shuts down due to any failure, the remaining UPS mod- ules can still power and protect the load. When redundancy is lost due to module failure or load increase, the parallel system will trigger an alarm.
The parallel system also has operation modes such as normal, battery, bypass and maintenance bypass. All UPS modules in the parallel system operate in coordination.
The basic installation procedure of parallel system is the same as that of single module system. The following sections introduce only the installation procedures specific to the parallel system.

Parallel system composed of two or more UPS modules using parallel cabinet
The UPS modules that will form the parallel system should be placed side-by-side. Each battery cabi- net is placed next to its corresponding UPS module.
The parallel cabinet should be placed in the middle of the system.
Each UPS module should have the same firmware and the same hardware version. Refer to the instructions in 4.3.1 - Conditions for Parallel System.
Wiring of power cables is similar to that of a single module system (See 2.1 - Power Cabling). The bypass sources of all modules should be the same, and the outputs should be connected altogether cor- rectly.
Power cables are field-supplied. Power cables to the UPS’s of the paralleling cabinet must be routed through either the top or bottom entry access of the UPS.
Parallel System Control Cables
Make the connections listed below on the parallel logic board (M3) inside the Liebert NX. (See Figure 23 for the location of the parallel logic board):
Shielded and double-insulated control cables, available in lengths of up to 100 feet (30m), must be interconnected in a ring configuration between UPS modules as shown below. The ring configuration ensures high reliability of the control (refer to Figure 17).
Options



The external output breaker of each UPS must have Normally Open auxiliary contacts. These con- tacts must be wired to connector X3 on the Parallel Logic Board (M3). See Figures 18 and 19.
! CAUTION The auxiliary control wire must be installed to ensure proper operation of the system.
Options · Interconnecting · Cables

UPS 1
UPS 2
UPS N
X3 Ext. Maint. Ext. Out
X3 Ext. Maint. Ext. Out
X3 Ext. Maint. Ext. Out

The external emergency stop facility is identical to that described for the single unit installation— that an individual emergency stop button is provided for each unit.
UPS2
X2:3 X2:4 Monitor Board
X2:3
X2:4 Monitor Board
UPS1
Normally Open EPO
UPS2
X2:1 X2:2
Monitor Board
X2:1 X2:2
Monitor Board
UPS1
Normally Closed EPO
Options

These specifications describe requirements for the Liebert NX UPS.
The UPS has been designed to conform to the following standards:
The UPS system has UL and c-UL approval.
The UPS is designed to operate under the following environmental conditions without damage or deg- radation in electrical operating characteristics:
Rated Power 40kVA 60/80kVA 100/120kVA
Operating Temperature, UPS 32°F to 104°F (0°C to 40°C)
Optimal Operating Temperature, Battery 68°F to 86°F (20°C to 30°C)
Relative Humidity 0 to 95%, non-condensing
Acoustical Noise, dBA at 39 in. (1m) 62 62 64
Altitude of Operation ≤1000m per IEC 62040/3
Storage-Transport Temperature, UPS, -4°F to 158°F (-20°C to 70°C)
Storage-Transport Temperature, Battery -4°F to 86°F (-20°C to 30°C)
Width, in. (mm) 23.6 (600)
Depth, in. (mm) 38 (965)
Height, in. (mm) 78.5 (2000)
Heat Dissipation, BTU/H (kWH) 5200 (1.52) 5500 (1.61)
Airflow, CFM (m3/h) 1760 (2990) 1668 (2834)
Cable Entry Bottom or Top
Protection Grade (with open/closed front doors) IP 20
Weight, lb (kg) 1290 (585) 1422 (645)
UPS Specifications · Parameter 80kVA 120kVA · Color Black (Z-0350)

Input (For Single-Input Unit)
Maximum Recommended Lug (Thomas & Betts part number)
2-Hole; 3/8" Bolt Mechanical
60 72 100.2 120.3 125 8M 54108 ADR21
80 96 133.6 160.4 175 8M 54157 ADR21
100 120 167.1 200.5 225 8M 54167 ADR50
120 144 200.5 240.6 250 8M 54172-TB ADR50
Rectifier input (for dual input unit only)
Maximum Recommended Lug (Thomas & Betts part number)
2-Hole; 3/8" Bolt Mechanical
60 72 101.3 124.5 125 8M 54108 ADR21
80 96 135 166 175 8M 54157 ADR21
100 120 168.8 207.6 225 8M 54167 ADR50
120 144 202.5 249.1 250 8M 54172-TB ADR50
Bypass input (for dual input units)
Maximum Recommended Lug (Thomas & Betts part number)
2-Hole; 3/8" Bolt Mechanical
60 72 100.2 110 8M 54107 ADR21
80 96 133.6 150 8M 54152-TB ADR21
100 120 167.1 175 8M 54157 ADR21
120 144 200.5 225 8M 54167 ADR50
Maximum Recommended Lug (Thomas & Betts part number)
2-Hole; 3/8" Bolt Mechanical
60 72 100.2 110 8M 54107 ADR21
80 96 133.6 150 8M 54152-TB ADR21
100 120 167.1 175 8M 54157 ADR21
120 144 200.5 225 8M 54167 ADR50

Maximum Recommended Lug (Thomas & Betts Part Number)
2-Hole; 3/8" bolt Mechanical
40 82 at 480VDC 98 at 400VDC 70 8M 54106 ADR21
60 122 at 480VDC 146 at 400VDC 110 8M 54107 ADR21
80 163 at 480VDC 195 at 400VDC 150 8M 54152-TB ADR21
100 204 at 480VDC 244 at 400VDC 175 8M 54157 ADR21
120 244 at 480VDC 293 at 400VDC 225 8M 54167 ADR50
1. Nominal (Nom) current is based on full rated output load. 2. Maximum (Max) current (125% of nominal) is short duration for battery recharge conditions. 3. UPS input and bypass cables must be run in separate conduit from output cables. 4. Nominal battery voltage is shown at 2.0 volts/cell per NEC 480-2. 5. OCPD = Overcurrent Protection Device. Recommended AC input and AC output overcurrent protection represents 125% of nominal full load current (continuous) per NEC 215. 6. Minimum-sized grounding conductors to be per NEC 250-122. Parity-sized ground conductors are recommended. Neutral conductors to be sized for full capacity per NEC 310-15 (b)(4). References are per NEC 1999. 7. Wiring requirements: a. AC Input: 3-phase, 4-wire, plus ground output. b. AC Output: 3-phase, 3- or 4-wire, plus ground 8. All wiring is to be in accordance with national and local electric codes.
Table 9 Rectifier input power
Rated Power kVA 40 60 80 100 120
Rated Voltage, VAC 480
Supply 3-phase, 3-wire plus ground
Input Voltage Tolerance, VAC (without derating)
Power Factor > 0.99 at full load; >0.98 at half load
Harmonic Current Less than 3% at full rated UPS output load
See Table 8 for current ratings. Overload capacity of input current: 100% Imax
Input Voltage Window
Percentage
Inverter Load,
Charger Load,
(L-L Voltage)
of Nominal
Percentage
Percentage
432VAC to 552VAC 90-115 100% 100%
431VAC to 384VAC 80-89 100% 30%
383VAC to 360VAC 75-79 100% 0%
359VAC to 288VAC 60-74 80% 0%
Battery Manufacturer Models Supplied
Enersys Yuasa HX205 — —
C&D Dynasty UPS12-100MR UPS12-150MR UPS12-210MR

Table 12 DC intermediate circuit
Rated Power kVA 40 60 80 100 120
Recommended number of lead-acid batteries Total 40 battery blocks of 12VDC (240 cells of 2VDC)
will be supported by UPS
Recommended float charge voltage 2.27VDC *
Recommended boost charge voltage 2.4VDC *
Recommended end of discharge voltage 1.67 - 1.75 VDC
Maximum recharge battery current, A * 14.8 22.2 29.6 37.0 44.4
Maximum boost charge duration, min. * 1800
Boost-float threshold current, A * 0.1 C default
Temperature voltage compensation, mV/°C * From 0 to 5 mV/deg. C/cell. Default value is 3mV/deg. C/cell.*
Ripple voltage superimposed % ≤ 1
* Set by configuration software and based on usage of VLRA batteries.
See Table 8 for current ratings.
Table 13 Inverter output
Rated Power kVA 40 60 80 100 120
Rated voltage, VAC 480
Supply 3-phase, 3-wire plus ground
Frequency, Hz 60 (50Hz in frequency converter mode)
Rated Power, kW 36 54 72 90 108
Three-phase transient overload, min. load
105% to 110% for 60 minutes 111% to 125% for 10 minutes
126% to 150% for 1 minute
Voltage Regulation % ±1.0% three-phase RMS average for a balanced three-phase load
±2.0% three-phase RMS average for a 100% unbalanced load
Frequency Regulation % Nominal frequency regulation is ±0.05% in single module mode,
and+/- 0.25% in parallel mode.
Maximum rate of change of frequency, Hz/sec For single mode, the slew rate is adjustable from 0.1Hz/s to 3Hz/s
See Table 8 for current ratings.
Table 14 Bypass input
Rated Power, kVA 40 60 80 100 120
Rated voltage, VAC 480
Supply Three-phase, 3-wire plus ground
Bypass voltage tolerance % Upper limit: +10%, +15% or +20%; Upper limit default: +15% Lower limit: -10%, -20%, -30% or -40%; Lower limit default: -20%
Input frequency tolerance % ±2.5%, ±5%, ±10% and ±20%; default ±10%
Time Long-term operation:
Load
Bypass overload capacity (all ratings)
See Table 8 for current ratings.
UPS Specifications · Frequency, Hz 60

The diagrams in this section illustrate the key mechanical and electrical characteristics of the Liebert NX UPS System cabinets.
Center of Gravity Without Internal Battery
600mm (23.6")
2000mm (78.7")
997mm (39.3")
301mm (11.9")
39.6mm (1.6")
360mm (14.2")
Left Side
1. All dimensions are in millimeters (in.). 2. Eight-inch minimum clearance above unit required for air exhaust. 3. Keep cabinet within 15 deg. of vertical while handling. 4. Top and bottom cable entry available through removable access plates. Remove access plate, punch to suit conduit size and replace. 5. Color - black. 6. Unit bottom is structurally adequate for forklift handling. 7. Open door to replace air filter, washable type. 8. M10 threaded mounting holes used for seismic anchoring or floor stand. NOTE: If floor stand is used, the weight of the unit must be supported under all casters.
9. Each mounting location is supported by (2) 10ga. (.135") galvanized steel. The threaded insert is approx. 3/4" deep. Mounting holes are underneath unit base; mounting bolts must be threaded into unit. 10. Includes side panel. Side panels must be removed from adjacent units that are bolted together. 11. Leveling feet are not designed to carry the full weight of the cabinet. 12. Finger-tighten leveler against the floor, then tighten with a wrench less than 2 turns for friction fit against floor.
Installation Drawings · Liquid Crystal Display



Installation Drawings


NOTES 1. All dimensions are millimeters (in.). 2. Top and bottom cable entry available through removable access plates. Remove, punch to accommodate conduit size and replace. 3. Control wiring and power wiring must be run in separate conduit. Output and input cables must be run in separate conduit. 4. Aluminum and copper-clad aluminum cables are not recommended. 5. All wiring is to be in accordance with national and local electrical codes.
Installation Drawings

896.6 (35.3)
169.5 (6.7)
372.7 (14.7)
172.1 (6.8)
26.8 (1.1)
609.3 (24)
474.3 (18.7)
322.9 (12.7)
575.9 (22.7)
322.9 (12.7)
779.1 (30.7)
872.2 (34.3)
Bottom (Viewed From Below)
Top (Viewed From Above)
845 (33.2)
418.9 (16.5)
Leveling Feet (See Note #9)
2000 (78.7)
683 (26.9)
1. All dimensions are in millimeters (inches) 2. Minimum clearance 36" front and 8" top required for air exhaust. 3. Top and bottom cable entry available through removable access plates. 4. Keep cabinet within 15 deg. of vertical while handling. 5. Control wiring and power wiring must be run in separate conduit. 6. Aluminum and copper clad cables are not recommended. 7. All wiring is to be in accordance with national and local electrical codes. 8. Intercabinet wiring between the UPS and the external battery cabinet is field-supplied. 9. Leveling feet are not designed to carry the full weight of the cabinet. Finger-tight leveler against the floor, then tighten with a wrench less than 2 turns for friction fit against floor. 10. Side panels included. 11. M10 threaded mounting holes used for seismic anchoring or floor stand. NOTE: If floor stand is used the weight of the unit must be supported under all casters. Mounting holes same spacing front and rear. 13. Battery-support tray connects to the front of the cabinet with the support brackets. Without the support, the battery may fall out of the cabinet.

Figure 26 Terminal details, 33" battery power pack system, single cabinet Liebert NX

NOTES: 1. All dimensions are in millimeters (inches). 2. All cables should be routed before bolting cabinets together. 3. The cables between the battery cabinet and the UPS cabinet must be supplied by others. 4. All hardware supplied with battery cabinet for bolting cabinet to UPS use M6 hardware provided; assemble as shown in detail drawings. 5. All external wiring is to be in accordance with national and local electrical codes.
Installation Drawings


Installation Drawings



A UPS Battery Terminal Block First External Battery Cabinet Positive, Negative
Control Terminal Block UPS Monitoring Board Battery Breaker Auxiliary Contacts
Installation Drawings

Figure 29 Outline drawing, Liebert NX480V, 80-120kVA Type E and E2 parallel cabinet
965 (38)
Top
Right Side
1. All dimensions are in millimeters (in). 2. Eight-inch minimum clearance above unit required for air exhaust. 3. Keep cabinet within 15 deg. of vertical while handling. 4. Top and bottom cable entry available through removable access plates. Remove access plate, punch to suit conduit size and replace. 5. Color - black. 6. Unit bottom is structurally adequate for forklift handling. 7. M10 threaded mounting holes used for seismic anchoring or floor stand. NOTE: If floor stand is used, the weight of the unit must be supported under all casters. 8. Each mounting location is supported by two 10 ga. (.135") galvanized steel. The threaded insert is approximately 3/4" deep. Mounting holes are underneath unit base; mounting bolts must be threaded into unit. 9. Side panels must be removed from adjacent units that are bolted together. 10. Leveling feet are not designed to carry the full weight of the cabinet. Finger-tighten leveler against the floor, then tighten with a wrench less than 2 turns for friction fit against floor.
Front
Installation Drawings


1. All dimensions are in millimeters (in). 2. Eight-inch minimum clearance above unit required for air exhaust. 3. Keep cabinet within 15 deg. of vertical while handling. 4. Top and bottom cable entry available through removable access plates. Remove access plate punch to suit conduit size and replace. 5. Color - black. 6. Unit bottom is structurally adequate for forklift handling. 7. M10 threaded mounting holes used for seismic anchoring or floor stand. NOTE: If floor stand is used, the weight of the unit must be supported under all casters. 8. Each mounting location is supported by two 10 ga. (.135") galvanized steel. The threaded insert is approximately 3/4" deep. Mounting holes are underneath unit base; mounting bolts must be threaded into unit. 9. Side panels must be removed from adjacent units that are bolted together. 10. Leveling feet are not designed to carry the full weight of the cabinet. Finger-tighten leveler against the floor, then tighten with a wrench less than 2 turns for friction fit against floor.
Installation Drawings

Figure 31 Main component location drawing Liebert NX 480V, Type E parallel cabinet
System O/P Tie Breaker
Kirk - Key Fuse Disconnect
System Bypass Tie Breaker

Figure 32 Main component location drawing Liebert NX 480V, Type E1 parallel cabinet
System Input 1240 (48.8)
2000 (78.7)
Front (With Covers )

Figure 33 Main component location drawing Liebert NX 480V, Type E2 parallel cabinet
System O/P Tie Breaker


A Utility Source Parallel Cabinet Ph A, B, C - System
C1-C4 UPS #1-UPS #4 Module AC Output Parallel Cabinet Ph A, B, C - UPS Outputs
D Parallel Cabinet Critical Loads Ph A, B, C - System
Installation Drawings


A Utility Source Parallel Cabinet Ph A, B, C - System Input
AC Input Ph A, B, C - UPS Inputs
AC Output Parallel Cabinet Ph A, B, C - UPS Outputs
D Parallel Cabinet Critical Loads Ph A, B, C - System Outputs
G1-G4 Parallel Cabinet UPS #1-UPS #4 Module UPS Parallel Logic Board (M3) Output Breaker Aux Contact
H1-H4 Parallel Cabinet UPS #1-UPS #4 Module UPS Parallel Logic Board (M3) UPS Bypass Detection
Installation Drawings



C1-C4 UPS #1-UPS #4 Module AC Output Parallel Cabinet Ph A, B, C - UPS Outputs
D Parallel Cabinet Critical Loads Ph A, B, C - System Outputs
E1-E4 Parallel Cabinet UPS #1-UPS #4 Module Gnd Ground - UPS
G1-G4 Parallel Cabinet UPS #1-UPS #4 Module UPS Parallel Logic Board (M3) Output Breaker Aux Contact
H1-H4 Parallel Cabinet UPS #1-UPS #4 Module UPS Parallel Logic Board (M3) UPS Bypass Detection
Installation Drawings

LEFT SIDE (Without Exterior Panels)
LEFT SIDE (Isometric View)
965 (38 in.)
NOTES: 1. All dimensions are in millimeters (inches) 2. All cables should be routed before bolting cabinets together. 3. The cables between the auxillary cabinets and the UPS cabinet must be supplied by customer. 4. All hardware supplied with ancillary cabinets for bolting cabinet to UPS. 5. Use M6 hardware provided. Assemble as shown in detail drawing. 6. All external wiring is to be in accordance with national and local codes.
2000 (78.7 in)
Remove when cabinets are to be bolted together
U3819301
A
RIGHT SIDE (Without Exterior Panels)
Installation Drawings

7.1 General Description
Liebert’s NX provides continuous, high-quality AC power to your business-critical equipment, such as telecommunications and data processing equipment. The Liebert NX UPS supplies power that is free of the disturbances and variations in voltage and frequency common to utility power, which is subject to brownouts, blackouts, surges and sags.
The Liebert NX utilizes the latest in high-frequency, double-conversion pulse width modulation tech- nology and fully digital controls to enhance its reliability and increase the ease of use. Specifically, the Liebert NX 480V utilizes soft-switching technology to greatly enhance efficiency.
As shown in Figure 38, the AC utility source is input at CB1 and the rectifier converts the AC utility into DC power. The inverter converts that DC power from the utility—or DC power from the batter- ies—into AC power for the load. The batteries power the load through the inverter in the event of a power failure. The utility source can also power the load through the static bypass.
If maintenance or repair of the UPS is necessary, the load can be switched without interruption in service to the maintenance bypass.

Operation

The Liebert NX contains an electronically controlled switching circuit that enables the critical load to be connected to either the inverter output or to a bypass power source via the static bypass line. Dur- ing normal system operation the load is connected to the inverter and the inverter contactor is closed; but in the event of a UPS overload or an inverter failure, the load is automatically transferred to the static bypass line.
To provide a clean (no-break) load transfer between the inverter output and static bypass line, the bypass static switch activates, connecting the load to bypass. To achieve this, the inverter output and bypass supply must be fully synchronized during normal operating conditions. This is achieved through the inverter control electronics, which make the inverter frequency track that of the static bypass supply, provided that the bypass remains within an acceptable frequency window.
A manually controlled, maintenance bypass supply is incorporated into the UPS design. It enables the critical load to be powered from the utility (bypass) supply while the UPS is shut down for routine maintenance.
In dual input configuration, the neutrals of each source must be connected to each other, to guarantee that the dual source has the same voltage potential to earth.
The UPS is designed to operate as an on-line, double-conversion, reverse-transfer system in the fol- lowing modes:
Operating in normal mode, the Liebert NX’s rectifier derives power from a utility AC source and sup- plies regulated DC power to the inverter, which regenerates precise AC power to supply the connected equipment. The rectifier also uses the utility source power to charge the batteries.
When utility AC power fails, the Liebert NX protects the critical load by instantaneously channeling battery power to the inverter, which continues supporting the critical load without interruption. When utility power returns and is within acceptable limits, the Liebert NX automatically shifts back to Normal mode, with the rectifier powering the critical load.
When the Liebert NX is in bypass mode, the load is directly supported by utility power and is without battery backup protection.
The Liebert NX’s inverter static switch and bypass static switch will shift the load from the inverter to bypass mode without an interruption in AC power if the inverter is synchronous with the bypass and any of the following occurs:
Operation

For maintenance or repair, the Liebert NX may be operated in maintenance mode. To place the Lie- bert NX in maintenance mode, the load must be transferred to bypass and the inverter must be turned off. When those conditions are met, the CB3 may be turned on and the UPS may be shut down, permitting disconnecting the batteries for maintenance.
! CAUTION The internal maintenance bypass must not be used when the UPS system is in a parallel system.
! WARNING The UPS input and output must be protected with external overcurrent protection devices. In maintenance mode, the input and output busbars remain energized.
For higher capacity, higher reliability or both, the outputs of up to four UPS modules can be pro- grammed for directly paralleling while a built-in parallel controller in each UPS ensures automatic load-sharing.
The Liebert NX can be programmed into frequency converter mode for either 50Hz or 60Hz stable output frequency. The input frequency may vary from 57Hz to 66Hz. In this mode, the static bypass operation is disabled and the battery becomes optional, depending on any requirement to operate in battery mode (stored energy mode).
Operation

Operator Control and Display Panel
8.1 Operator Control Panel
The control panel and LCD on the front of the Liebert NX let the operator:
The main areas of the control panel are shown below in Figure 39 and detailed in Figure 40.
Liebert NX 2007-01-06 09:20:37 Single Normal 80kVA-3X3
Liquid Crystal Display (LCD)
L2-N/L 3
L3-N/L 1
LED1
L-N current(A) Frequency (HZ)
buttons Control Mimic display
59.9 480 0.99
480 0.99
480 0.99
LED2
LED4 LED5
INVERTER OFF FAULT CLEAR
Input disconnect closed 01-06 09:15
Output disconnect closed 01-06 09 :15
Bypass abnormal 01-06 09:15
STATUS
F2 F4 HELP F1 F3
8.1.1 Display Panel Layout
Figure 40 shows the control panel in greater detail, identifying individual items that are described in the rest of this section.

Operator Control and Display Panel
1 3 2 4 5 6
8 9 10 11

14 15 16 17 18 19
Mimic indicators Control buttons Navigation keys 1. Rectifier indicator 8. Inverter Off Button 15. F1 2. Battery indicator 9. Emergency Power Off Button 16. F2 3. Inverter indicator 10. EPO Cover 17. F3 4. Bypass indicator 11. Fault Clear Button 18. F4 5. Load indicator 12. Silence On/Off Button 19. Help 6. Status indicator 13. Inverter On Button 7. Buzzer 14. LCD

Operator Control and Display Panel
The Mimic display on the front panel consists of six indicators arranged in a single-line diagram depicting the various paths of UPS power, as shown in Figure 41.
Liebert NX 2007-01-06 09:20:37 Single Normal 80kVA-3X3
L 2-N/L3
L 3-N/L1
L-N current (A) Frequency (HZ)
LED4 LED5
59.9 480 0.99
480 0.99
480 0.99
LED3
Output disconnect closed 01-06 09:15
Input disconnect closed 01-06 09:15
Bypass abnormal 01-06 09 :15
INVERTER ON
F2 F4 HELP F1 F3
The current operational status of the Liebert NX is indicated by the color of the indicators—green, amber or red—and whether they are ON (solid), flashing or OFF. Table 15 provides a guide to inter- preting the various states of the indicators.
(see Figure 41) Green Flashing Green / Amber Red Off
Rectifier Load on rectifier Flashing Green: Utility normal, but rectifier not operating
Rectifier fault Rectifier is normal, but utility is abnormal
Battery powering the load
Battery or battery converter abnormal*
Battery and converter are normal, and battery is not discharging
Inverter Inverter powering the load normally
Inverter fault Inverter normal, but off
Bypass Load on Bypass power — Bypass out of normal range
Load UPS output on — UPS output overloaded
UPS no output power
Status No alarms—UPS working normally
UPS has a serious alarm —
* Battery or battery converter abnormal events include these event messages (see Appendix A): No Battery, Battery Replaced, Battery Reverse, Batt. Conv. Over. Curr., Batt. Converter Fault, Batt. Converter Overtemp.

Operator Control and Display Panel
The Control Buttons on the front panel may be used to shut down the UPS completely, turn the inverter On or Off, restart the UPS after a fault and silence the alarm, as shown in Figure 42. The function of each button is described in Table 16.
Button cover EPO button
Liebert NX 2007-01-06 09:20:37 Single Normal 80kVA-3X3
L1-N/L 2
L 2-N/L3
L 3-N/L1
70.8 59.9
71.3 59.9
LED4 LED5
59.9 480
L-L voltage (V) PowerFactor
480 0.99
480 0.99
Input disconnect closed 01-06 09:15
Output disconnect closed 01-06 09:15
Bypass abnormal 01-06 09 :15
INVERTER ON
F2 F4 HELP F1 F3
Table 16 Control buttons
Button (see Figure 42) Function
Completely shuts down the UPS, including the static switch. CAUTION: Use caution before pressing the Emergency Power Off (EPO) button. This button completely shuts down the unit and cuts off power to the critical load.
Inverter Off Press this button to shut down the inverter during operation. The load will be transferred to static bypass.
Fault Clear After the UPS shuts down due to a fault and the alarm condition has been resolved, press this button to clear the fault and restart the UPS.
Press this button once to silence the alarm buzzer when an alarm is active. Any new fault will sound the buzzer again. If the alarm buzzer is not beeping, press this button to test the alarm sound.
Inverter On Press this button to start the inverter and transfer from static bypass to inverter. NOTE: If the inverter is not ready, this will not activate the UPS.

Operator Control and Display Panel
The buzzer produces three types of sounds:
If the buzzer makes no sound, the system may be operating properly, or an alarm may have been silenced manually.
Liebert NX 2007-01-06 09:20:37 Single Normal 80kVA-3X3
L 1-N/L2
L2-N/L3
L3-N/L1
L-N current (A) Frequency (HZ)
LED4 LED5
59.9 480 0.99
480 0.99
480 0.99
LED3
Output disconnect closed 01-06 09:15
Input disconnect closed 01-06 09:15
Bypass abnormal 01-06 09:15
INVERTER ON
F2 F4 HELP F1 F3
8.5 LCD Overview
The LCD on the front panel has five main sections, as shown in Figure 44. Press the F1 key below the LCD to scroll through these sections.
Liebert NX 2007-01-06 09:20:37 Single Normal 80kVA-3X3
Bypass Main LCD menu
L1-N/L2
L2-N/L3
L3-N/L1
L-N current(A) Frequency(HZ) L-L voltage(V) PowerFactor
71.4 59.9 480 0.99
70.8 59.9 480 0.99
71.3 59.9 480 0.99
Input disconnect closed 01-06 09:15
Output disconnect closed 01-06 09:15
Bypass abnormal 01-06 09:15
F2 F4 HELP F1 F3

Operator Control and Display Panel
The navigation keys on the front panel—F1 through F4 and Help—are used to access the LCD to view the current status and other information about the Liebert NX.
Navigation key icons on the LCD appear above each key to indicate its operation (see Table 17). The keys are “soft keys” that can change functions according to the icon.
Key F1 F2 F3 F4 HELP
The UPS system information displayed at the top of the LCD is detailed in Table 18.
Liebert NX UPS name 2007-10-12 Current date 12:30:36 Current time
080kVA-3x3 080 means UPS model is 80kVA; 3x3 means 3 by 3 system (three-phase input and three-phase output) Unit #1 #1 of 6 Paralleled changed to “Unit #1” Single UPS is configured as a single unit system running in Normal mode Normal UPS in normal operation, inverter powering load, no warnings Warning UPS has a general alarm Fault UPS has a serious fault

Operator Control and Display Panel
The LCD menus provide access to the following categories of information and settings for the UPS. Selecting a menu changes the information displayed in the UPS data items portion of the LCD. The menu choices are listed below and described in detail in Table 19.
L-N current (A) Frequency (Hz) L-L voltage (V) Power factor
Frequency (Hz) L-L voltage (V)
L-N current (A) Frequency (Hz) L-L voltage (V) Power factor
Sout (kVA) Pout (kW) Qout (kVAR) Loadlevel % Crest factor
Sout (kVA) Pout (kW) Qout (kVAR) Single unit, no parallel data
Battery voltage (V) Battery current (A) Battery temperature (°C) Remain Time Min. Battery boost charging Battery float charging Battery disconnected
Display contrast Date format set Date & time Comm1 baud rate Comm2 baud rate Comm3 baud rate Communication address Communication mode Callback times Phone No.1 Phone No.2 Phone No.3 Command password
Battery maintenance test Battery capacity test System test Stop testing Freshening Charge Stop Freshening Charge Modem auto-answer enable
UPS model Monitor version Rectifier version Inverter version
* When configured, input transformer voltages are displayed on the front LCD. When not activated, the values are hidden. ** When configured, output transformer voltages are displayed on the front LCD. When not activated, the values are hidden.

Operator Control and Display Panel
Menu Type Item Type Explanation
L-N current (A) Phase current
Frequency (Hz) Input frequency
L-L voltage (v Line-line voltage
Power factor Power factor
TX Input L-L voltage (V) Line-line voltage
Bypass Frequency (Hz) Bypass frequency
L-L voltage (A) Line-line voltage
L-N current (A) Phase current
Frequency (Hz) Output frequency
L-L voltage (V) Line-line voltage
Power factor Power factor
TX Output L-L voltage (V) Line-line voltage
Loadlevel % The percent of the UPS rating load
Crest factor Output current Crest Factor
Single unit, no parallel data When configured as a single unit, UPS has only native load, no system load.
Battery voltage (V) Battery bus voltage
Battery current (A) Battery bus current
Battery temperature (°C) Internal battery temperature °C
Remain Time Min. Battery run time remaining
Battery boost charging Battery is boost charging
Battery float charging Battery is float charging
Battery disconnected Battery is not connected
Records (History Log) Displays all records in the history log
Language (choices for text displayed) User may select any of 12 languages for LCD text.
Display contrast Adjust the LCD contrast
Date format set Choose the format for date display: M/D/Y, D/M/Y, M/D/Y, Y/M/D
Date & time Set the date and time
Comm1 baud rate Communication baud rate setting for Liebert IntelliSlot 1
Comm2 baud rate Communication baud rate setting for Liebert IntelliSlot 2
Comm3 baud rate Communication baud rate setting for Liebert IntelliSlot 3
Communication address This setting is applicable to RS485 communication mode
Communication mode Communication Mode Setting
Callback times When Liebert IntelliSlot 1 Communication mode is Modem, this parameter sets the number of times a number is redialed to send an alarm notification.
Phone No.1 When Liebert IntelliSlot 1 Communication mode is Modem, this is the first phone number to be dialed (to send an alarm notification).
Phone No.2 When Liebert IntelliSlot 1 Communication mode is Modem, this is the second phone number to be dialed (to send an alarm notification).
Phone No.3 When Liebert IntelliSlot 1 Communication mode is Modem, this is the third phone number to be dialed (to send an alarm notification).
Command password User can modify the command password.

Operator Control and Display Panel
Menu Type Item Type Explanation
Battery maintenance test This test performs a partial discharge of the battery to obtain a rough estimate of the battery capacity. Load must be between 20% and 80%.
Battery capacity test This test performs a full discharge of the battery to obtain a precise measure of the battery capacity. Load must be between 20% and 80%.
System test This is a self-test of the UPS. When the user activates this function, a pop-up window appears about 5 seconds later to show the results.
Command (start/stop battery & system tests)
Stop testing Manually stops a battery maintenance test, battery capacity test or system test.
Freshening Charge Allows a temporary Equalize charge for the batteries. This charge is configurable for 1 to 36 hours.
Stop Freshening Charge Manually stops a Freshening Charge
Manually enable the modem’s auto-answer function.
UPS version Provides UPS firmware version numbers for the inverter, rectifier and software display board.
UPS model Provides UPS model information—for example, 480V-60Hz.
The LCD menus and data display are available in 12 languages (Chinese, Dutch, English, French, German, Italian, Japanese, Polish, Portuguese, Russian, Spanish and Swedish). To select a different language:
Liebert NX 2007-01-12 12:30:36 80KVA-3X3 Single Normal
ITALIANO
ESPAÑOL
NEDERLANDS SVENSKA
Input disconnect closed 01-12 12:30 Output disconnect closed 01-12 12:30 Bypass disconnect open 01-12 12:30

Operator Control and Display Panel
To change the system date and time:
Liebert NX 2007-01-12 12:30:36 80KVA-3X3 Single Normal
M/D/Y D/M/Y
12:30:36
Input disconnect closed 01-12 12:30 Output disconnect closed 01-12 12:30 Bypass disconnect open 01-12 12:30

Operator Control and Display Panel
The Liebert NX displays status changes as they occur in the current status window of the LCD, then stores that data in the history log, as shown in Figure 48.
Liebert NX 2007-01-12 12:30:36 80KVA-3X3 Single Normal
2003-01-21 12 :21:12 2003-01-21 12 :21:12 UPS shutdown
2003-01-21 12 :21:12 2003-01-22 12 :30:16 Bypass abnormal
2003-01-21 12 :21:12 2003-01-21 12 :30:16
Input disconnect closed 01-12 12:30 Output disconnect closed 01-12 12:30 Bypass disconnect open 01-12 12:30
See Appendix A for a complete list of status messages, along with a description and any recom- mended actions.

Operator Control and Display Panel
This section provides a quick guide to the main types of LCD screens.
As the UPS begins powering up, the opening display appears, as shown in Figure 49.

HELP
8.12.2 Default Screen
After the UPS has powered up and completed a self-test, the output screen appears, as shown in Figure 50. This window is the default screen.
Liebert NX 2007-01-12 12:30:36 80KVA-3X3 Single Normal
L2-N/L3
L3-N/L1
70.8 59.9
71.3 59.9
59.9 480 0.99
480 0.99
480 0.99
Input disconnect closed 01-12 12:30 Output disconnect closed 01-12 12:30 Bypass disconnect open 01-12 12:30

Operator Control and Display Panel
Press the HELP key below the LCD to display the Help window shown in Figure 51. (Press the HELP key again to exit the Help window.)
Select the current record window
Select the previous menu item
Select the next menu item
Press ENTER key to view KVA history
Press ENTER key to view KVA history
Q2
Q1 Q5
Press help key back to main menu
Press help key back to main menu
8.12.4 Screen Saver Window
If there has been no interaction with the Liebert NX’s LCD for 2 minutes, the screen saver window appears. It remains on the LCD for 2 minutes, then the screen will go dark. The LCD will become active again when any key is pressed.
Liebert NX 2007-01-12 12:30:36 80KVA-3X3 Single Normal
Help information

Operator Control and Display Panel
Pop-up prompt windows appear when the user must confirm a choice or perform an operation. This section describes the pop-up windows.
If the bypass voltage or frequency exceeds the synchronized range and utility voltage or frequency is normal, the inverter cannot be in syn- chronization with the bypass, and the output can transfer to inverter only after an interruption of about 15ms when the user presses the INVERTER ON button. Before transferring, the system will let the user confirm whether the interruption can be accepted, as shown at right. If the bypass voltage returns to normal before the user makes confirmation, the UPS will transfer to inverter mode auto- matically. At the same time, the prompt window will close.
Transfer with Interrupt, please confirm or cancel
If the bypass voltage or frequency exceeds the synchronized range and the UPS is in inverter mode, the user must confirm and accept the power interruption danger before pressing the INVERTER OFF but- ton to shut down the output of the inverter. The user can also cancel the shutdown operation, as shown at right. If the bypass voltage returns to normal before the user makes the confirmation, the UPS will transfer to bypass operation mode automatically, and at the same time the prompt window will close disappear soon.
This operation leads to
output shutdown, Confirm or cancel
When a system self-test is completed, a pop-up window reports the results of the test, as shown at right.
When a battery capacity test is started from the Command menu, the battery will be discharged to low-battery warning level. The Liebert NX asks for confirmation before the test is started, as shown at right.
Battery will be depleted,
When a battery capacity test is started from the Command menu and the battery self-test criteria are not met, the Liebert NX will not per- form a battery test. User should check whether the battery state is boost charging and whether the load level is greater than 20 percent.
When a battery refreshening charge is started from the Command menu and battery refreshening condition fails to meet requirements, the Liebert NX will not perform a battery refreshening charge. User should check if boost charging condition has not met the test criteria, such as (No battery, charger failed, etc.).
aborted, Conditions not met

9.1 Liebert NX Operating Modes
The Liebert NX can operate in any of four modes, as shown in Table 20. This section provides instructions on switching between modes, resetting the UPS, switching the inverter On and Off and performing other operations.
Circuit Breaker State Description
The UPS is powering the load.
The UPS is shut down but the load is connected to utility power via the Maintenance Bypass Supply line. NOTE: The load is not protected against disturbances in AC input power in this mode.
No load power is supplied by the UPS. The load is connected to utility power via the Maintenance Bypass Supply line. NOTE: The load is not protected against disturbances in AC input power in this mode.
CB1:ON or OFF CB2:ON CB3:OFF CB5:ON
The load power is supplied through the static bypass line. This may be considered as a temporary mode during load transfers between inverter and maintenance bypass or supply under abnormal operating conditions.

The UPS can be isolated by means of circuit breakers, mounted inside the cabinet and accessible after opening the front door.
The location of the UPS power switches is shown in Figure 53.

The UPS unit circuit breakers are CB1, CB2, CB3 and CB5.
Operating Instructions

The Liebert NX must be fully installed and commissioned before startup, and external power isolators must be closed. Once those general conditions are met, the UPS may be started.
To start the UPS from a fully powered-down condition:
! WARNING During this procedure the output terminals will become live.
If any load equipment is connected to the UPS output terminals, please check with the load user and ascertain whether it is safe to apply power to the load. If the load is not ready to receive power, then ensure that it is safely isolated from the UPS output terminals.
2. Close CB1, CB2 and CB3 (CB5 is open). The main input contactor closes automatically and the LCD begins to show start-up screens. The Rectifier indicator flashes green while the rectifier is starting up. It stops flashing and becomes solid green about 30 seconds after the rectifier enters the normal operation state. After initialization, the bypass SCR closes. Because the output circuit breaker is still open, the UPS channels power through the Maintenance Bypass Supply line (CB3). The bypass indicator extinguishes, provided that the bypass is normal. The opening display is shown in the figure at right. The UPS Mimic display indicators will be:
HELP
3. Close CB5 (CB1, CB2, CB3 and CB5 are closed). The Maintenance Bypass supply is now in parallel with the UPS Static Switch supply. 4. Verify that the Bypass indicator is Green, then open CB3. The UPS powers from static bypass instead of from maintenance bypass. The bypass and load indicators turn on. The design of the hardware and software ensures uninterrupted output. 5. Close external battery circuit breaker. After the UPS detects that the battery is connected, the red battery indicator extinguishes moments after the battery charger starts operation. The UPS Mimic display indicators will be

Switch from Normal Mode to Battery Mode

Follow the procedure below to transfer the load from the inverter output to the Maintenance Bypass line of the UPS.
! CAUTION Before performing this operation, read the messages on the LCD to be sure that bypass supply is regular and the inverter is synchronous with it. If those conditions are not present, there is a risk of a short interruption in powering the load.
This procedure assumes that the UPS is operating normally.
2. Close maintenance breaker CB3. The Maintenance Bypass supply is now in parallel with the UPS Static Switch supply. 3. Open output breaker CB5. This ends the bypass procedure. The load is now powered directly from the Maintenance Bypass supply. 4. Press the EPO (Emergency Power Off) button at the UPS front panel of this UPS module only. This will disable further Rectifier, Inverter, Static Switch and Battery operation. This will not affect the manual maintenance bypass power switch. If a Liebert NX battery cabinet is connected, the battery circuit breaker will shunt trip open. 5. Open the rectifier switch CB1 and bypass breaker CB2. All operator indicators and messages will turn off as the utility-driven internal power supplies decay. The unit will power down, but the load will continue to be supplied by the manual Mainte- nance bypass.
! WARNING Wait 5 minutes for the internal DC busbar capacitors to discharge before attempting to remove the internal protective barriers.
! WARNING Even with the UPS in maintenance bypass and “Off,” portions of the unit are still energized. Service is to be performed by qualified personnel only.
! CAUTION The load equipment is not protected from normal supply aberrations when operating in maintenance bypass mode.
Operating Instructions

When the main and bypass sources fail, the UPS draws power from the battery system to supply the load until the batteries are depleted. When the UPS reaches its end of discharge (EOD) threshold, it will shut down.
The UPS will automatically restart and enable output power:
If the “Auto Recovery after EOD Enabling” feature is disabled, the user must restart the system man- ually.
This circuit has been designed to switch off the UPS in emergency conditions (i.e., fire, flood, etc.). The system will turn off the rectifier and inverter and will stop powering the load immediately (including the inverter and bypass), and the battery stops charging or discharging. If a Liebert NX battery cabi- net is connected, the circuit breaker in the battery cabinet will shunt trip open.
If input utility power is present, the UPS’s controls will remain active; however, the output will be turned off. To remove all power from the UPS, open the external feeder breaker.
Once all appropriate measures have been taken to correct the problem indicated by the alarm mes- sage appearing on the operator control panel display, carry out this procedure to restore the UPS to regular operation following an EPO action or for the following reasons: Inverter Overtemperature, Cut-off Overload, Battery Overvoltage, excessive switching (BYP: XFER COUNT BLOCK), etc.
When the user confirms that the fault is cleared:
After the EPO button is pressed, if the input utility is removed, the UPS will shut down completely. When input utility is returned, if the Bypass input circuit breaker (CB2) and UPS output circuit breaker (CB5) are closed, the UPS will start up on Bypass. There will be power at the output termi- nals of the UPS.
! WARNING If the internal maintenance bypass circuit breaker (CB3) is closed and input utility is present, there will be power at the output terminals of the UPS.
Operating Instructions

Before the end of discharge, the Liebert NX displays a Low Battery pre-warning. After this pre-warn- ing, the battery has the capacity for 5 minutes discharging with full load (default time). The Liebert NX can be user-configured to display this warning from 3 to 60 minutes before end-of-discharge.
If the battery voltage is lower than the end-of-discharge voltage, the battery converter will be shut down.
9.8.1 Isolating One Module in a Multi-Module System 1. Turn Off the inverter 2. Open External Output CB4 in Parallel Cabinet (see Figure 54). The UPS enters Isolation Status automatically, parallel signaling and communication become masked and output becomes inhibited. 3. Power Off the unit for maintenance. 4. Power On the unit. 5. Unit enters Test Mode by configuration software setting. 6. Diagnosis or testing. 7. The UPS exits Test Mode by configuration software setting. Output becomes inhibited because of Isolation Status. 8. Return all switches to the Normal position. 9. Close External Output CB4 in Parallel Cabinet (see Figure 54). The UPS exits Isolation Status automatically, parallel signaling and communication recovers, output becomes enabled but interlocking works now. 10. Turn On inverter and join the parallel system.
Operating Instructions

Figure 54 Typical parallel system block diagram with common input supply, with separate batteries and
480V 3W+G
480V 3W+G
CB 3
CB 3A
CB 1 CB 4
FPC
SBS
AC
AC
UPS

This procedure outlines how to integrate a UPS module that has been previously isolated from other modules of a group of paralleled UPS modules. It is assumed that the installation is complete, the sys- tem has been commissioned by authorized personnel and the external power isolators are closed.
Mains voltage will be applied to UPS output terminals.
No operator serviceable parts are located behind covers that require a tool for their removal.
Only qualified service personnel are authorized to remove such covers.
1. Open the UPS door to gain access to the main circuit breakers. 2. Open (or confirm disabled) maintenance bypass circuit breaker CB3. 3. Close Input breaker CB1. The Rectifier indicator flashes on the UPS mimic panel during the startup of the rectifier and becomes steady green once the rectifier reaches normal operation state after about 30 seconds. 4. Close external battery circuit breaker. This breaker is inside the battery cabinet or is otherwise adjacent to the battery racks. 5. After the UPS detects the batteries, the red battery indicator extinguishes when the battery charger starts operation. 6. Close bypass circuit breaker CB2. 7. Press the INVERTER ON control button for 2 seconds. The inverter will start up and the inverter indicator flashes while it synchronizes to the load volt- age and frequency. After the inverter is ready, the UPS connects to the load, the inverter indicator becomes steady green and the output indicator turns green. 8. Check that no “Warning” message is displayed in the top right corner of the LCD and that the indicators have the status shown below.
# LED LED Function Status
1 Rectifier indicator Green
2 Battery indicator Off
3 Bypass indicator Off
4 Inverter indicator Green
5 Output indicator Green
6 Alarm indicator Off
The UPS is now operating in NORMAL mode.
Operating Instructions

This procedure must be followed to completely power down the UPS and the load. All power switches, isolators and circuit breakers will be opened and power will be removed from the load.
In multi-module systems, perform each step of the procedure in every UPS module before proceeding to the next step.
! CAUTION This procedure will shut off power to the load.
! CAUTION Except in an emergency situation, do not press any remote EPO button
2. Open the UPS door to gain access to the main circuit breakers. 3. Open the Rectifier input circuit breaker CB1. 4. Open external battery circuit breaker. This breaker is inside the battery cabinet or is otherwise adjacent to the battery racks. 5. Open Output circuit breaker CB5. 6. Open bypass input circuit breaker CB2. 7. Ensure maintenance bypass circuit breaker CB3 is open. 8. All mimic panel LED indications and messages will extinguish as the mains-driven, internal power supplies decay. 9. To completely isolate the UPS from the AC supplies, the main external power input isolator (both isolators, where dual supplies are provided for rectifier and bypass) and external output isolator must be opened and tagged with warning labels accordingly.
! CAUTION The operations described in this section must be performed by authorized electricians or qualified technical personnel. If you have any difficulty, call 1-800-LIEBERT for assistance.
Check the input and output wiring of each UPS module. Ensure that the phase rotation sequence of the main inputs and the bypass inputs and outputs of each UPS module are the same. Ensure that the parallel cables are connected firmly.
It is assumed that the installation is complete, the system has been commissioned by authorized per- sonnel and the external power isolators are closed. Disconnect the load before startup.
Operating Instructions

9.10 Parallel System Start Up 1. Start each UPS normally as described in 9.2 - UPS Startup 2. Turn on the inverter of each UPS module one at a time. 3. Apply the load after the last UPS module transfers to inverter. The total load can be determined through the LCD of either UPS. 4. Verify the load rate of each UPS module. If the load rates are roughly the same, then the parallel system may be assumed to be operating normally.
NOTE If one module cannot transfer to inverter mode long after its inverter is on, its output connection may not be good or its output phase rotation may not be coincident with other modules. At this time, the LCD for the UPS module will display “inverter asynchronous” and the inverter indicator will flash continuously. If either UPS module makes abnormal noise after it transfers to inverter, its parallel cables may be incorrectly connected.
Operating Instructions

Several items of optional equipment are available for connection to the Liebert NX UPS.
The UPS can be integrated into advanced networking environments via UPS monitoring software such as Windows-based UPS Monitor, MultiLink™, Nform™, SiteNet, Modbus / Jbus, SiteScan, SiteScan 2, SNMP, etc. They allow UPS status monitoring and automatic and safe shutdown of the server and PCs.
J8
J3 J1
J22
LCD
J23
J12
J9
J2
PWR MODEM SNMP CARD
J15
J16
J17
J13 J21 J25 J28 J4 J26 J30 J10
J24
BFP INV ACF EPO Dry in MBC BCB
10.1.1 Analog Input Interface
At the X6 slot, there are two analog signal channels. Input range is from 0 to +5V, and the precision is 2 percent. “ENV-T” is used for environment temperature detecting.
The X5 slot can provide power for a modem or an external SNMP card. Available voltage is from 9V to 12V. The maximum current is 500mA.
The Liebert NX has three Liebert IntelliSlot ports to allow field-installation of optional communica- tion cards. Liebert IntelliSlot cards communicate via Liebert’s proprietary ESP2 protocol to cards that translate the information into such protocols as SNMP, IGMnet, Modbus or Jbus. Other cards provide dry contact signals for external signaling of operating status.
The Liebert IntelliSlot communication ports may be installed or removed while the Liebert NX is operating.

Liebert IntelliSlot Web Card - SNMP/HTTP Network Interface Card
This network interface card provides all real-time data and status information as SNMPv1 traps for connection to a 10/100-baseT Ethernet connection. The same card also will transmit the same status information and all measured parameters for display through a Web browser. Table 21 Liebert NX communication options
On the UPS LCD screen, under Settings,
controlled by:
Intellislot 2 (On Monitor
Liebert IntelliSlot WEB-LB 2400
Not simultaneous with Multilink in RS232-1; See 10.1.5 - Configuring Baud Rates
Modbus/Jbus 2400 See 10.1.5 - Configuring Baud Rates
Intellislot 1 (On Monitor
Liebert IntelliSlot WEB-LB 2400
See 10.1.5 - Configuring Baud Rates Not simultaneous with Multilink in RS232-2
Modbus/Jbus 2400 See 10.1.5 - Configuring Baud Rates
Intellislot 3 (On Monitor
Liebert IntelliSlot WEB-LB 2400 See 10.1.5 - Configuring Baud Rates
Modbus/Jbus 2400 See 10.1.5 - Configuring Baud Rates
Top DB9 port RS232-1 Comm 1
9600 Not simultaneous with Web card in top Liebert IntelliSlot.
Service Software (Reserved) 9600 Not simultaneous with Web card in middle Liebert IntelliSlot.
Bottom DB9 port RS232-2 Comm 2

The default baud rate for Liebert IntelliSlots is 9600. To communicate with the OCWEB-LB, Modbus/ Jbus, or the MultiLink cards, the baud rate must be set to 2400.
To change the baud rate (refer to Table 21):
Options



Options

The relay card provides voltage-free contact closures for remote monitoring of alarm conditions.
Delivering On Battery, On Bypass, Low Battery, Summary Alarm, UPS Fault and On UPS sig- nals, the easy-to-install card integrates with AS/400 computers (additional cable required) and other relay contact monitoring systems.
The relay card is rated for 24 VAC/DC at 1A and supported in any of the three Liebert IntelliSlot bays on the Liebert NX.
1 UPS Fault Closed if no UPS failure
4 UPS Fault Closed if UPS fails
5 Summary Alarm** Closed if SUMMARY ALARM** occurs
6 Summary Alarm** Closed if no alarm conditions are present
7 Any Mode Shutdown return Not supported – use External EPO terminal
9 Common - Low Battery
10 Low Battery Closed if battery is OK
11 Low Battery Closed if LOW BATTERY point occurs
14 UPS Any Mode Shutdown Not supported – use External EPO terminal
15 On UPS Closed if ON UPS (inverter) power
16 On Battery Closed if ON BATTERY power (Utility failure)
17 Common - UPS Fault, Summary Alarm, On UPS, On Battery, On Bypass
18 On Battery Closed if not ON Battery power (Utility OK)
24 On Bypass Closed if ON BYPASS
**A Summary Alarm occurs when any of the following conditions exist: 1. Utility power is out of the acceptable range (voltage and/or frequency). 2. UPS is in BYPASS MODE (load not on Inverter power). 3. UPS Battery is LOW. 4. UPS fault has occurred.
JP01 Pin 9 to Pin 17 Allows all relay COMMONS to be tied together.
ANY JP02 Pin 7 to Pin 17 REMOVE - (Interconnects all relay COMMONS and the (not supported) MODE SHUTDOWN Return

The MultiPort 4 card provides four sets of voltage-free contact closures for remote monitoring of alarm conditions UPS operation On Battery and Low Battery condition. A typical application is to allow a maximum of four computer systems to simultaneously monitor the status (e.g., utility power failure-low battery) of a single UPS.
This card is supported in any of the three Liebert IntelliSlot bays on the Liebert NX.


Options

The function of LBS is to keep the output of two independent UPS systems (single unit or multiple unit) in synchronization even when the two systems are operating in different modes (bypass/ inverter) or on batteries. It is usually used with a Static Transfer Switch connected to the critical load to achieve dual bus configuration.
Status and alarm conditions are available on an optional remote alarm monitor (RAM) panel, which is driven by volt-free alarm status contacts (from an optional relay alarm board).
10.3 Replacing Dust Filters 1. Open the UPS door. 2. The dust filters are behind the door. For each filter, there is a bracket on either side holding the dust filter in place, as shown in Figure 58. 3. Remove one bracket and loosen the other. The second bracket need not be removed. 4. Remove the old filter and replace with the new filter 5. Reinstall the bracket that was removed and tighten the other bracket.

Options · Bracket · Bracket Sems screw

Specifications and Technical Data
11.1 Lug Size and Torque Requirements
Use commercially available solderless lugs for the wire size required for your application. Refer to Table 24. Connect wire to the lug using tools and procedures specified by the lug manufacturer.
Nut and Bolt CombinationS
Electrical Connections with Belleville Washers
Lb-in N-m Lb-in N-m
1/4 53 6.0 46 5.2 5/16 107 12 60 6.8 3/8 192 22 95 11 1/2 428 22 256 29
Circuit Breakers With Compression Lugs (For Power Wiring)
Wire Size or Range Lb-in N-m
#6 - #4 100 11 #3 - #1 125 14 1/0 - 2/0 150 17 3/0 - 200 MCM 200 23 250 - 400 MCM 250 28 500 - 700 MCM 300 34
Circuit Breakers With Compression Lugs (For Power Wiring)
Current Rating Lb-in N-m
Terminal Block Compression Lugs (For Control Wiring)
AWG Wire Size or Range Lb-in N-m
#22 -#14 3.5 to 5.3 0.4 to 0.6
UPS12-100MR 40 (4.5)
UPS12-150MR 25 (2.8)
UPS12-210MR 25 (2.8)
UPS12-300MR 110 (12.4)
UPS12-350MR 110 (12.4)
UPS12-400MR 110 (12.4)
11.2 Cable Lengths: Floor to Connection Point Inside UPS
To help calculate the total cable length required, refer to Table 26 for the distance from the floor to selected connection points inside the Liebert NX. Determine the cable length required to reach the

Specifications and Technical Data
Liebert NX, then add the appropriate length from the table and adequate slack for repair and mainte- nance.
From Top of Unit
Connection Point on UPS
in. (mm)
in. (mm)
Bypass AC input supply 13 (330) 66 (1676)
UPS output AC 13 (330) 66 (1676)
Battery power 13 (330) 66 (1676)
Liebert IntelliSlot Communications 60 (1524) 19 (483)
Ground 13 (330) 66 (1676)
Parallel Board 70 (1780) 11 (279)
Output OCPCB Size (A)
System Max Input Current
(VAC)
80 480V 202.5 300 480V 144.3 200
E
120 480V 135.0 200 480V 96.2 125
80 480V 202.5 300 480V 144.3 200
E1
120 480V 135.0 200 480V 96.2 125
80 N/A N/A N/A 480V 144.3 200
E2
120 N/A N/A N/A 480V 96.2 125
80 480V 405.0 600 480V 288.7 400
E
120 480V 270.0 350 480V 192.5 250
80 480V 405.0 600 480V 288.7 400
E1
120 480V 270.0 350 480V 192.5 250
80 N/A N/A N/A 480V 288.7 400
E2
120 N/A N/A N/A 480V 192.5 250
80 480V 607.5 800 480V 433.0 600
E
120 480V 405.0 600 480V 288.7 400
80 480V 607.5 800 480V 433.0 600
E1
120 480V 405.0 600 480V 288.7 400
80 N/A N/A N/A 480V 433.0 600
E2
120 N/A N/A N/A 480V 288.7 400
Use wiring rated at 75°C or greater.

Specifications and Technical Data
Type E1 Parallel Cabinet
Unit Width Depth Height mm (inch) 1240 (48.8) 965 (38) 2000 (78.7)
Type E Parallel Cabinet
Unit Width Depth Height mm (inch) 845 (33.2) 965 (38) 1956 (77)
Unit Width Depth Height mm (inch) 845 (33.2) 965 (38) 1956 (77)
-0.5 100% 50%
-0.6 100% 60%
-0.7 100% 70%
-0.8 100% 80%
-0.9 100% 90%
Unity 1 90% 90%
-0.9 80% 72%
-0.8 77% 61%
-0.7 75% 52%
-0.6 74% 44%
-0.5 73% 36%
Cable Size (Copper Wire Only)
Torque to Tighten Terminal Bus & Lug Body
Main Input (Single Input) 4 10 N*m
Main Input (Dual Input) 4 10 N*m
Bypass Input (Dual Input) 4 10 N*m
Output 3 10 N*m
Cable Size (Copper Wire Only)
Torque to Tighten Terminal Bus & Lug Body
Main Input (Single Input) 1 10N*m
Main Input (Dual Input) 1 10N*m
Bypass Input (Dual Input) 2 10N*m

Specifications and Technical Data
Cable Size (Copper Wire Only)
Torque to Tighten Terminal Bus & Lug Body
Main Input (Single Input) 2/0 10 N*m
Main Input (Dual Input) 2/0 10 N*m
Bypass Input (Dual Input) 1/0 10 N*m
Output 1/0 10 N*m
Cable Size (Copper Wire Only)
Torque to Tighten Terminal Bus & Lug Body
Main Input (Single Input) 4/0 10 N*m
Main Input (Dual Input) 4/0 10 N*m
Bypass Input (Dual Input) 2/0 10 N*m
Output 2/0 10 N*m
Cable Size (Copper Wire Only)
Torque to Tighten Terminal Bus & Lug Body
Main Input (Single Input) 250 10 N*m
Main Input (Dual Input) 250 10 N*m
Bypass Input (Dual Input) 4/0 10 N*m
Output 4/0 10 N*m
Bus Type · Bus Type · Bus Type

Specifications and Technical Data
1 2 3 4
UPS12-150MR 13 33 53 75
UPS12-210MR 21 51 81 123
UPS12-100MR - 9 18 27
UPS12-150MR 7 19 33 47
UPS12-210MR 11 31 51 73
UPS12-100MR - 5 11 18
UPS12-150MR - 13 22 33
UPS12-210MR 6 21 36 51
UPS12-100MR - - 8 12
UPS12-150MR - 9 17 25
UPS12-210MR - 15 27 38
UPS12-100MR - - 5 9
UPS12-150MR - 7 13 19
UPS12-210MR - 11 21 31

Table 36 shows all event messages as they appear in the current status area of the LCD and in the history log, along with a description and recommended actions, if any. For further information on the current status area and the history log, see 2.11 UPS Status Messages.
Event Message Description / Suggested Action (if any)
Inverter Comm. Fail The RS-485 communication between internal monitor and inverter has failed. Contact Liebert Global Services at 800-543-2378 for assistance.
Rectifier Comm. Fail The RS-485 communication between internal monitor and rectifier fails. Contact Liebert Global Services at 800-543-2378 for assistance.
The CAN communication between different UPS units within a parallel system has failed. Check if there are some UPS units not powered on in the parallel system. If so, power on these UPS units and check if the alarm disappears. Press Fault Clear push button. If alarm does not clear, contact Liebert Global Services at 800-543-2378
Parallel Comm. Fail
Battery Overtemp. The battery temperature is over limit. Check the battery temperature and ventilation
Ambient Overtemp. The ambient temperature is over limit. Check the ventilation of UPS room.
Replace Battery Battery should be replaced. Contact Liebert Global Services at 800-543-2378 for assistance.
Before the end of discharging, battery under-voltage pre-warning should occur. After this pre- warning, battery should have the capacity for 3 minutes discharging with full load. The time is user configured from 3 to 60 minutes. Shut down the load in time to prevent damage to equipment and data.
Battery End of Discharge Inverter turned off due to low battery voltage. Check the utility failure and try to recover it.
Mains Volt. Abnormal Mains voltage exceeds the upper or lower limit and results in rectifier shutdown. Check the input line-to-line voltage amplitude of rectifier.
Mains Undervoltage Mains voltage is undervoltage 288V~384V line to line voltage with derated load. Check the input line-to-line voltage amplitude of rectifier.
Mains Freq. Abnormal Mains frequency is out of limit range and results in rectifier shutdown. Check the rectifier’s input voltage frequency
Rectifier Fault Contact Liebert Global Services at 800-543-2378 for assistance.
The temperature of rectifier inductor of rectifier common mode inductor is too high to keep the rectifier running. Check the ambient temperature and ventilation; contact Liebert Global Services at 800-543-2378 for assistance.
Input Inductor Overtemp.
Rectifier Overtemp. The temperature of the heat sink is too high to keep the rectifier running. The UPS can recover automatically. Check the environment and ventilation.
Charger Fault The charger has a fault. Contact Liebert Global Services at 800-543-2378 for assistance.
Control Power 1 Fail Control Power 1 has failed or has been lost. Contact Liebert Global Services at 800-543-2378 for assistance.
Mains Phase Reversed Input phase sequence is inverse. Contact Liebert Global Services at 800-543-2378 for assistance.
Rectifier Overcurrent The current of rectifier is over limit. Contact Liebert Global Services at 800-543-2378 for assistance.
Soft Start Fail Rectifier could not start due to low DC bus voltage. Contact Liebert Global Services at 800-543-2378 for assistance.
UPS Status Messages · Battery Low Pre-warning

Event Message Description / Suggested Action (if any)
This alarm is triggered by an inverter software routine when the amplitude or frequency of bypass voltage is beyond the normal range. The amplitude threshold is fixed for positive and negative 10% rating. This alarm automatically resets once the bypass voltage goes normal. First verify that the bypass voltage and frequency displayed on the panel is within the selected range. Note here the rated voltage and frequency are specified by “Output voltage level” and “Output frequency level” respectively. If the displayed voltage is believed to be abnormal, then verify the bypass voltage and frequency presented to the UPS. Check the external supply if it is found to be faulty. Contact Liebert Global Services at 800-543-2378 for assistance.
Bypass Unable to Trace
This alarm is triggered by an inverter software routine when the amplitude or frequency of bypass voltage exceeds the limit. This alarm automatically resets once the bypass voltage goes normal. First check whether there are relevant alarms such as “Bypass disconnect open,” “Bypass phase reverse” and “Mains neutral lost.” If they appear, solve them first. Then verify that the bypass voltage and frequency displayed on the panel is within the bypass limit. Note here the rated voltage and frequency are specified by “Output voltage level” and “Output frequency level” respectively. If the displayed voltage is believed to be abnormal, then verify the bypass voltage and frequency presented to the UPS. Check the external bypass supply if it is found to be faulty. If the utility is likely to trigger this alarm frequently, the bypass limit can be increased through the configuration software according to the customer’s agreement. Contact Liebert Global Services at 800-543-2378 for assistance.
This alarm is triggered by an inverter software routine when the inverter and bypass waveforms are misaligned by more than 6 degrees in phase. This alarm resets automatically once the condition clears. First check if the alarm “Bypass unable to trace” or “Bypass abnormal” occurs. If so, solve it first. Verify the waveform of the bypass voltage. Contact Liebert Global Services at 800-543-2378 for assistance.
Inverter Fault This alarm indicates a fault condition exists within the inverter. Contact Liebert Global Services at 800-543-2378 for assistance.
Output Voltage Abnormal This alarm indicates the inverter voltage waveform is abnormal. Contact Liebert Global Services at 800-543-2378 for assistance.
Input Current Abnormal This alarm indicates the rectifier input current is abnormal. Contact Liebert Global Services at 800-543-2378 for assistance.
The temperature of the inverter filter inductor or inverter common mode inductor is too high to keep inverter running. This alarm is triggered by the signal from a thermostat mounted in the inverter filter inductor. The UPS would recover automatically after a 5 minute delay from the disappearance of the overtemperature signal. If the overtemperature condition is true then check for and verify: High ambient air temperature. Blocked cooling airway Any fan failure Prolonged inverter overload. Contact Liebert Global Services at 800-543-2378 for assistance.
Inv. Inductor Overtemp.
The temperature of the inverter heat sink is too high to keep inverter running. This alarm is triggered by the signal from a temperature monitoring thermostat on the inverter bridge heat sink. The UPS will recover automatically after a 5 minute delay from the disappearance of the overtemperature signal. If the overtemperature condition is true then check for and verify: high ambient air temperature. blocked cooling airway. any fan failure. prolonged inverter overload. Contact Liebert Global Services at 800-543-2378 for assistance.
Inverter Overtemp.
Fan Fault At least one of the cooling fans has failed. Contact Liebert Global Services at 800-543-2378 for assistance.
UPS Status Messages · Bypass Abnormal · Inverter Asynchronous

Event Message Description / Suggested Action (if any)
Inverter STS Fail At least one of the static switches of inverter side is open or short circuit. This fault is locked until power off. Contact Liebert Global Services for assistance at 800-543-2378 for assistance.
At least one of the static switches of bypass side is open or short-circuited. This fault is locked until power off. Contact Liebert Global Services at 800-543-2378 for assistance.
Output Fuse Fail At least one of the output fuses is open. Contact Liebert Global Services at 800-543-2378 for assistance.
Control Power 2 Fail Control Power 2 is abnormal or lost. Contact Liebert Global Services at 800-543-2378 for assistance.
The UPS is overloaded when the load arises above 105% nominal rating. The alarm automatically resets once the overload condition is removed. Confirm that the alarm is true by checking the load percent indicated on the LCD panel to determine which phase is being overloaded. If the alarm is true, measure the actual output current to verify that the indications are valid. Disconnect unnecessary load. In a parallel system, a severe load sharing error can also lead to the alarm. Contact Liebert Global Services at 800-543-2378 for assistance.
The UPS parallel system is overloaded when the total load arises above 105% nominal rating for the set basic number of UPS units. The alarm resets automatically once the overload condition is removed. Confirm that the alarm is true by checking the system load percent indicated on the LCD panel to determine which phase is being overloaded. If the alarm is true, measure the actual output current to verify that the indications are valid. Disconnect unnecessary load and ensure the safety. In a parallel system, a severe load sharing error can also leads to the alarm.
The UPS is overloaded and the overload times out. Note 1: The highest loaded phase will indicate overload timing-out first. Note 2: When the timer is active then alarm “unit overload” should also be active as the load is above nominal. Note 3: When the timer has expired, the inverter Static Switch is opened and the load transferred to bypass. The inverter shutdown and will restart after 1 seconds. Note 4: If the load decreases lower than 95% after 5 minutes, the system will transfer back to inverter mode. Confirm that the alarm is genuine by checking the load percent indicated on the LCD. If an overload is indicated then check the load, and investigate any additional load connected prior to the alarm (if applicable).
Inverter Overcurrent The current of inverter IGBT is over limit. If the fault will not reset, contact Liebert Global Services at 800-543-2378 for assistance.
The phase sequence direction of bypass voltage is reversed. Normally, the phase of Phase B lags 120 degrees behind Phase A, and the phase of Phase C lags 120 degrees behind Phase B. Verify that the phase rotation of the bypass supply presented to the UPS is correct, and rectify it if it is found to be in error. Contact Liebert Global Services at 800-543-2378 for assistance.
Load Impact Transfer A transfer to bypass occurred due to a large step load. The UPS should recover automatically. Turn on connected equipment in sequential order to reduce the step loading of the inverter.
The load is on bypass power due to excessive number of transfers that occurred within the last hour. The UPS will recover automatically and will transfer the load back to inverter power within an hour.
Load Sharing Fault UPS units working within a parallel system are not sharing load current correctly. Contact Liebert Global Services at 800-543-2378 for assistance.
DC Bus Abnormal Shut off inverter due to abnormal DC bus voltage. Contact Liebert Global Services at 800-543-2378 for assistance.
System Transfer The whole paralleled UPS system transferred to bypass at the same time. This message will appear on the UPS which passive transfer to bypass.
Parallel Board Fault Parallel board is not working correctly. Contact Liebert Global Services at 800-543-2378 for assistance.

Event Message Description / Suggested Action (if any)
Rectifier, inverter and battery converter were shut down because DC bus voltage is too high. Check whether there is a fault in rectifier side. If not, check whether overload occurs. Restart the inverter after resetting the fault. If fault does not clear, contact Liebert Global Services at 800-543-2378 for assistance.
The parallel cables are not connected correctly in a parallel system. Reset the fault by pressing the Fault Clear button, then restart the inverter by pressing the Inverter On button. If the UPS does not resume normal operation, contact Liebert Global Services at 800-543-2378 for assistance.
Bypass current is over limit above 135% rating. The UPS just alarms and does nothing. Refer to your installation documentation or contact Liebert Global Services at 800-543-2378 for assistance.
LBS Active The LBS setting is active. The UPS is acting as an LBS master or slave in a dual bus configuration.
Battery ground fault Battery ground fault from dry contact signal. Contact Liebert Global Services at 800-543-2378 for assistance.
Inverter turned On manually
Manual Turn On via front panel
Inverter turned Off manually
Manual Turn Off via front panel
EPO Emergency Power Off
Transfer Confirm Interrupted Transfer Confirm
Transfer Cancel Interrupted Transfer is cancel
Unit Off Confirm Unit Turned Off Confirm
System Off Confirm Parallel System Turned Off Confirm
Fault Reset Fault Reset
Alarm Silence Alarm Silence
Turn On Fail Turn On Fail
Alarm Reset Audible Alarm Reset
Bypass Mode UPS in Bypass Mode
Normal Mode UPS in Normal Mode
Battery Mode UPS in Battery Mode
Check UPS output UPS Shutdown, output power-down
Output Disabled UPS Output Disabled
Generator Connected Generator is connected and a signal is sent to UPS
Input CB Open Input CB is Open
Input CB Closed Input CB is Closed
Bypass CB Open Bypass CB is Open
Bypass CB Closed Bypass CB is Closed
Output CB Open Output CB is Open
Output CB Closed Output CB is Closed
Maint. CB Open Maintenance CB is Open
Maint. CB Closed Maintenance CB is Closed
Battery Reverse Connect the battery again and check the wiring of batteries
No Battery Check the battery and the wiring of batteries
Auto start After the UPS was shut down at end of discharge, inverter auto starts when utility is restored
BCB closed BCB closed from dry contact signal
BCB open BCB open from dry contact signal

Event Message Description / Suggested Action (if any)
Battery Float Charging Battery is float charging
Battery Boost Charging Battery is boost charging
Battery Discharging Battery is discharging
Battery Period Testing Battery is period self-testing.
Batt. Capacity Testing Battery is capacity self-testing.
Batt. Maint. Testing Battery is maintenance self-testing.
UPS System Testing UPS System is testing
Inverter in Setting Inverter is in parameter setting
Rectifier in Setting Rectifier is in parameter setting
Balancer Fault Internal VDC (+) and VDC (-) offset by over 50V exceeding the inverter DC offset compensation capacity. Inverter shuts down. Load transfers to bypass.
Operation Invalid This record is registered following an incorrect operation.
Byp. Abnormal Shutdown Both bypass and inverter voltages unavailable. Load interruption
Setting Save Error History records not saved (Reserved)
Protocol version clash Firmware incompatibility between monitor board and digital signal processor board
MBP-T cabinet Fan Fault Maintenance bypass cabinet fans fault
Ext Input TX Overtemp External input isolation transformer overtemperature
Ext Output TX Overtemp External output isolation transformer overtemperature
Battery Room Alarm Environment in Battery Room Needs Attention
Rec Flash Update Rectifier firmware is being updated
Inv Flash Update Inverter firmware is being updated
Monitor Flash Update Monitor firmware is being updated
Input contactor fault Input contactor fault
LBS abnormal LBS is abnormal
DSP firmware error The inverter firmware is not compatible with the rectifier firmware.
Fan power fail Fan power has failed
Keyboard fault Keyboard has a fault. Check the cable between keyboard with U2 board. Contact Liebert Global Services at 800-543-2378 for assistance.
KVA Invalid An invalid kVA has been configured in unit.Contact Liebert Global Services at 800-543-2378 for assistance.
KVA updated The capacity updating is successful.
Output ground fault Output Line is shorted with ground
UPS Status Messages

UPS Status Messages



Ensuring The High Availability 0f Mission-Critical Data And Applications.
Emerson Network Power, the global leader in enabling business-critical continuity, ensures network resiliency and adaptability through a family of technologies—including Liebert power and cooling technologies—that protect and support business-critical systems. Liebert solutions employ an adaptive architecture that responds to changes in criticality, density and capacity. Enterprises benefit from greater IT system availability, operational flexibility and reduced capital equipment and operating costs.
Web Site www.liebert.com
Monitoring 800-222-5877 monitoring@emersonnetworkpower.com
800-222-5877 upstech@emersonnetworkpower.com
800-543-2378 powertech@emersonnetworkpower.com
800-543-2778 Outside the United States
614-888-0246 Locations United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229
Europe Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy +39 049 9719 111 Fax: +39 049 5841 257
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2007 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
Asia 7/F, Dah Sing Financial Centre 108 Gloucester Road, Wanchai Hong Kong 852 2572220 Fax: 852 28029250
Emerson Network Power. The global leader in enabling Business-Critical Continuity.
Embedded Computing Embedded Power Power Switching & Controls
Services Racks & Integrated Cabinets Outside Plant
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.
©2007 Emerson Electric Co.
Pages referenced in this manual — manufacturer, support and downloads.
Owners and our team usually reply within a day — and your question helps the next person too.
Be the first to ask — other owners or our team will answer.