4.0 OPERATION 22
4.1 Startup Checklist for the Liebert GXT3 22
4.2 Starting the UPS 22
4.3 Manual Battery Test 22
4.4 Manual Bypass 22
4.5 Shut Down the Liebert® GXT3™ 23
4.6 Disconnecting Input Power from the Liebert GXT3 23
5.0 COMMUNICATION 24
5.1 Liebert IntelliSlot Communication Cards 24 5.1.1 Liebert MultiLink 24
5.2 USB Port Communication 25 5.2.1 Configuration Program 25
5.3 Terminal Block Communication 26 5.3.1 Any-Mode Shutdown 26 5.3.2 Battery Mode Shutdown 27 5.3.3 On Battery 27 5.3.4 Low Battery 27
6.0 MAINTENANCE 28
6.1 Replacing the Internal Battery Pack 28 6.1.1 Battery Replacement Procedures 28
6.2 Battery Charging 30
6.3 Precautions 30
6.4 Checking UPS Status 30
6.5 Checking UPS Functions 30
7.0 TROUBLESHOOTING 31
7.1 UPS Symptoms 31 7.1.1 Indicators 31 7.1.2 Audible Alarm 32
7.2 Troubleshooting 32
8.0 BATTERY CABINET 34
9.0 SPECIFICATIONS 35
9.1 Product Warranty Registration 39




! WARNING Observe all cautions and warnings in this manual. Failure to do so may result in serious injury or death. Refer all UPS and battery service to properly trained and qualified service personnel. Do not attempt to service this product yourself. Opening or removing the cover may expose you to lethal voltages within this unit even when it is apparently not operating and the input wiring is disconnected from the electrical source. Never work alone.
This manual contains important safety instructions that must be followed during the installation and maintenance of the UPS and batteries. Read this manual thoroughly before attempting to install or operate this UPS.
UPS Safety Notes This UPS contains no user-serviceable parts except the internal battery pack. The Off/Bypass push button does not electrically isolate internal parts. Under no circumstances attempt to gain internal access other than to replace the batteries due to risk of electric shock or burn. Do not continue to use the UPS if the front panel indications are not in accordance with these operating instructions or if the UPS performance alters in use. Refer all faults to your local dealer, Emerson Network Power representative or Emerson Network Power Channel Support. This UPS has an internal battery, and the output receptacles of the UPS may carry live voltage even if the UPS is not connected to utility input power. Before moving or rewiring this UPS, disconnect utility input power and the battery and make sure that the UPS is completely shut down. Otherwise, the output terminal may carry live voltage, presenting an electric shock hazard. To ensure human safety and normal UPS operation, the UPS must be properly grounded before use. When the UPS is connected to an IT power distribution system, a short-circuit protection device must be installed on the neutral line. Install and use the Liebert® GXT3™ in the following environments:

The Liebert® GXT3™-3000RT208 was tested under 20A branch circuit in accordance with the National Electrical Code, ANSI/NFPA 70. To reduce the risk of fire, connect only to a circuit provided with 20A maximum branch overcurrent protection.
! CAUTION Do not dispose of batteries in a fire. The batteries may explode. Do not open or mutilate the batteries. Released electrolyte is toxic and is harmful to skin and eyes. Dispose of used batteries according to the instructions.
ELECTROMAGNETIC COMPATIBILITY—The Liebert GXT3 complies with the limits for a CLASS A DIGITAL DEVICE, PURSUANT TO Part 15 of FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference and (2) this device must accept any interference received, including interference that may cause undesired operation. Operating this device in a residential area is likely to cause harmful interference that users must correct at their own expense.
The Liebert GXT3 series complies with the requirements of EMC Directive 2004/108/EC and the published technical standards. Continued compliance requires installation in accordance with these instructions and use of accessories approved by Emerson.
UPS Servicing: UPS makes use of components dangerous for the environment (electronic cards, electronic components). The components removed must be taken to specialized collection and disposal centers.

Risk of electrical shock
Indicates caution followed by important instructions
Requests the user to consult the manual
Indicates the unit contains a valve-regulated lead acid battery
WEEE

The Liebert® GXT3™ is a compact, online uninterruptible power system (UPS) that continuously conditions and regulates its output voltage. The Liebert GXT3 is designed to supply microcomputers and other sensitive equipment with clean sine wave input power.
Upon generation, AC power is clean and stable. However, during transmission and distribution it is subject to voltage sags, spikes and complete failure that may interrupt computer operations, cause data loss and damage equipment.
The Liebert GXT3 protects equipment from these disturbances. The Liebert GXT3 continuously charges its batteries from utility power, enabling it to supply power to connected loads, even when utility power fails.
This sections describes the UPS, its features, models, appearance and components, operating principles and operating mode.
Eight UPS models are available.
Product Description

The Liebert® GXT3™ rack/tower and minitower models in various power ratings have the same general appearance, controls and features (see Figure 1). The various rack/tower and minitower models differ largely in the type of receptacles each has.

The Liebert GXT3-1000MT120™ has the same controls and features in a minitower arrangement (see Figure 2).

The rear panel of the Liebert GXT3 has these features:


Battery Connector Terminal Block Communication






The operating principle of the UPS is illustrated in Figure 6.
TVSS & EMI/
Rectifier /
Inverter
RFI Filters
PFC
DC-to-DC Converter
Battery Charger
Battery
L2/N
L2/N
G G
The UPS is composed of utility input, TVSS and EMI/RFI filters, rectifier/PFC, inverter, battery charger, DC-to-DC converter, battery, dynamic bypass and UPS output.
The Liebert® GXT3™ has surge protection and filters that protect the connected load from power surges, electromagnetic interference (EMI) and radio frequency interference (RFI). These features can minimize any surges or interference present in the utility power. The filters also prevent surges or interference generated by the UPS from adversely affecting devices connected on the same branch as the UPS.
In normal operation, the Liebert GXT3’s rectifier/power factor correction (PFC) circuit converts utility power to regulated DC power for use by the inverter while ensuring that the wave shape of the input current used by the UPS is near ideal. Extracting this sinewave input current achieves two objectives:
This results in cleaner power being available to other devices in the building not being protected by the Liebert GXT3.
In normal operation, the Liebert GXT3’s inverter utilizes the DC output of the PFC to produce precise, regulated sine wave AC power. When utility power fails, the inverter receives DC power from the DC-to-DC Converter. In either operation mode, the UPS inverter is online, continuously generating clean, precise, regulated AC output power.

The battery charger utilizes energy from the utility power and precisely regulates it to continuously float charge the batteries. The batteries are being charged whenever the Liebert® GXT3™ is plugged in, even when the UPS is not turned On.
The DC-to-DC converter raises the DC voltage from the battery to the optimum operating voltage for the inverter. This allows the inverter to operate continuously at its optimum efficiency and voltage, thus increasing reliability.
The Liebert GXT3 uses valve-regulated, nonspillable, lead acid batteries. To maintain battery design life, operate the Liebert GXT3 in an ambient temperature of 32°F to 77°F (0°C to 25°C).
Optional external battery cabinets are available to extend battery run times.
The Liebert GXT3 provides an alternate path for utility power to the connected loads in the unlikely event of a UPS malfunction. Should the Liebert GXT3 have an overload, overtemperature or UPS failure condition, the UPS automatically transfers the connected loads to bypass.
The UPS operation modes include: Utility (AC) mode, bypass mode, battery mode, battery recharge mode and frequency converter mode.
For the descriptions of indicators and control buttons in this section, refer to 3.0 - Controls and Indicators.
During Utility (AC) Mode, utility power provides energy to the Liebert GXT3. The filters, PFC circuit and the inverter process this power to provide computer-grade power to connected loads. Meanwhile, the UPS maintains the batteries in a fully charged state.
Manual Bypass Mode occurs when the Standby/Manual bypass button is pressed and held for about 2 seconds while the Liebert GXT3 is in Utility (AC) Mode. Bypass operation is indicated by an audible alarm and illuminated amber bypass indicator (If other indicators are illuminated, refer to 7.0 - Troubleshooting). During manual bypass mode, utility power bypasses the inverter and provides energy to the connected load.
Turning Off the UPS in bypass mode will result in loss of output power and dropped loads.
Product Description

The Liebert® GXT3™ enters Battery Mode when utility power fails or is outside acceptable values. The battery system supplies power through the DC-to-DC converter to the inverter to generate clean AC power for the connected loads.
When the Liebert GXT3 enters Battery Mode, the UPS sounds a half-second beep at 10-second intervals. When approximately 2 minutes of run time remains, the beeps sound every 5 seconds to warn that the battery is getting low (this Low Battery Warning is user-configurable).
In Battery Mode, the AC Input indicator goes Off and the Battery Level indicators illuminate. Each battery level indicator represents a 20% capacity level. As capacity decreases, fewer indicators remain illuminated. Refer to 7.0 - Troubleshooting.
For approximate battery run times, refer to 9.0 - Specifications.
Turning Off the Liebert GXT3 when it is in Battery Mode will result in loss of output power. If the UPS is turned Off manually, it must be manually restarted after utility power returns. If the UPS is turned Off by a communication signal or because the batteries are depleted, it will operate as selected in the configuration program for Auto-Restart (Refer to 5.2.1 - Configuration Program).
Once utility power is applied to the Liebert GXT3, the Battery Charger begins charging the batteries.
All models of the Liebert GXT3 are capable of frequency conversion. Frequency Conversion Mode can be selected using the configuration program. Allowable frequency operating modes include:
The default for all models of the Liebert GXT3 is “Auto Sensing - 50Hz or 60Hz – Bypass Enabled.”
Product Description

2.1 Unpacking and Inspection
Unpack the UPS and conduct the following checks:
Maintain at least 4 inches (100mm) clearance in the front and rear of the Liebert GXT3. Do not obstruct the air inlets on the front panel and rear panel of the UPS; blocking the air inlets reduces ventilation and heat dissipation, shortening the service life of the Liebert GXT3.
Installation

The Liebert® GXT3™ may be installed as a tower or in a rack, depending on space and use considerations. The Liebert GXT3 may be used alone, as a single UPS, or with up to four battery cabinets.
To install the Liebert GXT3 as a tower:


2. If optional Liebert external battery cabinets will be connected to the Liebert GXT3, take out the spacers shipped with the battery cabinet. 3. Connect the spacers and the support bases as shown in Figure 7. Each Liebert GXT3 needs two assembled support bases, one in the front and one in the rear. 4. Adjust the direction of the operation and display panel and logo on the Liebert GXT3. a. Remove the front plastic bezel cover as shown in Figure 8.

b. Pull the operation and display panel gently, rotate it 90 degrees clockwise and snap it back into position, as shown in Figure 9.


Operation and Display Panel Rotated Clockwise 90 Degrees
c. Pull the logo on the front plastic bezel cover gently, rotate it 90 degrees clockwise and snap it back into position. The rotated front plastic bezel cover is shown in Figure 10. d. Replace the front plastic bezel cover on the Liebert® GXT3™. At this point, the UPS operation and display panel and logo have been rotated 90 degrees clockwise, which provides upright viewing for users. 5. Place the Liebert GXT3 and any battery cabinets on the support bases. Each Liebert GXT3 needs two support assemblies, as shown in Figure 10.


Rotated for Tower Operation

NOTE
To install a Liebert GXT3 rack/tower UPS in a rack:

! CAUTION Reduce the risk of tipping the rack by installing the Liebert GXT3 as low as possible in the rack.

Installation



Installation



The UPS should move smoothly into slide rail assemblies. If not, recheck alignment of front and rear members from Steps 4 through 6.
Factory-supplied rack handles are not intended to be used to lift the UPS. These are intended to be used to slide the UPS into and out of the rack.
Installation

The Liebert® GXT3™ rear panel has an input cable and plug, output receptacles and output cable(s) (Output cables are on GXT3-3000 models only). Refer to 1.3.2 - Rear Panel Features for details. The battery cables are supplied with the battery cabinet.
Prepare an input power supply that is properly protected by a circuit breaker in accordance with national and local electrical codes. The wall receptacle must be grounded.
The plug on the power supply cord is intended to serve as the disconnect device. The socket-outlet must be installed near the equipment and must be easily accessible.
Emerson recommends installing an upstream circuit breaker of the same series as the Liebert GXT3’s input circuit breaker.
The specification of input circuit breaker on the rear panel of UPS is given in Table 2.
GXT3-500RT120 8A
GXT3-700RT120 10A
GXT3-1000RT120 15A
GXT3-1000MT120 15A
GXT3-1500RT120 15A
GXT3-2000RT120 20A
GXT3-3000RT120 30A
GXT3-3000RT208 20A
2.5.2 Connecting Battery Cables 1. Switch Off the input breaker of the battery cabinet. 2. Take out the battery cable included with the battery cabinet. 3. Connect one end of the battery cable to the external battery connector on the rear panel of the UPS, and connect the other end to any battery port on the rear panel of the battery cabinet. 4. Switch On the battery breaker on the rear of the external battery cabinet. 5. Use the Configuration Program included with the UPS to specify the number of external battery cabinets connected to the Liebert GXT3. See Table 15 for approximate battery run times.

Communication cable connection includes: USB and cables for option cards.
2.6.1 Connecting USB Communication Cables 1. Take the USB communication cables out of the accessories box. 2. Insert one end of the USB communication cable to the USB port on the rear panel of the Liebert® GXT3™ (see Figures 3 and 5). 3. Insert the other end of the USB communication cable to the USB port of the computer.
2.6.2 Installing the Optional Liebert IntelliSlot® Card and Communication Cables 1. Remove the protective cover of the Liebert IntelliSlot port on the Liebert GXT3 and set it aside. 2. Insert the Liebert IntelliSlot card into the Liebert IntelliSlot port and secure it with screws. 3. To connect any cable associated with a Liebert IntelliSlot card, refer to the user manual provided with the card.
To configure and use the Liebert IntelliSlot communication card, refer to the card’s user manual. Manuals for the various Liebert IntelliSlot cards are available at Liebert’s Web site: www.liebert.com
Installation

The operation and display panel, shown in Figure 18, is on the front panel of the Liebert® GXT3™ (see Figures 1 and 2).

The operation and display panel has two control buttons: On/Alarm Silence/Manual Battery Test and Standby/Manual bypass.
The On/Alarm Silence/Manual Battery Test button controls output power to connected load(s) and has three functions (see Table 3).

ON Press the button once for 3 seconds To start the UPS
Alarm Silence 1 Press the button for at least half a second To silence alarms 2
Manual Battery Test Press the button for at least half a second while operating in Utility (AC) Mode with no alarms present. To initiate a manual battery test
The Standby/Manual Bypass button controls output power to connected load(s) and has two functions (see Table 4).

Manual Bypass Press the button once and hold it for about 2 seconds 1 To initiate a manual transfer of the connected loads to the internal bypass, if available
Standby Press the button twice within four seconds while the UPS is in Manual Bypass or Battery Mode 2 To shut down the UPS and shut Off all power to the connected loads
Controls and Indicators

The operation and display panel has seven indicators (see Figure 18). The indicators can be divided into two groups according to the applications: level indicators and UPS status indicators.
Battery Level Indicators
The battery level indicator is composed of five sets of LED bars that illuminate and flash to indicate the battery capacity level. The Liebert® GXT3™ battery capacity level is shown in 20% increments (±5%). The battery level indicators will illuminate as shown in Figure 19.

The load level indicator is composed of five LED bars that illuminate to indicate the relative load on the UPS output in 25% increments (± 5%). The load level indicator will illuminate as shown in Figure 20.

Controls and Indicators

UPS status is indicated by five symbols: fault indicator, AC input indicator, battery indicator, inverter indicator and bypass indicator. Table 5 shows the symbols and their meaning.
Indicator Icon Color Description
Fault Indicator Red On if the UPS has detected a fault; Off if there is no fault
AC Input Indicator Green On when the utility input power is normal; Off during utility failure; flashing when utility power is outside specifications
Battery Indicator Amber On when the battery is supplying power; Off when the battery is not supplying power
Inverter Indicator Green On when the inverter is supplying power; Off when the inverter is not supplying power
Bypass Indicator Amber On when the bypass is supplying power; Off when the inverter is not supplying power; and flashing when utility power is outside specifications
Controls and Indicators · UPS Status

This section describes checks to be made before starting the UPS, how to start the UPS, manual battery test, manual bypass, shutting down the UPS and disconnecting the utility power from the UPS.
Before starting the UPS, perform these checks:
___ 1. Check that the input plugs and loads are connected properly and reliably.
___ 2. Check that all of the battery cables are connected properly.
___ 3. Check that the communication cables are connected properly.
4.2 Starting the UPS 1. Turn On the input circuit breaker—see Figures 3 and 5 for its location. 2. Turn On the UPS by pressing the On/Alarm Silence/Manual Battery Test button for three seconds. After the button is pressed, the LEDs on the display will signal that the unit has initiated the startup process. 3. Once the inverter LED has been illuminated, turn On the connected loads. 4. Check the status indicators to determine whether the Liebert GXT3 is operating normally. 5. Check the load level indicators to verify that the connected load does not exceed the UPS’ rated capacity.
The UPS is now providing conditioned power to the load.
To initiate a manual battery test, press the On/Alarm Silence/Manual Battery Test button for at least half a second while operating from utility power with no alarm conditions present.
Press the Standby/Manual Bypass button once while the UPS is in utility (AC) mode and hold it for about 2 seconds. The UPS will transfer the connected loads to the internal bypass. If the internal bypass is not available due to utility power problems, pressing this button once will be ignored. Bypass operation is indicated by an audible alarm and illuminated amber Bypass indicator. If other indicators are illuminated, refer to 7.0 - Troubleshooting.
Operation

Power to the connected loads is now Off.
4.6 Disconnecting Input Power from the Liebert GXT3 1. Once the UPS has been shut down as detailed in 4.5 - Shut Down the Liebert® GXT3™, disconnect the input cable plug. 2. Wait 30 seconds and verify that all indicators have turned Off and the fan has stopped; this indicates that the power-off is complete. 3. Turn the external battery cabinet breaker switch to the Off position if the UPS has an external battery cabinet.
After powering Off the UPS, the UPS ceases output and the load is powered Off.
Operation

This section describes UPS communication over the three types of communication connections on the rear of the Liebert® GXT3™:
! CAUTION To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables should be segregated and run separate from all other power cables.
The Liebert IntelliSlot port accepts three optional cards:
The Liebert IntelliSlot SNMP Card provides SNMP monitoring and control of the UPS across the network.
The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom-wired applications and delivers support for built-in shutdown for AS/400 systems.
The Liebert IntelliSlot 485 Card is used to connect the UPS and computer system.
Follow instructions provided with the Liebert IntelliSlot card to configure Liebert MultiLink®, the UPS or any additional ancillary product for the Liebert GXT3. These instructions are available at
5.1.1 Liebert MultiLink
Liebert MultiLink monitors the UPS continuously and can shut down your computer or server in the event of an extended power failure. Liebert MultiLink can also be configured to shut down the UPS.
Liebert’s MultiLink can also be configured for use without the USB cable when the Liebert IntelliSlot SNMP Card or Liebert IntelliSlot Web Card is installed in the UPS. An optional Liebert MultiLink License Kit permits shutting down the UPS over a network.
For more information about the Liebert IntelliSlot SNMP Card, Liebert IntelliSlot Web Card and Liebert MultiLink license kits, visit the Liebert Web site (www.liebert.com) or contact your local Emerson representative.
Communication

The standard B-type USB port is used to connect the UPS and network server or other computer system using Liebert® MultiLink®. Configuration program can be accessed through the communication port.
Accessing the Configuration Program via USB is a new feature of the Liebert GXT3™. For most users, the factory default settings will be adequate. This section illustrates the features available for modification, as well as the factory default setting.
The USB configuration program allows these features of the Liebert GXT3 to be changed:
Factory Default, VAC Output Voltage Option, VAC
GXT3-500RT120 - GXT3-3000RT120 GXT3-1000MT120 120 110, 115, 120 and 127
GXT3-3000RT208 208 208 / 220 / 230 / 240
The output voltage settings cannot be changed while the UPS is On and powering connected loads.
Communication · UPS Model

The Terminal Block includes eight pins, as shown in Figure 21.

The purpose of Any Mode Shutdown is to shut down the UPS output by turning Off the rectifier, inverter and bypass so that there is no power to the loads.
Any Mode Shutdown can be operated locally and remotely, as described as follows:
A current-limited source for this optocoupler (+12VDC, 50mA) will be available from the UPS.
The connection to the UPS for remote connection will be via terminal block connector.
Any Mode Shutdown wiring must conform to all national, regional and local wiring regulations.
! WARNING When the Auto-Enable output option is selected and the UPS output is disabled using Pin 1 and Pin 2, the Liebert® GXT3™’s output can turn On automatically and without warning if the Pin 1 and Pin 2 connection is changed.
Communication

Battery Mode Shutdown permits shutting down the UPS by turning Off the rectifier, inverter and bypass so that there is no power to the load when the UPS is On Battery.
Battery Mode Shutdown can be performed locally or remotely:
A current-limited source for this optocoupler (+12VDC, 50mA) will be available from UPS.
The connection to the Liebert® GXT3™ for remote connection will be via terminal block connector.
Battery mode shutdown wiring must conform to all national, regional and local wiring regulations.
This signal must last for 1.5 seconds or longer.
A battery shutdown signal will not cause an immediate shutdown. It will start a 2 minute shut down timer. This timer cannot be stopped once triggered. If utility power returns during this countdown, the Liebert GXT3 will still shut down and must remain shut down for 10 seconds. Whether the UPS turns back On when the power is restored depends on the auto-restart setting.
On Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power from the battery this dry contact will be closed.
Low Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power from the battery and has reached the Low Battery Warning time selected in the configuration program, this dry contact will be closed.
Communication

This section describes replacing the internal battery pack, precautions, checking the Liebert® GXT3’s status and checking UPS functions.
The Liebert® GXT3™ is designed to allow the user to replace the internal battery pack safely. Refer to Table 7 for internal battery pack part numbers for Liebert GXT3™ UPS:
Liebert GXT3-500RT120 GXT3-5A48BATKIT 1
Liebert GXT3-700RT120 GXT3-5A48BATKIT 1
Liebert GXT3-1000RT120 GXT3-5A48BATKIT 1
Liebert GXT3-1000MT120 GXT3-1MTBATKIT 1
Liebert GXT3-1500RT120 GXT3-7A48BATKIT 1
Liebert GXT3-2000RT120 GXT3-9A48BATKIT 1
Liebert GXT3-3000RT120 GXT3-9A72BATKIT 1
Liebert GXT3-3000RT208 GXT3-9A72BATKIT 1
Read all safety cautions before proceeding. Contact your local dealer or Emerson representative to obtain the part number and pricing of the appropriate replacement battery pack.
! CAUTION Risk of explosion if battery is replaced by an incorrect type. Dispose of used batteries according to the instructions.
6.1.1 Battery Replacement Procedures 1. Remove the front plastic bezel cover from the UPS. 2. Loosen and remove the six screws on the battery door, as shown in Figure 22. 3. Lay the battery door and screws aside for reassembly.



Battery Connector Battery Receptacle

Pull Out with Battery Handle
6. Unpack the new internal battery pack. Take care not to destroy the packing. Compare the new and old internal battery pack to make sure they are the same type and model. If so, proceed with Step 7; if they are different, stop and contact your local Emerson representative, or Emerson Channel Support. 7. Line up and slide in the new internal battery pack. 8. Reconnect the battery plug and battery receptacle 9. Push the battery wire and internal battery pack back into the UPS. 10. Reattach the front battery door with the six screws. 11. Reattach the front plastic bezel cover to the UPS.

The batteries are valve-regulated, nonspillable, lead acid and should be kept charged to attain their design life. The Liebert® GXT3™ charges the batteries continuously when it is connected to the utility input power.
If the Liebert GXT3 will be stored for a long time, Emerson recommends connecting the UPS to input power for at least 24 hours every four to six months to ensure full recharge of the batteries.
Although the Liebert GXT3 has been designed and manufactured to ensure personal safety, improper use can result in electrical shock or fire. To ensure safety, observe the following precautions:
Emerson recommends checking the UPS operation status every six months.
Emerson recommends checking the UPS functions once every six months.
Back up the load data before conducting the UPS functions check. Procedures are as follows:
Maintenance

This section indicates various UPS symptoms a user may encounter and troubleshooting steps in the event the UPS develops a problem. Use the following information to determine whether external factors caused the problem and how to remedy the situation.
The following symptoms indicate the Liebert® GXT3™ has malfunctions.
In addition to the fault indicator being illuminated, one or more of LED segments of battery level indicator will also be illuminated to provide a diagnostic aid to the user, as shown in Figure 25. The descriptions are listed in Table 8.
A B C D E
Table 8 Indicator descriptions
A - E On bypass from output overload (half-second beep every half-second)
A On bypass due to overtemperature condition (1-second beep every 4 seconds)
B On bypass due to DC bus overvoltage (1-second beep every 4 seconds)
C On bypass due to DC/DC power supply failure (1-second beep every 4 seconds)
D On bypass due to PFC failure (1-second beep every 4 seconds)
E On bypass due to inverter failure (1-second beep every 4 seconds)
A&B UPS Failure (includes dual-fan failure, single-fan failure under certain conditions and battery charger failure) and continuous alarm
A&C UPS failed battery test (2-second beep every60 seconds)
A&E Bypass feedback (1-second beep every 4 seconds)
B&E Short circuit on the output
C&E UPS shutdown by command from communication (USB port or Liebert IntelliSlot™ port) (no audible)
Utility LED flash L-N reverse
Battery not connected (continuous horn); check battery connection, power down and restart UPS
Flashing Utility power voltage or frequency is out of tolerance; bypass is unavailable
Indicators A - E are shown in Figure 25. If the UPS experiences an overload, the UPS will transfer from bypass back to inverter approximately 5 minutes after the overload ends.

An audible alarm will be used in conjunction with the visual indicators to indicate to the user a change in UPS operating status. The audible alarm will enunciate as given in Table 9.
Battery discharge half-second beep every 10 seconds
Low battery Two half-second beeps every 5 seconds
UPS fault, load on bypass 1-second beep every 4 seconds
UPS fault, no power to load Continuous
Overload half-second beep every half second
Battery replacement 2-second beep every 60 seconds
Wiring problem (including line-to-neutral reversal or a loss of proper grounding for UPS) Continuous
Bypass reminder 1-second beep every 2 minutes
In the event of an issue with the UPS, refer to Table 10 to determine the cause and solution. If the issue persists, contact Emerson Channel Support.
Ensure UPS is Off. Disconnect all loads and ensure nothing is lodged in output receptacles. Ensure loads are not defective or shorted internally.
UPS fails to start when the On/Alarm Silence/Manual Battery Test button is pressed
UPS is short-circuited or overloaded
UPS is operating from battery mode, ensure UPS is securely plugged into the wall receptacle.
UPS not plugged in
UPS is operating from battery mode. Save data and close applications. Reset UPS input breaker, then restart UPS.
UPS input protection circuit breaker has opened
Battery indicator is illuminated
UPS is operating from battery mode. Save data and close applications. Ensure utility supply voltage is within acceptable limits for UPS.
Utility power is out of tolerance
Batteries are not fully charged Keep UPS plugged in continuously at least 24 hours to recharge batteries.
UPS is overloaded Check load level indicator and reduce the load on the UPS.
UPS has reduced battery backup time
Replace batteries. Contact your local dealer, Emerson representative or Emerson Channel Support for replacement battery kit.
Batteries may not be able to hold a full charge due to age
Check load level indicator and remove non- essential loads. Recalculate the load and reduce number of loads connected to UPS. Check load for faults.
Fault and Bypass indicators and all LED segments of battery level indicator are illuminated
UPS overloaded or load is faulty
Ensure UPS is not overloaded, ventilation holes not blocked, or room ambient temperature is not excessive. Wait 30 minutes to allow UPS to cool, then restart UPS. If UPS will not restart, contact your local dealer, Emerson representative or Emerson Channel Support.
Fault and Bypass indicators and diagnostic A indicator are illuminated
UPS shutdown due to overtemperature condition. Load is on bypass power

Fault and Bypass indicators and diagnostic B indicator are illuminated
UPS internal DC bus overvoltage UPS requires service. Contact Emerson Channel Support.
Fault and Bypass indicators and diagnostic C indicator are illuminated
UPS DC/DC fault UPS requires service. Contact Emerson Channel Support
Fault indicator and diagnostic D indicator are illuminated
UPS PFC (Power Factor Correction Circuit) fault
UPS requires service. Contact Emerson Channel Support
Fault and Bypass indicators and diagnostic E indicator are illuminated
UPS inverter fault UPS requires service. Contact Emerson Channel Support
Replace batteries. Contact your local dealer, Emerson representative or Emerson Channel Support
Fault indicator and diagnostic A and C indicators are illuminated UPS failed the battery test
Your UPS has received a signal or command from the attached computer. If this was inadvertent, ensure the communication cable used is correct for your system. For assistance, contact your local dealer, Emerson representative or Emerson Channel Support
Fault and Bypass indicators and diagnostic C and E indicators are illuminated
UPS shut down by a command from the communications port(s)
UPS Failure (Includes Dual Fan failure, single fan failure under certain condition and Battery Charger Failure) and continuous alarm
Fault indicator and diagnostic A and B indicators are illuminated
Ensure fan is not blocked. If the fault is not removed, contact your local dealer, Emerson representative or Emerson Channel Support
UPS detected a line-to-neutral reversal or a loss of proper grounding for UPS; continuous alarm and UPS will not start in standby status. This is active only when power is first applied to the input. Once the UPS is running, the AC input indictor will flash, unless the input wiring is correctly changed
AC input indicator is flashing
Contact a qualified electrician to verify site wiring
Check battery connections, completely power down and restart UPS. NOTE: If the battery circuit opens while the UPS is running, it will be detected when the next battery test is performed
Battery indicator is flashing Battery source is not available; continuous alarm
The AC input powers the PFC input and serves as the bypass source. If the AC is present but the voltage or frequency exceeds the acceptable range for safe operation with a load, the bypass will be disabled and this indicator will flash, indicating that the bypass is unavailable
Because the voltage or frequency is outside acceptable limits, the bypass is disabled
Bypass indicator is flashing
When reporting a UPS issue to Emerson, include the UPS model and serial number. These are on the top panel of the Liebert® GXT3™.
Troubleshooting · Problem Cause Solution

Optional battery cabinets are available for the Liebert® GXT3™. The battery connectors and input breaker are on the battery cabinet’s rear panel, as shown in Figure 26. For battery cabinet specifications, refer to Table 13. The Liebert GXT3 may be equipped with a maximum of four extension battery packs.
For battery run times, refer to Table 15.

! WARNING Do not contact the battery connectors and ground without wearing protective gloves and clothing and taking other precautions against electrical shock. The battery loop and AC input are not insulated, which may cause a dangerous voltage between the battery connectors and ground.
Battery Cabinet · Input Breaker · Battery Connectors

GXT3-500RT120
GXT3-700RT120
GXT3-1000RT120
GXT3-1000MT120
(500VA/450W)
(700VA/630W)
(1000VA/900W)
(1000VA/900W)
Dimensions, D × W × H, in. (mm)
Unit 19.7 x 16.9 x 3.4 (497 × 430 × 85)
15.4 x 6.9 x 8.9 (390 × 175 × 225)
Shipping 25.5 x 23.9 x 10.6 (647 x 607 x 270)
22.1 x 12.9 x 14 (562 × 327 × 355)
Unit 37 (16.8) 37.5 (17)
Shipping 44.1 (20) 36 (16.5)
Voltage Range (typical) 120VAC nominal; variable based on output load
90% ~ 100% loading 90VAC/140VAC
70% ~ 90% loading 86VAC/140VAC
30% ~ 70% loading 77VAC/140VAC
0 ~ 30% loading 60VAC/140VAC
Frequency 40Hz ~ 70Hz; Auto Sensing
Input Power Cord 10 ft. attached w/ NEMA 5-15P plug
Output Receptacles 5-15R × 6
Voltage 110/115/120VAC (user-configurable); ±3%
Utility (AC) Mode Overload 200% for 2 seconds; 150% for 50 seconds with transfer to bypass
Type Valve-regulated, nonspillable, lead acid
Qty × V× Rating 4 × 12V × 5.0Ah
Battery Mfr./Part # YUASA/NPH5-12; CSB/ HR 1221W; CSB/GP1245
Backup Time See Table 15
Recharge Time 3 Hours to 90% capacity after full discharge with 100% load till UPS auto-shutdown (Internal Batteries Only)
Operating Temperature, °F (°C) 32 to 104 (0 to 40); see Table 14 - Operating temperature parameters
Storage Temperature, °F (°C) 5ºF to 122ºF (-15ºC to 50ºC)
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to 10,000 ft. (3000m) at 77ºF (25ºC) without derating
Storage Elevation 50,000 ft. (15000m) maximum
Audible Noise
< 50 dBA, at 3ft. (1m) rear < 45 dBA, at 3ft. (1m) front and sides
Safety UL 1778, cUL Listed
RFI/EMI FCC Part 15, Class A=CISPR22 Class B
Surge Immunity IEC 62040-2 2nd Ed
Transportation ISTA Procedure 1A

GXT3-1500RT120
GXT3-2000RT120
GXT3-3000RT120
GXT3-3000RT208
(1500VA/1350W)
(2000VA/1800W)
(3000VA/2700W)
(3000VA/2700W)
Dimensions, D × W × H, in. (mm)
Unit 19.7 x 16.9 x 3.4 (497 × 430 × 85)
23.7 x 16.9 x 3.4 (602 × 430 × 85)
Shipping 25.5 x 23.9 x 10.6 (647 x 607 x 270)
29.4 x 23.4 x 10.6 (747 x 607 x 270)
Weight, lb. (kg)
Unit 51.1 (23.2) 56.1 (25.5) 71.4 (32.4)
Shipping 57.3 (26) 61.7 (28) 77 (35)
Voltage Range (typical) 120VAC nominal; variable based on output load 208VAC nominal; variable based on output load
Frequency 40 - 70Hz; Auto Sensing
Input Power Cord 10 ft. attached w/ NEMA 5-15P plug
10 ft. attached w/ NEMA 5-20P plug
10 ft. attached w/ NEMA L5-30P plug
10 ft. attached w/ NEMA L6-20P plug
Output Receptacles 5-15R × 6 5-20R × 6 L5-30R×1+5-20R×6 L6-20R×1+L6-15R×2
Voltage 110/115/120VAC (user-configurable); ±3% 208/220/230/240 VAC (user-configurable); ±3%
Utility (AC) Mode Overload 200% for 2 seconds 150% for 50 seconds 200% for 2 seconds 150% for 10 seconds
Type Valve-regulated, nonspillable, lead acid
Qty×V×Rating 4 × 12V × 7.2Ah 4 × 12V × 9.0Ah 6 × 12V × 9.0Ah 6 × 12V × 9.0Ah
Battery Mfr./Part # Panasonic/UP-RW1236
CSB/GP 1272 Panasonic/UP- RW1245; CSB/HR 1234W F2
Backup Time See Table 15
Recharge Time 3 Hours to 90% capacity after full discharge with 100% load till UPS auto-shutdown (Internal Batteries Only)
Operating Temperature, °F (°C) +32 to +104 (0 to 40); see Table 14 - Operating temperature parameters
Storage Temperature, °F (°C) 5 to +122 (-15 to 50)
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to 10,000 ft. (3000m) at 77ºF (25ºC) without derating
Storage Elevation 50,000 ft. (15000m) maximum
< 45dBA at 3ft (1m) rear
< 46 dBA at 3ft. (1m)
Safety UL 1778, c-UL Listed
RFI/EMI FCC Part 15, Class A=CISPR22 Class B
Surge Immunity IEC 62040-2 2nd Ed
Transportation ISTA Procedure 1A

GXT3-48VBATT GXT3-72VBATT
GXT3-500RT120,GXT3-700RT120 GXT3-1000RT120,GXT3-1500RT120,
GXT3-3000RT120 GXT3-3000RT208
GXT3-2000RT120
Dimensions, D × W × H, in (mm)
Unit 19.7 x 16.9 x 3.3 (497 × 430 × 85)
23.7 x 16.9 x 3.3 (602 × 430 × 85)
Shipping 24.3 x 22.4 x 10.3 (617 x 570 x 262)
28.2 x 22.4 x 10.3 (717 x 570 x 262)
Unit 57.3 (26) 83.8 (38)
Shipping 61.7 (28) 92.6 (42)
Type Valve-regulated, nonspillable, lead acid
Qty × V× Rating 2 × 4 × 12V × 9.0Ah 2 × 6 × 12V × 9.0Ah
Battery Mfr./Part # Panasonic/UP-RW1245; CSB/HR 1234W F2
Backup Time See Table 15
Operating Temperature, °F (°C) 32 to 104 (0 to 40)
Storage Temperature, °F (°C) 19 to 122 (-15 to 50) High ambient temperatures will reduce battery life.
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to 10,000 ft. (3000m) at 104ºF (40ºC) without derating
Storage Elevation 50,000 ft. (15000m) maximum
Safety UL 1778, c-UL Listed
RFI/EMI FCC Part 15, Class A=CISPR22 Class B
Surge Immunity IEC 62040-2 2nd Ed
Transportation ISTA Procedure 1A
Ambient Temperature, °C (°F) 25-30 (77-86) 30-35 (86-95) 35 - 40 (95-104)
Maximum Output Power Factor Derating @ Maximum Load

120VAC RT Models 208 VAC RT Model
10% 128 105 90 77 77 74 77
20% 82 61 37 35 33 36 37
30% 41 37 30 23 21 21 21
40% 38 32 23 16 15 15 15
50% 34 27 17 11
60% 31 22 14 10 8 8 8
70% 27 18 11 6
80% 23 15 9 5
90% 20 13 8 4
100% 17 11 7 4 3 3 3
10% 328 306 212 199 183 166 183
20% 209 182 151 133 124 121 123
30% 166 149 123 97 80 79 79
40% 152 130 100 72 41 53 53
Internal Battery + 1 External Battery Cabinet
50% 139 109 80 41 38 46 45
60% 125 98 68 38 34 39 38
70% 109 81 41 35 30 31 31
80% 100 72 39 32 25 26 26
90% 92 63 37 27 21 21 22
100% 79 41 35 23 17 18 18
10% 480 373 336 314 311 307 311
20% 334 313 214 188 161 159 160
30% 309 211 166 148 134 133 133
40% 216 185 151 126 105 105 104
Internal Battery + 2 External Battery Cabinets
50% 197 159 137 103 80 81 80
60% 167 149 122 82 67 68 67
70% 159 139 105 72 40 52 52
80% 152 128 95 62 38 47 47
90% 144 112 80 40 36 43 43
100% 137 104 73 38 33 38 38
10% 480 480 480 341 335 332 335
20% 401 341 321 227 206 203 205
30% 338 318 218 185 157 157 157
40% 322 224 191 154 139 139 138
Internal Battery + 3 External Battery Cabinets
50% 306 205 162 139 120 120 113
60% 219 186 152 123 99 100 100
70% 205 163 141 105 80 81 81
80% 191 155 131 93 70 71 71
90% 167 148 120 79 60 62 62
100% 162 140 106 71 40 51 51

120VAC RT Models 208 VAC RT Model
10% 480 346 480
20% 480 480 339 317 304 301 303
30% 398 337 315 216 188 187 187
40% 340 321 220 183 156 156 155
Internal Battery + 4 External Battery Cabinets
50% 328 304 199 157 141 142 141
60% 316 217 167 145 126 127 126
70% 304 202 159 133 107 108 108
80% 221 186 151 120 95 97 97
90% 210 164 143 105 79 81 81
100% 199 158 134 96 71 73 73
Times in this table are approximate. They are based on new, fully charged batteries with 100% resistive loads and an ambient temperature of 77°F (25°C). To increase this time, turn Off non-essential loads (such as idle computers and monitors) or add optional external battery cabinets.
To register for warranty protection, visit the Quick Links section of the Liebert® Web site at:
Click on Product Warranty Registration and fill in the form.
If you have any questions, contact Emerson Channel Support at:

Specifications



Ensuring The High Availability Of Mission-Critical Data And Applications.
Emerson Network Power, a business of Emerson (NYSE:EMR), is the global leader in enabling Business-Critical Continuity™
Web Site www.liebert.com
from grid to chip for telecommunication networks, data centers, health care and industrial facilities. Emerson Network Power provides innovative solutions and expertise in areas including AC and DC power and precision cooling systems, embedded computing and power, integrated racks and enclosures, power switching and controls, infrastructure management, and connectivity. All solutions are supported globally by local Emerson Network Power service technicians. Liebert AC power, precision cooling and monitoring products and services from Emerson Network Power deliver Efficiency Without Compromise™ by helping customers optimize their data center infrastructure to reduce costs and deliver high availability.
Monitoring liebert.monitoring@emerson.com
Single-Phase UPS & Server Cabinets
liebert.upstech@emerson.com
Three-Phase UPS & Power Systems
Locations United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229
Europe Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy +39 049 9719 111 Fax: +39 049 5841 257
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2010 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
Asia 29/F, The Orient Square Building F. Ortigas Jr. Road, Ortigas Center
Philippines +63 2 687 6615 Fax: +63 2 730 9572
Emerson Network Power. The global leader in enabling Business-Critical Continuity™ EmersonNetworkPower.com
Embedded Computing Embedded Power
Racks & Integrated Cabinets Services
Power Switching & Controls Precision Cooling
Infrastructure Management & Monitoring
Emerson, Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks of Emerson Electric Co. or one of its affiliated companies. ©2010 Emerson Electric Co.
Pages referenced in this manual — manufacturer, support and downloads.
Common problems, likely causes, and what to do.
| Problem | Possible cause | Remedy | |
|---|---|---|---|
| UPS fails to start when the On/Alarm Silence/Manual Battery Test button is pressed | UPS is short-circuited or overloaded | Ensure UPS is Off. Disconnect all loads and ensure nothing is lodged in output receptacles. Ensure loads are not defective or shorted internally. | p.38 |
| Battery indicator is illuminated | UPS not plugged in | UPS is operating from battery mode, ensure UPS is securely plugged into the wall receptacle. | p.38 |
| Battery indicator is illuminated | UPS input protection circuit breaker has opened | UPS is operating from battery mode. Save data and close applications. Reset UPS input breaker, then restart UPS. | p.38 |
| Battery indicator is illuminated | Utility power is out of tolerance | UPS is operating from battery mode. Save data and close applications. Ensure utility supply voltage is within acceptable limits for UPS. | p.38 |
| UPS has reduced battery backup time | Batteries are not fully charged | Keep UPS plugged in continuously at least 24 hours to recharge batteries. | p.38 |
| UPS has reduced battery backup time | UPS is overloaded | Check load level indicator and reduce the load on the UPS. | p.38 |
| UPS has reduced battery backup time | Batteries may not be able to hold a full charge due to age | Replace batteries. Contact your local dealer, Emerson representative or Emerson Channel Support for replacement battery kit. | p.38 |
| Fault and Bypass indicators and all LED segments of battery level indicator are illuminated | UPS overloaded or load is faulty | Check load level indicator and remove non- essential loads. Recalculate the load and reduce number of loads connected to UPS. Check load for faults. | p.38 |
| Fault and Bypass indicators and diagnostic A indicator are illuminated | UPS shutdown due to overtemperature condition. Load is on bypass power | Ensure UPS is not overloaded, ventilation holes not blocked, or room ambient temperature is not excessive. Wait 30 minutes to allow UPS to cool, then restart UPS. If UPS will not restart, contact your local dealer, Emerson representative or Emerson Channel Support. | p.38 |
| Fault and Bypass indicators and diagnostic B indicator are illuminated | UPS internal DC bus overvoltage | UPS requires service. Contact Emerson Channel Support. | p.39 |
| Fault and Bypass indicators and diagnostic C indicator are illuminated | UPS DC/DC fault | UPS requires service. Contact Emerson Channel Support | p.39 |
| Fault indicator and diagnostic D indicator are illuminated | UPS PFC (Power Factor Correction Circuit) fault | UPS requires service. Contact Emerson Channel Support | p.39 |
| Fault and Bypass indicators and diagnostic E indicator are illuminated | UPS inverter fault | UPS requires service. Contact Emerson Channel Support | p.39 |
| Fault indicator and diagnostic A and C indicators are illuminated | UPS failed the battery test | Replace batteries. Contact your local dealer, Emerson representative or Emerson Channel Support | p.39 |
| Fault and Bypass indicators and diagnostic C and E indicators are illuminated | UPS shut down by a command from the communications port(s) | Your UPS has received a signal or command from the attached computer. If this was inadvertent, ensure the communication cable used is correct for your system. For assistance, contact your local dealer, Emerson representative or Emerson Channel Support | p.39 |
| Fault indicator and diagnostic A and B indicators are illuminated | UPS Failure (Includes Dual Fan failure, single fan failure under certain condition and Battery Charger Failure) and continuous alarm | Ensure fan is not blocked. If the fault is not removed, contact your local dealer, Emerson representative or Emerson Channel Support | p.39 |
| AC input indicator is flashing | UPS detected a line-to-neutral reversal or a loss of proper grounding for UPS; continuous alarm and UPS will not start in standby status. This is active only when power is first applied to the input. Once the UPS is running, the AC input indictor will flash, unless the input wiring is correctly changed | Contact a qualified electrician to verify site wiring | p.39 |
| Battery indicator is flashing | Battery source is not available; continuous alarm | Check battery connections, completely power down and restart UPS. NOTE: If the battery circuit opens while the UPS is running, it will be detected when the next battery test is performed | p.39 |
| Bypass indicator is flashing | Because the voltage or frequency is outside acceptable limits, the bypass is disabled | The AC input powers the PFC input and serves as the bypass source. If the AC is present but the voltage or frequency exceeds the acceptable range for safe operation with a load, the bypass will be disabled and this indicator will flash, indicating that the bypass is unavailable | p.39 |