Emerson 2200

32 pages·1.6 MB·Power Supply·PDF·ENDEFRITNLJA
Emerson 2200
Table of Contents 73 sections Important Safety Instructions · SAVE THESE INSTRUCTIONS · Size of Branch Circuit Overcurrent Protection · Battery Handling Precautions · … ShowHide
Important Safety Instructionsp.5SAVE THESE INSTRUCTIONSp.5Size of Branch Circuit Overcurrent Protectionp.5Battery Handling Precautionsp.5Glossary of Symbolsp.71.0 Introductionp.8Figure 1 Front view of UPSp.8Figure 2 1000 and 1500—rear viewp.8Figure 3 2200—rear viewp.9Figure 4 3000—rear viewp.92.0 What’s Includedp.10Figure 5 Accessoriesp.103.0 Installationp.113.1 Preparationp.11Figure 6 Placing the Liebert PSI XRp.113.2 Tower UPS Installationp.12Figure 7 Tower configuration—attach Tower Standsp.123.3 Rack-Mount UPS Conversion and Installationp.13Figure 8 Convert the Liebert PSI XR for rack installationp.133.4 Orient Display for Installationp.14Figure 9 Orienting the UPS displayp.143.5 Charge Batteries and Perform Battery Startupp.143.6 Connect Input Power and Loadp.14Figure 10 Connect input power and loadp.143.7 Connect Network Surge protectionp.15Figure 11 Connect network surge protectionp.153.8 Connect Communication Interfacep.15Figure 12 Connect communication interfacep.153.9 Set Up Liebert MultiLink softwarep.163.10 EPO Switchp.16Figure 13 EPO connection for normally open operationp.163.11 External Battery Cabinet Installationp.17Figure 14 Install the external battery cabinet in tower installationp.17Table 1 Battery cabinet connector color keyp.17Figure 15 Connect battery cabinets to UPSp.184.0 Controls and Indicatorsp.19Figure 16 Display and status indicatorsp.19Table 2 Display and status indicators function, legendp.194.1 Control Buttonsp.204.1.1 On/Alarm Silence/Manual Self-Diagnostic Testp.204.1.2 Off Buttonp.204.2 Status Indicatorsp.204.2.1 Status Change Buttonp.204.2.2 Load Level Indicatorp.204.2.3 Battery Level Indicatorp.214.2.4 UPS Status Indicatorsp.21Table 3 Status indicators—color, illumination modep.215.0 Operational Modesp.225.1 Normal Modep.225.2 Buck/Boost Modep.225.3 Battery Modep.225.4 Battery Recharge Operationp.226.0 Communicationp.236.1 DB-9 Connectorp.23Table 4 DB-9 pin assignmentp.236.2 Remote Shutdown Via the DB-9 Connectorp.236.2.1 Any Mode Shutdown Via Pins 5 & 6p.236.2.2 Battery Mode Shutdown Via Pins 4 & 5p.236.3 Network Surge Protection Connectorsp.236.4 UPS Communicationsp.246.5 UPS Inverter/Transfer Voltage Configurationsp.24Figure 17 DIP switch settings for 120V systemp.24Table 5 Voltage configurationsp.247.0 Battery Maintenancep.257.1 Battery Charging, Storagep.257.2 Internal Battery Replacement Procedurep.25Figure 18 Battery replacementp.258.0 Specificationsp.26Table 6 Liebert PSI XR specificationsp.26Table 7 Battery cabinet specificationsp.27Table 8 Liebert PSI XR battery run timesp.289.0 Troubleshootingp.30Table 9 Troubleshooting—problems, causes and solutionsp.30
Page 1 of the Emerson 2200 user manual
Page 1 · click to enlarge
Page 1
Emerson 2200 diagram (page 1)
Fig. 1
Page 2 of the Emerson 2200 user manual
Page 2 · click to enlarge
Page 2
Page 2 of the Emerson 2200 user manual
Page 3 of the Emerson 2200 user manual — Table of contents
Page 3 · click to enlarge
Page 3

Table of contents

Important Safety Instructionsp.5SAVE THESE INSTRUCTIONSp.5Size of Branch Circuit Overcurrent Protectionp.5Battery Handling Precautionsp.5Glossary of Symbolsp.71.0 Introductionp.8Figure 1 Front view of UPSp.8Figure 2 1000 and 1500—rear viewp.8Figure 3 2200—rear viewp.9Figure 4 3000—rear viewp.92.0 What’s Includedp.10Figure 5 Accessoriesp.103.0 Installationp.113.1 Preparationp.11Figure 6 Placing the Liebert PSI XRp.113.2 Tower UPS Installationp.12Figure 7 Tower configuration—attach Tower Standsp.123.3 Rack-Mount UPS Conversion and Installationp.13Figure 8 Convert the Liebert PSI XR for rack installationp.133.4 Orient Display for Installationp.14Figure 9 Orienting the UPS displayp.143.5 Charge Batteries and Perform Battery Startupp.143.6 Connect Input Power and Loadp.14Figure 10 Connect input power and loadp.143.7 Connect Network Surge protectionp.15Figure 11 Connect network surge protectionp.153.8 Connect Communication Interfacep.15Figure 12 Connect communication interfacep.153.9 Set Up Liebert MultiLink softwarep.163.10 EPO Switchp.16Figure 13 EPO connection for normally open operationp.163.11 External Battery Cabinet Installationp.17Figure 14 Install the external battery cabinet in tower installationp.17Table 1 Battery cabinet connector color keyp.17Figure 15 Connect battery cabinets to UPSp.184.0 Controls and Indicatorsp.19Figure 16 Display and status indicatorsp.19Table 2 Display and status indicators function, legendp.194.1 Control Buttonsp.204.1.1 On/Alarm Silence/Manual Self-Diagnostic Testp.204.1.2 Off Buttonp.204.2 Status Indicatorsp.204.2.1 Status Change Buttonp.204.2.2 Load Level Indicatorp.204.2.3 Battery Level Indicatorp.214.2.4 UPS Status Indicatorsp.21Table 3 Status indicators—color, illumination modep.215.0 Operational Modesp.225.1 Normal Modep.225.2 Buck/Boost Modep.225.3 Battery Modep.225.4 Battery Recharge Operationp.226.0 Communicationp.236.1 DB-9 Connectorp.23Table 4 DB-9 pin assignmentp.236.2 Remote Shutdown Via the DB-9 Connectorp.236.2.1 Any Mode Shutdown Via Pins 5 & 6p.236.2.2 Battery Mode Shutdown Via Pins 4 & 5p.236.3 Network Surge Protection Connectorsp.236.4 UPS Communicationsp.246.5 UPS Inverter/Transfer Voltage Configurationsp.24Figure 17 DIP switch settings for 120V systemp.24Table 5 Voltage configurationsp.247.0 Battery Maintenancep.257.1 Battery Charging, Storagep.257.2 Internal Battery Replacement Procedurep.25Figure 18 Battery replacementp.258.0 Specificationsp.26Table 6 Liebert PSI XR specificationsp.26Table 7 Battery cabinet specificationsp.27Table 8 Liebert PSI XR battery run timesp.289.0 Troubleshootingp.30Table 9 Troubleshooting—problems, causes and solutionsp.30
Page 4 of the Emerson 2200 user manual — Table of contents
Page 4 · click to enlarge
Page 4

Table of contents

Important Safety Instructionsp.5SAVE THESE INSTRUCTIONSp.5Size of Branch Circuit Overcurrent Protectionp.5Battery Handling Precautionsp.5Glossary of Symbolsp.71.0 Introductionp.8Figure 1 Front view of UPSp.8Figure 2 1000 and 1500—rear viewp.8Figure 3 2200—rear viewp.9Figure 4 3000—rear viewp.92.0 What’s Includedp.10Figure 5 Accessoriesp.103.0 Installationp.113.1 Preparationp.11Figure 6 Placing the Liebert PSI XRp.113.2 Tower UPS Installationp.12Figure 7 Tower configuration—attach Tower Standsp.123.3 Rack-Mount UPS Conversion and Installationp.13Figure 8 Convert the Liebert PSI XR for rack installationp.133.4 Orient Display for Installationp.14Figure 9 Orienting the UPS displayp.143.5 Charge Batteries and Perform Battery Startupp.143.6 Connect Input Power and Loadp.14Figure 10 Connect input power and loadp.143.7 Connect Network Surge protectionp.15Figure 11 Connect network surge protectionp.153.8 Connect Communication Interfacep.15Figure 12 Connect communication interfacep.153.9 Set Up Liebert MultiLink softwarep.163.10 EPO Switchp.16Figure 13 EPO connection for normally open operationp.163.11 External Battery Cabinet Installationp.17Figure 14 Install the external battery cabinet in tower installationp.17Table 1 Battery cabinet connector color keyp.17Figure 15 Connect battery cabinets to UPSp.184.0 Controls and Indicatorsp.19Figure 16 Display and status indicatorsp.19Table 2 Display and status indicators function, legendp.194.1 Control Buttonsp.204.1.1 On/Alarm Silence/Manual Self-Diagnostic Testp.204.1.2 Off Buttonp.204.2 Status Indicatorsp.204.2.1 Status Change Buttonp.204.2.2 Load Level Indicatorp.204.2.3 Battery Level Indicatorp.214.2.4 UPS Status Indicatorsp.21Table 3 Status indicators—color, illumination modep.215.0 Operational Modesp.225.1 Normal Modep.225.2 Buck/Boost Modep.225.3 Battery Modep.225.4 Battery Recharge Operationp.226.0 Communicationp.236.1 DB-9 Connectorp.23Table 4 DB-9 pin assignmentp.236.2 Remote Shutdown Via the DB-9 Connectorp.236.2.1 Any Mode Shutdown Via Pins 5 & 6p.236.2.2 Battery Mode Shutdown Via Pins 4 & 5p.236.3 Network Surge Protection Connectorsp.236.4 UPS Communicationsp.246.5 UPS Inverter/Transfer Voltage Configurationsp.24Figure 17 DIP switch settings for 120V systemp.24Table 5 Voltage configurationsp.247.0 Battery Maintenancep.257.1 Battery Charging, Storagep.257.2 Internal Battery Replacement Procedurep.25Figure 18 Battery replacementp.258.0 Specificationsp.26Table 6 Liebert PSI XR specificationsp.26Table 7 Battery cabinet specificationsp.27Table 8 Liebert PSI XR battery run timesp.289.0 Troubleshootingp.30Table 9 Troubleshooting—problems, causes and solutionsp.30
Page 5 of the Emerson 2200 user manual — Battery Handling Precautions
Page 5 · click to enlarge
Page 5

I MPORTANT S AFETY I NSTRUCTIONS

SAVE THESE INSTRUCTIONS

This manual contains important instructions that should be followed during installation and mainte- nance of the UPS.

  • Intended for installation in a temperature-controlled, indoor area free of conductive contaminants.
  • Maximum ambient temperature 104°F (40°C).

Read this manual thoroughly before attempting to install or operate this UPS.

The equipment can be installed and operated by individuals without previous training.

Size of Branch Circuit Overcurrent Protection

! CAUTION To reduce the risk of fire, connect PS3000RT3-120XR models only to a circuit provided with 30 amperes maximum branch circuit overcurrent protection in accordance with the National Electric Code, ANSI/NFPA 70. Other Liebert PSI models must be connected to a circuit with 20 amperes maximum branch circuit overcurrent protection.

! WARNING Operate the UPS only from a properly grounded (earthed) 110-127VAC, 50Hz or 60Hz AC supply. Some components are live, even when AC power is disconnected. For service, contact a properly trained and qualified technician. Do not remove the cover; the UPS has no user-serviceable parts inside except the internal battery pack.

  • ! WARNING Although the UPS has been designed and manufactured to ensure personal safety, improper use can result in electrical shock or fire. To ensure safety, observe the following rules:
  • Turn Off and unplug the UPS before cleaning it. Clean the UPS with a dry cloth. Do not use liquid or aerosol cleaners.
  • Do not install or operate the UPS in or near water.
  • Never block or insert any objects into the ventilation holes or other openings of the UPS. Keep all vents free of dust accumulation that could restrict air flow.
  • Do not place UPS power cord anywhere it might be damaged.

Battery Handling Precautions

  • ! WARNING Batteries should be replaced only by properly trained and qualified personnel knowledgeable of batteries and required precautions. A battery can present a risk of electrical shock and high short-circuit current. The following precautions must be observed when working on batteries:
  • Remove watches, rings and other metal objects.
  • Use tools with insulated handles.
  • Do not dispose of the battery or batteries in a fire. The battery may explode.
  • Do not open or mutilate the battery or batteries. Released electrolyte is toxic. It may cause injury to the skin and eyes.
  • When replacing the battery, use the same type of battery as is listed in Table 5 .
  • Handle, transport and recycle batteries in accordance with local regulations.
Page 6 of the Emerson 2200 user manual — Important Safety Instructions
Page 6 · click to enlarge
Page 6

CONDITIONS OF USE—The input supply outlet must be within 6 ft. (1.8m) of the UPS and be eas- ily accessed.

This UPS provides conditioned power to connected equipment. It is not intended for use with life-sup- port and other designated “critical” devices. Maximum load must not exceed that shown on the UPS rating label. If uncertain, consult your local dealer, local Emerson Network Power representative or Channel Support Applications.

When installing the UPS or making input and output connections, comply with all relevant safety codes and standards (e.g., UL 1778).

Placing magnetic storage media on top of the UPS may result in data corruption.

ELECTROMAGNETIC COMPATIBILITY—The Liebert PSI XR complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:

  • This device may not cause harmful interference, and
  • This device must accept any interference received, including interference that may cause undesired operation.

This equipment uses, generates and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference with radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, the user is encouraged to try to correct the interference by one or more of the following measures:

  • Reorient or relocate the receiving antenna.
  • Increase the separation between the UPS and the receiver.
  • Connect the UPS to an outlet on a circuit different from the one the receiver is connected to. NOTICE

Do not connect equipment that could overload the UPS or demand half-wave rectification from the UPS, such as electric drills, vacuum cleaners, laserjet printers and hair dryers.

Page 7 of the Emerson 2200 user manual — OFF
Page 7 · click to enlarge
Page 7

G LOSSARY OF S YMBOLS

Risk of electrical shock

!

Indicates caution followed by important instructions

Indicates the unit contains a valve-regulated, lead-acid battery

ON/Alarm Silence/Manual Self-Diagnostic Test

OFF

Show 6 more labels / short text on this page
Recycle · DC voltage · Equipment grounding conductor · Bonded to ground · AC voltage · Status Change Button
Page 8 of the Emerson 2200 user manual — Figure 2 1000 and 1500—rear view
Page 8 · click to enlarge
Page 8

1.0 I NTRODUCTION

The Liebert PSI™ XR is a 2U, line-interactive UPS that may be installed in a rack or used as a tower UPS. Status indicators on the front of the Liebert PSI XR display load level, battery level, buck/boost, site- wiring fault, overload, battery status and UPS operation. Controls include a combination On/Alarm Silence/Manual Self-Diagnostic Test button, an Off button and a Status Change button. The Liebert PSI XR has USB, DB-9 (contact closure) and Liebert IntelliSlot® ports. The DB-9 and USB ports provide detailed operating information including voltages, currents, and alarm status to the host system when used in conjunction with Liebert MultiLink™ software. The Liebert PSI XR is compliant with the Restriction of Hazardous Substances Directive (ROHS), prohibiting use of six hazardous materials manufacturing of electronics, including lead-free solder.

Figure 1 Front view of UPS

Emerson 2200 — Figure 1 Front view of UPS diagram (page 8)
Fig. 2 · Figure 1 Front view of UPS
Emerson 2200 — Figure 1 Front view of UPS diagram (page 8)
Fig. 3 · Figure 1 Front view of UPS

Liebert PSI XR rack-mount configuration Display rotates for use as tower

Liebert PSI XR tower configuration Display rotates for use in rack

Figure 2 1000 and 1500—rear view

DB-9 Port (Contact Closure)

Input Circuit Breaker (12A for 1000VA; 15A for 1500VA)

Output Circuit Breaker (8A for 1000VA; 15A for 1500VA) Receptacles NEMA 5-15R

Emerson 2200 — Figure 2 1000 and 1500—rear view diagram (page 8)
Fig. 4 · Figure 2 1000 and 1500—rear view

External Battery Cabinet Connector Voltage Configuration DIP Switch

Power Cord; 5-15P (not shown for clarity)

Show 4 more labels / short text on this page
Introduction · Liebert IntelliSlot Port · USB Port · Network Surge Protection
Page 9 of the Emerson 2200 user manual — Figure 4 3000—rear view
Page 9 · click to enlarge
Page 9

Figure 3 2200—rear view

15A Output Circuit Breaker for Receptacles #3 & #4

Receptacles #3 and #4 NEMA 5-15R

Power Cord; 5-20P (not shown for clarity)

Emerson 2200 — Figure 3 2200—rear view diagram (page 9)
Fig. 5 · Figure 3 2200—rear view

#5 and #6 NEMA 5-15R 30A Input Circuit Breaker

15A Output Circuit Breaker for Receptacles #5 & #6 20A Input Circuit Breaker Receptacles #1 and #2

Voltage Configuration DIP Switch

Figure 4 3000—rear view

15A Output Circuit Breaker for Receptacles #3 & #4

Power Cord; L5-30P (not shown for clarity)

Emerson 2200 — Figure 4 3000—rear view diagram (page 9)
Fig. 6 · Figure 4 3000—rear view

15A Output Circuit Breaker for Receptacles #5 & #6

Voltage Configuration DIP Switch

20A Output Circuit Breaker Receptacles #1 and #2

Introduction · Network Surge Protection

Page 10 of the Emerson 2200 user manual — Figure 5 Accessories
Page 10 · click to enlarge
Page 10

2.0 W HAT ’ S I NCLUDED

The Liebert PSI XR is shipped with the following items:

  • Multi-Language User Manual on CD
  • Liebert MultiLink Software and User Manual, downloadable at multilink.<a href="http://liebert.com" rel="nofollow noopener" target="_blank">liebert.com</a>
  • Contact Closure (ML9P9S) Cable
  • USB Cable
  • Tower Stands
  • Mounting Hardware
  • Rack-Mount Handles
  • Fixed Mounting Rails
  • EPO Connector
  • Battery-UPS Tab

Figure 5 Accessories

Emerson 2200 — Figure 5 Accessories diagram (page 10)
Fig. 7 · Figure 5 Accessories
Emerson 2200 — Figure 5 Accessories diagram (page 10)
Fig. 8 · Figure 5 Accessories

6 ft (1.8m)

6 ft (1.8m)

Emerson 2200 — Figure 5 Accessories diagram (page 10)
Fig. 9 · Figure 5 Accessories

Mounting Hardware (Screws and Washers)

Emerson 2200 — Figure 5 Accessories diagram (page 10)
Fig. 10 · Figure 5 Accessories
Show 10 more labels / short text on this page
What’s Included · Tower Stands · Contact Closure · USB cable · (ML9P9S) Cable · Rack-Mount · Handles · Fixed Mounting Rails · EPO Connector · Battery-UPS Tab
Page 11 of the Emerson 2200 user manual — Figure 6 Placing the Liebert PSI XR
Page 11 · click to enlarge
Page 11

3.0 I NSTALLATION

3.1 Preparation

! CAUTION The UPS and battery cabinets are heavy (see Table 6 and Table 7). Take proper precautions when lifting or moving either the UPS or battery cabinets.

The Liebert PSI XR may be installed in either a tower or rack configuration. Determine the method that suits the application and proceed.

Decide where to install the Liebert PSI XR. The UPS must be installed indoors in a controlled envi- ronment. Place it in an area with unrestricted airflow around the unit, away from water, flammable liquids, gases, corrosives and conductive contaminants (see Figure 6).

Maintain a minimum clearance of 12 inches (305mm) in the front and rear of the UPS. Maintain an ambient temperature range of 32°F to 104°F (0°C to 40°C).

Figure 6 Placing the Liebert PSI XR

AIR

AIR

32 F (0 C)

104 F (40 C)

AIR

12 in./305mm

0% ~ 90%

Installation · Relative humidity (non-condensing)

Page 12 of the Emerson 2200 user manual — Figure 7 Tower configuration—attach Tower Stands
Page 12 · click to enlarge
Page 12

3.2 Tower UPS Installation

See Figure 7 when using the Liebert PSI XR in a tower configuration.

Figure 7 Tower configuration—attach Tower Stands

Installation · Step 2 · Step 1

Page 13 of the Emerson 2200 user manual — NOTICE
Page 13 · click to enlarge
Page 13

3.3 Rack-Mount UPS Conversion and Installation

See Figure 8 when installing the Liebert PSI XR in a rack. External battery cabinets are installed in same manner.

Figure 8 Convert the Liebert PSI XR for rack installation

Emerson 2200 — Figure 8 Convert the Liebert PSI XR for rack installation diagram (page 13)
Fig. 11 · Figure 8 Convert the Liebert PSI XR for rack install…
Emerson 2200 — Figure 8 Convert the Liebert PSI XR for rack installation diagram (page 13)
Fig. 12 · Figure 8 Convert the Liebert PSI XR for rack install…

! WARNING Placing heavy equipment near the top of a rack may increase the risk of tipping. Place the UPS, and battery cabinet if one is being used, in the bottom of the rack.

! CAUTION Lifting equipment into rack may be a two-person job, depending on weight of equipment.

NOTICE

When rack-mounted, the UPS must be supported by a shelf, slide rails, brackets or fixed rails on each side. The rack-mount handles WILL NOT support the weight of the UPS. They are used to move the UPS into and out of the rack.

Installation

Page 14 of the Emerson 2200 user manual — Figure 10 Connect input power and load
Page 14 · click to enlarge
Page 14

3.4 Orient Display for Installation

The Liebert PSI XR features a rotating display that may be oriented for either tower or rack installations.

To set the display for your installation, pull out on the display and rotate it until it is oriented correctly, then press it into the UPS until it is seated.

Figure 9 Orienting the UPS display

Emerson 2200 — Figure 9 Orienting the UPS display diagram (page 14)
Fig. 13 · Figure 9 Orienting the UPS display

3.5 Charge Batteries and Perform Battery Startup

Before connecting input power or connecting the load, Emerson recommends these steps:

  • Charge the battery for at least 8 hours.
  • Start the UPS on battery to ensure the battery is fully functional and charged.
  • Turn the unit Off and proceed to 3.6 - Connect Input Power and Load .

3.6 Connect Input Power and Load

Connect input power to the UPS, then plug the equipment into the outlets on the rear of the UPS. These UPS outlets provide battery backup and surge protection to the equipment when utility power fails, spikes or sags (see Figure 10).

Figure 10 Connect input power and load

Emerson 2200 — Figure 10 Connect input power and load diagram (page 14)
Fig. 14 · Figure 10 Connect input power and load

Installation

Page 15 of the Emerson 2200 user manual — Figure 12 Connect communication interface
Page 15 · click to enlarge
Page 15

3.7 Connect Network Surge protection

Connect a 10 base-T/100 network cable to the network surge protection IN jack on the rear of the UPS. Connect from the OUT jack with network cabling to network equipment (see Figure 11).

Figure 11 Connect network surge protection

Emerson 2200 — Figure 11 Connect network surge protection diagram (page 15)
Fig. 15 · Figure 11 Connect network surge protection

Network surge protection IN Jack Network surge protection OUT jack

3.8 Connect Communication Interface

Determine what type of communication connection to use to manage the UPS. The Liebert PSI XR can be monitored with any of these communication methods:

  • Contact closure
  • USB
  • SNMP (requires optional IS-WEBRT3 card)

Connect the appropriate, factory-supplied cable to the interface port on the rear of the UPS and to the computer interface port.

See 3.9 - Set Up Liebert MultiLink software for details and installation information. Also refer to 6.4 - UPS Communications.

Figure 12 Connect communication interface

Emerson 2200 — Figure 12 Connect communication interface diagram (page 15)
Fig. 16 · Figure 12 Connect communication interface

Installation

Page 16 of the Emerson 2200 user manual — 1 = EPO+
Page 16 · click to enlarge
Page 16

3.9 Set Up Liebert MultiLink software

To start using Liebert MultiLink (software and user manual available at multilink.liebert.com):

  • Install the software. See the Liebert MultiLink quick-start guide or user manual for installation instructions.
  • Connect one end of the USB cable (supplied) to the USB port on the rear of the UPS. Connect the other end to a USB port on the computer. See the Liebert MultiLink user manual for operating instructions.

3.10 EPO Switch

The Liebert PSI XR is equipped with an Emergency Power Off (EPO) switch. The user must supply a means of interfacing with the EPO circuit to allow disconnecting the UPS input feeder breaker to interrupt all sources of power to the UPS and connected equipment to comply with national and local wiring codes and regulations.

Figure 13 EPO connection for normally open operation

Emerson 2200 — Figure 13 EPO connection for normally open operation diagram (page 16)
Fig. 17 · Figure 13 EPO connection for normally open operation

1 = EPO+

Short Pin 1 and Pin 2 to enable the EPO function

Installation · 2 = Ground

Page 17 of the Emerson 2200 user manual — Table 1 Battery cabinet connector color key
Page 17 · click to enlarge
Page 17

3.11 External Battery Cabinet Installation

Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery run time. External battery cabinets are designed to be placed all on one side of the UPS or stacked beneath the UPS. The batteries have a maximum run time of three hours at full load.

1. Install the external battery cabinet in toweror rack-configuration (see Figure 14 or 3.3 - RackMount UPS Conversion and Installation ). 2. Connect the external battery cabinet cable to the rear of the external battery cabinet, then to the rear of the UPS (see Figure 15 ).

Figure 14 Install the external battery cabinet in tower installation

Connect the top of the UPS to the top of the battery cabinet with the Battery UPS Tab and hardware

If two or more battery cabinets are used in a tower setup, the tower stand must be extended with the spacers included with each battery cabinet.

Connect tower stand and set the UPS and battery cabinet in them; check to ensure stability

NOTICE

External battery cabinet power connectors are color-coded as noted in Table 1. Do not try to install external battery cabinets with connectors that are a different color from the battery connector on the UPS.

Table 1 Battery cabinet connector color key

UPS Model Nominal System Voltage (connector color) External Battery Cabine Model

PS1000RT3-120XR PS1000RT3120XRW 24VDC (Red) PSRT3-24VBXR PS1500RT3-120XR PS1500RT3120XRW

PS2200RT3-120XR PS2200RT3120XRW 48VDC (Gray) PSRT3-48VBXR PS3000RT3-120XR PS3000RT3120XRW

Installation

Page 18 of the Emerson 2200 user manual — Figure 15 Connect battery cabinets to UPS
Page 18 · click to enlarge
Page 18

Figure 15 Connect battery cabinets to UPS

Emerson 2200 — Figure 15 Connect battery cabinets to UPS diagram (page 18)
Fig. 18 · Figure 15 Connect battery cabinets to UPS

See Table 8 for approximate battery run times.

Installation

Page 19 of the Emerson 2200 user manual — Table 2 Display and status indicators function, legend
Page 19 · click to enlarge
Page 19

4.0 C ONTROLS AND I NDICATORS

Buttons on the front panel display control the Liebert PSI XR. Eight LEDs indicate the UPS’s status. Refer to Figure 16 and Table 2.

Figure 16 Display and status indicators

1 2 3 4 5

Load Level Battery Level

6 7 8 9 10 11

Table 2 Display and status indicators function, legend

Item Name Status Indicators Description

1 LED 1 AVR Boost UPS Operation in AVR Boost Mode

2 LED 2 AVR Buck UPS Operation in AVR Buck Mode

3 LED 3 Battery Condition Battery Fault/Weak

4 LED 4 Grounding/Site Wiring Fault UPS Grounding/Site Wiring Fault

5 LED 5 Overload UPS Overload

1 to 5 Load/Battery Level Indicate Load/Battery Level

6 Status Change Button Switches Display from Load Level Indicators to Battery Level Indicators

7 OFF Button UPS Off

8 ON Button Turn on UPS, Manual Self-Diagnostic (Normal Mode), Silence Alarm (Battery Mode)

9 LED 9 Normal Mode UPS Operation in Normal Mode

10 LED 10 Battery Mode UPS Operation in Battery Mode

11 LED 11 UPS Fault UPS Fault

Controls and Indicators

Page 20 of the Emerson 2200 user manual — 4.2.2 Load Level Indicator
Page 20 · click to enlarge
Page 20

4.1 Control Buttons

4.1.1 On/Alarm Silence/Manual Self-Diagnostic Test

This button controls output power to connected load(s). It has three functions:

  • On
  • Alarm Silence
  • Manual Self-Diagnostic Test

ON—Start the UPS by pressing this button for more than 3 seconds, then releasing the button (an alarm will sound briefly). If the ON button is pressed and utility is outside input parameters, the UPS will start on battery (dark start).

Alarm Silence—Silence a battery mode audible alarm by pressing this button for longer than one second, then releasing it.

Manual Self-Diagnostic Test—To initiate a Manual Self-Diagnostic, press this button for at least three (3) seconds while operating from utility power. UPS will switch to Battery Mode to detect bat- tery voltage and whether the UPS is operating normally.

If LED indicates the battery is weak: Allow the UPS to recharge the batteries for 8 hours. Retest the battery after recharge.

If LED still indicates the battery is weak after the battery has been retested, contact your local dealer, local Emerson representative or Channel Support Applications. If LED indicates a Battery Fault: Contact your local dealer, local Emerson representative or Channel Support Applications. If LED indicates a UPS Fault: Remove the load, retest the self diagnostic test, if LED indicated UPS Fault, Contact your local dealer, local Emerson representative or Channel Support Applica- tions.

4.1.2 Off Button

When the UPS is operating in either Normal Mode or Battery Mode, pressing the Off button for more than three seconds will shut down the UPS.

4.2 Status Indicators

4.2.1 Status Change Button

The Status Change button determines the information displayed by the five LEDs on the front panel. The default information shown by the LEDs is the load level on the UPS. Pressing the Status Change button while the UPS is On prompts the LED display to show battery capacity for 5 seconds. This function assists in assessing the meaning of status indicators as described in 4.2.4 - UPS Status Indicators. See Figure 16 and Table 2 for the Status Change button’s location.

4.2.2 Load Level Indicator

The five LEDs at the top of the front panel illuminate with a steady glow to indicate the load level on the output of the UPS. The LEDs show the load level as a range, ± 5%. The LEDs’ load level meanings and colors are:

LED 1 LED 2 LED 3 LED 4 LED 5

10-24% — Green 25-49% — Green 50-74% — Yellow 75-99% — Yellow 100% or greater — Red

Controls and Indicators

Page 21 of the Emerson 2200 user manual — Table 3 Status indicators—color, illumination mode
Page 21 · click to enlarge
Page 21

4.2.3 Battery Level Indicator

The five LEDs illuminate with a steady glow to indicate battery capacity. Battery capacity is shown for five seconds after the Status Change button is pressed. The LEDs show the battery capacity as a range, ± 5% The LEDs’ battery level meanings and colors are:

LED 1 LED 2 LED 3 LED 4 LED 5

100-76% — Green 75-51% — Green 50-26% — Yellow 25-11% — Yellow 10% or less — Red

4.2.4 UPS Status Indicators

LEDs on the display panel illuminate with a steady glow or flash to indicate the UPS’s status:

Normal Mode—The Normal Mode indicator illuminates (LED 9) with a steady glow when utility power is available and within the input specifications.

Battery Mode—The Battery Indicator illuminates (LED 10) with a steady glow when the UPS is operating on battery

AVR Boost, AVR Buck—When the UPS is in AVR Boost/Buck Mode, the LED display will indicate the relative load level on the output of the UPS and will flash LED 1 (boost) or LED 2 (buck) to indi- cate which mode the UPS is in.

Weak Battery—When the UPS battery voltage is low, the LED display will indicate the relative load level on the output of the UPS and LED 3 will flash as a warning.

Site-Wiring Fault—In case of a site-wiring fault, the LED display will indicate the relative load level on the output of the UPS and LED 4 will flash as a warning.

Overload—When UPS operates in overload status, the LED display will indicate the relative load level on the output of the UPS and LED 5 will flash as a warning.

Table 3 Status indicators—color, illumination mode

Status LED 1 LED 2 LED 3 LED 4 LED 5 LED 9 LED 10 LED 11

Normal Mode Green Steady

AVR Boost Green Flashes

AVR Buck Green Flashes

Battery Mode (dark start)

Weak Battery Yellow Flashes

Site-Wiring Fault Yellow Flashes

UPS Output Abnormal Shutdown

Show 13 more labels / short text on this page
Controls and Indicators · Green Steady · Green Steady · Yellow Steady · Overload Red Flashes · Battery Fault Shutdown · Yellow Steady · Red Steady · Overload Shutdown · Red Steady · Red Steady · Yellow Steady · Red Steady
Page 22 of the Emerson 2200 user manual — 5.4 Battery Recharge Operation
Page 22 · click to enlarge
Page 22

5.0 O PERATIONAL M ODES

5.1 Normal Mode

When the UPS is in Normal Mode, the Normal Mode Indicator illuminates green.

5.2 Buck/Boost Mode

The Automatic Voltage Regulator (AVR) circuitry compensates for fluctuations in utility power, such as voltage surges and sags. When the Liebert PSI XR detects an abnormality, it raises the undervolt- age (boost) or lowers the overvoltage (buck) as needed. The AVR operates automatically and main- tains the output voltage to the connected equipment, without utilizing the batteries.

LED 1 flashes green and LED 9 illuminates steady green when the UPS is in Boost Mode. LED 2 flashes green and LED 9 illuminates steady green when the UPS is in Buck Mode (see 9.0 - Trouble- shooting for details).

5.3 Battery Mode

The UPS switches to Battery Mode in the event of an extreme input voltage/frequency condition or utility failure.

When the UPS is in Battery Mode, the Battery Indicator illuminates amber and an alarm sounds at two-second intervals. As capacity decreases, fewer indicators remain illuminated.

When a Low Battery condition occurs, the Battery Indicator flashes amber and an alarm sounds at one-second intervals. Refer to Table 8 for approximate battery run times.

5.4 Battery Recharge Operation

Once utility power is restored, the UPS resumes normal operation and the Battery Charger begins recharging the batteries.

Operational Modes

Page 23 of the Emerson 2200 user manual — 6.3 Network Surge Protection Connectors
Page 23 · click to enlarge
Page 23

6.0 C OMMUNICATION

6.1 DB-9 Connector

The UPS has a DB-9 (9 pin female) connector on the rear to allow UPS status communications with a computer running Liebert MultiLink software in contact closure mode. The connection provides On Battery and Low Battery notification.

When power is interrupted and battery power is low, Liebert MultiLink software can signal the host computer to gracefully shut down the operating system.

Table 4 DB-9 pin assignment

DB-9 Pin Assignment Description

1 Low Battery (open collector)

2 UPS TxD (not used)

3 UPS RxD (not used)

4 Remote Shutdown (5-12V); on-battery operation

6 Output Off, (short to Pin 5, non-latching); any mode operation

7 Low Battery (open emitter)

8 Utility Fail (open emitter)

9 Utility Fail (open collector)

Pin Assignment Collector to Emitter*

Emerson 2200 — Pin Assignment Collector to Emitter* diagram (page 23)
Fig. 19 · Pin Assignment Collector to Emitter*
Emerson 2200 — Pin Assignment Collector to Emitter* diagram (page 23)
Fig. 20 · Pin Assignment Collector to Emitter*
Emerson 2200 — Pin Assignment Collector to Emitter* diagram (page 23)
Fig. 21 · Pin Assignment Collector to Emitter*
Emerson 2200 — Pin Assignment Collector to Emitter* diagram (page 23)
Fig. 22 · Pin Assignment Collector to Emitter*
Emerson 2200 — Pin Assignment Collector to Emitter* diagram (page 23)
Fig. 23 · Pin Assignment Collector to Emitter*

6 7 8 9

5 4 3 2 1

6.2 Remote Shutdown Via the DB-9 Connector

The Liebert PSI XR can be shut down remotely by shorting Pins 5 and 6 or via Pins 4 and 5 of the DB- 9 connector.

6.2.1 Any Mode Shutdown Via Pins 5 & 6

When Pin 6 is shorted to Pin 5, the UPS output is shut Off no matter what mode the UPS is operating in. The UPS cannot be started as long as the pins are shorted. When the short is removed, the UPS output can be enabled by pressing the ON/Alarm Silence/Manual Self-Diagnostic Test button.

6.2.2 Battery Mode Shutdown Via Pins 4 & 5

While the UPS is operating on battery, a 5-12VDC signal for 2 seconds or longer is required to signal a shutdown. Signals for less than 2 seconds are ignored.

After Pin 4 receives the shutdown signal, a 2-minute shutdown timer begins a countdown. The shut- down timer cannot be stopped: If utility power returns during the 2-minute countdown, the shutdown timer continues until the end of 2 minutes and the UPS turns Off. The UPS will restart 10 seconds after utility power returns.

6.3 Network Surge Protection Connectors

Network (in and out) connectors on the rear of the UPS provide transient voltage surge suppression (TVSS) for network devices.

Show 6 more labels / short text on this page
Communication · 5 Common · Open Collector · (+) 330 Ohms · (-) · Open Emitter
Page 24 of the Emerson 2200 user manual — Figure 17 DIP switch settings for 120V system
Page 24 · click to enlarge
Page 24

6.4 UPS Communications

The Liebert PSI XR is equipped with a Liebert IntelliSlot port to provide advanced communication and monitoring options.

Liebert MultiLink software continually monitors the UPS and can shut down your computer or server via USB, contact closure and SNMP (via IS-WEBRT3 card) in the event of an extended power failure.

The Liebert IS-WEBRT3 provides SNMP and Web-based monitoring and control of the UPS across the network.

6.5 UPS Inverter/Transfer Voltage Configurations

A two-pin DIP switch on the rear of the PSI XR permits setting the UPS to operate at nominal volt- ages of 110V, 120V or 127V. This feature will change the high and low points at which the UPS switches to battery power. It also changes the UPS’ output voltage when the UPS is operating in bat- tery mode. The factory default setting is 120 VAC.

Turn Off the UPS before making any changes to the voltage configuration.

Figure 17 DIP switch settings for 120V system

FUNCTION 2 1

ON

Table 5 Voltage configurations

Emerson 2200 — Figure 17 DIP switch settings for 120V system diagram (page 24)
Fig. 24 · Figure 17 DIP switch settings for 120V system
Show 5 more labels / short text on this page
Communication · Voltage = 110V · Voltage = 120V · Voltage = 120V · Voltage = 127V
Page 25 of the Emerson 2200 user manual — Figure 18 Battery replacement
Page 25 · click to enlarge
Page 25

7.0 B ATTERY M AINTENANCE

7.1 Battery Charging, Storage

The batteries are valve-regulated, nonspillable, lead acid and must be kept charged to retain their design life. The Liebert PSI XR continuously charges the batteries when connected to the utility sup- ply, even while the UPS is switched Off.

If the Liebert PSI XR will be stored for an extended period, Emerson recommends connecting the UPS to input power for at least 8 hours every four to six months to keep the batteries charged.

Emerson recommends performing a monthly manual self-diagnostic test via the Web card or the front panel display.

7.2 Internal Battery Replacement Procedure

NOTICE

This UPS is equipped with internal batteries that the user can replace without shutting down the UPS or connected loads (hot swappable). Caution must be exercised when replacing the batteries because the load is unprotected from power fluctuations and power failures.

To replace the batteries:

1. Remove the two screws on the left side of the front bezel. 2. Pull the front bezel off the UPS. 3. Remove the screw on the battery connector holder. 4. Remove the two screws on the battery bracket. 5. Disconnect the two slotted, red/gray and black battery connectors. 6. Grasp the battery pack assembly by the handle and pull it out of the front of the UPS. 7. Unpack the new battery assembly, taking care not to destroy the packing. 8. Compare the new and old battery assemblies to make sure they are the same. If so, proceed with replacement. If they are different, STOP and contact your local dealer, local Emerson representative or Channel Support Applications. 9. Slide the new battery pack into the UPS. 10. Reattach the battery bracket with the two screws. 11. Reconnect the slotted, red/gray and black battery connectors. 12. Reinsert the screw on the battery connector holder. 13. Reattach the front bezel.

Figure 18 Battery replacement

Step 1 Step 2

Emerson 2200 — Figure 18 Battery replacement diagram (page 25)
Fig. 25 · Figure 18 Battery replacement
Emerson 2200 — Figure 18 Battery replacement diagram (page 25)
Fig. 26 · Figure 18 Battery replacement

Step 3 Step 4

Emerson 2200 — Figure 18 Battery replacement diagram (page 25)
Fig. 27 · Figure 18 Battery replacement
Emerson 2200 — Figure 18 Battery replacement diagram (page 25)
Fig. 28 · Figure 18 Battery replacement

Battery Maintenance

Page 26 of the Emerson 2200 user manual — PS1500RT3-120XR PS1500RT3120XRW
Page 26 · click to enlarge
Page 26

8.0 S PECIFICATIONS

Table 6 Liebert PSI XR specifications

PS3000RT3-120XR PS3000RT3120XRW Power Rating, VA/W 1000VA/900W 1500VA/1350W 1920VA/1920W* 3000VA/2700W Dimensions, W x D x H, in (mm)

Model Number PS1000RT3-120XR PS1000RT3120XRW

PS1500RT3-120XR PS1500RT3120XRW

PS2200RT3-120XR PS2200RT3120XRW

Unit 17.3 x 19.3 x 3.5 (440 x 490.5 x 88) 17.3 x 27.6 x 3.5 (440 x 700.5 x 88) Shipping 22 x 24.1 x 9 (560 x 612 x 228) 22 x 34.8 x 9.0 (560 x 884 x 228) Weight, lb (kg)

Unit 56 (25) 62 (28) 92 (42) 105 (48) Shipping 64 (29) 70 (32) 101 (46) 115 (52) Input AC Parameters

Surge Protection 570J Voltage Range Without Battery Operation 83-159 VAC (configurable)

Frequency Range 45~65Hz, (±0.5Hz) Input Power Cord, 10ft (3m) attached NEMA 5-15P plug NEMA 5-20P plug NEMA L5-30P plug

(4) NEMA 5-15R (2) NEMA 5-20R T-Slot,

(4) NEMA 5-15R (2) NEMA 5-20R T-Slot,

Output Receptacles (6) NEMA 5-15R

accepts15A Plug (1) NEMA L5-30R Voltage (Normal Mode) 110/120/127 VAC (configurable) Voltage (Battery Mode) 110/120/127 VAC; ±5% before low-battery warning Transfer Time 4-6 ms typical Waveform Sinewave Battery Parameters

Type Valve-regulated, nonspillable, lead acid Quantity x Voltage x Ah 4 x 12 x 7.2 4 x 12 x 9 8 x 12 x 7.2 8 x 12 x 9 Recharge Time 5 hours to 90% of rated capacity, after full discharge into resistive load Battery Backup Time

Full Load 5 minutes Half Load 10 minutes Environmental

Operating Temperature, °F (°C) 32 to 104 (0 to 40) Storage Temperature, °F (°C) 5 to 104 (-15 to 40) Relative Humidity 0% to 90%, non-condensing Operating Altitude Up to 10,000 ft (3000m) Audible Noise

Safety UL 1778, c-UL Listed Surge ANSI C62.41 CatA Lev3 (surges) IEC61000-4-5 ESD IEC61000-4-2 Susceptibility IEC61000-4-3 Electrical Fast Transient IEC61000-4-4 Emissions FCC Part 15, Class A Conducted Immunity IEC61000-4-6 Harmonics IEC61000-3-2 Network surge UL 497 B Transportation ISTA Procedure 1A Certification

* NEC limits the input current rating of the PS2200RT3-120XR and PS2200RT3120XRW models to 80% of the input plug's rating. Up to 2200VA/1980W is available by contacting a certified electrician to change the input plug to 30A plug. Emerson Network Power assumes no liability for damage caused by miswiring or misapplication of the input plug.

Show 4 more labels / short text on this page
Specifications · accepts15A Plug · ROHS compliant · Environmental
Page 27 of the Emerson 2200 user manual — PS1000RT3-120XR PS1000RT3120XRW
Page 27 · click to enlarge
Page 27

Table 7 Battery cabinet specifications

Model Number PSRT3-24VBXR PSRT3-48VBXR

PS1000RT3-120XR PS1000RT3120XRW

PS2200RT3-120XR PS2200RT3120XRW

PS1500RT3-120XR PS1500RT3120XRW

PS3000RT3-120XR PS3000RT3120XRW

Dimensions, W x D x H, in (mm)

Unit 17.3 x 19.3 x 3.5 (440 x 490.5 x 88)

Shipping 22 x 26.6 x 9 (560 x 675 x 228)

Type Valve-regulated, nonspillable, lead acid

Quantity x Voltage x Ah 8 x 12 x 7.2 8 x 12 x 7.2

Manufacturer CSB, YUASA or Equivalent

Operating Temperature, °F (°C) 32 to 104 (0 to 40)

Storage Temperature, °F (°C) 5 to 104 (-15 to 40)

Relative Humidity 0% to 90%, non-condensing

Maximum Operating Altitude 10,000 ft. (3000m)

Safety UL 1778, c-UL Listed

Emissions FCC Part 15, Class A

Transportation ISTA Procedure 1A Certification

Show 8 more labels / short text on this page
Specifications · Used w/UPS Model · Weight, lb (kg) · Unit 64 (29) · Shipping 73 (33) · Batteries · Environmental · Agency
Page 28 of the Emerson 2200 user manual — Table 8 Liebert PSI XR battery run times
Page 28 · click to enlarge
Page 28

Table 8 Liebert PSI XR battery run times

Number of Batteries Load % 1000 1500 2200 3000

10 83 82 76 75

20 52 48 48 47

30 31 28 28 28

40 18 17 17 17

50 15 13 14 13

60 12 11 11 11

70 11 9 9 9

80 9 7 8 7

90 7 6 7 6

100 6 5 5 5

10 263 222 161 143

20 165 131 101 83

30 120 93 69 60

40 95 68 55 47

Internal battery + 1 External Battery Cabinets

50 73 56 45 32

60 62 47 31 27

70 54 33 27 18

80 48 29 18 16

90 43 26 17 14

100 32 18 15 12

10 439 357 242 205

20 275 212 152 127

30 200 150 111 92

40 157 116 82 68

Internal battery + 2 External Battery Cabinets

50 129 95 68 56

60 110 76 57 47

70 96 65 50 33

80 80 58 44 30

90 71 52 32 26

100 65 47 29 18

10 614 492 322 267

20 385 291 202 166

30 280 207 147 120

40 220 160 116 94

Internal battery + 3 External Battery Cabinets

50 181 131 96 73

60 154 111 77 62

70 134 95 67 54

80 119 79 59 47

90 106 71 53 43

100 96 64 48 31

Run times are in minutes, assume fully charged batteries and are typical at 77°F (25°C) with resistive loads.

Specifications · Internal Battery

Page 29 of the Emerson 2200 user manual — Table 8 Liebert PSI XR battery run times (continued)
Page 29 · click to enlarge
Page 29

Table 8 Liebert PSI XR battery run times (continued)

Number of Batteries Load % 1000 1500 2200 3000

10 790 627 483 330

20 494 371 303 204

30 360 264 221 148

40 283 204 174 116

Internal battery + 4 External Battery Cabinets

50 233 167 143 95

60 198 141 122 76

70 172 122 106 66

80 152 108 94 59

90 137 96 79 52

100 124 82 72 48

10 965 762 564 392

20 605 452 354 243

30 440 320 258 176

40 346 248 203 138

Internal battery + 5 External Battery Cabinets

50 265 203 167 113

60 242 171 142 96

70 211 148 124 79

80 186 131 110 70

90 167 117 98 62

100 151 106 84 56

10 1140 897 644 454

20 714 531 405 281

30 520 377 295 204

40 408 292 232 160

Internal battery + 6 External Battery Cabinets

50 337 239 191 131

60 286 202 163 112

70 249 175 142 97

80 220 154 125 81

90 197 138 112 72

100 179 124 102 65

Run times are in minutes, assume fully charged batteries and are typical at 77°F (25°C) with resistive loads.

Specifications

Page 30 of the Emerson 2200 user manual — Table 9 Troubleshooting—problems, causes and solutions
Page 30 · click to enlarge
Page 30

9.0 T ROUBLESHOOTING

The information below indicates various symptoms a user may encounter if the Liebert PSI XR expe- riences a problem. See Table 9 for suggested solutions. 1. An alarm sounds, alerting that the UPS requires attention. The alarm can be silenced except for low battery, overload warning and fault. 2. One or more additional indicators will be illuminated to provide a diagnostic aid to the operator, as described below: If the UPS fails to operate properly, turn Off the unit and repeat the steps in 3.0 - Installation. If the problem persists, refer to Table 9.

Table 9 Troubleshooting—problems, causes and solutions

Problem Cause Solution

Check the circuit breaker on the rear of the UPS. If it is tripped, reset it and restart the UPS. For help, contact your local dealer, local Emerson representative or Channel Support Applications. Battery is disconnected or completely discharged

UPS will not start

Check for proper connection of battery or batteries.

UPS not plugged in Plug in the power cord securely.

Circuit breaker tripped Reset the circuit breaker and restart the UPS.

UPS starts on battery, but will not switch to AC (dark start)

Wait until voltage drops to an appropriate level or have the utility power checked by a properly trained and qualified electrician.

Remove the load and turn on the UPS again. For help, contact your local dealer, local Emerson representative or Channel Support Applications.

Short circuit or UPS output is abnormal; LED 10 and LED 11 illuminate and sound audible alarm

Check load level display and remove nonessential loads. Recalculate the load and reduce equipment connected to UPS - the total wattage must not exceed the capacity of the UPS. LED 3 and LED 11 illuminate and sound audible alarm

Overload; LED 5 and LED 11 illuminate and sound audible alarm

Recharge the battery for 8 hours, then turn ON the UPS.

Consult the Liebert MultiLink user manual or contact your LAN administrator.

Site Wiring Fault, UPS detected a line-to-neutral reversal or a loss of proper grounding.

Have the utility checked by a properly trained and qualified electrician.

Site Wiring Fault LED (LED 4) flashing

Battery weak LED (LED 3) flashing Batteries weak Recharge batteries. Batteries need to be replaced Replace batteries.

Show 5 more labels / short text on this page
Troubleshooting · Short circuit · AC overvoltage · UPS shuts down · Liebert MultiLink software
Page 31 of the Emerson 2200 user manual — 9.0 Troubleshooting
Page 31 · click to enlarge
Page 31
Page 31 of the Emerson 2200 user manual — 9.0 Troubleshooting
Page 32 of the Emerson 2200 user manual — SL-23315_REV03_07-09
Page 32 · click to enlarge
Page 32

Ensuring The High Availability Of Mission-Critical Data And Applications.

Emerson Network Power, the global leader in enabling business-critical continuity, ensures network resiliency and adaptability through a family of technologies—including Liebert power and cooling technologies—that protect and support business-critical systems. Liebert solutions employ an adaptive architecture that responds to changes in criticality, density and capacity. Enterprises benefit from greater IT system availability, operational flexibility and reduced capital equipment and operating costs.

Technical Support / Service

Web Site www.liebert.com

Monitoring 800-222-5877 Liebert.monitoring@emerson.com

Outside the US614-841-6755

800-222-5877 upstech@emersonnetworkpower.com

Outside the US614-841-6755

800-543-2378 powertech@emersonnetworkpower.com

800-543-2778 Outside the United States

614-888-0246 Locations United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229

Europe Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy +39 049 9719 111 Fax: +39 049 5841 257

While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2008 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.

Asia 7/F Dah Sing Financial Centre 108 Gloucester Road Wanchai Hong Kong 852 2572 2201 Fax: 852 2519 9210

SL-23315_REV03_07-09

Emerson Network Power. The global leader in enabling Business-Critical Continuity.

EmersonNetworkPower.com

Embedded Computing Embedded Power Power Switching & Controls

Services Racks & Integrated Cabinets Outside Plant

Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.

©2008 Emerson Electric Co.

Show 8 more labels / short text on this page
Single-Phase UPS · Three-Phase UPS · Environmental Systems · AC Power Connectivity · DC Power · Monitoring · Precision Cooling · Surge Protection
Sources

References & links

Pages referenced in this manual — manufacturer, support and downloads.

Fix-it

Troubleshooting

Common problems, likely causes, and what to do.

ProblemPossible causeRemedy
UPS will not startShort circuitCheck the circuit breaker on the rear of the UPS. If it is tripped, reset it and restart the UPS. For help, contact your local dealer, local Emerson representative or Channel Support Applications. p.30
UPS will not startBattery is disconnected or completely dischargedCheck for proper connection of battery or batteries. p.30
UPS starts on battery, but will not switch to AC (dark start)UPS not plugged inPlug in the power cord securely. p.30
UPS starts on battery, but will not switch to AC (dark start)Circuit breaker trippedReset the circuit breaker and restart the UPS. p.30
UPS starts on battery, but will not switch to AC (dark start)AC overvoltageWait until voltage drops to an appropriate level or have the utility power checked by a properly trained and qualified electrician. p.30
UPS shuts downShort circuit or UPS output is abnormal; LED 10 and LED 11 illuminate and sound audible alarmRemove the load and turn on the UPS again. For help, contact your local dealer, local Emerson representative or Channel Support Applications. p.30
UPS shuts downOverload; LED 5 and LED 11 illuminate and sound audible alarmCheck load level display and remove nonessential loads. Recalculate the load and reduce equipment connected to UPS - the total wattage must not exceed the capacity of the UPS. p.30
UPS shuts downLED 3 and LED 11 illuminate and sound audible alarmRecharge the battery for 8 hours, then turn ON the UPS. p.30
UPS shuts downLiebert MultiLink softwareConsult the Liebert MultiLink user manual or contact your LAN administrator. p.30
Site Wiring Fault LED (LED 4) flashingSite Wiring Fault, UPS detected a line-to-neutral reversal or a loss of proper grounding.Have the utility checked by a properly trained and qualified electrician. p.30
Battery weak LED (LED 3) flashingBatteries weakRecharge batteries. p.30
Battery weak LED (LED 3) flashingBatteries need to be replacedReplace batteries. p.30

Ask about the Emerson 2200

Owners and our team usually reply within a day — and your question helps the next person too.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
No questions yet about the Emerson 2200

Be the first to ask — other owners or our team will answer.