SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during installation and mainte- nance of the UPS.
Read this manual thoroughly before attempting to install or operate this UPS.
The equipment can be installed and operated by individuals without previous training.
! CAUTION To reduce the risk of fire, connect PS3000RT3-120XR models only to a circuit provided with 30 amperes maximum branch circuit overcurrent protection in accordance with the National Electric Code, ANSI/NFPA 70. Other Liebert PSI models must be connected to a circuit with 20 amperes maximum branch circuit overcurrent protection.
! WARNING Operate the UPS only from a properly grounded (earthed) 110-127VAC, 50Hz or 60Hz AC supply. Some components are live, even when AC power is disconnected. For service, contact a properly trained and qualified technician. Do not remove the cover; the UPS has no user-serviceable parts inside except the internal battery pack.

CONDITIONS OF USE—The input supply outlet must be within 6 ft. (1.8m) of the UPS and be eas- ily accessed.
This UPS provides conditioned power to connected equipment. It is not intended for use with life-sup- port and other designated “critical” devices. Maximum load must not exceed that shown on the UPS rating label. If uncertain, consult your local dealer, local Emerson Network Power representative or Channel Support Applications.
When installing the UPS or making input and output connections, comply with all relevant safety codes and standards (e.g., UL 1778).
Placing magnetic storage media on top of the UPS may result in data corruption.
ELECTROMAGNETIC COMPATIBILITY—The Liebert PSI XR complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
This equipment uses, generates and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference with radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, the user is encouraged to try to correct the interference by one or more of the following measures:
Do not connect equipment that could overload the UPS or demand half-wave rectification from the UPS, such as electric drills, vacuum cleaners, laserjet printers and hair dryers.

Risk of electrical shock
Indicates caution followed by important instructions
Indicates the unit contains a valve-regulated, lead-acid battery
ON/Alarm Silence/Manual Self-Diagnostic Test

The Liebert PSI™ XR is a 2U, line-interactive UPS that may be installed in a rack or used as a tower UPS. Status indicators on the front of the Liebert PSI XR display load level, battery level, buck/boost, site- wiring fault, overload, battery status and UPS operation. Controls include a combination On/Alarm Silence/Manual Self-Diagnostic Test button, an Off button and a Status Change button. The Liebert PSI XR has USB, DB-9 (contact closure) and Liebert IntelliSlot® ports. The DB-9 and USB ports provide detailed operating information including voltages, currents, and alarm status to the host system when used in conjunction with Liebert MultiLink™ software. The Liebert PSI XR is compliant with the Restriction of Hazardous Substances Directive (ROHS), prohibiting use of six hazardous materials manufacturing of electronics, including lead-free solder.


Liebert PSI XR rack-mount configuration Display rotates for use as tower
Liebert PSI XR tower configuration Display rotates for use in rack
DB-9 Port (Contact Closure)
Input Circuit Breaker (12A for 1000VA; 15A for 1500VA)
Output Circuit Breaker (8A for 1000VA; 15A for 1500VA) Receptacles NEMA 5-15R

External Battery Cabinet Connector Voltage Configuration DIP Switch
Power Cord; 5-15P (not shown for clarity)

15A Output Circuit Breaker for Receptacles #3 & #4
Receptacles #3 and #4 NEMA 5-15R
Power Cord; 5-20P (not shown for clarity)

#5 and #6 NEMA 5-15R 30A Input Circuit Breaker
15A Output Circuit Breaker for Receptacles #5 & #6 20A Input Circuit Breaker Receptacles #1 and #2
Voltage Configuration DIP Switch
15A Output Circuit Breaker for Receptacles #3 & #4
Power Cord; L5-30P (not shown for clarity)

15A Output Circuit Breaker for Receptacles #5 & #6
Voltage Configuration DIP Switch
20A Output Circuit Breaker Receptacles #1 and #2
Introduction · Network Surge Protection

The Liebert PSI XR is shipped with the following items:


6 ft (1.8m)
6 ft (1.8m)

Mounting Hardware (Screws and Washers)


! CAUTION The UPS and battery cabinets are heavy (see Table 6 and Table 7). Take proper precautions when lifting or moving either the UPS or battery cabinets.
The Liebert PSI XR may be installed in either a tower or rack configuration. Determine the method that suits the application and proceed.
Decide where to install the Liebert PSI XR. The UPS must be installed indoors in a controlled envi- ronment. Place it in an area with unrestricted airflow around the unit, away from water, flammable liquids, gases, corrosives and conductive contaminants (see Figure 6).
Maintain a minimum clearance of 12 inches (305mm) in the front and rear of the UPS. Maintain an ambient temperature range of 32°F to 104°F (0°C to 40°C).
AIR
AIR
32 F (0 C)
104 F (40 C)
AIR
12 in./305mm
0% ~ 90%
Installation · Relative humidity (non-condensing)

See Figure 7 when using the Liebert PSI XR in a tower configuration.
Installation · Step 2 · Step 1

See Figure 8 when installing the Liebert PSI XR in a rack. External battery cabinets are installed in same manner.


! WARNING Placing heavy equipment near the top of a rack may increase the risk of tipping. Place the UPS, and battery cabinet if one is being used, in the bottom of the rack.
! CAUTION Lifting equipment into rack may be a two-person job, depending on weight of equipment.
When rack-mounted, the UPS must be supported by a shelf, slide rails, brackets or fixed rails on each side. The rack-mount handles WILL NOT support the weight of the UPS. They are used to move the UPS into and out of the rack.
Installation

The Liebert PSI XR features a rotating display that may be oriented for either tower or rack installations.
To set the display for your installation, pull out on the display and rotate it until it is oriented correctly, then press it into the UPS until it is seated.

Before connecting input power or connecting the load, Emerson recommends these steps:
Connect input power to the UPS, then plug the equipment into the outlets on the rear of the UPS. These UPS outlets provide battery backup and surge protection to the equipment when utility power fails, spikes or sags (see Figure 10).

Installation

Connect a 10 base-T/100 network cable to the network surge protection IN jack on the rear of the UPS. Connect from the OUT jack with network cabling to network equipment (see Figure 11).

Network surge protection IN Jack Network surge protection OUT jack
Determine what type of communication connection to use to manage the UPS. The Liebert PSI XR can be monitored with any of these communication methods:
Connect the appropriate, factory-supplied cable to the interface port on the rear of the UPS and to the computer interface port.
See 3.9 - Set Up Liebert MultiLink software for details and installation information. Also refer to 6.4 - UPS Communications.

Installation

To start using Liebert MultiLink (software and user manual available at multilink.liebert.com):
The Liebert PSI XR is equipped with an Emergency Power Off (EPO) switch. The user must supply a means of interfacing with the EPO circuit to allow disconnecting the UPS input feeder breaker to interrupt all sources of power to the UPS and connected equipment to comply with national and local wiring codes and regulations.

Short Pin 1 and Pin 2 to enable the EPO function
Installation · 2 = Ground

Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery run time. External battery cabinets are designed to be placed all on one side of the UPS or stacked beneath the UPS. The batteries have a maximum run time of three hours at full load.
Connect the top of the UPS to the top of the battery cabinet with the Battery UPS Tab and hardware
If two or more battery cabinets are used in a tower setup, the tower stand must be extended with the spacers included with each battery cabinet.
Connect tower stand and set the UPS and battery cabinet in them; check to ensure stability
External battery cabinet power connectors are color-coded as noted in Table 1. Do not try to install external battery cabinets with connectors that are a different color from the battery connector on the UPS.
UPS Model Nominal System Voltage (connector color) External Battery Cabine Model
PS1000RT3-120XR PS1000RT3120XRW 24VDC (Red) PSRT3-24VBXR PS1500RT3-120XR PS1500RT3120XRW
PS2200RT3-120XR PS2200RT3120XRW 48VDC (Gray) PSRT3-48VBXR PS3000RT3-120XR PS3000RT3120XRW
Installation


See Table 8 for approximate battery run times.
Installation

Buttons on the front panel display control the Liebert PSI XR. Eight LEDs indicate the UPS’s status. Refer to Figure 16 and Table 2.
1 2 3 4 5
Load Level Battery Level
6 7 8 9 10 11
Item Name Status Indicators Description
1 LED 1 AVR Boost UPS Operation in AVR Boost Mode
2 LED 2 AVR Buck UPS Operation in AVR Buck Mode
3 LED 3 Battery Condition Battery Fault/Weak
4 LED 4 Grounding/Site Wiring Fault UPS Grounding/Site Wiring Fault
5 LED 5 Overload UPS Overload
1 to 5 Load/Battery Level Indicate Load/Battery Level
6 Status Change Button Switches Display from Load Level Indicators to Battery Level Indicators
7 OFF Button UPS Off
8 ON Button Turn on UPS, Manual Self-Diagnostic (Normal Mode), Silence Alarm (Battery Mode)
9 LED 9 Normal Mode UPS Operation in Normal Mode
10 LED 10 Battery Mode UPS Operation in Battery Mode
11 LED 11 UPS Fault UPS Fault
Controls and Indicators

This button controls output power to connected load(s). It has three functions:
ON—Start the UPS by pressing this button for more than 3 seconds, then releasing the button (an alarm will sound briefly). If the ON button is pressed and utility is outside input parameters, the UPS will start on battery (dark start).
Alarm Silence—Silence a battery mode audible alarm by pressing this button for longer than one second, then releasing it.
Manual Self-Diagnostic Test—To initiate a Manual Self-Diagnostic, press this button for at least three (3) seconds while operating from utility power. UPS will switch to Battery Mode to detect bat- tery voltage and whether the UPS is operating normally.
If LED indicates the battery is weak: Allow the UPS to recharge the batteries for 8 hours. Retest the battery after recharge.
If LED still indicates the battery is weak after the battery has been retested, contact your local dealer, local Emerson representative or Channel Support Applications. If LED indicates a Battery Fault: Contact your local dealer, local Emerson representative or Channel Support Applications. If LED indicates a UPS Fault: Remove the load, retest the self diagnostic test, if LED indicated UPS Fault, Contact your local dealer, local Emerson representative or Channel Support Applica- tions.
When the UPS is operating in either Normal Mode or Battery Mode, pressing the Off button for more than three seconds will shut down the UPS.
The Status Change button determines the information displayed by the five LEDs on the front panel. The default information shown by the LEDs is the load level on the UPS. Pressing the Status Change button while the UPS is On prompts the LED display to show battery capacity for 5 seconds. This function assists in assessing the meaning of status indicators as described in 4.2.4 - UPS Status Indicators. See Figure 16 and Table 2 for the Status Change button’s location.
The five LEDs at the top of the front panel illuminate with a steady glow to indicate the load level on the output of the UPS. The LEDs show the load level as a range, ± 5%. The LEDs’ load level meanings and colors are:
LED 1 LED 2 LED 3 LED 4 LED 5
10-24% — Green 25-49% — Green 50-74% — Yellow 75-99% — Yellow 100% or greater — Red
Controls and Indicators

The five LEDs illuminate with a steady glow to indicate battery capacity. Battery capacity is shown for five seconds after the Status Change button is pressed. The LEDs show the battery capacity as a range, ± 5% The LEDs’ battery level meanings and colors are:
LED 1 LED 2 LED 3 LED 4 LED 5
100-76% — Green 75-51% — Green 50-26% — Yellow 25-11% — Yellow 10% or less — Red
LEDs on the display panel illuminate with a steady glow or flash to indicate the UPS’s status:
Normal Mode—The Normal Mode indicator illuminates (LED 9) with a steady glow when utility power is available and within the input specifications.
Battery Mode—The Battery Indicator illuminates (LED 10) with a steady glow when the UPS is operating on battery
AVR Boost, AVR Buck—When the UPS is in AVR Boost/Buck Mode, the LED display will indicate the relative load level on the output of the UPS and will flash LED 1 (boost) or LED 2 (buck) to indi- cate which mode the UPS is in.
Weak Battery—When the UPS battery voltage is low, the LED display will indicate the relative load level on the output of the UPS and LED 3 will flash as a warning.
Site-Wiring Fault—In case of a site-wiring fault, the LED display will indicate the relative load level on the output of the UPS and LED 4 will flash as a warning.
Overload—When UPS operates in overload status, the LED display will indicate the relative load level on the output of the UPS and LED 5 will flash as a warning.
Status LED 1 LED 2 LED 3 LED 4 LED 5 LED 9 LED 10 LED 11
Normal Mode Green Steady
AVR Boost Green Flashes
AVR Buck Green Flashes
Battery Mode (dark start)
Weak Battery Yellow Flashes
Site-Wiring Fault Yellow Flashes
UPS Output Abnormal Shutdown

When the UPS is in Normal Mode, the Normal Mode Indicator illuminates green.
The Automatic Voltage Regulator (AVR) circuitry compensates for fluctuations in utility power, such as voltage surges and sags. When the Liebert PSI XR detects an abnormality, it raises the undervolt- age (boost) or lowers the overvoltage (buck) as needed. The AVR operates automatically and main- tains the output voltage to the connected equipment, without utilizing the batteries.
LED 1 flashes green and LED 9 illuminates steady green when the UPS is in Boost Mode. LED 2 flashes green and LED 9 illuminates steady green when the UPS is in Buck Mode (see 9.0 - Trouble- shooting for details).
The UPS switches to Battery Mode in the event of an extreme input voltage/frequency condition or utility failure.
When the UPS is in Battery Mode, the Battery Indicator illuminates amber and an alarm sounds at two-second intervals. As capacity decreases, fewer indicators remain illuminated.
When a Low Battery condition occurs, the Battery Indicator flashes amber and an alarm sounds at one-second intervals. Refer to Table 8 for approximate battery run times.
Once utility power is restored, the UPS resumes normal operation and the Battery Charger begins recharging the batteries.
Operational Modes

The UPS has a DB-9 (9 pin female) connector on the rear to allow UPS status communications with a computer running Liebert MultiLink software in contact closure mode. The connection provides On Battery and Low Battery notification.
When power is interrupted and battery power is low, Liebert MultiLink software can signal the host computer to gracefully shut down the operating system.
DB-9 Pin Assignment Description
1 Low Battery (open collector)
2 UPS TxD (not used)
3 UPS RxD (not used)
4 Remote Shutdown (5-12V); on-battery operation
6 Output Off, (short to Pin 5, non-latching); any mode operation
7 Low Battery (open emitter)
8 Utility Fail (open emitter)
9 Utility Fail (open collector)





6 7 8 9
5 4 3 2 1
The Liebert PSI XR can be shut down remotely by shorting Pins 5 and 6 or via Pins 4 and 5 of the DB- 9 connector.
When Pin 6 is shorted to Pin 5, the UPS output is shut Off no matter what mode the UPS is operating in. The UPS cannot be started as long as the pins are shorted. When the short is removed, the UPS output can be enabled by pressing the ON/Alarm Silence/Manual Self-Diagnostic Test button.
While the UPS is operating on battery, a 5-12VDC signal for 2 seconds or longer is required to signal a shutdown. Signals for less than 2 seconds are ignored.
After Pin 4 receives the shutdown signal, a 2-minute shutdown timer begins a countdown. The shut- down timer cannot be stopped: If utility power returns during the 2-minute countdown, the shutdown timer continues until the end of 2 minutes and the UPS turns Off. The UPS will restart 10 seconds after utility power returns.
Network (in and out) connectors on the rear of the UPS provide transient voltage surge suppression (TVSS) for network devices.

The Liebert PSI XR is equipped with a Liebert IntelliSlot port to provide advanced communication and monitoring options.
Liebert MultiLink software continually monitors the UPS and can shut down your computer or server via USB, contact closure and SNMP (via IS-WEBRT3 card) in the event of an extended power failure.
The Liebert IS-WEBRT3 provides SNMP and Web-based monitoring and control of the UPS across the network.
A two-pin DIP switch on the rear of the PSI XR permits setting the UPS to operate at nominal volt- ages of 110V, 120V or 127V. This feature will change the high and low points at which the UPS switches to battery power. It also changes the UPS’ output voltage when the UPS is operating in bat- tery mode. The factory default setting is 120 VAC.
Turn Off the UPS before making any changes to the voltage configuration.
FUNCTION 2 1
ON
Table 5 Voltage configurations


The batteries are valve-regulated, nonspillable, lead acid and must be kept charged to retain their design life. The Liebert PSI XR continuously charges the batteries when connected to the utility sup- ply, even while the UPS is switched Off.
If the Liebert PSI XR will be stored for an extended period, Emerson recommends connecting the UPS to input power for at least 8 hours every four to six months to keep the batteries charged.
Emerson recommends performing a monthly manual self-diagnostic test via the Web card or the front panel display.
NOTICE
This UPS is equipped with internal batteries that the user can replace without shutting down the UPS or connected loads (hot swappable). Caution must be exercised when replacing the batteries because the load is unprotected from power fluctuations and power failures.
To replace the batteries:
1. Remove the two screws on the left side of the front bezel. 2. Pull the front bezel off the UPS. 3. Remove the screw on the battery connector holder. 4. Remove the two screws on the battery bracket. 5. Disconnect the two slotted, red/gray and black battery connectors. 6. Grasp the battery pack assembly by the handle and pull it out of the front of the UPS. 7. Unpack the new battery assembly, taking care not to destroy the packing. 8. Compare the new and old battery assemblies to make sure they are the same. If so, proceed with replacement. If they are different, STOP and contact your local dealer, local Emerson representative or Channel Support Applications. 9. Slide the new battery pack into the UPS. 10. Reattach the battery bracket with the two screws. 11. Reconnect the slotted, red/gray and black battery connectors. 12. Reinsert the screw on the battery connector holder. 13. Reattach the front bezel.
Step 1 Step 2


Step 3 Step 4


Battery Maintenance

PS3000RT3-120XR PS3000RT3120XRW Power Rating, VA/W 1000VA/900W 1500VA/1350W 1920VA/1920W* 3000VA/2700W Dimensions, W x D x H, in (mm)
Model Number PS1000RT3-120XR PS1000RT3120XRW
PS2200RT3-120XR PS2200RT3120XRW
Unit 17.3 x 19.3 x 3.5 (440 x 490.5 x 88) 17.3 x 27.6 x 3.5 (440 x 700.5 x 88) Shipping 22 x 24.1 x 9 (560 x 612 x 228) 22 x 34.8 x 9.0 (560 x 884 x 228) Weight, lb (kg)
Unit 56 (25) 62 (28) 92 (42) 105 (48) Shipping 64 (29) 70 (32) 101 (46) 115 (52) Input AC Parameters
Surge Protection 570J Voltage Range Without Battery Operation 83-159 VAC (configurable)
Frequency Range 45~65Hz, (±0.5Hz) Input Power Cord, 10ft (3m) attached NEMA 5-15P plug NEMA 5-20P plug NEMA L5-30P plug
(4) NEMA 5-15R (2) NEMA 5-20R T-Slot,
(4) NEMA 5-15R (2) NEMA 5-20R T-Slot,
Output Receptacles (6) NEMA 5-15R
accepts15A Plug (1) NEMA L5-30R Voltage (Normal Mode) 110/120/127 VAC (configurable) Voltage (Battery Mode) 110/120/127 VAC; ±5% before low-battery warning Transfer Time 4-6 ms typical Waveform Sinewave Battery Parameters
Type Valve-regulated, nonspillable, lead acid Quantity x Voltage x Ah 4 x 12 x 7.2 4 x 12 x 9 8 x 12 x 7.2 8 x 12 x 9 Recharge Time 5 hours to 90% of rated capacity, after full discharge into resistive load Battery Backup Time
Full Load 5 minutes Half Load 10 minutes Environmental
Operating Temperature, °F (°C) 32 to 104 (0 to 40) Storage Temperature, °F (°C) 5 to 104 (-15 to 40) Relative Humidity 0% to 90%, non-condensing Operating Altitude Up to 10,000 ft (3000m) Audible Noise
Safety UL 1778, c-UL Listed Surge ANSI C62.41 CatA Lev3 (surges) IEC61000-4-5 ESD IEC61000-4-2 Susceptibility IEC61000-4-3 Electrical Fast Transient IEC61000-4-4 Emissions FCC Part 15, Class A Conducted Immunity IEC61000-4-6 Harmonics IEC61000-3-2 Network surge UL 497 B Transportation ISTA Procedure 1A Certification
* NEC limits the input current rating of the PS2200RT3-120XR and PS2200RT3120XRW models to 80% of the input plug's rating. Up to 2200VA/1980W is available by contacting a certified electrician to change the input plug to 30A plug. Emerson Network Power assumes no liability for damage caused by miswiring or misapplication of the input plug.

Model Number PSRT3-24VBXR PSRT3-48VBXR
PS2200RT3-120XR PS2200RT3120XRW
PS1500RT3-120XR PS1500RT3120XRW
PS3000RT3-120XR PS3000RT3120XRW
Dimensions, W x D x H, in (mm)
Unit 17.3 x 19.3 x 3.5 (440 x 490.5 x 88)
Shipping 22 x 26.6 x 9 (560 x 675 x 228)
Type Valve-regulated, nonspillable, lead acid
Quantity x Voltage x Ah 8 x 12 x 7.2 8 x 12 x 7.2
Manufacturer CSB, YUASA or Equivalent
Operating Temperature, °F (°C) 32 to 104 (0 to 40)
Storage Temperature, °F (°C) 5 to 104 (-15 to 40)
Relative Humidity 0% to 90%, non-condensing
Maximum Operating Altitude 10,000 ft. (3000m)
Safety UL 1778, c-UL Listed
Emissions FCC Part 15, Class A
Transportation ISTA Procedure 1A Certification

Number of Batteries Load % 1000 1500 2200 3000
10 83 82 76 75
20 52 48 48 47
30 31 28 28 28
40 18 17 17 17
50 15 13 14 13
60 12 11 11 11
70 11 9 9 9
80 9 7 8 7
90 7 6 7 6
100 6 5 5 5
10 263 222 161 143
20 165 131 101 83
30 120 93 69 60
40 95 68 55 47
Internal battery + 1 External Battery Cabinets
50 73 56 45 32
60 62 47 31 27
70 54 33 27 18
80 48 29 18 16
90 43 26 17 14
100 32 18 15 12
10 439 357 242 205
20 275 212 152 127
30 200 150 111 92
40 157 116 82 68
Internal battery + 2 External Battery Cabinets
50 129 95 68 56
60 110 76 57 47
70 96 65 50 33
80 80 58 44 30
90 71 52 32 26
100 65 47 29 18
10 614 492 322 267
20 385 291 202 166
30 280 207 147 120
40 220 160 116 94
Internal battery + 3 External Battery Cabinets
50 181 131 96 73
60 154 111 77 62
70 134 95 67 54
80 119 79 59 47
90 106 71 53 43
100 96 64 48 31
Run times are in minutes, assume fully charged batteries and are typical at 77°F (25°C) with resistive loads.
Specifications · Internal Battery

Number of Batteries Load % 1000 1500 2200 3000
10 790 627 483 330
20 494 371 303 204
30 360 264 221 148
40 283 204 174 116
Internal battery + 4 External Battery Cabinets
50 233 167 143 95
60 198 141 122 76
70 172 122 106 66
80 152 108 94 59
90 137 96 79 52
100 124 82 72 48
10 965 762 564 392
20 605 452 354 243
30 440 320 258 176
40 346 248 203 138
Internal battery + 5 External Battery Cabinets
50 265 203 167 113
60 242 171 142 96
70 211 148 124 79
80 186 131 110 70
90 167 117 98 62
100 151 106 84 56
10 1140 897 644 454
20 714 531 405 281
30 520 377 295 204
40 408 292 232 160
Internal battery + 6 External Battery Cabinets
50 337 239 191 131
60 286 202 163 112
70 249 175 142 97
80 220 154 125 81
90 197 138 112 72
100 179 124 102 65
Run times are in minutes, assume fully charged batteries and are typical at 77°F (25°C) with resistive loads.
Specifications

The information below indicates various symptoms a user may encounter if the Liebert PSI XR expe- riences a problem. See Table 9 for suggested solutions. 1. An alarm sounds, alerting that the UPS requires attention. The alarm can be silenced except for low battery, overload warning and fault. 2. One or more additional indicators will be illuminated to provide a diagnostic aid to the operator, as described below: If the UPS fails to operate properly, turn Off the unit and repeat the steps in 3.0 - Installation. If the problem persists, refer to Table 9.
Problem Cause Solution
Check the circuit breaker on the rear of the UPS. If it is tripped, reset it and restart the UPS. For help, contact your local dealer, local Emerson representative or Channel Support Applications. Battery is disconnected or completely discharged
UPS will not start
Check for proper connection of battery or batteries.
UPS not plugged in Plug in the power cord securely.
Circuit breaker tripped Reset the circuit breaker and restart the UPS.
UPS starts on battery, but will not switch to AC (dark start)
Wait until voltage drops to an appropriate level or have the utility power checked by a properly trained and qualified electrician.
Remove the load and turn on the UPS again. For help, contact your local dealer, local Emerson representative or Channel Support Applications.
Short circuit or UPS output is abnormal; LED 10 and LED 11 illuminate and sound audible alarm
Check load level display and remove nonessential loads. Recalculate the load and reduce equipment connected to UPS - the total wattage must not exceed the capacity of the UPS. LED 3 and LED 11 illuminate and sound audible alarm
Overload; LED 5 and LED 11 illuminate and sound audible alarm
Recharge the battery for 8 hours, then turn ON the UPS.
Consult the Liebert MultiLink user manual or contact your LAN administrator.
Site Wiring Fault, UPS detected a line-to-neutral reversal or a loss of proper grounding.
Have the utility checked by a properly trained and qualified electrician.
Site Wiring Fault LED (LED 4) flashing
Battery weak LED (LED 3) flashing Batteries weak Recharge batteries. Batteries need to be replaced Replace batteries.



Ensuring The High Availability Of Mission-Critical Data And Applications.
Emerson Network Power, the global leader in enabling business-critical continuity, ensures network resiliency and adaptability through a family of technologies—including Liebert power and cooling technologies—that protect and support business-critical systems. Liebert solutions employ an adaptive architecture that responds to changes in criticality, density and capacity. Enterprises benefit from greater IT system availability, operational flexibility and reduced capital equipment and operating costs.
Web Site www.liebert.com
Monitoring 800-222-5877 Liebert.monitoring@emerson.com
800-222-5877 upstech@emersonnetworkpower.com
800-543-2378 powertech@emersonnetworkpower.com
800-543-2778 Outside the United States
614-888-0246 Locations United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229
Europe Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy +39 049 9719 111 Fax: +39 049 5841 257
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2008 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
Asia 7/F Dah Sing Financial Centre 108 Gloucester Road Wanchai Hong Kong 852 2572 2201 Fax: 852 2519 9210
Emerson Network Power. The global leader in enabling Business-Critical Continuity.
Embedded Computing Embedded Power Power Switching & Controls
Services Racks & Integrated Cabinets Outside Plant
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.
©2008 Emerson Electric Co.
Pages referenced in this manual — manufacturer, support and downloads.
Common problems, likely causes, and what to do.
| Problem | Possible cause | Remedy | |
|---|---|---|---|
| UPS will not start | Short circuit | Check the circuit breaker on the rear of the UPS. If it is tripped, reset it and restart the UPS. For help, contact your local dealer, local Emerson representative or Channel Support Applications. | p.30 |
| UPS will not start | Battery is disconnected or completely discharged | Check for proper connection of battery or batteries. | p.30 |
| UPS starts on battery, but will not switch to AC (dark start) | UPS not plugged in | Plug in the power cord securely. | p.30 |
| UPS starts on battery, but will not switch to AC (dark start) | Circuit breaker tripped | Reset the circuit breaker and restart the UPS. | p.30 |
| UPS starts on battery, but will not switch to AC (dark start) | AC overvoltage | Wait until voltage drops to an appropriate level or have the utility power checked by a properly trained and qualified electrician. | p.30 |
| UPS shuts down | Short circuit or UPS output is abnormal; LED 10 and LED 11 illuminate and sound audible alarm | Remove the load and turn on the UPS again. For help, contact your local dealer, local Emerson representative or Channel Support Applications. | p.30 |
| UPS shuts down | Overload; LED 5 and LED 11 illuminate and sound audible alarm | Check load level display and remove nonessential loads. Recalculate the load and reduce equipment connected to UPS - the total wattage must not exceed the capacity of the UPS. | p.30 |
| UPS shuts down | LED 3 and LED 11 illuminate and sound audible alarm | Recharge the battery for 8 hours, then turn ON the UPS. | p.30 |
| UPS shuts down | Liebert MultiLink software | Consult the Liebert MultiLink user manual or contact your LAN administrator. | p.30 |
| Site Wiring Fault LED (LED 4) flashing | Site Wiring Fault, UPS detected a line-to-neutral reversal or a loss of proper grounding. | Have the utility checked by a properly trained and qualified electrician. | p.30 |
| Battery weak LED (LED 3) flashing | Batteries weak | Recharge batteries. | p.30 |
| Battery weak LED (LED 3) flashing | Batteries need to be replaced | Replace batteries. | p.30 |