Nfinity™ Power System
U SER M ANUAL

60Hz 12 to 20 kVA




3.5 Main Menu 20
3.5.1 UPS Status Screen 21
3.5.2 UPS Configuration Screen 22
3.5.3 Display Date/Time 27
3.5.4 Event Log 28
3.5.5 Active Alarms 28
3.5.6 Transfer to Bypass 28
3.5.7 Module Replacement 29
3.5.8 Service Tools for Liebert Global Services Engineers 30
4.1 Active Alarms 31
4.2 Module LED Indication 33
4.3 Module Replacement 34
4.3.1 Removing Modules 34
4.3.2 Adding or Replacing Modules 35
4.3.3 Replacing the User Interface 35
5.1 Maintenance 36
5.1.1 Proper Care 36
5.1.2 Scheduled Maintenance 36
5.1.3 Replacing Fan Filters 36
6.1 Product Warranty Registration 37
Figure 1 Front and back views 4
Figure 2 REPO switch connections 15
Table 1 Nfinity weight and dimensions 4
Table 2 Guide to LEDs 33

SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be closely followed during installation and maintenance of this UPS unit and during the installation and replacement of Power and Battery Modules.
This product is designed for Commercial/Industrial use only. This product is not intended for use with life support and other U.S. FDA-designated “critical” devices. Maximum load must not exceed that shown on the UPS rating label.
! WARNING Lethal voltages may be present within this unit even when it is apparently not operating. Observe all cautions and warnings in this manual. Failure to do so MAY result in serious injury or death. Never work alone.
Observe the following precautions when working with batteries:
! CAUTION DO NOT dispose of Battery Modules in a fire because the modules may explode.
DO NOT open or mutilate batteries; released electrolyte is harmful to skin and eyes and may be toxic.
A battery can present a risk of electrical shock and high short-circuit current. The following precautions should be observed when working on batteries:
Lead-acid batteries contain hazardous toxic materials. Handle, transport and recycle in accordance with local regulations.
This UPS is designed for use on a properly grounded (earthed), 208/240 VAC, 60 Hz supply and is to be installed by qualified personnel.
Electromagnetic Compatibility—The Nfinity™ UPS complies with the limits for a Class A digital device, pursuant to Part 15 of FCC rules. These limits provide reasonable protection against harmful interference in a commercial environment. This device generates, uses and radiates radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operating this device in a residential area is likely to cause harmful interference which users must correct at their own expense.
Operate the UPS in an indoor environment only in an ambient temperature range of 32°F to +104°F (0°C to +40°C). Install it in a clean environment, free from conductive contaminates, moisture, flam- mable liquids, gases and corrosive substances.
Turn the UPS off and isolate the UPS before cleaning. Use only a soft cloth, never liquid or aerosol cleaners. Keep the front and rear vents free of dust accumulation that could restrict airflow.
Never block or insert any object into the ventilation holes or other openings.
This UPS contains user replaceable modules. No attempts should be made to access the interior of any module. See 4.3 - Module Replacement.

Indicates caution followed by important instructions
AC input
AC output
Requests the user to consult the manual
Indicates the unit contains a valve-regulated lead acid battery
Recycle
DC voltage
Equipment grounding conductor
Bonded to ground
AC voltage
OFF
ON
Standby
No telecommunication connection
Locked position
Unlocked position
Contact closure signals
Serial communications

Congratulations on your purchase of Liebert’s Nfinity™ Uninterruptible Power System. As with every other Liebert product, we stand behind our quality. If you have any questions concerning this UPS, please feel free to contact your local dealer or Liebert representative or call the appropriate Technical Support number listed on the back of this manual.
To ensure proper installation and operation of this unit, please read this manual thoroughly.
For details on product warranty and registration, see 6.1 - Product Warranty Registration.
The Liebert Nfinity 12 to 20 kVA Power System is a modular UPS available in a 12 bay frame. It is intended for use with workstations, servers, network, telecom and other sensitive electronic equip- ment. It provides continuous, high-quality AC power to your equipment, protecting it from any power disturbance due to blackouts, brownouts, surges or noise interference.
The Nfinity modular UPS was designed to provide maximum system availability to business-critical equipment. Nfinity is also an easily adaptable UPS system. By simply installing additional Power or Battery Modules, you can expand your current system capacity or extend your backup runtime.
Nfinity has a comprehensive user interface that enables configuration according to the user’s prefer- ence. It also informs the user of details on the status of the UPS and keeps a log of events.
Introduction

User Interface Control Switch (SW2)


Manual Bypass Switch (SW1)
BACK VIEW with access plates removed
Refer to the table below for size and fully populated weight considerations.

BYPASS
EMI FILTER
POWER MODULE(S)
OUTPUT &
OUTPUT TRANSFORMER
BYPASS CONTACTOR
BATTERY MODULE(S)
SYSTEM CONTROL MODULE(S) CONTROL INTERFACE USER INTERFACE
POWER CONTROL
COMMUNICATIONS
Normal Mode
The Power Module rectifiers derive power from a utility AC source and supply regulated DC power to the inverter. The module’s inverter regenerates precise AC power to supply the connected equipment. The battery charger is in the Power Module and maintains a float-charge on the batteries.
When AC utility fails, the connected equipment is supplied power by the inverter, which obtains energy from the Battery Modules. The output power equipment will not be interrupted during the failure or restoration of the AC utility source.
After a power outage and complete battery discharge, and once AC utility is restored, the UPS will automatically restart and resume supplying power to connected equipment. This feature is enabled at the factory, but can be disabled by the user. The user can also program two auto restart delay settings:
The bypass provides an alternate path for power to the connected equipment and operates in the fol- lowing manner:
Introduction

Nfinity’s frame with bezels removed
The following is a general description of each compo- nent and its functions. Please review this section carefully, as it will give you a better understanding as to how the Nfinity operates.

The front of the Nfinity consists of a series of plastic bezels. By grasping these bezels from the left and right sides and pulling straight out, you can remove the bezel to reveal the Battery / Power Module bays. The bottom bezel covers the internal cooling fans and the manual bypass switch.
The User Interface Module is located above the Power / Battery Module bays for easy access. By mov- ing the User Interface and setting it on top of the frame, you will see the system control module bays.
The User Interface Module is the primary source of communication between the UPS and the user. From the interface, the user can:

For a more detailed explanation on how to operate the User Interface Module, see 3.1 - Controls and Indi- cators.
The System Control Module is the communications backbone of the UPS. It gathers input from all mod- ules and processes the data to control the operation of the system — including monitoring the condition of each module. An optional redundant System Control Module can be installed to provide full system func- tionality (operation and communication).

Under normal operation, the Status LED (green) will blink and the Fault LED (yellow) will be off. For any condition other than this, check 4.0 - Troubleshoot- ing.
Introduction · User Interface Module · System Control Module

Each power module is an independent 4 kVA, 2.8kW unit, consisting of a power factor corrected recti- fier, battery charger and inverter, with associated monitoring and control circuitry. The modules are paralleled to provide greater capacity and/or redundancy. Modules may be added or replaced on-line with no interruption or danger to the connected equipment.
Each battery module contains 10 individual 12-volt, 9 amp hour, valve-regulated (VRLA) battery blocks with associated monitoring and controls to isolate the Battery Module in the event of a battery failure. The modules are paralleled to provide greater capacity, backup time and/or redundancy. Mod- ules may be added or replaced on-line with no interruption or danger to the connected equipment, provided that the UPS is not operating on battery.
Power Module Battery Module

Under normal operation, the Green Status LED will blink continuously and the Yellow Fault LED will be off. For any condition other than this, check 4.0 - Troubleshooting.
Introduction · Shipping screws

Upon receiving the UPS, examine the packaging for any signs of mishandling or damage. If any dam- age is noted, call your local dealer or Liebert representative and/or notify your carrier.
The tools below are required to properly set up your UPS:

When deciding where to locate your UPS, consider the weight and size of the unit. Make sure that the structural integrity of the floor can withstand the weight of a fully loaded unit.
Check to make sure that your UPS will be located in a well-ventilated area with at least 12 inches (305mm) behind it. The UPS is air-cooled utilizing internal fans. Air is drawn into the front of the UPS and is exhausted through ventilation grilles in the back. It should also have at least 36 inches (915mm) in front in order to change modules when necessary.
The unit frame is bolted to the shipping pallet to ensure safety. It is recommended that a pallet jack be used to transport the unit to its operating location (prior to unbolting the unit).
Installation · 12" (305mm) · 36" (915 mm)

! CAUTION 2. Remove the metal ramp from the bottom of the UPS. This UPS is very heavy (see weight in Table 1). At least two people should assist in unloading it from the pallet.
Pull ramp out from under front of unit, then turn ramp over

Installation


Additional stability can be added by bolting the mounting brackets (used in shipping) to the floor, as shown below left.
Shipping Brackets Used for Stationary Mounting
Optional Stationary Mounting Dimensions

4.75" (120mm)
4.75" (120mm)
5/16" (7.94mm) diameter - in six places
For greater stability, use a higher-grade bolt. Refer to the dimensions above right when drilling holes for stationary mounting.

Customer-Provided Overcurrent Protection
! WARNING Please read this section thoroughly before attempting to install wiring to this unit.
A branch rated overcurrent protection device (cir- cuit breaker or fused disconnect switch) must be installed for the AC input.
If the start-up is on bypass, the UPS has a six- cycle inrush current that is up to 20 times the rated output current. This must be taken into account when selecting the overload protection device at the AC input supply distribution point. To avoid random tripping on start-up, it is recom- mended that the AC input supply be protected with a circuit breaker capable of withstanding this initial inrush.
This UPS should be installed by a qualified / certified electrician.

On the back of the UPS, cover plates are over the input and output terminals, as shown at right. Keep screws and plates to one side.
This UPS is fitted with EMI suppression filters. Earth leakage current is less than 40mA. Tran- sient and steady state earth leakage currents may occur when starting the equipment. This should be taken into account when selecting ground cur- rent detection devices, as the earth leakage cur- rents of both the UPS and load will be carried.
Input and output cables must be run in separate conduits.
The UPS voltage is factory-set to 208 V. Should the user have a utility supply of 240 V, the bypass voltage jumper will have to be changed to ensure correct output voltage. After selection, retorque jumper screws to 28 in-lb.

Installation

To connect the input wiring, follow these steps:
1. Locate the input wiring access, remove the knockout and pull the three input wires through it, allowing some slack for installation. 2. Secure the conduit to the rear panel of the UPS. 3. Input Power cables connect to screw terminals on the Input Terminal Block located to the right of the Bypass Voltage Terminal. Connect the wires to the block connections as shown below. Using a torque wrench, turn the screws clockwise until tightened to the proper torque value (28 in-lb). Insert the ground wire through the grounding lug and tighten it to the proper torque value (120 in-lb).



Grounding Conductor Installation
An insulated grounding conductor must be identical or larger in size, insulation material, and thickness as the grounded and ungrounded branch circuit supply conductors. This cable must be green with or without one or more yellow stripes and is to be installed as part of the branch circuit that supplies the unit or system.
The grounding conductor is to be grounded to earth at the service equipment or, if supplied by a separately derived sys- tem, at the supply transformer or generator set.
Output wiring may be configured one of two different ways (240/120 or 208/120). Refer to the chart below and the diagram at right when configuring the out- put wiring.


Voltage 120 208 240
Between terminals 1 & 4 3 & 4 2 & 3 1 & 3
Use only the connections listed above. Other connections will produce nonstandard voltages.
Installation

The following instructions are also shipped attached to the rear of the unit.
Stand-alone UPS or UPS equipped with a Maintenance Bypass Cabinet (Without Transformer)

12kVA 53 amps 75 amps 46 amps 75 amps
16kVA 70 amps 100 amps 62 amps 100 amps
20kVA 102 amps 125 amps* 88 amps 125 amps*
Single Input Feed: All UPS ratings must use 125A input circuit breaker protection. Dual Input Feed: See table below.

12kVA 53 amps 75 amps 46 amps 75 amps 125 amps*
16kVA 70 amps 100 amps 62 amps 100 amps 125 amps*
20kVA 102 amps 125 amps* 88 amps 125 amps* 125 amps*

Installation

UPS Output Terminal Block (TB3) Connection to External Panel Boards
208 VAC If connected equipment operates at 208VAC only, use a single-phase panel board connected to the UPS as follows.

UPS Output TB3 Panel Board Input
Max output current = 96A
GEC
Grounding Electrode Conductor (Field connection must be made)
Grounding Electrode Conductor (Field connection must be made)
208 VAC and 120 VAC If connected equipment is a combination of 208 VAC and 120 VAC, use a three-phase panel board connected to the UPS as follows.
UPS Output TB3 Panel Board Input
120 N
GEC
Grounding Electrode Conductor (Field connection must be made)
208 VAC also available as shown connected in Setup 1
Grounding Electrode Conductor (Field connection must be made)
240VAC and/or 120VAC If connected equipment operates at 240VAC only or 120VAC only or is a combination of both, use a single-phase panel board connected to the UPS as follows.

Max output current = 83A
UPS Output TB3 Panel Board Input
120 VAC also available as shown connected in Setup 2
GEC
5 GEC
Grounding Electrode Conductor (Field connection must be made)
Grounding Electrode Conductor (Field connection must be made)

The Nfinity is equipped with a Remote Emergency Power Off (REPO) connection.

Hanger for cable-tie to strain relief REPO wiring
REPO switch on rear of unit
REPO connections for normally closed switch system (fail-safe)

Key to REPO switch connections 1. 24 V DC, 50mA 2. Sense 3. Sense 4. Ground
! CAUTION To maintain safety, Signal Edge Low Voltage (SELV) barriers, and electromagnetic compatibility, signal cables should be segregated and run separately from power cables.

Nfinity is able to communicate through multiple communication ports simultaneously. Use only Liebert-provided communication cards. Connect only Signal Edge Low Voltage (SELV)/Class 2 cir- cuits when connecting to any communication port.



5 4 3 2 1
There are two DB-9 COM ports available on the rear of the Nfinity.
6 7 8 9
Relay contacts are available through a DB-9F communications connector. Contact closure provides the following:

4 UPS shutdown in battery mode (5-12 V DC for 1.5 sec)
These contacts are rated 48 VDC, 1 amp maximum and are compatible with Liebert MultiLink™ software.
Nfinity is able to communicate via Liebert proprietary protocol. This communication port can be used for serial communication with Liebert MultiLink software. For more detailed information, please see the MultiLink software documentation on the CD shipped with the Nfinity. The pin-out configuration of the DB-9 connector is:

The following communication cards may be used with Nfinity:
Installation · Pin Assignment

The User Interface Module informs you of the status of the UPS and lets you configure the UPS to your own needs or preferences.
The module consists of a series of Status LEDs, an LCD display window (four lines of 20 characters each), and buttons for navigation, as displayed below.

Refer to the legend below to properly navigate the Nfinity User Interface.
Refer to the legend below to indicate occurrence when an LED is lit.
Solid - A UPS fault condition has occurred. Fault/Warning
Flashing - A Warning has occurred. Consult event log.
On Bypass - The Bypass is supplying the power.
Inverter On - The inverter is supplying the power.
On Battery - Battery is supplying power to the inverter.
AC Output - Power is available to supply the load.


To review or change any settings on the UPS, use the buttons on the User Interface shown at left. Because some menus contain more than four rows of information, you may see an arrow on the display pointing up or down (as shown below)—indicating to scroll using the
or buttons.
If you are scrolling through any of the Main Menus, items will scroll one line at a time with the menu heading on the top line:
UPS is On, Utility is Good and Output is Off

UPS is On, Utility is Good and Output is On (Normal Operation)
UPS is On, Utility is Bad and Output is On (On Battery Operation)
UPS is On, Utility is Bad and Output is Off
UPS is in Manual Bypass Operation with Utility Out of Bypass Operation Range

To manually transfer the UPS to bypass, move the manual bypass switch to the bypass position. The manual bypass switch is behind the front bottom bezel. To transfer the UPS from bypass to normal mode, follow the on- screen instructions.
Follow these steps to start up the UPS.

Transfer to Bypass Press for bypass Press ESC to cancel
On Mains/Utility Output % = xx Battery Minutes yyy Press for menu
Once is pressed, the bypass alarm will annunciate and cannot be canceled until the manual bypass switch is operated.

Use the following procedure to power down the UPS.
To transfer the UPS from bypass to normal mode, simply operate the manual bypass switch back to the UPS position.
On return from bypass, the following screen will be displayed.
No active alarms See Event Log
Assert manual bypass

After initialization, the button will take you to the Main Menu. From here you may check on the status of the UPS, review the event log and active alarms, configure your UPS and even receive instructions on replacing modules. The Main Menu is divided into eight sub-menus as shown below:

UPS Configuration Display Date/Time Event Log Active Alarms Transfer to Bypass Module Replacement Service Tools
Present Load Redundant Status Battery Status Volts/Amps/kVA UPS Frequency Bypass Information UPS Information Module Information
Ctrl w/ Redundant Ctrl w/o Redundant Pwr w/ Redundant Pwr w/o Redundant Battery Module
Active Alarms Active Alarms Message UPS Configuration UPS Configuration
UPS Test Clear Failures BM Cell Replacement Reset Battery Stats Reset Bypass Stats
Transfer to Bypass Press for bypass Press ESC to cancel
Use the and buttons to select the desired menu item and press to access the appropriate submenu.

From the Main Menu the user may select UPS Status and press . Once at the UPS Status Screen, the user may access any information on the present condition of the UPS. Note the chart below when reviewing the UPS.
UPS Configuration Display Date/Time Event Log Active Alarms Transfer to Bypass Module Replacement Service Tools
UPS Status UPS Status
Present Load Redundant Status Battery Status Volts/Amps/kVA UPS Frequency Bypass Information UPS Information Module Information
UPS Status menu options
Volts/Amps/kVA Input Output xxx VAC xxx VAC xxx A xxx A xx.x kVA xx.x kVA
Redundant Status Redundant Status PMs Installed xx PM:N+1 redundant/non-redundant SC:Redundant/(non-redundant)
UPS Frequency UPS Frequency Input Hz: xx.x Output Hz: xx.x
Bypass Information Bypass Reasons Manual-User x Overload x Other x
Battery Status Battery Status Voltage (VDC) xxx Capacity % xxx Status: charging BMs Installed xx Ext batt present: No Discharge count: xxxx Batt Usage Hr: xxxx.x
UPS Information UPS Information UPS ID: xxxxxxxxxxxx xxxxxxxxxxxxxxxxxxx
Bays=x,XFMR=x Defaults = xxxV/xxHz Limit/Cnfg=xxxkVA/1x1 Model ID=x

Review Settings
Follow this procedure to review your UPS configuration settings. Follow the menus below by pressing
and to review the settings.

Display Date/Time Event Log Active Alarms Transfer to Bypass Module Replacement Service Tools
Review Settings Voltage Frequency Battery Alarm Service Contact Auto Restart UPS Shutdown Delay Remote Shutdown External Battery Bypass Alarm Mode Intelli-Battery Ca. Air Filter Reminder Guarantee Shutdown
Review Settings menu options

External Battery External batt config Amp.Hr 0000 Charge (A) 00.0
Frequency Frequency Settings Frequency Hz: 60 Sync Range Hz: +/- 5.0 Slew Range Hz/S: 3.0
Battery Battery Settings Test intrvl weeks: 2 on Wed 06:00 Low Batt Warn:2 min
Air Filter Reminder Air Filter Reminder Mode: 26 weeks

Change Configuration Settings - Change Settings Menu Starting from the Main Menu, locate and press UPS Configuration. From the UPS Configuration screen, select the Change Settings option. You may configure Nfinity from a large variety of selec- tions. Items indicated by an asterisk (*) are the selected settings.
UPS Status > UPS Configuration
Display Date/Time Event Log Active Alarms Transfer to Bypass Module Replacement Service Tools
UPS Configuration UPS Configuration
Review Settings > Change Settings
Change Settings Input Voltage Display Voltage Frequency Sync Range Frequency Slew Rate Set Password Auto Battery Test Low Battery Warning Auto Restart User Settings Set Date/Time Max Load Alarm Set UPS Shutdown Delay Redund Alarm Set Service Contact Remote Shutdown External Battery Bypass Alarm Mode Intelli-Batt Ca. Air Filter Reminder Guarantee Shutdown Line Compensation Factory Defaults
Input Voltage: Select the required input voltage set- ting. This voltage must match the bypass voltage jumper setting.
Frequency Slew Rate: Sets the rate of change of frequency through the sync range window.
Input Voltage * 208/120 240/120
0.5 Hz 1.0 Hz 2.0 Hz 3.0 Hz 4.0 Hz * 5.0 Hz
Display Voltage: Displays the actual voltage the unit is configured for.
Set Password: Set a Password to prevent unautho- rized users from changing the configuration of the Nfinity. It can be up to seven characters in length. Once set, the password will be required to change the configuration.
Frequency Sync Range: Sets the window to which the system synchronizes to the input supply.
0.5 Hz 1.0 Hz 2.0 Hz 3.0 Hz 4.0 Hz * 5.0 Hz

Auto Battery Test: Configure when and how often the Nfinity’s automatic battery test will run. This test is designed to ensure battery system integrity and provide early warning of problems.
Auto Restart: Automatically restarts once both delay parameters (battery capacity percentage and countdown timer) are met.

Mode Auto restart batt % Auto restart delay
Auto Restart Mode Auto Restart Mode * Enable Disable
1 week * 2 weeks 3 weeks 4 weeks 6 weeks Disabled
Auto Restart Batt % Auto Restart Batt % * 0% 10% 25% 40% 60% 80%
Start Day Batt Test Weekday SUN MON TUE WED THU FRI SAT
Auto Restart Delay Auto Restart Delay in 10-second increments,
User Settings: You may adjust the contrast of the user interface LCD or select the appropriate lan- guage.
Low Battery Warning: Notifies user how much run time is available. Can be set from 1 to 30 minutes.
Screen Contrast Display Language
Low Battery Warning 02 Minutes
Screen Contrast Screen Contrast
Press to increase Press to decrease
Display Language Display Language
English Francais Italiano Deutsch Espanol
Auto Restart · x0 sec · User Settings

Set Date/Time: Allows user to enable/disable DST (Daylight Saving Time), change the Day, Date and Time setting on Nfinity. When enabled, the time will automatically adjust to Daylight Saving Time.
Service Contact: Set a contact for the user to reach if problems occur.
Service Contact >Company Name
DST Mode Set Time/Date
DST Mode DST Mode
LIEBERT CORP.
Phone Number Phone Number
MM/DD/YYYY HH:MM:SS
Remote Shutdown: Enables / Disables the Remote Communications Shutdown.
Max Load Alarm Set: Allows an alarm to set when Nfinity’s load reaches a specific level.
If you are using MultiLink™ software, this parameter should be enabled in order for the UPS output to be turned off once the operating system has been shut- down.
Max Load Alarm Set
Remote Shutdn * Enable Disable
Alarm Mode Max Load Alarm Mode * Enable Disable
External Battery: Sets total amp-hour for external batteries to provide a more accurate runtime remain- ing value on the LCD display and through communi- cations.
Threshold Max Load Alarm Set Threshold kVA = xx.x
Amp-hour > Charge Current
UPS Shutdown Delay: Delays UPS shutdown for specified amount of time after receiving shutdown command via relay contacts only.
External Batt Config Enter total amp-hour
UPS Shutdown Delay xxx seconds
External Batt Config Enter charge current
Redundant Alarm Set: Sets Alarm to notify user when redundancy is no longer available.
Redundant PWR Alarm Set
When using the Non-Modular External Battery Cabinets with Chargers (P/N: PB10SLF105WC120), enter the following:


Bypass Alarm Mode: Allows the user to enable/dis- able alarm, indicating that the bypass is not quali- fied.
Guarantee Shutdown: Allows the user to guarantee a shutdown after a low battery warning is announced, even if the utility becomes qualified.
Bypass Alarm Mode > Enable
Intelli-Battery Ca.: Allows the user to enter the quantity of intelligent battery cabinets installed.
Line Compensation: Allows the user to control the amount of line drop compensation to be applied to the nominal output voltage. Line drop compensation is intended to compensate for any IR drop that may occur when the UPS is a significant distance from the protected load.
Enter Intelli- Battery cabinet count
Air Filter Reminder: Allows the user to set a warn- ing reminder to check the air filters.
Increase Decrease ESC to cancel
to Accept & Exit
2 weeks 4 weeks 10 weeks 26 weeks 52 weeks * Disable
Factory Defaults: Allows the user to reset all set- tings to the values in effect when the UPS was shipped from the factory.
Load Factory Default Are you sure? Press for yes Press ESC for no

Service Mode contains site identification information about the UPS system. The data is entered by Liebert Global Services (LGS). To view the data, go to the Main Menu, select UPS Configuration and press . Next, select Service Mode and press .
Set Site ID: Press to return to the Service Mode menu. Scroll to Set Site ID and press to display the screen shown below.
ESC

Display Date/Time Event Log Active Alarms Transfer to Bypass Module Replacement Service Tools
Set Tag Number Set UPS ID
Set Site ID -
Set Tag Number: Press to return to the Service Mode menu. Scroll to Set Tag Number and press to display the screen shown below.
Service Mode Service Mode

Set UPS ID: Press to return to the Service Mode menu. Scroll to Set UPS ID and press to display the screen shown below.
Service Mode Service Mode
Set Site ID Set Tag Number > Set UPS ID
This feature shows the current date and time. At the Main Menu, select UPS Configuration and press . Next, select Display Date/Time and press .

Event Log Active Alarms Transfer to Bypass Module Replacement Service Tools
Set UPS ID

3.5.5 Active Alarms
Accessing the Event Log enables the user to scroll through the Nfinity’s past 255 occur- rences. To open the Event Log, start at the Main Menu, select Event Log and press .
Alarms affecting the Nfinity can be viewed at the Active Alarms screen. To access the screen, go to the Main Menu, select Active Alarms and press .
Main Menu
UPS Status UPS Configuration Display Date/Time > Event Log
UPS Status UPS Configuration Display Date/Time Event Log > Active Alarms
Active Alarms Transfer to Bypass Module Replacement Service Tools
Transfer to Bypass Module Replacement Service Tools
Active Alarms Active Alarms Message
When an alarm sounds, the User Interface LCD will display a general explanation as to what the alarm is indicating. To view these messages in chronological order, press the and buttons.
Press the and buttons to scroll through the Nfinity’s Event Log in chronological order. The Event Log contains the following infor- mation.
Event Number Reference Code
Event 031/255 NC09 Power module warning S/N:0012200001002G1 19 MAY 2000 16:54:27
Event Detail or Serial Number Date of Event
Press to go back to the Main Menu.
3.5.6 Transfer to Bypass
The typical event log screen will display the event number and reference code on the first line. The purpose of this code is to assist fac- tory trained service personnel in trouble- shooting. Please make a note of the code number when contacting technical support. The second line contains the event descrip- tion. The third line will have either more detail about the event, a serial number indi- cating as to which module the event occurred, or be left blank. The last line will show the date and time the event occurred.
In the event of a UPS overload or failure, the UPS will transfer to bypass via its automatic bypass switch.
UPS Status UPS Configuration Display Date/Time Event Log Active Alarms > Transfer to Bypass
Module Replacement Service Tools
Press to go back to the Main Menu.
When an event or alarm occurs, the User Interface LCD will display the last message regardless of the default screen. See 4.1 - Active Alarms for a list of events and alarms and possible solutions. If you are unsure of the corrective action to take, contact a Liebert representative at the number listed on the back of this manual.
Transfer to Bypass Press for bypass Press ESC to cancel
Description · Time of Event

The user interface also supplies instructions for removing and replacing modules. From the Main Menu, access the module replacement screen and select the type of module. Refer to the screens below:
UPS Status UPS Configuration Display Date/Time Event Log Active Alarms Transfer to Bypass > Module Replacement
Ctrl w/o Redundant Pwr w/ Redundant Pwr w/o Redundant Battery Module
Module Replacement menu options
Control Module w/ Redundant Cntl Mod Replacement 1. Lift off display panel and place on top of UPS 2. Locate amber LED 3. Open lever 4. Loosen fastener 5. Replace module 6. Tighten fastener 7. Close lever 8. Replace display
Power Module w/ Redundant Pwr Mod Replacement 1. Remove all front bezels 2. Locate amber LED 3. Open lever 4. Loosen fastener 5. Replace module 6. Tighten fastener 7. Close lever 8. Replace all bezels
Battery Module Battery Module 1. Remove all front bezels 2. Locate amber LED 3. Loosen fastener 4. Replace module 5. Tighten fastener 6. Replace all bezels
Control Module w/o Redundant Cntl Mod Replacement 1. Remove bottom bezel and place UPS in bypass 2. Lift off display panel and place on top of UPS 3. Locate amber LED 4. Open lever 5. Loosen fastener 6. Replace module 7. Tighten fastener 8. Close lever 9. Wait for amber LED to stop flashing. 10.Replace display 11.Switch bypass to return to UPS operation 12.Replace bezel
Power Module w/o Redundant Pwr Mod Replacement 1. Remove bottom bezel and place UPS in bypass 2. Remove remaining front bezels 3. Locate amber LED 4. Open lever 5. Loosen fastener 6. Replace module 7. Tighten fastener 8. Close lever 9. Wait for amber LED to stop flashing. 10.Switch bypass to return to UPS operation 11.Replace all bezels
For more details on module replacement, consult 4.0 - Troubleshooting.
Service Tools

The Service Tools option is intended for use by Liebert Global Services engineers or Liebert-trained engineers to carry out certain tests and clear failures. These are advanced menus, entering changes may adversely affect UPS operation. From the Main Menu, shown below left, select Service Tools and press .
BM Cell Replacement: Allows a Liebert-trained engineer to reset the battery module (BM) energy val- ues to defaults after replacing battery cells within the module.
UPS Status UPS Configuration Display Date/Time Event Log Active Alarms Transfer to Bypass Module Replacement > Service Tools
Service Tools Service Tools

Clear Failures BM Cell Replacement Reset Battery Stats Reset Bypass Stats
UPS Test: Allows a Liebert-trained engineer to test the Batteries, LEDs or LCD.
Reset Battery Stats: Allows a Liebert-trained engi- neer to reset all battery statistics. These statistics include battery usage and discharge count.

Service Tools Service Tools
Clear Failures BM Cell Replacement Reset Battery Stats Reset Bypass Stats

UPS Test Clear Failures BM Cell Replacement > Reset Battery Stats
Clear Failures: Allows a Liebert-trained engineer to reset the UPS after a Battery Module failure alarm.
Reset Bypass Stats: Allows a Liebert-trained engi- neer to reset all bypass statistics. These statistics include manual bypass count, bypass overload count and other bypass count.
Service Tools Service Tools

BM Cell Replacement Reset Battery Stats Reset Bypass Stats
Service Tools Service Tools

UPS Test Clear Failures BM Cell Replacement Reset Battery Stats > Reset Bypass Stats

In the event of an alarm, the User Interface LCD will display the last message regardless of the default screen. A list of possible alarm messages is displayed below. If you encounter one of these or other alarm messages and are unsure of the corrective action to take, please contact a qualified Lie- bert representative at the number listed on the back of this manual.
User Interface Text Cause Action
Main Control Failure The Nfinity system has detected a System Control Module failure.
Identify and replace the failed System Control Module or contact Liebert Global Services for support.
Power Module Fail The Nfinity system has detected a Power Module failure.
Identify and replace the failed Power Module or contact Liebert Global Services for support.
Battery Module Fail The Nfinity system has detected a Battery Module failure.
Identify and replace the failed Battery Module or contact Liebert Global Services for support.
Redun. Control Fail The Nfinity system has detected a System Control Module failure.
Identify and replace the failed System Control Module or contact Liebert Global Services for support.
Battery Card Failure The Nfinity system has detected an Intellislot Battery Card failure.
Identify and replace the failed Intellislot Battery Card or contact Liebert Global Services for support.
UPS On Battery The Nfinity is drawing power from the batteries, not from utility.
Verify input breaker is closed. Verify input voltage is present and correct voltage. Verify input frequency is correct.
The fan filter reminder time has elapsed. Check and clean the fan filter and acknowledge the alarm. This alarm may be disabled or the interval between these alarms can be configured via the User Interface.
Short Circuit Recovery - Please
User tried to turn the output on following a short circuit on the output without waiting for the required 30 seconds to expire.
Wait for at least 30 seconds and then turn the output on.
Power Module N+1 Redundancy Alarm
Number of power modules is not adequate to provide power redundancy.
Reduce the UPS’s load, add power modules to the frame or disable the alarm feature via the User Interface.
Output Off - Output
A short circuit was detected on the output. Correct short (or extreme overload condition) and turn on the UPS’s output.
The load on the Nfinity exceeded the capacity of the active power modules.
Reduce the UPS’s load or add power modules.
Output exceeds max load setting
This will occur if the max load alarm is enabled, and the measured load at the UPS’s output is greater than the value set.
Reduce the UPS’s load, increase the Maximum Load Alarm limit via configuration or disable the Maximum Load Alarm limit via configuration.
Normally a severe overload will cause the unit to go to automatic bypass. This event informs the user that bypass was not qualified so the unit dropped the load to protect itself.
Reduce the UPS’s output load and verify that the UPS’s bypass source is qualified (amplitude and frequency). Verify that the configuration voltage and frequency settings are properly selected.
Switch To Manual Bypass
The Nfinity is on automatic bypass. Manual bypass switch should be activated before servicing.
Transfer Nfinity to manual bypass and call Liebert service for assistance.
Load Exceeds Battery Module
The measured load on the output will cause the battery modules to exceed their limits if the UPS transfers to battery mode.
Reduce the UPS’s load or add battery capacity. If external non-modular battery cabinet(s) are added, verify that the UPS’s configuration is set to match the external battery amp-hour rating and charger rating.
The input voltage is not within the specified voltage or frequency range so the UPS will not allow an automatic or manual transfer to bypass.
Verify UPS’s configuration for voltage and frequency. Check UPS’s input breaker; disable this alarm if desired via configuration.
Load is greater then the rated frame limit. Reduce the UPS’s load.

User Interface Text Cause Action
A user-initiated transfer to bypass will assert this alarm, instructing the user to enable the manual bypass switch. Once the manual bypass is asserted, the alarm will clear. This is a non-mutable alarm.
Engage the manual bypass switch (located at the bottom front on the left hand corner of the unit). Once engaged, the switch may be de-asserted to return to normal operation.
The most likely cause is that the incorrect cable has been connected to the COM port between the UPS and the host.
Check for a wiring problem to the Shutdown On Battery at the COM1 connector. If this problem is not addressed, the unit will shut down shortly after switching to battery operation.
on COM port 1
Battery Test Weak Battery
The battery was determined to be weak as a result of the battery test.
Depending on the age of the batteries, it may be appropriate to replace all batteries in the system. Schedule a battery test so that the system operation is double-checked once the batteries become fully charged.
Replace the battery modules that have active failures/ warnings. Depending on the age of the batteries, it may be appropriate to replace all batteries in the system. Schedule a battery test so that the system operation is double-checked once the batteries become fully charged.
This is intended to detect a situation where a Modular battery cabinet has been connected for communication, but the power busses are not connected.
Check that the Modular Battery breaker is closed. Verify proper connections between UPS and Modular Battery Cabinet.
Don’t Remove SC The only good System Control Module lock lever was raised with the output on and the unit is not on bypass.
The System Controller detected a failure. Select manual bypass so that the unit can be serviced.
Transfer UPS to manual bypass and contact Liebert Global Services.
Output Off - bypass unavailable
This event informs the user that bypass was not qualified so the unit dropped the load to protect itself.
Verify that the UPS’s bypass source is qualified (amplitude and frequency). Verify that the configuration voltage and frequency settings are properly selected.
REPO switch was pressed. If REPO wasn’t pressed, check for REPO wiring problems.
External Battery Module Warning
The energy delivered from the Non- Modular battery did not meet programmed battery capacity.
Verify proper connections between UPS and Non-Modular Battery Cabinet. Reenter the amp-hour rating for the external battery (set the amp-hour entry to zero and press the return key, then reset it to the appropriate value for the external battery). If the problem persists, the external battery should be replaced.
A battery module is not ready. In most cases, one or more battery modules should indicate a warning/failure condition.
Ensure that the battery module is fully seated and the 1/4 turn fastener is engaged. If the problem persists, replace the battery module with warning/failure condition indicated at the User Interface. If no User Interface warning/failure of battery module, look for the battery module with LEDs indicating a problem and replace that unit.
A power module is not ready. In most cases, one or more power modules should indicate a warning or failure condition.
Ensure that the power module is fully seated and the 1/4 turn fastener is engaged. If the problem persists, replace the power module with warning/failure condition indicated at the User Interface. If no User Interface warning/failure of power module, look for the power module with LEDs indicating a problem and replace that unit.

Every Battery, Power and Control Module features two LEDs to help inform the user of the module status, as shown below left. Refer to Table 2 for details.
Green Status LED Yellow Fault LED

OFF OFF Module not inserted into frame. System is OFF.

Green Status LED Yellow Fault LED
Module is in start-up qualification mode or module warning. **
OFF FLASHING Abnormal operation, re-insert module. If this persists, contact Liebert Global Services at 1-800-543-2378.
* If this persists for more than 30 seconds, check to verify the lever is in the down position, otherwise the module is faulty. ** If both green and yellow LEDs are flashing for more than 30 seconds, then reinsert module.
Troubleshooting · Green Status LED · Yellow Fault LED

MODULE REMOVAL (Steps 4a-c)
Follow the instructions below when replacing or adding a Control, Battery or Power Module to the system.

To order additional modules, contact your Liebert representative or call 1-800-LIEBERT.
4.3.1 Removing Modules 1. Remove bezel cover of appropriate module. When replacing a Power or Battery Module, verify the faulty module by confirming the yellow LED is lit. 2. If removing a Control or Power Module with no redundant modules, switch UPS to manual bypass. 3. Pull out and lift the lever if replacing a Control or Power Module, then turn fastener counterclockwise until it is loosened.

Lift lever up (for Control and Power Modules)
! CAUTION Battery Modules are heavy—66 lb (30 kg).
b. Slide module away from the center of the UPS (shown above right, center). c. Continue to pull until module is removed (shown above right, bottom). 5. Dispose of module in an environmentally responsible way that complies with local codes/regulations or return to Liebert for proper disposal.

POTENTIAL TIP HAZARD Install all battery modules starting from the bottom. For module removal, start from the top. Do not remove more than one module at a time. Failure to do so may cause unit to tip over and cause serious injury.
Troubleshooting · Turn fastener counterclockwise

1. Lift module to appropriate bay, resting end of module on bay shelf. Use caution not to rest the module on the lower bezel cover. 2. Push module into bay. Once halfway in, slide module sideways toward the center of the UPS. Continue pushing module until fully inserted. 3. Press and turn fastener clockwise until locked. If replacing a Control or Power Module, press lever down. 4. Wait about 15 seconds as the module performs a start-up test and synchronizes with the other modules. Both the yellow and green LEDs should be flashing. A green flashing LED will then confirm the module is properly installed. 5. If UPS was placed in bypass manually, transfer back to UPS operation. 6. Replace bezels.

Press lever down (for Control and Power Modules)
4.3.3 Replacing the User Interface 1. Lift off user interface and set it on top of the UPS frame. 2. The attached cable will be connected to an Intellislot card, found in a port between the control modules. 3. Remove the cable and the attached Intellislot card from the UPS. 4. Plug the new Intellislot card into the UPS. 5. Plug the new user interface cable into the Intellislot card. 6. Set replacement User Interface into proper position.

Troubleshooting · Turn fastener clockwise

Keeping your Liebert Nfinity UPS operating properly is imperative to optimal performance and life of the unit. It is recommended that a certified technician perform preventive and corrective mainte- nance. Liebert Global Services (LGS) is dedicated to ensuring the highest level of performance and unmatched support for your Nfinity UPS. Contact an LGS representative for service to guarantee maximum reliability and system availability.
It is recommended the following maintenance is performed at least monthly:
It is recommended the following maintenance is performed annually:
Nfinity’s intake fans contain filters that will need to be replaced or cleaned periodically, depending on the surrounding environment. Check by removing the bottom bezel and noting the condition of the two filters. If filters are dirty, replace them by removing the plastic cover over the filter frame and inserting a new filter in its place. Use caution when replacing filters when fans are running.

The fan filters are washable and can be reused. To wash filters, place them under running water (with the dirt side down) to remove dirt and dust. Blot dry with a towel and allow air-drying before reusing.
Maintenance

General & Environmental Units Configuration
Unit Rating kVA 12 16 20 20 kW 8.4 11.2 14 16 Conducted and Radiated EMC Levels FCC Part 15, Class A Compliant Safety Standards UL 1778; c-UL Compliant Immunity Standards IEEE C62.41, Category B Mechanical Units
20 (508) Depth 28 (711) Height 54 (1372) Environmental Units Operating Temperature (max) C (F) 0° - 40° (32° - 104°) Relative Humidity % 0-95% non-condensing Maximum operating altitude M (ft.) 3,000 (10,000) Nominal heat dissipation BTU/Hr 3,186 4,248 5,903 6,748 Acoustic noise level dBA
208VAC nominal: operating voltage range variable based on output loading percentages % UPS Load Input Voltage 80 – 100% 170 VAC 60 – 80% 144 VAC 30 – 60% 127 VAC 0 – 30% 110 VAC Power factor Cos ∅ >.98 Input frequency (nominal) Hz 60 Input frequency range Hz 40-70 Battery Module Units Number of lead acid batteries 10 Number of battery cells 60 Battery capacity A/hr 9 Autonomy time (full load) minutes 6 (With an equal number of Battery & Power Modules, in a non-redundant configuration) Maximum charge current (full load) A 3 Nominal Voltage VDC 120 Recharge Time Hrs Typically 6 (to 90% capacity) Output Data Units Output voltage VAC 208/120 or 240/120 Voltage regulation % ±3 Voltage stability (100% step load) % ±7 Recovery time msec 96
Voltage distortion %
Output overload capability %
If you have any questions, please contact us at:

Specifications



Nfinity ™ Power System
U SER M ANUAL
Technical Support/Service
Web Site www.liebert.com
With over a million installations around the globe, Liebert is the world leader in computer protection systems. Since its founding in 1965, Liebert has developed a complete range of support and protection systems for sensitive electronics:
Monitoring 800-222-5877 monitoring@liebert.com Outside the US: 614-841-6755
800-222-5877 upstech@liebert.com Outside the US: 614-841-6755
800-543-2378 powertech@liebert.com
Outside the United States
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
Italy Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) +39 049 9719 111 Fax: +39 049 5841 257
© 2003 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice.
® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
Asia 23F, Allied Kajima Bldg. 138 Gloucester Road Wanchai Hong Kong +852 2 572 2201 Fax: +852 2 831 0114
SL-23953 (9/08) Rev.3